Loading...
HomeMy WebLinkAboutCIRI-SXQ-CAEC Soldotna Police 2012-EEENERGY AUDIT REPORT      Soldotna Police Station  44510 Sterling Hwy  Soldotna, AK 99669    CAEC Project No.  CIRI‐SXQ‐CAEC‐08  May 2012    SUBMITTED BY: PRIMARY CONTACT:                                        22010 SE 51st Street 32266 Lakefront Drive  Issaquah, WA 98029 Soldotna, Alaska  99669  Phone (425)281‐4706 Fax (425)507‐4350     Phone (907) 260‐5311 Fax (907) 260‐5312  Email: andrew.waymire@siemens.com Email:  akengineer@starband.net     CONTACT: Andrew Waymire, C.E.M. CONTACT:  Jerry P. Herring, P.E., C.E.A.    REPORT DISCLAIMER    Privacy  The information contained within this report, including any attachment(s), was produced under contract to Alaska Housing Finance Corporation (AHFC). IGAs are the property of the State of Alaska, and may be incorporated into AkWarm-C, the Alaska Retrofit Information System (ARIS), or other state and/or public information systems. AkWarm-C is a building energy modeling software developed under contract by AHFC. This material is based upon work supported by the Department of Energy under Award Number DE- EE0000095. This report was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.   Limitations of Study  This energy audit is intended to identify and recommend potential areas of energy savings, estimate the value of the savings, and provide an opinion of the costs to implement the recommendations. This audit meets the criteria of a Level 2 Investment Grade Audit (IGA) per the American Society of Heating, Refrigeration, Air-conditioning Engineers (ASHRAE) and the Association of Energy Engineers (AEE), and is valid for one year. The life of the IGA may be extended on a case-by-case basis, at the discretion of AHFC. In preparing this report, the preparers acted with the standard of care prevalent in this region for this type of work. All results are dependent on the quality of input data provided. Not all data could be verified and no destructive testing or investigations were undertaken. Some data may have been incomplete. This report is not intended to be a final design document. Any modifications or changes made to a building to realize the savings must be designed and implemented by licensed, experienced professionals in their fields. Lighting upgrades should undergo a thorough lighting analysis to assure that the upgrades will comply with State of Alaska Statutes as well as Illuminating Engineering Society (IES) recommendations. All liabilities for upgrades, including but not limited to safety, design, and performance are incumbent upon the professional(s) who prepare the design. Siemens Industry, Inc (SII) and Central Alaska Engineering Company (CAEC) bear no responsibility for work performed as a result of this report. Financial ratios may vary from those forecasted due to the uncertainty of the final installed design, configuration, equipment selected, installation costs, related additional work, or the operating schedules and maintenance provided by the owner. Furthermore, many ECMs are interactive, so implementation of one ECM may impact the performance of another ECM. SII and CAEC accept no liability for financial loss due to ECMs that fail to meet the forecasted financial ratios. The economic analyses for the ECMs relating to lighting improvements are based solely on energy savings. Additional benefits may be realized in reduced maintenance cost, deferred maintenance, and improved lighting quality. The new generation lighting systems have significantly longer life leading to long term labor savings, especially in high areas like Gyms and exterior parking lots. Lighting upgrades displace re-lamping costs for any fixtures whose lamps would otherwise be nearing the end of their lifecycle. This reduces maintenance costs for 3-10 years after the upgrade. An overall improvement in lighting quality, quantified by numerous studies, improves the performance of students and workers in the built environment. New lighting systems can be designed to address all of the above benefits.           Table of Contents    REPORT DISCLAIMER.....................................................................................................................................2 1. EXECUTIVE SUMMARY..............................................................................................................................5 2. AUDIT AND ANALYSIS BACKGROUND.......................................................................................................7 3. Soldotna Police Station...........................................................................................................................10 4. ENERGY COST SAVING MEASURES..........................................................................................................19 Appendix A – Major Equipment Inventory ............................................................................................22 Appendix B – Partial Lighting Inventory ................................................................................................23 Appendix C – IR Photos / Heat Loss Signature ..................................................................................24 Appendix D – REAL Utility Data.............................................................................................................25   Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 5 of 30  1. EXECUTIVE SUMMARY  This report was prepared for the City of Soldotna using ARRA funds as part of a contract for:         City of Soldotna  Alaska Housing Finance Corporation  Contact: Kyle Kornelis Contact: Rebekah Luhrs  177 North Birch P.O. Box 10120  Soldotna, Alaska  99669 Anchorage, Alaska 99510  Phone (907) 262‐9107 Phone (907)330‐8141  Email:  kkornelis@ci.soldotna.ak.us Email: rluhrs@ahfc.us    The scope of the audit focused on Soldotna Police Station. The scope of this report is a  comprehensive energy study, which included an analysis of building shell, interior and exterior  lighting systems, HVAC systems, and plug loads.    Based on electricity and fuel oil prices in effect at the time of the audit, the annual predicted  energy costs for the buildings analyzed are as follows:     $17,258 for Electricity   $3,652 for Natural Gas    The total energy costs are $20,910 per year.    Table 1.1 below summarizes the energy efficiency measures analyzed for the Soldotna Police  Station.  Listed are the estimates of the annual savings, installed costs, and two different  financial measures of investment return. With all of these energy efficiency measures in place,  the annual utility cost can be reduced by $1,344 per year.        Table 1.1  PRIORITY LIST – ENERGY EFFICIENCY MEASURES Rank Feature Improvement Description Annual Energy Savings Installed Cost Savings to Investment Ratio, SIR1 Simple Payback (Years)2 1 Lighting Replace with 5 200 W INDUCTION LAMPS $1,340 $5,000 1.71 3.7 TOTAL, cost-effective measures $1,340 $5,000 1.71 3.7 The following measures were not found to be cost-effective: 2 Lighting Replace with 13 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic $4 $1,625 0.02 369.1 TOTAL, all measures $1,344 $6,625 1.30 4.9       Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 6 of 30  Table Notes:  1 Savings to Investment Ratio (SIR) is a life‐cycle cost measure calculated by dividing the total  savings over the life of a project (expressed in today’s dollars) by its investment costs.  The SIR is  an indication of the profitability of a measure; the higher the SIR, the more profitable the  project.  An SIR greater than 1.0 indicates a cost‐effective project (i.e. more savings than cost).   Remember that this profitability is based on the position of that Energy Efficiency Measure  (EEM) in the overall list and assumes that the measures above it are implemented first.    2 Simple Payback (SP) is a measure of the length of time required for the savings from an EEM to  payback the investment cost, not counting interest on the investment and any future changes in  energy prices.  It is calculated by dividing the investment cost by the expected first‐year savings  of the EEM.    With all of these energy efficiency measures in place, the annual utility cost can be reduced by  $1,344 per year, or 6.4% of the buildings’ total energy costs. These measures are estimated to  cost $6,625, for an overall simple payback period of 4.9 years.  If only the cost‐effective  measures are implemented, the annual utility cost can be reduced by $1,340 per year, or 6.4%  of the buildings’ total energy costs. These measures are estimated to cost $5,000, for an overall  simple payback period of 3.7 years.    Table 1.2 below is a breakdown of the annual energy cost across various energy end use types,  such as Space Heating and Water Heating.  The first row in the table shows the breakdown for  the building as it is now.  The second row shows the expected breakdown of energy cost for the  building assuming all of the retrofits in this report are implemented.  Finally, the last row shows  the annual energy savings that will be achieved from the retrofits.      Table 1.2  Annual Energy Cost Estimate  Description Space  Heating  Space  Cooling  Water  Heating Lighting Refrigera tion  Other  Electrical Cooking Clothes  Drying  Ventilatio n Fans  Service  Fees Total Cost  Existing  Building  $10,86 8  $0 $558 $7,987 $0 $1,046 $0 $0 $0 $451 $20,910  With All  Proposed  Retrofits  $10,86 9  $0 $558 $6,642 $0 $1,046 $0 $0 $0 $451 $19,566  SAVINGS ‐$1 $0 $0 $1,345 $0 $0 $0 $0 $0 $0 $1,344  Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 7 of 30    2. AUDIT  AND ANALYSIS BACKGROUND  2.1 Program Description  This audit included services to identify, develop, and evaluate energy efficiency measures at the  Soldotna Police Station. The scope of this project included evaluating building shell, lighting and  other electrical systems, and HVAC equipment, motors and pumps.  Measures were analyzed  based on life‐cycle‐cost techniques, which include the initial cost of the equipment, life of the  equipment, annual energy cost, annual maintenance cost, and a discount rate of 3.0%/year in  excess of general inflation.     2.2 Audit Description   Preliminary audit information was gathered in preparation for the site survey including actual  utility bills. The site survey provides critical information in deciphering where energy is used  and what opportunities exist within a building. The entire site was surveyed to inventory the  following to gain an understanding of how each building operates:    • Building envelope (roof, windows, etc.)  • Heating, ventilation, and air conditioning equipment (HVAC)  • Lighting systems and controls  • Building‐specific equipment  • Water  consumption, treatment (optional) & disposal    The building site visit was performed to survey all major building components and systems. The  site visit included detailed inspection of energy consuming components. Summary of building  occupancy schedules, operating and maintenance practices, and energy management programs  provided by the building manager were collected along with the system and components to  determine a more accurate impact on energy consumption.    Details collected from Soldotna Police Station enable a model of the building’s energy usage to  be developed, highlighting the building’s total energy consumption, energy consumption by  specific building component, and equivalent energy cost. The analysis involves distinguishing  the different fuels used on site, and analyzing their consumption in different activity areas of  the building.     Soldotna Police Station is classified as being made up of the following activity areas:   1) Police Station:  11,040 square feet  In addition, the methodology involves taking into account a wide range of factors specific to the  building. These factors are used in the construction of the model of energy used.  The factors  include:  • Occupancy hours  • Local climate conditions  • Prices paid for energy  Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 8 of 30  2.3. Method of Analysis  Data collected was processed using AkWarm© Energy Use Software to estimate energy savings  for each of the proposed energy efficiency measures (EEMs). The recommendations focus on  the building envelope; HVAC; lighting, plug load, and other electrical improvements; and motor  and pump systems that will reduce annual energy consumption.     EEMs are evaluated based on building use and processes, local climate conditions, building  construction type, function, operational schedule, existing conditions, and foreseen future  plans. Energy savings are calculated based on industry standard methods and engineering  estimations.     Our analysis provides a number of tools for assessing the cost effectiveness of various  improvement options.  These tools utilize Life‐Cycle Costing, which is defined in this context as  a method of cost analysis that estimates the total cost of a project over the period of time that  includes both the construction cost and ongoing maintenance and operating costs.    Savings to Investment Ratio (SIR) = Savings divided by Investment    Savings includes the total discounted dollar savings considered over the life of the  improvement.  When these savings are added up, changes in future fuel prices as projected by  the Department of Energy are included.  Future savings are discounted to the present to  account for the time‐value of money (i.e. money’s ability to earn interest over time).  The  Investment in the SIR calculation includes the labor and materials required to install the  measure.  An SIR value of at least 1.0 indicates that the project is cost‐effective—total savings  exceed the investment costs.     Simple payback is a cost analysis method whereby the investment cost of a project is divided  by the first year’s savings of the project to give the number of years required to recover the  cost of the investment. This may be compared to the expected time before replacement of the  system or component will be required. For example, if a boiler costs $12,000 and results in a  savings of $1,000 in the first year, the payback time is 12 years.  If the boiler has an expected  life to replacement of 10 years, it would not be financially viable to make the investment since  the payback period of 12 years is greater than the project life.     The Simple Payback calculation does not consider likely increases in future annual savings due  to energy price increases.  As an offsetting simplification, simple payback does not consider the  need to earn interest on the investment (i.e. it does not consider the time‐value of money).   Because of these simplifications, the SIR figure is considered to be a better financial investment  indicator than the Simple Payback measure.    Measures are implemented in order of cost‐effectiveness.  The program first calculates  individual SIRs, and ranks all measures by SIR, higher SIRs at the top of the list.  An individual  measure must have an individual SIR>=1 to make the cut.  Next the building is modified and re‐ simulated with the highest ranked measure included.  Now all remaining measures are re‐ evaluated and ranked, and the next most cost‐effective measure is implemented.  AkWarm  goes through this iterative process until all appropriate measures have been evaluated and  installed.     Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 9 of 30  It is important to note that the savings for each recommendation is calculated based on  implementing the most cost effective measure first, and then cycling through the list to find the  next most cost effective measure. Implementation of more than one EEM often affects the  savings of other EEMs. The savings may in some cases be relatively higher if an individual EEM is  implemented in lieu of multiple recommended EEMs. For example implementing a reduced  operating schedule for inefficient lighting will result in relatively high savings. Implementing a  reduced operating schedule for newly installed efficient lighting will result in lower relative  savings, because the efficient lighting system uses less energy during each hour of operation. If  multiple EEM’s are recommended to be implemented, AkWarm calculates the combined  savings appropriately.    Cost savings are calculated based on estimated initial costs for each measure. Installation costs  include labor and equipment to estimate the full up‐front investment required to implement a  change. Costs are derived from Means Cost Data, industry publications, and local contractors  and equipment suppliers.     2.4 Limitations of Study  All results are dependent on the quality of input data provided, and can only act as an  approximation.  In some instances, several methods may achieve the identified savings. This  report is not intended as a final design document. The design professional or other persons  following the recommendations shall accept responsibility and liability for the results.       Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 10 of 30  3. Soldotna Police  Station       (Photo from Google Maps)  3.1. Building Description    The 11,040 square foot Soldotna Police Station was constructed in 1994, with a normal  occupancy of 5‐15 people.  The number of hours of operation for this building average  18  hours per day. The building is of modern construction with heavily insulated walls, roof and  thermal windows.    Description of Building Shell    The exterior walls are constructed of a combination of 8” CMU and stucco covered plywood  sheathing. Exterior surfaces are backed by heavily insulated interior walls generally constructed  of 2”x6” framing and R19 fiber glass insulation. CMU sections include 4” of rigid insulation. All  interior walls are covered with 5/8” GWB (dry wall).     The roof of the building is constructed a built up assembly consisting of 2” rigid insulation, 3”  Rm.  Board, EPDM, 3”EPS, vapor barrier and plywood sheathing. Concrete pavers provide a  walking path around the perimeter. The estimated roof assembly insulating value is  approximately R30.    The floor/foundation of the building is constructed of an insulated concrete slab on grade with  2” rigid insulation. Radiant hot water piping is embedded within the slab.     Typical windows throughout the building are constructed of ¾” insulated glass units with  thermal broken aluminum frames. The insulating value is estimated at R2.2.      Entry doors are store front thermal insulated glass with insulated aluminum frames.  The main  entry includes an enclosed vestibule. The rear of the facility includes 6 insulated overhead  doors. There are 5 hollow metal man doors.    Description of Heating and Cooling Plants  Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 11 of 30    The Heating Plants used in the building are:    Boilers 1‐5   Nameplate Information: Weil‐McLain  GV‐6 Condensing  Quantity 5  MBH INOUT: 175/153   Fuel Type: Natural Gas   Input Rating: 875 BTU/hr   Steady State Efficiency: 87.4  %   Idle Loss: 1.5  %   Heat Distribution Type: Water   Boiler Operation: All Year      Space Heating and Cooling Distribution Systems  Hot water from the boilers noted above is circulated to a hot water coil in AHU‐1, assorted  terminal equipment and an in floor radiant heating system.      The radiant system carries the majority of the building heating load.  The system consists of 10  zones each of which includes a dedicated circulating pump and thermostatic mixing valve. The  room thermostat cycles the zone pump. The zone mixing valve has a manual setting capability.  Water temperature is constant and was noted to be 165’f when the outside air temperature  was approximately 50’f during and the facility was overheating. Zones were manually set from  140’f‐165’f.     Domestic Hot Water System  Domestic water is created by the main heating boilers via a heat exchanger located in the  domestic water tank. A dedicated fractional horsepower circulating pump moves water from  the primary heating loop into the domestic water heat exchanger.     Description of Building Ventilation System  The existing building ventilation system consists of a single air handling unit located in the  mechanical room.  This is a constant volume unit that serves all interior office spaces. The unit  consists of a supply fan, mixing box, heating coil and return fan. Cooling is provided by a one  pass cooling coil fed by municipal water. The unit is controlled by an older DDC system.  Outside  air was noted to be set at approximately 20%‐25%.    Fan motor starter was noted to be of two speed configuration but the control circuit was  limited to high speed operation.    Manual exhaust fans serve a variety of areas including the lab, storage and garage.    Lighting  The majority of the lighting is provided by 4’ ‐ T8 high efficiency florescent fixtures. The  perimeter fixtures are 4’‐T12 standard efficiency fixtures that provide an energy savings retrofit  opportunity.    Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 12 of 30  Plug Loads  There are limited plug loads consisting of approximately 20 computers, many of which were  off  during inspection.    Major Equipment  The equipment list, available in Appendix A, is composed of major energy consuming  equipment which through energy conservation measures could yield substantial energy savings.  The list shows the major equipment in the building and pertinent information utilized in energy  savings calculations.    Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 13 of 30  3.2 Predicted Energy Use  3.2.1 Energy Usage / Tariffs    The electric usage profile charts (below) represents the predicted electrical usage for the  building.  If actual electricity usage records were available, the model used to predict usage was  calibrated to approximately match actual usage. The electric utility measures consumption in  kilowatt‐hours (kWh) and maximum demand in kilowatts (kW). One kWh usage is equivalent to  1,000 watts running for one hour. One KW of electric demand is equivalent to 1,000 watts  running at a particular moment. The basic usage charges are shown as generation service and  delivery charges along with several non‐utility generation charges.     The natural gas usage profile shows the predicted natural gas energy usage for the building. If  actual gas usage records were available, the model used to predict usage was calibrated to  approximately match actual usage.  Natural gas is sold to the customer in units of 100 cubic feet  (CCF), which contains approximately 100,000 BTUs of energy.     The propane usage profile shows the propane usage for the building.  Propane is sold by the  gallon or by the pound, and its energy value is approximately 91,800 BTUs per gallon.    The fuel oil usage profile shows the fuel oil usage for the building.  Fuel oil consumption is  measured in gallons.  One gallon of #1 Fuel Oil provides approximately 132,000 BTUs of energy.    The following is a list of the utility companies providing energy to the building and the class of  service provided:     Electricity:  Homer Electric Assn (Homer) ‐ Commercial ‐ Sm     Natural Gas:  Enstar Natural Gas‐ Residential    The average cost for each type of fuel used in this building is shown below in Table 3.1.  This  figure includes all surcharges, subsidies, and utility customer charges:    Table 3.1 – Average Energy Cost Description Average Energy Cost Electricity $ 0.1387/kWh  Natural Gas $ 0.72/ccf    3.2.1.1 Total Energy Use and Cost Breakdown  At current rates, City of Soldotna pays approximately $20,745 annually for electricity and other  fuel costs for the Soldotna Police Station.     Figure 3.1 below reflects the estimated distribution of costs across the primary end uses of  energy based on the AkWarm© computer simulation.   Comparing the “Retrofit” bar in the  figure to the “Existing” bar shows the potential savings from implementing all of the energy  efficiency measures shown in this report.    Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 14 of 30  Figure 3.1  Annual Energy Costs by End Use        Figure 3.2 below shows how the annual energy cost of the building splits between the different fuels  used by the building.  The “Existing” bar shows the breakdown for the building as it is now; the  “Retrofit” bar shows the predicted costs if all of the energy efficiency measures in this report are  implemented.    Figure 3.2  Annual Energy Costs by Fuel Type        Figure 3.3 below addresses only Space Heating costs.  The figure shows how each heat loss component  contributes to those costs; for example, the figure shows how much annual space heating cost is caused  by the heat loss through the Walls/Doors.  For each component, the space heating cost for the Existing  building is shown (blue bar) and the space heating cost assuming all retrofits are implemented (yellow  bar) are shown.    Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 15 of 30  Figure 3.3  Annual Space Heating Cost by Component    $0 $2,000 $4,000 $6,000 Floor Wall/Door Window Ceiling Air Existing Retrofit Annual Space Heating Cost by Component       The tables below show AkWarm’s estimate of the monthly fuel use for each of the fuels used in the  building.  For each fuel, the fuel use is broken down across the energy end uses.  Note, in the tables  below “DHW” refers to Domestic Hot Water heating.       Electrical Consumption (kWh)   Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec  Lighting 4972 4531 4972 4812 4972 4812 4972 4972 4812 4972 4812 4972  Other_Electrical 651 593 651 630 651 630 651 651 630 651 630 651  Ventilation_Fans 0 0 0 0 0 0 0 0 0 0 0 0  DHW 56 51 56 54 56 54 56 56 54 56 54 56  Space_Heating 4885 4452 4885 4728 4885 4728 4885 4885 4728 4885 4728 4885  Space_Cooling 0 0 0 0 0 0 0 0 0 0 0 0    Natural Gas Consumption (ccf)   Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec  DHW 58 53 58 56 58 56 58 58 56 58 56 58  Space_Heating 635 512 493 357 272 173 130 141 217 369 477 623          Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 16 of 30  3.2.2  Energy Use Index (EUI)    Energy Use Index (EUI) is a measure of a building’s annual energy utilization per square foot of  building. This calculation is completed by converting all utility usage consumed by a building for  one year, to British Thermal Units (Btu) or kBtu, and dividing this number by the building square  footage. EUI is a good measure of a building’s energy use and is utilized regularly for  comparison of energy performance for similar building types. The Oak Ridge National  Laboratory (ORNL) Buildings Technology Center under a contract with the U.S. Department of  Energy maintains a Benchmarking Building Energy Performance Program. The ORNL website  determines how a building’s energy use compares with similar facilities throughout the U.S. and  in a specific region or state.    Source use differs from site usage when comparing a building’s energy consumption with the  national average. Site energy use is the energy consumed by the building at the building site  only. Source energy use includes the site energy use as well as all of the losses to create and  distribute the energy to the building. Source energy represents the total amount of raw fuel  that is required to operate the building. It incorporates all transmission, delivery, and  production losses, which allows for a complete assessment of energy efficiency in a building.  The type of utility purchased has a substantial impact on the source energy use of a building.  The EPA has determined that source energy is the most comparable unit for evaluation  purposes and overall global impact. Both the site and source EUI ratings for the building are  provided to understand and compare the differences in energy use.  The site and source EUIs for this building are calculated as follows. (See Table 3.4 for details):    Building Site EUI    =   (Electric Usage in kBtu + Gas Usage in kBtu + similar for other fuels)               Building Square Footage    Building Source EUI =   (Electric Usage in kBtu X SS Ratio + Gas Usage in kBtu X SS Ratio + similar for other fuels)        Building Square Footage  where “SS Ratio” is the Source Energy to Site Energy ratio for the particular fuel.    Table 3.4  Soldotna Police Station EUI Calculations    Energy Type Building Fuel Use per Year  Site Energy Use  per Year, kBTU  Source/Site  Ratio  Source Energy Use  per Year, kBTU  Electricity 124,468 kWh 424,809 3.340 1,418,863  Natural Gas 5,082 ccf 508,236 1.047 532,124  Total  933,046  1,950,987    BUILDING AREA 11,040 Square Feet  BUILDING SITE EUI 85 kBTU/Ft²/Yr  BUILDING SOURCE EUI 177 kBTU/Ft²/Yr  * Site ‐ Source Ratio data is provided by the Energy Star Performance Rating Methodology for Incorporating  Source Energy Use document issued March 2011.    Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 17 of 30  3.3 AkWarm© Building Simulation  An accurate model of the building performance can be created by simulating the thermal  performance of the walls, roof, windows and floors of the building. The HVAC system and  central plant are modeled as well, accounting for the outside air ventilation required by the  building and the heat recovery equipment in place.    The model uses local weather data and is trued up to historical energy use to ensure its  accuracy. The model can be used now and in the future to measure the utility bill impact of all  types of energy projects, including improving building insulation, modifying glazing, changing air  handler schedules, increasing heat recovery, installing high efficiency boilers, using variable air  volume air handlers, adjusting outside air ventilation and adding cogeneration systems.    For the purposes of this study, the Soldotna Police Station was modeled using AkWarm©  energy use software to establish a baseline space heating and cooling energy usage. Climate  data from Soldotna was used for analysis. From this, the model was be calibrated to predict the  impact of theoretical energy savings measures.   Once annual energy savings from a particular  measure were predicted and the initial capital cost was estimated, payback scenarios were  approximated. Equipment cost estimate calculations are provided in Appendix D.    Limitations of AkWarm© Models    • The model is based on typical mean year weather data for Soldotna. This data represents the  average ambient weather profile as observed over approximately 30 years. As such, the gas and  electric profiles generated will not likely compare perfectly with actual energy billing  information from any single year. This is especially true for years with extreme warm or cold  periods, or even years with unexpectedly moderate weather.                                            Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 18 of 30  Figure 3.4  Difference in Weather Data  Soldotna, AK Weather Data -20 -10 0 10 20 30 40 50 60 70 80 12/3/2009 1/22/2010 3/13/2010 5/2/2010 6/21/2010 8/10/2010 9/29/2010 11/18/2010 1/7/2011 2/26/2011 DateDry Bulb Temperature (F)Actual Dry Bulb (F)TMY3 Dry Bulb (F)   • The heating and cooling load model is a simple two‐zone model consisting of the building’s  core interior spaces and the building’s perimeter spaces.  This simplified approach loses  accuracy for buildings that have large variations in cooling/heating loads across different parts  of the building.  • The model does not model HVAC systems that simultaneously provide both heating and  cooling to the same building space (typically done as a means of providing temperature control  in the space).    The energy balances shown in Section 3.1 were derived from the output generated by the  AkWarm© simulations.  Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 19 of 30  4. ENERGY COST SAVING MEASURES  4.1 Summary of Results  The energy saving measures are summarized in Table 4.1.  Please refer to the individual measure  descriptions later in this report for more detail.  Calculations and cost estimates for analyzed measures  are provided in Appendix C.     Table 4.1  Soldotna Police Station, Soldotna, Alaska  PRIORITY LIST – ENERGY EFFICIENCY MEASURES Rank Feature Improvement Description Annual Energy Savings Installed Cost Savings to Investment Ratio, SIR Simple Payback (Years) 1 Lighting Replace with 5 200 W INDUCTION LAMPS $1,340 $5,000 1.71 3.7 TOTAL, cost-effective measures $1,340 $5,000 1.71 3.7 The following measures were not found to be cost-effective: 2 Lighting Replace with 13 FLUOR (2) T8 4' F32T8 32W Standard Instant StdElectronic $4 $1,625 0.02 369.1 TOTAL, all measures $1,344 $6,625 1.30 4.9   4.2 Interactive Effects of Projects  The savings for a particular measure are calculated assuming all recommended EEMs coming before that  measure in the list are implemented.  If some EEMs are not implemented, savings for the remaining  EEMs will be affected.  For example, if ceiling insulation is not added, then savings from a project to  replace the heating system will be increased, because the heating system for the building supplies a  larger load.    In general, all projects are evaluated sequentially so energy savings associated with one EEM would not  also be attributed to another EEM.   By modeling the recommended project sequentially, the analysis  accounts for interactive affects among the EEMs and does not “double count” savings.    Interior lighting, plug loads, facility equipment, and occupants generate heat within the building.  When  the building is in cooling mode, these items contribute to the overall cooling demands of the building;  therefore, lighting efficiency improvements will reduce cooling requirements in air‐conditioned  buildings.  Conversely, lighting‐efficiency improvements are anticipated to slightly increase heating  requirements.  Heating penalties and cooling benefits were included in the lighting project analysis.  Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 20 of 30  4.3 Building Shell Measures    No building shell improvements are recommended at this time.     Primarily Envelope Measures such as windows, doors, weather stripping, and insulation are only  considered cost effective if there is a visible deficiency which is noted during the audit. However it is  recommended that any time the facility replaces doors or windows that it uses a replacement with a  high efficiency rating. Also when renovating or constructing additions to the facility a energy cost  analysis should be taken when determining if a material with a greater R‐value should be used instead of  that of the code requirements.        Siemens Industry, Inc.  Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                 Page 21 of 30  4.4 Mechanical Equipment Measures    4.5 Electrical & Appliance Measures      4.5.1 Lighting Measures    The goal of this section is to present any lighting energy conservation measures that may also  be cost beneficial.  It should be noted that replacing current bulbs with more energy‐efficient  equivalents will have a small effect on the building heating and cooling loads.  The building  cooling load will see a small decrease from an upgrade to more efficient bulbs and the heating  load will see a small increase, as the more energy efficient bulbs give off less heat.    4.5.1a Lighting Measures – Replace Existing Fixtures/Bulbs          Rank Location  Existing Condition Recommendation  2  13 FLUOR (2) T12 4' F40T12 34W Energy‐Saver  Magnetic with Manual Switching  Replace with 13 FLUOR (2) T8 4' F32T8 32W Standard  Instant StdElectronic  Installation Cost  $1,625 Estimated Life of Measure  (yrs)7 Energy Savings    (/yr) $4 Breakeven Cost $28 Savings‐to‐Investment Ratio 0.0 Simple Payback   yrs 369 Auditors Notes:   ESTIMATE $125/FIXTURE  Rank Location  Existing Condition Recommendation  1  5 MH 400 Watt StdElectronic Replace with 5 200 W INDUCTION LAMPS  Installation Cost  $5,000 Estimated Life of Measure  (yrs)7 Energy Savings    (/yr) $1,340 Breakeven Cost $8,557 Savings‐to‐Investment Ratio 1.7 Simple Payback   yrs 4 Auditors Notes:   200W INDUCTION LAMPS  ESTIMATE $1000/FIXTURE  Siemens Industry, Inc.                     Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                          Page 22 of 31 Appendix A – Major Equipment Inventory  MAJOR EQUIPMENT INVENTORY Tag LOCATION FUNCTION MAKE MODEL TYPE CAPACITY  (input) EFFICIENCY MOTOR ASHRAE SERVICE LIFE ESTIMATED REMAINING LIFE NOTES Blr‐1‐5 Mechanical Room Bldg Heat Weil McLain PFG‐6 Gas Hot Water 175 mbh 87% est n/a 20 4‐6 Original PMP‐1,2 Mechanical Room Bldg Heat Grundfos UPC65‐160 In‐Line 93 gpm 88% est 1.5hp 20 4‐6 Main Circ pmps Zpmp 1‐9 Mechanical Room Zone Radiant Grundfos  In‐Line Varies per zone 88% est 150 w est 20 4‐6 Cycled by room t‐stat HWM‐1 Mechanical Room Domestic Hot Water (DHW) Amtrol WH‐10 In‐Tank Hx 240 gph  n/a 25 8‐10 Blr 1‐5 provide heat source AHU‐1 Mechanical Room Occupied  Space HVAC  Trane  Axial 6410 cfm  174 mbh heat 349 mbh cool 88% est 5hp 25 8‐10 2sp  starter not operating RF‐1 Mechanical Room Occupied  Space HVAC Trane  Avial  85% est 2hp 25 8‐10 Linked to SF‐1 SF‐1 Mechanical Room Mech  Rm Ventilation Penn Breezway P16T propeller 1680 cfm 85% est .25hp 15‐20 5 Manual Control EF‐1 Gun Area Exhaust Penn Z7 In‐line 100cfm 85% est 68w 15‐20 5 Manual Control EF‐2 Sally Port 117 Exhaust Lennox  In‐line 750 cfm 85% est 840w 15‐20 5   Manual Control EF‐3 Vehicle Evidence Exhaust Penn Z13 In‐line 1300 cfm 85% est 840w 15‐20 5   Manual Control EF‐4 Janitor 125 Exhaust Penn Z7 In‐line 100 cfm 85% est 68w 15‐20 5 Manual Control EF‐5,6 Toilets 126,127 Exhaust Penn Z7 In‐line 100 cfm 85% est 68w 15‐20 5 Manual Control EF‐7 Garage 104 Exhaust Penn Z13 In‐line 1900 cfm 85% est 1hp 15‐20 5 Manual Control EF‐8 Evidence 115 Exhaust Pace  85/u‐bf‐me Fume Hood 750 85% est .75hp 15‐20 5 Manual Control EF‐9 Men’s Locker Exhaust Penn  Z12 In‐line 400 cfm 85% est 265w 15‐20 5 Manual Control EF‐10 Women’s Locker Exhaust Penn  Z101 In‐line 250 cfm 85% est 239w 15‐20 5 Manual Control  Siemens Industry, Inc.                   Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                          Page 23 of 31 Appendix B – Partial Lighting Inventory  LIGHTING INVENTORY Location 13 W CFL 150 W MH 1x4x2 T12 1x4x2 T8 2 x 26W CFL 2x4x2 T8 2x4x3 T8 2x4x4 T8 35W MH 400W MH 70W MH Grand Total Exterior 5 3 5 5 18Gym 8 8Garage 20 20Hallways 2 211021 9 146Meeting Rooms 16 6 22Offices 8 211 17 17 55Restrooms 14 14Storage 1314 12 1 4024 Hour 10 10Grand Total 10 5 335137254 27356233                     Siemens Industry, Inc.                   Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                          Page 24 of 31 Appendix C – IR Photos / Heat Loss Signature   Expected heat loss through main door and around windows.   Heat loss through other doors and windows.  Heat from exterior lights.  Siemens Industry, Inc.                                                                        Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                         Page 25 of 31  Appendix D – REAL Utility Data First Name Last Name Middle  Name Phone Kyle Kornelis 262‐9107 State Zip AK 99669 Monday‐ Friday Saturday Sunday Holidays 24/7 24/7 24/7 24/7       Average # of  Occupants  During  84 0       Renovations Date PART II – ENERGY SOURCES  Heating Oil  Electricity  Natural Gas   Propane  Wood  Coal  $ /gallon  $ / kWh  $ / CCF  $ / gal  $ / cord  $ / ton xx Other energy  sources?  City of Soldotna Municipal 08/01/11 REAL Preliminary Benchmark Data Form PART I – FACILITY INFORMATION Facility Owner Facility Owned By Date Building Name/ Identifier Building Usage Building Square Footage Police Station Other 11,040 Building Type Community Population Year Built Mixed 4,021 1994 Facility Address Facility City Facility Zip 235 N. Binkley Soldotna 99669 Contact Person Email kkornelis@ci.soldotna.ak.us Mailing Address City 1. Please check every energy  source you use in the table below.  If known, please enter the base rate  you pay for the energy source. 2. Provide utilities  bills  for the most recent two‐year period for each energy source you use. Soldotna Details 177 N. Birch None Primary  Operating  Hours         Siemens Industry, Inc.                                                                        Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                         Page 26 of 31  Soldotna Police Station Buiding Size Input (sf) =11,040 2009 Natural Gas Consumption (Therms)6,159 2009 Natural Gas Cost ($)6,512 2009 Electric Consumption (kWh)138,320 2009 Electric Cost ($)22,637 2009 Oil Consumption (Therms) 2009 Oil Cost ($) 2009 Propane Consumption (Therms) 2009 Propane Cost ($) 2009 Coal Consumption (Therms) 2009 Coal Cost ($) 2009 Wood Consumption (Therms) 2009 Wood Cost ($) 2009 Thermal Consumption (Therms) 2009 Thermal Cost ($) 2009 Steam Consumption (Therms) 2009 Steam Cost ($) 2009 Total Energy Use (kBtu)1,087,986 2009 Total Energy Cost ($)29,149 Annual Energy Use Intensity (EUI) 2009 Natural Gas (kBtu/sf) 55.8 2009 Electricity (kBtu/sf)42.8 2009 Oil (kBtu/sf) 2009 Propane (kBtu/sf) 2009 Coal (kBtu/sf) 2009 Wood (kBtu/sf) 2009 Thermal (kBtu/sf) 2009 Steam (kBtu/sf) 2009 Energy Utilization Index (kBtu/sf)98.5 Annual Energy Cost Index (ECI) 2009 Natural Gas Cost Index ($/sf)0.59 2009 Electric Cost Index ($/sf)2.05 2009 Oil Cost Index ($/sf) 2009 Propane Cost Index ($/sf) 2009 Coal Cost Index ($/sf) 2009 Wood Cost Index ($/sf) 2009 Thermal Cost Index ($/sf) 2009 Steam Cost Index ($/sf) 2009 Energy Cost Index ($/sf)2.64 Siemens Industry, Inc.                                                                                                                             Soldotna Police Energy Audit Report  AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                         Page 27 of 31  2010 Natural Gas Consumption (Therms)4,648 2010 Natural Gas Cost ($)4,399 2010 Electric Consumption (kWh)134,080 2010 Electric Cost ($)20,027 2010 Oil Consumption (Therms) 2010 Oil Cost ($) 2010 Propane Consumption (Therms) 2010 Propane Cost ($) 2010 Coal Consumption (Therms) 2010 Coal Cost ($) 2010 Wood Consumption (Therms) 2010 Wood Cost ($) 2010 Thermal Consumption (Therms) 2010 Thermal Cost ($) 2010 Steam Consumption (Therms) 2010 Steam Cost ($) 2010 Total Energy Use (kBtu)922,415 2010 Total Energy Cost ($)24,426 Annual Energy Use Intensity (EUI) 2010 Natural Gas (kBtu/sf)42.1 2010 Electricity (kBtu/sf)41.5 2010 Oil (kBtu/sf) 2010 Propane (kBtu/sf) 2010 Coal (kBtu/sf) 2010 Wood (kBtu/sf) 2010 Thermal (kBtu/sf) 2010 Steam (kBtu/sf) 2010 Energy Utilization Index (kBtu/sf)83.6 Annual Energy Cost Index (ECI) 2010 Natural Gas Cost Index ($/sf)0.40 2010 Electric Cost Index ($/sf)1.81 2010 Oil Cost Index ($/sf) 2010 Propane Cost Index ($/sf) 2010 Coal Cost Index ($/sf) 2010 Wood Cost Index ($/sf) 2010 Thermal Cost Index ($/sf) 2010 Steam Cost Index ($/sf) 20010 Energy Cost Index ($/sf)2.21 Note: 1 kWh = 3,413 Btu's 1 Therm = 100,000 Btu's 1 CF ≈ 1,000 Btu's     Siemens Industry, Inc.                                                                                                                                                                                Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                                    Page 28 of 31 Soldotna Police StationNatural GasBtus/CCF =100,000Provider Customer #Month Start Date End Date Billing Days Consumption (CCF) Consumption (Therms) Demand Use Natural Gas Cost ($) Unit Cost ($/Therm) Demand Cost ($)Enstar NGC5765 Jan‐09 1,248 1,248 $1,300 $1.04Enstar NGC5765 Feb‐09 886 886 $927 $1.05Enstar NGC5765 Mar‐09 730 730 $766 $1.05Enstar NGC5765 Apr‐09 521 521 $550 $1.06Enstar NGC5765 May‐09 302 302 $324 $1.07Enstar NGC5765 Jun‐09 197 197 $215 $1.09Enstar NGC5765 Jul‐09 169 169 $191 $1.13Enstar NGC5765 Aug‐09 256 256 $280 $1.09Enstar NGC5765 Sep‐09 270 270 $291 $1.08Enstar NGC5765 Oct‐09 391 391 $416 $1.06Enstar NGC5765 Nov‐09 552 552 $582 $1.05Enstar NGC5765 Dec‐09 637 637 $670 $1.05Enstar NGC5765 Jan‐10 620 620 $544 $0.88Enstar NGC5765 Feb‐10 685 685 $599 $0.87Enstar NGC5765 Mar‐10 563 563 $495 $0.88Enstar NGC5765 Apr‐10 312 312 $283 $0.91Enstar NGC5765 May‐10 302 302 $275 $0.91Enstar NGC5765 Jun‐10 172 172 $162 $0.94Enstar NGC5765 Jul‐10 208 208 $193 $0.93Enstar NGC5765 Aug‐10 187 187 $259 $1.39Enstar NGC5765 Sep‐10 169 169 $245 $1.45Enstar NGC5765 Oct‐10 454 454 $473 $1.04Enstar NGC5765 Nov‐10 346 346 $253 $0.73Enstar NGC5765 Dec‐10 630 630 $618 $0.98Dec ‐ 08 to Nov ‐ 09 total:6,159 6,159 0$6,512 $0.00Dec ‐ 08 to Nov ‐ 10 total:4,648 4,648 0$4,399 $0.00$1.07$0.99Dec ‐ 08 to Nov ‐ 09 avg:Dec ‐ 08 to Nov ‐ 10 avg:         Siemens Industry, Inc.                                                                                                                                                                                Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                                    Page 29 of 31 Soldotna Police Station ‐ Natural Gas Consumption (Therms) vs. Natural Gas Cost ($)02004006008001,0001,2001,400Jan‐09Feb‐09Mar‐09Apr‐09May‐09Jun‐09Jul‐09Aug‐09Sep‐09Oct‐09Nov‐09Dec‐09Jan‐10Feb‐10Mar‐10Apr‐10May‐10Jun‐10Jul‐10Aug‐10Sep‐10Oct‐10Nov‐10Date (Mon ‐ Yr)Natural Gas Consumption (Therms)$0$200$400$600$800$1,000$1,200$1,400Natural Gas Cost ($)Natural Gas Consumption(Therms)Natural Gas Cost ($)    Siemens Industry, Inc.                                                                                                                                                                                Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                                    Page 30 of 31 Soldotna Police StationElectricityBtus/kWh =3,413Provider Customer #Month Start Date End Date Billing Days Consumption (kWh) Consumption (Therms) Demand Use Electric Cost ($) Unit Cost ($/kWh) Demand Cost ($)HEA 2002781 Jan‐09 12,120 414 26 $1,818 $0.15 $204.30HEA 2002781 Feb‐09 11,400 389 25 $2,417 $0.21 $182.36HEA 2002781 Mar‐09 10,480 358 23 $1,819 $0.17 $166.30HEA 2002781 Apr‐09 10,680 365 22 $1,836 $0.17 $154.55HEA 2002781 May‐09 10,640 363 23 $1,841 $0.17 $156.16HEA 2002781 Jun‐09 10,520 359 21 $1,837 $0.17 $148.05HEA 2002781 Jul‐09 9,960 340 22 $1,759 $0.18 $152.27HEA 2002781 Aug‐09 11,280 385 22 $1,956 $0.17 $156.49HEA 2002781 Sep‐09 11,160 381 21 $1,678 $0.15 $150.76HEA 2002781 Oct‐09 12,760 435 25 $1,903 $0.15 $178.27HEA 2002781 Nov‐09 12,920 441 25 $1,922 $0.15 $177.41HEA 2002781 Dec‐09 14,400 491 25 $1,851 $0.13 $181.71HEA 2002781 Jan‐10 11,800 403 24 $1,568 $0.13 $173.11HEA 2002781 Feb‐10 11,160 381 23 $1,496 $0.13 $167.95HEA 2002781 Mar‐10 12,200 416 23 $1,866 $0.15 $175.60HEA 2002781 Apr‐10 12,040 411 21 $1,834 $0.15 $163.14HEA 2002781 May‐10 9,360 319 20 $1,483 $0.16 $151.29HEA 2002781 Jun‐10 10,160 347 19 $1,597 $0.16 $174.00HEA 2002781 Jul‐10 10,280 351 21 $1,628 $0.16 $162.84HEA 2002781 Aug‐10 10,520 359 22 $1,660 $0.16 $163.45HEA 2002781 Sep‐10 10,960 374 21 $1,618 $0.15 $161.27HEA 2002781 Oct‐10 11,080 378 24 $1,656 $0.15 $184.80HEA 2002781 Nov‐10 11,600 396 23 $1,712 $0.15 $178.61HEA 2002781 Dec‐10 12,920 441 26 $1,909 $0.15 $199.04Jan ‐ 09 to Dec ‐ 09 total:138,320 4,721 281 $22,637 $2,009Jan ‐ 10 to Dec ‐ 10 total:134,080 4,576 268 $20,027 $2,055$0.17$0.15Jan ‐ 10 to Dec ‐ 10 avg:Jan ‐ 09 to Dec ‐ 09 avg:     Siemens Industry, Inc.                                                                                                                                                                                Soldotna Police Energy Audit Report AkWarm ID No. CIRI‐SXQ‐CAEC‐08                                                                                                                    Page 31 of 31 Soldotna Police Station ‐ Electric Consumption (kWh) vs. Electric Cost ($)02,0004,0006,0008,00010,00012,00014,00016,000Jan‐09Feb‐09Mar‐09Apr‐09May‐09Jun‐09Jul‐09Aug‐09Sep‐09Oct‐09Nov‐09Dec‐09Jan‐10Feb‐10Mar‐10Apr‐10May‐10Jun‐10Jul‐10Aug‐10Sep‐10Oct‐10Nov‐10Dec‐10Date (Mon ‐ Yr)Electric Consumption (kWh)$0$500$1,000$1,500$2,000$2,500$3,000Electric Cost ($)Electric Consumption (kWh)Electric Cost ($)