Loading...
HomeMy WebLinkAboutMV Library GSHP Evaluation R7 - FINALMendenhall Valley Library Geothermal Schematic Design Cost Estimate AIRPORT & DPAC GSHP COST INFORMATION DPAC Horizontal Piping 7272 DPAC Horizontal Piping Bid Cost 265,517$ DPAC Horizontal Piping Bid Cost/LF 36.51$ DPAC Bid + CO Cost/LF of borehole 12.81$ MENDENHALL VALLEY LIBRARY GEOTHERMAL LOOPFIELD DESIGN ASSUMPTIONS Mendenhall Valley Library SF 20,600 Peak BTUH per SF 25 Total BTUH Peak Heat Load 515,000 LF Borehole Piping per BTUH 0.01359 LF Boreholes required at Dimond Park Library1 7,000 Number of 350' boreholes 20 Estimated length of Horizontal Piping 1,560 MENDENHALL VALLEY LIBRARY GSHP SYSTEM CONSTRUCTION COST ESTIMATE Boreholes2 $89,670 --escalation 17.50% $15,692 Driller Mobilization2 $170,000 --escalation 17.50% $29,750 Horizontal Piping2 $56,959 --escalation 17.50% $9,968 Site Demolition & Earthwork $80,000 Heat Pump Infrastructure in Boiler Room $140,000 Construction Contingency $57,961 Estimated Construction Cost of MV Library GSHP System $650,000 MENDENHALL VALLEY LIBRARY GSHP SYSTEM PROJECT COST Construction Cost of MV Library GSHP System $650,000 Design $55,000 Test Wells - Use DPAC well performance for design1 $0 Conductance Tests - Use DPAC well performance for design1 $0 Permits $5,000 CBJ Bidding Services $5,000 Consultant Construction Inspection Services $14,000 CBJ Project Management Services $28,000 Commissioning $10,500 Annual O&M Reporting to AEA $10,500 Project Contingency $47,000 Total Project Cost $825,000 Project Capital Cost $675,000 Project Development Cost $150,000 1 Assumes similar heat transfer conductance in soil as Dimond Park Aquatic Center 2 Cost based on Spring 2009 bid & construction results for DPAC Loop Fields Printed: 9/18/2013 Page 1 of 1