Snettisham Hydro Project AK Electric Light and Power Company 1997
SNETTISHAM HYDROELECTRIC PROJECT HYDROLOGY AND POWER STUDIES • ALASKA ELECTRIC LIGHT AND POWER COMPANY MARCH 1997 -- RW ·~E(K March 7, 1997 Mr. Corry Hildenbrand Vice President/Power Generation Alaska Electric Light & Power 5601 Tonsgard Court Juneau, Alaska 99801-7201 Subject: !)ear Corry: Snettisham Hydroelectric Project Hydrology and Power Studies Enclosed is our final report on hydrology and power studies for the Snettisham Hydroelectric Project. Please contact me at 206-727-4557 if you have any questions or comments regarding the report. It has been a pleasure working with you and Scott Willis on this assignment, and I would be pleased to provide continuing development of the power study model at your request Very truly yours, R.W: BECK, INC. ~ John C. Haapala, P.E. Principal Engineer JCH/ato Enclosure FILE: 12-00317-10001-0001 (0:\HAAPAlA\JCH037.DOC) 2101 Fourth Avenue. Suite 600 Se,;ttle. \VA 98121-2373 Phone 12061 441-7.)00 Fax 12061441-4962 SNETTISHAM HYDROELECTRIC PROJECT HYDROLOGY AND POWER STUDIES TABLE OF CONTENTS LEITER OF TRANSMITIAL TABLE OF CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION ••.••••••..•••....••••...••••.....•••••..•...•.••......•.••.•.••••.••.••••••.•...•••• 1 2.0 DATA REVIEW •••••••••••••••••••••.•••••••••••••••••.••••••••••••••••••••••••••••••••••••••••••••••••••• 2 3.0 RESERVOIR INFLOWS ••••••••••••••••••.••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 2 4.0 LOADS AND RESOURCES ••.••••••••••••••••••••••••••••••••••••••••••••••••••..••••••••••••••.•• 3 5.0 POWER STUDY MODEL DESCRIPTION ••••••••••••••••••••••••••••••••••••••••••••••••••• 4 6.0 POWER STUDY RESULTS ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 7.0 PRELIMINARY RULE CURVES ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 9 TABLES Table 1 -Long River Recorded Flows at USGS Gate 15034000 Table 2-Long Lake Flows-Calculated from Generation and Storage Change Table 3-Crater Creek Recorded Flows and Crater Lake Recorded Inflows Table 4-Historic and Reconstituted Long Lake Inflows. Table 5-Historic and Reconstituted Crater Lake Inflows Table 6-Combined Long Lake and Crater Lake Inflows Table 7 -AEL&P Hydro (MWh) Table 8-Juneau Area Loads (MWh) Table 9 -Snettisham Hydroelectric Project Power Study Results FIGURES Figure 1 -Snettisham Hydrology -Data Availability -Calendar Years Figure 2 -Combined Long Lake and Crater Lake Inflows Figure 3 -Comparison of Lake Levels for Water Years 1980-85-Run 2 and Run 5 Figure 4 -Preliminary Rule Curves X1642121.920 '1/27/97 TABLE OF CONTENTS APPENDICES Appendix A -Power Study Model Output-Run 2 Appendix B -Power Study Model Output -Run 6 This report has been prepared for the use of the client for the specific purposes identified in the report. The conclusions, observations, and recommendations contained herein attributed to R. W. Beck, Inc., ("R. W. Beck") constitute the opinions of R. W. Beck. To the extent that statements, information, and opinions provided by the client or others have been used in the preparation of this report, R. W. Beck has relied upon the same to be accurate, and for which no assurances are intended and no representations or warranties are made. R. W. Beck makes no certification and gives no assurances except as explicitly set forth in this report. Copyright 1996, R. W. Beck, Inc. All rights reserved. X1642121.920 2/27197 R. W. Beck jj EXECUTIVE SUMMARY The Corps of Engineers (COE) developed inflows and generation estimates for Long Lake and Crater Lake in 1964. These studies were for a 48-year period from 1916 through 1963. Updated flow data for Long Lake and Crater Lake were developed by R.W. Beck for a continuous 82-year period from 1914 through 1995. Results of the study indicate that there is little difference in the average inflows between the R.W. Beck and COE studies. A power study model was developed by Beck to estimate firm and average energy from the Snettisham Hydroelectric Project, using the updated inflows, and with generation driven by current and projected AEL&P load levels and monthly patterns. The Beck power study model included the Long Lake and Crater Lake units in detail as separate plants, with the Annex Creek, Salmon Creek, and Gold Creek hydroelectric units included in an approximate manner. The COE power studies apparently assumed that all potential generation from Snettisham would be usable. This assumption reflects the current load and generating resource situation only during the most adverse water conditions (normally considered to define the firm energy) when the full generating capabilities of Snettisham and the other existing AEL&P hydroelectric projects would be usable. Generation estimates based on the assumption that all Snettisham generation would be usable do not accurately represent current average energy generation, but do provide a theoretical upper bound to the average energy generation potential of Snettisham. With the assumption that there is demand for all of the Snettisham energy output, the Beck power studies estimate that Snettisham firm energy would be 273,000 MWh and average energy would be 323,000 MWh. All generation values presented in this summary include estimated deductions for forced and unforced outages, station service, and transformer and transmission losses. With the same assumption regarding usable generation, and adjustments for outages and losses, the Beck and COE generation results are in close agreement. The Beck studies indicate that actual generation from Snettisham will be a complex function of total AEL&P energy demand, the order of dispatch among available generating resources, and the usage of reservoir operating rule curves. At load levels equal to or greater than current levels, operating rule curves are necessary to avoid excessive drawdown of both Long Lake and Crater Lake and to maximize the Snettisham firm energy generating capability. Snettisham average generation will increase with increasing load. With a power study assumption that the existing AEL&P hydroelectric units (Annex, Salmon, and Gold Creek plants) are always dispatched before Snettisham, the Snettisham average energy estimates vary from about 270,000 MWh under current conditions (330,000 MWh load) to about 304,000 MWh under conditions projected for about 10 years in the future (410,000 MWh load). These Snettisham average energy generation estimates should be slightly on the low-side because in actual operation, it is not anticipated that Snettisham would always be dispatched last. SNETTISHAM HYDROELECTRIC PROJECT HYDROLOGY AND POWER STUDIES 1.0 INTRODUCTION The Snettisham Hydroelectric Project (Project) is currently owned by the Alaska Power Administration (APA), a unit of the U.S. Department of Energy. The State of Alaska's Alaska Power Authority, now known as the Alaska Energy Authority (AEA), has entered into a purchase agreement to buy the Project. On November 28, 1995, President Clinton signed into law a bill that authorizes the sale of the Project. A Memorandum of Understanding for sale and purchase of power has also been negotiated between the Authority and AEL&P, the purchaser of nearly all of the Project's power. The Project is located in a remote area about 28 air miles southeast of Juneau, and consists of two reservoirs (Long Lake and Crater Lake), a small periodically constructed flashboard dam, power tunnels, an underground powerhouse, switchyard, transmission line, and substation. The Project was constructed in two primary stages, Long Lake was brought on-line in 1973, while Crater Lake was brought on-line in 1990. The Long Lake and Crater Lake systems are essentially separate, except that generating equipment is housed in the same underground powerhouse. The Long Lake generating equipment consists of two units with a total installed capacity of 47 Mw. The Crater Lake generating equipment has one unit with an installed capacity of 31 Mw, for a total Project installed capacity of 78 Mw. The Project is operated by remote control from Juneau under contract with AEL&P. Hydrology and power studies for the Project are the subject of this report. An update to previous Snettisham Project hydrology and power studies is appropriate at this time because additional hydrology data exists that may refine inflow estimates. Long-term monthly hydrologic inflows for both Long Lake and Crater Lake are developed. Also, the capability of Snettisham and AEL&P hydroelectric resources to reliably meet current AEL&P loads appears to be uncertain. The capability of existing resources to meet current and future loads will be addressed in the power studies. A long-term monthly power study model is developed that includes AEL&P loads, AEL&P hydro generation, Snettisham generation, and required thermal generation. The power studies provide estimates of both the firm energy and long-term average generation available from the Snettisham Project. X1642121.9:W WfJ7 HYDROLOGY AND POWER STUDIES 2.0 DATA REVIEW Data was obtained via the Internet in electronic form. Small FORTRAN programs were written to process the data into more useable forms. USGS surface water data was obtained from the following URL address: http://h2o.usgs.gov/swr/ AK1 Precipitation data was obtained from the National Climatic Data Center (NCDC) s~: . http://www.ncdc.noaa.gov/ncdc.html A summary of hydrologic data availability is presented in Figure 1. Long River flows were recorded at USGS gaging station 15034000 for an intermittent period of over 35 years, as presented in Table 1. As presented in Table 2, Long Lake inflows have been calculated based on generation and change in storage since development of the Snettisham Project for the periods when lake elevation data was available. Recorded flow data for Crater Creek is presented in Table 3. The early Crater Creek data is at USGS gage 15038000, with the more recent data calculated in a manner similar to Long Lake since development of the Snettisham Project. All data for Crater Creek is included in one table because both the USGS gage and the calculated inflows had the same drainage area, 11.4 square miles. 3.0 RESERVOIR INFLOWS Long River flows at Long Lake and Crater Lake outlets have been previously developed based on linear regression equations by the Corps of Engineers (COE) for the Snettisham Project as described in their Design Memorandum No. 1, Hydrology, dated September 1964. Long Lake flows were developed for a total of 46 years for the periods 1916-24, and 1927-63. The estimated long-term average flow at Long Lake outlet from the COE study was 446 cfs (323,000 ac-ft/yr). Crater Lake flows were developed for a total of 49 years for the periods 1913-24, and 1927-63. The estimated long-term average flow at Crater Lake outlet was 202 cfs (146,300 ac-ft/yr). In the Revised Design Memorandum No. 26, Snettisham Project, Second Stage Development, Crater Lake Phase, dated October 1984, the COE developed a revised set of flows using HEC-4. The revised flows for Crater Lake were for a 55-year period from 1914 through 1968. The estimated long-term average flow for Crater Creek was 201 cfs (145,600 ac-ft/yr). Long Lake and Crater Lake inflows for the current study were developed using the multiple correlation model HEC-4, Monthly Streamflow Synthesis, which was developed by the Hydrologic Engineering Center, U.S. Army Corps of Engineers. Both flow data and precipitation data were included in the HEC-4 input data set. X1642121.920 wm R. W. Beck 2 SNETTISHAM HYDROELECTRIC PROJECT Flow data for Long Lake and Crater Lake was developed for a continuous 82- year period for water years 1914 through 1995. Results of the HEC-4 flow data fill-in and extension are presented in Table 4 for Long Lake, Table 5 for Crater Lake, and Table 6 for combined inflows to Long Lake and Crater Lake. It is noted that Long Lake and Crater Lake were included separately in the power study model, but combined inflows provide the best indication of wet and dry years. Combined Long Lake and Crater Lake inflows are plotted on a water year basis in Figure 2. Compared with the previous studies cited above, Long Lake long-term average inflows as developed herein are about 4% greater, while the Crater Lake inflows are about 6.5% less. Long-term average combined inflows for Long Lake and Crater Lake are less than 1% greater than for previous studies. This is considered to be a confirmation for the previously developed long-term average flows, particularly when considering combined effects. The firm energy, which is the generation that would be available during the most adverse sequence of water years, occurs in 1921, the second driest of the 82 years, which is preceded by the seventh driest year in 1920. 4.0 LOADS AND RESOURCES Approximately 80% of AEL&P's current electric energy requirements are purchased from the Snettisham Hydroelectric Project. The remainder of AEL&P's energy requirements are supplied by hydroelectric and oil-fired generating plants owned and operated by AEL&P. The utility owns and operates 6 hydroelectric generating units (3 at the Gold Creek Hydroelectric Project, 2 at the Annex Creek project and 1 at the Salmon Creek project), 4 combustion turbines, and 15 diesel powered generators located at 5 separate sites. The AEL&P system is operated as an isolated utility. The hydroelectric units at Annex Creek, Salmon Creek, and Gold Creek are the first priority for generation and are used to their full capability as much as possible. Snettisham generation is used in priority ahead of the thermal units. In recent years prior to 1996, the AEL&P thermal units were used primarily during transmission and unit outages at Snettisham. The installed capacity of the three units at the Annex and Salmon Creek Hydroelectric Project totals 7.7 MW. Based on the Annex Creek and Salmon Creek Hydroelectric Project Application for New License, as submitted to the FERC in October 1985, the expected average annual generation for the Annex Creek component is 24,200 MWh, ranging from a minimum of 21,700 MWh to a maximum of 28,000 MWh per year. As presented in the FERC license application, the average generation for the Salmon Creek component is 31,500 MWh per year. The Salmon Creek component generation can range from a minimum of 23,000 MWh to a maximum of 38,000 MWh. The total average annual generation for the Annex Creek and Salmon Creek Hydroelectric Project X1642121.920 2/i:J/97 R. W. Beck 3 HYDROLOGY AND POWER STUDIES is 55,700 MWh. The total annual generation would range from a minimum of 44,700 MWh to a maximum of 66,000 MWh. Based on actual generation for the Gold Creek Hydroelectric Project for water years 1986 through 1996, the estimated average annual generation is 5,387 MWh, with a maximum of 6,667 MWh and a minimum of 4,152 MWh per year. Based on the foregoing data, total generation for all of the AEL&P existing hydroelectric is estimated to average 61,100 MWh per year, and will range from a minimum of 48,900 MWh to a maximum of 72,700 MWh per year. Actual generation for water years 1986 through 1996, as presented in Table 7, generally confirms the average generation and range of expected generation for the AEL&P hydroelectric projects. Although the Snettisham Project provides about 80% of AEL&P current loads, a simulation of the capability of the Snettisham Project to meet current and future loads should account for AEL&P's existing hydroelectric resources with some reasonable accuracy. The monthly and year to year variation of AEL&P's existing hydroelectric resources will affect required generation from the Snettisham Project. The Gold Creek Hydroelectric Project and the Annex Creek and Salmon Creek Hydroelectric Projects are not included in the power study model in a detailed manne4 but were included approximately as a pattern of monthly generation based on historic generation. The AEL&P hydroelectric projects annual generation, within the range of expected generation, is based on the relative magnitude of hydrologic inflows at Long Lake for the corresponding year. This incorporates a reasonable assumption that wet years and dry years occur concurrently over several watersheds in the Juneau vicinity. Annual generation is then distributed to monthly generation based on the historically observed pattern of average generation for the individual projects. Total AEL&P generation for 1996 has been about 327,000 MWh, with requirements at the load center estimated to be 322,000 MWh. The monthly distribution of the historic recorded loads for water years 1986 through 1996 are as shown in Table 8. Assuming a load growth of 2.5% per year, total load in 5 years (year 2001) would be 365,000 MWh. In 10 years (year 2006) total load would be 410,000 MWh, with a continued load growth of 2.5% per year. The monthly loads used for alternative power study model runs are also presented in Table 8. 5.0 POWER STUDY MODEL DESCRIPTION A monthly reservoir operation and power study model written in FORTRAN was developed for the Snettisham Hydroelectric Project based on Beck's standard reservoir power model routines. Long Lake and Crater Lake were modeled separately, with a basic operation assuming that the two lakes would be drawn down in proportion to each other. The model was developed with the intention of providing flexibility to accommodate possible future detailed inclusion of X1642121.92D R. W. Beck 4 SNETTISHAM HYDROELECTRIC PROJECT AEL&P's existing hydroelectric resources, or the future addition of potential new hydroelectric resources such as the Lake Dorothy Hydroelectric Project. The current power study model differs from previous models in that it does not appear that previous models accounted for both Long Lake and Crater Lake separately in the same model, nor did previous models account for the effects of existing AEL&P hydro generation on Snettisham Project generation. It is unclear whether previous studies developed usable energy at Snettisham in response to monthly loads as is done in the current study. These differences may in part account for some variation between previous and current generation estimates. The power study model assumption was to dispatch the Snettisham Project to meet the monthly loads after all of the AEL&P hydroelectric generation has been utilized. This simplifying assumption will result in Snettisham average energy generation estimates that are slightly on the low side because in actual operation, it is not anticipated that Snettisham would always be dispatched last. AEL&P existing hydro resources are included in an approximate manner. It is assumed that during years in which Snettisham inflows are relatively low, generation from the AEL&P hydroelectric projects will also be relatively low, with a corresponding situation during average and high water years. Thermal resources are assumed to bring total generation up to the monthly load, after all hydroelectric resources have been utilized. The basic operation makes withdrawals from Snettisham Project storage to meet loads without utilization of rule curves. This operation should demonstrate if the Snettisham Project can operate effectively at future loads without rule curves. An alternative operation assumed that all Snettisham potential generation would be usable. Input to the model consisted of monthly loads, monthly inflows, an elevation- capacity table each for Long Lake and Crater Lake, desired minimum reservoir level (rule curve). Other project characteristics and input parameters are as summarized in the following table: Xl642121.920 wm R. W. Beck 5 HYDROLOGY AND POWER STUDIES Parameter long Lake Crater Lake On-line date 1973 1990 Drainage area 31.9 sq. miles 11.4 sq. miles Maximum normal pool El824 El1,019 Minimum normal pool El703 El825 Average net head (design) 745 feet 945 feet Natural lake elevation El815 El1,019 Storage at maximum normal pool 360,000 ac-ft 120,000 ac-ft Storage at minimum normal pool 213,000 ac-ft 38,500 ac-ft Active storage 147,000 ac-ft 81,500 ac-ft Minimum releases at reservoir outlet None None Spillway Concrete weir at El818 Natural outlet Flashboards (wood) Crest at El824 None Tunnel type 13.5-ft modified 11-ft modified horseshoe, drill and horseshoe, drill and blast, unlined blast, unlined Tunnel length 8,445 feet 6,275 feet Penstock diameter 8.5 feet 6 feet Penstock length 922feet 846 feet Head losses 19 feet at 540 cfs 19.5 ft. at 450 cfs Turbines 2 vertical axis Francis 1 vertical axis Francis Tailwater level Eltl.O Elll.O Turbine hydraulic capacity 540 cfs each at 750ft. 450 cfs at 950ft. head head Turbine efficiency (est.) 90% avg. 90% avg. Installed capacity 47MWtotal 31MW Generator efficiency 97% avg. 97% avg. Transformer efficiency 99% 99% Station service (est.) 0.5% 0.5% Energy loss due to forced and 3% 3% unforced outages (est.) Transmission line losses 2% 2% Reservoir evaporation was not explicitly included in the power study model because it is very small and would already be accounted for in the available flow records. Output from the model for each month included: • net energy (MWh) from Crater Lake, Long Lake total, and Snettisham Project total • generation at existing AEL&P hydroelectric projects • required thermal generation • total generation from all resources • Long Lake and Crater Lake end-of-month elevations • Long Lake, Crater Lake, and combined storages • tunneVpenstock flows to Long Lake and Crater Lake units • spill at Long Lake and Crater Lake X1642121.920 2/0197 R. W Beck 6 SNETIISHAM HYDROELECTRIC PROJECT • flow through each of the units • static and net head on each unit • net power (MW) from each unit and three units combined • water balance each for Long Lake and Crater Lake Accuracy of model results is considered to be adequate for the purposes of the current study. The accuracy of model results could be improved primarily in several ways: (1) by including the existing AEL&P hydro resources in a detailed manner (similar to Long Lake and Crater Lake, providing potential for coordinated operations); (2) by using a daily (possibly even hourly) time increment to increase the simulation accuracy of spill, head losses, turbine efficiency, and load variation; (3) by dispatching units in an expected manner; and (4) by including reservoir operating rule curves. 6.0 POWER STUDY RESULTS 6.1 PARAMETER VARIATION BETWEEN RUNS Results of the power study runs are presented in Table 9. The parameter varied between runs was primarily the annual AEL&P base load. In Run 1 through Run 5, Snettisham generation was limited to that required to meet the load. In Run 6 and Run 7, all Snettisham potential generation was assumed to be usable, regardless of the monthly base loads. Run 7 assumes that the maximum normal operating level of Long Lake is at El 818 (no flashboards), all of the other runs assume the Long Lake maximum normal pool level is at El824. 6.2 fiRM AND MINIMUM ANNUAL ENERGY Table 9 reports minimum energy results rather than firm energy. This is because minimum annual energy varies between runs, but the Snettisham firm energy would remain the same under all conditions. Firm energy is defined as the generation available under the most adverse hydrologic conditions. Run 2 and Run 6 illustrate that the firm energy available from Snettisham would be 273,000 MWh (179,000 MWh from Long Lake and 94,000 MWh from Crater Lake), which occurs in water year 1921. The results show that at current AEL&P load levels, all of the firm energy would be usable. With 273,000 MWh firm energy from Snettisham and an estimated 49,000 MWh minimum energy from the AEL&P existing hydro resources, the hydro system firm energy can be estimated as 322,000 MWh. Detailed power study model output is presented in Appendix A for Run 2, and Appendix B for Run 6. For a lower annual load (Run 1), and with the assumption that Snettisham is dispatched last, Snettisham minimum annual generation occurs in the year of highest flow, when the AEL&P hydro resources are at maximum generation. For Run 2, where generating capabilities are about equal to the load, the minimum X1642121.920 2/0/)7 R. W. Beck 7 HYDROLOGY AND POWER STUDIES annual energy and the firm energy are the same. In Run 3 through Run 5, the minimum energy decreases with increasing load because, without the inclusion of rule curves, the reservoirs may be emptied to minimum pool for several consecutive months. The effect of increased drawdown with higher loads is illustrated in Figure 3 for a period of years that includes the minimum annual energy generation. Runs 3 through 5 do not represent recommended operations, they merely demonstrate the need for rule curves. One of the more significant results of the power studies is that loads and the total hydroelectric system firm energy capabilities are currently about equal. Under 1996 loads (Run 2 -322,000 MWh) the hydro system is capable of meeting load in all 82 years of simulation. However, with a load growth of 2.5% to 330,000 MWh (Run 3) as projected for 1997, the hydro system fails to meet load in 3 of the 82 years. After 10 years of load growth (Run 5-410,000 MWh load) the hydro system fails to meet load in 76 of the 82 years. 6.3 AVERAGE ANNUAL ENERGY As shown in Table 9, average annual generation from the Snettisham Project varies with the total load. Snettisham is capable of higher average annual generation in response to higher loads. Average generation can be increased at higher loads by reducing spill and routing more flow through the turbines. At an annual load near current levels, Snettisham generation would be about 270,000 MWh per year. However, this estimate should be on the low-side because in actual future operation, Snettisham would not always be dispatched last. Run 6 illustrates that average annual potential generation from Snettisham can be as high as 323,000 MWh. However, generation estimates based on the assumption that all Snettisham generation would be usable do not accurately represent current conditions, but do provide a theoretical upper bound to the average energy generation potential of Snettisham. 6.4 COMPARISON WITH PREVIOUS STUDIES Previous studies had estimated the Snettisham annual firm energy as 284,000 MWh, expressed as generator output. Including a 4% to 5% deduction to account for losses and outages, the previous Snettisham firm energy results are essentially the same as the current firm energy results of 273,000 MWh. Long Lake firm energy was previously estimated as 179,000 MWh and Crater Lake firm energy was previously estimated as 105,000 MWh. The net firm energy estimates from the current studies are 179,000 MWh from Long Lake and 94,000 MWh from Crater Lake. Compared to previous studies, the results presented in Table 9 generally indicate lower average energy from the Snettisham Project. Previous studies had estimated Long Lake average generation as 216,000 MWh and Crater Lake average generation as 121,000 MWh, for a total Snettisham average generation of 337,000 MWh, expressed as generator output. Including the existing AEL&P X1642121.920 R. W. Beck 8 SNETTISHAM HYDROELECTRIC PROJECT hydro resources as the first priority of usage and limiting generation to a given load level are the primary reasons that lower average generation. With the same assumption regarding usable generation, and adjustments for outages and losses, the Beck and COE average annual generation results are in close agreement. 7.0 PRELIMINARY RULE CURVES Results of the studies indicate that consideration of rule curves for Long Lake and Crater Lake is warranted. The purpose of rule curves would be to limit excessive reservoir drawdown and to maximize the firm energy available from the hydroelectric system. However, it is possible that adherence to rule curves designed to maximize system firm energy will also cause hydro system long- term average energy to be lower. Preliminary rule curves intended to maximize hydro system firm energy are presented on Figure 4. The indication is that if lake levels drop below the rule curves, other hydroelectric resources or thermal generation should be used. The preliminary rule curves were derived from the lake levels in Run 2 during the most critical drawdown period. Run 2 levels were used because this was the run that developed the maximum system firm hydro energy. It is emphasized that the rule curves presented in Figure 4 are preliminary. Additional studies should be performed to determine the effects of the rule curves on average and firm generation, required thermal generation, and to optimize the shape of the rule curves for their stated objectives. X1642121.920 W/97 R. W. Beck 9 R.W. Beck LONGH41N.XLS 2127197 Table 1 -Long River Recorded Flows at USGS Gage 15034000 Drainage Area 32.5 square miles Values are in acre-feet Ye.lli ~n Feb Mar Aru M<!y Jun .!!.!! Aim fum Qg! NQY. .Qru:; I.Q.1g1 1915 ~-----------------------------32,400 8,090 6,040 1916 3,070 2,840 3,070 7,680 15,600 51,400 52,600 65,800 61,900 37,200 8,630 5,310 315,100 1917 5,390 7,220 3,190 3,960 20,600 41,400 61,200 79,300 54,900 40,100 39,300 5,820 362,380 1918 6,000 2,280 1,600 4,230 18,400 44,300 65,800 75,000 63,100 31,000 20,400 11 '1 00 343,210 1919 12,900 3,050 3,070 7,440 19,000 32,400 53,100 64,600 59,500 32,300 11,400 7,870 306,630 1920 11 '1 00 5,450 2,800 3,090 14,400 34,500 56,400 73,800 38,100 23,400 15,600 3,690 282,330 1921 4,180 5,280 4,240 6,550 23,900 42,500 52,300 52,700 42,100 42,300 12,400 17,100 305,550 1922 5,600 1,670 1,540 6,900 24,900 42,000 56,100 64,600 49,300 29,300 31.100 6,400 319,410 1923 3,810 4,720 7,190 11,000 26,800 43,100 57,200 59,800 67,800 34,600 31,000 13,600 360,620 1924 4,800 2,880 5,530 8,030 35,400 54,100 71,900 64,600 64,300 1926 ----------------------------------------30,400 19,900 17,200 1927 ---------------53,100 59,000 59,400 57,100 21,300 7,500 3,070 260,470 1928 11,400 7,880 7,440 13,000 34,100 48,500 66,400 54,500 49,400 32,300 21,700 19,400 366,020 1929 12,100 2,380 6,460 4,940 21,400 49,200 54,400 51,400 44,900 66,400 28,900 8,860 351,340 1930 1,230 2,500 3,690 8,090 19,500 42,400 55,300 66.400 48,800 33,700 33,300 20,200 335,110 1931 9,350 14,700 3,180 7,380 30,100 57,200 58,700 67,000 48,900 42.400 10,800 5,190 354,900 1932 3,380 3,160 3,690 6,430 22,000 45,000 50,500 53,900 58,000 41,100 7,260 4,530 298,950 1933 2,770 2,220 2,540 17,900 33,100 1951 ------------------------------19,080 7,680 5,590 1952 2,340 2,190 3,050 8,920 27,010 43,640 64,150 58,900 65,660 69,110 26,480 7,440 378,890 1953 3,550 3,730 2,970 5,050 35,160 56,130 57,150 62,600 52,420 55,910 8,510 8,570 351,750 1954 4,360 15,280 3,670 2,980 19,750 44,840 50,180 38,770 54,070 28,650 27,980 22,510 313,040 1955 5,450 3,050 3,690 3,990 17,590 39,870 63,690 70,400 50,290 20,760 12,600 3,380 294,760 1956 1,840 1,730 2,460 4,170 30,090 35,170 62,770 83,160 39,720 22,990 25,850 21,340 331,290 1957 7,530 2,500 2,150 5,180 29,010 47,690 51,030 49,640 60,950 36,100 26,710 7,320 325,810 1958 11,880 3,890 3,070 8,900 33,750 62,080 60,200 60,840 31,510 45,990 15,110 8,770 345,990 1959 4,300 3,890 3,690 5,910 26,230 53,880 74,390 55,040 34,680 34,820 16,300 12,350 325,480 1960 5,600 3,140 4,410 8,730 29,040 41,960 64,170 59,820 58,280 50,320 19,990 17,940 363,400 1961 7,980 7,030 6,160 12,000 31 '170 60,520 83,520 91 '130 42,780 58,950 12,180 3,430 416,850 1962 11,230 4,340 5,630 5,070 18,750 47,420 55,430 51,200 65,610 36,400 24,160 18,490 343,730 1963 8,900 11,920 6,700 6,850 23,840 44,030 58,110 46,540 73,630 46,170 7,580 13,420 347,690 1964 7,700 6,220 4,270 9,300 19,190 59,050 73,840 52,410 29,110 42,540 16,200 12,560 332,390 1965 13,920 6,590 7,710 6,500 15,350 41.140 53,390 53,950 35,010 56,790 9,250 6,910 306,510 1966 3,210 2,510 4,010 7,720 23,540 47,530 57,150 64,940 66,220 43,670 13,570 3,380 337,450 1967 3,130 3,070 2,800 2,840 23,730 68,940 53,180 67,600 78,640 24,500 21 ,560 7,490 35 7,480 1968 3,640 7,730 13,560 6,540 26,680 38,910 55,460 41,360 76,070 24,680 10,570 5,690 310,890 1969 1,620 1,370 3,430 6,670 30,160 69,330 73,570 113,700 113.700 62,520 11,880 1,350 489,300 1970 354 218 518 1,120 60,240 76,830 56,570 57,450 42,000 55,520 17,430 2,340 370,590 1971 3,660 2,330 1,620 4,050 17,370 43,110 60,880 73,450 49,970 26,760 9,320 4,060 296,580 1972 1,040 575 1,200 762 5,960 3,410 1,940 37,070 45,760 37,830 8,900 3,930 148,377 1ill 3.020 ll9Q 2,700 ~ 21.430 .3..8.....6.3Q ~ ~ 40.240 Average 5,766 4,455 4,019 6,625 24,979 47,168 58,272 62,471 54,444 38,691 17,292 9,306 333,488 R.W. Beck 2/27/97 Year 1985 1986 1987 1988 1989 1990 1991 1992 1993 1995 1.9..9.2 Average Jan ----- 9,620 10,850 4,460 9,300 5,967 ----- 9,638 ____ .. ____ .. ----- 8,306 LONGH41N.XLS Table 2 -Long Lake Inflows -Calculated From Generation and Storage Change Drainage Area = 31.9 square miles -Values are in acre-feet Ee.b. Mar .8ru May J.un J.ul Aug Sep Q.c_t Jirul ~ Total ----------------------------------------24,880 3,480 19,980 11,080 11,880 9,480 22,150 49,160 52,950 54,550 23,220 85,000 18,500 13,485 361,075 6,871 6,705 12,246 28,882 44,581 51,875 38,960 73,693 58,000 22,800 8,350 363,813 9,980 7,290 9,217 27,314 42,008 50,974 54,781 76,000 80,000 17,900 9,790 389,714 ---.--4,030 7,990 38,180 41,520 50,210 42,390 50,980 32,120 20,371 19,181 4,113 7,669 11,186 27,710 46,292 69,229 65,590 72,000 -----_,.. ___ __ ,.. __ --------------- ----- ----------9,137 9,662 18,054 12,035 11,586 31,940 -----12,298 27,681 -------------------------34,163 34,868 60,155 28,447 2,747 ----------12.857 25.667 42.332 40.177 52.927 10,020 8,268 10,858 28,691 44,316 49,940 49,152 59,341 51,408 13,562 13,408 347,268 R.W. Beck October 1 996 Water Y.eM ~ 1913 ----- 1914 16,000 iJiC 1Q.?(l0 1916 11,400 1917 16,600 1918 15,400 1919 12,400 1920 12,900 1921 8,610 1922 1923 12,400 1924 ----- 1927 ----- 1928 8,300 1929 11,900 1930 28,500 1931 13,800 1932 20,500 1933 19,400 1990 ----- 1991 ----- 1992 ----- 1993 11 ,841 1995 ----- ~ ----- Average 14,947 Table 3 -Crater Creek Recorded Flows and Crater Lake Recorded Inflows Drainage Area = 11 .4 square miles -Values are in acre-feet Nov Dec Jan Feb Mar Apr M.Q¥ Jun Jul Aug ---------------2,610 2,970 3,410 12,500 31,600 51,000 52,800 6,430 2,350 1,290 2,500 2,260 3,140 8,850 16,200 31,800 25,100 6,190 1,470 2,220 955 2,740 4,400 14,400 24,600 30,600 28,800 ? I';}() L,U.3G 1 110 1,040 1 '170 2,620 5,530 22,000 22,800 28,500 3,050 2,010 2,150 2,470 1.380 1,420 8,730 18,100 27,100 33,100 14,900 2,150 2,040 933 781 1,23u 7,930 ?0,600 29,600 36,300 7,910 4,020 4,210 811 738 2,800 7,260 12,900 25,600 31.400 3,990 2,770 6,150 2,010 984 1 '190 3,280 10,500 25,000 32,700 5,460 1,520 -------------------------18,100 24,500 22,100 9,400 2,500 -------------------------17,700 27,800 29,700 -----------------------------------23,800 35,900 34,800 -----------------------------------20,800 23,200 22,000 2,660 1,540 5,450 1,770 2,460 2,520 11 ,900 22,700 32,500 23,200 6,720 5,040 4,670 1,060 3,030 1,740 5,650 22,700 25,800 24,800 13,200 3,700 301 500 904 2,050 6,400 18,300 25,800 29,800 15,200 8,980 4,190 5,660 1,370 2,700 13,000 23,900 25,600 29,100 4,330 1,700 1,230 1 '150 922 1,960 6,460 16,900 2,230 22,500 2,510 1,630 ---------------3,940 1,526 7,089 13,705 21,249 21,226 23,329 4,299 2,649 -----3,024 1 ,251 10,072 6,363 21,876 24,110 28,824 2,975 2,384 3,428 8,618 4,416 7,544 13,466 23,11 7 27,967 22,849 7,554 6,147 3,192 4,087 2,009 4,911 16,397 17,639 6,802 23,488 ----------1,864 1,487 3,828 6,995 13,032 17,622 24,378 19,420 -------------------------3.710 6.436 18.310 18.379 22.394 - 6,636 3,033 2,900 2,479 1,930 3,763 9,542 20,053 25,639 28,131 Note: Data for 1913 through 1933 is for USGS gage 15038000, Crater Creek. Data since 1990 is calculated based on Project operations. CRATH41N.XLS Sep Total 29,200 15,800 131 '720 23,100 1 58,675 28,000 128,870 21,500 137,610 24,500 156,364 25,000 135,049 15,600 117,074 29,900 34,600 20,900 20,400 1 35,400 20,600 133,710 21,400 1 50,855 21,500 165,000 25,500 105,382 19,937 124,004 6,104 22,419 141,470 H4FLOW2.XLS 'Lw Qld 1914 74,680 1915 36,020 1916 32,956 1917 36,513 1918 39,360 1919 30,428 1920 31,704 1921 22,968 1922 41,519 1923 28,759 1924 33,961 1925 35,672 1926 18,249 1927 29.839 1928 20,907 1929 31 '704 1930 65,174 1931 33,078 1932 41,617 1933 40,341 1934 27,153 1935 31,621 1936 30,844 19:)7 41,622 1938 78,944 1939 39,829 1940 64,011 1941 45,274 1942 31,625 1943 59,107 1944 67,668 1945 40,622 1946 74,629 1947 31,601 1948 37,734 1949 35,316 1950 28,487 1951 16,041 1952 18,728 1953 67,834 1954 54,878 1955 28,121 1956 20,377 1957 22,566 1958 35,434 1959 45,141 1960 34,177 1961 49,391 1962 57,862 1963 35,728 1964 45.318 1965 41,755 1966 55.742 1967 42,864 1968 24,048 1969 24,224 1970 19,629 1971 45,233 1972 26,599 1973 37,049 1974 28,781 1975 62,805 1976 29.044 1977 30,889 1978 35,519 1979 61,568 1980 72,621 1981 53,194 1982 37,496 1983 29,200 1984 37,392 1985 36,692 1986 24,880 1987 85,000 1988 58,000 1989 80,000 1990 32,120 1991 33,732 1992 42,087 1993 29,97~ 1994 40.'7. 1Jlll.!j, _g?.Q· Average Maximum Minimum 4C 7 8!" 0 I 1' ,( NmL 23,555 17,112 7,727 8,471 38,574 20.023 11.190 15,312 12,171 30,526 30,428 20,687 25,304 19,533 7,362 21,299 28,366 32,685 10,601 7,126 31,789 18,65; 12,40: 34,08 12,25 13,77 31,3'• 14,11 18,9• 19,9 2 23,6 19,1 8 5,f ·6 26,' •9 22, 1 3 18, :3'~ 35 gj 7. 61 7 31 25 9 8 5 27 6. 12 J67 25 173 2< 217 1• a:·1 1! 9~9 1' .6:n 1 .9•;5 2 ,714 ·,.<40 1 .;.~}01 J,<,79 3, ;19 1,162 () J75 1 110 7 660 0 089 ~ 795 ,( 724 a 012 I. 460 1! 585 236 416 1 •.163 L.146 ~li.922 5,007 8,433 4,500 3,460 16,500 22,800 17,900 20.371 3,111 9,137 12,492 23,378 -~ 17,245 38,574 3,111 a·.lle 4 ~ 10 563 7 859 1:.,374 '• 212 713 1'>,895 1,725 3,622 '6,784 6,282 3.349 6,544 •4,813 :6.682 3,013 :9,042 8,696 19,827 5,094 4,446 7,213 13,968 14,382 15,029 14,484 14,457 14,858 10,261 13,483 13,129 15,029 7,401 1,048 3,403 14,819 9,867 10,370 1,982 5,487 7,303 8.412 22,094 3,318 20,946 7,185 8,608 12,122 17,609 3,367 18,149 13,172 12,326 6,782 3,318 7,352 5,585 14,967 4,642 4,919 2,050 1,247 14,203 7,657 13,535 416 13,661 13,267 8,578 2,507 1,276 1,919 7,317 19,980 13,485 8,350 9,790 19,181 5,656 9,662 7,948 13,845 ~ 9,891 22,094 416 Historic and Reconstituted Long Lake Inflows (acre-feet) Drainage Area = 31.9 square miles Jiu:! 3,243 6,232 3,013 5,290 5,889 12,662 10,895 4,103 5,497 3,740 4,711 5,372 15,037 6,108 11,190 11,877 1.207 9,177 3,318 2,719 4,760 1,979 3,986 4,928 6,823 9,772 3,917 2,206 6,229 6,151 19,051 5,713 4,145 5,140 7,906 5,237 2,240 2,079 2,297 3,484 4,280 5,349 1,806 7,391 11,661 4,221 5,497 7,833 11,023 8,736 7,558 13,663 3,151 3,072 3,573 1,590 3,792 6,395 5,050 5,720 5,080 4,008 7,336 6,773 5,764 2,918 4,305 12,292 5,199 6,446 11,118 9,403 9,620 10,850 4,460 9,300 5,967 3,868 9,638 7,015 6,283 ~ 6,268 19,051 1,207 &Q 3,982 2,799 2,788 7.087 2,238 2,994 5.349 5,163 1.639 4,633 2,827 3,305 9,966 1,908 7,735 2,336 2,454 14,429 3,102 2,179 4,205 1,304 2,512 2,503 5,542 3,775 3,145 1.506 3,333 9,501 6,421 6,821 5,706 2,134 3,249 1.178 2,692 5,284 2,150 3,661 14,998 2,994 1,698 2,454 3,618 3,818 3,082 6,900 4,260 11,700 6,105 6,468 2.464 3,013 7,587 1,345 4,254 3,238 3,410 4,839 3,663 2,099 5,255 2,935 4,272 2,071 2,491 6,231 4,764 2,147 7,510 13,152 11,080 6,871 9,980 3,798 4,113 13,350 16,054 19,228 2,835 ~ 5,036 19,228 1,178 Mar 5,408 8,123 3,013 3,131 1,570 3,013 2,748 4,162 1,512 7,057 5,428 2,024 6,959 2,531 7,303 6,341 3,622 3,121 3,622 2,493 1,866 2,379 4,017 3,272 11,340 4,025 2,086 2,510 2,993 7,380 4,874 3,777 6,280 4,895 1,813 3,418 2,592 7,032 2,994 2,915 3,602 3,622 2,415 2,110 3,013 3,622 4,329 6,046 5,526 6,576 4,191 7,568 3,936 2,748 13,310 3,367 6,313 2,402 7,752 3,639 6,293 5,999 2,872 2,943 6,690 4,828 2,998 4,546 4,825 1,638 3,586 10,033 11,880 6,705 7,290 4,030 7,669 3,309 12,035 8,160 5,439 ~ 4,617 13,310 1,512 Mlr 6,972 12,675 7,538 3,887 4,152 7,303 3,033 6.429 6,773 10,797 7,882 1,778 4,000 8,939 12,760 4,849 7,941 7,244 6,311 17,570 6,578 6,958 8,370 8.079 8,196 7.156 11,210 8,903 2,947 4,536 11,522 6,196 6,311 12,508 2,578 6,218 4,519 5,795 8,755 4,957 2,925 3,916 4,093 5,064 8,736 5,801 8,569 11,778 4,976 6,724 9,128 6,380 7,577 2,788 6,419 6,547 7,784 11,997 3,893 11,210 5,709 7,008 9,808 12,859 7,467 3,465 11,346 7,474 7,096 6,307 10,122 10,233 9,480 12,246 9,217 7,990 11,186 13,994 11,586 12,298 12,611 ~ 7,773 17,570 1.778 Mlb' 21,971 34,329 15,312 20,220 18,060 18,649 14,134 23,459 24,440 26,305 34,746 14,921 26,325 19,920 33,470 21,005 19,140 29,544 21,594 32,489 24,075 23,492 36,803 21,743 31,194 27,187 20,032 21,707 20,763 33,946 36,196 30,394 27,479 28,046 30,623 27,322 14,504 32,906 26,511 34,511 19,385 17,265 29,534 28,474 33,127 25,746 28.504 30,595 18,404 23,400 18,836 15,067 23,105 23,292 26,187 29,603 26,543 31,369 22,692 26,229 16,898 25,212 21,662 24,435 23,818 32,691 26,449 24,511 26,943 17,726 25,814 29,113 22,150 28,882 27,314 38,180 27,710 24,587 31,940 27,681 34,352 ~ 25,718 38,180 14,134 .!l.!r! 45,526 52,815 50,451 40,636 43,482 31,802 33,863 41,715 41,225 42,304 53,101 43,173 51,786 52,120 47,605 48,292 41,617 56,144 44,169 36,562 53,375 34,204 47.393 69,568 45,148 41,192 43,722 48,661 44,783 49,443 46,609 56,415 49,428 53,864 60,091 40,973 38,526 62.577 42,834 55.094 44,012 39,134 34,521 46,810 60,934 52,885 41,185 59,403 46,545 43,217 57,960 40,380 46,653 67,667 38,192 68,050 45,187 42,732 38,765 42,399 39,837 42,015 37,164 43,962 44,766 41,481 46,195 36,159 50,455 55,371 55,362 33,460 49,160 44,581 42,006 41,520 46,292 54,278 48,041 46,630 50,433 ~ .!li1 78,588 71,405 51,629 60,070 64,585 52,120 55,359 51,334 55,064 56,144 70,573 50,991 47,833 57,911 65,174 53,396 54,279 57,616 49,568 44,805 51,091 71,329 62,216 52,478 50,801 67,636 57,709 81,340 55,537 103,759 51,977 71,159 56,518 55,237 62,051 55,109 47,909 47,733 62,966 56,095 49,254 62,514 61,611 50,088 59,089 73,017 62,985 81,978 54,407 57,037 72,477 52,404 56,095 52,198 54.436 72,212 47,759 64,277 49,369 54,084 55,129 60,324 61,848 58,256 44,379 71,067 75,912 55,221 43,991 51,235 48,382 60,505 52,950 51,875 50,974 50,210 69,229 66,768 60,609 41,802 57,408 __M..lli 46,699 58,276 69,568 103,759 31,802 34,163 R.W. Beck October 1996 &!9 68,870 61,863 64,585 77,836 73,615 63,407 72.438 51,727 63,407 58,696 63,407 63,317 40,384 58,303 53.494 50.451 65,174 65,763 52,905 59,327 76,412 69,983 56,856 .sw· 39,505 62,849 60,757 53,866 61.935 58,402 37,397 41,323 48,390 66,548 63,113 39,397 44,370 56,046 48,488 44,071 47,899 47,997 56,929 34,940 46,426 38,430 59,665 59,942 75,298 51,311 65,805 87,339 50,297 70,534 60,497 40,576 41,094 58,747 65,942 63,189 49.968 63,265 30,192 49,782 50,701 58,873 4 7,454 47,950 56.474 55,157 64,723 57,411 47,727 49,214 51,247 38,615 41.438 57,813 64,448 61,444 51,452 38,054 53,072 69,100 49,362 81,625 38,987 48,724 59,825 59,717 30,928 54,024 34,040 58,716 57,204 89,448 41,990 50,255 64,399 45,681 72.271 51,442 28,573 52,954 34,364 63,741 64,997 66,352 77,188 40,596 74,666 70,219 41,959 58,627 65,228 59,676 42,592 60,896 65,025 91.427 39,245 56,484 43,019 60,143 66,541 59,931 54,146 62,911 50,228 42,179 51,605 44,071 56,912 62,928 40,349 72,120 56,593 40,441 44,361 71,893 68,119 62,919 30,042 68,632 90,623 54,550 23,220 38,960 73,693 54,761 76,000 42,390 50,980 65,590 72,000 83,574 81,532 61,672 53.710 44,017 69,226 45,936 81,345 ~~ I<11lll 382,663 394,081 313,143 322.239 359,173 311,698 285,835 271.337 318,421 341,791 383,526 287,181 305,026 330,040 318,501 314,663 345,569 376,625 298,830 287,017 334,963 314,304 339,447 368,543 381,644 366,435 363,032 318,141 325,334 420,101 376.416 348,091 342,957 327,351 363,517 306.537 267,586 268,852 302,521 374,741 301,225 330,934 292,352 319,845 339,859 325,754 332,369 422,592 332,979 352,933 322,200 299,232 343,322 357,819 317,528 335,076 321,793 332,233 298,479 330,686 272,664 379,269 301,403 325,311 275.111 349,149 374,024 355,065 285,000 316,365 302,599 373,663 292,430 391,646 371,174 356,088 381,428 387,759 368,171 326,471 374,042 ~ 59,337 91.427 34,868 53,705 335,486 90,623 422,592 23,220 268,852 H4FLOW2.XLS Table 5 -Historic and Reconstituted Crater Lake Inflows (acre-feet) Drainage Area = 11 .4 square miles :r:.wn ~ 1914 16,000 1915 19,200 1916 11,400 1917 16,600 1918 15,400 1919 12,400 1920 12,900 1921 8,610 1922 14,637 1923 12,400 1924 13,527 1925 16,027 1926 9,846 1927 15,829 1928 8,300 1929 11,900 1930 28,500 1931 13,800 1932 20,500 1933 19,400 1934 11,624 1935 16,978 1936 11,457 1937 30,647 1938 24.211 1939 13,295 1940 18,489 1941 20,450 1942 13,557 1943 14,701 1944 17,926 1945 19,280 1946 21,519 1947 9,280 1948 16,663 1949 9,868 1950 11,895 1951 9,570 1952 11,516 1953 15,991 1954 18,326 1955 11,016 1956 11,094 1957 10,538 1958 14,211 1959 13,142 1960 14,548 1961 18,946 1962 21,746 1963 13,479 1964 20,101 1965 21,050 1966 15,965 1967 24,366 1968 14,507 1969 10,046 1970 12,897 1971 17,185 1972 10,716 1973 13,454 1974 20,425 1975 23,698 1976 14,396 1977 11,396 1978 11,983 1979 21,555 1980 22,344 1981 14,364 1982 10,436 1983 12,450 1984 17,773 1985 17,673 1986 16,503 1987 19,715 1988 11,344 1989 24,238 1990 14,667 1991 16.174 1992 13,683 1993 10.429 Nov 6,430 6,190 2,670 3,050 14,900 7,910 3,990 5,460 4,551 9,400 16,844 5,764 9,211 6,884 2,660 6,720 13,200 15,200 4,330 2,510 12,484 5,396 3,400 15,429 4,607 5,044 11,539 4,870 6,409 6,636 9,508 6,612 2,423 8,798 5,828 6,535 19,302 1,938 2,388 8,711 3,845 8,757 2,909 6,989 9,913 5,626 4,907 6,023 4,421 7,774 2,686 5,243 4,852 7,561 7,137 3,866 7,188 8,178 2,636 5,175 3,224 11,580 2,314 4,463 2,841 5,668 5,322 6,687 5,682 2,871 3,438 2,415 2,040 9,369 7,782 5,487 4,803 1,825 4,299 2,975 Q.el; 2,350 1,470 2,030 2,010 2,150 4,020 2,770 1,520 2,859 2,500 6,574 1,006 8,055 3,872 1,540 5,040 3,700 8,980 1,700 1,630 1,243 3,602 9,536 5,506 3,240 4,522 2,802 1,935 2,029 2,733 12,889 1,476 1,751 1,496 8,576 1,367 1,333 1,745 1,039 1,449 2,976 8,711 1,526 13,782 1,530 7,806 5,810 23,685 1,343 4,676 3,423 1,819 2,136 1,164 1,516 1,308 4,085 1,577 1,357 1,052 995 5,494 1,645 4,253 1,047 2,580 8,484 2,118 1,319 953 982 1,351 24,870 7,185 3,632 2,814 30,958 1,591 2,649 2,384 J.an 1,290 2,220 1,110 2,150 2,040 4,210 6,150 2,546 1,604 1,232 1,913 1,657 5,887 2,227 5,450 4,670 301 4,190 1,230 781 2,095 284 1,325 2,108 2,483 3,395 1,907 509 2,681 3,533 6,319 3,043 1,976 1,927 2,821 2,374 599 673 729 1,126 1,871 2,574 1,102 3,106 4,000 1,691 2,566 2,288 4,236 3,484 3,253 5,362 1,763 809 1,426 630 1,417 2,739 2,433 2,769 1,915 1,889 4,482 2,516 2,201 1,149 1,121 3,338 1,636 2,712 4,072 4,808 4,511 3,767 1,661 4,625 2,114 1,407 3,428 3,192 Ee!l. 2,500 955 1,040 2,470 933 811 2,010 2,499 601 2,565 1,406 660 1,337 808 1,770 1,060 500 5,660 1,150 1,138 3,440 690 551 679 19,309 2,196 842 514 1,267 2,105 1,884 3,720 3,203 983 1,574 240 1,818 3,920 742 742 2,629 730 791 923 920 2,043 1,498 1,966 2,006 2,345 1,205 1,723 1,812 873 2,086 605 1,650 771 1,340 1,603 903 924 1,496 681 2,021 2,160 830 1,792 1,733 974 1,847 5,252 7,902 3,314 3,314 1,782 3,940 3,024 8,618 4,087 1994 11,841 7,554 6,147 2,476 993 ~ ___1UlQll ~ ~ ~ ___j_Aj!l Average Maximum Mintmum 15,528 30,647 8,300 6,366 19,302 1,825 4,183 30,958 953 2,502 6,319 284 2,084 19,309 240 MM 2,260 2,740 1,170 1,380 781 738 984 1,392 627 2,389 2,107 732 1,791 1,009 2,460 3,030 904 1,370 922 1,145 824 841 1,333 1,290 3,984 1,773 505 989 920 2,775 1,927 1,197 2,090 2,794 577 1,089 1,382 2,058 1,130 802 937 1,031 1,119 668 1,080 1,193 1,408 1,911 1,212 1,985 1,394 2,322 1,952 1,507 4,286 1,220 2,202 762 2,105 1,324 1,895 2,224 929 1,109 2,108 1,285 1,352 1,530 2,494 602 1,328 2,218 3,610 1,691 2,423 983 1,526 1,251 4,416 2,009 2,047 ~ 1,643 4,416 505 Am 3,140 4,400 2,620 1,420 1,230 2,800 1,190 1,634 17,404 3,725 14,464 2,195 3,069 1,794 2,520 1,740 2,050 2,700 1,960 2,805 2,395 1,843 4,225 1,749 2,118 2,822 1,326 2,445 1,704 13,153 2,358 2,990 2,740 2,727 649 17,472 1,659 27,819 4,204 2,249 1,784 1,874 1,512 11,738 1,900 2,060 2,379 3,391 1,810 1,926 30,598 3,541 2,826 2,820 2,678 3,293 2,652 17,667 2,099 2,832 1,220 2,671 2,283 2,004 1,901 2,737 2,787 3,935 1,959 1,802 2,023 4,919 3,307 2,761 6,105 2,090 7,089 10,072 7,544 4,911 4,630 ~ 4,398 30,598 649 M.2Y 8,850 14,400 5,530 8,730 7,930 7,260 3,280 7,699 14,176 10,609 17,631 4,110 10,909 5,707 11,900 5,650 6,400 13,000 6,460 17,584 5,119 7,641 14,288 8,488 17,244 10,277 7,455 7,613 6,771 14,201 16,570 11,454 9,200 10,370 10,500 9,857 3,616 13,521 11,469 12,932 4,482 4,910 13,083 13,955 13,168 12,880 11,634 15,266 5,047 9,368 13,241 5,762 10,419 8,881 9,607 12,726 15,889 13,515 8,117 15,526 8,913 13,174 7,111 7,452 7,777 12,407 8,893 10,922 10,015 9,632 7,259 9,655 9,759 18,278 13,040 18,478 13,705 6,363 13,466 16,397 10,997 _u.Qll 10,495 18,478 3,280 .i.t.ill 16,200 24,600 22,000 18,100 20,600 12,900 10,500 18,100 17,822 17,700 23,800 18,801 21,842 20,800 22,700 22,700 18,300 23,900 16,900 14,830 18,966 12,673 25,546 28,714 19,902 16,441 19,095 20,890 15,581 24,408 22,392 26,080 22,870 25,801 25,036 12,682 19,804 23,814 17,705 20,938 16,940 17,726 13,536 18,323 23,421 24,115 19,431 22,775 21,186 19,513 27,072 17,484 19,621 23,536 17,351 29,799 20,723 21,169 14,499 17,221 13,768 18,239 13,954 19,558 21,550 17,773 22,625 15,442 21,784 25,291 22,611 13,207 21,839 18,812 19,660 22,553 21,249 21,876 J..i.!! 31,800 30,600 22,800 27,100 29,600 25,600 25,000 24,500 24,371 27,800 35,900 17,766 19,988 23,200 32,500 25,800 25,800 25,600 2,230 14,445 13,461 26,241 26,346 25,367 24,692 26,530 23,780 22,220 20,791 24,998 8,567 26,891 13,892 12,392 19,313 1,726 23,682 12,168 21,945 12,816 14,891 21,891 20,322 14,692 11,154 27,242 24,802 27,064 22,881 18,743 27,277 13,888 15,936 15,189 18,258 25,809 25,124 12,641 15,662 19,045 16,594 27,277 22,499 21,155 19,666 27,243 27,242 15,570 3,826 18,447 24,312 27,264 9,405 18,182 24,027 11,731 21,226 24,110 Al.!!l 25,100 28,800 28,500 33,100 36,300 31,400 32,700 22,100 24,689 29,700 34,800 26,135 22,202 22,000 23,200 24,800 29,800 29,100 22,500 19,768 31,347 26,858 20,860 29,919 18,769 53,656 30,048 19,226 24,657 19,275 26,521 20,562 22,203 21,380 24,485 22,543 22,676 18,751 23,883 29,421 18,114 26,406 34,999 20,485 24,008 22,316 26,009 35,288 23,294 18,379 22,552 20,059 28,452 26,353 20,659 32,910 26,372 22,941 21,831 33,410 22,381 19,994 22,606 22,277 20,568 18,512 24,577 30,130 21,797 29,167 26,601 26,325 22,253 22,223 20,120 18,824 23,329 28,824 23,117 27,967 22,849 17,639 6,802 23,488 23,487 4,197 20,754 ___11&ll ~ ~ 20,019 29,799 10,500 20,681 35,900 1,726 25,190 53,656 18,114 lli 15,800 23,100 28,000 21,500 24,500 25,000 15,600 23,300 24,462 29,900 34,600 23,763 17,389 20,900 20,400 20,600 21,400 21,500 25,500 17,248 18,798 24,006 26,620 23,726 26,149 26,283 19,651 23,028 24,046 24,622 23,408 26,443 18,778 27,255 27,270 10,148 14,428 16,812 26,869 25,511 19,432 25,574 21,245 23,698 21,988 23,158 25,885 24,771 26,639 22,014 14,491 15,835 25,431 27,173 27,141 20,502 25,669 25,381 24,085 21,923 25,273 25,961 26,231 24,005 18,951 21,945 23,120 27,498 23,282 25,131 15,055 26,421 11,422 26,285 17,797 24,782 26,368 27,498 27,471 19,937 27,460 ~ R.W. Beck October 1996 :D1U! 131,720 158,675 128,870 137,610 156,364 135,049 117,074 119,360 147,803 149,920 203,566 118,616 131,526 125,030 135,400 133,710 150,855 165,000 105,382 113,284 121,796 127,053 145,487 173,622 166,708 166,234 137,439 124,689 120,413 153,140 150,269 149,748 122,645 125,203 143,292 95,901 122,194 132,789 123,619 132,688 106,227 131,200 123,238 138,897 127,293 143,272 140,877 183,374 135,821 123,686 167,293 114,088 131,165 140,232 126,652 142,714 145,868 144,526 106,880 135,334 117,506 153,125 119,946 120,869 112,614 135,014 148,697 133,326 105,963 130,032 127,301 141,508 137,421 151,582 130,905 138,387 170,974 144,015 159,507 114,250 122,583 ~ 22,785 135,873 34,600 203,566 6,104 95,901 H4FlOW2.XlS ~ 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 W2. Average Maximum Minimum QJa 90,680 55,220 44,356 53,113 54,760 42,828 44,604 31,578 56,156 41,159 47.488 51,699 28,095 45,668 29.207 43,604 93,674 46,878 62,117 59.741 38,777 48,599 42,301 72.269 103.155 53,124 82,500 65,724 45,182 73,808 85,594 59,902 96,148 40,881 54,397 45,184 40,382 25,611 30,244 83,825 73,204 39,137 31.471 33,104 49,645 58,283 48,725 68,337 79,608 49,207 65,419 62,805 71,707 67,230 38,555 34,270 32,526 62.418 37,315 50,503 49,206 86,503 43,440 42,285 47,502 83,123 94,965 67,558 47,932 41,650 55,165 54,365 41,383 104,715 69,344 104,238 46,787 49,906 55,770 40,403 52,018 ZQ.hlZ 56,250 104,715 25,611 lii'llL 29,985 23,302 10,397 11.521 53,474 27,933 15,180 20,772 16,722 39,926 47,272 26,451 34,515 26,417 10,022 28,019 41,566 47,885 14,931 9,636 44,273 24,053 15,803 49,510 16,863 18,814 42,850 18,971 25.361 26,628 33,120 25,720 7,509 34,897 28,601 25,296 54,p88 9,306 9.926 34,702 12,198 36,220 15,276 32.362 36,130 20.457 20,906 25,644 16,376 31,488 10,126 21 '144 13,931 20,880 28,299 14,241 28,898 25,858 12,725 17,970 13,948 40,492 6.794 20,048 11,077 20,084 20,485 24,833 22,604 7,878 11,871 6,915 5,520 27.869 30,582 23,387 25,174 4,936 13,436 15,467 30,932 'l'1Xl1 23,610 54,588 4,936 Table 6 · Combined Long Lake and Crater Lake Inflows (acre-feet) w 12,913 9,329 15,404 7,222 7,863 14,915 10,495 5,142 19,643 8,782 19,923 7,550 22,868 20,754 4,553 24,082 12.396 28,807 6,794 6,076 8,456 17,570 23,918 20,535 17,724 18,979 17,660 12,196 15,512 15,862 27,918 8,877 2,799 4,899 23,395 11,234 11,703 3,727 6,526 8,752 11,388 30,805 4,844 34.728 8,715 16,414 17,932 41,294 4,710 22,825 16,595 14,147 8,918 4,482 8,868 6,893 19,052 6,219 6,276 3,102 2,242 19,697 9,302 17,788 1,463 16,241 21,751 10,696 3,826 2,229 2,901 8.668 44,850 20,670 11,982 12,604 50,139 7,247 12,311 10,332 19,992 ~ 14,074 50,139 1,463 Combined Drainage Area 43.3 square miles J.im 4,533 8,452 4,123 7,440 7,929 16,872 17,045 6,649 7,101 4,972 6,624 7,029 20,924 8,335 16.640 16,547 1,508 13,367 4,548 3,500 6,855 2,263 5,311 7,036 9,306 13,167 5.824 2,715 8,910 9,684 25,370 8,756 6,121 7,067 10,727 7,611 2,839 2,752 3,026 4,610 6,151 7,923 2,908 10,497 15,661 5,912 8,063 10,121 15,259 12,220 10,811 19,025 4,914 3,881 4,999 2,220 5,209 9,134 7,483 8,489 6,995 5,897 11,818 9,289 7,965 4,067 5,426 15,630 6,835 9,158 15,190 14,211 14,131 14,617 6,121 13,925 8,081 5,275 13,066 10,207 8,759 ~ 8,770 25,370 1,508 Ee.b. 6,482 3,754 3,828 9,557 3,171 3,805 7,359 7,682 2,240 7,198 4,233 3,965 11,303 2,716 9,505 3,396 2,954 20,089 4,252 3,317 7,645 1,994 3,063 3,182 24,851 5,971 3,987 2,020 4,600 11,606 8,305 10,541 8,909 3,117 4,823 1,418 4,510 9,204 2,892 4,403 17,627 3,724 2,489 3,377 4,738 5,861 4,580 8,866 6,266 14,045 7,310 8,191 4,276 3,886 9,673 1,950 5,904 4,009 4,750 6.442 4,566 3,023 6,751 3,616 6,293 4,231 3,321 8,023 6,497 3,121 9.357 18,404 18,982 10,185 13,294 5,580 8,053 16,374 26,672 23.315 3.828 1..ilil 7,120 26,672 1,418 M£r 7,668 10,863 4,183 4,511 2.351 3,751 3,732 5,554 2,139 9,446 7,535 2,756 8,750 3,540 9,763 9,371 4,526 4,491 4,544 3,638 2,710 3,220 5,350 4,562 15,324 5,798 2,591 3,499 3,913 10,155 6,801 4,974 8,370 7,689 2,390 4,507 3,974 9,090 4,124 3,717 4,539 4,653 3,534 2,778 4,093 4,815 5,737 7,957 6,738 8,561 5,585 9,890 5,888 4,255 17,596 4,587 8,515 3,164 9,857 4,963 8,188 8,223 3,801 4,052 8,798 6,113 4,350 6,076 7,319 2,240 4,914 12,251 15,490 8,396 9.713 5,013 9,195 4,560 16,451 10,169 7,486 ~ 6,459 17,596 2,139 &!!: 10,112 17,075 10,158 5,307 5,382 10,103 4,223 8,063 24,177 14,522 22,346 3,973 7,069 10,733 15,280 6,589 9,991 9,944 8,271 20,375 8,973 8,801 12,595 9,828 10,314 9.978 12,536 11,348 4,651 17,689 13,880 9,188 9,051 15,235 3,227 23,690 6,178 33,614 12,959 7,206 4,709 5,790 5,605 16,822 10,636 7,861 10,948 15,169 6,786 8,650 39,726 9,921 10,403 5,608 9,097 9,840 10,436 29,664 5,992 14,042 6,929 9,679 12,091 14,863 9,368 6,202 14.133 11,409 9,055 8,109 12,145 15,152 12,787 15,007 15,322 10,080 18,275 24,066 19,130 17.209 17,241 lUlU 12,171 39,726 3,227 ~ 30,821 48,729 20,842 28,950 25,990 25,909 17,414 31,158 38,616 36,914 52,377 19,031 37,234 25,627 45,370 26,655 25,540 42,544 28,054 50,073 29,194 31,133 51,091 30,231 48,438 37,464 27,487 29,320 27,534 48,147 52,766 41,848 36.679 38,416 41,123 37,179 18.120 46,429 37,980 47,443 23,867 ·22, 175 42,617 42,429 46,295 38,626 40,138 45,861 23,451 32,768 32,077 20,829 33,524 32,173 35,794 42,329 42,432 44,884 30,809 41,755 25,811 38,386 28,973 31,887 31,595 45,098 35,342 35,433 36,958 27,358 33,073 38,768 31,909 47,160 40,354 56,658 41,415 30,950 45,406 44,078 45,349 !§..ill 36,213 56,658 17,414 Jl.!!l 61,726 77,415 72,451 58,736 64,082 44,702 44,363 59,815 59,047 60,004 76,901 61,974 73.628 72,920 70,305 70,992 59,917 80,044 61,069 53.412 72,341 46,877 72,939 98,282 65.050 57,633 62,817 69,551 60,364 73,851 69,001 82,495 72,298 79,665 85,127 53,655 58,330 86,391 60,539 76,032 60,952 56,860 48,057 65,133 84,355 77,000 60,616 82,178 67,731 62,730 85,032 57,864 66.274 91,203 55,543 97,849 65,910 63,901 53,284 59,620 53,605 60,254 51,118 63.520 66,316 59,254 68,820 51,601 72,239 80,662 77,973 46,667 70,999 63,393 61,668 64,073 67,541 76,154 71.158 64,269 73,920 ~ 66,718 98,282 44,363 .!lL! 110,388 102,005 74,429 87,170 94.185 77,720 80,359 75,834 79,435 83,944 106,473 68,757 67,821 81,111 97,674 79,196 80,079 83,216 51,798 59,250 64,552 97,570 88,562 77,845 75,493 94,166 81,489 103,560 76,328 128,757 60,544 98,050 70,410 67,629 81.364 56,835 71,591 59,901 84,911 68,911 64,145 84,405 81,933 64,780 70,243 100,259 '87,787 109,042 77,288 75,780 99,754 66,292 72,031 67,387 72,694 98,021 72,883 76,918 65,031 73,129 71,723 87,601 84,347 79,411 64,045 98,310 103,154 70,791 47,817 69,682 72,694 87,769 62,355 70,057 75,001 61,941 90,455 90,878 88,576 48,604 61,605 ~ 78.957 128,757 47,817 &!!! 93,970 110,663 93,085 110,936 109,915 94,807 105,138 73,827 88,096 88,396 98,207 89,452 62,586 80,303 76,694 75,251 94,974 94,863 75.405 79,095 107,759 96,841 77.716 89,861 70,080 140,995 100,582 59,804 83,404 82,464 89,786 70,344 81,076 69,330 79,642 79,954 71,890 57.366 81.696 90,865 56,168 95.506 116,624 69,209 83,725 76,340 84,725 124,736 73,549 64,060 73.994 73,013 92.193 92,705 61,255 103,129 84,999 82,617 82.727 124,837 78,865 80,137 82,537 85,188 62,747 62,583 87,505 102,250 62,238 101,060 89,520 94,957 76,803 61,183 74,901 61,214 88,919 112,398 84,521 67,505 66,690 ~ 84,527 140,995 54,288 ~ 55,305 85,949 88,757 75,386 86,435 83,402 52.997 64,623 72,852 96.448 97,713 63,160 61,759 76,946 68,888 64,671 69.299 69,497 82,429 52,188 65,224 62,436 86.285 99.024 91,954 76,580 80,148 64,122 89,988 74,590 53,600 77,144 66,232 83,729 91,993 57,875 65,675 58,250 91,317 76,963 72,504 74.936 60,232 83,523 52,916 57,198 83,089 66,761 91,038 94,285 43,064 50,199 90,428 104,361 101,807 62.461 90,897 67,973 89,110 61,168 68,292 92,502 80,377 74,233 70,556 78.857 63.469 84,091 67,643 93,250 45,097 117.044 34,642 99,978 93,797 75,762 98,368 109,030 81,181 89,163 108,805 ~ 76,490 117,044 34,642 R.W. Beck 2/27197 Illlill 514.583 552.756 442,013 459,849 515,537 446,747 402,909 390,697 466.224 491,711 587,092 405,797 436,552 455,070 453,901 448,373 496.424 541,625 404.212 400,301 456,759 441,357 484,934 562,165 548,552 532,669 520,471 442,830 445,747 573,241 526,685 497,839 465.602 452,554 506,809 404,438 409,780 401,641 426,140 507.429 407,452 462,134 415,590 458,742 467,152 469,026 473,246 605,966 468,800 476,619 489,493 413,320 474,487 498,051 444,180 477,790 467,661 476,759 405,359 466.020 390,370 532,394 421,349 446,180 387,725 484,163 522.721 488,391 390,963 446,397 429,900 515,171 429.851 543,230 502,079 494,475 552,402 531,774 527,678 440,721 496,625 ~ 471,360 605,966 387,725 R.W. Beck 2/27/97 Water Year 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 .19..a6 Avg. 1986-96 Avg. 1992-1996 Percent of annual Maximum Minimum Oct Nov 5,310 4,039 5,700 5,374 7,105 6,407 4,777 3,959 5,243 3,785 5,911 3,625 6,724 4,967 5,331 4,336 5,155 6,408 7,648 3,488 ~.415 :.1.163 5,759 4,505 5,861 4,472 9.81% 7.49% 7,648 6,408 4,445 3,163 Table 7-AEL&P Hydro (MWh) Includes Annex Creek, Salmon Creek, and Gold Creek Dec Jan Feb Mar Apr May Jun 3,610 3,606 4,128 5,056 5,403 4,976 5,230 4,631 4,489 4,008 3,644 3,662 5,788 5,972 6,435 3,771 4,300 4,279 4,041 5,253 5,398 5,424 3,851 3,167 4,112 3,986 5,235 5,525 5,025 3,715 3,613 5,967 5,213 5,919 5,235 3,396 3,121 3,370 4,687 4,668 5,756 6,016 4,816 4,864 4,393 6,298 5,803 5,703 6,621 4,009 3,438 4,148 4,858 5,344 5,593 5,161 5,847 4,471 3,667 3,892 5,926 5,759 5,075 4,482 4,241 3,077 3,100 3,961 6,074 5,942 :.1.7~6 :.1.665 J.9Q5 J.Z53 4,299 3.1379 4,92Q 4,679 3,930 3,798 4,513 4,755 5,449 5,554 4,590 4,136 3,838 4,380 5,067 5,402 5,544 7.68% 6.92% 6.42% 7.33% 8.48% 9.04% 9.28% 6,435 4,864 4,393 6,298 5,926 6,074 6,621 3,396 3,121 3,077 3,100 3,662 3,879 4,920 HISTORY2XLS Jul Aug Sep Total -- 6,374 6,095 5,821 59,648 6,678 6,008 6,295 62,249 5,595 6,285 6,324 65,193 5,210 5,022 4,950 55,218 6,451 5,973 6,217 62,356 6,509 6,929 6,467 60,455 7,223 6,467 6,148 70,027 4,618 4,144 4,135 55,11 5 6,805 5,310 5,785 64,100 4,872 4,707 4,980 56,572 6,319 ~~.BM 4,9Qf! 52.131313 6,059 5,707 5,639 60,347 5,967 5,292 5,191 59,740 9.99% 8.86% 8.69% 100.00% 7,223 6,929 6,467 70,027 4,618 4,144 4,135 52,888 R.W. Beck 2/27/97 Water Year 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 1.9.9Q Avg. 1992-1996 Percent of annual Model Run 1 2 3 4 5 Oct 22,631 21 '198 22,150 22,301 23,414 24,516 25,287 26,244 24,337 29,438 26.169 26,295 8.51% Oct 25,532 27,404 28,085 31,064 34,894 Nov Dec 27,397 26,593 24,294 24,876 22,271 25,697 24,535 27,194 26,620 27,619 28,116 31,272 26,670 28,730 26,611 31,185 27,564 32,025 25,933 33,314 29.753 34.301 27,306 31,911 8.84% 10.33% Nov Dec 26,514 30,985 28,458 33,257 29,165 34,084 32,259 37,699 36,236 42,346 Table 8 -Juneau Area Loads {MWh) Historic Loads (MWh) Jan Feb Mar Apr May 24,298 24,111 24,103 22,237 20,027 25,271 22,336 25,026 21,286 19,878 27,094 26,552 22,540 21,885 20,682 30,539 24,622 28,027 21,344 20,317 29,168 28,274 26,585 23,373 19,989 31,894 21,842 31,359 24,307 21,883 27,749 27,763 26,465 24,301 23,551 33,598 27,.585 27,934 23,477 20,910 28,690 31,376 29,122 24,832 23,327 32,784 29,210 31,173 25,442 22,801 36.947 31.068 31.111 26.350 23.382 31,954 29,400 29,161 24,880 22,794 10.34% 9.52% 9.44% 8.05% 7.38% Distributed Loads (MWh) for Model Runs Jan Feb Mar Apr May 31,026 28,547 28,315 24,159 22,133 33,302 30,641 30,391 25,930 23,756 34,129 31,402 31,146 26,574 24,346 37,749 34,733 34,450 29,393 26,928 42,403 39,015 38,697 33,017 30,248 HISTORY2.XLS Jun Jul Aug Sep Total 17,372 17,572 17,958 18,223 262,522 18,188 17,549 17,225 18,957 256,084 17,338 18,444 19,008 20,206 263,867 18,145 17,675 18,477 19,816 272,992 19,083 18,845 19,230 20,666 282,866 19,501 19,480 20,879 21,136 296,185 19,592 20,206 20,250 22,917 293,481 19,128 19,694 20,132 21,517 298,015 18,682 23,135 21,137 23,631 307,858 21,496 21,355 22,702 22,176 317,824 21.383 21.757 22.588 __2L835 327.644 20,056 21,229 21,362 22,615 308,964 6.49% 6.87% 6.91% 7.32% 100.00% Jun Jul Aug Sep Total 19,474 20,613 20,742 21,959 300,000 20,902 22,125 22,263 23,569 322,000 21,422 22,675 22,816 24,155 330,000 23,694 25,080 25,236 26,717 365,000 26,615 28,172 28,347 30,011 410,000 R.W. Beck 2/25/97 Annual AEL&P Base Load Run (MWhl 1 300,000 ---·--· 2 322,000 ----- Long Lake Minimum Average (MWhl (MWh) 146,423 155,494 -·---- 159,648 170,233 -------· Table 9 Snettisham Hydrolelectric Project Power Study Results Hydroelectric Generation ( 1) Crater Lake Snettisham Total (2) Minimum Average Minimum Average (MWhl (MWh) (MWh) (MWhl 79,763 85,297 227,307 240,790 f------- 82,316 92,558 f-.-249,307 262,790 ------------- RESUL TS3.XLS Required Thermal Total Hydro (3) Generation Minimum Average Average Maximum (MWh) (4) (MWh) (MWh) (MWhl 300,000 300,000 0 0 -------·----· ------- 322,000 322,000 0 0 -· -------- 3 330,000 164,407 175,495 80,999 94,872 246,400 270,367 300,507 329,576 424 29,493 -------·-··---------· ---·-----------··-·---------- 1- 4 365,000 152,260 194,259 79,208 101,045 231,943 295,304 288,193 354,515 10,486 76,807 -------·----------·---------· ---·----·--- 5 410,000 144,705 202,440 75,571 101,847 220,276 304,287 276,526 363,497 46,504 133,474 ----------· -·--·· ------------·--·-----·-- 322,000 170,231 213,393 82,286 109,459 272,959 322,852 322,000 382,061 0 0 -6 (5) --··--------··-····-·----------- 7 (5) (6) 322,000 169,854 211,785 81,980 108,982 263,965 320,767 318,071 379,976 148 12,138 ~ ( 1) All generation is usable for the given load level, except as noted. (2) Firm energy, which is the generation available under the most adverse hydrologic conditions, is 273,000 MWh as shown in Run 2 and Run 6. Minimum energy can be less than firm energy because of hydro dispatch order, or operation at higher loads without rule curves. (3) System minimum hydro energy is greater than the sum of the minimum energy values because minimum annual energy does not occur in the same year for all components. (4) Total Hydro includes Long Lake, Crater Lake, and AEL&P hydroelectric projects. AEL&P hydro (Annex, Salmon, and Gold Creeks) provides 48,895 MWh minimum and 59,210 MWh average for each run. (5) All potential generation from Snettisham is assumed to be usable, regardless of AEL&P monthly base loads. (6) Long Lake normal maximum pool is at El 818. I R.)N. Beck October 1996 Station Lower Lake Dorothy Creek Lake Dorothy at ouUet Juneau City PredpltaUon Juneau Airport Precipitation Annex Creek Preclpllation ~dCreek.USGS1~~ ~dCreek·USGS1~~ Mendenhall R.-USGS 1~52500 Long River-USGS 1 ~34000 -..-..-.-..... NNNN NNNN §·~~~=~~~NM·~=~=~ ~ ~~2!2! 2!~~~ ~~~~ \~~l· ~~~~m ~;;~~;~, It= tH r!Mt Long Lk. OuUet-USGS 1 ~32000 l!@.}j! Long River· USGS 1~31000 Long Lake Inflows (1) Crater Lake Inflows (1) Crater Creek • USGS 1 ~38000 [!j; l{fflf'{{@ lmi Salmon Creek· USGS 1~51008 Salmon Creek· USGS 1~51010 MPl~~lllll!t;;ll!~e~NM::! ~~~~~~~~~t:'!~!~~ :=l!lt!l!i!l.@:!j, ~m~~~ Note: (1) Inflows were calculated from powerhouse flows and change in reservoir storage. ·'Partial years of record !~~! ffiii: ~n¥ 1m•n=:nr ;;;~~~ ~~~~ ~~=m 1/)l()'i)tl) ~~~~ ~~~~ AVAILDAT .XLS ~~~.,~~NM·~~~=m~~NM~~~~=m~~NMX~~ ~~~e~~~~~~~~~~~~~!~~!!~~~~~~~~ i~~f ~~~~f !~i!.t:::ntilt•=::ml 1t@l:~t:limnnl:~ r:~~r ;:::=:=tr:m:-~:~i 'i~~:k•=j~j:•m•l!l'M'lirrrrrmt :r:t n:rw=:wrti ;~~~t !)~~}: ;~~;fm; ~m @!~; @f~ I! if mt mr-r:: lit:: M:nrm:m•:r=tr::= ~~I~ 'IJ ·t~~ Snettisham Hydrology Data Availability-Calendar Years Figure 1 @m~· ~ I» ,.... C'D .. -< C'D I» ... 0 1914 1917 1920 1923 1926 1929 1932 1935 1938 1941 1944 1947 1950 1953 1956 1959 1962 1965 1968 1971 1974 1977 1980 1983 1986 1989 1992 1995 0 9 0 0 0 I I I ' I ' Inflow (ac-ft) f-.,) w ~ 0 0 0 0 0 p 0 0 0 0 0 0 0 0 0 I I I I ' ' I I I I I i ' I 0'1 (J) 0 0 0 p 0 0 0 0 0 0 I i I I •. ' I I I )> < ro I ..., Ql cc I C1) () 0 3 -: !:!. ::J I ro Q. I ::J -0 ~ - I I I I I I I I I I I I I : -....1 0 p 0 0 0 n., 0 -· 3CC ere -· .. ::;, C'D ~N Srn ::;, ::;, cc ! ,.... .... m r;r ~= C'D I» I» 3 ::;, :I: c.< (")c. .... I» 0 ;~ ... C'D r-(') I» !:t ~ c;· C'D _., ::;, .. :::!:: .E. 0 C'D =e ~ en Q:D (") . .... ~ 0 . gc:o ..., C1) _. (") CD""" CD (J) :J: .;:.. ., ' 0 :i! N X ' (f) R.W. Beck 2/27/97 1100 1050 1000 ·-- -..... 950 Q) Q) -- Q) > 900 Q) ..J Q) ....=.:: co 850 -----..J 800 750 -- 700 0) 0 I' co ' ' .... c (,) ctl 0 -, 0 co ' ..... a. <( SNETMO.XLS Figure 3 -Snettisham Hydroelectric Project Comparison of Lake Levels for Water Years 1980-85 -Run 2 and Run 5 --+--Long Lake -Run 2 -Crater Lake -Run 2 ---....--Long Lake -Run 5 """'*"""Crater Lake -Run 5 0 0 ..... ..... ..... ..... N N N N (") (") (") (") ""' ""' ""' ""' LO LO LO co co co co co co co co co co co co co co co co co co co co co ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' .... c ..... ::l .... c ..... :; .... c ..... .... c ..... :; .... c ..... :; ::l (,) ctl a. (,) ctl a. (,) ctl a. ::l (,) ctl a. (,) ctl c. -, 0 -, <( -, 0 -, <( -, 0 -, <( -, 0 -, <( -, 0 -, <( -, RULECR2.XLS R.W. Beck 2/27/97 ; ~ '1b > G> ..... G> .X: Ill ..... Figure 4 -Snettisham Hydroelectric Project Preliminary Rule Curves 1,050.-------------------------------------------------------------------------~ 1 ,ooo J.---··--·-~--+-Long Lake -Crater Lake -··---------------··--··--··--··--··--···~·---··-------··-----1 900 -1---~-----··--·----~--------------------·----/-------------1 850 ·--------··----·--··---···--·~--~---·---··--~---··---··--···--··-------------1 750 700~--------------------------_:~~====--------------------J Od Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep End-of-Month ·--------------~--~---·-----···----------------·--------- End-of-Month Rule Curve Elevations M_onth L!:!Dg Lals;e Crate[ Lake Oct 814 994 Nov 801 978 Dec 782 953 Jan 759 923 Feb 737 893 Mar 716 858 Apr 704 830 May 709 839 Jun 731 870 Jut 763 909 Aug 793 951 Sep 815 995 APPENDIX A POWER STUDY MODEL OUTPUT RUN 2 -322,000 MWH ANNUAL LOAD (Potential Generation Limited by Monthly Loads) 2/25/97 1914 191s 1916 1917 1918 1919 1920 1921 1922 1923 1924 19::15 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1214.6 585.8 53 6. 0 593.8 640.1 494.9 515.6 373.5 675.2 467.7 552.3 580.1 296.8 485.3 340.0 515.6 1060.0 538.0 676.8 656.1 441.6 514.3 501.6 676.9 1283.9 647.8 1041.0 736.3 514.3 961.3 1100.5 660.7 1213.7 513.9 613.7 574.4 463.3 260.9 304.6 1103.2 892.5 457.3 331.4 367.0 576.3 73«.1 555.8 803.3 941.0 581.1 737.0 679.1 906.6 697.1 391.1 394.0 319.2 735.6 432.6 602.5 468.1 1021.4 472.4 502.4 577.7 1001.3 1181.1 865.1 609.8 474.9 608.1 596.7 404.6 1382.4 943.3 1301.1 522.4 548.6 684.5 487 .s 653.4 938.5 662.3 NOV 395.9 287.6 129.9 142.4 648.3 336.5 188.1 257.3 204.5 513.0 Sll.4 347.7 425.2 328.3 123.7 357.9 476.7 549.3 178.2 119.8 534.2 313.5 208.4 572.8 206.0 231.4 526.2 237.0 318. s 336.0 396.8 321.1 85.5 438.6 3U.7 315.3 593.0 123.8 126.7 436.8 140.4 461.5 207.8 426.4 440.6 249.2 268.9 329.7 200.9 398.5 1H.O 267.2 152.6 223.8 355.6 174.4 364.8 297.1 169.6 215.0 180.2 485.9 75.3 261.9 138.4 242.3 254.8 305.0 284.4 84.1 141.7 75.6 58.5 310.9 383.2 300.8 342.3 52.3 153.6 209.9 392.9 335.1 289.8 DEC 171.8 127.8 217 .s 84.8 92.9 177.2 125.6 58.9 273.0 102.2 217.1 106.4 240.9 274.6 49.0 309.7 141.4 322.5 82.8 72.3 117.3 n1.2 233.9 244.4 235.6 235.1 241.6 166.9 219.3 213.5 244.4 120.4 17 .o 55.3 241.0 160.5 J.68. 7 32.2 89.2 118.8 136.8 359.3 54.0 340.7 J.l6. 9 J.40.0 J.97 .1 286.4 54.8 295.2 214.2 200.5 ll.O. 3 54.0 119.6 90.8 243.4 75.5 80.0 33.3 20.3 231.0 124.5 220.1 6.8 222.2 215.8 139.5 40.8 20.8 31.2 119.0 324.9 219.3 135.8 159.2 311.9 92.0 157 .1 129.3 225.2 210.8 160.9 Appendix A SNE'l'TISBA:II BYDR.OELECTRIC PROJECT -PRELIMINARY • INPUT, SNETOP2 . IN R17N 2 -322000 MWI! LOAll • BASIC OPER.. • OUTPUT: LON'GOPRl.OtlT, CRATOPR2.01l'T JAN 52.7 101.4 49.0 86.0 95.8 205.9 177.2 66.7 89.4 60.8 76.6 87.4 244.6 99.3 J.82.0 193.2 J.9 .6 149.2 54 .o 44.2 77.4 32.2 64.8 80.1 111.0 158.9 63.7 35.9 J.01.3 100.0 309.8 92.9 67.4 83.6 J.28.6 85.2 36.4 33.8 37.4 56.7 69.6 87.0 29.4 120.2 189.6 68.6 89.4 127.4 179.3 142.1 122.9 222.2 51.2 50.0 58.1 25.9 61.7 104.0 82.1 93.0 82.6 65.2 119.3 110.2 93.7 47 .s 70.0 199.9 84.6 104.8 180.8 152.9 J.S6. 5 176.5 72.5 151.3 97.0 62.9 156.7 114.1 102.2 91.7 101.9 IN7LOII TO LONG LAitE (CFS) FEB 71.7 50.4 50.2 127.6 40.3 53.9 96.3 93.3 29.5 83.4 50.9 59.5 179.4 34.4 139.3 42.1 44.2 259.8 55.9 39.2 75.7 23.5 45.2 45.1 99.8 68.0 56.6 27.1 60.0 171.1 115.6 J.22.8 102.7 38.4 58.5 21.2 48.5 95.1 38.7 65.9 270.1 53.9 30.6 44.2 68.7 68.7 55.5 124.2 76.7 2J.O, 7 109.9 116.5 44.4 54.3 136.6 24.2 76.6 58.3 61.4 87.1 66.0 37.8 94.6 52.8 76.9 37.3 44.9 112 .2 85.8 38.7 135.2 236.8 199.5 J.23. 7 179.7 68.4 74.1 240.4 325.1 346.2 51.0 55.5 90.7 88.0 132.1 49.0 50.9 25.5 u.o 44.7 67.7 24.6 J.l4.8 88.3 32.9 113.2 41.2 118.8 103.1 58.9 50.8 58.9 40.5 30.7 38.7 65.3 53.2 184.4 65.5 33.9 40.8 48.7 120.0 79.3 61.4 102.1 79.6 29.5 55.6 42.2 114.4 48.7 47.4 58.6 58.9 39.3 34.3 49.0 58.9 70.4 98.3 89.9 106.9 08.2 123.1 64.0 44.7 216.5 54.8 102.7 39.1 126.1 59.2 J.02.3 97.6 46.7 47.9 108.8 78.5 48.8 73.9 78.5 26.6 58.3 163.2 193.2 109.0 118.6 65.5 124.7 53.8 195.7 J.32. 7 88.5 153.9 78.3 APR 117.2 213.0 U6.7 65.3 69.8 122.7 SJ..O 108.0 113.8 181.4 132.5 29.9 67.2 150.2 214.4 81.5 133.5 121.7 106.1 295.3 110.5 ll6.9 140.7 135.8 137.7 J.20.3 188.4 149.6 49.5 76.2 193.6 104.2 106.1 210.2 43.3 104.5 75.9 97.4 147.1 83.3 49.2 65.8 68.8 85.4 J.46.8 97.5 J.44.0 197. 9 83.6 113 .o 153.4 107,2 127.3 46.9 107.9 110.0 130.8 201.6 65.4 188.4 95.9 117.8 164.8 216.1 125.5 58.2 190.7 125.6 119.3 106.0 170.1 172.0 159.3 205.8 154.9 134.3 188.0 235.2 194.7 206.7 2J.l.. 9 174.7 130.6 !lAY JON 357.3 765.1 558.3 887.6 249.0 847.9 328.8 682.9 293.7 730.7 303.3 534.5 229.9 569.1 381.5 701.0 397.5 692.8 427.8 710.9 565.1 892.4 242.7 725.5 428.1 870.3 324.0 875.9 544.3 800.0 341.6 811.6 311.3 699.4 480.5 943.5 351.2 742.3 528.4 648.4 391.5 897.0 382.1 574.8 598.5 796.5 353.6 1169.1 507.3 758.7 442.2 692.3 325.8 734.8 353.0 8l.7.8 337.7 752.6 552.1 830.9 588.7 783.3 04.3 948.1 446.9 830.7 456.l. 905.2 498.0 1009.9 444.3 688.6 235.9 647.5 535.2 1051.6 431.2 719.8 561.3 925.9 315.3 739.6 280.8 657.7 480.3 580.1 463.l. 786.7 538.8 1024.0 418.7 888.8 463.6 692.1 497.6 998.3 a9.3 782.2 380.6 726.3 306.3 97t.1 245.0 678.6 375.8 784.0 378.8 1137 .• 425.9 641.8 481.4 1143.6 431.7 759.4 510.2 718.1 369.1 651.8 426.6 712.5 274.8 669.5 410.0 706.1 355.6 624.6 397.4 738.8 387.4 752.3 531.7 697.1 430.2 776.3 398.6 607.7 438.2 847.9 288.3 930.5 419.8 930.4 473.5 562.3 360.2 826.2 469.7 749.2 444.2 706.0 620.9 697.8 450.7 778.0 399.9 912.2 519.5 807.4 450.2 783.6 558.7 847.6 549.6 658.9 418.3 784.8 1278.1 l.l.61. 3 839.7 976.9 1050.4 847.7 900.3 834.9 895.5 913.1 1147.8 829.3 777.9 941.8 1060.0 868.4 882.8 937.0 806.l. 728.7 830.9 1160.1 1011.8 853 .5 826.2 1J.OO.O 938.5 1322.9 903.2 1687.5 845.3 1157.3 919.2 898.3 1009.2 896.3 779.2 776.3 1024.0 912.3 801.0 1016.7 1002.0 814.6 961.0 1l.87 .5 1024.4 1333.2 884.8 927.6 ll.78.7 852.3 912.3 848.9 885.3 1174.4 776.7 1045.4 802.9 879.6 896.6 981.l. l.005.9 947.4 721.8 1155.8 1234.6 898.1 715.4 833.3 786.9 984.0 861.1 843.7 829.0 816.6 1125.9 1085.9 985.7 679.8 933.7 555.6 947.8 AUG SEP 1120.1 663.9 1331.4 1056.2 1050.4 1021.1 1265.9 905.6 1l.97.2 1040.9 1031.2 981.5 1178.1 628.5 841.3 694.5 1031.2 8l.3.2 954.6 l.l.18.4 l.031.2 1060.6 1029.8 662.1 656.8 745.7 948.2 941.9 870.0 814.9 820.5 740.6 1060.0 805.0 1069.5 806.6 860.4 956.7 964.9 587.2 1242.7 780.2 ll38.2 645.8 924.7 1002.7 974.9 1265.4 834.5 1105.9 1420.4 845.3 1147 .1 1016.7 659.9 690.6 955.4 1108.2 1027.7 839.7 1028.9 507.4 809.6 852.1 957.5 797.5 779.8 949.1 897 .o 1087.7 933.7 802.1 800.4 861.2 628.0 696.4 940.2 1083.1 999.3 864.7 618.9 891.9 ll23.8 829.6 1327.5 655.2 792.4 1005.4 971.2 519.8 878.6 572.1 954.9 961.3 1454.7 705.7 817.3 1082.3 742.9 1214.6 836.6 480.2 861.2 577.5 1036.6 1092.3 1079.1 1297.2 660.2 1254.8 1142.0 705.1 953.5 1096.2 970.5 715.8 990.4 1092.8 1486.9 659.5 918.6 723.0 978.1 1118.3 974.7 910.0 1023.1 844.1 686.0 867.3 716.7 956.4 1023.4-678.1 1172.9 951.1 657.7 745.5 1169.2 1144.8 1023.3 504.9 1116.2 1523.0 887.2 390.2 633.6 1238.5 890.9 1277.2 689.4 856.7 1066.7 1210.0 1359.2 1370.2 1003.0 902.6 715.9 1163.4 747 .1 1367. 0 567.1 1010.9 965.0 902.5 Page 1 AVG 524.7 541.1 430.5 442.6 493.8 428.2 392.0 373.2 436.7 470.7 527.2 394.4 420.5 453.7 438.0 432.2 474.4 519.0 410. 8 393.7 460.8 430.6 466 .·2 535.4 524.2 502.3 526.2 436.5 447.4 576.3 516.1 478.7 470.5 450.7 499.9 423.5 396.0 370.4 415.9 514.6 415.3 454.4 400.5 440.0 466.9 446.9 456.5 579.7 457.7 486.6 442.2 410.9 471.5 492.7 437.8 460.1 443.1 455.9 410.3 453.6 374.8 520.8 414.0 446.9 378.5 478.8 512.4 487.5 392.3 435.2 415.9 514.6 401.8 538.5 511.3 488.5 524.3 534.4 507.1 451.6 514.9 441.9 461.1 2/25/97 19l4 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 3.926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1.214.6 585.8 536.0 593.8 640.1 494.9 515.6 373.5 499.4 467.7 552.3 580.1 352.2 485.3 342.5 515.6 1060.0 538.0 676.8 656.1 368.2 514.3 501.6 676.9 1283.9 647.8 1041.0 736.3 514.3 961.3 1100.5 660.7 1213.7 513.9 613.7 574.4 463.3 369.3 361.4 1103.2 892.5 367.5 344.5 367.0 576.3 734.1 SSS.B 803.3 941.0 5U.1 737.0 679.1 906.6 697.1 391.1 394.0 334.6 735.6 432.6 602.5 468.1 824.9 472.4 502.4 577.7 793.6 1181.1 865.1 609.8 378.7 608.1 596.7 404.6 1382.4 943.3 1301.1 522.4 548.6 684.5 487 .s 653.4 938.5 655.1 NOV 395.9 378.4 391.7 389.9 648.3 394.1 397.8 416.3 3 96.5 513.0 511.4 402.7 406.7 391.7 391.3 396.4 476.7 549.3 394.1 417.7 421.5 397.6 389.5 572.8 379.5 382.9 526.2 392.7 393 .o 375.4 396.8 388.3 384.2 438.6 389.4 395.9 593.0 421.2 413.0 436.8 392.7 438.2 398.8 426.4 440.6 390.8 391.5 375.3 388.8 398. s 389.6 397.2 390.6 380.1 395.0 387.8 394.1 387.9 396.6 402.7 400.9 485.9 391.4 396.6 399.2 388.9 382.3 386.3 400.3 406.7 393.1 377.6 392.6 375.8 385.4 387 .a 385.6 374.6 379.8 392.8 392.9 392.4 412.0 DEC 449.2 443.6 465.8 454.4 443.6 456.3 462.7 480.4 471.1 447.2 438.3 466.8 464.3 460.6 454.8 464.6 446.2 441.7 458.4 486.6 485.5 464.8 448.0 441.0 449.7 450.2 446.8 460.9 462 .3 441.9 430.8 452.4 444.9 464.9 446.6 462.9 480.0 485.6 483.7 453.9 458.6 486.0 461.3 450.2 449.9 445.1 453.4 411.1 451.2 455.7 460.7 467.4 456.8 441.7 458.3 453.5 460.0 448.7 461.9 466.4 462.5 442.1 461.0 463.7 460.0 459.1 440.3 450.4 460.1 473.4 455.7 447.0 431.7 434.5 444.5 452.1 411.0 442.0 447.3 458.5 445.1 459.9 455.0 Appendix A SNETTISBAM HYDROELECTRIC PROJECT PRELIMINARY • INPUT: SNETOP2.IN Rllll2 • 322000 MWH LOAO ·BASIC OPl!R. • oti'IPUT: LONGOPR2.0UT, CR.ATOPR2.0UT TOTAL oti'IFLOW PROM LONG LAKE • TtlNN'EL + SPILL {CPS) JliN 461. s 458.2 475.2 467.5 458.3 471.9 472.3 491.7 482.0 460.5 449.4 480.9 477 .3 470.8 469.2 475.0 457.7 450.5 470.6 501.4 499.4 475.5 457.7 451..4 461.6 463.5 456.6 472.2 473.0 452.3 448.9 464.0 458.4 480.5 458.7 474.0 492.2 499.3 497.2 468.4 469.2 493.7 472.4 457.7 466.7 456.1 463.5 436.9 468.1 466.1 471.0 480.9 467.8 455.8 470.7 465.1 469.8 462.3 473.9 480.9 477.0 451.9 469.9 475.2 475.1 469.3 452.0 469.0 475.0 489.4 473.7 459.3 443.3 448.7 457.8 463.8 443.1 455.7 462.0 470.6 456.7 471.8 467.9 FEB 472.3 469.8 488.0 482.0 469.2 482 .o 483.2 504.3 494.2 471.7 460.1 495.6 494.9 482.2 484.4 484.2 472.0 465.2 482.6 512.7 507.8 488.0 470.5 463.5 430.2 471.9 470.1 484.8 485.3 470.4 457.8 474.7 467.0 492.5 468.7 486.0 504.6 503 .4 508.8 483.9 498.3 509.2 483.0 468.5 478.0 466.6 474.3 450.5 476.7 485.8 487.2 493.7 476.5 468.5 488.6 476.0 483.4 474.9 485.3 494.6 490.0 463.2 483.0 488.4 484.6 477.7 463.8 481.6 488.3 498.7 488.4 474 .o 449.1 457.8 474.9 473.6 449.7 480.2 475.3 499.9 468.2 483.2 479.9 415.7 416.7 429.8 421.8 411.1 427.2 425.3 446.2 435.3 418.3 406.0 437.1 440.2 425.7 429.2 429.0 417.4 405.5 427.1 449.5 446.1 430.9 415.4 407.9 383.7 414.8 413.9 427.0 428.7 412.9 402.9 417.5 413.1 432.5 412.6 430.5 444.7 447.4 443.1 426.2 436.8 452.7 423.8 414.3 421.5 411.1 419.3 396.9 423.9 428.9 429.6 439.7 417.7 409.0 438.0 419.1 429.0 417.8 435.0 435.2 437 .o 409.8 424.7 430.7 432.0 423.8 406.6 424.6 429.3 436.4 429.1 421.8 402.3 405 .s 418.7 418.8 401.5 417.1 417.9 440.9 413.8 429.8 423.6 APR 341.3 347.1 360.3 347.8 340.5 358.2 353.2 377.1 311.6 351.3 307.2 355.3 362.0 362.4 370.6 357.2 351.5 336.2 357.7 412.8 370.6 363.7 343.7 341.3 318.2 343.5 353.9 362.4 3 52.8 307.7 339.8 344.5 338.9 372.2 340.7 309.4 371.7 213.3 3H.3 349.8 359.3 374.7 349.1 321.1 357.0 342.6 353.9 329.4 350.7 357.0 282.2 363.7 347.1 326.2 361.7 343.3 359.2 313.1 355.4 372.1 368.1 338.1 364.8 374.6 365.9 343.0 345.3 349.3 363.0 363.7 369.6 345.9 338.1 340.9 339.7 351.5 326.7 333.3 338.0 368.4 345.8 350.6 347.6 MAY 298.1 302.4 318.7 310.6 297.4 314.5 322.1 347.6 277.9 309.0 273.0 324 .o 319.1 322.6 332.6 321.1 311.4 291.8 333.5 338.4 348.0 328.9 313.7 297.1 275.7 305.2 305.9 325.3 318.0 275.2 293.1 310.8 318.6 328.8 308.9 293.2 335.1 294.1 346.3 315.1 332.8 331.5 326.6 286.5 316 .s 301.7 314.3 279.8 318.2 309.7 247.3 317.6 307.6 301.1 321.9 314.8 303.9 288.1 326.7 309.9 317.9 290.0 331.4 333.0 340.9 314.6 307.3 304.0 331.3 311.1 339.8 309.1 297.7 283.0 293.8 306.6 281.5 304.1 295.8 308.3 309.1 314.5 310.8 268.5 256.7 292.9 282.1 265.1 280.6 306.8 308.0 260.2 272.0 241.3 297.9 281.9 287.8 283.1 279.9 275.6 254.3 lOS .2 303.7 308.1 293.7 264.5 265.0 242.7 268.1 265.6 290.9 291.7 235.1 248.6 270.7 279.4 281.9 270.7 277.7 291.4 301.5 313.6 276.0 301.7 286.5 296.8 261.0 279.5 272.8 272.5 245.0 282.4 267.3 245.5 285.1 280.1 288.7 279.2 284.6 269.3 255.2 299.7 281.1 311.0 254.9 300.2 287.2 299.1 274.2 262.7 266.2 296.4 297.3 300.9 267.1 269.1 246.8 254.4 256.8 245.2 269.8 253.4 275.5 261.4 271.6 276.8 JUL AUG 270.6 1074.8 474.1 1331.4 291.3 296.1 287.1 406.8 268.9 677.5 282.2 285.3 307.2 307.8 304.3 308.5 270.1 396.3 269.0 578.8 619.5 1031.2 309.9 313.2 280.1 417.7 285.7 561.7 ,277.2 637.0 275.8 482.2 274.5 379.5 624.4 1069.5 348.0 335.1 315.6 326.7 312.9 410.5 304.7 505.9 268.3 755.0 285.6 974.9 243.6 743.1 273.1 1198.4 266.8 781.1 310.4 323.6 294.5 296.8 1135.1 1027.7 558.7 1028.9 321.7 809.6 296.6 300.5 294.8 387.5 330.0 897.0 318.8 316.3 292.2 297.9 312.6 309.8 323.7 318.7 284.5 741.0 312.1 308.7 295.7 516.0 316.7 328.0 272.5 581.3 348.1 971.2 281.1 719.9 279.7 575.8 1081.3 1454.7 284.4 286.8 274.7 619.7 265.4 836.6 302.8 307.5 295.5 294.8 288.6 584.6 289.7 287.8 285.0 1022.8 265.9 483.3 282.6 721.1 3J.3.4 3ll0.2 291.4 684.9 329.6 3ll7.6 257.3 751.1 310.3 311.9 291.8 511.5 300.2 302.0 281.6 398.0 271.3 990.8 282.1 654.5 322.2 313.7 302.9 308.1 288.4 367.5 268.4 714.0 28&.2 737.2 252.7 618.5 255.1 !>10.7 272.7 355.4 573.4 1066.7 271.6 1161.5 434.4 1003.0 289.7 288.7 344.2 747.1 259.4 266.3 329.7 589.7 SiP 663.9 1056.2 855.6 905.6 1.040.9 932.0 388.2 325.6 813.2 1118.4 1060.6 324.0 745.7 941.9 814.9 740.6 805.0 806.6 363.5 342.5 780.2 645.8 1002.7 1265.4 1105.9 845.3 1016.7 690.6 1096.3 839.7 507.4 852.1 764.5 949.1 1087.7 782.7 337.0 339.4 491.1 864.7 342.0 829.6 655.2 1005.4 519.8 572.1 961.3 705.7 849.7 1214.6 480.2 427.1 1055.5 1297.2 l09S. 3 705.1 1096.2 715.8 655.7 659.5 337.7 1118.3 683.5 844.1 337.4 956.4 678.1 951.1 334.1 894.1 504.9 1523.0 390.2 1238.5 1277.2 856.7 1210.0 1370.2 902.6 1147.8 1367.0 690.5 814.2 Page 2 AVG 527.2 543.4 433.4 445.8 496.7 431.6 395.2 390.3 425.7 473.1 529.2 399.0 420.2 456.5 440.6 435.1 477.3 519.4 412.7 422.0 438.2 434.5 469.2 536.9 526.5 505.4 528.7 439.8 450.6 577.9 517.9 480.6 473.3 453.1 502.1 426.8 408.6 374.7 405.0 517.0 425.4 448.4 404.7 442.7 468.8 449.5 459.6 580.8 460.2 488.3 444.4 413.5 474.7 494.9 440.0 462.6 445.7 458.6 413.0 456.8 393.9 507.3 417.1 449.9 397.8 465.0 515.1 490.3 402.0 430.0 418.3 517 .o 403.7 540.4 512.9 491.4 526.4 535.7 507.8 452.4 517.1 444.0 463.5 2/25/97 1914 1915 J.9J.6 l.917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 J.942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG 352.5 321.0 347.7 341.7 336.0 345.1 351.7 366.8 356.6 336.9 328.9 349.7 352.2 336.3 342.5 346.0 339.5 329.7 345.5 380.3 368.2 351.3 340.1 313.4 342.1 336.8 340.3 343.4 344.6 333.2 344.3 334.5 352.5 358.0 332.5 352.3 382.0 369.3 361.4 363.8 355.7 367.5 344.5 342.6 339.6 350.1 339.9 322.5 345.4 337.6 343.0 345.0 364.1 328.3 336.9 338.7 334.6 343.9 347.8 362.2 343.1 352.4 344.1 350.2 358.1 360.1 343.1 346.0 358.8 361.5 350.1 328.3 340.7 347.3 348.3 349.2 326.9 324.6 337.4 343.7 337.4 359.1 346.0 NOV 385.8 378.4 391.7 389.9 3 89.0 394.1 397.8 416.3 396.5 394.3 375.7 402.7 406.7 391.7 391.3 396.4 386.5 380.9 394.1 417.7 421.5 397.6 389.5 379.1 379.5 382.9 384.0 392.7 393.0 375.4 382.4 388.3 384.2 406.6 389.4 395.9 421.5 421.2 413.0 393.2 392.7 422.7 398.8 398.3 390.6 390.8 391.5 375.3 388.8 389.4 389.6 397.2 390.6 380.1 395.0 387.8 394.1 387.9 396.6 402.7 400.9 384.5 391.4 396.6 399.2 388.9 382.3 386.3 400.3 406.7 393.1 377.6 392.6 375.8 385 .4 387.8 385.6 374.6 379.8 392.8 385 .4 392.4 392.5 Dl!C 449.2 443.6 465.8 454.4 443.6 456.3 462.7 480.4 471.1 447.2 438.3 466.8 464.3 460.6 454.8 464.6 446.2 441.7 458.4 486.6 485.5 464.8 448.0 441.0 449.7 450.2 446.8 460.9 462.3 441.9 430.8 452.4 444.9 464.9 446.6 462.9 480.0 485.6 483.7 453 .9 458.6 4U.O 461.3 450.2 449.9 445.1 453 .4 411.1 451.2 455.7 460.7 467.4 456.8 441.7 458.3 453.5 460.0 448.7 461.9 466.4 462.5 442.1 461.0 463.7 460.0 459.1 440.3 450.4 460.1 473.4 455.7 447 .o 431.7 4.34.5 444.5 452.1 411.0 442.0 447.3 458.5 445.1 459.9 455.0 Appendix A Slll!TTISRAM HYDROELECTRIC PROJECT -PRELIMINARY -INPUT, SNETOP2. IN R'CIN 2 -322000 Mllll LOAD -BASIC OPER. OUTPUT, LONGOPR2 .OUT, Cl!.ATOPR2 .OUT JAN 461.5 458.2 475.2 467.5 458.3 471.9 472.3 491.7 482.0 460.5 449.4 480.9 477.3 470.8 469.2 475.0 457.7 450.5 470.6 501.4 499.4 475.5 457.7 451.4 461.6 463.5 456.6 472.2 473.0 452.3 448.9 464.0 458.4 480.5 458.7 474.0 492.2 499.3 497.2 468.4 469.2 493.7 472.4 457.7 466.7 456.1 463.5 436.9 468.1 466.1 471.0 480.9 467.8 455 .a 470.7 465.1 469.8 462.3 473.9 480.9 477.0 451.9 469.9 475.2 475.1 469.3 452.0 469.0 475.0 489.4 473.7 459.3 443.3 448.7 457.8 463.8 443.1 455.7 462.0 470.6 456.7 471.8 467.9 l'Ulllil!L FLOW TO LONG LAX!! 'l'U.Rllii!ES (CFS) FEB 472.3 469.8 488.0 482.0 469.2 482.0 483.2 504.3 494.2 471.7 460.1 495.6 494.9 482.2 484.4 484.2 472.0 465.2 482.6 512.7 507.8 488.0 470.5 463.5 430.2 471.9 470.1 484.8 485.3 470.4 457.8 474.7 467.0 492.5 468.7 486.0 504.6 503.4 508.8 483.9 498.3 509.2 483.0 468.5 478.0 466.6 474.3 450.5 476.7 485.8 487.2 493.7 476.5 468.5 488.6 476.0 483.4 474.9 485.3 494.6 490.0 463.2 483.0 488.4 484.6 477.7 463.8 481.6 488.3 498.7 488.4 474.0 449.1 457.8 474.9 473.6 449.7 480.2 475.3 499.9 468.2 483.2 479.9 415.7 416.7 429.8 421.8 411.1 427.2 425.3 446.2 435.3 418.3 406.0 437.1 440.2 425.7 429.2 429.0 417.4 405.5 427.1 449 .5 446.1 430.9 415.4 407.9 383.7 414.8 413.9 427.0 428.7 412.9 402.9 417.5 413.1 432.5 412.6 430.5 444.7 447.4 443.1 426.2 436.8 452.7 423.8 414.3 4H.5 411.1 419.3 396.9 423.9 428.9 429.6 439.7 417.7 409.0 438.0 419.1 429.0 417.8 435.0 435.2 437.0 409.8 424.7 430.7 432.0 423.8 406.6 424.6 429.3 436.4 429.1 421.8 402.3 405.5 418.7 418.8 401.5 417.1 417.9 440.9 413.8 429.8 423.6 APR MAY 341.3 298.1 347.1 302.4 360.3 318.7 347.8 310.6 340.5 297.4 358.2 314.5 353.2 322.1 377.1 347.6 311.6 277.9 351.3 309.0 307.2 273.0 355.3 324.0 362.0 319.1 362.4 322.6 370.6 332.6 357.2 321.1 351.5 311.4 336.2 291.8 357.7 333.5 412.8 338.4 370.6 348.0 363.7 328.9 343.7 313.7 341.3 297.1 318.2 275.7 343.5 305.2 353.9 305.9 362.4 325.3 352.8 318.0 307.7 275.2 339.8 293.1 344.5 310.8 338.9 318.6 372.2 328.8 340.7 308.9 309.4 293.2 371.7 335.1 213.3 294.1 359.3 346.3 349.8 315.1 359.3 332.8 374.7 . 331.5 349.1 326.6 321.1 286.5 357.0 316.5 342.6 301.7 353.9 314.3 329.4 279.8 350.7 318.2 357.0 309.7 282.2 247.3 363.7 317.6 347.1 307.6 326.2 301.1 361.7 321.9 343.3 314.8 359.2 303.9 313.1 28a.1 355.4 326.7 372.1 309.9 368.1 317.9 338.1 290.0 364.8 331.4 374.6 333.0 365.9 340.9 343.0 314.6 345.3 307.3 349.3 304.0 363.0 331.3 363.7 311.1 369.6 339.8 345.9 309.1 338.1 297.7 340.9 283.0 339.7 293.8 351.5 306.6 326.7 281.5 333.3 304.1 338.0 295.8 368.4 308.3 345.8 309.1 350.6 314.5 347.6 310.8 268.5 256.7 292.9 282.1 265.1 280.6 306.8 308.0 260.2 272.0 241.3 297.9 281.9 287.8 283.1 279.9 275.6 254.3 305.2 303.7 308.1 293.7 264.5 265.0 242.7 268.1 265.6 290.9 291.7 235.1 248.6 270.7 279.4 281.9 270.7 277.7 291.4 301.5 313.6 276.0 301.7 286.5 296 .a 261.0 279.5 272.8 272.5 245.0 282.4 267.3 245.5 285.1 280.1 288.7 279.2 284.6 269 .3 255.2 299.7 281.1 311.0 254.9 300.2 287.2 299.1 274.2 262.7 266.2 296.4 297.3 300.9 267.1 269.1 246.8 254.4 256.8 245.2 269.8 253.4 275.5 261.4 271.6 276.8 270.6 255.7 291.3 287 .l 268.9 282.2 307.2 304.3 270.1 269.0 240.5 309.9 280.1 285.7 277.2 275.8 274.5 251.2 348.0 315.6 312.9 304.7 268.3 253.6 243.6 273.1 266.8 310.4 294.5 256.5 261.9 273.4 296.6 294.8 273.7 318.8 292.2 312.6 323.7 284 .5 312.1 295.7 316.7 272.5 289.5 281.1 279.7 248.7 284.4 274.7 260.5 302.8 295.5 288.6 289.7 285.0 265.9 282.6 313.4 291.4 329.6 257.3 310.3 291.8 300.2 281.6 271.3 282.1 322.2 302.9 288.4 268.4 288.2 252.7 255.1 272.7 257.0 271.6 253.0 289.7 282.5 259.4 284.1 AUG 273.8 262.7 296.1 293.0 270.4 285.3 307.8 308.5 282.3 271.3 252.5 313.2 279.7 291.2 279.4 278.1 280.1 259.6 335.1 326.7 310.3 303.6 276.2 257.7 259.7 262.7 272.9 298.6 296.8 257 .o 265.3 273.6 300.5 294.2 274.1 316.3 297.9 309.8 318.7 282.1 308.7 298.7 313.1 279.1 289.7 281.3 281.7 253.9 286.8 279.1 270.7 307.5 294.8 292.6 287.8 280.9 274.9 286.6 320.2 302.2 327.6 269.7 311.9 298.4 302.0 281.2 273.2 286.6 313.7 308.1 295.2 277.0 292.2 254.7 267.7 277.5 263.2 279.8 264.9 288.7 281.6 266.3 287.2 SEP 290.1 292.0 316.1 310.8 298.1 309.1 326.4 325.6 300.3 299.1 284.0 324.0 308.3 313.4 304.4 302.6 299.4 290.1 351.1 342.5 325.0 310.0 299.4 298.2 293.2 288.9 296.7 317.9 323.4 278.6 278.6 293.1 322.9 314.5 295.9 349.3 337.0 339.4 340.4 294.4 342.0 309.6 321.6 306.6 292.2 291.9 300.5 273.9 314.7 310.5 298.5 328.8 318.0 314.9 322.7 297.1 306.9 295.0 344.3 303.3 337.7 294.4 328.7 313.3 337.4 308.9 285.2 298.0 334.1 H0.9 311.9 305.7 305.3 294.4 308.1 300.7 296.0 297.9 289.2 326.1 309.3 323.0 309.9 Page 3 AVG 356.6 350.3 372.8 365.7 354.0 367.2 376.4 389.7 361.5 358.4 338.1 379.8 372.2 369.2 368.2 367.5 359.3 346.4 384.1 399.0 392.0 376.1 357.3 347.4 340.0 355.1 356.1 373.9 372.0 341.3 346.2 358.1 364.8 376.8 356.0 372.2 387.5 374.7 392.4 365.9 380.7 385.7 375.6 354.9 364.2 357.6 362.0 335.3 365.9 363.5 348.8 377.4 368.1 358.0 370.9 362.2 362.6 354.7 380.0 375.2 383.5 350.7 376.8 375.3 379 .5 365.2 352.8 362.0 381.0 381.7 374.7 356.8 354.2 345.2 354.0 359.3 340.6 354.2 351.2 371.9 358.0 365.1 365.1 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 190 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 l.9H 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 198l 1983 1984 1985 1986 1987 1988 19U 1990 1991 1992 1993 1994 1995 AVG OCT NOV 862.1 10.0 264.8 .0 188.3 0 252.1 .0 304.1 259.2 149.7 .0 163.9 . 0 6. 8 • 0 142.8 .0 130.8 118.7 223.4 135.7 230.4 .0 .0 .0 149.0 .0 .0 .o 169.6 .o 720.4 90.3 208.3 168.4 331. 3 . 0 275.8 .0 • 0 .o 163.0 .0 161.5 .o 363.5 193.6 941.8 .o 310.9 .o 700.7 142.2 392.9 .o 169.7 .0 628.1 .0 756.2 14.4 326.2 .o 861.3 .0 155.9 32.0 281.1 .o 222.0 .0 81.3 171.5 .0 .0 .o .0 739.5 43.6 536.8 .o .o 15.5 .0 . 0 24.4 28.1 236.7 50.0 384.0 .o 215.9 .0 480.8 .o 595. 6 • 0 243.4 9.2 394.0 .0 334.1 .0 542,4 .o 368.8 .o 54.2 .o 55.2 .0 .0 .0 391.7 .0 84.8 .0 240.4 .0 124.9 .0 472.5 101.4 128.3 .0 152.1 .o 219.6 .o 433.6 .o 838.0 .0 519.1 .0 251.0 .0 17.2 .0 258.0 .o 268.4 .0 63.9 .0 1035.1 .o 595.0 .o 951.9 . 0 195.5 .0 224.0 .0 347.1 .0 143.8 .0 316.0 7.5 579.4 .0 309.1 19.4 DEC .0 .0 .o .0 .o .0 .0 • 0 • 0 .0 .o .0 .0 .0 .o .0 .0 .0 .o .o .0 .0 .0 .0 .0 .0 .o .0 .o . 0 .0 .0 .o .0 .0 .o .0 .0 • 0 • 0 . 0 • 0 .o .o .0 .o .0 .0 .0 .o .0 .0 .0 .0 .0 .0 .0 • 0 .0 .0 • 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 • 0 .0 .0 .o .o .o .o . 0 • 0 .0 Appendix A SNETTISBAM HYDROELECTRIC PROJECT -PRELIMINARY· INPUT: SNETOP2.IN RUN 2 322000 MWR LOAD-BASIC OPER. -OUTPUT: LONGOPR2.0UT, CRATOPR2.0UT JAN • 0 • 0 . 0 • 0 .o .0 .0 .0 .0 .0 .0 .0 .0 .0 .o . 0 .0 .0 .0 .o .0 .0 .0 .o .o .0 .0 .0 .0 .o .0 .0 .0 .0 .0 .0 .o .0 .0 .0 .o .0 .0 .0 .0 • 0 .0 .0 .0 .0 .o .o .0 .0 • 0 .0 .0 .0 • 0 .o .0 .0 .o .0 .0 .0 .0 • 0 .0 .0 .0 .0 .0 .o .o .0 . 0 .o .0 .0 .o .0 .o SPILL AT LONG LAKE OUTLET (CFS) FEB .0 .0 .0 .0 .0 .o .0 .0 .0 .0 .o .o .0 .0 .0 .o .0 .0 • 0 • 0 • 0 • 0 • 0 .0 .0 .0 .0 .0 .0 .o .0 .0 .0 .0 .0 .0 .o .0 .0 .0 .0 .o .0 .0 .0 .o .0 .0 .o .0 .0 .0 .o .0 .0 .0 .o .o .o .o .0 .0 • 0 .0 .0 .0 .0 .0 .o .0 .0 .0 .0 .o .0 .0 .o .0 .0 .0 .0 .0 • 0 MAlt APR MAY .0 . 0 .o .0 .0 .0 .0 .0 .o .0 .0 .o . 0 • 0 • 0 .0 .o . 0 .0 .o .0 .0 .0 .0 .0 .o .o .0 .o .o .0 .o .0 .0 .0 .0 .0 .0 .0 .o .0 .o .o .0 .0 .o .0 . 0 .o .0 .o .0 .0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .o .o .0 .0 .0 .0 .o .0 .0 . 0 .0 .0 . 0 • 0 . 0 • 0 • 0 . 0 . 0 . 0 • 0 .0 .0 .0 .0 .o .o .0 . 0 .0 .o .0 .0 .0 . 0 .0 .o .0 .0 .0 .0 .0 .o .0 .0 .o .0 .o .0 .0 .0 .0 .0 .0 .0 .0 .o .0 .o .0 .0 .0 .0 .0 .0 .0 .o .o .0 .0 .0 .o .0 .0 .0 .0 .o .o .0 .0 .o .0 .0 .o .o .0 .0 .0 .o .o .o . 0 .o .0 . 0 .o .o .o .0 .0 .o .0 .0 .0 .o .0 .o .0 .0 .o .o .o .o .0 .0 .o .0 .o .0 .0 .0 .0 .0 .0 .o .0 .o . 0 .0 .0 .o .o .0 .o .0 .0 .0 .o .0 .0 .0 .0 .0 .0 .0 .0 .0 .o .0 .o .0 • 0 . 0 .0 .0 . 0 .0 .0 .o .0 .0 .o .0 .0 .0 . 0 .o .0 . 0 .0 .0 .o .0 .o .0 .0 .0 .o .0 . 0 .o .0 .0 • 0 .0 • 0 .o • 0 .o .o .o .0 .0 .o .0 . 0 • 0 .o .o .o .0 .0 .0 .0 .o .0 .0 .o • 0 • 0 .o .o .0 .0 • 0 • 0 .0 • 0 .o .0 .0 .0 .0 .0 .0 .0 .0 .0 .o .0 .0 .0 .o .o .0 .0 .o .o .0 • 0 .0 .0 .0 .o .o .0 .0 .0 • 0 .0 .0 .0 .0 .o .0 .0 .0 .o .0 .0 .o .0 .0 .0 .0 .0 J0L AUG SliP .o 801.0 373.8 218.4 1068.7 764.2 .0 .o 539.5 .0 113.9 594.8 .o 407.1 742.8 .o .0 622.9 .o .o 61.7 .o .o .0 .0 114.0 512.9 .0 307.5 819.3 379.0 778.7 776.7 . 0 .o . 0 .0 137.9 437.4 .0 270.5 628.5 .o 357.7 510.5 .0 204.2 438.0 .0 99.5 505.5 373.2 810.0 516.5 .0 .o 12.4 . 0 .0 .0 .0 100.3 455.2 .0 202.2 335.9 .0 478.8 703.3 32.0 717.2 967.3 .0 483.4 812.7 .0 935.6 556.3 .o 508.1 720.0 .0 24.9 372.7 .0 .0 772.9 878.6 770.6 561.1 296.8 763.6 228.8 48.3 536.0 559.0 .0 .0 441.6 .0 93.3 634.6 56.3 623.0 791.8 .0 .0 433.4 .0 .o .0 .0 .0 .0 .0 .0 150.7 .0 459.0 570.3 .0 .0 .0 .0 217.3 519.9 .0 14.9 333.6 .0 302.3 698.8 58.7 681.5 227.6 .0 438.6 280.2 .0 294.1 660.9 832.6 1200.8 431.8 .0 .0 535.0 .o 340.6 904.1 4.9 566.0 181.7 .0 .0 98.4 .0 .o 737.5 .0 292.0 982.3 .0 .0 775.7 .0 741.8 408.0 .0 208.4 789.3 .0 434.5 420.8 .0 . 0 311.3 .0 382.7 356.2 .0 . 0 .0 .0 481.4 823.8 .0 .o 354.8 .0 213.2 530.8 .o .0 .0 .0 116.8 647.5 .o 717.6 392.9 .0 367.9 653.1 .0 . 0 .0 .o .0 563.2 .o 72.3 193.0 .0 437.1 1217.2 .0 445.1 84.9 . 0 3 63 • 8 944 . 0 .0 342.9 969.1 .o 77.9 556.0 316.4 803.5 914.0 .o 881.6 1072.3 181.4 738.1 613.4 .0 .0 821.6 61.7 465.5 1057.7 .0 .o 367.5 45.6 302.5 504.3 Page4 AVG 170.6 193 0 60.7 80.1 142. 8 64.4 18.8 .6 64.1 114.7 191.1 19.2 47.9 87.3 72.3 67.7 118.0 173.0 28.6 23.0 46.3 58.4 112.0 189.5 186.5 150.2 172.6 65.9 78.6 236.5 171.7 122.5 108.6 76.3 146.0 54.6 21.1 . 0 12.6 151.0 44.7 62.7 29.0 87.8 104.5 91.9 97.6 245.5 94.2 124.8 95.5 36.0 106.7 136.9 69.2 100.4 83.1 103.9 33.0 81.6 10.4 156.6 40.3 74.7 18.3 99.8 162.4 128.3 20.9 48.4 43.6 160.2 49.5 195.2 158.9 132.2 U5.8 U1.5 156.7 80.5 159.0 78.9 98.4 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 198l 1984 1985 1986 1987 1988 1989 1990 1U1 1992 1993 1994 1995 AVG OCT 799.0 808.3 808.2 807.4 807.6 808.0 807.6 807.0 798.6 808.0 808.0 808.5 805.9 807.7 807.5 807.8 807.9 808.0 808.3 806.1 792.2 807.1 807.6 808.0 808.0 808.2 808.3 808.1 807.3 807.1 808.7 808.7 808.2 807.2 807 .5 808.1 806.2 800.5 798.8 806.5 808.1 801.0 807.6 807.2 807.7 808.2 808.2 807.9 808.8 807.5 807.6 808.0 806.9 807.3 807.4 807.2 808.1 807.7 808.1 806.4 807.8 797.2 808.1 806.9 807.5 796.6 807.7 808.4 808.0 802.0 806.9 807.6 807.8 807.8 808.1 807.7 807.9 808.1 808.0 808.3 807.0 807.6 806.7 NOV 806.0 807.2 806.2 806.5 806.7 806.3 806.1 805.5 805.9 806.6 806.9 806.2 802.1 806.7 806.3 806.3 806.5 806.9 806.3 804.9 794.6 806.1 806.5 807.5 806.4 806.6 806.5 806.4 806.3 806.8 806.4 806.7 806.0 805.8 806.8 806.0 804.8 794.1 795.3 805.6 805.9 804.3 805.7 806.4 806.5 806.1 806.5 807.2 806.3 806.6 806.4 806.3 805.6 807 .o 806.6 806.6 806.0 806.4 806.2 805.7 806.4 806.0 806.4 806.1 805.8 805.7 806.4 806 .3 805.8 805.7 806.1 807.0 806.5 806.2 806.2 806.2 807.0 807.1 806.6 806.4 806.6 805.8 805.8 DEC 804.7 BOO. 7 792.3 793.0 804,5 801.6 7H.4 795.9 795.3 804.3 805.1 801.3 800.7 801.4 791.9 802.4 804.6 804.9 794.3 789.4 797.4 800.1 796.1 805.0 796.8 797.7 804.7 797.1 800.8 803.2 804.8 801.4 790.9 803.7 804.2 800.4 803.l. 779.0 780.6 804.3 792.7 803.0 794.6 804.1 804.5 797.8 798.7 802.9 795.8 804.5 792.2 798.l. 793.4 797.6 802.4 794.7 802.2 800.3 793.6 795.2 793.7 804.7 789.8 797.9 792.0 797.7 798.8 800.8 798.6 788.9 792.7 791.0 789.0 802.0 804.6 800.4 802.6 790.3 794.4 795.8 804.7 801.6 798.2 Appendix A SNETTISI!AM IIY!lROELEC:'!'RIC PROJECT -PRELIMINARY -J:NPU'l': SNETOP2 . Ill RUN 2 -322000 MNB LOAD· BASIC OPER. -OUTPUT: LONGOPR2.0UT, CRATOPR2.QUT JAN 788.4 783.1 777.7 772.9 785.4 785.5 776.0 773.3 782.6 785.5 791.6 781.5 787.3 789.3 769.9 791.7 787.3 796.3 773.9 766.4 777.4 785.7 783.5 792.7 783.7 784.6 792.0 780.4 786.0 789.3 793.6 783.0 767.9 781.8 791.6 783.1 785.3 753.5 757.7 785.6 774.9 793.6 772.7 796.3 785.9 781.3 783.9 795.4 774.6 793.6 777.9 782.4 774.4 777.1 783.5 775.0 788.7 780.3 772.9 772.0 770.1 791.9 770.8 783.4 767.7 783.4 785.7 783.4 776.6 764.1 769.8 772.7 782.5 789.1 787.1. 783.9 796.7 770.8 778.3 777.9 791.3 786.6 781.5 NET HEAD ON LONG LAXE UNITS (FEETl PEB 768.6 765.1 756.3 753.7 767.4 772.4 760.9 752 .o 763.1 765.7 773.9 761.7 776.3 771.5 755.4 778.4 766.0 782 .o 753.1 743.8 756.0 764.1. 764.1 775.2 766.3 769.5 773.3 758.7 767.9 772.5 786.3 764.5 748.7 761.8 776.1 763.9 763.0 728.9 733.9 765.2 754.8 774.7 750.8 780.5 772.2 762.0 765.4 780.2 759.6 778.4 760.2 769.3 753.6 756.5 763.1 753.0 769.1 762.1 753.3 752.5 750.4 773.6 753.5 765.2 748.8 762.6 766.9 769.6 756.6 745.0 754.8 757.2 767.9 776.2 768.3 768.3 779.5 751.3 762.4 759.6 774.6 768.1 763.4 750.8 746.6 735.8 736.8 748.5 753.1 743.5 732.3 742.2 748.6 755.4 741.9 761.1 751.4 739.0 758.4 747.0 772.5 732.7 720.6 736.1 743.3 745.1 756.1. 753.7 751.6 754.5 737.5 749.0 758.4 771.4 748.9 730.8 741.2 757.4 743.1 742.6 710.2 711.7 746.6 743.3 753.7 728.9 761.3 753.7 744.1 746.9 764.9 741.5 765.0 742.9 752.3 733.2 737.1 747.1 731.4 750.8 743.3 733.1 732.9 729.8 754.4 735.0 745.9 728.9 743 .o 748.4 752.9 737.8 722.5 738.1 746.3 757.0 760.8 754.7 750.4 762.4 739.0 755.3 751.5 755.6 749.1 745.5 APR 736.6 734.0 719.2 720.7 730.9 736.6 726.3 716.2 723.7 735.3 742.1 723.7 748.5 734.4 725.5 745.4 730.6 758.2 716.9 703.4 718.0 725.6 729.1 741.0 745.8 736.4 738.0 720.5 732.0 747.1 758.4 733.0 7l.7 .9 725.7 741.0 726.1 724.5 695.3 694.1 729.3 726.5 736.8 712.8 745.5 737.6 728.1 731.1 753.3 726.5 752.6 726.7 739.1 718.2 721.2 738.1 710.0 736.7 726.2 719.9 716.9 715.7 741.3 718.6 728.5 715.5 727.4 732.2 738.0 722.6 705.2 721.9 735.1 749.2 749.3 742.5 734.7 751.6 723.3 747.4 739.0 742.0 737.5 730.7 IIAY 728.5 730.2 711.1 710.2 720.9 727.8 715.0 705.9 719.5 729.6 737.0 711.9 736.8 726.7 720.7 734.3 722.9 751.1 707.4 698.8 708.8 716.8 722.5 733.2 739.1 728.3 732.0 713.3 720.6 739.4 754.4 724,4 709.5 720.7 729.0 721.3 713.8 697.7 685.9 719.9 715.2 725 .o 701.4 737.2 729.7 719.4 723.8 749.7 716.9 743.7 726.4 729.4 710.5 711.1 728.6 707.5 728.3 725.2 709.3 711.0 705.1 732.9 711.7 723.5 706.4 717.3 727.2 729.9 713.9 694.5 715.1 729.6 742.6 745.0 736.3 726.8 747.7 722.1 743.4 733.9 738.0 731.9 723.2 733.0 745.4 708.8 712.6 722.3 728.9 711.5 709.0 726.5 737.3 753.8 708.5 744.3 728.3 732.6 736.8 724.4 761.. 7 709.3 712.5 712.2 720.8 738.0 737.8 752.9 736.6 734.9 716.0 722.9 755.2 770.0 734.7 717 .o 728.7 740.0 729.3 710.0 708.9 691.6 733.3 715.3 724.2 710.8 747.8 743.0 726.6 732.6 762.1 717.2 749.3 730.4 727.6 715.5 716.0 735.4 717.3 736.9 737.1 712.8 719.1 704.7 741.0 714.2 728.3 709.9 729.0 734.8 736.4 720.4 695.3 720.2 739.5 747.4 756.7 746.0 744.9 757.9 727.9 756.5 743.7 752.7 745.8 730.1 759.0 776.8 736.9 732.8 746.4 742.8 724.7 729.6 748.7 760.5 785.3 730.3 773.5 758.9 760.3 764.4 746.7 794.5 731.6 730.2 742.4 735.5 765.7 782.6 777.8 759.2 759.8 743.0 746.7 784.3 795.8 769.2 745.4 761.3 776.8 750.7 728.8 745.9 714.7 766.7 737.6 744.2 725.6 773.4 779.9 758.3 755.5 797.6 742.9 772.1 766.3 748.6 740.9 758.3 755.5 760.6 762.4 761.3 730.5 741.1 723.0 764.2 73 0. 8 752.8 733.3 751.9 761.9 755.2 749.1 728.1 753.1 756.0 774.6 781.2 768.8 767.6 784.0 760.9 763.8 769.2 781.6 765.8 756.0 AUG 806.7 809.3 764.8 767.6 785.0 770.8 755.4 757.3 779.0 791.3 809.8 756.9 797.1 790.3 797.5 792.7 776.6 809.5 754.1 751.5 768.0 778.1 800.8 809.4 805.2 798.2 791.8 7U.7 776.5 809.3 809.2 808.8 775.4 789.8 808.8 777.4 754.4 768.4 750.1 796.1 702.2 779.6 760.0 798.7 808.3 800.9 790.8 809.5 772.6 802.8 809.2 774.7 771.2 785.5 784.1 802.7 787.2 796.6 755.6 770.2 751.7 798.4 765.7 784.6 755.6 793.4 807. 3. 784.6 767.4 755.5 777.4 790.2 801.1 808.7 795.9 793.0 809.3 799.4 809.4 787.7 808.5 780.6 785.8 SEP 808.8 809.1 800.4 808.2 808.9 806.1 796.5 783 .o 808.5 808.9 809.4 790.9 808.6 808.3 808.6 808.7 808.6 809.2 780.0 782.3 807.6 807.8 808.7 809.3 809.2 809.1 808.8 808.0 807.5 809.3 809.1. 808.8 806.4 808.2 808.8 806.5 778.3 784.3 780.6 808.5 777.3 808.0 807.5 808.6 808.3 808.6 808.6 809.4 797.6 808.6 808.9 800.7 806.4 808.2 801.0 808.6 808.8 808.4 787.5 807.9 780.5 808.9 797.0 808.0 773.7 808.6 808.8 808.4 784.6 796.1 808.1 808.7 808.2 809.4 809.0 BOB. 7 809.1 808.6 809.1 807.6 SOB .6 794.3 803.5 Page 5 AVG 774.2 776.3 759.8 760.2 769.5 770.0 759.8 755.6 766.1 773.5 781.5 760.3 778.5 772.9 767.9 777.3 769.1 787.9 755.7 750.8 759.2 765.9 772.3 779.8 778.8 773.8 775.4 765.1 768.6 781.8 789.0 774.3 760.3 769.7 779.0 768.0 759.6 747.2 741.3 772.3 759.5 770.7 756.5 780.6 778.1 770.1 771.0 786.7 763.4 782.1 771.3 769.7 760.8 765.2 771.1 765.0 773.8 771.2 756.9 760.9 753.3 716.2 758.5 769.3 753.8 768.1 773.8 772.8 761.8 750.2 763.7 770.1 777.8 782.7 777.3 774.4 784.7 767.4 779.5 773.4 780.9 772.9 769.2 .. · 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 l928 1929 1930 1931 1932 1933 1934 1935 1936 1937 l93a 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 19ao 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 813.0 8ll.O 813.0 813.0 813.0 8l.3. 0 813.0 a13 .0 804.5 813.0 813 .o 813.0 811.8 813.0 a13.0 813.0 813.0 813.0 813.0 813.0 798.7 813.0 811.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813 .o 813.0 813.0 813.0 813.0 ao6.9 805.3 a13 .0 813.0 807.5 8ll.O 813.0 813.0 813.0 813.0 813 .o 813.0 813.0 813.0 813.0 a11.0 811.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 803.6 813.0 813.0 813.0 803.0 813.0 813.0 813.0 808.3 813.0 813.0 813.0 813.0 813.0 813 .o 813.0 813.0 813.0 U3.0 813.0 813.0 812.2 NOV 813.0 813.0 813.0 813.0 813.0 813.0 813.0 83.3. 0 813.0 813.0 a13.0 813.0 809.1 813.0 812.9 813.0 813 .o 813.0 813.0 813.0 802.2 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 a13. 0 a13 .0 813.0 801.8 802.6 813.0 813.0 811.9 a12 .4 813.0 813.0 813.0 813.0 813 .o 813.0 813.0 813.0 813.0 a13 .o 813.0 a13 .o 813.0 812.2 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 8ll.O 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 a13.0 813.0 812.5 DEC 813.0 808.7 800.9 aOL5 813.0 810.3 803.2 805.6 ao4.1 813.0 813 .o a10.4 809.9 810.0 800.5 811.2 813.0 813.0 803.0 799.2 807.4 ao9. 0 804.6 813.0 804.9 805.9 813.0 805.7 809.5 811.1 813.0 809.8 799.2 8l.3. 0 812.7 809.2 813.0 788.9 790.2 813.0 801.3 813.0 803.5 U3.0 813.0 806.4 807.2 810.8 804.2 813.0 BOO. 7 806.9 802.0 805.7 811.1 803.1 810.9 80B. 7 802.5 804.3 B02. 7 813 .o 798.4 806.7 BOO. 9 806.1 807 .o 809.1 807.5 798.1 801.3 799.0 797.7 809.9 B12.9 808.9 810.9 798.2 802.5 aO·l.5 813.0 B10. 3 806.9 Appendix A SNETTISHAM HYORO!LECTRIC PROJECT· PRELIMINARY • INPUT: SNETOP2.IN RUN 2 -322000 KWH LOAD· BASIC OPER. ·OUTPUT: LOI!GOPR2.00T, CRATOPR2.0UT JAN 799.7 794.1 789.8 784.5 796.5 797.1 788.0 786.2 795.0 796.7 802.4 793.7 799.3 aOl.1 781.5 803.8 798.5 807.2 785.7 779.7 790.6 797.a 794. a 803.6 795.1 796.0 803.1 792.3 798.0 800.2 804.0 794.4 778.9 793.9 802. B 795.1 798.2 766.7 770.8 797.1 786.7 806.9 784.7 807.7 797.2 792.4 795.4 804.9 786.0 805.3 789.8 794.6 786.1 788.0 795.3 786.5 800.5 791.6 784 .a 784.2 782.1 802.9 782.7 795.4 779.5 795.2 796.6 794.7 788.4 776.7 7a1.5 783.9 793 .o 799.7 na.2 795.3 806.2 781.7 789.5 789.6 802.4 798.5 793.1 STATIC 1t1!AD ON LONG LAltli: UJ!ITS (FEET) FEB 780.5 776.9 769.0 766.0 779.1 784.9 773.3 765.5 776.1 777.6 785.2 774.7 789.1 784.0 767.7 791.0 777.7 793.4 765.5 757.9 770.0 776.8 775.9 786.6 77a.2 781.5 785.0 771.2 780.5 784.0 797.6 776.5 760.4 774.7 787.9 763.3 758.9 749.1 749.a 760.8 766.1 756.5 746.5 755.9 761.0 767.3 755.7 774.9 764.4 752.2 771.5 759.4 7a4. 6 745.7 735.3 750.5 756.7 757.5 768.1 764.1 764.1 766.9 750.7 762.2 770.8 783.2 761.5 743.0 754.8 769.7 776.5 756.3 776.6 756.8 742.8 724.4 747.8 726.2 777.5 759.7 767.2 757.2 788.3 768.2 763.3 742 .o 792.2 773.6 784.4 766.5 773.6 756.3 777.4 759.5 790.9. 776.3 771.8 754.2 790.6 778.2 772.6 756.2 782.3 765.9 765.9 745.9 768.2 749.3 775.5 760.5 765.1 74<4.1 7a1.4 763.9 774.1 755.9 765.9 746.3 765.4 746.6 763.2 743.2 785.0 766.4 765.9 748.0 777.9 759.3 761.4 742.1 775.0 755.8 778.3 760.4 781.9 765.9 769.2 751.1 758.4 736.4 707.4 751.5 769.0 758.9 778.9 768.3 787.5 772.6 780.0 767.3 780.3 762.9 790.5 773.8 763.0 751.9 774.3 767.9 772.0 765.5 786.2 767.9 780.6 762.2 775.7 758.4 APR 746.3 743.7 729.6 730.7 740.4 746.8 736.4 727.3 734.4 745.1 751.4 734.4 759.4 744.6 735.8 755.a 740.3 767.4 727.1 714.7 729.2 736.0 738.8 750.3 754.1 746.1 747.6 730.7 742.3 756.7 767.5 742.8 727.4 736.2 750.6 736.5 735.6 706.5 705.1 739.5 737.2 748.3 722.8 755.2 747.6 737.6 740.9 762.2 736.5 762.9 737.0 749.9 727,9 730.6 748.8 725.8 747.0 736.0 730.5 727.5 726.4 750.7 728.7 738.9 725.9 737.5 741.5 748.1 732.9 715.9 732.2 745.0 758.3 758.5 752.4 744.5 760.7 733.0 757.2 749.8 751.6 747.9 740.7 735.1 737.0 718.4 717.0 727.4 735.0 722.0 713.9 724.9 736.5 742.3 718.9 744.2 734.0 728.4 741.5 729.8 757.4 714.6 708.3 716.5 724.2 729.1 739.7 744.7 734.9 739.0 720.6 727.6 744.7 760.8 731.0 716.0 728.5 735.5 726.7 7l1.5 700.2 693.1 726.8 722.4 732.9 708.2 743.0 736.9 725.9 730.8 755.8 723.8 75o.a 730.9 736.8 717.3 717.1 735.9 714.1 735.5 730.6 716.4 718.7 712.7 739.3 719.2 731.3 713.9 723.9 733.9 736.7 721.3 702.0 722.7 736.3 749.1 751.5 742.8 733.8 753.7 728.3 749.8 741.5 744.7 738.8 730.0 JllN 738.0 750.5 714.5 718.0 727.2 734.5 717.3 715.8 730.8 742.6 757.9 714.4 750.0 734.1 738.8 742.6 729.8 766.5 715.6 718.9 718.9 726.8 743.5 742.7 757.1 741.8 740.1 722.0 728.6 759.4 774.8 740.1 722.6 734.7 745.3 734.1 716.3 713.7 69a.3 738.9 721.5 730.4 716.8 752.4 748.6 731.7 738.1 766.5 722.9 754.6 733.8 733.2 720.8 721.1 741.2 n2.9 742.1 741.8 718.8 724.5 710.3 745.7 720.4 734.5 716.5 734.6 740.0 741.5 726.6 700.7 726.7 744.8 752.4 761.2 750.8 750.1 762.3 733.0 761.4 749.1 758.0 751.3 735.5 763.0 780.5 741.7 737.2 750.3 747.2 730.0 734.9 752.5 764.6 788.6 735.3 778.0 763.5 764 .a 76B.a 751.0 798.1 736.8 735.4 747 .? 740.3 769.7 786.6 781.1 763 .2 763.8 747.7 7 51.5 787.4 799.3 773.3 749.7 765.7 780.9 755.0 733.6 751.0 720.2 770.9 742.7 748.a 730.5 777.2 784.3 76:1.5 759.7 800.9 747.4 776.1 769.6 753.1 745.3 763.0 759.9 765.1 766.4 765.0 735.5 745.5 728.4 767.9 735.a 757.5 738.3 756.1 765.7 759.2 754.0 733.0 758.2 760.0 778.7 7a4.6 772.4 771.3 787.4 765.0 787.4 773.5 785.5 769.9 760.4 AUG 810.8 813.0 769.6 772.2 789.0 775.3 760.7 762.4 783.1 795 .4 813.0 762.3 801.5 794.9 801.8 797.0 780.8 813.0 760.8 757.1 773.5 783 .3 804.8 813.0 808.5 802.3 795.8 797.1 781.3 813.0 813.0 813.0 780.4 794.6 813.0 7a3.1 759.1 773.9 756.0 800.6 767.7 784.5 765.6 802.9 813.0 805.3 795.2 813.0 777.1 807.0 Bl.3.0 779.8 776.1 790.1 788.8 807.2 791.2 801.0 761.1 774.9 757.8 802.1 771.1 789.4 760.6 797.9 811.4 789.1 773.2 760.6 782.1 794.2 805.a 812.3 799.6 797.2 813.0 803.5 813.0 792.4 813.0 784.4 790.4 SEP 813.0 813.0 805.3 a13. 0 a13.0 810.6 801.a 788.4 813.0 813.0 813.0 796.4 813.0 813.0 813.0 8l.3. 0 813.0 813.0 786.3 788.2 813.0 813.0 813.0 813 0 813.0 813.0 813.0 813.0 812.4 813.0 813.0 813 .o Bl.1. 4 813.0 813.0 812.1 783.2 789.6 786.3 813.0 782.6 813.0 813.0 813.0 813.0 813.0 813.0 813.0 802.2 813.0 813.0 806.0 811.2 813.0 805.7 8l.3. 0 813.0 813.0 793.3 813.0 786.5 813.0 802.5 813.0 778.8 813.0 813.0 a13.0 790.1 801.4 a13.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 812.3 813.0 798.2 808.2 Page 6 AVG 782 .4 783.5 767.8 768.0 776.9 777 .a 767.9 764.4 773.9 781.0 788.3 768.5 786.7 780.8 775.9 785.2 776.6 795.0 763.9 760.1 768.2 774.2 779.8 786.9 785.6 781.2 782.8 773.1 776.7 788.9 796.0 781.8 767.9 777.9 786.4 775.9 768.3 755.5 750.2 7ao. 3 767.7 779.5 764.6 788.0 785.9 777.6 778.6 793.3 771.0 789.8 778.6 777.9 768.7 772.7 779.1 772.7 781.4 778.6 765.1 769.2 761.6 783.5 766.6 777 .s 762.0 775.9 781.2 780.4 770.0 758.7 771.9 777.5 785.1 789.7 784.6 781.9 791.5 774.7 786.a 781.3 788.4 780.7 777.0 2/25/97 1914 193.5 193.6 193.7 3.918 1919 3.920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1H9 3.940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 3.952 1953 1954 1955 1956 3.957 1958 1959 1960 1961 1962 1963 l.964 1965 3.966 1967 1968 1969 1970 3.971 1972 1973 1974 1975 19H 3.977 3.978 1979 1980 1981 1982 1983 1984 l.985 1986 1987 1988 l.989 l.990 un 1992 1993 1.994 l.995 AVG OCT 824.0 824.0 824.0 824,0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 820.1 824.0 823.9 824 .o 824.0 824.0 824.0 824.0 813.2 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 $24.0 812.8 813.6 824.0 824.0 8%2.9 823.4 824.0 824.0 824.0 824.0 824.0 8%4.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 823.2 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824 .o 824.0 823.5 NOV 824.0 819.7 8H.9 812.5 824.0 821.3 814.2 816.6 815.1 824.0 824.0 821.4 820.9 821.0 811.5 822.2 824.0 824.0 814.0 810.2 818.4 820.0 815.6 824.0 815.9 816.9 824.0 81.6. 7 820.5 822.1 824.0 820.8 810.2 824.0 823.7 820.2 824.0 799.9 801.2 824.0 812.3 824.0 814.5 824.0 824.0 817.4 818.2 821.8 815.2 824.0 811.7 817.9 813.0 816.7 822.l. 814.1 821.9 819.7 813.5 815.3 813.7 824.0 809.4 817.7 811.9 817.1 818.0 820.1 818.5 809.1 812.3 810.0 808.7 820.9 823.9 819.9 821.9 809.2 813.5 815.5 824.0 821.3 817.9 DEC 810.7 805.1 800.8 795.5 807.5 808.1 799.0 797.2 806.0 807.7 813.4 804.7 810.3 812.1 792.5 814.8 809.5 818.2 796.7 790.7 801.6 808.8 805.8 814.6 806 .1 807.0 814.1 803.3 809.0 811.2 815.0 805.4 789.9 804.9 813.8 806.1 809.2 777.7 781.8 808.1 797.7 817.9 795.7 818.7 808.2 803.4 806.4 815.9 797.0 816.3 800.8 805.6 797.1 799.0 806.3 797.5 811.5 802.6 795.8 795.2 793.1 813.9 793.7 806.4 790.5 806.2 807.6 805.7 799.4 787.7 792.5 794.9 804.0 810.7 809.2 806.3 817.2 792.7 800.5 800.6 813.4 809.5 804.1 Appendix A SNITTISRAM HYDROELECTRIC PROJECT PRELIMINARY INPUT, SNETOP2.IN RUN 2 322000 MIIR LOAD BA5rC OPIIR. OUTPUT' LONGOPR2 .Q'OT, CRATOPR2 .OUT JAN 791.5 787.9 780.0 777.0 790.1 795.9 784.3 776.5 787.1 788.6 796.2 785.7 800.1 795.0 778.7 802.0 788.7 804.4 776.5 768.9 781.0 7 87.8 786.9 797.6 789.2 792.5 796.0 782.2 791.5 795.0 808.6 787.5 771.4 785.7 798.9 787.5 787.6 753.8 758.8 788.5 778.2 799.3 774.3 803.2 795.4 784.6 788.4 801.9 782.8 801.6 783.6 793.3 776.9 779.2 786.5 776.1 792.4 785.1 776.9 776.4 774.2 796.0 776.9 788.9 772.4 786.0 789.3 792.9 780.2 769.4 778.4 780.0 789.9 798.5 791.0 791.3 801.5 774.0 785.3 783.0 797.2 791.6 786.7 END OF MONTH LONG LAKE ELEVATION (FBET) FEB 774.3 769.9 760.1 760.8 771.8 777.1 767.5 757.5 766.9 772 .o 778.3 766.7 785.9 775.4 763.2 782.5 770.4 795.6 756.7 746.3 761.5 767.7 768.5 779.1 775.1 775.1 777.9 761.7 773.2 781.8 794.2 772.5 754.0 765.8 780.7 767.3 767.8 735.4 737.2 770.7 768.2 779.2 753.0 784.6 777.5 767.3 770.5 787.3 765.2 789.2 767.2 776.9 756.9 760.3 771.5 755.1 774.9 766.9 757.3 757.6 754.2 777.4 759.0 770.3 75l.l 766.8 771.4 776.9 762.1 747.4 762.5 769.9 779.3 783.6 778.3 773.9 784.8 762.9 778.9 776.5 778.9 773.2 769.4 liAR 757.3 754.7 740.6 741.7 751.4 757.8 747.4 738.3 745.4 756.1 762.4 745.4 770.4 755.6 746.8 766.8 751.3 778.4 738.1 725.7 740.2 747.0 749.8 761.3 765.1 757.1 758.6 741.7 753.3 767.7 778.5 753.8 738.4 747.2 761.6 747.5 746.6 717.5 716.1 750.5 748.2 759.3 733.8 766.2 758.6 748.6 751.9 773.2 747.5 773.9 748.0 760.9 738.ll 741.6 759.8 736.8 758.0 747.0 741.5 738.5 737.4 761.7 739.7 749.9 736.9 748.5 752.5 759.1 743.ll 726.9 743.2 756.0 769.3 769.5 763.4 755.5 771.7 744.0 768.2 760.8 762.6 758.9 751.7 APR 746.1 748.0 729.4 728.0 738.4 746.0 733.0 724.9 735.9 747.5 753.3 729.9 755.2 745.0 739.4 752.5 740.8 768.4 725.6 719.3 727.5 735.2 740.1 750.7 755.7 745.9 750.0 731.6 738.6 755.7 771.8 742.0 727.0 739.5 746.5 737.7 732.5 711.2 704.1 737.8 733.4 743.9 719.2 754,0 747.9 736.9 741.8 766.8 734.8 761.8 741.9 747.8 728.3 728.1 746.ll 725.1 746.5 741.6 727.4 729.7 723.7 750.3 730.2 742.3 724.9 734.9 744.9 747.7 732.3 713.0 733.7 747.3 760.1 762.5 753.8 744.8 764.7 739.3 760.8 752.5 755.7 70.8 741.0 MAY 749.0 761.5 725.5 729.0 738.2 745.5 728.3 726.8 741.8 753.6 768.9 725.4 761.0 745.1 749.8 753.6 740.8 777.5 726.6 729.9 729.9 737 .a 754.5 753.7 768.1 752 .a 751.1 733.0 739.6 770.4 785.8 751.1 733.6 745.7 756.3 745.1 727.3 724.7 709.3 749.9 732.5 741.4 727.8 763.4 759.6 742.7 749.1 777.5 73l.9 765.6 744.8 744.2 731.8 732.1 752.2 733.9 753.1 752.8 729.8 735.5 721.3 756.7 7]1.4 745.5 727.5 745.6 751.0 752.5 737.6 711.7 737.7 755.8 763.4 772.2 761.8 761.1 773.3 744.0 772.4 760.1 769.0 762.3 746.5 774 .o 791.5 752.7 748.2 761.3 758.2 741.0 745.9 763.5 775.6 799.6 746.3 789.0 774.5 775.8 779.8 762.0 809.1 747.8 746.4 758.7 751.3 780.7 797.6 792.1 774.2 774.8 758.7 762.5 798.4 810.3 784.3 760.7 776.7 791.9 766.0 744.6 762.0 731.2 781.9 753.7 759.8 741.5 788.2 795.3 773.5 770.7 811.9 758.4 787.1 780.6 764.1 756.3 774.0 770.9 776.1 777.4 776.0 746.5 756.5 739.4 778.9 746.8 768.5 749.3 767 .1 776.7 770.2 765.0 744.0 769.2 771.0 789.7 795.6 783.4 7 82.3 798.4 776.0 798.4 784.5 796.5 780.9 771.4 JUL 821.8 824.0 780.6 783.2 800.0 786.3 771.7 773.4 794.1 806.4 824.0 773.3 812.5 805.9 812.8 808.0 791.8 824.0 771.8 768.1 784.5 794.3 815 .a 824.0 819.5 813.3 806.8 808.1 792.3 824.0 824.0 824.0 7lll.4 805.6 824.0 794.1 770.1 784.9 767.0 811.6 778.7 795.5 776.6 813.9 824.0 816.3 806.2 824 .o 788.1 818.0 824.0 790.8 787.1 801.1 799.8 818.2 802.2 812.0 772.1 785.9 768.8 813.1 782.1 800.4 771.6 808.9 822.4 800.1 784.2 771.6 7ll3 .1 805.2 816.8 823.3 810.6 808.2 824.0 814.5 824.0 803.4 824.0 795.4 801.4 AUG 824.0 824.0 8l6.3 824.0 824.0 821.6 812.8 799.4 824.0 824.0 824.0 807.4 824 .o 824.0 824.0 824.0 824.0 824.0 797.3 7ll9.2 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 823 .. 824.0 824.0 824.0 822.4 824.0 824.0 823.1 7ll4 .2 800.6 797.3 824.0 793.6 824.0 824.0 824.0 824.0 824.0 824.0 824.0 813.2 824.0 824.0 817.0 822.2 824.0 8l6.7 824.0 824.0 824.0 804.3 824.0 797.5 824.0 8l3.5 824.0 789.8 824.0 824.0 824.0 801.1 812.4 824 .o 824.0 824.0 824.0 824.0 824.0 824.0 824 .o 824.0 823.3 824.0 809.2 819.2 SEP 824.0 824.0 824.0 824.0 824.0 824.0 824.0 815.5 824.0 824.0 824.0 822.8 824.0 824.0 824.0 824.0 824.0 824.0 824.0 809.7 824.0 824 .o 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 817.9 816.3 824.0 824.0 818.5 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 814.6 824.0 824.0 824.0 814.0 824.0 824.0 824.0 819.3 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 823.2 Page 7 AVG 793.4 7!14.5 778.8 779.0 787.9 788.8 778.9 774.7 785.6 792.0 799.3 779.4 797.8 791.8 786.9 796.2 787.6 806.0 774.9 769.9 780.4 785.2 790.8 797.9 796.6 792.2 793.8 784.1 787.7 799.9 807.0 792.8 778.9 788.9 797.4 786.9 778.8 766.4 761.8 791.3 778.2 790.9 775.6 799.0 796.9 788.6 789.6 804.3 782 .o 800.8 789.6 788.9 779.7 783.7 790.1 783.7 792.4 789.6 776.1 780.2 771.8 795.3 777.6 788.5 772.2 787.8 792.2 791.4 780.6 770.1 782.9 788.5 796.1 800.7 795.6 792.9 802.5 785.7 797.8 792.3 799.4 791.7 788.0 2/25/97 19U. 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 l.929 1930 193l. 1932 1933 1934 1935 l.936 l.937 l.938 1939 1940 l.94J. l.942 1943 1944 1945 l.946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1.956 1957 1958 1959 1960 1961 1962 1963 1964 1965 l.966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 355080 360000 359848 360000 360000 360000 360000 360000 346155 360000 360000 3&0000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 345606 346653 360000 360000 358610 359192 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 359057 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 359393 NOV 360000 354593 344421. 345270 360000 356572 347521 350543 348577 360000 360000 356724 356181 356227 343925 357709 360000 360000 347148 342273 352863 354999 349227 360000 349672 350985 360000 350736 355569 357657 360000 356003 342222 360000 359599 355202 360000 327910 329617 360000 344987 360000 347828 360000 360000 351578 352706 357288 348820 360000 344257 352267 345836 350700 357659 347300 357317 354599 346491 348834 346870 360000 341188 351985 344484 351273 352413 355159 353103 340808 345044 342032 340120 356141 359869 354824 357425 340820 346535 349112 360000 356588 352125 Appendix A SNll:T'l'ISI!liM IITOROELECTRIC PROJECT -PIU!LI'IIIINARY • INPUT: SNETOP2. Ill RON 2 -322000 MWB LOAD • BASIC OPER. OUTPUT: LONGOPR2.0UT, CRATOPR2.0CT END OF HONTB LONG LAKE STORAGE (ACRE·FEl!T) lll!C JAN 342946 317810 335175 313233 329154 302949 322541 299083 338439 316148 339409 323052 326795 3086U 324626 298494 336392 312250 3387 85 314207 346398 323476 334568 310370 34244.3 328129 344788 321946 318971 301312 348185 330856 341261 314324 352669 33414.5 324.058 29844.0 316799 288689 330221 304271 340385 313129 336065 311906 347915 325088 336503 314941 337758 319033 347385 323224 332656 305826 340626 317773 343612 321955 348539 339987 335587 312770 315917 291877 334817 310413 346960 326662 336605 312695 340857 312832 300034 271410 305363 l77088 339391 314077 325199 300629 3 52211 327206 322785 295547 353165 332511 339523 322489 332819 308994 336951 313950 349622 330592 324447 306688 350126 330201 329103 307699 335859 319953 324530 298918 3l6859 301903 336830 311461 325002 297991 344002 318905 331650 309620 323008 298917 322204 298354 319676 2954:Z6 347022 323242 320496 298937 337010 314562 316616 293169 336707 310770 338607 315118 33 6045 319497 327317 303308 31.2974 289328 318945 300938 321863 303023 333553 315914 342911 326173 340888 317201 336816 317600 351338 330058 319296 295145 328693 309922 328877 306958 346475 324677 341270 317901 334036 311536 FEB 295561 289940 27 8635 279400 292329 299278 287166 275670 28644.2 292642 300753 286150 310609 297074 282145 306299 290565 322737 274742 262395 280272 287332 288286 301849 296592 296603 300260 280409 294156 305334 320981 293226 271645 285194 303881 286881 287501 248737 250980 290864 287952 301924 270419 308945 299763 286900 290689 31.2472 284473 314923 286745 299001 274919 278899 291912 272901 290311 286481 275375 275724 271874 299618 277368 290370 270527 286309 291852 298984 280951 263780 281321 289848 302051 307620 300809 295097 309197 281829 301578 298422 301509 2Hl49 28991.8 2754ll. 272443 255220 256598 268624 276024 2637 64 252395 26ll.88 273978 281215 261297 290502 273431 263060 286265 268526 300924 252103 237248 254729 263218 266761 280037 284341 275124 276895 256666 270788 287325 301084 271331 252525 263493 280322 263831 262748 228262 226726 267571 264697 277710 246777 285578 276856 265244 269238 294116 263935 2951.25 264520 279532 253171 25606 278291 25006 276247 2631.96 256383 252603 25J.295 280420 254l.2 6 266830 250653 265078 269847 277420 259380 238583 258521. 273944 289196 289391 282357 273376 292177 259493 287919 279475 281503 2771.89 268687 APR HAY 262074 265716 264467 280203 241322 237039 239791 240912 252514 252288 262012 261324 245779 < 2401.08 236382 238469 249417 256767 263671 '271174 270817 288776 241933 236931 272964 279671 260808 260893 253767 266785 269861 271124 255553 255545 2 88161 2 997 66 237129 238219 230256 241936 239256 241933 248532 251.799 254677 272190 267808 271283 273606 287848 261840 270262 267043 268269 244006 245711 252739 253946 273552 290579 292387 310562 257030 268314 238667 246553 253852 261679 262627 274257 251.636 260930 245150 239052 221366 236190 214100 219321 251714 266848 246242 245165 259328 256210 230095 239544 271553 282408 264348 278016 250660 257853 256749 265930 286293 299687 248043 246881 280606 284965 256857 260486 264270 259806 240096 244285 239876 244653 263187 269584 236616 246860 262659 270513 256561 270216 239131 241735 241673 248847 235101 232454 267309 274692 242225 243708 257396 261355 236346 239201. 248135 261481. 260648 268199 264108 20928 244877 251451. 223249 221848 246648 251566 263597 273706 278558 282403 281353 292835 271363 280612 260453 279783 283920 294324 253657 259547 279390 293141 269851 278575 273535 288881 266724 2811.77 255777 262386 295264 317746 270060 264762 279995 276427 255717 261857 282509 297292 327519 262378 314685 295890 297544 302762 280761 340777 264229 262446 276977 268527 303845 325081 318556 295503 296184 277062 281373 326035 342379 3086J3 279356 298771 318241 285380 260238 280826 243495 305517 271228 278297 256405 313686 322318 294505 290900 344511 276623 312279 303840 283219 274274 295141 291161 297978 299679 297764 262684 274518 253786 301539 263010 288227 266172 286649 298763 290247 284272 259528 289024 291273 315549 322731. 307480 306021 326027 297772 326102 308814 323758 304228 292617 357216 360000 303776 307180 328044 311193 292189 294479 320963 336893 360000 294313 345297 336237 345676 339201 318163 360000 292400 287843 308830 321123 349566 360000 3 54381 346345 337491 339317 318799 360000 360000 360000 31.7637 335879 360000 320886 290J.78 309340 286558 344121 301290 322630 298543 347022 360000 350241. 336686 360000 313540 352425 360000 317005 312201 329596 327786 352668 331090 344663 292783 310687 288648 346041 305776 328543 292092 340403 357995 328122 308449 292135 319675 335273 350781 359070 342767 339461 360000 347841 360000 332805 360000 322439 330618 A11G SEP 360000 360000 360000 360000 350155 360000 360000 360000 360000 360000 357055 360000 345701. 360000 327239 349190 360000 360000 360000 360000 360000 360000 338371 358486 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 324703 360000 327079 341641 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 359295 360000 360000 360000 360000 360000 360000 360000 358036 360000 360000 360000 360000 360000 358846 360000 321077 352272 328903 350145 324772 360000 360000 360000 320302 353 085 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 346164 360000 360000 360000 360000 360000 351052 360000 357812 360000 360000 360000 350689 360000 360000 360000 360000 360000 360000 360000 333989 360000 360000 360000 324990 34791.7 360000 360000 346527 360000 360000 360000 315703 347231 360000 360000 360000-360000 360000 360000 329603 354086 345081 360000 360000 360000 300000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 359071 360000 360000 360000 340933 360000 353698 358952 Page 8 AVG 321000 322317 30:Z728 302961 314032 315195 302783 297445 311209 319070 328246 303460 326297 318941 312753 324355 313725 336598 297764 291550 304.626 310754 317710 326588 324703 319454 321396 309366 313755 328837 337993 320240 302870 315342 326046 312741 302659 287394 282056 318342 301736 317844 298928 327914 325276 314899 316150 334548 306635 330054 316126 3151.64 303837 308677 316547 308984 319648 31.6229 299208 304454 294003 323324 301113 31.4690 294350 313900 31.9453 318293 304733 292276 307640 314547 324011 329852 323612 320286 332039 311283 326107 319331 328361 318550 314145 2/25/97 1914 U15 H16 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 193£ 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 U54 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 l.993 1994 1995 AVG OCT 20.8 19.2 20.8 20.4 20.1 20.6 21.0 21.9 21.0 20.1 19.6 20.9 21.0 20.1 20.4 20.7 20.3 19.7 20.6 22.6 21.6 20.9 20.3 18.7 20.4 20.1 20.3 20.5 20.6 19.9 20.6 20.0 21.0 21.4 19.8 21.0 22.8 21.8 21.3 21.7 21.2 21.8 20.6 20.4 20.3 20.9 20.3 19.3 20.6 20.1 20.5 20.6 21.7 19.6 20.1 20.2 20.0 20.5 20.8 21.6 20.5 20.8 20.5 20.9 21.4 21.2 20.5 20.7 21.4 21.4 20. 9 19.6 20.3 20.7 20.8 20.8 19.5 19.4 20.1 20.5 20.1 21.4 20.6 NOV 23.0 22.6 23.3 23.2 23.2 23.5 23.7 24.8 23.6 23.5 22.4 24.0 24.1 23.3 23.3 23.6 23.0 22.7 23.5 24.8 24.7 23.7 23.2 22.6 22.6 22.8 22.9 l3.4 23.4 22.4 22.8 23.1 22.9 24.2 23.2 23.6 25.1 24.7 24 .3 23.4 23.4 25.1 23.7 23.7 23.3 23.3 23.3 22.4 23.2 23.2 23.2 23.7 23.3 22.7 23.5 23.1 23.5 23.1 23.6 24.0 23.9 22.9 23.3 23.6 23.8 23.2 22.8 23.0 23.8 24.2 23.4 22.5 23.4 22.4 23.0 23.1 23.0 22.3 22.6 23.4 23.0 23.4 23.4 DEC 26.7 26.2 l7 .3 26.6 26.4 27.0 27.2 28.3 27.7 26.6 26.1 27.6 27.5 27.3 26.6 27.5 26.5 26.3 26.9 28.4 28.6 27.5 26.3 26.2 26.5 26.5 26.6 27.1 27.4 26.2 25.6 26.8 26.0 27.6 26.5 27.4 28.5 28.0 27.9 27.0 26.9 28.8 27.1 26.7 26.7 26.2 26.8 24.4 26.5 27.1 27.0 27.6 26.8 26.0 27.2 26.6 27.3 26.5 27.1 27.4 27.1 26.3 26.9 27.3 26.9 27.1 26.0 26.6 27.2 27.6 26.7 26.1 25.2 25.7 26.4 26.7 24.4 25 .a 26.3 27.0 26.5 27.2 26.8 Appendix A SNE'I'TISI!AM !fYllROELECTRIC PROJECT -PRELIMINARY -INPUT, SNETOP2. IN RUN 2 -322000 MW11 LOAD -BASIC OPER. • OO'l'PliT' LONGOPR2 .Otrr, CRATOPR2 .Otrr TOTAL NET POWl!R PROM l!OTII LONG LA1'J! UNITS (1111') JAN 26.9 26.5 27.3 26.7 26.6 27.4 27.1 28.1 27.9 26.7 26.3 27.8 27.8 27.5 26.7 27.8 26.6 26.5 26.9 28.4 28.7 27.6 26.5 26.4 26.7 26.9 26.7 27.2 27.5 26.4 26.3 26.8 26.0 27.8 26.8 27.4 28.6 27.8 27.8 27 .2 26.9 28.9 27.0 26.9 27.1 26.3 26.8 25.7 26.8 27.3 27.1 27.8 26.8 26.2 27.3 26.6 27.4 26.7 27.1 27.4 27.1 26.4 26.8 27.5 26.9 27.2 26.2 27.2 27.3 27.6 26.9 26.2 25.6 26.2 26.6 26.9 26.1 26.0 26.6 27.0 26.7 27.4 27.0 11'1!:8 MAl! APR 26.8 23.1 18.6 26.6 23.0 18.8 27.3 23.4 19.1 26.8 23.0 18.5 26.6 22.7 18.4 27.5 23.8 19.5 27.2 23.4 19.0 28.0 24.1 20.0 27.9 23.9 16.7 26.7 23.1 19.1 26.3 22.7 16.8 27.9 24.0 19.0 28.4 24.8 20.0 27.5 23.6 19.7 27.0 23.4 19.9 27.9 24.0 19.7 26.7 23.0 19.0 26.9 23.1 18.8 26.9 23.1 18.9 28.2 23.9 21.5 28.4 24.3 19.7 27.6 23.7 19.5 26.6 22.9 18.5 26.5 22.8 18.7 24.4 21.4 17.5 26.8 23.0 18.7 26.9 23.1 19.3 27.2 23.3 19.3 27.5 23.7 19.1 26.8 23.1 17.0 26.6 23.0 19.0 26.8 23.1 18.7 25.8 22.3 18.0 27.7 23.7 20.0 26.9 23.1 18.7 27.4 23.6 16.6 28.4 24.4 19.9 27.1 23.5 11.0 27 . 6 23 . 3 18. 4 27.4 23.5 18.9 27.8 24.0 19.3 29.1 25.2 20.4 26.8 22.8 18.4 27.0 23.3 17,7 27.3 23.5 19.5 26.3 22.6 18.4 26.8 23.1 19.1 26.0 22.4 18.3 26.8 23.2 18.8 27 • 9 24 • 2 19. 9 27.4 23.6 15.2 28.1 24.4 19.9 26.5 22.6 18.4 26.2' 22.3 17.4 27.6 24.2 19.7 26.5 22.7 18.2 27.5 23.8 19.6 26.7 22.9 l.6.8 27.0 23.6 18.9 27.5 23.6 19.7 27.2 23.6 19.5 26.5 22.8 18.5 26.9 23.1 19.4 27.6 23.7 20.2 26.8 23.3 19.3 20.9 23.3 18.4 26.3 22.5 18.7 27.4 23.6 19.0 27.3 23.4 19.4 27.5 23.3 19.0 27.2 23.4 19.7 26.5 23.3 18.8 25.5 22.5 18.7 26.3 22.8 18.9 27.0 23.3 18.6 26.9 23.2 19.1 25.9 22.6 18.1 26.7 22.8 17.8 26. 8 2 3. 3 18.7 28.1 24.5 20.1 26.8 23.1 19.0 27.4 23.8 19.1 27.1 23.3 18.8 IIAY 16.0 16.3 16.7 16.3 15.8 16.9 17 .o 18.1 14.8 16.7 14.9 17.0 17.4 17.3 17.7 17.4 16.6 16.2 17.4 17.5 18.2 17.4 16.7 16.1 15.1 16.4 16.5 17.1 16.9 15.0 16.3 16.6 16.7 17.5 16.6 15.6 17.7 15.2 17.5 16.8 17.6 17.8 ,16.9 15.6 17.1 16.0 16.8 15.5 16.9 17.0 13.3 17.1 16.2 15.8 17.3 16.5 16.4 15.4 17.1 16.3 16.6 15.7 17.4 17.8 17.8 16.7 16.5 16.4 17.5 16.0 18.0 16.7 16.3 15.6 16.0 16.5 15.6 16.2 16.2 16.7 16.9 17.0 16.6 14.5 14.1 15.3 14.9 14.1 15.1 16.1 16.1 14 .o 14.8 13.4 15.6 15.5 15.5 15.3 15.2 14.8 14.3 16.0 16.0 16.2 15.6 14.4 14.4 H.5 14.6 14.4 15.4 15.6 13.1 14.1 14.7 14.8 15.2 14.8 15.0 15.3 15.8 16.0 15.0 15.9 15.3 15.6 14.4 15.3 14.6 14.8 13.8 15.0 14.8 13.2 15.3 14.8 15.3 15.2 15.1 14.7 13.9 15.8 14.9 16.2 14.0 15.8 15.5 15.7 14.8 14.3 14.5 15.8 15.3 16.0 14.6 14.9 13.8 14.0 14.1 13.7 u.s 14.2 15.1 14.5 15.0 14.9 15.2 14.7 15.9 15.5 14.8 15.5 16.4 16.4 14.9 15.1 14.0 16.7 16.0 16 .o 15.6 15.6 15.1 14.7 lB. 8 17.0 17.2 16.6 15.2 14.7 14.0 15.3 15.0 17.0 16.3 14.9 15.4 15.5 16.3 16.6 15.7 17.7 15.7 17.2 17.1 l.6 .1 17.0 16.3 17.0 15.6 16.7 15.7 15.6 14.7 15.6 15.7 14.7 16.7 16.2 16.2 16.2 16.0 15.0 15.9 l6 .9 16.0 17.6 14.5 16.8 16.2 16.3 15.6 15.3 15.7 17.8 16.3 16.0 15.0 16.5 14.6 14.5 15.5 14.9 15.3 l.4. 7 16.5 16.3 14.7 15.8 AUG 16.3 15.7 16.7 16.6 15.7 16.3 17.2 17.3 16.3 15.9 15.1 17,5 16.5 17.0 16.5 16.3 16.1 15.5 18.7 18.1 17.6 17.5 16.3 15.4 15.5 15.5 16.0 17.5 17 .o 15.4 15.9 16.4 17.2 17.2 16.4 18.2 16.6 17.6 17.7 16.6 17.4 17.2 17.6 16.5 17.3 16.6 16.5 15.2 16.4 16.6 16.2 17.6 16.8 17.0 16.7 16.7 16.0 16.9 17.9 17.2 18.2 15.9 17.6 17.3 16.9 16.5 16.3 16.6 17.8 17.2 17.0 16.2 17.3 15.2 15.7 16.3 15.7 16.5 15.8 16.8 16.8 15.4 16.7 SEP 17.3 17.5 18.7 18.6 17.8 18.4 19.2 18.8 17.9 17.9 17.0 18.9 18.4 18.7 18.2 18.1 17.9 17.3 20.2 19.8 19.4 18.5 17.9 17.8 17.5 17.3 17.7 19.0 19.3 16.7 16.7 17.5 19.2 18.8 17.7 20.8 19.4 19.7 19.6 17.6 19.6 18.5 19.2 18.3 17.5 17.4 18.0 16.4 18.5 18.6 17.8 19.5 18.9 18.8 19.1 17.8 18.3 17.6 20.0 18.1 19.5 17.6 19.4 18.7 19.3 18.5 17.0 17.8 19.4 19.5 18.6 18.3 18.2 17.6 18.4 18.0 17.7 17.8 17.3 19.5 18.5 19.0 18.4 Page 9 AVG 20.4 20.1 21.0 20.6 20.2 21.0 21.2 21.8 20. s 20.5 19.5 21.4 21.4 21.1 20.9 21.1 20.5 20.2 21.5 22.2 22.0 21.3 20.4 20.0 19.6 20.3 20.4 21.2 21.2 19.7 20.2 20.5 20.5 21.5 20.5 21.2 21.9 20.8 21.6 20.9 21.4 22.0 21.1 20.5 21.0 20.4 20.1 19.5 20.7 21.0 19.9 21.5 20.7 20.3 21.2 20.5 20.8 20.3 21.3 21.1 2J..4 20.2 21.2 21.4 21.2 20.8 20.2 20.7 21.5 21.2 21.2 20.3 20.4 20.0 20.4 20.6 19.8 20.1 20.2 21.3 20.7 20.9 20.8 2/25/97 1914 1915 1916 1917 191B 1919 1920 1921 1922 1923 1924 1925 1926 1927 192B 1929 1930 1931 1932 1933 1934 1935 1936 1937 193B 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 195B 1959 1960 1961 1962 1963 1964 1965 1966 1967 196B 1969 1970 1971 1972 1973 1974 1975 1976 1977 197B 1979 19BO 1981 19B2 19B3 19B4 19BS 19B6 19B7 19BB 19B9 1990 1991 1992 1993 1994 1995 AVG OCT 6529 6699 5470 560B 6169 544B 5055 4B3S 5550 5905 6539 5075 5346 5726 5551 5493 5962 6434 5252 5073 SB01 54B7 SB69 6615 6513 6279 6531 5546 5655 7094 6431 6000 5922 56BS 6235 5400 SOB2 4797 530B 6405 52B9 5740 5154 5571 SB7S 5661 5762 7132 5771 6074 5607 525B 592B 6148 5536 SB03 5601 5760 5247 5736 485B 6474 5291 5655 4B92 6017 6394 6106 5042 5519 5310 63B9 5155 6662 6351 6122 6507 6603 6305 5672 6395 5595 SB09 NOV 49BS 5115 4176 42B2 4710 4159 3B60 3691 4237 450B 4992 3B75 40B2 4372 423B 4194 4552 4912 4010 3B73 4429 4190 4481 5050 4973 4794 49B7 4234 431B 5416 4910 4SB1 4522 4341 4760 4123 3BBO 3663 4053 4B90 403B 43B2 3935 4254 44B6 4322 4399 5445 4406 463B 42B1 4015 4526 4694 4227 4430 4276 439B 4006 43BO 3709 4943 4040 4317 3735 4594 4BB2 4662 3BSO 4214 4054 4B7B 3936 SOB6 4B49 4674 496B 5041 4B14 4331 4BB2 4272 4435 DEC 5111 5244 42B2 4390 4B29 4265 3957 37BS 4345 4623 5119 3973 41B6 44B3 4346 4300 466B 5037 4112 3971 4542 4296 4595 517.9 5099 4916 5113 4342 4427 5554 5034 469B 4637 4451 4BB1 4227 397B 3756 4156 5014 4140 4494 4035 4362 4600 4432 4511 SSB3 451B 4755 4390 4117 4641 4B13 4334 4543 43BS 4509 410B 4491 3B03 506B 4143 4427 3B30 4710 5006 47B1 394B 4320 4157 5002 4036 5215 4972 4793 5094 5169 4936 4441 5006 43BO 454B Appendix A SNETTISBAM HYDROELECTRIC PROJECT -PRELIMINARY -INPUT, SNETOP2.IN RUN 2 -322000 MWH LOAD • BASIC OPER. • OUTPUT, LONGOPR2.0UT, CRATOPR2.0UT GENERATION FROM ANNEX, SALMON, AND GOLD CREEK HYDRO (MWH) JAN 4605 4725 3BSB 3956 4351 3B43 3566 3411 3915 4165 4612 35BO 3771 4039 3916 3B75 4206 453B 3705 357B 4092 3B71 4140 4666 4594 4429 4607 3912 39B9 5004 4536 4233 417B 4011 439B 3B09 35BS 33B4 3745 451B 3731 4049 3636 3930 4145 3993 4064 5031 4071 42BS 3955 3709 41B2 4337 3905 4093 3951 4063 3701 4046 3427 4567 3733 39B9 3451 4244 4511 4307 3557 3B93 3745 4507 3636 4699 44BO 431B 4590 465B 444B 4001 4511 3947 409B FEB 4272 43B4 3SBO 3670 4037 3565 330B 3164 3632 3B64 4279 3322 3499 374B 3633 3595 3902 4210 3437 3320 3796 3591 3B41 4329 4262 4109 4274 3629 3701 4643 420B 3927 3B76 3721 40BO 3534 3326 3139 3474 4192 3461 3756 3373 3646 3B45 3705 3771 4667 3777 3975 3670 3441 3BBO 4024 3623 379B 3666 3769 3434 3754 3179 4237 3463 3701 3202 3937 41BS 3996 3300 3612 3475 41B1 3374 4360 4156 4006 42SB 4321 4126 3712 41BS 3661 3B02 MAR 4B7B 5005 40B7 4190 4609 4071 3777 3613 4147 4412 4BB6 3792 3995 4279 414B 4104 4455 4B07 3925 3790 4335 4100 43BS 4943 4B67 4692 4BBO 4144 4225 5301 4.BOS 44B4 4425 424B 4659 4035 3797 35B4 3966 47B6 3952 42B9 3B51 4163 4390 4230 4305 5329 4312 453B 4190 3929 4429 4594 4137 4336 41BS 4304 3921 42B6 3630 4B37 3954 4225 3655 4496 477B 4563 376B 4124 3967 4774 3B52 497B 4745 4574 4B62 4934 4711 423B 477B 41BO 4340 APR 5643 5791 472B 4848 5332 4709 4370 4179 4797 5104 5652 43B7 4622 4950 479B 474B 5154 5562 4540 43BS 5015 4743 5073 571B 5630 542B 5646 4794 4BBB 6132 5559 51B7 5120 4915 53B9 466B 4393 4147 45B9 5537 4572 4962 4455 4B16 5079 4B94 49B1 6165 49B9 5251 4847 4546 5124 5315 47B6 5016 4B42 4979 4536 495B 4199 5596 4574 4BBB 4229 5201 5527 527B 4359 4770 4590 5523 4456 5759 5490 5292 5625 570B 5451 4903 552B 4B36 5021 MAY 6016 6173 5040 516B 56BS 5020 465B 4455 5114 5441 6025 4677 4927 5277 5115 5062 5494 5929 4B40 4675 5346 5057 5409 6096 6002 57B6 601B 5110 5211 6537 5926 5529 545B 5239 5745 4976 46B3 4421 4B92 5902 4B74 52B9 4749 5134 5414 5217 5309 6572 531B 5597 5167 4B46 5463 5666 5102 5347 5161 530B 4B35 52B6 4477 5966 4B76 5211 4SOB 5544 SB92 5627 4647 SOBS 4B93 SBB7 4751 6139 SB53 5641 5996 60BS 5810 5227 SB93 5156 5353 JUN 6176 6337 5174 5305 SB35 5153 47B2 4574 5250 SSB6 61BS 4B01 SOSB 5417 5251 5196 5640 60B6 4969 4799 548B 5191 5552 6257 6161 5940 617B 5246 5349 6711 60B3 5676 5603 537B SB9B 510B 4B07 453B 5022 6059 5003 5430 4876 5270 SSSB 5355 5450 6747 5459 5746 5304 4974 560B SB16 5237 5489 529B 544B 4964 5426 4596 6124 5006 5349 462B 5691 6049 5776 4770 5220 5023 6044 4B77 6302 600B 5791 6155 6246 5965 5366 6049 5292 5495 JUL 664B 6B22 5570 5711 62B2 554B 514B 4924 5652 6013 6659 5169 5445 SB31 5653 5594 6072 6552 5349 5166 590B SSBB 5977 6736 6633 6394 6651 5647 5759 7224 6549 6111 6031 5790 6349 5499 5175 4BBS 5406 6523 53B6 SB45 5249 5674 59B3 5765 SB67 7263 SB77 61BS 5710 5355 6037 6261 563B 5909 5704 SB65 5343 SB41 4947 6593 53B9 57SB 49B2 6127 6512 621B 5135 5620 5407 6506 5250 67B4 646B 6234 6626 6724 6421 5776 6512 5697 5916 AUG SB96 6050 4940 5065 5571 4920 4565 4367 5012 5333 5905 45B4 4B29 5172 5014 4961 53BS SB11 4744 4SB2 5239 4956 5301 5974 SBB2 5671 SB99 5009 5107 6407 SBOB 5419 5349 5135 5631 4B77 45B9 4333 4794 57BS 4777 51B4 4655 5032 5306 5113 5204 6441 5212 54B6 5064 4749 5354 5553 5000 5241 5059 5202 4739 51B1 43BB SB47 4779 5107 441B 5434 5775 5515 4554 49B4 4795 5770 4656 6017 5736 5529 SB77 5963 5695 5123 5775 5053 5246 MINIMUM ANNUAL AELP HYDRO GENERATION • 4BB95. 2ND MIN ANNUAL AELP HYDRO GEII • 492BO. Page 10 SEP TOTAL 57B3 66543 5934 6B279 4B45 55751 496B 57159 5464 62B76 4B26 55527 447 B 51524 42B3 492BO 4916 5656B 5231 601BS 5792 4496 4736 5073 4917 4B66 52B1 5699 4653 4494 5139 4B61 5199 SB60 5769 5562 57 BS 4912 5009 62B4 5696 5315 5246 5036 5523 47 B3 4501 4249 4702 5674 46BS SOBS 4566 4935 5205 5015 5104 631B 5112 5381 4967 465B 5251 5446 4904 5140 4962 5102 464B 5081 4303 5735 46B7 5009 4334 5330 5664 5409 4467 4BB9 4703 5659 4567 5901 5626 5423 5764 SB49 SSB6 5025 5665 4956 5146 66646 51732 54495 SB366 565BO 559B6 60770 65577 53535 51707 59129 55931 59B23 67422 663BS 64000 66569 56525 5763B 72307 65545 61161 60366 57950 6354B 5503B 51795 4BB95 54107 652B6 53906 SBSOS 52533 567 BB 59BB6 57703 SB727 72693 SBB21 61910 57153 5359B 60422 62666 56430 59146 57090 SB706 534B1 SB466 49516 659B7 53934 57634 49B64 61324 65175 62240 51395 56250 54119 65119 52545 67903 64734 6239B 66321 67301 64269 57814 6517B 57025 59210 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 l982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NOV 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 DEC 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Appendix A SNETTISBAM HYDROELECTRIC PROJECT -PRELIMINARY-INPUT, SNETOP2.IN RUN 2 • 322000 MWB LOAD -BASIC OPER. • OUTPUT: L0NGOPR2.00T, CRATOPR2.00T JAN REQUIRED GENERATION FROM TllEl!MAL DNITS (MWB) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FEB 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 APR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 AUG 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 IJIAXIMOM ANN'tJAL TllEl!MAL GENERATION • 0. SEP 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Page II TOTAL 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 - 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 l984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 14497 13355 14465 14202 13970 14357 14623 15238 14661 14012 13680 14556 14611 13981 14237 14389 14120 13712 14376 15779 15015 14594 14141 13036 14231 14013 14161 14283 14322 13846 14333 13923 14664 14876 13823 14657 15854 15219 14860 15102 14797 15153 14324 14237 14119 14566 14143 13411 14383 14034 14261 14348 15127 13645 14005 14074 13917 14301 14469 15034 14270 14403 14314 14549 14886 14767 14264 14400 14923 14925 14542 13648 14168 14440 14489 14518 13596 13502 14033 14301 14017 14929 14367 NOV 15493 15218 15731 15664 15634 15831 15973 16703 15918 15844 15102 16173 16253 15739 15718 159H 15528 153l2 15832 16748 16685 15966 15649 15251 15248 15387 15428 15774 15785 15086 15361 15605 15429 16323 15653 15898 16898 16664 16361 15781 15766 16935 16008 16002 15696 15693 15728 15092 15617 15646 15652 15954 15676 15281 15872 15582 15823 15582 15928 16161 16105 15438 15724 15927 16024 15611 15359 15517 16069 16323 15785 15179 15773 15092 15478 15575 15503 15062 15263 15778 15487 15753 15757 DEC 18605 18285 18997 18551 18371 18829 18921 19682 19287 18515 18166 19253 19139 19002 18541 19189 18482 18300 18741 19775 19931 19147 183 57 18272 18447 18489 18509 18913 19058 18274 17849 18662 18112 19235 18487 19073 19842 19473 19436 18796 18713 20089 18867 18635 18630 18280 18640 16991 18481 18874 18787 19200 18657 18136 18932 18550 18994 18485 18872 19093 18899 18312 18746 19044 18754 18851 18106 18565 18915 19226 18594 18203 17536 17938 18410 18628 16979 17983 18293 18784 18419 18978 18696 Appendix A SNB'l"l'ISRAM ll'l!'Dl!OELECTRIC PRO>JECT -PRELIMINARY -INPUT: Sl!ETOP2 . IN RUN 2 322000 M11H LOAD -BASIC OPEl!. • Oll'l'PUT: LONG0Pll2 .OUT, Cl!ATOPR2 .OUT TOTAL NET ENEl!GY Fit())! BOTB: LONG LAKE UNITS (MIIH) JAN 18732 18471 19023 18602 18530 19083 18866 19574 19419 18622 18314 19347 19345 19130 18595 19357 18551 18466 18749 19781 19987 19232 18462 18419 18625 18719 18617 18971 19139 18376 18340 18701 18119 19337 18693 19110 19898 19369 19394 18941 18717 20168 18790 18763 18880 18346 18702 17888 18666 19043 18862 19368 18649 18235 18985 18557 19075 18570 18856 19111 18910 18423 18648 19165 18773 18925 18283 18915 18990 19251 18771 18270 17858 18226 18549 18714 18174 18081 18511 18843 18604 19103 18820 FEB 16878 16713 17161 16893 16740 17310 17093 17632 17535 16795 16555 17553 17865 17298 17013 17526 16810 16916 16897 17731 17851 17337 16717 16706 15327 16882 16904 H101 17327 16894 16738 16874 16258 17445 16913 17262 17901 17059 17363 17218 17490 18340 16861 17002 17161 16530 16880 16342 16836 17581 17221 17662 16696 16478 17337 16666 17287 16830 16997 17305 17098 16660 16922 17379 16872 16941 16537 17232 17179 17274 17143 16690 16036 16522 16962 16917 16297 16774 16849 17657 16862 17257 17031 16065 16014 16279 15996 15838 16562 16276 16822 16632 16119 15789 16694 17247 16466 16327 16747 16048 16126 16109 16675 16903 16487 15934 15878 14886 16048 16077 16209 16530 16121 15998 16095 15541 16504 16088 16465 16999 16355 16235 16380 16713 17563 15901 16238 16356 15748 16121 15627 16179 16891 16429 17028 15765 15519 16844 15782 16579 15985 16414 16419 16419 15914 16068 16538 16211 16210 15666 16458 16304 16232 16305 16205 15676 15882 16265 16177 15760 15866 16247 17055 16096 16573 16254 APR 12525 12691 12908 1::1487 12399 13145 12780 13455 11236 12868 11358 12810 13497 13258 13395 13263 12791 12700 12775 14463 13256 13148 12486 12599 11821 12603 13013 13008 12867 11452 12839 12580 12121 13458 12578 11193 13416 7388 12425 12709 13003 13755 1ll97 11927 13119 12426 12889 12363 12692 13385 10216 13391 12417 11719 13300 12244 13183 11328 12744 13287 13125 12485 13060 13596 13043 12428 12594 12843 13066 12777 13293 12665 12619 12724 12564 12864 12235 12007 12587 13562 12784 12881 12651 MAY 11179 11367 11666 11356 11037 11783 11856 12631 10294 11607 10358 11874 12102 12068 12341 12138 11589 11280 12143 12173 12698 12138 11669 11214 10489 11441 11526 11944 11798 10473 11381 11589 11639 12200 11592 10887 12312 10563 12225 11679 12251 12372 ,11793 10874 11888 11174 11709 10796 11744 11855 9247 11927 11252 11023 12072 11466 11395 10754 11929 11342 11538 10939 1H43 12402 12397 11617 11506 11421 12174 11122 12510 11607 11381 10852 11136 11471 10834 11303 11320 11648 11743 11850 11562 9805 9530 10343 10015 9539 10190 10873 10879 9417 9991 9061 10515 10452 10440 10332 10273 9946 9650 10784 10781 10929 10546 9723 9740 9101 9837 9725 10377 10504 8844 9536 9907 9979 10232 9978 10089 10307 10648 10804 10084 10750 10336 10509 9724 10346 9874 9945 9301 10089 9976 8933 10335 9983 10299 10230 10169 9884 9370 10644 10071 10917 9409 10681 10420 10577 9957 9615 9765 10636 10298 10795 9840 10021 9303 9456 9530 9257 9782 9551 10206 9802 10090 10053 10571 10225 11050 10829 10333 10792 11459 11429 10411 10532 9723 11651 11152 11159 10848 10852 10551 10274 13105 11865 11957 11535 10575 10216 9753 10675 10434 11872 11322 10357 10731 10828 11381 11555 10944 12320 10965 12002 11909 11427 11851 11328 11829 10847 11622 10971 10879 10211 10878 10919 10275 1166 8 11270 11264 11266 11158 10435 11077 117 85 11116 12268 101:13 11674 11307 11333 10898 10640 10968 12426 11354 11179 10446 11491 10161 10097 10777 10373 10638 10210 11470 11369 10228 11042 AUG 11370 10943 11658 11577 10927 11322 11969 12024 11323 11049 10526 12205 11480 11849 11470 11347 11196 10817 13006 12641 12266 12162 11385 10736 10766 10794 11125 12170 11865 10709 11052 11394 11993 11962 11411 12660 11567 12256 12308 11560 12113 11987 12249 11474 12055 11598 11467 10582 11404 11535 11274 12263 11705 11832 11615 11608 11142 11753 12457 11980 12676 11084 12296 12051 11746 11484 11353 11577 12391 11984 11813 11267 12049 10603 10970 11328 10966 11514 11036 11707 11721 10701 11601 MINIMUM ANNUAL LONG LAKE GENERATION • 159648. 2ND MIN ANNUAL LONG LAKE GEN • 160082. Page 12 SEP TOTAL 11689 167411 11770 164582 12603 171885 12513 168684 12012 165329 12414 171618 12 954 173 644 12700 178769 12095 168229 12052 168008 11451 160082 12768 175398 12418 175560 12620 173009 12262 171079 12191 173196 12062 167673 11694 165248 13644 176161 13346 181757 13077 180555 12475 174766 12061 167160 12021 164087 11821 160515 11646 166534 11956 167475 12795 173417 13009 173527 11234 161664 11227 165384 11808 167966 12972 168207 12661 175786 11922 168081 14033 173647 13065 179023 13261 170257 13236 176557 11857 171332 13242 175406 12463 180490 12936 172464 12352 168076 11766 171638 11758 166964 12102 169206 11043 159648 12505 169476 12508 172247 12028 163184 13114 176258 12775 169971 12680 166112 12876 173333 11969 167825 12365 170077 11880 165915 13 SOB 174604 12209 1731l9 13129 175354 11865 165117 13052 173328 12612 174991 13004 173619 12443 170132 11490 165412 12002 169661 13058 176132 13123 173888 12555 173286 12317 166338 12293 166901 11871 163615 12416 166792 l.2115 168613 1193 0 161905 11999 164512 11656 165556 lll.U 174131 l.2459 169383 12780 171124 12399 170233 2/25/97 1914 H15 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT NOV DEC 260.2 108.1 38.2 312.3 104.0 23.9 185.4 44.9 33.0 270.0 51.3 32.7 250.5 250.4 35.0 201.7 132.9 65.4 209.8 67.1 45.0 140.0 91.8 24.7 238.0 76.5 46.5 201.7 158.0 40.7 220.0 283.1 106.9 260.7 96.9 16.4 160.1 154.8 131.0 257.4 115.7 63.0 135.0 44.7 25.0 193.5 112.9 82.0 463.5 221.8 60.2 224.4 255.4 146.0 333.4 72.8 27.6 315.5 42.2 26.5 189.0 209.8 20.2 276.1 90.7 58.6 186.3 57.1 l.55.l. 498.4 259.3 89.5 393.8 77.4 52.7 216.2 84.8 73.5 300.7 l.93.9 45.6 332.6 8l..8 3l..5 220.5 107.7 33.0 239.1 111.5 44.4 29l..5 159.8 209.6 313.6 11l..l. 24.0 350.0 40.7 28.5 l.50.9 l.47.9 24.3 271.0 97.9 l.39.5 160.5 l.09.8 22.2 193.5 324.4 21.7 155.6 32.6 28.4 187 . 3 4 0 .1 l6 . 9 260.1 146.4 23.6 298.0 64.6 48.4 179.2 147.2 141.7 180.4 48.9 24.8 171.4 ll7.S 224.1 231.1 166.6 24.9 2l3.7 94.5 127.0 236.6 82.5 94.5 308.1 101.2 385.2 353.7 74.3 2l.8 219.2 130.6 76.0 326.9 45.1 55.7 342.3 88.1 29.6 259.6 81.5 34.7 396.3 127.1 18.9 235.9 ll.9.9 24.7 163.4 65.0 2l..3 :l09.7 120.8 66.4 279.5 137.4 25.6 l74.3 44.3 22.1 218.8 87.0 l.7.1 332.2 54.2 16.2 385.4 194.6 89.4 234.l. 38.9 26.8 185.3 75.0 69.2 194.9 47.7 17.0 350,6 95.3 42.0 363.4 89.4 138.0 233.6 112.4 34.4 169.7 95.5 21.5 202.5 48.2 15.5 289.1 57.8 16.0 287.4 40.6 22.0 268.4 34.3 404.5 320.6 157.5 116.9 184.5 130.8 59.1 394.2 92.2 45.8 238.5 80.7 503.5 263.0 30.7 25.9 222.5 72.2 43.1 l.69.6 50.0 38.8 1.92.6 1.26.9 100.0 208.3 133.4 36.3 252.5 107.0 68.0 Appendix A SNETTISBAM HYDROELECTRIC PROJECT -PRELIMINARY -INPUT> SNETOP2.rN RUN 2 • 322000 KWH LOAD • BASIC OPER. • OUTPUT, LONGOPR2.0UT, CRATOPR2.00T JAN 21.0 36.1 18.1 35.0 33.2 68.5 100.0 4l..4 26.1 20.0 31.1 26.9 95.7 36.2 88.6 76.0 4. 9 68.l. 20.0 12.7 34.1 4.6 21.5 34.3 40.4 55.2 Jl..O 8.3 43.6 57.5 102.8 49.5 32.l. 3l..3 45.9 38.6 9. 7 10.9 ll.. 9 l.8. 3 30.4 4l. .9 17.9 50.5 65.1 27.5 41.7 37.2 68.9 56.7 52.9 87.2 28.7 l.3 .2 23.2 10.2 23.0 44.5 39.6 45.0 31.1 30.7 72.9 40.9 35.8 18.7 18.2 54.3 26.6 44.1 66.2 78.2 73.4 61.3 27.0 75.2 34.4 22.9 55.8 51.9 40.3 30.3 40.7 INFLOW TO CRATER LAKE (CFS) FEB MAlt 45.0 36.8 l.7.2 44.6 18.7 19.0 44.5 22.4 16.8 12.7 14.6 12.0 36.2 l.6.0 45.0 22.6 l.0.8 10.2 46.2 38.9 25.3 34.3 ll.9 ll.9 24.1 29.1 14.5 16.4 31.9 40.0 19.1 49.3 9. 0 14.7 101.9 22.3 20.7 15.0 20.5 18.6 61.9 13.4 12.4 13.7 9.9 21.7 12.2 21.0 347.7 64.8 39.5 28.8 15.2 8.2 9.3 16.1 22.8 15.0 37.9 45.1 33.9 31. 3 67.0 19.5 57.7 34.0 17.7 45.4 28.3 9.4 4.3 17.7 32.7 22.5 70.6 33.5 l3 .4 18.4 l.3.4 13.0 47.3 15.2 13.1 16.8 14.2 18.2 16.6 10.9 16.6 17.6 36.8 19.4 27.0 22.9 35.4 31.1 36.1 19.7 42.2 32.3 21.7 22.7 31.0 37.8 32.6 31.7 15.7 24.5 37.6 69.7 10.9 19.8 29.7 35.8 13.9 1:l.4 24.l. 34.:l 28.9 21.5 16.3 30.8 16.6 36.2 26.9 15.1 12.3 18.0 36.4 34.3 38.9 20.9 14.9 22.0 32.3 24.9 31.2 40.6 17.5 9.8 33.3 21.6 94.6 36.1 142.3 58.7 59.7 27.5 59.7 39.4 32.1 16.0 70.9 24.8 54.5 20.3 155.2 71.8 73.6 32.7 17.9 33.3 26.8 62.3 37.5 26.7 APR 52.8 73.9 44.0 23.9 20.7 47.1 20.0 27.5 292.5 62.6 243.l. 36.9 51.6 30.1 42.4 29.2 34.5 45.4 32.9 47.1 40.2 31.0 71,0 29.4 35.6 47.4 22.3 4l..1 28.6 22l..O 39.6 50.2 46.0 45.8 10.9 293.6 27.9 467.5 70.7 37.8 30.0 31.5 25.4 197.3 31.9 34.6 40.0 57 .o 30.4 32.4 514.2 59.5 47.5 47.4 45.0 55.3 44.6 296.9 35.3 47.6 20.5 44.9 38.4 33.7 31.9 46.0 46.8 66.1 32.9 30.3 34.0 82.7 55,6 46.4 102.6 35.1 l.19.1 169.3 126.8 82.5 77.8 117.6 71.9 I!AY 143.9 234.2 89.9 142.0 129.0 118 .l. 53.3 l.25.2 230.6 172.5 286.7 66.8 177.4 92.8 1.93.5 9l.. 9 104.1 211.4 105.1 286.0 83.3 124.3 232.4 138.0 280.4 167.1 121.2 123.8 llO.l. 23l..O 269.5 186.3 149.6 168.7 170.8 160.3 58.8 2l.9. 9 186.5 210.3 72.9 79.9 212.8 227.0 214.2 209.5 189.2 248.3 82.1 152.4 215.3 93.7 169.4 144.4 156.2 207.0 258.4 219.8 l.32 .0 152.5 145.0 214.3 115.6 121.2 126.5 201.8 144.6 177.6 162.9 156.6 118.1 157.0 158.7 297.3 212.1 300.5 222.9 103.5 219.0 266.7 178.8 211.9 170.7 272.3 413.4 369.7 304.2 346.2 216.8 176.5 304.2 299.5 297.5 400.0 3l.6.0 367.l. 349.6 38l..5 381.5 307.5 40l.. 7 284.0 249.2 318.7 213.0 429.3 482.6 334.5 276.3 320.9 351.1 261.8 410.2 376.3 438.3 384.3 433.6 420.7 213.1 332.8 400.2 297.5 351.9 284.7 297.9 227.5 307.9 393.6 405.3 326.5 382.7 356.0 327.9 455.0 293.8 329.7 395.5 291..6 500.8 348.3 355.8 243.7 289.4 231.4 306.5 234.5 328.7 362.2 298.7 380.2 259.5 366.1 425.0 380.0 222.0 367.0 ll6.1 330.4 379.0 357.1 367.6 388.5 296.4 394.7 296.1 336.4 517.2 497.7 370.8 440.7 481.4 4l.6. 3 406.6 398.5 396.4 452.l. 583.9 288.9 325.l. 377.3 528.6 41.9. 6 4l.9. 6 416.3 36.3 234.9 218.9 426.8 428.5 4l.2 .6 401.6 431.5 386.7 361.4 338.1 406.6 l.39. 3 437.3 225.9 201.5 314.1 28.1 385.2 197.9 356.9 208.4 242.2 356.0 330.5 238.9 181.4 443.0 403.4 440.2 372.1 304.8 443.6 225.9 259.2 247.0 296.9 419.7 408.6 205.6 254.7 309.7 269.9 443.6 365.9 344.1 319.8 443.1 443.0 253.2 62.2 300.0 395.4 443,4 153.0 295.7 390.8 190.8 345.2 392.1 454.8 ll0.6 68.3 396.5 336.3 AUG 408.2 468.4 463.5 538.3 590.4 510.7 531.8 359.4 401.5 483.0 566.0 425.0 361 .l. 357.8 377.3 403.3 484.7 473.3 365.9 321.5 509,8 436.8 339.3 486.6 305.2 872.6 488.7 312.7 40l..O 3l.3.5 431.3 334.4 361.1 347.7 398.2 366.6 368.8 305.0 3 88.4 478.5 294.6 429.5 569.2 333.2 390.5 362.9 423.0 573.9 378.8 298.9 366.8 326.2 462.7 428.6 336.0 535.2 428.9 373.1 355.0 543.4 364.0 325.2 367.7 362.3 334.5 301.1 399.7 490.0 354.5 474.4 432.6 428.1 361.9 361.4 327.2 306.1 379.4 468.8 371.6 382.0 337.5 315.8 409.7 SEP 265 .s 388.2 470.6 361.3 411.7 420.1 262.2 391.6 4l.1.l. 502.5 58l..5 399.4 292.2 351.2 342.8 346.2 359.6 361.3 428.5 289.9 315.9 403.4 447.4 398.7 439.4 441.7 330.2 387.0 404 .1 413.8 393.4 444.4 315.6 458.0 458.3 170.5 242.5 282.5 451.5 428.7 326.6 429.8 357.0 398.3 369.5 389.2 435.0 416.3 447.7 370.0 243.5 266.1 427.4 456.7 456.l. 344.5 431.4 426.5 404.8 368.4 424.7 436.3 440.8 403.4 318.5 368.8 388.5 462.1 391.3 422.3 253.0 444.0 192.0 441.7 299.l. 416.5 443.1 462.1 461.7 335.1 461.5 102.6 382.9 Page 13 AVQ l.80.8 2l.7.8 177.3 188.9 2l.4. 8 us. 3 l.60.4 164.3 203.3 206.3 280.1 163.1 l.80.8 l.7l.. 8 l.85. 9 l.83.7 207 .o 227.3 145.2 155.4 167.9 174.3 200.0 238.6 23l. .1 227.9 l.88. 7 l. 7l..4 l.6S .5 2l.l..O 206.5 206.3 l.68.8 172.7 l.97 .l. 132.1 168.4 183.7 170.0 182.5 146.2 180.4 168.9 191.1 175.2 197.0 193.5 251.4 186.8 170.3 230.3 156.8 180.4 192.9 174.4 196.1 200.5 199.3 147.0 185.8 161.3 210.3 164.8 166.2 155.0 185.5 204.1 183.4 146.2 178.9 174.7 194.7 l.89.l. 208.5 180.2 190.3 235.0 198.4 220.2 l.57 .s 169.1 161.5 l.B6. 9 2/25/97 1914 1915 1916 1917 1918 1919 1920 1911 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 U44 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 19a5 19S6 1987 l9a8 1989 1990 1991 1992 1993 1994 1995 AVG 260.2 312.3 185.4 270.0 250.5 201.7 209. a 143.0 140.5 201.7 220.0 260.7 145.1 257.4 146.2 193.5 463.5 224.4 333.4 131.5 132 .a 142.9 186.3 498.4 393.8 216.2 300.7 332.6 180.6 239.1 291.5 313.6 350.0 133.5 271.0 160.5 129.4 145.8 143.1 116.() 298.0 129.8 180.4 146.2 231.1 213.7 236.6 308.1 353.7 219.2 326.9 342.3 124.6 396.3 235.9 163.4 209.7 279.5 174.3 130.5 332.2 127.8 234.1 139.5 194.9 130.5 363.4 233.6 169.7 137.1 231.7 286.6 268.4 320 .6 184.5 394.2 238.5 263.0 222.5 169.6 192.6 208.3 231.4 liOV 158.5 161.4 169.9 169.1 250.4 168.2 171.4 162.8 165.9 161.0 283.1 167 .l 163.5 165.8 169.1 165.7 211.8 255.4 171.2 159.1 151.9 165.2 165.4 259.3 163.6 164.4 193.9 167.9 166.0 158.0 162.6 164.3 168.9 157 .l 159.8 167.6 157.4 165.9 163.9 156.0 171.9 146.1 169.2 163.0 166.6 167.7 165.5 157.3 167.5 162.4 169.4 168.7 165.2 168.5 166 .l 167.8 166.1 168.4 169.4 159.7 171.8 178.3 172.7 163 .a 172.8 164.5 163.2 164.4 169.6 160.5 171.2 166.9 173.9 164.4 161.5 163.0 158.7 166.0 166.5 165.9 160.6 167.5 170.9 DEC 184.5 188.3 194.7 201.1 193.4 196.3 202.0 192.7 188.1 194.7 191.8 194.5 193.8 189.0 202.6 189.0 194.4 190.8 202.4 189.2 174.3 190.6 200.6 188.6 188.6 191.2 185.3 194.3 189.2 182.3 206.9 191.5 205.1 186.9 191.5 192.8 184.2 201.7 193.8 183.5 202.6 171.8 201.9 198.3 192.8 204.5 196.2 330.9 199.4 1a5. 8 196.6 192.9 194.9 199.2 193.2 197.8 191.0 198.1 200.5 19().3 205.7 189.9 202.5 190.8 208.2 l88.6 196.7 191.7 201.6 192.4 204.7 196.1 269.4 194.5 190.6 190.7 428.0 197.3 194.9 195.5 189.4 191.1 199.3 Appendix A S!IETTISRAN HYDROELECTRIC PROJECT· PRELI.IliARY INPUT' SNETOP2.Ill RUN 2 -322000 KWH LOAD -BASIC OPER. • OUTPUT, LO!IGOPR2.00T, CRATOPR2.0UT TOTAL OOTFLOW l'llOM CI!ATER I.AitE • '!'Ullllli:L + SPILL (CP'S) 195.8 199.0 206.5 213 .o 204.1 203.4 214.9 207 .5 197.3 205.9 201.5 204.9 200.0 198.8 214.8 197.2 206.0 199.0 214.7 202.7 187.2 200.8 209.4 ua. 7 198.6 199.5 196.9 205.7 20().3 194.7 200.5 204.2 218.8 197.6 198.9 204.6 194.8 217.7 209.1 194.3 214.6 180.6 216.0 204.5 201.5 214.6 206.8 199.7 209.1 194.9 207.3 2()1.8 208.4 211.4 205.0 210.9 201.5 209.9 213.6 204.1 218.1 200.6 217.3 200.2 220.7 200.0 205.2 198.3 212.5 206.7 214.4 209.1 227.3 201.5 201.3 202.2 202.8 210.0 204.2 206.9 198.6 201.3 204 .a FEB 2ll.. 6 213.2 224.1 227.8 218.6 215.4 228.6 225.2 213.7 221.7 215.1 219.6 204.2 212.8 225.2 209.2 220.2 207.2 233.2 223.6 207.5 217.9 223.8 210.8 246.7 U4.1 208.8 223.5 214.4 201.4 209.2 219.6 238.6 214.1 2ll.. 7 220.3 213.2 247.6 231.4 207.4 218.5 192.6 236.4 217.5 212.6 230.9 222.0 209.5 225.0 199.6 218.9 212.2 228.4 227.8 216.7 230.6 215.3 223.9 231.3 219.1 235.4 214.0 231.6 214.2 240.3 219.4 219.4 209.3 229.0 226 .o 226.2 219.8 244.2 213.4 211.2 215.7 ll9.5 216.7 216.3 208.5 210.9 216.4 219.5 194.5 194.1 211.1 213.8 204.5 lH.8 ll3.8 211.4 201.4 202.5 197.3 207.0 186.4 198.5 207.2 194.4 203.8 187.5 218.2 215.7 195.0 204 .3 207.8 194.8 ll1.7 l9a.o 193.0 210.7 199.0 183.2 189. B 201.8 219.4 202.3 195.9 205.9 201.4 230.3 224.8 192.2 202.7 178.2 225.5 200.7 197.4 214.2 205.3 188.5 205.8 181.7 203.6 194.2 215.0 214.8 194.8 217.1 198.0 209.3 212.0 205.7 219.1 196.4 217.6 200.2 222.7 201.5 204.3 192.6 215.9 216.8 2U.8 194.4 215.2 191.7 191.7 198.1 194.7 201.2 192.1 188.0 194.0 198.7 203.0 API! 169.0 163.0 186.0 191.8 179.3 175.6 193.5 187.5 220.9 172.9 191.4 194.4 168.1 168.7 171.4 170.1 175.0 160.7 193.7 164.2 173.5 178.4 183.6 164.1 177.8 171.7 157.9 181.8 179.5 179.5 157.3 178.3 194.6 167.9 171.6 223.0 181.2 339.8 211.3 170.1 185.3 159.4 205.6 195.7 167.9 188.5 176.4 156.0 182.3 155.9 240.7 174.0 188.2 197.9 170.9 195.3 172 .l 212.4 193.7 173.7 194 .l 168.9 185.8 164.5 195.0 183.5 170.2 170.0 189.0 193.6 179.3 169.1 184.a 158.2 169.9 169.6 170.1 183.2 168.7 163.1 164.1 178.5 181.8 IIAY 141.1 133.8 156.9 160.8 153.1 149.6 159.2 150.2 17a. 7 143.8 l.S2 .1 159.7 143.0 138.9 138 .l 139.6 145.0 135.1 151.6 159.1 128.3 144.6 144.6 137.6 150.6 140.3 133.7 148.7 147.2 139.7 132.7 l.43.4 148 .l 138.7 137.6 167.7 150.0 197 .o 156.8 135.4 146.3 133.4 163.5 160.0 138.8 160.2 146.1 132.4 147 .o 133.2 192.3 150.1 156.7 156.3 141.9 155.2 155.1 162.4 155.8 159.4 174.2 145.8 149.8 134.4 153.7 144.6 137.0 144.0 153.2 174.9 140.5 134.5 157 .o 141.7 143.1 143.6 142.5 138.0 138.1 147.6 129.6 143.6 148. 4 109.0 109.7 125.0 128.3 124.4 123.9 121.0 127 .l 136.2 117.1 117.9 129.7 117.4 113.5 119.0 120.2 119.9 108.6 119 .a 122.9 104.8 117.7 123.6 107.8 118.1 112.9 lll.l 121.2 114.2 112.5 109.8 117.5 121.8 119.1 110.4 124.9 134.5 130.8 122.6 106.1 ll.B. 5 116.9 127.4 124.4 109.4 126.1 122.1 101.9 122.5 112.5 140.8 125 .l 121.5 109.2 120.4 119.6 124.8 131.0 122.1 122.6 125.8 116.4 120.2 116.0 132.3 117.5 l.l6 .1 117.9 124.9 129.0 116.3 110.6 127.4 111.6 117.1 121.0 115.0 109.4 114.2 115.6 109.2 119.6 119.2 102.3 102.3 118.5 120.5 115.7 122.8 121.9 126.1 124.7 115.2 451.8 115.3 112 .l 107.4 116.6 116.5 116.4 228.8 80.2 111.3 92.7 108.4 113.0 103.9 170.1 105.0 104.7 98.4 107.6 220.4 94.4 105.4 99.9 98.9 97.8 89.8 130.0 110.6 108.4 90.7 105.8 105.8 110.8 ll.l.l 91.6 110.7 111.6 254.9 114.3 102.0 260.7 107.3 1()2.9 96.7 lOB .a 104.8 122.0 104.4 109.1 110.2 108.6 110.1 110.6 106.8 125.5 107.1 102.2 102.7 96.3 112.6 117.3 108.3 106.7 102.4 112.2 103.2 138.3 99.1 193.6 99.5 as .1 126.5 120.7 AtrG 193.4 462.5 116.7 114.8 289.7 121.8 120.3 122.3 130.3 251.5 566.0 115.3 128.2 105.1 196.8 179 .l 114.4 473.3 99.1 107.6 101.0 105.5 212.0 411.4 305.2 597.9 164.7 103.8 108.5 313.5 342.4 201.8 101.9 105.0 175.3 99.3 126.9 117.9 110.9 99.9 113.4 104.2 113.0 162.5 97.7 160.2 117.9 573.9 115.1 103.2 366.8 108.1 108.0 99.9 114.1 263.0 235.1 105.0 107.7 105.0 111.6 182.2 108.3 103.5 127.2 106.3 20().3 104.8 112.6 111.9 114.4 l.ll. 2 114.1 272 .5 191.4 107.4 379.4 146.8 371.6 ll.O .4 95.6 127 .a 178.0 SEP 265.5 388.2 246.1 273.5 411.7 365.6 125.3 137 .o 4ll.l 502.5 581.5 131.1 292.2 219.6 342.8 346.2 321.4 361.3 114.7 122.3 110.5 187.8 447.4 398.7 439.4 441.7 330.2 120.1 152.6 413.8 393.4 444.4 110.4 216.7 458.3 99.3 124.5 126.7 119.8 329.1 119.8 225.0 123.7 398.3 307.5 389.2 435.0 416.3 211.0 304.1 243.5 119.7 160.6 247.9 235.3 344.5 431.4 397.3 114.5 240.4 130.8 436.3 121.2 194.0 130.4 227.2 388.5 386.2 127.6 115.0 127.0 444.0 192.0 441.7 299.1 286.9 443.1 462.1 461.7 126.2 308.1 116.1 278.7 Page 14 AVG 182.1 219.0 17a. 4 190.4 216 .3 187 .o 173.5 166.1 192.4 207.5 280.8 174.9 171.2 173.0 187.5 185.1 208.5 227.7 177.7 159.1 146.6 163.7 201.5 239 .s 230.3 229.4 190.1 175.7 163.2 211.5 207.6 207.2 181.5 161.5 198.3 163 .o 160.6 186.0 166.3 165.1 174.8 153.7 172.8 190.2 176.3 198.4 195 .l 252.4 187.7 171.2 230.6 174.7 164.5 193.8 175.3 197.5 2()1.8 200.1 167.0 168.4 185.6 188.9 172.6 160.7 177.0 165.9 205.5 184.6 166.8 164.7 171.2 195.9 190.0 209.5 181.1 191.3 235.9 199.4 220.4 158.1 169.8 166.3 188.0 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 19H 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 l.984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 122.6 141.1 H3.4 145.8 139.5 145.9 148.3 143.0 140.5 143.8 137.9 149.2 145.1 147.8 146.2 144.4 140.6 139.3 149.3 131.5 132.8 142.9 141.9 148.8 127.8 136.5 128.8 145.4 143.2 124.1 127.5 143.6 130.9 133.5 141.0 141.0 129.; 145.8 143.1 116.0 140.5 129.8 152.1 146.2 142.2 137.8 144.0 131.7 139.2 140.0 144.6 149.7 124.6 146.1 150.9 144.5 151.4 141.0 147.6 130.5 158.9 127.8 149.7 139.5 146.4 130.5 129.5 132.4 142. 8 137.1 145.9 141.4 155.1 1n.o 126.0 129.8 140.1 140.1 135.6 142.6 134.2 132.0 139.5 NOV 158.5 161.4 169.9 169.1 161.2 168.2 171.4 162.8 165.9 161.0 166.1 167.1 163.5 165.8 169.1 165.7 166.4 163.6 171.2 159.1 151.9 165.2 165.4 162.1 163.6 164.4 159.7 167.9 166 .o 158.0 162.6 164.3 168.9 157.1 159.8 167.6 157.4 165.9 163.9 156.0 171.9 146.1 169.2 163.0 164.4 167.7 165.5 157.3 167.5 162.4 169.4 168.7 165.2 168.5 166.1 167.8 166.1 168.4 169.4 159.7 171.8 160.7 172.7 163.8 172.8 164.5 163.2 164.4 169.6 160.5 171.2 166.9 173.9 164.4 161.5 163.0 158.7 166.0 166.5 165.9 160.6 167.5 164.7 DEC 184.5 188.3 194.7 201.1 193.4 196.3 202.0 192.7 188.1 194.7 191.8 194.5 193.8 189.0 202.6 189.0 194.4 190.8 202.4 189.2 174.3 190.6 200.6 188.6 188.6 191.2 185.3 194.3 189.2 182.3 199.6 191.5 205.1 186.9 191.5 192.8 184.2 201.7 193.8 183.5 202.6 171.8 201.9 198.3 192.8 204.5 196.2 206.7 199.4 185.8 196.6 192.9 194.9 199.2 193.2 197 .a 191.0 198.1 200.5 190.3 205.7 189.9 202.5 190.8 208.2 188.6 196.7 191.7 201.6 192.4 204.7 196.1 228.4 194.5 190.6 190.7 216.9 197.3 194.9 195.5 189.4 191.1 194.6 Appendix A Slll!TTISIIAM IIYDROl!LECTRIC PROJECT -PRELIMINARY -INPUT, SNETOP2 .lN RUN 2 -322000 MWB LOAD -BASIC OPER. -OUTPUT: LONGOPR2.0UT, CRATOPR2.0UT JAN 195.8 199.0 206.5 213.0 204.1 203.4 214.9 207.5 197.3 205.9 201.5 204.9 200.0 198.8 214.8 197.2 206 .o 199.0 214.7 202.7 187.2 200.8 209.4 198.7 198.6 199.5 196.9 205.7 200.3 194.7 200.5 204.2 218.8 197.6 198.9 204.6 194.8 217.7 209.1 194.3 214.6 180.6 216.0 204.5 201.5 214.6 206.8 199.7 209.1 194.9 207.3 201.8 208.4 211.4 205.0 210.9 201.5 .209.9 213.6 204.1 218.1 200.6 217.3 200.2 220.7 200.0 205.2 198.3 212.5 206.7 214.4 209.1 227.3 201.5 201.3 202.2 202.8 210.0 204.2 206.9 198.6 201.3 204.8 ~L FLOW TO CRATER LAKE TURBINBS (CPS) FI!B 211.6 213.2 224.1 227.8 218.6 215.4 228.6 225.2 213.7 221.7 215.1 219.6 204.2 212.8 225.2 209.2 220.2 207.2 233.2 223.6 207.5 217.9 223.8 210.8 246.7 214.1 208.8 223.5 214.4 201.4 209.2 219. 6 238.6 214.1 211.7 220.3 213.2 247.6 231.4 207.4 218.5 192.6 236.4 217 .s 212.6 230.9 222.0 209.5 225.0 199.6 218.9 212.2 228.4 227.8 216.7 230.6 215.3 223.9 231.3 219.1 235.4 214.0 231.6 214.2 240.3 219.4 219.4 209.3 229.0 226.0 226.2 219.8 244.2 213.4 211.2 215.7 219.5 216.7 216.3 208.5 210.9 216.4 219.5 MAR 194.5 194.1 211.1 213.8 204.5 199.8 213.8 211.4 201.4 202.5 197.3 207 .o 186.4 198.5 207.2 194.4 203.8 187.5 218.2 215.7 195.0 204.3 207.8 194 .a 211.7 198.0 193.0 210.7 199 .o 183.2 189.8 201.8 219.4 202.3 195.9 205.9 201.4 230.3 224.8 192.2 202.7 178.2 225.5 200.7 197.4 214.2 205.3 188.5 205.8 181.7 203.6 194.2 215.0 214.8 194.8 217.1 198.0 209.3 2J.2.0 205.7 219.1 196.4 217.6 200.2 222.7 201.5 204.3 J.92.6 215.9 216.8 211.8 194.4 215.2 191.7 191.7 198.1 194.7 201.2 192.1 J.88. 0 194.0 198.7 203 .o APR 169.0 163 .o 186.0 191.8 179.3 175.6 193.5 J.87 .5 220.9 172.9 191.4 194.4 168.1 168.7 171.4 170.1 175.0 160.7 193.7 164.2 173.5 178.4 183.6 164.1 177.8 171.7 157.9 181.8 179.5 179.5 157.3 178.3 194.6 167.9 171.6 223.0 181.2 339.8 211.3 170.1 185.3 159.4 205.6 195.7 167.9 188.5 176.4 156.0 182.3 155.9 240.7 174.0 188.2 197.9 170.9 195.3 172.1 212.4 193.7 173.7 194.J. 168.9 185.8 164.5 195.0 183.5 170.2 170.0 189.0 193.6 179.3 169 .l 184.8 158.2 169.9 169.6 170.1 183 .2 168.7 163.1 164.1 178.5 181. B IIAY 141.1 133.8 156.9 160.8 153.1 149.6 159.2 150.2 178.7 143.8 152.1 159.7 143.0 138.9 138.1 139.6 145.0 135.1 151.6 159.1 128.3 144.6 144.6 137.6 150.6 140.3 133.7 148.7 147.2 139.7 132.7 143.4 148.1 138.7 137.6 167.7 150.0 197.0 156.8 135.4 146.3 133.4 163.5 160.0 138.8 160.2 146.1 132.4 147.0 133.2 192.3 150.1 156.7 156.3 141.9 155.2 155.1 162.4 l.55. 8 159.4 174.2 145.8 149.8 134.4 153.7 144.6 137.0 144.0 153.2 J.74.9 140.5 134.5 157.0 141.7 143.1 143.6 142.5 138.0 138.1 147.6 129.6 143.6 148.4 109.0 109.7 125.0 128.3 124.4 123.9 121.0 127.1 136.2 117.1 117.9 129.7 117.4 113.5 119.0 120.2 119.9 108.6 119.8 122.9 104.8 117.7 123.6 107.8 118.1 112.9 111.1 121.2 114.2 112.5 109.8 117.5 121.8 119.1 110.4 124.9 134.5 130.8 122.6 106.1 118.5 116.9 127.4 124.4 109.4 126.1 122.1 101.9 122.5 ll.2. 5 140.8 125.1 121.5 109.2 120.4 119.6 124.8 131.0 122 .J. 122.6 125.8 116.4 120.2 116.0 132.3 117.5 116.1 ll.7.9 124.9 J.29 .o 116.3 110.6 127.4 111.6 J.17 .1 121.0 115.0 109.4 114.2 115.6 109.2 119.6 JUL 102.3 102.3 118.5 120.5 115.7 122.8 121.9 126.1 124.7 115.2 J.l1. 9 115.3 112.1 107.4 116.6 116.5 116.4 103.8 80.2 111.3 92.7 108.4 113.0 103.9 112.9 105.0 104.7 98.4 107.6 89.0 94.4 105.4 99.9 98.9 97.8 89.8 130.0 110.6 108.4 90.7 105.8 105.8 110.8 111.1 91.6 110.7 J.11.6 91.1 114.3 J.02.0 120.4 107.3 102.9 96.7 108.8 104.8 J.22.0 104.4 109.1 110.2 108.6 110.1 110.6 J.06.8 125.5 107 .J. l.02.2 102.7 96.3 112.6 117.3 108.3 106.7 J.02.4 112.2 103.2 100.6 99.1 108.4 99.5 85.1 126.5 107.5 AUG 97.9 101.0 116.7 114.8 114.1 121.8 120.3 122.3 116.9 115.5 111.7 115.3 117.0 105.1 113.0 116.9 114.4 107.9 99.1 107.6 101.0 105.5 108.4 107.3 107.5 114.3 104.1 103.8 108.5 98.5 104.5 106.0 101.9 105.0 102.4 99.3 126.9 117.9 110.9 99.9 113.4 104.2 113.0 ll.2. 5 97.7 108.8 110.8 100.3 115.1 103.2 ll.3.5 108.1 108.0 99.9 114.1 106.7 118.7 105.0 107.7 105.0 J.ll. 6 103.8 108.3 103.5 127.2 106.3 100.5 104.8 112.6 111.9 114.4 103.7 109.3 109.2 108.1 107.4 103.8 95.0 105.9 110.4 95.6 127.8 108.9 SliP 120.9 116.3 124.4 122.0 120.9 126.4 125.3 137.0 130.1 124.7 125.5 131.1 127.3 118.3 126.8 129.2 124.1 122.5 114.7 122.3 110.5 126.5 125.2 112.9 118.6 126.2 115.6 120.1 113 .o 120.0 131.8 127.9 110.4 119.5 121.5 99.3 124.5 126.7 119.8 121.1 119.8 122.1 123.7 J.24 .6 131.8 134.8 126.2 123.1 121.1 113.5 J.30.4 ll.9. 7 113.0 110.4 l.l7.6 128.1 123.9 131.1 114.5 126.4 130.8 118.4 121.2 120.7 130.4 116.8 127.2 123.2 127.6 115.0 127.0 110.9 133.1 115.0 109.7 121.4 116.5 113.5 125.5 110.0 109.9 116.1 121.7 Page 15 AVG 150.6 151.9 164.8 167.4 160.7 162.4 168.3 166.1 167.9 159.9 160.0 165.6 156.5 155.4 162.5 157.7 160.5 152.2 162.3 159.1 146.6 158.6 162.3 153.1 160.2 156.2 150.0 160.1 156.8 148.6 151.7 158.6 163.2 153.4 153.4 161.4 160.6 186.0 166.3 147.7 161.7 145.1 170.4 163.2 J.54.0 166.6 161.1 10.8 162.4 148.7 173.2 J.58 .6 160.6 16J.. 5 158.4 164.9 161.6 166.4 164.8 158.9 171.2 154.4 165.6 154.5 172.9 156.7 156.0 154 .l 164.6 164.7 164.1 J.55 .4 171.9 152.0 153.5 155. s 156.8 155.8 155.9 154.5 148.4 159.9 159.5 2/25/97 1914 1915 1916 1917 1918 19l.9 1920 1921 1922 1923 1924 l.925 1926 1927 1928 1929 l.930 1931 1932 1933 1934 l.935 l.936 1937 1938 l.939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 l.954 1955 1956 1957 1958 1959 1960 1961 1962 19£3 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 137.6 171.2 42.1 124.2 111.0 55.8 61.5 .0 .0 57.9 82.1 lll.4 .o 109.7 .0 49.l. 3:12.9 85 .1 184.1 • 0 .0 .0 44.4 349.6 265.9 79.7 Hl.8 l.87 .2 37.4 115.0 164.1 1U.9 219.1 .0 130.0 19.5 .o .0 .0 .o 157.6 .o :l8.3 .0 88.9 75 9 9:1.6 176.4 214.5 79.2 3.82. 3 192.6 .o 250.2 85.0 18.9 58.4 138.5 26.7 .0 17), 3 .0 84.4 .o 48.5 .0 233.9 101.2 26.9 .0 85.8 145.2 113.3 199.6 sa. 5 264.4 98.4 123.0 86.9 27.0 58.4 76.3 91.8 NOV .o .0 .0 • 0 89.2 .0 .0 .o .0 .o 116.9 .o .0 • 0 .o .o 55.4 91.9 • 0 .0 .o .0 .0 97.2 .0 .0 34.2 .0 .0 .o .o .0 • 0 • 0 .0 .o .0 .0 .0 .0 .0 .0 • 0 .0 2.2 .0 • 0 .0 .0 .o .0 .0 .0 .0 .o • 0 • 0 .o .0 .o .0 17.6 • 0 .o .0 .0 .o .0 .0 .0 • 0 • 0 .o .o .0 .0 .0 .0 .0 .0 .0 .0 6. 2 DEC . 0 .0 .0 .o .o .0 .0 .0 .o .0 .0 .0 .o • 0 .0 .0 .o .0 .o .o .0 .0 .0 .0 .o .0 .0 .o • 0 .o 7.4 .0 .0 .0 .0 .o .o .o .0 .0 .0 ,0 • 0 .0 .o .0 .0 124.2 .o .0 .o .0 .o .o .o .o .0 .o .o .o .o .0 .0 .o .0 .o .o .o .0 .0 .0 .0 41.0 .o .0 .o 211.1 .o .o .o • 0 • 0 4. 7 Appendix A SIIETTISB.AM l!YDROELEC'l'RIC PROJECT • PRELIMINARY • INPO'I': SNE'l'OP2. IN RON 2 • 322000 MWB LOAD • BASIC OPER. • OO'I'Pll'l': LONGOPR2.01l'l', C&ATOPR2,01l'l' Jl\N . 0 .0 .0 .0 .o .0 .0 .0 .0 .0 .o .0 .0 .o . 0 .0 .0 .0 .0 • 0 .0 .0 .0 .0 .0 .o .o .0 .0 .0 .0 .0 .0 • 0 • 0 .0 .0 .0 .0 .o .o .0 .0 .0 .0 .0 .0 • 0 .o .o .o .0 .o .o .0 • 0 • 0 • 0 .0 .o .o .0 .0 .0 .0 .0 .0 .0 .0 .o .o .0 .o .0 .o .o .o • 0 .o .0 .0 .o .0 SPILL AT CRATER LA!I:E OO'I'LET (CI'S) I'EB • 0 .0 .0 .0 .o .o .0 .0 .0 .o .o .0 .0 .0 .0 .o . 0 .0 .o .o . 0 .o .0 .0 .0 .0 .o .o .0 .0 .0 .0 .0 .0 .0 .0 .o • 0 .0 .0 .o .0 .o .o .0 .0 .0 .o • 0 • 0 .0 .0 .o .o .0 .0 .a .0 .o .0 .o .o .0 .0 .0 .0 .0 . 0 .o .o .0 .o • 0 . 0 .a .0 .0 .0 .0 .o .0 .0 .o .0 .0 .0 .0 .o .0 . 0 • 0 .o .o . 0 . 0 .0 .o .0 .o .o .0 .o .o • 0 . 0 .0 .0 0 . 0 .0 .o .o .0 .0 .0 .0 .0 .a .0 .0 .o • 0 • 0 .0 .a .o .0 .0 .o .0 .o .0 .o .0 .0 .o .0 .o .0 .o .0 .0 .0 .o .o .0 .o .0 .0 .0 .o .0 .0 .0 .o .0 . 0 .o .0 .0 .0 .0 .0 .o .0 .0 APR .0 .0 .0 .0 .0 .0 • 0 • 0 .0 .o .0 .o . 0 .0 .0 .0 .0 .0 .0 .0 • 0 .0 .o • 0 . 0 • 0 .0 .0 .0 .0 .0 .0 .o .o .0 .0 .0 .0 .0 • 0 • 0 .0 .o .0 .a .0 .0 .0 .a .0 .0 .o . a • 0 .0 .a .0 .0 .o .0 .a .0 .0 .o .o .0 .0 .o • 0 . 0 .a .0 .0 .o • 0 .0 .o .0 .0 .0 .o .0 .0 MAY .0 .0 • 0 .0 .0 .0 .0 • 0 • 0 .o .o .0 .o .0 .0 .0 .0 .0 .0 .0 .0 .o .o .0 .o • 0 • 0 .o .0 .0 .0 .0 .0 .o .o .0 .0 .0 .o .o .o .o .o .0 .o .0 .o .a .a .o .0 .o .0 .0 • 0 .0 .a .0 .0 .o .0 .0 .o .o .0 .0 .o .0 • 0 • 0 .0 .0 .o .o • 0 .o .0 .0 .0 .o .0 .0 .o .o .0 .0 .o .0 .0 .0 .o • 0 .o .0 .o .0 .0 .o .0 .0 .o .0 .0 .o .0 .0 • 0 • 0 . 0 • 0 .o .0 .0 .o .o .0 .o .0 .o .0 .0 .o • 0 • 0 .o .o .o .o .0 .0 .o .0 .0 .0 .o .0 .0 . 0 • 0 .o .o .0 .0 .o .0 .o .o .o .o .a .o .o . 0 .0 .o .o .o • 0 . 0 .0 .0 .o .0 • 0 .0 .0 J1JL .0 .0 .0 .0 .0 .0 .o .o .0 .o 339.9 .0 .0 .o .0 .0 • 0 124.9 .0 .0 .o .0 • 0 .0 57.1 .0 .o .0 .0 131.3 .0 .o .o .o .0 .0 • 0 • 0 .o .o .0 .0 • 0 .0 .o .o .0 163.8 .o .0 140.4 • 0 .0 .o .0 .0 .o .0 .0 • 0 • 0 .0 .o .o .0 .o .0 .o .o .o .0 .0 .0 .o .0 .0 37.6 .0 85.3 • 0 .0 .o 13.2 AUG 95.5 361.5 .0 .o 175.5 .0 .o .0 13 .4 136.0 454.3 .o ll. .2 .0 83.8 62.2 .o 365.4 . 0 • 0 .0 .o 103.6 304.2 197.7 483.6 60.6 • 0 .0 215.0 237.9 95.8 • 0 .o 72.9 .0 .a • 0 .0 .0 .0 .0 .o 50.1 .0 51.5 7.2 473.6 .0 .o 253.3 .0 .0 .o .0 156.3 116.3 • 0 .0 .0 .0 78.4 .o .0 • 0 . 0 99.7 .0 .0 .0 .o 7.5 4.8 163.3 83.3 .0 275.6 51.9 265.7 .0 • 0 .0 69.1 SEP 144.6 271.9 121.7 151.5 290.9 239.2 .0 .0 281.0 377.8 456.0 .0 164.9 101.3 216.1 217 .o l.97. 3 238.8 • 0 • 0 .0 61.2 322.2 285.9 320.8 315.5 214.7 • 0 39.5 293.8 261.6 316.5 .o 97.2 336.8 .0 .o . 0 .0 208.0 .0 102.9 .0 273.6 175.7 254.4 308.8 293.1 90.0 190.6 113.1 .0 47.6 137.5 117.7 216.4 307.5 266.2 .o 114.1 .0 317.9 .o 73.3 .0 110.3 261.3 263.0 .o .0 .0 333.1 58.9 326.7 189.4 165.5 326.6 348.6 336.2 16.1 198.2 .0 157.0 Page 16 AVG 31.5 67.0 13.6 23.0 55.5 24.6 5.1 .o 24.5 47.6 no.s 9.3 14.7 17.6 25.0 27.4 48.0 75.5 15.3 . 0 .o 5.1 39.2 86.4 70.1 73.2 40.1 15.6 6.4 62.9 55.9 48.5 18.3 8.1 45.0 1.6 .0 .o .0 17.3 13 .l. 8.6 2.4 27 .o 22.2 31.8 34.0 102.6 25.4 22.5 57.4 16.1 4.0 32.3 16.9 32.6 40.2 33.7 2.2 9.5 14.4 34.5 7.0 6.1 4.0 9.2 49.6 30.4 2.2 .0 7.1 40.5 18.2 57.5 27.6 35.8 79.1 43.6 64.5 3.6 21.4 6.4 28.5 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1.937 1938 1939 1940 1941 1942 1943 1944 1945 1.94(; 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 l.96l 1962 1963 1964 1965 1966 1967 1968 1969 1970 l.911 U72 1973 U74 l.975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1.993 1994 1.995 AVG OCT 1005.1 1006.6 1006.7 1006.5 1006.6 1006.6 1006. 5 990.7 989.2 1006.4 1006.5 1006.5 991.4 1006.5 1006.7 1006.5 1006.4 1006.6 1006.6 962.5 958.5 990.0 1006.5 1006.5 1006.8 1006.7 1006.5 1006.7 1002.0 1006.8 1006.6 1006.4 1006.5 990.4 1006.7 1006.6 966.0 979.4 977.1 982.5 1006.6 969.5 1006.6 1003.5 1006.5 1006.4 1006.3 1006.5 1006 .6 1006.6 1006.8 1006.4 984.2 1.006.8 1006.9 1006.7 1.006. 5 1006.6 1006.4 982.4 1006.5 977.7 1006.7 997.4 1006.6 979.8 1006.7 1006.5 1006.6 981.0 1000.1 1006.4 1006.8 1006.3 1006.8 1006.9 1.006.6 1006.7 1.006.8 1006.5 1.006.9 1006.9 1000.7 NOV 1006.6 1006.1 1006.1 1006.0 1006.2 1006.0 1005.9 989.9 1000.5 1006 .1 1006.2 1005.9 992.7 1005.9 1004.7 1006.0 1006.1 1006.2 1005.9 984.8 966.5 1004.8 1006.1 1005.9 1006.5 1006.2 1006.4 1006.0 1006.1 U06.6 1006.5 1006 .1 1006.4 991.9 1006.1 1006.1 975.2 979.7 980.8 997.7 1006.1 976.9 1005.8 1005.9 1006.1 1006.2 1006.1 1006.4 1006.2 1006.2 1006.0 1005.9 998.8 1006.0 1005.9 1006.0 1005.8 1006.1 1006.0 990.6 1005.6 1004.6 1005.9 1002.3 1006.0 1003.0 1006.4 1006.4 1006.1 986.5 1006.0 1006.1 1005.7 1006.6 1006.5 1006.4 1006.2 1006.2 1006.3 1006.1 1006.3 1006.4 1002.7 DEC 999.9 999.1 991.2 992.0 1005.6 1001.3 993.4 982.6 989.7 1005.2 1005.4 997.4 991.2 999.7 989.9 999.5 1005.4 1005.5 994.1 972.2 974.6 995.7 993.2 1005.5 995.7 996.5 1005.6 995.6 998.8 1000.4 1005.2 999.4 990.8 990.3 998.6 998.8 990.6 961.4 964.5 995.6 993.1 976.6 991.7 1000.2 1005.5 997.1 996.0 999.3 994.8 1001.9 991.3 996.2 988.2 1000.6 1000.2 993.7 1000.3 1001.8 991.2 982.8 991.9 1005.6 990.1 991.5 991.1 994.3 997.2 999.6 996.9 976.0 992.4 991.1 989.4 1.004. 7 1002.1 997.5 996.8 990.1 994.7 992.3 1001.8 1001.5 994.7 Appendix A Slll!!TTISIIAI! lm)llOII:LECT!!IC PROJECT • PllELIIIINARY -INPUT, SNETOP2. IN Rtl'N 2 -322000 lllliB LOAD -BASIC OPER. • OUTPUT, LONGOPil2 .OUT, CRATOPR2 .OUT JAN 983.0 980.6 974.5 974.3 986.0 985.2 976.8 960.3 975.7 986.1 994.6 978.l. 983.5 984.6 970.1 986.2 988.8 999 .4 975.7 947.5 951.3 981.0 986.7 993.l. 980.7 982.7 988.5 978,1 981.2 984.1 1004.3 980.6 971.3 972.9 991.5 979.9 ,3 .5 935.9 938.5 978.4 976.8 971.2 972.5 1002.1 985.0 986.7 983.7 1004.0 976.0 988.3 976.7 978.6 970.7 980.2 981,1 975.4 985.1 981.8 971.7 959.9 970.9 992.9 970.7 978.7 969.4 978.7 989.2 981.6 977.3 948.9 971.7 972.3 1003.1 994.6 985.8 981.1 1003.6 971.4 978.4 976.1 990.4 983.4 979.3 NET liEAll ON CRATER LAXE tl'NITS !FEET) FEB 961.0 959.1 946.4 947.7 967 .o 971.5 959.9 936.5 950.1 964.8 977.0 953.1 973.3 966.0 951.1 974.9 966.0 984.1 947.0 919 .o 928.8 955.0 965.4 976.4 959.8 965.6 970.9 950.3 961.0 968.7 992.8 960.1 943.7 948.2 976.3 957.5 946.1 903.6 907.9 953 .6 950.1 950.6 943.2 984.1 970.9 965.6 964.1 985.3 955.2 975.1 954,2 963.0 944.1 953.6 957.1 945.5 964.4 960.8 945.8 937.2 943.3 975.7 949.0 956.6 942.2 953.3 968.8 963.7 950.8 924.7 949.5 952.5 985.2 979.7 966.1 965.3 984.6 943.7 957.7 953.0 974.7 962.5 957.8 939.4 933.7 918.3 922.9 940.3 944.6 935.0 911.0 922.8 941.6 952.3 925.5 949.2 939.9 925.5 949.1 938.2 975.5 918. 0 889.9 907.8 927.8 937.3 950.2 97l.8 942.5 945.0 921.4 936.2 947.1 976.7 940.3 918.6 921.6 95l..9 929.1 921.4 877.7 a76. 7 928.0 927.8 926.7 912.3 962.5 944.7 939.9 938.5 968.2 930.3 953.7 928.2 939.4 91.7.0 925 .3 934 .o 915.2 940.0 933.6 917.4 910.4 913.0 949.3 921.4 930.1 913.8 929.3 Hl.6 940.7 924.3 895.0 923.7 936 .2 976.1 961..4 946.1 941.2 970.5 921.8 949.5 935.9 948.5 937.8 933.8 APR 916.2 911.4 889.4 894.0 911. 9 917.4 905.3 882.5 893.8 917.9 929.7 896.0 927.1 913.0 900.5 928.8 910.2 952.1 887.4 860.0 880.4 899.0 909.6 925.7 951.5 918.0 918.2 892.0 908.6 927.7 955 .o 913.5 890.9 897.9 925.5 900.8 894.3 845.5 841.8 901.0 899.6 902.4 a80.9 936.4 918.7 911.2 911.5 946.3 902.5 933.2 901.0 916.5 889.4 896.6 915.6 885.5 916.3 903.9 890.9 882.6 884.7 926.8 890.9 902.7 885.6 902.2 914.9 916.1 897.9 863.6 895.1 913.0 955.7 939.1 924.5 914.5 946.7 894.6 933.4 912.9 925.8 917.8 907.8 MAY 899.8 899.2 869.2 869.9 889.2 899.1 880.2 859.3 903.7 902.6 937.4 873.0 910.4 893.4 882.6 908.7 890.3 937.3 864.4 840.1 861.3 878.0 a93.8 906.7 933.3 900.4 899.2 872 .l. 886.9 934.0 940.1 895.3 869.8 881.0 902.5 910.6 a72.3 861.4 819.1 882.1 877.1 884.0 853.7 936.8 899.5 889.3 892.3 933.6 880.7 915.7 939.6 900.2 869.5 874.9 897.7 865.5 898.2 916.4 868.0 865.0 859.8 909.3 870.2 884.4 862.5 882.4 897.8 901.4 875.7 835.1 874.7 901.0 939 .3 923 .9 915.3 895.5 940.7 893.2 927.9 901.8 914.0 909.5 892.5 901.0 915.5 859.3 868.0 886.4 895.1 865.1 855.7 913.3 907.8 957.5 859.5 916.4 887.2 892.1 902.2 884.9 948.7 857.8 864.1 854.0 875.9 908.5 907.5 952.5 905.4 897.9 869.3 882.2 948.2 959.9 902.9 a71.5 a86.4 908.5 911.5 858.5 a72 .1 825.8 894.6 a67.0 876.5 864.0 947.3 _911.9 897 .a 899.8 950.8 871.9 919.2 944.8 892.3 872.5 874.4 900.8 874.8 914.6 927.0 865.6 879.7 854.a 920.5 866.1 883.2 859.1 892.4 899.9 907.3 878.3 832.9 872.4 905.5 940.5 947.3 926.6 920.4 952.7 889.3 940.9 920.5 922.5 921.0 896.8 926.1 959.1 897 .1 895.1 920.1 909.5 874.4 883.9 938.7 935.3 99l..3 888.4 952.7 922.9 93l..6 941.2 913.4 985.7 883.9 883.8 888.0 890.8 953.0 961.5 981.6 930.4 929.7 904.2 905.0 985.7 991.2 950.1 911.3 933.7 953.8 925.8 889.l. 914.2 857.2 931.8 892.5 903.8 879.9 974.2 953.3 940.0 930.9 986.0 907.2 950.5 985.4 918.0 904.4 918.2 926.8 932.4 947.7 959.1 884.6 905.5 873.2 948.4 883.8 915.3 894.4 920.0 939.5 929.0 915.0 883.4 912.2 922.6 974.8 976.9 957.1 957.4 983.9 928.3 979.1 947.3 963.0 946.9 928.9 AUG 983.4 1006.3 936.0 943.8 974.0 953 .1 918.1 925. a 978.0 98l. 7 1006.8 915.4 981.6 962.1 986.2 982.3 958.1 1007.0 877.8 903.1 907.6 939.7 991.9 998.2 l.006.8 978.1 970.7 944.5 940.3 1007.3 996.8 991.5 931.1 948.8 982.8 917.0 928.4 928.1 896.8 949.1 913.7 942.1 914.0 987.1 966.5 984.3 973.4 1007.2 946.2 979.5 1006.6 936.6 928.8 941.2 954.3 978.3 984.9 974.9 907.3 936.4 898.3 990.2 923.3 950.7 924.4 969.4 984 .B 951.2 910.3 912.5 953.4 971.7 980.4 996.6 990.9 970.7 1007.0 971.1 1006.9 949.1 961.0 982.8 959.2 SEP 1007.1 1007.0 982.9 996.8 1006.8 1000.4 978.4 960.1 1006.7 1006.7 1006.8 960.8 l.006. 7 992.1 1006.8 1006.7 1.002.4 1006.9 918.5 936.0 967.8 983.9 1006.9 1006.9 1006.9 1006 .a 1007.0 974.7 980.8 1007.1 1007.0 1006.9 968.4 981.7 1007.0 956.1 963.2 954.9 939 .3 995.8 941.1 984.9 980.0 1006.8 1000.1 1006.9 1006.8 1007.1 981.9 999.6 1006.8 967.6 979 .s 984.6 983.3 1006.9 1006.7 1003.7 944.7 992.5 937.1 1007 .o 960.9 984.5 954.6 990.9 1007 .1 998.4 946.3 965.8 992.4 1007.0 1006.9 1006.9 1006.9 992.3 1007.0 1007.2 1006.9 984.4 989.8 1003.2 988.8 Page 17 AVG 960.7 965.3 939.8 943.1 958.3 957.5 941.6 928.2 955.2 963.5 981.0 938.3 964.7 956.1 954.0 966.0 955.8 984.6 928.1 913.6 920.6 943.5 963.2 970.3 9n.5 961.6 962.1 942.9 949.1 977.0 986.8 962.8 940.0 945.4 967.6 950.0 931.6 917.8 902.1 949.2 937.6 938.8 933.7 978.9 964.1 961.0 959.1 983.4 946.6 969.1 970.6 951.7 937.3 946.9 955.3 948.8 964.2 964.6 933.3 935.4 928.3 967.3 936.6 948.1 934.1 949.7 96l.8 958.5 940.5 917.1 945.3 957.1 980.3 978.7 969.6 962.4 983.9 952.0 974.0 957.2 967.1 965.0 953.6 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1H8 1969 1970 1971 1972 1973 1974 l975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT NOV DEC 1008.0 1008.0 1002.3 1008.0 1008.0 1001.5 1008.0 1008.0 993.9 1008.0 1008.0 994.7 1008.0 1008.0 1008.0 1008.0 1008.0 1004.0 1008.0 1008.0 996.2 992.1 991.8 985.1 991.0 1002.4 992.3 1008.0 1008.0 1007.7 1008.0 1008.0 1008.0 1008.0 1008.0 1000.1 993.0 994.7 993.7 1008.0 1008.0 1002.3 1008.0 1006.7 992.6 1008.0 1008.0 1002.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 996.9 963.7 986.4 974.6 960.0 968.2 976.8 991.2 1006.7 998.3 1008.0 1008.0 995.8 1008.0 1008.0 1008.0 1008.0 1008.0 998.3 1008.0 1008.0 999.0 1008.0 1008.0 1008.0 1008.0 1008.0 998.3 1003.3 1008.0 1001.4 1008.0 1008. 0 1002.7 1008.0 1008.0 1007.7 1008.0 1008.0 1002.0 1008.0 1008.0 993.5 991.6 993.6 992.6 1008.0 1008.0 1001.0 1008.0 1008.0 1001.5 966.~ 976.8 992.9 980.9 981.7 964.0 978.7 982.7 967.0 983.8 998.9 997.8 1008.0 1008.0 995.9 970.9 978.5 978.6 1008.0 1008.0 994.4 1005.0 1007.9 1002.7 1008.0 1008.0 1008.0 1008.0 1008.0 999.7 1008.0 1008.0 998.6 1008.0 1008.0 1001.7 1008.0 1008.0 997.5 1008.0 1008.0 1004.4 1008.0 1008.0 994.0 1008.0 1008.0 998.9 985.6 1000.2 990.8 1008.0 1008.0 1003.3 1008.0 1008.0 1002.8 1008.0 1008.0 99~.4 1008.0 1008.0 1002.9 1008.0 1008.0 1004.5 1008.0 1008.0 993.9 983.6 992.2 985.2 1008.0 1008.0 994.7 979.3 1006.2 1008.0 1008.0 1008.0 992.9 998.7 1004.1 994.1 1008.0 1008.0 993.9 981.4 1004.6 996.8 1008.0 1008.0 999.7 1008.0 1008.0 1002.1 1008.0 1008.0 999.6 982.5 988.2 978.5 1001.3 1008.0 995.2 1007.9 1008.0 993.7 1008.0 1008.0 992.2 1008.0 1008.0 1007.2 1008.0 1008.0 1004.~ 1008.0 1008.0 1000.0 1008.0 1008.0 999.2 1008.0 1008.0 992.7 1008.0 1008.0 997.3 1008.0 1008.0 994.9 1008.0 1008.0 1004.2 1008.0 1008.0 1004.1 1002.1 1004.5 997.3 Appendix A SNETTISEU.M EIYI)fitOELECTltiC PROJECT -PRELIMINARY -INPUT: SIIETOP2. IN RON 2 -322000 Jllll!l LOAtl -BASIC OPER. • OUTPUT; LONGOPR2 .OOT, CRATOPR2.0UT JAN 986.2 984.0 978.1 978.1 989.5 988.8 980.6 963.8 979.0 989.7 998.1 981.7 987.0 988.0 974.0 989.5 992.3 1002.8 979.6 950.9 954.1 984.4 990.4 996.4 984.0 986.2 991.7 981.7 984.6 987.2 1008.0 984 .1 975.3 976.2 994.9 983 .4 976.6 939.7 942 .o 981.6 980.6 974.0 976.4 1005.8 988.5 990.7 987.3 1008.0 979.8 991.6 980.3 982.1 974.2 983.9 984.6 979.0 988.5 985.5 975.5 963.3 974.9 996 .3 974.6 982.1 973.5 982.0 992.8 985.0 981.2 952.4 975.6 975.9 1008.0 998.1 989.2 984.5 1008.0 975.0 981.9 979.7 993.7 986.8 982.9 STATIC KEAtl ON CRATER LAKE UNITS (FEET} FEll 964.6 962.8 950.4 951.9 970.9 975.4 964.2 940.6 953.7 968.8 980.9 957.0 917.0 969.7 955.4 978.6 970.0 987.9 951.3 922.8 932.1 958.8 969.5 980.1 963.5 969.4 974.5 954.3 964.7 972.3 996.6 964.1 948 .2 951.9 980.0 961.4 949.6 908.0 912.0 957.2 954.5 953.7 947.6 988.1 974.7 969.9 968.1 989.0 959.3 978.7 958.2 966.8 948.2 957.8 961.1 949.7 968.2 965.0 950.1 941.1 947.7 979.5 953.4 960.3 946.8 957.1 972.8 967.4 955.1 928.8 953.9 956.6 990.0 983.6 969.9 969.2 988.5 947.9 961.6 957 .o 978.4 966.3 961.8 943.6 937.9 923.1 927.8 944.8 949 .o 939.9 915.7 927.0 946.2 956.7 930 .o 953.1 944.1 930.2 953.2 942.8 979.5 923.1 894.6 911.9 932.2 942.0 954.4 977.5 946.9 949.1 926.1 940.5 950.9 980.8 944.8 924.0 925.9 956.1 933.7 925.6 883.5 881.8 932.0 932.3 930.2 917.6 967.0 949.0 944.9 943.1 972.4 935.1 957.5 932.7 943.7 921.9 930.2 938.4 920.2 944.4 938.3 922.5 914.9 918.2 953.6 926.5 934.4 919.3 933.8 946.2 944.8 929.2 899.8 928.6 940.8 981.7 965.6 950.3 945.5 975.0 926.2 953.9 940.0 952.7 942.2 938.4 APR 919. a 914.9 893.5 898.3 915.9 921.1 909.6 886.7 897.6 921.8 933.4 900.0 930.4 916.7 904.5 932.4 914.1 955.4 891.8 864.4 884.0 902.9 913.7 929.2 955.7 921.6 921.7 896.2 912.4 930.9 958.3 917.3 895.5 901.8 929.1 904.8 898.1 850.5 846.5 904.5 903.4 905.4 885.7 940.2 922.3 915.5 915.5 949.6 906.5 936.3 904.9 920.1 893.7 901.0 919.2 889.9 920. a 908.0 895.1 886.5 889.3 930.4 895.3 906.4 890.3 906.1 918.9 919.6 902.3 868.0 899.3 916.6 960.0 942.5 928.0 918.2 950.3 898.4 936.9 916 .2 929.4 921.5 911.7 MAY 902.5 901.7 872.4 873.4 892.3 902.0 !83 .8 862.6 908.3 905.4 940.9 876.6 913.0 896.0 885.4 911.4 893.1 939.8 867.9 842.7 864.1 881.0 897 .o 909.2 936.3 903.2 901.5 875.2 889.9 937.1 942.4 898.3 873.4 883.6 905.2 915.3 875.3 872.2 823.3 884.8 880.3 886.4 857.7 940.4 902.1 892.7 895.2 935.9 883.9 917.9 945.0 903.1 872.8 878.6 900.5 869.1 901.0 920.6 871.6 867.8 863 .3 912.0 873.4 887.0 866.0 885.6 900.5 904.1 879.1 838.7 877.7 903.7 942.5 926.3 918.0 898.2 943.4 896.3 930.6 904.3 916.5 912.5 895.6 902.9 917.1 861.7 870.5 888.6 897.2 867.5 857.8 916.3 909.8 959.7 861.9 918.3 889.0 893.9 904.1 886.9 950.4 860.0 866.4 855.5 877.9 910.5 909.3 954.7 907.3 899.6 871.4 884.2 950.0 961.5 904.9 873.6 888.2 910.3 914.1 860.7 875.7 828.1 896.3 869.1 878.2 866.5 949.8 913.7 900.2 901.8 952.4 873.9 920.9 948.2 894.4 874.8 876.7 902.7 877.0 916.9 929.4 867.9 882.1 857.7 922.5 868.2 884.9 861.3 894.4 901.7 909.3 880.6 835.7 874.2 907.2 942.8 949.2 928.6 922.3 954.6 891.0 942.7 922.5 924.1 923.0 898.9 927.2 960.2 898.5 896.6 921.6 911.0 875.7 885.4 940.4 936.6 992.6 890.0 954.0 924.1 932.9 942.6 914.8 986.8 885.2 885.2 889.0 892.1 954.4 962.6 982.9 931.6 930.8 905.6 906.2 986.9 992.4 951.4 912.6 935.0 954.9 927.3 890.8 915.8 858.6 932.9 893.8 905.1 881.4 975.6 954.4 941.5 932.3 987 .o 908.6 951.7 987.2 919.5 905.8 919.3 928.1 933.7 949.1 960.7 886 .o 906.9 874.7 949.7 885.2 916.6 896 .1 921.3 940.8 930.4 916.4 884.9 913.5 923.8 976.3 978.1 958.4 958.7 985.1 929.5 980.3 948.5 964.1 948.3 930.3 AUG 984.4 1007.3 937.3 945.2 975.3 954.6 919.5 927.3 979.5 982.9 1008.0 916.7 982.8 963.2 987.4 983. 6 959.4 1008.0 878.4 904.2 908.4 940.8 993.1 999.2 1008.0 979.2 971.7 945.4 941.4 1008.0 997.6 992.5 932.0 949.7 983.7 917.8 930.0 929.2 897.9 949.9 914.7 943.1 915.2 988.3 967.3 985.5 974.6 1008.0 947.4 980.5 1008.0 937.7 929.8 942.1 955.4 979.4 986.3 975.9 908.4 937.6 899.4 991.3 924.4 951.8 925.9 970.5 985.8 952.2 911.2 913.7 954.6 972.8 981.5 997.6 992.1 971.7 1008.0 972.0 1008.0 950.1 961.7 984.3 960.3 SEP 1008.0 1008.0 984.2 998.1 1008.0 1001.8 979.7 961.5 1008 .o 1008.0 1008.0 962.0 1008.0 993.1 1008.0 1008.0 1003.7 1008.0 919.5 937.1 968.8 985.0 1008.0 1008.0 1008.0 1008.0 1008.0 975.7 981.9 1008.0 1008.0 1008.0 969.4 982.8 1008.0 957.0 964.7 956.3 940.4 996.7 942.3 985.9 981.2 1008.0 1001.0 1008.0 1008.0 1008.0 983.2 1000.6 1008.0 968.7 980.6 985.5 984.5 1008.0 1008.0 1004.7 945.7 993.5 938.2 1008.0 962.0 985.5 956.1 992.0 1008.0 999.4 947.5 967.0 993.7 1008.0 1008.0 1008.0 1008.0 993.4 1008.0 1008.0 1008.0 985.5 990.7 1004.7 989.9 Page 18 AVG 963.1 967.6 942.4 945.9 960.9 960.1 944.4 930.9 958.0 966.1 983.5 941.0 967.1 958.5 956.6 968.4 958.4 986.9 930.8 916 .l 922.7 945.9 965.9 972.7 982.1 964.0 964.4 945.5 951.5 979.2 989.1 965 .3 942.8 947.7 969.9 952.7 934.0 921.5 904.9 951.4 940.2 940.8 936.6 981.6 966.4 963.7 961.7 985.7 949.2 971.3 973.6 954.2 939.9 949.5 957.8 951.5 966.8 967.4 936.1 937.9 931.2 969.7 939.3 950.5 937.1 952.1 965.2 960.9 943.2 919.8 948.0 959.6 983.3 981.0 971.9 964.8 986 .3 954.4 976.4 959.6 969.3 967.5 956.1 2i25i97 1914 1915 1916 1917 1918 1919 1920 19H 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 19U 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1,0 1991 1992 1993 1994 1995 AVG OCT 9.2 10.5 10.7 10.9 10.4 10.9 11.1 10.5 10.3 10.7 10.3 11.2 10.7 11.0 10.9 10.8 10.5 10.4 11.2 9.4 9.5 10.5 10.6 11.1 9.6 10.2 9.6 10.9 10.7 9. 3 9.5 10.7 9.8 9. 8 10.5 10.5 9.3 10.6 10.4 8.5 10.5 9.3 11.4 10.9 10.6 10.3 10.8 9.8 10.4 10.5 10.8 11.2 9.1 10.9 ll.3 10.8 11.3 10.5 11.0 9.5 11.9 9.3 11.2 10.3 10.9 9.5 9.7 9.9 10.7 10.0 10.8 10.6 11.6 9.0 9.4 9.7 10.5 10.5 10.1 10.7 10.0 9.9 10.4 NOV 11.8 l.2 .l. 1L7 12.6 12.0 12.6 12.8 12.0 12.3 12 .o 12.4 12.5 12.1 12.4 12.6 12.4 12.4 12.2 12.8 11.6 10.9 12.3 12.4 12.1 12.2 12.3 11.9 12.5 12.4 11.8 12.2 12.3 12.6 11.6 11.9 12.5 11.4 12.1 11.9 11.6 12.8 10.6 12.6 12.2 12.3 12.5 12.4 11.8 12.5 12.1 12.7 12.6 12.3 12.6 12.4 12.5 12.4 12.6 12.7 11.8 12.8 12.0 12.9 12.2 12.9 12.3 12.2 12.3 12.7 11.8 12.8 12.5 13.0 12.3 12.1 12.2 11.9 12.4 12.4 12.4 12.0 12.5 12.3 DEC 13.7 14.0 14.3 14.8 14.4 14.6 14.9 14.1 13.8 14.5 14.3 14.4 14.3 14.0 14.9 14.0 14.5 14.2 14.9 13.7 12.6 14.1 14.8 14.1 13.9 14.2 l3. B 14.4 14.0 13.5 14.9 14.2 15.1 13.7 14.2 14.3 l3 .6 l4 .4 13.9 13.6 14.9 12.5 14.9 14.7 14.4 15.1 14.5 15.3 14 .• 7 13. B 14.5 14.3 14.3 14.8 14.3 14.6 14.2 14.7 14.8 13 .9 15.2 14.2 14.9 14.1 15.3 13.9 14.6 14.2 14.9 13.9 15.1 14.4 16.8 14.5 14.2 14.1 16.1 l4. 5 14.4 14.4 14.1 14.2 14.4 Appendix A SNETTISRAM HYDROELECTRIC PROJECT • PRELIMINARY • INPllT, SNETOP2 • IN RtlN 2 322000 IIWli LOAD BASIC OPER. 01!TP11T: LONGOPR2 .Ol!T, CRATOPR2 .Ol!T JAN 14.3 14.5 14.9 15.4 14.9 14.9 15.6 14.8 l4 .3 15.1 14.9 14.9 14.6 14.5 15.5 14.4 15.1 14.8 15.6 14.3 13.2 14.6 15.3 14.7 14.5 14.6 14.5 14.9 14.6 14.2 15.0 14.9 15.8 14.3 14.6 14.9 14.1 15.1 14.6 14.1 15.6 13.0 15.6 15.2 14.7 15.7 J.S.1 14.9 15.2 14.3 J.5. 0 14.7 15.0 15.4 14.9 15.3 14.7 15.3 15.4 14.6 15.7 14.8 15.7 14.6 15.9 14.5 15.1 14.5 15.4 14.6 15.5 15.1 16.9 14.9 14.7 14.7 15.1 15.2 14.8 15.0 14.6 14.7 14.9 NET POIII!R FROM CRATER LAEE UNIT (IIW) FEll 15 .J. 15.2 15.8 J.6.0 15.7 15.5 16.3 15.7 15.1 15.9 15.6 15.5 14.8 15.3 15.9 15.2 15.8 J.5.1 16.4 15.3 14.3 15.5 16.0 15.3 17.6 15.4 15.1 15.8 15.3 14.5 15.4 15.7 16.7 15.1 15.4 15.7 15.0 16.6 15.6 14,7 15.4 13.6 16.6 15.9 15.3 16.6 15.9 15.3 16.0 14.5 15.5 15.2 16.0 16.1 15.4 16.2 15.4 J.6.0 16.2 15.2 16.5 15.5 16.3 15.2 16.8 15.5 15.8 15.0 16.2 15.5 16.0 15.5 17.9 15.5 15.2 15.5 16.0 15.2 15.4 14.8 15.3 15.5 15.6 13.6 13.5 14.4 14.7 14.3 14.0 14.8 14.3 13.8 14.2 14,0 14.2 13.1 13.9 14.2 13.7 14.2 13.6 14.9 14.3 13.1 14.1 14.5 13.7 15.3 13.9 13.5 14.4 13.8 12.9 13.8 14.1 15.0 13.8 13.9 14.2 13.8 15.0 14.6 13.2 14.0 12.3 15.3 14.3 13.9 15.0 14.3 13.6 14.2 12.9 14.0 13.6 14.6 14.8 l3. 5 u.s 13.8 14.5 14.4 13.9 14.9 13 .B 14.9 13.8 15.1 13.9 14.3 13.5 14.8 14.4 14.5 13.5 15.6 13.7 13.5 13.8 14.0 13.8 13.5 13.1 13.7 13.8 14.1 APII. 11.5 11.0 12.3 12.7 12.1 12.0 13.0 12.3 14.7 11.8 13.2 12.9 11.6 11.4 11.5 11.7 11.8 ll.4 12.8 10.5 ll.3 ll.9 12.4 11.3 12.6 11.7 10.8 12.0 12.1 12.4 11.2 12.1 12.9 11.2 11.8 14.9 12.0 21.3 13.2 11.4 12.4 10.7 13.5 13.6 11.5 12.8 11.9 11.0 12.2 10.8 16.1 11.8 12.4 13.2 11.6 12.8 11.7 14.3 12. B 11.4 12.8 11.6 12.3 11.0 12.8 12.3 11.6 11.6 12.6 12.4 11.9 11.5 13.1 11.0 11.7 11.5 12.0 12.2 11.7 11.1 11.3 12.2 12.2 MAY 9.4 8.9 10.1 10.4 10.1 10.0 J.0.4 9. 6 12.0 9. 6 10.6 10.4 9.7 9.2 9.1 9.4 9.6 9.4 9.7 9.9 8.2 9.4 9.6 9.3 10.4 9.4 8. 9 9.6 9. 7 9. 7 9.3 9.5 9.6 9.1 9.2 11.3 9. 7 12.6 g. 5 8.9 9.5 8. 8 10.4 11.1 9.3 10.6 9.7 9.2 9. 6 9.1 13.4 10.0 10.1 10.2 9.5 10.0 10.3 11.1 10.0 10.2 11.1 9.8 9.7 B.B 9. 8 9.5 9.1 9.6 10.0 10.8 9.1 9.0 11.0 9.7 9.7 9.5 10.0 9.2 9.5 9. 9 8.8 9.7 9.8 7.3 7.5 8.0 B. 3 8.2 8.2 7.8 8.1 9.2 7.9 8.4 8.3 8.0 7.5 7.9 8.1 7.9 7.7 7.6 7.9 6. 6 7.7 8.3 7.3 8.4 7.6 7.4 7.8 7.5 7.9 7.8 7.9 7.9 7.8 7.4 8.5 8. 6 8. 5 7.5 7.1 7.6 7.6 8.2 8.8 7.4 8.4 8.2 7.2 7.9 7.7 9.9 8.3 7.9 7.1 8.1 7.8 8.5 9. 0 7.8 8.0 8.0 8.0 7.7 7.6 8.4 7.8 7.8 7.9 8.1 B.O 7.5 7.4 8. 9 7.9 8.1 8.3 8.1 7.2 8.0 7.9 7.5 8.2 7.9 7.0 7.3 7.9 8.0 7.9 8. 3 7.9 8. 3 8. 7 8. 0 8.2 7.6 7.9 7.4 8.1 8.1 7.9 7.6 5. 3 7.3 6.1 7.2 8.0 7.4 8.2 7.3 7.2 6.6 7.2 6.5 7.0 7.4 6. 8 6.9 6.9 6.2 8. 6 7.5 6.9 6.3 7.0 7.1 7.2 8.0 6.5 7. 7 7. 7 6.7 7.7 7.2 8.8 7.3 6. 9 6.6 7.5 7.3 8.6 7.4 7.2 7.4 7.0 7.8 7.3 7.3 8.3 7.3 7.1 7.1 6.5 7.4 7.9 7.4 7.7 7.4 8.0 7.3 7.4 6.8 7.9 7.0 6.1 8.9 7.4 AU(l 7.2 7.5 8.1 8.1 8.3 8.6 8.2 8.4 8. 5 8.4 8 .4 7.8 8. 5 7.5 a .3 8.5 8.1 a.1 6.5 7.2 6.8 7.4 8.0 8.0 8.0 a.3 7.5 7.3 7.6 7.4 7.7 7.a 7.0 7.4 7.5 6.8 8.7 8.1 7.4 7.0 7.7 7.3 7.7 8. 2 7.0 8.0 8.0 7.5 8.1 7.5 a.5 7.5 7.5 7.0 8.1 7.8 8.7 7.6 7.3 7.3 7.4 7.6 7.4 7.3 8.7 7.7 7. 4- .7.4 7.6 7.6 a.1 7.5 8.0 B .1 8.0 7.7 7.a 6. 9 7.9 7.8 6.8 9. 3 7.8 SBP 9.0 8.7 9.1 9.0 9.0 9.4 9.1 9.8 9. 7 9.3 9.4 9.4 9.5 8. 7 9. 5 9.7 9.2 9.2 7.8 8.5 7.9 9. 2 9.4 8.4 8.9 9.4 8.6 a.7 8.2 9.0 9.9 9.6 7.9 B. 7 9.1 7.1 a .9 9.0 8.4 9.0 8.4 8.9 9.0 9.3 9.8 10.1 9.4 9.2 8.8 8.4 9.8 B .6 8.2 8.1 8.6 9.6 9.3 9.8 a.o 9.3 9.1 8.9 8.6 8. 8 9.2 8.6 9. 5 9.1 9.0 8.~ 9.4 8. 3 10.0 8.6 8. 2 8. 9 8.7 8.5 9.4 8.0 8.1 8. 7 8.9 Page 19 AV<l 10.8 10.9 ll.. 5 11.7 11.5 11.6 ll.8 11.5 11.9 11.5 11.6 11.6 11.2 11.1 11.5 11.3 11.4 11.1 11.3 10.8 10.1 11.2 11.6 11.1 11.6 11.2 10.7 11.2 11.1 10.8 11.1 11.3 11.4 10.8 11.0 11.4 11.1 12.6 11.2 10.4 11.3 10.1 11.9 11. 9 11.1 ll..9 11.5 11.0 11.4 10.7 12.4 11.3 11.2 11.4 11.3 11.6 11.6 11.9 11.5 11.0 11.9 11.1 11.6 10.9 12.0 11.1 11.2 11.0 11.5 11.2 11.6 11.1 12.5 11.1 11.1 11.1 11.5 11.0 11.3 11.0 10.7 ll.. 5 11.3 2/25/97 1914 1915 lUG 1917 1918 1U9 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 JWG OCT 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1002.8 1013.4 1019.0 1019.0 1019.0 1005.7 1019.0 1017.7 1019.0 1019.0 1019 .o 1019.0 997.4 979.2 1017.7 1019.0 1019.0 1019 .o 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1004.6 1019.0 1019.0 987.8 992.7 993.7 1009.9 1019.0 989.5 1019 .o 1018.9 1019.0 1o19 .a 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1011.2 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1003.2 1019.0 1017.2 1019.0 1015.1 1019.0 1015.6 1019.0 1019.0 1019.0 999.2 1019.0 1019 .o 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1015.5 NOV 1013.3 1012.5 1004.9 1005.7 1019.0 1015.0 1007.2 996.1 1003 .3 1018.7 1019.0 1011.1 1004.7 1013.3 1003.6 1013.0 1019.0 1019.0 1007.9 985.6 987.8 1009.3 1006.8 1019.0 1009.3 1010.0 1019.0 1009.3 1012.4 1013.7 1018.7 1013.0 1004.5 1003.6 1012.0 1012 .s 1003.9 H5.0 978.0 1008.8 1006.9 989.6 1005.4 1013.7 1019.0 J.010.7 1009.6 1012.7 1008.5 J.OJ.5.4 1005.0 J.009 .9 1001.8 10J.4.3 1013.8 1007 .4 1013.9 1015.5 J.004.9 996.2 1005.7 1019.0 1003.9 J.005 .1 1004.9 1007.8 1010.7 1013.1 1010.6 989.5 1006.2 J.004. 7 1003.2 1018.2 1015.5 1011.0 1010.2 1003.7 1008.3 J.005.9 1015.2 1015.1 1008.3 Dl!:C 997 .2 995.0 989.1 9U.l 1000.5 999.8 99l. 6 974.8 990.0 1000.7 1009.1 992.7 998.0 999.0 985.0 1000.5 1003.3 1013.8 990.6 961.9 965.1 995.4 1001.4 1007.4 995.0 997.2 1002.7 992.7 995.6 998.2 1019.0 995.1 986.3 987.2 1005.9 994.4 987.6 950.7 953.0 992.6 991.6 985.0 987.4 1016.8 999.5 1001.7 998.3 1019.0 990.8 1002.6 991.3 993.1 985.2 994.9 995.6 990.0 999.5 996.5 986.5 974.3 985.9 1007.3 985.6 993.1 984.5 993.0 1003.8 996.0 992.2 963.4 986.6 986.9 1019.0 1009.1 1000.2 995.5 1019.0 986.0 992.9 990.7 1004.7 997.8 993.9 Appendix A SNETTISBAM HYDROELECTRIC PROJECT • PRELIMINARY INPUT, SNETOP2.IN RUN 2 322000 MNH LOAD • BASIC OPl!:R. -OUTPUT, LONGOPR2.0UT, CRATOPR2.0UT Jlll! 975.6 973.8 961.4 962.9 981.9 986.4 975.2 951.6 964.7 979.8 99l.9 968.0 988.0 980.7 966.4 989.6 981.0 998.9 962.3 933.8 943.1 969.8 980.5 991.1 974.5 980.4 985.5 965 .3 975.7 983.3 1007.6 975.1 959.2 962.9 991.0 972.4 960.6 919 .o 923.0 968.2 965.5 964.7 958.6 999.1 985.7 980.9 979.1 1000.0 970.3 989.7 969.2 977.8 959 .2 968.8 972.1 960.7 979.2 976.0 961.1 952.1 958.7 990.5 964.4 971.3 957 .a 968.1 983.8 978.4 966.1 939.8 964.9 967.6 1001.0 994.6 980.9 980.2 999.5 958.9 972.6 963.0 989.4 977.3 972.8 I!Nll OF MONTI! CRATER LAD ELEVATION (FEET) FEll 954.6 948.9 934.1 938.8 955.8 960.0 950.9 926.7 938.0 957.2 967.7 94l.O 964.1 955.1 941.2 964.2 953.8 990.5 934.1 905.6 922.9 943.2 953.0 965.4 988.5 957.9 960.1 937.1 951.5 961.9 991.8 955.8 935.0 936.9 967.1 944.7 936.6 894.5 892.8 943 .0 943.3 941.2 928.6 978.0 960.0 955.9 954.1 983.4. 946.1 968.5 943.7 954.7 932.9 941.2 949.4 93l. 2 H5.4 949.3 933.5 925.9 929.2 964.6 937.5 945.4 930.3 944.8 957.2 955.8 940.2 910.8 939.6 95l.8 99:l.7 976.6 961.3 956.5 986.0 937.2 964.9 951.0 963.7 953.2 949.4 930.8 925.9 904.5 909.3 926.9 932.1 920.6 897.7 908.6 932.8 944.4 911.0 941.4 927.7 915.5 943.4 925.1 966.4 902.8 875.4 895.0 913.9 924.7 940.2 966.7 932.6 932.7 907.2 923.4 941.9 969.3 928.3 906.5 912.8 940.1 915.8 909.1 86l.5 857.5 915.5 914.4 916.4 896.7 951.2 933.3 926.5 926.5 960.6 917.5 947.3 915.9 931.1 904.7 912.0 930.2 900.9 931.0 919.0 906.1 897.5 900.3 941.4 906.3 917.4 901.3 917.1 929.9 930.6 913.3 879.0 910.3 927.6 971.0 953.5 939.0 929.2 961.3 909.4 947.9 927.2 940.4 932.5 922.7 APR 913.5 912.7 883.4 884.4 903.3 913.0 894.8 873.6 919.3 916.4 951.9 887.6 924.0 907 .o 896.4 922.4 904.1 950.8 878.9 853.7 875.1 892.0 908.0 920.2 947.3 914.2 912.5 886.2 900.9 948.1 953.4 909.3 884.4 894.6 916.2 926.3 886.3 883.2 834.3 895.8 891.3 897.4 868.7 951.4 913.1 903.7 906.2 946.9 894.9 928.9 956.0 914.1 883.8 889.6 911.5 880.1 912.0 931.6 882.6 878.8 874.3 923.0 884.4 898.0 877.0 896.6 911.5 915.1 890.1 849.7 888.7 914.7 953.5 937.3 929.0 909.2 954.4 907.3 941.6 915.3 927.5 923 .5 906.6 IIAY 913.9 928.1 872.7 881.5 899.6 908.2 878.5 868.8 927.3 920.8 970.7 872.9 929.3 900.0 904.9 915.1 897.9 961.4 871.0 877.4 866.5 888.9 921.5 920.3 965.7 918.3 910.6 882.4 895.2 961.0 972.5 915.9 884.6 899.2 921.3 925.1 871.7 886.7 839.1 907.3 880.1 889.2 877.5 960.8 924.7 911.2 912.8 963.4 884.9 931.9 959.2 905.4 885.8 887.7 913.7 888.0 927.9 940.4 878.9 893.1 868.7 933.5 879.2 895.9 872.3 905.4 912.7 920.3 891.6 846.7 885.2 918.2 953.8 960.2 939.6 933 .3 965.6 902.0 953.7 933.5 935.1 934.0 909.9 938.2 971.2 909.5 907.6 932.6 922.0 886.7 896.4 951.4 947.6 1003.6 901.0 965.0 935.1 943.9 953.6 925.8 997.8 896.2 896.2 900.0 903.1 965.4 973.6 993.9 942.6 941.8 916.6 917.2 997.9 1003.4 962.4 923.6 946.0 965.9 938.3 901.8 926.8 869.6 943.9 904.8 916.1 892.4 986.6 965.4 952.5 943.3 998.0 919.6 962.7 998.2 930.5 916.8 930.3 939.1 944.7 960.1 971.7 897.0 917.9 885.7 960.7 896.2 927.6 907.1 932.3 951.8 941.4 927.4 895.9 924.5 934.8 987.3 989.1 969.4 969.7 996.1 940.5 991.3 959.5 975.1 959.3 941.3 995.4 1018.3 948.3 956.2 986.3 965.6 930.5 938.3 990.5 993.9 1019.0 927.7 993.8 974.2 998.4 994.6 970.4 1019 .o 889.4 915.2 919.4 951.8 1004.1 1010.2 1019.0 990.2 982.7 956.4 952.4 1019.0 1008.6 1003.5 943.0 960.7 994.7 928.8 941.0 940.2 908.9 960.9 925.7 954.1 926.2 999.3 978.3 996.5 985.6 1019.0 958.4 991.5 1019.0 948.7 940.8 953.1 966.4 990.4 997.3 986.9 919.4 948.6 910.4 1002.3 935.4 962.8 936.9 981.5 996.8 963.2 922.2 924.7 965.6 983.8 992.5 1008.6 1003.1 982.7 1019 .o 983.0 1019.0 961.1 972.7 995.3 971.3 AUG 1019.0 1019.0 995.2 1009.1 1019.0 1012.8 990.7 972.5 1019.0 1019.0 1019.0 973.0 1019.0 1004.1 1019.0 1019.0 1014.7 1019.0 930.5 948.1 979.8 996.0 1019.0 1019.0 1019.0 1019.0 1019.0 986.7 992.9 1019.0 1019.0 1019.0 980.4 993.8 1019.0 968.0 975.7 967.3 951.4 1007.7 953.3 996.9 992.2 1019.0 10J.2.0 10J.9.0 1019.0 1019.0 994.2 lOll. 6 1019 .o 979.7 991.6 996.5 995.5 1019.0 1019.0 1015.7 956.7 1004.5 949.2 1019.0 973.0 996.5 967.1 1003.0 1019.0 1010.4 958.5 978.0 1004.7 1019.0 1019.0 1019.0 1019.0 1004.4 1019.0 1019.0 1019.0 996.5 1001.7 1015.7 1000.9 Sl!:P 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1003.1 1002.0 1019.0 1019.0 1019.0 1004.0 1019.0 1019.0 1019 .o 1019.0 1019.0 1019.0 974.7 971.0 1002.2 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1014.3 1019.0 1019.0 1019.0 1019.0 1002.6 1019.0 1019.0 977.9 991.9 989.7 994.8 1019.0 981.9 1019.0 1016.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 10J.9.0 996.6 1019.0 J.019.0 1019.0 1019.0 1019.0 1019.0 994.6 1019.0 990.3 1019.0 1009.7 1019.0 992.4 1019.0 1019.0 1019.0 993.5 1012 .3 1018.9 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1014.2 1013.0 Page 20 AVG 974.1 978.6 953.4 956.9 971.9 971.1 954.1 941.8 970.4 977.1 994.5 950.7 979.3 969.5 967.6 979.4 969.4 997.9 938.1 926.8 936.3 958.3 976.9 983.7 993.1 975.0 975.4 956.1 962.9 990.2 1000.1 976.3 952.4 960.1 980.9 960.3 946.2 932.3 916.4 964.4 948.1 954.9 947.4 992.8 977.4 974.7 972.7 996.7 960.2 982.3 984.5 963.4 952.7 960.5 961.8 962.5 977.8 978.4 945.0 950.9 939.8 983.1 949.5 962.3 945.9 965.4 976.2 971.9 952.1 932.4 959.5 970.6 994.3 992.0 982.9 975.8 997.3 965 .4 987.4 970.6 980.3 978.1 967.1 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 U30 1931 1.932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1.951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1903 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT NOV 120000 117 001 120000 116586 120000 112562 120000 112987 120000 120000 120000 117900 120000 113793 111468 107239 117034 111716 120000 119818 120000 120000 120000 115821 113010 112490 120000 117016 119312 111909 120000 116860 120000 120000 120000 120000 120000 114144 108177 101222 98677 102124 11932 3 114891 120000 113556 120000 120000 120000 114873 120000 115262 120000 120000 120000 114881 120000 116532 120000 117236 120000 119834 120000 116834 120000 112370 112429 111882 120000 116318 120000 116562 102119 112054 104920 96988 105582 98216 115224 114652 120000 113616 102783 102846 120000 112841 119943 117234 120000 120000 120000 115648 120000 115059 120000 116662 120000 114451 120000 118111 120000 112608 120000 115207 115914 l.l0936 120000 117533 120000 l.l7253 120000 11l882 120000 117306 120000 118156 120000 112559 11167l 107341 120000 l.l3001 119028 120000 120000 112036 117949 112666 120000 112557 118234 114117 120000 115612 120000 116903 120000 115588 109462 102782 120000 113249 120000 112485 120000 111.694 120000 119587 120000 118174 120000 115786 120000 115362 120000 111950 120000 114394 120000 113105 120000 117995 120000 117971 H8076 114273 Appendix A SNETTISRAM HYDROELECTRIC PROJECT-PRELIMINARY-INPUT, SNETOP2.IH Rtm' 2 322000 Hlm LOA:O BASIC OPII!L -Oll'l'Pll'l', LONGOPR2 .Oll'l', CRA'l'OP!1.2.0ll'l' END OF HOH'I'l! CRATER LAKE STORAGE !AC1l.E-FEET) DEC JAN FEB 108005 97258 88006 106479 96462 85575 102623 91035 79627 102633 91686 81502 110258 99748 88543 109852 101555 90404 104142 97077 86393 96912 86700 76690 103012 92484 81218 110349 98919 89174 114781 104306 93768 104871 93932 82398 108630 102219 92213 109266 99272 88259 100994 93235 82500 110280 102825 92264 1ll.746 99382 87651 117250 109204 103359 103401 91428 79628 91219 79540 68:159 92650 83232 75148 106774 94711 83299 110755 99202 87325 113911 103801 92774 106518 96792 102401 108027 99153 89458 111410 101209 90453 104870 92730 80835 106929 97217 86659 108761 100322 91243 120000 113991 104255 106536 97024 88548 101511 90032 79986 101886 91663 80755 113120 103711 93525 106077 95869 83874 102060 90680 80656 86330 73618 63787 87340 75210 63102 104818 93998 83220 104137 92811 83304 100996 92462 82494 101952 89772 77435 118820 109354 98195 101673 101283 90394 110879 99377 88597 108804 98652 87820 120000 110007 100341 103535 94916 84429 111362 102862 94119 103941 94446 83491 105162 98ll.6 88053 101089 90041 79167 106449 94258 82479 106892 95716 85766 103029 90690 78486 109648 9867 8 88372 107554 97388 85724 101587 10889 79384 96691 86910 76346 101346 89848 77678 113 816 103371 92412 101229 92350 80986 105184 95387 84174 100800 89431 78108 105102 93956 83930 l.l2000 100505 89151 107231 9837 5 88544 104510 93 07 8 82094 91905 81905 70326 101644 92535 81821 101777 93730 86776 120000 110532 104871 114815 106192 97653 110089 993 74 90959 106876 99071 88874 120000 109645 101397 101407 89900 80887 105057 95931 92538 103468 93137 86445 112496 102757 92036 108449 97933 87400 106200 96108 86002 78307 76379 67818 69735 76749 78859 74231 65086 69459 79112 83743 70404 82543 77064 72219 83342 76023 93201 67135 56143 63984 71576 75882 82087 93369 79056 79088 68870 75341 82756 94509 77336 68583 71112 82055 72305 69656 51687 50413 72202 71776 72568 64689 86522 79334 76617 76603 90664 72988 84930 72367 78433 67898 70780 78072 66360 78397 73619 68456 65019 66104 82561 68535 72975 66522 72822 77942 78230 7ll14 57596 70125 77039 95248 87556 81592 77678 90953 69765 85141 76895 82153 79008 75160! APR 71392 71079 59367 59741 67308 71210 63907 55562 73718 72547 86817 61029 75611 68818 64542 74963 67660 86340 57570 49175 56053 62806 69183 74074 84909 71663 71016 60498 66366 85231 87505 69719 59746 63849 72492 76505 60536 59287 42043 64328 62534 64956 53969 86614 71244 67460 68486 84770 63949 77580 88644 71622 59527 61821 70580 58030 70808 78647 59029 57517 55777 75181 59764 65188 56817 64637 70600 72047 62028 47876 61476 71894 87556 80904 77586 69678 87923 68937 82647 72101 77016 75381 68743 MAY 71567 77254 55248 58581 65827 69271 57400 54028 76908 74314 95093 55322 77729 65987 67950 72028 65143 91031 54708 56978 53280 61555 74582 74103 92893 73313 70252 58969 64087 90840 95913 72354 59837 65688 74529 76052 54929 60695 43869 68932 58022 61663 57000 90731 75876 70488 71137 91897 59954 78757 90061 68156 60313 61092 71464 61214 77162 82174 57565 63239 53980 79391 57665 64375 55144 68154 71067 74115 62622 46755 60093 73281 87660 90471 81829 79329 92868 66818 87619 79420 80046 79582 70113 81283 95323 69808 69045 79022 74797 60699 64566 86623 85049 111878 66405 92584 80035 83571 87579 76ll0 108466 64480 64494 66010 67226 92774 96400 105765 83033 82736 72649 72873 108551 111770 91440 75458 84401 92998 81302 66729 76726 54276 83554 67910 72431 62953 101649 92789 87101 83302 108610 73849 91578 108754 78197 72706 78128 81651 83895 90460 95550 64800 73165 60262 90705 64468 77034 68820 78937 86781 82542 76976 64371 75784 79908 101917 102644 94521 94681 107275 82186 10313 9 90183 97033 90088 83039 JllL AUG 106793 120000 119636 120000 85321 106645 88734 114773 101510 120000 92844 116754 78204 103506 81311 95890 103324 120000 105764 120000 120000 120000 77080 96126 105680 120000 96629 112169 108901 120000 106213 120000 94956 117724 120000 120000 61779 78187 72094 85246 73774 98909 86800 107168 112174 120000 115379 120000 120000 120000 103109 120000 100078 120000 88821 101666 87 045 105031 120000 120000 114532 120000 111848 120000 83208 99147 90713 105639 106295 120000 77505 93939 82415 97292 82091 93592 69558 86620 90795 114074 76297 87440 87816 107816 76463 104511 109509 120000 98313 116311 107535 120000 101243 120000 120000 120000 89701 105919 104049 116083 120000 120000 85485 98899 82315 104126 87368 107579 93219 106861 103262 120000 108082 120000 101774 118260 73756 88966 85432 112384 70179 85700 111209 120000 80165 96110 91624 10753 7 80771 93515 99597 111573 107736 120000 91799 115485 74879 89751 75894 98183 92885 112455 100514 120000 104762 120000 114529 120000 111649 120000 100070 112291 120000 120000 100204 120000 120000 120000 90869 107570 95996 110872 106690 118255 96300 110543 SEP 120000 120000 120000 120000 120000 120000 111650 111036 120000 120000 120000 112088 120000 120000 120000 120000 120000 120000 96864 95219 111133 120000 120000 120000 120000 120000 120000 117546 120000 120000 120000 120000 111357 120000 120000 98178 104312 102863 106363 120000 99746 120000 118397 120000 120000 120000 120000 120000 120000 120000 120000 107613 120000 120000 120000 120000 120000 120000 106240 120000 103189 120000 115130 120000 104707 120000 120000 120000 105441 116474 119952 120000 120000 120000 120000 120000 120000 120000 120000 120000 120000 117448 116743 Page 21 AVG 98301 100398 89171 90785 97414 96954 89250 83874 96291 99587 107532 87956 100226 96210 95428 100529 96383 109071 82444 77314 81248 91344 99619 102711 106460 98506 98854 90195 93180 105412 110192 99303 88436 91668 101254 91514 85286 79382 73549 93816 86466 89069 86665 106548 99601 98642 97592 108579 91974 101619 102859 92912 88669 9H91 95623 93237 99909 99904 85269 87976 83089 102306 87370 92841 85599 94255 99283 97106 88190 80294 91835 96450 107020 106196 102148 98694 108785 94338 103939 96166 100700 99850 95109 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 un 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 U38 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG Appendix A SNE'l'l'ISIIJ\M l!YDROELECTlliC PROJECT -PRl!LIMIIfA.RY -IlfPOT, SN:ETOP2 • IN RU!I 2 -3l2000 M'ill! LOA!) -BASIC OPER. OOTPOT, LONGOPR:l.OOT, CRATOPR2.0trr OCT NOV DEC JAN 6376 7987 9547 9957 7348 8132 9733 10098 7467 8558 9983 10413 759:i 8519 103:12 10737 n 64 81:11 10063 10413 7598 8475 10169 10369 7724 8632 10384 10863 7330 8071 9796 10310 7192 8309 9630 9961 7486 8113 10125 10507 7184 8371 U78 10369 7771 8416 10036 10368 7445 8129 9938 10178 7695 8353 9778 10126 7614 8508 10375 10784 7520 8347 9773 10063 7320 8385 10113 10538 7l57 8:i40 9925 10:i90 7774 8622 10410 10841 6550 7844 9516 9935 6586 7350 8790 9216 7321 8310 9820 10192 7392 8335 10311 10692 77 51 8163 Ul2 10210 6658 8244 9716 10075 7110 8283 9858 10147 6710 8050 9640 10071 7573 8457 10008 10412 7425 8362 9778 10167 6462 7962 9435 9915 6639 8194 10379 10419 7479 8278 H03 10361 6816 8514 1051.4 10998 6841 7801 9576 9948 7345 8052 9895 10204 7345 8444 9962 10375 6466 7687 9442 9813 7386 8138 10034 10542 7234 8050 9671 10156 5895 7794 9453 9836 7317 8661 10409 10848 6510 7147 8680 9078 7924 8522 10361 10870 7593 8209 10266 10601 7407 8283 10033 10271 7175 8449 10551 10955 7498 8338 10112 10528 6859 7928 10689 10376 7249 8442 10263 10558 7294 8182 9633 9967 7534 8532 10085 10478 7795 8496 9946 10218 6348 8263 9965 10464 7609 8489 10314 10723 7861 8366 9997 10404 7525 8452 10170 10645 7884 8305 9884 10269 7342 8485 10268 10662 7686 8531 10283 10738 6632 7924 9678 10137 8274 8651 10560 10958 6465 8084 9882 10305 7797 8700 10374 10914 7199 8220 9792 10141 7624 8706 10679 11071 6619 8260 9702 10126 6744 8223 10151 10502 6896 8286 9917 10072 7436 8546 10400 10748 6958 7928 9716 10151 7551 8626 105ll 10778 7365 8408 10058 10518 8079 8756 11691 11800 6300 8286 10109 10369 6562 8138 9881 10266 6762 8216 9842 10263 7299 7994 llUO 10531 7297 8361 10110 10556 7064 8387 10034 10336 7429 8357 10038 10451 6990 8095 9818 10180 6878 8440 9905 10245 7227 8272 10019 10377 lfET ENERGY FROM CRATER LARE WIT {MWII) FEB 9504 9557 9914 10091 9877 9779 10253 9858 9487 9995 9820 9780 9291 9609 10009 9534 9943 9528 10320 9604 9007 9726 10097 9619 11066 9663 9476 9924 9627 9117 9708 9854 10521 9489 9661 9858 9428 10456 9817 9245 9704 8558 10420 10006 9648 10420 10003 9645 10042 9098 9764 9552 10079 10153 9695 10191 9702 10055 10223 9596 10377 t757 10270 9574 10580 9776 9933 9426 10175 9769 10037 9784 11245 9773 9536 9731 10099 9560 9679 9286 9608 9736 9822 9454 9378 10030 10211 9950 9764 10343 9963 9618 9866 9722 9911 9155 9652 9922 9546 9894 9463 10363 9931 9159 9809 10078 9577 10645 9657 9440 10044 9641 8975 9594 9819 10431 9645 9650 9897 9600 10457 10196 923l. 9732 8545 10645 9996 9651 10419 9971 9441 9905 8968 9778 9440 10202 10283 9416 10279 9633 10108 10062 9691 10348 9646 10375 9634 10531 9691 9953 9376 10325 10042 10124 9418 10869 9537 9387 9646 9775 9598 9439 9l.04 9523 9644 9803 APR 7753 7440 8285 8587 8189 8067 8771 8286 9887 7949 8911 8723 7802 7713 7727 7909 7976 7660 8606 7072 7650 8030 8361 7604 8470 7891 7262 8120 8166 8337 7523 8154 8680 7549 7954 10060 8112 14387 8907 7675 8346 7204 9068 9178 7723 8601 8051 7393 8240 7285 10858 7984 8380 8887 7836 8661 7897 9614 8641 7675 8597 7839 8287 7437 8650 8292 7799 7800 8496 8373 8038 7733 8846 7438 7867 7765 8062 8206 7884 7456 7610 8204 8249 MAY 6568 6224 7058 7240 7042 6961 7250 6677 8355 6716 7380 7213 6735 6419 6307 6564 6680 6555 6780 6916 5720 6569 6686 6454 7273 6537 6219 6709 6754 6753 6457 6645 6667 6325 6427 7900 6769 8780 6647 6182 6639 6102 7Z21 7755 6461 7373 6745 6395 6701 6311 9349 6991 7049 7075 6589 6950 7207 7702 6999 7136 7749 6858 6745 6151 6859 6602 6365 6716 6943 7557 6361 6269 7632 6773 6775 6651 6934 6376 6633 6889 6128 6758 6849 4917 5031 5380 5578 5523 5554 5243 5445 6230 5321 5652 5582 5388 5041 5314 5428 5311 5161 5145 5318 4481 5161 5622 4900 5635 5121 4995 5274 5044 5343 5279 5314 5316 5287 5021 5701 5783 5712 5072 4755 5145 5132 5513 5903 4994 5668 5502 4850 5349 5176 6661 5588 5307 4783 5431 5240 5715 60n 5291 5401 5385 5365 5212 5l.28 5693 5249 5234 5356 5492 5379 5080 SOH 6001 5293 5434 5577 5485 4870 5382 5326 5047 5516 5349 4902 5075 5501 5582 5507 5781 5515 5768 6059 5576 5740 5302 5525 5131 5620 5676 5499 5296 3668 5091 4257 4998 5570 5169 5736 505:i 5037 4602 5041 4541 4842 5183 4710 4777 4828 4303 5982 5234 4807 4372 4885 4948 5044 5600 4516 5385 5375 4648 5367 5017 6136 5099 4815 4596 5218 5054 5983 5179 4993 5164 4906 5405 5058 5056 5807 5097 4970 4935 4560 5147 5535 5169 5381 5176 5557 5110 5122 4759 5490 4875 4241 6196 5164 AUG 4983 5257 5652 5609 5752 6008 5715 5859 5915 5868 5818 5461 5942 5230 5767 5942 5669 5623 4500 5028 4744 5132 5564 5540 5602 5785 5227 5071 5278 5l.34 5390 5437 4908 5153 5209 4714 6094 566:1 5148 4905 5360 5079 5346 5745 4888 5539 5580 5227 5634 5230 5912 5238 5191 4865 5635 540:1 6050 5296 5055 5090 5186 5319 5175 sou 6086 5332 5122- 5158 5305 5282 5641 5213 5545 5630 5544 5393 5407 4772 5519 5421 4754 6497 5403 MINnmM ANNUAL CRATER LARE GENERATION • 82316. 2ND MIN: ANNUAL CRATER LAKE GEN • 83005. Page 22 SEP TOTAL 6098 88046 5867 89139 6l.22 94364 6090 96157 6094 93795 6331 94855 6139 96832 6587 93951 6559 97203 6287 93807 6327 95272 6307 94870 6417 91946 5878 90624 6391 94340 6514 92818 6227 93557 6177 91175 5274 92304 5731 88536 5355 82316 6235 91304 6310 95018 5690 90490 5980 95100 636l 91466 58l9 87956 5863 92059 5552 90835 6053 88029 6647 91071 6447 92873 5352 93427 5873 88264 6125 90371 4755 93315 6004 91182 6060 102848 5632 91336 6040 85382 5643 92688 6023 83005 6069 97003 6283 97135 6600 90475 6797 97333 6364 94067 6210 89660 5953 93703 5682 87843 6576 101663 5798 92145 SSH 91607 54H 932H 5791 92237 6461 95029 6244 94833 6588 97379 5414 93915 6280 90405 6138 97130 5971 90896 583l. 94738 5950 89374 6233 98517 5798 90544 6416 91413 6159 90099 6046 94473 5559 91862 63l.2 94596 5594 90543 6711 102554 5798 90483 5529 90474 6032 90989 5876 93775 5723 90187 6329 92176 5425 90055 5447 87439 5834 93851 6025 92558 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 l96l 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 197 8 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 U92 1993 1994 1995 AVG 20874 20703 21932 21794. 21233 21954. 22347 22567 21852 21497 20864 22327 22056 21676 21851 21909 21440 20968 22150 22U9 21601 21915 21533 20787 20889 21123 20871 21857 21747 20308 20972 21402 21480 21717 21167 22002 22321 22605 22094 20997 22113 21662 22248 21831 21527 21741 21641 20270 21631 21328 21795 22144 21474 21254 21866 21599 21801 21643 22155 21666 22544 20928 22111 21748 22510 21386 21008 21296 22360 21884 22093 21013 22247 20740 21051 21280 20895 20799 21097 21730 21008 21807 21593 NOV 23480 23350 24.289 24183 23755 24305 24605 24773 24227 23956 23473 24590 24383 24093 24227 24271 23913 23553 24455 24.592 24036 24275 23984 23414. 23492 23671 23478 24H1 24147 23048 23555 23883 23943 24124 23705 24342 24585 24802 24412 23574 24427 24082 24530 24211 23979 24142 24066 23020 24059 23827 24184 24450 23939 23771 24238 24034 24188 24067 24459 24085 24756 23522 :14425 24148 24730 23871 23583 23803 24615 l4251 24.411 23587 24529 23378 23616 23H1 23497 23423 23651 24134 23583 24193 24.030 DEC 28152 28018 28980 28872 28433 28998 29305 29478 28918 28640 28144 29289 29077 28780 28917 28962 28595 28226 29151 29291 28721 28967 28668 28084 28164 28347 28150 28921 28836 27709 28228 28565 28626 28812 28382 29035 29284 29507 29107 28248 29122 28769 29228 28901 28663 28831 28752 27679 28745 28507 28873 29146 28622 28449 28928 28720 28878 28754 29155 28772 29459 28194 29120 28836 29433 28552 28257 28482 29315 28942 29106 28261 29227 28047 28291 284.70 28169 28093 28326 28a22 28256 28883 28715 Appendix A SNETTISBAM HYDROELECTRIC PROJECT -PRELIMIKARY-INPUT, SNETOP2.IN RtJN 2 -322000 1111!1 L<JAD BASIC OPER. -OUTPUT, LONGOPR2.0UT, CllATOPRZ.OUT TOTAL NET EIIEI!GY FROM BOTH LONG LAXE AND CRATER LAXE {1111!1) JAN 28690 l$569 29436 29339 28943 29452 29729 29884 29380 29130 28682 29715 29523 29255 29379 29420 29089 28756 29590 29716 29203 29424 29155 28629 28700 28866 28688 29383 29306 28291 28759 29062 29117 29l84 28897 29486 29710 29911 29550 28777 29564 29:14.6 29659 29365 29150 29301 29230 28264 29224 29010 29339 29585 29113 28958 29389 29201 29344 29232 29594 29249 29868 28728 29562 29306 29844 29051 28784 28987 29738 29402 29549 28788 29658 28595 28815 28976 28705 28637 2884.7 29294. 28784 29348 29197 Fl!ll 26382 26270 27075 2U84 26617 27089 27346 27490 27022 26790 26375 27333 27156 26907 27022 27060 26753 26444 27217 27334 26858 27063 26813 26325 26392 26545 26380 27025 26954 26012 26446 26727 26779 26934. 26574 27121 27329 27515 27180 26463 27U3 26898 27281 27008 26809 26949 26884 25987 26878 26679 26985 27213 26775 26631 27031 26857 26989 26885 27221 26900 27475 264.18 27192 26954 27453 26717 26470 26658 27355 27043 27180 26473 27281 26295 26498 26648 26396 26333 26528 2694.2 26470 26993 26853 25519 25391 26310 26207 25788 26326 26620 26784 26250 25985 25511 26604 26402 26118 26249 26293 25942 25589 26472 26606 26062 26297 26011 25454 25530 25705 25517 26253 26172 25096 25592 25913 25972 26149 25738 26362 26600 26812 26430 25611 26445 26108 26546 26234. 26007 26167 26092 25068 26085 25858 26207 264.6& 25967 25803 26260 26061 26212 26093 26476 26111 26767 25559 26443 26172 26741 25901 25619 25834 26629 26273 26429 25623 26545 25419 25651 25823 25535 254.63 25685 26159 25619 26216 26056 APR 20278 20130 21193 21073 20589 21212 21551 21742 21124 :10817 20269 21534 21299 :10971 21123 21173 20767 20359 21381 21536 ~0906 21178 20848 20203 20291 20493 20275 21127 21033 19789 20302 20734 ~0801 21006 20532 U253 U528 21774 21332 :.10384. 21349 20959 21466 21105 20842 :11027 20940 19756 20932 20670 21074 :.!1375 20797 20606 21135 20905 21079 20942 21385 20963 21722 20325 21347 :1103 3 21692 20720 20394. 20643 21562 21151 21331 20398 21465 20162 20431 20629 20296 20213 20470 21018 20393 21085 20900 IIAY 1774.8 17591 18723 18596 18079 18743 19105 19308 186U 18322 17738 19087 18837 18487 18648 18702 18269 17835 18924 19089 18418 18707 18355 17668 17762 17977 17745 18653 18553 17226 17838 18234 18306 18524 1801.8 18788 19081 19343 18872 17861 18890 18474 19014. 18629 1834.9 18547 18454 1719:.1 184.4.6 18166 18596 18918 18301 18098 18662 18416 18602 18456 18928 184.78 19387 17798 18888 18553 19255 18219 17871 18137 19117 18678 18871 17876 19013 17625 17911 18122 17768 17679 17953 18537 17871 18608 184.11 14.722 14501 15724 15593 15062 15744 16116 16324 15648 1531:1 l47l:i 16097 15840 15481 15647 15702 15258 14812 15929 16099 15410 15707 15346 14640 14737 14958 14720 15652 15548 14187 14815 15222 15295 15519 15000 15790 16091 16360 15876 14839 15895 15468 16022 15627 15340 15542 15447 14151 15439 15152 15593 15923 15290 15082 15661 15409 15599 1540 15934 15472 16302 14774 15892 15549 16270 15206 14849 15121 16128 15677 1587 5 14854 16021 14596 14890 15107 14.74.3 14652 14933 15532 1484.9 15605 154.03 15473 15300 16551 16411 15839 16574 16974 17198 16470 16108 15463 16953 16677 16290 16468 16528 16050 15570 16773 16955 16214 16533 1614.5 15385 154.89 15727 154.70 16474 16363 14897 15573 16011 16090 16332 15772 16623 16947 17236 16716 15599 16736 16276 16873 16448 16138 16356 16254 14859 16245 15936 16411 16766 16085 15800 16484 16212 16418 16256 16778 16280 17174. 15529 16733 16363 17139 15994 15610 15903 16987 16501 16714 15615 16872 15337 15654 15887 154.95 15397 15700 1634.5 15610 16424 16206 AUG 16354 16200 17310 17185 16679 17330 17685 17884 17238 16917 16345 17666 17422 17078 17237 17289 16865 16439 17506 17669 17011 17294 16949 16276 16368 16579 16352 17242 17143 15843 16442 16831 16901 17115 16619 17373 17661 17918 17456 16465 17474 17066 17595 17218 16944 17137 17046 15809 17038 16764. 17186 17501 16896 16697 17250 17009 17192 17048 17511 17070 17863 164.03 17471 1714.3 17832 16816 16475 16735 17696 17206 17455 16480 17594 16233 16514 16721 163 74. 16287 16555 17127 16475 17197 17004. MINIMUM ANNUAL SNETTISBAM GENERATION • 249307. 2ND MIN ANNUAl< SNET GEN • 249693. Page 23 SI!P TOTAl< 17787 255457 17636 253721 18725 266249 18603 264841 18106 259124 18745 266473 19093 270476 19288 272720 18654 265432 18340 2 61815 17778 255354 19074 270:168 18834 267505 18498 2 63 634 18653 2654.20 18705 266014 18289 261230 17871 256423 18918 268465 19077 270293 18432 262872 18710 266069 18371 262177 17711 254578 17801 255615 18008 258000 17785 255431 18658 2654.75 18561 264362 17286 249693 17874 256455 18255 260839 18324 261634 18534 264050 1804.7 2584.52 18787 266962 19069 27 0205 19321 273105 18868 267893 17896 256714 18885 268094 18486 263495 19005 269467 18635 265212 18366 262114 18556 264297 18467 26327 3 17253 24.9307 18458 263179 18190 260090 18603 264847 18912 268402 18319 261578 18124 259334 18666 265570 18430 262854 18609 264910 1846 8 263294 18922 268519 18489 263534. 19267 2724.84 17836 256013 18883 268066 18561 264366 19237 272136 18241 260676 17906 256825 18161 259760 19104 270605 18682 265750 18867 267881 17911 256881 19004 269455 17669 254097 17944 257266 18147 259602 17807 255679 17721 254699 17985 257731 18546 264186 17 906 256822 18614 264.97 5 18425 262790 2/25/97 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 l9ll 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1905 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1U1 1992 1993 1994 1995 AW OCT 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 NOV 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465. 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 DEC 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 31263 33203 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 Appendix A SNETXISI!Al!! HYDROELECTltiC PROJECT -I'Rl!LIHINARY -mPOT: SNETOP2 . IN RUN 2 -322000 l!iiB LOAD-BASIC OPER. OUTPOT: LONGOPR2.00T, Cl!ATOPR2.00T TOTAL NET ENERGY FRO!! SNETXISI!Al!! PLUS AELP HYDRO (lliiBl JAN 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 3H95 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 APR 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 259ll MAY 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 JUN 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 J0898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 JO'L 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 221J1 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 All'G 22250 22050 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 2J250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22l50 22250 22250 22250 22250 22250 22250 22250 22250 22250 MmiMUM MNUAL SNET + AELP HYDRO GENERATION • 322000 · 2ND MIN MNUAL SNET + AELP HYDRO GEN • 322000 • SEP 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 l3570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 23570 Page 24 TOTAL 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 3 22000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 322000 122000 322000 322000 321999 2/25/97 1914 l.9l.5 191.6 1917 lU8 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1931 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954, 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1960 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 l98l. 1982 l983 1984 1985 1986 1987 l988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402· 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 27402 21402 27402 27402 27402 27402 27402 27402 NOV 28465 28465 28465 28465 28465 28465 28465 28465 28465 28t65 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 DEC 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 Appendix A SNETTISHA!! BYDROELECTI\IC PROJECT -PRELIMINARY -INPUT, SNETOP2. IN RON 2 322000 llllll LOAD-BASIC OPER. OUTPUT, LONGOPR2.0UT, CRATOPR2.0UT TOTAl NET ENERGY FROM AlL HYDRO PLUS T!ll!RMAL RESOURCES (IIWI!) JAN 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 332, 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 FEB 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 APR 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 2592l. 25921 25921 25921 25921 2592l. 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 MAY 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 JOL 22121 22121 2212J. 2212J. 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 AUG 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22:150 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 22250 Page 25 Sl!P TOTAl 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 32l000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 2357 0 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23 570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 H570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 32l000 l3570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23 57 0 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 322000 23570 3:12000 23570 322000 23570 322000 23570 321999 APPENDIX& POWER STUDY MODEL OUTPUT RUN 6-322,000 MWH ANNUAL LOAD (All Potential Caeneration is Assumed to be Usable) - 2/25/97 YEAR 1914 1925 19H l917 1918 1919 1920 1921 1922 :923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1.969 1970 1971 1972 1973 1974 1975 1976 1971 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 ocr 1214.6 585. 8 536.0 593. B 640.1 494.9 515.6 373.5 675.2 467.7 552.3 580.1 296.8 485.3 340.0 515.6 1060.0 538.0 676.8 656.1 441.6 514.3 501.6 676.9 1283.9 647.8 1041.0 736.3 5H.3 961 1100.5 660.7 1213.7 513 9 613.7 574.4 463.3 260.9 304.6 1103.2 892.5 457.3 331.4 367.0 576.3 734.1 555.8 803.3 941.0 581.1 737.0 679.1 906.6 697.1 391.1 394. c 319 '2 735.6 432.6 602.5 468.1 1021.4 472.4 502.4 577.7 1001.3 1181.1 865.1 609.8 4'14.9 608.1 596.7 404.6 1382.4 943.3 1301 .1 522.4 548. 6 684.5 487.5 653.4 938.5 662.3 sov 395. 287. 6 129.9 142.4 648.3 336.5 188.1 257.3 204.5 513.0 511 4 347,7 425.2 328 3 123.7 357.9 476.7 549.3 1'18.2 119.8 534.2 313.5 208.4 572.8 206.0 231.4 526.2 237.0 318.5 336.0 396.8 321.1 85.5 438.6 382.7 315. 3 593.0 123.8 126.7 436.8 140.4 461.5 207.8 426.4 440.6 249.2 268.9 329.7 200.9 398.5 125.0 267.2 152.6 223.8 355.6 174.4 364.8 29'1 .1 169.6 215.0 180.2 485.9 75.3 261.9 138.4 242.3 254.8 305.0 284.4 84.1 141.7 '15.6 58.5 310.9 383.2 300.8 342.3 52.3 153.6 209 9 392.9 335.1 289.8 DEC 171.8 12'1. 8 217 5 84.8 92.9 177.2 125.6 58.9 273.0 102.2 217.1 106.4 240.9 2'14. 6 49.0 309. 141.4 322.5 82.8 72.3 117.3 227.2 233.9 244.4 235.6 235.1 241.6 166.9 219.3 213.5 244.4 120.4 17.0 55. 241. 160.5 168.7 32.2 89.2 118.8 136.8 359.3 54.0 340.7 116.9 140.0 197.1 286.4 54.8 295.2 214.2 200.5 110.3 54.0 119.6 90.8 243.4 75.5 80.0 33.3 20.3 231.0 124.5 220.1 6.8 222.2 215.8 139.5 40.8 20. e 31.2 119 .o 324.9 219.3 135.8 159.2 311.9 92.0 157.1 129.3 225.2 210.8 160.9 Appendix B SNETTISHAM HYDROELECTR:C PROJECT • PRELIMINARY -INPUT, SNETOPR6.IN R1~ 6 • 322000 MWH LOAD· ALL SNET GEN USABLE· LONGOFR6.0UT, CRATOPR6.0UT JAN 52.7 101.4 49.0 86.0 95.8 205.9 177.2 66.7 89.4 60. e 76.6 87.4 244.6 99.3 182.0 193.2 19.6 149.2 54.0 44.2 77.4 32.2 64 '8 80.1 111.0 158. ~ 63 '7 35.9 101 100' 0 309.8 92.9 67.4 83.6 128.6 85.2 36.4 33.8 37.4 56.7 69.6 87.0 29.4 120.2 189.6 68.6 89.4 127.4 179.3 142.1 122.9 222 '2 51.2 50.0 58' 25. 61.7 104.0 82.1 93.0 82.6 65.2 119.3 110.2 93.7 47. 5 70.0 199 84.6 104.8 180 .a 152.9 156.5 176.5 72.5 151.3 97.0 62.9 156.7 114. 1 102.2 n.1 101.9 INFLOW TO LONG LAKE (CFSJ 71.7 50.4 50.2 127.6 40.3 53.9 96.3 93.3 29.5 83.4 50.9 59.5 179.4 34.4 139.3 42.1 44.2 259.8 55.9 39.2 '15. 7 23.5 45.2 45.1 99.8 68.0 56.6 27.1 60 '0 171.1 115.6 122.8 102.7 38.4 58.5 21. 48' 95. 38.7 65.9 27C .1 53.9 30.6 44.2 68.7 68.7 55.5 124.2 76.7 210.7 109.9 116.5 44.4 54.3 136.6 24.2 76.6 58.3 61.4 87.1 66.0 37.8 94.6 s2 .a 76 37' 3 44.9 112.2 as. 38.7 135.2 236.8 199.5 123.7 179' 7 68.4 74.1 240 4 325.1 346.2 51.0 55.5 90.7 88.0 132.1 49 .o 50.9 25.5 49.0 44.7 67.7 24.6 114.8 88.3 32.9 113.2 41.2 118.8 103.1 56.9 50.8 58.9 40.5 30.7 3a. 7 65.3 53.2 164.4 65 5 33.9 40.8 48.'1 120,0 79.3 61.4 102.1 7~. 6 29.5 55. 42.2 114.4 48.7 47.4 58.6 58.9 39.3 34 '3 49.0 58.9 70.4 9a .3 89.9 106.9 68.2 123.1 64.0 44 '7 216.5 54. a 102.7 39.1 126.1 59.2 102.3 97.6 46.7 4'1. 9 108.8 78.5 48.8 73.9 78.5 26.6 58.3 163.2 193.2 109.0 118.6 65.5 124.7 53.8 195.7 132.7 88.5 153.9 78.3 APR 117.2 213 '0 126.7 65.3 69.8 122. ') 51.0 108.0 113.8 181.4 132.5 29.9 67.2 150' 2 214.4 81.5 133.5 121.7 106.1 295.3 llC ,5 116.9 140.7 135.8 137.7 120.3 la8.4 1496 49.5 '16. 2 193.6 104.2 106.1 210.2 43.3 104.5 75.9 97.4 147.1 83.3 49.2 65.8 6a. 8 as.4 146.8 97' 5 144.0 197.9 83.6 113.0 153.4 107.2 127,3 46.9 107.9 110.0 130. 8 201.6 65.4 188.4 95.9 117.8 164.8 216.1 125.5 58.2 190.7 125.6 119.3 106.0 170.1 172 .o 159 3 205.8 154.9 134.3 188.0 235.2 194.7 206.7 211.9 174.7 130.6 MAY 357.3 558.3 249.0 328.8 293.7 303.3 229.9 381.5 397.5 427.8 565.1 242.7 428.1 324' 0 544.3 341.6 311.3 480' 351. 528.4 391.5 382.1 598.5 353.6 507.3 442.2 325.8 353.0 337.7 552. 588.7 494.3 446.9 456.1 498.0 444.3 235.9 535.2 431.2 561.3 315.3 280.8 480.3 463.1 53 a. a 418.7 463.6 497.6 299.3 380.6 306.3 245.0 375.8 378.8 425.9 JON 765.1 887.6 847.9 682.9 730.7 534.5 569.1 701.0 692 8 710.9 892.4 725.5 870.3 875.9 800.0 811.6 699.4 943.5 742.3 648.4 897' 0 574.8 796. 1169.1 758.7 692.3 734.8 817.8 752.6 830.9 7a3. 3 948.1 830.7 905.2 1009.9 688.6 647.5 1051.6 719 .a 925.9 JUL AUG 1278.1 1120.1 1161.3 1331.4 839.7 1050.4 976.9 1265.9 1050.4 1197.2 847.7 1031.2 900.3 1178. l 834.9 841.3 895.5 1031. 913.1 954,6 1147.8 1031.2 829.3 1029.8 777.9 656.8 941.8 948 2 1060 0 870.0 868.4 820.5 882.8 1060.0 937.0 1069.5 806.1 860.4 728.7 964' 9 830.9 1242.7 1160. 1138.2 1011. 924.7 853.5 974.9 826.2 834. 5 1100. 0 1420.4 938.5 1147.1 1322.9 659.9 903.2 955.4 1687.5 1027.7 845.3 1028.9 1157.3 809.6 919.2 957.5 898.3 779.8 1009.2 897.0 896.3 933.7 779.2 800.4 776.3 628.0 1024.0 940. 912.3 999.3 739.6 801.0 618. 1123.8 1327.5 792.4 971.2 878.6 954.9 657.7 1016.7 580.1 1002.0 786.7 814.6 1024.0 961.0 888.8 1187.5 692.1 1024.4 998.3 1333.2 782.2 884.8 726.3 927.6 974.1 1178.7 678.6 852.3 784.0 912.3 113 7. 2 848 '9 641.8 885.3 1454.7 817.3 742.9 836.6 861.2 1036.6 1079.1 660.2 SEP 663.9 1056.2 1021.1 905.6 1040.9 981.5 628.5 694.5 813 '2 1118 '4 1060.6 662.1 745. 941. 814.9 740.6 805.0 806.6 956.7 587.2 780.2 645.8 1C02.7 1265.4 1105.9 845.3 1016.7 690.6 1108.2 839.'1 50'1. 4 852.1 797.5 949.1 1087.7 802.1 861.2 696.4 1083.1 864.7 891.9 829.6 655.2 1005.4 519.8 572.1 961.3 705.7 1082.3 1214.6 480.2 577.5 1092.3 1297.2 1254.8 481.4 1143.6 1174.4 1142.0 705.1 431.7 759.4 776.7 953.5 1096.2 510.2 718.1 1045.4 970.5 715.8 369.1 651.8 802.9 990.4 1092.8 426.6 712.5 879.6 1486.9 659.5 274.8 669.5 a96.6 918.6 723.0 410.0 706.1 981.1 978.1 1118.3 355.6 624.6 1005.9 974.7 910.0 397.4 738.8 947.4 1023.1 844.1 387.4 752.3 721.8 686.0 867.3 531.7 697.1 1155. 716.7 956.4 430.2 776.3 1234.6 1023.4 678.1 398.6 607.7 898.1 1172.9 951.1 438.2 847.9 715.4 657.7 745.5 288.3 930 5 833.3 116 9. 2 1144 . 8 H9.8 930.4 786.9 1023.3 504.9 473,5 562.3 984.0 1116.2 1523.0 360.2 826.2 861.1 887.2 390.2 469.7 749.2 843.7 633.6 1238.5 444.2 706.0 829.0 890.9 1277.2 620.9 697.8 816.6 689.4 856.7 450.7 778.0 1125 9 1066.7 1210.0 399.9 912.2 1085.9 1359.2 1370.2 519.5 807.4 985 1003 '0 902. 6 450.2 783.6 679.8 715.9 1163.4 558.7 847.6 933.7 747.1 1367.0 549.6 658.9 555.6 567.1 l010.9 418.3 '184.8 947.8 965.0 902.5 Page 1 AVG 524.7 541.1 430.5 442 '6 493 '8 428.2 392.0 373.2 436.7 4'10.7 527.2 394.4 420.5 453.7 438.0 432.2 474.4 519.0 410.8 393.7 460. 430. 466.2 535.4 524.2 502.3 526.2 436.5 447.4 576.3 516.1 478.7 470.5 450.7 499.9 423.5 396.0 370.4 415.9 514.6 415.3 454.4 400.5 440.0 466.9 446.9 456.5 579.7 457.7 486.6 442.2 410.9 471.5 492.7 437.8 460.1 443.1 455.9 410.3 453.6 374.8 520.8 414.0 446.9 378.5 478.8 512.4 487.5 392.3 435.2 415.9 514.6 401' 8 538' 5 511.3 488.5 524.3 534.4 507,1 451.6 514.9 441.9 461.1 2/25/97 YEAA 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1214.6 585. e 536.0 593' 8 640. 494 '9 515.6 3 73 < 5 497.8 467 '7 552.3 580.1 352.3 485.3 362 '3 515 '6 1060 '0 538.0 676' 656.1 368' 5 514.3 501.6 676.9 1283.9 647.8 1041.0 736.3 514.3 961.3 1100' 5 660.7 1213 '7 513 '9 613.7 574.4 463.3 369.5 361 '7 1103 '2 892.5 367.9 359.3 367,0 576.3 734' 1 555.8 803.3 941.0 581.1 737.0 679.1 906.6 697.1 391.1 394 '0 344 '3 735.6 432.6 602.5 468.1 821.4 472.4 502.4 577.7 788.9 1181 '1 865.1 609.8 373.0 608.1 596.7 404.6 1382 '4 943.3 1301' 1 522 '4 548.6 684.5 487.5 653.4 938.5 655.5 NOV 424.6 384 396,2 396,4 648.3 397.6 401.7 416.6 400.0 513 '0 511.4 408.8 406.9 395.0 3 91.1 400.5 476.7 549 '3 403.6 426.6 421.8 402.1 393.2 572.8 417.9 391.2 526' 2 404-6 397.0 397,8 413.8 397.3 422.9 438.6 396.8 401.7 593.0 421.4 413.4 436.8 411.9 423.1 398 '7 426.4 440.6 402.4 396.8 390.0 410.6 398.5 401.5 406.8 410.7 390,4 396,1 388.9 394.0 399.6 398.4 409 '3 403 '7 485.9 394 '3 400.3 404 '9 403' 419.5 403.9 407,2 407 '2 399' 9 384.2 393' 413.7 407.1 426.9 390.1 379.8 389.4 396 0 394.0 414.1 419 8 DEC 449.3 443.7 465.8 454.4 452.0 456' 462.7 480.6 471.2 450.5 442.0 466.8 464.5 460' 7 454 '1 464' 6 448 '6 446.6 458.4 487 'c 485.9 465.5 447.9 446.7 449.6 450.2 450.9 461.0 462,3 441.9 431.1 452.4 444.1 467 '5 446.6 462.9 486.1 485.8 484 .1 455.8 458.4 486.9 460 7 451.5 451.2 445.0 453.4 411.0 451.0 456.0 460.7 467.4 457.0 441.8 458.4 453.5 459.7 448.7 461.9 466 .. 462.7 444.8 461.1 463.8 459.9 459.2 440.0 450.2 460.0 473.8 455.6 447.0 431.8 434.2 444.3 451.9 410.9 442.0 447' 2 458 '5 445.3 459.8 455.6 Appendix B SNE'ITISHAM HYDROELECTRIC PROJECT -PRELIMINAAY -INFUT, SNETOPR6, IN RUN 6 -322000 MWH LOAD -ALL SNET GEN USABLE -L0NGOPR6.0UT, CRATOPR6.0UT TOTAL Ol,;TFLOW FROM LONG LA.KE TUNNEL • SFILL (CPS) JAN 460.5 458. 475.0 467' 3 458.2 471.9 472.2 491.9 482.0 460.5 449.5 480.7 477.5 470.8 468.4 474.9 457.7 450' 5 470' 3 SOL 5 499.8 476 '0 457 '6 451.4 460.3 463.2 456.6 4n.8 472.8 451.5 448.3 463.8 456.3 482.4 458' 5 473.8 492 '4 499.5 497 '7 469.1 468.4 494 '6 471,7 458' 3 466.6 455.6 463.3 436.3 467.4 466.2 470.6 480 '7 467 '3 455.6 470 '7 465.1 469.5 461 '9 473.9 480.7 477 '1 451.9 469.9 475.2 474' 8 469.0 450.6 468.4 474 '7 489.8 473.4 459.1 443.3 447,4 456.9 462.4 442.9 455.5 461.6 470.4 456.7 470 9 467' 7 FEB 471.1 469' 6 487' 8 481.8 468.8 481.9 483.0 504.5 494' 2 471' 6 460.0 495.4 495.l 482.1 483.5 484.1 471.9 465 '1 482 '2 512 '8 508.1 488.6 470.4 463.3 428.2 471 '5 469 '9 484 '3 485.1 469 6 457.1 474.4 464' 6 494.6 468.5 485.7 504.5 503.4 509.3 484.6 497.6 510' 2 482' 469' 477.9 466' 0 474.1 450.0 475.7 485.8 486.8 493.5 475.8 468,1 488.6 4 75' 9 483.1 474.4 485 '2 494,3 490.0 463.0 482.9 488.4 484 '3 477.3 462 '1 480.9 488' 0 499.1 488.1 473.9 449.1 456.4 474 '0 472.0 449.8 480.0 475.0 499.8 468.2 482.3 479 '7 MAR 414' 4 416.5 429.6 421.5 410' 6 427.1 425.1 446 '4 435 '2 4lfLl 405' 9 436.9 440.3 425.6 428.4 428.8 417.3 405.4 426.7 449.4 446.3 431.4 415.2 407.7 382 '0 414,4 413.7 426-5 428.5 412.2 402 '2 417.2 410 '9 434.3 412.4 430.2 444.6 447.3 443.3 426.9 436.~ 453.6 422,8 414 '9 421 410.5 419.1 396.4 423.0 429.0 429' 2 439.5 416.9 408.7 438 '0 419.1 428 '6 417.2 434.9 434 '9 437.1 409.7 424.6 430.7 431.7 423.4 404 '9 424 '0 428.9 436. 428. 421 '7 402 '3 404.2 417.8 417.2 401.7 416 '9 417.6 448.8 413.8 428.9 423 '3 APR 340' 347.0 360.0 347.5 340.1 358.1 353' 0 377.3 311.4 351.2 307.1 355 '0 362 '0 362 '3 370.1 357.0 351.4 336.1 357.3 413.2 370.6 364 .2 343.6 341.1 317' 0 343 '2 353.8 362 '0 352 '7 306.8 339.3 344.2 336.9 373 '7 340.5 309.0 371.5 211.3 359 '0 350' 358.4 375.5 348.1 321.5 357.0 342.0 353.7 329' 1 349.8 357.0 281.4 363.5 346.3 325.7 361.7 343.2 358.9 312.5 355 '3 371.9 368.1 338 '0 364' 8 374.7 365.6 342.4 344.1 348.8 362.6 363' 9 369.4 345 '7 338 '1 340.1 339.0 350.2 326.8 333.1 337 '8 368' 3 345.8 349' 8 347 '3 MAY 297.6 302.4 318.6 310.6 297.2 314.4 322.0 347-7 277.9 309.0 273.0 323 '9 319.2 322' 6 332.7 321' 0 311.4 291.7 333' 6 338.5 348.7 329' 4 313.7 297.0 275.2 305.1 305.8 325.3 318 '0 274' 9 292.8 310.8 318' 9 329.9 308' 8 293.1 335.1 294 '7 347.4 315.5 332.7 332.1 326' 7 286.8 316.4 301.5 314.2 279.6 318.0 309.7 246.8 317.5 307 '6 3Cl.1 321.9 314.8 303.8 287 '9 326.7 309.8 317.9 289' 9 331.5 333.1 341.0 314.6 307.1 303.7 331.2 311.2 339' 9 309.1 297.7 282.5 233.5 306.3 281.6 304. 295.8 308 '3 309.1 314.3 310.8 255.7 293.0 282.2 265.1 280.6 306 '9 308.1 260.2 272.0 241.3 298.0 282.0 287.8 283.3 279.9 275.6 254.3 305.4 304.0 308.6 294.1 264.5 265.1 242.7 268.1 265.6 291.1 291.7 235.0 248 270' 8 279.9 282.4 270.8 277.7 291.5 302 1 314' 3 276.3 301.9 286.9 297.2 261.3 279.5 272 '9 272.5 245.0 282.6 267 '3 245.5 285 '2 280.5 289 '0 279.2 284.6 269.3 255.2 299' 8 281.2 311.2 254 '9 3QC. 287.3 299' 274.3 262.8 266' 2 296.4 297' 5 301.0 267.2 269. 246 '7 254.4 256.9 245.3 269.9 253.4 275.5 261 4 271 '6 276. JUL 270.9 468.2 291.4 287.2 269.0 282.3 307.2 304.4 270 '2 269 '1 616.0 310.1 280.2 285.7 277.4 275.8 274.5 619.9 348.5 316.0 313.4 305.0 268.3 280-4 243.8 273.2 266.8 310' 7 294 '6 1116.8 544.7 314.0 297.6 295.4 323 '7 '319.0 292' 3 313.1 324.2 284.7 312.6 296.0 317.1 272.7 347.1 281.2 279.8 1069.1 284.8 274 '7 260.6 303.0 296.1 288' 9 289.7 285.0 265.9 282.8 313.4 291.5 329.8 257.3 310.4 291.9 300.3 281.8 271' 7 282.3 322 4 303.1 288 268.5 288.2 252.9 255.2 273.2 568.7 271 '7 426.5 289 7 343 '0 259.4 328.7 AUG 1051.2 :331.4 296.2 401.4 670.5 285 '4 307.9 308.5 393.2 575.9 1031.2 313' 4 410.9 558.5 620.6 478.8 377.3 1069.5 335.4 327' 1 396.0 497.7 752 '0 974.9 712.2 1191.5 777.5 313' 3 296.9 1027.7 1028.9 809.6 301.3 375.7 897.0 316.5 298.0 310.2 319.1 735. 8 309.0 507.7 316.5 577.3 971.2 710 '9 571.2 1454 '7 287.1 619.2 832.3 307.7 295.3 575,4 287.8 1021.9 475.1 711.8 320.3 679.3 327.7 748.8 312.0 507.6 302.1 385.4 960.5 640.0 313.8 308' 2 361.7 708.1 736.0 587.0 593.2 323.1 1066' 7 1156.9 1003 '0 288.7 747 '1 266.4 584 '8 SEP 663.9 1056.2 851.8 905.6 1040.9 928.9 384.7 325.6 813.2 1118.4 1060.6 324.1 745. 941.9 814.9 740.6 805.0 806 6 354.2 342.8 780.2 645.8 1002.7 1265.4 1105' 9 845' 1016.7 690.5 1092.9 839.7 507.4 852.1 732.6 949.1 1087.7 778.0 337 '2 339.8 478.3 864.7 342 '4 829.6 655.2 1005 .4 519.8 572.1 961.3 705.7 830.9 1214 '6 480.2 417.8 1036.4 1297.2 1097.0 705.1 1096.2 715 '8 654.0 659.5 337.8 1118.3 680.7 844.1 337.5 956.4 678.1 951.1 334.2 891. 3 504.9 1523 '0 390.2 1238.5 127 7. 2 856.7 1210.0 1370.2 902.6 1144' 9 1367.0 672.5 812,4 Page2 AVG 527 '3 543.4 433.4 445.8 496.7 431.6 395.2 390.4 425.5 473.1 529.2 399 4 419.7 456' 5 440' 435.1 477.3 519.4 412.7 422.9 437' 3 434.5 469.2 536.9 526 '6 505.4 528 7 439.8 450. 577 '9 517.9 480 6 473 .3 453 502.1 426.8 409.1 374.8 404.3 517.0 426 .a 447.0 404.7 442.7 468.8 449.5 459.6 580.9 460 '2 488.3 444.4 413.5 474.7 494.9 440.0 462.6 445.7 458 '6 413.0 456.8 394.3 507.0 417.1 450.0 398.2 464 '7 515.2 490.4 402.4 429.6 418.3 517.0 403.7 540.5 513.0 491.5 526.4 535.7 507.9 452.4 517.1 444.0 463.5 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1.936 l937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 l97l 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1200.0 585.8 536.0 593. 8 640 494.9 515.6 373.5 497.8 467.7 552.3 580.1 352.3 485.3 362.3 515.6 1060.0 538.0 676.8 656.1 368.5 514. 3 501.6 676.9 12 00.0 647.8 1041.0 736.3 514.3 961.3 1100.5 660.7 1200.0 513.9 613.7 574.4 463.3. 369.5 361.7 1103.2 892.5 367.9 359.3 367.0 576.3 734.1 555.8 803.3 941.0 581.1 737.0 679.1 906.6 697.1 391.1 394.0 344.3 735.6 432.6 602.5 468.1 821.4 472.4 502.4 577.7 788.9 1181.1 865.1 609.8 373.0 608.1 596.7 404.6 1200.0 943.3 1200. 522.4 548.6 684.5 487.5 653.4 938.5 650.6 NOV 424.6 384.6 396.2 396.4 648.3 397.6 401.7 416.6 400.0 513.0 511.4 408.8 406.9 395.0 391.1 400.5 476.7 549.3 403.6 426.6 421.8 402.1 393. 572.8 417.9 391 526. 404 397.0 397.8 413.8 397.3 422.9 438.6 396.8 401.7 593.0 421.4 413.4 436.8 411.9 423.1 398.7 426.4 440.6 402.4 396.8 390.0 410.6 398.5 401.5 406. 9 410.7 390.4 396.1 388.9 394.0 399.6 398.4 409.3 403.7 485.9 394.3 400.3 404.9 403 .c 4.1.9.5 403.9 407.2 407.2 399.9 384.2 393.9 413.7 407.1 426.9 HO .1 379.8 389.4 396 0 394. 414.1 419.8 DEC 449.3 443.7 465.8 454.4 452.0 456.3 462.7 480.6 471.2 450.6 442.0 466.8 464.5 460.7 454.1 464.6 448.6 446.6 458.4 487.0 485.9 465.5 447.9 446.'7 449.6 450.2 450.9 461.0 462.3 441.9 431.1 452.4 444.1 467.5 446.6 462.9 486.1 485 8 484.1 455.8 458.4 486.9 460.7 451.5 451.2 445.0 453.4 411.0 451.0 456.0 460.7 467.4 457.0 441.8 458.4 453.5 459.7 448.7 461.9 466.4 462.7 444.8 461.1 463.8 459.9 459.2 440.0 450.2 460.0 473 .a 455.6 447.0 431.8 434.2 444.3 451. 9 410.9 442.0 447 <2 458 5 445.3 459.8 455.6 Appendix B SNETTISHAM HYDROELECTRIC PROJECT· PRELIMINk'Y • INPUT, SNETO?R6.IN RUN 6 • 322000 MW"H LOAD • ALL SNET GEN USABLE LONGOPR6. :JUT, CRATOPR6. O!IT JAN 460.5 458.1 475.0 467 .3 458.2 471.9 472.2 491.9 482.0 460.5 449.5 480.7 477.5 470.8 468.4 474.9 457.7 450.5 470.3 501.5 499.8 476. c 457.6 451.4 460.3 463.2 456. 471' 8 472 .a 451.5 448.3 463.8 456.3 482.4 459.5 473.8 492.4 499.5 497.7 469.1 468.4 494.6 471. 458. 466.6 455. 463.3 436.3 467.4 466.2 470.6 480.7 467.3 455.6 470.7 465.1 469 5 461 9 473.9 480.7 477.1 451.9 469.9 475.2 474.8 469.0 450.6 468.4 474.7 489.8 473.4 459.1 443.3 447.4 456.9 462.4 442.9 455.5 461.6 470.4 456.7 470.9 467,7 TIJNNEL !;'LOW TO LONG LAKE: TJRBINES (CFS) FE:B 471.1 469.6 487.8 461. a 468.8 48~.9 483.0 504.5 494.2 471.6 460.0 495.4 495.1 482 .1 483.5 484 .1 471.9 465 .1 482.2 512.8 508.1 488.6 470.4 463.3 428.2 471.5 469.9 484.3 485.1 469.6 457.1 474.4 464.6 494.6 468.5 485.7 504.5 503.4 509.3 484.6 497.6 510.2 482.1 469.1 477.9 466.0 474.1 450.0 475.7 485.8 486.8 493.5 475.8 468.1 488.6 475' 9 483.1 474.4 485.2 494.3 490.0 463.0 482.9 488.4 484.3 477.3 462.1 490.9 488.0 499. 488 .1 473.9 449.1 456.4 474.0 472.0 449 480.0 475.0 499. 468.2 482.3 479.7 MAR 414.4 416.5 429.6 421. 410.6 427.1 425.1 446.4 435.2 418.1 405.9 436.9 440.3 425 .6 428.4 428.8 417.3 405.4 426.7 449.4 446.3 431.4 415.2 407 382.0 414.4 413.7 426.5 428.5 412.2 402.2 417.2 410.9 434.3 412.4 430.2 444.6 447.3 443 .3 426.9 436.1 453.6 422.8 414.9 421.5 410 419.1 396.4 423.0 429.0 429.2 439.5 416.9 408.7 438.0 419,1 428.6 417.2 434.9 434.9 437.1 409.7 424.6 430.7 431.7 423.4 404.9 424.0 428.9 436.8 428.8 421.7 402.3 404.2 417.8 417.2 401..7 416.9 417.6 440.8 413.8 428.9 423 .J APR 340.3 347.0 360.0 34 7. 5 340.1 358.1 353.0 377.3 311.4 351.2 307 .1 355.0 362.0 362.3 370.1 357.0 351.4 336.1 357.3 413.2 370.6 364.2 143.6 341' 1 317.0 343.2 353.8 362.0 352.7 306.8 339.3 344.2 336.9 373.7 340.5 309.C 371.5 211 359. 350. 358.4 375.5 348.1 321.5 357.0 342.0 353.7 329.1 349.8 357.0 281.4 363.5 346.3 325.7 36:l.7 343.2 358.9 312.5 355.3 371.9 368.1 338.0 364.8 374.7 365.6 342.4 344.1 348.8 362.6 363.9 369.4 345.7 338.1 340.1 339.0 350.2 326. 333. 337.8 368.3 345.8 349 .a 347.3 MAY 297.6 302.4 318.6 310.6 297.2 314.4 322.0 347.7 277.9 309.0 273. c 323.9 319.2 322.6 332. 321. 3~1.4 291.7 333.6 338.5 3487 329.4 313.7 297.0 275.2 305.1 305.8 325.3 318.0 274.9 292.8 310.8 318.9 329.9 308. a 293.1 335.1 294.7 347.4 315.5 332.7 332 .l 326.7 286.8 316.4 301.5 314.2 279.6 318.0 309.7 246 .a 317.5 307.6 301.1 321.9 314.8 303.8 287.9 326.7 309.8 317.9 289.9 331.5 333.1 341.0 314.6 307.1 303.7 331.2 311.2 339.9 309.l 297.7 282.5 293.5 306.3 281.6 304.1 295.8 308.3 309 1 314.3 310.8 JlJN JUL 268.6 270.9 256.7 468.2 293.0 291.4 262.2 287.2 265.1 269.0 280.6 282.3 306.9 307.2 308.1 304.4 260.2 270.2 272.0 269.1 241.3 616.0 298.0 310.1 282.0 280.2 287.8 285.7 283.3 277.4 279.9 275.8 275.6 274.5 254.3 619.9 305.4 348.5 304.0 316.0 308.6 313.4 294.1 305.0 264.5 268.3 265.1 280.4 242.7 243.8 268.1 273.2 265.6 266 8 291.1 310.7 291.7 294.6 235 .o 1116. 248.5 544. 270.8 314 279.9 297. 282.4 295.4 270.8 323.7 277.7 3~9.0 291.5 292.3 302.1 313.1 314.3 324.2 276.3 284.7 301.9 312.6 286.9 296 .o 297.2 317.1 261.3 272.7 279.5 347.1 272.9 281.2 272.5 279.8 245.0 1069.1 282.6 284.8 267.3 274.7 245.5 260.6 285.2 303.0 280.5 296.1 289.0 288.9 279.2 289.7 284.6 285.0 269.3 265.9 255.2 282.8 299.8 313.4 281.2 291.5 311.2 329.8 254.9 257 300.3 310.4 287.3 291.9 299.2 300.3 274.3 281.8 262.8 271.7 266.2 282.3 296.4 322.4 297.5 303.~ 301.0 288.5 267.2· 268 269.1 288.2 246.7 252.9 254.4 255.2 256.9 273 2 245.3 568.7 269.9 271.7 253.4 426.5 275.5 289.7 261.4 343.0 271.6 259.4 276.9 328.7 AUG 1051.2 1200.0 296.2 401.4 670.5 285. 307. 308.5 393.2 575.9 1031.2 313.4 410.9 556.5 620.6 478.8 377.3 1069.5 335.4 327. 396. 497.7 752.0 974.9 712.2 1191.5 777.5 313.3 296.9 1027.7 1028.9 809.6 301.3 375.7 897.0 316.5 298.0 310.2 319.1 735.8 309. 507.7 316.5 577.3 971.2 710.9 571.2 1200.0 287.1 6~9.2 832.3 307.7 295.3 575.4 287.8 1021.9 475.1 111 a 320.3 679.3 327.7 748.8 312.0 507.6 302.1 385.4 960.5 640.0 313.8 308.2 361.7 708.1 736.0 587.0 593.2 323.1 1066.7 1156.9 1003. 0 288.7 747.1 266.4 580.1 SEP 663.9 1056.2 851.8 905.6 1040.9 928.9 384.7 325.6 813.2 1118.4 1060.6 324.1 745.7 941.9 814.9 740.6 805.0 806.6 354.2 342.8 780.2 645.8 1002.7 1200.0 1105.9 845.3 1016.7 690.6 1092. 839.7 507.4 852.1 732.6 949.1 1087.7 778.0 337.2 339.8 478.3 864.7 342 .4 829.6 655.2 1005.4 519.8 572.1 961.3 705.7 830.9 1200.0 480.2 417.8 1036.4 1200.0 1097.0 705.1 1096.2 715.8 654.0 659.5 337.8 1118.3 680.7 844.1 337. 956.4 678.1 951.1 334.2 B9l. 3 504.9 1200.0 390.2 1200.0 1200.0 856.7 1200.0 1200.0 902.6 1144.9 1200.0 672.5 800.7 Page3 AVG 526.0 532.4 433.4 445.8 496.7 431.6 395.2 390.4 425.5 473 1 529.2 399. 419.7 456.5 440.6 435.1 477.3 519.4 412.7 422.9 437. 434.5 469.2 531 4 5:9 6 505.4 528.7 439.8 450.6 577.9 517.9 480.6 472.2 453.1 502.1 426.8 409.1 374. 8 404.3 517.0 426.8 447.0 404.7 442.7 468.8 449.5 459.6 559.6 460.2 487.0 444.4 413.5 474.7 486.8 440.0 462.6 445.7 458 6 413.0 456.8 394.3 507.0 417.1 450.0 398.2 464.7 5~5.2 490.4 402 .• 429.6 418 3 490.1 403.7 522.1 506 .t) 483. 525. 521.5 507.9 452.4 503.2 444. 461.8 2'25/97 YEAR 19H 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 :1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1946 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1966 1969 1970 1971 1972 1973 1974 1975 1976 1977 1979 1979 1980 1981 :!.982 1983 1984 1985 1986 1987 1998 1989 1990 1991 1992 1993 1994 1995 AVG OCT 14.6 .0 .0 • 0 . 0 .0 .c .0 .0 .0 0 . 0 .0 .0 .0 . 0 .0 .o .0 .0 .0 . 0 .0 .0 83.9 .0 . 0 . 0 • 0 .0 .0 .0 13.7 .0 .0 .0 .0 .0 . 0 .0 .0 .0 . 0 . 0 . 0 .0 .0 .0 .o . 0 .0 .o . 0 .0 . 0 . 0 .0 .0 .0 .0 .0 .0 .o .o .0 0 .0 . 0 .0 .0 .0 .0 .0 182,4 .0 101.1 .~ . 0 . 0 .0 .0 .0 . 8 NOV .0 . 0 .0 . 0 . 0 . 0 . 0 . 0 . 0 .0 .0 .o . 0 . 0 . 0 .0 . 0 .0 • 0 . 0 .0 .0 .G .0 . 0 .0 .0 .0 .0 . 0 • 0 .0 .o .o .0 . 0 . 0 .0 .0 . c .0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .a . 0 . 0 .0 .0 .0 . 0 .o .o .0 . 0 . 0 .0 0 .0 .0 .0 . 0 . 0 .o .0 .0 .0 0 .0 .0 DEC .0 • 0 .0 . 0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .0 .0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 . 0 .0 . 0 • 0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .0 • 0 .0 .0 .0 .0 .0 .0 .0 .o . c • 0 . 0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 . a . 0 . 0 .0 .0 .0 .0 . 0 . 0 .0 . 0 .0 . 0 • 0 .0 .0 .o Appendix B SNETTISHAM HYOROELEC:RlC PROJECT -PRELIMINARY !NPU:, SNETOPR6.IN Rilll 6 -322000 MWH LOAD ALL SNET GEN USABLE LONGOPR6. OL"!', CRATOPR6. OUT JAN .0 . 0 . 0 .0 .c . 0 . 0 • 0 . 0 • 0 .0 .0 .0 .0 . 0 .0 .0 . 0 • 0 . 0 . 0 .o .0 .0 .0 .0 .0 .0 .0 .o . 0 .0 .0 .0 . 0 .o .0 .0 .0 .0 . 0 .0 .0 .0 .0 . 0 .0 • 0 .o .0 . c . 0 .0 .0 .0 .0 .0 .0 .o .0 .0 . 0 .0 .0 . 0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .~ .0 SPILL AT LONG LA.XE OUTLET (CFS) FEB . 0 . 0 . 0 .0 .0 . 0 . 0 .0 .c .0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 . 0 • 0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 • 0 .0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .o .0 .0 .0 . c . 0 .0 .0 .0 .0 .0 . 0 .0 .0 . 0 .0 .0 . 0 .0 .0 .0 . 0 .0 . 0 • 0 .0 .0 . 0 .0 . 0 . 0 .0 .0 .0 . 0 .o • 0 . 0 .0 .0 . 0 . 0 . 0 .c .c .0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .o .0 .0 . 0 .0 .0 .0 .0 .0 .o . 0 .0 .0 .0 .0 .0 .0 .0 .0 • 0 • 0 .0 .0 .0 .0 . 0 . 0 .o .0 .0 . 0 .0 • 0 .0 .0 .0 .0 .o .0 .0 . 0 . 0 . 0 .0 .o .0 .0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .c .0 .0 .c .0 APR .0 . 0 . 0 • 0 .0 .0 . 0 .0 • 0 .0 .0 . 0 . c . 0 .c 0 .0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .0 .c . 0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .o .0 .o .0 . 0 . 0 . 0 .0 .0 • 0 . 0 .0 .0 .0 .0 .0 .0 • 0 • 0 .0 .0 .0 . 0 .0 .o .0 .0 .0 .0 .0 . 0 .0 . c . 0 .0 .0 .0 . c . 0 . 0 .0 . 0 MAY .a .0 .a .0 . 0 . 0 • 0 • 0 • 0 .0 • 0 . 0 • 0 .a .a . a . 0 . 0 .0 .0 . 0 .0 .0 .0 .0 .0 . 0 . 0 .0 . J .0 . 0 . 0 . 0 .0 .o .0 .0 • 0 .0 .a .0 .0 .0 . 0 .o .o .0 . 0 . 0 . 0 . 0 .o .0 .0 .0 . 0 .o .0 .0 . 0 .0 .0 .o .o .G .0 . 0 .0 .o .0 • 0 • 0 • 0 .0 .0 .0 . 0 . 0 • 0 • 0 .0 • 0 .0 . 0 . 0 . 0 .0 .0 • 0 • 0 • 0 .0 .0 .0 .0 .0 . 0 . 0 0 .a .0 .0 .0 .0 .0 .o 0 . 0 .0 • 0 .G . 0 . 0 . 0 .0 . c . 0 .a . 0 .0 .0 .o .0 .0 .0 .0 .0 .G . 0 . 0 . 0 .0 .0 . 0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .0 . 0 .o . 0 . 0 .0 . 0 • 0 .0 .0 .0 .0 .0 JUL . 0 .0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 . 0 . 0 . 0 . 0 .0 .0 .0 . 0 . 0 .0 .0 . 0 . 0 .0 . 0 .o .0 . 0 . 0 .0 .0 . 0 • 0 • 0 . 0 .0 .0 .o .0 . 0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 .0 .0 . 0 .0 . 0 .0 . 0 . 0 . 0 .0 .0 . 0 . 0 • 0 .a .0 .0 .0 .0 .a . 0 .0 .o . 0 .a .0 .0 . 0 . 0 .0 .o .0 .o AUG .0 131.4 .0 . 0 . 0 . 0 .0 .0 .0 . 0 . 0 . 0 .0 .0 • 0 .0 • 0 .0 .0 . 0 . 0 . 0 . c . 0 • 0 .0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 . 0 . 0 . 0 .0 .0 254.7 .0 .0 .0 • 0 . 0 .a . 0 .0 . 0 .0 .o .0 .0 .0 .0 • 0 .a .o . o· .0 .a .0 . 0 . 0 .0 .0 .0 .0 0 .0 • 0 • 0 .0 .0 4.7 SEP . 0 . 0 .0 .0 .0 .0 .0 . 0 . 0 . 0 0 0 .0 . 0 . 0 .0 .0 .0 .0 • 0 .0 .0 . 0 65.4 .0 .0 .o . 0 . 0 . 0 . c .0 . 0 0 . 0 .o .0 .0 .0 .0 .0 .o .o .o .0 • 0 . 0 . a .0 14.6 .a . a .0 97.2 .0 . 0 .0 .0 . 0 . 0 .0 .0 . a . 0 .0 .0 .0 .a .0 . 0 .0 323.0 . 0 38.5 77.2 .0 10.0 170.2 . 0 .0 167 .a .0 11.7 Page4 AVG 1. 2 10.9 .0 .0 • 0 . 0 . 0 .0 .0 .0 . 0 . 0 . 0 .a .0 .0 .0 • 0 . 0 . 0 . 0 . 0 . c 5.5 7.0 .0 • 0 .0 .a .0 .0 .0 1.1 .0 .0 .0 .o . 0 . 0 .0 .0 .0 .o .0 . 0 . 0 .0 21.2 .0 1.2 .o .0 .0 a .1 . c . 0 .0 .0 .0 .0 . 0 • 0 .c .0 .0 . 0 .0 . 0 .0 .0 .0 26.9 . a 18.4 6 4 .4 . 8 14' 2 .0 . 0 13.9 .0 1.8 2/25/97 YEAR 1914 1915 1916 1917 1918 19l9 1920 192l 1922 1923 1924 1925 1926 1927 l928 1929 l930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 l952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 l967 1968 1969 1970 1971 1972 1973 1974 1975 1976 l977 l978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 732.4 793.8 796. 793.3 790.1 799.3 798.1 805.2 790.6 BOO. 7 795.9 794.2 805.6 799.8 763.3 798. 750.1 796 8 787.3 788 9 791.7 798.2 798.9 787.3 732.4 789.5 752.3 782.6 798.2 761.3 745.2 788.6 732.4 798.2 791.9 794.5 801.0 800.2 798.4 744.8 768.4 BOO .2 774.5 805.5 794.4 782.8 795.7 776.9 763.4 794.1 782.6 787.2 767.0 785.8 804.4 804.3 785.2 782.7 802.5 792.7 BOO. 7 765.6 800.5 798 9 794.3 767.9 734.9 771..1 792.2 800.2 792.3 793.1 803.8 732.4 763.2 732.4 797.7 796.1 786.8 799 7 789.1 763 784 .1 NOV 732.4 793.8 796.9 793.3 789.5 799.3 798.1 805.2 799.1 798.3 798.4 794.2 801.8 799.8 804.6 798.1 800.3 796_1 787.3 788.9 794.1 798.2 798.9 794.6 7 32 .4 789.5 797.5 762.6 798.2 761.3 745.2 788.6 732.4 802.2 791.9 794.5 793.3 793.8 794.9 802.3 768.4 803.5 804.4 802.8 802.1 782 8 795.7 776.9 763.4 804.1 782.6 787.2 767.0 785.8 804.4 804.3 805.1 782.7 802.5 792,7 800.7 799.8 800.5 798.9 794.. 778.1 734.9 771.1 792.2 805.2 792.3 793.1 803.8 '732 .4 763.2 732.4 797.7 796.1 786 8 799.7 789.1 763 7 787.9 DEC 801.5 800.1 791.9 792.4 789 s 801 794. 795. 794.9 798.3 798.4 800.7 800.4 80l. 791.0 802.0 800.3 796.1 793.4 788.6 796.8 799.7 795.7 794.6 793.4 797.0 797.5 796.0 800.4 801.2 802.6 800.5 787.5 602.2 803.5 799.9 793 _3 718.6 780.2 802.3 790.9 802.9 793.9 802.8 802.1 796.8 798.2 801.6 793.8 804.1 79l.2 797.2 791.6 796.7 802.3 794.6 801.7 799.2 793.5 794.6 793.5 799. a 789.6 797.5 791.5 796.4 795.4 799.2 797.9 788.8 792.1 790.5 788 '9 798.6 802 796.9 802.2 789.9 793.6 795.5 904.3 799. 796.4 Appendix B SNE'ITISHAM HYDROELECTRIC PROJECT -PRELIMINARY -INPIJ1': SNllTOl?R6. IN RUN 6 -322000 MWH LOAD-ALL SNllT GEN USABLE -LONGOPR6.0UT, CRAT0l?R6.01J1' JAN 787.1 782.8 777.5 772.6 784.6 785.3 775.8 773.2 782.4 785 2 791. 781.2 787. 789.1 769.0 791. s '187.~ 795.8 773.5 765.9 776.8 785.5 783.4 792 .1 782 .1 784 '3 791.6 779.9 785.9 788.3 792.8 782.6 766.2 781.5 791.3 782.9 784.7 753.2 757.3 785.4 774.0 793.4 772.0 796.2 785.8 780.9 783.7 794.7 773 6 793.6 777.4 782.0 773.4 776.6 783.5 774.9 788.3 779.8 772.8 771.7 769.9 791.7 770.7 783.2 767.4 782.8 784.2 782.7 776. 2 764.1 769 772.4 782.5 787.5 786.2 782.2 796.5 770.6 777_ 9 777.7 791.3 785.7 781.1 NET HEAD ON LONG LAKE UNITS \FEE":" I FEB 767 . .3 764.8 756.1 753.5 767.0 772.2 760.7 751.9 762.9 765.6 773.7 761.5 776.0 771.4 754.6 778.2 765.9 781.8 752.7 743.3 755.4 763.8 764.0 774.9 764.6 769 773.1 758.2 767.8 771.5 785.6 764.1 747.1 761.5 775. B 763.6 762.7 728.5 733.4 765.1 754.1 774.4 750.2 780.4 772 .l 761.5 765.2 779.6 758.6 778.4 759.7 768.9 752.7 756.1 763.0 753.0 768.6 761 6 753.2 752.2 750.3 773.5 753.4 765.1 748.6 762.0 765.3 768.8 756.3 744.9 754.6 756.9 767.9 774.5 767.3 766.5 779.3 751 1 762.0 759.5 "774. 5 767.1 763.0 749 "6 746.3 735.6 736 748.1 75J .0 743.3 732.2 742 0 748.4 755.2 741.6 760. 8 751.3 738.2 756.2 746.9 772.3 732.3 720.1 735.4 743.0 744.9 755. 752.2 751.3 754.3 73"7. 0 748.8 757.5 770.7 748.5 729.2 740.8 757.1 742. B 742.2 709.8 711.2 746.4 742.5 753.3 728.3 761.1 753.7 743.6 746.7 764.3 740.5 764.9 742.3 751. 732.2 736. 747.0 731.4 750. 742.8 733.0 732.6 729.6 754.3 734.8 745.7 728 7 742.3 746.9 752.2 737.5 722.4 737.8 746.0 756.9 759.3 753 a 748.8 762.2 738.7 754.9 751.4 755.5 748.3 745 .1 APR 735 .4 733.7 719.1 720.5 730.6 736.5 726.1 716_1 723.6 735.1 741.9 723.5 748.2 734.3 724.8 745.3 730.5 758. 716.5 702.9 717.4 725.2 729.0 740.7 744.2 736.1 737.8 720.0 731. 746. 757 .8 732.6 716.5 725.2 740.7 725.9 724.2 694.9 693.6 729.1 725.7 736.5 712.2 745.4 737.6 727.7 730.9 752.8 725.6 752 .6 726.2 738.6 717.3 720. B 738.0 715.9 736.3 725.7 719. B 7l6.6 715.6 741.1 718.5 728.3 715.3 726.8 730.6 737.2 722.3 705 .l 721.6 734.8 749.2 747.6 741.6 733.0 751.4 723.0 74.7.0 738.8 742.0 736.6 730.3 MAY 727 .4 729.9 710.9 709.9 720.6 727.7 714 9 705.9 719.3 729.4 736.9 711.6 736.5 726.5 720.0 734.2 722.8 750.8 707.0 698.2 708.1 716.5 722.4 732.9 737.5 727.9 731.8 712.8 720.5 738.4 753.7 724.0 708.0 720.2 728.7 721 1 713.5 697.4 685.3 719.7 714.4 724.6 700.8 737.0 729.7 718.9 723.6 749.1 716' 1 743.7 726_0 729.0 709.6 710.6 728.6 707.5 727.9 724.7 709.2 710.7 705.0 732.7 711.6 723.3 706.1 716.7 725.8 729.2 713.7 694.4 714.8 729.3 742.6 743.3 735.4 725.3 747.5 721.9 743.0 733. 7 737.9 731.1 722.8 JUN 731.9 745.1 708.6 712.3 721.9 728.8 711.3 708.9 726. 737.1 753.6 708.2 744.0 728.1 731.8 736.6 724.3 761.5 708.9 712.0 711.4 720.4 737.8 737.5 751.3 736 3 7)4. 7 715.6 722.7 754.3 769.3 734..3 '7:5 < 5 728.1 739.6 729.1 709.7 708.5 690.9 733.1 714.6 723.8 710.2 747.6 742.9 726.2 732.4 761.5 716.4 749.2 729.9 727.2 714.7 715.6 735.4 717.3 736.5 736.7 712.7 718.8 704.5 740.9 714.1 728.1 709.7 728.4 733.2 . 735.6 720.2 695.~ 719.9 739.2 747.4 755.2 745.1 743.2 757.7 ?27.6 756.1 743.6 752.6 744.9 729.7 JUL 757.9 767.9 736.7 732.5 746.0 742.6 724.5 729.5 748.5 760.3 767.2 730.1 773.2 758.7 759.5 764.3 746.6 776.4 731.2 729.7 741.6 735.1 765.6 781.9 776.3 758.9 759.6 742.5 746.6 716.6 782.0 767.4 74J.B 76G.7 774.7 753.4 728.5 745.6 714.1 766.4 736.7 743.8 725.0 773.2 777.5 757.9 755.3 736.3 742.0 772.1 765.8 748.1 740.0 757.9 755.5 760.6 762.0 760.9 730.4 740.8 122.9 764.1 730.6 752.6 733.1 751.2 760.5 754.5 748 .a 727.9 752.8 755.7 774.5 779.6 768.0 766.1 769.0 760.7 776.8 769.1 778.8 765.0 753.0 AUG 747.7 732.4 764.7 762.9 763.5 770 7 755.2 757-2 774.3 776.7 753 .4 756. 791. 7'77.3 779.5 784.0 772.7 748.9 753.6 751.0 764.0 769.0 773.0 759.8 '778.7 722.5 761. 791, 776. 753.9 753.7 776.3 773.9 786.2 767.9 777.1 754.0 768.1 749.5 770 76l.5 769.7 759.4 784.0 760.2 776.6 776.7 732.4 771.7 785.5 774.0 774.2 770.3 771.2 784.1 748_7 778.2 772.2 755.6 748.8 751.6 770.6 765.6 774.8 755.3 789.0 758.2 765.4 767 .1 755.4 774.4 765.9 775.4 791.4 '779.1 789.9 749.3 728 3 756.7 787.6 781.7 779.7 766-7 SEP 788.3 750.5 764.5 767.1 752.3 762.2 793.4 783.0 776.0 743.. 0 750.0 790.7 781.9 763.3 775.8 782.3 776.7 776.6 778.8 781.7 778.9 789.6 756.7 732.4 744.5 773.0 755.1 786.3 745.4 773.5 798.6 772.3 779.9 7€2.6 746.7 778.0 777.9 783.9 772.9 771.1. 776.5 774.5 789.0 756.4 797.9 794.7 761.2 785.1 762.7 732.4. 800.1 795.8 750.2 732.4 738.2 785.2 745.7 784.3 769.3 788.6 780.3 743.0 776.4 773.1 773.4 761.8 787.3 762.3 784.4 756.8 798.7 732.4 804. 5 732.4 732.4 771.9 732.4 732.4 767 4 738.7 732.4 772.1 768.1 PageS AVG 754.9 761. 754. 753.9 758. 764.9 758.0 755.3 761.7 764.8 768.0 757 8 775.6 766.7 759.3 772 760.3 775.9 751.9 747.6 756.0 762.0 764.2 765.4 757. ~ 761.3 762.3 758.7 761.9 760. 3 771.4 765.0 744.4 764.1 767.5 763.3 757.1 746.9 740,1 761.3 752 .3 766.7 751.7 774.4 771.3 762.5 763.8 767.6 752.3 772.9 763.1 765.6 748.8 753.8 765.4 758.1 765 5 762.8 754.5 755.1 752.0 764.7 755.5 764.1 751.5 758.6 754.8 760.8 759.1 746.7 760.1 759.l 774.8 761.2 761.5 757 .4 770.2 753.0 767 '4 766.3 769.1 763.1 760.7 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 192.1 1922 1923 1924 1925 1926 1927 1928 192 9 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1959 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 813.0 813.0 813 .c 813 .c 813 .o 813.0 813.0 813. 0 904.5 913.0 913.0 813.0 811.5 813 .o 813.0 813.0 813.0 813.0 813.0 813.0 798.3 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 806.6 804.9 813.0 813.0 806.7 813.0 813.0 813. c 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 913.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 803.4 913.0 813.0 813.0 802.8 813.0 813.0 813.0 808.0 813.0 813.0 8::.3,0 813 .o 813-0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 812 1 NOV 813 .o 813 .o 813.0 813.0 813.0 813.0 813.0 813.0 813.0 8l3.0 813.0 813.0 808.8 813.0 811.9 813.0 813.0 813.0 813.0 813.0 801.7 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 801.5 802.2 813.0 813.0 811.0 811.6 813.0 813.0 813.0 813.0 813.0 813 .o 813.0 813.0 813 0 813.0 813.0 813.0 813.0 811. 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813.0 813 0 813.0 813 0 813.0 813.0 813 '0 813.0 813.0 DEC 81l. 6 808.4 800.7 801.2 813.0 810.1 803.1 805.6 803.9 813. c 813.0 810.1 805.7 809.8 799.6 8ll.O 813.0 813.0 802.5 798.9 806.8 808.8 804.4 813.0 803.1 805.5 813.0 805.2 809. 810. 812.2 809.4 797.5 Sl3 .0 812.3 808.9 813.0 788 789.8 813.0 800.4 812.9 802.8 813.0 813.0 805.8 807.0 810.1 803.2 813.0 BOO. 2 806.5 801.0 805.2 811.1 803.0 810.4 808.2 802.4 804.0 802.6 813.0 798 3 806.5 800.6 805.5 805.3 808.3 807.2 798.1 801.0 798.7 797.6 808.1 811.9 807.1 810.7 797.9 802.0 804.3 812.9 809.2 806.4 Appendix B SNETTISF.AM HYDROELECTRIC PROJECT • PRELH'.INARY • INPUT, SNETOPR6. IN RUN 6 • 322000 M'IIH LOAD ALL SNET GEN USABLE LONGOPR6.0t:'T, CRATOPR6.0UT JAN 798.4 793.8 789.6 784.1 796.1 797.0 787.8 786.2 794.8 796.6 802.2 793.4 799.1 801.0 780.5 803.6 798.4 807 .o 785.2 779.2 790 .1 797-6 794.6 803.3 793.4 795.6 803.0 791.8 797.8 799.2 803.2 794- 777.2 793.8 802.5 794.9 797.9 766.4 770.4 797.1 785.7 806.7 783.9 807.6 797.2 792.0 795.2 804.2 785.0 805.2 789.3 794.2 785.1 787.5 795.3 786.4 800.1 791.1 784.7 783.8 781.9 802.7 782.6 795.3 779.2 794.6 795 .o 794.0 788.1 776.6 781.1 783.6 792.9 798.1 797.3 793.6 806. c 781.5 789. J. 789.5 802 .4 797.6 792.7 STATIC HEAD ON LONG LAKE UNITS (FEET) FEB 779.1 776.6 768.8 765.7 778.7 784.7 773.2 765.5 776.0 777.5 785.0 774.4 788.8 783.8 766.8 790.9 777.6 793.2 765.1 757.4 769.4 776.5 775.7 786.3 776-5 781.1 784.8 770.6 780.3 782.9 796.9 776.1 758.8 774.5 787.5 776.2 776 3 742.5 747.3 777.4 766.3 788 .1 762.6 792.1 784.3 773.1 777.2 790.3 770.9 790.6 772+1 781.8 765.0 767.7 775.5 765.1 781.0 773.6 765.8 765.1 763.0 784.9 765.7 777.7 761.2 774.3 776-7 781.1 768.9 758.3 767.1 768.7 778.9 785.7 779.0 778.5 790.3 762.7 773.9 771.9 786.2 779.6 775.2 762 .1 758 '6 748 9 749.5 760.4 766.0 756.3 746.5 755.7 760.9 767.1 755.4 774.6 764.3 751.2 771.4 759.3 784.4 745.3 734.9 749.9 756.4 757. 767.9 762.5 763 'i 766.7 750.1 762.0 769.8 782.4 761.1 741.3 754.5 769.4 756.0 756.5 724.0 725.7 759.5 756.3 767.9 741.3 773.5 766.5 755. a 759.3 775' 7 753.2 778.2 755.6 765.5 744.9 748.8 760-4 744.1 763.4 755.4 746.2 746.3 743.1 766.3 747.9 759.1 741.8 755.1 758.9 765.2 750.8 736.3 751.1 758.5 768.2 771.0 766.4 761.3 773.6 751.6 767-5 765. 3 767. 761. 758.0 APR 745.0 743.4 729.4 730.4 740. 746.7 736 . .L 727.3 734 .2 744.9 751.2 734.2 759.1 744.4 735.0 755.6 740.2 767.2 726.7 714.2 728.6 735-6 738.7 750.1 752 '4 745.7 74 7. 4 730.2 742,1 755.6 766.8 742.3 725.9 735.8 750.2 736.2 735.3 706.1 704.6 739.3 736.4 748.0 722.2 755.0 747.5 737.1 740.7 761.6 735.6 762.9 736.5 749.4 727.1 730. 748.8 725.8 746.6 735.5 730.4 727.2 726.3 750.5 728.6 738.7 725.7 736.8 739.8 747.3 732.6 715.8 731.9 744.7 758.2 756.7 751.4 742.8 760.5 732.8 756.8 749.7 75~.5 746.9 740.3 MAY 733.9 736.7 718.2 716.7 727.1 734.9 721. 713-8 724 _ e 736.4 742.1 718.7 743.8 733.9 727.6 741.3 729.7 757.2 714.1 707 8 715.8 723.9 729.0 739.4 743.1 734.5 738.9 720.1 727.4 743.7 760.2 730.6 714.4 728 .o 735.2 726.5 721.2 699.9 692.5 726.6 721.6 732.5 707.6 742.8 736.8 725.5 730.6 755.1 723.0 750.8 730.4 736.4 716.3 716.6 735. 714 .l 735.1 730.2 716.3 718.4 712.6 739.1 719.1 731.1 713.6 723.3 732.4 736.0 721.0 701.8 722.4 736.0 749.0 749.8 741.8 732 ~2 753.5 728.1 749.3 741.3 744.6 737.9 729.6 JllJil 736.8 750.2 714.3 717.7 726-9 734.3 717.1 715.7 730.7 742.5 757.8 714.1 749.7 734.0 738-0 742.4 729.7 766.3 715.1 718.4 718.2 726.5 743.4 742.4 755.5 741. 739. 721.5 728.4 758 5 774 .2 739.7 721.2 734.2 745.0 733.9 716.0 713.4 697-7 738.6 720.8 730.0 716.2 752-2 748.5 731.3 737.9 765.9 722.0 754.6 733-3 732.8 720.0 720.7 741.2 722.8 741.6 741.3 718.7 724.2 710.2 745.6 120.2 734.3 716.4 734.0 738.5 740. 726.3 700-6 726.4 744.5 752.3 759.7 749.9 748.4 762.1 732.8 761.0 748 758. 750.4 735.1 JUL 761. 780.2 741.5 736.9 749.9 747.0 729.8 734. B 752.3 764.5 788.4 735.1 777.'7 763.4 764.0 768.7 750.9 797.9 736.4 734. 746.9 739.9 769-5 786.3 779.6 762.9 763.6 747.2 751.3 786.4 798.7 773.0 748.2 765.2 780.5 754-8 733.3 750.7 719.6 770.7 741.9 748.4 730.0 777.0 784.2 762.0 759.5 BOO. 4 746,4 776.1 769.2 752.6 744.4 762.5 759.8 765.1 766.1 764.5 735.5 745.2 728.3 767.8 735.7 757.3 738.1 755.4 764.3 758.5 753.7 732.9 757. 9 759.7 778.6 783.0 771.6 769.8 787.1 764.8 787.0 773 785.4 769.1 759-9 AUG 809.6 813.0 769.4 772.0 788.7 775.2 760. 762 .4 783.0 795.2 813. c 762. 80".2 794.7 80l.O 796. 780.7 813.0 760.4 756.6 772.8 782.8 804.7 813.0 807.1 802.0 795. 796.6 781.2 813 .c 813.0 813.0 778.8 794.1 813.0 782.8 758.8 773.5 755 .4 BOO .4 766.9 784.1 765.0 802.7 813.0 804.9 795.0 813.0 776.3 807.0 812.8 779.4 775.2 789.7 788.8 807.2 790.8 800.6 761.1 774.6 757.6 802.0 771.0 789.2 760.4 797.3 809.9 788.4 772 9 760.5 781.8 793.9 805.7 810.7 798.8 795.8 813.0 803.3 8J.3.0 792.3 813.0 783.5 790.0 SEP 813.0 813 0 805 .1 813.0 813 0 810.5 801.7 788.3 813.0 813-0 813-0 796.2 813. 813, 813-0 813.0 813 .o 813 .c 785.8 787.7 813.0 813.0 813.0 813.0 813 0 813.0 813.0 813.0 812.3 SJ.3.0 8D.O 813.0 809.9 813.0 813.0 811.9 782.9 789 785.7 813.0 781.8 813.0 813.0 813.0 813.0 813.0 813.0 813-0 801.3 813.0 813.0 805.5 810.3 813.0 805.6 813.0 813.0 813.0 793.2 813.0 786.3 813.0 802 .4 813.0 778.6 813.0 813 .o 813.0 789.9 80l,2 813.0 8l3.0 813.0 813 813.0 813 .o 813.0 813.0 813.0 812.l 813.0 797.5 808.1 Page 6 AVG 781.5 793.3 767. 767 776- 777.7 767.8 764.3 773.8 780 9 788.2 768-3 786.4 780.7 775.2 785.0 776.5 794.8 763.6 759.6 767.6 773.9 779.7 786.7 784.3 781.0 782-7 772.7 776.5 788.2 795.5 781.5 766.6 777,7 786.2 775.7 768.1 755.2 749.6 780.1 767.0 779.1 764.1 787.9 785.8 777.2 778.4 792.9 770. 789.8 778.2 777.5 767.9 772.3 779.0 772.7 781.1 778.3 765- 769-0 761.5 783.4 766.5 777.3 76l. 8 775.4 780.0 779.9 769.8 758.6 771.6 777.3 785.0 788.5 783.9 780.7 791.3 774 786.6 781.2 788.4 779.9 776.7 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 192: 1922 1923 1924 :925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 :945 1946 :947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 l963 1964 1965 1966 1967 1968 1969 1970 197: 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG oc:: 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824. 0 824.0 824.0 824.0 819.8 824.0 822.9 824.0 824.0 824.0 824.0 824.0 812.7 824.0 824.0 824.0 824.0 824.0 824 0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 812.5 813.2 824. o. il24.o 822.0 822.6 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 822. 8 824.0 824.0 824 .o 824.0 824.0 824.0 824.0 824.0 824.0 824 0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 624.0 824.0 824.0 824 '0 824. 823.5 NOV 822.6 819 '4 811.7 812.2 824.0 821.1 814.1 816.6 814.9 824.0 824.0 821. 1 820.7 820.8 8~0.6 822.0 824.0 824.0 813.5 809.8 817.8 819. 815.4 824. 0 814. 816 824.0 816.2 820.3 821. 823. 820.4 808.5 824.0 823.3 819.9 824.0 799.6 800.8 824. 811 823. 813.8 824.0 824.0 816.8 818.0 821.1 814.2 824.0 811 2 817.5 812.0 816.2 822. 814.0 821.4 819.2 813.4 815.0 813.6 824.0 809.3 817.5 811.6 816.5 816.3 819.3 818.2 809.1 812.:l 809.7 808.6 819.1 822.9 818.1 821.7 BOB. 9 813.0 815.3 823.9 820.2 817.4 DEC 809.4 804.8 soc. 6 795. 807.1 ao8.a 798.8 797.2 aos. a 807.6 813.2 804.4 810.1 812,0 791.5 814.6 809.4 818,0 796.2 790.2 801.1 808.6 805.6 814.3 804.4 806.6 814.0 8C2.8 808.8 810 814.2 805.0 788.2 804.8 813.5 805.9 808.9 777.4 781.4 808.1 796.7 817.7 794.9 818.6 808.2 803.0 806.2 815.2 796.0 816.2 800.3 805.2 796.1 798.5 806.3 797.4 811.1 802.1 795.7 794.8 792.9 813.7 793.6 806.3 790.2 805.6 806.0 eos.o 799.1 787.6 792.1 794.6 803.9 809. 808.3 804.6 817.0 792.5 800.1 800.5 813.4 808.6 803.7 Appendix B SNETTISHAM HYDROELECTRIC PROJECT-PRELIMINARY-INPUTo SNETOPR6.IN RUN 6 -322000 MWH LOAD ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6.0UT JAN 790.1 787.6 779.8 776.7 789.7 795.7 784.2 776.5 787.0 788.5 796' 0 785.4 799.8 794.8 777.8 801.9 788.6 804.2 776 .l 768.4 780 '4 787.5 786.7 797. 787. 792.1 795.8 781.6 791.3 793.9 807.9 787.l 769.8 785.5 798.5 787.2 787.3 753.5 758 '3 788.4 777.3 799.1 773.6 803.1 795 '3 784.1 788.2 801.3 781.9 801.6 783 .l 792.8 776.0 778.7 786.5 776.1 792.0 784.6 776.8 776.1 774.0 795.9 776.7 788.7 772.2 785.3 787.7 792.1 779.9 769 778.1 779.7 789.9 796.7 790.0 789.5 801.3 773.7 784 '9 782.9 797.2 790.6 786.2 END OF MON':H LONG LAKE ELEVATION (FEET) FEB 773.1 769.6 759.9 760.5 771.4 777.0 767.3 757.5 766.7 771.9 778.1 766.4 785.6 775.3 762.2 782.4 770.3 795.4 756.3 745.9 760.9 767 4 768 '3 778.9 773.5 774.7 777.7 761.1 773.0 780.8 793.4 772.1 752.3 765.5 780.4 767' 0 767' 5 735.0 736.7 770.5 767.3 778.9 752.3 784.5 777.5 766.8 770.3 786.7 764.2 789.2 766.6 776.5 755.9 759.8 771.4 755.1 774.4 766.4 757.2 757.3 754.1 777.3 758.9 770.1 752.8 766.1 769.9 776.2 761.8 747.3 762.1 769.5 779.2 782.0 777.4 772 3 784,6 762.6 778.5 776.3 778.8 772.3 769.0 MAR 756.0 754.4 740.4 741.4 751.0 757.7 747.2 738.3 745.2 755.9 762.2 745.2 77C .1 755.4 746.0 766.6 751.2 778' 2 737.7 725.2 739 6 746.6 749.7 761.1 763.4 756.7 758.4 741.2 753.1 766.6 777.8 753.3 736.9 746.8 761.2 747.2 746.3 717.1 715.6 750.3 747.4 759.0 733.2 766 .o 758.5 748 .1 751.7 772.6 746.6 773.9 747.5 760.4 738.1 74l.l 759.8 736.8 757.6 746.5 741.4 738.2 737.3 761.5 739.6 749.7 736.7 747.8 750.8 758.3 743.6 726 8 742.9 755.7 769.2 767.7 762.4 753.8 77::...,5 743.8 767. 760. 7 762.5 757.9 751.3 APR 744.9 747 "7 729.2 727.7 7JB .1 745. 9 732.9 724.8 735.8 747.4 753.1 729.7 754.8 744.9 738.6 752.3 740.7 768.2 725.1 718.8 726.8 734.9 740.0 750.4 754 745.5 749.9 731.1 738.4 754.7 771.2 741.6 725.4 739.0 746' 2 737.5 732.2 710.9 703.5 737.6 732.6 743.5 718.6 753.8 747.8 736.5 741.6 766.1 734.0 761.8 741.4 747.4 727.3 727 '6 746.9 725.1 746.1 741.2 727.3 729.4 723.6 750.1 730.1 742.: 724.6 734.3 743.4 747.0 732.0 712.8 733.4 747 0 760.0 760.8 752 .a 743.2 764.5 739.1 760.3 752.3 755.6 748.9 740.6 MAY 747.8 761.2 725.3 728,7 737.9 745.3 728.1 726.7 741.7 753.5 768.8 725.1 760.7 745.0 749.0 753.4 740.7 777.3 726 1 729. 729 737.5 754.4 753.4 766.5 752.5 750.9 732.5 739.4 769. 785.2 750.7 732. 2 745.2 756.0 744.9 727 .c 724.4 708.7 749.6 731.8 741.0 727.2 763.2 759.5 742.3 748.9 776.9 733.0 765.6 744.3 743.8 731.0 731.7 752.2 733.8 752.6 752.3 729.7 735 '2 721.2 756.6 731.2 745.3 727.2 745.0 749.5 751.8 737.3 711.6 737.4 755.5 763.3 770 7 760.9 759.4 773.1 743.8 772.0 759.9 769.0 761.4 746.~ 772.9 791.2 752.5 747.9 760.9 758.0 740. 745. 763' 775' 799 746. 788.7 774.4 775. c 779.7 761.9 808.9 747.4 745.9 757' 9 750.9 780.5 797.3 790.6 773.9 774.6 758.2 762.3 797.4 809.7 784.0 759.2 776.2 791.5 765.8 744.3 761.7 730.6 781.7 752.9 759.4 741.0 788.0 795.2 773.0 770 811.4 757.4 787.1 780.2 763.6 755.4 773.5 770.8 776.1 777.1 775.5 746.5 756.2 739.3 778.8 746.7 768.3 749.1 766.4 775.3 769.5 764.7 743.9 768.8 770.7 789.6 794.0 782.6 780 .s 798.1 775.8 798.0 784.3 796.4 780.1 770.9 JliL 820.6 824.0 780.4 783.C 799.7 786.2 771.5 773.4 794.0 806.2 824.0 773.- 812.2 805 7 812.0 807.8 791.7 824.0 771.4 767.6 783.8 793.8 815.7 824.0 818.1 813.0 806. 807.6 792.2 824.0 824.0 824.0 789. 805. 824. 793.6 769.8 784.5 766.4 811.4 777.9 795 1 776.0 813.7 824.0 815.9 806.0 824.0 787.3 818.0 823.8 790.4 786.2 800.7 799 .a 818.2 801.8 811.6 772.1 785.6 768.6 813.0 782.0 BOO .2 771.4 808.3 820 '9 799 4 783.9 771.5 792. B 804.9 816.7 821.7 809.8 806.8 824.0 814.3 824' 0 803.3 824.0 794.5 801.0 AUG 824.0 824.0 816 824.0 824.0 821.5 812.7 799.3 824.0 824.0 824,0 807.2 824.0 824. 824.0 824.0 824.0 824.. 0 796.8 798.7 824.0 824.0 824 .o 824. c 824.0 824.0 824.0 824.0 823.3 824 .a 824 .o 824.0 820.9 824 .o 824.0 822.9 793.9 800.3 796.7 824.0 792.8 824. 824.0 824.0 824.0 824.0 824.0 824.0 812.3 824.0 824.0 816.5 821.3 824.0 816.6 824.0 824.0 824.0 804.2 824.0 797.3 824.0 813.4 824.0 789.6 824.0 824.0 824.0 800.9 812.2 824.0 824.0 824.0 824.0 824.0 824.~ 824.0 824.0 824.0 823.1 824.0 808.5 819.1 SEP 824.0 824.0 824.0 824.0 824.0 824.0 824.0 815.5 824.0 824.0 824.0 822.5 824.0 824.0 824.0 824.0 824.0 824.0 824.0 809.3 824.0 824.0 824.0 824.0 824 0 824.0 824.0 824 .o 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 817.6 815.9 824.0 824.0 817.7 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 824.0 814.4 824.0 824.0 824.0 813.8 824.0 824. c 824.0 819.0 824.0 824 '0 824.0 824.0 824.0 824.0 824.0 824.0 824. 0 824.0 824.0 824.0 824.0 823.1 Page7 AVG 792.5 794.3 778.7 778. 8 787.6 788.7 778.8 774.6 785.5 791.9 799.2 179.2 797.5 791.7 786.2 796.0 787.5 805.8 774.6 769.4 779.8 784.9 790.7 797.7 795.3 792.0 793.7 783.7 787.5 799.2 806 5 792.5 777.6 788.7 797.2 786.7 778.6 766.1 761.3 791.1 777.5 790.6 775.1 798.9 796.8 788.2 789.4 803.9 781.2 800,8 789.2 788.5 778.9 783.3 790.0 783.7 792 1 789.3 776.0 780.0 771.7 795.2 777.5 788.3 771.9 787 '3 791.0 790.9 780.4 770.0 782.6 788.3 796' 0 799.5 794 '9 791.7 802.3 785. 797.6 792.2 799.4 790.9 787.7 2/25/97 YEAR 1914 1915 1916 1917 1918 19~9 1920 192l 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951. 1952 1953 1.954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1997 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 354 73 9 360000 358629 360000 360000 360000 360000 360000 345463 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 345199 346157 360000 360000 357562 358285 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 358457 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 3 60000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 359323 NOV 356267 354212 34414 9 344884 360000 356365 347285 350524 348372 360000 360000 356362 355832 356028 342718 357467 360000 360000 346582 34l742 352151 354730 349006 360000 347387 350490 360000 350027 355330 356321 358990 355470 339922 360000 359163 354860 360000 327492 3 29097 360000 343845 359846 346929 360000 360000 350885 352389 356417 347520 360000 343551 351692 344641 350090 357595 347235 356721 353901 3463 8 2 348437 346701 360000 341017 351763 344140 350438 350199 354110 352693 340?76 344636 341636 340043 353886 358576 352498 357l58 340513 345965 346926 359935 355301 351588 Appendix B SNETTIS~~ HYDROELECTRIC PROJECT-PRELIMINARY INPUT: SNETOPR6.IN RUN 6 -322000 MWH LOAD -ALL sm:r GEN USABLE • LONGOPR6 .OUT, CRATOPR6 .OtT:: END OF MONTH LONG LAKE STORAGE (ACRE-FEET) DEC JAN FEB MAR 341222 316150 293969 273694 334790 312856 289572 272083 328884 302691 278389 254989 322156 298711 279041 256256 337919 315634 291B37 268l6: 339202 322851 299083 275836 326561 308424 286948 263557 324595 298449 275614 252326 336181 312040 286234 260984 338575 314000 292444 273790 346170 323245 300525 280992 334204 310017 285808 260970 342085 327762 310232 290116 344584 321745 296876 273238 317812 300200 281082 262045 347942 330620 306071 286044 341111 314175 290421 268387 352370 333845 322443 300637 323492 297891 274216 251601 316243 286123 261824 236685 329486 303514 279499 253945 340075 312783 266953 262807 335846 311695 288085 266570 347563 324736 301507 279709 334228 312750 294512 282361 337265 318558 296145 274687 347136 322977 300022 276669 331945 305139 279748 256037 340387 317543 293935 270577 342282 320671 304092 286128 347510 338998 320032 300175 335052 312250 292721 270845 313665 289751 269652 250664 334655 310133 284801 262990 346521 326234 303464 279920 336266 312371 286573 263540 340480 312444 287117 262371 299602 270969 248293 227819 304815 276509 250377 226115 339279 313921 290667 267334 324070 299548 286913 263702 35200! 326937 301596 277324 32192l 294724 269646 246062 353185 332395 308795 285394 339443 322411 299687 276785 332134 308342 286281 264660 336634 313643 290393 268955 348755 329762 311670 293342 323158 305445 283284 262800 350109 330181 314901 295100 328397 307016 286065 263885 335278 319384 298442 278986 323325 297740 273780 252079 326245 301302 278316 255935 336762 311392 291842 278221 324938 297929 272843 250441 343421 318342 295766 275724 330956 308953 285842 262588 322900 298813 275277 256290 321807 297970 275355 252252 319500 295246 271693 251112 346854 323077 299459 280269 320325 298770 277207 253971 336781 314332 290141 266603 316278 292848 270226 250371 335662 309945 285506 264299 336408 313009 289836 267939 335004 318495 298016 276494 326913 302923 280587 259038 312921 289252 263682 238465 318541 300550 280950 258168 321470 302641 289477 273582 333473 315838 301976 289121 340672 324014 305536 287388 339605 315973 299626 281226 334500 315368 292951 271329 351071 329803 308934 291904 318991 294850 281542 259216 328128 309381 301055 287413 328683 306772 298243 279301 346397 324599 301433 281428 339989 316672 292972 276066 333463 310975 289373 268160 APR 260619 264111 241104 239467 252075 261831 245582 236305 249225 263690 270602 241625 272574 260618 252780 269647 255419 297880 236651 229668 2 384 71 248096 254494 267489 271696 261419 266825 243401 252539 272408 291508 256559 236929 253261 262238 251370 244782 221039 2l3508 251446 245301 258896 229440 271348 264280 250109 256475 285539 246962 280580 256271 263736 239047 239345 263116 236564 262152 255991 239044 241334 234919 267165 242074 257168 236080 247389 258807 263216 244555 223115 246309 263241 278484 279399 270273 256477 283642 253389 278897 269662 273462 265646 255267 MAY JUN 264291 293832 279847 317386 236825 269842 240592 264435 251862 279569 261146 276249 239916 255519 238383 261766 256580 282329 270996 297113 288562 327304 236628 262068 279274 314279 260702 295696 265793 296543 270912 302549 255412 280628 299487 340498 237734 263727 241341 261833 241108 276120 251336 268042 272006 303663 270967 324763 285967 316672 269847 295085 268054 295969 245108 276448 253750 281174 289454 324911 309698 341518 267845 308148 244802 277573 261023 298081 273871 317850 260671 285119 238684 259865 235829 280429 218660 242793 266556 305209 244232 270278 255739 277804 238886 255725 282186 313451 277950 322250 257314 293962 265658 290626 298939 343761 245811 275542 284937 312250 259930 303280 259279 282668 243236 273200 244120 294590 269511 291087 246809 297926 270016 299180 269656 297202 241648 262595 248513 274179 232271 253592 274551 301399 243556 262853 261123 287990 238933 265898 260733 285890 266374 296929 269053 '289372 251133 283949 221708 259379 251224 288676 273350 290912 282326 315474 290920 320808 279542 306410 277826 304060 294040 325736 259278 297499 292652 325613 278408 308647 288806 323683 280112 303160 261876 292099 JUL 355765 360000 303554 306846 327612 311012 291987 294384 320770 336712 360000 293994 344883 336039 344663 338987 318028 360000 291866 287208 307940 320618 349381 360000 352482 345921 337274 338683 318597 360000 360000 360000 315793 335154 360000 320614 289799 308911 285824 343798 300312 322114 297835 346773 360000 349688 336408 360000 312437 352395 359731 316461 311088 329027 327710 352614 330588 344089 292691 310339 288443 345900 305614 326300 291813 339628 356133 327233 308114 291979 319321 334907 350703 357132 341692 337475 360000 347562 360000 332635 360000 321371 330163 AUG 360000 360000 349928 360000 360000 356872 345494 327142 3 60000 360000 360000 338043 360000 360000 360000 360000 360000 360000 324150 326422 360000 360000 360000 360000 360000 360000 360000 360000 359088 360000 360000 360000 356139 360000 360000 358566 320690 328451 324013 360000 319363 360000 360000 360000 360000 360000 360000 360000 345041 360000 360000 350495 356672 360000 350611 360000 360000 360000 333894 360000 324777 360000 346361 360000 315418 360000 360000 360000 329260 344920 360000 360000 360000 360000 360000 360000 360000 360000 360000 358899 3 60000 339860 353544 SEP 360000 360000 360000 360000 360000 360000 360000 349089 360000 360000 360000 358152 360000 360000 360000 360000 360000 360000 360000 340966 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 351875 349671 360000 360000 352062 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 347698 360000 360000 360000 346940 360000 360000 360000 353738 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 360000 358905 Page 8 AVG 319836 322071 302530 302699 313722 315037 302606 297381 311059 318943 328117 303156 325981 318794 311855 324187 313632 336430 297326 29l005 303975 310453 317562 326394 323271 3:3..9:..18 321244 308878 313577 328022 337369 319907 301241 315008 325772 312496 302342 2 86 97 5 281489 318184 300802 317485 298288 327794 325234 314448 315932 334015 305667 330038 315679 314703 302901 308247 316487 308941 319197 315765 299128 304182 293829 323223 300979 314517 294079 313308 317970 317583 304409 292183 307365 314268 323953 328312 322744 318701 331857 311070 325759 }19183 328312 317596 313728 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 ::.923 1924 1925 1926 1927 1929 1929 H30 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1959 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 l979 1980 1981 1982 1983 1984 1995 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 64 '9 34,4 31,6 34.8 37.4 29.2 30.4 22.2 29.1 27.7 32.5 34.0 21.0 28.7 20.4 3C.4 58' 7 31.7 39.4 38,2 21.6 30.3 29.6 39.4 64.9 37. 57' 9 42.6 30.3 54.1 60.6 39.5 64.9 30.3 35 '9 33.7 27.4 21.8 21.3 60.7 50,7 21.8 20.6 21.8 33.8 42.5 32.7 46.1 53.1 34 .1 42.6 39.5 51.4 40.5 23.2 23.4 20.0 42.5 25.7 35.3 27.7 46.5 27.9 29.7 33.9 44. 8 64.1 49.3 35.7 22.1 35.6 35.0 24.0 64.9 53.2 64.9 30. 32.3 39.8 28. 8 38.1 53. c 37.4 NOV 23.0 22.6 23.3 23.2 37.8 23.5 23.7 24. 8 23.6 30. 30.2 24.0 24,1. 23.3 23.3 23.6 28.2 32.3 23.5 24.9 24.8 23 '7 23.2 33. 22.6 22. a 31. c 23 .4 23.4 22.4 22.8 23.1 22.9 26.0 23.2 23.6 34.8 24 24 ,3 25.9 23.4 25.1 23.7 25.3 26.1 23.3 23.3 22.4 23.2 23.7 23.2 23.7 23.3 22.7 23.5 23.1 23.4 23.1 23.6 24.0 23.9 28.7 23.3 23.6 23.9 23.2 22.8 23.0 23.8 24.2 23.4 22.5 23.4 22.4 23.0 23.1 23.0 22.3 22.6 23.4 23.0 23.4 24.4 DEC 26 '6 26' 2 27.3 26.6 26 4 27.0 27 1 28.3 27.7 26.6 26.1 27.6 27.5 27.3 26.5 27.5 26.5 26.3 26.9 28.4 28.6 27.5 26.3 26.2 26.4 26.5 26.6 27. 1 27 '3 26.2 25.6 26. a 25.8 27.7 26.5 27.4 28.5 28.0 27.9 27. 0 26. 8 28.9 27.0 26.8 26.7 26 '2 26.7 24.3 26.5 27.1 26.9 27.5 26.7 26.0 27.2 26.6 27.2 26.5 27.1 27.4 27.1 26.3 26.9 27.3 26.9 27.0 25.9 26.6 27.1 27.6 26.7 26.1 25.2 25.6 26.4 26.6 24.4 25.8 26.2 27.0 26.5 27.2 26.8 Appendix B SNETTISHAM HYDROELECTRIC PROJECT -PRELIMINARY !NPU:, SNETOPR6.IN RUN 6 322000 MWH LOAD ALL SNET GEN USABLE -LONGOPR6. OU., CRATOPR6. OUT TOTAL NET POWER FROM BO':'H LONG LAKE UNITS [MWl JAN 26.8 26.5 27.3 26.7 26.6 27.4 27.1 28 1 27.9 26.7 26.3 27. a 27.8 27.5 26.6 27.8 26 6 26 5 26.9 28.4 28.7 27.6 26. 26.4 26.6 26.8 26.7 27.2 27.5 26.3 26.3 26. 8 25. 27. 26. 27.4 28.5 27.8 27.8 27.2 26.8 29.0 26.9 27.0 27.1 26 3 26.8 25.6 26,7 27.3 27.0 27.8 26.7 26.1 27.3 26.6 27.3 26.6 27.1 27.4 27.: 26.4 26 .a 27.5 26.9 27.1 26.1 27.1 27.2 27.7 26.9 26.2 25.6 26.0 26.5 26.7 26.1 25.9 26.5 27 .Q 26. 7 27.3 27.:J FEB 26.7 26. 5 2'7. 3 26.8 26.6 27.5 27.1 28.0 27.9 26.7 26.3 27.9 28.4 27.5 27. Q 27.8 26.7 26.9 26.8 28.2 28.4 27.6 26.6 26.5 24.2 26.8 26.8 27. 1 27.5 26. 26.5 26.8 25.7 27.8 26.9 27.4 28.4 27.1 27.6 27.4 27.7 29.2 26.7 27.1 27.3 26.2 26.8 25.9 26.7 27.9 27.3 28.0 26.5 26.2 27.6 26.5 27.4 26.7 27.0 27.5 27.2 26.5 26.9 27.6 26.8 26.9 26.1 27.3 27.3 27.5 27.2 26.5 25. 26.1 26.9 26.7 25.9 26.6 26.7 28.0 26.8 27.3 27.0 23.0 23.0 23 22. 22,7 23. B 23 '3 24.2 23.9 23.1 22.7 23.9 24.8 23.6 23.4 24.0 23.0 23.1 23.1 23.9 24.3 23.7 22.9 22.8 21.2 23.0 23.1 23.2 23.7 23.1 22.9 23.1 22.1 23.8 23 .l 23.6 24.4 23.5 23.3 23.5 23.9 25.3 22 8 23.3 23 .5 22.6 23.1 22.4 23.1 24.2 23.5 24.4 22.6 22.2 24.2 22.6 23.8 22.9 23.6 23.5 23.6 22 '8 23 '1 23.7 23.2 23.2 22.3 23.6 23 .4 23.3 23.4 23.2 22 "5 22.7 23.3 23.1 22.6 22.8 23.3 24.5 23.1 23.7 23.3 APR 18.5 18.8 19.1 18.5 18.4 19.5 19.9 20.0 16.7 19.1 16.8 19.0 20.0 19,7 19.8 19.7 19.0 18.8 18.9 21.5 19.6 19.5 18.5 18.7 :!._7 .4 18.7 19.3 19.3 19.1 16.9 19.0 18.6 17.8 20.0 19.6 16.6 19.9 10.9 18.4 18.9 19.2 20.4 18.3 17.7 19.5 18.4 19.1 18.3 18.8 19.9 15.1 19.8 18.4 17.3 l9. 7 18.2 19.5 16.8 18.9 19 '7 19.5 18.5 19.4 20.2 19 .3 18.4 18.6 19.0 19.4 19.0 19.7 18.8 18.7 1a. a 18.6 19.0 18 .1 17.8 18.6 20.1 19.0 19.0 l8 7 MAY 16.0 16.3 16.7 16.3 15.8 16.9 17.0 18 1 14.8 16.7 14.9 17.0 17.4 17.3 17.7 17.4 16.6 16.2 17 '4 17.5 18.2 17.4 16 7 16.1 15.0 16.4 16.5 :..7 .1 16.9 15.0 16.3 16.6 16.7 17.6 16.6 15.6 17.7 15.2 17.6 16 8 17.6 17.8 16.9 15.6 17.1 16.0 ::.6.8 15.5 16.8 17.0 13.2 17.1 16.1 15.8 17,3 16.5 16.3 15 .4 17.1 16.3 16.6 15.7 17.4 17.8 17.8 16.7 16.5 16.4 17.5 16.0 18.0 16.7 16.3 15.5 15.9 16.4 15.6 16.2 16.2 16.7 16.9 17.0 16.6 JUN 14.5 H.1 15.3 14.9 14,1 15.1 16.1 16.1 14.0 14.8 13.4 15.6 15.5 15.5 15.3 15.2 14.8 14.3 16.0 16.0 16.2 15 '7 14.4 14.4 13.5 14.6 14.4 15.4 15.6 1.3 .1 14.1 14.7 14.8 15.2 14.8 15.0 15.3 15.8 16.0 15.0 15.9 15.3 15.6 14.4 15.3 14.6 14.7 13.8 15,0 14.8 13.2 15.3 14.8 15.3 15.2 15 '1 14.7 13.9 15.8 14 '9 16.2 14.0 15.8 15.5 15,7 14 .8 14.2 14.5 15.8 15.3 16.0 14 6 14.9 l3 .8 14.0 14 .1 13.7 14.5 14.2 15.1 14.5 14.9 14.9 JUL 15.2 26.6 15.9 15.5 14.8 15.5 16.4 16.4 14.9 15.1 34., 16.7 16.0 16.0 15.6 15.6 15.1 35.6 18.8 17.0 17.2 1.6 .6 ~5 .2 16.2 14,0 15.3 15.0 17.0 16.3 59.1 31.5 17.8 16.4 16.6 18 '5 17.7 15.7 17.2 17.1 16.1 17.0 16.3 17.0 15.6 19.9 15.7 15.6 58.2 15.6 15.7 14.7 16.7 16.2 16.2 16.2 16.0 15.0 15.9 16. 9 16.0 17.6 14.5 16. 8 16.2 16.3 15.6 15.3 15.7 17.8 16.3 16.0 15.0 16.5 14.6 14.5 15,5 32.3 15.3 24.5 16. 19 '7 14 '7 18.3 AUG 58.1. 64. 16.7 22.6 37.8 16. 17.2 17.3 22.5 33.0 57.4 l7 .5 24.0 32.1 35.7 27,7 21.5 59.2 18.7 18.2 22.4 28.3 43.0 54.7 41.0 63.6 43.8 18.3 17.0 57.2 57.3 46.4 17 2 21.8 50.9 18.2 16.6 17.6 17.7 41.9 17.4 28.9 17. 8 33.4 54.6 40.8 32.8 64.9 16.4 35.9 47.6 17.6 16.8 32.8 16.7 56.5 27,3 40.6 17.9 37.6 18.2 42.6 17.7 29.1 16.9 22.5 53.8 36.2 17.8 17.2 20.7 40.1 42. 34 34 l 18 '9 59.1 62.3 56.1 16.8 43.2 15.3 32.7 SEP 38.7 58.6 48.1 51.3 57.9 52.3 22.6 18.8 46.6 61.4 58.8 18.9 43.1 53.1 46.7 42.8 46.2 46.3 20.4 19 8 44.9 37.7 56" 1 64.9 60.8 48 '3 56.7 40.1 60.2 48.0 29.9 48.6 42.2 53.5 60.0 44,7 19.4 19.7 27.3 49.3 19.6 47.5 38.2 56.2 30.6 33.6 54 .1 40.9 46.8 64.9 28.4 24.6 57.4 64.9 59.9 40.9 60.4 41.5 37.2 38 .4 19.5 61.4 39.1 48.2 19.3 53.8 39.4 53.6 19 '4 49.8 29.8 64.9 23.2 64.9 64 '9 48.9 64.9 64.9 51.2 62.5 64.9 38 .4 45.1 Page 9 AVG 29.3 29.9 24.3 25.0 28.0 24.5 22.3 21.9 24.1 26.8 30.0 22.5 24.1 26.0 24.8 25.0 26.9 29. 23. 23.5 24.6 24. 26.6 30.0 29.0 28,4 29.8 24.8 25.4 32.3 29.4 27.3 26.0 25.7 28.5 24.2 23.0 20.8 22.2 29.1 23.8 25.4 22.6 25.4 26.8 25.5 26.1 31.5 25.7 27.7 25.2 23.5 26.4 27.2 24.8 26.0 25.2 26.0 23.1 25.7 22.0 28.7 23.4 25.5 22.2 26.2 28.8 27.7 22.7 23.8 23.6 27.5 23.2 29.1 28.4 27 .o 29.7 28.9 28.8 25.5 28 .5 25.1 26.0 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 192l 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 194l 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 31952 10490 6623 9663 11646 5109 5922 230 5743 4821 7975 8305 0 5678 0 6382 27389 7999 12857 11184 0 6154 6323 13871 31009 ll466 26534 14861 6578 23544 28408 13070 31336 5897 10663 7897 2795 0 661 8738 15293 8606 18437 22996 9361 14453 13401 21336 13956 812 1129 0 14630 3066 9481 4805 18477 4043 5887 8326 16947 30920 20235 9360 471 9806 10802 1192 32094 21959 30722 7401 7805 12647 51.64 11587 21326 11433 NOV 9873 0 4606 5189 0 2438 6486 0 7281 0 4550 0 1066 0 0 6692 0 0 436 0 0 1083 1758 0 121 0 3425 0 0 0 0 0 0 0 671 DEC 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Appendix B SNETTISHAM HYDROELECTRIC PROJECT-PRELIMINARY-INPU?, SNETOPR6.IN RUN 6 322000 MWH LOAD ALL SNET GEN USABLE LDNGOPR6 .OUT, CRATOPR6 .OliT ENERGY ASSUMED ';'0 BE USABLE FROM LONG LAKE SPILL (MWHl JAN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FEB 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MAR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 APR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MAY 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUL 8397 0 0 0 14828 0 0 0 14734 0 0 0 1077 0 0 0 31725 11383 1597 0 1988 0 0 0 2303 0 0 31094 0 0 0 0 0 0 0 0 0 0 0 0 12331 0 6932 0 2423 0 1717 ADG 29908 35226 0 4253 15721 0 4415 12177 29979 0 5342 10692 13681 8099 3868 30999 3359 7670 18931 28037 18154 34541 19786 586 0 29318 29453 21392 3281 24599 0 0 0 17979 0 8268 119 12029 26638 17168 11575 34893 13753 22378 0 0 11215 0 28556 8017 16893 14530 0 19006 8342 4224 26810 13915 0 2647 16993 17712 B527 13045 1837 30808 32881 28666 0 18700 0 11418 Page 10 SEP 13805 27429 20399 22660 27539 23531 2300 19768 30122 28230 169El 23704 19474 16945 19507 19079 110 17590 13066 26117 32194 29800 20277 26658 14579 28571 20832 8290 21036 15885 24042 28870 16609 0 5298 21526 0 19905 13093 26122 8309 10739 24865 15761 ~9598 32207 6710 3521 26829 32081 28477 15126 29202 16080 11868 13672 0 30111 13613 20295 0 24502 14713 24525 0 21125 7634 32289 3003 32827 32319 21324 32120 31875 22685 30128 32108 13432 18263 TOTAL 75664 81542 27027 36576 64 779 28640 8222 230 29926 51726 86202 6305 22303 40074 33155 3l426 53203 79297 12967 1:184 20950 26890 51371 82460 78963 66284 77528 30026 35149 105118 77534 57095 47221 34284 66120 24505 9487 5298 68165 20559 28173. 13213 39896 47745 43201 45046 100186 42594 55443 43540 16922 48165 57252 29290 44812 37219 47602 14934 37684 4805 71018 17656 34524 8326 45673 72442 58675 9360 21596 20087 60084 21908 78449 67323 53884 82660 72561 70929 35292 64817 34757 43502 2/25/97 19l4 l915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 19'75 1976 1977 1978 1979 1980 1981 1982 1983 l984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 6529 6699 5470 5608 6169 5448 5055 4835 5550 5905 6539 5075 5346 5726 5551 5493 5962 6434 5252 5073 5801 5487 5869 6615 6513 6279 653l 5546 5655 7094 6431 6000 5922 5685 6235 5400 5308 6405 5289 5740 5154 5571 5875 5661 5762 7132 5771 6074 5607 5258 5928 6148 5536 5803 5601 5760 5247 5736 4858 6474 5291 5655 4892 6017 6394 6206 5042 5519 5310 6389 5155 6662 6351 6122 6507 6603 6305 5672 6395 5595 5809 NOV 4985 5115 4176 4282 4710 4159 3860 3691 4237 4508 4992 3875 4082 4372 4238 4194 4552 4912 4010 3873 4429 4190 4481 5050 4973 4794 4987 4234 4318 5416 4910 4581 4522 4341 4760 4123 3880 3663 4053 4890 4038 4382 3935 4254 4486 4322 4399 5445 4406 4638 4281 4015 4526 4694 4227 4430 4276 4398 4006 4380 3709 4943 4040 4317 3735 4594 4882 4662 3850 4214 4054 4878 3936 5086 4849 4674 4968 5041 4814 4331 4882 4272 4435 DEC 5U1 5244 4282 4390 4829 4265 3957 3785 4345 4623 5119 3973 4186 4483 4346 4300 4668 5037 4112 3971 4542 4296 4595 5179 5099 4916 5113 4342 4427 5554 5034 4698 4637 4451 4881 4227 3978 3756 4156 5014 4140 4494 4035 4362 4600 4432 4511 5583 4518 4755 4390 4117 4641 4813 4334 4543 4385 4509 4108 4491 3803 5068 4143 4427 3830 4710 5006 4781 3948 4320 4157 5002 4036 5215 4972 4793 5094 5169 4936 4441 5006 4380 4548 Appendix B S~~TTISHAM HYDROELECTRIC PROJECT -PRELIMINARY INPUT, SNETOPR6.IN RUN 6 -322000 MWH LOAD -ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6 .OUT GENERATION FROM ANNEX, SALMON, A!ID GOLD CREEK HYDRO (MWHI JAN 4605 4725 3858 3956 4351 3843 3566 3411 3915 4165 4612 3580 3771 4039 3916 3875 4206 4538 3705 3578 4092 3871 4140 4666 4594 4429 4607 3912 3989 5004 4536 4233 4178 4011 4398 3809 3585 3384 3745 4518 3731 4049 3636 3930 4145 3993 4064 5031 4071 4285 3955 3709 4182 4337 3905 4093 3951 4063 3701 4046 3427 4567 3733 3989 3451 4244 4511 4307 3557 3893 3745 4507 3636 4699 4480 4318 4590 4658 4448 4001 4511 394 7 4098 FEB 4272 4384 3580 3670 4037 3565 3308 3164 3632 3864 4279 3322 3499 3748 3633 3595 3902 4210 3437 3320 3796 3591 3841 4329 4262 4109 4274 3629 3701 4643 4208 3927 3876 3721 4080 3534 3326 3139 3474 4192 3461 3756 3373 3646 3845 3705 3771 4667 3777 3975 3670 3441 3880 4024 3623 3798 3666 3769 3434 3754 3179 4237 3463 3701 3202 3937 4185 3996 3300 3612 3475 4181 3374 4360 4156 4006 4258 4321 4126 3712 4185 3661 3802 4878 5005 4087 4190 4609 4071 3 777 3613 4147 4412 4886 3792 3995 4279 4:48 4104 4455 4807 3925 3790 4335 4100 4385 4943 4867 -4692 4880 4144 4225 5301 4805 4484 4425 4248 4659 4035 3797 3584 3966 4786 3952 4289 3851 4.163 4390 4230 4305 5329 4312 4538 4190 3929 4429 4594 4137 4336 4185 4304 3921 4286 3630 4837 3954 4225 3655 4496 4778 4563 3768 4124 3967 4774 3852 4978 4745 4574 4862 4934 4711 4238 4778 4180 4340 APR MAY 5643 6016 5791 6173 4728 5040 4848 5168 5332 5685 4709 5020 4370 4658 4179 4455 4797 5114 5104 5441 5652 6025 4387 4677 4622 4927 4950 5277 4798 5115 4748 5062 5154 5494 5562 5929 4540 4840 4385 4675 5015 5346 4743 5057 5073 5409 5718 6096 5630 6002 5428 5786 5646 6018 4794 5110 4888 5211 6132 6537 5559 5926 5187 5529 5120 5458 4915 5239 5389 5745 4668 4976 4393 4683 4147 4421 4589 4892 5537 5902 4572 4874 4962 5289 4455 4749 4816 5134 5079 5414 4894 5217 4981 5309 6165 6572 4989 5318 5251 5597 4847 5167 4546 4846 5124 5463 5315 5666 4786 5102 5016 5347 4842 5161 4979 5308 4536 4835 4958 5286 4199 4477 5596 5966 4574 4876 4888 5211 4229 4508 5201 5544 5527 5892 5278 5627 4359 4647 4770 5085 4590 4893 5523 5887 4456 4 751 5759 6139 5490 5853 5292 564: 5625 5996 5708 6085 5451 5810 4903 5227 5528 5893 4836 5156 5021 5353 6176 6337 5174 5305 5835 5153 4782 4574 5250 5586 6185 480~ 5058 5417 5251 5196 5640 6086 4969 4799 5488 5191 5552 6257 6161 5940 6178 5246 5349 6711 6083 5676 5603 5378 5898 5108 4807 4538 5022 6059 5003 5430 4876 5270 5558 5355 5450 6747 5459 5746 5304 4974 5608 5816 5237 5489 5298 5448 4964 5426 4596 6124 5006 5349 4628 5691 6049 5776 4770 5220 5023 6044 4877 6302 6008 5791 6155 6246 5965 5366 6049 5292 5495 JUL 6648 6822 5570 5711 6282 5548 5148 4924 5652 6013 6659 5169 5445 5831 5653 5594 6072 6552 5349 5166 5908 5588 5977 6736 6633 6394 6651 5647 5759 7224 6549 6111 6031 5790 6349 5499 5175 4885 5406 6523 5386 5845 5249 5674 5983 5765 5867 7263 5877 6185 5710 5355 6037 6261 5638 5909 5704 5865 5343 5841 494 7 6593 5389 5758 4982 6127 6512 6218 5135 5620 5407 6506 5250 6784 6468 6234 6626 6724 6421 5776 6512 5697 5916 AUG 5896 6050 4940 5065 5571 4920 4565 4367 50l2 5333 5905 4584 4829 5172 5014 4961 5385 5811 4744 4582 5239 4956 5301 5974 5882 5671 5899 5009 5107 6407 5808 5419 5349 5135 5631 4877 4589 4333 4 794 5785 4777 5184 4655 5032 5306 5113 5204 6441 5212 5486 5064 4749 5354 5553 5000 5241 5059 5202 4739 5181 4388 5847 4779 5107 4418 5434 5775 5515 4554 4984 4795 5770 4656 6017 5736 5529 5877 5963 5695 5123 5775 5053 5246 MINIMU!-1 ANNUAL AELP HYDRO GENERATION 48895. 2ND MIN ANNUAL AELP HYDRO GEN 49280. Page 11 SEP TOTAL 578J 66543 5934 68279 4845 55751 4968 57159 5464 62876 4826 55527 4478 51524 4283 49280 4916 56568 5231 60185 5792 66646 4496 51732 4736 54495 5073 58366 4917 56580 4866 55986 5281 60770 5699 65577 4653 53535 4494 51707 5139 59129 4861 55931 5199 59823 5860 67422 5769 66385 5562 64000 5785 66569 4912 56525 5009 57638 6284 72307 5696 65545 5315 61161 5246 60366 5036 57950 5523 63548 4783 55038 4501 51793 4249 48895 4702 54107 5674 65286 4685 53906 5085 58505 4566 52533 4935 56788 5205 59886 5015 57703 5104 58727 6318 72693 5112 58821 5381 61910 4967 57153 4658 53598 5251 60422 5446 62666 4904 56430 5140 59146 4962 57090 5102 58706 4648 53481 5081 58466 4303 49516 5735 65987 4687 53934 5009 57634 4334 49864 5330 61324 5664 65175 5409 62240 4467 51395 4889 56250 4703 54l19 5659 65119 4567 52545 5901 67903 5626 64734 5423 62398 5764 66321 5849 67301 5586 64269 5025 57814 5665 65178 4956 57025 5146 59210 2/25/97 YEAR 19:4 l91S 1916 19l7 1918 1919 1920 1921 1922 1923 192~ 1925 1926 1927 192.8 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 19.;3 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 :954 1955 l956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1965 1986 1987 :988 "1989 1990 1991 1992 1993 l994 1995 AVG OCT 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NOV 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 DEC 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Appendix B SNETTISHA-'1 HYDROELECTRIC PROJECT PRELIMINARY INPUT: SNETOPR6. IN RUN 6 322000 MWH LOAD ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6.0UT JA.'I REQUIRED GENERATION FROM THERMAL UNITS (MWHI 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FEB 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 APR 0 0 0 0 0 0 0 0 0 0 0 0 0 MAY 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUL 0 0 0 0 0 c 0 0 0 0 0 0 0 0 0 0 0 0 0 AUG 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MAXIM\JM ANN'JAL THERMAL GENERATION 0. SEP Page 12 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TO'::AL 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ·- 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 45240 23937 21988 24249 26034 20361 21184 15483 20259 19280 22630 23717 14611 19980 14237 21184 40928 22066 27433 26644 15016 21131 20630 27436 45240 26326 40316 29665 21133 37670 42216 26818 45240 21118 25017 23492 19103 15220 14867 42300 35303 15154 14324 15217 23566 29584 22767 32124 36981 23753 29691 27518 35793 28199 16196 16312 13917 29640 17871 24587 19294 32371 19465 20659 23620 31187 44680 34340 24868 15367 24802 24362 16744 45240 37058 45240 21451 22484 27722 20068 26542 36893 26029 NOV 15493 15218 15731 15664 25495 15831 15973 16710 15922 20401 20338 16173 16253 15739 15676 15924 19005 21785 15832 16765 16687 15989 15649 22673 15248 15387 20905 15774 15785 15086 15361 15605 15429 17529 15653 15898 23436 16665 16369 17458 1.5766 16937 15976 17054 17606 15693 15728 15092 15617 15964 15652 15954 15692 15281 15872 15582 15804 15582 15928 16164 16105 19359 15724 15932 16024 15621 15359 15517 16069 16335 15785 15179 15773 15092 15478 15575 15503 15062 15263 15778 15487 15753 16478 DEC 18539 18274 18986 18536 18371 18822 18912 19689 19283 18517 18166 19241 19138 18997 18488 19181 18482 18300 18721 19771 19932 19164 18349 18272 18361 18470 18509 18889 19049 18224 17812 18645 18002 19308 18473 19059 19852 19472 19445 18824 18665 20123 18827 18659 18630 18250 18629 16960 18428 18876 18762 19183 18621 18118 18931 18547 18973 18458 18868 19079 18898 18312 18740 19041 18738 18827 18019 18523 18897 19239 18576 18189 17536 17850 18357 18539 16970 17972 18269 18776 18437 18926 18680 Appendix B SNETTISHAM HYDROELECTRIC PROJECT-PRELIMINARY-INPUT, SNETOPR6.IN RUN 6 -322000 MWH LOAD-ALL SNET GEN USABLE -LONGOPR6.0UT, CRATOPR6.0UT TOTAL NET ENERGY FROM BOTH LONG LAKE UNITS (MWH) JAN 18659 18460 19011 18586 18508 19076 18857 19582 19414 18613 18308 19333 19344 19124 18542 19349 18545 18457 18727 19775 19987 19249 18453 18406 18532 18699 18606 18944 19129 18321 18296 18682 17998 19407 18678 19095 19889 19366 19402 18966 18663 20202 18746 18785 18876 18314 18690 17849 18611 19044 18834 19350 18607 18215 18985 18554 19052 18541 18851 19095 18908 18416 18641 19161 18756 18898 18188 18872 18970 19264 18753 18255 17854 18136 18491 18619 18162 18069 18486 18834 18602 19047 18800 FEB 16806 16701 17148 16878 16717 17302 17083 17639 17530 16786 16548 17540 17864 17292 16964 17517 16804 16907 16874 17721 17847 17352 16708 16693 15223 16863 16893 17072 17317 16845 16697 16855 16141 17510 16898 17247 17891 17052 17366 17240 17445 18371 16817 17022 17157 16498 16868 16312 16781 17582 17195 17644 16652 16457 17336 16663 17265 16801 16992 17289 17095 16653 16915 17375 16855 16912 16443 17191 17160 17286 17126 16677 16034 16436 16911 16824 16299 16763 16828 17650 16860 17202 17012 MAR 15992 16002 16266 15980 15813 16554 16266 16827 16626 16110 15782 16679 17246 16460 16278 16738 16042 16117 16084 16660 16895 16500 15924 15864 14793 16028 16066 16178 16520 16072 15956 16075 15426 16562 16072 16449 16988 16346 16228 16401 16666 17593 15852 16256 16352 15715 16108 15597 16125 16892 16402 17010 15716 15496 16844 15779 16557 15954 16409 16402 16416 15906 16061 16533 16194 16180 15568 16416 16284 16242 16287 16193 15674 15798 16214 16081 15761 15855 16227 17048 16094 16520 16233 APR 12465 12682 12897 12471 12378 13138 12771 13460 11226 12861 11350 12794 13494 13253 13364 13256 12787 12692 12754 14468 13245 13156 12478 12588 11751 12586 13005 12984 12857 11403 12808 12563 12025 13502 12564 11175 13404 7316 12404 12724 12957 13776 12352 11937 13116 12399 12880 12341 12644 13386 10179 13375 12377 11694 13299 12241 13165 11298 12740 13276 13122 12479 13055 13593 13029 12398 12526 12808 13050 12784 13280 12656 12618 12665 12523 12790 12235 11998 12571 13557 12782 12837 12633 MAY 11144 11363 11660 11349 11023 11779 11851 12635 10289 11603 10355 11866 12101 12066 12330 12133 11587 11275 12140 12168 12709 12147 11666 11207 10448 11432 11521 11935 11793 10448 11362 11582 11622 12230 11585 10880 12307 10579 12255 11690 12234 12389 11786 10882 11887 11160 11705 10783 11724 11856 9225 11916 11238 11016 12072 11466 11383 10742 11928 11334 11536 10936 12142 12401 12394 11609 11474 11399 12168 11124 12507 11603 11380 10810 11111 11435 10834 11301 11312 11644 11743 11829 11555 JUN 9795 9529 10343 10014 9535 10189 10874 10881 9417 9989 9059 10514 10452 10440 10327 10271 9946 9648 10787 10783 10936 10553 9722 9739 9084 9834 9722 10377 10503 8832 9525 9905 9979 10245 9977 10088 10305 10663 10817 10090 10748 10344 10513 9730 10345 9871 9943 9296 10085 9976 8928 10332 9986 10303 10230 10169 9879 9366 10644 10070 10920 9407 10681 10420 10577 9955 9601 9756 10635 10301 10795 9838 10020 9283 9444 9510 9258 9782 9546 10204 9802 10079 10052 JUL 10568 18509 11050 10830 10331 10791 11459 11430 10411 10531 24328 11653 11153 11159 10845 10850 10550 24775 13117 11870 11965 11541 10574 11286 9742 10674 10432 11876 11322 41197 21930 12405 11394 11569 12907 12323 10964 12017 11918 11233 11855 11335 11837 10853 13890 10971 10879 40526 10878 10919 10275 11669 11279 11269 11266 11158 10431 11078 11786 11117 12272 10123 11675 11308 11333 10899 10637 10966 12429 11357 11179 10446 11491 10150 10089 10773 22511 10639 17054 11470 13752 10217 12726 AUG 40462 45240 11658 15765 26352 11322 11969 12025 15673 23023 39997 12206 16749 22348 24901 19322 15010 41235 13011 12646 15576 19701 29923 38129 28549 44315 30490 12757 11865 39881 39921 32354 12003 15207 35462 12661 11567 12266 12313 29168 12114 20114 12373 23299 38005 28421 22840 45240 11404 25040 33160 12264 11710 22842 11615 39384 19034 28295 12457 26184 12678 29705 12297 20245 11746 15654 37492 25218 12392 11986 14419 27916 29375 23914 23789 13137 41145 43376 39068 11706 30064 10692 22791 MINIMUM ANNUAL LONG LAKE GENERATION 170231. 2ND MIN ANNUAL LONG LAKE GEN 179060. Page 13 SEP TOTAL 26073 241237 39491 245406 32439 199177 34606 204928 39010 229567 35270 200435 15205 182404 12700 179060 31436 197487 41393 219107 39629 246489 12768 184485 29044 197449 35816 212675 31494 203445 28863 204589 31147 220832 31205 244460 13743 189223 13348 192618 30275 201071 25406 201889 37798 217874 43781 246073 41017 237988 32550 233164 38245 244713 27052 203502 40582 207856 32359 266338 20186 242070 32784 224275 28462 213721 36054 210240 40463 233749 30151 198516 13066 188772 13269 170231 18416 181800 33217 239310 13244 195660 32006 208344 25752 185155 37885 207578 20659 220090 22647 209524 36457 213495 27600 259719 31569 210846 43781 227070 19139 207442 16562 192776 38732 216402 43781 222671 40344 202991 27581 213436 40723 206181 27967 213721 25064 189538 25912 210506 13130 180375 41390 235055 26330 191728 32510 209179 13004 182268 36296 214437 26594 236581 36120 227125 13057 185977 33603 194886 20089 193598 43781 225095 15639 190139 43781 239155 43781 233246 32945 221468 43781 243910 43781 237081 34506 236853 42132 208866 43781 233946 25867 205862 30404 213393 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 ~968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 260.2 312. 3 185.4 270.0 250.5 201.7 209.8 140.0 238.0 201.7 220.0 260.7 160 1 257.4 135.0 193.5 463.5 224.4 333.4 315.5 189.0 276.1 186.3 498,4 393.8 216 '2 300.7 332.6 220.5 239.1 291.5 313.6 350.0 150.9 271.0 160.5 193. 5. 155.6 187.3 260.1 298,0 179 '2 180.4 171.4 231.1 213.7 236.6 308,1 353.7 219.2 326.9 342 '3 259.6 396.3 235.9 163.4 209.7 279.5 174.3 218.8 332.2 385.4 234 '1 185.3 194.9 350.6 363.4 233.6 169.7 202.5 289.1 287.4 268 '4 320.6 184 '5 394.2 238.5 263.0 222.5 169.6 192.6 20a.3 252.5 NOV 108.1 104.0 44.9 51.3 250.4 132.9 67.1 91.8 76.5 158.0 283.1 96.9 154' 8 115.7 44.7 112.9 221.8 255.4 72.8 42.2 209 '8 90' 7 57,1 259 3 77.4 84' 8 193.9 8l.a 107.7 111.5 159.8 111.1 40.7 147.9 97.9 109.8 324.4 32.6 40.1 146.4 64.6 147.2 48.9 117.5 166 '6 94.5 82.5 101 '2 74.3 130.6 45.1 88.1 81.5 127.1 119,9 65.0 120.8 137.4 44.3 a7 .0 54.2 194.6 3a. 9 75.0 47 '7 95' 3 89 4 112' 4 95.5 48 '2 57.8 40.6 34.3 157.5 130 8 92.2 80.7 30.7 72.2 50' 0 126' 9 133.4 107.0 DEC 38.2 23.9 33.0 32.7 35,0 65,4 45.0 24.7 46.5 40.7 106.9 16.4 131.0 63.0 25.0 82 '0 60 '2 146 '0 27,6 26.5 20 '2 58.6 155.1 89.5 52.7 73.5 45.6 31.5 33 '0 44.4 209.6 24 .c 28.5 24.3 139.5 22.2 21.7 28 '4 16.9 23.6 48.4 141.7 24.8 224.1 24.9 127.0 94.5 385.2 2l.a 76.0 55.7 29' 6 34.7 18.9 24.7 21.3 66.4 25.6 22.1 17.1 16.2 89.4 26 '8 69' 2 17.0 42.0 138.0 34.4 21.5 15.5 16.0 22.0 404.5 116.9 59.;1. 45.8 503.5 25.9 43.1 38. a 100. 36.3 68.0 Appendix B SNE'ITIS!IAM HYDROELECTRIC PROJECT-PRELIMINARY INPUT, SNETQPR6.IN R~ 6 -322000 MWH LOAD · ALL SNET GEN USABLE LONGQPR6.0UT, CRATO?R6.0UT JAN 2l.C 36 .1 18,1 35' 0 33.2 68.5 100.0 4::..4 26.1 20.0 3l. 1 26.9 95 '7 36 '2 88.6 76.0 4.9 68.1 20.0 12.7 34.1 4.6 21 '5 34 '3 40.4 55' 2 31.0 8. 3 43.6 57' 5 102. a 49.5 32.1 31.3 45.9 3a '6 9 '7 10.9 11.9 1a. 3 30.4 41.9 17.9 50.5 65.1 27.5 41.7 37.2 68.9 56.7 52.9 87.2 28.7 13.2 23.2 10.2 23.0 44.5 39.6 45.0 31.1 30.7 72.9 40.9 35, a 18 7 18.2 54.3 26.6 44.1 66' 2 78 '2 73 '4 61.3 27.0 75.2 34.4 22.9 55.8 51.9 4C.3 30 3 40 '7 INFLOW TO CRATER LAKE ICFS) FEB 45' c 17.2 1a.7 44.5 16.8 14,6 36.2 45 'c 10. a 46 '2 25.3 11.9 24.1 14.5 31.9 19.1 9.0 ~01. 9 20.'.1 20' 5 61.9 12.4 9,9 12.2 347 '7 39,5 15.2 9,3 22.8 37.9 33 '9 67.0 57.7 17 '7 28 '3 4,3 32.7 70,6 13,4 13.4 47.3 13.1 14.2 16,6 16 '6 36.8 27,0 35 '4 36.1 42,2 21.7 31.0 32.6 15 '7 37.6 10.9 29.7 13.9 24 ,l 28.9 16.3 16.6 26.9 12.3 36.4 3a.9 14.9 32 '3 31.2 17.5 33.3 94.6 142.3 59.7 59.7 32.1 70.9 54.5 155 '2 73 '6 17.9 26.8 37.5 36' 8 44.6 19. 22 '4 12.7 12.0 16' 0 22.6 10.2 38.9 34.3 11 '9 29.1 16.4 40,C 49.3 14 '7 22 '3 15.0 18.6 13.4 13.7 21.7 21.0 64.8 Q8, 8 8. 2 16 1 15.0 45.1 31.3 19.5 34.0 45.4 9.4 17.7 22.5 33.5 18 '4 13.0 15.2 16 .a 18 '2 10.9 17.6 19.4 22.9 31. 19' 32.3 22' 7 37.8 31.7 24.5 69.7 19.a 35.8 12.4 34.2 21.5 30.8 36.2 15.1 18.0 34.3 20.9 22.0 24.9 40.6 9' 8 21.6 36.1 58' 7 27 '5 39.4 16.0 24.8 20.3 7:1.8 32.7 33' 62. 26' 7 APR 52.8 73.9 44.0 23' 9 20. 47. 20. 27.5 292.5 62.6 243. 36, 51. 30.1 42 '4 29' 2 34. 45.4 32,9 47.1 40.2 31.0 71,0 29.4 35.6 47.4 22.3 41.1 28.6 221.0 39.6 50.2 46.0 45.8 10.9 293.6 27,9 467.5 70.7 37.8 30.0 31.5 25,4 197 '3 31.9 34.6 40.0 57.0 30.4 32.4 514.2 59.5 47,5 47.4 45.0 55.3 44.6 296 '9 35 '3 47,6 20.5 44.9 3a.4 33.7 31.9 46.0 46.8 66.1 32.9 30.3 34.0 82.7 55.6 46.4 102' 6 35.1 119.1 169.3 126.8 a2.5 77.8 117.6 73,9 MAY 143.9 234.2 89.9 142.0 129.0 118.1 53.3 125.2 230.6 172.5 286.7 66.8 177,4 92. 8 193 '5 91.9 104.1 211.4 105.1 2a6. 0 83. 3 124.3 232.4 13a '0 280 '4 167.1 121.2 123 '8 110' 1 231.0 269.5 186.3 149.6 168.7 170.a 160,3 5a.a 219.9 186.5 210.3 72.9 79.9 212.8 227.0 214.2 209.5 189.2 248.3 82.1 152.4 215' 3 93.7 169.4 144.4 156.2 207.0 258.4 219 .a 132.0 252.5 145.0 214.3 115.6 121.2 126.5 201.8 144.6 177.6 162.9 156.6 11a '1 157.0 158.7 297.3 212.1 300' 5 222.9 103.5 219.0 266.7 178.8 211.9 170.7 JUN 272.3 413,4 369,7 304.2 346.2 216.8 176.5 304.2 299.5 297' 5 400.0 316.0 367.1 349.6 381.5 381.5 307.5 401.7 2a4.0 249,2 31a. 7 213.0 429' 3 482.6 334.5 276.3 320.9 351.1 261.8 410.2 376.3 43a. 3 384.3 433.6 420.7 213.1 332.8 400.2 297.5 351.9 284.7 297.9 227.5 307.9 393' 6 405.3 326.5 382.7 356.0 327.9 455 '0 293, a 329.7 395.5 291.6 500.8 348.3 355.8 243 '7 289.4 231.4 306 '5 234.5 328.7 362 '2 298.7 380.2 259 .s 366.1 425.0 380 '0 222.0 367.0 316.1 330.4 379.0 357' 1 367' 6 388. 296.4 394 '7 296.1 336.4 J'JL 517.2 497.7 370. a 440,7 4al. 4 416.3 406.6 398.5 396. 452 .1 5a3.9 288.9 325.1 377 3 528.6 419.6 419.6 416.3 36.3 234.9 218.9 426.8 42a.5 412.6 401.6 431.5 3a6' 361,4 338..1 406.6 139.3 437.3 225.9 201.5 314 1 28.1 3a5.2 197.9 356.9 20a.4 242.2 356,0 330.5 238, 181.4 443.0 403.4 440.2 372.1 304.8 443.6 225.9 259.2 247.0 296 '9 419.7 408.6 205.6 254.7 309.7 269.9 443.6 365.9 344.1 319.8 443.1 443.0 253.2 62.2 300.0 395 4 443.4 153.0 295' 390.8 190 '8 345.2 392 .l 454.8 110 6 6a. 3 396.5 336.3 AUG 408.2 468.4 463.5 538.3 590.4 510 7 531.8 359.4 401.5 483.0 566.0 425.0 361. 357 377.3 403.3 484.7 473.3 365.9 321 '5 509.8 436.8 339.3 486.6 305,2 872.6 488.7 312.7 401,0 313.5 431.3 334.4 361.1 347.7 398.2 366,6 36a.8 305.0 388.4 47a .5 294.6 429.5 569.2 333.2 390.5 362.9 423.0 573.9 378.8 298.9 366.8 326.2 462.7 428.6 336.0 535.2 428.9 373.1 355.0 543.4 364.0 325.2 367.7 362.3 334.5 301.1 399.7 490.0 354.5 474.4 432,6 426.1 361.9 361.4 327.2 306.1 379.4 468.8 371.6 382.0 337.5 315.8 409.7 Page 14 SEF 265 '5 388.2 470.6 361.3 411.7 420.1 262.2 391 '6 411.1 502.5 581.5 399.4 292.2 351.2 342.a 346' 2 359.6 361.3 428.5 2a9.9 315.9 403.4 447.4 398.7 439.4 441.7 330.2 387.0 404 -~ 413.8 393.4 444.4 315.6 458,0 458 '3 170.5 242.5 282.5 451.5 428 '7 326.6 429.8 357.0 398.3 369. 389, 435.0 416.3 447.7 370.0 243.5 266.1 427.4 456.7 456.1 344,5 431.4 426.5 404. 8 368.4 424.7 436.3 440.8 403.4 3:8.5 368.8 3a8.5 462.1 391 '3 422.3 253.0 444.0 192.0 441,7 299.1 416.5 443.1 462.1 46l.7 335.1 461.5 102.6 382.9 AVG laO. 8 217.8 177.3 188. 214. 1a5. 160 4 164' 3 203.3 206.3 280,1 163 .1 180.8 l71.8 165.9 183,7 207.0 227.3 145.2 155.4 167.9 174.3 200.0 23a. 6 231.1 227.9 1a8. 171.4 165.5 211. 206. 206.3 168.8 172.7 197.1 132.1 16a '4 183.7 170.0 182.5 146.2 180.4 16a. 9 191.1 175.2 197 '0 193.5 251 4 186.6 170.3 230 156.8 180 .4 192.9 174.4 196 '1 200.5 199 147.0 18S.a 161.3 210,3 164' 8 166.2 155.0 185.5 204.1 183.4 146.2 na.s 174. i 194.7 189.1 20a.5 180.2 190.3 235.0 198 '4 22~.2 157' 5 169.1 161 1B6. 9 -- 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 ~987 1988 19a9 1990 1991 1992 1993 1.994 1995 AVG OCT 260.2 312.3 la5.4 27C. C 2SC .5 201.7 209.a 142.9 140 5 201.7 220.0 260.7 1.45 .2 257 .4 146.6 193.5 463.5 224.4 333.4 131. 3 132. 9 142.6 186.3 49a.4 393. 216. 300.7 332.6 17S.a 239.1 291.5 313.6 350.0 132.7 271.0 160.5 129.2 145.8 143.1 115.6 298.0 129.9 180.4 145.9 231.1 213.7 236.6 30a. 1 353.7 219.2 326.9 342.3 124.4 396.3 235.9 163.4 209.7 279.5 174.3 130.4 332.2 127 ~8 234.1 139.4 194.9 130.6 363.4 233.6 169.7 137 230.1 284.0 268.4 320.6 184.5 3 94.2 238.5 263.0 222.5 169. 6 192.6 208.3 231.2 NOV 159.3 162.6 170.1 169.9 250.4 168.5 171.7 162.7 165.8 161.3 283.1 167.8 163.6 166. 170.0 166.0 221.8 255.4 172.6 158.8 152.0 164.8 165.7 259.3 165.7 164.8 193.9 169.3 166.1 158.6 163.6 165.5 170.6 156.2 160.6 167.7 157.3 165.9 163. a 155.7 173.0 146.2 17C.O 162.7 166. 6 168.1 166.1 158.5 169.2 162.8 170.7 170.2 165.0 170.7 166.6 167.9 166.8 169.3 169.5 159.7 173.2 176.3 173.3 163.7 173.1 164.3 165.0 165.0 169.8 160.3 171.7 167.8 174.7 165.8 161.7 165.2 159.2 166.7 166.9 166.0 160. 9 167.9 171.4 DEC 185.8 188.5 194.9 201.4 194.1 196.4 202.2 192.5 188.2 194.6 192.7 194.7 193.9 189.1 203.6 189.2 194. B 191.5 202.8 189.4 174.4 190.4 200.8 189.3 190.3 191.6 185.5 194.8 189.4 183.3 205.9 191.9 207.3 1a5. 8 191.8 193.0 184 .1 201.8 193.8 183.1 203.5 171.3 202.7 19a. 0 192.9 205.1 196.4 329.8 200.5 185.8 197.2 193.3 195. 7 199.6 193.2 197.8 191.4 198.6 200.6 190.6 205.8 190.0 202.6 190.9 208.6 189.1 198.5 192.6 202 .o 192.2 205.1 196.4 268.6 196.2 191.6 192.5 427.5 197.6 195.4 195.7 189.4 -:92.l 199.7 Appendix B Page 15 SNETTISHA.!!! HYDROELECTRIC PROJECT • PRELIMINARY INPUT, SNETOPR6. IN RUN 6 322000 MWH LOAD • ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6.0UT TOTAL OUTFLOW FROM CRATER LAKE TUNNEL + SPILL I CFS) JAN 197' 3 199.3 206.8 213.3 204.6 203 .6 215.1 207.4 197.4 206.1 201.6 205.1 200.1 198.9 216.0 197 .4 206.1 199.2 215.2 202.9 187.4 200.6 209.6 199.0 200. 5 199.9 197.1 206.3 200.5 19S.a 201.4 204.6 221.4 196.6 199.2 204.9 195.0 217.9 209.2 193.9 215.7 180.2 216.9 204.2 201.6 215.2 207.1 201.7 210.2 194.9 207.9 202.2 209.3 211.9 205.0 211.0 201.9 210.5 213.7 204.5 218.2 200.7 217.4 200.4 221.1 200.6 207.1 199 .2 213.0 206.5 214.8 209.4 227.9 203 3 202.4 204.1 205.6 210.3 204.7 207.1 198.7 202.5 205.3 FEB 213.3 213.5 224.4 228.2 219.1 215. 6 228.8 225.1 2l3 .8 22:1.9 215.2 219.9 204.4 213.0 226.4 209.5 220.4 207.4 233.8 224.0 207.8 217.8 224.0 211.1 249.2 214.6 209.1 224.2 214.6 202.6 210.1 220.1 :;:41.5 213.0 212.1 220.7 213.5 247.9 231.5 207.1 219.6 192.1 237.5 217.2 212.7 231.7 222.3 210.2 226.3 199.6 219.6 212.7 229.6 228.4 216 .a 230.7 215.8 224.6 231.4 219.5 235.5 214 ~1. 231.7 214.3 240.7 220.2 221.7 210.3 229.5 225.8 226.6 220 .1 244.3 215.4 212.4 218.0 219.5 217.0 216.8 208. 211.0 217.8 220.0 MAR 196.2 194.4 211.4 214.2 2C5 .1 200 .c 214. c 211.3 201. 6 202.7 197.5 207.3 186.5 198.6 208.4 194.6 204.0 187.7 218.8 216.2 195.4 204.3 208.0 195.1 213.8 198.5 193 .3 211.4 199.3 184.2 190.7 202.3 222.2 201.4 196.3 206.2 201.7 230.6 225.1 191.9 203.9 177.8 226.7 200.5 197.5 215.0 205.6 189.1 207.1 181.7 204.3 194.6 216. 3 215.4 194.9 217.1 198.6 210.0 212.1 206.2 219.2 196.5 217.8 200.3 223.1 202.3 206.5 193.6 216.4 216.7 212.3 194.7 215.2 193.6 192.9 200.3 194.7 201.5 192.6 188 .1 194.1 200.0 203.5 APR 170.5 163. 3 186.3 192.2 179.9 175.8 193.7 187.4 221.2 173.1 191.6 H4.9 168.2 168.9 172.2 170.3 175.1 160.9 194.3 164.3 174.0 17a .3 183.8 164.3 179.5 172.1 158.1 182 .4 179.7 180.7 15a.o 17a. 7 197.2 167.2 172.0 223.5 181.5 341.8 212.1 169.9 186.5 159.1 206.8 195.6 168.0 189.2 176.7 156.6 183 6 155.9 241.6 174.4 189.3 198.7 170.9 195.4 172.6 213.2 193.8 174.0 194.2 169 .1 185.9 164.6 195.4 184.4 172.0 170.9 189.4 193.5 179.7 169.4 184.9 159.7 171.0 171.5 170.1 183.5 169.1 163.2 164.2 179.6 182.3 MAY 142. 133.9 157.1 161.1 153.4 149.7 159.3 150.1 17a .a 143.9 152.3 159.9 143. 1 138.9 l38.5 l39. 7 145.1 135.3 151.8 159.4 128.3 144.5 144.7 137.8 151.8 140.6 133.8 149.0 147.3 140.4 133.2 143. 7 148.9 138.3 137.8 167.9 150.2 196.9 156.3 135.3 146.8 133 .2 163.9 159.9 138.9 160.6 146.2 132.7 147.7 133.2 192.9 150.4 157. 3 156.6 141.9 155.2 155.4 162.8 155.9 159.7 174.3 145.9 149.9 134.5 153.8 144.9 138.0 144.6 153.4 174.9 140.7 134.6 157.1 142.8 ~43. 7 144.6 142.5 138.1 138.4 147.8 129.6 144.2 148.7 JUN 109.4 109.8 125.1 128.4 124.6 124.0 121.0 127.1 136.3 117.1 117.9 129.8 117.5 113.5 119.2 120.2 119.9 108.7 119.8 123.0 104.8 117.6 123.6 107.9 118.7 113.1 111.2 121.3 114.2 112.9 110.1 117.7 122.2 119.0 110.5 125.0 134.7 130.6 122.5 106.1 118.7 116.9 127.5 124.4 109.4 126.2 122.2 102.0 122.8 112.5 141.0 125.2 121.6 109.2 120.4 119.6 125~0 131.2 122.1 122.7 125.8 116.4 120.2 116.0 132.4 117.6 116.7 118.2 124.9 129.0 116.4 llO. 7 127.4 112.2 117.5 121.7 115. c 109.4 114.4 115.6 109.3 120.0 119.3 JUL 1C2 1C2. 118.5 120.6 115.8 122.9 121.9 4..26.1 124.8 115.3 450.0 115.3 112.1 107.5 116.8 116.6 116.4 227.1 80. 0 111.3 92.6 108.4 113.0 104.0 156.5 lOS. 0 104 .a ga .4 107.7 213.3 94.6 105.5 99.9 98.7 97.9 89.8 130.1 110.5 108.3 90.6 105.8 105.8 110.7 111.1 91.6 110 .a 111.6 250.5 114.5 102.0 255.3 107.4 102.9 96.7 108.8 104.8 122.1 104.4 1J9 .1 110.3 108.5 110.2 110.6 106.8 125 .s 107.1 102.5 102.8 96.3 112.6 117.3 108.3 106.7 102.8 112.5 103.5 135.1 99.1 190.5 99.5 85.1 126.8 120.2 AUG 183.6 459.7 116.7 114.9 286.3 121.8 120.3 122.3 128.4 250.2 566.0 115.3 124.7 105.1 189.3 177.7 114.4 473.3 99. 0 107.6 1Cl.l 1C5. 5 210.6 409.3 305.2 595.0 163.3 103.8 108.5 3l3.5 338.2 198.1 101.9 104.9 172.6 99.3 126.9 117.8 110.9 99.9 113.5 104.2 113 1 158.6 97.7 155 8 115.8 573.9 115.2 103.2 366.a 108.1 108.1 99.9 SEP 265.5 388 2 244.2 270.4 41:1..7 364 .l 125.3 137.0 411.1 502.5 581.5 131.1 292.2 218.1 342.8 346. 2 320. 361. 114.7 122.3 110.2 182.8 447.4 398.7 439.4 441.7 330.2 119.9 151.0 413.8 393.4 444.4 110.5 208.1 458.3 99.3 124.5 126.7 119.8 325.4 119.9 219.6 123.4 398.3 307.1 389.2 435. 416. 201. 303.8 243.5 119.7 150.5 242.7 114.1 234.6 262.6 344.5 231.4 431.4 105.0 392.3 107.7 114.5 105.1 237.5 111.6 130.8 181.3 436.3 108.3 121 2 103.5 192.0 127.3 130.4 106.4 220.6 187.0. 389.5 104.9 379.9 112.7 127.6 111.9 115.0 114.4 126.9 108.5 444.0 113.4 192.0 260.3 441.7 184.4 299.1 107.7 272.1 379.4 443.1 144.6 462.1 371.6 461.7 110.4 125.0 95.6 307.5 l28.0 116.3 176.8 277.5 AVG 182.1 219.0 178.4 190.4 216. 3 197 173 166.0 192.3 207.5 280.8 175.2 17C. 9 173.0 187.5 185.1 208.5 227.7 178.0 159. 146.7 163.1. 201.5 239.5 230.4 229.4 190.1 176.1 162.8 2l1. 5 207.6 207.2 182.8 160.1 198.3 163.2 160.7 186.2 166.4 164.5 175.4 153.0 173.3 189.7 176.3 198.4 195.1 252.5 187.7 171.2 230.6 175.1 164.2 193.8 175.3 197.5 201.8 200.1 167.0 168.3 185.8 188.7 172.8 160.5 177.2 165.7 205.6 184.6 167.1 164 6 . 171. 195.7 190.0 209.5 18L1 191.3 235.9 199.4 220.4 158.1 169 .s 167.0 1a8 .0 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 H64 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 260.2 312.3 185 '4 270.0 250.5 201.7 209' 8 142.9 140.5 201.7 220.0 260,7 145.2 257 A 146 '6 193' 5 463.5 224 '4 333.4 131.3 132.9 142.6 186.3 498.4 393.8 216.2 300.7 332.6 175.8 239 '1 291.5 313.6 350,0 132 '7 271 0 160.5 129' 2 145.8 143' 1 115 '6 298.0 129.9 180 4 145.9 231. 1 213.7 236.6 308.1 353 '7 219.2 326 '9 342.3 124.4 396.3 235.9 163 .4 209.7 279.5 174..3 130 '4 332.2 121. a 234.1 139 4 194,9 130 '6 363 .4 233.6 169. 137.1 230.1 284.0 268.4 320.6 184 '5 394.2 23a.s 263 '0 222.5 169 6 192.6 208.3 231.2 NOV 159.3 ~62 .6 170. 169.9 250 '4 168' 5 171.7 162.7 165.8 161.3 283 '1 167. a 163.6 166.5 170.0 166.0 221.8 255.4 172.6 158.8 152.0 164.8 165 '7 259.3 165.7 164.8 193.9 169.3 166.1 158.6 163.6 165.5 170.6 156.2 160' 6 167.7 157.3 165.9 163.8 7 .0 146.2 170.0 162.7 166.6 16a.1 166.1 158.5 169.2 162.8 170.7 170.2 165.0 170 '7 166.6 167.9 166.8 169.3 169.5 159.7 173.2 176.3 1.73.3 163.7 173.1 164.3 165.0 165.0 169.8 160 .J 171.7 167.8 174.7 165' 8 161.. 7 165.2 159.2 166 '7 166' 166 160.9 ~67 .9 171.4 DEC 185.8 188.5 134.9 201.4 194.1 196.4 202.2 192 5 188.2 194.6 192.7 194' 7 193' 9 189.1 203' 6 189.2 194' 8 19:.5 202.8 189.4 :l74 .4 190,4 200' 8 189.3 190.3 191.6 185' 5 194.8 189.4 183.3 205.9 191.9 207.3 185' 191.8 193.0 184.1 201.8 193.8 183.1 203.5 171.3 202.7 198.0 192.9 205.1 196.4 329.8 200.5 185.8 197.2 193.3 195.7 199.6 193 '2 197.8 191.4 198.6 200.6 190' 6 205.8 190 '0 202.6 190.9 208.6 189 '1 198.5 192.6 202.0 192.2 205 196.4 268 '6 196.2 191.6 192.5 427.5 197.6 195,4 195 '7 189 192.1 199' 7 Appendix B SNETTISHAM HYDROELECTRIC PROJECT PRELIMIN~~y INPt~, SNETOPR6.IN RUN 6 -322000 MWH LOAD-ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6.0t~ JAN 197.3 199 '3 206.8 213.3 204.6 203 '6 215' 1 207' 4 197.4 206.1 201. 205.1 200.1 198.9 216. 197 '4 206' 199 < 215' 2 202.9 187.4 200.6 209.6 199.0 200' 5 199' 9 197.1 206.3 203,5 195.8 201.4 204.6 221.4 196.6 199.2 204.9 195.0 217.9 209.2 193.9 215.7 180.2 216 '9 204.2 201.6 215.2 207.1 201.7 210.2 194 '9 207.9 202.2 209.3 211.9 205.0 211.0 201.9 210.5 213' 7 204.5 218.2 200.7 217.4 200' 4 221.1 200.6 207.1 199.2 2~3' 0 206.5 214.8 209.4 227.9 203.3 202.4 204.1 205.6 210.3 204 '7 207.1 198.7 202.5 205' 3 TUNNEL FLOW TO CRATER LAKE T'JRBINES (CPS) FEB 213. 213' 5 224.4 228.,£ 219.1 215.6 228.8 225.1 2u. a 221 9 215.2 219.9 204 '4 213' 0 226.4 209.5 220 '4 207.4 233 '8 224 '0 201. a 211. a 224.0 211.1 249.2 214 '6 209,4 224.2 214.6 202.6 210.1 220.1 241.5 213 .o 212 1 220.7 213.5 247.9 231.5 207.1 219.6 192.1 237.5 217.2 212.7 231.7 222.3 210.2 226.3 199.6 219.6 212 '7 229.6 228.4 216 .a 230.7 215.8 224.6 231.4 219.5 235.5 214.1 23L 7 214.3 240.7 220' 2 221.7 210.3 229.5 22s. a 226.6 220.1 244 '3 215.4 212.4 218.0 219.5 217.0 216 '8 208' 211.0 217' 8 220.0 MAR 196' 2 194 '4 211.4 214.2 205' 1 200 0 2:4 '0 211' 3 201.6 202.7 197.5 207 3 186.5 198.6 208.4 194.6 204 '0 187.7 218' 8 216. 195.4 204 '3 208.0 195.1 213.8 198.5 193.3 211,4 199.3 184.2 190.7 202.3 222 2 201.4 196 '3 206.2 201.7 230.6 225.1 191.9 203.9 177 '8 226.7 200' 5 197.5 215.0 205.6 189.1 207.1 181' 7 204.3 194.6 216.3 215 '4 194 '9 217' 1 198.6 210.0 212.1 236 '2 219.2 196 < 5 217.8 200.3 223' 202.3 206.5 193.6 216.4 216.7 212.3 194.7 215.2 193' 6 192.9 200.3 194,7 201.5 192.6 189 '1 194.1 200.0 203.5 APR 170.5 163.3 186.3 192.2 179.9 175' 8 193.7 187.4 221.2 173.1 191.6 194.9 168.2 168.9 172.2 170.3 175.1 160.9 194' 3 164 '3 174,0 178,3 183' 8 164.3 179' 5 172.1 158 '1 182 '4 179.7 180.7 158.0 178.7 197.2 167.2 :72.0 223.5 181.5 341.8 212 .l 169.9 186.5 159.1 206. a 195.6 168.0 189.2 176' 7 156.6 183.6 155.9 241.6 1.74 .4 189.3 198.7 170.9 195' 4 172 '6 213.2 193.8 174.0 194.2 169.1 185.9 164.6 195.4 184.4 172.0 170.9 189.4 193 '5 179.7 169,4 H4.9 159 '7 171' 0 1 il. s 170.1 1a3.5 169.1 163 .2 164.2 179.6 ~82.3 MAY 142.0 133 '9 157.1 161.1 153.4 149.7 159.3 150.1 178.8 143.9 l52 .3 159.9 143.1 138.9 135 ~ 5 139.7 145.1 135.3 151.8 159.4 128.3 144' 5 144.7 137.8 151.8 140.6 133. a 149' 0 147.3 140.4 133.2 143 '7 148.9 1.38.3 137.8 167.9 150.2 196 9 156.3 135.3 146 '8 133.2 163.9 159.9 138.9 160 '6 146,2 132.7 147.7 ~33.2 192.9 150.4 157.3 156' 6 141.9 155.2 155.4 162.8 155.9 159.7 174.3 145.9 149.9 134,5 153.8 144.9 138.0 144.6 153,4 174 '9 140. 134.6 157.1 142 .a 143.7 144.6 142.5 138.1 138.4 147.8 129.6 144.2 148 '7 109 '4 109.8 125.1 128' 4 124 '6 124.0 121.0 127 .l 136' 3 117. :17 '9 129.8 ll7 .5 113.5 119.2 120.2 119.9 lOB. 7 119.a 123.0 104.8 117' 6 123.6 107 '9 118.7 113.1 111 '2 121.3 114.2 112.9 110.1 117' 7 122.2 119.0 11.0.5 125.0 :34.7 130.6 122.5 106.1 118' 7 116.9 127,5 124.4 109.4 126.2 122.2 102 '0 122 < 8 112.5 141.0 125.2 121' 6 109.2 120.4 119.6 125.0 131.2 122 1 122.7 125 .s 116.4 l2G 2 116.0 132.4 117' 6 116.7 118.2 124' 129' 116.4 110.7 127.4 112.2 117 '5 121.7 115.0 109.4 114.4 115.6 109 < 3 120.0 119.3 JUL 102' 5 102.3 118.5 120.6 115.8 122.9 121,9 126,1 124.8 115.3 450.0 115.3 112.1 107.5 116' 8 116.6 116.4 227.1 80.0 111.3 92.6 108.4 113 '0 104 '0 156.5 105.0 104 < 8 98.4 107.7 213.3 94.6 105.5 99.9 98.7 97.9 89. a 130' 110 .s 108.3 90.6 105.8 1o5. a 110.7 111.1 91.6 110. a 111.6 250.5 114.5 102.0 255 '3 107 .4 102.9 96.7 108.8 104.8 122.1 104.4 109.1 110.3 108.5 110.2 110.6 106.8 125.5 107.1 102.5 102. a 96 '3 112.6 117.3 108.3 106 '7 102' 8 112.5 103.5 135 '1 99.1 190.5 99.5 as .1 126.8 120 '2 AUG 183 '6 459.7 116 '7 114.9 286 .] 121.8 120' 122' 3 128.4 250.2 500.0 115' 3 124' 105.1 189.3 177'? 114 '4 473.3 99' 0 107.6 101 '1 105.5 210.6 409.3 305. 500 163.3 103.8 108 '5 313.5 338.2 198.1 101.9 104.9 172.6 99.3 126.9 117.8 110 '9 99.9 113.5 104.2 113~1 158.6 97.7 155.8 115.8 500.0 115.2 103.2 366.8 108.1 108.1 99.9 114.1 262.6 231.4 105.0 107.7 105.1 111.6 181.3 108.3 103.5 127.3 106 .4 187.0 104.9 112.7 H1.9 114.4 108.5 113.4 260' 3 184.4 107.7 379 '4 144.6 371 '6 110.4 95' 6 128 '0 173.9 Page 16 SE? 265.5 388.2 244.2 270' 4 411' 7 364.1 125 '3 137.0 4~1.1 500 '0 500 '0 131.1 292.2 218. 342. 346,2 320.3 361.3 114 '7 122.3 110.2 182.8 447.4 398' 7 439.4 441.7 330.2 119.9 151.0 413.8 393.4 444.4 110.5 208.1 458.3 99.3 124.5 126.7 119.8 325.4 119.9 219.6 123 .4 398' 3 307.1 389.2 435' 0 416.3 201.8 303.8 243.5 1~9 '7 150 '5 242.7 234.6 344.5 431.4 392.3 114' 5 237.5 130. B 436.3 121.2 192.0 130 '4 220.6 388.5 379. 127.6 115.0 126.9 444. 192.0 441.7 299~1 272.1 443.1 462. 461.7 125.0 307.5 116.3 276.5 AVG 182.1 219 "0 178.4 190 .4 216.3 187.0 173.6 166.0 192.3 207 268 5 175' 2 170' 9 173.0 187 185.1 208' 5 227,7 178 .c 159.2 146.7 163.1 201.5 239.5 230.4 221.5 190.1 176.1 162.8 211 '5 207.6 207.2 1e2. a 160.1 198.3 163.2 160.7 186.2 166.4 164.5 175.4 153 < 0 173' 3 189' 7 176.3 198.4 195.1 246.3 1.87.7 171.2 230.6 175.1 164.2 193.8 175' 3 197.5 201.8 200.1 167.0 168 '3 185.8 188.7 172.8 160.5 177.2 165 '7 205.6 184.6 167.1 164' 6 171.3 195 '7 190.3 209' 5 181.1 191.3 235.9 199.4 220.4 158.1 169 '8 167.0 187.7 - 2)25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 :1.978 1979 1990 1981 1982 1983 1984 HB5 1986 1987 1998 1989 1990 1991 1992 1993 1994 1995 AVG OCT • 0 • 0 .0 . 0 .o .o .0 .0 .0 .0 . 0 . 0 0 . 0 . 0 .0 .0 .o .0 .0 .0 .0 .0 .0 .0 .o .0 .0 . 0 . 0 • 0 . c .c .0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 • 0 . c • 0 . 0 . 0 • 0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 . 0 .0 .0 . 0 . 0 .0 .c .0 . 0 .o .0 . 0 . 0 .0 .c • 0 .0 NDV .0 . 0 .0 . 0 .0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .0 .0 . 0 . 0 . 0 • 0 • 0 .0 .0 .0 • 0 . 0 • 0 • 0 .0 . 0 .0 .0 . 0 . 0 • 0 .0 .0 .0 .0 .0 .0 . 0 . 0 .0 .o .0 .0 .0 .0 . 0 .0 .0 .0 .o . 0 . 0 . 0 . 0 . 0 .0 .0 .0 .0 .0 . 0 .0 . 0 .0 .0 .0 . 0 .0 .0 .0 0 .0 .0 .0 DEC .0 .0 .0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 . 0 . 0 • 0 . 0 .0 . 0 .0 • 0 .0 .0 . 0 . 0 . 0 .0 .c .0 .0 .0 • 0 • 0 . 0 .0 .0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 . 0 • 0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 . 0 . 0 .0 .0 .o .0 . 0 . 0 .0 .0 .0 . 0 .0 .o .0 .0 • 0 .0 .0 .0 .0 .0 .0 . 0 . 0 .0 . 0 .0 Appendix B SNETTISHAM HYDROELECTRIC PROJECT-PRELIMINARY-INPUT, SNETOPR6.IN RUN 6 322000 MI'I'H LOAD -ALL SNET GEN t.:SAELE ~ LONGOPR6. OUT. CRATDPR6 .OUT JAN .0 .0 .0 . 0 .0 . 0 .0 .0 .o .0 .0 .0 . 0 . 0 . 0 .0 .0 .0 . c .0 . 0 .0 .0 . 0 . 0 . 0 . 0 . c . 0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .o .0 .0 .0 .0 .0 . 0 .0 .0 . c . 0 • 0 . 0 . 0 .o .0 .0 .0 .0 • 0 . 0 .c .o . 0 .o .0 .0 . 0 .0 .0 .c . 0 . 0 .0 .0 .o . 0 .0 .c .0 .0 .0 . 0 SPILL AT CRATER LAKE Ol:'TLET (CFS) FEB . 0 . 0 "0 .0 • 0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .o .o .0 .0 .o .0 .0 • 0 . 0 . 0 . 0 .0 • 0 .o .0 . 0 . c . 0 • 0 .c .c .0 .0 .0 • 0 . 0 . 0 .0 .0 .0 .0 .0 .o • 0 .0 • 0 .0 .o .0 .0 .0 • 0 .0 .0 .o .0 • 0 . 0 . 0 . 0 .0 . 0 .0 .0 .0 . 0 . 0 . 0 .0 . 0 .0 .0 .0 • 0 . 0 . 0 . 0 .0 MAR .0 .0 .0 . 0 .0 .0 . 0 . 0 . 0 . 0 . 0 .0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .o .0 .0 .0 .0 . c . 0 .0 • 0 .0 .o .0 . 0 . 0 • 0 . 0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .0 . 0 .0 .o • 0 • 0 • 0 .0 .0 .0 .o .0 .0 .o • 0 .0 .0 .c .0 .0 .0 .0 .0 .0 .o .0 .0 .0 .0 .0 . 0 .0 . 0 .0 Al'R .0 . 0 . 0 . 0 .c .0 .0 .0 .0 . 0 . 0 . 0 . 0 . 0 .0 .o .0 . 0 .0 .o .0 .0 .0 .0 .o . 0 .0 .o .0 . c .0 . 0 .0 . 0 .0 .0 . 0 . c . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 . 0 . 0 . 0 • 0 .0 .0 .0 . 0 . 0 • Q . 0 .0 .0 .0 .0 . 0 .0 .0 .0 • 0 .0 . 0 .0 . c . c . 0 . 0 .c .c .0 .0 .0 .0 .0 . 0 . 0 . 0 .0 . 0 .0 • 0 .0 • 0 • 0 • 0 .o .0 .0 .0 .0 . 0 . 0 . 0 .0 .0 .o .0 .0 • 0 • 0 • 0 . 0 .0 .c .0 .o . 0 . 0 .0 .0 .0 .0 .0 . 0 • 0 .0 .0 .0 . 0 . 0 .0 .0 . 0 . 0 .0 .0 .0 . 0 .0 .0 .0 . 0 . 0 .0 .c . 0 .o "0 . 0 .0 .0 .0 JUN .0 .0 .0 . 0 . 0 . 0 • 0 .0 .0 .0 .0 .0 . 0 .0 . 0 .0 • 0 .0 . 0 . 0 . 0 .o .0 .0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 .0 .o . 0 .0 .0 .c .c .0 .0 .0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .c . 0 .0 .0 . c .0 . 0 .0 .0 .o .0 • 0 • 0 . c . 0 . 0 . 0 .0 .0 .0 . 0 . 0 .0 • 0 .0 .0 .0 . 0 . 0 . 0 JUL . 0 . 0 . 0 .0 . 0 0 .0 .o .o .0 . 0 .0 .0 .0 . 0 . c . 0 .0 .0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .0 . 0 . 0 • 0 • 0 • 0 .0 .0 . 0 .0 .0 . 0 .0 .0 .0 .0 .0 . 0 . 0 . 0 . 0 .0 .0 .0 .0 . 0 .0 .0 .0 .0 . 0 .0 .0 . 0 . 0 .0 .0 .0 .0 .0 . 0 . 0 . 0 .0 .0 .0 .0 .0 .0 .0 .0 . 0 AUG .0 .0 .0 .0 .0 .0 .0 .0 . 0 . 0 66.0 . 0 . 0 . 0 .0 .c .0 .0 .0 .0 . 0 . 0 • 0 . 0 . 0 95 .o .o .0 • 0 . 0 . 0 • 0 .0 .o .0 .0 .0 .0 .0 .0 .0 .o .o .o .0 .0 .0 73.9 .0 .0 .0 .0 . 0 . 0 .o .0 .0 .0 . 0 • 0 . 0 . 0 . 0 • 0 .0 .0 .0 . 0 . 0 . 0 . 0 . 0 .0 .0 .0 . 0 . 0 . 0 . 0 . 0 .0 . 0 2.9 Page 17 SEP .0 . 0 . 0 . 0 . 0 .0 .0 .o .0 . 5 81.5 • 0 . 0 .0 .0 • 0 .0 . 0 . 0 .0 .0 .0 . 0 • 0 • 0 • 0 .0 .c .o .o .o .0 .0 .0 . 0 . 0 • 0 .0 .0 . 0 . 0 • 0 .0 .0 • 0 .0 .0 .0 .0 .0 . 0 . 0 .0 .0 .0 .0 . 0 • 0 .o .0 .0 .0 .0 .0 .0 .0 • 0 .0 .0 .0 . 0 .0 .o . 0 . 0 .0 . 0 . 0 .c .0 .0 .0 1.0 AVG .0 . 0 . 0 . 0 .0 . 0 .0 . 0 • 0 . 2 12.3 .c . 0 . 0 . 0 .0 . c .0 .0 .0 .0 . 0 • 0 . 0 .0 7.9 .0 .0 .0 .0 .0 • 0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 .0 6. 2 . 0 • 0 .0 .0 .0 .0 .0 .0 .o .0 . 0 .0 . 0 .0 • 0 .0 .0 .0 .0 .0 • 0 .0 . 0 . 0 .0 .c . 0 . 0 .0 .0 .0 .0 .0 .0 . 3 - - 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1998 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1001.6 998.8 1004. 8 1001. 1 1002. ~ 1004.2 1003.9 990 989.1 ~004.2 1003.5 1001.6 991.0 1001.8 1003 5 1004.5 987.8 1003.3 997.6 961.9 957.8 989.3 1004. 984. 993. 1003.6 999.5 997.6 999.9 1002.6 1000.0 998.8 996.5 989.6 1001.1 1305.6 965.7 979.1 976.3 981.9 999.6 968 '4 1004.9 1002.8 1003.0 1003.7 1002.7 999.1 996.2 1003.5 998.0 997.0 983.9 993.2 1002.8 1005.5 1003.9 1000.7 1005.1 982.3 997.6 977.5 1002.8 997.2 1004.4 979.6 995.6 1002.9 1005.3 980.7 996.1 1000.0 1001 998.3 1004. B 993.4 1002. 1001.5 1003. 3 1005. 3 1004.5 1003.9 996. 3 NOV 1001 998.8 :004.8 ~001.1 1002.1 1004.2 1003.9 989.7 1000.4 1004.2 1000.5 1001.6 992.4 1001.8 1004.6 1004.5 1003.4 1001. 9 997.6 984.4 965.7 1004.1 1004.7 1001.7 993.4 1003.6 1004.5 997.6 1005.1 1002. 6 1000.0 998.8 996.5 990.2 1001.1 1005.6 974.9 979.4 980.3 997.0 999.6 975.7 1004.9 1005.2 1005.4 1003.7 1002.7 999.1 996.2 1003.5 998.0 997.0 998.3 993.2 1002 8 1005.5 1003.9 1000.7 1005.1 990.5 997.6 1003.0 1002.8 1002.1 1004 .4 1002 . 8 995.6 1002.9 1005.3 986.2 1003. 0 1000.4 1001. 998.3 10o4. a 993.4 1002.7 1001.5 1003.3 1005.3 1004.5 1003.9 999.1 Dl!C 999.8 998.9 991.1 991.9 1002.1 1001. 3 993.4 962.4 989.6 1005.2 1000.5 997.3 990.9 999.6 989.8 999.4 1003.4 1001.9 993.9 971.6 973.8 995.1 993.2 1001.7 995.4 996.4 1004.5 995.4 998.8 1000.3 1003.6 999.3 990.6 988.7 998.5 998.8 990.4 960.9 963.7 994.9 992.9 975.4 991.6 999.6 1005.4 997.0 996.0 991.3 994.6 1001.9 991.1 996.0 987.8 1000.3 1000.1 993.7 1000.2 1001.7 991.1 982.7 991.7 1005. 1 990.0 991.4 991.0 994.0 996.9 999.5 996.9 975.7 992.3 991.0 985.3 1004.5 1002.0 997.2 981. 990.0 994.7 992.3 1001.7 1001.4 994.0 Appendix B Page 18 SNETTISHAM HYDROELECTRIC PROJECT ?RELIMINARY -INPUT, SNETOFR6. IN RGN 6 322000 MWH LOAD A!:.L SNET GEN USABLE -LONGOPR6 .OOT, CRATOPR6 Otr. JAN 982.7 980.5 974.4 974.1 985.9 985.1 976.7 960. 975. 986.1 994.5 978.0 983.3 984.5 969.7 986.1 988.7 999.2 975.5 947.0 950.5 980. 986.6 993.0 980. 982. 988.4 977.9 981.2 993.9 1004. 0 980.5 970.7 971.0 991.3 979.9 973.2 935. 937. 978.0 976.5 970.1 972.3 1001.5 985 .o 986.6 983.6 997.8 975.7 988.3 976.5 978.4 969.9 980.0 981.0 975.3 985.0 981.7 971.7 959.7 970.7 992.8 970.6 978.6 969.3 978 .4 988.7 981.4 977.3 948.6 971.5 972.1 1001.2 994.2 985.6 980.7 990.8 971.2 978.3 976. c 990.3 983.2 978.8 NET HEAD ON CRATER LAKE UNITS (BET) FEB 960.4 958.8 946.3 947 .4 966.8 971.4 959.7 936.4 949.9 964.7 976. 952.9 972.8 965.8 950.6 974 8 965.9 984.1 946.7 918.4 927.9 954.3 965.3 976.3 958.9 965.4 97C. 8 950.0 960.9 968.3 992.7 959.8 942.7 946.6 976.2 957.4 945.8 903.0 907.1 953.0 949.7 949.7 942.8 983.7 970.9 965.3 963.9 985.0 954.6 975.0 953.8 962.6 943.3 953.1 957.1 945.4 964.1 960.5 945.8 937.0 943.1 975.7 948.9 956.4 942.1 952.8 967.9 963.4 950.7 924.4 949.3 952.2 985. 979. 965.7 964.4 984.3 943.5 957.4 952.9 974.6 962.1 957.5 MAR 938.6 933.4 918.2 922.6 940 944.5 934.8 910.8 922.6 941. 5 952. 1 925.2 946.8 939.7 924.7 949.0 938 .l 975.4 917.5 889.3 906.9 927.0 937.2 950.0 970.4 942.3 944.9 920.9 936.1 946.5 976.5 939.9 917.1 920.0 951.6 928.9 921.0 877.1 875 8 927.3 927.1 925.8 911.8 961.9 944.7 939.5 938.3 967 .a 929.5 953.7 927.7 939.0 915.9 924.8 933.9 915.2 939.7 933.:.. 917.4 910.1 912.7 949.2 921.3 929.9 913.6 928.6 940.5 940.2 924.1 894.7 923.5 935.9 976.0 960.2 945. 5 940.0 970. 921. 949.2 935.8 948.5 937.2 933.4 A?R 915.1 911.1 889.1 893.7 911.6 917.2 905.1 882.4 893.6 917.8 929.5 895.7 926.6 912. a 899.6 928.6 910.0 951.,9 886 .a 859 879.4 898.2 909.5 925.4 950.0 917.6 918.1 891.4 908.5 927.0 954.6 913.1 889.0 896.5 925.2 900.5 893.9 844.7 840.6 900.4 898.7 901.5 880.2 935.8 918.6 910.7 911.3 945.8 901.5 933.2 900.4 916.0 888.1 996.0 915.5 885.4 915.9 903.4 890.8 882.2 884.5 926.7 890.7 902.4 885.4 901.5 913.4 915.4 897.6 863. 894.8 912.7 955.6 937.8 923. e 912. 9 946.3 894.3 933.0 912.8 925. e 917.0 907.3 MAY 898.5 898.8 868.9 869.5 888.8 898. 880. 0 859.1 903 .4 902 .4 937.2 872.6 909.9 893.2 881.5 908.5 890.1 937 1 863.8 839.2 860.0 877.3 893.6 906.4 931.4 900.0 899.0 871.4 886.7 933 .l 939.6 894.8 867.5 879.6 902. 910 871. 860. 818.0 881.5 876.1 883.2 852.5 936.2 899.4 888.7 892.0 933.0 879.5 915.6 938.9 899.7 868.1 874.1 897.6 865.4 897.8 915.7 867.9 864.6 859.4 909.2 870.0 884.1 862.1 881.5 896.0 900.6 875.4 834.9 874.3 900.7 939.2 922.3 914.3 893 .6 940.2 892.9 927.5 901.6 913.9 908.5 891. 9 JUN 899.6 915.0 859.0 867.6 885.9 894.9 864.9 855.5 913.0 907,7 957.2 859.0 915. 9 886 9 891.0 902.0 884.7 948.5 857.0 863.3 852.7 875.2 908.3 907.2 950.7 905.0 897. 868.6 882.0 947.2 959.3 902 .4 869.2 885.1 908.1 911.2 858.0 871.1 824 .e 894.0 865.9 875.7 863.0 946.8 911.8 897.1 899.5 950.2 870.6 919.2 944.0 891.7 871.0 873.6 900.7 874.7 914.1 926.2 865.5 879.3 854.5 920.4 865.8 883.0 858.7 891.5 898.0 906.5 878.0 832.6 872.0 905.1 940.4 945.7 925.6 918.4 952.3 888.9 940.5 920.3 922.5 923.0 896.2 J17L 924.6 958.7 896.8 894.6 919.6 909.3 874.1 883.8 938.4 935. 973. 888. 952.2 922,7 930.5 941.0 9B .3 981.8 883.2 883.0 887.0 890. 952. 961.2 979.5 929 9 929.5 903.5 904.7 982.0 990.8 949.6 908.9 932 .4 953.4 925.5 888.6 913.3 856.0 331.3 891.3 903.0 878.9 973.6 953.3 939.4 930.5 980.7 905.9 950.4 980.6 91 '7 '4 902.9 917.4 926.7 932.3 947.2 958.4 884.5 905.1 872.9 948.3 883.6 915.0 894.0 919.1 937.7 928.1 914 6 883.1 911.8 922.2 974.7 975.1 956 .1 955.4 983.1 928 0 976 947. l 962.9 946.0 927.9 AUG 980.4 987.1 935.7 943 .4 967.1 952.9 9:7 9 925.6 977.7 977 .o 984.5 915.0 981. 961. 9 983.4 980.5 957.9 986.9 877.2 902.3 906.6 939.0 988.8 983.2 999.2 955.3 969.0 943 8 940. 998 8 986.4 988.4 928.7 947.6 980.7 916.7 927.9 927.2 895.8 948.6 912. 941. 913.1 985.6 966.4 982 .s 973.0 984.5 945.0 979.5 995.4 936.0 927.3 940.5 954.2 972.9 980.9 974.2 907.2 936.0 898.1 988.1 923.1 950.4 924.1 968.5 981.3' 950.3 909.9 912.3 953.0 971.3 980.2 989.8 988.1 968.5 994.5 969.7 995.0 949.0 961.0 982.1 955.9 SE!? 1001.4 993.8 976.4 990.8 992.1 989.2 978.2 959.9 992.3 984.5 984.5 960.4 1000.0 988.5 997.0 996.7 993.9 995 917.9 935 2 966.8 981.4 989.2 993.1 989.8 999.7 997.7 973.9 979.6 991.9 993.5 989.4 966.0 978.0 988.3 955.8 962.7 954.2 938.4 986.4 940.0 980.9 979.4 993.1 992.1 993.8 990.2 991.7 978.6 991.8 1002.4 967.0 977.6 979.6 979.3 996.8 990.5 989.7 944.5 987.9 936.8 990.1 960.1 981.8 954.2 986.7 993.8 985.1 946.0 965.5 992.1 989.5 1004.5 989.7 999.6 984.7 989.5 987.9 988.0 984.0 981.7 1002. 3 980.9 AVG 958. 961. 939.0 941.5 955.3 956.1 941.0 928.0 953.8 960.9 974 '5 937.3 963.7 954.9 952.2 964.6 953.1 980.6 926,2 912.9 919.6 942.6 961.2 965.3 974.4 957.6 960.3 941.0 948.6 973.7 983.4 959.6 936.9 943.7 964.8 949.7 931.2 911.1 901.2 947.9 935.8 937.6 932.9 977.2 963.0 959.0 957.0 977 944.0 968.0 967.2 949.8 936.2 943.8 954.3 947.4 961.9 962.2 933 1 934.8 926.6 965.5 935.9 947.7 933.6 948.7 958. 9 956.4 940.1 916.8 944.5 954.4 978.7 974.6 968.0 958. 975 .,{. 949.3 970.6 956. 966.0 964.0 951.6 - 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT NOV DEC 1008.0 1008.0 1002.2 10o8. 1008.0 10n.4 1008.0 1008. 993.8 1008,0 1008. 994.6 1008.0 1008.0 1008.0 1008.0 1008.0 1004.0 1008.0 1008.0 996.2 991.9 991.6 984.9 990.9 1002.3 992.2 1008.0 1008.0 1007.6 1008.0 1008.0 1008.0 1008.0 1008.0 1000.0 992.6 994.4 993.4 1008.0 1008.0 1002.3 1008.0 1006.6 992.5 1008.0 1008. 1002.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 996.7 963.1 986.1 974.0 959.2 967.4 976.0 990.4 1006.0 997.6 1008.0 1008.0 995.7 1008.0 1008.0 1008.0 1008.0 1008.0 998. 1008.0 1008.0 998.9 1008.0 1008.0 1008.0 1008.0 1008.0 998.1 1002.8 1008.0 1001.4 1008.0 1008.0 1002 1008.0 1008.0 1007 1008.0 1008. 1001 1008.0 1008. 993.3 989.8 991. 991 0 1008.0 1008. 1000.9 1008.0 1008.0 1001.5 966.6 976.5 992.7 980.6 981.4 963.5 977.8 982.2 966.2 983.3 998.2 997.2 1008.0 1008.0 995.7 969.7 977.3 977.4 1008.0 1008.0 994.3 1004.3 1007.2 1002.1 1008.0 1008. 0 1008.0 1008.0 1008.0 999.7 1008.0 1008.0 998.5 :oos.o 1008.0 1001.5 1008.0 1008.0 1008.0 1008.0 985.2 1008.0 1008.0 1008. c 1008.0 1008.0 1008.0 983.6 1008 '0 979.1 1008.0 998.6 1008.0 981.2 1008.0 1008.0 1008.0 982.3 1001.1 1007.6 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 1008.0 lOOa.o 1008 0 1008.0 1002.0 1008.0 997.3 1008.0 1004.4 100a.o 993.8 1008.0 998.7 999.8 990.3 1008.0 1003.1 1008 0 1002.7 lOOa.o 996.4 100a. 0 1002.8 1008.0 1004.4 1008.0 993.8 992.1 9as 1 1008.0 994.5 1005.9 1008.0 1008.0 992.8 1004.0 993.9 1008.0 993. 1004.4 996 100a.o 999.5 1008.0 1002.1 1008.0 999.6 9a8.0 978.1 1008.0 995.1 1008.0 993.6 1008.0 992.1 1008 a 1001.1 1008.0 1004.5 1008.0 999.8 100a.o 999.1 1008.0 992.6 10 08. 0 997.3 100a.o 994.9 1008.0 1004.2 1008.0 1004.1 1004.4 997.1 Appendix B Page 19 SNETTISHAM HYDROELECTR!2 PROJECT -PRELIMINARY -INPUT, SNETOPR6.IN RUN 6 322000 MWH LOAD -ALL SNET GEN USABLE -LONGO?R6.0UT, CRATCPR6.0UT JAN 986.0 983.8 978.0 977.9 989.4 988.7 980.6 963.6 978. 989. 998.0 981.6 986' 8 987.9 973.6 989.5 992.3 1002.7 979.4 950.3 953.3 983.9 990.4 996.3 983.7 986.1 991.7 981.5 984.6 987. 100a. 0 9a3. 9 974.7 974 '3 994.8 983.4 976.4 939.3 941.3 981.1 9ao .4 972.9 976.1 1005.2 988.5 990. 987,2 1008.0 979.5 991.5 980.2 9a1.9 973.5 983.1 984.5 979 .o 988.4 985.4 975.4 963.2 974.6 996.2 974' 5 982.0 973.4 9a1.8 992.4 984.9 981.1 952 .1 975. s 975.8 1008.0 997' 989 0 984.2 1008.0 974.9 981. 9 979.6 993.7 9a6. 7 982 7 STATIC HEAD ON CRATER LAKE UNITS (FEET) FEB 964.1 962.5 950.3 951.7 970.7 975.3 964.1 940.4 953.6 968.7 980.8 956.9 976.6 969.5 955.0 978.5 969.9 987. a 951.0 922.2 931.2 958.1 969.4 980. 962. 969.2 974.5 954 '0 964 '7 971.9 996.5 963.8 947.3 950 '2 979.9 961.3 949 4 907.5 911.2 956.5 954.0 952.7 947.2 987.7 974.7 969.7 96a .o 9a8' 8 958.7 978.6 957.9 966.4 94 7. 4 957.4 961.0 949.6 968.0 964.7 950.1 940 9 947.5 979. 953.3 960.1 946.7 956.6 971.9 967.1 955 0 928.5 953.7 956.4 990.0 9a3 .1 969.6 968.3 988.2 947.7 961.4 957.0 978.3 965.9 961.4 MAR 942.8 937.6 922.9 927,5 944.5 948.9 939.8 915.5 926.9 946.1 956.5 929.8 952.7 944.0 929.5 953.1 942.7 979.4 922.6 894.0 911.0 931 5 941 954.2 976.3 946.6 949.0 925.6 940.4 950.4 9aO. 6 944.5 922.6 924.2 955.9 933.5 925.3 882.9 880.9 931.4 931. 6 929.3 917' 1 966.3 949. 944.6 943.0 971.9 934.3 957.4 932 '3 943.3 920.9 929.7 93a. 3 920.2 944.1 937.9 922.4 914.6 918.0 953.5 926.3 934.2 919.1 933.2 945.1 944.3 929.0 899.5 928.3 940.5 981.6 964.6 949. a 944.4 974.5 926.0 953.6 939.9 952.7 941 '7 938 APR 918.7 914.6 893.3 898.0 915.5 92l.O 909.4 sa6.6 897.4 921.6 933.1 899.7 929.9 916.5 903.7 932.2 913.9 955.2 891.3 863.5 833.0 902.2 913.5 929.0 954.3 921.3 921.6 895.6 912.2 930. 958. 916.9 893.6 900. 3 928.8 904. 5 897.8 849.7 845.4 903.9 902.6 904.5 885.0 939.6 922 .3 915.1 915.3 949.1 905.5 936.3 904.3 919.6 892.5 900.3 919.1 889.8 919.6 907.5 895.1 886.2 8a9.0 930.3 895.2 906.2 890.0 905.3 917.4 918.9 902.0 867.7 899.0 916.3 959.9 941.3 927.3 916.6 949. 898 1 936.5 916.1 929.3 920.8 911.2 MAY 901. 2 901.3 872.2 872.9 891.9 901.9 883.5 862.4 908.0 905.2 940.6 876.2 912.5 895.8 884.3 9:1.2 893.0 939.6 867.3 841.7 862.9 880.2 896.8 908.9 934.4 902.8 901.4 874.5 889.7 936.2 942.0 897.8 871.2 882.2 904.9 915.0 874.9 a71.2 822.2 884.2 879.3 8a5.5 856.5 939. a 902.1 892.1 894.9 935.3 882.7 917.9 944.4 902.5 871.4 877.8 900.4 a69.0 900.6 920.0 a71.5 a67.4 863.0 911.8 873.2 886.7 865.7 8a4.7 898.7 903.4 a78. 7 838.4 877 .3 903.4 942 '4 924.7 917. 1 896.4 942.9 896.0 930 904.1 916.5 911.5 895.1 901.5 916. 7 861.3 870.0 888.1 897.0 867.3 857.7 916.0 909. 959.4 a6:. 4 917.8 888.7 892.8 903.9 886.7 950.2 859.1 865.7 854.2 877.1 910.3 908.9 952.8 906.9 899.4 870 884 .o 949.1 961.0 904.3 871.3 886.9 909.9 913.8 860.1 874.8 827.1 895.7 868.0 877.3 865.5 949.2 913.6 899.6 901.5 951.8 872.6 920.8 947.5 893.8 873.3 876.0 902.6 877.0 916.4 928.7 867.8 881.7 857.3 922.4 868.0 884.7 860.9 893.5 899.8 908.4 880.2 835.5 873.8 906.8 942 947.6 927.6 92~' 3 954.2 890 7 942 3 922.4 924.0 921.9 898.3 JUL 925.7 959.8 898.2 896.2 921. 910. 875.5 885.3 940.1 936.4 992.4 889.6 953 's 923.9 931.8 942.4 914.6 986.7 884.5 884.4 aa8.0 891.3 954.2 962.3 981.a 931.1 930.6 904.9 906.0 986.3 991.9 950.9 910.3 933.7 954.5 926.9 890.3 914.9 a57.4 932. 3 a92.7 904.3 880.4 975.0 954.4 940.9 931.9 986.6 907.3 951.6 986.7 918.9 904.3 918.5 928.0 933 '7 94a .6 960.0 885.9 906.5 a74.4 949.6 885.0 916.3 895.7 920.4 939.0 929.5 916.1 8a4. 7 913.1 923.4 976.2 976.3 957.4 956 8 984. 929.1 980.1 948,4 964.0 947.3 929.7 AUG 963.6 1007. 0 937.0 944.8 974.8 954.4 919.3 927.1 979,3 982.8 1008.0 916.3 982.5 962.9 986.8 983.5 959.2 1008.0 877.8 903.4 907.4 940.1 993 0 999.0 100a. 0 978.8 971.5 944.7 941.2 1008.0 997.1 992 1 929.7 94a.5 983 5 917.4 929.5 928.3 896.9 949.4 913.6 942.4 914.2 988.0 967,2 9a5.1 974.3 1008.0 SEP 1008.0 1008.0 984.0 997.7 100a. 0 1001.7 979.6 961.3 1008.0 .!.008.0 1008.0 961.6 ~008. 0 992.9 l008 '0 :ooa. o :003.5 1008.0 918. B 936.3 967.7 984.5 1008.0 1008.0 1008.0 1008.0 1008.0 974.9 981. a 1008.0 1008.0 1008.0 967.0 982.0 1008.0 956.7 964.2 955. 939.5 996. 941.2 985.4 980.6 1008.0 1000.9 1008.0 100a.o 1008.0 946.2 9a2.4 980.5 1000.5 1008.0 1008.0 937.1 968.1 na.3 979.8 941.4 985.1 955.3 984.5 979.3 1008.0 985.9 100a.o 975.2 1004.1 908.3 945.6 937.1 993.2 a99.2 938.0 991.2 1008.0 924.2 961.8 951.5 985.3 925.6 955.7 969.5 991.3 9a4.6 1008.C 951. 998.7 910.8 947.2 913.5 966.7 954.3 993.3 972.4 1008.0 981.5 1008.0 996.2 1008.0 991.3 1008.0 969.5 991. 1008.0 1008 971.7 1008 '0 1008.0 1008.0 949.9 985.4 961.6 990.6 983.6 1003.8 959.8 989.6 AVG 962.5 967.4 942. 3 945.6 960.7 960.0 944.3 930.7 957.8 966.0 983.4 94o.a 966.7 958.4 956.0 968.4 958.3 986.8 930.4 915.4 921.8 945.2 965.8 972.6 981.3 963.8 964.3 945.0 951.4 978.8 988.9 965.0 941 4 946.3 969.8 952.5 933.6 920.8 904.0 950.8 939.6 939.9 936.1 981.0 966.4 963 .4 961.6 985.4 948.5 971.3 973.3 953.9 938.9 949.1 957.7 951.5 966.5 967.0 936.0 937.6 931.0 969.6 939.2 950.3 936.9 951.5 964.4 960.4 943.0 919.6 94 7 '7 959 3 983.2 980.2 97l.S 963.7 986.1 954.2 976.3 959.5 969.2 966.9 955 '8 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 19H 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 19.4 23.2 13.8 20.1 18.6 15.0 15 6 10.5 10.3 15.0 16.4 19.4 10.7 19.2 10.9 14.4 34.0 16.7 24.7 9.4 9.5 10.5 13.9 36.5 29.1 16.1 22.3 24.6 13 ·- 17.8 21.7 23.3 25.9 9 20 .1 12.0 9.3 10.6 10.4 8.4 22.1 9.3 13.5 10.9 17.2 15.9 17.6 22.9 26.2 16.3 24.2 25.3 9.1 29.2 17.6 12.2 15.6 20.8 13.0 9.5 24.6 9.3 17.4 10. 3 14.5 9 26.9 17.4 12.7 1C. 0 17.0 21.1 20.0 23.8 13.8 29.1 17.8 19.6 16.6 12.7 14.4 15.5 17.1 NOV 11.8 12.1 12.7 12.6 18.6 12.6 12.8 12.0 12.3 12.0 21.0 12.5 12.1 12.4 12.7 12A 16.5 19.0 12.8 11.6 10.9 12.3 12 19. 12 12.3 14.5 12.5 12.4 11 8 12.2 12.3 12.6 11.5 11.9 12.5 11.4 12.1 11.9 11.5 12.8 10.6 12.7 :1.2.1 12.4 12.5 12.4 11.8 12.5 12.1 12.7 12.6 12 2 12.6 12.4 12.5 12.4 12.6 12.7 11.7 12.8 13.1 12.9 l2.2 12.9 12.2 12.2 12.3 12.7 11.7 12.8 12.5 13.0 12.3 12.1 12.2 11.9 12.4 12.4 12.4 12.0 12.5 12.7 DEC 13.8 14.0 14.3 14.8 14.4 14.6 14.9 l4 .0 13.8 14.5 14.3 14.4 14.3 14.0 15.0 14.0 14.5 14.2 15.0 13.7 12.6 14.1 14.8 14._ 14 ,.l.- 14.2 13.8 14.4 14.0 13.6 15.3 14.2 15.2 13.6 14.2 14.3 13.5 14.4 13.9 13.5 15.0 12.4 14.9 14.7 14.4 15.2 14.5 24.3 14.8 13.8 14.5 14.3 14.4 14.8 14.3 14.6 14.2 14.8 14.8 13.9 15.2 14.2 14.9 14.1 15.4 14.0 14.7 14.3 15. 13.9 1'5 .1 14. s 19.7 14.6 14.3 14.3 31.2 l4 .5 14.4 14.4 14.1 14.3 14.7 Appendix B SNETTISHAM HYDROE~EC7R!C PROJEC7 -PREL!M:NARY -INPUT, SNETOPR6.IN RUN 6 -322000 MWH LOAD ALL SNET GEN USABLE-LONGOPR6.0UT, CRATOPR6.0UT JAN 14.4 14.5 15. c 15.4 15.0 14.9 15.6 14.8 14.3 15.1 14.9 14.9 14.6 14.5 15.6 14.5 15 .1 14.8 15.6 14.3 13.2 14.6 15,4 14.7 14.6 14.6 14.5 15 .o 14.6 14.3 15.0 14.9 15.0 14.2 14.7 14.9 14.1 15.1 14.6 14 .l 15.6 13.0 15.7 15.2 14.7 15.8 15.1 15.0 15.2 14.3 15.1 14.7 15.1 15.4 14.9 15.3 14.8 15.3 15.4 14.6 15.7 14.8 15.7 14.6 15.9 14.6 15.2 14.5 15.5 14.6 15.5 15.1 16.9 15.0 14.8 14.9 l5 .1 15.2 14.9 15.0 14.6 14.8 14.9 NET POWER FROM CRATSR LAKE UN!T IMW) FEB 15.2 15.2 15.8 16.1 15.7 15.6 16.3 15.7 15.1 15.9 15.6 15.6 14.8 15.3 16.0 15.2 15.8 15.2 16.4 15.3 14.3 15.4 16.1 15.3 17.7 15.4 15.1 15. B 15.3 14.6 15.5 15.7 16.9 15.0 15.4 15.7 15.0 16.6 15.6 14.7 15.5 13.6 16.6 15.9 15.3 16.6 15.9 15.4 16.0 14.5 15.6 15.2 16.1 16.2 15.4 16.2 15.5 16.0 16.3 15.3 16.5 15 16. 15.2 16.8 15.6 15.9 15.0 16.2 15.5 16.0 15.6 1.7. 9 15.7 15.2 15.6 16.0 15.2 :5.4 14.8 15.3 15.6 15.6 13 7 13.5 14.4 14.7 14.3 14. Q 14.9 14.3 13.8 14.2 14. c 14.2 13.1 13.9 14.3 13.7 14.2 13.6 14.9 14.3 13.2 14 .1 14.5 13.8 15.4 13.9 13.6 14.5 13.9 13.0 13.8 14.1 15.1 13.8 13.9 14.2 13.8 15.0 14.6 13.2 14.0 12.2 15.3 14.3 13.9 15 .o 14.3 13.6 14.3 12.9 14.1 13.6 14.7 14.8 13.5 14.8 13.9 14.6 14.4 13.9 14.9 13.9 14.9 13.8 15.1 14.0 14.4 13.5 14.9 14 ,4 14.6 1).5 15.6 13. 13.5 14.0 14.0 13.8 13.6 ~3 1 13,7 13.9 14.1 APR 11.6 11.0 12.3 12. a 12.2 12.0 13.0 12. 3 14.7 11. a 13.2 13.0 11.6 11.4 11.5 11.7 11.8 11.4 12.8 10.5 11.4 11.9 12.4 11.3 12.7 11.7 10.8 12.1 12.1 12.4 11.2 12 .1 13.0 11.1 11.8 14.9 12.0 21.4 13.2 11.4 12.4 10.7 13.5 13.6 115 12.8 12.0 11.0 12.3 10.8 16.2 11~9 12.5 13.2 11.6 12.9 11.7 14.3 12.8 11.4 12.8 11.6 12.3 11.0 12. B 12.3 11. 11 12.6 12.4 11.9 11.5 13.1 11.1 11..7 11.6 12.0 12.2 11.7 11.1 .3 12.2 12.3 MAY 9.5 8.9 10.1 10.4 10.1 10.0 10.4 9. 6 12.0 9. 6 10.6 10.4 9. 7 9. 2 9.1 9. 4 9. .. . 7 . 9 8.2 9.4 9.6 9.3 10.5 9.4 8.9 9.6 9. 7 9. 7 9. 3 9. 5 . 6 . 0 .2 11,4 9. 7 12.6 9. 5 8.9 9.6 8.7 10.4 11.1 9. 3 10.6 9. 7 . 2 9. 6 9. 13.5 10.1 10.1 10.2 9.5 10.0 10.4 11.1 10.0 10.3 11.1 9.9 9.7 8.8 9.8 9.5 9.2 9. 7 10.0 10.8 9.1 9.0 11.0 9 .B 9.8 9.6 10.0 9.2 .5 9.9 8.8 9. 7 9. 9 JIJN 7.3 7.5 8.0 8. 3 8.2 9. 2 7.8 8.1 9.2 7. 9 8.4 8. 3 B. o 7.5 7.9 8.1 7.9 7. 7 7.6 . 9 . 6 7.6 8.3 7.3 8. 4 7.6 7.4 7.8 7. 5 7.9 7. 8 7.9 7.9 7. 8 7.5 8.5 B. 6 . 4 7. 5 . 0 .6 7 6 8.2 8.7 7.4 8.4 8. 2 7.2 7.9 7.7 9. 9 8. 3 7.9 7.1 8.1 .8 8 9.0 7.8 8.0 8. 0 8.0 7.7 7.6 8.4 7.8 7.8 8.0 8.1 8.0 7.5 7.4 8.9 7.9 8.1 8.3 8.1 7.2 8.0 7.9 7.5 8.2 7.9 J1JL 7.0 7.3 7.9 8 7 8. 3 7.9 8. 3 8' 7 8. 32. 7.6 7.9 7. 4 B .• a.1 7.9 16.6 5.2 7.3 6.1 7.2 8.0 7. 4 11.4 7. 3 . 2 . 6 7.2 15.6 7.0 7.4 6. 7 6.8 6. 9 6.2 8.6 7.5 6.9 6.3 7.0 7.1 7.2 8.0 6.5 7.7 7.7 18.2 7. 7 7.2 18.6 7.3 6.9 6.6 7. 5 7.3 8.6 7.4 7.2 7.4 7.0 7.8 7. 3 7.3 8.3 7.3 7,1 7.1 6.5 .4 7.9 7.4 7.7 7.4 B .0 7.3 9.9 6.8 13.8 7.0 6.1 B. 9 8.3 AUG 13 4 33.7 8. 8. 20.6 8. 6 8.2 8.4 9. 3 18.2 36.6 7.8 9.1 7.5 13.8 12.9 8.1 34.7 . 5 . 2 .8 .4 l.5 .5 29.9 22.7 35.5 ll.. 8 7.3 7.6 23.3 24.8 14.5 7.0 7.4 12.6 6.8 8. 7 8.l. 7.4 7.0 7.7 7. 3 7. 7 11.6 7.0 11.4 8.4 36.6 8.1 7.5 27.1 .4 7.0 8.1 19.0 16.9 7.6 7.3 7.3 7.4 13.3 7. 4 7.3 B. 7 7.7 13.6 7.4 7.6 7.6 8.1 7.8 8.3 19.1 13.5 7. 7 28.0 10.4 2? .5 7. 9 6. 8 9.3 :12. Page 20 SEP 19. 28.7 17.7 19.9 3J. 3 26.8 9.1 9.8 30.3 36. 36. 9. 4 21.7 16.0 25.4 25.6 23.6 26.7 7.8 8. 5 7.9 13.3 32. 29.4 32.3 32.5 24.5 8.7 11 0 30.5 29.0 32.7 7.9 15.1 33.6 7. 0 8.9 9.0 8.3 23.8 8.4 16.0 9.0 29.4 22.6 28.7 32.0 30.7 14.7 22.4 18.1 8.6 10.9 17.7 17.1 25.5 31.7 28.8 8.0 17.4 9.: 32 .1 8.6 14.0 9. 2 16.2 2S. 7 27.8 9.0 .2 9. 4 32.6 14.3 32.5 22.2 ~9.9 32.6 33.9 33.9 9 22.4 8. 7 20.3 AVG 13.1 15.8 12. 13.4 15. :3,4 1:.L2 ES 13.7 14.9 19.5 12.3 12.3 12.4 13.3 13.3 14.9 16.7 12.4 10. 10.1 11.5 14. 5 17.3 16.8 15.9 13.7 12.4 11.5 15.4 15.2 l4.9 12.8 11.3 14.3 11.5 11.1 12.6 11.2 11.7 12.3 10.7 12.1 13.8 12.7 14.2 14.0 18.0 13.3 12.4 16.6 12.4 11.4 13.7 12.5 14.0 14.5 14.4 11.6 11.7 12.9 13.6 12.1 11.4 12.3 :1.7 14.8 13.2 11.7 11.2 12.1 14.0 13.9 15.3 13.1 13.7 17.2 14.2 16 0 11.3 12.2 12.0 13 .4 2/25/97 YEAR 1914 1915 19l6 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 l941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 l971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1961 1982 1983 1964 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1002.6 1013.3 1019.0 1019.0 1019.0 1005.4 1019.0 1017.6 1019.0 1019.0 1019 0 10l9 .0 997.1 978.4 1017.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1002.9 1019.0 1019.0 987.5 992.4 993.2 1009. 2· 1()19. 0 968.3 1019.0 1018.2 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1010.8 1019.0 1019' 0 1019.0 1019.0 1019.0 1019.0 1003 .: 1019.0 1016.9 1019.0 1015.0 1019.0 1015.4 1019.0 1019.0 1019. 0 999.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.~ 1019' 0 1019.0 1019.0 1019.0 1019.0 1019.0 1015.4 NOV 1013.2 1012.4 1004.8 1005.6 1019.0 1015.0 1007.2 995.9 1003.2 1018.6 1019.0 1011.0 1004.4 10l3.3 1003.5 1013.0 1019.0 1019.0 1007.7 995.0 987.0 1008.6 1006.7 1019.0 1009.0 1009.9 1019.0 1009. 1 1012.4 1013.7 1018.6 1012.8 1004.3 1002.0 1011.9 1012.5 1003.7 974.5 977.2 1008.2 1006.7 988.4 1005.3 1013.1 1019.0 1010.7 1009.5 1012.5 1008.3 1015.4 1004.8 1009.7 1001.3 1014' 1 1013.7 1007.4 1013.8 1015.4 1004.8 996.1 1005.5 1019.0 1003.8 1004.9 1004. B 1007.6 1010.5 1013.1 1010.6 989.1 1006.1 1004.6 1003.1 1018.1 1015.5 1010.8 1010.1 1003.6 1008.3 1005.9 1015.2 1015.1 1008.1 DEC 997.0 994.8 989.0 988.9 1000.4 999.7 991.6 974.6 989.9 1000.6 1009.0 992.6 997.8 998.9 984.6 1000.5 1003.3 l:J13. 7 990.4 961.3 964.3 994.9 1001.4 1007.3 994.7 997.1 100 2. 7 992.5 995.6 998.1 1019.0 994.9 985.7 985.3 1005 '8 994.4 987.4 950.3 952.3 992.1 991.4 983.9 987.1 1016.2 999.5 1001.6 998.2 1019.0 990.5 1002.5 991.2 992.9 984.5 994.7 995.5 990.0 999.4 996.4 986 '4 974.2 985.6 1007.2 985.5 993.0 984 .4 992.8 1003.4 995.9 992.1 963.1 986,5 986.8 1019. 1008. lOCO. 0 995.2 1019.0 985.9 992.9 990.6 1004. 7 997.7 993.7 Appendix B Page 21 SNETTISHAM HYDROELECTRIC PROJECT -PRELIMINARY -INPU'::, SNETOPR6. IN RUN 6 -322000 MWH LOAD -ALL SNET Gllll USABLE -LONGOPR6. Olr., CRATOPR6 OUT JAN 975.1 973.5 961.3 962.7 981.7 986.3 975 .1 951.4 964.6 979.7 99l.8 967.9 987.6 980.5 966.0 989.5 980.9 998.8 962.0 933.2 942.2 969.1 980.4 991.1 973.7 980.2 985.5 965.0 975.7 982.9 1007. 974.8 958.3 961.2 990.9 972 ,_l 960 4 918.5 922.2 967.5 965.0 963.7 958.2 998.7 985.7 980.7 979. 999. 969.7 989.6 968.9 977.4 958.4 968.4 972.0 960.6 979.0 975.7 961.1 951.9 958' 5 990. 5 964.3 971.1 957.7 967.6 982.9 978. 1 966.0 939. 964.7 967.4 1001. 0 994.1 980.6 979.3 999.2 958.7 972.4 968.0 989.3 976.9 972.4 END OF MONTH CRATER LAKE ELEVATION (FllETl FEB 953.8 948.6 933.9 938.5 955.5 959.9 950. 926.5 937.9 957 .1 967.5 940.8 963.7 955.0 940. 964.1 953.7 990.4 933.6 905.0 922.0 942.5 952.9 965.2 987.3 957.6 960.0 936.6 951.4 961.4 991.6 955.5 933.6 935. 966 944 .5 936.3 893.9 891.9 942.4 942.6 940.3 928 .1 977.3 960.0 955 6 954.0 982.9 945.3 968.4 943.3 954.3 931.9 940.7 949.3 931.2 955.1 948.9 933.4 925.6 929.0 964.5 937.3 945.2 930.1 944.2 956.1 955.3 940.0 910.5 939.3 951.5 992.6 975 '6 960.8 955.4 985.5 937.0 964.6 950.9 963.7 952.7 949.0 MAR 929.7 925.6 904 .J 909 .o 926.5 932.0 920.4 897.6 908.4 932.6 944 '1 910.7 940.9 927.5 914.7 943.2 924.9 966.2 902.3 874.5 894.0 913.2 924.5 940.0 965.3 932.3 932.6 906.6 923.2 941. 969. 927.9 904.6 911.3 939.8 915.5 908.8 860.7 856.4 914.9 913.6 915.5 896.0 950.6 933.3 926.1 926.3 960.1 916.5 947.3 915.3 930.6 903.5 911.3 930.1 900.8 930.6 918.5 906.1 897.2 900.0 941.3 906.2 917.2 901.0 916.3 928.4 929.9 913.0 878.7 910.0 927.3 970.9 952.3 938.3 927.6 960.8 909 .1 947.5 927.1 940.3 931.8 922.2 APR 912.2 912.3 883.2 883.9 902.9 912.9 894 '5 873.4 919.0 916.2 951.6 887.2 923.5 906.8 895.3 922.2 904.0 950.6 878.3 852. 873. 891. 907.8 919.9 945.4 913.8 912.4 885.5 900.7 947.2 953.0 908.8 882.2 893.2 915.9 926.0 885.9 882 .2 833.2 895.2 890.3 896,5 867.5 950.8 913.1 903.1 905.9 946.3 893.7 928.9 955.4 913.5 882.4 888.8 911 '4 880.0 911.6 931.0 682.5 876.4 874.0 922.8 884.2 897 '7 876.7 895.7 909.7 914.4 889.7 849.4 888.3 914.4 953.4 935.7 928.1 907.4 953.9 907.0 941.2 915.1 927.5 922.5 906.1 MAY 9!2 .s 927.7 872.3 881.0 899.1 908.0 878.3 868.7 927.0 920.6 970.4 872.4 928.8 899.7 903.8 914.9 897.7 961.2 87C.1 876.7 865.2 888.1 921.3 919.9 963. a 917.9 910.4 881.7 895.0 960.1 972.0 915.3 882. 3 897.9 920.9 924.8 871.1 885.8 838 .1 906.7 879.0 888.3 876.5 960.2 924.6 910.6 912.5 962.8 883.6 931.8 958.5 904.8 884.3 887.0 913.6 888.0 927.4 939.7 878.8 892.7 868.3 933.4 879.0 895 .I 871.9 904.5 910.8 919.4 891.2 846 884.8 917. B 953.7 958.6 938.6 931.3 965.2 901.7 953.3 933.4 935.0 932.9 909.3 JUN 936.7 970.8 909 .• 907.2 932.1 921. B 886.5 896.3 951.1 947.4 1003.4 900.6 964.5 934.9 942.8 953.4 925.6 997.7 895.5 895.4 899.0 902.3 965.2 973.3 992.8 942.1 941.6 915.9 917.0 997.3 1002. 9 961.9 921.3 944.7 965.5 937.9 901.3 925.9 668.4 943.3 903.7 915.3 891.4 986.0 965.4 951.9 942.9 997.6 918.3 962.6 997.7 929.9 915.3 929.5 939.0 944.7 959.6 971.0 896.9 917.5 885.4 960.6 896.0 927.3 906.7 931.4 950.0 940.5 927.1 895.7 924.1 934.4 987.2 987.3 968.4 967.8 995.8 940.1 991.1 959.4 9i5.0 958.3 940.7 JUL 994. 1018.0 948.0 955.8 985.8 965.4 930 '3 938' 1 990.3 993.9 1019.0 927.3 993.5 973.9 997.8 994.5 970.2 10:9.0 888' 8 914.4 918.4 951.1 1004.0 1010.0 1019.0 989.8 982.5 955.7 952.2 1019.0 1006.1 1003 .l 940.7 959.5 994.5 928.4 940.5 939.3 907.9 960.4 924.6 953.4 925.2 999.0 978.2 996.1 985.3 1019.0 957.2 991.5 1019.0 948.1 939 '3 952.4 966.3 990.3 996.9 986. 919.3 948.1 910.2 1002.2 935.2 962.5 936.6 980.5 995.6 962.3 921.8 924. 965.3 983.4 992.5 1007.2 1002.3 980.5 1019. 982 . ., 1019.0 960.9 972.6 994. 970.6 AUG 1019.0 1019.0 995.0 1008.7 1019 "0 10:2.7 990.6 972.3 1019.0 :019.0 1019.0 972.6 1019.0 1003.9 1019.0 1019.0 1014.5 1019.0 929. a 94 7. 3 9'18.7 995.5 1019.0 1019.0 1019.0 1019.0 1019.0 985.9 992.8 1019.0 1019.0 1019.0 978.0 993.0 1019.0 967. 975. 966.5 950.5 1007. 952.2 996.4 991.6 1019.0 1011. 9 1019.0 1019.0 1019.0 993.4 1011.5 1019.0 979.1 990.8 996.1 995.5 1019.0 1019.0 1015.1 956.6 1004.2 949.0 1019.0 972.8 996.3 966.7 1002 .J 1019.0 1009.7 958.2 977.7 1004.3 1019.0 1019.0 1019.0 1019.0 1002.7 1019.0 1019.0 1019.0 996.4 1001.6 1014. 8 1000.6 SEP 1019.0 1019.0 1019. 1019.0 1019.0 1019.0 1002.9 1001.9 1019.0 1019. 1019.0 1003.6 1019.0 1019.0 1019.0 10:9.0 1019.0 1019.0 974.1 970.2 1001.4 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1013.8 1019.0 1019.0 1019.0 1n9.o 1000. 8 1019.0 1019.0 977.6 991.6 988.8 994.3 1019.0 980.7 1019.0 1015.3 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 996.2 1019 1019.0 1019.0 1019.0 1019.0 1019.0 994' 6 1019. 0 990.1 1019.0 1009.6 1019.0 992.2 1019. 1019. 1019.0 993.3 1012.1 1018.6 1019.0 1019. 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1019.0 1013.2 1012.9 AVG 973,5 978.4 953.3 956.6 971.7 971.0 953.9 941.6 970.2 977.0 994.4 950.5 979 0 969.4 967.0 979.4 969.3 997.8 937.7 926.1 935.4 957.7 976.8 983.6 992.3 974. 8 975. 955.6 962.8 989.8 999.9 976.0 950.9 958.8 980.8 960 1 945.8 931. 6 915.5 963.9 94 7,4 954. f 946.8 992.3 977.4 974.4 972.6 996.4 959.5 982.3 984.3 963.0 951. a 960.1 968.7 962.5 977.5 978.0 945.0 950.7 939.5 983.0 949.4 962.1 945.7 964.8 975.4 971.4 951.8 932.1 959.2 970.4 994.2 991.2 982.5 974.7 997.1 965.2 987.3 970.5 980.2 977.5 966.8 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 4946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 120000 120000 120000 120000 120000 120000 120000 1113 70 116974 120000 120000 120000 112839 120000 119284 120000 120000 120000 120000 107941 98350 118949 120000 120000 120000 120000 120000 120000 120000 120000 120000 120000 120000 111526 120000 120000 101997 104713 105236 114860 120000 102316 120000 119595 120000 120000 120000 120000 120000 120000 120000 120000 115671 120000 120000 120000 120000 120000 120000 111628 120000 118913 120000 117870 120000 118083 120000 120000 120000 10930: 120000 120000 120000 120000 120000 120000 120000 120000 120000 12000C 120000 120000 118017 Appendix B Page 22 SNET7ISHA.'1 HYDROELECTRIC PROJECT -PRELIMINARY INPUT: SNETOPR6. IN RUN 6 322000 MWH LOAD ALL SNI!T GEN USABLE -LONGOPR6 .OUT, CR.ATOPR6 .OUT END OF MONTH CRATER LAKE STORAGE !ACRE-FEET) NOV DEC JAN 116954 107880 97041 116516 106394 96361 112549 102596 90991 112939 102565 91597 120000 110217 99679 117881 1.09825 10151S 113772 104109 97031 107148 96828 86623 ll1660 102950 92414 119800 110332 98890 120000 114723 104239 115779 104812 93655 112316 108451 102036 116975 109218 99216 111830 100849 93019 116845 110255 102788 120000 111722 99351 120000 117207 109149 114059 103289 91267 101003 90990 79296 101792 nno 82863 114539 106434 94387 113542 110731 99166 120000 113666 103740 114745 106283 96439 115236 107978 99079 120000 111397 101183 114796 104755 92578 116523 106908 97264 117199 108664 100156 119771 120000 113935 116763 106442 96905 112270 101276 89640 111032 101105 90945 116271 113054 103626 116557 106054 95827 111939 101954 90561 96778 86113 73391 97874 86999 74867 114308 104500 93705 113549 104010 92615 102370 100549 92044 112794 101856 89620 116905 118511 109064 120000 109672 101277 115623 l10818 99275 115026 108758 98589 116594 120000 109884 :14352 103368 94679 118085 111338 102839 112527 103827 94296 115117 105049 97979 110707 100812 89703 117404 106295 94077 117223 10686: 95683 113877 103020 90678 117263 109579 98580 118101 107465 97262 112550 101574 90868 107300 96631 86828 112919 101260 89757 120000 113810 103356 112005 101190 92302 112591 105104 95301 112541 100764 69371 113974 104927 93745 115507 111787 100172 116869 107146 98236 115580 104480 93022 102633 91768 81780 113219 101592 92458 112428 101702 93634 111647 120000 110501 119506 114627 105891 118157 110010 99223 115659 106638 98713 115329 120000 109469 111904 10134 7 89823 114365 104999 95642 113097 103450 93908 1.17978 112477 102735 117947 108363 97776 114185 106091 95970 FEll 87693 85457 79567 81391 66442 90357 86334 76619 81141 89133 93692 82302 92023 88195 82215 92215 87611 103292 79453 67995 74783 82983 87276 92695 101908 89358 90413 80642 86613 91012 104148 88403 79433 80097 93421 83611 80521 63542 62751 82947 83046 82105 77222 97923 90383 88452 87740 100177 84116 94096 83304 87890 78762 82266 85731 76470 88244 85557 79357 76241 77581 92387 80928 84080 78024 83676 88692 88350 82012 70212 81720 66661 104836 97242 90740 88389 101219 80794 92421 86407 92011 87170 85836 77892 76242 67738 69596 76613 78600 74157 65020 69371 79058 83656 70286 82347 76990 71862 83281 75974 93121 66921 55848 63595 71265 75819 81989 92744 78927 79033 68630 75280 82458 94350 77162 67858 70509 81928 72219 69501 51420 50039 71947 71448 72206 64403 86265 79319 76426 76505 90459 72594 64909 72138 78244 67414 70528 78035 66339 76237 73407 68421 64887 66000 82526 68466 72871 66413 72522 77344 77977 71202 57491 69997 76906 95211 87027 81302 77057 90771 69655 84996 76847 82124 78703 74964 APR 70887 70927 59270 59580 67140 71141 63818 55500 73614 72462 86718 60886 75406 68736 64133 74890 67603 86248 57320 48877 55637 62497 69108 73960 84180 71509 70948 60219 66291 84861 87304 695~7 58866 63288 72342 76391 60361 58899 41621 64086 62136 64612 53611 86362 71224 67228 68372 84533 63478 77559 88358 71406 58974 61527 70542 58004 70620 78388 58987 57365 55666 75137 59687 65078 56686 64289 69895 71741 61691 47777 61327 7l744 87516 80288 77234 68943 87737 68811 82479 72045 76984 75010 66516 MAY JUN 7~003 80695 77094 95159 55141 69697 58406 68865 65637 78822 69194 74 717 57302 60599 53969 64508 76793 86505 74242 84974 94987 111769 55164 66242 77518 92369 65900 79946 67516 83122 71948 87494 65082 76247 90931 108362 54448 64217 56661 64173 52866 65599 61252 66927 74501 92689 7 3977 96270 92093 104929 73144 82857 70176 82656 58671 72344 64003 72786 90430 108119 95684 111524 72138 91217 58910 74511 65154 83874 74368 92831 75925 61170 54 744 66534 60314 76357 434 77 53893 68699 83324 57590 67467 61334 72106 56619 62569 90483 101404 75854 92766 70230 86833 71015 83175 91637 108340 59443 73321 78736 91558 89737 108418 67920 77951 59724 72108 6078: 77817 71425 81611 61186 83867 76953 90240 81892 95255 57519 64754 63072 72993 53862 60145 79341 90651 57584 64386 64262 76918 55005 68677 67785 78558 70303 85983 73774 82182 62473 76822 46656 64273 59936 75623 73123 79744 87618 101874 89786 101922 81436 94104 78528 93839 92679 107084 66685 82051 87436 103746 79357 90116 80013 96999 79174 89658 69871 62790 JUL 106191 119468 85208 66551 101304 92760 78103 61253 103204 105687 120000 76916 105463 96538 108439 106125 94891 120000 61529 71774 73367 86502 112068 115245 120000 102929 99995 88515 86957 120000 114277 111621 82264 90195 106125 77375 82216 81733 69178 90569 7585: 87495 76082 109267 98289 107263 101112 120000 89162 104028 120000 85236 81719 87059 93178 103234 107854 101476 73710 85258 70065 111154 80084 91507 80625 99213 106923 91430 74726 75797 92720 100346 104719 113783 111215 99209 120000 100067 120000 90802 95962 106238 95078 AUG 120000 120000 106530 114588 120000 116668 103403 95831 120000 nooco 120000 95961 120000 112077 120000 120000 117658 120000 77939 64927 98499 106871 120000 120000 120000 120000 120000 101359 104942 120000 120000 12 0000 98200 105126 120000 93809 97088 93241 86239 113850 86986 107496 10412 7 120000 116288 120000 120000 120000 105371 116063 120000 98646 103525 107270 106820 120000 120000 117960 88920 112208 85586 120000 96029 107419 93366 111184 120000 115109 89596 98087 112287 120000 120000 120000 120000 lll411 120000 120000 120000 107501 110840 1177 B 7 110399 SEP 120000 120000 120000 120000 12 0000 120000 111546 110977 120000 120000 120000 111920 120000 120000 120000 120000 120000 120000 96614 94896 110740 120000 120000 120000 120000 120000 120000 117250 120000 120000 120000 120000 110404 120000 120000 98049 104106 102516 105979 120000 99286 120000 118031 120000 l20000 uooco 120000 120000 120000 120000 120000 107356 120000 120000 120000 120000 12 0000 120000 106194 120000 103074 1.20000 115047 120000 104556 120000 120000 120000 105283 116377 119/9:1 120000 120000 120000 120000 120000 120000 120000 120000 120000 120000 ll6972 116570 AVG 98020 100301 89107 90673 97321 96905 89181 83804 96219 99550 107482 87844 100064 96149 95189 100487 96345 109026 82256 77032 80869 91051 99577 102645 106110 98418 98617 89980 93131 105242 110083 99181 87803 91071 101164 9l432 85127 79085 73179 93566 86165 88719 86411 106315 99589 98512 97524 108469 91657 101601 102717 92733 88260 92085 95592 93223 99798 99730 85238 87868 82993 102273 87309 92750 85502 93996 98884 96901 88091 80179 91722 96357 106993 105839 101952 98199 108691 94261 103657 96127 100677 99566 94949 2/25/97 19H l9l5 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 :970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 7132 8809 2089 6403 5716 2788 3108 0 2902 4101 5603 5635 2482 16436 4359 9421 0 2296 17679 13579 4019 8774 9596 1695 5962 8392 8686 11180 0 6713 876 0 0 0 8088 0 1446 0 4513 3893 4711 9008 10949 4093 9357 9907 0 12853 4378 955 2955 7054 1288 0 8915 0 4252 2505 0 12028 5164 1311 4344 7383 5730 10302 2930 13541 5064 6246 4379 1264 3033 3909 4685 NOV 0 4444 0 0 0 0 0 5835 0 0 0 2628 4586 G 0 0 4701 c 1664 0 0 0 0 0 0 0 0 0 0 0 84 0 0 0 0 0 0 791 0 0 0 0 0 0 0 0 0 302 DEC 0 0 0 0 0 291 0 0 0 6281 0 0 0 0 0 0 0 2052 0 10689 0 0 0 236 Appendix B SNEITISHAM HYDROELECTRIC PROJECT PREL!~!NARY -!NP:JT, SNETOPR6 . IN RUN 6 -322000 MWH LOAD ALL SNET GEN USABLE LONGOPR6.0UT, CRATOPR6.0UT ENERGY ASSUMED TO BE USABLE FROM CRATER LAKE SPILL (MWH) JAN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FEB 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MAR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 APR 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 MAY 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUN 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 JUL 0 0 17025 0 6258 0 2189 0 0 0 6312 0 0 0 0 0 0 0 8086 0 0 6842 0 0 0 0 0 0 0 0 0 0 1757 0 4146 0 0 642 AUG 4341 18329 8612 581 6809 19678 0 388 3876 3081 0 18637 0 5226 15367 10180 19062 2970 0 :1091 11.935 4719 0 0 3564 0 0 0 0 2356 0 2390 252 20335 13011 0 0 0 7845 5713 0 3961 0 0 0 4385 0 239 207 7722 3888 14179 2489 13666 0 0 3306 Page 23 SEP 7237 13419 5868 7367 14410 11776 0 l3957 18472 18322 0 8258 4941 10772 10818 9767 11783 0 2775 15941 14133 15858 15493 10716 0 1863 14541 12948 1566E 0 4356 16657 0 0 0 10094 4801 0 13600 8712 12650 15310 14417 3952 9451 5602 0 1834 6499 5738 10767 15230 12950 0 5502 0 15748 0 3509 0 5140 12989 12614 0 0 16502 2960 16162 9471 7458 16110 17241 16556 736 9716 0 7661 TOTAL 18711 40556 7958 13769 33181 14564 3108 0 14538 28183 64961 5603 8645 10576 14648 16381 28832 45623 9421 0 0 2775 23463 51879 41807 38575 24123 9596 3558 37906 33566 29071 11180 4356 26935 876 0 10094 8088 4801 1446 15956 13309 18932 20272 58128 14902 13344 34812 9907 1834 19352 10117 19568 23898 20005 1288 5502 8915 20499 4252 3509 2505 5140 29403 17838 1311 0 4344 24125 10948 34186 16288 20999 4 7799 25976 38746 2000 12749 3909 16831 ·- 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 :956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 13486 16138 9639 13985 12987 10478 10898 7324 7191 10478 11423 13509 7445 13344 7614 10059 23691 11651 17209 6535 6585 7300 9687 25394 20240 11228 15551 17168 9093 12404 15085 16204 18045 6787 14038 8350 6458 7386 7226 587S .15416 6508 9382 7573 11994 11100 12276 15929 18231 11382 16881 17661 6334 20366 12242 8500 10895 14471 9064 6630 17147 6464 :J.2149 7195 10129 6618 18720 12122 8829 6959 11862 14696 13905 16563 9592 20262 12375 13631 11553 8823 10009 10820 11932 NOV 7987 8132 8558 8519 12565 8475 8632 8064 8305 8113 14181 8416 8129 8353 8550 8347 11146 12815 8622 7826 7349 8286 8335 13006 8244 8283 9754 8457 8362 7962 8194 8278 8514 7743 8052 8444 7679 8137 8042 7771 8661 7145 8554 8188 8387 8449 8338 7928 8442 8182 8532 8496 8247 8489 8366 8452 8384 8485 8531 7921 8651 8857 8700 8215 8706 8250 8223 8286 8546 7917 8626 8408 8756 8286 8138 8216 7994 8361 8387 8357 8095 8440 8576 DEC 9612 9744 9995 10336 10063 10176 10393 9788 9634 10123 9978 10048 9939 9783 10429 9782 10113 9925 10430 9520 8789 9803 10319 9812 9803 9877 9640 10033 9787 9485 !0692 9920 10624 9503 9908 9977 9432 10035 9662 9425 10458 8646 l0401 10242 10033 10580 10123 16917 10317 9631 10111 9963 10001 10332 9997 10172 9905 10295 10287 9693 10561 9882 10380 9795 10695 9726 10238 9960 10418 9703 10529 10072 13696 ~0197 9933 9931 2172: 10121 10.057 10046 9819 9956 10267 Appendix B SNETTISHAM HYDROELEC7RIC PROJECT PRELIMINARY -INPUT, SNETOPR6.IN Ru~ 6 322000 MWH LOAD AL~ SNET GEN USABLE LONGCPR6.0UT, CRATOPR6.CUT JAN 10030 10ll0 10426 10753 10436 103"16 10872 10303 9966 10517 10375 10382 10179 10131 10837 10072 ~0544 10300 10863 9942 9216 10175 10702 10223 10169 10166 10082 10439 10177 9970 10463 10380 11119 9877 10219 10391 9821 10545 10149 9811 10902 9044 10913 10580 10274 10988 10540 10415 10613 9966 10505 10236 10506 10743 10405 10648 10291 10691 10743 10154 10960 10312 10921 10145 11088 10153 10596 10115 10768 10138 10797 10533 11804 1:)460 10323 10358 10543 10568 10361 10460 10182 10301 10397 NET ENERGY FRCM CRATER LAKE UNIT IMWH) FEB 9576 9569 9926 10106 9901 9787 10263 9852 9492 10004 9827 9793 9291 9615 10058 9543 9948 9537 10343 9613 9011 9711 10106 9632 11169 9682 9487 9953 9637 9167 9749 9872 10638 9424 9676 9874 9438 10463 9815 9223 9748 8527 10465 9986 9652 10452 10016 9675 10097 9097 9790 9569 10123 10174 9695 10194 9724 10084 10228 9612 10380 9765 10276 9579 10598 9805 10027 9467 10195 9757 10054 9797 11246 9858 9587 9824 10097 9570 9700 9293 9610 9791 98-41 9526 9389 10044 10227 9975 9772 10354 9957 9624 9875 9729 9926 9156 9658 9971 9554 9900 9473 10388 9947 9167 9797 10087 9591 10737 9677 9451 10075 9651 9024 9635 9838 10546 9586 9666 9913 9612 10466 10203 9210 9779 8515 10693 9978 9655 10452 9983 9471 9960 8966 9805 9457 10251 10307 9416 10282 9655 10139 10067 9709 10351 9653 10382 9639 10548 9721 10051 9418 10346 10031 10143 9430 10870 9621 9437 9741 9774 9609 9458 9111 9525 9697 9823 APR 7812 7448 8296 8602 8211 8073 8781 8282 9897 7956 8919 8739 7805 7718 7759 7917 7980 7668 8627 7068 7662 8021 8369 7615 8540 7907 7270 8~43 8175 8385 7554 8171 8777 7504 7968 10079 8124 14458 8928 7660 8392 7183 9114 9168 7726 8628 8061 7415 8288 7284 10895 8000 8420 8913 7836 8664 7915 9645 8646 7687 8600 7846 8292 7440 8663 8322 7867 7835 8Sl3 8366 8051 7743 8847 7498 7908 7839 8062 8215 7899 7461 7611 8248 8267 MAY 6604 6228 7063 7247 7056 6965 7255 6673 8360 6720 7383 7220 6736 6421 6318 6569 6683 6559 6783 6921 5709 6560 6689 6461 7314 6545 6224 6718 6759 6778 6476 6652 6684 6295 6433 7908 6774 8764 6617 6~72 6656 6085 7228 774S 6463 7387 6749 6409 6722 6311 9372 7002 7063 7082 6590 6951 7219 7714 700~ 7144 7751 6862 6746 6152 6861 6610 6397 6737 6949 7555 6364 6273 7633 6815 6801 6687 6933 6378 6642 6893 6:28 6779 6855 JUN 4927 5032 5381 5578 5528 5556 5242 5444 6231 5323 5653 5582 5388 5041 5320 5430 5312 5163 5142 5316 4474 5154 5624 4902 5652 5124 4997 5275 5045 5355 5289 5316 5317 5274 5023 5702 5785 5697 5059 4749 5::..47 5124 5509 5897 4995 5671 5504 4855 5354 5176 6665 5592 5305 4779 5431 5240 5720 6084 5291 5402 5382 5366 5211 5128 5693 5251 5248 5366 5493 5377 SOB! 5016 6001 5313 5446 5596 5484 4870 5387 5328 5047 5526 5351 JUL 4905 5075 5501 5581 5508 5782 5514 5767 6058 5577 22663 5300 5524 5131 5624 5677 5500 11535 3655 5086 4249 4993 5570 5171 7930 5054 5038 4598 5041 10840 4848 5183 4696 4763 4829 4300 5983 5220 4797 4366 4881 4941 5036 5594 4516 5385 5375 12713 5367 5017 12952 5098 4805 4591 5217 5054 5986 5178 4992 5163 4902 5406 5057 5056 5807 5095 4973 4937 4558 5145 5536 5170 5381 5187 5565 5114 6875 4759 9627 4875 4240 6207 5802 AUG 9315 23482 5652 5608 14326 6008 5715 5959 6495 12650 25471 5460 6328 5230 9632 9014 5670 24169 4496 5023 4741 5128 10774 20821 15782 24716 8189 5069 5278 16200 17263 10133 4898 5143 8756 4712 6094 5652 5143 4902 5360 5074 5343 8088 4887 7922 san 25471 5634 5230 18890 5237 5186 4862 5635 13217 11743 5294 5054 5088 5184 9269 5174 5091 6086 5331 9497 5159 5304 5280 5641 5453 5'751 13332 9426 5397 19523 7256 19132 5421 4752 6506 8695 MINIM1J1.! ANNUAL CRATER LAKE GENERATION 822 86. 2l>D MIN A.'Th'UAL CRATER LAKE Gl!N • 87581. Page 24 SEP 13314 19319 11964 13415 20454 18037 6138 6587 20423 24649 24649 6307 14633 10795 17115 17279 15940 18015 5272 5729 5335 8983 22159 19827 2liBl 21889 16499 5849 7409 20552 19569 22017 5344 10189 22679 4753 6003 6052 5629 16071 5642 10788 6051 19805 15258 19366 21570 20672 9890 15088 12224 5798 7368 11905 11535 TCTAL 107096 129666 102443 1.09957 :27006 109466 100057 93899 111677 121983 160249 100682 100553 101219 109226 109243 122426 136811 101831 88525 82286 93910 118421 142453 137362 130149 112183 101777 94415 126123 124818 121965 105201 92089 11724 7 94402 91203 102874 91271 95234 101040 87581 98688 112847 103840 116381 114366 147869 108914 101330 136621 102108 93610 112541 102335 17198 114572 213 96 118834 19439 117519 5414 95317 11748 95950 6137 106006 21631 111315 5831 99118 9439 92872 6232 101106 10901 95783 19335 121173 18741 1.08144 6046 95965 5558 91786 6304 98987 22000 114589 9655 113545 21891 125020 14970 107127 l3418 112385 21957 141339 22861 116198 22839 131042 6159 92225 15118 100137 5835 98107 13654 109459 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1911 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 58727 40076 31627 38234 39021 30840 32082 22806 27450 29758 34052 37226 22056 33324 21851 31243 64618 33717 44642 33179 21601 28431 30317 52830 65480 37554 55868 46833 30226 50074 57301 43022 63285 27904 39055 31842 25561 22605 22094 48176 50719 21662 23706 22790 35561 40685 35043 48052 55212 35135 46572 45178 42127 48564 28437 24812 24812 44111 26935 31216 36441 38835 31614 27654 33749 37805 63400 46462 33696 22326 36664 39058 30648 6:803 46650 65502 33821 36115 39275 28890 36552 47714 31961 NOV 23480 2 3350 24289 24183 38060 24305 24605 24173 24227 28513 34519 24590 24383 24093 24227 24271 30:5: 34600 24455 24592 24036 24275 23984 35619 23492 23671 30659 24231 24147 23048 23555 23883 23943 25272 23705 24342 31ll5 24802 244l2 25230 24427 24082 24530 25242 25993 24142 24066 2302G 24059 24146 24184 24450 23939 23771 24238 24034 24188 24067 24459 24085 24756 28216 24425 24148 24730 23871 23583 23803 24615 24251 24411 23587 24529 23378 23616 23791 23497 23423 23651 24134 23583 24193 25054 DEC 28152 28018 28980 28872 28433 28998 29305 294?8 28918 28640 28144 29289 29077 28780 28917 28962 28595 28226 29151 29291 28721 28967 28668 28084 28164 28347 28150 28921 28836 27109 28504 28565 28626 28812 28382 29035 29284 29501 29101 28248 29122 28769 29228 28901 28663 28831 28752 33876 28745 28507 28873 29146 28622 28449 28928 28720 28878 28754 29155 28172 29459 28194 29120 28836 29433 28552 28257 28482 29315 28942 29106 28261 31232 28047 28291 28470 38692 28093 28326 28822 28256 28883 28947 Appendix B SNETTISH&~ HYDROELECTRIC PROJECT • PRELIMINARY -INPUT, SNETOPR6.IN RUN 6 322COC MWli LOAD ALL SNET GEN USABLE -LONGOPR6.0UT, CRATOPR6.0UT TOTAL NE~ ENERGY FROM BOTH LONG LAKE AND CRATER LAKE (MWHl JAN 28690 28569 29436 29339 28943 29452 29729 29884 29380 29130 28682 29715 29523 29255 29379 29420 29089 28756 29590 29716 29203 29424 29155 28629 28700 28866 28688 29383 29306 28291 28759 29062 29111 29284 28897 29486 29710 29911 29550 28777 29564 29246 29659 29365 29150 29301 29230 28264 29224 29010 29339 29585 29113 28958 29389 29201 29344 29232 29594 29249 29868 28728 29562 29306 29844 29051 28784 28987 29738 29402 29549 28788 29658 28595 28815 28976 28105 28637 28841 29294 28184 29348 29191 FEB 26382 26270 27075 26984 26617 27089 27346 27490 27022 26790 26375 27333 27156 26907 27022 27060 26753 26444 27211 27334 26858 27063 26813 26325 26392 26545 26380 27025 26954 26012 26446 26727 26779 26934 26574 27121 27329 21515 27180 26463 27193 26898 27281 27008 26809 26949 26884 25987 26878 26679 26985 27213 26775 26631 27031 26857 26989 26885 27221 26900 27475 26418 27192 26954 27453 26717 26410 26658 27355 27043 27180 26473 21281 26295 26498 26648 26396 26333 26528 26942 26470 26993 26853 25519 25391. 26310 26207 25788 26326 26620 26784 26250 25985 25511 26604 26402 26118 26249 26293 25942 25589 26472 26606 26062 26297 26011 25454 25530 i25705 25517 26253 26172 25096 25592 25913 25972 26149 25138 26362 26600 26812 26430 25611 26445 26108 26546 26234 26007 26167 26092 25068 26085 25858 26207 26468 25967 25803 26260 26061 26212 26093 26476 26111 26167 25559 26443 26172 26741 25901 25619 25834 26629 26273 26429 25623 26545 25419 25651 25823 25535 25463 25685 26159 25619 26216 26056 APR 20278 20130 21.193 21073 20589 21212 21551 21742 21124 20817 20269 21534 21299 20971 21123 2ll73 20767 2C359 21381 21536 20906 21178 20848 20203 20291 20493 20275 21127 21033 19789 20362 20734 20801 21006 20532 21253 21528 21774 21332 20384 21349 20959 21466 21105 20842 21027 20940 :9756 20932 20670 21014 21375 20791 20606 21135 20905 21079 20942 21385 20963 21722 20325 21347 21033 21692 20720 20394 20643 21562 21151 21331 20398 21465 20162 20411 20629 20296 20213 20470 21018 20393 21085 20900 17748 11591 18123 18596 18079 18743 19105 l9308 18649 18322 17738 19087 18837 18487 18648 18702 18269 17835 18924 19089 18418 18107 18355 17668 17762 17977 17745 18653 18553 17226 17838 18234 18306 18524 18018 18788 19081 19343 18872 17861 18890 18474 19014 18629 18349 18547 18454 17192 18446 18166 18596 18918 18301 18098 18662 18416 18602 18456 18928 18418 19287 17798 18888 18553 19255 18219 17871 18131 1.9117 18618 18871 17816 19013 17625 17911 18122 17768 17679 11953 :18537 11871 18608 18411. 14 722 14561 15724 15593 25062 15744 16116 16324 15648 15312 14712 16097 15840 15481 15647 15702 15258 14812 15929 16099 15410 15707 15346 14640 14737 14958 14720 15652 15548 14187 14815 15222 15295 15519 15000 15790 16091 16360 15876 14839 15895 15468 16022 15621 15340 15542 15447 14151. 15439 15152 15593 15923 15290 15082 15661 15409 15599 15449 15934 15472 16302 14774 15892 15549 16270 15206 14849 15121 l6l.28 15617 15875 14854 16021 14596 14890 15107 14743 14652 14933 15532 14849 15605 15403 JUL 15473 23584 16551 16411 15839 16574 16974 17198 16470 16108 46990 16953 16677 16290 16468 16528 16050 36310 16773 l6955 16214 16533 16145 16456 11672 15727 15470 16414 16363 52037 26778 17588 16090 16332 17736 16623 16941 11236 16716 15599 16736 16276 16873 16448 18406 16356 16254 53239 16245 15936 23227 16766 16085 15860 16484 16212 16418 16256 16778 16280 17174 15529 16733 16363 11139 15994 15610 15903 16987 16501 16714 15615 16872 15331 15654 15887 29386 15397 26680 16345 11992 16424 18528 AUG 49777 68722 17310 21372 40679 17330 17685 17884 22167 35673 65467 17666 23017 27517 34533 28337 20679 65403 17506 17669 20318 24829 40697 58949 44331 6903l 38680 17827 17143 56081 57184 42487 16901 20350 44218 17373 17661 17918 17456 34069 17474 25187 17715 31381 42893 36343 28611 70711 17038 30270 52050 17501 16896 21704 l725Cl 52601 30177 33589 17511 31272 17863 38914 17471 25336 17832 20985 46989 30371 11696 11266 20061 33369 35126 37246 33215 18534 60668 50631 58200 17127 34811 17197 31486 MINIMUM ANNUAL SNETTISHAM GENERATION 272959. 2ND MIN ANNUAL SNET G~ 273070. Page 25 SEP 39381 58810 444 03 48020 59464 53307 21344 19288 51859 66042 64278 19074 43676 46611 48608 46142 47087 49220 19015 19077 35610 34389 59957 63608 62798 54439 54145 32900 47991 52911 39755 54801 33806 46243 63142 34904 19069 19321 24045 49288 18885 42794 31802 57689 35917 42013 58021 48273 41458 58869 31363 22360 46100 55686 51850 44779 62118 47406 30478 37659 19267 63020 32160 41949 19237 47198 45929 54861 19104 39161 26393 65780 25294 65671 58751 46363 65738 66642 57345 48291 58899 31702 44058 TOTAL 348332 375073 3C1621 314885 356575 309921 282462 272959 309164 341091 406739 285167 298003 313894 312671 313832 343258 381271 291054 281143 283357 295799 336295 388526 375350 363313 356896 305279 302271 392461 366888 346240 318922 302329 350996 292918 279975 273105 273070 334543 296700 295924 283843 320425 323930 325905 327861 407588 319760 328400 344063 294884 310011 335213 305325 328007 325016 331240 284855 306456 286381 346370 290841 302052 283375 310220 357754 335268 281942 286672 292585 33 9684 303684 364175 340313 333853 385250 353279 361894 301092 334083 303969 322852 2/25/97 YEAR 1914 1915 1916 19l7 l918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 65255 46775 37096 43842 45190 36288 37137 27641 33000 35663 40591 42301 27402 39051 27402 36736 70581 40150 49894 38252 27402 33918 36186 59445 7l993 43833 62399 52378 35881 57168 63732 49023 69208 33590 45290 37242 30642 27402 27402 54581 56008 27402 28860 28362 41436 46346 40805 55184 60983 41209 52179 50437 48055 54713 33974 30615 30413 49871 32182 36952 41299 45309 36905 33508 38641 43821 69794 52568 38739 27845 41974 45447 35803 68465 53001 71624 40333 42718 45580 34563 42946 53309 43770 NCV 28465 28465 28465 28465 42770 28465 28465 28465 28465 33022 39511 28465 28465 28465 28465 28465 34703 39512 28465 28465 28465 28465 28465 40729 28465 28465 35645 28465 28465 28465 28465 28465 28465 29613 28465 28465 34994 28465 28465 30120 28465 28465 28465 29496 30479 28465 28465 28465 28465 28784 28465 28465 28465 25465 28465 28465 28465 28465 28465 28465 28465 33159 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 29490 DEC 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33538 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 39460 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 35268 33263 33263 33263 43785 33263 33263 33263 33263 33263 33494 Appendix B SNETTISIIAM HYDROELECTRIC PROJECT PRELIMINARY INP!IT, SNETOPR6. IN RUN 6 • 322000 MWH LOAD ALL SNET GEN cSABLE LONGOPR6.0UT. CRATOPR6.0liT TOTAL NET ENERGY FROM SNETTIS!'.AM PLcS AELP HYDRO (MWH) JAN 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 FEB 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 MAR 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 APR 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921. 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 2592::. MAY 23?64 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 2376< 23764 23764 23764 23764 23764 23 764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23 764 23 764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23 764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23 764 23764 23764 23764 23764 JUN 20898 20896 20898 20898 20898 20898 20898 20899 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 2:1898 20898 20898 20898 20898 20898 20898 20898 20898 20899 20898 20898 20898 20898 20898 20898 20898 .JUL 22121 30406 22121 22121 22121 22121 22121 22121 22121 22121 53649 22121 2212l 22121 22121 22121 22121 42862 22121 22121 22121 22121 22121 23193 24305 22121 22121 22121 22121 59261 33327 23699 22121 22121 24085 22121 22121 22121 22121 22121 22121 22121 22121 22121 24389 22121 22121 60501 22121 22121 28937 22121 22121 22121 22121 22121 22121 22U1 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 36012 22121 33101 22121 24504 22121 24443 AUG 55673 74772 22250 26437 46250 22250 22250 22250 27180 41006 71372 22250 27905 32749 39546 33298 26064 71214 22250 22250 25557 29785 45998 64924 50213 74702 44578 22835 22250 62488 62992 47907 22250 25485 49849 22250 22250 22250 22250 39854 22250 30371 22370 36419 48199 41456 33875 77152 22250 35756 57114 22250 22250 33257 22250 57841 35835 38790 22250 36453 22250 44821 22250 30443 22250 26419 52764 35892 22250 22250 24856 39139 39782 43263 38951 24063 66544 56595 63895 22250 40592 22250 36732 MINIMUM ANNUAL SNE":" , AELP HYDRC GENERATION 322000. 2ND MIN ANNUAL SNET + AELP HYDRO GEN 322239. Page 26 SEP TCTAL 45170 414875 64744 443352 49248 357372 52989 372044 64928 419451 58133 365448 25821 333985 23570 322239 56775 365732 71273 40:276 70070 473384 23570 336899 48413 352497 51684 372261 53526 369251 5l008 369818 52368 404028 54920 446848 23668 344589 23570 332850 40749 342485 39249 351729 65156 396118 69468 455949 68568 441735 60001 427313 60530 423465 37813 361804 53000 3 59909 59195 464768 4545l 432433 60116 407400 39053 379288 51279 360280 68665 414544 39687 347956 23570 331770 23570 322000 28748 327177 54962 399829 23570 350606 47878 354429 36368 336375 62625 377214 41122 383816 47028 383608 63131 386588 54590 480281 46570 378581 64249 390310 36330 401216 27018 348482 51351 370434 61133 397879 56754 361755 49920 387153 67080 382106 52508 389946 35126 338336 42741 364923 23570 335897 68755 412357 36848 344780 46957 359686 23570 333239 52527 371544 51593 422929 60271 397508 23570 333337 44050 342922 31097 346704 7144C 404803 29861 356229 71573 432078 64377 405106 51786 396251 71502 451571 72491 420580 62931 432163 53316 358906 64563 399261 36658 360994 49203 382061 2/25/97 YEAR 1914 1915 1916 1917 1918 1919 1920 1921 1922 1923 1924 1925 1926 1927 1928 1929 1930 1931 1932 1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 1945 1946 1947 1948 1949 1950 1951 1952 1953 1954 .1955 1956 1957 1958 1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 1969 1970 1971 1972 1973 1974 1975 1976 1977 1978 1979 1980 1981 1982 1983 1984 1985 1986 l9S7 1988 1989 1990 1991 1992 1993 1994 1995 AVG OCT 65255 46775 37096 43842 45190 36288 37137 27641 33000 35663 40591 42301 27402 39051 27402 36736 70581 40150 49894 38252 27402 339l8 36186 59445 71993 43833 62399 52378 35881 57168 63732 49023 69208 33590 45290 37242 30642 27402 27402 54581 56008 27402 28860 28362 41436 46346 40805 55184 60983 H209 52179 50437 48055 54713 33974 30615 30413 49871 32182 36952 41299 45309 36905 33508 38641 43821 69794 52568 38739 27845 41974 45447 35803 68465 53001 ?:C624 40333 42718 45580 34563 42946 53309 43770 NOV 28465 28465 28465 28465 42770 28465 28465 28465 28465 33022 3951: 28465 28465 28465 28465 28465 34703 39512 28465 28465 28465 28465 28465 40729 28465 28465 35645 28465 28465 28465 28465 28465 28465 29613 28465 28465 34994 28465 28465 30120 28465 28465 28465 29496 30479 28465 28465 28465 28465 28784 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 33159 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 28465 29490 Appendix B SNETTISHAM HYDROELECTRIC PROJECT -PRELIMINARY -INPUT: SNETOPR6, IN RUN 6 -322000 MWl! LOAD -ALL SNET GEN USABLE -LONGOPR6.0UT, CRATOPR6.0UT TOTAL NET llNERGY FROM ALL HYDRO PLUS THERMAL RBSOL'RCES (MWHI DEC 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33538 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 39460 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 33263 35268 33263 33263 33263 43785 33263 33263 33263 33263 33263 33494 JAN 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 33295 FEB 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30654 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 30397 APR 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921. 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 25921 MAY 23764 23764 23764 23764 23764 23764 23764 23764 23 764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 23764 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 20898 JUL 22121 30406 22121 22121 22121 22121 22121 22121 22121 22121 53649 22121 22121 22121 22121 22121 22121 42862 22121 22121 2212j. 22121 2n21 23193 24305 22121 22121 22121 22121 5926:1. 33327 23699 22121 22121 24085 22121 22l21. 22121 22121 22121 22121 22121 22121 22121. 24389 22121 22121 60501 22121 22121 28937 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 22121 2212l 36012 22121 33101 22121 24504 22121 24443 At:G 55673 74772 22250 26437 46250 22250 22250 22250 27180 41006 71372 22250 27905 32749 39546 33298 26064 n2:4 22250 22250 25557 29785 45998 64924 50213 74702 44578 22835 22250 62488 62992 47907 22250 25485 49849 22250 22250 22250 22250 39854 22250 30371 22370 36419 48199 41456 33875 77152 22250 35756 57114 22250 22250 33257 22250 57841 35835 38790 22250 36453 22250 44821 22250 30443 22250 26419 52764 35892 22250 22250 24856 39139 39782 43263 38951 24063 66544 56595 63895 22250 40592 22250 36732 Page 27 SE~ TOTAL 45170 414875 64744 443352 49248 357372 52988 372044 64928 419451 58133 365448 25821 333985 23570 322239 56775 365732 7127 3 4Cl276 70070 473384 23570 336899 48413 352497 51684 372261 53526 369251 51008 369818 52368 404028 54920 446848 23668 344589 23570 332850 40749 342485 39249 351729 65156 396118 69468 455949 68568 441735 60001 427313 60530 423465 37813 36l804 53000 359909 59195 464768 45451 432433 60116 407400 39053 379288 51279 360280 68665 414544 39687 347956 23570 331770 23570 322000 28748 327177 54962 399829 23570 350606 47878 354429 36368 336375 62625 377214 41122 383816 47028 383608 63131 386588 54590 480281 46570 378581 64249 390310 36330 401216 27018 348482 51351 370434 61133 397879 56754 361755 49920 387153 67080 382106 52508 389946 35126 338336 42741 364923 23570 335897 68755 412357 36848 344780 46957 359686 23570 333239 52527 371544 51593 422929 60271 397508 23570 333337 44050 342922 31097 346704 71440 404803 29861 356229 71573 432078 64377 405106 51766 396251 71502 451571 72491 420580 62931 432163 53316 358906 64563 399261 36658 360994 49203 382061