HomeMy WebLinkAboutS Intertie report 10-1998CHUGACH ELECTRIC ASSOCIATION, INC. Cikine October 27, 1998 Alaska Industrial Development and Export Authority 480 West Tudor Road Anchorage, Alaska 99503-6690 Attention: Mr. Randy Simmons, Executive Director Subject: Southern Intertie Monthly Report for October 1998 W.0.#E9590081 Dear Mr. Simmons: Please find enclosed 1 (one) copy of the Southern Intertie Report for the Month of October 1998. If there are any questions, please contact Dora Gropp, (907) 762-4626. Sincerely, Fe WM (ye aN Bjornstad an General Manager ENG/DLG:jb Enclosures: 1 (one) copy of Southern Intertie Monthly Report CG Lee Thibert Joe Griffith Michael Massin Dora Gropp Jim Borden Mike Cunningham Don Edwards W.0.#E9590081, Sec., 2.1.3 RF 5601 Minnesota Drive ¢ P.O. Box 196300 * Anchorage, Alaska 99519-6300 Phone 907-563-7494 # FAX 907-562-0027 CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska SOUTHERN INTERTIE Report for the Month of October 1998 IV. Vi. TABLE OF CONTENTS PAGE SUMMARY ........cccccsssssesssssssssssesseesnesseeseesnessesneeeneeseesseeeeneeaeenesnesseeseeenenaenannas 1 FINANCIAL ........cccccsesssessecsseeseseeeseesessesssusseesasseesseesseusersensesseseesseeseeseeseesetenes 2 1. TOTAL PROJECT EXPENDITURES AS OF SEPTEMBER 30, 1998 2. CHUGACH STATEMENT FOR AUGUST AND SEPTEMBER 1998 3. BANK STATEMENT OF AUGUST 1998 4, PROPOSED CASH FLOW (REVISED 10/98) SCHEDULE ...........csssssssssssssessesssssersaesneesnsssessseseessseseeseessessesessseseeeaseneenensees 3 ITEMS FOR APPROVAL .........scccsssesssssssssssssseenseesessesersseeeteeesateseesessasensentons 4 FUNDING INCREASE FOR POWER ENGINEERS/DAMES & MOORE (LETTER OF OCTOBER 13, 1998). ITEMS FOR DISCUSSION .........:scscssssssssssssssessseseeessesssseesseeeensesseeesesaeeaneas 5 NONE. ITEMS FOR INFORMATION ........2c:scssssscsssesesseessesesseseessesseneenseesneesenaesenees 6 1. POWER ENGINEERS’ MONTHLY REPORT PHASE IB — ENVIRONMENTAL ANALYSIS, OCTOBER 16, 1998 2. USFS RETURN OF FUNDS, LETTER OF JULY 23, 1998 ii SUMMARY Power Engineers/Dames and Moore’s effort for the EVAL preparation (Phase iB) is 99% complete. The changes to the biology section of the Eval requested by USFWS during meetings in September have been evaluated and will cause a delay in completion of the document to December of this year. We are still planning on submitting the ANILCA permit application at the same time. A new schedule for the EIS development will be established after the EVAL has been submitted to the federal agencies. Dames and Moore is proceeding with the requested changes. Since the present funding under the contract is exhausted, the consultants have not submitted invoices this month, but they have requested an increase of $118,193 for the completion of the EVAL (see letter of October 13 in Section 4, Items for Approval) It is proposed to use contingency funds for the additional expenses. A change in overall funding will not be required as shown on the Cash Flow Plan included in Section Il. Expenditures for Phase 1B of the project stand as follows: DESCRIPTION | POWER |USFS/USFWS/| CHUGACH | TOTAL ENGINEERS RUS BUDGET $3,043,423 $100,000] $400,000] _ $3,543,423 ALLOCATED $19,981 $0 $40,000 $59,981 CONTINGENCY TOTAL [$3,063,404 $100,000! _$440,000| $3,603,404 AMENDMENTS $284,361 $31,437] $0| $315,798 TOTAL $3,347,765 $131 437 $440,000! $3,919,202 [COMMITMENT | SPENTTO | $3,304,151 $1 any $161,452| $3,596,160 DATE =| % OF TOTAL soul 99% 37% 92% Total Project expenditures, as of October 19, 1998 are $4,551,824, which = includes a payment to RUS for the EIS preparation in the amount of $97,670. ll. FINANCIAL 1. Total Project Expenditures as of September 30, 1998 2. Chugach Statement for August and September 1998 3: Bank Statement for August 1998 4. Proposed Cash Flow (Revised 10/98) Project Expenditures Direct Labor Indirect Labor Power Engineers Miscellaneous Total Grant Fund Expenditures Direct Charges that Chugach has been Reimbursed for Plus General, Administrative & Construction Overhead Total Amounts Paid to Chugach CHUGACH ELECTRIC ASSOCIATION, INC. Southern Intertie Transactions Inception Through August 31, 1998 (1) Chugach August 5, 1998 invoice for June 1998 charges RECEIVEr) SEP 3 0 1998 TRANSMISSION & SPECIAL PROJECT cc: Dora Gropp Alayne Switzer Year to Date Month Inception Through Ended Inception Through 12/31/97 7/31/98 8/31/1998 Through 8/31/1998 $108,471.09 $20,225.31 $1,875.42 $130,571.82 38,898.99 8,681.55 786.62 48,367.16 3,739, 166.41 342,178.87 23,378.97 4,104,724.25 108,961.39 61,406.73 97,670.00 268,038.12 $3,995,497.88 $432,492.46 $123,711.01 $4,551,701.35 Year to Date Month Inception Through Ended Inception Through 12/31/97 7/31/98 8/31/1998 Through 8/31/1998 $3, 842,318.24 $487,516.67 $59,362.04 (1) $4,389, 196.95 19,211.59 2,437.58 296.81 (1) 21,945.98 $3,861,529.83 $489,954.25 $59,658.85 (1) $4,411,142.93 9/30/98 Invoice Date Dec-95 Jan-96 Feb-96 Mar-96 Apr-96 May-96 Jun-96 Jun-96 Aug-96 Sep-96 Oct-96 Oct-96 Dec-96 Life to Date Jan-97 Feb-97 Mar-97 Apr-97 May-97 Jun-97 Jul-97 Aug-97 Aug-97 Sep-97 Oct-97 Nov-97 Dec-97 Year to Date Life to Date Jan-98 Feb-98 Mar-98 Apr-98 Apr-98 May-98 Jun-98 Jul-98 Aug-98 Sep-98 Oct-98 Nov-98 Dec-98 Year to Date Life to Date Month Incurred Jun-Oct 95 Nov-Dec 95 Jan-96 Feb-96 Mar-96 Apr-96 May-96 Jun-96 Jul-96 Aug-96 Sep-96 Oct-96 Nov-96 Dec-96 Jan-97 Feb-97 Mar-97 Apr-97 May-97 Jun-97 Jul-97 Aug-97 Sep-97 Oct-97 Nov-97 Dec-97 Jan-98 Feb-98 Mar-98 Apr-98 May-98 Jun-98 Costs OH Total 22,614.00 113.07 22,727.07 0.00 0.00 0.00 176,265.61 881.33 177,146.94 7,660.92 38.30 7,699.22 251,912.29 1,259.56 253,171.85 172,070.45 860.35 172,930.80 127,113.82 635.57 127,749.39 35,628.41 178.14 35,806.55 40,919.00 204.60 41,123.60 57,116.72 285.58 57,402.30 168,312.54 841.56 169,154.10 202,010.97 1,010.05 203,021.02 171,462.74 857.31 172,320.05 1,433,087.47 7,165.42 _ 1,440,252.89 234,735.50 1,173.68 235,909.18 306,667.10 1,533.34 308,200.44 5,045.85 25.23 5,071.08 124,380.57 621.90 125,002.47 177,117.40 885.59 178,002.99 165,814.35 829.07 166,643.42 158,762.80 793.81 159,556.61 158,786.12 793.93 159,580.05 154,159.15 770.80 154,929.95 243,365.76 1,216.83 244,582.59 193,127.79 965.64 194,093.43 258,833.19 1,294.17 260,127.36 228,435.19 1,142.18 229,577.37 2,409,230.77 12,046.17 —2,421,276.94 3,842,318.24 19,211.59 3,861,529.83 0.00 0.00 0.00 153,179.64 765.90 153,945.54 0.00 0.00 0.00 39,750.15 198.75 39,948.90 49,887.09 249.44 50,136.53 64,102.85 320.51 64,423.36 7,283.97 36.42 7,320.39 173,312.97 866.56 174,179.53 59,362.04 296.81 59,658.85 0.00 0.00 0.00 0.00 546,878.71 2,734.39 549,613.10 4,389,196.95 21,945.98 4,411,142.93 Inception-to-Date Charges 22,727.07 22,727.07 199,874.01 207,573.23 460,745.08 633,675.88 761,425.27 797,231.82 838,355.42 895,757.72 1,064,911.82 1,267,932.84 1,440,252.89 1,676,162.07 1,984,362.51 1,989,433.59 2,114,436.06 2,292,439.05 2,459,082.47 2,618,639.08 2,778,219.13 2,933,149.08 3,177,731.67 3,371,825.10 3,631,952.46 3,861 ,529.83 3,861 ,529.83 4,015,475.37 4,015,475.37 4,055,424.27 4,105,560.80 4,169,984.16 4,177,304.55 4,351,484.08 4,411,142.93 Chugach Electric Association, Inc. Southern Intertie Activity Summary August, 1998 Beginning Grant Chugach Ending Bank Funds Interest Invoices Bank Year Balance Received Earned Paid Balance 1996 0.00 2,771,277.00 40,361.59 (1,440,252.89) 1,371,385.70 1997 1,371,385.70 1,346,934.00 67,734.96 (2,421,276.94) 364,777.72 1998* 364,777.72 454,780.00 16,447.15 (549,613.10) 286,391.77 Total 4,572,991.00 124,543.70 _(4,411,142.93) * Through August, 1998 bank statement (does not include Chugach invoices for charges incurred in July or August, 1998) RECEIVED) SEP 3 0 1998 TRANSMISSION & SPECIAL PROJECT Chugach Electric Association, Inc. Southern Intertie Activity Summary September, 1998 Beginning Grant Chugach Ending Bank Funds Interest Invoices Bank Year Balance Received Earned Paid Balance 1996 0.00 2,771,277.00 40,361.59 (1,440,252.89) 1,371,385.70 1997 1,371,385.70 1,346,934.00 67,734.96 (2,421,276.94) 364,777.72 1998* 364,777.72 454,780.00 17,446.08 (588,600.46) 248,403.34 Total 4,572,991.00 125,542.63 _(4,450,130.29) * Through September, 1998 bank statement (does not include Chugach invoices for charges incurred in August or September, 1998) Project Expenditures Direct Labor Indirect Labor Power Engineers Miscellaneous Total Grant Fund Expenditures Direct Charges that Chugach has been Reimbursed for Plus General, Administrative & Construction Overhead Total Amounts Paid to Chugach CHUGACH ELECTRIC ASSOCIATION, INC. Southern Intertie Transactions Inception Through September 30, 1998 Year to Date Month Inception Through Ended Inception Through 12/31/97 8/31/98 9/30/98 Through 9/30/98 $108,471.09 $22,100.73 $2,982.77 $133,554.59 38,898.99 9,468.17 1,249.50 49,616.66 3,739, 166.41 365,557.84 14,222.60 4,118,946.85 108,961.39 159,076.73 570.20 268,608.32 $3,995,497.88 $556,203.47 $19,025.07 $4,570,726.42 Year to Date Month Inception Through Ended Inception Through 12/31/97 8/31/98 9/30/98 Through 9/30/98 $3,842,318.24 $546,878.71 $38,793.39 (1) $4,427,990.34 19,211.59 2,734.39 193.97 (1) 22,139.95 $3,861,529.83 $549,613.10 $38,987.36 (1) $4,450,130.29 (1) Chugach August 28, 1998 invoice for July 1998 charges ce: Dora Gropp Alayne Switzer 10/23/98 Invoice Month Date Incurred Costs OH Total Dec-95 Jun-Oct 95 22,614.00 113.07 22,727.07 Jan-96 0.00 0.00 0.00 Feb-96 Nov-Dec95 176,265.61 881.33 177,146.94 Mar-96 Jan-96 7,660.92 38.30 7,699.22 Apr-96 Feb-96 251,912.29 1,259.56 253,171.85 May-96 Mar-96 = 172,070.45 860.35 172,930.80 Jun-96 Apr-96 = 127,113.82 635.57 127,749.39 Jun-96 May-96 35,628.41 178.14 35,806.55 Aug-96 Jun-96 40,919.00 204.60 41,123.60 Sep-96 Jul-96 57,116.72 285.58 57,402.30 Oct-96 Aug-96 = 168,312.54 841.56 169,154.10 Oct-96 Sep-96 202,010.97 1,010.05 203,021.02 Dec-96 Oct-96 171,462.74 857.31 172,320.05 Life to Date 1,433,087.47 7,165.42 _ 1,440,252.89 Jan-97 Nov-96 234,735.50 1,173.68 235,909.18 Feb-97 Dec-96 306,667.10 1,533.34 308,200.44 Mar-97 Jan-97 5,045.85 25.23 5,071.08 Apr-97 Feb-97 124,380.57 621.90 125,002.47 May-97 Mar-97 177,117.40 885.59 178,002.99 Jun-97 Apr-97 —- 165,814.35 829.07 166,643.42 Jul-97 May-97 158,762.80 793.81 159,556.61 Aug-97 Jun-97 = 158,786.12 793.93 159,580.05 Aug-97 Jul-97 = 154,159.15 770.80 154,929.95 Sep-97 Aug-97 243,365.76 1,216.83 244,582.59 Oct-97 Sep-97 193,127.79 965.64 194,093.43 Nov-97 Oct-97 258,833.19 1,294.17 260,127.36 Dec-97 Nov-97 228,435.19 1,142.18 229,577.37 Year to Date 2,409,230.77 12,046.17 _2,421,276.94 Life to Date 3,842,318.24 19,211.59 3,861,529.83 Jan-98 0.00 0.00 0.00 Feb-98 Dec-97 153,179.64 765.90 153,945.54 Mar-98 0.00 0.00 0.00 Apr-98 Jan-98 39,750.15 198.75 39,948.90 Apr-98 Feb-98 49,887.09 249.44 50,136.53 May-98 Mar-98 64,102.85 320.51 64,423.36 Jun-98 Apr-98 7,283.97 36.42 7,320.39 Jul-98 May-98 173,312.97 866.56 174,179.53 Aug-98 Jun-98 59,362.04 296.81 59,658.85 Sep-98 Jul-98 38,793.39 193.97 38,987.36 Oct-98 0.00 Nov-98 0.00 Dec-98 0.00 Year to Date 585,672.10 2,928.36 588,600.46 Life to Date 4,427,990.34 22,139.95 4,450,130.29 Inception-to-Date Charges 22,727.07 22,727.07 199,874.01 207,573.23 460,745.08 633,675.88 761,425.27 797,231.82 838,355.42 895,757.72 1,064,911.82 1,267 ,932.84 1,440,252.89 1,676,162.07 1,984,362.51 1,989,433.59 2,114,436.06 2,292,439.05 2,459,082.47 2,618,639.08 2,778,219.13 2,933,149.08 3,177,731.67 3,371,825.10 3,631 ,952.46 3,861 529.83 3,861 ,529.83 4,015,475.37 4,015,475.37 4,055,424.27 4,105,560.80 4,169,984.16 4,177,304.55 4,351 ,484.08 4,411,142.93 4,450,130.29 CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska 09/28/98 TO: Dora Gropp - Manager, Transmission & Special Projects FROM: Kurt Parish, Plant Accountant SUBJECT: 9590081 - Southern Intertie Route Selection Study You had previously requested establishment of this work order to study route selection for the Southern Intertie for the Intertie Participants Group. The Association will be reimbursed for charges to this work order. The following charges occurred during August 1998. Direct Labor 1,875.42 Indirect Labor 786.62 Power Engineers Invoice #53625 22,684.41 Power Engineers Invoice # 53626 694.56 USDA - Rural Utililitiy Service 97,670.00 Sub-Total $123,711.01 General, Administrative & Construction Overhead (0.5%) 618.56 Total Charges $124,329.57 Please review the attached backup and indicate your concurrence below if you are in agreement that these charges are correct for this work order and time period. As per your request, | will keep the original in the work order file. Concur: ve. x Lr Y2Y/ 98 Signature Date KP WOfiles/E9590081 Attachments RECEIVEP) SEP 2 9 1998 NSMISSION & SPECIAL PROJECT 9/28/98 iy CHUGACH ASSOCIATION PAGE 429 MONTH K S : FOR MONTH ENDING: 08/31/98 WORK SOURCE 118947. 4119769 LETTER” 4862000002 SOURCE ID TOTAL SOURCE ID TOTAL 1862000015. £9590081 644 1862000001 7690 9590081 PYADM 574264414 1862000001 E9590081 574264414 [RECT LABOR DIRECT LABOR DIRECT LABOR ADMIN ADMIN PAY PER. ENDING 08/16/98 PAY PER. ENDING 08/16/98 1862000014 E9590081 ILCD ADMIN ADMIN ILCD 080798 1862000014 7690 £9590081 PYILA ILCD ADMIN ADMIN ILCD 082198 ‘Hae ees widow eee RK ORDER TOTAL : ‘on itt ilii ; 64,348.97 ~ £9590081 HR _: M SYSTEM aes : ACCOUNT WORK ORDER EMP # NAME MAJOR CENCC NUMBER TASK DEPT HOURS W/O TOTAL E9590081 TOTAL 46.00 1875.42 Employee 1D ** 05742644140 ** FINAL TIMESHEET RUN DATE: 08/03/98 Page 01 OF 02 GROPP , DORA L COMPANY 00010 DEPT# 430 Employee Signature e Supervisor Approval Ay hus, * BEGIN OATE 07/20/98 End Date 08/02/98 ACCOUNT # 8620/000/0 0726/000/0 6/000/0 0740/000/0 92000/000/0 10720/000/0 0750/000/0 0750/000/01 <-- OST CENTER Lesh rat earht bara ear ep a raat aor rag cc vac HOL FLT B-DAY 01 me | DATE oe = 00 700 00 700 ioe 960 | 709 | 952 | 726 Ai oF T 0 o a ee ee oryza| 1 7 ae TUE. ot aes 07/22 TE | Tag oe | SS 1 2.0 | male | is 1 Ao 1.0 tii ae <9 1 RI. Hes eS j___6.0 | if alee j___2,0 | = ep 1} : 07/26 | | IE =| MON. o7y27|__8.0| | orl | 2.0 1 [ 1.0 } Z 2, 1.0 10 = org3o 1.0 a, Li za A [UST 0 } ov3i| 2.0 i} q el TOTALS ae | ACCRUED LEAVE MEALS #920 | | | 6.150 PER DIEM #915 | —— | CAGE HEAL #927 | | -| Pl t SPLITS #911 alt | ¢ FINAL TIMESHEET RUN DATE: 08/17/98 Page 01 OF 02 Ri COMPANY 00010 DEPT# 430 ignature * Supervisor Approval Avy 2 BEGIN DATE 08/03/98 . End Date —08/16/' B - 5 s BE »| = Bs ree SUN. “| sail |__ 1.0 uo | —_|— 1 qt f + 1.0 1.0} vel | 1.0 = 1.0} 1 - r_| Dol led [- TOTALS Bs E - Ht | | r TH | RATE = + _____| Accrueo Leave HEALS #920 | 6.150 PER DIEM #915 - abe T —CHARGE MEALS #927 Jace LC + SPLITS #911 4 Employee ID ** 05742644140 ** FINAL TIMESHEET RUN DATE: 08/17/98 Page 02 OF 02 GROPP , DORA L COMPANY 00010 DEPT# 430 Employee Signature e Supervisor Approval Y * BEGIN DATE 08/03/98 End Date 08/16/98 ACCOUNT # 0740/000/01 10726/000/0 0720/000/0 6800/000/01 0750/000/0 8620/000/01 —f <== _ACCOUN COST CENTER Sali 90 690 690 2690 690 VAC WOL FLT B-DAY 0 0 9811499/10 |£9711270/30 | E959 DATE |---| Ps {| y Z 00 00 00 seo | roo | 952 | z2¢ [~a Tar oor = 1 or | sor ef TOTALS | ACCRUED LEAVE a L je C) INVOICE €) lyf in 3940 Glenbrook Drive hy £2 O18 —IENGINEERS a JOB: 120376-05 TASK S EVALUATION PREPARATION INVOICE NUMBER: $3625 CONTRACT#: 95-208 P.0.#: INVOICE DATE : 18-aug-1998 BILL THROUGH DATE : 08-aug-1998 PAGE NUMBER: i R ECEIVE DH CHUGACH ELECTRIC ASSOCIATIO S601 MINNESOTA DR. 19 PO BOX 196300 AUG 1998 ANCHORAGE. AK 99519-6300 5 TRANSMISSION & ATTW:MS. DORA GROPP SPECIAL PROJECT Oh < yo PROFESSIONAL SERVICES Hours Rate Aaount Kaufman. Laurie — 2.00 46.30 92.60 Kuemmgerer. Uta K 3.00 56.22 168.66 fMicGrau. Ginaveve 4.00 56.22 224.88 Pollock, Randy 9.00 115.76 1041.84 Valbert, Michael E 93.00 98.12 883.08 TOTAL LABOR 27.00 2411.06 2411.06 REIMBURSABLE EXPENSES Amount , PHONE & FAX 83.43 ut ge > POSTAGE & SHIPPING 183.28 SUBCONTRACTOR EXPENSE 20006. 64 ( TOTAL EXPENSES 20273.35 20273.35 dupsrerts a 1443, released, cae CURRENT CHARGES 22684, 412-7ask 33¢ Received APPROVED FOR PAYMENT y BY: W/A L- JECT ENGINEER DATE ie BY. Za PROJECT MANAGER BY W, DiREC? Os, Tadd SER! 23 DIVESON DATE TasK 35 = *PUBLIC INVOLVEMENT $8,270.71 si . whe 7 LANDS / REGULATORY $ 0.00 : EXECUTIVE MGR., 1&0 NETWORK SERVICE 3 CATE BY: V/A RECEIVED ’ GENERAL MANAGER DATE AUG 21 1998 W0.#_E?S9e081__ CON# 45-20 *Included in invoice total , ACCOUNTING ACCT. #£8L2000002 7690 DATE _J-20-78 _ ACCTS PAYABLE For any accounting questions please contact Ginaveve McGraw / f at (208)788-0311. b a For any other questions pleage contact Randy Pollock. TERMS: NET 30 DAYS FROM RECEIPT OF INVOICE. PAST DUE AMOUNT SUBJECT TO FINANCE CH: F 1%2% PER MONTH. xy Wily ENGINEERS JOB: 120376-06 TASK 6 AMNILCA APPLICATION INVOICE NUMBER: 53626 CONTRACT#: 95-208 P.0.#: INVOICE DATE : 18-aug-1998 BILL THROUGH DATE : 08-aug-1998 ECE PAGE _ NUMBER: t 19 CHUGACH ELECTRIC ASSOCIATION AUG 1998 S601 MINNESOTA DR. PO BOX 196300 TRANSMISSION & ANCHORAGE. AK 99519-6300 SPECIAL SANIECT ATTM:4S. DORA GROPP PROFESSIONAL SERVICES Houra Rate Amount Pollock, Randy 6.00 115.76 694.56 TOTAL LABOR 6.00 694.56 694.56 Released. at Dais. A BY: a 2 a] A > PROG PUBLIC INVOLVEMENT $0.00 LANDS/REGULATORY $0.00 oA! Geran. he W.0. #_E 7520086 CONE _VS-20F ACCT. #12420 009 02 7696 DATE _¥-20-77 — or any accounting questions please contact Ginaveve McGraw UG 21 1998 at (208)788-0311. SCOUNTING For any other questions please contact Randy Pollock. TERMS: NET 30 DAYS FROM RECEIPT OF INVOICE. PAST DUE AMOUNT SUBJECT TO FINANCE CHARGE OF 114% 3940 Glenbrook Drive P.O. Box 1066 Hailey, Idaho 83333 (208) 788-3456 Law d APEPOVED TOR PAYMENT | 1b. Fe PER MONTH. USDA AE United States Department of Agriculture Rural Development Rural Business—Cooperative Service » Rural Housing Service » Rural Utilities Service Washington, DC 20250 ‘ues25, SOD ECEIVE D Ms. Dora L. Gropp Manager, Transmission & Special Projects Aug 3 J 1998 Chugach Electric Association, Inc. P.O. Box 196300 TRANSMISSION & Anchorage, Alaska 99519-6300 SPECIAL PROJECT Dear Ms. Gropp: In a letter dated August 20, 1998, you agreed to amend the existing contract with the Mangi Environmental Group, Inc. (Mangi). The new Statement of Work (SOW) authorizes Mangi to prepare the Southern Intertie Project Draft Environmental Impact Statement (DEIS) from the Environmental Analysis. The SOW also authorizes a representative of Mangi to travel to Alaska and participate in public hearings that are mandated by ANILCA. At thistime the Rural Utilities Service (RUS) is requesting payment in the amount hich includes the 3% fee imposed by the Huntington District of the Army CorpsvfEngineers. In accordance with the provisions of Attachment C to the Cooperative Agreement between the RUS and the Intertie Participants Group (IPG), the check should be made payable to USDA, Rural Utilities Service. Any funds not spent or obligated under this agreement will be refunded to the IPG. If you have any questions, please contact Larry Wolfe at (202) 720-5093. APPROVED FOR PAYMENT BY: BY. BY: BY: OV eA AER ONE W.0.# E95200g) CON#_7%-233 ACCT. #18630 09002 767) DATE Aug. 3! ag erveb| LY "Cannons se ED ger 8 3 - SEP 02 1998 ENies ' ACCOUNTING _ AGCTS PAY AS -= CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska 10/23/98 TO: Dora Gropp - Manager, Transmission & Special Projects FROM: Kurt Parish, Plant Accountant SUBJECT: 9590081 - Southern Intertie Route Selection Study You had previously requested establishment of this work order to study route selection for the Southern Intertie for the Intertie Participants Group. The Association will be reimbursed for charges to this work order. The following charges occurred during September 1998. Direct Labor 2,982.77 Indirect Labor 1,249.50 Power Engineers Invoice #54326 8,843.64 Power Engineers Invoice # 54327 5,378.96 Dora Gropp - US Fish & Wildlife Meeting Expenses 570.20 Sub-Total $19,025.07 General, Administrative & Construction Overhead (0.5%) 95.13 Total Charges $19,120.20 Please review the attached backup and indicate your concurrence below if you are in agreement that these charges are correct for this work order and time period. As per your request, | will keep the original in the work order file. Concur: Bove, x. Ppp lofe 3/?f Signatui Date KP WOfiles/E9590081 Attachments REcEIVET) OCT 23 1998 10/23/98 PN W.O. NO. E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 E9590081 1862000001 1862000001 1862000001 1862000001 1862000001 1862000001 1862000002 1862000002 1862000002 1862000004 1862000014 1862000014 1862000014 1862000014 1862000015 COST ACCOUNT CENTER 7690 7690 7690 7690 7690 7690 7690 7690 7690 7690 7690 7690 7690 7690 2101 AMOUNT yeas LO ~ 163.08 + LeT 5S « 978.48 ~ 407.70 102.83- 2,982.77 8,091.67 5,378.96 751.97 14,222.60 570.20 570.20 57.04 576.10 §99.16 17.20 1,249.50 38,793 .39= 38,793 .39- 19,768.32- 19, 768:..3:2— EFFDATE 090498 090498 090998 091898 091898 092398 093098 093098 093098 093098 090998 090498 091898 092398 093098 REF1 PER. PER. PER. PER. PER. PER. PAY PAY PAY PAY PAY PAY HHA ae POWER ENGI POWER ENGI POWER ENGI DORA GROPP UNION ILCD ADMIN ILCD ADMIN ILCD UNION ILCD 09/30/1998 REF2 08/30/98 08/30/98 09/01/98 09/13/98 09/13/98 09/15/98 54326 54327 54326 9/9-9/10 E 090998 090498 091898 092398 EX00000106 DUN AND BRADSTREET _ REPORT 946 DBS HR “ORDER Z “CHECK EMP # NAME CENCC NUMBER TASK. DEPT HOURS AMOUNT DATE 5742644140 GROPP DL. w/O TOTAL E9590081 TOTAL Employee 1D ** 05742644140 ** GROPP , DORA L BEGIN DATE End Date a c mm 08/17/98 08/30/98 COMPANY 00010 DEPT# 430 FINAL TIMESHEET Employee Signature RUN DATE: 09/01/98 Page 01 OF 02 Supervisor Approval Avy * is : THU. Io FRI. Bee TOTALS ACCRUED LEAVE | 6.150 Employee 1D ** 05742644140 ** GROPP , DORA L BEGIN DATE 08/17/98 End Date 08/30/98 COMPANY 00010 DEPT# 430 Employee Signature FINAL TIMESHEET RUN DATE: 09/01/98 Page 01 Supervisor Approval Aw OF 02 gan 5 ! lores cooo/ot z <-- COST Ter | VAC HOL FLT | B-DAY 0 (045071 £9. 900) 0700 << <== CLASS 7 <-- MN. ST oF ST oT ST. oT ST —OT —j{—__1.0 | 60 — ele TOTALS ACCRUED LEAVE | 6.150 PER DIEM #915 — iS CHARGE MEALS #927 = a _SPLITS #911 __| pt isa el Employee ID ** 05742644140 ** FINAL TIMESHEET RUN DATE: 09/15/98 Page 01 OF 02 GROPP , DORA L 4 COMPANY 00010 DEPT# 430 Employee Signature * Supervisor Approval ii. ‘as BEGIN DATE 08/31/98 End Date 09/13/98 [ AUT OTALS RATE eee + ACCRUED LEAVE —$——MEALS #920 +— 6.150 Employee 1D ** 05742644140 ** GROPP , DORA L BEGIN DATE 08/31/98 End Date 09/13/98 NI # 0 COMPANY 00010 DEPT# 430 FINAL TIMESHEET RUN DATE: 09/15/98 Employee Signature * Supervisor Appr: Page 02 OF 02 oval Aun ——RATE — PER DIEM #915 SPLITS #911 ati I LOTTO TOTALS ACCRUED LEAVE 9.230 : aS : ACCOUNT WORK ORDER CHECK EMP # NAME MAJOR MIN CE CC NUMBER TASK DEPT HOURS AMOUNT DATE 210.41 Employee ID ** 04473027424 ** FINAL TIMESHEET RUN DATE: 09/02/98 Page 01 OF 01 BOYD , JESSIE M ae COMPANY 00010 DEPT# 900 Employee Signature s Supervisor Approval s BEGIN DATE 08/19/98 Dat 09/01/98 >’ Sete a 0/000/0 er 4 8620/000/0 0 0/000/0 0750/000/0 0 6/000/01 L __L L <-- ACCOUNT co searvasarad ee 690 <-- COST VAC WOL FLT B-pay | 7 essrorss7oo | £959008 2 26 " DATE {eee eee 700 00 760 09 2 $ ST OT s1__| WED. 08/19 a THU. 08/20 4.0 1.0 FRI. 08 1 0 SAT. SUN. 08/2 MON. 08, 0 TUE. — OTs) ACCRUED LEAVE +000 PER DIEM #915 CHARGE MEALS #927 SPLITS #911 Employee 10 ** 05746670131 ** FINAL TIMESHEET RUN DATE: 09/02/98 a Page 01 OF 0 HAYNTE , ANNALISA A COMPANY 00020 DEPT# 430 Employee Signature * Supervisor Approval ceN * BEGIN DATE 08/19/98 End Date 09/01/98 not | TOTALS + oa | ie — CHARGE MEALS #927 L — 1 4 SPLITS #911 INVOICE © =e RDM Ss IE NGINEERS NPE) 708-S466 JOB: 120376-06 TASK 6 AMNILCA APPLICATION INVOICE NUMBER: S4327 CONTRACT#: 95-208 P.0.#: INVOICE DATE : 17-sep-1998 BILL THROUGH DATE : 12-sep-1998 PAGE NUMBER: t CHUGACH ELECTRIC ASSOCIATION 5601 MINNESOTA DR. PO BOX 196300 ANCHORAGE. AK 99519-6300 ATTN:4S. DORA GROPP PROFESSIONAL SERVICES Hours Rate Amount Kaufman. Laurie 2.00 46.30 92.60 Kuemmerer. Uta K 1.00 56.22 56.22 McGraw. Ginaveve 1.00 56.22 56.22 Pollock. Randy 43.00 115.76 4977.68 | Valbert. Michael E 2.00 98.12 196.24 —— \ | TOTAL LABOR 49.00 5378.96 / 5378.96 .” » APPROVED FOR PAYMENT: | PUBLIC INVOLVEMENT $0.00 x_n LANDS/REGULATORY $0.00 gy x. “PROJECT MANAGER TE’ | 0 ll DIRECTOR, FD SERVITES DIVISION DATE BY: EXECUTIVE NIGR., TED NETWORK SERVICES DATE Released __ , BY. GE MANAGER DATE Ressived W.0. #_£9$%0F)_ CON #_GS- 208 ACCT. # 182d 000 0.2 2696 DATE 9-22-78 RECEIVED F ny accounting questions please contact Ginaveve McGrav | Sep 2 4Ft998 at (208) 788-0311. owt 28 we ACCOUNTING caer | ACCTS PAYARHE any other questions please contact Randy Pollock. ENie® TERMS: NET 30 DAYS FROM RECEIPT OF INVOICE. PAST DUE AMOUNT SUBJECT TO FINANCE CHARGE OF 112% PER MONTH. wu WIS MRE -s eer aes 3940 Glenbrook Drive P.O. Box 1066 Hailey, Idaho 83333 prelvEl (208) 788-2456 & 120376-05 TASK S EVALUATION PREPARATION INVOICE NUMBER: 54326 CONTRACT#: 95-208 P.0.#: INVOICE DATE 17-sep-1998 BILL THROUGH DATE : 12-sep-1998 PAGE NUMBER : 1 CHUGACH ELECTRIC ASSOCIATION S60L MINNESOTA DR. PO BOX 196300 ANCHORAGE. AK 99519-6300 ATTN:MS. DORA GROPP PROFESSIONAL SERVICES Houra Rate Amount Bryant. Vallace 14.00 56.22 787.08 Kueagerer. Uta K 6.00 56.22 337.32 ficGrau, Ginaveve 6.00 56.22 337.32 Pollock, Randy 30.00 115.76 3472.80 Valbert, Michael E 5.00 98.12 490.60 TOTAL LABOR 61.00 5425.12 5425.12 REIMBURSABLE EXPENSES Amount PC COMPUTER 7.00 PHONE & FAX 28.00 POSTAGE & SHIPPING 201.21 SUBCONTRACTOR LABOR 2961.45 SUBCONTRACTOR EXPENSE 220. 86 TOTAL EXPENSES 3418.52 3418.52 i Released__</| {| Det, | of nnn Y CURRENT CHARGES 8843.64 Resolved Sart APPROVED FOR PAYMENT BY: BY. , PUBLIC INVOLVEMENT $0.00 PROJECT MANAGER a LANDS/REGULATORY $0.00 BY: M/ (K DIRECTOR, TED SERVICES DIVISION DATE 5] Gl hs 94-12% ott ERSTE i a paw L Jo-2 | BY cg 9609) W.0. #_ EQSeet CON #_G5-20F ACCT. # 18624 00; m 27-' RECEIVED any accounting questions please contact Ginaveve sce eA ete = ATE 9-23-79 at (208)788-0311. : ‘ 49 ee any other questions please contact nyeREDa: i TERMS: NET 30 DAYS FROM RECEIPT OF INVOICE. PAST DUE AMOUNT SUBJECT TO FINANCE CHARGE OF 1%2% PER MONTH. Name (print): Dora L. Gropp Date: 9/17/98 ~ = | sence: Ore 2 P20 Period Covered: Sept. 8 thru Sept. 10, 1998 Page 1 Ot ap Chugach Business Expense Report ELECTRIC ASSOCIATION, INC. el Subtotals (Columns A- Total (make day entries) Work Order ae oun Direct billed | Employee | ™pensts Credit Card to Chugach Cash i See ote oo Discussions 18620/000/04/ 8 337.15 337.15 ie see ge a 17842 alae AEST AAA OT TT Bere cee ng TTT ATA Te age Fee eee TTT one Ae ft cee Te oT TAA RET NA rt i iii che AAA me Ee mG I ee 0.00 Total Expenses by Category HAT AT TTT ATTA TTA TAT Ta SF ee ee ‘attach travel authorization’ Balance Due DY employee C] check attached 2 RECEIVED oe mployee_[1 Company ( ) $570.20 ee er a ee D 0 < \ NTING hee fe NY neere PAYABLE L Date ac OM oa MIN ee 532 Mail original approved copy to Accounts Payable fa Southern Intertie Grant Fund Bank Account Activity Summary September, 1998 August Ending Balance Forward Total Deposits Total Withdrawals (Chugach invoice for July charges) Interest Earned Balance September 30, 1998 $286,391.77 $0.00 ($38,987.36) $998.93 $248,403.34 oO e aN Bern) of Anchorage Soules ce CHUGACH ELECTRI PO BOX 196300 ANCHORAGE AK 9 AIN BRANCH cO BOX 100720 ANCHORAGE AK 99510-0720 ooo © oo PAGE DATE: 09/30/98 aACcCcO C ASSOCIATION I 9519-6300 3 ali UNT: 41100033 30 DESCRIPTION RALANCE LAST STATEMENT ........---- RANSFER TO BUSINESS ACCOUNT 1106061 INTEREST NTEREST NTEREST INTEREST TNTEREST NTEREST 1NTEREST INTEREST NTEREST NTEREST INTEREST “NTEREST NTEREST INTEREST TNTEREST NTEREST -NTEREST INTEREST NTEREST NTEREST INTEREST “ALANCE THIS STATEMENT ........----. se * CON 38,987.36 33.72 33.73 33.73 33.74 134.96 33.70 33.71 33.71 100.79 33.36 33-637 33.37 33.38 99.43 32.68 32.68 32.68 32.69 98.08 32672 32.71 TINUED * * * 08/31/98 09/01/98 09/01/98 09/02/98 09/03/98 09/04/98 09/08/98 09/09/98 09/10/98 09/11/98 09/14/98 09/15/98 09/16/98 09/17/98 09/18/98 09/21/98 09/22/98 09/23/98 09/24/98 09/25/98 09/28/98 09/29/98 09/30/98 09/30/98 BALANCE 286,391.77 247,404.41 247,438.13 247,471.86 247,505.59 247,539.33 247,674.29 247,707.99 247,741.70 247,775.41 247,876.20 247,909.56 247,942.93 247,976.30 248,009.68 248,109.11 248,141.79 248,174.47 248,207.15 248,239.84 248,337.92 248,370.63 248,403.34 248,403.34 @ 000 00 PAGE: 2 DATE. 09/30/98 ACCOUNT: 41100033 DIMMER IE mr lil < we iets Member FDIC CHUGACH ELECTRIC ASSOCIATION I TOTAL CREDITS (21) 998.93 TOTAL DEBITS (1) 38,987.36 TAX ID NUMBER 92-0014224 INTEREST THIS STATEMENT 998.93 INTEREST PAID 1998 . 17,442.58 - END OF STATEMENT - SOUTHERN INTERTIE FUNDING REQUIREMENTS/CASH FLOW REV. 10/98 |. FUNDING REQUIREMENTS CONTRACT /ACTIVITY CONSULTANT AGENCIES RUS/Mangi USFWS USFS PROJECT MANAGEMENT TOTAL ll. CASH FLOW CONTRACT /ACTIVITY PHASE | AMENDMENT 6/98 TOTAL PROJECTED (CUMMULATIVE) TOTAL ACTUAL (CUMMULATIVE) St$sched.xIsNEPA BUDGET (2) COST ROUTE SELECTION (TO 6/96) $792,555 $0 $0 $0 $65,439 $857,994 COST $5,061,500 $720,000 $5,781,500 CHUGACH ELECTRIC ASSOCIATION COST COST CONTINGENCY TOTAL NEPATOEVAL NEPA-EIS TO (TO 10/98) ROD NEPA - EIS TO ROD (TO 05/00) (TO 05/00) $3,445,978 $730,000 $83,664 $5,052,197 $71,003 $150,000 $20,000 $241,003 $24,600 $30,000 $6,500 $61,100 $7,761 $5,000 $500 $13,261 $170,000 $270,000 $27,000 $532,439 $3,719,342 $1,185,000 $137,664 $5,900,000 CONTING. TOTAL 1995 1996 $38,500 $5,100,000 $196,275 $1,761,159 $80,000 $800,000 $118,500 $5,900,000 $196,275 $1,761,159 $196,275 $1,957,434 $56,420 $1,774,604 $56,420 $1,831,024 Page 1 == 1997 $2,007,375 $2,007,375 $3,964,809 $2,153,070 $3,984,094 1ST QTR. $190,000 $190,000 $108,972 10/19/98 SOUTHERN INTERTIE FUNDING REQUIREMENTS/CASH FL REV. 10/98 |. FUNDING REQUIREMEN CONTRACT /JACTIVITY CONSULTANT AGENCIES RUS/Mangi USFWS USFS PROJECT MANAGEMENT TOTAL ll. CASH FLOW CONTRACT /ACTIVITY PHASE | AMENDMENT 6/98 TOTAL PROJECTED (CUMMULATIVE) TOTAL ACTUAL (CUMMULATIVE) St$sched.xIsNEPA BUDGET (2) 1998 2ND QUTR. $200,000 $200,000 $239,727 CHUGACH ELECTRIC ASSOCIATION 3RD QUTR. $230,000 $230,000 $178,192 1998 4TH QUTR. TOTAL $170,000 $790,000 $170,000 $790,000 $4,754,809 $526,891 $4,510,985 Page 2 1ST QTR. $150,000 $150,000 1999 2ND QUTR. $195,191 $195,191 3RD QUTR. $300,000 $300,000 10/19/98 SOUTHERN INTERTIE FUNDING REQUIREMENTS/CASH FL REV. 10/98 |. FUNDING REQUIREMEN CONTRACT /ACTIVITY CONSULTANT AGENCIES RUS/Mangi USFWS USFS PROJECT MANAGEMENT TOTAL ll. CASH FLOW CONTRACT /ACTIVITY 4TH QUTR. PHASE | AMENDMENT 6/98 $300,000 TOTAL PROJECTED $300,000 (CUMMULATIVE) TOTAL ACTUAL (CUMMULATIVE) St$sched.xIsNEPA BUDGET (2) CHUGACH ELECTRIC ASSOCIATION 1999 2000 TOTAL 1ST QTR. 2ND QUTR. $345,191 $600,000 $120,000 $50,000 $945,191 $120,000 $50,000 $5,700,000 Page 3 3RD QUTR. $30,000 $30,000 2000 TOTAL $0 $200,000 4TH QUTR. $0 $200,000 $5,900,000 10/19/98 lil. SCHEDULE CHUGACH ELECTRIC ASSOCIATION ANCHORAGE - KENAI INTERTIE Mon 10/19/98 PHASE IB 1995 1996 1997 1998 1999 2000 ID | Task Name % Comp. Act. Cost Q2 | Q3 | Q4 | Q1 | Q2 | Q3 | Q4 | Q1 | Q2 | Q3 | Q4 | Q1 | Q2 | Q3 | Q4 | Q1 | Q2 | Q3 | Q4 | Q1 | Q2 | Q3 | Q4/Q1 1 | ENVIRONMENTAL & ENGINEERI 66% | $4,468,348.43 2 PROJECT MANAGEMENT 40% $160,011.90 3 ROUTE SELECTION STUDIE 100% $871,650.00 4 EVAL & PREL.ENGINEERIN 98%| $3,306,129.53 5 SCOPING 100% $375,997.34 6 INVENTORY 100% $680,396.25 z IMPACT/MITIGATION 100% $607,560.00 8 ALTERN.SELECTION 100% $335,392.00 9 EVAL (DRAFT EIS) 100% $783,056.00 10 ANILCA (FINAL EIS) 56% $29,747.20 11 STUDIES 100% $101,476.81 12 ENG.FIELD WORK 100% $202,645.44 13 PREL. ENGINEERING 100% $189,858.49 14 AGENCIES 63% $130,557.00 15 USFS 20%| $34,954.00 — 16 USFWS 100% 24,600.00 ° 5/31 17 RUS 96%| $71,003.00 Task summary a oled Up Progress Project: ANCHORAGE - KENAI INTE Pea cca Date: Mon 10/19/98 Progress Rolled Up Task = Milestone & Rolled Up Milestone © PH_IB.MPP Page 1 IV. ITEMS FOR APPROVAL Funding Increase for POWER Engineers/Dames & Moore CHUGACH ELECTRIC ASSOCIATION, INC. October 16, 1998 Anchorage Municipal Light and Power 1212 East First Avenue Anchorage, Alaska 99501 Attention: Ms. Meera Kohler, Utility Manager Subject: Southern Intertie, EIS Process — Chugach W.O. #E9590081 Additional Funding for the Environmental Analysis Dear Ms. Kohler: As part of their contract to perform the environmental assessment for the project our consultants, Power Engineers/Dames and Moore, have completed two drafts of the Environmental Analysis (EVAL). The final document is intended to form the basis for the Environmental Impact Statement (EIS) to be prepared by RUS’ consultant Mangi Environmental. The last draft (dated May 1998) incorporated changes to contents and format of the report as well as the maps requested by RUS and the cooperating agency, USFWS. We anticipated that its review would result in mostly “housekeeping” changes and that the final EVAL would be available by the end of July. During interagency meetings in June it became apparent, however, that the USFWS staff had not completed its review and that more time would be needed. When their comments became available at the end of July, major changes to the map presentations as well as the assessment approach were requested. New review meetings were scheduled in early September to reach agreement between the lead and cooperating federal agencies as to the formats to be used for the report and associated maps. PEI/Dames and Moore estimate the effort to comply with the agencies’ requests will add $118,193 to their expenses. Detailed documentation is included with PEI’s letter of October 13, 1998, which is enclosed with this letter. We agree with the consultants’ assessment that the EVAL preparation was severely impacted by the initial lack and subsequent repeated changes in direction from the federal agencies. We also feel very strongly that we need to produce an EVAL which addresses all agency concems and can be adopted into the EIS without changes. Therefore, it is recommended that the IPG approve the increase in funding to PEI/Dames and Moore’s contract as requested. 5601 Minnesota Drive * P.O. Box 196300 « Anchorage, Alaska 99519-6300 Phone 907-563-7494 © FAX 907-562-0027 Ms. Meera Kohler Page 2 October 16, 1998 Overall project funding will allow this expenditure without allocations, in addition to the $5,900,000 total for Phase I of the project as approved by AIDEA’s Board of Directors in June of this year. We will also remind USFWS and RUS of their obligations under the Memorandum of Understanding governing the NEPA process for the project, and request closer cooperation and regard for costs of changes. With this letter, I am requesting that an IPG meeting be scheduled at the earliest date to deal with this issue. Sincerely, CHUGACH ELECTRIC ASSOCIATION, INC. Eugene N. iomad A General Manager ENB/OUG jb C:\DATA\ANNALISA\WORDOCS\GROPP\ADD$1 098.DOC Enclosure c: AIDEA — Randy Simmons, Executive Director Lee Thibert Michael Massin W.O. E9590081, Sec.2.1.2.1 RF #) ECEIVE OLEF oawen.ios FR D OCT 14 1998 Dora L. Gropp, P.E. SMissio Manager, Transmission & Special Projects TRAN IN & Chugach Electric Association, Inc. SPECIAL PROJECT 5601 Minnesota Drive, Bldg. A D:.0. C&SVOO §/ Anchorage, AK 99518 ASE LZ. i F 0 Subject: 120376-05 Southern Intertie, Phase IB - Chugach Contract #95-208 Power Project 120376 - Additional Work Scope to Respond to USFWS Comments and Direction Dear Ms. Gropp, As you are aware, our recent communications and meetings with the US Fish and Wildlife Service (USFWS) on September 8-10, 1998 resulted in new direction from USFWS for the Final EVAL. Revision of the 2™ Draft EVAL to respond to USFWS direction will require substantial rework of the document, in order for the content and format of the Final EVAL to be acceptable to the USFWS. USFWS’s comments and direction centered around the biology sections of Chapters 3 and 4 of the 2" Draft EVAL, and in the formatting, content, and presentation of the maps. Substantial rework of the text will be required, consistent with the changes in the maps. The attached memo to me from Tim Tetherow outlines the background of Dames and Moore’s previous coordination and consultation with the USFWS over the past 2 years, and details the changes that are now required to respond to the current USFWS direction. A budget for the additional scope of work in the amount of $118,193 is attached. The additional funding would allow us to revise the EVAL document in compliance with USFWS direction. As you will recall, it was agreed at the September meetings that because of the substantial revisions to the document, we would submit the revised biology sections and maps to USFWS for a final review in November. They would only be reviewing those sections, not the entire document as before. If no further changes to the draft EVAL document are requested during this next review of the biology sections, this additional funding will allow us to complete the Final EVAL. It is important to realize that RUS intends to attach the Final EVAL to the EIS document as an appendix. As agreed to in the MOU between the agencies and the IPG, the EVAL is to serve as the basis for preparation of the EIS. The NEPA process is agency directed, and the EIS will address the issues deemed pertinent by the lead and cooperating agencies, in a manner acceptable to the agencies. As an appendix to the EIS, the Final EVAL must be consistent with the EIS. It is therefore our recommendation that the changes to the EVAL document directed by the USFWS at the September meetings be incorporated into the Final EVAL. DEN 26-708 (10/13/98) ukk POWER Engineers, Incorporated Lia CPM SERS ARERR a REN 3900 South Wadsworth Boulevard, Suite 700° Phone (303) 716-8900 Lakewood, CO 80235 Fax (303) 716-8980 Chugach Electric Association, Inc. October 13, 1998 Page 2 Summary of attachments included with this letter: 1. Budget Summary 2. Memorandum from Tim Tetherow, Dames & Moore, to Randy Pollock, Power Engineers dated October 13, 1998, including the following attachments: A. Table: Key Project Events Summary B. Notes: Changes in Direction from USFWS C. Memorandum: Impact Assessment Methodology D. Response from USFWS on Impact Methodology E. September 8-10, 1998 USFWS Meeting minutes e Table: Map Revisions e Notes: Biological Issues After you have had opportunity to review these materials, I will call you to see if further clarification or discussion is needed. ; Sincerely, 217 Randy Pollock, P.E. Sr. Project Manager RP/ukk Enclosures cc: Mike Walbert (PED) Tim Tetherow (D&M) File: 120376-05-55-00-30 DEN 26-708 (10/13/98) ukk Southern Intertie Project Budget Summary Task 5 Scope Additions to Respond to USFWS Comments and Direction | jal TTL | ___amerantnowe | Wi | tater [Papen] Sutoal [tater [Epes] tae [2% [sito omment Organization a eae | $12,502 | $5,610 | $18,112 | $362 sisa7 | | $18,474 tap Revisions Jf) ss0s77 | ace | sinonr | sani sao | 0.80 | ft ee IPG Meeting Attendance $1,830 $4,608 $2,829 $1,440 $4,269 $4,355 is Engineering Support & | Project Coordination ‘ $1,230 | $12,327 is 12327 Notes: 1. All of the work included as part of this proposed budget is either directly or indirectly related to the EVAL map and text revisions associated with the direction provided by the USFWS, resulting from the September 8-10, 1998 meetings. Please refer to the attached meeting minutes from those meetings and the Dames & Moore memo for more detailed information on the changes to the EVAL required. 2. Workscope for Dames & Moore is as described in the attached memo from Tim Tetherow to Randy Pollock dated October 6, 1998. 3. Work Item numbers correspond to the five tasks described in Tim Tetherow's memo, except PEI, which is Power Engineers work. 4. Workscope for Power Engineers (PEI) includes time for Randy Pollock to work with Dames & Moore to complete the required EVAL changes. Also included in the budget for Randy Pollock is one trip to Phoenix to review the changes to and assist in completion of the EVAL, and one trip to Anchorage to meet with the IPG (if required). | | | | | DEN 26-709 (10/13/98) 120376-05 Memorandum (Gag DAMES & MOORE fefteyeTA =A DAMES & MOORE GROUP COMPANY 7500 North Dreamy Draw Drive Suite 145 Phoenix, Arizona 85020 602 371 1110 Tel 602 861 7431 Fax Action Info File Randy Pollock, POWER 09203-009-050 Engineers, Inc. From Tim Tetherow, Dames & Moore, DEN Date 13 October 1998 Subject Southern Intertie Project - Budget Request for Additional Mapping and Required Supporting Analysis The purpose of this memo is to document the budget requirements to respond to requests by the US. Fish & Wildlife Service (FWS) for additional EVAL maps and analysis for the Southern Intertie project. Included in this memo is background information, requirements to revise the maps, estimated costs and attachments. Because of the complexity of these topics, the information provided in this memo is general, and is supported by five attachments that are referenced in the following sections. These attachments include: Key Project Events Summary Notes: Changes in Direction from FWS Memorandum: Impact Assessment Methodology Response from FWS on Impact Methodology September 8-10 Meeting Minutes ¢ Table: Map Revisions * Notes: Biological Issues MOA p Background Every effort has been taken to gain agency direction for and acceptance of the Southern Intertie environmental studies by the FWS from the project inception. Our goal has been to follow a process that would result in an efficient and cost-effective study. We recognized from the start that this would be a difficult task because of the location of the project, the amount of Federal lands involved, and the range of environmental issues. Our proposed participation and approach planned to involve FWS at each stage of the study (Tasks 1 through 5). Review of the project by the FWS began in early 1996 with their comments on environmental studies and mapping for the Phase 1 Alternative Corridor Selection studies. Following the Phase 1 Studies, the first step in the EVAL/EIS studies was to develop a scope of work and mapping requirements for each resource study (including geology and soils, water, marine, O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 aave Memorandum (GE October 13, 1998 Page 2 biology, land use, socioeconomic, visual and cultural resources). These were documented in the project Work Plan (June 1996). The scope of work for the EVAL and study results have been reviewed with the FWS over an extended period of time, beginning in November 1996. The approach and general scope of work was first presented at the Interagency Scoping meeting that was held in November 1996. At that time we summarized the proposed project, Phase 1 study results and issues, and a process that was planned to revolve around an Interdisciplinary Team (ID). We also requested informal direction from the FWS as an Interagency ID team member prior to the completion of a Memorandum of Understanding (MOU), which would establish formal agency direction for the studies. The work plan and study approaches were reviewed in detail by the FWS during the preparation of the MOU. The final work plan became an attachment of the MOU, which the FWS signed in June 1997. (See Attachment A, Key Project Events Summary). The purpose of the MOU is to “establish an understanding between the Lead Agency and Cooperating Agencies, and Applicant regarding the conditions and procedures to be followed in the preparation of the Environmental Impact Statement (EIS) through a joint Applicant/ Agency effort.” The responsibilities of the Lead and Cooperating Agencies include: providing direction the Applicant’s Consultant in the preparation of the EVAL; and ensuring that the DEIS is based on the Applicant’s EVAL. Over the eight-month period that the MOU was prepared, 18 drafts were produced, along with six versions of the work plan. Technical Direction from FWS In addition to the scoping process, we have been working with the FWS since November 1996 to develop of the work plan and MOU. We have also received technical input from the FWS on biological resource data, issues, study approaches, mapping results, assessment of impacts, and preparation of the EVAL drafts. A listing of general and technical project activities are listed on the attached Key Project Events. While the FWS has offered assistance through the series of meetings and comment reviews, there have also been changes in direction that have required revisions to the EVAL studies as the involve the KNWR. The following summarizes some of the selected points in the project when we were given specific direction from FWS for the preparation of the EVAL. (See Attachment B, meeting notes regarding Changes in Direction from FWS for additional detail): e FWS participated in an interagency biological impact assessment meeting in Girdwood with the Forest Service on April 22, 1997 to discuss biological impact issues and select the species for detailed studies. The selected species identified for detailed investigation included brown bear, black bear, moose, caribou, bald eagle, trumpeter swan, ducks and geese, beluga whale, and anadromous fish. Key impact issues included access, loss of habitat through clearing and bird strikes. The results of that meeting became the focus of the biological assessment studies for the EVAL. The general approach to the assessment was discussed, but not finalized. © D&M’s proposed impact assessment methodology was distributed for review on August 4, 1997. FWS reviewed and commented on the impact assessment approach and a nine-point impact scale on August 14, 1997 (see Attachments C and D for the Impact Assessment Methodology Memo and the Response from FWS on Impact Methodology). FWS O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 ears Memorandum (Ge October 13, 1998 Eat Page 3 direction on the assessment set the direction for the assessment of all environmental resource impacts along alternative routes. e The results of the biology assessment were presented to FWS at meetings in Anchorage and Soldotna on October 2 and 3, 1997, respectively. At those meetings, the maps, biology impact models, and impact results were presented to the FWS and Alaska State Division of Fish and Game (ADFG). Our approach for impacts to selected species had been to provide comprehensive mapping of wildlife habitat for the selected species within the study area on the Kenai Peninsula. We were informed that our mapping for brown bears, black bears, caribou and moose was not current with current KNWR understanding of those species. They informed us that neither the KNWR nor ADFG had any better comprehensive mapping for use in the EVAL. They directed us not to use the comprehensive mapping we had compiled from available sources for the four species mentioned above. For brown bears, they directed us to only use corridor level mapping that D&M had prepared. Direction at those meetings from the FWS and ADFG provided the basis of the biological studies that were documented in the first draft of the EVAL (November 1997). e FWS provided nine pages of comments on the first draft of the EVAL on February 9,1998. In the cover letter they stated that “In general, it appears that the document adequately identifies the range of issues associated with this proposed project, and that ample opportunity was provided for agency and community input. However, in the event that the IPG files a right-of-way application with the Service, the additional public process required under Title XI of the Alaska National Interest Lands Conservation Act may lead to the identification of additional issues.” Included was a request to analyze two additional species for detailed mapping and assessment - wolf and lynx. They also requested the inclusion of a new Interagency Brown Bear map. We responded to all of the FWS comments in the second draft of the EVAL. Meetings were held with the Kenai National Wildlife Refuge (KNWR) staff on December 10 and 11, 1997, and March 12, 1998 to discuss their comments and approaches prior to finalizing the second draft of the EVAL. e Over 40 pages of additional comments were submitted by FWS, including requests for extensive revisions in the assessment approach, additional maps and map changes. Two rounds of formal meetings have been held to discuss their comments (June 23 — 25 and September 8 — 10, 1998). These meetings were held with FWS, RUS and Mangi to discuss comments from the lead and cooperating agencies. FWS comments on the second draft of the EVAL (submitted in May 1998) were received on July 24, 1998, after the June meetings. The most recent meetings in September resulted in additional data requests that were not included in their July 24 comments. These included new direction for biological mapping, reformatting of map data, and new direction in the approach and display of impacts. A summary of the direction from FWS in the recent September meetings is provided below. September 1998 Meetings The meetings held in Soldotna this September represent the most recent direction from FWS. There were substantial requests for additional data and analyses by FWS in the recent September 1998 meetings that were not provided in their July 24 comments. This information was not previously available from FWS. They acknowledged that we were being “bounced around” in O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 eave Memorandum (GMs October 13, 1998 fm ~Page 4 terms of conflicting requests by the agency. Included were substantial changes to the cumulative impact assessment approach, and mapping content and format. The following are some of the key points to the meeting that will result in substantial changes to the EVAL (see attachment E for meeting minutes which include the table of Map Revisions, and the summary of Biological Resource Issues discussed at the meetings): = One of the more discouraging map change requests centers on the formatting of the data for maps on the Kenai Peninsula. The first draft of the EVAL combined the routes and data for alternatives on the Kenai Peninsula on one sheet for each resource topic. Environmental impacts were presented on separate maps for clarity purposes. When, Mangi Environmental Group (Mangi), RUS’s Third -party EIS contractor, requested separate small panel map sheets for the second draft of the EVAL, FWS did not object at the June meetings. The new maps were prepared to replace the large original maps. At that time, FWS concurred with Mangi’s comments on map changes. At the September 1998 meetings, FWS. stated emphatically that they did not like the small separate maps, and demanded the large sheet format that had been prepared for the first draft of the EVAL. = In addition, they requested that impacts be combined with the inventory maps. » Finally, they demanded that the nine-point impact scale be dropped, regardless of the direction from FWS last August. The format and scale for the impact maps is the same as those that we have prepared for EIS’s for several other transmission line projects. This is in response to NEPA requirements for a “rigorous analysis of alternatives.” = New map data were provided for wildlife habitat, the KNWR boundary, and ownership patterns within the refuge. Summary In summary, FWS has not tracked with the agreed-upon MOU and project work plan, which explicitly outlined a format, topics and schedule for participation in an interagency ID team during Tasks 1 through S. Instead, input has been inconsistent with the majority coming over the last few months, as summarized in the attached notes on biological impact from FWS. We are committed to complete a high-quality document that will satisfy FWS and provide the basis for the project EIS. We understand that additional funding for preparing the EVAL is a very sensitive issue. We have appreciated the project funding increases that the IPG has authorized so far, and have tried to be as effective as possible in the preparation of the EVAL studies and documents. It is regrettable that we need to make additional funding requests at this time. Map Requirements New maps, and maps requiring revisions are listed below (see attachment E, Map Revisions Table). An assumed level of effort to prepare each map is also provided (difficult — 3 to 4 days; average — 2 to 3 days; minor — 1 day): O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 aay C aol Memorandum October 13, 1998 Page 5 New Maps Subsistence - minor Cumulative Development — difficult Caribou Habitat and Impacts— average Moose Abundance Areas and impacts — average Brown Bear Habitat and Impacts — difficult Revised Maps Earth Resources and Impacts— average Vegetation Cover/Wetlands and General wildlife Habitat Inventory and Impacts — average Anchorage Area Vegetation Cover/Wetlands and General Wildlife Habitat Inventory and Impacts— minor Duck and Goose Concentration Areas and Impacts— difficult Eagle Habitat and Impacts— average Swan Nesting Areas and Impacts — average Wolf Abundance Areas and Impacts — average Lynx Abundance Areas and Impacts — average Anadromous Fish Streams and Beluga Whale Habitat and Impacts — average Jurisdiction and Ownership - minor Land Use and Impacts— minor Anchorage Area Land Use and Impacts— minor Recreation Use and Management Areas and Impacts — average Anchorage Area Views from Residences and Visual Impacts - minor Anchorage Area Recreation Facilities and Impacts— minor Views From Residences and Visual Impacts— average Anchorage area views from Recreation Areas and Travel Ways and Visual Impacts— minor Landscape Scenery and Impacts Anchorage Area Landscape Scenery and Impacts Construction Methods — minor Anchorage Area Construction Methods - minor Construction Season — minor Proposed Structure Type and Existing Utilities — minor Anchorage Area Proposed Structure Type and Existing Utilities - minor The preparation of these maps will require an estimated one and one-half GIS persons for a 5- week period (280 hours) in order to meet a November 2 draft completion date. Following FWS review, some clean-up time is expected (40 hours). In addition to the GIS staff involvement, biology and project management support will be required to create these new and revised maps. There also will be text additions required to incorporate the map results into the EVAL. O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 eavs Memorandum (GE October 13, 1998 Page 6 Tasks and Estimated Costs The additional work for completion of the EVAL, Task 5, has been organized into the following five subtasks: Comment organization — The FWS requested the attendance of D&M’s biology staff at the meetings held in Soldotna in September. The complexity and timing of the comments on the biology map comments required considerable preparation prior to the meetings, and on-going follow-up analysis to determine the proposed approach for each map. Changes to existing text, tables and analysis of impacts will be required as a result of the new maps and changes to existing maps. This has required ongoing meetings between project management, the project biologists and GIS staff. In addition to the biology maps, there has been additional effort to organize the approach to revising the other maps in the EVAL that will require changes, which includes every map in the document. EVAL Revisions — This task is necessary to make the EVAL text changes that correspond to the map changes. Data re-formatting and assessment refinements will be required, preparation of new tables to quantify impacts, and extensive changes to the content and format of the biology sections of Chapters 3 and 4. Map Revisions — This task will be to make the changes to the maps by the GIS staff. Finalize EVAL — The changes to the Biology sections of the EVAL will be reviewed by the FWS in November. We plan to finalize the EVAL by December 1998. However, this schedule is dependent on the timeliness and usability of the data to be supplied by FWS. This task is planned in response to the anticipated effort to finalize the maps and corresponding document changes. IPG Meeting - Attendance at IPG meeting to discuss status of EVAL. Estimated costs for the five subtasks 5a — Se are summarized below: ¢ 5a - Comment organization $18,112 ¢ 5b-EVAL Revisions $14,666 ¢ Sc - Map Revisions $40,041 ¢ 5d - Finalize EVAL $22,184 ¢ 5e-IPG Meeting $4,269 Total Estimated Costs $99,272 All of these tasks are either directly or indirectly related to the map revisions. Details will be provided in the supporting meeting notes. O:\PEOPLE\UKK\FOOTER LOG\26-713.DOC DEN 26-713 V. ITEMS FOR DISCUSSION None. Vi. ITEMS FOR INFORMATION 1. POWER Engineers’ Monthly Report Phase IB — Environmental Analysis, October 16, 1998 2. USFS Return of Funds, Letter of July 23, 1998 citation, ©, QRIDUWER OCT 19 1998 JIENGINEERS TRANSMISSION & SPECIAL PBQUEG To, 1998 Ms. Dora Gropp Chugach Electric Association 5601 Minnesota Drive, Building A Anchorage, AK 99518 Subject: POWER Project #120376 — EIS & Preliminary Engineering Chugach Contract #95-208 Monthly Status Report No. 26 For Period September 13 - October 10, 1998 Dear Dora: The following activities were performed during this invoicing period on the Environmental Impact Statement (EIS) and Preliminary Engineering portion of the Southern Intertie Project. Key Issues: e Completion of the Final EVAL. e Preparation of the ANILCA application. Invoice Period Overview: e Compilation of meeting minutes from the September 8-10 USFWS Meetings. e A detailed evaluation of requested USFWS changes to the maps and text was completed, along with an assessment of the impact on the EVAL schedule and budget. e Compilation of responses to Agency comments on the EVAL and completion of the comment tracking table. e Continuing preparation of comment responses and incorporation into the EVAL. e Reformatting of the maps in response to agency comments is continuing. Work Planned for the Next Invoice Period: e Incorporate Agency requested changes into the EVAL. e Revisions to maps consistent with USFWS changes. e Complete draft biology section of the EVAL for review by the USFWS in November. e Continue preparation of draft ANILCA application. HLY 23-459 POWER Engineers, Incorporated Os 3940 Glenbrook Dr. + P.O. Box 1066 Phone (208) 788-3456 Hailey, Idaho 83333 Fax (208) 788-2082 Chugach Electric Association October 16, 1998 Page 2 Schedule: At the meetings with USFWS on September 8-10, USFWS directed that significant changes in the maps and text be made for the final EVAL. The maps had previously been prepared based on prior reviews and discussions with RUS and USFWS, and the current direction from USFWS is different from agreements previously reached. A detailed summary of previous events and meetings held with the agencies to gain their direction for the preparation of the EVAL is summarized in my letter to you dated October 13, 1998. It was agreed at the September meetings that a revised biology section would be submitted to the USFWS for review in November, with final EVAL and ANILCA application completion in December. However, this schedule assumes that during the November review, the USFWS makes no further changes to the EVAL document or maps that are different from the agreements reached at the September meetings. Monthly Status Report Issues: Please refer to the Activities Summary attached for work completed and planned for each Task. Activity summaries are only included for Tasks 5 and 6, since all other tasks are completed. Project Overview: Although work is ongoing to complete the final EVAL, we.are not submitting an invoice this month because the funding for Task 5 - EVAL Preparation has been exhausted. The remaining budget indicated below is for Task 6 - ANILCA Application. Based on the added work requested by the USFWS at the September meetings, a request for added funding for Task 5 was submitted in my October 13 letter to you. Total Budget $3,327,786 Actual $ Expended (to date) $3,304,151 Actual Remaining Project Budget $ 23,635 Contract Amendment No. 10 for $678,069 (not included above), which provides for Power to furnish support to RUS and USFWS during the DEIS/EIS preparation and review periods, has been agreed upon and signed. Contract Amendment No. 10 is expected to be incorporated into the monthly status report after work covered under that amendment begins. Work under Contract Amendment No. 10 is not expected to begin until completion of the EVAL and submission of the ANILCA application. HLY 23-459 ROMER para cna Chugach Electric Association October 16, 1998 Page 3 Dora, should you have any questions about this report or any of the backup, please do not hesitate to contact Mike Walbert or me. Sincerely, POWER Engineers, Inc. Randy Pollock, P.E. Project Manager RP/Ik Enclosures ce: PROJECT TEAM HLY 23-459 GS powey SOUTHERN INTERTIE ROUTE SELECTION STUDY - PHASE 1 120376 PROJECT FINANCIAL SUMMARY OCTOMBER, 1998 INVOICE Project Task 1 Task 2 Task 3 Task 4 Task 5 Task 6 Task 7 Task 8 Task 9 Total Base Not to Exceed $351,050 $660,706 $584,010 $303,475 $402,570 $247,616 $101,480 $202,655 $189,861 $3,043,423 Budget CWG Contract $23,789 $18,885 $22,602 $32,866 $4,904 N/A N/A N/A N/A $103,046 Amendment No. 4 DFI Contract N/A N/A N/A N/A $45,000 N/A N/A N/A N/A $45,000 Amendment No. 5 DFI Contract N/A N/A N/A N/A $11,400 N/A N/A N/A N/A $11,400 Amendment No. 6 DFI Contract N/A N/A N/A N/A $3,502 N/A N/A N/A N/A $3,502 Amendment No. 7 DFI Contract N/A N/A N/A N/A $89,487 N/A N/A N/A N/A $89,487 Amendment No. 8 | Task 5&6 N/A N/A N/A N/A $194,150 | ($194,150) N/A N/A N/A $0 Reallocation * Contract N/A N/A N/A N/A $31,926 N/A N/A NIA N/A $31,926 Amendment No. 9 Total Not to Exceed $374,839 $679,591 $606,612 $336,341 $782,941 $53,466 $101,480 $202,655 $189,861 $3,327,786 Budget Actual Budget $374,839 $679,583 $606,540 $336,315 $782,922 $30,014 $101,476 $202,610 $189,852 $3,304,151 Expended Through Previous Invoice Current Invoice $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 Amount Actual Budget $374,839 $679,583 $606,540 $336,315 $782,922 $30,014 $101,476 $202,610 $189,852 $3,304,151 Expended Through Current Invoice Remaining $0 $8 $72 $26 $19 $23,452 $4 $45 $9 $23,635 Budget * Task 5 and 6 budget amounts reallocated per April 24, 1998 letter from Robert Martin to Randy Pollock. HLY 23-459 OCTOBER 1998 INVOICE ACTIVITIES SUMMARY TASK 5 - EVAL PREPARATION DESCRIPTION ACTIVITIES DURING CURRENT PERIOD AND PLANNED FOR NEXT 30 DAYS EVAL Preparation Compilation of meeting minutes from the September 8-10 USFWS Meetings. A detailed evaluation of requested USFWS changes to the maps and text was completed, along with an assessment of the impact on the EVAL schedule and budget. Compilation of responses to Agency comments on the EVAL and completion of the comment tracking table. Continuing preparation of comment responses and incorporation into the EVAL. Reformatting of the maps in response to Agency comments is continuing. Incorporate Agency requested changes into the EVAL. Revisions to maps consistent with USFWS changes. Complete draft biology section of the EVAL for review by the USFWS in November. Continue preparation of draft ANILCA application. HLY 23-459a Task 5 Activity Summary (continued) KEY ISSUES: Production and distribution of the Final EVAL. SCHEDULE: — Schedule for completing of this Task has been delayed as a result of USFWS comments. Completion of this Task is now anticipated in December. BUDGET: Contract amendments Nos. 4, 5, 6, 7, 8, 9 and the budget reallocation! for Tasks 5 and 6 are included in the budget ($402,570 + $4,904 + $45,000 + $11,400 + $3,502 + $89,487 + $194,150 + $31,926= $782,941). $ Budgeted $ Expended $ Remaining $782,941 782,922 19 SCOPE: The changes in scope resulting from the September 8-10 USFWS meetings have been discussed and negotiated. ' Tasks 5 and 6 budget amounts reallocated per April 24, 1998 letter from Robert Martin to Randy Pollock. HLY 23-459a OCTOBER 1998 INVOICE ACTIVITIES SUMMARY TASK 6 - ANILCA APPLICATION DESCRIPTION ACTIVITIES DURING CURRENT PERIOD AND PLANNED FOR NEXT 30 DAYS ANILCA Application e continue preparation of the draft ANILCA application. KEY ISSUES: Completion of the ANILCA application. SCHEDULE: Schedule for completing of this Task has been delayed as a result of USFWS comments on the EVAL document. BUDGET: The budget reallocation” for Tasks 5 and 6 is included in the budget ($247,616 - $194,150 = $53,466). $ Budgeted $ Expended $ Remaining 53,466 30,014 23,452 SCOPE: No outstanding issues. > Tasks 5 and 6 budget amounts reallocated per April 24, 1998 letter from Robert Martin to Randy Pollock. HLY 23-459a CHUGACH ELECTRIC ASSOCIATION, INC. Cikn ASSOCIATION, INC. September 28, 1998 Via Fax: 271-3992 U.S. Forest Service Chugach National Forest 3301 C Street, Suite 300 Anchorage, Alaska 99503 Attention: Mr. David Gibbons Subject: Southern Intertie Project, EIS Collection Agreement 96CC-10-04-023 Chugach Contract 96-265, W.O. E9590081 Dear Mr. Gibbons: We acknowledge receipt of your letter of July 23,1998 which terminates subject agreement. We also agree with the financial summary as presented and expect a refund in the amount of $27,154.93. We thank you for your and your staff's cooperation on this project. Sincerely. Lore Payf Dora L. Gropp, P-E. Manager, Transmission & Special Projects DHL;jb CADATA\ANNALISA\WORDOCS\GROPPIUSFSOUT1.DOC ic Bob Martin Alayne Switzer w.0. E9590081. Sec. 73, 4 RF 5601 Minnesota Drive * P.O. Box 196300 * Anchorage, Alaska 99519-6300 Phone 907-563-7494 © FAX 907-562-0027