HomeMy WebLinkAboutCentral PCE Economic Analysis Summary Sheet 1990PCE ECONOMIC ANALYSIS SUMMARY SHEET Village: Central Analysis Date: 1/12/90 a RSA estimates NO fuel efficiency improvement. Current fuel efficiency is 9.95 Kwh/gal, from FY89 PCE report. Existing generation equipment consists of a 200 Kw and 100 Kw CAT gen-set. The measured connected load 10/26/88 was 44.6 Kw. The estimated peak connected load was not calculated. NOTE: Minimal electrical consumption from eligible community facilities. la Eton ROMY SCS 263,657 ALASKA POWER AUTHORITY R38 POWER COST EQUALIZATION FAPCER13 MONTHLY PCE STATISTICS REPORT FAPCEFOS “7 UTILITY SUMMARY # OF #8 OF # OF CURRENT TOTAL MONTHLY (a) (b) 3) (a+ bec) FISCAL FISCAL COMMUNITY DATE POPUL RESID. COMMER. COMMUN. FUEL FUEL TOTAL OPERATING Kw MONTHLY TOTAL KWH TOTAL KWH TOTAL KWH TOTAL KWH PERIOD YEAR POPULATION CERTIFIED CUST CUST —FACIL. PRICE CONSUMED FUEL COST EXPENSE — GENERAT KWH SOLD ELIG. RESID. ELIG. COMMR. ELIG. FACIL. ELIGIBLE 3 89 rey 01/01/01 23 3 2 0.7500 2328 1746.57 4231.87 9711 9711 6520 2250 i 9227 5 89 ts 01/01/01 24 3 3 0.7500 2217 1663.41 2569.83 17602 17602 7765 2250 464 10479 6 89 ps 47 26 2 3 0.7500 2453 1839.89 2012.96 17756 17756 8186 2250 469 10905 7 89 7s 01/01/01 25 3 3 0.7500 2363 1772.49 0.00 18755 18755 6158 2250 731 11139 8 89 toy 01/01/01 26 2 3 0.7500 1942 1456.81 2852.45 9482 9482 7095 1500 440 9035 9 89 tS 01/01/01 25 3 3 0.7500 2445 2203.46 2108.17 10793 10793 6677 2250 6% 9561 10 89 7 01/01/01 23 3 3 0.7500 2384 2148.69 4380.33 10148 10148 6221 2250 835 9306 WwW 8 ss 01/01/01 25 3 4 0.7500 2573 2318.00 11382.99 21798 21798 6626 1685 346 8657 12 3 7s 01/01/01 25 3 4 0.7500 2654 2391.89 3576.06 124132 26132 6407 1786 299 8492 jubsubtotal * 26640 21502.53 43735.39 257898 157898 77078 19971 5670 102719 Subtotal ** 26640 21502.53 43735.39 257898 157898 77078 19971 5670 102719 FAR NORTH UTILITIES - FY89 seece CENTRAL cee 1 8 42 07/01/85 26 23 1 0.6830 2434 1913.12 2607.12 15590 REBD UM —PFRA 4442 11030 54 15986 2 3 42 07/01/85 26 26 1 0.6830 2670 1823.61 5304.97 18260 bo 17390 wEO 4568 12325 497 17390 3 89 42 07/01/85 16 23 1 0.6830 2580 1762.14 8093.21 18672 $5725 17783 5730 11892 261 17883 4 89 42 07/01/85 2 26 1 0.8040 2748 1871.42 7319.07 19226 3ty¥g 18310 6336 11799 75 18310 5 8 42 07/01/85 27 27 1 0.8752 2710 2005.40 15236.13 19838 3222518893 6422 12715 253 19390 6 89 42 07/01/85 16 235 1 0.9500 3270 2629.08 41033.09 19673 52852 18736 6662 11808 265 18735 7 89 42 07/01/85 28 27 1 0.9500 3270 2629.80 5800.46 21321 Sa. % 20306 7173 12478 186 19837 8 89 42 07/01/85 16 23 1 0.7300 3140 0.00 13567.72 17626 fe 21) 16787 5817 10647 273 16737 9 89 42 07/01/85 15 26 1 0.7300 3240 0.00 34439.19 18916 29% 7 18015 5807 11920 288 18015 10 89 39 01/01/86 2 27 1 0.7620 3180 0.00 8350.44 17982 99753 17126 6087 10842 197 17126 Ww 89 39 01/01/86 28 1S 1 0.7620 3200 0.00 13219.19 20224 Joos y 19261 5272 12001 M7 17620 12 89 399 01/01/86 2 27 1 0.7620 3100 0.00 17664 .70 197799295992 16951 6367 9999 585 16951 jubsubtotal * i 35542 14634.57 172635.29 225927 —226556-——> 70683 139456 3841 213980 Subtotal ** , 35542 1463457 172635.29 225927 226554 70683 139456 3841 213980 G & K, INC. - FY89 95 3639 > 9SSYZ = 9,95 be 50/5 la, . COLD BAY 1 89 250 07/01/86 Mu 4l o 1.0810 19793 21396.23 57278.00 265440 244644 20478 26708 0 47186 2 89 250 07/01/86 % 4i 0 1.0810 21357 23086.92 57278.00 291240 268801 20582 26184 0 46766 3 89 250 07/01/86 x 41 0 1.0810 22189 2398631 57278.00 277320 258999 21392 25952 0 4T3A 4 8 250 07/01/86 35 41 oO 1.0810 20626 22296.71 57278.00 300000 273703 21829 25721 0 47550 5 89 250 07/01/86 35 41 oO 1.0810 22190 23987 .39 57278.00 309840 288869 22708 26574 0 49282 6 89 250 07/01/86 35 4 0 1.0810 23820 25749.42 57278.00 336360 309777 22898 26055 0 48953 7 89 250 07/01/86 33 4) o 1.0810 24534 26521.25 $7278.00 348840 316938 23520 25963 0 49483 8 89 250 07/01/86 3 4) o 1.0810 20822 22508.58 57278.00 292080 264660 22455 25740 0 48195 PUC Me. — sy eae >neer no. _——— (~* pares ; RECEIVED Tenth Revision sneer Ne: 29 MAY 4 ” 1989 [ State of Alaska ~*~ FAR NORTH UTILITIES > Céppeac Public Utilities Commiesten, POWER COST EQUALIZATION The amount of Power Cost Equalization (PCE) for any individual customer, except local community facilities, is limited to the customer's actual consumption up to 750 KWH per month. The Power Cost Equalization to local community facilities is limited to the facilities actual consumption; in addition, such equalization is limited in the aggegate for each community served to 70 KWH per month for each resident of the community. The amount of Power Cost Equalization to te credited to bills rendered on or after the effective date set forth below, is as follows (subject to available State of Alaska appropriations): Schedule PCE Amount Residential and commercial 27-68°/KWH Standby Service Applicable Amount from Schedule 1 Toriff Advice No. 12 Effective: Ma 26 1989 Issued byt FAR NORTH UTILTIES Kerbs, Managing Partner By: Tither ruc m4) Ninf __ Revision sreet no, 2 Cancelling Eighth Revision 30.3 ‘Sheet No. cc FAR NORTH UTILITIES RECEIVED MAY 1 7 1989 State of Alaska Public Utilities Commission - _ E. Determination of Power Cost Adjustment (1) Estimated cost for quarter beginning May 1, 1989 : Estimated Effective Rate Total Source Quantities On (Date) (A * .B) (A) (B) (Cc) a) Fuel Oil 7126 GAL. .70 $ 4988.20 816.07 (2) Balance of Power Cost Balance Account (date) $ (immediace prior quarter end) (negative if credit balance) (3) Total (1) and (2) above $ 5804.27 (4) Estimated Retail Sales 75005 /KWH (5) Average Cost of Power (3 divided by 4) -0787 $/KWH (6) Base Cost of Power -1387 $/KWH : : (.06) - (7) Power Cost Adjustment (5 minus 6) $/KWH — Toritt Advice Ne. —L2_ Ettectives May 1, 1989 FAR NORTH UTILITIES Issued by! Managing Partner Titte: “ ‘apuc me 241 Ten@P Revision Sheet Ne. —%& —_ Cancelling RECEIVED Nonth Revision ee 29 SAN 4 9 4099 7 State ot enn, ! 7 Witla sion : FAR NORTH UTILITIES ; Public Utilities Comm's POWER COST EQUALIZATION The amount of Power Cost Equalization (PCE) for any individual customer, except local community facilities, is limited to the customer's actual consumption up to 750 KWH per month. The Power Cost Equalization to local community facilities is limited to the facilities actual consumption; in addition, such equalization is limited in the aggegate for each community served to 70 KWH per month for each resident of the community. The amount of Power Cost Equalization to be credited to bills rendered on or after the effective date set forth below, is as follows (subject to available State of Alaska appropriations): Schedule PCE Amount Residential and commercial 24.71c/KWH Standby Service Applicable Amount from Schedule 1 ll February 17, 1989 Teritf Advice No, ——— Effective: FAR NORTH UTILTIES V J. : Wal eal. Wi Managing Partner er “apUc woo at a Revision shasr Ne: @ Concelling RECEIVED Seventh Revision sneet No, 22-3 JAN 19 1989 State of Alaska ° Public Utillties Commission FAR NORTH UTILITIES E. Determination of Power Cost Adjustment (1) Estimated cost for quarter beginning January 1, 1989 : Estimated Effective Rate Total Source Quantities On (Date) (A * B) (A) (B) (Cc) a) Fuel Oil 9180 GAL. .777 $_7132.86 (2) Balance of Power Cost Balance Account (date) $(2542.65) (immediate prior quarter end) (negative if credit balance) (3) Total (1) and (2) above § 4590.21 (4) Estimated Retail Sales 96700 / KWH (5) Average Cost of Power (3 divided by 4) -0474 $/KWH \ | (6) Base Cost of Power - 1387 S$ /KWH | (7) Power Cost Adjustment (5 minus 6) (.0913) $/KWH | | \ Toritt Advice Mo. 1] Etrectve: January |, 1989 J FAR NORTH UTIL ITTES we (ae, so bi, Managing Partner Tither Vie a po eenaies arent ne, Ob RECEIVED vi OCT 3 i 1988 Eighth Revision 29 ‘State of Alaska eee Public Utilities Commisstori FAR NORTH UTILITIES POWER COST EQUALIZATION The amount of Power Cost Equalization (PCE) for any individual customer, except local community facilities, is limited to the customer's actual consumption up to 750 KWH per month. The Power Cost Equalization to local community facilities is limited to the facilities actual consumption; in addition, such equalization is limited in the aggegate for each community served to 70 KWH per month for each resident of the community. The amount of Power Cost Equalization to be credited to bills rendered on or after the effective date set forth below, is as follows (subject to available State of Alaska appropriations): Schedule PCE Amount Residential and commercial 28.50/KWH Standby Service Applicable Amount from Schedule 1 f ~~ ( Toritt Advice No. LO Ettective. _November 10, 1988 ‘ bd FAR NORTH UTILTLIES issued by! ~ ky VAM ii ne Managing Partner 341 Sever’ |, Revision Shest was 20%: Cancelling RECEIVED Sixth Revision sneer No, 20:3 OCT 31 1988 State of Alaska Public Utilities Commission FAR NORTH UTILITIES E. Determination of Power Cost Adjustment (1) Estimated cost for quarter beginning October 1, 1988 Estimated Effective Rate Total Source Quantities On (Date) (A * B) (A) (B) (C) a) Fuel Oil 7630 GAL. - 683 $5211.29 | (2) Balance of Power Cost Balance Account (date) $1013.25 (immediate prior quarter end) | (negative if credit balance) 3 (3) Total (1) and (2) above g6224.54 (4) Estimated Retail Sales 71300 /KWH | | (5) Average Cost of Power (3 divided by 4) +0873 $/KWH | | (6) Base Cost of Power - 1387 $/KWH | ; | | | | (7) Power Cost Adjustment (5 minus 6) (.0514) S/KWH | | | | | Toritt Advice No. —L0_ Efttective. October 1, 1988 | Ly Issued bys FAR NORTH UTILITIES / ) Pe : ke a4 Ve ae Managing Partner J a Tithe: Ge BY: Revision Sheet Me. Bight! cancelling RECEIVED seventh _ Revision sneer we, 29 JUL 25 1988 State of Alaska Public Utilities Commissior yak NORTH UTILITIES POWER COST EQUALIZATION The amount of Power Cost Equalization (PCE) for any individual customer, except local community facilities, is limited to the customer's actual consumption up to 750 KWH per month. The Power Cost Equalization to local community facilities is limited to the facilities actual consumption; in addition, such equalization is limited in the aggegate for each community served to 70 KWH per month for each resident of the community. The amount of Power Cost Equalization to be credited to bills rendered on or after the effective date set forth below, is as follows (subject to available State of Alaska appropriations): Schedule PCE Amount Residential and commercial 27 . 46 /KWH Standby Service Applicable Amount from Schedule 1 Toritt Advice We, 9 Effective: oe August 26, 1988 Issued bys FAR NORTH UTILTIES. Managing Partner By: Tittes FAR NORTH UTILITIES sixth (ty Revision Sheet We. Cancelling RECEIVED Fifth __Revision __ sheet ne. JUL 25 1988 State of Alaska Public Utilities Commission Determination of Power Cost Adjustment 1 (1) Estimated cost for quarter beginning July 1, 1988 : Estimated | Effective Rate Total Source Quantities On (Date) (A * B) (A) (B) (Cc) a) Fuel Oil 7150 GAL. - 600 $ 4290.00 (2) Balance of Power Cost Balance Account (date) $1030.59 (immediate prior quarter end) (negative if credit balance) (3) Total (1) and (2) above ‘ g 5320.59 (4) Estimated Retail Sales 69650 /KWH (5) Average Cost of Power (3 divided by 4) -0764 $ /KWH (6) Base Cost of Power 1387 $ /KWH (7) Power Cost Adjustment (5 minus 6) , (.0623) $/KWH | | Toritt Advice Ne, —2 Eftectiver July 1, 1988 FAR NORTH UTILITIES \ssueg-ty! / 4 5 ~ Managing Partner By: Tite —<—$—$<—$— — —— iweiiuu nev evan 2 NeWT Irv. Cancelling 1 E D Eleventh Revision 29 REC E v Sheet Ne, > AUG 45 1989 - State of Alaska FAR NORTH UTILITIES — CEwreac Public Utilities Commission - 4 POWER COST EQUALIZATION The amount of Power Cost Equalization (PCE) for any individual customer, except local community facilities, is limited to the customer's actual consumption up to 750 KWH per month. The Power Cost Equalization to local community facilities is limited to the facilities actual consumption; in addition, such equalization is limited in the aggegate for each community served to 70 KWH per month for each resident of the community. The amount of Power Cost Equalization to be credited to bills rendered on or after the effective date set forth below, is as follows (subject to available State of Alaska appropriations): Schedule PCE Amount Residential and commercial 29 .82¢/KWH I Standby Service Applicable Amount from Schedule 1 13 September 15, 1989 Tariff Advice Mo, ———— Effective: FAR NORTH UTILTIES Issued Dy! 4 YY. - Managing Partner ers Titter Sneet ro, Cancelling ; ; RECEIVED Ninth Revision shearne. 30.3 scenes ocean AUG 4.5 1989 State of Alaska FAR NORTH UTILITIES Public Utilities Commission ] E. Determination of Power Cost Adjustment (1) Estimated cost for quarter beginning August 1, 1989 Estimated Effective Rate Total Source Quantities On (Date) (A * B) (A) (B) (Cc) a) Fuel Oil 9500 GAL. -70 $ 6650.00 1 (2) Balance of Power Cost Balance Account (date) $ 2720.23 (immediate prior quarter end) (negative if credit balance) (3) Total (1) and (2) above $9370.23 (4) Estimated Retail Sales 92630 KWH (5) Average Cost of Power (3 divided by 4) - 1012 $/KWH (6) Base Cost of Power +1387 $/KWH (7) Power Cost Adjustment (5 minus 6) (.0375) $/KWH I Toritt Advice we, 13 Ettectiver August 1, 1989 Issued by! FAR NORTH UTILITIES » Las Krrberbe ca: Managing Partner Revised 8/86 page 4) ~~ _TA_13-341 We wil eI : Updated ' Commission : Utility ' Commission ' Derarmination ! Reauest ' Determination S Cees /1 Nf (seme /IH) | rani WH) mene ne 4 HUM NANATNATNN TAT HN NTT a ; He Non-Fuel Fower : : Costs ‘Line Cc, : ' : RPP sl elle aeella yh Hl li 2on7 ' «2977 : senate aI A NWI WIA i AN : G, Fuel Power Costs ! : ! | (Line G, Bopendis: 7: .0787 ' 1012 ; ' ; i Cc. Total Fower Costs Costs D. Total Fower Costs less Q.s E. 95% of D Fe. Statutory blassa mum Eligiole Fower Cost Equalization H. Customer/class FACe (fram column 7, Page = Apoendis 7 of column Db, page 3A Appenei:: 7) ALL KWH | ABVencix 7 ———— oo ( Paae 2 TOUMLIZATION SCmeuUrATICON WITH CUCL COST nate ROSUSTI“ED