HomeMy WebLinkAboutAS12-054 Senior Housing Polysun Report - Financial[1]Financial Report 1 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. City of Tanana Senior Housing Complex Space heating and DHW system Location of the system USA AK Fairbanks Longitude: -147.98° Latitude: 64.82° Elevation: 446 ft This report has been created by: Nathan Stumpff - Arctic Sun, LLC Thorsten Chlupp Po Box 74798 99707 Fairbanks 907/457-1297 System overview (annual values) Total fuel and/or electrical energy consumption of the system [Etot]241,408 kBtu Total energy consumption [Quse]242,809.8 kBtu System performance (Quse / Etot)1.01 Comfort demand Energy demand covered Financial Report 2 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Overview solar thermal energy (annual values) Collector area 326.9 ft² Solar fraction total 20.8% Solar fraction hot water [SFnHw]48.6 % Solar fraction building [SFnBd]15.3 % Total annual field yield 52,458.5 kBtu Collector field yield relating to gross area 160.5 kBtu/ft²/Year Collector field yield relating to aperture area 176.1 kBtu/ft²/Year Max. fuel savings 478 gal: [Heating oil] Max. energy savings 61,737.1 kBtu Max. reduction in CO₂ emissions 11,993.6 pound Solar fraction: fraction of solar energy to system [SFn] Horizon line Meteorological data-Overview Average outdoor temperature 29.2 °F Global irradiation, annual sum 318.3 kBtu/ft² Diffuse irradiation, annual sum 123 kBtu/ft² Financial analysis - Solar thermal Purchase costs 37,900 USD Life span 30 years Proportional incentives 0 % Incentives per area 0 USD Fixed incentives 0 USD Inflation 1.3 % Interest 0 % Increase of energy prices 5 % Electricity 0.71 USD/kWh(el.); 0.71 USD/kWh Heating oil 5.504 USD/gal; 0.043 USD/kBtu Financial Report 3 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Financial analysis - Solar thermal Effective purchase cost after grants 37,900 USD Annual energy cost savings 2,630.671 USD Solar energy cost per kWh 0.079 USD Payback period 11 years Present value of the system 217,731.5 USD Net present value 179,831.5 USD Component overview (annual values) Boiler Oil boiler 50kW with internal pump Power kBtu/hr 170.65 Total efficiency %83 Energy from/to the system [Qaux]kBtu 200,256.6 Fuel and electrical energy consumption [Eaux]kBtu 241,173.9 Energy savings solar thermal kBtu 61,737.1 CO₂ savings solar thermal pound 11,993.6 Fuel savings solar thermal gal 478 Collector North America Empire EC-40-1.5 Data Source SRCC Number of collectors 8 Number of arrays 2 Total gross area ft²326.88 Total aperture area ft²297.945 Total absorber area ft²297.95 Tilt angle (hor.=0°, vert.=90°)°70 Orientation (E=+90°, S=0°, W=-90°)°0 Collector field yield [Qsol]kBtu 52,458.5 Irradiation onto collector area [Esol]kBtu 148,200 Collector efficiency [Qsol / Esol]%35.4 Direct irradiation after IAM kBtu 88,913.9 Building Multifamily house, low-energy building Heated/air-conditioned living area ft²3,168 Heating setpoint temperature °F 70.5 Heating energy demand excluding DHW [Qdem]kBtu 210,162.8 Specific heating energy demand excluding DHW [Qdem]kBtu/ft²66.3 Solar gain through windows kBtu 62,854.1 Total energy losses kBtu 297,676.9 Financial Report 4 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Convector Floor heating Floor heating Number of heating/cooling modules -38 Power per heating module under standard conditions kBtu/hr 3 Nominal inlet temperature °F 104 Nominal return temperature °F 95 Net energy from/to heating/cooling modules kBtu 210,055.5 Hot water demand Constant Volume withdrawal/daily consumption gal/d 120.4 Temperature setting °F 120 Energy demand [Qdem]kBtu 31,177.1 External heat exchanger Fresh water station heat exchanger Plate heat exchanger, medium size Transfer capacity W/K 10,000 External heat exchanger Solar loop heat exchanger Plate heat exchanger, large Transfer capacity W/K 17,000 Pump Space heating loop pump Pump Eco, medium Circuit pressure drop psi 3.055 Flow rate gpm 19.2 Fuel and electrical energy consumption [Epar]kBtu 145.3 Pump Fresh water station pump Pump Eco, small Circuit pressure drop psi 0.063 Flow rate gpm 2.2 Fuel and electrical energy consumption [Epar]kBtu 6.3 Pump Tank Side Circulator Wilo-Stratos ECO 25/1-3 Circuit pressure drop psi 0.689 Flow rate gpm 4.7 Fuel and electrical energy consumption [Epar]kBtu 32.3 Pump Main Solar Circulator Wilo-Stratos 25/1-6 Circuit pressure drop psi 0.569 Flow rate gpm 5.7 Fuel and electrical energy consumption [Epar]kBtu 50.2 Financial Report 5 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Storage tank Buffer tank 2000gal US universal tank Volume gal 2,000 Height ft 7.22 Material Enameled steel Insulation Flexible polyurethane foam Thickness of insulation in 4 Heat loss kBtu 5,598.7 Connection losses kBtu 1,522.3 Loop Solar loop Fluid mixture Propylene mixture Fluid concentration %40 Fluid domains volume gal 17.3 Pressure on top of the circuit psi 58.016 Solar thermal energy to the system [Qsol]kBtu Financial Report 6 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Heat generator energy to the system (solar thermal energy not included) [Qaux]kBtu Solar fraction: fraction of solar energy to system [SFn]% Total fuel and/or electrical energy consumption of the system [Etot]kBtu Financial Report 7 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Year Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Solar thermal energy to the system [Qsol] kBtu 52459 1138 4326 8889 8464 6469 3902 3639 4368 5503 4007 1770 -18 Heat generator energy to the system (solar thermal energy not included) [Qaux] kBtu 200257 41567 28027 18545 5968 674 0 0 331 6071 20836 34051 44185 Heat generator fuel and electrical energy consumption [Eaux] kBtu 241174 49765 33676 22471 7415 923 0 0 439 7579 25199 40839 52869 Solar fraction: fraction of solar energy to system [SFn] %20.8 2.7 13.4 32.4 58.6 90.6 100 100 92.9 47.5 16.1 4.9 0 Total fuel and/or electrical energy consumption of the system [Etot] kBtu 241408 49794 33703 22499 7434 936 8 7 448 7594 25222 40866 52896 Irradiation onto collector area [Esol] kBtu 148200 3524 11015 21020 20868 18731 15859 15530 13839 12618 9701 5496 0 Electrical energy consumption of pumps [Epar] kBtu 234 29 27 28 20 13 8 7 9 16 23 27 28 Heat loss to indoor room (including heat generator losses) [Qint] kBtu 50394 8756 6266 4689 2265 1222 1102 1209 1068 2235 5018 7385 9179 Heat loss to surroundings (without collector losses) [Qext] kBtu 751 29 66 96 89 86 80 83 70 54 52 45 1 Total energy consumption [Quse] kBtu 242810 41954 31653 26524 13191 5804 2726 2736 3861 11136 24160 35293 43771 Collector North America Daily maximum temperature [ °F] Financial Report 8 /8 V5.10.9.16810 / 21.09.2012 / 10:38:25 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results. Energy flow diagram