Loading...
HomeMy WebLinkAboutASRC-PIZ-RSA Cully Kali School 2012-EE Richard S. Armstrong, PE, LLC Mechanical/Electrical Engineer Comprehensive Energy Audit of Point Lay Cully (AKA Kali) School Project # ASRC!PIZ!RSA!1 Prepared for: North Slope Borough School District Contact: Pat Kennedy Jr, Director of Maintenance & Operations March 20, 2012 Prepared by: Richard S. Armstrong, PE, LLC 2321 Merrill Field Drive, C!6 Anchorage, Alaska 99501 ii TABLE OF CONTENTS 1. Executive Summary 1 2. Audit and Analysis Background 5 3. Acknowledgements 6 4. Building Description & Function 7 5. Historic Energy Consumption 8 6. Energy Efficiency Measures Considered 8 7. Interactive Effects of Projects 9 8. Loan Program 9 Appendix A – AkWarm4C Report 10 Appendix B – Building Plans & Equipment Schedules 20 Submitted by: _______________________________ Richard S. Armstrong, PE, CEM, CEA Date: March 20st, 2012 iii REPORT DISCLAIMERS The information contained in this report, including any attachments, is intended solely for use by the building owner and the AHFC. No others are authorized to disclose, copy, distribute or retain this report, in whole or part, without written authorization from Richard S. Armstrong, PE, LLC, 2321 Merrill Field Drive, C!6, Anchorage, AK 99501. Additionally, this report contains recommendations that, in the opinion of the auditor, will cause the owner to realize energy savings over time. All recommendations must be designed by a registered engineer, licensed in the State of Alaska, in the appropriate discipline. Lighting recommendations should all be first reviewed by running a lighting analysis to assure that the recommended lighting upgrades will comply with State of Alaska Statue as well as IES recommendations. Payback periods may well vary from those forecast due to the uncertainty of the final installed design, configuration, equipment selected, and installation costs of recommended Energy Efficiency Measures (EEMs), or the operating schedules and maintenance provided by the owner. Furthermore, EEMs are typically interactive, so implementation of one EEM may impact the cost savings from another EEM. Neither the auditor, Richard S. Armstrong, PE, LLC, AHFC, or others involved in preparation of this report will accept liability for financial loss due to EEMs that fail to meet the forecasted payback periods. This audit meets the criteria of an Investment Grade Audit (IGA) per the Association of Energy Engineers definition, and is valid for one year. The life of the IGA may be extended on a case!by!case basis, at the discretion of the AHFC. IGSs are the property of the State, and may be incorporated into AkWarm!C, the Alaska Energy Data Inventory (ARIS), or other state and/or public information system 1 Investment Grade Energy Audit Point Lay Cully (aka Kali) School 1. Executive Summary: This comprehensive Energy Audit is performed in connection with AHFC’s Retrofit Energy Assessment for Loans (REAL) program. Select Building: Point Hope Cully School 1029 Qasigiaklik St Point Lay, Alaska 99759 Building Owner: North Slope Borough School District Pat Kennedy Jr, Director of Maintenance & Operations Building Contact: Daryl Daugaard, School Principal (907) 85270311 The Cully School was originally constructed around 1981. The school has seen several additions and remodels, performed in 1994, 1995, 2002, and 2003. This analysis measured an area of 35,558 SF. Energy consumption recorded for this school is noted below, with the basis being the actual fuel bills for 2010, and the reported power. The power bills have been averaged for two years, 2009 and 2010, but the report models less power use than actual. This could be the result of inaccurate model estimating, or the result of actual electricity reported potentially including other out buildings, such as teacher housing or storage buildings which were not included in the report. Table 1 2010 2011 Utility Consumption Cost/Year Electricity+kWh 549,440 $ 191,055 Oil Consumption (gallons) 26,393 $112,171 Total Energy (kBtu) 5,359,664 $303,226 A benchmark measure of energy use relative to other similar function buildings in the area is the Energy Use Index (EUI), which takes the total annual energy used by the facility divided by the square footage area of the building, for a value expressed in terms of kBTU/SF. This number can then be compared to other 2 buildings to see if it is about average, higher or lower than similar buildings in the area. Likewise, the Energy Cost Index (ECI) is the cost of all energy used by the building expressed in $/SF of building area. In order to develop the most accurate EUI and ECI comparisons possible, only North Slope Borough Schools in remote communities were used to develop the baseline averages. This allows for similar energy cost, facility usage, and climate comparison between the subject school and the benchmark average. The EUI and ECI baseline averages are comprised of two years worth of data (2010 & 2011). The comparative values for the subject building are listed in Table 2 below: Table 2 Point Lay Cully School Wainwright Alak School Atqasuk Meade River School Energy Use Index (EUI) kBTU/SF 2010 150.7 209 224 Energy Cost Index (ECI) Average 2010 $8.53 $9.07 $8.52 Various Energy Efficiency Measures (EEMs) have been analyzed for this building to determine if they would be applicable for energy savings with reasonably good payback periods. Those EEMs that have a payback period or those that are recommended for code compliance, life cycle replacement, or other reasons are also included. Specific EEMs recommended for this facility are detailed in the attached AkWarm Energy Audit Report along with specific payback times, as well as estimated installation costs and estimated energy savings. The higher priority items are summarized below: a. Exterior Lighting Upgrades: Replace all exterior building wall mounted HID fixtures with new dark sky compliant LED type wall mounted light fixtures: LED technology has come a long way, and for applications like this, LED lights are ready for prime time. LED fixtures use nano reflector technology with drivers offering 50,000 hours life. That equates to about 6 years, as compared to only 20,000 hours with HID fixtures. LED fixtures offer the instant7on feature of fluorescent, but use significantly less energy than the HID fixtures. LED lamps like the cold, have been factory tested to operate down to 740 deg F (actual installations in Antarctica and Fairbanks indicate they operate at lower temperatures as well, depending on manufacturer. The proposed LED fixtures are dark sky compliant by using 100% cutoff optics to reduce light pollution. The following chart indicates energy savings for the various exterior building mounted light fixtures (HSP High Pressure Sodium) using Scotopic lighting measurements: 3 HID Lamp HID System Wattage LED System Wattage Energy Savings (%) 70W HPS 105W 27W 74 250W HPS 300W 108W 64 b. Occupancy Sensor Lighting Control Upgrades: Occupancy sensors have evolved over the years to now be more reliable, and have fewer false starts and stops. Dual technology occupancy sensors combine passive infrared (PIR) and ultrasonic technologies into one unit to achieve precise coverage and to eliminate false triggers. The sensors can be mounted on the wall in place of the existing light switch, or on the ceiling where more uniform coverage and detection is desired in a larger room. Wall switch type automatic occupancy sensors are appropriate for small rooms, such as utility rooms, one person toilet rooms, small open offices, and places where the wall switch is located such that occupants can be detected with line7of7sight from anywhere in the room. They can turn lights on and off based on both occupancy and ambient light levels. Devices in break rooms, utility rooms, storage rooms, small offices, and small open (non7partitioned) bathrooms can save up to 60% of the cost of the lighting where rooms are infrequently used, but the lights are typically left on. c. Air Handling Unit Upgrades: Install a CO2 sensor in the return air stream of air handlers serving classrooms, gyms, or multipurpose rooms to reduce outside air requirements. Carbon dioxide (CO2) is a known tracer gas for human metabolic activity, and has been recognized by ASHRAE and code authorities as a credible way to reduce minimum outside air (OSA) requirements in air handling units (AHUs). The CO2 sensor would drive the outside air dampers to provide return air from the rooms with CO2 levels at or below CO2 set7point, (typically <750 PPM CO2), thus avoiding over7ventilation of the space. The two primary sources of heat loss from a building are conduction through the building envelope and loss of heated air through ventilation or infiltration. Ventilation loads approach conduction loads in well ventilated buildings located in cold climates. Additionally, building DDC static pressure controls should be implemented if not already in place. The payback for this ECM is very difficult to assess without extensive historical review of actual OSA settings, but it is estimated to save 25% of the OSA heating requirements caused by over7 ventilating. The payback cost, assuming a cost of $1,500 to install and program each CO2 sensor, is under 2 years. 4 d. Install Programmable Set7back Thermostats: Buildings that are not continuously occupied do not require continuous heating levels at 70 degrees, so they can be set back to 55 or 60 degrees F. This is typically done with relatively inexpensive programmable set7back thermostats or through DDC systems. The cost of each thermostat with installation should not exceed $250, with paybacks of one year or less in most cases. The school has a JCI DDC system, but we could not verify if the baseboard thermostats are set back through the DDC system. If they are already set back, ignore this recommendation. e. Fuel Oil Metering: In order to understand current and future fuel consumption, a fuel meter is essential to be installed at the fuel supply to the building, assuming the supply is piped. The Pathfinder Instruments FM7200 meter is for fuel pipes sized ¾” to 1” (different meters, must specify pipe size), and they cost around $225 each. They operate at a flow range of 4720 GPM. These are mechanical meters with strainers and 37digit display that shows both present fuel use, and cumulative fuel use. Any ESCO contract, or AHFC financed contract will require fuel metering to verify paybacks of energy conservation measures. Electronic turbine meters are also available. Fuel consumption was tallied by reviewing actual fuel receipts for 2010, but the total fuel accounted for by the receipts did not agree with the fuel consumption reported by the NSBSD. It is possible that the reported NSBSD numbers included teacher housing and other outbuildings, that would account for the higher numbers. See http://pathfinderinstruments.com/gpifuel.htm?gclid=CJuzvdzon6kCFSUaQgodvg JDvQ. f. Air Infiltration Reduction: It is estimated that door and window weatherstripping could be replaced or upgraded by local maintenance personnel at an estimated cost of $5,000. If this could reduce infiltration into the school by 10%, the payback would be only 2.9 years. g. Relamp using 28 watt fluorescent lamps: The school presently uses 32 watt T78 flourescent lamps. At the next re7lamping it is recommended that all 32 watt lamps be replaced with 28 watt lamps. This results in a 4% reduction in light output, but a 12% reduction in energy consumed. In addition to EEMs, various Energy Conservation Measures (ECMs) are recommended since they are policies or procedures that are followed by management and employees that require no capital outlay. Examples of recommended ECMs for this facility include: • Turn off lights when leaving a room that is not controlled by an occupancy sensor that automatically turns off lights. • All doors and windows should be properly maintainedand adjusted to close and function properly. • Turn off computers, monitors, printers, faxes, coffee makers, etc when leaving the office for the day. 5 The 60 priority recommendations in the detailed report (Appendix A) are estimated to save $17,325 /year, with an installed cost of $29,560, for a 1.7 year payback. This assumes that maintenance people could install most of the upgrades as part of their normal assigned duties, and does not include design or CA services, but overall it does indicate a cost effective energy savings program. 2. Audit and Analysis Background: a. Program Description: This audit included services to identify, develop, and evaluate energy efficiency measures at the subject building. The scope of this project included evaluating the building shell, lighting, other electrical systems, and heating, ventilating, and air conditioning (HVAC) equipment. b. Audit Description and Methodology: Preliminary audit information was gathered in preparation for the site survey, including benchmark utility consumption data, floor and lighting plans, and equipment schedules where available. A site visit is then performed to inventory and evaluate the actual building condition, including: i. Building envelope (roof, windows, etc) ii. Heating, ventilating, and air conditioning iii. Lighting systems and controls iv. Building specific equipment v. Plumbing systems c. Method of Analysis: The information gathered prior to the site visit and at the site visit is entered into AkWarm7C, an energy modeling program developed for Alaska Housing Finance Corporation (AHFC) specifically to identify forecasted energy consumption which can be compared to actual energy consumption. AkWarm7C also has some pre7programmed EEM retrofit options that can be analyzed with energy savings forecasted based on occupancy schedules, utility rates, building construction type, building function, existing conditions, and climatic data that is already uploaded to the program based on the zip code of the building. When new equipment is proposed, energy consumption is calculated based on manufacturer’s cataloged information. Cost savings are calculated based on the historical energy costs for the building. Installation costs include in7house labor and equipment to estimate the full up7front investment required for implementing a change, but design and construction management costs are excluded. Maintenance savings are calculated were applicable and are added to the energy savings for each EEM. 6 The cost and savings are applied and a simple payback and simple return on investment (ROI) is calculated. The simple payback is based on the number of years that it takes for the savings to pay back the net installation cost (Net Installation divided by Net Savings.) A simple life7time calculation is shown for each EEM. The life7time for each EEM is estimated based on the typical life of the equipment being replaced or altered. The energy savings is extrapolated throughout the life7time of the EEM. The total energy savings is calculated as the total life7time multiplied by the yearly savings. d. Limitations of the Study: All results are dependent on the quality of input data provided, and can only act as an approximation. In some instances, several methods may achieve the identified savings. This report is not intended as a final design document. A design professional, licensed to practice in Alaska and in the appropriate discipline, who is following the recommendations, shall accept full responsibility and liability for the results. Budgetary estimates for engineering and design of these projects in not included in the cost estimate for each measure, but these costs generally run around 15% of the cost of the work. 3. Acknowledgements: We wish to acknowledge the help of numerous individuals who have contributed information that was used to prepare this report, including: a. Alaska Housing Finance Corporation (Grantor): AHFC provided the grant funds, contracting agreements, guidelines, and technical direction for providing the audits. AHFC reviewed and approved the final short list of buildings to be audited based on the recommendation of the Technical Service Provider (TSP). b. North Slope Borough School District (Owner): The NSBSD provided building sizing information, two years energy billing data, building schedules and functions, as well as building age. c. Nortech Engineering (Benchmark TSP): Nortech Engineering Company compiled the data received from the NSB and entered that data into the statewide building database, called the Alaska Retrofit Information System (ARIS). d. Richard S. Armstrong, PE, LLC (Audit TSP): This is the TSP who was awarded the projects in the Arctic Slope Regional Corporation, North Slope Borough area, and the Nana area. The firm gathered all relevant benchmark information provided to them by Nortech Engineering Company, cataloged which buildings would have the greatest potential 7 payback, and prioritized buildings to be audited based on numerous factors, including the Energy Use Index (EUI), the Energy Cost Index (ECI), the age of the building, the size of the building, the location of the building, the function of the building, and the availability of plans for the building. They also trained their selected sub7contracted auditors, assigned auditors to the selected buildings, and performed quality control reviews of the resulting audits. They prepared a listing of potential EEMs that each auditor must consider, as well as the potential EEMs that the individual auditor may notice in the course of his audit. Richard S. Armstrong, PE, LLC performed this audits to assure current knowledge of existing conditions. 4. Building Description and Function: The subject structure is called the Kali School, but was formerly known as the Cully School. This facility was originally constructed in 1982, and four additions, renovations or upgrades have occurred since the original construction in 1993, 1995, 2002, and 2003. The building is located on pilings and is mostly a one story structure with a peaked roof and drop ceilings. The only second floor space utilized is the fan room and the communications room. a. Heating System: The building heating system consists of three Weil McLain 988 cast iron oil fired boilers with John Zink Burners. The boilers and burners appear to have been installed in 2004 and are in good condition, despite the fact that two of the three were down for repairs during the audit. The boilers are used to heat the buildings’ hydronic heating system, which in turn provides all of the heating for the building through baseboard, unit heaters, and heating coils in the air handlers. The building has six main loops, with each loop equipped with a primary and a backup circulator. All circulators were set to operate at speed 2, which agrees with the design intent settings on the plans. b. Ventilation System: The ventilation system for the School is composed of numerous fans and air handlers that provide the outside ventilation air for the facility. Each of the fans has been modeled in the AkWarm7C program to hopefully understand the total air movement. The fans include: eight air handlers, four make7up air units, 14 exhaust fans, and two return fans. As mentioned on the executive summary, carbon dioxide sensors are recommended to be installed at the air handlers and programmed through the DDC system to modulate down the outside air dampers to only maintain required CO2 levels, so the amount of outside air could be reduced to reflect the actual need for fresh air rather than constantly dumping excessive amounts of outside air to the space. The air handlers are operated on a time clock program provided through the DDC system, and they all appeared to be functioning correctly except the kitchen exhaust and make up which was operating after normal school 8 hours, and another air handler that was found to have the motor controller overridden to manual. c. Plumbing System: The Cully School appears to have energy efficient plumbing fixtures, reflecting the relatively new construction of the facility. No replacement plumbing fixtures are recommended at this time. d. Domestic Hot Water: Hot water for the Cully School is produced by two 120 gallon hot water generator (Amtrol Boilermate WHS7120ZCDW). The hot water generators have a first hour rating of 372 gallons at a temperature rise of 90 °F and a continuous flow rating of 268 gallons per hour. The current hot water generator was installed in 2004 when the boiler room and boilers were upgraded. e. Lighting: Typical lighting throughout the building is comprised of T78 fluorescent fixtures with electronic ballasts. The lighting in the gym is comprised of new T75 high output fluorescent fixtures which can be switched off when not in use since the lights can be started without any restrike time as found on high intensity discharge fixtures. The three summary level lighting recommendations are: i. Change 32 watt fluorescent lamps with 28 watt lamps during the next re7lamping effort. This reduces light output by 4% but reduces energy consumption by 12%. ii. Change the outside HPS lighting fixtures out with LED fixtures. iii. Install occupancy sensor switches at the classrooms and other spaces so the lights go off when occupants leave the space. 5. Historic Energy Consumption: Energy consumption is modeled within the AkWarm7C program. The program only analyzes 12 months of data, so where 24 months of data are available, the data is averaged and input to AkWarm7C to provide more accuracy. The energy consumption data is presented and graphed in the attached AkWarm7C program results. The 2010 electric consumption for the building is 549,440 kWh/year at an average cost of $191,055 /year. The 2010 fuel oil consumption is 26,393 gallons/year, at a 2010 cost of $112,171 /year. This results in the total utility costs for the building of $303,226 /year. 6. Energy Efficiency Measures considered or recommended: The building was examined for application of a multitude of potential EEMs. Those EEMs that appear to have an application for the subject building are further analyzed for estimated payback periods, either within the AkWarm7C program or separately. The accuracy of the cost estimates and paybacks varies significantly due to a multitude of conditions, but is estimated to be approximately +/7 25%. 9 Assumptions made regarding energy costs and the life of the EEM, noting that post7construction measurement and verification are based on energy savings, not energy cost savings. Many of the selected EEMs are analyzed within the AkWarm7C program using the schedules and estimated costs input into the model. 7. Interactive Effects of Projects: The AkWarm7C program calculates savings assuming that all recommended EEM are implemented. If some EEMs are not implemented, savings for the remaining EEMs will be affected, in some cases positively, and in others, negatively. For example, if the fan motors are not replaced with premium efficiency motors, then the savings for the project to install variable speed drives (VFDs) on the fans will be increased. In general, all projects were evaluated sequentially so that energy savings associated with one EEM would not be attributed to another EEM as well. For example, the night setback EEM was analyzed using the fan and heating load profile that will be achieved after installation of the VFD project is completed. By modeling the recommended projects sequentially, the analysis accounts for interactive effects between the EEMs and does not “double count” savings. Interior lighting, plug loads, facility equipment, and occupants generate heat within the building. When the building is in cooling mode, these contribute to the overall cooling demands of the building; therefore lighting efficiency improvements will reduce cooling requirements on air conditioned buildings. Conversely, lighting efficiency improvements are anticipated to increase heating requirements slightly. Heating penalties are included in the lighting project analysis that is performed by AkWarm7C. 8. Loan Program: The Alaska Housing Finance Corporation (AHFC) Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State of Alaska program enacted by the Alaska Sustainable Energy Act (senate Bill 220, A.S. 18.56.855, “Energy Efficiency Revolving Loan Fund). The AEERLF will provide loans for energy efficiency retrofits to public facilities via the Retrofit Energy Assessment for Loan System (REAL). As defined in 15 AAC 155.605, the program may finance energy efficiency improvements to buildings owned by: a. Regional educational attendance areas; b. Municipal governments, including political subdivisions of municipal governments; c. The University of Alaska; d. Political subdivisions of the State of Alaska, or e. The State of Alaska Native corporations, tribal entities, and subsidiaries of the federal government are not eligible for loans under this program. Appendix A Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 1 ENERGY AUDIT REPORT – PROJECT SUMMARY – Created 3/21/2012 4:34 PM General Project Information PROJECT INFORMATION AUDITOR INFORMATION Building: Cully School aka Kali School Auditor Company: Richard S. Armstrong, PE, LLC Address: 1029 Qasigialik St Auditor Name: Richard S. Armstrong, PE City: Point Lay Auditor Address: 2321 Merrill Field Drive Unit C-6 Anchorage, Ak 99501 Client Name: Daryl Daugaard Client Address: 1029 Qasigialik St Point Lay, Alaska 99759 Auditor Phone: (907) 229-0331 Auditor FAX: (907) 276-1751 Client Phone: (907) 852- 031 Auditor Comment: Client FAX: Design Data Building Area: 35,558 square feet Design Heating Load: Design Loss at Space: 2,941,571 Btu/hour with Distribution Losses: 3,268,412 Btu/hour Plant Input Rating assuming 82.0% Plant Efficiency and 25% Safety Margin: 4,982,335 Btu/hour Note: Additional Capacity should be added for DHW load, if served. Typical Occupancy: 201 people Design Indoor Temperature: 69.4 deg F (building average) Actual City: Point Lay Design Outdoor Temperature: -37 deg F Weather/Fuel City: Point Lay Heating Degree Days: 19,109 deg F-days Utility Information Electric Utility: North Slope Borough Utilities - Commercial - Lg Natural Gas Provider: None Average Annual Cost/kWh: $0.320/kWh Average Annual Cost/ccf: $0.000/ccf Annual Energy Cost Estimate Description Space Heating Space Cooling Water Heating Lighting Refrige ration Other Electric al Cooking Clothes Drying Ventilatio n Fans Service Fees Total Cost Existing Building $115,41 8 $0 $11,605 $12,176 $23,30 5 $26,07 9 $0 $0 $3,421 $0 $192,004 With Proposed Retrofits $102,23 8 $0 $13,110 $6,526 $23,30 5 $26,07 9 $0 $0 $3,421 $0 $174,680 SAVINGS $13,180 $0 -$1,505 $5,650 $0 $0 $0 $0 $0 $0 $17,325 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 2 $0 $50,000 $100,000 $150,000 $200,000 Existing Retrofit Ventilation and Fans Space Heating Refrigeration Other Electrical Lighting Domestic Hot Water Annual Energy Costs by End Use $0 $50,000 $100,000 $150,000 $200,000 Existing Retrofit #1 Oil Electricity Annual Energy Costs by Fuel $0 $20,000 $40,000 $60,000 $80,000 Floor Wall/Door Window Ceiling Air Existing Retrofit Annual Space Heating Cost by Component Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 3 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 1 Setback Thermostat: Classroom - 122 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 122 space. $1,100 $200 74.61 0.2 2 Setback Thermostat: Classroom - 116 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 116 space. $1,067 $200 72.34 0.2 3 Setback Thermostat: Library - 105 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Library - 105 space. $990 $200 67.15 0.2 4 Setback Thermostat: Classroom - 123 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 123 space. $904 $200 61.31 0.2 5 Setback Thermostat: Storage - 168 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Storage - 168 space. $763 $200 51.72 0.3 6 Setback Thermostat: Classroom - 110 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 110 space. $672 $200 45.60 0.3 7 Setback Thermostat: Classroom 112 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom 112 space. $612 $200 41.50 0.3 8 Setback Thermostat: Classroom - 113 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 113 space. $606 $200 41.07 0.3 9 Setback Thermostat: Classroom 111 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom 111 space. $597 $200 40.51 0.3 10 Setback Thermostat: Classroom - 120 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 120 space. $502 $200 34.04 0.4 11 Setback Thermostat: Classroom - 121 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 121 space. $497 $200 33.74 0.4 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 4 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 12 Setback Thermostat: Science - 109 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Science - 109 space. $479 $200 32.51 0.4 13 Setback Thermostat: Classroom - 119 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Classroom - 119 space. $358 $200 24.26 0.6 14 Setback Thermostat: Work Room - 104 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Work Room - 104 space. $356 $200 24.14 0.6 15 Lighting: K-90, 90 watt HPS exterior Replace with 6 LED 25W Module StdElectronic $1,102 $1,200 22.09 1.1 16 Setback Thermostat: Principal - 101 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Principal - 101 space. $321 $200 21.78 0.6 17 Setback Thermostat: Conference - 102 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Conference - 102 space. $301 $200 20.44 0.7 18 Setback Thermostat: Student Store - 108 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Student Store - 108 space. $217 $200 14.71 0.9 19 Setback Thermostat: Office - 103 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Office - 103 space. $217 $200 14.70 0.9 20 Setback Thermostat: Commons - 107 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Commons - 107 space. $190 $200 12.88 1.1 21 Setback Thermostat: Office - 163 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Office - 163 space. $101 $200 6.82 2 22 Setback Thermostat: Kitchen - 162 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Kitchen - 162 space. $94 $200 6.39 2.1 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 5 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 23 Lighting: 2002 Addition D3 Shop Lights Replace with 21 FLUOR (3) T8 4' F32T8 28W Energy- Saver (2) Instant StdElectronic $30 $30 6.06 1 24 Lighting: I-100 Boiler room and maint office lights Remove Manual Switching and Add new Occupancy Sensor $818 $1,500 4.47 1.8 25 Lighting: U100 Corridor lights Replace with 6 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $69 $120 3.39 1.7 26 Air Tightening Perform air sealing to reduce air leakage by 10%. $1,781 $5,000 3.31 2.8 27 Lighting: 2002 Addition canopy lights Replace with 3 LED 25W Module StdElectronic $479 $900 3.30 1.9 28 Lighting: P90 HPS Exterior Replace with 6 LED 25W Module StdElectronic $721 $1,500 2.97 2.1 29 Lighting: Shop Classroom Lighting Remove Manual Switching and Add new Occupancy Sensor $21 $500 2.77 23.4 30 Lighting: 1995 Addition Exterior HPS fixtures Replace with 7 LED 25W Module StdElectronic $669 $1,500 2.76 2.2 31 Lighting: B-100 Suspended louvered classroom fixture Remove Manual Switching and Add new Occupancy Sensor $24 $600 2.32 25.1 32 Lighting: B-200 Suspended louvered classroom fixture Remove Manual Switching and Add new Occupancy Sensor $140 $3,000 1.64 21.4 33 Lighting: 2002 Addition 4-tube classroom lights Replace with 16 FLUOR (4) T8 4' F32T8 28W Energy- Saver (2) Instant StdElectronic $30 $160 1.14 5.3 34 Lighting: 1995 Addition classroom lights B Remove Manual Switching and Add new Occupancy Sensor $81 $500 0.97 6.2 35 Lighting: 2003 Addition B-3 fixtures Replace with 12 FLUOR (3) T8 4' F32T8 28W Energy- Saver (2) Instant StdElectronic $19 $120 0.96 6.2 36 Lighting: 1995 Addition Pool and locker room lighting D Replace with 21 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $20 $150 0.79 7.6 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 6 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 37 Lighting: 1995 Addition B1 Fixture CR Remove Manual Switching and Add new Occupancy Sensor $31 $250 0.75 7.9 38 Lighting: 2002 Addition A2 Fixtures Remove Manual Switching and Add new Occupancy Sensor $30 $250 0.71 8.5 39 Lighting: B-100 Suspended louvered classroom fixture Replace with 12 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $14 $120 0.67 8.8 40 Lighting: 1995 Addition classroom lights B Replace with 27 FLUOR (3) T8 4' F32T8 28W Energy- Saver (2) Instant StdElectronic $28 $270 0.63 9.5 41 Lighting: 2002 Addition D3 Shop Lights Remove Manual Switching and Add new Occupancy Sensor $48 $500 0.56 10.5 42 Lighting: 2002 Addition 4-tube classroom lights Remove Manual Switching and Add new Occupancy Sensor $47 $500 0.56 10.5 43 Lighting: 1995 Addition under cabinet task lights Replace with 5 FLUOR (2) T8 4' F32T8 28W Energy- Saver Program StdElectronic $4 $50 0.48 12.5 44 Lighting: 2003 Addition D2 lights Replace with 6 FLUOR (2) T8 4' F32T8 28W Energy- Saver (2) Instant HighEfficElectronic $5 $60 0.45 13.1 45 Lighting: 2003 addition A3 fixtures Replace with 12 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $8 $120 0.38 15.5 46 Lighting: I-100 Boiler room and maint office lights Replace with 42 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $27 $420 0.38 15.7 47 Lighting: 2003 D-2 fixtures Remove Manual Switching and Add new Occupancy Sensor $21 $500 0.25 23.6 48 Lighting: 2003 Addition D2 lights Remove Manual Switching and Add new Occupancy Sensor $9 $250 0.21 28.3 49 Lighting: 1995 Addition B1 Fixture CR Replace with 8 FLUOR (4) T8 4' F32T8 28W Energy- Saver (2) Instant StdElectronic $10 $320 0.18 33.2 50 Lighting: 1995 Addition corridor C & D fixtures Replace with 16 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $5 $160 0.16 35.4 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 7 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 51 Lighting: B-200 Suspended louvered classroom fixture Replace with 60 FLUOR (4) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $62 $2,400 0.15 38.5 52 Lighting: 2002 Addition A2 Fixtures Replace with 5 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $1 $50 0.12 49.2 53 Lighting: 2003 addition A3 fixtures Remove Manual Switching and Add new Occupancy Sensor $7 $350 0.12 49.8 54 Lighting: 2003 D-2 fixtures Replace with 18 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $3 $130 0.11 51.4 55 Lighting: G-100 Water resistant Room Lights Replace with 18 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $5 $360 0.08 70.9 56 Lighting: D100 Corridor lights Replace with 31 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $9 $620 0.08 71 57 Lighting: H100 or I100 surface mount Replace with 15 FLUOR (2) T8 4' F32T8 28W Energy- Saver Instant StdElectronic $4 $300 0.08 70.8 58 Setback Thermostat: Chase - 131 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Chase - 131 space. $0 $200 0.00 Infinity 59 Setback Thermostat: Warehouse - 169 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Warehouse - 169 space. $0 $200 0.00 Infinity 60 Setback Thermostat: Storage 201 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Storage 201 space. $0 $200 0.00 Infinity TOTAL $17,325 $29,560 7.48 1.7 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 8 School Exterior School Exterior Circulators Additional circulators Boilers Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Cully School aka Kali School Page 9 Johnson Controls Metysys Controls Old pneumatic control panel Plugged air inlet preheat coil at AHU AHU starter on manual ------------------------------------------ AkWarmCalc Ver 2.1.4.2, Energy Lib 3/1/2012