Subject: Southern Intertie Monthly Report for July 1999
W.0.#E9590081
Please find enclosed 1 (one) copy of the Southern Intertie Report for the Month of July
1999. If there are any questions, please contact Dora Gropp, (907) 762-4626.
Enclosures: 1 (one) copy of Southern Intertie Monthly Report
c Lee Thibert
Michael Massin
Dora Gropp
Jim Borden
Mike Cunningham
Don Edwards
W.0.#E9590081, Sec., 2.1.3
RF
5601 Minnesota Drive ¢ P.O. Box 196300 * Anchorage, Alaska 99519-6300
Phone 907-563-7494 # FAX 907-562-0027
CHUGACH ELECTRIC ASSOCIATION, INC.
Anchorage, Alaska
SOUTHERN INTERTIE. |
Phase IB — Environmental Analysis —
MONTHLY REPORT
for
jaly 1999
5601 Minnesota Drive
P.O. Box 196300
Anchorage, Alaska 99519-6300
Il.
Il.
IV.
VI.
TABLE OF CONTENTS
SUMMARY
FINANCIAL
1. Bank Statement of June 1999
2. Chugach Statement for June 1999
3. Total Project Expenditures, Inception Through June
1999
SCHEDULE
ITEMS FOR APPROVAL
None
ITEMS FOR DISCUSSION
None
ITEMS FOR INFORMATION
I. POWER Engineers’ Monthly Report Phase IB -
Environmental Analysis, July 19, 1999
SUMMARY
The EVAL has been completed and submitted to RUS and USFWS, the agencies
involved in preparation of the EIS.
The application (“ANILCA” application) for a ROW permit through the Kenai National
Wildlife Refuge (KNWR) is being finalized and will be submitted to the USFWS this
month.
A new schedule and budget for the EIS development will be established after the USFWS
has accepted the application for a project permit and after RUS has coordinated the
activities through their consultant Mangi Environmental.
Expenditures for Phase IB of the project stand as follows :
DESCRIPTION POWER __|USFS/USFWS/ |CHUGACH| TOTAL
ENGINEERS RUS
ORIG. BUDGET $3,043,423 $100,000 $400,000} $3,543,423
ALLOCATED $0 $0 $0 $0
CONTINGENCY |
TOTAL $3,043,423 $100,000 $400,000} $3,543,423
AMENDMENTS $867,769 $25,593] — -$200,000 $693,362
TOTAL $3,911,192] $125,593 $200,000} $4,236,785
COMMITMENT
SPENT TO DATE $3,883,177 $125,593 $185,612} $4,194,382
[% OF TOTAL 99% 100% 93% 99%
Total Project expenditures as of 07/19/99 are $5,199,622 which includes a payment to
RUS for the EIS preparation in the amount of $97,670.
Il. FINANCIAL
ip
De
Bs
Bank Statement of June 1999
Chugach Statement for June 1999
Total Project Expenditures, Inception Through June 1999
Southern Intertie Grant Fund
Bank Account Activity Summary
June, 1999
May Ending Balance Forward $334,564.18
Total Deposits ($176,243.94)
Total Withdrawals $0.00
Interest Earned $1,400.01
Balance June 30, 1999 $159,720.25
RECEIVER
JUL 21 1999
TRANSMISSION & SPECIAL PROJECT
OTR MME ECE mesilate
of Anchorage
Ayo ome
MAIN BRANCH
PO BOX 100720
ANCHORAGE AK 99510-0720
99519-6300
000 O01 OO
DATE: 06/30/99
CHUGACH ELECTRIC ASSOCIATION I
PO BOX 196300
ANCHORAGE AK
PAGE:
ACCOUNT:
1
41100033
30 oo
DESCRIPTION
BALANCE LAST STATEMENT
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
INTEREST
TRANSFER TO BUSINESS ACCOUNT 1106061
INTEREST
INTEREST
BALANCE THIS STATEMENT
176,243.94
132.33
44.05
44.06
44.06
44.07
as 59)
21.61
21562
ee ee
CONTINUED * * *
05/28/99
06/01/99
06/02/99
06/03/99
06/04/99
06/07/39
06/08/99
06/09/99
06/10/99
06/11/99
06/14/99
06/15/99
06/16/99
06/17/99
06/18/39
06/21/99
06/22/99
06/23/99
06/24/99
06/25/39
06/28/99
06/29/99
06/29/99
06/30/99
06/30/99
BALANCE
334,564.18
334,736.65
334,780.70
334,824.75
334,868.81
334,999.95
335,042.98
335,086.01
335,129.05
335,172.09
335,302.29
335,346.41
335,390.54
335,434.67
335,478.81
335,611.14
335,655.19
335,699.25
335,743.31
335,787.38
335,920.97
159,677.03
159,698.64
159,720.25
159,720.25
a cO0nC HOUSING LENDER
000 O01 00 PAGE:
DATE: 06/30/99 ACCOUNT: 4110003
First National Bank
of Anchorage
enema
CHUGACH ELECTRIC ASSOCIATION I
TOTAL CREDITS (22) 1,400.01 i TOTAL DEBITS (2) 176,243.94
INTEREST THIS STATEMENT 1,400.01
INTEREST PAID 1999 Te Tense’
- END OF STATEMENT -
CHUGACH ELECTRIC ASSOCIATION, INC.
Anchorage, Alaska R E c E I V E D
07/21/99
JUL 2 1 1999
TO: Dora Gropp - Manager, Transmission & Special Projects speNSM PROS
FROM: Kurt Parish, Plant Accountant
SUBJECT: 9590081 - Souther Intertie Route Selection Study
You had previously requested establishment of this work order to study route selection for -
the Southern Intertie for the Intertie Participants Group. The Association will be reimbursed for charges to this work order. The following charges occurred during June 1999.
Direct Labor 1,045.17
Indirect Labor 472.96
Power Engineers - Invoice 62409 128,199.59
Sub-Total $129,717.72
General, Administrative & Construction Overhead (0.5%) 648.59
Total Charges $130,366.31
Please review the attached backup and indicate your concurrence below if you are in
agreement that these charges are correct for this work order and time period.
As per your request, | will keep the original in the work order file.
Concur: By. eH x. z ey ?9
Signature Date
WOfiles/E9590081
Attachments
7/21199
Project Expenditures
CHUGACH ELECTRIC ASSOCIATION, INC.
Southern Intertie Transactions
Inception Through June 30, 1999
Year to Date Month
Inception Through Ended Inception
Through 12/31/98 6/1/99 6/30/1999 Through 6/30/1999
Direct Labor $139,963.89 $6,897.90 $1,045.17 $147,906.96
Indirect Labor 52,278.09 3,171.94 472.96 55,922.99
Power Engineers 4,180,875.68 327,149.01 128,199.59 4,636,224.28
Miscellaneous 268,608.32 27,316.00 0.00 295,924.32
Total $3,995,497.88 $364,534.85 $129,717.72 $5,135,978.55
Grant Fund Expenditures
Year to Date Month
Inception Through Ended Inception
Through 12/31/98 6/1/99 6/30/1999 Through 6/30/1999
Direct Charges that Chugach has
been Reimbursed for $4,570,726.42 $260,167.30 $175,367.11 $5, 006,260.83
Plus General, Administrative
& Construction Overhead 22,853.64 1,300.83 $876.83 25,031.30
Total Amounts Paid to Chugach $3,861 ,529.83 $261,468.13 $176,243.94 $5,031,292.13
JUL 21 1999
TRANSMISSION & SPECIAL PROJECT
cc: Dora Gropp 7/21/99 Alayne Switzer
Chugach Electric Association, Inc.
Southern Intertie Activity Summary
June, 1999
Beginning Grant Chugach Ending
Bank Funds Interest Invoices Bank
Year Balance Received Earned Paid Balance
1996 0.00 2,771,277.00 40,361.59 (1,440,252.89) 1,371,385.70
1997 1,371,385.70 1,346,934.00 67,734.96 (2,421,276.94) 364,777.72
1998 364,777.72 525,214.00 19,424.02 (732,050.23) 177,365.51
1999* 177,365.51 388,194.64 7,712.24 (413,552.14) 159,720.25
Total 4,643,425.00 127,520.57 (4,593,580.06)
* Through June, 1999 bank statement (does not include Chugach invoices
for charges incurred in June 1999)
REcEIVET)
JUL 2 1 1999
NSMISSION & SPECIAL PROJECT
Ill. SCHEDULE
CHUGACH ELECTRIC ASSOCIATION ANCHORAGE - KENAI INTERTIE Wed 7/21/99 PHASE IB
1995 1996 1997 1998 1999 2000
ID | Task Name % Comp. Act. Cost Qi | Q2 | Q3 1 [ENVIRONMENTAL & ENGINEERING 86%| $5,027,581.93
2 PROJECT MANAGEMENT — “42% $187,427.52
3 | ROUTE SELECTION STUDIES — -100%| $871,650.00
4 | EVAL & PREL.ENGINEERING 95%| $3,887,634.41
5 ~~ SCOPING — 100%| $375,997.34
6 INVENTORY - 100% $680,396.25
7 ~ IMPACT/MITIGATION 100%| $607,560.00
8 " ALTERN.SELECTION =| ~—=—«100%| +~—« $335,392.00
9] EVAL (DRAFTEIS) 99%| $1,347,809.76
10 | ANILCA (FINAL EIS) 57% $46,498.32
1 ~ STUDIES 100% $101,476.81
121 ENG.FIELD WORK - 100%! ——- $202,645.44
13 | —-~ PREL. ENGINEERING ~ 100% $189,858.49
14| AGENCIES ~-99%| $80,870.00
15| ~~—~*USFS a 100% $34,954.00
16 USFWS 100%| $45,916.00
17 RUS - 96%; $0.00
Task ea Rolled Up Task aL) Project Summary a
Project: ANCHORAGE - KENAI INTE Progress Rolled Up Milestone Oy Split
Date: Wed 7/21/99 Milestone ® Rolled Up Progress 99 = Rolled Up Split
Summary pay External Tasks eae] ' PH_IB.MPP Page 1
Iv. ITEMS FOR APPROVAL
None.
V. ITEMS FOR DISCUSSION
None.
VI. ITEMS FOR INFORMATION
Is POWER Engineers’ Monthly Report Phase IB — Environmental Analysis, July 19,
1999.
ROMER ENGINEERS Facsimile Cover Sheet
Project Number 120376-05-55-00-32
Original To Follow Via U.S. Mail: Yes M@ NoO
Total Number Of Pages, Including This Page:
July 19, 1999, 03:51 PM
To: Dora Gropp - Chugach Electric Fax No.: (907) 762-4617 .
Association
Subject: Monthly Status Report for the Southern Intertie Project
Dora,
This fax contains the Southern Intertie Project Monthly Status Report for July, 1999. We will
send the report out on Monday for delivery on Tuesday morning (7/20).
Please contact Mike Walbert or me if this does not give you all the information you need.
Randy Pollock, P.E.
Project Manager
RECEIVED)
JUL 2 0 1999
cc: Mike Walbert (POWER)
Jenny McGraw (POWER) TRANSMISSION &
SPECIAL PROJECT
HLY 23-321b
PLEASE CALL (208) 788-0357 IF FACSIMILE IS INCOMPLETE OR ILLEGIBLE
THIS MESSAGE IS INTENDED ONLY FOR THE USE OF THE INDIVIDUAL OR ENTITY TO WHICH IT IS ADDRESSED, AND MAY CONTAIN INFORMATION THAT IS
PRIVILEGED, CONFIDENTIAL AND EXEMPT FROM DISCLOSURE UNDER APPLICABLE LAW. IF THE READER OF THIS MESSAGE IS NOT THE INTENDED
RECIPIENT, OR THE EMPLOYEE OR AGENT RESPONSIBLE FOR DELIVERING THE MESSAGE TO THE INTENDED RECIPIENT, YOU ARE HEREBY NOTIFIED
THAT ANY DISSEMINATION, DISTRIBUTION OR COPYING OF THIS COMMUNICATION IS STRICTLY PROHIBITED. IF YOU HAVE RECEIVED THIS
COMMUNICATION IN ERROR, PLEASE NOTIFY US IMMEDIATELY BY TELEPHONE AND RETURN THE ORIGINAL MESSAGE TO US AT THE BELOW ADDRESS
VIAU.S. MAIL SERVICE. THANK YOU.
POWER Engineers, Incorporated
3940 Glenbrook Drive * P.O. Box 1066 Phone: (208) 788-3456
Hailey, Idaho 83333 Fax: (208) 788-2082
ROWER ENGINEERS July 19, 1999
Ms. Dora Gropp
Chugach Electric Association
5601 Minnesota Drive, Building A
Anchorage, AK 99518
Subject: POWER Project #120376 EIS & Preliminary Engineering
Chugach Contract No. 820, Monthly Status Report No. 6
For Period June 13 — July 10, 1999
Dear Dora:
This report summarizes the activities completed during June 1999 for Tasks 5a — Se and 6.
During this period, Dames and Moore completed the Final EVAL. The ANILCA
Application is scheduled for completion in July 1999.
This report includes the following attachments:
1) Overall Financial Project Summary
2) Detailed Budget and Percent Complete Summary for Tasks 5a — Se and Task 6
3) Activity Summaries for Tasks 5 and 6
4) Dames and Moore Monthly Report, including:
a) July 9, 1999 - Letter to Randy Pollock, PEI, from Tim Tetherow, D&M, regarding
the Project Status, including a summary of activities table, and D&M percent
complete and cash flow projections table.
b) June 23, 1999 — Letter to Tim Tetherow, D&M, from Sharon Janis, USFWS,
regarding the Biological Resources portion of Chapter 4 and the Map Set for the
Southern Intertie Project EVAL.
c) June 16, 1999 — Record of Conversation between Tim Tetherow, D&M, and Larry
Wolfe, RUS.
d) June 15, 1999 — Record of Conversation between Tom Tetherow, D&M, and Brian
Anderson, USFWS.
Invoice Period Overview:
Dames & Moore -
e Completed Final EVAL.
¢ Completed Draft ANILCA Application.
HLY 23-321
POWER Engineers, Incorporated A LS 3940 Glenbrook Dr. + P.O. Box 1066 Phone (208) 788-3456 Hailey, Idaho 83333 Fax (208) 788-2082
Chugach Electric Association
July 19, 1999
Page 2
Power Engineers —
e Worked with Dames and Moore to finalize engineering/environmental issues for completion
of the Final EVAL.
e¢ Monitored and managed Dames and Moore’s completion of the Final EVAL and the Draft
ANILCA Application.
Work Planned for the Next Invoice Period:
Dames & Moore —
e Finalize the ANILCA Application.
Power Engineers —
e Continue to monitor and manage Dames and Moore’s completion of the final ANILCA
Application.
Schedule:
The Final ANILCA Application is scheduled to be completed in July.
Budget:
Total Budget $3,911,194
Actual $ Invoiced (to date) $3,883,177
Actual Remaining Project Budget $28,017
Dora, should you have any questions about this report or any of the backup, please do not
hesitate to contact Mike Walbert or me.
Sincerely,
POWER Engineers, Inc. 2 lk
Randy Pollock, P.E.
Project Manager
RP/lk
Enclosures
cc: PROJECT TEAM
HLY 23-321
DOWER
SOUTHERN INTERTIE ROUTE SELECTION STUDY - PHASE 1 - 120376
PROJECT FINANCIAL SUMMARY
JULY, 1999 INVOICE
Project
Task 1 Task 2 Task 3 Task 4 Task 5 Task 6 Task 7 | Task 8 Task 9 Total
Base Not to Exceed $351,050 $660,706 $584,010 $303,475 $402,570 $247,616 $101,480 $202,655 $189,861 $3,043,423 Budget
CWG Contract $23,789 $18,885 $22,602 $32,866 $4,904 N/A N/A N/A N/A $103,046
Amendment No. 4
DF! Contract N/A N/A N/A N/A $45,000 N/A N/A N/A N/A $45,000 Amendment No. 5
DFI Contract N/A N/A N/A N/A $11,400 N/A N/A N/A $11,400 Amendment No. 6 | |
DFI Contract N/A N/A N/A N/A $3,502 N/A N/A N/A $3,502
Amendment No. 7 |
DFI Contract N/A $89,487 N/A N/A $89,487
Amendment No. 8
Task 5 &6 $194,150 | ($194,150) N/A $0
Reallocation *
Contract N/A $31,926 N/A N/A $31,926 Amendment No. 9
Contract N/A N/A N/A N/A $118,193 N/A N/A N/A $118,193 Amendment No. 11 | |
Contract 820, N/A N/A N/A N/A $465,215 N/A N/A N/A N/A $465,215 Amendment No. 1 alt Total Not to Exceed $374,839 $679,591 $606,612 $336,341 | $1,366,349 $53,466 $101,480 $202,655 $189,861 $3,911,194 Budget | |
Actual Budget $374,839 $679,583 $606,540 $336,315 | $1,300,200 $30,014 $101,476 $202,610 $189,852 $3,821,429 Expended Through
Previous Invoice | Current Invoice $0 $0 $0 $0 $45,509 $16,239 $0 $0 $0 $61,748
Amount _|
Actual Budget $374,839 $679,583 $606,540 $336,315 | $1,345,709 $46,253 $101,476 $202,610 $189,852 $3,883,177
Expended Through
Current Invoice |
Remaining $0 $8 $72 $26 $20,640 $7,213 $4 $45 $9 $28,017
* Task 5 budget amount reflects the addition of Contract No. 820, Amendment No. | funds.
HLY 23.321 '
JULY 1999 INVOICE
ACTIVITIES SUMMARY
TASK 5 - EVAL PREPARATION
DESCRIPTION ACTIVITIES DURING CURRENT PERIOD AND
PLANNED FOR NEXT 30 DAYS
EVAL Preparation ¢ Completed Final EVAL.
KEY ISSUES: No outstanding key issues.
SCHEDULE: The Final EVAL was completed.
BUDGET: Contract amendments Nos. 4, 5, 6, 7, 8, 9, 11 and the budget reallocation! for
Tasks 5 and 6 are included in the budget. Also included is Contract No. 820, Amendment No. 1
($402,570 + $4,904 + $45,000 + $11,400 + $3,502 + $89,487 + $194,150 + $31,926 + $118,193
+ $465,215 = $1,366,349).
$ Budgeted $ Expended $ Remaining
$1,366,349 $1,345,709 $20,640
SCOPE: No outstanding issues.
' Tasks 5 budget amount reflects the addition of Contract No. 820, Amendment No. 1 funds.
HLY 23-321a
JULY 1999 INVOICE
ACTIVITIES SUMMARY
TASK 6 - ANILCA APPLICATION
DESCRIPTION ACTIVITIES DURING CURRENT PERIOD AND
PLANNED FOR NEXT 30 DAYS
ANILCA Application e Completed draft ANILCA Application.
e Finalize ANILCA Application.
KEY ISSUES: Completion of the ANILCA application.
SCHEDULE: The ANILCA application is scheduled to be completed in July 1999.
BUDGET: _ The budget reallocation’ for Tasks 5 and 6 is included in the budget ($247,616 -
$194,150 = $53,466).
$ Budgeted $ Expended $ Remaining
$53,466 $46,253 $7,213
SCOPE: No outstanding issues.
* Tasks 5 and 6 budget amounts reallocated per April 24, 1998 letter from Robert Martin to Randy Pollock.
HLY 23-321a
7/19/99 SOUTHERN INTERTIE PROJECT THROUGH PERIOD ENDING:
03/18/99 Contract 820 Amendment No. 1
HLY 23-321a1
Page 1 of 2 PROJECT SUMMARY REPORT 07-10-99
2ND QUARTER 1999 3RD QUARTER 1999 TASK MONTH| MAR APR MAY JUN JuL_ | auG | sep |
5a_|COMMENT ORGANIZATION (Dames & Moore) | Actual % Work Completed 60% 100%| 100% 100%] __- 100%| i
| Planned % Complete $ (to date) 60% 100%; 100%, 100%| 100% | 100%| 100%
Actual % Expended $ (to date) 60% 100% | 100% | 100% 100% | |
___ Planned $ (this period) ~ $28,349 | $19,292 $0 | __ $0 $0 $0 | $0
Actual $ Expended (this period) $28,349 $19,292 | $0 $0 $0
Planned $ (to date) $28,349 $47,641 | $47,641 $47,641 $47,641 $47,641 $47,641
Actual $ Expended (to date) $28,349 $47,641 $47,641 | $47,641 $47,641 | - |
Contract No. 820, Amend. No. 1 $47,641 $47,641 | $47,641 | $47,641 $47,641 $47,641 | $47,641
Actual Remaining Task Budget $19,292 $0 $0 | $0 $0 |
5b |EVAL REVISIONS (Dames & Moore) | | | |
| ___ Actual % Work Completed 2096) _45%| 76% 100% 100% |
Planned % Complete $ (to date) 27% 51%) 77% 100% 100% 100% 100%
Actual % Expended $ (to date) 27% 45% | 76% 100% 100% | ___ Planned $ (this period) $48,540| $41,696 | $45,329! $41,105 | _ $0 $0 | $0
Actual $ Expended (this period) $48,540 $30,727 | $55,393 | $41,922 $0
Planned $ (to date) $48,540 $90,236 $135,565 | $176,670 | $176,670 | $176,670 | $176,670
Actual $ Expended (to date) $48,540 | $79,267 $134,661 $176,583 | $176,583 |
Contract No. 820, Amend. No. 1 | $176,670 | $176,670 | $176,670 | $176,670 | $176,670 | $176,670 | $176,670
Actual Remaining Task Budget | $128,130 $97,403 | $42,009 | $87 $87
5c_|MAP REVISIONS (Dames & Moore)
| __ Actual % Work Completed 27% 35% 55% | 100%| 100%, |
Planned % Complete $(todate) | __—- 27% 38%! 71% 100%| 100% 100% 100%
Actual % Expended $ (to date) 27% 35% | 56% | 100% 100% | |
Planned $ (this period) $38,744 $15,357 | $47,693 $40,791 | | $0 | $0 $0
Actual $ Expended (this period) $38,744 $11,605 $28,942 | $63,220 $0 | |
Planned $ (to date) $38,744 $54,101 | $101,794 | $142,585 | $142,585 | $142,585 $142,585
Actual $ Expended (to date) $38,744 $50,349 | $79,291 $142,510 | $142,510 | | Contract No. 820, Amend. No. 1 | $142,585 | $142,585 | $142,585 | $142,585 | $142,585 | $142,585 $142,585
Actual Remaining Task Budget | $103,841 $92,236 $63,294 | $75 $75
5d_| FINALIZE EVAL (Dames & Moore) | I |
Actual % Work Completed 0% 0%) «0% 28% 100%
| Planned % Complete $ (to date) 0% 0% __0% 14% 100% | 100%! 100%
Actual % Expended §$ (to date) 0% 0% 0% 28% 100% |
Planned $ (this period) $0 $0 | $0 $7,956 $48,780 $0 $0
Actual $ Expended (this period) $0 $0 $0 $16,129 $40,607 |
Planned $ (to date) $0 _ $0 $0 $7,956 $56,736 $56,736 $56,736 |
Actual $ Expended (to date) $0 $0 $0 $16,129 $56,736 |
Contract No. 820, Amend. No. 1 | $56,736 | $56,736 | $56,736 | $56,736 | $56,736 | $56,736 | $56,736 |
Actual Remaining Task Budget $56,736 $56,736 | $56,736 $40,607 ($0),
7/19/99 Page 2 of 2
SOUTHERN INTERTIE PROJECT
PROJECT SUMMARY REPORT
2ND QUARTER 1999
THROUGH PERIOD ENDING:
07-10-99
3RD QUARTER 1999
MAY JUN
|ENGINEERING SUPPORT & PROJECT COORDINATION (POWER Engineers)
Actual % Work Completed 8%| 18%! 40% 39% 85% | _
Planned % Complete $ (to date) 8% 27% 52% | 78% 100% | 100% | 100%
Actual % Expended $ (to date) 8% 17% 22% 39% 51% |
| __ Planned $ (this period) $3,280 $8,000 $10,500 $10,500 $9,303 | $0 | lL $0
Actual $ Expended (this period) $3,280 $3,893 $2,102 $6,929 $4,902 | |
Planned $ (to date) $3,280 | $11,280 $21,780 [ $32,280 $41,583 | $41,583 $41,583
Actual $ Expended (to date) $3,280 | $7,173 | $9,275 $16,204 $21,106 | | -
Contract No. 820, Amend. No. 1 $41,583 $41,583 $41,583 $41,583 $41,583 | $41,583 $41,583
Actual Remaining Task Budget $38,303 $34,410 | $32,308 | $25,379 $20,477 |
TASK 5 TOTAL
Actual % Work Completed 26%) 40%| 60%! 86% 99%| _
Planned % Complete $ (to date) 26% 44% 66% | 88% 100% 100% | 100%
Actual % Expended $ (to date) 26% 40%| 58%| 86% 96%
Planned $ (this period) $118,913 | $84,345 $103,522 | $100,352 $58,083 | $o| $o
Actual $ Expended (this period) | $118,913 $65,517 | $86,437 | $128,200 $45,509 | _
Planned $ (to date) _ $118,913 | $203,258 | $306,780 $407,132 | $465,215 | $465,215 | $465,215
Actual $ Expended (to date) $118,913 | $184,430 $270,867 $399,067 | $444,576 | ill Contract No. 820, Amend. No. 1 | $465,215 | $465,215 | $465,215 | $465,215 | $465,215 | $465,215 | $465,215
Actual Remaining Project Budget | $346,302 $194,348 $66,148 $20,639 | |
ANILCA APPLICATION
$280,785 |
TASKS 5 and 6 TOTAL
Actual % Work Completed 55% 55% 55% | 55% 85%| |
Planned % Complete $(todate) | 56% 56%| «67% 78% 100% 100% | 100% Actual % Expended $ (to date) 56% 56% 56% | 56% 87% | | | Planned $ (this period) $0 $o| $5,866/ $5,866 | $11,720 $0 $0
Actual $ Expended (this period) $0 $0 | $0 | $0 $16,239 |
Planned $ (to date) $30,014 | $30,014| $35,880! $41,746| $53,466 $53,466 | $53,466
Actual $ Expended (to date) $30,014 | $30,014 $30,014. $30,014 | $46,253 | |
Total Task 6 NTE Budget $53,466 | $53,466 $53,466 $53,466 | $53,466 $53,466 $53,466
Actual Remaining Task Budget $23,452 $23,452 $23,452 | $23,452 $7,213 | |
Notes:
$304,237
|1) $30,014 had previously been expended in Task 6.
|2) The March 1999 invoice is $122,887 of which $3,973 was applied to the previous remaining budget in Task 5.
Actual % Work Completed 29% 41% 60% 83% 95% | | -
Planned % Complete $ (to date) 29% _ 45% 66% 87%| 100% 100%, 100%
Actual % Expended $ (to date) 29% 41% 58% | 83% 95% |
__Planned $ (this period) $118,913 | $84,345 | $109,388 | $106,218 $69,803 | $o, _— $0
Actual $ Expended (this period) | $118,913 | $65,517 $86,437 | $128,200 | $61,748 | Ts
Planned $ (to date) $148,927 | $233,272 $342,660 | $448,878 | $518,681 $518,681 $518,681
Actual $ Expended (to date) $148,927 | $214,444 | $300,881 $429,081 | $490,829 |
Tasks 5 and 6 Total $518,681 | $518,681 $518,681 | $518,681 | $518,681 | $518,681 | $518,681 |
Remaining Tasks 5 & 6 Budget | $369,754 $217,800 $89,600 $27,852 | |
03/18/99 Contract 820 Amendment No. 1
i=
HLY 23-321a1
|3) The dollar amounts in tasks 5a, 5b, 5c, and 5d include the two percent (2%) mark-up on D&M's budget and expenditures, ) The co = S ; ic ne
~ DAMES & MOORE
A DAMES & MOORE GROUP COMPANY
7500 North Dreamy Draw Drive
Suite 145
Phoenix, Arizona 85020 July 9, 1999 602 371 1110 Tel 602 861 7431 Fax
Randy Pollock
POWER Engineers, Inc.
3900 S. Wadsworth Blvd., Suite 700
Lakewood, CO 80235 -
Progress Billing D&M # 09203-009-050
Southern Intertie EIS Environmental/Preliminary
PE # 120376-01
Dear Mike:
Transmitted with this letter is our thirty-third progress billing dated July 2, 1999 for the Southern
Intertie Project Environmental Impact Statement. This covers the period beginning May 29, 1999
and ending June 25, 1999. The billing for the attached invoice is in the amount of $55,731.50,
which brings the total, billed to $2,808,125,70.
This report provides a summary of the activities conducted for each task involved in the
preparation of the Environmental Analysis Report (EVAL). The attached table summarizes the
costs during May 1999 for the Southern Intertie Project. The principal activities conducted
during this period are summarized below.
Task 5a —- Comment Organization
During June we finalized the responses on the tracking tables to reflect actual responses in the
EVAL.
Task 5b — Revise EVAL
During May we prepared 50 copies of the Final. We received comments from USFWS on
Chapter 4 Biology section and incorporated responses into the Final EVAL.
Task 5c — Maps and Graphics
During May we completed the map volume.
During June we finalized the Map Volume and Project Descriptions and Simulations Graphics
Volume.
FADATA\PRON09203\009\Prog RptsVuly99-PROG.doc
Offices Worldwide
it | DAMES & MOORE
MNS" A DAMES & MOORE GROUP COMPANY
July 9, 1999
Page 2
Schedule (same as last month)
Task 5d - Finalize EVAL Complete by July 2, 1999
Task 6 - ANILCA Application Draft Complete by July 2, 1999
Finalized early July
For questions regarding the enclosed billing, progress report, or backup information, please
contact Brandie Powers or me for clarification.
Sincerely,
DAMES & MOORE
Tim Tetherow in
Project Manager
Enclosure: Invoice
cc: Brandie Powers
FADATA\PRON09203\009\Prog RptsUuly99-PROG.doc
Offices Worldwide
ACTIVITIES COMPLETED DURING
CURRENT PERIOD
DESCRIP- TION ACT% | SCH%
Scoping
Inventory
Impact
Assessment/
Mitigation
Planning
Alternative
Selection
@ completed final EVAL
@ completed draft application
KEY ISSUES:
@ None
SCHEDULE: On schedule
BUDGET:
$ Budgeted | $ Expended $ Remaining
Totals $2,814,008.28 | $2,808,125.70 $5,882.58
(C\TEAMLINK\STAGING\IM1667.D0C
ACTIVITIES TO BE COMPLETED IN NEXT
30 DAYS
Scoping
Inventory
3 Impact
Assessment/
Mitigation
Planning
4 Alternative
Selection
™@ finalize ANILCA application
C.\TEAMLINK\STAGINGUM1667.DOC
yur av 22
SUBTOT
|5oMap Revisions
4$ 19,320.00
Resource S$ 3,807.00
GIS} 68,590.00
amy S$ 2,024.00
S 14,780.00
O $ 113,521.00
\Sd-Finalize EVAL
Management §
Resource Swidics| $
GIs|$
15,877.00 | s
8,824.00 | s
1,948,00| s
Suppor} $ 3,315.00] s
Expenses| $ 25,660.00
SUBTOTA: it ‘Application 16 ll
45,000.00
Resource Studics| 5 303,00
GIS|$ :
500,00
6,000.00
$ 21,803.00
TOTAL $ 384,110.00
P:09203/009/Mngmt/CashFlow Projections
acrorm! yews & MUURE
S$ 13,199.00
100%
335.00
100%)
3,178.00
5 a ala
1
5,378.65
6,309.66
138%)
143.78
1,23440
100%
PZ
3 - |8 - |S 45,016.00
100%)
$ - Is - |S 78,640.73
108%
s - Is > |S 2,897.60
WE
s . s . S 12618.89
138%
$ - s . S 7481.78
19%)
146,455.00
100%
$ 19,320,00
100%
S 32,261.50
366%
$ 45,135.50
66%
3 2,024.00
100%
S$ 14,780.00 00%
113,531.00
o% 3,980.87 85% 13,118.34 | $ .
61% 1,433.65 | $ -
28S% 11,037.72
sams om
TASIRB
vu av ao) ater onic & MuURt P.3
United States Department of the Interior
FISH AND WILDLIFE SERVICE
1011 E. Tudor Rd.
Anchorage. Alaska 99503-6199
JUN 23 1999
Tim Tetherow
Dames & Moore
7500 North Dreamy Draw Drive
Phoenix, Arizona 85020
Dear Mr. Tetherow:
This is to provide you with comments from this office and the Kenai National Wildlife Refuge on
the Biological Resources portion of Chapter 4, and the Map Set for the Southern Intertie Project
EVAL. Due to the short review time during the busy field work season, some staff reviewers
were not available at this time, and we understand that some tables and maps are still undergoing
final revision. However, we believe that the content and organization of the EVAL is now
sufficient to provide a basis from which the Rural Utilities Service can begin preparing the
preliminary draft EIS for the proposed project.
GENERAL:
Chapter 4 contains a great amount of information with regard to potential impacts of the proposed project down to the level of individual route segments. However, the agencies will base right-of-way decisions on a comparison of alternative routes, which should be highlighted
throughout the EVAL.
Foreseen and unforeseen cumulative effects will, in time, reduce the suitability of the northem
portion of the Kenai NWR as wildlife habitat. Conversely, degradation of habitats and wildlife populations will occur along the Tesoro route whether the project is built or not. The area is
largely platted, subdivided, and slated for development. In a cumulative effects analysis, this
cannot be understated.
Throughout the Chapter, impacts are discussed on the habitat conditions as they exist, which is as it should be. However, in the cumulative impacts section, and the discussions of long-term
impacts, it needs to be pointed out that habitat conditions can change dramatically, and thus
statements like the Mystery Creek area being low lynx density, therefore is no significant impact, is only true for now. A significant fire in the northern portion of Game Management Unit 15A,
may result in this area becoming the next “hot spot” for critters like moose, hare, and lynx. An event of this type is not improbable during the life of the line.
In relation to potential bird strikes, the cumulative effects analysis did not adequately address the _ Specific number of utility corridors already in place across the peninsula. Also, the potential bird collision hazard can not be dismissed by stating that collision with power lines has not been
wee ee sr eS & MUU Poa
identified in the literature as a major source of mortality in birds in Alaska (page 4-9), especially if
no research has been conducted to specifically address the number of bird strikes in Alaska.
SPECIFIC COMMENTS:
[Page | Paragraph [Line |Comment
What does MOA have to do with a link-by-link analysis?
MOA should be spelled out
[42 | istbuller | 2nd | spell out DLP ;
“Project is not expected to reduce ...” Disagree with this
statement. Widening an existing corridor could increase edge
4-12 7-8th
quotation needs to be checked.
j4i3 fs || alder really isn’t moose forage on Kenai Peninsula
Chapter 3 (Section 3.6.5), since the National Marine Fisheries
Service is currently reviewing petitions under the Marine
oo disagree with statement that “application of selective
effect or cutting new corridors will further reduce habitat into
4-14 [3rd | sth | “lynx population...” delete “had”, replace with “may have”
Mammal Protection Act and the Endangered Species Act
mitigation measures will avoid such'impacts. Mitigative
4-10
smaller isolated patches if habitat is already fragmented .
“r.o.w. represents”... delete word “very”
Although not currently listed as threatened or endangered, the
which could affect the status of the Cook Inlet population of
measures identified on pages 4-4 & 4-5 “minimize” impacts.
4-11 “Black bears are more widespread”... More than what?
Delete the word “more.”
“Vegetation per se”... delete word “is” and “‘nearly” This
beluga whale should be discussed in this section, and in
this species.
The Steller’s eider should be evaluated in this Section (see
Chapter 3, Section 3.6.5).
wee ee tt rs er oe PURE Pa
“during winter construction”... [Be aware that black bears are known to den in the immediate vicinity of the corridor].
“is not expected to impact”... Why not?- impact may not be
“road is open to”... Delete the words “four wheeled” and
replace with the word “highway”. Insert the word “August”
in front of “September.”
“road is open to....” delete “two-wheeled vehicles in the
summer and.”
“Moose”... Several prescribed burns are planned for the area .
This will have a positive effect for moose. Power lines create
safety concerns for fire management operations and if the line
precluded burning moose will be negatively affected,
4-34 | General Fire issue is addressed in the summaries but should be
included in the specific moose impact section
The following additional discussion points should be added to
the cumulative impacts introduction:
1. Examples of why certain lands within the KNWR
are not fully protected (i.e., Native selections and
conveyance, Federal oil and gas leases, etc.)
2. Examples of the types of future development that
are reasonably foreseeable, such as timber harvesting, oil and gas field development, and lodge and resort
development. As corporations for profit, Native
inholders will seek a positive return from their land
holdings.
3. Which species are already considered to be
adversely affected by cumulative impacts (i.e., brown
bear and Canada Lynx),
[4-55 |6th | Sth __| Insert the word “additional” in front of the word “canine.” 455 |7th | ist | Delete “1949" replace with “1969" ia uO a Delete “1967" replace with “1947"
Insert the word “current” in front of the word “high”
wee et ee UR ‘ P.6
The statement is made that “the potential for long-term
collision hazard for waterfowl along the Enstar alternative is
probably low ...” Although the degree of collision hazard is
not possible to predict, there will be some hazard that will
remain over the long term (i.e., the life of the project).
Delete the words “And General Wildlife Habitat" from the
Md tae map. General wildlife habitat is shown on map
MV- In the title, replace the word “development” with the word
17 "impacts."
Revise this map as per previous discussion to simplify multiple
interest land status.
Thank you for your efforts to work closely with the Service toward developing an EIS for this
project. Please contact Brian Anderson at (907) 786-3379 if you have questions or need
additional information.
Sincerely,
Sharon N, Janis
Chief, Division of Realty
cc. Larry Wolf
Rural Utilities Service
Dora Gropp FT Chuigach Electric Association wg
We,
bec: Robin West *
KNWR
RECORD OF CONVERSATION
DATE: June 16, 1999 JOB NO.: 09203-009-050
RECORDED BY: _ Tim Tetherow OWNER/CLIENT: Chugach Electric
TALKED WITH: Larry Wolfe OF: Rural Utilities Service
Engineering and Environmental
TELEPHONE: wx visit 0 MEETING 0
ROUTE TO: INFORMATION ACTION
MAIN SUBJECT: SIP EVAL Biology Comments
ITEMS DISCUSSED:
| informed Larry that we had received the comments from the KNWR on the EVAL Biology impact
section. Of the two pages of comments, one page is general, focusing on cumulative impacts, and the
other page consists of specific comments that are primarily requested word changes. As a result of the
brief comments from KNWR, | told Larry that we would incorporate them into the EVAL. Brian Anderson
has promised his comments by June 21. Assuming his comments are brief, we will incorporate them
also. That way we can confirm that the EVAL reflects the review of the FWS on the biology sections.
Larry said that he is looking forward to getting started on the EIS with Mangi Environmental. We will send
two copies to RUS and two to Mangi.
FADATA\PRON09203\000\Prog Rpts\UuneROC2.doc DAMES & MOORE
RECORD OF CONVERSATION
DATE: June 15, 1999 JOB NO.: 09203-009-050
RECORDED BY: Tim Tetherow OWNER/CLIENT: Chugach Electric
TALKED WITH: Brian Anderson OF:U.S. Fish and Wildlife Service
Division of Realty
TELEPHONE: w (907) 786-3379 visit 0 MEETING 0
ROUTE TO: INFORMATION ACTION
MAIN SUBJECT: Changes to SIP EVAL Biology Maps
ITEMS DISCUSSED:
We had a conference call with Brian Anderson and Roy Baker, Dames & Moore GIS specialist to review
the map changes with Brian. Brian had sent a new FWS jurisdiction map for our use. Due to the
complexity of the categories of native, state, and FWS lands, we developed a simplified legend. We also
reviewed all of the changes in land status and will incorporate them into the Land Jurisdiction and
cumulative impact maps. We also discussed all of the biology maps. There were no specific changes
with the maps from Brian, and he had not received any comments from the KNWR. We agreed that we
would proceed with printing the biology maps.
Brian informed us that he had just received the comments from the KNWR, and that there were only two
pages. | asked him to fax them. Upon review, it is apparent that we will be able to respond to most of
them and still meet our schedule. Brian said that he had not reviewed the report yet, but would provide
comments by June 21.
\DM_PHXI\SYS\DATA\PRON09203\009\Prog RptsUuneROCI.doc DAMES & MOORE