HomeMy WebLinkAboutBradley Lake Final Supporting Design Report Vol 9 final 1988A~skaPowerAu~orny FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT BRADLEY LAKE HYDROELECTRIC PROJECT FEDERAL ENERGY REGULATORY COMMISSION PROJECT NO. P-8221-000 VOLUME 9 CALCULATIONS Prepared By STONE & WEBSTER ENGINEERING CORPORATION MARCH 1988 TABLE OF CONTENTS TABLE OF CONTENTS FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 1 -REPORT VOLUME 2 -DESIGN CRITERIA VOLUME 3 -DAM AND SPILLWAY STABILITY ANALYSIS VOLUME 4 -CALCULATIONS VOLUME 5 -CALCULATIONS VOLUME 6 -CALCULATIONS VOLUME 7 -CALCULATIONS VOLUME 8 -CALCULATIONS VOLUME 9 -CALCULATIONS 0216R-4460R/CG i TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 1 REPORT 1.0 INTRODUCTION 2.0 DESIGN AND GENERAL TECHNICAL DATA 2.1 DESIGN 2.2 DESIGN LOADS 2.3 STABILITY CRITERIA 2.4 MATERIAL PROPERTIES 2.5 GENERAL TECHNICAL DATA 3.0 SUITABILITY ASSESSMENT 3.1 SPECIFIC ASSESSMENTS 4.0 GEOTECHNICAL INVESTIGATIONS 4.1 CHRONOLOGY OF INVESTIGATIONS 4.2 BORING LOGS, GEOLOGICAL REPORTS AND LABORATORY TEST RESULTS 5.0 BORROW AREAS AND QUARRY SITES 5. 1 BORROW AND QUARRY AREAS 5. 2 OTHER MATERIAL SOURCES 6.0 STABILITY AND STRESS ANALYSIS 6.1 GENERAL 6.2 DIVERSION TUNNEL INCLUDING INTAKE STRUCTURE 6. 3 MAIN DAM 6.4 SPILLWAY 6.5 POWER TUNNEL AND PENSTOCKS 6.6 POWERHOUSE/SUBSTATION EXCAVATION, COFFERDAM AND TAILRACE CHANNEL 6.7 POWERHOUSE 6.8 REFERENCES 7.0 BASIS FOR SEISMIC LOADING 7.1 GENERAL 7.2 SEISMOTECTONIC SETTING 7.3 SEISMIC DESIGN 0216R-4460R/CG ii TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 1 REPORT 8.0 SPILLWAY DESIGN FLOOD BASIS 8.1 STUDY METHODOLOGY 8.2 WATERSHED MODEL CALIBRATION 8.3 PROBABLE MAXIMUM FLOOD 8.4 SPILLWAY DESIGN FLOOD 8.5 MODEL TEST 9.0 BOARD OF CONSULTANTS 9.1 INDEPENDENT BOARD OF CONSULTANTS 9.2 FERC BOARD OF CONSULTANTS APPENDIX A Plates Exhibit F 1 2 3 4 5 6 1 8 9 10 13 14 15 16 17 18 19 20 Figures F.6.2-5 F.6.2-6 DRAWINGS Title General Plan General Arrangement -Dam, Spillway and Flow Structures Concrete Faced Rockfill Dam -Sections and Details Spillway -Plan, Elevations and Sections Power Conduit Profile and Details Intake Channel and Power Tunnel Gate Shaft -Sections and Details Civil Construction Excavation at Powerhouse -Plan Civil Construction Excavation at Powerhouse -Elevations 90 MW Pelton Powerhouse Construction Diversion -Sections and Details Main Dam Diversion -Channel Improvements General Arrangement -Permanent Camp and Powerhouse Barge Dock Powerhouse Substation and Bradley Junction Main One Line Diagram Martin River Borrow Area Waterfowl Nesting Area Powerhouse Access Roads Mean Horizontal Response Spectrum Design Accelerogram 0216R-4460R/CG iii TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 1 REPORT APPENDIX B ATTACHMENTS B.l Construction Schedule Contract Dates 8.2 Meetings of the Independent Board of Consultants Meeting No. 1 May 12 and 13, 1983 Meeting No. 2 July 11 to 15, 1983 Meeting No. 3 September 25 to 27, 1984 Meeting No. 4 November 4 and 5, 1985 with response of November 25, 1985 Meeting No. 5 January 28, 1986 Meeting No. 6 May 6 to 8, 1986 with response dated May 21, 1986 Meeting No. 7 August 12 to 14, 1986 with response dated October 20, 1986 Meeting No. 8 December 8 to 10, 1986 Site Visit by Mr. A. Merritt on December 11, 1986 Meeting No. 9 May 5 to 7, 1987 Meeting No. 10 December 17 and 18, 1987 8.3 Meetings of the FERC Board of Consultants Meeting No. 1 Meeting No. 2 March 6 and 7, 1986 May 28 and 29, 1986 with response dated July 11, 1986 Hydraulic Model Test of Spillway July 9, 1986 Meeting No. 3 August 18 to 20, 1986 with response dated October 28, 1986 Meeting No. 4 Meeting No. 5 Meeting No. 6 0216R-4460R/CG Hydraulic Model Test Spillway and Diversion Tunnel August 29 and September 25, 1986 January 27, 1987 with response dated January 29, 1987 May 26 to 28, 1987 with response December 7 and 8, 1987 with response iv TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 2 DESIGN CRITERIA 1.0 Civil Design Criteria 2.0 Geotechnical Design Criteria 3.0 Structural Design Criteria Part A General Design Criteria Part B Special Requirements for Major Structures Section 1. Section 2. Section 3. Section 4. Section 5. Section 7. Main Dam Diversion Main Dam Spillway Power Tunnel Lining, Intake and Gate Shaft Steel Liner and Penstock Tailrace 4.0 Hydraulic Design Criteria 1. Main Dam Diversion 2. Tailrace 3. Hydraulic Turbines, Governors and Spherical Valves 4. Spillway 5. Power Intake, Tunnel and Penstock 5.0 Architectural Design Criteria 0216R-4460/CG v TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 3 DAM AND SPILLWAY STABILITY ANALYSIS DAM STABILITY REPORT Section Section Title 1.0 INTRODUCTION 1.1 PURPOSE 1.2 SCOPE 1.3 DAM SAFETY CRITERIA 2.0 DESCRIPTION OF PROJECT FEATURES 2.1 GENERAL 2.2 MAIN DAM 2.3 UPSTREAM COFFERDAM 3.0 DESIGN EARTHQUAKE REGIME 3.1 SEISMOTECTONIC SETTING 3.2 DESIGN RESPONSE SPECTRA 3.3 ACCELEROGRAM DEVELOPMENT 4.0 ALTERNATIVE METHODS OF ANALYSIS 4.1 GENERAL STABILITY CRITERIA 4.2 PSEUDOSTATIC METHOD 4.3 SARMA/NEWMARK METHOD 4.4 FINITE ELEMENT METHOD 4.5 SELECTION OF SARMA METHOD 5.0 SARMA ANALYSIS METHODOLOGY 5.1 MATERIALS PROPERTIES AND EARTHQUAKE SELECTION 5.2 LEASE II ANALYSIS 5.2.1 Static Analysis 5.2.2 Critical Circles and Accelerations 5.3 SARMA ANALYSIS 5.3.1 Data Requirements 5.3.2 Processing 5.3.3 Analytical Output 5.3.4 Significance of Results 6.0 BRADLEY LAKE EMBANKMENT ANALYSES 6.1 EARTHQUAKE RECORDS 6.2 INPUT PARAMETERS 6.3 DESIGN CASES 6.4 LEASE II ANALYSES 6.5 SARMA ANALYSES 6.6 INTERPRETATION OF RESULTS 0216R-4460R/CG vi TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 3 DAM AND SPILLWAY STABILITY ANALYSIS Section Section Title 7.0 8.0 6.7 6.7.1 6.7.2 6.7.3 6.7.4 6.7.5 6.7.6 6.7.7 6.7.8 6.8 7.1 7.2 7.3 7.4 SPECIAL STUDIES Megathrust (a = .55g) DBE (ah .375g) Influence of Downstream Berm Failed Concrete Face Varying Embankment Height Planar Slip Surfaces La Union Accelerogram Parametric Analyses COFFERDAM CONCLUSION CRITICAL CASES SUMMARY OF CRITICAL FAILURE SURFACES PREDICTED DISPLACEMENTS RESPONSE TO VARIOUS EVENTS BIBLIOGRAPHY LIST OF FIGURES Figure Title 1 Project Location Map 2 Main Dam Area -General Arrangment 3 Main Dam Sections 4 (Not Used) 5 MCE Response Spectra -Mean and Chosen 6 Rockfill Friction Angles 7 Intermediate av/ah Ratio 8 Selected Sliding Surfaces -Main Dam 9 Critical Acceleration Plots 10 Permanent Deformation Plots 11 MCE Response/Displacement Plots 12 Megathrust Response/Displacement Plots 13 DBE Response/Displacement Plots 14 Flow Through Dam Without Face 15 Dam Height vs. Acceleration and Displacement 16 Wedge Stability: Sloped Sliding Planes 17 Wedge Stability: Horizontal Sliding Planes 18 La Union Response/Displacement Plots 19 Response Spectrum -La Union E-W Record 20 Response Spectrum -Taft Record 21 Arias Intensity 22 Taft Response/Displacement Plot 0216R-4460R/CG Vll TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 3 DAM AND SPILLWAY STABILITY ANALYSIS SPILLWAY STABILITY REPORT Section Section Title 1.0 INTRODUCTION 1.1 PURPOSE 1.2 SCOPE 1.3 SPILLWAY SAFETY CRITERIA 2.0 DESCRIPTION OF PROJECT FEATURES 2.1 GENERAL 2.2 OGEE SECTION 2.3 NON-OVERFLOW SECTIONS 2.4 GEOLOGIC CONDITIONS 3.0 DESIGN EARTHQUAKE REGIME 3.1 SEISMOTECTONIC SETTING 3.2 DESIGN RESPONSE SPECTRA 3.3 ACCELEROGRAM DEVELOPMENT 4.0 STABILITY CRITERIA 4.1 GENERAL 4.2 LOADS 4.2.1 Deadweight 4.2.2 Ice 4.2.3 Hydrostatic 4.2.4 Earthquake 4.2.5 Wind 4.2.6 Uplift 4.2.7 Temperature 4.3 LOADING CONDITIONS 4.4 ACCEPTANCE CRITERIA 4.4.1 Stability Requirements 4.4.2 Minimum Allowable Stress 4.4.3 Shear-Friction Factor of Safety 5.0 METHODS OF ANALYSIS 5.1 STATIC METHOD 5.2 FINITE ELEMENT METHOD 5.3 SARMA METHOD 6.0 STATIC ANALYSIS 6.1 STABILITY ANALYSIS 6.2 RESULTS 7.0 FINITE ELEMENT ANALYSIS 7.1 STRESS ANALYSIS 7.2 RESULTS 0216R-4460R/CG viii Section 8.0 8.1 8.2 9.0 9.1 9.2 10.0 Figure 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 0216R-4460R/CG TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 3 DAM AND SPILLWAY STABILITY ANALYSIS Section Title SARMA ANALYSIS STABILITY ANALYSIS RESULTS CONCLUSIONS CRITICAL CASES SUMMARY OF STABILITY CONDITIONS BIBLIOGRAPHY LIST OF FIGURES Title Project Layout Map General Arrangement -Main Dam Area General Arrangement -Spillway Project Response Spectra Hybrid Accelerogram Static Spillway Model Case I -Static Analysis-Base El 1124 Case II -Static Analysis-Base El 1124 Case IV -Static Analysis-Base El 1124 Finite Element Model -Base El 1160 Finite Element Model -Base El 1150 Finite Element Model -Base El 1124 Finite Element Analysis: Case III -Max. Tensile Stresses -Base El 1160 Finite Element Analysis: Case III -Max. Compressive Stresses -Base El 1160 Finite Element Analysis: Case V -Max. Tensile Stresses - Base El 1160 Finite Element Analysis: Case V -Max. Compressive Stresses -Base El 1160 Finite Element Analysis: Case III -Max. Tensile Stresses -Base El 1150 Finite Element Analysis: Case III -Max. Compressive Stresses -Base El 1150 Finite Element Analysis: Case V -Max. Tensile Stresses - Base El 1150 Finite Element Analysis: Case V -Max. Compressive Stresses -Base El 1150 Finite Element Analysis: Case III -Max. Tensile Stresses -Base El 1124 ix Figure 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 0216R-4460R/CG TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 3 DAM AND SPILLWAY STABILITY ANALYSIS LIST OF FIGURES Title Finite Element Analysis: Case III -Max. Compressive Stresses -Base El 1124 Finite Element Analysis: Case V -Max. Tensile Stresses - Base El 1124 Finite Element Analysis: Case V Max. Compressive Stresses -Base El 1124 SARMA Analysis Model, Ogee Sections -Sheet 1 SARMA Analysis Model, Ogee Sections -Sheet 2 SARMA Analysis Model, Non-Overflow Sections SARMA Analysis: Base El 1160 -Ogee SARMA Analysis: Base El 1150 -Ogee SARMA Analysis: Base El 1130 -Ogee SARMA Analysis: Base El 1124 -Ogee SARMA Analysis: Base El 1160 -Left Abutment SARMA Analysis: Base El 1124 -Right Abutment Spillway Stability Analysis Summary -Sheet 1 Spillway Stability Analysis Summary -Sheet 2 Spillway Stability Analysis Summary -Sheet 3 X HYDRAULIC TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 4 CALCULATIONS Calculation Title No. SPILLWAY CREST SHAPE H-027 FLOOD ROUTING-P.M.F. THROUGH SPILLWAY H-028 FLOOD ROUTING -FLOOD OF RECORD THROUGH H-033 BRADLEY LAKE & DIVERSION TUNNEL DESIGN THRUSTS -POWER PENSTOCK NEAR H-036 MANIFOLD SIMPLIFIED DAM BREAK ANALYSES AND WATER H-046 SURFACES PROFILES WAVE RUNUP AND FORCE ON DAM PARAPET H-048 TAILRACE CHANNEL SLOPE PROTECTION H-050 PROTECTION AGAINST WAVES FOR THE H-066 UPSTREAM COFFERDAM & POWER TUNNEL INTAKE ROCK PLUG ICE FORCE ON DAM PARAPET H-068 INVESTIGATION OF NEED FOR AERATION OF SPILLWAY FLOW H-077 RIPRAP DESIGN H-079 FILLING BRADLEY LAKE RESERVOIR H-081 0216R-4460R/CG xi TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 5 CALCULATIONS GEOTECHNICAL Calculation Title No. ROCK STRESS IN CIRCULAR TUNNEL LININGS G(Ak)-04 AND SELECTION OF EXTERNAL WATER PRESSURE CRITERIA GROUND WATER SEEPAGE LOADS ON DIVERSION TUNNEL LINER G(Ak)-08 VERIFICATION OF INTAKE GEOMETRY FOR THE POWER AND DIVERSION INTAKES AT THE BRADLEY LAKE RESERVOIR G(Ak)-10 EXTERNAL ROCK & GROUND WATER LOADS ON POWER INTAKE AND GATE SHAFT STRUCTURES G(Ak)-22 FINAL STABILITY ANALYSIS: BRADLEY LAKE G(D)-24 MAIN DAM PENSTOCK -MANIFOLD THRUST BLOCK EMBEDMENT LENGTH AND STABILITY ANALYSIS G(Ak)-29 ROCK MODULI FOR POWER TUNNEL TRANSIENT STUDY G(Ak)-31 DESIGN OF ROCK SUPPORT FOR THE MAIN POWER INTAKE STRUCTURE G(Ak)-35 PLINTH AND TOE SLAB GEOMETRY -MAIN DAM G(D)-38 0216R-4460R/CG xii TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 6 CALCULATIONS GEOTECHNICAL Calculation Title No. GROUNDWATER INFLOW & LEAKAGE INTO POWER TUNNEL G(Ak)-41 EVALUATION OF SHEAR STRENGTH OF ROCK MASSES AT THE BRADLEY LAKE SITE G(Ak)-47 EVALUATION OF EXTERNAL LOADS ON POWER TUNNEL LINER G(Ak)-48 VERIFICATION OF CONFINEMENT TO PREVENT HYDRAULIC JACKING OF THE POWER TUNNEL G(Ak)-49 TAILRACE SLOPE STABILITY & PROTECTION G(A)-50 DESIGN OF ROCK BOLTS FOR DIVERSION G(A)-58 TUNNEL & GATE SHAFTS DAM TOE PLINTH LOADS G(A)-60 POWER TUNNEL INTAKE EXCAVATION DESIGN MANIFOLD & PENSTOCK THRUSTBLOCK STABILITY CONSIDERING SHEAR ZONE FEATURE POWERHOUSE CELLULAR SHEETPILE COFFERDAM STABILITY ANALYSIS EVALUATION OF CONCRETE LINER REQUIREMENTS FOR THE MAIN POWER TUNNEL MAIN DAM FACE SLAB DESIGN SPILLWAY: SARMA DISPLACEMENT ANALYSIS SPILLWAY OF THE UPSTREAM COFFERDAM TOE AND ABUTMENT PLINTH DOWEL EMBED. LENGTHS AND QUANTITIES 0216R-4460R/CG xiii G -70 G -86 G(Ak)-89 G(Ak)-90 G(Ak)-93 G -98 G -104 G -106 TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 7 CALCULATIONS STRUCTURAL Title WIND LOADS FOR DESIGN CRITERIA SNOW & ICE LOADS FOR DESIGN CRITERIA SEISMIC DESIGN DATA MAIN DAM DIVERSION TUNNEL LINING AND GATE CHAMBER ANALYSIS POWER TUNNEL INTAKE POWER TUNNEL GATE CHAMBER AND LINING DESIGN AND ANALYSIS GATEHOUSE CONCRETE STRUCTURE 0216R-4460R/CG xiv Calculation No. SDC.l SDC.2 SDC.3 SC-133-3 SC-151-16 SC-152-21 SC-152-32 TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 8 CALCULATIONS STRUCTURAL Title DAM PARAPET MAIN DAM TOE PLINTH DESIGN SEGMENTS A, B, C, D ABUTMENT DESIGN SPILLWAY STABILITY ANALYSIS - STATIC ANALYSIS FINITE ELEMENT ANALYSIS OF SPILLWAY FOR SEISMIC LOAD COMBINED WITH DEAD WEIGHT, ICE THRUST, AND WATER LOADS SPILLWAY TRAINING WALLS 0216R-4460R/CG XV Calculation No. SC-191-26 SC-191-27 SC-191-29 SC-201-SA SC-201-34 SC-205-23 TABLE OF CONTENTS (Continued) FINAL SUPPORTING DESIGN REPORT GENERAL CIVIL CONSTRUCTION CONTRACT VOLUME 9 CALCULATIONS STRUCTURAL Calculation Title No. PENSTOCK AND MANIFOLD ANCHOR BLOCKS SC-261-25 MAIN DIVERSION & MAIN INTAKE BULKHEADS SS-132-2 MAIN DAM DIVERSION PENSTOCK DESIGN SS-134-12 POWER TUNNEL INTAKE TRASH RACKS SS-153-10 POWER PENSTOCK THRUST RINGS AND MISC. COMPONENTS SS-261-16A REQUIRED THICKNESS OF STEEL LINER UNDER INTERNAL AND EXTERNAL PRESSURE SS-261-17A STRESS ANALYSIS OF FLANGE WITH 108" INSIDE DIAMETER SS-261-17B LOCAL STRESSES DUE TO GEOMETRY DISCONTINUITY AT REDUCERS AND MITERED ELBOWS SS-261-17C REQUIRED THICKNESS OF ELLIPSOIDAL HEADS FOR PENSTOCK SS-261-17D STRESS ANALYSIS OF POWER PENSTOCK WYE BRANCH SS-261-17F PENSTOCK ACCESS FLANGE BOLTS SS-261-18 0216R-4460R/CG XVl STRUCTURAL CALCULATIONS .t. 5010.64 rFRONTl CLIENT 6. PROJECT STONE E. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE A(_ /)F., kl+ 'PO"'NFP Aur~"''7"'"" -'f$1l-ADL~Y LAke CALCULATION TITLE (Indicative of the 6bjective): ( -;:)'=:tJS!V~ ~. MAl\}/ fOLD 1\-AX)-lo]l 8LoG/£-s CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O NO. DIVISION 6. GROUP CALC. NO. TASK CODE 1 '5 3:::::0. C) 3 sc ~G/-~~ *APPROVALS-SIGNATURES. DATE REV. NO. OR NEW PAGE 1 OF 5"0 & QA CATEGORY (\I) OI-NUCLEAR SAFETY RELATED Oli om ~ A.J/f. OTHER OPTIONAL WORK PACKAGE NO. 20 ( SUPERSEDES CONFIRMATION *CALC. NO. * R EQ U I RED ( v') REVIEWER(S)/DATE (S) INDEPENDENT PREP A RER (5)/DATE (S) REVIEWER (S)/ DATE(S) CALC NO. OR REV. NO. YES NO D. :..0 • P:.l"'[t:l<,. i>A-V't.. C A i!>LMX1tE7Tf v/ 0 o~H.·?J~ II /14/Bec, I jl?-/87 f<;>. ~ au.:. 0 rj) ¥~0 f)};; !f~tt~ ~,A!..;.-~9 'f C.•N;:!J("!!EJ 4-l-'0 7 1), A-P.:V\AJC»ETTE ~t< MADI7Ek_J ~ \)\3}S~~ 1·&5, es ' 0 JJ,w).O., ~ 7flc..rJ~ . DISTRIBUTION*' I 1 COPY I I COPY GROUP I NAME E. LOCATION l SENT GROUP I NAME S. LOCATION I SENT I . ( v1 I I (V} RECORDS MGT. I JoE> ~k I / I I FILES(OR FIRE I I I I FILE IF NONE) I Fr~ Fh.t:. I / I I I I I I I I I I I I I I I I I I I I l I I I I I I I I I ! I I l CALCUL.ATtON SHE£T 1 .L.O..JV..~.J C.a.&..CI.ILJ.t'IO., .'fQ. I""";(· I ~·;" _,.,,0 ,, I SB oo , 0 8 / s-c. 2 (Q r-2 ~ I"<'C ...... CII/:J.&t'C / / I"OICWCII/c:JICC:XI:II/OAU: i INOCI"L"'OC.JH •cVU'WClt/OAt'l: J ....._ 7::> II J 8<::, b-cti3 t/n/87 J. U) . 0 ...,---;-,~ 'uP'"''-· 1 nn . .! f!.t.J 5 DC'< ¢ MI1-N!~D Al\lCA·MR Gjl.O Ck.\ 1'"~ ;;..J.r!lO•'I' I;::::~ CI..~:S I TABLE OF CONT~NTS A.'W HISIO~IC OAT A (RcY~On~ Additia~ Dde:ion-s, i::~) PAG' I OE.SettmON I ORIG. REV1Sm,'4 I I ~-REVIEW R£.'rlAAKS ."<J. 0~~ I 'DN9 r I \ lltiln I I -r, -rz... ""(; I I I I TTIJIIA I ~. ....--:-.~ .L.. I p.r:; I I-'" or '-<"t I""'"'"N~ I I 3731\-1 I I \ I l)JJ/nl ~(r 31\'") 1?.-EV £\)MI\1.MLV AOOED 1 Ctnc..u LA--· "'J ("' ..J UMIJ! AftM I I I I G!:tJ!:~f\L ''})1:sc u so:; to-....) I I I I I ~1) I I i G ~ 71 P~N<O""'QO(.. ~~5T pl.«:k ~u,onfrq,-i~ I I I I I I 8 I Pw5TbCk ArJ c '-..-; ~L r f.+.-~,J ,e.,o Ln I I i I I I 1-141 S'ca-L -(PVJsmcl) I I I .8uR.s77,111G . ! I IS-I~ /fuop STQ;L (Pcc:.JS""T"::lci~ h I I i I I ! 18-Zo I slftA~ 4'/u~"~( ;'J:..; - /e_:;·J ''T""1( •. t\ I I : I I I -' -~-I \ I I jl<f-39. I 8 I MJti\JI f:A'LD TJ..~MJr Loc.~t. Lw-;n+l ~. j I I I loNG twD;J0fh. S"mc.. { "-'lhV,Rrto )I I I i 39 I 1 ! I~ (~fh.JIHJLf) ') I \ I 1/13 /2?1 i 1-o $"'~ I I I I 1-1 I ~ltJPlJ!<. c~ ~AJCIJ..EIF: Gvm I i I : I I ~z-4L! fk~Tr.~ I I \ i 1/13/~ I ~Vl~fO PG-G-] ltiiJO lfll I I I ! j •piG /t;A) o~ EIJIJ-t''-"c.ts p.a.._ Posr-j I I I ~1-,44 "f"~:DU>!d-N{:;l) UIJL~ '' R).loiJntf Tu~Ai&J ! I : / i I -~ 1 ~ T'7 1 h I I CALCULATION SUMMARY &501062 I<I.O./W.O./CALCULATI9fil MO. I S"8oo. o<a I:S= Cr!l ~I-2 s- OI<IICTIVE 0' CALCULATION ' I .. AIE !4 .:? 0, ""t QA CATIIOifY I CODE CLASS )J /p. THt PtN'S -rn C..)( '7 }..A ,4 tJ I t'=0, :_ I) -~,c-Jj ' ~ .{' -,~ ~ CALCULATIO. METHOD/AIIUIIII'TIOMI -~) !tSI(;:.Rt=~-t )...)t>'11Al/l-1-k8fs WILL 6E P~~D~. rA-.vAJG ~P,l( A'L cr:::) .s·~:-'- b\2 LIM Ill:;~ -o -r<..Lt; ULT/~ft'"(t c:A:P!+-e-1-r-t ()F P-oe/< ( ao !::.:;~ j ~"-" '>~Ck A-1\.)(..t~L ~l.D-CH. w 'tl o t f'c ''::::r-7\::.r..l)IO.NtiQ ""rD p P-e J.:;.tJ ..-Lot··~ -;c /\f\1 :-=t...R ~ "TT+t ~C"A)~ l~•JS~ WM..l. -s\IR<T7A.6 ~ '-UP Pe-)e::-''"J.JtC ";:)~ ~~-,_: ·~ i. IOUitC:II 0' OATA/EQUATIOfill 1. " D~::':) t&N ol= El..) c "w <:.\<-s; +=-o-tt LoN~s 1 "beL l9C. 7 3. C:OMCLUIIONI 42-44- ltEVIIWEit (I) COMMIIITI DATE !} 12 iP7 DATE CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I J.D./W.O./CALCULATION NO. I REVISION I PA8! A501061 \SS{)Q·08 -5C-';t-~\-l~ :l-3A PRIEPARER /DATE I R£VI EWER /CHI!:CKIER /OAT!: IINOIEPENOIENT REVII!:W!R /OAT! SUBJECT I TITLE IQA CATEGORY I CODE CLASS Pe~STDC K 1\~\J N\Pt~1:FO\...t> Pt~C\10~ ~LOt: \<..S 0 \ \ ' \ l \ 'I \3}S?g \ [t3/~ 'P3l98 \ /13/8g \/13}'88 i/JJ/8'8 \/13/~~ t:.W\t.\6-E. 'fOTI\"1... 't.lO. OrPA\TE.S A-NP R~y t\JQ. o~ i:S:T'-E. ~A-G-E ~~\.[l:~Etl TA~'-~ 0\'0 Q)f\rt6NT A;\Jt)E.\) R'C\I:I:S:t:OI"i t\-]:5 TO~ V 9(;.- ft{J OEl) ~0 TE. lt-00 ~.IS ~0 0 ES.I:&-f\J ttl) \)c-D ~OTt /tfVfJ Re\JJ:S EJ) l) ~ SJ:G.IJ REV.:C:SED l>ETA-J:t..S A-J) 0 ED PAb-E '+ 5' -7> S5' ON S !+EM( T~NSF6""R-JrT Tfil2.l).ST BU?Ck:iEY~ -- \ CALCULATION SHEET 45010.61 PR{PARIER /DATE D-LV. PoT'l~ SUB.IIECT I TITLE p Lo~tDo:;. NoP..M.M.. E~-t~Gl/ E' /( c.EPt"~ ('r.._ Fl::.~s t?JCK. 3o44'" 4-o4:?k 4 B~o k:_ STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.D./CALCULATIDN NO. REVIS I ON /:)8oo,oa s-c~r;;f-:<!; 0 M.AN/~r...O ~3Sk 77401::. ) 151-DIL 5 QA CATEGORY I CODE CLASS (The. Duur-> -ro )1-h:./(NA,.J CJrJCM 7/j;~ "ICN-.JI{L i PUJS"!'JQ 1'-l=''J'St!j ~->f,IJ~ ~ .. ) (roc 1-iR..<:s,.,; ~ 5/J-.,;rl_~~'~ 4/z.; /a:;, ?~f\:J ')"-Oc.k ..,... ~.)j ::--~1'-os. . ' \ .,.. ( \ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION 45010 61 PREPARER /DATE b' w ' "P,-r--r-;- l) 0 REVIEWER /CHECKER /DATE tJ OJ3 I I I ~ 157 QA CATEGORY I CODE CLASS r 1..0 ~ ~s A::.r:t. cei"'IDI::-.;N 11+-t ~Nc..~c. C::: ~ C...k IJJ tLl S~ (.~ f:,f 11-h; ~LI._cv..j//'JG ,' :a.) UL.TIN!A-(E c;..,_~C-rH M'CCHof) I w l!('t Ot8S" Due: 70 TtZfCf "-A-<A< OF <-rr~~I!TV/?..€ oiJ PuP.£ S hf':-R... 1--.J c.e/'lc.~c; . F~ -s~rtAA F..tte-.nor) J Acr-3'8 -83 ::P /I s-"s,8 ~~ A?-.J ufPI:ft LtA-u/ o.0 s-1-f-:r;~ oF 8 ~ A ':_; :_. _ _,pi,JG /Ue7 rJ ~ IJG ) W t+tL-r 1[-f'r= J)E"Sl&N wlL..L P~10e FULL Lo~O -:-pflrJ; Cf.=./Z CPrf AC.--1 TY If'-) .::;~) lJ6 M II'J fh_. \<-tys Wl U 8r P~J:r'i ·DE h.J U"r5 .:0 O'F LoCM_Lf Pf<A:-aU~ ?.eCJL f't-r l,lf-6 (_..L)rJ(f£7; I~'* ) AJTE:Fu=-Prr:e . 'B~ING Of'J """1/+t)~ k..t-t r l.J,_) I L ~ (tLL $ I..;..,,;;P-f<._ -f, R.-€11 sTPr10 c{ iGtJO uD S.Lf1HA f.!;,c L~S THA-0 0-+--E uLT I"" f.--' t3 ~C!<-'&~.!,Jcs CAfJ ~.fl 7'1 8o 1<-s+ /~ CALCULAT!ON SHEET STONE & WEBSTER ENGINEERING CORPORATION ... 0./W.O./ CALCULAT ON NO. REVIS I ON A5010.61 /~&J<::>,Oii?> .:; c_;}(o/-~r:;-(';:) PREPARER /OAT! ,r_.u, D~~e,a lo -0 -8G SU·~"'ECT I TITLE , . --rc:>r\:' t) AJ..JCI~It 8o'-TS WILl... BE Uyw•M-6 ;J.) NA-x. ~0 I Lif~r~-t"' b) PR.eoF LoAo : C), 8o~uA L:x_,.__OFF LoAQ ::: 0.7o A flU II [) B,/ {n,) II loAQ :: o , roo +,.u It ~ ~. ~. /? ~ 2) 1 '"'l!;Vt~v"" IZ:>oLr SPAG!IJ(;. --'- GAAof" 156 .: 189. c, k -:::-/(:.; $". 9 t ': 1</.2.'21: QA CATEGORY I CODE CLASS R.rf: ))'t '<) I (}/'t (y T ~-1'0 i p"S"'(t.f.-St;All/'06 S';s/}:N! (A-f'T!'rCW !_) , 3) 1i-re: F'crLU>wtl'llG d I::?Jt~fu_ CotJ FtC,UAA"fr.-QrJ WILl B F US !ilD <: 'TVAINlt""t. \ oPey <..ur ;;;r ;: ? ~~====~~====~==~~====~~==~-~ i I I I 2o I ~ ~t.N I I 4) le~ WI L.L 'Bl[ -rA_~ fif ~/-f1;~ P~tc..TZ.AJ.,J IN 'J"Uiti/l)t?_, /)ur;-v Po SS'Bl e ~Pt!: ~ s~ftt:.el Kt:'fs v-~tu.. BE' Mow As 11 c;;r-PtE::-v Cfl-".-(~. loADS ./ ~(M.Pn._ 3o44k ~ roc DuLtAJ ~ st.hJo. .... ft,.J / DurJChJ 1/!e/c6 ''Tv JWJI:L ~ Pi::N s 77JCl:. f!r.l''i~v 1~sl ~/"t7s; r ~l1l.&rkJOj '. 4013'-14-t= ', roc_ ~ ro I) l:h..'R.HIP,J 4/z!/8(; '' P~CrJ s rou r~s.r 6:Aos ,, 4J8o 1 £ k c.ep·p o-...J ~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I.J.O./W.O./CALCULAT)ON NO. !REVISION IPAGE .r.so10.61 /ffiCO, 08 Is-C:!._ ~ 1-2j-0 7 PREPARER /~TE !REVIEWER /CHECKER// DATE I INDEPENDENT REVIEWER /DATE b.w, HJr7~a /o-~-8b JJa ~ I/J2.-/P7 ( SUB~CT I TITLE IQA CATEGORY I COOE CLASS 1-"(U\J '· rn f"'.k A-;,vo+rvz. BLoQ::. !::' - Posr 11-fe' S~.s R..tzv 6-"!Z S A-L ' D U/(t/t)C AAJ I?M t:I'LG nJ/ ~~ .. Jcs (L)l-'-·~~ C&tJLD l#+r.JE R..t-"3 uc.. 7?:::(J ;AJ S"~..S C4~Sta,.J C~~Xl,JG, Tt~ ,, , p b\1 ~lOCI<.. WILL BE !fNCt-IORA::{) ltr r'f 7f/7eA.Jsr ~~~ 5 D IS 1?._ I B u 'fd.:j ~ I+ --r1f-E ~ '1D T1f"'c .4-NC!fOf\ f3o L 7S . / /-1-E Ben. n ~ 71-ltl tel'+-() ( e y ~:--,_ /.J 77/1/C. fJ~ r,;;-~ _ :.. ) -ro Tlf-e"" -( 1-rc A Tl# ~O<:,J u/o PN/ L<J/H) ~-J?jl'{_f 4-rJJ) c 1:-i-t~J) ~R ~~oF [So% "u) .'h-JQ ~t) /(nU (~a "lo P\; ~ • A.k, LoA-!) Pfk.:rof<J IS ,AP{)U E=D 70 71IF fJLT1#J,It1'C ~/tO ~F ~ 77:: /1} 0 tJ ,J .f/I'Vc..£' 1r /:; T/ltf() -r1lt£ U'-I!Mif7G" Ln!tQ oF I) ) TP-€ G u fJ eA!J ""T1:E D UL TIIVJ 11-(f:E' "J;;--,v; I L E CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 P~ARI!R/DATE W. '"Po SUBJ!ECT /TITLE rt:..Ns-roc. .1.0./W.O./ CALCULATION NO. I ,93oo. 0 g 5 -C:Z ~ /- RI!VI EWER /CHECKER /DATI! fo-0.,-8t:; ~.~ C':. 1z_ p l:1-1 VI. Gt( 4CJ4'$A:. /-42,2 ~otT CifU./..£ DIA CiftC,-::-'TJcl=-?:l./7( A9o1JT REVIS I ON ~ PA81! b QA CATEGORY/ CODE CLASS 0+E4. ~Cl...T L.oA'O!,v6 \..JrlC f!ll.. 1:;'/-cti'--c.Y'-·-'-oPo ·, CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVIll ON &5010.61 l58oo. oS 0 PREPAR!R /Jl..AT£ b, w , Po-rT~:: SU8.JECT I TITLE pf:.f--JS"";::)U QA CATEGORY I CODE CLASS PP--oeF LoAo ~ ~o.{; tpi.)A -::: 189. b t: / Bot..r Dl?) lG;v la/W =-0o% tpu A -:. /4 '7. · 1 ic / i?OL\ ,. .. '?..D (Acr .. '318 ~ [gS I...IM.IT'S l..oc.rn.o--1( \AM. '10 6/14-.C ~ Dt--:,lt./0 Lo/'0 ':1-e. o.7o .f,7 J.l--577Vt A12 .. ?... SPl<:(...fpt;:--s A-11/IJ(M!J,Ifl ~~"" D, 8 Cfu , s;"f<et..l~c.Ati..-W ~'< rt!IS fMJf:?.?r ~'DUtRt::l A~su..,.._i£. -fp~""t,,f:.SCru -=/ ~~-= O.C1f(o·~5...{.~0 ): dt7 .. ~,v ) l)'CSI&N o ·70 (a,~..~..P!J) =-0' 0 -f'J 1} .(\_-:::. 3oco ?,· ... II ,, I J1,;.'' 7 )<. 7/z... )I /4 ------t' ~ .--,' <D --L,,, Q) I L.._.__j VAll..{ A /){L/7 IN /AJS'n%LLA{ld'>0 Msv~e 1) AkA BMt.-o ~) c lo-l Tl:.'1l -Ct;:,.u 71.~ (J~ 7~7" ~ SfAUAJt:. f3fl'· ';, ()N 11' ( 211) z._ 7\.-7'xt' -4 ... CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION ..1.0./W.O./CALCULA ION NO. REVISION 45010.61 /~ooo, oa s-c;<G /-c PREPAR!R/OATE :b. W. '"PorTh REVIEWER /CHECKER /DATE :tJClB ;/tc_ ~7 SUB.IECT / TITLE QA CATEGORY I CODE CLASS ---~ Pt. '----d' lq -rttl! PR.Is~ :. 1!-( 8" DEFr~~ , PLME< ~PAc.tAJ6 @ il'lSIOE" ~ll OF-PLAt"F s~ ?a_ ::. f\ "' ~f¥\. ~~., L 3 ,/t;" 4~94--(),{ 7 318 ~ 18. /JA- J Ac-1. 318 LOMKf!t-.lT~ 'it> 18,1.:$ 912"" Llt· .. wn;o ay /, 25" -If:. R.~u I~ 1/I.A~tMu lf1 /+LLt-1..Ufrf3ic &1::P.I' J'K"; ~ ~lfP/AI6 Clle-c/t:.I.J6 Lh.,-,Mr?"f'" A6tA;AJ,sr t1t7ti P/t(:n,< : 5'.17 ks~ r N.C.. W6Ull) 'BE'" A~t 0 = Pvq--'?. '3 7k c; 3, '2-'::: -s-3 r 142.5'" ..f' I "3. 7S" ~[ ... £....., c:;_ - TH-r~ "-'o IJ LD R..t:ou 'U Ol)t:.1{ 4N gil squAtl£ ~ e:,p.,__ A It_ ()/{ A ~'1"M6U ?lP\1'~ Sua-+ Prs eo\ 'X /Dk A ~ /'r7J6 u LIV< P~-Ar~: 'JUOu \.f) •\}<::.""!" ::~ D~si~LE !)ue;-"'TT 1../MtJEO C..OtJ~ of'J Pt/+C 1:: f'i1 v·..J-;-. ( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./CALCULAJIOII NO. 'REVISION 'PAGE ... so1o6, 15z3oo.d~ /:;-c~0f-.:Jr o li PREPARER /DATE / / !REVIEWER /CHECKER/ DATE I INDEPENDENT REVIEWER /DATE D, w, 8,1TL'R 10/ 9/,~r;. JJ o...CD I /12, I B? SUBJECT 1 TITLE I · r IQA CATEGORY 1 cooE CLASS P&.!VS ""G? Ck 1-AJCL-4/J BL<Ju.:--- '-\.. 11 l!o·h~ 15 AcU?Hir'B>l.F-S/.uu-FoR. 77-1-C 7ll ')(7Tf 4 ==5'Z..·)-3,/ ::-19,q rj.;;.:-) {b.,. 4.9 '-.£iC-f'' C)!, Cti?U ) 89. (D l:. 4s-.& cl.h:r...k ~ e-A-ItrA.J6 @ U~[ 6~ LoA{) : ("'c.~ 3l8 ~ro.(l/tl::t-J~ -q 18 t\) ) < - v-J/ ,::-uLL '?l...ft-fc SI'H.- cA = sn.l~/~,) CALCULATION SHEET .. 5010.61 PREPARER /DATE J). W. Po'7"-r·cfl +L ~ ? -lAc... '237"' = 89·7 ~.,.; '::. (_, "7 los~ -C~ -::: B~ (_ -::: o, 4 { 2·~7,v,J ~ I, o? /c.s~ STONE & WEBSTER ENGINEERING CORPORATION J.O./W. 0./ CALCULATION NO. /~8co, 08 S-c REVIEWER /CHECKER/ ATE lJ Q B 1 ( 12-( p 7 REVIll ON C:> PAGE ~~ QA CATEGORY I CODE CLASS oF o-J c. -~ LoU:.5 FoR. t>os r Cewc.u-cr£ J ba 11 G 7 ,, 'Tt IJ H~..Jt-C ~ 1'':. ~:.::;, (AT7ACffMUJT A ) .fx-=-UtoJt ~ Dtl4-u s~-,· :,..J P~t;sl/! /"' : A.I!A)( tAo! UA1 /)!(E?577U:-~S lNG ~ A(._ .. A:/ttt:A OF P~ISI/I ::. ";; A2 -~ e;.c-ouc..r ;-~· !O ). = 9/.<Jt.,-1/r'-~ 9/.J--:~'J :: T-:. c_y T~ i!>'T PM... l:lu'-ST7"''- ~A..<-€" ::£ Ocl8 (z37k J a -:z ~ ( .. .'"' {.c;q;.FIC.!tiJT ~ ~ '-f.tton ~ "tetJtt. rri 4'?. 71t... u· :: ~ e>t!S .... 0 ,.... .... . . . , II.· <.: [~"' .r ~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./CALCULATION NO. REVISION PAGE &501061 I 6 o (') . 03 S -C ~C. (-0 }?, REVIEWER /CH!CKER /DATE :;cts 1 tU!n PR"PARER /.RATE [),C...). t'c;, !::;~ SUBJECT/ TITLE Pr QA CATEGORY/ COOE CLASS ,_ -r, ~ T[1-~l +.~;,.,. P~::.tM.I:srteLr "i"l::'t>JPL.E ~~ s "' [ ( o.~(1A7)(2"'SO)fj T,-" 42.7 1-\: 1 o;-;0 Jj -= o.~Kr J,47 (J .r- l'·.f-r:J':.:;t~ ' ~;:J~'l( ~10<J"!. ('/16~) T,. <l? 7 [1-6~io] , 39.{ k 'r"' ""l:J...><;tu: '> P1..-1 r771'JG S'PA.tJ6iH- Assvl.{E G! o . S ( M.) 0 · 7 l-~3"<>D<'> •T_,1 .. ~ ""\"' ~ltf"(r S~IJ::i"'- =/ r = 0 IS'( 4-,00CJ) "•7 r; 25() ;os~ ' I r- 5"'<t'L "'-0~ ( 'I')C. 'do 1 ...... -:.1.. )7/~ - / ~ Pu?() '<:: V~/1 (M< os'S S/NIIl/'"' 1'o AC1 1&. ->, '2d" c;. 7) " a-.. sc, o.c..a.,_ j,~8" C) 8 Cl ~ 2.43 a. s~o., 4. 29" I IO '!. 7 <;' (~. lo J CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION r.J.O./W.O. I CALCULA~ION NO. 'REVIS I ON •5010 61 1 5'8 oa , 0 S / {'-c o:J__f; 1-2 s o PREPARER/DATE I REVIEWER /CHECKER '/DATE I INDEPENDENT REVIEWER/DATE !), W . 'f> <>T"rt;R ID· Jo-8(.1 ~ 0, b 1 IlL/~ 7 SUBJECT/ TITLE Pv:r J <,. -n) (..\-:_ A rue 1-h\ J) IQA CATEGORY I CODE CLASS ~LoCI!- ~- 0 1701- SIN~ "'1'WE 5.-PIIlA-LS: CuMF 11-vy C~..)e; l'lt.<rx;M 1 ~~ eciuJ~~?tJ -3,.4;1/J WCiJLO 3fF LOc.A-L. AssuM~ A 1"/IN/1\ttht/1 ~c.l'r?_ GLi:=rP/70~ or=--·I~~ /TNCJ 'D~;-r~:::"?{/VIt.N~ ~ boLr c;J!-c..L€: ~u/P--£.D 0 68 !/ttt0 iHI s C-Lt..~,.cm!G€'. 5PJNIH._ p ~AO d ,r-~f,/rQAJG. 'I r r .. 7> ~u1b:Q '3iJ~A6 = ;o, s -+ o, 6 2-r ~ 1 == 1 z. 12 '5 UsE /D t-(r> Cl 3.2 :: I /D. \9 "T (,o.s)('z'0) = '3 '2. e~n l'Y-o"¢ Cli!J\O~e \~ .f wzo '5 P! 1'kL lull-q ¢ I "\ Crui\Jf-JCL I ~ /4-I) ~ 1-=2£ R-eQ 0 11.37 "' BOLl'-~; 2 ~ p /TV_-J II Ill L.&A.lG , ) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &501061 REVIEWER/CHECI<E /DATE ]j{)_f, I I'L /§7 OA CATEGORY I COD£ CLASS 1 ~1 T) A = AL fr.;S u 111 tl) -:. j/, '1 51;, =7 IF we-/tSSU~G 0 ~ ~ 80.'-~ t[,l ~ 7A' (!),7s-> ~. 72. -7 -:::. 9-3-::. c:::: 6t77 ( AL, 4 62--d<) . ~ '!4 (11-'-[t:,.s • zf..,~J) Ptec.oRO M'-f: V-J / J\ L.'f" 3 { S ~ -n~ ()-tea~ ~) WILl B~ ' I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I .J.O./W.O. I CALCULAlJON NO. I REVIS I ON I PAGE •5010.61 P.f!.EPARER /DATE j). (;..J , PorTex:. SUBJECT/ TITLE !5'9oo. 08 /S-c;<C,/-;;<~ o /(p IRE VI EWER/ CHEC~ER /DATE I INDEPENDENT REV I EWER /DATE /6 -1("-8 G JJ ct 0 I ;12-( t 7 pf'l'J.S"Ti) (V f+,..y ~JK Q _.LO~k I QA CATEGORY I CODE CLASS AssuNtt: · '·) IN/77/h_ /l.AJ) I JS c;"~' Bt?7UJ1:1::1J ;ue}...)s~c~<c F-0/J~-r£" ~F a, os% ::J\ oF LuJe:-1( ( St~IL.~ ~ 'l:btG;V l~l~tA-!I" S'. J. '2. ) GN = (__o,o~)(c.o!)('-f~;z_J;) -Q,0/9St1 -=-{),oo/fol..'S" 1 -z) De.?] tc..v Jlfl 3) !: /IPVS ro(l:., .,_ E~hl. -= 30 x_ /0 (, f'S I 4) Pe3t~ Fc'R "-Jo~Pr.-CA-s~ p::: 64o D 'f'H .. l lv/ 0....1::\J /1:;1...0 CF" ULTIIVII'r"t't: $~6TH Merff001 -r:'--H~ r I':'!F c;~~J tP ~) ~ . ~~~""''"'' ui.c..y J .uez;u"'LT' I:'PPt?c:rs (_ SitJC,£ ~X= "'Y~: -)-1 oy/c ! Gltf wtu. Be-ccrrsev f.odllleA or-8!11'1.t.lh-Lo/11)1/'.JGS.. AJ B'i> Lt= CTI A.) (j vy "1 tc,o'W 5 ~ 1-".A~-::...~r-c-· c-J' .· __;.) ~ DECT~:~ '-' I A) 'C STJUt•A...J (Q) Gf\p c... 1...-o<;. \J ~ •• LJRL.Ur--\~~ll]\J(..£ @GkP c..t.oSUI£-:: G ·5" r 0 ·0016 z~') rr.;;.. 20, 1-Zo ~)2 o . oo ~ ro::;- o,oo~/os- 2..o ·4 '2636~ - .... / ~ Pous roCJc_ ~ t; l<.eeAI'... -r o,ooo2s- c::--" ~ "O>'lOC.i<: -~~ -+-o,..oo2r I:: e- CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REV lSI ON 45010 61 CJ.fooP 0 REV I EWER/ CHECKER I DATE /o-lr-8 )jQco 1 ''-fg? QA CATEGORY/ CODE CLASS c~4ofsi_'f,s~12~)(1i') -= 5'19 1 D4o 11:--I~ c:tpl!:7<1sroct:.. +-;).. 0~?1mt 299 SbO -::... ) <J. 9 91 :)Z)(J -- 23 21000 :: 4;-51./A{£ ~~ ? (v-!?.alk. f-7 57'0 ) t-~MZ- 9 ~,31~ f-0 0 s-oo .J.-cr-/4:'8,. f+1 7 v-~~ ~--~8 ~ A J't = 24 t o-~ l)s.G. >1A-)f r 7 ( 24; 000 ) _,. :24/ O"C'l::! fi-;, 24-r~ ~s. -IJ. ' '/ l.Jse ... 8 @ z CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./CALCULATION NO. !REVISION A5010.61 158oo, 08 /c;;-c.20 1-eo<s-() ' REVIEWER/CHECKER/DATE 'INDEPENDENT REVIEWER/DATE 1:)-/o-~G, !J()fi3 l/tL{27 SUB.IECT /TITLE Pt:Nsnc.t ~c.A..J.,:;~ IQA CATEGORY I CODE CLASS ::::t ~•..aC}<. I <. 2-0 - f.o b £1ss triAJS > --v,? >. [!( 1-u."l·J 7 tP,U A-(= "!fr7' cJ = l!.')..t'L ;(::. t<./l-o IU j .e ., /de /,'-' c k-'Jc--:, s ::c /s'' ,, = z.-r. 3 ( ~1+1~ '-~"" tn. '11fi:T t::FFt::crs or-5tn{)II)IJ!fflAj s~n :-DuE i7+1VJ<o,:r f.ttJ6, F'rFII.. GWtPA-L IAI'FOI See Fol(""fvL/1-'_ f=c,.< R.oAI{~ 1 Y~tJ6 1 I i7) 1 sczr....rw.J 12.3 Ct+e~ CtJJJCfl..€.-rl!" FoA. S/-H;!'rTZ. 3 CD FAILIJ~ ~~ ~r ltiJC'S ·...::J~ snL(_ "c...A;fJ'T:'UR.-f 11 A-lJCH-oA.. ~ so FA' c...utt-t-wou l.P NC( Oc..(.V"' CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I ~.O.IW.O.ICALCULATION NO. IREVISI ON I PAlE &5010.61 1_s-8oo, oa /:;:-c ~G I :::? ) 0 ICf PREPARERI~TE 1),6), '/-:,7Trn !REVIEWER I CHECkER /DATE ~INDEPENDENT RIVIEWIRIDATI IO-(o~8G, .'!JaB lfn .... /:?7 SU"'ECT I TITLE )-) f::..I-..J 'TIJcl( A.). 1 uJ'!'Jr. :3 u.'"" c. k:: I QA CATEGORY I CODE CLASS Ne"" ID PIW ~ ~ h.l6 I I I //~ 11 ( c/-~" + z.(o,ce'7s ') + ~-o~~ (g.-+ 2·) 7,98'rr (0+-z') ":. 2 5, D7 ) ( l t L) -3o" 11 ( Q +-2) SA-<t 31 ~CC> Q ( Q ~ teet ) / fFR Jr;;:' #A.) :_, ·-,.t • /J, Pf>rr'r b ~-'.4-c-r"!)ft.t-1) f..<J fr{), ·, \ S"-E"O'AJrJ 5. 0 , f!<, g ~ 5"-15*" J 1.) lJ= 1.7P ?. ) E AI\ a<G.rnc; P-:: 4 04 ?, u ~ 6,7s:-{ 1·7 p) .=. s-,1 5'5 {-_ ( s) l?xc.-'af,_cr,.Jk f-::. 4~ Bo LJ --;::::. 1o<:> = """J. wo C,) D~~rn.-JVtt.Ve-s~ lt~t.W R.Rih.JI~-o -. PuNC.~.ttuc. sH"r;~ (P~ Ac..r 318 f1> 1\. ll, 2., I) V L-~ (J. + %) f%_ lo o J < 1 Vi;_ b0 d VL= ~ DCb"J ';. 4 T 4 ;;;PJ~ ( 3, {p 0 0 ) ~ IIO {)_ k Vu-= '5/75 ~ ~VM-= o,8s Ve- S77)-.:: 773 .Q y j Mt;J ;;;.- 5(7) 773 I (~ !AJ 4-r ) " CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I J.O./W.O./CALCUL~TION NO. IREVI810N J PAll£ .. so1o.s1 I S13 oo. o e, IS'-c ::2 0 I -:2 s-a '2o PR~PARER/0~ .I REVIEWER /CHECKER /DATE !INDEPENDENT REVIEWER/DATE D, w, f.-lt1rrM /o -11-B~I '/J QB 1 /t7.. tt. 7 SUB~ECT I TITLE IQA CATEGORY I CODE CLASS Vt.N'STQ CJ-4/\JC{-;oR 13 l.od (_-::.~ e_ n~r ~tAlC. , w'r ') De--r ~""llM \ t-J E. <;' 1-h:-~~ ~IN FORLJ;" M tNT & o88 ~" J-,i)(,.f) Pftovl DC: Tl~ 1\C.R.cs ~ ntis \ ~...Y~$-fff:r /,4 f"':l"l +-----+--!}PI ~.,.;-i -- l~l \~ H -----1-.. ·--!--~· I_ • ~~ ....... ~ • ~ 'S P/t-(.1 AJG 7?-irt5£ 'P>e-tWl:~ ~ 7 2 .'5'" -:: z(o,3t) 3~ lfrjG~} /17 1/7 -1[ A?.e ~ U I /lt:'1) @ "•Jic:8 {,.., c A-7"'t.~S;J ::. ---32- M4..Jot.J!?-'c";:!(...L--;/ ;;:J~__,f"!) Cg_.}C, / \ ) 3,G, UJE 4 / 0~1!)€" b&U~\..E ~" ~~... ~15 ~~ j CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 PREPARER /DATE rf.A..), "Po..,....-r(i. 1-s,s I REVISION 0 PAGE z; QA CATEGORY I CODE CLASS li CCer-..>~tU~ oF I.-6AD ~ "BETt..U~ 11-+l< . .n">T RJIUCS ":i' AI\JC~P-S f 1 ;= === ====-- I I \ - Q 19 !_ 4 ~II +o <6) I ....r.. i -'~-Z&l A I '21 l_ou 1"ffl> (A') Fe~ UIA I I n· fii'\ t.l ~ I "' I I I f ~1\ ( I l i lb ~I .. ~;!..... ;? & & £ « // 1':;1'~ l,c' ~ I~ • ~-v r:; r--~~~~ l I r\\J :(3.- ..,· • 1..11 ... ~~ :: wm= = I 1-@ I'~ '-/..( I < I-. ---- I 2~0 11 l~fA ~'~o• -I F"':>-U.I ~ -! I ...,._ ft..· ~ ... -~ ~ I~ .' _J.... '-<. ~ ~ LUI ·Ill\. \ -~ \ -~ loS' iS!:)\!rT [\Jt..J ... \ ,, \ ' J - ,..-., ' \J • - ~ ,. ---/ ( I . \.!;I ~~r-iAAD .,~ M., :j[~g?_ <:? 2'-o lA I ~1 / v t .. \ I \ -l t ;) / ' /. ~J ~t ~lO) o-. i <""'~! ~ 1 I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION PAGE J.D./W.O./CALCULATION NO. REVISION 45010.61 PREPARER /DATE b.w. SUB~ECT I TITLE r~"iiC) l Clfeuc_ ~F 10-soo . De?. -sc -2C:> I -2-s-o ??.... 1-8-8 So I:~-·-------- --/} -J>-- ,\If "" (i) r;"'\ I Ill I l<t I • !J ~ \..fJ 'f111J ~~Hf( ( 1...0 1"/JiroJG- LOfr{) /IV 1!!' ~t=( ) OF QA CATEGORY I CODE CLASS UNO~ ~ b-A C /:AI~ l....cltt) .l ~pj,-CSS!o,.J bu~Jt/6 ·~----- i .}) • .t ' \ "' k I ' -I ~H ij -C WILL .. I ' I I l"""'i.;i--"+""'--"-@-1!/,,_,_1_:_7_c._~+...:...' -"-!'7-~)>----11-----1-_'-_2_0/ _____ f 8-83' No-re: A.Jr::::. U>r!P~!o-N 13~~tt-tA.JA> /ls$u#Jt:TJ S;IIJ(£ 11/o h A c_7 UN(}~ AfvD ~pf4!SS.li::J70 WILL B~ T{Jt'?&) f3tt ~ C..OW,p1Zf5SII#...) R.J,J(;. rt\ N CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.D./W.O./ CALCULATION NO. REVIS I ON A5010.61 158CO . o 8 -S C.. -0 PREPARER /DATE }), t.u. PortER J-t3-8 QA CATEGORY I CODE CLASS 5' 01..,1//r£ Fc>~t_ \i ·. ~ Lt;( .P: I .. UL'TIIVJ.t-f~ 4AO :X: '¢ I PeR. fh:g~ 19 )Jol(tff/11. Cit!~ ~€:)!~ 1-------'----l----L---X---Cl--t ______ , __ -· --- ~.e. P::T::' LJ=-5"17S"'- .f~=O =7 p c.~;,'J & (8.3]) I O.stl-1 C•·'-•) • 0.71-14 c~. 41) .. o.~oH( G.n)•o· 1711G.I1 ~ /I-f-( ' l..u bCJL 0 B~ ~, /J...f8ULT7AJ G UAJ! FDilM 394-k. 7r (c..,s ') - T~ ~u'-llJJG lJl T/ f..f;f E' L.oAO I~ -r?fc (.1'1'" Sl£{ O!= 1-!o 01' -5 t..oo utO 8E; '(-; t:d (l~, f f: /, )( ~ IS I ) 0'2.7 k. :; 7_ -'1-r 'St.uc...e "11+t5 Is r-s~ A s-cr of= 2. H-ooPs. :;> ~ItO;~~ -: G7k _ L -3).3/r; uo{"' AC-TUftt.L/ l.,..oost; L4nPPA:SSt~ .. lkJ~f ~n Lo!fP,.AJG (p5, 17) #J.P Ac.ucp.,... CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W. 0. /CALCULATION NO. REVIll ON &501061 IS8oo,oa s C:Q~j-:2s:-~ QA CATEGORY I CODE CLASS Dt:;--s/&,J rolf!. El~ d) 4 A:OJ~T 77::;TJCPI'J~ (! t..oc.J.OF!!' l..twJ !.U J ~/riJ ~ll-: J."f =-),4x.4(t.s-:9~" l29A.. .b) 3 f:r().J~r 71:!AiJo!U~@ ULTJitfltt'tr (t...F:.!.o) ::. 3{~"37J..Jc: 7//-<:. ~P~'\lo.ol "6oA.)E t:"5 It MAt €' A<::. I ~I I -r 1 -lu -1.' Me\\f'!l-:.--tl - -~-,~ ....... w;;-. __ , ~1-b E. nto~ '1'1>1-ltVt."""L ·::::-{ll , .5Mff: IGNo~O l'b/2.. r{ft:'Yiii: CA-LC: S ~ ":-J{ -=--/,9 lf d"A~I!'= /3'2.1• e ~ ~ :. s.s- I-.,. 00"'( I.. I 1<-t.l...{ 'T-O ~"X~ TO 'Sol 1 0 C-\ 1\.WJ L M C-¢1..u M t\J I 1/cl .tof.Vm R.e1 f-.Fo,L/."fl.f ~~ 1/ I 0,7!) ._:;7 ( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION ,J.O./W.O./ CALCULATION NO. REVISION PAGE /5Boo. og o 25' REVIEWER /CHECKER /DATE 'I)o£; lite_. 7 QA CATEGORY I CODE CLASS /&>60" 7T ( ~:_~)'- If ... f (cJ. .. -d, ... ) ~ £...+ ll1~ ]\. -s - v c.u-ttl' -:;:.. 2-7, 9 k-"Sf rr--::: -/2,5 ~f v 70JJlqY ( llk'Sel) o,v Ac..r sJB-2 : ) ~ = 6,4- 51(:) tJ , () •0'1~ 17$' (14f -(f. ,:f) f ~ 0•09817S'" I+ z.o I '1.. / }A.~?.) \JI}t 0 r= ~N!:J. /91le>) f1· ~--n.) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I J.O./W. 0./ CALCULATION NO. t~goc. oe Is-c ' REVISION I PAGE -;JG,/-2) C) 2~ •5010.61 PRE PARER /DATE 2).,J > Parra ) REVIEWER/ CHECkER/ DATE ia-l,-13b ~(A f6 \/ll_/§'7 liNDEP!NDINT REVIEWER/DATE SU8.1ECT I TITLE p t!N 5 77) Ck Avc..Poll. I QA CATEGORY I CODE CLASS (v...,NIMUM 6r Act 319 7,11,z.,/) o.oo11 C~l i<f~i'·J'-(t.·S'~/2'!1 ~) ~ 21 :> vJe-D 1 As -~·i>-~ 0 .7(o s0 ;; /D/ifl. use-::!:::f:_ g C? 12 1 ' CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .J.O./W.O./ CALCULATION NO. REVIll ON PA8E 1_( .sow 61 PREPARER /DATE b, ;_.0, t>o-r-rt::- SU8.JECT /TITLE 0~.:::-Ns. c> fo.-Nr c.APA &1 Lt 1f L:J;,_ -,; IO' D 'jj,"'\t.:N~I N P<ZR ~ <;Kn'U-\ -it ls<Boo-QP>-2-3 I -I /,)Boo, as s-C;;z(o/-o QA CATEGORY I COOE CLASS 1/_d ('>.; ~~ cP -~~ '6 /8~ :.j !4-' D // LD ~--" .. I ·~//, ! ~ I ~7 ~I I I /(I 19 I ~I • I A_s">u M.G HI""'IMUM L~G 7!-1 -:::. ..Q A~tA:"A-:: 0-r + 14 1 1-2. (I') J Q ~ /lf( 7j _. 14 • 14-) Q_ -:. 50~ ~ ::. C:,oc ~ x f"({.tl M p l 19 ) i-J 6 /{ M ft1_ c..A$ €" Cot0 TF<.§J'L <.. lJ -:. 1 .7 P1-9o A.-1~ = l. 7 ( 3o44-~ -:: c:; 1 7 r "' ~? -¢ Vc.:~ 6 ' ~ <;; ( 2. ~ A J ~ o ~85 (~ V -46;,) &ao j) J 5;/75"t t)C>Olf. . . --8 l;f -:/ ~ M1;J ~ CQ.<l3Siz.)(~\rooo\-· 0 · '2.. -I t 7 J / "" lot. , _ l.t:> c....<-wf.M::n"-1 ~~1011"-fj) CALCULATION SHEET 45010.61 PR!PARER/OSE ]), (J._) • · o Tre SUBJECT/ TITLE {J rpj .,..., ANC/+of.. g,'-OCI<-.J Zo'cp 18'/J-.. ·· / ~ / 10,' {f) _ I 14'0 + l L ------ 2. -2 2o 1 cf STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVIS I ON J 58oo. o s :;; -c .20 I-6. QA CATEGORY I CODE CLASS 50.7 11 O[c.. \ , I\/.. l'l@ j 4 )""'11 . 5r .-,::: I '3<1s• ~ D 4-f.J -(. J l - I 39 ;-'".Jr. - I 0; 48bo ~ _ 1 39 ~ft ,) r- . ·~-'· ')'' ' :,; ' . ' ,,, . r~, . '-._. : -l-12~~). L , f. ~I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010 61 REVIEN PRE PARER /DATE ! , CD , 'j) t' 7'"""'!C'1 SUB.IECT /TITLE QA CATEGORY I CODE CLASS P~ j<: (A.;vu~rz I?>Lcc..j(_ K~ I 0t.1J Aj ' .,-) Ct+t;-u<.. S4t:..¥ );<:.~'>.'So )<_!E'tf (I - J } /•. I SE.E ~ 1\GE.S 45 TO SS 'R>~ S '~-\€~ REJ;I\)f=() RC. G"MS ~ ,-\)ESI:G-~ CALCULATION SHEET &5010.61 PRE PARER I OAT~ D.w. Yt>!T STONE & WEBSTER ENGINEERING CORPORATION J.O./W. 0./ CALCULATION NO. REVIS I ON PAGE I oo, o8-c-o 30 OA CATEGORY I CODE CLASS I~ A-:. LS"S~t. (~wtO/K. lt:I\JG m =-48' + r--""11\J 8A-I( ""-.J)'f'l{"i' O,.) z(4") : 48.b7' 1"1 ? I AX tin_ =tr t.u if't;ot E --5"71'Ui'S..J c.- L, L t:~.J6 7'1""" t:-: ~r;l.n!JG~ M.aout.1.:.s, (o~ P~F LoAD (6.so ~ru A) ~ 1 aq.e:, ~ ?:: 1..-0 A() (lt09d, ~~Oii~ r 49''X'"~) I•$"&!M1.. '( I 2.43 If LocJ<-oFF LeAD ( Cl ,7o -t.,.., A) -= I~ 'S, 9 t (Jr.:,5~7 &.'ggo%)(49 ~It/;) v "\..q 't\10 .. 1~ ~ - '-C>, too ~pv AJ :: )42. 2 k (14-?.). ""x l~oo ~ ) (49'xn/,) "-= 1·!>-g "'YYl z, 1 S (I -1.32.. Lf '2.)3q ) tl ,, • 0 "2 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION •5010 61 I.J.O./W.O./CALCULATION NO. /REVISION I PAGE 1§""8oc. oa -sc-lip/-zr o 3/ PREPARER /DATE D, eo . Po TTf£1{ !REVIEWER /CHECkER /DATE !INDEPENDENT REVIEWER/DATE /-8-'?37 ~a. 115 \{lJ.../8'7 SUB.JECT I TITLE r:;::,E 1'0S 70 c.k. -r;AAJ s -r B Lo cJ<--~ IQA CATEGORY I CODE CLASS I} - E s 11M A r r;; c /Yt,J G. ~ , AJ LI::;N6 r 1-1 aM ro. o,...; A v ~lrG li" P llf:s '174:1 ':.> 11 17s s u,., 1"' c "' C.. f ft(.,UL~ C~$S 5~/K. ~ Ac c:::. I~ ooc -sg w:, {? eo ... c/lt'Tc:. = 2.9 xro G. psI. ( L ({) l L-:-.. 48 1 f'~ -if IF 0. 67 I 11 c.o~-»&w~ l.oAO -/rp5".1k ')(: 3"l ~n.::: 53o1'r:- f (ff}o ~ k c. /ooo ~;I<:') )~8 ~ h/,) .r-:, ~ 171000 ${...:, l &I I 2 ,9 i(I'O 6 fc;;:_ C), C>6 2 l( ~ +5_s-o'k t< /so-o ~)) ( 43, X/2 u;,) ~ ~ ~~~ ~u., z.qxra'fsl C). 053 II STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET REVISION PAet: &5010.61 0 3'2.- PREPARER /DATE , w. 'Porti J-e-& SU8.1ECT I TITLE QA CATEGORY I CODE CLASS Pc.; S.v« "'tt!r7' A'L ~AJ~E c~ <. bf\R. Slfoll.. 11zJUIN G -Crn.IGIJ.trrt: l..bi.JGt"l/1' AJ (; (~ 70% 10 'tJ)O ~)'A-'"( :.40 ) o.17 0 ·31 II {)rso I' ~ -O,OO? ..... ..... ...:;:> As'lr>vA1fr~ (!)~ ~o% D~tt;~Y {Alii) I) ::::.7 L.,. 3. 75' I Des~G~~J CR.tn:.-x.1A , P~,.. 13' .r~;-J S:o , IJ· B-S'"-1.3 J ~ v(&) L, -t E<. = o,3 (z '8ps~j( ~t1S 1 xl24) _ f...f:txro 4 fs-~ - tl C),OQI'Z.. hCC...I:::""PT'ML€. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 IJ,O./W.O./ CALCULATION NO. !REVIll ON l PAGE /Q3oo. os-sc-2~1-2~ o 35 PREPARER /DATE b · Lo . ?o-rrf']{ IREVI EWER/ CHECkER/ DATE 'INDEPENDENT REV I EWER /DATE 1-8 -a 7 JS cue. \ t 1 "-' 97 SU8.JECT I TITLE 'j)!---;..lS~cl::. T '>-HU)~'i IQA CATEGORY I CODE CLASS b>c...o<-1~ - .UuG It> ~s77c S~lf._7l::N!Ai6 OF II \ De-?~· O.OG'2 ) c:--: b._g, I?~ (<;,,.,,L~ -rt:> ~/#Ilk.. s~~ . ) L... CA1..c. 1i. !!)lJCXJ -ss-2.& I..:.;(; A (o I bC. "2-0c Z9 c10" , ... ~) . ~,X /1.1'/,) -31 /Z.o psc.. A OIIJ/..7 r CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &501061 IJ.O./W.O./CALCULATION MO. IS"Boo, Q3 /:;--C :2_&1- IRE VI EWER I CHECKER/ DATE to~ 21-!,c.:, )lq~ 1 I~~ I -a1 'INDEPENDENT REVIEWER/DATE PREPARER /DATE 'D. w · 'PoTTeR SU~ECT I TITLE , t-' I:N S. ""0 C. K l QA CATEGORY I CODE CLASS ~ H ~,c"'l!(, ~'1 7 74-ok. E ~Ctl"rt o~f\'-Cf 'S {o /1... l :r:ac... H~..u"'!b <)ln£1J!A?J ~l::nJS"f'3Q<. '!~~ E"Miill6c.:ll.l'1 \j:: o .-rs-(}.Txt'f~):.. 0·7~(1·7'!. 774-o"-J;::.. 9 8 7o lc. Etc'.;:-f'(tA)tJfh u:. I ,6 ~'ltc.cp.) ~ Cj ~ 4-o l: /, -lo ALLOt.-.) 5'77\ I + So ( '0 P @ VJy e-i ~ srn 2 ~ Ia. 9?... 3o 1 ~~ w.P. wyl: ..l 1/v;ac Lo/<f) ~ " ) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCUL TION NO. &5010.61 /~Boo.(:::, 8 S-C ~&:,I -2 PREPARIR (.Jt.,ATI ! I !JJ ! 1'0 T""'"".::: r<._ SUKECT I TITLE ) ""' "'"' .-'t"OC....L - / (_~At) I :e:cn_ u -"' .... c~=C) ...... ~~ ~ • ~~ ~'p -+-R.tJA.) ~I> l .... ..;;§'~<J:t::.J----1---------->i....;:... I~ '_.-o_,_i --"8;;_1_-_o_v,.,.-i J-3 REVIS I ON QA CATEGORY I COOE CLASS ·~p w~ -r;I.!Ni.i! L. :.irn-I I /0. 9o r CALCULATION SHEET &5010.61 PREPARER /DATE D. W . Po ~~•.::F SUB.IECT /TITLE P~e, oF i L STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVISION PACIE / 5~0 0 I 0 8 ..5 -c ()_ G I -.2 :;-C) 3G DATE ! 0rN'r) fl-ltUST R..trJG S ; QA CATEGORY I CODE CLASS ) J -, ; 41.--A-~ Y L,~ tJ c 2 \)u 1\1 ll i i".l G S f-h:: --p.q(_ G> Dl A, oF -r-J-J-wsT RJ,JG s CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O.I CALCULATION NO. REVISION 45010 61 Pr~t_EPAR ER I DATE v. 0-> . P6--rt~:: SU~.JECT I TITLE Y I.<N ~· T:J ck - !I- Is-Boo. o 8 s-c;;_r;, /-G REVIEWER I CHECKER I DATE .:rJ cJ. ~ I ( P,, 8l QA CATEGORY I CODE CLASS (H.AtJI""'oLQ .'Wc-ti-OR £h . .oo., (.o,k>1 ~') c~MA!Z 4:"XJ67'fl ~ 'JJ I UyJ I r) ~ /3.4 IJ : qc, Lo ~ (p' ~ ~J z fR A :: C9 I 8 )J 2. ~]I 0~:) ( (o (o I I (o I II 'I ~"' i ' / ' r-\ CA-tv C.fU:::"""r E ~c.!< I NTO-..Pftt:.£ s-:s 3 s-ooo tJ. l l - op I b6 psl. 8 g !I ( ct) 1 ·rr.: ~-9,3 'S'( <) \ .:;..oCJa ) )D7(',L I := 7. 3~ < 1].1 .Q,..,,t-J-= (joOpsi.)(c,~l") ( s ( f'v1 A c. r 31 g -s 3 Tf ; r 11. z. 1) )\+~ ~"' rrd ~f'!w :.1T~~o·)~ z(l}· 2-(8'')] !),._, ,.J ::: /C),S ~~~~IN -::. 3 3 I}_JL<,,o.,j -= ?,C) (s; Q_ 'Vf\ ' ,...) u ~ ~ v G ~ 0 ~e~( 4 ~ A) q/1Zok -==-(o,e0(4)~3o~~ ,~5°~)?/'·~ Cf, 92o ooot:-_ ~ /' !{ !-' f'J = {9 'S) \( 1) hOOD (.) ~ b J -J _s; 4 ' 5 -II. 2._ I < I? ,d._ I CALCULATION SHEET .0.5010 61 PREPARER lrf_,ATE ]),(D, LO ~ WtT{-t __Q MI.V R-EQu ~~o Fo.< ......._ __ . STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O.ICALCULATION NO. REVIS I ON PAGE J~8oo. o 8. Is-CrJr 0 38 REVIEWER I CHECKER I DATE ;::s-cu~ til""/~? QA CATEGORY I COOE CLASS ' c..o-N'r-) L~G(f..J ~QUI/(.kD) fUc; fJ FoiLCt 10 G 15 !_} c,-;" s 1-h::ftR. p~/01£ fVb-; A) Fe~ { ,-)(:;, ;::::_ .. /l -·" st~: ey IN~ A:c..f"':..AJD 5 II'.) Cf /< c J ) ¢ Pu1'1C.-1:1tlll 6 s m'ft1! G2 )o ·5 1 d ~tto (.), RA:'D I -//.2.) ~ tJ'*'u---c..-r ADH/251()~ ~ FR.tcTJ¥0 ( )(_ ( tc(8 ') ?_ v. ·)) lT )o 1 -"-= -z. + 7( /0 ~~+~++--(:6.) ID I.~ Y~ +f, 76. I ks I +-1)-z.) / CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATION NO. REVISION £501061 / .s-8 oo I o 8 's -c ;;; G 1-z r o PREPARER /DATE j' ' . ID, 'Po7"70 ll 14 d(o SUB.IECT I TITLE QA CATEGORY I CODE CLASS Pu :; '"OGi'. HA (oN~t: AR,t~: " [ z~(B)lJ + 7. c,,:J] -G (4.s 14 9 '0t, -C-t- v As5 v M<:: SING Lt LA 'ita<, 0~ J)A~S. OIIJ' A ;41 ]) I #-1 pr c-~ ~ CtR..<..,;. -= )4-rr -::: 41' ; \I Assuvt ~ 1'2. c;; fJ It<:.) tJ G -/ 44B~ :n .. '~ ""' D~7'L /.15~ -= 1 f if/r1L{ 5b ""' Df>;fl- Ust CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 PREPARER /DATE '2:1. w. 'PoTTt: SU~JECT I TITLE \ .:::..J.J:--::__,r I< ~ '' t' ,.A) Cr-OR. J (S f:>.N l ~D I AI-lo.A-0 I' _J ~ ST/~.Jt uu ~ p A -n BIL L f 3 ~{u.> ~ T!fr: ft./\l'S/0 C k.. II AJC( P-e~u ·~ , usc: p~/0£ R.c>c .. .k J PA8E 4o QA CATEGORY I CODE CLASS !tiJO lw/LL ,_ lb. s E~ \"' 1\-(;.-ES i Lt s--;::-s-s-FOR i S.\"\tPtR RsrA) FORCEIYJt;orj ~55 }:6-tV. i CALCULATION SHEET A5010.61 PREPARER I DATE }), • Volfi?R SUBJECT I TITLE f \ \ ..... STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O.I CALCULATION NO. REVISION 1 t;;Boo . o 8 / s: -c .;J 0 I 0 REVIEWER I CHECKER I DATE (J;J <1. ~ 1/1~(87 QA CATEGORY I CODE CLASS ~ r" c.~", j ~~~-::_ ,, 1 ! I B/ IN'S f'f£Z.;[l..-·~ t.J ~ !J :_ru::;-~ ; '.,u/...-..J. l£L 7.J::;l I :{ ,f\: fl( ~""-,:;-e~ 0 V t--R !3 u R_D ~:.0 LoN) 51 1-:;:: :\ ARGI:+ttJ6 l'rCXAf'l . I ~"'L· 15' .oo PP-tr-v,oe-R.!?/ A.> PJ/<. C.-I /'J G R:>l< C II fl-.'-/<. Cer-N~ OtJUJ, (_ez. ?o + p A.e-ut DE As "" 0/00/:) A~ '-=' \ G I 00 Is: V:.'' ~ .... 1' "' ' - ::c :5,4] :....., .:J......t.- CALCULATION SHEET .0.5010.61 a:: )- C<( (/)~ ,_<0 wN <ll' )- _jll.. wu.. ~w VlCl: a:: )- 1- STONE & WEBSTER ENGINEERING CORPORATION .J.O./W.O./CALCULATION NO. ! 58co. o 8 -S c-ZC:> I -2 .;- <') I t/l w ~ <') ' ;:::; ~t- . - ., ·~ ' - REVIS I ON 0 QA CATEGORY I CODE CLASS u.. 1- Q._ ,_) 0 a: 1-z 0 u w ~ _j 0 a: 1-z -··o :::s::: u f2 (/) z w a_ IY w, s. ~: I z <:( _J a_ ":._'--+1----'0l u -.r- 0 1-a.. ,_) 0 a: 1-z .Q u I ( iJJWiiUUt~.~~v\L ii:·· . J; _u;>_c;_I1._2~00 __ _ CJ (AS REOD)-- 1'-0' {MIN)-1-- 11?'Q" 5tc, 51 ~i {. 1if <j, 01<AD£ 150 PC~T -TFr-t>IONlD A~HOflS WI ~Hl A liNG {NOll 41 { c• :1,_ fl) WlRf SPIRAL 12llq; x.. l2"LG ~-8 (fYP ~A ANCHOR EA [NDl _f ANCHOR PL & NUT ~ t if-1J~rn~Y~----,.-;~~~ ··:_ ~=-~,;-[<rYPEA ANCHOREA t:NDl . • jL: ~ z"~ 1.·;._, =-r-CROWN b11UI1!!NC :~-.··:_~, ._ .. , ___ .Jt·-1~-·ft .-: .. ·_ .. ., = . ' )~~-:---- --c-~- 8 {J-7) FY 2618 DRAINS FY·261A 5' 3"RA'b 1 1 (8·3){ll-4) (E-3) _ T.OCE.L 220Q'_ .. -\-:-;;--;-c\-~ _. • 4 11 \tl DRAIN':> 6'-6"RAD- LU SP ' . . .. i . --. "' . !£PENSTOCK ~------~4·: . ~-.. ~~~-\--~~\~,\- \ r UNflEJNFORCED !_CONCRETE BACKFill & p 1/13/8~ \)(,.S 4-S" -7 S S ~R \) E 1 rlt:t.- ~ PENSTOCK ~sTEEL SfTS 6 6 7 7 l_!3F lWI:_LN Ar1l.HOH'::l, 5 5 (H-21 (L-11 (I l) ?r-IU STO ex r, n c ~)~ c: (J 2) I j tA "' c \J" CD Ill .... "' Ill 0 ~ ~~ -t n r Ill c:s ,. . ...... a ~ ,, 'I \:- <::JQ, -J (") )> r (") c r )> -1 0 z (J) ::a: 1"11 1"11 -1 ~ 0 z m 0)!"'110 O !=:l:E 'm (::.) ~ gJ • I"' -i (). n m c :0 ()\.)~ ~ I :::! G> 0 -z z '·?z m () 0 ;:!! . z I G> N o IS"-o :0 (3 :0 ~ 0 z 0 =I~ II> -t Ill G) ~ z 0 :a Ill -< ' • 0 Ill 0 :a "' 0 ...... ,. I'll 0 ·f\-= II> n -t ,.. Ill LV II> (I> "' ~ ~ -J' r v ,/ =\ ~ V' I OJ 5 L() '<( . ~ ---------_ _1§~-Q~_ I L.3(H-8) ~- 2-2 CJ (AS FIEOD) } 4 c--JJ _/ EO Sf' / _/ --, ___ 3-3 !>tG' PA'-~ yS--'ls-5 ~ tl'Effi!:L f1 JrD.-B l /IJ) gg TUNNEL I 4-t!8DIAG '"----- CJ (AS f<EOD) ~ 0 "' l> 0 0 r-~ 0 c r- l> -i 0 z U) :r 111 I fTI -i >') -\ I ~ Ill CJ) (/(~ c.. ...; Ill 0 0 7':-~. -·-----. z "'~ ...... m t?:. Q!illO ...... g~ ~ n ...._ m z n CD Ill ,. CJ) -~ · r ill "'Og:ll !'-'~ C£)~ !i2 -CJ ... G'l "'<>" l 0 z ._);;: z HI :ll z G'l 0 0 :ll , 0 :ll > ...; 6 z _J 0 ~ ,. Ill 0 < ~ ,. ... Ill z G> 0 :II Ill -< • ...... Ill n ~ "11 0 0 ,. ~= Ill n ·f4. r ,. en Ill CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PAlE 1 l-t-5 QA CATEGORY I CODE CLASS T\\-b T~\) ~ T \b\...OC K TO 0 r;-vruPc Stt6fr{L R-b"~IST.pt)fr ~c; K. t:t~ c; \+OR..S It-S ~6 ~ \)J; RE"" 0 6 y SyOAJt; ft/1)0 \I\) \:iS~ tE R C: ITLCVL.It TWN IS800 . "'E-&--8 b R.-f? 1/. 1 6 A--LSO Ttl-IS '?O{tTIOI\) OF 'CI1LC /)PO().()~-5C-)bJ-:2S"' ltCC1)\)t\.)"lS Yo'L R6VI:S.WN TO il+t THfLVJT BLOC/'\: '¥-OCK EXCAVA-TIOf\l (~~A-R t.'>f5"Ttt.I:L.Ii16--) /t!UD J-JOClUDtS A-DD 'I TX:OAJ/fL. DO C\J IYt fi/IJT 11-T .r{)l1] TO 6"' V;f-L-Ull-TG"' I#~ ~~ U :t:/l.--e"ME?vVT f)F -.SJ+SI4/L AL.r:c:-rroi\J {l.&riVFOflC&:/11 &1. S \H:; ftL FR.-r:: r;-r:r:o 10 R-&-:vtO Rl fl..CGl'tt &AJ T H--A-5 £ 6" r;-/lJ PtDO SO :CN STbAD'' OF GOOArr.rAJG-OA> TltE' .S H l;-A.fL TVlMK .ST R.t;l\) G-Tt+ o P CO A) CRETe-TO C AAA'I Lb l'tiJ ..s r o T Jte KS Y&() POfL.T.t:f)l\) Clr TH-E" TI+R-OST" gwc~ .rAJ RoCk. G \-ti;7PrfL R..~A) FQitC:[;MC.NT tS tiEbr::.&-'0 Fb\L r Tl-\) D \Jo~PCSc~~ \) lt'GR-!:M~r&A-~11-RS :~tRE OE"SJ:&+J f\) FOR T!VTI\)~ Fe fLJ::N6-'rOlL-11\-R \)~ \ LO AO TO T ~ f20C K K~'{. z) 00\JJ~L ~~ A-~E \)~~:t..G-\Jh"D .. FOR \1LPti\JS r=~,oc;.. s ~AiC.r ro-f»-G WCk: NVCHOIL ~~fi SL~ A-IU() DE\Jt"t.-0\>J:~r,.. \~ Tt-+R\J£T BLOCk ~CK ~OL-T fo\<.. SL!:.O ~~fa-S\P£>1:-d TY .~SF. ~ t-uY Cf.\i..-C , ~oe>, o~-&~ 8& ~r:EV i. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION NO. I REVISION I PAll "501061 \5"~00· os -sc:-~"''-~s-1-4-G::. PREPARIR/DATE \/II/ Sl I REVIIWIR /CHICICIR /DATI 'INDEPENDENT REVIEWER/DATI 1:H\'li\J ~'-11-~c WC.ITE I M MAor:>ei--1 I 1. ~5· ss SUB.JECT I TITLE IQA CATEGORY I COD£ CLASS ?~~<;.To C K Tl-tR\.)S I ~LOCK - "0\.:: S:.:I:b-f'.-) S'rte A-~ rR..l:CT ION REitJFO~CE.fhEI\)T FOR.. T\tt l'~~STOCK T~R.IJ~T BLK. ~EQ\)r:R..e-0 TO TRFti0SFER. Tt+Rl)s I L.OttOS lo T\tt ~oc. K. . CO~CRtTE J:A)TER. t=A-GE. ~~oM ~EF. t:ALC. \S""~oo.og -& -<i?C; -REV fu. ?<;. 4-0 fuR E:tf\\:,R G Et\)t:'{ c:; ftS E \J~ (_9 ·IS" l\·l) ( 46 '+5 )) 1\~R-.J~\ \..OPdJ E'Q.\)f\LS ,..... 40't3 rz 0...-.!.--/ S"lS'+ KrPs \0\ A-\... T Pc ~'e. t.:} ~ '{ 1\1\) CltOR 5-:.:: A-t-lD t)OWElS f;Mf>. W ~01TDm .St.,A:€> :ross ~OR MAL t: P6E: Tl1 P\ 'V~\ \_0 tr\) ~Q\)PtLS -'JJI- \ 0\ ~ \A KEN 1.) '{ A-t\) c PDR.& ::: MVCl DOWE:\...~ G"M~. I A> EOTTOfV\ SLA~ \J L..r ( c .7s-CJ./)( l36z..) ~es. ~ 173"1 \<\.TPS (t!7)( :>ow) ~~ Sl!§"K 1:? 5. vLI (J ·7 )<:fSJJ O~ t &12 KIPS 'fOR-f:fV\E;R(:,-t~rc~ CASE Tltb PERJ:McTER. BARS MUST Tfi-KS J \....y 5\Slf--113 7 =-1'-trl K:tPJ oF S ttE'tttc.. (0CT.) F~ft NoR..MA-t., r::A-Se TH-6 PERJ:tr\ETbR. BftRS fV\\)ST TA-kE 1 l.::> 517 5' -= J'lg , ::: 3'5 5"7 k :r P .S oF s ~ E" A-IL (_ IJLT.) so t>E; s r.&r0 ~ PG"~:rf\t~b"R BA-RJ TO lA-t"(; 3r~7-K ~A~-l«:R.W't .. A1£b CD~~ A \>OLOE:W TO T A\<~ l7~7k.J;PS. -~~R&G"A)C'Y CMG" CD'l)Tf(.Ot.S \.JS E: ~5 Fe(l.. \:>0\.QEiU A-~0 P£CL..:z;n.t6T6't B 11-U r AU..oWA·~ LDAil P6fL @J\1L l31t;;!(20 ~1\) ~~ P~Io'\J)>t.ti:?J~-BJ sEcn::oN ll.7.lf. --:::; 'fl\-A-vf-ty..u., U)JtER.~ Vu=-~Vri) so \lvj~ll R.. = 0· ~~(rJ·7'1 ){'D) ( I·O) = 4-0.:l.q k/Sp,R.-~~~ M~c+n+rc FitJ:tT ~E~Etc:~ ~ gea'o == 3 ~{~6 = €8 .3 -IJsr q, Blfi-.S. _ 9, • 1trt :? \RotUS'' oF 3~ -!f:l CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 \) £ \J~LOPEM6~ I SLJ'T~. PrCI \~, ~ .~ REVISION QA CATEGORY I CODE CLASS DP BA~:t. c Dc'JELOPfYl E=.AJT t£AX,-Ht = o .oy.Ab Sr.j / V+e- -::-~ -ol..f[7tt) r,.o_Jooo 1 ~ «+ooo = :,o 11 ~ z-~Fr \),5 E"" Cff) 0 H00 \( A-C"I:-\ 'l s-.). ~ 11-.S.JC 'D E\fELOPMe~T L.. E)\rl7 T tf-::-..fh ~ == 0~ VJE"Ls wrrt+ C(O() Hro K .. = J;(()o(t.oy1 ~ --/q J' D £II ELOP ~flf G1J r 0 F "). FT L-OP H STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET J.D./W.O./ CALCULATION NO. REVIS! ON PAGII &5010.61 \sgoo.og -sc-?.Gl-J-5' ' 1.+9 QA CATEGORY I CODE CLASS l 5-0 5-o .I I ~ ) -:1. ........-- = I Q L Q t>r; I :::t' I I 9 ·:r .------.-... -:-----...-----------~-- I I :: 0 0 • I .T I 7 0 t:= -,.-~ _j .. .------ l '+l 11 J. I II I ,, I '+'-o'' I . -o z.-o z'-0 I I I I , 7 ._r:) ,. I tl 7 -o LO \... 6> ,. !o'-O I I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 QA CATEGORY/ COOE CLASS #II? [3.?-L.G-T~ vr.~~ • "ll' 1'0 tot,, LJ:.~E A I ~'M -~ E'TEP.. ~ ~<\1 TO COL t;rA>€ A ~- ~" -~-bC"K r SUPPOI'-f ,rr 6. u 3. se.ns ArJT A$41'--i E'. D FAit...4r2E ,, . -~--PL.A.~--t E \o·,o ~ ' '1._ ... h~ ~ J - ~1'-0'' .:.._ ~~~" ~ -TYf ~l~/1/:;z;\ \\ I'"' 3'(C\.-"' nt'l ----r--- ' . ..,.. ~ \ ·1 ,, :-"3-~ r ~\.. ,-;.o / ' -CJ ~ -I -~ ~ P~TOC --./"~( T~c ------------ ~I!~ .~\ ~. rn\\ [tll( (~II ::::11 !E I\\;; /I ~, .... ,... ~ -~ 1.. \0 O· l.(-0 ) \'iiillljil '! ==· ~/ f--t: 'J. •q( ' ·~" ~ . -_,_ ln1 tllf:?O 'FAILUI<.E t-/~ --~ , i ...... ' . -~ rEL J...~ PLANE" ~ .. • ~ Jl.~JJ i =~ \\:: rr=-\\\= '/: 0.\ '{!~\"'; '\' II ..,). f>~E '' -ig,) S\..-1'\-S ,~.--:.--......... ... ~ ' \o \)0 !? .s ~ \G • l'-e' "h~ r ~g @t~ T :1> B ~ J lg '-!) •I 1 , 1 -1 CALCULATION SHEET Q _, - STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULATION NO. REVIll ON PAGE \S8oO·o8-c-abl-AS' I 50 1-1. QA CATEGORY I COOE CLASS \ t\ 6"1.. 'l$ ,f) "\) ---~~ '\"}~ J'-~g> !rT r;;q si>c. lr\..(_ 1'\ f£.0 \.) "-) 0 . 3\f / lg tf A".)GitOIL W SLGt-l)bJ 3 1-. A-1 e;:-q <;, PG. EL \S'-o'' 3 ?-. # ffs ItT el{ ~Pr;. At.-l ftlLOVAJC . CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I .J.O./W.O./CALCULATION NO. !REVISION I PAGE ... 50,061 ~~DO. ew-s c-"J.~ 1-~s-1 51 PREPARIER/DATI£ \ /l'l.j~~~ REVIEWER/CHECkER ID/-.TE liNDEPENDENT REVIEWER/DATE 'D~'l:tO ~L.~CF.TTE 'I M MA.t>D;;;t\.1 I I·'ZS· 02' SUB.JECT I TITLE I I QA CATEGORY I CODE CLASS \'f\f\ \\)1 FOU) TAA\lS T ~LOCk: l>E.SIC7tJ S\it:I\R '\=~C.T:t:O~ RE:J:A)FOR.CEMeAJT R.9R. lij-E' 1}141UIFOL.0 T\-tR\)~ T ~\...K, RCQ0.IREtl 10 TRAIVsFER lltR0~ T L.O~OS. TD THE '¥-.oC\'<. C:OA)CR.E:TE" :t:IJTeRFifCE. ~\:::. F . CALC. lb€OO.ocz-G-<g" -R-EV ln. ~ 3i? R?R .\\JO~M~ '9\&E: _...,. ~ K \}L,\ l;i c .5"&'35') T\\-R\)~T I_OA;Q 'CQU~ 3S \)6S,~ ::'¥ qq zo \'( 'SPJ Tt>\Al... TIH<.Ef..) BY Pr\.)~r\Qfts ..... A-00 t>O~ELS E'fflf>. r.~ BC>TlOJ\..t SUH3 T D T A;., TAi<El\) SY AtJC~~ ...,.. 4 )8 Ar'J/0 DOtDEL.S G{'rtf3 . .rN PJJJI()lt ..SUUl 1·7 Co) C) ~ -/S(I-7) [77'+0) .=-'f$>b1 kJPJ 0 ·75'(!·7)( 'f1'il) S'£'Cj KT€;. fO~ ~~At. CASE T 1ft f>ERJ: ME 'fER. &lR.S m o~ I T !1-I<E J '---==.;. 1'/'L()-0 · :: qtj~O KIP! (OL-'f·) 'foR '6MER.&EtVCY CAS& THE PfRIM6fER F?Jfil0 M05T TltK~ j Cf .f'f/( -~!>!:( = q 3 iO KrP!. (. \X.T-) SO UE5l:GrN ~~MtTE R 'Of\'fl~ TO TA-KE. q q~O k.IP..s fJO~At-C45 r;-COAJ~t,J ) ~'tlt.LS TO TA-KE 55'/ KIPS f:711(~cY Clt!ii"' C011)TftOL.S A\...LO\.O~LE. LOAO ?(?((.. ~A~ ~A-SIS'~ 0 t\) s H-EITR r Fll-J:CT~DAJ .. ,/tCI-318-s:J 5 tiC rr::o A) II 7 ·lf = \l' (\ :=r A'4-~ :t .u... '1\l \H?fR€' V u = f!! '1/ t1 .) so '-~"/BAR. ~ D -~{"(e-7q) (G,o)(t·O) = LtD·;J.Cf k/BJtR..· -woAJ M-OII.JOLJTI-T.JCC!lt. ~/&l'tF-::: 0 -€S'(o:JC1)(b0)l\·'f) = !;C,, 4--CONCiLI?Tt ~O.QCQ71f1C ct. q ~0 K . t:o~G-AC"'*-etl t'!;tl..Ift\ET~R ~AAS. RE£1't> -'5'fc.; -l7 C. Bfti'-J -tv.otvo~:2~J:C s-~q ~ m MAJJ~ ) ~O\Jr;E ()0\).)E\..S RE'l{O :::--Jl+ B~. t::.E6: ~6:XT P<:r. 40-2C{ (to4 SAle~ f~IOE"Q 'M,t-.1.) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVIS I ON PAGE &5010.61 5;2_ QA CATEGORY I CODE CLASS t:.A-LC. 'NE.::.\:&\tT oF ROC\<. ~0\fE fttvCitO\\. ~LOCK. CQA)S.J DER A-S A ?ERMM0St01 COtv\?R.ESS:.WIV FOR..CE I)) H-J:C rt W~LL R.E"\J \)Cc TH-E A-'M-0\}NT OF ?t:;D<JMEtER.. SitE.+£ 8Jt~S R.~Q\):t=REO. b"SI.IfAJrn; ~Ck W~:t&HT A-BOVE" ~ OF TUAJAI~L POfL J.JJ Fr \).)r Dltt OF ntt.bST 6LOC K A-.s · c~l--'0 -Et :JS ·5') c :~.ol -± 1r g <-J 'f.S9 FT (./)0 "'IPTl) l;; -= ~Lf g I< \)55 TOTA-L CJr \>~~tv-'OTE\'L bt\IL g \.t'6 ;:: t 5"" (bl't:fl. 5J·-'t 17c..,-/~ -j (./ $ 8 PGA~METri~ B~S i SEE" D~TA-.JLs FoQ.. f'DUITL DeSr.&-tv. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .... 0./W. 0,/ CALCULATION NO. REVISION £5010.61 \s8oo.og-sc-l(;l-;{~ 1 QA CATEGORY I CODE CLASS --I~ ... I \ ----+-~ _, ~ 0 \ ...a .. t-... -;. 0 I -"-'' -• I I I I --i ' v ,, 4-..0 tl-0 II '6'-o ,. 1? {-e I\ to '-o •' to '-o I' .....-l<J- ?LJ\-N MA-N:CFOLJ) T~~\)ST BLOCK 5XCA-{A-"TI:C>"-> '\\t.r. CA-LC. \SSOO .b~-& -<?b -~E: V 1 CALCULATION SHEET I J.O./W.O./C:ALC:ULATION NO. I REv•a;oN I PAGE 54 &5010.61 \5~~· o~-sc-~ bl.-~~ STONE & WEBSTER ENGINEERING CORPORATION PREPARIIt/OATE i/1~/K?J IRIVIIWU/C:HIC:KER/OJTI I INDEPENDENT REVIEWER/DATI ''DAVID "P.LJJ.NCHETTe M M.lOOt=N 1. Z5. as SUBJECT I TITLE I T QA CATEGORY I CODE CLASS N\ M:)J:FOUJ TI+R\)ST \:,LOCK. 0 r: 'I ...) '::: ~ n ':....:J '-" - ~ 1 " .J (V\ -IJ) <C .,.,. )'""' ,_ ~.... ""' .... - ! ! ~ I.J.J= ~ ! "'Q:) ~ -.c<rt: c:r (Q...J ~"" \1) -~ - - \I) I~ I 'J- .Ji) .., .... -i'" • - c ,... "' \ T I L i -0 ,d I -~ 'M .,.. 1(1 g .,. ~ ·o \1) "" . .. ... . .. (t 0 "" --'!. 4:. "' ··o I ~ ~ 1-.... "' . ~ "' ·~;\ "' s , j ' \ ~w .. " I I ~1~ J ~tu. ~ . (""( \-'::1 u.. ' It '0:' \ c:r-\,.l) \6 1/:1 ~ b a.. ~ ~ <:r -=-.... .,.. c -· ,.... c=J·2? v I .( n 1 J I 00 ~ u u I :;: 'C 1..1\, ! -~ f IRA t. I ·' i• .. :s:>' lf r too <-'p. ~/ ~f r '="" :\11 1?-<'S' r ~ ',li:. ~ ( .. "" """ M ) o::r- ~ ........ ~ ~ / lXI A ~ .... r -'f ~i - I <t I -;:.w 1-- ' ...... I 1-tij ...... 3:.J ~~ CALCULATION SHEET \ /tl./8'\ STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVISION PAGE \S80D.og-S G -2b 1-~ r-ss QA CATEGORY/ CODE CLASS l.oc:A-TE AT H-J:G-H-POJ"A>T er TH-W5t ~LOCK &XCihTitr:J:<)IIl 1 ll 3 -" L~~ (T~l>) 1---1+--11+--c J JT5 RE"CiO· i SBoo, o8/ r-c ,z e:. 1 -2;::-<\_~ __ .;.:~. '/ ~ Crmcrl!.fe ])ec. 191>7 f+-r.-/t-().; Ai J ... D~sign of end-blocks for post-tensioned cables In the following a detailed description of the method of design of end blocks for post-tensioned prestressed concrete beams due to Zielinski and Rowe is given. Use of the method is considerably facilitated by design curves and a table prepared by the authors. and the application of these aids is illustrated by means of a worked e:tample. U:-ITIL ltECE:-:TLY, the dcsi!!n of end-blocks for the an- chorage or post-tensioned-cables has been largely empiri..:al. Many theories had been advanced but none h:~d re~.-cived completely satisfactory experimental veri- li'-"ation anc.J most were difficult to apply and clumsy in usc. However, the work of Zielinski and Rowe in 1960 and 1962 produced extensive test data. and a din:ct method of design based on these tests has now been devised. r 0 Two important aspects affecting the design of end- ' . hlocks should be noted, namely, that the gre:1test pos- . . ... ible load en never exceed the breaking load of .the t.:ndon (and in pmctice should never exceed S.S per cent of th.: latter load), and that the complex system of stress in an end-block modifies the tensile stress-stmin relation- :;hip of com.:rcte so that the ten:;ile stmin :ll whi<;h crack- in!; occurs is gre:llcr than that in ordinary bending. The jl\!rmissiblt.: tensile stresses can therefore cxca."ll those norm:llly used in prestressed concrete design. The im- port:mt criteria to be considered are the compressive :>tn.."S.~-s in the concrete immediately behind the anchor.;. and the bursting (tensile) stresses and forces induced by the conccntmtcd loads. The fir.;t of th'-':>C is t:tkcn into a~:~:ount in the design of the anchors. Most maker.; specify a minimum cube-strength for the concrete and a minimum sp::tdng for the anchors, and these should be carefully observed. However, the safe compressive stress h.:hind an anchor en far eJtceed the cube-crushing strength. Zielinski and Rowe suggest a maximum value ,,.-I·'J times the cube-strength, and the writers have witnc:>s~d tests in which the compressive stresses at failure were up to four times the cube-strength. Hence, if failure ,x:curs due to simple crushing of the concrete around an anchor. it is invariably caused by bad com- p:1ction. The sm:lll helix often welded to and provided with the anchor gives an additional factor of safety against had compaction ·by provilling r!!sistance to the _ ltl\:al strcSSt."S in the concre!e dirc.:ctly be::inc.J the anchor. ·· d~s not form part of the end-block reinforcement. }· hcrefore the calculation of the bur.;tin~ (tensil.:) forces -:tnd the determination of the corn:t:t amount of the reinforcement to resist th'-"SC ftlrCo."S is the only problem that c,mccrns th.: Jcsi!mcr. Zielinski and .R.owe~ crried out two series of teststll, fr,ml \\ hid1 a method of Jesi~n was SU!:!l;'-"Sted, bascu on Guyon·s assumption!=> of 'symmetrical prisms'. This is basic to end-block design and the detailing of the rein- forcement, since the maxim 11m tensile stresses invariably occur along the line of action of the· applied load. Reinforcement must therefore be provided behind each anchor and within each sepamte 'prism' to resist these stresses. Jn the tests. the ma•n variable was the ratio of the loaded arc to the :~rca of the end block, and the maximum tensile stress and total tensile force were expressed as a function of this ratio. Design method Selection of prisms A st~tmrc anclwr of sillc :?a, is ao;sumcd to act on ;• pri5m pr "ilk ami dsmh 2q. The dimension 2a1 1s equal to the :;i;r.c of the propo:.cd anchor, and the dimension 2a is found by inspection; it is usually as- su•ncd to be the distance between the centre-lines of adjacent anchor.; or twice ::u: djstjlncc; !?etw;co 1 he cc:otrs-line of the anchor and the eyge of the concn:u: whichever is lcs.o;. Examples are shown in Figurf! I. Similarly, a rc.:ct~ngular anchor with a dimension of 2o 1 by 2h1 acts on a rcctan;~·llar prism of cross-section 2o by 2b. In this case two ratios u1/u and h1/b ~::m be computed. giving different t.:nsile forces in two perpen- dicular .directions. Similarly, the prism will have a. theo· rcticl uepth of 2a for tension in one direction and 1h lor tension in the direction pcrjl\!ndicular to the former. Circular anchors arc assumcJ to uct on souarc r>nsms, in· which 2u, · · v arc-.1 of anchor face. - / I" -.· .... ~ ( ~ , . • Ues1gn approach Fpr ~ch prism,/. = P/ A •• in which/. is the uniform direct stress in the prism; pis the maximum erestressing ~; and A. is the cross-secuonal ar~ ol the priSm minus the area of the duc:t. The maximum tensile stress in a. direction normal to the centr::U a.xis of the prism and par.lllcl to o1 (or b1) Ciln be c.."tpressed as[.= Dj.. and '::£ the total bursting tensile force Ciln be expres.'>Cd as 0·1 F"- T =-CP, in which D and C are parameters which vary with the ratio otfa and which have been determined b) tests (Figur~ 2). Q z~c------~----~--­ ~ The distribution of tensile stress in the lon!.!itudinal •J direction (along the depth of the prism) can be 'approxi- m:ated by a triangle. the leading dimensions of which are :; shown in Figure 4. If a permissible tensile stress is speci- . tied then the theoretieo~l length requiring reinforcement can be curtailed as shown· in Figure 4. With the concrete ::l thus resisting part of the tensile force, the tension T, to J be resisted by the reinforcement !s given by -1. T.=ii-(~YJ (I) in which fe. is the permissible tensile stress. . 0 0·3 s -t----+---i----tl·:) .. 0 o·;, Zielinski :md Rowe found that the strains which occur in end-blocks prior to cracking correspond to apparent tensile strengths in excess of the splitting tensile strength of the concrete. The r.uio of apparent strength to splitting strength is a function of the r.Hio a.fa and is denoted hy the coellicicnt K (Figurr 2). The pcrmis.'iihle tensile stn.-s..'i f, is therefore assumei'fto be equal to 0.8 Kr, in which r is the tensile splitting strength of the concrete. Tensile stresses g~ter than f, must be resisted by the reinforce- ment, at a working stress/. of 20.000 lb. per sq. in. for mild steel bars or 30,000 lb. per sq. in. for hot-rolled deformed bars. The a~ of reinforcement A, required in each direction, in any prism containing a single anchor, is T,/j.. Figure 2 Values of coefficients B. C and K lor various values of r<ltio a 1/a. Figure 3 Areas of reiniOfcement required lor particular valuH of p and ada. · Tensile splitting strength It is not yet common practice to specify a tensile ~-~!----!+-­ splitting strength for concrete. and the designer must usually relate his figures to the cube-crushing Streng'"· Unfortunately, the relationship between tensile and CC' • pressive strengths Cilnnot be accurately defined. How- done during C.''(pcriments at the Cement and Com .:te HI---+-+~' ever. Dowrickt'll ha."' plotted the results of controlled : · I Association, and concludes that (with the types of cement " • and aggregnte used in these tests) it is safe to assume that for a cube-strength of 5,000 lb. per sq. in., r is 400 lb. per ;:;- sq. in. and for a cube-strcngthof9,0001b.pcrsq. in .• ris :i 600 lb. per sq. in. f ntcrmediate values COlO be Obtained by linear interpol:nion. The relation r = o .. Su..-1 ~. in which u ,.• is the cube-strength, has been proposed by the Depart-lOt----'-t---....,---......... =:-:::-"'""~-_,..o;:---..,..:r ment of Road Research. -' ... ... VI Design graphs ... Substituting the valu~ of T.f, and/. in 1\mnul:i (I) to 0 gi vc T, and l his va I U\! a nJ [. in I he .::t prt.:·ssion ..1, T,.'):. -11 o A,= ~[1-(0·8:;A~ )1 . (2) Assuming suitable values for r and[.. it is pns..sihle In plot a family of curves relating the area of rdnfurccn-n.:nt ) to the r:uio a 1/tz for particular values of P and, since the coefficients C, D ::md K all depend on a 1/tt, the only remaining tmknown is A •• Fortunately, for any particular 0 0·~.)--~.0~.~.~~~G.~,.w~~C~.~~~~~~~--~~ VA.l.U~S OF a,;a 4)2 Concrete December 1967. .. -I· .. l ' ... • prestressing force there is lillie variation in the sizes of anchors. and the value of 2a 1 for any prestressing force is practically constant. The curves in F(r;urr-3 have been \.":llculau.'d for square prisms, but they may also be u~t.l for n:ct:1ngular prisms, for which the results will be slightly conservative. The graphs arc based on the as- sumptil.)ns th:u r = 450 lb. per sq. in., and j. == 20.0CO lb. per sq: in. The values of 2a1 and the areas of the ducts for various prestrcS.'iing forces arc shown in F~t:rm.-1. V:1lues of K for ratios of a11 'a exceeding 0·7 have been obtainet.l by c.'ttrapulation. Jn practice, the absolute maximum value of the rc- stressme: orce lor anv anchor can be assumed to be 8?, per cent of the eu::~.rantecd tensile: stren!!th of the tendon. Values for the various tendons commercially obl:lm3ble :J.re given in Table 1. Table 1 Maximum prestressing forces for design of end-blocks Wire Tendon material large diameter strand Multi-strand cables Tendon composition 12 No. 0•276 in. 24 No. 0·276 in. 1 No. 1i in. 7 No. 0·5 in. 12 No, 0·5 in •. 7 No. 0·5 in. (D) 12 No. 0·5 in. (D) 7 No. 0·6 in. 12 No. 0·6 in. 7 No. 0·6 in. (D) 12 No. 0·6 in. (D) 7 No. 0·7 in. 10 No. 0·7 in. D denotes 'DYFORM' strand. Maximum forea (lb..) ( 85 'lC. of tensile suength) 136.700 273.400 157.250 220.150 3n.4oo 285.600 489,600 303.450 520.200 386,750 663.000 493.850 705,500 Ultimate-load conditions n..,.,.,,H,/i111'i IJ. -.,'].A; The fore~toin~t considerations relate to conditions at working load. ttis al!'lo n\.'CCll!';;lry to ensure that ullimate- loau cumlitiuns arc s.~tisliu.:tory. that is, that sullicicnt reinforcement is provided to resist the tensile forces inuucetl by :a load equal to the guarantcetl t-.:nsilc strcn!;th of the tt:mJ.on multiplic\.1 by a suitable loat.l-iactor. A value of 1-1 f~~r the latter is SU!.!2L'Stct.l. :u1u the ~tress in the reinforcement mu::.t th~:n n,;j c~~:cct.l the vidd stress. Additional tensile stresses arc also produc'cd between the :mchors nc-.1r the loat.lct.l !'a~o"C. the m:~l!nitudcs of these stresses Jcpcnuing on thl: loat.ls. the uiStam:es between the anchors and the shape of the end-block. A precise determination of these sti'CSSI.'S ~:an not _be made. but they can be allowed for by providing ttie reinforcement for each separate prism as near as practicable to the face of the end-block. These tensile zones are not the same :l.S those suggested by Guyon as arising in prisms subjected to partial resultant forces. Example Cl.)nsider the case shown in Figurt: Ia, that is, a prism 7! in. squ:-.re with ::~.n anchor having a flange 6 in. square. The duct has a diameter of 2 in. The value of u is assumed to be 6.000 lb. per sq. in. so that r is 450 lb. per sq. in. Titc cable comprises seven !-in. srrands. P =-7 X 37.0CO x 0·85 = 220,0CO lb., assuming the strands have a tensile strength of 250,000 lb. per sq. in. a 6 ' ...!=-=0·8 a 7·5 -~ ~- Area of duct = :r x 1 (from Figure J) = 3·14 sq. in. . A. = 7·5: -3-14 = 53 sq. in. p 220.000 . J. =A.= -5 ,r.-= 4,140 lb. per sq. 10. j. =-' B/.. · 0·34 X 4140,..., 1,408 lb. per sq. in. and occurs at a distance of 7·5/4 =-" 1·1!7 in. from the face of the anchor. T 'CP. , 0·15 >: 220.COO ..., 13.000 lb. . f, -"' 0-S Kr ,. ' 0-g X l-52 /. 450 ,...., 547 lb. per sq. in. No allowanc~ for the ~rea ol the. duct need be m~de T, = 7ll _ (j,/J:)=J Allowance for duct when calcul:llm!! the ratro a,;a but m order to determm~... ,;,. 33,000(1 _ (547 /1,408)=] = 28,300 lb. 6 the are:~ of duct must be deducted from the area of the prism. For an ordinary plate anchor, the diameter of the duct to be incorporated in the calcuhuion is th<Jt ;u the point of maximum tension, th;tt is, at a distance of ia from the face of the anchor. However, many stranded anchors embody a metal tubular unit and the force is transmitted into the concrete by the combined end-plate and tube. In such cases. it is therefore allowable to :tdopt the diameter of the sheath as the dimension to be used in do::"Sign. Figure 4 Approximation tor distribution of tensile stress in longitudinal direction. 28.300 ... . I . Hence A. = io.ooo = 1·4-~. sq. sn. t 1s not necessary to m::tkc the preceding calculations in practice; the same result ( 1·42 sq. in.) is simply obtained directly from Figur~ J. Provide eight 1-in. bars (A, = I· 38 sq. in.), that is, four bars at each side (Figur~ .5). ::1000 ... .. -.. ... z Figure 5 1 .. · · ; Ultimatti load • ' ' 1 ~--· · Qcsign force in strands= 7 X 37,000 x 1·1 = 2ll5,000 lb. • U!timate ten~ile f~rce = 0·15 X 285,000 = 42,600 lb. Y1eld stress an reinforcement = 40,000 lb. per sq. in. Hence A, = 42,600,-40,000 = 1·06 sq. in .• which is Jess The reinforcement should start as near to the anchor face as possible. TI1e cover at the end of a beam is not a problem :ts the :tnchors :tre normally set in recesses, which are filled with mort:tr :tfter the stressing and grout· ing are completed. . )'-than that required for working-load conditions • Length of end-block For beams less than 4 ft deep, it is usual to make the length of the end-block equal to the depth of the beam. The end-block then forms a 'deep beam·. In the c:1se of an 1-beam with a rectangular end-block. the 'beam' spans between the top and bottom tlanl!eS. Zielinski and Rowe found that }n end-blocks with a i'-"ntio of depth to length equal to unity, a tensile zone occurs at the junction of the web and the flange, and that this tension is 70 per cent of that at the anchors. This tensile zone occurs at the same distance along the beam as that produced at the anchors. In practice, an area of reinforcement equal to 70 per cent of that in the end-block is provided in this zone, :tnd as large a splay as possible should be provided · at the transition point. For deeper beams the ratio of depth to length is almost always less than unity, and ratios as low as G-5 are common. Practic:1l considerations and concreting pro- blems usually determine the length of the end-block. Short vertical cables c:1n be used with advantage in some c:1ses, providing considerable savings.in concrete. Reinforcement detail The following matters should be considered \'•hen detailing the reinforcement. Each prism must be adequately reinforced and the reinforcement so det~led that all the prisms are con- nected. This naturally leads to the use of rectangular stirrups, or layers of welded mesh spaced out from the end of the beam. Separate mats of reinforcement placed behind each anchor are not sufficient and should not be used. Welded mesh reinforcement should preferably be used. It is es.<;cnti:tl th:tt the concrete is well compacted; it is far better to use :tn under-reinforced but well-compacted end-block than to produce an over-reinforced detail which cannot be efficiently concreted. If the reinforce- ment is congested and adequate compaction is difficult to ensure, it is often practic:1ble to precast the end-block since it c:1n usually be concreted more easily with the anchors placed face downwards. While it is preferable in theory to group the reinforce- ment more closely around the point of maximum tension (at G-Sa from the anchor face), in practice it is rarely possible. The spacing is determined by the minimum distance between centres consistent with good compaction of the concrete. ., Conclusions The curves reproduced in this :trticle enable the designer to determine immediately the amount of rein- forcement required in the sep:~rate :~nchor.1ge prisms, as required by the Zielinski and Rowe method of calcula- tion. In some cases it may be impossible to produce :1 practical detail and also provide the c:~lculated :~re-.1 of steel. In such cases the designer must do his best to provide a." much sh:d as possible. bearing in mind th:ll the over-riding criterion is always to have enough space to place and vibrate well-compacted concrete. Bibliographical references I. ZIELINSKI and ltOWE. Rese-.1rch Reports Nos 9 and IJ. Cement :tnd Concrete-Association. London. :!. GUYON. Pr~:slr~:sgc/ Cunc-"t~. C.R. Books Ltd. London. 1955. 3. oowRICK. 'Anchorage Zone Reinforcement for Post· tensioned Concrete'. Ci•·il Engin~~rin! and Public Works &vi~w. Sc:ptcmber 1964.9 Conference on prestressed"t!oncrete pressure vessels SIXTY·TH REE papers dealing with most aspects of the theory, properties, design and construc:lion of prestressed con- crete pressure vessels were presented at a conference held in London in March last and sponsored jointly b.y the lnstilution of Civil Engineers. the British Nuclear Energy Society and rhe Joinr British Committee for Stress Analysis. Allrhe papers were concerned with pressure vessels for nuclear-power stations; it appears that no other com- mercial demand exists at present. In view of the large number of papers, the time available for discussion of each was exrrcmely limiled. and rhe v:~lue of many of the contributions will become ap- parent only when the complete pro- ceedings. including the written contri- butions, are published. Nevertheless, the 434 information included in the papers is of quite outstanding completeness and thoroughness, and constilutes an in- valuable guide to present-day pr.1cticc and problem!>. The p:!pcrs were group<.'t.l under the following headings. Review of current pracrice. Design philosophy. crircria and safcry. Properties nf materials: concrete; pn:srrcssing srcels; prestressing rendons. · Design and analysis of vessel SlructU res. Models: <:omparison of theory with experimen al results. Sln:M conccntr.11ions.. ln!>trumcntation and commissioning. Liners. Insulation and cooling systems. In addition to the presentation of the papers. visirs were paid to the Dungc· ness. Wylfa ana Oldbury-on-Severn nuclear-power stations, and to labor.!· tories. including the Taylor Woodrow Construction L!boratori1.-s at Sourhall. the Central Labor.11ories of the Atomic Power Constructions Consorrium al Heston. the Ccntr.1l Elcctricirv Board's Llboratories at Le:uherhead' and the new concrete Jabor.1tories of rhe Im- perial College of Science and Techno· logy. London. Concrete December 196 7 · II -~·A+ ( ' . '-·· --.Rt DYWIDAG Threadbar Postte~sioning System Pine V•lley Creek Bridge, CA. DYWIDAG Cast In PIKe Segment .. Conatructlon l 2 ' .. The components of Dywidag Threadbar System are manufactured in the United States exclusively by Dywidag Systems International. Used world-wide since 1965, the threadbar system provides a simple, rugged method of efficiently applying prestress force to a wide variety of structural systems including posttensioned concrete, rock and soil anchor systems. Available in %", 1 ", 1 V4" and 13/a" nominal diameter, Dywidag Threadbars are hot rolled and proof stressed alloy steel conforming to ASTM A 722 . The Dywidag Threadbar prestressing steel has a continuous rolled-in pattern of threadlike deformations along its entire length. More durable than machined threads, r the deformations allow anchorages and \ ;ouplers to thread onto the threadbar at any point. The strength of the Dywidag Threadbar anchorages and couplers exceeds the requirements of ACI 318. Test reports are available for the main components of the system. ·Conforming to the requirements of ASTM A 615, the threadbar deformations DYWIDAS develop an effective bond with cement or resin grout. The continuous thread simplifies stressing. Lift off readings may be taken at any time, and the prestress fbrce increased or decreased as required. The Dywidag Threadbar System is primarily used for grouted construction. All components of the system are designed to be fully integrated for quick and simple field assembly. Sheathing, sheathing transitions; grout sleeves, and grout tubes all feature thread type connections. Placing Dywidag tendons is simplified through the use of re-usable plastic pocket formers. Used at each stressing end, the truncated, cone shaped pocket former can extend through or butt up against the form bulkhead. Available in mill lengths to 60', threadbars may be cut to specified lengths before shipment to the job site. Or where circumstances warrant, the threadbars may be shipped to the job site in mill lengths for field cutting with a portable friction or band saw. Ti.readbars may be coupled for ease of handling or to extend a previously stressed bar. Tendon Assembly with Bell Anchorage ....... . r ~~ . . . Threadbar Posttensioning System Prestressing steel properties Nominal Ultimate Cross Ultimate Prestressing Force -(kips) Minimum Thread bar Stress Section Strength Weight** Elastic Diameter (fpu·ksi) Area (lbs./ft.) (inches) (Aps·inches') (fpu A ~~e) 0.80fpuApa 0.701 .pu Aps 0.60fpuApa Bend in~ Radius ( t.) ~ 157 0.28 43.5 34.8 30.5 26.1 0.98 26 1 150 0.85 127.5 102.0 89.3 76.5 3.01 52 1 160* 0.85 136.0 108.8 95.2 81.6 3.01 49 1 Y4 150 1.25 187.5 150.0 131.3 112.5 4.39 64 1Y4 160* 1.25 200.0 160.0 140.0 120.0 4.39 60 1% 150 1.58 237.0 189.6 165.9 142.2 5.56 72 HI 160* 1.58 252.8 202.3 177.0 151.7 5.56 67 *Grade 160 Dywidag Threadbars available on special order when lead time permits. **Prebent bars are required for radii less than the minimum elastic radius. Steel stress levels Dywidag Thread bar may be stressed to the r;--~llo~able limits of ACI 318. The maximum ").~ jackmg stress (temporary) may not exceed 0.80 '""· and the transfer stress (lockoff) may not exceed 0. 70 '""· ( ACI 318 does not stipulate the magnitude of prestress losses or the maximum final effective (working) prestress level. Prestress losses due to shrinkage. elastic shortening and creep of concrete Plate Anchorage as well as steel relaxation and friction must be considered. The final effective {working) prestress Ievel depends on the specific application. In the absence of a detailed analysis of the structural system, 0.60 '"" may be used as an approximation of the effective (working) prestress leveL Actual loss calculations require structural design information not normally present on contract documents. Coupling r ----------~ · .. :: .:---·---------:-· --··· ..... :. . -·_: --: --··· ----..:-· ··--·. ·----.. ..:::... Maximum Threadbar Diameter (inches) 3/4 1Ya I 1 Ya I 1l/,a I FAa J I 19/ta I 19Ae I 3 4 .~-DYWIDAG Posttensioning System Details ( __ . DYWIDAG Beli Anchorage DYWIDAG Plate Anchorage DYWIDAG Coupler DYWIDAG Tendon Assembly Pocket Former (reusable)r + d * Grout Tube Plastic Nut~-­ (reusable) STRESSING END ....... '.::.··-· ··--=. -.. B4- j ( J ,/ I l l (_.I Anchorage Details Threadbar Diameter o/s 1 1 V4 13/s (inches) Bell Anchor Size 3V4 {II X 1 Y2 5V2 ~ x 25fs 63/4 0 x 25fs 73/4 0 x 3Vs (inches) Anchor Plate Size• 3x3x 3/4 4x6Y2 x 1V4 5x8x11f2 5 X 9Y2 X 13/4 (inches) 2 X 5 X 1 5 X 5 X 1 V4 6x7x1V2 7 X 7Y2 X 13/4 Nut Extension a 1 9/16 His 2V2 2 3/4 (inches) Min. Bar Protrusion • • b 2V2 3 3Y2 4 (inches) *Other plate sizes available on special order. • *To accommodate stressing. Coupler Details Threadbar Diameter o/s (inches) Length (inches) c 4Y2 Diameter (inches) d 1Y• ' *7Va" long coupler available on special ordef. Sheathing Details Threadbar Diameter o/w I (inches) Thre?dbar Sheathing O.D. 1 (inches) Threadbar Sheathing I.D. 3/4 (inches) Coupler Sheathing O.D. 13/4 (inches) Coupler Sheathing I.D. 13/a (inches) Pocket Former Details Threadbar Diameter o/a (inches) Length (inches) 4 3/4· Maximum Diameter 3Y& (inches) Coupler Sheathing Coupler 1 5Y2 2 t 1Va 1 V4 2 3/4, 23/a 1 7 5Va 1 V4 63/4* 2 3/s 1V .. His 15fs 3V4 2Ya 1V4 8 6V2 , Grout Tube \ Grout Sleeve Sheathing 13/s 8 5/s 25fs Pis ' 2 13/4 3 3/4 33/a 13/a 8 5/a 6V2 Bell Anchorage FIXED END ( / d = Total tendon elongation. ( 6 Stressing Dywidag Threadbars are stressed using compact lightweight electric powered hydraulic jacks. Easily handled by one man, the jack fits over a pull rod designed to thread over the threadbar protruding from the anchor nut. The jack nose contains a socket wrench and ratchet device which allows the nut to be tightened as the threadbar elongates. The magnitude of the prestress force applied is monitored by reading the hydraulic gauge pressure and by measuring the threadbar elongation. The elongation can be measu_red directly by noting the change in threadbar extension. Also, a counter mounted on the jack records the revolutions of the anchor nut which is a direct measure of the threadbar elongation. Stressing Data Jack Capacity {Kips) 60 150 250 Jack Application !Sfa f/1 t ,1Y•0 1Y•, 13/a (II a (inches) 73/.e 8% 11 b (inches) 3Y• 4 6 c Min . (inches) 24 26 30 Weight (lbs.) 50 80 100 Grouting Grouting completes the in~tallation process for posttensioned concrete construction. The grout is important in protecting the steel from corrosion and contributes significantly to the ultimate strength of the structure. A portable grout mixer is used to flush out the tendon sheathing to remove debris. Then cement and water grout are pumped into the grout tube at one end of the tendon using a grout tube at the other end as a vent. An admixture is used to control expansion and pumpability. ( ... ····--------------·--~·__! ,·.' . ; -.. j '., Precast Segmental Constru~tion. Kishwaukee River Bridge, Rockford, Illinois. Trunnion Anchorages/Stilling Basin Rock Anchors/Rock Bolts. Tennessee-Tombigbee Waterway structures at Gainsville and Aliceville. Alabama: Columbus. Smithville, Aberdeen, Amory, Bay Springs and Fulton , MS . 7 '_( . . Citizens Bank Center Richardson, Texas. FAA Air Traffic Control Towers Atlanta. GA Charleston, SC Charfotte, NC Colorado Springs, CO Dallas/Fort Worth-. TX Honolulu, H• las Vegas, NV DYWIDAG SYSTEMS INTERNATIONAL, USA, INC. Miam~ FL Nashville, TN Ortando, Fl Philadelphia. PA Phoenbc, AZ rRochester, NY Santa Ana. CA Corpotate Headquarters: P,O. Box <488, 107 Beaver Brook Road. Uncoln Pn, NJ 07035-0488 (201) 628-a700 17-40 East Joppa Road. Baltimore, MD 21234-3682 (301) 882-6111 7225 Southwest 86th Avenue, Portland, OR 97223-7298 (503) 2454. 4 Castlewood Drive, Greenville. SC 29615 (803) 268-4452 2854 S. Ouray way, Aurora. CO 80013-1945 (303) 690-4103 1113 Pueblo Drive, Richardson, TX 7~2914 (214) 690-6411 1384 Grandview /We~ Suite 204, Columbus, OH 43212-2805 (614) 486-8793 11528 Sorrento 'Ialiey Road. San Diego, CA 92121·1314 (714) 27~7153 301 Marmon Drive, Lemont, IL 60439-9006 (312) 739-1100 5111:1 5M OSI•lA '· .II. 5010.64 fFRONTl STONE C. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE '·':'l..IENT S. PR~CT . fJ... LP : :, r· · :.; >.J "' ~ f.\ t.n..: eft 11" ~ -~ R. ~ ~LF'-1 LAk't CALCULATION TITLE (Indicative of the Objective): I N 1\ I ('...) Dl \} I::?RS I (No.) I MA ',._) "L-srAk-~ Ti-srAkt:-Bu L ~ 1-H::-nos ~ CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. DIVISION S. GROUP CALC. NO. TASK CODE 155Co. ()8, ss I 32.,-l *APPROVALS-SIGNATURE E. DATE REV. NO. INDEPENDENT OR NEW PAGE 1 OF 54 OA CATEGORY ('II) 0 I-NUCLEAR SAFETY RELATED OII om G( NA OTHER OPTIONAL WORK PACKAGE NO. bC SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED (v') PREPARER (5)/DATE (S) REVIEWER(S)/OATE (S) REV I EWER (S)/DATE(Sl CALC NO. OR REV. NO. YES NO D.w. ~.,...,.-~ 0 · \1 \..--P!~c \-\~ITt. 0 / 1../J-3/~ > I~ /3o/B<C ~li' ,:~, "'! V,,~;rr'. ,:,~ ~vJJP~tk ~~OJ~~J_~ D. (.,U • t->o,-rc~ Q. SLA~~.t: 1-it:iTC II J/•s-/e~ '11 lfJ'/flC. ( 0 .·~Q·~ /)~deJ~ C»JF ;"4.-~C lJ.w, ?o-rroz... 1) . ~ L.. A-Nt\+ 'CTTE ' 1-l~ "L !' ;-2/f-87 11~~~~~ ~Y'JJfr~ DISTRIBUTION* I l COPY r I COPY GROUP I NAME C. LOCATION j SENT GROUP I NAME E. LOCATION I SENT I (v') I l h,/) RECORDS MGT. I F;u Fiur I v I I FILES (OR FIRE I .Joa. Book I v· I I FILE IF NONE) I I I I 1)' (}j. ';':) 0,....., . .:.. I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! ! I CAt.CULA TiON SHE~ - 1.1.4./W.II./ c:.I.4.~V· .. u·J ~ I ~cvz:-o• I~~-! . ......., .. JS:2:oo.oa S· S/32_-'2 · P•CHotC.It/~1'C lt./JtJ/~s I"IIYl n u 1 <:lUtCJ: u 1 dill ? /; i IWOC.I'~ . .'tCCJo11' 4(VICWClt!OAn: I D. 4)' ' ,..,. --~R u. \::.l_L..f\K 4t?Tn::. 1J2<tlgs- :11.1.,;&;;:" I T!TI.~ 1-J.t. :..t.r:tlC.IIT I::.;;;:~~: C:'-~~ I B l) L.k 1-/£-p. f'J TASLf Of' CONTE:NTS A.'IO HISIOF:.tC OATA (RI:ortsion~ Additions. Ode:ions, i:r::.) f'AG~ OE:.SalYTTON l OR.tG. RSVISION I Rf.'WAAK:S I NO. !U:VtEW ."'«). OA·.; '/,TL£ ~(:£ t "2. ,_ 2+81 ! I I 3 -?S" -t.% I IIABt.~ or f L. I 1·'2.4-0 /J.e' <r) .v~J -! '"' Gllf7?!N73 oJ... , 13-25'-~ Aoooo R..v I 3 I CAL c. v LAI c.a...) So~ 1'-\ P.ft '1 I '2. II-2.f-3ii . ~ J r:.;;IHI' rl J'-r ,;,-1.J6-Lor.J6 !::?'2 f/1:?71) 0 I ) 13-'1<"·6'1R.wti~ Mwr~.. f"'-"""A<;,7o c .. ov:> -+u A~7C.,..,I 445'/ ri>J'l"Ake= l I l ! (; e:b 1-1 ET R. \J t I i b-8 1 sf:~s~,(_ I I I I I loADt,J::; I ! I HttQJ~S7MI'-~O;IIJC. Drs~JBuT7~ I I I I r~ lo I I i I :;:,k I,._) 'N?.. ~ I i I l 1/-14 I~lop · Hc)?P .,...,... Bffi~S I : 3-25'-9~! K~'e61 ~~\.. ,,.._ A57o Gd'!)-A 517 UAs; I I 15-171 I I I i foP 5ot.N1 'De:-si&>.V I I ! - &rr otvt B t:P/-1 I I I ! /B..-~ 1 l:::v-stG>}.) I I I I I ~TtR. or It'-! Lt' i·. i I 31-351 I I 7 I f-8 j ~v? tu r.o;.. ~ ~ 6 u· # • • -, -"' !81fo'f'! ! 1-2.f. 7 . J ~ .:..,.w,;:,g..,":J ~., ... ;t'hui ,<:. ' ' L!Fii/V~ Luc; I I.H~·Sc., ~~~ ..,m, 1'14v.. '-t;7o G. ;:;u ~,. ASfi' Gjy·, I !M-3il I I I ' ' 5P~tAX: be-s (tiP""' I I ' I 1o~41l I i I I clkf:.\AA1'f{..f 'Sk.~CI*--"'~'" I I ; 1z -.r41DrrALL S'ketC.:..ct:s t ~. I I, i I ! 100'ff~-I ]·tf-8 c.!2,;L MAYL At;?o G1 so -) A517 Cl.il!lo ) I I i I i I ! ! ! i l I i l ' ' ~ L u&~' E P frt.JJ( o,.) 0 e11VI'KI Ott At.ts I I , I I i I i Cu~ l)!( IJ.Jf::.o I f.OCI:£) CALCULATION SUMMARY RIVIIION -2.. 2.. OI.IICTIVI 0' CALCULATION Ve-siG.,J i5u Lk H-tN::l~ 64/'t:S "ttS C...Lose-oFt bl\1 E'R..SIW Of:\ Pou..le-R.. 'TUI\)"'-lE1,.. CALCULATION MITNOD/A .. UMPTIONI I' Dl?!lt & .u "tt:. A Is <.::.. A Ll-0-wM (.( 'r>1'/I!.£SH:: :) «' HA7~ IM. E)c.C.Ii'PT 'Sf:I>.A lNG ~LOU s) s it'A-f-L 'BE ASTM I S , l...t> Ac 1 fJG C.. N () I "T"t.Cf\S '5. ( a·) J..l~ O~.ST1'1rftc. -rz:. "PMF' ).1\t,j tOt. "J "'-F.; Ll<>W • .b) ~()ltb~"'.::. ""'::l ~""' 0 p~ ~.vJ.I::L. ... ()Be -lo ... e 4s~l;-.,1 c_ + <. 1.33i=""'-to;u. <-) /~'11>~5~'1tc. Y> II!A.'I-OPt:OI }./,1).) !:\ . .,. O.JS ~!I"!!< { "'-1. "? '? ~="flt~ow. Don: $~r'~"'t<-P~A Bull.a\-<J "'F REc.l.4~7'Lw 1 \)(i;~IGAJ oc ~~·J•-__. ':::JA>v; .. A.I 3 OF 4, S'kt!V (li.A.tt; SAAtl 'i'r-o.U Vf'S'~M, F~ ----·-·. . - S, . Dc,i::;,~ l='cllil l,;l'S¥.G~lA1':..h.U /V..Jf:J RRM<> 1/M.-vrr1-l I o<::>o c.-fs ~~-.......:. ( ro' oP<:.AJ : -1'-~J.J{.c~ :,_:t---.<.1 J ,~'JE:----+n-r_~,;.~ i:&=iio-~; f;t:O--;;; f~~ ·:ro;,.->tl'.,;~·u· 6S,Me t'1bJ ; tu ~w-.vu..,....,.=-·+--fli?<:---H--+- CONCLUSIONS DATI . 1 j_ }121 /?S" DATI CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVISION /!:)OD, Ol!; S-.S./32. -2 Q QA CATEGORY I COOE CLASS T IJTJC~tf: POP...71fL tft:"?'JME~Y. ~~· ! ~tl I . I I I !> ' () J I I I I I I I I I· I I J . I 1!1 ~ I I r-1 ·~--'--:-=-----:-:---- ' 1-------''-'-~c (. " I '~ ,- /2 1-f?V ~I 14'-tb 11 ~I E"t ru A1 c.-otJ z!' --- Ass\Jwt, l:li'Jl..lttAJG i>P!R.. Acn o-.> E Dr= ExP.o'ro Covcr;a-ert. 'l zs. 9:3',. ~': z.c.. C:. 7 1 "''-8 </ -t "l -+ --t ~ J ~ . / Jh?>.lt j,J(:, '"LOC.l:: . / -==±!"~ I" *"" l.'o: (o''-r -},p;~ • 134119 l I • £~· ~ ---Jh % ~ ~0~ r:. --~· I'~ u C.U,ll1f' \'!l'rl\. ~ ~ K ~ ,, ( c..o...:r ) w.~lj'\.1~ 6~ Y,!x), (~NT) I ;:-~8-«~16'' "" O.k - 'P 0\tJ ER. T u NNE1. G eoMen•w· s I IV\ ll A-~ ..,.-1) D tV t;;YtS, l c ~ w lT71 -r:. 0 L 1.!1. ' /03o F~ ~ ~DC. f/., ~~~8 I 3 -r;b" @4'1 c:.c. CALCULATION SHEET &5010.61 PREPARER/OATE 'D. w · 'Pon-AL SUB.JECT /TITLE /'" )3 u L~f-iU\0 SLol l) cFt.IOtnD. SPt•NG .3" - v -I ~ sP•' Go, ~ ' Z" '~ 1'~10~. c,.cu w I) t: I I 1/ + /+-(.(;~( ~,.t s-mn.. --~------- I) I ...... L{•J 8'4 ': 11.'-(, I II f CL., I I \ ,,_ STONE & WEBSTER ENGINEERING CORPORATION REVISION 0 QA CATEGORY I CODE CLASS ~"P.;;.t .. 1/{ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION a QA CATEGORY I CODE CLASS MA.F • OPt:Pl 'N. s. ~ l\80 I £1. 1191 I -I l\)j Nl "1 : --11f\~~~--~-~~ I I I I I I R- ! I I l-I -~JJ -~~-+ -.-~--i I 'Par ,..1 Mer (!)f)~ w. r. }\~ D&~ TI'W I C. ~-=~z.4)(,z) ~ ~990 1sf S"ElS M \ <;, ( P~ PlfTf 7) LAsErir P5 -=-173f'fsf N -- ; ~(o7S' f3f By I tJSPRTlb~ /, 33 P .... ~ > P +-P ~ YHt ~~...,.~t rc CAse ~tJU& , -.r M,<~rl( c,._p._ Sti<.:>lollfC. -r r!1 .,_,.,," ( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I.J.O.IW.O. I CALCULJ_TION NO. I REV lSI ON I PAGE ... 5010 61 15"~00. 08 / ~-S'/.3_2_ -2 0 7 PRIEPARIER /DATE D. w. 'R:,T/atr IRIEVIIEWIER I CHIECKIER I DATE IINDEPIENDIENT RIEVIIEWIER IDA TIE .0 A-\JT=£) e, LA-1\X \+FIT E 'J-/zgj g.{' SUBJECT I TITLE , BuuJ..J.r.AD lQA CATEGORY I COOE CLASS -DNt:7Ut~,J !t:.tVAlk.?.. Lol'lolt\JG P~ U8c. ec,..," 4 _ ~ ~Tk-cs(u-)j: ,(,)(-z:::(,,,4J(w) Dl5so.JMt!lk; c:ct:uPMCtf ~te of: /. o) ::;/ 0.... = o. 2 S. '-""'o'NG PFDI{ FER c._ APh.tc.At"wJ Folt_ l"~c.'(') Vt>L. 4-) p~. F-94 oJ...:: o .J r ~ .!) I II ~LON 't"UNNUI.-/)1?!{'/G,N t:.( I Ttlll.f Po.. j)G'SI6toJ o,:; ~AVII[ D~ 1 'Bv(I?Au o,_ 12cuAI-':141ulll /9'1C.J P] , 7o ~ 71 , PE "' c~w-C= ~ [~ CA-})· V Hz-:}D = cO<. ('"z.4)(wz:) CM~ 0.7</ ~,c.. ~= 0 ::;: C. 99o co<. i! ~ )/ 2, I % ~(z-i) <:: :. ~F'" r ~e-rr ~ ~ d·~4 (~Cz-~ )~-~j(2-~} P~ c.(o:z~)('-99o) t>~ c. (o·35')("'99o) 8(.,1 0.76,/C) ().'9~/ o. 7orr /390 /73) 8S 0.7rt,5'( o.CJs-41 0,7114 j4oo 1750 qe; 0$03~ 0 .9~!4 o.?/8~ 14!15 /700 9'Z. c. 8 '2/4-0.9"81 o. 7~:l.'J... 141'5' 17~s J4 o.'B 373 Q.97..f-L 0.7:J.s-C; J4l._o 177~ 9(p o.€671 0.'17% 0.72~7 /425" /78~ ?8 o. 87.fr) () ·??344 C>,7313 1430 /1'10 r II!J(J o,S~z_~ (),9885 o.7ssro 14 3)" /795' jt) 2. o ·11o7i C> ·99l a {).73~ 114-o /80C i /tJ-1 cs .~·zec..l6, ?94-? (j '73 72._ 14-1-5" ttsos-' ; /06 o.94(AJ, 0 .99 7 f ().738 4 1446 /605 laB 6.9(,f~ () /i987 o.13~3 !445 !8 /() I /tO 0·?8211 0,9997 o,7J9S !450 I BID II z. /. 0 /.o Q,74 1</5() I BID CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCUL TION NO. REVISION PAGE ... 5010.61 SUBJECT/ TITLE "Ruck :...:..t.r' IS s-c::::o. Od S-S }30 -2._ 0 8 QA CATEGORY I COOE CLASS 11 /! /I I ! MA'I< o~ ~H. '\J ~· -----···· ~~-f I - I ;· I ~I I! I '----eo-'-··~; l J ~-+-. _r:;_4----'!.,..,....._ .. ~-----·--·--·. ) .~ t . t ~(. lo3a ctriSI-'''-( o<"' 6 ,"?<;'"") p3.,..PS P, ;;;: f4+ Pro Pz..... :;;. 7, 740t 7.]70 8420 M!i c;P'<'R. \0,) · 1-l ~t)~ ST'flf 'C. P3 ~~2.4%.#J(I~~~) -:: ~ 74o rs.f 1)4: (b2.4%ftY;9>? -= '1; 5ro6ts f ~ /2 ~ /3'] 9 3C:. 0 + 242-o /, 17 < /,3'? -;D1 OS"D 1,: = ~ {5 (z-~j+ ·~~(z-~~ ~ w:e c"'::. o .74:. P5 (%,-:6./J2~ -= '37D rs f Peo (~=I J-=-::?,4 zo f:. -f :::p. P ,_.., F 1:!!1. v!UJ ~ 711 ~ c_ Lo~-rn Cl'f)r: ~·Jt.AA1.5 CALCULATION SHEET l'\8''3flt 1 . ~~'"r J) I B ,I " '· IO" 2. J I ~· i -( () )) 2. 0'521 ..;! t ?.OS;JI / ::> c; ,05;J) 7 Ll .;(, 05~1 ;:Y ,, . . -... ! 0 .:;;'1 lo.oS"' 7. 8 S' .11 ~.73 9. ocr 8. 37 I i Cf.<3S" Cf./3 9.'59 I 9,4(., 9. 35 9./9 9~o7 STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATIQN NO. REVIEWER/CHECKER /D'ATE tlt.J:;:-( ~L ' . f X J.kETT;:-1./z8 /P c C) J.43 2.93 3.S4 3 .'3 I 3.3~ Q.9'L 3 31 3. 3 I 3. 2 r-. 3 .) ) 3. !7 ~ .~~ 3.7~ 3.77 0 ·; o. IS' /: REVIS! ON PA8E 0 10 QA CATEGORY I CODE CLASS Cf.o9 8.72 2.0.)3 /8.43 l9.4l 13.'2..2- 1 ,') i 7 ~o~~ 17./2- /'?,79 C:,82. ( CALCULATION SHEET .0.5010 61 STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULATION NO. 1~5oo. as Is:-- REV I EWER /CHECKER/ DATE ;CA\JJ:"C s:f.I'Y '-"PTTE REVISION I SUBJECT I TITLE BuL/<.4 QA CATEGORY I CODE CLASS r r ,_,_ t:::>r.Cf:.PT COQ '1"'0P f dOt C)t/1 '/?FAfV/) MAX !_<)AD ~ ..iS€ rc.< At<. l;,)-:: 20.'33 ~;; ';)<:.._' !I) ~ -··;E"' -~ I 401}0.5 ,tl-{le APPiii.-tJX.. 15'?:.:. f?pflM..!:.. ''\ ;_ o.87SJ ~ 'D '( f '( "' " t f:,'f..IAL \.oP.\) \)\ll<. -+-., vJo.~·,," \:i:F.~-. c•'X !>._1 f:/0':::: <. R R_ )4 ~ OF f~ul..t<'-'<?AC;, I-1A:-)C, A'o;-:_ '_:)r[: (191-z" ·) _ /k. Pet'1,M -z. 20,,3 S 1"'"'~--39. IJ-i~-hE. T14:; <;3\)lK""X:f'l'!) ! <:. FLlLL/ Wtrl...U A:) 1 Kr;;i(/+1'G. SC) 45Su.vtG: 'i.IMYL'-f 1ruPPt;e."rSO. ('20.33 '-<:/1 \(141 )"'- 4<18 k I -: ~ 0.P r ?:X 1 I') 143" R = V:(+~ :;_ -:. (.?LJ' '33 I ff / :: 2-.., - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PAGE 0 /d., QA CATEGORY I CODE CL.ASS 1 CJ'f'J I ~, l'f " VEEP Bt-"1\M CBI\SW ON :)4" Pc<:..k£1) I H :..t;:flcr!'!_&c_E'!'!.>J:.:i:,€ w1or;t.;.:!, 1 -1o . (~7) y X ___t_. __ ~/± Aftrr-t y c.. 0 19. 'l. 5"" /8.St, ® 7.4? 9,'£"fa (J) /0,0 o.S" 3~. 74 <r£ AY 433.9 -II 8! II x=---2_A. ::: 8~.74 -. _I h-x:: 19-)/. 8/' 71{ X -= s T)< :2 377 :: -= TEf-j~loN X Jj,81 S:w.,..p Lv () '377 :=. -::: ':... )(I ltl"f K:{ 357.3 7/. fa S.o <l-33/1 :lD/ 33o 2o~, =/ 0 '/" o.4J7 I( ,---. ~~~S{_(l_,.) 1-•kf\..!::lt. M ~w 4-9S '";n_ . _ p..,:z;(?~;. ~it Fb"' -b" = (o.bj(eck:;({7.Jz') G A -r:;. Ill I (l X. / C:u T"j .:.., -A.:t X 0 F{.ftri(, E T-= \,_+it:? -o __ 4..;..... JY\ c\ = \ Y-x I t\d' ""' ~..t.. G..7S 877 '2. ?.$"' 3B !83 11.1/ 127~ J 194 133 Iy ~ K(o,s7~(,,)1 ---~ (!'·)(;o J7 :::0 77 ~ -+-g 3 -=-8 5 ~ ry=~ r;~~ ~ 4.8 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION NO. . 'REVISION I PAGE .. 5010.61 PREPARER /DATE }). v,f, Pa---i. ;; SUBJECT I TITLE f)VL" .u c-'PC ( ) E :. 1GrrJ 6 ~ F d !5SCX5-0S /:;-')1:;';;:-L_. I !::S l / ~REVIEWER/CHECKER. /DATE , !INDEPENDENT REVIEWER/DATE l;}fi31Bs-nA\;:rc eLArx'-'!~Tre uzzl?.' I IQA CATEGORY I CODE CLASS c'1\1't:s -DtU(!.e_q_ "'J I P&voll:-/( lv.-JAJtU L.. -_ /4' ~~ ,5/ ks~ ( t. 'se. ,. ~'-t: \ 3-s-o) fv, -V ~ b-&- _ft:.'-~ -f-a -= l Lop..o~ ~~M. p~, I I) ii_ S-~:_ - !1.. .s'- k A -- - (j98kY;_1Y,) _ ~o 1 ~3 (49~:/ 'Xn%) -=- 3 5D 3?. I"' 3b.71 /S. I ~<-s~ /, / /c-.s;_ 143 k - (j 7.11s")(o.437~)-1'7· I "-st Tl=.r..JStl)-,-l ', lkt_ ~a J.Cf:.7 J, I o,qs-....:::. --= Fb T-:: 30 !_(P.5' q ~P~ta-oJ (~! ~ o.o4...:..0,f) J 1.1 -9-b._ ~ @J_+ o,~1 < ---F~ ~ ~-= 3o :2G,S _s-,~ f TVJStCJ7'l ·. )....) c( R.k:-t:;:l \ D / ! (' ·---'---1-'--."~.: 1/-so\ I Of<... I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION A5010.61 IJ.O./W.O./ CALCULAT)ION NO. . IREVISI ON I PA;'5 J55oo. a8 s--s J3Q -~ () , PJtEPARER~TE D. \D. 't-'6..,.,.121< J I IR!VIEWE.R/C .. HECkER/DATE !INDEPENDENT REVIEWER/DATE tt_; 13/8) ~I--\IT{ e· IC.fJC f.lGTf~ 1/:2/8.;- SUB.JECT I TITLE \?rJ\..i::j,;...•·/'.r {:,A~·c·-[) II..Jc;"'. I.:)',.,.\ / p'r'/ )&;..·? I 0/fi"J (1"2'% \[c. 4375) .._ IQA CATEGORY I CODE CLASS ? <5n"'-''::C. 77-'~ ::1J.v7+N' sm.e:c:e-~ ( ~ AfJIII.n;#!ll~:-.-:: 0 1 '!':'~ __) e&'J-101,.1(; 57:1U'rilc3 A,iu; ~- 3. 9 Ks~ v~ 143 k ;Ld .., '\V :. ':12.-(i 43k):::" 10~~ )(11·31')- -r -7...?. 7 7 c... -4 - STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET IJ.O./W.O./CALCULATION NO. 'REVISION I PAGE ... 501061 ;s <Soo, 0€3 Is-r;; r} :::-~ o ; :s- PRE PARER /~E -I -j_ I REVIEWER /CHECKER /DATE I ' -IINDEPENOENT REVIEWER /DATE D. UJ · }-" o T"Ti::R I .4' I 3'!851 CJJ'\r:t:C \3Cf'./X: ur:~TTF 1./7~/2:_ ~ .c~~;: 0, '3 ( "10 }G·~ ) :: 2 \ k,J,~ 9,6 kj~ -U, 2 cQ II {~taz>'o :. C,;i:(o.7o7)(.2l!--s~)- US6 Z'' C~c.~ "':k-·n .. E:'"._::rUr>t-J or-) "'BeAM, ) 4- 5 ..._;.Q-4 _ 6" ( 1.7 ";. ( lfoS ") A=-38{£! -384-('-h/o!,.'...~; ... )()..377 } ~ 0 I '2. (DLI ])fE:'r;R, IJ 1 rJ b -I:... tV ; A::sl.l...._t wtn. .:J•~PL·j $ uPf'~~ Q'-0· 32ly, Pe~~ 1(17,1?5")~ M:: ~ = ___::' 2_=-":.:.II_B __ _ P cP. roy, +a = p; -:: (h ·;, )(o,fo2S·) ::: 0 · 8 g k.s~ ~ + ..h. ":-0, SB + 3,::( I 8 -0 6 ~ ~ 'PI:7 IS:B4 57·S -I - f Kl~ ~(1~-a~) -;. G~~~ == 6. S8 11 f-= o.?~l1t "'f?,2f19'f.?~rc2cs!}= o. \e'' t<D 17,/2. -r =-o.t8 = 95' +-D. B8 :::. 0 ,94-L. /, 0 C>k. - STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET ,..~.0./W.O./CALCULAT)ON NO. .· IREVISION I PAGE ... so1u 61 J )5o o . o ~ I ~ · S' 1 _? ::J -')_ 0 I 6 P~PARER_LDATE J _ j REVIEWER/CHECKER /DATE I INDEPENDENT REVIEWER/DATE D.W. ·po'l"7"j;::'".c:_ 1.2fl"'/8(1cAV:rD E_r .. P ... lk!+e-nr= 1-.J-zt/eS" SU~CT I TITLE I IQA CATEGORY I CODE CLASS 'l::::SIJU·!.;.,_,.-""..., ~~ -f\u~_fi'~:~J Lf~n.Alrcr.z. Tv,;t!Aitf-s. l-oa Pu~Pc>F o~ ,tr,._;/1-ty-zt,v::;. TC>P B~) AsS:Uf!..t£ .S/<r.tVR ,s Frx~:=-CJ 4No T/-fr;' B4ek FL/TrJG t:?' ( ~ ~ 3 ) e,ryyo...s UN{) &1( f2 2. !...cAP , R I f+)C lf+l_ Lo/1-D !(., ::2'-o~".,. Z4.C::,15 rt< I ~.~ /<./, ..ca = 12.'1 +'-<.) -:::: (!?-/';)( c.S.u;'J• = rb "" Z9. e ~$ ~ (r~ . 12) D, C,_s lc.fi. -4- 1 5·:: /<->< 29.8~<s~ c .d .., / 0 .._ OrO! ...._ ' -37. S"~i Cu~ 1)~:.-No,~Vc. <:t~r= FLll-NG.t R ( 'fL-#. 3) w-: R :a.:= <a I 'V, } t J i J.-t·...--.--J -.--L --,-} --rl---.t L~ J 6L - 1" ~~ ; i- ~ ~ v ('3~~)(/!t;.7 0 7; 7 7, ?_If --:: (a ,4 I ;.'/~ () .081% Lo 14 ~ R~ svePi!>ftT ~Uiv\k)S G> 4 fJe(J\ST'"S, .....:/ X: 3,5 f:::: 42 ,, CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J .1.0./W.O./ CALCUL~TION NO. I REVISION I PAGE .. so10.61 15s-oo. oa / ~-S 13~ -;A, o 17 I IREVI EWER /CHECKER I DATE 'INDEPENDENT REVII!WER /DATE 17..-J!&./sr-U· CO ctJ!.-!0Ci-+SITG :...-j?_z!£:; SUB.IECT / TITLE B>uL~ ,..__!::'f'P. ~fi7'·-, - M l'l""r : o. l o 7 w 9 ~._ ::: o, 1a7 (;s. I t/(3,5') "l -/(),(; }_( ld.7 - /b.7iln~- /2 7 J I/ {(7). !1) < !; --o,6~'1 = Jo"s' ::: Em.vl/tY£ AOJ)PZJ 5r?<u-ss I-'\J We.# ~ Du~F '1'-0 k)J)1- A fiPNG.t -:= 0 · 00 ~ s EI' = G 06{a)((W)(.r-''') 4 ) , (;."f,OX!0 3i',)f..83 3~ ~ ::: o. 00571,1 /1 lp M ~ ~--------~- 17. 12 ,( I r >i ~ JJ,/ k_ R,~ ().393t..VX =- R-z_: /.145 0 J "" 3:2. 4 /< J<:3 = o.918 "'""') =' c)C,,3 k.. 0~ - k.. ,, 6. Ob << - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.D./W.O./CALCULATION NO. REVISION PAlE .. so10.61 ls-s-o<J .oBIs:-Sts':J -:~.. o /8 ~EPARER/DATE .:._)' \_0. ):.), -r--.~(.J REV I EWER I CHECKER I DATE <tLA~)Cf+ST\t= SUBJECT/ TITLE ~ .. QA CATEGORY I CODE CLASS s\JLkJ.+•-.("'\ ...:rr--..,... -_}/'.)ifi P.,. 8.72 ~ at3; p~ ,Cf ) ~<:t AttcA A"' I ~' k 4 1 Ary'; '-_x_ _.L_ ..::t-j_ I (o cs 3 734-2>23 3 18 o,Ct; .:z 12> 2 7.75' 5.41 41.9 2· 43. 40 1.4 (o,'J 2,1. 38 .3 I(),'ZIQ 15.'77 113.0 'd3 380 5,(p 57.fc 1_,0 41 GO z4.o3 /B8.~ 75'5 I)O gc,,-s 8( 78 ' ~ ~ g f X Ax tse.~ "' A .::.. 2 1-.o ~ = 7. 84 'L:x 8Gs-~ 4 ..- ':. I -/S7 c...,4 -'1 Y-=-Av 8(o, 'f ~ 3 C:, r;: ':: 2~.<>3 , ry: -= i I =-" . r:;:::- G, /.. _ 11=-. -2,' 11 y-iA, - wtr1f Q-::/foB ~· KD _ 64. (; ~x r Tx 8 G:> S';., -1 1/0 ~ 3 :: 2/.9 ;...._., c:. s '::" --7-84-Z, -lt:N 1/i>.-J -x r::_ o.:c. _, ' 6(0S c., 4 JJ• ·-'-~~~Jt. c;;:~p T)( 84.~:? -::. ""' :: Jts, '3-X:. /0.'29 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .0.5010 61 J J.O./W.O./CALCYLATION NO. I5Yoo.o8 I s-S!-::?.J _ ::2. PREPARER /DATE D.w. Do-r-:SR (}IJT7r>T7 /:;~ ~,. 'r J A Kl fn__ ~A-0 :: ( 8 ·7"2 Y .tt" )( ~~~ J :.. /4.5 k. "? -7 A ~be~ l:i_ -(:1.14 I< t)(i2'Y.) -.23,3t-~; s.l - I(Ovi-.7 ~ ~ M -p/4-)(rr_) -30, ~ J<sl be s;c.. -84-- ~!)IN(.;{) s '11U-'1:.) : I' _('be 0,(, ]o,eo ~ .. -~ - \=": ::.. ..} 3o - " !=""" 2/,9 Q .:::.. r; ...,_.. ~ ,....,.. /o5 I INDEPENDENT REVIEWER/DATE I QA CATEGORY I CODE CLASS I v ..... 5t,.r::~ r/K t:.bfl//le-7;;srv/F ~1:-?J()/NS S'J;%ss, 5~blf7'-'j E'KC~.S 77ft ~AI)U) SO?VJF r-rJpH~ ~}/rf-U/It'LPJ I~ ~t.JI/LEO. ~ )S>v"'ff¥U>.rl r/-1/Jf r!f1r e;c-R.cT!oJE-F41f}GE W!J)/P = 'i's-yr;z;; MCGL£cr;, -:-'~ S7J'Frt::Nt/lf? ,).A+t/1/)t-?} .By ~ S:kt/IJ /l. .47"7Ai-H1?[) AT -4-~ 0-rvo<., 8'~ 1-;S-: :JI/ /J;; A PLA7-JGe WISY!-1 ~ulk-....-a Y-z_ -rtfc or::.m,.,Jq:T r.J 77.~£"" !I)EK:-r !JtfV'A , 3 /D. 8 ;, {o 5". 1-) 14·19 /8SG, g,7'' 3 41.9 d_C,,7 I )<. 8.'2... I -o)(" r -- ;;.-:::, · f I I " 1 -lo --L-- I - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION •5010.61 IJ.O./W.O./ CALCULAT_!PN NO. IREVISI ON I PAGE ;s::;oo. oe 1 -;:;~ s 13::< -~ 0 26 PREPARER /DATE .D.w, P(")-r"'Q< I ' /, IREVIEWER/CHECKER/DA.TE !INDEPENDENT REVIEWER/DATE /;, ~? /9 ~ li A-\j J:O e Lf-f.)C-li:;:-r r[ 'J,jzy/&5- SU~ECT /TITLE ~I )Lk ;-fFftO ~~ <:- T:to /088 /:}5" c:., J -t;~ ~~ 1"Yt2'/,) =. ..?0 Is-.<;;L' < 11 s -----:: X -8.7 -tl?vs1 o..J -J:<s- Tt s~f' -/088 ':. /9''-z_--_ -- jo.] - /.:;c /65~3 -h Dc_ = < 17 (c-~49 n:;-p{l y G,;1-ld_.(r2/) ..<4, Sfcs~ =. ID5 Q5: !t115-o.oo437(Jt)lf:; = /.4)5-C;,oc4J7(1&~)¥~o­ fb ~ O~epF; Q 5 =-o.ro(s-o){_o -90 =-o< 7 4 ~s~--' o, ~ ksL ::<4, '5 _ ';<}.C] -+-.27."4- WC21_.cS @_ V!ol7"'~ ~ V-=-(8.7-z..~;,'(;.:t-')= 0/lc_ 'L 81 C-f,11 PAI'Ut0 ~ 0 1i!r-tR Bt::A-M I J ~' )S .. I~) US[ ~ \o r::IUEf" ALLeWMU fJ...'-'eP;; c~ PAl( nAt. -Pt~r~M :_'-"u ~ 6."'?, f:c ~ o ·S (7o J ::.-:{ ft~ ~ USE'" ;:u L~ f?f'J.J~.f.,4:-:',~:r-J !AJ'.;:;'-I) ~ STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET I REVISION I PAGE I .1 .• 0./W. 0./ CALCULATIO!II NO. .0.5010 61 SUBJECT I TITLE i) ·, · < , I. ;'\ c -··-l.ol-'c..J' r ~~s-oo, o-9 . ! :; --~ • ::: -;:).__ 6 2. I IRE VI EWER/ CHECKER/ DATE CP'JJO I(:I_NX. r+r=-n-s t/z;?JcS I INDEPENDENT REVIEWER/DATE I QA CATEGORY I CODE CLASS Sk_f,J ~-~ A/l'Jt.!!c;)..,.. ::;J-;,-r-;<r c·.J--'lrJ ::>1-J a.. a 1-SS:Jt-'·. A. ,-(· I , kfi?r----H-,1_ LoP.Q!{\..)(. CWi::ll """i7--E" 1'-/~:1 5fA;N B'F7WEi:;-t-.J i?~/1...1!:, f~Cr-.JAL<j) --rt+E P ~-, s ll M A <::rs pUp t:J..J 'D I c u 1... A-1{ 'TO "'T1:-tf: S v ((_ r;:: k-t , F'-J P A 6-"'N5EI'tUit71~ Cf-+t<4. of= ""J'1./!s J'fJfi-r.J 1 A)":.UM.f" F·Jv., 'J;f·C· ~;. :t.J \J~l3G"I-J"T' Lr:.-..:JGTI-1, ( -:;,N'"'--re+~:-"B'rv-JI S~..r::,o.) o,)''..J-A~--f'\3, AJ ARLt-J l A:C.:IIJA:--... Uc.bM'<:t-.J '\ '-"''U... '01: LIC'SS W~ C/\\..u..JLA-:<:~ ) /7.." fY ~.p-\sJ~' _:~ ==r:=======r~, 2.052.-!' - :J<, q '<J I ~~ DF /.I?... /. 0 -3. aL + 2.7 ro -z.71p + 3.1<- -}.'12. f \.\( +J.ce,3 +o.n. -o. 4'L <----J.84 -6.74-_ +C>,j ~ -f 0. ?.Co ~ -1-0r\3 1 1-o.j -6 ,O(o -o112.! -od( .o.ot.. H).61 -ro,ot..l -o,e:.l • -o,ol 0 -4.41 -1-1-.41 -2. (o(o ~ z. ~ (p 5-m..ESS ' ~ = ( 4 • 41 ~ I )0 2 /,) b /.53 c.:...,) -34. Co {)/< - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PA8E 4501061 6 ;;;;., QA CATEGORY/ CODE CLASS ,, o. s.z •§ ~ ,, ' '! A c..\ z. r Yj', '% 1... y AY c\ lo 5 [, 2 9,..:j(p /'1 'j-I ~ -,~ 18 ,S(o { {p z. 783 ' -J·. ~ r r~ 2. /0.7 9.SC:, /0~ oAr, ..Q J[p ( "to!-· ..3 /0 o.S" ~ 8tb 746 if! iJ 1,'5';{5 ;:;r, I I" ' ~~. 45' ~&9 I 2' ~ !:J__ ::2 c; lC 1?. r Ass u"'q:: Q~ ,;), 0 I -/ r -J,B ':. 4D. 9 a:c ;)S: 83 . .4:>~ .{,~ ? o, 393'0~ D/393(?. 38 x ;~'. )6·s~ ;. ~hi 6. 7~<sL p; ::: :. Q A 0<,.45" ~ ~ J.9.4~,;...'1. Cu~c..~ c:rwMAJ F~tt t?'c:!UDIII.j5. ~~~.~,~_A-M 'tC -mp ~fM 1 ll~ ,l ~~· e~~ ~or~~.J<> IN r(./l.r\lc.~: ~ (' 1'5· lo H ~ (3. 791<1{~.:) ~ C,. b I< I " 79 .Co" {f ~> 1&.. 7 ~ 3 (rc:; I(&,) ~a: ~ ~ ~t~~:r -::: 4.8 A$£.. ~ Fv-_ 3o~~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .0.5010 61 I J.O./W.O./ CALCULATI~N NO. IREVISI ON I PAGE ISYOO, 0 8 /~-S 13;;_, -?._ 0 1..3 PREPARER /D~ b · uJ . )-J() T""rFR . I /. 'REVIEWER/CHECKER/DATE !INDEPENDENT REVIEWER/DATE 1!7!86 .nA•JTD Ecfl/)Ct-t~-rp:::-1/7?1~!'" SUBJECT I TITLE ( ~ IQA CATEGORY I CODE CLASS -Dn)~ILSt.·;,j /f.~,.Jf;/.' 1..,;/JI'I:~ ]3 I) L. k u t-70f) ( '71!--( ~ It Aw.~ y t;1 \ 2.D, Co !S.C.. 393 2. ~ ·4 9.(., (oZ.. 3 ~ o.S' J ---- 33 448 AY 44B 1~.~ y-= --p;-:. ~~ S~ruu '1l C:*/1' BE Lft1 fD })!JWtJ 5ktll) flf)f eF: T s:: ~ ·~( y A,'f,(A-L u;.M> : p ia=f:= ~€ >I)C s~ J.E:2-\3Q. -= 13, c.. - '23.5 11 A M'l 5" 515""" 4 /02 /)~ I? t/ /, ()JO /1 ~4 7 t -I ~-· . ,..,.... ... , .L 7!l7"'.A1.. = 6AJ (:,{~ r-o '{f= i '~;~ "-74~ (I I~ ) -::y" S.4 = 33o As-\JMl= Q ~), 0 I k .,_ ! )< ~ 2&/r. t2';; --;:--:. ~-=-4?_-q ~ Uo->C(iX T!41~ ~SUM.ft't ~ +b 1._"" 29,3 ~>; <>q.e, I J7.s---D.6/ ~ 6.7~ =-0, 8( < 0 ~Sv~ , 1) f3u._~oc l~ IS hlt.._ C,.F-IN~'(ClC,. :l.) ~0 IS 1'1\lq.U SOLE<j ~ L/pfJ.,vC («.u...,tJ~(too>Ll) M s ( '3 2 I J/ k I II. I ksi. L.. Fb ~ o.&> rr~ 3D!<-~·L.. I I 1 - c.t~ AGuP'~"P<BtE /EVI:f,.j wm-J ;NJPAI.X /..4/'..fl; t 'J~0 o6...... Q_s kJ( '2o," spi..J( ~'~)_ 18oJ ..:..,..._ By 1/lllf'E~~--~ . .J) MJI.i, wnD -~II I () r / / 1\'\.-// ~ . ..)C 8 ~ J 1.0 " 'Ft.ArJo ~ ~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .0.5010 61 1 .1.0./W.O./C:ALC:ULATI.ON NO. I REVISION I PAGE ;s-s-oo.os Is;. S/32-;2 t o 2f P~RER/~ V w .·:.-bTrc:'fZ /. / JREVIEWER/CH.EC.K .. !R. /DATE 1 r -!INDEPENDENT REVIEWER/DATE 1zJI9J 8)1 OM:rc hAAY H-F.TTP 1..r'FIR.5 SUBJECT I TITLE ·D'JL\c:.1..l-1'cl'·O Gft'"f'.t-- -:{L ooo.ti. '-' ·; D.l., - ...-;.:.r-r,... &i)Dji7rJCij - ), 25: J 0' ~'------------------------~1 ~ ~~ .. i I 3,! sc; 11 - ~AX G rJO'j PrrJ"f '0\-k..-N. v->I>,'"(~::R Di' "PTT..\ J v sf"" ~wM..s t+ElG,p 1' ot::' 'O?u1..~ 1-h;;P..C . :. Z G. 'tr 1 D&:.;o"J) ~r "O&Pr.!.l, ~wA~o 1..61-03 e;rv T'lfri tt:JP Stn~ oFF::=· .... ,,.y J<' _ • .') UPLIF-t' F~ce-:;,. \~ Buo 1 ~cy ~ (;;tc,.zs X~ 2.47""~ )~3.9tto?'( 1q,-t ) -~-2 (Q·;;~:~d ) j = I, (.18 ( ;;;;_ .03-!. IG d 1-0. o-45 cf J ~ 3~/:;)9'7.. .:./ P'J Jo' -::: ;?4CCO -=- J· ?.'£' Zoo ? f:!tto 1 F7'J"-;7: JG I 6 9 2. - ~; d :> 4. 8 G l' ~ /&3od ; 7jff;.-A-C!"!/""-~l'rF&;Ty F11C77:JI(. /kMIAI~r I.I~LIF!T wOUW !?F ,A-fUCfl 11/t:;./l:..c;( .SIAJG{;;' F!((r._rto,J wtu kl.so PRK1i~::toJI uP<IF-7, I!V~:AJ lf-sSuLfiAJG ~LI..),...) St.t{);,.v6 S<~f?.P./'V"..-{,: j f-1::, ~ o./, ,; = uC> f7l't-f.J = o J ( t3. 9/r;, 7 )(&2 4.) ( Z(,~f:2.) :: 3o1 o~-~=. · F.s. -= ]).L. f. ~l(tc..no~ UPi.lrt' :: 31-t ~ 1-30;~ -ott '2 ~.1/2_ Jt-. ~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./CALCULATION NO. 'REVISION I PA~E5 .0.5010.61 SUBJECT I TITLE 3ut!<'Wf::,"·D lss-oo. os / S-S(3:{ -~ o <>< , I / 'REVIEWER /CH. ECIC.ER /DATE 'INDEPENDENT REVIEWER /DATE 12f2aJ8> ltt-vrc r;yJ.{)U1r=Tif= j_.}i..Zlf::...., E,q/i'.TH OuAt:r= · AssvM.t' cxlf" ().s~ e><v" % o<H --o. '23 b.L ~ {1-cxv )VJe7ro 1~-r ~ (;-o.n)(3~oor:::.)-= cifo, /8C) 1!- Ur£1F1 :t ( 1 +-CM o<./.1 )((3. 9/ro 7)&c.. zs)(ro:z.+) , -ti ~ (J ;-{?·74f(?.·y;)'frs. 9l~?X z_c...2s'f.e:.z4 J ~ .2 B 17oo "1 F'tt1c:ru~ "<, ,if0 (I+ C# ~)1_3'.91~7)};?.1)( 20~S ~ -c:_0,f) (u-§.74j{or'?r) J ~~. ?/(p -/(to?. A)( u;,:_r') -= 17; G,oo :!d 2), l.. 1 F/f t ( . .'T7.A::.N ~JBo,.. 3/jiOoo:::.. 2'i]1 7oo 2 22.. OK - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .0.5010 61 1 .1.0./W.O./CALCULAJION NO. I REVISION I PA8E ;~sao, os;s-S"/3:2 -1 ;;J._ J(,;. /_ / IREVIEWER/CHECKE.R/. DATE !INDEPENDENT REVIEWER/DATE /Z/.?1"5_1 Cf'-lfnJ e:_r_y..t.J r r-+CT!G '1./z!?,/ RF SUBJECT/ TITLE J?,J u N-l?AlJ -I QA CATEGORY I CODE CLASS ?r AR t/,X Bcoc Vs Suvu; -rt¥ t.ef'l)ti\.)G , ~ ec,..~ ~~. rz.:.e U·,,<I[?~J'lk \3~) ""~'iut-<.E: KTI!UG" ~!'" f: <>P B~::A'I{cA..)(; P~+-o. .2..' 2. - j -~r' ~ "" 2" ""¥ CL, : "-'::: '2 ,,(::-" ~ ~~· ---:;_~ "-~ ,1,;::3,-;5:' 1'-~.~-~'8 -" '~\1 APP~ II.S II .l1 "L ~ A 1 ~ 1-'',x l Lli:AJ61!-I 6!= '9f..oCft. r ::2 {ft..·J) Az.-:-1/:S.(L~:rtl or 6 c.oO<. .r :2('1,~)~7..(3,1r')) '----~~-~) -8~ '~Jf, 61_:::>C.· f.J;:; ~~tO T:::> ~(,L!?Cf" lt.ef>En '-BAD .!)l~T. Q f:"#JOS. OF Ot:.AR.tAlG D~L.5 LU81UJ1j SB.F -l'.JtC':I>-Al (j /tSCU;;NG(H OF B<.oct f-2(X. ·)) PL-ft-(~:.-s :J:::-A -....,.A 3 ;4~ J+tu ·..1 4 1 I {t...b7t.J6( f.'. 0/" ~ C/c. 1-2. ( ~ l ) ) ~ "[)5' ;»1-:-:-)'!_.~:--h<'·C_:: (ju"-" !'J;; ::: 7:J:J~ ;... _:_ . Bf Wlf~.T"-'rJ )Ju ~>-:".) ~--:::. ~-C. t; IJ~.r ·• ~~ 0G--4~0k = Vf {rj )(6.&).{~ ~(!.eog)(o.~)~~3:)(4k~) =1~s~ ?~..._ Hc~.R.I""!A1U (Lrr-r~J) LCJvs71t,e"S) 11 LuBII.tte" f?XPJt-rJSu~ .&~;;06 .. MA¥ stPRtJ06 ~ 35"DO f's.i.. '-J-S";....sl. 8t7\-N1 ii u~+o!st L"-1 -(j~ q) I 9.72 2_ ~·53 3 /8A3 4 2o, 2.-f. :5' n,47 \.> /?. 5~ 7 /'1.64 § IS. 71 9 ;s,sz Lo 18. zz... II /8.17 n .. !7 /7 .... 13 19.79 }A-c:. . 2l "L t~{) ~(l) C/~ I )< Lo-~<o)'fl) (0 J. k. J 4.3 /2..9 142- l3C, )]<{ 133 I :)2.. 130 12g 12.7 /?.0 139 -roP i')tf>rY) 5.8'' /3, ~ -- 12.3 13. 5' i> /3 'I 12.9 lA ! J?.( \ /2.'5' \ /?.; /7_' I I 1"2, I)! II ·4 /3.?.. !'(~[") 2_ ~Jf' 1-..;...d-j, Jl).6 Jjz2/27 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O./W. 0./ CALCULA ION NO. PA8E A5010.61 /;>:Joo. 08 5-Srs;;: -~ :<7 P~PA.· RER lDATE 1),).) , ---~ --~ R SU8.JECT I TITLE e u Ll< WK'l~\ \)E{l::1i'M t..J(~ A L) Mr.,., Bf"A1/,,.J': ¢(o.~$"J~(. = (6·7)(o,2>r)( 4~i.J = 2 . 3 a J.-s-t. < 3 sl':>i. :< .::: o.?<; (Alsc. /·lb-10 ) -tc(~rZl<-') -e._ -2k ~~'D ;:. +-( ot1'5 ~ \ ;44 - 2 (1,3/H:) ~ Q2,(p2 5"''(37-S ~t.) -:::;. 3.)'' .::.._ ll1 I A-criJir'-- QA CATEGORY I COOE CLASS J,US":"J1 ~Lfi-( C:.CrJ , /Pf'E7?. CUL,..,PriVG ~ @ I -;u ::_;.;~.;:::'SJ. 2U' L..:>P.;~·< F h~.ING PA.C, ~~i .• NoM•I.JI"- T:.:.·c;:.rJ"2S, t-I~,;·Uttl..l( iof'.!D<C ""t:> crt: E !:t . 'KNA-x= R.}=4= J, /45 w ~ ~ ),!4-z ~.3~ 3s) ':" '2.7. 5 J:.. Lut::tf :-r r:-BG1t 1.uc; fAD, .• ;. .. ..::OM "'p..._ -., ""t'I~:(4Jf_'"';; 5 :.,U:f.)f" JltP, C..T[!;,J ' /d_d.._ <. )"".-"'-"' . Y. ... -r(J!C,;.(.A.)e'if o."' W(:{!, (.-:3. ) Lf:.:NG71! ct= fltf+~ v.JG ( S ~ . '2.!)) DISl?'17\Ja: 1'14-~ o1----r;~~< .ctAN6 ::-ro m6 6F P;ue/ = I -3fo " CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 SUI.IECT I TITLE 8uc!<~"' -, R A AJ 'S t:: ~:;e~: o T ~ c, H '-(J)v) p fl,t--s s: u:; N St-A-t_ REVISION 0 QA CATEGORY I CODE CLASS ~ l t 1 k D w"" e · 38 %;; J:f I t ~? ,.,0 j.,.o Fr' (f. ssV YJ~~) ~ '---~....! ~ ~JuM~ J1U!..)<.I-i-O.O •..J t -; ]).l 'e!t-~ lNG 01) f;""R I" W(f) ti" ARKA G. 3 r;, ~t;:-;~!AIG =-(f)(IZ f,) £>~ "'N D u11 c. l II) B Ef.\rtV1 G l!'t w ~c~ Cc1.. u 1111 N r. ( ftS~vAJlE' .;,..c....:n..Jli'..'J Pito\leRTIE'S. P~ fTJ 18 J :=. 1 s-et .;. 4 c= (1.4 8.71)-3.1a u = s:·~p = 'T 't '"":;. 15'1.:;_,d :2. 5", ~ ~ '3 --:::.. c.. (pI I 'S ~; T 1'5~ -· \.J 41-~s __.___-y ::::. 3, (o :;_ /0.3 ·~· t /2 11("·~75") ~ (c - 4@ J.G' .,;.£ -I )1 f!A>t ~ 0, I 0 i I JJ k?. .... \2.. s, -:. o.r 0 11: e:,.r 8 }7 I< I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULAJION NO. IREVOISION 45010.61 PRE PARER /~TE Q,U_), / :;/7'"rR SUa,(ECT I TITLE !,:_0lk)..}c: t' 0 1 - I f. ~ c.. I 5 soo. c8! s-/~:)-:A I IREVI EWER /CHECKER I DATE ·. IIND!PEND!NT REVIEWER /DATE :< .7 3'/.d') Ct-\)]:0 £ Lh-1) ~:...;;: .... ::-c ":!../7[ :.,..,,-1 I IQA CATEGORY I CODE CLASS -D I Ut'}L\ ' r;n...) f ,¥,/') ::i< r,_.JAY ., li_ $ { I~ 7 c ) ~ ( 12 '/: \ '2 S, 9 ~, (B,A7u)(J"L~) '-..:. V~T(CA-t_ ~P SIIS<I) Lh= J4.91( INSPE"U"'~ 11-j):;;, D(S'( A J ~~ f.H;I(t~L oC.LVR.S ItT" }OCTO c~ ) I I - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION ... solO s1 I REVISI ON 1 PA81! D 3r:J I .1.0./W. 0./ CALCUL~TIOH NO. 15700-o '8 !'S-5:'13.:< -;;l.. PREPARE:R..(DATE bw. f-0..,.....-;:p J INDEPENDENT REVIEWER/DATE SU8.1E:CT /TITLE ?uLk~Pf' !4.zos'" 2'5:.74' ..,. 3~>G". 7 SO-H-@. 3':£.7%.~# 14. zoo'"' m: :: 14-.G, 5~ .tf e J'f,7%# 14. 2o9' >: s.S<o;r:t~, ~ ;o. "S splf ~ 'JS.7%p/1 , F/.l'of'){.(! re l'xlo" 1'3u ... )l /2,G""f.1 i.G, : /(:,3 I~ 34 *,.;;..p Wet; 1:(' .1'"'" 1 r;: 12 W~J1? x~ 8 )r 17. /7_ 4.;[) ex. ~#'A) 1.1)1:/3 ~·· 8 ~ 17.1 11 ""'q .. ; )3, 137-:; I;:: I c;,~ I 17.12 ~ . .s-ce K x ,..,. 9 ~... I li:AGJ,J 1$, 87[' 1 :. I :r{: t7.n ~ s. sz e n: ;x zs: z,. 2~ ~ 49 , I t?./'2 ..$. -1(,. ~ 52. 9 3 @ It ,. 2S:s'Y, 3wl-l -<C..\:: ?&.J(i/~2~JS.?,~ ;) EA41 ;}(;.57 ',. SJ. l<f.Q 34 ltt_,F .),~, t«AI?•..:G ,;u:x:.l<~. ci~P<W 3;;._"~1< 18'xl-"G ftx2..x /!.9 5e-A1...s ·• 'JJ'sfT-11.. "s·""1 e ?o/, (As5\lNtru \ ~"d''•)At.I::!AIC. SAA C.,s'@ S"',/o~0 ~ "x 3 C...l../+MP &l'ff!l-c; @ 7. (oG -it:-~ !4 1@ 5u!t { A'Ssut.?Gb) 14'@ z.r;~t£.~ )4 e 2.>s~/, I,CfiJ( 170C) ) I 8D7 J II '1 857 /97 33/ 498 70 3(, 36> /2.0 I QA CATEGORY I CODE CLASS HoM~:;'IJ-r . ~..,,,,~T -'}<;...,1 ,e F/.!""...c o. 4-"37~ S'"71'1 4.8 iso:::~ 13. 5j 5",0'14 /8.5 /6J;'54D'" /8.'5 41 733 9.# 4..q!:JC; ' / 1.41 4.. 7k,S 744 '3,!95"" (.44 '3.d.. I : /8.') 3?,4-2~ 19 • .S 2(,(? Zo /1 ), 38o Zo" 17113 Co r~o. 3, l3C., / r. z.'5" 0, 58 f 1'1. 44 c '19 ;,<.?' /3 II ·~;o !/. nr; 3'71 14.g7f 5'"3( 2.5 -3oo - ~9! ,-.-5"" "" I )::;)':;;, / ( ? STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET J.O. /W.O./ CALCULATION NO. REVISION PAGE )5500. 08 ~I REVIEWER /CHECKER /DATE t-P-')}-[1 e,r_.r-t.Jc I.<C!Tr; 1jz QA CATEGORY I CODE CLASS DFst(,.r-...::J LLFr,I\JG. LUGS c~R..EO orJ ~ Po;~Jn Fol\. 0-<.f:/!&f:.NCj Dl\ll:~n.-) OPtlilfr1 _,,.,, LD/77-f ~-lli' \ \.:: "-\ ~ hJ 3 ~ ~ 6uti<H-tAO 1N.Sn'l.ll 1:?0 i.J A._c.w /t1Uo R.~l;f) ...um.r Di~~'Jnh. 1-tt'AD I C~"'D ~I 1~101'\.Aul.!c:.. A7Y D .,)_ ~ c. ~·JI!.k 'JAT'i::D 1-1/-e. & C'A-w.... 01 f3 1 A-rT,....-~...u;,:v=--~ --=-tl\1... LIFr' @ /D()O c..P..s PUJ--..) U.CIJI..O B ~ c;:-1. 3 i<._ A SsvA.<•f'.)cf, flt :.z · -~~,) &:;~•otr..~Jru 01= Is:-' DifFCIU::~ \~ 4~-JO \)~P.u.JO~t-l =-Q_C)!I. 4MttoJ6 UJo.vt..D 8£ <::<: \/\ ~' '-08&t-+1 : b.l + /07o -= ~4 1<. .,_ lo% j RJc;<; 1 N c;, A-!;s u '-"-E I k. \ co 0 Q)4t ~ 0 <""- ~ ~ Ll 0 a s \--~ \L :; "'- ""' -;:.. <I;. :) <: .u "' "-::; () -t~ \) ~ t: "' '::( 3 ~ .s: Cl ~ .lJ ~ 0 { ..., "" . \31Joy~ ~~5"')(pA2.4-rvJ+.'t_,3.'d7<;'>t ;~;, r: 14~ S.r&.JrJG FR.Ic.:n..tl" ·. IJ"uote-,,.~~,. ~f31f.rll)6 ldMJ "'7 ~~Aill/11.:0 1".1.1C..j'~' P~ ~~:2..4':{_1s-'?(l4') +71:.. :::-981<. 5'<711_ 'F~ttc.:rr...oN Ass()M_f 8 11/;, PR,e'f ~ C.'5 1 r-/'2"/. .><8/u ~ 0k-1"' [W<!Cit<<.,.,...,.l<:.): \(b7.4)(1r~(Lx~:-:-)c s,s'] ~ r.s RcJ "2- fOE /-72-£1 fY/·JP t-J-4-E 7 ~-;,a..~ 1-?.8-r; s,,.,u;: TH€ l.l!'liNG Ll.fo':> LUlU.. Auo ~E. USDJ ,....,j_~'l..i" \.)P -·-~ C:•JLkH:f·:;) -'·:E___ t .1, W, \..o~I/\Ju MLIST 8f (..m,o~l!)t;u:O /K:nf\6 -=> S ~ ,,'J .:.c._ 1 l_,P, ·~ -r/i1•'U"f'tJif-r; iJJt: Sl'i2.r:F+{)tif!. !3,.4-~ ~~€ L}u'-/<1-hAD, J.\s. .5/f&vJN ~I..J ~~ .5'JJ .,....~ 'itJ, or:~ G,+1't: ~~ I+PPiflc-!t,voMny J!....;e;" DQec.u ~ T,:Y.(_,, :f':e. U'-.g{r 6A. C!..fA.t~ VI:71.T7LA-t.!, PrR.~t-L)5FD 9cTu.Jt-.N T1+f SPI«:40tn "&!1~ 1 BUL/-'.l.J-~r-{)1 <:uF;:::-rU:/Jr /We_._., Musr .i3e-fll4rlrDf'O F& Dt\Jt'"\ .Ae:a-:s. SNo: CLCIJ.RhJCf<: u; /JG A f)P.RGt U.ULO ee-A P14tHBVI J MA.K-t -rJ+f <;PIU:.r'OeJ 'Jf.-R.. ASSi:;t/101..>{ ,_!r;-;>! -:_..,. J) 1'"0'-'S (62 k) Don: c ~>rJ.-JSIC C!MttJ RA7eD c~rfr't ry l/ssuf11E A .r~_..;671( nAA"G1rJ cr 4 "'< S" wP/i;./ ~n-H ;)e.:IG~ fJA.hVIDt-~ Fe~< A F~P oF ~::::r::~"j ~ 2. :;;INCt;< ...-:.-;-cor'(): flp£ 50M.~W~ UtJft/\Jrru.J}J J ~I{=,,_) ~ S~ ~N~CIJ~ i=&l(. -... J/C.~ ~~ t:s 7 7M.P-('t':D Lof'tP so -r-rre-ULT'I'1fr1'€ c.PtfJfK-l-r7 oF 7ff1; srcn ~ uLntl1JI(f U'PP..~c~~-or-~ suNt:;s, I ~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./CALCU ATION NO. 1r-s-o o. cs s--Sl5~ _.. REVISION PACIE 45010 61 ~EPARER~AT£ V.W. o-r-r.: SUBJECT/ TITLE ~ ::::'u (., \. t'-411 7~' PlrJ 1- M,o..): Si~ CH-t-u<.. 51-tt.M l='c1t 51-l-t:::A-R. ::../ c.zk .:;;; • '2'8 '3 .:.... 7.938 I( p c.z.lc. fp=. (~,,..qS'(_!t:nw)-(_2.•)[,•'')-:.. ~ 32. OA CATEGORY I CODE CLASS 0}< < r: :-o.q ~ = o.~('So14;-._) ~ 4SH~ 0/( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION NO. 'REVISION 'PAGE .so10.61 l5"'£"oo, oR Is-s;<>:;;--;:, 0 3 J PR~PARERffATE I ~ /a/ IRE.VIE.WU /C·H· ECKER /DATE . . . I INDEPENDENT REVIEWER /DATE !),1)-J .. 't:;-r-r;;) 1/8/z:,<:::> C~·)-+-,t, 21_;A:t)(tJCrf~ ~lz?/1!,... SUBJECT I TITLE IQA CATEGORY I COOE CLASS D / :....-;uLJ.;t-rr:PD bHC r---~~~=---~~~~-----------------------------------------L--------------------- (_!-IP11/VG £ i.JG.S J ~' I) /)r_)\t?i"'JG SP-vle; ~, !'!,...) -ot... -- Wl!"l-D5 ? .y c..?. }:. 4"2.(, lc ~ ,...., • --:. -} 1'\ s :J.x 17.12:!' 9.:3~'- = !. s I +-C)' {3. " 2· z4-:itt I' 2. 24 ~ F1i.LF 5/;>c ~N;>'tJ :: (o.7o7)('5J_)-::. (Q,1o7)(Zl~<s<\... c. 1:) ~, IN')f>~f'J t..tJO-<) L D -rA;:.. I< I L '«._ 7 J1b: (r;~k. p =-2~ ~ I.VIJ ~5Vtnt:f {.,.o/f/) k_;:{l/'J6 ol'\l OAJL/ O,f)c }; I' ri. ---------------------------- ~ = G.4S'~ = nS~-'1L 0/4 - r Ck - > PJ,?!PI:tvDI(VlM ll::""N.H~ l4AQON ;:"l.fl,.!'Jf,. ~+=Co2~ > pb~ -: &, "2 ~ (!)/~:.... e)> /w~ ft} .f ~fJ ~ {j_(j; kJO~s)~ 0S"t~ 7 3 k ).. ~} :::-(o l ~ ~ • _ \J~£ \tJLov?.~ CALCULATION SHEET SUBJECT I TITLE 8 v u~_ l-k.::: ,.. STONE & WEBSTER ENGINEERING CORPORATION REVISION PAGE 2-34 QA CATEGORY I CODE CLASS ~'~t~f-: I. ?l7!i'" _ ~ Wt'l-D :_/~ _z~'"'"" c::o~ '2 !:t ,. Ptr.J 2 :1•" 51»~<-'"LO"" $ J/Ji/87 -= Pe = {jqt.k )(,, 9 J7s-') ~ r ';l.O Jc-II ~C 14. s1!:5'J-:= 1s.7.r'' ; ='11 :: •}1-. 37 J) ) \ {fo'L"'-;"20' l. (cO(. \1.. o/ -= ~C~ + ~ )'\~) ~ -:c \ \(<8.7!' ~ GB.')} .;.-\:2_s.7:fl 4.5 "'/t, -= ( o •707 X 2-/lcst.) ~ CALCULATION SHEET A5010 61 PREPARER /DATE }),w. Po"""T""-r>CR SUBJECT I TITLE 'e:>u._\<. STONE & WEBSTER ENGINEERING CORPORATION J.D./W.O./CALCULATION NO. /5<; 00, Ll 3 / S-S" I]::?._-:Z REVIEWER /CHECKER/ DATE r_ Pnc tJc ~---lhEic.,... REVIS I ON PAGE 0 3S,.... QA CATEGORY/ CODE CLASS WH-1;-,.._) r•c..l:...trJG 8\Jll(Jh:7\-0 ~.1\ /*'tl,J:tc.>N-r-A-i_, ~· ~· 23) LifT fJt:: tQ ~ (2ok )( 7 t') = )4o )!_it ~dL-: O"K/7.12)'0~ G V? 20k ---117.1<>" ' ~ \ _\_ '1 I II "I Cl ~ 51\r~"""i''~··• ', "·" ; 44-1:._ Ltr(tAIG LUC. V5e5 J S#;IU./t (;;~ WI'!? J 4 f'·,.j I .J-f G,4/' t-In.. ·~~ ~ r pc., 2'S, "l}...k PILl< vJ/ ~mo,.,A GA.fl:' x., 20 k ::=") I ~ v s~u; I~ "P'lli 1 J k. ;, :.or!' '-2::x:-r,t.., l -K> i p:.,: BoiH s-lfF'(.J<.LEJ , Pn:>~·MS ~ ~ t; -9F1 = 4~-~t;~ p 4--f-" l'P "' lr·"'¢J~ T1<)-=-Cz~)O~)"' J I ksZ ~F, <F.; ~fr.J.Ct/IIG I!J..) SE:r--M 4ssu~ IO"x I"' -r)l..~f:t l..eft"VING 0 ''- \" 17.175'-3" =I b" 14, 1"1.-i 1 aY' 1 r == I, 11 o -3 7 ~ -= iiI p 1' ' -~. \ 22. ~ CALCULATION SHEET &501061 SUBJECT I TITLE "?'-JL k:: - 3s"-{rss'~9~ (3'-~" 14'.,. <.s' )11'1, STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULA7T.ION NO. JS5"6C>. O,g !;-517'2...-~ REVIEWER /CHECKER /DATE C4 \Jrv ~lftt.Jct4-:; "J.-h.!IP.f R.e'F l-lu._,.,.,t-J6ic.-.l ., E.,_y;,iiJI.?CJI rAJG Lu~Jt-1.147'~ Mf) '!:P"'-ur:•' 11""J:JN.s. F-t!:r"' lWPihtJ G/'.rs-s-<:YH_ l ) . I ; II .<'' z J.,'W! j_ I A-= /~u !.- REVISION QA CATEGORY I CODE CLASS II' p~~ 3' \( -··~·' A.5'5uM..€ ~·-· p~ ( k 'l>e;,q~-t .... :) p f4!:,~f L 2. oF -n:>'i'/'<.'-. ~~b 3~ 5~ sA-J so/~ Will }.)t:eQ '1"0 Ce#rp;u,.;..s "'P S't:l'ft. {-v IJ.4 ') MO sPr<wG)-= ~%, )( ''-:.f + s.sl(l-z%) ~ 0 · 73~ p SAt 6/fOO u,m.,;rr~ y I"'-(,) 1£ IS 5 1 60c::J f:, i, I 321 ODOJ7<;;; 31 y;oG /.$~ r 30.:<_ J31'( r.NA)t::'"'L ~KtJJtfP.....s STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .0.5010.61 JJ.O./W.O./CALCULAJION NO. I REVISION I ~AGE ;s-s-oo, 08 1 ~-:::-1.3:2 -~ 0 .J7 ~EPARERLJIATE .2), w. 8:,...,.,.-::.f' IRE VI EWER /CHECKER/ DATE I INDEPENDENT REV I EWER /DATE Cf.\JT£1 '8-Mtr-+r::--nr:; 1-/z2ff~ SUBJECT I TITLE Bf.JU_ LV(:A.O bA7~ F;,f{(k CCAIJSI::D 37' Dou:c .. n..o,..J' 'Pl3 bcP A= 1BE1 r:-I""L 48 ET 6 4'6£ I b0 3 l.. => p., L. 'J :: D n. Ls 41: bd 3 4 ., 1,.7 4-bJ3 % ., 3/x/1.) '3 P-=-C,. 2 /(/0 --tr:: 4 ":' 2. 'E-; /'-:,~ =/ L1 MA:><-1\~~f.C>L€ FoRe.£ r=o~ SPR.1A1~ · H H: PL. ~ \I>= s ocl'-S-:-~ ~b ~ !t 0 PL -:: 4cd'-bd'- lo P= 4-fbbc}Z.. GL ,. ().)k;tb J.b ., D .7:> ~ (A lsc. ""ll-v I I. S',J,<::t. s) J AsSu'-'1.E ,(::b ~ o. c, r, S,NCc -p~ ==/ G.z. 'J'~I+!1lJ:...>'> IN A . 4 ( o, ror=z) bd ._ (pt_ 52.6 ...::. "P"' Wm~ f-j :-Is .Z. 1<-s i bd 3 bd 2 4-'/ /0 L._J L.. ~2.8 L _d_ 5"2. ''0 L'-<. (p. '2 x ( o.!. d ~-z. -:::::..'? ~ /17~ I QA CATEGORY I CODE CLASS ·- CALCULATION SHEET .. 5010.61 PREPARER /DATE 'i) ' (.}_J ' ~0 -r-r·:;I"Z SUB.IECT I TITLE 8uL!</~.D If. L-= J4 II L-c.. 2oll 11-L-= .Jo ~ STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./CALCULAT)PN NO. IREVISOION lp~8E 15)00 '02, I::-s I~ 2-:2._ 2l IRE VI EWER /CHECKER /DATE I INDEPENDENT REV I EWER /DATE £?1)1:'(' ~Cf-!Y<:.c::fTE 1)t2/8: I QA CATEGORY I CODE CLASS I ~ 4,., c ~ )17.5' = o, 9 ,, a.57:: ~ :~, 2,\(0~ ~j3 . p.D ;_,3 - b --(~~2K/~4)(J 7)- (!. /<){24) 3 ( ro, nro 4 { o · ns-]3 = d <:_ (j, "J4 II s" { _ I/,, c -r._ ~: C,. 2xro 4 l:x) 1 --L7 (oft_ -+b ~ := 4hd'- r 6/< -fruu:.!+e"QO WI'Dr?f-~eA-{J~ 6~1: W!i)T!,.._ -17"'' -21t I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION m··] /v'lAN/v1Ui'-'\ S.PttttJG (;, E -t 6, 4 = Yz...l' J.O./W. 0./ CALCULATION NO. /,5"fJOO, 08 c = 31 'Xfo? !4'-: -~::~ ~ '1 /... ·-Ja e~ REVISION 0 QA CATEGORY/ CODE CLASS / v '?V 3 < It -) tt ::= ;) 1:.. lt 1 Pur CALCULATION SHEET .. solO 61 SUBJECT/ TITLE 3uu:~cl' 8E't-R_:~o.G :3LDCk: r STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULATION NO. REVISION /Sjoo, oc:a :::;; -s; 0 QA CATEGORY I COOE CLASS 12'-&" ~~--o-P::-t-tv--.,, ... \Jg=- ......-r -~ ·-------------r-- I i 13'-J34. -=-1----'"'};a~l::-1>- S~L c. l q\R fti0CES \ f ' I) I --I I I . --1 c;'[ ' I ' ' I I ___ y \ 9. I\ -j /1-7" " II ~ ), gcy' / /rB .~~.18° j CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION A5010 61 PREPARER /DATE D. W. Po-r-"R SUBJECT/ TITLE 8\j\._)., If-orA I 11=~ ....... ...... , _, "' ,...., o), ...... _, "'' REVIS I ON 0 QA CATEGORY I CODE CLASS /~)00-~-I]/ D !) ~'7' 2 2-'22.. CL ~AII!rr"" <.£ 1"~ cf St1H -ro l:l)(PI:" 0~ ~- S urr:-rc;~;;ur 10 w ~.XC 5.oAL_ ok: CALCULATION SHEET 45010.61 PII£PAR£RI~T£ 2:). \J...), ~o"'~""'""'";.;.;fZ. SUBJECT I TIT I.E BuLk ~ s (j' -·' _, "'* .. "" '<) ~.J "-_. rei 7 ~ STONE & WEBSTER ENGINEERING CORPORATION .I.O.IW.O./CAI.CULA ION NO. 1 scs-oo . o s s: - REV I f:W£11 I CHECKER/ OAT£ 0 A-l)TJO rd-'" tY. r.o t::~ r F " G lV ~I 1 i ! p,= 'I ==i I! ! I llf!VISI ON 0 QA CATEGORY/ CODE CLASS N I N CALCULATION SHEET I I "" ..... .... \..) .t ""' i <J ~ "' \ STONE & WEBSTER ENGINEERING CORPORATION 5-S!J.<- c!. 4 Cl" ..: ~ ~ < C; l- ('V ~ >{ >1- :;-I'- f'--_, X. ~'* X s -'....! ~ ~--------- i ---+-- 1 j l _., ... , ~I V)! --\ : ---~+ ;. 'vf lfl ('I) REVISION PAGE 0 4s- QA CATEGORY I CODE CLASS s- ' r-----~ <..U II ((j ~ ....._ c_::; ..... ..__J ~ ~ )--._ ~ \.L 'j\ '-. --.; ; CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .J.O./W.O./ CALCULATION NO. ISSQQ.05 S-S/3:;< -~ REVISION .&501061 P~PARE~ATE jj.W. 1-br~ SUB.JECT I TITLE 1?uL 1-rl.A.D 7" 12./1 (o -- 5'' 0 QA CATEGORY I CODE CLASS II u I ;{I(} rj; *"t.E 0 -4" e>. <- l /';'1. ~· ~s. C=>k L•.t.c ·:~.-.~./'S.S. \i~x !.lvr~ ~cct w~r-s;c;:::11,. Vs' Sa\t Vtcl::l 2:______2?.;~~, 8ACJ<.11\JG ~,q/1,, 1:.0~1.) f..3~ ::,-~c.;­ -~ 21.('1<. ~·· c.. t.!tMP i:lf>.R) U>I<.JI. ) A 5<D ~.,.., ... RouiVO Ce>RIJfi~ "...\''5e-l'IL 1 Soi.\'0 ;:;:'ULB 1 ....,)/ 0.030 Y../8c: F.C. f;'J~_M 1 c;,ji", A.PPL!CA""' to!V ot: 'J • Sf>\ I.. ';;IM'-F"ou.o~ Plttx.-o•;~f "-<COI·H-\~l-'0<'0 B'f 1'-\l'"G· 'Der 1\ \. \. E v~~'T? C::::I'K-:__:.:::=----::-=-'"-7-'=- ---5" X 1~'' )1: ~6 '' . ;j" Se-AL J 'S.:>Co t> SuL!), C.,...n:;) w/o.030 11 f./8o"/-.(. r!<.M, 'Yt~·· ¢ '-'<>lt ) o'-4-' o. c . T:o(.{ ~·· S5 CSK ~£:; Ei'::n_; wj S,S, ).\-€,\ Uf.Ji £, •OC( et>t,o, , ~f-) 1. , A 1 v, .., r:.;..~ .... CALCULATION SHEET •5010.61 PRIEPARER ~TE ) . w . . () T""T '~'"P. SUBJECT/ TITLE BuL STONE & WEBSTER ENGINEERING CORPORATION '1;,14 ",f Ito~.¥ J 6'-"-u o.c. 17!1~<_ Yz.. ss. C'l\<.. ~0 l!.~tt.T w; s . .,. . I+E )< ... )!.r• ~ l..cJcl<. <U/1-S !-' "R 4" f.to~rfll6fo~ Rvai3FR Gt-rE" SEJ\1., > K"LO 47b 7 0~ SQu)h.. '\)l?{'J\ L L \) ~T'0~"' S:t P ..... \... REVISION () QA CATEGORY I CODE CLASS \ \ / CALCULATION SHEET A5010.61 PREPARER /DATE D, W, 'Po -r..,..e SUB.IECT I TITLE BuL :-t :-- I I II II II -----~~--------- II II II I I STONE & WEBSTER ENGINEERING CORPORATION PAGE 48 REV I EWER I CHECKER/ DATE 0 Au TID G Utfl) c-r -J.Jzz I!!:.- QA CATEGORY I COOE CLASS 41( (i W~R 1Y R»'-"'0 G>wa 1 / ~ / '11 7. I I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 0 0 ---- .1.0./W.O./CALCULA.TION NO. /s-.)o(J, 08 /5:'-~IJ',;:? -)...., REVIEWER /CHECkER/ DATE ' T.!J i?:J.fi~)C~I _ L '------'-tr-- -----_l I'' -t -! ~I REVIS I ON _:> QA CATEGORY I CODE CLASS -g:-"i' ~~ q:l'/ / ~ . I·· .. ~.~ ~­ "" ; -~/ !/ _l __ .!, -' I -~ / CALCULATION SHEET &5010.61 P~EPARE~A.TI. J), \1_), J--'or-n;:t-<, SUBJECT I TITLE 73ut..k!-l-t.-~O STONE & WEBSTER ENGINEERING CORPORATION I.J.O./W.O./CALCULAjiON NO. IREVI!!ON I PAGE 15""500 08 ;S'-S!<Q -::L_ CJ :5(::) _/,~ /_ I REVIEWER /CME.CKE. R /OAT. E IINOEPENOENT REV I EWER/OATE 12flq8s1 OAYJ( G(_Af.!C-"!Y':-"""r-: 1-/7.!/.?'.6 I QA CATEGORY I COOE CLASS L -PI\ 11 'J (A uflltmr f-" 13t"A~WG ,.,o, 3 1.010,;, /tb IJt!~>'Mf+-r .. ~t(.J<Jtlt~~~ """=C~fCJ+U( eal'lD/::'0 ""to A3t.o 'S7n:l,. eM>ec Ptft-r~ ..--- ;;;.4 ~1.{) lyPr? 1 a ~<-I!'C> ~~ Tv PE 1L /~,..2-11 TlfP€" r 8 \1 T'1PE:f 1:["" CALCULATION SHEET .. 501061 P~PARER /DATE .. 1 ), v-J . 1-bT -r:-.:.1( SUBJECT I TITLE PULKI...H:--P..D I STONE & WEBSTER ENGINEERING CORPORATION I J.O./W.O./CALCUL~TION NO. !REVIS I ON l PAGE /s'5"oo. oa 1 ~-Sl3.:< -)-.. 1 s-; IREVIEWER/CHECICER /DATE {....... r 'INDEPENDENT REVIEWER/DATE DA-lJrf fS::.,Jd 'cr-~'1::: rrr;: 1-J gygr I QA CATEGORY I CODE Cl.ASS - !) • ..,,Porr~t. 3·'25"-~10 ~{ Do R.?J l,:.lo/J 1 IV Y/t.11J S11f:t-vQ;1';¥ Z, 3. 4-, bfLB /~u. wf'~ 5H1\<..l Se Cll.vit,..Uvous. 7.4 F'Ll~1' -U;.JU::-s::: A.X:>TC!J r:;:f>R-tNG ~e<.. MA1GRtP.t. Sf/"f!LL Be s.n? .. 'NG Sw::n.. SA~;;-5"'155' M SII. 0 "-'' 7"'7..! 7'/1? r 0/!Lo-Wn't.KS J?A.t:?>Pt:-P /7 {:;:<:" 1~006 Pri ULr;,.nM£ lg ~ 0°0 Psc '/1612-C 3B::<-3G-z Bl(,.v-ua /../-,..er;oo~C-K:c-' E ::: 3 ~ o oo, ooo ;si 5'". -r-w o G A { es;.. RA,;-<?:j> u , ft..e"D t:: -:<~. 000 ~ r::..srrMAt:if:l ~tGl-f'r ot= r..A7"1F" .:: ..... ~ . GAT liS. MA( 1?.. E" /tuSTJlq ED . 1t--.l fltk.) of(?).J Cft-1" ..-..J;Vt; L Ftc •.J o"" I OOD C.!;. ( "'-'A7'c1Z DEP<~ ""' (o ') A'IVD Re-tout:D WIT1-I A 1/IAA/MUIV1 Dtr:=-r:tr.fil.krJ,_f'-~,. '..J.Jf-~~~ H1:lbi-H' OF-8 1 • Tl'-lSTALLiill""'J ~0 ~ovA-1.. l=oR. A.u .. OT~R. L()NOI'-'J,.::,) '6::1-11\(..L. 'Qe UM/EJ( DitLA-ri<:.kt:l H'ln\0 UtvO 177-t>NS. CALCULATION SHEET A5010 61 STONE & WEBSTER ENGINEERING CORPORATION REVIEWER /CHECkER /DATE Df'r\)W €f.Pf')( u ~--.-,::; tiz21 g:; +--i M~t')<Cl (e8J~<r.t l-fv#JT(<.(jto~ ~-<o(.[) 178 3 ~ r:::::;·Jfl c. CALCULATION SHEET .. sow 61 SUBJECT I TITLE B.JLJ:: !-1--eP-£J STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./CALCULA'TION NO. ISS~a. G& S-517~ -;;.,.._ REVISION C) QA CATEGORY/ CODE CLASS STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .1.0./W.O./CALCULATJON NO. !t;§oo. o& !5-S!J QA CATEGORY I CODE CLASS q!.t'' S~4419l LITTON INDUSTRIES INC/ 'HC oozoq CAL-c... ~~~oo.oe/s-s13 ,. --?.. SPECIFICATION FOR LUSRITE F" BEARINGS A"Ti4{.#. A L Bearmgs w1th PTFE Sl1ding Surfaces /~~-·----.., -----·~ ~1\jD\'2; LvM •"!"! m-r us~ ~~ '· A. Matenals ··~ j::l~Pr\... ·:? · ..;o,J. Mfl:T~R'/A-·1 ·--------~1'1-.:z;-:> :...ver..&,.) . r~ ' 1. Polytetrafluoroethylene (PTFE) self-lubricahng sliding surfaces shall be composed-of lew'o-¥+tgln f'7. 'Z ~ 1 unfilled Polytetrafluoroethylene fabric manufactured from oriented multifilament PTFE Fluorocar6on..__J fibers. The resin from which these fibers are produced shall be tOO% virgin material meetmg the A::-1 2. requirements of ASTM Designation D-1457. Specific gravity shall be 2.13tc· 2.19 as determmed by O'.'f ASTM Method D-792. Test A 1. A2 or A3. The PTFE fabric shall have a minimum thickness of 1 /32"' and a maximum thickness of 1 /8"' after compression. The test for cold flow is to be ASTM 0-621 at 2000 psi for 24 hours at 70 F. Properties of PTFE fiber shall be as follows: Load Borne without Cold Flow Ultimate Tensile Strength Elongation at Break lnitral Modulus Maximum Coefficient of Friction @ 3500 psi. Static or Dynamic 60.000 psi 45.900 PSI 550.000 psi .04 The above figures represent the ""Standard Specification for Highway Bridges"".-AASHTO 12th Editron 1977 The Application Test Method for determination of Ultimate Tensile Strength and Elongation at Break sha!l be D-2256. The Coefficient of Friction shall be evaluated in a test which simulates tt'le application parameters. The Statrc Coefficient of Friction shall be determined at breakaway by dividing the horizontal force to start motion by the vertically applied force which shall be equivalent to application pressure. The Dynamic Coefficient of Friction shall be determined by the same method. but at a speed not exceeding 1" per minute in order to approximate actual conditions. Welding to a steel plate which has a bonded PTFE surface may be permitted providing welding procedures are established which restrict the maximum temperature reached by the bond area to less than 300 F. (tSO''C) as determined by temperature indicating wax pencils or other suitable means. The PTFE fabric shall be mechanically interlocked with the steel substrate plate under factory controiled conditions in a manner approved by the engineer. The interlock should be equally distributed over no less than 25% of the bearing area and shall be sufficiently strong to develop 10% of the allowed vertical load in the horizontal shear plan. Adhesive mat~rial may be used to suppiement the mechanical bond but the 10'% development shall be by mechanical interlock only. The stainless steel surface mating to the PTFE should be an accurate. flat. cylindrical or spherical surla~~ as required by the design and shall have a surface finish of 20 micro inches. The stainless steel su•race shall be attached by welding or other suitable mechanical means approved by the engineer. B. General 1. The manufacturer shall be required to furnish facilities for the testing and inspection of the complete bearings or representatiVe samples in his plant. or at an independent test facility. Manufacturer's certification of all materials used in the construct1on ot the bearings shall b.: furnished. 3't01 LUBRITE F• is a composite high-compression bearing, patented by Merriman. Inc .• and manufactured exclusively by Merriman and ils license1n. The construction of LUBRITE F• is unique. A pad of woven TEFLON fiber is pressed onto the geometrically-grooved surtace of a metal substrate. This creates a firm mechanical lock between the TEFLON fabric and the substrate. providing very high shear resistance at the Iabrie/ substrate interface. LUERITE F.., with woven TEFLON fiber has several important advantages over composite bearings which rely only on TEFLON resin. 1) Woven TEFLON fiber has approximately 30 times the bearing strength of TEFLON resin. 2} The mechanical fabric/substrate lock circumvents the difficult chemical bonding process used to join a TEFLON resin pad to its substrate. 3) High bearing strength in combination with high shear resistance virtually elimina!es cold flow under structural loads and maintains a low coefficient of friction. TEFLON ls a registered trademark of the DuPont Company. The Woven TEFLON Surface TEFLON fiber is unaffected by weathenng, moisture and severe chem1cal reagents. There are stgniflcant benefits m the bearing properties of TEFLON fibers above TEFLON resin. and a woven TEFLON bearing IS suoerror in many ways to one witt.l s1mp1y TEFLON resm. The molecular onentation of the TEFLON l1ber increases tts compressive s:rencth to approximalely 30 limes that of resin. and yi;lds a propontonat mcrease 111 res1stance to cold flow. The DuPont Company released the foltowmg mtormatior. • Compansor. of properties of TEFLON PTFE fiber. PTFE restn TEFLON TEFLON PTFE Fiber PTrE Restn Density glee 2.1 2.2 Ultimate Tensile Strength. psi· 45.900 2.000 ElongatiOn at Sreak o.· 35 300 Initial Modul~;s. ps,· 550.000 60.000 Load beanng capacity wtthout cold flow. ps1 60.000 2.000 CoeHic1ent of Fncl!on. as low as 0.01 0.02 • At 7C'F. 55"'• R.H T~*! fi-~ure, g:~teo '" lt"~ts tab I~ are tor c~mparattve purpos!!5 -:1n1y Com;:lr~1s•·,., stren<;:hs and c~Nic,ents ~t t .. ;c:;cn of the restn.s and fiDI!tS vary ccn-s•deratHy ~e-=:~t1du''";1 on a var.ety ol ia::!O'S 1:1 CO!":"'';:'Ionent ces•qn and use. 3~03 93C OOZ&8 TEFLON fiber has demonstrated exceptional stability 4rtNP A ~z in inlermil1ent application at temperature extrem~ ot 425' F and -32tP F. Increased load and temperature ac!ually improve bearing function. providing a buill-in safeguard against overloading. The Metat Substrate Substrates are commonly formed in alloy steel. stainless steel and bronze. Since Merriman has 60 years of experience in high-compression bearings. the Merriman engineering dapartment can assist in the specification of the correct metal substrate. Configuration LUBRITE F" can be custom designed as bearings for expansion. rotation and/or deflection. The physical size of LUSP.ITE FJ' is virtually unlimited. and therefore can be applied when large bearing areas are required. Coefficiant of Friction Operating under loads up to 6000 psi and temperatures between 425 F and -100 F. LUSRITE P offers a coefficient cf fricticn that is considerably lower than that of lubricated metal bearings. Specific information is avatlaole upon request. (See graph. page 5} Applications LUBAITE F"' may be custom designed and built for virtua;:y any heavy duty bearing application. Successful installations are now commo:1 in bridges. overpasses. precipitators. tank and pipe supports. refinery operations, hydro/ electric gates and e<;uipment, and offshore dnll rigs. Write with details of your apo!ication to the Merriman Bearing Engineers. MERRIMAN. Oiv1S10n o! L:!ton lndus:r1af Products 100 lndustnal Park Road. Htngha:n. MA 020-!J Tel. 617-749-5100. Telex 494-0246 0 ~ .. ..... 0 FACING· STAINLESS STEEL WI 20 RMS SURFAC£ FINISH WOVEN LUBRITE F@ PAD PERFORATED PLATE-STEEL TOLl lANtlS ,..... I R. R. 0. . -.. ......ut CIIM&•••u ••u I 1 '""··· r...CTIO+II :o O(CIWAL.S S: AIIGI.U :o ••aH't-..;1 l'·tlll '---. ,.,..OWl. BASE PLATE-STEEL ·-~ ... .._.. .•.. ..,. ........... ~ ........ .._._ .. ,_.,..._. ............... ... ..................................... ............................... _ ....... ........,.. -..~ ..... ,__, .. ~ ............ ... ,..,..._ .. _...._. -........... -.....__.,_ ...................... . ................ ~ .. -.--.. -..-.... ....................... ' ~:-:J ll/2 MIN. ___ J ----·1112 MIN .. ...r. Lla llYIIIONI ['.JOTES I. DESIGN BEARING PRESSURE·3500 P.S.I 2 DESIGNED EXPANSION· UNLIMITED. 3 BASE AND SOLE PLATE MATERIAL· ASTM A36 STEEL OR ASTM A588 STEEL OR EQUIVALENT. 4. FACING PLATE SHOULD BE AT LEAST 1" LARGER,OVERALL,THAN THE TEFLON ~D, WITH THE AMOUNT OF EXPANSION REQUIRED ADDED IN THE DIRECTION OF EXPANSION. 5. SOLE AND BASE PLATES MAY BE EXTENDED BEYOND FACING AND TEFLON TO FACILITATE MOUNTING BY MEANS OF WELDING, BOLTING OR OTHER. DO NOT SCALE DRAWING I ... , W101...:1o LUBRITE F@ rn MERAIYAH Ut:aoft ~-..... -~-... "n EXPANSION BEARING B 341e121 ·""- 1 ./1 "' ~ ~ -.0 A r -rr-.-c/1, ffS 1 · . INTEROFFICE CORRESPONDENCE=:-· -~~----------~~~~~~~,~·~~· ~~·---TO: 1 LOCATION SUBJECT I REFERENCE, I J.O. NO. ,,......,_O I n.,.,..,..l ~ lA ;::>OU f-;;::;:;;::::;::-..;._~-;._;::.:::::::~~-----~O:>~~:::r£: •-'V!!::L__J I<J IJl.!(Ht"A£) {;It'"(£ /'"' 1/t( e-R.II'h.. FROM: .,..._ Ill l LOCATION u.lJ..>, ron ·~ z op 2.. MESSAGE:- 4-,) THE' CA-n: \.UIU.. ee JJJ~'71\LLEtJ ro ll.Atse-"J1+e" U:lJl?l or T1ff: REst"ltt.Jo(R.. 1\f:.Tia{ ~ ~P u:-n.QI\J . La 110 '"' G w tL.L 11f'EJZ.t'"'F<:>A-t Cf-fti7J6E s-LOLULY. TM.PAa"" LoAos Au: "~ {)fiJ ~..,~1 . ~ 71fe" Dl\/~loi\J 1\1.-.JrJ~:::"t. '"11+€ DBtGI'-l ~~ ~~ jQ)I. ftfe' GA"tt: tJ.J~ A-t-5o i>e"S\G.f.Jeo FoR Po~S19U;: LISE IN 'tt.+t Po-wt:"'R TU ~ "-'~1.. wITH A D~IG!'i 1~0 OF I (o I '. h.~t il+c I" I I l-h:7tf)) i1-tf!" MI+Y-11-1. UN., S71U?'SS IS <f<f% DF Au.trWIJfJI..E (,AJ 7E?JS£t!YJ 'Pt..Ar.ft:.G) . ~-J -ru..e C/+7"/f IS ,:ULL'/ W[;t.,/)1!'0 c..LWS714J c.l'U:.AJ /.J.J/71four 771-tF uS F o,e ~'<.1?7) tt£H1tfJb"'J ( 1'() MINIMICt! ()J#i!'l6/t(), '"fH1.s ~UL r.;, I.N jQ (S,RArft-r" DE1K., OF FILtgt I.IJai)t#G • tjf€ wftl.Oe() ~F/Gu!!.JrT!b.J Is f'l+c-wrJ OA..J 1'lf'e ~eo c..t>Py oF 71{-E" P~rAJ/ttfJj f>flArt..JJ,JG. '&~ 6J<,.) Tift$ ti'IPdll.M./+"tunJ) We-W~LO APP~It£C. '/trUI\ ~1-•H:?UOI't't'UN-}$ o,v HA--r~·~"' 1 L..e. A'517 c~.,. IJ As7;;~, Go( so) AS'"'a2 oR.. o-r~. Yo-u" C..OG.~Ottvlr(wr-J w lnl ~'5'HA-'L CL.4t(J{ UJC>uLO Jtt,S.o 6€ APPIU''-IIr"t'l;?(), As. THtr DMWt1116 Is ~~ TltE (e\J/!;LJ Pilo(.eS"S 'tt:x~,._ U"Sf~, . .ue WtT'Hf,.J otJE we::"'/-;. AF71::.7{ KA::U::7 "' VJOVLO iJC N 6 J r HeZ.f'F<Jt.. _..::3-;_4_:__-8~~,.------J-£)~ PKk (9·~;;~-JM DATE SIGNATURE TELEPHONE REPLY: SIGNATURE TELEPHONE A 040.138 MESSAGE: STSa.s Fo~ 'DIVa.:stOAJ TVA.JI..JE<.. B ULk.l-fallJ l!;frTES You I.NOICA7i:7:J ) A Poss 18~ FIR..Irrte" FI(Ac.TZJ~GE 411.£ illti CA7t! IS I() Se:(l/IC€ P~GU?1'1 WITH A57J} G~t.. st:> .47' l..oc.J ~Tt.:LES, A?vo LoAOFf) "T"lE Wlt71Pl o.I\J oA.Je S!()F A..vo I 71-lt:; 4CxJ 1 t...cvV6 o,OJ:JV DIVailo...-.) T7..JJJA1f?L OAJ 711E ~ S'I/Jt: 'SNouLI) l',(!.of.IIOE A 5"17\Sl€ TV--tP~-rutlE 6eTUJ~ + 3~i=' ;w0 + 5o"F. WOUI..o -rlto t?e /AJ i'/t'G 1\A-NG€" oF ._.. PoT't'NT'iAc PUl&leN.S ? fl-k Foi..t.cwoJ6 ADDITZot<fltt. IAJf:oltM/t7usrJ MAo-( 6e-I+E'LPFUL t,J ~At.vATi.J'G Tl-fE" HA1t:?J(IIh. : I) 1-\t<;U ~GTH '~TEa. ( ry"' ~"&i.) ~ 'SPEUFIE?D 10 l..INIT WlilGitT -:2) Ar;;ag wA-s IJR.U;,If'/Au..j $PeXfFifE0 eur w~ R.b\JISE'O TO AS7:1., cl( so buE" it) ~N<:.e'R.JUS A~r DtFFicV/..r/#.r~ ,,.) Wt:LOtd;. i) 11-t'E" BULk.l1e'AD C..Ul.O eE t:)cJ>osE1) '"tt> Low~ TI!:M.P~/t(U£Ef {-~t") wHit.£ 110 ~7tJ/V6C eo,.1T ON f'il· 2. ... z U::.'. 1--ltk;.F ~,J ~:SHAt.. Ct.AU u.;,{~l. DATE REPLY: DATE ... 04().138 8u.L. ~M -------:-=-""=,...-------=~~-I:?Q V~ ""'---S SIGP .... TURE TELEPHONE T-(!i.Jr'"o.s N. g,,:r H DP. r SIGNATURE TElEPHONE '•:·:··········. --~~~:' -~: -~···~·:~:·~·~:·>>-·:·~···· .• -r.i::.. ~f-4tv.;e. ~ +o 'J,J!A"'e~ of /~ Sl2 C-<t So JS V\llAr:it~1~\ Ct + a,__ J.r-5..1 ~ . .,.. \elf/.. pe /'4. ~.A.t'.:.. c{. + :, :: ~ F . 'o .:t .:c. J .c.~~ c. .. \,~ .r(.{ h~ f(. ~-c-~J_e_J --~ DT . ( v.tl -JJ c t, t ~ +/~~ __..:, b'-"'"'U.:l·_lkt..-<. l {'tM,p.f~~~~ of -'\.. 3ocF \vo. _ __c_~~..if'"\ V-~"~"h~ Te.d .. ~ .. ~~~t1t~tV\J ~e:..t +~~ ~~£'{l-q..\t~.vw1'_,~ .1a:t 1.; l~_Lu:t'Ml~~--JQacll'-1\. d ct.IA.rA .. ~-c.....f_ .1 .G!.C.C.u.L~ ___ j :J PIAl:. +a C.. 1 .. -~'-v-cu.L l_o a. J.s -j ----O~ 1:{..., __ 4---;Le_ wt 1\ cit""~ c: _o""~ slo~l~ :tk !tSJz_G<Z. So -.-4~ V\at ~u..c!_~_:L ___ .k Q.cv h ~ or~!.4-ll1 --~cce.p±-Jl~------... _ 1· ---~-~ .f>.,""Ju.& -=b~14 .GU shvtJ potld.t~r--tiA__a_~---: -------4-h, ~~\.!.J_c:.~±~U.Vlv~C<l lw-~_ of ~ A SJ2. & S"Qr1 __ J_ __ JA. __ ~-~ttMc,J tt~+ tk yi(e. __ MJjy,,j ~···-I __ ___1\:_~_~) __ .c_l~.s~ ___ l_. ._Tk. A S:SI clas._s I M a.14~.i bi.J _____ J ----~:r:e~~\t~\,ej ___ \11~ ~ii\V\IA';) ·si.l~e"'o/" ~.ruct-u.~-1-v.~..tS~vt~s CL\1\o{ ·j eq~tnvc;~\t'vv\ o,.... h\3\x:..r ~lt\lC#\ ~~~ ~~.i ~vt"" A 'SlZ Ga.. 5·J. --------------.. " ~":~ ·~". :. nftft MAR 1 7 ,986 C.IL ... -· uu . /"'------::>.--#: ' I ~~ ~ 7.. ~.'-~ALe --/f5oo.-o81 5S-IS'z_-<- , ~41' 1'2 "-';j--,./ Ar--rA-u--¥1.f:?NT 6/ )))(.!-------'r-----'E--f-r--E ~ r G-210 & S-210 1/JI/?) I c I • SCREW PIN CHAIN SHACKLES •: : G-215 & S-215 ROUND PIN CHAIN SHACKLES* W.LL TOLERANCE WT. TONS SIZE A 8 c D E F G K l M N PLUS OR MINUS G A EACH 11 2 25 47 .31 .25 .25 .97 .69 .88 1.63 16 1.44 1.34 .06 .06 .11 3/4 .31 .53 .38 .31 .31 1.16 .81 1.03 1.94 .19 1.72 1.59 .06 .06 .17 1 .38 .66 .44 .38 .38 1.41 .97 1.25 2.34 .22 2.06 1.88 .13 .06 .29 1 1/2 .44 .72 .50 .44 .44 1.59 1.06 1.44 2.66 .25 2.34 2.13 .13 .06 .42 2 .50 .81 .63 .50 .50 1.81 1.19 1.63 3.09 .31 2.72 2.38 .13 .06 .68 3 1/4 .63 1.06 .75 .63 .63 2.31 1.56 2.00 3.78 .38 3.41 2.91 .13 .06 1.21 4 3/4 .75 1.25 .88 .81 .75 2.75 1.88 2.38 4.50 .44 4.03 3.44 .25 .06 2.14 6 1/2 .88 1.44 1.00 .97 .88 3.19 2.13 2.81 5.25 .50 4.63 3.84 .25 .06 3.1 8 1/2 1.00 1.69 1.13 1.00 1.00 3.69 2.38 3.19 5.94 .56 5.31 4.53 .25 .06 4.5 9 1/2 1.13 1.81 1.25 1.25 1.13 4.06 2.63 3.56 6.63 .63 5.88 5.13 .25 .06 6.6 12 1.25 2.03 1.38 1.38 1.25 4.53 3.00 3.94 7.38 .69 6.44 5.50 .25 .13 8.9 13 1/2 1.38 2.25 1.50 1.50 1.38 5.00 3.31 4.44 8.22 .75 7.13 6.13 .25 .13 12 17 1.50 2.38 1.63 1.62 1.50 5.38 3.63 4.88 9.00 .81 7.66 6.50 .25 .13 16.2 25 1.75 .. 2.88 2.00 2.12 1.75 6.38 4.31 5.75 10.66 1.00 9.19 7.75 .25 .13 25 35 2.00 3.25 2.25 2.00 2.00 7.25 5.00 6.75 12.38 1.13 10.34 8.75 .25 .13 36 t 55 2.50 4.13 2.75 2.00 2.62 9.13 6.00 8.00 15.25 1.38 12.97 --.25 .25 74 ·Round Pin Through 35 Tons. t Furnished in Screw Pin Only. G-21 0, S-21 0 Screw Pin Chain Shackles Meet or Exceed Requirements of Federal Specification RR-C-271 b Type IV Clas_ G-215. S-215 Round Pin Chain Shackles Meet or Exceed Requirements of Federal Specification RR-C-271 b Type IV Class 5. G-2160 "WIDE BODY" SLING SHACKLES INCREASES SLING LIFE ON HEAVY LIFTS • All ratings are in metric tons. embossed on side of bow. • Sizes 75 through 400 tons are proof tested on two times the Working Load Limit. Stzes 500 and larger are tested to 907 metric tons. • Ultimate load is five times the Working Load Limit. • All sizes quenched and tempered for maximum strength. • Forged alloy steel from 75 through 300 metric tons. • Cast alloy steel from 400 through 1000 metric tons. • All bows and pins hot-dip galvanized, with pins painted orange. PATENTED IN U.S.A. 17 Working ~ DIMENSIONS IN INCHESt Load Weight Umlt" In Metric Tons A 8 c D E F Pounds 75 4 13 2.75 11.42 7.28 4.72 2.52 99 125 5.12 3.15 14.37 8.66 5.90 3.15 161 200 5.90 4.13 18.90 10.83 8 07 4.33 500 300 7.28 5.25 24.60 13.78 10.43 5.51 811 400 8.66 6.30 25.20 16.54 11.81 6.30 1122 500 9.84 7.09 27.16 18.90 12.60 6.69 1440 600 10.83 7.87 28.94 21.26 13.78 7.28 1784 700 11.81 8.46 3<f.51 22.83 14.57 7.87 2086 1000 14.96 10.63 34 61 26.77 16.93 9 06 3210 tRounded from mm to two dec,rl\al places. Working DIMENSIONS IN MILLIMETERS Weight Load In limit" Kilo- Metric Tons A 8 c D E F grams 75 105 70 290 185 120 64 45 125 130 80 365 220 150 80 73 200 150 105 480 275 205 110 227 300 185 133.5 625 350 265 140 368 400 220 160 640 420 300 160 509 ... ~oo 250 180 690 480< ~29.:~ 170. )6.1;" . ~ . ... . ........ ~ ... iJI,;. 600 275 200 735 540 350 185 f 700 300 215 775 580 370 200 .94b I 1000 380 270 880 680 430 230 1456 "Proof Load 1s 2 t1mes the Workmg Load Ltmtt. Minimum Ultimate Strength is 5 time~ the Working Load Limit. !~""""'·~---- A 5010.64 IFR N l 0 T CLIENT S. PROJECT STONE e;. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE ~\..A~ 'I< ~ '? /J\1' l t:. R A\)T\-\n~=tTTV /e~~D1..EY L-J\~£ CALCULATION TITLE (Indicative of the Objective): \'{\~IN ~~ff\ \:>1:.\fER$rOtJ ?E~STOC'K. DESJ:&tv CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. DIVISION S. GROUP CALC. NO. TASK CODE 1Sgeo.o8 ss \!>'+-\A * APPROVALS -SIGNATURES. DATE REV. NO. INDEPENDENT PREPA RER (S)/DATE (S) REVIEWER(S)/DATE (S) REV I EWER(S)/DATE(S) OR NEW CALC NO. "D~.\1ID ~U\Qi-ft'lTE ~~'I L. ~1£J-M2_ 0 '5 f\l./~'7 '/ 1'2./ 81 ' * ~~~ ' I; j.. ;-, . ..) ') 0 •. J DISTRIBUTION* I I COPY I PAGE 1 OF Cfd.. QA CATEGORY (v') 0 I-NUCLEAR SAFETY RELATED OII om d ~)f.: OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED (v') OR REV. NO. YES NO v , ' I COPY GROUP I NAME S. LOCATION I SENT GROUP I NAME S. LOCATION I SENT _] (v') I I (v') RECORDS MGT. I ~~~:::: FtL~ lv I I FILES (OR Fl RE I \ ~ -I I I FILE IF NONE) I I J I I ~·)b ~0'=>':<. I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! ! I CALCUU1iON SHE-,.r..a., .... ,_, c:.?o~ ..... 1"1011 ltQ. I II&VIa&O• I ,..":. .-.e .. 1..Sl;'OO. og I S S-l3tt-l:l. 0 ,.._CfiiUU/\1ATt <:;;jt?._ i8{p v Pr"!I:O ~'-A:-+0 t.I-+E r r E J .11,-.7-»~cc:xu' o..n: '/rl./, ~ 'l.l!i L.A r4L I , B 7 i IMOC-'00&111' IIC'tlhU/0..1"1 I 3U • .o&.;:' I TtTl.S I ~ ... :.t.r.t::s4•T 1 ;;:::-::c ~ D:t: Vc~I.O t0 TlJ rJ ~) EL f~Ef\lSTDCK. oe.sr<rf'J TABLE OF CON"lc.NTS ANO HISi'ORIC DATA (R.Arrisiom,. Additions. Oefe:iom,. En:.) p~ CESOJPTlOtf ORJG. ~VtSIO.'I R.E.YV.RKS f NO. !lEVtEW NO. OA~ 1 11:-TL~ 'f~E: :2-TA-~S C0101Ef\>T I ICA\L I I . I 3 s \Jf'l\ M J.\ ~ '{ f. \-tEET I I If 1 ~s t0~ TOC K G--E rJE;RA-L I I I I ARP.P-cnr:,..:E"Mt::NT DETt+I:L I I t:.A:L(. ~ 1,;-f\-N\ ~E"tVt; I:J\lf:r I I I I I 5" ..:-, ~ lO .A-lJ£ :r:AJ p t;" t-':lsl 1')(. ~-I I I I to ~ \]tv\ 'tJ\ 1\1<-'-? Pt::-AJ'S; TCC..K I I i I (;, \) P t-oR-,..-LOA-Ds I I I '\ n-1 f'E0SLOCK STEEL T~.U.tiJS£ I I I I '·) cA-LL. • I i I \3.;;.2\ s\:r:~rE: t0t?R-~1::10(:,-CALC... f I I ~ :t: p t::= l=ULL CA-f.t==: I I 22~4 ST'J:F FEJJE?fL {L I:; A) ()..-CA-LL . I I I I Pr:P~ \+A-tr )::ULL C.lt~E' I I I ~lf . .s 1 1= F t:='l;?~ti'L 1<-:r A) G-(A{,{.. • I I ! . I -·~ '\ v ' 14-l~tttf s. T1:F P'e.UE:P-1<-::t::NG-CAt.C..· ' I I I I 6Q . CJ4f;,F I ' I ! lll-7 -4-8 $ rr: F-'F 1'2? JJ GiL · \<-.J::.A)c;. G4tL · I I I I l \{ f..C.PfV' (,f!lCC : I I . f·;;::eFLf I I I I Lfq-\,0 5L.:::::DrA}G-; U PPOr''-T I (OOAJGCTU)A) CALC· I I I ft!O-=:; 73 lt.IVC.H:OQ.. ~ WC.tc I COAJIJEC..i:r-b/0 I I I I r IJ..! c.. ! I i I. I o;~:; G E'~ "J 'r80Si"''t..K. FUl-L I I r I 7~-'lql C.'c-\-EC K I I I t I I I I I I I i I I I j I t I I I I I I I i I I I I ' I I j I I I I I I CALCULATION SUMMARY 1 ~.0./W. 0./CALCULATIOII 110. &501062 1J;(S'oo . Cf6 I 5 s -t3 y. -I;~._ IPAer 3 Of' CLIIIIT /PitO~ICT OA CATieORY/CODI CLAU P-:\.-.AS ":< f-'?r)•,)-'JE~ A. ViM\tiTY " IUI~ECT I TITLE C1:. \j ERSIOf\) Tl) #.J 10 SL-f> Ell}.\ TOC K 0 c: c TG-sA-} OI~ECTIVI Of' CALCULATION ~~I()S TO C..K ANO f. uPPOI"LTS M~T/0 DA;tl\ {) I \f EP. s.mrJ T U 10/J -2 L CALCULATIOII .ITMOD/AIIU.PTIOIII \1\E"T'r\:OD-= tr\'E'T\-\0\) P6. DOC.IJM~tVTt=tJ "I:~ Tt+G ~OULtlEf<. C..~IJ\'OAJ \)~o;n;;C..T J FJ:IJ4L-R.E?~OIL\ S J PA-~1 V 1;-\.....':lD ! ~ ,:.5-l:C 1-'.SS \J i'f\ f>TJ:OJ.-)S. : (D 9:tP8 t7JVIJ;)i';' 00 Q_J::-1'\)G-t7AR T tt Q. '·)A K 5 c F ons c;.. (9 f E"c C4L(,-S.. Fog.. IY'~OfL E SPec..::r: FJ::C. D b'!;,r( ... /IJ f.:f:; :Jfl ~ ": :::C>/.J5 · (JI \)!.~~ 'F0\....L. t}vR-:t:t-l& E. I\~ T\\ G.\) f\\<.€. Or o.1. s G- AL\..OWAe.\..E ~TR'E.~5 "I.l\lC."E'A~t ::: SO '10 IOUltCII Of' lATA /EOUATIOIII Q.t;;t: 1. ~TEEL ?L.A-Tt; G"A.>G--riVe;t;;-p.:rtJG-D A-i A-VOLUME U.. 'T l:ILI; :: ~\8::\.., Pe=A?sTOC..tc..~ P,A)0 T0f0k>EL L..]:I\J~R-.s ]' ~{) ~ ~-.'J:A)T :tAJ (r L"f '1?\.i. -B '-? Pt M elL:.£.;. IJ 1-fl..t;1.J P.IJC ! ; :; :; · -Of~ .. J'~: Q.e~ ~. ~QJ:U:l:I:-NGr C.O()E R€Q.ul.1'-6tn~NT.!. ~ R."e:I:A>F0R(f::(, co/J. 1=<;:: 3.'e f?> ~ ~ ~ rV''S"Q'}:(.JirN CCli\)C.#(..~IE '!: ;'l.),s-r ;;t;( iJT8 ~'F-:L l'i\A-t.)U4L.-OF f.TcE'L C.Of'.:lS"'rll\)C'T :;;;oAJ €T.t+-ii?C -c.or·>r,.::_"-·'""7 1c,J>" B '{ ~Mt:fLUAI\J "I:. I'(')!", T rr \)T G" OF S Tf?8 L COOJ"ifl..{)p!: aAJ n E;r 1.+. \3-QVLCSR. C410Yr:uJ PR.O"J-SC\. F:!:NAL R<:cc;:>Ofa..1 <;..; ?A;~i'f ltr.l+IJlr.O.\.... ::;:;t)i/!;'.&71:'6-A-T"l"-t.l' 1.... ~uLLE!J:AJ s: · PEV.rR?c.l( A-A}4L.t>~z~ A-ND sr::rFFr;AJt:/2... cc::.:::.s-r.J ~~ U-5>. Ce~T· 61= I!+E' XNT· ~v~. 0~ ILEC..... CONCLUtiOMa ~SQS\DU<.. ~1:PE.-'T~':J:.Ctc.t.J~.S.S.-:: lt·/ ?'Et\lS.\Oc..K Sut'P0(2_T SPA-<-~&-rs l'f<.O?o~.:r-::;:o.<).Ac "':'"":> 'p-'+ 'i>~I0!TOCK 1:1 A-IJC t4 0(2_t;(1 AT •Jp!:..-12 fl' ':'/J[ l !'C ~ 'wl) E.& A-T ()o t..t..M)S> R~: A tv\ E DO. \JEt.JS\OC..K ST~~L To ~E \)~Et) -:rs A~TN\ ~l\D 1 c,.RPttlt: A IIIVIIWIII (a) co• MINTI .......... ... ' j /'(_ /;'':, tf:.'-~r ~·y)r \.:c::~..:::: uv•••!!!.:!"~~KI:It "n , I ft Cl:L t1J:u2 IIID.PEIIOINT ltiVIIWElt DATE DATE DATI CLA!lS 3 1/tt}fJ1 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCUUTION NO. REVISION PAll A5010.61 'l.s-g 00 08 .s-s-l3lf -1~ 0 s- 1/r?../87 QA CATEGORY I CODE CLASS '\-JOT(:;::; \.:.OPtt::; CP.~\:: c A:-~ c: +- c.. A~ e 1- c*s.e-'3 cA-~c 4 cv-r.s e s- .,. ' / ) ) ~ \I+A-i ,!/ ( lj ~ IJJ \0 I v it ~\IJ \ It II ' f lt w = 10~., oF~J:P&/t==r 1-DL-1-ho 1 pr- ~ 'Tt" (,rz.)C~~,_o) + 'J..ltR Lt ~ncE"L. ~w J J/ ~ it .v ' !t ' J-\IJ li ' I -~ .!J ~ '~ .v /j. = 11 ( S".t.S) ,_ L b '-·.£" \b/FT~ J + ;A 1f (S'·"bS) ( i J (! ~< ft) Y:Cfo \b /F(> 54-\} CALCULATION SHEET •I\ r> /' ~ ~ .._;("< -£11 c (!' li\ - II 0 [\ 0 .-trl :r ~ ~'i ""' rr: .!!:. STONE & WEBSTER ENGINEERING CORPORATION .J.O./W.O./ CALCULATION NO. ls-goo.os s-.s-1 r: r:l~~l ~.it REVISION PA8E 0 (o QA CATEGORY/ CODE CLASS !'"-:-C)o .,.... ~ .;::;;! .::- ~ If "'T'" oc 0 " \j V) "' ~ ~.:; J.l=2 __, ~ Q ...., .'"'-.-;:JJI-T C::. v) JJ c ::::::~ c.i w ~o a.. -::;:-..;:::::, -. " 0 ·'""'r \v} -..J <::\.,. <:::::. ''"": C::.· r-< -:;:!,..,. ~:::-> -;;;. C:C :: v1 C0 --"...;.)\...- -::. ~ <, \_, v) ;-, CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULATION NO. REV lSI ON '1-s-goo. oe s -s-1 3 Y...-1 2_ o PA8E l QA CATEGORY I CODE CLASS 0 <:) o:- i.l) ~ 0.. ~ a~o . V\ l:X\ 01\l . --::; + I ::;: I -1--I ~ i t ~ OM ~ \..;)·~ ":.' \/) :::r ..... f;<l-C! e(:) -+-I -+-~+-.... --..f) ~r "" . ~ -f\l .... ~ ,. .... .,.. \A 0 ::1 'Q --? l J I ""'-<:"" rflr;i I i CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./CALCULATIOII NO. REVISION PA8t: 45010.61 1£""goo.og s -S-13 4--l;)_ o PREPARER /DATI£ \)f.:?, IT QA CATEGORY I COOE CLASS f r ""' M v. I';' .c: cP. :::>- U>_ 07:, 1-r N N\ .c::: ! ti I r r->oo <J-...,Q ~ r:.IA ' . 1 +-I +I .... ;:s ~ 7 00 M ...» >!: 3-~A ;"I + I + J T 1-:( i ·., "' ~ < 1..1} ~ ~ ~ < I ~ ~u:cu: ~ Cx>c~~o-:- <. ~~ft)C'-M 1.1) I'JCV'\M X -rJNN ~ st: 1-~ ..;: ~ t'r :::A c:;. ~ ~ U} r r:- M M C'J I 1-lb ...!J < < L.}) \..) 0 ~ rl ('J fV\ '::)--\n 0 <0 i ..t:: :3 CALCULATION SHEET -:oP-A\f\J rRec ~~'< i'!\ 'i. N\ e. 'e \<. 1. STONE & WEBSTER ENGINEERING CORPORATION "-J= s-. 9 n lli rro..-= z.~.1 FT ltEVISION 9 QA CATEIORY I COO£ CLASS tJ ~ f\A '-= -RP. ( \q .11 '.l -t 5'81'1 ( \'"-t :?>3) 7-Co ·$") + :2.~3 'I ~l.-~--=;.......:.~L---tol ~IL \R..'it = b f{ ,Q_ g ·~ ~ ~ \-= S ·'H'1 (:\9·33) -"'~·d-.8 -= '-1-S",10 K. ~ (.\ c .... ,-... z. +-f{\ tv~.At := '+S-1( '1.hd..J -S>dl ''"'.ii = 1.. '7::2, FT-K \>;)::.s·ql1 1 'o/~r ..J 2:.~\.. ::. -t..2>3.q ~\CJS., 1-5"·~\'l(l'1<n)\es) .... ~~(\9.?.1 ~ ~R. = 54-·IS' K ;.; z1'J...~= 17S-\ -S·'fl'i(i'l·:>:,)'-(os) +RL (r't:!J)-2JJ.~ ~ \.--::: ~·L3 K -t l'f\ ""~X -::: G,O · ~~ (\0 ·U~) -S:. ~!J~O-t~ '.~"'" -'2:~3. 1 = [').. 7rr ~iL~...,-:: ~R-.: ~-ctn (1'1-33) = S'l-\q K '2 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PA8E &501061 'l..S' 'ie-~T 1.. (;, q ,(..g + "Cl.~ 54 ·1:5 + 57·lq 1 S1.lCf + 5t+IS"' 0 lO QA CATEGORY I COOE CLASS C~l:TJ:::.LA-L C...A-SE w 'N\tE~ ?TPE 1:.~ J"U S.. \ fJ:u...tD \N ITH . W 1\-it?lL ftt\) C ( ... "1\:)1-IL.Ii\-C...T':COI\) OCCORs l>OE TO CAAt0ErE"' ~..v T& fli\P E?AA T\.>1£-e;-E E;C AD~ E OF t; X Pt-erG'{) tn::~I\)Lb-J:~ WJ'\I~IL TG'M(J, tV•J() IH€ AM ~ :r: Gt\J r TFM P. e> r iH s-T \) ~ t0 ~ ~..-o o u.>~STflFI:M ~ F-1\-tt GATE f. H-A-FT· l-OA-P rrz.:t:.r...\l:o N FI'\{..TOIL R.tb\)C:f'l==I'J6-\-\02-~IA~ ~fo\{) l=N ~r.~s-= \?..q ,g\~ 0 I ~\. \lOI'I.~\.C. \~·'isK • -~T'l:o,.;:, r-.l.TO~ ::. l H . 3.<t f). I L1.N-K r ::::\\\.1t.t f) . \ \\ ay. k '-1-'=>O. "21 +~q :z&' ::. \d... CiS~ o. 1 \ "· CfS"k: WJ\LL 45'·1.0 +_ ~. \q'i.~-=-$"5·4 0·7 38·1eK 3 RfiL 'P'"'"~ C~ -'5AV 0~<.-FLI)61t-G.-OLIJ W-Z\ FA-<."'t '0~ft co~~. 10\t'\-L "'X:t:ttL H:Jrte.~ ~ f'TPt {) l)b \0 TEMP-e Ht\JV(;.b ~ -= ~7.3GK' CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION \ I QA CATEGORY I CODE CLASS \)tTE.R \Y\J:\-)t::_ STR E.S~ t:S AND i>lFTTE TrtiCK }\)'S~S. BE\'IV EE tv S\J?~ORTS. -'JSI::: A '1 \0 51 ttl. -Pt\...\..0\N ~~\_~ S."'ITE.L ~TrLS£.:;:.: 0 S (1;>') .:: 5'7 .) "' >:: -\JSE 1...= d-..'-W r""'c.t.t.> 'f"CQ-t>~:t:&-!U. C c~ 1\)~.) '"2.. STE~ '1. 'tf~'"Lw' _ '\f(\0·5(Jt)"'/¢0·CO~-d)(C:.1.-SJ Q'N -::. 'Nc:S:<:r\+T o-r 'N'P-;-IE~ o0~C £-i>A-"-l-= 4(,~.~-'t)(r.L) -'-t U4-4-)\\~) Q ~ = "N'C!C,.\iT Or SiE EL !:IV ONe s? Pr~ = O•<g9 \)~ \_:: 0-€9 (\e:>-S (n .. )"' ( ~ ~('~o). (t:.~ = l~Oq~-\'o.s,j SPAJJ \f\f\X \f\O'N\ t. l\)\ == ?-~s r-:-1-r-. -:::: 3190000 uv-,'<>f> ( \42.0Mv M(1M..6A)-T 0» I· CJ4;LC.... -e.A-SeQ O!V F:t::IVA-1-~es.:r:.&-N s('>IW. W""TER..E"O GF\SE. Q.:: Q s. +D. '1/\f ~ 1.1£?~31 .o \\-\-~ CIK.ClJfYl FE~tJTIAL ~TR.ES,S B"ET'N't: 'Cf J :;;. 'JPF-~r::.--;-S 0 0 'G TO .1-IVT cR. tV A-L t>\?..C bS \J 12.. S: J: .S. SE'\ ~ = ~c.? f:. ~ Sx _; ~ ' = &o ( 03) _ . -\:. o::ns \'1\0f'f\t:NT 0'\=" I t-Ye RTI:A t=OR 'J_Il f>t,A-TE l.:S O~Tf=7:!t-.)cD 8 't=~0N\ T -'11 r '-t -c. roo__ ~ -3" I 'tf" ( G1,) ~(e>·3.'1SJ = l.f (;1~ I'N s --,--= 8 c ,= \!.:rc.. T":t:OI() A\, R G:P\C..T.I:OIJ A-T PJ:E"R S 11"( 0 -\"-\.-)t = EXSV'A-N S.IC>/J J'OJ:(I)/ oF fdvc 1-KJR. -!. 3 \ S? 000 0 :t::N-L~S 4~1 (o ID3 STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET RI!VIIION PAial! &5()10.61 0 \~ PRI!PARI!R /DATE C. 'H: () ~ Lf'; ~,)C \1 E QA CATEGORY/ CODE CLASS tlt:Tc.~m;ri\)~ &-n:\~6~ f'rt--H) ~LA-TE. \1-1-J:CKVSSSc;S. ~cTW~EN s 0 fl fb 12-:rs -c.o 10r;r:: tJ VE o ; tl8E:Rfv\1:t0~ EQ\.)J::'{A-\...'b:f0T STI2-&f:.b V.J:A t+EAJCKV-M.,p;e.s. THE?OfZ.Y Se'" = £x-z. -sx 5;s -t-S~ '1... Se uo~oso)ct34-l) '>co'-'! . L OK MvM Tf.r)::C.K tJE"~S C>'F T'L.J:1-rE' J:3 G-0Vf:R.t0EO ~ t: F ER.:c 1'0 c s tTR. 1.1-c. t-E: V~:t:t\r.t. fY\ \) M ,. ~ r:c K tv as. 'fOrL tt~rAJ[J L~A>C:r <;;, ~E'L F>I:P E:. R.= G 1:.'' {'1\A,X ALL{)uJt'\Ble l=RQfYl c CffftL r ~J:P ~ 11Y ~· ilA-~MA~LA-1\J 1:10 W r;,.j~R. POW cR. .t {)f.Jr(t\ CODSTa..ucrroAJ T\) tJ E" 1'1~ -C I·Uta.-r f'G-tq s T<La s = 3 7 . :; tc.) r '* 3 [;ooo F s:r -.\::-12.-e~ ~C?.J.6'1 l L 0-3~-..::.o frl) s-Q UA-T t; FCl'-H-4N D LI/JC,... ses FOR- r~\SR 1\1\:l:: OI=A-\t s;.Tr:FFE?f0 GR.. KSQ\YI::\2-'C ft/1 = AJTS Vf\;C. u 'J tf\ ~&-~ :.±1 ~ l;tg r CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PA8E \3 QA CATEGORY I CODE CLASS ,, C'=C\ i ,-,-I " ~ \::.~1 ( l'·'2 'E. f:t = l (o~so) ('-) + t (3 ·'1"1 +'t + 3-19) ::. l~· f-1 11 '2=1 .... 1$11 CP.,LC\JLC\\'i:.. J: OF S"a:...\1:0\-J -I = ~ (I +P..c\'-) =-1. ~ .., f. 'L ~vrCE·s)({.,) ""' '1 (')\P::;o)(6{: -\.ls-"'"~'Js) ~~(J.4.~i)(i'l:. of-~(l."S8)~\·15 -f; "L ..,.... \1-tt.oq ....L ?::: 1·'1'5 'I. '+~·09 -f. u.~ 3 - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1,0./W.O./CALCULATION NO. REVISION PA8E 4501061 1Sb'eo.QB s -.S-134--1~ o QA CATEGORY I CODE CLASS ~er -'1. ~~ ~ ~b-3~ X --R = ( c, 3 _ 1 "\ ( 1 _ ;A CD·ss-SY-) \ tlt.'TS' ) \ (!93") ) -().olf = -o.o~s~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I .1.0./W.O./CALCULATION NO. IREVIOSION I PAGE 1£ .. 501061 iS ?.?Co. ~8 1 <;;:.-s-r~q-n: PREPARER/DATE . '+/:J.."l/8'((.;> ~~~~~·~:"!c,K!R /DATE '/ J I INDEPENDENT REVIEWER/DATE \)P,\(i:'D B\....i\-")c_l;-\t:l\1= f,f..,. /lt~A-IUZ_ l"l .. 81 SUBJECT I TITLE IQA CATEGORY I CODE CLASS ui\f'C.R~I:o0 TD~~l\JC.L t''t:WSTCX:...K CJ\LC\) LAT:ro~ CO"-'Tt: 10 UE l). -~ 't;~ ~ v= J::G-. l ~ ?T'?S: r '.)\,..L_ o" ... 11'i?·3~~·~s8131J-+ .<gttao {.·3\83\0)J = 5·~'73\..fK = '+3~~s:r 1S 0 = 118 ·~11.{5. -:;),I..J.\3~4-J -+ .gCfoo (_ • 3.07%Y.)] ~ 3. f!11:t K 3\ 'l ~~r 30° =11~·331~-iZ-I.f-8415) + o.~'1oo (·l1.Sl,bt.ti1 == -0.3~3.~1< :o '""'3.Dp5.1' 'tS 0 = 11~.'~:i~1~-'.~1lCf8) +O.~qoo CJ.?..so?q)]:: -fo.1304-'K "" -sst.'?~:;- b00 =-11~.~~-.J..b3704-J ~ o-~croo C\~tnss)] = -\~.\·P+3oK == -11C6'd-.l>~s 'lS 0 :::: t1'B'.33{-.~r;;,:o:r~') ;-o.<gqeo (.os:x~s)] .::: -12 ·'+Y-7t.t l<.:::: -ts~ 1 f.St: qoo_ -= ll~ ·3J{\-·:ls-CWO J "t 0 ·itlJOO ( o')] -::: -~9 · S8'J$ k = -d-lt':l.1 P~:t: qd'"' = 1-l~~31(+:Jso:o::>) + o .g<roo(o)) := +~9 ·SB~'K = +-'A~ll psr 105° ::::: 11~· 33{ +·1~.? J -T 0 · 8YtX> l-.00:2?2$ ~::: +Z.L ·~'+1lt\( ::::. +-1~~1 ~~1: \J-Oo \~0" = 11~·23l}t+. '1~'70+) + 0 9?tx>(-·I ~~~s-')J = := 1-1.2 ."3,3~-+ .J.S7l'!E) * 0 .~tl) (-.£:l.£;O']q TI = :::118. 3'1 Jf. + • 'l \1-\N·lS) -t o · 8~ro (-:2.1 S" bh\f )] ==- ::::l~·~{+·J'fi3~\,L) t 0·&100(-·101~4-1= =o 11~ ·33lf. -t. 'l3S'732 ) +C'. gyro(-· 3HH\O)J ::: +llt·l...tlt10l<:::: +\l~~lfJS.!: 6 ·1304-K :::o + Sb"l.~s;r 0 ·3~3~k. :::;:. +-10 p~-r: -3 ·~11l'K-= -sl'l~J: -S' .?.133 'r:\ = -43'J.~1 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION PAGE QA CATEGORY /CODE CLASS STlFF\-0S'R ~1:1\J(r Cft\_..CULA;-\IOD C61VTJ'AJUI:\> ~ ?:CPE fuu... \'f\::::Q(R\'\3 +-X'K't) 0° '=' \\B.33l ( Co4,.r-}$' (.Ojl~j) +-2.· S9 (-~Ob~3(0J') = 105.3'1\5 z.v-K = = t\g,J;I l b 't·15 ( ·0~6!SJ + :J-, S9 (-·OS7\.fbCf.)) := tf2 ·'-t\111 \\8 ·~3\ ( 6 lt·lS l .()0 J~g~) + f... f;C\ ( -·0~ s-{kS)) :: 4.1ll24- \\~·3.31 ('-'\t.'15 ( -·00'7lcte) t 'J..s-9 ( +·Ol'fCf~l)) = -'+I·ST~-9 \\S.331 ( b 4 0S l-.0 ~~ 704-) + ~~ ~q ( -t . O'lOglfS )) = -1'7. \~ll ng.n\ \64·75 (-.OI~J) + 1.s-q ( +·\b1bt')J = -'i~·'-ttW 1\2.33\ \b4.1S ( fJ) + ~ .s;-'1 l +·Jrooo)) ==-/(? ·'Ol'U 118·33\ (~4-lS ( 0) + J.. r9 t-~2SOOO)) ::. -1~·6\q3 ll<Z. 331 \ b 4lS. l + .o\!03-3) + :;!. S9 I,-· (b7bl")) -== lf2 ·t.t!OO 11&-~3\ ( b4lS" ( + .ot:notJ-1 t J, s-et· \-!mogy.s-)) = 17 ·IST2 \12·13\ l64.l$ ( +·Ob'7R2) + ~.5q (-·Oli.JClJ.!)J= lf1·~\).g \\~·~1\lb4lS (-.001~) + 'l·sr-l l +-··01[bbS)J= -Y...J.1g4 l \8.331 ( ~4.lS ( -.00~~) + ::< • _rq \ +-·OS7%lf ))= -\1-g · 4 \q I uv,.111 (64·15 \-O\'Ob1) .._ ~.s-~ l+·~lo)}= -65".~'11$ r STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .1.0./W.O./CALCULATION NO. REVISION PAGE 1.S~L.?O·Ge s-S-l3tt-~ J l. 0 \'l QA CATEGORY I CODE CLASS s T::r: rr E f\'H:: R Q..I. N & c A-1....c.. u t... AT!:O t0 ; t> !:-~ ~ ~ D u .... S= Q (Ks +CKb) = \t\5' .~~ 1 ( 0 + 0 ') -= ~ HB .?>31 l+-OI'lf.s-1 + (-o.o6S91('"·08~~s)) -\12."3:?.1 (+.o'!l.?.3go ~ (-o.o~x~·15"~1s~)) lf5° ---\\8-31.1. ( +-03)\1'7 ~ \. -o-o~~)( ~.-n.scn'f)) b0° -\\~ -33.1 l+ ·Ollf-lfl'? ~ (-O·C~9?)l+·11S""6h<f') J 1s;o = l\e-z.:s1 f-·O')..'),qtr.s ~ ~-o.ots<J)\+·?01%3)) qoo -lt9 ·331 (-·0'7qr77 ;-l-o.o~stl1(+·318'3IO ) ) qo 0 _ \le -:S'31 ( -·o?qrn t l-o.o6gr)\+·~l~.StO)) JOS 0 =-lt~ -3ll (-.o)~q4-S 1-(-0-0f,Sil){t-~;c>l%3 )J lUJ 0 = \1§>-3.:?.1 l+·l914-l.f-j7 t (-O·ObSt!}(t,l1~<?-)) 135"0 -ll~ -?:.~ 1 ( + · OQ.\ \1 t l-o ·Op.$"q ( + .72.)0?1)) J.r0° -llg-331 (+.o~;;l._sgo t (-o.o~~cr)(+-.JS"'fJSS )) IC;~0 =-ll~ ·~3 I ( +~OICfbS"I ;-(~-~£"q)~-r.()8.:l3$")) lro 0 -I!~ J 3 l l r3 o \-l -o.oc,SI)l+. D 0 ) ) 0 1.G,elCJ '1.5905 ::: 'J_ • () 4 53 ::: -O.'-\-'i31 = -5 .\\:l/ : -1~. pqg~ == -ll .ecu?0 = -5.11:27 -0-+4-Z/ 2-0lf-S'3 2.S~05 \.CoS'J.9 0 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PA8E .0.501061 0 U? PREPARER IOATI !) 1i \II D SUBJECT I TITLE QA CATEGORY I CODE CLASS I :s r:G-AJ 5TJ:FFE0eR. R:t:~G-CltlL.U LAT :t.o IJ ; CO~TI:NIJt:D. P IPt= r\)Ll. * J: f¥\ ~ Cs 1.) :v.J 3 _;t_ S.:t') A "l:tV-f" X .:t,u3 00 lt;qy~ lt-1'1 ,5.3'11$ 2-~ .os-\l).k, lS"o 4-cH3 :5\l 't-55 ·'tlq 1 ~.0$ \0. b :see> lt'U~ -30 4-· d. 7b'lJ. 'l8·05" \0. b 4-SO t.tctl~ -S5l -lf7.sl;.q J,g.(:6 \o. b b0° 't~\3 -li~A -17 ·lb1J. ~~·CS" \f) . b ~~0 't~l3 -tR3'1 ~lfg ,lf-(06 l~·OS \0. b qd'c_-) 4-<ft3 -?.i-Jl -7~ ·blqs :ts.os-\0.6 qoo(+) 4-'t\3 +-lil1 -7fe. G!«U d.,~.o; \0.~ 10$0 ~~l3 -1-l&:;l 4-)] . ttl C16 'AS·05 \0. \, \'W 0 Lf~l3 +II gl_ 77·157~ d.~·t'S to. b ls~ 't~l3 +-SS"I Y-'7 -S"Il<l ?.g.os 10.~ IS£:)0 lf'fl3 -t-30 -4-:"7glf. :1-~ .r:J; \D·b lbS'0 t.}1[~ -3l~ --~ ·Y-1~1 ).8.(1; W-b [goo '-t1l) ~lf3?---bS .~,15 ?£.fh 10.(g CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVIS I ON PAGE 19 QA CATEGORY I CODE CLASS STI:t:FE;l0SR. \<..J:I\)(:,.. CA-L.CU L,Pt ILDN ;, COI'V!J:AJUE0; ~Tfe. f\)LL 'BEN{)l:~f::r ST~bSf. 10\A-L STRBS <;J~r: .::.IUOMFE?i2-E~ 5.1. \ $ (_ J:~J.l:()E) 5 ' ( Ol.lT.S :tOE ) £t. ?. A:'!>~R. ::>. t=-r~ e Fl. tl' 'J-3~\ -"1bq '1~1~ -SA4 \~ \1~~ -1Sbg "qs1 + 0S:/ 300 tS3 --4olf-!01~ + ll-l.f-'79 1/-SO -\Co~'4--t LtttgQ :lb(;S +8~ttli. 1::::00 -:ns1 4-l ?:.,]~ q~ -\-\ lOlO 7r 0 -\1'2.~ ~'+Sl·>l \350 lrQY-3 cwoc-) "?., 11?._ ~7?J..g 5:J.'J.tj--Y-130 qoo(+) -'), 11}, -t7JJ$3 '-t-bO:J. l45"'~~ l0~0 t '7lCo -Lt-5~1 gtf7ro ~~~~ 1~0° ~1Sl - 7 2.'7~ <6~Lf(7 -1124 L3b 0 lb9\t -4-Y-~'l '7/58 C(8:l 1.~00 -\ss -\-40lf \f1't0 s 3'+/ /GJ.,.-o -11?..~ -T 4-S'b~ 'dv<B1S Cfl(oi £~0° -~3'31 + '-I "q 'l\SO r 10 ~r;;o S-z N T S1 --+ A + A S:l I N _.. T 4 £ ll .... It A CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION PA8£ 4501061 R!:.N& R~~TRA-It:)T £TR'2SS • • 0 ~0 QA CATEGORY I CODE CLASS A = 'ACA..\\ + c:l = ?.._(_o.s-D)(b) -t q (r:;,.~7r) = '\ ~ ~ ~ \ .S(o *' V' t -J...c;;~ ~ Jr., s.(\) ~ ';A. ~y. ~ 4- '? -=-bO ~o ros.1.: S'c :. 1.tg~ [ C~ -c-1:. l y~ J ( ~ -1-\·9o-tr;t) J = 1. .g ~ [ ~ q. ?.'15 -q ~:~1s') j bO.o (" 12] ( '!·115 ·d·Sbl\Jy'(.:,(\)) t J ::. + 9 001 ~~fir\\\ ~t: ~ti.~& 1¥\ 5.\)~lJO~T R.I. NIS: 1<\A-= t{\~ = ~C:.S "P-1-K. (?'aEVJbi).S,\...Y (.4-U:..vLAT~O} Sj = d-.~S( \),Qn) :::: t~O ~!::.!' 4"7~ '-0~(:,.1: 1\)~1:~¥\'-S\i<..'Cf,.S t:: S. -:r:~ t>-:t ~ t:. rR."I. C TIDIV kL 'fbRLES. A:: T l':r:t=R.S, 410./J 1-tY {)R.O.ST A-T:t.C ~~E.S.S \) \t.E e;A) ~LPG J:l0 E?X PIH\J5.IOt0 J"'O.I A)T- c 0 _r-;~,sr "-r-1 -:::. pt .:: -..... ~s PS'"t ~ ~~o m \ I)IQJ:(r#J -~AIJ. , S/>rl Ok OP!f), F -z...-$.-s Q 1\1 ::: -b~~ ~~, 1f(t:>-t--l)-l SnELL tl\) E"" TO A-106 e-XP!lt\)f:!OI\J .JOLUT e.X P05ED i::;iUO OF PR.£\/IO\)S'-'-< CA-\...C. DL PIT e 0 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1. QA CATEGORY/ CODE CLASS ST!:~'FE~e-R ~J::/0(:,.-CA-LC.\.) \..A-lLOt\) CONTJ:A)L)(:;;{)~ ~~t;; y\) Ll.. ."; · l-0 ~~ :t. T IJ v :c "-J Pr-L s:r~-ss.s. c& M PuT A-T xo 1\J s \.) M M ~\ :r:o 1\1 . &-= 00 ~?. ::. Ft... ;. ~" -r 'F~ +-5. b -+ ~ y = ...:"3:, ~ -G:.12 -0 & -= C{Oo(-) s 3 =-~3--~) ~ --() -\-C{Wf. "'] 0' -g33$>, l>!>t.. &-:= q(f>4) S:, ~--s-s ..:.....G:>3>g--o .r<fQ;q 4-C) r::y .: 100° s'1 =-~) -b~~ -o -t-~roq -C:fgf; \.) ~1: k)G-1-:LG-. ii ~c-r 1.. 1+1JO ~.3 --s:::_t-0 F \ G-\) 'i2-~ (s,'+ RE"F --.1. 1-T:A)/) ~S.e ~x) (5~) ~ &-.:::-(5() 5. 'Z-= 7 ~1 ~ -~~s.l: S-s = qqt2 ~SI: S.e - C7 = qfl(-) s z.. .4' t;'l'J,.Lf-~~~ s 3 = ~y~ t~t s~ ..,. & =-Cftl'(t) ~ -z-:::. 't~C>~ ~·n: .S.3 = ~33~ p~I Se - fT .:= !~8"( +-') .S '--=-'l1SO '~~:t:-53 = l~Sg ~s~ £ e. - A 100 .$'2.. ~4-'dSs ps:t 'l ?.9&' p.sr 1 ?-stt p.sr ~b'\fl psr. A-lSO DOTe-Tlf4f 11-T qOof O!J TffE c>oT SJ:DE l==J;€ SQ. 1..4-r~ d-.. ps~ ST~e-.f.S .:r..s L(%£ T ff 4-N ~ 1 soo f>S.L ,/ . CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 'OETE~M:I:t0-t cot-.)[) :r:. r.r:o (\) :_ STI.FF\-JB~ ~,;$j-~TR.ESS.SS.. -S T \::. r:> :1. •!> fRCM r I..Gr. \ (o R I:f..J(,. S\~ t:SS 'E~ ~ = Co tt ·375 \I G s =\roc\~ 1'o~ CX ~ = WS~!:.~ \\o!. a.. = 0-04 R. :: ~ .s;g \' ~~r= i ~~ ~s ~R ~ cA. -= 1.roo REVISION PAlE 0 ~)_ QA CATEGORY I CODE CLASS FOR-H-A-LF J==Ul.l \1\~ = (G~ + ~w) ~ (\ e>o:r~ +-\e>~_d--~~ ~ (2.~1\) - ~ -- ffio 9~?3~3 -11..~1 -= -R b'-t31S T. = Ltq .oq IIV\J. ~ -4·~3 r~ 7! .::-"1·1S J:.IV· A -i?._ • ':;). ')_ \ I (J~ ;;; TOT A-\.. 'f:. \ .::-\0 T tt-L - l- L ~\RES<; ~ 112-E"Sb -- J:_l\.) I. I\.) :l '6:1.~3· ~~-\tis. ' ~i e\)TE\L r-I: B E'R = f.:>.; -.r:. r\ W\? I: t\H) E1<-r-==r:~ e: R-= 1\ -r-I. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION PAll .1.0,/W.O./ CALCULATION NO. REVIll ON •5010.61 1sgoo.of?/ s-..S-13 -J.. ')..~ QA CATEGORY I CODE CLASS \J~ TE.Rfi'\!:.~~ S.\1:\=-r NER. R'!.: t-JEr ~;;;n~-'CSSES. \=OR \-\-PtL \'= 1=-\)LL co~ t:> 1:: '1.:.010 co 10 TI/0 '-' e \) . ~oR. ;;t «-= .l. ~oo ::. T~ i=' 1 0 \$ 15 \OS \':<.0 \1>£' iSO l"-S \~0 IT\"::: ti\ 0 ""1. 8~933 C-0·\Sb\;.'lO) = -\ 12·\1_ '6:tm3 (-D·l\4-<t:t~) ::. -9S;ID 9 :l.~3l {-0 ·~I ~lq) =--'+lSl. <6?-~3 ( 1-0.0~~~'l..J:-+~\~~ ~:l833 ( +0· \~\6~0) ,.. '\-\ soso ~J.SE3 ( T0·~1SZ..1\J =+ J-1'TGg g ~ S13 ( te · s ooc:oo) =-+ 4-L'-T \1 ~::l~~3 ( -O·SOOeto): -4-lt.;-\1 @?.g33 \ -0·~3$l~\) = ..;?_11'-'<:J R'l833 (-0 · \<6 \ ~'\0) = -150$0 ~;;l.£33 ( -0·0'-t9~'-+l.);: -4-\'2'f ~~~3' ( -\-0-0S\]:tc:f)= tl;JS~ 81.81~ ( -\-0.\\Lt<q~~\ = 4-q£"~0 81$33 \ -\{). \"1<Qb~) =+-113lb T-~ v -R ''~ \J.~7 (-D·B~~J.O) \'l<B1 \-0· (., ll¥1~ ') \ lg1l-o .5:$""1 ~2q) \~7l-lJ·'tS01S"S) \'").'g7 t-0·3\'g'3lQ) \ d-.B1l-O· \~4-l{,t=t) \'l~1l o) \ J..87 lo) \'J.S1l +O. \Cc.Y.lb'f) \'J.£'T (ttJ·1t~3tO) ::: -1Ci1 ::; -1t0 = -51<1 = -Lt10 ~-2\~ .: 0 = 0 ::; ~ \2, -l-\lO \lB7\,-tO.'t-S61~) : 5'1q \?.2'T ~+DS.5"ls:Lq) :.:: 7 !0 \:t81 l-1-0. ~ llfC{~) = 7q 1 \':l.~r:T ~+0 ·6"l~l0) = ~\9 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 QA CATEGORY I CODE CLASS \)~TE~ . ..\1\I:.~E ST.I:.FF E'NER R-IIV~ S\R~S~~S FOR H-)\L F F\) \... \... C0 t-.J \:YI.\:!:.0 ).J !. CO l.J T I. ~ \) E 0 · S \ E' q.:-"1. 0 30 1$ 1'20 1S::O i fl\x \1"?>-= ~ -I -g \q -(-1\3 \1) (·O'N3) :::10.00 \"2.-z:z.. -1't1. _ (-'lSlO)(.O'PB) =933 12-1.1.. -110 -t-'-\7.5"1.l.ort\f;)) ="?ltt-3 \'l.U -s1q _ (-r!.ftlt:t)(-o,t.t~) -= -~~1 ll·l1 -'4-lo (~lsoso)(,..o~:J~31 -=--t453 t'l·ll -:tt:l G-lTl~)C.CJN~)-:::: ~1~1(o p, .).'l o _[+If 1411 )~OCJ't~) == -YfCJo. \J-.J-1 0 _ l-4Nl7}\·(Yf'f3) =-4-3,qof.. \J..l'l l\:>. -(-117,~)(·CR4-3>)=+2~3C, \a;l'2 1.:\ tO _ (:-\Sost>) (·lm3l-::--t /ltSs \1·1-'l S1q ll·ll (-'-til~)(· O:N-3):: 4-lf31 -' 11-0 _ (-t-\f.l9-)Coqlf)) -=-~"t') \'l.)J. 'lq 1 -[-t-952.0) (,~Y-3):: -933 t'l·l1 S \ ~ _ (+II.3!G) (.Ortt3) -=--\DC\l \'J...;).J- -~t9 +(-1\si1'X.·o:.g,) -= -4-10 \;}..22. -~lq + (-qszoX .o3S\,) -= -Y-O\.\- \l."l.1.. -.2J:i_ +-(+4-ll'l)(.o:.s") =-+ 100 l"2.·2l. 0 + (-"-tl'+l1}\•.03!>b) :::;-! 41'-t ta.·~l :t\1 -r(-?-11~)(.03~) =--9ll \J..1'l lfLO +( -ISoSO )(-035'(,) -= -S'Ol, \d. ·1?.. 57q + ( -4-llqj(·O:'£~) = -WO \l.?.?. l !0 4-l -t~Ul )(·03Sl,) = +-~(X{ yj..?..1... 7Cf I +-( 145"~ )(035;b) :::: + 40f \J,.Jl g\q 1-L-tll31(,)(.o::s~~ ::::~\1-10 \J. .).) . ·. .-.. -·~ -.¥ l J' .... ;/;-· ) " ~---."'t , STONE C. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE .t. 5010.64 IFRONTI CLIENT &i>OJECT . Al./¥;kA &'~\~ ~TI~I'rlf -~AOu--v LAkE CALCULATION TITLE (Indicative of the Objective): ~0\A.\~ ~ICNSTO<:.k. T~~~ \R_\,_x;.S 4-~l'&C..' ~PdNW\s, l CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. I DIVISION & GROUP CALC. NO. TASK CODE \S:;co1 C:S ss -~4> I -t "-A *APPROVALS-SIGNATURE 6. DATE REV. NO. OR NEW PAGE \ OF .. &OJ !b. QA CATEGORY (v') 0 I-NUCLE~R SAFET" RELATED OII om o ;J/_~ OTHER OPTIONAL WORK PACKAGE NO. ZG L SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED (I/) REVIEWER(S)/DATE (S) INDEPENDENT PREP A RER (S)/DATE (S) REVIEWER{S)/OATE(S) CALC NO. OR REV. NO. YES NO D~ w , rp"77eR.. 'l;~a.~ / /I-'S-.Be;. tfn/81 (} f'JJ~9(JA DIW"t"l:l tel.. A-"X t' ETi~ M . L.. (7l,r\l;t'J r1 ~v.J cv~t. .. I~ & u v I-~ -f';~ \ f'J.S'/88 1/~ ' (O.W.Patiar) f'1 UJ?~~· . - DISTRIBUTION* I I COPY : I COPY GROUP I NAME & LOCATION 1 sf~T GROUP NAME 6. LOCATION ~ SENT I I ('II) RECORDS MGT. I ~Ok. I I I FILES lOR Fl RE I Jo~ I / I I FILE IF NONE) I t=,u l=j~,.., I / I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! I I ~--_..,..... _____ ..,...... ......... """!"1 ........ '!'1"'!"'~--~·· ~---·-·..,..,··~:--"'-• -·------,..--------- CAL.CtJLATtON SHE!:T TABLE OF CONI~TS ;..•m HIS70"1C OAT A (R.c:Yi:Won1,. Additions. Oee:iocn. c.ct:.J PAG~ I OESO'W'T10N I ORIG. R.EYISlO."' I ltf.rtAA!CS :-40. !tE.VtEW .'«J. OA·.::. I I 'Tine ~AGe I L. I TMlr O.F Lc.v~~ I I IJAx I L.lh1' n~ ~6-VJ~::"I1H.f..? I £. Jt. p,.~f· 3 I L ""'-C. \.II. ... -c \.o'Jo.) :::n..~~~ Atll.&j I I I 4-<a I A<Ssu'"'Pf\o-N. Pot 'Peo~cJc S'1lE'!><:.etl I I I ! I 7-19 11lfl'~,,"~'fi..OI\l 1F 'f>~<,;TZ)Q ~1'RA::'ru;n I I I I I l.o-2.2.1 'SoMf-1~ oF Pe-~"RX!:. ) 71l.c'"SS~ I I I I I 2.3 ~ -ztl CoMP.,1Jm S';ur~e-s '"' \ tp~~roct I I I ; ! ! ZS"-3() I Movt~~ @ S'P!tft,ck ~lrLI/€ I I i I I I ' 'IT tbl..u~l ltt,.,J6 L.+yl\.1'1" A:NO I I I 3/-3(.. ~c. UL.A-1"' ~ t-1 1::"-f'U..Il I I I I . . I I I I I I I I I . ' I I r. i I I I I I r Jil l~H'al~~g.,..;f1!no I I I I I I I I i I l I i I ! . I i I ··"· ~·--------------~~~---~----.-~----~----------------------------~------ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION QA CATEGORY I COOE CLASS N 1 I' ~~11~ CALCULATION SUMMARY 1 .1.0 .. IW. 0./CALCUL7ATION NO. 'S3oa . 0-~ s:-SQ !_, l-t,::_ ,:::::, &501062 CLIENT lf'IIIO,I!:CT ~PA -,..._ "j I' I-c !, :::--.-~ IUI.IICT I TITLE (\ ' Y cr.~..;::;R t"v;}}<;---:)r 'r OI.IICTIVI 01' CALCULATION CALCULATIO. IIITHODIAI&UIIf'TIONI LoN:li..JG \ : 1) P~;;sv e.e-: ~) 1'-Jo~t.M Il-L '"f "-AN~ I t:N T .b) Ew..r:o.&~ ~A.VSieN'f c) f""C!c""P..,.t-tN~- IIIIIVIIION h-,.lf'~U L.U. j 01' QA CATI!IOIIIY I CODE CLASS - Cfr·t) /o "Z o f1~ ( uo-t' A DtoJ(,,V ?DJSitlC..\< i ~ ... ~~~..i. J.~.~ 1 .) / ~ -~,' . 1'-:.-"t,. M,;.,;_:C:·.;.Jl. -tvr .: I'X;___ · o) UoAM!n... 3-o"+ff 0 ~ E:~o~.~C.I::IJCLI 4o 45'!: j\ <:::: c:.J~'XLE'P""'...u...,~ · 46ool:. l\ ~1'~1..!<.1><.. '1/>r-\.vE. MPtX. l"''.UM M./)1/~t;:N( :. Ytb l> ' S"t::lsM_tc.. -= Ri4l~'h:h;;:.t~i'h "lrlr:1 5 ~t"t.,....,.,,..~ A.Jo""' F--.Jl\.,1 :erx:.t:..-_::; r; :.J :5'""'3-;Jk. 7 74-o ~ ~ ; 4.o c IOUIICIIOI'OATAII!QUATIO~ ~ '"'"··'ill, 1) s~c.ru;tA-,.. 'D"':-s: G:,,.J '--R-'""'"1.1? p. """"!R.:T A, -. r --. /""' , .. , )-r!.u:.-:JPf.· ~c'::rJ --1 ·-:_j: :=-'f.,o_:-r-3 1 O::.r'·r..cr) """''~ J) ~~<,..v~ c,, s~_..::..s t" ~ • .,,. 1-J Ro~~£_ .;--"~->IJJ.Jt.. .:::-:::. --::----=----.,:::------:;;--·-' . . I ~ F")!t.JJt..c:. c.-:-, ;7f~~--: ·r -7',•-·..J, ·""':..;::Jf"t~:, 3u~r..oN , ) '5~/VG'tf.l or: Mll?"tll'IM.:S Suv61::1Z, I 2 tV f) IW1"0~.0 J 1"1(;, (_ ~) n~~~-~~~_c,...,....,J,~, :;;,~ >, ~URNAv o_r; R ... u..AINJ/'f(lo,..,, t<t1s' I) roc_ "p1;;;7'JS77:1C)c ~~ST lol'lf)S 'I J. ~,J ""0 loJ' ')~1'11'-rJ 1)1+;":>1) 4. 2/-8:; 8) ::::oc • f2..w,src""1) -:-~ ••. nr L;m;,::'( 1J11~rN -ru 'G:Hr;lt#';;.,.Jj,,v~ ~t1J 7~11• dC, "r1 Ac.:r: 318..: ·a?. r ~~I\) E. p£_,..J ',_,-<-'_ -DATI II '1 3'0 DATI , J.J: /2 '7 DATI CALCULATION SHEET 45010.61 P~REPARER_fDATE I , !N, '-·~-. -. '"?". SUBJECT I TITLE Ptr.IS A STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATI H NO. PA8E 158oo, og QA CATEGORY I COOE CLASS Le;N~r.i!' ¥=> Sn.t..~ y.::.. +AT= -A,T:: 0755e>2~ D I 675'5 -' /o o I + f::...T -= c -J:::..T=-22" "' ---' 6, ooaoo 6 ( t::nl'tHi.Jt.IK: ct;,,_ )"'M:,'":S -~f'o..·,.J ~ R.of.<t.t < 'lo•JtJ~ o-,... \ ' . .:> 0 • Ot':l oo 6 G:, $"' CcCJ7 ;;:; / ~ 1 J fc":! 0) ) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I J.O./W.O./ CALCULA~ION NO. I REVISION I PAGE &5010 61 PREPARER /DATE D, (Aj ' PD -r-rt:;;-c SUBJECT I TITLE A::;f\j<::_ 77')C< I 5B 0 0 I 0 8 I '5-s o_c; f-I(:, }\ I & c: I REVIEWER /CHECK E. R /DAT.E I INDEPENDENT REVIEWER/DATE !l CJ (~. :_ .. : /f!,'l I QA CATEGORY I CODE CLASS - G4op~~.~ ~ 315' fJs, ' ' 0 - ~'~"-": :-:u""'":: 'f/;,.fl. J.A:':; '>..0 '-f · -,·., ·f.· lo 2o p, ;_ P~rB ,~ttr~~ lf.)-f:.~ ?S'S"-2 , r,. B-s-;;, j Ce,IIJ ~("£:: Y ()-<.JIIfC. ~ 1/Lo D"' l..u S Po ISS oN 1 5 l(ft-rvr:, '/ervNG ~ ~ui...\Jj Po t s so JUs IV'r-t' G.ir M.oov1..v~ ~-F R.I<O/Dtry I l?: 2... 9 'f/6" I'>~ v = 6 I J c-=-"2?f x ~'0~ ps~ v::: 0 .3 C "-If ,S";x/6 fs~ ~rt ·. i)/Hrs b~tJ.>~ '11ff <:.c-NC ~I? 5 f2' IS "1l <-LcnCf[hAi6 !ftJ/) t...y r o,J L y -ro ~F 71?tA)'ST R.,f,1/G.:S. UPs~A r;:,t:F r.:: NC .Ac OAt:AJ r /...) 1 u... RA::-sll'tP.r ,..J 77fc "7~ T{-/fWST '-'-v"'~. z) wl-j(Lti 1'11-£ Sfn<;Mt<.... LDAOtNG. Is CQ,rf,;tJbO •.•J'-..:. ~orz.M/\1... l-1':>/'rrm.JG) tr 15 ;NJfJ~.BfiBLr: T11?tr .11 /V!CI! ( o,?s)) w G--U Lp (!)c..uJ P.. D!) .I{ I J\1 G ".) c f.-1m lti_ ~ s f {:{IJ T. "'N .J Ti:.f"r!) /1" I ; M/OR.k lil".k'l..y 1"'~ A SfJ-!Jr/)0"-NN Wi'.riJI./) OC.;:.u<.. p.t:-=_;: '11-1-f: A:e:r'ulh_ ~~7!'t4HJA~~. ~ 171/ s ~ cJ..N _.~ IL)O I.NC/Z.·(i7i;:(:-- lt0 P IJ..t:r-s s 0 ~ b u e: 11:::. 17f fl<jfJ Jl.c:, vy JJ lt1'1; <-.: r:. >-::e- -rl..w-~~~!,}Ct.{: t.J/45. Gt;l\)5t0t."'J.k{) )).J C/tt.c..UI_/t....,~ (,...! d.::- J+o~ p <;'fk.•? .. ".:. ' CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULAZTION NO. I REVISION I PAGE .0.5010.61 PREPARER/DATE b,w. Po-rr£((_ SUBJECT I TITLE /\ ft-!d ') "'"J ('_.k. IS8oo. os 5-s ~fl,.,/-16 A 0 (o IRE VI EWE.R / CHECKER./DATE !INDEPENDENT REV I EWER /DATE JJ1C ;/0/?"" I QA CATEGORY I CODE CLASS ' \ (_y_l'i-+'2Uc...A-L Vf'n.Vr= "'\011{<11.1\Zf..-lTI 1 CJ:W I i) Cr=o,._,_..::-r~ : @ I I ;--' I I ' Cf ;:::. /8,25 7 SC4lUD l-:-'--13-,--~~---'-----._..------------··-----.--~-c---2.!2 ;;;- II ' < I)' ..... ... aol ... -~ ~ > ~ -'~--+-----------+---if- --+_r.../""{_ l ----- ;-- ( r '[. P lo. L Ul-1 P~"':::>lf>LEO 11A-1!;J.l ~'<'- : ~! ·~i '.{: -.!..-+----r- 1 5'-o 1 _r::J) <?'" Cf-g 39 1 ~ As-suN!c:o cf:_ .or-umuc A-S'>u,..,_w w .r--=-=-----------"---'-------------___.. Ot= ";..f/WS I I{J tJ5 S to) u) I= r-- f=: /:-"::- GJ: (DBI6,J CRI:-1:1(.1,&..) ?A-if 3 I S'er.1.0 ( T f':9'-~ E ~-~ 1 P~:9£ 3:-s--, ) Is 00{' ft flrPPLJ(D Tb/Z.Que- A.FifJ!U.!> I .0 J7!l{,l m_ Pfl+;;svM W~'--rH'ICJ41JHS fr L4,.JG!{Ufl!Nih... s~~ :: Z:t fr -c- 2. 'T(r rt:.) -:: -rr (Cr+-t)1--,...t.) Bur "-... r"; t:'~Wv!..H ~r-< :w_.o;-~) ;> f ~ ~ki<.. _.' '11-\Jt.Jr. \ J -• u J 197:;. -:-mL~ ?.9; \c., S Tf'(k>J6 -r:~ o ~ J-1/11 tJUM... s. ~-;9c. 7. -,--p-~~-(.<{ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .t.5010.61 IJ.O./W.O./ CALCUL~TION NO. IREVISI ON I PA~ s-3.)<').08 /S-S<.~/-/6 A 0 ! PREPARER/ DATE .;;;. !.JJ, Po .,....,...,;-R J I !REVIEWER/CHECKER/DATE !INDEPENDENT REVIEWER/DATE lo !?. 7 /.'3 c., 1 r 1 :<. /n SU8..1ECT I TITLE I QA CATEGORY I CODE CLASS UJI~I A, -n<l.Ut:: l..oM)ll\.)cO UJNO!TUJrJ ( -r-n;. ~hJS:I'::;AJI P/J.R5>UPJ-;-::. v .. nitf~.;T Vf'n>J ~ oPI:::RA't:..cyJ ~) --rttrs IS oF "'-:1-f. P.'l II+<. L<JIJ.r; l:lF'iJG ~s R.::P--t:IJ l'tr-.a,J6 --;g .;&l..lc.-.:.. .;:)!:' --~ PIPfF. 1:> 1N 5 pr;cr ... hl..) jt:: "I ~~ 1../.f'NC}(-Hrs~:--; ~-:> :_)/;:_..,--<' •. J =-1# > o--: -I v . )A) WIJ!I Vlh. Lf e b) Ax.tlrL f!+ttvsr {...<)P..fJ c...) ~P.r;r~L Lofr~ bl)e; To U/f-r_·J f: fJ."l-r /'",._.,. :.. r, ., l1') '3(C70D rAJ6 i)UE 77:> Vhll£ M-tJ tJ tiV! e:vr I" f-J 0 /l...JVl h. I ! /l..A7-J 'i I i:N'T-lV/1/-i If '' I s A.) ()-'f' A A...Jo~ lf"L ~ l) I rw,..J ) - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 IREVI810N I PAGE 10{1-& 6 1 ..1.0./W.O./CALCULAT)ON NO. /58(":) a, C 8/S-.S 2(:,/- PRE PARER /DATE ·\ . u 1 . PC!("'""'/· 'l' . I / IR!VIEWER/CHECKER /DATE IG);zr:V 8 G ::L I i'J. f('! I INDEPENDENT REVIEWER/DATE SUB.IECT I TITLE !Vt:..f'l"i;f"'?) c.k ,.-( ll ;::::;>-0 se-~~' =/ !>?< 17{_ "'"" 3o u £.kUZPr~: P:: lo to fs ~ t::.~·o= E A1 f11.. C::.eNcw : r:.. ~4i-' f$:... Ek c.r....--;orw lh..: P: /OtC>,,.. ... f':: P~tJ:;-:.suiL-1::- r -= 'f4>-o n; s f-.:. ..;.._;.,c;.j<)t:;;"c;:; (:,4D 1 s~){ sa") =- 0. 8$'" ( 4btksi:J (t:s45"es~ J ( 3o ') :. ( o ·ES~J { 00.~ ~.;) I QA CATEGORY I CODE CLASS Ck.1DtsJ ( 39 ') _ ::.. O ' ( S 1-,1 <t C:>rl~..oc..;.,. (9·85 )( 40 ks.~J r CeA<; tst.)( 39 •) -:::. _:J ' )8 ~L. (o·9 :::-) (6G.S~c-s~) o · ')S CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &501061 IJ.O •. /W.O./CALCULATIO.N NO. . 'REVISION I PAGE ;~-sod. og Is-s;; c?GI-16A-ffi '1 _/ / JR£VI£WER/CHECKER/DATE 'INDEPENDENT REVIEWER/DATE IOjzP./ .8(; :. /1'l/8'l SUB.IECT I TITLE 1{,__../\J s 77'\ r 1.- C~fh. f = I o 2. c P!> .:. E K n --r'rr...QIIJ th.- P-::. /OZOf'i."... Pt~ -l:-: .%" ....-vn ~ -- o-;; ':::. r .. s9 '' " (, 4of~ ;)( 3~ u)- 0 17'5;"" (a+~>si. )(59 9 017:;~< (J6'LDrs~'f 31')_ (Ot"7r-1 ) - I QA CATEGORY I CODE CLASS - ' l..:::: '"c:;, " ~;; / cor. 3~. 28 ).;..::.(_ ., ..::. 4.o~z -' a'- \ ;::; 15f{ kSL' (~ ~~-G~cl) ' ; ,/ ) o4 /.-$ ~ ( < 80~2 CALCULATION SHEET 65010 61 PREPARER/DATE b.w. P~y:----BJ SUB.IECT I TITL.E p"" " c.r: E. )ccEfrw,JA-t_ 'f :;_ /Ol.Op"':>i. Ekc.t:Pfi-()/'IAt.. P:... /olor,z.. STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATION NO. PA8E !~(Soc.>. c>& s-S:<.Co(-to REVIEWER/ CHECkER /DATE 1 "'"' l;n c;-;-:-~46fJ;X39") 2 { 0 '"7 s-) :::: c-;-::. (e4'::(;,.:..}( ~9:) 2 (o.7s-") = ([o "LorsY51·) _ v:; ...,. 2.. (CJ·7~") - QA CATEGORY I CODE CL.ASS \ (..;. 4o~2) !'"', ~ 4 ~~ / ,\ l.. .( 4-0k.::,l/ 2J,97ks~ ( .c....c,G.(,t,. / 2C>. 52. ~<csi. (_ 4 eo~!· CALCULATION SHEET •5010.61 PltiPAitllt I DATI b.w.R~~ SUIS.JECT I TITLE Pe:,Js-rc:> / / / /' / ~ G -/' G - :. S-18-310 \ '-9.s""'/ !,{ '1 lb ~~ 0. OGo7 lo9 5~8 ~4 I STONE & WEBSTER ENGINEERING CORPORATION .I.O.IW. 0.1 CALCULATIO. 1110. I' All !S8co,o8 /~-S:1(p} -Ito /( QA CATEGORY I CODE CLASS \ "" \ '\ t ~ 0 °-) /-38 •S II S3 11 , I r ( / / / ~ \ ' ---,L ~ \ J ' - 0, OS""G3 K <- 1/ "' 0 SE: f/6 r'J~ 3 ~Aio 'rJ G \ \ LBO"'"!...' s up{'ofi..-T"S Lif'-r4G CALCULATION SHEET 45010 61 PREPARER /DATE ]), w. PG>7":?'""~< SUBJECT I TITLE Pe:NS". ck STONE & WEBSTER ENGINEERING CORPORATION J.O./W.O./ CALCULATION NO. / Boo. C8 s-5:.:<0 /-/~A REV I EWER/ CHECKER/ DATE llt'J... In REVISION PAGE & I~ 1(....- QA CATEGORY I CODE CLASS I (e-0 I 0 e:. ) I RAO) s;_,,.,Lt /bP4JI< R.~u!R..€'0 'K> of'n\ttJ A G/t}lfi-J A.l::.7M~ I~ flfi-Cifdl<.na/11/J-L 7""0 ~ Pct.~tt< MAII'f~:iiJr OF /NI::?fTlA-( 1 = :e J) ) (.(')tJStJ'(..V'H-?'!1Jta.7 /f~Sf..)/Vl!F ~:::?vr;;e.e l_tg.j61' II c,,:-lle ouc..e~ 1s li:Qu 1 v R-t-15N r -ro 77-fZ; ~ !_ G u f Ill' ,o~ \ -J -&-::: JL JG I= Tr - ~ / Fo-fV.\<Jt./'rJ. .'> 'f<.tp,~ti. ) I j P7· 2.2;>7 r- '!=-of(. ;t.1sJ I 51+( 1(1 (1?.-d~l /}Cc..o/J/111 Pol( P.~...~+"Jt:> ->iJfF ~:f> -· I lfl I\ S"'~s .;. .G-'"' o. 00 I/ /U+()IfirJ 'i !t:>TA-t, ~"r71;4/,l\..) You,J(, Ptpt'N-1Ft) I TZ,o_,.J li1r;' I I ) ~ t-6P-~ = 0, oc II ll.AP!Jh.IS IL1. :::. 6, oo/( RPo,JWS CALCULATION SHEET .0.5010.61 SUBJECT I TITLE P~J s "'"DC!< STONE & WEBSTER ENGINEERING CORPORATION REV I EWER I CHECKER I DATE 1-/l'J-)E'f = (), Q c I I }UIIPtA,JS /(#- ~~ REVISION PAGE ;1\ . 1_3 QA CATEGORY I CODE CLASS A!Jit..yf::/J 3)' A.JC~~ ~ !Jw~z_c,r n5/< t;Jue- :z:::_ ,.. 5", .B4f)o o -:: r -3')ll DUE 33 ., (0, 0 G 2" )( '-9 )(({J c, f'i) ~ 48! :{12 'I; 2S7 -1oo.;, 4 ( fiJ:Lif2:J!E -f/!1.5 I£'Utsrlc ::;.:..:-,~ 9J rJ.:;: • C,:>~t;J 5'Gq<AI(_ /.oM)> 4Q.e CNI8t~<JW :-vf"'"'..J 7t.RAJ5r c.otrfJs CALCULATION SHEET .&5010.61 P~PARERjOATE .P, w , t-'o 71..::: . SU,fECT I TITLE r (:;:!' J s~JC/(. ( tJ ' --'iJ - ;A) «. STONE & WEBSTER ENGINEERING CORPORATION REVIEWER/CHECKER /DATE 1../t?. (81. .;// 1. ALt M.~u1110 -I ~ tk ''if 16 ' ii ~..u. /bV,<;t 'j~£ 8fr'; E7? (A I.S' 111/Nu/11.. . 8vJ> q)~' f7. t..-n) 3/:::.ET 3 = / p -3 ::: --""---7~---,.:......,;_.:__.::.____.:.:......:!. ...::';::> PA8E 14 QA CATEGORY I COOE CLASS -' II u_ ;/..f.:-D~ ~ o~= ~/, r CALCULATION SHEET .lt.5010.61 PREPARER £!'ATE b.w. Po,-r· SUBdECT I TITLE J 13tJS ~ CK_ Pul{f'o Sf! oF 71ft;, lof10'N6, STONE & WEBSTER ENGINEERING CORPORATION REVISION PAGE & \5' OA CATEGORY I COOE CLASS WA-ftr7'-~NS~ C.r VA-t I)'<:: vlh . .tJG'") EL ·~-'-=~'==~,.--i'~ lA~IU.N OF r;IVJ...l' ...,_.! ~ ; t:\£.t:-~ ~::.. P-t-~ :.A/Mfr?';..t,J l'/ 7C. 1 Pi . 7o i "7 I . i De": f~(t (z-~) t~ ~(z-~)] ~we- ,_ <:1 /03o -' a .J -Cl LO PIP~;·. p , E I~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. REVIS I ON .. 5010 61 1s-a oo. o~ s-s ::?c., 1 -/c, & PREPARER/DATE REVIEWER /CHECKER /DATE "1.w. Po,-n:. JJae 1./!'J-/2'7 PAGE Uo SUB.IECT /TITLE QA CATEGORY I CODE CLASS peNS17 C! 5 1 -0 b ~ P!PG A$;, 'H.IVE "'-'-\: '>4lS~!T" -p, < ... ,) "'' o~_~ ::-r_,..J "'! ~ .,..~A-rj) .:Oc"-tO ~, ~-~:;r P.l/'.16~. Smess I ~-tt .. 1 r 1 I I ! i 1 ~ 7/ i _, CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION ..1.0./W.O.ICALCULATI N NO. A5010 61 /~8oa,o8 .s-S ;;;GI-Ao A- PREPARI!R ~~~TE ]), w, lo~ REVIEWER I CHECKER I DATE UJ3 i/l~[t'l SUBJECT/ TITLE -' .J~C~ ________ !"~~"~~ ~~~~--~'s~--'-----+~~,~~----~~~-~-~~-~~~~~~.~·J~:~~~~~~~]~~-.~~~-c~~~~-/--~i -.,., • ~ ;___---..41 II Ass~ M. E. r.Jf- v Aft I '-CS L 11\Hi-.A R L -: 1"'1 vvV\ivv- 4oo /, Z;t/, I. 2.3 "/r t -I i· Co;; PAGE 17 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I.J.O./W.O./CALCULJTION NO. !REVISION I PAGE /s-8oo. 02l;_s-.5"::20/ -IG A ~ IS PREPARER /DATE ]), W, 'Po-rrt c / / lREVI EWER /CHECKER /DATE liNDEPENDENT REV I EWER /DATE 10fzB!8r" JJ ~~ 1-II ~./2'"1 SUB.JECT I TITLE A-''}J~( K ~tJS~/"'1 M~JJA)c ~ ~ /o 7 I ;.__, 'til')!] 0 9<. -.,. L.. j~ g J< I 5 '-a to rO f'IPE - p!) ~ ~ I QA CATEGORY I CODE CLASS :.C;I'.l -) ' \.) f ~ TR.(; ~ 'E' ':;01.A)I\) ~-rrwt:t'! --~A}~--~~---!:-~~~ / \ / ,...., ; \... . /79Z.. .l I f-4o <r I a '{J ) -o !D 'Pt' ~ ~· 11?.t ., 840 ~ I '/, Jt z K-17)'. 0:ro') (32 _ 1,) !A) r ~ L . 79. ~4-78 o.o9817r( 79 .5 )"""- CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION r .1,0./W.O./CALCUL~TION NO. ls-8 Od 'os / ~ S'"::>G I •5010.61 P~EPARER ~ATE j, w i 0..,...,--~-,; SUBJECT I TITLE P<t-~j ';,""':)r 1, =-7 I -! ~REVIEWER /CHECkER /DATE ':; 2B)B; JJ r}_ ~ 1-(t~IJ>'? I INDEPENDENT REVIEWER/DATE r QA CATEGORY I CODE CLASS 17-rt::s~ 1?~-Mit't... "'~~!:"' 0(.C.UI( OAJL't UP';"tf?Ai'/rtvl Ill!= Pr!VC,tf.JI{ DLoU:. .,;:,1\JCA!: D~t-Js~.A->vl ~~ Jr:-fJ-t;t; '1-0 l:;.'"}:_jJftNI) ,;-. ':';>yJ?P--T Due: ~ St. I P yt!> r N r, Cp/(;.,-.-dtVA 5~S' !.:::;-: /)v E 70 -;_:..-:?0 ;r/h'_ ?'-' /1'-,.!J I J ;oJ IS lt)IJ(,,;;.[{ct:,f"..=:t)_ S~ Jus.77P':./r"'~4N 1'17"' Btx"-J>'fl ~;:-/',A:J-~. o,_, I AF-r!CR C¢,-J vp~-/Af G Is (..,.)A) s /~eiit.A"D 17../-1? lt-Nc...rrJ/l La c,t. IS,. ~u,/J.-ko f:::;,l(. 4--:r~p-.A~r. Aer~ ('..,r'Mfht;;r""/"&'),.j ,r.: ..,-._:...c HX.i~/.. 'e:>~..ACI'-eur Pfi...A..DI\ -n> PL~IU-.)T cF ~M:Cr='u. en,.kP::--'? --:-~ MAr--ltC:Ol(;) IS 1\ll>-r 5 1 G#.jli-'!c_.4.,(_1 f<.K"S--FJ. rJ.:.--;s > !:;;cJt:_:;_,t -~::F s~--...se:. PL A /trJD !),!)_:. t=' -==7 p =- jjf) At: "' Ac = c '- A!J At;: LA - ("' -=-x =-c·ctL,LJ~;;; £:7 {:,4-,v<; ' •'..; ( lJ6"'( i)f!P'V).) CllciVT 0,.,; V-J(,:'" ~ M CFUJ-;s s~-:r .... )rJ~· r··~or ~ ) 4, 2 ks i. /:)(fG-rZ-o-;VIf-1.._ 5';";(-£$$~ CAN 8E C.,.,Vs; ~OUJ) A.I(;:C.. Lt C:.II3.Lt:-.Pap---::> ---:-'-'1;' ~.J lihue;:-:;. . ~ ,...JG >'-0 P'J. ~ 'AI~-':c·'Z I; ~.vLy ..,.., I.S Yt ~tJ w,-r,opRA:..sr 13tE 1/J~~(J? •/'\_ 1 :s -ri"...-t:: Sf ik:J< ' ::._r: 11 At. I} E .LJA-' fJ.. ~ 4,-~ •• ~ ~"" 17 1 1:-th:: UAJ rr ;;:>~: -"'P :..J~ ·; ~"' 6;!=' -.;.... _,-·c- 'kssv'*t: _11-=-7. o , r!)'7'h~ FlU ::-;J,....) p ~ Pf ki ~ 2 ·0 (;. S" ( 17 f //, 7$;') ":' 30 )c:. ' !-·~.)(._J1JJ;-) ~Ll01tJG %f(r::~....-£ tv-r /JS;,u.-~·J.;JA-::{)•2 .::;?P "'t""')-r·_ f.--1 c 5 1<. I c 3 k-/1?h,&.. T 1 '1 -~· 1-:--s: l ""'7 .VEGU r:.! w: . CALCULATION SHEET &5010.61 PREPARER I DATE D, w. PdTTi SUBJECT I TITLE / A s:l.J fv\~t.~ of: s~S.S!::-s q: ~ \.!.., ~ : .J J ~ -~ ~ I I I i .. ~ ~ I 1/l ~ a (. ~ co 'f=~ o;;:;: ~ -. C0<1 '-' ) i "'\!~-'"'t o -...::.. • I .......::. >( "' ~g II> 1/1 <8 ~ :;1 ~ ~ <8 j l/1 "" Q.~ ~ ~ ~ ),-1." t-\,-\,"' ,J "' -..9-.Y.... ~ ~ ~ 0 ,.) a- 4; ~ '! " ~ <l '2 ~ C\ r£ w .Q =o 3 -I ....) --\,/) 0 .1.0./W.O.I CALCULATION NO. REVISION PA8E /5"8oa,ofS s-s;;<b/-IG & LC' REVIEWER I CHECKER I DATE ;::-J-0 ~ 1-/~&-iC:,.· I ' I I l ; i i (~· I I ~· l J : ' - . ---t \j-. t "'i L ~ ' -.:~ --i I ® 'tS: . ..., --I QA CATEGORY I COOE CLASS "/ ::. w.,uc ~>sn ~.:. ~. s~5ES I -= s ~+r~rq_ -;; ne.t->Sf:"-.:l ~I I I -I ~ i c;-i c'") i '-"" I GO ; ~ ; i \ i ! I ; I [ ! I ! I ! I I i I "'t' : ''7-i .--....; i --~-...: - I i ..,... I ·o -. <0 I '"') I "-'"' 1 ·-' X .!' . ..., I o::--"-"' .ll.. i "' 0'- ~ "' ;t I /.r) N -- ~ ®-~ ~ ----- -0 n CALCULATION SHEET .o.5010.61 PREPARER /DATE D, w . 'P()T!i ~ t Vl'tc;; 0. w•c.c~ I C.n C.I ... UU'fC.C.nU'IIU Vvnr vnn. II VI 'I .1.0./W. 0./ CALCULATION NO. Is-Boa. a e. s-s~b I -!rcA REVIEWER /CHECkER /DATE ~Ill Q 'If·~' f?r 0'--j LJ-'C -I 1, G' i ( I REVIll ON PASE & :_I SUB.IECT I TITLE QA CATEGORY I CODE CLASS R;c -s '/ ::. u,.JC 5"77~!.t:>S"'J rt_::. TAU:;. S~5CS T -:= S" ~ ., no1-->St:----:. ~.· ~r-+---~--------------------------~----~--;-------------------~---------------- ..J i t;1l ~ "<t-· ! ~ ..., !"--i ~ ~ ! ~ ~ ~. : ~ ~ ~ ~ n "':f-I.J} ;~ M [<) + ~· I ~ . I l l -c \;'I ..J : ! ~ ~ ~ ' I : I I ~ ~· : ~ ~. ~~~~----r----~:-.1--~~.~.~(~.~,~.---.. +--~----:--~:---~~~~~0.--lv l I I I ~~~ ! ) : I ~~ "\ j* -rJ ~~ , I I ' .. ' 1.[ ( (_. - - - . - c CALCULATION SHEET I.J.O./W.O./CALCULATION NO. I REVIS I ON I PAGE •5010.61 PREPARER /DATE D, w . ?"' -r-rr-"R SUBJECT I TITLE A-::N '5 TIX-' ..J < '::!. 1< I s-8 oc l 0 8. J s-s ~ b I -I~ A () 2.. (__ / I I REVIEWER /CH. ECKER /DATE I INDEPENDENT REVIEWER/DATE lojZ2/8c. 1-)\'; ~~~! ;}JOB ..,.._, 0' ('1-. \J) rJ i"; i ~ i .J ~ -+. • i "t' I : 1- I I I ' ; i i r-J ...f N i "i- I I \ 00 (') - C') C"J l QA CATEGORY I CODE CLASS '/ "-L#,.;C ~>SIO ~ :;. TAU;, S~<::..:!>ES I -::: s ~ <>ne-t->Sf:'~ j I' < ~r-r-------~------------~----~--~--------+---------~------------------------~ ~ ~ I ! I ' In ~ Q if &rl ...., ~ "2 0 ....J 1/1' "" Q.~ ~ ~ ll> _, '£ ~ g I -' ~ .. \1.1 .., 5 <. s l'- ~ 0 -..J w_ i I • I ! I .. \ ·f~i*~ -+ '-9 --··· ~ ., -~ I rl i I "' of) I ~.-I." t- ,J "" ~ a i '{ I i ~ ..: 0 2 I a ..: ~ ~ .£ ::::; c;; I.L. ~ --9 "'-() -l ~ c:J:: .....) ~ \ ) ; I I i l . i i : i I ! I I i I : I I ! i ! : l i i I I • I j I I ! : ·/~ I -' I () I fQ I J ::2. ... ~ ~ ~ 1-- j ~ .... ~ ~ l.t CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I J.O./W.O./ CALCUL,ATION NO. I REVIS! ON I PA8! .0.501061 PREPAR!R /DATE ]) ' l..u . "Po T'T€7{_ SUB~ECT I TITLE 1"¥"-N <;.mGk_ A_._~ . ...)~/-1 !h P..'::>Of'Jfl.ra LV ;sooc. osj~-S::?.Gf-IG, f. a '"2.3 I ). IR~IEWE_R/CHECKER/DAT! J0/"?.9 a' If> o C:. 111' lei' I INDEPENDENT R!VI!W!R/DAT! r OA CATEGORY I CODE CLASS c:t'"'~r -l!:tj)ui!/MbAi-S~~ ""1 1 J -::_ /)~//r.J(;;f':,F :S~-:-.-:-_,., ~ s~ -.~-.::s 11:. Ou1'rl; LoW (t.~ /<c1~ J./!A-1<-) A-,_; D ':.,.,..Jl,., ·,J 3e: IJ G::S l ~~-:-;~~ (. !{~ ~E: Pttwc 1Pt-1£ s-~-sS&> Cl/-.n/ e,..-c;:... '--'J~I'--"'1::.:2 i i., e , - CALCULATION SHEET PREPARER I DATE ]), IJ.) ' F6'("'/l'-~ SUBJECT I TITLE ...... ~I'.JS ""3'-:< ,I STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O.I CALCU ATION NO. REVIS I ON PAGE IEJBoo, 08 5-<::: ;:((0/-Ira . & 2.-4 REV I EWER I CHECKER I DATE dS CA.£ ;,_. I \ ~ ( 2 r/ QA CATEGORY I COOE CLASS /9,80 7./0 r.~7 11.0 { ~~ 8.94 ~ /0, 30 3c·9 46~6~ 49.67 ~ ~~ i ! Jo./ ep: ~® 1-'59 '2 cp. /.p9 "26'.3S"" 58 ,o& 45.9~ ~ 3o.o'"3, 2~ J4 ]8,33 . 4;;, .lf ~· l. 27,03 ..J._r-.:;> 7d.., C) A.o G~ -~ 90 GG 0 ,-/ ..) <) •• J L:;- ....., d.. C) I , yo 74f; 7+o STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .1.0./W. 0./ CALCULATION NO. REVISION PASE A5010.61 I ~0 C) C) I C) 8 Is; -S" e><'" G I -/6 & ~s- REVIEWER /CHECKER/ DATE 70 n l ~ :;~I SUBJECT I TITLE QA CATEGORY I CODE CLASS p-' J::: c": c 0 f! c /'J --;;.;..,c: 7;._C I(;, A.) (l J ~· ~/ r:. 4 . ":: G'.i?: ~ 2. . ps '- I lA '""" o . oo 9 B -::::.. o . I { 8 l 0 I '3 )) -::;.. Q ' I II CALCULATION SHEET P~ARER/~T:___ .:_)' w ' ro [ . ~ SUBJECT I TITLE c:~ ~ c)-~" . :r ll 1-J .___. .;~()" I 0 c, "¢ STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATION NO. REVISION 1 Boo. o8 :;--S: :2G 1-!ro A & PAGE 2./..D QA CATEGORY I COOE CLASS [--t ~ i . I;- /(p ·S r ! J =-r I ( , .-{; "-._ ~IIJ6 --4-c-fl-.>~) rr-~..,._.~c, IS. 3G. k?L. "1-H>, 3o.72 ,l.:..sl_ c:-'-"1\l& = l(o. G. 4 J.-si.. o-lft>~ .::. 36.?..8 ks~ E J1n.G&)Jo/ : 1cr. 2S: 1 I ;: \ 10r.. (:_1 l \\ _ 4 .f-,::. 7...9'Xfo' (!o1 28o -or3l4o1 s-~)) 1-l.CJ~toC -u 1 97o-Ot](j_-3 1 94:7;;)-.:.. ::.., o/o39 1-::. EK. C.~f'Lt:n.l A1_ •. dJ = ~4~Jb, (z-t,46o-6rJG6)ro~)) + ~~~' G~s-~-0,3 (53 1 ~:>4o)) ~ 6,01'?.5 1 -:.. _), IS' I( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 45010.61 r J.O./W.O./ CALCULATION NO. I REVIS I ON I PA8E I I S8 oo . o <3 Is -<s: ::u~ I -16 A o '2 7 PREPARER /DATE D' yj,l=6..,-"7tP • I / !REVIEWER/CHECKER/DATE !INDEPENDENT REVIEWER/DATE 1 ()1'-9/~c ";Jo-':: 1-/lJ../8'7 SUBJECT/ TITLE ---.:\:/'.J ~ ~ <:_ ... )_ -~Ar--~ 6"1-) ,'>:/ t::.MtR (_4;)-J~ E X c.J:'fll'c_ a-rJ ft-t.. I - Cr:,N ·-) ~ '--o II rJ::> L -=-I I. z.s-.£ 2-'3>/ {( 14-:. /9 63 s-g If:.. 21327 ~q h, A5 -=-II '1 _y5,.;; I II 8 I D \ 2, 39o k 7_/ 3 g 5" 1\ O, J '2 I [I 0 I ( (o Q 6' 234"~ Ot307~< I QA CATEGORY I CODE CLASS I 4._ 8 7 5 ,<._ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 <1.0./W.O./CAL. CULATION NO. . 'REVISION I PAGE &501061 PREPARER.(_D~_:_­ ),W.('(). J' SUBJECT I TITLE 0;;/\.'S:-;::)Ck ;s-Boo. os/ s -~Qt. 1-J(c, p. ZB !REVIEWER /CHECK~R /DATE ~INDEPENDENT REVIEWER/DATE ~ (]..~ l-, \~ {21 I QA CATEGORY I CODE CLASS C I I I 39 I l= 1 +-/':) + /(,7) r ?.2..5" ~ ... f::.Q,. (o.ooaoob~)(~<J'.xJI.''/,)(7o•J ._ 0, ?.13'' -11 ,2_ = ( o .ooooobr:;;J{?.9 \r;'j, K-75c) ::: -o, 7 "LQ (A +-IJ.,J_ -D -f::, .Q_ = l 0 I ooOCu~G~ X 39 1 )</2,/: )(-z?.:) -;:: -J. 6 G 7 [I ____. I 6 Tlh._ J:;... '1\.t!K. M. ()" IJ'Nt 1::;/'JTI Co,.;n~_.J G S'rltt-lllck VmuE . .. ?-;.Tf.rrl {. ~~ -0./lB- (9 <;"L.IP Jot/If'( I 5h ! CALCULATION SHEET .. 5010.61 PREPARER I DATE '). w ' ? 0~0::1' SUBJECT I TITLE D-f!:_~ ... l"'!, ,,. ~ ....J _,.- L STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./ CALCULATION NO. /s-Boc,oa .s-s -<e:,l-/(o A t "/'/' -0 ~. QA CATEGORY I CODE CL.ASS A601J1 4' F~ 1fJ-r! C~NC..R.e(f: 'SPIPAt. C:.lr">. ;JJG J /Jt:C&L.r;cr ,Jt:::?'-o!g-C-7'"'/.J,J .-LrJ/J rz..o...J . (t..>!:iGttvf'" LA"f~•A'\.. ~vPI'~r J IJ~&UO IAJC~/'t'Sti) ~ Wti:Ui>t-+f 8 RKD IJC.£~ $It ~ c_c " T D P 1 P!: J 1:: "" o, 0 2 f ~& r-:; a, o 4 0 o s 7 ( o () 4 -ro 4 ) 6 .o49o87 r}fif!i)4 ~o)4 ) ~ )1; (;, 9 3 "' ~~.II CALCULATION SHEET &5010.61 PREPARER/~TE b. W. t o-r:7Y.. SUiil.JECT I TITLE P::..JJ<;;"TOC A = STONE & WEBSTER ENGINEERING CORPORATION .J.O./W.O./ CALCULATION NO. PAGE Is-Boo. os 3D QA CATEGORY I CODE CLASS CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVIS I ON 65010 61 0 REVIEWER/CHECK! /DATE s--·~ J-~:, ~ o tS 1.-I l~ ( ~ 1 SUB.JECT I TITLE QA CATEGORY I CODE CLASS '-"'I;' f) •.I" f· ·-LP. i,.... :;-r'" : p,; \S9co-FS-: :~~::fl. SILrrQ-1 iS300-3-S-SQ,G :7 c SPHU>ti'L IJI4c~€ (."'19) [1, IJ llf"R,J~T Q,uG~ lP~ r:oc.''P~sroc.~<. THTw~r-Lllru~: J,~ TO w.s ... lliJI~~ J_·u-8(., fM..ER-Gt4 Ex C.cPn c..,J A,_ ~o-Qiptl:/J BJ l:.DC. "~tst'OTH1wsr~"1 bu~IN"' ~1/fRNM/D""'t.l>rJ '1-lg-3' ' II B 3 o44-k.. I ~83.) I 4-o43 1 ' I -• r _!_ ) CALCULATION SHEET 4501061 6-ZJ-8(o SUBJECT I TITLE p(:c STONE & WEBSTER ENGINEERING CORPORATION IIIEVISI ON 0 QA CATEGORY I CODE CLASS ' ''A" 1~,------------::::-...- ( 4oo:::;; pra't eL.o(.\(.. ~ ) GMotf A 1 C 3 -~~(~ ~ '\ \:;:;::::::::. \ 3D DO f5 ;_ 1 '3 w c.J.<-.. ~ (b!C'>/(;kJ CY{'t.I'A ) PA"(_'2 <;;;t-v J),.Y ;; 0 I 'i-f; f. • s: l' I CALCULATION SHEET &5010.61 PREPARER /~TE. D' (;) I Fe> {Tel< STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULAT)ON NO. 'REVISION I PAGE 1580':3. 08 / ~-S.;zrp/ -/c, A 6 3 3 ' REVIEWER /CHECK~R {D~T~ 'INDEPENDENT REVIEWER/DATE 7-so -Be. '(;; 0-. r;._ ~ 1 t "' 1'21 IQA CATEGORY/ CODE CLASS R..,,A/~ \~It 'fk PeA. De:rr&.v C~trn.t,A-, ~r ~. S"'e-zn.)t) :i, -rNJu 2. ~Jkm ol') Yl~no 4. ?'"\! • v '~:.. 'f k~Gf'tJ'J {; X C..e(J "f t-(TN fr.- \ 45t<-s!: ( o,<sor:; 71.9 J.-s~ (a,a;~~ 72-. a Cfok.s~ (,,o,)) CALCULATION SHEET .0.5010.61 .. REPAR!R /DATE l>. w. :P~..,.,.-e~ IUB.J.f:CT I TITLE '. ~N5-n5C~ -7'Z. STONE & WEBSTER ENGINEERING CORPORATION .1.0,/W.O./ CALCULATION NO. REVIS I ON 15800. og, -5 -'fAG? ( -( (., f:-D QA CATEGORY I CODE CLASS 1-1 FoRMULA' fcq ~..,.! ~·Al r=;;::ru Ci1..., -J KoM)<. 4 Yaurop /Cf7'5 MBLE ~ G CA:se /o 59 7 I ' ~I ) ~2-1 f_; Co'-rFfCib-....J'TS ,::~ c..f(/t/!J o,.J AJa:r f).oc STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .1.0./W.O./CALCULATI N NO. REVISION 65010.61 I 5"8 C)O ' 08 s -5 .Q (., f -I(:, ;. 0 5'"-2/-8 c. 3AsrnJ e>JJ 1/ ALU t:!S (3, I ~L 2·0 I /,<;> /. C> 0.'5 0 RE"F '. ~: 'T'"A8uti\'t:I?O tAl , I /.o OJ<.) V = 0, 7_ ~~"c.""'() iM Lt ) [ ? 2..0 QA CATEGORY I CODE CLASS I ~ C.kf' CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION A5010.61 I.J.O./W.O./CALCUL,.IOII NO. I REVIll ON I .. AeE. 15"8 o o , 013 I .S -j c9Jo ) -I f.A f. 0 ; G PltEPARE!!LDATE ]) W. ·~cyr-.;~t IRI:"VI [W[It I CM[Ck[R /DAT .. E IINDI .. ENOINT REV I EWER /DATI S-'2/-8 b )5() ~ j_ /!""-. /2 r) IQA CATEGORY I CODE CLASS 12tAK SU8.JECT I TITLE Pe rJs roa .. -~ ps-r fV~ D1=-1?llf>ortoll.) OF i3~AJG Du~ 10 U7:(..M:CC CL>!JFt!lfi?J.(t:::x.JI /IL-.,Wil!:;Si;: .. ~l,...~<\'5-i~'.{~S"'·'··<.•:,: .. ~~ ~ : : ' t_1J-;. ~ .. : 'R ·;7 ~ F,~d ~m J~ T~+tU.Jsr laAO c~()11:!' ·. G!,,uc4(e-'S~IItC£ l.o.~tp Ot:i 1cv-J us 1:?"0 \ 6,J '1 7f.J De<fe:i lllt/'lc LoltfJuJr; otJ S 'i'i.:er j A:::uuMt; Au~ ~"-iiCAJ!.t;J:; s~s VAR!b""! F-et? Loi"GIN6 :..t"'' ·-:~,ds 'GIM/(../t~ rD /tLLI'r'WASl.E S7n<.. S'~JI:-"~ ~ E ><car u:;r,JIJ-,._ C~v~t>O) f-l ~.+~t.C .5'-ra:t. Sm..es1\ Fi."~1'C!I..<; ' (~ Pt'>'-:,,.; 0:7"4"'.4 1 17o,.,_·-E,5~ S.o 1 -r,,!Hf' ?-s-5) % YL.~D fir.~ ~ ... J..J::,I(',..._ ?; -ru.JS/: ' :;. •Aft ... I J:.o~.•;'f' I. o }, Cc, 2., 0 tl AI\ II II 8 CME' 1/#W~/ Lo~ ?!fl~ c/>e 78" ; p,r,(; ~~ !0 8 It ''£ (' No(.f<l!/lrt.. )o{4" ) ~5 F'A(:1::).(::! I EA-1121?..Gtl\1'1 464 3t ~T) "".Aor>~<::. I.(, , B '~ - :rB::,s •k A k 7710 h .:: _£_ b I( L ,, I( -4 ~ ---- ), 7 /. 3 4.8 z. (o .. .--. . . ~.- ,, 0 0 2.+ £xud"1t t:JI'iA-L 48(3o 1.: q34o" 3, I t. 3 ~7X..e:s F~ -. /,C,6, 7 CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I.I.O· •. IW.O.ICAL,CUjATION NO. ~. IIIIIVIIION I IIIU_! .so,o.sl /C91o , 08/ s -S ;;). ~ I -/ [p r: o s 7 PltEPA!tlltr(DA.TI! lit IV.· II!WI!It I CHICk lit I DATI II NDIIIII!NDINT It lVI EWIIt I DATI JJ.w, tOr-rt::-r< s--u-8ro J'l~; t: 1ftJ i2'1 SUB.IECT I TITLE lOA CATEGORY I COOl CLASS · · ?e~Usmc.J:.. ' ~.1JST PwGs - U) 1.4.)1 E X'c...t..P~;; -;>,All':_ /' 4 88D J:- 0, 78 1<-S.:. /, o3 1-<s3~ Q::. /.2.~ll /(:. J.S7 1.5 b ~ 8. ~ --7 Yrf:-•,_ p ~ bt. o/ -6 -cr--= ·t:z - p! = D. 7.2."7 f 2 =0 '434 r P;, -:.. /. o7 3 ----.:::.~,_,~~.. ... (' r ' . l_f\.{rp. : ,_ 6/{jJ V lftl .::c.~. • ~· • ' •/f1" I rJ R.a,.o:. > ':1 ~'.},..:, . ~ ~1)'7:~..:. Ill -? I 1?'>, 'l'gcZG,~."'n) ler C?-"' ":;. ~ ~ b-rc (A(;O\Jr;r) C-4:;~ _fL (L<>Q,j_) v(t.D73~ ~) 'L J_ {-.:. p:'a VoiVYf A-t.. 45 lc-s~ (),78~<-t~ /, () ~ ,, ...... Co IJ 'llt.l:n_. ~ '::' cJ, I (/ /!" 1"1t.t7l.Gf:.Y·"J 71.9 t.;.~i /,a3 ~<-s~ e--:.r c.a' / c.crllh 1'o k>i /. '2.4-!:-s.~ 6 ,q7[/ CALCULATION SHEET 45010.61 SUBJECT I TITLE Vel\l )JOCk ) STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./ CALCULAT~N NO.. . . 'REVIS I ON I PU! 158o6 08 /S'-S"'~hJ-IG f-o .::s3 ' REVIEW. ER /CHECKER /DATE. 'INDEPENDENT REVIEWER/DATE ;t, ~ 0 L I t If I 2! I QA CATEGORY I CODE CLASS Vs. <::;T'!Mir"t'i:iD (' c @_ 1i""' ), '57) ...,. /,/ s- !:.:b!. ~ (j.;~{o.79ks;J(_8')~ 45,d~{. > S ~ 4!:'/<:ft -t,:z. -Q /?.'5"') t.. -'"" (J,;s-J(l. 2-1-J:s~ ){e") ~ c:r-1"? ,4~ ..,.. ( /t ~.>"') \.. '-s-7, ~~i 41}, = 9./)Jq.,_ ~~- r CALCULATION SHEET 4501061 PREPARER /DATE f), QJ. "fo-rr SUB.!,.fCT / TIT L.E {(::?N C..k STONE & WEBSTER ENGINEERING CORPORATION REVISION c QA CATEGORY/ CODE CLASS -~f...le M/1.~ t..ci'JG. ~ ~ll 1A.Xi S7Rk'"TJ : -1::.. "2. Fo~ 7fr.AJJ'5 r !{lNG ',A" A.,. )~" x e/l -:: /0 SD 4-, c... ::: I~ '4 {(_-;;.. 6. ~ ',r: n.:'6_ 3~ k <.. ~ 71-h! c~" rf BNt-rvo.-1 Ltl"it; lk'H .A?v /fSS U All f:?'() r Wh£. "f?U J c;_K 'I::-::::.:; 6r-~~~' 4ssvM~ 1111!1 )f to cAt'-/ 77-lfCk I::?Jt-?J !JI /8" ( ,f/1 ,A.. X./ .M u'""' .A-5S {/ M liV flf(C!~E3S VM I A 1" C.c~ A-7" CA.)£" tv~) =7 -t~ h" f 1-~ -=-re~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &501061 l<J.O./W.O./ CALCULATION NO. /SBoo. oS /s.-r-<:< .. G f-Ira PREPARER/DATE b.w. 'Pa-;:-T~;o~ loPaier.. IRf!:VIf!:WER /CHECKER/ DATE ~ J c: 1 . f l o./ g I SUB<JECT I TITLE P~:.J< -::>C< -T;..,.,_)J,, R._, dG J /Vsl( Mk GH: r P-=-C::>4o f'!>;_ lofr[) O.-v <(' 1/VfS. -: 2V.., /' :fi. 2,_j1 445' ~ ) ' -z. 2,9 Y...; a 1/o -51-'1;:7"..-ll. 'i>i1U"':; s . ' t ... ~M.\'ltGtt'J"f CMt f'~ 84') p~;_ (7"":. e4~o (_ 'LS, 8 1<,.~ l '-of<{) ;; 9 %o (2,89) $~ --S+% , ) r.fa (_I·{,;. '{" e ~' f1'"'1" c...Qt;J,en. CA-re: p-= /6 2..0 jl!fl.. No = lo% ~6 Cs,?.9oJ Jo = 161J{4o ( ) 1 &..4,;-) c:-=-(ol_~J ( 25" e) ; C,{o · /. 44S" )._/c.; 0 I ~7f''' :::: '1 Co t;"" l:.s i ~ 34. I t~-.c.: ""' 3. <a 2Yc-.:, -:::--:;?,1 ~~ II#:. "::. S 1 24o -?., '300 ::6/~ ~ .,_ 41. I k--=-~ Lok[) .... /o:Ly0d6 (7.~9) :;:.. 4.C, "I. ""' 'Sf~~-: /o2o;{% (u~s-) ::: 2,(,. ~<c;i 1-I RE~SI ON I PA~ ·~ !INDEPENDENT REVIEWER/DATE I OA CATEGORY I CODE CLASS (-J '-coM f"-'=S!':' >d ~A.I )'.>""'I'.)C -==/~.:: (__i-) 1::.-"N~ ~ ·S'"l.J 0 /'J I /'J-~~ ~:: i CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION I.J.o.:w.O./CALCULATION NO. lREVISt ON I PAG~ '· 45010.61 PREPARER /DATE b.r.u. Pt;7"""7~ J':;Boo,Cf!./s-s.xGf-lt;;,f 0 - . I IREVIEWER/CHECkE~ ~D~!~ 'INDEPENDENT REVIEWER/DATE /Oj:Jo/t.C. 1\0{f :!,_;Ia:( SUB.IECT I TITLE P~t::~Js-ron I QA CATEGORY I CODE CLASS -f~;sr ~ "JGS l (_.c-,\) 'r) I PIPf! : 39 II P; ) (f 4o) ( "3'? ") ~ ... C·!7S'" -:- ( €>-I-'S" )(39) ~ o,e7-;-37, ( k:;,L. ( ro 2 o) ( 39) _ 0•7!..7';) - (0 ~ ::) _ (&> +o )(3_2) :::. -ZCQ ,~7r-} (g,4'S')( .?2.) "::; '-; 2.0 'e:,7~ :: C[<::>-zo)(W) - 2 (o· e7:J) --z-z · 7 /c "::.l. r f..-f"F fl~. 13, ( s-; t, 111 IM 11 d.)( 39 ") :... ~ ((39, B7s-)4-(s9yt) ) ~ t(p · ~lt/f' .JI.~ «'m _ _:-~<_.,.,.,: ':_: ;:;h) ~~ ~ Y .. vAlc. f~. +5"8 ~ ..... ::7RAri0t::7) 5't 4rJC~€ I, C. / Lr~· - STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET 1 ..1.0./W.O./CALCULATI)'N NO. !REVISION IPA6E &5010.61 SUBJECT I TITLE PE::N'S"'O~ - (_ \1 ~':>1" 1<1 N6 I 18 ~ I - P-- /5600. u& /S-_r-;;;;_G /-/0 /-0 4z_ '/_ I JREV. I EWER/CHECKER /DATE. !INDEPENDENT REVIEWER/DATE JDf3lV66 )Ia~ t--//;/21 IQA CATEGORY I CODE CLASS -r/.J.;}.)J<:f R, /'J(.. R.IAJG = 2V0 '= l. 89 kj ~ CrJ. 4o) Y-z.. ( -z\J~(78~) ~ Y'-( -z.s9 "/;,.)( 7?/) - ~-=- }J.G s,/1) c_~ ~ ll..\.L~Ae.l\::" 'i'~S LI!VI::'\,. D~:-~e-s FDI\ '1141 (J::.JIJ t-~ :> !:"':. e\1~ I';, ~, Abt> ADD I "fLo-..v A1.. -ru.w_,r ~.·iUG :~ RA.:c:F· ·-4-) &.l:.f'J 0 <;;~::.sc.::. 6A.J (rAJ G. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./ CALCULATION NO. !5"8 OD, Od ~ H-? ';. i-I REVI~ON I PA48E3 ! '-!) A ...,~ ... 5010.61 ' REV I EWER /CHECKER/. DATE ; 12-87 ::ro 1,2 _:_/;; 12'"" liNOE:P!NDENT R!VII!W!R/OAT! SUB~E:CT I TITLE .Poj<~ o Q,t0G 1 QA CATEGORY I COOE CLASS i"P'itUJsr lor>o -rHfiWS r lt:tl'f 0 /V:;t.MA-r_ c T-=-J o-/..4-k. +-= (73-::,~-)(rr )(a''Y5()J<J6s) -;; ~> c S88o ( 1"-= 4643~) I£MM, G)(Ci:;;7'. {r""' 4SSo) ~~ ~· 38 ~ :: /. IS' (p¢11 %: /.$7) J lvj~ ~~G ~s IIJ (!( 1/J G : (/fssuM.£ b ~ _f)_) f.JoA.MJh_ . c;,Al< :: 'SHT-I'r£... '> /.l'..R"'.>S =-T : W;J ;tO O'A.l ,{' ( ;<)(:, -:;:: ~ ~ b \ (c \G ·)' /,/5: (),5?.ks;) 8 Jo, Zkt;;_ £"2. ( f, /7 'i' ") L '· ((J:r Yo ,6 z-"'!>~){8 ") L = /1, n s-j '- (;, /:) ){o .8 'j..kri)(i") L _ /J, n ::'') 'l ~ ~ - </.8. 3 "'~' 24.3 '{ 1. 377Y~ /.5 7 f. s ~ 0 -":. '"'/ -t D•87f' 2-4<:) -;: i.( I. 177 ~{.) :! .., 7('L/ .t. . 1.47 ,.. ~.5"2 7'--: q: /., J_<C: O.G? ts~ ~ ;;: :::_) s:' . I ~ C .J· ""- ..::: ::-,I r-. '0 =--.') ~<(, torr. - < r: 1.7 ' .. S L - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ .• O./W.O./ CALCULATION NO. I REVISION I P~E./ .0.5010 61 PREPARER /DATE !) 'W • 'Do-r-r (~ 1 58oo.o8-SS-2C.I-/{,/} o -!-"1- I REVIEWER /CHECKER/ DATE !INDEPENDENT REVIEWER /DATE I-/Z-87 d'JO ~ :.-{lit-!?'! SUeiJECT I TITLE fg.r;-:) C.1•.. r'4.__1.) s-r ;fl,;'):, _.-I QA CATEGORY I CODE CLASS o-- )'-' l.nltJ) •fJ of" A.JciiMI'-1.. (ItS[ ; }.)o/Utlft<.. (Pdo1oJ 24-'5 ~'~ -roMo = -.£"- \}0 --T /. 57Jcs; I.1NG ~ Zlfo ~~ ~-:. ~ --9'5;1/;1 v;Q..IOJ/10') = :. _j c, ' ( /<.<; ~ /5.1 /<-'J.L cf~-+s) \ p ~ k. c~-S8 L</~;c78"J -::; [/0, s c7h-:. ~ ~ l?o'Jf ~;.,. :. / q. 0 /<.:.,' C'61rfU~ItJ6 :: -:.. 48 'j ~~ ( ,,. 4)) ~u'v ::. ~ (-~.?)'l-(4.;)(1tt.c.}{/9.aY - lo7. 3 lc. 3!<.. - 1~/<.;2 < Fb = 7+9 ~ Lcv-t-~ CALCULATION SHEET STONE&. WEBSTER ENGINEERING CORPORATION I.J.O./W.O./ CALCULA70N NO. 1saoo. os s-S:?~' I RIEVISI ON I PAlE &5010 61 PRIEPARIER /DATE 0 ' Lu ' ?.:. 77€7<, SU8.1ECT I TITLE Pe::AJS~C/c - -;c, A a 1 1 IREVIEWER/CMECI<ER./}?AT_E r lo/?dl llG d)()_({ "' , ! " ; g ; liNDEPENOENT REVIEWER/DATE J QA CATEGORY I COOE CLASS /7;,1.-;j S~ 5/Nf::T)JL-? ~ 5:;/"':t:'!C.It">V:-:..w ~_,._) I cr; :. .t..cNG. 1-Di::"ND 11>16 DvF.., I{ 1/VG>.S .... ilh?tl>'l rn.... (~ 4):-!M '>~s ... ,c ) --:_ /+oof 'S;~l:;r .,_ D~:(t:.t\..M•,JI:!f t:{f vI VII L. t;:;>J r s r;:ru-:. S' BJ ct;: -::. v o;-t.-o-; r;"""L ..j. c:r'- 2.. I • I 'tOO P t..oNG S'I!?UOIM'.. btJe J 'O.El~M !C i CfrSt-4/) I l (p9 -40 (1, ~~-~i~) 1l!vl""~ j'l: .0. X f 1\-( ~ l c-; ! c-._ I "A 1 Au.c-~J,..Slf I Cr;:s· \'1, Uo ·-----~--~-----··--------I . j 41·E I l I 671 /4.3 '!.2.1.?:. <f,7_ I 4 )...Jof{tvtPrL : ?.E>.'$' -,_ .e i zg,) 3 J, B I• <5 <.... i I I ! ' _)K_ I ~ILMP..<-I 44-.4 I 39,0 I ' + S'8<;>MIL I ?B· ') 11.3 ~24.3 4. z. ;, ~ 1 --4~1 I 2$,,5 3o,s 71-.9 kf,;_ ! i of<. ·----------I 5""5. f I r 48 .B I FMI!PG£/UW i 37-7 J(;.~ !:.3 2. J ( 4. ?._ -q, I 3-r 1 45.0 """7.4_ Q ' . ' ~ I I I f ( .a::...)~ Clk.. ·-----~~-~-" --~ .. '---·--~5',fp] 53''?- E:'~:(.Fp..rt J-.1'1 P..L 45:5 72.7 ~ 3&. 7 4-z. -II ~j 4 ,<{ : 52·4 i .;: ") ;:..J ;_ -I I i C5/<-. ,..,_.,,, .,.~,.-·-- ' I c:;;;oOf . [) E?C.Jl-ef)-5 t":> 5! t-J c.p-l'.IAX.3:!:. ~ ? I P!:? 5~ :ST/U; S 'S e CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULA/TION NO. JREVISION I PA8E ... so1o.61 /S"8oo, o g s-~ :?C 1-!C:. f.-o 4 to PREPARER ~ATE 1REVIEWER /CHECKER/ DATE 'INDEPENDENT REVIEWER /DATE 't>.\0.~-o~r~::R 7-so-8(;. ~)_0 l-/rc./87 sur=~~_;::~ ~ /...1-R...tls -r . Q.,A~ <: I QA CATEGORY I CODE CLASS = () /:\ 2~' tl rLI'tc£ R...., tJG S \..!:"' «+- ( fJ· 13) c.z.sy 3 71.Frb-J~ -=7 C),~k(~ (~7al\ ~3,D J /. t.lc. /~ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 45010.61 PREPARI!R~DATE D.w. 1-"oT:-.:;:;7 SUBJECT I TITLE r li)j <; "C)r .\:'. r J.O./W.O./ CALCULATION NO. 1 s-23oc. 0&' /s-~ 2(, r- I IRE VIEW. ER /CHECKER I DATE lo/?o/% ::00 {!-1 /1?-. I?! ID "'-/08 11 l'f (4J ..-,u a H rc,!+ R.!t.X;S W/'fH fJoR.f.Ah. 58 J$"' k /:: r 1--1~ ...... '='~ 714-o"" Cf 34o <. EicO..'flr':.trJtL (P, ~ a, Cf4 f-L~ o,sL. ~l -::o /.2?_ -UN~L o.54r<:.s:... 0,7/ !<:s ~ D.S<o ~o.sZ Ct_ 7. "2 )( o.s-.f. )( ~) '- ( 1·1'2.s-)l- I REVIll ON l PA81! /0 1-0 47 'INDEPENDENT REVIEWER/DATE 1 QA CATEGORY/ CODE CLASS I, I z. 0 ' "'[0 - STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .0.5010.61 I J.O./W.O./CALCULATj~N NO. !REVISION IPAGE 159oo log ;s-~.2C 1-/~I Q S PREPARER /DATE [),UJ, .Do"7"7(::c7t / I 'REVIEWER /CHECKER/ DATE . 'INDEPENDENT REVIEWER/DATE !of?a/81'. ~Ct ~ L I !)_ { 6 ,..? SU~.JECT /TITLE .:/ II.::J \"::_-z=:>(~ -T H?UJ ~ R r;..J0 ;- ( ~C\fefl.... R_\ AJC.. ,, f:} I L.,;)) ) Urrt:~M ,.Ji:! !2l=~c:rs. or ~AlGs of.J Pe-tJ•s7ack <-vfr'I...L It=-~ l:::lF R_tiiJ c -QlzSy&u) =-'I :€f.~ () c.-.. -n.J-1 (.. k It)~!."> s or: R.I;JcS -=-/,Jz<;/1 R= 9'rJ211 5{-4 --:c-:::- i' -0 ~ p LD OF P-=-B4-~ r'i~ f::__ -(!? 4.1J) c 5""-+) ~ :::: -t:::-jl' - ..f.c_ 0 45)( 5;'<{-) 0-=-2k ::.... 2_ (I') ;::: 0 ' 2.?. o ks._ P.= !oLar-;~ 'S"S, /;~~..· c;--2._ 7' 5" k;_ IQA CATEGORY I CODE CLASS r CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 4501061 J .J.O./W.O./CALCULATI~N NO. IREVISI ON I PA8E ls-8oo. 08 1 ~-S-:::2 ro I-I G. / o J. ~ PREPARER /DATE !),w. P~-r-7.~---p_ . / I IREVIEWER/CHECk~R/DAT~ !INDEPENDENT REVIEWER/DATE /()j?o/3G :!).') @_ _._I!; / 2/ SUB.JECT /TITLE / D , f::t) ~-.-,._;>c_}< -IQA CATEGORY I CODE CLASS ~ rp I ;~-'Jsr ,'.IN6 S. fH . , , / 9 -/, 125 (r J . ., d.. Hoc O.?o4 ?ft e: ~~Gi •(<t)" D.lof(b46t<C jj-/f_l )('7 i J,sof 0 («<J(!j J "-4 , 04 J I A-ct-\ /, ~ \V_s:N) ( 1 ?-/,1 2 ~(, J .·. \[6 0::0.78 r\U ~A~ IS~tW r=o-78 (_0 .I TJ.._I . 9 + /.s-~(1) \15d.c··: -=- -=:· / / . -G {1 o4J) ( -) ~P~orw •N =-I 11 -~ 2 4. 3 k"J~ ( -1-) /<.s L ~4-5" (_ 4 64 3) -5 33 B II :fi:_ ~ -=' b1o 0 Vo-=: &4Zo ( /41'-J -/8 C,{ it-/~ B4;/04-o ( ~4. 3) - J2, I - o--: -ks:_ LoAD ~ 24~+o (-;,. 8 2.) ""' S • 7 1~ s;'f-h-p,~ <:"11Ut-"':'> ... ~to C '·1) -1. cr \z5 ·"' I o 26 f<; (_ 102.% (~ 041) G /413 ,, I± Ho -=-0<to -:: /o 2-j{ (j4J '-) -22.50 t/~ \Jo -::_ 61o - -IDl.% / \ 38.7 ~s~ c-, ~4() l_ '-4. 3 _) ~ Lo.Ai) ::: /u"L%4o ("L.e,~ -4.5' Y:;_, 5~ s.~; -lcz?{4a(1.4~-=--2 · 2-ks ,___ - J .J.O./W.O./CALCULATI9N NO. . . !REVISION I PAlE STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .. 501061 PREPARER /DATE _b .(..u • ?,YT7t:71 !5"Boo, 08 Is-t;;.Q(:;!-IC:. l-6 9'> I I IREVIEWER/CHECXER./OATE !INDEPENDENT REVIEWER/DATE lonaJ?;r: JJ 0 E. .L I I~ I f?'7 IQA CATEGORY I CODE CL.ASS .Bc...o c.,t: _____ , ---- '~ ~ ...... _.. __ Lo,.;G ') I<J..v&; 8~NIJ!AJ6 I ""f /toof "7: z..) cp,.·-sliO ( f>'j. 4-'B) ( ,., ' 4'< ( f'9' 4'} -~ (tJ6~ 1_) c~ .• E ~ ALtt>w t0ai{.MA:L :s+. Cp 17·? I iLCo tp ~g " ) I -:.. 24. 3 '4~ 34-1 (p 17·] -710 'J4r C,. 38 ( V> I l ' 4<), Co '5""4. c; 4-s-, c.. ! 5'0 ·~ i E"1e-Rr;~ T'2. a ' I .::3z.1 : 7+.9 4:i( Co 2"2·8 -9-3 45'", c... 50.9 l ' / l EXC'a'TLo,Jftt_ 5$', f 27.') (p{o, z ~'5", I /I 4 (j) I ' = 3g·7 c;o s-s, 1 'J7,) l -/1.1-'5"5. f b/,5 ) I -·-·-·--------· IJ.::>-re · !JC: STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET 4501061 J J.O./W.O./ CALCUL,JION NO. .• I REVIS I ON I PA8E 1 <""8 oc , 08 / s; -~ :2 C, I-I C:, r-6 -; P,REPARER /"[)ATE b' '». 'l-'o(f".:-:-'R 'I . I IREt!WE_ R/CHI!:Cki!:R/DATE, . 'INDEPENDENT REVIEWER/DATE ;c::z3oft>G dJ o. B 1-.11;1 g! S~B.JECT /TITLE :..;cr..ls""'"Ocl::.. ~ -r-rtRJ J S 'I '"& '-Cl C/t.. )A.) lt!A)G i /08" i ! ! ~ ·. 2 \Jo-::. '2. ozf!t, f-_ /'7-bv~JUo-o) ~ ~ (?.8~(/o 5) = IS?. 8 !c. !52.8/c./ c--:. ~ ,__ / 9 ~ ~ ;;. I Z o ~<-~ ;_ E;_ N1 '<Y G (:;.r<J '::7 L Lb -:;-3' 76 "-/;,. P-=-~ (z vo)(t oo) - v-~ % ~ tcr9·Ycr ,.-. _1-A ?,· <:> t.u t:-v ,teN[I!tJc> -r-,; o - Y<. (5,7o)ltou)--= IQA CATEGORY I CODE CLASS ( -.d_ c.--.· 0 Lot.J-_ .,. . " 27, o !<-<;;L (P). 47) - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATI.9N NO. !REVIS I ON I PAGE .0.5010 61 PREPARER/DATE 'b_ U-J, ?t:>--:-:=--t SUBJECT I TITLE peN570ck - .-r- IO lj8oo, 02 Is-S(}G,/-/c;; /-6 :s-2.- /. .-IREVIEWER/CHECKER/OATE IINDEPENOENT REVIEWER/DATE I 0 jJo J~ ~ dJ () e 1 I :; I 2 7 JQA CATEGORY I CODE CLASS --;-;;7{-AJ;:; r R.t #& ) ( ~-Sii-Mvi..ftr ~=<;~ (~.->~ft ....J Jlf.O 1::.7)1/Uc.J/ Pi· 27t -::. '2 2, 9 / I 1m S"e:c..t>rJD~ s~~C'3 UJ/U-I:?<-77!N/) JtPP /4n<(Mit:P!.-y "/')\ ~ Lv/'0/I'JG, I tte r<.{ff")AU:: ICA:./ei\Jp "111 { 0-f'J f:jj Si!:"'~', ~7 ~-31 %,75-::. ?,f, ']!.< 5A-<1 j r CALCULATION SHEET .t.5010.6~ PREPAREFIIDATE 1::>, ·_.u. u:>_2P SUBJECT I TITLE \)IGnS"'"'::>~"'' ...... j::' R4rJ'\ ' ·-p...(flv, ( Lol'r() r,l';-&t: fAcf 6/IJ ( 14/D /:::.. )~ 1') STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O./CALCULATION NO. REVISION ) 5800. 08 ~-s c((o /-/(a ,_) REVIEWER I CHECKER I DATE ;:r o r;, 1-I r;;.J r; QA CATEGORY/ COOE CLASS .f£!:/511/1() =-'ffl!:M'llh_ -4 -) A~~-.£-=-lf.' '' i?..tv1~:£!J Tl-fltWsr Lo/W > '·', ).;LJrv ) 147 f<::-t -::. -= /8) . 56 ~ 707l ! .~ 'H ~~.•' ''fr) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION A501061 REVISION 0 PAGE 51 SUBJECT I TITLE QA CATEGORY I COOE CL.ASS P~('J cJ" •I ....... ____ _ CIR_(, " 1f' -i 1.£ ~ 'i ~/ ""' ' \ \ l / l\ 17t:/ '2.S I • ~. ( J</. $, 0"" I L/1-J II ;::criZ "5!/111 j? L! C .. -/"7 Ot=-C/H.. C L..JLA-1? (J"rJ .,1 .4-SS UNt£ '/7-11'17" tD )1:57?'</f/ A...l 17-l/5 Lc~ { 7/ir!. /l:ss o.Mf7,::tr.,J .IJ-t_s.o il~ 5T t:.P.1f) .5!/IJU p 7/f;W.rr '::Jt. 2 ~A""J't lf-N.,O 4 ft-(._71Jii·r.Ll ;J k s 1:.7JT "'7V #S { <,. T /7:J12 cc 5 ) ). 4·r"-li (:)•OGf% l > CALCULATION SHEET &5010.61 PREPARER /DATE ............._ r.-. _;' 'J..). ;<,--;/? SUEIJECT I TITLE P,;:~y._,.....,r' -/4 '<:: c / /7///// (SIMI Lft« -rD \ r) '"3 04 ' &:,4') r~\. -f}:-11 ) STONE & WEBSTER ENGINEERING CORPORATION IRE. VISION I PAGE -lc;~ :; 55" I REV. I EWER/ CHECKER/ DATE .11 a rs 1-/1?. / er-; I INDEPENDENT REVIEWER/DATE I QA CATEGORY I CODE CLASS rtuJC:> s PP M"<:. -:;;- 1...- :::,J'- s-:;.. -=. u Q~::~ )C d. ~L < k '-' <... (1··\(J/ ·,1.. l } ·t:i. ) -·6957 '" '~ ...... G ~ k C,/L 6 ,09 J'7c;.,X:, A,. ~~r)G)•7s-J -::. c...-:.. 6 .7.s" -b --I It Ck ( : ( e, (...lf'MpP,P.S I. ':'>V ·..w ~~-r .ZIJ ;::.., Y~ ~~~ " \ ( 3 -:p.7 s-)Wl_'j' -759;:>. ( 0 ,...,., ---") .... ~9 ) J \.3+-I·SGJ(,rt1'iiJ ) u\....: "'""'' f, ( 17 s 4-o " .::. ) l ( .· (..;~ = -·3 /-0•3)); .... 1Cf,4 4 ) - Jt:l:rJT)1 E' s~~: .>-)/!...{_ ~~5'!Vt:' u1~~ -rtt-c ~-sso IJF A c~'-'NDt.~''f~ _ ... ,_.:-,..J ("Doe t-.Jo._,. APFCc:1 '5 7~-::':it-r (? M•~?J Jor!'Jt'J As Cl>·u.vt.}tu) ;,..) lhtc.. /':;,""300/:B c r.::,:-)7C) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION PAGE J.D./W.O./CALCULATION NO. REVISION .501061 /~Boo . 03 1 ::;-5:"'/]-:; 1-Jr.:. It-0 50 P.!'fEPARERt_OATE QA CATEGORY/ CODE CLASS p r P t: Pr (f 4orsJ( sq'IJ o-.., ""' ,~.. -t... · .. / \ Pr .J.6r~·~ 1 rc; ·) c; -::: ~--:: Z.t -z. (1') r-~ --::;... 2-S" joe.~.:. :ss-I -~ ~ '2.0 's !::.~. cr-o; c-:: ":!' !1...5'" .... 8h~ :: z... -:::: + B=OI/!)6 -" ~.., ~ c/;. -=-~ ~:; ~ +-~~ = ~(1_1,3Y·-Q4.sj-3'L) i"(n)?- 4ux ~[, CALCULATION SHEET A5010 51 PREPARER ,(DATE ") I \ ;,__ W, ~~---c>::::P SUB.JECT I TITLE ~ -+-".:::.' -l ~ ';:"_) (f._ - ' II ,. ~ ' I -:./ .\ '·' ;/ il 1-o• r:.D + STONE & WEBSTER ENGINEERING CORPORATION J,O.IW.O.I CALCULATION NO. REVIS! ON !53 J::J , o! :S-5~ ~ I -..) QA CATEGORY I CODE CLASS II I --I ~'--' K « ST7FFel.ltx~ :, ~z2i2-• / l 73l k ) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./ CALCULAJION NO. IREVISI ON I PAGE 45010.61 PREPARER /~TE :::,, '_,_), ~) T-r-~p SUBJECT I TITLE /itJf) LVL.LJ) 2 WI '17-1 A wtr?t 4 =;> c:r-~ '->56'" C2) ts8oo.o8 j.s-S::<__(o!-/(_c;, ft 6 ·::--.3 ! REVIEWER/CHECKER/DATE I !INDEPENDENT REVIEWER/DATE 'J':CJ(2., :1-/1~ 37 I QA CATEGORY I CODE CLASS \ (...6 Llft~S u-,d,-) I Lo/\-D --; ~ ), (p ~ ~;( .,_ 0 ,OG'S ,:,/::, ~ '- (o 4rt ~ LJA-:--c~, 5101' $'i)C ·:._:. .: 21. G !:-s;_ / .._ ~ '-.ijhl_s . --· ---·~ r-4s-l<.:.t. (' 1-::: .!:> " { C.OCP-c ' -f~ ~.? ) / OK_ - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULA"?ON NO. IREVISI ON I PA8f! Js-8c:::o, oSI ~-s;. ra I >'"I 6 P.. o 59 IRlVIEW.ER./CHECkER Z/DATE 'INDEPENDENT REVIEWER /DATE 7-?.,ZC, rll O, fl.. J_. t;J/6? SUIHECT I TITLE /Jr~ SIDC~ -s 'l7?e?_ G 1\} t!::;Y< Dt="/..t /1 r IQA CATEGORY I CODE CLASS - l...ltJ€0 ~D Is oervevtu....7 AJo-r JoFLvli?NCRO Sf1if::;r.... L I,.; t;;'l{_ y-:: Or30 l(_-::: 5 '-G:, II::: lO {p u t-=.. (!) I 5'75. If ::: ?r-o. !~3 (c/:A -3 Co . ( CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./ CALCULATION NO. ' . IREVISI ON I P~8E- .0.5010.61 / 50oo, C) e Is-S.)CJJ-/0 It 0 /,::; ") PREPARER /~TE ~, c..u. r l>7{t7t IRtVI EWER/ CHECkER/ DATE I INDEPENDENT REV I EWER /DATE 7-7-8~ -:Y l1-'3 ~ /rJ. 187 SUB~ECT /TITLE 1-'l,:'j'J )"''"""'JC...l:: - LtAI~ J D~T~IIA!...JE lOAb ON :51\J.O.) 1\ssvltl[ J "-llT1 f\L Gf\P =-o.os% oF MD' u~ = o.o.s--6 (eec:) -=-0.033" F'oR. #J! 1.JL A3 Fa "Z. <;"' ~-:s-~ 1ftoL E ;3 o J Vo J fr --2(33z.1 ooo)(__t!>,?..(_1J L APffl..c-f.. ) I ) /.4 ; L/ I t}thJC I . I ::. CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION REVISION 45010,61 = :. 6 QA CATEGORY I CODE CLASS L'~~l) , -::-) 3 0:'1 xrD 6 fn )( c:;,;-s) 1'2 ( 1-.. ~ , sY·) 'j -\ Q -jA ('2 D A)_) ~ lo l7 df./~ \ (9. o3/' )( 2 x /4o 1 o4s x (__ o ,z;2>-;, ) = Q I~ 1/ ,, fl1~eDI/\b.Jf YitbPQ17Z or. )c: · ~ ~_, bA-r p I o or= '2 I ( /JIDIJ \...,q )/<I) J CALCULATION SHEET &501061 SUB.IECT I TITLE ~. I I li)l/8G:. '' ' /" C,y-vc~:~ ' <. I j I J ~: _, j-l, ,___. \ ll----------------' Z_" ""' \ \ I __ LJ ' ,.___ / / /lj l i (/ / _______, ~ "'-,. '\. \ \ ) REVISION 0 QA CATEGORY I CODE CLASS ~~ CALCULATION SHEET &5010 61 P~PARIR /Df%-.,E D. uJ, 'r-'oTTtY 7-3'o -e<o SUB;\ECT I TITL.E ......,..- /"t;l\JS17!1 C!~ /;~RAJ C,-r \ v STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./ CALCULA)ION NO. REVIll ON I PA~~ -;'J ISSoo, o.g 1 S-SJGI -/b A c ~_:;;, !REVIEWER /CHICKIR /DAT/E IINDIPINDENT REVIIWIR /DATI ::tJ ~ .e j_ / /;} g 7 QA CATEGORY I CODE CLASS I --+1--------~t- -- J I / I ' I I J ' \ -----\ _L CALCULATION SHEET .0.5010.61 P~EPAR£R /~TE .L> I w • r ()"l'""n 7-3o-8<;, ~· ) STONE & WEBSTER ENGINEERING CORPORATION REVISION 0 QA CATEGORY I CODE CLASS I I CALCULATION SHEET &5010.61 PREPARER /DATE b. 'J.J • ?~ ~~t.? SUB.IECT I TITLE ~P..r.J.'c.r,, ·" STONE & WEBSTER ENGINEERING CORPORATION 1 "·?·/W.O./ CALCULAT~ON NO. IREVISI ON I PA8E - ~s-sco . o 3 .· s-~d<'o/-J;:, A ~ ~ 5 IREVI EWER /CHECKER/ DATE I INDEPENDENT REV I EWER /DATE .JJ cu~ 1-1 tJ .. l e? I QA CATEGORY I CODE CLASS I • Vz. ~ .-·;71/ (_ ~/-~/ // r-----+ ----=----" ========~!==========~=--~·-~~-=-=-·=-=· t -<:-~ ) II ------J\ I \ ~========~! ==========- I ~ i I I ! ~------~-- ~ - r_ I cf1 I ~~ - i -~ 1--+ I I __,• , ~-~ ;:::::=; -< ........ !-< I i lr- I ' I I ' c'-(:o,u I -~- I I I I i I ' I I I I I ] l 3 ,_?" 111/') C ryp e71{)1 010) i \ -- t" ) CALCULATION SHEET •SOlO 61 PREPARERI~~E _ "D. {_)..) , 1-'c-rrr:-f.< SUBoiECT I TITLE ;v ,..._:::.:--_ ! --..:::::.; j 0! ! 7·'30-8(. R~ J& STONE & WEBSTER ENGINEERING CORPORATION oi.O./W.O./CALCULAT ON NO. REVISION t5:8oo. a a :; -J".2r;; 1-1~ A o PAGE / / (a(p QA CATEGORY I CODE CLASS -------------~==a / )Y" I 1/ {--:: ULATION SHEET QA CATEGORY I COD£ CLASS t\ssoMt;-: /. Lt,AJ6f;tJI11.-Jitr... U1t1PIWSSI~ ~ 3' I k' l (CALl. .J/;.;;BCJ0-55-2~/·lfol+p, I 13) 5'. :Z. f.JeGUec:r MlhJC.Tt.l:.,.l IN ~PIA!I~Lo.tJ/k. sm.t':o Dv;; "10 77<.AIJ:st~FN/ '-4;JO/A.f6 EMCJZC.t;;J+J'1 = 45. 9+ It-s~ ~ '( u:Prw~>~lrt. = 5? · tS 4 J..-s;. -r1+t;-Q,vt,lh. s~s: ,s "2.2-o -rl:MP c.~') e-""'~'ri...C::fi'J"1 ~kC~P?"'-o..Ufh. 0 ~1'~-s:. ~11..1 € • 4, 't l<s ,· { ~ t:..+c.e I {I;oo-SS' • 2'-1-1 6A, ;; . 22) 3"3.2.8 Jt.sL 14,'! I' 4-,...,~ 53. c+ k:sl ''· '•· ----~-.......... ----......_,_..._-,...,;.·,--...:-.-~~----·--'-,~-·:-:.-";..:.-:.. __ ._..:_.__.:,__...._. ___________ _ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 PREPAIU!It/~TE I"" IREVIIWU/CHICKEit lOtTIE /,' IINOEPINOENT REVIIWIR/DATE ~n~·~W~.~~~~~l!~~~~~~-·,~l1~~~8~7~~~~·~~~·-~~L~l~~~~~Z~n~2~W!~S~--~-~==~~~~--~; SUB>IECT I TITLE IQA CATEGORY I CODE CLASS ?~ ~ 10 c.~ ,.-l41iU.>!>,.. a (..0 c..t AssoNg : S". 1. LoNGtrullt -"'lk.. ~Pil6S to,u ;;: 3 , I k, t. ( CA"' "'/.;;Boo -ss-'2" 1-lfo/tf?. J3) :Z • />J~ Ml)cx.:n.ob...S IN '-lr7ttPUZ~U:.l.Nik.. .smt-:0 Ou(i "10 77tAJ..)SIIFN1" '-"1\?/1116 THIWJT SC.Od: '7'0 li!l.DAJtiA'f'V "TJJE..!e8y 141(Juo;l(; CtJ,.>.~~'IIJ~ fTiC'IB'S J £.Mr;JJ.C:.t:JU'7 :: 45. 9-1-~si. '=~'i::Prw~Nirt. : 5?. c:s 4 ~s~ 1\!I~OIVI.E T1+t;'"Qt4"1Jlh. S~,S;' fS Cr.:.a.. 1.'2-0 'T'!!MP C/~) f\L\...0-UJ~ \..\; s. ~::.nu· : f: "'f "-'ta..fCN"-f ~lc CC::'f'( '-OA! A-t P1· 1<..) Cdwtf'ILir"-t ,., u € • 4 I 't ,.._H. ((~Ad: cA-L~ /.faoo-r;). ze. 1-1 hA I ,. zz) 3 3. 2--ZS J..sL 4~·'4 ,.. .. ~ ?3. C <4-l:s\ \' ---·· ------~-_ _._.;;,.~~- CALCULATION SHEET N.o~'s ------~-·-·· ------.-.-. --------~· QA CATEGORY I CODE CLASS .... M<&.--··-------. o;:· ti3.ti),. ... (-7.1)(s?·'-b)., (7·3)t. = 37.4" {<.~ ~ CA ~ '8-i·~4)1-(-7.7)(4-s.,~)-JQ1 -4 8 J.:.s,;:_ r~:: ea ;...,.;, c._ _f4 :::-5'{ .OlfkS.r: ----~----------------.~------~--~_.------~·~~._ __ ._~·~~· -~~~~~----~~~~~~---~~~~--~·----------~---- I ;boo, o9/s-S' 2t;./ ~t& ~-r-rf'rt.4l. A i TABL.& XIII.-FOB.IIoiULAa roa STuasu A-ND D~~:roB.IIoiA.TION8 lN PRIC8SUIUII VzasELtL-(Continud) '\· •;'\. ·- Atpalalo011i-w "'-at. (,....;.); ... • [I -1.1(i)' }•': tt' • ;'[ 0.421oc-!!]. ..n..n,6-0.215 +o..s[' ;']I ,...--:;_;- 0 ~ At paialo OD looclod .......,._ (r uio): ,., • Ill • -/[ 0.421oc-0•2!511 ] . M , -P[042 ,_ 0.215R + 6•] lood u.-. -p . -...-,-4"; at. M.u ... • ::!.[o.42 -~ + .!.] "'''*' " . . .. At pa~a~a 011looclod el-*.l'llllilldisplooemeat--C0·1~1;!!)c..,·ll-~:< + .U.~:<l • ..n..n."-o.aiu· Mu.l'lldill ~ • -O.I3.!PR' ot.lood; clwlce in~ for oqual..,.j oppaoile loodo • -0.%1 PR' u u :;.. .... (Rer.2 ~ ~~ > Z!Cl /' ~ ell ..., M.u ,.• • (M.u ,.• lcrlood ..-U.. eodl (0~) 1 (wboa • > O::R. lood may be -'dored ,_. r~ eod) S ;; Mutt' • (Mutt' forlood """""'''-ODd) c:!~) I (•heft • + b > o.7R. 1...t may bo ......idcred ..-from eod.) (1\J. 2~ : Cylindri<al Rodlal diapla.oement atl...t • -:J:,fll[ 0.48 -0.22 (j) 0 "] (wbeu • > 2R. lood ID&1 bo c:oaoiderod. ..-f.-eodl ~ =<!: -----------1-~--~----l--------------~----~~------------------------~) ~ 8. UaiiC11111 ndial _.,.. p -3p ell o1 p lb. per 1'-ia. o1 M.u M • ij; atlood; Mu,.•-;;;;; .._, cin:umf-..... ~ M. • (Mu J()[.-"•(-A%-Ilia A%)] ::; I £B R.odia! dioplacemeat --pH'). :I.E I Mu.. hoop-" • ~HA at 1...t (Rer.3) =<:: ~ ~ > .., I ----------~-------------1-----------------------------------------··-------------------- 19. Uai1C11111, ia......., (cr ... , Mo-OJ04•Rt( A -<t ) , ::"!'i. ir:.-"" of p lb. , A + !..561 Viii (Jt, • OJ04pRIIor ricld riDe or diatl -!.. '- .,.;. I Vo • O.iSp.Jiii( '4 -d ) (l'o • O.'lSpVJii for ricid rlnc or diak) -.-'v ~ ~---~. as : -~+1..561V/ii ":- ' , 6Jio . • . ! Mu.lonc. bead•n&...,. • -1,-a\ od&e ol ""C· Furmul .. lor c._ 10 omd II may be .-1 to fiDd M,, n' and f • at otber •••11o01. \.."Jilad.rlcol. .nth rt!inlor<Jnc riDe ol ~oual ......... 1 Rin« ,_..,""'linear lo. olci ... mi ....... _ zv~ Tbe above lormulu ...., valid if rincs .,. spac.d .. lar apart that lbc inll.,nce ol uoe 00.. not ex!.ead lo lbc ,, .. f.. Tbd IIP"Cill& 5 ~· Tbo...., ol tbo dim:l and beadincloncitudinal-., + ,. . .........U lbc oorm>l hoop......,., uol,.lbc ru.c si!>clnc < ~ ,;Ri (Rei•. (. 5) .41 .. - ----------~10-Unifonn radial s~,.., "" ~t',lb.f'ICI'linmf' tn. of cireum(cre.uce at. tnd r.. ~;-6,~f; Mu ••' • 1.9~t V•; n' '*-f Cy\mJnc:al tl..oH~J r uiform ,...ii.al moment .\I o iu.-lh. tn· hnA~r in. ol cm:uwft-rt·ncc at t.'t:ld Hoop st..,.." • ~(>JI.-J.•..., )..r); ~~ .. ., • - 21 \R atead I t ll.adiaid' pi -v, -r. " &ccme~~t -2i»:i ~ • 2DJ.• Mu 11 • 2·:1'1.'11 at ODd _______ . .J ______ __._ _______________________ __ ou.r •.• 1. e1 ---:>; ell I? l""" I ( \ ctu.. t58oo,os Is-5..2.0/ -t6 ~--........ ----.... --· .. N-U--HIETURN ~HITIE COPY. FORWARD WHIT£ ANO PINK COPIES. RETAIN PI~K COPY FOR FILE. · INTEROFFICE CORRESPONDENCE TO: Bill Sherman FROM: Jay Hron MESSAGE:- cc: 0 0 0 1 LOCAnON SUBJECT I REFERENCE I J.O. NO. lANe 1 LOCATION Penstock Thrust Loads IANC Critikos Bishop Duncan 0 0 0 Hron Hughes Blanchette 0 0 0 15800.08 WPk 26C • -1. b Sherman Val lens Please find enclosed two sketches showing the penstock thrust loads. These are the external forces from the penstock into the concrete calculafed for normal design, emergency and exceptional condi~tions. Prt-T~tle4 i#Jt-~ IJ01 b~tG-J fOe. ~y-toJ 1!t-L @..J)qj~ {T( oJs. 11{E ~Mls ~ s~~t-1 I 5-() THE:-s;;:~~e:-S. 4t.J ~6 ~t..€1J • I ' · 21-Apr-86 Jay Hron ll{J Ext.39 DATE SIGNAl{J E TELEPHONE REPLY: ---. --~' ., • 0<40. 138 OATE SIGNATUfiE TELEPHONE • I ··-----------.. ----·---------·----·---······ · ....• ···. . . ... · ..• rt .• ... . .... !' '' 1 '· ' t·.· ! • '· ,,. ; -1 ~ i ' \· '. ~ ... i- ': I. '. i·' !·· -- \ .... :..-:--· '· . r I ... .. . ., 1&1 1: :::l ..J o&l w .... :I j ... ~ . ·-L . ~~. ~ ~~~·~~- l .. ' .. ;., ..... t =-~: ~~ , .. : .. : :-, ,·. 1: I· • t ._; ; .. ·• !-; !; ·. ' , . . •.. i . ;; ; . • II .. ' t••• I·' i~ f· ... ::' (. f· ,. ' r •. I i ... l.·· ; . ·-~--..........---,~-~---:--~------:-:-'--.. ·-·--~-·-------------~-------------~---:- ,..._~ ~ ·t... '!-""' 't... ·~ ~ -~~~s ;~~s ~~-~~c SENDER -RETAIN YELLOW C:OPY. FORWARD WHITE AND PINK COPIES. : ....... R~UER -RETURN WHITE C:OPY. ·· .. ,-. • RETAIN PINK COPY FOR FILE. -· --·--------------·----------~~-.:_ -·---;-y· ----·- 1'1(1J+(/.I-G:r_ INTEROFFICE CORRESPONDENCE -~------------~~~~~~~-------~ j LOCAnON SUBJECT I REFERENCE I J.O. NO. TO: B Sberman/L Duncan ) II ) I !.u.-. ~-----------------------------------~~,N~L~~~Tunnel and Penstock I LOCAnON Revised Thrust Loads IAhl,. FROM:R Dulin MESSAGE:- 15800.08 Wpk 06F Wpk 26C- cc:·O Bishop 0 Critikos 0 Hron 0 Potter 0 Finnimore -17 • Per Jay ..Hron' s IOC Dated 9/J:e/86, the normal transient pressure bas . REDUCED ·from 715 psi to 637 psi. The following loads have been reduced: Fl = 5835 kips F2+F3 = 3044 kips F4 = 2882 kips F5 = F6 = 8805 kips Resultant = 5879 kips F7 = FS. = 3076 kips Resultant = 1~10 kips 6.5 foot BEND .. The change only effects forces by normal transient pressure. The emergency and extreme emergency forces remain the same. . . .. REPLY: HOT!D SEP 18 1986 J. HION 18-Sep-86 DATE DATE ... 040.138 -. ~ .,::-.·. ;.. -~ R Dulin )'t'O Ext.38 SIGNATURE TELEPHONE .-.~ -· -~----:.~~ SIGNATURE TELEPHONE --·-··----~----·-·-· -----~ i. !.. _() ' ') t . r ' •' ~ ,Q i ll .;. od ~ !I ~~t~ If ,; If l t I ~~I \ .... ri .. _, .. .; t ... • .. ~~ I I I I I ~ ~ t/~ ~ .... :1~ It i! z: fj ltJ I f I ~1 r t ... . 6.• . I I j I ... ., ..... .JT l I~ ...,. ....... + ll~ ,j\ ~ l ... ... t L~t~ ·""~ .. ···T I~ ,~ ..... -.. ,JT ~~ -r I I '"""<IOL•""T c I I ~.1 ............. T ....... I ' " u t .J .> .. q .. s g .. &~§h io~l'i-... '~' ! d~~·;!:1 ". . "' ~ ~:!t'"~ t--L ~,!. \ .1~ .. .. ~tT u~~~! . "' ~~~r 1-H r • "I: ~~~!~ i: .II . . rs~~~ II . ~ I. 1 0 ~ ,. -z:- :t::l'lll ~~ {~gj I I H._ \. ::-~ ... t;.! ';! ........ \ .... .. ..., bl ........ f .. Ill ,"! r. ·-(\ w..l :J ..J _J ~ uJ z. uJ \-'~ ~ ~i ~ •.. ~1:~ 41 :· !f c :. J I i ..u ·~"l.J ~Q " \} ,. .. ., a ~ r. \11 _j __ ll.. -u. () ~ tL. t fJr::::f.I:STCJC',(./5 f/faetL-IfL VIILIJE /JM'lt.-YS/5 /)/S C V"P 5/ t";v v T. U IT7K (7J ]) ~167V rerz. 51 n, {/ '-771-I'V€<710- ________ Cf!!JIY~!f!._ /}1/1-~1/9'- g C?f? BZA-7?P?V ?tF" t/ /!t..vt: 'J) f/e:::-{C) ~ ~~~ -'"~----/ -~··· ---··· Ei? f.,t,/_lt..-t::: _____ !../]{!IL~~--5"/ft/T.])~~"'!! __ _pf V/1/// ~ C/L.OS//1/c.. dF -----~---·----~ ----~· --~~~ Wc;/6--HTOF -w-;in:k .. -- =""'-----"'-L:.-t-Pin'L.,_P--f.-.4-7-<:::-s-~----- l'a£..1??// L'}r:Befft- -______ -~_----.. ___ ;;:--~=-r-_k-_= ___ ~ ~-~-~-_= ___ = __ ....... ___ -__ -___ -_ ~mw::e:~------------· --~po6.¥V]>;977t?v -----------~----C,:i:i42.iZ/E:>--vez_r?c;9<--· ------------------WBG--/TT--£--/4jv£:.tt~---F~<;~ _ -----------·---------- ·-------------·----~---- J/VIZ lA/& ~ c:q~/77/c ,) ~ V&-Z~AL / /.,(/G76-HT oF VAL t/E .£ 8.])J?9CE=?VT P~~ct::_ -CJ~f!f/ZIZIG7) 8~ V/9-LI/E pi:>.N; u PH W'.4~J PI?N~TP'a -rzetS'JC.P et VII-1--1/E t-P/1/.. (g PH -/ltL/avcK 0) J L~t-TE)z../?L !>IE?Smtc jA//!?YZ7119 t?F .f!L 1/1'9-Lvt: tvE?&Iff &. t#/fTFIZ-wt:/67-fT -tzBJSTEJ) gy fo'ev~tA/~ /A/ j>ev.>JZ;ct 1 ) -ll~vme PtyfE]:> ·vj!? oP PI-I t.¥/9-L-L · tfj Ve'YLTI "'f-1...-~~rt-T7ew' PN tvE/6-H-7$ (;/1/c/Z~€" ~ J>t:Ctzli9PSE ~P"_e:tT/1/t:: WGr(~H-iJ _ ·1----------------.. -. __ !:5) V.A-t.._'!~ ___ tJ(/_~lJ~& __ E_~~-~~?.?i_0/1./__ P-1 "f-Nc.ife;fe> A!VP Pt::~TE/1/TI/IL TZ>IZ.5/v/V/k_ ~ IN .:Tifti:J'ff'l ON P-£1V5"c/~ ~/Ill? B/'1"CJC. ~ T7"/7el/5/ a/#? . .. /-/1 ---·-····--· ........ --··· . T1172v> r .Pvc TO W/i~ _l'/Zf?'SVd~_. 0/ll V/1-L.Vt: w) -ckfZILI 8 IN 7E?I/flt?IV § 19&~ fC .. J'.~t:K. 7/r/f!.t(ST ,<e / ..VC... 7) I NJ"l:;)Z/1,/,11-t, ...v/llat.-i'J?e?~fAlE-/-tl7Pt7 ~~.J ......, ~ ~ /..011/6-tTc//).1'/V-'1£. .__,~ ~ '¢-"? /3 BVJ:'(NF-.>r;e ~ :!> _ ... . _ _ ~~ ...... --\..... LOAIG-1TV1>/.N~L.. ~5/Qt.- 5T12~5 ,&:,12g;n.. 7'7nf?IIST J.pA/6-JTVf)IIV,i/ L srrze.s- Tlf7Z11$T+ BBfF})./41& II t ..... ~ 1G~ JJ=f'.F:cuP J'J? Zt T inJ----------------· -----------~-----------------·- --------.-----· STONE t. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE .._5010.64 fFRONTl CLIENT S. PROJECT ALAS I< A p o wr;-R A-u l(+o /?.I rr-ls/CAJLI:" t" u.tKG CA LCU LAT I 0 N Tl TLE (lndicat i ve of the Objective): 171!: f\.Gt3..W ~~i,) /1-IICK 1/t'~ CYF S'7'1N~ (. LI~R. (jiiDT-~ I A/Tf:' R NttL. fl. l?KTCR.N-tc.. ?N~tJicfi CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. DIVISION 6. GROUP CALC. NO. TASK CODE I sa-oo ...s S261-17/t *APPROVALS-SIGNATURE E. DATE REV. NO. OR NEW PAGE I OF -4:$ QA CATEGORY (v') 0 I-NUCLEAR SAFETY RELATED OII om cr-ll (l>k. OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED (\I) REVIEWER(S)/DATE (S) INDEPENDENT PREPARER (S)/DATE (S) REV I EWER(S)/ DATE(S) CALC NO. OR REV. NO. YES NO c. T ;t. A)~ p __ ~- 0 ...,/ 9-2.S-~ f. lhlft PP..Akfrs I+ - lj:Lo/Kb r.T~ ~r;·~ P, ..... -) 0 v' -IZ-?..-':l7 4ut 7 ~I<A~.t.ASt.-1 ,:z. I" /-r1 i DISTRIBUTION* I : COPY I I COPY GROUP I NAME t. LOCATION SENT GROUP I NAME 6. LOCATION I SENT I I <v? I I (v') RECORDS MGT. I Job €o (\/4 I v I I FILES(OR FIRE I I I I FILE IF NONE) I c I ;?.A:: ,:;, L € I .......... I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! l I 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 37 38 39 40 41 42 43 44 45 46 .1.5010 65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. /:>ttft>l> DIVISION & GROUP s CALCULATION NO. OPTIONAL TASK CODE s;;;{.t-J7A ~1/.f I. TITLE i>AiJG 2. TA/3LJ; c/F CoiJT!?/JTs ZC\. R'EII/~IfJN J7i177.J) Tltf!lE .3. CALcuunotJ SuJ--tJ..tA-RY 4 S" 6 7 8 OBJI?crt ~ f1"'F CALCULA'TJDN CltLC.()l/t'Tio£1 1'-ll?"rhll ~ /tdJUM/TIUA/S Rt::~t~ llll?.s (ONCLtJJio#./.S ,4-U..OI.Jif./!lt; srRrss rTF S 71?'1? L Lll~ /'-'1.A /t"{(r lh: f.:>Ro p7:-R71G! df= COJ.I C~-r,le J:::.G-.J{6JJ j 1(11:1{>/V k(_ f>/li:.S.SiJ j>E ])[;111.,.; l?>t7/?ttlfiA L '?NC"S!fl~/; CA-lcu tArtotJ ;;}; l?tJ c)(, 8·1 I(BSJ()/I{e~ £..;~ 7/ftc~AJI;JS OF' .sm;:L .1../,1.,/'l:'R u.v/Jl?~ [7ft: ~~411\t.. ?Al?Jlll ~~~ S·Z R{;(!/;WIIf?'d /.JftU.. 7/ftc~n t/F ST'l!t'--l.. LIJ./CR tJNOtt~ 171E ~I.JIItt_ "?1?&-!.kJI~G PAGE~ I 7 a -12a.... )2-ZC::: ..2/-40 <f./ / ! REVISION STATUS TABLE PAGE NO. ? Cl.__. CALCULATION NO. s.s 2.'1 -I 7A , tc:.v-A JOB ORDER NO. I S8 f/O REV PAGE REASON REVISION/DATE NON-INDEPENDENT INDEPENDENT APPROVAL/DATE NO. NQ REVIEWER I DATE REVIEWER I DATE 0 lflL ORJl;I#IK. - I Al>b f{{?VJJJ6N r://ITU I TArMt: c.r.:;t. ;z.~ 1-'/ ~-~ F-r --:2t:::L 71/15 '/lAGTi ( M:·w) l:t/ 3/tJ s-Tile <' HA~C 1-J G60Tr-cll vE fJ(;..J CRtlVI?/'1 !=61?. Tl(l: Fl. A )1J c. 14 (JIJvLl/) fiF tro tk_ • /o-/2A JJ en; 70 rtu: <QJ NJ6 r-1 ,..rrllt: 12-JS 6c:~cii.JvJit\N Clttfl!'tt4 ftCpl-ffC Tift dlO ~4r)G! :l c. .I /liE' C/./IM/l,l: /N 711 f.' /?C(]Jflllt:L. -1-f 7/ffU!Jtr.J cp s;r:t:L /..111$~ I I -, --·-- CALCULATION SUMMARY STONE & WEBSTER ENGINEERING CORPORATION A50!0 62 1 .1.0./W. D./CALCULATION NO. /'Sa="t>ll-S-S::z~l-174 REVISION 0 I PA8E -t:::sr" .J CLIENT /PROJECT OA CATI!80RY /CODE CLASS ALASkA Mwl?R Au7Hifli1' -[)/(,4DLt''l LAi(€ wM SUB.JI!CT /TITLE IJ./12 tri:~J.JittC:d 71hcK~!t; FaA JTFc-t_ Ltlv'PR Ulh)CA If/11:/UI-Yt... AND OI.JI!CTIVI! OF CALCULATION lc> CALCULATE: Tift; /(t;CIUI!Uib 77flcl(NC'-:SS HJI( .J]l:tX l...t;vr·f? (!=ROHL-1 70 L-7:>) J==ft..O H '711C: CogJ t67?~A-.,..,{).A/ t:fF: :::t:Nr't:/eNif't ';/ .l;l( rl:?~ !VIM... plelH.J VltfS • CALCULATION MITHOD/ASSUMPTIONS l't'IE OJ;Rtv;t7t->1'1J CSH'InJ 1..J i?~F. ~ <(.J JttU: ()!t;:'b 70 CALCt.H.I97t: /1f1;:" i(~iJI/'?t~ 71/lt:KJ./t..fl UNDGI( THE /NTGI?NAt... ""ftr&-S!"HE-. ~t:;F. 4 ~r A Rf: FO.R: C:X1T?RII/Itt-'PRl?.J.JVIi'E. nt£ t;F{C'CT ;::.J:.ol'-1 SurM.ovwd Coi./Cif:Tl: ~ ~tJcK, IS CoNJiu'F/fL-~. 1/lt: :J:JETAII..f:jj 1'R0Cli-IJCI~£ IS CStvt;JI.IA 7Hiii S~TiaJJ ~ CA-L~CJLAi1oJ, SOURCES Of DATA/IlOUATIONI - I. SmL L/1'11?~ ;u/b '"PEAJ.s:rock' Sllvrrut4L 7>t;"J'/6/J C~t7l?fttt1 Pit:. ALA rlr:A po~A~ri: AG~Tifdi/11', 'tlt.I\OU Y L11/(l" J..l'lllRaGu:c il?tC '"Jl~~ fJReJCCT 2 '-"RO~CI( PRof)l:~T!tS ANll S.Tf:("...f.. T7NJ~<. .Lt/1/1?/?S' qy ($.H. /(~rJSE, AJc~ p;1Juc 14 ''J"I ::;-, r/F -:rnf '}oWl:"( JJNWON • Vo '-· ~' • NO. -p 03. , ]T;.;t: 1 ~ 7 0 ~. ('RE.SSURE: lf~7'~1 fWT'toiJ JIJ S7'fH -LtV!lD Roc~ 7vN#r.U AN'i) S'HA'F/s' 11r .s J"f!c"'e.f7?,v, t.JA1l?~ }lOwt.>l( ~ ..DAM CDIJl~IJCTtlll'o.J , §l!C. t ~"'7 <f. 1 /Jvc t I..IIJ(, OF" 7-'Rt'SSUJt€ -..s;tAPT A.vi> TUul./1.!(. J../Qul'-5. "IJY E'. AM.S77.il:l-..-W!477:{ 'j::cWPR , 1-foY. 19'7o S 'ST!f!.:.£ /..)ptl{t,S FOP!. H'(DI?OTvi141C'<.S: 'AY .S. vA C'oSE'N, "-'An"~ f.:>()illr-1?, <l-D.W CqNJ.,.!i:rJ(n6111, :TtJvt; ~~~1 t .S.t-w.D.J~. ~IS~ -F=-S-S261A-1 IS~!Jo-F.J --.!26!11-L l~e!SU-F'.I-SU,lA-1 1~-;-s-setel!-1 CONCLUSIONS r Rf()J.tJ.~C>;.tiJr;j £N'Itu. T/llc.k.I.Jl-0 f6J? J"Tr-t:L '-'~'( 1!. (J,vr:-J o;.J f!: ~u -RIVII!WER (S l CO MilliE NTS REVIEWER /CHECK!fiR M"""'i \L,. .....--...... DATI! I /}~u 't/ INDIEPI!NDI!NT RI!VIEWI!R DATI! 2 3 4 5 6 1 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 65010 65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. I DIVISION & GROUP lst?rJb s CALCULATION NO. OPTIONAL TASK CODE J2.6.1-17A 4 ALLOWABLE STRESS -ASTH 1710, GRADE A, C3 (with material properties as given herein) Minimum Ultimate Minimum Material Tensile Yield Thickness Strength Strength ~in.} ~2Si} !2si) To 1-1/4 100,000 90,000 Over 1-1/4 to 2, incl. 85,000 75,000 Over 2 to 4, incl. 75,000 65,000 Governing Allowable Stress ~2sil Normal Emergency Condition Condition 40,000 66,600 34,000 56,610 30,000 49,950 PAGE.:!::_ 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 :H 38 39 40 41 42 43 44 45 46 .A.5010 65 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION f) GROUP I CALCULATION NO. OPTIONAL TASK CODE I s<ftS-u S S2&1-!7A S. jvlAT"FI(.tJt.'-. ?/Copl?tti'lc~S dF Ccwcpr;re: ~ 7(ocl( PI{ oM P. 8-S -rz. CF RFF. .1 • a) CD/1/cRI:"!'F : )J = 0.2 v =-o. 2:7 I, ' r PAGE..!!__ 1£ ~~ l 2 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 2! 24 25 26 27 28 29 !0 3 I 32 33 34 35 !6 37 38 39 40 41 42 43 44 45 46 &5010 65 STONE B. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION & GROUP I CALCULATION NO. !OPTIONAL TASK CODE PAGEL I s-<:.f'rt"o 6. S S-2 61--1'74 'bi:St6tJ JJJTP(N*C... 7?;u::nv-tt: THE FaLLOWJ#4 ??ti!L£ /S FRo~ (A-hl.li BS-2 d/=' Rl:F. 1. INTERNAL PRESSURE AT CENTERLINE (PSI) -ll-l(lt X~ Power -r-Normal Condition Emergency Exceptional JtY Dr o Conduit Members Condition Condition l1:'T Penstock At 845 1020 and Turbine Manifold Inlet Steel L-1 Liner through L-30 Steel L-31 Liner through L-71- ~ Jtt:'Ft: fit EAI J I'll, /0 s ... k..l l) w1, ' =6 I~ -F.s. -161 A -1 Fe~ LIN£ J'L;:'(i kt'IH' }.10, ~ H YtJ~O -rtr.rr /.J /ft;tJIJIIf.c ~ ~I( i. 7 o Tu L 7~ AA.ID 9/:,o ( L7t)-L]ft J pt:NP•r: ,( /'W tl kAIVI f=ol JJ. (see .S&'-J iJ414. I !"(1'11'" -ps-U 2A -I) -nm tr MJT' ..t b'E'Jit.,; c()wu•llu..}, SrRc:s1e.s CALc flo reo nt?.. 7/lfJ O;w-ot rtu4.1 ;:r~t? Fot. /l&fl'~~Ailc: CJ411-r. 2 3 4 s 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 36 37 38 39 40 41 42 43 44 45 46 65010 65 STONE 1?. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION & GROUP CALCULATION NO. OPTIONAL TASK CODE PAGE.2_ /S'~u s $:<61-17A EXTERNAL HYDROSTATIC PRESSURE External Liner Sections L-~through L-74. · L-4o through L-~ L-ao through L-)1 L-zo through L-2.9 L-10 through L-t9 L-1 through L-9 Hydrostatic Pressure (psi} 117 160 195 230 320 380 External Head (ft} 270 369 450 531 738 877 The external pressures g1 ven by 1 and 2 above shall not be considered to act simultaneously. Reduction in External Hydrostatic Pressure Criteria External Reduced Design Liner Section Pressure Pressure ~ Llo to Ll3 230 psi 190 psi LIO to Ll9' 320 psi 265 psi L I to L 9 380 psi 315 psi 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 36 37 38 39 40 41 42 43 44 46 .fo.501Q.65 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION Ci GROUP s CALCULATION NO. OPTIONAL TASK CODE SC-1:.!-(7A PAGEL I ScJ't:rD I I UAJIJ(?(( 71tli T!/7'CtfNJrL ?/?ttftiJ~G ""''ll Tift; CALCfJ£ATiiJ¥J elf.= T/IICkf.ll?IS,. ::ry-IS A-.fJllh£/J T/IAT oNL.r Tilt: 'l?t:rck sut~od VJJt Nl, "Ff<O,., C.4.1J L 1 Tc> t;(AI L 2 :J ( t>t=-;= .. 1 ) W1' L ~/IA!(c IIIli' ~N-tt r;~t?1J~c '-''711 J7ttFt J..,,vr-~. -rtt£ G-t-t /!(!''7f-.,Cr;,J Lt;.A:>I( Mil 1?1../CAS!Jl, Cov!'~r-;~ IS ;4-JJVkOA o. us-~ tfF llll:: ~AAUJJ t.f1: Jlt7:<. LtAfr-1< , (.fir.F.f) Tift: MJjiUl cl1= Co/JC/tl!"{e ?a~ (Rc J I..f 7: -n!Rt:E ])Jf{'t.;J:::;NT RA./JIU5 (fir) en: CNrCK~~ Rod<. 2oJJ(; /tl(fl /.HJu .... ,r-.0 ,., ~~e. 7\r = I· I 7\t. , -/?,. ~ /. 'l/?.~,. AM.U 7?,.::: s-Rs . )lr:: ~ c: ~ J )..! "TFtr:' 7CA tJ) v j dF ... r17:(:L L/ ;.JP/'i , r T ·r ..s s.~+l.. 71/E FoLLOWJ~ P~t-GE S/foWj TW£ eavA7ti.JN$) w/{IC/1 AI?. t: P'X7'RA!7"EIJ pR0/41 f(r:F. 2 ct1.1 (/P.:U To CAL cutA Tt: Ttl!; 2 3 4 5 45010.65 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. I DIVISSION fj. GROUP /!r>oo CALCULATION NO. OPTIONAL TASK CODE S~l.I-17A PAGEL 7 ----·····--····-·-······--···· 8 9 10 II ... ::::::.:.' 12 ,7 ;::1CCbf3EN 'b I"'IE"li·IUD (~~OM RL:F. J) 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 b ::::: ;::"·i<·F'*R·:::./t WHERE b -TENSILE STRESS IN STEEL LINER E_-ELASlTC MODULUS OF CONCRETE Er -ELASTIC MODULUS OF ROCK F:·:::; ... F.:r.~:u ·r I li'', (JF =::TEi:::t... ; I t·.~E: F< .1 • '....1 ~:::· ,_ Pc ·-F:A D I u:;;; OF CCH'~C~F;:ETE hr-·-F~AI) l us (:Ji::;' CHI~Cf::ED F{CJC~I< M~c= POISSON'S RATIO OF CONCRETE MUr= POISSON'S RAT£0 OF ROCK - (", ;·· DESIGN INTERNAL PRESSURE WALL THICKNESS OF STEEL LINER GAP= GAP BETWEEN STEEL LINER & CONCRETE 1-(1-Pk/P)*B OR A=i (STEEL LINER W/0 ROCK: -1/((i+(1+MUrl/<1-MUs~2)*t*Es/(Er*R~)*(~~·Rr,Rcl / < 1 +r1Ur-\ + 1 ) 1) 38 NoT£: 39 40 41 42 43 44 45 46 /. Tf. Til& SJ[.;[-L }.;~~.&'?.._ CAN !lefT 1'-IOV£ /A.} TIIC A{'XftrL .1Jitr('CTIIVJ ,:7:: LINn? , 771t= LO!v4tlutJ '"'/f'L. ST~t-JS IN TIIC L!Nr-~ ;.s. ff?.uM /)oJJJ ();J RATIVN cf{r--c{. 7ff/( JlRt-JJ If IJI!our o. 3 rfl= llvup .JTPf'.i.S. 2 11-71ft-.. rrr-r-1.. Ll~ov~lt c~~.u MeAT.= IH Tile A-Xu~·(.. .. 'blttcxrnj;.l r7F-L;~z:-~t A-11./.U ;VU CONCIH?~ A PC! 7?. oeiC /tROUJ.ID L..//vf:!~ ~ 7/IC J:I;i..lt; t(CJ dt/11~-S"r!U:~J\ ll o.~ or-Jftlaf 5TR(;.!S. 3 If t::/1/d('r N' fl;. j sm~n 1 s tc;Ir Tlf;+t-/ 1 f&'OI) Jf~t;J< . ;tJ At?. Hr cM~s . _"!· UST:; Jf!Jap .JTtl:JI TO (/1-LCulA?E TtltC((I./7:'.-jJ . JJ rr,).JJ(-~ VAT/o/t. . ' '~ I , DESIGN CONDITION ALLOWABLE STRESS t.sra-v-.s -s 21.1-17 A DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'~ RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(% OF RS) NORMAL 40000.00 615.00 27900000.00 3000000.00 500000.00 0.30 0.20 0.27 66.00 84.00 92.40 0.75 0.05 TENSILE STRESS IN STEEL LINER 0 KRUSE'S METHOD S1 = 34452.1 PSI < 40000.0 PSI JACOBSON'S METHOD S2 = 35817.5 PSI < 40000.0 PSI PSI PSI PSI PSI F'SI IN IN IN IN X I~-s-J' 2 6 I~ /7 A STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE L I -L lJ NORMAL 40000.00 615.00 ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK 27900000.00 POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER 3000000.00 500000.00 0.30 0.20 0.27 66.00 84.00 109.20 0.75 / GAP BETWEEN STEEL LINER AND CONCRETE(% OF RS) 0.05 I \, __ ·TENSILE STRESS IN STEEL LINER r ., . "-. •] ~/ KRUSE'S METHOD S1 = 35454.6 PSI < 40000.0 PSI JACOBSON'S METHOD S2 = 36770.3 PSI < 40000.0 PSI f 1/ F'SI PSI PSI F'SI F'SI IN IN IN IN I. '_ .. -t. ·-~_ ... __ .. ~ .. ·---__ .. --·--._..,. _ __,.-------· ---... --~---·---·-------------.. ..-"'---~~ -· ... ' .. . , . l : : jstt;o-.s-r c.~l-17.4- to V-I L J-L ZJ STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROC~~ ZONE NORMAL 40000.00 615.00 27900000.00 3000000.00 500000.00 0.30 0.20 O.E7 66.00 84.00 330.00 ~ WALL THICKNESS OF STEEL LINER 0.75 ' GAP BETWEEN STEEL LINER AND CONCRETE(% OF RS) ----,_TENSILE STRESS IN STEEL LINER ( ·~----------------------------\J KRUSE'S METHOD S1 = 40163.8 PSI > 40000.0 PSI JACOBSON'S METHOD S2 = 41217.4 PSI > 40000.0 PSI 0.05 f /'L PSI PSI PSI PSI F'SI IN IN IN IN % J s-tuv -s-s zc r -I 7 A P. c-v. 1 L 1-L l.3 STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER NORMAL 40000.00 615.00 27900000.00 3000000.00 500000.00 0.30 0.20 0.7.7 66.00 84.00 330.00 0.94 GAP BETWEEN STEEL LINER AND CONCRETE(/. OF RS) 0.05 TENSILE STRESS IN STEEL LINER f::RUSE' S METHOD 51 = JACOBSON'S METHOD 52 = 34622. 4 F'S I 3532.3.8 PSI < 40000.0 PSI < 40000.0 PSI PSI F'SI PSI F'SI PSI IN IN IN IN I. /24., - ' I . ' _, • j ' ' .. 0 LI-L2.} STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK F'OISSON' S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(/. TENSILE STRESS IN STEEL LINER EMERGENCY 66600.00 815.00 27900000.00 3000000.00 500000.00 0.30 0.20 I(>. 27 66.00 84. (H) 92.40 0.94 OF RS) 0 .0~· KRUSE'S METHOD S1 = 38396.3 PSI < 66600.0 PSI JACOBSON'S METHOD 52= 39851.2 PSI < 66600.0 PSI PSI PSI PSI PSI PSI IN IN IN IN /. ··-~·---.,...·-·--.. -·-.-+'!' -.. --------... -~------~----..----~ ---·-----.. -·---~---· -------~--------·--·~--- i 157tfu-.s--.S 2' I-17A STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE l-1-L 23 EMERGENCY 66600.00 81::.'·. 00 ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK 27900000.0(1 POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(% TENSILE STRESS IN STEEL LINER OF 3000000.00 500000.00 0.30 0.20 (>. 27 66.00 84.00 109.20 0.94 RS) 0. o::, KRUSE'S METHOD 81 = 39466.7 PSI < 66600.0 PSI JACOBSON'S METHOD 52 = 40853.2 PSI < 66600.0 PSI F'SI PSI PSI PSI F'SI IN IN IN HI I. . -~~~~---~·-__ .. ___ .. __ ., ____ ._ .. ____ . __ .._..... ___ ~,.. ---------·-------~-~~------- / icv. I L 1-Ll-3 STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) ' . ' DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE F·OISSON' S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(/. OF RS) ~· TENSILE STRESS IN STEEL LINER EMERGENCY 66600.00 815.00 27900000.00 3000000.00 500000.00 0.30 0.20 0.£7 66.00 84.00 330.00 0.94 0.05 (,·_.) ____________________________ _ KRUSE'S METHOD S1 = 44335.5 PSI ( 66600.0 PSI JACOBSON'S METHOD S2 = 45390.2 PSI < 66600.0 PSI f. }s- PSI PSI PSI PSI PSI IN IN IN IN I. ~------------___ , ________ -·---··-----·-~ ...,_, .,. .. ----.. --_____ .. ___ ....__ --~-... ~ <---·-----,...,------. ...... ·-~..-.. -.. -"'""""'----... -,..., j~-~-S-S .26;-/7A. (tc"v. 1 LJ-L 2) STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(/. OF RS) TENSILE STRESS IN STEEL LINER EXCEPTIONAL 80000.00 975.00 27900000.00 3000000.00 500000.00 0.30 0.20 (>. 27 66.00 84.00 92.40 0.94 0.05 KRUSE'S METHOD Sl = JACOBSON'S METHOD S2 = 44575.7 PSI < 80000.0 PSI 46420.4 PSI < 80000.0 PSI p. /~ PSI PSI PSI :=·s I PSI IN IN IN IN i'. ' •' . ' ' . (-----_, ,, ' (~\ ·' -/ . ..-' (~) L 1-L 2..) STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(/. TENSILE STRESS IN STEEL LINER EXCEPTIONAL 80000.00 97: •. 00 27900000.00 3000000.00 500000.00 0.30 0.20 (l.27 66.00 84.00 109.20 0.94 OF RS) 0.05 KRUSE'S METHOD Sl = 45932.9 PSI < 80000.0 PSI JACOBSON'S METHOD 62 = 47690.8 PSI < 80000.0 PSI -~----·-------··-· -~------------·-·-----------------··----------- f. 17 PSI PSI PSI PSI PSI IN IN IN IN % ; \.. / /.)~-J-Sell-1 7.A L 1-LZJ STEEL LINER UNDER INTERNAL PRESSURE(CONT'D) ------------------------------------- DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(% TENSILE STRESS IN STEEL LINER OF EXCEPTIONAL 80000.00 975.00 27900000.00 3000000.00 500000.00 0.30 0.20 0.27 66.00 84.00 330.00 0.94 RS) 0.0!':· KRUSE'S METHOD S1 = 52106.1 PSI < 80000.0 PSI JACOBSON'S METHOD 52 = 53443.2 PSI < 80000.0 PSI PSI PSI PSI PSI PSI IN IN IN IN /. ' 1 .-' 15800-S-5261-17 A STEEL LINER UNDER INTERNAL PRESSURE<CONT'D) L l. (J,-L3 o DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE(% TENSILE STRESS IN STEEL LINER OF RS> ONLY STEEL LINER TAKES THE INTERNAL PRESSURE NORMAL 40000.00 PSI 615.00 PSI 27900000.00 PSI 0.00 PSI 0.00 Ps-I- 0.30 o.oo 0.00 66.00 IN 0.00 IN 0.00 IN 1. 00 IN o.oo /. S= 40590. 0 I'll > 40000. 0 P'il S. Li6fT.L r a VI?( • ilcJT. o .K. r " ---------------~--:-·---~------------------------------------~-- --·---------------------·--·--··---·---------------··--··--------------··---- I 5800-S-5261-17 A = STEEL LINER UNDER INTERNAL PRESSURE<CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE<% OF RS> TENSILE STRESS IN STEEL LINER ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 53790.0 ~ < 66600.0 ~I EMERGEI'ICY 66600.00 815.00 27900000.00 0.00 0.00 0.30 0.00 0.00 66.00 o.oo 0 .. 00 1 . (l(l o.oo r f. zo PSI PSI PSI PSI PS1. IN IN IN IN I. • . . ' l \ 15800-S-5261-17 A STEEL LINER UNDER INTERNAL PRESSURE<CONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE<% TENSILE STRESS IN STEEL LINER OF RS> ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 64350.0 .iilol < 80000.0 ru EXCEPTIONAL 80000.00 975.00 27900000.00 0.00 o.oo 0.30 o.oo o.oo 66.00 o.oo 0.00 1. 00 0.00 , . PSI PSI PSI PSI PSI. IN IN IN IN I. -·-· --·-··---·· ·---------.-···· .. ---------------.-----~-·-·-· --·-------------- / (~.1 ·~ 15800-S-S261-17A ' STEEL LINER UNDER INTERNAL PRESSURECCONT'D) L 31-L 74 DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE<% OF RS> TENSILE STRESS IN STEEL LINER ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 42240. 0 Rf > 40000. 0 P.St NORMAL 40000.00 PSI 640.00 PSI 27900000.00 PSI o.oo PSI 0.00 PSI 0.30 o.oo 0.00 66.00 IN o.oo IN (l, (H) IN 1. (l(l IN (l. (H) % r '5800·5 .. 5261-17 A STEEL LINER UNDER INTERNAL PRESSURE<CONT'D) DESIGN INPUT ( ' ""'----,. DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE . WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE<% OF RS> TENSILE STRESS IN STEEL·LINER ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 39755. 3 ~ < 40000. 0 PSI L 31-L74 NORMAL 40000.00 PSI 640.00 PSI 27900000.00 PSI o.oo PSI (l. 00 PSI 0.30 o.oo 0.00 66.00 IN 0.00 IN o.oo IN 1.06 IN 0.00 f. r 15800-S -52 61-17 A ~ STEEL LINER UNDER INTERNAL PRESSURE<CONT'D) L 31-L 74- DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROC~( RADIUS OF STEEL LINER RADIUS OF CONCRETE / RADIUS OF CRACKED ROCK ZONE \ ' WALL THICKNESS OF STEEL LINER : . ._,/ GAP BETWEEN STEEL LINER AND CONCRETE<% 0~ RS) TENSILE STRESS IN STEEL LINER ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 55770. 0 1"M" < 66600. 0 ~ll EMERGENCY 66600.00 PSI 845.00 PSI 27900000.00 PSI 0.00 PSI 0.00 PSI 0.30 0.00 0.00 66.00 IN 0.00 IN 0.00 IN 1. 00 IN 0.00 !. r .-·-~ ---·-~--.................. _ ... _.._...... .............. ~-~-------_ __...._..._..-~---'---·~-,-..-. ._--··-----~---------~--- ( 15800-S-5261-17 A -STEEL LINER UNDER INTERNAL PRESSURECCONT'D) DESIGN INPUT DESIGN CONDITION ALLOWABLE STRESS DESIGN INTERNAL PRESSURE ELASTIC MODULUS OF STEEL LINER ELASTIC MODULUS OF CONCRETE ELASTIC MODULUS OF ROCK POISSON'S RATIO OF STEEL LINER POISSON'S RATIO OF CONCRETE POISSON'S RATIO OF ROCK RADIUS OF STEEL LINER RADIUS OF CONCRETE RADIUS OF CRACKED ROCK ZONE WALL THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER AND CONCRETE<!. TENSILE STRESS IN STEEL LINER OF RS> ONLY STEEL LINER TAKES THE INTERNAL PRESSURE S= 6 7320. 0 11¢ < 800(10. 0 ~· L31-L 71- EXCEPTIONAL 8(l(l(H). 00 1020.00 27900000.00 o.oo (1.00 0.30 0.0(1 0.00 66.00 (l. (H) 0.00 1 • (l(l o.oo ( PSI PSI PSI PSI ps·r IN IN IN IN I. c·,: 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 (~, . 20 . , ;i 21 22 23 24 u 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 --0~42 43 44 45 46 ------~-~--------------··-----·---·--·-·--·-------- &5010 65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION e; GROUP CALCULATION NO. OPTIONAL TASK CODE }S'r:Pf;O s .s ;(( 1-17A J(r;v.t f·l /(t:Clulltf?-b ~ TlltcKI/f!1J cJF' ..1'rtf:( Lll-./l>~ t/JJtJFft Tf(E lr/TfJ(ft/kt.. j?ltt-Hu'(E ( C~t1) ~lifJ.U/Kr-IJ T'tc~s l..l·-L 23 w/ /{tJcJ<.. lS/fb /.. lf.!-LJ'iJ W/o ~oCJ<. //, LJI-L74 fo ~ocK ~" * I ' f11-H7 w/o R_oeK Y'a ,, .;. PI -f"lS" J - f '7-pq .....,./o :tocJ< -% ,, ~ ?II-Pll 1'~>. r'tf3.f(l '1/o 7?tl;.l( 1.2 h .. '* I NCI::IR~Te ..,.k RJu.IJWI.., c 1/t.ttJtA'Trt>V ~ Nfl~Nif"'-. El41.?1t.fir .,JC,. {?xt'l7f714Nip.. -· .. 1'-f,-MT · o.XF 0·' '1.5' o. ~li'V" .. , -. pi-Pr" p-, _,, Ot 't.fl o-~ r"-,.,t. ..,,;?h .. rrJ 0~~ <'•31\ 0' Jf z. L7t~-l7f.--, !. f· . -'-...... . ' ' --r - ' .wr-o ()1.1 t-~ ?~ J>: Q7i?J/4~ /Vit-tN~ "'}R.ti:JJilG R.• /1/JI/E' J?JrJ)I() J -s~ ~IJ(t' ~. PAGE 2 ' ID II ':..e., ~ /1'-o"" I ,. II -o- ,'--6'- G c..,,, HfDRD-T'fill . .:Q. '"' l'~ I , "-· 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 (~) 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 :u 36 37 38 39 40 41 (---,.,_ 42 (__;' 43 44 45 46 ... 5010.65 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER PAGE2.7 J.O. OR W.O. NO. I DIVISION Ei GROUP I CALCULATION NO. 'OPTIONAL TASK CODE /~o S S 2.&1-17A --pRi:JSUit£ J.S 6~~~ II-IAN CAirtOk .. OocKLJ~ r:-~/YIIA-'-r-p,RC'Il(.((E: .::nJ 7/IIS J/fQ7diJ) A FA~#t..Y dF C/117/CifC... /JC)CKUNf, OX7t"'ltMtt... fl.t'-;$.1.11/tG IS CA-LCutlf7GJJ ~"R .))JFfr-~AJT wlf'{.l. T/ftC/(A,tlL TliE Gtf ~f!W 4.1~1( ArFiJ l?IFC~tN~ C4JA:i~57c JJ ~t::u Q •• .r:% OF 71IG" ~4J)I(f1 elF J'rt:r--L Lt~R.. ( ~~ I) ··---------·-----···--~~-~----~---··--·-· <Sn-Sv}*(Rs/i)A3*<Sn/Es>A1.5-<Sa-Sn)*1.73* <Rsle>*<1-0.225*<Rs/e)*CSa-Sn>/Es>=O ---------(1) Per= A*Sni<Rs*C1+0.175*<Rs/e)*(Sa-Sn)/Es>> ---<2> 'tl~i"l) WHERE Sa = At: IE: 1:1' II i'' E STRESS OF STEEL LINER Sn = CRITICAL BUCKLING NORMAL STRESS Sv = -Es*GAP/Rs Es = ELASTIC MODULUS OF STEEL LINER r GAP= GAP' BETWEEN STEEL LINER 81. CONCRETE Rs = RADIUS OF STEEL LINER i = RADIUS OF GYRATION e = THE DISTANCE FROM OUTER FIBER OF RING A = AREA OF SECTION Per= CRITICAL BUCKLING EXTERNAL PRESSURE USE NEWTON RAPHSON MET~OD TO SOLVE EQ <1> FOR Sn SUBSTITUDE Sn IN EQ <2> TO OBTAIN Per TO N.A. 1»1& CRtnfi.AL /jUCI(Lt~ ~~AJ}I... '"P/tf:.-.f...II,/1(£; ~/?. 1/l'f-~/Ci.l$ TJt:t~rJ PRII-f . t. I .y os"TO I~-I<: hJJ.r..N' ,~,.) 7111: F:"'-'.(){Qtll/l, /J'ttie.J ~ "'f/ltr Sl='cT~'ftlif ' . I 5800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) DESIGN INPUT YIELD STRESS ELASTIC MODULUS OF STEEL LINER INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS 90000.0 PSI 27900000.0 PSI 66.0 IN 0.5000 IN .05 Y. OF RADIUS AMSTUTZ 8( JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA SECTION MOMENT INERTIA RADIUS OF GYRATION OUTER FIBER OF RING TO N.A. RADIUS OF RING SECTION CRITICAL BUCI<LING NORMAL STRESS CRITICAL BUCKLING PRESSURE • A J i e R Sn Per = = = = ... = = 0. 5 IN-''2 0.0 IN""-4 0.144 IN 0.250 IN 66.3 IN 13740.2 F'SI 92.0 PSI . . ' ' I ' . .~ I I \ . ~ 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE(CONT'D> DESIGN INPUT ( YIELD STRESS 90000.0 PSI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A = SECTION MOMENT INERTIA J = RADIUS OF GYRATION i • OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn = CRITICAL BUCKLING PRESSURE Per = 66.0 IN 0.5625 ·IN .05 'l.. OF RADIUS o. 6 Iw·-2 0. 0 IW"·4 0. 162 IN 0. 281 IN 66.3 IN 154~8.6 PSI 118.2 PSI r 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) DESIGN INPUT YIELD STRESS 90000.0 PSI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS 0 TOTAL CROSS SECTION AREA SECTION MOMENT INERTIA RADIUS OF GYRATION OUTER FIBER OF RING TO N.A. RADIUS OF RING SECTION CRITICAL BUCKLING NORMAL STRESS CRITICAL BUCKLING PRESSURE A = J = i = e = R = Sn = Per = 66.0 IN 0.6250 IN .05 I. 0.6 o.o o. 180 0.313 66.3 17110.2 147.0 OF RADIUS- IN''·2 IN-''4 IN IN IN PSI PSI r p. 30 -• ---. ..._-.-----~--·-------.--·--• •----~-r-,.·---··-----------------------.--r-·-,---~--..-·----~-~-----------....----·~ -~ . ._. ... -·-........... --..............-~ .. 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D> DESIGN INPUT YIELD STRESS ELASTIC MODULUS OF STEEL LINER 90000.0 PSI 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A ~ SECTION MOMENT INERTIA J • RADIUS OF GYRATION i • OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn = CRITICAL BUCKLING PRESSURE Per = 66.0 IN 0.6875 IN .05 I. OF RADIUS 0. 7 IN··'·2 0. 0 IN""A 0. 198 IN 0.344 IN 66.3 IN 18700.3 PSI 178.4 PSI r 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) DESIGN INPUT YIELD STRESS 90000.0 F'SI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A = SECT I ON MOMENT INERT I A J· • RADIUS OF GYRATION i = OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn = CRITICAL BUCKLING PRESSURE Per = 66.0 IN 0.7500 IN .OS I. OF RADIUS 0.8 IN<'·2 o.o Iw··4 0.217 IN 0.375 IN 66.4 IN 20233.3 PSI 212.2 PSI r ""' .. ·. 15800-S-5261-17 A BUCKLING. OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) -----~----------------------------------------- DESIGN INPUT YIELD STRESS ELASTIC MODULUS OF STEEL LINER INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER &c .. CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS 90000.0 PSI 27900000.() PSI 66.0 IN 0.8125 IN .05 I. AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA SECTION MOMENT INERTIA RADIUS OF GYRATION OUTER FIBER OF RING TO N.A. RADIUS OF RING SECTION CRITICAL BUCKLING NORMAL STRESS CRITICAL BUCKLING PRESSURE A J i e R Sn F?cr = 0.8 = o.o = 0.235 = 0.406 = 66.4 = 21713.3 = 248.3 OF RADIUS IW"·2 IN·~-4 IN IN IN PSI PSI r 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) uESIGN INPUT YIELD STRESS 90000.0 PSI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A ~ SECTION MOMENT INERTIA J ~ RADIUS OF GYRATION i = OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn • CRITICAL BUCKLING PRESSURE Per = 66.0 IN 0.8750 IN .05 I. OF RADIUS 0. 9 IN-''2 0. 1 IN-''4 0.253 IN 0.438 IN 66.4 IN 23143.6 PSI 286.6 PSI r -----~----~-----------------.·---. ------·------------------~--~-------------------~----------~-------------------------- -.;_.. . · •• l "-~"--------------------· ··------~------- 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE\CONT'D> uESIGN INPUT YIELD STRESS ELASTIC MODULUS OF STEEL LINER INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER 90000.0 PSI 27900000.0 PSI 66.0 IN 0.9375 IN GAP BETWEEN STEEL LINER & CONCRETE .OS I. OF RADIUS CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A • SECTION MOMENT INERTIA J = RADIUS OF GYRATION i = OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn = CRITICAL BUCKLING PRESSURE Per ~ 0.9 0.1 0.271 0.469 66.5 24527.3 326.9 IN-''2 IN-''4 IN IN IN PSI PSI , . . ~- J 5800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D> uE:SIGN INPUT YIELD STRESS 90000.0 PSI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER & CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE ------------------------------------ LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A • SECTION MOMENT INERTIA J • RADIUS OF GYRATION i • OUTER FIBER OF RING TO N.A. e = RADIUS OF RING SECTION R = CRITICAL BUCKLING NORMAL STRESS Sn ~ CRITICAL BUCKLING PRESSURE Per • 66.0 IN 1.0000 IN .OS I. 1.0 0.1 0.289 0.500 66.5 25867.2 369.2 OF RADIUS IN-''2 IN..-'4 IN IN IN PSI PSI ( p. 3b -------~-....... 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) .... c::SIGN INPUT YIELD STRESS 90000.0 PSI ELASTIC MODULUS OF STEEL LINER 27900000.0 PSI INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER ~ CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS AMSTUTZ & JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA A = SECTION MOMENT INERTIA J = RADIUS OF GYRATION i = OUTER FIBER OF RING TO N.A. e • RADIUS OF RING SECTION R • CRITICAL BUCKLING NORMAL STRESS Sn = CRITICAL BUCKLING PRESSURE Per • 66.0 IN 1.0625 IN .05 Y. OF RADIUS 1. 1 IN-''2 0.1 IN-"'4 0.307 IN 0. 531 IN 66.5 IN 27165.7 PSI 413.4 PSI (' . :.-· 15800-S-5261-17 A BUCKLING OF STEEL LINER UNDER EXTERNAL PRESSURE<CONT'D) DESIGN INPUT YIELD STRESS ELASTIC MODULUS OF ST6EL LINER INSIDE RADIUS OF STEEL LINER THICKNESS OF STEEL LINER GAP BETWEEN STEEL LINER ~ CONCRETE CRITICAL BUCKLING EXTERNAL PRESSURE LINER W/0 STIFFENERS 90000.0 PSI 27900000.0 PSI 66.0 IN 1.1250 IN .05 I. AMSTUTZ ~JACOBSEN GIVE THE SAME RESULTS TOTAL CROSS SECTION AREA SECTION MOMENT INERTIA RADIUS OF GYRATION OUTER FIBER OF RING TO N.A. RADIUS OF RING SECTION CRITICAL BUCKLING NORMAL STRESS CRITICAL BUCKLING PRESSURE A J i e R Sn Per = 1.1 = 0.1 = 0.325 = 0.563 = 66.6 = 28425.0 = 459.4 OF RADIUS IW'2 I N·h'4 IN IN IN PSI PSI . --------------~-·----- 2 u Ill >( !! ~ ~ i • ~~ ~;; ~~ i I 1311;1: ~ :::::: I 11~1 'I ~~ ! II • -lh I I ~! --------......;.. ________ ,. ___ _,. __ ~-------_...;'" .. ~· I • ••• fi • I ~ i • I •• I • .. -... -,. . . . ~· . . . . ..· .. · .. -: ...... , -' .. . . . ~..:·. . .. ....... •-. . ._, ... , . . . . . • .. •··. ... ··: .o: ..-~·::' :;·. _: . ' . . ~ .... ~ . . . . · .. · .. .. . ; . . .. , : . ., . ~..... . :_. ·• ' .. : .. ·· . . ~ •.· "f'" : .. · ... :". ..... ·. ... . . . . ~-. . ,• ;,· .. .. . . . . . . ·. .... . · .. . . "':). -.~.· . -.. . . .. -~ . , .. . .. . .. .. . . . --.: t·::~~~ _: ·-.. ·. . . . . .. ... -··-----------·-• ·--.-o:----~~--~ T "' _ _.._. ...... ...,--. ___ ,-•--~--· _.,......,._.._.~.-. -•. ----·--r---.. . ---~ 2 3 s • 7 8 9 10 II 12 13 14 15 Ill 17 18 19 20 21 22 23 24 Z5 26 27 28 29 30 31 32 :u 34 35 36 37 38 39 40 41 42 43 44 45 48 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CAL.CUI..ATION IDENTIFICATION NUMBER .J.O. OR W.O. NO. DIVISION & GROUP I CALCULATION NO. !OPTIONAl.. TASK CODE PAGE q_o I;-<ft:Jr) 5 S2t.I-17A /tGO.ut(~J ltnCK~s t:»al{ ~ItA!""'-Ptrli!'.f.I(I/l e ( LJ~~ .t'E'CTt<JIJ llJt:rE~ 141.. f' lrf'!a ftC: ~"'(} ~~ l(r-fl 71/1 ck~t't-h (/lfl~ (;N) L' -t...., 3Jr /!"/,' . ,L10 -LJfl ..2~1"" ..,~ Lw-1..2..1 1'1 0 ~~ L3o-L:J' 11r ..}il L~.AJ-LV.9 16• l I . ·""· :{L Lfn -(]?.. 117 ~& --r 2 5 7 ' 9 10 II 12 13 IS 16 17 ,, 20 21 41 46 J.O. OR W.O. NO. /ScfOlJ STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION u GROUP s LIO-Lt'l Ll..:>-t.lJ LJo 'f">l...,..ft" 1'7 .... P9 ""' -r,, CALCULATION NO. OPTIONAL TASK CODE .Q41-/7A ~C-1/.f 77tt~J) ,f$-~'i) ~~ I ;./'lT;(#AI.. P~IJII~&" IS: ,, ij, I " 1)/c" ,~, ~ ~~,. }g'' 7Rfc~11 /t-4'4 f:;-6( /!)f~H.IItf( /II! crvtr 'SAl. r PAGE4/ I u 1){(. 4 5010.64 I FRONT) CLIENTS. PROJECT CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE ALI\sKA Pow'l?t AI/T/fOI2tT( -/]R,tiJL~r LAkE CALCULATION TITLE (Indicative of the Objective): S"Ttf.CIS ;"tAJ,fL'f.JU c,'"f rlh-(; G J,vlrf/ ;oil'~ j;V..StC;C" V/Af/[7t:tz J. 0. OR W.O. NO. CALC U L AT I 0 N IDENTIFICATION NUMBER DIVISIONS. GROUP CURRENT CALC. NO. S~61-1?8 OPTIONAL TASK CODE *APPROVALS-SIGNATURES. DATE REV. NO. INDEPENDENT OR NEW PREPARER(S)/DATE(S) REVIEWER(S)/DATE (S) REVIEWER(S)/DATE(S) CALC NO. 10·~ P-~ ~ A.Jit· '7 I/( A k. ,4-s ~I c.T. _;<. C)-2?-1l 0 lj:u/~7 DISTRIBUTION* I I COPY I PAGE 1 OF 2() QA CATEGORY (v') OI-NUCLEAR SAFETY RELATED 0 II 0 m r!:f' II rJJt. · OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC.NO. *REQUIRED(..;) OR REV. NO. YES NO r I COPY GROUP I NAME £.LOCATION l SENT GROUP I NAME S. LOCATION I SENT I (v') J I (.,;) RECORDS MGT. I ' ~01J 0,'( I / I I 0'03 FILES (OR FIRE I ~~-7~ I '/ I I FILE IF NONE) I -~~ I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! I I I 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET .. 5010 65 CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION Ci GROUP CALCULATION NO. OPTIONAL TASK CODE PAGEL ~~ 3 s Jc61-17B OI]Ja::n Ill.;; d"F CAlCf..JUf Tl o,J (ALCUlA "Tioll) ~l[':rtfofl / AJSlJ"-'IY71~.S RF:FF R.f? NC ~ r WIJc LUfltJAJ 4 !f-LLOW /rf!U: STifi?.SJ FoR /=Uwt,£ A#lJ boL/r s-JY~J/6N /tl~#ltt.. 'JRI?!!V/(t; 7 8 STRESS CALCULA /1 o tJS 3 7 d'-2o ---------- CALCULATION SUMMARY STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION NO. I 5"'.?o'O -s-.S 261-;7 8 45010 62 CLIENT /PROJECT ALAS,t'-4 J)oWFR ,4{/jllo~tr't -llRA:i)LEr LAkE SUBJECT I TITLE SI~EJJ A;.,PU .. (JI ~ dF' T-tA~t: OBJECTIVE OF CALCULATION REVISION 0 I PAGE 1~3 QA CATEGORY/ CODE CLASS tv/A 70 ');7?~/t)tJ THE' f=/.J'ti./Oe C'OJJif!XTtuN f=OR T/112 c L.OSUN£: A-T 7/tf' l?tJJJ OF- ? l:NJ/IJ c J( . CALCULATION METHOD/ASSUMPTIONS 71fe 'f~occjj~G' nJ kpfftiiJ/'( ~ oiF A!.M£ SF'CT VIII -VI VI 11 ()fl:"u /() 'J) 12-f 16 AI PL A/lA 'C co v J/l:'CT IIH./ ~-'V rrlt a oL rr- SOURCES OF DATA/EQUATIONS / ..STC:(;.L LJA/("'~ l'rJJil j)~lll.IGCK .ST/ti)Crt.Jitlfr(. )Jl:J(t..JJ C~li~tVA Fe~ AlAI/(,~ pa,_m_ AifTif~tt'Tr~ l!k.AJ)LE'( LA)(c ll'ro,fcta:cr/lt<. 'P~r-t /ltlflCT. (. MMt; sn:r VIII -j) 11/. I f7S'.J 3 1 PROCfE!SS ~utPMcNT J:JY/tw' !JY LLoyi) /3/?(JlA)Nf:-t..( ~ l?t)IV,II) '(outJt;~ JoJhJ 'WILr:r 1 J 0 N i , J:..i.l?, I ., r-cj +. saw ~tttHJ'~ t!:>'lfDI>-F-J-2t.Ja -1 CONCLUSIONS Tilt Ftlol14-( 1JT::fl6tJ d'l=PLA.d~r= 11 Jllot-.;Al QAi. J> 7. T/1~ ./)l!TH,lt:il );T-J!6JJ ";;:::. /161..11 5(-E J .t t.J CifU'. ~/.!a::~_ J~.,r ~~-I ~ , REVIEWER (S) COMMENTS PRE PARER c. 7. L--.r. REVIEWER/ CHECKER l ,4-,-"'"""' "'\.-? ---. INDEPENDENT 1 REVI~WER J tvj!} OAT~ /_ 1 '1/ ,2 7 lo-t. DATE . } ,v jll ' 2 3 4 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET ... 5010 65 CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION u GROUP s CALCULATION NO. OPTIONAL TASK CODE PAGE_£_ / 5-<f'ov S26!-17 8 J<r 1 .(Si (5y:c-6r; ,fu:: /)) /7ft; f...tA7t?tlt/H_ FOR ?LA,<J{,'t-;.s. ,;ts.7J--r A/1o GR A . C3"" 4~VLJ Fe~ ,&oLTf ;s At6i.T'~'t'£63~,kttr-o (sr~Jof"/\JJ, St!J= n~lrl;) S/Rl=J( U..Se-f Ill?-0/1/C r/IJIY 77t/U~ UC S ~ 2 J c"r ;tfll.f~ S&l VIII -vtll. /lltS .4lLOW41lLcf" STAf:-.iS Jf F<1/( Nolf.N),;-c_ C()NJ)i ljj;J, \.vtl/f MATT?RtiH._ NO/? MM.._ F14t·~~t-toJr'f' H r o ~ o A<--+ Cot1D1iHAJ Q};.JIJtTI u.-J Tl;.S.T (/>51) C;)SI} r PSI) FLAIII1.J F i'-A 71o. r.~. A c Sf:. 2 7 000 lf~4~9 j.f'. .fr 2. ~o ' ' > J 2 {, ooo ~/60 0 i )s_s-oo $ct. if .A.s-6~, TP6?D /-+II sO 7E pt>R. ThtctAA;n OIIF~ -<. '' ,FRol'-1 /A-aa;· BS~ cfF Pt"r. I ~_,.J/ , c f/u. R~.!)/) en a ,..; • 2 3 4 5 7 8 9 10 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET ... 5010 65 CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION & GROUP CALCULATION NO. OPTIONAL TASK CODE PAGE 4£v /";;~ s S2t.l-178 SH < I, S' Sf JA~l?t-.17/ttr._ FtAN~C j"[lf(J] ST (S~t ..J s~) /z. < S;- (SJ.I...f.STJ /z.. <-.Sf- J L-.N 1: ~;:"' c '('" ~s .. ooo ~ }IYJJRt~-~~ 6S?oo * 2 4 5 6 1 8 9 10 I I 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 • 5010 65 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION u GROUP s CALCULATION NO. OPTIONAL TASK CODE sz<::.;-t7B PAGE_5:_ I S"<f'ov Tilt: IJJ Tt'-I?V4'?_ p~1?:1s (}I(£ AT 77+t5 FLAM, 1: CdN!v'l'rr' !),..} H /h!tJ,._,tij To pr: 711~ J'A/<.f& /-H 71/E s-,-r.::c-L Lt~t?. F/?.()M L 3 I .....,..() L 7 2.. FROM /IJ/)lf2 Bs-z cJr ~r::-F l, 77ft: foLt-()Lo.)'...,l, JS 7111: ))1!]'16 ,.J l..v?l=~llltk_ '"ffolr!!i.l i!fS - ~ f/Oft...Wit'C.. l?4 !;IUJfi'IJ(. t' ['"X(t? P "lluil/kL 11 'f!Ji?o -TnT (PSI) Ct>ff' (VII) rr>rJ) (;<J.o J'<J-r /Dto 96..:;, ~ -ntJJ /J MJr A !JE:JI6N CoJ../l>tTI(J)/. Sl{fl;r,}f?S CAUullf70"D A.;R., 71/'J CONOtnoAI A1'(c;-/='-r>r( pr;:-fFiEAilr!' OM. r. { f 18. -P"l,o) 2 3 4 5 6 1 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 2!1 26 27 28 29 30 31 32 33 34 3::i 36 37 38 39 40 41 42 43 44 45 46 A5010.65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. /5-Boo DIVISION Ci GROUP s CALCULATION NO. OPTIONAL TASK CODE SZ/:.1-t//1 PAGE_§_ Bolt Size d )Lif ,z S~" :t~lf 7/, '8 l" )I 8" I J ~" I 3~" l t "2, 1 ~~" P~" Hf' 2" ~') 1/" -4 2'-2" "l.'J~" -4 3" • n, ('2J FLA~E 't .III~ttAL TYie . OJ UJt:. 2 T/l~et1-~ .S(?At& l!ot...Ts Standard Thread 8-thread Series Bolt Spucin!!* ~o. of Root Threads No. of Root Area ;\I inimum Pre- Area Threads 8, ferrcd )I~" 3" )I~ .'l P:i 3 :_!I { 6 3 0 :>51 ·>v 3 -,, 13 0 126 :\l'o. 8 11 0.202 thread !() 0.302 series q Oll9 below I" 8 0.551 8 0.728 :!'i :J 0.929 ·lt :1/. 3 -.·16 1.155 .'ll'f6 1.405 31~ 7 0.69:l 8 7 0 890 8 6 l. 05t 8 6 1.29·t 8 1 680 31~ l 980 3}~ 2.304 4 .) '2 l. 51.') 8 5 l.iU 8 ,") 2 .O-t9 8 P:i 2.300 8 2.652 p~ Pf 3.020 8 3 423 p~ ' 3.71:> 8 4.292 ;}1~ t 4.618 8 5.259 5~~ l 5.621 8 6 .. '121-61~ center-to-center distance bel ween bolts, inches \linimum Maximum Radial Ed::e :'\ul Fillet Dislanee Dislanee Dimension Radius R E (a I' russ !Ia ls} r l :li 6 " .i,'i " 711" I/ " .j, t:\s J4 1'16 !ill ll,j 1 ~1 t; 1'-~o .1' s 1'.1 J,).i f) I 7 I .. :'-'~' [:!8 1'1 !\ P, ~~ Pi )l• II ;1[6 71(,, s P.! 1'.1 ::! ., I~ l18 l ~8 :!"in ,, J>; 2 Jl2 ~l :) _~, ' -s ' ..,, . )58 ~")~· / ·~ -a -16 'lj/ H:i .,:i/ ;( -.j, -4 2~s J1i ·~! ~. ~ -16 2'z 2 31. ll{ ~ . .~ 2!!:4 'lJ/ :J '2 I 11 6 -4 3 1 ,6 2% F!i 13.1 fi 3% 2~8 -H~ 7, 3% 2)"11( ·H~ 1 ,ii tl I 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 38 39 40 41 42 43 44 45 46 &5010.65 J.O. OR W.O. NO. I'>~ 7 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP s CALCULATION NO. OPTIONAL TASK CODE S~61-1711 PAGEL <. .. ''; ., '_, . i ,. ·. l ~ \:2.~./ 0 ' < . 0 < < DESIGN INPUT OF FLANGE (l~-l-SZl(-178 INTEGRAL FLANGE BOLT-CIRCLE DIAMETER C= 121.5 IN DIAMETER AT LOCATION OF GASKET LOAD REACTION G-= 110.5 IN INSIDE DIAMETER OF FLANGE B= 108 IN OUTSIDE DIAMETER OF FLANGE A= 128 IN THICKNESS OF HUB AT 8ACI< OF FLANGE g 1 = 3. 375 IN THICKNESS OF HUB AT SMALL END OF F-LANGE go= 1,125 IN FLANGE THICKNESS t= 5 IN HUB LENGTH h= 10.5 IN ALLOWABLE BOLT STRESS AT AMBIENT TEMP. Sa;:; 26000· F'SI ALLOWABLE BOLT STRESS AT DESIGN TEMP. Sb= 26000 F·;: DESIGN INTERNAL PRESSURE P= 640 PSI /' ' THIS IS A SELF-ENERGIZING· GASKET ( THE FOLLOWING CALCULATION IS BASED ON THE PROCEDUF(E DESCRIBED IN THE ASME SECTION VIIl-01'-./. 1 ,APPENDIX 2 • rr p.t ® . . -- ~ YJ:) VALUES OF F,FL,V,VL,T,U,Y,Z,f,L,t,e F = .6990377 FL= .9016821 v = 8.531234E-02 VL= .1296357 T = 1.844895 u = 12.65552. ~ '. y = 11.51655 z = 5.942.374 f = 1 ' L = .774312 ' .. t = 5 e = 6.341799E-02. ·\ -.. -.. ~.,.;;_. . '. r ·o··· ' '' . . '.~."' . : ~ ·, ' . 0 .. l ~ ·~· ·; r . ;.r~ ,.. s-.s ztl-171l DESIGN OF BOLTS Bcetr LOAD WM1= 6134430 LBS FOR OPERATING CONDITION WM2= 0 LBS FOR GASI<ET SEATING REQUIRED BOLT AREA AM= 235.9396 IW'2· NO. OF BOLTS AND ITEM NO. NO .. 1 DIAMETER OF BOLTS 70 . .., ..... 3 4 5 6 BOLTS SELECTED 72 ·74 76 78 .. ao .. TABLE DIAMETi;R <IN> 2.250 2.250 2.25(1 2.250 2.250; . 2.250' 72 OF 2 ... 25 .. UNL. IliA.. .. BOLTS ... TOTAL BGLT AREA 239.6 246.5 253.3 260.1 267.0 273.8 Bo.L n ..S/AC/tl{j-.::0/Z:f~~ Jrlr fi~ : .il ,_.) .. ~;, ~A/. !t«l.l, ( Jprr. P.C:l R• ( 1~1· .. ~ -~~~)~ ~~'Y?-= ::1 ~· ?"-~ ~. 71""; ··;An~ R...t~Jr~ .)tSTA.Vfl! ( P. €) .t:: ('Zt-rt~r)lf.• ) . .l;r >l . ..,r i-h*· t"~ JJII7~it.-n~ (f.IJJ .... ~,. . .,.,,_..._...,,. . . . . ~· :: . - Ill~ _E~;-l"Jtltr:4. .. a7;Jf,,J tfi:' 14~,r. ~ ...rttt.J CA"'. ~ 1~ -s-s z,,_,,. ) . ' .. • C) . . . . @ . . ~ \J STRESSES IN FLANGE FLANGE MOMENT Ji-A~-.S -.S l~l-1111 JJOK. ~ /1t... CD~t~thT ,.A) Mo = MD + MT + MG OPERATING CONDITION Mo = CAm +~Abl * Sa * CC -G) I 4 GASKET SEATING FOR INTEGRAL TYPE AND.-LOOSE TYPE W/ HUB FLANGES LONGITUDINAL HUB ~TRESS SH = f * Mo I C L * fl ·" 2 * B1 RADIAL FLANGE STRESS. ·. · SR = (1.33 * t * e + 1) * Mo I CL * tA2 * BJ TANGENTIAL FLANGE STRESSES ST = Y * Mo I ct~2 * B)~ Z * SR FOR LOOSE TYPE W/0 HUB FLANGE ST .-Y *. Mo I <.t· .. 2 * B> SR = SH = O. . ·' OPERATING CONDITION LONGI.TUDINAL HUB. STRESS SH= 32908. 7 < J.t'~ • 4o...hll-,lU RADIAL FLANGE STRESS SR:, 21317 .AS.. < . .rf .,. .2"0o.• ,.._ TANGENTIAL FLANGE STRESS ST= 7031 .. 532 .. ~ -r'i=-. . . --·'<-'" ~·;• ·--·-.>;t-,~ .... ~ .. ,:........ ... , . GASKET SEATING. CONDl.TION ~­/' --~--------- LONGITUDINAL HUB~STRESS SH= 0 t ~-. .... . . . . f. ~ s,1• _,._s_k'r 7.] J I l ;J I . 7fliJ RADIAL FLANGE STRESS SR= O. TANGENTIAL FLANGE STRESS ST= 0 .. \ '· ... 0\II'R · S.r. r r /-II -~ :t > i' •. . i 'i ,. ' . . 0 @ . . . lr<fw-s-S?l ,_ 1 111 DESIGN INPUT OF FLANGE INTEGRAL FLANGE BOLT-CIRCLE DIAMETER C= 121.5 IN DIAMETER AT LOCATION OF GASKET LOAD REACTION G= 110.5 IN · INSIDE DIAMETER OF FLANGE B= 108 IN· OUTSIDE DIAMETER OF FLANGE A= 128 IN THICKNESS OF HUB AT BACK OF FLANG~ g 1= 3. 375 IN THICKNESS OF HUB AT SMALL END OF FLANGE go= 1.125 IN FLANGE THICKNESS t= 5 IN HUB LENGTH h= 10.5 IN ALLOWABLE BOLT STRESS AT AMBIENT TEMP. Sa= 41600 PSI ALLOWABLE BOLT STRESS'AT DESIGN TEMP. Sb= 41600 PSI DESIGN INTERNAL PRESSURE P= 845 PSI THIS IS A SELF-ENERGIZING GASKET THE FOLLOWING CALCULATION IS BASED' ON THE PROCEDUPE DESCRIBED IN. THE ASME, SECTION. Vtii-DIV. 1 ,APPENDIX 2 .. .-........... ·-----··~ ·-'"~'--. ... ·-~-· ... ···~·..,.,._,:,'•,, , ... ~." t-<;;M'··'f~ ... ~· .... . -~ rr 0 l ~ . @ ~ ~ 'l 'o~·~ .. : ~-. . - . . . ·. . ~ /$'"'~ -s-sz,,,.. 17 a / DESIGN OF BOLTS 8oLT LOAD ·-wM'f= 9776748. LBS FOR OPERATING CONDITION WM2= 0 LBS FOR GASI<ET SEATING REQUIRED BOLT AREA AM= 188 .. 0144 IN·-..2 NO. OF BOLTS AND DIAMETER TABLE ITEM NO. NQ .. OF~ BOLTS DIAME1ER <IN> TOTAL BOLT 1 70 2.250 239.6 2 72 2.000 190.9 \3 74 2.000 196.2 4 76 2.000 201.6 5 78 2 .. 000 206.9 6 80 2 .. 000' 212.2 7 82 1.87:5 188.9 ~~ ~ :-84 1 •. 875 193.5 9. eo..,. .1.875 198.:1. 10 88 .. ·1..8.75 202.8 11 9(1' 1.875 207.4 -. ..92;.c 12 1 .. 875 212.0 13. 94 1.875 216.6 14 96 1 ... 750 190.1 ..... 15. "9a. 1.750 194.0 16 1.100 1 .. 750 198.0 BOt. TS--· SELECTED. ,. __ .-... ·--~-·,__,;~·."-~ ~. ~-..... -. ..:-~-~··---:-~ ~·- 72 OF 2 (IN}. DIA:,.. BOLTs·· . . ~ ·~ f AREA .. ... . ,. ;, '"' --~ j ' . . ! ,) 0 . . . IPPro-~--.SC.,I-l?ll STRESSES IN F~ANGE Z:k~~Nr'f_ CC)NQ,(IoAJ FLANGE MOMENT Me = MD + MT + MG OPERATING CONDITION Me = <Am + Ab) * Sa * <C -G> I 4 GASKET SEATING -FOR INTEGRAL T-YPE AND LOOSE TYPE W/ HUB FLANGES LONGITUDINAL HUB STRESS SH = f * Me I <L * 41 A 2 •B> RADIAL FLANGE. STRESS SR = (1.33 * t * e + 1) * Me I CL * tA2 * B) TANGENTIAL FLANGE STRESSES ST = Y * Me I -(t""'2· * B>-Z * SR FOR LOOSE TYPE W/0 HUB FLANGE ST = Y * Me /(t....,2-*-B> SR :s SH = O. OPERATING COND!TION -----------------~ ,-· ·'-- . LONG.ITUOINAL. HUB STRESS . . . ( ... SH= 43449· .. 76 · < ~ ··/U1 f: :$ .. ARt;. /t.S'JI > .S"' ,u('l" I7 ) RADIAL FLANGE STRESS . SR= 28145.6.9 -· .. <: . .t"".p-<tttf.:t.:t-fl-1 TANGENTtAL FLANGE STRESS · sT:= 9283. s.1.2 · ', · ;~-< 4 ' . . · .. · ... ;. ... ,_.,,,.,· ... : /·~·.,.,., ~ ;.;,;,.~ ... '• ..... i GASKET_:~Tl~~~~~.:~~~-. ~(Sit+ .rj,):::. :ln'/7 /'JI ( S.J LONS'ITUOINAL HUB-S'T'RESS. ...• --~··'··.--··. ~··. ·SH= 0 . .··· RADIAL FLANGE-STRESS . SR=. 0 -~-....... ·«-· •... TANGENTIAL FLANGE STRESS \ ST= 0 f' ( Pllf. 0 ~l ~- DESIGN INPUT OF FLANGE INTEGRAL FLANGE · · /Scho-S -.s Z/1-/7 Jl /{YDIO-.'71!rr BOLT-CIRCLE DIAMETER C= 121.5 IN DIAMETER AT LOCATION OF GASKET LOAD REACTION G= 110.5 HJ INSIDE DIAMETER OF FLANGE 8: 108 IN OUTSIDE DIAMETER OF FLANGE A= 128 IN THICKNESS OF HUB· AT BACK OF FLANGE-gl~ 3.375 IN THICKNESS OF HUB AT SMALL END OF FLANGE go= 1. 125 H-1 FLANGE THICKNESS t= 5 I~ HUB LENGTH h= 10.5 IN ALLOWABLE BOLT STRESS AT AMBIENT TEMP. Sa= 75000 PSI ALLOWABLE BOLT STRESS AT DESIGN TEMP. Sb= 75000 PSI DESIGN INTERNAL PRESSURE P~ 960 PSI THIS IS A SELF~ERGIZING GASKET . ... ;;,._,_ •• <. '•; 4; THE FOLLOWING CALcULA.TIDK/IS BASED ON THE PROCEDURE QESCRIBED .IN THE ASME SECTION. VIIt'"'"DIV .. !,APPENDIX 2 l ' . ~. . ;_;. <. .. s. r<', @ ' . . @ . . -~:-_'<· DESIGN OF BOLTS /~he..-s-s z,,_ 178 H y D It 0 .. ..,.-,::.rr J8oL"T LOAD ~-WM1= 9201645 LBS FOR OPERATING CONDITION t~M2= 0 LBS FOR GASKET SEATING REQUIRED BOLT AREA AM= 122.6886 INA2 NO. OF BOLTS AND DIAMETER . -· ITEM NO. NO • OF. BOLTS 1 70 2 72 3° '14- 4 76 r 78 ...J 6 BO 7 82. l· 8 84 -9 .s6.: ..•.. ~ .. IO ee:· 11 90: , .. 12. ...• 92...''"'·;,.· 13 94·· . 14 96 15 . ---... 9a-~ 16 .• ,...100 ·1:7 ·~1()2:: .ta ,.~U04- 19' ··X.1Qb: 20· X.t Ol;f. ,:: _ 'BOLTS SELECTED TABLE DIAMETER (IN> loc750 1. 750 1.625 1.625 1 .• 625 1.625 - 1.625 1.625 1 ... o2s I.-500 .~ 1..-500 :, ... -·1 .. 500- 1.500 1.500 1 .. 500 1.500 -1 .. 500 L .. 500 1:.500 '1..3:75" 72 OF 1.75 CINI OIA. BOLTS ., . .I ... ,,·__..,._ -'•" 0 ~-.. . ;.• " TOTAL BOLT 138.6 142.6 124.3 127.7 131.0 134.4 137.8 141.1 ' 144.5 123.6 126.5 \129.3 132.1 134.9 137.7 140.5 143.3 146. 1 148.9 124.7 r r AREA -----------------~,------------""'--------------------- s: f ,_· ·. _j . ! ;. .. I . 1 j ·1 l 0 @ . . 0 . . STRESSES IN FLANGE I ~cf'Oo-s-Sl61-J/8 H'flJR6-?erT FLANGE MOMENT Mo = MD + MT + MG OPERATING CONDITION Mo = CAm + Ab> * Sa * CC -G> I 4 GASKET SEATING FOR INTEGRAL TYPE AND LOOSE TYPE W/ HUB FLANGES LONGITUDINAL HUB STRESS SH = f * Mo I <L * 01 A 2 *B} RADIAL FLANGE STRESS ¢ -. . SR = < 1. 33 * t * e-+ 1> * Mo I CL * t·''2 * B) TANGENTIAL FLANGE STRESSES.· ST ~ Y * Mo I (tA2 * B>-Z * SR FOR LOOSE TYPE W/0 HUB FLANGE sr = v * MQ./(tAz * Bl SR = SH = O • .. -.· .,,_ .. · ........... : ,_ _ _.._:"".~~--,~· .. ).-;.-, .. ~· -~~---~:.:.._. ___ ~ ,, ....... • ~ ' OPERATING• CONDITION . . I --~--~- LO~~:T~~~~~:o~UB ~R'~ f'JJ ( (JJ1; S'y • .Jilvt~ /. r-S( ) j 1 ) RADIAL FLANGE. STRESS , SR=. 31976.17. ·<-S, _..~'Prf TANGENTIAL FLANGE STRESS ' . ST= 10547 .. 28 -~ P'-f . . ___ }·;._j ~ ••... ~:, ;"'~ .... '~-..... ,. GASKET SEAT lNG CONDIT I ON· -----. -. _;_ __ . LONGITUDINALHUB~STRESS SH= 0· -.:: RADIAL FLANGE STRESS .. SR= 0 . ~-... .. TANGENTIAL FLANGE STRESS __ ST: o· : -~ '. · ·=-~··c ~ -~~ .... ..;~ .... : .. \ .~:'*."·':"'._.~.·,.. ~--: .. 1 -.o~:'.-.;;:.-.. ,;_._ -'.' .. ·.·'·- ~ -.. ~ .-_ ..... iiOI• ...... ···~---"'. J<' .... ~-... :-.., r r /)./? ' ; ~ j) \ DESIGN INPUT OF FLANGE INTEGRAL FLANGE 1 r_~-s-s 2.1.1-l?~t li?>cUT/1'1lNI(f._ Cf"u'i'W Mf'r If .Jl::-J/4,.; COIV/J(TiuJ, 11~ ·f'"IJt. ftr!fJ?lt.c·ifl.c: a..vz.r_ BOLT-CIRCLE DIAMETER C= 121.5 IN DIANETER AT LOCATION OF GASKET LOAD REACTION G= 110.5 IN INSIDE DIAMETER OF FLANGE B=-108 IN OUTSIDE DIAMETER OF FLANGe A= 128 IN TH I CI<NESS OF HUB AT BACK OF FLANGE .. g 1::. 3. 375 IN THICKNESS OF. HUB AT SMALL END OF FLANGE go~ 1.125 IN FLANGE THICKNESS t= 5 I~ HUB LENGTH h= 10.5 IN ALLOWABLE BOLT STRESS AT AMBIENT TEMP. Sa= 52000 PSI ALLOWABLE BOLT STRESS AT DESIGN TEMP. Sb= 52000 PSI DESIGN INTERNAl. PRESSURE P=10.2Q., PSI THIS IS A SELF-ENERGIZING GASKET THE FOLLOW!Np CALCULATION-IS BASED ON THE PROCEDURE DESCRIBED IN\ THE ASME SECTION..VIlL-DIV-.. 1 ,APPENDIX 2 . r ' . r ~-------~~----------------~--~-~---~-------~------------------------------------~ . .. .. ~.· . ; ·. --·· ,"' -,~ : . - () } / r7':\ \;.9 ~?]·:-_'· '·.•.' ,' ~ '~- ·..J DESIGN OF BOLTS 13o.L'1" LOAD WMl= 8099365 LBS FOR OPERATING CONDITION WM2= 0 LBS FOR GASKET SEATING REQUIRED BOLT AREA AM= 194 .. 6963 IN-"'2, -. ., : NO. OF BOLTS ' ITEM No.- 1 2 3 4 5 .. o.. 7 .a <·---9' .• -' 1.0 :. ·tt 12. 1S: AND DIAMETER TABLE NO~---OF SOL TS D-IAMETER <IN) ,70 2.250 72 2 .. 250. 74-2 .. 000 76 2.000 78 2.000 ao · .2 .. 000. 82 ''·2 .. 000 84_ 'i,o:, ,''>:'2;,.000 --~·~·•··" <·"'··--""'"r" ~.t...S7S,- ..···!t~--"'~2H~ .. 94 ' 1..,875 .. ··· BOLTS SELECTED~·· ._ ... ~ · ... ~~-~ ,.~ ~ 72 OF Z.2S c:t.N} DIA. BOLTS .; - TOTAL BOLT AREA 239.6 246.5 196.2 201.6 206.9 212.2 217.5 222.8 198.1 202.8 207.4 212.0 216.6 -.). ' r r f· ') -' '. ~--'• > .• -.. 0 . ' ® . . . . i i 'l () . . STRESSES IN FLANGE FLANGE MOMENT . I It~-s-.r l4J-1711 C'?('t.(!l p 71 WJrt. C;oA/IJ J'r·,u.J Mo = MD + MT + MG OPERATING CONDITION Mo = <Am + Ab) * Sa * <C -G) I 4 GASKET SEATING FOR INTEGRAL TYPEAND LOOSE TYPE WI HUB FLANGES LONGITUDINAL HUB STRESS . SH = f * Mo I < L * 91 ·" 2 *B~ RADIAL FLANGE STRESS .. SR = .<1 • 33 * t * e + 1> * Mo I < L * t ""2 * E: i TANGENTIAL FLANGE STRESSES ST= Y * Mo I <t""2 * B}-Z * SR FOR LOOSE TYPE WIO HUB FLANGE . ST ;::: Y * Mo /.Lt""2· * B.l SR =-' SH =-0. - •'• ,::: . .;· •' . . " _· -.. -."~ :_~.'':' .-.,.,~ .. ~ ...... ;-., ., ... ':~-·<r:·;~~;_·; --~~-~'":-"~~::.-{-:~·:· OPERATING CONDITION- ---~-------~-;; ~ --·· . ' .... LONGITUDINAL .HUB .. S:tRESS .. SH= 52448 .. 24 · RADIAL FLANGE STRESS SR= 33974 .. 68 .... TANGENTIAL F~ANGE STRESS ST.= 112oo;,.s· GASKET SEATING CONDITION. -------.;.... ~-~----\;". • . f . . . . ·. LONGITUDINAL. HuB. STRESS. ... ··-·· .... -··· ... SH= 0. . . ., ·. RADIAL FLANGE STRESS. '-. . .. SR= . 0. • , . . . •. . TANGENTIAL FLANGE.STRESS' ST:r() . '. rr ·~ , -.; ·,' 65010.64 fFRONTI CLIENT S. PROJECT STONE e;. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE ALASkA ?>o~Afl?:r< ;w Tff6A. ,rr --BRA6Lc:r Llti<E CALCULATION TITLE (Indicative of the Objective): LQCAL ._ji"JN;!J '()(jl; to 71ft: ($~1-f(;~Y JJlJ (l,>IJ T"l NU I rf" A7 te ~Ll 0 Cf?tJ AAJU J..a I r-tr~jj /fj-LIJ OW\ . CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. DIVISION 6. GROUP CALC. NO. TASK CODE /~3ln s J Z&.l-17C * APPROVALS-SIGNATURE 6. DATE REV. NO. INDEPENDENT OR NEW PAGE 1 OF zq QA CATEGORY (.J) 0 I-NUCLEAR SAFETY RELATED OII om ~ J.l rJ)I{ OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. * REQUIRED ( v1 PREPARER (S)/DATE (S) REVIEWER(S)/DATE (S) REVIEWER(S)/DATE(S) CALC NO. OR REV. NO. YES NO \. (.l c fij, f~--~ a ./ #'_{."~· /1,;11'1 /(JIJ<..Jk II ~;A /o-{-"3Z t/ :V/Y) ' ' r DISTRIBUTION* I I COPY I I COPY GROUP I NAME e;. LOCATION I SENT GROUP I NAME 6. LOCATION I SENT I (v') I I (v') RECORDS MGT. I JoB B~,, I 1/ I I FILES (OR Fl RE I I v I I FILE IF NONE) I f:tu-,CriE " I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ! I I J 0 . 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 0 21 ,. 22 23 24 25 26 27 28 29 30 31 32 33 i . ' 34 35 36 37 38 "' ! 39 • ' j 40 41 0 42 43 44 45 46 45010 65 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. /r~ DIVISION & GROUP .s CALCULATION NO. OPTIONAL TASK CODE SZ61,... 17c OIUC-c:Tl vt' ~ CA-I..t:u~rt.:J <:;,4l CU(,.,.tcJV j..,/t;"7'i'tw'a / kt..ltiHjJ(I,p.} J lti!'FPttG~~ C C 01/"C L. US/ uJ S :tJTFJI'I./ :J;"/t/ft;~IJ.Ir(.. ?~.!!(}~~ & C/tLC.ULATtoAis- (·I p:tJ/(HCJI:A'S ·~ '11-lr:: ux::Ai.l2t'JJ STtrf?4ffi AT T#l: fiJ~t~Cr,IMI OF 0>~ ..wv cru;JI}t.>lt . I -t ,;.." _ 6 · Z.. /'-11 "ro-ttt:-J /SeND LOUL. S7'Jtt-lj ' • 3 l(r...OUC.t?~ t O(t M... S7llC'~1 PAGE~ I P~C- I ~-7 17-2~ j ·' .. ., . ' ' j CALCULATION SUMMARY STONE & WEBSTER ENGINEERING CORPORATION 1.1.0./W. 0./CALCULATION NO. .sow62 /S"<flt1o-.S-SZ~I-17C CLIINT /PRO.IICT AlA-lKI\ ffl£./l?l< M11#o~tTY-1114/JlEY LAK.c RIVIIION 0 QA CATI80RY I COOl CLASS '-~ lA ~-........ .• , SUI.IICT /TITLI "--.. , Laut ..n-kt:Jr );m;; "'To TJ.Jt: 6.r"' .·-/iJ...!rt:uJ7>uui1"Y AT /?C.ilftFt ltvil ,Mnzytt;j) t;l81}t.) 0 OI.IICTIVI 0' CALCULATION TO CMcutAlF 711£ L ~II<. S71UJ!l .JJ f/7; T6 tS'Eo~ttr-r-tr /Jt.st:cltf7tll()t rY /IT it:/)(Jlt"-1(1 All'[) M 11'1!tf!-b t:'l/U-..J ( CALCULATION MITHOO/AISUMPTIONI r#E (AAr;~r J)JSC()"nuu,rt' AI ~~~ AtJJ) ,.,.,IC'ttb c:Le•-.v orJ Htrvf!' -,.n: Lur:.Maru .:rtttesu;:J. AT Tl~:::tu·vc"'rV HP-~. 711E' '}>.ttJtf!"'.o(J((e J 7i'f(.nlt;lJ ,;.~ J>. · 23 & . ti"f ftt:f 2 IJ (11'F'i) Tb c,ft.cutKl'li 711f!':!.T ..DI.SCOi/TIMJirf' S7fit .. U~·f'. 71f£ PJ~ktJJ./H / FtJ'1 ReF'· 2 J . .S '1'~~1./fT'..V nJ 7/f£' sr::c(IUA/ elF cAl Ctlt.ltft l.l~. /rl!FT:~Et.llfff: _ (IJ ..S,1£(!(. Lf/IAP~ AMl ~~~.srrJcl{ -Srn()C71JMI.. l;)'I?J/611 C~ITf:ti:.t~ Po~ A-lA--!1(~ f()l.../l:!R. ~nr" PWI.Ef LA'Kfi ur~· r:t.Gr:'Tttc ~ /ftE.Ja-cr. (2 J / J>/?t?!.!uHc. YesJ& J:JGJ1W //AJ.IllBD¥1< 'nr II· fl. k~.>tw~~. vA,(J N'OJ..TI!AAti:J ~etN/1-oLb Coi-f /Ait!J'_~ z ~JD 'fflJI77 t>N _. 1 <l JlC 81 ra.w o~. t.ti~-Fs-161 p-1 (...J) J'tW OW4 l!'rt--F!-Z,I J-1 cJ-; s~ .M ~~-Ft-'ZI.ta-r CONCLUSIONS ' LocJH../1/?a Sjttes e1 'N ;-nrr; ttc=JJu ct?K.J.~ ANd--ri-lE MtTr:er:-lJ 1!6'111'/lJ uJz;:L) 1 N Jln; pt:-IJ.rtoek. dF TfflJ '(!t'!}T<T .-fJU: All... khTI/1,./ Tilt' A-t..LilJAt~Jtc:-t. RIEVIIWIER (S) COIIMINTI RIVIIWIIt /CH~!(IER /) M.,........., t'.,_..,. -- INOIPIENOINT RIVIIWIIt DATI I ~ to-o-...,.0 DATI' I ' ' • . I . ; . 'l ' ('. ........ ~- 0 2 3 4 5 6 7 8 9 tO II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET 65010 65 CALCULATION IDENTIFICATION NUMBER PAGE 4 J.O. OR W.O. NO. I DIVISION Ei GROUP I CALCULATION NO. !OPTIONAL TASK CODE ~~ .5 S Zl:./-)7(. (R.rn::: ... t) JHr; .ltfE)( CoNE ltlfl.tE d"F T/lr: ,._~ucc-( lo /Jc AN-+t.r:zc-u I ( L(f-{s TJM.Iol 1 ~ (J /b.ll) · TifE /3"G-i/ij ~A-~ IUS r:::;rr:., TftfC ~v~,n:tec-IJ ST1tL. J.IA4/1F L·ol:,/K. .t77tfiJ!E'J AT --r{lt;.rr;;,. G&o.._,r, 1"-J J:JtJCOA/itNvtne-r. 7/lfltfi'f.olte • "THE f, ~S [INfi.S. TliF HGblllt7f.; ML"""-lttlli....E ...S?fr(:;f;t-! E'l'ff.R'W'r (pH) 7¥.9 2.) I f.IYDR.o-7BT fo.JJ-s:sy) ClnJ r I .~ ·-_.' . ·,I .... . -1 ' - i ': . -. ~ ·-i ' . I -.. .. ' ) ~ . . ·; ' I ' ~ l --~ ---~----------·--~-----·--------------~~ C· . 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 c~~ 20 2 I 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 0 42 43 44 45 46 65010 85 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. 1r~ I DIVISION & GROUP I CALCULATION NO. 'OPTIONAL TASK CODE s 521:./-/7C PAGE~ li{E .J'Jl;S/6,.) IIJ7!?1fA/k'L 'J#i!H-UIIl._l;f FOI?' TH£ /el?JJU(fiRS hvz.l 7Hti /rl1"TE"1t£lj ~~.v& 7D ~ 'ANI+Lr.?t?'4 NM.H,C.. ( p!{ ) '!:: ~ t-Ui r.:l./ c.'( (p11) -t-'~ ~ A--! Td LL() l-<.1/A/f t ~ .)( /?KCC? jJf/.J~V ¥1.- ( f'JI J ~ 71/lt JJ JII1T A-or?j/',./ eMF A--NY lltdltC , ]~es CfLCULA T[:.iJ ~ THIJ COII'IJtTNhJ ,Aff<::-PIR JiJF~~MA7u.)IJ. --·-------------------------------·------------~---------------------------. -----· ~------------------------------.. ·. ~----·--·-.. -~ ·--~ ·----~--~----~..........__.......__.._~--~--~------'-----------·-----------·--·'--~-··· _______ .._. ___________ . ----~---o. ~---~---· .. -·---·--·---·--~-~ .. ··'"'. ' -~ ·.! .. ' .. ·~ I 1 ~ c) (~; 0 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010.65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION Ei GROUP s CALCULATION NO. OPTIONAL TASK CODE PAGE~ SchiJ .5'2/./ -/7C ( ~C,f. l) T/lr: ~MUlA sNoW# a!oi AP1t7 j>ll6ti 1s AAi ANI+tYf/r ~ 7HT; lgelflt ;t:.IJ S'l'N"-JSF--! .ItT THE ~-CYI.tl/r.~ ]oWlitu~. IU?pC.Ittur/f.. TltE ~ IJirt{ A,tu ~Utl/~t-t.ravr· crLtMIZ'~ AI: 111£ J'UvtTttJII) po'N'T' CIAIIJ1J~ f'N~.!f,w-tr,UA.J. (scr F14 fJU-.JJ Tilfl~Fol£> 7flt; F&~HtJLAS" SltO£JN oJJ /1/i'Xr PA6t ClfN /)t; (J!r?IJ ro ~LcoLA-~ -rttr Loc+<-s-rM;-.ss~ rol? Rr:JJvct?l( l'rJJc) ~I 1z./tf"..J /J {;fo/J · r Fig. 8.7. Unit edge load diagram at cone-cylinder junction. C·· . ) 0 0 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010 65 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. /~60 DIVISION €i GROUP I CALCULATION NO. OPTIONAL TASK CODE 0 .S~i-1-17C. T.W. 1.3. S1NMI at ~nder Junc:tuns.~ M= external moment at juncture W= weight at juncture D = 2R or 2R$ t, t $ = corroded shell thickness Positive (plus) sign means tension. The upper sign specifies the stress on the outside surf ace. -n.. t (,<)1/E It: crct. P ~ "P + (41/D), equivalent pressure for longitudinal stress. I= t(4M/wD2 )-(11'/•D), unit longitudinalload,lb/in. Juncture L Combined stress in cylinder. longitudinal: membrane tangential: Combined stress in cone. longitudinal: membrane tangential: JunctureS Combined stress in cylinder. longitudinal: membrane tangential: Combined stress in cone. longitudinal: membrane tangential: P~R( O.S 0) 0£"'-----+ u - t ncosa t orm = PR (-l _ P~ y, f'!.) t ncosa P Vt II': - / J!!:L t:. a~-t '")1~1. )(a ~"' Vt. ~o(_ y = /, 21-r c 'Vt .. ~;, j .z;. t6C... PAGEL "' ~ -1< (14 'rJ 2.(1-t ~It.,))/( i 'rt (/.+ ~ ~ 2n 1 -1-2 i.,. '1.+ 2 tt ~1. } ~ ~ ~ n [ t + 111 ( 'YI ..._o] /€1-C ~ w1 + 1)) I u z X/nz. _, -4 ::::[~e<)/W'I] r -~--·----~-----------~--------------,--~-----------~----·----~-----------~-------------·--------------..--._._ ....... _______________ ·----- . ~. •, ·,, ' ~ ' • j \ . . I .. , . i '1 c·· ,/ c·,, C-\ 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 65010.65 STONE S. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. DIVISION & GROUP ·s CALCULATION NO. OPTIONAL TASK CODE ".26 .f-17C /~cfoo lefuLT1 SJfrl~iJ or/ p. 9-v/2 R. GJ U L TJ .51-f o \.J 1.J rf)J I? 11 "'" ,, ' I I /)ot NT A Clt/J 16 I I I ~ ~~ ~.Stilr~ A--f ...L 4.81r',., CMF:Ii {: !3.lc,t" CASC ~z. i>t·.. ll'-O ... ~,. CM~ ., 1), ·.. ~ ~," -ft.,. C.trr' •t f t I· ~ ... JJ'-o.,. ft.. r~.-,. I j)t=-G!..c' if-c~·~ PAGE_!_ .. •' ' . I . . : .J ". ' .. i i .! 15800-S-5261 17C DESIGN INPUT ( (.A1£' :Ill) ~·-----------: \ LARGER CYLINDER THICKNESS = 1.250 IN SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = ALLOWABLE STRESS SA = 1.250 IN 1. 250 IN 640.0 0 0 0 0 45.00 STRESSES AT JUNCTURE L (AT poJt.JT A) () ... --"" COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL== ·4.67 KSI OUTSIDE SL= 29.44 KSI INSIDE TANGENTIAL: SC= 23.58 KSI OUTSIDE SC= 31.01 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 4.73 I<SI OUTSIDE SL= 29.50 KSI INSIDE TANGENTIAL: SC= 23.70 I<SI OUTSIDE SC= 31.13 I<SI INSIDE STRESSES AT JUNCTURE s (AT ]JOI~ .8) ---------------------- C' 1 } COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 29.44 KSI OUTSIDE SL= 4.67 KSI INSIDE TANGENTIAL: SC= 37.21 KSI OUTSIDE SC= 44.6~ I<SI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 29.50 KSI OUTSIDE SL= 4.73 KSI INSIDE TANGENTIAL: SC= 37.34 KSI OUTSIDE SC= 44.76 I<SI INSIDE MEAN RADIUS = 66.62 MEAN RADIUS = 66.62 HALF APEX ANGLE= 4.88 PSI..,_ Noll N<i '-C()AI/) I 1'"1 tJ JoJ IN-v IN-LBS LBS LBS KSI r IN IN DEG •· . ,.,, . . l ' ' . :,..; ~' ~ "' ; .. ~ -.: . l ' ,~! '4 ., l i ~ .. '"' ·. "l . " 1 .: J ) ! I tibOO-S-5261 17C DESIGN INPUT ( (~11 /) o~~~~;~-~~~INDER THICKNESS = 1. 250 IN . SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = 1. 250 IN WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = ALLOWABLE STRESS SA = 1. 250 845.0 IN (l 0 (l 0 74.90 STRESSES AT JUNCTURE L (A( pr.>1"'7 1\) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 6. 17 KSI OUTSIDE SL= 38.87 I<SI INSIDE TANGENTIAL: SC= 31.13 KSI OUTSIDE SC= 40.94 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 6.25 KSI OUTSIDE ("' SL= 38.95 KSI INSIDE . . \ TANGENTIAL: ' / SC= 31.29 I<SI OUTSIDE ·"' SC= 41. 10 KSI INSIDE STRESSES AT JUNCTURE S ( ,t;; 'jlcii'/'T 8) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 38.87 KSI OUTSIDE SL= 6.17 KSI INSIDE TANGENTIAL: SC= 49.13 KSI OUTSIDE SC= 58.94 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 38.95 I<SI OUTSIDE SL= 6.25 KSI INSIDE TANGENTIAL: SC= 49.29 r.::si OUTSIDE SC= 59.10 KSI INSIDE f;~ADIUS = RADIUS = APEX ANGLE= .. r 66.62 IN 66.62 IN 4.88 DEG Alt. JrlfE;t~s l r?JJ J7;MI 7</ 9/(JJ .. •' ( "' . -~ ,. .. ·. ; .. ' •.• ,.4 ... " ' : .i . ' .. ~ ; ~ 15800-S-5261 17C DESIGN INPUT ( t~ Z/1) o-~~~~~~-~~~INDER THICKNESS = ,-SMALLER CYLINDER THICKNESS= 1.250 IN 1. 250 IN = 1. 250 CONE SECTION THICKNESS DESIGN INTERNAL PRESSURE EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = IN WEIGHT AT· JUNCTURE L = WEIGHT AT JUNCTURE S = 0 0 0 0 ALLOWABLE STRESS SA = 90.00 STRESSES AT JUNCTURE L ( pt;IM; AJ COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 7.44 KSI ·OUTSIDE SL= 46.92 KSI INSIDE TANGENTIAL: SC= 37.58 KSI OUTSIDE SC=. 49.42 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 7.54 KSI OUTSIDE ('• SL= 47.02 KSI INSIDE l TANGENTIAL: ~-SC= 37.78 KSI OUTSIDE SC= 49.61 KSI INSIDE STRESSES AT JUNCTURE S ( PtJ 11{7" 6 J ---------------------- COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 46.92 KSI OUTSIDE SL= 7.44 KSI INSIDE TANGENTIAL: SC= 59.31 KSI OUTSIDE SC= 71. 15 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 47.02 KSI OUTSIDE SL= 7.54 KSI INSIDE TANGENTIAL: SC= 59.50 KSI OUTSIDE SC= 71.34 I<SI INSIDE (J MEAN RADIUS = 66.62 IN MEAN RADIUS = 66.62 IN HALF APEX ANGLE= 4.88 DEG PSI....---ld<CC: 'fT'"'''Jir'-(;JJ~tl 'T7 f>Ai IN-LBS IN-LBS )J6'T ,+ lfl?flti~o.J CuA/D t7 1 JA) • LBS L B S J=. R. )(, {:'f l?1t t'J./Ui' 0 ~ L y KSI r .. -' . ' . ' . ' . . ' ' j~;-~-s-.s 261-17<-f /2.. DESIGN INPUT C A1f "'I LAHGER CYLINDER THIC~::NESS 1" 25(> IN SMALLEI::;: CYLINDER THID<NESS= 1. 250 IN ·) CONE SECTION THICI<NESS ::::: 1. 250 IN c~--- (~) DESIGN INTERNAL PRESSURE ·-960.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOI'1ENT AT JUNC s = 0 WEIGHT AT JUNCTURE L = (l WEIGHT AT JUNCTURE s = 0 ALLOWABLE STRESS SA = 63.00 STRESSES AT JUNCTURE L COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 6.99 I<SI OUTSIDE SL= 44. 18 ~<SI INSIDE TANGENTIAL: SC= 35.35 I<SI OUTSIDE SC= 46.51 I<SI INSIDE COI'1BINED STRESSES IN CONE: LONGITUDINAL: SL= 7.08 r<S I OUTSIDE SL=. 44.27 KSI INSIDE TANGENTIAL: SC= 35.54 KSI OUTSIDE SC= 46.69 KSI INSIDE STRESSES AT JUNCTURE S ( pourr 11) COMBINED STRESSES IN CYLINDER: LONGITUDINAL; SL= 44.18 KSI OUTSIDE SL= 6.99 KSI INSIDE TANGENTIAL: SC= 55.82 KSI OUTSIDE SC= 66.98 t<::SI INSIDE . COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 44.27 KSI OUTSIDE SL= 7.08 KSI INSIDE TANGENTIAL: SC= 56.01 KSI OUTSIDE SC= 67.16 KSI INSIDE~ 1'1EAN RADIUS = 66.62 IN MEAN RADIUS = 66.62 IN HALF APEX ANGLE= 4.88 DEG PSI IN-LBS IN-LBS LBS I-I ret. o · TcJ T LBS r(S I ( .. -:_: ~ ... - " . . "" . . .. ~ " " ." . . . "' "• 'I '· .. ~. ' ' I ' ' . ~ J -'l 15800-S-5261 17C /_DESIGN INPUT ( (kST: # l.) ~ ~~;~~~~-~;~INDER THICKNESS = SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = ALLOWABLE STRESS SA = STRESSES AT JUNCTURE L 1. 000 IN 1. 000 IN 1.000 IN 640.0 0 0 0 0 45.00 COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -9.03 I<SI SL= 34.31 KSI TANGENTIAL: SC= 6.85 KSI SC= 19.85 KSI COMBINED STRESSES IN CONE: LONGITUDINAL: SL= -8.69 I<SI SL= 34.66 KSI TANGENTIAL: SC.,;, 7.54 KSI SC= 20.54 KSI OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE STRESSES AT JUNCTURE S c f011'/T /J) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 34.31 KSI OUTSIDE SL= -9.03 KSI INSIDE TANGENTIAL: SC= 30.71 KSI OUTSIDE SC= 43.71 KSI INSIDE COMBINED STRESSES IN CONE: • LONGITUDINAL: SL= 34.66 KSI OUTSIDE SL= -8.69 KSI INSIDE TANGENTIAL: SC= 31.40 KSI OUTSIDE SC= 44.40 KSI INSIDE MEAN RADIUS = 39.50 IN MEAN RADIUS = 39.50 IN HALF APEX ANGLE= 13.24 DEG PSI IN-LBS IN-LBS LBS LBS I<SI r :·' . i ·; i 15800-S-5261 17C ~DESIGN INPUT ( (.SF ~2.) ( :~;~~;~-~~~INDER THICKNESS = 1. 000 IN SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = 1. 000 IN 1.000 IN 845.0 0 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE S = 0 ALLOWABLE STRESS SA = 74.90 COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -11.92 f<SI OUTSIDE SL= 45.30 I<SI INSIDE TANGENTIAL: SC= 9.05 KSI OUTSIDE SC= 26.21 I<SI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= -11.47 f<SI OUTSIDE SL= 45.76 I<SI INSIDE TANGENTIAL: SC= 9.96 KSI OUTSIDE SC= 27.12 KSI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 45.30 KSI OUTSIDE SL= -11.92 KSI INSIDE TANGENTIAL: SC= 40.55 f<SI OUTSIDE SC= 57.71 I<SI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 45.76 KSI SL= -11.47 KSI TANGENTIAL: SC= 41.46 I<Sl SC= 58.62 I<SI OUTSIDE INSIDE ~· OUTSIDE INSIDE MEAN RADIUS = 39.50 IN MEAN RADIUS = 39.50 IN HALF APEX ANGLE= 13.24 DEG PS IN-LBS IN-LBS LBS LBS KSI r 15800-S-5261 17C DESIGN INPUT C;ofJC :IJ 2 ~J~~~~~~-~~~INDER THICKNESS = 1.000 IN , SMALLER CYLINDER THICKNESS= 1.000 IN CONE SECTION THICKNESS = 1.000 IN DESIGN INTERNAL PRESSURE = %1020.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L • 0 WEIGHT AT JUNCTURE S = 0 ALLOWABLE STRESS SA=, 90.00 STRESSES AT JUNCTURE L ( flO 111/i A ) 0- COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -14.39 KSI OUTSIDE SL= 54.68 KSI INSIDE TANGENTIAL: SC= 10.92 KSI OUTSIDE SC= 31.64 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL--13.84 KSI SL= 55.23 KSI TANGENTIAL: SC= 12 .. 02 KSI SC= 32.. 74 KSI OUTSIDE INSIDE OUTSIDE INSIDE STRESSES AT JUNCTURE S 0 COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 54.68 KSI OUTSIDE SL= -14.39 KSI INSIDE TANGENTIAL: SC= 48.94 KSI OUTSIDE sc~ 69.66 KSI INSIDE COMBINED STRESSES IN CONE: ·LONGITUDINAL: SL= ·55.23 KSI SL= -13.84 KSI TANGENTIAL: sc .... 50.04KSI SC= 70.76 KSI OUTSIDE INSIDE OUTSIDE INSIDE MEAN RADII)S = MEAN RADIUS = HALF APEX ANGLE; PSI IN-LBS IN-LBS LBS 39.50 IN 39.50 IN 13.24 DEG LBS · KSI...,..__ J../UT A !Jl!;..f/o/\1 c()I..IJJtr, u ,J, ~ RFft:-IUtat:!' 5.vlr, r .. J .. ' /'5 PcJo-s-s 2.~1-17t:.. ::ll; DESIGN INPUT [~'f" 1., ------------0 ..... "_ ..... LARGER CYLINDER THICKNESS = 1.000 IN SMALLER CYLINDER THICKNESS= 1.000 IN CONE SECTION THICKNESS = 1.000 IN DESIGN INTERNAL PRESSURE = 960.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE S = 0 ALLOWABLE STRESS SA = 63.00 STRESSES AT JUNCTURE L c~ l COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -13.55 KSI OUTSIDE SL= 51.47 t<SI INSIDE TANGENTIAL: SC= 10.28 KSI OUTSIDE SC= 29.78 I<SI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= -13.03 KSI OUTSIDE SL= 51.98 KSI INSIDE TANGENTIAL: SC= 11.31 KSI OUTSIDE · SC= 30.81 I<SI INSIDE STRESSES AT JUNCTURE S ~ v COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 51.47 KSI OUTSIDE SL= -13.55 KSI INSIDE TANGENTIAL: SC:: 46.06 KSI OUTSIDE SC• 65.56 KSI INSIDE ' COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 51.98 KSI OUTSIDE SL= -13.03 KSI INSIDE TANGENTIAL: SC=· 47.10 KSI OUTSIDE SC• 66.60 KSI INSI.DE { '•" ' I· I RADIUS = 39.50 IN RADIUS = 39.50 IN APEX ANGLE= 13.24 DEG '·- . ~ . \ . .,· ~ 2 j 3 4 . ~ 5 • ., 8 !t 10 II 12 13 14 IS 16 17 II l!t () 20 21 u u 24 25 2& 27 21 2!t 30 31 3Z 33 34 35 3a 37 38 3!t 40 41 0 42 43 44 u 46 J.O. OR W.O. NO • /~&'Do STONE & WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP CALCULATION NO. OPTIONAL TASK CODE .s Se61-17C - 6 -3 ·lRIJdCt?f?. I L()(:kt_ ~Kf:-r!c:-1- CA:f'l! :at I_ ~~·+tt'l• .. A ----L~ z.6~s· ~r 'L---...1----~----- PAGE.l.2. -~ . 1t __ --r/fl1 ",PoaJwJ..I/It1_ .{JE.9J _f3,CJAI.tFIIH~ t.ri' CAt-c. IS'&"o• -S"-.I2(J-I7 • . -:"..i"nl?S!_..AM\c.t .llJ rJF: _ ~~ -pi?'II17U'CI( ~-8 ~IIC.H •. ·-r 't::.l~ s.flll.• ' -r--...-----a • .. -·-----------·-.. ---· ·-- ; .·, l ' . ~ ' DESIGN INPUT (A,it!df r-0; --~~~~~~-~~~INDER THICKNESS = 2. 000 IN ~~~) SMALLER CYLINDER THICKNESS= 1.000 IN CONE SECTION THICKNESS = 2.000 IN MEAN RADIUS = MEAN RADIUS = HALF APEX ANGLE= DESIGN INTERNAL PRESSURE = 640.0 EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = 0 IN-LBS 54.00 IN 45.50 IN 10.30 DEG WEIGHT AT JUNCTURE L = 0 ~~-=L~S 0 LBS 1/tJRJA~/r<. C() ;JJ), i lfh-.1 CJ WEIGHT AT JUNCTURE S == 0 LBS ALLOWABLE STRESS SA = 4:5.00 KSI +-- STRESSES AT JUNCTURE L ( liltt) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -0.85 KSI OUTSIDE SL= 18.13 KSI INSIDE TANGENTIAL: SC= 9.21 KSI OUTSIDE SC= 14.90 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= -0.70 KSI OUTSIDE SL= 18.27 KSI IN.SIDE TANGENTIAL: SC= 9.50 KSI OUTSIDE SC= 15.19 KSl INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: ( ptuwr A) LONGITUDINAL: SL= 33.67 KSI OUTSIDE SL= -4.55 KSI INSIDE TANGENTIAL: SC= 30.62 KSI OUTSIDE SC= 42.08 KSI INSIDE <4~t11 COMBINED STRESSES IN CONE: (II/A) LONGITUDINAL: SL= 12.18 KSI OUTSIDE SL= 2.62 KSI INSIDE TANGENTIAL: SC= 20.60 KSI OUTSIDE SC= 23.46 KSI INSIDE 0 r .. . ,. (J /tlvu-s-.s 2ti-17C. DESIGN INPUT LARGER CYLINDER THICKNESS = 2.000 IN SMALLER CYLINDER THICKNESS= 1.000 IN CONE SECTION THICKNESS = 2.000 IN DESIGN INTERNAL PRESSURE = 845.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE S = 0 ALLOWABLE STRESS SA = 74.90 STRESSES AT JUNCTURE L (filA) COMBINED STRESSES IN. CYLINDER: LONGITUDINAL: SL= -1.12 KSI OUTSIDE SL= 23.93 KSI INSIDE TANGENTIAL: SC= 12.17 KSI OUTSIDE SC= -19. 68 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= ~0.93 KSI OUTSIDE SL== 24.12 KSI INSIDE TANGENTIAL: SC= 12.54 KSI OUTSIDE SC= 20.05 I<SI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER:( f1Nr A) LONGITUDINAL: SL= 44.45 KSI OUTSIDE SL= -6.00 KSI INSIDE TANGENTIAL: sc ... 40.43 KSI OUTSIDE RADIUS = 54.00 IN RADIUS = 45.50 IN APEX ANGLE= 10.30 DEG SC= 55.56 KSI INSIDE < ;~ f7 ICJI r COMBINED STRESSES IN CONE: (!llt'fJ LONGITUDINAL: SL= 16.08 KSI OUTSIDE SL= 3.46 KSI INSIDE TANGENTIAL: SC= 27.20 KSI OUTSIDE SC= 30.98 KSI INSIDE 0 . . 0 \ .... ·~.·_) 0 DESIGN INPUT C~ M I LARGER CYLINDER THICKNESS = 2.000 IN SMALLER CYLINDER THICKNESS= 1.000 IN CONE SECTION THICKNESS = 2.000 IN DESIGN INTERNAL PRESSURE = 1.1020.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE s = 0 ALLOWABLE STRESS SA = 90.00 STRESSES AT JUNCTURE L c-~/AJ COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -1.35 KSI Sl:.= 28.89 KSI TANGENTIAL: SC= 14.68 KSI SC= 23.75 KSI COMBINED STRESSES IN CONE: LONGITUDINAL: OUTSIDE INSIDE OUTSIDE INSIDE SL= -1.12 KSI OUTSIDE SL= 29.11 KSI INSIDE TANGENTIAL: SC= 15.14 KSI OUTSIDE SC= 24.20 KSI INSIDE STRESSES AT JUNCTURE S MEAN MEAN HALF PSI IN-LBS IN-LBS Las· LBS KSI COMBINED STRESSES IN CYLINDER: lp~INt~J LONGITUDINAL: SL= 53.65 KSI OUTSIDE SL= -7.24 KSI INSIDE TANGENTIAL: SC= 48.81 KSI OUTSIDE SC= 67.07 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 19.40 KSI OUTSIDE SL= 4.18 KSI INSIDE TANGENTIAL: SC= 32.83 KSI OUTSIDE. SC= 37.40 KSI INSIDE . / ) " . RADIUS = 54.00 IN RADIUS = 45.50 IN APEX ANGLE= 10.30 DEG /!:}(Ctrr., •*lrl CoiF;) t/lfl ,J IWr J\ {)EJ'/6A.J Caul) 1.,.o.V Ben-p. '? l?tif~A-1.~1./l.: 0 N L 'r. "' '·. ·, ""· •'" J . ·' .. ·' .. ' • • ~.! 1 ' .. •... f . ' ' . . .. ' '! DESIGN INPUT c.Jr-)C 21 I LARGER CYLINDE~ THICKNESS = 2.000 IN MEAN RADIUS = 54.00 SMALLER CYLINDER THICKNESS= 1.000 IN MEAN RADIUS = 45.50 CONE SECTION THICKNESS = 2.000 IN HALF APEX ANGLE= 10.30 DESIGN INTERNAL PRESSURE = 960.0 PSI:--\_ EXTERNAL MOMENT AT JUNC L = 0 IN-LBS EXTERNAL MOMENT AT JUNC S = 0 IN-LBS WEIGHT AT JUNCTURE L = 0 Lils ~· HYot..-TttT WEIGHT AT JUNCTURE s = 0 LBS ALLOWABLE STRESS .. SA = 63.00 KSI STRESSES AT JUNCTURE L (('I /It) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= -1.27 KSI OUTSIDE SL= 27.19 KSI INSIDE TANGENTIAL: SC= 13.82 KSI OUTSIDE SC= 22.36 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= -1 .. 06 KSI OUTSIDE . ' SL= 27.40 KSI INSIDE TANGENTIAL: SC= 14.25 KSI OUTSIDE sc-22.78 KSI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: ({JO llVr If) LONGITUDINAL: SL= 50.50 KSI O~TSIDE SL= -6.82 KSI INSIDE TANGENTIAL: SC= 45.94 KSI OUTSIDE SC= 63.13 KSI INSIDE COMBINED STRESSES IN CONE: (#/A) LONGITUDINAL: SL= 18.26 KSI OUTSIDE SL= 3.93 KSI INSIDE TANGENTIAL: SC= 30.90 KSI OUTSIDE SC= 35.20 KSI INSIDE I' -- /..; I, i r . . - p. z. { IN IN DEG ( 0 ) ' - 0 ,)- , I DESIGN INPUT ------------ LARGER CYLINDER THICKNESS = SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = 1.000 IN 0.750 IN 1.000 IN 640.0 WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = 0 0 0 (> ALLOWABLE STRESS SA = 45.00 STRESSES AT JUNCTURE L ( JJ/,.) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 3.18 KSI OUTSIDE SL= 31.38 KSI INSIDE TANGENTIAL: SC= 22.57 KSI OUTSIDE SC= 31.03 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 3.26 KSI OUTSIDE SL= 31.46 KSI INSIDE TANGENTIAL: SC= 22.73 KSI OUTSIDE SC= 31.18 KSI INSIDE STRESSES AT JUNCTURE S ( poot;-8) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 30.69 KSI OUTSIDE SL= 2.90 KSI INSIDE TANGENTIAL: SC= 35.52 KSI -OUTSIDE SC= 43.86 KSI INSIDE COMBINED STRESSES IN CONE: . LONGITUDINAL: SL= 20.47 KSI OUTSIDE SL= 4.84 KSI INSIDE TANGENTIAL: SC= 29 .. 06 KSI OUTSIDE SC= 33.75 KSI INSIDE· RADIUS = RADIUS = APEX ANGLE= 54.00 IN 39.37 IN 5.44 DEG ............ l ... f?. z 2.. (~ '· l"t 0 DESIGN INPUT .JI. Cl~ l LARGER CYLINDER THICKNESS = SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = ~~-s~ :.J261-/7(. 1. 000 IN 0.750 IN 1. 0')0 IN 845.0 MEAN RADIUS = MEAN RADIUS = HALF APEX ANGLE= 0 IN-LBS 0 IN-LBS 54.00 IN 39.37 IN 5.44 DEG WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = ALLOWABLE STRESS SA = PSI E\ 0 LBS /-. f3-tER6T:I/l r 0 LBS 74.90 KSI <t-- STRESSES AT JUNCTURE L C.IJ(AJ COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 4.20 KSI OUTSIDE SL= 41.43 KSI INSIDE TANGENTIAL: SC= 29.80 KSI OUTSIDE SC= 40.97 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 4.30 KSI OUTSIDE SL= 41 •. 53 I<:SI INSIDE TANGENTIAL:· SC= 30.01 KSI OUTSIDE SC= 41.17 KSI INSIDE STRESSES AT JUNCTURE S c p () I A/'f fJ) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 40.53-KSI OUTSIDE SL= 3.83 KSI INSIDE TANGENTIAL: SC= 46.90 KSI OUTSIDE SC= 57.91 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 27.03 KSI OUTSIDE SL= 6.39 KSI INSIDE TANGENTIAL: SC= 38.37 KSI OUTSIDE SC= 44.56 KSI INSIDE r p.z .3 (] 0 JS'Ih-.!-r 241-/7(. r~ r-4.1 DESIGN INPUT V'.,)~; ------------ LARGER CYLINDER THICKNESS = 1.000 IN SMALLER CYLINDER THICKNESS= 0.750 IN CONE SECTION THICKNESS. = 1.000 IN DESIGN INTERNAL PRESSURE = 1.1020.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE S = 0 ALLOWABLE STRESS SA = 90.00 STRESSES AT JUNCTURE L COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 5.07 KSI OUTSIDE SL= TANGENTIAL: 50.01 KSI INSIDE SC= SC= 35.97 KSI 49.45 KSI COMBINED STRESSES IN CONE~ LONGITUDINAL: OUTSIDE INSIDE SL= 5.19 KSI OUTSIDE SL= 50~14 KSI INSIDE TANGENTIAL: SC= 36.22 KSI OUTSIDE SC= 49.70 KSI INSIDE COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 48.92 KSI OUTSIDE SL= 4.62 KSI INSIDE TANGENTIAL: SC= 56.61 KSI OUTSIDE SC= 69.90 KSI INSIDE COMBINED STRESSES IN CONE; LONGITUDINAL: . SL= 32.63 KSI OUTSIDE SL= 7.71 KSI INSIDE TANGENTIAL: SC= 46.32 KSI OUTSIDE SC= 53.79 KSI INSIDE MEAN RADIUS = MEAN RADIUS = HALF APEX ANGLE= IN-LBS 54.00 IN 39.37 IN 5.44 DEG IN~~is~~ LBS 'S~t7f"'t1t)l.fkL. QJ.~uli/IJ,..J LBS KSI ~ #lrr A l>r::f/I,1J Cow() tiltJJJ. ~t.!f rrR. RCfc~t;l(t-cwzr r 0 L 1 rJrro -s-.r a&t-t7c. p.2.r DESIGN INPUT CA:>c ~ ./ LARGER CYLINDER THICKNESS = 1.000 IN SMALLER CYLINDER THICKNESS= 0.750 IN CONE SECTION THICKNESS = 1.000 IN DESIGN INTERNAL PRESSURE = 960.0 EXTERNAL MOMENT AT JUNC L = 0 EXTERNAL MOMENT AT JUNC S = 0 WEIGHT AT JUNCTURE L = 0 WEIGHT AT JUNCTURE s = <) ALLOWABLE STRESS SA = 63.00 STRESSES AT JUNCTURE L C 11/lt) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 4.77 KSI OUTSIDE SL= 47.07 KSI INSIDE TANGENTIAL: SC= 33.86 KSI OUTSIDE SC= 46.54 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 4.89 KSI OUTSIDE SL= 47.19 KSI INSIDE TANGENTIAL: SC= 34.0~·KSI OUTSIDE SC= 46.78 KSI INSIDE STRESSES AT JUNCTURE S ( {JOINT p) COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 46.04 KSI OUTSIDE SL= 4.35 KSI INSIDE TANGENTIAL: SC= 53.28 KSI OUTSIDE SC= 65.79 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 30.71 KSI OUTSIDE SL= 7.26"KSI INSIDE TANGENTIAL: SC= 43.59 KSI OUTSIDE SC= 50.62 KSI INSIDE MEAN RADIUS = 54.00 IN MEAN RADIUS = 39.37 IN HALF APEX ANGLE= 5.44 DEG PSI IN-LBS IN-LBS LBS H-YuR.fJ .. lt:'q LBS KSI~ r I I fr/.l. LF1J 7H4-'V ?I r KJJ 15800-S-5261 17C . DESIGN INPUT G+ic ~2. MEAN MEAN HALF RADIUS == RADIUS = APEX ANGLE= ~~;~~~~-~~~INDER THICKNESS= 0.750 IN SMALLER CYLINDER THICKNESS= 0.750 IN CONE SECTION THICKNESS = 0.750 IN DESIGN INTERNAL PRESSURE = 640.0 PSI+--""' 0 IN-LBS EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC & = 0 IN-LBS WEIGHT AT JUNCTURE L = 0 LBS WEIGHT AT JUNCTURE S = O·LBS ALLOWABLE STRESS SA = 45.00 KS I .,._ _ __, STRESSES AT JUNCTURE L 0 COMBINED STRESSES IN CYLINDER: L.9J'IG I TUD I NAL: , SL• 9.70 KSI OUTSIDE SL= 23.89 KSI INSIDE TANGENTIAL: SC= 27.56 KSI OUTSIDE SC::r· 31.82 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL== 9.72 KSI OUTSIDE SL• 23.91 KSI INSIDE TANGENTIAL: SC== 27.60 KSI OUTSIDE sc-31.86· KSI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= ~7.7h KSI OUTSIDE SL= 8.15 KSI INSIDE TANGENTIAL: SC= 27.12 KSI OUTSIDE SC= 30.00 KS! INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 17. 7}3 KSl OUTSIDE SL= 8.17 KSI INSIDE TANGENTIAL: SC= 27 •. 15 KSI OUT.SIDE SC= 30.04 KSI INSIDE ... . . 39.37 IN 30.37 IN 2.86 DEG • ' .. 15800-S-5261 17C DES I GN . INPUT CA!E :/J 2. c=:;-~~~~~~-~~~INDER THICKNESS= 0.750 IN SMALLER CYLINDER THICKNESS= 0.750 IN CONE SECTION THICKNESS = 0.750 IN DESIGN INTERNAL PRESSURE = 845.0 MEAN RADIUS = MEAN RADIUS = HALF APEX ANGLE= EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = ALLOWABLE STRESS SA = PSI 0 IN-LBS 0 IN-LBS 0 LBS 0 LBS 74.90 KSI STRESSES AT JUNCTURE L 0 COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL• 12.81 KSI SL= 31 .. 55 KSI TANGENTIAL: SC= 36.39 KSI SC= 42.01 KSI COMBINED STRESSES IN CONE~ LONGITUDINAL: OUTSIDE INSIDE OUTSIDE INSIDE SL= 12 .. 84 KSI OUTSIDE SL= 31.57 KSI INSIDE TANGENTIAL: SC= · ·36.45. KSI OUTSIDE SC"" 42.07 KSI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL"" 23.45. KSI OUTSIDE SL= 10.76 KSI INSIDE TANGENTIAL: SC= 35.81 KSI OUTSIDE sc-39.61 KSI INSIDE COMB I NED STRESSES IN CONE:. LONGITUDINAL: SL ... 23.48 KSI OUTSIDE SL= · 10.78 KSI INSIDE TANGENTIAL: sc-35.85 KSI OUTSIDE SC= 39.66 KSI INSIDE r 39.37 IN 30.37 IN 2.86 DEG 15800-S-5261 17C DESIGN INPUT C~l: ttl 2. ~-~~~~;~-~~~INDER THICKNESS= 0.750 IN MEAN RADIUS= . SMALLER CYLINDER THICKNESS= 0. 750 IN MEAN RADIUS = 39.3T IN 30.37 IN CONE SECTION THICKNESS == 0.750 IN HALF APEX ANGLE= 2.86 DEG DESIGN INTERNAL PRESSURE = 1.1020.0 PSI ~ EXTERNAL MOMENT AT JUNC L = 0 IN-LBS EXTERNAL MOMENT AT JUNC S = 0 IN-LBS t::xCG'pT1ov.tA... Coi.II)I}J,J..) WEIGHT AT JUNCTURE L = 0 LBS _/ WEIGHT AT JUNCTURE S • 0 LBS -ANT A-()F:IIf)N C(ji.}./JrnbAl. ALLOWABLE STRESS SA -90.00 KSI M ~f"ltG~Il.C. ONLY STRESSES AT JUNCTURE L COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 15.46 KSI SL• 38.08 KSI TANGENTIAL: SC= 43.93 KSI SC= 50.71 KSI COMBINED STRESSES IN CONE: ()· LONGITUDINAL: SL= 15.50 KSI SL= 38.11 KSI TANGENTIAL: SC= SC.= 43.99 KSI 50.78 KSI STRESSES AT JUNCTURE S OUTSIDE INSIDE . OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE COMBINED STRESSES IN CYLINDER: @ . . . . LONGITUDINAL: SL= 28.31 KSI SL= 12.99 KSI TANGENTIAL: SC= 43 .. 22 KSI SC= · 47.82 KSI COMBINED STRESSES IN CONE: LONGITUDINAL: SL• 28.34 KSI SL= 13.02 KSI TANGENTIAL: SC= 43.27 KSI. SC= 47 .. 87 KSI OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE OUTSIDE INSIDE r r'i'!.r 1J, DESIGN I NF'UT ....,. \ ....-c;... {~--~~~~~~-~~~I NDER TH I CI<NESS = 0.750 IN 0.750 IN MEAN RADIUS = MEAN RADIUS = 39.37 IN 30.37 IN ' :~· SMALLER CYLINDER THICKNESS= CONE SECTION THICKNESS = DESIGN INTERNAL PRESSURE = EXTERNAL MOMENT AT JUNC L = EXTERNAL MOMENT AT JUNC S = 0. 750 ·IN HALF APEX ANGLE= 2.86 DEG . 0 WEIGHT AT JUNCTURE L = WEIGHT AT JUNCTURE S = 960.0 0 ~~.:LBS~~ 0 IN-LBS o Las . lt'(()eo-'Tt;'rr 0 LBS ALLOWABLE STRESS SA = 63.00 KSI c--.- STRESSES AT JUNCTURE L COMBINED STRESSES IN CYLINDER: LONGITUDINAL: SL= 14.55 KSI OUTSIDE SL= 35.84 KSI INSIDE TANGENTIAL: SC= 41.34 KSI OUTSIDE SC= 47.73 KSI INSIDE COMBINED STRESSES IN CONE:. LONGITUDINAL: SL= 14.59 KSI OUTSIDE SL= 35.87 KSI INSIDE TANGENTIAL: SC= 41.41 KSI OUTSIDE SC= 47.79 KSI INSIDE STRESSES AT JUNCTURE S COMBINED STRESSES IN CYLINDER: LONGITUDINAL:: SL= 26.65 KSI OUTSIDE SL= 12.23 KSI INSIDE TANGENTIAL: SC= 40.68 KSI OUTSIDE SC= 45.00 KSI INSIDE COMBINED STRESSES IN CONE: LONGITUDINAL: SL= 26.67 KSI OUTSIDE SL= 12.25 KSI INSIDE TANGENTIAL: SC= 40.73 KSI OUTSIDE SC= 45.05 KSI INSIDE @ . . . )__, STONE e:. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE A 5010.64 IFRONn CLIENT S PROJECT MA-SJr.t~ p (JI,R(? AIRifoR.t T't' -B~Ai>li?i I.AK E CALCULATION TITLE {Indicative of the Objective): Tft~ /lf;"trLVI/lC:Zl rlh c k: 11/1:>--IJ tip ty.t.,pson)4f.... /(r:;W1 p;/? 'ft:N.l?" 0 c 1(. . CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O. NO. DIVISION S. GROUP CALC. NO. TASK CODE Is~ s S~i.I-Jlil *APPROVALS-SIGNATURES. DATE REV. NO. OR NEW PAGE t OF 9 QA CATEGORY {.J) 0 I-NUCLEAR SAFETY RELATED OII om I!( Iff'})~~ OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED {v') INDEPENDENT PREPARER {S)/DATE (S) REVIEWER(S)/DATE (S) REVIEWER(S)/OATE(S) CALC NO. OR REV. NO. YES NO ~(.LC Of-r P---0 ~ ;-~-t? AJ"A i I p.A-u...lrs If Njff' ("':T ./:.. j:v/¥'7 . ' ' ' ( DISTRIBUTION* I T COPY : I COPY GROUP I NAME e:. LOCATION I SENT GROUP NAME S. LOCATION I SENT I (..;) I I (V) RECORDS MGT. I Jot!:.. @ ... ,, I / I I FILES (OR FIRE I I I I FILE IF NONE) I r:=, u-,::., u! I v I I I I I I I I I I I I I I I I I I I . I I I I I I I I I I I ! ! I ., ~o ' , :-"' () 1 ~ ; c~ -----~- 2 3 4 5 & 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 2& 27 28 29 30 31 32 33 34 55 3& 37 38 39 40 41 42 43 44 45 46 &5010 85 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. /)J'ou DIVISION ~ GROUP s CALCULATION NO. OPTIONAL TASK CODE S'"l{./-)7?; oRJ"FCTtvr: t:tr-C4Uflutrr J,..; CAJ.C:ulA'TtbtJ 1-IE'TNt>b fit"Ft:AINJ'l c C...O,.J Ct.() J I oA/! r PAGE .2:..:, J ---------~-----·--------·--·· --··--------~~--------·--·-··-·------·---- ,.,-; ., '' G ~--·-····-----------------·------~- CALCULATION SUMMARY STONE & WEBSTER ENGINEERING CORPORATION I.I.O.IW.O.ICALCULATION NO. .so10.62 ; tf/Uo-s-sztt-;7D SUB.I!CT I TITLE It-It: R(S{Ru 1ft~ i:l -r/1 I ( I( Vl?rs cf!: t:li.J P.:I' 0 I D A-t. Jfl:/f'V J 08.1!CTIV! OF CALCULATION REVISION ~ I PA8! ~3oF OA CAT!80RY I COD! CLASS ~/A To C,flcourrl: 71/F tfl?dUI/U=-"'il /HIC/(N'l=-lt RJR FUJpsotDh<-Jf'l;tfUS Fi>( --p~R M14 1'4/i=Nr CLO.S U~EJ ,4,1} "'rt:"~~lf~'f cl'OS'(IPEJ. (.)~off/C. lfliA.M lf't._ tow/),..,., i>,J ) EHfi:MiC"~<K-r coJ.Jol'n~JJ ~ Jl~o-~ CALCULATION M!THODIA88UMPTIONS ·· l:&OATtON Ff()/1 /tSJf.IG .Ill.: .JFCr VIII .. lJ1 V. f Fo!t t=L'-' P Jt:.~ om_ l~*ll J.! ttsr:b 77!J C/fLClJL.hTC" IHTi ~IRFI) -r-HtcK~U. SOURC!I OF DATA I EQUATIONS t. ..S ~ Lt~ .4NO 'Pf"lffrtJcJ( ~tU71~*t. lPJI6~o~ C~IT~k.tA. ~R MA .SicA ~R... ~R.,..,..f. ae~raLllf L'«T: llrtJtoc-t«rtu:. ""/J~t.. 'fttul'cr-: ~ S ~L.) P'-'IZ. /JftN-F.s-.2.6/1! -1 l. s +w .b W4 1ri'to -F-1 -c?tZA -I ~ )r IN e ..llr, ~'"r Vllt ~nl. 1 _ J ~ ~ t-tJ . • CONCLUSIONS REVIEWER (S) COMMENTS PR! PAR !R C', 7 LI RI:YI!W!'!_ICHICKij,i trl........., f'-... INDEPENDENT REVIEWER DATE 1--z..-17 "'J 4-DA't; I A ------·-·--·-==-----=-·-':"" .. =--=--.... ·---=---==--------__ -__ -___ ---__ -___ -___ -_ ...J_ ~---=--=---~--==--=----.. -... :..:.L __ ::.. __ ==---=-----l-==-:..L-~ __ :.... __ -_-_ --. _-_ ·I . . ,• ' .. "j Q; 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 () 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 0 42 43 44 45 46 A5010 65 .J.O. OR W.O. NO. /~IJO IH~A-IllE STONE 8 WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP s ST1!t:Jl ES : CALCULATION NO. OPTIONAL TASK CODE S2~/-17D (~cr. I ) - PAGE_£ A-'JJD erst(. A . C l.,41S1 /\)(lA. N/'r'L <?J.i'fi"~tif!=41Z f' P~H IJI('C; T~T 14." (/01) (ASIJ (CU 70 <1-0 ,6.1. 76.r .. r ------------~----~-_...--------------------~----··----~------~-----------~ -------------.- . : ' "' '. -; '.· .. . ") . ' . ! C: r-' \__) 0 I 2 3 4 5 & 7 8 9 10 I 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 .5010 65 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER -----.. ---~- J.O. OR W.O. NO. I DIVISION & GROUP CALCULATION NO. !OPTIONAL TASK CODE PAGEL J~ho ..s .r~6(J-17b ( fir::F. l ) q '-d' IiJ f · s'-D ., .i6 f~~,.-J~:wr CLASu1te et 1 A/T'PR ""lf"t.. P Rt:-15.0 It 1:! : r ~ ~- 2 3 4 5 6 7 8 9 10 II 12 13 '; 14 I~ 16 17 18 19 C;. 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 0 42 43 44 45 46 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. l~tfC.> I DIVISION & GROUP CALCULATION NO. !OPTIONAL TASK CODE S .J'Z(/.-/7D E"f.LI rso, t>.k. 1/C'If j)S z-2) • . . (/tr-, 2-fl) I. -o 91 ., Z.b C.t..6SUI(G ?. s-t c. -o 1::-/J CLtrsvlt~ ( VNI I tJ(3 j)(A.J~J.Ifll/1(;) 3. sr-o· .J:IJ -:rt::'~o~~r" ]:dR HtMtJ~ Tt:::ST I t. .t"b 1. Jl -o lt:f..,Pt1~M1', AJn. Nr~~cJ.. 7£ST r .. ·---·---~-------·· --·~ ' PAGEL '• . . . I c 2 3 4 6 7 8 9 10 II 12 14 15 16 17 18 19 c\, :~ 22 23 24 2!1 26 27 28 29 30 31 32 33 34 :u 36 37 38 39 40 41 4!1 46 45010 65 J.O. OR W.O. NO. ~~~ -~------~-·-......:---~ ---~----------- STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I OJVIS~N e; GROUP CALCULATION NO. OPTIONAL TASK CODE S 2~o-17'b PAGEL ·t J:. _ E ~ c. rt 0 CJ '-;o" r7r · '/)Cit ~:tA~Nr CLoru~e 6,CJ.o ~ Jol i ~ --~----------------a.r <f-otm~ >Xo.8S'-o. 2. .<t6~o -1-•1 ;' 0 /VG~~ r -t .._ 6 E~,r 'o ::: t?. .ff .r,. <:J,.I(,._x,8S'-O.l K '~C) .. \ ·' i ~ -; ., ~ . ! . j . ; .. 1 ' ' •1 i j i 'l '1 1 ' I l I 'l 1 ' 0 2 3 4 5 6 7 a 9 10 II 12 13 14 15 16 17 18 19 C:· 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 0 42 43 44 45 46 ... 5010 65 J.O. OR W.O. NO. /~ 0 () IF --------------·------------------·- STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP 1.1 CALCULATION NO. OPTIONAL TASK CODE .5 26o-17D PAGEL s'-o ,, :r:u ~MIJ 11r.. Alt r ~lt.. ~~UittE ~ CL/J,S (fit G 96o )( to It -t---= O.f-44- 2 .-. -:?6fn'>'.Pf'-.2k1t• ~ " {)Jt: //~0 ,,. ..rD ~--~ Pll~..rsa~c: ~sr .,r:~po ltJf~ r CLD.JuRE 0, '-o ., J::D ' ... s-o ~ll _L ,, -c -:: 0. Cftf'l S L o'' .riJ ·/CHPOI'l~t~r ~ \JJA.~VIffi-~ -t_ -.. ~-3 7' .. UJfi' ~ ~ ;i'-r:/"' ro -rc~toMttr ~t? ~~-1s111t~ f't;-l ' -t ':. 0· 3 2'} , (l.l~ -~ ,, -- ·--------.... -------------------··------------------~-----·------------------------.. --------------- 2 3 4 s 6 7 8 9 10 II 12 13 14 15 16 17 18 19 c-, 20 . ' I 21 . .Y 22 23 24 25 26 27 28 29 30 31 32 33 34 3~ 36 37 38 39 40 c/ 41 42 43 44 45 46 A5010 65 J.O. OR W.O. NO. I S'tfou !'. 2. .3. 4 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION e; GROUP I CALCULATION NO. !OPTIONAL TASK CODE ..:5 SUo-/70 /If; CK /o$1.j • if (I' Xb " -o use I .. ~ r '~ ~ ., -o ZO (J$ SLo , To TE"MfOMP.r fvR ]J~t:IJI/k.'t TC-ry-ljjt: /I '-c> ,,. .la 7Ti:~p'U'-'f f:eR. pAe-vv~ r: 7~ tT ar: r PAGEL }s_"~ 'Z- ,,. I . ·---~~------·------~----···----- STONE E. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE .A.5010.64 ( FRONT\ CLIENTS. PROJECT:-ALASk4 Po£.JtJJ< /Jvn-lo~rr y BR!7ot...e '1' L/1~<-£' li Yc>Roc:t....e crR.tC POW(ii/i!! P.RoJEcr CALCULATION TITLE (Indicative of the Objective)·. S-rfZES:5 ANAL-Y5/S c1F PoW£.12. PE/'IS'TCCJ:::. wyt' -Bt<A!-ICH CALCULATION IDENTIFICATION NUMBER CURRENT OPTIONAL J. 0. OR W.O NO. DIVISION S. GROUP CALC. NO. TASK CODE 1~800 5 52tl -17F *APPROVALS-SIGNATURES. DATE REV. NO. OR NEW PAGE 1 OF 37 -rt:>TAt. f-At. E <, 72 QA CATEGORY (v') 0 I-NUCLEAR SAFETY RELATED on om ,:M ll't.PJt./?U{.IC$ OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. *REQUIRED (V) PREPA RER (S)/DATE (S) REVIEWER(S)/DATE (S) INDEPENDENT REV I EWER(S)/DATE(S) CALC NO. OR REV. NO. YES NO ~·J f-c ~ c-:T~ 0 / AJfl'( f~<AJ'ASH rr.L~:.. /;~jg·~ Q)./:t/fl . :- DISTRIBUTION • I : COPY I I COPY GROUP 1 NAME E. LOCATION j SENT GROUP I NAME S. LOCATION I SENT I (v') _l I (vi) RECORDS MGT. I )of) ~ooK I v I I FILES (OR FIRE I l=tf<..€ ~ILi I ~ I I FILE IF NONE) I I I I J.L Cook:. tB I / I I :;, j¥J 0 -Ot"IV ££ I I I I I I I I I I I I I I I I I I I I I I I I I I ! I .. 5010 65 ( J.O. OR W.O. NO. ;sr"o 2 3 4 5 6 7 a 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION €i GROUP S' CALCULATION NO. ~OPTIONAL TASK CODE s .21t. -nF CJbi t:!'rlivt!!. c;/ Ca. /t!"""/ a l,·t>..., Cc.-lw/c. )c... /"''t:" lr.c~ NOpE Coo!ZDI/'JJ47l! C.F/'/Eii!R7;o,../ PJU.>P.IVIM /.ISTII'Jt:.5 El,hle..(.ll"'rtoi'J Oil' 5'!t:At.t.E BEllM 1:>£ S/C./'.1 CHIINd..F I PAGE~ ?c-7 <!. I 2- ~ '"71 q 5" t 7 8-35 3G 37 4 5 6 T 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 23 24 25 26 21 28 29 30 31 32 33 34 35 36 3!! 39 40 41 42 43 44 45 46 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET 45010 66 CALCULATION IOENTIFICATION NUMBER J.O. OR W.O. NO. I OIVISION & GROUP l CALCULATION NO. 'OPTIONAL TASK CODE PAGE __ 3 IS"$ao s -::;-2 &~ -I 7;:; -- REVISION HISTORY REVISION REVISION REVISION DESCRIPTION PAGES AFFECTED NUMBER DATE r / 2 4 5 6 7 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 A5010 65 J.O. OR W.O. NO. IS"i?CJo STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP I CALCULATION NO. !OPTIONAL TASK CODE ~ $' ::u~-J7P: ~ ohjt::c 1-ivt:: o/ l;l._,·.s u...lcv.d.. kc;., is fa PAGEL ?~rl(l("r>'/ 0. 5.frt:"s.S c;A,t:A./'7 s~·.s o.f. ,1--L__ pol--'t!r I::Jt!?,..,Si-cck. v.,~-,6,..-a,c.J... :lor desi'j""' a,.d ;...7 dr-o-f~sf ,-.,.,-l<t'r.nal p,re.ssvr-..{""S.; o.,d lo ,;...ru/'tf!:. ~~ fi...L. I'Yio.-x,·~""uM '!;'-lr-<'!'s5 !t!'v<?l !5 t..vi#""' allo~oblt!! S'lrt!!"S.J J,....,;/-_s ../ei,AJa.f<"el ,,... IL... df.'!"s ''J" C ,..-, ·1-~o';::... ~J I) • CAL C:.Vt-A7tcu./ tVIE THoD ' ~ F,;..;,tt!!' -EJ~P"'t!'rt.f Co..-v~,hul-<'!"r Cod(!!. AN.sY5 IS (/ .fi/:.s t!!!../ for If....._ .5 r.-'f!" .f .f C:.n.:::.. I 7 .5 l s. 7l..c... ,Pf!"nsloc k t-.J"fC:-br-a rzcl.... '5' J.t::" II ,_s-,...,.,cxiR led V:S'AlJ l"'-L 8'-Alode I.sc)u:~...-anFt""fr,c: M·-5~1/ ~/-1!",-.1!!'-"'f • 71:..:.s c:lt!!'I""'O::::,.I ,Pr-.r:>v.·d<".s .b~,d-~ i "",...d ,..., <"I"' bo::t . ..-....L S:kfl~ ,$ S o./o,....J tA..)I~ i!,·,.._,.,k._j~ wic 2- J'< -/'la"'-L 5;>ff~ .S$ . A ,Po r -h ·o,. of lk. _,Pt!!',Sfoc:. k w,-/1-~ L-o..J'ft!!"-.brt::»nCJ.. c;,. <f)f ft.-<_ br e;.. .... c J.. • 7£:.._ _.t; ,.. 7 #. sk 1/ all e;;/ ~ p#,-.S lock: s-k II /~c lvd t!!! d /A a .... cL 11:..,_ e...,d bov ... da /"'7 .s:elf!'c l-<'!"cl ~ r~d ve~ }t.,__ Cond, · ,l, ·i!!:J., .! 0. r <!'! s--2-... e~l ft._._ ,....., od,/ e::<,..d. /'?,,..,""'ii!.c /1...,__ ~)Jt!!cl o/-~ r1d aJI<!!!'c /.s e?n ~ r~ .f vflh ~ CJ,./'7 Ae.IJ /.l._ ;O<t,..ffock t..vy~-br-o-.... c.J.. /_s ,.......~<"It:.:::! fo /c.,k...-a. dv0v1le.. / -t' oJ fy.....,~ },.7 . l I 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 2 1 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010 65 J.O. OR W.O. NO. 15 8"0 0 I. STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION & GROUP CALCULATION NO. !OPTIONAL TASK CODE ~ ~2M.-17F J 7L-,c:, "/It!-£ /.-:,... <!'"";. d-:scrt!' +I!' .tdt"e. ;:· r, h~ .. /l$.fv,..,,bkll1"" ..1 r.-:k It'd /·,...,pJ.·cll '"' /J...Js ,..., t!"lto.:/ of e.. ;1-c ~··.s ~ ... .,.11 s,·s. /-f!'prt!".St"""7/f e:'" Dn -1. ""ve v 5 PAGE_L Z. D~c.r-E lc..s.lc / l..o""'t:Hj t'···~·t::n/S -.-e/ isolro) 1c tt:. S .f vrt .""~. 3. rv-. e...ft!!r•'e...) prt:> }~ / J,·t!! .s e.. r<Of!! .:r;;, .... c ko ..... s b, ;..~<-~~ JG.. rL 1/.s ev-. d host!"' b.-:I~.U-tU."' ~ .:>411:1' ~,..; l'l.J St<'k/.,... b,.-a,.... t::. /~ C 1/J,...,s,:.:J'f!!'l't! d ~! 'Jt!'Cr?t:•/,., '.c, d<.r <"'oro..:,.-: :/I}, <"' S . S.rnoo.lt.. /-rc:<~">.S' h'on5 prov1dt""d 1,7 c.JI""/',...t_s a / ~ Yl a f c ""' s I d II!!! ,.. !!' .d .I " 11.. # a n """ I s J • 7Z... "jt!!or1t!'l/ J ""t:>dtt'/(".,/ c..s ):>osSibl~ • ~.v 'ft'-b/""" ~c I. ~-d ~:1 '7"- / ( 4 5 6 7 a 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 2~ 26 27 28 29 30 31 32 33 34 3~ 36 37 38 39 40 41 42 43 44 46 il.5010 65 J.O. OR W.O. NO. 15%oo I. 2. 3. STONE B. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP s CALCULATION NO. OPTIONAL TASK CODE PAGE~ s.:v~-J?F At-'ISKA .P.:>wER. AvrNo;t;?;TY .J i?/'!1"10(.£ Y L./11«6 ;-IY OF-:; .5 c: c CTI'llc. P£o:;rt,; c.r ; J. o. Afo. IS'j'oo .) ( 5r&E'-t..../J'./E£ /JHO P!fi--I.STOCK S"r.evcn:.-'I<At.-OE.S/&;N c /€ 1 r t?' ,1:2 "4 Pt4~T 8 ' j :)gcr;o,J 5. 0 / -RE Y. CJ ..J c:Jc.rptJE ...e-15/ /'jzrC: { 5 ..f W 0£AwtAf~ l'lo. 15 K'oo -F.S-.:2~/ C ?oNE ,e_ .) ) Ptf;V.STocJ:: c.JYf£-8.A!.A~CH Pt../1.1'1/ SeCTION o/ DeTAILS, Pot-1€R /Jurii<!:>RirY OR.A'-';N't:. »o. llo5 -.C-31 -S.:Jo 7 -J<oo A!Y.S Y5 /"?At-JUAL 5ys T£1115 ENC.;,...;£ex:uvt::::. ~hvAtY..JIS :JY.STG~ ust;<..s VoL. I +..II J S't-J.AIVJoA./ rh-tflt.... '/S!S /IVC . .I /<.£VIS to,.J 'J. 2-. • I ( 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 35 Ho 37 38 39 40 41 42 43 44 45 46 ... 5010 65 J.O. OR W.O. NO. 1$$ CJ 0 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION & GROUP I CALCULATION NO. !OPTIONAL TASK CODE 5 5 :Zit:. -I 7 ~ PAGE Co!Vct..v5 IONS : /L. p 0 ...,<1!'r p.R_.,slock VJ7t:!' br-e.,c A c..s dt"'lc..tit!'d r,.. /&.f 2. /"! t!!J' Is /1..... d ~.St)" C .-_,/,ott:.. cJ /6./ J • JL...e &H..S 'j S .::11-ro.:../ 7 51'.! $' .lt:>c-; S ~ ,..,c,IJ :5eJ/"'t!'.-./J t::.~f lt..L s-./u./1 fo bl!' S:fr<"..JJ"d b~)'Or'l.d ~ C //oL-Je. /;,/(!' Sfr"-1!'"$J )-,...,.J·,t ..> ov//,. :..,_,_../ /A I<....J / / , . JloJ,..J-l'V<!'I'.J H-L.st!! r L 7,;,,.... 5 C<r..e ;vdc;"'d 1-z:, b-<! t-J,jt.,"' ~ t--~t!'/d bl!!!'/~~, /~ sh/1 cv.-c>1 ttL r'"(!"JnJOr'("J·r.~ St'f."K/<f' b.-!'~.....,./ ~~cl ~r-<"'l(.r<.. tf......c_ ·sf--r-<!'.>.S.t':; t-.11·;; i:>e c/,sJr,".tvf..,.c-~ rJ-.o.-4!' (/ni}OI'I"''J, rt::.lt.</ Aa_... sJ.cw uf ~.!> 5.tr-"'ji/Jc,.-;/1t"J t:).~ ~~ ~ ,;:;:-.-J7 'S;f • J4. C!l""lPr9.Cnc 7 lA ftJ. I IS Ce::.lcvfc.. f.·o,... ~ IDc..d, ..... i ct:J .... d, Aa,.. ne~l-t:::t:u .... s;d <'rJI' d 71....... Jv..rk.kc ,.,j,-117..., = I. 3 /.5 d ,hr..£ d Jt_,~ fLs-I.$ - /, c A 5010 65 .r J.O. OR W.O. NO . IS8oo 2 3 4 5 6 7 /, 0 8 9 10 II 12 13 14 15 16 17 18 19 20 f 21 \ 22 23 24 25 26 27 28 29 30 31 32 33 34 3!1 36 37 38 39 40 41 42 43 44 45 46 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION €i GROUP s CALCULATION NO. OPTIONAL TASK CODE 5 21r..~ J?r PAGE--'L_ branc J... a .... d del-o.iled ,_ ~ //,,Jere-,~ 7 A.,J z_ A .?/s" ¢> .6.--a ... cJ... ,j Jor/"''<!'d /,..~>,..... Mar~; fold (.,..hit._ .c::t. :>'! .,...,~ /,-, c · Co,.-p cJ lt.r-b! C:.OAi cJ 5Lt//s, 7Z...,_ l~ 0/"1 ~ .fr 'J oJ ft._;_. Con I!' .S 1-z:, )rod we:~ ,;., 1,., t".f c'cho,.. .s ;l(c.l t...J,"h::_.. ~ ... ,,~,,·.,..J lo/(1!'.-.,.r'ICr"'.f, ~ re, ... Jorc-·-~ 5,c-_k:_.& -b<!'e..,--. a-. ~-dot.-/"' .s 1,-C' Q,..., s,,.; t:' oJ 1.5 ft"'lt!'cll"'d fo J>,ov,d~ for #.rC/ ft.....L h~" a,. c I.e a.-. d J-o s-A-t II ,, lt..t.'5 c "'' 14 ·cJ A.,-1~._ r'o /;t? ).-o ,;-,dt'a /t._., bl"o. ...,. c L }c..,..CJ,c. 6/~ flo.....J r-t:,/'.forc<!" :ll...L. I ~LASKA BRADLEY LAKE CAM -WYE BRANCH STRESS ANALYSIS 1 !5%oo_ 5-'521C-17~ ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 1!:3'oo-:;; -s:ut.-17,::- ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 f';;. /1 ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS l ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 1.., 13 J ' )~$oo-5-'52/t.-n;::- ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS l 153oo -~-~2/C-J?F p~. 15 ,... ~ \. ..., ~4. "' " ,, ~ 10' ~ ... ~" \.t 1:"' ,_ .~ ' " " "' " ~ -..., " ., ( ~ """ ~ ~ ) .... ~~ "' \1 ' " ~ ~,? t~ ~ \l "' "" ~ ' C) ~ () ~ .... I· "' .... ,. ~II ,;, .., " ~~~ "' "~ ~ii "" ~ \) ~~~ l( .., ::t (XJI ~ ~ ~· I I '::: ·~ ~· ~ ~ ~ ~ ).. I..T'< -, :s. ~~c:7 : ..... w ' ~ "' " ,'I: 'f'l ,.., .... ... 0 <. • ~-s·; " ~ . ·~ \\1 \ !\1 \ t-"' ~--~ \ VI 2 !1.. ~ In .... 1-.. 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 ... 5010 65 STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER PAGE /C, J.O. OR W.O. NO. I DIVISION & GROUP I CALCULATION NO. 'OPTIONAL TASK CODE !5'?oo ~ '5.2/C.-17;::: Z.o W'(t' 6-ra,.-,cL -it.,,. 5u II .5h 1/ 1.5 a))rc/,,-.6 / "'_ d .:/·,., ·ie <"" ~ /"! ",--, fs 1,., ~- Cor>?)vJ.-t!'r j.:>rc"J~"'a........,. I 7f..L it!o,-., .!' 1-r 7 of h..<. l>ra,.. c J._ , s d.-;/.~.:1 ,,.. d/5"cr-t!.~'··?.,_.,.:J ( ...... uC(:: j.,_ d-1"-t!!... Con"' ;!!c J.,...J Jar.-. VS•"J 110dt!'.- h, i~)L... k )~/,......, It:_,_.,_-ski/ e 1..,.,...., t!"' .... ls . 7Jj. iR~ reo ~a-cf ~"~Odt! C'oord• ,.... c. I<"' 5 ,_s /:>.trfcr--"1t'd 1/.S•"'/ /'l'?a-7 5,·A ,~~ • ~~~-(/ _f't:;. / 41! FoKT;(/IN ,bro7'""' ,-,5 a .S 5"/,c~... ~~ /J 1/e. t!' 1,....., /',-f I. Cc,i!>,d,,. ... .ft'.S Jor /'LL d/J;r_,,..J fe'j~""~<I!,IJ Cv..t!. Cc.lc.v/e.lt!d '" ~ · focJ Cocrd-,oll!" f'!sl-'"'"' o. ... J a.rR ./re...-,_s.foo-L-R d ~ 4. !J./"' iJ C"oc-rcl:...e.. le .>;sf,,...., J.,r lz_.c_ I"? od' R I. ;1 },-,_c./ cLLck o} ~ ("l,C,d("' b7 c::;t!;fa_,·,.,· .... / l"'lod,.. I 'jt! o,....., <!"' fr 1 1..5 .:::;. p/cl--oJ ~ r--o,J,./.~ 71.., ·s '.s .$' i.cu •. .;.. i!J ~ J'""'?t!!!f 1-1"1 .:>I ~t,_,·J .!""'e../cv/e.. /,·.,.,.. , o ... /7 /,_,;. j) it..L. b/'C<"'-C L lo lok:<!' advaniA'Jt:!. oJ 5411 ,_s ,......, od,-l<d 5'7,.., -:-a <'!" f" ':1 • ' ( of -......,a,.Jcld A Jor~o .... A.t:.. 5'-¥ p o,.., be.)/. ~ ... .;.s ~d a. )or hD_. (;!J /'"'-'._ qs /:.rt)·r.CL ar'<'!' ... .:.. elvd.t"d ...... ft...,.L r""lt:>d,.f • 7{.._ I!! J( /-1!',../ of ""'(;ld I!! ), .__ J ,j; bc...s ..... d 0.-. C<>M}vlt!'r CtHI c"'"' s. d t! rt::. ;,·,::,.-. s' ~d. ~- - C"flrcl t~f tt",e/ ... Jfl!!'cl.s On L a. t!'CG/rac 7 af rt!' .s v/ /.s /<'\ ~ ,6,-c.....,.cj_. ~ohi~ of If...._ t-...~7 e' -b/".._,.,ci.. s-L..tl/ /'._'7 e._ 15 t>f /L .s C.t:>-/ ~(//c. kC/-. 9:> I 2 4 5 6 1 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 .1.5010 65 J.O. OR W.O. NO. /5' 15ao STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION & GROUP I CALCULATION NO. JOPTIONAL TASK CODE 5 ~ .21&--J?r 7]:..,... e>'?l..l Nod~ .7so)c.rbr-:,P.J,-,·e. -/t.,.., 6?/t!!'/VI.t!nf /.r 51!!'/f!!"r-lr!"d /2.:> .l'>'lodf!!'/ w 1 (! l>ranc 1. s4 II. PAGE_/_]_ 7J;,s- for lc-r c.. I .and e/,,....,1!",.,-/ IS pt;t"kcv/a,.ll w("'ll fv:J_,.c/ /"''c;o!.t'j,;,.) f't:..,:., Cut'vt'd 54., I/.>. J:/ }>rov,de-J :s'/x de!"'/r<t:LS of f,-..u,Jo,.., ftr "'ks)J<><c-~r-11!'",.,-J ea.c/.. nodt!. :n::.s '" clvdLS Ire;. ~.r /c. he,.. /,.., / fola.ha...-. &.bow/ ~ 1'/,~ a.yf!'f . ?Z:...t-e/~""""'""1 prt::Jv,dt't!!'f };~ ru::/,d 5},jjr-l' .f'S a..! on j r-,/c..ht>n..,. I sAJ/......, s.5. -,c._._ /sofc.ra,...,t'Jr,e. .11c../ur~ o/ ~. !"7£.,.......tnl /$ va./rrc;,_b/~ ..1-o/ d,f;/\1· ..... 7 C:vrv~cl Jt"c/""lf!!'lr:t's. 4 fla..r ?la.J~ e/~r-· .. Ju .. 1-~c. ..Is ~ )-'re:1.l/-,,...,. ..s G../~" ~ dL 1'1CJ../t'J' dl".f, ... ·~.... 11..-..-£ tpj(!,....,_,,..J I d.. ,..of' f, ·/!!' /;, a _fo/a, .-.....J! ; a.. s /S /'""'-<!' t""c. J'~ 1/t /t...Ls ;:,,-cb/1!!,....,. ~ c.v~"ve,/ C~eua cl<!"'/' of /t...c... I!!'J.t't"'tt!!"'"IJ u r.t'lo..~~d '" ~- /so}>t:trc.. .1"1 t!!':f,...,c ...fer,..,(.,/./.:::,), c:~,., of r ~. ,..,;_, ,_,_,,.... f 5",( IJ~ss. A dt!' ,t&:J.,'/.ed dt!'sc,-,}fio-of of /1...,.1' e.&l'1en-J a.,.. j,~ ~. c e.) ,;. !:, ; ), -).;"'!. ./CJv" .,/ 1-I(, f 3 2 3 4 5 6 7 8 9 10 I I 12 13 14 15 16 17 18 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 .t.5010 65 J.O. OR W.O. NO. I:JSoo STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION u GROUP s CALCULATION NO. OPTIONAL TASK CODE :S .:2 ~~ -I ? p PAGEl.!_ ~ '-'7~-6ro...,.c/. ,..,,d,l Ccn.s;sh c;f Jr.-v-r bDv.-. d.,. r· '<' 5 , r7 .,.,..p If l't....t.._ b ov,-. d~ ''7 o./c,.. / 1-t-.t. ,Pit:t......_ of :S'l,.,,..,~lr; ·h .. vc /:,uv,-.dc.r/t!'_s af /.4 jv,cktMS ~ /1-..... ~7' ~ ¢ r1 t:~..,,_l~ ld .:;..,,d li_,_ bov"' d .. r '1 .:::t 1-~ jvn c A·c,... lc -~ "75 .. <:;b br-a. .... ct.. S7 rY7 ,..... I!! /,_ "..::::. V.$1"' cf hr cJ," i fl...<_ Cc,,d, ,;.,e,_...J hov,.,d.a.,-7 Ca.rrd .4c,... f' ~ '10 d t!" .s a.f /Z._ .. _p/a......e_ of 5;""~-lr'J. UY = o !<X :::. 0 e :z "' o or-<t:- .6ovn d <> ,..-'1 -;rz:._,t J" -I!! ( ~ . .Nod t!" s Jt:J"'Z /t....L pic. "'-.-it of ::;.:/,...,,......_; -1r 7 ?lre re J .f..-t:v ,.._.( d .Jro,-'1 a.1.Jl ovl-of-?I t::~"-.JL r"loV~I"'!e,f-(UY) .t::~.,..J ,ro/c..kc-"'5 {/<>' .J ic~) 71:..,.._ Ce>o,d,;.. ... ft! S'/.s.f~,...., 1S 5/..cl.-,j,., e-P•;:~ '7 of ft.,·s ce..l c A,.,j.:; o,... ~ rt' />'\e._,-_.,,../ lt.r..t:.<. "'--',/!. ?,·.., f:,~vn.d c>.r-7 ux == 0 UY :; 0 u'i~ 0 bov,...d ... ..-. <!' s C-e ,..d. h-o.-. .s ( ar-t! ,..b~c: .,,;,.; .,.. d l.t' 7f.,..._ l"'!c..,,}oJd o."d ~ hrc. ... cl. prcnod<t! ;51-,-j J -u SS' th /t....._ .h r a ,._ c /._ a" d )>r-<" .,. ., " I ~"' 7 r• ·'?,;.; bod 7 ~"'! o v<!,..., -t"n f. of ~ br ~,.,.c t . ~ .... ce"_ ~ <!!'" ,{r-£ r1 a.,.,, /old av-...d bra." d A 7 &.,.. n.c.f-b.L ;", c I.,. d ~ d ,,. ~, l"'?odt!! I /or ~bv!ov! Cosf-r'l!"'e~._so-s) ~,_.)J,-c;t!',..f ~ ... (hf' oJ ft...,. ,....,....,,,}oJa' a-._.._d ~ bra,.c J. li!!'j or-e //lt'/vdt"' d ''"' ~ r'1oc/p/ '-''/1, 11.-t_ ~Cv~ ,6&Jvrlc/.::;:>r'( Co,.d,J;c ... -1?::> :flr.,vlt::~.le ~ dt!!"s,>·t?d !?«<f'),..,.~v,·or-. I 2 3 4 5 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 37 38 39 40 41 42 43 44 45 46 ... 5010 65 J.O. OR W.O. NO. l!:)f Ot:J STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER PAGE_;_!_ DIVISION & GROUP I CALCULATION NO. 'OPTIONAL TASK CODE S l '5 .:2./C-I 7;: /lv~ k Jt...... 5..!".&c!rt:c:l bov"'~"l C'c-r·rlA~ ..... s /t_t_. ~ lc:.. v/or of ~ t.J7 e -b,.,a .-. c /._ Chva. 1 }r"""" /1.v_ bov,.... de.,;~ s c-v,// I,<!!" C...f d t!" .s,-' <' d ./ lot...J t" .,., I'_, ~ e; I"' ft..., bo v,..., . ..-/~,.. 7 /t..L ,"c-Jv~h ,,..~~-;; """;-.be a.c-ct./,...:::~;/~ t:::<.,...d ar~ ...,af l.l..ft!'d /"" )1._,-.f Cc...lcv/c.),·on. yr:_., .L,_ "'i /1.. of fL. ,...._, c;..,., ,j., lc/ .&, V..f<!!d ,_ ;i,._..... I""'Odl!'j /$ ~ Jt!! J.::;.,..'le e .... ovJA. ..5"(/cl. c;...J J~r I of (!"",...,::1 -<""" f J,..,.. Is ) :5;. v.,..,...,...,....; t::JJ..«!'~I:s o,., ~ J lr. JL.._ W1 ~ -j;,,.,IIA.,.. c.l ..::J.r.!!' ~d ),....a,.,ci, .5'~-t~ ,..l~d #c/ ~ k,..-,oc,.v.... af r<"' J._,./1$ /""1,,-,,f""?i?~d .. Fo, /Z... t/YD!l.O TEST Co,.,.,/,i/o,. /oc..J Cc.St' / 11....... C""nds of w7e.-bro. ... cl.. t..Jij/ b.e Cc.fj:>.-.~~, -Jr.,.,,..Jcr.:: /l),.,,fv.J;,.,. cJ )>rt'SJ vr<l! ::?1-r.t'.SJ'I!"S :.....;;// ,:1,.,-,,../.--.··'-. 70 &}Jec/,v<'l/ l"'!cdt!!'/ ~.s 1 fL<. boun<~lc;.,'l t"cu,c/,,1,-0 ..., C'..f ~ f!!?,d~ ;5 e. II,,...,..,/ l'~ c.1f tot.-0 }o,. .I"VJovt"r>'lt!',.f lonl,,0d,-c..JI7 c..~l. )L ~.x.l."!: ~~ ft._... />1t:l_,-,ifcld Jo,· /1.., ;"'>c:,,,Jc-/,./ hov,-,de.o<"$' .-' Oc,....,_ d ..,./c-.... '? ~ a_ X' .f e .f. / !.__,.. bro.-r L .fo I' .k.... l:u'ct-r I. J ov ,-, d 41. tJ , A /s 6 .:::;. ,) l;t_, f .e b()t:/1'1 da.o· t' .J " .:!" /...1-~?r"' <:<. / .Jo., t:: ~ s do-i h..._.._ lo,7 .-lvd/nc..l d-r.t!"t'At:;,... .o.,,.,. c:}}J. "d ""'.r . dt!"rcoi.>t!"d o~ _J>c..,f!!!:-5 2c-2/ t:>f /1-..s c.,.lc:.,./c.Ao,.., 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 IS 19 20 2 I 22 23 24 2~ 26 27 28 29 30 3 I 32 33 34 3~ 36 37 38 39 40 41 42 43 44 46 .. 5010 65 J.O. OR W.O. NO. JS"S'oo STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION & GROUP I CALCULATION NO. !OPTIONAL TASK CODE PAGE 2-0 S !f .:2U -/?F ;::>~~.sJoc:k "'-1 7 f!!' -b.re:..-.. .::1.. /.:-e..d Cc,..S~S. IS Loe>-d C.. s~ I Co,.. d, t4·o~ (.....~, }t._ .,_.;. Ct' ... //",..),~ r~}r~..f<'" /s A..-Nor/"'\ t::. J t:'-0"\ ,·.,.,.,t,,.. .... ~I / ,.. ... s s (// L oJ ~¥o ~;r. • t.~.::>.d us-ott! :< ~"'"<t.!)r<'-'..rc-rs /.Z....... /-/'7 .:.//C • ~sf Co,c::J; );.,~ e-),· If. c::::._..... ""' ..J,..,. , e......(' ,P; <!"' $ _; U/" L af C ertlt!".r /. ·~ of /, 5 ..>< .C$1o /'iT> = ere o /'"¥~ 7-G.. t!!",-,.J..f. rtodR /So)c.rc. ,_,...,),_,-ff,~ si._, II .t!! A,....,<',.. f v.s tf!' d ,...... .k, .r .:::< rt c. I '7 ..fl 5 c-_{/C' , ___ ; .s for ~ A)::.j::.l-c.,._/.-.,,... of Sv;./c.ce /'r<"'.S5 vr~ lot::td . .,. J . ;;t:;s Jc ... fv,.c oJ /t...L e/.c_.-, _.,,I 1S 1/J.PJ A, e.ff/7 lt.... /0 c..d s. Ov~ ,{, ~ d,·S'Crf!" lr_<!!cl /""'odt'l"/1" J;6_ o.f)>l:c.,..ko~ o} ~ pn~ s.s vr.-t! lo.:..t!oJ,-'.'; 'J "of p<'r.!<t"cl!.; ,..,...,1,;::;.../1 """d ~-~-t!"~,-__:/\1 jv,.._c,L.·,::"''.S 5'1""\-...f.P ,Por f. ·o,. s ol ~ ,Pr<'.'.sS v.r-l' )C) <>cc/,,..) ~"""!""/ nof .6~ Co .... s•dttrt!'d. JJ,~..Pv.-1'-' c:;;,_.,c(!'_ ~ ""'-? <!" o/ l'? /.f!"~.-.1 f {/$~ d ~~ .>'v}fic,·t!',...f/1 S"rvo.c..ll..~ JtL ~1..1~c~ of d,"fcr~l,·-ea..ho.-.. c..L,JI / prodvc.~ Vtt!r/ r"l•r-Or '"" ....._ cc"'fro..C ;~ S", ;:o, It,.. )IY.O£o-TeST Lo"'-d Co,..,d,/,c,.., C".~l?/nc:i./ }orccs ar-c e:..fp/.-i!'d :h:> s-,;-v.u)..._j,p ~ e>jJ.,c/ tt~} -~~7' fvc/,.--.e-,.) _/'rL.5~t.H<!" sJ-/_,Sf,J." GA.$ p.r<~""v,·ovs 17 d.-...rc /lh<'!'d 0 ,.. ,Pe. ljt' 1'1 c.of /J..:s Cc..lcvla..~·o,... /4 ""'-C..'jntNd-t!' c} 1/......;J_ lt>rC.Pf i.f ce..lcv./e../--t!"d a.1 Jo!J.:-v.JS- PD LI-t I I 2 3 4 5 6 7 a 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 3B 39 40 41 42 43 44 45 46 ... 5010 65 . J.O. OR W.O. NO. ;1?Foo STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER t DIVISION e. GROUP I CALCULATION NO. 'OPTIONAL TASK CODE S 5.2N J7r -;;::,.. lc"'/'·A.,_,.;;.-,.t=.c/ pre'J.fvr-.e s-)r<".JJ .15 5" h·-< .J 5 /1.. "t./ /"tv.. 11... c k ~ .5.1 t:> ;f ./1...... Force of}>/ . .,.) o..} as .Jc//c t......~S - PD -)< ~t -,;_ · .!>vi~r '1 le-~,ft.. f'"cr /V't::W e 1.3 P.D ;'r-l.,.,,..e../ Prt!'.JSv,.~ o. '"-r'1 ,;!11!/ ' 51.... /I . PAGE 2/ 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 • 5010 65 J.O. OR W.O. NO. /5'% 00 :3.0 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION f) GROUP I CALCULATION NO. !OPTIONAL TASK CODE ~ S.21(-l/l= 5riZ.6S s. L/1"'71 rs PAGE 22- :S'/RVCTI/IV'lL DE'SI6.N CRI7£R/.4 ' I{, J. I } ~. '5:"1~~_/ />"le..f~.--,-e./ 1-c be! U.S.t'd .Jor h.__,_ ?~_.,slat::"l..c- /VIomk/..1 5'./....,_// ~/A lt!'.J IS AST/>'1 A-7/o C::P.A Ct.IISS. 3. ~ --f!..Poc...u:. ble sl-rt!' .!_5 /,;...,.,,·Is lu /;{ ,j Me> l<""r--= I Vt::J..,-'7 a..ccan:::::/;:...7 A, ~ :S'J,t.ll ?7:.ck-.,-t!".J.:5. ~ Jovt!'r,n'"') o..Lfoe.-Ja.61~ :>,t-...-.t".U J'or "'-''te-.l:u-c..,(;.J...es <::<re. a6fe..;""-"l-d ..fro,..._, S<l!"c. 5". 2. 3 c::>J /IJ f. / , I r .:5 J.. c,,/ d bt!'!!' '? o ~" d .It e. .;: .tt::.. dP .:::· ,...~.::... l: /e -5~r.e.fJI!!'.S ;:r·.rt!', ,:... 7A6/e 85 -~ of Arl. I ore h:, l:>e o!! dvcllf!"d 6 7 /o% .lor t-.1 7·-- b r e>nc /.. t!!f'. L rL dvc ,d c:::..1fl ct-J a 6 ;.,., 5 p ... ./c,.. 7 (..._.};ft. rv>c. .f. t!" r /A / )?r C) "r h.,. .J c; r t!" /C. b er/c. / t!" d o... ~'""7e z)f c:tf lf.,:s cc..lcC//.:::::. Aon . 4/so/ ..lor /oca./;·2t"'d 5"/,..-.;~ss Co,..d,/14:>,.,; c...f A:rrJ.I'l 51-r(".r.J"ed O.r(!'e..S S"vi> .. /!!"'t:-1 h j'crll!!'. n ~;-AI )/ i~ /d,"' 'j.) ~ d L s-7,-.. c ,., !~,. /&:<.. (ZJ~!) ~t::~t-.J.! Jo/ ~ r~dvt!:e'd d.....(J'~&-~o6/t" :71-r.ef; .4 6e ,~;..creAs-ed .67 a. ./c.~_-lor- 0 .I /. 2 S. 7r.,·.s ~;. ere ecf-t!"d J/ ct.... .-:: -!:>)<!'! ~~ Also fa.j,...,. #a It'd o,.,. /"" j C' 2 ~ c·J ;-,t.. --5 c ..... lcv~Q .,4-~..,. . 7.G.. 7X;.... sk II of ~ w7 ~-),,..-.,..,.. d , ··s /"' ~ #..--~ J;_...,'f!',.SIC1nt:>t./ 5'J-1"-<i!.fS s/..-:..1<!!'. L,..r}cr<!" /0.. c.....Lfe~wc..6)<!' 5'/r.-<f!S S l""'l/5f .6"'1!. ("'CI_-. }c.,-., d ,.l.t..l a" ~r'-''vt'l~-1 Si,-..crr ba.st!?cl p.-. ft._,_ /lt',ck 1 -/YJ,'j~.J /t..Lo"'7 cJ ./c.,lvr< (}(,/I) c::<S 5).o ~.<.~"' 6" 1~ w -/ tT 0: u I ' Z J 3 I 2 3 4 7 B 9 10 II 12 13 14 15 16 17 IB 19 20 2 I 22 23 24 25 26 27 28 29 30 31 32 33 34 35 37 38 39 40 41 42 43 44 45 46 "'5010 65 J.O. OR W.O. NO. ;5 foo STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER I DIVISION u GROUP I CALCULATION_ NO. !OPTIONAL TASK CODE -s --s.2'' n~-I_ PAGE2i_ ~ /lyf)A!o-re..sr Le>~D Ce,.ud/ Ao..., /..r c. C>,-.,.,.JL fi~ f-~.JI-Cort.-1/·k~, , 7IJ-c.o/t!",...,P JC?r dt!!.s')" ..Je-,-r:t,:s cc,..d, ,1,-t::;-.,.., ,·.s /c.k"'-k bt!-. lt.c..-1-no """"#ol-t!'o·..._./ ~:~ld---~, .:;.1/ b.t! pt!!r;l'l"'; llr-.:1. ~ "'" J "'' ~/ ft_<L 1 a..LfJ o C-Ja b)~ ::5'1-r-<!!.55 ;,~:..;-..}&>,-f1._,-.s /.,.,;..d ca.se 5 J.... c.. II ). e. .rt.-.. fVI ;,..; P'l ,,.,.., '""'a I e' ,·.· y·e-/d 5rre-,.. 7}(.- ( 2. 3 4 5 7 a 9 10 ll 12 13 14 15 IS 17 IS 19 20 21 22 23 24 2.6 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010 65 STONE S. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. I DIVISION & GROUP I CALCULATION NO. ~OPTIONAL TASK CODE /Sao a 5 S..21C-1/1= i I i "' v"" i I "\ \.) () " "' .s ~ I () --.() t :::-"'1 \ ;::') t'l,j ~ "'\. \1 ~ ~ 'v) ' ~ ~" \n ~' .., ~ ...... ~ i ~ IV\ rn \1~ '"'"' (Y) \1 "t !.') "-1 ~ I I ~ I ' I ...... ( --.o-..1 0 \j <:) ' IS i) ~· .. ! 0 (l (J t '-4:. l"' (l '-! ~ V) . "'~ .... ~ "'ll -::::: '-.. 'v' ' r--. "\ .... "< ~ "1:.. ~ t ~ M ('<) ('( ..... --...J I ¥11 ~I ::;: (l Ci(l' ~, () () I I-. !• 0 \ h \) v Cl f) ll "' . ' 1;:1 Q ~ " " 0 I! ~ ,, " \l' "'' ""' I \. ....... ' ij c \;; ll'-f' " ~<.,, t I "l ~· ! "'"I ~· (;) ~ ~ \l "' G Q ~ --C) ,. <;. Q \) C) .\: ~ () \) Q r ....:: ~ """ I In' ........ .; 1;)' ~' ~ ~ ~ \:.1 ~ " " " ' . ' "' 'i ' ~ .J "' 't .... • > ~' ' 'U ~ ~: ' < 1:1! -~ ::r ~ ll. .... \l <I( "t ~ \' ~ "" ~ ~ .. t ;;. ,. a <:) . ' I PAGE ;2.~ ( 2 3 4 5 6 7 a 9 10 II 12 13 14 15 16 17 18 19 20 2 I 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 .. 5010 65 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER PAGE 25 J.O. OR W.O. NO. I DIVISION Ci GROUP I CALCULATION NO. !OPTIONAL TASK CODE 168'oo S '5 .2'' -/7F 0,.., c/7 S (_;," •:"! ,-..,.. V~,rJ e'xft"',_S;V-<"! ; a...r-<"! S"/-o,-,.,-,1 o-p; ,.., ... ......, ~ "~~~ ..., f d ... l,._ 5<' l-5 fo,r ,_PrOC t" J.! /...., ":• c/ R..,,~v/h cJ ,, lh-'II ~o,-J:t.,:s Cc. lev/;. /;,c,~ /0_ elf"',.,~-""'~ ,Pr,,-,<t;pA .{! :f:'lr<f!'fft" $" ,:::;< r.d ~ t!?'t'v,"v'f!"/e-.,..1 .>1-r~f.S. 7J:,j /.,..,/or,r>->&.. ·k&/,. , .<: c:Avt')o.l/c...b/~ .io, e&-cL t!"/.,.,,.,f!"',..l a.J //_;-c(".-. ""o,.,// c;.f L /c)>-' 1-'!•dd/r:: «f 6c//o,_ 5v,r/ert"J. 7L._ e/<!!M .::,I e-,.vsv<'lo~l Sl.r'f!"fJt!'.S a/ 4 loj / /"l;dd!~ + bol/o,_., S"v..-./e-c<"r ~r~ f,. !){.,""' ~-I"' .:-I In d'f!"sCt!",.. d,·,_j O,r dt!"r V~'-'j /i:.. ,;Do:/ ,,_c,C,C"JJ'r. ?':C; de./<:< .fo'" /,"'ft. /c:>c.d Ca..'S'<"s ,_:; "'vc. • /c,o I~· ;,.. sl-r..!'..f$,...5 o.l ~ el ..... ,...., ....... I Sur) Q rt'J o,r--' ,..,...,,dd!t: v Polio,.., /-&;.bv/e-1-,.-cl J.,., boH CJt lt.,-s ce-lcvkko,.... loAd Cc.. .fr" .r "'/'l ~C· ~ .:"". ;?~ -2 7 Co,. lcv,r p/e> h of /t..s S'l-.r-<l!'ss c/. sir,;!/-.:,·.,_ I ~ hfo 5 wf-c.c.t!! of /Lt.. e~,.., ~ ... I ~,,., '.)J...oi.Nn. Jc;r No,,.,.c..l Cc"'d' h-C/,... toeo.d On P""7 t!! s 2 8 fo 3 :3 cf fl...,.s c,.._ I e vie. li Cl,_ , .P'/'-<! Obh:../,,.,Ld .Jrt>'""" fZc./1•./ NO, 00/ J /t...... ,....C<.JVAo.<~-<i!l.~d ,..,_;,..;"""'-no/.,-.,1 .::)..._ I£.... C:aniov.-p/ois r< j:u'"t'.fcnf /!-.-. ""A'I(tr>'fv,.,.. ~d ,.....,",.,,... 1/;""'1 s-J.-~.r.J _.6 v..(' Js o:f /(.._ eo .... fovr ),A.J...s ~ $~ v.alv"'.f c;;.,.., ,oJ ~ t?<b.so/v.fc: ""'c.Jt;l'hv,-, tt:>v-..d />'!t·...,,-,...,v,.., s-1-'""i..f /<"vl"l.r. 7i··s 1.1 a ;,~-,,·J.c. l.o~ ,.; /'t..L c .. ...,J.ov,-/!"' fi.,-,., I ro,~-...._,) t:<,..l lf...<_,.,.Jo.rc:._ Jk. Co.-.fpw _?lo,L5 ~iovl) 6e V5~d hr /" )..,,,..,~ko..... pvrpo.S"'S "'"/J. / ' 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 ... 5010 65 J.O. OR W.O. NO. 15lioo STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION El GROUP :s CALCULATION NO. OPTIONAL TASK CODE 'S ..2 u. -I 7!= PAGE 2 6 Le>Ao cASe -I · /1/o!i! MAt.. Cow D J TION /oC I /053 loo'i CJto looo eQUwElAivr :'i"TRESS {PSi) 357'1 z_ 35/C I R,.s,.;lh oi;,~-v ,/ J,l>.-.. Ru-<" •k. Co/, ]., ? · ) 5"5" 7 ~ t;t..ei"'EI>/r EQU/V/it.At'llT et.Err€#7 /'JO, -s-rltef.f ,Vo. ( I'.J i) 1'183 3""i13o I tlJ 7 33 tf/2. 1$8'/ 3 31~'1 1882- 377 32to/ / 8'~/ 3&o '"3 z 1 2o 381 38l :2ooo 18~ 3 357 I '!:<--~ ,""-.; 7 EQUIV£t;WT 'S""TKE:$5 £Psi) :? /o5 J :?5853 I 3L/7~1 I I 3<1257 33'1t.3 3 3211 33 o'7Z 32 750 I ( 2 3 4 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 65010 65 J.O. OR W.O. NO. Is g C)l;) lo 53 lao'J 18'17 looo 3 7'1 STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER 1 DIVISION Ei GROUP I CALCULATION NO. !OPTIONAL TASK CODE -5' S 2 I~ -I? p /:QIJJ VE/..M'T '5"7"JZ£S.$ {f'St) ?3:<./'j 5'11<15 ~l.£t>1EI'I7' ~QVIV!it.AIV7' NO· 5rus.s ( f'St-J 5'"/lo~/ 5 (.) 7..20 5o.?oo 38'/ So13LJ 35'8' /YB'O eLe/"1eN7 EQV/Vl'L,..11'.J-:- Alo 5r,:?£$J (' P;~ J 1%17 57337 ( 5"3 3 '-17 I I 512 .. 7 Z-- 185o 5o371 3 ~/ PAGE..!!_ 158oo-'5'-SZ!&.-/7,C ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 , ... 2~ • lo Cc ¥-ro<.~lii' !. /.v,r 5 A"T !NC.!!.Iir"U'-Jr OF /2 /tf !'S. 15i'oo-~-S21l:.-17F 10 CoNToue Ll"-lE S A-T I II RLRSKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS -,.,~~., p~. M')(-:::_ .iv-•"-" Mf'.l ~ C553 PSt IO C.C.,r-J"TOIJ/2. L1>-1£S Prr IIJC/2./:Mt:N"'r or:: 23 q5 fSt ~LASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS l ""~ 3o 1(/ ' ISB'oo-:5-S.21C.-J 7F ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 H~"" 3ol75 Mi<J "' 7<4(. PSi. f~ 31 IO Coi'JTouiZ-~..,,..,E:;; AT INCREMENT OF' 2543 F'5t MI-l ALASKA BRADLEY LAKE DAM -WYE BRANCH STRESS ANALYSIS 1 r JV!x = 3oJ7S P5 ~ MN -::. 7'-/t. PS t JO Co..JTOVk LINt.$ ftT JNCRe,..f:NI Of-:: z '143 p :s; AlASKA BRADLEY lAKE DAM -WYE BRANCH l ANALYSJS N /0 CcN "tO VIi! l/1'-lt; ':: nr J~CJ2EM£NT OF ;24'3/:"5t 2 3 4 6 7 B 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 35 36 37 38 39 40 41 42 43 44 45 46 ... 5010 65 J.O. OR W.O. NO. 15'Eao s:.o STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER l DIVISION & GROUP l CALCULATION NO. !OPTIONAL TASK CODE -;..: PAGE ...:::...:.._ :5 5 :<.1~-17F c.re ,o./1 l!'f','~r o,... ~ ;!(..._ L/?Lsl ,.....,c..,' j,,;.J 6.--e-,t: 1..) A/o~ If c:J"l ~ :s-•ckl.'f!! ~ r.t lor<!!!-,; l.t... ,.,.., .,.)(,·1">'1 v.-. t'J.. • ,c k ""'-" $5 S"k II I!""~~--t', l.s-;J JZ,../u/'"''j .?L ~ ro,., 1-ovl" p/ols/ lt_c.. 1-/1...;. t...Jcr 51 51--r <' $ ..f<'.; ~ dot.J.,.._S..f/t!'e>o.,-t S"•dt"" o) .f-L.., of /h ;,;,,~l!'!'~..J,i::;._ ~,-Jt.. ft....... /II · ~ j vro r.Jt.,_ 1+L.. lo t:e:. / o.llo(;J.a...6/-<!!!. t.'s ' - '5 occur o,.-, r--1C.,..,; J"'"l~' J .::;Jr.c:;.,.. c i.... .. /J II 6 t./ f .fo vr e /""""' <!"' r> I.!' Ao.ye .s-lr-<!".sse_s- be>/o,_; ft..,·s ~cu . ...J.:::..b/ ~ • 77:.,. ,::"" /.,.,.,...., .,.,. ~ -1 ..> {,.JI-Jt_ /.._;'7J..A.r srr.'f!!.SJt!'J .:::1_r~ c.// V<'r,1 $,..-,•,;/ (!""/<!',..., t!'.-.l.s f:;,~;; Jo,._; /t..,._ St.Ck/-t!' bR&J'A # Jkst!' s~.--<!!'SS~s ~r£ vt!'r7 loc.::-/e<"d 1-o /-".,...__.__ ;-... h/St!!!'chc~ e>f ft...:_ s4 II h. ~ s-,-ck I~ h(l"a,.... 1 t::l.,_c/ pr.oi>c..b/'1 /,~ c.,.,//:t._,_ ~ W'<"'ld b~ .Jt.-i ee"' !t...._ 5'1-..... II a,...l ft......_ .t~ a,...., • 7.C.. ,.,a.'1Jr..t·lz._,cJ-tt5 e>j /t....L.st!"' 5}/:.,:'SSt!'S /s '---'ez// (..Vift,.-. /f....._ /""/Jro.I-,....Vr-t 1it!' /d 5'-!/.-l!',._ 'lit- of It_,_ ,.....c../-t"'r,c-1 ~J •- t~· 75t:~oo ~ t"~ j()/ <("',I /t:.L t.U'Jf!' bre>.rot!'l... s-1-r-t' s; 14. rtOt" t""?e.../ C'oro d, J, o .... ~~ Cons•-dl!'rt!"d ~ 6, w/ho,"' /t....t. .. c;,.£1 c we. 6 / ~ .5' .J / <" .r.s ../u-. i Is C'Jj ~ d <" ;-' ~ ,.. C: ,; It!' r; e::.. / I .&5010 65 J.O. OR W.O. NO. I 15'%oo 2 3 4 5 6 1 B 9 10 II 12 13 14 15 16 17 IB 19 20 2 I 22 23 24 25 26 27 26 29 30 31 32 33 34 35 36 37 36 39 40 41 42 ' 43 44 45 46 STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP l CALCULATION NO. JOPTIONAL TASK CODE PAGE 35 :S 5".2/t;-J7,C:. II Yo/Co-T&s r A.s .Jo, fk_ lc-,. .f>1a,.,, /c;,./ ~ Nole.t"'11"1L CoA/DJ71oN t. oe. J Uf ~ J.., 7 l..t_ Sf-S'h<!'.JSC'_s c..,-f!' c, I/ o, ,lt...,L or ~ bre;.,.C /.. • t!' 1~ /"' t!'"' Is J c. v-<' d ,-t! /d 5lr<!'"'J fi.. P'i- 75coo 7ZL t11~ C"l<"',..., .,,.. I w/~ ~ slr-t"5.:, ol sfr-<'!.! <" > ol /t_._ /j a. Vt'ry 5.-..a./1 .J,-,·o..,., I vlcv ,P/..-.-. ,.,_ :1- C/c.s~ h:> /1...... ,·_, l<""rft""ck,._.. b<!'l •. -..uv~ V<",-J ;---..._._ / ski/ ~d L f.'ckl..-J:;..,,...,.. • JZ.-,; c.~ )>rt"l-'iovs/7 t!"x)fe;._/,-,.4. d.~ pro!:,.,t:,.l~ e;:.._.__, ,..~I G...h I I /:~ tJJ/t"·"' I'L. t.W"Ic/ • 7!.,_,, .-l'r,; :J it' /c/ .... ; •S /lt.",C t' "' Co"' d; ,.;;,,.. l.-JI·tt....,. Ct>" !1 d t! r t"d o-..LI o c..J o... 6 I.e- .J 111 t::).CC("" )Ja.b/~ ) C., ,_,d ~ 1-r< .sS /, .--. 1 J. .5 . 2 3 4 5 !) 7 a 9 10 II 12 13 14 15 IS 17 18 19 20 2 I 22 23 24 25 2& 27 28 29 30 3 I 32 33 34 35 3& 37 38 39 40 41 '---.. 42 43 44 45 46 4501065 J.O. OR W.O. NO. /58oo STONE a WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP I CALCULATION NO. 'OPTIONAL TASK CODE :S 52/t-17;:; Car-1Pvre:R.. P~ot::1CAr>1 :Z:D£N7'j,C;C 11 7' JON ' - 5 tv~C. Coi""!P1.17'itll /'1 1./ rl-lolt 1 '? fl T ION No. /{.t.'l P12.o C. lUI fY'I A.IAMC ' ArJSYS L1t3/CARY 12.EF', NO. I sr 3'1?4 ' VERSION . 04 L~ 1/ E L ' CJZ. r I PAGE 3~ L"''~PUTER LOG Jilt Rllf JOB NO. NO. * 018 7'138 ---- 0);/ ;!.fig ·------ ---- ool ~578 ---- C) (12-· 7''1Z FICUE LOC. PAOf SfCI --· --· -- --- ---- 8 8 W AUTtt. NO. CDC aiAROE NO. PftfPARfD BY IlONA lURE bAlE /)} .l ~-e --._ 'f¥/n ~--'? fl~. ----'is/st.. ~-.., p"" ~ ~~ 'l'lhJ --~-, p_ ·----f'S/tzl IC& l/ CAlClLATION NO. 1'53oo 5-5 21 t.-J7F f./ J t1 JOB ORDER NO. IS8ao REVIEWED BY lcow. ... .. OOUUENIS BIOHAIWE DAlE r:r./!. bl./l/8 I A r--tSys, Rul'-/ l ott D CAS 1:: I ---rf',, Ill\.) s ~, s AvtJ r:y, 17 ~· L o/lt o C 115 f Z.. ----· PosT-· P~Cl. S.f. l<f:!..Ul.TJ, T fl(. }1/-( fl lollo cAS c i ~-'T ~· M~ Po.t 7-P/loCt! J P, £5 VL T_$ l..oA D ~list-2... ---------___._ I ------I • -------- --------- ---------- ----------·- --· -----· --- - H· f.(JllllJTfR OfNfRAlfD J08 tiJUOER ** tOUI'UIERtJS£0 IBBW OR toe' ~ ......, VI ..j 2 4 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 35 36 37 38 39 40 41 42 43 44 45 46 .. 5010 65 J.O. OR W.O. NO. IS""roo STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER a-I DIVISION €i GROUP CALCULATION NO. OPTIONAL TASK CODE PAGE 5 5:216-I ?I= 3c. A77ACHMti-IT /1./o. I ( ) Nooc CCC.IZD/NArt: c; ENE: I<! 11 r1oAJ J' /i.t)/5. ll til M L1SrJN6.. :5 i <: t' f. 2- ... ": "( " ~ 'l ~ ll: ~ (\ ~ ~ I 41 J (\ ~ '" G) \J i! ~ ., 'I ~ij ~ ~~ "' :,:,• "' ~ i ~· ~ ,._, ~! ~ .j ' ... ~ .... t IS G 'il I* /R1664001 JOB DV,PRAKASH, II HSGLEVEL=l /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIHE=l II EXEC FORTXCLG //FORT.SVSIN DD * REAL X V,Z,R ZN DIMENSiON X(iOO),V(lOO),Z(100),XG(lOO),VG(lOO).ZG(100) H=500 ZH=O. c C LOCATE POINTS ON INTERSECTIONS c 1 I=O c 1001 c 10 c 20 4 I* R=45.+0.281874674*ZN COS1=(2.09677*ZN-206.2216)/R COS2=(55.42342203-0.56346l85*ZN)/R IF(COS1.LT.-1.0.0R.COS1.GT.1.0) GOTO 10 SIN1=SQRT(l.-COS1**2) Xli~=R*COSl V I =R*SIN1 X { l=97.944+(ZN*0.817922846+X(I)*0.575327922)*(-1.) VG I =V(I) ZG I =189.01872+X(I)*0.817922846-ZN*0.575327922 J=N--1 WRITE(6~1001) JiXGCI)1 VG(I)tZG(I) FORHAl(~X,'N,', 5,2X,~F10.3J IF(COS2.LT.-1.0.0R.COS2.GT.1.0) GOTO 20 SIN2=SQRT(l.-COS2**2) · X11~=R*COS2 V I =R*SIN2 X { l=97.944+(ZN*O.B17922846+X(I)*0.575327922)*(-1.) VG I =V(I) ZG I =189.01872+X(I)*0.817922846-ZN*0.575327922 J=N-WRITE(6,1001) J,XG(I),VG(I).ZG(I) N=N+35 IF(ZN.GE.98.) GOTO 4 ZN=ZN+2. GOTO 1 STOP END ( .IN T£f25tC1/0N ) Po1N·15 vJ /* /R1664001 JOB DV,PRAKASH, II HSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIHE=1 II EXEC FORTXCLG //FORT.SYSIN DO * REAL XIY,Z,R,ZN DIHENS ON X(100),Y(100),Z(100) N=O R=54. ZN=O. 1 THETA=O. DO 100 1=1 16 THETA=CI-1~*6.*3.1415926/180. X(I)=R~COS THETA)+ZN*0.1 Y(I)=R*SIN THETA) J=N+I 100 WRITE(6f1001) J,X(I),Y(I),ZN DO 101 =17 22 THETA=C90.+fi-16~*15.)*3.1415926/180. X(I)=R~COS(tHETA +ZN*0.1 Y(I)=R*SIN(THETA J=N+I 101 WRITEf6 1001) J X(I),Y(I) ZN 1001 FORMA (~X,'N,',I5,2X,F10.l,',',f10.3,',',F10.3) c N=N+25 IF(ZN.GE.54.) GOTO 2 ZN=ZN+6. R=54.+ZN*0.1 GOTO 1 c 2 IF(ZN.GE.57.) GOTO 4 ZN=ZN+3. R=54.+ZN*0.1 GOTO 1 4 STOP END /* ( St &.1"1(; /'1 T I ~ /* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=60K,TIME=1 II EXEC FORTXCLG //FORT.SYSIN DO * REAL X Y,Z,R ZN DIMENSiON X(iOO),Y(100),Z(100) N=276 R=60. ZN=60. 1 THETA=O. DO 100 1==1 16 THETA=il-1l*6.*3.1415926/180. X(I)=R*COS THETA)+6.+(ZN-60.)*0.1781 Y(I)=R*SIN THETA) J=N+I 100 WRITE(6f1001} J,X(I),Y(I),ZN DO 101 =17 22 THETA=l90.+1I-16l*15.)*3.1416926/180. X(I)=R*COS(tHETA +6.+(ZN-60.)*0.1781 Y(I)=R*SIN(THETA J=N+I 101 WRITE(6 1001) J X(I),Y(I),ZN 1001 FORHAT(2X,'N,•,i5,2~,F10.3,',',F10.3,',',F10.3) c c N=N+25 IF(ZN.GE.66.) GOTO 2 ZN=ZN+3. R=60.+(ZN-60.)*0.1781 GOTO 1 2 IF(ZN.GE.90.) GOTO 3 ZN=ZN+6. R=60.+(ZN-60.)*0.1781 GOTO 1 3 IF(ZN.GE.97.590) GOTO 4 ZN=ZN+3.795 R=60.+(ZN-60.)*0.1781 GOTO 1 4 STOP END /* -, ( ~£.6 ME t-1 T 2 1.1'1 /* /R1664001 JOB DV,PRAKASH, I I MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SVSIN DO * 1 REAL X.V,Z,R,ZN DIMENSION X(100),V(100),Z(100) N=2450 R=60. READ(5 1000) ZN R=60.+1ZN-60.)*0.1781 1000 FORMAT 28X,F10.3) c THETA= • DO 100 1=1 16 THETA=ll-1l*6.*3.1415926/180. X(I)=R*COS THETA)+6.+(ZN-60.)*0.1781 V(I)=R*SIN THETA) J=N+I C1=X(I)+1.776185*ZN-252.7275 IF(Ct.GT.O.O) GOTO 100 c 100 WRITE(6~1001) J,X(I),V(I),ZN CONTI NUt. DO 101 1=17 22 THETA=l90.+li-16l*15.)*3.1415926/180. X(I)=R*COS(tHETA +6.+[ZN-60.)*0.1781 V(I)=R*SIN(THETA J=N+I 101 1001 WRITE(6 1001} J.X(l),V(l) ZN FORMAf(lX,'N.',I5,2X,F10.!,•,•,F10.3,',',F10.3) N=N+25 IFCZN.GE.132.) GOTO 4 GOfO 1 c 4 STOP END I* //GO.FT05F001 DO * N, 1689 78.940 N, 1724 74.891 N, 1759 70.843 N, 1794 66.794 N, 1829 62.746 N, 1864 58.697 N, 1899 54.649 N, 1934 50.600 N, 1969 46.552 N, 2004 42.503 N, 2039 38.455 N, 2074 34.406 N, 2109 30.358 N, 2144 26.309 N, 2179 22.261 N, 2214 18.212 I* 8.201 25.615 34.791 41.595 47.068 51.635 55.518 58.855 61.733 64.215 66.344 68.155 69.671 70.911 71.891 72.620 97.843 100.122 102.402 104.681 106.960 109-~240 111.519 113.798 116.078 118.357 120.636 122.916 125.195 127.474 129.754 132.033 (su;.t4£"-'T 3 "' /* /R1664001 JOB DV,PRAKASH, /1 HSGLEVEL=l /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIHE=l II EXEC FORTXCLG //FORT.SYSIN DO * REAL x1v,Z,R,ZN DIHENS ON X(lOO),Y(lOO),Z(lOO) N=2450 1 READ(5 1000) XN ZN R=60.+iZN-60.)*0.1781 1000 FORMAT BX F10.3 lOX F10.3 YN=SOR (R~*2-(XN-(ZN-60.)l0.1781-6.)**2) WRITEC6 1001) N XH YN ZN 1001 FORHA1(lX,'N,•,f5,2X,F10.3,',',Fl0.3,',',F10.3) N=N+25 1FfZN.GE.132.) GOTO 4 GO 0 1 c 4 STOP END /* //GO.FT05F001 00 * N, 1689 78.940 N, 1724 74.891 N, 1759 70.843 N, 1794 66.794 N, 1829 62.746 N, 1864 58.697 N, 1899 54.649 N, 1934 50.600 N, 1969 46.552 N, 2004 42.503 N, 2039 38.455 N, 2074 34.406 N, 2109 30.358 N, 2144 26.309 N, 2179 22.261 N, 2214 18.212 /* 8.201 25.615 34.791 41.595 47.068 51.635 55.518 58.855 61.733 64.215 66.344 68.155 69.671 70.911 71.891 72.620 97.843 100.122 102.402 104.681 106.960 109.240 111.519 113.798 116.078 118.357 120.636 122.916 125.195 127.474 129.754 132.033 C..C.Mt Nl A ""' /* /R1664001 JOB OV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SVSIN DO * REAL x1v,Z,R,ZN DIMENS ON X(100),V(100),Z(100),XG(100),VG(100),ZG(100) N=500 R=45. ZN=O. 1 THETA=O. c c c 1001 100 4 /* DO 100 I==1 31 THETA=ll-1~*6.*3.1415926/180. X(I)=R*COS THETA) V{I)=R*SIN THETA) J=N+I XG~Il=97.944+(ZN*0.817922846+X(I)*0.575327922)*(-1.) VG I =V(l) ZG I =189.01872+X(I)*0.817922846-ZN*0.575327922 C1=XG(Ii+1.776185*ZG~l)-252.7275 C2=XG(I -0.4765*ZG(I +45.6108 IF(C1.L .O.O.OR.C2.L .0.) GOTO 100 WRITEC6 1001) J XG(I) VG(I)1ZG(I) FORMATC2X,'N,',i5,2X,F10.3, ,',Fl0.3,',',F10.3) CONTINUE IF(ZN.GE.98.) GOTO 4 ZN=ZN+2. R=45.+ZN*0.281874674 N=N+35 GOTO 1 STOP END 'SE C.MEN T 5 t'X\ I* /R1664001 JOB DV,PRAKASH, II HSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SYSIN DO * REAL X,Y,Z,R.ZN N=2850 1 REA0(5 1000) XN,ZN R=54.+t238.5072-ZN)*0.177595 1000 FORMAT 8X,F10.3,10~ F10.3 YN=SQR (R**2-(0.177~95*C2A8.5072-ZN)-XN)**2) WRITEf6 1001) N XN YN ZN 1001 FORMA (ZX,'N,•,i5,ZX,F10.3,',',F10.3,',',f10.3) N=N+25 IFfZN.LE.133.) GOTO 4 GO 0 1 c 4 STOP END I* //GO.FT05F001 DO * N, 745 59.145 N, 780 58.157 N, 815 57.170 N, 850 56.182 N, 885 55.195 N, 920 54.207 N, 955 53.220 N, 990 52.232 N, 1025 51.245 N~. 1060 50.257 N, 1095 49.270 N, 1130 48.282 N, 1165 47.295 N, 1200 46.307 N, 1235 45.320 N, 1270 44.332 N, 1305 43.345 N, 1340 42.357 N, 1375 41.370 N, 1410 40.383 N, 1445 39.395 N, 1480 38.408 N, 1515 37.420 N, 1550 36.433 N, 1585 35.445 N, 1620 34.458 N, 1655 33.470 N, 1690 32.483 N, 1725 31.495 N, 1760 30.508 N, 1795 29.520 N, 1830 28.533 N, 1865 27.545 N, 1900 26.558 N, 1935 25.570 N, 1970 24.583 N, 2005 23.595 11.669 17.249 21.378 24.790 27.753 30.397 32.800 35.011 37.065 38.987 40.794 42.503 44.124 45.667 47.139 48.547 49.896 51.191 52.436 53.634 54.788 55.902 56.978 58.017 59.021 59.993 60.934 61.845 62.727 63.583 64.412 65.216 65.996 66.753 67.487 68.199 68.890 219.844 217.772 215.699 213.627 211.554 209.482. 207.410 205.337 203.265 201.193 199.120 197.048 194.975 192.903 190.831 188.758 186.686 184.613 182.541 180.469 178.396 176.324 174.251 172-~ 179 170.107 168.034 165.962 163.889 161.817 159.745 157.672 155.600 153.528 151.455 149.383 147.310 145.238 ( 5£t:.. r-1C:.N T <.: -{' N. 2040 N. 2075 N. 2110 N. 2145 N. 2180 N. 2215 22.608 21.620 20.633 19.645 18.658 17.670 69.560 70.211 70.842 71.454 72.048 72.623 143.166 141.093 139.021 136.948 134.876 132.804 -0 /* /R1664001 JOB OV,PRAKASH, II MSGLEVEL=::l /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=l II EXEC FORTXCLG //FORT.SVSIN 00 * REAL X,V,Z,R,ZN N=2850 1 READ(5,1000) XN,ZN R=54.+(238.5072-ZN)*0.177595 1000 FORMAT(8X,F10.3,10X,F10.3) XN=XN-3.4763 VN=SQRT(R**2-(0.177595*(238.5072-ZN)-XN)**2) WRITE(6,1001) N,XN,VN,ZN 1001 FORMAT(2X,'N,',l5,2X,F10.3,',',F10.3,',',F10.3) N=N+25 IF(ZN.LE.133.) GOTO 4 GOTO 1 c 4 STOP END /* //GO.FT05F001 DO * N, 745 59.145 N, 780 58.157 N, 815 57.170 N, 850 56.182 N, 885 55.195 N, 920 54.207 N, 955 53.220 N, 990 52.232 N, 1025 51.245 N, 1060 50.257 N, 1095 49.270 N, 1130 48.282 N, 1165 47.295 N, 1200 46.307 N, 1235 45.320 N, 1270 44.332 N, 1305 43.345 N, 1340 42.357 N, 1375 41.370 N, 1410 40.383 N, 1445 39.395 N, 1480 38.408 N, 1515 37.420 N, 1550 36.433 N, 1585 35.445 N, 1620 34.458 N, 1655 33.470 N, 1690 32.483 N, 1725 31.495 N, 1760 30.508 N, 1795 29.520 N, 1830 28.533 N, 1865 27.545 N, 1900 26.558 N, 1935 25.570 N, 1970 24.583 11.669 17.249 21.378 24.790 27.753 30.397 32.800 35.011 37.065 38.987 40.794 42.503 44.124 45.667 47.139 48.547 49.896 51.191 52.436 53.634 54.788 55.902 56.978 58.017 59.021 59.993 60.934 61.845 62.727 63.583 64.412 65.216 65.996 66.753 67.487 68.199 219.844 217.772 215.699 213.627 211.554 209.482 207.410 205.337 203.265 201.193 199.120 197.048 194.975 192.903 190.831 188.758 186.686 184.613 182.541 180.469 178.396 176.324 174-.'251 172.179 170.107 168.034 165.962 163.889 161.817 159.745 157.672 155.600 153.528 151.455 149.383 147.310 ( 5£0 r-1!3'1'1 T C A ' ""' N, 2005 23.595 68.890 145.238 N, 2040 22.608 69.560 143.166 N, 2075 21.620 70.211 141.093 N, 2110 20.633 70.842 139.021 N, 2145 19.645 71.454 136.948 N, 2180 18.658 72.048 134.876 N, 2215 17.670 72.623 132.804 '-- !" I* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SVSIN DD * REAL XG,YG,ZG,R,XN,YN,ZN,XP,ZP N=2850 1 READ(5,1000) XP,ZP 1000 FORMAT(8X,F10.3,10X,F10.3) XN=-98.2529-XP*0.575327969+ZP*0.81792301 ZN=188.8584-XP*0.81792301-ZP*0.575327969 XN=XN-2.2956 c R=45.+ZN*0.281874674 XG=97.944+(ZN*0.817922846+XN*0.575327922)*(-1.) YG=SQRT(R**2-XN**2) ZG=189.01872+XN*0.817922846-ZN*0.575327922 c 1001 WRITE(6,1001) N,XG,VG,ZG FORMAf(2X,'N,',I5,2X,Fl0.3,',' ,Fl0.3,',' ,F10.3) N=N+25 IFCZP.LE.l33.) GOTO 4 GOtO 1 4 STOP END /* //GO.FT05F001 DD * N, 745 59.145 N, 780 58.157 N, 815 57.170 N, 850 56.182 N, 885 55.195 N, 920 54.207 N, 955 53.220 N, 990 52.232 N, 1025 51.245 N, 1060 50.257 N, 1095 49.270 N, 1130 48.282 N, 1165 47.295 N, 1200 46.307 N, 1235 45.320 N, 1270 44.332 N, 1305 43.345 N, 1340 42.357 N, 1375 41.370 N, 1410 40.383 N, 1445 39.395 N, 1480 38.408 N, 1515 37.420 N, 1550 36.433 N, 1585 35.445 N, 1620 34.458 N, 1655 33.470 N, 1690 32.483 N, 1725 31.495 N, 1760 30.508 N, 1795 29.520 11.669 17.249 21.378 24.790 27.753 30.397 32.800 35.011 37.065 38.987 40.794 42.503 44.124 45.667 47.139 48.547 49.896 51.191 52.436 53.634 54.788 55.902 56.978 58.017 59.021 59.993 60.934 61.845 62.727 63.583 64.412 219.844 217.772 215.699 213.627 211.554 209.482 207.410 205.337 203.265 201.193 199.120 197.048 194.975 192.903 190.831 188.758 186.686 184",'613 182.541 180.469 178.396 176.324 174.251 172. 179 170.107 168.034 165.962 163.889 161.817 159.745 157.672 I 5E &I'""'~E ~"'' CB ~ t.,.J N, 1830 28.533 65.216 155.600 N, 1865 27.545 65.996 153.528 N, 1900 26.558 66.753 151. 455 N, 1935 25.570 67.487 149.383 N, 1970 24.583 68.199 147.310 N, 2005 23.595 68.890 145.238 N, 2040 22.608 69.560 143.166 N, 2075 21.620 70.211 141.093 N, 2110 20.633 70.842 139.021 N, 2145 19.645 71.454 136.948 N, 2180 18.658 72.048 134.876 N, 2215 17.670 72.623 132.804 --t: I* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SVSIN DO * REAL X,Y,Z,R,ZN DIMENSION X(100),Y(100),Z(100) N=2850 1 READ(5,1000) ZN R=54.+l238.5072-ZN)*0.177595 1000 FORMAT 28X,F10.3) c THETA= . DO 100 1=1,16 THETA=(180.-(I-1)*6.)*3.1415926/180. X(I)=0.177595*f238.5072-ZN)-R*COS(THETA) Y(I)=R*SIN(THE A) J=N+I C2=X(I)-0.4765*ZN+45.6108 IF(C2.GT.O.O) GOTO 100 c 100 WRITE(6,1001) J,X(I),Y(I),ZN CONTINUE DO 101 1=17 22 THETA=(90.-1I-16)*15.)*3.1415926/180. X(I)=0.1775~5*f238.50?2-ZN)-R*COS(THETA) V(I)=R*SIN(THE A) 101 1001 c J=N+I WRITEf6 1001) J,X(I),Y(I),ZN FORMA (2X, 'N, ',15,2X,Fi0.3, ',',F10.3, ', ',F10.3) N=N+25 IFfZN.LE.133.) GOTO 4 GO 0 1 c 4 STOP END I* //GO.FT05F001 DO * N, 745 59.145 N, 780 58.157 N, 815 57.170 N, 850 56.182 N, 885 55.195 N, 920 54.207 N, 955 53.220 N, 990 52.232 N, 1025 51.245 N, 1060 50.257 N, 1095 49.270 N, 1130 48.282 N, 1165 47.295 N, 1200 46.307 N, 1235 45.320 N, 1270 44.332 N, 1305 43.345 N, 1340 42.357 N, 1375 41.370 11.669 17.249 21.378 24.790 27.753 30.397 32.800 35.011 37.065 38.987 40.794 42.503 44.124 45.667 47.139 48.547 49.896 51.191 52.436 219.844 217.772 215.699 213.627 211.554 209.-482 207.410 205.337 203.265 201.193 199.120 197.048 194.975 192.903 190.831 188.758 186.686 184.613 182.541 ( '5£uMLr-IT 7 ~ VI N, 1410 40.383 53.634 180.469 N, 1445 39.395 54.788 178.396 N, 1480 38.408 55.902 176.324 N, 1515 37.420 56.978 174.251 N, 1550 36.433 58.017 172.179 N, 1585 35.445 59.021 170.107 N, 1620 34.458 59.993 168.034 N, 1655 33.470 60.934 165.962 N, 1690 32.483 61.845 163.889 N, 1725 31.495 62.727 161.817 N, 1760 30.508 63.583 159.745 N, 1795 29.520 64.412 157.672 N, 1830 28.533 65.216 155.600 N, 1865 27.545 65.996 153.528 N, 1900 26.558 66.753 151.455 N, 1935 25.570 67.487 149.383 N, 1970 24.583 68.199 147.310 N, 2005 23.595 68.890 145.238 N, 2040 22.608 69.560 143.166 N, 2075 21.620 70.211 141.093 N, 2110 20.633 70.842 139.021 N, 2145 19.645 71.454 136.948 N, 2180 18.658 72.048 134.876 N, 2215 17.670 72.623 132.804 " I* /R1664001 JOB DV,PRAKASH. II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG //FORT.SVSIN DO * REAL X,V,Z,RiZN DIMENSION X( OO),V(100),Z(100) N=2250 R=54. ZN=O. 1 THETA=O. DO 100 1=1,16 THETA=(180.-(I-1)*6.)*3.1415926/180. Xfll=0.177595*ZN-R*COS(THETA) V I =R*SIN(THETA) Z I =238.5072-ZN J=N+I 100 WRITE{6f1001) J,X(I),V(I),Z(I) DO 101 =17 22 THETA=(90.-'I-16)*15.)*3.1415926/180. X{I~=0.1775~5*ZN-R*COS(THETA) V I =R*SIN(THETA) Z I =238.5072-ZN J=N+I 101 WRITEf6,1001) J X(I),V(I) Zlll 1001 FORMA (2X, 'N,•,ts,2X,F10.!, , ,F10.3,'.',F10.3) c N"'N+25 IF(ZN.GE.15.) GOTO 2 ZN=ZN+3. R=54.+ZN*0.177595 GOTO 1 c . 2 IF(ZN.GE.16.) GOTO 3 ZN=ZN+1.8924 R=54.+ZN*0.177595 GOTO 1 3 STOP END I* 1 St6.McN T 8 ~ ...J I* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=l II EXEC FORTXCLG //FORT.SVSIN DO * REAL X,V,Z,R,ZN DIMENSION X(100),V(100),Z(lOO),XG(lOO),VG(100),ZG(100) N=9600 R=45. ZN=-23. 1 THETA=O. c c 1001 100 4 /* DO 100 1=1,31 THETA=(I-1I*6.*3.1415926/180. X(I)=R*COS THETA) V(I)=R*SIN THETA) J=N+I XG~I~=97.944+(ZN*0.817922846+X(I)*0.575327922)*(-1.) VG I =V(l) ZG I =1a9.01872+X(I)*0.817922846-ZN*0.575327922 WRITE(6,1001) J,XG(I),VG(I),ZG(l) FORMAf(2X,'N, ',15,2X,F10.3,',',F10.3,1 , ',F10.3) CONTINUE IF(ZN.LE.-92.) GOTO 4 ZN=ZN-23. R=45. N=N+35 GOTO 1 STOP END { S E. C. r-""11:-N T '3 "<< I* /R1664001 JOB DV,PRAKASH, II MSGLEVEl=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=l II EXEC FORTXCLG //FORT.SVSIN DD * REAL X,V,Z,R,ZN DIMENSION X(lOO),V(lOO),Z(lOO) N=9500 R=54. ZN=O. 1 THETA=O. DO 100 1=1,16 THETA=(lB0.-(1-1)*6.)*3.1415926/180. X~l~=-i.*R*COS(THETA) V I =R*SIN(THEiA) Z I =350.-lN J=N+I 100 WRITE(6,1001) J,X(I),V(I),Z(I) DO 101 I=17 ,22 THETA=(90.-(I-16)*15.)*3.1415926/180. X~I~=-1.*R*COS(THETA) V I =R*SIN(THETA) Z I =350.-lN J=N+I 101 WRITE(6,1001) J,X(I),V(I),Z(Il 1001 FORMAi(2X, 'N, I. I5,2X,F10.3,.' ,F10.3, ••• ,F10.3) c c N=N+25 IF(ZN.GE.84.) GOTO 3 ZN=ZN+28. R=54. GOTO 1 3 STOP END I* ., ( r-JI /0 :5f,.1!(."'/C. /<c;V7N-/6-/5 USG"O To ?Eri£.RI17E Cc:>o;.'!.OI!Y'ATE S F o;Z SEC.f">{~l7 II /* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K 1 TIME=1 //EXEC FORTXCLG,TIMt=5 //FORT.SYSIN DO* REAL X,Y,Z,R,THETA DIMENSION X(100),Y(100),Z(100),R(100),THETA(100) DO 100 1=1,45 READ(5 1001) X(Ii,Y(I),Z(I) 1001 FORMAT 7X 3~10.3 X(I~=SbRTl(X(I\-7.670\**2+(1(1)-132.804)**2) R(I =SQRT XCll'*2+Y(Il'*2) THE A I)= RCOS X I) R I 100 WRITE~6~1002) ~(i),fH Tlll) 1002 FORMAt(~F10.l) STOP END I* //GO.FT05F001 DO * N 2401 60.000 N 2402 59.816 N 2850 59.145 N 2875 58.157 N 2900 57.110 N 2925 56.182 N 2950 55.195 N 2975 54.207 N 3000 53.220 N 3025 52.232 N 3050 51.245 N 3075 50.257 N 3100 49.270 N 3125 48.282 N 3150 47.295 N 3175 46.307 N 3200 45.320 N 3225 44.332 N 3250 43.345 N 3275 42.357 N 3300 41.370 N 3325 40.383 N 3350 39.395 N 3375 38.408 N 3400 37.420 N 3425 36.433 N 3450 35.445 N 3475 34.458 N 3500 33.470 N 3525 32.483 N 3550 31.495 N 3575 30.508 N 3600 29.520 N 3625 28.533 N 3650 27.545 N 3675 26.558 N 3700 25.570 N 3725 24.583 N 3750 23.595 0.000 5.965 12.958 18.968 23.414 27.079 30.247 33.063 35.608 37.940 40.092 42.095 43.968 45.728 47.386 48.954 50.438 51.848 53.188 54.465 55.681 56.841 57.949 59.007 60.019 60.985 61.909 62.792 63.637 64.443 65.214 65.950 66.653 67.322 67.960 68.568 69.145 69.693 70.213 221.615 221.253 219.844 217.772 215.699 213.627 211.554 209.482 207.410 205.337 203.265 201.193 199.120 197.048 194.975 192.903 190.831 188.758 186.686 184.613 182.541 180.469 178.396 176.324 174.251 172.1-19 170.107 168.034 165.962 163.889 161.817 159.745 157.672 155.600 153.528 151.455 149.383 147.310 145.238 Cor-JvE.fl.TS Coo/ZIJJI'-IIIT£5 Or-J 7Ht IN71i-R5l:.t'T 1t"~'-l To PoLAR Coo,:Z0/1'-JI/T[j N 0 N 3775 22.608 70.705 143.166 N 3800 21.620 71.169 141.093 N 3825 20.633 71.607 139.021 N 3850 19.645 72.018 136.948 N 3875 18.658 72.404 134.876 N 2825 17.670 72.764 132.804 I* 1\) '- I* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50KLTIME=1 II EXEC FORTXCLG,TIMt=5 //FORT.SVSIN DO * c 1001 1 c c REAL X(50)LV(50),B(50),C(50),0(50),R(50),THETA(50) REAL S~U,StVAL,RF(50),THETF(50) INTEGEK I,N N=12 DO 1 1=1 N READ(5 1001) X(I),Y(I) FORMATl2F10.31 R(I)=S~RT(X(I **2+¥(1)**2) THEtA(I)=ARCO (X(I)/R(I)) CONTINU£ CALL SPLINE(N,THETA,R,B,C,D) READ(5 1002) 1002 FORMATl15X) c 12 1003 DO 12 1=1,45 READ(5,1001) RF(I),THETF(I) U=THETFll) S=SEVAL N,U,THETA,R,B,C,D) K=4000+ 5*11-1) XC=S*COS U *0.43019+17.670 ZC=S*COSlU *0.90274+132.B04 VC=S*SIN U WRITEf6 0 3) K XC YC ZC FORMA (2X,'N,•,fs,2x,t10.3,',',F10.3,',',F10.3) STOP END SUBROUTINE SPLINE(N,X,Y,B,C,D) INTEGER N REAL X(N),V(N),B(N),C(N),D(N) c C THE COEFFICIENTS B(1),C(1) AND 0(1), 1=1,2, ••• N ARE COMPUTED C FOR A CUBIC INTERPOLATING SPLINE c C S(X)=V(I) + B(I)*(X-X(I)) + C(I)*(X-X(I))**2 + D(I)*(X-X(I))**3 c C FOR X(I).LE.X.LE.X(I+1) c -, C INPUT c C N=THE NUMBER OF DATA POINTS OF KNOTS fN.GE.2) C X=THE ABSCISSAS OF THE KNOTS IN STRIC LV INCREASING ORDER C V=THE ORDINATES OF THE KNOTS c C OUTPUT C B,C,D = ARRAYS OF SPLINE COEFFICIENTS AS DEFINED ABOVE c C USING P TO DENOTE DIFFERENTIATION c C V(I)=S(X(I)) C B(I)=SP(X(l)) :::,lct<lE /'JvDtS .5H~ll BtJJ,v'l /1 8ov£ --r f-1(:; :INTER Sl t" 11('1/J 1'-1 "' C(I)=SPP(X(I))/2 D(I)=SPP(X(I))/6 (DERIVATIVE FROM THE RIGHT) c c c C THE ACCOMPANYING FUNCTION SUBPROGRAM SEVAL CAN BE USEO C TO EVALUATE THE SPLINE c c c c INTEGER NM1,1B,I REAL T NM1=N-1 IF (N.LT.2) RETURN IF (N.LT.3) GOTO 50 C SET UP TRIDIAGONAL SYSTEM c C B=DIAGONAL, D=OFFDIAGONAL, C=RIGHT HAND SIDE c Dl1l=X(2)-X(1) c 2 =(¥(2)-¥(1))/D(l) D 0 I=2,NH1 B 1)=2.* D I-1)+D I ) Dli)=X(I+l{-X(I) c I+1>=c~c +1)-v(i)J/D(I) C I)=C(I+1)-C(I) 10 C NtiNUE c C END CONDITIONS. THIRD DERIVATIVES AT X(I) AND X(N) C OBTAINED FROM DIVIDED DIFFERENCES c . c 811~=-1. *D(l) B N =-L *O(N-1) c 1 =0. C N =0. I (N.Er.3. 1 GOTO 15 C 1 =C 3)/ X 4 -X(2 -C 2)/ X(3 -X 1 ) C!Nl=C N-1 /~XlN)-X}~-2~)-ClN-2!/(1(~-1)-X(N-3)) C 1 =C 1\* (t\ *2/Clt4)-l(1 ) C N =-.*C(N)*D(N-1)~*2/(i( )-X(N-3)) C FORWARD ELIMINATION c 15 20 c DO 20 I=2,N T=Oli -1 )/B(I -1) Bbi =B(I)-f*D(I-1) C I =C(I)-T*C(I-1) C N INUE C BACK SUBSTITUTION c C(N)=C(N)/B(N) DO 30 IB=1,NM1 I=N-IB C(I)=(C(I)-D(I)*C(I+1))/B(I) 30 CONtiNUE c C C(I) IS NOW THE SIGMA(!) OF THE TEXT c C COMPUTE POLYNOMIAL COEFFICIENTS c " vJ 40 c 50 B(N)=(Y(N)-Y(NM1))/D(NM1)+D(NM1)*(C(NM1)+2.*C(N)) DO 40 1=1,NM1 B1Il=lY11+1~-Y(I))/D(I)-D(I)*(C(I+1)+2.*C(I)) 0 I = C 1+1 -C(I))/0(1) C I = • C(l C N INUE C1N)=3.*C(N) 0 N)=D(N-1) R TURN Bl11~(Y(2)-Y(1))/(X(2)-X(1)) c 1 -0. 0 1 =0. B 2 =B(1) c 2 =0. 0 2 =0. R T RN END REAL FUNCTION SEVAL(N,U,X,Y,B,C,O) INTEGER N REAL U,X(N),Y(N),B(N),C(N),D(N) c C THIS SUBROUTINE EVALUATES THE CUBIC SPLINE FUNCTION c C SEVAL = Y(I) +B(I)*(U-X(I)) + C(I)*(U-X(I))**2 + D(I)*(U-X(I))**3 c C WHERE X(I).LT.U.LT.X(I+1), USING HORNER'S RULE c C IF U.LT.X(1) THEN 1=1 IS USED C IF U.GE.X(N) THEN I=N IS USED c C INPUT c C N•THE NUMBER OF DATA POINTS C U=THE ABSCISSA AT WHICH THE SPLINE IS TO BE EVALUATED C X,Y=THE ARRAYS OF DATA ABSCISSAS AND ORDINATES C B,C,D=ARRAYS OF SPLINE COEFFICIENTS COMPUTED BY SPLINE c C IF U IS NOT IN THE SAME INTERVAL AS THE PREVIOUS CALL THEN A C BINARY SEARCH IS PERFORMED TO DETERMINE THE PROPER INtERVAL c c INTEGER I,J,K REAL OX DATA 1/1/ IF (I.GE.N) 1=1 IF(U.LT.X(l)) GOTO 10 IF(U.LE.X(I+1)) GOTO 30 C BINARY SEARCH c 10 20 c 1=1 J=N+1 IF U.Lt.X(K ) J=K K=1 I+J )/2 IF U.GE.X(K ) I=K IF J.GT.I+1~ GOTO 20 C EVALUATE SPLINE 30 DX=U-X( I) SEVAL=Y(l)+DX*(B(I)+DX*(C(I)+DX*D(I))) f\l ' RETURN END /* //GO.FT05F001 DD * 104.000 0.000 102.000 12.000 96.000 22.500 90.000 30.000 84.000 36.000 72.000 46.500 60.000 55.000 48.000 63.000 36.000 69.500 24.000 74.000 10.000 76.000 0.000 75.000 INTERSECTION 98.383 0.0 98.158 0.061 97.283 0.134 96.013 0.199 94.763 0.250 93.535 0.294 92.329 0.334 91.146 0.371 89.988 0.407 88.854 0.441 87.746 0.475 86.666 0.507 85.613 0.539 84.590 0.571 83.596 0.603 82.634 0.634- 81.705 0.665 80.808 0.697 79.946 0.728 79.121 0.759 78.332 0.791 77.580 0.822 76.868 0.854 76.196 0.886 75.566 0.918 74.977 0.950 74.432 0.982 73.931 1.015 73.476 1.047 73.066 1.080 72. 703 1. 113 72. 388 1. 146 72.121 1.179 71.902 1.212 71.733 1.245 71.613 1.278 71.542 1.311 71.521 1.344 71.551 1.377 71.631 1.410 71.759 1. 442 71.937 1.475 72.164 1. 507 ., '\J V\ Ql.-1 1'1) .... LIUn ........ 0..,. ..,.10 ..,. ..... NN .......... /* /R1664001 JOB DV,PRAKASH, II MSGLEVEL=1 /*ROUTE PRINT DV /*JOBINFO REGION=50K,TIME=1 II EXEC FORTXCLG,TIME=5 //FORT.SYSIN DD * REAL X(50),Y(50),B(50),C(50),D(50),R(50),THETA(50) c 1001 1 c c 1002 c 12 1003 REAL S,U,SEVAL,RF(50),THtTF(50),RR INTEGER I,N N=7 DO 1 1=1, N READ(5,1001) X(I),Y(I) FORMAT(2F10.3i R(I)=SQRT(X(I **2+¥(1)**2) THETA(I)=ARCO (X(I)/R(I)) CONTINUE CALL SPLINE(N,THETA,R,B,C,D) READ(5,1002) FORMAT(15X) DO 12 1=1,45 READ(5,1001) RF(I),THETF(I) U=THETF(I) S=SEVAL(N,U,THETA,R,B,C,D) AC=0.25 K=5100+(1-1)*25 RR=RF(I)*I1.-AC)+S*AC XC=RR*CQS U *0.43019+17.670 ZC=RR*COS U~*0.90274+132.804 VC=RR*SIN U~ WRITE(6,1003) K,XC,VC,ZC CONTINUE FORMAT(2X, 'N,' ,15,2X,F10.3,' ,' ,F10.3,' ,' ,F10.3) STOP END SUBROUTINE SPLINE(N,X,Y,B,C,D) INTEGER N REAL X(N),Y(N),B(N),C(N),D(N) c C THE COEFFICIENTS B(1),C(1) AND D(1), 1=1,2, ... N ARE COMPUTED C FOR A CUBIC INTERPOLATING SPLINE c c c c c c c c c c c S(X)=Y(I) + B(I)*(X-X(I)) + C(I)~(X-X(I))**2 + D(I)*(X-X(I))**3 FOR X(I).LE.X.LE.X(I+1) INPUT N=THE NUMBER OF DATA POINTS OF KNOTS (N.GE.2) X=THE ABSCISSAS OF THE KNOTS IN STRICtLY INCREASING ORDER Y=THE ORDINATES OF THE KNOTS C OUTPUT C B,C,D = ARRAYS OF SPLINE COEFFICIENTS AS DEFINED ABOVE c c USING P TO DENOTE DIFFERENTIATION 5iCIC l L ELIH"' J-.loDE.S BELoL,) THF S'IIELl J.N7t.Ji!StC71C>r-l lv '-.) B I =SP(X(I YIII=S(X(I)l C I =SPP X /2 D I =SPP~X~I~l/6 (DERIVATIVE FROM THE RIGHT) c c c c c c C THE ACCOMPANYING FUNCTION SUBPROGRAM SEVAL CAN BE USED C TO EVALUATE THE SPLINE c c c c INTEGER NM1,1B,I REAL T NM1=N-1 IF (N.LT.2l RETURN IF (N.LT.3 GOTO 50 C SET UP TRIDIAGONAL SYSTEM c C B=DIAGONAL, D=OFFDIAGONAL, C=RIGHT HAND SIDE c Db1l=X(2)-X(1l C 2 =(Y(2)-Y( ))/D(1) D 0 1=2,NM1 B I =2.*(D I-1)+D(I ) Dlll=X(I+1)-X(I) C 1+1)=(Y(i+1)-Y(I)l/D(I) C I)=t(l+1)-C(I) 10 CONTINUE c C END CONDITIONS. THIRD DERIVATIVES AT X(l) AND X(N) C OBTAINED FROM DIVIDED DIFFERENCES c Bl11=-l. *D( 1) B N =-l.*D(N-1) c 1 =0. C N =0. I (N.EQ.3.) GOTO 15 CI11=C~3)/(Xt4)-X(2))-C(2)/(X(3l-X(1)) C N =C N-1)/ XlN)-X(N-2))-C(N-2 /(X(N-1)-X(N-3)) C 1 =C 1)*0( l**2/CX(4)-X(1)l C N =-.*C(N)*D(N-1)**2/(X(N -X(N-3)) c C FORWARD ELIMINATION c 15 20 c DO 20 1=2,N T=D(I-1)/B(I-1) B(I~=B(Il-t*D(l-1l C(I =C(I -T*C(I-1 CON INUE C BACK SUBSTITUTION c C(N)=C(N)/B(N) DO 30 IB=1,NM1 I=N-IB C(I)=(C(I)-D(I)*C(I+1))/B(I) 30 CONtiNUE c C C(I) IS NOW THE SIGMA(!) OF THE TEXT N OQ c C COMPUTE POLYNOMIAL COEFFICIENTS c BCN)=(Y(N)-Y(NM1))/D(NM1)+D(NM1)*(C(NM1)+2.*C(N)) DO 40 l=l,NM1 B~Il=1Y11+1~-V(I))/D(I)-D(I)*(C(I+1)+2.*C(I)) D I = C I+1 -C(I))/D(I) C I = . C(I 40 CON INUE C1N)=3.*C(N) D N)=D(N-1) R TURN c 50 Bll =(Y(2)-V(1))/(X(2)-X(1)) c 1 =0. D 1 =0. B 2 =B(l) c 2 =0. D 2 =0. R TURN END REAL FUNCTION SEVAL(N,U,X,V,B,C,D) INTEGER N REAL U,X(N),V(N),B(N),C(N),O(N) c C THIS SUBROUTINE EVALUATES THE CUBIC SPLINE FUNCTION c C SEVAL = Y(I) +B(I)*(U-X(I)) + C(I)*(U-X(I))**2 + D(I)*(U-X(I))**3 c C WHERE X(I).LT.U.LT.X(I+1), USING HORNER'S RULE c C IF U.LT.X(1) THEN I=l IS USED C IF U.GE.X(N) THEN I=N IS USED c C INPUT N=THE NUMBER OF DATA POINTS U=THE ABSCISSA AT WHICH THE SPLINE IS TO BE EVALUATED X,V=THE ARRAYS OF DATA ABSCISSAS AND ORDINATES B,C,O=ARRAVS OF SPLINE COEFFICIENTS COMPUTED BY SPLINE c c c c c c C IF U IS NOT IN THE SAME INTERVAL AS THE PREVIOUS CALL, THEN A C BINARY SEARCH IS PERFORMED TO DETERMINE THE PROPER INTERVAL c c INTEGER I,J,K REAL OX DATA 1/1/ IF ( I.GE.N) I=1 IF(U.LT.X(l)) GOTO 10 IF(U.LE.X(I+1)) GOTO 30 C BINARY SEARCH c 10 20 c I=l J=N+l IF U.Li.X(K ) J=K K=!I+J)/2 IF U.GE.X(K ) I=K IF J.GT.I+1~ GOTO 20 -, ~ '4:> C EVALUATE SPLINE 30 DX=U-X(I) SEVAL=Y(l)+DX*(B(I)+DX*(C(I)+DX*D(I))) RETURN END /* //GO.FT05F001 DO * 66.000 0.000 60.000 20.000 48.000 37.000 36.000 48.000 24.000 57.000 12.000 65.000 0.000 71.500 INTERSECTION 98.383 98. 158 97.283 96.013 94.763 93.535 92.329 91. 146 89.988 88.854 87.746 86.666 85.613 84.590 83.596 82.634 81.705 80.808 79.946 79. 121 78.332 77.580 76.868 76. 196 75.566 74.977 74.432 73.931 73.476 73.066 72.703 72.388 72. 121 71.902 71.733 71. 613 71.542 71. 521 71. 551 71.631 71.759 71.937 72. 164 72.440 72.764 0.0 0.061 0. 134 0. 199 0.250 0.294 0.334 0.371 0.407 0.441 0.475 0.507 0.539 0.571 0.603 0.634 0.665 0.697 o. 728 0.759 0.791 0.822 0.854 0.886 0.918 0.950 0.982 1. 015 1.047 1.080 1.113 1.146 1. 179 1. 212 1.245 1. 278 1.311 1.344 1.377 1. 410 1.442 1. 475 1. 507 1.539 1.571 LJ c 2 3 4 6 7 a 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010 65 J.O. OR W.O. NO. I 15'lt:~~ STONE e. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP I CALCULATION NO. I OPTIONAL TASK CODE .s :5'.21'-/71: ,4 I 71'1 C #/>! /1:1'1 T NO, 2 I l E .rt4t..vl"'710/'l O.F SICKLE BEll/VI 1),;-$16N c: WAI'IC::tr r I PAGE __!__::> 5 -·- ) ) INSTRUCTIONS 0817-6 ...,. l.--L - -SENDER-RETAIN YELLOW COPY. FORWARD WHITE AND PINK COPIES. RETAIN PINK COPY FOR FILE. INTEROFFICE CORRESPONDENCE TO: C T. L 1 LOCATION SUBJECT 1 REFERENCE 1 J.o. No. ts-Bot:J, C8 .. r : 1--:F=:Ro::-:M-=-: -])--=-,...:..w-.~P=-o-7-7-~--r~----+~k-L~-cA-T~-oN-1 PmsTOC.K OJye -BRAtfCr-t SICJ:.t€ BFlf14.1 MESSAGE: lis w~: 'Diswss€:!J ~ S'/C/(Lt" ISG+"1 H;tfs ~l?t::?J £aJts-ifJ ) "TO Pl<.eiiiOt: AlJDtrto~llt MA(I?l(ll11_ 0(.) TSI{)€ T/11: IAJEZ.D ~ /"'ff~llt ITS IU:s IST7ht.JGI:( "rt> 1..1/Htit.L;JI( ~tAi6. A CcMplfltStorJ OF '71fEi OI{IGIA!A'L AND R.£\JIStD Q:,I'JFIGUie!lTl.o'\.J IS P~tOEJ:> ON i1f£ ftT7;+eHf!:!) SH1:!E(, 7ic HAX/1\.llJM JAJC/lffl-£F IN MA-c~ IAL 14) APPP-try.. IMA-1lFI..f 3 ~ P(e=ASE"' fCEV /tiN T1ft; wy 1£ De-s l~AJ -ro l>rrt::""RJII/Wt I r- /-29~ 87 DATE REPLY: w o u lO fH11/€ AAij c.t.: w. S.~ TELEPHONE ~ ;, }I v-<,..<!' ~ oJ ft.-_ ,-t!!v• ·s~ d c;"', ),-l vr-&::< j.,-o,... c-f ft._._ $ic.l</ t! b~.:;..,..,.... P~ ft..._._ t.-J7111! -hrt:!."" c/.. Sf/-<' LS t:A .., el /7 s ,-s IS J<./ d7.u.J /lo/-~ .t~ .s', / ..,,./.u-e. ..... / Yv.skh.ce:.·kc.-. ,_s ?""ov·-d.,d ,...lc . J5oCJo-s -21? /7F DATE SIGNATURE TELEPHONE - ' CALCULATION SHEET I I I \ \ \ \ \ ~\ \ \ /J7Til cfiM€/V T STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATIO. NO. REVISION 1£/Too-:;; -S.216-17F .3 QA CATEGORY I CODE CLASS 0 \f) ,<:: 0 .._I -\I 2 3 4 5 6 7 8 9 10 II 12 13 14 15 16 17 18 19 20 21 22 23 24 2~ 26 27 28 29 30 3 I 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 45010 65 STONE B. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER J.O. OR W.O. NO. 1!: 0 oo I DIVISION & GROUP I CALCULATION NO. !OPTIONAL TASK CODE 5 5'" . .:uc-1 7r PAGE_!i_ ~ }d/e.w,_.i ar'Jv,..,..,, 15 {!IJ.r.,; h fv·s J,-/.1 J~ e,..,_,,~,-~, jvd~,,.,t!',..f I'A.c..-f Co,-,},·7 vi'A.~D.--O.t:i!:< p/e.b/~. - r~vJ-S"t!'d :;r,·c: k I-<! J..-o.,..._, c.) 6) c.) -n::.. r..,,.k 5tr.us oavd ;;.. ...t.... /"7c.,..,,·/e.;d sL /I 1\.-t..~>-r lt-..A. c..f_.., x of L .S•c k 1~ 6.., c..,..... . I,-, /iJs l'e'i'("" J H....,..., ij no c./...c.,.'j.t' )'ro}os..-d /...- ~ !{'".·ck I..-b<41t-. C""o"' j.,·? vreo.lc.,-,. P..,a.k 5'fr..-:ss~s 6r~ v~,.-'1 /occ.---l 1·,;;-f'd. /1.:..&~r C /.._c.'"' '1 ~ r ;,.. <Jl!'or"1 .!" lr7 .c.. -I r~ /e. 1,·;---.., 11 1"""'1' ~ d /S fev-c·-c 5 )reu-. ft,..L v .t"'J, etr-o/ A ., t. S/r<sJ Wt/1 /10~ aJJ~c~ IL. 5f,-...i'~J l<'v<"ls. ~0-.......41)1.1''7 .~-i/ "~ J,·,,. o.-d J1....,.... Lou.../ h<!!ne:/,",_ i &A..f !Z-tt ,..,-,,-d Co ... ./,., /,.., j.,,.s J, ~ I...., ...t:Jt ,., It~ s, t"'"k !(! 6~ c.,...,_ A;; S fr_.-ss /"'1/A"'/I~·I.d .c:<rL' t:> I L /YI. c.. "'l 1/~ /"" Jv,.,ch·c;, 7[..,.. '>• ck I< 6 _..,A,...... ,·s r< Ia. k "''f" 17 rAj J ,,. c-o ..... }:u:..o·.sc"" wd·~o J2__.,__ rv; 1(;<;"1JJe~ld s:-iv II ~ o. a/ ...I, -h o,.,_ c. J .r;, e:. / ~ ,.., C'-t t:Jv fr /c/ ~ lz_._ I sf.....L 1/..s t.,.vl/1 ,.:.. t:r.f' t:L,U' Jt..a._-,, 7 ,cJ, ·~-; g) ~- b'a""'. /-/ot..JI?v..,r .I ~ I""Cr.<f!'.-.:>1!!!' ,~ or ?'I r ti'A./ '! /,..,-9 -tt: ey-ve-" .;,-~-; vV, J) ,., of r~svll ,,.. lfk 5'''!"'·.:kc~,...f CJ...e--.; I' 1:. L (o,..lv,·bu}ia ... h 5/-r.ess dtd' ;;>b l't..-.:. l&~cJ .b e',-,d;~ 7 of-tt.....-51-I/~ A 5010 65 J.O. OR W.O. NO. t58oo 2 3 4 5 & 7 B 9 10 II 12 13 14 15 16 17 18 19 . 20 2 I 22 23 24 25 26 27 28 29 30 3 I 32 33 34 35 3& 37 38 39 40 41 42 \ \ 43 44 45 4& STONE 8. WEBSTER ENGINEERING CORPORATION CALCULATION SHEET CALCULATION IDENTIFICATION NUMBER DIVISION & GROUP CALCULATION NO. OPTIONAL TASK CODE 5 52/t-1/F- PAGE 5 c:>? 5 77:..L S"t!!cA:e.,.. J='""cf,rA·"'s ~J.. ~ s~c,{a.... .si.ac,...j,., On J'A7f!' L/ t.;.JI"/1 b"' o-/1,,-'lf!"d W/h.. ;lt......L_ ~d.::~,-J,-p,.,._l Stck.l-<. lu!-:a,..., ,....,e.I."'>;·.,_._J, ~ ce,ln>,·d /!..J/:1/ / .. k~/7 ,.._,,pv-!' vj>~Nc..rds. Jlo.,_n.!'v~ / / .:::. f ~ fop of h.-:5 t"' ..-J,c....._ ~ ~""'~ Ct jo,..-. -~ <!)f ~ .::J.r-<1' 1!. ,·s )>,..-c: ,..,d...-,::·:! j, 7 ~ ~t._,_ll) tii1A-,.d ft..,·s J...J:/1 ,.e>J cJ..o,<; • .e 1 ~ r~sv-1',£,· .... 7 CJ....c.,...'j~S ;,.., e::,..-e>rS-· S<'..-J,e-- ?"'t'f,.rh~f!"S 5J....a~,;/,J b-' 1__...5"'7.'"' ,)., re.,.,-f. L ,...-e lev .e _..~ !t......_ c(;,., .fr.".bvJ,-&7..... &:7! .b ~c.,...... b~f'.d,:-..e; .fo ~lr.t"5S 5Aov/cl o....lsc roJ-h< :::;:.-,,.~ h C"Q..n 11 7 a /1-t!!r~d. I \ . .,r- A 5010.64 I FRONT) STONE E. WEBSTER ENGINEERING CORPORATION CALCULATION TITLE PAGE *SEE INSTRUCTIONS ON REVERSE SIDE CLAENT s. PROJECT PA 'BR-JlD Lt''--1 LA!'.;::- CALCULATION TITLE {Indicative of the Objective)·. PE.rJS~C)<. ArCOc:::: r "S?aLT:::. ~Lf+rdCt CA LCU LAT ION IDENTIFICATION NUMBER CURRENT OPTIC NAL J.O. OR W.O NO. DIVISION E. GROUP CALC. NO. TASK CODE :r2, r__;,.~ s:; '"' r I /8 i '7 ()~. '-> -ol ·<, ' - * APPROVALS-SIGNATURE E. DATE REV. NO. INDEPENDENT OR NEW PAGE 1 OF 2Z- QA CATEGORY {V) 0 I-NUCLEAR SAFETY RELATED OII om 0 .JJ/-- OTHER OPTIONAL WORK PACKAGE NO. SUPERSEDES CONFIRMATION *CALC. NO. * R EQ U I RED { V) PREPA RER (S)/DATE (S) REVIEWER(S)/DATE (S) REV I EWER (S)/DATE(S) CALC NO. OR REV. NO. YES NO tu . .u , 'P orr eJt. ("', /. L J:. v(A 0 J. --1--. F ... hJb[ i-13 -<1-r ~~-·J,u I l-1 ~' ~7 I' ~t =: flvY~~D jJ~ c:r-7!..· >';,-"1(,;-'7 ~ pll''~ . A I. ~ -,,-~" ;:~:Y - DISTRIBUTION* I I COPY I I COPY GROUP I NAME E. LOCATION I SENT GROUP I NAME E. LOCATION I SENT I (v') I I (v') RECORDS MGT. I I ./ I I FILES (OR Fl RE I JoG So~i.... I I I FILE IF NONE) I c:,4 ::-,u: I / I I I I I I I I I I I I I I I I I I I I I I I I I I I I I l ! l I CAI..CULA TtON SHE-I J...O..I'W..u.l c.\4.C:l.IUT1aN-.. I"CVI.S3• I ~uc .....,,0 •• ! '5"8 0 0 ' 0 2::. -s; -2 ; ' -'_?> •:'>< I'<OC ...... CII I o:!ATC l"""":•cii/CliiCC:Xlll IO ... n: i INOCjOL'WOC.Itt' "(VU'IrC.!L'O ... t'11: """ r-~,... .... ~ lt.-.d-3:, r. 7 Lc 1-111-37 tJ/A ...... ':_,~J' -.su!_..;•~· 1 r1 rt.:. I ,J~ :.lr:!:l(llt'l' I;:::::(; CI.~.S I _; ... I'J C""'"'j :::: P.cc t=-::. -':::r...f-t):::,.;:. '2ot.-:tJr ') f_:... TABLE OF CONTC:NTS A."m HISIORIC OAT A (R.evr.uons. Additions. Odc:!:ion-s, C:r::..) f'AGC: I Oe:.sctlP'nON I OR.IG. REVISIO.~ I I :-40. REVIEW Rf.\-fARKS .'«). OA·.::. I --;-,__ I ! I 1"'1'1 ~ \.Jp..r,t_ I I ,.....--I I ~. Co 1-S"i::::.t:; '"'"'J . i hG uc. or:: I I l \ I I I I. I s ( ALCuL/'r1 <J:.).) ..;U!-AM/ti?Y) I l i I Ass u,., f>'ri_;:; ~;;: ~ )€:, I CJJ / I I I I 1-8 Y:JA-rA ' I i I be's,v PeR 'S'au-I I I I 9 loA-D~ I I I I ?HT ~'R.A-J1 r: I i I !o ~.-·D ,?"<. I I l -' I I I I 1 ! : Sr_)o ;,_~r I l I I I I I t '2. ,.- ' PP._,..p C E!Y6AG•.N< EJJT I I ! -I 13-1$"'1 '201_., I I : E Lll r-JG f:7' ~·.'y.J I I i t ~ . j I ! I \Oo(ki!J& btrrr.. -~~ I I I i ' A1-A3 Wr<PI<'AJ~ <;:; c;:-( A 'STJV! ~ Dt: fu '], I I I ! I I I I I ! ; I I l ' ' I'"' s Mt::: I APP~o" r I ~~lc r-"· o I l I I ±?1 MovuLr !lF f3i..As'""7c' _.., ! I I / CA CU AT 0 S M A L L I N u M RY 1-J,O.IW. O.ICALCULATIOII 110. ltEVIIIOII I3~F •5010.62 ; c:&oo. o8. s-)-.?fr. I -'.3 0 2'2- CL I ~~~,.;r.,/!ltO.J EC!-, Q A CATUOitY I CODE CLASS '[.) ... ':I fV f.(' ('::.I : {! > -!J r--' . SU.~ICT I TITLE tl.r·--· -........_ j..il.::r-lS~ c_r, ,/ ' ...... '~ -:::: ' -,_/'LX:' -..,. -tJ·'- o•.IICTIVI OP CALCULATION To D~J l G AI 'Jt..tc \So~.._r:::, Fo~ li+f 9' () /1 Tb 0 (AJ s '"":) ,::_ .l::. Prcr ... .,. c::' I "-t="' ~_, !="' LA,.JG.I? I b e-1-;;cr<...M.• .U E t-.1\E'IL..faO O!::. CP.f_ .f.J. .·I~ ?,::.:_~ '""'"C::> uA..t-JiiJ.J'~ C't.._Ar-JGE ';'tf>AP A-rUJ....J UAJ Ot:.k' 0::! P-C .• /J .:_) . CALCULATIOII MITHOD/AaSUMI'TIONa S-rvo1 / A sTill! A s--e:-4 J1fJG b:S;J )../ !j~ I . ~ A.Ju rr '11:) Be I ,1 2. Au"'w ,418[ [ f~) -o "3E NJ !till M !JM DJ:" o.z;;-rE;) 01( o, 20 (J_,.. s_ 3. '3avr;, "'0 "Sf \)(;<::; 1Gt.l Tt:> o F=Fs e--r 1\JO!l.Mfll L.o A .0 I ..VG ,_.._) .-:.....-., J-HJ.!'...t?':: 5 f. PAR A-..,.( OJ\,.) s-% :".f....t 4, p~ID€ .5-rn.t:--s s R.!c£.1+ kk'f 4>10 /A) )~( ""'!' f+:::-----:r::~ . -~ Fol<.. ;..t-.. aouac11 Of' DATA/ IQUATIOIII t. De:.r ~~ ,_) Cr;r~} PARr ~ ) fr .,...:.AN 5, () I ~-iZ'J , 0 /(.) .· ·-::IE 2> ) ' "' 8uc ;',A ANA-L S'Tt"e<. (oN 5 ..,.-0 C. '7" ..J:¥J t;: I C.H":' l£o '-::...-,,J ~a:;::) .;. ' c:>r- ~-----I =< MACH I A) f!<.<t '; 1-f.A--N b ;oo k' '20 ,J.··Z,. Ut.:JIO~G €""'. ;1 (. ;C.....,..c. - '-'· @)I T'4AI 1 I , :' :.:;:, ' .--/)-; ·-;,:,fl-_ , .. ::.~ .... ) J .. " P~ce:s r;;: <;>u 'p M f:AJ1' Dr::-: 1 G JJ lJ~w.V«.U.. ~ Vou,.;c 1'1)C U_) IL~~, 4-, ) ; J -S77tNOARO 1-f.Mo Bock ;\ll~:c :....~ry c !!-<_ r ft.X:, ,,.JI::C:.P ( ) ~-1A~..."'-s "'"'" I-A /" ' '-' . .t:::.ofl. I-i::C: ~oJ (.l')~/I.W--:(.. :;,. ~INlet::; I( !N(;. 77~"-'..l. o D!.iM/hl-" • ·.:;.. Kr;ytJat..o s f! Pr::.."-t:/'.1.:; 19'7., I ' l ' tl 7 \N6u: .. uJG 1) f\--rA ·. CAA~J;~.JT'EfZ S''MwU:~s s: ., Tte'L ( AT-rP,-:_I~I·;;,JJ ..... A 1-A3) CONCLUIIOIII ~P..tW 1 C f / . I~$ ) r_ 4 /z." VJ/ 4_ ,,LG I ... 1.72 ) -2ii AJ6MttJ frt. 'STVO') '....o,.;G "2 ..... .. G'JI-Jf~ t 2Sjt;,'' cp s r.lfJ c-r. IJun s'~Lc r>~ P...~: AOS Ef'R.j-1 \;1\.J[l "' - '· " 3'%(1 cf '2;,--l.. 'I t..>/ 1.. y u a u~ . -r?-ll'l4: ;;,o ) . J:j r} (. r-; ; '-'f.'.-.. ,~ X ff'C(..f z... fJP..R·:~-:,5/:::J U5 rAIC l:-f"C1l-r WIT'-fi 12 "u;. /2~6 vr--f-..''ci ! ~ f----c:tJ., I A.J 5 a Tl:!V !A) k!ld i..:..0Lf' 11\..J S'r>JD Po{2.. 8 Hrr.J\) ~:;, )_)t.J.,......_, -s~< .. t G«. .R.oT~1'e0 ~I 0 1--~. if'fll b I t;7\J T sJJua Pas -_.i)(J. aEVIIWIIII (a) COMMENTI ""~ju -9 Vtfh DATI I; -L~S t I ~'Vy'/ ' ~ ~ ! IIIIVIEWEa ICJ~KIIII DATE i cT , /-) 'j-?? llfDEI'INDENT lllrVIEWEIII DATI CALCULATION SHEET 45010 61 PREPARER /DATE D.w. Po..,..,...~ SUBJECT I TITLE l~ :-3 '~ STONE & WEBSTER ENGINEERING CORPORATION J.O.IW. 0./ CALCULATION NO. REVISION PA&E Is-Boo . o B -S S -2 :fl ( -I 8 4 QA CATEGORY I CODE CLASS N(A ! /, 77~ S-rt~..O 9oL~ ~ JJU"7; !__) 5 t::l) I A.) ---~ IUS -t n /, ) S:ru.i:J,S A ::'I .A Asro4 f7ipq ~30 ,'' I • s::::> ,q,..;o IV f./"!!" s~;'-)€ ,' "1 j / ' I Fy ;:: /O) /<.si_ UT~ ;:: 15CKsC:. Nu75 S!~~L 73"10 l..I~Uif) AJ/7"'1'(./j)C:£) AFT'G'R M.~c.:..,J /J ~':.) (.A j ~ 1 -S/!r_u, 2.) D~:::S'sAJ D~su P..k~":.; c.) tJortMA\.. ro4o psL LAs 1:Jr-J b) E_,_,Ui:,~G ~;;-t-Jo; B4s-'fS\.. -1 ABlt0 c_) t X C.. <:.1->TL orl f<\-/6~ o r~~ d) Pl4:s.s u~ ~s-r s~(j ( 3.) ALLoVJAQ.u:. STj!::..e~S E:5 J,._) 0) ~DR_""M_ <:.A<.;E : Mti\.1/MUM ot:= ~ o. z.~ C!r ) .. o, 25" (to5"k,-J ~~ D. '2.0 ~~ \J T S J -= o :?. 0 ( l ~;; J = CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W. 0./ CALCULATION NO. IREVISI ON A>5010.61 /59oo, 08-S\ -2(pr -1 B 0 PREPARER /DATE :0 ' I-<_) , '"':::> (y·;---r':::;p IREVIEWER I CHECKER I DATE I INDEPENDENT REVIEWER /DATE IZ-3-8(;_, c'T"'L1:. l-lfl)-i7 SUBJECT I TITLE -::> E'l...l s-~:> c ,_,. IQA CATEGORY I CODE CLASS t:'LA-tfr,r: ~11... TI~G ;\1 //1 "BP«st:a ltJ bn 10..0 At.:ArtA.J f'+SU:: :3--;t'....J::-~ -(' f~~ J; 0 "0 :;::-6 _..-K:, • --G:, ........ ) f'+IJ_;;-..J)f''3'"" f+tL~J/''3' < /\. '' '-·-""CN V5' (, 12'"-D , ::J 5 1~s :_ ~L~ ~~ .VAitlA"f'lD,tJS IN ?~~-r,QJ, ~:. 1 !t::l"""f Ci-te-c..K \IS. 7o "'o lYrELD ) ::. 0t7 (lo)J --:_ 7 5' ls ~ +) (N6-r~: 'Dts.l(:)f0 C..f?l~!P. A~$ es% Ytt;;t.[) '=-tt' ,·,_... . ...),-.,-n::.r-) ffH'> /i-SSu/ll!flloA> @ Jt-% 1$ C-11W>C::P'II""(')G h.)(') -:-.. •.. r: r€" ,00-~_...v) 1:.0 . ?r:tovl.lJt: FDR 5'% s~s. Rl:::LA)CP\'"'tl o,...J f,fiEfl.... ( SIN!L~ 'TC> A\S( 1::.61-\fv\8-1171~ ol.j MTM A3:/.5"" SaLTS ; A/5(. HA-l-0li,A-t.) Fe· ~ '-;--"...{~,..) JQ.7) OT~ D!AM t(I::HZ. oF 6-R.tr-.JG. CALCULATION SHEET 45010.61 SUB.JECT I TITLE r.-,_)c--)c..:' flc.z..v~~ ~ p ..J 0 (!) STONE & WEBSTER ENGINEERING CORPORATION J.O.IW.O.ICALCULATION NO. IS" 8 oo -<;: s-.?& f -I~ REVIEWER I CHECKER I DATE r. T L Z I I '7-~7 .. I~ "' ~~ '· .,. T~: \... ~Q "'"' ~.~ In l i _-.;: I .a ~I REVIll ON PAGE (:, QA CATEGORY I CODE CLASS ;v lA c. "--}.1 :::; \.n d ' ~ -.!) ... ~ ., "" "'-' \; "'-V'l <: -.) I--l-i-......., ...:!.. ~.::-. v p b 3 L CALCULATION SHEET A5010.61 PRt:PARI!R /ptJt: __ ).w. 0• eR SUB.IECT I TITLE pli.:t-->'S't?C.. :_ Acc.>::c: STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATION NO. /58oo.o8 ss -2-f.:,j-/S REVIt:WER/CHECKE'R /DATE 12.-s-3(:, cr.-~_[ t-,c;-17 REVISION () QA CATEGORY I COOE CLASS JJ /I'~ e.) Sc~ Tl~.Ao:;. suA\.\_ ~E ASP.., S. PITCH c.. 'JS>£ 'JN~ '.i::\-rd<.tJA-<- tlfA-.t:fl<vs. tt> rNf~l/l£" FAn &U~ STI!A:N67"'-! oF fl-o-o'f" nf~A D -\ Qep fv1A<J.l fN 1::~ ':;, ~hJO Boo!: 2 C :!;_ E'D r:r"'<4N J (!:; Bl::31l(, '?1' .AL, , 'c -~ , P4, 12.7 8) Bolt Soar>danl Th,..d Tobie IO.A. Boll Data {157) (Courtesy ol Taylor Foroe & Pip.e Works) Minlmum 8-thre<id S.ri .. Bolt Spucintt• Rndial EUge .. "1\:ut Size :\o. ol Root No. of Root :\Hnimum Pre-Dbuance Disfnnct' Dimension d Threads A,.., Threads Area B. fcrre~l R F. !a('~ Oats) ]i" ~l" %:" '!" l" ,,, .. ~~~-- J:l'u Jlf' I'!" J:V" . P-i" ... • /1, I ll 0.1:!6 No.8 IU" 3" l~f. " ··;" .. II 0 202 tlm<ld I'~ .1 a\, ;,( 10 0.302 $oerles ~~ 3 Pi l~{. 9 0 1!9 below!" !!its. 3 p~ I ;'if 8 ()_ 551 8 f) 551 :n~ 3 I~ H)~~o 0.693 Oi21 2t~ 3 Jl'i l>i 0.890 g 0. 929 21~. l IV, IJ~ I OS. I 8 1.155 3'\• 1 ,, 11& 1.29~ 3 1.~05 1~~ IH ~lt L3.15 1.1.110 3'> 2'' J ., > l. j ~l I 930 ;p~ Jt:l,' H~ 2 0.19 2.:W.L ~ 11! 1!i ·Pi !.100 2.652 ·~-~ :!'·l ,, "' 1.fl20 3 -123 p~ :1% 2'4 t 3. 7J~ L .292 .:p~ 31~. !!(i ,, 61& 5 2;)!) -'>% 3" :!:~ 5 621 6 :'i:!l fi I~ 3% z;, f"enter-tu-<enter distann hft•·een bohs. inches. 'i• .. " .. ll II IO ' • a & • ' a Tablo 13. Screw Threads for High-strength Bolting (AU dimeuiou io iod:t,a) 0.001 t.oo 0.00 Maio< diam ....... --Mu pitch diam• Ma. ,XIeb M- diam ...... ...,._ -- Nut Nut Nut .,; ..... .... miaor diam plt<:h diam ICier· di.t.rn• Nul .... pi\eb dl~ toler- O.OOS6 0.0059 0.006-1 0.0070 0.0076 0.0079 O.OOal o.ooeo l.f79 0.11 1.000 0.01-11 l. I :I'll 0.01 2.17~ 0.0110 1.37ts·o.ot 1.4JOS o.om 2.619 0.11 1.t.ll 0.0124 0.0148 1.931 0.01)0 1.0148 ).If 0.01)2 a.ot-~a 1.4321 o.onJ Tt.:-A meO.:.D •t&Ddard fCinl ol ~ tlhal1 'be u.aed.. Pi&eb diamew:t ~ iacn.de..,..... ol &.d ...., •~~~~tko ~ - ...:.!!:"mu.&mWnpit.eh~ol.....,.ue~tJs&.tbe~umpttdtdiamc...,.~-au~bythelt 1~" 1'!4 }I~ 1J I~ I'• ~·~. 2:.,-\6 23S 2'"'ftl 2'; Z 1 ~6 J!' 31~ 3'; ~H l% Mn'\imum t"illet Radius ·~ " ''>• ,, ,. ' ;_,' i' :·;' .. ., ,, ., \ II., it f'C-. v CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &501061 r.I.O./W.O./CALCULATION NO. I REVISION I PAGE 153 CIO . 0 8 -S S' -J ~ ( -'5 3 _ 'REVIEWER/CHECKER /DATE ~INDEPENDENT REVIEWER/DATE 1 2· L -:3::. ('' T L z. /-19-l' 7 - SUB.IECT I TITLE P'-erus r::>c)( A~-...r I QA CATEGORY I CODE CLASS c-,_,..,0'S r:: 'SoL-JX, /'1 /.-t) 1. ,A-::-I(_ 1-h.:: ...... o-r 5"'1""'::::~1... = o. lo Bl'(. ·~ r::: 1[) ( Kt·F •I I Ph,.jG 'JMA :::::0/.Z C;tP Pc-A.J 11c'L S77a:-'-) /0. " / --.;;, """ ' lo ):. •:.J ) Ar-rP..~.)-11" ;:l'J-A L ) I ( , s4J 2 'Jru I p(;l{ As f1t AnuJ 0,, ..:... M9LE T-0 :) ~;--1':'-:c -~ - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CA. LCULATION NO. 'REVISION I PAGEc;> &5010.61 PRE PARER /DATE D' w' D:) "L'""'""~ SUBJECT I TITLE 1?-']-8(;. /c;?j Oo. (.)C -<;'S -zr;:, ( -18 a I IREVIEWER/CHEfKER /DATE liND! PENDENT REVIEWER/DATE C(..:A_. ;-1€f-8] Pl2:'u:::~-:: < f'+cce---: IQA CATEGORY I CODE CLASS 8{)LT/r-.lG: ( DIA NotM~ : I 95:'}0 ~ .. ;...) c~.J.o f~~) -- \ r ,~o ~ ~ I 5J...u G /'::>6 '~ 'J) l ::5 0 - /f'Nit£1J.GfJJC 7 : (900 :; ~) (84-)fsJ -_ i< 'z C) . ,-:5 I :; c () )o) ---.::> l.f)cc.~:.-fJ-rcorlfJ-L . (CJ0o;·.;., , (to;;;o(5~) ' ~ = 1.75 l _, :)oo - --re::;r q )jo ~..:. ) ( 9G.Ots. z) J ~ J ,3 7J.ou<· :::: - lo Ace o uJI/ 7 rol{ CA-$'e_ , --I'R-~ 72_ ''j) ' ! I:::.:!"I&AJ Gl ~ok o, 9s- ~o\..TS Lo.4[Js \t Lotto ) -:::::- ' @ -1-;c;-(o @ -t rr% (los001.7J ~( Cj S"" 1;/ebl T) ft.-/V D 5'/C£:;:: <:: ( / 0 5 yeo l ...-) :..u ;-~ ;;:.o!JC:!r;-~'c..:.tu -5" <7a ( 8 s-1 f.!, vr ') e I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION l..t.O./W.O./CALCULATION NO. . . IREV1810N IPA8E &5010 61 /~oo.oa S"S'-2Co(-lo <:::::.-> /o PR~AREit/D~ ), W, · o !'""7ldZ !REVIEWER/ CHECKER /DATE I INDEPENDENT REVIEWER /DATE iz-3-9ra l-tCJ-.f7 SU8..tECT /TITLE b EIJ~.....,._) C.'<._ hcc ~:'c "> l.lttJ G C .7? t> r ... :r ~1 c; (SoL-r \ 'l)~<.s •GI'J ~.o Ao s. I ~.N 'r ) = ( fJ"TE: '51/VC.t; -rf:-/1<; i(_n~v-r( dA o,z I> /Ur( A l!iU:"::>T~ s5 l Cl'tO V/1-1(! ~--(( OA1 1::; LoAP) IVC..,.- 'P::=: ) o 5 I=' I . e:"' I ' . ..f "" () J <SL J4G "/fat r I r:, <;' lu:, i.. L75 IQA CATEGORY I COOE CLASS 'N ~l":·c ,C..A_':::.' "\ \ . -' ) :_I 0 . 3:"JL/ - CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .. 5()10.61 J.J.O.IW.O./CALCULATION NO. 159.:J:J,6.9 -;-s:-20( IREVISI ON t PAGE 18 ~ /; PR~PARERI~TE :_::;, 'J,), ~::;~o:_p IREVI EWER/ CHECkER/ OAT£ c.T'Lz t-t,~t7 IINOEPENOENT REVIEWER/OAT£ SUB.JECT I TITLE .--, A Y~I\J 5~(1( Crt.:.-:; o::: I QA CATEGORY I COOE CLASS :5TU D 'S leE : WILL B'f = \\ 4.o 4 -+ 0 , s-'2... \ o.1 Bs-4.. I \ o. :;-2._ ) C_Mwa,4( r::..•A -:::: ' --{.-'""---- ( ") l 2. 31 'ZS S H1\Fr ( rf:h:.: Vli:'JUJ S(/& H-1' Yl-:.Pc~: $ ~ _., , r, _/ llue -rt> MANY t-tt1'JS<NVf'r1''Ut::; MSUMft~r: -'Do No__.. 1/VC!UJ':>= ,._, 1g .-/'JCe:r -t-:~/17' f..v.)ur..o l'?rct::c:-v Mt/'JO~ btll. ) Ac;u~ A{(.RA ar: Sr+f\F=r = {J,(6')(fl.:.31ZS'11 2.)-(~·5'<):: 4.oo "'~·_,-, 1.o:;y~ r !Jc. -:; -zC,."2J'I._,~ v 1' -4-,oo sf.;, ~ ~.f.='~ ' 'l::. "'->~ " 95" ~n r -!--t .._ '2'$. 7C::: k$i_ ~ 1='£ ": ..,.. () 0 '5<(,(,., "'2ta~ ..(~ 115"-IJSo..cr-2.8. 7s ,,,..~ -::: 4-, 0 0 '!\,;.,-::: < c 4'2.'. .c -_,; -,l. 9-1' _c; 1.5,o L(e,,_IJ 35!u:,r: t, -..f._., oo -;. c:::. /O£t..r "6 ~ """ ~<.?(c 4 l?o ~ie&~.7 -:::-+.e-o s~' :::. 32,j;..,i .:::. 1i 7St..5 -- ·,'-"" ~ 'l't::r .... CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 IJ.O./W.O./ CALCULATION NO. 'REVIll ON I PA8E !5Boo ,o8 -ss-20/-'3 o 1'- PREPARJR /DATE b . VI. Po r-:;::1< IREVIEWER/CHECKER/OATE IINOEPENOENT REVIEWER/DATE I L . '3 8 c; (, T L 1:. 1-I ' ~ y 7 1='"'--1\"-'G<:::: ~ O!.'lif'..lG IQA CATEGORY/ CODE CLASS Rt"F' f1Ac L 1'1 :;<~>-:; ___ ~~~~ ";"' «) '4/J-'i:-!::,; I ~WI 197 E:. 0 i!Hf I' c; , i!'Y fH 11~ !i 0 a) /4!&;, ( --- 8 ,. -?, 3 9 :::> :: = (J '2 ( 0 ( /: ,, 2 2.. CALCULATION SHEET &5010.61 SU8.1ECT /TITLE ct.. I'], "'"""r ~--A c (_'2:_ <; "'' .:..J 'C:T\7_)J f-A • -===·"·=· Nu/. -I !It:;; "17-f"E C~::;NTCI(J j~ -z/IL 1>4"' .. lc i +<tP A STONE & WEBSTER ENGINEERING CORPORATION .1.0./W. 0./ CALCULATION NO. /s-aoo t o<B -s s-2G, f -/3 REVIIWIR/CHICKIR /DATI t2-3·B,.C> c rcr.. J-1?-87 ()r ~ ,11./1.)7';, 5'' fl , ., r 1<" 5 j-2/',_ 1 > .... AS~UM~O kFEet-rr:J 1£ LI::./\JC.((-1 ,.. /2. !:1 11 1Jo1..r \i:L.o~AT~ F L!huG ~<:" ]) t:FoA. }!!A( £..Or.) ~'-.,.. \?1.-.o A) 6tr1 ~ Pttv/h. BoLT at=. rp REVISION PA8! 0 /J QA CATEGORY I CODE CLASS p .9.. &.,.._ "!"' G/AJU:: !0-'.:::: Q) )JE'&Lte::'", 21 ~ ...:, ~-~-1"~' e; ~ e, ·~-:-) CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION 1110. Jsgoo, a& -ss-21al- 1-/J-8 7 IRE VI EWE!!..!.:HECKER I DATE C. I L l 1-!')-87 I INDEPENDENT REVIEWER/DATE SU,.IECT I TITLE VeJJ5i'JCK A u:F-<::: I QA CATEGORY I CODE CLAS: .. _:,..; )/1. 8oLr II 7T}((Ji. n""2\ = 11 F ~ /..f. l'' 1 -"2-) =7 ~PR.€S:Sta~ k~ IN J!' (.J!I-,J 6~ ? Ql=UW~:tr A Fu.,f;' f{.hJ6( p QB~r A Bo-t. r E:r.,.~r / ,_QV'"...- p \:_A ~""-,.. S tx:n_.... + Q Fyt>:~G.t" A M..!f,.JGf ==-F~J~f 'I· I( .R~r ., 12.t;(' j !'t..,.::: 4. ::.~ c,:, Y .. l'~ .,. !'::) (.1 TLhJGC;. 17/<:;; sfm M-? (~._)t~'~ >~tf,.i{ ('~'~-:! .. y,9,~;to'0l) - -r ( I. o1 :x(o-1 "-0. 'LO [JD-~) '7 Jc:-.... ' ' ! ...,/ , t; ~-/"" / Z9. Z. ,Xr 0 G fsc· z9,9 .\ ~, ~._" CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION •5010.61 1 .... 0./W.O./CALCULATION NO. Jl!lf:VIOSION IPAG;f:...- 158CXJ, o 8-<SS-2ro I-I 8 -:;, IRf:Vlf:Wf:R /CHECKER /DATI llNDf:PENDINT RIVIIWIR/DAT£ /-13-87 (' T L t I-,~-17 IQA CATEGORY I CODE CLASS h AIJ6F 'f?oL illl.f ~ " 'JJ /B I J ,.,J y -=r.~/eoLI ,f~· q) AQ= 0. 6 r Zo 11 Lo,.,J) ~= II '?-::: ~ / ) A~ o. t:.\ s5 l! 11 MA'f' LoAD loS PoLr '-Pi! .9 -- • \I ~= S5k/~t.r (~.9) 4 _Q_ = ul o/ 0 ~ 11 fl\11\..l IA>FIP (( s-Y~~ 6~ /{)) 0, of4Co t; ~V\ER-GtN~ lofli) 1'->-::: A~ -=- '· P~".SUi!_,t;-~:::: i3o Yeot.1 ( ,,, ro) IJ~ C>. o/ " ~T -c 1 -/ r· '---~""C.K s~~'SE"::. l'F Rt;AY:;te ot l::!..oA)GAf'c.cvJ 1 ' SfJe:~; =~ 20 l\ As 0. u \ 0 -t-o 0, D l 3 q !J!) ~ 7= J. 27~/0-1%) t:J, 0/0 I< 11 27x ;o -.<t ;:{ o, 0/3" ),7_ 7'!<( 0 -41:,{ ..... /0 2 YsoLT :: 2s-. c, Fl_= 2 k, <: r ,· 5~~s -=-1 /<st. <( s~ !..+., "~ C/:::... - '/ s~'2"() r=; R-A-10GE As o I o 1o'' 0, 013 (( ltJ CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION &5010.61 I J.O./W.O./ CALCULATION NO. 'REVIll ON I PA.GE !5Bao. o,B-.cs,-20 ( -18 /(o PREPARER /DATE ) '1-U , rD,.,--'::'~ !REVIEWER /CHECKER /DATE !INDEPENDENT REVIEWER/DATE C C !. c ;-1 ~ · i7 SUBJECT I TITLE '7" j.,.JI;f·J'---::l c..!<. rr ' r: ( WN'> r:_-,; Uk'{·J~.;:7 I -~ocr-. 0~10\i. c;"TlJ D ~I ,4-t-.J 1J Y;_ ,, f'.Ju"T) ~ I QA CATEGORY I CODE CLASS ~I ~ uJ/ \ + Jo o .'='" SUJ •A)G: ') " ( -2.o c 1.$ L.. '}{ G> •. S l+rtF7' J ¢ f.;..,cc-!f..) '3( 318 (/ ¢ ) -----------------------------------------------------------~-~--------------- CALCULATION SHEET .. 501061 SUBJECT I TITLE PE,J<;..,..., CJ<. /. STONE & WEBSTER ENGINEERING CORPORATION .1.0./W.O./CALCULATION NO. REVISION Is-Boo. o8 S5:.-2(p ( -18 R!VI EWER/ CHECKER /DATE 1 2-4-86 c 1-I')-i>? QA CATEGORY I COO£ CLASS ,/ --lui') Mef'~o '.,.;oiJl!J /?.~:::>·,·,.,~ 1-/IG,f+ n:!PtjUf: ( ~ J.) ..). 2 ..f 2.. ,, V{PFtCULr ])ue: -ro J '·' 1)e;:, !G 1\.) loAO .,. Dt::slr:.,u 0. 0 \Ob 11 i\L~o \-\1::A( ~ l.::.'xfll'f'JO (), O(b G 4 :::: /o" CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .0.5010.61 1 .1.0./W.O./ CALCULATION NO. IREVISI ON I PA8E Is-Boo .o8-~S-2./;:;;-~a o 8 !REVIEWER /CHECKER /DATI I INDEPENDENT REVIEWER /DATE C/LL 1-1~·.87 SUI'.JECT I TITLE 1<<0"/')'S....,~CI:~ Acc:-sc ::J,JGE" I QA CATEGORY I CODE CLASS '1)1£)1 ;,rl e~.:: i'-1 A-)c l-o.f\0 Mr/\J LoAo {), 0 D 0 3 4 7 y, fto-r'P.1' ~,,.> ,r----~· IS" o.o\Zcl• --0, C06J<f..7 foP-o"P."'-C-'- -- ':: CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION IJ.O./W.O./CALCULATION NO. , IREVIIION IPAeE A501061 PREPARER/D8E '{), LU · 1> 7-:-::::R. ISBoo. us -ss--2-:b 1 !REVIEWER /CHECKER /DATE './:"l~ ,-,9-?7 +20LTIJJG. /3 () 17 I INDEPENDENT REVIEWER /DATE I QA CATEGORY I CODE CLASS To A ~ u 1J -r f=df/ != LJ4 ..u::;E P. C11 ,.JG A:, 1-feJl.?"' :; lt.Jf:. 1 PS s '..Jr~·:.:: 6 0 EFF< '::-;.J'Jf 5L.e-w hcA7' 71'/J-~~-· 't";:) r:....f'rJGE;J i• - /A..) ( A. I R. SPfr<-E 'f"F4:n.mO SlfAF-r WI !..L I I i -i -- -·--+----- I I 1 L I I I I I ) I /(o.$., ····--"; ')z. 7 If r :U.!.Y:.~r \. I 2.. '&. I 4--..: 19.7 ( 19. 71: o. I o !STYt b 'I') ( llo I';;)/ o,roo 53o BTU kw·~ 530 BnJ/-' /3TI2 0,/"5"'45 )~ ~ l s-4 UJ ' \-t7\ STONE & WEBSTER ENGINEERING CORPORATION .. 5010 61 CALCULATION SHEET I .1.0. /W.O./ CALCULATION NO. l REVIS I ON I PAGE /s-800 , 08 -S ~ -2/P ( -/8 o ZD P~PARER/D~TE ~. w, · orTJ_O:IZ IRE VI EWER I CHECKER I DATE /2-..{-BS c./.LC 1-19-37 I INDEPENDENT REVIEWER/DATE SUB.IECT I TITLE r~"'-l1 C 1-Ak';. T'o;:.R(_,.-Cit-Pl... lt1JA1tl'tf!>L~ 1/\j 1Je"' ---'5:> % ., 'J.r."""A--r 9 ( 6. 49(::, /• ) ' D,A A pt:::qc:ry ..JG SO w,4--r:'"s /4-, ~I 3o6· "'-'· ~•N 'oo 0 'J..JM-:":_. TI-ft:: I~ I QA CATEGORY I CODE CLASS ~ /54 4.). H-"Z -I 3'oo w "-!rAJ / c fr" .C-tJY~ II P~. 9~<} Crt.:~,._ :-_; ::-__.._ ;'-'-' ".:_,rJ f ) ) % ~ I h'5 > cH/"-.'-If/" -? fA.) ST{) z I. _;..:--:;:.P"P. ,- S--ry) ~ flKJ!::A.JT /zoo a s--uo . ;/0'< ;U!':EQ 1-h::~r'O( LorJG 2 3 Q 0 w.,... •,a;:) --:::... l-z. 0 0 '-<h"~-/zo-o I (7." CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION 1 .1.0./W.O./CALCULATION NO. IREVISI ON I PAGE &5010.61 PREPARER /DATE D· W. Po-r-Ter>- SUB.II!CT I TITLE Pr-:r Jc-:; (.I•_ !~Ct Jc:"8oo. o 8-r-s -2~ ( -/9 2 I !REVIEWER/CHECKER /DATE I INDEPENDENT RIVII!WI!R/DATI! · 2 -A..-8 S c . 7 L l I -1 VJ-1'7 ;.-. IQA CATEGORY I CODE CL.ASS 1-r.;+-,JGI~ ..-'<n .. .,-MG "-lr.)T '.NIL<... .. ct~·l..k_ 't0C. I(_AQ 11'\-L. I.::K.jJ fWs I urJ ~ 8Mtc_ PI wfJ f) (I+;/ :::· '=A:.. \. 2 ' 4/ 9 3 : ) ~ ; (Z·~ 83 ')( 2fjc>" )(C.'~ X (G) -y .. F) ~ /1-!1 s /5 1) .~I"""'G z..) -rrrc ?..A lB. ) NuT 3) 1/1/.s 1;, -r1h /l/'1 ,JGe o;::: -- C)l0024 /k/'?'c-£) Ct. i:frP /r..l ::.( /)/A? &;A.J£' / ,r.; _s- .Q/( - 0 ' 0 2..2 '? :; ,_ ....> 'I CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION .. 5010.61 I.J.O./W.O. /CALCULATIO~ NO. / .;-3 c::> o . o 8-~ s:--2G I IREVI EWER /CHECkER /DATE ''--4 -Br;, c. T L z-1-,c;-i7 SUB.JECT I TITLE LtV""'::>~· , ; -,~--~ :. --.... 4-'' __ j ___ _ f/6" ------~ ~ f1. '' I z_ " -----··---------'=--------___..-1, IREVISI ON I PAGE _/g 0 z_z_ 'INDEPENDENT REVIEWER/DATE I QA CATEGORY I CODE CLASS ST\J D s. -AY'M AS(:,4) Typo; &-~0 ~I; s-_) ~~\<.. AU. wrz IJ titS '13 z_ RAD _I ~~ I 72.... f2..~'D ?, " "" I '-o ., ,-. MUT5 144 u~' .) !+<:. "Tf'.J.. 3 /(--=-l(_o ct I ·-'"""'-....···-.• "·"". :-; ' ( ··, ·~~?'"''"'''' ... -·--·· """ __ .. ,.,,,...,..,.::.t~· ..... '-41rt..__. Ai Carpenter Custom 630 (17Cr-4Ni), Continued Relative Machinability of Custom 630 (17Cr-4Ni) in Various Conditions Turning Speeds tor C. .tion Comments Screw Machines ft/min m/s High hardness and strength limit machin- H900 ability, especially in mill-2Q-30 0.1D-0.15 ing and forming. Use car- bides for max. prod. A Machines comparable to 6Q-80 0.3D-0.41 1 (Solution i Treated) Types 302, 304 Machinability improves H 1075 as hardening temp. 7Q-90 0.36-0.46 increased Machinability improves H 1150 as hardening temp. SD-100 0.41-0.51 increased Best machinability, H 1150-M comparable to free-1 OQ-130 0.51-0.66 i machining Type 303 PHYSICAL CONSTANTS: Pspecific ;ravity A 7.75 I Density lb/inl 0.280 kg/ml 7750 Electrical resistivity (RT) ohm-cir millft 589 microhm-mm 980 Magnetic permeability at 100 oersteds 74 at 200 oersteds 48 Maximum 95 Coefficient of thermal expansion "F ·c 1Q-6/"F K-1 I -100 to 70 -73 to 21 -- I 70 to 200 21 to 93 6.0 10.8 i 70 to 400 21 to 204 6.0 10.8 ! 70to600 21 to 316 6.2 11.2 70to BOO 21 to 427 6.3 11.3 Thermal conductivity "F ·c 300 149 - 500 260 - 860 460 - 900 482 - ! Poisson's Ratio - ' c::~ ~ific heat Btu/lb/"F kJ/kg·K f-~ L 12"F(O to 100"C) 0.11 460 Welding: Custom 630 (17Cr-4Ni) can be satisfactorily welded by all methods. No preheating is required. Properties in the weld comparable to those of the parent metal can be obtained by suitable postweld heat treatment. Weldment design and welding procedures, as for any high strength steel, should avoid concen- tration of welding stresses at sharp notches. FORMS AVAILABLE: Billets Bars, hot rolled and cold finished Wire and wire rods Strip Tubular Products Condition of Metal H900 H 1075 7.80 7.81 0.282 0.283 7806 7833 463 - 770 - 90 88 56 52 135 136 10-&/" F K-1 1Q-&/"F K-1 5.8 10.4 -I - 6.0 10.8 6.3 11.3 r 6.1 11.0 6.5 11.7 6.3 11.3 6.6 11.9 6.5 11.7 6.8 12.2 Btu/ ft/hr/" F W/m·K 124 17.9 - 135 19.5 - 156 22.5 -· 157 22.6 - 0.272 0.272 Btu/lb/" F kJ/kg·K 0.10 419 - H 1150 7.82 0.284 7861 -- 59 38 71 1Q-6/"F K-1 6.1 11.0 6.6 11.9 6.9 12.4 7.1 12.8 7.2 13.0 ---- 0.272 - 109 I l I I -6<..c_-i-t ~2>oo,(>l;>-ss,7c,l-lg ArrALf+M<,v-r /11. CARPENTER CUSTOM 630 117Cr-4NiJ ( v' DESCRIPTION: Custom 630 (17Cr-4Ni) is a martensitic precipitation/age hardening stainless steel offering high strength and hardness along with excellent corrosion resistance. It has good fabricating characteristics and can be age hardened by a single- step, low temperature treatment. It is used for a variety of ap- plications including oil field valve parts , chemical process equipment, aircraft fittings, fasteners, pump shafts, nuclear reactor components, gears, paper mill equipment •. missile fit- tlf10Sl, and jet engine parts. · . . . ( • .lm 630 (17Cr-4Ni) mee;s specifications AMS 5643, ASTM A-461 , A-564, MIL-C-24111 . and many others. CORROSION RESISTANCE: Custom 630 (17Cr-4NI) withstands corrosive attack better than any of the 400 series hardenable stainless steels, and, in most corrodents. its corrosion resistance closely approaches that of Stainless Types 302 and 304. Good resistance to stress-corrosion cracking is gained by hardening at temperatures 1 025• F (552•C) and higher. Erosion- corrosion is also withstood well due to the good combination of corrosion resistance and high hardness. Surfaces should be entirely free of scale and foreign particles. After parts are finished, they should be passivated for 30 minutes in a solution of 20% by volume nitric acid contain ing 3 oz. per gallon (22 glliter) of sOdium dichromate at 120/140•F (49/SO.C). Follow by a water rinse. HEAT TREATMENT: This alloy is hardened by heating solution treated material , Con- dition A, to a temperature of soo•F (482.C) to 115o•F (621•C) for one to four hours, depending on the temperature, then air cooling . The various heat treatments are as follows: Condition A (Solution treated): Heat at 1900• F (1 oaa•C) ::25•F (::14•C) for V2 hour, cool to so•F (32.C) so that the material is completely transformed to martensite. Sections unrler 3" (76 .2 mm) can be oil quenched and sections over 3" \ 'Tim) should be air cooled. '--. .Jt use in this condition without age hardening due to low toughness, poor impact strength and susceptif?ility to stress corrosion cracking. Condition H 900: Heat solution treated material at soo•F (482°C) for 1 hour and air cool. 108 (517400) (ASTM Type 630) Condition H 925, H 1025, H 1075, H 1100, H 1150: Heat solu- tion treated material at specified temperature :: 15•F (:: a•c) for 4 hours and air cool. Condition H 1150-M: Heat solution treated material at 1400• F (76Q•C) :: 15• F (:: a•c) for 2 hours. air cool : then treat at 11so•F (621.C) :: 15• F (:: a•c) for 4 hours and air cool. Removal of Heat Tint: The light discoloration or heat tint resulting from age hardening may be removed in a pickling solu- tion of 10% nitric acid and 2% hydrofluoric acid maintained at 11 0/140•F (43/so•c) followed by a short dip in 30 to 50% by volume nitric acid at room temperature. It is recommended that cleaning time be maintained at a minimum and should not re- quire more than 3 minutes. Discoloration removal may also utilize vapor or abrasion blasting, electropolishing or abrasive tumbling .. WORKABILITY: Hot Working: Carpenter Custom 630 (17Cr-4Ni) can be readily forged, hot headed and upset. Material which is hot worked must be solution treated prior to hardening if the material is to respond properly to hardening. Forging: Heat uniformly to 2150/2200•F (1177/1204•C) and hold one hour at temperature before forging. Do not forge below 1sso• F (1 01 o•c). To obtain optimum grain size and mechanical properties, forgings should be cooled in air to so•F (32•C) before further processing. Forgings must be solution treated prior to ha_rdening. r Cold Working: Custom 630 (17Cr-4Ni) can be fabricated by cold working to an extent which is limited by the high initial yield strength. Machinability: Custom 630 (17Cr-4Ni) is readily machined in both the solution treated and various age hardened conditions. In the solution treated condition, it machines similar to Stainless Types 302 and 304. The machinability will improve as the hardening temperature is increased. Condition H 1150-M pro- vides optimum machinability which will be much like free- machining Type 303. Having procured Condition H 1150-M for best machinability, higher mechanical properties can only be developed by addi· tiona I heat treatment after machining. Properties equal to those of Condition H 1150 are produced by heating to soo• F (482°C) for one hour and air cooling . Properties superior to those of Condition H 1150 can only be obtained by solution treating and heat treating at standard hardening temperatures . IC -= II: IC £ E E IC E IC IC E E IC E IC It E E ·E II: E It E 1: ... .;__,.,._ . ___ ...... ·.--.......·---~ ......... ~----... --""'---····~ ... -··~--.... ·--··-···· :~ . ·l All'll'fmX I TMII.w.l ~r~ . ' .. J (~ TAIL!. J..6.0 .. :··-: MOOUU OF EU$TICITV E OF MATERW.S FOR CIVP TEMPERATURU . ... , -· .. J ......_ fll......, I -Y .... ;a.. • lOt> Ifill. fir T....., 'fl' flit ~ ....... .... ..... -100 7Q ---liCIO 61'10 7110 eoo •! ! \ t Ftmlld~ ··~ C&ttloort ...... wttn' Ci1LI'bon ~ 30.0 29-$. 29.4 %7.9 rr.7 21.4-27.0 26.4-%5.1' 24-.. ... :1 O.SO or lal, J~HI / ;J Covtlon .. witn Ci1LI'bon Cl:llltMt. .n..o. JQ.6 !0.4 ,!j!~· Z!:!l ~· 2U 27.4 26.1 t5.A '·' .-Yil ,, .; ·:.: 0" i•' ~-----'-31..1! 30.6 JQ.4 'Z!-' 29.0 2$.4 11.d %7.4 26.6 -· CllftiiM ICIIII tmutll 3Ct ,, ~ ~~ ~ dnmtt RRI:I H.4 21.1 ~ 27 .•• ) :rl.l. a.a 26.4 :u .. a 2!1A :Z4.' tsCr tlnuflb -4Ctl I ··~~ ~~t.~sU04,no, J0..4. 29.9 29.4 au rr.T :U.l 26.io 26.1. 2!.4 2A..S 24.1. Ul6t, lU. Mri ~ :! 4 str.ilht c:tvomll.m ..... )U. 3U :u 2'9.2: 2&.7 2U %1.1 U.tJ :eu 24.8 D...t. ~j . <UCr,.. %.7Cr, 27~ • "!. ~ . .. ...... , ' 4 -;·· ·~A ,. . . ,4 .. 'l .... .., Hanl'lr'fiM ....... ,t .. i HioJII Miclcd ~ · ... <1 / , .. ., ~~ !n ··n N~} .. , •' ·'l ·.;.j). ltr-f"....C.. . U.T JQ.9-~ JO.O ••• ~ 2&.6 :U..9' :;: N~ ~~ atcr-a... %1lf %1'-' %1',1 at.t a..J u:.a ·~ '1 Alllmlnllllr Aikin ac-. w1 ':~ ~ • 11.1 1,44 10.0 .... 9.1 .., ·;} l004 10.0 ••• 'l.l Ll_ "' ~5U4 1U' 10;0 10.2 ... 9.4 1.4 j !454, !:l4!6 10.% , .. t.o LO !OS!,'"· U.4 U.7 lO.l lOA 9.5 1.7 ' OC•l U-l. 1M 10.0 ••• •.a &.~ . i fiOU 10.0 '·' t.:t u 101.4, lO:t4 l:U u.o 144 lQ.l '·" 9.2 ·' ·~ l l Otlllr ~ Mftlrilll' ·• . I ~IWI <70/:JQ) 22.0 :.1 CllfiPI'I' u.o 14.1 t6.S 16.0 1!.6 l!l.4 U.l 1.4.t 14~ u.7 j u~ Tltllnlwll 1U UA u.a U.2. u.s lU l.l.l ~ ·NO.T~· ..... •' ,.·. ···: . '' "' ..... ~ ... -1 (U n-.,...tJC~cal modul1111 ~ I'IGt ............. 011' S~~Kifllld. I .• I J ~ ; -.r, I '·i ...., l\., ..... .:.- CALCULATION SHEET STONE & WEBSTER ENGINEERING CORPORATION ,.1.0./W.O./CALCULATION NO. I REVIll ON I PAlE •5010.61 PREPARER/DATE ~ 2/Sf'iel REVIEWER /CHECKER /DATE I INDEPENDENT REVIEWER/DATE SUB.IECT I TITLE . I) V i-I.JIIN6--:::: 7S.881~"-( I/S.38)1T" ::::-Z7 .so3 1,..;JJ L)T :: 4Jo o/~ (Z1S03) ~ 78oo._ l: t &u ... .~.~.;~ v :;. !l 7T a.b c.. 3 ) Yz, v ~ !:L rr ( ss.tzs)3 I ~ Yz. J -:. .:L rr ( :s4)3 (, . D ~~ -:::-. Zlo# ~~ 172~ WI ~ 4;o(i,o~~J ::; fcc~tx:i*·· ;7ze I QA CATEGORY I CODE CLASS i 7P~ ·""" "'B-/+:: Jl)" ~ "' Q ~ ~ ~' ~: .,. "& ,, ~ 1 ! .... -c ~ t G-u 11' xil 0{~-'-Ht::trc LJ 1 ft.,IJ.Jt.. e (' )