Watt Buster Final Report
F-1
Appendix F: Summarized Commercial Data
This assessment was conducted using a combination of on-site visual inspections, conversations with
building maintenance personnel, and measurements from the BuildingAdvice system. Particular attention
was paid to obtaining accurate data. Due to potential changes in occupancy, operations, and variable
weather conditions, implementation of the proposed energy conservation measures does not guarantee a
reduction in energy usage.
1001 – Office
This is an office building originally built as a bank. The office configurations have changed many times
over the past 30+ years. These changes did not always take into account the original ducting,
temperature settings and facility control mechanisms. This is a government facility so funding for major
capital improvements needed depend on inclusion in annual budgets.
1002 – Office
This location is primarily office space, with a bank, restaurant, and small exercise room. This facility is an
example of excellent maintenance and some needed upgrades over the years. The building owners are
trying to determine what to do next. Among the options are more energy efficient control systems and
new elevators. A more efficient boiler was installed in the past year.
1003 – Office and Warehouse
This mail/cargo handling facility underwent a major lighting retrofit over the 2010 summer. The changes to
electricity consumption should be apparent in the winter months. The customer asked for tracking and
feedback over the next 6 months. Since it is a large facility and a time critical operation, any downtime
does not allow for complete or even partial shutdown of boilers during summer months. This customer
has chosen to maintain and rebuild large pieces of equipment rather than replacing. The lighting was an
obvious change with a quick payback period and could be done without impacting operations. Lighting is
a quarter to a third of the facility’s operating costs.
1004 - Office
This was the largest facility in the BEM project. It is an extremely well maintained building. Although it
became a government facility about ten years ago, it has retained a professional property management
team. The government made a decision to fund the maintenance to keep the integrity of a premier
building. Boilers have been replaced, HVAC and controls are monitored. The managers of this building
are very enthusiastic about being an ENERGY STAR building. They are already eligible; a few lighting
changes could get them to a score of 100. We will revisit the building in January.
1005 - Office
This building has not been maintained as well as other facilities its age. Things have been fixed and
upgraded on an as-needed basis. The one energy plus is installation of new boilers a year ago. The
building owner is considering selling it or doing a major overhaul if kept. The recommendations will be
followed if they decide to keep the facility.
1006 - Office
Built and maintained as an office condominium, this building presents additional challenges in the
decision making process. The condominium group had put aside funds, anticipating the need to upgrade
to more energy efficient building systems and common area changes. Individual office owners had
upgraded lighting but many T 12's tube lights needed conversion to T-8. The common areas had some
compact fluorescents but the tube lights need to be converted. At the time of our assessment, plans were
Watt Buster Final Report
F-2
being made to move ahead on HVAC and control upgrades. We were able to connect them to Otis for
information about an energy efficient elevator which uses one-third less energy.
1007 – Office & Warehouse
This customer's facilities include refrigeration for perishable cargo. All wiring for the main units and
refrigeration are buried underground which makes it difficult to access and assess. CCI believes that it
may be a major energy hog. The company is considering upgrades to more efficient systems on a
company-wide basis. They have a team designated to make green improvements to the facility.
1008 – 1009 - Schools
Anchorage School District facilities management had determined that these two school facilities are
energy hogs. 1009 had gone through an extensive upgrade so the low score was a disappointment. The
BEM pointed out two issues that could be resolved through communication and control adjustment –
lights had been left on and fans running 24/7. Funding to implement recommendations is based on bonds
requiring voter approval so it is difficult to strategically plan changes. The school district is pursuing grants
and opportunities to become more energy efficient.
1010 – Office, Small Industrial & Warehouse
This facility was one of the stars as the owner is very interested in energy efficiency as it impacts the
bottom line. The facility has undergone majority lighting retrofit in the past few years. The retrofit resulted
in a 22% reduction in utility costs and the investment was returned in less than one year. We continue to
work with the facility toward its goal to attain an ENERGY STAR rating of 100. Even more important to the
owner is to eliminate the electric demand charges by changing from a Large General Service customer to
a Small General Service customer. This customer believes the business model for improving the bottom
line goes hand-in-hand with improving the earth by being energy efficient.
Control Contractors conducted a blower test and found the building to be very well sealed, with little room
for improvement. Control Contractors is helping the customer look at changes in its equipment operation
to lower the demand levels. Once some of the older machines are retrofitted, this location is likely to
attain a 100 ENERGY STAR rating.
1011 – Office & Telecommunications
This facility is a wires center in the communication industry. As such, it has a very low worker census but
some very high tech computers and other equipment. It was difficult to identify potential for savings in
either efficiency or cost. The equipment requires a certain level of HVAC systems to maintain the
temperatures and humidity. In the current economy, making optimum use of the space is not an option.
The space configuration used previously by a much bigger workforce has been left as is. Energy
efficiency opportunities may be small and consist mostly of lighting changes. As with many of the
locations, the lights are retrofitted as ballasts go bad and retrofit becomes easy and low cost.
1012 – Retail & Mixed Use
This facility has eclectic uses – standard retail, office, theater, residential (one apartment) and audio-
visual center. The owner pays the electricity and gas for the entire building. The owner is aware the
HVAC and control systems need major overhaul. Short term fixes have been made to control
temperatures. In winter some of the retail tenants use space heaters most of the time they are open.
Control Contractors will be working with the owners to upgrade the control systems and HVAC which
should result in greater energy efficiency.
Watt Buster Final Report
F-3
1013 – Office & Radio Stations
The office areas of this building are pretty standard. The customers noted that the ambient light affects
their HVAC system. They are also dealing with two systems rather than one integrated system. They plan
to budget for some changes in 2011. The radio stations are an unusual addition and some run 24/7.
There are also problems with heat generated by the equipment. The customer will not be making
changes to the radio station areas but will check on the control side. This facility has the same problem as
90% of the facilities we monitored; i.e. changing walls and office configurations. Most buildings have gone
through several different types of tenants. This building was originally built as a Native Corporation
headquarters.
1014 – Retail/Supermarket
The high ENERGY STAR rating from this assessment was a surprise, as the walk-through and
discussions led us to expect a low rating. Most of the facility, originally a Safeway Store, is close to 40
years old. The equipment has been maintained but no major upgrades have been made. The refrigeration
both in the back area and the front are running well. Major changes could help reduce energy costs. The
local owners are sticking with the "if it isn't broke why fix it" attitude toward upgrades. Control Contractors
helped the customer resolve problems with the air handling system. The customer was most concerned
about ML&P billing for demand. The ML&P website has a good explanation of demand billing so that was
forwarded to the customer.
1015 – Office – Engineering
This building is looking at control issues, major renovations and updating of several floors. The building
has been well maintained and used as office space since first built. The space is used primarily for
engineering work so lighting is an issue. The customer is considering a lighting retrofit and has received
bids. If the lighting work is included in the budget, the customer would see energy reduction in 2011. The
customer has requested information on alternatives to the expensive seasonal affective disorder lights
that some workers have requested. The property manager informed us at the assessment meeting that
we had the wrong square footage. We ran the report again with the correct square footage which raised
their ENERGY STAR rating.
1016 – Office & Retail
The primary tenant sells electrical supplies and has a retail operation in addition to its sales department.
We found some immediate low-cost fixes such as replacing and moving thermostats. These would be the
responsibility of the tenants. The owners do not plan any major capital improvements. The lights have
been changed out to T-8s as they fail.
1017 - Office
These offices were originally built as office condominiums but have come under one owner in the past
few years. The building has a lot of cooling and heating problems. They recently replaced the boiler,
which presumably has corrected the excessive-heat/excessive-cold problem. This will be the first winter
for the new boilers. All the offices have very cut-up spaces so ventilation through the HVAC is proving
difficult. It was recommended they start with simple steps of checking controls, checking dampers and
thermostats. In the coming months, it will be interesting to see the impact of the major boiler change.
1018 – Office
This building has a good control system but the ducts and ventilation handling should be studied more.
The standard damper check should be done. The equipment for the most part is original equipment that
has been maintained. The recurring theme of offices being changed as the occupants have changed may
be a major culprit of uneven ventilation. Lighting retrofit, which the facility manager would like to see,
would yield some energy and cost savings. He felt that the results of our assessment may help him get
Watt Buster Final Report
F-4
the retrofit through for 2011. CCI has offered to run a cost analysis to determine approximate return on
investment.
1019 – Office
The facility manager needs some help in understanding its controls and dampers adjustment. The lease
is coming up for renewal so the discussion and assessment provided information for the owner to become
more energy efficient. All their lights were T-8s. The customer was very interested in power factor not for
this building but for the batch plants they own and operate. They also would like to discuss the total
electrical system for their primary facilities including the batch plant and asphalt plant. This education
opportunity will be done as soon as the construction season is completed.
1020 – Office
This building was probably the worst example of space changes due to movement of walls and cubicles .
It is fully occupied by one tenant, a state entity, which has had the property about one year. We met with
the owner's property manager. They are trying to assess what changes are needed. A lighting retrofit of
all the remaining T-12s is doable. A full assessment of controls and schedules for the controls will most
likely be undertaken. The timing of the assessment and the new owner should allow for some energy
efficiency improvements.
1021 – Office
This building is one of the older Class A spaces in town. Its ENERGY STAR score of 82 indicates the
building is well maintained and all the big fixes have been done, e.g. lighting retrofits. New energy
efficient boilers were installed in the past few years which has added to the total efficiency of the facility.
Easy ways for this building to boost its rating include careful study of dampers, control schedules and
elimination of space heaters in the offices. The building managers know that many space heaters are
being used in the building but cannot find a way to shut them down. This is a common problem in older
office spaces and differences in employees’ comfort levels.
1022 – Office & Warehouse
This facility is owned 49% by the employees, which adds an unusual element to perspectives about
energy savings. One employee-owner gave us the walk through and he felt strongly that saving energy
would result in more earnings for the employee shareholders. This is a huge facility that includes
administration, the sales staff and the warehouse. The administration employees had more complaints
about the temperatures. About 80% of the lights in the warehouse had been retrofitted. Some offices had
new lighting. Retrofitting the remaining lights would produce additional savings.
1023 – Office & Warehouse
This is the only facility where construction of an addition was about to begin and some ventilation issues
could be addressed as part of the work. There is obviously high humidity and condensation that have
affected the window sills and some of the office spaces. This facility is making use of space air
conditioners to combat the heat and humidity problems. The HVAC and control systems need overhaul.
The manager would like to see how the additional 3,000 square feet will impact energy consumption and
would budget for some changes. There is a fair amount of T-12 lighting that could be changed to T-8 for
some immediate impact on energy costs. Balancing the ventilation and the additional space may even out
the anticipated increase in energy costs.
1024 – Office & Printing Warehouse
This facility presents a puzzle. Its large warehouse space is a printing facility. A more detailed study is
needed of the printing equipment and its power draw. When the presses are running there is a huge heat
Watt Buster Final Report
F-5
factor. The building as a whole has been retrofitted and moved to CFLs where appropriate. The office
spaces have but are not using programmable thermostats. This building is an example of the problems
that arise from repeated reconfiguration of office space. Thermostats that control several offices were
moved as the offices were reconfigured and occupants didn’t know how to control them. It was an easy
fix, however, and the maintenance staff was able to resolve the problem. The facilities manager is
budgeting funds to implement many of the recommendations in the assessment. It will be interesting to
track their consumption in the next year.
1025 – Office and Warehouse w/refrigeration
This facility is a huge beverage distributor, with plans to expand its warehouse space in the next year.
Chugach previously conducted a lighting audit that recommended a total retrofit. The lighting in some key
areas was so low that many mistakes were made in order filling. The complete retrofit in the warehouse is
probably a major factor in its rating of 68. The changes in controls and ventilation would most likely bring
it up to an ENERGY STAR building. The manager has seen the evidence of lowering costs through
energy efficiency.
1026 – Office
This is one of the smallest facilities at 10,000 square feet. It was built originally as an office condo but the
developer/owner did not follow through with it as condominium space. The building is leased to a variety
of small businesses. This facility hit the magic number of 75 to be an ENERGY STAR building. The
heating and cooling for most of the building is balanced by the owner who also has his business in the
building. He does recognize how long it takes to cool his facility down by using the windows and air
conditioning fans at the right time. In the warm months, they shut off the boilers, and control heating and
cooling with sunlight and opening windows. A lighting retrofit could most likely bring the rating up.
1027 – Office & Warehouse
This is the star of the facilities we monitored with a 97 rating. It is only 7 years old so was built with some
thought to energy efficiencies. We did find a few items including one very low-cost: weather stripping a
high-traffic door with a 2-inch gap that lets in ice and snow. It has a heat balance problem with the
upstairs and the downstairs where the windows bring in lots of light and heat. Putting in another zone with
a separate thermostat could solve the problem. The warehouse lighting could be changed to high bay T-
5s. It could significantly reduce costs and require much less maintenance. They may want to look at an
analysis of return on investment. Ironically, they could have installed T-5s when the warehouse was built
but it was a newer technology at the time.
1028 – Office/High Electronic Usage
This government-owned building has a low score mostly because of what they can't do. It is a 24/7
operation with many computers and equipment that cannot be turned off. Because of the security level
they could not provide specific information. Since the original part of the facility was built in the 1960's
they have added on and changed configuration many times. The main energy efficiency change being
made is retrofitting lights as they burn out or the ballasts go bad. We have recommended they look at the
fans (HVAC) and thermostats, as well as controls. There were instances of two sides of a shared office
space having completely different air temperatures. It will be interesting to see how they deal with the
executive order that mandates energy efficiency changes by 2012.
1029 – Office
This building had 1-1/2 tenants in the facility during the monitoring. By the time the assessment was
done, the half tenant had moved out. The lower level is fully occupied and has a high level of computer
use. The facility manager and the building owner were very concerned about "dirty power" which was
mentioned by an ML&P crewman. Chugach checked the lines and the power. It all seemed to be a good
Watt Buster Final Report
F-6
secondary power coming into the entrance. The “dirty power” label may be referring to the potential for
surges, in light of the quantity of computers. Low-cost suggestions included getting a handle on controls
for the building, and checking ducts and dampers.
1030 – Office & Warehouse
This facility utilizes its space for offices, customer payment/service and a warehouse/garage for trucks.
CCI began working with them on controls and HVAC while we were in the middle of the BEM project. The
warehouse set up brings in a lot of outside air. The doors to the warehouse are continually open from
7:00 – 4:00 which can translate to excess ventilation. The facilities manager was concerned about CO2
but it did not show up at danger levels in the monitoring process. The manager plans to budget for system
improvements.
1031 – Office/ Athletic Club (Medical Facility Match)
ENERGY STAR did not have a category for an athletic club. CCI decided that it fit the parameters of a
medical facility because of the equipment. One part of the club was recently renovated as the premier
level for the club. This side has all energy efficient lighting and equipment. The other side of the facility is
much older and has a swimming pool as well. The boilers serve both sides of the building. The
temperature in the boiler room with all the pool pumps operating can be as high as 90-100 degrees. They
are looking into boiler replacements. Lights are being retrofitted to T8s as the T12s burn out. The new
boilers, if they move ahead, will definitely make a difference.
1032 – Lodge –no match in ENERGY STAR
This is the only facility considered rural and the only one that had no match in ENERGY STAR. The
BuildingAdvice system can do the report without the ENERGY STAR component. The other anomaly is
that this building is fueled by propane. The costs per square foot are extremely high. Temperature is
controlled by opening and shutting windows and doors. All possible lighting has been changed to T8s and
CFLs. The aesthetic qualities of certain fixtures prevent changing to energy efficient bulbs. This facility is
used from mid-May to mid-September but the administration and facilities shop are open year-round.