HomeMy WebLinkAboutAlaska Electric Power Statistics 1960-1982 Alaska Power Authority LIBRARY COPY 1960 - IALASKA ELECTRIC POWER STATISTICS 1960-1982 EIGHTH EDITION = AUGUST 1883 UNITED STATES DEPARTMENT OF ENERGY ALASKA POWER ADMINISTRATION ECO 046 i960 - 1982 DATE ISSUED TO ——— The Alaska POWeE! Alii. crommmtcenprrmereepremmmeesNLEDINUSA Inlickets power for Alaska's two Federal hydroelectric projects—-the 30,000—kw Eklutna Project near Anchorage and the 47,160-kW Snettisham Project near Juneau. APA also conducts investigations of future water and power projects as well as studies of transmission and power system development, all in cooperation with other Federal, State, and local entities. APA was established in June of 1967 as a unit of the Interior Department and became a unit of the Department of Energy on October 1, 1977, as provided under Public Law 95-91. APA reports to the Assistant Secretary of Energy, for Conservation and Renewable Energy. The APA headquarters are in Juneau, Alaska, with field offices at the two projects. Department Of Energy Alaska Power Administration P.O. Box 50 Juneau, Alaska 99802 FOREWORD: Alaska Electric Power Statistics 1960-1982 This is the eighth in a series of statewide electric power data summaries compiled by the Alaska Power Administration (APA). It continues the efforts by APA to provide a convenient and current reference source on Alaska power system data and trends in statewide electric power use. The report has fairly complete data summaries through calendar year 1982 with some monthly data for the early part of 1983. Included are data series for the electric utility systems, National defense installations, and self-supplied industrial systems. The following table presents a four-year summary of installed capacity and energy produced with breakouts in ownership, types of installation, and energy source. The table also has select data on residential use and consumer costs. Installed Capacity (MW) 1979 1980 1981 1982 Total 1911 1963 2078 2119 Utility 1255 1280 1379 1413 National Defense 206 206 205 206 Industry and Misc. 451 478 493 501 Total consists of: Hydro 6.5% 6.3% 6.0% 7.3% Gas Turbine 53.6% 55.2% 53.4% 52.2% Steam Turbine 16.5% 15.8% 18.4% 17.9% Diesel 23.4% 22.7% 22.2% 22.6% Growth from previous yr.: Total 5.9% 3.2% 5.9% 2.0% Utilities 11.1% 2.0% 7.7% 2.5% Net Energy Generated (GWH) Total 4861 5112 5271 5741 Utility 3086 3170 3289 3721 National Defense 498 501 494 490 Industry and Misc. 1278 1441 1489 1530 Total consists of: Hydro 9.4% 10.7% 11.4% 10.2% Gas 55.9% 56.4% 56.7% 59.1% Oil 17.9% 17.0% 15. 3% 15.2% Coal 10.5% 9.8% 10. 6% 9.9% Other 6. 3% 6.1% 6.0% 5.6% Growth from previous yr.: Total 2.1% 5.1% 3.1% 8.9% Utilities 4.2% 2.7%. 3.8% 13.15 Residential Customers Average Use (Kwh/yr./cust.) 10,014 10,309 9943 105373 Growth from previous year 2.9% lisdh -3.6% 4.3% Average Cost (¢/Kwh) 5.0 oa, 5.9 6.7 Highest Cost (¢/Kwh) 39.3 42.1 47.3 Sie/ Lowest Cost (¢/Kwh) 3.4 3.1 3.6 4.4 Average U.S. Cost (¢/Kwh) 4.4 Sol 5.9 6.1 Statewide power generating capacity at the end of 1982 totaled over 2.1 million kilowatts of which 67% was in the utility sector. Net production of electric energy totaled 5.7 billion kilowatt hours with 65% by the utility system. Total 1982 energy production was 8.9% above the prior year; energy produced by the utilities in 1982 was 13.1% above the prior year. Much smaller growth occurred in each of the three previous years. More detailed data presented in the report show large increases in 1982 in the Anchorage-Cook Inlet, Fairbanks, and Juneau areas as well as for many smaller utility systems. Based on the general level of economic activity throughout the State, it appears likely that similarly large increases may prevail over the next few years. Generating plant additions in 1982 totaled 41 MW, or a 2% increase. The mix of energy sources has not changed very much in recent years. Between 1979 and 1982, the share for natural gas increased from 55.9% to 59.1% while the share for oil dropped from 17.9% to 15.2%. The hydro share will increase somewhat in the near future with completion of the several projects in the State Power Authority program. As in other parts of the country, consumer power costs have increased significantly in recent years. Statewide averages for residential customers in 1982 was 6.7 cents per KWH, a 34% increase since 1979. Rates remain much higher for most smaller systems. Data sources are indicated on most exhibits and include the Alaska Public Utilities Commission, Department of Energy, Rural Electricfication Administration, Edison Electric Institute, and statistics reported directly to APA from various utilities Statewide. We appreciate Alaska's electrical industry cooperation in compiling this report and welcome any suggestions for improvement in future publications. 7 a , } Robert J. Cross Administrator TABLE OF CONTENTS TITLE NO. LOCATION OF ELECTRIC UTILITIES AND GENERATING CAPACITY - 1982 ... ALASKA UTILITY ABBREVIATIONS. .......ceeceeeeeeeees SUMMARY POWER AND ENERGY DATA Utility Installed Nameplate Capacity, Net Generation, Peak Demand, and Fuel Use by Location (Tables)......... Alaska Utilities Load Data and Installed Capacity (Graph)... Regional Summary -- Capacity and Net Generation (Table)..... 1982 Energy and Power Data (Table)........... INSTALLED CAPACITY DATA 1982 Installed Capacity by Fuel and Prime Mover (Table)..... Alaska Utility Installed Capacity Type -- Accumulative Nameplate Ratings by Year (Graph)....... Alaska Electric Power Installed Capacity -- Nameplate Ratings in Kilowatts (Table).. Total Installed Capacity -- Utility and Non-Utility (Graph)......... 1982 Installed Nameplate Capacity -- Regional WENT CI OSS (Table) ore rarere create rele rsieie clerslererecieic Installed Capacity Summary MW Summary Summary -- National Defense Installed Capacity dneAliaskal (lable) lererectecteciclewinncine GENERATION DATA 1982 Net Generation by Fuel and Prime Mover (Table)......... Annual Utility Generation Data by Region (Graph and Table).. Summary -- National Defense Generation in Alaska (Table).... Monthly Utility Generation by Fuel (Graph and Table)........ Twelve Month Running Totals - - Utility Net Generation (Gieaphzaind TaD ©) :ovc:0s0s51 0c, ore: e1e/ore ere erecsitaero wrersreressia TRANSMISSION LINES Existing Transmission Systems (Map).......... Transmission Lines and Major Interconnections (Tables)...... MARKET DATA Monthly Peak Loads (3 Graphs)............50e- Regional Peak Loads (MW) (Table).........-..+ Regional Energy Generation (1,000 MWH) (Table)... Energy Sales, Revenue, Customers -- 1982 (Table). Energy Use, Billing, Charge -- 1982 (Table).. Typical Electric Bills Monthly Residential (2 Tables)...... : GENERAL DATA Growth Indicators (Graph and Table) Electric Plant In Service (Table)... Alaska and Conterminus U.S. Average Energy Charge, Use, Billing (Table) 13 14 15 16 17 18 19 23 24 26 27 29 35 36 41 44 45 46 47 48 53 55 56 Borrow UAE) O.4mW iD) ‘e.smw (GT) Kattovie (NSBPEN) QeMwio) A \ UNITED STATES DEPARTMENT OF ENERGY ALASKA POWER ADMINISTRATION ALASKA \ Noaiek AVES ‘asMw (0) LOCATION OF ELECTRIC UTILITIES \ AND GENERATING CAPACITY—1982 \ Kira AVEC, OGM OH, 6 i *Noorvik AVEC, 06M B ‘ ori moras ‘ \ “Seige nec) Bettie 181.8), 06 mW (0) “ies Wines 13 Mw (0) \ Scale in miles —_—__ \ g te ae Pate (aver) : ‘02 Mw (0) \ F cqipsisiouid ger mere aa De Tonana (TPC) wine UwEC) \ Sea wo) temw'o) + og mw) {> =. (sprees tavec.og uw 0) 102 MW(0) «Maney Hot Springs (MUC), 0.1 ew (0) © 7 \ I) * . ‘Mulate (AVEC),O.7MW (0) / a fees (FM, GVEA) i ‘*Katteg (AVEC), 0.1 MW(D) ij ( repay — ia \ mag a8 we) i shea : 1 3 aw) che Minchumine {S3)) Dot Loke APATIOZ MWD) | ‘or mw iD) : \ ee Germ Teh Pani, gamwio) _Gravting AVEC) OM DI i sma wees) lcci ere a) Stealers | Rca sem nes snogena wrecyo2 wwe)" 1EmWED) ) eta Sconmen boy ecios ww oh Cam ives 9 wares Hooper Boy AMEC',0.7 saw (| Piet Stim (AVEC) * Holy Crowe (AYEC).O2 MW (0) ee) Ow) 0.8 Mw (0) onan! Kelshog) (AVEC), 0S mW (O} Lowy Kolahag}? «Anion (APC). Mekoryut (AVEC LO. 2Mw (0) 7 *Chstochine CTP) EBD) \ ‘05 Mw{0) 7 Numapitcin| avec, OS MW (0) Kenmaha cco et BOO, 2 kes % . | ce 22 mwio S% seen tavec,oz ww A aise even nee, TSAR, \pQuinhapek (AVEC).O3 Mw ©) * Glennotien (CvE a) "78M (0) slear coe ome a verge 7 Sa ' ¢ New Stuychok (AVEC), 0.21 GCoodnews Boy (AVECL!) Mw (0) Tomah (AVEC) eases si acrage meas ann (0 Kivewon (EU) ‘Cook Inlet Systeme 5 | same ween 28MM LES nwo, S2mW0) Hones (HL | \, sad NG |e, ew i 22 Mw ems MW CT) : s pas Mw (ST) ~ raya. 4 ® ware nie (HEA) =) - . ‘Wokrak (NEA), BMW 9 i owt (ne,01 se 0X? Paice ue 2mm w detuwb) ei nen ; = el Gao cryeganiou : sie ee ‘ : bie] koe 20.0 ww 0) ia 2p StelSED a rece wwe) arctic \ | er oa | aaent seem: | cr sida! isecloalees eoam | 7 i somes rc, Seth yOr¥O . J Oe | Craig (AP AT), LI MW{0) } ‘3 a (or oh LH Hydoburg (AP871,07 ha) ‘Sywoa swe SS — a Je (fend ran res st | ae ew rma Ai oS ven) oe ee ‘sue LP aco te Tew) 7 mPa) 1 (0) : es tna thats me rt -cnams gos tee Page sourneasy AE AEL&P AMFAC AML&P APA-E APA-S APC AP&T AVEC AUI BU&EC BUC BL&P CE CEA cEC com cTP CVEA DLE FMU FYU GHEA GVEA HEA HL&P H (EJJ) I-Nec KC Kec Kdea KEU KI KtEA KPU ALASKA UTILITY ABBREVIATIONS Alaska Electric Light & rower Company (Juneau) AMFAC Foods, Inc. (Sand roint on Popov Island [6] Anchorage Municipal Light & Power Department Alaska Power Administration-Eklutna (Anchorage: Alaska Power Administration-Snettisham (Juneau) Aniak Power Company Alaska Power & Telephone Company (Craig, Hydaourg, Skagway, Tok, Dot Lake? Alaska Village Electric Cooperative, Inc. (48 villages) Arctic Utilities, Inc. (Deadhorse) [13 Barrow Utilities & Electric Cooperative, Inc. Bethel Utilities Corporacion, Bettles Light & Power, Inc. Circle Electric Chugach Electric Association, Cordova Electric Cooperative, City of Manokotak Chistochina Inc. Inc. (Anchorage Area) Inc. Copper Valley Electric Association, (Glennallen, Valdez) Dot Lake Electric, Inc. C43 Eas C3] Inc. Fairbanks Municipal Utilities System Fort Yukon Utilities Glacier Highway Electric Association, Inc. (Juneau Area) Golden Valley Electric Association, (Fairbanks Area) ? Homer Electric Associatiun, Inc. Haines Light & Power Co. Inc. Hughes (Esther J. James) Inc. (Kenai Peninsula) Iliamna-Newhalen Electric Cooperative, Inc. (Iliamna, Newhalen, Nonaalton) Kotlik City King Cove City Kodiak Electric Association, Inc. Klukwan Electric Utility Kwethluk, Inc. Kotzebue Electric Association, Ketchikan Public Utilitics Inc. Private Private Municip. Federal Federal Private Private Coop. Private Coop. Private Private Private Coop. Coop. Municip Private Coop. Private Municip Private Coop. Coop. Coop. Private Private Coop. Municip. Municip. Coop. Municip. Municip. Coop. Municip. (SE) (SW) (sc) (sc) (SE) (SW) (SE; Y) (SCi Yi SW; A-NW) CA-NW) (A-NW) (SW) cy) ty) (sc) (sc) (SW) «sc)> (sc) cy) cy) «Y> (SE) GY? (sc) (SE) Cv (SW) cy) (SW) (sc) (SE) (SW) (A-NW) (SE) Manokotak (See COM) M&DE M&D Enterprises (Galena) MEA Matanuska Electric Association, Inc. (Palmer-—Talkeetna Area and Unalakleet) MUC Manley Utility Co., Inc. (manley Hot Springs) MP&L. Metlakatla Power & Light MGL&P McGrath Light & Power MKEC Middle Kuskokwim Electric Coop., Inc. (pending», (Chuathbluk, Crooked Creex, Sleetmute, Stony River) Nac Napakiak Corporation (SWGR Service from BUC) NEA Naknek Electric Association, Inc. NEC Nushagak Electric Cooperative, Inc. (Dillingham, NIP&L Nikolski Power & Light Co. (Umnak Is. ) NJUB Nome Joint Utilities Board (was N.&P) NSBP&L No. Slope Borough Power & Light System (Atkasook, Kaktovik, wainwright, Point Hope Point Lay, Nuiqsut, anaktuvuk Pass) NP&L. Northway Power & Light, inc. PLI Paxon Lodge, Inc. PMP&L Petersburg Municipal Power & Light Puc Pelican Utility Company (Pelican and Sand Point) SED Sitka Electric Department SES Seward Electric System ss Semloh Supply (Lake Minchumina) TePC Teller Power Company T-HREA Tlingit-Haida Regional Eiectrical Authority (Angoon, Hoonah, Kake, nasaan, Klawock) TPC Tanana Power Company VE Unalaska Electrio (was COU) UVEC Unalakleet Valley Electric Cooperative (5] WML&P Wrangall Municipal Light & Power WTC Weisner Trading Co. (Rampart) VRE Yakutat Power, Inc. Ci] Owned by Atwood Enterprises, Inc. Private Coop. Private Municip. Private Coop. Private Coop. Coop. Private Municip. Municip. Private Private Municip. Private Municip. Municip. Private Private Coop. Private Municip. Coop. Municip. Private Private C2] Owned by Northern Power & Engineering Corporation of Anchorage (33 CEC changed from Cordova Public Utility in March 1979 C4] Dot Lake transferred to AP&T in March 1978 C5] UVEC is in process of taking over the Unalakleet electric function from MEA C6] AMFAC changed to PUC in 1981 cy) (SC; A-NW) cy) (SE) (SW) (sw) (sw) (sw) (SW) (SW) (A-NW) (A-NW) (y) (sc) (SE) (SE; SW) (SE) «sc) cy) (A-NW) (SE) cy) (SW) (A-NW) (SE) (Y) (SE) SUMMARY POWER AND ENERGY DATA HG, A ST a UTILITY INSTALLED NAMEPLATE CAPACITY. NET GENERATION, PEAK DEMAND, AND FUEL USE BY LOCATION, 1982 SOUTHEAST AREA UTILITY INSTALLED /4/ pees NAMEPLATE CAPACTTY--KW ______ __________ NET GENERATION =~ MWH PEAK ___FUEL USE /5/___ Sym- /1/ Diesel Gas Steam /2/ /3/ TEMAND ail Gas Coal ~bel_ Location Tzee Tetal Hydro _(IC)_ Turbine Turbine Tetal Hydro Qil Gas Coal MW. KGal MMCF KTon THREA ANGOCN c 950 oO 3950 0 oO 1125 Oo 112! oO oO 3 107 oO ° APAT CRAIG P 1050 Oo 1050 oO o 2166 Oo 3166 oO oO S 262 ° 0 HL&P HAINES P 4120 Oo 4120 0 O 8320 QO 8320 oO 0 1.8 664 0 O THREA HOONAH c 1700 QO 1700 oO o 234z OQ 234z oO oO 6 221 ° ° AP&T HYDABURG P 735 ° 735 o oO 1102 QO 1102 ° oO .3 103 ° ° APA--S JUNEAU F 47160 47160 ° 0 oO 160954 160954 ° oO O 27.21 oO oO oO AEL&SP *” P 41122 7900 15722 17500 oO 48521 37401 11120 oO O 41.6 3988 oO o GHEA ae c 2500 QO 2500 oO oO 1695 Oo 1695 o ° 3.4 123 ° ° THREA KAKE c 1600 Oo 1600 oO oO 1956 Oo 1956 oO o 5 198 ° oO THREA KASAAN c 180 o 180 oO oO 92 o 92 o oO +O+ 21 oO oO KPU «KETCHIKAN M 28750 11300 17450 oO o 96052@ 60963 35089 oO O 19.1 2489 oO o THREA KLAWOCK c 1365 Oo 1365 oO o 1803 Oo 1809 oO o is 200 oO 0 KEU = KLUKWAN M 685 0 685 oO oO 300 oO 300 0 o -1E 26 oO 0 MP&L =METLAKATLA M 6000 3000 3000 0 oO 15484 1056 ° oO 3.6 92 0 0 PUC PELICAN P 1100 500 600 oO 0 2693 1128 O 0 “7E 398 o oO PMP&L PETERSBURG M 7100 2000 5100 oO 0 21314 13253 ° oO 4.3 1059 oO oO SED SITKA M 32640 24540 98100 oO oO 82849! 3223 oO O 16.7 z54 oO oO AP&T SKAGWAY P 4095 7800-3315 ° oO 5975 2692 oO oO 1.3F 308 oO oO TSU TENAKEE SPRINGS P 180 0 180 0 o Zz00 0 200 0 o aa 29 oO oO TE THORNE BAY oO o oO oO oO o o oO o o oO ° 0 WML&P WRANGELL M 7745 0 7745 0 oO 12896& Oo 12896 oO oO 3.0 9286 oO 0 YPI YAKUTAT P z02z5 Oo 2025 oO oO 4407 O 4407 0 oO 3 258 oO oO TOTAL SOUTHEAST 192802 97180 78122 17500 0 365281 LO7S7L 0 Oo 0699.4 «8586 ° ° /i/ TYPE: P-PRIVATE, M-MUNICIFAL, C-COOPERATIVE, F-FEDERAL. /2/ > E-ESTIMATE, P-PRELIMINARY, /3/ W-INCLUDES GENERATION FROM WASTE (SEE NOTE /W/ BELOW). /4/ I-PEAK DEMAND INCLUDED IN OTHER JUNEAU PEAKS AND NOT ADDED SEPARATELY TO REGION TOTAL. 73/ OQIL--THOUSANDS OF GALLONS, GAS--MILLIONS OF CUBIC FEET, COAL--THOUSANDS GF TONS. @ ADD 8156 MWH NET RECEIVED FROM LOUISIANA PACIFIC-KETCHIKAN CO. = 104Z08 MWH NET ENERGY USE. /W/ GENERATIGN FROM WOOD WASTE/OIL IN LPK KETCHIKAN = 8002392 MWH ! ADD 92 MWH PURCHASED FROM ALASKA LUMBER & PULP CO. = 82941 MWH NET ENERGY USE. /W/ GENERATION FROM WOOD WASTE/OIL IN ALP SITKA = 1011888 MWH & ADD 213 MWH RECEIVED FROM WRANGELL LUMBER CO. = 13109 MWH NET ENERGY USE. /W/ GENERATION FROM WOOD WASTE/OIL IN ALP WRANGELL = 27340 MWH * PEAK DEMAND AT THIS LOCATION IS INCLUDED ABOVE IN THE UTILITY WITH THE SAME SYMBOL, REGARDLESS CF REGION. APA 8/1983 /1/ /2/ 13/ /4/ /3/ /W/ ee UTILITY INSTALLED NAMEPLATE CAPACITY, NET GENERATION, PEAK DEMAND, AND FUEL USE BY LOCATION, 1982 SOUTHCENTRAL AREA Zz ---FUEL_USE_/5/___ Gas Coal Oil S UTILITY INSTALLED 14/ ___-- NAMEPLATE CAPACITY=-KW oo NET GENERATION -_MWH PEAK /2/ /3/ DEMAND Total Hydro Ql Gas Coal ANCHORAGE -FPALMER M 233444 oO 2236 198208 33000 579474 0 O 579474wW O 121.0 ae C 507800 15000 QO 421300 71500 1718427 44390 O 1674037W O 352.2 ae: Cc oO 0 oO 0 oO oO 0 0 0 0 Re ee F 30000 30000 oO oO oO 147851 147951 oO oO oO 33.0 CHISTOCHINA F 535 oO 535 oO oO 475 oO 475 oO oO ozk CORDOVA c 8450 oO 8450 0 oO 17993 QO 17993 0 oO 3.8E ENGLISH BAY c oO oO oO 0 oO oO oO oO oO oO #* GLENNALLEN c 764Z oO 7642 0 oO 13450 O 13450 oO oO 3.5 HOMER ic oO QO 0 oO 0 QO oO oO 0 oO He KENALI c 0 0 0 oO oO oO oO oO eo oO He KODIAK & PT LIGNS c 29875 0 29875 0 oO 6Zz269 oO 62269 oO oO 12.1 LARSEN BAY M 220 0 2Z0 0 0 290 oO 290 0 oO LE OLD HARBOR c 310 oO 310 oO oO 504 oO 504 oO 0 was PAXSON LODGE P 375 0 375 0 0 750 oO 750 oO oO -3E PORT GRAHAM Cc 0 oO 0 0 oO oO oO 0 oO oO He SELDOVIA c 2100 oO 2100 0 oO 447 oO 447 oO 0 ee SEWARD M 5500 0 5500 0 oO oO oO 0 oO oO He VALDEZ ic 22104 12000 7304 2800 0 35941 27026 8915 oO oO 5.4 TOTAI SOUTHCENTRAL 848355 57000 64547 622308 104500 2577871 219267 105093 2253511 O 531.7 GENERATION FROM WASTE, INCLUDED ABOVE 131263 oO QO 131z68 oO TYPE: P-PRIVATE, M-MUNICIPAL, C-COQPERATIVE, F-FEDERAL. E-ESTIMATE, P-FPRELIMINARY W-INCLUDES GENERATION FROM WASTE (SEE NOTE /W/ BELOW). I-PEAK DEMAND INCLUDED IN OTHER JUNEAL! PEAKS AND NOT ADDED SEPARATELY TO REGION TOTAL. OIL--THOUSANDS OF GALLONS, GAS--MILLIONS OF CUBIC FEET, COAL--THOUSANDS OF TONS. GENERATICN FROM WASTE IN AML&F ANCHORAGE-FPALMER : TOTAL = 131268 MWH, HYDRCG = O MWH, GIL = oO GAS = 131262 MWH, COAL = O MWH, WOOD/GIL = O MWH. PEAK DEMAND AT THIS LOCATION IS INCLUDED ABOVE IN THE LITILITY WITH THE SAME SYMBOL, REGARDLESS OF REGION. CEA PEAK INCLUDES DEMAND OF HEA (62.8 MW), MEA (76.0 MW), AND SES (5.7 MW). APA MWH, 8/1983 Gif /2/ 13/ /4/ /3/ UTILITY INSTALLED NAMEPLATE CAPACITY, NET GENERATION, PEAK DEMAND, AND FUEL USE BY LOCATION, 1982 TYPE: P-PRIVATE, M-MUNICIPAL, C-COOPERATIVE, F-FEDERAL. E-ESTIMATE, P-PRELIMINARY, W-INCLUDES GENERATION FROM WASTE (SEE NOTE /W/ BELOW). I-PEAK DEMAND INCLUDED IN OTHER JUNEAU PEAKS AND NOT ADDED SEPARATELY TO REGION TOTAL. QIL--THOUSANDS OF GALLONS, GAS--MILLIONS OF CUBIC FEET, COAL--THOUSANDS OF TONS. PEAK DEMAND AT THIS LOCATION IS INCLUDED ABOVE IN THE UTILITY WITH THE SAME SYMBOL, REGARDLESS OF REGION. APA 8/1983 YUKON AREA UTILITY INSTALLED /4/ a NAMEPLATE _CAPACITY--KW ______ ___________NET_GENERATION - MWH PEAK ___FUEL USE_/5/___ Tage Diesel Gas Steam /2/ /3/ DEMAND ail Gas Coal Location Ivee TIetal Hydro _(IC)_ Turbine Turbine Tetal Hydro Qil Gas Coal _MW = KGal MMCF KTon ALAKANUK c 650 oO 650 oO 0 752 0 ley oO oO a 74 0 ° ANVIK c 150 oO 150 o 0 192 oO 192 o oO aids BL 0 o BETTLES P 600 0 600 0 0 1140 Oo 1140 0 oO -2E 120 oO ° CHEVAK c 810 ° 810 oO ° 685 oO 685 o 0 ee. 76 oO oO DOT LAKE P 200 ° 200 ° oO 300 ° 300 ° o -iP 27 ° ° EMMONAK c 475 ° 475 o o 770 oO 770 oO o 2 87 ° oO FAIRBANKS AREA M 67850 O 8250 31100 28500 163300 Oo -487 0 163787 26.5 24 oO 172 Ee Cc 216891 O 21625 170z66 25000 316357 0 120688. 0195669 67.9 13154 Oo 164 FT YUKON P 1350 Oo 1350 ° ° 2129 oO 2129 o o “6 200 o ° GALENA P 760 Qo 760 o o 1106 Oo 1106 ° o -3E 128 oO ° GRAYLING c 200 o 200 0 oO 314 0 314 o 0 ck 36 o ° HOLY CROSS c 235 oO 235 oO o 346 0 346 oO o eal! 46 0 o HOOPER BAY c 775 oO 775 oO oO 1025 Oo 1025 0 oO 2 85 0 o HUSLIA ce ze5 oO 285 0 o 347 oO 347 oO o i 46 o 0 KALTAG © 180 oO 180 ° 0 398 o 398 o oO az, 55 o ° LAKE MINCHLIMINA P 130 oO 130 oO o 200 oO 200 o oO -1E ze o oO MANLEY HOT SPRINGS PF 185 ° 185 o ° 150 oO 150 oO oO -1E 12 ° oO MARSHALL c 215 o 215 o oO 483 o 483 o 0 aa! 51 o ° MINTO c 215 ° 215 ° oO 260 ° 260 0 oO ok 36 oO ° MT VILLAGE Cc 650 o 650 o o 1390 Oo 1390 o oO “3 124 ° ° NORTHWAY P 920 oO 920 oO oO 1310 QO 1310 oO oO -4E 100 oO oO NULATG c 725 oO 725 0 oO 680 0 680 oO o wll a1 oO ° PILOT STATION e 216 ° 216 oO 0 551 oO 551 0 0 2 57 oO ° 5ST MARY’S c 1500 Oo 1500 o ° 1972 oO 1972 oO 0 4 163 oO oO PITKAS POINT ° ° 0 ° ° ° ° o oO o -O+ oO o o ANDREAFSKI oO o ° ° oO °o ° o ° 0 -O+ o o ° SCAMMON BAY c 185 ° 185 o oO 359 ° 359 oO ° eal 43 oO oO SHAGELUK G 200 ° 200 o oO 223 ° 223 o o nS 29 o ° TANANA P 1950 Oo 1950 o ° 1780 Oo 1780 oO oO -4E 152 ° o TOK P 2275 Oo 2275 o ° 7139 Oo 7139 oO o 1.2P 573 o oO TOTAL YUKON 300777 0 45911 201366 52500 505658 O 146202 0 359456 101.0 15636 0 336 UTILITY INSTALLED NAMEPLATE CAPACITY, NET GENERATION, PEAK DEMAND, AND FUEL USE BY LOCATION, 1992 ARCTIC AND NORTHWEST AREA UTILITY INSTALLED /4/ eh NAMEPLATE CAPACTTY=-KW oo WL NET GENERATION -_MWH ______. PEAK ___FUEL USE /5/___ Sym- Fi Diesel Gas Steam /2/ /3/ TEMAND ail Gas Coal bol. Location Type Tetal Hydro _(IC)_ Turbine Turbine Total Hydro Oil Gas Coal _MW KGal MMCF KTon AVEC AMBLER Cc 420 0 4z0 0 0 412 0 4iz 0 0 a2 46 ° ° NSBPL ANAKTUVAK PASS c 920 0 930 0 0 1100 Oo 1100 0 0 4 98 oO 0 NSBPL ATKASOOK CG 300 ° 300 0 ° 48g 0 489 ° 0 LE Zz 0 0 BUXEC: BARROW Cc 6950 0 450 6500 ° 22822 0 0 Z22822 0 4.0 0 400 0 AUI DEADHORSE P 6100 Oo 6100 0 0 152344 Oo 15344 ° 0 3.0E 1422 0 0 AVEC ELIM Cc 231 0 231 0 ° 413 0 413 0 0 na. 49 0 ° AVEC GAMBELL c 460 0 460 ° 0 821 0 821 ° ° 2 a6 0 0 NSBPL KAKTOVIK c 655 0 655 0 oO 800 0 800 0 0 -3E 74 0 0 AVEC KIANA c 650 0 650 0 0 79L 0 TIL 0 0 rs 75 0 0 AVEC KIVALINA fc 460 0 460 0 0 463 0 463 0 0 wa 58 0 0 KtEA KOTZEBUE Cc 4825 Oo 3025 1800 oO 12249 oO 12249 oO 0 2.2 ||| 1194 0 ° AVEC KOYUK C 270 0 270 0 0 370 0 370 0 ° mit 4z 0 0 AVEC NCIATAK c 250 0 350 0 ° 550 0 550 oO ° at 62 ° ° NJUB NOME M 6968 Oo 6968 0 0 17511 O 17511 0 ° 3.1E 1372 ° 0 AVEC NOORVIK c 600 0 600 0 0 1023 0 1023 ° 0 2 30 0 0 NSEPL NUIQSUT Cc 720 ° 720 0 ° 550 ° 550 0 oO -2E 51 0 ° NSBPL POINT HOPE c 930 0 930 0 oO 1625 Oo 162 ° ° ES 170 0 0 NSBPL POINT LAY c 400 0 400 0 0 450 0 450 0 ° -1E 40 0 0 AVEC ST MICHAEL c 340 0 340 0 ° 556 ° 556 oO 0 gt 4g 0 ° AVEC SAVOONGA c 650 0 650 0 0 830 0 390 0 oO a2 S41 0 ° AVEC SELAWIK Cc 650 ° 650 oO 0 810 0 810 oO 0 2 az 0 ° AVEC SHAKTOOLIK c 200 0 200 0 oO 314 0 314 0 0 ai 38 ° ° AVEC SHISMAREF c 705 ° 705 0 0 689 ° 689 oO 0 AZ 76 0 ° AVEC SHUNGNAK c 580 0 580 0 0 569 ° 569 0 ° a 59 0 ° AVEC STEBBINS Cc 220 0 220 0 oO 395 0 395 0 0 al 58 0 oO TePC TELLER P 445 0 445 0 0 583 0 583 0 ° -1E 46 0 ° MEA UNALAKLEET c 1150 Oo 1150 0 0 2668 O 2668 0 oO .5E 235 0 0 NSBPL WAINWRIGHT c 1060 0 1060 0 0 1400 Oo 1400 0 0 SE 128 0 0 AVEC WALES c 155 ° 155 0 o 156 0 156 oO ° 10+ 22 0 0 TOTAL ARCTIC AND NORTHWEST 38374 0 30074 8300 6 86813 0 63991 22822 0 1675 “5845 ~~" 400 “0 /1/ TYPE: P-PRIVATE, M-MUNICIPAL, C-COOPERATIVE, F-FEDERAL. /2/ €E-ESTIMATE, P-PRELIMINARY, /3/ W-INCLUDES GENERATION FROM WASTE (SEE NOTE /W/ BELOW). /4/ T-PEAK DEMAND INCLUDED IN OTHER JUNEAU PEAKS AND NOT ADDED SEPARATELY TO REGION TOTAL. /5/ OQIL--THOUSANDS OF GALLONS, GAS--MILLIONS OF CUBIC FEET, COAL--THOUSANDS OF TONS. * PEAK DEMAND AT THIS LOCATION IS INCLUDED ABOVE IN THE UTILITY WITH THE SAME SYMBOL, REGARDLESS OF REGION. He CEA PEAK INCLUDES DEMAND OF HEA (62.8 MW), MEA (76.0 MW), AND SES (5.7 MW). APA 8/1983 UTILITY INSTALLED NAMEPLATE CAPACITY, NET GENERATION, PEAK DEMAND, AND FUEL USE BY LOCATION, 1982 SOUTHWEST AREA UTILITY INSTALLED /4/ voneea NAMEPLATE _CAPACITY--KW NET_GENERATION - MWH PEAK ___FUEL USE /5/___ Sym- J1/ Diesel Gas Steam /3/ DEMAND oil Gas Coal bol. Location Tzee Ietal Hzdre (IC) Turbine Turbine Hydro Oil Gas Coal _MW KGal MMCF KTon APC = ANIAK P 1260 Oo 1260 oO ° Oo 1346 0 ° +3 116 o ° BUC = BETHEL P 8400 Oo 3400 ° oO O 22244 oO 0 4.0 1812 oO oO NP&E COLD BAY P 1525 Oo 1525 oO o 0 2800 oO oO aT 218 0 0 NEC [DTLLINGHAM c 3850 Oo 3850 ° 0 Oo 10258 0 oO 1.9 757 oO ° NEC ALEKNAGIK 0 ° oO ° 0 oO ° ° o * oO ° oO AVEC EEK c 206 ° 206 oO o ° 402 o ° <i 49 ° 0 AVEC GOODNEWS BAY c 150 oO 150 oO 0 0 367 ° oO a 38 ° oO I-NEC ILIAMNA c 125 oO 125 oO ° oO 245 o oO LE oF ° oO I-NEC = NEWHALEN c 150 ° 150 o oO ° 100 ° ° -O+ 12 0 ° I-NEC —NONDALTEN c 150 ° 150 oO ° ° 100 oO oO -O+ iz ° o AVEC KALSKAG, LOWER c 335 0 335 oO oO ° 512 ° ° at 56 ° ° AVEC KALSKAG, UPPER o ° o ° o 0 Oo o 0 0 oO 0 ° KI KWETHLUK M 560 ° 560 oO oO oO 400 oO oO -1E 40 oO oO COM = MANOKOTAK M 600 0 600 oO oO oO 300 0 ° LE 30 oO ° MGL&P MCGRATH P 1250 Oo 1250 0 oO Oo 2789 oO ° -6E 238 ° oO AVEC MEKORYUK c 275 ° 275 o oO o 501 oO oO ol 49 o o NEA NAKNEK c 6170 Oo 6170 oO 0 Oo 13964 ° ° 3.0 1007 oO ° NEA EGEGIK e 135 ° 135 ° oO ° 175 o oO * 1s ° oO NaC = NAPAKIAK P 300 0 300 ° oO oO 500 o oO .ZE 6z oO o AVEC NEW STUYAHCIK : z60 0 260 oO oO 0 388 oO 0 eh 43 oO oO NiP&lL NIKOLSKI P 110 0 110 oO oO oO 161 o ° -1E 20 oO o AVEC NUNAPITCHUK c 350 0 350 oO o Oo 1067 0 ° ua 36 oO o AVEC KASIGLUK 0 ° ° oO oO 0 oO ° ° al ° oO ° AVEC GUINHAGAK c 310 ° 310 oO o ° 677 o oO ok 80 o oO PUC SAND POINT P 3250 0 3250 0 oO O 6121 ° ° 1.4E 471 ° oO AVEC TOGIAK c 460 ° 460 oO 0 ° 977 oO ° 2 80 ° ° AVEC TOKSOOK BAY c 390 ° 390 O ° 0 411 o ° od. 58 o ° AVEC TUNLUNAK c 125 oO 125 oO o ° 442, oO 0 ad 51 ° ° UE UNALASKA M 1500 Oo 1500 0 oO Oo 1800 ° oO 1.4E 180 oO 0 TOTAL SOUTHWEST 0 0 0 68953 0 o TOTAL ALASKA 1412504 154180 250850 949474 158000 2712547 «584548 492210 2276333 359456 758.6 43156 30513 336 GENERATION FROM WASTE, INCLUDED ABOVE 131268 ° O 131268 0 /1/ /2/ 13/ 74/7 /3/ * ee TYPE: P-PRIVATE, M-MUNICIPAL, C-COGPERATIVE, F-FEDERAL. E-ESTIMATE, P-PRELIMINARY, W-INCLUDES GENERATIGN FROM WASTE (SEE NOTE /W/ BELOW). I-PEAK DEMAND INCLUDED IN OTHER JUNEAU PEAKS AND NOT ADDED SEPARATELY TO REGION TOTAL. OIL--THOUSANDS OF GALLONS, GAS--MILLIONS GF CUBIC FEET, COAL--THOUSANDS OF TONS. PEAK DEMAND AT THIS LOCATION IS INCLUDED ABOVE IN THE UTILITY WITH THE SAME SYMBOL, REGARDLESS OF REGION. “EA PEAK INCLUDES DEMAND OF HEA (62.8 MW), MEA (76.0 MW), AND SES (5.7 MW). APA 8/1983 ALASKA_UTILITIES LOAD DATA AND INSTALLED CAPACITY +1100 | ! | 1 I 82% Installed Capacity Pacha P (% of State Total) | a | + 300 Ww ! ! E R t 800 | M + 700 W ! #1 Monthly Peaks | t 600 | t 500 \' te / + 400 o ot | t 300 | od | Average Power t 200 | a pee yeep een heen tne +t JF MANS J ASONDIF NANT JASONDJFMAMTJASONDIF NAM TASONDIF MANS JASONDJF HAMS JASONDIFMANS JASONDJF HAM JASONDIF MAT JASOND 1974 1975 1976 1977 1978 1979 1980 1981 1982 LEGEND -- (-—) INSTALLED CAPACITY EAR (*) MONTHLY PEAKS (o) AVERAGE POWER NOTE Itilities included: AEL&P, APA-S, GHEA, KP" Utilities inclu ep QPATB SHE! u FMU, GVEA APA - 8/ 1983 REGIONAL SUMMARY ALASKA CAPACITY AND NET GENERATION 1980, 1981, 1982 * 1980 1980 * 1981 1981 1980-1981 * 1982 1982 1981-1982 * CAPACITY NET GEN ¥* CAPACITY NET GEN GROWTH * CAPACITY NET GEN GROWTH REGION/Sector * KW MWH * KW MWH % * KW MWH 2 HEME TE TE TE HEHE FE ETE TE HEHE FETE EE HEHE HEHE HE FETE IE HE HEHE HE HE TE HE HE ETE FETE FE TE FETE HE HE FETE TE TE TE TE HE TE HE TE TE SE TE HE TE FE TE TE TE FETE TE TE TE HEHE TE TE HE TEE TE TE TE TE TE FE FE TE TET TE TE TE FETE ETE TE TE TE FETE TEE HE TE HE HE TE FE FE FE FE TE TE TE FE FE FE FE FE TE IE TE FE ETE TE FE FEE HEHE EEE: SOUTHEAST * * * Utility * 174082 365355 * 174097 401982 10.0 * 192802 481408 19.8 Industrial * 66075 310620 * 71125 310620 0 * 71762 313505 9 Total * 240157 675975 * 245222 712602 5.4 * 264564 794913 11.6 * * * SOUTHCENTRAL * * * Utility * 750298 2234790 * 836355 2305825 3.2 * 848355 2577871 11.8 Nat. Der. * 55726 155946 * 58726 153510 -1.6 * 58726 15081z Sle Industrial * 114735 390702 * 117410 362770 te * 119445 340701 -6.1 Total * 920809 2781438 * 1012491 2822105 1.5 * 1026526 3069384 8.8 * * * YUKON He * * Utility * 299382 45072z * 300102 449228 -.3 * 300777 505658 12.6 Nat. Def. * 86625 207031 * 83125 207531 “Zz * 83125 207533 0 Industrial * 23825 59618 * 33425 59896 5 * 33625 69323 15.7 Total * 409832 717371 * 416652 716655 ave. * 417527 782514 9.2 * * * ARCTIC-NORTHWEST * * * Utility * 27824 63936 * 38234 71665 12.1 * 38374 86813 21.1 Nat. Def. * 6940 18255 * 63940 18255 a] * 6940 14255 =2u.9 Intustrial * 228250 598620 * 226650 673764 12.6 * 236400 733126 8.8 Total * 263014 680811 * 271824 763684 izee * 281714 834194 9.2 * * * SOUTHWEST * * * Utility * 28296 54733 * 30046 59865 9.4 * 32196 68953 15.2 Nat. Def. * 56550 119298 * 56550 114531 -4.0 * 56948 117320 2.4 Total * 84846 174031 * 86596 174396 2 * 89144 186273 6.3 * * * ALASKA Be * * Utility * 1279882 3169536 * 13782834 3288565 3.8 * 1412504 3720703 Loot Nat. Des. * 205841 500530 * 205341 493827 -1.3 * 205739 489920 -.8 Industrial * 432935 1359560 * 448610 1407050 3.5 * 461232 1456655 3.5 Miscellaneous * 44800 81900 * 44800 81900 -0 * 39300 73500 -10.2 Total * 1963458 5111526 * 2077585 5271342 3.1 * 2118775 5740778 8.9 ALASKA POWER ADMINISTRATION 98/83 ENERGY AND POWER DATA — INSTALLED NET orp ain Fel 'C @ 0 e kt eke CAPACITY ______ GENERATION SOUTREAST RW) TRARY OFiTIty = Juneau 90732 ZIeEZO Ketchikan 28750 96052 Haines 4120 8320 Petersburg 7100 21314 Wrangell 7745 12856 Sitka 32640 82849 Other Southeast __ZLe6S 48807 Total I5zZ802 AB1408 Industrial - Total(e) Ea ZG2 312505 TOTAL SOUTHEAST. aa 794512 __ SOUTHCENTRAL Otility ~ Anch/Cook Inlet 771244 2445752 Glennallen/Valdez 29746 49391 Kodiak 29875 82269 Gther Southcentral 17430 20453 Total "248355 2577871 National Defense - Anch. Areale) 49726 132130 Kodiak Area __, 3000 __ 18682 Total 58726 150812 Industrial - No. Kenai 25630 129557 Valdez 40000 35000 Other _ 23815 176144 Total LTi3445 340701 TOTAL SQUTHCENTRAL OZ 85 26_____ 3069384 _ YUKON Otility - Fairbanks Area 2284741 479657 Other Yukon __ 16036 __ 26001 Total 300777 505658 National Defense - Fairbanks Areale) 73500 181527 Other Yukon e) __ 3825 __ 26006 Total B2125 207533 _~ 33625 _ 89323 pieeessasseesseese er aI7s27_____7Be5TS 6950 22822 Kotzebue 4925 12249 Nome S968 EAST Other Arctic—NW 19631 34231 Total 38374 BESIS National Defense - Barrow(e) 4000 Other Arctic-NW(e) 10255 Total 14255 Industrial -- Total 733126 TOTAL ARCTIC-NORTHWEST o_o BEPTA OT B2a154 SOUTHWEST Otility - Bethel 8400 22244 Dillingham 22850 10258 Naknek 8305 14139 Other Southwest 13641 22312 Total 32156 685953 National Defense -— Total(e) __56948 117320 TOTAL SOUTHWEST oo 99144. ag6273__ TOTAL ALASKA Ota ity 1412504 3720703 National Defense 205739 429920 Industrial — 461232 1456655 Misc. (Not included above) 39300 73500 TOTAL seni h spite ets et eeeee CTT E77 90 eee 5730778 __ estimate APA 8/82 INSTALLED CAPACITY DATA SRT UES OY a a RE ST n 198Z INSTALLED CAPACITY BY FUEL ~- MW ‘HYDRO =__GAS___OTL. CGAL =: WOOD OTL UTILITIES SOUTHEAST S72 ae 95.6 =O) 0 SOUTHCENTRAL $7.0 724.0 67.3 -O a0 YUKON 20 0 247.3 53°55 eo. ARCTIC-NORTHWEST ao 7a 31.4 «0 20 SOUTHWEST 0 0 oe ae 0 00 ALASKA 154.2 731.0 473.8 33.5 20 INDUSTRIAL SOUTHEAST 0 0 5.0 0 66.8 SOUTHCENTRAL 0 60.5 59.0. 0 «0 YUKON 0 me 20.6 13.0 0 ARCTIC-NGRTHWEST 20 183.2 $3.2 0 20 ALASKA 0 243.7 137.8 13.0 66.8 NATICNAL DEFENSE SGUTHCENTRAL, -O 40.5 18.2 re) 20 YUKON =O 0 23.6 Sao me ARCTIC-NORTHWEST -0 S20 3.9 a) «0 SOUTHWEST 0 a0) 36.9 =o 0 ALASKA ao 43.5 102.6 59.5 mG TOTAL ALASKA SOUTHEAST $7.32 0 100.6 a0 66.8 SOUTHCENTRAL, 57.0 825.0 144.5 0 0 YUKON 0 -O 291.5 126.0 a ARCTIC-NORTHWEST 0 193.2 88.5 0 20 SOUTHWEST a0 0 89. 0 0 misc. 0 0 39.3 -O sO ALASKA 154.2 Lele TZ Tadeo 126.0 66.8 (1) The Southeast pulp mill wood/oil fuel is more than 1/3 oil. 71.8 119.4 33.6 236.4 461.2 ou GO GHW co aD yi wwohN 264.6 1026.5 417.5 281.7 89.1 39.3 2118.7 (Z) Anchorage waste heat steam turbines are included in gas for fuel. el 83.1 114.2 75.3 78.0 89.1 39.3 479.0 PRIME MOVER ~ MW ST TOTAL 66.8 71.8 37.5 119.4 13.0 33.6 0 236.4 117.3 461.2 44.5 58.7 59.5 82.1 0 6.9 -0 56.9 104.0 205.6 66.8 167.4 186.5 969.5 126.0 417.5 0 281.7 +0 89.1 0 39.3 379.3 1964.5 264.6 1026.5 417.5 281.7 89.1 39.3 2118.7 8/ 1983 ALASKA UTILITY INSTALLED CAPACITY TYPE ACCUMULATIVE NAMEPLATE RATINGS BY YEAR c A Pp A Cc I T Y | ! + | | + 1 x 1 ! . ! 1 x | ' / | x yo" JL * / *—* | 1 x —-— + 7 *— | x 1 DIESEL ! x a ‘ | ee po — * / | — +o 4—t* + Zig ye === | i a STEAM o AF — #—— 4 4A—— 4 4 | a to 1 o—o—_ 0 0 0 __0__0 —— t Oh: eC) eC) ee) es C2) 9 =>? ae | HYDRO | + ttn non bt ttt tt $$ $$ $4 tt 1958 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 739 8O BL B82 YEAR LEGEND -- (o) HYDRO (4) STEAM + HYDRO (*) DIESEL + STEAM + HYDIRG (x) GAS TURBINE + DIESEL + STEAM + HYDRO APA - S/ 1983 600 500 400 } 300 200 100 1972 1973 ALASKA ELECTRIC POWER INSTALLED CAPACITY 54600 (48%) 60225 (49%) 60225 (49%) 82225 (S52) 82300 (48%) 82300 (412) 82300 (38%) 82225 (34%) 82225 (32%) 76600 (29%) 78700 (23%) 76600 (222) 76600 (19%) 75275 (16%) 74275 (14%) 121000 (19%) 122260 (17%) 122535 (162%) 123235 (13%) 122460 (12%) 122460 (11%) 123310 (10%) 123310 (10%) 123640 ( 9”) 154180 (11%) Nameplate Ratings in Kilowatts (32%) 35575 (314%) 35575 (29%) 32875 (27%) 32875 (22%) 32875 (19%) 32875 (16%) 32750 (15%) 32750 (13%) 32750 (13%) 32750 (13%) 54750 (16%) 54750 (16%) 74750 (18%) 68250 (14%) 68250 (13%) 68250 (10%) 68000 ( 9”) 68000 ( 9x) 88000 ( 7a) 68000 ( 7H) 68000 ( 6”) 101000 ( 8H) 101000 ( Sh) 158000 (11%) 158000 (11%) 19738 (20%) 21628 (19%) 24534 (21%) 26079 (21%) 29459 (24%) 33595 (23%) 41993 (25%) 47368 (23%) 49482 (23%) 59437 (24%) 69273 (27%) 81023 (31%) 89538 (26%) 38963 (28%) 123256 (30%) 140627 (30%) 144975 (27%) 147700 (23%) 148054 (21%) 176706 (23%) 205110 (21%) 221251 (21%) 219831 (19%) 231506 (18%) 233198 (18%) 247720 (18%) 250850 (18%) Utilities and Various Other. Sources: Gas Turbine 12800 ( 8%) 39700 (20%) 54050 (25%) 68400 (28%) 693900 (282) 69900 (272%) 116700 (34%) 116700 (342%) 131990 (33%) 188803 (40%) 246139 (462) 313100 (48%) 385324 (53%) 396257 (32%) 575454 (39%) 624074 (60%) 719814 (64%) 799114 (64%) 822374 (642%) 849474 (622) 849474 (60%) Utilities 100318 111803 114709 121873 122559 148695 iss968 202243 218582 242812 254148 260273 339688 347013 406596 472955 533633 850100 723638 763498 9717399 1035785 1130105 12543930 1279882 1378834 1412504 APA 8/1983 Non- Utilities 247000 255400 257000 262600 295100 303600 303500 304200 303300 279200 284100 287300 303500 344500 355100 354900 387700 376100 411900 403654 469504 611056 655826 656726 683576 698751 706271 5 1 OmMCCDpaAwiZH EZ <AHODVDO +O * TOTAL INSTALLED CAPACITY UTILITY AND NON-UTILITY National Defense included in non-utility | ! fr ! 2000+ VA +2000 co | | ail | 1800+ ALASKA TOTAL ye +1800 + | | | | | A | 1600+ 4 | ‘ | Port hil UTILITY |_| —-* 14 | | | | | + 1 1200+ “ue +1200 | + | 1 * | | | 1000+ i 1.1000 + * + 3 YA la | + | 1 + I 800+ Li + 800 7 - | ! cae | rs NON-UTILITY 1 o—9 — Oo | vA ne 1 600+ * o + 600 / a 1 —T — 1 | Jee J 1 400 | awe o—om + 400 +$—— + va, LO om ! 1 ey #— #7 90 | | aay 1 1 lt oar) NATIONAL DEFENSE 1 Z00+4+ —+ _*—* _? X——x—— x —— *— x + 200 l 22S SS x, x x xX. x: x x x xx | *——*—* | 1 | O+ + 0 trate tt $$ $$ - 1958 59 60 Gl 6Z G3 64 65 GE 6 68 69 70 71 72 73 74 75 76 77 #78 79 80 81 82 YEAR UTILITY NON-UTILITY NATIONAL DEFENSE ALASKA TOTAL APA - &/ 1983 State Subdivision Southeast Southcentral Yukon Arctic and Northwest Southwest ALASKA 1982 INSTALLED NAMEPLATE CAPACITY Type of Private Municipal Coop. Federal TOTAL Private Municipal Coop. Federal TOTAL Private Municipal Coop. TOTAL Private Municipal Coop. TOTAL Private Municipal Coop. TOTAL Private Municipal Coop. Federal TOTAL REGIONAL SUMMARY UTILITIES Total Hy dro MW =e 54.4 9.2 82.9 40.8 8.3 0 ~-42+2 42.2 192.8 97.2 ae) 0 239.2 0 578.3 27.0 ~-39+9 30.9 848.4 57.0 8.4 «0 67.9 0 ~224.6 ~--22 300.8 -0 6.5 -O 7.0 +O 2423 --~+2 38.4 «0 16.1 0 2.7 +O --13-4 ae 32.2 0 86.3 Sez 399.6 40.8 849.4 27.0 ~ 2722 2722 1412.5 154.2 55.7 ‘ Gl >! 1 SIN AN Oe el ee 1 ge IanO Be WN NIPNE FIGSOU WIDWS UIC Uo Wik Oo NIOND Gas Turbine ee 17.5 0 0 aad 0 17.5 229.3 602.7 alee 849.5 20 61.5 96.5 aie 158.0 Note: Federal classification applies only to Eklutna and Snettisham powerplants which supply wholesale energy to utilities. Sources: FPC, APUC, APA. APA 8 /1983 INSTALLED CAPACITY SUMMARY MW National Other 2/ Total Total 3/ Alaska Year Defense 1/_ Non-Utility Non-Utility Utility Total_ 1956 197.0 50.0 247.0 100.3 347.3 1957 205.5 49.9 255.4 111.8 367.2 1958 207.0 50.0 257.0 114.7 Wis? 1959 212.6 50.0 262.6 121.9 384.5 1960 245.1 50.0 295.1 122.6 417.7 1961 251.4 52.1 303.6 148.7 452.3 196z 251.5 52.0 303.5 170.0 473.5 1963 252.2 52.0 304.2 202.2 506.4 1964 245.4 58.8 303.9 218.6 522.5 1965 216.3 62.9 279.2 242.8 522.0 1966 217.8 66.3 284.1 254.1 538.2 1967 221.0 66.3 287.3 260.3 547.6 1968 239.7 63.8 303.5 339.7 643.2 1969 243.7 100.7 344.5 347.0 691.5 1970 252.4 102.7 355.1 406.6 761.7 1971 252.41 102.7 354.9 473.0 827.9 1972 256.9 130.9 387.7 533.6 921.3 1973 244.6 131.5 376.1 650.1 1026.2 1974 245.4 166.5 411.9 723.6 1125.5 1975 224.7 179.0 4/ 403.7 763.5 1167.2 1976 208.7 260.8 4/ 469.5 971.8 1441.3 1977 198.6 412.4 611.1 1035.8 1646.8 1978 205.8 450.0 655.8 1130.1 1785.9 1979 205.8 450.9 656.7 1254.9 1911.7 1980 205.8 477.7 683.6 1279.9 1963.5 1981 205.3 493.4 698.8 1378.8 2077.6 1982 205.7 500.5 706.3 1412.5 2118.8 1/ National Defense includes USAF, USA, USN, USCG. 2/ Other Non-Utility includes private industry and State and Federal government (excluding APA). 3/ Utility totals include APA capacity at Eklutna and Snettisham. 4/ Does not include temporary pipeline activity installations (about 60 MW for construction camps, etc.) Sources: various APA 8 /83 REGION SOUTHEAST USN & USCG TOTAL YUKON ARMY USAF TOTAL USAF USN & USCG TOTAL SOUTHWEST USN & USCG TOTAL ASKA_ TOTAL ARMY USAF USN & USCG TOTAL SUMMARY ~ NATIONAL DEFENSE INSTALLED CAPACITY IN ALASKA (KW) Diesel GTurb Steam TOTAL_ Diesel GTurb_ Steam TOTAL _ Diesel GTurb Steam TOTAL All installations leased to private industry. 7226 0 =18000 25226 7226 0 18000 25226 7226 000000 18000. 25z26 2000 0 22500 24500 2000 0 22500 24500 2000 0 22500 24500 — 2000 Q _.4000 __3000 --3000, _____ Q 4000 __3000 —— 0 Q 4000 __3000 14226 0 44500 58726 14226 0 44500 58726 14226 ° 44500 = 58726 3000 0 =. 23500 32500 9000 0 22000 31000 3000 o 22000 31000 Sh sl Q _375300 _S21Zz5 24825) _....9 _37500 = _52Z125 24825 __...2 _37502 _S2125 23625 0 61000 84625 23625 0 “59500 83125 23625 0 59500 83125 3940 o 0 3940 3940 0 0 3940 0 ° w-22-2 --3200 _____! Q _-3000 Se eet el ee Oe O00 eee 3940 3000 0 6940 3940 3000 ° 3940 3000 0 32150 0 0 32150 32548 0 o 32548 32548 o Oo 32548 =64400 Q ----2 _24400 =68400 Ceo Q _24400 eee oe Q _24400 56550 0 ° 56550 56948 0 Oo 56948 56948, oO Oo 56948 16226 OQ 41500 57726 16226 0 40000 56226 16226 0 40000 = 56226 52715 0 60000 112715 53113 0 60000 113113 53113 o 60000 113113 -22400 =__3000 __4000 36400 -22400 __3000 _ 4000 _36400 -22400 = __3000 __4000 _36400 98341 3000 105500 206841 98739 3000 104000 86205739 98739 3000 104000 205739 APA - 8/ 1983 GENERATION DATA BR SPAN HAR LA RE SY 21 UTILITIES SOUTHEAST SOUTHCENTRAL YUKON ARCTIC-NORTHWEST SOUTHWEST ALASKA INDUSTRIAL SOUTHEAST SOUTHCENTRAL YUKON ARCTIC-NORTHWEST ALASKA NATIONAL DEFENSE SOUTHCENTRAL YUKON ARCTIC--NORTHWEST SOUTHWEST ALASKA TOTAL ALASKA SOUTHEAST SOUTHCENTRAL YUKON ARCTIC—NORTHWEST SOUTHWEST MISC. ALASKA 1982 NET GENERATION BY FUEL - GWH --91L_ _COAL_ 108.0 +0 105.4 -0 146.2 359.5 64.0 0 69.0 +0 2.3 0 57.7 20 39.3 30.0 35.6 0 134.9 30.0 18.7 0 26.1 181.4 10.3 0 117.3 0 172.4 181.4 110.3 0 181.5 -O 211.6 570.9 109.9 0 186.3 -0 73.5 +0 873.1 570.9 319.4 (1) The Southeast pulp mill wood/oil fuel is more than 1/3 oil. (Z) Anchorage waste heat steam turbines are included in gas for fuel. £2 —TOTAL 481.4 2877.9 505.7 86.8 69.0 3720.8 313.5 340.7 69.3 733.1 1456.6 150.8 207.5 14.3 117.3 489.9 794.9 3063.4 782.5 834.2 186.3 73.5 5740.8 20 2076.7 117.6 25.5 0 2219.8 0 201.4 27.3 715.2 943.9 118.4 213.6 65.6 89.7 186.3 73.5 747.1 PRIME MOVER — GWH -0 86.8 0 69.0 537.4 3136.2 311.2 313.5 35.0 340.7 30.0 69.3 +O 733.1 376.2 1456.6 146.6 150.8 181.4 207.5 -0 14.3 +0 117.3 328.0 489.9 311.2 429.6 358.4 2850.1 572.0 782.5 0 834.2 0 186.3 +0 73.5 1241.6 5156.2 0 <0 0 0 +0 584.6 APA - 313.5 340.7 69.3 733.1 1456.6 150.8 207.5 14.3 117.3 483.9 794.9 3063.4 782.5 834.2 186.3 73.5 5740.8 8/ 1983 vz ANNUAL UTILITY GENERATION DATA BY REGION 1 | > i | I g 3300+ / ‘ N | ALASKA a \ R 1 7 el | ‘ ul a as ; a I ; * | N | 2700+ / + 1 1 oO 1 | 0 1 * ol 0 1 2400+ + ™ | ! 7 ; - SOUTHCENTRAL 4° | "wel | o 1 2100+ ae y cer 1 | aoe | 1 1800+ oe i ! ° 1 | / 1500+ + I ©. \ | 1 * 1 1200+ i | I saa ' | ° 1 1 * | Lat 1 bash YUKON T | —x. | I ° | 300+ oe eee on -—s AT ‘ ° 1 — —+! ——— + + ++ + ea | + Opp ppp eg mg ng ARGTIC.HORTHPEST: SOUTEMEST , $ 1960 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 73 80 S1 82 YEAR LEGEND -- (4) — SOUTHEAST (o) - SOUTHCENTRAL (x) — YUKON (+) - ARCTIC NORTHWEST AND SOUTHWEST NOTE (*) - ALASKA TOTAL Taken from 1982 Net Generation Table APA - 8/ 1983 3600 3300 3000 2700 2400 2100 1800 1500 1200 900 D Ss Ss 300 State Subdivision Southeast Southcentral Yukon Z/ Arctic & Northwest Southwest ALASKA Type of Private Municipal Coop. Federal 1/ TOTAL Private Municipal Coop. Federal 1/ TOTAL Private Municipal Coop. Federal 1/ TOTAL Private Municipal Coop. Federal 1/ TOTAL Private Municipal Coop. Federal 1/ TOTAL Private Municipal Coop. 32443 71395 Qo Q 103838 65 10413 53508 187550 251536 2636 39694 43619 36953 124383 99594 148121 190 117961 198543 134855 451349 3652 53179 60519 117350 170 4958 3993 56231 274915 268125 --434855 733926 73620 127996 336 201952 1053 205103 443560 154733 804449 4087 85638 150407 240132 170 8060 7606 87897 427454 611226 ~454233 1281310 ANNUAL ENERGY GENERATED Alaska Utility Systems Regional Summary (MWH) 97589 158440 6033 _-28969 289031 1792 400118 962672 135066 1499648 8587 137186 287804 433577 170 11996 16647 127071 708397 1290717 ~162035 2288220 64106 155647 15352 311445 1201 434480 1281406 ~293623 1920710 4227 133480 364071 501778 5126 13772 26010 101619 738236 1701196 279963 2821014 73950 168250 6240 ~-22209 325649 1230 458800 1412178 180097 2052305 11945 128170 346498 486613 30z0 13915 28766 122175 770233 1809890 252308 2959604 73577 184268 7283 100227 365355 1190 494881 1554434 22347390 13069 112144 325509 450722 9817 15261 38858 130528 808311 1946185 284512 3169536 74870 196188 e622 124302 401982 1190 486801 1595131 222703 2305825 142399 155810 279019 449228 10964 15935 44766 136008 856809 1948743 347005 3288565 74384 237051 9013 iso954 481408 1515 3579474 1849031 147851 2577871 15254 163300 327104 505653 15927 17511 53375 143041 999436 2269421 398805 3720703 Average Annual Growth Average Annual Growth ” 6.38 13.2 11.1 16.0 11.9 a 10.2 5.86 964 16.1 9.86 ‘5.88 1/ Federal classification applies only to Snettisham and Eklutna hydro projects which supply wholesale energy to utilities. Z/ Lower Yukon River Coop. supplied villages changed from Southwest Region to Yukon Region in 1976. (r) - Revised from previous data publications Sources: FPC, REA, APUC, APA. G2 (e) — Estimated. APA 8/1983 92 REGION SOUTHEAST SOUTHCENTRAL USN & USCG TOTAL SOUTHWEST USN & USCG TOTAL USN & USCG TOTAL SUMMARY — NATIONAL DEFENSE GENERATION IN ALASKA (MWH) All installations leased 119298 23 106796 ~49165 155984 0 0 9 On 55700 77073 ~22841 155614 65400 121100 192605 22841 336546 to private industry. 55700 77130 65423 207031 10255 121123 299401 500530 114531 23 100852 152945 54500 77073 19877 151450 65900 115532 120400 192605 19877 332882 54500 77130 -~21882 153510 65923 141608 207531 10255 114531 120423 293457 493827 117320 25 1o17z1 28167 157913 1982 —GTurb Steam 0 55000 0 77073 a Q _14502 O 146575 0 65900 — Q 115532 O 181432 0 0 _-4000 _____0 4000 0 0 0 -----9 ____.9 oO oO OQ 120900 Oo 192605 --4000 _14502 4000 328007 APA - 55000 77130 --18892 150812 65925 141608 117320 120925 294326 489920 8/ 1983 MONTHLY UTILITY GENERATION BY FUEL BIO TTT ; 3390 5 | 1 60+ + 360 1 | | G 330+ + 330 E— 1 1 P| \ maf | | A 300+ x + 300 I x | oO ! x \ x | N | \ 1 270+ x + 270 3 | 1 8 | x x ie / | M 240+ “ / ! / 3 i 240 4 | { x x ‘\ /* | 210% | \ \ vr. ; 210 1 ; i f\ \w x “er . / \/ GAS T 180 1 é i 150+ x ° + 150 “ /\ 3 fi 1204 RK ‘o d } 7 120 P : oo \ | ! f / om ve | 90+ rs Kr OO, ve Vy + 30 | \ po. Vj +4) et i Y is mY / * i} Iba, as od \. [* aN ee x. ya A. ¢ “ ae I ans. %s Vi AN As oN \e | af y ty + 60 \\7 * ae + \a ty wy HYDRO | Aen SS Boe ie RK jee + 30 ee A AR — NPR a pet oie | ! COAL \ “TFMAM] JASONDIF MAMI J ASONDJFHAMJ JASONDIFMANT JASONDIF MAJ TASONDIFMAMTJASONDIFNANTJASONDIFMARIJASONDIFMARTTASOND 1974 1975 1976 1977 1978 i379 19: 198. 1982 YEAR LEGEND -- (*) COAL (+) HYDRO + COAL (o) OIL + HYDRO + COAL 8 OTE (x) GAS + GIL + HYDRO + COAL This graph represents about 90% of statewide generation. APA - 8/ 1983 1974 oil Gas Coal Hydro Total 1975 oil Gas Coal Hydro Total 1976 oil Gas Coal Hydro. Total 1977 oil Gas Coal Hydro Total 1978 oil Gas Coal Hydro Total i979 oil Gas Coal Hydro Total 1980 Oil Gas Coal Hydro. Total 1981 Oil Gas Coal Hydro Total 1982 oil Gas Coal Hydro Total 39 148 27 37 251 45 a7L 31 47 294 43 49 317 SL i178 22 s2 283 59 237 35 6o SOL February 22 96 26 20 164 26 108 28 26 188 38 136 29 23 226 3s isi 24 33 223 41 146 26 44 202 28 23 303 34 163 25 41 263 31 165 29 48 273 56 192 25 48 321 NET GENERATION by FUEL (1000 MWH) March = April Mi Tune July 23 17 12 1 1a 35 35 72 62 70 27 2a 23 2. 20 24a 23 26 23 25 senses) sesame oo =sseee oo sames= 0 saneee 166 146 133 123 126 19 18 13 15 97 93 81 76 26 22 24 25 23 22 28 165 155 144 31 28 24 49 22 136 115 104 93 98 31 26 2. 22 21 34 26 32 28 27 aucmeso suse== oo =amees00o suaee= 0 sese== 229 195 181 162 168 34 26 2a 23 19 148 129 110 7 8a 30 29 26 20 24 38 33 39 39 43 250 217 196 179 174 38 29 23 19 2. 152 132 127 108 110 30 28 20 26 27 33 35 33 41 39 sesse=0o exeee= 0 sesee= 0 eeeees 0 nenees 259 224 209 194 197 29 34 20 23 144 123 117 118 27 18 25 24 39 39 239 241 30 26 37 24 25 169 139 121 114 115 29 27 10 19 20 36 39 47 42 47 264 231 215 199 “207 29 29. 27 20 25 163 150 134 135 137 31 26 25 28 27 50 45 43 35 41 273 250 229 218 230 Sa 31 30 20 29 191 172 158 145 151 34 32 31 27 25 40 48 45 45 47 316 283 264 237 252 132 21 81 23 30 15s 19 100 24 SL 174 21 33 23 4g 186 28 109 24 39 200 26 120 22 37 205 22 113 26 53 214 27 i131 24 49 231 32 is1 24 47 254 September 1s 76 20 22 133 fea 164 20 26 dit 21 30 188 39 102 7 45 193 30 i116 23 38 207 32 122 19 33 24 ize 26 46 224 23 123 27 29 162 27 45 263 Gctober is 93 29 27 164 24 110 29 33 196 28 132 29 34 223 32 132 25 4g 238 32 149 29 39 249 238 148 28 42 246 26 i161 19 40 246 27 169 31 34 281 41 204 28 46 319 November December 19 102 31 36 188 33 128 32 37 230 33 142 28 33 236 43 i168 29 46 286 37 i175 29 37 278 30 160 ian 40 257 31 iss 29 39 288 31 194 33 52 310 42 21s 32 ss 342 APA 204 35 149 33 254 42 iss 40 268 46 191 33 47 317 33 195 30 36 300 42 207 30 47 326 366 38 212 35 s3 338 46 233 34 s2 365 8/1983 203 1047 299 319 1sé6s 277 2502 378 1537 297 498 2710 338 1690 323 463 2864 1844 290 332 3034 338 1897 338 S81 3154 466 2211 354 S76 3607 OWwZWEI-HHOZ 4OOO ESI g g 2 g g 2 2 g g g —— a ee x a lel len ener el fla ! 1 | k | Ss. 18) ! — iF bei fs t ! ! th ig t ie r — at | $3 t | iF | if r —>| zi 8 EEE x Be 1 laa pee ; i Lu El ! | | EE Sp =E ei ~ ei z | @ I 3 ie | ia iE — —+ ig iS | ti 1 tu a eee $------- a $$ -- - - - $4 —+---------+-------=- iL 2 g g 2 g g g g 2 g YEAR 8/ 1983 APA - FAIRBANKS AREA UTILITY NET GENERATION ‘TWELVE MONTH RUNNING TOTALS 3 Ss 3° Ss i=} 8 : 5 g 3 3 —— ne nema ae +2 Fi 18g i" ete t ' —— iS. ao Ea a i i ! i$g | ' a ee 1§ i) is ! | “A LER re | | te +3 18 ge ri . lf — ——+8 iF s io sy Ft ea iE +3 iF ist igs | Gad stent Ae ------- a a ----- ee t ------ -- st 2 : 5 3 : g OCW AZMaAKhHHOZ —coo £3=z YEAR 8/ 1983 APA 30 RUNNING TOTALS--NET GENERATION ANCHORAGE /COOK INLET & FAIRBANKS AREAS i 1981 i 1978 1977 1976 Anchor age/Cook Inlet — 12 month total (GWH) for year ending in Sieleiedsiede ShOMTKMONOON® RESSSERE SEES AA NADNNOOMOREH SRESaNS ATES ANA “ay qnseauneaces BERLESETETEE HONTOONMH TON RRRSRSRELLEE 38! 931 941 939.5 931 Rann ono ne ZaSS aS SEE288 ber uary October February March April May June July August Sep November a J * = ° 2 £ S 3 a 3 % 3} ® = € = 2 o x t 2 < A o g 3 & é o € < 1 Onootenes BOO cs see ss a = SSSSeseNN NOGAAA AAA t44Oena4NHoee AGOTeTHHH OHO DAOROKROKRADOD WNASSSSOddGN BRLANHON HANH HOCNGOHHHTED qteannedaae Bedagadads BAS A AAA Aka Zl 4 =| ‘ » S665 »2 Bos ts eesa3 S32- Sage 3265 orn 32088 Eset net esesy SketEsseds2d — 12 month total (GWH) for year ending in Fairbanks Area ot Denso 38 39833 we TOaMeTOON 28 gh98d99 eteee we ° peters 882 eee ON HHATONNTOO BSE SH83E8 January ONKeANeD Li $33999338 encoon seSeesee8 § ¥, 248 aes Ste Zh8 Bes e33 ” 3 479. ‘ ao BE 5 468.0 ‘ « Nov December - % change of 12 month totals Fairbanks Area anetoo4 Nowedag a HOTHOOMNMMOS Bees a Se eee aces THGONNNGDOGAA eauenookaed? Vodddaaddaa? ADNOHHOKANMD Oy tate tateata renal QHOKAROT OMA TTT TP eh January February March April May 2.9 Tune July August September October November 3 Alaska Power Administration 8-83 uv TRANSMISSION LINES ———————— 33 7 138/345 KV Under Construction Glennallen UNITED STATES DEPARTMENT OF ENERGY ALASKA POWER ADMINISTRATION EXISTING TRANSMISSION SYSTEMS Scale in miles 100 A.PA.- AUGUST 1983 RMI se eM SSeS SSeS ssSsSLeKS SVS SSS sees KsessS SSL VSSSSVSSVLSLsSSsssss sss S SAT: TRANSMISSION LINES AND MAJOR INTERCONNECTIONS (Nete: Lines under 33 KV not included) te SUMMARY Circuit KV Miles Fairbanks 133 LLG 6g az 34.5 42 230 Anchorage-Cook Inlet 138 151 Overhead 133 16 Submarine 115 403 69 &3 34.5, 33 126 773 Other Southcentral 132 104 13.8/69 4 1083 Seutheast 138 41 Overhead 138 3 Submarine eo 36 34.5 25 105 Alaska 132 412 Overhead Lae 13 Submarine LTS 402 69,13.8/69 195 34.5, 33 193 1Z2z2 Seurces: APLC, AFA APA 8/1983 TRANSMISSION LINES AND MAJOR INTERCONNECTIONS (Note: Lines under 33 KV not included) Interconnections 1/ Transmission Lin Designation transmission under construction WML AP Wrangell Lumber mill 6 mi. 1 ' Area ! Substation = en ao = = eae Fairbanks GVEA Healy-Gold Hill 1 U. of Alaska University Gold Hill-Zehnder (2 ckts.) 1 Ft. Wainwright Ft. Wainwright Zehnder-Ft. Wainuwright-Hwy. Pk-Johnson Rd.69 40 | Eielson AFB Eielso Zehnder-Fox 69 6 1 Ft. Greely Ft. Greely Musk Ox-Gold Hill 69 5 1 FMU Zehnder Huy .Pk.-North Pole 63 2 1 North Pole-Ft. Wainwright 138 12 1 Misc. within city 69 s ' Gold Hill-Murehy Dome 34.5 24 1 Fox -Pilot Blug¢ 34.5 18 ' 1 FMU Muni. Pur. Plt.-Zehnder 69 a; 1 Ft. Wainwright 19th Street 1 (See GVEA also) Railbelt APAuth. Willow (Anch.)-Healy (Fbks.) ' under construction ' ' Anchor aae~ MEA Misc. 115 KV 415 40 1 APA Palmer Cook Inlet NW Knik Arm System-Willow 115 20 1 APA Parks Palmer-NW Knik Arm System 415 27 1 APA Reed Palmer-SE Knik Arm System 34.5 28 | APA Eaale River | APA Dow | CEA Teeland 1 APA Ek lutna—Dow-Lucas-Palmer 115 12 1 AMLAP Anchor Ex lutna-Parks-Eagle River- 1 AMLaP City Plant #2 City Plant #2-Anchorage 4/ 115 32 | CEA Anchorage ' AML AP Gen. Sta. #i-Gen. Sta. #2 115 6 1 Elmendors City System APA line tap-2 ckts. thru 1 (See APA also) city-APA Anchorage Sub. 115 12 ' Anchorage APA Sub-City System 34.5 4 1 Misc. sub transmission 34.5 26 1 ' CEA Pt. MacKenzie-W. Terminal 138/230 7 1 (See APA and HEA) W. Terminal-E. Terminal 138/230 4(Submarine Cable) E. Terminal-Fossil Creek-University 4/ 138/230 aa ' Pt. MacKenzie-Teeland (1 ckt.) 138 26 ' Beluga-Pt. MacKenzie (2 ckts.) 138 43 1 Pt. Mackenzie-Pt. Woronzof (4 ckts.) 138 3(Submarine Cable) Pt. Woronzof-International-Univ. Sys. 138 21 ' Anchorage APA Sub-Bernice Lake 2/ 115 169 ' Cooper Lake-Quartz Creek 63 6 ' 2 Lines to Soldotna 3. 69 73 1 Misc. within Greater Anchorage 34.5 60 ' 1 HEA Seldotna-Homer 415 85 1 CEA Kasilos Kenai Area Lines 69 4 1 No. Kenai 115 & 69 KV Systems 33 3 ' leased to CEA & included there. ' ' Other Kaa Kodiak-U.S.C.6. 13.8/69 4 | Coast Guard Kodiak Southcentral ' APAuth Glennallen-Valdez (CVEA to 7-82) 138 104 ' Kodiak-Terror Lake under construction. 1 1 Southeast APA Snettisham-Thane (Juneau) 138 44 (Incl.3 | AELaP Thane mi.Submar- | ine Cable) 1 1 AELAP Thane-Capital Ave. Sub 63 5 1 GHEA Loop Thane-Loop Sub (Mendenhall Valley) 69 17 1 (See also APA & GHEA) 1 GHEA Upper Mendenhall Bridge-Auke Bay— 1 AELSP Brotherhood Bridge Brotherhood Bridge 69 3.5 1 (See also AEL&P) 1 SED Blue Lake-Sitka and thru city 63 5 1 Sitka Pulp Mill Blue L. Green Lake-Blue Lake Tie 69 3 1 1 KPU Silvis Lake-Beaver Falls-Ketchikan | Ketchikan Pulp and thru city to Totem Bight Sub 34.5 25 1 mill Line Tie ' APAuth. Tyee and Swan Lake hydro project ' 1 ' 1 ' 1/ Listed once under substation ownership (The National Defense-owned subs are listed under the interconnected utility). 2/ Incl. spur line to Porta Quartz Creek-Bernice Lake portion (71 mi.) leased from HEA. 2/ Leased from HEA: Soldotna-Quartz-Creek (50 mi.) & Soldotna-Bernice Lake (23 mi.). 4/ Part of the Fossil Creek-University 138/230 KV line is double circuited with part of the APA Exlutna-Anchorage 115 KV line. APAdmin. 8/1983 a2is 41s 115 11s us 11s 138 115 115 41s 34.5 69 13.8 69 13.5 37 MARKET DATA ESTE EE TL Ta TT OE LL TE 39 it] zAomyt o por = 4 SOUTHCENTRAL MONTHLY PEAK LOADS 450+ Pi y N > S - Fe FS —— 2 8 o> N a 9.---$__ => a SN, c a — p= r i y rome SOND FMAM J: ASONDI Ene SOND FMAMI J. ASONDI Bee SONOS FMAMS J. ASONDII FMAM J. ASONDT FMAMI Ji ASONDS FMAMIT: ASOND 1975 197 1977 1973 1980 1981 1982 YEAR APA - 8/ 1983 450 420 390 360 330 270 240 210 180 150 zy p> mm 4 o D ° =z YUKON MONTHLY PEAK LOADS TFMANJ JASONDJFMAMJJASONDJFMAMY J ASONDIJFMAMJJASONDJFMANI JASONDJFMANS JASONDIFMAMJJASONDIFMAMI.JASONDIFMANISASOND 1974 1975 1976 1977 1973 1979 1980 1981 1982 YEAR APA - 8/ 1983 110 + 100 80 70 So 40 o por =z SOUTHEAST MONTHLY PEAK LOADS IFMAMIJASONDIFMAMI J: ASONDIF MAMI, ASONDIFMAMI JASONDIFMAMJ JASONDIFMAMI JASONDIFMAMJ JASONDIFMAMI JASONDJIFMAMI J: ASOND 1974 1975 1976 1977 1978 TS 1980 1981 1982 YEAR APA - 8/ 1983 So 30 REGIONAL PEAK LOADS (MW) Tans -Febs Mac. = flea Baz- Jung = -Julzy Bugs Seeks -Osks Neve Dass Aooval 19.6 16.6 14.9 14.6 14.9 14.0 15.0 14.7 16.7 18.5 20.9 71.2 62.2 68.6 60.3 30.6 9 48.8 53.0 61.5 67.3 72.4 82.4 Yunon 3/ 2027 —AZs8 15:2 Ader 122 —1i2 1414 18:8 12:4 22:3 -- 24.8 TOTAL 111.5 96.5 99.4 90.6 79.4 77.0 82.1 92.8 103. 113.2 127.6 23.8 21.2 20.4 19.7 19.5 18.0 19.8 19.4 20.0 21.9 23.6 24.8 24.8 Southcentral 133.9 120.8 102.8 93.0 88.5 92.4 91.2 103.2 126.1 141.7 152.5 152.5 Yuron wnS4e5 14227 0 13829-3220 129.0 __28.5 28:8 28:2 34:5 42:9 Skid __57.1 -=3Z24 TOTAL 202.2 184.7 168.0 153.5 141.5 135.0 141.0 138.8 157.7 190.8 216.6 234.4 234.4 A974 Southeast 26.1 23.0 22.3 20.5 20.2 20.0 19.5 139.8 22.0 23.5 26.8 26.8 Southcentral 166.5 146.9 151.5 124.4 413.2 7.2 105.8 112.7 132.4 156.5 165.6 166.5 Yuron --8222 5329 52.720 45.9 9 -_46.4 = __ 48.4 Be A ee ee ee CY -=20:8 TOTAL 254.8 223.8 226.5 190.8 179.8 165.6 162.8 181.5 207.8 246.3 263.0 263.9 4972 South: t 26.7 24.1 22.9 22.8 22.8 21.7 20.9 23.0 21.4 25.4 26.7 27.7 27.7 Southcentral 183.3 157.4 156.8 132.9 120.7 117.5 113.4 118.7 137.0 A61.1 180.2 195.4 195.4 Yuron wpZhed 8722-8822 9-43.89 «37.20 348 9 --33.4 -35.8 «42.8 9.48.1 956.1 9 __ 65.3 =nZhs2 TOTAL, 281.2 "248.6 245.7 “159.5 “180.7 “173.8 “ie7.7 “377.5 “201.0 "234.3 263.0 “288.4 294.3 2273 Southeast 24.0 24.1 23.8 27.4 30.4 27.8 30.1 Southcentral 125:5 136.0 150.3 177.0 199.7 202.7 2i1.5 Yuron 232723 32292 44.2 __52.3 -n74.5 TOTAL 186.8 200.0 218.3 256.4 313.4 4974 South t 25.6 27.4 27.6 30.3 Southcentral 154.2 160.9 191.8 225.9 Yuron wn$hs3 4924 9 __84.1 -=8229 TOTAL 221.3 "237.7 280.5 5.2 1973 Southeast 26.1 27.5 32.0 30.6 32.7 32.7 Southcentral 162.0 189.0 254.0 268.6 311.7 311.7 Yuron -s3323 0.3824 = 88:2 39.0 108.8 408.8 TOTAL 243.6 "274.9 "374.2 398.2 "453.2 ‘453.2 1976 Southeast 28.3 29.4 29.9 32.6 33.7 33.7 Southcentral 197.7 218.0 277.7 276.2 311.0 311.0 Yukon i DE Se ee) 40120 TOTAL 278.9 (307.4 389.7 393.3 442.0 445.7 4977 Southeast 32.3 31.7 33.5 37.9 41.6 41.6 Southcentral 216.3 253.3 293.0 344.4 375.4 375.4 Yuron -a3328 --8324 73:2 9 10213 417.5 247.5 TOTAL 304.2 350.4 405.7 484.3 534.5 534.5 32.3 32.5 35.9 40.0 39.9 40.0 Southcentral 236.6 253.1 B12.4 353.2 382.8 382.8 Yuton --35:3 --8228 _.72.3 ~~ 23:8 TOTAL 324.2 348.4 420.3 518.6 1972 Southeast 33.3 Southcentral 219.5 Yuron 38.2 TOTAL 310.3 2282 Southeast 36.6 Southcentral 240.8 Yukon -=52.5 TOTAL 334.9 2282 Southeast 40.9 Southcentral 251.9 Yukon ~~ 80:7 TOTAL 353.5 4282 Southeast 45.5 Southcentral 330.9 Yuron -20:7 TOTAL 447.1 17 "Southeast: AELAP, APA-S, GHEA , KPU 2/ Southcentral: AML&P, APA-E, CEA . 3/ Yukon (*‘Interior’ before 1971; changed to agree with newer State subdivision designations) Fmu , GVEA. Note; 1. These utilities represent about 3/4 of statewide utility installed capacity. 2. TOTALS obtained from rounded values. btained from unrounded da 3. Annual values SOURCE: FPC Monthly Electric Power Statistics, other FPC/DOE reports, APUC reports, and APA Files. APA 8/1983 REGIONAL ENERGY GENERATION (GWH) ~Tans —Febs Mare fer, = _Max_ -June ~July Aug: Seets Ost. _Novs —Des: 8.7 7.8 7.9 es a2 6.8 6.7 7.8 8.3 9.2 Southcentral 2/ 34.6 29.5 29.3 30.0 27.8 25.4 24.5 33.4 35.7 41.4 Yukon 3/ cope) eae || oeeitaas | eee TT eae TeGmEe ras ead ihe de kee TOTAL 55.1 48.4 47.4 36.8 44.2 8 38.7 52.0 56.0 63.5 st 11.4 9.5 9.7 9.8 9.6 8.8 9.4 9.6 9.5 10.5 10.9 12.4 A2i.i Southcentral 70.4 54.7 57.4 53.4 50.3 468.0 48.0 50.3 53.3 64.3 69.3 83.0 700.4 Yukon 22329-4728 = A827 46.6 24.2 22.0 24.0 _45.3 26:2 20:3 22:8 -.20:) 222.4 TOTAL 105.7 82.0 85.8 79.8 74.1 66.8 71.4 75.2 79.7 95.1 102.8 125.5 1043.9 1971 Southeast 12.6 10.8 11.2 10.4 10.0 9.4 9.1 9.6 10.0 10.8 11.5 12.6 128.0 Southcentral 91.8 71.9 77.9 66.4 60.8 53.2 53.9 57.2 60.1 71.6 83.5 89.7 838.0 Yukon -p2425 0 125220 12624 20.0 _AZeL 45:2 4524 4824 4824 22:5 22:3 -_34.5 273.2 TOTAL 138.9 107.8 115.5 96.8 87.9 77.7 78.4 85.2 38.5 104.9 124.5 133.8 1239.9 1972 Souths 13.3 12.2 12.0 11.2 10.5 12.2 12.5 12.8 138.7 Southcentral 99.7 84.4 88.4 73.1 68.2 83.5 94.8 109.3 962.1 Yukon --95:6 -.30:92 30:8 _ 23,5 _ 19.8 --8523 0 30:2 __ 34.0 203.4 TOTAL 148.6 ~i27.5 ~i31.2 “io7.8 98.3 121.0 “137.4 "156.1 1404.2 14.0 ii. 14.0 11.9 11.5 13.2 13.5 13.2 148.9 Southcentral 15.0 96.7 95.6 82.2 77.2 97.0 111.8 113.3 1083.4 Yukon --38:8 20:8 29:2 23:2 _20.7 --8Z:5 33:5 33.7 248.0 TOTAL 67.6 139.3 139.5 117.3 109.4 137.7 158.8 160.2 1548.3 1974 Southeast 14.3 12.6 12.5 13.7 13.6 14.7 157.7 Southcentral 120.9 104.5 82.8 102.5 117.0 126.5 1165.0 Yukon <es8) eae -~2h23 — 8428 32:0 __44:2 242.5 TOTAL 173.6 152.0 116.6 8.0 169.6 185.4 1670.2 1975 South t 16.0 14.5 15.1 14.1 13.9 12.8 12.9 13.8 13.6 14.9 15.5 17.1 174.2 Southcentral 132.3 124.8 118.0 96.5 93.7 89.0 86.2 90.4 100.7 113.1 141.4 166.4 1352.6 Yukon ugha aed eee tl oraea) 22722 124.0 = 24:7 912722 -_Bhs2 0 -_92:2 3418 9-39.29 452.5 TOTAL 196.8 181.4 181.7 143.3 134.8 125.8 123.8 132.1 145.5 167.9 211.7 243.4 1978.3 16.9 15.5 16.6 14.6 14.9 13.7 14.7 15.3 16.2 16.4 17.4 187.0 Southcentral 157.4 149.6 143.8 124.5 115.4 101.8 109. 119.9 141.8 150.6 170.0 1589.6 Yukon =-35-2 53:2 43.8 34.5 29:2 -_27Z.1 20:0 __3he2 40:4 _.43:2 _.3324 = AZZ TOTAL 230.2 219.0 204.2 173.6 159.9 142.6 149.14 154.6 166.5 198.4 210.2 240.8 2249.3 Southeast 18.1 16.5 17.4 16.1 15.2 15.6 17.5 18.6 20.5 195.2 Southcentral 163.5 143.9 165.0 143.0 123.5 128.1 158.9 193.8 216.9 1803.6 Yukon eared |) AGT | |) aRa?) || 5 are -220s2 --Bhad = 4420 9 33120 _.92.7 ~472.7 TOTAL 229.0 201.1 229.3 196.3 169.4 175.1 217.4 266.3 297.1 2478.5 i978 Southeast 16.8 16.7 16.9 18.0 19.8 21.0 Southcentral 149.6 132.1 138.7 169.4 A9L.d 209.0 Yuron -=37.0 23022 3224 9 32:2 44.1 _.44.8 TOTAL 203.4 379.7 “i88.0 227.3 255.0 "274.8 1979 South 21.2 20.1 20.6 18.6 17.3 417.5 19.0 19.1 21.5 Southcentral 209.2 210.4 185.2 161.5 138.2 137.8 168.1 178.4 231.3 Yukon + npM828 __S0s2 __42.5 __36.8 22222 3423 0-35-68 -.26:2 _.48.0 TOTAL 279.2 280.6 248.3 216.9 164.6 186.6 222.7 233.7 300.8 1980 Southeast 23.0 19.6 19.6 18.8 16.2 18.2 18.3 18.5 18.6 21.7 26.4 236.3 Southcentral 221.3 181.8 157.0 146.2, 136.8 9141.2 143.9 152.3 177.4 = 202.5 259.1 2104.9 Yukon wa4Zs3 39nd © _2Bek «= -_39cd 0 -_Bda2 0 2813 27.3 20.2 32:2 -.2221 40:7 --54s0 422.2 TOTAL 391-8 240.5 241.2 209.7 “196.3 161.3 186.7 192.2 203.7 223.1 264.9 339.5 2770.3 1982 Southeast Southcentral Yukon TOTAL 1982 South t 24.2 21.5 Southcentral 176.4 158. Yukon 52422 9 -. 3024 TOTAL 234.8 210.6 1983 Southeast 22.7 Southcentral 166.5 Yukon 332.8 TOTAL 246.2 "222.0 AELaP, APA-S. GHEA , KPU . 2/ Southcentral: AMLSP, APA-E. CEA . 3/ Yukon (*Interior’ ore 1971; chang Fmu , GVEA . Note; 1. Ze 3. Annual values obtained from unrounded data. SOURCE: FPC Monthly Electric Power Statistics, other FPC/DOE reports, APUC reports, and APA files. APA 8/1983 45 > a REGION/Place S Villages Auke Bay Haines Juneau Ketchikan Metlakatla Petersburg Sitka Skaquway Wrangell Yakutat SQUTHCENTRAL Anchorage Cordova Glennallen Homer Kodiak Seward Valdez YUKON Fairbanks Fort Yukon 48 Villages Barrow Kotzebue SOUTHWEST Dillingham Egegik McGrath Naknek ALASKA TOTALS NOTE AML&P CEA MEA cEc CVEA HEA KdEA SES CVEA BL&P FMU GVEA Fyu 188913 129010 546736 215796 4697 3137 131942 issis 9649 1065938 40 27758 » 150487 369 178654 7562 4367 1460183 ENERGY SALES, REVENUE, CUSTOMERS - 1982 ~-£1,.000 1033.6 1027.5 368.1 4606.8 3511.2 343.0 821.3 1733.8 283.8 675.3 14679.3 6584.1 24287.9 14744.3 1079.7 586.6 7437.7 2747.1 696.3 59293.8 20.7 2196.9 16374.9 18705.7 3712.7 547.5 100168.0 Sales Customers —--MWH___ 614 2345 971 1840 483 4882 7487 46925 4769 39213 397 5795 1160 12139 2546 21328 294 1495 839 6256 ----242 ~~. 2893 13772 144827 14745 474345' 46560 375969 14941 390937 825 11164 656 13008 10307 191106 2611 39996 1203 9528 ~--1197 —--__1 8066 93045 1222119 ar 239 4709 90923 16176 172590 ~-~-124 ~--~1478 21096 265230 3201 15733 790 12740 ----357, ~---_8899 4548 35372 1245 14798 533 5206 29 62 148 1844 ee Bone! 5387 2308 27297 140769 1694845 Revenue --£1..000 891.1 143.0 612.3 2964.9 3062.2 523.8 1246.6 1723.9 173.5 749.8 19242.7 15308.4 4728.8 2167.0 1850.5 8214.6 6104.1 496.4 _-1997.4 60109.9 121.0 7892.6 16477.9 —-1390.5 5480.3 112052.6 All AVEC villages are included in Arctic-Northwest region; however, 16 are in Yukon, 10 in Southwest. and 1 in Southcentral. Customers 73 53 161 755 175 ~--~133 1069 611017 927921 306893 16082 16709 323323 57363 32134 25063 2316505 855 122090 323405 23403 17293 ----11070 51766 21142 9233 154 2321 3243776 26899.8 18183 40000.9 51464 19489.7 16375 3280.6 1138 2520.8 927 15688.7 11978 8973.1 3247 1896.5 1525 ~~ 2218.5 ~~ 1492 121968.6 106329 426.0 10235.8 32889.3 8 10112.5 3977 1755.9 966 2421.3 weeny 14289.7 5689 3747.5 1463 1852.1 755 58.1 36 712.9 214 —-1851.7 8222.3 220120.4 164087 APA 8/ 1983 ENERGY USE, BILLING. CHARGE - 1982 __-Commercial/Industrial = Lt ists). —--.---Average Annual oo Average Annual —_____ Use Bill Charge Use Bill Charge Rlace Utility Kwh/Cust. $/Cust. C/Kwh_ Kwh/Cust. $/Cust. C/Kwh_ Kwh/Cust. $/Cust. C/Kwh_ S Villages THREA 4486 1683 37.35 30064 11424 37.9 8150 3122 38.3 Auke Bay GHEA 10789 1058 9.8 34716 2698 7.7 13523 1259 9.3 Haines HL&P 5273 762 14.4 30322 3803 12.5 11283 1484 13.1 Juneau AEL &P 11194 615 5.4 43773 2765 6.3 18761 1102 5.8 Ketchikan KPU 9050 736 8.1 48833 3813 7.8 14093 1137 8.0 Metlakatla MP&L 17070 863 5.0 86492 7817 9.0 28413 1944 6.8 Petersburg PMP&L 6450 708 10.9 54680 S615 10.2 14197 1496 10.5 Sitka SED 9428 680 7.2 S9I7AZ 4834 8.0 15699 1215 7.7 Skagway AP&T 7482 965 12.8 21357 2478 11.6 14002 1754 12.5 Wrangell WML&P . 5125 805 13.7 22666 2716 11.9 10188 1384 13.5 Yakutat YPI 6575 1294 19.6 54354 9156 16.8 14536 2586 17.7 Regional Ayerage 9555 742 7.8 45160 3908 8.7 15846 1287 8.1 SOUTHCENTRAL Anchorage AML&P 8749 446 5.0 146856 5957 4.0 33603 1479 4.4 CEA 11742 S21 4.4 77074 3139 4.0 18030 TL 4.3 MEA 14443 986 6.8 63815 3318 S.1 18741 1190 6.3 Cordova CEC Seg3 1308 22.9 36012 6990 19.4 14131 2882 20.3 Glennallen CVEA 4782 894 18.6 55353 7874 14.2 18024 2719 15.0 Homer HEA 12801 721 5.6 115471 4963 4.2 26993 1309 4.8 Kodiak KdEA 6363 1052 16.5 63085 9627 135.2 17666 2763 15.6 Seward SES 8020 578 Tee 33528 2788 5.2 21071 1243 5.8 Valdez CVEA 6979 944 13.5 62030 Tea 12.4 16798 2157 12.8 Regional Average 11456 637 5.6 95448 4695 4.9 21786 1147 5.3 YUKON Bettles , BL&P 2352 A217 51.7 11950 6050 50.6 22500 1210 5.3 Fairbanks FMU 5894 464 7.8 735953 6593 8.6 20143 1705 8.4 GVEA 9303 1012 10.8 82500 7876 9.5 17694 1799 10.1 Fort Yukon FYU i902. 635 33.3 34740 15251 27.8 6617 1920 29.0 Regional Average 8469 887 10.5 79505 7465 9.4 18178 1792 9.9 ARCTIC NORTHWEST 48 Villages AVEC 2362 1159 49.0 20838 8421 40.4 5884 2542 43.2 Barrow BUSEC 5527 693 12.5 72800 6791 9.3 17901 1817 10.1 Kotzebue KtEA 5560 S27 22.8 49633 10646 21.4 14839 3245 21.8 Regional Average 3304 1092 33.1 33089 8444 25.5 9099 2512 27.6 SOUTHWEST Bet BUC S095 986 19.3 67880 11556 17.0 14451 2561 17. Billingham NEC S561 1160 20.8 38562 7430 19.4 12229 2453 20.0 Egegik NEA 3172 1203 37.9 8857 3314 37.4 4277 1613 37.7 McGrath MGL&P 3222 1162 36.0 28369 8247 29.0 103845 3331 30.7 Naknek NEA 5020 1325 26.3 34754 8970 25.8 14182 3681 25.9 Regional Average 5049 1092 21.6 47064 9449 20.1 13458 2768 20. > 3 ALASKA AVERAGE 10373 712 6.9 80722 5337 6.6 19769 1341 6.8 APA 8/ 1983 8b TYPICAL ELECTRIC BILLS MONTHLY RESIDENTIAL (Including fuel cost rate adjustment where available.) 100 500 KWH KWH REGION/Community.__ won HEALL SY _—__4980__ 1981 __4982__—__1980___1984___1982 ' ' SOUTHEAST | ' 1 | + Angoon THREA 1 ' 185.80 187.15 Auke Bay GHEA ' ' 58.50 67.50 Craig AP&T ' ' 104.01 100.86 Haines HL&P ' ' 87.95 87.50 Hoonah THREA 1 1 185.80 187.15 Hydaburg AP&T ' ' 111.92 102.92 Juneau AEL&P 1 ! 28.25 33.65 Kake THREA 1 1 185.80 187.15 Kasaan THREA | ' 185.80 187.15 Ketchikan KPU ' ' 26.20 26.20 Klawock THREA 1 1 185.80 187.15 Pelican PUC ' ' 50.55 52.85 Petersburg PML&P I 1 55.50 55.50 Sitka SED 1 1 38.00 38.00 Skagway AP&T ' ! 63.65 66.75 Wrangell WML&P I 1 76.18 76.18 Yakutat YPr ' ' 103.92 102.70 REGIONAL AVERAGES | 1 101.98 102.73 | 1 SOUTHCENTRAL ' ! 1 1 Anchorage AML&P I 9.37 9.68 9.17 | 27.17 27.66 27.85 Anchorage (Urban) CEA ! 6.70 7.80 10.15 1 19.80 22.95 29.95 Anchorage (Suburban) CEA 1 7.15 8.35 10.80 | 24.60 28.65 37.30 Cordova CEC | 18.77 36.00 37.00 | 87.87 108.00 113.00 Eagle River MEA 1 11.60 25.25 26.72 | 37.65 46.27 53.58 Glennallen CVEA ! 26.51 26.58 22.81 | 108.05 108.40 89.56 Homer HEA 1 12.50 16.78 18.12 | 20.75 33.91 40.61 Hope CEA 1 14.08 29.23 37.88 | 44.98 52.59 68.22 Kenai HEA 1 12.50 16.78 18.12 | 20.75 33.91 40.61 Kodiak KdEA | 17.68 17.68 18.72 1 82.39 82.39 86.99 Palmer MEA § 11.60 25.25 26.7Z 1 37.65 46.27 53.58 Port Graham HEA | 12.50 17.63 18.97 1 25.00 38.16 44.86 Port Lions KdEA 1 35.58 53.38 55.04 | 160.90 238.46 246.77 Seldovia HEA 1 12.50 17.63 18.97 1 25.00 38.16 44.86 Seward SES 1 15.38 | 32.90 Soldotna HEA § 12.50 16.78 18.12 | 20.75 33.91 40.61 Talkeetna MEA 1 11.60 25.25 26.72 1 37.65 46.27 53.58 Valdez CVEA | 22.59 22.67 18.81 1 988.95 89.35 70.06 Wasilla MEA § 11.60 25.25 25.25 1 37.65 46.27 46.27 Whittier cea 1 14.08 14.94 _19.37 | _44.98 _5Z.59 _§8.22 REGIONAL AVERAGES 1 14.84 21.73 23.02 | 49.27 61.80 66.13 49.42 32.05 39.85 53.65 189.60 41.50 69.98 41.50 152.77 53.65 50.00 313.79 50.00 41.50 53.65 153.90 53.65 1000 1500 _KWH KWH 19011982. ____1980____1981,___1982__ | ' $ 1 $ 357.50 360.20 | 521.25 529.20 533.25 88.55 102.10 1 102.95 111.55 128.60 204.46 198.16 | 302.05 304.91 295.46 162.38 161.48 | 232.52 232.53 231.18 357.50 360.20 | 521.25 529.20 533.25 220.52 202.52 | 354.62 329.12 302.12 53.30 60.30 | 69.40 78.35 86.95 357.50 360.20 | 521.235 529.20 533.25 357.50 360.20 | 521.25 529.20 533.25 46.20 46.20 1 66.20 66.20 66.20 357.50 360.20 | 521.25 529.20 533.25 101.10 105.70 | 153.60 151.65 158.55 101.00 101.00 | 146.50 146.50 70.50 70.50 | 103.00 103.00 103.00 117.20 123.40 | 196.10 170.75 180.05 127.18 127.18 | 178.18 178.18 178.18 192.20 | _247.76 _280.09 _276.70 193.63 | 288.29 282.28 283.51 1 1 1 50.14 51.20 | 71.67 72.61 74.55 37.20 48.45 1 43.55 50.70 65.95 46.40 60.55 | 51.35 59.90 78.05 198.00 208.00 | 278.00 293.00 72.55 87.16 I 67.20 96.02 117.76 190.30 152.61 1 267.15 268.20 211.67 55.32 68.72 | 57.25 71.73 91.83 81.84 106.22 1 79.98 93.34 121.22 55.32 68.72 1 57.25 71.73 91.83 152.77 160.67 | 221.16 221.16 232.13 72.55 87.16 1 67.20 96.02 117.76 63.82 77.22 «1 75.00 89.48 109.58 463.54 480.17 | 466.69 688.63 713.57 63.82 77.22 1 75.00 89.48 109.58 1 55.32 68.72 1 57.25 71.30 91.83 72.55 87.16 1 87.20 96.02 117.76 174.70 116.11 | 216.85 218.05 160.17 72.55 72.55 1 87.20 96.02 96.02 9.98 __81.84 106.22 1 __79.98 __93134 _121.22 108.45 114.99 | 116.05 148.51 158.71 TYPICAL ELECTRIC BILLS MONTHLY RESIDENTIAL (Including fuel cost rate adjustment where 100 S00 KWH KWH REGION/Community__________USility___1280___1281___1982__—__4980___1981___1282_ 1 ' YUKON ' | ; 1 $ ! $ Bettles BL&P 1.37.24 53.40 51.00 | 186.22 267.00 255.00 Circle cE 1 32.00 32.00 32.00 1 105.00 105.00 105.00 Delta Junction GVEA 1 16.39 18.60 20.08 | 53.39 60.60 60.42 Dot Lake AP&T 1 21.96 21.30 20.91 | 98.35 95.00 93.05 Fairbanks FMU 1 12.00 12.00 12.00 | 42.50 42.50 42.50 GVEA 1 16.39 18.60 20.08 | 53.39 60.60 60.42 Fort Yukon Fyu 1 39.73 45.85 46.67 | 147.65 169.70 173.39 Galena M&D | 27.00 37.30 37.30 | 124.50 186.50 186.50 Manley Hot Springs MUC | 30.00 | 130.00 Nenana GVEA 1 16.39 18.60 20.08 | 53.39 60.60 60.42 Northway NP&L 1 22.27 25.07 28.93 1 111.35 125.35 144.65 Tanana TPC 1 33.32 35.91 38.70 | 158.10 171.05 184.50 Tok AP&T 1 _21.97 _21.30 _20.91 | _98.35 _95.00 _93.05 REGIONAL AVERAGES | 25.13 28.33 29.06 | 104.78 115.91 121.58 1 J ' ARCTIC NORTHWEST ! ! ' | 48 Villages AVEC 1 44.47 48.27 48.27 | 222.35 241.35 241.35 Barrow BUsEC | 15.00 15.00 15.00 | 66.00 66.00 66.00 Deadhorse AUI 1 29.37 30.64 30.64 | 146.85 153.20 153.20 Kotzebue KtEA | 28.61 30.30 31.93 1 101.05 109.50 117.65 Teller TePC | 35.00 35.00 35.00 | 175.00 175.00 175.00 Unalakleet MEA | 35.14 _38.08 _38.08 | 117.70 132.40 132.40 REGIONAL AVERAGES | 31.27 32.88 33.15 | 138.16 146.24 147.60 1 ' SOUTHWEST | ! ' 1 Aniak APC 1 39.10 40.42 38.66 | 186.85 193.45 184.65 Bethel BUC { 23.14 23.15 23.12 | 97.22 97.28 97.17 Cold Bay NP&E | 22.27 22.73 20.64 | 104.75 107.05 36.60 Dillingham NEC 1 26.41 26.52 27.75 | 101.89 102.45 106.73 Egegik NEA | 33.10 1 137.70 Tliamna I-NEC | 35.00 35.00 | 175.00 175.00 King Salmon NEA 1 30.65 | 106.95 Kwethluk KI ' 30.00 ' 150.00 McGrath MGL&P | 27.24 32.97 34.85 | 128.45 155.55 164.15 Naknek NEA 1 30.65 | 106.95 Sand Point AMFAC | 21.24 26.92 1 100.20 126.98 Puc eae MONE * eee sree 122.29 REGIONAL AVERAGES | 28.42 29.71 29.43 | 119.00 138.47 135.23 | | ALASKA _AVERAGES 1 22.79 25.93 26.53 | 91.75 102.13 103.18 NOTE State power cost assistance (cents/KWH): CE=16.14; NP&E=4.02; tv NEC=7.11; .FYU=18.60; KtEA=9.09; MGL&P=14.32; NP&L=12.45; KdEA(Pt.Lions)=30.40; PUC(Sand Pt.)=3.5 TPC=16.06; THREA=20.10; MEA(Unalakleet)=11.63; AVEC=25.98; BUC=3.69; BL&P=30.40; M&D=20.00; HL&P=2.14; YPI=3.56 KdEA=2.23; available.) 1000 1500 _KWH _KWH ~,--1200____1201____1982______1980___1981____1982__ 1 1 $ 1 $ 372.43 534.00 510.00 | 558.64 801.00 765.00 190.00 190.00 190.00 | 275.00 275.00 275.00 99.64 113.10 102.09 | 145.89 165.60 143.76 190.70 184.00 180.10 | 275.55 265.50 259.65 72.00 72.00 72.00 | 101.50 101.50 101.50 99.64 113.10 102.09 | 145.89 165.60 143.76 250.70 287.31 294.28 | 353.75 404.92 415.18 373.00 373.00 1 559.50 559.50 255.00 | 380.00 99.64 113.10 102.09 | 145.89 165.60 143.76 222.70 250.70 289.30 | 334.05 376.05 433.95 303.20 329.10 353.00 | 448.30 487.15 521.50 190.70 _184.00 _180.10 | _275.55 _265.50 _259.65 195.53 228.62 229.00 | 286.67 336.08 335.18 ! 1 1 444.70 482.70 482.70 | 667.05 724.05 724.05 122-56) (122.56 "i28.56 1), 177.12 ‘177.12 | 1477-12 293.70 306.40 306.40 | 440.55 459.60 459.60 191.60 208.50 224.80 | 282.15 307.50 331.95 350.00 350.00 350.00 | 525.00 525.00 525.00 220.90 _250.30 _250.30 | _324.10 _368.20 _368.20 270.41 286.58 289.29 | 402.66 426.91 430.99 1 1 ! 365.05 378.25 360.65 | 543.25 563.05 536.65 181.40 181.50 181.28 | 265.56 265.73 265.40 202.75 207.35 186.45 | 297.35 304.25 272.90 190.89 192.01 199.75 | 279.89 281.57 292.78 1 350.00 350.00 | 525.00 525.00 I 300.00 1 450.00 247.10 299.15 315.15 | 365.75 442.75 466.15 1 196.40 248.88 1 292.60 370.78 AOE ear 2 239.441 ______ 356.59 230.60 269.64 261.82 | 340.73 400.39 387.92 1 172.55 192.82 193.33 | 251.76 280.94 281.29 APA - 8/ 1983 GENERAL DATA Re RE Oe TE a ee 51 500+ ' | | | ' | % ! | it N 400+ D Ee x | ! | ' ' 1 ! B 300+ Aa S | Es | | ™ ec a | R | ' 1 * 200+ Ss ' we oO ! | ! ! ' | GROWTH INDICATORS 4 a. -l- 3 ae aoe | 8 @ S 0g eee ++------- +------ = +-------+------= +------— +------- + 1970 71 ie 73 74 75 76 YEAR LEGEND -- (1) Population (2) (3) (4) (5) (6) Utility Installed Capacity Utility Energy Production Utility Investment Personal Income Employment “——~e 6 1 1 ------ +-------+ 77 738 > INVESTMENT I ! \ ! ! I ' I I 5 ' ! PERSONAL INCOME Poe \ 5 \ | \ 1 1 1 ! ZI CAPACITY ~2-——— 3] 1 ae ei \ $— ee — Se ee 6 6— ae POPULATION 1 ; pons 4 —------. 4-------4+-------+------- + 73 80 a1 az APA - 8/ 1983 GROWTH INDICATORS -1980_ ~1283_ ~4970_ -1972_ -1974_ -1276_ ~2978_ -2980_ ~1981_ ~2282_ POPULATION 226167 265192 3083500 329800 348100 409800 411600 419700 435200 460800 HOUSING UNITS 67193 90827 99747 108421 120232 136982 162393 168000 175000 EMPLOYMENT 92500 104200 127200 170500 163500 170600 183700 194400 INCOME/CAPITA - $ 2870 3235 4665 5234 7138 10353 10625 13117 13500 15011 PERSONAL INCOME - x $1,000,000 649 858 1412 1698 2436 4195 4369 5283 5700 6917 UTILITY: INVESTMENT - x $1,000 92976 146150 237991 328612 398160 542860 689214 792260 911300 1026912 CAPACITY - MW 122.6 242.8 470.0 533.6 723.6 971.8 1137.7 1282.9 1372.7 1412.5 NET GENERATION - GWH 431 735 1281 1624 1935 2572 2966 3159 3281 3713 FUEL USE: OIL - GALLONS x 1,000 24672 22659 36913 42550 41781 36074 43156 GAS - MCF x 1,000 12518 ie 22366 24757 28991 29371 30513 COAL - TONS 248152 266347 252213 268556 268358 320000 336000 NOTES: (1) Population revised according to Alaska Dep’t. of Labor figures which include North Slope residents. U.S. census 1980 population = 401, 851. (2) 1970 & 1980 housing units shown are census figures --- others are estimates (3) Data sources are various government agencies and parts of this book. APA - 8/ 1983 ELECTRIC PLANT IN SERVICE UTILITIES AND FEDERAL HYDRO ($1,000) ~1960__ -1985__ 41970__ -1973__ -2974__ -12735__ -1276__ -4280__ -1381__ -4282__ POWERPLANT Cooperative $ 13222 & 26761 $ 52723 $ 69391 $ 80763 $ 90577 $ 142390 $ 155048 $ 175887 $ 181559 Federal 30276 29898 31207 735599 81872 83039 83585 780900 79331 79386 Municipal 9828 25537 39662 52197 52212 60711 68199 95835 107365 106422 Private ~-- 4589 ~~~ 4382 ~-~ 2459 ~~~ 2154 -=~3225 -~10312 11977 18409 ~~ 23938 24931 TOTAL 57886 87156 131042 206341 224572 244639 306151 347292 385731 392298 TRANSMISSION Cooperative 6500 13500 26500 31180 40827 41594 58304 91767 94336 140631 Federal 2450 2454 2529 19440 223594 25773 26249 30870 29684 30065 Municipal 1000 1200 1970 1976 1832 2115 2277 10448 9444 11043 Private eared ~--~449 ----352 - ___1959 ~-~4119 ~-~1125 ~-~1134 ~-~3447 --~4473 ~-~5875 TOTAL 10399 173534 31549 53646 $6363 70607 87964 136532 137943 187614 DISTRIBUTION Cooperative 13200 27000 53000 68674 76841 89713 1098593 190143 209727 237504 Federal 0 0 oO Qo oO 0 oO 0 oO oO Municipal 10000 12000 19200 25623 25371 28056 33087 44367 47789 56063 Private ---1509 ~~ 2409 3299 ~-4198 ~--3943 ---3371 ~--52799 41338 14199 ~~42904 TOTAL 24700 41400 735400 98495 107225 123140 148745 245868 271625 BLOS7L GENERAL /MISC. Cooperative oO 0 oO 0 0 oO ° 51763 103285 121546 Federal o 0 oO o oO oO o 2731 2858 3136 Municipal oO 0 0 0 0 0 0 4734 6394 7409 Private 2 Q es Q ome eee See cel Q --~3342 ---34ZzZ ---4338 TOTAL oO 0 0 0 0 0 oO 62568 116009 136429 TOTAL ELECTRIC PLANT Cooperative 32922 67261 132223 169245 198431 221884 310553 488721 383235 681240 Federal 32726 32352 33736 95039 104466 108812 109834 111601 111923 112587 Municipal 20828 38737 60832 79796 79415 90882 103563 155384 170992 180937 Private ---8399 ~~-2800 11200 ~~14402 ~~15848 -~18808 ~~18319 --28534 ~~45158 ~~32148 TOTAL 92976 146150 237991 358482 398160 438386 542860 792260 911308 1026912 NOTE 1977-1979 Data is available but not yet compiled. 1960-1976 “General” data is included in “Powerplant” data. APA - 8/ 1983 ALASKA AND UNITED STATES ge Energy Charge, Use, Billing Year Alaska uU. Ss. 1960 4.32 2.47 4.09 2.46 4.11 1.69 1961 4.41 2.45 4.22 2.35 4.21 1.69 1962 4.08 2.41 4.03 2.37 3.97 1.68 1963 3.67 2.37 3.71 2.28 3.50 1.65 1964 3.46 2.31 3.59 Zead 3.34 1.62 1965 3.53 2.25 3.59 2.13 3.38 1.59 1966 3.48 2.20 3.51 2.06 3.29 1.56 1967 3.37 2.17 3.39 2.04 3.20 1.56 ig6s 3.36 2.12 3.35 2.00 3.15 1.55 ig69 3.13 2.09 3.10 1.99 2.95 1.54 1970 3.01 2.10 3.12 2.01 2.91 1.59 L972 3.0L 2.19 3.22 zZ.1z 2.95 1.69 1972, 3.33 2.29 3.55 2.22 3.20 1.77 1973 3.05 2.38 3.27 2.30 3.02 1.86 1974 3.06 2.83 3.26 2.85 3.00 2.30 1975 3.17 3.21 3.298 3.23 3.17 2.70 1976 3.45 3.45 3.25 3.46 3.40 2.89 1977 3.92 3.78 3.74 3.84 3.85 3.21 i978 4.20 4.03 3.98 4.10 4.10 3.46 1979) 4.31 4.33 4.19 4.40 4.25 3.74 1980) 4.35 4.93 4.51 5.09 4.48 4.37 1981 Use--Annual KWH/Customer 1960 4,253 3, 854 21, 477 17,006 7,595 11,704 Ag61L 4,344 4,019 21, 063 19,709 7,624 12,099 1962 4,987 4,259 24,172 20,733 8,673 12,763 1963 5,039 4,442 27,168 23, 224 9,525 13, 366 1964 5,126 4,703 28,075 25,213 9,734 14,015 1965 5, 383 4, 933 30,123 27,399 10, 269 14, 694 i966 5,825 5,265 33, 662 30,133 11,461 15, 678 1967 6, 469 5,577 25, 263 32, 041 12, 493 16, 384 1968 6,547 6, OS7 35,769 34, 637 12, 857 17,445 i969 6,954 6, S71 39, 613 36, 950 13, 669 18, 563 1970 7,266 7, 066 41, 806 39, 952 14,181 19, 380 is7i 7,842 7,380 44,451 41,943 15, 106 19, 956 1972 7,899 7,691 45, 425 44,496 15,524 20, 964 1973 9,275 8,079 53, 828 47,580 17,760 21,955 1974 9,323 7,907 54, 355 46,557 18,131 21,448 1975 9,289 8,176 54, 829 48, 964 17,703 21,417 1976-9, 835 8, 360 68, 426 50,733 18,594 22,361 1977 10,375 8,693 75, 347 52, 892 19, 882 23, O52 1978 10,253 8, 849 75, 016 53,085 19,768 23,315 1979 10,548 8, 833 75,001 53,135 20, 068 23, 454 1980 10,681 8,976 72, 967 53, 646 19, 902 23,154 1981 Billing--Annual $/Customer 1960 184 95 879 413 312 193 1961 i39Z 98 890 463 321 204 1962 204 103 974 491 344 214 1963 185 105 1,008 530 333 221 1964 178 109 1, 007 552 325 227 1965 190 i111 1,083 534 3428 234 i966 203 iis 1,181 621 377 245 1967 218 121 1,196 654 400 256 1968 220 128 1,198 693 405 270 1969 218 137 1,228 735 404 286 1370 219 148 1,304 803 412 3038 1971 236 162 1,429 seg 445 337 1972 263 176 1,611 988 497 371 1973 283 192 1,759 1,094 535 408 1974 28s 224 1,774 1,327 543 493 1975 295 262 1,799 1,582 Se1 573 1976 339 288 2,221 1,755 632 646 Lone 406 329 2,815 2,031 76S 740 1978 430 357 2,982 2,176 810 807 Lacs. 454 382 3,137 2,339 852 876 1980 464 442 3,290 2,733 8g2 1,012 1981 Source: Edison Electric Institute APAdmin. 8-83 ALASKA SALES, REVENUES, CUSTOMERS Comm. & Indus. HHHRHRH AHHH ERS Small Large Street & Other Inter- Resi- Light & Light & Highway Public depart- Year Total dential Power Power Lighting Auth. mental anne seeeee | REE wanes sHeHHe aHRMHHRE eeHee | HeHEHEE Energy Sales -- Thousand MWH 1960 349 iss 128 30 a 8 6 1961 365 178 134 33 8 8 4 1962 440 215 173 28 5 12 7 1963 sis 233 203 53 8 15 4 1964 S6z 253 223 61 8 13 4 1965 616 277 244 6s 3 14 4 1966 694 303 273 84 3 alg 8 1967 7386 348 307 a4 10 30 7 1968 841 366 324 87 13 42 9 1969 956 417 377 93 is So 4 1970 1, 054 465 413 100 14 58 4 1971 1,212 S543 465 103 14 77 4 1972 1,279 S62 486 122 15 g1 3 1973 1,639 743 625 143 is 1093 3 1974 1,713 765 644 153 is 131 4 1975 1,839 834 734 195 17 54 5 1976 2,152 982 1,027 61 415 61 6 Loi, 2,471 1,113 1,217 sé 14 65 6 1978 2,602 1,164 1,295 56 13 67 zr i373) 2,774 1, 257 1, 366 61 12 71 7 1980 2,795 1,292 1,352 60 9 82 oO 1981 13960 14,340 7,264 5,236 977 344 137 1961 15, 377 7, 854 5,659 1,069 313 116 1962 17,449 8,774 6,968 844 236 142 1963 18, 065 8,553 7,530 1,075 288 74 1964 18,792 8,762 7,998 1,107 287 70 13965 20, 851 9,789 8,769 1,291 30L 8s is66 22,818 10,548 9,581 1,468 321 199 1967 25,163 11,738 10,415 1,550 364 197 1968 26, 461 12,285 10, 851 1,530 S589 265 13969 28,239 13, 048 11, 686 1,558 619 131 1970 30,655 14,015 12,878 1,713 SsS1L 91 1971 35,725 16, 331 14, 953 1,902 608 108 1972 40,959 18,725 17,237 2,247 602 68 1973 49,417 22,670 20,418 2,852 693 oa 1974 51,338 23, 406 21,019 3,107 721 81 1975 58, 305 26, 449 24, 088 4,196 803 180 i976 73,167 33,374 33, 336 2,020 3900 213 1977 95,074 43,580 45,474 1,813 981 258 1978 106,578 48,859 51,481 1, 806 1,135 264 1979 117,828 54,144 57,139 1,990 1,022 246 1980 125, 305 56,143 60, 966 2,051 1,533 315 1981 Customer——-Average Number 1960 45,953 39,498 5, 960 1961 47,872 40,980 6, 362 1962 50,734 43,112 7,157 1963 54,174 46,239 7,472 1964 57,738 49,358 7,943 Data coverage represents i965 59, 986 51, 456 8,100 . 80% to 90% of Statewide 1966 60,554 52,019 8,110 installed capacity 1967 62,917 53,797 8,706 1968 65, 412 55,902 9,058 Sources Edison Electric i969 69, 938 53, 967 9,517 Institute 1970 74,323 63, 996 9,879 Ag71 80, 231 69, 239 10, 461 1972 82,388 71,144 10,699 1973 92, 286 80,105 ii, 611 1974 394, 480 82, 051 11,848 1975 103, 883 89,786 13, 387 1976 115,735 99, 851 15,009 1977 124, 286 107,278 16, 152 1978 131,624 113, 532 17,263 1979 138, 228 119,170 18,213 1980 140, 438 120, 968 18,529 1981 APAmin. 8-83