HomeMy WebLinkAboutKwigillingok PCE Economic Analysis Summary Sheet 1990PCE ECONOMIC ANALYSIS SUMMARY SHEET
Village: Kwigillingok
Analysis Date: 1/16/90 iH1¢ 70
Summary:
RSA estimates NO fuel efficiency improvement. FY89 line
losses are approximately 29%, and the loads are imbalanced (65A, 80A, 100A)
Recent information indicates that approximately one-half
of the 29% line losses was a result of improper metering
at the school. This was corrected 4/89 and losses are
currently 15.4% in FY90.
The fuel efficiency in FY90 is 8.1 Kwh/gal.
Existing generation equipment consists of 2-Deutz gen-sets
(1-150 Kw and 1-100 Kw) and a 125 Kw John Deere gen-set.
The 150 Kw Deutz was new 10/89. The 125 Kw JD is STANDBY
ONLY.
The measured connected load 6/20/89 was 65 Kw. The
estimated peak (est’d by Utility Mgr. 1/10/90) intermittent
load is 145 kw.
Automatic paralleling switchgear is available, but not used.
There is a possibility of repowering the 125 Kw JD to 75 OR
90 KW for use in the summer and as backup in the winter to
be used in parallel with the 100 Kw Deutz if needed.
NO ESTIMATE OF COST OR SAVINGS HAS BEEN CALCULATED.
fb Zor Avr