HomeMy WebLinkAboutGambell Village End Use Energy Efficiency Measures Grant 2195225 2006Village End Use Energy Efficiency Measures Program ’05 – ’06 AEA Grant # 2195225 Administered by Alaska Building Science Network Gambell Final Report Community Summary 12 Community buildings received energy efficiency upgrades August ’05 – June ’07 City Hall, Washeteria, Clinic, Qernughvik Building, Community Building, Library, Small Trailer, Sivuqaq Lodge, Village Corporation Annex, Village Corporation Rental Trailer, Birder’s Building 1, Birder’s Building 2 Village-Wide Lighting Retrofit Summary: • Retrofitted 291 light fixtures village-wide with electronic ballasts and T8 lamps • Installed: 160 compact fluorescent light bulbs village-wide • T5 Light fixtures were installed in the school Gym • Pre-retrofit energy use for all lighting: 49,601 watts • Post-retrofit energy use for all lighting: 27,488 watts • Energy savings projection: 22,113 watts (22.11 kW) • Pre-retrofit to post retrofit energy reduction: 45 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $4,423 1,620 Gallons $2,948 7 Hours $7,740 2,835 Gallons $5,160 10 Hours $11,057 4,050 Gallons $7,371 • Total project cost for all measures: $ 38,235 • Simple mean payback 4.94 Years *(All grant funds, but accounting for lighting savings only) • Total village wide in-kind contribution: $ 9,528 Additional Energy Efficiency Measures: (Budget Expense: $ 2,350 ) • Installation of a Monitor heater in the Gambell IRA Bingo hall and community building. In-kind labor provided by Native Village of Gambell IRA.
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 2 Gambell City Owned Buildings Energy efficient lighting upgrades were completed in four buildings owned by the City of Gambell. City owned Buildings - Lighting Retrofit Summary: • Substantial lighting upgrades completed in December, 2006. The washeteria is scheduled to be completed by June 2007. We found out in May, 2007 that parts of this building did not receive lighting retrofits. We were asked if this building could be completed. Since we still had some remaining ’05-’06 grant funds we agreed to provide materials for the retrofits. The City of Gambell will provide in-kind labor for these upgrades.) • Retrofitted 164 linear fluorescent fixtures with T8 lamps and electronic ballasts • Installed: 17 compact fluorescent light bulbs • Pre-retrofit energy use for all lighting: 16,109 watts • Post-retrofit energy use for all lighting: 10,975 watts • Energy savings projection: 5,134 watts (5.13 kW) • Pre-retrofit to post retrofit energy reduction: 32 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $1,027 376 Gallons $685 7 Hours $1,797 658 Gallons $1,198 10 Hours $2,567 940 Gallons $1,711 City Hall Outside of City Hall Building City Hall Upstairs Hallway City Hall Main Room Downstairs Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL City Hall 40 6 0 0 0 0 0 0 • Pre-retrofit energy use: 3,832 watts • Post-Retrofit Energy Use: 3,120 watts • Energy savings projection: 712 watts (.71 Kw) • Pre-retrofit to post retrofit energy reduction: 19 %
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 3 • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $142 52 Gallons $95 7 Hours $249 91 Gallons $166 10 Hours $356 130 Gallons $237 Washeteria & Garage Washeteria & Garage Outside Laundry Room Garage Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Washeteria 46 2 0 0 0 10 0 0 • Pre-retrofit energy use: 4,700 watts • Post-Retrofit Energy Use: 3,130 watts • Energy savings projection: 1,570 watts (1.57 Kw) • Pre-retrofit to post retrofit energy reduction: 33 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $314 115 Gallons $209 7 Hours $550 201 Gallons $366 10 Hours $785 288 Gallons $523
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 4 Clinic Clinic From the Outside Miller Campbell and his lighting upgrades in the Clinic Hall Small Office Inside Clinic Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Clinic (Old Portion) 21 6 0 0 0 0 2 1 • Pre-retrofit energy use: 3,751 watts • Post-Retrofit Energy Use: 2,045 watts • Energy savings projection: 1,706 watts (1.71 Kw) • Pre-retrofit to post retrofit energy reduction: 45 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $341 125 Gallons $227 7 Hours $597 219 Gallons $398 10 Hours $853 312 Gallons $569
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 5 Qernughvik Building One of the Two Local Bingo Halls Inside the Q Building with Miller Campbell Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Qernughvik (Q Building) 43 0 0 0 0 0 0 4 • Pre-retrofit energy use: 3,826 watts • Post-Retrofit Energy Use: 2,680 watts • Energy savings projection: 1,146 watts (1.15 Kw) • Pre-retrofit to post retrofit energy reduction: 30 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $229 84 Gallons $153 7 Hours $401 147 Gallons $267 10 Hours $573 210 Gallons $382
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 6 Gambell IRA Owned Buildings Energy efficient lighting upgrades were completed in 3 buildings owned by the Gambell IRA IRA owned Buildings - Lighting Retrofit Summary: • Substantial lighting upgrades completed in December, 2006. The library is scheduled to be completed in June 2007. (This building was originally operated by the City of Gambell and was not in use. It was subsequently transferred to the IRA. In May, ’07 we were asked if this building could be done. Since we still had some remaining ’05-’06 grant funds we agreed to provide materials for the retrofits. The Gambell IRA will provide in-kind labor for these upgrades.) • Retrofitted 48 linear fluorescent fixtures with T8 lamps and electronic ballasts • Installed: 1 compact fluorescent light bulbs • Pre-retrofit energy use for all lighting: 3,689 watts • Post-retrofit energy use for all lighting: 2,321 watts • Energy savings projection: 1,368 watts (1.37 kW) • Pre-retrofit to post retrofit energy reduction: 37 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $274 100 Gallons $182 7 Hours $479 175 Gallons $319 10 Hours $684 251 Gallons $456 Community Building The Second Gambell Bingo Hall Bingo Hall Offices Bingo Hall Main Room Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Community Building 0 0 18 9 0 0 1 0 • Pre-retrofit energy use: 2,039 watts • Post-Retrofit Energy Use: 1,334 watts • Energy savings projection: 705 watts (.71 Kw) • Pre-retrofit to post retrofit energy reduction: 35 %
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 7 • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $141 52 Gallons $94 7 Hours $247 90 Gallons $165 10 Hours $353 129 Gallons $235 Library Materials Installed 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fix tures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Library 0 0 15 0 0 0 0 0 • Pre-retrofit energy use: 1,230 watts • Post-Retrofit Energy Use: 705 watts • Energy savings projection: 525 watts (.53 Kw) • Pre-retrofit to post retrofit energy reduction: 43 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $105 38 Gallons $70 7 Hours $184 67 Gallons $123 10 Hours $263 96 Gallons $175 Small Office Trailer TC/IRA Buildings 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL Small Office Trailer 0 0 6 0 0 0 0 0 • Pre-retrofit energy use: 420 watts • Post-Retrofit Energy Use: 282 watts • Energy savings projection: 138 watts (.14 Kw) • Pre-retrofit to post retrofit energy reduction: 33 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $28 10 Gallons $18 7 Hours $48 18 Gallons $32 10 Hours $69 25 Gallons $46 Gambell Village Corporation Owned Buildings
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 8 Energy efficient lighting upgrades were completed in 5 buildings owned by Sivuqaq Inc. Village Corporation owned Buildings - Lighting Retrofit Summary: • Substantial lighting upgrades completed in December, 2006. The Annex, Rental Office, Birder’s Building #1, Birder’s Building #2 is scheduled to be completed in June 2007. (These buildings were not originally part of USKH energy audits. We were asked by Sivuqaq Inc. in April if these buildings could be done. Since we still had remaining ’05-’06 grant funds we agreed to provide materials for the retrofits. Sivuqaq will provide in-kind labor for these upgrades.) • Retrofitted 36 linear fluorescent fixtures with T8 lamps and electronic ballasts • Installed: 142 compact fluorescent light bulbs • Pre-retrofit energy use for all lighting: 13,615 watts • Post-retrofit energy use for all lighting: 4,202 watts • Energy savings projection: 9,413 watts (9.41 kW) • Pre-retrofit to post retrofit energy reduction: 69 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $1,883 690 Gallons $1,255 7 Hours $3,295 1,207 Gallons $2,196 10 Hours $4,707 1,724 Gallons $3,138 Sivuqaq Lodge Outside of Sivuqaq Lodge Lodge Bathroom Lodge Sitting Room & Hansen Irrigoo Vilage Corp Buildings 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-way CFLs Sivuqaq Lodge 30 0 0 60 0 0 0 • Pre-retrofit energy use: 6,460 watts • Post-Retrofit Energy Use: 2,340 watts • Energy savings projection: 4,120 watts (4.12 Kw) • Pre-retrofit to post retrofit energy reduction: 64 %
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 9 • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $824 302 Gallons $549 7 Hours $1,442 528 Gallons $961 10 Hours $2,060 755 Gallons $1,373 Annex Vilage Corp Buildings 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-way CFLs An ne x 0 0 0 0 8 10 10 0 • Pre-retrofit energy use: 2,480 watts • Post-Retrofit Energy Use: 554 watts • Energy savings projection: 1,926 watts (1.93 Kw) • Pre-retrofit to post retrofit energy reduction: 78 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $385 141 Gallons $257 7 Hours $674 247 Gallons $449 10 Hours $963 353 Gallons $642 Rental Office Vilage Corp Buildings 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-way CFLs Rental "Office" 6 0 0 0 0 0 0 0 • Pre-retrofit energy use: 420 watts • Post-Retrofit Energy Use: 282 watts • Energy savings projection: 138 watts (.14 Kw) • Pre-retrofit to post retrofit energy reduction: 33 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $28 10 Gallons $18 7 Hours $48 18 Gallons $32 10 Hours $69 25 Gallons $46 Birder’s Building 1
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 10 Vilage Corp Buildings 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-way CFLs Birder's Building 1 0 0 0 0 9 8 12 7 • Pre-retrofit energy use: 3,175 watts • Post-Retrofit Energy Use: 717 watts • Energy savings projection: 2,458 watts (2.46 Kw) • Pre-retrofit to post retrofit energy reduction: 77 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $492 180 Gallons $328 7 Hours $860 315 Gallons $574 10 Hours $1,229 450 Gallons $819
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 11 Birder’s Building 2 Vilage Corp Buildings 2-Lamp Ballasts 25w lamps 2-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Fixtures 3-lamp ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-way CFLs Birder's Building 2 0 0 0 0 8 7 1 2 • Pre-retrofit energy use: 1,080 watts • Post-Retrofit Energy Use: 309 watts • Energy savings projection: 771 watts (.77 Kw) • Pre-retrofit to post retrofit energy reduction: 71 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $154 56 Gallons $103 7 Hours $270 99 Gallons $180 10 Hours $386 141 Gallons $257 Notes: The majority of lighting in Sivuqaq Inc buildings was incandescent bulbs. Throughout their buildings Sivuqaq maintenance staff replaced 142 incandescents with CFLs which will result in sizeable savings and substantially reduced energy use.
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 12 Gambell School Owned Buildings Energy efficient lighting upgrades were completed in six room spaces in the school owned by the Bering Straits School District. School owned Buildings - Lighting Retrofit Summary: • Lighting upgrades completed in August, 2005 • Retrofitted 43 linear fluorescent fixtures with T8 lamps and electronic ballasts • Pre-retrofit energy use for all lighting: 16,188 watts • Post-retrofit energy use for all lighting: 9,990 watts • Energy savings projection: 6,198 watts (6.20 kW) • Pre-retrofit to post retrofit energy reduction: 38 % • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $1,240 454 Gallons $826 7 Hours $2,169 795 Gallons $1,446 10 Hours $3,099 1,135 Gallons $2,066 School Building Gambell School School Hallway School Shop School Buildings 2-Lamp Ballasts 32w lamps 4-Lamp Ballasts 32w lamps 2-Lamp Ballasts 25w lamps 4-Lamp Ballasts 25w lamps 13w CFL 20w CFL 25w CFL 3-Lamp Fixtures 3-lamp ballasts (3) 32w lamps Fixture T O T A L S 24 0 0 0 0 0 0 19 • Pre-retrofit energy use: 4,153 watts • Post-Retrofit Energy Use: 3,150 watts • Energy savings projection: 1,003 watts (1 Kw) • Pre-retrofit to post retrofit energy reduction: 24 %
Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell 13 • Estimated Annual Savings: Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $201 73 Gallons $134 7 Hours $351 129 Gallons $234 10 Hours $502 184 Gallons $334 High Output T5 Lighting Upgrades for the School Gym School Gym Hours Per Day / 250 Days Per Year Electrical Savings Avoided Diesel Use Avoided Diesel Costs 4 Hours $1,039 381 Gallons $693 7 Hours $1,818 666 Gallons $1,212 10 Hours $2,598 951 Gallons $1,732 Notes: With the darker walls of the Gambell gym, we chose to use all 4-lamp fixtures to provide ample lighting. Four choices of wall switching also give flexibility in selecting light levels. The lighting plan with all 4-lamp fixtures will result in a 43% reduction in energy use while providing exceptional light level.
14 Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell Gambell School, T5 Lighting Upgrade Details, ABSN Energy Efficiency Projects '05 -'06 These retrofits were completed in August, 2005. Gambell Gym Length (feet) Width (feet) Ceiling Hieght (feet) # of Existing Fixtures Existing Fixture Wattage Total Existing Wattage Existing Foot -candles New Foot -Candles # of New Fixtures lamps / fixture New Fixture Wattage Total New Wattage 86 58 27 29 415 12,035 92 30 4 228 6840 New T5 wattage = 57 watts / lamp, which includes ballast wattage New foot candles per Industrial Lighting Products Total New wattage for gym = ~43 % savings ! Savings & Payback Calculation for Gym: Assume 1800 hrs / year for 250 days/year of use Full cost of electricity: $ 0.20 /kWh Watts of existing lighting: 12,035 New wattage for T5 fixtures: 6,840 Calculation: (Watts) x (hrs/year) / (1000w/kw) x (cost of electricity) = (cost / year) Existing Cost: $ 4,333 /yr Retrofitted Cost: $ 2,462 /yr Annual Savings: $ $ 1,870 /yr Est material & shipping cost of Gym retrofit: $ 6,417.42 Simple Payback: Materials cost / annual savings = 3.431408 years (for retrofit to pay for itself in materials)
15 Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell Measures Beyond Lighting: Notes: With the expense of T5 lighting upgrades for the Gambell school gym, little materials and labor budget was left for energy saving measures beyond lighting. New Monitor heater for the Gambell IRA Bingo Hall Prior to the VEUEEM program The Gambell IRA Bingo Hall had an old, worn out forced air furnace barely heating that building. Duct leakage into the attic space was also occurring. The Gambell IRA staff mentioned what they thought was excessive fuel use for that building. During the course of the grant, the old forced air furnace broke down for the last time and we used grant funds to purchase a replacement Monitor heater. Fuel savings and payback on the measure is expected to be substantial. Gambell IRA maintenance staff installed the new Monitor through in-kind labor.
16 Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell Gambell, In-Kind Contribution Tracking Record - ABSN Energy Efficiency Projects: Village entities worked with: Tribe, City, Village Corp, School District. In-Kind Item Dates Hours Contri-buted Hourly Wage Value / Amount Notes Staff time for project contact, introduction, and reviewof intro materials (Number of entities x 1 hour each) 4 $15.00 $60.00 # of entities we worked with in the village is indicated in the Hrs contributed column. $15 / hr is our generic estimated average wage for local village staff: Tribal Administrators, City Clerks, etc. Staff time for Attending teleconference village-wide 10.5 $15.00 $157.50 Hrs contributed column indicates length of telecon multiplied by # of village telecon participants Tribal Maint. Staff time to assist Field Manager on building assessments - 1st site visit 3 $15.00 $45.00 list hrs of in-kind staff assisting FM on building assessments. CityMaint. Staff time to assist Field Manager on building assessments - 1st site visit 3 $15.00 $45.00 School Maint. Staff time to assist Field Manager site visits 16 $15.00 $240.00 in-kind portion Lighting training 3-05 March '05 3 $15.00 $45.00 City of Gambell paid for training - lighting upgrades Village office administrative percentage of total project cost less ABSN Admin %. Total project cost = $37,775/village - (our admin percentage , (around 9%) Approx: $3,400) = $34,375 x 5% = $1,718 (this 5% village admin cost estimate is spread across all entities we work with for the course of the grant for completing all energy efficiency measures. These are primarily for cumulative, otherwise unaccounted time expense for project support. Jan '05 - Jan '07 $1,718.00 Each time we call, email, or fax a village entity, someone has to receive the communication, review and/or foward the information, follow-up on requests, etc. Wether it is to set-up a teleconference, verify maintenance staff participation in lighting or boiler trainings, set-up in-kind lodging and transportation, lighting trainings, track a shipment, verify completion of lighting in a given building, ship lamps and ballasts out of the village, request a labor reimbursement agreement, or invoice etc, etc. Village expenses for phone charges, copying and fax costs, office supplies, etc are part of this ammount. Lodging for Final site visit $125.00 reg rate of $105/night, less discounted rate of $85/for 2 nights Transportation and fuel costs during 2nd Site-visit $100.00 2 days @ $50/day Employer share of payroll contributions $158.33 Natiive village of Gambell Payroll & w/c employer share from 12-28-06 invoice School & teacher housing lighting upgrades $360.00 estimate T8s: 1 staff, 20 hours X $18/hr, = Installation of Monitor heater in IRA Bingo hall / community bldg 15 15 $225.00 15 hours In-kind labor by Gambell IRA, research materials, shipping, purchase, set -up, install School T5 Gym lighting upgrades $6,250.00 estimate based on half of Savoonga's itemized BSSD expense for the T5 installations. As Gambell was the 2nd village, many of the install bugs had been worked out. TOTAL $9,528.83
17 Alaska Building Science Network – Village End Use Energy Efficiency Program – ’05-06 Final Report – NW/SW Regions - Gambell