HomeMy WebLinkAboutASRC-BRW-RSA Barrow Public Works 2012-EE
Richard S. Armstrong, PE, LLC
Comprehensive Energy Audit
Barrow Public Works
Project #
The North Slope Borough
Department of Public Works
Richard S. Armstrong, PE, LLC
2321 Merrill Field Drive, C
Barrow Public Works Office
Barrow Public Works Office Comprehensive Energy Audit
3
REPORT DISCLAIMERS
The information contained in this report, including any attachments, is
intended solely for use by the building owner and the AHFC. No others are
authorized to disclose, copy, distribute or retain this report, in whole or
part, without written authorization from Richard S. Armstrong, PE, LLC,
2321 Merrill Field Drive, C-6, Anchorage, Ak 99501. Additionally, this
report contains recommendations that, in the opinion of the auditor, will
cause the owner to realize energy savings over time. All recommendations
must be designed by a registered engineer, licensed in the State of
Alaska, in the appropriate discipline. Lighting recommendations should all
be first reviewed by running a lighting analysis to assure that the
recommended lighting upgrades will comply with State of Alaska Statue as
well as IES recommendations.
Payback periods may well vary from those forecast due to the uncertainty
of the final installed design, configuration, equipment selected, and
installation costs of recommended Energy Efficiency Measures (EEMs), or
the operating schedules and maintenance provided by the owner.
Furthermore, EEMs are typically interactive, so implementation of one
EEM may impact the cost savings from another EEM. Neither the auditor,
Richard S. Armstrong, PE, LLC, AHFC, or others involved in preparation of
this report will accept liability for financial loss due to EEMs that fail to
meet the forecasted payback periods.
This audit meets the criteria of an Investment Grade Audit (IGA) per the
Association of Energy Engineers definition, and is valid for one year. The
life of the IGA may be extended on a case-by-case basis, at the discretion
of the AHFC.
IGSs are the property of the State, and may be incorporated into AkWarm-
C, the Alaska Energy Data Inventory (ARIS), or other state and/or public
information system
Barrow Public Works Office Comprehensive Energy Audit
4
Investment Grade Energy Audit
Barrow Public Works Office
1. Executive Summary: The Barrow Public Works Office Was
Originally constructed in 1976 as a 29-unit apartment building. In
2005, the building underwent a complete renovation and has been
used 100% as an office for the NSB Public Works Department. The
facility contains 52 offices, four restrooms, three storage rooms, two
conference rooms, two break rooms, a mechanical bay, a reception
area, and a lobby. The building is in good condition. The 2010 and
2011 annual utility energy consumption reported by BUECI and
collected as benchmark data by WHPacific, Inc. is displayed in Table
1 below:
Table 1
2010 2010 2011 2011
Utility Consumption Cost/Year Consumption Cost/Year
Electricity-kWh 244,080 $25,862 235,280 $26,988
Natural Gas-CCF 26,886 $8,245 31,251 $9,576
Total Energy Costs $34,107 $36,564
A benchmark measure of energy use relative to other similar function
buildings in the area is the Energy Use Index (EUI), which takes the
total annual energy used by the facility divided by the square footage
area of the building, for a value expressed in terms of kBTU/SF. This
number can then be compared to other buildings to see if it is about
average, higher or lower than similar buildings in the area. Likewise,
the Energy Cost Index (ECI) is the cost of all energy used by the
building expressed in $/SF of building area. The comparative values
for the subject building are listed in Table 2 below:
Table 2
Public Works Barrow Avg NSB Admin Bldg
Energy Use Index (EUI)
kBTU/SF
154 224 238
Energy Cost Index (ECI)
$/SF
$1.51 $1.83 $2.42
Various Energy Efficiency Measures (EEMs) have been analyzed for
this building to determine if they would be applicable for energy
savings with reasonably good payback periods. Those EEMs that
Barrow Public Works Office Comprehensive Energy Audit
5
have a payback period of less than 8 years, or those that are
recommended for code compliance, life cycle replacement, or other
reasons are also included. Also, where a lighting upgrade is
recommended from T-12 lamps with magnetic ballasts to T-8 lamps
with electronic ballasts, then the entire facility should be relamped
and reballasted to maintain a standard lighting parts inventory,
regardless of the payback. For example, a storage room that is
infrequently used may not show a very good payback for a lighting
upgrade, but consistency dictates a total upgrade.
Specific EEMs recommended for this facility are detailed in the
attached AkWarm Energy Audit Report along with specific payback
times, as well as estimated installation costs and estimated energy
savings. The higher priority items are summarized below:
a. Exterior Lighting Upgrades: The exterior high pressure
sodium lights operate during periods of darkness, which is
about half of a year. It is estimated that the use of LED
exterior lights can reduce the power consumption by 60%.
b. Air Handler Unit Cycling: The AHU-1 currently operates
24/7 because it is in manual rather than auto mode. AHU-1
is meant to ventilate the south wing of the building, which is
unoccupied during non-business hours. The purpose of this
EEM is to only start AHU-1 when the south wing is
occupied.
c. Air Handler Unit Summer Pre-Filters: AHU-1 and AHU-2
have pre-filters for filtration of summer dust. These should
be removed in the winter to prevent clogging from snow.
This has been seen to lower the building CO2 levels by over
10%, and decreases the load on the AHUs.
d. Glycol Circulation Pumps: The hydronic heating system is
designed to have two sets of glycol loops run by two
circulation pumps, CP-1 and CP-2, running at the pumps’
preset speed 2. A third pump, CP-3 is plumbed-in as a
backup to either CP-1 or CP-2 and should be run only when
another pump fails.
All three pumps were found running 24/7, with CP-3 running
on speed 3. Operation of the third pump is causing the
control valves to bypass, thus overheating the building and
wasting energy (from both the pump and heat loss).
Barrow Public Works Office Comprehensive Energy Audit
6
Additionally, CP-2 was found to be set on speed 3. This is
also exceeding the designed flow and wasting money and
energy.
CP-3 should be switched to “auto” rather than “hand”, and
CP-2 should be switched to speed 2 rather than speed 3.
These EEMs require minimal time and effort and give a
combined instant payback of $1,088 per year.
e. Headbolt Heater Controls: Leaving the headbolt heaters
energized 24/7 is unnecessary for typical winter
temperatures in Barrow. The building already has a timer
system installed, but it has had the dogs removed. This
timer should be returned to auto and tested. Returning the
timer to service and cycling the headbolt heaters every 20-
minutes (20-minutes on, 20-minutes off) will still maintain
vehicle components at adequate temperatures and may
save around $2,500 per year.
In addition to EEMs, various Energy Conservation Measures (ECMs)
are recommended since they are policies or procedures that are
followed by management and employees that require no capital
outlay. Examples of recommended ECMs for this facility include:
• Turn off lights when leaving a room that is not controlled by an
occupancy sensor that automatically turns off lights.
• Turn off computers, monitors, printers, faxes, coffee makers,
etc when leaving the office for the day.
• Keep overhead doors closed except when they are required to
be open for movement of vehicles.
The 10 priority recommendations in the detailed report estimate to save
$ 10,940/year, with an installed cost of $ 14,354. This does not include
design or CA services, but overall it does indicate a cost effective
energy savings program.
2. Audit and Analysis Background:
a. Program Description: This audit included services to identify,
develop, and evaluate energy efficiency measures at the
subject building. The scope of this project included evaluating
the building shell, lighting, other electrical systems, and
heating, ventilating, and air conditioning (HVAC) equipment.
Barrow Public Works Office Comprehensive Energy Audit
7
Measures were selected such that an overall simple payback
period of 8 years or less could be achieved.
b. Audit Description and Methodology: Preliminary audit
information was gathered in preparation for the site survey,
including benchmark utility consumption data, floor and lighting
plans, and equipment schedules where available. A site visit is
then performed to inventory and evaluate the actual building
condition, including:
i. Building envelope (roof, windows, etc)
ii. Heating, ventilating, and air conditioning
iii. Lighting systems and controls
iv. Building specific equipment
v. Plumbing systems
c. Method of Analysis: The information gathered prior to the site
visit and at the site visit is entered into AkWarm-C, an energy
modeling developed for Alaska Housing Finance Corporation
(AHFC) specifically to identify forecasted energy consumption
which can be compared to actual energy consumption.
AkWarm-C also has some pre-programmed EEM retrofit
options that can be analyzed with energy savings forecasted
based on occupancy schedules, utility rates, building
construction type, building function, existing conditions, and
climatic data that is already uploaded to the program based on
the zip code of the building. When new equipment is proposed,
energy consumption is calculated based on manufacturer’s
cataloged information.
Cost savings are calculated based on the historical energy
costs for the building. Installation costs include labor and
equipment to estimate the full up-front investment required to
implement a change, but design and construction management
costs are excluded. Costs are derived from Means Cost Data,
industry publications, experience of the auditor, local
contractors, and equipment suppliers. Applicable maintenance
savings were calculated and added to the energy savings for
each EEM.
Barrow Public Works Office Comprehensive Energy Audit
8
The cost and savings are applied and a simple payback and
simple return on investment (ROI) is calculated. The simple
payback is based on the number of years that it takes for the
savings to pay back the net installation cost (Net Installation
divided by Net Savings.)
A simple life-time calculation is shown for each EEM. The life-
time for each EEM is estimated based on the typical life of the
equipment being replaced or altered. The energy savings is
extrapolated throughout the life-time of the EEM. The total
energy savings is calculated as the total life-time multiplied by
the yearly savings.
d. Limitations of the Study: All results are dependent on the
quality of input data provided, and can only act as an
approximation. In some instances, several methods may
achieve the identified savings. This report is not intended as a
final design document. A design professional, licensed to
practice in Alaska and in the appropriate discipline, who is
following the recommendations, shall accept full responsibility
and liability for the results. Budgetary estimates for engineering
and design of these projects in not included in the cost
estimate for each measure, but these costs generally run
around 15% of the cost of the work.
3. Acknowledgements: We wish to acknowledge the help of
numerous individuals who have contributed information that was
used to prepare this report, including:
a. Alaska Housing Finance Corporation (Grantor): AHFC
provided the grant funds, contracting agreements, guidelines,
and technical direction for providing the audits. AHFC reviewed
and approved the final short list of buildings to be audited
based on the recommendation of the Technical Service
Provider (TSP).
b. North Slope Borough (Owner): The NSB provided building
sizing information, two years energy billing data, building
schedules and functions, as well as building age.
Barrow Public Works Office Comprehensive Energy Audit
9
c. Nortech Engineering (Benchmark TSP): Nortech
Engineering compiled the data received from the NSB and
entered that data into the statewide building database, called
the Alaska Retrofit Information System (ARIS).
d. Richard S. Armstrong, PE, LLC (Audit TSP): This is the TSP
who was awarded the projects in the Arctic Slope Regional
Corporation, Bering Straits area, and the Nana area. The firm
gathered all relevant benchmark information provided to them
by Nortech, cataloged which buildings would have the greatest
potential payback, and prioritized buildings to be audited based
on numerous factors, including the Energy Use Index (EUI),
the Energy Cost Index (ECI), the age of the building, the size
of the building, the location of the building, the function of the
building, and the availability of plans for the building. They also
trained their selected sub-contracted auditors, assigned
auditors to the selected buildings, and performed quality
control reviews of the resulting audits. They prepared a listing
of potential EEMs that each auditor must consider, as well as
the potential EEMs that the individual auditor may notice in the
course of his audit. Richard S. Armstrong, PE, LLC also
performed some of the audits to assure current knowledge of
existing conditions.
e. WHPacific, Inc (Audit Preparer): This firm specializes in
mechanical, electrical, and civil design, and has one
mechanical EIT who is a Certified Energy Auditor in Training.
This CEIT has received additional training from Richard S.
Armstrong, PE, LLC to acquire further specific information
regarding audit requirements and potential EEM applications.
WHPacific prepared this audit and submitted it for review by
Richard S. Armstrong, PE, LLC.
4. Building Description and Function: The subject building is called
the Barrow Public Works Building. It was originally constructed in
1976 as an apartment complex and had a complete renovation in
2005 to become an office for the North Slope Borough Department
of Public Works. The total size of the building is 22704 ft2. The
building has two stories.
Barrow Public Works Office Comprehensive Energy Audit
10
a. Heating System: The building heating system consists of two
Weil-Mclain 1080 cast iron boilers, fired sequentially. Hot glycol
is distributed to baseboard heaters, a unit heater, and the air
handler coils through copper pipe.
b. Ventilation System: Two make up air units supply air to the
building. These are labeled AHU-1 and AHU-2 and are located
in the mechanical room. AHU-1 supplies air to the south wing
at a rate of 1960 CFM. AHU-2 supplies air to the north wing at
a rate of 1510 CFM. The south wing is exhausted with a 2000
CFM exhaust fan, and a 1600 CFM exhaust fan pulls air from
the north wing. The two first floor restrooms are exhausted with
individual 330 CFM exhaust fans. The two second floor
restrooms are exhausted with a single 660 CFM exhaust fan. A
300 CFM fan exhausts the communication room.
c. Plumbing System: The restrooms contain 16 toilets, 4 urinals,
and 12 sinks for hand washing. The break rooms contain 2
sinks for dishes and coffee, the conference rooms contain 2
sinks, and there are 4 water fountains outside the restrooms.
d. Domestic Hot Water: Hot water is generated in an Amtrol
HWG, located in the mechanical room, using hot glycol from
the boilers.
e. Lighting: Office lighting throughout the building is composed
of T-8 fluorescent fixtures with electric ballasts. The hallways
are lit by wall-mounted CFLs. Exterior lighting utilizes 250, 150,
and 100 watt high pressure sodium (HPS) wall packs, pole-
mounted flood lights, and canopy lights.
5. Historic Energy Consumption: Energy consumption is modeled
within the AkWarm-C program. The program only analyzes 12
months of data, so where 24 months of data are available, the data
is averaged to provide more accuracy. The energy consumption data
is presented and graphed in the attached AkWarm-C program
results.
Energy consumption was analyzed using two factors: the Energy
Cost Index (ECI) and the Energy Use Index (ECU).
Barrow Public Works Office Comprehensive Energy Audit
11
The energy cost index takes the average cost of gas and electrical
energy over the surveyed period of time (typically 2 years) and
averages the cost, divided by the square footage of the building.
The ECI for this building is $ 1.51/SF, and the average ECI for all
buildings in Barrow that were surveyed is $ 1.83/SF. The NSB
Administration building, an older office building in Barrow has an ECI
of $ 2.42/SF
The energy use index (ECU) is the total average electrical and
heating energy consumption per year expressed in thousands of
BTUs/SF. The average ECU for all buildings in Barrow that were
surveyed is 224 kbtu/sf, and the EUI for this building is 154 kbtu/sf,
compared to 238 kbtu/sf for the NSB administration building.
6. Energy Efficiency Measures considered or recommended: The
building was examined for application of a multitude of potential
EEMs that are discussed below. Those EEMs that appear to have an
application for the subject building are further analyzed for estimated
payback periods, either within the AkWarm-C program or separately
within this report. The accuracy of the cost estimates and paybacks
varies significantly due to a multitude of conditions, but is estimated
to be approximately +/- 25%. Assumptions made regarding energy
costs and the life of the EEM, noting that post-construction
measurement and verification are based on energy savings, not
energy cost savings.
Many of the selected EEMs are analyzed within the AkWarm-C
program using the schedules and estimated costs input into the
model. Some of the other EEMs are not modeled within AkWarm-C,
and are individually discussed within this report.
7. Interactive Effects of Projects: The AkWarm-C program calculates
savings assuming that all recommended EEM are implemented. If
some EEMs are not implemented, savings for the remaining EEMs
will be affected, in some cases positively, and in others, negatively.
For example, if the pump motor’s speed is not reduced, then the
savings for putting the pump on “auto” will be increased.
In general, all projects were evaluated sequentially so that energy
savings associated with one EEM would not be attributed to another
Barrow Public Works Office Comprehensive Energy Audit
12
EEM as well. For example, the unoccupied thermostat setback EEM
was analyzed using the fan and heating load profile that will be
achieved after switching AHU-1 to “auto”. By modeling the
recommended projects sequentially, the analysis accounts for
interactive effects between the EEMs and does not “double count”
savings.
Interior lighting, plug loads, facility equipment, and occupants
generate heat within the building. When the building is in cooling
mode, these contribute to the overall cooling demands of the
building; therefore lighting efficiency improvements will reduce
cooling requirements on air conditioned buildings. Conversely,
lighting efficiency improvements are anticipated to increase heating
requirements slightly. Heating penalties are included in the lighting
project analysis that is performed by AkWarm-C.
8. Loan Program: The Alaska Housing Finance Corporation (AHFC)
Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State
of Alaska program enacted by the Alaska Sustainable Energy Act
(senate Bill 220, A.S. 18.56.855, “Energy Efficiency Revolving Loan
Fund). The AEERLF will provide loans for energy efficiency retrofits
to public facilities via the Retrofit Energy Assessment for Loan
System (REAL). As defined in 15 AAC 155.605, the program may
finance energy efficiency improvements to buildings owned by:
a. Regional educational attendance areas;
b. Municipal governments, including political subdivisions of
municipal governments;
c. The University of Alaska;
d. Political subdivisions of the State of Alaska, or
e. The State of Alaska
Native corporations, tribal entities, and subsidiaries of the federal
government are not eligible for loans under this program.
Appendix A: Photos
Reception area
Mechanical room; boilers and circulation pump #1 shown
Appendix A: Photos
Mechanical room; equipment control panels, circulation pumps, and hot water
generator shown
Mechanical room mezzanine; Make-up air units shown
Appendix A: Photos
Mechanical room mezzanine; AHU-1 shown
Mechanical room mezzanine; snow-clogged pre-filter shown
Appendix A: Photos
Snow infiltration in AHU-1 intake duct
Mechanical room; headbolt heater timer
Appenendix B
Energy Audit – Energy Analysis and Cost Comparison
AkWarm Commercial Audit Software
NSB Public Works Building
Page 1
ENERGY AUDIT REPORT – PROJECT SUMMARY – Created 1/10/2012 6:24 AM
General Project Information
PROJECT INFORMATION AUDITOR INFORMATION
Building: NSB Public Works Building Auditor Company: Richard S. Armstrong, PE, LLC
Address: 1689 Okpik Auditor Name: Richard S. Armstrong, David Robbins
City: Barrow Auditor Address: 2321 Merrill Field Drive C-6
Anchorage, Ak 99501 Client Name: Charlie Sakeagak
Client Address: PO Box 69
Barrow, AK 99723
Auditor Phone: (907) 229-0331
Auditor FAX:
Client Phone: (907) 852-0489 Auditor Comment:
Client FAX:
Design Data
Building Area: 22,704 square feet Design Heating Load: Design Loss at Space: 1,164,683
Btu/hour
with Distribution Losses: 1,164,683 Btu/hour
Plant Input Rating assuming 82.0% Plant Efficiency and
25% Safety Margin: 1,775,432 Btu/hour
Note: Additional Capacity should be added for DHW load,
if served.
Typical Occupancy: 76 people Design Indoor Temperature: 68 deg F (building average)
Actual City: Barrow Design Outdoor Temperature: -41 deg F
Weather/Fuel City: Barrow Heating Degree Days: 20,370 deg F-days
Utility Information
Electric Utility: Barrow Utilities & Electric-elec -
Commercial - Lg
Natural Gas Provider: Barrow Utilities & Electric-gas -
Commercial - Lg
Average Annual Cost/kWh: $0.112/kWh Average Annual Cost/ccf: $0.307/ccf
Annual Energy Cost Estimate
Description Space
Heating
Space
Cooling
Water
Heating Lighting Refrige
ration
Other
Electric
al
Cooking Clothes
Drying
Ventilatio
n Fans
Service
Fees Total Cost
Existing
Building
$8,703 $0 $69 $7,896 $412 $14,30
2
$0 $0 $1,385 $1,222 $33,989
With
Proposed
Retrofits
$2,815 $0 $62 $7,548 $412 $10,59
0
$0 $0 $398 $1,222 $23,048
SAVINGS $5,889 $0 $6 $348 $0 $3,711 $0 $0 $987 $0 $10,941
Appenendix B
Energy Audit – Energy Analysis and Cost Comparison
AkWarm Commercial Audit Software
NSB Public Works Building
Page 2
$0
$5,000
$10,000
$15,000
$20,000
$25,000
$30,000
$35,000
Existing Retrofit
Service Fees
Ventilation and Fans
Space Heating
Refrigeration
Other Electrical
Lighting
Domestic Hot Water
Annual Energy Costs by End Use
$0
$5,000
$10,000
$15,000
$20,000
$25,000
$30,000
$35,000
Existing Retrofit
Natural Gas
Electricity
Annual Energy Costs by Fuel
Appenendix B
Energy Audit – Energy Analysis and Cost Comparison
AkWarm Commercial Audit Software
NSB Public Works Building
Page 3
PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES
Rank Feature Recommendation Annual Energy
Savings
Installed
Cost
SIR Payback
(Years)
1 Ventilation change from "HAND" to
"AUTO"
$6,571 $1 83179.41 0
2 Other Electrical:
Glycol pump speed 2
Remove Manual Switching
and Add new Other
Controls
$841 $1 5360.77 0
3 Other Electrical:
Glycol pump speed 3
Replace with pump $252 $1 1605.41 0
4 Other Electrical:
Headbolt Heaters
Add new Clock Timer or
Other Scheduling Control
$2,486 $20 1526.17 0
5 Setback Thermostat:
First Floor
Implement a Heating
Temperature Unoccupied
Setback to 60.0 deg F for
the First Floor space.
$224 $200 14.26 0.9
6 Setback Thermostat:
Second Floor
Implement a Heating
Temperature Unoccupied
Setback to 60.0 deg F for
the Second Floor space.
$218 $200 13.86 0.9
7 Lighting: Type H1
exterior
Replace with 2 LED 115W
Module StdElectronic
$77 $2,695 0.35 35
8 Lighting: Type G
exterior
Replace with 5 LED 115W
Module StdElectronic
$179 $6,736 0.33 37.5
9 Lighting: Type K
exterior
Replace with LED 72W
Module StdElectronic
$24 $900 0.32 38.1
10 Lighting: Type H
exterior
Replace with 4 LED 48W
Module StdElectronic
$68 $3,600 0.23 53.3
TOTAL $10,941 $14,354 9.1 1.3
ENERGY AUDIT REPORT – ENERGY EFFICIENT RECOMMENDATIONS
1. Building Envelope
Insulation
Rank Location Existing Type/R-Value Recommendation Type/R-
Value
Installed
Cost
Annual
Energy
Savings
Exterior Doors – Replacement
Rank Location Size/Type/Condition Recommendation Installed
Cost
Annual
Energy
Savings
Windows and Glass Doors – Replacement
Appenendix B
Energy Audit – Energy Analysis and Cost Comparison
AkWarm Commercial Audit Software
NSB Public Works Building
Page 4
Rank Location Size/Type/Condition Recommendation Installed
Cost
Annual
Energy
Savings
Air Leakage
Rank Location Estimated Air Leakage Recommended Air Leakage
Target
Installed
Cost
Annual
Energy
Savings
2. Mechanical Equipment
Mechanical
Rank Recommendation Installed
Cost
Annual
Energy
Savings
Setback Thermostat
Rank Location Size/Type/Condition Recommendation Installed
Cost
Annual
Energy
Savings
5 First Floor Existing Unoccupied Heating
Setpoint: 68.0 deg F
Implement a Heating
Temperature Unoccupied
Setback to 60.0 deg F for
the First Floor space.
$200 $224
6 Second Floor Existing Unoccupied Heating
Setpoint: 68.0 deg F
Implement a Heating
Temperature Unoccupied
Setback to 60.0 deg F for
the Second Floor space.
$200 $218
Ventilation
Rank Recommendation Cost Annual
Energy
Savings
1 change from "HAND" to "AUTO" $1 $6,571
3. Appliances and Lighting
Lighting Fixtures and Controls
Rank Location Existing Recommended Installed
Cost
Annual
Energy
Savings
7 Type H1 exterior 2 HPS 250 Watt Magnetic with
Daylight Sensor
Replace with 2 LED 115W
Module StdElectronic
$2,695 $77
8 Type G exterior 5 HPS 250 Watt StdElectronic
with Daylight Sensor
Replace with 5 LED 115W
Module StdElectronic
$6,736 $179
9 Type K exterior HPS 150 Watt Magnetic with
Daylight Sensor
Replace with LED 72W
Module StdElectronic
$900 $24
10 Type H exterior 4 HPS 100 Watt Magnetic with
Daylight Sensor
Replace with 4 LED 48W
Module StdElectronic
$3,600 $68
Refrigeration
Rank Location Existing Recommended Installed
Cost
Annual
Energy
Savings
Appenendix B
Energy Audit – Energy Analysis and Cost Comparison
AkWarm Commercial Audit Software
NSB Public Works Building
Page 5
Other Electrical Equipment
Rank Location Existing Recommended Installed
Cost
Annual
Energy
Savings
2 Glycol pump speed
2
2 pump with Manual Switching Remove Manual Switching
and Add new Other
Controls
$1 $841
3 Glycol pump speed
3
pump with Manual Switching Replace with pump $1 $252
4 Headbolt Heaters 36 Headbolt Heater with Other
Controls
Add new Clock Timer or
Other Scheduling Control
$20 $2,486
Cooking/Clothes Drying
Rank Recommended Installed
Cost
Annual
Energy
Savings
Appendix C: Equipment Schedules - Mechanical
Appendix C: Equipment Schedules - Mechanical
Appendix D: Building Plan
Appendix D: Building Plan
Appendix E: Lighting Plan
Appendix E: Lighting Plan
Appendix F: Mechanical Schematics
Appendix F: Mechanical Schematics
Appendix F: Mechanical Schematics
Appendix F: Mechanical Schematics
Appendix F: Mechanical Schematics