Loading...
HomeMy WebLinkAboutBESS ANALYSIS - NEA BESS Scenario Analysis - 2 - Data AnalysisNEA BESS Scenario Analysis Data Analysis 1 FUEL USAGE (GAL) - EXISTING SCENARIO, 100% SPIN FUEL USAGE (GAL) - FUTURE SCENARIO, 0% SPIN RUNTIME (HOURS) - EXISTING SCENARIO, 100% SPIN Summary by Month Summary by Month Summary by Month Detailed Calculaon, Genset setup Detailed Calculaon, Genset setup Detailed Calculaon, Genset setup Record Data Detailed Calculaon, by Record Detailed Calculaon, by Record Detailed Calculaon, by Record Month Rec Hours Month Factor Peak Min kWh Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal January 62 1 0.50 2,243 1,404 1,350,262 January 26,793 21,463 21,463 21,463 9,010 0 0 0 0 0 0 0 0 0 100,192 January 36,777 28,260 26,456 1,823 0 0 0 0 0 0 0 0 0 0 93,316 January 744 744 744 744 225 0 0 0 0 0 0 0 0 0 3,201 February 57 2 0.49 2,103 1,458 1,169,917 February 24,810 19,791 19,791 19,791 1,839 0 0 0 0 0 0 0 0 0 86,022 February 32,289 24,852 23,957 0 0 0 0 0 0 0 0 0 0 0 81,098 February 672 672 672 672 47 0 0 0 0 0 0 0 0 0 2,735 March 62 3 0.50 2,198 1,391 1,322,708 March 27,918 22,210 22,210 22,210 2,367 0 0 0 0 0 0 0 0 0 96,915 March 36,169 27,799 27,410 108 0 0 0 0 0 0 0 0 0 0 91,486 March 744 744 744 744 60 0 0 0 0 0 0 0 0 0 3,036 April 60 4 0.50 2,981 1,650 1,380,309 April 26,475 21,134 21,134 21,134 12,063 117 0 0 0 0 0 0 0 0 102,056 April 36,165 27,741 27,741 3,330 158 0 0 0 0 0 0 0 0 0 95,135 April 720 720 720 720 297 3 0 0 0 0 0 0 0 0 3,180 May 60 5 0.52 7,404 685 2,369,410 May 29,804 23,470 23,470 23,412 33,966 7,629 5,898 5,504 5,251 8,861 3,112 0 0 0 170,379 May 38,350 29,261 29,261 26,284 9,691 7,445 6,056 5,915 5,605 5,200 0 0 0 0 163,067 May 744 744 744 741 741 168 140 131 125 121 65 0 0 0 4,464 June 30 6 0.99 8,397 976 2,473,725 June 30,153 23,588 23,588 23,447 34,002 18,131 7,484 5,327 4,068 4,802 1,472 306 0 0 176,369 June 37,022 28,360 28,177 27,913 23,625 9,458 5,723 4,587 2,849 2,454 335 0 0 0 170,502 June 720 720 720 714 714 422 179 125 95 65 30 6 0 0 4,510 July 31 7 1.00 12,384 3,584 6,559,673 July 32,701 25,416 25,416 25,416 36,823 32,701 29,380 27,663 25,865 40,625 23,956 21,601 63,634 48,384 459,582 July 39,187 29,977 29,977 29,977 43,134 38,510 32,251 30,509 27,902 44,484 23,948 20,463 59,705 0 450,025 July 744 744 744 744 744 744 732 690 648 600 540 492 408 312 8,886 August 31 8 1.00 4,019 1,321 1,386,500 August 26,749 21,431 21,431 21,431 10,541 799 244 0 0 0 0 0 0 0 102,627 August 37,530 28,808 22,971 4,937 1,045 307 0 0 0 0 0 0 0 0 95,597 August 744 744 744 744 246 18 6 0 0 0 0 0 0 0 3,246 September 30 9 1.02 1,647 943 1,065,685 September 23,537 19,174 19,174 18,678 0 0 0 0 0 0 0 0 0 0 80,563 September 35,982 27,675 10,065 0 0 0 0 0 0 0 0 0 0 0 73,722 September 720 720 720 702 0 0 0 0 0 0 0 0 0 0 2,862 October 31 10 1.01 1,746 301 1,103,959 October 24,281 19,781 19,695 19,695 0 0 0 0 0 0 0 0 0 0 83,451 October 37,383 28,623 10,264 0 0 0 0 0 0 0 0 0 0 0 76,270 October 744 744 738 738 0 0 0 0 0 0 0 0 0 0 2,964 November 46 11 0.65 1,827 578 1,117,207 November 24,549 19,848 19,766 19,388 0 0 0 0 0 0 0 0 0 0 83,551 November 34,991 26,679 15,836 0 0 0 0 0 0 0 0 0 0 0 77,505 November 720 720 716 700 0 0 0 0 0 0 0 0 0 0 2,857 December 62 12 0.50 2,180 1,348 1,240,841 December 26,329 21,153 21,153 21,153 2,354 0 0 0 0 0 0 0 0 0 92,140 December 36,279 27,918 21,665 106 0 0 0 0 0 0 0 0 0 0 85,968 December 744 744 744 744 60 0 0 0 0 0 0 0 0 0 3,036 Year:22,540,197 Year:324,099 258,459 258,290 257,217 142,965 59,378 43,007 38,494 35,184 54,289 28,539 21,906 63,634 48,384 1,633,846 Year:438,123 335,956 273,778 94,478 77,652 55,719 44,031 41,010 36,356 52,138 24,283 20,463 59,705 0 1,553,693 Year:8,760 8,760 8,750 8,707 3,135 1,356 1,057 946 868 787 635 498 408 312 44,977 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100%Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100%Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100% Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Scenario kW 0 649 1,298 1,946 2,809 3,671 4,427 5,183 5,939 6,865 7,765 8,665 10,025 13,325 Scenario kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Scenario kW 0 649 1,298 1,946 2,809 3,671 4,427 5,183 5,939 6,865 7,765 8,665 10,025 13,325 Record:Rec kW Hours # Gens Load GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL # Gens Load GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL GAL # Gens Load HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS 971.66 6.0 3 45%169 142 142 0 0 0 0 0 0 0 0 0 0 0 453 2 64%233 184 0 0 0 0 0 0 0 0 0 0 0 0 418 3 45%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 1603.49 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1434.58 6.0 4 51%190 155 155 155 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1509.77 6.0 4 54%199 161 161 161 0 0 0 0 0 0 0 0 0 0 683 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 614 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1590.76 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1592.92 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1423.84 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1476.90 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1535.51 6.0 4 55%202 163 163 163 0 0 0 0 0 0 0 0 0 0 692 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 653 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1593.73 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1449.46 6.0 4 52%191 157 157 157 0 0 0 0 0 0 0 0 0 0 661 2 96%335 256 0 0 0 0 0 0 0 0 0 0 0 0 591 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.52 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1687.74 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 746 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1641.59 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%271 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1417.28 6.0 4 50%188 154 154 154 0 0 0 0 0 0 0 0 0 0 650 2 94%328 251 0 0 0 0 0 0 0 0 0 0 0 0 579 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1489.01 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1493.85 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1498.04 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1319.01 6.0 4 47%176 146 146 146 0 0 0 0 0 0 0 0 0 0 615 2 87%307 235 0 0 0 0 0 0 0 0 0 0 0 0 542 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1475.16 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 601 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1551.88 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 658 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1533.00 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1324.35 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 617 2 88%308 236 0 0 0 0 0 0 0 0 0 0 0 0 544 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1440.48 6.0 4 51%190 156 156 156 0 0 0 0 0 0 0 0 0 0 658 2 95%333 254 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.43 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1031.49 6.0 3 48%179 148 148 0 0 0 0 0 0 0 0 0 0 0 475 2 68%246 193 0 0 0 0 0 0 0 0 0 0 0 0 439 3 48%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 1303.26 6.0 4 46%174 145 145 145 0 0 0 0 0 0 0 0 0 0 609 2 86%303 232 0 0 0 0 0 0 0 0 0 0 0 0 536 4 46%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1423.21 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1426.46 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 653 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 582 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1452.87 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1329.74 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 618 2 88%309 236 0 0 0 0 0 0 0 0 0 0 0 0 546 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1429.19 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 654 2 95%331 252 0 0 0 0 0 0 0 0 0 0 0 0 583 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1461.00 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 595 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.84 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 686 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1365.97 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 632 2 90%317 242 0 0 0 0 0 0 0 0 0 0 0 0 559 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1448.44 6.0 4 52%191 157 157 157 0 0 0 0 0 0 0 0 0 0 661 2 96%335 256 0 0 0 0 0 0 0 0 0 0 0 0 591 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1504.96 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 612 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.72 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1411.56 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 648 2 93%327 250 0 0 0 0 0 0 0 0 0 0 0 0 576 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.90 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1666.15 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.00 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1369.78 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1495.07 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1460.08 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 665 2 97%337 258 0 0 0 0 0 0 0 0 0 0 0 0 595 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.61 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1326.41 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 617 2 88%308 236 0 0 0 0 0 0 0 0 0 0 0 0 544 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1483.65 6.0 4 53%196 159 159 159 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1511.96 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%251 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1446.79 6.0 4 52%191 156 156 156 0 0 0 0 0 0 0 0 0 0 661 2 96%335 255 0 0 0 0 0 0 0 0 0 0 0 0 590 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1290.09 6.0 3 60%218 175 175 0 0 0 0 0 0 0 0 0 0 0 567 2 85%301 230 0 0 0 0 0 0 0 0 0 0 0 0 531 3 60%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 712.30 6.0 3 33%131 115 115 0 0 0 0 0 0 0 0 0 0 0 360 1 83%292 0 0 0 0 0 0 0 0 0 0 0 0 0 292 3 33%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 1462.60 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.45 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1453.26 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1462.15 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1464.52 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 667 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 597 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1513.36 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1360.04 6.0 4 48%181 150 150 150 0 0 0 0 0 0 0 0 0 0 629 2 90%316 241 0 0 0 0 0 0 0 0 0 0 0 0 557 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1427.15 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 654 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 582 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1465.92 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 667 2 97%339 259 0 0 0 0 0 0 0 0 0 0 0 0 597 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1573.25 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1463.64 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 667 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1518.12 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 686 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 647 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.69 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.57 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1445.02 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1627.74 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1571.08 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 11/15/19 11 11/15/19 17 11/15/19 23 11/16/19 5:0 11/16/19 11 11/16/19 17 11/16/19 23 11/17/19 5:0 11/17/19 11 11/17/19 17 11/17/19 23 11/18/19 5:0 11/18/19 11 11/18/19 17 11/18/19 23 11/19/19 5:0 11/19/19 11 11/19/19 17 11/19/19 23 11/20/19 5:0 11/20/19 11 11/20/19 17 11/20/19 23 11/21/19 5:0 11/21/19 11 11/21/19 17 11/21/19 23 11/22/19 5:0 11/22/19 11 11/22/19 17 11/22/19 23 11/23/19 5:0 11/23/19 11 11/23/19 17 11/23/19 23 11/24/19 5:0 11/24/19 11 11/24/19 17 11/24/19 23 11/25/19 5:0 11/25/19 11 11/25/19 17 11/25/19 23 11/26/19 5:0 11/26/19 11 11/26/19 17 11/26/19 23 11/27/19 5:0 11/27/19 11 11/27/19 17 11/27/19 23 11/28/19 5:0 11/28/19 11 11/28/19 17 11/28/19 23 11/29/19 5:0 11/29/19 11 11/29/19 17 11/29/19 23 11/30/19 5:0 11/30/19 11 11/30/19 17 11/30/19 23 12/1/19 5:00 12/1/19 11:0 12/1/19 17:0 12/1/19 23:0 12/2/19 5:00 12/2/19 11:0 NEA BESS Scenario Analysis Data Analysis 2 RUNTIME (HOURS) - FUTURE SCENARIO, 0% SPIN JW HEAT REJECTION (MMBTU) - EXISTING SCENARIO, 100% SPIN JW HEAT REJECTION (MMBTU) - FUTURE SCENARIO, 0% SPIN Summary by Month Summary by Month Summary by Month Detailed Calculaon, Genset setup Detailed Calculaon, Genset setup Detailed Calculaon, Genset setup Detailed Calculaon, by Record Detailed Calculaon, by Record Detailed Calculaon, by Record Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Subtotal January 744 744 702 51 0 0 0 0 0 0 0 0 0 0 2,241 January 715 606 606 606 260 0 0 0 0 0 0 0 0 0 2,793 January 986 752 705 49 0 0 0 0 0 0 0 0 0 0 2,492 February 672 672 651 0 0 0 0 0 0 0 0 0 0 0 1,995 February 661 557 557 557 53 0 0 0 0 0 0 0 0 0 2,384 February 864 665 641 0 0 0 0 0 0 0 0 0 0 0 2,170 March 744 744 735 3 0 0 0 0 0 0 0 0 0 0 2,226 March 744 623 623 623 69 0 0 0 0 0 0 0 0 0 2,681 March 968 742 732 3 0 0 0 0 0 0 0 0 0 0 2,444 April 720 720 720 90 3 0 0 0 0 0 0 0 0 0 2,253 April 706 595 595 595 347 3 0 0 0 0 0 0 0 0 2,840 April 970 736 736 89 4 0 0 0 0 0 0 0 0 0 2,535 May 744 741 741 672 168 140 128 125 118 65 0 0 0 0 3,642 May 795 650 650 648 951 204 160 149 142 228 80 0 0 0 4,655 May 1,030 773 773 696 258 200 160 156 148 131 0 0 0 0 4,327 June 720 720 714 708 422 179 119 95 60 30 6 0 0 0 3,773 June 804 647 647 643 944 484 203 144 110 123 38 8 0 0 4,795 June 995 750 744 738 633 254 151 121 75 61 8 0 0 0 4,531 July 744 744 744 744 744 732 684 648 594 540 444 384 312 0 8,058 July 873 691 691 691 1,013 873 805 758 709 1,057 624 564 1,671 1,272 12,291 July 1,054 789 789 789 1,148 1,036 854 809 740 1,111 600 514 1,508 0 11,740 August 744 744 606 126 18 6 0 0 0 0 0 0 0 0 2,244 August 714 605 605 605 299 21 7 0 0 0 0 0 0 0 2,857 August 1,008 764 612 131 28 8 0 0 0 0 0 0 0 0 2,550 September 720 720 299 0 0 0 0 0 0 0 0 0 0 0 1,739 September 629 551 551 537 0 0 0 0 0 0 0 0 0 0 2,268 September 966 735 275 0 0 0 0 0 0 0 0 0 0 0 1,976 October 744 738 302 0 0 0 0 0 0 0 0 0 0 0 1,784 October 649 568 566 566 0 0 0 0 0 0 0 0 0 0 2,349 October 1,004 759 279 0 0 0 0 0 0 0 0 0 0 0 2,043 November 720 712 454 0 0 0 0 0 0 0 0 0 0 0 1,886 November 655 566 564 553 0 0 0 0 0 0 0 0 0 0 2,338 November 938 712 428 0 0 0 0 0 0 0 0 0 0 0 2,078 December 744 744 597 3 0 0 0 0 0 0 0 0 0 0 2,088 December 702 599 599 599 68 0 0 0 0 0 0 0 0 0 2,569 December 972 745 582 3 0 0 0 0 0 0 0 0 0 0 2,301 Year:8,760 8,743 7,265 2,398 1,356 1,057 931 868 772 635 450 384 312 0 33,929 Year:8,646 7,259 7,253 7,222 4,004 1,584 1,174 1,051 961 1,408 742 572 1,671 1,272 44,819 Year:11,756 8,922 7,296 2,497 2,071 1,499 1,166 1,086 963 1,303 608 514 1,508 0 41,188 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Unit ID 9 1 2 3 4 10 5 6 7 11 12A 12B 13 14 Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Simulate As 3516 3512B 3512B 3512B 3512B 3516 3512B 3512B 3512B 3512B 3512B 3512B 3512B 3512B Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Prime kW 1,135 865 865 865 1,322 1,135 1,050 1,050 1,050 1,360 900 900 3,300 3,300 Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100%Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100%Preferred 76%75%75%75%70%76%72%72%72%100%100%100%100%100% Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Pref. kW 863 649 649 649 925 863 756 756 756 1,360 900 900 3,300 3,300 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Staging Order 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Stage kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Scenario kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 Scenario kW 0 649 1,298 1,946 2,809 3,671 4,427 5,183 5,939 6,865 7,765 8,665 10,025 13,325 Scenario kW 863 1,511 2,160 2,809 3,734 4,597 5,353 6,109 6,865 8,225 9,125 10,025 13,325 16,625 # Gens Load HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS HOURS # Gens Load MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU # Gens Load MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU MMBTU 2 64%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 45%4.5 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 12.9 2 64%6.2 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 11.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.4 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 68%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 48%4.8 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 13.4 2 68%6.5 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 11.9 2 86%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 46%4.7 4.2 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.4 2 86%8.1 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.3 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 85%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 60%5.8 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 85%8.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.2 1 83%6 0 0 0 0 0 0 0 0 0 0 0 0 0 6 3 33%3.5 3.5 3.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 10.5 1 83%7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 7.8 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 NEA BESS Scenario Analysis Data Analysis 3 1692.10 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1596.19 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1763.49 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 732 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1759.18 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1813.16 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1655.42 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1817.96 6.0 4 65%235 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 752 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.79 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1820.47 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1593.36 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%263 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1713.95 6.0 4 61%223 177 177 177 0 0 0 0 0 0 0 0 0 0 755 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1678.13 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1595.56 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1404.05 6.0 4 50%186 153 153 153 0 0 0 0 0 0 0 0 0 0 645 2 93%325 248 0 0 0 0 0 0 0 0 0 0 0 0 574 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1609.95 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1563.80 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 702 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1529.35 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1348.00 6.0 4 48%179 149 149 149 0 0 0 0 0 0 0 0 0 0 625 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 552 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1422.57 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1540.25 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1548.12 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1379.04 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 636 2 91%320 244 0 0 0 0 0 0 0 0 0 0 0 0 564 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1441.69 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 95%333 255 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.69 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1604.27 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1443.74 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1481.90 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 673 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 603 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1505.97 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1561.71 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 701 3 72%259 201 201 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1361.48 6.0 4 48%181 150 150 150 0 0 0 0 0 0 0 0 0 0 630 2 90%316 241 0 0 0 0 0 0 0 0 0 0 0 0 558 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1476.92 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1470.51 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1584.39 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1367.69 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 632 2 90%317 242 0 0 0 0 0 0 0 0 0 0 0 0 560 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1491.40 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1522.61 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 688 3 70%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1551.36 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 658 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1348.59 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 625 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 553 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1479.65 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 603 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1514.11 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1533.19 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1375.21 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 635 2 91%319 244 0 0 0 0 0 0 0 0 0 0 0 0 563 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1525.88 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1532.77 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1548.74 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1381.06 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 637 2 91%320 245 0 0 0 0 0 0 0 0 0 0 0 0 565 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1461.68 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.89 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 686 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1568.16 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 664 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1382.10 6.0 4 49%184 151 151 151 0 0 0 0 0 0 0 0 0 0 637 2 91%321 245 0 0 0 0 0 0 0 0 0 0 0 0 565 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1419.24 6.0 4 51%188 154 154 154 0 0 0 0 0 0 0 0 0 0 651 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 579 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1453.25 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1542.33 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1352.76 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 627 2 90%314 240 0 0 0 0 0 0 0 0 0 0 0 0 554 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.57 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1493.98 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1560.39 6.0 4 56%205 165 165 165 0 0 0 0 0 0 0 0 0 0 701 3 72%259 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1381.86 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 637 2 91%320 245 0 0 0 0 0 0 0 0 0 0 0 0 565 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1522.82 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 688 3 70%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1550.59 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 658 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1597.79 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1495.05 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1696.73 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.71 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1812.95 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.93 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1782.62 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 83%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1803.31 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1876.33 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1712.43 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1831.40 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 795 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1838.35 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 797 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 759 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1791.63 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 742 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1621.52 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%268 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1640.17 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.13 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1788.95 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%292 225 225 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1600.04 6.0 4 57%209 169 169 169 0 0 0 0 0 0 0 0 0 0 715 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 675 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.89 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1653.33 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%272 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.80 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1446.69 6.0 4 52%191 156 156 156 0 0 0 0 0 0 0 0 0 0 661 2 96%335 255 0 0 0 0 0 0 0 0 0 0 0 0 590 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1568.89 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 664 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1643.26 6.0 4 59%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 690 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1717.52 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1498.40 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1697.57 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.39 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1858.69 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1775.53 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1855.09 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 232 232 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1952.85 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1913.30 6.0 4 68%245 193 193 193 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 787 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1757.95 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1886.00 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 814 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 777 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1925.89 6.0 4 69%247 194 194 194 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 792 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1994.63 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1874.80 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2054.83 6.0 5 55%203 164 164 164 239 0 0 0 0 0 0 0 0 0 934 3 95%333 254 254 0 0 0 0 0 0 0 0 0 0 0 840 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 12/2/19 17:0 12/2/19 23:0 12/3/19 5:00 12/3/19 11:0 12/3/19 17:0 12/3/19 23:0 12/4/19 5:00 12/4/19 11:0 12/4/19 17:0 12/4/19 23:0 12/5/19 5:00 12/5/19 11:0 12/5/19 17:0 12/5/19 23:0 12/6/19 5:00 12/6/19 11:0 12/6/19 17:0 12/6/19 23:0 12/7/19 5:00 12/7/19 11:0 12/7/19 17:0 12/7/19 23:0 12/8/19 5:00 12/8/19 11:0 12/8/19 17:0 12/8/19 23:0 12/9/19 5:00 12/9/19 11:0 12/9/19 17:0 12/9/19 23:0 12/10/19 5:0 12/10/19 11 12/10/19 17 12/10/19 23 12/11/19 5:0 12/11/19 11 12/11/19 17 12/11/19 23 12/12/19 5:0 12/12/19 11 12/12/19 17 12/12/19 23 12/13/19 5:0 12/13/19 11 12/13/19 17 12/13/19 23 12/14/19 5:0 12/14/19 11 12/14/19 17 12/14/19 23 12/15/19 5:0 12/15/19 11 12/15/19 17 12/15/19 23 12/16/19 5:0 12/16/19 11 12/16/19 17 12/16/19 23 12/17/19 5:0 12/17/19 11 12/17/19 17 12/17/19 23 12/18/19 5:0 12/18/19 11 12/18/19 17 12/18/19 23 12/19/19 5:0 12/19/19 11 12/19/19 17 12/19/19 23 12/20/19 5:0 12/20/19 11 12/20/19 17 12/20/19 23 12/21/19 5:0 12/21/19 11 12/21/19 17 12/21/19 23 12/22/19 5:0 12/22/19 11 12/22/19 17 12/22/19 23 12/23/19 5:0 12/23/19 11 12/23/19 17 12/23/19 23 12/24/19 5:0 12/24/19 11 12/24/19 17 12/24/19 23 12/25/19 5:0 12/25/19 11 12/25/19 17 12/25/19 23 12/26/19 5:0 12/26/19 11 12/26/19 17 12/26/19 23 12/27/19 5:0 NEA BESS Scenario Analysis Data Analysis 4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 90%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 NEA BESS Scenario Analysis Data Analysis 5 2135.59 6.0 5 57%210 169 169 169 245 0 0 0 0 0 0 0 0 0 963 3 99%345 263 263 0 0 0 0 0 0 0 0 0 0 0 872 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2180.36 6.0 5 58%214 172 172 172 249 0 0 0 0 0 0 0 0 0 978 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 915 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2002.93 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 916 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2037.81 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 928 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 834 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2058.11 6.0 5 55%203 164 164 164 239 0 0 0 0 0 0 0 0 0 935 3 95%333 254 254 0 0 0 0 0 0 0 0 0 0 0 842 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2098.97 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1942.68 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%316 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1999.00 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 915 3 93%324 247 247 0 0 0 0 0 0 0 0 0 0 0 819 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2089.24 6.0 5 56%206 166 166 166 242 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 854 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2008.00 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 918 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 822 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1809.91 6.0 4 64%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1882.80 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%306 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1931.43 6.0 4 69%247 194 194 194 0 0 0 0 0 0 0 0 0 0 829 3 89%314 240 240 0 0 0 0 0 0 0 0 0 0 0 794 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1955.05 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%317 243 243 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1783.20 6.0 4 63%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1878.51 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 811 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 774 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1923.38 6.0 4 68%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1953.03 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1812.10 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/1/20 5:00 1847.03 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 800 3 86%301 231 231 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1907.23 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 821 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 785 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1996.44 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 914 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 818 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1892.20 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/2/20 5:00 2061.07 6.0 5 55%203 165 165 165 239 0 0 0 0 0 0 0 0 0 937 3 95%334 255 255 0 0 0 0 0 0 0 0 0 0 0 843 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2072.97 6.0 5 56%204 165 165 165 240 0 0 0 0 0 0 0 0 0 941 3 96%335 256 256 0 0 0 0 0 0 0 0 0 0 0 847 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2158.78 6.0 5 58%212 170 170 170 247 0 0 0 0 0 0 0 0 0 971 3 100%348 266 266 0 0 0 0 0 0 0 0 0 0 0 881 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1992.10 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 912 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 816 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1/3/20 5:00 2093.22 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 948 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 855 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2103.83 6.0 5 56%207 167 167 167 243 0 0 0 0 0 0 0 0 0 952 3 97%340 260 260 0 0 0 0 0 0 0 0 0 0 0 859 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2117.84 6.0 5 57%208 168 168 168 244 0 0 0 0 0 0 0 0 0 956 3 98%342 261 261 0 0 0 0 0 0 0 0 0 0 0 865 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1947.86 6.0 5 52%193 158 158 158 229 0 0 0 0 0 0 0 0 0 897 3 90%316 242 242 0 0 0 0 0 0 0 0 0 0 0 800 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1/4/20 5:00 2058.14 6.0 5 55%203 164 164 164 239 0 0 0 0 0 0 0 0 0 935 3 95%333 254 254 0 0 0 0 0 0 0 0 0 0 0 842 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2042.13 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 930 3 95%331 252 252 0 0 0 0 0 0 0 0 0 0 0 835 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2084.82 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 945 3 97%337 257 257 0 0 0 0 0 0 0 0 0 0 0 852 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1890.79 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 815 3 88%308 235 235 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/5/20 5:00 1937.65 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 831 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 796 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1989.44 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%323 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2118.41 6.0 5 57%208 168 168 168 244 0 0 0 0 0 0 0 0 0 957 3 98%342 261 261 0 0 0 0 0 0 0 0 0 0 0 865 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1963.80 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 902 3 91%319 243 243 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1/6/20 5:00 2109.21 6.0 5 56%208 168 168 168 243 0 0 0 0 0 0 0 0 0 953 3 98%341 260 260 0 0 0 0 0 0 0 0 0 0 0 861 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2138.61 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 964 3 99%345 264 264 0 0 0 0 0 0 0 0 0 0 0 873 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2207.47 6.0 5 59%216 173 173 173 252 0 0 0 0 0 0 0 0 0 988 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 924 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2036.23 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 928 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 833 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1/7/20 5:00 2164.26 6.0 5 58%212 171 171 171 248 0 0 0 0 0 0 0 0 0 973 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 909 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2169.55 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 974 4 77%275 212 212 212 0 0 0 0 0 0 0 0 0 0 911 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2216.69 6.0 5 59%217 174 174 174 252 0 0 0 0 0 0 0 0 0 991 4 79%280 216 216 216 0 0 0 0 0 0 0 0 0 0 927 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2083.15 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 944 3 96%337 257 257 0 0 0 0 0 0 0 0 0 0 0 851 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1/8/20 5:00 2214.75 6.0 5 59%217 174 174 174 252 0 0 0 0 0 0 0 0 0 990 4 79%280 216 216 216 0 0 0 0 0 0 0 0 0 0 927 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2224.57 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 994 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 930 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2202.32 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 986 4 78%278 215 215 215 0 0 0 0 0 0 0 0 0 0 922 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1942.65 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%316 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/9/20 5:00 1994.77 6.0 5 53%198 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1956.00 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 803 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1994.53 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1832.96 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1963.48 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 902 3 91%319 243 243 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1988.78 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%323 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1952.47 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1745.42 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1786.69 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1857.06 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1850.56 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 802 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 764 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1692.94 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1731.84 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.85 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1757.50 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1642.11 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 209 209 0 0 0 0 0 0 0 0 0 0 0 690 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.69 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.69 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1748.07 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.53 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1797.84 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1791.36 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 742 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1867.61 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 807 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.15 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1909.18 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 785 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1875.29 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1947.34 6.0 5 52%193 158 158 158 229 0 0 0 0 0 0 0 0 0 896 3 90%316 242 242 0 0 0 0 0 0 0 0 0 0 0 800 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1811.75 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1967.37 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 903 3 91%319 244 244 0 0 0 0 0 0 0 0 0 0 0 807 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1935.72 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 831 3 90%314 240 240 0 0 0 0 0 0 0 0 0 0 0 795 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2006.94 6.0 5 54%199 161 161 161 234 0 0 0 0 0 0 0 0 0 917 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 822 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1879.39 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 812 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 774 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2022.78 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 923 3 94%328 250 250 0 0 0 0 0 0 0 0 0 0 0 828 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1916.14 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 824 3 89%312 238 238 0 0 0 0 0 0 0 0 0 0 0 788 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1900.95 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 819 3 88%309 237 237 0 0 0 0 0 0 0 0 0 0 0 782 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1717.40 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1761.19 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 732 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1804.41 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1799.06 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1630.44 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1727.12 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.29 6.0 4 63%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1874.21 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 772 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.02 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1857.08 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1696.20 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2007.57 6.0 5 54%199 161 161 161 235 0 0 0 0 0 0 0 0 0 918 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 822 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1896.56 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 817 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 12/27/19 11 12/27/19 17 12/27/19 23 12/28/19 5:0 12/28/19 11 12/28/19 17 12/28/19 23 12/29/19 5:0 12/29/19 11 12/29/19 17 12/29/19 23 12/30/19 5:0 12/30/19 11 12/30/19 17 12/30/19 23 12/31/19 5:0 12/31/19 11 12/31/19 17 12/31/19 23 1/1/20 11:00 1/1/20 17:00 1/1/20 23:00 1/2/20 11:00 1/2/20 17:00 1/2/20 23:00 1/3/20 11:00 1/3/20 17:00 1/3/20 23:00 1/4/20 11:00 1/4/20 17:00 1/4/20 23:00 1/5/20 11:00 1/5/20 17:00 1/5/20 23:00 1/6/20 11:00 1/6/20 17:00 1/6/20 23:00 1/7/20 11:00 1/7/20 17:00 1/7/20 23:00 1/8/20 11:00 1/8/20 17:00 1/8/20 23:00 1/9/20 11:00 1/9/20 17:00 1/9/20 23:00 1/10/20 5:00 1/10/20 11:0 1/10/20 17:0 1/10/20 23:0 1/11/20 5:00 1/11/20 11:0 1/11/20 17:0 1/11/20 23:0 1/12/20 5:00 1/12/20 11:0 1/12/20 17:0 1/12/20 23:0 1/13/20 5:00 1/13/20 11:0 1/13/20 17:0 1/13/20 23:0 1/14/20 5:00 1/14/20 11:0 1/14/20 17:0 1/14/20 23:0 1/15/20 5:00 1/15/20 11:0 1/15/20 17:0 1/15/20 23:0 1/16/20 5:00 1/16/20 11:0 1/16/20 17:0 1/16/20 23:0 1/17/20 5:00 1/17/20 11:0 1/17/20 17:0 1/17/20 23:0 1/18/20 5:00 1/18/20 11:0 1/18/20 17:0 1/18/20 23:0 1/19/20 5:00 1/19/20 11:0 1/19/20 17:0 1/19/20 23:0 1/20/20 5:00 1/20/20 11:0 1/20/20 17:0 1/20/20 23:0 NEA BESS Scenario Analysis Data Analysis 6 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 95%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 98%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 79%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.5 4.5 4.5 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 94%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 NEA BESS Scenario Analysis Data Analysis 7 2076.94 6.0 5 56%205 166 166 166 240 0 0 0 0 0 0 0 0 0 942 3 96%336 256 256 0 0 0 0 0 0 0 0 0 0 0 849 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2044.16 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 931 3 95%331 253 253 0 0 0 0 0 0 0 0 0 0 0 836 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2067.69 6.0 5 55%204 165 165 165 240 0 0 0 0 0 0 0 0 0 939 3 96%335 255 255 0 0 0 0 0 0 0 0 0 0 0 845 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1880.03 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 812 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 775 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1969.31 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 904 3 91%320 244 244 0 0 0 0 0 0 0 0 0 0 0 808 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1924.50 6.0 4 69%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2029.89 6.0 5 54%201 163 163 163 236 0 0 0 0 0 0 0 0 0 926 3 94%329 251 251 0 0 0 0 0 0 0 0 0 0 0 831 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1839.65 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2003.95 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 916 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1927.04 6.0 4 69%247 194 194 194 0 0 0 0 0 0 0 0 0 0 828 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 792 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2009.16 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 918 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 823 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1863.02 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%304 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2013.98 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 920 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 825 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1972.52 6.0 5 53%196 159 159 159 232 0 0 0 0 0 0 0 0 0 905 3 91%320 244 244 0 0 0 0 0 0 0 0 0 0 0 809 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2012.96 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 920 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 824 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1903.63 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 820 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 783 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1978.39 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 907 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2009.05 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 918 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 823 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2108.30 6.0 5 56%208 167 167 167 243 0 0 0 0 0 0 0 0 0 953 3 98%341 260 260 0 0 0 0 0 0 0 0 0 0 0 861 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1994.56 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2068.94 6.0 5 55%204 165 165 165 240 0 0 0 0 0 0 0 0 0 939 3 96%335 255 255 0 0 0 0 0 0 0 0 0 0 0 846 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2074.46 6.0 5 56%205 165 165 165 240 0 0 0 0 0 0 0 0 0 941 3 96%336 256 256 0 0 0 0 0 0 0 0 0 0 0 848 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2183.33 6.0 5 58%214 172 172 172 250 0 0 0 0 0 0 0 0 0 979 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 916 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2028.66 6.0 5 54%201 163 163 163 236 0 0 0 0 0 0 0 0 0 925 3 94%329 251 251 0 0 0 0 0 0 0 0 0 0 0 830 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2174.86 6.0 5 58%213 171 171 171 249 0 0 0 0 0 0 0 0 0 976 4 77%275 213 213 213 0 0 0 0 0 0 0 0 0 0 913 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2177.61 6.0 5 58%214 172 172 172 249 0 0 0 0 0 0 0 0 0 977 4 78%275 213 213 213 0 0 0 0 0 0 0 0 0 0 914 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2195.67 6.0 5 59%215 173 173 173 251 0 0 0 0 0 0 0 0 0 984 4 78%278 214 214 214 0 0 0 0 0 0 0 0 0 0 920 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2050.68 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 933 3 95%332 253 253 0 0 0 0 0 0 0 0 0 0 0 839 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2203.65 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 986 4 78%278 215 215 215 0 0 0 0 0 0 0 0 0 0 923 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2225.11 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 994 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 930 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2243.24 6.0 5 60%219 175 175 175 255 0 0 0 0 0 0 0 0 0 1,000 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 937 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2094.91 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 948 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 856 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2190.90 6.0 5 59%215 172 172 172 250 0 0 0 0 0 0 0 0 0 982 4 78%277 214 214 214 0 0 0 0 0 0 0 0 0 0 918 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2212.56 6.0 5 59%217 174 174 174 252 0 0 0 0 0 0 0 0 0 989 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 926 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2184.91 6.0 5 59%214 172 172 172 250 0 0 0 0 0 0 0 0 0 980 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 916 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1993.86 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2125.76 6.0 5 57%209 168 168 168 245 0 0 0 0 0 0 0 0 0 959 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 868 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2137.13 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 963 3 99%345 263 263 0 0 0 0 0 0 0 0 0 0 0 872 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2112.35 6.0 5 57%208 168 168 168 244 0 0 0 0 0 0 0 0 0 954 3 98%341 261 261 0 0 0 0 0 0 0 0 0 0 0 862 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1955.96 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 803 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2109.06 6.0 5 56%208 167 167 167 243 0 0 0 0 0 0 0 0 0 953 3 98%341 260 260 0 0 0 0 0 0 0 0 0 0 0 861 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2080.04 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 943 3 96%336 257 257 0 0 0 0 0 0 0 0 0 0 0 850 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2096.90 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 949 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1999.31 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 915 3 93%324 248 248 0 0 0 0 0 0 0 0 0 0 0 819 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2/1/20 5:00 2103.13 6.0 5 56%207 167 167 167 243 0 0 0 0 0 0 0 0 0 951 3 97%340 259 259 0 0 0 0 0 0 0 0 0 0 0 859 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2086.29 6.0 5 56%206 166 166 166 241 0 0 0 0 0 0 0 0 0 945 3 97%337 258 258 0 0 0 0 0 0 0 0 0 0 0 852 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2095.85 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 949 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 856 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1868.73 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/2/20 5:00 1825.83 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 85%298 228 228 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1801.73 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 746 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.91 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1640.64 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/3/20 5:00 1747.43 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1696.85 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1675.26 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1529.37 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/4/20 5:00 1672.63 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1634.07 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1634.03 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1458.25 6.0 4 52%193 157 157 157 0 0 0 0 0 0 0 0 0 0 665 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/5/20 5:00 1612.14 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1703.03 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1760.79 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1522.37 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 687 3 70%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/6/20 5:00 1696.10 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1727.13 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1677.83 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1489.61 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/7/20 5:00 1667.35 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1572.94 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1638.80 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1515.31 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/8/20 5:00 1602.95 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1615.36 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1704.03 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.47 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/9/20 5:00 1598.18 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1667.42 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1768.36 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1670.86 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1863.15 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%304 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1809.20 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1964.58 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 902 3 91%319 244 244 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1834.05 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1988.90 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%323 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1952.23 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1898.78 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.21 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1893.93 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 780 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1913.43 6.0 4 68%245 193 193 193 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 787 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1950.72 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1850.80 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 802 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 764 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2023.22 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 923 3 94%328 250 250 0 0 0 0 0 0 0 0 0 0 0 828 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2046.82 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 931 3 95%331 253 253 0 0 0 0 0 0 0 0 0 0 0 837 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2019.05 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 922 3 93%327 250 250 0 0 0 0 0 0 0 0 0 0 0 827 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1814.63 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1891.80 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1844.27 6.0 4 66%238 187 187 187 0 0 0 0 0 0 0 0 0 0 800 3 85%301 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.15 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/21/20 5:00 1/21/20 11:0 1/21/20 17:0 1/21/20 23:0 1/22/20 5:00 1/22/20 11:0 1/22/20 17:0 1/22/20 23:0 1/23/20 5:00 1/23/20 11:0 1/23/20 17:0 1/23/20 23:0 1/24/20 5:00 1/24/20 11:0 1/24/20 17:0 1/24/20 23:0 1/25/20 5:00 1/25/20 11:0 1/25/20 17:0 1/25/20 23:0 1/26/20 5:00 1/26/20 11:0 1/26/20 17:0 1/26/20 23:0 1/27/20 5:00 1/27/20 11:0 1/27/20 17:0 1/27/20 23:0 1/28/20 5:00 1/28/20 11:0 1/28/20 17:0 1/28/20 23:0 1/29/20 5:00 1/29/20 11:0 1/29/20 17:0 1/29/20 23:0 1/30/20 5:00 1/30/20 11:0 1/30/20 17:0 1/30/20 23:0 1/31/20 5:00 1/31/20 11:0 1/31/20 17:0 1/31/20 23:0 2/1/20 11:00 2/1/20 17:00 2/1/20 23:00 2/2/20 11:00 2/2/20 17:00 2/2/20 23:00 2/3/20 11:00 2/3/20 17:00 2/3/20 23:00 2/4/20 11:00 2/4/20 17:00 2/4/20 23:00 2/5/20 11:00 2/5/20 17:00 2/5/20 23:00 2/6/20 11:00 2/6/20 17:00 2/6/20 23:00 2/7/20 11:00 2/7/20 17:00 2/7/20 23:00 2/8/20 11:00 2/8/20 17:00 2/8/20 23:00 2/9/20 11:00 2/9/20 17:00 2/9/20 23:00 2/10/20 5:00 2/10/20 11:0 2/10/20 17:0 2/10/20 23:0 2/11/20 5:00 2/11/20 11:0 2/11/20 17:0 2/11/20 23:0 2/12/20 5:00 2/12/20 11:0 2/12/20 17:0 2/12/20 23:0 2/13/20 5:00 2/13/20 11:0 2/13/20 17:0 2/13/20 23:0 2/14/20 5:00 2/14/20 11:0 2/14/20 17:0 NEA BESS Scenario Analysis Data Analysis 8 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 95%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 3 96%9.0 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.4 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 98%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 3 96%9.0 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.4 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.7 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.6 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.7 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 98%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 94%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 95%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 NEA BESS Scenario Analysis Data Analysis 9 1673.24 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.61 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 764 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1735.10 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1682.54 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1520.75 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 687 3 70%253 197 197 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.31 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1706.03 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1705.49 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1556.52 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1696.61 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.35 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1753.59 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1631.87 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1748.93 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.97 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1659.04 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 736 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1530.50 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1646.44 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.46 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1769.10 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1558.85 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1631.58 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1644.84 6.0 4 59%214 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1765.54 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1690.08 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1836.06 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 797 3 85%299 230 230 0 0 0 0 0 0 0 0 0 0 0 759 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1892.26 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1875.32 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.65 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 764 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1803.98 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1781.92 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1895.11 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 817 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 780 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1822.51 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1898.17 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1853.55 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1944.77 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 834 3 90%316 241 241 0 0 0 0 0 0 0 0 0 0 0 799 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1833.61 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1978.66 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 907 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1868.32 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1914.01 6.0 4 68%245 193 193 193 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 787 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1772.90 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1902.13 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 819 3 88%309 237 237 0 0 0 0 0 0 0 0 0 0 0 783 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1899.81 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 782 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1948.93 6.0 5 52%193 158 158 158 230 0 0 0 0 0 0 0 0 0 897 3 90%316 242 242 0 0 0 0 0 0 0 0 0 0 0 800 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1800.28 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 746 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1902.19 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 819 3 88%309 237 237 0 0 0 0 0 0 0 0 0 0 0 783 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1835.37 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1844.44 6.0 4 66%238 187 187 187 0 0 0 0 0 0 0 0 0 0 800 3 85%301 230 230 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1737.99 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1846.39 6.0 4 66%238 187 187 187 0 0 0 0 0 0 0 0 0 0 800 3 85%301 231 231 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1811.56 6.0 4 64%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1846.77 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 800 3 85%301 231 231 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1795.31 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 783 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 744 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1946.20 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 834 3 90%316 242 242 0 0 0 0 0 0 0 0 0 0 0 799 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1769.87 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1841.22 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1751.19 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1803.01 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1795.03 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 783 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 744 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.20 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1530.70 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/1/20 5:00 1576.93 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 707 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 667 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1720.10 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1832.50 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 795 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1664.07 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/2/20 5:00 1752.79 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1726.89 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1797.76 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.66 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/3/20 5:00 1844.09 6.0 4 66%238 187 187 187 0 0 0 0 0 0 0 0 0 0 799 3 85%301 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1840.89 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1917.36 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 824 3 89%312 238 238 0 0 0 0 0 0 0 0 0 0 0 788 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1834.87 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/4/20 5:00 1924.73 6.0 4 69%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1862.92 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%304 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1923.97 6.0 4 68%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1825.27 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/5/20 5:00 1936.19 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 831 3 90%315 240 240 0 0 0 0 0 0 0 0 0 0 0 795 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1835.95 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 797 3 85%299 230 230 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1906.83 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 821 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 784 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1784.21 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/6/20 5:00 1874.83 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1766.07 6.0 4 63%229 181 181 181 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1702.41 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1604.16 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/7/20 5:00 1660.53 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 736 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1391.42 6.0 4 50%185 152 152 152 0 0 0 0 0 0 0 0 0 0 641 2 92%323 246 0 0 0 0 0 0 0 0 0 0 0 0 569 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1647.43 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1492.25 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/8/20 6:00 1553.18 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1591.20 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1604.27 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/9/20 0:00 1547.90 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/9/20 6:00 1791.92 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1779.57 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 738 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1811.81 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1762.56 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 732 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1929.63 6.0 4 69%247 194 194 194 0 0 0 0 0 0 0 0 0 0 829 3 89%314 240 240 0 0 0 0 0 0 0 0 0 0 0 793 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1785.32 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/14/20 23:0 2/15/20 5:00 2/15/20 11:0 2/15/20 17:0 2/15/20 23:0 2/16/20 5:00 2/16/20 11:0 2/16/20 17:0 2/16/20 23:0 2/17/20 5:00 2/17/20 11:0 2/17/20 17:0 2/17/20 23:0 2/18/20 5:00 2/18/20 11:0 2/18/20 17:0 2/18/20 23:0 2/19/20 5:00 2/19/20 11:0 2/19/20 17:0 2/19/20 23:0 2/20/20 5:00 2/20/20 11:0 2/20/20 17:0 2/20/20 23:0 2/21/20 5:00 2/21/20 11:0 2/21/20 17:0 2/21/20 23:0 2/22/20 5:00 2/22/20 11:0 2/22/20 17:0 2/22/20 23:0 2/23/20 5:00 2/23/20 11:0 2/23/20 17:0 2/23/20 23:0 2/24/20 5:00 2/24/20 11:0 2/24/20 17:0 2/24/20 23:0 2/25/20 5:00 2/25/20 11:0 2/25/20 17:0 2/25/20 23:0 2/26/20 5:00 2/26/20 11:0 2/26/20 17:0 2/26/20 23:0 2/27/20 5:00 2/27/20 11:0 2/27/20 17:0 2/27/20 23:0 2/28/20 5:00 2/28/20 11:0 2/28/20 17:0 2/28/20 23:0 2/29/20 5:00 2/29/20 11:0 2/29/20 17:0 2/29/20 23:0 3/1/20 11:00 3/1/20 17:00 3/1/20 23:00 3/2/20 11:00 3/2/20 17:00 3/2/20 23:00 3/3/20 11:00 3/3/20 17:00 3/3/20 23:00 3/4/20 11:00 3/4/20 17:00 3/4/20 23:00 3/5/20 11:00 3/5/20 17:00 3/5/20 23:00 3/6/20 11:00 3/6/20 17:00 3/6/20 23:00 3/7/20 11:00 3/7/20 17:00 3/7/20 23:00 3/8/20 12:00 3/8/20 18:00 3/9/20 12:00 3/9/20 18:00 3/10/20 0:00 3/10/20 6:00 3/10/20 12:0 NEA BESS Scenario Analysis Data Analysis 10 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 NEA BESS Scenario Analysis Data Analysis 11 1786.90 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1794.34 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1997.20 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 914 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 818 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1866.81 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 807 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1823.42 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.97 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1859.31 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1836.42 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 797 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 759 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1804.56 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.52 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1832.57 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 795 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1767.28 6.0 4 63%229 181 181 181 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1735.67 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1747.17 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1775.29 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1771.36 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1748.67 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.96 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1737.92 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.82 6.0 4 62%226 179 179 179 0 0 0 0 0 0 0 0 0 0 764 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.45 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1689.92 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1743.94 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1718.67 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1727.83 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1685.07 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1732.91 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1733.78 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1759.17 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1700.38 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1746.11 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1677.91 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1715.65 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1678.43 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1732.71 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.75 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1727.97 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1691.32 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1740.45 6.0 4 62%226 179 179 179 0 0 0 0 0 0 0 0 0 0 764 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.55 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.34 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1682.51 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1713.08 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1712.33 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.42 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 218 218 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1689.76 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.23 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1677.05 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.57 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1695.12 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1751.94 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1700.71 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.87 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1680.64 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.86 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.13 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.14 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1673.61 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1712.25 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.91 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1732.27 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1672.33 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1696.47 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1663.28 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.39 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1674.62 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%275 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.98 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1714.56 6.0 4 61%223 177 177 177 0 0 0 0 0 0 0 0 0 0 755 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1746.85 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1695.55 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 78%279 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.87 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1744.01 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1774.78 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1757.50 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1769.29 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.13 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.08 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1755.81 6.0 4 63%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1788.76 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 225 225 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.10 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.24 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.94 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.63 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1765.98 6.0 4 63%229 181 181 181 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1754.43 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 769 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/1/20 0:00 1701.84 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/1/20 6:00 1754.25 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 769 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1736.03 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1731.35 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/2/20 0:00 1690.17 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/2/20 6:00 1728.50 6.0 4 62%224 178 178 178 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1746.26 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1734.81 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/3/20 0:00 1695.72 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/3/20 6:00 1735.72 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1742.97 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.73 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/4/20 0:00 1699.62 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/4/20 6:00 1701.68 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 216 216 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/10/20 18:0 3/11/20 0:00 3/11/20 6:00 3/11/20 12:0 3/11/20 18:0 3/12/20 0:00 3/12/20 6:00 3/12/20 12:0 3/12/20 18:0 3/13/20 0:00 3/13/20 6:00 3/13/20 12:0 3/13/20 18:0 3/14/20 0:00 3/14/20 6:00 3/14/20 12:0 3/14/20 18:0 3/15/20 0:00 3/15/20 6:00 3/15/20 12:0 3/15/20 18:0 3/16/20 0:00 3/16/20 6:00 3/16/20 12:0 3/16/20 18:0 3/17/20 0:00 3/17/20 6:00 3/17/20 12:0 3/17/20 18:0 3/18/20 0:00 3/18/20 6:00 3/18/20 12:0 3/18/20 18:0 3/19/20 0:00 3/19/20 6:00 3/19/20 12:0 3/19/20 18:0 3/20/20 0:00 3/20/20 6:00 3/20/20 12:0 3/20/20 18:0 3/21/20 0:00 3/21/20 6:00 3/21/20 12:0 3/21/20 18:0 3/22/20 0:00 3/22/20 6:00 3/22/20 12:0 3/22/20 18:0 3/23/20 0:00 3/23/20 6:00 3/23/20 12:0 3/23/20 18:0 3/24/20 0:00 3/24/20 6:00 3/24/20 12:0 3/24/20 18:0 3/25/20 0:00 3/25/20 6:00 3/25/20 12:0 3/25/20 18:0 3/26/20 0:00 3/26/20 6:00 3/26/20 12:0 3/26/20 18:0 3/27/20 0:00 3/27/20 6:00 3/27/20 12:0 3/27/20 18:0 3/28/20 0:00 3/28/20 6:00 3/28/20 12:0 3/28/20 18:0 3/29/20 0:00 3/29/20 6:00 3/29/20 12:0 3/29/20 18:0 3/30/20 0:00 3/30/20 6:00 3/30/20 12:0 3/30/20 18:0 3/31/20 0:00 3/31/20 6:00 3/31/20 12:0 3/31/20 18:0 4/1/20 12:00 4/1/20 18:00 4/2/20 12:00 4/2/20 18:00 4/3/20 12:00 4/3/20 18:00 NEA BESS Scenario Analysis Data Analysis 12 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 NEA BESS Scenario Analysis Data Analysis 13 1704.06 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1750.52 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/5/20 0:00 1701.85 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/5/20 6:00 1710.04 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 753 3 79%281 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1692.82 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1765.24 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/6/20 0:00 1731.76 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/6/20 6:00 1742.09 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 764 3 81%285 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1698.43 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1723.74 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/7/20 0:00 1692.22 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/7/20 6:00 1728.56 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1732.70 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.67 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/8/20 0:00 1693.46 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/8/20 6:00 1732.91 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.85 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.92 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/9/20 0:00 1681.85 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%277 213 213 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/9/20 6:00 1712.48 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1677.68 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1701.89 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1678.90 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1707.59 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1671.53 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1689.80 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1665.68 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1690.58 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1720.96 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1720.54 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1672.34 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1695.92 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.26 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1706.10 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1663.38 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1700.21 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1691.93 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1697.00 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1662.51 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1685.38 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1697.09 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1697.07 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1649.67 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1710.60 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 753 3 79%281 216 216 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1787.34 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.80 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.49 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1766.86 6.0 4 63%229 181 181 181 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1742.81 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1761.03 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1740.29 6.0 4 62%226 179 179 179 0 0 0 0 0 0 0 0 0 0 764 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.14 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1747.59 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.64 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1727.31 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1751.00 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1760.87 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1756.17 6.0 4 63%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1722.75 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1755.06 6.0 4 62%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1785.06 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1780.43 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 738 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1726.20 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1770.82 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1769.17 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1771.93 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.11 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1803.35 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1813.37 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1798.96 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1756.82 6.0 4 63%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1817.08 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%297 227 227 0 0 0 0 0 0 0 0 0 0 0 752 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1847.13 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 800 3 86%301 231 231 0 0 0 0 0 0 0 0 0 0 0 763 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1808.82 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1781.12 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1829.34 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 756 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1827.79 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 756 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1815.67 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.43 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1796.75 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 783 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 744 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1800.09 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1819.70 6.0 4 65%235 185 185 185 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1823.21 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1841.26 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1821.40 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1984.79 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 910 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 814 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1948.85 6.0 5 52%193 158 158 158 229 0 0 0 0 0 0 0 0 0 897 3 90%316 242 242 0 0 0 0 0 0 0 0 0 0 0 800 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1955.02 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%317 243 243 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1942.05 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1978.70 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 907 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1959.91 6.0 5 52%194 159 159 159 230 0 0 0 0 0 0 0 0 0 901 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 804 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2004.09 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 916 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1983.36 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 813 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2011.64 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 919 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 824 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2003.21 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 916 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2092.47 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 948 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 855 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2116.33 6.0 5 57%208 168 168 168 244 0 0 0 0 0 0 0 0 0 956 3 98%342 261 261 0 0 0 0 0 0 0 0 0 0 0 864 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2087.98 6.0 5 56%206 166 166 166 241 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 853 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2053.06 6.0 5 55%203 164 164 164 238 0 0 0 0 0 0 0 0 0 934 3 95%332 254 254 0 0 0 0 0 0 0 0 0 0 0 840 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/4/20 12:00 4/4/20 18:00 4/5/20 12:00 4/5/20 18:00 4/6/20 12:00 4/6/20 18:00 4/7/20 12:00 4/7/20 18:00 4/8/20 12:00 4/8/20 18:00 4/9/20 12:00 4/9/20 18:00 4/10/20 0:00 4/10/20 6:00 4/10/20 12:0 4/10/20 18:0 4/11/20 0:00 4/11/20 6:00 4/11/20 12:0 4/11/20 18:0 4/12/20 0:00 4/12/20 6:00 4/12/20 12:0 4/12/20 18:0 4/13/20 0:00 4/13/20 6:00 4/13/20 12:0 4/13/20 18:0 4/14/20 0:00 4/14/20 6:00 4/14/20 12:0 4/14/20 18:0 4/15/20 0:00 4/15/20 6:00 4/15/20 12:0 4/15/20 18:0 4/16/20 0:00 4/16/20 6:00 4/16/20 12:0 4/16/20 18:0 4/17/20 0:00 4/17/20 6:00 4/17/20 12:0 4/17/20 18:0 4/18/20 0:00 4/18/20 6:00 4/18/20 12:0 4/18/20 18:0 4/19/20 0:00 4/19/20 6:00 4/19/20 12:0 4/19/20 18:0 4/20/20 0:00 4/20/20 6:00 4/20/20 12:0 4/20/20 18:0 4/21/20 0:00 4/21/20 6:00 4/21/20 12:0 4/21/20 18:0 4/22/20 0:00 4/22/20 6:00 4/22/20 12:0 4/22/20 18:0 4/23/20 0:00 4/23/20 6:00 4/23/20 12:0 4/23/20 18:0 4/24/20 0:00 4/24/20 6:00 4/24/20 12:0 4/24/20 18:0 4/25/20 0:00 4/25/20 6:00 4/25/20 12:0 4/25/20 18:0 4/26/20 0:00 4/26/20 6:00 4/26/20 12:0 4/26/20 18:0 4/27/20 0:00 4/27/20 6:00 4/27/20 12:0 4/27/20 18:0 4/28/20 0:00 4/28/20 6:00 4/28/20 12:0 4/28/20 18:0 4/29/20 0:00 NEA BESS Scenario Analysis Data Analysis 14 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 NEA BESS Scenario Analysis Data Analysis 15 2160.86 6.0 5 58%212 171 171 171 248 0 0 0 0 0 0 0 0 0 971 4 77%274 211 211 211 0 0 0 0 0 0 0 0 0 0 908 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2178.63 6.0 5 58%214 172 172 172 249 0 0 0 0 0 0 0 0 0 978 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 914 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2123.26 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 958 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 867 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2098.94 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2203.65 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 986 4 78%278 215 215 215 0 0 0 0 0 0 0 0 0 0 923 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2171.56 6.0 5 58%213 171 171 171 249 0 0 0 0 0 0 0 0 0 975 4 77%275 212 212 212 0 0 0 0 0 0 0 0 0 0 912 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2151.60 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 968 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 878 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/1/20 0:00 2099.58 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 858 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/1/20 6:00 2173.95 6.0 5 58%213 171 171 171 249 0 0 0 0 0 0 0 0 0 976 4 77%275 212 212 212 0 0 0 0 0 0 0 0 0 0 912 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2173.34 6.0 5 58%213 171 171 171 249 0 0 0 0 0 0 0 0 0 976 4 77%275 212 212 212 0 0 0 0 0 0 0 0 0 0 912 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2226.65 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 994 4 79%281 217 217 217 0 0 0 0 0 0 0 0 0 0 931 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/2/20 0:00 2193.46 6.0 5 59%215 172 172 172 250 0 0 0 0 0 0 0 0 0 983 4 78%277 214 214 214 0 0 0 0 0 0 0 0 0 0 919 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/2/20 6:00 2297.52 6.0 5 62%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,019 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 956 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2306.52 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,022 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 959 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2361.76 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,041 4 84%297 227 227 227 0 0 0 0 0 0 0 0 0 0 979 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/3/20 0:00 2302.23 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,020 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 957 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/3/20 6:00 2421.81 6.0 5 65%235 186 186 186 269 0 0 0 0 0 0 0 0 0 1,061 4 86%303 232 232 232 0 0 0 0 0 0 0 0 0 0 1,000 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2411.75 6.0 5 65%234 185 185 185 269 0 0 0 0 0 0 0 0 0 1,058 4 86%302 232 232 232 0 0 0 0 0 0 0 0 0 0 997 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2436.78 6.0 5 65%236 186 186 186 271 0 0 0 0 0 0 0 0 0 1,066 4 87%305 234 234 234 0 0 0 0 0 0 0 0 0 0 1,006 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/4/20 0:00 2403.10 6.0 5 64%233 185 185 185 268 0 0 0 0 0 0 0 0 0 1,055 4 86%301 231 231 231 0 0 0 0 0 0 0 0 0 0 994 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/4/20 6:00 2609.02 6.0 5 70%251 196 196 196 285 0 0 0 0 0 0 0 0 0 1,125 4 93%325 248 248 248 0 0 0 0 0 0 0 0 0 0 1,070 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2395.12 6.0 5 64%233 184 184 184 267 0 0 0 0 0 0 0 0 0 1,052 4 85%300 230 230 230 0 0 0 0 0 0 0 0 0 0 991 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2305.50 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,021 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 959 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/5/20 0:00 2163.51 6.0 5 58%212 171 171 171 248 0 0 0 0 0 0 0 0 0 972 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 909 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/5/20 6:00 2354.24 6.0 5 63%229 182 182 182 264 0 0 0 0 0 0 0 0 0 1,038 4 84%296 227 227 227 0 0 0 0 0 0 0 0 0 0 976 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2316.98 6.0 5 62%226 180 180 180 261 0 0 0 0 0 0 0 0 0 1,025 4 82%291 224 224 224 0 0 0 0 0 0 0 0 0 0 963 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2223.99 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 993 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 930 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/6/20 0:00 2144.93 6.0 5 57%211 170 170 170 246 0 0 0 0 0 0 0 0 0 966 3 99%346 264 264 0 0 0 0 0 0 0 0 0 0 0 875 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/6/20 6:00 2379.93 6.0 5 64%231 183 183 183 266 0 0 0 0 0 0 0 0 0 1,047 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 985 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2322.94 6.0 5 62%226 180 180 180 261 0 0 0 0 0 0 0 0 0 1,027 4 83%292 224 224 224 0 0 0 0 0 0 0 0 0 0 965 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2157.27 6.0 5 58%212 170 170 170 247 0 0 0 0 0 0 0 0 0 970 3 100%348 266 266 0 0 0 0 0 0 0 0 0 0 0 880 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/7/20 0:00 2081.61 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 944 3 96%337 257 257 0 0 0 0 0 0 0 0 0 0 0 851 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/7/20 6:00 2256.82 6.0 5 60%221 176 176 176 256 0 0 0 0 0 0 0 0 0 1,005 4 80%284 219 219 219 0 0 0 0 0 0 0 0 0 0 941 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2305.22 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,021 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 959 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2287.20 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,015 4 81%288 221 221 221 0 0 0 0 0 0 0 0 0 0 952 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/8/20 0:00 2142.12 6.0 5 57%211 169 169 169 246 0 0 0 0 0 0 0 0 0 965 3 99%346 264 264 0 0 0 0 0 0 0 0 0 0 0 874 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/8/20 6:00 2297.68 6.0 5 62%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,019 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 956 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2276.68 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,012 4 81%287 221 221 221 0 0 0 0 0 0 0 0 0 0 948 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2210.35 6.0 5 59%217 173 173 173 252 0 0 0 0 0 0 0 0 0 989 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 925 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/9/20 0:00 2121.43 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 958 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 866 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/9/20 6:00 2290.13 6.0 5 61%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,016 4 82%288 222 222 222 0 0 0 0 0 0 0 0 0 0 953 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2244.77 6.0 5 60%220 175 175 175 255 0 0 0 0 0 0 0 0 0 1,001 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 937 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2182.44 6.0 5 58%214 172 172 172 249 0 0 0 0 0 0 0 0 0 979 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 915 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2098.37 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2271.20 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,010 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 946 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2296.21 6.0 5 61%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,018 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 955 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2183.03 6.0 5 58%214 172 172 172 250 0 0 0 0 0 0 0 0 0 979 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 916 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2089.26 6.0 5 56%206 166 166 166 242 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 854 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2343.03 6.0 5 63%228 181 181 181 263 0 0 0 0 0 0 0 0 0 1,034 4 83%294 226 226 226 0 0 0 0 0 0 0 0 0 0 972 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2382.61 6.0 5 64%232 183 183 183 266 0 0 0 0 0 0 0 0 0 1,048 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 986 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2288.90 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,016 4 81%288 222 222 222 0 0 0 0 0 0 0 0 0 0 953 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2164.88 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 973 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 909 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2379.05 6.0 5 64%231 183 183 183 266 0 0 0 0 0 0 0 0 0 1,047 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 985 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2386.18 6.0 5 64%232 184 184 184 267 0 0 0 0 0 0 0 0 0 1,049 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 988 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2245.89 6.0 5 60%220 175 175 175 255 0 0 0 0 0 0 0 0 0 1,001 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 938 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2128.13 6.0 5 57%209 169 169 169 245 0 0 0 0 0 0 0 0 0 960 3 99%344 262 262 0 0 0 0 0 0 0 0 0 0 0 869 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2342.99 6.0 5 63%228 181 181 181 263 0 0 0 0 0 0 0 0 0 1,034 4 83%294 226 226 226 0 0 0 0 0 0 0 0 0 0 972 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2237.31 6.0 5 60%219 175 175 175 254 0 0 0 0 0 0 0 0 0 998 4 80%282 217 217 217 0 0 0 0 0 0 0 0 0 0 935 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2121.61 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 958 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 866 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2074.78 6.0 5 56%205 165 165 165 240 0 0 0 0 0 0 0 0 0 941 3 96%336 256 256 0 0 0 0 0 0 0 0 0 0 0 848 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2330.53 6.0 5 62%227 180 180 180 262 0 0 0 0 0 0 0 0 0 1,030 4 83%293 225 225 225 0 0 0 0 0 0 0 0 0 0 968 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2278.49 6.0 5 61%222 177 177 177 258 0 0 0 0 0 0 0 0 0 1,012 4 81%287 221 221 221 0 0 0 0 0 0 0 0 0 0 949 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2207.26 6.0 5 59%216 173 173 173 252 0 0 0 0 0 0 0 0 0 988 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 924 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2097.61 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 949 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2316.92 6.0 5 62%226 180 180 180 261 0 0 0 0 0 0 0 0 0 1,025 4 82%291 224 224 224 0 0 0 0 0 0 0 0 0 0 963 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2275.36 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,011 4 81%287 220 220 220 0 0 0 0 0 0 0 0 0 0 948 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2143.14 6.0 5 57%211 169 169 169 246 0 0 0 0 0 0 0 0 0 965 3 99%346 264 264 0 0 0 0 0 0 0 0 0 0 0 874 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2087.35 6.0 5 56%206 166 166 166 241 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 853 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2281.18 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,013 4 81%287 221 221 221 0 0 0 0 0 0 0 0 0 0 950 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2243.68 6.0 5 60%219 175 175 175 255 0 0 0 0 0 0 0 0 0 1,000 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 937 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2173.49 6.0 5 58%213 171 171 171 249 0 0 0 0 0 0 0 0 0 976 4 77%275 212 212 212 0 0 0 0 0 0 0 0 0 0 912 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2088.73 6.0 5 56%206 166 166 166 242 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 853 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2261.76 6.0 5 61%221 176 176 176 256 0 0 0 0 0 0 0 0 0 1,006 4 81%285 219 219 219 0 0 0 0 0 0 0 0 0 0 943 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2215.27 6.0 5 59%217 174 174 174 252 0 0 0 0 0 0 0 0 0 990 4 79%280 216 216 216 0 0 0 0 0 0 0 0 0 0 927 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2133.58 6.0 5 57%210 169 169 169 245 0 0 0 0 0 0 0 0 0 962 3 99%345 263 263 0 0 0 0 0 0 0 0 0 0 0 871 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2044.69 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 931 3 95%331 253 253 0 0 0 0 0 0 0 0 0 0 0 836 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2353.79 6.0 5 63%229 182 182 182 264 0 0 0 0 0 0 0 0 0 1,038 4 84%296 227 227 227 0 0 0 0 0 0 0 0 0 0 976 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2382.94 6.0 5 64%232 183 183 183 266 0 0 0 0 0 0 0 0 0 1,048 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 986 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2279.63 6.0 5 61%223 177 177 177 258 0 0 0 0 0 0 0 0 0 1,013 4 81%287 221 221 221 0 0 0 0 0 0 0 0 0 0 949 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2132.76 6.0 5 57%210 169 169 169 245 0 0 0 0 0 0 0 0 0 962 3 99%344 263 263 0 0 0 0 0 0 0 0 0 0 0 870 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2354.11 6.0 5 63%229 182 182 182 264 0 0 0 0 0 0 0 0 0 1,038 4 84%296 227 227 227 0 0 0 0 0 0 0 0 0 0 976 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2367.83 6.0 5 63%230 183 183 183 265 0 0 0 0 0 0 0 0 0 1,043 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 981 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2270.05 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,009 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 946 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2149.35 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 967 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 877 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2397.76 6.0 5 64%233 184 184 184 267 0 0 0 0 0 0 0 0 0 1,053 4 85%301 230 230 230 0 0 0 0 0 0 0 0 0 0 992 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2340.05 6.0 5 63%228 181 181 181 263 0 0 0 0 0 0 0 0 0 1,033 4 83%294 226 226 226 0 0 0 0 0 0 0 0 0 0 971 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2301.38 6.0 5 62%224 179 179 179 259 0 0 0 0 0 0 0 0 0 1,020 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 957 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2161.28 6.0 5 58%212 171 171 171 248 0 0 0 0 0 0 0 0 0 972 4 77%274 211 211 211 0 0 0 0 0 0 0 0 0 0 908 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2454.06 6.0 5 66%238 187 187 187 272 0 0 0 0 0 0 0 0 0 1,072 4 87%307 235 235 235 0 0 0 0 0 0 0 0 0 0 1,012 5 66%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2435.26 6.0 5 65%236 186 186 186 271 0 0 0 0 0 0 0 0 0 1,066 4 87%305 233 233 233 0 0 0 0 0 0 0 0 0 0 1,005 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2284.02 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,014 4 81%288 221 221 221 0 0 0 0 0 0 0 0 0 0 951 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2166.89 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 974 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 910 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2419.90 6.0 5 65%235 185 185 185 269 0 0 0 0 0 0 0 0 0 1,061 4 86%303 232 232 232 0 0 0 0 0 0 0 0 0 0 1,000 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2359.53 6.0 5 63%230 182 182 182 264 0 0 0 0 0 0 0 0 0 1,040 4 84%296 227 227 227 0 0 0 0 0 0 0 0 0 0 978 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2234.30 6.0 5 60%219 175 175 175 254 0 0 0 0 0 0 0 0 0 997 4 80%282 217 217 217 0 0 0 0 0 0 0 0 0 0 934 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2154.32 6.0 5 58%212 170 170 170 247 0 0 0 0 0 0 0 0 0 969 3 100%348 266 266 0 0 0 0 0 0 0 0 0 0 0 879 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2345.04 6.0 5 63%228 181 181 181 263 0 0 0 0 0 0 0 0 0 1,035 4 83%295 226 226 226 0 0 0 0 0 0 0 0 0 0 973 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2294.82 6.0 5 61%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,018 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 955 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2245.83 6.0 5 60%220 175 175 175 255 0 0 0 0 0 0 0 0 0 1,001 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 938 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/29/20 6:00 4/29/20 12:0 4/29/20 18:0 4/30/20 0:00 4/30/20 6:00 4/30/20 12:0 4/30/20 18:0 5/1/20 12:00 5/1/20 18:00 5/2/20 12:00 5/2/20 18:00 5/3/20 12:00 5/3/20 18:00 5/4/20 12:00 5/4/20 18:00 5/5/20 12:00 5/5/20 18:00 5/6/20 12:00 5/6/20 18:00 5/7/20 12:00 5/7/20 18:00 5/8/20 12:00 5/8/20 18:00 5/9/20 12:00 5/9/20 18:00 5/10/20 0:00 5/10/20 6:00 5/10/20 12:0 5/10/20 18:0 5/11/20 0:00 5/11/20 6:00 5/11/20 12:0 5/11/20 18:0 5/12/20 0:00 5/12/20 6:00 5/12/20 12:0 5/12/20 18:0 5/13/20 0:00 5/13/20 6:00 5/13/20 12:0 5/13/20 18:0 5/14/20 0:00 5/14/20 6:00 5/14/20 12:0 5/14/20 18:0 5/15/20 0:00 5/15/20 6:00 5/15/20 12:0 5/15/20 18:0 5/16/20 0:00 5/16/20 6:00 5/16/20 12:0 5/16/20 18:0 5/17/20 0:00 5/17/20 6:00 5/17/20 12:0 5/17/20 18:0 5/18/20 0:00 5/18/20 6:00 5/18/20 12:0 5/18/20 18:0 5/19/20 0:00 5/19/20 6:00 5/19/20 12:0 5/19/20 18:0 5/20/20 0:00 5/20/20 6:00 5/20/20 12:0 5/20/20 18:0 5/21/20 0:00 5/21/20 6:00 5/21/20 12:0 5/21/20 18:0 5/22/20 0:00 5/22/20 6:00 5/22/20 12:0 5/22/20 18:0 5/23/20 0:00 5/23/20 6:00 5/23/20 12:0 5/23/20 18:0 NEA BESS Scenario Analysis Data Analysis 16 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.4 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.7 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.2 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.5 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.8 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.4 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.8 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.6 4 83%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.6 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 78%7.4 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.6 4 83%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 79%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.6 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.4 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 95%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.8 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.8 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 85%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.4 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 66%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.6 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.4 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 NEA BESS Scenario Analysis Data Analysis 17 2141.99 6.0 5 57%211 169 169 169 246 0 0 0 0 0 0 0 0 0 965 3 99%346 264 264 0 0 0 0 0 0 0 0 0 0 0 874 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2382.79 6.0 5 64%232 183 183 183 266 0 0 0 0 0 0 0 0 0 1,048 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 986 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2381.61 6.0 5 64%231 183 183 183 266 0 0 0 0 0 0 0 0 0 1,048 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 986 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2294.24 6.0 5 61%224 178 178 178 259 0 0 0 0 0 0 0 0 0 1,018 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 955 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2209.90 6.0 5 59%216 173 173 173 252 0 0 0 0 0 0 0 0 0 988 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 925 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2433.37 6.0 5 65%236 186 186 186 270 0 0 0 0 0 0 0 0 0 1,065 4 87%305 233 233 233 0 0 0 0 0 0 0 0 0 0 1,005 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2409.53 6.0 5 65%234 185 185 185 268 0 0 0 0 0 0 0 0 0 1,057 4 86%302 231 231 231 0 0 0 0 0 0 0 0 0 0 996 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2288.00 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,015 4 81%288 221 221 221 0 0 0 0 0 0 0 0 0 0 952 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2222.54 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 993 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 929 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2457.38 6.0 5 66%238 188 188 188 272 0 0 0 0 0 0 0 0 0 1,073 4 87%308 235 235 235 0 0 0 0 0 0 0 0 0 0 1,013 5 66%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2395.63 6.0 5 64%233 184 184 184 267 0 0 0 0 0 0 0 0 0 1,052 4 85%300 230 230 230 0 0 0 0 0 0 0 0 0 0 991 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2256.55 6.0 5 60%221 176 176 176 256 0 0 0 0 0 0 0 0 0 1,005 4 80%284 219 219 219 0 0 0 0 0 0 0 0 0 0 941 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2188.20 6.0 5 59%215 172 172 172 250 0 0 0 0 0 0 0 0 0 981 4 78%277 214 214 214 0 0 0 0 0 0 0 0 0 0 917 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2426.73 6.0 5 65%235 186 186 186 270 0 0 0 0 0 0 0 0 0 1,063 4 86%304 233 233 233 0 0 0 0 0 0 0 0 0 0 1,002 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2427.90 6.0 5 65%235 186 186 186 270 0 0 0 0 0 0 0 0 0 1,063 4 86%304 233 233 233 0 0 0 0 0 0 0 0 0 0 1,003 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2270.57 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,009 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 946 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2165.84 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 973 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 910 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2407.03 6.0 5 64%234 185 185 185 268 0 0 0 0 0 0 0 0 0 1,056 4 86%302 231 231 231 0 0 0 0 0 0 0 0 0 0 995 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2352.62 6.0 5 63%229 182 182 182 264 0 0 0 0 0 0 0 0 0 1,038 4 84%295 227 227 227 0 0 0 0 0 0 0 0 0 0 975 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2166.75 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 973 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 910 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2080.05 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 943 3 96%336 257 257 0 0 0 0 0 0 0 0 0 0 0 850 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2384.98 6.0 5 64%232 183 183 183 266 0 0 0 0 0 0 0 0 0 1,049 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 987 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 684.81 6.0 3 32%127 112 112 0 0 0 0 0 0 0 0 0 0 0 351 1 79%281 0 0 0 0 0 0 0 0 0 0 0 0 0 281 3 32%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 976.04 6.0 3 45%170 142 142 0 0 0 0 0 0 0 0 0 0 0 454 2 65%234 185 0 0 0 0 0 0 0 0 0 0 0 0 419 3 45%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 2419.21 6.0 5 65%235 185 185 185 269 0 0 0 0 0 0 0 0 0 1,060 4 86%303 232 232 232 0 0 0 0 0 0 0 0 0 0 1,000 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/5/20 0:00 2222.48 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 993 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 929 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/5/20 6:00 3187.93 6.0 6 69%249 195 195 195 283 249 0 0 0 0 0 0 0 0 1,368 5 85%301 230 230 230 332 0 0 0 0 0 0 0 0 0 1,324 6 69%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2826.50 6.0 6 61%224 178 178 178 259 224 0 0 0 0 0 0 0 0 1,242 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,198 6 61%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2559.95 6.0 5 69%247 193 193 193 281 0 0 0 0 0 0 0 0 0 1,108 4 91%319 244 244 244 0 0 0 0 0 0 0 0 0 0 1,052 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/6/20 0:00 2315.75 6.0 5 62%226 180 180 180 261 0 0 0 0 0 0 0 0 0 1,025 4 82%291 224 224 224 0 0 0 0 0 0 0 0 0 0 962 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/6/20 6:00 3401.07 6.0 6 74%264 205 205 205 297 264 0 0 0 0 0 0 0 0 1,441 5 91%319 244 244 244 351 0 0 0 0 0 0 0 0 0 1,402 6 74%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3073.19 6.0 6 67%241 190 190 190 276 241 0 0 0 0 0 0 0 0 1,328 5 82%291 223 223 223 323 0 0 0 0 0 0 0 0 0 1,284 6 67%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2541.13 6.0 5 68%245 192 192 192 279 0 0 0 0 0 0 0 0 0 1,102 4 90%317 242 242 242 0 0 0 0 0 0 0 0 0 0 1,045 5 68%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/7/20 0:00 2386.10 6.0 5 64%232 184 184 184 267 0 0 0 0 0 0 0 0 0 1,049 4 85%299 229 229 229 0 0 0 0 0 0 0 0 0 0 988 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/7/20 6:00 3024.51 6.0 6 66%238 188 188 188 272 238 0 0 0 0 0 0 0 0 1,311 5 81%287 220 220 220 319 0 0 0 0 0 0 0 0 0 1,267 6 66%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2835.13 6.0 6 62%225 179 179 179 260 225 0 0 0 0 0 0 0 0 1,245 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,201 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2487.56 6.0 5 67%241 189 189 189 275 0 0 0 0 0 0 0 0 0 1,084 4 89%311 238 238 238 0 0 0 0 0 0 0 0 0 0 1,025 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/8/20 0:00 2363.31 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,041 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 979 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/8/20 6:00 2899.33 6.0 6 63%229 182 182 182 264 229 0 0 0 0 0 0 0 0 1,268 5 78%276 213 213 213 308 0 0 0 0 0 0 0 0 0 1,223 6 63%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2783.41 6.0 5 75%266 206 206 206 299 0 0 0 0 0 0 0 0 0 1,184 4 99%346 264 264 264 0 0 0 0 0 0 0 0 0 0 1,137 5 75%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2423.26 6.0 5 65%235 186 186 186 270 0 0 0 0 0 0 0 0 0 1,062 4 86%304 232 232 232 0 0 0 0 0 0 0 0 0 0 1,001 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/9/20 0:00 2159.06 6.0 5 58%212 170 170 170 247 0 0 0 0 0 0 0 0 0 971 3 100%348 266 266 0 0 0 0 0 0 0 0 0 0 0 881 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/9/20 6:00 3078.33 6.0 6 67%242 190 190 190 276 242 0 0 0 0 0 0 0 0 1,330 5 82%291 224 224 224 323 0 0 0 0 0 0 0 0 0 1,285 6 67%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2946.62 6.0 6 64%232 184 184 184 267 232 0 0 0 0 0 0 0 0 1,284 5 79%280 216 216 216 312 0 0 0 0 0 0 0 0 0 1,240 6 64%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2491.73 6.0 5 67%241 190 190 190 275 0 0 0 0 0 0 0 0 0 1,085 4 89%312 238 238 238 0 0 0 0 0 0 0 0 0 0 1,026 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2324.93 6.0 5 62%227 180 180 180 261 0 0 0 0 0 0 0 0 0 1,028 4 83%292 224 224 224 0 0 0 0 0 0 0 0 0 0 966 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3011.11 6.0 6 66%237 187 187 187 271 237 0 0 0 0 0 0 0 0 1,307 5 81%285 220 220 220 318 0 0 0 0 0 0 0 0 0 1,262 6 66%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2939.47 6.0 6 64%232 184 184 184 267 232 0 0 0 0 0 0 0 0 1,282 5 79%279 215 215 215 312 0 0 0 0 0 0 0 0 0 1,237 6 64%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2485.64 6.0 5 67%240 189 189 189 275 0 0 0 0 0 0 0 0 0 1,083 4 88%311 238 238 238 0 0 0 0 0 0 0 0 0 0 1,024 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2222.22 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 993 4 79%281 216 216 216 0 0 0 0 0 0 0 0 0 0 929 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2847.32 6.0 6 62%226 179 179 179 260 226 0 0 0 0 0 0 0 0 1,250 5 76%271 210 210 210 304 0 0 0 0 0 0 0 0 0 1,206 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2833.54 6.0 6 62%225 179 179 179 260 225 0 0 0 0 0 0 0 0 1,245 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,201 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2568.04 6.0 5 69%248 194 194 194 281 0 0 0 0 0 0 0 0 0 1,111 4 91%320 245 245 245 0 0 0 0 0 0 0 0 0 0 1,055 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2289.49 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,016 4 82%288 222 222 222 0 0 0 0 0 0 0 0 0 0 953 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3035.63 6.0 6 66%239 188 188 188 273 239 0 0 0 0 0 0 0 0 1,315 5 81%288 221 221 221 320 0 0 0 0 0 0 0 0 0 1,270 6 66%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3009.44 6.0 6 65%237 187 187 187 271 237 0 0 0 0 0 0 0 0 1,306 5 81%285 220 220 220 318 0 0 0 0 0 0 0 0 0 1,261 6 65%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2567.85 6.0 5 69%247 194 194 194 281 0 0 0 0 0 0 0 0 0 1,111 4 91%320 245 245 245 0 0 0 0 0 0 0 0 0 0 1,055 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2314.38 6.0 5 62%226 179 179 179 261 0 0 0 0 0 0 0 0 0 1,025 4 82%291 224 224 224 0 0 0 0 0 0 0 0 0 0 962 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3090.58 6.0 6 67%243 191 191 191 277 243 0 0 0 0 0 0 0 0 1,334 5 83%292 224 224 224 324 0 0 0 0 0 0 0 0 0 1,290 6 67%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2955.00 6.0 6 64%233 184 184 184 268 233 0 0 0 0 0 0 0 0 1,287 5 79%281 216 216 216 313 0 0 0 0 0 0 0 0 0 1,242 6 64%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2473.67 6.0 5 66%239 189 189 189 274 0 0 0 0 0 0 0 0 0 1,079 4 88%309 237 237 237 0 0 0 0 0 0 0 0 0 0 1,019 5 66%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2205.24 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 987 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 923 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2876.26 6.0 6 63%228 181 181 181 262 228 0 0 0 0 0 0 0 0 1,260 5 77%274 212 212 212 307 0 0 0 0 0 0 0 0 0 1,215 6 63%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3126.71 6.0 6 68%245 192 192 192 279 245 0 0 0 0 0 0 0 0 1,346 5 84%295 227 227 227 327 0 0 0 0 0 0 0 0 0 1,302 6 68%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2683.07 6.0 5 72%257 201 201 201 291 0 0 0 0 0 0 0 0 0 1,150 4 96%334 255 255 255 0 0 0 0 0 0 0 0 0 0 1,098 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2400.87 6.0 5 64%233 184 184 184 268 0 0 0 0 0 0 0 0 0 1,054 4 85%301 231 231 231 0 0 0 0 0 0 0 0 0 0 993 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3277.67 6.0 6 71%256 199 199 199 289 256 0 0 0 0 0 0 0 0 1,398 5 88%308 236 236 236 340 0 0 0 0 0 0 0 0 0 1,357 6 71%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3164.62 6.0 6 69%248 194 194 194 282 248 0 0 0 0 0 0 0 0 1,360 5 85%299 229 229 229 330 0 0 0 0 0 0 0 0 0 1,316 6 69%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2770.15 6.0 5 74%265 206 206 206 298 0 0 0 0 0 0 0 0 0 1,179 4 99%344 263 263 263 0 0 0 0 0 0 0 0 0 0 1,132 5 74%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2403.44 6.0 5 64%233 185 185 185 268 0 0 0 0 0 0 0 0 0 1,055 4 86%301 231 231 231 0 0 0 0 0 0 0 0 0 0 994 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3419.24 6.0 6 74%265 206 206 206 299 265 0 0 0 0 0 0 0 0 1,447 5 92%321 245 245 245 352 0 0 0 0 0 0 0 0 0 1,409 6 74%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3439.87 6.0 6 75%267 207 207 207 300 267 0 0 0 0 0 0 0 0 1,454 5 92%323 246 246 246 354 0 0 0 0 0 0 0 0 0 1,416 6 75%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2771.95 6.0 5 74%265 206 206 206 298 0 0 0 0 0 0 0 0 0 1,180 4 99%344 263 263 263 0 0 0 0 0 0 0 0 0 0 1,133 5 74%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2412.34 6.0 5 65%234 185 185 185 269 0 0 0 0 0 0 0 0 0 1,058 4 86%302 232 232 232 0 0 0 0 0 0 0 0 0 0 997 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3294.00 6.0 6 72%257 200 200 200 290 257 0 0 0 0 0 0 0 0 1,404 5 88%310 237 237 237 341 0 0 0 0 0 0 0 0 0 1,362 6 72%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3654.45 6.0 6 79%282 217 217 217 314 282 0 0 0 0 0 0 0 0 1,529 5 98%342 261 261 261 374 0 0 0 0 0 0 0 0 0 1,498 6 79%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3009.47 6.0 6 65%237 187 187 187 271 237 0 0 0 0 0 0 0 0 1,306 5 81%285 220 220 220 318 0 0 0 0 0 0 0 0 0 1,261 6 65%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2637.44 6.0 5 71%253 198 198 198 287 0 0 0 0 0 0 0 0 0 1,134 4 94%329 251 251 251 0 0 0 0 0 0 0 0 0 0 1,081 5 71%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3922.59 6.0 7 73%262 204 204 204 295 262 240 0 0 0 0 0 0 0 1,669 6 85%301 230 230 230 332 301 0 0 0 0 0 0 0 0 1,624 7 73%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 3431.52 6.0 6 75%266 207 207 207 299 266 0 0 0 0 0 0 0 0 1,451 5 92%322 246 246 246 353 0 0 0 0 0 0 0 0 0 1,413 6 75%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2826.60 6.0 6 61%224 178 178 178 259 224 0 0 0 0 0 0 0 0 1,242 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,198 6 61%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2519.65 6.0 5 67%243 191 191 191 278 0 0 0 0 0 0 0 0 0 1,094 4 90%315 241 241 241 0 0 0 0 0 0 0 0 0 0 1,037 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3239.85 6.0 6 70%253 198 198 198 287 253 0 0 0 0 0 0 0 0 1,385 5 87%305 234 234 234 337 0 0 0 0 0 0 0 0 0 1,343 6 70%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3295.51 6.0 6 72%257 200 200 200 290 257 0 0 0 0 0 0 0 0 1,405 5 88%310 237 237 237 342 0 0 0 0 0 0 0 0 0 1,363 6 72%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2834.36 6.0 6 62%225 179 179 179 260 225 0 0 0 0 0 0 0 0 1,245 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,201 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2566.92 6.0 5 69%247 194 194 194 281 0 0 0 0 0 0 0 0 0 1,110 4 91%320 245 245 245 0 0 0 0 0 0 0 0 0 0 1,054 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3931.21 6.0 7 73%262 204 204 204 296 262 240 0 0 0 0 0 0 0 1,672 6 86%301 231 231 231 333 301 0 0 0 0 0 0 0 0 1,627 7 73%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 4381.58 6.0 7 82%289 222 222 222 321 289 261 0 0 0 0 0 0 0 1,828 6 95%333 254 254 254 365 333 0 0 0 0 0 0 0 0 1,794 7 82%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 2908.45 6.0 6 63%230 182 182 182 265 230 0 0 0 0 0 0 0 0 1,271 5 78%277 214 214 214 309 0 0 0 0 0 0 0 0 0 1,226 6 63%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2599.24 6.0 5 70%250 196 196 196 284 0 0 0 0 0 0 0 0 0 1,121 4 93%324 247 247 247 0 0 0 0 0 0 0 0 0 0 1,066 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3229.04 6.0 6 70%252 197 197 197 286 252 0 0 0 0 0 0 0 0 1,382 5 86%304 233 233 233 336 0 0 0 0 0 0 0 0 0 1,339 6 70%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3051.18 6.0 6 66%240 189 189 189 274 240 0 0 0 0 0 0 0 0 1,320 5 82%289 222 222 222 321 0 0 0 0 0 0 0 0 0 1,276 6 66%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2880.35 6.0 6 63%228 181 181 181 263 228 0 0 0 0 0 0 0 0 1,261 5 77%274 212 212 212 307 0 0 0 0 0 0 0 0 0 1,217 6 63%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2625.06 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3815.04 6.0 7 71%255 199 199 199 289 255 235 0 0 0 0 0 0 0 1,632 6 83%293 225 225 225 325 293 0 0 0 0 0 0 0 0 1,586 7 71%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5010.99 6.0 8 82%290 223 223 223 322 290 262 262 0 0 0 0 0 0 2,093 7 94%328 250 250 250 359 328 293 0 0 0 0 0 0 0 2,057 8 82%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3785.73 6.0 7 71%254 198 198 198 287 254 233 0 0 0 0 0 0 0 1,622 6 82%291 223 223 223 323 291 0 0 0 0 0 0 0 0 1,575 7 71%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 2790.31 6.0 5 75%267 207 207 207 300 0 0 0 0 0 0 0 0 0 1,186 4 99%346 265 265 265 0 0 0 0 0 0 0 0 0 0 1,140 5 75%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4286.25 6.0 7 80%284 218 218 218 316 284 257 0 0 0 0 0 0 0 1,795 6 93%326 249 249 249 358 326 0 0 0 0 0 0 0 0 1,758 7 80%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5/24/20 0:00 5/24/20 6:00 5/24/20 12:0 5/24/20 18:0 5/25/20 0:00 5/25/20 6:00 5/25/20 12:0 5/25/20 18:0 5/26/20 0:00 5/26/20 6:00 5/26/20 12:0 5/26/20 18:0 5/27/20 0:00 5/27/20 6:00 5/27/20 12:0 5/27/20 18:0 5/28/20 0:00 5/28/20 6:00 5/28/20 12:0 5/28/20 18:0 5/29/20 0:00 5/29/20 6:00 5/29/20 12:0 6/4/20 12:00 6/4/20 18:00 6/5/20 12:00 6/5/20 18:00 6/6/20 12:00 6/6/20 18:00 6/7/20 12:00 6/7/20 18:00 6/8/20 12:00 6/8/20 18:00 6/9/20 12:00 6/9/20 18:00 6/10/20 0:00 6/10/20 6:00 6/10/20 12:0 6/10/20 18:0 6/11/20 0:00 6/11/20 6:00 6/11/20 12:0 6/11/20 18:0 6/12/20 0:00 6/12/20 6:00 6/12/20 12:0 6/12/20 18:0 6/13/20 0:00 6/13/20 6:00 6/13/20 12:0 6/13/20 18:0 6/14/20 0:00 6/14/20 6:00 6/14/20 12:0 6/14/20 18:0 6/15/20 0:00 6/15/20 6:00 6/15/20 12:0 6/15/20 18:0 6/16/20 0:00 6/16/20 6:00 6/16/20 12:0 6/16/20 18:0 6/17/20 0:00 6/17/20 6:00 6/17/20 12:0 6/17/20 18:0 6/18/20 0:00 6/18/20 6:00 6/18/20 12:0 6/18/20 18:0 6/19/20 0:00 6/19/20 6:00 6/19/20 12:0 6/19/20 18:0 6/20/20 0:00 6/20/20 6:00 6/20/20 12:0 6/20/20 18:0 6/21/20 0:00 6/21/20 6:00 6/21/20 12:0 6/21/20 18:0 6/22/20 0:00 6/22/20 6:00 6/22/20 12:0 6/22/20 18:0 6/23/20 0:00 6/23/20 6:00 NEA BESS Scenario Analysis Data Analysis 18 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.4 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.2 5.1 5.1 5.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 66%6.3 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.6 4 87%8.3 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.4 4 86%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.4 4 86%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.8 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 1 79%6 0 0 0 0 0 0 0 0 0 0 0 0 0 6 3 32%3.4 3.4 3.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 10.3 1 79%7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 7.5 2 65%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 45%4.6 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 12.9 2 65%6.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 11.4 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 5 85%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 69%6.6 5.4 5.4 5.4 7.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.3 5 85%8.1 6.1 6.1 6.1 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.3 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 61%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.3 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.4 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.4 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 5 91%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 74%7.0 5.6 5.6 5.6 8.2 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.0 5 91%8.6 6.4 6.4 6.4 9.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.1 5 82%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 67%6.4 5.3 5.3 5.3 7.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.3 5 82%7.8 6.0 6.0 6.0 8.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 4 90%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 68%6.5 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.3 4 90%8.5 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 5 81%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 66%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.9 5 81%7.7 5.9 5.9 5.9 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.0 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.5 4 89%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.4 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.8 4 89%8.4 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%7.9 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 5 78%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 63%6.1 5.1 5.1 5.1 7.5 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.9 5 78%7.4 5.7 5.7 5.7 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.0 4 99%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 75%7.1 5.6 5.6 5.6 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.1 4 99%9.4 6.8 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.9 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 5 82%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 67%6.4 5.3 5.3 5.3 7.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.4 5 82%7.8 6.0 6.0 6.0 8.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 5 79%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 64%6.2 5.1 5.1 5.1 7.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.3 5 79%7.5 5.8 5.8 5.8 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.4 4 89%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.4 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.9 4 89%8.4 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.6 4 83%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 5 81%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 66%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.8 5 81%7.6 5.9 5.9 5.9 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.9 5 79%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 64%6.2 5.1 5.1 5.1 7.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.3 5 79%7.5 5.8 5.8 5.8 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.3 4 88%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.4 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.8 4 88%8.3 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.5 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.6 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.5 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.5 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%6.0 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 5 81%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 66%6.4 5.2 5.2 5.2 7.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.0 5 81%7.7 5.9 5.9 5.9 8.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.1 5 81%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 65%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.8 5 81%7.6 5.9 5.9 5.9 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.9 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.5 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 82%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 5 83%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 67%6.5 5.3 5.3 5.3 7.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.5 5 83%7.8 6.0 6.0 6.0 8.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.5 5 79%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 64%6.2 5.1 5.1 5.1 7.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.4 5 79%7.5 5.8 5.8 5.8 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.4 4 88%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 66%6.4 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.7 4 88%8.3 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 79%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 5 77%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 63%6.1 5.1 5.1 5.1 7.4 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.7 5 77%7.3 5.7 5.7 5.7 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.8 5 84%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 68%6.5 5.3 5.3 5.3 7.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.8 5 84%7.9 6.0 6.0 6.0 8.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.8 4 96%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.9 5.5 5.5 5.5 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.3 4 96%9.0 6.7 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 85%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 5 88%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 71%6.8 5.5 5.5 5.5 8.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.0 5 88%8.3 6.2 6.2 6.2 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.1 5 85%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 69%6.6 5.3 5.3 5.3 7.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.1 5 85%8.0 6.1 6.1 6.1 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.1 4 99%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 74%7.1 5.6 5.6 5.6 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.0 4 99%9.3 6.8 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.8 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 5 92%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 74%7.1 5.6 5.6 5.6 8.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.1 5 92%8.6 6.4 6.4 6.4 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.3 5 92%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 75%7.1 5.6 5.6 5.6 8.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.3 5 92%8.7 6.5 6.5 6.5 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.5 4 99%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 74%7.1 5.6 5.6 5.6 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.0 4 99%9.3 6.8 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.8 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.2 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 5 88%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 72%6.8 5.5 5.5 5.5 8.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.1 5 88%8.3 6.3 6.3 6.3 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.2 5 98%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 79%7.5 5.8 5.8 5.8 8.5 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 41.1 5 98%9.2 6.8 6.8 6.8 9.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.4 5 81%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 65%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.8 5 81%7.6 5.9 5.9 5.9 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.9 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 71%6.8 5.4 5.4 5.4 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.0 4 94%8.9 6.6 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 6 85%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 73%7.0 5.5 5.5 5.5 8.1 7.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 45.3 6 85%8.1 6.1 6.1 6.1 8.9 8.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.4 5 92%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 75%7.1 5.6 5.6 5.6 8.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.2 5 92%8.7 6.5 6.5 6.5 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.4 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 61%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.3 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.4 4 90%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.5 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.1 4 90%8.5 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 5 87%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 70%6.7 5.4 5.4 5.4 8.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.7 5 87%8.2 6.2 6.2 6.2 9.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.8 5 88%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 72%6.8 5.5 5.5 5.5 8.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.1 5 88%8.3 6.3 6.3 6.3 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.2 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.5 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.5 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 6 86%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 73%7.0 5.6 5.6 5.6 8.1 7.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 45.4 6 86%8.1 6.1 6.1 6.1 8.9 8.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.4 6 95%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 49.0 6 95%9.0 6.6 6.6 6.6 9.6 9.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 47.5 5 78%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 63%6.1 5.1 5.1 5.1 7.5 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.0 5 78%7.4 5.8 5.8 5.8 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.1 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.7 4 93%8.7 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 5 86%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 70%6.7 5.4 5.4 5.4 7.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.6 5 86%8.2 6.2 6.2 6.2 9.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.7 5 82%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 66%6.4 5.2 5.2 5.2 7.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.2 5 82%7.7 5.9 5.9 5.9 8.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.2 5 77%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 63%6.1 5.1 5.1 5.1 7.4 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.8 5 77%7.3 5.7 5.7 5.7 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.9 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 6 83%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 71%6.8 5.5 5.5 5.5 8.0 6.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.4 6 83%7.8 6.0 6.0 6.0 8.8 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.4 7 94%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 82%7.8 5.9 5.9 5.9 8.7 7.8 7.0 7.0 0.0 0.0 0.0 0.0 0.0 0.0 56.1 7 94%8.8 6.5 6.5 6.5 9.5 8.8 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 54.5 6 82%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.2 6 82%7.8 6.0 6.0 6.0 8.7 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.2 4 99%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 75%7.1 5.6 5.6 5.6 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.2 4 99%9.4 6.9 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.0 6 93%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 48.2 6 93%8.8 6.5 6.5 6.5 9.5 8.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 46.6 NEA BESS Scenario Analysis Data Analysis 19 4603.76 6.0 8 75%269 208 208 208 302 269 245 245 0 0 0 0 0 0 1,952 7 86%303 232 232 232 334 303 272 0 0 0 0 0 0 0 1,907 8 75%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3368.05 6.0 6 73%262 204 204 204 295 262 0 0 0 0 0 0 0 0 1,430 5 90%316 242 242 242 348 0 0 0 0 0 0 0 0 0 1,390 6 73%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2689.48 6.0 5 72%258 201 201 201 291 0 0 0 0 0 0 0 0 0 1,152 4 96%335 255 255 255 0 0 0 0 0 0 0 0 0 0 1,101 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3855.90 6.0 7 72%258 201 201 201 291 258 236 0 0 0 0 0 0 0 1,646 6 84%296 227 227 227 328 296 0 0 0 0 0 0 0 0 1,600 7 72%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 3818.64 6.0 7 71%256 199 199 199 289 256 235 0 0 0 0 0 0 0 1,634 6 83%293 225 225 225 325 293 0 0 0 0 0 0 0 0 1,587 7 71%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 3339.03 6.0 6 73%260 202 202 202 293 260 0 0 0 0 0 0 0 0 1,420 5 89%314 240 240 240 345 0 0 0 0 0 0 0 0 0 1,379 6 73%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2815.70 6.0 6 61%223 178 178 178 258 223 0 0 0 0 0 0 0 0 1,238 5 75%269 208 208 208 302 0 0 0 0 0 0 0 0 0 1,195 6 61%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 4558.12 6.0 8 75%266 206 206 206 299 266 243 243 0 0 0 0 0 0 1,937 6 99%346 264 264 264 378 346 0 0 0 0 0 0 0 0 1,862 8 75%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 4808.59 6.0 8 79%279 215 215 215 312 279 253 253 0 0 0 0 0 0 2,023 7 90%315 241 241 241 347 315 282 0 0 0 0 0 0 0 1,982 8 79%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3452.36 6.0 6 75%268 207 207 207 301 268 0 0 0 0 0 0 0 0 1,459 5 92%324 247 247 247 355 0 0 0 0 0 0 0 0 0 1,421 6 75%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2988.97 6.0 6 65%235 186 186 186 270 235 0 0 0 0 0 0 0 0 1,299 5 80%284 218 218 218 316 0 0 0 0 0 0 0 0 0 1,254 6 65%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 5691.59 6.0 9 83%293 225 225 225 325 293 264 264 264 0 0 0 0 0 2,376 8 93%326 249 249 249 358 326 291 291 0 0 0 0 0 0 2,340 9 83%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 6219.36 6.0 10 76%269 209 209 209 302 269 245 245 245 422 0 0 0 0 2,625 9 91%318 243 243 243 349 318 284 284 284 0 0 0 0 0 2,565 10 76%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5143.05 6.0 8 84%297 228 228 228 329 297 267 267 0 0 0 0 0 0 2,140 7 96%336 256 256 256 368 336 299 0 0 0 0 0 0 0 2,107 8 84%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3116.55 6.0 6 68%244 192 192 192 279 244 0 0 0 0 0 0 0 0 1,343 5 83%294 226 226 226 326 0 0 0 0 0 0 0 0 0 1,299 6 68%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7078.94 6.0 11 78%276 213 213 213 308 276 250 250 250 432 286 0 0 0 2,967 10 86%303 232 232 232 335 303 272 272 272 478 0 0 0 0 2,931 11 78%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 8397.24 6.0 12 84%295 227 227 227 327 295 266 266 266 466 308 308 0 0 3,479 11 92%322 246 246 246 354 322 288 288 288 510 338 0 0 0 3,449 12 84%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 6832.39 6.0 10 83%293 225 225 225 325 293 264 264 264 462 0 0 0 0 2,842 9 100%347 265 265 265 380 347 309 309 309 0 0 0 0 0 2,797 10 83%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 3930.70 6.0 7 73%262 204 204 204 296 262 240 0 0 0 0 0 0 0 1,672 6 86%301 231 231 231 333 301 0 0 0 0 0 0 0 0 1,627 7 73%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5683.78 6.0 9 83%292 224 224 224 324 292 263 263 263 0 0 0 0 0 2,373 8 93%326 249 249 249 357 326 291 291 0 0 0 0 0 0 2,337 9 83%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 6110.15 6.0 10 74%265 206 206 206 298 265 242 242 242 415 0 0 0 0 2,587 9 89%313 239 239 239 344 313 280 280 280 0 0 0 0 0 2,525 10 74%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5621.88 6.0 9 82%289 222 222 222 322 289 261 261 261 0 0 0 0 0 2,351 8 92%322 246 246 246 354 322 288 288 0 0 0 0 0 0 2,314 9 82%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 5441.29 6.0 9 79%281 217 217 217 313 281 254 254 254 0 0 0 0 0 2,289 8 89%313 239 239 239 344 313 280 280 0 0 0 0 0 0 2,247 9 79%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 6672.99 6.0 10 81%287 221 221 221 319 287 259 259 259 452 0 0 0 0 2,785 9 97%339 259 259 259 371 339 303 303 303 0 0 0 0 0 2,736 10 81%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6471.64 6.0 10 79%279 215 215 215 312 279 253 253 253 438 0 0 0 0 2,713 9 94%330 252 252 252 361 330 294 294 294 0 0 0 0 0 2,659 10 79%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6056.24 6.0 10 74%263 204 204 204 296 263 240 240 240 411 0 0 0 0 2,568 8 99%346 264 264 264 378 346 308 308 0 0 0 0 0 0 2,478 10 74%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5739.29 6.0 9 84%295 226 226 226 327 295 266 266 266 0 0 0 0 0 2,392 8 94%329 251 251 251 360 329 293 293 0 0 0 0 0 0 2,358 9 84%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 7497.34 6.0 11 82%290 223 223 223 322 290 262 262 262 457 303 0 0 0 3,118 10 91%320 244 244 244 351 320 286 286 286 505 0 0 0 0 3,085 11 82%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7587.94 6.0 11 83%294 225 225 225 325 294 264 264 264 463 306 0 0 0 3,150 10 92%323 247 247 247 355 323 289 289 289 511 0 0 0 0 3,119 11 83%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6943.34 6.0 11 76%271 210 210 210 304 271 247 247 247 424 281 0 0 0 2,919 10 84%298 228 228 228 329 298 268 268 268 469 0 0 0 0 2,882 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7/1/20 0:00 5863.69 6.0 9 85%301 230 230 230 333 301 270 270 270 0 0 0 0 0 2,437 8 96%335 256 256 256 367 335 299 299 0 0 0 0 0 0 2,405 9 85%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 7/1/20 6:00 6712.39 6.0 10 82%289 222 222 222 321 289 260 260 260 454 0 0 0 0 2,799 9 98%341 261 261 261 373 341 304 304 304 0 0 0 0 0 2,751 10 82%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5482.10 6.0 9 80%283 218 218 218 315 283 256 256 256 0 0 0 0 0 2,303 8 90%315 241 241 241 346 315 282 282 0 0 0 0 0 0 2,262 9 80%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 4462.88 6.0 8 73%261 203 203 203 295 261 239 239 0 0 0 0 0 0 1,904 6 97%339 259 259 259 371 339 0 0 0 0 0 0 0 0 1,825 8 73%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 7/2/20 0:00 5575.55 6.0 9 81%287 221 221 221 319 287 259 259 259 0 0 0 0 0 2,335 8 91%320 244 244 244 351 320 286 286 0 0 0 0 0 0 2,296 9 81%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 7/2/20 6:00 6453.63 6.0 10 78%278 215 215 215 311 278 252 252 252 437 0 0 0 0 2,707 9 94%329 251 251 251 361 329 294 294 294 0 0 0 0 0 2,653 10 78%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6285.91 6.0 10 76%272 210 210 210 305 272 247 247 247 426 0 0 0 0 2,648 9 92%321 245 245 245 352 321 287 287 287 0 0 0 0 0 2,590 10 76%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6526.64 6.0 10 79%281 217 217 217 314 281 255 255 255 442 0 0 0 0 2,733 9 95%332 254 254 254 364 332 297 297 297 0 0 0 0 0 2,680 10 79%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 7/3/20 0:00 7171.51 6.0 11 79%279 215 215 215 311 279 253 253 253 438 290 0 0 0 3,000 10 87%307 235 235 235 338 307 275 275 275 484 0 0 0 0 2,965 11 79%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7/3/20 6:00 7400.16 6.0 11 81%287 221 221 221 319 287 259 259 259 451 299 0 0 0 3,083 10 90%316 241 241 241 347 316 282 282 282 499 0 0 0 0 3,049 11 81%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 8502.44 6.0 12 85%299 229 229 229 331 299 269 269 269 472 312 312 0 0 3,517 11 93%326 249 249 249 358 326 291 291 291 517 342 0 0 0 3,490 12 85%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 8574.07 6.0 12 86%301 231 231 231 333 301 271 271 271 475 315 315 0 0 3,544 11 94%329 251 251 251 360 329 294 294 294 521 345 0 0 0 3,517 12 86%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7/4/20 0:00 8214.40 6.0 12 82%290 223 223 223 322 290 261 261 261 456 302 302 0 0 3,412 10 100%348 266 266 266 381 348 310 310 310 559 0 0 0 0 3,365 12 82%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7/4/20 6:00 9649.80 6.0 13 72%259 202 202 202 293 259 237 237 237 405 268 268 982 0 4,051 12 96%336 257 257 257 368 336 300 300 300 534 354 354 0 0 3,953 13 72%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 10750.27 6.0 14 65%234 185 185 185 269 234 218 218 218 365 242 242 886 886 4,569 13 81%286 220 220 220 318 286 258 258 258 449 297 297 1,090 0 4,456 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 9692.91 6.0 13 73%260 202 202 202 294 260 238 238 238 406 269 269 986 0 4,067 12 97%338 258 258 258 370 338 301 301 301 537 355 355 0 0 3,970 13 73%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 7/5/20 0:00 9618.83 6.0 13 72%258 201 201 201 292 258 237 237 237 404 267 267 979 0 4,040 12 96%335 256 256 256 367 335 299 299 299 533 352 352 0 0 3,940 13 72%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 7/5/20 6:00 9893.10 6.0 13 74%265 206 206 206 298 265 242 242 242 414 274 274 1,006 0 4,140 12 99%344 263 263 263 377 344 307 307 307 550 364 364 0 0 4,053 13 74%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 10607.52 6.0 14 64%232 183 183 183 266 232 216 216 216 361 239 239 876 876 4,519 13 80%282 217 217 217 314 282 255 255 255 443 293 293 1,076 0 4,403 14 64%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10042.90 6.0 14 60%221 176 176 176 256 221 207 207 207 345 228 228 837 837 4,323 13 75%269 208 208 208 302 269 245 245 245 421 278 278 1,020 0 4,194 14 60%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/6/20 0:00 9337.17 6.0 13 70%252 197 197 197 285 252 232 232 232 393 260 260 952 0 3,938 12 93%326 249 249 249 358 326 291 291 291 516 342 342 0 0 3,830 13 70%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 7/6/20 6:00 10996.82 6.0 14 66%239 188 188 188 273 239 222 222 222 373 247 247 904 904 4,656 13 83%291 224 224 224 324 291 263 263 263 459 304 304 1,114 0 4,548 14 66%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11375.00 6.0 14 68%246 193 193 193 280 246 227 227 227 384 254 254 932 932 4,791 13 85%301 230 230 230 332 301 270 270 270 474 314 314 1,151 0 4,689 14 68%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11763.32 6.0 14 71%254 198 198 198 288 254 233 233 233 396 262 262 961 961 4,932 13 88%310 237 237 237 342 310 278 278 278 490 324 324 1,189 0 4,835 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/7/20 0:00 10719.30 6.0 14 64%234 185 185 185 268 234 218 218 218 364 241 241 884 884 4,558 13 80%285 219 219 219 317 285 257 257 257 448 296 296 1,087 0 4,444 14 64%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/7/20 6:00 11135.93 6.0 14 67%242 190 190 190 276 242 224 224 224 377 249 249 914 914 4,706 13 84%295 226 226 226 327 295 265 265 265 465 308 308 1,128 0 4,600 14 67%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10445.78 6.0 14 63%228 181 181 181 263 228 213 213 213 356 236 236 865 865 4,462 13 78%278 215 215 215 311 278 252 252 252 437 289 289 1,060 0 4,343 14 63%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11366.03 6.0 14 68%246 193 193 193 280 246 227 227 227 384 254 254 931 931 4,788 13 85%300 230 230 230 332 300 270 270 270 474 314 314 1,150 0 4,686 14 68%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/8/20 0:00 10616.56 6.0 14 64%232 183 183 183 266 232 216 216 216 361 239 239 877 877 4,522 13 80%282 217 217 217 315 282 256 256 256 444 294 294 1,077 0 4,406 14 64%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/8/20 6:00 11505.97 6.0 14 69%249 195 195 195 283 249 229 229 229 388 257 257 942 942 4,839 13 86%304 233 233 233 336 304 273 273 273 480 317 317 1,164 0 4,738 14 69%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11553.40 6.0 14 69%250 195 195 195 284 250 230 230 230 390 258 258 945 945 4,856 13 87%305 233 233 233 337 305 274 274 274 482 319 319 1,169 0 4,756 14 69%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11683.78 6.0 14 70%252 197 197 197 286 252 232 232 232 394 260 260 955 955 4,903 13 88%308 236 236 236 340 308 276 276 276 487 322 322 1,181 0 4,805 14 70%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/9/20 0:00 10985.73 6.0 14 66%239 188 188 188 273 239 222 222 222 372 246 246 903 903 4,652 13 82%291 224 224 224 323 291 263 263 263 459 304 304 1,113 0 4,544 14 66%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 7/9/20 6:00 11707.34 6.0 14 70%253 197 197 197 287 253 232 232 232 394 261 261 957 957 4,912 13 88%309 236 236 236 340 309 277 277 277 488 323 323 1,184 0 4,814 14 70%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11751.83 6.0 14 71%254 198 198 198 287 254 233 233 233 396 262 262 960 960 4,928 13 88%310 237 237 237 341 310 278 278 278 490 324 324 1,188 0 4,831 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11730.87 6.0 14 71%253 198 198 198 287 253 233 233 233 395 261 261 959 959 4,920 13 88%309 237 237 237 341 309 277 277 277 489 323 323 1,186 0 4,823 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10907.37 6.0 14 66%237 187 187 187 272 237 220 220 220 370 245 245 898 898 4,624 13 82%289 222 222 222 321 289 261 261 261 456 301 301 1,105 0 4,514 14 66%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11793.52 6.0 14 71%254 199 199 199 288 254 234 234 234 397 263 263 963 963 4,943 13 89%311 238 238 238 342 311 279 279 279 491 325 325 1,192 0 4,846 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11933.53 6.0 14 72%257 200 200 200 291 257 236 236 236 401 266 266 974 974 4,994 13 90%314 240 240 240 346 314 281 281 281 497 329 329 1,206 0 4,899 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11909.37 6.0 14 72%257 200 200 200 290 257 235 235 235 401 265 265 972 972 4,985 13 89%314 240 240 240 345 314 281 281 281 496 328 328 1,203 0 4,890 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10670.77 6.0 14 64%233 184 184 184 267 233 217 217 217 363 240 240 881 881 4,541 13 80%284 218 218 218 316 284 257 257 257 446 295 295 1,082 0 4,426 14 64%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11579.02 6.0 14 70%250 196 196 196 284 250 231 231 231 390 258 258 947 947 4,865 13 87%306 234 234 234 337 306 274 274 274 483 319 319 1,171 0 4,766 14 70%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12042.12 6.0 14 72%259 202 202 202 293 259 237 237 237 405 268 268 982 982 5,034 13 90%317 242 242 242 348 317 284 284 284 501 332 332 1,216 0 4,941 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11950.84 6.0 14 72%257 201 201 201 291 257 236 236 236 402 266 266 975 975 5,001 13 90%315 241 241 241 346 315 282 282 282 498 329 329 1,207 0 4,906 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10799.17 6.0 14 65%235 186 186 186 270 235 219 219 219 367 243 243 890 890 4,586 13 81%287 221 221 221 319 287 259 259 259 451 299 299 1,095 0 4,474 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11481.37 6.0 14 69%248 195 195 195 282 248 229 229 229 387 256 256 940 940 4,830 13 86%303 232 232 232 335 303 272 272 272 479 317 317 1,162 0 4,729 14 69%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11736.68 6.0 14 71%253 198 198 198 287 253 233 233 233 395 262 262 959 959 4,922 13 88%309 237 237 237 341 309 277 277 277 489 324 324 1,186 0 4,825 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11943.25 6.0 14 72%257 200 200 200 291 257 236 236 236 402 266 266 975 975 4,998 13 90%315 240 240 240 346 315 282 282 282 497 329 329 1,207 0 4,903 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10746.63 6.0 14 65%234 185 185 185 269 234 218 218 218 365 242 242 886 886 4,568 13 81%285 220 220 220 318 285 258 258 258 449 297 297 1,090 0 4,455 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11757.52 6.0 14 71%254 198 198 198 287 254 233 233 233 396 262 262 961 961 4,930 13 88%310 237 237 237 342 310 278 278 278 490 324 324 1,189 0 4,833 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11866.57 6.0 14 71%256 200 200 200 289 256 235 235 235 399 264 264 969 969 4,970 13 89%313 239 239 239 344 313 280 280 280 494 327 327 1,199 0 4,874 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11727.99 6.0 14 71%253 198 198 198 287 253 233 233 233 395 261 261 958 958 4,919 13 88%309 237 237 237 341 309 277 277 277 489 323 323 1,186 0 4,822 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10738.11 6.0 14 65%234 185 185 185 269 234 218 218 218 365 242 242 886 886 4,565 13 81%285 220 220 220 317 285 258 258 258 449 297 297 1,089 0 4,451 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11654.72 6.0 14 70%252 197 197 197 286 252 232 232 232 393 260 260 953 953 4,892 13 87%307 235 235 235 339 307 276 276 276 486 321 321 1,179 0 4,794 14 70%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11630.68 6.0 14 70%251 196 196 196 285 251 231 231 231 392 259 259 951 951 4,884 13 87%307 235 235 235 338 307 275 275 275 485 321 321 1,176 0 4,785 14 70%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12088.42 6.0 14 73%260 202 202 202 293 260 238 238 238 406 269 269 986 986 5,051 13 91%318 243 243 243 350 318 285 285 285 503 333 333 1,221 0 4,958 14 73%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11034.15 6.0 14 66%240 189 189 189 274 240 222 222 222 374 247 247 907 907 4,669 13 83%292 225 225 225 324 292 264 264 264 461 305 305 1,118 0 4,562 14 66%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12023.03 6.0 14 72%259 202 202 202 292 259 237 237 237 404 268 268 981 981 5,027 13 90%317 242 242 242 348 317 283 283 283 500 331 331 1,214 0 4,933 14 72%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12383.95 6.0 14 74%266 206 206 206 299 266 243 243 243 416 275 275 1,009 1,009 5,160 13 93%325 248 248 248 357 325 291 291 291 515 341 341 1,250 0 5,072 14 74%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12226.08 6.0 14 74%263 204 204 204 296 263 240 240 240 411 272 272 997 997 5,102 13 92%322 246 246 246 353 322 287 287 287 509 337 337 1,234 0 5,011 14 74%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11163.92 6.0 14 67%242 191 191 191 277 242 224 224 224 378 250 250 916 916 4,716 13 84%296 227 227 227 327 296 266 266 266 466 308 308 1,131 0 4,610 14 67%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11766.25 6.0 14 71%254 198 198 198 288 254 233 233 233 396 262 262 961 961 4,933 13 88%310 237 237 237 342 310 278 278 278 490 324 324 1,189 0 4,836 14 71%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 12376.96 6.0 14 74%266 206 206 206 299 266 242 242 242 416 275 275 1,008 1,008 5,158 13 93%325 248 248 248 357 325 290 290 290 515 341 341 1,249 0 5,069 14 74%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11493.46 6.0 14 69%249 195 195 195 283 249 229 229 229 388 257 257 941 941 4,834 13 86%304 232 232 232 335 304 273 273 273 479 317 317 1,163 0 4,734 14 69%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10146.29 6.0 14 61%223 177 177 177 258 223 209 209 209 348 230 230 844 844 4,358 13 76%271 210 210 210 304 271 247 247 247 425 281 281 1,030 0 4,232 14 61%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10786.46 6.0 14 65%235 186 186 186 270 235 219 219 219 366 242 242 889 889 4,582 13 81%286 220 220 220 319 286 259 259 259 451 298 298 1,094 0 4,469 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 11362.00 6.0 14 68%246 193 193 193 280 246 227 227 227 384 254 254 931 931 4,787 13 85%300 230 230 230 332 300 270 270 270 474 314 314 1,150 0 4,684 14 68%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 10645.02 6.0 14 64%232 184 184 184 267 232 216 216 216 362 240 240 879 879 4,532 13 80%283 218 218 218 315 283 256 256 256 445 294 294 1,080 0 4,417 14 64%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 9788.56 6.0 13 73%262 204 204 204 296 262 240 240 240 410 272 272 996 0 4,101 12 98%341 260 260 260 373 341 304 304 304 543 359 359 0 0 4,009 13 73%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 6/23/20 12:0 6/23/20 18:0 6/24/20 0:00 6/24/20 6:00 6/24/20 12:0 6/24/20 18:0 6/25/20 0:00 6/25/20 6:00 6/25/20 12:0 6/25/20 18:0 6/26/20 0:00 6/26/20 6:00 6/26/20 12:0 6/26/20 18:0 6/27/20 0:00 6/27/20 6:00 6/27/20 12:0 6/27/20 18:0 6/28/20 0:00 6/28/20 6:00 6/28/20 12:0 6/28/20 18:0 6/29/20 0:00 6/29/20 6:00 6/29/20 12:0 6/29/20 18:0 6/30/20 0:00 6/30/20 6:00 6/30/20 12:0 6/30/20 18:0 7/1/20 12:00 7/1/20 18:00 7/2/20 12:00 7/2/20 18:00 7/3/20 12:00 7/3/20 18:00 7/4/20 12:00 7/4/20 18:00 7/5/20 12:00 7/5/20 18:00 7/6/20 12:00 7/6/20 18:00 7/7/20 12:00 7/7/20 18:00 7/8/20 12:00 7/8/20 18:00 7/9/20 12:00 7/9/20 18:00 7/10/20 0:00 7/10/20 6:00 7/10/20 12:0 7/10/20 18:0 7/11/20 0:00 7/11/20 6:00 7/11/20 12:0 7/11/20 18:0 7/12/20 0:00 7/12/20 6:00 7/12/20 12:0 7/12/20 18:0 7/13/20 0:00 7/13/20 6:00 7/13/20 12:0 7/13/20 18:0 7/14/20 0:00 7/14/20 6:00 7/14/20 12:0 7/14/20 18:0 7/15/20 0:00 7/15/20 6:00 7/15/20 12:0 7/15/20 18:0 7/16/20 0:00 7/16/20 6:00 7/16/20 12:0 7/16/20 18:0 7/17/20 0:00 7/17/20 6:00 7/17/20 12:0 7/17/20 18:0 7/18/20 0:00 NEA BESS Scenario Analysis Data Analysis 20 7 86%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 52.9 7 86%8.1 6.1 6.1 6.1 9.0 8.1 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 50.9 5 90%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 73%7.0 5.5 5.5 5.5 8.1 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.7 5 90%8.5 6.4 6.4 6.4 9.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.8 4 96%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.9 5.5 5.5 5.5 8.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.4 4 96%9.0 6.7 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 6 84%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 72%6.9 5.5 5.5 5.5 8.1 6.9 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.8 6 84%7.9 6.0 6.0 6.0 8.8 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.8 6 83%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 71%6.8 5.5 5.5 5.5 8.0 6.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.5 6 83%7.8 6.0 6.0 6.0 8.8 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.5 5 89%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 73%6.9 5.5 5.5 5.5 8.1 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.5 5 89%8.4 6.3 6.3 6.3 9.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.6 5 75%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 61%5.9 5.0 5.0 5.0 7.3 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.2 5 75%7.2 5.6 5.6 5.6 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.4 6 99%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 8 75%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 52.5 6 99%9.4 6.9 6.9 6.9 9.9 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 49.2 7 90%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 54.5 7 90%8.5 6.3 6.3 6.3 9.2 8.5 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 52.7 5 92%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 75%7.1 5.6 5.6 5.6 8.3 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.4 5 92%8.7 6.5 6.5 6.5 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.6 5 80%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 65%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.7 5 80%7.6 5.9 5.9 5.9 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.7 8 93%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 83%7.8 6.0 6.0 6.0 8.8 7.8 7.1 7.1 7.1 0.0 0.0 0.0 0.0 0.0 63.6 8 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0 62.0 9 91%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 76%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 0.0 0.0 0.0 0.0 70.6 9 91%8.5 6.4 6.4 6.4 9.3 8.5 7.5 7.5 7.5 0.0 0.0 0.0 0.0 0.0 68.1 7 96%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 84%7.9 6.1 6.1 6.1 8.8 7.9 7.2 7.2 0.0 0.0 0.0 0.0 0.0 0.0 57.2 7 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 55.7 5 83%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 68%6.5 5.3 5.3 5.3 7.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.7 5 83%7.9 6.0 6.0 6.0 8.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.7 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 78%7.4 5.7 5.7 5.7 8.4 7.4 6.8 6.8 6.8 11.1 7.4 0.0 0.0 0.0 79.2 10 86%8.1 6.1 6.1 6.1 9.0 8.1 7.3 7.3 7.3 12.1 0.0 0.0 0.0 0.0 77.5 11 92%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 7.8 7.8 0.0 0.0 91.6 11 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 12.6 8.4 0.0 0.0 0.0 89.9 9 100%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 83%7.8 6.0 6.0 6.0 8.8 7.8 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.5 9 100%9.4 6.9 6.9 6.9 9.9 9.4 8.1 8.1 8.1 0.0 0.0 0.0 0.0 0.0 73.6 6 86%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 73%7.0 5.6 5.6 5.6 8.1 7.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 45.4 6 86%8.1 6.1 6.1 6.1 8.9 8.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.4 8 93%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 0.0 0.0 0.0 0.0 0.0 63.6 8 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0 61.9 9 89%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 74%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 6.6 10.8 0.0 0.0 0.0 0.0 69.7 9 89%8.4 6.3 6.3 6.3 9.2 8.4 7.4 7.4 7.4 0.0 0.0 0.0 0.0 0.0 67.1 8 92%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 0.0 0.0 0.0 0.0 0.0 63.1 8 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 0.0 0.0 0.0 0.0 0.0 0.0 61.3 8 89%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 0.0 0.0 0.0 0.0 0.0 61.6 8 89%8.4 6.3 6.3 6.3 9.2 8.4 7.4 7.4 0.0 0.0 0.0 0.0 0.0 0.0 59.7 9 97%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 0.0 0.0 0.0 0.0 74.2 9 97%9.2 6.7 6.7 6.7 9.8 9.2 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 72.1 9 94%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 0.0 0.0 0.0 0.0 72.6 9 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 7.7 0.0 0.0 0.0 0.0 0.0 70.3 8 99%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 10 74%7.0 5.6 5.6 5.6 8.2 7.0 6.6 6.6 6.6 10.7 0.0 0.0 0.0 0.0 69.3 8 99%9.4 6.9 6.9 6.9 9.9 9.4 8.1 8.1 0.0 0.0 0.0 0.0 0.0 0.0 65.3 8 94%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 0.0 0.0 0.0 0.0 0.0 64.0 8 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0 62.4 10 91%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 82%7.8 6.0 6.0 6.0 8.7 7.8 7.0 7.0 7.0 11.7 7.7 0.0 0.0 0.0 82.6 10 91%8.6 6.4 6.4 6.4 9.3 8.6 7.6 7.6 7.6 12.5 0.0 0.0 0.0 0.0 81.0 10 92%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 83%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 7.8 0.0 0.0 0.0 83.3 10 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 12.7 0.0 0.0 0.0 0.0 81.7 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.2 10 84%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.4 8 96%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 85%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 0.0 0.0 0.0 0.0 0.0 65.1 8 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 0.0 0.0 0.0 0.0 0.0 0.0 63.5 9 98%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 0.0 0.0 0.0 0.0 74.5 9 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 72.5 8 90%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 80%7.6 5.8 5.8 5.8 8.6 7.6 6.9 6.9 6.9 0.0 0.0 0.0 0.0 0.0 62.0 8 90%8.5 6.3 6.3 6.3 9.2 8.5 7.5 7.5 0.0 0.0 0.0 0.0 0.0 0.0 60.1 6 97%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 8 73%7.0 5.5 5.5 5.5 8.1 7.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 51.8 6 97%9.2 6.7 6.7 6.7 9.8 9.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 48.3 8 91%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 0.0 0.0 0.0 0.0 0.0 62.7 8 91%8.6 6.4 6.4 6.4 9.3 8.6 7.6 7.6 0.0 0.0 0.0 0.0 0.0 0.0 60.9 9 94%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 78%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.2 0.0 0.0 0.0 0.0 72.4 9 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 7.7 0.0 0.0 0.0 0.0 0.0 70.2 9 92%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 76%7.3 5.7 5.7 5.7 8.3 7.3 6.7 6.7 6.7 11.0 0.0 0.0 0.0 0.0 71.1 9 92%8.6 6.4 6.4 6.4 9.4 8.6 7.6 7.6 7.6 0.0 0.0 0.0 0.0 0.0 68.7 9 95%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 0.0 0.0 0.0 0.0 73.0 9 95%9.0 6.6 6.6 6.6 9.6 9.0 7.8 7.8 7.8 0.0 0.0 0.0 0.0 0.0 70.8 10 87%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 79%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.3 7.5 0.0 0.0 0.0 80.0 10 87%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.2 0.0 0.0 0.0 0.0 78.2 10 90%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 7.6 0.0 0.0 0.0 81.8 10 90%8.5 6.4 6.4 6.4 9.2 8.5 7.5 7.5 7.5 12.4 0.0 0.0 0.0 0.0 80.1 11 93%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 7.9 7.9 0.0 0.0 92.4 11 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 7.7 12.7 8.4 0.0 0.0 0.0 90.8 11 94%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 86%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 7.9 7.9 0.0 0.0 93.0 11 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 7.7 12.8 8.5 0.0 0.0 0.0 91.4 10 100%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 7.7 7.7 0.0 0.0 90.1 10 100%9.4 6.9 6.9 6.9 10.0 9.4 8.1 8.1 8.1 13.6 0.0 0.0 0.0 0.0 87.5 12 96%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 72%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.5 7.0 7.0 25.6 0.0 108.1 12 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 13.1 8.7 8.7 0.0 0.0 102.0 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.2 5.2 5.2 5.2 7.6 6.2 6.1 6.1 6.1 9.7 6.4 6.4 23.5 23.5 123.3 13 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 7.0 11.5 7.6 7.6 27.9 0.0 117.0 12 97%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 73%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.6 7.0 7.0 25.7 0.0 108.4 12 97%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 13.1 8.7 8.7 0.0 0.0 102.4 12 96%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 72%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.5 7.0 7.0 25.5 0.0 107.8 12 96%9.1 6.7 6.7 6.7 9.7 9.1 7.8 7.8 7.8 13.0 8.6 8.6 0.0 0.0 101.7 12 99%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 74%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 6.6 10.8 7.1 7.1 26.1 0.0 110.1 12 99%9.3 6.8 6.8 6.8 9.9 9.3 8.0 8.0 8.0 13.4 8.9 8.9 0.0 0.0 104.3 13 80%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 64%6.2 5.1 5.1 5.1 7.5 6.2 6.1 6.1 6.1 9.6 6.3 6.3 23.3 23.3 122.2 13 80%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.4 7.5 7.5 27.6 0.0 115.9 13 75%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 60%5.9 5.0 5.0 5.0 7.3 5.9 5.9 5.9 5.9 9.2 6.1 6.1 22.4 22.4 117.9 13 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 7.2 26.4 0.0 111.3 12 93%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.3 6.8 6.8 24.9 0.0 105.6 12 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 7.7 12.7 8.4 8.4 0.0 0.0 99.2 13 83%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 66%6.4 5.2 5.2 5.2 7.7 6.4 6.2 6.2 6.2 9.8 6.5 6.5 23.9 23.9 125.3 13 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 11.7 7.7 7.7 28.4 0.0 119.0 13 85%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 68%6.6 5.3 5.3 5.3 7.8 6.6 6.3 6.3 6.3 10.1 6.7 6.7 24.5 24.5 128.3 13 85%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 7.9 7.9 29.1 0.0 122.0 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 6.4 6.4 10.4 6.9 6.9 25.1 25.1 131.4 13 88%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.8 0.0 125.0 13 80%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 64%6.2 5.1 5.1 5.1 7.6 6.2 6.1 6.1 6.1 9.7 6.4 6.4 23.4 23.4 123.1 13 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.5 7.6 7.6 27.8 0.0 116.8 13 84%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 67%6.4 5.3 5.3 5.3 7.7 6.4 6.2 6.2 6.2 9.9 6.6 6.6 24.1 24.1 126.4 13 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 7.8 7.8 28.6 0.0 120.1 13 78%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 63%6.1 5.1 5.1 5.1 7.4 6.1 6.0 6.0 6.0 9.5 6.3 6.3 23.0 23.0 121.0 13 78%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.2 7.4 7.4 27.3 0.0 114.5 13 85%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 68%6.6 5.3 5.3 5.3 7.8 6.6 6.3 6.3 6.3 10.1 6.7 6.7 24.5 24.5 128.2 13 85%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 7.9 7.9 29.1 0.0 121.9 13 80%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 64%6.2 5.1 5.1 5.1 7.5 6.2 6.1 6.1 6.1 9.6 6.3 6.3 23.3 23.3 122.3 13 80%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.4 7.5 7.5 27.6 0.0 115.9 13 86%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 69%6.6 5.4 5.4 5.4 7.9 6.6 6.4 6.4 6.4 10.2 6.7 6.7 24.7 24.7 129.3 13 86%8.1 6.2 6.2 6.2 9.0 8.1 7.3 7.3 7.3 12.1 8.0 8.0 29.3 0.0 123.0 13 87%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 69%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.2 6.8 6.8 24.8 24.8 129.7 13 87%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.1 8.0 8.0 29.4 0.0 123.4 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.0 25.0 130.8 13 88%8.3 6.2 6.2 6.2 9.1 8.3 7.3 7.3 7.3 12.2 8.1 8.1 29.6 0.0 124.4 13 82%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 66%6.4 5.2 5.2 5.2 7.7 6.4 6.2 6.2 6.2 9.8 6.5 6.5 23.9 23.9 125.2 13 82%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 11.7 7.7 7.7 28.4 0.0 118.9 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 70%6.7 5.4 5.4 5.4 8.0 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.0 25.0 131.0 13 88%8.3 6.2 6.2 6.2 9.1 8.3 7.4 7.4 7.4 12.2 8.1 8.1 29.7 0.0 124.6 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 6.4 6.4 10.3 6.8 6.8 25.1 25.1 131.3 13 88%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.8 0.0 124.9 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.7 5.4 5.4 5.4 8.0 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.1 25.1 131.2 13 88%8.3 6.2 6.2 6.2 9.1 8.3 7.4 7.4 7.4 12.2 8.1 8.1 29.7 0.0 124.8 13 82%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 66%6.3 5.2 5.2 5.2 7.6 6.3 6.2 6.2 6.2 9.8 6.5 6.5 23.7 23.7 124.6 13 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 7.7 7.7 28.2 0.0 118.3 13 89%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 6.4 6.4 10.4 6.9 6.9 25.2 25.2 131.7 13 89%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.8 0.0 125.2 13 90%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.9 5.5 5.5 5.5 8.0 6.9 6.5 6.5 6.5 10.5 6.9 6.9 25.4 25.4 132.8 13 90%8.4 6.3 6.3 6.3 9.2 8.4 7.5 7.5 7.5 12.4 8.2 8.2 30.1 0.0 126.3 13 89%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.8 5.5 5.5 5.5 8.0 6.8 6.5 6.5 6.5 10.5 6.9 6.9 25.4 25.4 132.6 13 89%8.4 6.3 6.3 6.3 9.2 8.4 7.4 7.4 7.4 12.4 8.2 8.2 30.0 0.0 126.1 13 80%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 64%6.2 5.1 5.1 5.1 7.5 6.2 6.1 6.1 6.1 9.6 6.4 6.4 23.4 23.4 122.7 13 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 7.6 7.6 27.7 0.0 116.4 13 87%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.2 6.8 6.8 24.8 24.8 129.9 13 87%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.1 8.0 8.0 29.5 0.0 123.6 13 90%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.5 7.0 7.0 25.6 25.6 133.7 13 90%8.5 6.4 6.4 6.4 9.3 8.5 7.5 7.5 7.5 12.5 8.3 8.3 30.3 0.0 127.2 13 90%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.9 5.5 5.5 5.5 8.0 6.9 6.5 6.5 6.5 10.5 6.9 6.9 25.4 25.4 132.9 13 90%8.5 6.3 6.3 6.3 9.2 8.5 7.5 7.5 7.5 12.4 8.2 8.2 30.1 0.0 126.5 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.3 5.2 5.2 5.2 7.6 6.3 6.1 6.1 6.1 9.7 6.4 6.4 23.6 23.6 123.7 13 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 7.6 7.6 28.0 0.0 117.4 13 86%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 69%6.6 5.4 5.4 5.4 7.9 6.6 6.3 6.3 6.3 10.2 6.7 6.7 24.7 24.7 129.1 13 86%8.1 6.2 6.2 6.2 9.0 8.1 7.3 7.3 7.3 12.1 8.0 8.0 29.3 0.0 122.8 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.7 5.4 5.4 5.4 8.0 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.1 25.1 131.2 13 88%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.7 0.0 124.8 13 90%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.9 5.5 5.5 5.5 8.0 6.9 6.5 6.5 6.5 10.5 6.9 6.9 25.4 25.4 132.9 13 90%8.5 6.3 6.3 6.3 9.2 8.5 7.5 7.5 7.5 12.4 8.2 8.2 30.1 0.0 126.4 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.2 5.2 5.2 5.2 7.6 6.2 6.1 6.1 6.1 9.7 6.4 6.4 23.5 23.5 123.3 13 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 7.0 11.5 7.6 7.6 27.9 0.0 117.0 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 6.4 6.4 10.4 6.9 6.9 25.1 25.1 131.4 13 88%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.8 0.0 125.0 13 89%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.5 5.5 5.5 8.0 6.8 6.5 6.5 6.5 10.4 6.9 6.9 25.3 25.3 132.3 13 89%8.4 6.3 6.3 6.3 9.2 8.4 7.4 7.4 7.4 12.3 8.2 8.2 30.0 0.0 125.8 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.7 5.4 5.4 5.4 8.0 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.1 25.1 131.1 13 88%8.3 6.2 6.2 6.2 9.1 8.3 7.4 7.4 7.4 12.2 8.1 8.1 29.7 0.0 124.7 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.2 5.2 5.2 5.2 7.6 6.2 6.1 6.1 6.1 9.7 6.4 6.4 23.5 23.5 123.2 13 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 7.0 11.5 7.6 7.6 27.9 0.0 116.9 13 87%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.3 6.8 6.8 24.9 24.9 130.5 13 87%8.3 6.2 6.2 6.2 9.1 8.3 7.3 7.3 7.3 12.2 8.1 8.1 29.6 0.0 124.2 13 87%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.3 6.8 6.8 24.9 24.9 130.3 13 87%8.2 6.2 6.2 6.2 9.1 8.2 7.3 7.3 7.3 12.2 8.1 8.1 29.5 0.0 124.0 13 91%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 73%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.6 7.0 7.0 25.7 25.7 134.1 13 91%8.6 6.4 6.4 6.4 9.3 8.6 7.5 7.5 7.5 12.5 8.3 8.3 30.3 0.0 127.6 13 83%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 66%6.4 5.2 5.2 5.2 7.7 6.4 6.2 6.2 6.2 9.9 6.5 6.5 23.9 23.9 125.6 13 83%7.8 6.0 6.0 6.0 8.8 7.8 7.1 7.1 7.1 11.7 7.8 7.8 28.5 0.0 119.3 13 90%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 72%6.9 5.5 5.5 5.5 8.1 6.9 6.5 6.5 6.5 10.5 7.0 7.0 25.6 25.6 133.5 13 90%8.5 6.4 6.4 6.4 9.3 8.5 7.5 7.5 7.5 12.5 8.2 8.2 30.2 0.0 127.0 13 93%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 74%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 6.6 10.8 7.1 7.1 26.2 26.2 136.5 13 93%8.8 6.5 6.5 6.5 9.4 8.8 7.7 7.7 7.7 12.7 8.4 8.4 30.9 0.0 129.9 13 92%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 74%7.0 5.6 5.6 5.6 8.2 7.0 6.6 6.6 6.6 10.7 7.1 7.1 25.9 25.9 135.2 13 92%8.7 6.4 6.4 6.4 9.4 8.7 7.6 7.6 7.6 12.6 8.3 8.3 30.6 0.0 128.6 13 84%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 67%6.5 5.3 5.3 5.3 7.7 6.5 6.2 6.2 6.2 9.9 6.6 6.6 24.1 24.1 126.6 13 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 7.8 7.8 28.7 0.0 120.3 13 88%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 6.4 6.4 10.4 6.9 6.9 25.1 25.1 131.4 13 88%8.3 6.3 6.3 6.3 9.1 8.3 7.4 7.4 7.4 12.3 8.1 8.1 29.8 0.0 125.0 13 93%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 74%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 6.6 10.8 7.1 7.1 26.2 26.2 136.4 13 93%8.8 6.5 6.5 6.5 9.4 8.8 7.7 7.7 7.7 12.7 8.4 8.4 30.9 0.0 129.9 13 86%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 69%6.6 5.4 5.4 5.4 7.9 6.6 6.4 6.4 6.4 10.2 6.7 6.7 24.7 24.7 129.2 13 86%8.1 6.2 6.2 6.2 9.0 8.1 7.3 7.3 7.3 12.1 8.0 8.0 29.3 0.0 122.9 13 76%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 61%5.9 5.0 5.0 5.0 7.3 5.9 5.9 5.9 5.9 9.3 6.2 6.2 22.6 22.6 118.7 13 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 7.3 26.6 0.0 112.1 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.3 5.2 5.2 5.2 7.6 6.3 6.1 6.1 6.1 9.7 6.4 6.4 23.5 23.5 123.6 13 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 7.6 7.6 28.0 0.0 117.3 13 85%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 68%6.6 5.3 5.3 5.3 7.8 6.6 6.3 6.3 6.3 10.1 6.7 6.7 24.5 24.5 128.2 13 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 12.0 7.9 7.9 29.1 0.0 121.9 13 80%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 64%6.2 5.1 5.1 5.1 7.5 6.2 6.1 6.1 6.1 9.6 6.4 6.4 23.3 23.3 122.5 13 80%7.6 5.8 5.8 5.8 8.6 7.6 6.9 6.9 6.9 11.4 7.5 7.5 27.7 0.0 116.2 12 98%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 73%7.0 5.6 5.6 5.6 8.1 7.0 6.6 6.6 6.6 10.7 7.1 7.1 25.9 0.0 109.2 12 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 13.3 8.8 8.8 0.0 0.0 103.3 NEA BESS Scenario Analysis Data Analysis 21 9724.82 6.0 13 73%261 203 203 203 294 261 239 239 239 408 270 270 989 0 4,078 12 97%339 259 259 259 371 339 302 302 302 539 357 357 0 0 3,983 13 73%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 10767.83 6.0 14 65%235 185 185 185 269 235 218 218 218 366 242 242 888 888 4,575 13 81%286 220 220 220 318 286 258 258 258 450 298 298 1,092 0 4,463 14 65%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 9386.22 6.0 13 70%253 198 198 198 287 253 232 232 232 394 261 261 957 0 3,956 12 94%328 250 250 250 359 328 293 293 293 519 343 343 0 0 3,849 13 70%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8862.24 6.0 13 67%240 189 189 189 275 240 223 223 223 374 248 248 908 0 3,769 11 97%339 259 259 259 371 339 302 302 302 540 357 0 0 0 3,631 13 67%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 9368.39 6.0 13 70%252 197 197 197 286 252 232 232 232 394 261 261 955 0 3,949 12 93%327 250 250 250 359 327 292 292 292 518 343 343 0 0 3,842 13 70%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 10070.72 6.0 14 61%221 176 176 176 256 221 208 208 208 346 229 229 839 839 4,332 13 76%269 209 209 209 302 269 245 245 245 422 279 279 1,023 0 4,205 14 61%6 6 6 6 6 6 6 6 6 6 6 6 6 6 84 9139.17 6.0 13 69%247 194 194 194 281 247 228 228 228 385 255 255 934 0 3,867 12 91%320 244 244 244 351 320 286 286 286 505 335 335 0 0 3,754 13 69%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8735.10 6.0 13 66%237 187 187 187 272 237 220 220 220 370 245 245 897 0 3,724 11 96%335 255 255 255 366 335 298 298 298 531 352 0 0 0 3,580 13 66%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8660.15 6.0 12 86%304 233 233 233 336 304 273 273 273 480 318 318 0 0 3,576 11 95%332 253 253 253 364 332 296 296 296 526 348 0 0 0 3,550 12 86%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 8989.02 6.0 13 67%243 191 191 191 277 243 225 225 225 379 251 251 920 0 3,814 11 99%344 262 262 262 376 344 306 306 306 549 363 0 0 0 3,682 13 67%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8050.06 6.0 12 80%284 219 219 219 317 284 257 257 257 447 296 296 0 0 3,352 10 98%342 261 261 261 374 342 305 305 305 545 0 0 0 0 3,298 12 80%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7880.82 6.0 12 79%279 215 215 215 311 279 253 253 253 438 290 290 0 0 3,291 10 96%335 256 256 256 367 335 299 299 299 532 0 0 0 0 3,231 12 79%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 8614.54 6.0 12 86%302 232 232 232 334 302 272 272 272 478 316 316 0 0 3,559 11 94%330 252 252 252 362 330 295 295 295 523 346 0 0 0 3,533 12 86%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 9174.94 6.0 13 69%248 194 194 194 282 248 229 229 229 386 256 256 937 0 3,880 12 92%321 245 245 245 352 321 287 287 287 507 336 336 0 0 3,768 13 69%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8156.27 6.0 12 81%288 221 221 221 320 288 260 260 260 453 300 300 0 0 3,391 10 99%346 264 264 264 378 346 308 308 308 554 0 0 0 0 3,341 12 81%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7542.20 6.0 11 83%292 224 224 224 324 292 263 263 263 460 304 0 0 0 3,134 10 92%321 245 245 245 353 321 287 287 287 508 0 0 0 0 3,102 11 83%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 8392.60 6.0 12 84%295 227 227 227 327 295 266 266 266 466 308 308 0 0 3,477 11 92%322 246 246 246 354 322 288 288 288 510 337 0 0 0 3,448 12 84%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 9277.44 6.0 13 70%250 196 196 196 284 250 230 230 230 390 258 258 947 0 3,917 12 93%324 247 247 247 356 324 290 290 290 513 339 339 0 0 3,807 13 70%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 8795.40 6.0 13 66%239 188 188 188 273 239 221 221 221 372 246 246 902 0 3,745 11 96%337 257 257 257 369 337 300 300 300 535 354 0 0 0 3,604 13 66%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 7727.57 6.0 11 85%298 229 229 229 330 298 268 268 268 471 312 0 0 0 3,201 10 94%329 251 251 251 360 329 293 293 293 521 0 0 0 0 3,172 11 85%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 8063.77 6.0 12 80%285 219 219 219 317 285 257 257 257 448 296 296 0 0 3,357 10 98%342 261 261 261 374 342 305 305 305 546 0 0 0 0 3,304 12 80%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 8456.96 6.0 12 84%297 228 228 228 329 297 268 268 268 469 310 310 0 0 3,501 11 93%325 248 248 248 356 325 290 290 290 514 340 0 0 0 3,472 12 84%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 8043.15 6.0 12 80%284 219 219 219 316 284 257 257 257 447 296 296 0 0 3,350 10 98%341 261 261 261 373 341 304 304 304 544 0 0 0 0 3,295 12 80%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7488.14 6.0 11 82%290 223 223 223 322 290 262 262 262 457 302 0 0 0 3,114 10 91%319 244 244 244 351 319 285 285 285 505 0 0 0 0 3,082 11 82%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 8145.06 6.0 12 81%287 221 221 221 320 287 260 260 260 452 299 299 0 0 3,387 10 99%345 264 264 264 378 345 308 308 308 553 0 0 0 0 3,336 12 81%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7843.55 6.0 12 78%278 214 214 214 310 278 252 252 252 436 289 289 0 0 3,278 10 95%333 254 254 254 365 333 297 297 297 529 0 0 0 0 3,217 12 78%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 7198.07 6.0 11 79%280 216 216 216 312 280 254 254 254 439 291 0 0 0 3,010 10 88%308 235 235 235 339 308 276 276 276 486 0 0 0 0 2,974 11 79%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6505.95 6.0 10 79%280 216 216 216 313 280 254 254 254 441 0 0 0 0 2,725 9 95%331 253 253 253 363 331 296 296 296 0 0 0 0 0 2,672 10 79%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6769.51 6.0 10 82%291 223 223 223 323 291 262 262 262 458 0 0 0 0 2,819 9 99%344 263 263 263 376 344 307 307 307 0 0 0 0 0 2,773 10 82%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6589.15 6.0 10 80%284 218 218 218 316 284 257 257 257 446 0 0 0 0 2,755 9 96%335 256 256 256 367 335 299 299 299 0 0 0 0 0 2,704 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6915.08 6.0 11 76%270 209 209 209 303 270 246 246 246 423 280 0 0 0 2,909 10 84%296 227 227 227 328 296 267 267 267 468 0 0 0 0 2,871 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6037.67 6.0 10 73%262 204 204 204 296 262 240 240 240 410 0 0 0 0 2,561 8 99%345 263 263 263 377 345 307 307 0 0 0 0 0 0 2,471 10 73%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6858.07 6.0 10 83%294 226 226 226 326 294 265 265 265 464 0 0 0 0 2,851 9 100%348 266 266 266 381 348 311 311 311 0 0 0 0 0 2,807 10 83%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6869.46 6.0 11 75%268 208 208 208 301 268 244 244 244 420 278 0 0 0 2,893 10 84%295 226 226 226 327 295 265 265 265 465 0 0 0 0 2,855 11 75%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6591.86 6.0 10 80%284 219 219 219 316 284 257 257 257 446 0 0 0 0 2,756 9 96%336 256 256 256 367 336 299 299 299 0 0 0 0 0 2,705 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5359.82 6.0 9 78%277 214 214 214 310 277 251 251 251 0 0 0 0 0 2,261 8 88%308 236 236 236 340 308 276 276 0 0 0 0 0 0 2,217 9 78%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 5472.58 6.0 9 80%282 218 218 218 315 282 256 256 256 0 0 0 0 0 2,299 8 90%314 240 240 240 346 314 281 281 0 0 0 0 0 0 2,258 9 80%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 5742.44 6.0 9 84%295 226 226 226 327 295 266 266 266 0 0 0 0 0 2,394 8 94%329 251 251 251 361 329 294 294 0 0 0 0 0 0 2,359 9 84%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 5056.41 6.0 8 83%292 224 224 224 324 292 263 263 0 0 0 0 0 0 2,109 7 94%330 252 252 252 362 330 295 0 0 0 0 0 0 0 2,074 8 83%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 4037.21 6.0 7 75%269 208 208 208 302 269 245 0 0 0 0 0 0 0 1,709 6 88%309 236 236 236 340 309 0 0 0 0 0 0 0 0 1,666 7 75%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5153.81 6.0 8 84%297 228 228 228 329 297 268 268 0 0 0 0 0 0 2,143 7 96%336 257 257 257 368 336 300 0 0 0 0 0 0 0 2,111 8 84%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 5690.32 6.0 9 83%293 225 225 225 325 293 264 264 264 0 0 0 0 0 2,375 8 93%326 249 249 249 358 326 291 291 0 0 0 0 0 0 2,339 9 83%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 4918.07 6.0 8 81%285 219 219 219 317 285 258 258 0 0 0 0 0 0 2,061 7 92%322 246 246 246 353 322 288 0 0 0 0 0 0 0 2,022 8 81%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3916.78 6.0 7 73%262 203 203 203 295 262 239 0 0 0 0 0 0 0 1,667 6 85%300 230 230 230 332 300 0 0 0 0 0 0 0 0 1,622 7 73%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5156.01 6.0 8 84%298 228 228 228 329 298 268 268 0 0 0 0 0 0 2,144 7 96%337 257 257 257 368 337 300 0 0 0 0 0 0 0 2,112 8 84%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 5643.21 6.0 9 82%290 223 223 223 322 290 262 262 262 0 0 0 0 0 2,359 8 92%324 247 247 247 355 324 289 289 0 0 0 0 0 0 2,322 9 82%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 4612.68 6.0 8 76%269 208 208 208 302 269 245 245 0 0 0 0 0 0 1,955 7 86%303 232 232 232 335 303 272 0 0 0 0 0 0 0 1,911 8 76%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 3787.95 6.0 7 71%254 198 198 198 288 254 233 0 0 0 0 0 0 0 1,623 6 82%291 224 224 224 323 291 0 0 0 0 0 0 0 0 1,576 7 71%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 4324.21 6.0 7 81%286 220 220 220 318 286 258 0 0 0 0 0 0 0 1,808 6 94%329 251 251 251 361 329 0 0 0 0 0 0 0 0 1,773 7 81%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 4914.86 6.0 8 80%285 219 219 219 317 285 257 257 0 0 0 0 0 0 2,059 7 92%322 246 246 246 353 322 288 0 0 0 0 0 0 0 2,021 8 80%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 4065.66 6.0 7 76%270 209 209 209 303 270 246 0 0 0 0 0 0 0 1,718 6 88%311 238 238 238 342 311 0 0 0 0 0 0 0 0 1,676 7 76%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 3584.14 6.0 6 78%277 214 214 214 309 277 0 0 0 0 0 0 0 0 1,504 5 96%335 256 256 256 367 0 0 0 0 0 0 0 0 0 1,471 6 78%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3654.87 6.0 6 80%282 217 217 217 314 282 0 0 0 0 0 0 0 0 1,529 5 98%342 261 261 261 374 0 0 0 0 0 0 0 0 0 1,498 6 80%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 4410.78 6.0 7 82%291 224 224 224 323 291 262 0 0 0 0 0 0 0 1,839 6 96%335 256 256 256 367 335 0 0 0 0 0 0 0 0 1,806 7 82%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 3776.79 6.0 7 71%253 198 198 198 287 253 233 0 0 0 0 0 0 0 1,619 6 82%290 223 223 223 322 290 0 0 0 0 0 0 0 0 1,572 7 71%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8/1/20 0:00 3366.27 6.0 6 73%262 203 203 203 295 262 0 0 0 0 0 0 0 0 1,429 5 90%316 242 242 242 348 0 0 0 0 0 0 0 0 0 1,389 6 73%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 8/1/20 6:00 3482.79 6.0 6 76%270 209 209 209 303 270 0 0 0 0 0 0 0 0 1,469 5 93%326 249 249 249 358 0 0 0 0 0 0 0 0 0 1,432 6 76%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 4019.08 6.0 7 75%268 207 207 207 301 268 244 0 0 0 0 0 0 0 1,702 6 87%307 235 235 235 339 307 0 0 0 0 0 0 0 0 1,659 7 75%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 2335.94 6.0 5 63%227 181 181 181 262 0 0 0 0 0 0 0 0 0 1,032 4 83%294 225 225 225 0 0 0 0 0 0 0 0 0 0 969 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/2/20 0:00 2083.29 6.0 5 56%205 166 166 166 241 0 0 0 0 0 0 0 0 0 944 3 96%337 257 257 0 0 0 0 0 0 0 0 0 0 0 851 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/2/20 6:00 2420.09 6.0 5 65%235 186 186 186 269 0 0 0 0 0 0 0 0 0 1,061 4 86%303 232 232 232 0 0 0 0 0 0 0 0 0 0 1,000 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2259.51 6.0 5 61%221 176 176 176 256 0 0 0 0 0 0 0 0 0 1,006 4 80%285 219 219 219 0 0 0 0 0 0 0 0 0 0 942 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2131.36 6.0 5 57%210 169 169 169 245 0 0 0 0 0 0 0 0 0 961 3 99%344 263 263 0 0 0 0 0 0 0 0 0 0 0 870 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/3/20 0:00 1889.44 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 815 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 778 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 8/3/20 6:00 2370.08 6.0 5 63%230 183 183 183 265 0 0 0 0 0 0 0 0 0 1,044 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 982 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2427.12 6.0 5 65%235 186 186 186 270 0 0 0 0 0 0 0 0 0 1,063 4 86%304 233 233 233 0 0 0 0 0 0 0 0 0 0 1,002 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2344.45 6.0 5 63%228 181 181 181 263 0 0 0 0 0 0 0 0 0 1,035 4 83%295 226 226 226 0 0 0 0 0 0 0 0 0 0 973 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/4/20 0:00 2122.76 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 958 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 867 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/4/20 6:00 2628.17 6.0 5 70%253 197 197 197 286 0 0 0 0 0 0 0 0 0 1,131 4 94%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2569.99 6.0 5 69%248 194 194 194 282 0 0 0 0 0 0 0 0 0 1,112 4 91%321 245 245 245 0 0 0 0 0 0 0 0 0 0 1,055 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2270.20 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,009 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 946 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/5/20 0:00 2010.38 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 919 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 823 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/5/20 6:00 2565.91 6.0 5 69%247 194 194 194 281 0 0 0 0 0 0 0 0 0 1,110 4 91%320 245 245 245 0 0 0 0 0 0 0 0 0 0 1,054 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2554.55 6.0 5 68%246 193 193 193 280 0 0 0 0 0 0 0 0 0 1,106 4 91%319 244 244 244 0 0 0 0 0 0 0 0 0 0 1,050 5 68%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2265.73 6.0 5 61%221 177 177 177 256 0 0 0 0 0 0 0 0 0 1,008 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 945 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/6/20 0:00 2018.71 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 922 3 93%327 250 250 0 0 0 0 0 0 0 0 0 0 0 827 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/6/20 6:00 2607.78 6.0 5 70%251 196 196 196 285 0 0 0 0 0 0 0 0 0 1,124 4 93%325 248 248 248 0 0 0 0 0 0 0 0 0 0 1,070 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2696.64 6.0 5 72%259 201 201 201 292 0 0 0 0 0 0 0 0 0 1,154 4 96%335 256 256 256 0 0 0 0 0 0 0 0 0 0 1,104 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2451.98 6.0 5 66%238 187 187 187 272 0 0 0 0 0 0 0 0 0 1,071 4 87%307 235 235 235 0 0 0 0 0 0 0 0 0 0 1,012 5 66%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/7/20 0:00 2246.98 6.0 5 60%220 176 176 176 255 0 0 0 0 0 0 0 0 0 1,001 4 80%283 218 218 218 0 0 0 0 0 0 0 0 0 0 938 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/7/20 6:00 2561.80 6.0 5 69%247 194 194 194 281 0 0 0 0 0 0 0 0 0 1,109 4 91%320 244 244 244 0 0 0 0 0 0 0 0 0 0 1,052 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2303.34 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,021 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 958 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2138.57 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 964 3 99%345 264 264 0 0 0 0 0 0 0 0 0 0 0 873 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/8/20 0:00 1910.99 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 238 238 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 8/8/20 6:00 2135.92 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 963 3 99%345 263 263 0 0 0 0 0 0 0 0 0 0 0 872 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2119.02 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 957 3 98%342 261 261 0 0 0 0 0 0 0 0 0 0 0 865 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2035.24 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 927 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 833 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 8/9/20 0:00 1853.21 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 8/9/20 6:00 2042.37 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 930 3 95%331 252 252 0 0 0 0 0 0 0 0 0 0 0 836 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2138.71 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 964 3 99%345 264 264 0 0 0 0 0 0 0 0 0 0 0 873 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1955.08 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%317 243 243 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1780.73 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2035.16 6.0 5 54%201 163 163 163 237 0 0 0 0 0 0 0 0 0 927 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 833 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1983.70 6.0 5 53%197 160 160 160 232 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 813 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1870.01 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1741.88 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 764 3 81%285 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2038.76 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 929 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 834 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1899.98 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 819 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 782 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1798.51 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 7/18/20 6:00 7/18/20 12:0 7/18/20 18:0 7/19/20 0:00 7/19/20 6:00 7/19/20 12:0 7/19/20 18:0 7/20/20 0:00 7/20/20 6:00 7/20/20 12:0 7/20/20 18:0 7/21/20 0:00 7/21/20 6:00 7/21/20 12:0 7/21/20 18:0 7/22/20 0:00 7/22/20 6:00 7/22/20 12:0 7/22/20 18:0 7/23/20 0:00 7/23/20 6:00 7/23/20 12:0 7/23/20 18:0 7/24/20 0:00 7/24/20 6:00 7/24/20 12:0 7/24/20 18:0 7/25/20 0:00 7/25/20 6:00 7/25/20 12:0 7/25/20 18:0 7/26/20 0:00 7/26/20 6:00 7/26/20 12:0 7/26/20 18:0 7/27/20 0:00 7/27/20 6:00 7/27/20 12:0 7/27/20 18:0 7/28/20 0:00 7/28/20 6:00 7/28/20 12:0 7/28/20 18:0 7/29/20 0:00 7/29/20 6:00 7/29/20 12:0 7/29/20 18:0 7/30/20 0:00 7/30/20 6:00 7/30/20 12:0 7/30/20 18:0 7/31/20 0:00 7/31/20 6:00 7/31/20 12:0 7/31/20 18:0 8/1/20 12:00 8/1/20 18:00 8/2/20 12:00 8/2/20 18:00 8/3/20 12:00 8/3/20 18:00 8/4/20 12:00 8/4/20 18:00 8/5/20 12:00 8/5/20 18:00 8/6/20 12:00 8/6/20 18:00 8/7/20 12:00 8/7/20 18:00 8/8/20 12:00 8/8/20 18:00 8/9/20 12:00 8/9/20 18:00 8/10/20 0:00 8/10/20 6:00 8/10/20 12:0 8/10/20 18:0 8/11/20 0:00 8/11/20 6:00 8/11/20 12:0 8/11/20 18:0 NEA BESS Scenario Analysis Data Analysis 22 12 97%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 73%7.0 5.5 5.5 5.5 8.1 7.0 6.6 6.6 6.6 10.6 7.0 7.0 25.8 0.0 108.7 12 97%9.2 6.7 6.7 6.7 9.8 9.2 7.9 7.9 7.9 13.2 8.7 8.7 0.0 0.0 102.7 13 81%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 65%6.2 5.2 5.2 5.2 7.6 6.2 6.1 6.1 6.1 9.7 6.4 6.4 23.5 23.5 123.5 13 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 7.0 11.5 7.6 7.6 27.9 0.0 117.1 12 94%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 70%6.7 5.4 5.4 5.4 8.0 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.0 0.0 106.0 12 94%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 7.7 12.8 8.5 8.5 0.0 0.0 99.6 11 97%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 13 67%6.4 5.2 5.2 5.2 7.7 6.4 6.2 6.2 6.2 9.9 6.5 6.5 24.0 0.0 101.8 11 97%9.2 6.7 6.7 6.7 9.8 9.2 7.9 7.9 7.9 13.2 8.7 0.0 0.0 0.0 94.0 12 93%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.3 6.8 6.8 25.0 0.0 105.8 12 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 7.7 12.8 8.5 8.5 0.0 0.0 99.5 13 76%6 6 6 6 6 6 6 6 6 6 6 6 6 0 78 14 61%5.9 5.0 5.0 5.0 7.3 5.9 5.9 5.9 5.9 9.3 6.1 6.1 22.5 22.5 118.1 13 76%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 7.2 26.5 0.0 111.5 12 91%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 69%6.6 5.3 5.3 5.3 7.8 6.6 6.3 6.3 6.3 10.1 6.7 6.7 24.5 0.0 104.0 12 91%8.6 6.4 6.4 6.4 9.3 8.6 7.6 7.6 7.6 12.5 8.3 8.3 0.0 0.0 97.6 11 96%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 13 66%6.3 5.2 5.2 5.2 7.6 6.3 6.2 6.2 6.2 9.8 6.5 6.5 23.7 0.0 100.8 11 96%9.0 6.7 6.7 6.7 9.7 9.0 7.8 7.8 7.8 13.0 8.6 0.0 0.0 0.0 92.9 11 95%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 86%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.1 8.0 8.0 0.0 0.0 93.7 11 95%9.0 6.6 6.6 6.6 9.6 9.0 7.8 7.8 7.8 12.9 8.6 0.0 0.0 0.0 92.2 11 99%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 13 67%6.5 5.3 5.3 5.3 7.8 6.5 6.3 6.3 6.3 10.0 6.6 6.6 24.2 0.0 102.8 11 99%9.3 6.8 6.8 6.8 9.9 9.3 8.0 8.0 8.0 13.4 8.9 0.0 0.0 0.0 95.2 10 98%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.5 7.6 7.6 0.0 0.0 88.8 10 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 13.3 0.0 0.0 0.0 0.0 85.9 10 96%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 79%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.3 7.5 7.5 0.0 0.0 87.5 10 96%9.0 6.7 6.7 6.7 9.7 9.0 7.8 7.8 7.8 13.0 0.0 0.0 0.0 0.0 84.3 11 94%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 86%8.1 6.1 6.1 6.1 9.0 8.1 7.2 7.2 7.2 12.0 8.0 8.0 0.0 0.0 93.3 11 94%8.9 6.6 6.6 6.6 9.6 8.9 7.8 7.8 7.8 12.9 8.5 0.0 0.0 0.0 91.8 12 92%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 69%6.6 5.3 5.3 5.3 7.9 6.6 6.3 6.3 6.3 10.1 6.7 6.7 24.6 0.0 104.3 12 92%8.6 6.4 6.4 6.4 9.3 8.6 7.6 7.6 7.6 12.6 8.3 8.3 0.0 0.0 97.9 10 99%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 81%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 7.7 7.7 0.0 0.0 89.7 10 99%9.4 6.9 6.9 6.9 9.9 9.4 8.1 8.1 8.1 13.5 0.0 0.0 0.0 0.0 86.9 10 92%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 11.7 7.7 0.0 0.0 0.0 83.0 10 92%8.6 6.4 6.4 6.4 9.4 8.6 7.6 7.6 7.6 12.6 0.0 0.0 0.0 0.0 81.3 11 92%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 7.8 7.8 0.0 0.0 91.6 11 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 12.6 8.4 0.0 0.0 0.0 89.9 12 93%6 6 6 6 6 6 6 6 6 6 6 6 0 0 72 13 70%6.7 5.4 5.4 5.4 7.9 6.7 6.4 6.4 6.4 10.2 6.8 6.8 24.8 0.0 105.1 12 93%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 12.7 8.4 8.4 0.0 0.0 98.7 11 96%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 13 66%6.4 5.2 5.2 5.2 7.7 6.4 6.2 6.2 6.2 9.8 6.5 6.5 23.8 0.0 101.2 11 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 13.1 8.7 0.0 0.0 0.0 93.4 10 94%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 7.9 0.0 0.0 0.0 84.4 10 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 7.7 12.8 0.0 0.0 0.0 0.0 82.9 10 98%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.5 7.6 7.6 0.0 0.0 88.9 10 98%9.3 6.8 6.8 6.8 9.8 9.3 8.0 8.0 8.0 13.3 0.0 0.0 0.0 0.0 86.0 11 93%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 12 84%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 7.9 7.9 0.0 0.0 92.1 11 93%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 12.7 8.4 0.0 0.0 0.0 90.4 10 98%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 7.6 7.6 0.0 0.0 88.8 10 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 13.3 0.0 0.0 0.0 0.0 85.8 10 91%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 82%7.8 6.0 6.0 6.0 8.7 7.8 7.0 7.0 7.0 11.6 7.7 0.0 0.0 0.0 82.5 10 91%8.6 6.4 6.4 6.4 9.3 8.6 7.5 7.5 7.5 12.5 0.0 0.0 0.0 0.0 80.9 10 99%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.6 7.6 7.6 0.0 0.0 89.6 10 99%9.4 6.8 6.8 6.8 9.9 9.4 8.0 8.0 8.0 13.5 0.0 0.0 0.0 0.0 86.8 10 95%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 12 78%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.2 7.4 7.4 0.0 0.0 87.2 10 95%9.0 6.6 6.6 6.6 9.6 9.0 7.8 7.8 7.8 13.0 0.0 0.0 0.0 0.0 84.0 10 88%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 7.5 0.0 0.0 0.0 80.2 10 88%8.3 6.2 6.2 6.2 9.1 8.3 7.3 7.3 7.3 12.2 0.0 0.0 0.0 0.0 78.5 9 95%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 0.0 0.0 0.0 0.0 72.9 9 95%8.9 6.6 6.6 6.6 9.6 8.9 7.8 7.8 7.8 0.0 0.0 0.0 0.0 0.0 70.6 9 99%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 82%7.8 6.0 6.0 6.0 8.7 7.8 7.0 7.0 7.0 11.7 0.0 0.0 0.0 0.0 75.0 9 99%9.3 6.8 6.8 6.8 9.9 9.3 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 73.0 9 96%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.5 9 96%9.1 6.7 6.7 6.7 9.7 9.1 7.8 7.8 7.8 0.0 0.0 0.0 0.0 0.0 71.4 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 77.9 10 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.9 0.0 0.0 0.0 0.0 76.2 8 99%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 10 73%7.0 5.5 5.5 5.5 8.1 7.0 6.6 6.6 6.6 10.7 0.0 0.0 0.0 0.0 69.2 8 99%9.3 6.8 6.8 6.8 9.9 9.3 8.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0 65.1 9 100%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 83%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.7 9 100%9.4 6.9 6.9 6.9 10.0 9.4 8.1 8.1 8.1 0.0 0.0 0.0 0.0 0.0 73.8 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 77.6 10 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.8 9 96%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.5 9 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 71.4 8 88%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 78%7.4 5.8 5.8 5.8 8.4 7.4 6.8 6.8 6.8 0.0 0.0 0.0 0.0 0.0 61.0 8 88%8.3 6.2 6.2 6.2 9.1 8.3 7.4 7.4 0.0 0.0 0.0 0.0 0.0 0.0 59.0 8 90%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 80%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 0.0 0.0 0.0 0.0 0.0 61.9 8 90%8.4 6.3 6.3 6.3 9.2 8.4 7.5 7.5 0.0 0.0 0.0 0.0 0.0 0.0 60.0 8 94%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 0.0 0.0 0.0 0.0 0.0 64.1 8 94%8.9 6.6 6.6 6.6 9.5 8.9 7.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0 62.4 7 94%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 0.0 0.0 0.0 0.0 0.0 0.0 56.5 7 94%8.9 6.6 6.6 6.6 9.6 8.9 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 54.9 6 88%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 46.2 6 88%8.3 6.2 6.2 6.2 9.1 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.4 7 96%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 84%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 0.0 0.0 0.0 0.0 0.0 0.0 57.3 7 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 55.8 8 93%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 83%7.8 6.0 6.0 6.0 8.8 7.8 7.1 7.1 7.1 0.0 0.0 0.0 0.0 0.0 63.6 8 93%8.8 6.5 6.5 6.5 9.5 8.8 7.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0 62.0 7 92%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 0.0 0.0 0.0 0.0 0.0 0.0 55.4 7 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 53.7 6 85%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 73%7.0 5.5 5.5 5.5 8.1 7.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 45.3 6 85%8.0 6.1 6.1 6.1 8.9 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.3 7 96%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 84%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 0.0 0.0 0.0 0.0 0.0 0.0 57.3 7 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 55.8 8 92%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 82%7.8 6.0 6.0 6.0 8.7 7.8 7.0 7.0 7.0 0.0 0.0 0.0 0.0 0.0 63.2 8 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 0.0 0.0 0.0 0.0 0.0 0.0 61.5 7 86%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 76%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 52.9 7 86%8.1 6.2 6.2 6.2 9.0 8.1 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 51.0 6 82%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 71%6.8 5.4 5.4 5.4 8.0 6.8 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.2 6 82%7.8 6.0 6.0 6.0 8.7 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.2 6 94%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 48.5 6 94%8.9 6.6 6.6 6.6 9.5 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 47.0 7 92%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 55.3 7 92%8.7 6.4 6.4 6.4 9.4 8.7 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 53.6 6 88%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 46.4 6 88%8.3 6.3 6.3 6.3 9.1 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.6 5 96%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 78%7.4 5.8 5.8 5.8 8.4 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 40.5 5 96%9.1 6.7 6.7 6.7 9.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.8 5 98%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 80%7.5 5.8 5.8 5.8 8.5 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 41.1 5 98%9.2 6.8 6.8 6.8 9.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.4 6 96%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 82%7.8 6.0 6.0 6.0 8.7 7.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 49.3 6 96%9.1 6.7 6.7 6.7 9.7 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 47.8 6 82%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 71%6.7 5.4 5.4 5.4 8.0 6.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.1 6 82%7.8 6.0 6.0 6.0 8.7 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 42.1 5 90%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 73%7.0 5.5 5.5 5.5 8.1 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.7 5 90%8.5 6.4 6.4 6.4 9.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.8 5 93%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 76%7.2 5.7 5.7 5.7 8.3 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 39.7 5 93%8.8 6.5 6.5 6.5 9.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.9 6 87%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 75%7.1 5.6 5.6 5.6 8.3 7.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 46.1 6 87%8.2 6.2 6.2 6.2 9.1 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.2 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 96%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.3 4 86%8.1 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 87%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.4 4 86%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.7 4 83%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 94%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.5 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.4 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 68%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.4 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.8 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 96%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.9 5.5 5.5 5.5 8.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.4 4 96%9.1 6.7 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 66%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.6 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 4.9 4.9 4.9 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.1 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.4 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.8 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 95%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 NEA BESS Scenario Analysis Data Analysis 23 1675.96 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1923.74 6.0 4 68%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1889.61 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 815 3 87%308 235 235 0 0 0 0 0 0 0 0 0 0 0 778 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1798.66 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1678.69 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1942.38 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1917.25 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 824 3 89%312 238 238 0 0 0 0 0 0 0 0 0 0 0 788 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1976.56 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 907 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1823.18 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2087.72 6.0 5 56%206 166 166 166 241 0 0 0 0 0 0 0 0 0 946 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 853 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2036.42 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 928 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 833 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1858.79 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1698.83 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2008.28 6.0 5 54%199 162 162 162 235 0 0 0 0 0 0 0 0 0 918 3 93%326 249 249 0 0 0 0 0 0 0 0 0 0 0 823 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1969.26 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 904 3 91%320 244 244 0 0 0 0 0 0 0 0 0 0 0 808 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1859.64 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1685.98 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1880.15 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 812 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 775 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1885.69 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 814 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 777 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1815.63 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1607.57 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1813.75 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1871.61 6.0 4 67%241 189 189 189 0 0 0 0 0 0 0 0 0 0 809 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.84 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.75 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1731.70 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1737.36 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1682.30 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1524.94 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 688 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1648.68 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.81 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1648.24 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1495.86 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 264 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1639.91 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1668.10 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 739 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 699 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.77 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1452.46 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1614.92 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.49 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.99 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1473.10 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1612.87 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 719 3 75%266 207 207 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1693.79 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1662.31 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1505.30 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.01 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1618.63 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 721 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 681 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.05 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1413.45 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 649 2 94%327 250 0 0 0 0 0 0 0 0 0 0 0 0 577 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1614.81 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1543.09 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1481.05 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 673 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 603 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1335.94 6.0 4 48%178 148 148 148 0 0 0 0 0 0 0 0 0 0 621 2 88%311 237 0 0 0 0 0 0 0 0 0 0 0 0 548 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1505.38 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1510.60 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 683 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 615 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1493.45 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1346.10 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 624 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 552 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.48 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1557.07 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1529.60 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1347.52 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 625 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 552 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1541.31 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.48 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1478.19 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%341 261 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1345.05 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 624 2 89%312 239 0 0 0 0 0 0 0 0 0 0 0 0 551 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1573.57 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.63 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1434.42 6.0 4 51%190 155 155 155 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1320.92 6.0 4 47%176 146 146 146 0 0 0 0 0 0 0 0 0 0 615 2 87%307 235 0 0 0 0 0 0 0 0 0 0 0 0 542 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1483.30 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 674 2 98%343 261 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.47 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1490.77 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1323.03 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 616 2 88%308 235 0 0 0 0 0 0 0 0 0 0 0 0 543 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1464.00 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 667 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 597 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1528.32 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1559.15 6.0 4 56%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1355.92 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 628 2 90%315 241 0 0 0 0 0 0 0 0 0 0 0 0 555 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1585.39 6.0 4 56%208 167 167 167 0 0 0 0 0 0 0 0 0 0 710 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.42 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1538.73 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/1/20 0:00 1346.24 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 624 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 552 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/1/20 6:00 1504.73 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 612 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1533.65 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1471.73 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/2/20 0:00 1325.15 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 617 2 88%308 236 0 0 0 0 0 0 0 0 0 0 0 0 544 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/2/20 6:00 1571.14 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1611.12 6.0 4 57%211 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1585.13 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 710 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/3/20 0:00 1397.76 6.0 4 50%185 153 153 153 0 0 0 0 0 0 0 0 0 0 643 2 92%324 247 0 0 0 0 0 0 0 0 0 0 0 0 571 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/3/20 6:00 1597.54 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1600.44 6.0 4 57%209 169 169 169 0 0 0 0 0 0 0 0 0 0 715 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 675 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1542.51 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/4/20 0:00 1439.80 6.0 4 51%190 156 156 156 0 0 0 0 0 0 0 0 0 0 658 2 95%333 254 0 0 0 0 0 0 0 0 0 0 0 0 587 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/4/20 6:00 1634.28 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1505.49 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1512.53 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/5/20 0:00 1430.31 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 655 2 95%331 253 0 0 0 0 0 0 0 0 0 0 0 0 584 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/5/20 6:00 1543.17 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1469.48 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 8/12/20 0:00 8/12/20 6:00 8/12/20 12:0 8/12/20 18:0 8/13/20 0:00 8/13/20 6:00 8/13/20 12:0 8/13/20 18:0 8/14/20 0:00 8/14/20 6:00 8/14/20 12:0 8/14/20 18:0 8/15/20 0:00 8/15/20 6:00 8/15/20 12:0 8/15/20 18:0 8/16/20 0:00 8/16/20 6:00 8/16/20 12:0 8/16/20 18:0 8/17/20 0:00 8/17/20 6:00 8/17/20 12:0 8/17/20 18:0 8/18/20 0:00 8/18/20 6:00 8/18/20 12:0 8/18/20 18:0 8/19/20 0:00 8/19/20 6:00 8/19/20 12:0 8/19/20 18:0 8/20/20 0:00 8/20/20 6:00 8/20/20 12:0 8/20/20 18:0 8/21/20 0:00 8/21/20 6:00 8/21/20 12:0 8/21/20 18:0 8/22/20 0:00 8/22/20 6:00 8/22/20 12:0 8/22/20 18:0 8/23/20 0:00 8/23/20 6:00 8/23/20 12:0 8/23/20 18:0 8/24/20 0:00 8/24/20 6:00 8/24/20 12:0 8/24/20 18:0 8/25/20 0:00 8/25/20 6:00 8/25/20 12:0 8/25/20 18:0 8/26/20 0:00 8/26/20 6:00 8/26/20 12:0 8/26/20 18:0 8/27/20 0:00 8/27/20 6:00 8/27/20 12:0 8/27/20 18:0 8/28/20 0:00 8/28/20 6:00 8/28/20 12:0 8/28/20 18:0 8/29/20 0:00 8/29/20 6:00 8/29/20 12:0 8/29/20 18:0 8/30/20 0:00 8/30/20 6:00 8/30/20 12:0 8/30/20 18:0 8/31/20 0:00 8/31/20 6:00 8/31/20 12:0 8/31/20 18:0 9/1/20 12:00 9/1/20 18:00 9/2/20 12:00 9/2/20 18:00 9/3/20 12:00 9/3/20 18:00 9/4/20 12:00 9/4/20 18:00 9/5/20 12:00 NEA BESS Scenario Analysis Data Analysis 24 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 87%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 88%8.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.6 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 NEA BESS Scenario Analysis Data Analysis 25 1477.64 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%341 261 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/6/20 0:00 1320.01 6.0 4 47%176 146 146 146 0 0 0 0 0 0 0 0 0 0 615 2 87%307 235 0 0 0 0 0 0 0 0 0 0 0 0 542 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/6/20 6:00 1441.75 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 95%333 255 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1527.62 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1443.56 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/7/20 0:00 1285.54 6.0 3 60%218 174 174 0 0 0 0 0 0 0 0 0 0 0 566 2 85%300 230 0 0 0 0 0 0 0 0 0 0 0 0 529 3 60%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 9/7/20 6:00 1460.45 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 665 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 595 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1484.20 6.0 4 53%196 159 159 159 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1446.08 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 590 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/8/20 0:00 1305.27 6.0 4 46%174 145 145 145 0 0 0 0 0 0 0 0 0 0 610 2 86%304 233 0 0 0 0 0 0 0 0 0 0 0 0 537 4 46%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/8/20 6:00 1482.73 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 673 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1472.25 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1452.03 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 662 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 9/9/20 0:00 1294.07 6.0 3 60%219 175 175 0 0 0 0 0 0 0 0 0 0 0 569 2 86%301 231 0 0 0 0 0 0 0 0 0 0 0 0 532 3 60%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 9/9/20 6:00 1474.32 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 601 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1410.42 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 648 2 93%327 249 0 0 0 0 0 0 0 0 0 0 0 0 576 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1448.41 6.0 4 52%191 157 157 157 0 0 0 0 0 0 0 0 0 0 661 2 96%335 256 0 0 0 0 0 0 0 0 0 0 0 0 591 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1354.07 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 627 2 90%314 240 0 0 0 0 0 0 0 0 0 0 0 0 555 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1528.09 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1444.97 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1451.24 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 662 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1355.16 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 628 2 90%315 240 0 0 0 0 0 0 0 0 0 0 0 0 555 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1562.96 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 702 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1473.01 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1445.25 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1374.51 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 635 2 91%319 244 0 0 0 0 0 0 0 0 0 0 0 0 562 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1511.11 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 683 2 100%349 266 0 0 0 0 0 0 0 0 0 0 0 0 615 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1470.24 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1470.61 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1371.25 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.58 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1461.32 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1457.64 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1324.90 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 617 2 88%308 236 0 0 0 0 0 0 0 0 0 0 0 0 544 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1531.57 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1502.29 6.0 4 53%198 161 161 161 0 0 0 0 0 0 0 0 0 0 680 2 99%347 265 0 0 0 0 0 0 0 0 0 0 0 0 611 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1519.41 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 686 3 70%253 197 197 0 0 0 0 0 0 0 0 0 0 0 647 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1339.08 6.0 4 48%178 148 148 148 0 0 0 0 0 0 0 0 0 0 622 2 89%311 238 0 0 0 0 0 0 0 0 0 0 0 0 549 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1549.37 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1488.45 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%344 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1454.57 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1355.07 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 628 2 90%315 240 0 0 0 0 0 0 0 0 0 0 0 0 555 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1531.13 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.61 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1479.14 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1330.23 6.0 4 47%177 147 147 147 0 0 0 0 0 0 0 0 0 0 619 2 88%309 237 0 0 0 0 0 0 0 0 0 0 0 0 546 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1563.67 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 702 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.28 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1552.61 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1369.05 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 560 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1576.31 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 707 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 667 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.09 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1532.61 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%254 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1418.28 6.0 4 50%188 154 154 154 0 0 0 0 0 0 0 0 0 0 650 2 94%328 251 0 0 0 0 0 0 0 0 0 0 0 0 579 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1559.42 6.0 4 56%204 165 165 165 0 0 0 0 0 0 0 0 0 0 701 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1490.79 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1493.43 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1375.25 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 635 2 91%319 244 0 0 0 0 0 0 0 0 0 0 0 0 563 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1521.33 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 687 3 70%253 197 197 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1477.60 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%341 261 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1507.53 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1356.09 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 628 2 90%315 241 0 0 0 0 0 0 0 0 0 0 0 0 556 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1567.88 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 664 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.38 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1479.57 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 603 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1338.62 6.0 4 48%178 148 148 148 0 0 0 0 0 0 0 0 0 0 622 2 89%311 238 0 0 0 0 0 0 0 0 0 0 0 0 549 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1591.21 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1513.26 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1491.00 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1392.55 6.0 4 50%185 152 152 152 0 0 0 0 0 0 0 0 0 0 641 2 92%323 246 0 0 0 0 0 0 0 0 0 0 0 0 569 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1602.80 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1576.70 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 707 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 667 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.21 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1406.50 6.0 4 50%186 153 153 153 0 0 0 0 0 0 0 0 0 0 646 2 93%326 249 0 0 0 0 0 0 0 0 0 0 0 0 575 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.86 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.96 6.0 4 57%211 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1580.74 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1407.81 6.0 4 50%187 153 153 153 0 0 0 0 0 0 0 0 0 0 647 2 93%326 249 0 0 0 0 0 0 0 0 0 0 0 0 575 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1647.44 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1604.18 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1528.69 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1371.96 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 634 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1541.22 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1515.87 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1514.90 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1423.61 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1546.06 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 696 3 72%256 200 200 0 0 0 0 0 0 0 0 0 0 0 656 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1557.84 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1524.97 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 688 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1365.63 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 631 2 90%317 242 0 0 0 0 0 0 0 0 0 0 0 0 559 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1571.06 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1598.51 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1597.70 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1415.78 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 649 2 94%328 250 0 0 0 0 0 0 0 0 0 0 0 0 578 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1625.91 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1612.38 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 719 3 75%266 207 207 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1600.82 6.0 4 57%209 169 169 169 0 0 0 0 0 0 0 0 0 0 715 3 74%265 205 205 0 0 0 0 0 0 0 0 0 0 0 675 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1375.53 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 635 2 91%319 244 0 0 0 0 0 0 0 0 0 0 0 0 563 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 943.16 6.0 3 44%165 139 139 0 0 0 0 0 0 0 0 0 0 0 443 2 62%227 180 0 0 0 0 0 0 0 0 0 0 0 0 407 3 44%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 9/5/20 18:00 9/6/20 12:00 9/6/20 18:00 9/7/20 12:00 9/7/20 18:00 9/8/20 12:00 9/8/20 18:00 9/9/20 12:00 9/9/20 18:00 9/10/20 0:00 9/10/20 6:00 9/10/20 12:0 9/10/20 18:0 9/11/20 0:00 9/11/20 6:00 9/11/20 12:0 9/11/20 18:0 9/12/20 0:00 9/12/20 6:00 9/12/20 12:0 9/12/20 18:0 9/13/20 0:00 9/13/20 6:00 9/13/20 12:0 9/13/20 18:0 9/14/20 0:00 9/14/20 6:00 9/14/20 12:0 9/14/20 18:0 9/15/20 0:00 9/15/20 6:00 9/15/20 12:0 9/15/20 18:0 9/16/20 0:00 9/16/20 6:00 9/16/20 12:0 9/16/20 18:0 9/17/20 0:00 9/17/20 6:00 9/17/20 12:0 9/17/20 18:0 9/18/20 0:00 9/18/20 6:00 9/18/20 12:0 9/18/20 18:0 9/19/20 0:00 9/19/20 6:00 9/19/20 12:0 9/19/20 18:0 9/20/20 0:00 9/20/20 6:00 9/20/20 12:0 9/20/20 18:0 9/21/20 0:00 9/21/20 6:00 9/21/20 12:0 9/21/20 18:0 9/22/20 0:00 9/22/20 6:00 9/22/20 12:0 9/22/20 18:0 9/23/20 0:00 9/23/20 6:00 9/23/20 12:0 9/23/20 18:0 9/24/20 0:00 9/24/20 6:00 9/24/20 12:0 9/24/20 18:0 9/25/20 0:00 9/25/20 6:00 9/25/20 12:0 9/25/20 18:0 9/26/20 0:00 9/26/20 6:00 9/26/20 12:0 9/26/20 18:0 9/27/20 0:00 9/27/20 6:00 9/27/20 12:0 9/27/20 18:0 9/28/20 0:00 9/28/20 6:00 9/28/20 12:0 9/28/20 18:0 9/29/20 0:00 9/29/20 6:00 9/29/20 12:0 9/29/20 18:0 9/30/20 0:00 9/30/20 6:00 NEA BESS Scenario Analysis Data Analysis 26 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 85%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 60%5.8 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 85%8.0 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.1 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 86%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 46%4.7 4.2 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.4 2 86%8.1 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.3 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 86%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 60%5.8 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 86%8.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.2 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 88%8.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 62%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 3 44%4.4 4.1 4.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 12.6 2 62%6.0 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 11.1 NEA BESS Scenario Analysis Data Analysis 27 300.80 6.0 2 20%93 86 0 0 0 0 0 0 0 0 0 0 0 0 178 1 35%137 0 0 0 0 0 0 0 0 0 0 0 0 0 137 2 20%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 1581.72 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.95 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1407.56 6.0 4 50%187 153 153 153 0 0 0 0 0 0 0 0 0 0 646 2 93%326 249 0 0 0 0 0 0 0 0 0 0 0 0 575 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1560.95 6.0 4 56%205 165 165 165 0 0 0 0 0 0 0 0 0 0 701 3 72%259 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1538.46 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1511.11 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 683 2 100%349 266 0 0 0 0 0 0 0 0 0 0 0 0 615 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1370.84 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1523.20 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 688 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1540.52 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1487.90 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%344 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1352.95 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 627 2 90%314 240 0 0 0 0 0 0 0 0 0 0 0 0 554 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1469.64 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1415.02 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 649 2 94%328 250 0 0 0 0 0 0 0 0 0 0 0 0 578 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1477.31 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1342.10 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 623 2 89%312 238 0 0 0 0 0 0 0 0 0 0 0 0 550 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1532.13 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%254 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1397.15 6.0 4 50%185 152 152 152 0 0 0 0 0 0 0 0 0 0 643 2 92%324 247 0 0 0 0 0 0 0 0 0 0 0 0 571 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1441.66 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 95%333 255 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1332.34 6.0 4 47%178 147 147 147 0 0 0 0 0 0 0 0 0 0 619 2 88%310 237 0 0 0 0 0 0 0 0 0 0 0 0 547 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1528.43 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1434.99 6.0 4 51%190 156 156 156 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1491.85 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1346.92 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 625 2 89%313 239 0 0 0 0 0 0 0 0 0 0 0 0 552 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1585.42 6.0 4 56%208 167 167 167 0 0 0 0 0 0 0 0 0 0 710 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.62 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1513.08 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1308.99 6.0 4 47%175 145 145 145 0 0 0 0 0 0 0 0 0 0 611 2 87%305 233 0 0 0 0 0 0 0 0 0 0 0 0 538 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1508.74 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 683 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 614 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1488.11 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%344 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1496.03 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 264 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1319.93 6.0 4 47%176 146 146 146 0 0 0 0 0 0 0 0 0 0 615 2 87%307 235 0 0 0 0 0 0 0 0 0 0 0 0 542 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1506.96 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1416.58 6.0 4 50%188 154 154 154 0 0 0 0 0 0 0 0 0 0 650 2 94%328 250 0 0 0 0 0 0 0 0 0 0 0 0 578 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1452.68 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 256 0 0 0 0 0 0 0 0 0 0 0 0 592 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1319.34 6.0 4 47%176 146 146 146 0 0 0 0 0 0 0 0 0 0 615 2 87%307 235 0 0 0 0 0 0 0 0 0 0 0 0 542 4 47%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1476.90 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1433.99 6.0 4 51%190 155 155 155 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1489.61 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1380.36 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 637 2 91%320 245 0 0 0 0 0 0 0 0 0 0 0 0 565 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1482.98 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 673 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1372.30 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 634 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 562 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1461.52 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1352.00 6.0 4 48%180 149 149 149 0 0 0 0 0 0 0 0 0 0 627 2 89%314 240 0 0 0 0 0 0 0 0 0 0 0 0 554 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.60 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1411.81 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 648 2 93%327 250 0 0 0 0 0 0 0 0 0 0 0 0 577 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1525.12 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 688 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1428.95 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 654 2 95%331 252 0 0 0 0 0 0 0 0 0 0 0 0 583 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1571.57 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1434.43 6.0 4 51%190 155 155 155 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1502.52 6.0 4 53%198 161 161 161 0 0 0 0 0 0 0 0 0 0 680 2 99%347 265 0 0 0 0 0 0 0 0 0 0 0 0 611 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1357.88 6.0 4 48%181 149 149 149 0 0 0 0 0 0 0 0 0 0 629 2 90%315 241 0 0 0 0 0 0 0 0 0 0 0 0 556 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1566.80 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1524.39 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 688 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.54 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1477.24 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1655.03 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.76 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1561.48 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 701 3 72%259 201 201 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1448.33 6.0 4 52%191 157 157 157 0 0 0 0 0 0 0 0 0 0 661 2 96%335 256 0 0 0 0 0 0 0 0 0 0 0 0 591 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1652.30 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 211 211 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1487.50 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1552.68 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1443.09 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 95%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1557.77 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1579.19 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1551.63 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 658 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1363.11 6.0 4 49%181 150 150 150 0 0 0 0 0 0 0 0 0 0 631 2 90%316 242 0 0 0 0 0 0 0 0 0 0 0 0 558 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.94 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1404.68 6.0 4 50%186 153 153 153 0 0 0 0 0 0 0 0 0 0 645 2 93%325 248 0 0 0 0 0 0 0 0 0 0 0 0 574 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1473.14 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1369.78 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1522.45 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 687 3 70%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1495.98 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 264 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1508.36 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 614 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1367.64 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 632 2 90%317 242 0 0 0 0 0 0 0 0 0 0 0 0 560 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1547.26 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 696 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1424.39 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 653 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.08 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1426.87 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 653 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 582 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.32 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1556.93 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1569.87 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1410.22 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 647 2 93%327 249 0 0 0 0 0 0 0 0 0 0 0 0 576 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1585.83 6.0 4 56%208 167 167 167 0 0 0 0 0 0 0 0 0 0 710 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1580.55 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1558.12 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1389.12 6.0 4 49%184 152 152 152 0 0 0 0 0 0 0 0 0 0 640 2 92%322 246 0 0 0 0 0 0 0 0 0 0 0 0 568 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.45 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1490.77 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 676 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1488.30 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%344 262 0 0 0 0 0 0 0 0 0 0 0 0 606 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1343.15 6.0 4 48%179 148 148 148 0 0 0 0 0 0 0 0 0 0 623 2 89%312 239 0 0 0 0 0 0 0 0 0 0 0 0 551 4 48%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1454.48 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1461.34 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1463.40 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1303.18 6.0 4 46%174 145 145 145 0 0 0 0 0 0 0 0 0 0 609 2 86%303 232 0 0 0 0 0 0 0 0 0 0 0 0 536 4 46%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1430.93 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 655 2 95%331 253 0 0 0 0 0 0 0 0 0 0 0 0 584 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1549.02 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1538.84 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 10/1/20 6:00 10/1/20 12:0 10/1/20 18:0 10/2/20 0:00 10/2/20 6:00 10/2/20 12:0 10/2/20 18:0 10/3/20 0:00 10/3/20 6:00 10/3/20 12:0 10/3/20 18:0 10/4/20 0:00 10/4/20 6:00 10/4/20 12:0 10/4/20 18:0 10/5/20 0:00 10/5/20 6:00 10/5/20 12:0 10/5/20 18:0 10/6/20 0:00 10/6/20 6:00 10/6/20 12:0 10/6/20 18:0 10/7/20 0:00 10/7/20 6:00 10/7/20 12:0 10/7/20 18:0 10/8/20 0:00 10/8/20 6:00 10/8/20 12:0 10/8/20 18:0 10/9/20 0:00 10/9/20 6:00 10/9/20 12:0 10/9/20 18:0 10/10/20 0:0 10/10/20 6:0 10/10/20 12 10/10/20 18 10/11/20 0:0 10/11/20 6:0 10/11/20 12 10/11/20 18 10/12/20 0:0 10/12/20 6:0 10/12/20 12 10/12/20 18 10/13/20 0:0 10/13/20 6:0 10/13/20 12 10/13/20 18 10/14/20 0:0 10/14/20 6:0 10/14/20 12 10/14/20 18 10/15/20 0:0 10/15/20 6:0 10/15/20 12 10/15/20 18 10/16/20 0:0 10/16/20 6:0 10/16/20 12 10/16/20 18 10/17/20 0:0 10/17/20 6:0 10/17/20 12 10/17/20 18 10/18/20 0:0 10/18/20 6:0 10/18/20 12 10/18/20 18 10/19/20 0:0 10/19/20 6:0 10/19/20 12 10/19/20 18 10/20/20 0:0 10/20/20 6:0 10/20/20 12 10/20/20 18 10/21/20 0:0 10/21/20 6:0 10/21/20 12 10/21/20 18 10/22/20 0:0 10/22/20 6:0 10/22/20 12 10/22/20 18 10/23/20 0:0 10/23/20 6:0 10/23/20 12 10/23/20 18 10/24/20 0:0 10/24/20 6:0 10/24/20 12 10/24/20 18 10/25/20 0:0 10/25/20 6:0 10/25/20 12 10/25/20 18 NEA BESS Scenario Analysis Data Analysis 28 1 35%6 0 0 0 0 0 0 0 0 0 0 0 0 0 6 2 20%2.5 2.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 5.3 1 35%3.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 90%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.2 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 88%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 88%8.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.6 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.3 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.5 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 87%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 47%4.7 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 87%8.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.4 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 2 90%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 90%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 89%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 48%4.8 4.3 4.3 4.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 89%8.4 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.7 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 2 86%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 46%4.7 4.2 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.4 2 86%8.1 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.3 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 NEA BESS Scenario Analysis Data Analysis 29 1376.47 6.0 4 49%183 151 151 151 0 0 0 0 0 0 0 0 0 0 635 2 91%319 244 0 0 0 0 0 0 0 0 0 0 0 0 563 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1538.12 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1424.27 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1501.30 6.0 4 53%198 161 161 161 0 0 0 0 0 0 0 0 0 0 680 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 611 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1369.58 6.0 4 49%182 150 150 150 0 0 0 0 0 0 0 0 0 0 633 2 91%318 243 0 0 0 0 0 0 0 0 0 0 0 0 561 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1556.06 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1496.95 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.70 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1384.01 6.0 4 49%184 151 151 151 0 0 0 0 0 0 0 0 0 0 638 2 92%321 245 0 0 0 0 0 0 0 0 0 0 0 0 566 4 49%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1579.12 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1569.30 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 664 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1580.68 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1425.54 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 653 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 582 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1611.24 6.0 4 57%211 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1617.80 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 721 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 681 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1625.89 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1505.01 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 681 2 100%347 265 0 0 0 0 0 0 0 0 0 0 0 0 612 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1746.14 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1669.54 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 739 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 699 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.04 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.29 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.51 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.06 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1671.97 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1569.97 5.0 4 56%171 139 139 139 0 0 0 0 0 0 0 0 0 0 587 3 73%217 169 169 0 0 0 0 0 0 0 0 0 0 0 554 4 56%5 5 5 5 0 0 0 0 0 0 0 0 0 0 20 1622.06 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 207 207 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1670.43 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1768.61 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1620.34 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1786.07 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1806.08 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1781.36 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1606.42 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 717 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 677 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1738.50 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1656.89 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 735 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 695 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1736.39 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1595.50 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1784.36 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1721.40 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 218 218 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1792.26 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1620.91 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%268 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1750.56 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1770.72 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1662.18 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1463.43 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 666 2 97%338 258 0 0 0 0 0 0 0 0 0 0 0 0 596 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.36 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1553.01 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1580.77 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1422.56 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1499.61 6.0 4 53%197 161 161 161 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 610 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.70 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1607.49 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1390.94 6.0 4 50%185 152 152 152 0 0 0 0 0 0 0 0 0 0 641 2 92%322 246 0 0 0 0 0 0 0 0 0 0 0 0 569 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1487.05 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 675 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1596.70 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1645.66 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1432.33 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 655 2 95%331 253 0 0 0 0 0 0 0 0 0 0 0 0 584 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1592.03 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1588.71 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 711 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1621.21 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%268 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1422.02 6.0 4 51%188 154 154 154 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 580 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1570.05 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.65 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.34 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1423.56 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%330 252 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1554.39 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1648.80 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1630.53 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.63 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1660.94 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 736 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1709.85 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 753 3 79%281 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1684.25 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1472.69 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1624.75 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1554.69 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1666.78 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1530.86 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1643.14 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 690 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1301.67 6.0 4 46%174 145 145 145 0 0 0 0 0 0 0 0 0 0 608 2 86%303 232 0 0 0 0 0 0 0 0 0 0 0 0 535 4 46%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1753.72 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1624.32 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1681.51 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1720.77 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1816.46 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%297 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1636.65 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1778.35 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 738 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1700.25 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1806.28 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1625.41 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1760.31 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 81%288 222 222 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1728.72 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.91 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 738 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1591.52 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1774.01 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1779.21 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 777 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 738 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1826.99 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1609.07 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1646.65 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1618.57 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 721 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 681 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 10/26/20 0:0 10/26/20 6:0 10/26/20 12 10/26/20 18 10/27/20 0:0 10/27/20 6:0 10/27/20 12 10/27/20 18 10/28/20 0:0 10/28/20 6:0 10/28/20 12 10/28/20 18 10/29/20 0:0 10/29/20 6:0 10/29/20 12 10/29/20 18 10/30/20 0:0 10/30/20 6:0 10/30/20 12 10/30/20 18 10/31/20 0:0 10/31/20 6:0 10/31/20 12 10/31/20 18 11/1/20 0:00 11/1/20 5:00 11/1/20 11:0 11/1/20 17:0 11/1/20 23:0 11/2/20 5:00 11/2/20 11:0 11/2/20 17:0 11/2/20 23:0 11/3/20 5:00 11/3/20 11:0 11/3/20 17:0 11/3/20 23:0 11/4/20 5:00 11/4/20 11:0 11/4/20 17:0 11/4/20 23:0 11/5/20 5:00 11/5/20 11:0 11/5/20 17:0 11/5/20 23:0 11/6/20 5:00 11/6/20 11:0 11/6/20 17:0 11/6/20 23:0 11/7/20 5:00 11/7/20 11:0 11/7/20 17:0 11/7/20 23:0 11/8/20 5:00 11/8/20 11:0 11/8/20 17:0 11/8/20 23:0 11/9/20 5:00 11/9/20 11:0 11/9/20 17:0 11/9/20 23:0 11/10/20 5:0 11/10/20 11 11/10/20 17 11/10/20 23 11/11/20 5:0 11/11/20 11 11/11/20 17 11/11/20 23 11/12/20 5:0 11/12/20 11 11/12/20 17 11/12/20 23 11/13/20 5:0 11/13/20 11 11/13/20 17 11/13/20 23 11/14/20 5:0 11/14/20 11 11/14/20 17 11/14/20 23 11/15/20 5:0 11/15/20 11 11/15/20 17 11/15/20 23 11/16/20 5:0 11/16/20 11 11/16/20 17 11/16/20 23 11/17/20 5:0 11/17/20 11 11/17/20 17 11/17/20 23 11/18/20 5:0 11/18/20 11 11/18/20 17 11/18/20 23 11/19/20 5:0 11/19/20 11 NEA BESS Scenario Analysis Data Analysis 30 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 91%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 91%8.5 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.9 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 49%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 92%8.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 73%5 5 5 0 0 0 0 0 0 0 0 0 0 0 15 4 56%4.6 3.9 3.9 3.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.4 3 73%5.8 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.1 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 86%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 46%4.7 4.2 4.2 4.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.4 2 86%8.1 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 14.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 NEA BESS Scenario Analysis Data Analysis 31 1622.90 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1446.35 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 590 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1589.13 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 711 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1698.11 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1603.63 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1414.42 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 649 2 94%328 250 0 0 0 0 0 0 0 0 0 0 0 0 578 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1507.93 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 614 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1571.25 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.30 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1455.99 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1526.40 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.87 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.05 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1404.60 6.0 4 50%186 153 153 153 0 0 0 0 0 0 0 0 0 0 645 2 93%325 248 0 0 0 0 0 0 0 0 0 0 0 0 574 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 578.42 6.0 2 38%148 127 0 0 0 0 0 0 0 0 0 0 0 0 274 1 67%242 0 0 0 0 0 0 0 0 0 0 0 0 0 242 2 38%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 1392.59 6.0 4 50%185 152 152 152 0 0 0 0 0 0 0 0 0 0 641 2 92%323 246 0 0 0 0 0 0 0 0 0 0 0 0 569 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1653.20 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%272 211 211 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1453.81 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1537.03 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 653 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1572.75 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1681.45 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1431.58 6.0 4 51%189 155 155 155 0 0 0 0 0 0 0 0 0 0 655 2 95%331 253 0 0 0 0 0 0 0 0 0 0 0 0 584 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1543.63 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1555.98 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.64 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1455.89 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1520.27 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 687 3 70%253 197 197 0 0 0 0 0 0 0 0 0 0 0 647 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1613.28 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%266 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.07 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1472.55 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.26 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1623.69 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1680.62 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1456.99 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1538.00 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 693 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1640.59 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1640.43 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1514.99 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1563.46 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 702 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1655.65 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1704.37 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1533.87 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 692 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1706.07 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1759.64 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1641.75 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1465.47 6.0 4 52%193 158 158 158 0 0 0 0 0 0 0 0 0 0 667 2 97%339 258 0 0 0 0 0 0 0 0 0 0 0 0 597 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1606.02 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 717 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 677 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1662.96 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1661.78 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1492.31 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1641.52 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%271 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1704.95 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1789.42 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%292 225 225 0 0 0 0 0 0 0 0 0 0 0 742 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1643.24 6.0 4 59%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 690 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1827.96 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 756 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1843.55 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 799 3 85%301 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1909.73 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 237 237 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.37 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1845.40 6.0 4 66%238 187 187 187 0 0 0 0 0 0 0 0 0 0 800 3 85%301 231 231 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1896.75 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 817 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1950.10 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 897 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1788.34 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1848.65 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 801 3 86%301 231 231 0 0 0 0 0 0 0 0 0 0 0 763 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1957.35 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 900 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 803 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1984.33 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 813 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1820.26 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1882.60 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%306 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1997.70 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 914 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 819 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1978.89 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 908 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1748.82 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1799.67 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1842.74 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 799 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1817.60 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 752 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1615.62 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1736.21 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1747.43 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1754.02 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1540.95 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1697.33 6.0 4 60%221 176 176 176 0 0 0 0 0 0 0 0 0 0 749 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 709 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1798.00 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1864.60 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 769 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1738.52 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1898.26 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1954.84 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1924.98 6.0 4 69%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1726.57 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1826.64 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1842.35 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 799 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.63 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1507.74 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1530.95 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.37 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1614.24 6.0 4 57%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1442.32 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 95%334 255 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.39 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1587.34 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 710 3 73%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1588.50 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 711 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1422.17 6.0 4 51%188 154 154 154 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1591.41 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 11/19/20 17 11/19/20 23 11/20/20 5:0 11/20/20 11 11/20/20 17 11/20/20 23 11/21/20 5:0 11/21/20 11 11/21/20 17 11/21/20 23 11/22/20 5:0 11/22/20 11 11/22/20 17 11/22/20 23 11/23/20 5:0 11/23/20 11 11/23/20 17 11/23/20 23 11/24/20 5:0 11/24/20 11 11/24/20 17 11/24/20 23 11/25/20 5:0 11/25/20 11 11/25/20 17 11/25/20 23 11/26/20 5:0 11/26/20 11 11/26/20 17 11/26/20 23 11/27/20 5:0 11/27/20 11 11/27/20 17 11/27/20 23 11/28/20 5:0 11/28/20 11 11/28/20 17 11/28/20 23 11/29/20 5:0 11/29/20 11 11/29/20 17 11/29/20 23 11/30/20 5:0 11/30/20 11 11/30/20 17 11/30/20 23 12/1/20 5:00 12/1/20 11:0 12/1/20 17:0 12/1/20 23:0 12/2/20 5:00 12/2/20 11:0 12/2/20 17:0 12/2/20 23:0 12/3/20 5:00 12/3/20 11:0 12/3/20 17:0 12/3/20 23:0 12/4/20 5:00 12/4/20 11:0 12/4/20 17:0 12/4/20 23:0 12/5/20 5:00 12/5/20 11:0 12/5/20 17:0 12/5/20 23:0 12/6/20 5:00 12/6/20 11:0 12/6/20 17:0 12/6/20 23:0 12/7/20 5:00 12/7/20 11:0 12/7/20 17:0 12/7/20 23:0 12/8/20 5:00 12/8/20 11:0 12/8/20 17:0 12/8/20 23:0 12/9/20 5:00 12/9/20 11:0 12/9/20 17:0 12/9/20 23:0 12/10/20 5:0 12/10/20 11 12/10/20 17 12/10/20 23 12/11/20 5:0 12/11/20 11 12/11/20 17 12/11/20 23 12/12/20 5:0 12/12/20 11 12/12/20 17 12/12/20 23 12/13/20 5:0 12/13/20 11 12/13/20 17 12/13/20 23 12/14/20 5:0 NEA BESS Scenario Analysis Data Analysis 32 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 1 67%6 0 0 0 0 0 0 0 0 0 0 0 0 0 6 2 38%4.0 3.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 7.8 1 67%6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.4 2 92%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%4.9 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 92%8.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 73%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 NEA BESS Scenario Analysis Data Analysis 33 1636.95 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1649.80 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 732 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 692 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1485.46 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 674 2 98%343 262 0 0 0 0 0 0 0 0 0 0 0 0 605 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1665.09 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1680.38 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1674.94 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%275 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1475.51 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 671 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 601 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1615.50 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1722.70 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1733.62 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.61 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1731.12 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1832.92 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1870.07 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1676.73 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1823.58 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1896.71 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 817 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1879.91 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 812 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 775 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1695.83 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.20 6.0 4 63%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1804.11 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1797.68 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1544.02 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 656 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.57 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1659.85 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 736 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1704.19 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1525.30 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1631.40 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1671.44 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1632.56 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1454.62 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1540.12 6.0 4 55%202 164 164 164 0 0 0 0 0 0 0 0 0 0 694 3 71%256 199 199 0 0 0 0 0 0 0 0 0 0 0 654 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1548.41 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1599.47 6.0 4 57%209 169 169 169 0 0 0 0 0 0 0 0 0 0 715 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 675 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1434.14 6.0 4 51%190 155 155 155 0 0 0 0 0 0 0 0 0 0 656 2 95%332 253 0 0 0 0 0 0 0 0 0 0 0 0 585 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1533.36 6.0 4 55%201 163 163 163 0 0 0 0 0 0 0 0 0 0 691 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1602.82 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1633.07 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1444.28 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 660 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1516.66 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1670.77 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1668.74 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 739 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 699 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1457.96 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 665 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1483.28 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 674 2 98%343 261 0 0 0 0 0 0 0 0 0 0 0 0 604 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1508.84 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 683 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 614 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1560.63 6.0 4 56%205 165 165 165 0 0 0 0 0 0 0 0 0 0 701 3 72%259 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1472.43 6.0 4 52%194 159 159 159 0 0 0 0 0 0 0 0 0 0 670 2 97%340 260 0 0 0 0 0 0 0 0 0 0 0 0 600 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1535.53 6.0 4 55%202 163 163 163 0 0 0 0 0 0 0 0 0 0 692 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 653 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1641.40 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%271 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1693.72 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 748 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 708 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1515.91 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.13 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1592.71 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 205 205 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1631.06 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1447.27 6.0 4 52%191 156 156 156 0 0 0 0 0 0 0 0 0 0 661 2 96%335 255 0 0 0 0 0 0 0 0 0 0 0 0 590 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1527.19 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1570.99 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1603.62 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1443.44 6.0 4 51%191 156 156 156 0 0 0 0 0 0 0 0 0 0 659 2 96%334 255 0 0 0 0 0 0 0 0 0 0 0 0 589 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1526.14 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1583.38 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1616.56 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 721 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 681 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1419.29 6.0 4 51%188 154 154 154 0 0 0 0 0 0 0 0 0 0 651 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 579 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1530.40 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1620.37 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1611.70 6.0 4 57%211 169 169 169 0 0 0 0 0 0 0 0 0 0 719 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1469.70 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1575.21 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1589.37 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 711 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1626.66 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1477.49 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%341 260 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/1/21 5:00 1506.39 6.0 4 54%198 161 161 161 0 0 0 0 0 0 0 0 0 0 682 2 100%348 265 0 0 0 0 0 0 0 0 0 0 0 0 613 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1529.44 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 651 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1660.26 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 736 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.86 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/2/21 5:00 1671.51 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.38 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1818.59 6.0 4 65%235 185 185 185 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 752 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1680.96 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/3/21 5:00 1743.74 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.07 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1869.12 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%304 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1687.18 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/4/21 5:00 1732.43 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.26 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1775.99 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.86 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/5/21 5:00 1758.72 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1869.25 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%304 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1850.30 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 802 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 764 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1672.24 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 213 213 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/6/21 5:00 1776.42 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1861.31 6.0 4 66%239 189 189 189 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1834.92 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1604.44 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 677 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/7/21 5:00 1703.03 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1822.62 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1820.33 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1597.50 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 12/14/20 11 12/14/20 17 12/14/20 23 12/15/20 5:0 12/15/20 11 12/15/20 17 12/15/20 23 12/16/20 5:0 12/16/20 11 12/16/20 17 12/16/20 23 12/17/20 5:0 12/17/20 11 12/17/20 17 12/17/20 23 12/18/20 5:0 12/18/20 11 12/18/20 17 12/18/20 23 12/19/20 5:0 12/19/20 11 12/19/20 17 12/19/20 23 12/20/20 5:0 12/20/20 11 12/20/20 17 12/20/20 23 12/21/20 5:0 12/21/20 11 12/21/20 17 12/21/20 23 12/22/20 5:0 12/22/20 11 12/22/20 17 12/22/20 23 12/23/20 5:0 12/23/20 11 12/23/20 17 12/23/20 23 12/24/20 5:0 12/24/20 11 12/24/20 17 12/24/20 23 12/25/20 5:0 12/25/20 11 12/25/20 17 12/25/20 23 12/26/20 5:0 12/26/20 11 12/26/20 17 12/26/20 23 12/27/20 5:0 12/27/20 11 12/27/20 17 12/27/20 23 12/28/20 5:0 12/28/20 11 12/28/20 17 12/28/20 23 12/29/20 5:0 12/29/20 11 12/29/20 17 12/29/20 23 12/30/20 5:0 12/30/20 11 12/30/20 17 12/30/20 23 12/31/20 5:0 12/31/20 11 12/31/20 17 12/31/20 23 1/1/21 11:00 1/1/21 17:00 1/1/21 23:00 1/2/21 11:00 1/2/21 17:00 1/2/21 23:00 1/3/21 11:00 1/3/21 17:00 1/3/21 23:00 1/4/21 11:00 1/4/21 17:00 1/4/21 23:00 1/5/21 11:00 1/5/21 17:00 1/5/21 23:00 1/6/21 11:00 1/6/21 17:00 1/6/21 23:00 1/7/21 11:00 1/7/21 17:00 1/7/21 23:00 NEA BESS Scenario Analysis Data Analysis 34 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 98%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%9.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 NEA BESS Scenario Analysis Data Analysis 35 1/8/21 5:00 1732.44 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1758.09 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1776.56 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1666.35 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/9/21 5:00 1755.42 6.0 4 62%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 729 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1808.17 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1829.01 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 756 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1653.02 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 77%272 211 211 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1587.43 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 710 3 73%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1625.61 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1630.87 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1457.35 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1582.29 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.30 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1632.98 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1440.43 6.0 4 51%190 156 156 156 0 0 0 0 0 0 0 0 0 0 658 2 95%333 254 0 0 0 0 0 0 0 0 0 0 0 0 588 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1570.62 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 705 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 665 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1638.77 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1682.20 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1512.59 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1628.23 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1643.23 6.0 4 59%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 690 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1657.04 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 735 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 695 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1510.52 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 683 2 100%348 266 0 0 0 0 0 0 0 0 0 0 0 0 615 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1675.29 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1702.98 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1687.20 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1526.50 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1632.07 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1671.41 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1645.43 6.0 4 59%215 172 172 172 0 0 0 0 0 0 0 0 0 0 731 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 691 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1515.38 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 685 3 70%252 197 197 0 0 0 0 0 0 0 0 0 0 0 646 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.63 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1623.43 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1601.58 6.0 4 57%209 169 169 169 0 0 0 0 0 0 0 0 0 0 715 3 74%265 205 205 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1422.77 6.0 4 51%188 155 155 155 0 0 0 0 0 0 0 0 0 0 652 2 94%329 251 0 0 0 0 0 0 0 0 0 0 0 0 581 4 51%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1479.55 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%342 261 0 0 0 0 0 0 0 0 0 0 0 0 603 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1534.54 6.0 4 55%202 163 163 163 0 0 0 0 0 0 0 0 0 0 692 3 71%255 199 199 0 0 0 0 0 0 0 0 0 0 0 652 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1610.28 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 75%266 206 206 0 0 0 0 0 0 0 0 0 0 0 679 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1453.93 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 663 2 96%336 257 0 0 0 0 0 0 0 0 0 0 0 0 593 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.82 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1651.96 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1719.32 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1602.56 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 716 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 676 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1718.59 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1793.11 6.0 4 64%232 183 183 183 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1701.28 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1456.91 6.0 4 52%192 157 157 157 0 0 0 0 0 0 0 0 0 0 664 2 96%337 257 0 0 0 0 0 0 0 0 0 0 0 0 594 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1605.15 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 717 3 74%265 206 206 0 0 0 0 0 0 0 0 0 0 0 677 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1622.42 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1663.36 6.0 4 59%217 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1470.83 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 669 2 97%340 259 0 0 0 0 0 0 0 0 0 0 0 0 599 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1574.21 6.0 4 56%206 167 167 167 0 0 0 0 0 0 0 0 0 0 706 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 666 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1624.84 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1615.67 6.0 4 58%211 170 170 170 0 0 0 0 0 0 0 0 0 0 720 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 680 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1415.63 6.0 4 50%187 154 154 154 0 0 0 0 0 0 0 0 0 0 649 2 94%328 250 0 0 0 0 0 0 0 0 0 0 0 0 578 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1551.33 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 698 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 658 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1584.28 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1580.69 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 708 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 668 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1403.86 6.0 4 50%186 153 153 153 0 0 0 0 0 0 0 0 0 0 645 2 93%325 248 0 0 0 0 0 0 0 0 0 0 0 0 574 4 50%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1492.28 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1609.13 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1664.78 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1526.81 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1553.90 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1632.29 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 726 3 76%269 208 208 0 0 0 0 0 0 0 0 0 0 0 686 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1701.55 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1543.19 6.0 4 55%203 164 164 164 0 0 0 0 0 0 0 0 0 0 695 3 71%256 200 200 0 0 0 0 0 0 0 0 0 0 0 655 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1664.14 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 737 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 697 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1705.75 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1729.98 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 720 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1576.97 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 707 3 73%261 203 203 0 0 0 0 0 0 0 0 0 0 0 667 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1742.92 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1736.61 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%285 219 219 0 0 0 0 0 0 0 0 0 0 0 723 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1820.89 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1637.66 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1763.50 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 732 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1764.43 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1733.66 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1491.62 6.0 4 53%196 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%344 263 0 0 0 0 0 0 0 0 0 0 0 0 607 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1638.11 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1664.76 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 738 3 77%274 212 212 0 0 0 0 0 0 0 0 0 0 0 698 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1642.64 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 730 3 76%271 210 210 0 0 0 0 0 0 0 0 0 0 0 690 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1449.54 6.0 4 52%191 157 157 157 0 0 0 0 0 0 0 0 0 0 662 2 96%335 256 0 0 0 0 0 0 0 0 0 0 0 0 591 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1594.72 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1668.64 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 739 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 699 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1702.07 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1638.89 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1742.53 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1812.67 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1890.88 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 815 3 88%308 235 235 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1747.60 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1806.25 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1821.99 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1919.63 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 825 3 89%312 239 239 0 0 0 0 0 0 0 0 0 0 0 789 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.89 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/1/21 5:00 1922.70 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 826 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 790 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1955.84 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 803 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1922.47 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 826 3 89%312 239 239 0 0 0 0 0 0 0 0 0 0 0 790 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1/8/21 11:00 1/8/21 17:00 1/8/21 23:00 1/9/21 11:00 1/9/21 17:00 1/9/21 23:00 1/10/21 5:00 1/10/21 11:0 1/10/21 17:0 1/10/21 23:0 1/11/21 5:00 1/11/21 11:0 1/11/21 17:0 1/11/21 23:0 1/12/21 5:00 1/12/21 11:0 1/12/21 17:0 1/12/21 23:0 1/13/21 5:00 1/13/21 11:0 1/13/21 17:0 1/13/21 23:0 1/14/21 5:00 1/14/21 11:0 1/14/21 17:0 1/14/21 23:0 1/15/21 5:00 1/15/21 11:0 1/15/21 17:0 1/15/21 23:0 1/16/21 5:00 1/16/21 11:0 1/16/21 17:0 1/16/21 23:0 1/17/21 5:00 1/17/21 11:0 1/17/21 17:0 1/17/21 23:0 1/18/21 5:00 1/18/21 11:0 1/18/21 17:0 1/18/21 23:0 1/19/21 5:00 1/19/21 11:0 1/19/21 17:0 1/19/21 23:0 1/20/21 5:00 1/20/21 11:0 1/20/21 17:0 1/20/21 23:0 1/21/21 5:00 1/21/21 11:0 1/21/21 17:0 1/21/21 23:0 1/22/21 5:00 1/22/21 11:0 1/22/21 17:0 1/22/21 23:0 1/23/21 5:00 1/23/21 11:0 1/23/21 17:0 1/23/21 23:0 1/24/21 5:00 1/24/21 11:0 1/24/21 17:0 1/24/21 23:0 1/25/21 5:00 1/25/21 11:0 1/25/21 17:0 1/25/21 23:0 1/26/21 5:00 1/26/21 11:0 1/26/21 17:0 1/26/21 23:0 1/27/21 5:00 1/27/21 11:0 1/27/21 17:0 1/27/21 23:0 1/28/21 5:00 1/28/21 11:0 1/28/21 17:0 1/28/21 23:0 1/29/21 5:00 1/29/21 11:0 1/29/21 17:0 1/29/21 23:0 1/30/21 5:00 1/30/21 11:0 1/30/21 17:0 1/30/21 23:0 1/31/21 5:00 1/31/21 11:0 1/31/21 17:0 1/31/21 23:0 2/1/21 11:00 2/1/21 17:00 NEA BESS Scenario Analysis Data Analysis 36 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 73%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 95%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 95%9.0 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.6 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 100%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 100%9.4 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 51%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 94%8.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 97%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 94%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 94%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.4 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 2 93%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 50%5.0 4.4 4.4 4.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 2 93%8.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.3 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 71%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.7 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 96%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 2 96%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.7 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 NEA BESS Scenario Analysis Data Analysis 37 1701.06 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/2/21 5:00 1799.43 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1769.04 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1711.25 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 216 216 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1557.34 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/3/21 5:00 1715.70 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1701.61 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 216 216 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1702.44 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 751 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 711 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.22 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 677 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/4/21 5:00 1670.49 6.0 4 59%217 174 174 174 0 0 0 0 0 0 0 0 0 0 740 3 77%275 212 212 0 0 0 0 0 0 0 0 0 0 0 700 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1699.64 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1809.17 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1684.12 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/5/21 5:00 1739.39 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1716.70 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 756 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1683.13 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1512.30 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%251 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/6/21 5:00 1582.05 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 203 203 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1707.75 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1799.99 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1675.87 6.0 4 60%218 174 174 174 0 0 0 0 0 0 0 0 0 0 741 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 701 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/7/21 5:00 1730.49 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1773.74 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1812.76 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 750 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1683.06 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/8/21 5:00 1833.99 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1865.39 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 807 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 769 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1894.22 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 817 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 780 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1743.18 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/9/21 5:00 1883.86 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1954.34 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1916.09 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 824 3 89%312 238 238 0 0 0 0 0 0 0 0 0 0 0 788 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1705.72 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1807.94 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1756.02 6.0 4 63%227 181 181 181 0 0 0 0 0 0 0 0 0 0 769 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1802.71 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 746 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1711.47 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 714 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1820.51 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 753 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1838.90 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1824.53 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1563.20 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 702 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 662 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1708.34 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 753 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1689.30 6.0 4 60%220 175 175 175 0 0 0 0 0 0 0 0 0 0 746 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1683.78 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1565.48 6.0 4 56%205 166 166 166 0 0 0 0 0 0 0 0 0 0 703 3 72%259 202 202 0 0 0 0 0 0 0 0 0 0 0 663 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1650.88 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1621.23 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%268 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1720.11 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 757 3 80%282 217 217 0 0 0 0 0 0 0 0 0 0 0 717 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1569.14 6.0 4 56%206 166 166 166 0 0 0 0 0 0 0 0 0 0 704 3 73%260 202 202 0 0 0 0 0 0 0 0 0 0 0 664 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1609.10 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1636.61 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1653.16 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%272 211 211 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1494.50 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 678 2 99%345 263 0 0 0 0 0 0 0 0 0 0 0 0 608 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1592.46 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 712 3 74%263 205 205 0 0 0 0 0 0 0 0 0 0 0 672 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1583.97 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1637.12 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1512.03 6.0 4 54%199 162 162 162 0 0 0 0 0 0 0 0 0 0 684 3 70%251 197 197 0 0 0 0 0 0 0 0 0 0 0 645 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1629.30 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 725 3 75%269 208 208 0 0 0 0 0 0 0 0 0 0 0 685 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1627.14 6.0 4 58%212 171 171 171 0 0 0 0 0 0 0 0 0 0 724 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 684 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1633.83 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%269 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1466.80 6.0 4 52%194 158 158 158 0 0 0 0 0 0 0 0 0 0 668 2 97%339 259 0 0 0 0 0 0 0 0 0 0 0 0 598 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1587.45 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 710 3 73%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1597.00 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 714 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 674 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1623.04 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 723 3 75%268 208 208 0 0 0 0 0 0 0 0 0 0 0 683 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1459.08 6.0 4 52%193 157 157 157 0 0 0 0 0 0 0 0 0 0 665 2 97%337 257 0 0 0 0 0 0 0 0 0 0 0 0 595 4 52%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1595.33 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1683.22 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 744 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 704 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1777.00 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1776.44 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1935.42 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 831 3 90%314 240 240 0 0 0 0 0 0 0 0 0 0 0 795 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1939.59 6.0 4 69%248 195 195 195 0 0 0 0 0 0 0 0 0 0 832 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 797 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1998.86 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 915 3 93%324 247 247 0 0 0 0 0 0 0 0 0 0 0 819 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1823.96 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1836.01 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 797 3 85%299 230 230 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1905.73 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 821 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 784 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1893.22 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1714.41 6.0 4 61%223 177 177 177 0 0 0 0 0 0 0 0 0 0 755 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1722.24 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 718 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1783.15 6.0 4 63%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1871.44 6.0 4 67%241 189 189 189 0 0 0 0 0 0 0 0 0 0 809 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1745.36 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 726 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1908.94 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 785 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1878.99 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 811 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 774 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1959.90 6.0 5 52%194 159 159 159 230 0 0 0 0 0 0 0 0 0 901 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 804 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1771.27 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1823.65 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 792 3 84%298 228 228 0 0 0 0 0 0 0 0 0 0 0 754 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1739.29 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 763 3 81%285 219 219 0 0 0 0 0 0 0 0 0 0 0 724 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1692.00 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 215 215 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1525.64 6.0 4 54%200 163 163 163 0 0 0 0 0 0 0 0 0 0 689 3 71%253 198 198 0 0 0 0 0 0 0 0 0 0 0 649 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1636.45 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1687.65 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 746 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1651.73 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1558.47 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 700 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 661 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1690.95 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1651.49 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1684.78 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1522.74 6.0 4 54%200 162 162 162 0 0 0 0 0 0 0 0 0 0 688 3 70%253 198 198 0 0 0 0 0 0 0 0 0 0 0 648 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1637.45 6.0 4 58%214 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1687.79 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 746 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 706 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2/1/21 23:00 2/2/21 11:00 2/2/21 17:00 2/2/21 23:00 2/3/21 11:00 2/3/21 17:00 2/3/21 23:00 2/4/21 11:00 2/4/21 17:00 2/4/21 23:00 2/5/21 11:00 2/5/21 17:00 2/5/21 23:00 2/6/21 11:00 2/6/21 17:00 2/6/21 23:00 2/7/21 11:00 2/7/21 17:00 2/7/21 23:00 2/8/21 11:00 2/8/21 17:00 2/8/21 23:00 2/9/21 11:00 2/9/21 17:00 2/9/21 23:00 2/10/21 5:00 2/10/21 11:0 2/10/21 17:0 2/10/21 23:0 2/11/21 5:00 2/11/21 11:0 2/11/21 17:0 2/11/21 23:0 2/12/21 5:00 2/12/21 11:0 2/12/21 17:0 2/12/21 23:0 2/13/21 5:00 2/13/21 11:0 2/13/21 17:0 2/13/21 23:0 2/14/21 5:00 2/14/21 11:0 2/14/21 17:0 2/14/21 23:0 2/15/21 5:00 2/15/21 11:0 2/15/21 17:0 2/15/21 23:0 2/16/21 5:00 2/16/21 11:0 2/16/21 17:0 2/16/21 23:0 2/17/21 5:00 2/17/21 11:0 2/17/21 17:0 2/17/21 23:0 2/18/21 5:00 2/18/21 11:0 2/18/21 17:0 2/18/21 23:0 2/19/21 5:00 2/19/21 11:0 2/19/21 17:0 2/19/21 23:0 2/20/21 5:00 2/20/21 11:0 2/20/21 17:0 2/20/21 23:0 2/21/21 5:00 2/21/21 11:0 2/21/21 17:0 2/21/21 23:0 2/22/21 5:00 2/22/21 11:0 2/22/21 17:0 2/22/21 23:0 2/23/21 5:00 2/23/21 11:0 2/23/21 17:0 2/23/21 23:0 2/24/21 5:00 2/24/21 11:0 2/24/21 17:0 2/24/21 23:0 2/25/21 5:00 2/25/21 11:0 2/25/21 17:0 2/25/21 23:0 2/26/21 5:00 2/26/21 11:0 NEA BESS Scenario Analysis Data Analysis 38 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 73%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.0 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.3 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.5 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 75%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.2 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.9 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 73%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 2 97%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 52%5.1 4.5 4.5 4.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.8 2 97%9.1 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 15.8 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.5 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.9 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 70%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.3 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 70%6.7 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 NEA BESS Scenario Analysis Data Analysis 39 1639.13 6.0 4 58%214 172 172 172 0 0 0 0 0 0 0 0 0 0 729 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 689 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1477.86 6.0 4 53%195 159 159 159 0 0 0 0 0 0 0 0 0 0 672 2 98%341 261 0 0 0 0 0 0 0 0 0 0 0 0 602 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1549.03 6.0 4 55%203 165 165 165 0 0 0 0 0 0 0 0 0 0 697 3 72%257 200 200 0 0 0 0 0 0 0 0 0 0 0 657 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1679.28 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1757.05 6.0 4 63%227 181 181 181 0 0 0 0 0 0 0 0 0 0 770 3 81%288 221 221 0 0 0 0 0 0 0 0 0 0 0 730 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1657.35 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 735 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 695 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1734.01 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 762 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 722 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1691.63 6.0 4 60%220 176 176 176 0 0 0 0 0 0 0 0 0 0 747 3 78%278 214 214 0 0 0 0 0 0 0 0 0 0 0 707 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1808.71 6.0 4 64%233 185 185 185 0 0 0 0 0 0 0 0 0 0 787 3 84%295 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1678.36 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 742 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 702 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/1/21 5:00 1775.72 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1773.55 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1743.10 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 765 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 725 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1555.76 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/2/21 5:00 1653.32 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%272 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1589.59 6.0 4 57%208 168 168 168 0 0 0 0 0 0 0 0 0 0 711 3 74%263 204 204 0 0 0 0 0 0 0 0 0 0 0 671 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1635.04 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 727 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 687 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1553.56 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 659 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/3/21 5:00 1784.53 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1856.00 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%302 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1875.08 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1789.97 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 742 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/4/21 5:00 1952.46 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1854.99 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 232 232 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1908.79 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 785 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1636.38 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/5/21 5:00 1747.75 6.0 4 62%226 180 180 180 0 0 0 0 0 0 0 0 0 0 766 3 81%286 220 220 0 0 0 0 0 0 0 0 0 0 0 727 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1655.45 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 734 3 77%273 211 211 0 0 0 0 0 0 0 0 0 0 0 694 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1679.32 6.0 4 60%218 175 175 175 0 0 0 0 0 0 0 0 0 0 743 3 78%276 213 213 0 0 0 0 0 0 0 0 0 0 0 703 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1651.09 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/6/21 5:00 1768.21 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 734 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1709.85 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 753 3 79%281 216 216 0 0 0 0 0 0 0 0 0 0 0 713 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1713.14 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 754 3 79%281 217 217 0 0 0 0 0 0 0 0 0 0 0 715 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1555.81 6.0 4 55%204 165 165 165 0 0 0 0 0 0 0 0 0 0 699 3 72%258 201 201 0 0 0 0 0 0 0 0 0 0 0 660 4 55%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/7/21 5:00 1583.74 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1595.05 6.0 4 57%209 168 168 168 0 0 0 0 0 0 0 0 0 0 713 3 74%264 205 205 0 0 0 0 0 0 0 0 0 0 0 673 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1608.51 6.0 4 57%210 169 169 169 0 0 0 0 0 0 0 0 0 0 718 3 74%266 206 206 0 0 0 0 0 0 0 0 0 0 0 678 4 57%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1528.19 6.0 4 54%201 163 163 163 0 0 0 0 0 0 0 0 0 0 690 3 71%254 198 198 0 0 0 0 0 0 0 0 0 0 0 650 4 54%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/8/21 5:00 1687.07 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1766.48 6.0 4 63%229 181 181 181 0 0 0 0 0 0 0 0 0 0 773 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1715.95 6.0 4 61%223 178 178 178 0 0 0 0 0 0 0 0 0 0 755 3 79%282 217 217 0 0 0 0 0 0 0 0 0 0 0 716 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1497.45 6.0 4 53%197 160 160 160 0 0 0 0 0 0 0 0 0 0 679 2 99%346 264 0 0 0 0 0 0 0 0 0 0 0 0 609 4 53%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/9/21 5:00 1619.99 6.0 4 58%212 170 170 170 0 0 0 0 0 0 0 0 0 0 722 3 75%267 207 207 0 0 0 0 0 0 0 0 0 0 0 682 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1586.57 6.0 4 56%208 168 168 168 0 0 0 0 0 0 0 0 0 0 710 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 670 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1661.78 6.0 4 59%216 173 173 173 0 0 0 0 0 0 0 0 0 0 737 3 77%274 211 211 0 0 0 0 0 0 0 0 0 0 0 696 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1583.66 6.0 4 56%207 167 167 167 0 0 0 0 0 0 0 0 0 0 709 3 73%262 204 204 0 0 0 0 0 0 0 0 0 0 0 669 4 56%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1685.73 6.0 4 60%219 175 175 175 0 0 0 0 0 0 0 0 0 0 745 3 78%277 214 214 0 0 0 0 0 0 0 0 0 0 0 705 4 60%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1636.08 6.0 4 58%213 171 171 171 0 0 0 0 0 0 0 0 0 0 728 3 76%270 209 209 0 0 0 0 0 0 0 0 0 0 0 688 4 58%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1750.43 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 767 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1700.29 6.0 4 61%221 176 176 176 0 0 0 0 0 0 0 0 0 0 750 3 79%279 215 215 0 0 0 0 0 0 0 0 0 0 0 710 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1870.58 6.0 4 67%241 189 189 189 0 0 0 0 0 0 0 0 0 0 809 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1898.32 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1917.58 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 825 3 89%312 238 238 0 0 0 0 0 0 0 0 0 0 0 788 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1860.98 6.0 4 66%239 189 189 189 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1952.34 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 801 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1858.13 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1870.81 6.0 4 67%241 189 189 189 0 0 0 0 0 0 0 0 0 0 809 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1850.89 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 802 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 764 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1923.41 6.0 4 68%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1818.94 6.0 4 65%235 185 185 185 0 0 0 0 0 0 0 0 0 0 791 3 84%297 228 228 0 0 0 0 0 0 0 0 0 0 0 752 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1858.81 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1706.54 6.0 4 61%222 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1776.39 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%291 223 223 0 0 0 0 0 0 0 0 0 0 0 737 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1764.70 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1732.14 6.0 4 62%225 179 179 179 0 0 0 0 0 0 0 0 0 0 761 3 80%284 219 219 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1651.45 6.0 4 59%215 173 173 173 0 0 0 0 0 0 0 0 0 0 733 3 76%272 210 210 0 0 0 0 0 0 0 0 0 0 0 693 4 59%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1781.49 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1705.22 6.0 4 61%221 177 177 177 0 0 0 0 0 0 0 0 0 0 752 3 79%280 216 216 0 0 0 0 0 0 0 0 0 0 0 712 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1816.29 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%297 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1764.93 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 772 3 82%289 222 222 0 0 0 0 0 0 0 0 0 0 0 733 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1940.19 6.0 4 69%248 195 195 195 0 0 0 0 0 0 0 0 0 0 832 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 797 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1807.09 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 787 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1803.68 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 83%295 226 226 0 0 0 0 0 0 0 0 0 0 0 747 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1762.52 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 732 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1964.82 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 903 3 91%319 244 244 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1994.30 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1955.29 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 899 3 91%317 243 243 0 0 0 0 0 0 0 0 0 0 0 803 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1868.11 6.0 4 67%240 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2120.94 6.0 5 57%209 168 168 168 244 0 0 0 0 0 0 0 0 0 957 3 98%343 262 262 0 0 0 0 0 0 0 0 0 0 0 866 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1982.67 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 813 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1983.05 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 813 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1997.00 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 914 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 818 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2197.79 6.0 5 59%215 173 173 173 251 0 0 0 0 0 0 0 0 0 984 4 78%278 214 214 214 0 0 0 0 0 0 0 0 0 0 921 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2090.80 6.0 5 56%206 166 166 166 242 0 0 0 0 0 0 0 0 0 947 3 97%338 258 258 0 0 0 0 0 0 0 0 0 0 0 854 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2027.46 6.0 5 54%200 163 163 163 236 0 0 0 0 0 0 0 0 0 925 3 94%328 251 251 0 0 0 0 0 0 0 0 0 0 0 830 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1897.64 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1963.74 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 902 3 91%319 243 243 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1943.49 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%316 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1859.15 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1760.97 6.0 4 63%228 181 181 181 0 0 0 0 0 0 0 0 0 0 771 3 82%288 222 222 0 0 0 0 0 0 0 0 0 0 0 731 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1858.51 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1786.78 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 780 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 741 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1780.69 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1724.60 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 758 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1914.11 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 787 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1827.48 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1879.23 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 811 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 774 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1884.61 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2100.38 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%340 259 259 0 0 0 0 0 0 0 0 0 0 0 858 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2/26/21 17:0 2/26/21 23:0 2/27/21 5:00 2/27/21 11:0 2/27/21 17:0 2/27/21 23:0 2/28/21 5:00 2/28/21 11:0 2/28/21 17:0 2/28/21 23:0 3/1/21 11:00 3/1/21 17:00 3/1/21 23:00 3/2/21 11:00 3/2/21 17:00 3/2/21 23:00 3/3/21 11:00 3/3/21 17:00 3/3/21 23:00 3/4/21 11:00 3/4/21 17:00 3/4/21 23:00 3/5/21 11:00 3/5/21 17:00 3/5/21 23:00 3/6/21 11:00 3/6/21 17:00 3/6/21 23:00 3/7/21 11:00 3/7/21 17:00 3/7/21 23:00 3/8/21 11:00 3/8/21 17:00 3/8/21 23:00 3/9/21 11:00 3/9/21 17:00 3/9/21 23:00 3/10/21 5:00 3/10/21 11:0 3/10/21 17:0 3/10/21 23:0 3/11/21 5:00 3/11/21 11:0 3/11/21 17:0 3/11/21 23:0 3/12/21 5:00 3/12/21 11:0 3/12/21 17:0 3/12/21 23:0 3/13/21 5:00 3/13/21 11:0 3/13/21 17:0 3/13/21 23:0 3/14/21 6:00 3/14/21 12:0 3/14/21 18:0 3/15/21 0:00 3/15/21 6:00 3/15/21 12:0 3/15/21 18:0 3/16/21 0:00 3/16/21 6:00 3/16/21 12:0 3/16/21 18:0 3/17/21 0:00 3/17/21 6:00 3/17/21 12:0 3/17/21 18:0 3/18/21 0:00 3/18/21 6:00 3/18/21 12:0 3/18/21 18:0 3/19/21 0:00 3/19/21 6:00 3/19/21 12:0 3/19/21 18:0 3/20/21 0:00 3/20/21 6:00 3/20/21 12:0 3/20/21 18:0 3/21/21 0:00 3/21/21 6:00 3/21/21 12:0 3/21/21 18:0 3/22/21 0:00 3/22/21 6:00 3/22/21 12:0 3/22/21 18:0 3/23/21 0:00 3/23/21 6:00 NEA BESS Scenario Analysis Data Analysis 40 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 2 98%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.2 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 2 98%9.2 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 72%6.8 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.9 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 81%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 78%7.4 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 72%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 55%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 72%6.9 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.8 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 74%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.2 3 74%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 57%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 74%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.3 3 71%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 54%5.4 4.7 4.7 4.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.4 3 71%6.8 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 17.6 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 2 99%6 6 0 0 0 0 0 0 0 0 0 0 0 0 12 4 53%5.3 4.6 4.6 4.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 2 99%9.4 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.2 3 75%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.6 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 75%7.1 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.4 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.6 5.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 77%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 77%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.7 3 73%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 56%5.5 4.8 4.8 4.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 73%7.0 5.5 5.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.1 3 78%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 60%5.8 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 78%7.4 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.9 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 58%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 76%7.2 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.5 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.0 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 76%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 59%5.7 4.9 4.9 4.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 76%7.3 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 18.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 79%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%5.9 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 79%7.5 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.9 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.7 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.4 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.2 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 NEA BESS Scenario Analysis Data Analysis 41 1959.25 6.0 5 52%194 159 159 159 230 0 0 0 0 0 0 0 0 0 901 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 804 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1932.48 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 830 3 89%314 240 240 0 0 0 0 0 0 0 0 0 0 0 794 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1855.01 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 232 232 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2006.80 6.0 5 54%199 161 161 161 234 0 0 0 0 0 0 0 0 0 917 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 822 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1987.68 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1861.44 6.0 4 66%239 189 189 189 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1774.45 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1961.19 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 901 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 805 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1878.98 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 811 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 774 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1785.05 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1752.21 6.0 4 62%227 180 180 180 0 0 0 0 0 0 0 0 0 0 768 3 81%287 221 221 0 0 0 0 0 0 0 0 0 0 0 728 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1910.08 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 238 238 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1902.60 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 819 3 88%309 237 237 0 0 0 0 0 0 0 0 0 0 0 783 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1815.57 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1781.21 6.0 4 63%230 183 183 183 0 0 0 0 0 0 0 0 0 0 778 3 82%291 224 224 0 0 0 0 0 0 0 0 0 0 0 739 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1914.16 6.0 4 68%246 193 193 193 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 787 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1847.19 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 801 3 86%301 231 231 0 0 0 0 0 0 0 0 0 0 0 763 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1795.61 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 783 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 744 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1770.98 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 774 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 735 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1892.50 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 779 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1859.69 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 805 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 767 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1825.49 6.0 4 65%235 186 186 186 0 0 0 0 0 0 0 0 0 0 793 3 85%298 228 228 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1730.39 6.0 4 62%224 179 179 179 0 0 0 0 0 0 0 0 0 0 760 3 80%284 218 218 0 0 0 0 0 0 0 0 0 0 0 721 4 62%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1897.25 6.0 4 68%244 191 191 191 0 0 0 0 0 0 0 0 0 0 818 3 88%309 236 236 0 0 0 0 0 0 0 0 0 0 0 781 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1870.47 6.0 4 67%241 189 189 189 0 0 0 0 0 0 0 0 0 0 808 3 87%305 233 233 0 0 0 0 0 0 0 0 0 0 0 771 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1799.32 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 784 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 745 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1725.41 6.0 4 61%224 178 178 178 0 0 0 0 0 0 0 0 0 0 759 3 80%283 218 218 0 0 0 0 0 0 0 0 0 0 0 719 4 61%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1935.24 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 831 3 90%314 240 240 0 0 0 0 0 0 0 0 0 0 0 795 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1834.58 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1805.71 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 786 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1797.28 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 783 3 83%294 225 225 0 0 0 0 0 0 0 0 0 0 0 744 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2019.66 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 922 3 93%327 250 250 0 0 0 0 0 0 0 0 0 0 0 827 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1911.90 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 823 3 89%311 238 238 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1854.99 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 803 3 86%302 232 232 0 0 0 0 0 0 0 0 0 0 0 765 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/1/21 0:00 1911.39 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 238 238 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/1/21 6:00 2150.25 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 968 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 877 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2060.45 6.0 5 55%203 165 165 165 239 0 0 0 0 0 0 0 0 0 936 3 95%333 255 255 0 0 0 0 0 0 0 0 0 0 0 842 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2000.03 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 915 3 93%324 248 248 0 0 0 0 0 0 0 0 0 0 0 819 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/2/21 0:00 1959.34 6.0 5 52%194 159 159 159 230 0 0 0 0 0 0 0 0 0 901 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 804 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/2/21 6:00 2201.61 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 986 4 78%278 215 215 215 0 0 0 0 0 0 0 0 0 0 922 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2143.08 6.0 5 57%211 169 169 169 246 0 0 0 0 0 0 0 0 0 965 3 99%346 264 264 0 0 0 0 0 0 0 0 0 0 0 874 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1941.97 6.0 4 69%249 195 195 195 0 0 0 0 0 0 0 0 0 0 833 3 90%315 241 241 0 0 0 0 0 0 0 0 0 0 0 798 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/3/21 0:00 1835.05 6.0 4 65%236 187 187 187 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 758 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/3/21 6:00 1953.39 6.0 5 52%194 158 158 158 230 0 0 0 0 0 0 0 0 0 898 3 90%317 242 242 0 0 0 0 0 0 0 0 0 0 0 802 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1986.64 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 910 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 814 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1831.92 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 795 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/4/21 0:00 1794.35 6.0 4 64%232 184 184 184 0 0 0 0 0 0 0 0 0 0 782 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 743 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/4/21 6:00 1893.92 6.0 4 67%243 191 191 191 0 0 0 0 0 0 0 0 0 0 816 3 88%308 236 236 0 0 0 0 0 0 0 0 0 0 0 780 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1843.30 6.0 4 66%237 187 187 187 0 0 0 0 0 0 0 0 0 0 799 3 85%301 230 230 0 0 0 0 0 0 0 0 0 0 0 761 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1832.96 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 796 3 85%299 229 229 0 0 0 0 0 0 0 0 0 0 0 757 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/5/21 0:00 1827.01 6.0 4 65%236 186 186 186 0 0 0 0 0 0 0 0 0 0 794 3 85%298 229 229 0 0 0 0 0 0 0 0 0 0 0 755 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/5/21 6:00 2038.17 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 928 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 834 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1972.07 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 905 3 91%320 244 244 0 0 0 0 0 0 0 0 0 0 0 809 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1964.48 6.0 5 53%195 159 159 159 231 0 0 0 0 0 0 0 0 0 902 3 91%319 244 244 0 0 0 0 0 0 0 0 0 0 0 806 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/6/21 0:00 1906.59 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 821 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 784 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/6/21 6:00 2117.78 6.0 5 57%208 168 168 168 244 0 0 0 0 0 0 0 0 0 956 3 98%342 261 261 0 0 0 0 0 0 0 0 0 0 0 865 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1994.37 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 913 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1876.10 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%305 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/7/21 0:00 1863.41 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%304 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/7/21 6:00 2085.40 6.0 5 56%206 166 166 166 241 0 0 0 0 0 0 0 0 0 945 3 97%337 257 257 0 0 0 0 0 0 0 0 0 0 0 852 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2149.92 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 968 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 877 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1988.83 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%323 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/8/21 0:00 1909.66 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 237 237 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 4/8/21 6:00 2218.71 6.0 5 59%217 174 174 174 253 0 0 0 0 0 0 0 0 0 992 4 79%280 216 216 216 0 0 0 0 0 0 0 0 0 0 928 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2191.28 6.0 5 59%215 172 172 172 250 0 0 0 0 0 0 0 0 0 982 4 78%277 214 214 214 0 0 0 0 0 0 0 0 0 0 918 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2151.86 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 968 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 878 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/9/21 0:00 2150.48 6.0 5 58%211 170 170 170 247 0 0 0 0 0 0 0 0 0 968 3 100%347 265 265 0 0 0 0 0 0 0 0 0 0 0 877 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 4/9/21 6:00 2367.00 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,043 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 981 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2235.28 6.0 5 60%219 175 175 175 254 0 0 0 0 0 0 0 0 0 997 4 80%282 217 217 217 0 0 0 0 0 0 0 0 0 0 934 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2104.59 6.0 5 56%207 167 167 167 243 0 0 0 0 0 0 0 0 0 952 3 97%340 260 260 0 0 0 0 0 0 0 0 0 0 0 859 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1986.88 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 910 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 814 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2111.71 6.0 5 57%208 168 168 168 243 0 0 0 0 0 0 0 0 0 954 3 98%341 260 260 0 0 0 0 0 0 0 0 0 0 0 862 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2037.57 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 928 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 834 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1867.06 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 807 3 86%304 233 233 0 0 0 0 0 0 0 0 0 0 0 770 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1815.86 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1991.56 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 912 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 816 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2050.57 6.0 5 55%202 164 164 164 238 0 0 0 0 0 0 0 0 0 933 3 95%332 253 253 0 0 0 0 0 0 0 0 0 0 0 839 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1933.26 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 830 3 89%314 240 240 0 0 0 0 0 0 0 0 0 0 0 794 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1809.92 6.0 4 64%234 185 185 185 0 0 0 0 0 0 0 0 0 0 788 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 749 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1995.70 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 913 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 818 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1990.05 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%323 246 246 0 0 0 0 0 0 0 0 0 0 0 816 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1911.53 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 822 3 88%311 238 238 0 0 0 0 0 0 0 0 0 0 0 786 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1839.37 6.0 4 65%237 187 187 187 0 0 0 0 0 0 0 0 0 0 798 3 85%300 230 230 0 0 0 0 0 0 0 0 0 0 0 760 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2032.62 6.0 5 54%201 163 163 163 237 0 0 0 0 0 0 0 0 0 926 3 94%329 251 251 0 0 0 0 0 0 0 0 0 0 0 832 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1992.44 6.0 5 53%197 161 161 161 233 0 0 0 0 0 0 0 0 0 912 3 92%323 247 247 0 0 0 0 0 0 0 0 0 0 0 817 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1907.32 6.0 4 68%245 192 192 192 0 0 0 0 0 0 0 0 0 0 821 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 785 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1800.90 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 746 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2003.97 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 916 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1958.85 6.0 5 52%194 159 159 159 230 0 0 0 0 0 0 0 0 0 900 3 91%318 243 243 0 0 0 0 0 0 0 0 0 0 0 804 5 52%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1884.06 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1774.89 6.0 4 63%230 182 182 182 0 0 0 0 0 0 0 0 0 0 776 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1972.52 6.0 5 53%196 159 159 159 232 0 0 0 0 0 0 0 0 0 905 3 91%320 244 244 0 0 0 0 0 0 0 0 0 0 0 809 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1978.85 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 907 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 811 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1815.65 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 790 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1790.82 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 781 3 83%293 225 225 0 0 0 0 0 0 0 0 0 0 0 742 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2022.21 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 923 3 94%328 250 250 0 0 0 0 0 0 0 0 0 0 0 828 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2004.47 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 917 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1784.62 6.0 4 64%231 183 183 183 0 0 0 0 0 0 0 0 0 0 779 3 83%292 224 224 0 0 0 0 0 0 0 0 0 0 0 740 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1806.46 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 787 3 84%295 226 226 0 0 0 0 0 0 0 0 0 0 0 748 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 3/23/21 12:0 3/23/21 18:0 3/24/21 0:00 3/24/21 6:00 3/24/21 12:0 3/24/21 18:0 3/25/21 0:00 3/25/21 6:00 3/25/21 12:0 3/25/21 18:0 3/26/21 0:00 3/26/21 6:00 3/26/21 12:0 3/26/21 18:0 3/27/21 0:00 3/27/21 6:00 3/27/21 12:0 3/27/21 18:0 3/28/21 0:00 3/28/21 6:00 3/28/21 12:0 3/28/21 18:0 3/29/21 0:00 3/29/21 6:00 3/29/21 12:0 3/29/21 18:0 3/30/21 0:00 3/30/21 6:00 3/30/21 12:0 3/30/21 18:0 3/31/21 0:00 3/31/21 6:00 3/31/21 12:0 3/31/21 18:0 4/1/21 12:00 4/1/21 18:00 4/2/21 12:00 4/2/21 18:00 4/3/21 12:00 4/3/21 18:00 4/4/21 12:00 4/4/21 18:00 4/5/21 12:00 4/5/21 18:00 4/6/21 12:00 4/6/21 18:00 4/7/21 12:00 4/7/21 18:00 4/8/21 12:00 4/8/21 18:00 4/9/21 12:00 4/9/21 18:00 4/10/21 0:00 4/10/21 6:00 4/10/21 12:0 4/10/21 18:0 4/11/21 0:00 4/11/21 6:00 4/11/21 12:0 4/11/21 18:0 4/12/21 0:00 4/12/21 6:00 4/12/21 12:0 4/12/21 18:0 4/13/21 0:00 4/13/21 6:00 4/13/21 12:0 4/13/21 18:0 4/14/21 0:00 4/14/21 6:00 4/14/21 12:0 4/14/21 18:0 4/15/21 0:00 4/15/21 6:00 4/15/21 12:0 4/15/21 18:0 4/16/21 0:00 4/16/21 6:00 4/16/21 12:0 4/16/21 18:0 4/17/21 0:00 NEA BESS Scenario Analysis Data Analysis 42 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 81%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 81%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.5 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 82%7.7 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.6 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 62%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 80%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 61%6.0 5.0 5.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 80%7.6 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.3 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 89%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 93%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.4 5.4 5.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 90%8.5 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 3 90%8.5 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 3 88%8.3 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.1 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.3 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.6 3 97%9.1 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.1 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.7 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.9 4 80%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 98%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.9 3 98%9.2 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.8 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 95%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 3 95%9.0 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.5 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 85%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 85%8.0 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.2 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.4 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.9 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 52%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.3 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 94%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 83%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.8 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 NEA BESS Scenario Analysis Data Analysis 43 1924.13 6.0 4 69%247 193 193 193 0 0 0 0 0 0 0 0 0 0 827 3 89%313 239 239 0 0 0 0 0 0 0 0 0 0 0 791 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2069.94 6.0 5 55%204 165 165 165 240 0 0 0 0 0 0 0 0 0 940 3 96%335 256 256 0 0 0 0 0 0 0 0 0 0 0 846 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1862.32 6.0 4 66%240 189 189 189 0 0 0 0 0 0 0 0 0 0 806 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 768 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1773.93 6.0 4 63%229 182 182 182 0 0 0 0 0 0 0 0 0 0 775 3 82%290 223 223 0 0 0 0 0 0 0 0 0 0 0 736 4 63%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1973.94 6.0 5 53%196 159 159 159 232 0 0 0 0 0 0 0 0 0 906 3 91%320 245 245 0 0 0 0 0 0 0 0 0 0 0 810 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2007.60 6.0 5 54%199 161 161 161 235 0 0 0 0 0 0 0 0 0 918 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 822 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1857.33 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1815.05 6.0 4 65%234 185 185 185 0 0 0 0 0 0 0 0 0 0 789 3 84%296 227 227 0 0 0 0 0 0 0 0 0 0 0 751 4 65%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2095.60 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 949 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 856 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2167.34 6.0 5 58%213 171 171 171 248 0 0 0 0 0 0 0 0 0 974 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 910 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1857.64 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1801.50 6.0 4 64%233 184 184 184 0 0 0 0 0 0 0 0 0 0 785 3 83%294 226 226 0 0 0 0 0 0 0 0 0 0 0 746 4 64%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2095.57 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 949 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 856 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1987.75 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 911 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 815 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1846.95 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 800 3 86%301 231 231 0 0 0 0 0 0 0 0 0 0 0 762 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 1852.19 6.0 4 66%238 188 188 188 0 0 0 0 0 0 0 0 0 0 802 3 86%302 231 231 0 0 0 0 0 0 0 0 0 0 0 764 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2212.52 6.0 5 59%217 174 174 174 252 0 0 0 0 0 0 0 0 0 989 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 926 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2251.96 6.0 5 60%220 176 176 176 255 0 0 0 0 0 0 0 0 0 1,003 4 80%284 219 219 219 0 0 0 0 0 0 0 0 0 0 940 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2040.09 6.0 5 55%202 163 163 163 237 0 0 0 0 0 0 0 0 0 929 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 835 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1857.24 6.0 4 66%239 188 188 188 0 0 0 0 0 0 0 0 0 0 804 3 86%303 232 232 0 0 0 0 0 0 0 0 0 0 0 766 4 66%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2220.31 6.0 5 59%217 174 174 174 253 0 0 0 0 0 0 0 0 0 992 4 79%280 216 216 216 0 0 0 0 0 0 0 0 0 0 929 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2206.10 6.0 5 59%216 173 173 173 251 0 0 0 0 0 0 0 0 0 987 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 924 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1979.55 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 908 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 812 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1884.72 6.0 4 67%242 190 190 190 0 0 0 0 0 0 0 0 0 0 813 3 87%307 235 235 0 0 0 0 0 0 0 0 0 0 0 776 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2228.78 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 995 4 79%281 217 217 217 0 0 0 0 0 0 0 0 0 0 932 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2093.85 6.0 5 56%206 167 167 167 242 0 0 0 0 0 0 0 0 0 948 3 97%339 258 258 0 0 0 0 0 0 0 0 0 0 0 855 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1984.49 6.0 5 53%197 160 160 160 233 0 0 0 0 0 0 0 0 0 909 3 92%322 246 246 0 0 0 0 0 0 0 0 0 0 0 814 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1903.75 6.0 4 68%244 192 192 192 0 0 0 0 0 0 0 0 0 0 820 3 88%310 237 237 0 0 0 0 0 0 0 0 0 0 0 783 4 68%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2226.73 6.0 5 60%218 174 174 174 253 0 0 0 0 0 0 0 0 0 994 4 79%281 217 217 217 0 0 0 0 0 0 0 0 0 0 931 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2211.37 6.0 5 59%217 173 173 173 252 0 0 0 0 0 0 0 0 0 989 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 925 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1981.06 6.0 5 53%196 160 160 160 232 0 0 0 0 0 0 0 0 0 908 3 92%321 245 245 0 0 0 0 0 0 0 0 0 0 0 812 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1876.40 6.0 4 67%241 190 190 190 0 0 0 0 0 0 0 0 0 0 810 3 87%306 234 234 0 0 0 0 0 0 0 0 0 0 0 773 4 67%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2099.04 6.0 5 56%207 167 167 167 242 0 0 0 0 0 0 0 0 0 950 3 97%339 259 259 0 0 0 0 0 0 0 0 0 0 0 857 5 56%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2138.80 6.0 5 57%210 169 169 169 246 0 0 0 0 0 0 0 0 0 964 3 99%345 264 264 0 0 0 0 0 0 0 0 0 0 0 873 5 57%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2024.28 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 924 3 94%328 250 250 0 0 0 0 0 0 0 0 0 0 0 829 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1934.99 6.0 4 69%248 194 194 194 0 0 0 0 0 0 0 0 0 0 830 3 90%314 240 240 0 0 0 0 0 0 0 0 0 0 0 795 4 69%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 2282.92 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,014 4 81%287 221 221 221 0 0 0 0 0 0 0 0 0 0 951 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2366.96 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,043 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 981 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2158.68 6.0 5 58%212 170 170 170 247 0 0 0 0 0 0 0 0 0 971 3 100%348 266 266 0 0 0 0 0 0 0 0 0 0 0 880 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2064.90 6.0 5 55%204 165 165 165 239 0 0 0 0 0 0 0 0 0 938 3 96%334 255 255 0 0 0 0 0 0 0 0 0 0 0 844 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2444.09 6.0 5 65%237 187 187 187 271 0 0 0 0 0 0 0 0 0 1,069 4 87%306 234 234 234 0 0 0 0 0 0 0 0 0 0 1,009 5 65%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2674.19 6.0 5 72%257 200 200 200 290 0 0 0 0 0 0 0 0 0 1,147 4 95%333 254 254 254 0 0 0 0 0 0 0 0 0 0 1,095 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2018.78 6.0 5 54%200 162 162 162 236 0 0 0 0 0 0 0 0 0 922 3 93%327 250 250 0 0 0 0 0 0 0 0 0 0 0 827 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 1996.82 6.0 5 53%198 161 161 161 234 0 0 0 0 0 0 0 0 0 914 3 92%324 247 247 0 0 0 0 0 0 0 0 0 0 0 818 5 53%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2400.64 6.0 5 64%233 184 184 184 268 0 0 0 0 0 0 0 0 0 1,054 4 85%301 231 231 231 0 0 0 0 0 0 0 0 0 0 993 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2269.25 6.0 5 61%222 177 177 177 257 0 0 0 0 0 0 0 0 0 1,009 4 81%286 220 220 220 0 0 0 0 0 0 0 0 0 0 946 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2038.86 6.0 5 55%201 163 163 163 237 0 0 0 0 0 0 0 0 0 929 3 94%330 252 252 0 0 0 0 0 0 0 0 0 0 0 834 5 55%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2005.33 6.0 5 54%198 161 161 161 234 0 0 0 0 0 0 0 0 0 917 3 93%325 248 248 0 0 0 0 0 0 0 0 0 0 0 821 5 54%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2363.09 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,041 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 979 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2676.51 6.0 5 72%257 200 200 200 290 0 0 0 0 0 0 0 0 0 1,148 4 95%333 254 254 254 0 0 0 0 0 0 0 0 0 0 1,096 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2250.81 6.0 5 60%220 176 176 176 255 0 0 0 0 0 0 0 0 0 1,003 4 80%284 219 219 219 0 0 0 0 0 0 0 0 0 0 939 5 60%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2209.85 6.0 5 59%216 173 173 173 252 0 0 0 0 0 0 0 0 0 988 4 79%279 215 215 215 0 0 0 0 0 0 0 0 0 0 925 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2981.13 6.0 6 65%235 186 186 186 269 235 0 0 0 0 0 0 0 0 1,296 5 80%283 218 218 218 315 0 0 0 0 0 0 0 0 0 1,252 6 65%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2616.02 6.0 5 70%252 197 197 197 285 0 0 0 0 0 0 0 0 0 1,127 4 93%326 249 249 249 0 0 0 0 0 0 0 0 0 0 1,073 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2299.66 6.0 5 62%224 179 179 179 259 0 0 0 0 0 0 0 0 0 1,019 4 82%289 222 222 222 0 0 0 0 0 0 0 0 0 0 957 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/1/21 0:00 2302.77 6.0 5 62%225 179 179 179 260 0 0 0 0 0 0 0 0 0 1,021 4 82%290 223 223 223 0 0 0 0 0 0 0 0 0 0 958 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/1/21 6:00 2620.58 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2678.89 6.0 5 72%257 200 200 200 291 0 0 0 0 0 0 0 0 0 1,148 4 95%333 254 254 254 0 0 0 0 0 0 0 0 0 0 1,097 5 72%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2501.75 6.0 5 67%242 190 190 190 276 0 0 0 0 0 0 0 0 0 1,088 4 89%313 239 239 239 0 0 0 0 0 0 0 0 0 0 1,030 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/2/21 0:00 2319.65 6.0 5 62%226 180 180 180 261 0 0 0 0 0 0 0 0 0 1,026 4 83%292 224 224 224 0 0 0 0 0 0 0 0 0 0 964 5 62%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/2/21 6:00 2550.92 6.0 5 68%246 193 193 193 280 0 0 0 0 0 0 0 0 0 1,105 4 91%318 243 243 243 0 0 0 0 0 0 0 0 0 0 1,048 5 68%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2609.40 6.0 5 70%251 196 196 196 285 0 0 0 0 0 0 0 0 0 1,125 4 93%325 248 248 248 0 0 0 0 0 0 0 0 0 0 1,070 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2527.02 6.0 5 68%244 192 192 192 278 0 0 0 0 0 0 0 0 0 1,097 4 90%316 241 241 241 0 0 0 0 0 0 0 0 0 0 1,039 5 68%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/3/21 0:00 2392.17 6.0 5 64%232 184 184 184 267 0 0 0 0 0 0 0 0 0 1,051 4 85%300 230 230 230 0 0 0 0 0 0 0 0 0 0 990 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/3/21 6:00 3152.55 6.0 6 69%247 194 194 194 281 247 0 0 0 0 0 0 0 0 1,355 5 84%298 228 228 228 329 0 0 0 0 0 0 0 0 0 1,312 6 69%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2888.12 6.0 6 63%228 181 181 181 263 228 0 0 0 0 0 0 0 0 1,264 5 77%275 212 212 212 308 0 0 0 0 0 0 0 0 0 1,219 6 63%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2463.14 6.0 5 66%238 188 188 188 273 0 0 0 0 0 0 0 0 0 1,075 4 88%308 236 236 236 0 0 0 0 0 0 0 0 0 0 1,016 5 66%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/4/21 0:00 2373.16 6.0 5 64%231 183 183 183 265 0 0 0 0 0 0 0 0 0 1,045 4 84%298 228 228 228 0 0 0 0 0 0 0 0 0 0 983 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 5/4/21 6:00 3223.57 6.0 6 70%252 197 197 197 286 252 0 0 0 0 0 0 0 0 1,380 5 86%304 233 233 233 335 0 0 0 0 0 0 0 0 0 1,337 6 70%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 4004.56 6.0 7 75%267 207 207 207 300 267 243 0 0 0 0 0 0 0 1,697 6 87%306 234 234 234 338 306 0 0 0 0 0 0 0 0 1,654 7 75%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 4321.55 6.0 7 81%286 220 220 220 318 286 258 0 0 0 0 0 0 0 1,807 6 94%329 251 251 251 361 329 0 0 0 0 0 0 0 0 1,772 7 81%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5/5/21 0:00 4324.98 6.0 7 81%286 220 220 220 318 286 258 0 0 0 0 0 0 0 1,808 6 94%329 251 251 251 361 329 0 0 0 0 0 0 0 0 1,773 7 81%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 5/5/21 6:00 4601.46 6.0 8 75%268 208 208 208 301 268 245 245 0 0 0 0 0 0 1,951 7 86%303 232 232 232 334 303 272 0 0 0 0 0 0 0 1,906 8 75%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 6348.30 6.0 10 77%274 212 212 212 307 274 249 249 249 430 0 0 0 0 2,670 9 92%324 247 247 247 355 324 289 289 289 0 0 0 0 0 2,613 10 77%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5619.75 6.0 9 82%289 222 222 222 321 289 261 261 261 0 0 0 0 0 2,351 8 92%322 246 246 246 354 322 288 288 0 0 0 0 0 0 2,313 9 82%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 5/6/21 0:00 6261.12 6.0 10 76%271 210 210 210 304 271 247 247 247 425 0 0 0 0 2,639 9 91%320 244 244 244 351 320 286 286 286 0 0 0 0 0 2,581 10 76%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/6/21 6:00 6590.45 6.0 10 80%284 218 218 218 316 284 257 257 257 446 0 0 0 0 2,755 9 96%335 256 256 256 367 335 299 299 299 0 0 0 0 0 2,704 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6735.82 6.0 10 82%289 222 222 222 322 289 261 261 261 456 0 0 0 0 2,807 9 98%342 261 261 261 375 342 305 305 305 0 0 0 0 0 2,760 10 82%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6597.91 6.0 10 80%284 219 219 219 316 284 257 257 257 447 0 0 0 0 2,758 9 96%336 256 256 256 368 336 300 300 300 0 0 0 0 0 2,707 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/7/21 0:00 6342.03 6.0 10 77%274 212 212 212 307 274 249 249 249 430 0 0 0 0 2,668 9 92%324 247 247 247 355 324 289 289 289 0 0 0 0 0 2,611 10 77%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/7/21 6:00 6956.66 6.0 11 76%271 210 210 210 304 271 247 247 247 425 281 0 0 0 2,924 10 85%298 229 229 229 330 298 268 268 268 470 0 0 0 0 2,886 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6950.06 6.0 11 76%271 210 210 210 304 271 247 247 247 425 281 0 0 0 2,922 10 85%298 228 228 228 330 298 268 268 268 470 0 0 0 0 2,884 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6756.34 6.0 10 82%290 223 223 223 322 290 262 262 262 457 0 0 0 0 2,814 9 98%343 262 262 262 376 343 306 306 306 0 0 0 0 0 2,768 10 82%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/8/21 0:00 6571.79 6.0 10 80%283 218 218 218 315 283 256 256 256 445 0 0 0 0 2,749 9 96%335 255 255 255 366 335 298 298 298 0 0 0 0 0 2,697 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/8/21 6:00 6890.00 6.0 11 76%269 208 208 208 302 269 245 245 245 421 279 0 0 0 2,900 10 84%296 227 227 227 327 296 266 266 266 466 0 0 0 0 2,862 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7403.92 6.0 11 81%287 221 221 221 319 287 259 259 259 452 299 0 0 0 3,084 10 90%316 241 241 241 347 316 283 283 283 499 0 0 0 0 3,050 11 81%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6916.77 6.0 11 76%270 209 209 209 303 270 246 246 246 423 280 0 0 0 2,910 10 84%297 227 227 227 328 297 267 267 267 468 0 0 0 0 2,872 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 5/9/21 0:00 6863.31 6.0 10 83%294 226 226 226 326 294 265 265 265 464 0 0 0 0 2,853 9 100%349 266 266 266 381 349 311 311 311 0 0 0 0 0 2,809 10 83%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 5/9/21 6:00 7049.08 6.0 11 77%275 212 212 212 307 275 249 249 249 431 285 0 0 0 2,957 10 86%302 231 231 231 333 302 271 271 271 476 0 0 0 0 2,920 11 77%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7223.10 6.0 11 79%281 216 216 216 313 281 254 254 254 441 292 0 0 0 3,019 10 88%309 236 236 236 340 309 277 277 277 488 0 0 0 0 2,983 11 79%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6939.12 6.0 11 76%271 210 210 210 304 271 246 246 246 424 281 0 0 0 2,918 10 84%297 228 228 228 329 297 268 268 268 469 0 0 0 0 2,880 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6807.26 6.0 10 83%292 224 224 224 324 292 263 263 263 460 0 0 0 0 2,833 9 99%346 264 264 264 378 346 308 308 308 0 0 0 0 0 2,787 10 83%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6662.39 6.0 10 81%287 220 220 220 319 287 259 259 259 451 0 0 0 0 2,781 9 97%339 259 259 259 371 339 302 302 302 0 0 0 0 0 2,732 10 81%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 7286.77 6.0 11 80%283 218 218 218 315 283 256 256 256 445 294 0 0 0 3,042 10 89%311 238 238 238 343 311 279 279 279 492 0 0 0 0 3,007 11 80%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6933.55 6.0 11 76%271 209 209 209 303 271 246 246 246 424 280 0 0 0 2,916 10 84%297 228 228 228 329 297 267 267 267 469 0 0 0 0 2,878 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6084.70 6.0 10 74%264 205 205 205 297 264 241 241 241 413 0 0 0 0 2,578 8 100%347 265 265 265 380 347 310 310 0 0 0 0 0 0 2,489 10 74%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 7035.19 6.0 11 77%274 212 212 212 307 274 249 249 249 430 284 0 0 0 2,952 10 86%301 231 231 231 333 301 271 271 271 475 0 0 0 0 2,915 11 77%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7283.42 6.0 11 80%283 218 218 218 315 283 256 256 256 445 294 0 0 0 3,041 10 89%311 238 238 238 343 311 279 279 279 491 0 0 0 0 3,006 11 80%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6875.70 6.0 11 75%269 208 208 208 301 269 245 245 245 420 278 0 0 0 2,895 10 84%295 226 226 226 327 295 266 266 266 465 0 0 0 0 2,857 11 75%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 4/17/21 6:00 4/17/21 12:0 4/17/21 18:0 4/18/21 0:00 4/18/21 6:00 4/18/21 12:0 4/18/21 18:0 4/19/21 0:00 4/19/21 6:00 4/19/21 12:0 4/19/21 18:0 4/20/21 0:00 4/20/21 6:00 4/20/21 12:0 4/20/21 18:0 4/21/21 0:00 4/21/21 6:00 4/21/21 12:0 4/21/21 18:0 4/22/21 0:00 4/22/21 6:00 4/22/21 12:0 4/22/21 18:0 4/23/21 0:00 4/23/21 6:00 4/23/21 12:0 4/23/21 18:0 4/24/21 0:00 4/24/21 6:00 4/24/21 12:0 4/24/21 18:0 4/25/21 0:00 4/25/21 6:00 4/25/21 12:0 4/25/21 18:0 4/26/21 0:00 4/26/21 6:00 4/26/21 12:0 4/26/21 18:0 4/27/21 0:00 4/27/21 6:00 4/27/21 12:0 4/27/21 18:0 4/28/21 0:00 4/28/21 6:00 4/28/21 12:0 4/28/21 18:0 4/29/21 0:00 4/29/21 6:00 4/29/21 12:0 4/29/21 18:0 4/30/21 0:00 4/30/21 6:00 4/30/21 12:0 4/30/21 18:0 5/1/21 12:00 5/1/21 18:00 5/2/21 12:00 5/2/21 18:00 5/3/21 12:00 5/3/21 18:00 5/4/21 12:00 5/4/21 18:00 5/5/21 12:00 5/5/21 18:00 5/6/21 12:00 5/6/21 18:00 5/7/21 12:00 5/7/21 18:00 5/8/21 12:00 5/8/21 18:00 5/9/21 12:00 5/9/21 18:00 5/10/21 0:00 5/10/21 6:00 5/10/21 12:0 5/10/21 18:0 5/11/21 0:00 5/11/21 6:00 5/11/21 12:0 5/11/21 18:0 NEA BESS Scenario Analysis Data Analysis 44 3 89%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 89%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.0 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.5 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 3 96%9.0 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%8.1 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 82%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 63%6.1 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.4 3 82%7.8 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.7 3 91%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 3 91%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 84%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 65%6.2 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 3 84%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.0 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.5 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 3 83%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 64%6.2 5.1 5.1 5.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 83%7.9 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 19.9 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.3 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.3 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 86%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 66%6.4 5.2 5.2 5.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.0 3 86%8.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.4 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.9 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.6 4 79%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.6 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.7 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.7 4.7 4.7 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.7 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.6 3 88%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 68%6.5 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.4 3 88%8.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.8 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.0 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.2 4.6 4.6 4.6 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.8 3 92%8.7 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.5 3 87%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 67%6.4 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.2 3 87%8.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 20.6 3 97%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 56%5.5 4.8 4.8 4.8 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 3 97%9.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.7 3 99%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 57%5.6 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.1 3 99%9.4 6.8 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.0 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.7 4.7 4.7 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 94%8.8 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 90%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 4 69%6.6 5.3 5.3 5.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.6 3 90%8.4 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.1 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.2 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.4 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 100%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.2 3 100%9.4 6.9 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 23.2 3 96%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.5 3 96%9.0 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.3 4 87%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 65%6.3 5.2 5.2 5.2 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.5 4 87%8.2 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.8 4 95%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.8 5.5 5.5 5.5 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.3 4 95%9.0 6.6 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.9 3 92%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 53%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.9 3 92%8.7 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.7 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 85%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.1 4 81%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.3 3 94%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 55%5.4 4.7 4.7 4.7 6.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 3 94%8.9 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 22.1 3 93%6 6 6 0 0 0 0 0 0 0 0 0 0 0 18 5 54%5.3 4.6 4.6 4.6 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 3 93%8.8 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 21.8 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%7.9 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 95%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.8 5.5 5.5 5.5 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.3 4 95%9.0 6.6 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 80%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 60%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 80%7.6 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.2 4 79%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.8 4.9 4.9 4.9 7.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.7 4 79%7.5 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.8 5 80%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 65%6.3 5.2 5.2 5.2 7.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.6 5 80%7.6 5.8 5.8 5.8 8.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.6 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.8 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 82%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 82%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.6 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 95%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 72%6.8 5.5 5.5 5.5 8.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 31.3 4 95%9.0 6.6 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 89%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.4 5.3 5.3 5.3 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.0 4 89%8.4 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 83%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 62%6.0 5.0 5.0 5.0 7.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 83%7.8 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.7 4 91%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 68%6.6 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.3 4 91%8.6 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.8 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.8 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 90%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 68%6.5 5.3 5.3 5.3 7.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.1 4 90%8.5 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 85%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.1 4 85%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.3 5 84%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 69%6.6 5.3 5.3 5.3 7.8 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.0 5 84%8.0 6.1 6.1 6.1 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.0 5 77%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 63%6.1 5.1 5.1 5.1 7.4 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.8 5 77%7.3 5.7 5.7 5.7 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.9 4 88%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 66%6.4 5.2 5.2 5.2 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.7 4 88%8.3 6.2 6.2 6.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.0 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.2 5 86%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 70%6.7 5.4 5.4 5.4 7.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 37.6 5 86%8.1 6.2 6.2 6.2 9.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.6 6 87%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 75%7.1 5.6 5.6 5.6 8.2 7.1 6.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 45.9 6 87%8.2 6.2 6.2 6.2 9.0 8.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 44.1 6 94%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 48.5 6 94%8.9 6.6 6.6 6.6 9.5 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 47.0 6 94%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 7 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 48.5 6 94%8.9 6.6 6.6 6.6 9.5 8.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 47.0 7 86%6 6 6 6 6 6 6 0 0 0 0 0 0 0 42 8 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 0.0 0.0 0.0 0.0 0.0 0.0 52.8 7 86%8.1 6.1 6.1 6.1 9.0 8.1 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 50.9 9 92%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 0.0 0.0 0.0 0.0 71.6 9 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 0.0 0.0 0.0 0.0 0.0 69.2 8 92%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 9 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 0.0 0.0 0.0 0.0 0.0 63.1 8 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 0.0 0.0 0.0 0.0 0.0 0.0 61.3 9 91%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 0.0 0.0 0.0 0.0 70.9 9 91%8.6 6.4 6.4 6.4 9.3 8.6 7.6 7.6 7.6 0.0 0.0 0.0 0.0 0.0 68.4 9 96%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.5 9 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 71.4 9 98%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 0.0 0.0 0.0 0.0 74.7 9 98%9.3 6.8 6.8 6.8 9.8 9.3 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 72.7 9 96%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.6 5.9 5.9 5.9 8.6 7.6 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.6 9 96%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 71.5 9 92%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 0.0 0.0 0.0 0.0 71.6 9 92%8.7 6.5 6.5 6.5 9.4 8.7 7.6 7.6 7.6 0.0 0.0 0.0 0.0 0.0 69.2 10 85%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.3 10 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.5 10 85%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.2 10 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.4 9 98%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 82%7.8 6.0 6.0 6.0 8.7 7.8 7.0 7.0 7.0 11.7 0.0 0.0 0.0 0.0 74.9 9 98%9.3 6.8 6.8 6.8 9.9 9.3 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 72.9 9 96%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.6 5.8 5.8 5.8 8.6 7.6 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.4 9 96%9.0 6.7 6.7 6.7 9.7 9.0 7.8 7.8 7.8 0.0 0.0 0.0 0.0 0.0 71.2 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 77.7 10 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.9 10 90%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 7.6 0.0 0.0 0.0 81.8 10 90%8.5 6.4 6.4 6.4 9.2 8.5 7.5 7.5 7.5 12.4 0.0 0.0 0.0 0.0 80.2 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 78.0 10 84%7.9 6.1 6.1 6.1 8.8 7.9 7.1 7.1 7.1 11.9 0.0 0.0 0.0 0.0 76.2 9 100%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 83%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.7 9 100%9.4 6.9 6.9 6.9 10.0 9.4 8.1 8.1 8.1 0.0 0.0 0.0 0.0 0.0 73.9 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 7.4 0.0 0.0 0.0 79.0 10 86%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 0.0 0.0 0.0 0.0 77.2 10 88%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 7.5 0.0 0.0 0.0 80.4 10 88%8.3 6.2 6.2 6.2 9.1 8.3 7.4 7.4 7.4 12.2 0.0 0.0 0.0 0.0 78.7 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.1 10 84%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.3 9 99%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 11.7 0.0 0.0 0.0 0.0 75.3 9 99%9.4 6.9 6.9 6.9 9.9 9.4 8.1 8.1 8.1 0.0 0.0 0.0 0.0 0.0 73.4 9 97%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 81%7.7 5.9 5.9 5.9 8.6 7.7 7.0 7.0 7.0 11.5 0.0 0.0 0.0 0.0 74.1 9 97%9.2 6.7 6.7 6.7 9.8 9.2 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 72.0 10 89%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 80%7.6 5.8 5.8 5.8 8.6 7.6 6.9 6.9 6.9 11.4 7.5 0.0 0.0 0.0 80.9 10 89%8.4 6.3 6.3 6.3 9.1 8.4 7.4 7.4 7.4 12.3 0.0 0.0 0.0 0.0 79.2 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.1 10 84%8.0 6.1 6.1 6.1 8.8 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.3 8 100%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 10 74%7.0 5.6 5.6 5.6 8.2 7.0 6.6 6.6 6.6 10.7 0.0 0.0 0.0 0.0 69.5 8 100%9.4 6.9 6.9 6.9 10.0 9.4 8.1 8.1 0.0 0.0 0.0 0.0 0.0 0.0 65.6 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 7.3 0.0 0.0 0.0 78.9 10 86%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 0.0 0.0 0.0 0.0 77.1 10 89%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 80%7.6 5.8 5.8 5.8 8.6 7.6 6.9 6.9 6.9 11.4 7.5 0.0 0.0 0.0 80.9 10 89%8.4 6.3 6.3 6.3 9.1 8.4 7.4 7.4 7.4 12.3 0.0 0.0 0.0 0.0 79.2 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 77.6 10 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.8 NEA BESS Scenario Analysis Data Analysis 45 6709.07 6.0 10 82%288 222 222 222 321 288 260 260 260 454 0 0 0 0 2,798 9 98%341 260 260 260 373 341 304 304 304 0 0 0 0 0 2,750 10 82%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 7160.76 6.0 11 78%278 215 215 215 311 278 252 252 252 437 289 0 0 0 2,997 10 87%306 234 234 234 338 306 275 275 275 484 0 0 0 0 2,961 11 78%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7195.55 6.0 11 79%280 216 216 216 312 280 253 253 253 439 291 0 0 0 3,009 10 87%308 235 235 235 339 308 276 276 276 486 0 0 0 0 2,973 11 79%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6968.16 6.0 11 76%272 210 210 210 305 272 247 247 247 426 282 0 0 0 2,928 10 85%299 229 229 229 330 299 268 268 268 471 0 0 0 0 2,891 11 76%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6882.71 6.0 11 75%269 208 208 208 302 269 245 245 245 421 278 0 0 0 2,898 10 84%295 226 226 226 327 295 266 266 266 465 0 0 0 0 2,860 11 75%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7039.61 6.0 11 77%274 212 212 212 307 274 249 249 249 430 285 0 0 0 2,953 10 86%301 231 231 231 333 301 271 271 271 476 0 0 0 0 2,916 11 77%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7191.11 6.0 11 79%280 216 216 216 312 280 253 253 253 439 291 0 0 0 3,007 10 87%307 235 235 235 339 307 276 276 276 486 0 0 0 0 2,972 11 79%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6802.47 6.0 10 83%292 224 224 224 324 292 263 263 263 460 0 0 0 0 2,831 9 99%346 264 264 264 378 346 308 308 308 0 0 0 0 0 2,785 10 83%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6699.87 6.0 10 81%288 221 221 221 320 288 260 260 260 453 0 0 0 0 2,794 9 98%341 260 260 260 373 341 304 304 304 0 0 0 0 0 2,746 10 81%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 7056.15 6.0 11 77%275 212 212 212 308 275 250 250 250 431 285 0 0 0 2,959 10 86%302 231 231 231 334 302 271 271 271 477 0 0 0 0 2,922 11 77%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 7112.17 6.0 11 78%277 214 214 214 309 277 251 251 251 434 287 0 0 0 2,979 10 86%304 233 233 233 336 304 273 273 273 480 0 0 0 0 2,943 11 78%6 6 6 6 6 6 6 6 6 6 6 0 0 0 66 6638.94 6.0 10 81%286 220 220 220 318 286 258 258 258 449 0 0 0 0 2,773 9 97%338 258 258 258 370 338 301 301 301 0 0 0 0 0 2,723 10 81%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6376.22 6.0 10 78%275 213 213 213 308 275 250 250 250 432 0 0 0 0 2,680 9 93%325 248 248 248 357 325 290 290 290 0 0 0 0 0 2,624 10 78%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 6545.84 6.0 10 80%282 217 217 217 314 282 255 255 255 443 0 0 0 0 2,740 9 95%333 254 254 254 365 333 297 297 297 0 0 0 0 0 2,687 10 80%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 4561.30 6.0 8 75%266 207 207 207 299 266 243 243 0 0 0 0 0 0 1,938 6 99%346 264 264 264 378 346 0 0 0 0 0 0 0 0 1,863 8 75%6 6 6 6 6 6 6 6 0 0 0 0 0 0 48 2367.08 6.0 5 63%230 182 182 182 265 0 0 0 0 0 0 0 0 0 1,043 4 84%297 228 228 228 0 0 0 0 0 0 0 0 0 0 981 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2161.46 6.0 5 58%212 171 171 171 248 0 0 0 0 0 0 0 0 0 972 4 77%274 212 212 212 0 0 0 0 0 0 0 0 0 0 908 5 58%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2502.63 6.0 5 67%242 190 190 190 276 0 0 0 0 0 0 0 0 0 1,089 4 89%313 239 239 239 0 0 0 0 0 0 0 0 0 0 1,030 5 67%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2403.51 6.0 5 64%233 185 185 185 268 0 0 0 0 0 0 0 0 0 1,055 4 86%301 231 231 231 0 0 0 0 0 0 0 0 0 0 994 5 64%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2286.37 6.0 5 61%223 178 178 178 258 0 0 0 0 0 0 0 0 0 1,015 4 81%288 221 221 221 0 0 0 0 0 0 0 0 0 0 952 5 61%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2186.29 6.0 5 59%214 172 172 172 250 0 0 0 0 0 0 0 0 0 980 4 78%276 213 213 213 0 0 0 0 0 0 0 0 0 0 917 5 59%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2830.39 6.0 6 62%224 179 179 179 259 224 0 0 0 0 0 0 0 0 1,244 5 76%270 209 209 209 303 0 0 0 0 0 0 0 0 0 1,200 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2922.88 6.0 6 64%231 183 183 183 266 231 0 0 0 0 0 0 0 0 1,276 5 78%278 214 214 214 310 0 0 0 0 0 0 0 0 0 1,231 6 64%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2576.19 6.0 5 69%248 194 194 194 282 0 0 0 0 0 0 0 0 0 1,114 4 92%321 245 245 245 0 0 0 0 0 0 0 0 0 0 1,058 5 69%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2355.04 6.0 5 63%229 182 182 182 264 0 0 0 0 0 0 0 0 0 1,038 4 84%296 227 227 227 0 0 0 0 0 0 0 0 0 0 976 5 63%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 3095.55 6.0 6 67%243 191 191 191 277 243 0 0 0 0 0 0 0 0 1,336 5 83%293 225 225 225 325 0 0 0 0 0 0 0 0 0 1,291 6 67%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3288.45 6.0 6 72%256 200 200 200 290 256 0 0 0 0 0 0 0 0 1,402 5 88%309 237 237 237 341 0 0 0 0 0 0 0 0 0 1,360 6 72%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 3286.70 6.0 6 71%256 200 200 200 290 256 0 0 0 0 0 0 0 0 1,402 5 88%309 237 237 237 341 0 0 0 0 0 0 0 0 0 1,360 6 71%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2869.91 6.0 6 62%227 180 180 180 262 227 0 0 0 0 0 0 0 0 1,257 5 77%273 211 211 211 306 0 0 0 0 0 0 0 0 0 1,213 6 62%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 2625.27 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.53 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.15 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2627.22 6.0 5 70%253 197 197 197 286 0 0 0 0 0 0 0 0 0 1,131 4 94%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2626.34 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,131 4 94%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.11 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.90 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2626.13 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.56 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.74 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.74 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2627.59 6.0 5 70%253 197 197 197 286 0 0 0 0 0 0 0 0 0 1,131 4 94%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2626.00 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.49 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.06 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2626.84 6.0 5 70%253 197 197 197 286 0 0 0 0 0 0 0 0 0 1,131 4 94%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,077 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.52 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.58 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.59 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.95 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.02 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.27 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.47 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.33 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.62 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.12 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.91 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.26 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.83 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.25 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.40 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.81 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.54 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.00 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.71 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.98 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.39 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.76 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.83 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.75 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.68 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.89 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.39 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.12 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.34 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.29 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.63 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2625.19 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2624.32 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.36 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.36 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/1/21 0:00 2623.28 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/1/21 6:00 2617.98 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,128 4 93%326 249 249 249 0 0 0 0 0 0 0 0 0 0 1,074 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.12 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.77 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/2/21 0:00 2624.62 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/2/21 6:00 2623.39 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.43 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.88 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/3/21 0:00 2623.87 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/3/21 6:00 2623.21 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.32 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.69 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/4/21 0:00 2623.42 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6/4/21 6:00 2623.58 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,130 4 93%327 250 250 250 0 0 0 0 0 0 0 0 0 0 1,076 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2622.29 6.0 5 70%252 197 197 197 286 0 0 0 0 0 0 0 0 0 1,129 4 93%327 249 249 249 0 0 0 0 0 0 0 0 0 0 1,075 5 70%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 2623.23 5/12/21 0:00 5/12/21 6:00 5/12/21 12:0 5/12/21 18:0 5/13/21 0:00 5/13/21 6:00 5/13/21 12:0 5/13/21 18:0 5/14/21 0:00 5/14/21 6:00 5/14/21 12:0 5/14/21 18:0 5/15/21 0:00 5/15/21 6:00 5/15/21 12:0 5/15/21 18:0 5/16/21 0:00 5/16/21 6:00 5/16/21 12:0 5/16/21 18:0 5/17/21 0:00 5/17/21 6:00 5/17/21 12:0 5/17/21 18:0 5/18/21 0:00 5/18/21 6:00 5/18/21 12:0 5/18/21 18:0 5/19/21 0:00 5/19/21 6:00 5/19/21 12:0 5/19/21 18:0 5/20/21 0:00 5/20/21 6:00 5/20/21 12:0 5/20/21 18:0 5/21/21 0:00 5/21/21 6:00 5/21/21 12:0 5/21/21 18:0 5/22/21 0:00 5/22/21 6:00 5/22/21 12:0 5/22/21 18:0 5/23/21 0:00 5/23/21 6:00 5/23/21 12:0 5/23/21 18:0 5/24/21 0:00 5/24/21 6:00 5/24/21 12:0 5/24/21 18:0 5/25/21 0:00 5/25/21 6:00 5/25/21 12:0 5/25/21 18:0 5/26/21 0:00 5/26/21 6:00 5/26/21 12:0 5/26/21 18:0 5/27/21 0:00 5/27/21 6:00 5/27/21 12:0 5/27/21 18:0 5/28/21 0:00 5/28/21 6:00 5/28/21 12:0 5/28/21 18:0 5/29/21 0:00 5/29/21 6:00 5/29/21 12:0 5/29/21 18:0 5/30/21 0:00 5/30/21 6:00 5/30/21 12:0 5/30/21 18:0 5/31/21 0:00 5/31/21 6:00 5/31/21 12:0 5/31/21 18:0 6/1/21 12:00 6/1/21 18:00 6/2/21 12:00 6/2/21 18:00 6/3/21 12:00 6/3/21 18:00 6/4/21 12:00 6/4/21 18:00 NEA BESS Scenario Analysis Data Analysis 46 9 98%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 82%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 0.0 0.0 0.0 0.0 74.5 9 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 72.5 10 87%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 78%7.4 5.8 5.8 5.8 8.5 7.4 6.8 6.8 6.8 11.2 7.4 0.0 0.0 0.0 79.9 10 87%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.2 0.0 0.0 0.0 0.0 78.2 10 87%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 7.5 0.0 0.0 0.0 80.2 10 87%8.3 6.2 6.2 6.2 9.1 8.3 7.3 7.3 7.3 12.2 0.0 0.0 0.0 0.0 78.4 10 85%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 76%7.2 5.7 5.7 5.7 8.3 7.2 6.7 6.7 6.7 11.0 7.3 0.0 0.0 0.0 78.4 10 85%8.0 6.1 6.1 6.1 8.9 8.0 7.2 7.2 7.2 11.9 0.0 0.0 0.0 0.0 76.6 10 84%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 75%7.2 5.6 5.6 5.6 8.3 7.2 6.7 6.7 6.7 10.9 7.2 0.0 0.0 0.0 77.7 10 84%7.9 6.0 6.0 6.0 8.8 7.9 7.1 7.1 7.1 11.8 0.0 0.0 0.0 0.0 75.9 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 7.3 0.0 0.0 0.0 78.9 10 86%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 0.0 0.0 0.0 0.0 77.2 10 87%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 79%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.3 7.5 0.0 0.0 0.0 80.1 10 87%8.2 6.2 6.2 6.2 9.1 8.2 7.3 7.3 7.3 12.2 0.0 0.0 0.0 0.0 78.4 9 99%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 83%7.8 6.0 6.0 6.0 8.7 7.8 7.1 7.1 7.1 11.7 0.0 0.0 0.0 0.0 75.2 9 99%9.4 6.8 6.8 6.8 9.9 9.4 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 73.3 9 98%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 81%7.7 5.9 5.9 5.9 8.7 7.7 7.0 7.0 7.0 11.6 0.0 0.0 0.0 0.0 74.4 9 98%9.2 6.8 6.8 6.8 9.8 9.2 8.0 8.0 8.0 0.0 0.0 0.0 0.0 0.0 72.4 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 77%7.3 5.7 5.7 5.7 8.4 7.3 6.8 6.8 6.8 11.1 7.4 0.0 0.0 0.0 79.1 10 86%8.1 6.1 6.1 6.1 8.9 8.1 7.2 7.2 7.2 12.0 0.0 0.0 0.0 0.0 77.3 10 86%6 6 6 6 6 6 6 6 6 6 0 0 0 0 60 11 78%7.4 5.8 5.8 5.8 8.4 7.4 6.8 6.8 6.8 11.2 7.4 0.0 0.0 0.0 79.5 10 86%8.2 6.2 6.2 6.2 9.0 8.2 7.3 7.3 7.3 12.1 0.0 0.0 0.0 0.0 77.8 9 97%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 81%7.6 5.9 5.9 5.9 8.6 7.6 7.0 7.0 7.0 11.5 0.0 0.0 0.0 0.0 73.9 9 97%9.1 6.7 6.7 6.7 9.7 9.1 7.9 7.9 7.9 0.0 0.0 0.0 0.0 0.0 71.8 9 93%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 78%7.4 5.7 5.7 5.7 8.4 7.4 6.8 6.8 6.8 11.1 0.0 0.0 0.0 0.0 71.8 9 93%8.8 6.5 6.5 6.5 9.4 8.8 7.7 7.7 7.7 0.0 0.0 0.0 0.0 0.0 69.5 9 95%6 6 6 6 6 6 6 6 6 0 0 0 0 0 54 10 80%7.5 5.8 5.8 5.8 8.5 7.5 6.9 6.9 6.9 11.4 0.0 0.0 0.0 0.0 73.2 9 95%9.0 6.6 6.6 6.6 9.6 9.0 7.8 7.8 7.8 0.0 0.0 0.0 0.0 0.0 71.0 6 99%6 6 6 6 6 6 0 0 0 0 0 0 0 0 36 8 75%7.1 5.6 5.6 5.6 8.2 7.1 6.6 6.6 0.0 0.0 0.0 0.0 0.0 0.0 52.5 6 99%9.4 6.9 6.9 6.9 9.9 9.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 49.2 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.9 4 84%8.0 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.1 4 77%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 58%5.7 4.8 4.8 4.8 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 77%7.3 5.7 5.7 5.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.4 4 89%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 67%6.4 5.3 5.3 5.3 7.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.0 4 89%8.4 6.3 6.3 6.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.3 4 86%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 64%6.2 5.1 5.1 5.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 29.2 4 86%8.1 6.1 6.1 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.4 4 81%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 61%5.9 5.0 5.0 5.0 7.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.3 4 81%7.7 5.9 5.9 5.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 25.5 4 78%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 59%5.7 4.9 4.9 4.9 7.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.5 4 78%7.4 5.8 5.8 5.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 24.6 5 76%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.0 5.0 5.0 5.0 7.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.4 5 76%7.2 5.7 5.7 5.7 8.3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.5 5 78%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 64%6.1 5.1 5.1 5.1 7.5 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 35.1 5 78%7.4 5.8 5.8 5.8 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 33.2 4 92%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 69%6.6 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.5 4 92%8.7 6.4 6.4 6.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.0 4 84%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 63%6.1 5.1 5.1 5.1 7.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.8 4 84%7.9 6.0 6.0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 26.0 5 83%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 67%6.5 5.3 5.3 5.3 7.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.5 5 83%7.8 6.0 6.0 6.0 8.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.6 5 88%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 72%6.8 5.5 5.5 5.5 8.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.1 5 88%8.3 6.3 6.3 6.3 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.2 5 88%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 71%6.8 5.5 5.5 5.5 8.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 38.1 5 88%8.3 6.2 6.2 6.2 9.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 36.1 5 77%6 6 6 6 6 0 0 0 0 0 0 0 0 0 30 6 62%6.1 5.1 5.1 5.1 7.4 6.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 34.7 5 77%7.3 5.7 5.7 5.7 8.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 32.8 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 94%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 94%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 94%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.5 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 94%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 94%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.8 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 4 93%6 6 6 6 0 0 0 0 0 0 0 0 0 0 24 5 70%6.7 5.4 5.4 5.4 7.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 30.9 4 93%8.8 6.5 6.5 6.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 28.4 NEA BESS Scenario Analysis Data Analysis 47 NEA BESS Scenario Analysis Data Analysis 48 NEA BESS Scenario Analysis Data Analysis 49 NEA BESS Scenario Analysis Data Analysis 50 NEA BESS Scenario Analysis Data Analysis 51 NEA BESS Scenario Analysis Data Analysis 52 NEA BESS Scenario Analysis Data Analysis 53 NEA BESS Scenario Analysis Data Analysis 54 NEA BESS Scenario Analysis Data Analysis 55 NEA BESS Scenario Analysis Data Analysis 56 NEA BESS Scenario Analysis Data Analysis 57 NEA BESS Scenario Analysis Data Analysis 58