Loading...
HomeMy WebLinkAboutBSSD-WBB-RSA Stebbins Tukurngailnguq School 2012-EERichard S. Armstrong, PE, LLC Mechanical/Electrical Engineer Comprehensive Energy Audit of Stebbins Tukurngailnguq K12 School Stebbins, Alaska Project # BSSDWBBRSA01 Prepared for: Bering Strait School District Contact: Richard Ried, Maintenance Supervisor Phone: 9076244249 Unalakleet, Alaska February 17, 2012 Prepared by: Richard S. Armstrong, PE, LLC 2321 Merrill Field Drive, C$6 Anchorage, AK 99501 and RSA Engineering, Inc. 2422 Arctic Blvd., Suite 200 Anchorage, AK 99503 Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 2 TABLE OF CONTENTS 1. Report Disclaimers 3 2. Executive Summary 4 3. Audit and Analysis Background 8 4. Acknowledgements 10 5. Building Description & Function 11 6. Historic Energy Consumption 15 7. Energy Efficiency Measures Considered or Recommended 15 8. Interactive Effects of Projects 23 9. Loan Program 24 Appendix A: Photos 25 Appendix B: AkWarm7C Report 40 Appendix C: Building Schedules and Plans 56 Performed by: ___________________________ Adam W. Wilson, PE, CEA CEA # 1618 RSA Engineering, Inc. Reviewed by: ___________________________ Richard Armstrong, PE, CEM CEA #178, CEM # 13557 Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 3 1. REPORT DISCLAIMERS This audit was performed using American Recovery and Reinvestment Act (ARRA) funds, managed by the Alaska Housing Finance Corporation (AHFC). The information contained in this report, including any attachments, is intended solely for use by the building owner and the AHFC. This report contains recommendations that, in the opinion of the auditor, will cause the owner to realize energy savings over time. All recommendations must be designed by a registered engineer, licensed in the State of Alaska, in the appropriate discipline. Lighting recommendations should all be first reviewed by running a lighting analysis to assure that the recommended lighting upgrades will comply with State of Alaska Statue as well as IES recommendations. Payback periods may well vary from those forecast due to the uncertainty of the final installed design, configuration, equipment selected, and installation costs of recommended Energy Efficiency Measures (EEMs), or the operating schedules and maintenance provided by the owner. Furthermore, EEMs are typically interactive, so implementation of one EEM may impact the cost savings from another EEM. Neither the auditor, Richard S. Armstrong, PE, LLC, AHFC, or others involved in preparation of this report will accept liability for financial loss due to EEMs that fail to meet the forecasted payback periods. This audit meets the criteria of an Investment Grade Audit (IGA) per the Association of Energy Engineers definition, and is valid for one year. The life of the IGA may be extended on a case$by$case basis, at the discretion of the AHFC. IGSs are the property of the State, and may be incorporated into AkWarm$ C, the Alaska Energy Data Inventory (ARIS), or other state and/or public information system. AkWarm$C is a building energy modeling software developed under contract with AHFC. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 4 Investment Grade Energy Audit Stebbins Tukurngailnguq K12 School 2. Executive Summary: The Stebbins Tukurngailnguq K$12 School was constructed in 1992, using design concepts and construction materials that were common at that time for school buildings in Western Alaska. It is owned and operated by the Bering Strait School District (BSSD). Benchmark energy use data collected for this building is presented in Table 1 below: Table 1 2009 2009 2010 2010 Utility Consumption Cost/Year Consumption Cost/Year Electricity$kWh 304,459 $166,653 287,513 $133,177 No. 2 Fuel Oil $ Gallons 28,098 $104,785 27,243 $ 84,597 Ttl Energy Costs $271,438 $217,774 A benchmark measure of energy use relative to other similar function buildings in the area is the Energy Use Index (EUI), which takes the total annual energy used by the facility divided by the square footage area of the building, for a value expressed in terms of kBTU/SF. This number can then be compared to other buildings to see if it is about average, higher or lower than similar buildings in the area. Likewise, the Energy Cost Index (ECI) is the cost of all energy used by the building expressed in $/SF of building area. The comparative values for the subject building are listed in Table 2 below: Table 2 Stebbins Tukurngailnguq K$12 School Saint Michael Andrews K$12 School (neigh$ boring village) Average for All BSSD Schools Energy Use Index (EUI) kBTU/SF Avg 2009, 2010 133.0 153.1 125.3 Energy Cost Index (ECI) Average 2009, 2010 $6.98 $7.04 $6.73 Various Energy Efficiency Measures (EEMs) have been analyzed for this building to determine if they would be applicable for energy Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 5 savings with reasonably good payback periods. Those EEMs that have a payback period or those that are recommended for code compliance, life cycle replacement, or other reasons are also included. Specific EEMs recommended for this facility are detailed in the attached AkWarm Energy Audit Report along with specific payback times, as well as estimated installation costs and estimated energy savings. The higher priority items are summarized below: a. Building HVAC Controls i. The building heating, ventilation and air conditioning (HVAC) system is currently operated by an electric control system that runs equipment using time clocks, thermostats and some manual over rides. It is recommended that the existing control system be replaced with an electronic control system. This will allow greater control of the HVAC systems, providing more communication between devices/spaces and easier programming. It will also keep the controls relatively simple for maintenance personnel to work with. ii. Upgrading controls would overlap with other recommended work described below so it is difficult to identify the savings and payback of this upgrade alone. An estimate of $60,000 would be reasonable, with a savings of about 10% and a pay back of approximately 2.5 years. b. Building Ventilation i. The main ventilation system for the building consists of a supply fan and an exhaust fan. The outside air and exhaust air pass through an energy recovery coil to help capture some of the heat in the exhaust air stream. This is a very inefficient way to provide ventilation for the school. The energy recover coil only captures a small amount of the heat in the exhaust air (roughly 35%) while the rest is blown out of the building. It is recommended that the system be reconfigured to provide a bypass damper between the Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 6 exhaust and outside air ducts in order to reuse the heated air in the exhaust stream. There are code related issues that need to be addressed for this to be done, which are described in more detail further down in this report. The cost estimate for this work is about $40,000, with a savings around 10$15% and a payback of approximately 1.2 years. c. Carbon Dioxide (CO2) Monitoring i. CO2 sensors can be utilized to help reduce the amount of outside air drawn into the building. Rather than supply a set minimum amount of outside air during ventilation fan operation (15% of the total fan air volume, for example) the outside air can be varied to maintain the CO2 levels below a determined setpoint, typically 750 parts per million for schools. This often results in less outside air being drawn into the building, which reduces the amount of energy needed to heat the air. ii. The above changes to ventilation fan control would be integral to a controls upgrade, but if this was the only work performed, and only for the gymnasium air handler, it would provide an estimated 1% annual energy savings at a cost of approximately $20,000, with an expected payback of about 6.2 years. This appears to be a small gain but along with other upgrades it will have an added impact on energy savings. d. Pumps i. The main constant volume heating circulations pumps for the school can be changed out for variable speed (VFD) pumps. VFD pumps can run at lower speeds when the school has a low heating demand, which will save power and reduce cost. The main circulation pump can also be controlled to only run when there is a heating demand, rather than run on a time clock as it currently does. ii. The constant duty domestic hot water recirculation pump can be replaced with a pump that runs on an electric timer and only operates during school hours. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 7 iii. The utilidor heat trace pump and the domestic water service recirculation pump can both be operated based on the outside air temperature rather than run constantly as they currently are. iv. The pump changes will cost approximately $30,000, provide roughly 5% energy savings for the building with a payback of about 2.4 years. e. Thermostat Afterhours Setback: The school heat is currently controlled such that the building operates with Day and Night temperature settings, with hours set using a time clock and temperatures adjusted using one of five Night setback thermostats. This system has inherent flaws that make it undesirable. It is recommended that each space be provided with a programmable thermostat with schedules set to match the occupancy of the space. In addition it is recommended that all spaces have their temperatures reduced to 60 degrees F when unoccupied. Again this work is linked to an overall building controls upgrade, but the approximate cost would be $6,400, with an energy savings of about 5% and payback of less than 1$year. f. Add Occupancy Sensors for Lighting: Occupancy sensors are recommended for most spaces in the building. The cost is about $12,000, with a savings near 4% and payback around 1$year. g. Upgrade Exterior Lighting: There are 15 exterior wall mounted light fixtures that use high pressure sodium (HPS) lamps and only operate during dark times of the year. It is recommended that the fixtures be replaced with light emitting diode (LED) fixtures. If the fixtures are replaced the energy savings will be approximately 1% at a cost of about $22,500 and a payback of about 7.5 years. In addition to EEMs, various Energy Conservation Measures (ECMs) are recommended that were not part of the energy audit model. Some involve a modest capital investment. Others are policies or procedures that are followed by management and employees that require no capital outlay. Examples of recommended ECMs for this facility include: Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 8 1. Consider replacing Use infrared automatic lavatory faucets and water closet flush valves in all restrooms. 2. If automatic flushing is not desired then install water closet flushometer valves for dual level flushing. 3. Turn off computers, monitors, printers, faxes, coffee makers, etc when leaving the office for the day. Turn off computers, monitors, printers, faxes, coffee makers, etc., when leaving for the day. These devices can also be plugged into power strips equipped with occupancy sensors so they will automatically turn off when the building is not in use. 4. Provide occupancy sensors for unoccupied spaces such as bathrooms, storage spaces and utility rooms. The payback for this change may never be realized but the retrofit serves to ensure that unseen lighting is not accidentally left on for long periods of time such as summer break. 5. Install an illuminated indicator to show if attic lighting is on. It is not practical to install occupancy sensors in the attic due to the large area. However small light bulbs or illuminated switches could be installed on the walls just outside the attic access doors to indicate if the lighting is on. This will help to reduce the likelihood of attic lights accidentally being left on. 6. Disconnect refrigeration equipment over the summer, including walk$in units and residential style refrigerators throughout the building. This will save approximately $2,000/year. The priority recommendations in the detailed report are estimated to save $82,603/year, with an installed cost of $169,805, for a 2.1 year payback. This does not include design or CA services, but overall it does indicate a cost effective energy savings program. 3. Audit and Analysis Background: a. Program Description: This audit included services to identify, develop, and evaluate energy efficiency measures at the subject building. The scope of this project included evaluating the building shell, lighting, other electrical systems, and Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 9 heating, ventilating, and air conditioning (HVAC) equipment. Measures were selected such that an overall simple payback period of 8 years or less could be achieved. b. Audit Description and Methodology: Preliminary audit information was gathered in preparation for the site survey, including benchmark utility consumption data, floor and lighting plans, and equipment schedules where available. A site visit was performed to inventory and evaluate the actual building condition, including: i. Building envelope (roof, windows, etc) ii. Heating, ventilating, and air conditioning iii. Lighting systems and controls iv. Building specific equipment v. Plumbing systems c. Method of Analysis: The information gathered prior to the site visit and at the site visit is entered into AkWarm$C, an energy modeling developed for Alaska Housing Finance Corporation (AHFC) specifically to identify forecasted energy consumption which can be compared to actual energy consumption. AkWarm$C also has some pre$programmed EEM retrofit options that can be analyzed with energy savings forecasted based on occupancy schedules, utility rates, building construction type, building function, existing conditions, and climatic data that is already uploaded to the program based on the zip code of the building. When new equipment is proposed, energy consumption is calculated based on manufacturer’s cataloged information. Cost savings are calculated based on the historical energy costs for the building. Installation costs include labor and equipment to estimate the full up$front investment required to implement a change, but design and construction management costs are excluded. Costs are derived from Means Cost Data, industry publications, experience of the auditor, local contractors and equipment suppliers. Maintenance savings are calculated were applicable and are added to the energy savings for each EEM. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 10 The cost and savings are applied and a simple payback and simple return on investment (ROI) is calculated. The simple payback is based on the number of years that it takes for the savings to pay back the net installation cost (Net Installation divided by Net Savings.) A simple life$time calculation is shown for each EEM. The life$ time for each EEM is estimated based on the typical life of the equipment being replaced or altered. The energy savings is extrapolated throughout the life$time of the EEM. The total energy savings is calculated as the total life$time multiplied by the yearly savings. d. Limitations of the Study: All results are dependent on the quality of input data provided, and can only act as an approximation. In some instances, several methods may achieve the identified savings. This report is not intended as a final design document. A design professional, licensed to practice in Alaska and in the appropriate discipline, who is following the recommendations, shall accept full responsibility and liability for the results. Budgetary estimates for engineering and design of these projects in not included in the cost estimate for each measure, but these costs generally run around 15% of the cost of the work. 4. Acknowledgements: We wish to acknowledge the help of numerous individuals who have contributed information that was used to prepare this report, including: a. Alaska Housing Finance Corporation (Grantor): AHFC provided the grant funds, contracting agreements, guidelines, and technical direction for providing the audits. AHFC reviewed and approved the final short list of buildings to be audited based on the recommendation of the Technical Service Provider (TSP). b. Bering Strait School District (Owner): The BSSD provided building access, original construction plans, two years energy Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 11 billing data, building schedules and functions, as well as other resources needed to perform the audit. c. Central Alaska Engineering Company (Benchmark TSP): Central Alaska Engineering Company compiled the data received from the BSSD and entered that data into the statewide building database, called the Alaska Retrofit Information System (ARIS). d. Richard S. Armstrong, PE, LLC (Audit TSP): This is the TSP who was awarded the projects in the Arctic Slope Regional Corporation, Bering Straits area, and the Nana area. The firm gathered all relevant benchmark information provided to them, cataloged which buildings would have the greatest potential payback, and prioritized buildings to be audited based on numerous factors, including the Energy Use Index (EUI), the Energy Cost Index (ECI), the age of the building, the size of the building, the location of the building, the function of the building, and the availability of plans for the building. They also trained their selected sub$contracted auditors, assigned auditors to the selected buildings, and performed quality control reviews of the resulting audits. They prepared a listing of potential EEMs that each auditor must consider, as well as the potential EEMs that the individual auditor may notice in the course of his audit. Richard S. Armstrong, PE, LLC also performed some of the audits to assure current knowledge of existing conditions. 5. Building Description and Function: The subject structure is called the Stebbins Tukurngailnguq School, which was constructed in 1992. The building serves as a kindergarten through twelfth grade (K$12) educational facility, which includes classrooms, administrative offices, a commercial kitchen, a multi$purpose room/cafeteria, a gymnasium, locker rooms, vocational education room with shop, restrooms, and multiple storage and utility spaces. The building is primarily a single story structure with limited second story occupancy consisting of a mezzanine around 3/4 of the gymnasium, one apartment, one multi$ person sleeping room and/or meeting room and storage. An enclosed attic space in the center of the school serves as a mechanical room. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 12 The gymnasium fan room is connected to the gymnasium mezzanine. The entire school is on raised piles with about 4$feet of space between the bottom of the building and the surface of the ground. The gymnasium, student shop, multi$purpose room, north and south entries have high ceilings extending to the underside of the roof. This is also true of three locations in the east corridor along the classrooms where clerestorys are installed. Corridors and locker rooms have ceilings just under 9 feet high. Classrooms have “peaked” ceilings partly following the roof slope with an average height of about 10 feet. The offices and kitchen and various storage and utility rooms have ceilings heights around 9.5 feet high. The gymnasium has an average ceiling height of 23.5 feet. The building roof is constructed of TJL/W and other similar ‘TJ’ style trusses with plywood and metal roofing on the exterior and 2$layers of gypsum wall board on the interior. The interstitial space is filled with R$60 fiberglass batt. The bottom of the building is constructed of TJL/W trusses with plywood on the interior, gypsum wall board on the exterior and R$60 blown$in fiberglass. The exterior walls are 2x10 wood studs with gypsum wall board on the interior, plywood, gypsum wall board and cedar siding on the exterior, and filled with R$30 batt insulation. The overall building design and construction is similar to many schools that were built in Western Alaska at that time. The building is in good condition overall and appears to operate more or less as designed. The building is occupied from the middle of August through the middle of May. The school is unused during the summer months. a. Heating System: The school heating plant is in the northwest corner of the school building. The building heating system consists of two Weil McLain cast iron sectional boilers with Gordon$Piatt model R8.3$0$15 single$stage burners. The boilers provide heat to the school buildings and one teacher housing building. The boilers are original to the 1992 school construction. Hot glycol is circulated around the building using a Grunfos model UMC 65$80 (labeled H$7), 3$ speed circulator, set at speed 2, with a 2 HP motor. The pump is a duplex setup with primary and back up pumps mounted on the same frame. The pump is operated on a time clock so it runs constantly during the school day. The pump is also connected to the Night set back thermostats in Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 13 the building to operate as needed outside of school hours. Both ventilation fans (V$1 and V$12) are equipped with heating coils and each is served by a dedicated duplex pump arrangement. Pump H$9 serves V$1 and is a Grundfos UMC 65$80, 3$speed unit, set at speed 2, with a 1 HP motor. Pump H$10 serves V$12 and is a Grundfos UMC 65$80, 3$ speed unit, set at speed 2, with a 3/4 HP motor. A heat trace pump (H$8) provides heat for the utilidors under the building and runs constantly. It is a Grundfos UMS 50$80, 3$speed unit, set at speed 3, with a 1/3 HP motor. None of the pumps are equipped with variable frequency drives (VFD), so they run at full speed when they operate. Heat is distributed throughout the building using fintube baseboard in most perimeter and some interior spaces, cabinet unit heaters in the gymnasium, vestibules, and corridors, unit heaters in utility spaces, and some supplemental heat through tempered ventilation air. b. Ventilation System: There are two ventilation fans in the building as well as multiple exhaust fans. V$1 is the fan that serves all of the building except the gymnasium. It is also designed to provide make$up air for the kitchen cooking line exhaust fan, V$9. V$12 serves the gymnasium. V$3 is the relief/exhaust fan for V$1 and is interlocked to operate with that unit. V$1 is operated using a time clock and the flow rate is adjusted using a VFD. It was designed to run from 3,000 cfm up to 10,700 cfm. The higher flow rate is designed to be used for make$up air when V$9 operates. V$1 provides 100% outside air. V$3 operates with V$1 and has a VFD to vary its speed to track V$1 up to 9,100 cfm and provides 100% relief/exhaust. An energy recovery device called a tilt coil (V$ 2) is installed in the outside and relief/exhaust ducts. It is intended to absorb heat from the relief/exhaust air stream and transfer it to the outside air stream before it enters V$1. The device appears to be operational and provides heat transfer with about 35% efficiency. Heating of ventilation (outside) air is a significant source of energy consumption for commercial buildings. State of Alaska design codes mandate that certain quantities of ventilation air must be provided. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 14 However, there are devices and strategies that can be employed to regulate the introduction of ventilation air so energy is not wasted, such as demand control ventilation based on CO2 concentration. c. Plumbing System: Water is provided from the village utility and there is not any on$site storage. Fixtures include water closets, lavatories, showers, classroom sinks, mop sinks, and large sinks for cooking. Most fixtures are located in bathrooms, locker rooms, custodial closets and the commercial kitchen. Classrooms for the younger elementary school children have adjoining water closets and lavatories as well as sinks in the classroom. d. Domestic Hot Water: How water for most of the building is generated using a shell in tube heat exchanger (H$26) and stored in a 300$gallon insulated tank (H$11) at about 130 degrees F. Hot water is supplied to the kitchen using a 70$ gallon oil fired water heater (P16) that draws water from H$ 11. The kitchen water is supplied over 140 degrees F. No additional hot water storage is provided. There is a hot water recirculation pump that runs constantly to provide instant hot water to remote fixtures. e. Lighting: Typical lighting used throughout occupied spaces in the building is provided with T$8 fluorescent fixtures using electronic ballasts and controlled manually with a single toggle switch. The gymnasium has high bay lighting fixtures with (5) 2$tube, plug$in, compact fluorescent bulbs at 55 watts each. Gymnasium lights are switched on manually. The multi$purpose room has two high pressure sodium (HPS) fixtures that are operated manually. Exterior lights are 150 watts HPS wall packs. Exterior lights operate using daylight sensors. f. Fire Sprinkler: The building is equipped with a fire sprinkler protection system throughout. Water is stored in bulk tanks across the road from the school and piped underground to the sprinkler riser in the mechanical room. Water is Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 15 circulated in the water line between the school and water treatment building across the road to keep the line from freezing. g. Additional Buildings: The fuel oil use benchmarked for this building included fuel used in teacher housing. Some of the teacher housing buildings have their own boilers and some use heating water from the school boilers. The commercial energy audit only takes the school building into consideration so the additional floor area and construction types for the additional buildings are not taken into account. However, in order to make the model fuel oil consumption match the benchmark data the school inputs were "padded" to make up the difference. Specifically the infiltration rate was set very high. The additional fuel used by "infiltration" will not be affected since no recommendations are made to improve the building envelope. The overall energy saved by the recommended upgrades and/or operational adjustments would be the same whether the teacher housing fuel use was taken into consideration or not. All that being stated, it is highly recommended that energy upgrades be made to teacher housing as the building envelopes and heating equipment are very inefficient. 6. Historic Energy Consumption: Energy consumption is modeled within the AkWarm$C program. The program only analyzes 12 months of data, so where 24 months of data are available, the data is averaged and input to AkWarm$C to provide more accuracy. The energy consumption data is presented and graphed in the attached AkWarm$C program results. Based on the benchmark energy data for 2009 and 2010, the average electric consumption for the building was 295,986 kWh/year at an average cost of $149,915/year. The average fuel oil consumption was 27,672 gallons/year, at an average annual cost of $94,692/year. 7. Energy Efficiency Measures Considered or Recommended: The building was examined for application of a multitude of potential EEMs that are discussed below. Those EEMs that appear to have an Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 16 application for the subject building are further analyzed for estimated payback periods, either within the AkWarm$C program or separately within this report. The accuracy of the cost estimates and paybacks varies significantly due to a multitude of conditions, but is estimated to be approximately +/$ 25%. Assumptions made regarding energy costs and the life of the EEM, noting that post$construction measurement and verification are based on energy savings, not energy cost savings. Many of the selected EEMs are analyzed within the AkWarm$C program using the schedules and estimated costs input into the model. a. Occupancy Sensors for Lighting: The occupied spaces in the building can be retrofitted with occupancy sensors so the lights are only on when rooms are in use. This applies to hallways, classrooms, offices, storage rooms, assembly rooms, and restrooms. Though most rooms will be occupied during the majority of the school day, certain times of the day, such as lunchtime, will cause most rooms to be empty. Occupancy sensors have improved over the years, increasing their reliability and reducing false starts and stops. Dual technology occupancy sensors combine passive infrared (PIR) and ultrasonic technologies into one unit to achieve precise coverage and to eliminate false triggers. The sensors can be mounted on the wall in place of the existing light switch, or on the ceiling where more uniform coverage and detection is desired in a larger room. Wall switch type automatic occupancy sensors are appropriate for small rooms, such as utility rooms, one person toilet rooms, small open offices, and places where the wall switch is located such that occupants can be detected with line$of$sight from anywhere in the room. They can turn lights on and off based on both occupancy and ambient light levels. Many also offer the option of manual override switches, allowing the occupant to adjust lighting levels or turn off the lights all together. Devices in break rooms, utility rooms, storage rooms, small offices, and small open (non$partitioned) bathrooms can save up to 60% of the cost of the lighting where rooms are infrequently used, but the lights are typically left on. Occupancy sensors are not recommended for basements and crawlspaces since the Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 17 spaces are typically broken up with shelving, boxes and partition walls, requiring too many sensors to be installed. It is recommended that light or illuminated switches be installed above the floor near crawlspace accesses so it is possible to see whether crawlspace lights have been turned off without entering the crawlspace. b. Exterior Lighting Upgrade: High$intensity discharge (HID) fixtures, such as high pressure sodium (HPS), are commonly used for building exterior lighting in Alaska because they perform well in cold weather and are more efficient than many other types of lighting. However, light emitting diode (LED) fixtures are proving to be a viable alternative to HPS. LED fixtures use nano reflector technology with drivers offering 50,000 hours life, about 6 years, as compared to only 20,000 hours with high$intensity discharge (HID) fixtures. LED fixtures offer the instant$on feature of fluorescent fixtures but use significantly less energy than the HID fixtures. LEDs have an added benefit of operating more efficiently (using less power) as the ambient temperature gets colder, and some have been factory tested to operate down to $40 deg F (actual installations in Antarctica and Fairbanks indicate they operate at lower temperatures as well) depending on manufacturer. The proposed LED fixtures are dark sky compliant, using 100% cutoff optics to reduce light pollution. LEDs provide a different type of light than HPS, both in color and lumen output, that has the effect of providing a clearer, brighter light while using less power than a HPS bulb. The following chart indicates energy savings for various exterior building mounted light fixtures (MH Metal Halide; HSP High Pressure Sodium) using Scotopic lighting measurements: HID Lamp HID System Wattage LED System Wattage Energy Savings (%) 150W HPS 188W 54W 71 Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 18 c. HVAC Control: The building HVAC systems are operated using basic electric controls. They provide effective control when looking at the building as a whole but they are not able to address the unique requirements of each space, specifically with regard to temperature. It is recommended that the existing HVAC controls be upgraded to an electronic system that will provide tighter control of temperature and ventilation throughout the building. Programmable thermostats will allow the heat demand for each space to be specifically programmed to match the occupancy of the space. Pressure and/or temperature sensors throughout the building will enable the ventilation fans to adjust speed and amount of outside air to meet occupancy demands. This will require the installation of new thermostats and sensors, actuators, valve motors, control dampers, control panel(s) and low (24) voltage wiring throughout the building. Most of the wiring can be installed in the attics and above suspended ceilings, making for a simpler installation and cleaner appearance. d. Ventilation: The main ventilation fan for the building, V$1, supplies 100% outside air and the relief/exhaust fan, V$3, sends 100% of its airflow out of the building. An energy recovery device known as a tilt coil is installed between the outside and relief/exhaust duct to reclaim some of the heat from the outgoing air stream and dump it into the incoming airstream. The device operates at roughly 35% efficiency, meaning 65% of the heat in the outgoing airstream is thrown away. A better, more efficient design for air handling is to recirculate some of the relief air back into the incoming air stream and use it to temper the outside air. If the outside air stream was set at 15% then 85% of the return air is being reused by ventilation system. This allows 85% of the heat to be reclaimed rather than just 65%. This will require installing a bypass duct and damper between the outside and relief/exhaust ducts, and another damper to regulate the amount of outside air drawn into the fan. Ideally the bypass duct would be installed on the side of the tilt coil that is closest to the fan equipment in order to continue using the tilt coil to extract heat from the relief air before it exits the building. The Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 19 plans indicate that V$3 serves as the return, exhaust and relief fan, including exhausting air from the locker rooms. Since code does not permit the recirculation of exhaust air into the building a dedicated exhaust fan will have to be provided for the locker rooms, and any other such spaces, and the ductwork will need to be modified. Given the potential for cost savings with these changes they would be very worthwhile. e. Ventilation Control: The ventilation fans serving the school were designed to function using time clocks and electrical connections with other fans. It appears that the units are working as designed however control upgrades can be made that will make it simpler to program the fan schedules and allow the fans to vary their performance based on space conditions. The following items would improve the performance of the fan units and reduce the amount of energy they consume: i. Operation Schedules: Time clocks are analog devices that function using markers fastened to a dial. They perform well and are very reliable. However setting them up is time consuming so once a schedule is set it is not likely to change. This appears to be the case with main ventilation fan, which is running 7:00 A.M. to 11:00 P.M. every day including the weekends. This does not fit the school usage and is wasting energy. There also appears to be concern about VFD operation because the VFD was locked in at 30 hertz (1/2 speed). The following programming changes are recommended: 1. V1, Main School Building (Suggested Operation) – Operate the unit only during school hours. Set the outside air and bypass dampers to maintain 15% outside airflow and set the VFD speed such that 15% outside air meets the ventilation requirement of the school (to be determined). When the kitchen exhaust fan is operating the outside air damper can open as Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 20 needed to maintain a positive building pressure. If the building requires cooling the outside air damper can open and the fan speed can increase to meet the demand. Replace the front office fan override switch with an electronic timer. 2. V12, Gymnasium – Operate the unit during known periods of occupancy such as lunch hours and scheduled “open gym” hours. Provide with VFD to vary airflow based on ventilation and cooling requirements. Replace the front office fan override switch with an electronic timer. ii. Carbon Dioxide (CO2) Monitoring: The amount of CO2 in a building has been shown to have a direct effect on the performance of the occupants in the building. High levels of CO2 cause occupants to feel sleepy and lose concentration. It is also an indication that other indoor contaminants, such as volatile organic compounds (VOCs), odors and excessive humidity are likely increasing in concentration. For these reasons ventilation air is required by code to refresh indoor building air. Typically the ventilation rate is determined based on the number of occupants and space sizes. In many cases this over$ventilates the space. Another method of ventilating spaces is called demand control ventilation, which entails varying the amount of outside air supplied based on CO2 levels in the building. Sensors can be placed in spaces throughout the building (preferred) or in the return air duct at the ventilation fans, and the fan outside air dampers can be modulated to increase or decrease the outside air delivered to the building. This modification applies specifically to V$12 and may also be appropriate for V$1. f. VFD Heating Pumps: In most cases heating circulators are designed for greater flow rates than is needed during normal operation. Bypass valves are installed to allow the constant volume of flow to continue even when a small amount of that Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 21 flow is providing heat. Energy is wasted circulating heated glycol that is not needed. There are a number of pumps on the market that have variable frequency drives (VFD), which allow the speed of the motor to be adjusted to match the flow rate demand. Pump affinity laws show that motor speed and power have a cubic mathematical relationship to each other. As the pump speed is reduced “X” RPM the power consumption is reduced by X1/3 watts (or horsepower), showing that a small change in pump speed has an amplified affect on power input. Operating pumps at lower speeds when there is lower flow demand significantly reduces power consumption. It is recommended that the heating circulators be replaced with VFD pumps so power savings can be realized. g. Boiler Temperature Outdoor Air Reset: As the outside air temperature varies building heat loss varies as well, losing heat at a faster rate as the ambient temperature drops. Boiler systems are typically sized to meet the heating demands of the coldest expected temperatures. These extreme temperatures may only occur for short durations in a given winter and will vary in frequency and length year to year. Most cast iron sectional boilers supply heating water at the same temperature year$round. During periods of warmer weather in the heating season high heating water supply temperatures may cause space temperatures to overshoot setpoints because the hot boiler water dumps heat into the building at a faster rate than the building is losing it, leading to occupant discomfort. This will also cause the boilers to cycle more often since it takes less time to heat the returning water, putting unnecessary wear on the boilers. A common way of handling this issue is to use an outdoor reset controller to reduce the heating loop temperature so that heat is transferred into the building closer to the rate at which the building is losing heat. Outdoor reset varies the boiler or heating loop water temperature based on the ambient temperature – increasing the water temperature when outdoor conditions are cold and decreasing water temperature for warmer outdoor conditions. It was observed on site that maintenance personnel were manually adjusting the boiler temperature to give the same effect. In order to Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 22 maintain tighter control and prevent issues such as setting the boiler temperature too low (causing the boiler to condense or providing inadequate heating water temperatures for the hot water generators), or forgetting to reset the boiler temperature, it is recommended that a controller be installed that will perform the outdoor reset automatically. There is not a provision for simulating this in the AkWarm$C program so no energy savings are considered here. However it is recommended that a licensed professional engineer perform the design for installation of this controller at which time an energy savings analysis could be performed. h. Domestic Hot Water Recirculation: The domestic hot water system is provided with a small pump that circulates the hot water loop back to the water heater so there is always hot water available at the furthest fixtures in the building. This pump operates constantly, which is unnecessary since hot water is only needed during building occupancy. It is recommended that controls be provide for the hot water recirculation pump so it will only run during school hours, which will reduce the energy consumed by the pump. i. Waste Heat: The school building is not currently supplied with waste heat. However the school is less than 0.5 miles from the village power utility. If the school was supplied with waste heat from the village power plant it would have a tremendous impact on energy savings for the school, likely surpassing fuel oil as the primary heating source. Connecting the school heating plant to the village power plant would require a large capital investment but could have a payback of 10$15 years. No investigation has been performed on the amount of heat that would be available from the power plant, which would require a thorough engineering analysis. It is recommended that a preliminary investigation be performed to determine the viability of this option. j. Fuel Oil Metering: It is recommended that fuel oil meters be installed to track the amount of fuel used by the boilers and electric generator. The only methods currently used on site for Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 23 tracking fuel usage are recording the amount of fuel put into bulk fuel storage tanks when they are refilled and maintenance personnel manually recording the fuel levels in the tanks. Neither method is able to provide precise information nor does it give a detailed picture of the rate at which fuel is used. In order to understand current and future fuel consumption, a fuel meter should be installed on the boiler fuel line and another on the generator fuel line. The Pathfinder Instruments FM$200 meter is for fuel pipes sized ¾” to 1” (different meters, must specify pipe size), and they cost around $225 each. They operate at a flow range of 4$20 GPM. These are mechanical meters with strainers and 3$digid display that shows both present fuel use, and cumulative fuel use. This information can be tied into the building DDC system and saved as trend log data and/or the meter can have an analog dial for visual inspection. Any ESCO contract, or AHFC financed contract will require fuel metering to verify paybacks of energy conservation measures. Electronic turbine meters are also available. See pathfinderinstruments.com for product information. 8. Interactive Effects of Projects: The AkWarm$C program calculates savings assuming that all recommended EEM are implemented. If some EEMs are not implemented, savings for the remaining EEMs will be affected, in some cases positively, and in others, negatively. For example, if the fan motors are not replaced with premium efficiency motors, then the savings for the project to install variable speed drives (VFDs) on the fans will be increased. In general, all projects were evaluated sequentially so that energy savings associated with one EEM would not be attributed to another EEM as well. For example, the night setback EEM was analyzed using the fan and heating load profile that will be achieved after installation of the VFD project is completed. By modeling the recommended projects sequentially, the analysis accounts for interactive effects between the EEMs and does not “double count” savings. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 24 Interior lighting, plug loads, facility equipment, and occupants generate heat within the building. When the building is in cooling mode, these contribute to the overall cooling demands of the building; therefore lighting efficiency improvements will reduce cooling requirements on air conditioned buildings. Conversely, lighting efficiency improvements are anticipated to increase heating requirements slightly. Heating penalties are included in the lighting project analysis that is performed by AkWarm$C. 9. Loan Program: The Alaska Housing Finance Corporation (AHFC) Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State of Alaska program enacted by the Alaska Sustainable Energy Act (senate Bill 220, A.S. 18.56.855, “Energy Efficiency Revolving Loan Fund). The AEERLF will provide loans for energy efficiency retrofits to public facilities via the Retrofit Energy Assessment for Loan System (REAL). As defined in 15 AAC 155.605, the program may finance energy efficiency improvements to buildings owned by: a. Regional educational attendance areas; b. Municipal governments, including political subdivisions of municipal governments; c. The University of Alaska; d. Political subdivisions of the State of Alaska, or e. The State of Alaska Native corporations, tribal entities, and subsidiaries of the federal government are not eligible for loans under this program. Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 25 Appendix A: Photos North Elevation North Entrance, Classrooms on left, Administration and Mechanical Room on right, Gymnasium roof visible on right School pile foundation Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 26 West Elevation – Gymnasium wall, Student Shop entrance Southwest Corner Elevation – Classrooms and South Entrance Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 27 Southeast Corner – Classrooms and South Entrance ramp West Elevation – Classrooms, Clerestorys on roof Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 28 Typical Hallway, low ceiling Typical Hallway, high ceiling with Clerestory Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 29 Typical Classroom MultiPurpose Room/Caffeteria Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 30 Gymnasium, North wall and Mezzanine Gymnasium, Southeast corner and Mezzanine Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 31 Kitchen cooking equipment under exhaust hood Kitchen dish washing equipment Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 32 Kitchen walk in refrigerator/freezer and rolling refrigerator Walk in refrigerator/freezer condensing units in attic Fan Room Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 33 Main building air handler (VF1) VF1 variable frequency drive (VFD) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 34 VF1 Time Clock Main building relief air fan (V3) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 35 Gymnasium air handler (VF12) Oil fired boiler (typical of 2) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 36 Heating circulation pumps School domestic hot water storage tank (H11) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 37 Domestic hot water heat exchanger serving H11 (H26) Kitchen domestic water heater (P16) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 38 Typical outside air damper in Mechanical Room Night and Day thermostats (typical of 5 in building) Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 39 Stebbins Village, Ariel View Village Power Utility School Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 40 Appendix B: AK Warm Energy Model Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 1 ENERGY AUDIT REPORT – PROJECT SUMMARY – Created 3/2/2012 9:31 AM General Project Information PROJECT INFORMATION AUDITOR INFORMATION Building: Stebbins K-12 School (Tukurngailnguq School) Auditor Company: RSA Engineering, Inc. Address: Stebbins Alaska 99671 Auditor Name: Adam Wilson City: Stebbins Auditor Address: 2522 Arctic Blvd Suite 200 Anchorage, AK 99503 Client Name: Richard Ried Client Address: PO Box 225 Unalakleet AK 99684 Auditor Phone: (907) 276-0521 Auditor FAX: Client Phone: (907) 624-3611 Auditor Comment: Client FAX: Design Data Building Area: 36,935 square feet Design Heating Load: Design Loss at Space: 1,087,664 Btu/hour with Distribution Losses: 1,087,664 Btu/hour Plant Input Rating assuming 82.0% Plant Efficiency and 25% Safety Margin: 1,658,024 Btu/hour Note: Additional Capacity should be added for DHW load, if served. Typical Occupancy: 218 people Design Indoor Temperature: 71.7 deg F (building average) Actual City: Stebbins Design Outdoor Temperature: -34 deg F Weather/Fuel City: Stebbins Heating Degree Days: 14,272 deg F-days Utility Information Electric Utility: AVEC-Stebbins - Commercial - Lg Natural Gas Provider: None Average Annual Cost/kWh: $0.527/kWh Average Annual Cost/ccf: $0.000/ccf Annual Energy Cost Estimate Description Space Heating Space Cooling Water Heating Lighting Refrige ration Other Electric al Cooking Clothes Drying Ventilatio n Fans Service Fees Total Cost Existing Building $89,724 $0 $30,392 $75,838 $10,24 3 $30,65 7 $10,123 $0 $6,672 $60 $253,710 With Proposed Retrofits $35,335 $0 $21,851 $60,793 $7,786 $30,70 3 $10,138 $0 $4,442 $60 $171,108 SAVINGS $54,390 $0 $8,542 $15,046 $2,456 -$47 -$14 $0 $2,230 $0 $82,603 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 2 $0 $50,000 $100,000 $150,000 $200,000 $250,000 $300,000 Existing Retrofit Service Fees Ventilation and Fans Space Heating Refrigeration Other Electrical Lighting Domestic Hot Water Cooking Annual Energy Costs by End Use $0 $50,000 $100,000 $150,000 $200,000 $250,000 $300,000 Existing Retrofit #2 Oil Electricity Annual Energy Costs by Fuel Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 3 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 1 Refrigeration: Walk- in Freezer Add new Seasonal Shutdown $1,108 $1 6775.00 0 2 Refrigeration: Walk in Refrigerator Add new Seasonal Shutdown $443 $1 2709.63 0 3 Refrigeration: Moblie Refrigerator in Kitchen Add new Seasonal Shutdown $222 $1 1354.75 0 4 Refrigeration: Chest Freezer Add new Seasonal Shutdown $202 $1 1236.13 0 5 Refrigeration: Refrigerators Add new Seasonal Shutdown $100 $1 609.75 0 6 Setback Thermostat: Gymnasium - 137 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Gymnasium - 137 space. $1,414 $200 95.99 0.1 7 Setback Thermostat: Voc. Ed. - 148 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Voc. Ed. - 148 space. $1,042 $200 70.74 0.2 8 Setback Thermostat: First/Second Grade - 104 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the First/Second Grade - 104 space. $843 $200 57.22 0.2 9 Setback Thermostat: History - 161 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the History - 161 space. $733 $200 49.75 0.3 10 Setback Thermostat: Home Economics - 159 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Home Economics - 159 space. $730 $200 49.53 0.3 11 Setback Thermostat: Itenerant Suite - 204 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Itenerant Suite - 204 space. $718 $200 48.73 0.3 12 Lighting: Classroom, Hallways - Type A3 - Metalux 2P3MX340S36HLCW M/ES2 Replace with 166 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic and Remove Manual Switching and Add new Occupancy Sensor $4,832 $700 42.73 0.1 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 4 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 13 Setback Thermostat: Kindergarten - 103 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Kindergarten - 103 space. $583 $200 39.56 0.3 14 Setback Thermostat: Third/Fourth Grade - 106 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Third/Fourth Grade - 106 space. $576 $200 39.10 0.3 15 Setback Thermostat: Itenerant Suite - 203 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Itenerant Suite - 203 space. $482 $200 32.72 0.4 16 Setback Thermostat: Fifth/Sixth Grade - 127 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Fifth/Sixth Grade - 127 space. $455 $200 30.89 0.4 17 Setback Thermostat: Seventh/Eiighth Grade - 133 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Seventh/Eiighth Grade - 133 space. $448 $200 30.40 0.4 18 Setback Thermostat: Bilingual/Bicultural - 151 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Bilingual/Bicultural - 151 space. $428 $200 29.06 0.5 19 Setback Thermostat: Language - 160 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Language - 160 space. $415 $200 28.20 0.5 20 Setback Thermostat: Business - 155 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Business - 155 space. $412 $200 27.99 0.5 21 Lighting: Classroom, Hallways - Type A3 - Metalux 2P3MX340S36HLCW M/ES2 Perimeter Remove Manual Switching and Add new Occupancy Sensor $3,163 $700 27.66 0.2 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 5 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 22 Setback Thermostat: Math/Science - 154 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Math/Science - 154 space. $366 $200 24.87 0.5 23 Setback Thermostat: Weight Room- 147 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Weight Room- 147 space. $340 $200 23.10 0.6 24 Setback Thermostat: Elementary Resource - 138 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Elementary Resource - 138 space. $303 $200 20.59 0.7 25 Setback Thermostat: High School Resource - 139 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the High School Resource - 139 space. $297 $200 20.14 0.7 26 Lighting: Classrooms, Restrooms - Type B3 - Metalux 2MC340A125LCWM/ ES2 Remove Manual Switching and Add new Occupancy Sensor $844 $300 17.42 0.4 27 Setback Thermostat: Lab - 140 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Lab - 140 space. $231 $200 15.71 0.9 28 Setback Thermostat: Vestibule - 157 Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the Vestibule - 157 space. $191 $200 12.98 1 29 Lighting: Office - Type A4 - Metalux 2P3MX440S48HLCW M/ES2 Perimeter Remove Manual Switching and Add new Occupancy Sensor $596 $300 12.17 0.5 30 Setback Thermostat: Conference - 111 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Conference - 111 space. $177 $200 12.02 1.1 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 6 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 31 Lighting: Office - Type A4 - Metalux 2P3MX440S48HLCW M/ES2 Replace with 10 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic and Remove Manual Switching and Add new Occupancy Sensor $385 $200 11.93 0.5 32 Setback Thermostat: Staff - 113 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Staff - 113 space. $163 $200 11.10 1.2 33 Setback Thermostat: Couns/Sick - 110 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Couns/Sick - 110 space. $161 $200 10.93 1.2 34 Setback Thermostat: Principal - 112 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Principal - 112 space. $142 $200 9.63 1.4 35 Setback Thermostat: Corridor - 115 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 115 space. $107 $200 7.30 1.9 36 Lighting: Classrooms, Restrooms - Type B3 - Metalux 2MC340A125LCWM/ ES2 Perimeter Remove Manual Switching and Add new Occupancy Sensor $398 $400 6.09 1 37 HVAC And DHW Change heat loop circ. pumps to VFD, run domestic hot water recirc. pump on time clock or temp. sensor, only operate heat trace and domestic water circ. pumps when outside temperature is less than 40 deg F $12,641 $30,000 5.92 2.4 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 7 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 38 Ventilation Use CO2 sensors to operate Gym AHU. Provide exhaust fans for the locker rooms to disconnect them from V-1 return air. Install a bypass damper between the exhaust and outside air ducts to allow tempering of outside air intake. Update all HVAC equipment to DDC controls. $41,768 $100,000 5.62 2.4 39 Lighting: Corridor Lighting - Type H - Prudential P1003M42-04SPL-SA (1 lamp 4' fixture according to site visit) Remove Manual Switching and Add new Occupancy Sensor $341 $500 4.23 1.5 40 Lighting: Storage - Type F - Metalux SS240WG/SS-4FT LCWM/ESE Perimeter Remove Manual Switching and Add new Occupancy Sensor $104 $200 3.18 1.9 41 Lighting: Kitchen Storage - Type B2 - Metalux MCM240A125LCWM /ES2 Perimeter Remove Manual Switching and Add new Occupancy Sensor $104 $200 3.17 1.9 42 Lighting: Multipurpose - Type C - Holophane BL2C40LHP27RX Remove Manual Switching and Add new Multi-Level Switch $374 $1,000 2.31 2.7 43 Setback Thermostat: Vestibule - 100 Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the Vestibule - 100 space. $32 $200 2.17 6.2 44 Lighting: Corridor Lighting - Type H - Prudential P1003M42-04SPL-SA (1 lamp 4' fixture according to site visit) Perimeter Remove Manual Switching and Add new Occupancy Sensor $99 $300 2.03 3 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 8 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 45 Setback Thermostat: Corridor - 101 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 101 space. $24 $200 1.65 8.2 46 Lighting: Similar to Type H fixture with T12 lights Remove Manual Switching and Add new Occupancy Sensor $33 $200 1.01 6.1 47 Lighting: Exterior Lighting - Type L - Holophane PARK15AMP27CEBZ AF1 Replace with 15 LED 80W Module StdElectronic $3,006 $22,500 0.83 7.5 48 Lighting: Locker Room, Restrooms - Type I - Holophane 7200-4-H1-WB-TB Perimeter Remove Manual Switching and Add new Occupancy Sensor $25 $200 0.75 8.2 49 Lighting: Similar to Type H fixture with T12 lights Replace with 3 FLUOR T8 4' F32T8 32W Standard Instant StdElectronic $17 $300 0.36 17.3 50 Lighting: Multipurpose - Type C - Holophane BL2C40LHP27RX Replace with 6 FLUOR (4) T8 4' F32T8 32W Standard (2) Instant StdElectronic $210 $5,000 0.26 23.8 51 Setback Thermostat: Corridor - 102 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 102 space. $0 $200 0.00 Infinity 52 Setback Thermostat: Reception - 108 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Reception - 108 space. $0 $200 0.00 Infinity 53 Setback Thermostat: Office - 123 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Office - 123 space. $0 $200 0.00 Infinity 54 Setback Thermostat: Commons - 130 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Commons - 130 space. $0 $200 0.00 Infinity 55 Setback Thermostat: Library/IMC - 141 Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Library/IMC - 141 space. $0 $200 0.00 Infinity Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 9 PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 56 Lighting: Storage - Type B2 - Metalux MCM240A125LCWM /ES2 Remove Manual Switching and Add new Occupancy Sensor $0 $200 0.00 Infinity 57 Lighting: Mech/Elec, Janitor, Storage - Type F - Metalux SS240WG/SS-4FT LCWM/ESE Remove Manual Switching and Add new Occupancy Sensor -$225 $200 -6.96 -0.9 TOTAL $82,603 $169,805 5.89 2.1 ENERGY AUDIT REPORT – ENERGY EFFICIENT RECOMMENDATIONS 1. Building Envelope Insulation Rank Location Existing Type/R9Value Recommendation Type/R9 Value Installed Cost Annual Energy Savings Exterior Doors – Replacement Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Windows and Glass Doors – Replacement Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Air Leakage Rank Location Estimated Air Leakage Recommended Air Leakage Target Installed Cost Annual Energy Savings 2. Mechanical Equipment Mechanical Rank Recommendation Installed Cost Annual Energy Savings 37 Change heat loop circ. pumps to VFD, run domestic hot water recirc. pump on time clock or temp. sensor, only operate heat trace and domestic water circ. pumps when outside temperature is less than 40 deg F $30,000 $12,641 Setback Thermostat Rank Location Size/Type/Condition Recommendation Installed Cost Annual Energy Savings Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 10 6 Gymnasium - 137 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Gymnasium - 137 space. $200 $1,414 7 Voc. Ed. - 148 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Voc. Ed. - 148 space. $200 $1,042 8 First/Second Grade - 104 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the First/Second Grade - 104 space. $200 $843 9 History - 161 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the History - 161 space. $200 $733 10 Home Economics - 159 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Home Economics - 159 space. $200 $730 11 Itenerant Suite - 204 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Itenerant Suite - 204 space. $200 $718 13 Kindergarten - 103 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Kindergarten - 103 space. $200 $583 14 Third/Fourth Grade - 106 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Third/Fourth Grade - 106 space. $200 $576 15 Itenerant Suite - 203 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Itenerant Suite - 203 space. $200 $482 16 Fifth/Sixth Grade - 127 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Fifth/Sixth Grade - 127 space. $200 $455 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 11 17 Seventh/Eiighth Grade - 133 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Seventh/Eiighth Grade - 133 space. $200 $448 18 Bilingual/Bicultural - 151 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Bilingual/Bicultural - 151 space. $200 $428 19 Language - 160 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Language - 160 space. $200 $415 20 Business - 155 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Business - 155 space. $200 $412 22 Math/Science - 154 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Math/Science - 154 space. $200 $366 23 Weight Room- 147 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Weight Room- 147 space. $200 $340 24 Elementary Resource - 138 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Elementary Resource - 138 space. $200 $303 25 High School Resource - 139 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the High School Resource - 139 space. $200 $297 27 Lab - 140 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Lab - 140 space. $200 $231 28 Vestibule - 157 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the Vestibule - 157 space. $200 $191 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 12 30 Conference - 111 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Conference - 111 space. $200 $177 32 Staff - 113 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Staff - 113 space. $200 $163 33 Couns/Sick - 110 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Couns/Sick - 110 space. $200 $161 34 Principal - 112 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Principal - 112 space. $200 $142 35 Corridor - 115 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 115 space. $200 $107 43 Vestibule - 100 Existing Unoccupied Heating Setpoint: 60.0 deg F Implement a Heating Temperature Unoccupied Setback to 55.0 deg F for the Vestibule - 100 space. $200 $32 45 Corridor - 101 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 101 space. $200 $24 51 Corridor - 102 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Corridor - 102 space. $200 $0 52 Reception - 108 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Reception - 108 space. $200 $0 53 Office - 123 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Office - 123 space. $200 $0 54 Commons - 130 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Commons - 130 space. $200 $0 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 13 55 Library/IMC - 141 Existing Unoccupied Heating Setpoint: 70.0 deg F Implement a Heating Temperature Unoccupied Setback to 60.0 deg F for the Library/IMC - 141 space. $200 $0 Ventilation Rank Recommendation Cost Annual Energy Savings 38 Use CO2 sensors to operate Gym AHU. Provide exhaust fans for the locker rooms to disconnect them from V-1 return air. Install a bypass damper between the exhaust and outside air ducts to allow tempering of outside air intake. Update all HVAC equipment to DDC controls. $100,000 $41,768 3. Appliances and Lighting Lighting Fixtures and Controls Rank Location Existing Recommended Installed Cost Annual Energy Savings 12 Classroom, Hallways - Type A3 - Metalux 2P3MX340S36HLC WM/ES2 166 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Replace with 166 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic and Remove Manual Switching and Add new Occupancy Sensor $700 $4,832 21 Classroom, Hallways - Type A3 - Metalux 2P3MX340S36HLC WM/ES2 Perimeter 127 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $700 $3,163 26 Classrooms, Restrooms - Type B3 - Metalux 2MC340A125LCW M/ES2 29 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $300 $844 29 Office - Type A4 - Metalux 2P3MX440S48HLC WM/ES2 Perimeter 18 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $300 $596 31 Office - Type A4 - Metalux 2P3MX440S48HLC WM/ES2 10 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Replace with 10 FLUOR (4) T8 4' F32T8 32W Standard Instant StdElectronic and Remove Manual Switching and Add new Occupancy Sensor $200 $385 36 Classrooms, Restrooms - Type B3 - Metalux 2MC340A125LCW M/ES2 Perimeter 30 FLUOR (3) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $400 $398 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 14 39 Corridor Lighting - Type H - Prudential P1003M42-04SPL- SA (1 lamp 4' fixture according to site visit) 63 FLUOR T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $500 $341 40 Storage - Type F - Metalux SS240WG/SS-4FT LCWM/ESE Perimeter 6 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 $104 41 Kitchen Storage - Type B2 - Metalux MCM240A125LCW M/ES2 Perimeter 4 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 $104 42 Multipurpose - Type C - Holophane BL2C40LHP27RX 6 HPS 400 Watt Magnetic with Manual Switching Remove Manual Switching and Add new Multi-Level Switch $1,000 $374 44 Corridor Lighting - Type H - Prudential P1003M42-04SPL- SA (1 lamp 4' fixture according to site visit) Perimeter 11 FLUOR T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $300 $99 46 Similar to Type H fixture with T12 lights 3 FLUOR T12 4' F40T12 40W Standard StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 $33 47 Exterior Lighting - Type L - Holophane PARK15AMP27CEB ZAF1 15 HPS 150 Watt Magnetic with Daylight Sensor Replace with 15 LED 80W Module StdElectronic $22,500 $3,006 48 Locker Room, Restrooms - Type I - Holophane 7200- 4-H1-WB-TB Perimeter 2 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 $25 49 Similar to Type H fixture with T12 lights 3 FLUOR T12 4' F40T12 40W Standard StdElectronic with Manual Switching Replace with 3 FLUOR T8 4' F32T8 32W Standard Instant StdElectronic $300 $17 50 Multipurpose - Type C - Holophane BL2C40LHP27RX 6 HPS 400 Watt Magnetic with Manual Switching Replace with 6 FLUOR (4) T8 4' F32T8 32W Standard (2) Instant StdElectronic $5,000 $210 56 Storage - Type B2 - Metalux MCM240A125LCW M/ES2 11 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 $0 Energy Audit – Energy Analysis and Cost Comparison AkWarm Commercial Audit Software Stebbins K-12 School (Tukurngailnguq School) Page 15 57 Mech/Elec, Janitor, Storage - Type F - Metalux SS240WG/SS-4FT LCWM/ESE 17 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic with Manual Switching Remove Manual Switching and Add new Occupancy Sensor $200 -$225 Refrigeration Rank Location Existing Recommended Installed Cost Annual Energy Savings 1 Walk-in Freezer Walk-in Freezer Add new Seasonal Shutdown $1 $1,108 2 Walk in Refrigerator Walk in Refrigerator Add new Seasonal Shutdown $1 $443 3 Moblie Refrigerator in Kitchen Commercial Refrigerator (Kitchen) Add new Seasonal Shutdown $1 $222 4 Chest Freezer Chest Freezer Add new Seasonal Shutdown $1 $202 5 Refrigerators 3 Refrigerator Add new Seasonal Shutdown $1 $100 Other Electrical Equipment Rank Location Existing Recommended Installed Cost Annual Energy Savings Cooking/Clothes Drying Rank Recommended Installed Cost Annual Energy Savings ------------------------------------------ AkWarmCalc Ver 2.1.4.2, Energy Lib 3/1/2012 Stebbins Tukurngailnguq K-12 School Comprehensive Energy Audit 56 Appendix C: Existing Plans