AKIACHAK VILLAGE
Summary:
The existing overhead distribution is 2400/4160V, 3-phase,
4-wire. The substation consists of 3-100 kVA 240/120V -
4160/2400V, 3-phase, 3-wire transformers mounted on an
H-platform. Two generator buildings are provided with Halon fire
protection system and are in good condition. One 150 kW
generator and one 100 kW generator are located in the same
generator building; and the 300 kW generator is located in the
other generator building.
According to the PCE report, the Annual System Line Loss is 1.6%,
however, the only Line Loss recorded was in November, 1988 which
was 13.6%. It, therefore, appears that the meter readings for the
other months are incorrect.
Annual Fuel Consumption is 5.76 kWH/Gal.
High Average Load is 118.0 kW.
Low Average Load is 59.8 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
Cc mmunity: AKIACHAK Utility: AKIACHAK LIMITED
O ership: AKIACHAK LIMITED Contact:
Date: 06/19/89 Phone:
G-1 G-2 G=3 Operational? (Y/N): Y¥ y Y
Engine Make: DEUTZ WAUKESHA DEUTZ
Engine Model: BF6L413FRG BA6M816 F6L413FR
Engine RPM: 1800 1800 1800
Serial Number: 6728147 7212896 6213262 Horsepower: 201 402 125
Governor Type: BOSCH BOSCH BOSCH
Model Actuator: BOSCH#44C008007 BOSCH#552165808 BOSCH#92331806
Model Speed Control:
DC Voltage: 24 24 24
Unit Circuit Breaker: DISC SWITCH DISC SWITCH DISC SWITCH Type/Amp/Volt: SQ D/600/600 ZENITH UNKNOWN SQ D/600A/600V_
Year Installed: 1984 1984 1984 Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 2524.2 12,938.8 NO METER
Generator Make: KATO CAT KATO Generator Capacity (KW): 150 300 100
Generator Voltage: 240 240 240 Parallel Switchgear: N N N
KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N):
Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type: SANGAMD FM-S-L5-DS, CL 20
Catalog #:
Number of Stators: 2 MULTIPLIER=200
Demand? (Y/N): Y CT Ratio: 1000/5
Battery Charger/Type/Model: SENS/#2507-1,120V/24VDC
Individual Genset Meter: KATG#89487-1,93230,UNKNOWN (G3 Fuel Day Tank Type: SIMPLEX#STF-25
Pump #: : Motor #:
Fuel Day Tank Meter: KEN METRON: 8443.7 GAL Fire Protection Type/Operational?: HALON KIDDIE Original Contractor: WAKASAU ALASKA Spot Reading A Amps: 250 Spot Reading B Amps: 250 Spot Reading C Amps: 250 Spot Reading Volts: 220 Spot Reading Freq.: 60
Power (KW): 76 zI|<| > Notes: 1. HEAT EXCHANGER INSTALLED ON G-2. G-2 HAS 2 BEARINGS.
DAY TANK METER IS LOCATED OUTSIDE.
BOTH POWER HOUSES ARE MODULAR PACKAGES (VANS) WITH STEEL FLOORS.
G-1 WAS ON-LINE AT TIME OF INSPECTION. BWM eee
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c mmunity: AKIACHAK Utility: AKIACHAK LIMITED
Ow.2ership: AKIACHAK LIMITED Contact: Date: 06/19/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: v HOUSES
Multi Family: wy APARTMENTS Commercial: iY STORE
Public: ¥. SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 30,000 Number of Bulk Tanks: 3
Diked Containment? (Y/N): N NO MEMBRANE.SAND BAGS AROUND Visual Evidence of Leaks: NO. GOOD CONDITION
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 2400/4160V, 3-PHASE, 4-W
Underground: Combined:
Laid on Ground:
SUBSTATION TRANSFORMER
Capacity: 300 KVA
Pad:
Pole: 3 100 KVA ON "H" PLATFORM Voltage In/Out: 4160V/240V
UNMETERED STREET LIGHTS
Quantity: YES. APPROX 10
GENERAL NOTES
1. POWER HOUSES IN GOOD CONDITION. WELL MAINTAINED & LOG FORM IS USED.
2. BOTH POWER HOUSES ARE FIRE RESISTANT W/HALON FIRE PROTECTION
3. NEW AUTOMATIC OIL CHANGER OPERATIONAL 4. REMOTE RADIATOR IS AIR X-CHANGER #42HS
5. 100KW & 150KW ARE LOCATED IN THE SAME POWER HOUSE.
POWER HOUSE WITH MAIN
TRANSFORMER BANK : SERVICE DISCONNECT SWITCH
e ntiiiia ile: |" MAIN LINE 12.47 KV, 3-PHASE Oeae: BOSE =| 700 EW AD 4-WIRE WITH STREET LIGHT. 150 KW GENERATORS ARE LOCATED s oe Me LOCK OVERHEAD LINE IS IN EXCELLENT
CONDITION
ese 799977974 | |
|
POWER HOUSE WITH A 300 KW
GENERATOR AND MAIN SWITCH
GEAR LOCATED INSIDE
2 — POWER HOUSES (MODULE
PACKAGE) WITH HALON FIRE
PROTECTION SYSTEM
HOVa SNOTTYD OOO‘OT - TWOILYSA ?
SUNWL BZOVAOLS NING - 7%
a
4 BULK STORAGE TANK > al ites
| HORIZONTAL - 10,000 GALLON wd F + fi 1s < i
| 300 KW
TOTALIZING KWH METER. GENERATOR AND DAYTANK
SIMPLEX - 25 GAL.
SS > =e oor isa
TYPICAL STEP-DOWN TRANSFORMER, 100 KW DEUTZ GENERATOR WITH HOUSE SERVICE | GENERATOR PANEL (UNIT MOUNTED)
150 KW DEUTZ GENERATOR WITH GENERATOR PANEL (UNIT MOUNTED) MANUAL TRANSFER SWITCH AND HALON FIRE ALARM PANEL
AKIACHAK VILLAGE
Recommendations:
1.
2.
3.
5.
Install a new kWH station service meter at the main
generator building.
Install a dike around the daytank to contain any possible
fuel spills.
Test existing totalizing kWH meter for accuracy and install
an LED type instantanous kW meter.
Train the Operator/Utility manager on how to most
efficiently operate the power plant and in the use of plant
logs to enhance preventative maintenance, tracking parts
costs, fuel and oil consumption.
Trade a 300 kW generator set for a 150 kW generator set to
better match the load and increase fuel efficiency. The new
150 kW generator set should be provide with an electronic
governor. The Operator should run a 100 kW generator in
summer instead of a 150 kW generator.
Specify and install paralleling switchgear to allow load
transfer between units. Convert the governors on two
existing generators to electronic governors.
Install an hour meter on the 100 kW generator.
AKIACHAK VILLAGE
Cost Estimate:
1. Install a new KWH station service meter Labor (10 hours @ $25/hour) Materials (allow $150)
2. Install a sheet metal dike around
the daytank (typical of 3) Labor (4 hours @ $25/hour) Materials (allow $750)
Total of 3
3. Test existing totalizing kWH meter and install an instantaneous kWH meter Labor (16 hours @ $25/hour) Materials (allow $200) Contract (test existing meter)
4. Train the Operator/Utility Manager (8 hours @ $25/hour) Engineering Costs ° (24 hours @ $32.50/hour) Travel and Per Diem Costs AEA Administrative Costs
5. Remove 300 kW generator and its associated devices Labor (24 hours @ $25/hour) Trade 300 Waukasha generator for 150 kW
Waukasha generator, generator controller (unit mounted), etc. (Assume credit for
300 kW generator covers cost of new unit) Labor (60 hours @ $25/hour)
6. Specify and install switchgear: Materials (allow $25,500) Freight Labor (50 hours @10/hour) (88 hours @ $25/hour) Engineering (40 hours @ $32.5/hour)
7. %Install hour meter
Labor (16 hours @ $25/hour) Materials (allow $300)
SUBTOTAL | Contingency @ 20%
TOTAL COST ESTIMATE
$25,500.0 $1,000.0 $500.0 $2,200.0 $1,300.0
$400.0
$2,550.0
$650.0
$8,280.0
$2,100.0
$30,500.0
ATMAUTLUK VILLAGE
Summary:
The existing overhead distribution is 480/277V, 3-phase 4-wire
throughout the entire village. The power house is a metal
building with a wood floor, and a plywood liner to attach
panelboards and equipment. Upgrade wood floor to provide
one-hour construction in accordance with NFPA 37. There is one
125 kW, one 150 kW, and 230 kW generator.
According to the PCE report, the Annual System Line Loss is
7.3%. Low Average System Line Loss is 10.82%; and High Average
System Line Loss is 7.9%.
Annual Fuel Consumption is 4.21 kWH/Gal.
High Average Fuel Consumption is 10.26 kWH/Gal.
Low Average Fuel Consumption is 7.94 kWH/Gal.
High Average Load is 75.66 kW.
Low Average Load is 29.1 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
2 munity: ATMAUTLUAK Utility: ATMAUTLUAK JOINT UTILITIE dywership: Contact: { Date: 06/19/89 Phone:
G-1 G-2 G=3 Operational? (Y/N): Y¥ ¥. ¥ Engine Make: WHITE JOHN DEERE CUMMINGS Engine Model: 1990220 028000-329 NT855G Engine RPM: 1800 1800 1800 Serial Number: 87K19L N/A 55636 Horsepower: 167.5 201 356 Governor Type: ROOSA MASTER BOSCH COLMAN
Model Actuator: DM46294B2860 24607156 N56293 Model Speed Control:
DC Voltage: 24 24 24 Unit Circuit Breaker:
Type/Amp/Volt:
DISC SWITCH
SQ D/400A/480V DISC SWITCH DISC SWITCH SQ _D/400A7480V_ SQ D/400A/480V
Year Installed: ---- ---- 1981 Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 9651.2 23,156.8 7,384.1
Generator Make: KOHLER KOHLER KOHLER Generator Capacity (KW): 125 150 230
Generator Voltage: 277/480V 277/480V 277/480V Parallel Switchgear: N N N KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended: 3 Waste Heat Recovery Installed? (Y/N): N Waste Heat Recovery Operational? (Y/N): N
Powerhouse KWH Meter Type: WESTINGHOUSE FM-6S, CL 2
Catalog #: S280C097G08, 240V, 4W Y Number of Stators: 2 MULTIPLIER=200
Demand? (Y/N): Y CT Ratio: 400/75 Battery Charger/Type/Model: KOHLER #B269215, 120V/24VDC Individual Genset Meter: YES. KOHLER Fuel Day Tank Type: SIMPLEX 275 GAL. Pump #: Motor #: Fuel Day Tank Meter: Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
OUTSIDE-NOT CORRECTED NONE KINETIC ?
80
80
90
460* 60
53
Votes: 1.
2.
3.
As
MISSING EQUIPMENT COVER PLATES FOR G-1. NO STATION SERVICE KWH METER FOR POWER HOUSE. DAY TANK METER IS INSTALLED IN WRONG SIDE. G-3 ON-LINE AT TIME OF INSPECTION. * - LOW VOLTAGE READING
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
2 ammunity: ATMAUTLUAK Utility: ATMAUTLUAK JOINT UTILITIE dw.ership: Contact:
Date: 06/19/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: Y HOUSES
Multi Family: ¥ APPARTMENT Commercial: Y STORE
Public: ; SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 28,000
Number of Bulk Tanks: 3 Diked Containment? (Y/N): N Visual Evidence of Leaks: TANKS ARE RUSTY
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 480V, 3-PHASE, 4-W
Underground: N/A Combined: N/A
Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: N/A
Pad: oR
Pole: 56
Voltage In/Out: 480V/480V, 3-PHASE, 4-W
UNMETERED STREET LIGHTS
Quantity: APPROX 10
GENERAL NOTES
1. POWER HOUSE HAS WOODEN FLOOR WITH METAL BUILDING.
2. DEMAND LOAD CALCULATED: (1.73) (460) (83.33) = 66.4 KVA (53.1 KW)
DANGE.. HGH |
DOUBLE THROW TRANSFER SWITCHES
AND A TOTALIZATING KWH METER.
NEW TOTALIZING KWH METER.
NEW TOTALIZING KWH METER TO
BE REPLACED.
POWER HOUSE - WOOD FLOOR
WITH METAL CONSTRUCTION
OLD GENERATORS AND TRANSFOR-
MERS ARE ABANDONED AT SITE.
ALVIdUHAOD INAWdINOA TIVLSNI - MOLVYANES ZLIHM MM SZT DAYTANK - SIMPLEX - 275
GALLONS METER IS LOCATED
OUTSIDE.
O KW CUMMINS, 150 KW JOHN
DEERE AND 125 KW WHITE
GENERATORS WITH GENERATOR
PANELS (UNIT MOUNTED)
VNVUNU Nee
f TYPICAL STEP-DOWN TRANSFORMER, MAIN LINE 480 V, 3-PHASE, HOUSE SERVICE W/ STREET LIGHT. 4-WIRE. OVERHEAD LINE 1S IN
GOOD CONDITION.
ATMAUTLUK VILLAGE
Recommendations:
1. Equipment coverplates need to be installed.
2. Install diamond steel plate on the floor for a minimum of 12
inches around each engine in accordance with NFPA 37.
3. Remove existing totalizing kWH meter, and install a new
totalizing kWH meter and an LED type instantaneous kW meter.
4. Install a station service kWH meter to measure electrical
consumption for the power plant.
5. Train the operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
6. Install a dike around the daytank to contain any possible
fuel spills.
7. Trade a 230 kW Cummins generator set for a 75 kW Cummins
generator set to better match the summer load and increase
fuel efficiency. The new 75 kW generator set should be
provided with an electronic governor.
8. Specify and install paralleling switchgear to allow load
transfer between units. Convert the governors on two
existing generators to electronic governors.
9. Install a dike around the bulk storage tanks to contain any
possible fuel spills.
ATMAUTLUK VILLAGE
Cost Estimate:
1. Install equipment cover plates as the operator's duty at no cost. $0.0
2. Install diamond plate on powerhouse floor
Labor(40 hours @ $25/hour) $1,000.0 Materials (allow $750) $750.0
$1,750.0 3. Remove existing totalizing kWH meter, and install a new totalizing kWH meter and
an instantaneous LED kWH meter Labor (24 hours @ $25/hour) $600.0 Materials (allow $350) $350.0
$950.0
4. Install a station service kWh meter
Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
$400.0 5. Train the Operator/Utility Manager
(8 hours @ $25/hour) $200.0
Engineering Costs (24 hrs @ $32.5/hr) $780.0
Travel and Per Diem Costs $3,400.0
AEA Administrative Costs $3,900.0
6. Install a sheet metal around daytank Labor (4 hours @ $25/hour) $100.0 Materials (allow $750) $750.0
$850.0 7. Remove 230 kW generator & its associated devices. Trade 230 Cummins generator
for 75 kW Cummins generator, generator
controller (unit mounted), etc. (Assume credit for 230 kW generator covers cost of new unit) Labor (84 hrs @ $25/hr) $2,100.0
8. Specify and install switchgear: Materials & Freight $26,500.0 Labor (50 hours @ $10/hour) $500.0 (88 hours @ $25/hour) $2,200.0 Engineering (40 hours @ $32.5/hour) $1,300.0
$30,500.0
9. Install a dike around the bulk storage tanks Labor (40 hours @ $25/hour) $1,000.0 Materials (allow $5,000) $5,000.0
SUBTOTAL $50,830.0 Contingency @ 20% $10,166.0
TOTAL COST ESTIMATE $60,996.0
CLARK POINT VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire and of recent construction. The substation consists of
3-50 KVA 480/277V - 12.47 kV, 3-phase, 4-wire transformers
cluster mounted on a pole. There is one 50 kW, one 60 kW, and
one 100 kW generator. The generator building is new and has a
concrete floor.
The monthly PCE report for the year of 1988 only has the
available data of July, 1988. System Line Loss for this month is
0.4%; Fuel Consumption is 10.9 kWH/Gal; and Average Load is 13.88
kW.
The monthly PCE report for the year of 1989 is not available
because of poor bookkeeping by the Operator/Utility Manager.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
2 munity: CLARKS POINT Utility: CITY OF CLARKS POINT ),..ership: Contact: { Date: 06/21/89 Phone:
G-1 G-2 G=3 Operational? (Y/N): N 4 x Engine Make: PEKINS CAT CAT Engine Model: IBAE/19/781 3304-D1 3304-D1
Engine RPM: 1800 1800 1800
Serial Number: 3777E06B 83Z00881 83201173 Horsepower: 67 80.4 134 Governor Type: WOODWARD CAT CAT
Model Actuator: 8256-017
Model Speed Control: WOODWARD8290400 CAT CAT DC Voltage: 24 24 24
Unit Circuit Breaker: YES YES YES Type/Amp/Volt: GE/100A7600V___—~GE/125A7600V._—s«SQ_D/150A/600V Year Installed: 1988 1988 1988 Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 7,043.8 49.1 359.4
Generator Make: KATO CAT. CAT Generator Capacity (KW): 50 60 100 Generator Voltage: 480V 480V 480V Parallel Switchgear: N N N KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): N
\ Waste Heat Recovery Operational? (Y/N): N Powerhouse KWH Meter Type: GE FM-6S-VM-65-S, CL 10, 240V
Catalog #: 700X25G16
Number of Stators: 2 MULTIPLY # IS 80
Demand? (Y/N): Y CT Ratio: 400/75 Battery Charger/Type/Model: SENS#1652-17, 1714-39
Individual Genset Meter: VOLT/AMP/FREQ METER Fuel Day Tank Type: SIMPLEX 100 GAL.
Pump #: N/A Motor #: N/A
Fuel Day Tank Meter: KENT#86628972; 4,667.1 GAL Fire Protection Type/Operational?: NO; FIRE EXTINGUISHER ONLY Original Contractor: HUMPHREY Spot Reading A Amps: 28 Spot Reading B Amps: 28 Spot Reading C Amps: 28 Spot Reading Volts: 480 Spot Reading Freq.: 60.5
Power (KW): 19
Notes: 1. STATION SERVICE METER: GE#700X22G47, FM-14S-V-65-S,CL 100,240V 4W,Y 2. MISSING EQUIPMENT COVER PLATES FOR G-1. BATTERY VOLTAGE IS 12 VDC. 3. G-2 & G-3 ARE SHARING A BATTERY CHARGER. ITS VOLTAGE IS 24 VDC. 4. DEMAND LOAD CALCULATED: (1.73) (480) (28) = 23.3 KVA (18.6 KW)
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
CLARKS POINT
06/21/89
FACILITY INVENTORY
Cc munity: O-rership: ( Date:
Meter Status (Yes/No)
Single Family: Y Multi Family: N Commercial: Y Public: ¥
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: Number of Bulk Tanks: Diked Containment? (Y/N): Visual Evidence of Leaks:
Utility:
Contact:
Phone:
CITY OF CLARKS POINT
Notes
HOUSES
STORE SCHOOL
10,000
2 Y CONCRETE FLOOR & WALLS
NEWLY INSTALLED
POWER DISTRIBUTION SYSTEM
System Overhead: Underground: Combined: Laid on Ground:
Voltage/Phases
12.47KV, 3-PHASE, 4-WIRE
N/A
N/A
N/A
{ SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A
Pole: 3-50 KVA CLUSTER MOUNTED
Voltage In/Out: 480V/12.47KV, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX 15
GENERAL NOTES
1. POWER HOUSE IS NEW, HAS CONCRETE FLOOR, AND IS WELL INSULATED.
2. POWER HOUSE HAS EMERGENCY LIGHTS AND FIRE EXTINGUISHERS.
3. DAY TANK IS LOCATED IN ADJACENT ROOM. IT IS ON FLOOR
4. G-4 LOCATED IN OLD POWERHOUSE: ALLIS SHALMERS #AC2900, 1800 RPM,
75 KW, 208V/12.47KV, 3-PHASE, 4-WIRE. GOVERNOR TYPE: UNITED TECHNO-
LOGIES #AGB130D3; MODEL ACTUATOR: STANDDYNE #DBGFC-637-19JU.
HOURS: 5,331.1 5. G-2 WAS ON-LINE AT TIME OF INSPECTION.
ica) H & & vo = ° oO
I
joa)
u > ° =x
m% fea} = 9° Ay
= & = POWER HOUSE WITH STEP-UP TRANSFORMER BANK
= °
et HH vo D2 a H n = ° vo
a 9 ° =
G i= H =
ioe 5 ° ol fy
| i_i_/i x |
3 - 50 KVA —- 480/12.47 KV,
3-PHASE, 4-WIRE STEP-UP
TRANSFORMER
TYPICAL
3-PHASE, 4W WITH STREET LIGHT.
OVERHEAD LINE IS IN EXCELLENT
CONDITION.
DOWN GUY IS TOO CLOSE
POWER POLE
TO
SCHOOL IS APPROX- IMATELY 200 YARDS AWAY FROM POWER HOUSE. STEP DOWN TRANSFORMER BANK TO SCHOOL. STATION SERVICE KWH METER.
MOVE BOTTLES AND BARREL AWAY
TO MAINTAIN 3 FT CLEARANCE
IN FRONT OF PANEL
porn 2m
STEP-DOWN DRY TYPE TRANSFORMER | AND STATION SERVICE KWH METER. SIMPLEX DAYTANK - 100 GAL
BATTERY CHARGER FOR 60 KW
AND 100 KW CAT GENERATOR
io fj B i] =
x
=z 4 BH >
et a
100 KW CAT GENERATOR WITH 150A UNIT MOUNTED CIRCUIT BREAKER. 60 KW CAT GENERATOR WITH 125A UNIT MOUNTED CIRCUIT
a & = re & me QQ
‘50 KW PERK Ss WE
INS GENERATOR WITH 100A UNIT MOUNTED
CIRCUIT BREAKER. IT NEEDS TO
BE REPAIRED.
TOTALIZING KWH METER.
3 - 15 KVA, 208V/12.47, 3-PHASE, 4-WIRE STEP-UP TRANSFORMER a H H = wu mS = e H ie wo ee ina oO e wn a | > a fy o = ics fy > H 4 oS > vo joa) uw STORAGE TANKS DRAIN x = i] i oO rr] > a joa) un = ° = & a B wn a = «et
UALAW LNOHLIM ANVLIAVA 75 KW ALLIS CHALMERS GENERATOR
WITH UNIT MOUNTED GENERATOR
ABANDON CONDUIT AND WIRES
IN PLACE
CLARKS POINT VILLAGE
Recommendations:
1. Equipment coverplates need to be installed.
2. Train the Operator/Utility Manager on how to most efficiently
operate the power plant and in the use of plant logs to
enhance preventative maintenance, tracking parts costs, fuel
and oil consumption.
3. Install an LED type instantanous kW meter in the Operation
room.
4. Recommission the 50 kW Perkins generator set for summer
loads.
5. Specify and install paralleling switchgear to allow load
transfer between units. Convert all generators to electronic
governors.
6. Potential Waste Heat Recovery for School. School is
approximate 300 feet away from the power house.
CLARK POINT VILLAGE
Cost Estimate:
1.
2.
Install equipment cover plates as the operator's duty at no cost.
Train the Operator/Utility Manager (8 hours @ $25/hour) Engineering Costs (24 hours @ 32.50/hour)
Travel and Per Diem Costs AEA Administrative Costs
Install an instantaneous LED kWH meter Labor (10 hours @ $25/hour) $250.0 Materials (allow $200) $200.0
Recommission 50 kW generator set
Labor (32 hours @ $25/hour) $800.0 Materials (allow $1,000) $1,000.0
Specify and install switchgear:
Materials $25,500.0 Freight $1,000.0 Labor (50 hours @ $10/hour) $500.0 (88 hours @ $25/hour) $2,200.0 Engineering (40 hours @ $32.5/hour) $1,300.0
AEA Administrative Costs in new Wast Heat Recovery to be installed for School.
Install valve at fuel line of bulk
storage tank as the operator's duty
at no cost. $0.0 Material (allow $50) $50.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$0.0
$200.0
$780.0 $3,400.0 $3,900.0
$450.0
$1,800.0
$30,500.0
$5,000.0
$9,216.0
EKWOK VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-25 kVA 240/120 V - 12.4/7.2
kV, 3-phase, 3-wire transformers cluster mounted on a pole.
There are two generators. Each generator is housed in its own
generator building. Each generator building has wooden floor and
wall construction. Upgrade wood floor to provide one-hour
construction in accordance with NFPA 37. This power house is
only used in summer. The Southwest Regional School provides
power in winter. The school power house was locked at the time
of inspection.
Ekwok Village is not on the PCE Program; therefore, System Line
Loss, Fuel Consumption and High/Low Load Average cannot be
computed at this time.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c nmunity: EKWOK Utility: CITY OF EKWOK
Oy 2xrship: Contact:
‘ Date: 06/22/89 Phone:
G-1 G-2 G-3
Operational? (Y/N): Y¥ 4
Engine Make: DEUTZ DEUTZ
Engine Model: F6L912 F6L912
Engine RPM: 1800 1800
Serial Number: 9035037 9035037
Horsepower: 67 67 Governor Type: BOSCH BOSCH
Model Actuator: 15018591 15018591
Model Speed Control: BOSCH BOSCH
DC Voltage: 24 24
Unit Circuit Breaker: YES YES
Type/Amp/Volt: 2??/200A/240V 22?/200A/240V
Year Installed: N/A N/A
Last Major Overhaul (Hrs): NONE NONE
Current Hours: NONE NONE
Generator Make: KATO KATO
Generator Capacity (KW): 50 50
Generator Voltage: 120/208V 120/208V :
Parallel Switchgear: N N
KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N):
Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type:
Catalog #:
Number of Stators:
Demand? (Y/N):
CT Ratio:
Battery Charger/Type/Model:
Individual Genset Meter:
Fuel Day Tank Type:
Pump #:
Motor #:
Fuel Day Tank Meter:
Fire Protection Type/Operational?:
Original Contractor:
Spot Reading A Amps:
Spot Reading B Amps:
Spot Reading C Amps:
Spot Reading Volts:
Spot Reading Freq.:
Power (KW):
Notes:
STATION SERVICE METER:
DEMAND LOAD CALCULATED:
MAIN DISCONNECT SWITCH IS SQ D 200A, 240V. SANGAMO#36661904, (1.73) (215) (36.7) = THIS GENERATOR ONLY RUN FOR 3 MONTHS IN SUMMER.
2
N
N
GE FM-14S,V-65-S,CL 200,120V
700X22G46
2
N
NONE
NONE - UNIT ALTERNATOR
VOLT/AMP/FREQ METER
OUTSIDE 300 GAL
N/A
N/A
NEPTUNE#VLF2-8A1; 2,091 GAL
NONE >
60
20
30
215
60.5
ri
NO CT, 5 JAW METER.
FM-25, CL 200, 240V
13.7 KVA (OR 11 kW)
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
¢ mmunity: EKWOK Utility: CITY OF EKWOK Oy 3xrship: Contact:
‘ Date: 06/22/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: Y HOUSE Multi Family: N
Commercial: y STORE
Public: = SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 2,500
Number of Bulk Tanks: 1
Diked Containment? (Y/N): N_SET ON GROUND
Visual Evidence of Leaks: NO. IT IS IN GOOD SHAPE
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 12.47KV, 3-PHASE, 4-WIRE
Underground: N/A
Combined: N/A
Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 75 KVA
Pad: N/A
Pole: 3-25 KVA CLUSTER MOUNTED
Voltage In/Out: 240V/12.47KV, 3-PHASE
UNMETERED STREET LIGHTS
Quantity: APPROX 15
GENERAL NOTES
1. POWER HOUSE #2: STATION SERVICE METER: GE#720X70G2567, FM2S, CL 200
240V, 3W. DAY TANK: SIMPLEX#SFT-10, 25 GAL; PUMP:WESTINGHOUSE
316P566B, 1/3 HP. GENERATOR #2 IS STAND-BY.
2. POWER HOUSE #1 & 2 HAVE WOODEN FLOOR W/WOOD CONSTRUCTED. NO FIRE
ALARM PROTECTION.
3. CITY POWER HOUSE IS PRESENTLY LOCKED.
generator notes cont.: 5. FUEL METER INSTALLED ON GEN. SUPPLY LINE -
REINSTALL. 6. 50KW DEUTZ GEN. WAS ON-LINE AT TIME OF INSPECTION.
TYPICAL STEP-DOWN TRANSFORMER
TO CLINIC
TYPICAL MAIN LINE 12.47 KV,
3-PHASE, 4-WIRE. OVERHEAD
LINE IS IN EXCELLENT
CONDITION. VILLAGE CLINIC
TYPICAL STREET LIGHT THROUGH-
OUT THE VILLAGE
a4 25 KVA - 208V/12.47 KV, Gl POWER HOUSE - WOOD FLOOR
3-PHASE, 4-WIRE STEP—UP WITH WOOD CONSTRUCTION. 50 KW
TRANSFORMER BANK DEUTZ GENERATOR IS INSIDE.
IY 3NIT NOILOHdSNI JO SWIL LIVYANAD ZLInNea my os NO SYM ¥O
| 4 | i
200 AMP, 240 VAC, SQUARE D
MANUAL TRANSFER SWITCH.
INSTALL INCANDESCENT LIGHTS.
FUEL HOSE AND BATTERY CABLES
LAID ON FLOOR
G2 POWER HOUSE -
50 KW DEUTZ GENERATOR WAS
DOWN AT TIME OF INSPECTION
(ASNOH ‘USMOd 7-9 AGCISNI) MOLVYANATD ZLNAC MA OS NMOd SI eee 3 m4 aa
STATION SERVICE KWH METER
FOR G2 POWER HOUSE
TOTALIZING AND STATION SERVICE DAYTANK WITH METER
KWH METER FOR Gl POWER HOUSE.
EKWOK VILLAGE
Recommendations:
1. Install diamond plate on the floor for a minimum of 12 inches
around each engine in accordance with NFPA 37.
2. Train the operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
3. Install a 5 pound fire extinguisher in each generator
building.
4. Install incandescent bulbs in all powerhouses.
5. Existing daytank meter is not working. Replace it with a new
one to account for the exact amount of fuel the utility is
consuming.
6. Install an hour meter for generator 1.
7. New HUD Housing project is scheduled for 1990 construction.
These new houses will increase the electrical loads.
8. Trade the 50 kW Deutz generator set for a 25 kW Deutz
generator set to better match the summer loads and increase
fuel efficiency.
9. Loads are higher on Phase A than Phase B and C. Connect new
loads on Phase B and C to better balance the system.
EKWOK VILLAGE
Cost Estimate:
1. Install diamond plate on powerhouse floor Labor (40 hours @ $25/hour) $1,000.0 Materials (allow $750) $750.0
$1,750.0
2. Train the Operator/Utility Manager (8 hours @ $25/hour) $200.0 Engineering Costs (24 hrs @ $32.5/hr) $780.0 Travel and Per Diem Costs $3,400.0
AEA Administrative Costs $3,900.0
3. Install a 5 pound fire extinguisher in each powerhouse (total of 2) $200.0
4. Install 2 incandescent lights to each
powerhouse (total of 4). Materials Materials (allow $50) $50.0
5. Remove existing daytank and install a new one in its place. Labor (8 hrs @ $10/hr) $80.0 Materials $500.0 Engineering (8 hrs @ $32.5/hr) $260.0
$840.0
6. Install hour meter at G-1l. Labor (16 hrs @ $25/hr) $400.0 Materials (allow $300) $300.0
$700.0
7. Remove 50 kW generator and its associated devices Labor (24 hrs @ $25/hr) $600.0 Trade 50 kW Deutz generator for 25 kW
Deutz generator, generator controller (unit mounted), etc. (Assume credit for
50 kW generator covers cost of new unit) Labor (40 hrs @ $25/hr) $1,000.0
$1,600.0
SUBTOTAL $13,420.0 Contingency @ 20% $2,684.0
TOTAL COST ESTIMATE $16,104.0
IGIUGIG VILLAGE
Summary:
The existing overhead distribution is 480/277V, 3-phase 4-wire
throughout the entire village. The power house is a metal
building with a concrete floor. The building has plywood wall
liners for attaching electrical equipment.
According to the PCE report, the Annual System Line Loss is 9%.
Annual Fuel Consumption is 7.2 kWH/Gal.
High Average Load is 15.7 kW.
Low Average Load is 6 kW.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
c munity: IGIUGIG Utility: IGIUGIG VILLAGE COUNCIL oO i1ership: Contact: MR. DANIEL R. SALMON Date: 06/26/89 Phone: 533-3211
G-1 G-2 G-3 Operational? (Y/N): Y Y
Engine Make: JOHN DEERE JOHN DEERE
Engine Model: 3164DF-01 4276DF001
Engine RPM: 1800 1800
Serial Number: 594176T T704276D125091
Horsepower: 26.8 53.6
Governor Type: STANDYNEJD83010 STANDYNEJD83010
Model Speed Control: Model Actuator: WW#8256-013
WW#501-8209-029
WW#8256-013
WW#501-8209-029 DC Voltage: 24 24 Unit Circuit Breaker: NO NO
Type/Amp/Volt: N/A N/A
Year Installed: ---- ---- Last Major Overhaul (Hrs): NONE NONE
Current Hours: 1,749.7 7,276.6
Generator Make: LIMA LIMA Generator Capacity (KW): 20 40
Generator Voltage: 480V 480V Parallel Switchgear: Y Y KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N): Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type: KK] WESTINGHOUSE FM-16S,CL 200,
Catalog #: 70189001; 240V, 4W, Y
Number of Stators: 3 READING: 80705 KWH
Demand? (Y/N): Y¥ CT Ratio: NO
Battery Charger/Type/Model: NONE
Individual Genset Meter: VOLT/AMP/FREQ METER Fuel Day Tank Type: 3-OVAL 56 GAL. EACH Pump #: N/A Motor #: N/A Fuel Day Tank Meter: Fire Protection Type/Operational?: Original Contractor:
LIQUID CONTROLS 66,932 GAL
NO. ONLY HAS FIRE EXTINGUISHER UNKNOWN
Spot Reading A Amps: 20 Spot Reading B Amps: 12
Spot Reading C Amps: 26 Spot Reading Volts: 480 Spot Reading Freq.: 60.5
Power (KW): 13
Notes: 1. POWER HOUSE DOES NOT HAVE A STATION KWH SERVICE METER.
2. TOTALIZING KWH METER IS NOT WORKING PROPERLY.
3. DEMAND LOAD CALCULATED: (1.73) (480) (19.3) = 16.0 KVA (20 KW)
4. INCORRECT ENGINE ON-LINE FOR LOAD. SHOULD BE 20kW UNIT.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
mmunity: IGIUGIG Utility: IGIUGIG VILLAGE COUNCIL
.-nership: Contact: MR. DANIEL R. SALMON
{ Date: 06/26/89 Phone: 533-3211
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: y. HOUSES. SERVICE 120/240V,1ph
Multi Family: N Commercial: Y STORE
Public: ; SCHOOL, SERVICE 120/208V,3ph
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 25,000
Number of Bulk Tanks: 4 Diked Containment? (Y/N): Y TANK FARM W/SECURITY FENCE
Visual Evidence of Leaks: NO TANKS ARE IN GOOD SHAPE.
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 480V, 3-PHASE, 4-WIRE
Underground: N/A Combined: N/A Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: N/A
Pad: WR
Pole: N/A
Voltage In/Out: 480V/480V, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: NONE
GENERAL NOTES
1. POWER HOUSE HAS CONCRETE FLOOR W/FREE SPAN METAL BUILDING. PLYWOOD
WALLS. POWER HOUSE HAS EMERGENCY LIGHTS AND FIRE EXTINGUISHER.
2. THE OPERATOR USES PLANT LOG. IN GENERAL, THE POWER HOUSE IS IN FAIR
SHAPE.
3. 480V/240/120V STEP DOWN DRY-TYPE TRANSFORMERS TO PROVIDE POWER TO
HOUSES, CHURCH, ETC. THROUGHOUT THE ENTIRE VILLAGE.
TYPICAL MAIN LINE 480 VOLT, ate jum = YPOWER HOUSE — CONCRETE FLOOR,
3-PHASE, 4-WIRE. OVERHEAD ' : oe METAL BUILDING WITH 480 VOLT
LINE IS IN GOOD CONDITION : i MAIN LINE
“SHSNOH OL UWHWHYOASNVUL TWOIdAL AdAL AUC NMOG-daLs
OVERHEAD 480 VOLT, 3-PHASE
4-WIRE LINE THROUGHOUT
THE VILLAGE
3 VERTICAL AND 1 HORIZONTAL
20 KW AND 40 KW JOHN DEERE ; BULK STORAGE TANKS. TOTAL OF
GENERATORS WITH REMOTE z 25,000 GAL. TANKS ARE INSIDE
GENERATOR CONTROLLERS SECURITY FENCE.
Zuaaa NHOLS MA OF 4 MAIN SWITCHGEAR IS IN
EXCELLENT CONDITION. THE
TOTALIZING KWH METER TO BE
REPLACED WITH A NEW ONE.
HZLAYONOO NI SHNIT Tans - HOLVYANES \
FUEL DAY TANK METER
CE iin
IGIUGIG VILLAGE
Recommendations:
1. Install a station service kWH meter to measure electrical
power consumption for the power plant.
2. Existing totalizing kWH meter is apparently not working.
Replace it with a new one and also install an LED type
instantanous kW meter.
3. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative tracking parts costs, fuel and oil consumption.
4. Loads are higher on Phase C than Phase A and B. Rebalance
village loads by shifting some loads on Phase C to Phase B.
Reconfirm Phase balance when school starts in the Fall.
5. The Operator should operate the 20 kW John Deere generator in
the summer to better match the loads and increase fuel
efficiency.
IGIUGIG VILLAGE
Cost Estimate:
1. Install a station service kWH meter Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
$400.0
2. Remove existing totalizing kWH meter and install a new totalizing kWH meter and an instantaneous LED kWH meter Labor (24 hours @ $25/hour) $600.0 Materials (allow $350) $350.0
$950.0
3. Train the Operator (8 hours @ $25/hour) $200.0 Engineering Costs (24 hrs @ $32.5/hr) $780.0 Travel and Per Diem Costs $3,400.0 AEA Administrative Costs $3,900.0
4. Rebalance the loads in the village Labor(32 hours @ $25/hour) $800.0
SUBTOTAL $10,430.0 Contingency @ 20% $2,086.0
TOTAL COST ESTIMATE $12,516.0
ILLIAMNA VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-250 kVA, 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on an
H-platform. The power house is a metal building with a concrete
floor. There are 3-320 kW generators and 1-60 kW generator.
Generators and switchgear are near new and is well maintained.
Annual System Line Loss is 20.6% which is not acceptable.
Annual Fuel Consumption is 13.7 kWH/Gal.
High Average Load is 297.5 kW.
Low Average Load is 201 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
mmunity: ILIAMNA Utility: I-N-N ELECTRIC CO-OP
oy -2rship: Contact: JOHN W. JOHNSON
Date: 06/27/89 Phone: 571-1259
G-1 G-2 G-3
Operational? (Y/N): ¥ Y y
Engine Make: CAT CAT CAT
Engine Model: 3412-DT 3412-DT 3412-DT
Engine RPM: 1200 1200 1200
Serial Number: 81Z01200 81Z01298 81Z01008
Horsepower: 429 429 429
Governor Type: WOODWARD#2301 WOODWARD#2301 WOODWARD#2301
Model Actuator: WOODWARD#EG3P WOODWARD#EG3P WOODWARD#EG3P
Model Speed Control: WOODWARD#2301 WOODWARD#2301 WOODWARD#2301
DC Voltage: 24 24 24
Unit Circuit Breaker: NO NO NO
Type/Amp/Volt: N/A N/A N/A
Year Installed: 1982 1982 1982
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 20,930 3,909 22,726
Generator Make: KATO KATO KATO
Generator Capacity (KW): 320 320 320
Generator Voltage: 2400/4160 2400/4160 2400/4160
Parallel Switchgear: Y Y¥ Y
KWH Meter? (Y/N): Y¥ ¥ XY
OEM:
Hours/Day Attended: 8
Waste Heat Recovery Installed? (Y/N): Y
Waste Heat Recovery Operational? (Y/N): Y¥
Powerhouse KWH Meter Type: GE TYPE DSM-63, CL 10, 120V
Notes:
Catalog #:
Number of Stators:
Demand? (Y/N):
CT Ratio:
Battery Charger/Type/Model:
Individual Genset Meter:
Fuel Day Tank Type:
Pump #:
Motor #:
Fuel Day Tank Meter:
Fire Protection Type/Operational?:
Original Contractor:
Spot Reading A Amps:
Spot Reading B Amps:
Spot Reading C Amps:
Spot Reading Volts:
Spot Reading Freq.:
Power (KW):
1. DEMAND LOAD READING: 0.3 X 1200
2-STATORS, FM-14S, CL 200, 120V,
700X64G1 MULTIPLIER 1200
2
y.
200/5
MCS #MBC-7X-24V-20A-FL
VOLT/AMP/FREQ METER OVAL 275 GAL (TYP OF 4) N/A N/A LIQUID CONTROL#M5-44200-2 NO - FIRE EXTINGUISHERS ONLY BOB DRYDEN 100 100 110 2400 60 344
= 360 KW (OR 282 KVA @ 0.85 PF)
POWER HOUSE HAS A STATION SERVICE METER. WESTINGHOUSE #69181963,
4W, Y, TYPE D4S-8M. READING 116KW
3. WASTE HEAT RECOVERY FOR SCHOOL, OFFICE, AND CITY HALL.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
' mmunity: ILIAMNA Utility: I-N-N ELECTRIC CO-OP Or -2rship: Contact: JOHN W. JOHNSON
Date: 06/27/89 Phone: 571-1259
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: W. 120/240V,1-PHASE, 3-WIRE
Multi Family: ¥ 120/240V,3-PHASE, 3-WIRE
Commercial: Y 120/240V,1-PHASE, 3-WIRE
Public: ¥. 120/208V,3-PHASE, 4-WIRE
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 315000
Number of Bulk Tanks: 18
Diked Containment? (Y/N): N WILL INSTALL DIKES W/FENCE
Visual Evidence of Leaks: NO - EXCELLENT CONDITION
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 12.47KV, 3-PHASE 4-WIRE
Underground: N/A
Combined: N/A
\ Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 750 KVA
Pad: N/A
Pole: 3-250 KVA ON "H" PLATFORM
Voltage In/Out: 2400V/12.47KV, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: 2 150 W_HPS
GENERAL NOTES
1. POWER HOUSE IS VERY CLEAN. HAS CONCRETE FLOOR, EMERGENCY LIGHTS AND
FIRE EXTINGUISHERS.
2. SWITCHGEAR WAS INSTALLED IN 1982, MADE BY LLOYD CONTROLS, INC.
3. G-4: CAT #3508DI, 1200RPM, 600KW, 2400/4160V. GOVERNOR TYPE.
WOODWARD#2301, WOODWARD#EG310P MODEL ACTUATOR AND WOODWARD#2301
SPEED CONTROL. CURRENT HOURS=2,000. G-4 IS OPERATIONAL.
4. G-2 WAS ON-LINE DURING INSPECTION.
TYPICAL MAIN LINE 3-PHASE, 4-WIRE. OVERHEAD LINE IS IN EXCELLENT CONDITION. 12.47 KV, 4160 VOLT/208 VOLT
) To
4-WIRE STEP-DOWN
2 —- 50 KVA,
3-PHASE,
TRANSFORMER (PAD MOUNTED
POWER HOUSE SERVICE
A 4
1 m4 1 j 3 - 250 KVA, 4160 VOLT/12.47 KV STEP-UP TRANSFORMER BANK AND A SHUNT REACTOR. FUEL DAYTANK METER
MAIN SWITCHGEAR WITH TOTAL—
IZING KWH METER AND RECORDING
DEMAND METER
5
| = ecce___| ___4
TYPICAL GENERATOR SWITCHGEAR
KWH METER, INSTRUMENT TRANS-—
FORMERS, VOLT METER, AMP
METER, ETC. MAIN SWITCHGEAR IS NEAR NEW AND WELL MAINTAINED.
G-1: 320 KW CAT GENERATOR. G-2: 320 KW CAT GENERATOR
STANDBY IT WAS ON-LINE AT TIME OF
INSPECTION
ANDBY | STANDBY
ac 320 KW CAT GENERATOR. | G-4: 600 KW CAT GENERATOR.
|
UPLAW HLIM LNW -dInOa IWOINWHOSW YOd ANVLAVG 3 - 320 KW AND 1 - 600 KW CAT
GENERATORS ARE NEAR NEW AND
WELL MAINTAINED
GENERATORS ARE ON SKIDS AND SET ON CONCRETE FLOOR SHIUALLVA YOLVYANAS ANY USOUVHO AUMHLLIVA TWOIdAL
DAYTANK FOR GENERATOR
(TYPICAL OF 4) FIRE EXTINGUISHER AT EXIT DOOR
ILLIAMNA VILLAGE
Recommendations:
1. Install a dike around the bulk storage tanks and security
fence with gate.
2. 20.6% Annual System Line Loss is excessively high. Install a
recording kW Test meter to establish feeder losses.
3. Perform a system wide meter audit.
4. Monitor station service; consumption should decrease with
waste heat installation due to reduce radiator fan operation,
reduce powerhouse consumption, conservation, etc.
ILLIAMNA VILLAGE
Cost Estimate:
1. Install a dike, security fence and gate for bulk storage tanks. This job is
currently funded and, therefore, no cost estimate is provided.
Alaska Energy Authority should provide technical assistance to perform meter audit system wide to track feeder losses. Engineering Costs (160 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$0.0
$5,200.0 $7,100.0 $10,000.0
$22,300.0
$22,300.0 $4,460.0
$26,760.0
KOKHANOK BAY VILLAGE
Summary:
The existing overhead distribution is 480/277V, 3-phase 4-wire
throughout the entire village. The power house is a metal
building with a concrete floor. There is one 25 kW and one 35 kW
generator. This power house is only operated in the summer.
Winter power production is by the School District's generators
which incorporate Waste Heat Recovery for the school.
The monthly PCE report for the year of 1989 is not completed
because of poor bookkeeping by the Village or School Utility
manager, therefore, the percentage Annual System Line Loss, Fuel
Consumption, High and Low Average Load can not be computed.
Cc
o
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
munity: KOKHANOK BAY Utility: KOKHANOK VILLAGE COUNCIL iership: Contact: MS. MARY ANDREW Date: 06/27/89 Phone: 282-2210
G-1 G-2 G-3 Operational? (Y/N): Y¥ iv.
Engine Make: JOHN DEERE JOHN DEERE
Engine Model: 3164DF001 4219DF001
Engine RPM: 1800 1800
Serial Number: 1T03164D110807 T0429D112531
Horsepower: 33.5 47 Governor Type: #JDB-435CM3009 JDB-297A
Model Actuator: WW#8230013-1712 WW#8256017-1712
Model Speed Control: WW#8290-040-C WW#8290-040-C
DC Voltage: 24 24 Unit Circuit Breaker: NO NO
Type/Amp/Volt: N/A N/A
Year Installed: 1985 1985 Last Major Overhaul (Hrs): NONE NONE
Current Hours: 4,216.3 5,060.1
Generator Make: STAMFORD STAMFORD Generator Capacity (KW): 25 35 Generator Voltage: 480V 480V Parallel Switchgear: Y vi KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): N
Waste Heat Recovery Operational? (Y/N): N
Powerhouse KWH Meter Type: GE FM-14S V-65-S, CL 200, 240V Catalog #:
Number of Stators:
Demand? (Y/N): CT Ratio:
Battery Charger/Type/Model:
Individual Genset Meter:
Fuel Day Tank Type:
700X22G48 2__ MULTIPLIER IS UNKNOWN
N NONE
SENS#1506-104;1430-74 FC-12-6
VOLT/AMP/FREQ METER 2-OVAL 220 GAL EACH
Pump #: N/A Motor #: N/A
Fuel Day Tank Meter: TOKHEIM Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps:
Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.: Power (KW):
Votes: DEMAND LOAD CALCULATED: (1.73) (23
GOVERNOR TYPE IS STANDYNE FOR G-1
WOODWARD IS ABBREVIATED WW.
POWER HOUSE DOES NOT HAVE A STATI
NONE - FIRE EXTINGUISHERS ONLY
BOB DRYDEN
18
24
27
480
59.6
15
) (480) = 19.1 KVA (OR 15.3 KW) AND G-2.
ON SERVICE KWH METER.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
2 amunity: KOKHANOK BAY Utility: KOKHANOK VILLAGE COUNCIL )..aership: Contact: MS. MARY ANDREW
Date: 06/27/89 Phone: 282-2210
i FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: yi 120/240V, 1-PHASE, 3-WIRE
Multi Family: Y, 120/240V, 1-PHASE, 3-WIRE Commercial: Ng Public: i
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 20,000
Number of Bulk Tanks: 2 Diked Containment? (Y/N): Y Visual Evidence of Leaks: GOOD SHAPE
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 480V, 3-PHASE, 4-WIRE
Underground: N/A Combined: N/A Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: N/A Pad: N/A
Pole: N/A Voltage In/Out: 480V/480V, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: NONE
GENERAL NOTES
1. POWER HOUSE IS ONLY USED IN SUMMER TIME. THE ENTIRE VILLAGE
IS USING SCHOOL POWER HOUSE IN WINTER TIME. SCHOOL POWER HOUSE WAS
LOCKED DURING INSPECTION. 2. AEA TO PROVIDE ASSISTANCE IN DESIGNING NEW POWER DISTRIBUTION LINE
TO 4 HOUSES. 3. G-1 WAS ON-LINE DURING INSPECTION.
POWER HOUSE - METAL BUILDING,
AND CONCRETE FLOOR BULK STORAGE TANK WITH
SECURITY FENCE
2 — HORIZONTAL TANKS — ee : MAIN LINE 480V, 3-PHASE, 10,000 GALLONS EACH FOR ; ee. Ee DIT VILLAGE POWER HOUSE ; . 4-WIRE IS IN GOOD CONDITION
KOKHANOK WATER PLANT SASNOH OL YAWHOASNVUL AdAL AUT NMOG-daLS IWOIdAL 10,000 VERTICAL TANKS
GALLONS EACH FOR SCHOOL
2
KOKHANOK BAY VILLAGE
Recommendations:
1. Install a station service kWH meter to measure electrical
consumption for the power plant.
2. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
3. Loads are higher on Phase C than on Phase A or B. Rebalance
village loads by shifting some loads on Phase C to Phase A;
or connect new loads to Phase A. Reconfirm Phase balance when
School starts in Fall.
4. AEA to provide assistance for designing new power
distribution line and service to four houses.
5. Village Data is incomplete in the PCE Records. Train School
and/or Village Utility Manager to accurately record readings.
6. Install an LED type instantanous kW meter.
KOKHANOK BAY VILLAGE
Cost Estimate:
1. Install a station servicer kWH meter Labor (10 hours @ $25/hour) Materials (allow $150)
Train the Operator (8 hours @ $25/hour) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
Rebalance the loads in the village Labor (24 hrs @ $25/hr)
Design overhead distribution line 480/277 V, 3-phase, 4-wire system to feed four houses. Labor (80 hrs @ $25/hr) Materials (allow $17,000) AEA Administrative Costs
Train Village or School Utility
Manager on how to report accurate
readings for PCE (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
Install an instantaneous LED kWH meter Labor (10 hrs @ $25/hr) Materials (allow $250)
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$2,000.0 $17,000.0 $8,000.0
$400
$200
$780 $3,400 $3,900
$600
$27,000
$200
$780 $3,400 $3,900
$45,060 $9,012
$54,072
-0
-0
0 0 0
-0
-0
-0
0
-0
0
-0
0
-0
KOLIGANEK VILLAGE
(SCHOOL POWER HOUSE)
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-25 kVA, 240/120 V -
12.47/7.2 kV, 3-phase, 3-wire transformers cluster mounted on a
pole. The School power house is a metal building with a concrete
floor. There are two 90 kW and one 100 kW generators.
The Village power house consists of a single 60 kW Onan generator
in a new wood frame building. Normally, the village supplies all
power in the summer months and the School supplies power in the
winter. Waste Heat Recovery is connected to the school power
house.
The monthly PCE report for the year of 1989 is not completed
because of poor bookkeeping by the School and/or Village Utility
Manager. Therefore, the percentage of Annual Line Loss, Fuel
Consumption, High and Low Average Load can not be computed.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
Number of Stators:
Demand? (Y/N): CT Ratio:
Battery Charger/Type/Model: Individual Genset Meter: Fuel Day Tank Type:
Pump #: Motor #:
Fuel Day Tank Meter: Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
Notes:
c mmunity: KOLIGANEK Utility: KOLIGANEK VILLAGE COUNCIL
C nership: KOLIGANEK CITY Contact:
Date: 06/22/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): Y¥ yi Y
Engine Make: CAT ALLIS CHALMERS JOHN DEERE
Engine Model: 3304 670T 1215P
Engine RPM: 1800 1800 1800
Serial Number: 44BH1296 70-20462 190442
Horsepower: 120.6 120.6 134
Governor Type: UNITED TECH UNITED TECH(UT) STANDYNE
Model Actuator: AGB-130-D3 AGB-130-D3 DM43335
Model Speed Control: UT#ECD675111 UT#ECD67—-5111 UT#ECD13005
DC Voltage: 24 24 24
Unit Circuit Breaker: NO NO NO
Type/Amp/Volt: N/A N/A N/A
Year Installed: ---- ——— ==
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 524.5 528.6 5,488.1
Generator Make: CAT CAT STAMFORD
Generator Capacity (KW): 90 90 100
Generator Voltage: 240V 240V 240V Parallel Switchgear: N N N KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): Y
Waste Heat Recovery Operational? (Y/N): Y
Powerhouse KWH Meter Type: WESTINGHOUSE FM-9S,D5S-3E
Catalog #: 78-588-175; CL 20,120V 3 MULTIPLY # IS 60
Yi 30075 SENS#1902-36, 1902-33, 1902-38 VOLT/AMP/FREQ METER VOLT/AMP/FREQ METER OVAL 275 GAL BROOK MOTOR #X201445, 1HP WORTHINGTON #8GAU NO NO. FIRE EXTINGUISHER ONLY BOB DRYDEN 30 50 50 220 59.8 13
1. TOTAL DEMAND LOAD WAS 15.7 KW (19.6 KVA) DURING THE INSPECTION.
(SCHOOL LOAD ONLY, REMODEL IN PROGRESS)
2. DEMAND LOAD CALCULATED: (1.73) (220) (43.3) = 16.5 KVA (13.2 KW)
3. POWER HOUSE DOES NOT HAVE A STATION SERVICE KWH METER.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c amunity: KOLIGANEK Utility: KOLIGANEK VILLAGE COUNCIL Oo ership: KOLIGANEK CITY Contact: Date: 06/22/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: Y HOUSES Multi Family: Y Commercial: XY STORE
Public: Y SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 25,000
Number of Bulk Tanks: 3 Diked Containment? (Y/N): Y Visual Evidence of Leaks: NO. TANK FARM W/SECURITY FENCE
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 12.47KV, 3-PHASE, 4-WIRE
Underground: N/A Combined: N/A
Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 75 KVA Pad: N/A
Pole: 3-25 KVA CLUSTER MOUNTED
Voltage In/Out: 208V/12.47KV, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX 12
GENERAL NOTES
1. CONDUCTORS NOT SAGGED PROPERLY. THEY MAY TOUCH DURING HIGH WINDS,
CAUSING A BLACK OUT. ‘ 2. POWER HOUSE WAS VERY CLEAN, CONCRETE FLOOR W/WOOD CONSTRUCTION.
3. POWER HOUSE DOES NOT HAVE EMERGENCY LIGHTS.
4. G-4 (CITY): CUMMINS #4BT-39, 1800RPM, 60KW, 208/12.47KV, 3-PHASE,
4-WIRE. CURRENT HOURS: 548.2. WAS ON-LINE DURING INSPECTION. CITY
POWER HOUSE DOES NOT HAVE TOTALIZING AND STATION SERVICE METER.
5. G-3 WAS ON-LINE DURING INSPECTION.
ily vit 240 VOLT/12.47 KV,
3-PHASE STEP-UP TRANSFORMER
25 KVA,
BANK.
3- “ONIGTING WALAW a (2 wn a 4YOOTT ALHYONOD - ASNOH UAMOd Gh oO (Zea MHOW é HHA > by PHOR sO by] p ~- fea) YHW “NHO “_ ia “Fa WMHOR Seay HW rH Hho meoH BHeH A, Heh alah Suv zTU
dan wenaooe oe r
& TOTALIZING KWH METER.
90 KW CAT GENERATOR WITH UNIT
MOUNTED VOLT/AMP/FREQ METERS
AND BATTERY CHARGER. STANDBY.
= 2
I aN ss Se & 7 - > iti: Sette Leone | (100 KW JOHN DEERE GENERATOR i
< . 7 n | WITH UNIT MOUNTED GENERATOR
CONTROLLER. IT WAS ON-LINE
AT TIME OF INSPECTION.
ee Ty
POWER HOUSE - TERMINATION
PULL-BOX.
STEMS RE
DAYTANK (TYPICAL OF 3) —- ONE
FOR EACH GENERATOR.
VILLAGE KWH METER. OIL STAIN
ON CONCRETE FLOOR.
BULK STORAGE TANKS FOR VILLAGE
AND SCHOOL. LOCATED INSIDE
SECURITY FENCE WITH PAD LOCK.
120/240 VOLT, 1-PHASE, 3-WIRE Ss : . 4 - BULK STORAGE TANKS,
ORricE. ge ca eleg aa Bet 15,000 GALLONS EACH (SCHOOL)
VILLAGE POWER HOUSE - WOOD
FLOOR AND WOOD CONSTRUCTION.
TOTALIZING AND STATION SERVICE
KWH METER. 60 KW CUNININS GENER ATOR
WITH ETAL DRIP PAW Arno
Vol T/(4mp/PREQ suETE., ZT WHS
ON HNE AT TIME PF INSPECTION
FIRE EXTINGUISHER AT EXIT
DOOR. NEED EMERGENCY LIGHT.
EXTERIOR DAYTANK - 100
GALLONS DAYTANK DOES NOT HAVE
FUEL METER.
TYPICAL STEP-DOWN OIL FILLED
TRANSFORMER TO HOUSE.
KOLIGANEK VILLAGE
(SCHOOL POWER HOUSE)
Recommendations:
1.
2.
Install a station service kWH meter to measure electrical
consumption for the power plant.
Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
Loads are higher on Phase B and C than Phase A. Rebalance
village loads by shifting some loads on Phase B and C to
Phase A; or connect new loads to Phase A. Reconfirm Phase
balance when School starts in the fall.
AEA to provide assistance for designing new power
distribution line and service to four houses.
Village data is incomplete in the PCE records. Train School
and/or Village Utility Manager to report accurate readings.
Install an LED type instantaneous kW meter.
Equipment coverplates need to be installed.
Replace all Native Poles to taller poles in accordance with
NESC requirements. Existing conductors, cross arms, pin
insulators, etc. appeared to be in good condition, and they
can be reused.
Install emergency lights in the School and Village power
houses.
KOLIGANEK VILLAGE (SCHOOL POWERHOUSE)
Cost Estimate:
1. Install a station servicer kWH meter Labor (10 hours @ $25/hour) Materials (allow $150)
2. Train the Operator (8 hours @ $25/hour) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs
AEA Administrative Costs
3. Rebalance the loads in the village Labor (24 hrs @ $25/hr)
4. Install daytank meter Labor (4 hours @ $10/hr)
Materials (allow $500) Engineering Costs (8hrs @ $32.5/hr)
5. Train Village or School Utility
Manager on how to report accurate readings for PCE (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr) Travel and Per Diem Costs AEA Administrative Costs
6. Install an instantaneous LED kWH meter Labor (10 hrs @ $25/hr) Materials (allow $250)
7. Install equipment coverplates as the
operator's duty at no cost.
8. Remove all distribution poles, install new poles in their places and reconnect
as before. Labor (60 hrs @ $10/hr) (100 hrs @ $25/hr) Engineering (40 hrs @ $32.5/hr) Materials 25 poles @ $300/pole
9. Install one emergency light in each powerhouse. Labor (4 hrs @ $25/hr) Materials (allow $500)
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$400.0
$200.0 $780.0 $3,400.0 $3,900.0
$600.0
$800.0
$200.0 $780.0 $3,400.0 $3,900.0
$500.0
$0.0
$11,900.0
$6,272.0
$37,632.0
KONGIGANAK VILLAGE
Summary:
The existing overhead distribution system is 12.47/7.2 kV,
3-phase, 4-wire. The substation consists of 3-50 kVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on an
H-platform. There are four generators. Each generator is housed
in its own building. There is one 75 kW and three 150 kW
generators. The generator buildings are metal buildings with
wood floors. Upgrade the wood floors to provide one-hour
construction in accordance with NFPA 37.
Annual System Line Loss is 28.5%, which is not acceptable.
Annual Fuel Consumption is 6.77 kWH/Gal.
High Average Load is 78.5 kW.
Low Average Load is 41.15 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
¢ mmunity: KONGIGANAK Utility: PUVURNAQ POWER CO.
Oo ership: Contact:
Date: 06/20/89 Phone:
G-1 G-2 G-3
Operational? (Y/N): Y¥ Y Y
Engine Make: JOHN DEERE JOHN DEERE DEUTZ
Engine Model: 6466AF-00 6466AF-00 BF6L413FRC
Engine RPM: 1800 1800 1800
Serial Number: RG6466A333363 RG218380 6930667
Horsepower: 201 201 201
Governor Type: WOODWARD WOODWARD
Model Actuator: B8256-007 B8256-007
Model Speed Control: BOSCH#84200454 BOSCH#84200454 BOSCH
DC Voltage: 24 24 24
Unit Circuit Breaker: NO NO NO
Type/Amp/Volt: N/A N/A N/A
Year Installed: 1982 1982 1984
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 16,893.7 15,800.7 5,319.8
Generator Make: CONDEC CONDEC KATO
Generator Capacity (KW): 150 150 150
Generator Voltage: 480V 480V 480V
Parallel Switchgear: Y ¥ N
KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): N
Waste Heat Recovery Operational? (Y/N): N
Powerhouse KWH Meter Type: SANGAMO TYPE S40DS, CL 20
Catalog #:
Number of Stators:
Demand? (Y/N):
CT Ratio:
Battery Charger/Type/Model:
Individual Genset Meter:
75778443 277V, 4W ¥ NOT MARKED MULTIPLY # IS 80 ¥ 400/5 SENS G3: VOLT/AMP/FREQ METER
Fuel Day Tank Type: 50 GAL
Pump #: HAIGHT PMP DIV # 3D
Motor #: UNKNOWN
Fuel Day Tank Meter: NO
Fire Protection Type/Operational?: NO
Original Contractor: KINETIC ENERGY
Spot Reading A Amps: 120
Spot Reading B Amps: 145
Spot Reading C Amps: 110
Spot Reading Volts: 470
Spot Reading Freq.: 59
Power (KW): 81
Notes: 1.
2. DEMAND LOAD CALCULATED:
POWER HOUSE DOES NOT HAVE A STATION SERVICE METER. (1.73) (470) (125)=101.7 KVA (OR 81.4 KW)
3. DEMAND LOAD READING AT TIME OF INSPECTION WAS (1.69) (80)=135.2 KW.
UNABLE TO DETERMINE LAST TIME DEMAND SCALE RESET.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c nmmunity: KONGIGANAK Utility: PUVURNAQ POWER CO. G -ership: Contact:
Date: 06/20/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: Y HOUSES Multi Family: Ni APARTMENTS
Commercial: y STORE
Public: XY SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 60,000
Number of Bulk Tanks: 4
Diked Containment? (Y/N): N
Visual Evidence of Leaks: NO
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 12.47KV, 3-PHASE, 4-W
Underground: N/A
Combined: N/A
Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A
Pole: 3-50 KVA ON "H" PLATFORM
Voltage In/Out: 480V/12.47KV, 3-PHASE, 4-W
UNMETERED STREET LIGHTS
Quantity: APPROX 12
GENERAL NOTES
1. POWER HOUSE IS MODULE PACKAGE BY CRAIG TAYLOR (TYPICAL OF 3)
2. MODULE PACKAGE POWER HOUSE HAS WOODEN FLOOR W/FIRE EXTINGUISHER.
3. G3 IS LOCATED INSIDE A WOODEN CONSTRUCTION POWER HOUSE. IT HAS A
WOODEN FLOOR W/FIRE EXTINGUISHER.
4. CITY OF KONGIGANAK IS PLANNING TO BUY A 250 KW OR 300 KW GENERATOR.
5. CITY OF KONGIGANAK IS GOING TO INSTALL A NEW METER FOR THE
LAUNDROMAT BY THE END OF THIS MONTH.
6. DAY TANK FOR G1 & G2 IS 50 GAL EACH.
iandidiidanannene = WOOD CONSTRUCTION POWER HOUSE WITH 150 KW DEUTZ GENERATOR. IT WAS ON-LINE AT TIME OF INSPECTION.
“WOOD CONSTRUCTION POWER HOUSE
*MAIN LINES ARE SAGGING TOO
LOW TO THE GROUND.
*MAIN LINES ARE LAID ON ROOF.
"AX UAWNAOASNWUL “SSWHd-€ Lb°TI/LIOA O8% —- WAN OS - € dn-daLs HuaIM-b
3 - 150 KW MODULAR PACKAGE POWER HOUSE BY GRAIG TAYLOR
:
MAIN SWITCHGEAR IS
AND WELL MAINTAINED.
NEAR NEW
CTLs
LOCATED INSIDE MODULAR POWER
HOUSE #2
al tn
150 KW JOHN DEERE GENERATOR
AND TRAMONT DAYTANK ARE
LOCATED INSIDE MODULAR POWER
HOUSE #2. STANDBY
MODULAR POWER HOUSE #2-
WOOD FLOOR, METAL BUILDING
WITH FIRE EXTINGUISHER
50 GAL FUEL DAYTANK DOES NOT
HAVE FUEL DAYTANK METER.
TYPICAL.
Se A! OL On es NOILIGNOO INS'TTHOXA NI SI SANIT QVHHYAAO *AMIM-p “ASWHd~€ i) - ‘AN Lb°@L ANIT NIVW ‘IVOIdAL fm ip ne ! Hypa AOE ond H mn ma WH: kum AZ+* { 4 | foo SES ie a Sa oO f£ nono aH A, STANDBY 150 KW JOHN DEERE GENERATOR
IS LOCATED INSIDE MODULAR
POWER HOUSE #1.
50 GAL FUEL DAYTANK AND FIRE EXTINGUISHER
4 BULK STORAGE TANKS - 15,000 GALLONS EACH. APPROXIMATELY
600 FT. AWAY FROM POWER HOUSE.
POTENTIAL WASTE HEAT FOR
SCHOOL.
KONGIGANAK VILLAGE
Recommendations:
1.
10.
dd.
12.
Loads are higher on Phase B than Phase A or C. Rebalance
village loads by shifting some loads on Phase B to Phase C,
or connect the Laundromat load to Phase Cc. Confirm Phase
balance when School starts in the fall.
Install diamond steel plate on the floor for a minimum of 12
inches around each engine in accordance with NFPA 37.
Install a fuel meter on the daytank to accurately account for
the fuel the utility is consuming. Typical of four daytanks.
Install a station service kWH meter to measure electrical
consumption for the power plant. Also install an LED type
instantanous kW meter.
Train the operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
Install a dike around the daytank to contain any possible
fuel spills (typical of 4).
Install a kWH meter to measure electrical consumption of the
Laundromat.
28.5% Annual System Line Loss is excessively high. A system
wide meter audit is required to accurately establish feeder
losses.
The existing output feeders of the 150 kW Deutz generator is
presently too close to the ground and touches the power house
roof. Reinstall the feeder to meet the vertical clearance
required in accordance with NESC 234.
Repair leaks on the 150 kW Deutz generator.
There is a potential to install waste heat recovery for the
school as it is across from the power house.
Install a dike around the bulk storage tanks to contain any
possible fuel spills.
KONGIGANAK VILLAGE
Cost Estimate:
1. Rebalance loads. Labor (32 hrs @ $25/hr)
2. Install diamond plates (40 hrs @ $25/hr) $1,000.0 Materials (allow $3,000) $3,000.0
$160.0 $2,000.0 $260.0
3. Install daytank meters. (16 hrs @ $10/hr)
Materials (allow $2,000) Engineering Costs (8 hrs @ $32.5/hr)
4. Install a station service kWH & and an instantaneous LED KWH meter. (20 hrs @ $25/hr) $500.0
Materials (allow $350) $350.0
5. Train the Operator (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
6. Install a sheet metal dike around the daytank (typical of 4). Labor(16 hrs @ $25/hr) $400.0
Materials (allow $2,000) $2,000.0
7. %Install kWH meter for the Laundromat Labor (10 hrs @ $25/hr) $250.0
Materials (allow $150) $150.0
8. Alaska Energy Authority to provide technical assistance
$800.0
$4,000.0
$2,420.0
$850.0 $200.0 $780.0 $3,400.0 $3,900.0
$2,400.0
$400.0
to perform meter audit system wide to track feeder losses. Engineering Costs (100 hrs @ $32.5/hr) $3,250.0
Travel and Per Diem Costs $4,500.0
AEA Administrative Costs $7,000.0
9. Reinstall output feeders to meet NESC 234 Labor (40 hrs @ $25/hr) $1,000.0 Engineering Costs (24 hrs @ $32.5/hr) $780.0
10. Repair/replace leaking front. This is a maintenance item and, therefore, no cost estimate has been provided.
11. AEA Administrative Costs in new Waste Heat Recovery to be installed for School.
12. Install a dike around the bulk storage tanks Labor (40 hrs @ $25/hr) $1,000.0
Materials (allow $5,000) $5,000.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$14,750.0
$1,780.0
$0.0
$5,000.0
$6,000.0
$56,016.0
KWIGILLINOK VILLAGE
Summary:
The existing overhead distribution is 12.47/77.2 kV, 3-phase,
4-wire. The substation consists of 3-50 kVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on an
H-platforn. The power house is a wood building with a wood
floor. A new power house is under construction. It is
approximately half way between the existing power house and
school. There is one 100 kW, one 125 kW and one 150 kW
generator. All generators are in good condition.
According to the PCE Report, the Annual System Line Loss is
29.6%, which is not acceptable.
Annual Fuel Consumption is 11.1 kWH/Gal.
High Average Load is 82.8 kW.
Low Average Load is 44.6 kW.
¢ mmunity:
¢ nership:
Notes:
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
KWIGILLINGOK Utility: KWIG POWER CO.
Contact:
Date: 06/20/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): ¥ YX XY
Engine Make: DEUTZ DEUTZ JOHN DEERE
Engine Model: BF6L413FRC F6L413FR 6466AF-00 Engine RPM: 1800 1800 1800
Serial Number: 6941188 6213344 RG6466A247498
Horsepower: 201 134 167.5
Governor Type: BOSCH BOSCH BOSCH
Model Actuator: PESSP110A720RV_ RQ900AB1054L 82922217
Model Speed Control: WW _#8271-344 WW_#8271-344 WW_#8271-344
DC Voltage: 24 24 24 Unit Circuit Breaker: NO YES NO Type/Amp/Volt: N/A WH/125A/7600V._‘~‘N/A
Year Installed: 1987 1981 1984
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 6,612.9 19,144.8 22,831.2
Generator Make: KATO KATO CONDEC
Generator Capacity (KW): 150 100 Lao
Generator Voltage: 480V 480V 480V
Parallel Switchgear: Y XY Y
KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N): Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type: Catalog #: Number of Stators:
Demand? (Y/N): CT Ratio:
Battery Charger/Type/Model: Individual Genset Meter: Fuel Day Tank Type: Pump #: Motor #:
Fuel Day Tank Meter:
Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
DEMAND LOAD CALCULATED: PRWNP eee
2
N
N
WESTINGHOUSE D4B-3FM, CL 20
280C210G01 120V, 4W, Y
3 MULTIPLIER # IS 288
> 40075 SENS#1416-04, 1502-51, 1416-05 VOLT/AMP/FREQ METER
VOLT/AMP/FREQ METER 300 GAL (OUTSIDE) GREAT PLAIN IND. #1100 DATA IS NOT AVAILABLE YES — OUTSIDE PYROTRONIC SYSTEM 3 KINETIC ENERGY
POWER HOUSE HAS NO STATION SERVICE KWH METER. (1.73) (470) (81.7) SWITCHGEAR IS MADE CONTROLLER POWER COMPANY. . EQUIPMENT COVER PLATES ARE MISSING FOR ALL GENERATORS.
= 66.5KVA (53.3KW)
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
¢ munity: KWIGILLINGOK Utility: KWIG POWER CO.
Ownership: Contact:
Date: 06/20/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: y HOUSES Multi Family: Y APPARTMENTS Commercial: ry STORE Public: iv SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 30,000 Number of Bulk Tanks: 3 Diked Containment? (Y/N): N Visual Evidence of Leaks: GOOD SHAPE
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 12.47KV, 3-PHASE, 4-W
Underground: N/A Combined: N/A Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A Pole: 3-50 KVA ON "H" PLATFORM
Voltage In/Out: 480V/12.47KV, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX 11
GENERAL NOTES
1. POWER HOUSE HAS WOODEN FLOOR W/WOOD CONSTRUCTION.
2. POWER HOUSE HAS EMERGENCY LIGHTS.
3. MAIN 480V FEED IS APPROX. 6'-0" ABOVE GROUND.
4. MAIN BREAKER IS 600 AF, 400 AT.
5. A NEW POWER HOUSE WAS UNDER CONSTRUCTION APPROX HALF WAY BETWEEN
EXISTING PLANT AND SCHOOL. UNDERGROUND 3-PHASE MAIN LINES.
6. G-2 WAS ON-LINE DURING TIME OF INSPECTION.
3 - 50 KVA - 480V/12.47 KV,
3-PHASE, 4-WIRE STEP-UP
TRANSFORMER
3-PHASE, 4-WIRE WITH STREET
LIGHT. OVERHEAD LINE IS IN
EXCELLENT CONDITION.
a ALO Ra. ¥ { ABOVE GROUND POWER HOUSE — WOOD CONSTRUC- : TION. NEW POWER HOUSE IS UNDER i Se CONSTRUCITON, APPROXIMATELY a HALF WAY BETWEEN OLD POWER | / MATELY |7)/—~6" HOUSE AND SCHOOL.
AONZOMAWNA LHSIT aNW ZILLOG INSNY “TaNVd TOMLNOOD WUVIY ZYIaA NOTH
HS N 2
HH 2a Qa n A= ZH mA Q SG tf} @ He by ww
= H H ~
PY
H oO a 3 — HORIZONTAL BULK STORAGE
E TANKS - 10,000 GALLONS EACH. NO DIKED CONTAINMENT.
EXTERIOR FUEL DAYTANK — 300 GALLONS
=.
— 100 KW DEUTZ GENERATOR WAS ON-LINE AT TIME OF INSPECTION. EQUIPMENT COVER PLATE TO BE WAS DOWN AT TIME OF INSPEC | TION. TYPICAL BATTERY INSTALLED. NSTALL CHARGER (WALL MOUNTED)
E GENERATOR 150 KW DEUTZ GENERATOR WAS
DOWN AT TIME OF INSPECTION FUEL DAYTANK METER
MAIN SWITCHGEAR IS IN
EXCELLENT CONDITION =
Le <a 12 “~ Ba
KWIGILLINOK VILLAGE
Recommendations:
1. Equipment coverplates need to be installed.
2. Repair fuel leaks.
3. Install an LED type instantaneous LED kW meter.
4. Install a station service kWH meter to measure electrical
consumption for the power plant.
5. Train the operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
6. Install a dike around the new daytanks to contain any
possible fuel spills.
7. Loads are higher on Phase C than Phase A or B. Rebalance
village loads by shifting some loads on Phase C to Phase A.
Reconfirm Phase balance when school starts in Fall/Winter.
8. 29.6% Annual System Line Loss is excessively high. A system
wide meter audit is required to accurately establish feeder
losses.
KWIGILLINOK VILLAGE
Cost Estimate:
1.
2.
Install equipment cover plates as the
operator's duty at no cost.
Repair/replace fuel drippings. This is a maintenance item and, therefore, no cost estimate has been provided.
Install an instantaneous LED kWH meter Labor (10 hrs @ $25/hr) $250.0
Materials (allow $200) $200.0
Install a station service kWH meter Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
Train the Operator (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs
AEA Administrative Costs
Install dike around new daytanks to be included
in new power house's budget and, therefore, no cost estimate is provided.
Rebalance loads in the village Labor (24 hours @ $25/hour)
AEA to provide technical assistance to perform meter audit system wide to track feeder losses. Engineering Costs (100 hrs @ $32.5/hr) $3,250.0
Travel and Per Diem Costs $4,500.0
AEA Adiminstrative Costs $7,000.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$0.0
$0.0
$450.0
$400.0
$200.0 $780.0 $3,400.0 $3,900.0
$0.0
400.0
$14,750.0
$4,776.0
LEVELLOCK VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-50 kKVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers cluster mounted on the
pole. The power house is a metal building with a concrete
floor. There is one 50 kW and two 130 kW generators. All
generators are in good condition.
Village Data is incomplete in the PCE Records. Therefore, the
percentage of Annual System Line Loss can not be computed.
Annual Fuel Consumption is 9.2 kWH/Gal.
High Average Load is 62.2 kW.
Low Average Load is 20 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
Cc nmmunity: LEVELOCK Utility: LEVELOCK ELECTRIC CO-OP
o.aership: Contact: MR. JOHN APOKEDAK
( Date: 06/26/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): Y¥ YX N Engine Make: CAT CAT JOHN DEERE
Engine Model: 3306-PC 3306-DT 4276TFO1L
Engine RPM: 1800 1800 1800
Serial Number: 66D47976 85Z00622 695875T
Horsepower: 174.3 174.3 67.0
Governor Type: WOODWARD WW#8256-008 ROSAMASTER#DM44
Model Actuator: WOODWARD WOODWARD WW#8256-108
Model Speed Control: WOODWARD#1701 WOODWARD#1701 UNKNOWN
DC Voltage: 24 24 24
Unit Circuit Breaker: YES YES YES Type/Amp/Volt: GE/225A/600V__—s«- GE/7225A/7600V GE/90A/600V___
Year Installed: ---- a sooe
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 2,038.6 1,576.8 9,019.8
Generator Make: KATO KATO CONDEC
Generator Capacity (KW): 130 130 50
Generator Voltage: 480V 480V 480V
Parallel Switchgear: Y y M2 KWH Meter? (Y/N): ¥ ae ee |S Yor ie aT Y
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N):
Waste Heat Recovery Operational? (Y/N): Powerhouse KWH Meter Type: GE TYPE VM-64S, 120V Catalog #: 706X16G5
Number of Stators: 3
Demand? (Y/N): Y¥
CT Ratio: 300/5 MULTIPLIER: 240
Battery Charger/Type/Model: LAMARCHE#A-46-6-24V-Al (TYP)
Individual Genset Meter: VOLT/AMP/FREQ METER
Fuel Day Tank Type: 3-OVAL 275 GAL EACH
Pump #: N/A Motor #: N/A
Fuel Day Tank Meter: LIQUID CONTROLS #MS44200-2
Fire Protection Type/Operational?: NONE ONLY FIRE EXTINGUISHERS
Original Contractor: BOB DRYDEN Spot Reading A Amps: 20 Spot Reading B Amps: 20 Spot Reading C Amps: 25 Spot Reading Volts: 490 Spot Reading Freq.: 60
Power (KW): 15 KK] Notes: 1. DEMAND LOAD CALCULATED: (1.73) (490) (21.7) = 18.4 KVA (25 KW) 2. P.F. LAG=75% 3. DEMAND LOAD READING: (0.05) (120)=14.4 KW 4. DEMAND READING WAS 28 KW ON TOTALIZING METER
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c amunity: LEVELOCK Utility: LEVELOCK ELECTRIC CO-OP 9,.1rership: Contact: MR. JOHN APOKEDAK
( Date: 06/26/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: Y SERVICE 120/240V,1-PHASE, 3W
Multi Family: Y SERVICE 120/240V,1-PHASE, 3W
Commercial: Y SERVICE 120/208V,3-PHASE, 4W
Public: XY SERVICE 120/208V,3-PHASE, 4W
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 30,000 Number of Bulk Tanks: 3 Diked Containment? (Y/N): Y WITHOUT MEMBRANE Visual Evidence of Leaks: GOOD CONDITION
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 12.47KV, 3-PHASE, 4-WIRE
Underground: N/A Combined: WR
N/A Laid on Ground:
SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A
Pole: 3-50 KVA CLUSTER MOUNTED
Voltage In/Out: 480V/12.47KV, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX. 12
GENERAL NOTES
1. G3 HAD BEEN DOWN SINCE MAY '89 WITH BAD WATER PUMP.
2. POWER HOUSE HAS CONCRETE FLOOR W/METAL CONSTRUCTION. INSULATION NOT
COMPLETE.
3. POWER HOUSE HAS EMERGENCY LIGHTS AND FIRE EXTINGUISHERS.
OPERATOR USES DAILY LOG.
POWER HOUSE WASTE HEAT RECOVERY IS PROVIDED FOR SCHOOL.
G-2 WAS ON-LINE DURING INSPECTION.
POWER HOUSE DOES NOT HAVE A STATION SERVICE KWH METER. NOS oe ee
3 - 50 KVA, 480V/12.47 KV,
3-PHASE, 4-WIRE STEP-UP
TRANSFORMER BANK
TYPICAL MAIN LINE 12.47 kv,
3-PHASE, 4-WIRE. OVERHEAD
LINE IS IN EXCELLENT CONDITION
TYPICAL STEP-DOWN TRANSFORMER,
HOUSE SERVICE
EXHAUST STACKS AND MUFFLERS. CONCRETE FLOOR.
7 -NO SWM MOLWYENAD LVYO MX OET *“NOILOHGSNI 4O AWIHL LW AN GENERATORS - UNIT MOUNTED
GENERATOR CONTROLLERS AND
CIRCUIT BREAKERS. 3 - DAYTANKS
3 —- HORIZONTAL BULK STORAGE
TANKS —- 10,000 GALLONS EACH.
DIKED CONTAINMENT WITHOUT
MEMBRANE.
WELL SECURITY FENCE WITH GATE
AND PAD LOCK
J
390 KW JOHN DEERE GENERATOR 130 KW CAT GENERATOR WAS DOWN | WAS NOT OPERATIONAL. REPAIR AT TIME OF INSPECTION. WATER PUMP AND OPERATE IN | SUMMER. |
BATTERY CHARGERS FOR GENERATORS FUEL DAY TANK METER
LEVELLOCK VILLAGE
Recommendations:
1. Install a station service kWH meter to measure consumption of
the power plant.
2. Repair the 50 kW generator and use it to carry the load in
the summer.
3. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
_ preventative maintenance, tracking parts costs, fuel and oil
consumption.
4. Village Data is incomplete in the PCE Records. Train the
Village Utility Manager to report accurate readings.
LEVELLOCK VILLAGE
Cost Estimate:
1. Install a station service kWH meter Labor (10 hours @ $25/hour) Materials (allow $150)
Complete repairing a 50 kW generator. This job is currently funded and, therefore no cost estimated is provided.
Train the operator (8 hours @ $25/hour)
Engineering Costs (24 hours @ 32.50/hour)
Travel and Per Diem Costs
AEA Administrative Costs
Train Village Utility Manager on how
to report accurate readings for PCE (8 hrs @ $25/hr)
Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs
AEA Administrative Costs
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$400.0
$0.0
$200.0
$780.0
$3,400.0
$3,900.0
$200.0
$780.0
$3,400.0
NEWTOK VILLAGE
Summary:
The existing overhead distribution is 480/277V, 3-phase 4-wire
throughout the entire village. The power house is a metal
building with a wood floor. Upgrade the wood floor to provide
one-hour construction in accordance with NFPA 37. There is one 50
kW, one 30 kW and one 125 kW generator.
Village Data is incomplete in the PCE Records. Therefore, the
percentage of Annual System Line Loss and Annual Fuel Consumption
can not be computed.
High Average Fuel Consumption is 8.06 kWH/Gal.
Low Average Fuel Consumption is 7.43 kWH/Gal.
High Average Load is 24.8 kW.
Low Average Load is 14.8 kW.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
Cc amunity: NEWTOK Utility: UNQUSRAG POWER CO. 0 1ership: Contact:
( Date: 06/20/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): ¥ Y YX
Engine Make: JOHN DEERE JOHN DEERE JOHN DEERE
Engine Model: DES-35 DES-35 6466AF-00
Engine RPM: 1800 1800 1800
Serial Number: 583763T 598258T 210393RG
Horsepower: 67 40 167.5
Governor Type: BOSCH BOSCH BOSCH
Model Actuator: 83023460
Model Speed Control: WOODWARD8256016 WOODWARD8256016 WOODWARD8256016
DC Voltage: 24 24 24
Unit Circuit Breaker: NONE NONE NONE
Type/Amp/Volt: N/A N/A N/A
Year Installed: ---- <--> ===>
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 24,081.6 31,091.6 2,169.2
Generator Make: STAMFORD STAMFORD CONDEC
Generator Capacity (KW): 50 30 125
Generator Voltage: 480V 480V 480V Parallel Switchgear: Y Y ¥
KWH Meter? (Y/N): ¥ Xx Y
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): Y
Waste Heat Recovery Operational? (Y/N): Y
Powerhouse KWH Meter Type: NONE
Catalog #: Number of Stators: N/A
Demand? (Y/N): N CT Ratio:
Battery Charger/Type/Model: SENS #1351-05, TYPE FCA-24-10
Individual Genset Meter: YES Fuel Day Tank Type: Pump #: Motor #:
Fuel Day Tank Meter: Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
Notes: 1. Gl: 24A,12A,26A,470V DEMAND LOAD
G2: 14A,14A,20A,470V DEMAND LOAD
Gl & G2 ARE RUNNING IN PARALLEL.
INSTANANEOUS KWH METER READING: PWN
SIMPLEX SFTA-25
NO METER
YES. PYROTRONIC SYSTEM 3 HALON
KINETIC ENERGY
38
26
46
470
59.9
24
CALC.: (1.73) (480) (20.7)=17.2 KVA CALC.: (1.73) (480) (16.0)=13.3 KVA TOTAL DEMAND LOAD IS 24.2 KW.
50KW
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c nmunity: NEWTOK Utility: UNQUSRAG POWER CO.
dwaership: Contact:
( Date: 06/20/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: 4 HOUSES Multi Family: N Commercial: Y STORE Public: Y SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 20,000 Number of Bulk Tanks: 3
Diked Containment? (Y/N): N WITHOUT MEMBRANE Visual Evidence of Leaks: NO
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 480V, 3-PHASE, 4-W
Underground: N/A Combined: N/A Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: N/A
Pad: N/A
Pole: N/A
Voltage In/Out: 480V/480V, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX. 10
GENERAL NOTES
1. POWER HOUSE HAS WOODEN FLOOR W/METAL BUILDING.
2. HALON FIRE ALARM SYSTEM INSTALLED. FIRE EXTINGUISHERS AVAILABLE.
3. SWITCHGEAR WAS FAIRLY NEW. MANUFACTURED BY CONTROLLED POWER.
4. TYPICAL STEP-DOWN IS DRY-TYPE, POLE MOUNTED, 2-WIRE, 120-240/480V.
SINGLE PHASE, 3-WIRE TO HOUSES.
5. Gl IS EQUIPPED W/125 KW. IT ONLY PUTS OUT 30 KW PER THE OPERATOR.
6. POWER HOUSE OPERATOR IS CHARLES TEDDY. HIS HOME PHONE # 237-2528.
7. USES (4) 55 GALLON DRUMS OF FUEL PER DAY.
HOIAWAS ASNOH ‘UHWUOASNVUL NMOG-daLS TWOIdAL
MAIN LINE 480V, 3-PHASE,
4-WIRE. OVERHEAD LINE IS IN
GOOD CONDITION.
POWER HOUSE - METAL BUILDING,
WOOD FLOOR. IT IS IN GOOD
CONDITION.
300 - GALLON SUBFEED TANK.
WAS PUMPING AT TIME OF
INSPECTION
LT
EXTERIOR
COPPER GROUND LAID ON THE
GROUND. BURY BARE COPPER
GROUND CONDUCTOR A MINIMUM OF
18" BELOW GRADE.
HALON FIRE SYSTEM CONTROL
PANEL AND HALON ANSUL BOTTLE
(WALL MOUNTED)
ee
ta o 4 7 Lest . Hl
i: ye itl fT oo B Ke ck cen
UHOUWHO AUALLVWE TWOIdGAL
. (a = ei ee a
cakes ome i MAIN SWITCHGEAR WITH INSTAN-
Se ‘) ‘ ° TANEOUS KW METERS. 3 - GENERA-
——\ y | TOR SWITCHGEARS WITH VOLT/AMP/
7 f 4 FREQ METERS. NEAR NEW AND WELL
ef a aly ce MAINTAINED.
Wd y. 1° | ee a =
a
EMERGENCY LIGHT TO BE HARD- WHOALV Td NO SNOTTIWS OO€ - UNWL ZOVUYOLS PROVIDE A SHEET METAL DIKE.
25 GALLON DAYTANK WITHOUT
FUEL METER - ON WOOD FLOOR.
125 KW JOHN DEERE GENERATOR
WAS DOWN AT TIME OF INSPECTION
a:
30 KW JOHN DEERE GENERATOR WAS ON-LINE AT ITME OF INSPECTION. 30 KW AND 50 KW GENERATORS ARE RUNNING PARALLEL.
50 KW - JOHN DEERE GENERATOR
WAS ON-LINE AT TIME OF
INSPECTION
NEWTOK VILLAGE
Recommendations:
1. Install a fuel meter on the daytank to accurately account for
the fuel the utility is consuming.
2. Install diamond steel plate on the wood floor for a minimum
of 12 inches around each engine in accordance with NFPA 37.
3. Install a totalizing kWH meter and a station service kWH
meter to measure the power house electrical consumption.
4. Complete driving the ground rods and bury the copper ground
conductors a minimum 18 inches below grade.
5. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption. Village Data is incomplete in PCE Records.
Train Village Utility Manager to report accurate readings.
6. Install a dike around the daytank to contain any possible
fuel spilis.
7. Fix the leaning poles.
8. Loads are higher on Phase C than A or B. Rebalance village
loads by shifting some loads on Phase C to Phase B. Reconfirm
Phase balance when school starts in Fall.
9. Hardwire the existing emergency light and connect to a
dedicated circuit.
10. Install a dike around the bulk storage tanks to contain any
possible fuel spills.
NEWTOK VILLAGE
Cost Estimate:
1. Install daytank meter Labor (4 hrs @ $10/hr) $40.0 Materials (allow $500) $500.0 Engineering Costs (8 hrs @ $32.5/hr) $260.0
Install diamond plate on the wood floor Labor (24 hrs @ $25/hr) $500.0 Materials (allow $750) $750.0
Install a totalizing and a station service kWH meter. Labor (20 hrs @ $25/hr) $500.0 Materials (allow $300) $300.0
Drive and bury ground rods and ground
conductor as the Operator's duty at no cost.
Train the Operator (8 hrs @ $25/hr) Train the Village Utility Manager (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
Install a sheet metal dike around the daytank Labor (4 hours @ $25/hour) - $100.0 Materials (allow $500) $500.0
Provide stubbed poles to fix leaning poles Labor (20 hrs @ $10/hr) $200.0
Use local materials at no costs. $0.0
Rebalance loads in the village Labor (32 hrs @ $25/hr)
Hardwire existing emergency light to a dedicated circuit. (4 hrs @ $25/hr)
Install a dike around the bulk storage tanks
Labor (40 hrs @ $25/hr) $1,000.0 Materials (allow $5,000) $5,000.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$800.0
$1,250.0
$800.0
$0.0
$200.0
$200.0 $780.0 $3,400.0 $3,900.0
$600.0
$200.0
$800.0
$100.0
$6,000.0
$22,836.0
NIGHTMUTE VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-37.5 kVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on an
H-platform. The power house is of wood construction with a wood
floor. Upgrade the wood floor to provide one-hour construction
in accordance with NFPA 37. There is one 75 kW and one 100 kW
generator.
Nightmute Village is not on the PCE Progran.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
c nmunity: NIGHTMUTE Utility: NIGHTMUTE POWER PLANT
oy ership: Contact:
Date: 06/20/89 Phone:
G-1 G-2 G-3
Operational? (Y/N): Y ¥
Engine Make: DEUTZ DEUTZ N/A
Engine Model: GF61913 F6L413FR
Engine RPM: 1800 1800
Serial Number: 6271759 6292620
Horsepower: 100.5 134
Governor Type: WOODWARD WOODWARD
Model Actuator: 8290-048-D 8290-048-D
Model Speed Control: WOODWARD8330040 WOODWARD8330040
DC Voltage: 24 24
Unit Circuit Breaker: YES YES Type/Amp/Volt: UNMARKED ?/225A/600V
Year Installed: 1981 ===s
Last Major Overhaul (Hrs): NONE NONE
Current Hours: 18,824.8 15,828.1
Generator Make: KATO KATO
Generator Capacity (KW): 75 100
Generator Voltage: 480V 480V
Parallel Switchgear: Y ¥
KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended: 2
Waste Heat Recovery Installed? (Y/N): N
Waste Heat Recovery Operational? (Y/N): N
Powerhouse KWH Meter Type: WESTINGHOUSE D4B-3FM,CL 20
Catalog #: 280C210G01 120V,4W,Y
Number of Stators: 3 MULTIPLIER: 288
Demand? (Y/N): Y
CT Ratio:
Battery Charger/Type/Model: SENS#1416-07 & 1416-06
Individual Genset Meter: KATO-VOLT/AMP/FREQ METER
Fuel Day Tank Type: SIMPLEX--50 GAL.
Pump #: N/A
Motor #: N/A
Fuel Day Tank Meter: NO
Fire Protection Type/Operational?: NONE. NO FIRE EXTINGUISHERS
Original Contractor: KINETIC ENERGY
Spot Reading A Amps: 30
Spot Reading B Amps: 60
Spot Reading C Amps: 55
Spot Reading Volts: 470
Spot Reading Freq.: 60
Power (KW): 31
Notes: 1. POWER HOUSE DOES NOT HAVE A STATION SERVICE KWH METER
2. SWITCHGEAR IS MANUFACTURED BY CONTROLLED POWER.
3. TOTALIZING KWH METER IS APPARENTLY NOT WORKING.
4. DEMAND LOAD CALCULATED: (1.73) (470) (48.3) = 39.3 KVA (31.4 KW)
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
Cc munity: NIGHTMUTE Utility: NIGHTMUTE POWER PLANT
oy -ership: Contact:
Date: 06/20/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: Y HOUSES
Multi Family: N
Commercial: Y STORE
Public: Y SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 47,000
Number of Bulk Tanks: 5
Diked Containment? (Y/N): Y
Visual Evidence of Leaks: NO TANKS ARE IN GOOD CONDITION
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 12.47KV, 3-PHASE, 4-W
Underground: N/A
Combined: N/A
Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: 112.5 KVA
Pad: N/A
Pole: 3-37.5 KVA ON "H" PLATFORM
Voltage In/Out: 12.47KV/480V
UNMETERED STREET LIGHTS
Quantity: YES UNKNOWN
GENERAL NOTES
1. POWER HOUSE HAS WOODEN FLOOR W/WOOD CONSTRUCTION, WELL INSULATED.
2. POWER HOUSE DOES NOT HAVE FIRE EXTINGUISHERS.
3. POWER HOUSE HAS EMERGENCY LIGHTS
4 AMPERAGE FLUCTUATED ABOUT 2 AMPS AT AN 8 SECOND INTERVAL
5. DAY TANK HAS NO DIKE.
6. G-1 WAS ON-LINE DURING INSPECTION.
LHSIT LESYLS aNw UAWHOASNWUL NMOG daLS IWOIdAL 3 - 37.5 KVA, 480V/12.47 KV,
| me 3-PHASE, 4-WIRE STEP-UP
| { TRANSFORMER BANK. POWER
| ; HOUSE - WOOD CONSTRUCTION.
wero DHS H2 Otd au wm _ pp Do fs 0 CR
on | a4 bw DH 2w uG | 4 QAH fo Oo=24 n hr
Nd aie 4 - HORIZONTAL AND 1 - One VERTICAL BULK STORAGE TANKS. TOTAL OF 47,000 GALLONS. é
SPOT ee TEONE NH
EUTZ MAIN SWITCHGEAR WITH TOTALIZ-—
GENERATOR ING KWH METER.
SWITCHGEAR - VOLT/AMP/FREQ
AND POWER FACTOR METER. GENERATORS WITH UNIT MOUNTED
GENERATOR CONTROLLER ARE ON
75 KW DEUTZ AND 100 KW D
WOOD FLOOR.
1 we 75 KW DEUTZ GENERATOR WAS ON- LINE AT TIME OF INSPECTION 100 KW DEUTZ GENERATOR WAS DOWN AT TIME OF INSPECTION -— |
100 KW DEUTZ GENERATOR WITH 7 5 KW DEUTZ GENER i BATTERY CHARGER (WALL MOUNTED) BATTERY CHARGER (WALL MOUNTED)
POOR EXHAUST THIMBLE THROUGH :
PLYWOOD CEILING (TYPICAL) : 50 GALLON FUEL DAYTANK. IT
‘ DOES NOT HAVE A FUEL METER.
BULK STORAGE TANKS ARE MANI- MAIN 12.47 KV, 3-PHASE, 4-WIRE
FOLDED LINE. OVERHEAD LINE IS IN
EXCELLENT CONDITION.
lOvqns Moe Wrane Mute
NIGHTMUTE VILLAGE
Recommendations:
1. Install a fuel meter on the daytank to accurately account for
the fuel the utility is consuming.
2. Install diamond steel plate on the wood floor for a minimum
of 12 inches around each engine in accordance with NFPA 37.
3. Install a new totalizing kWH and an LED type instantaneous kW
meter.
4. Install a station service kWH meter to measure electrical
consumption for the power plant.
5. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
6. Install a dike around the daytank to contain any possible
fuel spills.
7. Provide a 5 pound fire extinguisher in the power plant.
8. Reconfigure the existing cross arm construction to meet
clearances over and beside the footbridge in accordance with
NESC 234.
9. Enroll Nightmute Village in the PCE Program to benefit from
the technical assistance training program, etc.
10. Poor exhaust thimble through plywood ceiling.
11. Power factor meter is showing "LEAD" instead of "LAG". Repair
or replace with a new meter.
NIGHTMUTE VILLAGE
Cost Estimate:
1.
10.
Install a daytank meter (4 hrs @ $25/hr) $100.0 Materials (allow $500) $500.0 Engineering Costs (8 hrs @ $260.0
Install diamond plate on the wood floor Labor (40 hrs @ $25/hr) $1,000.0 Materials (allow $1,500) $1,500.0
Remove and install a totalizing kWH meter
and an instantaneous LED kWH meter Labor (24 hrs @ $25/hr) $600.0 Materials (allow $350) $350.0
Install a station service kWh meter Labor (10 hours @ $25/hour) $250.0
Materials (allow $150) $150.0
Train the Operator (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr) Travel and Per Diem Costs
AEA Administrative Costs
Install a sheet metal dike around the around the daytank. (4 hrs @ $25/hr) $100.0 Materials (allow $750) $750.0
Install a 5 pound fire extinguisher
Reconfigure the existing cross arms of the entire distribution line (200 hrs @ $25/hr) $5,000.0 Engineering Costs(60 hrs @ $32.5/hr) $1,950.0
Travel and Per Diem Costs $3,500.0
AEA Adiministrative Costs $3,900.0
Install slience & flange at existing exhaust stack thimble (12 hrs @ $25/hr) $300.0 Materials (allow $500) $500.0
Replace P.F. meter (8 hrs @ $25/hr) $200.0 Materials (allow $250) $250.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$860.0
5,000.0
$2,500.0
$950.0
$400.0
$200.0
$780.0 $3,400.0 $3,900.0
$850.0
$100.0
$14,350.0
$35,448.0
PEDRO BAY VILLAGE
Summary:
The existing distribution system is 7200 V, l1-phase, 2-wire and
is laid in the water. The substation consists of 1-100 kVA
480/240 V - 7.2 kV, 1-phase, 3-wire pad-mounted transformer. The
power house is a metal building building with a concrete floor.
There is one 85 kW and one 100 kW generator.
According to the PCE Report, the Annual System Line loss is
-52.1%, which is unacceptable.
Annual Fuel Consumption is 9.76 kWH/Gal.
High Average Load is 77.9 kW.
Low Average Load is 9.3 kW.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
Cc nmunity: PEDRO BAY O jership: { Date: 06/27/89
Utility: PEDRO BAY VILLAGE COUNCIL
Contact: BARBARA JACKO,CARL JENSEN-OP
Phone: 850-2225
G-1 G-2 G-3 Operational? (Y/N): Y¥ N
Engine Make: JOHN DEERE CUMMINS
Engine Model: DES-85 3904197
Engine RPM: 1800 1800
Serial Number: 2840190X 44155808
Horsepower: 114 134
Governor Type: WW#825601/7-1712 WW#8250-O022-512
Model Actuator: ROSAMASTDM42826 WW#342F-290x
Model Speed Control: WW#8290-040C WwW#8290-040C
DC Voltage: 24 24 Unit Circuit Breaker: NO NO Type/Amp/Volt: N/A N/A
Year Installed: ---- 1986 Last Major Overhaul (Hrs): NONE NONE
Current Hours: 4,512.1 2,067.8
Generator Make: STAMFORD STAMFORD Generator Capacity (KW): 85 100
Generator Voltage: 480V 480V Parallel Switchgear: Y Y
KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended: 3
Waste Heat Recovery Installed? (Y/N): Y
Waste Heat Recovery Operational? (Y/N): Y
Powerhouse KWH Meter Type: WESTINGHOUSE FM-5S, CL 20,
Catalog #: 68681368 TYPE D4S-2M, 240V
Number of Stators: 2 MULTIPLIER: 40
Demand? (Y/N): Y
CT Ratio: 200/5 1 ONLY
Battery Charger/Type/Model: SENS#1834-103 & 1704-17 Individual Genset Meter: VOLT/AMP/FREQ METER
Fuel Day Tank Type: 3-OVAL 220 GAL. EACH Pump #: N/A INARI te al es ee ee Motor #: N/A
Fuel Day Tank Meter: LIQUID CONTROLS#M5442002-M1120
Fire Protection Type/Operational?: NONE; FIRE EXTINGUISHERS ONLY Original Contractor: BOB DRYDEN Spot Reading A Amps: 75 Spot Reading B Amps: 75 Spot Reading C Amps: N/A Spot Reading Volts: 475 Spot Reading Freq.: 60
Power (KW): 49
Notes: 1.TOTALIZING KWH METER IS ONLY READING A SINGLE PHASE LOAD. 2.DEMAND LOAD CALCULATED: 2(240)(75) = 36.0 KVA (OR 28.5 KW) 3.ACTUAL READING: A:75A; B:75A; LINE-NEUT:240V; LINE-LINE:480V 4.ACTUAL DEMAND LOAD READING: (0.56) (40) = 22.4 KW
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
2 munity: PEDRO BAY Utility: PEDRO BAY VILLAGE COUNCIL
d.7 yship: Contact: BARBARA JACKO,CARL JENSEN-OP
Date: 06/27/89 Phone: 850-2225
FACILITY INVENTORY
Meter Status (Yes/No) Notes
Single Family: x 120/240V, 1-PHASE, 3-WIRE
Multi Family: Y 120/240V, 1-PHASE, 3-WIRE
Commercial: ¥. Public: Y
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 40,000 Number of Bulk Tanks: 4
Diked Containment? (Y/N): Y DIAPER TANK Visual Evidence of Leaks: EXCELLENT CONDITION
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: N/A
Underground: N/A Combined: N/A Laid on Ground: 7200 KV, 1-PHASE, 3-WIRE
SUBSTATION TRANSFORMER
Capacity: 100 KVA
Pad: YES
Pole: N/A
Voltage In/Out: 480V/12.47KV, 1-PHASE, 3-WIRE
UNMETERED STREET LIGHTS
Quantity: NONE
GENERAL NOTES
1. G-2 WAS DOWN. THE OWNER IS HAVING A PROBLEM GETTING
ASSISTANCE FROM THE CUMMINS REPRESENTATIVE.
2. POWER HOUSE HAS A CONCRETE FLOOR W/WOOD CONSTRUCTION.
3. SWITCHGEAR MADE BY CONTROLLED POWER.
SHUNT REACTOR (PAD MOUNTED) -40 KVAR, 7200V, 1-PHASE, 3-WIRE
BULKTANKS ARE MANIFOLDED.
POWER HOUSE DOES NOT HAVE A STATION SERVICE KWH METER. IT WILL BE
INSTALLED THIS SUMMER (1989). an cee
nad WHWK +4 td <MH eS Q QAP Hear a n GH tH bl ms 'd Pi 2Uu gO = Ba tl HAH be pd wy - & n So ae POWER HOUSE - METAL BUILDING,
ml FF CONCRETE FLOOR. IT IS IN
GOOD CONDITION.
4 - DIKED BULK STORAGE TANKS ARE MANIFOLDED. TOTAL OF 40,000 GALLONS.
40 KVAR, 7,200 V, 1 3-WIRE SHUNT REACTOR AND
100 KVA, 480/7,200 V, 1-—PHASE,
3-WIRE STEP-UP TRANSFORMER
SUADUWHO AUALLVA ANY SUOLVYANAD “daowldad uo daulvdad Ad OL UALAW HMM ONIZI —TWLOL “YSLAN HMM ONIZITIWLOL QNW SUVWHOHOLIMS YOLVYANAS | 85 KW JOHN DEERE GENERATOR WAS
ON-LINE AT TIME OF INSPECTION OO KW CUMMINS GENERATOR WAS i
NEEDS TO BE N WHICH BROKE
FIXED.
|
DAYTANK METER AND FIRE
EXTINGUISHER AT EXIT DOOR.
PEDRO BAY VILLAGE
Recommendations:
1. Install a station service kWH meter to measure electrical
consumption for the power plant.
2. Existing totalizing kWH meter is not reading properly.
Calibrate totalizing kWH meter or replace it with a new one.
3. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption. Village Data is not accurate readings. Train
Village Utility Manager to report accurate readings.
4. 52.1% Annual System Line Loss is excessively high. A system
wide meter audit is required to accurately establish line
losses.
PEDRO BAY VILLAGE
Cost Estimate:
1. Install a station service kWH meter. Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
$ 400.0
2. Repair/replace a totalizing kWH meter Labor (14 hours @ $25/hour) $350.0 Materials (allow $150) $150.0
$500.0
3. Train the Operator (8 hrs @ $25/hr) $200.0
Train the Village Utility Manager (8 hrs @ $25/hr) $200.0 Engineering Costs (24 hours @ 32.50/hour) $780.0
Travel and Per Diem Costs $3,400.0
AEA Administrative Costs $3,900.0
4. AEA to provide technical assistance to perform
meter audit system wide to track feeder losses. Engineering Costs (80 hrs @ $32.5/hr) $2,600.0 Travel and Per Diem Costs $4,500.0
AEA Administrative Costs $5,000.0
SUBTOTAL $21,080.0 Contingency @ 20% $4,216.0
TOTAL COST ESTIMATE $25,296.0
PLATINUM VILLAGE
Summary:
The existing overhead distribution is 208/120V, 3-phase 4-wire
throughout the entire village. The power house is a wood
building with a concrete floor. There is one 50 kW, and one 135
kW generator.
Platinum Village is not on the PCE Program.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
DS munity: 222727227222222222222222222? Utility: -22222?722e2e terre tee e ere. 2. .ership: PLATINUM Contact:
Date: 06/21/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): ¥ N Engine Make: CAT CAT
Engine Model: 3306PC 3306 Engine RPM: 1800 1200
Serial Number: 66D33240 23C822 Horsepower: 181 67 Governor Type: CAT CAT
Model Actuator: CAT CAT
Model Speed Control: CAT CAT DC Voltage: 24 24
Unit Circuit Breaker: NO NO
Type/Amp/Volt: N/A N/A
Year Installed: 1978 1978 Last Major Overhaul (Hrs): NONE 10/788
Current Hours: 1,054.2 10,254
Generator Make: CAT CAT Generator Capacity (KW): 135 50
Generator Voltage: 208V 208V Parallel Switchgear: N N
KWH Meter? (Y/N): N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N): Waste Heat Recovery Operational? (Y/N): Powerhouse KWH Meter Type: Catalog #: Number of Stators:
Demand? (Y/N): CT Ratio:
Battery Charger/Type/Model: Individual Genset Meter: Fuel Day Tank Type: Pump #: Motor #:
Fuel Day Tank Meter: Fire Protection Type/Operational?:
Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
Notes: 1. DEMAND LOAD: (1.73) (205) (50)
KK] 2 ONE
A
NONE VOLT/AMP/FREQ METER
DRUM 2-300 GAL N/A N/A NO. USE DIP STICK TO MEASURE NONE. NO FIRE EXTINGUISHERS UNKNOWN 62 38 50 205 59.6 14
DEMAND LOAD READING: A AMPS:62;B AMPS:38;C AMPS:50;LINE VOLTAGE: 205 = 20.6 KVA (16.5 KW). POWER HOUSE DOES NOT HAVE A TOTALIZING OR STATION SERVICE KWH METER G-1 WAS ON LINE DURING INSPECTION.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
2, 1ership: PLATINUM Date: 06/21/89
FACILITY INVENTORY
Meter Status (Yes/No) Single Family: Y Multi Family: N Commercial: ¥ Public: Y
FUEL SYSTEM INVENTORY
Bulk Storage Capacity:
Number of Bulk Tanks: 1
> amunity: 2?2222222222222222222?2??? Utility’:
Contact:
Phone:
Notes
HOUSES
STORE
POST OFFICE
Diked Containment? (Y/N): N SET ON GROUND Visual Evidence of Leaks: GOOD SHAPE
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 120/208V, 3-PHASE, 4-WIRE
Underground: YES
POPP PPP PPPPPPPPPPPPPPPPP?
10,000
Combined: N/A Laid on Ground: N/A
SUBSTATION TRANSFORMER
Capacity: N/A
Pad: N/A
Pole: N/A
Voltage In/Out: 208V/208V, 3-PHASE, 4-WIRE
UNMETERED STREET LIGHTS
Quantity: APPROX 10
GENERAL NOTES
1. POWER HOUSE HAS CONCRETE FLOOR W/WOOD CONSTRUCTION.
2. POWER HOUSE DOES NOT HAVE EMERGENCY LIGHTS
3. PLATINUM POWER HOUSE IS NOT ON PCE PROGRAM. 50 CENTS/KW/HR. NOOSE 4W,Y; 2-STATORS. READING:
50 KW GENERATOR IS USED YEARLY. STORE SERVICE METER: WESTINGHOUSE #66382535, FM-14S, CL 200, 240V,
- INSULATION ON OVERHEAD WIRES IS RUBBED THRU AND HAS CAUSED SHORTS.
- THERE ARE 27 CUSTOMERS IN THIS VILLAGE. . 135 KW GENERATOR IS STAND-BY
21.1 KW DURING THE INSPECTION.
NO DIKE uw = = ec B ee «xc a a & > By Zz ° pe 4 ee 0 ° So m | ss vo H a n ay H aA 63} n P foe i) Ge io] = od ico =} fy Oo = - HORIZONTAL STORAGE TANK
10,000 GALLONS.
CONTAINMENT.
1 TYPICAL MAIN LINE 208V, | 4-WIRE OVERHEAD CONDUCTORS 3-PHASE, 4-WIRE WITH STREET HAVE RUBBED THROUGH THE INSUL-— LINE. ATION AND HAS CAUSED SHORTS. i oO = > ° = ee & oc H. a & fy On Dp Ho ze DH Of og o «x ° B
‘POWER HOUSE — CONCRETE FLOOR,
WOOD CONSTRUCTION. REINSTALL
MAIN FEEDER TO MEET THE VERTI-
CAL CLEARANCE IN ACCORDANCE
POWER HOUSE DOES NOT HAVE
EITHER TOTALIZING OR STATION
SERVICE KWH METER. WITH NESC 234.
:OILVH Lo - UVADHOLIMS NIVW ¢:00oS
50 KW AND 5 KW CAT GENERATORS B/ Gea 2 Sania a
TYPICAL NATIVE POLE IS +-20 FT 4 135 KW CAT GENERATOR - WASTE { HEAT LINE TO THE UTILIDOR
WASTE HEAT LINES THROUGH 135 KW CAT GENERATOR WAS UTILIDOR TO STORE
ON-LINE AT TIME OF INSPECTION
é
‘ane Z
50 KW CAT GENERATOR IS BROKEN. MAIN SWITCHGEAR IS NEAR NEW
IT NEEDS TO BE FIXED. AND IN GOOD CONDITION.
wou 401d sanwr aan
PLATINUM VILLAGE
Cost Estimate:
1. Install a daytank meter (10 hrs @ $25/hr) $250.0 Materials (allow $500) $500.0 Engineering Costs (8 hrs @ $32.5/hr) $260.0
a $1,010.0
2. Install a totalizing kWH meter
Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
$400.0
3. Install a station service kWH meter Labor (10 hours @ $25/hour) $250.0
Materials (allow $150) $150.0
$400.0
4. Train the Operator (8 hrs @ $25/hr) $200.0
Train the Village Utility Manager
(8 hrs @ $25/hr) $200.0
Engineering Costs (24 hrs @ $32.5/hr) $780.0
Travel and Per Diem Costs $3,400.0
AEA Administrative Costs $3,900.0
5. Install a 5 pound fire extinguisher $100.0
6. Rebalance loads (40 hrs @ $25/hr) $1,000.0
7. Upgrade distribution line to 12.47/7.2 kV 3-phase, 4-W. Labor (80 hrs @ $10/hr) $800.0
Labor (260 hours @ $25/hour) $6,500.0
Materials (allow $30,000) $30,000.0
Engineering Costs(40 hrs @ $32.5/hr) $1,300.0
Travel and Per Diem Costs $2,750.0
AEA Administrative Costs $6,500.0
Remove overhead lines & poles Labor (40 hrs @ $10/hr) $400.0
Labor (80 hrs @ $25/hr) $2,000.0
$50,250.0
8. Install emergency light in the powerhouse
Labor (2 hrs @ $25/hr) $50.0
Materials (allow $250) $250.0
$300.0
9. Repair 50 kW generator (32 hrs @ $25/hr) $800.0
Materials (allow $1,500) $1,500.0
$2,300.0
10. Remove 135 kW generator set & trade for 25 kW
Cat generator, generator controller (unit mounted),
etc. (Assume credit for 135 kW generator cover costs
of new unit). Labor (90 hrs @ $25/hr) $2,250.0
SUBTOTAL $66,490.0
Contingency @ 20% $13,298.0
TOTAL COST ESTIMATE $79,788.0
PLATINUM VILLAGE
Recommendations:
1. Install a fuel meter on the daytank to accurately account for
the fuel the utility is consuming.
2. Install a new totalizing kWH meter.
3. Install a station service kWH meter to measure electrical
consumption for the power plant.
4. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption. Train the Village Utility Manager on how to
report accurate readings.
5. Install a 5 pound fire extinguisher in the power house.
6. Loads are higher on Phase A than Phase B or C. Rebalance
village loads by shifting some loads on Phase A to Phase B.
7. The existing overhead conductors have rubbed through the
insulation and caused shorts. AEA will provide assistance to
upgrade the existing overhead distribution lines to a
12.47/7.2 kV, 3-phase, 4-wire underground system.
8. Enroll Nightmute Village in the PCE Program to benefit from
the technical assistance, training programs, etc.
9. Install emergency light in the powerhouse.
10. Repair the 50 kW Cat generator and use it to carry winter
loads.
11. Trade a 135 kW generator set for 25 kW generator set to
better match the load and increase fuel efficiency. The
Operator should run the new 25 kW generator in the summer.
SHELDON VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase,
4-wire. The substation consists of 3-50 kVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on a
H-platforn. The power house is a wood building with a wood
floor. Upgrade the wood floor to provide one-hour construction
in accordance with NFPA 37. There is one 45 kW and one 110 kW
generator.
The monthly PCE Report for the year of 1989 is not complete
because of poor record keeping by the Village Utility Manager.
Therefore, the percentage of Annual System Line Loss, Annual Fuel
Consumption, High and Low Average Load can not be computed.
S
2.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N):
Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type: Catalog #:
Number of Stators:
Demand? (Y/N): CT Ratio:
Battery Charger/Type/Model: Individual Genset Meter:
Fuel Day Tank Type: Pump #: Motor #:
Fuel Day Tank Meter: Fire Protection Type/Operational?: Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
Notes: 1. EQUIPMENT COVER PLATES FOR G-1 AR
2.
3. POWER HOUSE DOES NOT HAVE A STATI
amunity: SHELDON POINT Utility: SHELDON POINT CITY COUNCI ership: Contact:
Date: 06/19/89 Phone:
G-1 G-2 G=3
Operational? (Y/N): ¥ Y
Engine Make: JOHN DEERE JOHN DEERE Engine Model: 4276DF001 6466TF-00 Engine RPM: 1800 1800
Serial Number: 1T04276D157379 RG6466T234563
Horsepower: 60.3 147.5
Governor Type: WOODWARD WOODWARD
Model Actuator: B290-048-C B290-0-48-C
Model Speed Control: WOODWARD8256017 WOODWARD8256017
DC Voltage: 24 24 Unit Circuit Breaker: NONE NONE
Type/Amp/Volt: N/A N/A Year Installed: ---- --~ Last Major Overhaul (Hrs): NONE NONE
Current Hours: 10,570.1 20,497.7
Generator Make: STAMFORD STAMFORD
Generator Capacity (KW): 45 110 Generator Voltage: 480V 480V Parallel Switchgear: Y Y,
KWH Meter? (Y/N): N N
2
XY
4 WESTINGHOUSE-FM-145, CL 200
S280C098G43. TYPE D4S-8M, 240V 2 MULTIPLY # IS 10
4
NONE SENS#1351-10, 1351-09, 120/12VDC
YES
SIMPLEX--50 GAL.
Fy ena ek ——
N/A
KENT--7,153.2 GAL. di rae NONE. FIRE EXTINGUISHER ONLY. KINETIC ENERGY
25 25
50 480 59
22
E MISSING.
TRANSFER SWITCH IS RATED AT 250 AMPS. ON SERVICE KWH METER.
ALASKA POWER AUTHORITY
RURAL UTILITY POWERHOUSE INVENTORY
> amunity: SHELDON POINT 2. .ership:
Date: 06/19/89
FACILITY INVENTORY
Meter Status (Yes/No) Single Family: y Multi Family: ¥ Commercial: Y Public: ¥.
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: Number of Bulk Tanks: 3 Diked Containment? (Y/N): N Visual Evidence of Leaks: NO
POWER DISTRIBUTION SYSTEM
System Voltage/Phases Overhead: 12.47KV, 3-PHAS
Combined: N/A
Utility:
Contact:
Phone:
Notes
HOUSES
STORE
SCHOOL
E, 4-W
SHELDON POINT CITY COUNCI
30,000
ae Underground: N/A NZD Laid on Ground: N/A
( SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A
Pole: 3-50 KVA ON "H" Voltage In/Out: 480V/12.47KV, 3
UNMETERED STREET LIGHTS
Quantity: APPROX 12
GENERAL NOTES
1.
2. BULK STORAGE TANKS ARE APPRO)
4. INSTANTANEOUS READING: 25 KW
PLATFORM
-PHASE
X.
4-WIRE
THERE IS A SUBFEED TANK OUTSIDE-500 GALLON CAPACITY 600 FT AWAY FROM POWER HOUSE. 3. DEMAND LOAD CALCULATED: (1.73) (480) (33.3) = 27.7 KVA (22.2 KW)
5. POWER HOUSE HAS WOOD FLOOR WITH WOOD CONSTRUCTION
bee pee
POWER HOUSE - WOOD CONSTRUC- x8 a ; | = So eva, eee ee,
TION. EMERGENCY LIGHT TO BE Fc | 4-WIRE STEP-UP TRANSFORMER
INSTALLED Me
TYPICAL MAIN LINE 12.47 KV, 45 KW AND 110 KW JOHN DEERE “8 A\'E # 3-PHASE, 4-WIRE. OVERHEAD LINE GENERATORS WITH HEAT ' ——; IS IN GOOD CONDITION. EXCHANGERS.
\ anal
MAIN SWITCHGEAR IS IN GOOD TOTALIZING KWH METER CONDITION.
rere ees a
45 KW JOHN DEERE GENERATOR
WAS DOWN. EQUIPMENT COVER hs He
PLATE TO BE INSTALLED. paeuLtl CHARGERS FOR G-1 AND
50 GALLON FUEL DAYTANK - ON
WOOD FLOOR. FUEL DAYTANK METER. FIRE EXTINGUISHER AT EXIT 300 GALLON SUB-FEED DAYTANK
DOOR
Mn a ee ee
SHELDON VILLAGE
Recommendations: 3
1. Equipment coverplates need to be installed.
2. Install diamond plate on the wood floor for a minimum of 12
inches around each engine in accordance with NFPA 37.
3. Trade the 110 kW generator set for a 50 kW generator set to
better match the load and increase fuel efficiency. The new
50 kW generator set should be provided with an electronic
governor.
4. Install a station service kWH meter to measure the electrical
consumption for the power plant.
5. Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption. Train the Village Utility Manager on how to
report accurate readings.
6. Install a dike around the daytank to contain any possible
fuel spills.
7. Enroll Sheldon Point Village in the PCE Program to benefit
from technical assistance, training programs, etc.
8. Install a dike around the bulk storage tanks to contain any
possible fuel spills.
9. Install one emergency light in the powerhouse.
SHELDON VILLAGE
Cost Estimate:
1.
2.
Install equipment cover plates as the operator's duty at no cost.
Install diamond plate on wood floor Labor (40 hrs @ $25/hr) $1,000.0 Materials (allow $1,000) $1,000.0
Remove 110 kW generator & its associated
devices. Trade 110 kW John Deere generator for 50 kW John Deere generator,
generator controller (unit mounted), etc. (Assume credit for 110 kW generator covers cost of new unit) Labor (84 hrs @ $25/hr)
Install a station service kWh meter Labor (10 hours @ $25/hour) $250.0 Materials (allow $150) $150.0
Train the Operator (8 hrs @ $25/hr) Train the Village Utility Manager (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
Install a sheet metal dike around the daytank. Labor(4 hrs @ $25/hr) $100.0 Materials (allow $500) $500.0
Install a dike around bulk storage tanks Labor (40 hrs @ $25/hr) $1,000.0 Materials (allow $5,000) $5,000.0
Install one eae light in the powerhouse
2 Labor (2 hrs @ 5/hr) $50.0
Materials (allow $250) $250.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$0.0
$2,000.0
$2,100.0
$400.0
$200.0
$200.0 $780.0 $3,400.0 $3,900.0
$600.0
$6,000.0
$23,856.0
TUNTUTULUK VILLAGE
Summary:
The existing overhead distribution is 12.47/7.2 kV, 3-phase, .
4-wire. The substation consists of 3-50 kVA 480/277 V -
12.47/7.2 kV, 3-phase, 4-wire transformers mounted on an
H-platform. There are three generators, each generator is housed
in its own building. The generator buildings are metal shells
with a wood floor. Upgrade the wood floor to provide one-hour
construction in accordance with NFPA 37.
There are two 80 kW and one 150 kW generator.
According to the PCE Report, the percentage of Annual System Line
Loss is 2%, which is acceptable.
Annual Fuel Consumption is 10.5 kWH/Gal.
High Average Load is 72.2 kW.
Low Average Load is 44.3 kW.
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
C amunity: TUNTUTULIAK Utility: TUNTUTULIAK COMM. SERV. A
9 .ership: Contact:
Date: 06/20/89 Phone:
G-1 G-2 G-3 Operational? (Y/N): Y ¥ Y
Engine Make: JOHN DEERE JOHN DEERE JOHN DEERE
Engine Model: 6466AF-00 6466AF-00 6466AF-00
Engine RPM: 1800 1800 1800
Serial Number: 1235F 1232FD RG6466A292057
Horsepower: 107 107 201
Governor Type: WOODWARD WOODWARD WOODWARD
Model Actuator: 8251-016 8251-016 8251-016
Model Speed Control: BOSCH#93131551 BOSCH#01150922 BOSCH#44913855
DC Voltage: 24 24 24 Unit Circuit Breaker: NO NO NO
Type/Amp/Volt: N/A N/A N/A
Year Installed: ---- ---- ----
Last Major Overhaul (Hrs): NONE NONE NONE
Current Hours: 23,756.6 25,624.1 1,226.2
Generator Make: CONDEC CONDEC STAMFORD
Generator Capacity (KW): 80 80 150
Generator Voltage: 480V 480V 480 Parallel Switchgear: Y Y N KWH Meter? (Y/N): N N N
OEM:
Hours/Day Attended:
Waste Heat Recovery Installed? (Y/N):
Waste Heat Recovery Operational? (Y/N):
Powerhouse KWH Meter Type:
Catalog #:
Number of Stators:
Demand? (Y/N): CT Ratio: Batte Charger/Type/Model: Individual Genset Meter:
Fuel Day Tank Type:
Pump #: Motor #:
Fuel Day Tank Meter: Fire Protection Type/Operational?:
Original Contractor: Spot Reading A Amps: Spot Reading B Amps: Spot Reading C Amps: Spot Reading Volts: Spot Reading Freq.:
Power (KW):
Notes: DEMAND LOAD CALCULATED:
DEMAND LOAD READING:
(1.73) (440) (91.7) SWITCHGEAR IS MANUFACTURED BY CONTROLLED POWER. POWER HOUSE HAS NO STATION SERVICE KWH METER. (1.6) (80)=128.0 KW (102.4 KVA) SINCE DATE UNK.
KK] GE TYPE FM-6S, VM-65-S, CL 10
700X25G16 240V, 4W Y
2 MULTIPLIER: 80
4
400/5
SENS/FCA-24-10/1351-05
VOLT/AMP/FREQ METER
TRAMONT 50, 25 & 50 GAL
DATA NOT AVAILABLE
DATA NOT AVAILABLE
OUTSIDE.
NO FIRE EXTINGUISHERS ONLY
KINETIC ENERGY
80
120
Zo
440
60
56
= 69.9 KVA (55.9 KW)
ALASKA POWER AUTHORITY RURAL UTILITY POWERHOUSE INVENTORY
Cc munity: TUNTUTULIAK Utility: TUNTUTULIAK COMM. SERV. A O iership: Contact:
Date: 06/20/89 Phone:
FACILITY INVENTORY
Meter Status (Yes/No) Notes Single Family: Y HOUSES Multi Family: Y APARTMENT Commercial: Y STORE
Public: Y SCHOOL
FUEL SYSTEM INVENTORY
Bulk Storage Capacity: 60,000 Number of Bulk Tanks: 3 Diked Containment? (Y/N): N
Visual Evidence of Leaks: TANKS ARE RUSTY.
POWER DISTRIBUTION SYSTEM
System Voltage/Phases
Overhead: 12.47KV, 3-PHASE, 4-W
Underground: N/A Combined: N/A
Laid on Ground: N/A
{ SUBSTATION TRANSFORMER
Capacity: 150 KVA
Pad: N/A
Pole: 3 50 KVA ON "H" PLATFORM
Voltage In/Out: 480V/12.47KV, 3-PHASE, 4-W
UNMETERED STREET LIGHTS
Quantity: APPROX. 12
GENERAL NOTES
1. POWER HOUSE IS MODULE PACKAGED BY CRAIG TAYLOR COMPANY (TYP OF 3)
2. WASTE HEAT RECOVERY IS PROVIDED FOR LAUNDROMAT.
3. DOUBLE 2x12 BRACES AT "H" PLATFORM ARE BROKEN.
4. SUBFEED TANK (OUTSIDE) CAPACITY=300 GAL. HAS METER BUT IT IS NOT
INSTALLED PROPERLY TO READ AMOUNT OF GASOLINE BEING USED.
5. ALL 3 DAY TANKS DO NOT HAVE LEVEL METERS
6. G-2 WAS ON-LINE DURING INSPECTION.
2 - 80 KW AND 1 - 150
MODULAR PACKAGE POWER HOUSE
BY CRAIG TAYLOR
TYPICAL MAIN LINE 12.47Kv,
3-PHASE, 4-WIRE. OVERHEAD LINE IS IN GOOD CONDITION
DWHw Ww ww | Oru! A2D Had oy 2a oO ~~ rs a PEA > | yo Se OWH Ss” dD oO = 2 Ho aS HA BN vO 'd-! wie tan Eto. PR Qa i <s 3 - HORIZONTAL BULK STORAGE fo TANKS —- 20,000 GALLONS EACH
80 KW JOHN DEERE GENERATOR
WAS ON-LINE AT TIME OF |
INSPECTION |
80 KW JOHN DEERE GENERATOR
WAS DOWN
TYPICAL BATTERY CHARGER
(WALL MOUNTED)
150 KW JOHN DEERE GENERATOR | TYPICAL 50 GALLON FUEL DAYTANK
WAS DOWN INSIDE EACH MODULAR PACKAGE
POWER HOUSE.
TOTALIZING KWH METER
(EXTERIOR) WASTE HEAT TO WASHETERIA
| DAYTANK METER (OUTSIDE) TO BE SUBFEED TANK (300 GALLON) | REINSTALLED AT INCOMING FUEL | LINE
TUNTUTULUK VILLAGE
Recommendations:
1. Loads are higher on Phase B than Phase A or C. Rebalance
village loads by shifting some loads on Phase B to Phase C.
Reconfirm Phase balance when school starts in Fall.
Install diamond plate on the wood floor for a minimum of 12
inches around each engine in accordance with NFPA 37.
The existing fuel meter is presently located on the wrong
side of the daytank. Relocate the fuel meter to properly
meter the fuel supplied to the generators.
Install a station service kWH meter to measure electrical
consumption for the power plant.
Train the Operator on how to most efficiently operate the
power plant and in the use of plant logs to enhance
preventative maintenance, tracking parts costs, fuel and oil
consumption.
Install a dike around the daytank to contain any possible
fuel spills. (typical of 3)
Replace two broken 2 x 12 braces on the H-platform.
Repair the many fuel leaks around the power house.
Separate the Washeteria's fuel line from the power house fuel
line.
TUNTUTULUK VILLAGE
Cost Estimate:
1.
2.
Rebalance loads in the village Labor (32 hours @ $25/hour)
Install diamond plates on 3 wood floors Labor (30 hrs @ $25/hr) $750.0 Materials (allow $1,500) $1,500.0
Relocate exterior fuel meter Labor (8 hours @ $25/hour) $200.0 Materials (allow $100) $100.0
Install a station service kWH meter Labor (10 hours @ $25/hour) $250.0
Materials (allow $150) $150.0
Train the Operator (8 hrs @ $25/hr) Engineering Costs (24 hrs @ $ 32.5/hr)
Travel and Per Diem Costs AEA Administrative Costs
Install a sheet metal dike around the daytank (typical of 3) Labor (12 hrs @ $25/hr) $300.0 Materials (allow $1,500) $1,500.
Replace two 2 x 12 braces Labor (8 hours @ $25/hour) $200.0 Materials (allow $250) $250.0
Repair many fuel leaks around the power house.
This is a maintenance item and, therefore, no cost estimate has been provided.
Separate Washeteria's fuel line from the
power house. Or install a fuel meter to
account for the exact amount of fuel the Washeteria is comsumming.
Labor (32 hrs @ $25/hr) $800.0 Materials (allow $500) $500.0 Engineering Costs (8 hrs @ $32.5/hr) $260.0
SUBTOTAL Contingency @ 20%
TOTAL COST ESTIMATE
$800.0
$2,250.0
$300.0
$400.0
$200.0 $780.0 $3,400.0 $3,900.0
$1,800.0
$450.0
$19,008.0