Togiak Feasibiity Study Supplemental Data Report 1985
fEASIBILITY STUDY FOR TOGIAK HYDROELECTRIC PROJECT SUPPLEMENTAL DATA REPORT: HYDROLOGY Prepared For: Alaska Power Authority Prepared By: DOWL Engineers May, 1985 W. 0 • f!D 1 3 4 7 0 TABLE Of CONTENTS Purpose •• Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drainage Area •. ......................................... Gaqe •••••....••. ........................................ Reference Marks .....••• ................................. Discharge Measurements. ................................. Rating Curve ••••. Channel. ................................................ Control. ................................................ Remarks. ................................................ APPENDICES Appendix A -Discharge Rating Curve Measurements Appendix B -Printout of Discharge Measurements 4-Hour Stage Data and Corresponding Discharges Figure Figure 2 - Figure 3 Table 1 LIST Of FIGURES Project Location Map Discharge Rating Curve -Kurtluk Togiak, Alaska 1984 Hydrograph of Kurtluk River Summary Kurtluk LIST Of TABLES Streamflow Data, 1984. River, Togiak, Alaska River 1 1 2 3 3 4 4 5 5 TOGIAK Streamflow nata, Kurtluk River Purpose: The purpose of this effort is to collect streamflow data for Kurtluk River as part of the Togiak Hydroelectric Project Feasibility Study. Streamflow data collection began on October 20, 1982. Streamflow data reports for the calendar years 1982 and 1983 were submitted to the Alaska Power Authority in connection with the feasibility study. The streamflow data presently being gathered is an additional supplement to the hydrology study completed for the feasi- bility of hydropower development. This report includes a daily stream discharge summary table as well as stage and discharqe records for four-hour periods for the 1984 calendar year. Location: The gage is located on the left bank of the river, Lat. 59°03'40", Long. 160°29'30" based on Goodnews Bay /l..-4 Qu8d, 5 miles west of Togiak Village. The gage can be reached by walking from the edge of town in summer ur by snowmachine in winter (see Figure 1 -Location Map). Drainage Area: The drainage area is 13.9 square miles at the gage site. No glaciers exist within the drainaqe basin and basin eleva- tions rise as high as 2500 feet mean sea level (MSL). ------·'·' I!! SCALE - 1• repreeent• 1 MI. Q 0 ~\ .,.. LOCA TlON t.4AP ,.,...-/ NOT T 0 SCAI..l ~ENGINEERS LOCATION OF STREAM GAGING STATION AND HYDROELECTRIC PROJECT AREA FIGURE TOGIAK ALASKA ~: Gaging equipment consists of a digital (Omnidata Datapod) and a staff gage. recorder/sensor Digital Gage: The digital gage is an Omnidata Datapod coupled with a small piezo-electric pressure transducer and a thermistor temperature probe. The datapod is an ultra low power microprocessor controlled recorder with several advan- tages. The device contains a battery supply, an analog to digital converter (12-15 bits), a microprocessor, a non- volatile storage module and a clock with an accuracy of several minutes per month. The transducer is housed inside a cylindrical brass casing which is secured to the streambed by driving a steel rebar through a hole in the casing. A cableway extends to the recorder on the streambank. The recorder is set to sample the pressure and temperature every five minutes. The average of the 5-minute readings are recorded every four hours in an 8-bit format. Following the 8Ssembly of the datapod, a digital stage recorder was in- stalled on October 20, 1982. Gaqing equipment specifications are attached to the 1982 report as Appendix C. Staff Gage: The staff qaqe is a rigid, precisely graduated, porcelain enameled iron plate securely fixed to a fence post driven into the streambed. It was installed on Kurtluk River during an initial site visit for the hydroelectric feasibility study. 2 Reference Marks: RM-1 (base) is at the top of an 18-inch diameter CMP stilling well: Elevation 5.41 feet, gage datum. RP-1 is at the top of a rebar 30 feet downstream on the right bank: Elevation 5.25 feet, gage datum. Discharge Measurements: Continuous measurements of stream discharge are obtained through collection of stage data at the gaging station. The stage of a stream is the height of the water surface above an established datum. The stage data on Kurtluk River is collected every four hours by an Omnidata Datapod digital recorder. In stream gaging procedures, stage data is used as the independent variable in a stage-discharge relation to derive discharges. It is, therefore, norm3l practice to establish a relationship (rating curve) between the stage at the gaging station and the discharge. This relationship depends on the shape of the cross-section and the roughness of the streambed. Therefore, the relationship has to be established empirically. As part of establishing the rating discharge measurements were taken at using a Marsh-McBirney Model 201 flow curve relationship, the gaging station current meter. 1he stage of the stream was also noted during discharge measurements and is provided below along with the discharge measurements. 3 Date Discharge (cfs) Gage Height (ft)(Stage) 0. 49 [shift (+)0. 31] 1 • 20 01/18/84 05/16/84 10/29/84 Rating Curve: 1 5 53 1 5 0.80 The rating curve for Kurtluk River will continue to be developed as additional stage-discharge data points are col- lected. A preliminary rating curve is plotted for the period of record and is shown in Figure 2. computation sheets are provided in Appendix A. The discharge After having established the ratin9 curves, measurements will have to be continued to enable verification, and if necess;:ny, Adjustment of the rating curve to the actual cir- cumstances. Deviations from the discharges read from the ratinq curve <'He caused by morphological chFinges of the streambed and stream icing problems. Channel: lhe channel 3bove the qage location is in a floodpl"lin with 8 steep bedrock valley wall (20-40 feet) on the west side and sloping topography on the east side. The channel hanks and the floodpL:lin ~re covered with grass, small brush, anll alders. Above the floodpl3in the terrain is covered wi~-h tundra vegetation. Bed material consists of gravels, pebbles and cobbles. 4 2.0 - 1.5 !- -- 1.0 - .9-- .8----.7-r- ... .6 r-1.1..1 1.1..1 Lt.. .5 1-z ... :X: .4 1-(!) ijj :r 1.1..1 (!) .3 1-<t (!) .2~ ... . 2 ... . 15 - I L I I I I I I I I I I .1+------1----+---+--+---+---+--+---+---+--+--+-----1 10 15 20 25 30 40 so eo 10 eo so 100 r5o DISCHARGE IN CUBIC FEET PER SECOND ~ RATING CURVE FOR KURTLUK RIVER FIG 2 ~ENGINEERS TOGIAK, ALASKA-YEAR 1984 . Control: The control is a cross-section or reach of stream channel that determines the relationship between stage and discharge f'lt that section and for some distance upstream. Permanent controls are desired for 8 stable stage-discharge relation- ship; however, changes (shifts) in the control occur affect- ing the relationship of stage to discharge. At low stages, B protruding rock outcrop downstream of the digital gage will be the control for stream water levels. At medium and high stages, the channel will be the dominant control. Remarks: Stage records are good for those periods when the stage sensing and recording instruments were functioning proper- ly. Otherwise, data gaps exist for winter and summer months, and data for these periods were synthesized on the b8sis of weather data (Dillingham and King Salmon) and from data on nearby qaginq stations (Eskimo Creek). Reliable data were obtained for forty-eiqht percent of the monitorinq period. Shifts in the stream control and a malfunctioning transducer due to flood damage prevented recovery of stage datB for fifty-two percent of the monitoring period. Loss in the data collection percentage (when compared to the 1982 and 1983 records) is primarily due to the flood-induced transducer damage and river ice problems. The period of synthesized data is indicated in the summary stream dis- charge table (Table 1). In ;Jddition to the staqe, stream temperature was also measured and the results are provided in the following printout sheets. Stream gaging activity on this creek has been terminated as of February, 1985. 5 TABLE 1 A SUMMARY OF KURTLUK RIVER (TOGIAK, ALASKA) STREAMFLOW RECORDS FOR JANUARY 1, 1984 THROUGH SEPTEMBER 31, 1984 1984 Day Jan Feb Mar Apr May Jun Jul Aug Sep I 7.6 10 9.1 18 29 23 35 5.1* 11 * 2 7.2 13 7.8 18 20 23 33 5.4* 9.4* 3 6.8 18 7.2 18 19 23 30 5.4* 8.5* 4 6.4 15 7.2 16 20 23 30 5. 1* 8. 1* 5 6.1 15 13 17 18 22 28 5.1* 7.6* 6 5. 7 15 13 15 18 22 28 4.8* 7.3* 7 5.4 13 14 14 19 22 27 4.9* 7.3* 8 5.0 1 5 10 11 21 20 27 4.6* 7.3* 9 4.7 15 12 20 22 21 26 4.6* 7.5* 10 4.4 16 13 24 24 21 22 4. 3* 7.3* 11 4. 1 18 16 19 24 21 22 6. 3* 7.3* 12 4.0 19 14 19 23 21 22 6.5* 7. 1* 13 15 24 7.0 21 23 21 5.2* 6. 3* 7. 7* 14 15 37 5.9 23 24 20 5.4* 5.6* 7.9* 15 11 39 5. 1 21 48 19 5.0* 5. 1 * 7.9* 16 10 37 9.5 18 34 19 5.0* 4.8* 7.5* 17 12 40 19 17 31 20 5.2* 4.3* 6.9* 18 13 33 20 16 30 20 4.9* 4.8* 6.7* 19 13 26 15 12 28 19 4.9* 4. 9* 6.3* 20 15 24 14 12 27 21 5. 7* 4.6* 6.7* 21 15 33 14 15 27 24 6.8* 5.5* 7. 1 * 22 15 62 13 12 24 22 6.8* 7.7* 6.7* 23 1 5 83 13 1 3 24 31 6.8* 7.9* 6.6* 24 12 62 12 11 24 66 5.4* 13* 6.5* 25 10 39 11 11 24 58 5. 1 * 18* 6.5* 26 11 28 11 18 24 42 5.4* 22* 6. 3* 27 9.3 20 12 39 24 37 5.2* 23* 6.0* 28 6.6 14 12 52 24 34 5.1* 21* 5.6* 29 7.4 11 15 54 24 35 4.9* 16* 5.6* 30 6.8 -13 31 24 36 4.9* 14* 6. 1 * 31 9.9 -1 3 -24 -5. 1 * 12* - Total 290 794 371 595 769 806 433 270 216 Mean 9 27 12 20 25 27 14 9 7 MEAN FLOW FOR THE PERIOD OF RECORD 17 CUBIC FEET PER SECOND. *Synthesized data 100 100 .a 80 80 ~ 110 70 70 eo ~ eo .a ~ t1 eo I (\I I It ~· I~ , I 1 40 so 20 20 ___ -------~MEAN FLOW 17 CFS :t I , v\ r \ / r \/ I I \ ~: Cf) I.J.... CJ) u LL. • (.) ~\j V"J '\J ~ '-"'-v· ' 6 w w C) C) !l 0::: 0: <( <( I 4 I (.) u CJ) Cf) 0 5 0 z .. '2 -· ·~ 1.0 ~ANUARY FEBRUARY MARCH APRIL MAY JUNE JULY AUGUST !ZPTEMBER ~ENGINEERS 1984 HYDROGRAPH OF KURTLUK RIVER, TOGIAK, ALASKA FIGURE 3 APPENDIX A Discharge Rating Curve Measurements '• PROJECT NAME RIVER NAME TRANSECT NO. TOGIAK HYDROELECTRIC :.-<.URTLUK RIVER GAGE SITE-1-18-84 PT. STAT ICN l..JI DTH <FEET> <FEET> -----------~-·--·- 1 43 00 0. 00 2 44. 00 1. 00 3 45. 00 100 4 46. 00 1 00 5 47. 00 1. 00 6 48. 00 1. 00 7 49. 00 1. 00 8 50. 00 1. 00 9 51. 00 1. 00 10 52.00 1 00 1 1 53. 00 100 12 54 00 1. 00 13 55. 00 1. 00 14 56. 00 1. 00 15 57. 00 1. 00 16 58. 00 1. 00 17 59. 00 1. 00 18 60. 00 1. 00 19 61. 00 1 00 20 62 00 1 00 21 63 00 1. 00 "';"') 64 00 1 00 c:.c::. 23 65. 00 1 00 24 66. 00 0. 00 SUM OF CELL DISCHARGES = 15. 43 SUM OF CELL AREAS = 23. 30 i•iEAN VELOCITY = 0. 66 Pag; DEPTH VELOCITY AREA DISCHARGE (FEE f> (FTISEC> (SO FT> <CFS> ----·-·---·-·--.. . ----·-------------- 0 00 0 00 0. 00 0.00 0 70 0 00 0. 70 0.00 0 80 0 10 0. 80 0.08 0 70 0. 05 0. 70 0. 03 0 90 0. 00 0. 90 0.00 1 10 0 00 1. 10 000 1 10 0 05 1 10 0. 05 1 50 0 05 1. 50 007 1. 50 0. 30 1. 50 0. 45 1. 60 0 70 1. 60 1 12 1 40 1. 00 1 40 140 1. 40 105 1. 40 1 47 1. 30 1. 10 1. 30 1. 43 130 1. 10 1. 30 1. 43 1. 40 1. 30 1. 40 182 1. 00 1. 30 100 1. 30 1. 30 1. 00 1 30 1. 30 1 10 1 00 1 10 1. 10 1. 00 0. 90 1 00 0. 90 0. 80 1. 10 0. 80 0. 88 0. 70 0 60 0. 70 0. 42 0. 50 0. 30 0 50 0. 15 0 20 0. 10 0 20 0.02 0 00 0. 00 0. 00 0.00 CUBIC F f. /SEC. SQUARE Ff FT /SEC PROJECT NAt1E R I VER Nt~~1E TRAtJ3EC T h!O TOGIAK HYOROELECTP P hUF"~ H. UK R I VFr~ GAGE SITE 0~/16/84 PT. STATION lJIDTH I FEET> (FEET) -··--------~-··-- 1 3 00 0. 00 ,.., 3. 50 0 50 c.. 3 4. 00 1' 25 4 6. 00 2 00 5 8. 00 1. 50 6 9 00 1 CIJ 7 1000 1. 00 8 11 00 1 00 9 12 00 1 00 10 13. 00 l 00 1 1 14.00 1 50 12 16 OG 2 co 13 18 00 2 00 14 20 00 2 00 15 22 00 2. 00 16 24 00 2 00 17 2t, 00 2 00 18 28. 00 2. 00 19 30 00 2. 00 20 32 00 0 00 SUM OF CELL DISCHARGES = 5:3. 69 SUM OF CELL AREAS --25 75 MEAN VELOCITY ... 2 08 PagF DEPTH VELOCITY AREA DISCHARGE <FEETl <FT!SECl (SQ FTl (CFSl ·-·--·-·· ---.. ·~~ ~·----~ -·---..._._ ---·--·----..... 0 00 0. 00 0 00 0 00 l 00 0 90 0. 50 0. 45 1 00 1 35 125 1 69 0 90 1 80 1 80 3 24 1 00 2. 10 1 50 3. 15 0 80 2 20 0 80 1 76 0. 70 2. 30 0. 70 1' 61 0 70 2 30 0. 70 1. 61 0 75 2 60 0. 75 1. 95 0 70 2. 80 0. 70 1. 96 0 70 3. 00 1. 05 3. 15 0 70 2. 70 1 40 3 78 0 80 2. 30 1. 60 3. 68 0 90 2 90 1 80 5 .,,., <:.c.. 1. 00 2 :w 2 00 4. 60 1 20 2 60 2. 40 6. 24 1 20 2 60 2 40 6.24 1. 00 1. 20 2. 00 2. 40 120 0 40 2. 40 0. 96 0 00 0. 00 0 00 0. 00 CUBIC FT /SEC SQUARE FT. FT /SEC. 'I 'I .,.,, I !I' I I' R II,-; 1-~~i I ~ I I· I,! I I• i ~A~ ,J '''I il.j l····i 1,,1 In 171 111 ,, ,. "' !l '"I '" ,,I •. 1 171 ~ ':1 ,., I PROJECT NAME RIVER NAME TRANSECT NO. KURTLUK HYDROELEC PR KURTLUK RIVER GAGE SITE-10/29/84 PT. STATION WIDTH <FEET> <FEET> ------------ 1 0. 00 0.00 2 1. 00 1. 50 3 3. 00 2.00 4 5. 00 2. 00 5 7. 00 2.00 6 9. 00 2. 00 7 11. 00 2. 00 8 13. 00 2. 00 9 15. 00 2.00 10 17.00 2. 00 11 19. 00 2. 00 12 21. 00 2. 00 13 23. 00 2.00 14 25. 00 2. 00 15 27. 00 0. 00 SUM OF CELL DISCHARGES = 15. 81 SUM OF CELL AREAS -16. 30 MEAN VELOCITY = 0. 97 F DEPTH VELOCITY AREA DISCHARGE <FEET> <FT/SEC> <SG.FT> <CFS> --------------------· -~------- 0. 00 0. 00 0.00 0.00 0. 60 0. 30 0.90 0. 27 0.80 0. 60 1. 60 0. 96 1. 10 1. 00 2.20 2. 20 0.90 0. 90 1. 80 1. 62 0. 70 1. 00 1. 40 1. 40 0. 50 0. 90 1. 00 0. 90 0. 60 1. 20 1. 20 1. 44 0. 70 1. 30 1. 40 1. 82 0. 60 1. 40 1. 20 1. 68 0. 50 1. 20 1. 00 1. 20 0. 40 0.90 0. 80 0. 72 0. 40 1. 00 0.80 0.80 0. 50 0.80 1. 00 0.80 0. 00 0. 00 0.00 0. 00 CUBIC FT. /SEC. SQUARE FT. FT. /SEC. t ' i i ~ I I PROJECT NAME RIVER NAME TRANSECT NO. TOGfA~ HYDRO PRJ KURTLUK RIVER GAGE SITE-2/28/85 PT. STATION WIDTH <FEET~ <FEET) ------------·- 1 11. 50 0.00 2 15. 70 3. ~35 3 18. 20 2. 75 4 21. 20 3. 1.0 5 24. 40 3. lO 6 27. 40 3. 10 7 30. 60 1. 80 8 31. 00 0. OC• SUM OF CELL DISCHARGES = 13 94 SUM OF CELL AREAS = 17 58 MEAN VELOCITY = 0 79 DEPTH VELOC IT'{ AREA DISCHARGE <FEET) (FT/SEC) <SG FT) 1 c~-s! -·--------··-----------·-----.. ·-~--·- 0. 00 0. 00 0. 00 0 00 0 80 o. :..10 2. 68 0 80 0. 80 0 45 2. 20 0 99 0 90 0. "10 2. 79 1 95 1 30 1 30 4.03 5 24 1. 20 1. 10 3. 72 4. 09 1 20 0 40 2. 16 0. 86 0. 00 0. 00 0.00 0 00 CUBIC FT /SEC. SQUARE FT. FT. /SEC. APPENDIX B Printout of Discharqe Measurements 2-Hour and/or 4-Hour Staqe Data and Corresponding Discharges I I I 1 I I •1 II 1111 PROPO~:>EJ: TU(~JAK H•'lY'·-FtY~. fP 1 ., '] t[ T KURTLU•\ RfVER NEAR T••<:;If.,.u, ,4•J,-.+;> DATE TIME -=::.:==:-.:::: ·~= ::::=:::~= 01/19/84 04:00 01/1.9/84 08:00 01119/84 12:00 01119 I E\4 16: 00 01119/1.:;)4 20:00 i) 1 / 1 9 h3 il 00: 00 01/20/84 04:00 01/20/'.)l! 08· 00 1,}1/20/84 12: 00 01/20/84 16:00 01120/84 20: 00 01!20h)4 00:00 01/21/fH 01121184 01/21/!:14 01/21/84 01121/84 01/21/84 04:00 08:00 .12:00 16·00 20:00 00:00 01/22/84 04:00 01/22/84 08:00 01122/84 12:00 01122/84 16: 00 01/22/5-)4 20· 00 01122/84 oo·oo 01/23/84 04:00 01123/84 08:00 01/23/84 12:00 01/23/84 16:00 01/23/84 20:00 01/23/84 00:00 BY r. I:U>,~J D•1;,.:. .:;:;-~ !!."::-:::~":! ~::;::::;·::: ~~4 -~. 00 "'4 ·,* i :24 no 24 .i. ()I) ~~:4 : (\,1 I' 24 .l•)O DAILY AVERAGE VALUES 1 J 24 tOO I~ Jf!. 1.\") i. 7 24 i '.)•.) i9 24 1•\f) d! 24 tOO 2 .q. 1~ ·~1(} DAILY AVERAGE Vt,UJFS ~~-5 24 ·:;:7 24 .-2t:i 24 3!. ;~ 1l 3::< 24 '].:.y 2'+ DAIL V 1".\JERAGE tOO i.O(! l. ()i\ 11.){) }.(!0 ~ {"lr) \-' t~. t IJE ~~i }7 24 100 :Jo 24 U.l·') 41. 24 1 ,·~·~) 4<.=i 21~ t nr:- ~~-5 2 {~ 1 ')(_) 47' 24 1~::; DAILY AVERAGE ~ALUES 19 24 100 51 24 tOO 5~ 24 lOU ~~ 24 !00 51 23 100 :}9 24 100 DAILY tNERAGE 'v'ALUES I I l"'H,/ ·~ 8 '" p ·I 8 i 8 iJ. 8 •! 8 ;J. 8 /f 8 ;J. 8 '+ 8 4. 8 't El .:1 8 ll 8 '" 8 8 ol-8 .~ f) ·< 8 -'.i. B 4 8 I 8 ;{. EJ 4. 8 ,:;. ~3 -~ ~J ·~ i:] 4 8 r:j. 8 4 8 4 8 4. 8 4 6 ~.8 ~-8 r 1 r 1 f j -! <:''1 · 10/I'J. ,-,.,GE 1 ~;r,,r-;r 'ir·lE OJ/t':;r3·1 04 OC> DEPTH INCHES =====".:: 9. 6 9.6 9. 6 9 6 9 6 9 6 9. 6 9.6 9. 6 9.6 9. 6 9. 6 9.6 9. 6 9 6 9. 6 9. 6 9. 6 9. 6 9.6 9. 6 9. 6 9.6 9. 6 9.6 9.6 9.6 9. 6 9. 6 9. 6 9. 6 9. 6 9. 2 9. 6 9. 5 STAG':~ FI:CE r 0 t-:•.1 0 8<) () 8•') I} 8 0 j::l(') () (~~() 0 8(· 0 8<.: 1). 8•: Q. 8·) 0. 8•) 0. 8ti 0 8ij (! 8(' n B~) 0 8(• I) 8•) \) 8•~) 0. 8() 0. 8·~ 0. 8<! U. \::i·> 0.8G c 8• 0. 8<) 0 8•.} (i 8i) 0 8·} G 8•.·; f) 8:) 0 8'1 0. 8•.-1 0. 7 7 0. 80 0 8•) DI');'HG c:·· t ---· t r.:. -; r:-.;. 1 :3 l ~~ t':i J.~ 15 l5 1 :::· i5 l5 15 1 :-=: 15 i ''j i3 i3 i5 .• t:; ..... 1'5 t C) 15 1.5 iS i"i !'-'> 15 15 L '" J.S 13 15 15 TEMP DEG C ·===== 0.0 0 0 0.0 0.0 () 0 0. 0 0.0 0 0 0. 0 0.0 0.0 0. 0 0.0 0 0 0. 0 0.0 0. 0 0 0 0 0 0 0 0 0 0.0 0.0 0. c 0. 0 0 0 0. 0 0.0 0.0 0. 0 0. 0 0. 0 0. 0 0. 0 0. 0 PROPOSED TOGIAK HYDROELECTRIC ~-'RO.JECT 0~5/ 10/85 PAGE 2 KURTLUK RIVER NEAR TOGIAK, ALAS!': A START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME flYTE RAW DATA MV INCHES FEET CFS DEG C =:::=::==:::::-~· ====:::t ::=:::::"'!':~ ===::~=t-e:_:.:;•: =~== =====~:-: ====-= ==:::=:=~~ ===== 01/24/84 04:00 61 24 100 4 8 9. 6 0. 80 15 0. 0 01/24/84 08:00 63 23 100 4. l: 9. 2 0. 77 13 0.0 01124/84 12: 00 65 22 100 4. 4 8. 8 0. 73 11 0 0 01/24/84 16:00 6l 22 100 4. 4 8. 8 0 7] 11 0.0 01/24/84 20:00 69 24 100 4. 8 9. 6 0 8:) 15 0 0 01124/84 00: 00 71. 19 1.00 3.8 7. 6 0.6J -t _..., 0 0 I . C.. DAILY AVERAGE VALUES 4. 5 8. 9 0 74 12 0. 0 01/25/84 04:00 ?3 21 100 4 2 8. 4 0. 70 9.8 0. 0 01/25/84 08:00 75 22 1 f)() 4. 4 8. 8 0. 7: .. 1 11 0.0 01125/84 12: 00 ·.'7 2!. 100 4 ·-· d.. 8. 4 0 7;i 9. 8 0.0 01/25/84 16:00 7P 24 100 4 8 9. 6 0 8•:· 15 0.0 01/25/84 20:00 81 18 J. (J() 3 6 7.2 0 60 6. 0 0.0 01/25/84 00:00 8'~ •J 22 100 4 4 8. 8 0. 7.J 11 0.0 DAILY AVERAGE VALUES 4. 3 8 5 0. 71 10 0. 0 01126/84 04: 00 85 25 1()() ... , 0 10. 0 0 8'] 17 0.0 01/26/84 08: 00 87 23 100 ~~ 6 9. 2 0. 7? 1.-_; '"' 0.0 01/26/84 12:00 89 20 100 t:j. 0 8. 0 0 67 8 4 0.0 01/26/84 16:00 91 20 100 l.j._ 0 8. 0 0. 67 8. 4 0. 0 01/26/84 20:00 93 22 100 ~~ 4 8. 8 0. 7:J 11 0.0 01/26/84 00:00 95 18 1 ')(\ J 6 7.2 0 6rJ 6 0 0. 0 DAILY AVERAGE VALUES 1}. :3 8. 5 0. 71 11 0.0 01/27/84 04:00 97 20 10C• 4 0 8. 0 0 67 8. 4 0. 0 01/27/84 08:00 99 20 100 4. 0 8.0 0.67 8. 4 0. 0 01/27/84 12:00 101 20 1 ()() 4. 0 8.0 0.67 8. 4 0. 0 01/27/84 16:00 103 20 100 4. 0 8. 0 0 67 8 4 0.0 01/27/84 20:00 105 2i1 100 4-. /.j. 8.8 0 73 1 l 0.0 01/27/84 00:00 107 22 10(> .'f. 4 8. 8 0. 7: 11 0. 0 DAILY AVERAGE Y'I~LUES 4. j 8.3 0 69 9. 3 0 0 01128/84 04: 00 109 18 100 J 6 7.2 0. 6() 6. 0 0.0 01/28/84 08:00 1.11 20 100 4 0 8. 0 0. 67 8. 4 00 01/28/84 12:00 11.3 18 t 0~) .:3 6 7. 2 0. 60 6. 0 0.0 01/28/84 16:00 1 f 5 15 100 3 0 6.0 0 5(} 3. 4 0.0 01/28/84 20:00 117 19 t (\() ~3. 8 7.6 0 6:3 7. 2 0.0 01/28/84 00:00 119 20 100 ·~ 0 8.0 0.67 8. 4 0. 0 DAILY AVERAGE VALUES J. 7 7.3 0 61 6 6 0. 0 i' • j PROPOSED TOGIAK HYORUELECTRIC PROJECT 05/10/85 PI->.GE 3 KURTLUK RIVER NEAR TUG I AK, ALASKA START TIME 01/19/84 04·00 DEPTH STAGE DISCHG TEMP DATE TIME BVTE RAW DATI:; t'l\v' INCHES FEET CFS DEG C .::=ra::::=:::::: ===== ::::::::·"'!;"':' =====~=-~:-::::::-: =::=~~ ======= -:;-::::::::;::::== ==~-:::-::::.::::::: ===:.:::::::.:= 01/29/84 04:00 i :21. 20 .tOO ~ 0 8. 0 0 67 8 4 0.0 01/29/84 o8·oo 1~3 18 100 J. 6 7. 2 0. 60 6 0 0.0 01/29/84 12:00 125 20 100 .... 0 8.0 067 B. 1t 0. 0 01129/84 16: 00 127 21 10() 4. 2 8. 4 0 71} 9 H 0. 0 01/29/84 20:00 129 18 il)0 3 6 7. 2 0. 6Cr 6 •I 0. 0 01./29/81+ 00: 00 131 18 1 0\) 1 6 7. 2 0. 6(• 6 0 0. 0 DAILY AVERAGE VALUES J 8 7. 7 0 64 7 I~ 0.0 01/30/84 04:00 133 19 100 J 8 7 6 0 c,J 7 ,-2 0.0 01/30/84 08:00 135 19 10n :l. 8 7. 6 0. 63 7 2 0 0 01/30/84 12:00 13:' 18 100 6 7. 2 0 60 6 0 0 0 01130/84 16: 00 1Ji::1 19 100 8 7 6 0.63 7. ;: 0.0 01/30/84 20:00 141 19 100 J 8 7. 6 0. 6:J 7. 2 0. 0 01/30/84 00:00 143 18 100 .J 6 7. 2 0 60 6. I) 0.0 DAILY AVERAGE VALUES ·~ 7 .C) • 7 5 0. 6:;: 6 1'-] 0. 0 01/31184 04: 00 1.4Cj 20 100 '1 0 8. 0 0 67 8 4 0 0 01/31/84 08:00 14.7 21 100 4 ,;; 8. 4 0 70 9 8 0.0 01131/84 12: 00 14':"' 20 1.00 4 0 8. 0 0. 67 8 4 0.0 01/31/84 16: 00 151 22 1. 00 1 4 8 8 0 73 11 0.0 01/31/84 20:00 1.53 2" "'-i 0(1 i) 4 8. 8 0 7.] i 1 0.0 01131184 00: 00 l5::i 22 100 4 4 8. 8 0 73 i 1 0.0 DAILY f.IVERAt~E VAUJES rl 2 8 5 0. 7!. 9 9 0.0 02/01184 04: 00 15l 21 100 1L 2 8. 4 0. 70 9. 8 0. 0 02/01/84 08:00 i t;Q 4 .... t 22 100 4 4 8. 8 0. 73 i1 0. 0 02/01/84 12:00 161 20 100 4 0 8. 0 0 67 8. I~ 0.0 02/01/84 16:00 163 21 100 lj, 2 8 4 0. 70 9 FJ 0. 0 02/01/84 20:00 1~J5 22 lOCi '·l 4 8 8 0 73 11 0. 0 02/01/84 00:00 167 21 tOO ,.;_ 2 8. 4 0. 70 9 H 0.0 DAILY AVERAGE VALUES Lt 2 8. 5 0. 7J. 10 0 0.0 02/02/84 04:00 l.b9 21 1.00 4 2 8. 4 0 70 9. 8 0.0 02/02/84 08:00 1 71 22 100 4 4 8. 8 0 7:3 t 1 0. 0 02/02/84 12:00 173 23 100 <l 6 9. 2 0. 77 13 0.0 02/02/84 16:00 175 24 t ()0 4. 8 9. 6 0. 80 15 0.0 02/02/84 20:00 171 25 lOO 5. 0 10. 0 0. 83 17 0.0 02/02/84 00:00 179 24 100 4. 8 9. 6 0. 80 15 00 DAILY AVERAGE VALUES 4 6 9. 3 0. 77 13 0.0 PROPOSED TOGIAK HYDROELECfRIC PROJECT 05·10/8'5 PAGE 4 KURTLUK RIVER NEAR TOGIAK, ALA':ii'~A START TIME 01/19/84 04•00 DEPTH STAGE DISCHG TEMP DATE TIME BY f[ RAW DATf• MV INCHES FEEf CFS DEG C ::::======"':": ==::==== =--=== :::===:::.=::::.::.:;:_· =!.:::-;:;·.~ ======;-:::; =.:==:: ====:::-:: :::=.==== 02/03/84 04:00 181 25 100 5. 0 10. 0 0. 83 17 0. 0 02/03/84 08:00 HJ3 25 100 :::'. 0 10.0 0 8~:! 17 00 02/03/84 12:00 t85 25 1 (10 5 0 10.0 0 83 i.7 0 0 02/03/84 1600 1.87 26 100 "' .... J ,:: 10. 4 0 8:" 19 0. 0 02/03/84 20:00 189 26 1()(> "' ., ~ "'· 10. 4 0. 8 7 19 0.0 02/03/84 00:00 191 25 H>O 5 0 10. 0 0. 8,] i7 00 DAILY AVERAGE VALUES 5. 1 10. 1 0. 84 18 0.0 02/04/84 04·00 193 24 100 4. 8 9.6 0 80 1.5 0. 0 02/04/84 08:00 19:-i 24 ton 4 8 9. 6 0 8(1 i~ 0 0 02/04/84 12:00 197 25 100 5 0 10.0 0. 8J l7 0. 0 02/04/84 16:00 199 24 100 1l. 8 9.6 0. 8<) 15 0. 0 02/04/84 20:00 201 24 100 4 8 9. 6 0.80 15 0. 0 02/04/84 00:00 203 23 100 4. 6 9. 2 0. 77 1-:l ,J 0.0 DAILY AVERAGE VALUES 4. B 9.6 0. 80 15 0.0 02/05/84 04:00 205 23 1.00 4 6 9. 2 0. 7-:" 13 0. 0 02/05/84 08:00 ~~07 24 100 4 8 9. 6 0. 80 15 0.0 02/05/84 12:00 209 24 100 4. 8 9.6 080 15 0 0 02/05/84 16:00 211 24 1 ijQ 4 8 9.6 0.80 1.5 0.0 02/05/84 20:00 21~3 25 100 5. 0 10. 0 0 8J 17 0.0 02/05/84 00:00 21 !;") 24 tOO 4 8 9. 6 0 80 15 0.0 DAILY AVERAGE VALUES 4. H 9. 6 0. 80 15 0.0 02/06/84 04:00 217 24 100 4 8 9. 6 0. 80 15 0. 0 02/06/84 08:00 21'7 24 100 4. 8 9. 6 0. 80 15 0. 0 02/06/84 12:00 2;21 24 !00 4 8 9.6 0. 80 1 ,. ".J 0 0 02/06/84 1.6:00 '1:;1') c..~ ... · ... f 24 100 4. 8 9.6 0 80 1 •:, 0. 0 02/06/84 20:00 2;25 24 100 ·l 8 9. 6 0. 80 iS 0.0 02/06/84 00:00 227 24 1.00 4. 8 9. 6 0.80 1:7 0.0 DAILY t>.VERAGE VALUES 4 8 9.6 0. 80 15 0. 0 02/07/84 04·00 229 23 100 4 6 9. 2 0 77 13 00 02/07/84 08:00 231 23 100 4 t,, 9. 2 0. 77 13 0.0 02/07/84 12:00 23'3 23 10() '"" 6 9. 2 0. 77 13 0.0 02/07/84 16:00 2:35 23 100 4 6 9. 2 0 77 13 0.0 02/07/84 20:00 2.37 23 100 4 6 9. 2 0 77 13 0. 0 02/07/84 00:00 23'1' 23 100 4. 6 9.2 0. 77 13 0.0 DAILY AVERAGE VALUES ~~ 6 9.2 0. 77 13 0.0 • l PROPOSED TOGIAK HYDROELECTRIC ~RGJECT 05.-10/8:5 Ft~GE 5 KURTLUK RIVER NEAR TUGIAK, ALAS!o<A START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYfE RAW DATt., !"1\/ INCHES FEET CFS DEG C ======::::= ===== ==:.::..:~ ::;;:::::;;:==:::.;.:::::;.::""' ==':":"= ====== :::=:::=:;:::::=4: ==:=::::::.::::: ====== 02/08/84 04:00 24l 24 100 4 8 9. 6 0 81.1 15 0.0 02/08/84 08:00 243 24 100 ~. 8 .9. 6 0. B•l 15 00 02/08/84 12.00 24:::· 24 100 4 8 9. 6 0 BtJ 15 0.0 02/08/84 16:00 247 24 1.00 4 8 9. 6 0. 80 15 0. 0 02/08/84 20:00 249 24 100 4. 8 9. 6 0. 8i) 1::5 0.0 02/08/84 00:00 251 24 100 4. 8 9. 6 0.80 i5 0.0 DAILY AVERAGE VALUES 4 8 9. 6 0.80 15 0 0 02/09/84 04:00 253 24 100 4 8 9. 6 0.80 15 00 02/09/84 08:00 255 24 lOO 4 8 9.6 0.80 15 0. 0 02/09/84 12:00 257 24 100 4 8 9.6 0 8!} 15 0 0 02/09/84 16:00 259 24 100 4 8 9. 6 0. 80 15 0. 0 02/09/84 20:00 261 24 100 4 8 9.6 0. 80 15 0.0 02/09/84 00:00 263 24 100 4.8 9. 6 0. 8fj i5 0. 0 DAILY AVERAGE VALUES 4 8 9.6 0.80 15 0. 0 02/10/84 04:00 2o5 24 100 :.j. 8 9. 6 0. B•j 15 0.0 02/10/84 08:00 2~)7 24 100 14.. 8 9. 6 0. Bi:• 15 0 0 02/10/84 12:00 269 25 100 s 0 10.0 0. 83 17 0 0 02/10/84 16:00 271. 25 100 ~i () 10.0 0.83 J. 7 0. 0 02/10/84 20:00 273 '.25 100 5. 0 10. 0 0 83 1 7 0.0 02/10/84 00:00 27':; 25 100 5 0 10. 0 0 E-:3 i7 0.0 DAILY AVERAGE VAl.UES 4 9 9. 9 0 8:,:: 16 0. 0 02/11i84 04:00 277 25 100 'j 0 10.0 0. 8:3 17 0. 0 02/11/94 08:00 27'<:t 25 lOG ~-0 10. 0 0. 8:3 17 0.0 02/11/84 12: 00 281. 26 100 '5. 2 10. 4 0 87 19 0. 0 02/11/84 16:00 28~~ 26 11)0 5 2 10. 4 0 87 l9 0 0 02/11/84 20:00 285 26 100 5 2 10. 4 0 87 19 0. 0 02/11/84 00:00 287 26 100 ~ 2 10. 4 0 87 t9 0. 0 DAILr AVERAGE VALUES 5 1 10.3 0 86 18 0.0 02/12/84 04:00 289 26 100 ~· -.. 10. 4 087 19 0.0 ~· ~ 02/12/84 08:00 291 26 1.01) r-; 2 10. 4 0 87 19 0.0 02/12/84 12:0() 2\?~1 26 too :') 2 10. 4 0. 87 19 0. 0 02/12/84 16:00 29"1 26 100 ~' 2 10. 4 0.87 19 0.0 02/12/84 20:00 297 26 100 ~ 2 10. 4 0. 8 7 19 0.0 02/12/84 00:00 299 26 100 5 ;( 10. 4 0. 87 19 0.0 DAILY AVERAGE VALUES ·= L"" 10. 4 0.87 19 0.0 ...) ~ PROPOSED TOGIAK HYDROELECTRIC PROJECT 05t10/8:3 PAGE 6 KURTLUK RIVER NEAR TOGIAK, ALASV..A START TIME 01/19/84 04·00 DEPTH STAGE DI ~:JCHG TEMP DATE TIME BYTE RAW DATA l"'V INCHES FEET CFS DEG C =======-::= =:::===::::: :..==~::::; -::::::::-:::::.:=::::::::-'::.~-~ ~----=:::===: --·---::::::::::::::-:-::::::=-: ====== 02/13/84 04:00 301 27 100 5 4 10. 8 0. 90 '" ;,;;.. c: 0 0 02/13/84 08:00 :)0,] 27 100 ";. 4 10. 8 0.90 22 0.0 02/13/84 12:00 305 27 100 5 4 10. 8 0. 90 22 0.0 02/13/84 16:00 3C>7 28 100 5 6 112 0. 9J 24 0.0 02/13/84 20:00 3()9 28 100 5 1-J 112 0 9J 2'+ 0. 0 02/13/84 00:00 311 29 10\' 9 8 116 0. 97 -. "r 1.:.. I 0 0 DAILV AVERAGE VALUES :=;. 5 11. 1 0. 9'~ 24 0 0 02/14/84 04:00 313 :30 100 :-:) 0 12. 0 1 00 30 0.0 02/14/84 08:00 315 31. 100 ''J ::;! 12. 4 i. 0 "! ~]4 0.0 02/14/84 12:00 317 31 100 ' ·::> • ... } ..... 12. 4 t OJ 34 0.0 02/14/84 16:00 31<;' :]3 100 ':_1 6 13. 2 t 1<) 41 0. 0 02/14/84 20:00 321 33 100 •':, 6 13.2 1. 1 t) 41 0. 0 02/14/84 00:00 3;2? :33 100 ~;; 6 13. 2 1.. 1 \) 41 0 0 DAILY AVERAGE VALUES ,;_, 4 12. 7 106 ]7 0 0 02/15/84 04:00 32::· 33 tOO .£_, 6 13. 2 1. 1 •) 41 0 0 02/15/84 08:00 3~~7 33 tOO 1, 6 13 2 1 10 41 0. 0 02/15/84 12:00 32° 33 100 ); 6 13. 2 1. 10 41 0. 0 02/15/8l.J 16: 00 3:.:11 32 l.di) ,.._, 4 12.8 1. 07 37 0.0 02/15/84 20:00 3'33 32 101) o. 4 12. 8 1 1)7 37 0.0 02/1~/84 00:00 33:? 32 lOCI ,t, 4 12 8 1 07 . ..,..., 0 0 \,..::)'' DAILY AVERAGE VALUES 6 5 13. 0 1 09 Jt;' 0. 0 02/16/84 04:00 337' 31 1.00 (~ 2 12 4 1. (}'] 34 0.0 02/16/84 08:00 33S' 3i 1 (}('! b. 2 12. 4 1 03 34 0. 0 02/16/84 12:00 341 32 J. ~)') ·'-' 4 12.8 1. 07 , .... \-r 0.0 I I 02/16/84 16:00 34:.3 32 1. ()/\ r.J 4 12.8 1. 07 J7 0.0 02/16/84 20.00 3!\-5 3;2 tOO f.:.r 4 12 8 1. 07 37 0. 0 02/16/84 00:00 347 33 1 oc ~> 6 13. 2 1 1. () il'i 0.0 DAILY AVERAGE VALUES 6 4 12. 7 1 06 •• y 0 0 . ..:;, / 02/17/84 04:00 349 3:1 100 t.·. 6 13.2 1. 10 4 1 0.0 02/17/84 08:00 351. 33 100 1,; 6 13. 2 1 10 41 0. 0 02/17/84 12:00 353 33 100 h. f.J 13. 2 1 1. I) 41. 0.0 02/17/84 16:00 355 33 1 !!C• 6 ,.., 13. 2 1. j 0 41 0. 0 02/17/84 20'00 357 33 100 6 6 13. 2 1. 10 41 0.0 02/17/84 00:00 ~]59 32 100 6. 4 12. 8 1 07 37 0. 0 DAILY AVERAGE VALUES tJ 6 13. 1 1. 11} 40 0. 0 ,, PROPOSED TOGIAK HY[lRiJELECTRI,: PRO,}ECT 0.} '10/85 PAGE 7 KURTLUK RIVER NEAR T•IGIAK, ALASV.A START TIME 01/l9/84 0400 DEPTH STAGE DISCI-J(i TEMP DATE TIME BY fF. RAl.J OAT A MV INCHES FEE' CF'"S DEG C =::::====-== ===== ::=:::-=.~~ ====:.!::·:=::::-:.::..-=··.:::-:= ====== ==~=...::;;:. ::::;:;::::::;::::.:::;: ===== 02/18/84 04:00 3tJ 1 '12 tOO ~~ 4 12. 8 t. o:' 37 0.0 02/18/84 08:00 36:-:.; 31 100 c.> 2 12. 4 l. OJ 34 0.0 02/18/84 12:00 3/,5 31 l.OO c) 2 12. 4 1 OJ 34 0 0 02/18/84 16:00 ]1,7 30 100 0 12. 0 l 0\i lO 0.0 02/18/84 20:00 3bC:' 30 l.•}O b 0 12.0 J. 0•) ]0 0. 0 02/18/84 00:00 37i 30 }. ~~1(} ~· 0 12.0 i 0<.') JC• 0. 0 DAILY AVERAGE VALUES ·S i 12. 3 t. 0 ~ 13 0 0 02/19/84 04:00 3'73 29 100 5 8 11. 6 0. 9: 27 0.0 02/19/84 08:00 J"')JC., ·..;i I •. 29 100 ''5 8 11. 6 0. 97 27 0 0 02/19/84 12:00 377 29 lOO "" 8 11. 6 () 9 27 0 0 02/19/84 16:00 3'7';' 28 tOO ': 6 11 2 0 9J '"'Jtl ,_ ' 0 0 02/19/84 20:00 381 28 100 15 6 11.2 0. 91 24 0.0 02/19/84 00:00 3;:]3 28 100 ;s 6 11.2 0 9 24 00 DAILY AVERAGE ~Al.UES 7 11. 4 0 9:3 2.b 0 0 02/20/84 04:00 38'') ').., e..r 1, (11) 'S 4 10. 8 0 9(1 ., ... , -:...~ 0.0 02/20/84 08:00 3U7 ~:7 l (l!) 4 10 8 0 90 '22 0. 0 02/20/84 12:00 3t~<:;:· 28 !.0\) ": 6 1.1. 2 0 9~3 :24 0.0 02/20/84 16:00 3'l ''0 ~ .. 100 8 j 1. 6 0 97 .27 0. 0 02/20/84 20:00 ......... -.~"'\ 28 1.00 ~ <!:I 11 2 0 9J 24 0. 0 . .::., •• , ,;> 02/20/84 00:00 3~?;,} 28 ~.l)i) :';. ~J 11 2 0. ~3 24 0 0 DAILY ~VERAGE VALUES 5 6 11 1 0 93 ,24 0. 0 02/21/84 04:00 397 28 iOO 5 6 11. 2 0 9J 24 0 0 02/21/84 08:00 399 29 1. (),_) 5 8 11. 6 0 97 27 0 0 02/21/84 12:00 401 30 i oo b 0 12.0 1 00 JO 0 0 02/21/84 16:00 40:3 31 100 6 2 12. 4 1 03 .34 0 0 02/21/84 20:00 40:'1 33 1 ()() i~. b 13.2 1 10 ·ll 0. 0 02/21/84 00:00 407 33 1 <X.· ~;1, 6 13. 2 1 1.0 '11 0.0 DAILY AVERAGE VALUES ;::: i 12.3 1. 02 .33 0 0 02/22/84 04:00 40l7' 34 100 ~' 8 13.6 1. iJ 45 0.0 02/22/84 0800 411 35 100 7 I) 14.0 1. 17 49 0.0 02/22/84 12:00 413 37 1.00 7 4 14. 8 1 23 59 0 0 02/22/84 16:00 415 39 1 (){ _) 7 8 15. 6 1 3•') 70 0. 0 02/22/84 20:00 417 40 100 t:l 0 16.0 i 3J 75 0. 0 02/22/84 00:00 419 40 1 ,)0 8. 0 16 0 1. 33 75 0.0 DAILY AVERAGE VAUJES 7 5 1'5. 0 1.. 25 62 0.0 PROPOSED TOGIAK HYDfhJELECTH I·--PRiJ"IECT OS' i0/8:3 fAGE 8 KIJRTLUv; RIVER NEAR TOGIAK, ALAUII'.A STARf TIME 01/19/84 04·00 DEPTH STAGE DISCHG TEMP DATE TIME BVfE RAW DATA l'1l~f INCHES FEET CFS DEG C =====-===~= ===== -:.::;r. ::.:::::-::::-::·:=.:..7:; -"'•-"----·-----·--n =::::::=·-::::::::-:·:-::::: ----·-__ ,....,.. ___ ------ 02/23/84 04:00 421 41 1.00 8 2 16. 4 1. 3 7 81 0 0 02/23/84 08:00 4~.?:3 4i lOG 8 2 16. 4 1. 37 81 0 0 02/23/84 12:00 4.25 41 100 13 2 16. 4 1 3? 81 0. 0 02/23/84 16:00 4~U 42 lOO 8 4 16. 8 1 4<) 09 0 0 02/23/84 20:00 4 '){."\ ;~. ' 42 100 8 4 16. 8 1 40 88 0. 0 02/23/84 00:00 4c') i 41 f)(l ''1 16. 4 1. :37 131 0. 0 J J c. DAILY AVERAGE 'iALUES e :J 16. 5 1. 3~3 KJ 0.0 02/24/84 04:00 433 40 100 8 0 16.0 1 -·., ..J.;J 75 00 02/24/84 08:00 435 39 100 7 8 15.6 1 30 7() 0.0 02/24/84 12:00 4 :·7 •-'· 38 1 ']{) , 6 15. 2 1. 2 7 .<;,4 0.0 02/24/84 16:00 4:3.:? 37 100 ., 4 14.8 1 23 59 0 0 02/24/84 20:00 441 36 1. 00 ~· 2 144 1 20 54 0. 0 02/24/84 00:00 443 35 100 7 0 14.0 1. 17 4·q 0.0 DAILY AVERAGE VALUES 7 5 15.0 1. 25 6.=~ 0 0 02/25/84 04:00 445 35 1 0•) 7. 0 14. 0 1 i7 49 0. 0 02/25/84 08:00 44/ 34 100 6 8 13.6 1.13 45 0. 0 02/25/84 12:00 449 33 100 6. 6 13.2 l 1<1 41 0. 0 02/25/84 16:00 451. 32 J.<JO 6 4 12.8 1. 0 7 37 0.0 02/25/84 20:00 45:3 :Ji 1 ()() 6 2 12. 4 1 OJ ]4 0. 0 02/25/8"1 00:00 455 30 100 6 () 12.0 1 o,·t1 30 0. 0 DAILY AVERAGE VAI.i.ff.:C') (;; 5 130 1 0'·} ]9 0 0 02/26/84 04:00 457 30 100 tJ 0 12.0 1 00 :JO 0.0 02/26/84 08:00 459 30 l.OO h 0 12.0 1 00 30 0 0 02/26/84 12:00 461 30 iOO 6 0 12. 0 1 00 :30 0. 0 02/26/84 16:00 463 29 l '10 5 8 11. 6 0 9 ."27 0 0 02/26/84 20:00 L165 29 j(JO 5 8 11. 6 0. 9.7 27 0 0 02/26/84 00:00 4l,"l 28 1 (F) ~ ~~ 11 2 0. 9'::: 24 0 0 DAILV AVERAGE '..'t.,L.UES 5 9 11. 7 0 9i:l ~8 0. 0 02/27/84 04:00 469 27 1.0<) 5. 4 10.8 0. 9(; 22 0. 0 02/27/84 o8·oo 4/i 27 iOO 5 4 10. 8 0. 9(1 ·")<") 0. 0 "'"' 02/27/84 12:00 4 . .,. .. , I ·~1 27 1 ()0 3 4 10.8 0. 9() 22 0.0 02/27/84 16:00 4"7t" .. ,, 26 100 5. :~ 10.4 0. 8 19 0 0 02/27/84 20:00 4 , .• • I 25 iOO 5 0 10.0 0. 83 i7 0. 0 02/27/84 00:00 479 24 100 4. 8 9.6 0. 80 15 0. 0 DAILY AVERAGE V~-UES 5. 2 10. 4 0. 87 20 0. 0 PROPOSED TOGIAK HYDR0ELECTR[C ~RDJECT 05.·10/85 PAGE 9 KURTLUK RIVER NEAR TOGIAK, AU~SIAA START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYrt-: RAl"' DP.fA MV INCHES FEEf CFS DEG C =====:::c:::::::: ===== :::::-:;·:..:::. ==~"'.::===~=::::;::."".:::::;; ==~== ====== =====·= ==~=== "!:::::::::=== 02/28/84 04:00 48l 24 100 4. 8 9. 6 080 15 0.0 02/28/84 08:00 4B3 24 100 4. 8 9. 6 0 80 15 0.0 02/28/84 12:00 4f35 24 lOO 4 8 9.6 0. 80 l.5 0.0 02/28/84 16·00 4~F 23 1.00 4. 6 9 2 0 77 i ... ,J 0.0 02/28/84 20:00 4B9 23 ).()() 4. 6 9. 2 0. 77 1] 0.0 02/28/811-00:00 4"i1. 23 100 4 6 9. 2 0. 7 7 1-:! '-' 0. 0 DAILY AVERAGE VALUES !f 7 9. 4 0 79 14 0.0 02/29/84 04:00 !l-93 23 1.00 :+ 6 9.2 0 7 7 13 0.0 02/29/84 08:00 495 22 100 4 4 8. 8 0. 7:J 11 0. 0 02/29/84 12:00 497 22 100 4 4 8 8 0. 7J i 1 0.0 02/29/84 16:00 499 22 100 4 4 8.8 0 7'3 11 0 0 02/29/84 20:00 501 21 100 4 ~, c.. 8. 4 0. 7\j 9 8 0.0 02/29/84 00:00 503 21 100 4 2 8. 4 0. 7•.) 9. 8 0.0 DAILY AVERAGE VALUES ·-+ 4 8. 7 0 73 i1 0.0 03/01/84 04:00 505 2i 100 4 8. 4 0. 70 9. 8 0.0 03/01184 08: 00 507 21 100 4. 2 8 4 0. 70 9. 8 0.0 03/01/84 12:00 509 21 l.OO 4 2 8. 4 0 70 9. 8 0.0 03/01/84 16:00 511 20 100 4. 0 8.0 0. 67 8. 4 0 0 03/01/84 20:00 513 20 1. 01) 4. cl 8. 0 0 67 8 4 0. 0 03/01/84 00:00 :=n '} 20 1.00 '+ ~..\ 8.0 0 67 8. 4 0. 0 DAILY AVERAGE VALUES 'l 1 8.2 0 69 9. 1 0.0 03/02/84 04:00 517 20 tOO 4 \.) 8.0 0 67 8 4 0.0 03/02/84 08:00 519 20 1.00 4 0 8.0 0. 67 8. 4 0.0 03/02/84 12:00 5::-"!I i9 100 2 8 7 6 0 b'J 7. 2 0.0 03/02/84 16:00 523 19 tOO .1. 8 7. 6 0 6:] 7 0. 0 03/02/84 20:00 52:. 1"2.0 10() -~ 0 8.0 0. 6 7 8 4 0.0 03/02/84 00:00 527 19 1.00 J 8 76 0 6:] 7. 2 0.0 DAILY AVERAGE VALUES J. 9 7. 8 0 65 7. 8 0.0 03/03/84 04:00 529 19 100 .:: 8 7. 6 0. 63 7 2 0.0 03/03/84 08:00 5-:..11 19 1.00 ~. 8 7.6 0. 6] 7 2 0 0 03/03/84 12:00 5]3 19 100 8 7. 6 0 6~3 7 2 0.0 03/03/8 1-t 16: 00 535 19 100 3 D 7. 6 0. 63 7 2 0.0 03/03/84 20:00 53'7 19 100 J. 8 7.6 0 6:3 7 2 0.0 03/03/84 00:00 5.:19 19 100 1 8 7. 6 0 63 7 . .., . <:.. 0.0 DAILY AVERAGE VALUES 8 7. 6 063 7 2 0.0 PROPOSED TOGIAK H''!'DRlJELECTR IC ''fO,..fECT 0'3tiQ/85 PAGE 10 KURTLUK RIVER NEAR 10GIAK, ALAEWA SlART TIME 01/19/84 04·00 DEPTf...l STAG(. DIBCHG TEMP DATE TIME Oi'TE RAW Di'> fl• 11 1./ INCHES FEEr CFS DEG C ===::=:===~= =:::::::::::::::::: ~::;;"::-;:.:; .:::::=:.:::::::=~ .. ~· ... ; ,::::; ::::::::::::=== '::===:=: ====== ===== 03/04/84 04:00 541 19 100 :18 7 6 0. 6:3 7 ,, "-0.0 03/04/84 08:00 542 19 iO•) '1. 8 7. 6 0. 63 7 ;;:> 0 0 03/04/84 12:00 545 19 100 ·.:; 8 7. 6 0 b] 7. ;;: 00 03/04/84 16:00 '547 19 tOO .3. 8 7. 6 0 b? .., .-, I ,."! 0. 0 03/04/84 20:00 549 19 t ~'Jt: J 8 7. 6 0 6] 7 2 0. 0 03/04/84 00:00 551 19 100 J. 8 7. 6 0 6~3 7. 2 0. 0 DAILY AVERAGE VALUES 3. 8 7.6 0 6J 7 ·;) DO 03/05/84 04:00 55] 19 100 J. f3 7 6 0 6] 7. 2 0. 0 03/05/84 08:00 555 19 tOO J. 8 7. 6 0 6'3 7 .-, '"' 0.0 03/05/84 12:00 557 20 tOO 'L 0 8. 0 0 67 8 4 0 0 03/05/84 16:00 5:-q :J, 27 1.00 5. 4 10.8 0. 9() 22 0.0 03/0!'1/84 20:00 561 25 100 '?. 0 10.0 0 83 17 0. 0 03/05/84 00:00 56] 26 iOO 5. 2 10. 4 0 87 i ~~ 0.0 DAILY AVERAGE VALUES .,~; 5 9 1 0 7-'.: 13 00 03/06/84 04:00 56'3 25 !.00 ~3 0 10. 0 0 8J 17 0. 0 03/06/84 08:00 56/ 22 1 01} 4 4 8. 8 0 7:] 11 0 0 03/06/84 12:00 56-9 23 lOO 4 6 9. 2 0. T7 1:3 0. 0 03/06/84 16:00 571 24 100 ·'t. 8 9. 6 0. 80 15 0. 0 03/06/84 20:00 5T3 19 tOO J 8 7.6 0. 63 7 2 0. 0 03/06/84 00:00 575 25 100 ~5 0 10. 0 0 83 17 0. 0 DAlLY AVERAGE VALUES 4 b 9.2 0 77 13 0. 0 03/07/84 04:00 577 22 1.•JO 4 4 8.8 0 l"i it 0. 0 03/07/84 08:00 579 19 1 ':>':) .1 8 7. 6 0. 6] 7. 2 0. 0 03/07/84 12:00 581 26 1 o,·, 5 2 10. 4 0. 8' 19 0. 0 03/07/84 16:00 583 28 1 (\() 5 6 11. 2 0. 93 ?4 0. 0 03/07/84 20:00 585 23 t t~O /.l. ic 9. 2 0 77 t:J 0. 0 03/07/84 00:00 587 2'' "'-j_ !)(! 4. 4 8 8 0 7] 1.1 0.0 DAIL '( AVERAGE VA~ .. UES d 7 9.3 0 78 14 0 0 03/08/84 04:00 589 2.3 101) 4. b 9.2 0 77 1:3 0 0 03/08/84 08:00 591 20 1 t)(; 4. (_) 8. 0 0. 67 8 4 0. 0 03/08/1]4 12:00 593 22 100 4 if 8.8 0 7] 1 1 0.0 03/08/84 16:00 51:;15 19 toe :J. 8 7. 6 0 63 7 ;::> 0 0 03/08/84 20:00 597 18 100 J. b 7.2 0 60 6 0 0. 0 03/08/84 00.00 599 24 100 4. 8 9. 6 0 80 15 0.0 DAILY AVERAGE VALUES 4 2 8. 4 0. 70 10 0. 0 PROPOS£0 TOGIAK HYDP~ELECTRIC ~ijQJECT 03/10185 Pi->GE 1 i KURTLU~ RIVER NEAR TOGIAK. ~\LA!;,v A STARf fiME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW DAr;" r"!V INCHES FEEf CFS DEG C ======"'='= ===== ~=-:-== ~===:=::::::'"':":'"~ =::·.-=·~ =====:-~• ::::~===;:.:: :::::::::::~:-== ==::=== 03/09/84 04:00 1.:.01 20 1 ~:,,J 4 0 8. 0 0 6 8. 4 0.0 03/09/84 08:00 1:.03 21 100 4 ;.?.. 8. 4 0. 70 9. l3 0.0 03/09/84 12:00 605 22 1()(! 4. •i 8.8 0. 7~J 11 0. 0 03/09/84 16:00 607 2J lOt\ 4 ~ 9. 2 0. 7 7 13 00 03/09/84 20:00 609 24 iOU 4. i3 9.6 0 8') 15 0.0 03/09/84 00:00 b11 24 1 ()!\ 4 8 9.6 0 8(• 15 0.0 DAILY AVERAGE VALUES 4. 5 8.9 0 7"": 12 0 0 03/10/84 04:00 613 23 1 (\0 ij. 6 9. 2 0. 77 13 0. 0 03/10/84 08 00 615 24 100 '·L 8 9. 6 0. BrJ 15 0. 0 03/10/84 12:00 617 23 1. ()\) 4. ~ 9. 2 0 7' 13 0.0 03/10/84 16:00 619 24 100 4·. i2 9. 6 0 8•) 15 0 0 03/10/84 20:00 621 20 100 4 0 8.0 () 6 ."' 8. 4 0.0 03/10/84 00:00 623 23 100 4 6 9.2 0. 71 13 0. 0 DAILY AVERAGE VALUES 4. 6 9. 1 G. 7-'c 13 0 0 03/11/84 04:00 625 26 100 5 ;.~ 10. 4 0 8 7 19 0.0 03/11/84 08:00 627 22 I.(}!} ~ 4 8. 8 0 7'1 1 1 0.0 03/11/84 12:00 629 21 !t)O 4. 2 8. 4 0. 7u 9, 8 0 0 03/11/84 1600 631 28 j t'l() 5 6 112 0 93 24 0. 0 03/11/84 20: 00 63~:' 25 iO,) r::. () 10.0 0. g-j 17 0.0 03/11/84 00: 00 635 24 100 4. 8 9. 6 0. 80 15 0.0 DAILY AVERAGE VALUES 4. •;• 9. 7 (j 8i 16 0.0 03/12/84 04:00 637 23 100 4.6 9.2 0 7 .:' 13 0.0 03/12/84 08.00 6':19 22 10\J 4. 4 8.8 0. 7:3 11. 0. 0 03/12/84 12:00 641 23 100 4·, 6 9.2 0 77 13 0.0 03/12/84 16:00 643 25 100 5. 0 10. 0 0. 83 1 7 0.0 03/12/84 2000 645 25 100 !7 ,, 10.0 0. 83 17 0.0 03/12/84 00:00 647 22 1 (}() 4 4 8.8 0 7.J 11 0 0 DAILY AVERAGE VALUES 4. l 9.3 0 78 i4 0. 0 03/13/84 04:00 649 19 1 •:>O 3. 8 7.6 0. 63 7. 2 0.0 03/13/84 os·oo 651 18 100 i 6 7.2 0. 60 6 0 0.0 03/13/84 12:00 653 18 1, Cr(} l ,"..J 7. 2 0. 6;) 6. 0 0.0 03/13/84 16:00 655 20 1t){) t.f •J 8. 0 0 6':" 8. 4 0.0 03/13/84 20:00 657 20 10t) 4 0 8. 0 0 6i 8. 4 0.0 03/13/84 00:00 659 18 lOO 3.6 7. 2 0. 6•) 6. 0 0. 0 DAILY AVERAGE VALUES 3 8 7. 5 0 6J 7. 0 0. 0 PROPOSED TOGIAK HYDRUELECTRI( PROJECT O'ii 10185 PAGE 12 KURTLU~ RIVER NEAR TOGIA~. ALAS"-. A STARf TIME 01/19/84 04·00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE:: RAW DAfA t1\.' INCHES FEEl" CFS DEG C ======== ====== ==::.::·::...-: ===.:::::::;:·_-;.,-:-:-::::..-_ :::-·.-:-:::::: ====== :::::-=.::::::= :::::===:.:=::::: -------··--- 03/14/84 04:00 661 19 1.00 3 8 7. 6 0. 6:3 7 • . G. 0. 0 03/14/84 08:00 66:3 18 tOO 3. fC) 7. 2 0. 60 6.0 0 0 03/14/84 12:00 bb5 18 1.00 .. ~ 1::, 7. 2 0 60 6. 0 0 0 03/14/84 16:00 6tC. .... 17 100 •J 4 6.8 0 5? 5. 0 0.0 03/14/84 20:00 669 17 1.00 ] 4 6.8 0 57 5. () 0 0 03/14/84 00:00 6"7< 'l 18 l.OO -; 6 7. 2 0. 6,.} 6 0 0 0 DAILY AVERAGE VALUES .l 6 7. 1 0. 6(~, 5. 9 0 0 03/15/84 04:00 673 18 100 :; 6 7 2 060 6.0 0. 0 03/15/84 08:00 67~ 16 1.00 .~: 2 6. 4 0 5'1 4 .-, . c.. 0 0 03/15/84 12:00 6.!7 17 1.00 ::: 4 6. 8 0 57 5 0 00 03/15/84 16:00 679 1.7 100 ·::: 4 6. 8 0 57 5 0 0.0 03/15/84 20:00 681. 18 100 J. 6 7. 2 0. tJO 6. 0 0. 0 03/15/84 00:00 683 16 1.00 j 2 6. 4 0. S3 4. 2 0.0 DAILY AVERAGE VALUES J. 4 6. 8 0 57 5 1 0. 0 03/16/84 04:00 6f~'5 19 100 -, 8 7. 6 0 6] 7 2 0 0 03/16/84 08:00 6f;7 20 1.00 "1 0 8. 0 0 6:: 8. 4 0.0 03/16/84 12:00 68l? 20 100 4 u 8. 0 0. 6 7 8 4 0. 0 03/16/84 16:00 691 20 1.00 .'~. 0 8 0 0. 67 8. 4 0.0 03/16/84 20:00 6'n 21 1.00 J ,..., <=. 8. 4 0 /1) 9. 8 0. 0 03/16/84 00:00 6'~~ 24 1.0(} 4 8 9. 6 0 80 15 0. 0 DAILY AVERAGE V~.UES "-. 1 8 3 0. 69 9. 5 0.0 03/17/84 04:00 6'17 26 100 ~j :-2 10. 4 0. 8? 19 0. 0 03/17/84 08:00 699 24 100 a.. 8 9. 6 0 80 15 0.0 03/17/84 12:00 701 25 iOO :=;. 0 10. 0 0 83 1 7 0. 0 03/17/84 16:00 703 28 tOO ~s 6 11. 2 0 !7•1 :24 0. 0 03/17/84 20:00 705 27 1.tJO 5 4 10. 8 0 90 , . ., 0.0 ;:: . .:--_ 03/17/84 00:00 7()7 25 100 5 l) 10. 0 0 8"3 i:-' 0.0 DAILY AVERAGE VALUES '] ;;-: 10. 3 0 86 19 0. 0 03/18/84 04:00 709 26 100 5. 2 10. 4 0 8? .t9 0. 0 03/18/84 08:00 7 i 1 26 1.00 =~ . ..., '-' .:::. 10. 4 0 87 19 0. 0 03/18/84 12:00 7L3 26 100 '5 "2 10. 4 0 87 19 0. 0 03/18/84 16:00 71.5 ~27 100 5 4 10. 8 0. 9() 22 0 0 03/18/84 20:00 717 27 100 5 4 10. 8 0. 90 . ..,.., c..:::.. 0.0 03/18/84 00:00 71Q 26 100 ::\. 2 10. 4 087 i9 0.0 DAILY 4VERAGE VALUES 5 3 10. 5 0 88 20 0. 0 • I PROPOSED TOGIAK HYDRUFLEC TR I L PPQ,JECT 05.·10/8j PAGE 13 KURTLUK RIVER NEt,R TiJG·rAK, ALAS!' A START TIME 01/19/84 04 00 DEPTH STAGE DIGCHG TEMP DATE TIME BYIF RAW DAT,I> 1'1\) INCHES FEET CFS DEG C ======== ===== =:;:_::~. =::.::=== !'::=::::.:~7:'"' =:-:::.:.::.~-::: ====== ===== .:::;;:;:=:::::-;::;;:=:: ===== 03/19/84 04:00 721 24 1.00 4. 8 9.6 0. 80 15 0. 0 03/19/84 08.00 ..... -}-.. I "'-:J 24 1.00 .~ 8 9. 6 0. 80 15 0. 0 03/19/84 12:00 """"'" I~'"' 24 101 -+. 8 9. 6 0 80 1 'i 0. 5 03/19/84 16:00 72.7 24 101 4. 8 9. 6 0. 80 15 0 5 03/19/84 20:00 72~ 24 !01 4. 8 9. 6 0 8() 15 0. 5 03/19/84 00:00 rn 24 ' r., ! ~ • 4 8 9.6 0. 80 15 0. 5 DALLY AVERAGE VALUES 4. 8 9.6 0.80 15 0. 3 03/20/84 04:00 73~3 23 101 4. 6 9.2 0. 77 :1.:3 0. 5 03/20/84 08:00 7':~5 23 101 4 6 9.2 0 7 1 1:3 0 5 03/20/84 12:00 TF 23 11)2 4. h 9. 2 {j Tc 13 1.0 03/20/84 16:00 7~39 24 102 ·4-8 9. 6 0 8(• 15 1.0 03/20/84 20:00 74t 24 101 4 8 9. 6 0. 80 1'5 0 5 03/20/84 00:00 743 24 101 4. 8 9.6 0.80 iS 0. 5 DAILY AVERAGE VALUES 4 7 9. 4 0 79 14 0. 7 03/21/84 04:00 74~" 23 101 4. 6 9. 2 0 77 13 0. 5 03/21/84 08:00 747 23 1.01. 'f. 6 9. 2 0 77 t:3 0. 5 03/21/84 12:00 749 23 1,1)4 4 0 9.2 0 77 13 2.0 03/21/84 16:00 751 24 t03 4. 8 9.6 0. 80 15 1 5 03/21/84 20:00 75.] 24 102 -+ 8 9.6 0 80 15 l. 0 03/2li84 00: 00 755 23 1.01. '-!-6 9. 2 0 ]'7 13 0. 5 DAILY AVERAGE ~ALUES 4. 7 9. 3 0 78 14 1.0 03/22/84 04:00 757 23 1()1 4. 6 9. 2 0 J:l 13 0 5 03/22184 08:00 759 23 10~ 4 6 9.2 0. 77 13 1.0 03/22/84 12:00 761 23 104 4. 6 9.2 0. T7 13 2. 0 03/22/84 16·00 UJ3 23 1 0~? 4. 6 9 2 0. 7 7 13 2. 5 03/22/84 20:00 765 24 103 ·'+. 8 9. 6 0. 8!) 15 1.5 03/22/84 00:00 767 23 102 4. 6 9. 2 0. 71 13 1 0 DAILY AVERAGE VALUES 4 t> 9.3 0. 7•J 13 1 4 03/23/84 04:00 769 23 102 4. 6 9. 2 0. T? 13 1.0 03/23/84 08:00 7'7 1 22 t02 !.j. 4 8. 8 0 7] 11 1.0 03/23/84 12:00 77 J . -' 23 105 '4 6 9.2 0. 7 7 13 2. 5 03/23/84 16:00 7?5 24 1.06 4 8 9. 6 0. 80 i5 3.0 03/23/84 20:00 777 24 102 4. 8 9. 6 0.80 15 1.0 03/23/84 00:00 779 23 100 ·~ 6 9. 2 0. Tl 13 0. 0 DAlLY AVERAGE VALUES 4 6 9. 3 0. 77 13 1. 4 PROPOSED TOGIAK HYDROELECTRIC PROJECT 0~110/85 FAGE 14 KURTLUK RIVER NEAR TOGIAK. ALAC]FA START TIME 01/iQ/84 04.00 DEPTH STAGE DISCHG TEMP DATE TIME BYTF.: RAW DAT'A M\..' INCHES FEET c~-s DEG C =====.=::::::::::::::.= ~==== :· !':'!::':!'!:::::" ===-====~::::··.; =:::.:::::':;! ====== ~~==~ :~====.:=: ===== 03/24/84 04:00 7•31 23 i.Ot) 4 6 9.2 0. 77 13 0. 0 03/24/84 08:00 783 23 100 4. 6 9.2 0. 7' 13 0. 0 03/24/84 12:00 785 22 tO] 'i-. 4 8. 8 0. T3 11 1 5 03/24/84 16:00 787 22 108 -1-4 8. 8 0. 7.3 11 15 03/24/84 20:00 789 22 lOt :j. 4 8.8 0. 73 i1 0. 5 03/24/84 00:00 7•7:!. 22 101 4 :'j. 8.8 0. TJ 11 0. 5 DAILY AVERAGE VALUES 4 5 8. 9 0 74 12 0. 7 03/25/84 04:00 793 22 10t 4. 4 8. 8 0. 7J 11 0. 5 03/25/84 08:00 7•::i5 22 1 Ot 4. 4 8.8 0 7] 11. 0 5 03/25/84 12·00 7S'7 22 10:3 .::). 4 8.8 !) li 11 1.5 03/25/84 16:00 79S' 22 102 4. 4 8. 8 0 7'3 1 i 1.0 03/25/84 20:00 801 22 101 a 4 8. 8 0 7:3 i 1 0. 5 03/25/84 00:00 803 22 1.01 4. 4 8.8 0 7J 11 0. 5 DAILY AVERAGE VALUES 4. 4 8.8 0. lJ 11 0.8 03/26/84 04:00 805 22 100 4. 4 8. 8 0 TJ i 1 0.0 03/26/84 08:00 807 22 100 l 4 8. 8 0 7~3 11 0.0 03/26/84 12:00 809 22 1.03 4 4 B. 8 0 73 11 1.5 03/26/84 16:00 811. 22 1.03 .a. 4 8.8 0. 73 11 1. 5 03/26/84 20:00 813 22 102 lj. 4 8. 8 0. 73 11 1.0 03/26/84 00:00 81<) 22 101 4· 4 8.8 0. 73 11 0. 5 DAILY AVERAGE 1/D,LUES 4. 4 8 8 0 73 11 08 03/27/84 04:00 817 22 101 4. 4 8. 8 0 73 11 0. s 03/27/84 08:00 819 22 102 ii· 4 8. 8 0 T3 1i 1. 0 03/21/84 12:00 821 22 tOb 4. 4 8 8 0 73 11 3. 0 03/27/84 16:00 8:=23 22 106 J. 4 8. 8 0 Ti 11 3. 0 03/27/84 20·00 8~5 23 104 4 6 9. 2 0 77 13 2.0 03/27/84 00:00 8 ......... C..i 23 102 [;. 6 9. 2 0 77 i3 1.0 DAILY AVERAGE VALUES 4 5 8.9 0 74 i2 1 8 03/28/84 04:00 829 22 102 >'t. 4 8.8 0 71 11. 1.0 03/28/84 08:00 8:31 ·'")"! c:..;::. 102 .q. 4 8.8 0. Tl 11 10 03/28/84 12:00 8'33 22 1.06 4. 4 8.8 0. 7J 11 3.0 03/28/84 16:00 8:15 23 106 4. 6 9.2 0. 7 7 1'" ·..! 3. 0 03/28/84 20:00 837 24 103 4. 8 9. 6 0.80 15 1. 5 03/28/84 00:00 839 23 101 4. 6 9.2 0. 77 13 0. 5 DAILY AVERAGE VALUES 4. 5 9. 1 0. 76 12 1.7 ' • PROPOSED TOGIAK HYDROELECTRIC PROJECT 0;•10!85 PAGE 15 KURTLUK RlVER NEAR TOGIAK, ALASY.A START TIME 01/19/84 04.00 DEPTH STAGE DISCHG TEMP DATE TIME ih' n;_ RAW OAf A M'.i INCHES t=EEi CFS DEG C d======= ===== :::::.;:;::..::.::t ::::::.::====::::::=: = ::;=::.:~ =====: -::::::::::::::;: ===:=::::::=;:; ----------- 03/29/84 04:00 841 23 101 4 6 9. 2 0 7 i-13 0. 5 03/29/84 08:00 843 23 101 4, 6 9. 2 0. 77 13 0. 5 03/29/84 12:00 845 23 1. OA 't. 6 9. 2 () 77 13 3 0 03/29/84 16:00 847 24 10~.· 4 8 9. 6 0. B•j 15 3. 0 03/29/84 20:00 849 26 10?-5. 2 10.4 0. 8 1.9 1.5 03/29/84 00:00 851 24 1.00 4 8 9. 6 0.8G 15 0.0 DAILY AVERAGE VALUES 4. 8 9. 5 0. 8•) 15 1.4 03/30/84 04:00 853 24 100 4 8 9. 6 0 80 15 0.0 03/30/84 08:00 855 23 100 'L 6 9.2 0 7: i3 00 03/30/84 12: 00 857 23 105 '-l· 6 9.2 0. 7/ i3 2. 5 03/30/84 16:00 859 23 105 4. 6 9. 2 () 77 i3 2. 5 03/30/84 20:00 861 23 1.03 4. 6 9.2 0 .. .., . I : 13 1. 5 03/30/84 00:00 86:3 23 101 'i·. 1:. 9.2 0. 7' 13 0 5 DAILY AVERAGE VALUES 4. 6 9. 3 0 78 13 1 2 03/31184 04: 00 865 23 101 '+ 6 9. 2 0 Ti 13 0.5 03/31/84 08:00 867 22 101 4. 4 8.8 0. T3 11 0. 5 03/31184 12: 00 869 23 i 04 4 6 9. 2 0. T? 13 2.0 03/31184 16: 00 871 23 105 4. 6 9. 2 0 "T'T . I l i] 2. 5 03/31/84 20:00 8,.,., ,...., 23 103 4. 6 9. 2 0 77 13 1. 5 03/31184 oo· oo 875 23 102 4 6 9. 2 0 77 13 1.0 DAlL~ AVERAGE VALUES 4. 6 9. 1 0 76 13 1.3 04/01/134 04:00 877 23 i02 4. 0 9.2 0 77 1-:1 "" 1.0 04/01/84 08:00 879 23 103 4. 6 9. 2 0 Tl 13 1.5 04/01/84 12:00 881 23 1()'.~ 4. 6 9. 2 0 77 13 3. 5 04/01/84 16:00 8f33 27 105 5. 4 10.8 0 90 22 2. 5 04/01/84 20·00 8~35 29 t02 ~:]. 8 11 6 0. 97 27 1.0 04/01/84 oo·oo 887 27 1(\i 5 i.i 10. 8 0. 90 22 0. 5 DAILY AVERAGE VALUES 5. j 10. 1 0.85 18 1. 7 04/02/84 04:00 889 25 101 5. 0 10. 0 0. 8.3 17 0.5 04/02/84 08:00 891 24 1 o;: 4 8 9.6 0 80 15 1 0 04/02/Bil 12:00 893 24 1•)? 4. 8 9.6 0.80 15 3. 5 04/02/84 16:00 895 26 1 08 5. 2 10. 4 0 87 i9 4. 0 04/02/84 20:00 897 27 10 1~ 5 4 10.8 0 90 22 2. 0 04/02/84 00.00 899 26 102 5. 2 10. 4 0.87 19 1.0 DAlLY AVERAGE VALUES 5. 1 10. 1 0. 85 18 2.0 PROPOSED TOGIAK HYDfWELECTR IC f·f;OJFCT 05/10/8:3 PAGE 16 KURTLUv;. RIVER NEAR TOGifiK, ALM:WA START TIM[ 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW OAT·"-MV INCHES FEET CFS DEG C ==:::::==== ::::=== :-:=::~ :=====-==:::.!':::: ---·-====== --·· --·-====== ===== 04/03/84 04:00 901 25 101 5 0 10.0 0. 83 17 0. 5 04/03/84 08:00 Q03 24 i ()3 4. 8 9. 6 0.80 15 1. 5 04/03/84 12:00 905 24 1.08 4 8 9. 6 0.80 15 4.0 04/03/84 16·00 007 27 100 5 4 10. 8 0. 90 22 4.0 04/03/84 20:00 909 '17 "'-· t IYJ s 4 10. 8 0.90 2"' ""-1. 5 04/03/84 00:00 911 25 101. 5 0 10. 0 0 83 1? 0. 5 DAILY AVERAGE VALUES "" 1 10. 1 0 84 18 2 0 04/04/84 04:00 913 24 101 4 8 9. 6 0. 80 t5 0. 5 04/04/84 08:00 0 15 24 1.00 4 8 9. 6 0 80 15 0.0 04/04/84 12:00 9!.7 24 102 4 8 9. 6 0. 80 15 1.0 04/04/84 16:00 91.9 24 10] '1 8 96 0 80 13 1. 5 04/04/84 20:00 921 26 102 :, ·'j •• tt'~ 10. 4 0 87 10 1.0 04/04/84 00:00 9·Y:; f.'!,...._j 26 l.OJ 5 2 10. 4 0.87 19 0 5 DAILY AVERAGE VALUES 4. 9 9.9 0 82 16 0.8 04/05/84 04:00 C125 25 101 : 0 10. 0 0 83 i 7 0. 5 04/05/8'1 08:00 927 24 to:::: 4 8 9. 6 0 80 15 LO 04/05/84 12:00 929 24 t(J'j ~~ 8 9. 6 0 80 13 2. 5 04/05/84 16:00 9]1 25 1 o:j '7 0 10.0 0 83 17 2. 5 04/05/84 20:00 9 _"3:3 26 1.03 :;. ~2 10. 4 0 8l 19 1.5 04/05/84 00:00 9]':';· 25 tO! ':· 0 10. 0 0 8:J 17 0. 5 DAILY AVERAGE VALUES ::. 0 9.9 0 83 17 1. 4 04/06/84 04:00 937 24 1.00 4 8 9. 6 080 15 0.0 04/06/84 08:00 939 24 1 Oi 4 8 9.6 0 80 15 0. 5 04/06/84 12:00 941 24 i05 4 8 9. 6 0 80 15 2. 5 04/06/84 16:00 94'3 24 1 Q(:, 4 8 9.6 0.80 15 3. 0 04/06/84 20:00 945 24 u:? 4 8 9. 6 0 80 1'5 1.5 04/06/84 00:00 C147 24 l ('1 4 8 9.6 0. 80 iS 0. 5 DAILY AVERAGE VAl.UES 4. 8 9.6 080 15 1.3 04/07/84 04:00 949 23 100 4. 6 9. 2 0 -·7 . I ' 13 0.0 04/07/84 08:00 c:l'51 23 t ();) 4 6 9.2 0. 77 13 1.0 04/07/84 12:00 953 23 1()9 4. 6 9.2 0. Tl i] 4. 0 04/07/84 16·00 055 24 1 0'"' 4. 0 9. 6 0 80 15 3. 5 04/07/84 20:00 957 24 tOJ 4. 8 9.6 0 80 15 1.5 04/07/84 00:00 959 24 101 4. 8 9.6 0 80 15 0. 5 DAILY AVERAGE V~.UES 4. 7 9. 4 0. 79 14 1.8 • I PROPOSED TOGIAK HYDFIOELECTRIC PPOJECT 05-10/83 PAGE 17 KVRTLUI'i RIVER NEAR TOGIAK, ALAS~' A START T[ME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW D1Hi~ l"1'./ INCHES FEET CFS DEG C ==·===== ===:o:== :::-::::.<::::::: ::::::::::::::::~;."'!::::"":;::=:--=~::.--.:::-: ====== ====: ===:=..== ===-=== 04/08/84 04:00 961 23 100 4 6 9. 2 0. 77 1J 0. 0 04/08/84 08:00 9h3 23 101 4 6 9. 2 0 'T"7 . I r 13 0. 5 04/08/84 12:00 9t,5 23 lfh; 4 6 9. 2 0. 77 13 3.0 04/08/84 16:00 967 23 1.05 4. 0 9. 2 0. 77 13 2. 5 04/08/84 20:00 9bc;· 21 j()() 4 -. c. 8. 4 0 7() 9 8 0. 0 04/08/84 00:00 971 16 1 ()fi ] 2 6. 4 () 53 4. 2 0.0 DAILY AVERAGE VALUES 4. 3 8.6 0. 7 11 1 0 04/09/84 04:00 973 23 100 .q .. l;;r 9. 2 0 7 7 13 0. 0 04/09/84 08:00 975 :33 100 t.;. 6 13. 2 1. 10 41 0.0 04/09/84 12:00 917 25 100 5. 0 10. 0 0 83 17 0.0 04/09/84 16:00 Q]9 24 lOU 4. 8 9. 6 0. 80 15 0.0 04/09184 20:00 981. 23 1 ()() 4. 0 9.2 0. T! 13 0.0 04/09/84 00:00 98:] 26 1 Cn) 5 d 10. 4 t) 8 19 0.0 DAILY AVERAGE VALUES s l i0.3 0. 8~. 20 0.0 04/10/84 04:00 985 30 10!) 6 •j 12. 0 1. 00 30 0.0 04/10/84 08:00 987 34 1•)0 -:::. 8 13. 6 1. 1J 45 0.0 04/10/84 12:00 989 27 100 5 <l 10.8 0. 9() 22 0.0 04/10/84 1600 991 24 1 o')l) 4. 8 9.6 0 80 15 0.0 04/10/84 20:00 993 23 10(1 4. 6 9 2 0 77 13 0.0 04/10/84 oo·oo 995 25 100 5 0 10. 0 0 83 17 0.0 DAr L 'V AVERAGE \!At. UES 5 4 10 9 0 91 24 0. 0 04/11/84 04:00 9q7 28 100 '5 b 11. 2 0. 93 24 0.0 04/11/84 08:00 9'?'1' 30 100 6. G 12.0 1.. 00 30 0.0 04/11/84 12: 00 001 26 100 5. 2 10. 4 0. 8.7 19 0.0 04/11184 16:00 003 23 100 4 6 9. 2 0. 7 ;r 13 0. 0 04/11184 20·00 005 2:3 ::.no 4 6 9. 2 0. 77 13 0.0 04/11/84 00:00 007 24 1 ()t_'i 4 8 9. 6 0 81') 15 0. 0 DAILY AVERAGE '.I ALLIES '5 j 10. 3 0 8":> 19 0.0 04/12/84 0400 009 28 100 5. 6 11.2 0 9.] 24 0.0 04/12/84 08:00 011 3] 100 6 ~ 13.2 1. 10 41 0.0 04/12/84 12:00 013 25 1 ()(: 5 0 10.0 0.83 17 0. 0 04/12/84 16.00 015 22 100 4. 4 8.8 0 ,.-. .. .) 11 0.0 04/12184 20·00 017 22 100 4. 4 8. 8 0 73 1i 0.0 04/12/84 00.00 019 21 tO<) 4. 2 8. 4 0. 70 9. 8 0. 0 DAILY AVERAGE VALUES 5 0 10. 1 0. 84 19 0. 0 PROPOSED TOGIAK HYDROELECTRIC PROJECT OS 10/85 PAGE 18 KURTLUK RIVER NEAR TOGIAK. ALI..,SV.A START TIM€ Oi/19/84 04:00 DEPTH STAG[ DISCHG TEMP DATE TIME BYTE RAW DATi', 1'1'.•' INCHES FEE' CFS DEG C ======== ===== ::::::::·.::::::.:;:: :.:::::=::::::::=-=.:::~ -.--=====::.:~ ---·-·-·-:::::=·=:::=-===== 04/13/84 04:00 021 26 100 2 10. 4 0 8 7 19 0. 0 04/13/84 08:00 o-,-. c.-::: 34 100 .· 8 13.6 t Li 45 0.0 04/13/84 12:00 02:'· 26 lOCi 5 2 10.4 0.8? 19 Q_ 0 04/13/84 16:00 027 23 1. ~Jo 4 6 9.2 Q_ Tl 13 0 0 04/13/84 20:00 029 23 100 4 6 9.2 0. 7 1'3 0.0 04/13/84 00:00 031 24 tOO 4. 8 9. 6 0 8 1 ~' 15 0.0 DAILY AVERAGE VALUES 5 .-, . c.. 10.4 0.8:' 21 0.0 04/14/84 04:00 033 29 100 5-. 8 11. 6 0. 9;' 27 0.0 04/14/84 08:00 035 35 100 7 0 14.0 1 1' 49 0 0 04/14/84 12:00 0:37 ':26 tOO -? ::? -10. 4 0. 87 19 0 0 04/14/84 16:00 039 23 tOO 4. 6 9.2 0 77 13 0. 0 04/14/84 20:00 041 23 100 4 6 9. 2 0. 7 13 0. 0 04/14/84 00:00 04.3 24 tOO 4 8 9. 6 0.811 15 0. 0 DAILY AVERAGE VALUES t:J 3 10 7 0 so 23 0. 0 04/15/84 04:00 045 29 tOO 5 8 11. 6 0 9~ '27 0.0 04/15/84 08:00 047 ;33 l•)O i:, 6 13.2 L 10 41 0.0 04/15/84 12:00 049 25 101 "' 0 10.0 o 9:3 17 0. 5 04/15/84 16:00 051. 22 lOt -~ 4 8.8 0 73 11 o_ 5 04/15/84 20:00 053 23 1.(10 4 6 9.2 0. 77 13 0.0 04/15/84 oo·oo 055 25 1.00 "' () 100 0.83 17 0.0 DAILY AVERAGE VALUES ... , 0 " <:.. 10. 5 0.87 21 0.2 04/16/84 04:00 0""-' ._)/ 27 100 5 4 10. 8 0. 9;) 22 0. 0 04/16/94 08:00 Q"'iO 32 tOO !.:> 4 12.8 1. 07 37 0. 0 04/1o/S4 12:o0 061 24 101 .1-8 9.6 0. 80 1'3 0. 5 04/16/84 16:00 063 22 tOJ. .·~ 4 8.8 o_ 7'.3 i 1 0. 5 04/16/84 20:00 06~ ~--; -"-100 4 4 8.8 0. TJ 11 0.0 04/16/84 00:00 067 21 tOO ~;. 2 8. 4 0 70 9. 8 0.0 DAILY AVERAGE VALUES 4 9 9. 9 0. 82 18 0 ., . c. 04/17/84 04:00 069 26 100 5 2 10 4 0. 87 19 0.0 04/17/84 08:00 071 31 100 ~ ::;: 12. 4 1 03 34 0.0 04/17/84 12:00 n7'? .. -..1 ~~r.; "'·~ 1 (\1 S. f) 10.0 0 8:3 i7 0.5 04/ 17/81~ 16: 00 075 22 l (() 4 4 8. 8 0 7.3 11 1 0 04/17/84 20:00 077 21 iOO 4. 2 8. 4 0 70 9 8 0. 0 04/17/84 00:00 079 21 100 4. 2 8. 4 0 70 9.8 0.0 DAILY AVERAGE VALUES 4 9 9. 7 0. 81 i7 0.3 ' I PROPOSED TOGIAK HYDROELECTRIC PROJECT 05l 10185 PAGE 19 KVRTLVK RIVER NEAR TOGIAK, ALAS!-A START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME flr' IE RAW DATA !'11) INCHES FEET CFS DEG C ======:== ===== ==·-=~ ':.:::::::::::==":!:"!'!::;::::"::;::. =-:::::;;;:::!::= =====~ ~%:=.:::::::-:.:. :::::::::::::::7;:":.-::::=-: ====== 04/18/84 04:00 Ct81 25 100 .::; ,··, .... '-.; 10.0 0.83 17 0.0 04/18/84 08:00 083 30 l OC· -~ 0 12.0 1.. 00 .JO 0.0 04/18/84 12:00 085 25 101 "'· 0 10. 0 0. 8:3 17 0. 5 04/18/84 16:00 Of:37 21 102 4 .-, . "'-8. 4 0. ?C.> q 8 1. 0 04/18/84 20·00 ()80 2t 10! 4 2 8. 4 0. 70 9. 8 0. 5 04/18/84 00:00 091 2i 10() 4. 2 8. 4 0. 70 9 8 0.0 DAILY AVERAGE VALUES 4. 8 9. 5 0 7Q 16 0.3 04/19/84 04:00 09:] 23 J <X: 4 6 9. 2 0 7 7 13 0.0 04/19/84 08:00 095 27 1 (){) 5 4 10. 8 0. 91') ... 0.0 """' 04/19/84 12·00 097 22 1•)3 'f 4 8. 8 0. TJ i 1 1.5 04/19/84 16:00 099 21 104 4. :;, 8. 4 0 1" 9. 8 2.0 04/19/84 20:00 101. 20 100 4 0 8.0 0 67 8 4 0.0 04/19/84 00:00 103 19 1. ()() .1 8 7 6 0 6-:J 7 2 0.0 DA[LY AVERAGE V~.UES 4. 4 8 8 0 73 12 0 6 04/20/84 04:00 105 20 1f)0 4 0 8. 0 0 67 8. 4 0.0 04/20/84 08:00 lr)'/ 26 101) 5 .. 2 10. 4 0. 87 19 0.0 04/20/84 12:00 109 24 1 ;)1 4. 8 9. 6 0. 80 15 0. 5 04/20/84 16:00 111 21. 102 4 2 8. 4 0. 70 9. 8 1 0 04/20/84 20:00 113 21 100 4 2 8.4 0. 7i} 9. 8 0. 0 04/20/84 00:00 115 20 10() 4. 0 8. 0 0.6? 8. 4 0. 0 DAILV '.WERAGE \1,£•.:.\JES 4 4 8. 8 0. 74 12 0. 3 04/21/84 04:00 ii7 25 ). r)(; :;. 0 10.0 0. 8 . .:S 17 0.0 04/21184 08: 00 1 iS 30 100 o.O 12.0 1 Ol) 30 0.0 04/21/84 12:00 12t 24 l 0~. 4· 8 9. 6 o.8n 15 0. 5 04/21184 16: 00 1 ;;':.; 21 1 \)I. 4 ~: 8. 4 0. 70 9. 8 0. 5 04/21/84 20:00 L=25 ~:1 iOO 4. 2 8. 4 0. 70 9. 8 0.0 04/21/84 00:00 127 22 100 ij. 4 8. 8 0. Ti 11 0.0 DAILY AVERAGE VALUES 4. 8 9. 5 0. 7":' 15 0.2 04/22/84 04:00 129 23 100 4 6 9. 2 0. 77 13 0.0 04/22/84 08:00 L11 25 1 l)O 'S. 0 10. 0 0. 8] 17 0.0 04/22/84 12:00 L33 23 100 4 6 9. 2 0 7 7 i3 0.0 04/22/8·~ 16: 00 13'5 21 1. 01 4. 2 8 4 0 70 9. 8 0. 5 04/22/84 20:00 137 20 100 4. 0 8. 0 0.67 8. 4 0. 0 04/22/84 00.00 t·"'t:;' ..;>. 21 t•JO 4 2 8 4 0. 70 t;l, 8 0.0 DAILY AVERAGE VALUES 4. 4 8. 9 0 74 12 0. 1 PROPOSED TOGIAK HVDRO~LECTRI <>RiJJECT 0'5 10/8:3 PAGE 20 KURTLUK RIVER NEAR TO(;: I AK, ALASI!A START TIME 01119/84 04·00 DEPTH STAGE DISCHG TEMP DATE TIME Bvn-: RAW DAtA r1V INCHES FEEr CFS DEG C =====:::::== :;"!::':::::=== == :':' .::..: =::-=:==:o=:=:::::~:: --··"~-======= -=:::::::==~~ ===:::-:::::::::: ===== 04/23/84 04:00 141 24 100 1f. 8 9.6 0 8() 15 0. 0 04/23/84 08·00 1·'+3 28 100 5 6 11.2 0 93 24 0. 0 04/23/84 12:00 14S 23 i02 4 6 9. 2 () 77 13 1.0 04/23/84 16:00 147 21 10::? 4 '"'; . "' 8. 4 0 70 9 8 ., c; <:.. w 04/23/84 20:00 14° 20 101 4. 0 8. 0 0 6.7 8 4 0. 5 04/23/84 00:00 1St 19 100 3 8 7. 6 0.63 7 ;? 0.0 DAILY AVERAGE V~_UES 4. 5 9. 0 0 75 13 0. 7 04/24/84 04:00 1 '53 22 100 4. 4 8. 8 0 TJ 11 0.0 04/24/84 08:00 155 26 i. s. :;~ 10. 4 0.87 t9 0. 0 04/24/84 12:00 1 "'' 23 1 n·· .• ,.J 4 tJ 9. 2 0. 77 1'3 1' 5 04/24/84 16:00 j o:;c· 21 t ()/c. 4 2 8.4 0. 70 9 8 3. 0 04/24/84 20:00 Ud. 20 t 1),3 4 () 8.0 0 6 8 4 1.5 04/24/84 00:00 163 19 1. i~'G J. 8 7. 6 0 6j 7 2 0.0 DAIL'r ,:'~VERAt.:;E \/;':I'.UE·3 4 4 8. 7 0 7'? t1 1.0 04/25/84 04:00 165 19 1 ()() ~' 8 7. 6 0 6J 7 .-. '. <!. 0. 0 04/25/84 08:00 1tS7 24 t ()0 4. 8 9.6 0. 8(• 15 0. 0 04/25/84 12:00 u.,9 22 i!J6 4. 4 8.8 0. TJ t1 3. 0 04/25/84 16.00 171 22 110 4. 4 8.8 0. 73 11 5. 0 04/25/84 20:00 1 ·-r~ L I ,_. 22 1C=b .:1 4 88 0. 7J ii 3. 0 04/25/84 00:00 17"i 21 103 ., ") "'1·, C-8.4 0. 70 9. 8 1.5 DAILY AVERAGE ~A~UES 4 3 8. 7 0 7:2 11 2. 1 04/26/84 04:00 1.77 2t 102 4 2 8. 4 0. 70 9 8 1 0 04/26/84 08:00 l 7C: 21 iC/3 4 2 8. 4 0 70 9. 8 1.5 04/26/84 12·00 i8i 21 t05 .;~. .;.~ B. 4 0. 7C 9. 8 2 5 04/26/84 16:00 188 25 i 05 5 0 10. 0 0 BJ 17 2. 5 04/26/84 20:00 185 30 tc: b 0 12. 0 1.00 JQ 0. 5 04/26/84 00:00 FJ7 3i 1 (:•;:: ,.\ 2 12 4 1. 03 34 1.0 DAILY AVERAGE '..1AI".L'ES '5 0 9. 9 0. 83 i8 1 5 04/27/84 04:00 H.!'? 28 102 '5 6 11 2 0. 9~3 .24 1.0 04/27/84 08.00 1 'l/1 28 103 '5 6 11 2 0. 9:J 24 1.5 04/27/84 12•00 Ft:J 33 iO·t t:o 6 13.2 1. 10 41 2. 0 04/27/84 16:00 1 1';.'5 38 :04 7 6 15. 2 1 27 64 2.0 04/27/84 20:00 1'-"i:'/ 34 103 t •. 8 13. 6 1 ' 1 ~l 45 1 5 04/27/84 00:00 199 31 102 6 2 12.4 1. 03 :34 1.0 DAILY AVERAGE VALUES (~-4 12. 8 1. 07 39 1.5 • • PROPOSED TOGIAK HYDROELECTRIC ~~OJECT 05 1 10/85 FAGE 21 KURTLUK RIVER NEAR TOGIAK, lo~i .. A9A START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYrt:_ RAW DAIA t~\/ INCHES FEET CFS DEG C :======= =:=:::::::: =::::::~-:-:::=:": :=::.:= = .: -.~:.; ======= =====";;:'! ::.:.::;~== ===== 04/28/84 04·00 2Ul. 28 t02 ~, 6 11. 2 0 9;] 24 1.0 04/28/84 08:00 203 . ..,-, i 04 ":: 4 10. 8 0 9i) 2~· 2. 0 ... "! : 04/28/84 12:00 20:3 29 t ,)5 5 8 11. 6 0 9/ .~7 2. 5 04/28/84 16:00 ?07 4:3 t ~Jr:,1 :'1 b 17.2 1 4.3 95 1.5 04/28/84 20:00 209 41 i.O:~ s 2 16.4 1 31 81 1 0 04/28/84 00:00 21 i 38 102 7 6 15.2 1 27 64 1.0 DAILY AVERAGE VALUES t; 9 13. 7 1 15 '52 1.5 04/29/84 04:00 21:3 38 J.O=? 7 6 i52 1 27 64 1.0 04/29/84 08:00 215 39 103 7 8 15.6 1 30 71} 1.5 04/29/84 12:00 217 38 103 7' b 15.2 l.':n 64 1.5 04/29/84 16·00 21.:::' 35 1 (}t~ 7 0 14.0 1 17 40 2. 0 04/29/84 20:00 221 33 103 6 6 13.2 1. 1 () 4i 1.5 04/29/84 00:00 223 31 1 {) l 6 ., "" 12. 4 1. OJ '34 0. 5 DAIL\ AVERAGE VALUES 7 l 14.3 1. 19 54 1.3 04/30/84 04:00 225 29 iOt 5 8 11. 6 0 97 27 0 5 04/30/84 08:00 227 28 11)<./. 5 b 11. 2 0. 9J 24 2.0 04/30/84 12:00 •") :;.:;:-c. .... ' 29 106 5. 8 11. 6 0 97 27 3. 0 04/30/84 16:00 231 31 108 io 2 12. 4 103 .34 4. 0 04/30/84 20·00 ·'""\ ..,.-, c:::,,,).,:; 33 i.O'J ,,_ 6 13. 2 1 10 41 2. 5 04/30/84 00:00 2:J'5 31 1.()3 1:; 2 12. 4 1. 0:3 a4 1 5 DAILY AVERAGE VALU~S r. 0 12 1 i. Oi. .'3 i 2 3 05/01/84 04:00 237 30 i02 b 0 12. 0 1. 00 30 1.0 05/01/84 08:00 2.J'-' 29 103 ~-8 11. 6 0 9l ,..., ~.I 1.5 05/01/84 12:00 241. 30 110 t_· 0 12 0 1 00 30 5. 0 05/01/84 16:00 243 31 110 i ~. ~-1 .:::. 12. 4 1 03 34 5. 0 05/01/84 20.00 245 30 l•Y.; (:, 0 12. 0 1. 00 ~10 2. 5 05/01/84 00:00 247 28 10l 5 6 112 0. 93 :24 0 5 DAlLY AVERAGE VALUES s 9 119 0. 99 29 2.6 05/02/84 04:00 249 25 100 5. 0 10.0 0. 8:3 17 0. 0 05/02/84 08:00 251 27 101. 5. 4 10.8 0 90 '")·"') 0. 5 ·~.:::... 05/02/84 12:00 253 28 108 5 6 11. 2 0 9J 24 4. 0 05/02/84 16:00 255 27 110 5 4 10.8 0. 90 22 5.0 05/02/84 20:00 257 27 104 5 4 10.8 0 90 22 2.0 05/02/84 00:00 259 24 100 4. 8 9.6 0.80 15 0. 0 DAILY AVERAGE VALVES ~ 3 10 :;, 0. 88 20 1.9 PROPOSED TOGIAK HYDROELECTRIC ~ROJECT 0:5,10/85 PAGE 22 KURTLUK RIVER NEAR TOGIAK, ALAUI'A START TIME 01/19/84 04 00 DEPTH STAGE DISCHG TEMP DATE TIME BY fE RAW Ol-'1 r,..'\ ~"1\.: INCHES FEET CFS DEG C =~====== '!:::!::=:::~:::::: ==~~ =====·::::::.::::·.·':'::.. = ';. =====-::::: ===== :=::=:::::::::;::::::::::;:.: ===::== 0~/03/84 04:00 261 23 100 4 6 9. 2 0. 77 13 0. 0 05/03/84 08:00 26J 26 lOt '5 2 10. 4 0. 87 19 0. 5 05/03/84 12:00 265 29 1.0'5 8 11. 6 0 97 27 2.5 05/03/84 16:00 267 27 t09 "1 4 10.8 0. 9(\ 22 4. 5 05/03/84 20:00 269 26 1.0:1 .:::;, -~ -<!:. 10. 4 0. 87 19 1.5 05/03/84 00:00 271 23 100 4 6 9.2 0. 77 1 'J 0.0 DAILY AVERAGE VALUES ;, j 10.3 0. 8,i., 19 1.5 05/04/84 04:00 273 24 100 4 8 9. 6 0.80 15 0. 0 05/04/84 08:00 '"l7<; c. ' . .., 28 tO! :-; 6 11.2 0 9 J 24 0. 5 05/04/84 12:00 277 28 107 ":> 6 11 2 0.93 24 3. 5 05/04/84 16:00 ·""")70.:1-<:.· • 26 if1 ·: 2 10. 4 0. 87 1'7' 5. 5 05/04/84 20:00 281 26 105 t:; .-, ...... c.;. 10. 4 0. 87 19 2 5 05/04/84 00:00 283 25 101 .0 10. 0 0 83 17 0 5 DAILY AVERAGE VALUES :;. ' r2 10. 5 o s.:-20 2 1 05/05/84 04:00 285 24 100 4. 8 9. 6 0. 80 15 0. 0 05/05/84 08:00 287 26 1 OJ 5 2 10.4 0. 87 1 '7' 1 5 0~/05/84 12:00 289 25 111 5. 0 10. 0 0. 83 17 5. 5 05/05/84 16:00 291 26 114 5. 2 10. 4 0.87 19 7. 0 05/05/84 20:00 293 26 1.08 5 2 10.4 0 87 19 4. 0 05/0~/84 00:00 29!1 25 10;:! 5. 0 10.0 0.83 17 1 0 DAILY AVERAGE VALUES 5 1 10. 1 0.85 18 3. 2 05/06/84 04:00 297 25 101 'j 0 10.0 0.83 17 0. 5 05/06/84 08:00 2'?9 25 106 5 0 10.0 0. 83 17 3.0 05/0b/84 12:00 301 25 114 ::". 0 10.0 0.83 17 7.0 0~/06/84 16:00 308 26 1 i.f) 5 2 10. 4 0. 87' 19 8.0 05/06/84 20:00 305 27 i i () :5 4 10. 8 0. 90 :22 5. 0 05/06/84 00:00 307 25 1 O':l 5. 0 10. 0 0.8"3 17 1. 5 DAILY AVERAGE VALUES t: 1 10. 2 0 85 1B 4.2 " 05/07/84 04:00 309 25 101 5 0 10.0 0 B~J t7 0. 5 0~/07/84 08:00 311 25 105 5 0 10.0 0.83 1.7 2. 5 05/07/84 12:00 31 ~J 26 1. !t.., 5.2 10.4 0. 87 19 B. 0 05/07/84 16:00 31'5 '""7 <:,. \18 5 4 10. 8 0. 9() ;:22 9.0 05/07/84 20:00 317 27 f 11 5. 4 10.8 0.90 ::;~ ..... e_ 5. 5 05/07/84 00:00 319 26 105 '? 2 10.4 0 87 19 2. 5 DAILY AVERAGE VALUES :.:;. 2 10. 4 0.87 19 4. 7 • . PROPOSED lOGIAK HYDROELECTRIC ~ROJECT 05110/85 PAGE 23 KURTUJK RIVER NEAR TOGIAK, AL.ASI'\A SlART TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BY fE RAW DATt-; ,~i\) INCHES FEET CFS DEG C ========-:-::::= ===== ==~~:-:' =::::=:::-::=~::::-=.~ -· •.... -:::::::::::::::-; ==:::::::=::::=·<:~ :::::::::::::::::::::: ---------- 05/08/84 04:00 T21 26 i02 ::,· ~ 10. 4 0. 87 19 1.0 05/08/84 08:00 3.-...... r!.·...J 25 106 :j 0 10. 0 o.8:; 17 3. 0 05/08/84 12:00 :],J5 26 1l7 j 2 10. 4 0.8 7 19 8. 5 05/08/84 16:00 327 28 t l. ')• s 6 11. 2 0 9:.! 24 9. 5 05/08/84 20:00 3'-.(:/ c:' •• 29 t j 2 ·] 8 11. 6 0. 97 27 6. 0 05/08/84 00:00 331 27 I 0 ~) ":. 4 10. 8 0 90 22 2. 5 DAILY AVERAGE VALUES 'J 4 10. 7 0. 90 21 5. 1 05/09/84 04:00 333 26 10~ ::i 2 10. 4 0 87 19 1.0 05/09/84 08:00 3:35 26 106 5. 2 10. 4 0 8..,. 19 3.0 05/09/84 12:00 3~37 27 1 j h 5. 4 10. 8 0. 90 22 8.0 05/09/84 16:00 339 28 !itt 5. 1-J 11. 2 0 9J 24 9. 5 05/09/84 20:00 341 29 112 5 8 11.6 0. 97 27 6.0 05/09/84 00:00 343 27 105 5. 4 10.8 0.90 22 2. 5 DAILY AVERAGE VALUES '5 4 10. 9 091 22 5 0 05/10/84 04:00 345 27 102 s 4 10.8 0. 90 22 1 0 05/10/84 08:00 347 27 !.07 5. 4 10.8 0. 90 22 3. 5 05/10/84 12:00 349 27 116 5 4 10. 8 0. 90 22 8.0 05/10/84 16:00 351 28 1 "c' •. J.., 5 6 11. 2 0. 9J 24 9. 5 05/10/84 20:00 351 29 1. 1.;;: '5. 8 11.6 0 97 27 6. 0 05/10/84 00:00 355 28 10"1 ~ 6 11 2 0. 93 24 2. 5 DAILY AVERAGE VALUES :3 s 11. 1 0 92 24 5. 1 05/11/84 04:00 357 27 1 0~3 5 4 10. 8 0. 90 22 1.5 05/11/84 08:00 359 27 107 5. 4 10. 8 0 90 2' "" 3.5 05/11/84 12: 00 361 28 11.} 5 6 11 2 0.93 24 8. 5 05/11184 16:00 363 ::28 119 5 6 11 2 0. 9~'3 ;:~4 9. 5 05/11/84 20:00 :365 29 112 5 8 11 6 0 97 -·7 c.. 6.0 05/11/84 00:00 367 28 1.05 s 6 11.2 0 93 24 2. 5 DAILY AVERAGE VALUES '5. 6 11. 1 0. 93 24 5. 3 05/12/84 04:00 369 27 102 5 4 10.8 0. 90 22 1.0 05/12/84 08.00 371 27 107 '5 4 10. 8 0.90 22 3. 5 05/12/84 12:00 .373 27 11 b 5. 4 10. 8 0. 90 ;22 8.0 05/12/84 16:00 37~j 28 11 '7' 5 6 11. 2 0. 93 24 9. 5 05/12/84 20: 00 377 28 112 5 6 11. 2 0.93 24 6. 0 05/12/84 00:00 379 27 105 5 4 10.8 0 90 22 2. 5 DAILY AVERAGE VALUES :3. 5 10.9 0.91 23 5. 1 PROPOSED TOGIAK HYDROELECTRIC PROJECT 05110/85 PAGE 24 KURTLUK RIVER NEAR H:JGIAK, ALAS!\ A START TIME 01/19/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTC RAW DAHl M•' v INCHES FEEf CFS DEG C :::::=.:==:=== ===== :::::=:=::::-:::::::::::::::=.:::::.-:::. ---·-....... ====== =-===:= :=:===== ===== 03/13/84 04:00 381 ,...,. .. ~ / to;;.~ 5. 4 10.8 0. 9!.i 22 1.0 05/13/84 08:00 31]3 27 to? :s 4 10.8 0. 90 22 3. 5 05/13/84 12:00 Ji-35 ., .. c:.l 115 5. 4 10 8 0. 90 22 7. 5 05/13/84 16:00 387 28 1! :5 5 6 11. 2 0. 9:] 24 7. 5 05/13/84 20:00 389 28 111. 5. 6 11. 2 0. 9:] 24 5. 5 05/13/84 00:00 391 28 1.0? 5 6 11. 2 0 93 24 3. 5 DAILY AVERAGE VALUES S. 5 11. 0 0 92 23 4. 8 05/14/84 04:00 393 27 lOt• 5. 4 10. 8 0.90 22 3.0 05/14/84 08:00 395 27 1 o~ .. ":• 4 10. 8 090 2;2 3. 0 05/14/84 1200 397 28 lOS· 5 6 11. 2 0 9:1 24 4. 5 05/14/84 16:00 399 28 1t0 5 6 11 2 0 93 24 5. 0 05/14/84 20:00 401 28 1 Oi:i 5 6 11 2 0. 93 24 4 0 05/14/84 00:00 403 29 107 5. 8 11. 6 0. 97 ·:~.7 3. 5 DAILY AVERAGE V~_UES '5 6 11. 1 0 93 24 3.8 05/15/84 04:00 4()5 30 1 ()/., b. 0 12.0 1 00 .JO 3.0 05/15/84 08:00 407 31 lOt:• 6. 2 12. 4 1. 03 34 3.0 05115184 12:00 409 36 10fl 7 2 14. 4 1 20 54 4.0 05/15/84 16:00 411 38 10El 7. b 15.2 1 ., .. .::. I 64 4. 0 05/15/84 20:00 41~3 36 107 ...., , I "'-14.4 120 54 3. 5 05115184 oo·oo 415 35 1 ,., c; •,J". 7 () 14. 0 1. 1 7 49 2. 5 DAILY AVERAGE VALUES 6 9 13. 7 1. 15 48 3.3 05/16/84 04:00 417 34 105 6. 8 13.6 1 13 45 2. 5 PROPOSED TOGIAK HVDROELECTRI<: dWJECT 05r10/85 PAGE 1 KURTLUK RIVER NEAR TOGIAK, A LASh A START TIME 05/17/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW DATA !1\/ INCHES FEET CFS DEG C e=•-=•=:= ===== =:=:-.:.:: =======~=~ ==== ====== ====: ====== ===== 05/17/84 04:00 1 35 106 7. 0 14. 0 1. 17 49 3. 0 05/17/84 08:00 . ., 34 106 6. 8 13. 6 1. 13 45 3. 0 •J 05/17/84 12:00 5 34 107 6. 8 13. 6 1. 13 45 3. 5 05/17/84 16:00 7 34 113 6. 8 13. 6 1 1 ~J 45 6. 5 05/17/84 20:00 9 34 1.19 6 8 13.6 1 13 45 9. 5 05/17/84 00:00 11 34 114 6 8 13. 6 1. 13 45 7. 0 DAILY AVERAGE VALUES 6. 8 13. 7 1 14 46 5. 4 : " 05/18/84 04:00 13 33 109 6. 6 13.2 1. 10 41 4. 5 05/18/84 08:00 15 33 1.06 6. 6 13. 2 1. 10 41 3.0 05/18/84 12:00 1.7 33 110 6 6 13. 2 1. 10 41 5. 0 05/18/84 16:00 19 33 1.19 6 6 13. 2 1. 10 41 9. 5 05/18/84 20:00 21. 33 120 6. 6 13.2 1. 10 41 10. 0 05/18/84 00:00 23 33 115 6. 6 13. 2 1. 10 41 7. 5 DAILY AVERAGE VALUES 6. 6 13. 2 1. 10 41 6.6 05/19/84 04:00 25 32 109 6 4 12.8 1 07 37 4. 5 05/19/84 08:00 2"Y ( 32 J. O~j 6 4 12. 8 1. 07 .. ,....,. ,;J/ 2. 5 05/19/84· 12:00 29 32 10'? ~ 4 12.8 1. 0 7 37 4. 5 05/19/84 16:00 3i. 32 116 6. 4 12.8 1. 07 37 8.0 05/19/84 20:00 33 32 117 '.J. 4 12. 8 1. 07 37 8. 5 05/19/84 00:00 35 32 114 6 4 12. 8 1 07 37 7.0 DAILY AVERAGE VAl .. UES 6 4 12. 8 1. 07 37 5. 8 05/20/84 04:00 37 31 1 l 0 6 2 12. 4 1. 0:3 34 5. 0 os'lle4 o8:oo 39 31 107 6 2 12. 4 1. 03 34 3. 5 05/ /84 12:00 41 31 1.09 f:, 2 12. 4 1. 03 34 4. 5 05/20/84 16:00 43 31 117 6 2 12. 4 1. 03 34 8. 5 05/20/84 20:00 45 31 1.18 6 2 12. 4 1. 03 34 9.0 05/20/84 00:00 47 31 l14 6. 2 12. 4 1. 03 34 7.0 DAILY AVERAGE VALUES 6. 2 12. 4 1. O~J 34 6. 3 05/21/84 04:00 49 31 110 f:, 2 12.4 1. 03 34 5. 0 05/21/84 08:00 51 30 1.07 6. 0 12.0 1. 00 30 3. 5 05/21/84 12:00 53 30 109 b 0 12. 0 1. 00 30 4. 5 05/21184 16: 00 55 31 118 6 2 12. 4 1. 03 34 9.0 05/21/84 20:00 57 31 121 6.2 12. 4 1. 03 34 10. 5 05/21/84 00:00 59 31 117 6. 2 12. 4 1. o·J 34 8. 5 DAILY AVERAGE VALUES 6. i 12. 3 1. 02 33 6.8 Af: PROPOSED TOGIAK HYDR0ELECTRIC ~POJECT 05>10/85 PAGE 2 KURTLUK RIVER NEAR TOGIAK, AL.O,r.-W.A START TIME 05/17/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW Dt'H A tv!'./ INCHES FEEf CFS DEG C =======~= ===== ~==·::.= =·~===:-:t:::::::":":":::: -·--·-· =====:::: =:-:===:.: :=::::::::::::::.:: =::::=== 05/22/84 04:00 61 31 U1 6. 2 12. 4 1. 03 :)./l. 5. 5 05/22/84 08·00 63 3i 109 6. 2 12 4 1 03 :34 4. 5 05/22/84 12:00 65 31 u.o 6. 2 12. 4 1. O:J 34 5. 0 05/22/84 16:00 f.J7 31 l 18 !-}. 2 12. 4 1. 0:::1 34 9.0 05/22/84 20:00 LS9 31 l.20 ·~ 2 12. 4 1 OJ 34 10.0 05/22/84 00:00 '1 31. j U:o .. '1 'J e~ 12. 4 1 C·3 )4 B. 0 DAILY AVERAGE VALVES 6 2 12 4 1 o·J 34 7. 0 05/23/84 04:00 73 30 111 b 0 12. 0 1 00 30 5. 5 05/23/84 08:00 75 30 i09 6 0 12. 0 1 00 30 4. 5 05/23i84 12:00 ...,.'7 30 ttl I~) 0 12.0 1 00 ]0 ~. 5 05/23/84 16:00 ::'9 30 ~ t") -1 ;.,.:= ... 6 0 12 0 1.. 00 30 10. 5 05/23/84 20:00 81 31 122 6 2 12. 4 1 O:J 34 11. 0 05/23/84 00:00 83 30 j 1.6 t::J. (j 12 0 1. 00 :Jo B. 0 DAILY AVERAGE VALVES b 0 12. 1 1. 01 31 7. 5 05/24/84 04:00 85 30 I. 1 0 b. 0 12. 0 1 0i) 30 5 0 05/24/84 08:00 87 30 1 n·: 'J.' 0. 0 12.0 1. Oti :30 3. 5 05/24/84 12.00 89 30 109 6. 0 12.0 1 00 30 4. 5 05/24/84 16:00 'H 30 116 6. I) 12.0 1. 00 30 8.0 05/24/84 20:00 Q? . ,, 30 1 JS' 6. 0 12. 0 1. 00 30 9. 5 05/24/84 00:00 9'5 29 Ub 5. 8 11.6 0.9 ... 27 8.0 DA[LY AVERAGE VALUES >!:1 IJ 11. 9 1. 00 30 6 4 05/25/84 04:00 97 29 lit) 5 8 11. 6 0. 97 27 5. 0 05/25/84 08:00 99 29 t07 5. 8 11. 6 0. 9l 27 3. :- 05/25/84 12:00 101 29 108 5. B 11 6 0.97 2'7 4. 0 05125184 16:00 11Y1 29 115 5 8 11. 6 0.91 27 7. 5 05/25/84 20:00 10'5 30 i20 6. 0 12. 0 1 00 30 10.0 05/25/84 00:00 1C•7 29 ttb 5 8 11. 6 0. 97 27 8.0 DAILY AVERAGE VALVES 5 8 11 7 0. 98 28 6. 3 05/26/84 04:00 10° 29 109 5. 8 11. 6 0. 9 7 27 4. 5 05/26/Btl o8·oo 111 29 lOt, 5. 8 11. 6 0 97 27 3.0 05/26/84 12:00 U3 '"lO c:..' 107 ::. 8 11. 6 0 9.7 .-,....,. <!.} 3. 5 05/26/84 1600 115 29 i09 :~ 8 11. 6 0. 97 27 4. 5 05/26/84 20:00 1i7 29 1 i ' ~ L s 8 11. 6 0 97 27 5. 5 05/26/84 0000 uo 29 109 8 11 6 0 97 27 4. 5 DAILY AVERAGE VALUES s e 11. 6 0.97 27 4.3 PROPOSED TOGIAK HYDFWELEC TR IC t-FtJ,)EC T 0~-'10r85 PAGE 3 KURTLUK RIVER NEAR WGIAI'\, AU~SI'A START TIME 05/17/84 04:00 DEPTH STAGE DI!:"lCHG TEMP DATE TIME BVTE RAW Dt~ T l:. :11,' INCHES FEET CFS DEG C =======:== ::::::::=::<:-== =!".::;.!'".::: ::::::::::::=::==:=::~~=-=~== :::::::=== :=:::::.:;::: =:::=::-=-::== -::==== 05/27/8 1~ 04: 00 121 29 10 7 ':.• 8 11.6 0 9.7 2? 3 5 05/27/84 08.00 123 29 10'j 'j 8 11. 6 0.9? 27 2 5 05/27/84 12:00 125 28 106 5 6 11. 2 0. 9] 24 3.0 05/27/84 16:00 127 20 111 5. B 116 0 97 2? 5. 5 05/27/84 20:00 .. ,.~ ~. .... 29 11'1 5. 8 11 6 0 97 27 8. 5 05/27/84 00:00 1 ]1 29 1 l .a 5. 8 11 6 0 97 27 7. 0 DAIL¥ AVERAGE VALUES 5. 8 11. 5 0 96 27 5. 0 05/28/84 04:00 13] 28 108 '5 6 11. 2 0.93 ;?.4 4.0 05/28/8ll· 08: 00 13"i 28 105 5 6 11. 2 0. 9:3 24 2. 5 05/28/84 12.00 137 28 1 o;' '3 6 11 2 0 9] 24 3. 5 05/28/84 16:00 1 :iS' 28 ti2 5. 6 11. 2 0. 93 24 6.0 05/28/84 20:00 141 28 i 1 5 '5 6 11 2 0 93 24 7. 5 05/28/84 00:00 1.43 28 113 5 6 11 2 0 9::1 24 6. 5 DAILY AVERAGE VALUES '5 6 11. 2 0. 93 24 5. 0 05/29/84 04·00 145 28 108 ~· tJ 11 2 0 93 24· J.l .. 0 05/29/84 08:00 14' 28 1 ()1,:) 5 ~:I 11 2 0. 93 24 3. 0 05/29/84 12:00 149 28 108 :~ 6 11. 2 0 93 24 4.0 05/29/84 16:00 l 5 j 28 115 5 6 11 2 0.93 :24 7. 5 05/29/84 20:00 153 28 117 ~~ . ..,.,' 6 11. 2 0. 9:] 24 8. 5 05/29/84 00:00 15'3 28 1 121 5 6 11 2 0 93 24 6. 5 DAILY AVERAGE VALUES '5 6 11 2 0 93 24 5 6 05/30/84 04:00 15 ·; 28 108 5 6 11. 2 0 93 24 4. 0 05/30/84 08:00 15-=? ~,-. ,._ { 103 5. 4 10.8 0 90 .... ...., .:0«. 2. 5 05/30/84 12:00 161 28 108 5 6 11. 2 0 93 24 4. 0 05/30/84 16:00 16:-~ 28 lt9 6 11. 2 0 93 24 9. 5 05/30/84 20:00 165 28 124 5 6 11.2 0 9~J 24 12.0 05/30/84 00:00 1h7 28 lt9 s 6 11. 2 0 93 <24 9. 5 DAILY AVERAGE VALUES ·:: 6 11. 1 0. 9'3 24 6. 9 05/31/84 04:00 laS' 28 lll 5 6 11. 2 0 9::1 .24 5. 5 05/31/B4 08.00 171 27 t06 5 4 10.8 0 90 22 3. 0 05/31/84 12:00 173 28 : 11 ::; b 11. 2 0. 93 .'24 5. 5 05/31/84 16:00 1.7'5 28 123 ':' 6 11. 2 0. 93 24 11. 5 05/31/84 20: 00 177 28 126 5 6 11. 2 0. 93 24 13.0 05/31/84 00:00 17q 28 12~ 5 6 11. 2 0 93 24 10. 5 DAILY AVERAGE VALUES '5. 6 11 1 0. 9:] 24 8. 2 PROPOSED TOGIAK HYDRUf::LEf:TRIC ~'PQ'-IE.CT 05 10/85 PAGE 4 1-\URTLUI-\ RIVER NEAR TOG I AI-\, ALAS!/. A START TIME 05/17/84 04:00 DEPTH STAGE: DISCHG TEMP DATE TIME BY iE RAW DA rA !"''"' INCHES FEEf CFS DEG C ==========-====== ==··':!:;::"" =~===-::':'":::".~~~~ == ~!". = =====: -::::::::::=:~ ~=:-::-::~~::=" ===== 06/01/84 04:00 1!31. 27 113 s 4 10. 8 0.9() ::J·""~ -"'-6. 5 06/01/84 08:00 18:3 27 108 5 4 10.8 0.90 '"\•""\ 4.0 c:-.c-:, 06/01/84 12:00 185 27 11.2 5 4 10 8 0. 90 ::;~~, •-"'-6 0 06/01184 16:00 18? 28 1.24 5 6 11. 2 0 Q'• •• ,_.J 24 12.0 06/01/84 20.00 ll]Q 28 1 :~··? 5. 6 i 1. 2 0. 9"1 24 13. 5 06/01/84 oo·oo 191 28 1 ,:::·;=.: 5 6 11. 2 0 9J 24 11. 0 DAlLV AVERAGE VALUES 5 5 11. 0 092 23 8.8 06/02/84 04.00 193 27 114 5 4 10.8 0 90 22 7. 0 06/02/84 08:00 iOIC: .&. ' ·~i 27 1 (19 :: 4 10. 8 0. 91) 22 4. 5 06/02/84 12:00 197 27 113 ":· 4 10.8 0 90 22 6. 5 06/02/84 16.00 19° 28 L!:? :::: 6 11. 2 0 93 24 12. 5 06/02/84 20:00 201 28 1::n 5 6 11. 2 0.93 24 13 5 06/02/84 00:00 203 27 122 5. 4 10.8 0.90 22 11. 0 DAILY AVERAGE VALUES 5. 5 10.9 0 9i 23 9.2 06/03/84 04:00 20:'; -~·.., 114 5 4 10. 8 0 9t.'l 22 7.0 "'-' 06/03/84 08:00 2G'7 27 109 5. 4 10. 8 0 90 22 4. 5 06/03/84 12:00 209 27 11:?. 5. 4 10.8 0. 90 22 6. 5 06/03/84 16:00 2U 28 125 5 6 11. 2 0. 93 24 12.5 06/03184 20:00 213 28 127 5. 6 11. 2 0.93 24 13. 5 06/03/84 00:00 215 27 1.2:? 5 4 10.8 0. 90 22 11. 0 DAlLV AVERAGE V~.UES "3 5 10. 9 0. 91 23 9.2 06/04/84 04:00 217 ,..,..., c..: 115 ~ 4 10.8 0 9<) ,......, ""'"" 7. 5 Ob/04/84 08:00 219 27 1 J 0 5 '-1 10. 8 0 90 22 5.0 06/04184 12:00 221 27 114 4 10. 8 0.90 22 7 0 Ob/04/84 16:00 223 28 1?.5 :: 6 11 2 0 9J 24 12. 5 06/04/84 20:00 2~:c; 28 1. ·'.)() t--. :s 1:, 11. 2 0. 93 24 14. 5 06/04/84 00:00 2;::::7 27 t25 5. 4 10.8 0. 90 --.~-. .=:.. c_ 12. 5 DAILY AVERAGE VALUES s 5 10.9 0 91 2~3 9. 8 -06/05/84 04·00 229 27 u.: 5 4 10 8 0 90 2'" -<!. 8.5 06/05/84 08:00 2]1 27 112 :~ 4 10. 8 0.90 22 6.0 06/05/84 12:00 2'Y:> ,J,..• 27 1.16 5 4 10.8 0. 90 22 8. 0 06/05/84 16·00 2:55 27 126 5 4 10. 8 0 90 22 13.0 06/05/84 20:00 237 28 128 5 6 11 2 0 93 :;;4 14 0 06/05/84 oo·oo 239 27 123 ;;.; 4 10.8 0 90 ·::;!·""\ -"'-11. 5 DAILY AVERAGE VALUES 5 4 10. 9 0 91 22 10.2 PROPOSEV TOGIAK HYDR1JELEC TR IC ~·RU,.iE.:CT 1)'5 .' 10/85 F-·AGE 5 KURTLUK RIVER NEAR TOGIAK, ALMWA START TIME 05117/84 04:00 DEPTH STAG!:~ DISCHG TEMP DATE TIME BYTE RAW DA1A !"!',.' INCHES FEEr CFS DEG C :========~ :..:::=:::=::: ==-.. ~..::_.. =-=~=':"::..::::~:...::· ::::~== =====::=.: :;·.:;:::::::::::::;::=. :::::::::::::::::::= ===== 06/06/84 04:00 2'+1 27 116 5 4 10.8 0. 9<) 2' "-8. 0 06/06/84 08:00 243 27 1l3 5. 4 10. 8 09iJ 22 6. 5 06/06/84 12:00 24~} 27 ll:J :5 4 10. 8 0. 9() 22 6 5 06/06/84 16:00 24? 27 ,,..,., ..,,c-:,,:•_ 5 4 10.8 0 90 22 11. 0 06/06/84 20:00 249 27 126 5 4 10. 8 0. 90 22 13. 0 06/06/84 00:00 251 27 122 s 4 10. 8 0. 90 22 11. 0 DAILY i1VERAGE ',iALUES 5. 4 10.8 0 90 22 9. 3 06/07/84 04:00 253 26 115 5. 2 10. 4 0 87 19 7. 5 06/07/84 08:00 25~5 27 11.1 5 4 108 0 90 22 5. 5 06/07/84 12·00 257 .. .,7 e.. 1 i ll s 4 10. 8 0 9(.• 22 7.0 06/07/84 16:00 2sc: 27 126 5 4 10. 8 0 9 1J 22 13. 0 06/07/84 20:00 2t!i 27 1 7Q ·~ . 5 4 10. 8 0 9(! 22 14. 5 06/07i84 00:00 263 27 1.;;n 5 4 10.8 0. 9C• 22 11 5 DAILY AVERAGE VALUES 5 4 10. 7 0. 9(• 22 9.8 06/08/84 04:00 ,..\: c: r.::,.Q.) 26 11:'-:: .;! 10 4 0 8 ;r i9 7. 5 06/08/84 08:00 ;;u::J 7 26 110 5 2 10. 4 0 87 i9 5 0 06/08/84 12.00 269 26 1]"1 3. 2 10. 4 0.87 19 6. 5 06/08/84 16:00 •"'1w"T 1 C:.,.! I 27 122 :: 4 10. 8 0. 90 22 11. 0 06/08/84 20:00 273 27 1 ;zh 5 4 10. 8 0 90 22 13.0 06/08/84 00:00 275 26 1~2 5. 2 10. 4 0 87 19 11. 0 DAILY AVERAGE VALUES =; 3 10. 5 0. Bt~ 20 9. 0 06/09/84 04:00 277 26 tlb <-; .-; ' ~ 10. 4 0 8' 19 8. 0 06/09/84 08:00 ""''lQ ""' . 27 ! i. Jl. ::5 4 10.8 0 90 22 7. 0 06/09/84 12:00 281 26 114 5 2 10. 4 0. 87 19 7. 0 06/09/84 16:00 2t33 27 ti8 "; 4 10.8 0 9(J 22 9.0 06/09/84 20:00 2'3'5 27 122 'S 4 10. 8 0 90 22 11. 0 06/09/84 00:00 287 27 1 1° 5 4 10. 8 0 90 22 9 5 DAILY AVERAGE VALUES 5 ~3 10. 7 0 89 ,:;: 1 8. 6 06/10/84 04:00 289 27 11.5 :::: If 10.8 0. 90 .-,.--. 7. 5 ._}. ..,. c:'.c:. 06/10/84 08:00 291 26 11.3 "' ., ... r.:_ 10. 4 0. 87 :L9 6. 5 06/10/84 12:00 293 26 11~ :::;_ .., 10. 4 0. 87 19 7. 5 -c.. 06/10/84 1600 2t=;•c; 27 12;.,? :-; 4 10.8 0. 90 22 11 0 06/10/84 20:00 '"1'-..:/..,. .::. .. 27 123 5 4 10. 8 0 90 22 12. 5 06/10/84 00:00 2'?9 27 1 -:.>~ ~ .:;,. l s 4 10 8 0 90 ,..,,.., .:..::. 10. 5 DAILY 1\VERAGE \'A:_UES ·:·. 3 10. 7 0 gcJ 21 9 3 - PROPOSEC TOGIAK HYDROELECTRI P~OJECT KURTLUK RIVER NEAR TOGIAK. ALAS~A DATE TIME =======:= ------·--·--- 06/11/84 04:00 06/11/84 08:00 06/11/84 12:00 06/11184 16: 00 06/11/84 20: 00 06/11/84 00:00 06/12/84 04:00 06/12/84 08:00 06/12/84 1200 06/12/84 16:00 06/12/84 20:00 06/12/84 00:00 06/13/84 04:00 06/13/84 08:00 06/13/84 12:00 06/13/84 16:00 06/13/84 20:00 06/13/84 00:00 06/14/84 04:00 06/14/84 08:00 06/14/84 12:00 06/14/84 16:00 06/14/84 20:00 06/14/84 00:00 06/15/84 04:00 06/15/8tl 08 00 06/15/84 12:00 06/15/84 16:00 06/15/84 20:00 06/15/84 00:00 BYTE RAW OAT I• :.:::::::::::::::::;::.::,;~.;::.:· 301 26 115 303 26 112 303 26 115 ]tJ-27 l25 ~.:J.:~lQ 2 7 1_ ,~7 311 27 12? DAILY AVERAGE VALUES 31 '] 21-J 1 ~ 7 31':' ;"]6 11.2 31.7 26 i 1~; 31° 27 1:?1 321 27 125 323 27 1 ~'1 DAIU' AVER.~GE VALUES 32:; .~6 3'?7 26 3:;''1' 26 3'Jt 27 TJ3 27 335 27 DAILY AVERAGE ' . ",_ . t 4 1 15 1,2.::: 125 1. ,::{:' v,;,_UES 33? 26 t t ~:f 339 26 11:'> 3'1 i 26 1. p 343 27 1:::'? 345 27 1;28 347 26 12a. DAILY AVERAGE \'At.IJF:S 34" 26 351 26 :353 26 :355 26 :~57 26 359 26 DAILY A 1JERAGE: 1 t >3 113 1 :. ;J i .~ .... -. L•'!:...•-: 131 12:" 1/f,!.UES ~1\·' 5 2 5 2 ~~ 2 4 5 4 e; 4 5 3 5 2 s 2 5 2 ~ 4 5 4 ":'· 4 '5. 3 • .. j 2 •-"; <!'! ""7 2 5 4 5 4 ':': 4 '3. 3 c: '""' . .l ~~ ·~ r; :' C~ •.; 2 5 4 <. 4 •";;i :2 '5 3 'j 2 5. 2 5 :~ 5 .. 2 c; -, w. e.. 5 ;.1 e.. -. ""' r-... 05;10/85 PAGE 6 START TIME 05/17/84 04:00 DEPTH INCHES ====== 10. 4 10. 4 10 4 10. 8 10. 8 10. 8 10.6 10. 4 10. 4 10. 4 10 8 10. 8 10. 8 10.6 10. 4 10. 4 10. 4 10. 8 108 10 8 10. 6 10. 4 10. 4 10. 4 10. 8 10. 8 10. 4 10. 5 10. 4 10. 4 10. 4 10. 4 10. 4 10. 4 10. 4 STAGE FEET 0 87 0 87 0.87 0. 9:) 0 91) (\ 9':· 0 89 0 87 0 8 7 o 9-:r 0 9C! 0 90 0 9i) 0.89 0 8 ;< 0 87 0 87 0. 91.~1 090 0 co 0.89 0 87 0 87 0. 87 0 9t) 0 90 0. 8 7 0 8~1 0 87 0 87 0 87 0 87 0 87 0 8 7 o s::· DISCHG CFS ==:::::::=:::=!: 19 19 1'7 2 "1 "'-...,,.., .::::...::::. 22 21 1.9 19 19 ::;!2 ':)r") ~c. .-;..., C:<!. 21 19 1 .., . 19 22 :22 ·-\, .... .:.::..:... 21 •o k ' i9 19 22 ·>·""'"\ .. 'i.e_ !<:;' 20 19 t .;· 19 19 19 19 19 TEMP DEG C ===== 7. 5 6.0 7 5 12. 5 13. 5 11. 5 9. 8 8. 5 6 0 8 0 11. 5 12. 5 10. 5 9. 5 8 0 7. 0 7. 5 11. 0 12. 5 11. 0 9. 5 8 5 7. 5 8. 5 115 14.0 12. 0 10. 3 9.0 6. 5 9. 0 14.0 15.5 13. 5 11 3 PROPOSED TOGIAK Hl'[if,IJELC<:TRI:~ :-f:'I],)[•~T 0'5·10/85 PAGE 7 KURTLUK RIVER NEAR TOGIAK, ALI~SIA.A START TIME 05/1 7 /84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME RVTE RAW DATA t1\/ INCHES FEET CFS DEG C ======:::: ====== :::-::==:~ ======-=-:::-~~ --.,~ -· ====== ====...:,: ==:.::::::=~ ===== 06/16/84 04•00 361 26 118 ;:;; --) •...J, .-::.. 10. 4 0 87 19 9. 0 06/16/84 08:00 363 26 113 t; 1"'"\ .... ~ 10. 4 0 87 19 6. 5 06/16/84 12:00 365 26 11b S. 2 10. 4 0. 8 7 19 8.0 06/16/84 16:00 367 26 128 5 :;] 10. 4 0 8 7 19 14. 0 06/16/84 20•00 369 26 131 <::; ") .. :~ .. 10. 4 0.87 i.9 15 5 06/16/84 00:00 371 26 1..2,.., '5 ::;:! 10. 4 0 8; 19 13.0 DAILY AVERAGE VALUES 5 -~ 10. 4 0.87 19 11 0 06/17/84 04:00 3'"''~- ! ·' 26 11"" 5. 2 10. 4 0.87 19 9. 5 06/17/84 08:00 3 7 5 26 117 '5 2 10 4 0.87 1 <?' 8. 5 06/17/84 12:00 .37 ·' 26 116 5 ::;-10. 4 () 8 1.9 8. 0 06/17/84 16:00 :3?q 26 1 j7 5 ;;; 10.4 0 8? 19 8 5 06/17/84 20:00 381 27 1 t. -7' 5 4 10.8 0. 9C• 22 9. 5 06/17/8£1-00:00 38:i 27 117 5 4 10.8 0 90 22 8. 5 DAILY AVERAGE VALUES 5 3 10. 5 0. 88 ·"'Jii .-;:_ . ..., 8.8 06/18/84 04:00 38'5 26 1 15 :· 2 10. 4 08? 19 7 5 06/18/84 08:00 ]87 26 11'1 s 2 10. 4 08? 19 7.0 06/18/84 12:00 389 26 1 i 5 5 2 10. 4 0. 87 i9 7. 5 06/18/84 16.00 391 27 110 5 4 10.8 0. 90 22 9.0 06/18/84 20:00 3S'3 27 124 5. 4 10. 8 0 90 22 12. 0 06/18/84 oo·oo 30'5 26 ~ ·"')'") .;.."; .. ~:':. 5. :?. 10. 4 0 87 19 11. 0 DAILY AVERAGE VAI.UES '5. 3 10. 5 0 88 20 9.0 06/l't'/84 04:00 :]07 26 116 5 -~ 10. 4 0 8'7 19 8.0 06/19/84 08·00 :399 26 1 j 4 5. 2 10.4 0 87 19 7. 0 06/19/84 12:00 401 26 1 16 5 2 10. 4 0 87 19 8. 0 06/19/84 16:00 403 26 LJ4 ;c ·-l 10. 4 0 87 i9 12 0 . ..; ."':;.. 06/19/84 20:00 40'5 26 129 .::: --. 10.4 0.8/ 19 14. 5 ~· .. ·-:,. 06/19/84 oo·oo 407 26 125 5. 2 10. 4 0 87 19 12. 5 DAILY AVERAGE VALUES 5. ;:~ 10. 4 0.87 19 10.3 06/20/84 04:00 409 26 1 F< c ,-, ·..1 e. 10. 4 0 87 19 9. 5 06/20/8l~ 08:00 411 26 iill. 5 2 10.4 0 87 19 7.0 06/20/84 12:00 413 26 117 3 2 10. 4 0 87 19 8. 5 06/20/84 16:00 415 26 1 ;;:s 5 .~ 10. 4 0. 87 19 12. 5 06/20/84 20:00 417 26 122 '5 2 10. 4 0. 87 19 11 0 06/20/84 00:00 419 30 119 6 I) 12 0 1. 00 30 9.5 DAILY AVERAGE VALUES 5. J 10. 7 0.89 21 9. 7 PROPOSED TOGIAK HVDROELECTRTC PROJECT 0': 10/85 PAGE 8 KURTLUK RIVER NEAR TOGIAK. ALM)VA START TIME 05/17/84 04:00 DEPTH STAGE DISCHG TEMP DATE TI11E B'lTE RA~.J DATf, t"i\.l INCHES FEEf CFS DEG C -=====::==== :::.:::::::::::::: ::-::=:.·:.::._~; :::::=:::=::::!:::::!:=.::. ~ -~ -_.,_ =.:::::::::::: =~=== ::::::::::::~:::::::.::.:::: ----------- 06/21/84 04:00 421 29 llll 5 8 11. 6 0.97 ,..,.., 7. 0 ,:.'!,I' 06/21/84 08:00 423 28 111. 5. 6 11. 2 09J 24 S. S 06/21184 12. 00 425 27 115 5 4 10. 8 0. 90 22 7. 5 06/21/84 16:00 4_:;:':" 28 127 "3 6 11. 2 0. 93 24 13 5 06/21/84 20:00 429 ,.., .... ..::..t 1. 'JO 3 4 10. 8 0. 9() 22 15.0 06/21/84 00: 00 4:31 27 i 2~~ '] 4 10 8 0 9'.' :22 12. 5 DAILY AVERAGE VN.UES ~j 5 11. 1 0. 92 24 10 2 06/22/84 04:00 433 27 l20 ::'. 4 10.8 0.90 22 10.0 06/22/84 08.00 4'3;:! 26 1 • -· l : "' ,., • <"-10. 4 0 87 19 8. 5 06/22/84 12:00 4T7 27 116 5 4 10. 8 0. 9() 22 8.0 06/22/84 16:00 439 27 1 V:: '5 4 10. 8 0. 9\) 22 8 0 06/22/84 20:00 441 27 11..,. 5 4 10.8 0. 9() 22 8. 5 06/22/84 00:00 443 28 1 ic· S. 6 11 2 0.9J 24 8.0 DAILY AVERAGE VALUES 5 4 10. 8 0.90 22 8. 5 06/23/84 04.00 445 '"'0 115 s I] 11. 6 0 <:;17 .-.~ 7. 5 ""-· t;;.l 06/23/84 08:00 ll-47 30 L t.4 6.0 12. 0 1. 00 :30 7.0 06/23/84 12:00 449 30 115 b. 0 12.0 1 00 30 7. 5 06/23/84 16:00 451 31 121 6. 2 12.4 1 03 :34 10. 5 06/23/84 20:00 45'3 30 1 ::·a ·-+ 6.0 12. 0 1. 00 30 12.0 06/23/84 oo·oo 455 32 119 6 4 12.8 1. 07 37 9. 5 DAILY AVERAGE v,.;,;, UES 0 1 12. 1 1 Oi 31 9.0 06/24/84 04•00 457 34 1.15 6 8 13. 6 1 Li 45 7. 5 06/24/84 08·00 459 34 1.14 6 8 13.6 1. 1 3 45 7.0 06/24184 12:00 461 40 1l4 i3 0 16. 0 1 3] 75 7. 0 06/24/84 16:00 463 :)q 1 L7' 7 8 15.6 1 30 70 8. 5 06/24/84 20:00 465 40 i.1t: 8. (j 160 I 33 75 8.0 06/24/B4 00:00 46? 42 1.14 t;; !l 16.8 1. 40 88 7. 0 DAILY AVERAGE VALUES ~ 6 15. 3 1 27 66 7. 5 06/25/84 04:00 46'7' 40 113 8 L' 16.0 1 ")·"\ ..... J 75 6. 5 06/25/84 08:00 'l71 38 11:2 "T 6 15.2 1.. 27 64 6.0 06/25/84 12:00 47::;: '37 1 i a 7 4 14. 8 1. 2:] 59 7.0 06/25/84 16:00 47"' 36 t l ., ~ i4. 4 1. 2t) 54 8. 5 f .~ 06/25/84 20:00 477 35 118 7. Q i4 0 1 1' 49 9.0 06/25/Btl oo·oo 479 35 116 7. 0 14 0 1 17 49 8.0 DAILY AVERAGE VALUES 7 4 14. 7 1. 2J 58 7. 5 ' ~ PROPOSED TOGIAK H''I'DR:Jr:_LEt.: fR IC f'P\J.JECT 05· 10/85 PAGE 9 KVRTLV~o'. RIVER NEAR TOG I Ali" AL/>SI' A START TIME 05/17/84 04:00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW DA!t' I"'V INCHES FEE r CFS DEG C ========-===== ~.~:::::-:·~ ::=:::O::"!'::="::-::::::':·:::: :!:!!"':t=:·.:.:-====== ===== ::=:-:::·:::;=::::::::: ===== 06/26/84 04:00 481 34 t14 ~ .. 8 13. 6 1. 1.:.1 45 7. 0 06/26/84 08:00 483 34 112 6. 8 13.6 1. 13 45 6.0 06/26/84 12:00 485 34 114 6 8 13. 6 1.13 45 7.0 06/26/84 16:00 4-87 33 t 1 ° 6. /;, 13. 2 1 1 (', 41 9. 5 06/26/84 20·00 •H39 :33 12:1 6 s 13.2 1. 1 (• 41 11. 5 06/26/84 00:00 491 32 122 6. 4 12. 8 1. 0! 37 11. 0 DAILY AVERAGE VALUES 6. 7 13.3 1. 1i 42 8. 7 06/27/84 04:00 49·.::: 32 11'7 6 4 12.8 1. 07 37 8.5 06/27/84 08:00 40': 32 1 j 4 ".;. 4 12.8 i. 07 ~37 7. 0 06/27/84 12:00 4•:;•7 32 1. !.6 b 4 12.8 1. 07 37 8. 0 06/27/84 16·00 49'~' :32 i 2t~ ~ 4 12.8 1. 0 ,' 37 13 0 06/27/84 20:00 501 .32 L29 6. 4 12. 8 1. 0; 37 14. 5 06/27/84 00:00 50:1 31 l ,;: :; 6. :2 12 4 1. o:~ 34 12 5 DAILY AVERAGE VAL.VES 6 4 12. 7 1. Oij 37 10.6 06/28/84 04:00 50':i :31. i ~ R 6 2 12. 4 1. OJ 34 9.0 06/28/84 08:00 507 31 114 6 2 12. 4 1. o:·J 34 7. 0 06/28/84 12·00 5~);.~:; :31 ~ i ~ ....... 6 :2 12. 4 1 OJ 34 7. 5 06/28/84 16:00 511 31 11~ .6 2 12. 4 l. 0:3 34 9. 5 06/28/84 20:00 513 :31 120 " .-. ,. "" 12 4 1 03 34 10. 0 06/28/84 00:00 51.'5 '31 118 1'-.-. ,I C:: 12 4 i. OJ 34 9 0 DAILY r,VERAGE 'v'AL.UES 6 2 12. 4 1. OJ 34 B. 7 06/29/84 04:00 51;· ~:H 1 t~ ::,, 2 12. 4 1. 03 34 8.0 06/29/84 08:00 51c; 31 l. i 4 6. 2 12. 4 t 0:3 34 7. 0 06/29/84 12:00 521 :31 115 ~ 2 12 4 i. OJ 34 7. 5 06/29/84 16:00 523 32 1.11.:> 6 4 12 8 t. 0? 37 B. 0 06/29/84 20·00 525 32 i j9 et 4 12. 8 1. 0 ;r 37 9. 5 06/29/84 00:00 s·:.'7 31 1. j 7 f, '2 12. 4 1. 0 ~ 34 8. 5 DAILY AVERAGE VALUES 1:, :,3 12. 5 l. 04 35 8. 1 06/30/84 04:00 529 31 115 ;_) 2 12 4 1. OJ 34 7. 5 06/30/84 08:00 5:31 32 113 '=' 4 12. 8 1. 07 37 6. 5 06/30ft-j4 12: 00 5]3 3:l 1 '1.4 L>. 4 12.8 1 07 37 7. 0 06/30/84 16:00 53~ 32 1 i :" c. 4 12.8 1. 07 37 8. 5 06/30/84 20:00 s~n 32 120 I':J 4 128 1.0 37 10. 0 06/30/84 00:00 53° 31 11<:) 6 2 12. 4 1. 0:3 34 9.5 DAILY AVERAGE VALUES 6. 3 12. 7 1. 06 36 82 PROPOSED TOGIAK HYCR~ELECTRIC ~~OJECT 0:5c10/85 PAGE 10 KURTLUK RIVER NEAR ltJGIAK, AL,c\Sv.A START TIME 05/17!84 04:00 DEPTH STAG'~ DISCH(; TEMP DATE TIME GVTt RAW DArr, ~-!;./ INCHES FEET CFS DEG C ~=====:::::= ::===== ~~-~~:t:;"' :::::::::::::::::::·:~:;::.•;;!: :-::.': -··-·-======= :=::=:;:::=:::..: ====~~ ===== 07/01184 04.00 S.:lt 31 t1 ~i ..:.. ., .•• . <=~ 12.4 l. 01 34 7. 5 07/01/84 08:00 54~~ 31 j j 4 6. 2 12. 4 1. 03 34 7 0 07/01/84 12:00 545 3i 1 l ll ;... /'"'\ -·. C:~ 12. 4 1. o.:o 34 7. 0 07/01/84 16:00 'j.:F 32 123 ':;; 4 12. B 1. 0 7 ·-l'"T • .;> t 11. 5 07/01/84 2000 54•:' ~H 127 .;,. 2 12. 4 'i OJ 34 13. 5 07/01/84 00:00 551 31. j ;~':! 6. 2 12.4 1 OJ 34 11. 5 DA[LY AVERAGE VALUES !.j 2 12. 5 i. 04 ,,t:; ,.l·~ 9 7 07/02/84 04:00 ~")] 31 112 6 2 12. 4 1. OJ 34 9. 0 07/02/84 0800 557 31 ! 16 ,_ . ., ::J 1:-12. 4 1 o·:; 34 8. 0 07/02/84 12:00 5 '5: 31 117 ,s 2 12 4 1. 0.3 34 8. 5 07/02/84 16:00 l:.:i r.:-(,i ._, ::; . :31 j :;:.:l ."-, 2 12.4 1. 0:: 34 11. 5 07/02/84 20:00 5~.:> 1 31 125 6 2 12.4 1. OJ 34 12. 5 07/02/84 00:00 5'.':>3 30 1.21 6 () 12.0 1. 00 30 10. 5 DAILY AVERAGE VALUES 6. 2 12.3 1. t]j 33 10.0 07/03/84 04:00 ~·~}5 30 i t t: 6 0 12.0 1. Q:) ,30 8.0 07/03/84 08:00 56'7 30 u.a. 0. () 12. 0 1. 0() JO 7. 0 07/03/84 12:00 569 30 1 ~ .• 6 I) 12.0 1. O•J 30 8. 5 07/03/84 16:00 571 30 126 t: (; 12.0 1. O!J 30 13. 0 07/03/84 20:00 '5>'3 30 1. 2:; h 0 12.0 1 00 30 14. 5 07/03/84 00:00 57~ 30 1.25 ·> 0 120 1. 0<) .30 12. 5 DAILY AVERAGE VA~UES ":.> () 12. 0 1. O•J 30 10. 6 07/04/84 04:00 '5TT 29 11 c,: 5 f-) 11. 6 0. 9? 27 9. 5 07/04/84 08:00 5 7 9 30 1b t.. 0 12.0 1. 00 30 8.0 07/04/84 12:00 '581 30 1 i 5 6. 0 i2.0 1. 00 30 7. '5 07/04/84 16:00 ~·83 30 118 b. 0 12.0 1. 00 30 9. 0 07/04/84 20·00 585 30 118 6. I) 12.0 1. 00 '30 9 0 07/04/84 00:00 587 30 11o 6. 0 12.0 1. 00 30 8.0 DAILY AVERAGE VALUES 6 0 11. 9 1. 0:.:• :30 8. 5 07/05/84 04:00 589 29 1.15 5. 8 11. 6 0. 97 27 7. 5 07/0~184 08:00 591 29 114 c, 8 1L 6 0 91 ,..._, ,;.t 7. 0 07/05/84 12:00 5<?:3 29 115 ':'J 8 11.6 0. 9.r ·""\..., 7. 5 "'-<' 07/05/fl4 16:00 5GS 30 1 .;c:o b 0 12.0 1. OC.t 30 10. 0 07/05/84 20:00 59i" 30 124 ~. 0 12. 0 1. 00 30 12. 0 07/05/84 00:00 599 29 12.? 5 8 11. 6 0.97 27 11. 0 DAILY AVERAGE VALUES s s· 117 0. 9t:1 28 9. 2 PROPOSED TOGIAK H'r'DR~"JtLECTh'IC ;;··p,J,)lCT 0'5' 10/85 PAGE 11 KURTLUK RIVER NEAR TOGIAK. .~u~s•.,A START TIME 05117/84 04:00 DEPTH STAGE DI•3CHG TEMP DATE TIME BYl E RAW Dl-,f-" ~t"?l) INCHES FEET CFS DEG C ========= ==r:::::= ==::::~ :::::::-::====..::.~~ = ~-;': ~--=====:::: -----==:·::.::.== ==~== ---·-- 07/06/84 04:00 601 29 11? s 8 11. 6 0 07 .,., 8. 5 .:.::.: 07/06/84 08:00 603 29 115 5 8 11. 6 0. 9 7 "\'T :::::.. I 7. 5 07/06/!34 12.00 605 29 116 5 8 11. 6 0. 9 7 27 8 0 07/06/84 16:00 60.,. :30 ; , ... j "' 1'::.-f:!'-b 0 12.0 1. Q) 30 11. 0 07/06/84 20:00 609 30 l.2t_-b 0 12.0 1 0() :30 13.0 07/06/84 00:00 61 "l 29 i ~~:3 5 8 11. 6 () 9 7 27 11. 5 DAILY AVERAGE VALUES 5 9 11 7 0. 98 28 9. 9 07/07/84 04:00 613 29 1th 5 8 116 0.97 27 8. 0 07/07i84 08:00 tJi5 29 j 14 5 8 11. 6 0.97 27 7 0 07/07/84 12:00 617 29 1 i ':; 5 8 11. 6 0 97 2? 8.0 07/07i84 16:00 b19 29 1 ;;~n s 8 11. 6 0 97 27 10.0 07107184 20:00 6.21 29 1. j '? 5. 8 11. 6 0. 97 27 9. 5 07/07/84 00:00 623 29 1P 5 8 11. 6 0.97 27 8. 5 DAILY AVERAGE VALUES S. 8 11 6 0 97 -,..,. ~~ 8. 5 07/08/84 04:00 62-5 ''G ""' ' U<l 5. 8 11. 6 0. 97 27 7.0 07/08/84 oe·oo b27 29 11.3 5.8 11. 6 0 97 27 6.5 07/08/84 12:00 629 29 114 5. 8 11. 6 0. 9 7 27 7. 0 07/08/84 16:00 6]1 29 12:~ '5 8 11 6 0. 97 27 11. 5 07/08/84 20:00 6:"'·-:J _J._, 29 126 ::. 8 11. 6 0.97 27 13.0 07/08/84 00:00 6 ~lS 29 1 :J 1 5 8 116 0. 97 27 10. 5 DAILY 4VERAGE VALUES :::: 8 11. 6 0.97 27 9.3 07/09184 04:00 637 29 1.1o 5 8 116 0. 9: 27 8. 0 07/09/84 08:00 639 28 114 5 6 11. 2 0.9J 24 7.0 07/09/84 12:00 641 29 116 5 8 11. 6 0. 97 27 8.0 07/09/84 16:00 643 ~~9 122 5 8 lL 6 0. 9? 27 11.0 07/09/84 20:00 645 29 122 ·:; 8 11. 6 0. 9? 27 11 0 07/09/84 00:00 647 28 119 5. 6 11 2 0. 93 24 9. 5 DAILY AVERAGE VALUES 5 7 11. 5 0 96 2f:. 9. 1 07/10/84 04.00 649 27 1 UJ s 4 10.8 0.90 ..... .., 8.0 "'"" 07110/84 08 00 t~51 27 1t4 s 4 10.8 0. 90 22 7. 0 07/10/84 12:00 t.53 27 11.::. 5 4 10. 8 0 90 22 8.0 07/10/84 1600 655 27 119 s 4 10. 8 0 90 22 9. 5 07/10184 20:00 657 27 121 5 4 10.8 0. 90 '}-J "-"-10. 5 07/10/84 00:00 659 27 120 5 4 10.8 0 90 22 10.0 DAILY AVERAGE VALUES 5 4 10.8 0 90 22 8. 8 PROPOSED TOGIAK HYDROELECl"RIC 0ROJ£CT G3i10/8S, f'AGE 12 KURTLUK RIVER NEAR T!JGIAK. ALASv:A START TIME 05/17/84 04.00 DEPTH STAGE: DISCHG TEMP DATE TIME BVTE RAW DATA Mi\ INCHES FEET CFS DEG C ====~=:::-.; =::::::::::-:;: ==:::-:.::..-:-';:;:;:::;:;;::;:':':".'::::~=~- _, .. ___ ====== ====-= :::::::;.:;..:.::.·-::::-::-===== 07/11/84 04: 00 661 27 11.6 5. 4 10.8 0 90 ;"22 8.0 07/11/84 08:00 663 27 l.!.3 5. 4 10.8 0 90 . ., ..... 6. 5 <:::.<=. 07/11/84 12:00 665 27 i.15 5 4 10.8 0 90 22 7. 5 07/1 1/8lt 16: 00 6!:,"/' ,.,7 !21 :: 4 10 8 0 9(} ,..,,.., 10. 5 "'' r.:..<: 07/11184 20: 00 669 ""'7 122 5 4 10 8 0 90 :-,r-·, i 1. 0 c::: •• c::..r::.. 07/11184 00: 00 671 27 1.20 5 4 10. 8 0. 90 2"2 10.0 DAILY AVERAGE VALVES 5 4 10.8 0.90 .-,J-, 8. 9 (=:.e:. 07/12i84 04:00 6?3 27 11a s 4 10. 8 0. 9(1 22 8.0 07/12/84 08:00 67":. 27 1H 5 4 10.8 0. 90 22 7.0 07/12/84 12:00 677 27 116 s 4 10. 8 0 90 91 -~. 8.0 07/12/84 16·00 670 27 1 ~?4 s 4 10.8 0 90 22 12.0 07/12/84 20'00 681 27 125 5 4 10.8 0 90 22 12. 5