HomeMy WebLinkAboutLarsen Bay Feasibility Study supplemental Hydrology Aug 1983FEASIBILITY STUDY FOR LARSEN BAY HYDROELECTRIC PROJECT SUPPLEMENTAL DATA REPORT: HYDROLOGY Prepared For: Alaska Power Authority Prepared By: OOWL Engineers AUQust 1983 W.O. 11013470 TABLE Of CONTENTS Purpose •. 1 Location................................................ 1 Drainage Are a ••••••••••••••••••••••••••••••••••••••••••• 3 Gage •••.. ............................................... 3 Reference Marks ......................................... . 4 Disch arge Measurement s ....••.•••••.•..•.••..••..••...••. 5 Rat inq Curve............................................ 6 Channel. ... . . .. . . . . . . . . .. .. . . . . . . . .... ... . . . . ... .. .. .. . . 8 Control. . . . . .. ... .. .. .. .. .. .•. . .. ..... . ..... .. . .. . .... .. 8 R em ark s,. . • • • • • • • • • • • • • • • . • • . • • • • • • • • • . • . . • • . • . • • • • • • • • • • 9 Appendix A Appendix B Appendix C APPENDICES Discharge Rating Curve Measurements ..•.•.•• Printout of -Hour Stage charges •••. Discharge Measurements Data and Corresponding 2 and Dis- 4- Digital Gage Specifications .•.........•...• 1 2 18 86 LIST Of fIGURES Fig ur e 1 -Proj ect Loc at io n Map......................... 2 Figure 2 -Discharge Ratinq Curve Humpy Creek La rsen Bay, Al a sk a. . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 3 -1982 Hydrograph of Humpy Creek .•.••.........• 11 LIST Of TABLES Table 1 -Summary Streamflow Data, 1982. Humpy Creek, Larsen Ray, Alaska •...••.•.•...• 10 Pur ose: LARSEN BAY Streamflow Data, Humpy Creek The purpose of this effort is to collect streamflow data for Humpy Creek as part of the Larsen Ray Hydroelectric Project Feasibility Study. The U.S. Geoloqical Survey has also collected a year of streamflow data on Humpy Creek at a location one mile upstream of the hydroelectric qaqinq station. The streamflow data presently being gathered will supplement the hydrology study completed for the feasibility of hydropower development. Streamflow data collection began on December 28.1981. This report includes a daily stream discharge summary table as well as stage and discharqe records for two-hour periods for the full 1982 calendar year. Gaging equipment specifi- cations are attached to the report as Appendix C. Location: The gage is located on the left bank of the creek, 0.5 miles upstream from the mouth and 0.4 miles south of Larsen Bay, 200 fee t below the old dam, La tit u de 57° 31 ' 56" , Lon g it u d e 153°59'08", in NE 1/4 SE 1/4 sec. 31, T.30S., R.29W., Kodiak C-6 Quad (see Figure 1 -Location Map). " J U YAK , SAY 8 SCALE 1-r.pr •••• t. 0.87 ml' LOCATION MAP NOT TO ICALI; FIGURE Draina e Area: The drainage area is 6.37 square miles at the stream gaging site. No glaciers exist within the basin. Ga e: Gaging equipment consists of a digital recorder/sensor (Omnidata Datapod) and a staff gage. Digital Gaqe: The digital gage is an Omnidata Datapod coupled with a small piezo-electric pressure transducer and a thermistor temperature probe. The datapod is an ultra low power microprocessor controlled recorder with several advan- tages. The device contains a battery supply, an analog to digital converter (12-15 bits), a microprocessor, a non- volatile storage module and a clock with an accuracy of several minutes per month. The transducer is housed inside a cylindrical brass casing which is secured to the streambed by driving a steel rebar through a hole in the casing. A cableway extends to the recorder on the streambank. The recorder is set to sample the pressure and temperature every five minutes. The average of the 5-minute readings are r e cor d e d eve r y t wo h 0 u r s t h r 0 ugh J un e 1 98 2 and eve r y f 0 u r hours through December 1982 in an 8-bit format. Following - 3 - the assembly of the datapod, a digital stage recorder was installed on December 28, 1981. Staff Gage: The staff gage is a rigid, precisely graduated, porcelain enameled iron plate securely fixed to a fence post driven into the streambed. It was installed on Humpy Creek during an initial site visit for the hydroelectric feasibil- ity study. Reference Marks: RM-1 (base) The 7th wood-stave aquaduct pile downstream from the cannery dam is the reference mark. The top of the wooden pile is at an assumed elevation of 100.00 feet. Elevation of transducer: 94.00 feet The gage was moved to an upstream location 100 feet from the dam on May 5, 1983. New elevation of transducer: 105.88 feet -4 - RP-1 The top of a 2 inch stake on the right bank 10 feet from the gage is the reference point. Elevation: 108.92 feet Discharge Measurements: Continuous measurements of stream discharge are obtained through collection of stage data at the gaqing station. The staqe of a stream is the height of the water surface above an established datum. The stage data on Humpy Creek is collected every two and four hours by an Omnidata Datapod digital recorder. In stream gaging procedures, stage data is used as the independent variable in a stage-discharqe relation to derive discharges. It is, therefore, normal practice to establish a relationship (rating curve) between the staqe at the gaqing station and the discharge. This relationship depends on the shape of the cross-section and the rouqhness of the streambed. Therefore, the relationship has to be established empirically. As part of establishing the rating curve relationship, dis- charge measurements were taken at the gaging station usinq a Marsh-McBirney Model 201 flow current meter. The stage of -5 - the stream was also noted during discharqe measurements and is provided below alonq with the discharge measurements. Date Discharge (cfs) Gage Height (ft)(Stage) 12/29/81 10.5 01/23/82 6.2 Ice 03/31/82 6.2 1. OS 06/14/82 27.7 1. 64 10/26/82 16.3 1. 24 01/06/83 13.5 1. 36 Rating Curve: The rating curve for Humpy Creek wi 11 continue to be devel- oped as additional stage-discharge data points are collect- ed. A preliminary rating curve is plotted for the period of record and is shown in Figure 2. The discharge computation sheets are provided in Appendix A. After havinq established the rating curves, measurements will have to be continued to enable verification, and if necessary, adjustment of the rating curve to the actual circumstances. Deviations from the discharges read from the - 6 - 3.0 2.5 1.5 L2 1.1 1.0 0.9 0.8 0.7 0.6 DISCHARGE RATING CURVE O. -t-= 0.4 u.. -w <.!) ~ 03 CJ) 0.25 0.2 0.15 DISCHARGE (FT.lSEC.) 5678910 1!5 20 2!5 30 40 50 60 70 80 90 100 S LARSEN BAY. ALASKA -HUMPY CREEK FIGURE 2 ............. ENGINEERS rating curve are caused by morpholoqical chanqes of the streambed and stream icing problems. Channel: The channel above the gage is in a narrow incised, deep canyon with bed material consisting of gravels, cobbles and some boulders. Only a narrow discontinuous floodplain has developed within the canyon. The floodplain and slopes are covered with alders and brush. Control: The con t r 0 lis a c r 0 s s -sec t ion 0 r rea c h 0 f s t ream c han n e I that determines the relationship between staqe and discharge at that section and for some distance upstream. Permanent controls are desired for a stable staqe-discharge relation- ship: however, changes (shifts) in the control occur affect- ing the relationship of stage to discharge. a protruding rock outcrop downstream of the will be the control for stream water levels. A t low stag e s, digital gage At medium and high stages, the channel will be the dominant control. - 8 - Remarks: Stage records are good for those periods when the stage sensing and recording instruments were functioning properly. Otherwise, data gaps exist for winter months, and data for these periods were synthesized on the basis of weather data (Kodiak) and from data on a USGS qage on the same stream at an elevation of 800 feet mean sea level. Reliable data were obtained for seventy-five percent of the monitoring period. Backwater effects from winter stream icing and a malfunctioning transducer (which senses stream water levels and is coupled to digital recorder) prevented recovery of stage data for thirty percent of the monitoring period. The period of synthesized data is indicated in the summary stream discharge table (Table 1). In addition to the stage, stream temperature was also measured and the results are provided in the following printout sheets. A discharge of 3.0 cubic feet per second was added to all discharge values between June and August 31 because the Larsen Bay salmon cannery withdraws water above the gaging sit e. - 9 - Day 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 . 30 31 Tolal Mean A SUMMARY Of HUMPY CREEK (LARSEN BAY, ALASKA) STREAMfLOW RECORDS fOR JANUARY 1, 1982 THROUGH DECEMBER 31, 1982 MEAN DAILY DISCHARGE IN CUBIC fEET PER SECOND 1982 . Jan* feb* Mar* Apr May Jun Jul Aug Sep Oct Nov 8.8 • 6.4 6.0 7.5 9.2 49.0 22.0 13.0 7.6 9.8 17.0 8.2 9.0 6.0 7.5 9.3 49.0 22.0 13.0 7.0 9.9 14.0 8.2 10.0 6.0 7.5 9.2 48.0 21.0 13.0 6.8 9.7 13.0 8.2 9.6 6.0 7.5 9.3 49.0 22.0 12.0 6.7 10.0 20.0 8.5· 9.0 6.0 6.9 9.7 49.0 21.0 12.0 5.4 10.0 23.0 7.7 9.0 6.0 6.9 14.0 51.0 21.0 12.0 4.1 9.2 22.0 7.6, 8.8 6.0 7.5 16.0 48.0 20.0 12.0 4.3 9.4 28.0 6.0 8.8 6.0 7.5 26.0 46.0 18.0 12.0 3.6 9.1 19.0 6.( 8.8 6.0 8.3 38.0 44.Q 17.0 13.0 4.4 8.0 15.0 6.( 8.2 6.0 8.3 38.0 43.0 17.0 12.0 5.0 6.9-14.0 7.( 8.3 6.( 8.3 37.0 40.0 18.0 12.0 4.5 7.1 16.0 7.( 8.2 6.( 14.0 35.0 38.0 19.0 12:0 5.3 9.1 15.0 7.( 6.0 6.( 12.0 33.0 35.0 19.0 12.0 5.8 7.2 15.0 6.€ 6.0 6.( 8.3 33.0 34.0 18.0 12.0 7.2' 7.4 15.0 7.( 6.0 6.( 7.5 33.0 32.0 19.0 12.0 12.0 6.5 14.0 6.€ 6.0 6.( 8.3 32.0 29.0 19.0 12.0 12.0 8.1 14.0 6.6 6.0 6.( 8.3 31.0 28.0 18.0 11.0 15.0 7.2 14.0 6.6 6.0 6.0 7.5 31.0 28.0 18.0 11.0 19.0 7.1 13.0 6.2 6.0 6.( 7.5 33.0 27.0 18.0 11.0 17.0 7.3 13.0 6.4 6.0 6.( 7.5 32.0 26.0 17.0 11.0 18.0 7.0 14.0 6.6 6.0 6.0 6.9 31.0 25.0 18.0 11.0 18.0 6.6 9.2 6.2 6.0 6.0 6.9 31.0 24.0 17.0 12.0 16.0 5.8 12.0 6.2 6.0 6.0 7.5 31.0 23.0 20.0 12.0 15.0 5.5 13.0 6.2 6.0 6.0 7.5 30.0 23.0 17.0 11.0 13.0 8.1 11.0 6.2 6.0 6.0 8.3 28.0 23.0 16.0 11.0 13.0 4.4 11.0 6.2 6.0 6.0 9.2 32.0 23.0 15.0 11.0 14.0 10.0 14.0 6.2 6.0 6.0 9.0 42.0 23.0 14.0 10.0 12.0 8.9 12.0 6.2 6.0 6.0 9.0 44.0 22.0 14.0 11.0 14.0 16.0 11.0 6.2 6.0 8.9 43.0 22.0 15.0 11.0 12.0 13.0 11.0 6.2 6.0 9.0 44.0 26.0 14.0 12.0 11.0 12.0 11.0 6.2 6.0 45.0 13.0 12.0 14.0 211. 2 200.1 186.0 246.8 909.7 1027.0 557.0 364.0 308.7 270.3 443.2 6.81 7.15 6.00 8.23 29.35 34.23 17.97 11.74 10.29 8.72 14.77 MEAN fLOW fOR THE PERIOD Of RECORD 13.8 CUBIC fEET PER SECOND * DATA fOR THESE MONTHS ARE ESTIMATED - 6 - -10- Dec 11.0 11.0 11.0 11.0 11.0 11.0 11.0 9.0 7.9 13.0 15.0 13.0 9.5 12.0 15.0 11.0 8.8 7.5 9.0 9.9 8.7 7.3 7.1 7.5 8.4 9.0 2.2 9.6 13.0 12.0 11.0 313.4 10.11 100 10 10 70 .0 150 40 10 to 10 • • , -. Cf) LL a (,) - w (!) I a: « ::z: (,) ~ 2 o .f •• .7 •• .. .4 .I .2 MEAN DISCHARGE 13.8 CFS --------.....--- .f ~ . ..-' -.1 ... - . 3._ -.7 . • .IS A .S .2 ~ ________ ~ __________ ~ __________ L-________ ~ __________ ~ ________ ~L-________ -L __________ ~ ________ ~~ __ . ______ -L __________ ~ ________ ~ .I ,JANUARY FEBRUARY MARCH APRIL tolAY JUNE AUGUST S£PTEMBER CoCroSER HOJEMSER DECEMB!R ~ENGINEERS 1982 HYDROGRAPH OF HUMPY CREEK NEAR LARSEN BAY FIGURE 3 100 .0 10 70 eo 150 40 10 10 • • 7 • IS .. 2 -en LL (,) - w (!) a:: « ::z: u Cf) o - APPENDIX A DISCHARGE RATING CURVE MEASUREMENTS HUMPY CREEK, LARSEN BAY AL A S KA -12- PAGE PROJECT NAt'll!: LARSEN BAY HYDRO .JUVEIL NAME: ' HtJMPV CREEK rRAI'.!SECT NO. GAG£ SrT~ 12/29/81 PT.$TATION.t.JIDTH DEPTH . VELOCITY .---__ . __ . ..:...-_--'-'-..::..-.;l...(.I::F.cE.cE...I.T..;t)~_'__ ___ __.;;....J{....a:F::.J:€:.J:E:...TJ...L...i _;.;..; .. ··-'-······_···..L.'F~· .c..f'c..ET.L ___ . eEl/SEC) . ~ __ L_. -." .. ____ ....;.:.--...7~j1~_. __ ..j.Jn:.,.... ,....I-'.:.,;r,;.-..... ....,---_'""0. QO __ . ___ .. _Q •. ..oo._. __ .JLQ.Cl~ __ ._ .. _. ~Q¥-. ...cQw,Ow,. _-.--,......,.. ......... ~.."...,.,.,..,.,.,..,.,..,...... __ . ____ .. _~. ___ ._i __ -'--"__'_----"'-_.=i;.;..{LL:LL··· •. ·.·_·:_· ~ __ ·.··· ..... "IW..:...s..~AgL;;····· •... "_ .•... ----: __ ...1.: _:.c:I~""~'-' _. _ _ ng i :~ ~:5::-:','r::~:,(\, .---W t 5 7.00 1.00 1. ~O 145 1.50 2.17 1. 00 1. 50 1. 40 1. 50 2. 10 -... :/ .. ------~-._~~~-_---'-J .........,,('1 ..... '1 .J._f1.O-. _ _. __ .~. L .2!L . __ . _ ....... L._4.0 .. __ . ___ ..1_~_ . 8 9 10. 00 t.l.CO LOO 1.00 1.30 0.85 1.30 1.10 1.05 O. 651. 05.0.OS _-i.D ____ . ___ ~__"'_ ....... :L_J'-Ll.L ___ ~...L.....l..LU.. _----'-'---1 00 .i~_ O.2(L .. ___ ~_1 10. 0 22 1 1 . 1 :;} _.l.:L.. ___ .. : __ ~..,...,... ..... _..:...:..\.o'----_ 14 15 16·Q9 17.00. 1 00 ]00 0 10 1.00 0.10 1 ()t) 0.90 0.]0 0.90 0.09 --!---,-i~~'\)h-... _~_-.-.l_.c.w.. .1.0-. __ .. ___ ... __ :w."" .. _ ........... ~._...,._~~O.¥.-___ . ____ ,..,..,..",,.....,,.,.,.,,...._ L 000. 90 0.050.90 0.04 . 0;.00 0 000. 00 .' O.QQ . 9 i OQ lei ·j.';i CUBIC FT. /SEC. 15 86 SQUARE FT. ____ ~ ______ . ________ ~ ______ _'__ _ _'__-'--_____ '"'_~~_~. __ ~ __ _'_._~ __ . ______ . __ ---~-.:.........;'--~,"",,-,-..ii;ii;..~~~~ I~-------.. · \ PRO·.JEcr NAME ----.--.---.--.-~ ,-RIVER NAME TRt:\f.:5ECT :~lJ. PT. LARSEt'>l bf;, 1 H {uRO HUt:'iP'L.c..R j:.:r ;- ~l PAGE . L ... ,~_. __ ~~ ___ .......I-..J..o.l*-.-.,...,..-,..........,..,.--\,.C.~l-'-, ________ (L.uD . ____ . 0 00 "'_"__ ..... Q'--'"'Q ..... Q'---__ --".-.lotO~O.w:Q...,.....-..,.......,...,.".",,..,...,,.,..,.....,.,- 0.35 0.200;35 "0,07 ' .. ; ';i' ...•.. . ' ... f 3 . O. 55 O. 45. O. 55·().~a ',.,;;+,./ ~A _______ ~ __ ~4~o~n~._· ~~~'.·~·.~1~·~.OO~··~····· __ ~ __ ~O~7~O~ 1 bO ~Q~7L' O~~ __ ~~1_···~12.<_··~.·.~,~~~~~ __ 5 5 00 1.00 0.55 2.45 0.55 1.35 6 &" 00 1. 00 0, 50 1. 25 O. 50. O. 63 7. ,---.,-~~~ ... J~~.OU---. ~... 1 QO. __ ..... Ol..,.!iCL._,. __ , ...... , . .2.J3Q .. ,_,, ____ . __ Jl.....5D 1 !O ~ J '~;:! j~~ _1 i~----..... ~L.:~~ ..... g ...... ~~--'----:...30: ..... ;"""·.~ .... : .... '···"·_" ... "'_""'-"_>_'.,.,',._'.-: ... ,_ ••• : ...••. """y];;;.. •• ;... •••••••. ,_ ..•• '.;,.;..,._, j 1 12 14 11 00 1 00 0 10 0.00 0.10 0.00 12 00 I. CO 0, l~ 0.60 0.15 0.09 .. O~-_~. ~-_-.!l .. ~ __ ...,......,Q~Q.,;;;;411'.......-~~ . ....,.,....~,.,.....".~ 0.0.0 0.00 0.00 0.00 O;QO _.-_._-_ .... _._.--SUM .Of: CEll Dlc,CHARGE~; S011 (iF CE'L.t, f',.:;:E,;,::: hEAl': ,,'i::UlC L 1 )" b 22 4. 45 1 40 COBIC' £1 ISEC SQUARE FT FT ISEC. ------" ----. -.~~----~.........,-..,....,..,-~ I ... " I PROJ£Cl NAl"iE RIVER NAME T~:l~N5ECT NCT PT 1 4 6 '7 { 8 9 10 '11 12 13 14 15 16 LARSEN DAY HVDRO GAGE S T TE:5/31 /"8::: sr;,\T I ON (FEET) o SO 1. 00 2, 00 3" 00 4. 00 5 00 b. 00 7' 00 8. 00 9, 00 IiJ I:JO 11. 00 1:;-:. 00 13.00 14, 00 14,50 ("'11 DTH (FEET' O. 00 0.75' 1" 00 1.00 100-' ... 1. 00 i 00 1,,00 1. 00 1. 00 -'1 00- 1" OD 1.00 1.00 o 75 0,,00 DEPTH (FEET) o Oc. 0.40' o 45 0" 45 '0 40" 0" 3,) o 35 O. 40 O. 35 O. 30 -'0" 2S--- O. 2S O. 20 0:20 O. 20 0" 00 VELOCITY (FT/SEC) AREA DISCHARGE (SG FT) ( C FS ) PAGE ----_._---" -.... __ ._-----------..;,--_ .... =~-=-=-=-=------- o 00 O. 30 O. 90 O. 30 O. 00 O. 00 .. -0-30--_ ... -------0. 09 ---.--.---- 045 0.40 o 4S O. 13 --2"'2':.i' -" -----0-:-40 O. 90 1.60 030 0.48 1.90 03S 0,66 2.80 0.-40---------.r--.-t.~~~-,.-----.. 2.35 0,35 1. 80 0,30 1.'70--" O. 25 0,50 0.25 090 0.20 0.85 -0.20 0.50 0,15 0,00 0.00 O. 82 0.54 0.42 0.12 O. 18 ------0'.-77 .. ·-'----0·"---,·---·-0---- 0.07 0.00 ._---_._. -.---~------" ... SUM OF \·"E: .. L. L,IS(t'iAt,I;ES 80M OF :~LL AREAS . MEAN VELDC r TY ,:, 13 CU1H C FT. ISEC. 4. 35 SQUARE FT -"1.' 4 I' -FT. -fSEC~ -_._._-...... _--_ .. _---- .......... -.... ------_ ..... '-----_._---... I .- 0' I PRO·Jt::~: T NAI"lt: LARSEN BA\ HYDRO R I \.iCR NA!'1E TRAN':-;t~CT N'.J PT 1 4 5 8 9 10 14 15 16 1/ 18 1e; 2("} 21 STATION (FEET) ., ._.-.. _ ..... :~C;· t..}l.J ...... ~.~\J . 50 31 00 31 50 32 00 ·32 SCt -:>:; . ,J'.~ .JtJ :]3 50 34 00 34. 50 :35 ]'5 5(; -3 C:t 0'-' \J 87. OC j':':; ~~. ()() :::39 CIO 4() (}C 4'; C;I'~! ""4 .. 2 OCI 43. 00 4 " -~ -00 4 " . "t. 20 Sur1 OF -::EI..., 0 rS,:H""FGC:-) SUM OF CELL AREAS i"'lf:.t~N VEUJC IT;, ~,JI DTH DEPTH \ FEET; (FEET) ---~------_ .. _, .. , ...... - O. ('teJ u. 00 O. 30 j .. . 10 O. 50 1. 45 O. 50 i 50 O. :30 l. O. SCI 1 SO 0 50 1 50 O. 50 l. 30 0 50 i-25 0 50 1. 10 -- O. 5t) , 10 .>. (I S() 1 ()(J 0. ""71~ i " 9~) ~ -... [ \.1. 1. 00 0. 70 L 00 O. 50 i. 00 0 SO 1. 00 O. cO 1. 00 0 70 1 00 O. 80 l. 00 '0: 90 O. 60 0. 25 O. 00 0 00 27 71 CUaIC FT ;SEC 12 45 SQUARE FT '2 22 . Ft: lSEC.· VELOC ITY (FT/SEC ) ----.-..... -.-... ~ .. ~ 0 00 1. 20' 'j <:.. 90 'J 0::.. 00 2. 3. 30 '1 65 <:.. • 2. 40 r1 40 .c:;.. 3. 20 3. t;;() :3 10 ., Co • 50 1. 60 0. 95 1. 20 1. O. 90 '1 .::. 25 2. 30 0. 95 0, 00 PAGE AREA DISCHARGE (SG FT) ( C FS ) o ()O o 33 O. 72 o 75 o 75 0-65 O. 63 o 55 o 55 0_ 50 o 67 O. 70 O. 50 O. 50 o 60 o 70 o 80 . ----0.-90 o 15 0. 00 ---.--------------_ .. _.-._-_._----- 0,00 -O:"4<Y--------·--· --.---- 2_ 10 L 50 2. 47 1. 99 . -56---'· 1. 50 1. 76 i,-98 1. 55 1. 69 -1.£2"- 0.47 0.60 ----. 0-'72- O. 63 1. 80 2-. -1)'7---' 0.14 0.00 I -........ I PRO·Jt~C T !\lAMF R I \JER NAl"IE l" j\ Af·mE cr NO. '"IT t-•. i r; .::.. 3 4 6 '7 8 9 iO 1 1 , ., .1.<':':' 1:3 14 LARSEl'~ GAy riYDRtJ HUr"lPIE C~';:Cj.-\ GA~E SrTE ~0/26!82 STAT lOI'J WIDTH 'FEET) (FEET i .H< __ ~ __ -------- :2 00 O. 00 ~ 00 i. 00 ..<. 4. 00 1. 00 '5 00 1. 00 6 60 L -00 7 00 1. 00 8 tJf] 1 00 ~I ()() 1. 00 ~< .-"\ .I.\.,; . 00 1. 00 U. O() i 00 1.2 00 1 00 13 ()() 1 00 14-00 J.. 1)0 15 00 0 00 ·S:,.n'1 OF GEL_! DJSCr1;~R(;ES 16. 28 SUi"! D~' ',~ELL l,REJ-\S DEPTH (FEET) VELOC If V (FT/SEC) PAGE AREA DISCHARGE (SQ, FT) (CFS) ---':"':":':::"---~----.--------_._-------------------- ° O. 0 O. ~" (j. 0. 0. 00 50 75 80 'iO 70 50 0. 00 '0.40 0.30 1. 50 2: 6U 0. 60 L 20 0: 60 -3.00 0, 70 0. 60 -0 80 1. 00 (\. 80 0. 00 LVIiI.: FT, lSEC. SQUARE FT. 3. 15 2.35 -:3. -30 2, 20 1. 30 O. 00 0.00 0.00 0.-50 -"---rr. ~------~-- 0.75 0.22 0.80 1. 20 --u.-9u-----,~ .... ") ,-,3-..-4.,..-------- o. 70 O. 42 0. 50 0. 60 0.60 O. 70 O. 60 2.20 i.41 v.1m ~~'----~--··-:,..,__r-Ir-----~'----·····'-· i.OO O. 80 0.00 - 2. 20 1. 04 . -'--0: 00 L 88 FT. /SEC, APPENDIX B PRINTOUT OF DISCHARGE COMPUTATIONS STAGE AND TEMPERATURE READINGS AND CORRESPONDING DISCHARGES HUMPY CREEK, LARSEN BAY ALASKA -18- APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HU"PY CREEK NEAR LARSEN BAY DATE TI"E BYTE RAW DATA •••••••• ••••• •••• • ••••••• 03/31/82 18:00 1 3~ 101 03/31/82 20:00 3 34 101 03/31/82 22:00 5 34 100 03/31/82 24:00 7 33 100 04/01112 02:00 04/01/82 04:00 114/01/12 06:00 04/01/12 08:00 ii4/01/U 10:00 04101/12 11:00 ii4101/U 14:01 04/01182 16:00 04/01/82 18:00 04101/12 20:00 04/01/12 22:00 04101/82 24:00 04/02/82 02:00 1i4102/U 04:00 04/OJ/82 06:00 04/02/12 08:00 04/02/12 10:00 04/02/12 12:00 04/02/12 14:00 04/02/82 16:00 04/02/82 18:00 04/02/82 20:00 04/02.182 U;OO 04/0318Z 24:00 04/03/82 02:00 04/03/82 04:00 ii4/03/82 06:00 04/03/82 08:00 04/03/82 10:00 04/03/82 12:00 04/03/82 14:00 04/03/82 16:00 04/03/12 18:00 04/03/82 ao:oo 04/03112 22:00 04/03/12 24:00 DAILY AVERAGE VALUES , 35 100 11 35 100 13 36 100 15 U 100 17 37 100 ., 35 101 21 34 100 23 34 100 25 34 100 27 34 100 2t 34 lOO 31 30 100 DAILY AVERAGE VALUES 33 35 37 39 41 43 45 47 4t 40 100 46 100 54 100 58 100 50 100 42 100 35 100 35 100 35 100 51 34 100 53 34 100 55 35100 DAILY AVERAGE VALUES 51 Sf 61 63 65 67 6t 71 13 75 11 " U 100 53 100 65 100 67 100 40 100 35 100 35 100 34 100 34 10' 34 100 34 100 34 100 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HU"P03.POD PAGE 1 O'-AUG-83 START TI"E 03/31/82 18:00 DEPTH STAGE DISCHG INCHES FEET eFS •••• a ••••• 1.0 6.8 6 .• 6.6 6.8 1.0 7.0 7.2 7 .• 7.4 7.0 6.8 6.8 6,8 6.8 6.8 7.2 7. 1 14,0 13.6 13.6 13,2 13.6 14,0 14.0 14,4 U.6 14,8 14.0 13.6 13.6 13.6 13 , 6 13,6 14.4 14,1 8.0 16.0 9.2 18.4 10,8 21,6 11.6 23.2 10,0 20.0 8.4 16.8 7.0 14.0 7,0 14.0 7.0 14.0 6.' 6.8 7.0 8.3 13.6 13.6 14.0 16.6 '.4 16.' 10.6 21.2 13.0 1'.0 13.4 20.8 8.0 16.0 1.0 14.0 7.0 14.0 6.8 13.6 6.8 13.6 6.8 13.6 6.8 13.6 6.8 13,6 •. 5 16. , -19- ••••• 1. 17 1.13 1.13 1. 10 1. 13 1. l' 1.17 1.1O 1.30 1. 23 1.17 1 . 13 1. 13 1.13 1. 13 1. 13 1. 20 1.18 1. 33 1. 53 1. 80 1.93 1.67 1. 40 1. 17 1. 17 1. 17 1.13 1. 13 1.17 1. 38 1. 40 1.77 2.17 2.23 1. 33 1.17 1.17 1. 13 1 . 13 1 . 13 1.13 1.13 1. 41 • ••••• 8.4 7.5 7.~ 6.9 7.6 '.3 8.3 , , 1 n 9,9 8.3 7.S 7.~ 7.5 7,S 7.5 9.1 8.5 is 20 33 41 U 1~ 8.3 8.l 8.3 7.5 1.S 8.3 16 15 31 60 U 13 8.3 8.3 7.5 7.5 7.5 7.~ 1.5 20 TE"P DEG C ••••• O,S O.S 0.0 0.0 O.S 0.0 0.0 0.0 0.0 0.0 0,0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Ii. 0 0.0 0.0 0.0 0.0 0,0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUKP' CREEl NEAR LARSEN BAY DATE TIKE •••••••• ••••• 04/04/82 02:00 04/04/82 04:00 04/04/82 0&:00 04/04/82 08:00 04104182 10:00 04/04182 12;00 04/04/82 14:00 04/04/82 16:00 04/04182 18:00 114/04/82 20:00 04/04/82 22:00 04/04182 24;00 04/0H82 02;00 04/0:1/82 04;00 04/05/82 06:00 04/03182 0':00 04/05182 10:00 04/05182 12;00 04/05182 14:00 04/05/82 16;00 04/0HU 18;80 04/05/82 20:00 04/05182 22;00 04/05/82 24:00 04/06182 01;00 114/06182 04:00 04/06182 06:00 04/06l1Z 08;00 04/06/12 10:00 04/06/82 12:00 04106112 14:00 04106/12 16:00 04/06182 18:00 04/06182 20:00 04/06lU 22;00 04/06/82 24:00 BYTE RAW DATA ..... ....... . 81 34 100 83 35 100 .5 31 100 87 31 100 89 34 100 U 34 100 93 34 101 95 34 102 97 34 102 99 34 102 101 34 102 103 34 102 DAILY AVERAGE VALUES 105 34 102 101 34 102 lot 34 102 111 33 102 113 33 103 115 34 103 111 35103 119 35 102 121 35 103 123 35 103 125 35 103 121 35 103 DAILY AVERACE VALUES 129 131 133 135 131 139 34 102 34 102 34 102 34 102 33 101 33 104 141 34 lOS 143 35 105 145 31 104 141 36 104 149 36 104 151 35 103 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUKP03.POD PAGE 2 OI-AUCi-83 START TIKE 03/31/.2 18:00 DEPTH STAGE DISCHCi KV INCHES FEET CFS •••• =-••••• ••••• ..=-••. 6.' 1.0 1.6 1.4 6.1 6.8 6.8 6.' 6 .• 6.' 6.' 6.' &.9 &.8 6.8 6.8 6.6 6.6 6.8 1.0 7.0 1.0 1.0 7.0 7.0 6.' 6.8 6.' 6.8 6.1 6.6 6.6 6.8 1.0 7.4 1.2 7." 7.0 6.9 -20- 13.6 14.0 13.2 14.' 13.6 13.6 13.6 13.6 13.6 13.6 13.& 13.6 13.9 13.6 13.6 13.6 13.7. 13.2 13.6 14.0 14.0 14.0 14.0 14.0 14.0 13.7 13.6 13.6 13.6 13.6 13.1- 13.2 13.6 14.0 14.' 14.4 14.4 14.0 13.8 1. 13 1. 11 1. 21 1.23 1.13 1.13 1.13 1. 13 1.13 1. 13 1. 13 1 . 13 1 . lei 1.13 113 1.13 1. 10 1.10 1.13 1. 17 1. 17 1. 11 1. 17 1. 11 I. 17 1. 14 1.13 1.13 1.13 1.13 1. 10 1. 10 1. 13 1.11 1.7.3 1.%0 1.20 1. 11 1. 15 1.5 8.3 11 ,., 1.5 1.5 1.S 1.5 7.5 7.S 7.5 1.5 8.0 1.5 7.:1 7.5 6.J &.9 7.5 8.3 8.3 8.3 8.3 8.3 8.3 7.a 7.5 1.S 7. S ?S 6.9 6.9 7.5 '.3 t.9 9. 1 9. 1 8.3 8.0 TEKP DEG C ••••• 0.1i 0.0 0.0 0.0 0.0 0.0 0.5 1.0 1 .0 1.0 1.0 1.0 0.5 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.0 1.5 1.5 1.5 1.5 1.3 1.0 1.0 1.0 1.0 1.0 2.0 Z.S 2.5 ".0 2.0 2.0 1.5 1.6 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN' LARUE DATA FILE HUMP03.POD PAGE 3 o8-AUG-83 HUMPY CREEK NEAR LARSEN BAY START TIME 03/31/12 18:00 DATE TIME •••••••• ••••• 04/01112 02:00 04/01/82 04:00 04/01/82 06:00 04/01/12 08:00 04/07182 10:00 04/01/82 12:00 04/01182 14:00 04/01/12 16:00 04/01182 18:00 04/01/82 20:00 04/07182 21:00 04/01/82 24:00 04/08/82 02:00 04/08182 04:00 04/08/82 06:00 04/08/82 08:00 04/08182 10:00 04/08/82. 12:00 il4/08/82 14:00 04/08/82 16:00 04/08182 18:00 04/08/82 20:00 04/08/82 21:00 04/08/82 24:00 04/09182 02:00 04/09182 04:00 04/09lU 06:00 04/09lU 08:00 04/09182 10:00 04/09/82 12:00 04/09182 14:00 04/09/82 16:00 04/09182 18:00 04/09/82 20:00 04/09/82 21:00 04/09182 24:00 BYTE RAW DATA •••• • ••••••• IS3 3S 103 ISS 35 103 151 35 103 159 35 103 161 34 103 163 34 104 165 36 106 161 31 105 169 38 105 111 31 103 113 36 103 115 36 102 DAILY AVERAGE VALUES 111 119 181 183 185 181 189 191 193 195 191 199 35 102 35 102 36 102 35102 35 103 34 104 35 106 36 105 36 105 36 104 36 103 36 103 DAILY AVERAGE VALUES 201 203 105 201 209 211 213 215 217 219 211 223 35 102 3S 102 35 102 3~ 102 n 103 3S 104 35105 36 105 35 104 35 103 35 103 35 102 DAILY AVERAGE VALUES DEPTH STACE DISCHC MV INCHES FEET eFS •••• • ••••• • •••• •••••• 1.0 7.0 1.0 1.0 6.8 6.8 1.2 1.4 1.6 1.4 1.2 1.2 7. 1 1.0 1.0 7.2 1.0 1.0 6 .• 1.0 1.2 7.2 1.2 1.2 7.2 1. 1 1.0 1.0 1.0 1.0 1.0 7.0 1.0 1.2 1.0 1.0 7.0 7.0 1.0 -21- 14 0 14.0 14.0 14.0 13.6 13.6 14. 4 14 . 8 15.2 14.8 14.4 14 . 4 14.3 14.0 14.0 14.4 14.0 14.0 13.6 14.0 14.4 14.4 14. 4 14.4 14.4 14 . 2 14.0 14.0 14.0 14.0 14.0 14 0 14.0 14.4 14.0 14.0 14.0 14.0 14.0 1.17 1.17 1.17 1. 11 1.13 1. 13 1. 20 1.23 1. 21 1.23 1. 20 1. 20 1.19 1. 17 1. 17 1.20 1. 17 1.17 1.13 1. 17 1.iD 1. 20 1. 20 1. 20 1. 10 1.18 1. 11 1 . 11 1. 11 1. 11 1.11 1 . 11 1. 11 1.20 1. 17 1. 17 1.17 1. 11 1.17 a.3 8.3 a.3 8.3 1.S 1.5 , . 1 9.9 11 9.9 ., . 1 9. 1 8.a B.3 1.3 9. 1 8.3 8.3 1.5 8.3 9.1 '.1 , . 1 , . 1 , . 1 8.6 8.3 8.3 8.3 8.3 1.3 B.3 B.3 9. 1 8.3 8.3 8.3 8.3 8.4 TEMF DEG C • •••• I.S 1.5 1.5 1.5 1.5 2.0 3.0 2.5 2.5 1.5 1 . 5 1.0 1.8 1.0 1.0 1.0 1.0 1 .5 2.0 3.0 2.S LS 2.0 1.5 1.5 1.1 1.0 1.0 1.0 1.0 1.5 2.0 2.5 2.5 2.0 1.5 1.5 1.0 1.5 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 04/10182 02:00 04/1018204:00 04110182 16:00 04/10/82 08:00 04/10182 10:00 04110182 12:00 04/10182 14:00 04110182 16:00 04/10/82 18:00 04/10182 20:00 04/10182 22:00 04/10/82 24:00 04/1118202:00 04/11/82 04:00 04111182 06:00 04/11182 08:00 84/11182 10:00 04/11/82 12:00 04/11182 14:10 04/11/82 16:00 04/11/8218:00 04/11182 20:00 04/11/82 22:00 04/1118224:00 04/12182 02:00 04/12/82 04:00 04/12/82 06:00 04/11182 08:00 04/12182 10:00 04/12182 12:00 04/12182 14:00 04/12182 16:00 04/12182 18:00 84/12/82 20:00 04/12/82 22:00 04/12/82 24:00 BYTE RAW DATA •••• •••••••• 22:1 227 229 231 233 23:1 237 239 3:1 102 35 102 35 102 3:1 102 35 102 35 103 3:1 102 3:1 102 241 35 102 243 35 102 24:1 3:1 101 247 3:1 101 DAILY AVERAGE VALUES 249 3:1 100 2:11 3:1 100 2:13 36 100 25:1 38 100 257 40 100 2:19 38 100 261 36 100 263 35 100 26:1 36 100 267 39 100 269 n 100 271 48 100 DAILY AVERAGE VALUES 273 27:1 277 iH 281 283 :19 100 69 100 76 100 79 100 77 100 68 100 28:1 52 100 287 41 100 289 41 100 291 43 100 293 42 100 29:1 45 100 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 4 08-AUG-83 START TIME 03/31/82 18:00 DEPTH STAGE DISCHG MV INCHES FEET CFS •••• • ••••• ••••• •••••• 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.2 7.6 8.0 7.6 7.2 7.0 7.2 7.8 8.4 9.6 7.6 11 .8 13.8 15.2 1:1.8 15 .4 13.6 10.4 8.2 8.2 8.6 8.4 9.0 11. 5 -22- 14 . 0 14.0 14. 0 14.0 14.0 14.0 14.0 14.0 14.0 14 . 0 14.0 14.0 14. 0 14.0 14.0 14.4 1:1. 2 16.0 15. 2 14.4 14.0 14 .4 1:1.6 16.8 19.2 IS.3 23.6 27.6 30.4 31 .6 30.8 27.2 20.8 16.4 16.4 17 . 2 16.8 18.0 23. 1 1. 17 1. 17 1. 17 1. 17 1. 17 1. 17 1. 17 1. 17 1.17 1. 17 1.17 1. 17 1.17 1. 17 1.17 1. 20 1. 27 1.33 1. 27 1 .20 1. 17 1. 20 1. 30 1. 40 1 .60 1.27 1.97 2.30 2.53 2.63 2.57 2.27 1.73 1. 37 1.37 1.43 1. 40 1. 50 1. 92 .3 .3 .3 .3 .3 .3 .3 .3 .3 .3 .3 .3 .3 8.3 8.3 9.1 11 13 1 1 9. 1 8.3 9. 1 12 15 23 11 44 72 98 111 102 69 29 14 14 16 15 18 50 TEMP DEG C • •••• 1 . 0 1.0 1 .0 1.0 1 . 0 1.5 1 .0 1.0 1 . 0 1.0 0.5 0.:1 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 o . 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 o . 0 0.0 0.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN & LARUE DATA FILE HUMP03.POD PAGE 5 08-AUC-83 HUMPY CREEK NEAR LARSEN BAY START TIME 03/31/82 18:00 DATE TIME •••••••• ••••• 04/13/82 02;00 04/13182 04:00 04/13182 06:00 04/13/82 08:00 04113/82 10:00 04113/82 12:00 04113/82 14:00 04/13/82 16:00 04/13/82 18:00 04/13/82 20:00 04/13182 22:00 04/13/82 24:00 04/14182 02: 00 04114182 04:00 04/14/82 06:00 BYTE RAW DATA •••• •••••••• 297 49 100 2" "100 301 66 100 303 16 100 305 72 100 307 13 100 309 49 100 311 40 100 313 39 100 315 39 100 317 41 100 319 43 100 DAILY AVERAGE VALUES 321 323 325 45 100 48 100 55 100 04/14/82 08:00 327 66 100 04/14/82 10:00 329 66 100 04/14/82 12:00 331 55 100 04/14/82 14:00 333 41 tOo 04/14/82 16:00 335 38 100 04/14/82 18:00 337 38 100 04/14/82 20:00 339 37 100 04/14/82 22:00 341 36 100 04/14/82 24:00 343 35 100 04/15182 01:00 04/15182 04:00 04/15/82 06:00 04/15/U 08:00 04/15182 10:00 04/15/82 12:00 04/15/82 14:00 04/1S/82 16:00 04/151U 18:00 04/151U 20:00 04/15182 22:00 04/15/82 24:00 DAILY AVERAGE VALUES 345 34 100 347 34 101 349 34 101 331 34 101 353 34 100 355 n 100 357 35 100 359 35 100 361 35 100 363 35 100 365 35 100 361 35 100 DAILY AVERAGE VALUES DEPTH STAGE DISCHG MV INCHES FEET CFS •••• • ••••• 9.8 11. 0 13.2 15.2 14.4 14.6 9.8 8.0 7.8 7.8 8.2 8.6 10.7 9.0 9.6 11. 0 19.6 22.0 26.4 30.4 21.8 29 .2 19.6 16.0 15.6 15.6 16.4 17 . 2 21.4 18.0 19.2 n.o 13.2 26.4 13.2 26.4 11.0 n.o 8.2 16.4 7.6 15.2 1.6 1'.2 7.4 14.8 7.2 14.4 7.0 14.0 9.3 18.7 6.8 6.8 6.8 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.9 -23- 13.6 13.6 13.6 13.6 13.6 14.0 14.0 14.0 14.0 14.0 14.0 14.0 13.8 • •••• 1.63 1.83 2.20 2.'3 2.40 2.43 1.63 1. 33 1.30 1. 30 1. 37 1.43 1. 78 1. 50 1 .60 1.83 2.20 2.20 1. 83 1. 37 1.27 1.27 1. 23 1.20 1. 17 1.56 1. 13 1. 13 1.13 1. 13 1.13 1. 17 1. 17 1. 17 1.17 1. 17 1. 17 1. 17 1. 15 •••••• Z4 35 63 98 83 86 24 13 12 12 14 16 40 18 23 35 63 63 35 14 11 11 9.9 9. 1 8.3 2' 7. S 7.5 7.S 7.5 7.S 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.0 TEMP DEG C • •••• 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 D.O 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 O.S 0.5 0.5 O. D 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 1PA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 04/16182 02:00 04/16182 04:00 04/16182 06:00 04/16/82 08:00 04/16/82 10: 00 04/16182 12:00 04/16/82 14:00 04/16182 16:00 04/16112 18:00 04/16182 20:00 BYTE RAW DATA •••• • ••••••• 369 371 373 375 377 379 381 383 385 387 35 100 37 100 39 100 42 100 40 100 36 100 36 100 3S 100 35 100 35 100 04/16/82 22:00 389 36 100 04/16/82 24:00 391 37 100 04/17/82 02:00 04117/82 04:00 04/17/82 06:00 04/17/82 08:00 04/17/82 10:00 04/17/82 12:00 04117/82 14:00 04/17/82 16:00 04/17/82 18:00 04/17/82 20:00 04/17/82 22:00 04/17/82 24:00 04/1 /82 02:00 04/1 /82 04:00 04/1 /82 06:00 04/1 /82 08:00 04/1 /82 10:00 04/1 /82 12:00 04/1 /81 14:00 04/1 /81 16:00 04/1 /82 18:00 04/1 182 20:00 04/1 /82 22:00 04/1 /81 24:00 DAILY AVERAGE VALUES 393 395 397 399 401 403 405 407 409 4 11 413 415 37 100 39 100 43 100 46 100 44 100 36 100 35 100 34 100 34 100 35 100 35 100 38 100 DAILY AVERAGE VALUES 417 42 100 419 47 99 421 55 " 423 58 100 425 48 100 427 38 100 429 35 100 431 34 100 433 34 100 435 34 100 437 34 100 439 34 100 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP03.POD PAGE 6 OS-AUG-II START TIME 03/31/82 18:00 MV DEPTH INCHES •••• • ••••• 7.0 7.4 7.8 8.4 8.0 7.2 7.2 7.0 7.0 7.0 7.2 7.4 7.4 7.4 7.8 8.6 9.2 8.8 7.2 7.0 6.8 6.' 7.0 7.0 7.6 7.6 8.4 9.4 11.0 11.6 9.6 7.6 7.0 6.8 6.8 6.8 6.8 6.8 8.2 -24- 14. 0 14.8 15.6 16.8 16.0 14.4 14.4 14.0 14. 0 14.0 14. • 14.8 14 .• 14.8 15.6 17.2 18.4 17.6 14.4 14.0 13.6 13.6 14.0 14 . 0 15. 2 15.2 16 .• 18.8 22.0 13.2 19. 2 lS.2 14. 0 13.6 13.6 13 . 6 13.6 13.6 16.4 STAGE FEET ••••• 1. 17 1.23 1.30 1. 40 1. 33 1.20 1.20 1. 17 1. 17 1. 17 1.20 1.23 1.23 1.23 1.30 1.43 1 . :i3 1.47 1.20 1. 17 1.13 1. 13 1. 17 1.17 1. 27 1. 27 1. 40 1. S7 1.83 1.93 1. 60 1.27 1. 17 1. 13 1. 13 1. 13 1.13 1 . 13 1. 37 DISCHG CFS • ••••• 8.3 9.9 12 IS 13 9. 1 9.1 8.3 8.3 8.3 9. 1 9.9 10 9.9 12 16 2D 17 9. 1 8.3 7.5 7.S 8.3 8.3 11 11 15 21 35 41 23 11 •. 3 7.5 7.S 7.S 7.5 7.S 16 TEMP DEC C • •••• 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -O.S -O.S 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 -0. 1 IPA HYDRO-ELECTRIC FEAIUILITY STUDY FOUR VILLAGES PREPARED 8Y DRYDEN & LARUE DATA FILE HUMP03.POD PAGE 1 DI-AUG-83 HUHPY CREEX NEAR LARSEN lAY START TIME 03/31/.2 18:00 •••••••• • •••• 04119/82 02:00 04/19/82 04:00 04/19/82 06:00 04119/82 01:00 04/19/82 10:00 04/19/82 12:00 04/191U 14:00 04/19182 16:00 04/19182 18:00 04/19/82 20:00 04/19/12 22:00 04/19182 24:00 04/20/82 02:00 04/20/82 04:00 G4120/82 06:00 04/:20/82 0':00 04/:20182 10:00 04/:20182 U:OO 04110/82 14:00 04/20/82 16:00 04/10182 18:00 04/20/82 20:00 04/Z0/82 22:00 04/20182 24:00 04/21/82 02:00 04/21/82 04:00 04/21/82 06:00 04/11182 08:00 04/21/82 10:00 04/21/8% 12:00 04/21/82 14:00 04/21/8% 16:00 04/21/82 18:00 04/U/82 20:00 04/21/82 22:00 04/21182 24:00 BYTE RAW DATA •••• • ••••••• 441 34 100 443 34 100 44:5 34 100 447 34 lOO 449 34 101 451 34 100 H3 34 100 455 34 100 457 34 100 459 n ltO 461 35 100 463 34 100 DAILY AVERAGE VALUES 465 467 469 34 100 34 100 34 100 471 34 100 473 34 100 475 34 101 477 34 101 479 34 101 481 34 101 483 34 101 485 34 100 487 34 100 DAILY AVERAGE VALUES 489 491 493 495 497 499 34 100 34 101 34 101 33 101 33 101 33 103 :i01 34 103 503 34 103 505 34 102 507 35 102 509 34 102 511 34 102 DAILY AVERAGE VALUES DEPTH STAGE DIStHG MV INCHES FEET eFS •••• • ••••• ••••• • ••••• 6.8 6.' 6.' 6.8 6.. 6.' 6.' 6.' 6.' 7.0 1.0 6.8 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.' 6.8 6.8 6.8 6.' 6.8 6.6 6.6 6.6 6.8 6.' 6.8 1.0 6.' 6.' 6.' -25- 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 14.0 14.0 13.6 13.7 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13. , 13.6 13.6 13.6 13.6 13.2 13.2 13.2 13.6 13.6 13.6 14.0 13.6 13.6 13.5 1.13 1.13 1. 13 1.13 1.13 1.13 1.13 1.13 1. 13 1. 11 1. 11 1.13 1.14 1.13 1. 13 1. 13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1. 13 1.13 1. 13 1.13 1.10 1.10 1.10 1.13 1.13 1.13 1.17 1.13 1. 13 1. 13 1.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1.S '.3 8.3 7.5 7.6 7.5 7.5 7.5 1.5 7.5 7.S 1.5 1.5 1.5 1.5 7.5 7.5 7.5 7.5 7.5 7.5 6.9 6.9 6.' 1.S 7.5 7.5 '.3 1.5 7.5 7.4 TEMP DEG e • •••• 0.0 0.0 0.0 0.0 0.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.5 0.5 G.S 0.5 0.5 0.0 0.0 0.2 0.0 0.5 0.5 0.:; 0.5 1.5 1.5 1.5 1 . D 1.0 1.0 1.0 0.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PAGE 8 OI-AUG-83 PREPARED BY DRYDEN' LARUE DATA FILE HUH'03.'OD HUHPY CREEK NEAR LARSEN BAY DATE TIHE •••••••• ••••• 04/U/U 02:00 04/U/U 04:00 04/U/U 06:00 84/22/82 08:00 04/U/U 10:00 04/22/U 12:00 04/U/U 14:00 04/U/82 16:00 04/U/82 18:00 04/U/U 20:00 04/UII2 U:OO 04/U/82 24:00 04/23/82 02:00 04/23/U 04:00 04/23/82 06:00 04/23/82 08:00 04/23182 10:00 04/23/82 12:00 04/23/82 14:00 04/23182 16:00 04/23/82 18:00 04/23182 20:00 04/23/82 U:OO 04/23182 24:00 04/24182 02:00 04/24/82 04:00 04/14182 06:00 04/24182 08:00 04/24182 10:00 04/24/82 12:00 04/24182 14:00 04/24182 16:00 04/24183 18:00 04/24182 20:00 04/24182 22:00 04/24182 24:00 BYTE RAY DATA •••• •••••••• 513 34 101 515 34 101 517 34 100 519 33 100 521 33 102 523 33 103 SZ5 34 104 521 34 103 529 35 103 531 35 102 533 n 102 535 34 102 DAILY AVERAGE VALUES 537 539 541 543 543 34 102 34 102 34 102 34 102 34 103 547 34 104 5., 34 105 551 36 103 553 38 102 555 37 103 557 U 102 559 36 102 DAILY AVERAGE VALUES 561 35 102 563 3S 103 565 35 102 567 35 103 569 34 104 571 36 105 573 36 104 575 37 104 577 38 104 579 H 103 581 38 103 583 37 103 DAILY AVERAGE VALUES START TI"E 03/31/82 18:00 DEPTH STAGE DISCHG TEHP INCHES •••• • ••••• 6.8 6 .• 6.8 6.1 6.6 6.6 6 .• 6 .• 7.0 7.0 7.0 6.' 6.8 6.8 6.8 6 .• 6.8 6.8 6.8 6.8 7.2 7.6 7.4 7.2 7.2 7.0 7.0 7.0 7.0 7.0 6.8 7.2 7.2 7.4 7.6 7.8 7.6 7.4 7.3 -26- 13.6 13.6 13.6 13.2 13. 2 13.2 13.6 13 .1 14.0 14.0 14.0 13. , 13.6 13.6 13.6 13.6 13.6 13.6 13.6 13.6 14.4 15.2 14.8 14.4 14.4 14.0 14.0 14.0 14.0 14.0 13.6 14.4 14.4 14.8 15.2 15 . 6 15.2 14.8 14.5 FEET • •••• 1 . 13 1. 13 1.13 1. 10 1. 10 1.10 1.13 1.13 1.17 1.17 1. 17 1.13 1.13 1.13 1. 13 1. 13 1. 13 1.13 1. 13 1.13 1.20 1.27 1.23 1.20 1.20 1.17 1.17 1. 17 1.17 1.17 1. 13 1. 20 1. 20 1.23 1. 27 1. 30 1. 27 1.23 1.21 CPS •••••• 7.5 7.5 7.5 ,., 6.' ,., 7.S 7.5 8.3 '.3 8.3 7.5 7.6 7.5 7.5 7.5 7.S 7.5 7.5 7.5 , . 1 11 '.9 9.1 9.1 8 4 8.3 8.3 8.3 8.3 7.5 9. 1 9. 1 9.9 11 12 11 9.9 9.3 DEG C • •••• 0.5 0.5 0.0 0.0 1.0 1.5 2.0 1.5 1.5 1.0 1.0 1.0 1.0 1 .0 1.0 1.0 1.0 1.5 2.0 2.5 1.5 1.0 1.5 1.0 1.0 1.3 1.1 1.5 1.0 1.5 ,,0 2.5 2.0 2.0 2.0 1.5 1.5 1.5 1.7 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NIAR LARSEN BAY DATE TI"E •••••••• ••••• 04/25/11 02:00 04125 112 04: 10 04/25/82 06:00 04/25/11 08:00 04/25/82 10:00 04/25/11 12:00 04/25182 14:00 04125/12 16:00 04/25112 18:00 04/25/12 20:00 04/25/12 22:00 04/25112 24:00 04/26182 02:00 04126182 04:00 04/26/82 06:00 04/26182 08:00 04/16/82 10:00 04/26/82 12:00 04/16/82 14:10 04/26182 16:00 04/26/82 18:00 04/26/82 20:00 04/16/82 22:00 04/26182 24: 00 04/27/82 02:00 04127182 04:00 04/27/82 06:00 04/27181 08:00 04/21182 10:00 04/27/82 12:00 04/27/82 14:00 04/27182 10:00 04/27/82 18:00 04/27/82 20;00 04/27/82 22:00 04/27182 24:00 BYTE RA\I DATA •••• •••••••• 585 16 102 587 36 102 589 36 102 591 35 102 593 35 104 595 35 106 597 37 106 599 37 105 601 38 105 603 38 104 60S 31 103 601 37 103 DAILY AVERAGE VALUES 609 611 613 US 617 6lt 621 623 625 627 62' 631 36 103 36 103 36 103 36 103 36 104 36 105 36 106 36 105 37 105 37 104 36 103 36 102 DAILY AVERAGE VALUES 633 36 102 635 36 102 637 36 102 639 36102 641 34 102 643 35 106 645 36 107 641 36 101 649 37 105 651 37 104 653 36 102 655 36 102 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUJfP03.POD PAGE , 08-AUG-13 START TI"£ 03/31/82 18:00 DEPTH STAGE DISCHG "V INCHES FEET CFS •••• • ••••• • •••• • ••••• 7.2 7.2 1.2 7.0 7.0 7.0 7.4 7.4 7.6 7.6 1.4 7.4 7.3 7.2 7.2 7.2 1.2 7.2 1.2 7.2 7.2 7.4 7.4 7.2 7.2 7.2 7.2 7.2 7.2 1.2 6.8 7.0 7.2 7.2 7.4 7.4 7.2 7.2 7.2 -27- 14.4 14.4 14.4 14.0 14.0 14.0 14.8 14.8 15.2 15.2 14.8 14.8 14.6 14 . 4 14.4 14.4 14.4 14.4 14.4 14.4 14.4 14.8 14.8 14.4 14. 4 14.5 14. 4 14.4 14. 4 14.4 13.6 14.0 14.4 14.4 14.8 14.8 14.4 14 .4 14. 4 1. 20 1. 20 1. 20 1.17 1. 17 1. 11 1. 23 1.23 1. 27 1.27 1.23 1.23 1.21 1.20 1.20 1. 20 1. 20 1. 20 1. 20 1. 20 1. 20 1.23 1.23 1. 20 1. 20 1. 21 1. 20 1.20 1. 20 Lao 1.13 1.17 1.20 1. 20 1. 23 1.23 1.20 1.10 1. 20 , . 1 , . 1 '.1 8.3 8.3 8.3 9.' ,., 11 11 ,., ,., '.4 9. 1 9. 1 9. 1 , . 1 , . 1 '.1 9.1 9.1 9.9 9.9 9. 1 9.1 9.2 9. 1 9. 1 9. 1 9.1 1.5 8.3 , 1 9.1 9.9 9.9 9. 1 9.1 9.0 TEMP DEG C ••••• 1.1i 1.0 1.0 1.0 2.0 3.0 3.0 2.5 2.5 2.0 1.5 1.5 1.8 1.5 1.5 1.5 1.5 2.0 2.S 3.0 2.5 2.5 200 1.5 1.0 1.9 1 .0 1 . D 1.0 1 .0 1.0 3.0 3.S 3.S 2.5 2.0 1.0 1.0 1.8 APA HYDRO-ELECTRIC FEASI81LITY STUDY PREPARED 8Y DRYDEN , LARUE HUMPY CREEK NEAR LARSEN 8AY DATE TIME •••••••• ••••• 04/28182 02:00 04/28/82 04:00 04/28/82 06:00 04/28182 08:00 04/28/82 10:00 04/28182 12:00 04/28/82 14:00 04/28/82 16:00 04/28182 18:00 04/28182 20:00 04/28182 22:00 8YTE RAW DATA •••• • ••••••• 651 65' 661 663 665 661 66' 611 613 615 611 36 102 36 101 36 101 36 102 36 103 36 104 35 lOS 36 106 36 105 36 104 36 103 04/28/82 24:00 61' 36 103 04/29182 02:00 04/29182 04:00 04/2'/82 06:00 04/29182 08:00 04/29182 10:00 04/29182 12:00 04/29182 14:00 04/29182 16:00 04/2'/82 18:00 04/29182 20:00 04/29182 22:00 04/29182 24:00 04/30/82 02:00 04/30/82 04:00 04/30/82 06:00 04/30/82 01:00 04/30/82 10:00 04/30/82 12:00 04/30/82 14:00 04/30/82 16:00 04/30/82 18:00 04/30/82 %0:00 04/30/82 22:00 04/30/82 24:00 DAILY AVERAGE VALUES 681 683 685 681 689 691 693 695 691 '" 101 103 36 103 36 102 36 102 35 lOZ 35 103 35 J 05 36 106 36 106 36 106 36 104 36 103 36 103 DAILY AVERAGE VALUES 10S 101 10' 111 113 115 111 11' 121 123 36 103 36 lOZ 36 lOZ 3S 103 35 103 35 106 36 101 36 101 31 106 31 105 125 36 104 121 36 103 DAILY AVERAGE VA~UES FOUR VI LLAGES DATA FILE HUMP03.POD PAGE 10 88-AUG-83 START TIME 03/31/82 18:00 MV DEPTH INCHES •••• • ••••• 1.2 1.2 1.2 1.2 1.2 1.2 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.2 12 1.2 -28- 14.4 14 . 4 14. 4 14 . 4 14. 4 14.4 14.0 14.4 14.4 14.4 14. 4 14 . 4 14.4 14.4 14.4 14 .4 14.0 14 . 0 14.0 14 . 4 14 . 4 14 . 4 J 4. 4 14 . 4 14. 4 14.3 14 . 4 14 . 4 J 4.4 14. 0 14. 0 14.0 14. 4 14 . 4 14 .8 14.8 14.4 14.4 14.4 STAGE FEET ••••• 1. 20 1. 20 1. 20 1.%0 1 .20 1. 20 1. 11 1.20 1.20 1.%0 1. 20 1. %0 1. 20 1.20 1. 20 1.20 1 . 11 1 . 11 1. 11 1.20 1.20 1. %0 1.20 1 .20 1.20 1 . 1 , 1. 20 t .20 1. 20 1 . 11 1. 11 1 . 11 1.20 1.20 1.23 1. 23 1.20 1.20 1.20 DISCHG CFS • ••••• , . 1 , . 1 , . 1 , . 1 , . 1 '.1 8.3 , . 1 , . 1 , . 1 , . 1 , . 1 '.0 , . 1 , . 1 , . 1 8.3 8.3 8.3 , . 1 , . 1 '.1 , . 1 , . 1 , . 1 8.' , . 1 , . 1 9.1 8.3 8.3 8.3 9 . 1 9.1 9.' 9.9 9.1 9.1 9.0 TEMP DEG C 1.0 0.5 0.5 1.0 1.5 2.0 2.5 3.0 2.5 2.0 1 . 5 1.5 1.6 1.5 1.0 1 . 0 1 . 0 1.5 2.5 3.0 3.0 3.0 2.0 1.5 1.5 1.9 1 . S 1 .0 1.0 1.S 1 . :I 3.0 3.5 3.S 3.0 2. S 2.0 1 5 2.1 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME ••••••••••••• OS/01/82 02:00 05/01/82 04:00 05/01/82 06:00 05/01182 08:00 OS/01/82 10:00 05/01/82 12:00 OS/01/82 14:00 1i5/01/82 16:00 05/01/82 18:00 05/01/82 20:00 05/01/82 U:OO 05/01/82 24.00 05/02/82 02:00 05/02/82 04:00 05/02182 06:00 05/02/82 08:00 05/02/82 10.00 05/02/82 12:00 05/02182 14:00 05/02/82 16:00 05/02/82 18:00 05/02182 20:00 05/02/82 22.00 05/02182 24:00 05/03/82 02:00 05/03/82 04:00 05/03/82 06:00 05/03182 08:00 05/03/82 10:00 05/03/82 12:00 05/03/82 14:00 05/03/82 16:00 05/03/82 18:00 05/03/82 20:00 05/03/82 22:00 1i5/03/82 24:00 BYTE RAW DATA •••• •••••••• 729 36 102 731 36 101 133 36 101 135 35 102 131 34 103 739 35 107 741 36 108 143 31 108 145 38 106 741 31 105 149 31 104 151 31 103 DAILY AVERAGE VALUES 153 36 103 155 36 102 751 36 102 159 35 102 161 35 103 163 36 101 165 36 109 161 31 108 169 38 106 111 31 104 113 31 103 115 36 102 DAILY AVERAGE VALUES 111 119 181 183 185 181 1St 36 102 36 101 36 101 3:; 101 35 103 36106 36 10' 191 36 108 193 37 107 195 31 105 191 31 104 199 36 103 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 11 08-AUG-83 START TIKE 03/31/82 18:00 MV DEPTH INCHES •••• • ••••• 1.2 1.2 1.2 1.0 6.8 1.0 1.2 1.4 1.6 7.4 1.4 7.4 1.2 1.2 1.2 7.2 1.0 1.0 1.2 1.2 1.4 1.6 1.4 1.4 1.2 1.3 1.2 1.2 1.2 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.4 1.2 1.2 14. 4 14 . 4 14.4 14.0 13.6 14.0 14.4 14.8 15.2 14.8 14.8 14.8 14.S 14.4 14.4 14.4 14.0 14.0 14.4 14.4 14.8 15.2 14.8 14.8 14.4 14 . 5 14. 4 14.4 14. 4 14.0 14.0 14.4 14.4 14.4 14.8 14.8 14.8 14.4 14.4 STAGE FEET • •••• 1.20 1 .20 1. 20 1. 11 1. 13 1. 11 1.20 1. 23 1. 21 1. Z3 1.23 1.23 1. 21 1.20 1. 20 1. 20 1.11 1. 11 1. 20 1. 20 1.23 1 .21 1. 23 1 .23 1.20 1. 21 1.20 1. 20 1. 20 1 . 17 1. 17 1.20 1 .20 1. 20 1.13 1. 23 1. 23 1. 20 1. 20 DISCHG CFS • ••••• 9. 1 9 1 9.1 8.3 1.5 8.3 9. 1 9.9 11 9 9 9.9 9.9 9.2 9.1 9. 1 9. 1 8.3 8.3 9.1 9. 1 9.9 11 9.9 9. 9 9. 1 9.3 , . 1 9.1 9. 1 8.3 B.3 9.1 , .1 9. 1 '.9 9.9 '.9 9.1 9.2 TEMP DEC C • •••• 1.0 0.5 0.5 1.0 1 .5 3.5 4.0 4.0 3.0 2. :I 2.0 1.5 2. 1 1.5 1 .0 1. Ii 1.0 1.5 3. S 4.5 4.0 3.0 2.0 1.5 1.0 2.1 1.0 0.5 0.5 O.S 1.5 3.0 4.5 4.0 3.5 2.5 2.0 1.5 2.1 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME :I •••••••••••• 05/04/82 02:00 05/04/82 04:00 05/04/82 06:00 05/04/82 08:00 05/04/82 10:00 05/04182 12:00 05/04/82 14;00 05/04/82 16:00 05/04/82 18:00 05/04/82 20:00 05/04/82 22:00 05/04/82 24:00 05105182 02:00 05/05/82 04:00 05/05/82 06:00 0:)/05/82 08:00 05/05/82 10;00 05/05/82 12:00 05/05/82 14:00 05/05/82 16:00 05/05/82 18:00 05/05/82 20:00 05/05/82 22:00 05/05/82 24:00 05/00182 02:00 05/06182 04:110 05/06182 06:00 05/0cS/82 08:00 05/0cS/82 10:00 05/0cS/SZ 12:00 05/06182 14:00 05/06182 16:00 05/06182 18:00 05/0cS/82 20:00 05/06182 22:00 05/06182 24:00 BYTE RAW DATA •••• • ••••••• 801 36 102 803 36 101 805 36 101 807 36 102 809 35 103 811 36 106 813 3cS 107 815 H 107 817 37 106 819 37 105 821 37 105 823 37 104 DAILY AVERAGE VALUES 825 827 829 831 833 835 837 839 841 843 H5 847 36 104 3cS 103 36 103 36 104 3cS 105 36 105 37 10 cS 38 10cS 38 105 38 104 37 104 37 103 DAILY AVERACE VALUES 849 37 104 851 31 103 853 37 .103 855 33 104 857 38 105 859 39 108 861 43 109 863 46 108 865 47 107 867 46 10cS 869 44 104 871 43 104 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PACE 12 08-AUC-S3 START TIME 03/31/82 18:00 MV DEPTH INCHES •••• • ••••• 7.2 7.2 7.2 7.2 7.0 7.2 7.2 7.2 7 4 7.4 7.4 7.4 7.3 7.2 7.2 7.2 7.2 7.2 7.2 7.4 7.cS 7.cS 7.6 7.4 7.4 7.4 7.4 7.4 7.4 CS.CS 7.6 7.S 8.6 9.2 9.4 9.2 1.8 8.6 1.2 -30- 14.4 14.4 14.4 14.4 14.0 14.4 14.4 14.4 14.8 14. 8 14. 8 14 . 8 14. 5 14.4 14. 4 14.4 14.4 14.4 14.4 14.8 15.2 15.2 15.2 14.8 14.8 14.7 14. 8 14.8 14.8 13.2 1S.2 15.6 17.2 18.4 11.8 18.4 17. 6 17.2 16.3 STACE FEET ••••• 1.20 1.20 1. 20 1. 20 1. 17 1. 20 1. 20 1. 20 1.23 1.23 1.23 1.23 1.21 1.20 1.20 1. 20 1. 20 1. 20 1 20 1. 23 1. 27 1. 27 1. 27 1. 23 1.23 1. 23 1 . :t.3 1.23 1.23 1. 10 1. 27 1.30 1. 43 1 .53 1 . :i7 1.53 1. 47 1. 43 1.36 DISCHC CFS •••••• 9 . 1 9. 1 9. 1 9. 1 8.3 9. 1 9. 1 9. 1 9.9 9.9 9.9 9.9 9.3 9. 1 9.1 , . 1 9. 1 9. 1 9. 1 9.9 11 11 11 9.9 9.9 9.7 9.9 9.9 9.9 6.9 11 12 1& 10 21 20 17 16 14 TEMP DEC C 1 . 0 0.5 0.5 1 .0 1.5 3.0 3.S 3:; 3.0 Z.S 2.5 2.0 2.0 2.0 1 . 5 I.S 2.D 2.5 2. S 3.0 3.0 2.S 2.0 2.0 1.5 2.2 2.0 1.5 1.5 2.0 2. :; 4.0 4.5 4.0 3.5 3.0 2.0 2.0 2.7 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN' LARUE DATA FILE HUKP03.POD PAGE 13 08-AUG-83 HUKPY CREEl NEAR LARSEN BAY START TIKE 03/31/82 18:00 DATE TIKE •••••••• • ••• a 05/07182 02:00 0~/07/82 04:00 0:1/07182 06:00 BYTE RAW DATA •••• • ••••••• 873 875 877 43 104 42 104 42 104 05/07/82 08:00 879 42 105 05/07/82 10:00 881 42 105 05/D7/82 12:00 883 42 107 05/07/82 14:00 885 44 108 05/07/82 16:00 887 4~ 108 05/07/82 18:00 889 45 108 05/07/82 20:00 891 45 107 05/07/82 22:00 893 44 106 0~/07/82 24:00 895 44 105 05/08/82 02:00 05/08/82 04:00 05/08182 06:00 05/08/82 08:00 05/08182 10:00 05/08/U 12:00 05/08/82 14:00 05/08/82 16:00 05108182 18:00 05/08182 20:00 05/08/82 22:00 05/08/82 24:00 05/09182 02:00 05/09182 04:00 05/09lU 06:00 O~/09/U 08:00 05/09182 10:00 05/09182 12:00 05/09182 14:00 05/09182 16:00 05/09/U 18:00 05/09182 20:00 05/09/82 22:00 05/09/82 24:00 DAILY AVERAGE VALUES 897 899 901 903 90~ 907 909 911 43 105 43 105 43 105 44 105 45 106 H 107 49 108 52 108 913 56 107 915 58 106 917 57 105 919 56 105 DAILY AVERAGE VALUES 921 923 925 55 105 55 105 55 ID4 9Z7 5~ 10:i 929 55 106 931 55 106 933 56 109 935 58 109 937 59 107 939 59 106 941 58 104 943 57 104 DAILY AVERAGE VALUES DEPTH STAGE DISCHG KV INCHES FEET CFS •••• • ••••• ••••• •••••• 8.6 8.4 8.4 8.4 8.4 8.4 8.8 9.0 9.0 9.0 8.8 8.8 8.7 8.6 8.6 8.6 8.8 9.0 9.2 9.8 10.4 11. 2 11 . 6 11. 4 11 .2 9.' 11. 0 11.0 11.0 11.0 11.0 11.0 11.2 11.6 11.8 11 .8 11 .6 11 . 4 11. 3 -31- 17.2 16.8 16.8 16.8 U.8 16.8 17.6 18 0 18.0 18.0 17.6 17.6 17.3 17. 2 17.2 17.2 17.6 18.0 18.4 19.6 20.8 22.4 23.2 22.8 22.4 19.7 22.0 22.0 2Z.0 n.o n.o 22.0 22.4 23.2 23.6 23.6 23.2 22.8 22.6 1.43 1. 40 1. 40 1. 40 1. 40 1. 40 1. 47 1. 50 1. 50 1. 50 1. 47 1. 47 1.44 1.43 1. 43 1. 43 1. 47 I. 50 1. 53 1.63 1. 73 1. 87 1.93 1 .90 1. 87 1. 64 1.83 1.83 1. 83 1. S3 1.83 1.83 1. 87 1.93 1.97 1.97 1. 93 1. 90 1.88 16 15 15 15 15 15 17 18 18 18 17 17 16 U 16 16 17 18 20 24 29 37 41 39 37 26 35 35 35 n 35 35 37 41 44 44 41 39 38 TEMf DEG C ••••• 2.0 2.0 2.0 2.4 2.S 3.5 4.0 4.0 4.0 3.5 3.0 2.5 3.0 2.5 loS 2.5 ,.S 3.0 3.S 4.0 4.0 3.5 3.0 z.~ 2.S 3.0 2.5 2.5 2.0 Z.5 3. D 3.0 4.5 4.5 3.S 3.0 2.0 2.0 2.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 05/10/82 02:00 05/1018204:00 05/10/82 06:00 05/10/82 08:00 05/10/82 10:00 05/10/82 12:00 05/10/82 14:00 05/10/82 16:00 05/10182 18:00 05110/82 20:00 05/10182 22.00 05/10/82 24;00 05/11182 02:00 05/11/82 04:00 05/11/82 06:00 05/1118% 08:00 05/11/82 10:00 05/11/8212:00 05/11182 14:00 05111182 16:00 05/11182 18:00 05/11/82 20:00 05111182 22:00 05/11182 24:00 05/12/82 02:00 05/12182 04:00 05112/82 06:00 05/12182 08:00 05/12182 10:00 05/12182 12.00 05/12/82 14:00 05/12/82 16:00 05/12/82 18:00 05/12/82 20:00 05/12/82 22:00 05/12/82 24:00 BYTE RAW DATA •••• •••••••• 945 941 949 951 953 955 951 959 961 963 965 961 51 104 56 104 56 103 56 104 56 106 56 101 56 109 51 110 58 108 58 101 51 106 56 105 DAILY AVERAGE VALUES 969 911 913 915 911 979 981 983 985 981 989 991 56 104 55 104 55 103 56 104 55 106 55 107 56 108 51 108 51 107 51 106 56 105 56 104 DAILY AVERAGE VALUES 993 55 103 995 55 10% 991 55 102 999 54 103 1001 55 105 1003 55 108 1005 55 109 1001 56 109 1009 S6 108 1011 55 107 1013 55 105 1015 55 104 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 14 08-AUG-83 START TIME 03/31/82 18:00 DEPTH STAGE MV INCHES _... . ..... 11 .4 11 .2 11. 2 11 . 2 11. 2 11. 2 11. 2 11. 4 11. 6 11.6 11 .4 11. 2 11. 3 11. 2 11.0 11.0 11.2 11.0 11.0 11. 2 11 .4 11. 4 11 .4 11 .2 11. 2 11.2 21.8 21.4 22.4 22.4 22.4 22.4 22.4 22.8 23.2 23.2 22.8 21.4 22.6 22 4 22..0 22.0 22.4 22.0 22.0 22.4 22.8 22.8 22.8 22.4 22.4 22. . 4 11.0 22.0 11.0 22.0 11.0 22.0 10.8 21.6 11.0 22.0 11.0 22.0 11.0 22.0 11.2 21.4 11.2 22.4 11.0 22.0 11.0 22.0 11.0 22.0 11.0 22.0 -32- FEET ••••• 1.90 1.81 1." 1. 87 1.87 1. 87 1. 87 1. 90 1. 93 1.93 1.90 1. 81 1.89 1. 87 1. 83 1.83 1. 81 1.83 1. 83 1. 87 1.90 1. 90 1. 90 1.87 1. 81 1.16 1. 83 1.83 1. 83 1.80 1. 83 1. 83 1. 83 1.87 1.87 1. 83 1. 83 1.83 1. 84 DISCHC eFS • ••••• 39 37 37 37 37 31 37 39 41 41 39 37 38 37 35 35 37 35 35 37 39 39 39 37 31 37 35 35 35 33 35 35 35 37 37 35 35 35 35 TEMP DEG C • •••• 2.0 2.0 1.5 2.0 3.0 3.S 4.5 5.0 4.0 3.!l 3.0 2.S 3.0 :LO 2.0 1.5 2.0 3.0 3.5 4.0 4.0 3.5 3.0 2.5 2.0 2.1 1.5 1.0 1 .0 1 . S 2.5 4.0 4.5 4.5 4.0 3.S 2.5 2.0 2. 'i APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN & LARUE DATA FILE HUMP03.POD PAGE 15 08-AUG-a3 HUMPY CREEK NEAR LARSEN BAY START TIME 03/31/82 18:00 DATE TIME a •••••••••••• 05113/82 02:00 05/13/82 04:00 05/13/82 06:00 05/13182 08:00 05/13/82 10:00 05/13/81 11:00 05/13182 14:00 05113/82 16:00 05/13/82 18:00 05/13182 20:00 05/13/82 22:00 05113/82 24:00 05/14/81 02:00 05/14182 04:00 05/14/82 06:00 05/14182 D8:00 05/14/82 10:00 05/14/82 12:00 05/14/82 14:00 05/14/82 16:00 05/14/82 18:00 05114182 20:00 05/14/82 22:00 05114/82 24:00 05/15182 02:00 05115/81 04:00 05/15/82 06:00 0:1115182 08:00 05115/82 10:00 05/15/82 12:00 05/15/82 14:00 05/15182 16:00 05115/82 18:00 05/15/82 %0:00 05/15182 22:00 05/15/82 24:00 BYTE RAY DATA •••• • ••••••• 1017 1019 1021 1023 1025 1027 1029 1031 1033 1035 103'1 1039 55 103 54 102 54 102 53 102 :53 106 :53109 55 111 54 110 55109 55 107 55 106 54 104 DAILY AVERAGE VALUES 1041 1043 1045 1047 1049 1051 10:53 1055 10:57 10:59 1061 1063 54 103 54 102 54 102 53 104 53 105 54 107 54 111 55 111 55 11 0 55 108 55 106 54 104 DAILY AVERAGE VALUES 1065 1067 1069 1071 ID73 1075 to 77 54 103 54 103 54102 :13 lOZ 52 106 54 111 54 112 1079 54 111 1081 55 110 1083 55 107 1015 55 106 1087 54 104 DAILY AVERAGE VALUES DEPTH STAGE DISCHC MV INCHES FEET eFS •••• • ••••• 11.0 22.0 10.8 21.6 10.8 21.6 10.6 21.2 10.6 21.2 10.6 21.2 11.0 22.0 10.8 21.6 11.0 22.0 11.0 22.0 11.0 22.0 10.8 21.6 10.8 10.8 10.8 10.8 10.6 10.6 10.8 10.8 11 . 0 11 .0 11 .0 11. 0 10.8 10.8 10.8 10.8 10.8 10.6 10.4 10.8 10.8 10.8 11. 0 11 .0 11.0 10.8 10.8 -33- 21.1 21 .6 21.6 21.6 21.2 21.2 21.6 21.6 22.0 22.0 22.0 2Z.0 21.6 21.1 21.6 21.6 21.6 Z 1 • Z 20.8 21.6 21.6 21.6 22.0 22.0 22.0 21.6 21.6 • •••• 1.83 1. 80 1. 80 1.1'1 1.77 1 .77 1.13 1. 80 1. 83 1.83 1.13 1.80 1.81 1. 80 1. 80 1. 80 1.77 1 .1'1 1. 80 1. 80 1.83 1.83 1.83 1.83 1. 80 1.81 1. 80 1. 80 1. 80 1. 77 1. 13 1. 80 1. 80 1. 80 1.83 1.83 1 .83 1. 80 1. 80 • ••••• 35 33 33 31 31 31 35 33 35 35 35 33 33 33 33 33 31 31 33 33 35 35 35 35 33 33 33 33 33 31 29 33 33 33 35 35 3:i 33 33 TEMP DEG C • •••• 1.5 1.0 1.0 1.0 3.0 4.5 S.5 5.0 4.5 3.5 3.0 2.0 3.0 1.5 1.0 1.0 2.0 2.5 3.5 5.5 5.S 5.0 4.0 3.0 2.0 3.0 1 . 5 1.5 1.0 1.0 3.0 5.5 6.0 5.5 S.O 3.5 3.0 2.0 3.~ APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PRIPARED BY DRYDEN & LARUE DATA FILE HUKP03.POD PAGE 16 08-AUG-U HUKPY CREEl NEAl LARSEN BAY START TIKE 03/31/B2 18:00 DATE TIl'll •••••••• ••••• 0~/16182 02:00 O~/16/U 04:00 0~/16182 06:00 05/1&182 08:00 05/U/U 10:00 OHU/82 12:00 05/16182 14:00 n/16182 16:00 OHU/82 18:00 05/16/82 20:00 05/16182 22:00 05/1&1B224:00 05/17182 02:00 05117182 04:00 05/17182 0&:00 05/17182 08:00 05/17/82 10:00 0~/17182 12:00 05/17182 14:00 05/17182 16:00 05/17182 18:00 05/17/82 20:00 05/17/82 22:00 05/17182 24:00 OSl18/82 02:00 05/18/82 04:00 05/18/82 0&:00 05/18/82 08:00 05/18/82 10:00 05118182 12:00 05/18182 14;00 05/18/82 16:00 05/18182 18:00 05118182 20:00 05/18/82 22:00 05/18/82 24;00 BYTE RAW DATA •••• •••••••• 1089 54 103 IOU 53 102 1093 53 102 1095 52 102 1091 52 106 1099 54 112 1101 54 114 1103 54 113 1105 54 111 1101 54 108 1109 54 106 1111 54 105 DAILY AVERAGE VALUES 1113 1115 1111 1119 1121 1123 1125 1121 53 105 53 104 53 104 52 106 52 109 53 112 53 113 ~3 112 1129 S3 111 1131 ~3 109 1133 53 107 1135 52 106 DAILY AVERAGE VALUES 1137 1139 1141 1143 1145 1147 1149 11' 1 1153 1155 1157 1159 52 105 52 104 52 105 51 10& SO 108 52 110 52 111 54 110 55 109 55 101 5&106 55 In DAILY AVERAGE VALUES DEPTH STAGE DISCHG KV INCHES FEET CFS _... . ..... 10.8 10.6 10.6 10.4 10.4 10.8 10.8 10.8 10 .8 10.8 10.8 10.8 10.7 21.6 21.2 21.2 20.B 20.8 21. 6 21.6 21.6 21.6 21.6 21.6 21.6 21.4 10.6 21.2 10.6 21.2 10.6 21.2 10.4 20.B 10.4 20.B 10.6 21.2 10.6 21.2 10.6 21.2 10.6 10.' 10.6 10.4 10.6 10.4 10.4 10.4 10.2 10.0 10. 4 10.4 10.8 11. 0 11. 0 11. 2 11.0 10.6 -34- 21.2 21.2 21.2 20.8 21. 1 20.8 20.B 20.8 ZO.4 20.0 20.8 20.8 21.6 22.0 22.0 22.4 22.0 21.2 ••••• 1. 80 1. 77 1. 71 1. 73 1. 73 1. BO 1. 80 1. 80 1. 80 1.80 1. 80 1. 80 1. 78 1. 77 1. 77 1.77 1.73 1. 73 1. 77 1. 71 1.71 1. 77 1. 77 1. 77 1. 73 1.76 1. 73 1. 73 1.73 1. 70 1. 61 1 .73 1. 73 1. 80 1. B3 1 .83 1. 87 1.83 1.77 • ••••• 33 31 31 29 29 33 33 33 33 33 33 33 32 31 31 31 H 29 31 31 31 31 31 31 29 31 29 29 19 27 U 29 29 33 35 35 37 35 31 TEMP DEC C • •••• 1.5 1.0 1.0 1.0 3.0 6.0 7.0 6.5 5.S 4.0 3.0 2.5 3.5 2.~ 2.0 2.0 3.0 4.5 '-0 6.5 6.0 ~.5 4.~ 3.5 3.0 4. 1 2.5 2.0 ,,5 3.0 4.0 5.0 5.S 5.0 4.5 3.5 3.0 2.5 3.6 APl HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN & LARUE DATA FILE HUMP03.POD PAGE 11 08-AUC-83 HUMPY CREEK NEAR LARSEN BAY START TIKE 03/31/82 18:00 DATE TIME s •••••••••••• 05/19/82 02:00 05119182 04:00 05/19182 0&:00 05/19/82 08:00 05/19/82 10:00 05/19182 12:00 05/19/82 14:00 05/19/82 16:00 05/19/H 18:00 05/19182 20:00 05/19182 22:00 05/19/82 24:00 05/20/82 02:00 05/20182 04:00 05/20/82 04:00 05/20/82 08:00 05/U/82 10:00 05/20/82 12:00 1i5/20/82 14:00 05/20/82 16:00 05/ZO/82 18:00 OS/20/82 20:00 05/20182 22:00 OH20/82 24:00 01121/82 02:00 05/Zl/82 04:00 05/21/82 06:00 U/Zl/82 08:00 OS/U/82 10:00 05/Zl/82 12:00 05/U/82 14:00 G5/Zl/SZ 16:00 05/21/82 18:00 BYTE RAW DATA •••• • ••••••• 1161 55 105 1163 54 105 1165 54 104 1161 53 104 1169 53 101 1111 52 110 1113 54 113 1115 54 112 1111 55 110 1119 55 loa 1181 55 101 1183 55 105 DAILY AVERAGE VALUES 1185 54 105 1111 54 105 1189 53 105 1191 53 10& 1193 53101 1195 53109 1191 :;3 III 1199 H 111 1201 53 111 1203 54 109 1205 53 101 1201 53 10& DAILY AVERAGE VALUES 1209 1211 1213 121 5 1211 1219 1221 1223 1225 53 104 53 105 52 106 52 106 52 108 52 III 53 11 5 54 114 54112 05/21/82 20:00 1221 54 110 05/21/82 22:00 1229 54 108 05/21/82 24:00 1231 54 106 DAILY AVERAGE VALUES DEPTH STAGE DISCHe MV INCHES FEET CFS =... . ....• 11.0 10.8 10.8 10.6 10.6 10.4 10.8 10.8 11.0 11.0 11. 0 11.0 10.8 10.8 10.8 10.6 10.6 10.6 10.& 10.6 10.6 10.6 10.8 10.6 10.6 10 .1 22.0 21.6 21. & 21.2 21.2 20.8 21.6 21. & 22.0 22 .0 22.0 22.0 21.6 21. & 21.6 21.2 21. 2 21.2 21.2 21.2 21.2 21.2 21.6 21.2 21.2 21.3 10.6 21.2 10.6 21.2 10.4 ZO.8 10.4 ZO.8 10.4 ZO.8 10.4 ZO.8 10.6 21.2 10.8 21.6 10.8 21.6 10.8 10.8 10.8 10.6 -15- 21.6 21. 6 21.6 21. 2 ••••• 1. 83 1. 80 1. 80 1.11 1.11 1.13 1. 80 1. 80 1. 83 1. 83 1. 83 1. 83 1. 80 1. 80 1. 80 1. 11 1. 11 1. 11 1. 11 1. 11 1.11 1.11 1. 80 1.11 1.11 1. 18 1. 11 1. 11 1. 13 1. 13 1.13 1. 13 1.11 1. 80 1. 80 1. 80 1. 80 1. 80 1.11 • ••••• 35 33 33 31 31 29 33 IJ 35 35 35 35 as 33 33 31 H 31 31 31 31 JI 33 31 31 31 31 31 29 H H 29 31 33 33 33 33 33 31 TEMP DEC C • •••• 2.5 2.5 2.0 "Ii a.s 5.0 &.;) 6.0 5.0 4.0 3.5 2.5 3.& 2.:; 2.5 2.5 3.0 3.5 4.5 5.5 5.5 :;.5 4.5 3.5 3.0 3.8 3.0 2.5 3.0 3.0 4.0 5.5 1.5 1.0 6.0 5.0 4.0 J.O 4.5 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 05/22/82 02:00 05122182 04:00 05/22/82 06:00 05/22/82 08:00 05/22/82 10:00 05/22/82 U:OO 05/22/U 14:00 05/22/82 16:00 05/22/82 18:00 05/22/82 20:00 05/21/12 22:00 BYTE RAW DATA •••• • ••••••• n33 1235 U37 1239 1241 1243 1245 1247 1249 U51 U53 54 104 54 104 53 103 52 104 52 108 53 112 53 115 53 115 53 112 54 110 53 108 05/22/82 24:00 1255 53 107 05l23/U 02:00 05/23182 04:00 05/23/82 06:00 05/23/82 08:10 0~/23/82 10:00 05/23/82 12:00 05123182 14:00 05/23/82 16:00 05/23182 18;00 05/23/82 20:00 05123/82 22;00 OS/23/82 24:00 05124/82 02;00 05124/82 04:00 05/24/82 06:00 05124182 08:00 OH24/SZ 10:00 0:;/24/82 12:00 05/24182 14:00 05124/82 16;00 OS/24/SZ 18:00 05/24/82 20:00 OS/24/82 22:00 05/24/SZ 24:00 DAILY AVERAGE VALUES U57 U59 1261 1263 1265 un 1269 U71 12 7 3 1275 12 77 1279 53 106 53 106 53 106 53 107 53 107 53 108 53 109 53 108 $3 108 53 108 53 107 53 107 DAILY AVERAGE VALUES 1281 1283 12n 53 106 53 IDS 52 105 li17 52 105 1289 53 106 U91 53 107 1293 53 107 1295 52 108 1297 52 108 un 53 108 1301 53106 1303 52 104 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 18 08-AUG-1l START TIME 03/31/82 18:00 DEPTH STAGE MV INCHES s... . ..... 10.8 21.6 10.8 21.6 10.6 21.2 10.4 20.8 10.4 20.8 10.6 21.2 10.6 21.2 10.6 21.2 10.6 21.2 10.8 21.6 10.6 21.2 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 10.4 10.6 10.6 10.6 10.4 10.4 10.6 10.6 10.4 10.5 -36- 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21.2 21 .2 21.2 21 .2 21.2 21.2 20.8 20.8 21.2 21. 2 21.2 20.8 20.8 21.2 21.2 20.8 21.0 FEET ••••• 1. 80 1. 80 1.77 1. 73 1. 73 1. 77 1. 77 1.77 1. 77 1. 80 1. 77 1. 77 1.77 1.77 1. 17 1. 77 1. 17 1. 77 1. 71 1. 11 1. 71 1.11 1. 11 1.71 1. 71 1. 17 1. 77 1. 17 1. 73 1. 73 1. 71 1. 77 1. 77 1. 73 1. 73 1.11 1. 11 1 .73 1. 15 DnCHC crs • ••••• U 33 31 29 29 31 31 31 31 33 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 29 H 31 31 31 29 29 31 31 29 30 TEMP DEG C . ..... 1.0 2.0 1 . 5 2.0 4.0 6.0 7.5 7.5 6.0 ~.O 4.0 3.5 4.3 3.0 3.0 3.0 3. 5 3.5 4.0 4.5 4.0 4.0 4.0 3.~ 3.5 3.6 3.0 2.5 2.5 2.5 3.0 3.~ 3.5 4.0 4.0 4.0 3.0 1.0 3. 1 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 05125/82 02:00 05125112 04:00 05125/12 06:00 05125182 08:00 05/U/U 10:00 U125/U 12:00 05125/82 14:00 05/25/82 16:00 05125181 18:0D 05/25/12 20:00 05/25/82 2%:OD 05125/12 24:00 05/16/12 02:00 OSI26182 04:00 05/26182 06:00 05/16/82 08:00 05/26/12 10:00 05/16/12 12:00 05/26/82 14:00 05/26/82 16:00 05/26/82 18:00 05/16/82 20:00 05/26/82 22:00 05126182 24:00 05/U/U 02:00 OS/U/U 04;00 05121/82 06:00 OS/U/U 08:00 05/%7/82 10:00 05121182 12:00 OS/211U 14:00 05/27182 16:00 05/21/82 18:00 05/U/82 20:00 05/21/82 21:00 05/21182 24:00 BYTE RAW DATA •••• •••••••• 1305 1301 1309 1311 1313 1315 1317 13U 1321 1323 1325 In1 52 104 a 104 51 104 51 105 51 109 51 112 51 114 51 113 52 111 52 110 51 109 51 108 DAILY AVERAGE VALUES 1329 51 108 1331 51 108 1333 51 108 1335 51 109 1331 51 110 1339 52 112 1341 54 111 1343 55 111 1345 56 111 1341 5. 110 1349 56 108 1351 51101 DAILY AVERAGE VALUES 1353 57 101 1355 58 101 13H 58 101 1359 51 101 1361 :is 108 1363 59 109 1365 58 109 1361 58 109 1369 59 109 1311 59 108 1313 59 101 1315 59 101 DAILY AVERACE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 19 08-AUG-13 START TIME 03/31/82 18:00 DEPTH STAGE DISCHG TEM' MV INCHES •••• • ••••• 10.4 20.8 10.4 20.8 10.2 20.4 10.2 20.4 10.2 20.4 10.2 20.4 10.2 20.4 10.2 20.4 10.4 20.8 10.4 20.8 10.2 20.4 10.2 20.4 10.3 20.5 10.2 20.4 10.2 20.4 10.2 20.4 10.2 20.4 10.2 20.4 10.4 20.8 10.8 21.6 11.0 22.0 11.2 21.4 11.2 22.4 11. 2 11 .4 10.1 11. 4 11.6 11.6 11. 6 11.6 11.8 11.6 11.6 11. 8 11.8 11 . B 11.8 11 . 1 -'0- 22.4 22. I U 4 22.8 23.2 23.2 23.2 23.2 23.6 23.2 23.2 23.6 23.6 23.6 23.6 23.3 FEET ••••• 1. 13 I. 13 I. 10 1. 10 1. 10 1. 10 1. 10 1. 10 1. 13 1.13 1. 10 1. 10 1. 11 1.10 1. 10 1. 10 1. 10 1. 10 1.13 1.80 1. 83 1.81 1." 1.81 1. 90 1. 1 B 1.90 1.93 1.93 1. 93 1. 93 1.91 1. 93 1. 93 1.97 1.91 1. 91 1. 91 1. 94 CFS • ••••• 29 29 27 Z7 27 21 27 27 19 29 21 21 28 21 27 21 21 21 2f 33 35 31 31 31 39 32 39 41 41 41 41 44 41 41 44 44 44 44 42 DEG C • •••• i II 2.0 1.0 2.5 4.5 6.0 1.0 6.5 5.5 S.O 4.5 4.0 4.3 4.0 4.0 4.0 4.5 5.0 '-0 5.5 5.5 S.5 LO 4.0 3.5 4.1 3.5 3.S 3.5 3.S 4.0 4.5 4.5 4.5 4.5 4.0 3.5 3.S 3.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 05/28/82 02:00 05/28/82 04:00 05/28/82 0&:00 05/28182 08:00 05/28/82 10:00 05/28/82 12:00 05/28/82 14:00 05/28/8216:00 05/28/82 18:00 05/28/82 20:00 OS/28/8222:00 05/28/82 24:00 65/29/82 02:00 05/29/8204:00 05/29/82 06:00 05/29/82 08:00 05/29/82 10:00 05/29182 12:00 65/29/82 14:00 05/29/8216:00 05/29/82 18:00 05/29/82 20:00 05/29182 22:00 05/29182 24:00 05/30/82 02:00 05/30/82 04:00 05/30/82 06:00 05/30/82 08:00 05/30/82 10:00 05/30/82 12:00 05/30/82 14:00 05/30/82 16:00 05/30/82 18:00 05/30/82 20:00 05/30/82 22:00 05/30/82 24:00 BYTE RAW DATA •••• • ••••••• 1377 1379 1381 1383 1385 1387 1389 60 106 6010& 59 10& 59 107 58 108 59 11 0 59 112 1391 59 112 1393 59 110 1395 59 109 1397 59 107 1399 59 106 DAILY AVERAGE VALUES 1401 1403 1405 1407 1409 1411 1413 1415 59 106 58 107 59 107 58 108 SP 109 59 110 58 112 H 114 1417 59 112 1419 59 110 1421 59 109 1423 59 107 DAILY AVERAGE VALUES 1425 1427 1429 59 106 60 106 59 106 1431 H 108 1433 59 112 1435 59 113 1437 59 114 1439 59 114 1441 59 113 1443 60 111 1445 60 109 1447 59 108 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP03.POD PAGE 20 D8-AUG-83 START TIME 03/31/82 18:00 MV DEPTH INCHES •••• • ••••• 12 . 0 12.0 11 .8 11. 8 11. 6 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.8 11.6 11.8 11. 6 11.8 11 .8 11 .6 11.8 11 .8 11 .8 11 .8 11. 8 11.8 11. 8 12.0 11 .8 11 .6 11.8 11 . II 11 .8 11 .8 11 .8 12.0 12.0 11 .8 11.8 -38- 24.0 24.0 23.6 23.6 23.2 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.2 23.6 23.2 23.6 23.6 23.2 23.6 23.6 23.6 23.6 23.6 23.5 23.6 24.0 23.6 23.2 23.6 23.6 23.6 23.6 23.6 24.0 24.0 23.6 23.7 STACE FEET • •••• 2.00 2.00 1.97 1.97 1.93 1.97 1.97 1.97 1.97 1.97 1.97 1.97 1.97 1.97 1.93 1.97 1.93 1.97 1.97 1. 93 1.97 1.97 1.97 1.97 1.97 1.96 1.97 2.00 1. 97 1.93 1.97 1.97 1.97 1.97 1.97 2.00 2.00 1.9? 1.97 DISCHC CFS •••••• 46 46 44 44 41 44 44 44 44 44 44 44 44 44 41 44 41 44 44 41 44 44 44 44 • 44 43 44 46 44 41 44 44 44 44 44 46 46 44 44 TEMP DEG C .zz •• LO 3.0 3.0 3.5 4.0 ~.O 6.0 6.0 :> . 0 4.5 3. :> 3.0 4 . 1 3.0 LS 3.5 4.0 4.5 5.0 6.0 7.1 6.0 5.0 4.S 4.6 3.0 3.0 3.0 4.6 6.0 6.5 7.0 7.0 6.5 5.5 4.5 4.0 S.O 1PA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 05/31/82 02:00 05/31/82 04:00 05/31182 06:00 05/31/82 08:00 05/31/82 10:00 05/31/82 11:00 05/31/82 14:00 05/31/82 16:00 05/31/82 18'00 05/31/82 %0:00 05/31112 22:00 05/31/82 24:00 06/01182 02:00 06101/82 04:00 06101182 06:00 06101/82 08:00 06/01/82 10:00 06/01/82 11:00 06101182 14:00 06101/82 16:00 06101/82 18:00 06101/82 20:00 06/01/82 21:00 06101182 24: 00 06102182 02:00 06102/82 04:00 06102/82 06:00 06lOZ/82 08:00 06102/82 10:00 06102/82 11:00 06102/82 14:00 06102/82 16:00 06102182 18:00 06102/82 20:00 06102182 22:00 06102/82 24:00 BYTE RAW DATA s ••••••••••• 1449 5'1 101 1451 st 108 1453 5'1 101 1455 58 108 1457 58 111 145'1 5t 114 1461 59 116 1463 60 116 1465 60 114 1467 61 111 1469 60 lOt 1471 60 107 DAILY AVERAGE VALUES 1473 1475 1477 147t 1481 1483 1485 1487 148'1 1491 1493 1495 60 107 60 106 60 106 59 108 59 111 60 114 60 116 61 116 61 114 61 112 60 110 60 109 DAILY AVERAGE VALUES 149 7 1499 1501 1503 1505 1507 61 109 60 108 60 108 60 109 60 109 59 111 150'1 59 114 1511 60 114 1513 60 113 1515 60 110 1517 60 108 1519 60 107 DAILY AVERAGE VALUES FOUR VI LUGES DATA FILE HUMPG3.POD PAGE 21 DB-AUC-83 START TIME 03/31/12 11:00 DEPTH STAGE DISCHC TEMP MV INCHES •••• • ••••• 11 .8 11.8 11.8 11. 6 11.6 11.8 11 .8 12.0 12.0 12.2 12.0 11.0 11 .9 23. , Z3.6 23. , 23.2 23.2 23.6 23.6 24.0 24.0 24.4 24.0 24 0 23.7 12.0 14.0 11.0 24.0 11.0 24.0 11.8 23.6 11.8 23.6 12.0 24.0 12.0 24.0 12.2 24.4 12.2 24.4 12.2 24.4 12.0 24.0 12.0 24.0 12.0 12.2 12.0 12.0 12.0 H.O 11.1 11.8 12.0 12.0 11.0 11.0 11.0 12.0 -39- 24.0 24.4 24.0 24.0 24.0 l4.0 23.6 23.6 24.0 24.0 24.0 24.0 24.0 24.0 FEET ••••• 1.97 1.97 1.97 1.93 1. 93 1.97 1.97 2.00 2.00 2.03 2.00 2.00 1.98 2.00 2.00 2.00 1.97 1.97 2.00 2.00 2.03 2.03 2.03 2.00 2.00 2.00 2.03 2.00 2.00 2.00 2.00 1.97 1.97 2.00 2.00 2.00 2.00 2.00 2.00 crs • ••••• 44 44 44 41 41 44 44 46 46 49 46 46 45 49 49 49 47 47 49 49 52 52 52 49 49 49 52 49 49 49 49 47 47 49 49 49 49 49 49 DEC C • •••• 4.6 4.0 4.0 4.0 5.5 7.0 8.0 B.O 7.0 6.0 4.5 3.5 S.S 3.5 3.0 3.0 4.0 S.S 7.0 1.0 8.0 7.0 6.0 5.0 4.5 5.4 4.5 4.0 4 . 0 4.5 4.5 5.5 7.0 7.0 ... S S.O 4.0 3.5 5.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMFY CREEK NEAR LARSEN BAY DATE TIME = •••••••••••• 06103/81 02:00 06/03/82 04:00 06/03/82 06:00 06/03182 08:00 06103/82 10:00 D6/D3/81 12:00 06103/82 14:00 06103/82 16:00 06103182 18:00 06/03/82 20:00 06103112 22:00 06/03/82 24:00 116/04/82 02:00 06104/82 04:00 06104182 06:00 06/04/82 OS:OO D6/04/81 10:00 06/04/82 12:00 06/04/S2 14:00 06104182 16:00 06104/82 IS:00 06/04182 20:00 06104/S2 22:00 06/04/81 24:00 06/oS/82 02:00 06/05/82 04:00 06/05182 06:00 06/05/82 OS:OO 06/05/82 10:00 06/05/82 12:00 04/05182 14:00 06/05/82 16:00 06115/82 18:00 06/05/82 20:00 06lOS112 22:00 06/05/82 24:00 BYTE RAW DATA •••••••••••• lS21 1523 1525 1527 1529 1531 1533 153S 1537 60 106 60 105 Sf 105 58 106 Sf 110 5P 115 60 117 60 117 59 115 1539 60 112 1541 60 110 1543 5P IDS DAILY AVERAGE VALUES 1545 1547 1549 1551 1553 1555 59 108 59 lOS 59 109 58 109 59 111 60 112 1557 60 114 1559 60 114 1561 61 112 1563 61 110 1565 61 110 IS67 60 IDS DAILY AVERAGE VALUES 1569 59 108 1571 60 108 1573 59 108 1575 59 109 1577 59 110 ISH 59 112 1581 60 112 1583 U 113 un 60 112 1587 61 111 1589 61 110 1591 61 109 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUKP03.POD PACE 22 0'-AUC-S3 START TIME 03/31/82 1':00 DEPTH STACE DISCHC MV INCHES FEET CPS •••• • ••••• 14.0 24.0 14.0 24.0 11.' 23.6 11.6 23.2 11.8 23.6 11.8 23.6 12.0 24.0 14.0 24.0 11.S 23.6 12.0 12.0 11 .• 11.9 11.8 II.' 11. S 11. 6 11 .• 12.0 12.0 12.0 12.2 14.2 12.2 12.0 12.0 24.0 24.0 23.6 23.' 23.6 23.6 23.6 23.2 23.6 24.0 24.0 24.0 24.4 Z4.4 24.4 24.0 23.' I1.S 23.6 12.0 24.0 11.S 23.6 11.8 23.6 11.8 23.6 11.8 23.6 12.0 24.0 12.0 24.0 12.0 24.0 12.2 24.4 12.2 24.4 12.2 24.4 12.0 23.9 -40- ••••• 2.00 2.00 1. 97 1.93 1. 97 1.97 2.00 2.00 1. 97 2.00 2.00 1.97 1. 98 1. P? 1.97 1.97 1. 93 1.97 2.00 2.00 2.00 2.03 2.03 2.03 2.00 1.99 1. 97 2.00 1.97 1. 97 1. 97 1.97 2.00 2.00 2.00 2.03 2.03 2.03 1.99 •••••• 49 49 47 44 47 47 49 49 47 49 49 47 48 47 41 47 44 47 49 49 49 52 52 52 49 49 47 49 47 41 47 47 49 49 49 52 51 52 49 TEMP DEC C • •••• 3.1i 2.S 2.5 3.0 5.0 7.5 '.5 8.5 7.5 6.0 5.0 4.0 5 3 4.0 4.0 4.::; 4.5 5.S 6.0 7.0 ? Ii 6.0 5.0 5.0 4.0 5.2 4.0 4.0 4.0 4. ::; 5.0 6.0 6.0 6.5 6.' 5.5 5.0 4.5 5. 1 lPA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAl LARSEN BAY DATE TIME •••••••• ••••• 06/06182 02:00 06106182 04:00 06/06182 06:00 06/06182 08:00 06106182 10:00 06/04/82 12:00 06/16/82 14:00 06106/82 16:00 06106/82 18:00 06/06/82 20:00 06''''82 U:OO 06/06182 24:00 06107182 02:00 06101182 04:00 06107182 06: 00 06101182 08:00 06/01182 10:00 06107/8% U:OO 06/01182 14:00 06101182 16:00 06/01182 18:00 06101182 20:00 06/01182 U:OO 06/01182 24:00 06108/8% 02:00 06108/82 04:00 06108/82 06:00 06/08/82 08:00 U/08/8% 10:00 06/08/8% U:OO 06/08/82 14:00 06/08/82 16:00 06/08/82 18:00 0610818% 20:00 06108/82 22:00 06/08/82 24:00 BYTE RAW DATA • ••••••••••• 1593 1595 1591 1599 1001 1003 16 OS 1607 U 109 U 109 U 108 61 109 62 110 60 11 0 61 112 61 112 1609 61 111 1611 61 110 1613 60 109 1615 60 109 DAILY AVERAGE VALUES 1611 1019 1621 1623 1625 1621 60 108 60 108 60 108 59 109 60 110 60 111 1029 60 113 1631 60 113 1633 59 112 1035 60 111 1631 59 109 1039 59 108 DAILY AVERAGE VALUES 1641 59 108 1043 59 108 un 59 108 1041 51 109 1649 5& 111 1651 59 114 1653 58 116 1055 58 116 1651 59 114 1659 59 112 1661 59 11 0 1063 59 109 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 23 08-AUG-1l START TIME 03/31/82 18:00 DEPTH STAGE DISCHe INCHES FEET CFS •••• • ••••• ••••• •• = ••• U.2 12.2 12.2 12.2 12.4 12.0 12.2 12.2 12.2 U.2 12.0 12.0 12.2 12.0 12.0 12.0 11 .8 12.0 12.0 12.0 12.0 11.8 12.0 11.8 11. 8 11 .9 11. 8 11. 8 11.8 11.6 11. 6 11. 8 11 .6 11.6 11 . 8 11. 8 11.8 11.8 11 .1 -41- 24.4 24.4 24.4 24.4 24.8 24.0 24.4 24.4 24.4 24.4 24.0 24.0 24.3 24.0 24.0 24.0 23.6 24.0 24.0 24.0 24.0 23.6 24.0 23.6 23.6 23.9 23.6 23.6 Z3.6 23. Z 23.2 23.6 13.2 %3.2 23.6 23.6 23.6 23.6 23.5 2.03 2.03 2.03 2.03 2.01 2.00 2.03 2.03 2.03 2.03 2.00 2.00 2.03 2.00 2.00 2.00 1.91 2.00 2.00 2.00 2.00 1.97 2.00 1.91 1.91 1.99 1.91 1.97 1.97 1. 93 1.93 1.97 1.93 1. 93 1. 91 1.91 1.91 1.91 1.96 S2 52 52 52 54 49 52 52 52 52 49 49 :H 49 49 49 41 49 49 49 49 41 49 41 41 48 41 41 41 44 44 41 44 44 41 41 41 41 46 TEMP DEC; C • •••• 4.5 4.5 4.0 4.5 5.0 5.0 6.0 6.0 5.S 5.0 4.5 4.5 4.9 4.0 4.0 4.0 4. :) 5.0 5.5 6.5 6.5 6.0 5.5 4.5 4.0 5.0 4.0 4.0 4.0 4.:) 5. :> 1.0 8.0 8.0 ? . 0 6.0 5.0 4.$ 5.6 1PA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUKPY CREEK NEAR LARSEN BAY DATE TIKE 06/09112 02:00 06109182 04:00 0610918% 06:00 06109182 08:00 06109182 10:00 06109182 12:00 06/09182 14:00 06/09182 16:00 06109112 18:00 116109/82 20:00 06119182 22:00 06109/82 24:00 06/10112 02:00 06/10/82 04:00 06110/82 06:00 06110182 08:00 06/10/82 10:00 06110/82 12:00 06/10/82 14:00 06/10/82 16:00 /)6/10/82 18;00 06/10/12 20:00 06/10182 22:00 06/10/82 24:00 06111/82 02:00 06/11182 04:00 06/11/82 06:00 06111/82 08:00 06/11/82 10:00 1i6111/82 12:00 06/11/82 14:00 06111182 16:00 06/11/82 18:00 06/11/82 20:00 IIYTE RAW DATA •••••••••••• 1665 1667 1669 5& 109 59 109 51 109 1671 58 109 1673 57 111 1675 58 115 1677 57 116 1679 57 117 1681 58 116 1613 58 114 1685 S. 112 1687 58 111 DAILY AVERAGE VALUES 1689 1691 1693 1693 1697 1699 170 1 1703 1705 58 110 58 109 57 109 57 111 57 113 59 115 57 116 58 11 5 57 111 1707 57 111 1709 57 110 1711 57 109 DAILY AVERAGE VALUES 1713 57 109 1715 S7 lOP 1717 56 108 1719 56 110 17%1 56 110 1723 56 111 17U 56 111 172? 56 112 1729 56 112 1731 56 111 06/11/.2 22:00 1733 56 109 06/11/82 24:00 1735 56 108 DAILY AVERACE VALUES FOUR VI LUGES DATA FILE HUKP03.POD PACE 24 08-AUG-II START TIKE 03/31/12 18:00 DEPTH STACE DISCHC INCHES FEET eFS •••• aa: ••• 11.6 11.8 11.6 11.6 11.4 11. 6 11 .4 11. 4 11. 6 11. 6 11.6 11.6 11. 6 %3.2 23.6 23.2 23.2 22. I 23.2 12.8 22.8 23.2 %3.2 23.2 23.2 23.1 11.6 23.2 11.6 23.2 11.4 22.8 11.4 22.8 11.4 n.8 11.8 23.6 11.4 22.8 11.6 U.2 11.4 22.8 11. 4 11. 4 11 .4 11 .5 11 .4 11. 4 11.2 11.2 11. 2 11. 2 11. 2 11.2 11. Z 11.2 11. 2 11 .2 11 .2 -47- n.8 22.8 22.8 U.O 22.8 22.8 22.4 22.4 22.4 22.4 n.4 22.4 12.4 22.4 22.4 n.4 22. :5 • •••• 1.93 1.97 1.93 1.93 1.90 1. 93 1 .90 1.90 1. 93 1. 93 1.93 1.93 1. 93 1. 93 1.93 1. 90 1.90 1. 90 1.97 1.90 1.93 1. 90 1. 90 1. 90 1. 90 1.91 1.90 1. 90 1. 87 1. 87 1. 87 1. 87 1. 87 1. 87 1. 87 1. 87 1. 87 1.87 1. 87 • ••••• 44 47 44 44 42 44 42 42 44 44 44 44 44 44 44 42 H 42 4? 42 44 42 42 42 42 43 42 42 40 40 40 40 40 40 40 40 40 40 40 TEMP DEC e ._ ... 4.5 4.5 4.5 4.5 5.5 '1.5 &.0 8.S &.0 7.0 6 . 0 5.5 6.2 S.O 4.5 4.5 5. :s 6.5 7.5 8.0 7.5 6.0 S.S 5.u 4.5 5 .• 4.5 4.5 4.0 5.0 5.0 5.S 5.5 6.0 6.iI ~.5 4.5 4.0 5.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• :a •••• 06112/82 02:00 06/12/82 04:00 00/12/82 00:00 06/12/82 08:00 06112182 10:00 06/12/8% 12:00 06/12/82 14:00 86/12/82 16:00 06/12/82 18:00 06/12/82 20:00 0611218% 22:00 06/12182 24:00 06/13/82 U:OO 00/13/82 04:00 06/13/82 06:00 06/13/82 OS:OO 06113182 10:00 06113112 12:00 06113/82 14:00 06113/82 16:00 06113/82 18:00 06113/82 20:00 06/13/82 22:00 00/13/82 24:00 00114/82 02:00 06114/82 04:00 06114/82 06:00 06l14/U 08:00 06114/82 10:00 06114/82 12:00 BYTE RAW DATA :a... . •.•.•.• 1737 1739 1741 1743 1745 1741 1749 1751 1753 1755 1757 1759 56 107 55 107 54 107 55 108 55 112 5S 114 54 113 54 113 55 112 55 110 55 109 55 108 DAILY AVERAGE VALUES 1761 1763 176:i 176 7 1769 1771 1773 1775 1777 1779 1781 1783 54 108 54 107 54 108 54 108 53 109 53 112 :5 3 114 S3 114 53113 54 112 53 110 53 109 DAILY AVERAGE VALUES t 785 1787 1789 17 " 1793 1795 53 108 53 108 53 108 51 10? 53 110 S2 11 2 06/14/82 14:00 1797 53 114 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP03.POD PAGE 25 08-AUG-83 START TIME 03/31/82 18:00 DEPTH STAGE DISCHG MV INCHES FEET CFS :I... . ..... 11.2 22.4 11.0 22.0 10.8 21.6 11.0 n.o 11.0 22.0 11.0 22.0 10.8 21.6 10.8 21.6 11.0 22.0 11.0 22.0 11.0 22.0 11.0 22.0 11.0 21. 9 10.8 21.6 10.8 21.6 10.8 21.6 10.8 21.6 10.6 21.2 10.6 21.2 10.6 21.2 10.6 21.2 10.6 21.2 10.8 21.6 10.6 21.2 10.6 21.2 10. 7 10.6 10.6 10.6 10.4 10.6 10.4 10.6 10.5 -4~- 21.4 21.2 21.2 21.2 ZO.8 21.2 20.8 21.2 21. 1 ••••• 1. 87 1. 83 1. 80 1. 83 183 1.83 1. 80 1. 80 1.83 1.83 1. 83 1. 83 1.83 1. 80 1. 80 1.80 1. 80 1. 77 1. 77 1. 77 1. 77 1. 77 1. 80 1.77 1. 77 1. 78 1. 77 1. 77 1. 77 1. 13 1. 77 1. 73 1. 77 1.76 • ••••• 40 38 36 38 38 38 36 36 38 38 38 38 38 36 36 36 36 34 34 34 34 34 36 34 34 35 34 34 34 32 34 32 34 34 TEMP DEG C • •••• 3.S 3.5 3.S 4.0 6.0 7.0 6.5 6.5 6.0 S.O 4.3 4.Ci S.O 4.0 3.5 4.Ci 4.0 4.~ 6.0 7.0 7.0 6.5 6.0 5.0 4 • :5 5.2 4.0 4.0 4.0 4.:1 5.0 6.0 7.0 4.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRIDEN , LARUE HUMPY CREIK NEAR LARSEN BAY DATE TIME 06/15/SZ 04:00 06i15/SZ 08:00 06/15/SZ 12:00 06/15182 16:00 06/15/SZ 20:00 06/15/82 24:00 06/16/SZ 04:00 06/16/82 08:00 06/16/82 12:00 06/16/8216:00 06/16/82 20:00 06/16/SZ 24:00 06/1'7182 04:00 06/1'7182 08:00 06/17/82 12:00 06/17/SZ 16:00 06/17/SZ 20:00 06/17182 24:00 06/18/SZ 04:00 06/18/SZ 08:00 06/18182 12:00 06/18/82 16:00 06118182 20:00 06/1818224:00 06119182 D4:0D 06l19/SZ 08:00 06/19/8212:00 06/19/82 16:00 Q6/U/82 20:00 06/19/SZ 24:00 BYTE RAW DATA 1 31 108 3 31 108 5 31 111 7 31 114 9 31 114 11 30 111 DAILY AVERAGE VALUES 13 30 10'7 15 30 106 1'7 29 111 19 30 116 Z1 30 116 23 29 112 DAILY AVERAGE VALUES 25 %7 29 29 107 29 107 29 111 31 29 114 33 29 115 35 29 111 DAILY AVERAGE VALUES 37 39 41 43 4S 47 19 110 29 lH 28 111 30 11 5 29 115 29 113 DAILY AVERAGE VALUES 49 51 53 29111 29 110 29 112 55 29 114 57 29 114 H Z8 112 DAILY AVERACE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 1 06-AUG-8~ START TIME 06/15/82 04:00 MV DEPTH INCHES =... :_== •• 6.2 6.2 6.2 6.2 6.2 6.0 6.2 6.0 6.0 5.8 6.0 6.0 5. B 5.9 5.8 5.8 5.8 5.8 5.8 5.8 :i.8 5.8 5.8 5.6 6.0 5.8 5.8 ~.8 5.8 5.8 5.8 5.8 5.8 5.6 5.8 -44- 12.4 12.4 12.4 12.4 12. 4 12.0 12. 3 12.0 12.0 11.6 12.0 12 . 0 11 . 6 11 .9 11 .6 11 .6 11. 6 11 . 6 11.6 11 . 6 11.6 11. 6 11 . 6 11 . Z 12.0 11 . 6 11 . 6 11 .6 11.6 11. 6 11.6 11 .6 11 . 6 11.2 11 . 5 STAGE FEET 1.73 1. '73 1. 73 1. 73 1.73 1. '70 1. H 1." 1.69 1.66 1.69 1.69 1.66 1.68 1 .65 1. 65 1 .65 1.65 1 .65 1. 65 1. 65 1.65 1.65 1.61 1.68 1.65 1. 65 1. 65 1.64 1.64 1 .64 1 .64 1.64 1.61 1.64 DISCHG CFS = ••••• 30 30 28 30 30 28 28 28 28 2Ii 28 28 Z8 28 26 29 28 28 28 28 28 28 28 28 26 27 TEMP DEG C 4.u 4.0 5.5 '7.0 7.0 S.5 5.5 3.5 3.0 5.5 8.0 B.O 6.0 5.'7 ~ ~ ". oJ 3.5 5.5 7.0 7.5 5.5 5.4 5.0 4.5 S.S 7.5 '7.5 6.5 6.1 5.5 S.1i 6.0 7.0 '7.0 6.1i 6. 1 APA HYDRO-ELECTRIC FEASIBILITY STUDY ; FOUR VILLACES PREPARED BY DRYDEN & LARUE DATA FILE HUMP04.POD PACE 2 08-AUC-83 HUMPY CREEK NEAR LARSEN BAY START TIME 06/15/82 04:00 DATE TIME == ••••••••••• 06110/82 04:00 06/20/82 08:00 06110/82 12:00 06/20/81 16:00 06120/82 20:00 06120/82 24:00 06/21/81 04:00 06/21/81 08:00 06121/U U:OO 06121/81 16:00 06/21/82 20:00 06l21/U 24:00 06/12/81 04:00 06/21/82 08:00 06122/81 12:00 06121/81 16:00 06/22/81 10:00 06/22182 24:00 06123/82 04:00 06/23/82 08:00 06/23/U 12:00 06/U/U 16:00 06/U/82 20:00 06/23/82 24:00 06/24182 04:00 06/24/1Z 08:00 06/24182 12:00 06/24/1Z 16:00 06124/1Z 10:00 06/24181 24:00 BYTE RAW DATA •••• •••••••• 61 28 110 63 28 110 6~ 28 112 67 28 113 69 n 114 71 28 112 DAILY AVERACE VALUES 73 7S 27 11 0 27 110 77 28 113 79 Z9 117 81 28 118 83 27 114 DAILY AVERAGE VALUES 8~ 27 112 87 27111 89 27 111 '1 27 116 '3 27 11~ ,~ 27 112 DAILY AVERACE VALUES 97 2'1 11 0 " 26 110 101 26 111 103 17 114 105 27 115 107 26 113 DAILY AVERACE VALUES 10' 16 111 111 26 111 113 26 112 115 21 116 111 27 119 119 26 117 DAILY AVERACE VALUES DEPTH STAGE DISCHG MV INCHES FEET CFS • :f.. :I ••••• • •••• • ••••• 5.6 5.6 5.6 5.6 s.a 5.6 5.6 S.4 5.4 ~.6 s.a 5.6 5.4 :LS 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 S.2 5.2 5.4 5.4 ~.2 5.3 5.£ 5.1 5.2 5.4 S.4 5.2 5.3 11. 2 11 .2 11.2 11 . 2 11. 6 11. 2 11. 3 10.8 10.8 11.2 11. 6 11. 2 10.8 11 . 1 10.8 10.8 10.8 10.a 10.a 10.8 10.8 10.8 10.4 10.4 10.8 10.8 10. 4 10. 6 10.4 10.4 10.4 10.8 10.8 10.4 10.5 1 .60 1. 60 1. 60 1.60 1. 64 1. 60 1.61 1.51 1. 57 1. 60 1.63 1.60 1. ~ 7 1. 59 1.56 1. 56 1.50 1 .56 1. 56 1.56 1.56 1.56 1 .51 1. S2 1. 56 1.56 1.:iZ I.H I.H 1. 52 1. 52 1. 5~ 1. 55 1 .52 1.53 26 26 26 26 27 26 26 24 24 U 27 26 24 25 24 24 24 24 24 24 24 24 22 22 24 24 22 23 U 22 22 23 13 21 U TEMP DEC C ••••• S.O 5.0 6.0 6.5 7.0 6.0 S.' 5.0 ~.O 6.5 1.5 '.0 1.0 6.8 6.0 5.S 6.0 8.0 7.5 6.0 6.S 5.0 5.0 5.S 7.0 7.5 6.S 6. 1 5.~ S.S 6.0 8.0 L:i 8.5 7.2 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 06/25/82 04:00 061l~/82 08:00 0612~/U 12:00 06/25/82 16:00 06/25182 20:00 06/2~/82 24:00 06/26/82 04:00 06/26/82 08:00 06/26182 12:00 06/26/82 16:00 06/26182 20:00 06/26182 24:00 06/21182 04:00 06/21182 08:00 06121182 12:00 06/27/82 16:00 06/21181 20:00 06/21182 24:00 06/28182 04:00 06/28182 08:00 06128/82 12:00 06128/82 16:00 06/28/82 20:00 06/28182 24:00 06/29/82 04:00 06/29182 08:00 06/29182 12:00 06129182 16:00 06/29182 20:00 06/29182 24:00 BYTE RAW DATA • s •••••••••• 121 26 114 123 26 114 125 26 11~ U1 28 120 129 21 120 131 27 117 DAILY AVERAGE VALUES 133 21 114 13~ 26 114 137 21 114 139 28 116 141 21 116 143 26 114 DAILY AVERAGE VALUES 145 26 112 141 26 112 149 21 112 151 28 113 153 29 114 155 28 113 DAILY AVERAGE VALUES 151 26 112 159 26 111 161 21 113 163 Z8 116 165 26 115 161 U 113 DAILY AVERAGE VALUES 169 111 26111 25 111 113 26 112 115 21 113 111 21 113 119 21 112 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP04.POD PAGI 3 08-AUG-83 START TIME 06/15/82 04:00 DEPTH STACE DISCHe MV INCHES FEET CFS •••• =-s=-••• ••••• • ••••• 5.2 5.2 5.2 5.6 5.6 5.4 5.4 ~.4 5.2 5.4 5.6 5.4 5.2 5.4 5.2 5.2 5.4 5.6 5.1 5.6 5.5 5.2 5.2 5.4 5.6 5.2 S.2 5.3 5.Z 5.0 5.2 5.4 5.4 5.4 5.3 -46- 10.4 10.4 10.4 11.2 11. 2 10.8 10.1 10:8 10. 4 10. 8 11. 2 10.8 10.4 10.1 10.4 10.4 10.8 11 .2 11. 6 11 .2 10.9 10 . 4 10. 4 10.8 11.2 10.4 10.4 10.6 10. 4 10.0 10.4 10.8 10.8 10.8 10.l 1.St 1. 51 LSI 1. 58 1. 58 1.55 1.54 1.54 LSI 1 .54 1. 57 1. 54 1. 51 La 1. 50 1. SO 1.54 1.57 1. 60 1. 57 1. 55 1. SO 1. 50 1. 53 1.56 1. SO 1. 50 1. 51 1. 49 1.46 1.49 1. 53 1. 53 1. 53 1. 50 n 22 22 2S 25 23 23 23 22 23 24 23 22 23 21 21 23 24 21 21 22 21 20 21 22 22 22 22 TEMP DEG C ••••• 7.0 7.0 7.5 10.0 10.0 8.S 8.3 7.0 1.0 1.0 8.0 8.0 7.0 1.3 6.0 6 Ii 6.0 6.5 7.0 6.5 6.3 6.0 5.5 6.5 8.0 7.5 6.5 6.1 S.5 !i. :; 6.0 6.S 6.3 6.0 6.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME =.=~8 ••• 8 •••• 06130/82 04:00 0./30/82 08:00 06/30/82 12:00 0./30182 U:OO 06130/82 20:00 0"30/82 24:00 07/01/82 04:00 07/01/82 08:00 07/01/82 12:00 07/01/82 U:OO 07/01/82 20:00 07/01/82 24:00 07/02182 04:00 07/02/82 08:00 07/02182 12:00 BYTE RAW DATA •••• • ••••••• 181 183 185 187 U 111 n 111 30 112 30 114 189 3Z 114 191 29 113 DAILY AVERAGE VALUES 193 Z8 111 195 27 111 197 21 112 199 27 114 201 U 115 203 26 113 DAILY AVERAGE VALUES 205 207 209 U 111 H 110 27 111 07/02/82 16:00 211 28 113 07/02/82 20:00 213 28 115 07/02/82 24:00 215 27 113 07/03/82 04:00 07/03/82 08:00 07/03/82 12:00 07/03/82 U:OO 07/03/82 20:00 07/03/82 24:00 07/04/82 04:00 07/04/82 08:00 DAILY AVERACE VALUES 217 26 111 219 U 111 221 26112 223 27 115 225 27 115 227 27 113 DAILY AVERAGE VALUES 229 231 U 111 26 111 07/04/82 12:00 233 27 113 07/04/82 16:00 235 28 115 07/04/82 20:00 237 28 114 07/04/82 24:00 239 29 112 DAILY AVERACE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 4 08-AUG-83 START TIME 06/15/82 04;00 MV 5.6 5.8 6.0 6.0 6.4 5.8 5.9 5.6 5.4 5.4 5.4 5.6 S.2 5.4 5.2 5.2 5.4 5.6 5 . 6 5.4 5.4 5.2 5.2 5.2 5.4 5.4 S.4 5.3 S.2 5.2 5 .4 S.6 5.6 5.8 5.S -47- DEPTH INCHES 11 . 2 11.6 12.0 12.0 12.8 11 .6 11 . 9 11. 2 10. 8 10.8 10. 8 11. 2 10. 4 10.9 10. 4 10.4 10.8 11 . 2 11. 2 10 . 8 10. 8 10.4 10. 4 10. 4 10.8 10.8 10.8 10.6 10.4 10. 4 10.8 11 . 2 11. 2 11 .6 10.9 STAGE FEET 1. 55 1 .59 1.62 1.62 1.69 1.59 1.61 1 .55 1.52 1. 52 1.52 1. 55 1.48 1 .52 1. 48 1. 48 1.51 1. :54 1. :54 1 . 51 1.51 1. 47 1. 47 1.47 1.51 1 . :i 1 1.51 1.49 1. 47 1.47 1. 50 1.53 1.53 1.57 1.51 DISCHG CFS 24 25 27 21 30 25 U 21 21 22 23 23 22 22 20 20 20 22 22 22 21 20 20 21 23 23 24 22 TEMP DEG C • •••• 5.5 5.5 6.0 7.0 7.0 6.5 6.3 S.S 5.5 6.0 7.0 7. :; 6.S 6.3 5.0 5.5 6.5 7.5 6.5 6. 1 S.S 5.5 6.0 7.S 7.5 6.S 6.4 5.5 5.5 6.5 7.5 7.0 6.0 6.3 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME ;....... . .... 07/05/82 04:00 07/05/U 08:00 07/05/U 12:00 07/05/82 16:00 07/05182 10:00 07/05/82 24:00 07/06/U 04:00 07/06182 D8:0D 07/06/82 12:00 07/06182 16:00 07/06182 20:00 07/06182 24:00 07/07/82 04:00 07/07/82 08:00 07/07/82 12:00 BYTE RAW DATA =... . ...... . 241 %8 lit 243 27 110 245 27 112 247 27 114 249 27 115 251 27 113 DAILY AVERAGE VALUES 253 Z6 111 25S Z6 110 257 27 112 23'1 27 117 261 28 117 263 27 115 DAILY AVERAGE VALUES 26 113 Z6 112 26 113 07/07/82 16:00 271 27 117 07/07/82 20:00 273 26 118 07/07/82 24:00 275 26 116 07/08/82 04:00 07/08/82 08;00 07/08/82 12:00 07/08/82 16:00 07/08/8% 20:00 07/08/82 24:00 07/0718204;00 G7/09l82 08:00 07/09/821200 07109/82 16;00 07/09/82 20:00 07/09182 24;00 DAILY AVERAGE VALUES 277 279 281 283 25 113 25 112 25 114 26 120 285 25 120 287 24 117 DAILY AVERAGE VALUES Z89 HI 24 114 24 113 293 24 114 295 24118 297 24 119 299 Z4 117 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE S 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES :s... . ..... 5.6 5.4 5.4 S.4 S.4 5.4 5.4 5.2 5.2 5.4 5.4 5.6 5.4 5.4 S.2 5.2 5.2 5.4 5.2 5.2 S.2 5.0 5.0 S.O 5.2 5.0 4.6 5.0 4.8 4.8 4.8 4.8 4.8 4.8 4.8 -48- 11.2 10.8 18.8 10.8 10.8 10.8 10.9 10.4 10.4 10.8 10. 8 11. 2 10.8 10.7 10.4 10.4 10.4 10.8 10.4 10.4 10. S 10.0 10.0 10.0 10.4 10.0 9.6 10.0 9.6 9.6 9.6 '.6 9.6 9.6 9.6 STAGE DlSCHG FEET CFa ••••• 1.53 1.50 1.50 1. 50 1. SO 1. SO 1. 50 1.46 1.46 1.49 1.49 1.52 1.49 1. 48 1.4 S 1. 4S I.U 1.49 1. 45 1.4S 1. 46 1. 41 1.41 1.41 1. 4S 1 41 1.38 1.41 1. 38 1.31 1.38 1. 38 1 . 3Ii 1 .38 1. 38 •••••• 23 21 21 21 21 21 21 20 20 21 21 22 Z1 21 20 20 20 21 20 ZO 20 18 18 18 19 18 1 ? 18 1 ? 17 17 17 17 17 17 TEMP DEG C • •••• S.5 S.O 6.0 7.0 7.5 6.5 6.3 S.S 5.0 6.0 8.5 8.5 7.5 6.& 6.5 6.0 6.S 8.5 9.0 B.O 7.4 6.5 6.0 7.0 10.0 10.0 B.S B.a 7.0 6 . S 7.0 1.0 9.5 &.5 7.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEX NEAR LARSEN BAY DATE TIME . =-s..... . .... 01/10/82 04:00 01110182 08:00 01/10/82 12:00 01/10/82 16:00 01/10/82 20:00 01/10/82 24:00 01/11/8204:00 01111/82 08:00 01/11/82 12:00 01111182 16:00 01/11182 20:00 01111/82 24:00 01112/82 04:00 01112/8208:00 01/12/U 12:00 0'7/12/82 16:00 01/12/82 20:00 01112/82 24:00 01/13/82 04:00 01/13/82 08:00 0'7113/8212:00 01/13/82 16:00 01/13/82 20:00 01/13/82 24:00 01/14/82 04;00 01/14/82 08:0D 01/14/82 12:00 01/14/82 16:00 01/14/82 20;00 01/14/U 24:00 BYTE RAW DATA •••••••••••• 301 24 113 303 24 112 305 24 114 301 24 118 309 24119 311 24 111 DAILY AVERAGE VALUES 313 25 114 315 2l 113 311 24 114 319 25 119 321 25 120 313 25111 DAILY AVERAGE VALUES 325 321 20 114 26 112 329 H 114 331 20 111 333 21 116 335 28 114 DAILY AVERAGE VALUES 331 339 341 343 345 26 113 26 112 26 114 26 115 21 115 341 26 114 DAILY AVERACE VALUES 349 351 353 H 113 26 112 26 113 355 26 114 351 20 116 359 26 115 DAILY AVERACE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 6 OB-AUG-8S START TIME 06/15/82 04:00 MV 4.8 4.8 4.B 4.8 4.8 4.8 4.8 5.0 j.O 4.8 5.0 5.0 S.O ~.O S.2 5.2 5.2 5.2 5.4 5.6 5.3 5.2 5.2 5.2 5.2 5.4 5.2 5.2 5.2 5.2 5.2 52 S.2 5.2 5.2 -49- DEPTH INCHES 9.6 9.6 9.6 9.6 9.6 9.6 9.6 10.0 10.0 9.6 10.0 10.0 10.0 9.9 10.4 10 4 10.4 10 . 4 10. B 11.2 10.6 10. 4 10.4 10. 4 10 . 4 10.8 10. 4 10.5 10.4 10 4 10 4 10.4 10.4 10.4 10.4 STAGE FEET ••••• 1. 31 1 .3'7 1.31 1. 31 1. 31 1.31 1 . 31 1.40 1.40 1.31 1 40 1.40 1. 40 1.39 1.43 1. 43 1. 43 1. 43 1. 46 49 1.44 1.42 1.42 1.42 1.42 1.46 1.42 1.43 1 42 1. 42 1.42 1. 42 1.42 1. 42 1.42 D IStRe. eFS 11 11 11 11 17 11 11 18 1& 11 18 18 1& 18 19 19 19 19 zo 21 19 19 19 19 19 20 1 9 1 9 18 18 1 & 18 18 18 18 TEMP DEC C .a=== 6.5 6.0 1.0 9.0 9.S 8.5 7.1i 7 0 6.5 1.0 9.5 10. 0 Ii.S 8.1 7.0 6.1i 7.0 8.S B.O '7.0 1.3 6.S 0.0 7.0 7 . 5 7.5 7.0 6.9 6.5 6.0 6.5 7.0 8.0 7.5 6.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME 07/15/82 04:00 07/15/82 08:00 07/15/82 12:00 07/15/82 16:00 07/15/82 20:00 07/15/82 24:00 07/16182 04:00 07/16/82 08:00 07/16/8212:00 07/16182 16:00 07/16/82 20:00 07/16/82 24:00 07/17/82 04:00 07/17/82 08:00 07/17/8212:00 07/17/82 16:00 07/17/8220:00 BYTE RAY DATA •••• • •••••• s 361 363 365 367 369 371 26 113 26 112 26 113 27 115 27 116 28 115 DAILY AVERAGE VALUES 373 375 377 27 113 27 113 27 114 379 27 118 381 26 117 383 26 115 DAILY AVERAGE VALUES 385 387 389 391 393 26 114 Z6 113 26 113 26 115 27 11 ~ 07/17/82 24:00 395 26 114 07/18/8204:00 07/18/82 08:00 07/18/82 12:00 07/18/82 16:00 07/18/82 20:00 07/18/8224:00 07/1"82 04:00 07/19/82 08:00 07/19/8212:00 07/19/82 16:00 07/19/82 20:00 07/19/8224:00 DAILY AVERAGE VALUES 397 399 401 403 405 407 26 113 26 113 26 114 27 118 26 118 26 116 DAILY AVERAGE VALUES 409 411 413 26 114 26 113 26 115 415 26 122 417 26 124 419 26 119 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 7 08-AUG-83 START TIME 06/15/82 04:00 MV 5.2 5.2 5.2 5.4 5.4 5.6 5.3 5.4 5.4 5.4 5.4 5.2 :i.2 5.3 5.2 5.2 :i.2 5.2 5.4 5.2 5.2 S.2 5.2 S.2 5.4 5.2 5.2 5.2 5.2 5.2 S.2 5.2 S.2 S.2 S.2 -50- DEPTH INCHES 10. 4 10.4 10. 4 10 . 8 10. 8 11 . 2 10. 7 10. 8 10. 8 10 . 8 10.8 10. 4 10. 4 10 . 7 10. 4 10.4 10 . 4 10. 4 10. 8 10.4 10. 5 10 . 4 10. 4 10. 4 10.8 10.4 10.4 10.5 10. 4 10. 4 10. 4 10. 4 10. 4 10. 4 10. 4 STAGE FEET 1 . 41 1. 41 1 . 41 1.45 1.4S 1 .48 1. 43 1.44 1.44 1 . 44 1.44 1 . 41 1. 41 1.43 1.40 1.40 1. 40 1.40 1.44 1.40 1 . 4 1 1.40 1.40 1.40 1.43 140 1.40 1.40 1.39 1.39 1.39 1 .39 1.39 1.39 1.39 DISCHG CFS 18 18 18 19 l'i 21 1 If 19 19 19 19 18 18 19 18 18 18 18 19 18 !Ii 18 18 18 19 18 18 18 18 18 16 18 18 18 18 TEMP DEG C 6.S 6.0 6.5 7.5 8.0 7.5 7.0 6.:; 6.5 7.0 9.0 8. 5 7. j 7.:; 7.0 6.5 6.5 7.5 7.5 7.0 7.0 6.5 6.5 7.0 9.0 9.0 8.0 7.7 7.0 6.5 7. S 11 . 0 11 . 0 9.5 B.8 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME ==s_=.:a •• s ••• 01120/82 04:00 01120/82 08:00 01120/82 12:00 01120/82 16:00 01120/82 20:00 01120182 24:00 01121/8204:00 01121/82 08:00 01121/82 12:00 01121/82 16:00 01121182 20:00 07/21/82 24:00 07/22182 04:00 01112/82 08:00 01122/82 12:00 01112182 16:00 01122/8220:00 01112/8214:00 01123/82 04:00 01123/82 08:00 01123/82 12:00 01123/82 16:00 01123/82 20:00 07/23/8224:00 01124/82 D4:00 01124/82 08:00 01124/B212:00 01114/82 16:00 01124/82 ZO·OO 01i14/8224:00 BYTE RAW DATA 421 26 III 423 26 114 425 26 115 421 26 119 429 26 120 431 26 118 DAILY AVERAGE VALUES 433 435 437 439 21 116 21 115 26 115 26 116 441 26 116 443 26 115 DAILY AVERAGE VALUES 445 441 449 21 114 26 114 26 115 451 Z6 118 453 26 119 455 21 118 DAILY AVERAGE VALUES 457 31 111 459 3D 111 461 28 118 463 28 121 465 28 120 461 21118 DAILY AVERAGE VALUES 4H 411 413 27 116 26 116 26 117 475 26 122 471 26 122 419 25 119 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 8 OB-AUG-83 START TIME 06/15/82 04:00 MV 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.4 5.4 5.2 S.' 5.2 5.2 5.3 5.4 5.2 5.2 5.2 5.2 5.4 S.3 6.2 6.0 5.6 5.6 5.6 l.4 5.1 5.4 5.2 5.2 5.2 :;.2 5.0 5.2 -'11- DEPTH INCHES 10. 4 10.4 10.4 10. 4 10. 4 10. 4 10. 4 10.8 10. 8 10. 4 10. 4 10.4 10.4 10. 5 10. B 10.4 10. 4 10. 4 10. 4 10.8 10 . l 12. 4 12.0 11 .2 11. 2 11 . 2 10. 8 11 . :; 10.8 10 . 4 10.4 10.4 10. 4 10. 0 10. 4 STAGE FEET 1.39 1.39 1.39 1.39 1.39 1.39 1.39 1.42 1. 42 1.38 1.38 1.38 1.38 1.39 1.41 1.38 1.38 1.38 1.38 1.41 1.39 1.54 1 . 51 1.44 1. 44 1.44 1 . 41 1.46 1 . 40 1.31 1.31 1.31 1.31 1.33 1.37 DISCHG CFS 1 'i 11 17 11 17 17 17 18 18 11 11 17 11 18 18 11 11 11 11 18 11 23 22 19 19 19 18 20 1 B 11 17 11 11 16 11 TEMP DEG C ••••• 7. S 1.0 1.5 9.5 10.0 9.0 8.4 8.0 7.5 1.5 8.0 B.O 1. S 7.8 7.0 1.0 1.5 ~ 0 9.5 9.0 8.2 8.5 8.S 9.1i 10. S 10.0 9.0 9.3 8.0 8.0 B.S 11 . 0 11 . 0 9.5 9.:; APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME 01125182 04:00 01125/82 08:00 01125/82 12:00 61125/82 1&:00 01125182 20:00 01125/82 24:00 01126182 04:00 01126/82 08:00 61126/82 12:00 01126/82 16:00 01126/82 20:00 01126/82 24:00 01121182 04:00 01121182 08:00 01121182 12:00 01121182 16:00 01121182 20;00 01121182 24:00 01128/82 04:00 01128182 08:00 01128/82 12:00 01128/82 16:00 61128182 20:00 01128/82 24:00 011291SZ 04:00 011H/82 08:00 01129182 12:00 01129/82 16:00 01129182 20:00 01129182 24;00 BYTE RAW DATA .. :-....... . 481 483 483 481 489 4U 25 111 2611& 25 111 25 120 25 120 25 118 DAILY AVERAGE VALUES 493 495 491 499 501 25 111 25 115 25 111 25 119 24 120 503 24 119 DAILY AVERAGE VALUES :'iDS 25 111 501 24 115 'S09 24 116 511 23 120 513 24 119 515 24 118 DAILY AVERAGE VALUES 511 519 521 523 525 521 2S 116 24116 23 116 24 111 24 118 24 116 DAILY AVERAGE VALUES H9 531 25 116 25 116 533 25 111 53S 25 120 531 24 120 539 24 118 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP04.POD PAGE 9 as-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• S.O S.2 5.0 5.0 5.0 S.O 5.0 5.0 5.0 5.0 5.0 4.8 4.8 4.9 5.0 4.8 4.8 4.6 4.8 4.8 4.8 5.0 4.8 4.6 4.8 4.8 4.8 4.8 5.0 S.O 5.0 5.0 4.8 4.8 4.9 10.0 10.4 10.0 10.0 10.0 10.0 10.1 10.0 10.0 10 . 0 10.0 9.6 9.6 9.9 10.0 9 6 9.6 9.2 9.6 9.6 9.6 10.0 9.6 9.2 9.6 9.6 9.6 9.6 10.0 10.0 10.0 10.0 9.6 9.6 9.9 STACE FEET 1 .33 1.36 1. 33 1. 33 1. 33 1.33 1.33 1.32 1.32 1.3Z 1.32 1.29 129 1. 31 1 . 32 1 .29 1.29 1. 25 1.29 1 . 29 1.29 1 31 1. 28 1 25 1.28 1.28 1. 28 1.28 1.31 1.31 1 . 31 1. 31 1.28 1.28 1.30 DISCHC CFS U 11 16 16 16 16 16 15 15 15 1 S 14 14 15 15 14 14 13 14 14 14 14 13 14 14 14 14 1 :; 15 15 IS 14 14 IS TEMP DEG C 8.5 8.0 Ii.S 10 . Ii 10.0 9 0 9.0 8.5 7.5 8.5 9.5 10.0 9.S 8.9 8 :; 1.5 8.0 10. 0 '.5 9 Ii 8.8 8.0 8.0 8.0 8.5 9.0 8.0 8.3 8.0 8.0 8.5 10 . 0 10.0 9.0 8 , APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 01130/82 04:00 01/30/82 08:00 01130/82 12:00 01/30182 16:00 01130/82 20:00 01130/82 24:00 01131/82 04:00 01131/82 01:00 01131/82 12:00 01/31/82 16:00 01/31182 20:00 01131/82 24:00 08/01/82 04:00 08101182 08:00 08/01182 12:00 08/0118216:00 08101/82 20:00 08101/82 24:00 08/02182 04:00 08/02/82 08:00 08/02/82 12:00 08/02/82 16:00 08102182 20:00 08/02/82 24:00 08103/82 D4:00 08103182 08:00 0810318212:00 08/03182 16:00 08103/8220:00 OB/03/82 24:00 BYTE RAW DATA •••• • ••••••• 541 24 116 543 24 115 545 24 llS 541 24 111 549 24118 551 24 116 DAILY AVERAGE VALUES 553 55S 551 24 114 24 113 23 114 559 24 118 561 24 llB 563 23 111 DAILY AVERAGE VALUES 56S 561 Z3 114 23 114 569 23 114 511 23118 513 23 118 515 23 116 DAILY AVERACE VALUES 511 24 114 5" 23 112 581 23 113 583 Z3 118 585 23 119 581 23 111 DAILY AVERAGE VALUES 589 591 24 114 24 112 H3 23 113 595 Z3 119 H1 23 120 5n 23 118 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PACE 10 OS-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES =... . ..... 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.B 4.8 4.6 4.1 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.B 4.6 4.6 4 6 4.6 4.6 4.6 4.8 4.8 4.0 4.6 4.6 4.0 4.1 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9 6 9.6 9.2 9.6 9.6 9.2 9.5 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.6 9.2 9.2 9 2 9.2 9.2 9.3 9.6 9.6 9.2 9.2 9.2 9.2 9.3 STAGE FEET ••••• 1. 27 1. 21 1. 27 1. 21 1. 21 1. 21 1.21 1. 21 1. 27 1. 23 1 .21 1. 21 1.23 1. 25 1 23 1.23 1. 23 1. 23 1.23 1. 23 1. 23 1.26 1. 22 1.22 1.22 1.22 1.22 1 23 1.25 1. 25 1 .22 1.22 1.22 1.22 1. 23 DISCHC CFS • ••••• 14 14 14 14 14 14 14 14 14 13 14 14 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 12 12 12 1Z 13 TEMP DEC C • •••• 8.0 7.5 1.5 8.5 9.0 B.O 8 . 1 1.0 6.5 7.0 9.0 9.0 8.S 7,8 1.0 7 0 1.0 9.0 9. a 8.0 1 8 1.0 D.O D.5 9.0 9.5 8.5 1.8 7.0 6 0 6.5 'I.:; 10 0 9.0 8 0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 08/04182 04:00 08/04/82 08:00 08/04/82 12:00 08/04182 16:00 08/04/82 20:00 08/04/82 24:00 08/05/82 04:00 08/05/82 08:00 08/05182 12:00 01/0H82 16:00 08/05/82 20:00 08/05/82 24:00 08/06/82 04:00 08/0&182 08:00 08/06/82 12.00 08/06/82 16:00 08/06/82 20:00 08/06182 24:00 08/07182 04:00 08/07/82 08:00 08/07/82 12:00 08/07/82 16:00 08/07182 20:00 08/07/U 24:00 08/08/82 04:00 08/08182 08:00 08/08/82 12:00 08/08/82 16:00 08/08/82 20:00 08/08/82 24;00 BYTE RAW DATA .... . ..... :.. 60 1 603 60S 607 609 611 23 115 23 113 23 114 23 119 23 119 22 117 DAILY AVERACE VALUES 613 23 115 615 23 114 617 23 liS 619 23 119 621 23 119 623 23 118 DAILY AVERAGE VALUES 625 23116 627 23115 629 23 116 631 23 120 633 23 121 635 23119 DAILY AVERAGE VALUES 637 23 118 639 23 117 441 23 118 643 23118 645 22 119 647 23 117 DAILY AVERAGE VALUES 649 651 653 24 115 23 113 23 114 655 23 118 637 23 118 659 23 117 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 11 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 4.6 4.6 4.6 4.6 4.6 4.4 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.4 4.6 4.6 4.8 4.6 4.6 4.6 4.6 4.6 4.6 -54- 9.2 9.2 9.2 9.2 9.2 8.8 9. 1 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 88 9.2 9. 1 9.6 9.2 9.2 9.2 9.2 9.2 9.3 STAGE FEET ••••• 1.21 1. 21 1. ~ 1 1.21 1.21 1.18 1. 21 1. 21 1.21 1.21 1.21 1.21 1.21 1.21 1.20 1. 20 1.20 1. 20 1. 20 1.20 1.20 1.20 La 1.20 1.20 1 . 16 1.2D 1 . 19 1.23 1.19 1 . 19 1.19 1. 19 1 . 19 1. 20 DISCHG ers • ••••• 12 12 12 12 12 12 12 12 12 12 11 12 12 12 12 12 12 12 12 12 12 12 12 12 1 2 11 D 12 13 12 12 12 12 12 12 TEMP DEC C • •••• 7.5 6.S 7.0 9.5 9.5 8.5 8. 1 7.~ 7. D 7.5 9.5 9.5 9.0 8.3 B.O 7.S 1.0 10.0 10. 5 '.5 8.9 9.0 8.5 9.0 9. D 9.5 8. 5 8.9 7.5 , 5 7.0 '-0 9.0 8.S 7.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •• 8.8 ••••••• 8 08/091112 04:00 08/09/82 08:00 08/09182 12:00 08/09/82 16:00 08/09/82 20:00 08/09/82 24:00 08/10/82 04:00 011/10/82 08:00 08/10/82 12:00 08/10/82 16:00 08/10/82 20:00 08/10/82 24:00 08/11/82 04:00 08/11/82 08:00 08/11/82 12:00 08/11/82 16:00 08/11/82 20:00 08/11/8224:00 08/12182 04:00 08/12/82 08:00 08/12/82 12:00 08/12/82 16:00 08/12182 20:00 08/12/82 24:00 08/13/82 04:00 08/13/82 08:00 08/13/82 12:00 08/13/82 16:00 BYTE RAW DATA .... . .. ~ .... 661 663 66S 667 669 671 24 114 24 113 24 114 24 117 24 118 24 116 DAILY AVERAGE VALUES 673 67S 677 24 115 24 115 23 IlS 679 24 118 681 23 118 683 23116 DAILY AVERAGE VALUES 68S 24 115 687 24 IlS 689 24 I1S 691 24 117 693 24118 695 24 116 DAILY AVERAGE VALUES 697 699 701 703 705 707 24 113 24 111 24 113 24 118 24119 24118 DAILY AVERAGE VALUES 709 711 713 71S 24 117 24 116 24 116 24 119 08/13/82 20:00 717 24 121 08/13/82 24:00 719 24 120 DAILY AVERAGE VALUES FOUR VILLACES DATA FILE HUHP04.POD PAGE 12 08-AUG-83 START TIME 06/15/82 04:00 HV DEPTH INCHES ~... .88 ••• 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.6 4.8 4.6 4.6 4.7 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 -55- 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.2 9.6 9.2 9.2 9.4 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 STAGE FEET 1.22 1. 22 1. 22 1. 22 1 . 22 1.22 1. 22 1. 22 1.22 1.18 1 . 22 1 . 18 1.18 1.20 1.21 1 . 21 1.21 1 . 21 1 . 21 1 . 21 1 . 21 1.21 1. 21 1 . 21 1 . 21 1 . 21 . 21 1 . 21 1.20 1.20 1.20 1.20 1. 20 1. 20 1.20 DISCHG CFS 13 13 13 13 13 13 13 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 TEMP DEC C 7.0 6.S 7.0 8.S 9.0 8.0 7. 7 7.S 7 . ~ 7 . ~ 9 . 0 9.0 B.O 8.1 7 . :; 7.5 7.~ 8.5 9.0 8.0 8. 0 6.5 3.5 6.5 9.0 9.S LO 7.7 B.~ 8.0 8.0 9.5 10.S 10.0 9 . 1 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 08/14/82 04:00 08/14/82 08:00 08/14/82 12:00 08/14/8216:00 08114182 20:00 08114/82 24:00 08/1~/82 04:00 08/15/82 08:00 0811S182 12:00 08/1~182 16:00 08/15/82 20:00 08/15/82 24:00 08116182 04.00 08/16/82 08:00 08/16/82 12:00 08/16/82 16:00 08/16/82 20:00 08/16/82 24:00 08111182 04:00 08/11/8208:00 08/11182 12:00 08/11182 16:00 08/11182 20:00 08111/82 24:00 08118/82 04:00 08/18/82 08:00 08/18/82 1.2:00 BYTE RAW DATA • ••••••••••• 121 123 125 121 129 24 11' 24 111 24 118 24 119 24 118 131 24 111 DAILY AVERAGE VALUES 133 25 115 135 2S 11S 131 24 115 139 24 111 141 23 111 143 24 115 DAILY AVERAGE VALUES 145 25 114 141 25 114 149 25 115 151 23111 133 23 118 1~5 23 116 DAILY AVERAGE VALUES 151 23 116 1:19 24 115 161 13 115 163 23 111 16~ 23 118 161 23116 DAILY AVERAGE VALUES 76' 111 113 2t 115 25 114 24 1 t 4 08/18/82 16:00 115 23 111 08/18/82 20:00 111 23 11' 08/18/82 24:00 '" 23 111 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 13 08-AUC-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 4.8 4.8 4.8 4.8 4.8 4.8 4.8 5.0 5.0 4.8 4.8 4.6 4.8 4.8 5.0 5.0 5.0 4.6 4.6 4.6 4.8 4.6 4.8 4.6 4.6 4.6 4.6 4.6 4.8 5.0 4.8 4.6 4.6 4.6 4.1 -56- '.6 '.6 9.6 '.6 '.6 '.6 '.6 10.0 10.0 '.6 '.6 '.2 '.6 '.1 10.0 10.0 10.0 '.2 9.2 '.2 9.6 '.2 '.6 '.2 '.2 '.2 '.2 '.3 '.6 10 . 0 '.6 '.2 '.2 '.2 '.S STAGE FEET ••••• 1. 20 1. 20 1. 20 1. 20 1.20 1 .20 1. 20 1. 22 1. 22 1.19 1.19 1.16 1.19 1. 20 1 .22 122 1.Z2 1.15 1 . 1 :l 1.15 1.19 1 . 15 1.18 1 . 15 1. 15 1.15 1 . 15 1 . 15 1. 18 1. 21 1 . 18 1 . 14 1. 14 1. 14 1.16 DIBCHG CFS .a •••• 12 12 12 12 12 12 12 13 13 12 12 11 12 12 13 U 13 11 11 11 12 11 12 11 11 11 11 11 11 12 11 11 11 11 11 TEMP DEC C , . :; 8.S '.0 '.S 9.0 8.5 9.0 1.:i 1.S 1.5 &.5 8.5 1.S 1.8 1.0 1.0 1. S 8.5 LO 8.0 1.& 8.0 1.S 1.S 8.S , . Ii 8.0 8.1 1.5 1.0 1.0 8.5 9.S 8 :; 8.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 08119/82 04:00 08/19/82 01:00 08119/12 12:00 08119/82 16:00 01/19/82 20:00 01/19/81 24:00 OI/ZO/82 04:00 OI/ZO/IZ OB:OO 01/20/82 12:00 08/20/82 16:00 OB/20/82 20:00 OB/20/82 24:00 08/21182 04:00 OB/21/82 08:00 08/21/82 12:00 OB/21/82 16:00 08121/82 ZO:OO OB/21/1Z 24:00 01/22/82 04:00 OB/22/82 08:00 08/22/82 12:00 08/22112 16:00 08/22/82 20:00 OB/22/82 24'00 01113182 04:00 OB/23/82 08:00 08/23182 12:00 OB/23/B2 16:00 08/23/82 20:00 08/23/1224:00 BYTE RAW DATA •••• • ••••••• 781 24 116 783 14 114 785 23 114 711 23 119 789 23 119 191 24111 DAILY AVERAGE VALUES 793 2S 117 795 25 116 797 24 116 799 24 119 BOI 24 120 B03 24 118 DAILY AVERAGE VALUES IDS 24 lIS 807 24 114 B09 24 115 Bl1 24 117 813 24 111 B15 24 117 DAILY AVERAGE VALUES 817 119 BU 823 825 8%7 24 116 25 116 Z6 117 26 120 2S 121 25 11 9 DAILY AVERAGE VALUES 8Z9 131 B33 83$ 837 IS? UI18 25 111 n 117 25 118 2S 11' 24 118 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUM'04.POD PAGE 14 OI-AUC-83 START TIME 06/1~/IZ 04:00 MV DEPTH INCHES :.... . ..... 4.8 4.8 4.6 4.6 4.6 4.B 4.7 5.0 S.O 4.8 4.8 4.B 4.8 4.9 4.8 4.8 4.8 4.8 4.8 4.B 4.8 4.8 5.0 5.2 5.2 5.0 5.0 5.0 3.0 5.0 5.0 5.0 5.0 4.B 5.0 -57- 9.6 9.6 9.2 9.2 9.2 9.6 9.4 10.0 10.0 9.6 9.6 9.6 9.6 9.1 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 10.0 10.4 10.4 10.0 10.0 10. 1 10.0 10.0 10.0 10 0 10.0 9.6 9.9 STAGE FEET ••••• 1. 17 1. 17 1.14 1. 14 1. 14 1. 17 1. 15 1. 20 1. 20 1. 17 1. 17 1. 17 1 . 17 1.18 1. 16 1.16 1.16 1.16 116 1.16 116 1.16 1.19 1.22 1. 22 1. 19 1.19 1.19 1. J B 1.18 1.18 LIB 1.18 1 . 15 1.18 DISCHC ers •••••• 11 11 11 11 11 11 11 12 12 11 11 11 11 11 11 11 11 11 11 11 11 11 12 13 13 12 12 12 U 12 12 12 12 11 12 TEMP DEG C ..-:- 8.0 7.0 7.0 9.5 9.5 9.0 8.3 B.3 1.0 1.0 , :; 10.v 9.0 8.B 7. S 7.0 7.5 8.S 9.0 8.3 8.0 1.0 8.0 1.5 10.0 10 . :; 9. S 9 1 , .0 I.S 1.5 9.0 ,.S 9.0 I. , lPl HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME ••••••••••••• 08/24/82 04:00 08/24/82 08:00 08/24/82 12:00 08/24/82 16:00 01/24/82 20:00 BYTE RAW DATA •••• •••••••• 841 843 845 847 849 24 117 24 116 24 117 25 118 25 118 08/24/82 24:00 851 25 116 08/25/82 04:00 08/25/SZ 08:00 08/25/82 12:00 08/25/SZ 16:00 08/25182 20:00 08/25/SZ 24:00 08/26182 04:00 08/26/82 08:00 08/26/82 12:00 08/26182 16:00 08/26/82 20:00 08/26182 24:00 08127/82 04:00 08/27/SZ 08:00 08/27182 12:00 08/27/82 16:00 08/27182 20:00 08/27182 24:00 08128/82 04:00 08/28/82 08:00 08/28/82 12:00 08/28/82 16:00 08/28182 20:00 08/28/82 24:00 DAILY AVERAGE VALUES 853 855 857 859 861 863 25116 25 116 25 116 25 117 25 117 25 116 DAILY AVERAGE VALUES 865 25 115 867 25 115 869 25 liS 871 25118 873 24 118 875 24116 DAILY AVERAGE VALUES 877 24 114 879 24 113 881 24 114 883 24 115 885 24 116 887 24 116 DAILY AVERAGE VALUES 889 2S 116 8'11 24 116 893 24 116 8'15 24 118 897 24 118 899 25 117 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 15 08-AUG-8! START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 4.8 4.8 4.8 5.0 5.0 5.0 4.9 5.0 5.0 5.0 S.O :i.0 5.0 ~.O 5.0 5.0 5.0 S.O 4.8 4.8 4.9 4.8 4.8 4.8 4.8 4.8 4.8 4.8 5.0 4.8 4.8 4.8 4. B 5.0 4.9 -58- '.6 '.6 9.6 10.0 10.0 10.0 9.8 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 9.6 '.6 9.9 9 6 9.6 9.6 9.6 '.6 9.6 '.6 10.0 9.6 9.6 9.6 9.6 10.0 9.7 STAGE FEET ••••• 1 . 15 1. 15 1 . 15 1.18 1.18 1.18 1.16 1. 17 1. 17 1. 17 1. 17 1 . 17 1. 17 1. 17 1 . 17 1 . 17 1.17 1. 17 1. 14 1 14 1.16 1.13 1.13 1 . 13 1. 13 1. 13 1.13 1.13 1.16 1.13 1 . 13 1.13 1. 13 1.16 1. 14 DISCHG crs s ••••• 11 11 11 12 12 12 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 10 10 10 10 10 10 10 11 10 10 10 10 11 11 TEMP DEC C • •••• 8.5 8.0 8.5 '.0 '.0 8.0 1.5 8 0 8.0 8.0 8.5 8.5 1.0 8.2 7 5 7.S 7. 5 '.0 9.0 8.1i 8. 1 7 Ii 6.5 7.0 7. 5 8.0 1.0 7.3 8.0 8.0 8.0 '.0 9.0 8 5 8. 4 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME 08/29182 04:00 08/29182 08:00 08/29182 12:00 08/29/82 16:00 08/29/82 20:00 08/29/82 24:00 08/30/82 04:00 08/30/82 08:00 08/30/82 12:00 08/30/82 16:00 08/30/82 20:00 08/30/12 24:00 08/31/82 04:00 08/31/82 08:00 08/31/82 12:00 08/31/82 16:00 08/31/82 20:00 BYTE RAW DATA 901 26 118 903 25 117 905 25118 907 25 118 909 25 118 911 25 117 DAILY AVERAGE VALUES 913 915 917 919 921 923 25 117 25 116 27 116 27 118 26118 26 117 DAILY AVERAGE VALUES 925 927 929 931 933 28 116 27 115 26 116 26 117 25 118 08/31/82 24:00 935 25 117 09101182 04:00 09101/8208:00 09101/82 12:00 09101/82 16:00 09101/8220:00 09101/8224:00 09102/82 04:00 09102/82 08:00 09102/82 12:00 09102/82 16:00 09102/82 20:00 09102/82 24:00 DAILY AVERAGE VALUES 937 939 941 943 25 116 25 116 25 116 25 118 945 25 118 947 25 116 DAILY AVERAGE VALUES 949 24 lIS 951 25 113 953 24113 955 24 115 957 24116 959 24 115 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PACE 16 08-AUC-83 START TIME 06/1~/82 04:00 MV 5.2 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.4 5.4 5.2 5.2 5.2 5.6 5.4 5.2 5.2 5.0 :i.0 5.2 5.0 5.0 :i.0 5.0 5.0 5.0 S.O 4.8 5.0 4.8 4.8 4.8 4.8 4.8 -59- DEPTH INCHES 10. 4 10.0 10.0 10.0 10. 0 10. 0 10 . 1 10.0 10. 0 10.8 10. 8 10.4 10.4 10. 4 11 . 2 10.8 10.4 10.4 10. 0 10.0 10. 5 10.0 10. 0 10 . 0 10. 0 10.0 10. 0 10.0 9.6 10.0 9.6 9.6 9.6 9.6 9.7 STAGE DISCHC FEET eFS 1. 19 1 . 15 1 . 15 1 . 1:) 1 . 15 1 . 15 1 . 16 1 . 1 :i 1 . 15 1.22 1.22 1.18 1 . 1 8 1.18 1.24 1 . 21 1.18 1.18 1 . 14 1 . 14 1. 18 1 . 14 1. 14 1 . 14 1 . 14 1 . 14 1 . 14 1 . 14 1 . 10 1 . 13 1. 10 1 . 10 1 . 10 1 . 10 1. 11 1 i. 11 1 1 11 11 11 1 1 11 1 1 12 12 12 12 12 13 12 12 1 2 11 11 12 7.6 7.6 7.6 7. 6 7.6 7.6 7.6 6.9 7.5 6.9 6.9 6.9 6. 9 7.0 TEMP DEC C 9.0 8.S 9. 0 9.0 9. 0 8.5 8.8 8.5 8. 0 8.0 9.0 9.0 8. 5 8.5 8 0 7.5 8.0 8.:i 9. 0 8.5 8.3 8.0 8.0 8.0 9. 0 9. 0 8.0 8.3 7.5 6.5 6.5 7.5 8.0 7.5 7.3 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME = •••••••••••• 09103/82 04:00 09103/82 08:00 09103/82 12:00 09/03/82 16:00 09103/82 20:00 09103/82 24:00 09/04182 04:00 09/04/82 08:00 09/04/82 12:00 09/04/82 16:00 119/04/82 20:00 09/04/82 24:00 09/05182 04:00 09105182 08:00 09/05/12 12:00 09/U/82 16:00 09/05182 20:00 09/05/82 24:00 69/06182 04:00 09/06182 08:00 09/06182 12:00 09/06182 16:00 09/06182 20:00 09/06/82 24:00 09/07/82 04:00 09/07/82 08:00 09/07/82 12:00 09/07/82 16:00 09/07182 20:00 09/07/82 24:00 BYTE RAW DATA •••• • ••••••• 961 24 114 963 24 113 965 24 114 967 24 115 969 24 116 971 Z4 114 DAILY AVERAGE VALUES 973 24112 975 24 111 977 24111 979 24 114 981 24 115 983 24 115 DAILY AVERAGE VALUES 985 987 27 114 U 114 989 32 114 991 32115 993 31 115 995 29 115 DAILY AVERAGE VALUES 997 999 1001 1003 100S 1007 28 114 28 113 Z8 114 28 115 28 liS 28 114 DAILY AVERAGE VALUES 1009 1011 28 113 28 113 1013 30 113 1015 29 116 1017 28 116 1019 28 116 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 17 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES =... . .... = 4.8 4.8 4.8 4.8 4.8 4.& 4.8 4.8 4.8 4.8 4.8 4.& 4.8 4.' 5.4 6.4 6.4 6.4 6.2 5.& 6.1 a.6 S.6 S.6 5.6 5.6 5.6 5.6 !L 6 5.6 6.0 5.8 S.6 5.6 5.7 -60- 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 10.8 12.8 12.8 12.8 12.4 11 . 6 12. 2 11. 2 11 . 2 11. 2 11. 2 11 . 2 J 1. 2 11 .2 11.2 11 . 2 12.0 11 . 6 11 . 2 11 .2 11 .4 STAGE FEET • •••• 1. 10 1. 10 1. 10 1.10 1. 10 1. 10 1. 10 1. 09 1. 09 1. 09 1. 09 1. 09 1. 09 1. 09 0.90 1. 07 1.07 1. 07 1. 03 0.9? 1.02 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 1.00 0.97 0.93 0.93 0.95 DISCHG CFS •••••• 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.7 6.7 6.7 6.7 6.7 6.7 6.7 3.6 6.2 6.2 6.2 :>.6 4.5 5.4 4.1 4.1 4 1 4. 1 4. 1 4. 1 4. 1 4. 1 4. 1 5. 1 4.5 4. 1 4.1 4.3 TEMP DEG C • •••• 7.0 6.5 7.0 7.5 8.0 Lei 7.2 6.0 5.S 5.5 7 0 7.5 7.5 6.5 7.0 7.0 '7.0 7.5 7. S '7 5 7.3 7.0 6.S 7.0 7.5 7.5 7.0 7 6 S 6.5 6.5 8.0 8.0 8.0 7.3 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 09/08112 04:00 09/08112 08:00 09101182 12:00 09/01182 16:00 09108112 20:00 09/08/82 24:00 09/09/82 04:00 09/09/82 08:00 09/09/82 12:00 09/09/82 16:00 09/09/82 20:00 09/09/82 24:00 09/10/82 04:00 09110182 08:00 09/10/8212:00 09/10/82 16:00 09/10/82 20:00 09/10/82 24:00 09/11/82 04:00 09/11/82 08:00 09/11/82 12:00 09/11/82 16:00 09/11/82 20:00 09/11/8224:00 09/12/82 04:00 09/12182 08:00 09/12/82 12:00 BYTE RAW DATA •••• •••••••• 1021 1023 102$ 27 115 27 114 27 114 1027 27 116 1029 27 117 1031 27 116 DAILY AVERAGE VALUES 1033 1035 1037 1039 1041 27 115 26 114 28 114 30 115 30 116 1043 30 115 DAILY AVERAGE VALUES 1045 1047 30 115 30 115 1049 30 115 1051 30 117 1053 30 117 lOSS 29 114 DAILY AVERAGE VALUES 1057 1039 29 112 29 111 1061 29 111 1063 29 114 1065 29 114 1067 29 113 DAILY AVERAGE VALUES 1069 1071 1073 29112 29 111 29 112 09/12/82 16:00 107~ 31 114 09112/8220:00 1077 31 117 09/12/82 24:00 1079 33 117 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 18 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.6 6.0 6.0 6.0 5.7 6.0 6.0 6.0 6.0 6.0 5.8 6.0 5.8 5.8 5.8 5.8 5.8 5.8 S.8 5.8 S.8 5.8 6.2 6.2 6.6 6. 1 -61- 10. 8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10. 4 11 .2 12.0 12.0 12. 0 11 .4 12.0 12.0 12. 0 12.0 12.0 11 .6 11 . 9 11 .6 11. 6 11 . 6 11 . 6 11 . 6 11. 6 11 . 6 11. 6 11 . 6 11 . 6 12.4 12.4 13.2 12 . 1 STAGE FEET • •••• 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.87 0.93 1. 00 1 .00 1.00 0.9$ 1.00 1.00 1.00 1.00 1.00 0.97 0.99 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 1.03 1 . 03 1.10 1. 01 DISCHG CFS •••••• 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.2 4.1 5. 1 5.1 :I. 1 4.4 :I. 1 5 . 1 5 . 1 5.1 :I. 1 4.5 5.0 4.5 4.:5 4.5 4.5 4.5 4.5 4.5 4.S 4.5 4.5 5.6 5.6 6.9 5.3 TEMP DEG C = •••• 7.S 7.0 7.0 8.0 8. :5 8.0 7.7 7.5 7.0 7.0 7.5 8.0 7.5 7.4 7. 5 7.5 7. 5 8.5 8.5 7.0 7.8 6.0 5.5 5.5 7.0 7.0 6.5 6.3 6.0 :i. 5 6.0 7.0 8. 5 8.5 6.9 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE •••••••• ••••• 09113/82 04:00 09/13/82 08:00 09113/82 12:00 09/13/U 16:00 09113182 20;00 09113/82 24:00 09114/82 04:00 09114182 08:00 09114/82 12:00 09114/82 16:00 09/14/82 20:00 09114/82 24:00 0911:1/82 04:00 09115/82 08:00 09/15/82 12:00 09/15/82 16:00 09/15/82 20:00 09115182 24:00 09116182 04:00 09/16/82 08:00 09116/82 12:00 09116/82 16:00 09116/82 20:00 09116/82 24:00 09117/82 04:00 09117/82 08:00 09117/82 12:00 09117/82 16:00 09111182 20 00 09111182 24:00 BYTE RAW DATA •••• •••••••• 1081 1083 1085 32 117 32 116 31 116 1087 31 117 1089 31 111 1091 31 116 DAILY AVERAGE VALUES 1093 31 115 1095 31 114 1091 33 114 1099 34 116 1101 35 118 1103 36 118 DAILY AVERAGE VALUES 110S 38 119 1107 38110 1109 41 119 1111 41 120 1113 40 119 Ilt5 39 116 DAILY AVERAGE VALUES 1117 1119 11 %1 1123 1125 1121 39 114 39 113 39 114 39 115 39 116 39 116 DAILY AVERAGE VALUES 1129 11 31 1133 1135 1137 39 115 40 115 41 116 42 117 42 117 1139 48 116 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUftP04.POD PAGE 19 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 6.4 6.4 6.2 6.2 6.2 6.2 6.3 6.2 6.2 6.6 6.8 7.0 7.2 6.1 1.' 1.6 8.2 8.2 8.0 7.8 1.9 7.8· 7.8 1.8 7.8 7.8 7.8 7.8 1.8 8.0 8.2 8.4 8.4 9.6 1.4 -h?- 12.8 12.8 12.4 12.4 12.4 12.4 12.5 12.4 12.4 13.2 13.6 14.0 14.4 13.3 15.2 15.2 16.4 16.4 16.0 15.6 15.8 15 . 6 15.6 15.6 15.6 15.6 is 6 15.6 1:1 . , 16.0 16.4 16.8 16.8 19.2 16 .• STAGE FEET ••••• 1. 01 1. 07 1. 03 1. 03 1. 03 1.03 1. 04 1. 03 1. 03 1. 10 1. 13 1. 17 1. 20 1. 11 1. 27 1. 27 1. 37 1. 37 1.33 1 30 1.32 1 30 1. 30 1. 30 1.30 1 30 1 30 1 .30 1.30 1. 33 1. 37 1 .40 1.40 1. 60 1.40 OISCHG CFS •••••• 6.2 6.2 S.6 5.6 5.6 5.6 5 8 5.6 $.6 6.9 7.S 8.3 9. 1 7.2 11 11 14 14 13 12 12 11 12 12 12 12 12 12 12 13 14 t :I 15 23 t :i TEMP DEG C ••••• 8.~ 8.0 8.0 8.5 1.5 B.O 8. :; 7.S 7.0 1.0 1.0 9.0 9.0 7.9 9.5 10.0 9.S 10.0 9.~ 8.0 9.4 7.0 6.5 1.0 7.S 8.0 8.0 7.3 1.S 7.S 8 0 8.5 8.5 8.0 8.0 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 09/U/82 04:00 09/18/82 08:00 09/18/82 12:00 09/18/82 16:00 09/18/82 20:00 09118/82 24:00 09119/82 04:00 09/19/82 08:00 09/19/82 12:00 Ot/lt/B2 16:00 09/19182 20:00 09/19/B224:00 09/20/82 04:00 09l20/B2 08:00 09/20/82 12:00 091%0/82 16:00 09/20/82 20:00 09120/8224:00 09l21/B204:00 09121/82 08:00 09121/82 12:00 09121/8216:00 09121/82 20:00 09/21/82 24:00 09/22/82 04:00 09122/82 08:00 09/22/82 12:00 09122/82 16:00 09122/82 20:00 09122/8224:00 BYTE RAY DATA •••• • ••••••• 1141 48 115 1143 46 115 1145 46 IlS 1147 45 117 1l4t 45 116 1151 45 114 DAILY AVERAGE VALUES 1153 1155 1157 1159 45 114 45 113 45 114 45 11 S 1161 46 115 1163 46 114 DAILY AVERAGE VALUES 116 5 1167 1169 1171 1173 1175 46 113 46 113 46 114 46116 47 117 48 117 DAILY AVERAGE VALUES 1177 1179 1181 1183 1185 1187 47 115 47 113 46 113 47 115 46 114 47 113 DAILY AVERAGE VALUES 1189 47 111 1191 47 lOt 1193 46 109 1195 46 112 1197 46 112 11tt 46 110 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 20 08-AUG-S3 START TIME 06/1~/82 04:00 MV DEPTH INCHES •••• • ••••• 9.6 9.2 9.2 9.0 9.0 9.0 9.2 9.0 9.0 9.0 9.0 9.2 9.2 9. 1 9.2 9.2 9.2 9.2 9.4 9.6 9.3 9.4 9.4 9.2 9.4 9.2 9.4 9.3 9.4 9.4 9.2 9.2 9.2 9.2 9.3 -63- 19.2 18.4 18.4 18.0 18.0 18.0 l8.3 18.0 18.0 18.0 18.0 18.4 18.4 18 . 1 18.4 18.4 18.4 18.4 18.8 19.2 18.6 18.8 18.8 18.4 18.8 18.4 18.8 18.7 18.8 18.8 18. 4 18.4 18 . 4 18.4 18.5 STAGE FEET • -= •• 1.58 1.51 1. 51 1.48 1.48 1.48 1.51 1.46 1.46 1.46 1.46 1.4t 1 .49 1 . 47 1 . 47 1.47 1.47 1.47 1 . 51 1 .54 1.4t 1.4t 1.4t 1.45 1. 49 1. 45 1. 49 i .48 1.47 1.47 1.43 1.43 1.43 1 . 43 1.44 DISCHC CFS •••••• 22 19 19 18 18 18 19 17 17 17 17 18 1 8 17 17 1 7 17 17 19 20 18 18 18 17 18 17 18 18 17 17 16 16 16 16 16 TEMP DEC C • •••• 7.5 7.S 7. 5 8.5 8.0 7.0 7. ? 7.0 6.S 7 Ii 7.5 7.:' 7.0 7 . 1 , " " • ,J 6.5 7.0 8.0 8.5 8.5 7.5 7 5 6.5 6.5 7.5 7.0 LS 6.9 s. S 4.5 4.S Lli LO 5.0 5.3 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME =:1:1 •••••••••• 09/13/82 04:00 09/23/82 08;00 09/23/82 12;00 09/23/82 16;00 09/23/82 20:00 09/23/82 24;00 09/24182 04;00 09/24/82 08:00 09/24/82 12:00 09/24182 16:00 09/24/82 20;00 09/24/82 24:00 09/2318204;00 09/25/82 08:00 09/25/82 12;00 09/25/82 16:00 09/2:5/82 20:00 09/25/8224;00 09/26/8204:00 09/26/82 08:00 09/26182 12:00 09/26/82 16:00 09/26/82 20:00 09/26182 24;00 09/27/82 04:00 09/27/82 08:00 09/27/82 12:00 BYTE RAW DATA •••• •••••••• 1201 1203 1205 1207 1209 46 109 46 110 46 110 46 112 46 112 1211 46 110 DAILY AVERAGE VALUES 1213 45 110 1215 45 110 1217 45 112 1219 4S 113 1221 45 114 1223 45 114 DAILY AVERAGE VALUES 1225 4:5 113 1227 45 113 1229 45 113 1231 46 114 1233 46 114 1235 46 113 DAILY AVERAGE VALUES 1237 41 113 1239 47 112 1241 47 112 1243 46 113 1245 46 113 1247 46 111 DAILY AVERAGE VALUES 12 4 9 1251 1253 46 110 46 109 45 109 09/27/82 16;00 1255 45 111 09/27/82 20:00 1257 4S 112 09/27/82 24:00 1259 45 111 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 21 08-AUG-83 START TIME 06/15/82 04;00 MV DEPTH INCHES •••• • ••••• 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 11.0 9.0 9.2 9.2 9.2 9. 1 11.4 9.4 11.4 9.2 11.2 9.2 9.3 9.2 9.2 9.0 9.0 9.0 9.0 9. 1 -64- 18.4 18.4 18.4 18.4 18. 4 18. 4 18.4 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.4 18.4 18.4 18. 2 18.8 18.8 18.8 18.4 18.4 18.4 18.6 18 .. 4 18.4 18.0 18.0 18.0 18.0 18.1 STAGE DISCHG FEET CFS 1.41 1.41 1. 41 1. 41 1.41 1.41 1.41 1.36 1.36 1.36 1.36 1. 36 1. 36 1.36 1. 34 1.34 1.34 1.37 1.37 1.37 1,36 1.39 1.39 1. 39 1.35 1.35 1. 35 1.37 1. 33 1.33 1.30 1.30 1. 30 1.30 1 . 31 •••••• 15 15 IS 15 IS 15 1 :5 13 13 13 13 13 13 13 13 13 13 14 14 14 13 14 14 14 13 1 3 13 14 13 13 12 12 12 12 12 T£MP DEG C s •••• 4. :i S.O 5.0 6.0 6.0 5.0 5.3 !j.0 S,O 6 0 6.5 1.0 1.0 6.1 6.5 6.S 1.0 1.0 6.5 6.7 6.5 6.0 6.0 6.5 6 :.; 5.S 6.2 :;D 4.5 4.5 !j.S 6.0 S.5 S.2 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME z •••••••••••• 09128/82 04:00 09lU1I2 08:00 09lU/82 12:00 G9/U/82 16:00 09/28/82 20:00 09/U/82 24:00 09129/82 04:00 09/H/82 08:00 09/H/82 12:00 09/HII2 16:00 09/19/82 20:00 09/H/82 24:00 09/30/82 04:00 09/30/82 08:00 09/30/82 12:00 09/30/U 16:00 09/30/82 20:00 09/30182 24:00 10/01182 04:00 10/01/82 08:00 10/01/82 12:00 10/01/82 16:00 10/01/82 20:00 10/01/82 24:00 10/02/82 04:00 10/02/n 08:00 10/02/82 12:00 10/02/U 16:00 10/02182 20:00 10/02/82 24:00 BYTE RAW DATA •••• •••••••• 1261 47 til 1263 48 112 IUS 49 113 1261 49 11S 1269 48 114 1211 41 113 DAILY AVERAGE VALUES 1273 121:5 12 71 1279 lUI 1283 47 112 U 111 46 112 U 114 46 114 46 111 DAILY AVERAGE VALUES IUS 1287 1289 12 91 1293 IH5 40 110 40 109 40 110 46 113 46112 46 111 DAILY AVERAGE VALUES 1297 1299 46 111 46 110 1301 45 110 1303 n 112 1305 45 112 1307 4S 110 DAILY AVERAGE VALUES 1309 1311 1313 46 110 46 110 46 111 1315 46 112 1317 40 112 1319 46 110 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE U 08-AUG-83 START TIME 06/1~/82 04:00 DEPTH STAGE MV INCHES FEET •••• • ••••• ••••• 9.4 9.6 9.8 9.8 9.6 9.4 9.6 9.4 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.1 9.2 9.2 9.0 9.0 9.0 9.0 9. 1 9.2 9.2 9.2 9.2 9.2 9.2 9.2 -F,c,- 18.8 19.2 19. , 19.6 19.2 18.8 19.2 18.8 18.4 18.4 18.4 18.4 18.4 18.5 18.4 18.4 18. 4 18.4 18.4 18.4 18.4 18.4 18.4 18.0 18.0 18.0 18.0 18.1 18.4 18.4 18.4 18.4 18.4 18.4 18.4 1.35 1.38 1 . 41 1.41 1. 38 I. as 1.38 1.33 1.H 1.29 1.29 1.29 1.29 1. 30 121 1.27 1. 21 1.21 1.27 1.27 1. 21 1. 2~ 1. 2 S 1.22 1.22 1.22 1.22 1.23 1. 23 1.23 1.23 1.23 1.23 1.23 1.23 DlleHG CFS • ••••• 13 14 15 15 14 13 14 12 11 11 11 11 11 12 11 11 11 11 11 11 11 10 10 9.5 9.5 9.5 9.5 9.8 9 9 9.9 9.9 9 9 9.9 9.9 9.9 TEME' DEG C s.s 6 0 6.5 7. S 1.0 6.S 6.0 l.5 6.0 1.0 1.0 5.5 6.2 5.0 4.5 5.0 6.5 6.0 5.5 5.4 5.5 5 . 0 :.i.0 6.0 6.0 5.0 5.4 S. 0 ~.O 5.5 6 0 6.0 5.0 5 .• APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUKPY CREEK NEAR LARSEN BAY DATE TIKE s •••••••••••• 10103/82 04:00 10/03/82 08:00 10/03/82 12:00 10/03/82 16:00 10/03/82 20;00 10/03/82 24:00 10/04/82 04:00 10/04/82 08:00 10/04/82 12:00 10/04/82 16:00 10/04/82 20;00 10/04/82 24:00 10/05/82 04:00 10/0:1182 08:00 10/05/82 12:00 10/115/82 16:00 10/05/82 20:00 10/0S/82 24:00 10/06/82 04:00 10/06182 08:00 10/06182 12:00 10/06182 16:00 10/06/82 20:00 10/06182 24;00 10/07/82 04:00 10/07182 08;00 10/07/82 12:00 10/07/82 16:00 10/01182 %0:00 10/07182 24;00 BYTE RAW DATA •••• •••••••• 1321 1323 1325 1321 1329 1331 46 110 46 109 47 109 47 110 46 109 46 107 DAILY AVERAGE VALUES 1333 1335 1331 1339 1341 46 106 47 105 47 105 48 108 48 109 1343 48 loa DAILY AVERAGE VALUES 1345 1341 48 lOa 4a 107 1349 4a 106 1351 4a 101 1353 48 107 1355 48 105 DAILY AVERAGE VALUES 13S1 48 104 1339 47 103 1361 47 103 1363 48 105 1365 48 105 1367 48 104 DAILY AVERAGE VALUES 1369 4a 101 1371 47 102 1373 48 103 1375 49 105 1311 49 105 1319 49 lOS DAILY AVERAGE VALUES FOUR VI LUGES DATA FILE HUKP04.POD PAGE 13 08-AUG-83 START TIKE 06/15/82 04:00 KV DEPTH INCHES •••• • ••••• 9.2 9.2 9.4 9.4 9.2 9.2 9.3 9.2 9.4 9.4 9.6 9.6 9.6 9.S 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.4 9.4 9.6 9.6 9.6 9.5 9.6 9.4 9.6 9.8 9.a 9.a 9.1 -f..f..- 18.4 18.4 18.8 18. a 18.4 18.4 18.5 18.4 18.8 18.8 19.2 19.2 19.2 18.9 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 18.8 18.8 19.2 19.2 19.2 19.1 19. 2 18 a 19.2 19. {, 19.6 19.6 19.3 STAGE FEET • •••• 1 . 21 1.21 1. 25 1.25 1.21 1.21 1.22 1.19 1 .23 1.13 1. 26 1.26 1.26 1.24 1.24 1. 24 1.24 1.24 1.24 1. 24 1.24 1.22 1.19 1 . 19 1.22 1.22 1.22 121 1.20 1. 17 1. 20 1.23 1. 23 1.23 1.21 DISCHG CFS •••••• 9.4 9.4 1 D 10 9.4 9.4 9.7 8.9 9.7 9.7 11 11 11 10 10 10 10 10 10 10 10 9.5 a.7 8.7 '.5 9.5 9.5 9.2 9. 1 8.3 9. 1 9.9 , .9 9,9 9.4 TEKP DEG C • •••• LO 4.5 4 . S 5.0 4.5 3.:1 4.5 3.0 2..5 2.5 4.0 4.5 4.0 3.4 4.0 3,5 3. 0 3.:' 3. :; 2 :; 3.3 2.0 1.5 1.~ LS 2.5 2 .• 2 0 1 . 0 1.0 1.5 2.5 2.5 2.5 1.8 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••••• ••••• 10/08/82 04:00 10/08/82 08:00 10/08/82 12:00 10/08/82 16:00 10/08/82 20:00 10/08/82 24:00 10/09182 04:00 10/09182 08:00 10/09182 12:00 10/09182 16:00 10/09182 20:00 10/09182 24:00 10/10/82 04:00 10110182 08:00 10/10/8212:00 10/10/8216:00 10/10/82 20:00 10/10182 24:00 10/11182 04:00 10111/82 08:00 10/11/8212:00 10/11/82 16;00 10/11182 20:00 10/11182 24:00 10/11/82 04:00 10/12/SZ 08:00 10/lZ/82 12:00 10/12/82 16:00 10/12/82 20:00 10/12/82 24:00 BYTE RAW DATA •••• •••••••• 1381 49 105 1383 49 104 1385 49 104 1387 49 105 1389 48 105 1391 48 103 DAILY AVERAGE VALUES 1393 1395 1397 47 102 48 102 48 103 1399 48 105 1401 48 105 1403 48 103 DAILY AVERAGE VALUES 1405 48 103 1407 47 102 1409 46 102 1411 47 103 1413 46 103 1415 47 102 DAILY AVERAGE VALUES 1417 46 103 1419 47 104 1421 48 105 1423 48 106 1425 48 107 1427 49 107 DAILY AVERAGE VALUES 1429 1431 1433 ~2 107 52 101 51 107 1435 51 107 1437 50 100 1439 50 104 DAILY AVERAGE VALUES FOUR VILLACES DATA FILE HUMP04.POD PACE 24 DB-AUC-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 9.8 9.8 9.8 9.8 9.6 9.6 9.7 9.4 9.6 9.6 9.6 9 6 9.6 9.6 9.6 9,4 9.2 9 4 9.2 ',4 9,4 9,2 , 4 9.6 9.6 '.6 9.8 9.5 10.4 10,4 10.2 10.2 10.0 10.0 10.2 19.6 19.6 19.6 19.6 19.2 19.2 19 5 18.8 19.2 19.2 19. 2 19.2 19.2 19.1 19.2 18,8 18,4 18.8 18.4 18.8 18.7 18,4 18.8 19.2 19,2 19.2 19.6 19.1 20 8 20.8 20.4 20.4 20.0 20.0 20.4 STACE FEET ••••• 1.21 1.21 1. 21 1.21 1.18 1.18 1. 20 1. 13 1.16 1.16 1.16 1.16 1.16 1 . 1:; 1. 14 1.11 1. 07 1. 11 1. 07 1.11 1. 10 1. 05 1. 09 1.12 1.12 1.12 1. 15 1. 11 1.23 1.23 1. 20 1. 20 1. 17 1.17 1. 20 DISCHC cn 9.4 9.4 9.4 9.4 8.6 8.6 9. 1 7.4 B . 1 8.1 8 . 1 B . 1 B. 1 8.0 7.7 7.0 6.3 7.0 6.3 7.0 6.9 6.0 6.6 7.3 7.3 7.3 8.0 7. 1 '.? 9.9 , 1 9 . 1 B.3 8.3 9, 1 TEMP DEC C 8 •••• 2.5 2,0 2.0 2,5 2.5 1.:) Z,2 1 0 1 . a 1 . :) 2.5 2,5 1 . 5 1.7 1.5 1. Ii 1.0 1.5 1 5 1.0 1.3 1.5 2.0 2.5 3. I) 3.5 3.5 2,7 3.S 3.S 3.5 3 S 3.0 2.0 3., APA HYDRO-ELECTRIC FEASIBILITY STUDY ; FOUR VILLAGES PREPARED BY DRYDEN & LARUE DATA FILE HUMP04.POD PAGE 25 OS-AUG-83 HUMPY CREEK NEAR LARSEN BAY START TIME 06/15/S2 04:00 DATE TIME ••••••••••••• 10/13112-04:00 10/13/82 08:00 10/13/82 12:00 10/13/82 16:00 10/13/82 20;00 10/13/82 24:00 10114182 04:00 10/14/82 08:00 10/14/82 12.00 10/14/82 16:00 10/14/82 20:00 10/14/82 24:00 10/15/82 04:00 10/15/82 08:00 10/15/82 12:00 10/15182 16:00 BYTE RAW DATA 1441 49 102 1443 49 102 1445 49 102 1441 50 104 1449 49 106 1451 49 106 DAILY AVERAGE VALUES 1453 1455 50 101 50 106 1451 50 101 1459 50 109 1461 50 108 1463 50 101 DAILY AVERAGE VALUES 1465 1461 1469 1411 50 106 49 105 49 105 49 108 10/15/82 20:00 1413 49 110 10/15/82 24:00 1415 50 110 10/1618204:00 10/16182 08:00 10/16/82 12:00 10/16/82 16:00 10/16/82 20:00 10/16/82 24:00 10/11182 04:00 10/11182 08:00 10/11182 12:00 10/11182 16:00 10/11182 20:00 10/11182 24.00 DAILY AVERAGE VALUES 1411 1419 1481 1483 1485 1481 50 110 51 111 54 112 53 112 53 110 52 109 DAILY AVERAGE VALUES 1489 1491 1493 1495 1491 1499 5% 108 52 101 51 101 51 108 51 101 52 106 DAILY AVERAGE VALUES DEPTH STAGE MV INCHES FEET •••• • ••••• ..211 .. 9.8 9.S 9.8 10.0 9.8 '.8 9.8 10.0 10. 0 10.0 10.0 10.0 10.0 10.0 10.0 9.8 9.8 9.8 9.S 10 0 9.9 10.0 10. 2 10.8 10. 6 10.6 10. 4 10.4 10.4 10.4 10.2 10.2 10.2 10.4 10.3 -68- 19.6 19.6 19.6 20.0 19.6 19.6 19.1 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 19.6 19.6 19.6 19.6 20.0 19. 1 20.0 20.4 Z1 6 21.2 21 .2 20.8 20.9 20.8 20.8 20.4 20 4 20.4 20.8 20.6 1.11 1. 11 1.11 1. 15 1. 11 1.11 1.12 1. 13 1. 13 1 . 13 1 . 13 1 . 13 1 . 13 1 . 13 1. 11 1. 01 1.01 1. 01 1. 01 .11 108 1. 09 1.12 1 .22 1.19 1.19 1. 15 1.16 1 . 1 3 1 . 13 1. 10 1 . 10 1.10 1. 13 1.12 DISCHG eFS ..s ... ,. 1 1. 1 1. 1 1.8 1.1 1. 1 1.2 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1,0 6,3 6,3 6.3 6.3 1.0 6.5 6.6 1.3 9 :; 8.1 8.1 8.0 8.1 1.S 1.5 6.9 6.9 6.9 1.5 1.2 TEMP DEG C • •••• 1.0 1 .0 1.0 2.0 3.0 3.0 1.1 3.5 3 . 0 3.5 4.S 4.0 3.5 3.1 3.0 2.5 .'1.. 5 4 U :; . 0 5.0 3.1 5.0 S.S 6.0 6.0 5.0 4 S :; 3 4.0 3.5 3. S 4.0 3.5 3.u 3.6 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME = •••••••••••• 10/18/82 04:00 10/18/82 08:00 10/18/BZ U:OO 10/18/82 16:00 10/18182 20:00 10/18/82 24:00 10/19/82 04:00 10/19182 08:00 10/19/82 12:00 10/19/82 16:00 10/19182 20:00 10/19/82 24:00 10/20/82 04:00 10/20/82 08:00 10/20/82 12:00 10/20/8216:00 10/20/82 20:00 10/20/82 24:00 10/21/8204:00 10/21/82 08:00 10/21/8212:00 10/21/8216:00 10/21/8220:00 10/2118224:00 10/22/8204:00 10/22/82 08:00 10/22/82 12:00 10/22/8216:00 10/22/82 20:00 10/22/8224:00 BYTE RAW DATA •••• •••••••• 1501 1503 1505 1501 1509 1511 52 106 52 105 52 105 52 108 52 101 52 10~ DAILY AVERAGE VALUES 1513 1515 52 105 52 105 1511 53 101 1519 54 108 1521 53 101 1523 53 105 DAILY AVERAGE VALUES 1525 1521 1529 53 104 53 104 53 104 1531 53 106 1533 53 106 1535 53 104 DAILY AVERAGE VALUES 1531 1539 1541 1543 1545 1541 53 104 :)3 103 53 103 53 104 53 103 53 102 DAILY AVERAGE VALUES 1549 1551 1553 53 102 52 102 :> 2 102 1555 53 102 1:)51 52 102 15H 52 101 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMP04.POD PAGE 26 08-AUG-83 START TIME 06/15/82 04:00 MV DEPTH INCHES •••• • ••••• 10.4 10.4 10.4 10.4 10.4 10.4 10. 4 10. 4 10.4 10. 6 10. 8 10.6 10.6 10.6 10. 6 10. 6 10. 6 10. 6 10. 6 10.6 10. 6 10. 6 10. 6 10. 6 10. 6 10.6 10. 6 10.6 10. 6 10.4 10 . 4 10. 6 10 . 4 10. 4 10 . :s 20,8 20,8 20.8 20.8 20.8 20.8 20.8 20,8 20,8 21 . 2 21.6 21 .2 21 .2 21 . 1 21.2 21.2 21.2 21.2 21 . 2 21 .2 21.2 21 .2 21.2 21.2 21.2 21 .2 21 . 2 21 .2 21 .2 20.8 20.8 212 20.8 20,8 20.9 STAGE FEET • •••• 1. 11 1 . 11 1. 11 1 . 11 1 . 11 1 . 11 1 . 11 1.09 1.09 1 . 13 1 . 16 1 . 13 1.13 1 . 12 1 . 11 1 . 11 1. 11 1 . 11 1 . 11 1 . 11 1 . 11 .09 1,09 1.09 109 1 .09 1.09 1 .09 1.01 1. 03 1. 03 1 .01 1.03 1.03 1.04 DISCHC eFS • ••• =. 1 . 1 1.1 1. 1 1. 1 1,1 1.1 1,1 6.1 6.1 1.4 8,1 1.4 1.4 1.3 1,0 1.0 1,0 1.0 1.0 1,0 1.0 6,6 6.6 6.6 6.6 6,6 6.6 6.6 6.2 5,6 5.6 6,2 5.6 5.6 5.8 T£MP DEC C 3.0 2,5 2.5 4.0 3.5 2.5 3.0 2.5 2.S 3.5 4.0 3. :i 2.:> 3. 1 2.0 2.0 Z 0 3.0 3.0 2.0 L3 2.0 1 . :) 1.5 2.0 1 . :i 1 . 0 1.6 1 . 0 1 .0 1 0 1 .0 1 . 0 0.5 0.9 APA HYDRO-ELECTRIC FEAS IBI L ITY STUDY FOUR VILLAGES PAGE 27 PREPARED BY DRYDEN , LARUE DATA FILE HUHP04.POD 08-AUG-83 HUHPY CREEK NEAR LARSEN BAY START TIHE 06115/82 04:00 DEPTH STAGE DISCHC TEMP DATE TIME BYTE RAW DATA MV INCHES FEET CFS DEC C •••••••• ••••• •••• •••••••• = ••• •••••• ••••• •••••• • •••• 10/23/82 04:00 1561 52 102 10 . 4 20.8 1 . 01 5.3 1 . 0 10/23182 08:00 1563 52 102 10.4 20.8 1.01 ::. .3 1.0 10/23/82 12:00 1565 52 102 10 .4 20.8 1. 01 5.3 1 . 0 10/13/82 16: 00 1547 52 103 10.4 20.8 1.01 :; . 3 1.::' 10/23/82 20:00 1569 52 102 10.4 20.8 1.01 3.3 1 . 0 10/23182 24:00 1571 54 101 10.8 21 . 6 1. 08 6.5 0.5 DAILY AVERAGE VALUES 10.5 20.9 1.02 5.5 1 . 0 10/14/82 04:00 1573 58 101 11 .6 23.2 1.19 8.9 0.5 10/24/82 08:00 1575 62 101 12 .4 24.8 1.33 12 G.5 10/24/82 12:00 1577 61 101 12.2 24.4 1.29 11 0.5 10/24/82 16:00 1579 53 101 10.6 21.2 1.03 3.5 0.5 10/24/82 20:00 1581 52 101 10.4 20.8 0.99 S.O O.S 10/24/82 24:00 1583 52 1 01 10.4 20.8 0.99 5.0 O. S DAILY AVERAGE VALUES 11. 3 22.5 1 . 14 8. 1 D.::. 10/25/82 04: 00 1585 53 101 10. 6 21.2 1 . 0 1 S.l 0.5 10/25/82 08:00 1587 52 101 10 . 4 20.8 0.97 4.6 O.S 10/25/82 12:00 1589 :it 103 10.2 20.4 0.94 4.2 1 . S 10/25/82 16:00 1591 51 104 10. 2 20.4 0.94 4.2 La 10/25/82 20:00 1593 51 103 10. 2 20.4 0.94 4 . 2 1 . 5 10/25/82 24:00 1595 51 101 10. 2 20.4 O. 94 4.2 O. 5 DAILY AVERAGE VALUES 10. 3 20.6 0.96 4.4 1 . 10/26182 04:00 1597 56 101 11 . 2 22.4 1 .09 6.6 a. ~ 10/26/82 08:00 1599 62 101 12.4 24.8 1.29 11 0 5 10/26/82 12:00 1601 64 101 12.8 25.6 1.35 13 0 5 DAILY AVERACE VALUES 12.1 24.3 1.24 10 0 .5 -70- APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUKPY CREEK NEAR LARSEN BAY DATE TIKE •••• = •••••••• 10/21/83 04:00 10/21183 08:00 10/21/83 12:00 10/21183 16:00 10/21/83 20:00 10/21183 24:00 10/28183 04:00 10/28/83 08:00 10/28183 12:00 10/28/83 16:00 10/28183 20:00 10/28/83 24:00 10/29183 04:01 10/29183 08:00 10/29183 12:00 10/29183 16:00 10/29183 20:00 10/29183 24:00 10/30i83 04:00 10/30/83 08:00 11i130/83 12:00 10/30/83 16:00 10/30/83 20:00 10/30/83 24:00 10/31/83 04:00 10/31183 08:00 10/31/83 12:00 10/11/83 16:00 10/31/83 20:00 10/31/83 24:00 BYTE RAV DATA • ••••••••••• 3 S 38 101 38 10 1 3S 102 1 35 101 9 34 102 11 34 104 DAILY AVERAGE VALUES 13 15 11 19 21 36 104 39 104 49 lOS 46 101 44 101 23 43 116 DAILY AVE.AGE VALUES 25 21 Z9 31 33 35 41 106 41 1 0 ~ 40 105 40 101 40 106 40 lOS DAILY AVERAGE VALUES 31 39 41 43 45 41 40 105 40 lOS 39 lOS 39 105 39 104 39 102 DAILY AVERAGE VALUES 49 51 53 39 102 39 103 39 105 55 39 101 51 43 101 59 41 106 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUKPD5.POD PAGE 1 08-AUG-83 START TIKE 10/21/83 04:00 KV DEPTH INCHES •••• • ••••• 1.6 1.6 1.0 1.0 6.8 6.8 1. 1 1.2 1.8 9.8 9.2 8.8 8.6 8.6 8.2 8.2 8.0 8.0 8.0 8.0 8.1 8.0 8.0 1.8 1.8 1.8 1.8 1.9 1.8 1.8 1.8 1.8 8.6 9.4 8.2 -71- lS.2 1 S . 2 14. 0 14.0 13.6 13.6 14.3 14 . 4 1S.6 19.6 18.4 11.6 11. 2 11.1 16.4 16.4 16.0 16.0 16.0 16.0 16.1 16.0 16.0 15.6 1 S . , 1 S . 6 15.6 1 S . 1 15.6 15.6 1 S . 6 15.6 11.2 18.8 16.4 STAGE FEET . _11 .. 1. 21 1. 21 1. 11 1. 11 1 . 13 1. 13 l. 19 l. 2D 1.30 1 .63 1.53 1. 41 1.43 1.43 1.31 1.31 l. 33 1 .33 1.33 1.33 l. 34 1.33 l. 33 1.30 1.30 1. 30 l. 30 1.31 l. 30 1 .30 1.30 1.30 1.43 l. 57 l. 37 DISCHG CFS •••••• 1 1 11 8.3 8.3 1.S 1.5 8.9 , . 1 12 24 20 11 16 16 14 14 13 13 13 13 13 13 13 12 12 12 12 12 12 12 12 12 16 21 14 TEKP DEG C == ••• D.S D.S 1.0 0.5 1. 0 2.1i D.~ LO 2.0 2.5 3.S 3.S 3.0 2.8 3.0 2.S 2.S 3.5 3.0 2.5 2.8 2.5 2.5 2.S 2.S 2.0 1.0 2.2 1. 0 l.5 2. :i 3.5 3.5 3.0 2.S APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED 8Y DRYDEN' LARUE DATA FILE HUMPO'.POD PAGE 2 OB-AUG-83 HUMPY CREEK NEAR LARSEN lAY START TIME 10/27/83 04:00 DATE TIME _c ••••••••••• 11/01/83 04:00 11/01/83 08:00 11/01/83 12:00 11/01/83 16:00 11/01183 20:00 11/01/83 24:00 11/02/83 04:00 11/02/83 08:00 11102/83 12:00 11/02/83 16:00 11/02/83 20:00 11/02/83 24:00 11/03/83 04:00 11/03/83 08:00 11/03/83 12'00 11/03/83 16:00 11/03/n 20:00 BYTE RAW DATA • ••••••••••• &1 63 6~ 67 69 71 45 105 44 105 43 105 44 106 43 1 O~ 4Z 104 DAILY AVERAGE VALUES 73 75 42 103 4Z 102 77 41 102 79 41 103 81 41 104 83 41 102 DAILY AVERAGE VALUES 85 87 89 91 93 40 102 41 102 40 1 D2 40 103 40 102 11/03/83 24:00 9' 40 101 11/04/83 04:00 11/04/83 08:00 11/04/8312:00 11/04/83 16:00 11/04/8320:00 11/04/83 24:00 11/05/83 04:00 11/05/83 08:00 11/05/83 U:OO 11/05/83 16:00 ll/U/83 20:00 11/05183 24:00 DAILY AVERAGE VALUES 97 99 101 103 46 101 50 101 52 101 47 101 105 40 101 107 41 101 DAILY AVERAGE VALUES 109 111 113 41 101 52 101 55 101 115 48 101 117 41 101 119 41 101 DAILY AVERAGE VALUES DEPTH STACE DISCHC MV INCHES FEET ers •••• • ••••• _: ... _.sa •• 9.0 8.8 8.6 8.8 8.6 8.4 8.7 8.4 8.4 8.2 8.2 8.2 8.2 8.3 8.0 8.2 8.0 8.0 8.0 8.0 8.0 9.2 10.0 10.4 9.4 8.0 8.2 9.2 9.4 10.4 11. 0 9.6 8.2 8.2 9.5 -72- 18.0 17.6 17.2 17.6 17.2 16.8 17.4 16.8 16.8 16.4 16.4 16.4 16.4 16.5 16.0 16.4 16.0 16.0 16.0 16.0 16.1 18.4 lO.O 20.8 18.8 16.0 16.4 18. 4 18.8 20.8 22.0 19. 2 16.4 16.4 18.9 1. 50 1.47 1.43 1. 47 1.43 1.40 1.45 1. 40 1. 40 I.J7 1. 37 1.37 1. 37 1.38 1.33 1. 37 1. 33 1. 33 1.33 1 33 1.34 1. 53 1. 67 1.73 1. 57 1.33 1. 37 1. 53 1. 57 1.73 1. 83 1. 60 1. 37 1. 37 1. 58 18 17 16 17 16 15 17 15 15 14 14 14 14 14 13 14 13 13 13 13 13 20 H 29 21 13 14 20 21 29 35 23 14 14 23 TEMP DEG C ••••• 2.5 2.5 2.S 3.0 2.5 2.0 2.5 1 .5 1 . 0 1 .0 1.5 2.0 1.0 1.3 1.0 1.0 1.0 1.5 1.0 0.5 1.0 0.5 O.S 0.5 0.5 0.5 0.5 0.5 O.S 0.5 O. S 0.5 0.5 O.S 0.5 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIPIE •••••••• ••••• 11/06/83 04:00 11/06/83 08:00 11/06183 12:00 11/06183 14:00 11106183 20:00 11/06/83 24:00 11/07183 04:00 11/01/83 08:00 11/07/83 12;00 11/01113 16:00 11/01/83 20:00 11/07113 24:00 11/08/83 04;00 11/08183 08:00 11/08/83 12:00 11/08/83 16:00 11/08/83 20;00 11/08/83 24:00 11/09183 04:00 11/09/83 08:00 11/09/8312:00 11/09/83 14:00 11/09/83 20;00 11/09/8324;00 11/10/83 04:00 11/10/83 08'00 11110/83 12:00 11/10/83 16;00 11/10/83 20:00 11/10/83 24:00 BYTE RAW DATA •••• • ••••••• 121 123 125 44 101 50 101 H 101 127 46 101 129 42 101 131 4f 101 DAILY AVERAGE VALUES 133 5& 101 135 60 101 131 55 101 139 44 102 141 41 102 143 43 101 DAILY AVERAGE VALUES 145 141 149 151 153 155 50 102 48 104 45 105 44106 43 104 42 104 DAILY AVERAGE VALUES 151 42 104 159 42 103 161 42 104 1&3 42 105 1&5 41 104 161 42 104 DAILY AVERAGE VALUES 169 111 113 115 117 I1f 41 104 41 104 41 104 41 105 42 105 42 105 DAILY AVERAGE VALUES FOUR VI LUGES DATA FItE HUMPOl.POD PAGE 3 0I-AUG-83 START TIME 10/21/83 04:00 DEPTH STAGE DISCHG MV INCHES FEET CFS •••• • ••••• • •••• • ••••• 8.8 10.0 10 . 2 9.2 8.4 9.8 9.4 11. 2 12.0 11. 0 8.8 8.2 8.& 10.0 10.0 9.& 9.0 8.8 8.& 8.4 9 . 1 8.4 8.4 8.4 8.4 8.2 6.4 8.4 8.2 8.2 8.2 8.2 8.4 8.4 8.3 11.& 20.0 20.4 18.4 16.8 19. & 18.8 22.4 24.0 22.0 17.& 16.4 17.2 19.9 2D.0 19.2 18.0 11.6 17.2 16.8 18.1 16.8 U.8 16.8 16.8 14.4 16.8 16.7 16.4 16.4 16.4 16.4 U.8 16.8 U.~ 1. 41 1.&1 1. 10 1. 53 1. 40 1. &3 1.'S1 1. 81 2.00 1. 83 1. 41 1. 31 1.43 1.&& 1.&1 1.&0 1. SO 1. 41 1.43 1. 40 1.51 1. 40 1. 40 1. 40 1. 40 1. 31 1.40 1.39 1.31 1. 31 1. 31 1. 31 1. 40 1. 40 1.38 17 26 21 20 15 24 22 31 H 35 17 14 U 28 26 23 18 11 16 IS 19 15 15 15 l!i 14 15 15 14 14 14 14 IS 15 14 TEMP DEC C ..:_ . O.!) 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 1.0 1.0 0.5 0.1 1.0 2.0 2.5 3.0 2.0 2.0 2.1 2.0 1.5 2.0 2.~ %.0 2.0 2.0 2.0 2.0 2.0 2.S 2.S 2.5 2. 3 lPA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUftPY CREEK NEAR LARSEN BAY DATE TIftE ... _:a... . .... 11/11/83 04:00 11/11/83 08:00 11/11/83 12:00 11/11183 16:00 11/11/83 20:00 11/11/83 24:00 11/12/8304:00 11/12/83 08:00 11/12/83 U:DO 11/12/83 16:00 11/12/83 20:00 11/12/83 24:00 11/13/83 04:00 11/13/83 08:00 11/13/83 12:00 11/13/83 16:00 11/13/83 20:00 11/13183 24:00 11/14/83 04:00 11/14/83 08:00 11/14/83 12:00 11/14183 16:00 11/14/83 20:00 BYTE RAW DATA •• 21. • ••••••• 181 44 104 183 43 104 185 43 104 18'1 43 105 189 43 106 191 43 106 DAILY AVERAGE VALUES U3 44 10'1 195 47 10'1 19'1 48 107 199 47 101 201 4'1 106 203 46 106 DAILY AVERAGE VALUES :u:s 207 209 211 213 215 41 106 4'1 106 46 106 4'1 106 46 106 46 105 DAILY AVERAGE VALUES 211 2U 221 223 225 46 105 46105 46 105 n 105 45 104 11/14/83 24:00 227 45 102 11/15/83 04:00 11/1;)183 08:00 11/15/83 12:00 11115183 16:00 1l/UII3 20:00 11/15/83 24:00 DAILY AVERAGE VALUES 229 231 133 235 237 239 n 101 49 101 52 101 49 101 48 101 51 101 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUftPOS.POD PAGE 4 08-AUG-83 START TIftE 10/2'1/83 04:00 DEPTH STAGE DISCHG ftV INCHES FEET eFS :s... . ....• • •••• •••••• 8.8 8.6 8.6 8.6 8.6 8.6 8.6 8.8 9.4 9.6 9.4 9.4 9.2 9.3 9.4 9.4 9.2 9.4 9.2 9.2 9.3 9.2 9.2 9.2 9.0 9.0 9.0 9. 1 9.0 9.8 10.4 9.8 9.6 10.2 9.8 -74- 1'1.6 1'1.2 1'1.2 1'1.2 1'1. 2 1'1.2 1'1.3 1'1.6 18.8 19.2 11.8 18.8 18.4 18.6 18.8 18.8 18.4 18.8 18.4 18.4 18.6 18.4 18.4 18.4 18.0 18.0 18.0 18.2 18.0 19.6 20.8 19.6 19.2 20.4 19. 6 1.43 1.43 1.43 1. 43 1.43 1.43 1 43 1.42 1.42 1.42 1.42 1.42 1.42 1.42 1. 41 1. 41 1 .41 1.41 1.41 1.41 1.41 1. 40 1.40 1 .40 1. 40 1.40 1.40 1.40 1. 39 1.39 1.39 1. 39 1. 39 1. 39 1. 39 16 16 16 16 16 16 16 15 IS 15 15 15 IS 15 15 15 15 15 1:) 15 15 15 n 15 1 S 15 IS 15 14 14 14 14 14 14 14 TEMP DEG e sa ••• 2.0 2.0 2.0 2.5 3.0 3.0 2.4 3.S 3 :) 3.5 3.S 3.0 3.0 3.3 3.0 3.0 3.0 3.0 3.0 2.5 2.9 2.5 2.S 2.5 2.5 2.0 1. 0 2.2 O.S D.S O.S 0.5 0.5 0.5 O.S APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN' LARUE DATA FILE HVMP05.POD PAGE 5 08-AUG-a:; HUMPY CREEK HEAR LARSEN BAY START TIME 10/27/83 04:00 DATE TIME •••••••• ••••• 11/16/83 04:00 11/16/83 08:00 11/16/83 12:00 11/16/83 16:00 11/16183 20:00 11116183 24:00 11/11/83 04:00 11/11/83 08:00 11/17/83 12:00 11117183 16:00 11/17/83 ZO'OO 11/1?!83 24:00 11/18/83 D4:00 11/18/83 08:00 11/18/83 12:00 11/18183 16:00 11/18/83 20:00 11/18/83 24:00 11/19183 04:00 11/19/83 08:00 11/1918312:00 11119183 16:00 11119/83 20:00 11/19/83 24:00 11120/83 04:00 11/20/83 08:00 l1/Z0183 12:00 11/%0183 16:00 11/20/83 ZO:OO 11/20/8324:00 BYTE RAW DATA • ••••••••••• 241 241 245 sa 101 64 0 o 101 247 69 101 249 68 101 251 68 101 DAILY AVERAGE VALUES 253 69 101 ns 71 101 257 72 101 259 64 101 261 54 101 263 5S 101 DAILY AVERAGE VALUES 265 267 269 271 273 275 60 101 69 101 75 101 76 101 78 101 79 101 DAILY AVERAGE VALUES 277 279 Ul U3 80 101 80 101 7~ 101 57 101 285 48 101 287 46 101 DAILY AVERAGE VALUES 289 HI H3 n 101 44 10 1 46 101 295 39 104 297 U 104 299 36 104 DAILY AVERAGE VALUES DEPTH STAGE DISeHG MV INCHES FEET CFS •••• • ••••• ••••• •••••• 11. 6 12.8 12.8 13.8 13. 6 13. 6 13.0 13.8 14.2 14.4 12.8 10.8 11 .0 12.8 12.0 13.8 15.0 15.2 15.6 15.8 14.6 16.0 16.0 I!L 0 11. 4 9.6 9.2 12. , 9.0 8.8 9.2 7.8 7.2 7.2 8.2 23.2 25.6 25.6 27.6 27.2 27.2 26.1 27.6 28.4 28.8 n.6 21. 6 22.0 2S.7 24.0 27.6 30.D 30.4 31.2 31.6 29.1 32.0 32.0 30.0 22.8 19.2 18.4 25.7 18.0 17.6 18.4 15.6 14.4 14.4 16.4 1.38 1. 38 1. 38 1.38 1. 38 LSI 1. 38 1. 37 1. 37 1. 37 1.37 1. 37 1. 37 1. 37 1. 36 1. 36 1.36 1.36 1.36 1.36 1.36 1. 35 1. 3S 1. 35 1.35 1 .35 1. 35 1. 35 1. 50 1.47 1 .53 1. 30 1. 20 1. 20 1. 37 14 14 14 14 14 14 14 14 14 14 14 14 14 14 13 13 13 13 13 13 13 13 13 13 13 13 13 13 18 17 20 12 9. 1 9. 1 14 TEMP DEC C • ••• 2 0.5 0.5 ASSUMED PREVo 0.5 ASSUMED PREVo O. S 0.5 0.5 0.5 0.5 O.S 0.5 0.5 0.5 O.S o.~ 0.5 O.S 0.5 0.5 O.S 0.5 O.S 0.5 O.S 0.5 0.5 0.5 0.5 0.5 O.S 0.5 0.5 2.0 2.0 2.0 1.3 lPA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED 8Y DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIKE •••••••• • •••• 11/21183 04:00 11/21183 08:00 11/21183 12:00 11/Z1183 16:00 11/21/83 20:08 11/21183 24:00 11/22/83 04:00 11/22/83 08:00 11/22/8312:00 11/22183 16:00 11/22/83 20:00 11/22/83 24:00 11/23183 04:00 11/23/83 08:00 11/23/83 12:00 11/23/83 10:00 11/23183 20:00 11/23183 24:00 11/24/83 04:00 11/24183 08:00 11124183 12:00 11/24183 10:00 11/24183 20:00 11/24183 24:00 11/25/83 04:00 11125/8308:00 11115/83 12:00 11/25/83 16:00 11113/83 20:00 BYTE RAW DATA •••••••••••• 301 36 104 303 36 104 30S 36 105 307 36 105 309 37 105 311 36 105 DAILY AVERACE VALUES 313 36 105 315 37 IDS 317 38 106 319 39 106 321 39 106 323 43 105 DAILY AVERACE VALUES 325 327 329 331 333 335 43 105 41 106 40 105 40 105 39 104 39 104 DAILY AVERACE VALUES 337 38 104 33' 38 104 341 38 104 343 39 105 345 38 104 347 38 104 DAILY AVERAGE VALUES 349 351 353 3:;5 351 38 104 38 106 39 106 39 107 39 106 11/25/83 24:00 359 39 107 DAILY AVERAGE VALUES FOUR VILLAGES DATA FIL! HUl'fP05.POD PAGE 6 o8-AUC-83 START TIKE 10/27/83 04:00 DEPTH STAGE DISCHG MV INCHES FEET CFS •••• • ••••• • •••• 7.2 7.2 7.2 7.2 7.4 7.2 7.2 7.2 7.4 7.6 7.8 1.8 8.6 7.7 8.6 8.2 8.0 8.0 7.8 7.1 8.1 7.6 7.6 7.6 7.8 7.6 7.6 7.6 7.6 7.6 7.8 7.8 7.8 7.8 7.7 -76- 14.4 14.4 14.4 14.4 14 . 8 14.4 14.5 14.4 14.8 IS.2 IS. , 15.6 17.2 15.5 17.2 10.4 10.0 16.0 15.6 15.6 16.1 15.2 15.2 15.2 15.6 15.2 15.2 15.3 15. 2 15.2 15. 6 15.6 1:S.6 15.6 15.5 1. 20 1.20 1. 20 1. 20 1. 23 1. 20 1. ZI 1.20 1.23 1.27 1. 30 1. 30 1.43 1.29 1.43 1. 37 1. 33 1.33 1. 30 1. 30 1. 34 1 27 1. 27 1. 27 1. 30 1. 27 1.27 1. 27 1. 27 1. 2 '7 1. 30 1. 30 1. 3D 1. 30 1.29 , . 1 9. 1 , . 1 9. 1 9.9 9. 1 9.2 9. 1 9.9 11 12 12 10 12 16 14 13 13 U 12 13 11 11 11 U 11 11 11 11 11 12 12 12 12 11 TEKP DEG C • •••• 2.0 2.0 2.5 2.5 2.S 2.5 2.3 2.5 2.S 3.0 3.0 3.0 2.5 2.8 2.S 3.0 2.5 2.5 2.0 2.0 2.4 2.0 l.o 2.0 2.S 2.0 20 2.1 2.0 3.0 3.0 3.5 3.0 3.5 3. a APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME •••••• c= •• =_. 11/26/83 04:00 11/26/83 08:00 11/26/83 12:00 11116183 16;00 11/26183 20:00 11/16/83 24;00 11/2'1/8304:1i0 1112'1183 08:00 11/2'118312:00 11/2'1183 16;00 1111'1183 20;00 11/2'1IU 24:00 11/28/83 04:00 11/ZS/83 08:00 11/28/83 12:00 11/28183 16:00 11/28/83 ZO:OO 11/28/8324:00 11/19/83 1i4:00 11/29/83 08;00 11129/83 12:00 11129183 16:00 11/29183 20:00 11/29183 24:00 11/30/83 04:00 11/30/83 08:00 BYTE RAW DATA -.......... . 361 363 40 10'1 41 10'1 365 41 10'1 361 U 10'1 369 41 10'1 371 40106 DAILY AVERAGE VALUES 3'13 3'1S 3'11 3'19 381 383 40 106 39 105 at lOS 39 106 3J 106 38 105 DAILY AVERAGE VALUES 38S 38 lOS 38'1 38 105 389 38 104 391 38 104 393 38 103 395 38 103 DAILY AVERAGE VALUES 397 399 401 403 40S 40'1 38 1IJ3 38 103 38 102 38 103 38 104 3'1 102 DAILY AVERAGE VALUES 409 411 46 101 55 101 11130/83 12:00 413 60 101 11/30/83 16:00 415 65 101 11/30/83 20:00 41'1 69 101 11/30/83 24:00 419 '12 101 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMPDS.POD PAGE 1 08-AUG-83 START TIME 10/21183 04:00 MV 8.0 a.2 8.2 8.4 8.2 8.0 8.2 8.0 7.8 '1.8 7.8 '1.8 7.6 '1.a 7.6 '1.6 7.6 '1.6 '1.6 '1.6 '1.6 '1.6 7.6 '1.6 '1.6 '1.6 '1.4 '1.6 9.2 11.0 12.0 13.0 13.8 14.4 12.2 -77- DEPTH INCHES 16.0 16.4 16.4 16.8 16.4 16.0 16.3 16.0 15.6 15.6 15.6 IS.6 15.2 15.6 15. 2 15.2 15.2 15.2 15.2 15.2 15.2 IS.2 15.2 1 S. 2 1 S . 2 1:; .2 14.8 15.1 IB.4 22.0 24.0 l6.D 2'1.6 28.8 24. S STAGE FEET • •••• 1.33 1. 37 1. 3 '1 1. 40 1.3'1 1.33 1.36 1. 33 1. 30 1. 30 1. 30 1. 30 1.2'1 1. 30 1. 2 '1 1.2'1 1.2'1 1.2'1 1. 2 '1 1.21 1. 2 '1 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 DISCHG cn :;;:=-: •••• 13 14 14 1 S 14 13 14 13 13 12 12 12 1 1 12 1 1 11 11 1 1 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 TEMP DEC C 3.5 3.5 3. S 3.S 3.S 3.0 3.4 3.0 2.S 2.5 3.0 3.0 2.5 2.8 2.S 2.S 2.0 2.0 1 . 5 I.S 2.0 1.5 1.S 1.0 1.5 2.0 1.0 1.4 0.5 0.5 O.S O.S O.S O.S 0.5 lPl HYDRO-ELECTRIC FE1SIBILITY STUDY PREPARED BY DRYDEN , LARUE HUHPY CREEK NEAR LARSEN BAY DATE TI"E c....... ..a .. 12/01/83 04:00 12/01/83 08:00 12/01/83 12:00 12/01/83 16:00 12/01/83 20:00 12/01/83 24:00 12/02/83 04:00 12/02/83 08:00 12/0%/83 12:00 12/02/83 16:00 12/02/83 20;00 12/02/8324:00 12/03/83 04:00 12/03/83 08:00 12/03/83 12:00 12/03113 16:00 12/03/83 20:00 12/0311324:00 12/04/83 04:00 12/04/83 08:00 12/04183 12:00 12/04/83 16:00 12/04183 20:00 12/04/83 24:00 12/05183 04:00 H/OS/83 08:00 12/05/83 12:00 12/05/83 16:00 12/05/83 20:00 BYTE RAli DATA •••• • ••••••• 421 75 101 423 78 101 US 80 101 427 8Z 101 429 83 101 431 85 101 DAILY AVERAGE VALUES 433 435 437 439 441 443 86 101 88 101 Sf 101 91 101 92 101 9Z 101 DAILY AVERAGE VALUES 44S 447 449 451 453 n 101 94 101 94 101 95 101 U 101 455 103 101 DAILY AVERAGE VALUES 457 106 101 459 108 101 461 109 101 463 107 101 465 "101 467 87 101 DAILY AVERAGE VALUES 469 471 473 475 4?? 79 101 6t 101 65 101 62 101 57 101 12/05/83 24:00 479 51 101 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUHP05.PDD PAGE 8 08-AUG-83 START TI"E 10/27/83 04:00 "V DEPTH INCHES •••• • ••••• 15.0 15.6 16.0 16.4 16.6 17.0 16.1 17.2 17.6 17.8 18.2 18.4 18.4 17.9 18.6 18.8 18.8 19.0 19.6 20.6 19.2 21.2 21.6 21.8 21.4 19.8 17.4 20.5 IS.' 13.8 13.0 12.4 11. 4 10.2 12.8 -7R- 30.0 31.2 32.0 :12.8 33.2 34.0 32.2 34.4 3S.2 35.6 36.4 36.8 36. a 35.9 37.2 37.6 37.6 38.0 39.2 41.2 38.S 42.4 43.2 43.6 42.8 39.6 34.8 41 . 1 31.6 27.6 Z6.0 24.8 Z2.8 20.4 25.5 STAGE FEET • •••• l.U 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 l.U 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 DISCHG CFS • ••••• 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 TEMP DEG C O.S 0.5 O.S 0.5 O.S 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 O.S 0.5 0.5 0.5 0.5 0.5 O.S 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 O.S 0.5 0.5 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLAGES PREPARED BY DRYDEN' LARUE DATA FILE HUMPD5.POD PAGE 9 08-AUG-83 HUMPY CREEK NEAR LARSEN BAY START TIME 10/21/83 04:00 DATE TIME = •••••••••••• 1%/06/83 04:00 12/06183 08:00 1%/06183 12:0D 12/06183 1&;00 12/06183 %0:00 12/06183 14:00 12/01183 04:00 12/07183 08:00 12/01183 12:00 12/07/83 1&:00 12/01183 20:00 12/07183 24:00 12/08183 04:00 12/08/83 08:00 12/08183 12:00 12/08/83 16:00 12/08183 20:00 12/08/83 24:00 12/09183 04:00 12/09183 08:00 12/09183 12:00 12/09183 1&:00 12/09183 20:00 12/09183 2.4:00 12/10/83 04:00 12/10183 08:00 12110/83 12:00 12110/83 16:00 12/10/83 20:00 12/10/83 24:00 BYTE RAW DATA •••• • ••••••• 481 49 101 483 48 101 485 51 101 481 S1 101 489 41 103 491 41 104 DAILY AVERAGE VALUES 493 41 104 495 40 104 491 39 104 499 38 104 501 31 104 S03 37 104 DAILY AVERAGE VALUES 505 31 104 501 37 104 509 3& 104 511 35 104 513 35 103 515 35 103 DAILY AVERAGE VALUES 511 35 103 519 34 103 521 34 102 H3 34 102 525 35 102 H1 35 102 DAILY AVERAGE VALUES 529 S 31 S33 53S 531 539 3& 103 38 104 39 104 41 105 43 105 44 105 DAILY AVERAeE VALUES DEPTH STAGE OISCHe MV INCHES FEET ers :IS.. • ••••• ••••• •••••• 9 .• 9.4 10.2 11. 4 8.2 8.2 9.6 8.2 8.0 1.8 1.6 7.4 1.4 1.1 7.4 1.4 7.2 1.0 1.0 1.0 1.2 1.0 6.8 6.8 6.' 1.0 1.0 6.9 1.2 1.6 7.8 '.2 8.6 '.8 8.0 -7q- 19.6 19 2 10.4 2Z.8 1&.4 16.4 19.1 16.4 16.0 15.6 15.2 14.8 14. 8 15.5 14.8 14. 8 14.4 14.0 14.0 14.0 14. :; 14.0 13.6 11.6 13.6 14 . 0 14.0 13.8 14.4 15.2 15.4 16.4 17.2 11.6 16.1 1.26 1.24 1.26 1.26 1.26 1.26 1.26 1. 31 1.33 1. 30 1. 27 1. 23 1.23 1. 29 1.23 1. 23 1. 20 1. 11 1. 17 1. 11 1.19 1. 11 1.13 1.13 1. 13 1 . 1 1 1. 11 1. l!i 1. 20 1. 21 1 . :; 0 1 .31 1. 43 1. 41 1.34 11 11 11 11 11 11 11 14 13 12 11 9.9 9.9 11 9.9 9.9 9. 1 8.3 8.3 8.3 9.0 8.3 1.5 7.5 7.5 8.3 8.3 7.9 9. 1 11 12 14 16 11 13 TEMP DEC C 0.5 0.5 0.5 0.5 l.l 2.0 0.9 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2 . 0 Z.ti ~.O 2.0 l.l 1.5 1., 1 . 5 1.5 1.0 1.0 1.0 1 . 0 1.2 I.S 2.0 2.0 2.5 2.5 2.5 2.2 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME =_==2 •••••••• 12/11/8304:00 12/11/83 08:00 12/11/83 12:00 12/11183 16:00 12/11/83 20:00 12/11/83 24;00 12/12/83 04:00 12112/83 08:00 12/12/83 12:00 12/12/83 16:00 12/12/83 20:00 12/12/83 24:00 12/13/83 04:00 12/13/83 08:00 12/13183 12;00 12/13/83 16:00 12/13/83 20:00 12/13/83 24;00 12/14/83 04:00 12/14/83 08;00 12/14/83 12:00 12/14/13 16:00 12/14/83 20:00 12114/83 24:00 12/15/83 04:00 12/15/83 08:00 11115/83 12:00 12/15/83 16:00 12115183 20:00 12/15/83 24:00 BYTE RAW DATA •••• ••••••• s HI 543 545 547 5H 551 42 lOS 43 105 42 105 42 105 42 105 42 105 DAILY AVERAGE VALUES 553 42 105 555 42 105 557 39 105 S59 41 lOS 561 39 105 563 38 lOS DAILY AVERAGE VALUES 565 567 569 571 5n 38 104 37 103 36 103 37 103 36 103 575 35 102 DAILY AVERAGE VALUES 577 35 101 5'19 36 102 581 38 103 583 40 104 585 42 104 587 41 104 DAILY AVERAGE VALUES S89 591 593 595 597 599 41 104 42 105 42 104 42 105 43 105 42 105 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP05.POD PAGE 10 08-AUG-83 START TIME 10/27/83 04:00 DEPTH INCHES •••• • ••••• 8.4 8.6 8.4 1.4 8.4 8.4 8.4 8.4 8.4 7.8 8.2 7.8 7.6 1.0 7.6 7.4 7.2 7.4 7.2 7.0 7.3 7.0 7.2 7.6 8.0 8.4 8.2 7.7 8.2 8.4 8.4 8.4 8.6 8.4 8.4 -80- 16.8 17.2 16.8 16.8 16.8 16.8 16.9 16.8 16.8 15 . , 16.4 15.6 15.2 16.1 15.2 14.8 14.4 14.8 14.4 14.0 14.6 14.0 14.4 15.2 16.0 16.8 16.4 15.5 16.4 16. a 16.8 16.8 17.2 16.8 16.8 STAGE FEET ••••• 1. 40 1.43 1. 40 1.40 1. 40 1. 40 1.41 1. 40 1.40 1. 30 1.37 1. 30 1.27 1.34 1.27 1.23 1.20 1. 23 1. 20 1. 17 1. Z2 1. 17 1. aD 1. 27 1. 33 1.40 1 .37 1.29 1.37 1.40 1. 40 1. 40 1. 43 1. 40 1. 40 DISCHG ers •••••• 15 16 15 15 15 15 15 15 15 12 14 12 11 13 11 ,., '.1 ,., 9.1 8.3 ,.S 8.3 , . 1 11 13 15 14 12 14 15 15 15 16 15 15 TEMP DEG C 2.5 2.5 2.5 2.5 2.5 2.5 z.s 2.5 2.5 Z.5 2.5 2.5 2.5 2.5 2.0 1 .5 1.5 1.5 1.5 1.0 1.5 0.5 1.0 1.5 2.0 2.0 2.0 1.5 2.0 2.5 2.0 2.5 2.5 2.5 2.3 APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN & LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME • = •••••••• ::as. 12/16/83 04:00 12/16/83 08:00 12/16/83 12:00 12/16/83 16:00 12/16183 20:00 12/16/83 24:00 12/17/8304:00 12/17/83 08:00 12/17/83 12:00 12/17183 16:00 12/17/83 20:00 12/17/83 24:00 12/18/8304:00 12/18/83 01:00 12/18183 12:00 12/18183 16:00 12/18183 20:00 12/18/8324:00 12/19183 04:00 12/19/83 08:00 12/19183 12:00 12/19183 16:00 12/19/83 20:00 12/19183 24:00 12/20183 04:00 12/20/83 08:00 12/20/83 12:00 12/20/83 16:00 12/20183 20:00 12/20183 24:00 BYTE RAW DATA =--=-•••••••• 601 41 105 603 39 105 605 38 104 607 38 104 609 37 104 611 37 104 DAILY AVERAGE VALUES 613 615 617 619 621 623 36 103 36 103 36 103 36 104 35 104 35 104 DAILY AVERAGE VALUES 625 34 104 627 34 104 629 34 104 631 34 104 633 34 103 635 34 102 DAILY AVERAGE VALUES 637 34 101 639 35 101 641 36 101 643 36 103 645 37 103 647 37 103 DAILY AVERAGE VALUES 649 651 653 655 657 37 103 37 104 36 104 37 104 37 104 659 38 104 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE HUMPoS.POD PAGE 11 o8-AUG-83 START TIKE 10/27/83 04:00 MV 8.2 7.8 7.6 7.6 7.4 7.4 7.7 7.2 7.2 7.2 7.2 7.0 7.0 7. 1 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.8 7.0 7.2 7.2 7.4 7.4 7.2 7.4 7.4 7.2 7.4 7.4 7.6 7.4 DEPTH INCHES 16. 4 15 .6 15.2 15.2 14 . 8 14.8 15. 3 14.4 14. 4 14. 4 14. 4 14.0 14.0 14.3 13.6 13.6 13.6 13.6 13. 6 13.6 13. 6 13.6 14.0 14 .4 14. 4 14.8 14.8 14.3 14. 8 14.8 14.4 14.8 14.8 15.2 14. 8 STAGE FEET 1.37 1.30 1.17 1.27 1.23 1.23 1. 28 1. 20 1. 20 1. 20 1. 20 1. 17 1. 17 1.19 1. 13 1 . 13 1. 13 1. 13 1.13 1 . 13 1. 13 1.13 1 . 17 1.20 1.20 1.23 1.23 1.19 1.23 1. 23 1.20 1 .23 1. 23 1.27 1.23 DISCHC CFS s ••• s. 14 12 11 11 9.9 9.9 11 9. 1 9. 1 9. 1 9. 1 8.3 8.3 8.8 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 8.3 9.1 9. 1 9.9 9.9 9.0 9.9 9.9 9. 1 9.9 9.9 11 9.9 TEMP DEG C 2.5 2.5 2.0 2.0 2.0 2.0 2.2 1 .5 1.5 1.5 2.0 2.0 2.0 1.8 2. 0 2.0 2.0 2.0 1.5 1.0 1.8 0.5 0.5 0.5 1.5 1.5 1.:i 1 . 0 1.5 2.0 2.0 2.0 2.0 2.0 1 . , APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUKPY CREEK NEAR LARSEN BAY DATE TIKE •••••••• • a ••• 12/21/83 04:00 12/%1/83 08:00 12/21/83 12:00 12/21/8316:00 12/21/83 20:00 12/21/83 24:00 12/22/83 04:00 12/22/83 08:00 12/22/83 12;00 12/22/83 16:00 12/22/83 20:00 12/21/83 24:00 12/23/83 04:00 12/23/83 08:00 12/23113 12:00 12/23/83 16:00 12/%3/83 20:00 12/23/83 24:00 12/24183 04:00 12/24/83 08:00 12/24/83 12:00 12/24/83 16:00 12/24/83 20:00 12/24/13 24:00 12/25183 04:00 12/25/83 01:00 12/25183 12:00 12/25/83 16:00 12/25183 20:00 12/25/83 24:00 BYTE RAW DATA •••• •••••••• 661 37 104 663 36 104 665 3!S 104 667 36 104 669 35 104 671 34 103 DAILY AVERAGE VALUES 673 67S 677 679 681 683 34 102 34 101 33 101 34 101 34 101 33 101 DAILY AVERAGE VALUES 33 101 687 33 101 689 33 101 691 34 102 693 34 102 695 33 103 DAILY AVERAGE VALUES 6" 33 102 69' 34 101 '101 38 101 103 34 101 705 32 101 707 32 101 DAIlY AVERAGE VALUES 709 711 713 715 717 34 101 41 101 38 101 32 102 32 103 719 32 103 DAILY AVERAGE VALUES FOUR VILLAGES DATA FILE KUHPOS.POD PAGE 12 08-AUG-U START TIKE 10/27/83 04:00 MV DEPTK INCHES =... . ..... 7.4 7.2 7.0 7.2 7.0 6.8 7. 1 6.8 6.8 6.6 6.8 6.8 6.6 6.7 6.6 6.6 6.6 6.8 6.8 6.6 6.7 6.6 6.8 7.6 6.8 6.4 6.4 6.8 6.8 8.2 7.6 6.4 6.4 6.4 7.0 -R?- 14.8 14.4 14.0 14.4 14.0 13.6 14.2 13.6 13. , 13.2 13.6 13.6 13.2 13.5 13.2 13.2 13.2 13.6 13.6 13.2 13.3 13.2 13.6 15.2 13.6 12.8 12.8 13.5 13.6 16.4 15.2 12.8 12.8 12.8 13.9 STAGE FEET ••••• 1. 23 1. 20 1. 17 1.20 1. 17 1.13 1.18 1.13 1.13 1. 10 1. 13 1. 13 1. 10 1. 12 1. 10 1. 10 1. 10 1. 13 1. 13 1. 10 1.11 1.10 1. 13 1. 27 1.13 1. 07 1. 07 1 . 13 1 . 13 1. 37 1.27 1. 07 1. 07 1. 07 1.16 OISCHG ers 9.9 9. 1 8.3 9. 1 8.3 7.5 8.7 7.5 7.1 6.' 1.5 7.5 6.' 7.3 6.9 6.9 6.9 7.5 7.5 6.' 7.1 6.' 7.S 11 7.S 6.2 6.2 7.::; 7.5 14 11 6.2 6.2 6.2 8.4 TEKP DEG C 2.0 2.0 2.0 2.0 2.0 1.5 1.9 1.0 0.5 0.5 0.5 O.S 0.5 0.6 0.5 0.5 O.S 1.0 1.0 1.5 0.8 1 .0 0.5 0.5 0.5 0.5 0.5 0.6 0.5 O.S O.S 1.0 1.5 1.5 0.' APA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME == ••••• a •••• a 12/26/83 04:00 12/26/83 08:00 12/26/83 12:00 12/26/83 16:00 12/26183 20:00 12/26/8324:00 12/27/83 04;00 12/27/83 08:00 12/27183 12:00 12/27/83 16:00 12/27183 20:00 12/27/83 24:00 12/28/83 04:00 12/28183 08:00 12/28/83 12;00 12/28183 16:00 12/28/83 20;00 12/28113 24:00 12/29/83 04:00 12/29/83 08:00 12/29/8312:00 12/29/83 16:00 12/29/83 20:00 12/29/83 24:00 12/30/83 04:00 12/30/83 08:00 12/30113 12:00 12/30/83 16:00 12/30/83 20:00 12/30183 24:00 BYTE RAW DATA •••• •••••••• 721 723 72:5 727 729 731 33 104 36 104 3:5 104 36 105 38 104 37 104 DAILY AVERAGE VALUES 733 73:5 35 104 3:5 104 737 41 104 739 41 104 741 40 104 743 38 104 DAILY AVERAGE VALUES 74:5 38 104 747 41 105 749 :54 104 751 5:5 105 7:53 56 10:5 7:5:5 59 105 DAILY AVERAGE VALUES 757 759 761 58 105 56 104 S6 104 763 56 104 765 56 104 767 56 104 DAILY AVERACE VALUES 769 771 773 56 104 55 103 :55 103 775 54 103 777 54 104 779 S4 103 DAILY AVERACE VALUES FOUR VILLACES PACE 13 08-AUC-83 MV 6.6 7.2 7.0 7.2 7.6 7.4 7.2 7.0 7.0 8.2 8.2 8.0 7.6 7.7 7.6 8.2 10. 8 11.0 11. 2 11.8 10.1 11 .6 11. 2 11. 2 11. 2 11. 2 11 .2 11 . 3 11. 2 11. 0 11 .0 10.B 10. B 10.8 10.9 -8~- DATA FILE HUMPO:5.POD DEPTH INCHES 13.2 14.4 14.0 14. 4 1:5.2 14.8 14.3 14.0 14.0 16.4 16.4 16.0 15.2 15.3 1:5 . 2 16.4 21.6 22.0 22.4 23.6 20.2 23.2 22.4 22.4 22.4 22.4 22.4 22. :5 22.4 22.0 22.0 21 .6 21 .6 21 .6 21. 9 START TIME 10/27/83 04;00 STAGE FEET .::1 ••• 1 . 10 1. 20 1. 17 1.20 1. 27 1.23 1. 19 0.6~ 0.65 0.B5 0.85 0.81 0.75 0.76 0.7:5 O.B:5 1. Z8 1.31 1. 35 1.45 1.16 1 . 41 1. 3:5 1. 35 1 .3:5 1 .3:5 1.3:5 1.36 1. 35 1. 31 1. 31 1.2B 1.Z8 1.2B 1. 30 DISCHe crs 6.9 9.1 B.3 9. 1 11 9.9 9.0 1.3 1 . 3 3.0 3.0 2.6 2.0 2.2 2.0 3.0 11 12 13 16 9.6 1:5 13 13 13 13 13 13 13 12 12 11 11 11 12 TEMP DEC C l.0 2.0 2.0 2.:5 2.0 2.0 2 . 1 2.0 2.0 l.0 2.0 2.0 2.0 2.0 2.0 2.5 2.0 2.5 2.5 2.S 2.3 2.S 2.0 2.0 2.0 2.0 2.0 2. 1 2.0 1 .5 1.S 1 .5 2.0 1 .5 1.7 1PA HYDRO-ELECTRIC FEASIBILITY STUDY PREPARED BY DRYDEN , LARUE HUMPY CREEK NEAR LARSEN BAY DATE TIME =:.=..... a •••• U/31/83 04:00 12/31/83 08:00 U/31/83 12:00 12/31/83 16:00 12/31/83 20:00 12/31/83 24:00 01/01/84 04:00 01/01/84 08:00 01/01/84 12:00 01/01184 16:00 01/01/84 20:00 01/01/84 24:00 01/02184 04:00 01/02/84 08:00 01/02/84 12:00 01/02/84 16:00 01/02/84 20:00 01/02/84 24:00 01/03/84 04:00 01/03/84 08:00 01/03/84 12:00 01/03/84 16:00 01/03/84 20:00 01/03/84 24:00 01/04/84 04:00 01/04/84 08:00 01/04/84 12:00 01104/8416'00 01/04/84 20.00 01/04/84 24:00 BYTE RAW DATA •••• •••••••• 781 54 103 783 54 103 785 H 104 787 H 105 789 H 105 791 53 105 DAILY AVERAGE VALUES 793 53 1 O~ 795 53 105 ?97 53 lOS 799 53 104 801 53 105 803 53 105 DAILY AVERAGE VALUES ao5 S3 105 807 53 106 809 53 106 811 53 106 813 52 105 815 52 105 DAILY AVERAGE VALUES 817 52 106 819 51 105 821 51 105 823 51 106 825 50 105 827 50 105 DAILY AVERAGE VALUES 829 SO 104 831 49 104 833 49 104 835 49 104 837 49 103 839 49 103 DAILY AVERAGE VALUES FOUR VI LLAGES DATA FILE HUMP05.POD PAGE 14 08-AUG-83 START TIME 10/27/83 04:00 MV DEPTH INCHES -=.. • •.••• 10.8 10. 8 10.8 10.8 10.8 10.6 10 .8 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.4 10.4 10.5 10.4 10. 2 10.2 10.2 10.0 10. 0 10.2 10.0 9.8 9.8 9.8 '.8 '.8 9.8 -84- 21.6 21.6 21.6 21.6 21.6 21 .2 21.5 21.2 21.2 21.2 21.2 21.2 21.2 21.Z 21.2 21.2 21.2 21.2 20.8 20.8 21. 1 20.8 20.4 20.4 20.4 20.0 20.0 20.3 20.0 19.6 19.6 19.6 19.6 19.6 19.7 STAGE FEET • •••• l.U 1.28 1.28 1.28 1.28 1. 25 1. 27 1 .25 1.25 1. 25 1 .25 1. 25 1. 25 1. 25 1. 25 1. 25 1. 25 1. 25 1.21 1 . 21 1. 24 1.21 1.18 1.18 1.18 1 . 15 1.15 1. 17 1. 15 1. 11 1.11 1.11 1. 11 1.11 1.12 DISCHG cn • ••••• 11 11 11 11 11 10 11 10 10 10 10 10 10 10 10 10 10 10 9.4 9.4 9.9 9.4 8.6 8.6 1.6 'P.8 7.8 8.5 7.8 7.1 7. 1 7 1 7. 1 7. 1 7.2 TEMP DEG C ••••• 1.:S 1.5 2.0 2.5 2.5 2.5 2. 1 2.5 2.S 2.5 3.0 2.5 1.5 2.6 2.5 3.0 3.0 3.0 2.5 2.5 LI 3.0 2.5 Z.5 3.0 1.5 2.5 2.7 2.0 2.0 2.0 2.0 1.5 1.5 1.1 APA HYDRO-ELECTRIC FEASIBILITY STUDY FOUR VILLACES PAGE 15 PREPARED BY DRYDEN & LARUE DATA FILE HUMP05.POD 08-Aue-83 HUMPY CREEK NEAR LARSEN BAY START TIME 10/27/83 04: 00 DEPTH STAGE DISCHG TEMP DATE TIME BYTE RAW DATA MV INCHES FEET CFS DEe c ••• = •••• ••••• == •• •••••••• :a_ •• = ••••• •• = •• -== ••• ==-== 01/05/84 04:00 841 49 103 9.8 19.6 1. 11 7.1 1 . 5 01/05/84 08:00 843 48 103 9.6 19. Z 1.08 6.5 1.5 01/05/84 12:00 845 48 103 9.6 19.2 1. 08 6.:> 1 . S 01/05/84 16; 00 847 48 101 9.6 19.2 1. 08 6.5 0.5 01/05/84 20:00 849 48 101 9.6 19.2 1. 08 6.5 0.5 01/05/84 24:00 851 53 101 10.6 21 . Z 1.25 10 0.5 DAILY AVERAGE VALUES 9.8 19.6 1 . 11 7.2 1 . 0 01/06/84 04:00 853 55 101 11 .0 22.0 1 . 31 12 0.5 01/06184 08:00 855 58 101 11. 6 23.2 1 . 41 15 0.5 DAILY AVERACE VALUES 11 . 3 22.6 1.36 14 0.5 -85- APPENDIX C GAGING INSTRUMENT SPECIFICATIONS DATAPOD PRESSURE/TEMPERATURE PROBES HUMPY CREEK, LARSEN BAY ALASKA -86- , DATAPOD MODEL DP211SG TWO CHANNEL MILLIVOL T /MI LLiVOL T OR MILLIVOLT/TEMPERATURE RECORDER OPERATOR'S MANUAL The pressure/temperature probe as manufactured by Dryden & LaRue requires the use of a modified DP211 Omnidata recorder. This modification is a program change providing for different scan and record intervals as detailed in this manual. The program modification was done by Omnidata personnel at the request of Dryden & LaRue, 4060 "IB I Street, Suite 102, Anchorage, Alaska 99503, (907) 276-6965. Revision Number 0 ....................... ' ......................................................... .. OMNIDATA INTERNATIONAL P. o. Box 3489 Logan, Utah 84321 (801) 753-7760 March 1982 TABLE OF CONTENTS I GENERAL DESCRIPTION 1.1 1.2 Features ••••••••••••••••••••••••••••••••••••••• Specifications ••••••••••••••••••••••••••••••••• II OPERATING INSTRUCTIONS 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 Connecting the Sensors •••••••••••••••••••••••• The Recording Interval ••••••••••••••••••••••• Start-up Procedure ............................ . Installing the Data Storage Module •••••••••••• Sensor Test and Calibration ••••••••••••••••••• Preset Time Til Run ••••••••••••••••••••••••••• Data Storage Module Test •••••••••••••••••••••• Logging data •••••••••••••••••••••••••••••••••• Displaying Stored Data •••••••••••••••••••••••• Changing Data Storage Modules ••••••••••••••••• III MAINTENANCE 3.1 3.2 3.3 3.4 Preventive Maintenance ••••••••••••••••••••••••• Battery Replacement •••••••••••••••••••••••••••• Hardware warranty •••••••••••••••••••••••••••••• Limited software Warranty •••••••••••••••••••••• ILLUSTRATIONS 2-1- 2-2 2-3 2-4 2-5 2-6 2-7 Input Connector Positions •••••••••••••••••••••• Datapod Internal View •••••••••••••••••••••••••• Control Switch Settings •••••••••••••••••••••••• Initialization Sequence •••••••••••••••••••••••• Short Display Sequence ••••••••••••••••••••••••• Long Data Dump Sequence ••••••••••••••••••••••••• Model 217 Reader Output Format •••••••••••••••••• 1 2 3 3 3 4 4 5 5 6 6 7 8 8 8 9 10 11 12 13 14 15 15 SECTION 1 SECTION I GENERAL DESCRIPTION 1.1 Features The DATAPOD Model DP2ll is a miniature, battery-operated two channel millivolt/millivolt or a millivolt/temperature recorder (user selectable). It is totally sealed and operates over a broad temperature range with little or no protection from the environment. It is powered by 8 penlight cells, typically providing 6 months battery life. . The DATA POD Model DP211 will read the voltage on each channel, at user selectable intervals, the channel 1 reading will be recorded as a millivolt reading, the channel 2 reading will be either a ~ millivolt reading or temperature readin~. The user has the option of selecting which type of reading channel 2 will perform. Each set of readings will be recorded as an average or an instantaneous reading depending on the recording interval set by the user. Each set of readings is recorded on a UV erasable solid state DATA STORAGE MODULE CDSM). When the DSM is full, it is removed and replaced with a fresh one. The Model 217 Reader transmits the data from a DSM to a printer or computer for ease of data retrieval. The data stored in the DSM remains there until it is erased by exposure t6 an ultraviolet erasing lamp, after which the DSf.!. can be reused. 1 SECTION I 1.2 SPECIFICATIONS FUNCTION: GENERAL DESCRIPTION Two channel millivolt or millivolt/temperature recorder. '" 'l'YPE OF SENSORS: o to 40 millivolt output, Omnidata LI200 Radiometer, and TPIOV Temperature Probe (See figure 2-1). RECORDING FUNCTIONS: Records millivolts or millivolts and temperature. RECORDING INTERVALS: Use~ selects the recording interval. 1, 2, 5, 10,or 30 minutes or 1, 2, or 24 hour. PRESET TIME TIL RUN (logging of data): User may preset t.he time until DATAPOD starts to run. INPUT CONNECTOR: Two 3-pin environmentally sealed connectors. ,'. DATA STORAGE: Capacity: 1023 recordings. Medium: Non-volatile, interchangeable memory module. Retrieval: Via built-in display or Model 217 Reader. OPERATING CONTROLS AND DISPLAY: Display: 4 1/2 digit LCD with low battery indicator. Push Button: Controls data display and retrieval. CLOCK ACCURACY: +-3 minutes per month (-lOC to +60C) SELF TEST: Performs self test functions on power-up OPERATING ENVIRONMENT: -35 deg C to + 60 deg C, 0 to 100 , RB, dust and watertight POWER: 8 "AA" alkaline cells last, 6 months typically. SIZE & WEIGHT: 6.3" x 3.3 w x 2.3-, 1.2 lb. 2 SECTION II SECTION II OPERATING INSTRUCTIONS 2.1 ~onnecting the Sensors Two sealed rubber input connectors are located on the left hand side of the DATAPOD. Two CIO cables are furnished with the instrument. Figure 2-1 shows the proper hookup for both potentiometric and millivolt producing sensors. For potentiometric devices, be sure your output voltage is below 40 millivolts. The recorded number for over-ranged signals is unpredictable. Contact the factory if your sensor appears incom- patible. When plugging the connector into the DATAPOD, align the polarizing tabs on both connectors.· Because the plugs are flexible, it is possible to mate them improperly if they are forced. 2~2 The Recording Interval Locate the RECORDING INTERVAL CONTROL SWITCH shown in figure 2-2. The desired recording interval is set on the switch as shown in figure 2-3. Use your fingernail or a small tool to slide the small levers up or down. Set the switches before powering the system up (inserting the last battery). 2.3 Start-up Procedure The first time you experiment with the DATAPOD, it is best to leave the DSM out so that you can get a feel for the startup procedure without recording unwanted data in the DSM. If that happened, you would have to erase the DSM, for one hour, before trying it again. Leaving the DSM out will also give you a chance to observe the DSM test error messages. Insert 8 fresh ALKALINE penlight "AA" cells into the battery clips. DO NOT USE ORDINARY ZINC C~.RBON BATTERIES. They may leak and damage the DATAPOD, thus voiding the warranty. Locator patterns in the bottom of the clips indicate the proper battery polarity. Keep the battery terminals clean. The DATAPOD has no OFF-ON switch and will turn on immediately upon insertion of the last battery. After a few seconds, the display should cycle thru these messages "DATA" ·POD" "211" (for DATA POD Model 211>. If nothing happens after you have inserted the batteries, check to be sure they are properly oriented. A "lo-bat" or "<" indication from the display indicates the batteries are bad or that one of them has been installed backwards. 3 £l:.:C'l'lON 11 The "211" will remain displayed for 2 seconds. A series of messages and numbers will now be displayed at approximately 2 second intervals. Refer to Figure 2-4 for a sequential listing of the messages and their meanings. Following the message -DATA POD 211-, the recording interval that you set on the control switche will be displayed so you can verify it. First REC will display for 2 seconds then the interval XXXX (in m inut es). Because the 7-segment LCD display was not designed to display alphabetic characters, you may need a touch of imagination to read some characters in some of the messages. 2.4 Installing the Data Storage Module (DSM) Remove the cover of the DATAPOD by loosening the 4 captive slotted screws located at its outer corners. Remove a D5M from its case and insert it into the socket labeled DATA STORAGE MODULE at the top of figure 2-2. The adjacent socket, labelled PROGR~M STORAGE contains the program memory and must not be removed. . The notch at one end of the DSM should be oriented to the left to match the drawing. Polarizing blopks are mounted on both the socket and the DSM to help prevent improper insertion. Carefully plug the DSM into its socket to avoid bending the pins or the contacts on the socket. In order to retrieve the stored data using the Model 217 reader, or by using the display dump mode, it is necessary to know the starting month, day, hour, and minute. If you have more than one DATAPOD in the field it is also necessary to know' which station the data came from. It is best to record this information on a stick-on label and attach it directly to the DSM. It is advisable to also write this information in a log book. No initial time data nor station 10 is stored in the D5M. If you mix up the DSM's from several stations or lose the initial time data, it will not be much fun figuring out which is which. 2.5 Sensor ChecKout and Calibration After the DP211 has displayed the recording interval it will display CHNI (Channell) followed by a number MXX.X, this number is the millivolt reading from channell. These two displays will then repeat, allowing you to check the sensor and the DATAPOD. You will have to press the EXTERNAL button to exit the cycle. The cycle will then repeat for channel 2, displaying millivolts (MXX.X) or degrees C (CXX.X) depending on the option you have selected (see figure 2-3), You will have to press the EXTERNAL button to exit this cycle also. 4 SECTION II OPEHJ\ TING INSTRUCT IONS 2.6 Preset Time Til Run (logging of data) The display will now show "PRE" "SET" "PUSH". You now must decide if you want to set the time in minutes until the DATAPOD starts to run, or if you want the DATAPOD to start running as soon as the DSM tests are over. Normally, you will wish to start logging data at a known time, but you will want to setup the DATA POD at some time before. The Preset mode allows you to synchronize the DATAPOD to start logging data at a known time. If you push just the EXTERNAL button then the DATAPOD will skip the preset mode, and start the DSM tests immediately. If you push both the EXTERNAL and INTERNAL buttons simultaneously then the DATAPOD will allow you to preset the time in minutes til run. Once in the preset mode the DATAPOD will display "MIN" "LEFT" -TIL" IIRUN" and then the display will show how many minutes there are until the DATA POD begins to record data (RUN). To preset the time, just push and hold the EXTERNAL button to INCREMENT the time, the longer that you hold the button the . faster the time will increment. If you push and hold the INTERNAL button then the time will DECREME~IT: the longer that you hold the button the faster the time will decrement. When the preset has reached the time in minutes that-you desire, push both the EXTERNAL and I~ITERNAL buttons simultaneously. This will cause the DATA POD to store the preset time and automatically start the DSH tests. The maximum preset is 19999 minutes, you cannot preset a negative number. 2.7 Data storage Module Test The DSM is a uv erasable memory into which the data is stored or 'burned'. The term 'burned' is a holdover f rom fusible-link PROM technology when tiny fuses in the memory were actually burned to store data. The data is not really burned into the DSM, but the term remains useful to indicate data storage in a non-volatile memory. The DSM is reusable and can be erased by exposing it to a surgical grade ultraviolet erasing lamp for one hour. The DSM must be erased before it c~ be used in the DATAPOD. The DATAPOD will tell you when it is going to start the DSM tests by asking you to plug in the DSM and push the button, IIPLUG" "IN" 8DSM II ·PUSH". Once you have plugged in the DSM, push the EXTERNAL button and the tests will start. nDSH II -TEST-"ERA" will display to tell you that the tests have begun. If your hands are wet and you touch the DSM pins, it is possible that the DATl.,POD will not continue with the DSM tests. If this happens, leave the DSX in place, remove a battery and wait until the display fades completely, then insert the battery and proceed to this point again. 5 SECTION II The RERA" display appears at the start of the ERASE test and remains displayed for 10 seconds while the DSM is being tested. If the DSM is erased, the "PASS" prompt will be displayed. If the DSM is not erased, the "FAIL" prompt appears, followed by the number of unerased storage locations. If only a few loca- tions are unerased, you could use the DSM in a pinch, with the number of unerased locations being the number of storage errors you will obtain. Normally, you should replace the DSM with an erased one if this test fails. The RBURN" test starts automatically after the erase test ends. The BURN LED on the right side of the front panel will flash while the previously selected storage interval is being "burned" into the first location in the DSM. If data can be stored in the DSM, the "PASS" prompt will display. If data cannot be stored, the "FAIL" prompt will appear. Try a new DSM if this test fails. If the erase test passes but the burn test fails, the DP211 may have a problem. contact the factory. At the end of the DSM tests, the display will show "MIN" "LEFT· "TIL" "RUN" and the number of minutes until data logging starts will be displayed. The number will decrement once each minute .until 0000 is reached, at which time'data logging will . start, according to the control switch setting that has been selected (see figure 2-3). 2.8 Logging Data While "RUN" is displayed, the DP211 is keeping time and scanning the sensor according to the scan interval set by the user on the control switch. The "burn" light will flash each time data is stored. Each data point is recorded as· a one byte (8 bit) number and has a range from 0 to 255. The millivolt values are recorded as 5 times the actual millivolt reading. For example, 30.2 millivolts is recorded in the DSM as 151. The temperature values pre offset by 100 and multiplied by 2 before recording. For example, the 24.5 degrees C is recorded in the DSH as 149. 2.9 Displaying Stored Data There are two modes of displaying stored data, a short and a long mode. Figure 2-5 shows the short display sequence. The short display is activated by holding the button on the side of the case down until the display shows ·DLY" (delay). 'rhe figure 2-5 is self explanatory. A second method of data retrieval has been included so that you can recall each of the stored data values to the display_ We have named it the Long Dump_ Normally the Model 217 reader woufd be 6 SECTION II OPERATING INSTRUCTIONS used to read the data back from the DSM to a printer or computer. However, there may be occasions when you wish to check the recorded data values in the field. To activate the long data dump mode, first press the external button to initiate a short display sequence. Continue to hold the button while the "DLY" prompt displays. After about 2 seconds "LONG" "DUMP" will display_ Release the button you are now in the long dump mode. Figure 2-6 is an example of a typical long dump. The data will be dumped out to the display on a last in, first out basis (LIFO), that is, the last piece of information burned will be the first to be displayed in the long dump etc. The word "DATA" will display and then a number, this number is the number of the last burn. After this number ftCHNl" will display and then the millivolt reading. Then ·CHN2" will display and then either the millivolt reading or degrees C, depending on which option the user has selected. The display will continue to cycle until either all the values have been displayed, or until you hold the external button down, . until "END" "LONG" "DUMP" is displayed.' This indicates that the 'long dump is complete or tha t you aborted., After" END" • LONG" "DUMP" has been displayed, the DATAPOD will resume its normal logging of data and the display will show "RUN". 2.10 Changing Data Storage Modules Before changing the DSM, review the data as described above to be sure the DATAPOD is operating normally. It should be sufficient to use the short display sequence to check for proper instantaneous readings and storage errors. If these are wrong, do not insert a new DSM without determining the problem. If the data looks good, remove one of the batteries, remove the full DSM, insert a new DSM, replace the battery, and restart the unit •. Make sure that a station ID tag is securely fixed to the DSM so that it will not get mixed up with others. Be sure to label the new DSM with the starting month, day, hour, and minute. Refer to the Model 217 reader manual when reading the Data Storage Module into your printer or computer. Figure 2-7 illustrates the reader output for the long dump data shown in figure 2-6. The DSM can be erased by exposing it to a surgical grade ultra- violet lamp for one hour at a distance of one inch (e.g. the Model UVS-IIE supplied by Omnidata). The Model 217 reader includes a test function that verifies that the DSH is fully erased. 7 3.1 Preventive Maintenance SECTION III MAINTENANCE No periodic adjustments are required. If your data looks good, the DATAPOD is working. Check for moisture condensed inside the DATAPOD case when changing DSM's. If there is any, carefully dry the inside and inspect the case for damage and leaks. Check the gasket in the lid for breaks or foreign matter. Inspect the battery clips for any sign of corrosion and clean them carefully if necessary. Do not use solvents of any kind. They will destroy the case by chemical reaction. CAUTION: Do not leave the instrument in direct sunlight. '. 3.2 Battery Replacement ******** USE ONLY ALKALINE BATTERIES ******** : . . . . . . . • • • • • • • REGULAR BATTERIES OFTEN LEAK AND CORRODE . . . . . . . . • • • • • • • • The batteries will typically last about 6 months. When the -10 bat-or -<-symbol on the display appears, there is 30% life left in the batteries. If this happens sooner than about 2 months, there may be a weak component on the circuit board. Measure the current drain in series with a battery using a VOM or DM M. Nor mal ope ra ting cur rent is under 100 mic roamps. I f the current drain is normal, the batteries Eay have been old when purchased. Battery life is a function of the recording interval set by'the user on the control switch. 3.3 Hardware warranty The warranty covers products against defects in materials or workmanship for a period of 6 months after the date of shipment. Omnidata International, Inc. is not liable for damages resulting from an instrument failure. This warrant applies only to the products manufactured by Omnidata. Before returning any DATAPOD or accessory for repair, please contact Omnidata Customer Service Department for a Returned Materials Authorization Number. (RMA t ) This will facilitate the prompt handling of your equipment. 8 " r J SECTION III MAINTENANCE , 3.4 Limited Software Warranty Omnidata International, Inc. represents and warrants to customer that Omnidata International, Inc. has developed all software systems with reasonable diligence and skill. Upon receipt of written notice from customer outlining and describing any apparent program error within one year of shipment, Omnidata International, Inc. agrees to correct such program errors with reasonable diligence. OMNIDATA INTERNATIONAL, INC. MAKES NO OTHER REPRESENTATION OR WARRANTY, EXPRESS OR IMPLIED, WITH REGARD TO THE SYSTEM. OMNIDATA INTERNATIONAL,· INC. MAKES NO REPRESENTATION OR WARRANTY WITH REGARD TO THE FITNESS OF THE SYSTEM FOR ANY PARTICULAR PURPOSE OR USE BY CUSTo:.,ER. OMNIDATA INTERNATIONAL, INC. SHALL NOT BE LIABLE TO CUSTOMER OR ANY THIRD PARTY FOR ANY SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO, LOSS OF REVENUES OR LOSS OF PROFITS, OR INJURY OR DAMAGE TO THE PROPERTY OF BUSINESS OF CUSTOMER OR ITS AGENTS OR EMPLOYEES ARISING OUT OF, OR IN ANY WAY RELATED TO THE USE OR IMPLEMENTATION OF THE SYSTEM. Omnida·ta Internationc:il, Inc. shall be under no obligation to update or modify the system except as herein noted to correct program errors. Further, customer agrees that the representation and warranty in the first sentence of this section shall be immediately null and void in the event of any modification, alteration or change in or to the system effected by or on behalf of customer, except for any change made by Omnidata International Inc. or under direct supervision of Omnidata International, Inc. 9 ..., -J. \0 c::: .., t'O N I --' ..... :::I '"'0 c::: ....,. -0 ("") 0 ::I :::I ro n ....,. 0 .., '"'0 0 II' -J • ....,. -J, 0 ::s II' CHN I OMN I DATA C 10 .-C=A=B=L E====::::C:JI/JI ~ 9 S. '-LJ o TO 40 t.1V SE NSOR OR ~DA T A TP/OV T EMP PR~BhQ..E_(_S_E_E_P_A_G_E-,-....I) cEf ~ I POTENTIOMETER [~I L LlVOLT S£N~R OR 4-2100K MAX SENS RESISTANCE -0-40MV MAX ~ . :, 3~Z . ,secKET ON DATAPOO CASE ~ PIN COLOR SIGNAL I GREEN 2V EXCITATION , 2 RED 511 GNAL I NPiJT I :, BLACK COMMON DP21' TWJ CHANNEL MV MVor MV TEMP RECORDER " Inside of Front Panel Inside of Case 0 1 0 Data 0 0 0 r Storage 0 Module Control Switch l Program 1 1234 1 ( Stor-age lUI "Mil Alkalines Only J+L J+L: : ~. Microcomputer . + + I I I i + + Internal Button D 0 0 ~+J -L.r I o 0 0 0 CAUTION: Use only alkaline penlight cells. Regular penlight cells may leak and damage this instrument, voiding the warranty_ , Figure 2-2 Datapod Internal View 11 Externa Button SPEC1AL Figure 2-3 Recording Interval Control Swtich Settings Switch Recording Scan Type Service Setting Interval Interval Reading Interval [ill • • • 15 min 15 min 1nst 10 days [IT'J • • • 30 min 15 min ave 20 days ~ 1 hour • • 60 min 60 min ave 40 days ~ 2 hours I • 120 min 60 min ave 80 days ~ 4 hours • I 240 min 60 min ave 160 days ~ 6 hours I • 360 min 60 min ave 240 days ~ 12 hours 720 min 60 min ave battery life ~ daily 1440 min 60 min ave battery 1 He With Switch 1 in the lower positio~ Channel 2 records temperatures. With Switch 1 in the upper position Channel 2 records millivolts. 000 ~ Program ~ 0 n I Storage ~ U ------_---1 n n D D Control Switch Orientation Diagram 12 DISPltAY DATA POD 211 REC XXXX CHNI MXX.X CHN2 MXX.X or CXX.X PRE SET PUSH MIN LEFT TIL RUN XXXX PLUG IN DSM PUSH DSM TEST ERA PASS FAIL XXXX lLLU~iKNl' IOhS Figure 2-4 Initialization Sequence COMMENTS Place batteries in DATAPOD to power up the system. Data Pod 211 will display. The recording interval is displayed in minutes to check the setting of the control switch. Sensor test channell. Data is read from the sensor and displayed. Push EXTERNAL button ,to exit. ' Sensor test channel 2. Data is read from the sensor and displayed. 'Push EXTERNAL button to exit. You now have two options: RUN or PRESET. To Run and begin normal data logging, press' the external button. To PRESET the time in minutes til run, press the internal and external buttons simultaneously. PRESET TIL RUN Set minutes til run (logging of data). Pushexternalbutton to skippreset, Default= o. Push external and internal buttons simultaneously to enter preset mode. If in preset mode the display shows minutes left til run. EXTERNAL button to increment. INTERNAL button to decrement. Minutes increment or decrement. Push both buttons simultaneously to exit preset. RUN Prompt tells user to plug in the DSM. And then push the external button. The beginning of the DSM tests. Data storage Module Erase Test (lasts 10 seconds). Pass the test, DSM is erased. Fail the test, DSM is not fully erased. If fail, display shows number of data points not erased. 13 ILLUSTRATIONS BURN Data Storage Module Burn Test (LED flashes). PASS Pass test, Data can be stored. FAIL Fail test, Data can not be stored. MIN LEFT TIL RUN XXXX RUN If either test fails, remove a battery, replace the DSM with a fresh one, and start again. Minutes left til run. Counts down the minutes til run. The DP2l1 DATAPOD is running and logging data. Figure 2-5 Short Display Sequence The following sequence of messages will appear if you press the "button on the case while the -RUN" message is displayed. DISPLAY RUN D~ CHNI MXX.X CHN2 MXX.X or CXX.X ERR XXXX MIN LEFT XXXX DSM USED XXXX RUN COMMENTS Normal display while running. Press the button on the case. Delay while readings are taken. Current channel 1 data. Millivolt reading. Current channel 2 data. Millivolt reading or temperature in degrees C to nearest .5 degree. Number of errors if any. Minutes left til next reading. Data storage module space used so far. There are 2047 spaces available when empty. Normal display while running. 14 lLLus'rRATlONS Figure 2-6 Long Data Dump Sequence Example The following sequence is initiated by pressing the button on the case and holding through the "DLY" until "LONG" "DUMP" appears. DISPLAY LONG DUMP DATA XXXX CHN1 MXX.X CHN2 MXX.X CXX.X END LONG DUMP RUN or COMMENTS Begin a long data dump. Displays the number of the last burn. Displays the millivolt reading stored. Displays the millivolt or temperature reading stored. The display will continue cycling thru this sequence until the end of the long dump or you abort the long dump by pressing the EXTERNAL button. End of the long dump. Normal display while running If the DATAPOD needs to scan the channels and burn some data during a long dump, it will temporarily interrupt the long dump then resume the long dump where it left off when the scan is over Figure 2-8 Model 217 Reader Output Format To use the DP2ll with the Model 217 reader, set the reader up as follows: Use CTL N and set: FMT = 04 for Julian days or 05 for mo-da-yr. BYT = 1 NCH = 2 Use CTL T and set: recording inte rval in minutes. Use CTL B and set: starting date and time. Use CTL Q to obtain a printout on a terminal like this: 05 16 82 161 149 05 16 82 172 150 15 ILLUSTRATIONS The first series of three digits is the month, day, and year. If Julian days were set, month and day would be replaced by the day of the year. The number on the left is channell, the number on the right is channel 2. The temperature values are recorded as 2 times the actual temperature reading plus 100. For example 30.5 degrees is recorded in the DSM as 161. To convert the number from the DSM to degrees C use the following formula. (number stored in DSM -100) I 2 The millivolt values are recorded as 5 times the actual millivolt reading. For example 19.4 millivolts would be recorded as 97 in the DSM. To convert the number from th'e DSM into voltage use the following formula. number stored in DSM I 5 USER NOTES 16 · . PRESSURE PROBE OPERATORS MANUAL , A Companion Device to the DP211 Datapod Recorder DRYDEN & LaRUE 4060 "B P Street, Suite 102 Anchorage l Alaska 99503 (907) 276-6965 3/19/82 k . DRYDEN & LaRUE PRESSURE PROBE DESCRIPTION The pressure probe has been designed as a companion device to the Omni- data DP211 Datapod recorder. The probe consists of a 0-6 psi semi- conductor strain gage transducer attached to an interface containing a power supply and the interface electronics. An external push button and an LED indicator provide for field battery test. SPECIFICATIONS OPERATING TEMPERATURE RANGE LINEARITY I REPEAT AB IlITY RESOLUTION POWER SUPPLY BATTERY LIFE In typical usage with the DP211 recorder the interface is calibrated to provide 0.5 mV per inch of water. This results in a range of 0-80 inches of water. The interface and transducer can produce up to 100 mV for a full scale pressure of 6 PSIG. 2% over OOC to 50°C. Expected error will be zero drift. Should be user calibrated -35°C to O°C In typical usage, recorder output resolved to 0.2 mV representing 0.4 inches of water. 8 "AA" alkaline cells Battery life is dependent upon temperature and usage since the interface circuit turns on at the request of the recorder. Note, usage is dependent on scan rate Scan Rate 60 Min. Scan Rate 15 Min. Scan Rate 5 Min. not record interval. The following table assumes use of new Eveready "Energizer" E9l batteries. Temeerature 21°e {700F~ oDe (32 °F 2 -1S De{OOF} -29°e( -2o o F2 16,000 hrs. 12,800 hrs. 8,000 hrs. 4,800 hrs. 4,000 hrs. 4,000 hrs. 3,200 hrs. 1,200 hrs. 1,333 hrs. ',066 hrs. 666 hrs. 400 hrs. One year is 8,760 hours. One month is approximately 720 hours. USAGE A 3-prong connector Is provided for connection to a DP211 recorder. See the DP211 manual for connection diagram. The external push button on the interface is used to test the batteries. New batteries wou Id provide 12.0 volts. The indicator will not light if the battery supply has fallen below 10.4 volts. The interface circuitry will not function below 9.7 volts. Thus there ;s still 20~-30% of the life left after the indicator fails to light.· PRECAUTIONS . The strain gage transducer is a· shock sensitive device undamaged at SOG. It should be handled with care and wrapped in a one inch foam blanket for shipping. The diaphragm itself should not be touched. An impact pres- sure of 12 psi will damage the transducer. The batteries should only be alkaline type cells. Eveready "Energizer" E91 cells are strongly recommended. {For low temperature operation, these batteries can be purchased in gross quantities. The gross quantity outer box will be marked with a number near 300. This Is a manufac· - 2 turers date code where 300 corresponds to Jan. 81, 301 Is Feb. 81 etc. Batteries older than one year would not provide quoted service life, deteriorating by 5-10% per year.) An atmospheric reference Is delivered to the transducer through a teflon capillary tube. This capillary tube is terminated In a mounting well of the interface box near the push button. Submersion of the interface box can result in a small water plug in the capillary tube. Such.8 plug can cause hysteresis and unpredictable low temperature operation. The interface box can not be placed in a sealed enclosure. -3 • # , DRYDEN & LaRUE PRESSURE TRANSDUCER INTERFACE CIRCUIT CALIBRATION AND TEST POINTS 0 @ E1 4 ) '" PI . .~,. ..:--. 40 +0 • -a ... EJ . .. "0 .D 4 f"~ I ~:. "ttso o 888H o ADJUSTMENTS ,. Applied power supply of 10.4 V at Test Points + and -. Adjust trim pot Pl to obtain borderline LED operation with switch depres5ed. Z. With 12 V supply across test point + and -, and one milliamp current across test points BE to GC (common), adjust trim pot P2 to obtain 5.00 V at R with respect to main power supply (-). 3. With 12 V supply and one milliamp current as above and no pressure on the transducer, adjust trim pot P6 to obtain 0.0 millivolts at RS with respect to GC. 4. Trim pots P3 and P5 may not be on the board. If they are, turn P3 completely clockwise and P4 completely counterclockwise. (These two may be used to adjust a measurement window.) 5. With same power supplies as adjustment 2, adjust P4 to provide desired scaring. The signal as 5een by the recorder is available at test point RS with respect to GC. Normally a known pressure of 80 inches of water is applied to the transducer and P4 is adjusted to provIde a 40.0 mV output. - 4 - • PHYSICAL TYPE PSIG -PSIA available. Units 100 PSI and above have cases sealed from the surrounding atmosphere. providing maximum reliability In humid or corrosive environment (psis). Ranges below 100 PSI are vented to the atmosphere and read gage pressure independently of barometric pressure changes (psig). RANGES CHS, 15,25,50, 100,200,500, 1000,2000,3000,5000,10,000, 15,000 and 20,000 OVERLOAD 2 times rated pressure without damage; 5 times rated pressure without bursting CASE MATERIAL 316L stainless steel for ranges 50 PSI and under 15-5PH stainless steel for ranges 100 PSI and over SHOCK & Undamaged by 50 G's. Meets VIBRATION MIL-STO-a10 B, Fig. 514-4, RESISTANCE curve AP. time scnedule Ii ELECTRICAL SIGNAL OUTPUT 100 millivolts at rafed pressure, :t 1 %, open circuit EXCITATION 5 Vdc ()( ac nns recoin- .VOLTAGE mended; 6 V maximum ZERO BALANCE Within :t 5 mV at 70 of (21.1°C) SENSITIVITY 20mVN BRIDGE Input, 150 ohms :t 50 ohms RESiSTANCE Output, 1 15 ohms :t 25 ohms EL[;CTP.ICAL 4 conductor shielded cable, CONNECTION 3 feet (O.9m) lone. See OPTIONS PERFORMANCE ACCURACY Within 1 % from best fit straight line, Including non·linearity, repeatability and hysteresis. See OPTIONS RESOLUTION Infinite OPERATING -65° to 200°F (-53.goC to 93.3°C) TEMPERATURE Can be extended to 300°F (14g·C) RANGE See OPTIONS General The AB pressure transducer Is a rugged, accurate and small pressure measuring Instrument dC~lgned tor industnal service. Its construction features Simplicity. ruggodness, land ab50nce of movmg parts. Semiconductor strmn gages mounte<! on a unique sensor ml'asure the doiloctlon 01 the dlaphraQm at it!. center. The strain gaocs are wir::~d mto a Model AB Pressure Transducer Instruction Sheet COMPENSATED 3Q°F to 130°F(-1.1°C to 54."'OC) TEMPERATURE standard RANGE THERMAL EFFECT Less than 5% of full scale over com- ON ZERO pensated range. See OPTIONS THERMAL EFFECT Less than 2% of reading over ON SENSITIVITY compensated range. See OPTiONS OPTIONS Various optional operating characteristiCS and mechanical features can be incorporated ·in standard Moder AB transducers. at additional cost, for applications which require improved periormance. These are designated by a numerical code: Option 1 Absolute pressure version. Available in 15, 25 and 50 PSIA Option 2 Improved zero and span temperature compensa· tion to 1%'100°F (55.5-C) and improved accuracy (combined non·linearity, hysteresis and repeatability) from 1 % to 0.5% Option 3 Barbed fitting for attaching protective hose around cable Option" Install longer cable by splicing to existing 3 ft. cable Option 5 Install longer continuous cable Option 6 Install Bendix PTIH·1()..6P electrical connector with an extended case Pin Code: A + Excitation B + Signal C -Sigflal D -Excitation E and F not used Option 7 Extended Operating Ternperature Range to 300'F (148.9·C.) 6 and 15 psi excluded. Includes Option 6. • -== = . Wheatstone Bridge which Is balanced at no-load conditions. Pressure on the'diaphragm causes it to deliect. ~tralninQ the gages, and changtnQ ttleir electrical resistance. When an 6xcltallon voltage Is arplied across two corners 01 the bridge, a signal voltage proportlOoal to pressure Is producod across the other two corners. The high sensitivity 01 the