Loading...
HomeMy WebLinkAboutBSSD-SKK-RSA Shaktoolik School 2012-EERichard S. Armstrong, PE, LLC Mechanical/Electrical Engineer Comprehensive Energy Audit of Shaktoolik K12 School Shaktoolik, Alaska Project # BSSDSKKRSA01 Prepared for: Bering Strait School District Contact: Richard Ried, Maintenance Supervisor Phone: 9076244249 Unalakleet, Alaska April 9, 2012 Prepared by: Richard S. Armstrong, PE, LLC 2321 Merrill Field Drive, C$6 Anchorage, AK 99501 and RSA Engineering, Inc. 2422 Arctic Blvd., Suite 200 Anchorage, AK 99503 Shaktoolik K-12 School Comprehensive Energy Audit 2 TABLE OF CONTENTS 1. Report Disclaimers 3 2. Executive Summary 4 3. Audit and Analysis Background 8 4. Acknowledgements 10 5. Building Description & Function 11 6. Historic Energy Consumption 14 7. Energy Efficiency Measures Considered or Recommended 14 8. Interactive Effects of Projects 20 9. Loan Program 20 Appendix A: Photos 22 Appendix B: AkWarm7C Report 34 Appendix C: Building Schedules and Plans 47 Performed by: ___________________________ Adam W. Wilson, PE, CEA CEA # 1618 RSA Engineering, Inc. Reviewed by: ___________________________ Richard Armstrong, PE, CEM CEA #178, CEM # 13557 Shaktoolik K-12 School Comprehensive Energy Audit 3 1. REPORT DISCLAIMERS The information contained in this report, including any attachments, is intended solely for use by the building owner and the AHFC. No others are authorized to disclose, copy, distribute or retain this report, in whole or part, without written authorization from Richard S. Armstrong, PE, LLC, 2321 Merrill Field Drive, C$6, Anchorage, AK 99501. Additionally, this report contains recommendations that, in the opinion of the auditor, will cause the owner to realize energy savings over time. All recommendations must be designed by a registered engineer, licensed in the State of Alaska, in the appropriate discipline. Lighting recommendations should all be first reviewed by running a lighting analysis to assure that the recommended lighting upgrades will comply with State of Alaska Statue as well as IES recommendations. Payback periods may well vary from those forecast due to the uncertainty of the final installed design, configuration, equipment selected, and installation costs of recommended Energy Efficiency Measures (EEMs), or the operating schedules and maintenance provided by the owner. Furthermore, EEMs are typically interactive, so implementation of one EEM may impact the cost savings from another EEM. Neither the auditor, Richard S. Armstrong, PE, LLC, AHFC, or others involved in preparation of this report will accept liability for financial loss due to EEMs that fail to meet the forecasted payback periods. This audit meets the criteria of an Investment Grade Audit (IGA) per the Association of Energy Engineers definition, and is valid for one year. The life of the IGA may be extended on a case$by$case basis, at the discretion of the AHFC. IGSs are the property of the State, and may be incorporated into AkWarm$ C, the Alaska Energy Data Inventory (ARIS), or other state and/or public information system. Shaktoolik K-12 School Comprehensive Energy Audit 4 Investment Grade Energy Audit Shaktoolik K12 School 2. Executive Summary: The Shaktoolik K$12 School was constructed in 1980. It is owned and operated by the Bering Strait School District (BSSD). The school will be remodeled starting in the summer of 2012, with completion expected at the end of 2013. Recommendations made in this report may or may not be necessary or appropriate depending on the result of the remodel. It is assumed that all new construction and equipment will be provided in accordance with current codes, which will significantly increase the overall building energy efficiency from the original school construction. This audit will serve as an energy benchmark against which the new building can be compared if the owner so chooses. Current benchmark energy use data collected for this building is presented in Table 1 below: Table 1 2009 2009 2010 2010 Utility Consumption Cost/Year Consumption Cost/Year Electricity$kWh 120,804 $ 73,068 65,377 $ 55,452 No. 2 Fuel Oil $ Gallons 11,477 $ 47,667 5,553 $ 17,352 Ttl Energy Costs $120,735 $ 72,804 A benchmark measure of energy use relative to other similar function buildings in the area is the Energy Use Index (EUI), which takes the total annual energy used by the facility divided by the square footage area of the building, for a value expressed in terms of kBTU/SF. This number can then be compared to other buildings to see if it is about average, higher or lower than similar buildings in the area. Likewise, the Energy Cost Index (ECI) is the cost of all energy used by the building expressed in $/SF of building area. The comparative values for the subject building are listed in Table 2 below: Shaktoolik K-12 School Comprehensive Energy Audit 5 Table 2 Shaktoolik K$12 School Unalakleet Elementary & High Schools (neighboring village) Average for All BSSD Schools Energy Use Index (EUI) kBTU/SF Avg 2009, 2010 87.8 106.2 125.3 Energy Cost Index (ECI) Average 2009, 2010 $5.89 $4.84 $6.73 Various Energy Efficiency Measures (EEMs) have been analyzed for this building to determine if they would be applicable for energy savings with reasonably good payback periods. Those EEMs that have a payback period or those that are recommended for code compliance, life cycle replacement, or other reasons are also included. Specific EEMs recommended for this facility are detailed in the attached AkWarm Energy Audit Report along with specific payback times, as well as estimated installation costs and estimated energy savings. The higher priority items are summarized below: a. Air Handler Controls i. Individual Control for Fans: The main air handler, make$up air unit, and restroom exhaust fan for the facility are all operated using a single time clock. Each piece of equipment should be controlled using a dedicated controller so they can be programmed to operate only when necessary. New controls should include operation of control dampers and control valves and may require installation of new sensors to help with temperature controls. ii. Carbon Dioxide (CO2) Monitoring: CO2 sensors can be utilized to help reduce the amount of outside air drawn into the building. Rather than supply a set minimum amount of outside air during air handler operation (20% of total supply air volume, for example) the outside air can be varied to maintain the CO2 levels below a determined set point, typically 750 parts per million for schools. This often results in less Shaktoolik K-12 School Comprehensive Energy Audit 6 outside air being drawn into the building, which reduces the amount of energy needed to heat the air. iii. The above changes to ventilation control will provide an estimated 6$10% annual energy savings with an expected payback of approximately 8 years. b. Pumps i. The main constant volume heating circulations pumps for the school can be changed out for one variable speed (VFD) pump (presumably two would be provided for one to serve as a backup). VFD pumps can run at lower speeds when the school has a low heating demand, which will save power and reduce cost. The main circulation pump can also be turned off when there is no call for heating, rather than run continuously as it currently does. ii. The constant duty domestic hot water recirculation pump can be replaced with a pump that runs on a time clock and only operates during hours that it is needed. iii. The pump changes will provide about a 3$5% energy savings for the building with a payback of about 8.5 years. c. Install Programmable Thermostats: Non$programmable thermostats in occupied spaces in the building can be replaced with programmable thermostats to allow for automatically reducing space temperatures when they are unoccupied. Recommended set points are 68$72 deg. F during occupancy and 60 deg. F when unoccupied. This will provide an energy savings of about 6$10% with an expected payback of 1 year. d. Interior Lighting Upgrade: Most of the facility lighting is provided with T12 fluorescent fixtures. It is recommended that all of these fixtures be retrofitted with new ballasts so they can operate using T8 fluorescent bulbs, which are more efficient. The anticipated energy savings is around 3$ 5% with a payback of about 6.5 years. e. Occupancy Sensors for Interior Lighting: Lighting is controlled throughout the building using wall$mounted toggle switches. It is recommended that all lights be Shaktoolik K-12 School Comprehensive Energy Audit 7 equipped with occupancy sensors to reduce the amount of time the lights are on when the spaces are unoccupied. The annual energy savings will be about 3$5% with a payback of approximately 6.5 years. f. Exterior Lighting Upgrade: There are six exterior wall mounted light fixtures, and six recess can type, that use high pressure sodium (HPS) lamps and only operate during dark times of the year. It is recommended that the fixtures be replaced with light emitting diode (LED) fixtures. If the fixtures are replaced the energy savings for lighting will be approximately 2% and have a payback of about 8 years. In addition to EEMs, various Energy Conservation Measures (ECMs) are recommended that were not part of the energy audit model. Some involve a modest capital investment. Others are policies or procedures that are followed by management and employees that require no capital outlay. Examples of recommended ECMs for this facility include: 1. Use infrared automatic lavatory faucets and water closet flush valves in all restrooms. 2. If automatic flushing is not desired then install water closet flushometer valves for dual level flushing. 3. Turn off computers, monitors, printers, faxes, coffee makers, etc when leaving the office for the day. Turn off computers, monitors, printers, faxes, coffee makers, etc., when leaving for the day. These devices can also be plugged into power strips equipped with occupancy sensors so they will automatically turn off when the building is not in use. 4. Provide occupancy sensors for unoccupied spaces such as bathrooms, storage spaces and utility rooms. The payback for this change may never be realized but the retrofit serves to ensure that unseen lighting is not accidentally left on for long periods of time such as summer break. 5. Disconnect refrigeration equipment over the summer, including walk$in units and residential style refrigerators throughout the building. This will save approximately $415/year. Shaktoolik K-12 School Comprehensive Energy Audit 8 The priority recommendations in the detailed report are estimated to save $24,763/year, with an installed cost of $132,179, for a 5.3 year payback. This does not include design or CA services, but overall it does indicate a cost effective energy savings program. 3. Audit and Analysis Background: a. Program Description: This audit included services to identify, develop, and evaluate energy efficiency measures at the subject building. The scope of this project included evaluating the building shell, lighting, other electrical systems, and heating, ventilating, and air conditioning (HVAC) equipment. Measures were selected such that an overall simple payback period of 8 years or less could be achieved. b. Audit Description and Methodology: Preliminary audit information was gathered in preparation for the site survey, including benchmark utility consumption data, floor and lighting plans, and equipment schedules where available. A site visit was performed to inventory and evaluate the actual building condition, including: i. Building envelope (roof, windows, etc) ii. Heating, ventilating, and air conditioning iii. Lighting systems and controls iv. Building specific equipment v. Plumbing systems c. Method of Analysis: The information gathered prior to the site visit and at the site visit is entered into AkWarm$C, an energy modeling developed for Alaska Housing Finance Corporation (AHFC) specifically to identify forecasted energy consumption which can be compared to actual energy consumption. AkWarm$C also has some pre$programmed EEM retrofit options that can be analyzed with energy savings forecasted based on occupancy schedules, utility rates, building construction type, building function, existing conditions, and climatic data that is already uploaded to the program based on the zip code of the building. When new equipment is Shaktoolik K-12 School Comprehensive Energy Audit 9 proposed, energy consumption is calculated based on manufacturer’s cataloged information. Cost savings are calculated based on the historical energy costs for the building. Installation costs include labor and equipment to estimate the full up$front investment required to implement a change, but design and construction management costs are excluded. Costs are derived from Means Cost Data, industry publications, experience of the auditor, local contractors and equipment suppliers. Maintenance savings are calculated were applicable and are added to the energy savings for each EEM. The cost and savings are applied and a simple payback and simple return on investment (ROI) is calculated. The simple payback is based on the number of years that it takes for the savings to pay back the net installation cost (Net Installation divided by Net Savings.) A simple life$time calculation is shown for each EEM. The life$ time for each EEM is estimated based on the typical life of the equipment being replaced or altered. The energy savings is extrapolated throughout the life$time of the EEM. The total energy savings is calculated as the total life$time multiplied by the yearly savings. d. Limitations of the Study: All results are dependent on the quality of input data provided, and can only act as an approximation. In some instances, several methods may achieve the identified savings. This report is not intended as a final design document. A design professional, licensed to practice in Alaska and in the appropriate discipline, who is following the recommendations, shall accept full responsibility and liability for the results. Budgetary estimates for engineering and design of these projects in not included in the cost estimate for each measure, but these costs generally run around 15% of the cost of the work. Shaktoolik K-12 School Comprehensive Energy Audit 10 4. Acknowledgements: We wish to acknowledge the help of numerous individuals who have contributed information that was used to prepare this report, including: a. Alaska Housing Finance Corporation (Grantor): AHFC provided the grant funds, contracting agreements, guidelines, and technical direction for providing the audits. AHFC reviewed and approved the final short list of buildings to be audited based on the recommendation of the Technical Service Provider (TSP). b. Bering Strait School District (Owner): The BSSD provided building access, original construction plans, two years energy billing data, building schedules and functions, as well as other resources needed to perform the audit. c. Central Alaska Engineering Company (Benchmark TSP): Central Alaska Engineering Company compiled the data received from the BSSD and entered that data into the statewide building database, called the Alaska Retrofit Information System (ARIS). d. Richard S. Armstrong, PE, LLC (Audit TSP): This is the TSP who was awarded the projects in the Arctic Slope Regional Corporation, Bering Straits area, and the Nana area. The firm gathered all relevant benchmark information provided to them, cataloged which buildings would have the greatest potential payback, and prioritized buildings to be audited based on numerous factors, including the Energy Use Index (EUI), the Energy Cost Index (ECI), the age of the building, the size of the building, the location of the building, the function of the building, and the availability of plans for the building. They also trained their selected sub$contracted auditors, assigned auditors to the selected buildings, and performed quality control reviews of the resulting audits. They prepared a listing of potential EEMs that each auditor must consider, as well as the potential EEMs that the individual auditor may notice in the course of his audit. Richard S. Armstrong, PE, LLC also Shaktoolik K-12 School Comprehensive Energy Audit 11 performed some of the audits to assure current knowledge of existing conditions. 5. Building Description and Function: The subject structure is called the Shaktoolik School and was constructed in 1980. The building serves as a kindergarten through twelfth grade (K$12) educational facility, which includes classrooms, administrative offices, a commercial kitchen, a gymnasium, locker rooms, restrooms, two residential apartments, and multiple storage and utility spaces. The building is a two story structure with a full height basement under the center portion of the building. The foundation on the west side of the building is 4” slab on grade concrete, on which sit the gymnasium, language arts classroom, gym storage, and a portion of one second floor apartment. The east portion of the building is also 4” slab on grade, on which sit classrooms and administrative offices. The center portion of the building has a basement, first and second floors. The basement has the maintenance workroom, mechanical/electrical room, and kitchen storage. The first floor has the main entries, central corridor, locker rooms, restrooms, commercial kitchen, and enclosed delivery “dock” area. The second floor has two apartments, a small office, two fan rooms, and limited storage. The basement is 8 feet in height, the first floor in the center of the building is 8 feet in height, and the second floor ceiling height in the center of the building follows the roof slope from 6.5 to 9.5 feet high. The gymnasium ceiling follows the roof slope, giving a ceiling height ranging from 18 to 23 feet. The classroom ceilings also follow the roof slope, having ceiling heights varying from 10.5 to 15 feet. The building roof is constructed of open web trusses with sheathing and/or gypsum board on top and bottom and batt insulation in between. The center portion of the building has trusses that are slightly shallower than the slab portions, and were designed for 16” of batt insulation as opposed to 18” for the rest of the roof. The original overall roof insulation value was approximately R$ 40, but given the high amount of heat loss seen in the AkWarm$C model it is assumed that the insulation has either degraded over time, which is possible since it is a vented roof, the insulation has significantly compressed over time, or there was slightly less batt insulation installed than the plans called for. In any case the roof has been modeled with an insulation value of R$28. The exterior walls are constructed of 2x12 wood studs, 24 inch on center, with sheathing Shaktoolik K-12 School Comprehensive Energy Audit 12 and/or gypsum board on either side and batt insulation in between. The original overall insulation value may have been around R$30, however the actual value is assumed to be closer to R$18 due to the high rate of heat loss in the model. Overall the building is decent condition though it is showing its age and is not built to current energy conservations standards. Occupants commented that it did not maintain comfortable space temperatures during winter weather, dropping down as low as 50 deg. F during especially cold outdoor temperatures. The building is occupied from the middle of August through the middle of May. The school is unused during the summer months. a. Heating System: The school heating plant is in the basement of the building. The heating system consists of two Weil$ McLain WGO$8 cast iron sectional boilers with Beckett model 707502 single$stage burners. The boilers are not original to the 1980 construction and appear to have been installed in 2008. The new boilers have a combined total heat output of about 528 MBH. The original boilers were designed for a heat output of 873 MBH. This is a difference of 345 MBH, which is likely the reason that the building has difficulty maintaining temperature. It was also noted that the boiler pumps were undersized, which would exacerbate the already inadequate heating output. Hot glycol is circulated around the building using multiple Grundfos single$speed circulators. Each pump covers a zone or piece of equipment in the building. No backup pumps are installed. It appears that all of the pumps are operated manually and set to run constantly during the heating season. The pumps are not equipped with variable frequency drives (VFD), so they run at full speed when they operate. Heat is distributed throughout the building using fintube baseboard in most perimeter spaces, cabinet unit heaters in the vestibules and main corridor, unit heaters in utility spaces, and some supplemental heat through tempered ventilation air. b. Ventilation System: There are two air handlers and one make$up air unit in the building as well as multiple exhaust fans. SF$1 is a make$up air unit that serves the kitchen hood Shaktoolik K-12 School Comprehensive Energy Audit 13 exhaust fan. SF$2 is the air handler that serves classrooms and administrative spaces in the building. SF$1 and 2 are operated using the same time clock. SF$3 serves the gymnasium and was installed in 2005 presumably because SF$2, which previously served the gymnasium, was too small to provide effective ventilation. SF$3 is operated using a controller mounted on the unit that is capable of programming schedules for automatic operation. Relief air is provided by a large opening in the west wall of the gymnasium that opens when SF$3 is operating. A thermostat in the gymnasium controls the air handler heating coil. The unit was not operating at the time of the site visit and is likely only used when large gatherings are held in the gymnasium. EF$1 exhaust fans serve the locker rooms and switch on with the lights. EF$2 exhaust fan serves the main restrooms and is controlled using the same time clock as SF$1 and 2. EF$3 are small ceiling exhaust fans in restrooms operated manually with the lights. EF$4 is the kitchen hood exhaust fan, which is switched on at the wall next to the hood. Two ceiling paddle fans are installed in the gymnasium presumably to destratify the space. They are operated manually with a wall switch. State of Alaska design codes mandate that certain quantities of ventilation air must be provided. However, there are devices and strategies that can be employed to regulate the introduction of ventilation air so energy is not wasted, such as demand control ventilation based on CO2 concentration. c. Plumbing System: Water is provided from the village utility and there is not any on$site storage. Fixtures include water closets, lavatories, individual showers, classroom sinks, mop sinks, and large sinks for cooking. Most fixtures are located in bathrooms, locker rooms, custodial closets and the commercial kitchen. d. Domestic Hot Water: How water is generated using a 68 gallon oil fired water heater. No additional hot water storage is provided. There is a hot water recirculation pump that runs constantly to provide instant hot water to remote fixtures. Shaktoolik K-12 School Comprehensive Energy Audit 14 e. Lighting: Lighting throughout the building is provided with T$ 12 fluorescent fixtures using magnetic ballasts and controlled with wall mounted toggle switches. In the central corridor, vestibules and a few limited locations T$8 fluorescent fixtures have been installed, which are also operated manually. The gymnasium has high bay lighting fixtures with (5) 2$tube, plug$ in, compact fluorescent bulbs at 55 watts each. Gymnasium lights are switched on manually. Exterior lights are high pressure sodium (HPS) fixtures and include wall packs (150 watts) and recess can canopy mounted (70 watts) fixtures. Exterior lights operate using daylight sensors. f. Fire Sprinkler: The building is equipped with a fire sprinkler protection system in the basement. 6. Historic Energy Consumption: Energy consumption is modeled within the AkWarm$C program. Two years of benchmark data were provided for this building, for 2009 and 2010, however the data for 2010 showed that virtually no electricity was used between March and August. This could be due to a number of causes such as inaccurate data or work being performed at the school but in any case it does not come close to representing the energy used in 2009. Consequently only the energy data for 2009 was used in the energy model since it is likely a more accurate picture of the building energy use. The energy consumption data is presented and graphed in the attached AkWarm$ C program results. Based on the benchmark energy data for 2009 the electric consumption for the building was 120,804 kWh/year at an average cost of $73,068/year. The average fuel oil consumption was 11,477 gallons/year, at an average annual cost of $47,667/year. 7. Energy Efficiency Measures Considered or Recommended: The building was examined for application of a multitude of potential EEMs that are discussed below. Those EEMs that appear to have an application for the subject building are further analyzed for estimated payback periods, either within the AkWarm$C program or separately within this report. The accuracy of the cost estimates and paybacks varies significantly due to a multitude of conditions, but is estimated to Shaktoolik K-12 School Comprehensive Energy Audit 15 be approximately +/$ 25%. Assumptions made regarding energy costs and the life of the EEM, noting that post$construction measurement and verification are based on energy savings, not energy cost savings. Many of the selected EEMs are analyzed within the AkWarm$C program using the schedules and estimated costs input into the model. a. Fluorescent lamp and ballast only upgrades: It is recommended that all of the T$12 lamps and magnetic ballasts be replaced with programmable electronic ballasts and T$8 lamps. Programmed start ballasts are also suitable for motion detector switching control, so the lights can be switched on and off frequently without adversely affecting the life of the lamps. This is one proposed measure that re$uses the existing fixtures, thus minimizing costs. Savings will vary depending on installed and replaced equipment. b. Occupancy Sensors for Lighting: The spaces in the building can be retrofitted with occupancy sensors so the lights are only on when rooms are in use. This applies to hallways, classrooms, offices, gymnasium, storage rooms, and restrooms. Though most rooms will be occupied during the majority of the school day, certain times of the day, such as lunchtime, will cause most rooms to be empty. Allowing lights to turn off automatically during these times will save energy. Occupancy sensors are not recommended for the kitchen since it is important that kitchen staff have control over lighting for safety reasons. a. Exterior Lighting Upgrade: High$intensity discharge (HID) fixtures, such as high pressure sodium (HPS), are commonly used for building exterior lighting in Alaska because they perform well in cold weather and are more efficient than many other types of lighting. However, light emitting diode (LED) fixtures are proving to be a viable alternative to HPS. LED fixtures use nano reflector technology with drivers offering 50,000 hours life, about 6 years, as compared to only 20,000 hours with high$intensity discharge (HID) fixtures. LED fixtures offer the instant$on feature of fluorescent fixtures but use Shaktoolik K-12 School Comprehensive Energy Audit 16 significantly less energy than the HID fixtures. LEDs have an added benefit of operating more efficiently (using less power) as the ambient temperature gets colder, and some have been factory tested to operate down to $40 deg F (actual installations in Antarctica and Fairbanks indicate they operate at lower temperatures as well) depending on manufacturer. The proposed LED fixtures are dark sky compliant, using 100% cutoff optics to reduce light pollution. LEDs provide a different type of light than HPS, both in color and lumen output, that has the effect of providing a clearer, brighter light while using less power than a HPS bulb. The following chart indicates energy savings for various exterior building mounted light fixtures (MH Metal Halide; HSP High Pressure Sodium) using Scotopic lighting measurements: HID Lamp HID System Wattage LED System Wattage Energy Savings (%) 70W HPS 90W 27W 79 150W HPS 188W 54W 71 c. Ventilation Operation Schedules: Some of the ventilation fans in the facility are operated on the same time clock schedule. Each of the fans serves a space (or spaces) with unique occupancy schedules so they should be programmed to match the space use. It is recommended that each fan discussed below have a dedicated electronic controller that will allow it to be programmed as indicated. New programmable controllers will also allow for faster, simpler programming so they can be easily adjusted if building use schedules change. In order to reduce the amount of electric and heating energy used by the fans the following scheduling changes are recommended: i. SF1, Kitchen Exhaust MakeUp Air – Interlock this unit to operate with the kitchen cooking hood exhaust fan, EF$4. Shaktoolik K-12 School Comprehensive Energy Audit 17 ii. SF2, Classrooms and Administration – Operate the unit only during school hours. iii. SF3, Gymnasium – Operate the unit during known periods of occupancy such as lunch hours and scheduled “open gym” hours. Provide an electronic timer in the main office for operation during off$schedule hours. iv. EF2, Main Restroom Exhaust Fan Operate the unit during known periods of occupancy such as school hours and “open gym”. Provide an electronic timer in the main office for operation during off$schedule hours. e. Carbon Dioxide (CO2) Monitoring: The amount of CO2 in a building has been shown to have a direct effect on the performance of the occupants in the building. High levels of CO2 cause occupants to feel sleepy and lose concentration. It is also an indication that other indoor contaminants, such as volatile organic compounds (VOCs), odors and excessive humidity are likely increasing in concentration. For these reasons ventilation air is required by code to refresh indoor building air. Typically the ventilation rate is determined based on the number of occupants and space sizes. In many cases this over$ventilates the space. Another method of ventilating spaces is called demand control ventilation, which entails varying the amount of outside air supplied based on CO2 levels in the building. Sensors can be placed in spaces throughout the building (preferred) or in the return air duct at the air handlers, and the air handler outside air dampers can be modulated to increase or decrease the outside air delivered to the building. This modification applies specifically to SF$3 and may also be appropriate for SF$2. d. VFD Heating Pumps: In most cases heating circulators are designed for greater flow rates than is needed during normal operation. Bypass valves are installed to allow the constant volume of flow to continue even when a small amount of that flow is providing heat. Energy is wasted circulating heated glycol that is not needed. There are a number of pumps on Shaktoolik K-12 School Comprehensive Energy Audit 18 the market that have variable frequency drives (VFD), which allow the speed of the motor to be adjusted to match the flow rate demand. Pump affinity laws show that motor speed and power have a cubic mathematical relationship to each other. As the pump speed is reduced “X” RPM the power consumption is reduced by X1/3 watts (or horsepower), showing that a small change in pump speed has an amplified affect on power input. Operating pumps at lower speeds when there is lower flow demand significantly reduces power consumption. It is recommended that the heating circulators be replaced with VFD pumps so power savings can be realized. e. Boiler Temperature Outdoor Air Reset: As the outside air temperature varies building heat loss varies as well, losing heat at a faster rate as the ambient temperature drops. Boiler systems are typically sized to meet the heating demands of the coldest expected temperatures. These extreme temperatures may only occur for short durations in a given winter and will vary in frequency and length year to year. Most cast iron sectional boilers supply heating water at the same temperature year$round. During periods of warmer weather in the heating season high heating water supply temperatures may cause space temperatures to overshoot set points because the hot boiler water dumps heat into the building at a faster rate than the building is losing it, leading to occupant discomfort. This will also cause the boilers to cycle more often since it takes less time to heat the returning water, putting unnecessary ware on the boilers. A common way of handling this issue is to use an outdoor reset controller to reduce the heating loop temperature so that heat is transferred into the building closer to the rate at which the building is losing heat. Outdoor reset varies the boiler or heating loop water temperature based on the ambient temperature – increasing the water temperature when outdoor conditions are cold and decreasing water temperature for warmer outdoor conditions. It is very common for maintenance personnel to manually adjust the boiler temperature to give the same effect. In order to maintain tighter control and prevent issues such as setting the boiler temperature too low (causing the boiler to condense), or Shaktoolik K-12 School Comprehensive Energy Audit 19 forgetting to reset the boiler temperature, it is recommended that a controller be installed that will perform the outdoor reset automatically. There is not a provision for simulating this in the AkWarm$C program so no energy savings are considered here. However it is recommended that a licensed professional engineer perform the design for installation of this controller at which time an energy savings analysis could be performed. f. Waste Heat: The school building is not currently supplied with waste heat. However the school is roughly 0.25 miles from the village power utility. If the school was supplied with waste heat from the village power plant it would have a tremendous impact on energy savings for the school, likely surpassing fuel oil as the primary heating source. Connecting the school heating plant to the village power plant would require a large capital investment but could have a payback of 10$15 years. No investigation has been performed on the amount of heat that would be available from the power plant, which would require a thorough engineering analysis. It is recommended that a preliminary investigation be performed to determine the viability of this option. b. Fuel Oil Metering: It is recommended that fuel oil meters be installed to track the amount of fuel used by the boilers and electric generator. The only methods currently used on site for tracking fuel usage are recording the amount of fuel put into bulk fuel storage tanks when they are refilled and maintenance personnel manually recording the fuel levels in the tanks. Neither method is able to provide precise information nor does it give a detailed picture of the rate at which fuel is used. In order to understand current and future fuel consumption, a fuel meter should be installed at the fuel supply to the building. The Pathfinder Instruments FM$200 meter is for fuel pipes sized ¾” to 1” (different meters, must specify pipe size), and they cost around $225 each. They operate at a flow range of 4$20 GPM. These are mechanical meters with strainers and 3$ digid display that shows both present fuel use, and cumulative fuel use. Any ESCO contract, or AHFC financed contract will require fuel metering to verify paybacks of energy conservation Shaktoolik K-12 School Comprehensive Energy Audit 20 measures. Electronic turbine meters are also available. See pathfinderinstruments.com for product information. 8. Interactive Effects of Projects: The AkWarm$C program calculates savings assuming that all recommended EEM are implemented. If some EEMs are not implemented, savings for the remaining EEMs will be affected, in some cases positively, and in others, negatively. For example, if the fan motors are not replaced with premium efficiency motors, then the savings for the project to install variable speed drives (VFDs) on the fans will be increased. In general, all projects were evaluated sequentially so that energy savings associated with one EEM would not be attributed to another EEM as well. For example, the night setback EEM was analyzed using the fan and heating load profile that will be achieved after installation of the VFD project is completed. By modeling the recommended projects sequentially, the analysis accounts for interactive effects between the EEMs and does not “double count” savings. Interior lighting, plug loads, facility equipment, and occupants generate heat within the building. When the building is in cooling mode, these contribute to the overall cooling demands of the building; therefore lighting efficiency improvements will reduce cooling requirements on air conditioned buildings. Conversely, lighting efficiency improvements are anticipated to increase heating requirements slightly. Heating penalties are included in the lighting project analysis that is performed by AkWarm$C. 9. Loan Program: The Alaska Housing Finance Corporation (AHFC) Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State of Alaska program enacted by the Alaska Sustainable Energy Act (senate Bill 220, A.S. 18.56.855, “Energy Efficiency Revolving Loan Fund). The AEERLF will provide loans for energy efficiency retrofits to public facilities via the Retrofit Energy Assessment for Loan System (REAL). As defined in 15 AAC 155.605, the program may finance energy efficiency improvements to buildings owned by: a. Regional educational attendance areas; Shaktoolik K-12 School Comprehensive Energy Audit 21 b. Municipal governments, including political subdivisions of municipal governments; c. The University of Alaska; d. Political subdivisions of the State of Alaska, or e. The State of Alaska Native corporations, tribal entities, and subsidiaries of the federal government are not eligible for loans under this program. Shaktoolik K-12 School Comprehensive Energy Audit 22 Appendix A: Photos Classrooms, East Elevation Main Entrance, Northeast Elevation Shaktoolik K-12 School Comprehensive Energy Audit 23 Delivery Area, Second Floor Apt., Gym, Northwest Elevation Gym, Second Floor Apartment, West Elevation Shaktoolik K-12 School Comprehensive Energy Audit 24 Gym Entrance, Classroom Entrance, Second Floor Apartment, South Building Entrance, Classrooms, South Elevation Typical Classroom Shaktoolik K-12 School Comprehensive Energy Audit 25 Gymnasium, North wall Gymnasium, East wall with SF3 ductwork, Kitchen on the left Shaktoolik K-12 School Comprehensive Energy Audit 26 Kitchen cooking equipment under exhaust hood, hot wells to right Kitchen dish washing equipment Shaktoolik K-12 School Comprehensive Energy Audit 27 Kitchen walkin refrigerator and freezer Kitchen makeup air Air Handler SF1 Shaktoolik K-12 School Comprehensive Energy Audit 28 Classroom Air Handler SF2 Gym Air Handler SF3 Shaktoolik K-12 School Comprehensive Energy Audit 29 Kitchen Hood exhaust fan on roof Building exhaust fan Shaktoolik K-12 School Comprehensive Energy Audit 30 Air handler and fan time clock Domestic water pressure booster system Shaktoolik K-12 School Comprehensive Energy Audit 31 Boilers and water heater, heating circulation pumps in background Heating circulation pumps Shaktoolik K-12 School Comprehensive Energy Audit 32 Shaktoolik Village, Ariel View Village Power Utility School Shaktoolik K-12 School Comprehensive Energy Audit 33 Appendix B: AK Warm Energy Model Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 1 ENERGY AUDIT REPORT – PROJECT SUMMARY – Created 4/9/2012 10:32 AM General Project Information PROJECT INFORMATION AUDITOR INFORMATION Building: Shaktoolik School Auditor Company: RSA Engineering, Inc. Address: Shaktoolik Alaska 99771 Auditor Name: Adam Wilson City: Shaktoolik Auditor Address: 2522 Arctic Blvd Suite 200 Anchorage, AK 99503 Client Name: Richard Ried Client Address: PO Box 225 Unalakleet AK 99684 Auditor Phone: (907) 276-0521 Auditor FAX: Client Phone: (907) 624-3611 Auditor Comment: Client FAX: Design Data Building Area: 17,468 square feet Design Heating Load: Design Loss at Space: 280,495 Btu/hour with Distribution Losses: 280,495 Btu/hour Plant Input Rating assuming 82.0% Plant Efficiency and 25% Safety Margin: 427,584 Btu/hour Note: Additional Capacity should be added for DHW load, if served. Typical Occupancy: 156 people Design Indoor Temperature: 70.1 deg F (building average) Actual City: Shaktoolik Design Outdoor Temperature: -24.4 deg F Weather/Fuel City: Shaktoolik Heating Degree Days: 13,919 deg F-days Utility Information Electric Utility: AVEC-Shaktoolik - Commercial - Lg Natural Gas Provider: None Average Annual Cost/kWh: $0.508/kWh Average Annual Cost/ccf: $0.000/ccf Annual Energy Cost Estimate Description Space Heating Space Cooling Water Heating Lighting Refrige ration Other Electric al Cooking Clothes Drying Ventilatio n Fans Service Fees Total Cost Existing Building $43,363 $0 $7,037 $28,176 $2,393 $5,947 $8,299 $0 $7,214 $60 $102,489 With Proposed Retrofits $30,519 $0 $6,830 $16,820 $1,902 $5,975 $8,339 $0 $7,281 $60 $77,725 SAVINGS $12,844 $0 $207 $11,356 $492 -$28 -$41 $0 -$67 $0 $24,763 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 2 $0 $20,000 $40,000 $60,000 $80,000 $100,000 $120,000 Existing Retrofit Service Fees Ventilation and Fans Space Heating Refrigeration Other Electrical Lighting Domestic Hot Water Cooking Annual Energy Costs by End Use $0 $20,000 $40,000 $60,000 $80,000 $100,000 $120,000 Existing Retrofit #2 Oil Electricity Annual Energy Costs by Fuel Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 3 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 1 Refrigeration: Walk- in Refrigerator/Freezer Add new Seasonal Shutdown $193 $1 1174.50 0 2 Refrigeration: True Mfg. Model T-49 Add new Seasonal Shutdown $125 $1 774.06 0 3 Refrigeration: Refrigerator/Freezer Add new Seasonal Shutdown $87 $1 528.50 0 4 Setback Thermostat: 122 - Multi-Purpose Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 122 - Multi-Purpose Room space. $1,768 $200 119.83 0.1 5 Refrigeration: small fridge Add new Seasonal Shutdown $10 $1 58.75 0.1 6 Setback Thermostat: 108C - Elementary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108C - Elementary Classroom space. $516 $200 35.01 0.4 7 Setback Thermostat: 123 - Language Arts Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 123 - Language Arts space. $491 $200 33.29 0.4 8 Setback Thermostat: 104 - High School Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 104 - High School space. $426 $200 28.86 0.5 9 Setback Thermostat: 107 - Resource Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 107 - Resource Room space. $399 $200 27.04 0.5 10 Setback Thermostat: 108D - Elementary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108D - Elementary Classroom space. $359 $200 24.34 0.6 11 Setback Thermostat: 105 - Science Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 105 - Science space. $344 $200 23.32 0.6 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 4 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 12 Setback Thermostat: 108B -Elementary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108B -Elementary Classroom space. $300 $200 20.32 0.7 13 Setback Thermostat: 113 - Boys Locker Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 113 - Boys Locker Room space. $273 $200 18.52 0.7 14 Setback Thermostat: 106 - Home Economics Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 106 - Home Economics space. $262 $200 17.75 0.8 15 Setback Thermostat: 204 - Dining/205 - Living/206 - Kitchen Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 204 - Dining/205 - Living/206 - Kitchen space. $239 $200 16.21 0.8 16 Setback Thermostat: 201 - Studio Apartment Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 201 - Studio Apartment space. $193 $200 13.07 1 17 Setback Thermostat: 211 - Bedroom Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 211 - Bedroom space. $119 $200 8.06 1.7 18 Setback Thermostat: 216 - Bedroom Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 216 - Bedroom space. $108 $200 7.35 1.8 19 Lighting: Gymnasium: Type F - Sportlite SLC275-PC- WG Core Zone Remove Manual Switching and Add new Occupancy Sensor $759 $700 6.71 0.9 20 Setback Thermostat: 209 - Bedroom Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 209 - Bedroom space. $76 $200 5.17 2.6 21 Setback Thermostat: 210 - Bedroom Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 210 - Bedroom space. $76 $200 5.13 2.6 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 5 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 22 Lighting: Gymnasium: Type F - Sportlite SLC275-PC- WG Perimeter Zone Remove Manual Switching and Add new Occupancy Sensor $519 $700 4.51 1.3 23 Lighting: Classrooms: Type B3 - Surface F40WW/RS/WM Perimeter Zone Remove Manual Switching and Add new Occupancy Sensor $964 $1,400 4.18 1.5 24 Setback Thermostat: 102 - Main Corridor Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 102 - Main Corridor space. $54 $200 3.66 3.7 25 Lighting: Utility, Storage, Restrooms, Locker Rooms, Stair: Type C2 Core Zone Remove Manual Switching and Add new Occupancy Sensor $1,094 $2,100 3.22 1.9 26 Lighting: Classrooms: Type B3 - Surface F40WW/RS/WM Core Zone Remove Manual Switching and Add new Occupancy Sensor $711 $1,400 3.14 2 27 Lighting: Science 105/Language Arts 123: Type D2 - Surface F40WW/RS/WM Remove Manual Switching and Add new Occupancy Sensor $357 $700 3.10 2 28 Lighting: Principal 110: Type A4 - Recessed F40WW/RS/WM Core Zone Replace with 2 FLUOR (4) T8 4' F32T8 32W Standard Program StdElectronic $128 $350 2.26 2.7 29 Setback Thermostat: 207 - Bathroom Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 207 - Bathroom space. $33 $200 2.26 6 30 HVAC And DHW Change heat loop circ. pumps to one VFD pump, run domestic hot water recirc. pump on time clock or temp. sensor $3,407 $30,000 1.57 8.8 31 Lighting: Boys/Girls Restrooms: Type K2 - Surface 60A/99 Core Zone Remove Manual Switching and Add new Occupancy Sensor $163 $700 1.45 4.3 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 6 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 32 Ventilation Provide new electronic controls to operate air handling units. Use CO2 sensor to operate gym air handler. Reprogram air handlers to operate on proper schedules $4,635 $50,000 1.25 10.8 33 Lighting: Science 105/Home Ec 106: Type H2 - Wall F40WW/RS/WM Replace with 3 FLUOR (2) T8 4' F32T8 32W Standard (2) Program StdElectronic $108 $525 1.25 4.9 34 Lighting: Classrooms: Type B3 - Surface F40WW/RS/WM Core Zone Replace with 26 FLUOR (3) T8 4' F32T8 32W Standard Program StdElectronic $917 $4,550 1.25 5 35 Lighting: Exterior Wall Pack: Type I - Wall LU150/S5 Replace with 6 LED 50W Module StdElectronic $1,598 $9,000 1.10 5.6 36 Lighting: Principal 110: Type A4 - Recessed F40WW/RS/WM Core Zone Remove Manual Switching and Add new Occupancy Sensor $57 $350 1.01 6.1 37 Lighting: Classrooms: Type B3 - Surface F40WW/RS/WM Perimeter Zone Replace with 45 FLUOR (3) T8 4' F32T8 32W Standard Program StdElectronic $1,235 $7,875 0.95 6.4 38 Lighting: Science 105/Language Arts 123: Type D2 - Surface F40WW/RS/WM Replace with 16 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $319 $2,800 0.69 8.8 39 Lighting: Utility, Storage, Restrooms, Locker Rooms, Stair: Type C2 Core Zone Replace with 23 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $422 $4,025 0.65 9.5 40 Lighting: Corridor 128: Type A2 - Recessed F40WW/RS/WM Replace with 2 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $34 $350 0.59 10.3 41 Lighting: Exterior Recessed Can: Type M - Recessed LU70 Replace with 6 LED 25W Module StdElectronic $820 $9,000 0.56 11 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 7 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 42 Lighting: Corridor 128: Type A2 - Recessed F40WW/RS/WM Remove Manual Switching and Add new Occupancy Sensor $23 $350 0.39 15.5 43 Lighting: Science 105/Home Ec 106: Type H2 - Wall F40WW/RS/WM Remove Manual Switching and Add new Occupancy Sensor $42 $700 0.37 16.5 44 Setback Thermostat: 108A - Elementary Classroom Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108A - Elementary Classroom space. $0 $200 0.00 Infinity 45 Setback Thermostat: 109/111 - Teachers Work Area Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 109/111 - Teachers Work Area space. $0 $200 0.00 Infinity 46 Setback Thermostat: 110 - Conference Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 110 - Conference Room space. $0 $200 0.00 Infinity 47 Setback Thermostat: 114 - Girls Locker Room Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 114 - Girls Locker Room space. $0 $200 0.00 Infinity 48 Setback Thermostat: 212 - Hall Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 212 - Hall space. $0 $200 0.00 Infinity TOTAL $24,763 $132,179 1.95 5.3 ENERGY AUDIT REPORT – ENERGY EFFICIENT RECOMMENDATIONS 1. Building Envelope Insulation Rank Location Existing Type/R:Value Recommendation Type/R: Value Installed Cost Annual Energy Savings Exterior Doors – Replacement Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 8 Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Windows and Glass Doors – Replacement Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Air Leakage Rank Location Estimated Air Leakage Recommended Air Leakage Target Installed Cost Annual Energy Savings 2. Mechanical Equipment Mechanical Rank Recommendation Installed Cost Annual Energy Savings 30 Change heat loop circ. pumps to one VFD pump, run domestic hot water recirc. pump on time clock or temp. sensor $30,000 $3,407 Setback Thermostat Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings 4 122 - Multi- Purpose Room Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 122 - Multi-Purpose Room space. $200 $1,768 6 108C - Elementary Classroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108C - Elementary Classroom space. $200 $516 7 123 - Language Arts Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 123 - Language Arts space. $200 $491 8 104 - High School Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 104 - High School space. $200 $426 9 107 - Resource Room Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 107 - Resource Room space. $200 $399 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 9 10 108D - Elementary Classroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108D - Elementary Classroom space. $200 $359 11 105 - Science Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 105 - Science space. $200 $344 12 108B -Elementary Classroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108B -Elementary Classroom space. $200 $300 13 113 - Boys Locker Room Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 113 - Boys Locker Room space. $200 $273 14 106 - Home Economics Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 106 - Home Economics space. $200 $262 15 204 - Dining/205 - Living/206 - Kitchen Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 204 - Dining/205 - Living/206 - Kitchen space. $200 $239 16 201 - Studio Apartment Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 201 - Studio Apartment space. $200 $193 17 211 - Bedroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 211 - Bedroom space. $200 $119 18 216 - Bedroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 216 - Bedroom space. $200 $108 20 209 - Bedroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 209 - Bedroom space. $200 $76 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 10 21 210 - Bedroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 210 - Bedroom space. $200 $76 24 102 - Main Corridor Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 102 - Main Corridor space. $200 $54 29 207 - Bathroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 207 - Bathroom space. $200 $33 44 108A - Elementary Classroom Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 108A - Elementary Classroom space. $200 $0 45 109/111 - Teachers Work Area Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 109/111 - Teachers Work Area space. $200 $0 46 110 - Conference Room Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 110 - Conference Room space. $200 $0 47 114 - Girls Locker Room Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the 114 - Girls Locker Room space. $200 $0 48 212 - Hall Existing Unoccupied Heating Setpoint: 72.0 deg F Implement a Heating Temperature Unoccupied Setback to 65.0 deg F for the 212 - Hall space. $200 $0 Ventilation Rank Recommendation Cost Annual Energy Savings 32 Provide new electronic controls to operate air handling units. Use CO2 sensor to operate gym air handler. Reprogram air handlers to operate on proper schedules $50,000 $4,635 3. Appliances and Lighting Lighting Fixtures and Controls Rank Location Existing Recommended Installed Cost Annual Energy Savings Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 11 19 Gymnasium: Type F - Sportlite SLC275- PC-WG Core Zone 8 FLUOR 250 Watt StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $759 22 Gymnasium: Type F - Sportlite SLC275- PC-WG Perimeter Zone 7 FLUOR [Unknown Lamp] with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $519 23 Classrooms: Type B3 - Surface F40WW/RS/WM Perimeter Zone 45 FLUOR (3) T12 4' F40T12 40W Standard Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $1,400 $964 25 Utility, Storage, Restrooms, Locker Rooms, Stair: Type C2 Core Zone 23 FLUOR (2) T12 4' F40T12 40W Standard Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $2,100 $1,094 26 Classrooms: Type B3 - Surface F40WW/RS/WM Core Zone 26 FLUOR (3) T12 4' F40T12 40W Standard Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $1,400 $711 27 Science 105/Language Arts 123: Type D2 - Surface F40WW/RS/WM 16 FLUOR (2) T12 4' F40T12 40W Standard Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $357 28 Principal 110: Type A4 - Recessed F40WW/RS/WM Core Zone 2 FLUOR (4) T12 4' F40T12 40W Standard Magnetic with Manual Switching Replace with 2 FLUOR (4) T8 4' F32T8 32W Standard Program StdElectronic $350 $128 31 Boys/Girls Restrooms: Type K2 - Surface 60A/99 Core Zone 2 INCAN (2) A Lamp, Halogen 60W with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $163 33 Science 105/Home Ec 106: Type H2 - Wall F40WW/RS/WM 3 FLUOR (2) T12 4' F40T12 40W Standard (2) Magnetic with Manual Switching Replace with 3 FLUOR (2) T8 4' F32T8 32W Standard (2) Program StdElectronic $525 $108 34 Classrooms: Type B3 - Surface F40WW/RS/WM Core Zone 26 FLUOR (3) T12 4' F40T12 40W Standard Magnetic with Manual Switching Replace with 26 FLUOR (3) T8 4' F32T8 32W Standard Program StdElectronic $4,550 $917 35 Exterior Wall Pack: Type I - Wall LU150/S5 6 HPS 150 Watt Magnetic with Daylight Sensor Replace with 6 LED 50W Module StdElectronic $9,000 $1,598 36 Principal 110: Type A4 - Recessed F40WW/RS/WM Core Zone 2 FLUOR (4) T12 4' F40T12 40W Standard Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $350 $57 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 12 37 Classrooms: Type B3 - Surface F40WW/RS/WM Perimeter Zone 45 FLUOR (3) T12 4' F40T12 40W Standard Magnetic with Manual Switching Replace with 45 FLUOR (3) T8 4' F32T8 32W Standard Program StdElectronic $7,875 $1,235 38 Science 105/Language Arts 123: Type D2 - Surface F40WW/RS/WM 16 FLUOR (2) T12 4' F40T12 40W Standard Magnetic with Manual Switching Replace with 16 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $2,800 $319 39 Utility, Storage, Restrooms, Locker Rooms, Stair: Type C2 Core Zone 23 FLUOR (2) T12 4' F40T12 40W Standard Magnetic with Manual Switching Replace with 23 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $4,025 $422 40 Corridor 128: Type A2 - Recessed F40WW/RS/WM 2 FLUOR (2) T12 F40T12 35W U-Tube Energy-Saver Magnetic with Manual Switching Replace with 2 FLUOR (2) T8 4' F32T8 32W Standard Program StdElectronic $350 $34 41 Exterior Recessed Can: Type M - Recessed LU70 6 HPS 70 Watt Magnetic with Daylight Sensor Replace with 6 LED 25W Module StdElectronic $9,000 $820 42 Corridor 128: Type A2 - Recessed F40WW/RS/WM 2 FLUOR (2) T12 F40T12 35W U-Tube Energy-Saver Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $350 $23 43 Science 105/Home Ec 106: Type H2 - Wall F40WW/RS/WM 3 FLUOR (2) T12 4' F40T12 40W Standard (2) Magnetic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $42 Refrigeration Rank Location Existing Recommended Installed Cost Annual Energy Savings 1 Walk-in Refrigerator/Freeze r Walk-in Refrigerator/Freezer Add new Seasonal Shutdown $1 $193 2 True Mfg. Model T- 49 Mobile Refrigerator in Kitchen Add new Seasonal Shutdown $1 $125 3 Refrigerator/Freeze r 3 Residential Refrigerator/Freezer Add new Seasonal Shutdown $1 $87 5 small fridge small fridge Add new Seasonal Shutdown $1 $10 Other Electrical Equipment Rank Location Existing Recommended Installed Cost Annual Energy Savings Cooking/Clothes Drying Rank Recommended Installed Cost Annual Energy Savings Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Shaktoolik School Page 13 ------------------------------------------ AkWarmCalc Ver 2.1.4.2, Energy Lib 3/1/2012 Shaktoolik K-12 School Comprehensive Energy Audit 47 Appendix C: Existing Plans