Loading...
HomeMy WebLinkAboutCIRI-ANC-CAEC MOA Fire Station 1 and Admin 2012-EE I F O C M P Investm Fire Statio Owner: The M Client: Alaska May 2, 2012 Project # CIR ment Gra on #1 and Municipality of a Housing Fin RI-ANC-CAEC ade Ene d Administ f Anchorage nance Corpora C-45 ergy Au tration Bu ation udit uilding ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 2 of 57 Project # CIRI-ANC-CAEC-45 Prepared for: The Municipality of Anchorage May 2, 2012 Fire Station #1 and Administration Building 100 & 122 East 4th St Anchorage, AK 99517 Audit performed by: Energy Audits of Alaska P.O. Box 220215 Anchorage, AK 98522 Contact: Jim Fowler, PE, CEA#1705 Jim@jim-fowler.com 206.954.3614 Prime Contractor: Central Alaska Engineering Company 32215 Lakefront Drive Soldotna, AK 99699 Contact: Jerry Herring, PE, CEA #1484 AKEngineers@starband.net 907.260.5311 ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 3 of 57 TABLE OF CONTENTS 1. Executive Summary 5 2. Audit and Analysis Background 14 3. Acknowledgements 15 4. Building Description & Function 17 5. Historic Energy Consumption 20 6. Interactive Effects of Projects 20 7. Loan Program 20 APPENDICES Appendix A: Photos 22 Appendix B: AkWarm-C Report 28 Appendix C: Equipment Schedules 33 Appendix D: Additional, Building-Specific EEM detail 40 Appendix E: Specifications supporting EEM’s 44 Appendix F: Benchmark Data 50 ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 4 of 57 REPORT DISCLAIMERS This audit was performed using American Recovery and Reinvestment Act (ARRA) funds, managed by the Alaska Housing Finance Corporation (AHFC). This energy audit is intended to identify and recommend potential areas of energy savings, estimate the value of the savings and approximate the costs to implement the recommendations. Any modifications or changes made to a building to realize the savings must be designed and implemented by licensed, experienced professionals in their fields. Lighting recommendations should all be first analyzed through a thorough lighting analysis to assure that the recommended lighting upgrades will comply with State of Alaska Statute as well as Illuminating Engineering Society (IES) recommendations. Energy Audits of Alaska, LLC and Central Alaska Engineering Company bear no responsibility for work performed as a result of this report. Payback periods may vary from those forecasted due to the uncertainty of the final installed design, configuration, equipment selected, and installation costs of recommended Energy Efficiency Measures (EEMs), or the operating schedules and maintenance provided by the owner. Furthermore, EEMs are typically interactive, so implementation of one EEM may impact the cost savings from another EEM. Neither the auditor, Central Alaska Engineering Company, AHFC, or any other party involved in preparation of this report accepts liability for financial loss due to EEMs that fail to meet the forecasted payback periods. This audit meets the criteria of an Investment Grade Audit (IGA) per the Association of Energy Engineers definition, and is valid for one year. The life of the IGA may be extended on a case-by-case basis, at the discretion of the AHFC. IGA’s are the property of the State, and may be incorporated into AkWarm-C, the Alaska Energy Data Inventory (ARIS), or other state and/or public information system. AkWarm-C is a building energy modeling software developed under contract by AHFC. This material is based upon work supported by the Department of Energy under Award Number DE-EE0000095. This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 5 of 57 1. Executive Summary Building Owner: Municipality of Anchorage 3640 East Tudor Anchorage, AK 99507 Building contact: Paul Urbano Sr. Captain 907-267-5001 Alaska Housing Finance Corporation P.O. Box 10120 Anchorage, AK 99510-1020 Contact: Rebekah Luhrs Energy Specialist 907-330-8141 rluhrs@ahfc.us Guidance to the reader: The Executive Summary is designed to contain all the information the building owner/operator should need to determine how the subject building’s energy efficiency compares with other similar use buildings, which energy improvements should be implemented, approximately how much they will cost and their estimated annual savings. Sections 2 through 7 of this report and the Appendices, are back-up and provide much more detailed information should the owner/operator, or their staff, desire to investigate further. This audit was performed using American Recovery and Reinvestment act (ARRA) funds to promote the use of innovation and technology to solve energy and environmental problems in a way that improves the State’s economy. The audit and this report are pre-requisites to access AHFC’s Retrofit Energy Assessment Loans (REAL) program, which is available to the building’s owner. The purpose of the energy audit is to identify cost-effective system and facility modifications, adjustments, alterations, additions and retrofits. Systems investigated during the audit included heating, ventilation, and air conditioning (HVAC), interior and exterior lighting, motors, building envelope, and energy management control systems (EMCS). ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 6 of 57 The site visit to this building occurred on February 6th, 2012. Fire Station #1 houses one fire department precinct and the Administration building houses the fire department museum and administrative offices. The two buildings are directly adjacent, but not attached and they share the same boilers and electric meter. The fire station houses up to 20 personnel in dormitory style overnight accommodations. Both buildings were built in 2000 and no major modifications have been made. Energy Consumption and Benchmark Data Benchmark utility data for 2009 and 2010 is summarized in Tables 1 and 2 below. Table 1   2009 2010    Consumption Cost Consumption Cost  Electricity ‐ kWh 347,880  $     33,916  380,880  $    39,806   Natural Gas ‐ CCF 60,500  $     61,785  49,121  $    40,343   Totals    $     95,701       $    80,149   A benchmark measure of energy use relative to other similar function buildings in the area is the Energy Use Index (EUI), which takes the total annual energy used by the facility divided by the square footage area of the building, for a value expressed in terms of kBTU/SF. This number can then be compared to other buildings to see if it is average, higher or lower than similar buildings in the area. Likewise, the Energy Cost Index (ECI) is the cost of all energy used by the building expressed in $/SF of building area. Comparative values are shown in Table 2 below. Table 2 – 2009 & 2010 Average EUI and ECI    Subject  Building  Fire Station 11  (Eagle River)  Fire Station 12  & Dispatch  Public Order & Safety  Buildings in Continental  US in 2003**  Energy Use Index  (EUI) ‐ kBTU/SF 225 171 267 116  Energy Cost  Index (ECI) ‐ $/SF $2.94  $3.47  $5.33  n/a  ** Data retrieved from the US Energy Administration database, these figures are for “Places of Public Order and Safety”, the most relevant category tracked by the USEA. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 7 of 57 Evaluation of energy consumption & benchmark data As observed in Table 1 above, there was a 10% increase in electricity consumption and an 18% decrease in natural gas (NG) consumption between 2009 and 2010. These differences are clearly evident in the energy consumption graphs in Appendix F; several reasons are listed below, but the confirmed cause of these changes is not known. Table 2 shows that the subject building’s energy use per square foot falls between the two comparison buildings and its ECI is 15% lower than Fire Station (FS) 11 and 45% lower than FS 12. The reasons for the significant difference in ECI can be observed in Chart 1 below. 80% of the subject buildings consumed energy is in the form of NG, which is 1/5th cost per BTU of electricity. As is typical for Alaskan buildings, a comparison to similar buildings in the continental US shows Alaska buildings have a much higher EUI – which is to be expected given the weather differences. A deeper analysis of the energy consumption of these three fire stations follows: Chart 1 Chart 1 above shows the subject building’s gas and electrical EUI compared to the two other fire stations. 0 50 100 150 200 Subject Building ‐ FS 1 & Admin Bldg Fire Station 11 (Eagle River) Fire Station 12  & Dispatch Natural Gas EUI Electrical EUI ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 8 of 57 Natural gas consumption: All three of the buildings have overnight accommodations for rotating shift firemen. Having audited all three buildings, the auditor believes that the subject building’s excessive NG consumption is a result of: - RTU-7 bringing in 78,000 cubic feet (11,200 CFM for 7 minutes) of unheated OSA every time a vehicle enters or exits through an overhead door - A larger percentage of overhead doors per square foot of vehicle bay, resulting in more OSA infiltration with each door opening (300% more than FS 12 and 150% more than FS 11) - higher occupancy and more calls per day which means more door openings - this building uses NG-fired boiler’s to supply hydronics for snow melt on the apparatus bay aprons and administration building sidewalks, the other buildings do not have snow melt capabilities Electrical consumption: Based on Chart 1, the subject building’s lower electrical consumption appears to be the result of a more efficient building and after the site survey, this is believed to be true. But the significant difference between FS 12 and the subject building’s electrical consumption is deceiving. Upon deeper investigation, FS 12, which is almost identical in use to the subject building (it has adjacent offices, residential quarters, etc.), has a separate communications building on its north side, which has a massive amount (and unknown consumption) of Alaska Land Mobile Radio (ALMR) communications equipment, requiring 25 Tons of cooling capacity. This building shares an electrical meter with FS 12, so its consumption is included in the EUI for FS 12. This is believed to explain the nearly triple consumption when compared to the subject building. Recommended Energy Efficiency Measures Various Energy Efficiency Measures (EEMs) have been analyzed for this building to determine if they would provide energy savings with reasonably good payback periods. EEMs are recommended for reasons including: 1.) they have a reasonably good payback period 2.) for code compliance 3.) end of life (EOL) replacement 4.) reasons pertaining to efficient building management strategy, operations, maintenance and/or safety All the EEMs considered for this facility are detailed in the attached AkWarm-C Energy Audit Report in Appendix B and in Appendix D. Each EEM includes payback times, estimated installation costs and estimated energy savings. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 9 of 57 The summary EEM’s that follow are the only EEM’s that are recommended for this building. Others have been considered (See Appendix D-3) but are not considered to be justified or cost effective. The recommended EEM’s were selected based on consideration from three perspectives: overall efficiency of building management, reduction in energy consumption and return on investment (ROI). Efficient building management dictates, as an example: that all lights be upgraded, that lamp inventory variations be minimized and that all appropriate rooms have similar occupancy controls and setback thermostats - despite the fact that a single or several rooms may have an unjustifiably long payback on their individual lighting or controls upgrade. Some of the summary EEM’s below contain individual EEM’s that are grouped by type (i.e. all relevant lighting upgrades are summed and listed as a single upgrade, all thermostat setback retrofits are grouped together and listed as a single upgrade, etc.). They are prioritized as a group, with the highest ROI (shortest payback) listed first. Table 3 at the end of this section summarizes these EEM’s and Appendix B (the AkWarm-C detailed report) and Appendix D provide additional detail pertaining to each individual recommendation. A.) SETBACK THERMOSTATS The cabinet unit heaters (CUH), unit heaters (UH) and radiant ceiling panels in this building have local, low voltage thermostats which should be replaced with digital thermostats that have occupancy sensing, nighttime and unoccupied setback capabilities. The air handlers and rooftop furnaces are controlled by digital thermostats; it is recommended that these be checked to assure that nighttime and unoccupied setback temperatures are properly programmed for the current building usage. It is further recommended that occupancy sensor thermostats (see Appendix E) be retrofitted in residences as well as the intermittently occupied common areas like the kitchen, exercise and TV rooms so that heat is provided to these rooms only when occupied. Finally, nearly every residence in the building has an ancillary oil-filled electric heater which, onsite personnel stated, have to be used when the OSA temperature is low (<25F) because their rooms are uncomfortably cold. It is estimated that these heaters are adding $2,412/yr in energy costs if they are operating 10 hrs/day during the coldest winter months. It is believed that they could be eliminated after the retro-commissioning recommended in EEM “E” below, either as a result of increasing flow rates to this zone, or altering other HVAC settings. Appendices B-1, 2, 3, 7 and 11 provide detail for this EEM. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 10 of 57 Combined Setback Thermostat EEM’s: Estimated cost $4,500 Annual Savings $9,841 Payback 6 months B.) REFRIGERATION & REFRIGERATED VENDING MACHINES There are (3) refrigerated beverage vending machines, (5) full size residential type refrigerators a small chest freezer and a large upright freezer in this building. The (5) full size refrigerators are all less than 10 years old and appear to be Energy Star models and as such, there is no recommended retrofit. The (2) freezers appear to be 15 years old or older and should be replaced at their end of life (EOL) with Energy star models. The (3) vending machines should have a vendingmiser (see www.vendingmiser.com) installed, which saves an estimated 46% of energy costs by cycling the machine during periods of non-use. These EEM’s are found in Appendix B-5 & 8. Combined refrigeration EEM’s: Estimated cost (incremental difference for the freezers) $ 1,200 Annual Savings $ 505 Payback 2.4 years C.) HEADBOLT HEATERS The (8) duplex outlet headbolt heaters outside this building should be retrofitted with a microprocessor controlled duplex outlet that cycles power based on ambient temperature and heater demand. (See www.iplc.com). Appendix B-10 and Appendix E provided additional detail. Headbolt Heater EEM: Estimated cost $ 2,000 Annual Savings $ 701 Payback 3 years D.) DE-STRATIFICATION FANS In the apparatus bay, there was a measured temperature differential between the thermostat sensors and the ceiling of 9.8 F. It is recommended to add de-stratification fans in the apparatus bay. See Appendix D-2 for more detail. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 11 of 57 De-Stratification Fan EEM: Estimated cost $ 4,800 Annual Savings $ 1,434 Payback 3.3 years E.) HVAC SYSTEM RTU-7 repair Onsite personnel stated that the heater in RTU-7 has not operated “for years” and the temperature in the apparatus bay gets below 50F in the winter, because the sub-floor heating cannot keep up with the incoming OSA. It is assumed that the fan in RTU-7 operates correctly, and is providing make up air when EF-6 and EF-7 are on. It is recommended to repair this gas-fired unit. Estimated costs and savings are not provided, this is a maintenance recommendation. Replace exhaust fans and make up air with air scrubbers Air scrubbers, similar to those used in Fire Stations 11 and 12, are more efficient than exhausting air and heating make up air each time a vehicle enters or exits the apparatus bay. See Appendix D- 4 for details on estimated costs and savings; these figures are included in the total for this EEM below. Retro-commission the HVAC system It is recommended to perform an engineering evaluation and retro- commissioning of the HVAC & HVAC controls in this building. It is assumed that HVAC maintenance including belts, bearings, actuators, etc. are well managed by MOS. It is also assumed that the HVAC controls have not been evaluated and adjusted for the current occupancy and usage of this building since it was originally commissioned 10-12 years ago. A typical, conservative, annual energy savings of 10% ($4,407) of current building heating and cooling costs would be expected after a retro-commissioning of the control system. Estimated cost is $10,000. HVAC System combined EEM’s: Estimated cost $41,985 Annual savings $ 8,229 Payback 5.1 years F.) LIGHTING AND LIGHTING CONTROLS There are several incandescent bulbs in the residences, they should be replaced with CFL bulbs. At the next re-lamp of the ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 12 of 57 building, all T8-32 watt lamps should be replaced with T8-28 watt energy saver lamps. All exterior lighting should be replaced with LED lamps and all rooms in the building should have occupancy sensors installed. The apparatus bay should have ceiling mounted, zoned occupancy sensors installed, so that only the row or section of lighting above the occupant is lit. This lighting could be integrated with the alarm/call notification system so that all appropriate apparatus/hallway/common area lighting is turned on when a fire alarm is recognized. This requires a digital lighting management system (LMS) similar to one shown in Appendix E, which is not included in the estimated cost of this EEM. This EEM summarizes Appendix B-4, 6, 9, 12 through 17 and 19. See Appendix E for more information on occupancy sensors. Combined Lighting Control EEM’s: Estimated cost $ 44,657 Annual Savings $ 5,783 Payback 7.7 years A summary of the estimated cost totals and estimated annual savings totals of the eight (A. through H.) summary EEM’s listed above, is found in Table 3 below, and again at the end of Appendix B. Table 3 Combined total of recommended EEM’s  summarized above:  Estimated total cost $ 99,143  Annual Savings $ 26,493  Simple payback   3.7 years  Does not include design or construction management costs In addition to EEM’s, various Energy Conservation Measures (ECM’s) are recommended. ECM’s are policies or procedures to be followed by management and employees that require no capital outlay. ECMs recommended for this facility include: ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 13 of 57 1. Turn lights off when leaving a room that is not controlled by an occupancy sensor. 2. All man-doors, roll-up doors and windows should be properly maintained and adjusted to close and function properly. 3. Turn off computers, printers, faxes, etc. when leaving the office. 4. Re-configure building occupants to group un-occupied offices (i.e. no tenant or staff using the space), rooms and spaces into the same HVAC zone so that zone’s energy consumption can be set back to minimal levels. 5. A building is a living mini-ecosystem and its use changes. Re- evaluate building usage annually and confirm that building set points, zones, lighting levels, etc. are optimized for the current usage and occupancy. 6. Re-lamp the entire building or entire usage zones (a zone of the building that has similar lighting usage, so lamps have roughly the same lifetime) as part of a scheduled preventative maintenance routine. This assures all lamps are the same color temperature (e.g. 3000K) which enhances occupant comfort and working efficiency. It also minimizes expense because it is more cost effective to order large quantities of the same lamp, and more labor efficient to dedicate maintenance staff to a single re-lamp activity in a building zone, rather than replace individual lamps as they fail. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 14 of 57 2. Audit and Analysis Background Program Description: This audit included services to identify, develop, and evaluate energy efficiency measures for the subject building. The scope of this project included evaluating the building shell, lighting, hot water generation and HVAC equipment. The auditor may or may not identify system deficiencies if they exist. The auditor’s role is to identify areas of potential savings, many of which may require more detailed investigation and analysis by other qualified professionals. a. Audit Description and Methodology: Preliminary audit information was gathered in preparation for the site survey, including benchmark utility consumption data, floor and lighting plans, and equipment schedules where available. A site visit is then performed to inventory and evaluate the actual building condition, including: i. Building envelope (walls, doors, windows, etc) ii. Heating, ventilating, and air conditioning iii. Lighting systems and controls iv. Building specific equipment v. Plumbing Systems b. Benchmark Utility Data Validation: Benchmark utility data provided through AHFC’s initial phase of their REAL program is validated, confirming that meter numbers on the subject building match the meters from which the energy consumption and cost data were collected. If the data is inaccurate or missing, new benchmark data is obtained. In the event that there are inconsistencies or gaps in the data, the existing data is evaluated and missing data points are interpolated. c. Method of Analysis: The information gathered prior to the site visit and during the site visit is entered into AkWarm-C, an energy modeling software program developed specifically for AHFC to identify forecasted energy consumption. The forecasts can then be compared to actual energy consumption. AkWarm-C also has some pre-programmed EEM retrofit options that can be analyzed with projected energy savings based on occupancy schedules, utility rates, building construction type, building function, existing conditions, and climatic data uploaded to the program based on the zip code of the building. When new equipment is proposed, energy consumption is calculated based on manufacturer’s cataloged information. Energy cost savings are calculated based on the historical energy costs for the building. Installation costs include the labor and equipment required to implement an EEM retrofit, but design and construction management costs are excluded. Cost estimates are +/- 30% for this level of audit, and are derived from one or more of the following: Means Cost Data, industry publications, experience of the auditor, local contractors and/or equipment suppliers. Brown Electric, Haakensen Electric, Proctor Sales, Pioneer Door, ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 15 of 57 and J.P. Sheldon, all in Anchorage, were consulted for some of the lighting, boiler, overhead door and air handling retrofit and/or replacement costs. Maintenance savings are calculated, where applicable, and are added to the energy savings for each EEM. The costs and savings are considered and a simple payback period and ROI is calculated. The simple payback period is based on the number of years that it takes for the savings to pay back the net installation cost (Net Installation costs divided by Net Savings.) In cases where the EEM recommends replacement at EOL, the incremental cost difference between the standard equipment in place, and the higher efficiency equipment being recommended is used as the cost basis for payback calculation. The SIR found in the AkWarm-C report is the Savings to Investment Ratio, defined as the annual savings multiplied by the lifetime of the improvement, divided by the initial installed cost. SIR’s greater than 1.0 indicate a positive lifetime ROI. The life-time for each EEM is entered into AkWarm-C; it is estimated based on the typical life of the equipment being replaced or altered. d. Limitations of the Study: All results are dependent on the quality of input data provided, and may only act as an approximation. Most input data such as building and equipment usage, occupancy hours and numbers, building and HVAC operating hours, etc. was provided to the auditor by on site personnel. In some instances, several methods may achieve the identified savings. This report is not a design document. A design professional, licensed to practice in Alaska and in the appropriate discipline, who is following the recommendations, shall accept full responsibility and liability for the results. Budgetary estimates for engineering and design of these projects in not included in the cost estimate for each EEM recommendation, but these costs can be approximated at 15% of the cost of the work. 3. Acknowledgements: We wish to acknowledge the help of numerous individuals who have contributed information that was used to prepare this report, including: a. Alaska Housing Finance Corporation (Grantor): AHFC provided the grant funds, contracting agreements, guidelines, and technical direction for providing the audits. AHFC reviewed and approved the final short list of buildings to be audited based on the recommendation of the Technical Service Provider (TSP). b. The Municipality of Anchorage (Owner): MOA provided a review and brief history of the benchmarked buildings, building selection criteria, building plans, equipment specifications, building entry and coordination with on-site personnel. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 16 of 57 c. Central Alaska Engineering Company (Benchmark TSP): CAEC oversaw the compilation of electrical and natural gas consumption data through their subcontractor, Energy Audits of Alaska, LLC. CAEC also entered that data into the statewide building database, called the Alaska Retrofit Information System (ARIS). CAEC was awarded the auditing contract for this MOA building. d. Energy Audits of Alaska (energy auditor): This firm has been selected to provide audits under this contract. The firm has two mechanical engineers, certified as energy auditors and/or professional engineers and has also received additional training from CAEC and other TSP’s to acquire further specific information regarding audit requirements and potential EEM applications. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 17 of 57 4. Building Description and Function: The site visit and survey of subject building occurred on February 6th, 2012. Both buildings on this site, the fire station and an administration building, are two story structures. The buildings are not connected, but the fire station boilers supply heat to the administration building and it’s sub-sidewalk snow melt system and they share a single electric meter, so they are combined in this audit. The administration building houses a small museum on its first floor and offices on its second floor. The fire station has a large apparatus bay (over 8400 square feet), mechanical rooms, laundry, hose drying and work rooms on its first floor and common areas including a kitchen, exercise facility and TV room, multiple offices and 20 dormitory style residence rooms on its second floor. The fire station also has an attached 4-story hose drying facility. The administration building has 5567 square feet while the fire station has 24,324 square feet including 8417 square feet contained in the apparatus bay. The total building size, calculated from plans is 29,891 square feet. This building is constructed on a 6” reinforced concrete slab poured on grade under the apparatus bay and a 4” slab under all other spaces. The building structure consists of either 12” concrete masonry unit (CMU) and 6” metal stud walls. The support a 4” poured concrete second floor and steel roof trusses with metal roof decking. Roof insulation consists of tapered rigid foam with a minimum thickness of 3” (R-15) covered with an EDPM membrane. Wall insulation values as calculated by AkWarm-C are R-16.0 for the 6” metal stud walls and R-12.1 for the first floor south wall which consists of CMU’s covered with 2” of rigid foam. Exterior walls are covered either with metal siding or rock veneer. Interior walls are either painted CMU or gypsum. All windows in this building are double pane aluminum and in good condition. Overall, both buildings are very well maintained and in excellent condition. Building details are as follows: a. Heating, Cooling, Ventilation and Controls: Heat is provided by two gas fired, dual fuel boilers via hydronic finned tube baseboard radiators, radiant ceiling panels, cabinet unit heaters at all entry points and unit heaters in mechanical and work rooms. Heated ventilation is provided by (7) gas fired rooftop furnaces, although one of them, RTU-7 has nonfunctional heat. Cooling is provided by (6) of the rooftop units and (2) split-system air conditioning units. All hydronics except the unit heaters are fluid valve controlled by local, low voltage thermostats – some of which have been retrofitted ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 18 of 57 with digital models. The unit heaters have wall mounted thermostats controlling the fan with glycol running wild (i.e. no fluid control valve). The RTU’s are controlled by zone using digital thermostats. End effectors are electric actuators and fans are not variable speed. There is not a building-wide, integrated HVAC control system. Apparatus bay: The HVAC design for this space presumably called for heat to be provided by sub-floor hydronics and the gas-fired furnace & make up air unit (MAU), RTU-7. The heating function of RTU-7 has been inoperable for several years, consequently, when OSA temperatures fall below 15F or so, this bay cannot be maintained at comfortable temperatures. Snow Melt: There are heated aprons on the north and south sides of the apparatus bay and on a portion of the north sidewalk outside the administration building. The snow melt system is supplied through a flat plate heat exchanger located in the boiler room and controlled by a Tekmar 662 controller. Energy Recovery: An air to air heat recovery unit was installed in 2007, it runs continuously. Cooling: Six of the seven RTU’s also have cooling capacity totaling 27.25 Tons. Additionally, there are two 3-Ton units serving the residence rooms. b. Appliances: There are (5) residential type refrigerators, (2) gas range/oven units, (3) dishwashers and (3) microwaves in the well equipped kitchen in this fire station. There is also a large commercial clothes washer and electric dryer for contaminated clothing, as well as a stacked washer/dryer for street clothes. This building has 15 PC’s in use; it is generally recommended to replace desktop PC’s with laptops at EOL. c. Plumbing Fixtures: This building contains a total of (10) toilets, (5) urinals, (10) lavatory sinks and (6) showers. All have manual valves except the lavatory sinks, which have proximity sensing valves. The toilets consume 1.6 gallons per flush (gpf), the urinals 1.0 gpf and the shower heads appear to have a 2.6 gallons per minute (gpm) flow rate. See Appendix D-1 for EEM recommendations. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 19 of 57 d. Domestic Hot Water: Hot water for sinks and showers is provided by (4) indirect hot water generators supplied by the boilers. There is an additional electric hot water heater located in the administration building, providing hot water to its lavatory sinks. e. Interior Lighting & Controls: There does not appear to have been any lighting upgrades since the building was constructed in 2000. Room lighting generally consists of T8- 32W fixtures with electronic ballasts. The only occupancy sensor in the building is located in the main entry to the fire station. There are (2) metal halide fixtures in the hose drying tower. Appendix B details the recommendation of a full lighting upgrade. See Appendix E for additional information on occupancy sensors. All exit signs in the building are either LED or unlit, self luminous. f. Exterior Lighting: There are (12) wall pack lights on the exterior of this building; (11) that appear to use 150 watt high pressure sodium bulbs and one using a 1000 watt metal halide bulb. There are 27 HPS-70 watt or 100 watt soffit lights and (2) non-functional landscape/art uplights. g. Building Shell: The building shell is described earlier; it appears to be in good condition, inside and out. h. Motors: There are 3 large (5 HP or larger) motors in use in this building. They are listed in Appendix C and were considered for replacement with premium efficiency motors, see Appendix D-3. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 20 of 57 5. Historic Energy Consumption: Energy consumption is modeled within the AkWarm-C program. The program typically analyzes twelve months of data. Two year’s worth of natural gas and electricity consumption were averaged then input into AKWarm-C. This monthly data is found in Appendix F. Energy consumption was analyzed using two factors: the Energy Cost Index (ECI) and the Energy Use Index (EUI). The energy cost index takes the annual costs of natural gas and electrical energy over the surveyed period of time (two years) divided by the square footage of the building. The ECI for this building is $2.94/SF, the ECI for two very similar buildings, Fire Station’s 11 and 12, are $3.47 and $5.33 respectively. The energy use index (EUI) is the total annual average electrical and heating energy consumption expressed in thousands of BTU/SF. The average of the 2009 and 2010 EUI for this building is 225 kBTU/SF; the average 2009/2010 EUI for Fire Station 11 is 171 kBTU/SF and 267 kBTU/SF for Fire Station 12. The average for Public Order and Safety buildings across the US is 116 kBTU/SF as logged by the US Energy Information Administration. This source data can be viewed at: www.eia.gov/emeu/efficiency/cbecstrends/cbecs_tables_list.htm. 6. Interactive Effects of Projects: The AkWarm-C program calculates savings assuming that all recommended EEM are implemented in the order shown in Appendix B. Appendix D EEM’s are not included in the AkWarm-C model unless referred to in the Appendix B EEM as “see also Appendix D-X”; in these cases, the EEM is included in the AkWarm-C calculations. If some EEMs are not implemented, savings for the remaining EEMs will be affected, in some cases positively, and in others, negatively. In general, all projects were evaluated sequentially so that energy savings associated with one EEM would not be attributed to another EEM as well. By modeling the recommended projects sequentially, the analysis accounts for interactive effects between the EEMs and does not “double count” savings. Interior lighting, plug loads, facility equipment, and occupants generate heat within the building. When the building is in cooling mode, these contribute to the overall cooling demands of the building; therefore lighting efficiency improvements will reduce cooling requirements on air conditioned buildings. Conversely, lighting efficiency improvements are anticipated to increase heating requirements slightly. Heating penalties resulting from reductions in building electrical consumption are included in the lighting analysis that is performed by AkWarm-C. 7. Loan Program: The Alaska Housing Finance Corporation (AHFC) Alaska Energy Efficiency Revolving Loan Fund (AEERLF) is a State of Alaska program enacted by the Alaska Sustainable Energy Act (senate Bill 220, A.S. 18.56.855, ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 21 of 57 “Energy Efficiency Revolving Loan Fund). The AEERLF will provide loans for energy efficiency retrofits to public facilities via the Retrofit Energy Assessment for Loan System (REAL). As defined in 15 AAC 155.605, the program may finance energy efficiency improvements to buildings owned by: a. Regional educational attendance areas; b. Municipal governments, including political subdivisions of municipal governments; c. The University of Alaska; d. Political subdivisions of the State of Alaska, or e. The State of Alaska Native corporations, tribal entities, and subsidiaries of the federal government are not eligible for loans under this program. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 22 of 57 Appendix A - Photos Administration building on left, fire station on right, hose drying tower in left center Administration building – museum on first floor, offices on second floor ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 23 of 57 Snow melt aprons outside fire station entry/exit doors Apparatus bay with subfloor heat ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 24 of 57 Residence hall Exercise facility ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 25 of 57 Kitchen dining area TV room ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 26 of 57 Apparatus sub-floor heat thermostat – note it is “pegged” on at 110F; without operative RTU-7 heat, sub-floor heat cannot maintain reasonable temperatures in the apparatus bay. The slam temperature was measured at 80 F. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 27 of 57 Aerial View of the subject building Administration Building Fire Station NORTH Appendix B – Detailed AkWarm-C report Energy Audit – Energy Analysis and Cost Comparison  AkWarm Commercial Audit Software  Fire Station #1 & Fire Station Administration Offices Page 28   ENERGY AUDIT REPORT – PROJECT SUMMARY – Created 5/3/2012 11:33 AM General Project Information  PROJECT INFORMATION AUDITOR INFORMATION  Building: Fire Station #1 & Fire Station Administration  Offices  Auditor Company: Energy Audits of Alaska  Address: 100 & 122 East 4th Auditor  Name: James Fowler  City: Anchorage Auditor Address: 5935 Pioneer Park Pl    Langley, WA 98260  Client Name: Paul Urbano  Client Address: 100 East 4th   Anchorage, AK 99501  Auditor Phone: (206) 954‐3614  Auditor FAX: (   )    ‐  Client Phone: (907) 267‐5001 Auditor Comment:   Client FAX:   Design Data  Building Area: 29,891 square feet Design Heating Load: Design Loss at Space:  2,720,827  Btu/hour   with Distribution Losses:  2,945,175 Btu/hour   Plant Input Rating assuming 82.0% Plant Efficiency and  25% Safety Margin: 4,489,597 Btu/hour   Note: Additional Capacity should be added for DHW load,  if served.  Typical Occupancy: 35 people  Design Indoor Temperature: 68.6 deg F (building average)  Actual City: Anchorage Design Outdoor Temperature: ‐18 deg F  Weather/Fuel City: Anchorage Heating Degree Days: 10,816 deg F‐days     Utility Information  Electric Utility: Anchorage ML&P ‐ Commercial ‐ Lg Natural Gas Provider: Enstar Natural Gas ‐ Commercial ‐  Lg  Average Annual Cost/kWh: $0.110/kWh Average Annual Cost/ccf: $0.811/ccf     Annual Energy Cost Estimate  Description Space  Heating  Space  Cooling  Water  Heating Lighting Refrige ration  Other  Electric al  Cooking Clothes  Drying  Ventilatio n Fans  Service  Fees Total Cost  Existing  Building  $44,069 $6,200 $4,467 $15,357 $1,553 $9,914 $0 $0 $3,634 $1,842 $87,037  With  Proposed  Retrofits  $30,029 $5,876 $4,573 $8,409 $1,001 $5,042 $0 $0 $3,662 $1,842 $60,434  SAVINGS $14,040 $324 ‐$105 $6,948 $552 $4,872 $0 $0 ‐$28 $0 $26,603    Appendix B – Detailed AkWarm-C report Energy Audit – Energy Analysis and Cost Comparison  AkWarm Commercial Audit Software  Fire Station #1 & Fire Station Administration Offices Page 29                     Appendix B – Detailed AkWarm-C report Energy Audit – Energy Analysis and Cost Comparison  AkWarm Commercial Audit Software  Fire Station #1 & Fire Station Administration Offices Page 30   PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 1 Room electric oil‐ filled heaters  Eliminate after Retro‐ commissioning radiant  panels  $2,412 Included  in Setback  Thermost at and  HVAC  retro‐ commissi oning  costs  14755.00 0 2 Setback Thermostat:  Apparatus Bay  Implement a Heating  Temperature Unoccupied  Setback to 55.0 deg F for  the Apparatus Bay space.  $830 $200 53.61 0.2 3 Setback Thermostat:  Offices, corridors,  common areas other  than kitchen, TV, rec  & workout rooms  Implement a Heating  Temperature Unoccupied  Setback to 55.0 deg F for  the Offices, corridors, &  common areas other than  kitchen, TV, rec & workout  rooms space.  $6,134 $2,000 39.60 0.3 4 Lighting:  Incandescent ‐  residential section  Replace with 13 FLUOR  CFL, A Lamp 15W  $212 + $65 Maint.  Savings $130 13.11 0.6 5 Refrigeration:  Freezers  Replace with 2 Energy Star  versions  $98 $150 9.19 1.5 6 Lighting:  Incandescent ‐  offices  Replace with 18 LED 17W  Module StdElectronic  $186 + $90 Maint.  Savings $450 8.79 2.4 7 Setback Thermostat:  Kitchen, Rec & TV  rooms, exercise  room  Implement a Heating  Temperature Unoccupied  Setback to 60.0 deg F for  the Kitchen, Rec & TV  rooms, exercise room  space.  $266 $500 6.86 1.9 8 Refrigerated Vending  machines  Add Vendingmiser  (www.vendingmiser.com)    $407 $1,050 2.38 2.6 9 Lighting: T8‐3lamp,  add OS ‐ residential  section  At next building re‐lamp,  replace (133) 32 watt  lamps with 133 FLUOR (3)  T8 4' F32T8 28W Energy‐ Saver Instant StdElectronic  and Remove Manual  Switching and Add new  Occupancy Sensor  $1,874 $5,169 2.22 2.8 Appendix B – Detailed AkWarm-C report Energy Audit – Energy Analysis and Cost Comparison  AkWarm Commercial Audit Software  Fire Station #1 & Fire Station Administration Offices Page 31   PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 10 Head Bolt Heaters Remove Manual Switching  and Add new Other  Controls  $701 $2,000 2.17 2.9 11 Setback Thermostat:  Residences  Implement a Heating  Temperature Unoccupied  Setback to 60.0 deg F for  the Residences space.  $199 $1,800 1.43 9 12 Lighting: Exterior  soffit lighting ‐ HPS‐ 70  Replace with 16 LED 17W  Module StdElectronic  $268 $1,200 1.38 4.5 13 Lighting: T8‐2lamp,  add OS ‐ residential  section  At next building re‐lamp,  replace (22) 32 watt lamps  with 22 FLUOR (2) T8 4'  F32T8 28W Energy‐Saver  Instant StdElectronic and  Remove Manual Switching  and Add new Occupancy  Sensor  $209 $1,032 1.24 4.9 14 Lighting: Exterior  Soffit lighting HPS‐ 100  Replace with 19 LED 34W  Module StdElectronic  $379 $1,900 1.23 5 15 Lighting: T8‐3lamp;  already OS ‐ offices  Replace with 2 FLUOR (3)  T8 4' F32T8 28W Energy‐ Saver Instant StdElectronic  $3 $18 1.09 5.7 16 Lighting: T8‐2lamp,  add OS ‐ offices  At next building re‐lamp,  replace (208) 32 watt  lamps with 208 FLUOR (2)  T8 4' F32T8 28W Energy‐ Saver Instant StdElectronic  and Remove Manual  Switching and Add new  Occupancy Sensor  $1,197 $6,998 1.05 5.8 17 Lighting: T8‐3lamp,  add OS ‐ offices  At next building re‐lamp,  replace (90) 32 watt lamps  with 90 FLUOR (3) T8 4'  F32T8 28W Energy‐Saver  Instant StdElectronic and  Remove Manual Switching  and Add new Occupancy  Sensor  $766 $5,760 0.82 7.5 Appendix B – Detailed AkWarm-C report Energy Audit – Energy Analysis and Cost Comparison  AkWarm Commercial Audit Software  Fire Station #1 & Fire Station Administration Offices Page 32   PRIORITY LIST – RECOMMENDED ENERGY EFFICIENCY MEASURES Rank Feature Recommendation Annual Energy Savings Installed Cost SIR Payback (Years) 18 Other Electrical:  Personal Computers  Replace with 15 Laptop at  EOL; This EEM is not  economically justified  since average laptop life is  3‐5 years, but still  recommended as many  users prefer laptops and it  does provide energy  savings  $484 $3,000 0.74 6.2 19 Lighting: Exterior  HPS‐150 wall packs  Replace with 11 LED 50W  Module StdElectronic  $314 + $220 Maint.  Savings $22,000 0.15 70.1 THE FOLLOWING EEM’S WERE CALCULATED OUTSIDE OF AkWARM-C. Savings will affect and be affected by the EEM’s listed above, depending on their order of implementation. See  Appe ndix  D‐1  Plumbing Fixtures:  (10) W.C., (10)  lavatories, (5)  urinals, (6) showers  Replace urinal valves with  proximity sensing on/off  controls, replace urinals  with ultra‐low flow and  proximity sensing controls;  retrofit toilet valves with  2‐stage valves  See  Appe ndix  D‐2  De‐Stratification  Fans   Install (10) de‐stratification  fans in pool area.  $1,434 $4,800 3.0 3.3 See  Appe ndix  D‐4  Air Scrubbers Eliminate EF‐6 & EF‐7,  replace with 4 air  scrubbers;, use RTU‐7 for  heat only  $3,822 $31,985 1.2 8.3 Retro‐commissioning  HVAC system   $4407 $10,000 4.4 2.3 TOTAL  $26,603 + $375 Maint.  Savings $102,143 2.87 4.1                 ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐  AkWarmCalc Ver  2.2.0.1, Energy Lib 4/6/2012    ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 33 of 57 Appendix C – Equipment Schedules ALL SCHEDULES COMPILED FROM PLANS OR ON‐SITE NAMEPLATE OBSERVATION,  WHERE ACCESSIBLE     e= estimated   COOLING AND HEATING ROOFTOP UNIT SCHEDULE  SYMBOL MFGR/MODEL FAN CFM  MOTOR DATA   HP/VOLTS/PH REMARKS  RTU‐1  Trane YCD049C1HAAA; 4  Ton, 52.2 MBH 1600 .5/208/3e Offices ‐ cooling  120 MBH input, 94 MBH  output, 78% efficient .75/208/3e Offices ‐ heating  RTU‐2A  Trane YCD049C1HAAA; 4  Ton, 52.2 MBH 1600 .5/208/3e Offices ‐ cooling  120 MBH input, 94 MBH  output, 78% efficient .75/208/3e Offices ‐ heating  RTU‐2B  Trane YCD037C1HAAA; 3  Ton, 39.5 MBH 1200 .5/208/3e Exhibit area ‐ cooling  120 MBH input, 94 MBH  output, 78% efficient .5/208/3e Exhibit area ‐ heating  RTU‐3  Trane YCD037C1HAAA; 3  Ton, 39.5 MBH 1200 .5/208/3e Dining ‐ cooling  120 MBH input, 94 MBH  output, 78% efficient .5/208/3e Dining ‐ heating  RTU‐4  Trane YCD075C1HAAA; 6.25  Ton, 78.3 MBH 2500 .75/208/3e Rec room ‐ cooling  205 MBH input, 150 MBH  output, 73% efficient 1/208/3e Rec room ‐ heating  RTU‐5  Trane YCD049C1HAAA; 4  Ton, 52.2 MBH 1600 .5/208/3e First floor ‐ cooling  120 MBH input, 94 MBH  output, 78% efficient .75/208/3e First floor ‐ heating  RTU‐6  Trane YCD037C1HAAA; 3  Ton, 39.5 MBH 1200 .5/208/3e TV room ‐ cooling   120 MBH input, 94 MBH  output, 78% efficient .5/208/3e TV room ‐ heating  RTU‐7  Rupp RXH218‐1000; 1250  MBH input, 1000 MBH out,  80% efficient 11,200 7.5/208/3  Apparatus Bays ‐ interlocked to OH  door opening through EF‐6 and EF‐ 7 ‐ HEATING REPORTED BY ONSITE  PERSONNEL TO BE NON‐ FUNCTIONAL FOR LAST 5‐7 YEARS;  assumed today, to provide only  unheated make up air   AC‐1  Trane TDC036F300A; 3 Ton,  39.5 MBH 1200 .75/208/3E residences ‐ cooling only  AC‐2  Trane TDC036F300A; 3 Ton,  39.5 MBH 1200 .75/208/3E residences ‐ cooling only  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 34 of 57 HRU‐1 Innovent 5000 air to air heat  exchanger installed in 2007  1800 1.5/208/3  Heat recovery fan ‐ supply side ‐  runs continuously  1800 1.0/208/3  Heat recovery fan ‐ exhaust side ‐  runs continuously  DE‐STRATIFICATION FAN SCHEDULE  SYMBOL MOTOR MFGR/MODEL CFM  MOTOR DATA   HP/VOLTS/PH REMARKS  DF‐1 unknown ‐ 60W/115/1  In administration  building  DF‐2 unknown ‐ 60W/115/1  In administration  building  DF‐3 unknown ‐ 60W/115/1  In administration  building  DF‐4  unknown ‐ 60W/115/1  In administration  building  EXHAUST FAN SCHEDULE  SYMBOL MOTOR MFGR/MODEL CFM  MOTOR DATA   HP/VOLTS/PH REMARKS  VF‐1 Greenheck S‐18 2200 .25/120/1  supplies  combustion air  for boilers; on  adjustable wall  thermostat  EF‐1 Cook 90R150L 400 .125/120/1  Office toilet  rooms  EF‐2 Cook 120R10D 720 .125/120/1 Shower room  EF‐3 Cook 100515DL 310 .125/120/1  second floor  toilets  EF‐4 Cook 10R150H 570 .125/120/1 showers  EF‐5 Cook GC‐140 100 70w/120/1 elevator fan  EF‐6 Cook 195W8B 5600 1.5/208/3  Apparatus bay,  interlocked with  OH doors  EF‐7 Cook 210 SQN‐8 5600 1.5/208/3  Apparatus bay,  interlocked with  OH doors  EF‐8 Cook GC140 100 70w/120/1  Communications  room  EF‐9 Fantech DBF 4XL 139 75w/120/1 Dryer booster  KH‐1 Broan 48000 230 300w/120/1  Cabinet hood ‐  kitchen  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 35 of 57 KH‐2A Imperial IS4S1900PS 740 300w/120/1  Island range  hood ‐ kitchen  KH‐2B Imperial IS4S1900PS 740 300w/120/1  Island range  hood ‐ kitchen  PUMP SCHEDULE   SYMBOL MFGR/MODEL GPM  MOTOR DATA   HP/VOLTS/PH REMARKS  CP‐1 Grundfos UPS 40‐240 2F 41 990w/208/3 Fire Station main  heating loop; 1 in  use at a time CP‐1A Grundfos UPS 40‐240 2F 41 990w/208/3  CP‐2 Grundfos UPS 40‐240 2F 22 990w/208/3 Administration  Bldg main  heating loop; 1 in  use at a time CP‐2A Grundfos UPS 40‐240 2F 22 990w/208/3  CP‐3 Grundfos 50‐80 4F 71 640/208/3  on "hand"  radiant heat and  snow melt  CP‐4 Grundfos 32‐160 F 40 430w/208/3  on "hand"; circ  to HWG  CP‐5 Grundfos UPS 40‐160F 26 800w/208/3  Radiant slab  system circ ‐ on  "hand"  CP‐5‐1 Emerson P55 BLZ‐96 21 .5/200/3  supplies HRU‐1,  on "Hand"  (sequence of  operations call  for on when OSA  temp <60F)  CP‐6 Grundfos UPS 15‐42 F 9 85w/115/1  Radiant slab  injection  CP‐7 Grundfos UP 43‐75 F 31 215/115/1  snow melt heat  exchanger hot  side  CP‐8 Grundfos UP 2‐64 F 25 185w/115/1  snow melt  injector  CP‐9 Grundfos UPS 40‐160 34 800w/208/3  snow melt  system pump  CP‐10 Grundfos 15‐42 8 3 85w/115/1 DHW re‐circ  CP‐11 Grundfos UP 43‐75 F 3 215/115/1  anti‐shock  circulator on  boiler  CP‐12 Grundfos UP 43‐75 F 3 215/115/1  anti‐shock  circulator on  boiler  SP‐1 Grundfos SU25 10 .25/115/1 Elevator pit  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 36 of 57 sump pump  SP‐2 Grundfos SU25 10 .25/115/1  Elevator pit  sump pump  BOILER SCHEDULE   SYMBOL MFGR/MODEL CONTROLS  MOTOR DATA   HP/VOLTS/PH REMARKS  B‐1 Burnham V910A 690W/115/1 1/115/1  1528 MBH input,  1329 MBH  output, 87%  efficient, gas  fired (dual fuel  burner) cast iron  sectional  B‐2 Burnham V910A 690W/115/1 1/115/1  1528 MBH input,  1329 MBH  output, 87%  efficient, gas  fired (dual fuel  burner) cast iron  sectional  UNIT HEATER SCHEDULE  SYMBOL MFGR/MODEL CFM  MOTOR DATA   HP/VOLTS/PH REMARKS  UH‐1 Beacon Morris HB‐24; 17,400 MBH 450 9w/115/1  located in  generator room  UH‐2 Beacon Morris H‐72S; 52,000 MBH 1100 .05/115/1  located in hose  tower  CUH‐1 Dunham Bush CUH‐100; 19,900 MBH 175 .035/120/1  South stairwell  Admin bldg  CUH‐2 Dunham Bush CUH‐100; 19,900 MBH 175 .035/120/1  Vestibule Fire  station  CUH‐3 Dunham Bush CUH‐100; 19,900 MBH 175 .035/120/1  Stairwell Fire  station  CUH‐4 Dunham Bush CUH‐100; 19,900 MBH 175 .035/120/1  second floor  vestibule  CUH‐5 Dunham Bush CUH‐100; 19,900 MBH 175 .035/120/1  Second floor  lobby  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 37 of 57 HOT WATER GENERATOR SCHEDULE   SYMBOL MFGR/MODEL GALLONS  NUMBER OF  ELEMENTS ELEMENT SIZE  HWG‐1 Amtrol WHS120ZCDW 119    Indirect water  generator; set at  120F  HWG‐2 Amtrol WHS120ZCDW 119    Indirect water  generator; set at  120F  HWG‐3 Superstor 119    Indirect water  generator; set at  134F  HWG‐4 Amtrol WHS120ZCDW 119    Indirect water  generator; set at  120F  HWH‐1 Bradford White 12 1  1500 watts,  located in Admin  bldg for DHW for  lavatories & sinks HEAT EXCHANGER SCHEDULE  SYMBOL MFGR/MODEL     REMARKS  HX‐1 Flat Plate, Snow Melt  Snow melt, 31 gpm hot side,  24.9 gpm cold side  Tekmar 662  controller  PLUMBING FIXTURES   SYMBOL FIXTURE GPF QUANTITY REMARKS    W.C. 1.6 10  manually  operated    Urinal 1 5  manually  operated    Lavatory         n/a 10   with proximity  sensing valves    Showers 2.6e 6  manually  operated    Clothes washer ‐ commercial   1  Large load  contaminated  clothing, runs 5‐8  loads/day    Stacked clothes washer/dryer   1  runs 8‐10 loads  per day    Residential type electric clothes dryer   1  runs 8‐10 loads  per day  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 38 of 57 EQUIPMENT   SYMBOL FIXTURE QUANTITY  MOTOR DATA   HP/VOLTS/PH REMARKS    Elevator ‐ Fire Station 1 20/408/3 used 3‐4x/day    Elevator ‐ Admin Bldg 1 20/408/3 used 15x/day  PLUG LOAD SUMMARY  SYMBOL FIXTURE QUANTITY  MOTOR DATA   HP/VOLTS/PH REMARKS    Personal printers 1 20/408/3      desk and task lighting 1 20/408/3      chop saw 1 .25/115/1      UPS, Hubs, ethernet switches 1 rack est 1000 w      boot dryers 2 200 w      handheld radio battery charging stations 16 85w      personal coffee machine 1 450w      Epson projectors 2 400w      Wall hand and hair dryers 1 2000w      Extra PC monitors 9 125w      Large Screen TV's 5 450w      Sound system 1 1500w      paper shredders 2 500w      large copy/scan/fax machines 2 1250 w      Truck drop for battery charging 10 20a/115/1  trickle charges  batteries     Treadmills 2 1500w/115/1 used 3‐4 hrs/day    Residential dishwasher 1   run 10x/day    Electric Oven 1   used 2‐3 hrs/day    Gas range 1    2 burners 4‐6  hrs/day    Kitchenaid mixer 1   used 10 min/day    toasters 1   used 1 hr/day    microwaves 2    used 1 hr/day  each    Liftmaster OH door openers 10 .75/208/3      Fan drying hoses 1 .3/115/1  runs  continuously    Hose Lift 2 e.25/115/1  each lift used  2x/day  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 39 of 57 LIGHTING SCHEDULE  FIXTURE  TYPE DESCRIPTION LAMPS MOUNTING  NUMBER WATTS TYPE HEIGHT  Wall pack HPS ‐ Exterior, magnetic ballast 1 150 surface 20'  Wall pack Metal Halide ‐ Exterior, magnetic ballast 1 1000 surface 20'  Recess can HPS recessed fixture 1 70 recess soffit  Recess can HPS recessed fixture 1 100 recess soffit  T8‐3 Florescent, T8 lamps, electronic ballast 3 32 surface ceiling  T8‐2 Florescent, T8 lamps, electronic ballast 2 32 recess ceiling  Recess can CFL, electronic ballast 2 18 recess ceiling  Recess can CFL, electronic ballast 2 26 sconce 7'  Incandescent table lamps 1 60 surface 4'  Pendant Metal Halide ‐ interior, magnetic ballast 1 400 hanging 28'  LARGE MOTOR SCHEDULE  Motor  use &  location  (5 HP or  larger) HP/Volts/Ph   Existing  Efficiency  Premium  Efficiency Estimated  annual  usage  (hrs)  Annual  Savings Burn‐out  payback  (yrs/cost)  Replacement  payback  (yrs/cost)  RTU‐7 7.5/208/3 e82.3% 91.70% 365 $23.47 8.5/$200 38.3/$900  Elevator  1 20/408/3 72%  93.00% 8  insufficient operating hours to justify  replacement with premium efficiency  motors  Elevator  2 20/408/3  e72% 93.00% 32  Efficiency ratings at Full Load, per nameplate  e = estimated because nameplate not accessible or information not on nameplate  Payback figures based on power consumption at 66% of full load     ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 40 of 57 Appendix D Additional, Building-Specific EEM details Appendix D-1: Plumbing fixtures: All urinals should be retrofitted or be replaced with ultra low flow models. The lavatory faucets in this building already have proximity sending on/off valves. Urinals should have proximity sensing on/off controls as well. All toilets in this building are 1.6 gallons per flush with manual valves, they should be retrofitted with dual flush valves (see below). This audit does not include water usage and AkWarm-C does not allow for the modeling of it, but a typical ultra low flow urinal (1 pint to ½ gallon per flush) can save up to 66% of water used, and typically pays back within 3 years, depending on usage. Dual flush toilet valves will typically pay back within 1-3 years, depending on usage. These payback periods are reduced by 66% or more if the fixture or valve is replaced at its EOL rather than while it’s still functioning. For an EOL replacement, the cost used is the incremental difference in cost between an ultra-low-flow fixture and a straight across replacement with the same fixture. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 41 of 57 Appendix D-2: De-Stratification Fans: The apparatus bay (29’ ceilings) in this building makes up approximately 28% of the total square footage and is estimated to consume approximately 20% of the total space heating costs, equal to $7,174 after implementation of all EEM’s. The measured temperature differential between the thermostats and the ceiling was 9.8 F. Per the chart below, anticipated savings by adding de-stratification fans should be 20%. This results in an annual savings of $1,434 after implementation of all EEM’s. Estimated cost to install a de-strat fan over the pool is $1200 each; assuming 4 fans are appropriate (number, location and size of fans must be determined by an engineer or fan vendor), total costs are $4,800 and payback is 3.3 years. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 42 of 57 Appendix D-3: EEM’S considered but not recommended Variable frequency drives (VFD): Motors considered for VFD’s included the (2) 20 HP elevator motors, the 7.5 HP in RTU-7, the 4 main glycol circulation pumps for the Fire Station and Administration building and the snow melt circ pump. The elevator and RTU-7 motors have insufficient operating hours and the circ pumps have a 10 year payback. Additionally, RTU-7 is used for make-up air and the elevator motors power hydraulics intermittently so variable speed is not required. Motor replacements with premium efficiency versions: insufficient operating hours on the 3 large motors (RTU-7 and two elevator hydraulic motors) to justify replacement with premium efficiency, now and at EOL. Appendix D-4: Replace Exhaust Fans with Air Scrubbers in apparatus bay When a truck breaks the optical beam (entering or exiting) at any OH door, exhaust fans EF-6 and EF-7 turn on for approximately 7 minutes. This exhausts 11,200 CFM of conditioned air. RTU-7 is interconnected to provide make up air at 11,200 CFM. It is estimated that a unique entry or exit (there is no difference in operation if more than 1 vehicle enters or exits after the beam has been broken) occurs an average of 12 times per day, so the air handlers are running for 1.4 hours per day, 365 days/year. It should be noted that a 7 minute exhaust cycle only results in 31% of an air change in the apparatus bay; this does not seem adequate, but for without knowing the concentration of carbon monoxide, it is assumed for calculation purposes that this is sufficient. This should be verified. (4) AirHawk 3000XL air scrubbers (see Appendix E) will process 12,000 CFM of inside air. See table 4 below for a comparison of the annual costs of operating the current system and the system recommended by this EEM. Table 4 ANNUAL OPERATING COSTS     Existing System with  EF‐6, EF‐7 and RTU‐7  Proposed EEM using  4 air scrubbers  Electric (fan motors) costs  $                480    $                183   Cost of NG for sensible  portion of load to heat OSA  $             1,262    $                     ‐   Cost of NG for latent portion  of load to heat OSA  $             2,263    $                     ‐   TOTALS  $             4,005   $                183   ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 43 of 57 It is recommended to disable or remove EF-6 and EF-7, and modify the controls on RTU-7 (which is recommended to be repaired, as on-site personnel stated that the heating portion of this unit is non-functional) to be controlled by a local thermostat in the apparatus bay, and to only provide heat as needed, not make up air. The estimated cost to install (4) air scrubbers, similar to those used in Fire Stations 11 and 12, is $31,985 (see quote in Appendix E). The estimated annual savings is $3822, and the payback is 8.3 years. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 44 of 57 Appendix E – Specifications supporting EEM’s Lighting Controls Occupancy sensors sense the presence of occupants, turn the lights on at a pre- determined level, and then turn the lights off after a programmed time period of no occupancy. Line of sight, motion sensing occupancy sensors can be installed in existing duplex switch boxes, as well as on ceilings. Dual technology sensors are typically ceiling mounted in rooms, lavatories, corridors, vehicle bays and storage areas where obstacles may interfere with line-of-sight sensors. The second technology in these sensors activates lighting based on sound or changes in position, and work even when a person is fully obscured by an obstacle. Zoned occupancy controls are typically recommended for long corridors, large vehicle bays and large storage areas with multiple switches and lighting zones. Zoned controls are designed to activate and de-activate lighting by zone, by row, or even by fixture, based on the location of the occupant. Occupancy sensors can reduce power consumption by 25-60%. Paybacks on occupancy sensors range from 1 to 5 years, depending on the light fixture consumption and occupancy of the room. Lighting Management Systems (LMS) today have the capability to manage lighting based on a wide variety of parameters including building usage, daylight conditions and occupancy. They are retro-fittable, and can be stand alone or integrated into a building’s HVAC, alarm or other control systems. Additionally, they can be easily re- configured as a building’s usage or occupancy pattern changes. Sample LMS systems and a sample high bay occupancy sensor (which could be used for zone lighting control) follow. ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 45 of 57 Appendix E – Lighting Controls ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 46 of 57 ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 47 of 57 Appendix E - Occupancy Sensing Thermostat ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 48 of 57 Appendix E – Headbolt Heater controls ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 49 of 57 Appendix E – Air Scrubber Quote ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 50 of 57 Appendix F – Benchmark Data $0 $2,000 $4,000 $6,000 $8,000 $10,000 $12,000 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 Jan‐09Mar‐09May‐09Jul‐09Sep‐09Nov‐09Jan‐10Mar‐10May‐10Jul‐10Sep‐10Nov‐10Natural Gas Cost ($)Natural Gas Consumption (Therms)Date (Mon ‐Yr) Building Name‐Natural Gas Consumption (Therms) vs. Natural Gas Cost ($) Natural Gas Consumption (Therms) Natural Gas Cost ($) $0 $500 $1,000 $1,500 $2,000 $2,500 $3,000 $3,500 $4,000 $4,500 0 5000 10000 15000 20000 25000 30000 35000 40000 Jan‐09Mar‐09May‐09Jul‐09Sep‐09Nov‐09Jan‐10Mar‐10May‐10Jul‐10Sep‐10Nov‐10Electric Cost ($)Electric Consumption (kWh)Date (Mon ‐Yr) Building Name‐Electric Consumption (kWh) vs. Electric Cost ($) Electric Consumption (kWh) Electric Cost ($) ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 51 of 57 REAL Preliminary Benchmark Data Form  PART I – FACILITY INFORMATION  Facility Owner Facility Owned By Date (mm/dd/yyyy)  MOA Municipal  Government/Subdivision  04/06/12 Building Name/ Identifier Building Usage Building Square Footage  Fire Station #1 & Admin (2 buildings,  combined sq ft)    29,891 Building Type Community Population Year Built   261,000 2000 Facility Address Facility City Facility Zip  100 & 122 E 4th Ave Anchorage 99517  Contact Person  First Name Last Name Middle Name Email Phone               Mailing Address City State Zip           Primary Operating  Hours  Monday‐ Friday  Saturday Sunday Holidays                   Average # of  Occupants During  Operating Hours                 Renovations    Date (mm/dd/yyyy) Details PART II – ENERGY SOURCES    1. Please check every energy source you use in the table below.  If known, please enter the base rate you pay for  the energy source.  2. Provide utilities bills for the most recent two‐year period for each energy source you use.       ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 52 of 57  Heating Oil  Electricity  Natural Gas  Propane Wood  Coal   $ /gallon  $ / kWh  $ / CCF $ / gal $ / cord  $ / ton           Other energy  sources? Describe         NOTES TO AUDITOR:             These are (2) separate bldgs, with (2) NG meters, but site inspection revealed only 1 elec meter, so bldgs are  combined in this benchmark, as are NG usage data.  Fire Station #1 & Admin (2 buildings, combined sq ft) Buiding Size Input (sf) = 29,891 2009 Natural Gas Consumption (Therms) 60,500.00 2009 Natural Gas Cost ($) 61,785 2009 Electric Consumption (kWh) 347,880 2009 Electric Cost ($) 33,916 2009 Oil Consumption (Therms) 0.00 2009 Oil Cost ($) 0 2009 Propane Consumption (Therms) 0.00 2009 Propane Cost ($) 0.00 2009 Coal Consumption (Therms) 0.00 2009 Coal Cost ($) 0.00 2009 Wood Consumption (Therms) 0.00 2009 Wood Cost ($) 0.00 2009 Thermal Consumption (Therms) 0.00 ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 53 of 57 2009 Thermal Cost ($) 0.00 2009 Total Energy Use (kBtu) 7,237,314 2009 Total Energy Cost ($) 95,701 Annual Energy Use Intensity (EUI) 2009 Natural Gas (kBtu/sf) 202.4 2009 Electricity (kBtu/sf) 39.7 2009 Oil (kBtu/sf) 0.0 2009 Propane (kBtu/sf) 0.0 2009 Coal (kBtu/sf) 0.0 2009 Wood (kBtu/sf) 0.0 2009 Thermal (kBtu/sf) 0.0 2009 Energy Utilization Index (kBtu/sf) 242.1 Annual Energy Cost Index (ECI) 2009 Natural Gas Cost Index ($/sf) 2.07 2009 Electric Cost Index ($/sf) 1.13 2009 Oil Cost Index ($/sf) 0.00 2009 Propane Cost Index ($/sf) 0.00 2009 Coal Cost Index ($/sf) 0.00 2009 Wood Cost Index ($/sf) 0.00 2009 Thermal Cost Index ($/sf) 0.00 2009 Energy Cost Index ($/sf) 3.20 2010 Natural Gas Consumption (Therms) 49,121.00 2010 Natural Gas Cost ($) 40,343 2010 Electric Consumption (kWh) 380,880 2010 Electric Cost ($) 39,806 2010 Oil Consumption (Therms) 0.00 2010 Oil Cost ($) 0 2010 Propane Consumption (Therms) 0.00 ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 54 of 57 2010 Propane Cost ($) 0 2010 Coal Consumption (Therms) 0.00 2010 Coal Cost ($) 0 2010 Wood Consumption (Therms) 0.00 2010 Wood Cost ($) 0 2010 Thermal Consumption (Therms) 0.00 2010 Thermal Cost ($) 0 2010 Total Energy Use (kBtu) 6,212,043 2010 Total Energy Cost ($) 80,149 Annual Energy Use Intensity (EUI) 2010 Natural Gas (kBtu/sf) 164.3 2010 Electricity (kBtu/sf) 43.5 2010 Oil (kBtu/sf) 0.0 2010 Propane (kBtu/sf) 0.0 2010 Coal (kBtu/sf) 0.0 2010 Wood (kBtu/sf) 0.0 2010 Thermal (kBtu/sf) 0.0 2010 Energy Utilization Index (kBtu/sf) 207.8 Annual Energy Cost Index (ECI) 2010 Natural Gas Cost Index ($/sf) 1.35 2010 Electric Cost Index ($/sf) 1.33 2010 Oil Cost Index ($/sf) 0.00 2010 Propane Cost Index ($/sf) 0.00 2010 Coal Cost Index ($/sf) 0.00 2010 Wood Cost Index ($/sf) 0.00 2010 Thermal Cost Index ($/sf) 0.00 20010 Energy Cost Index ($/sf) 2.68 Note: ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 55 of 57 1 kWh = 3,413 Btu's 1 Therm = 100,000 Btu's 1 CF ≈ 1,000 Btu's Natural Gas consumption Btus/CCF =100,000 Month Billing Days Consumption (CCF)  Consumption  (Therms)  Demand  Use  Natural  Gas Cost  ($)  Unit Cost  ($/Therm)  Demand  Cost ($)  Jan‐09 31 9343 9343    $9,528  $1.02    Feb‐09 32 7016 7016 $7,130  $1.02  Mar‐09 27 6458 6458 $6,567  $1.02  Apr‐09 31 7187 7187 $7,294  $1.01  May‐09 29 5209 5209 $5,305  $1.02  Jun‐09 33 2888 2888 $2,971  $1.03  Jul‐09 30 2521 2521 $2,606  $1.03  Aug‐09 32 2558 2558 $2,642  $1.03  Sep‐09 31 2730 2730 $2,815  $1.03  Oct‐09 31 4245 4245 $4,366  $1.03  Nov‐09 28 4477 4477 $4,579  $1.02  Dec‐09 29 5868 5868 $5,982  $1.02               Jan‐10 34 7395 7395 $6,215  $0.84  Feb‐10 30 7542 7542 $6,334  $0.84  Mar‐10 28 5748 5748 $4,844  $0.84  Apr‐10 33 6398 6398 $5,435  $0.85  May‐10 28 3429 3429 $2,949  $0.86  Jun‐10 29 1335 1335 $1,198  $0.90  Jul‐10 31 1366 1366 $1,223  $0.90  Aug‐10 32 1514 1514 $1,336  $0.88  Sep‐10 30 1410 1410 $1,253  $0.89  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 56 of 57 Oct‐10 32 2445 2445 $2,082  $0.85  Nov‐10 28 4141 4141 $2,227  $0.54  Dec‐10 34 6398 6398 $5,247  $0.82  Jan ‐ 09 to Dec ‐ 09 total: 60,500 60,500   $61,785    $0   Jan ‐ 10 to Dec ‐ 10 total: 49,121 49,121   $40,343    $0   Jan ‐ 09 to Dec ‐ 09 avg: $1.02  Jan ‐ 10 to Dec ‐ 10 avg: $0.83  Electricity Consumption Btus/kWh = 3,413 Month  Billing  Days  Consumption  (kWh)  Consumption  (Therms)  Demand  Use  Total  Electric  Cost ($)  Unit Cost  ($/kWh)  Demand  Cost ($)  Jan‐09 32 35040 1195.9152   $2,862 $0.08 $810.80  Feb‐09 28 25320 864.1716   $2,186 $0.09 $693.90  Mar‐09 30 27240 929.7012   $2,731 $0.10 $713.20  Apr‐09 32 29400 1003.422   $2,877 $0.10 $701.30  May‐09 29 24240 827.3112   $2,480 $0.10 $618.50  Jun‐09 30 28320 966.5616   $2,890 $0.10 $735.50  Jul‐09 33 34920 1191.8196   $3,473 $0.10 $825.60  Aug‐09 29 28440 970.6572   $2,913 $0.10 $750.20  Sep‐09 30 28440 970.6572   $2,894 $0.10 $716.10  Oct‐09 32 30720 1048.4736   $3,148 $0.10 $798.90  Nov‐09 28 26640 909.2232   $2,761 $0.10 $719.10  Dec‐09 30 29160 995.2308   $2,701 $0.09 $702.50                   Jan‐10 33 35760 1220.4888   $3,198 $0.09 $759.30  Feb‐10 29 29400 1003.422   $2,724 $0.09 $709.60  Mar‐10 30 28800 982.944   $3,154 $0.11 $651.30  Apr‐10 31 30000 1023.9   $3,261 $0.11 $655.50  May‐10 30 29280 999.3264   $3,460 $0.12 $847.80  Jun‐10 29 27840 950.1792   $2,958 $0.11 $785.70  ENERGY AUDITS OF ALASKA FIRE STATION #1 & ADMINSTRATION BUILDING May 2, 2012 Page 57 of 57 Jul‐10 33 35520 1212.2976   $3,610 $0.10 $853.80  Aug‐10 28 29640 1011.6132   $3,152 $0.11 $841.90  Sep‐10 30 30480 1040.2824   $3,245 $0.11 $790.10  Oct‐10 33 34920 1191.8196   $3,610 $0.10 $806.40  Nov‐10 29 32280 1101.7164   $3,389 $0.10 $793.10  Dec‐10 33 36960 1261.4448   $4,045 $0.11 $792.05  Jan ‐ 09 to Dec ‐ 09 total: 347880 11873.1444   $33,916   $8,786  Jan ‐ 10 to Dec ‐ 10 total: 380880 12999.4344   $39,806   $9,287  Jan ‐ 09 to Dec ‐ 09 avg: $0.10  Jan ‐ 10 to Dec ‐ 10 avg: $0.10