Loading...
HomeMy WebLinkAboutBSSD-ELI-RSA Elim Aniguiin School 2012-EERichard S. Armstrong, PE, LLC Mechanical/Electrical Engineer Comprehensive Energy Audit of Elim Aniguiin K12 School Elim, Alaska Project # BSSDELIRSA01 Prepared for: Bering Strait School District Contact: Richard Ried, Maintenance Supervisor Phone: 9076244249 Unalakleet, Alaska February 17, 2012 Prepared by: Richard S. Armstrong, PE, LLC 2321 Merrill Field Drive, C$6 Anchorage, AK 99501 and RSA Engineering, Inc. 2422 Arctic Blvd., Suite 200 Anchorage, AK 99503 Elim Aniguiin K-12 School Comprehensive Energy Audit 2 TABLE OF CONTENTS 1. Report Disclaimers 3 2. Executive Summary 4 3. Audit and Analysis Background 8 4. Acknowledgements 10 5. Building Description & Function 11 6. Historic Energy Consumption 14 7. Energy Efficiency Measures Considered or Recommended 14 8. Interactive Effects of Projects 21 9. Loan Program 21 Appendix A: Photos 23 Appendix B: AkWarm7C Report 35 Appendix C: Building Schedules and Plans 48 Performed by: ___________________________ Adam W. Wilson, PE, CEA CEA # 1618 RSA Engineering, Inc. Reviewed by: ___________________________ Richard Armstrong, PE, CEM CEA #178, CEM # 13557 Elim Aniguiin K-12 School Comprehensive Energy Audit 3 1. REPORT DISCLAIMERS This audit was performed using American Recovery and Reinvestment Act (ARRA) funds, managed by the Alaska Housing Finance Corporation (AHFC). The information contained in this report, including any attachments, is intended solely for use by the building owner and the AHFC. This report contains recommendations that, in the opinion of the auditor, will cause the owner to realize energy savings over time. All recommendations must be designed by a registered engineer, licensed in the State of Alaska, in the appropriate discipline. Lighting recommendations should all be first reviewed by running a lighting analysis to assure that the recommended lighting upgrades will comply with State of Alaska Statue as well as IES recommendations. Payback periods may well vary from those forecast due to the uncertainty of the final installed design, configuration, equipment selected, and installation costs of recommended Energy Efficiency Measures (EEMs), or the operating schedules and maintenance provided by the owner. Furthermore, EEMs are typically interactive, so implementation of one EEM may impact the cost savings from another EEM. Neither the auditor, Richard S. Armstrong, PE, LLC, AHFC, or others involved in preparation of this report will accept liability for financial loss due to EEMs that fail to meet the forecasted payback periods. This audit meets the criteria of an Investment Grade Audit (IGA) per the Association of Energy Engineers definition, and is valid for one year. The life of the IGA may be extended on a case$by$case basis, at the discretion of the AHFC. IGSs are the property of the State, and may be incorporated into AkWarm$ C, the Alaska Energy Data Inventory (ARIS), or other state and/or public information system. AkWarm$C is a building energy modeling software developed under contract with AHFC. Elim Aniguiin K-12 School Comprehensive Energy Audit 4 Investment Grade Energy Audit Elim Aniguiin K12 School 2. Executive Summary: The Elim Aniguiin K$12 School was constructed in 2002, using design concepts and construction materials that were similar to present day Western Alaska school construction. It is owned and operated by the Bering Strait School District (BSSD). Benchmark energy use data collected for this building is presented in Table 1 below: Table 1 2009 2009 2010 2010 Utility Consumption Cost/Year Consumption Cost/Year Electricity$kWh 199,482 $109,565 128,627 $ 75,292 No. 2 Fuel Oil $ Gallons 9,408 $ 38,954 14,396 $ 44,657 Ttl Energy Costs $148,519 $119,949 A benchmark measure of energy use relative to other similar function buildings in the area is the Energy Use Index (EUI), which takes the total annual energy used by the facility divided by the square footage area of the building, for a value expressed in terms of kBTU/SF. This number can then be compared to other buildings to see if it is about average, higher or lower than similar buildings in the area. Likewise, the Energy Cost Index (ECI) is the cost of all energy used by the building expressed in $/SF of building area. The comparative values for the subject building are listed in Table 2 below: Table 2 Elim Aniguiin K$12 School Koyuk Malimiut K$ 12 School (neigh$ boring village) Average for All BSSD Schools Energy Use Index (EUI) kBTU/SF Avg 2009, 2010 71.2 136.4 125.3 Energy Cost Index (ECI) Average 2009, 2010 $4.49 $7.17 $6.73 Various Energy Efficiency Measures (EEMs) have been analyzed for this building to determine if they would be applicable for energy savings with reasonably good payback periods. Those EEMs that Elim Aniguiin K-12 School Comprehensive Energy Audit 5 have a payback period or those that are recommended for code compliance, life cycle replacement, or other reasons are also included. Specific EEMs recommended for this facility are detailed in the attached AkWarm Energy Audit Report along with specific payback times, as well as estimated installation costs and estimated energy savings. The higher priority items are summarized below: a. Building HVAC Controls i. The building heating, ventilation and air conditioning (HVAC) system is currently served by pneumatic controls. It is recommended that the pneumatic control system be replaced with an electronic control system. This will allow greater control of the HVAC systems and reduce the amount of maintenance costs associated with a pneumatic controls, while keeping the controls relatively simple for maintenance personnel to work with. ii. Upgrading controls would overlap with other recommended work described below so it is difficult to identify the savings and payback of this upgrade alone. However it is safe to assume that most of the energy savings for the project will be due to controls upgrades. An estimate of $40,000 would be reasonable, with a savings of about 15$20% and a pay back of approximately 4.5 years. b. Air Handler Controls i. Automated Schedules vs. Manual Control: The air handling units (identified as H&V units on the plans – referred to as HVU in this report) are designed to operate primarily using time clock schedules but are actually operated manually by the school maintenance personnel. The units should be operated automatically rather than manually in order to ensure they are running as needed and only when needed. Upgrading the building control system will make it simpler to provide this level of control and easier to Elim Aniguiin K-12 School Comprehensive Energy Audit 6 adjust equipment operating schedules as building use changes over time. ii. Carbon Dioxide (CO2) Monitoring: CO2 sensors can be utilized to help reduce the amount of outside air drawn into the building. Rather than supply a set minimum amount of outside air during HVU operation (20% of total HVU air volume, for example) the outside air can be varied to maintain the CO2 levels below a determined setpoint, typically 750 parts per million for schools. This often results in less outside air being drawn into the building, which reduces the amount of energy needed to heat the air. iii. The above changes to HVU control will provide an estimated 10$15% annual energy savings with an expected payback of approximately 1 year. c. Pumps i. The main constant volume heating circulations pumps for the school can be changed out for variable speed (VFD) pumps. VFD pumps can run at lower speeds when the school has a low heating demand, which will save power and reduce cost. The main circulation pump can also be turned off when there is no call for heating, rather than run continuously as it currently does. ii. The constant duty domestic water recirculation pump can be replaced with a pump that runs on a time clock and only operates during hours that it is needed. iii. The pump changes will provide about a 2% energy savings for the building with a payback of about 5.3 years. d. Reduce Thermostat Set Points: Many of the rooms in the building have problems overheating. As a result the building maintenance man has set the room temperatures at 60 degrees F. This kind of issue will likely be corrected with the control system upgrade mentioned previously. Nonetheless, even if the building controls were operating properly it does not appear that there are provisions in place to reduce the unoccupied temperatures of the building. It is recommended that the daytime space temperatures for Elim Aniguiin K-12 School Comprehensive Energy Audit 7 most spaces be set to 72 degrees F and that the nighttime setpoint be set to 60 degrees F. The lower nighttime setback will save approximately $8,346 per year. e. Add Occupancy Sensors for Lighting: Most of the interior, occupied spaces are equipped with occupancy sensors for operating lighting. However the kitchen, cafeteria and restrooms are not but can be provided with some. The annual lighting energy savings will be about 6% with a payback of approximately 5 years. f. Upgrade Exterior Lighting: There are 9 exterior wall mounted light fixtures that use high pressure sodium (HPS) lamps at 150 watts each and only operate during dark times of the year. It is recommended that the fixtures be replaced with light emitting diode (LED) fixtures. If the fixtures are replaced the energy savings for lighting only will be approximately 6.5% and have a payback of about 7.4 years. In addition to EEMs, various Energy Conservation Measures (ECMs) are recommended that were not part of the energy audit model. Some involve a modest capital investment. Others are policies or procedures that are followed by management and employees that require no capital outlay. Examples of recommended ECMs for this facility include: 1. Consider replacing Use infrared automatic lavatory faucets and water closet flush valves in all restrooms. 2. If automatic flushing is not desired then install water closet flushometer valves for dual level flushing. 3. Turn off computers, monitors, printers, faxes, coffee makers, etc when leaving the office for the day. Turn off computers, monitors, printers, faxes, coffee makers, etc., when leaving for the day. These devices can also be plugged into power strips equipped with occupancy sensors so they will automatically turn off when the building is not in use. 4. Provide occupancy sensors for unoccupied spaces such as bathrooms, storage spaces and utility rooms. The payback for this change may never be realized but the retrofit serves Elim Aniguiin K-12 School Comprehensive Energy Audit 8 to ensure that unseen lighting is not accidentally left on for long periods of time such as summer break. 5. Install an illuminated indicator to show if crawlspace lighting is on. It is not practical to install occupancy sensors in the crawlspace due to the large area. However small light bulbs or illuminated switchs could be installed on the walls just above the crawlspace access hatches to indicates if the lighting is on. This will help to reduce the likelihood of crawlspace lights accidentally being left on. 6. Disconnect refrigeration equipment over the summer, including walk$in units and residential style refrigerators throughout the building. This will save approximately $1,900/year. The priority recommendations in the detailed report are estimated to save $17,113/year, with an installed cost of $71,256, for a 4.2 year payback. This does not include design or CA services, but overall it does indicate a cost effective energy savings program. 3. Audit and Analysis Background: a. Program Description: This audit included services to identify, develop, and evaluate energy efficiency measures at the subject building. The scope of this project included evaluating the building shell, lighting, other electrical systems, and heating, ventilating, and air conditioning (HVAC) equipment. Measures were selected such that an overall simple payback period of 8 years or less could be achieved. b. Audit Description and Methodology: Preliminary audit information was gathered in preparation for the site survey, including benchmark utility consumption data, floor and lighting plans, and equipment schedules where available. A site visit was performed to inventory and evaluate the actual building condition, including: i. Building envelope (roof, windows, etc) ii. Heating, ventilating, and air conditioning iii. Lighting systems and controls iv. Building specific equipment Elim Aniguiin K-12 School Comprehensive Energy Audit 9 v. Plumbing systems c. Method of Analysis: The information gathered prior to the site visit and at the site visit is entered into AkWarm$C, an energy modeling developed for Alaska Housing Finance Corporation (AHFC) specifically to identify forecasted energy consumption which can be compared to actual energy consumption. AkWarm$C also has some pre$programmed EEM retrofit options that can be analyzed with energy savings forecasted based on occupancy schedules, utility rates, building construction type, building function, existing conditions, and climatic data that is already uploaded to the program based on the zip code of the building. When new equipment is proposed, energy consumption is calculated based on manufacturer’s cataloged information. Cost savings are calculated based on the historical energy costs for the building. Installation costs include labor and equipment to estimate the full up$front investment required to implement a change, but design and construction management costs are excluded. Costs are derived from Means Cost Data, industry publications, experience of the auditor, local contractors and equipment suppliers. Maintenance savings are calculated were applicable and are added to the energy savings for each EEM. The cost and savings are applied and a simple payback and simple return on investment (ROI) is calculated. The simple payback is based on the number of years that it takes for the savings to pay back the net installation cost (Net Installation divided by Net Savings.) A simple life$time calculation is shown for each EEM. The life$ time for each EEM is estimated based on the typical life of the equipment being replaced or altered. The energy savings is extrapolated throughout the life$time of the EEM. The total energy savings is calculated as the total life$time multiplied by the yearly savings. Elim Aniguiin K-12 School Comprehensive Energy Audit 10 d. Limitations of the Study: All results are dependent on the quality of input data provided, and can only act as an approximation. In some instances, several methods may achieve the identified savings. This report is not intended as a final design document. A design professional, licensed to practice in Alaska and in the appropriate discipline, who is following the recommendations, shall accept full responsibility and liability for the results. Budgetary estimates for engineering and design of these projects in not included in the cost estimate for each measure, but these costs generally run around 15% of the cost of the work. 4. Acknowledgements: We wish to acknowledge the help of numerous individuals who have contributed information that was used to prepare this report, including: a. Alaska Housing Finance Corporation (Grantor): AHFC provided the grant funds, contracting agreements, guidelines, and technical direction for providing the audits. AHFC reviewed and approved the final short list of buildings to be audited based on the recommendation of the Technical Service Provider (TSP). b. Bering Strait School District (Owner): The BSSD provided building access, original construction plans, two years energy billing data, building schedules and functions, as well as other resources needed to perform the audit. c. Central Alaska Engineering Company (Benchmark TSP): Central Alaska Engineering Company compiled the data received from the BSSD and entered that data into the statewide building database, called the Alaska Retrofit Information System (ARIS). d. Richard S. Armstrong, PE, LLC (Audit TSP): This is the TSP who was awarded the projects in the Arctic Slope Regional Corporation, Bering Straits area, and the Nana area. The firm gathered all relevant benchmark information provided to them, cataloged which buildings would have the greatest Elim Aniguiin K-12 School Comprehensive Energy Audit 11 potential payback, and prioritized buildings to be audited based on numerous factors, including the Energy Use Index (EUI), the Energy Cost Index (ECI), the age of the building, the size of the building, the location of the building, the function of the building, and the availability of plans for the building. They also trained their selected sub$contracted auditors, assigned auditors to the selected buildings, and performed quality control reviews of the resulting audits. They prepared a listing of potential EEMs that each auditor must consider, as well as the potential EEMs that the individual auditor may notice in the course of his audit. Richard S. Armstrong, PE, LLC also performed some of the audits to assure current knowledge of existing conditions. 5. Building Description and Function: The subject structure is called the Elim Aniguiin School, which was constructed in 2002. The building serves as a kindergarten through twelfth grade (K$12) educational facility, which includes classrooms, administrative offices, a commercial kitchen, a multi$purpose room/cafeteria, a gymnasium, locker rooms, vocational education room with shop, restrooms, and multiple storage and utility spaces. The building is a one story structure with an enclosed mechanical mezzanine above the locker rooms and an insulated crawlspace below the entire building footprint except the gymnasium. The gymnasium, student shop, and two classroom “commons” have high ceilings extending to the underside of the roof. Hallways have 9.5 feet ceilings. Classrooms, offices, locker rooms, the kitchen and various storage and utility rooms have ceilings heights ranging from 8 to 10 feet. The crawlspace averages about 3.25 feet in height and is about 75% below grade. The building roof and exterior walls are constructed of structural insulated panels (SIPs) and the exteriors are covered with metal roofing and metal siding respectively. The roof insulation value is approximately R$53 and the exterior walls approximately R$44. The overall building design and construction is similar to many schools that have been built in Western Alaska in the last 5 to 10 years. The building is in very good condition overall and appears to operate more or less as designed. The building is occupied from the middle of August through the middle of May. The school is unused during the summer months. Elim Aniguiin K-12 School Comprehensive Energy Audit 12 a. Heating System: The school heating plant is in a detached utility building located northwest and adjacent to the school on the school property. Heat is delivered to the school through a utilidor below grade that enters the school building in the north corner of the building under the Dry Storage room. The building heating system consists of two Burnham V$908A cast iron sectional boilers with Carlin model 702CRD, two$stage burners. The boilers provide heat to the school and utility buildings only. The boilers are original to the 2002 school construction. Hot glycol is circulated around the building using two Grundfos model UPS 50$240, 3$speed circulators, set at the highest speed, each with a 2 HP motor. A third pump is also installed as a back up in the event that one of the two main pumps goes down. The two main pumps operate in lead$ lag fashion. The lead pump operates by itself as long as it is able to maintain pressure and temperature within the heating loop. When the lead pump is not able to keep up by itself the lag pump runs. The pumps are not equipped with variable frequency drives (VFD), so they run at full speed when they operate. The lead pump runs constantly, year round. Heat is distributed throughout the building using fintube baseboard in most perimeter and some interior spaces, cabinet unit heaters in the gymnasium, vestibules, and crawlspace, unit heaters in utility spaces, and some supplemental heat through tempered ventilation air. b. Ventilation System: There are three air handlers in the building as well as multiple exhaust and relief fans. HVU$1 is the air handler that serves the classrooms and administrative spaces in the building. HVU$2 serves the multipurpose room and also provides make$up air for the kitchen cooking line exhaust hood. HVU$3 serves the gymnasium. RF$1 is the return/relief fan for HVU$1 and is interlocked to operate with that unit. RF$3 is the return/relief fan for HVU$3 and is interlocked to operate with that unit. EF$1 is the general building exhaust fan and is interlocked to operate with HVU$1. EF$2 is the cooking line exhaust hood fan and is interlocked to operate with HVU$2. Other exhaust fans include the commercial dishwasher hood, small restroom fan and (3) Elim Aniguiin K-12 School Comprehensive Energy Audit 13 residential range hoods. A wall$mounted propeller fan provides ventilation for the boiler utility building. Heating of ventilation (outside) air is a significant source of energy consumption for commercial buildings. State of Alaska design codes mandate that certain quantities of ventilation air must be provided. However, there are devices and strategies that can be employed to regulate the introduction of ventilation air so energy is not wasted, such as demand control ventilation based on CO2 concentration. c. Plumbing System: Water is provided from the village utility and there is not any on$site storage. Fixtures include water closets, lavatories, column style “gang” showers, classroom sinks, mop sinks, and large sinks for cooking. Most fixtures are located in bathrooms, locker rooms, custodial closets and the commercial kitchen. Classrooms for the younger elementary school children have adjoining water closets and lavatories as well as sinks in the classroom. d. Domestic Hot Water: How water is generated using three indirect water heaters, each with a holding capacity of 120 gallons. No additional hot water storage is provided. There is a hot water recirculation pump that runs constantly to provide instant hot water to remote fixtures. e. Lighting: Typical lighting used throughout occupied spaces in the building is provided with T$8 fluorescent fixtures using electronic ballasts and controlled with occupancy sensors. Most occupied rooms also have two toggle switches for two levels of lighting with minimum lighting levels at 30$50% depending on 3$ or 4$lamp fixtures. Occupancy sensors only turn on one level of lighting where two levels exist. The gymnasium has high bay lighting fixtures with (5) 2$tube, plug$ in, compact fluorescent bulbs at 55 watts each. Gymnasium lights are switched on manually. Exterior lights are high pressure sodium (HPS) fixtures and include wall packs (150 watts) and recess can canopy mounted (50 watts) fixtures. Exterior lights operate using daylight sensors. Elim Aniguiin K-12 School Comprehensive Energy Audit 14 f. Fire Sprinkler: The building is equipped with a fire sprinkler protection system throughout. A fire sprinkler water storage tank, approximately 10,000 gallons in capacity, is installed in the utility building. 6. Historic Energy Consumption: Energy consumption is modeled within the AkWarm$C program. The program only analyzes 12 months of data, so where 24 months of data are available, the data is averaged and input to AkWarm$C to provide more accuracy. The energy consumption data is presented and graphed in the attached AkWarm$C program results. Based on the benchmark energy data for 2009 and 2010, the average electric consumption for the building was 164,055 kWh/year at an average cost of $92,428/year. The average fuel oil consumption was 11,902 gallons/year, at an average annual cost of $41,806/year. 7. Energy Efficiency Measures Considered or Recommended: The building was examined for application of a multitude of potential EEMs that are discussed below. Those EEMs that appear to have an application for the subject building are further analyzed for estimated payback periods, either within the AkWarm$C program or separately within this report. The accuracy of the cost estimates and paybacks varies significantly due to a multitude of conditions, but is estimated to be approximately +/$ 25%. Assumptions made regarding energy costs and the life of the EEM, noting that post$construction measurement and verification are based on energy savings, not energy cost savings. Many of the selected EEMs are analyzed within the AkWarm$C program using the schedules and estimated costs input into the model. a. Exterior Lighting Upgrade: High$intensity discharge (HID) fixtures, such as high pressure sodium (HPS), are commonly used for building exterior lighting in Alaska because they perform well in cold weather and are more efficient than many other types of lighting. However, light emitting diode (LED) fixtures are proving to be a viable alternative to HPS. LED fixtures use nano reflector technology with drivers offering 50,000 hours life, about 6 years, as compared to only 20,000 Elim Aniguiin K-12 School Comprehensive Energy Audit 15 hours with high$intensity discharge (HID) fixtures. LED fixtures offer the instant$on feature of fluorescent fixtures but use significantly less energy than the HID fixtures. LEDs have an added benefit of operating more efficiently (using less power) as the ambient temperature gets colder, and some have been factory tested to operate down to $40 deg F (actual installations in Antarctica and Fairbanks indicate they operate at lower temperatures as well) depending on manufacturer. The proposed LED fixtures are dark sky compliant, using 100% cutoff optics to reduce light pollution. LEDs provide a different type of light than HPS, both in color and lumen output, that has the effect of providing a clearer, brighter light while using less power than a HPS bulb. The following chart indicates energy savings for various exterior building mounted light fixtures (MH Metal Halide; HSP High Pressure Sodium) using Scotopic lighting measurements: HID Lamp HID System Wattage LED System Wattage Energy Savings (%) 150W HPS 188W 54W 71 b. HVAC Control: The building HVAC system is operated using pneumatic controls. This method of control utilizes air in pressurized tubing to monitor environmental conditions and actuate equipment. The power behind the system is an air compressor that operates as needed to maintain pressure in the tubing. By its very nature a pneumatic control system has inherent inefficiencies, namely the need to continually re$ pressurize the system. As sensors and actuators operate they release air from the pressurized tubing, which is how they are designed to work. Loose fittings, damaged pipe, broken equipment all contribute to air escaping from the system. As a result the air compressor will operate intermittently throughout the life of the system. As the system’s integrity degrades over time more air leaks occur and the compressor operates more frequently. Failures in the system often leads to equipment “running wild” $ operating at full capacity with no ability to make Elim Aniguiin K-12 School Comprehensive Energy Audit 16 adjustments. This is likely the cause of the heating problem in a number of the classrooms, where the maintenance man reduced the space temperatures to 60 degrees F because occupants were complaining that the rooms were too hot. Under these circumstances occupants will typically open windows, which releases heat from the building and wastes energy. Pneumatic control systems require a level of training to operate and maintain that is difficult to provide to onsite personnel given the remote nature of the location and frequent and/or sudden turn over of maintenance staff. The remote location also makes it costly to hire contractors to come and maintain and/or repair the pneumatic control system. For these reasons it is recommended that the pneumatic control system be demolished and an electronic control system be installed. This will require the installation of new thermostats and sensors, actuators, valve motors, control panel(s) and low (24) voltage wiring throughout the building. Most of the wiring can be installed in the crawlspace and above suspended ceilings, making for a simpler installation and cleaner appearance. Pneumatic equipment that is being replaced will need to be removed. Items such as tubing and fittings that are out of site and not conflicting with new equipment can be abandoned in place. c. Ventilation Control: The air handling units (HVU) serving the various school spaces were designed to function using time clocks and electrical connections with other fans. Even though the time clocks appear to be functional the HVUs are operated manually, turned on and off daily by maintenance personnel based on their knowledge of space occupancy. This creates two problems. First, in the event that a unit is not turned on the school will not have adequate ventilation air, which will affect occupant comfort and performance. Second, if a unit is left on outside of school hours it is a waste of energy. There are two adjustments that can be made at the same time that will improve control of the HVUs. i. Operation Schedules: Each of the HVUs serves a space (or spaces) with unique occupancy schedules. Elim Aniguiin K-12 School Comprehensive Energy Audit 17 During the course of the audit the time clocks were observed and it appeared that there were two programmed schedules in use; one for the classrooms and administration and the other for the gymnasium. What was most significant about the scheduling was that it did not accurately track the hours that the spaces were in use. In order to reduce the amount of electric and heating energy used by the HVUs the following scheduling changes are recommended: 1. HVU1, Classrooms and Administration – Operate the unit only during school hours. 2. HVU2, Kitchen Exhaust MakeUp Air – This unit is interlocked with the kitchen cooking hood exhaust fan, EF$2, to serve as make$up air. It can also be operated independent of EF$2 using a spring wound manual override timer located in the multi$purpose room. The existing timer should be replaced with an electronic timer and provided with a locking cover so it can only be operated by building staff. The spring in the spring wound timer will eventually fail and the timer will no longer shut off automatically, making it possible for the HVU to “run wild” if not manually turned off. 3. HVU3, Gymnasium – Operate the unit during known periods of occupancy such as lunch hours and scheduled “open gym” hours. The existing spring wound manual override timer in the gymnasium should be replaced with an electronic timer and provided with a locking cover so it can only be operated by building staff. ii. Carbon Dioxide (CO2) Monitoring: The amount of CO2 in a building has been shown to have a direct effect on the performance of the occupants in the building. High levels of CO2 cause occupants to feel sleepy and lose concentration. It is also an indication that other indoor Elim Aniguiin K-12 School Comprehensive Energy Audit 18 contaminants, such as volatile organic compounds (VOCs), odors and excessive humidity are likely increasing in concentration. For these reasons ventilation air is required by code to refresh indoor building air. Typically the ventilation rate is determined based on the number of occupants and space sizes. In many cases this over$ventilates the space. Another method of ventilating spaces is called demand control ventilation, which entails varying the amount of outside air supplied based on CO2 levels in the building. Sensors can be placed in spaces throughout the building (preferred) or in the return air duct at the HVUs, and the HVU outside air dampers can be modulated to increase or decrease the outside air delivered to the building. This modification applies specifically to HVU$3 and may also be appropriate for HVU$1. d. VFD Heating Pumps: In most cases heating circulators are designed for greater flow rates than is needed during normal operation. Bypass valves are installed to allow the constant volume of flow to continue even when a small amount of that flow is providing heat. Energy is wasted circulating heated glycol that is not needed. There are a number of pumps on the market that have variable frequency drives (VFD), which allow the speed of the motor to be adjusted to match the flow rate demand. Pump affinity laws show that motor speed and power have a cubic mathematical relationship to each other. As the pump speed is reduced “X” RPM the power consumption is reduced by X1/3 watts (or horsepower), showing that a small change in pump speed has an amplified affect on power input. Operating pumps at lower speeds when there is lower flow demand significantly reduces power consumption. It is recommended that the heating circulators be replaced with VFD pumps so power savings can be realized. e. Boiler Temperature Outdoor Air Reset: As the outside air temperature varies building heat loss varies as well, losing heat at a faster rate as the ambient temperature drops. Boiler systems are typically sized to meet the heating demands of the Elim Aniguiin K-12 School Comprehensive Energy Audit 19 coldest expected temperatures. These extreme temperatures may only occur for short durations in a given winter and will vary in frequency and length year to year. Most cast iron sectional boilers supply heating water at the same temperature year$round. During periods of warmer weather in the heating season high heating water supply temperatures may cause space temperatures to overshoot setpoints because the hot boiler water dumps heat into the building at a faster rate than the building is losing it, leading to occupant discomfort. This will also cause the boilers to cycle more often since it takes less time to heat the returning water, putting unnecessary ware on the boilers. A common way of handling this issue is to use an outdoor reset controller to reduce the heating loop temperature so that heat is transferred into the building closer to the rate at which the building is losing heat. Outdoor reset varies the boiler or heating loop water temperature based on the ambient temperature – increasing the water temperature when outdoor conditions are cold and decreasing water temperature for warmer outdoor conditions. It was observed on site that maintenance personnel were manually adjusting the boiler temperature to give the same effect. In order to maintain tighter control and prevent issues such as setting the boiler temperature too low (causing the boiler to condense or providing inadequate heating water temperatures for the hot water generators), or forgetting to reset the boiler temperature, it is recommended that a controller be installed that will perform the outdoor reset automatically. There is not a provision for simulating this in the AkWarm$C program so no energy savings are considered here. However it is recommended that a licensed professional engineer perform the design for installation of this controller at which time an energy savings analysis could be performed. f. Domestic Hot Water Recirculation: The domestic hot water system is provided with a small pump that circulates the hot water loop back to the water heater so there is always hot water available at the furthest fixtures in the building. This pump operates constantly, which is unnecessary since hot water is only needed during building occupancy. It is Elim Aniguiin K-12 School Comprehensive Energy Audit 20 recommended that controls be provide for the hot water recirculation pump so it will only run during school hours, which will reduce the energy consumed by the pump. g. Waste Heat: The school building is not currently supplied with waste heat. However the school is roughly 0.5 miles from the village power utility. If the school was supplied with waste heat from the village power plant it would have a tremendous impact on energy savings for the school, likely surpassing fuel oil as the primary heating source. Connecting the school heating plant to the village power plant would require a large capital investment but could have a payback of 10$15 years. No investigation has been performed on the amount of heat that would be available from the power plant, which would require a thorough engineering analysis. It is recommended that a preliminary investigation be performed to determine the viability of this option. h. Fuel Oil Metering: It is recommended that fuel oil meters be installed to track the amount of fuel used by the boilers and electric generator. The only methods currently used on site for tracking fuel usage are recording the amount of fuel put into bulk fuel storage tanks when they are refilled and maintenance personnel manually recording the fuel levels in the tanks. Neither method is able to provide precise information nor does it give a detailed picture of the rate at which fuel is used. In order to understand current and future fuel consumption, a fuel meter should be installed on the boiler fuel line and another on the generator fuel line. The Pathfinder Instruments FM$200 meter is for fuel pipes sized ¾” to 1” (different meters, must specify pipe size), and they cost around $225 each. They operate at a flow range of 4$20 GPM. These are mechanical meters with strainers and 3$digid display that shows both present fuel use, and cumulative fuel use. This information can be tied into the building DDC system and saved as trend log data and/or the meter can have an analog dial for visual inspection. Any ESCO contract, or AHFC financed contract will require fuel metering to verify paybacks of energy conservation measures. Electronic turbine meters are also Elim Aniguiin K-12 School Comprehensive Energy Audit 21 available. See pathfinderinstruments.com for product information. 8. Interactive Effects of Projects: The AkWarm$C program calculates savings assuming that all recommended EEM are implemented. If some EEMs are not implemented, savings for the remaining EEMs will be affected, in some cases positively, and in others, negatively. For example, if the fan motors are not replaced with premium efficiency motors, then the savings for the project to install variable speed drives (VFDs) on the fans will be increased. In general, all projects were evaluated sequentially so that energy savings associated with one EEM would not be attributed to another EEM as well. For example, the night setback EEM was analyzed using the fan and heating load profile that will be achieved after installation of the VFD project is completed. By modeling the recommended projects sequentially, the analysis accounts for interactive effects between the EEMs and does not “double count” savings. Interior lighting, plug loads, facility equipment, and occupants generate heat within the building. When the building is in cooling mode, these contribute to the overall cooling demands of the building; therefore lighting efficiency improvements will reduce cooling requirements on air conditioned buildings. Conversely, lighting efficiency improvements are anticipated to increase heating requirements slightly. Heating penalties are included in the lighting project analysis that is performed by AkWarm$C. 9. Loan Program: The Alaska Housing Finance Corporation (AHFC) Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State of Alaska program enacted by the Alaska Sustainable Energy Act (senate Bill 220, A.S. 18.56.855, “Energy Efficiency Revolving Loan Fund). The AEERLF will provide loans for energy efficiency retrofits to public facilities via the Retrofit Energy Assessment for Loan System (REAL). As defined in 15 AAC 155.605, the program may finance energy efficiency improvements to buildings owned by: a. Regional educational attendance areas; Elim Aniguiin K-12 School Comprehensive Energy Audit 22 b. Municipal governments, including political subdivisions of municipal governments; c. The University of Alaska; d. Political subdivisions of the State of Alaska, or e. The State of Alaska Native corporations, tribal entities, and subsidiaries of the federal government are not eligible for loans under this program. Elim Aniguiin K-12 School Comprehensive Energy Audit 23 Appendix A: Photos Main Entrance and Classrooms Southwest entrance Elim Aniguiin K-12 School Comprehensive Energy Audit 24 Southwest wall of Gymnasium, Northwest Classrooms Northwest wall of Gymnasium Elim Aniguiin K-12 School Comprehensive Energy Audit 25 Multipurpose Room, Kitchen, Gymnasium in background, Utility Building, Northeast view Kindergarten Classroom, Northeast view Elim Aniguiin K-12 School Comprehensive Energy Audit 26 Typical Classroom Elim Aniguiin K-12 School Comprehensive Energy Audit 27 Gymnasium, Southwest wall Gymnasium, Southeast wall with HVU3 ductwork Elim Aniguiin K-12 School Comprehensive Energy Audit 28 Kitchen cooking equipment under exhaust hood Kitchen dish washing equipment Elim Aniguiin K-12 School Comprehensive Energy Audit 29 Kitchen walk in refrigerator and freezer Typical Fan Room air handler (HVU2 shown) Elim Aniguiin K-12 School Comprehensive Energy Audit 30 Indirect Hot Water Heaters in Fan Room (three total) HVAC pneumatic control panel and air compressor in Fan Room Elim Aniguiin K-12 School Comprehensive Energy Audit 31 Pneumatic control panel Air compressor Elim Aniguiin K-12 School Comprehensive Energy Audit 32 Utility Building, Northeast and Southeast walls, intermediate fuel tank Utility Building, Northwest and Southwest walls Elim Aniguiin K-12 School Comprehensive Energy Audit 33 Heating Boilers and Circulation Pumps in Utility Building Elim Aniguiin K-12 School Comprehensive Energy Audit 34 Elim Village, Aerial View Village Power Utility School Elim Aniguiin K-12 School Comprehensive Energy Audit 35 Appendix B: AK Warm Energy Model Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 3 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 1 Refrigeration: Walk in Refrigerator/Freezer Add new Seasonal Shutdown $780 $1 4432.63 0 2 Refrigeration: Domestic Refrigerator 2-door Add new Seasonal Shutdown $240 $1 1535.25 0 3 Refrigeration: Mobile refrigerator in kitchen Add new Seasonal Shutdown $130 $1 735.63 0 4 Setback Thermostat: 134 Gymnasium Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 134 Gymnasium space. $1,250 $750 25.01 0.6 5 Setback Thermostat: 146 Science Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 146 Science Classroom space. $561 $750 11.22 1.3 6 Setback Thermostat: 148 Social Studies Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 148 Social Studies Classroom space. $531 $750 10.62 1.4 7 Setback Thermostat: 108 Primary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108 Primary Classroom space. $525 $750 10.50 1.4 8 Setback Thermostat: 110 Kindergarten Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 110 Kindergarten Classroom space. $517 $750 10.35 1.5 9 Other Electrical: Air Compressor Replace with Demolished $840 $500 9.59 0.6 10 Setback Thermostat: 126 Dry Storage Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 126 Dry Storage space. $462 $750 9.25 1.6 11 Setback Thermostat: 141 Itinerant Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 141 Itinerant Classroom space. $446 $750 8.93 1.7 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 4 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 12 Setback Thermostat: 153 Library Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 153 Library space. $313 $750 6.26 2.4 13 Setback Thermostat: 107 Intermediate Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 107 Intermediate Classroom space. $306 $750 6.13 2.4 14 Setback Thermostat: 109 Primary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 109 Primary Classroom space. $285 $750 5.70 2.6 15 Lighting: Kitchens, Type B - Lithonia 2SP-GB-432-A12125- 120-GEB10 Remove Manual Switching and Add new Occupancy Sensor $409 $500 5.22 1.2 16 Setback Thermostat: 106 intermediate Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 106 intermediate Classroom space. $250 $750 5.01 3 17 Setback Thermostat: 120 Cafeteria Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 120 Cafeteria space. $248 $750 4.97 3 18 Setback Thermostat: 121 Kitchen Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 121 Kitchen space. $220 $750 4.41 3.4 19 Setback Thermostat: 138 Bi-Cultural Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 138 Bi-Cultural Classroom space. $203 $750 4.06 3.7 20 Setback Thermostat: 149 Language Arts Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 149 Language Arts Classroom space. $200 $750 4.00 3.8 21 Setback Thermostat: 147 Mathematics Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 147 Mathematics Classroom space. $166 $750 3.32 4.5 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 5 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 22 Setback Thermostat: 150 Computer Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 150 Computer Classroom space. $158 $750 3.16 4.8 23 Setback Thermostat: 140 Home Ec. Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 140 Home Ec. Classroom space. $128 $750 2.56 5.9 24 Setback Thermostat: 104 CSLs Office Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 104 CSLs Office space. $118 $750 2.37 6.3 25 Setback Thermostat: 151 Conference Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 151 Conference Room space. $112 $750 2.24 6.7 26 HVAC And DHW Change heat loop circ. pumps to VFD, run domestic hot water recirc. pump on time clock or temp. sensor $3,766 $20,000 2.18 5.3 27 Setback Thermostat: 139 Special Needs Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 139 Special Needs Classroom space. $118 $750 2.36 6.3 28 Setback Thermostat: 125 Customer Loading Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the 125 Customer Loading space. $96 $750 1.93 7.8 29 Setback Thermostat: 102 Reception Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 102 Reception space. $96 $750 1.91 7.8 30 Setback Thermostat: 103 Principal Office Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 103 Principal Office space. $93 $750 1.86 8 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 6 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 31 Lighting: Restrooms, Type H - Lithonia VDS232-120-GEB10- WL Remove Manual Switching and Add new Occupancy Sensor $1,291 $4,750 1.74 3.7 32 Lighting: Kitchens, Type B - Lithonia 2SP-GB-432-A12125- 120-GEB10 Remove Manual Switching and Add new Occupancy Sensor $124 $500 1.44 4 33 Lighting: Caffetria, Type O - Linear D675-B-2T8-120- PBL-C60-BW-GEB10- 8' Remove Manual Switching and Add new Occupancy Sensor $111 $500 1.41 4.5 34 Setback Thermostat: 118 Corridor Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 118 Corridor space. $59 $750 1.18 12.7 35 Lighting: Exterior Wall Mount, Type M - Lithonia TWP-150S- 120-SF-70F Replace with 9 LED 72W Module StdElectronic $1,827 $13,500 0.86 7.4 36 Lighting: Cafeteria, Type O - Linear D675-B-2T8-120- PBL-C60-BW-GEB10- 8' Remove Manual Switching and Add new Occupancy Sensor $64 $500 0.74 7.8 37 Setback Thermostat: 101 Main Commons Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 101 Main Commons space. $31 $750 0.62 24.2 38 Lighting: Restrooms, Type H - Lithonia VDS232-120-GEB10- WL Remove Manual Switching and Add new Occupancy Sensor $23 $250 0.54 10.8 39 Setback Thermostat: 144 Corridor Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 144 Corridor space. $10 $750 0.19 77.5 40 Lighting: Exercise, Type O - Linear D675-B-2T8-120- PBL-C60-BW-GEB10- 8' Remove Manual Switching and Add new Occupancy Sensor $6 $250 0.16 39.6 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 7 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 41 Setback Thermostat: 111 Elementary Commons Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 111 Elementary Commons space. $0 $750 0.00 Infinity 42 Setback Thermostat: 114 Girls Restroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 114 Girls Restroom space. $0 $750 0.00 Infinity 43 Setback Thermostat: 116 Boys Restroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 116 Boys Restroom space. $0 $750 0.00 Infinity 44 Setback Thermostat: 105 Faculty Workroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 105 Faculty Workroom space. $0 $750 0.00 Infinity 45 Setback Thermostat: 128 Exercise Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 128 Exercise Room space. $0 $750 0.00 Infinity 46 Setback Thermostat: 127 Kitchen Administration Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 127 Kitchen Administration space. $0 $750 0.00 Infinity 47 Setback Thermostat: 132 Boys Locker Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 132 Boys Locker Room space. $0 $750 0.00 Infinity 48 Setback Thermostat: 133 Mens Toilet Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 133 Mens Toilet space. $0 $750 0.00 Infinity 49 Setback Thermostat: 135 Womens Toilet Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 135 Womens Toilet space. $0 $750 0.00 Infinity Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 8 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 50 Setback Thermostat: 136 Girls Locker Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 136 Girls Locker Room space. $0 $750 0.00 Infinity 51 Setback Thermostat: 156 Girls Bathroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 156 Girls Bathroom space. $0 $750 0.00 Infinity 52 Setback Thermostat: 158 Boys Bathroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 158 Boys Bathroom space. $0 $750 0.00 Infinity 53 Setback Thermostat: 154 High School Commons Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 154 High School Commons space. $0 $750 0.00 Infinity 54 Refrigeration: Walk in Refrigerator/Freezer Replace with Walk in refrigerator/freezer $0 $1 0.00 Infinity 55 Refrigeration: Mobile refrigerator in kitchen Replace with Mobile refrigerator in kitchen $0 $1 0.00 Infinity 56 Refrigeration: Domestic Refrigerator 2-door Replace with 4 Domestic Refrigerator 2-door $0 $1 0.00 Infinity TOTAL $17,113 $71,256 2.7 4.2 ENERGY AUDIT REPORT – ENERGY EFFICIENT RECOMMENDATIONS 1. Building Envelope Insulation Rank Location Existing Type/R:Value Recommendation Type/R: Value Installed Cost Annual Energy Savings Exterior Doors – Replacement Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 9 Windows and Glass Doors – Replacement Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Air Leakage Rank Location Estimated Air Leakage Recommended Air Leakage Target Installed Cost Annual Energy Savings 2. Mechanical Equipment Mechanical Rank Recommendation Installed Cost Annual Energy Savings 26 Change heat loop circ. pumps to VFD, run domestic hot water recirc. pump on time clock or temp. sensor $20,000 $3,766 Setback Thermostat Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings 4 134 Gymnasium Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 134 Gymnasium space. $750 $1,250 5 146 Science Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 146 Science Classroom space. $750 $561 6 148 Social Studies Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 148 Social Studies Classroom space. $750 $531 7 108 Primary Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108 Primary Classroom space. $750 $525 8 110 Kindergarten Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 110 Kindergarten Classroom space. $750 $517 10 126 Dry Storage Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 126 Dry Storage space. $750 $462 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 10 11 141 Itinerant Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 141 Itinerant Classroom space. $750 $446 12 153 Library Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 153 Library space. $750 $313 13 107 Intermediate Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 107 Intermediate Classroom space. $750 $306 14 109 Primary Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 109 Primary Classroom space. $750 $285 16 106 intermediate Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 106 intermediate Classroom space. $750 $250 17 120 Cafeteria Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 120 Cafeteria space. $750 $248 18 121 Kitchen Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 121 Kitchen space. $750 $220 19 138 Bi-Cultural Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 138 Bi-Cultural Classroom space. $750 $203 20 149 Language Arts Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 149 Language Arts Classroom space. $750 $200 21 147 Mathematics Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 147 Mathematics Classroom space. $750 $166 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 11 22 150 Computer Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 150 Computer Classroom space. $750 $158 23 140 Home Ec. Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 140 Home Ec. Classroom space. $750 $128 24 104 CSLs Office Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 104 CSLs Office space. $750 $118 25 151 Conference Room Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 151 Conference Room space. $750 $112 27 139 Special Needs Classroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 139 Special Needs Classroom space. $750 $118 28 125 Customer Loading Existing Unoccupied Heating Setpoint: 60.0 deg F Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the 125 Customer Loading space. $750 $96 29 102 Reception Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 102 Reception space. $750 $96 30 103 Principal Office Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 103 Principal Office space. $750 $93 34 118 Corridor Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 118 Corridor space. $750 $59 37 101 Main Commons Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 101 Main Commons space. $750 $31 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 12 39 144 Corridor Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 144 Corridor space. $750 $10 41 111 Elementary Commons Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 111 Elementary Commons space. $750 $0 42 114 Girls Restroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 114 Girls Restroom space. $750 $0 43 116 Boys Restroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 116 Boys Restroom space. $750 $0 44 105 Faculty Workroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 105 Faculty Workroom space. $750 $0 45 128 Exercise Room Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 128 Exercise Room space. $750 $0 46 127 Kitchen Administration Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 127 Kitchen Administration space. $750 $0 47 132 Boys Locker Room Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 132 Boys Locker Room space. $750 $0 48 133 Mens Toilet Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 133 Mens Toilet space. $750 $0 49 135 Womens Toilet Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 135 Womens Toilet space. $750 $0 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 13 50 136 Girls Locker Room Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 136 Girls Locker Room space. $750 $0 51 156 Girls Bathroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 156 Girls Bathroom space. $750 $0 52 158 Boys Bathroom Existing Unoccupied Heating Setpoint: 68.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 158 Boys Bathroom space. $750 $0 53 154 High School Commons Existing Unoccupied Heating Setpoint: 65.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 154 High School Commons space. $750 $0 Ventilation Rank Recommendation Cost Annual Energy Savings 3. Appliances and Lighting Lighting Fixtures and Controls Rank Location Existing Recommended Installed Cost Annual Energy Savings 15 Kitchens, Type B - Lithonia 2SP-GB- 432-A12125-120- GEB10 19 FLUOR (4) T8 4' F32T8 32W Standard (2) Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $500 $409 31 Restrooms, Type H - Lithonia VDS232- 120-GEB10-WL 32 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $4,750 $1,291 32 Kitchens, Type B - Lithonia 2SP-GB- 432-A12125-120- GEB10 10 FLUOR (4) T8 4' F32T8 32W Standard (2) Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $500 $124 33 Caffetria, Type O - Linear D675-B-2T8- 120-PBL-C60-BW- GEB10-8' 6 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $500 $111 35 Exterior Wall Mount, Type M - Lithonia TWP-150S- 120-SF-70F 9 HPS 150 Watt Magnetic with Daylight Sensor Replace with 9 LED 72W Module StdElectronic $13,500 $1,827 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Elim Aniguiin School Page 14 36 Cafeteria, Type O - Linear D675-B-2T8- 120-PBL-C60-BW- GEB10-8' 6 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $500 $64 38 Restrooms, Type H - Lithonia VDS232- 120-GEB10-WL FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $250 $23 40 Exercise, Type O - Linear D675-B-2T8- 120-PBL-C60-BW- GEB10-8' 6 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $250 $6 Refrigeration Rank Location Existing Recommended Installed Cost Annual Energy Savings 1 Walk in Refrigerator/Freeze r Walk in refrigerator/freezer Add new Seasonal Shutdown $1 $780 2 Domestic Refrigerator 2-door 4 Domestic Refrigerator 2-door Add new Seasonal Shutdown $1 $240 3 Mobile refrigerator in kitchen Mobile refrigerator in kitchen Add new Seasonal Shutdown $1 $130 54 Walk in Refrigerator/Freeze r Walk in refrigerator/freezer Replace with Walk in refrigerator/freezer $1 $0 55 Mobile refrigerator in kitchen Mobile refrigerator in kitchen Replace with Mobile refrigerator in kitchen $1 $0 56 Domestic Refrigerator 2-door 4 Domestic Refrigerator 2-door Replace with 4 Domestic Refrigerator 2-door $1 $0 Other Electrical Equipment Rank Location Existing Recommended Installed Cost Annual Energy Savings 9 Air Compressor Quincy Air Control with Other Controls Replace with Demolished $500 $840 Cooking/Clothes Drying Rank Recommended Installed Cost Annual Energy Savings Elim Aniguiin K-12 School Comprehensive Energy Audit 48 Appendix C: Existing Plans