HomeMy WebLinkAboutFalse Pass Final Report Village End Use Effic Measures 2008 Village End Use Energy Efficiency Measures Program
AEA Grant # 2195225 Administered by Alaska Building Science Network
False Pass Final Report
Community Summary
11 community buildings received energy efficiency upgrades as follows:
City Office/Community Center, City Shop, Clinic, Library/Post Office, Old Generator building, Water Treatment
Plant , Tribal Office/Warehouse, Isanotski Corp Office & Triplex B&B, Grocery Store , Liquor Store, K-12 School
and Gymnasium.
Retrofits Completed: July 2007 - December 2008
Village-Wide Lighting Retrofit Summary:
• Retrofitted 275 light fixtures with electronic ballasts & T8 lamps
• Installed 71 compact fluorescent light bulbs
• Installed 8, T5 linear fluorescent fixtures in the School Gym
• Pre-retrofit energy use for all lighting: 36.964 Kilowatts
• Post-retrofit energy use for all lighting: 20.067 Kilowatts
• Energy savings projection: 16.897 Kilowatts
• Pre-retrofit to post retrofit energy reduction: 46%
• Estimated Annual Savings:
kWh Rate (as of Fall 2008): $0.65 Fuel Cost (FY 2007 Ave): $2.48
Comparative Comparative Hours Per Day/ Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs
Locally Estimated $19,154.19 2524.32 $6,260.31
4 Hours/day $11,033.70 1454.13 $3,606.24
7 Hours/day $19,309.00 2544.73 $6,310.93
10 Hours/day $27,584.30 3635.33 $9,015.61
• Total project cost for all measures: $37,775
• Simple Payback (lighting measures only, using 7 hours/day lighting use run-time): 1.96 years
• Total village wide in-kind contribution: $ 10,369 (extended grant capacity by 27.4 %)
2
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
City of False Pass Owned Buildings
John Shelikof and Siri Goullete
work on a fixture. Crab pots in storage.
John and Siri take a break after
completing lighting retrofits in the
community library.
6 buildings owned by the City of False Pass received energy efficient lighting upgrades as follows:
City Office/Community Center, City Shop, Clinic, Library/Post Office, Old Generator building, Water Treatment
Plant
• Lighting upgrades completed in November 2007
• Retrofitted 77 light fixtures with electronic ballasts & T8 lamps
• Installed 24 compact fluorescent light bulbs
• Pre-retrofit energy use for all lighting: 11.838 Kilowatts
• Post-retrofit energy use for all lighting: 6.389 Kilowatts
• Energy savings projection: 5.449 Kilowatts
• Pre-retrofit to post retrofit energy reduction: 46%
• Estimated Annual Savings:
Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided
250 Days Per Year Savings Use (gal) Diesel Costs
Locally Estimated $6,678.07 880.10 $2,182.65
4 Hours/day $3,558.20 468.93 $1,162.95
7 Hours/day $6,226.84 820.63 $2,035.17
10 Hours/day $8,895.49 1172.33 $2,907.38
3
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
City Office/Community Center
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 1 4-lamp electronic ballast, (4) 25 watt T8 lamps 17 CFL-14 W 7 • Pre-retrofit energy use: 2940 watts
• Post-retrofit energy use: 1675 watts
• Energy savings projection: 1265 watts
• Pre-retrofit to post retrofit energy reduction: 43%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 2000 Hours/year (Est.) $1,652.09 217.73 $539.97
4 Hours/day $826.05 108.86 $269.98
7 Hours/day $1,445.58 190.51 $472.47
10 Hours/day $2,065.11 272.16 $674.96
City Shop
Materials Installed Quantity 4-lamp electronic ballast, (4) 32 watt T8 lamps 3 CFL-23 W 7
• Pre-retrofit energy use: 1204 watts
• Post-retrofit energy use: 521 watts
• Energy savings projection: 683 watts
• Pre-retrofit to post retrofit energy reduction: 57%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 2150 Hours/year (Est.) $958.90 126.37 $313.40
4 Hours/day $446.00 58.78 $145.77
7 Hours/day $780.50 102.86 $255.10
10 Hours/day $1,115.00 146.94 $364.42
4
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Clinic
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 2 4-lamp electronic ballast, (4) 25 watt T8 lamps 18 CFL-14 W 2 CFL-20 W 3 • Pre-retrofit energy use: 3517 watts
• Post-retrofit energy use: 1802 watts
• Energy savings projection: 1715 watts
• Pre-retrofit to post retrofit energy reduction: 49%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs
2000 Hours/year (Est.) $2,239.79 295.18 $732.05
4 Hours/day $1,119.90 147.59 $366.02
7 Hours/day $1,959.82 258.28 $640.54
10 Hours/day $2,799.74 368.98 $915.06
Library/Post Office
Materials Installed Quantity
2-lamp electronic ballast, (2) 25 watt T8 lamps 7 4-lamp electronic ballast, (3) 25 watt T8 lamps 15 CFL-20 W 1 CFL-23 W 1 • Pre-retrofit energy use: 2824 watts
• Post-retrofit energy use: 1497 watts
• Energy savings projection: 1327 watts
• Pre-retrofit to post retrofit energy reduction: 47%
• Estimated annual savings: Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 2000 Hours/year (Est.) $1,733.06 228.40 $566.43
4 Hours/day $866.53 114.20 $283.22
7 Hours/day $1,516.43 199.85 $495.63
10 Hours/day $2,166.33 285.50 $708.04
Notes: Fifteen 4-lamp fixtures were de-lamped to three, 25-watt T-8 lamps each for additional savings.
5
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Old Generator Building
Materials Installed Quantity 2-lamp electronic ballast, (2) 32 watt T8 lamps 10 CFL-20 W 1 • Pre-retrofit energy use: 915 watts
• Post-retrofit energy use: 620 watts
• Energy savings projection: 295 watts
• Pre-retrofit to post retrofit energy reduction: 32%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 100 Hours/year (Est.) $19.26 2.54 $6.30
4 Hours/day $192.64 25.39 $62.96
7 Hours/day $337.11 44.43 $110.18
10 Hours/day $481.59 63.47 $157.40
Notes: these lights were changed to maintain consistency with updating lighting in other City buildings. Small
measurable savings is anticipated since lights are rarely on.
Water Treatment Plant
Materials Installed Quantity 2-lamp electronic ballast, (2) 32 watt T8 lamps 4 CFL-14 W 1 CFL-20 W 1
• Pre-retrofit energy use: 438 watts
• Post-retrofit energy use: 274 watts
• Energy savings projection: 164 watts
• Pre-retrofit to post retrofit energy reduction: 37%
• Estimated annual savings: Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 700 Hours/year (Est.) $74.96 9.88 $24.50
4 Hours/day $107.09 14.11 $35.00
7 Hours/day $187.41 24.70 $61.25
10 Hours/day $267.73 35.28 $87.50
6
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
False Pass Tribal Council Owned Buildings
Lighting supplies delivered to False
Pass.
1 building owned by the False Pass Tribal Council received energy efficient lighting upgrades as follows:
Retrofits Completed: December 2008
Tribal Office/Warehouse
Energy efficient T-8 lighting retro-kits used to
update inefficient high output fixtures.
Materials Installed Quantity
2 ft fixture, 2-lamp electronic ballast, (2) 17 watt T8 3 2-lamp electronic ballast, (2) 25 watt T8 lamps 8 2-lamp electronic ballast, (2) 32 watt T8 lamps 15 (four of these are 4ft, 2-lamp retro-kits) 4-lamp electronic ballast, (4) 32 watt T8 lamps 18 (all of these are 8ft, 4-lamp retro-kits)
CFL-20 W 1
• Lighting upgrades completed in November 2007
• Retrofitted 44 light fixtures with electronic ballasts & T8 lamps
• Installed 1 compact fluorescent light bulbs
• Pre-retrofit energy use for all lighting: 6.751 Kilowatts
• Post-retrofit energy use for all lighting: 3.552 Kilowatts
• Energy savings projection: 3.199 Kilowatts
• Pre-retrofit to post retrofit energy reduction: 47%
• Estimated Annual Savings:
Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided
250 Days Per Year Savings Use (gal) Diesel Costs
Locally Estimated $3,133.42 412.95 $1,024.12
4 Hours/day $2,088.95 275.30 $682.75
7 Hours/day $3,655.66 481.78 $1,194.81
10 Hours/day $5,222.37 688.25 $1,706.87
7
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Isanotski Corporation Owned Buildings
3 buildings owned by the Isanotski Corporation received energy efficient lighting upgrades as follows:
Isanotski Corp Office & Triplex B&B, Grocery Store, Liquor Store
• Lighting upgrades completed in November 2007
• Retrofitted 25 light fixtures with electronic ballasts & T8 lamps
• Installed 46 compact fluorescent light bulbs
• Pre-retrofit energy use for all lighting: 5.767 Kilowatts
• Post-retrofit energy use for all lighting: 2.187 Kilowatts
• Energy savings projection: 3.58 Kilowatts
• Pre-retrofit to post retrofit energy reduction: 62%
• Estimated Annual Savings:
Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided
250 Days Per Year Savings Use (gal) Diesel Costs
Locally Estimated $3,903.60 514.45 $1,275.84
4 Hours/day $2,337.74 308.09 $764.06
7 Hours/day $4,091.05 539.16 $1,337.11
10 Hours/day $5,844.35 770.22 $1,910.15
8
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Triplex-Isanotski Office
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 2 CFL-14 W 3 CFL-20 W 4 CFL-23 W 1 CFL-27 W 4 • Pre-retrofit energy use: 1148 watts
• Post-retrofit energy use: 347 watts
• Energy savings projection: 801 watts
• Pre-retrofit to post retrofit energy reduction: 70%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 1750 Hours/year (Est.) $915.34 120.63 $299.17
4 Hours/day $523.05 68.93 $170.95
7 Hours/day $915.34 120.63 $299.17
10 Hours/day $1,307.63 172.33 $427.38
Triplex-Leased Upstairs Apartment
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 3 CFL-14 W 13 CFL-20 W 6 CFL-23 W 4
• Pre-retrofit energy use: 1882 watts
• Post-retrofit energy use: 535 watts
• Energy savings projection: 1347 watts
• Pre-retrofit to post retrofit energy reduction: 72%
• Estimated annual savings: Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 1500 Hours/year (Est.) $1,319.39 173.88 $431.23
4 Hours/day $879.59 115.92 $287.48
7 Hours/day $1,539.28 202.86 $503.10
10 Hours/day $2,198.98 289.80 $718.71
9
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Tri-Plex-B&B
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 3 CFL-14 W 1 CFL-20 W 2 CFL-23 W 5 • Pre-retrofit energy use: 950 watts
• Post-retrofit energy use: 310 watts
• Energy savings projection: 640 watts
• Pre-retrofit to post retrofit energy reduction: 67%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 1500 Hours/year (Est.) $626.88 82.62 $204.89
4 Hours/day $417.92 55.08 $136.59
7 Hours/day $731.36 96.39 $239.04
10 Hours/day $1,044.80 137.69 $341.48
Grocery Store
Siri Goulette performs a systems watts
test during the lighting assessment.
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 2 2-lamp electronic ballast, (2) 32 watt T8 lamps 10
CFL-20 W 1 • Pre-retrofit energy use: 1167 watts
• Post-retrofit energy use: 714 watts
• Energy savings projection: 453 watts
• Pre-retrofit to post retrofit energy reduction: 39%
• Estimated annual savings: Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs
2400 Hours/year (Est.) $709.94 93.56 $232.04
4 Hours/day $295.81 38.98 $96.68
7 Hours/day $517.67 68.22 $169.19
10 Hours/day $739.52 97.46 $241.70
10
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Liquor Store
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 5 CFL-23 W 2 • Pre-retrofit energy use: 620 watts
• Post-retrofit energy use: 281 watts
• Energy savings projection: 339 watts
• Pre-retrofit to post retrofit energy reduction: 55%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 1500 Hours/year (Est.) $332.05 43.76 $108.53
4 Hours/day $221.37 29.17 $72.35
7 Hours/day $387.39 51.05 $126.61
10 Hours/day $553.42 72.93 $180.88
11
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
Aleutians East Borough School District Owned Buildings
False Pass School
1 building owned by the School District received energy effic ient lighting upgrades as follows:
False Pass K-12 School and Gymnasium
• School Lighting upgrades completed July 2007 - December 2007
• Retrofitted 129 light fixtures with electronic ballasts & T8 lamps
• Installed 8 T5 linear fluorescent fixtures in the School Gym
• Pre-retrofit energy use for all lighting: 12.608 Kilowatts
• Post-retrofit energy use for all lighting: 7.939 Kilowatts
• Energy savings projection: 4.669 Kilowatts
• Pre-retrofit to post retrofit energy reduction: 37%
• Estimated Annual Savings:
Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided
250 Days Per Year Savings Use (gal) Diesel Costs
Locally Estimated $5,439.10 716.82 $1,777.70
4 Hours/day $3,048.86 401.81 $996.48
7 Hours/day $5,335.50 703.16 $1,743.84
10 Hours/day $7,622.14 1004.52 $2,491.20
12
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’07-’08 Final Report NW – SW Region – False Pass
K-12 School
All classroom and hallway fixtures updated with energy efficient electronic ballast and 25 watt T -8 lamps save energy while
improving light levels for a better learning environment.
Materials Installed Quantity 2-lamp electronic ballast, (2) 25 watt T8 lamps 125 2-lamp electronic ballast, (2) 32 watt T8 lamps 4 • Pre-retrofit energy use: 9288 watts
• Post-retrofit energy use: 6115 watts
• Energy savings projection: 3173 watts
• Pre-retrofit to post retrofit energy reduction: 34%
• Estimated annual savings: Comparative Comparative Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs 1800 Hours/year (Est.) $3,729.54 491.51 $1,218.96
4 Hours/day $2,071.97 273.06 $677.20
7 Hours/day $3,625.95 477.86 $1,185.10
10 Hours/day $5,179.92 682.66 $1,692.99
Gymnasium
Existing 400 watt metal halide fixtures-
pre retrofit
T-5 fluorescent fixtures installed in
high school gymnasium.
T-5 fixtures save energy while
improving light levels in large spaces.
Materials Installed Quantity T5 fixture, electronic ballast, (4) 54 watt T5 HO 8
• Pre-retrofit energy use: 3320 watts
• Post-retrofit energy use: 1824 watts
• Energy savings projection: 1496 watts
• Pre-retrofit to post retrofit energy reduction: 45%
• Estimated annual savings: Comparative Comparative
Hours Per Day / Electrical Avoided Diesel Avoided Diesel
250 Days Per Year Savings Use (gal) Costs
1750 Hours/Year (Est) $1,709.55 225.30 $558.75
4 Hours/day $976.89 128.74 $319.28
7 Hours/day $1,709.55 225.30 $558.75
10 Hours/day $2,442.22 321.86 $798.21
False Pass - Alaska Building Science Network - T5 Lighting Upgrade Details
These retrofits were completed in July 2007
False Pass
Gym
Length
(feet)
Width
(feet)
Ceiling
Height
(feet)
Type of
Existing
Fixture
# of
Existing
Fixtures
Existing
Fixture
Wattage
Total
Existing
Wattage
Existing
Foot-
candles
New
Foot-
Candles
# of
New
Fixtures
New
fixtures
New
Fixture
Wattage
Total
New
Wattage
81ft/10in 50
ft/3in. 19ft/10in.
HPS
150
watt
160 0 14 34 T-5
2 lamps 114 0
HPS
250
watt
260 0 T-5
3 lamps 171 0
Multi-
Vapor
400
watt
8 415 3,320 8 T-5
4 lamps 228 1824
Other
School
Gym
0 T-5
6 lamps 342 0
Other
School
Gym
0 Other
fixtures 0
Total Existing Watts 3,320 Total New Watts 1824
Percent Savings Pre to Post Retrofit: 45.06%
Savings & Payback Calculation for Gym: 1750 New watts / old watts
Assume 1750 hrs / year for 250 days/year of use neg 1 (New watts / Old watts x 100 - 100) / 100
Full cost of electricity:
$0.6530 /kWh
Watts of existing lighting: 3,320
New wattage for T5 fixtures: 1,824
Calculation: (Watts) x (hrs/year) / (1000w/kw) x (cost of electricity) = (cost / year)
Existing Cost: $3,794
Retrofitted Cost: $ 2,084
Annual Savings: $ $ 1,710
Est material & shipping cost of Gym retrofit: $1,698 PO 199 is ~ $,1500
Simple Payback: Materials cost / annual savings = 0.99 years (for retrofit to pay for itself in materials)
False Pass, In-Kind Contribution Tracking Record - ABSN Energy Efficiency Projects:
In-Kind Item Dates
Hours
Contri-
buted
Hourly
Wage
Value /
Amount Notes
Staff time for project contact,
introduction & review of intro
materials (Number of entities x
1 hour each)
4.00 $15.00 $60.00 list number of entities
Staff time for Attending
teleconference (TC/IRA) 1.00 $15.00 $15.00
list # of staff and wages if possible
($15/hr is an average wage
designated for village entity staff).
Staff time for Attending
teleconference 1.00 $15.00 $15.00 City
Staff time for Attending
teleconference 3.00 $15.00 $45.00 Village Corp
Staff time for Attending
teleconference 2.00 $15.00 $30.00 School
Maint labor hours for lighting
upgrades - in-kind from Isanoski
Corp.
11/27/07 15.00 $4.00 $60.00 4 hours x $15/hr
Maint labor hours for lighting
upgrades - in-kind from False
pass Tribal Council.
11-27 to
11-30-
07
66.50 $20.00 $1,330.00 16.5 hours x $20/hr - estimated wage
including fringe
Maint labor hours for lighting
upgrades - in-kind from False
Pass School - Siri G
11-29 to
1-24-08 85.00 $22.00 $1,870.00 85 hours x $22/hr - estimated wage
including fringe
Conservative village office
administrative percentage of total
project cost less ABSN Admin %.
Total project cost = $37,775/village
- (our admin percentage , (around
9%) Approx: $3,400) = $34,375 x
5% = $1,718 (this 5% village admin
cost estimate is spread across all
entities we work with for the course
of the grant for completing all
energy efficiency measures. These
are primarily for cumulative,
otherwise unaccounted time
expense for project support.
Feb, '07
through $1,718.00
Each time we call, email, or fax a village
entity, someone has to receive the
communication, review and/or foward the
information, follow-up on requests, etc.
Wether it is to set-up a teleconference,
verify maintenance staff participation in
lighting or boiler trainings, set-up in-kind
lodging and transportation, lighting
trainings, track a shipment, verify
completion of lighting in a given building,
ship lamps and ballasts out of the village,
request a labor reimbursement
agreement, or invoice etc, etc. Village
expenses for phone charges, copying and
fax costs, office supplies, etc are part of
this ammount.
Lodging for ABSN Field
Managers - 1st assessment
site visit
Oct 22-
25, 2007 $255 $85/nightx3 nights
Lodging for ABSN Field
Managers - 2nd site visit
Nov 26-
Dec 1,
2007
$340 $85/nightx4 nights
School gymnasium lights,
labor $4,271.00 see ext tab to the right: itemized
statement-paid for by AEBSD
Isanotski Corporation
labor 24.00 $15.00 $360.00 All corp buildings labor hours in-kind.
Estmate hrs from tallysheet
TOTAL $10,369.00