Supercritical CO2 Power Cycle Developments and Commercialization: Why sCO2
can Displace Steam Ste
am
Michael Persichilli, Alex Kacludis, Edward Zdankiewicz, and Timothy Held (a)
Echogen Power Systems LLC
365 Water St.
Akron, OH 44308 U.S.A.
www.echogen.com
ABSTRACT
The U.S. DOE estimates that 280,000 MW discharged annually in the U.S. as waste heat could
be recycled as usable energy to provide 20 percent of U.S. electricity needs while slashing GHG
by 20 percent and saving USD $70-150B per year on energy costs. Waste heat can be
considered as the other green energy because it is a renewable energy equivalent resource that
improves energy efficiency from existing fossil fuel usage, while reducing grid demand by
converting the recovered heat into usable electricity, heating and/or cooling. While various
sources of independent data suggest that this waste heat recovery opportunity is valued at over
USD $600B for the U.S. market, similar large opportunities exist worldwide.
Echogen Power Systems LLC (Akron, OH U.S.A.) is developing power generation technologies
that transform heat from waste and renewable energy sources into electricity and process heat.
The thermal engine technology; the Thermafficient® Heat Engine converts waste heat to power
using a breakthrough supercritical CO2-based power cycle.
Compared to organic and steam-based Rankine Cycle systems, supercritical CO2 can achieve
high efficiencies over a wide temperature range of heat sources with compact components
resulting in a smaller system footprint, lower capital and operating costs. The Levelized Cost of
Electricity (LCOE) is calculated at an average USD $0.025 per kWh for the CO2-based heat
engine and averages at USD $0.065 per kWh for a complete combined cycle gas turbine system
utilizing the supercritical CO2 heat engine for bottom cycling.
This paper presents an exemplary trade study comparison between the CO2 and steam-based
heat recovery systems. An update is also provided for the Echogen 250 kW demonstration
thermal engine which completed initial testing at the American Electric Power’s research center
during 2011. Also presented is current status of long term testing with this system at a
commercial district heating organization, and a multi-megawatt heat engine that will be
installed at a U.S. customer host site during 2013.
__________________
(a) Presenting author.
2
INTRODUCTION
Concerns about energy affordability, energy security, and greenhouse gas emissions have
heightened interest in the potential for energy efficiency because it offers a largely untapped
energy resource for the economies of the world. Usable (waste) heat to power is a leading
application area for energy efficiency that can address this growing need. This paper presents
an exemplary trade study of two heat recovery technologies that can capture and convert these
energy sources: heat recovery steam generation and Echogen’s supercritical CO2 based heat to
power cycle.
Usable (waste) heat to power – the existing market opportunity
Repurposing usable (waste) heat to power represents a critical component of addressing global
energy stability and security. The International Energy Outlook 2011 Report (1) estimates that
the United States consumed 100.1 quadrillion BTU (quads) of energy in 2008 which is projected
to increase 0.5 percent annually to 114.2 quads by 2035. Comparable energy consumption
estimates for India, China and the non-OECD Asia region are summarized in Table 1.
Table 1: Total Primary Energy Consumption by Region (from Ref. 1)
Region
Energy Consumption by Region (quadrillion BTU)
2008 (Historical) 2035 (Projected)
Average Annual
Percent Change
(2008-2035)
Non-OECD Asia 137.9 298.8 2.9
China 86.2 191.4 3.0
India 21.1 49.2 3.2
Other 30.7 58.2 2.4
United States 100.1 114.2 0.5
According to the U.S. Department of Energy (DOE), U. S. industry alone consumes
approximately 32 quadrillion BTUs (quads) of energy per year, almost one third of all energy
used in the U. S., of which 280,000 MWh lost as waste heat may be recoverable and repurposed
as useable energy, while slashing GHG emissions by 20 percent and saving USD $70-150B per
year on energy generation costs (2). Similar opportunities exist for India, China and the rest of
the Non-OECD Asia region.
Energy-intensive manufacturers such as steel, glass, cement, chemicals, glass, aluminum and
pulp/paper, oil & gas, etc. often experience slim profit margins in the U.S. and reducing
operating costs through reductions in energy consumption can help them gain a competitive
edge. For example, a steel company with typical profit margins that cuts energy spending by
$66,000 (e.g. by converting waste heat into electricity) would have to increase total sales by
$1,000,000 in order to achieve the same financial impact.
3
While gas turbines accounted for 15 percent of the power generation industry in 1998, they are
expected to account for 40 percent of U.S. power generation by 2020. A 2009 Forecast
International study estimates the global installed base for industrial gas turbines at 46,455 units
consisting of 21 percent (9,755 units) aeroderivative, 46 percent (21,370 units) light frame
units, and the remaining 33 percent (15,330 units) as large frame turbines (3). The large frame
units (e.g. above 120 MWe size) are typically installed for utility-scale power generation and are
usually configured for combined cycle service with large heat recovery steam generators for
bottom cycling. The small to medium size gas turbine markets are typically sold as simple cycle
units because of the difficulties and economics in scaling down steam systems for combined
cycle service. The small to medium gas turbine market makes sense for other bottom cycling
technologies such as the supercritical CO2 based power cycle which can deliver smaller, more
economical solutions for bottom cycling. We estimate that a 10 percent market share to install
Echogen heat engines as a bottoming cycle on existing and new 20-120 MWe, simple cycle GTs
projected over the next five years would be an opportunity estimated at more than $3B.
ECHOGEN’S UNIQUE TECHNOLOGY
Echogen is currently commercializing a waste
(useable) heat to power system through
development of a proprietary thermal engine
which is entering the product introduction and
customer demonstration phase of development
for industrial markets. The Echogen heat engine
consists of five main components: exhaust and
recuperator heat exchangers, condenser, system
pump, and power turbine (Figures 1 and 2).
Ancillary components (valves and sensors)
provide system monitoring and control. Heat
energy is introduced through an exhaust heat
exchanger installed into the exhaust stack of a
gas turbine or the furnace or flue gas exhaust of
an industrial process, or other external heat
sources with 200oC to greater than 540oC
operating temperature range (400oF to greater
than 1000oF). Echogen’s technology can provide integrated power, heating and/or cooling
through a flexible system architecture, that can be configured for power, co-generation or tri-
generation. The useable energy can be generated from the turbine exhaust heat without
burning fuel or producing resultant emissions which will provide the added benefit of reducing
greenhouse emissions while improving overall energy efficiency.
The sCO2 heat engine is a platform technology scalable from 250 kWe to greater than 50 MWe
to support the widest possible variety of industrial and utility scale applications. The Echogen
technology is thermal source agnostic, meaning that it is suitable with a wide range of heat
sources for energy recovery with efficiencies up to 30 percent. Our patent-pending thermal
Figure 1: Simplified process flow diagram
for the Echogen heat engine.
4
engines can transform significant amounts of waste heat into electricity for applications ranging
from bottom cycling in gas turbines, stationary reciprocating engine gensets, industrial waste
heat recovery, solar thermal, geothermal, and hybrid alternatives to the internal combustion
engine (4-6).
Advantages of supercritical CO2 over steam
Supercritical CO2 is an ideal working fluid for closed-loop power generation applications. It is a
low-cost fluid that is non-toxic, non-flammable, non-corrosive and readily available. The high
fluid density of sCO2 enables extremely compact turbomachinery designs. Figure 3 compares
Echogen’s 10 MWe CO2 turbine, which is being designed for commercial service, to a
commercially available 10 MWe steam turbine. Supercritical CO2 turbines are very compact and
highly efficient with simpler, single casing body designs while steam turbines usually require
multiple turbine stages (i.e., high, medium and low-pressure) and associated casings with a
10 MWe
SUPERCRITICAL CO2
POWER TURBINE
10 MWe
STEAM
POWER TURBINE
Figure 3: Echogen’s 10 MWe sCO2 power turbine compared to a 10 MWe steam turbine.
Cycle Description:
Liquid CO2 pumped to
supercritical pressure
Internal system heat recycled
at recuperator
Turbine exhaust or industrial waste
heat added at waste heat exchanger
High energy sCO2 expanded at
power turbine drives generator
Generator produces electrical
power to customer specifications
Figure 2: The Echogen Cycle is a compact, high-efficiency solution for exhaust heat to power from large
scale industrial and utility applications including concentrating solar power.
5
corresponding increase in systems packaging complexity for additional inlet and outlet piping
(7, 8). For example, the power turbine for the large-scale Echogen supercritical carbon dioxide
heat engine uses a 0.24-meter (9.5-inch) turbine impeller to produce enough electrical power
for approximately 8,000 homes.
The high density of sCO2 on both sides of a recuperating heat exchanger for service in an
Echogen heat engine permits the use of highly compact, microchannel-based heat exchanger
technology. A comparison of the physical layout and weight for a shell and tube versus a highly
compact heat exchanger of comparable overall heat duty is summarized in Table 2.
Table 2: Comparison of Shell & Tube and Highly Compact HX Technologies
Recuperator Type Dimensions (m) [in] Weight (kg) [lbs]
Shell & Tube 4-shells, 0.25 dia. x 6.09 lg.
[10 dia. X 240 lg.]
7,711
[17,000]
Highly Compact
Microchannel
0.58 x 0.58 x 0.58
[23 x 23 x 13]
969.78
[2,138]
Carbon dioxide also more effectively captures waste heat from sources that have an
approximately constant heat capacity, such as turbine exhaust or other hot gases. This is due
to the character of its heat capacity in the supercritical region which provides superior
matching to the heat source temperature profile compared to the boiling process utilized with
other working fluids such as steam or organic working fluids used in Organic Rankine Cycle
(ORC) systems.
As shown in Figure 4, the so-called pinch point occurs during the constant-temperature phase
change from water into steam which limits the maximum fluid temperature, and resulting cycle
efficiency for steam-based waste heat recovery and power generation technologies. This
Figure 4: Unlike steam (left), supercritical CO2 (right) is a single-phase fluid during heating in the
exhaust heat exchanger resulting in higher fluid temperatures and cycle efficiencies.
6
phenomenon is not encountered in the heat exchange process with supercritical CO2 due to its
single-phase characteristics well above the critical point, which permits a higher fluid
temperature to be achieved for the same heat source. The boiling process in steam systems
limits the maximum fluid temperature and requires multiple pressures (e.g., double and triple-
pressure HRSG systems) to achieve close approach to the exhaust or flue gas temperature. The
Echogen Cycle enables single phase heat transfer resulting in improved heat exchanger
effectiveness while reducing exhaust heat exchanger size and cost (9, 10).
The single phase nature of supercritical CO2 allows for the design of simple, single phase, single
pressure exhaust heat exchangers with low gas-side pressure drop. Due to the superior thermal
stability and non-flammability of CO2, direct heat exchange from high temperature sources is
possible, permitting higher working fluid temperature (and thus higher cycle efficiency). With
proper material selection and heat exchanger design, the sCO2 system is also capable of “dry-
running,” where the main process can operate uninterrupted when the heat recovery system is
not operating, thus eliminating the diverter and bypass stack.
EXEMPLARY SYSTEM TRADE STUDY
Echogen is currently building the EPS100, a 6 to 8+ MWe thermal engine (depending upon the
size of the heat source), which is designed for large industrial, fuel-fired utility and
concentrating solar thermal utility applications. The EPS100 uses supercritical CO2 and
incorporates a patent-pending, advanced power cycle that maximizes utilization of exhaust
thermal energy by reducing the exhaust temperature to a minimum practical limit. The EPS100
thermal engine will be used for the exemplary system trade study.
Heat recovery steam generators
Heat recovery steam generators (HRSGs) are water to steam boilers which capture or recover
waste heat from the exhaust of a combustion turbine, fuel-fired reciprocating engine as a
combined cycle or fuel-fired duct burner to create steam (11). In a combined cycle plant, this
steam is expanded through a turbine for conversion into mechanical, and then electrical power.
HRSGs consist of four major components: evaporator, superheater, economizer and water
preheater. The evaporator consists of banks of tubes are mounted in the exhaust stack where
gases at 427°C to 650°C (800°F to 1,200°F) heat the tubes. Water is pumped and circulated
through the tubes and can be held under high pressure to temperatures of 188°C (370°F) or
higher to produce steam. HRSG's are typically found in combined cycle power plants or at other
steam-intensive industries such as pulp and paper processing and chemical processing.
Numerous suppliers exist globally that offer HRSG hardware and turnkey systems as part of
their larger product offerings in power generation and pollution abatement.
Modular HRSGs are categorized by the number of pressure levels – either single pressure or
multi-pressure. Single pressure HRSGs have only one steam drum and steam is generated at
single pressure. A double-pressure HRSG (DP-HRSG) system consists of a low pressure (LP)
7
section and high pressure (HP) pressure section. Each section has a steam drum and an
evaporator section where water is converted to steam. This steam then passes through
superheaters to further raise the temperature and pressure past the saturation point. The
added complexity of multiple pressure HRSG systems is necessary to achieve higher steam
temperature, and therefore cycle efficiency, due to the “pinch” phenomenon depicted in Figure
3. However, this improvement comes at a significantly increased complexity and cost derived
from the multiple heat exchangers required for the multiple pressure systems.
A comparably sized, double-pressure HRSG will be used in the exemplary trade study because its
performance closely matches the Echogen EPS100 heat engine.
System performance comparisons
The performance of the EPS100 system (power output versus ambient temperature)
significantly exceeds single-pressure steam systems and is comparable to a double-pressure
steam system (Figure 5). All cases shown below for the EPS100 heat engine assume an
evaporatively-cooled system condenser. For most climates, the baseline cycle provides a good
balance of performance. For high ambient temperature climates, especially where water
restrictions are an operating constraint, a high-ambient, fully air-cooled version is under
development. The Echogen system can also increase net power production from heat in gas
turbine exhaust. For example, net power on 20-50 MWe gas turbines can be increased by up to
30%.
Smaller system installation footprint
Due to the compact equipment set and reduced auxiliary support equipment required, sCO2
systems can be installed in a much smaller footprint than can comparable steam-based
Figure 5: Power out versus ambient temperature -- Echogen’s EPS100 heat engine
performance is comparable to a double-pressure heat recovery steam system. The
simple cycle LM2500 gas turbine (SC) is shown for reference.
8
systems. Figure 6 compares the overall site installation for a DP-HRSG versus a sCO2 heat
engine, both sized to produce 8 MWe additional electrical power configured as a bottoming
cycle to a stationary gas turbine. The overall site installation footprint for an Echogen heat
engine to a gas turbine is less than two-thirds of a steam system / HRSG plant.
The EPS100 sCO2 heat engine is delivered on two truck-shippable skids plus an off-skid CO2
storage tank. Footing and foundation requirements are similar to those typically used for
industrial environments. The exhaust heat exchanger is modular, with components that are also
truck-shippable and can be field-erected quickly. The technology is ideal for simple cycle
retrofits due to its small footprint and rapid, flexible installation.
Lower installed and O & M costs
A detailed cost estimate of a fully-installed 6 to 8+
MWe sCO2 system has been compared to a similar
double-pressure steam system (Figure 7) utilizing
GT-PRO/PEACE (12). The lower installed cost is a
function of the simplicity of the sCO2 system, its
smaller footprint, and reduced auxiliary system
requirements. Note that many of the component
costs are based on actual purchased hardware
costs accumulated during the ongoing fabrication
of the prototype 6 to 8+ MWe system (see later
section). Installation costs are based on a study
performed by an independent EPC that has Figure 7: Installed cost per kilowatt for
Echogen EPS100 is up to 40% less
compared to heat recovery steam.
GAS TURBINE / GENERATOR HRSG ECHOGEN EPS100 Figure 6: The Echogen EPS100 heat engine requires a smaller installation footprint compared to a
heat recovery steam system for gas turbine heat recovery.
9
performed numerous small gas turbine simple and combined cycle installations.
The sCO2 power cycle is a compact, closed loop system requiring minimal operational and
maintenance support. Operation and Maintenance (O&M) costs are projected to be
significantly lower for the sCO2 system compared to the steam system. For HRSG systems, a
large com-ponent of O&M cost is water quality and associated chemical treatment for
feedwater supply and condensate return systems which can adversely impact system
availability, hardware reliability and its ability to tolerate peaking (cycling) operation (13-16). By
contrast, CO2 is a clean, non-scaling, non-fouling, and provided it is maintained in a dry
condition, it is non-corrosive with the associated lesser maintenance costs. Consequently, the
number of personnel required to maintain a sCO2 system will be greatly reduced because
technicians will not be needed for water quality and treatment support functions typically
found in a steam-based power plant.
Finally, the growing trend to operate CCGT plants on an as-needed, cyclical basis can cause
severe HRSG hardware damage and premature life due to thermal fatigue and flow-assisted
corrosion in boiler and superheater tube bundles. Cyclical operation can also cause turbine
blade erosion due to water droplet carryover in the low-pressure stage of the condensing
steam turbines which are typically installed with HRSGs for power generation.
Because supercritical CO2 is a single-phase working fluid, it does not require the heat input for
phase change from water to steam and does not create the associated thermal fatigue or
corrosion associated due to two-phase flow within the system components. The compact
equipment set and advanced controls give the EPS100 a fast startup time (approximately 20
minutes to full power), enabling application in peaking duty.
Levelized Cost of Electricity – the key performance metric
Ultimately, the levelized cost of electricity (LCOE) is the most important parameter for
comparison because it appropriately accounts for all equipment, installation and
operating/maintenance costs over the lifetime of the system installation. Based on the
approach described by Can Gulen (17), we have calculated the LCOE for several different
equipment configurations, using a 22 MWe LM2500 stationary gas turbine as the primary
power generator with either a steam or sCO2-based heat recovery system on the turbine
exhaust:
• Simple cycle gas turbine (SC)
• Combined cycle gas turbine (CCGT) with two-pressure HRSG bottoming cycle
and wet-cooling (Steam wet)
• CCGT with two-pressure HRSG bottoming cycle and air (dry) cooling (Steam dry)
10
• CCGT with Echogen EPS100 bottoming cycle and wet cooling (sCO2 wet)
• CCGT with Echogen EPS100 bottoming cycle and dry cooling (sCO2 dry)
The expression for LCOE is:
L𝐶𝑂𝐸 = (𝛽∙𝐶)/(𝑃∙𝐻) + 𝑓/𝜂 + 𝑂𝑀/𝐻 + 𝜇∙𝑂𝑀(𝑣,𝑏)
Where: 𝛽 = Levelized carrying charge factor or cost of money 𝐶 = Total plant cost (USD $) 𝐻 = Annual operating hours 𝑃 = Net rated output (kW) 𝑓 = Levelized fuel cost (USD $/kWh) 𝜂 = Net rated efficiency of the combined-cycle plant (LHV) 𝑂𝑀 = Fixed O&M costs (USD $/kW-yr)
(𝑣,𝑏) = Variable O&M costs for baseload operation (USD $/kWh) 𝜇 = Maintenance cost escalation factor (1.0 for baseload operation)
The levelized carrying charge factor was calculated based on a 4 percent nominal discount rate
(18) as recommended by the US DOE EERE office for 2010-2011, and a 20-year equipment
lifetime. Plant cost was the owners total cost estimated for a US market by GT-PRO/PEACE for
SC and CCGT, and comparable estimates for the sCO2 plant.
To calculate total net rated output (P·H), performance models were run using three different
sets of climate design conditions from the ASHRAE database to represent a range of annual
outdoor conditions typically found in the U.S.: temperate (Akron OH), hot with low relative
humidity (Phoenix, AZ), and hot with high relative humidity (Houston, TX). Two different duty
cycles were also assumed, “baseload” (8,000 hours, 50 start/stop cycles per year), and a once
per day cyclic operation (3,500 hours, 250 start/stop cycles per year). The startup time of each
system was also accounted for by derating the system output during initial operation.
Operation and maintenance costs were calculated based on reduction in personnel costs due to
lower head count required on site, and elimination of boiler feedwater treatment costs.
Periodic top-off of CO2 due to seal and other fugitive leakage was included, but has a minimal
impact on operating costs.
Several models were prepared assuming natural gas fuel costs for the gas turbine ranging from
USD $5.50/MCF to USD $3.50/MCF to better understand the impact of fuel cost on overall plant
performance and resulting LCOE. The modeling results are presented in Figure 8 for baseload
11
operation (8,000 hours per year) and in Figure 9 for peaking (cyclic) operation (3,500 hours per
year, one start/stop cycle per day).
Note that Figures 8 and 9 are for the total plant, including both the gas turbine and sCO2 engine
power outputs and costs. A similar analysis can be undertaken for the sCO2 engine in isolation,
in which only the output and costs are used in the LCOE calculation. In these calculations, the
LCOE of the sCO2 engine ranges from USD $0.019 to 0.031 per kWh for baseload operation, and
USD $0.047 to 0.075 for cyclic operation. In all cases, the incremental power of the sCO2 system
is being produced at a significant discount relative to the output of the gas turbine. In
comparison, the steam-based HRSG LCOE ranges from USD $0.036 to 0.043 for baseload, and
USD $0.105 to $0.126 for cyclic operation. The lower LCOE of the sCO2 system makes for an
economically superior solution for both baseload and cyclic operation (Figure 10).
Figure 8: Baseload operation using an Echogen EPS100 for bottom cycling results in a 10 to 20 percent
LCOE improvement compared to a simple cycle GT or CCGT with a steam bottoming cycle under wet-
cooled conditions, and 4 to 15 percent LCOE improvement for dry-cooled cases.
12
ECHOGEN HEAT ENGINE STATUS
Echogen Power Systems is currently entering the product introduction and customer
demonstration phase of commercialization through several parallel initiatives.
During the AEP test program conducted from April 2010 through April 2011 (Figure 11), eight
turbo-alternator configurations were evaluated (4, 5). Test data was collected to calculate and
compare predicted versus actual isentropic, aerodynamic, fluid power and grid power
performance. In general, actual performance was found to be slightly better than predicted
values (Figure 12). Results were used to define design features for power turbine improvements
which include increasing rated power output from 250
kWe to 400 kWe. Two configurations of new power
turbine hardware are currently in fabrication and will
begin long term endurance testing during the next
deployment of the demonstration system.
The heat engine is currently being installed at Akron
Energy Systems (Akron, OH), a municipal district
heating utility, located close to Echogen’s corporate
offices. Site design was completed by Echogen’s
engineering team during mid-2011. Installation of the
balance of plant hardware is now underway with
system commissioning scheduled for April 2012 (Figure
13). Long term endurance testing will provide the
opportunity to operate the system with supercritical
Figure 10: The lower LCOE of the sCO2 system makes for an economically superior solution for both
baseload and cyclic operation compared to heat recovery steam systems.
High output power + low cost + low O&M cost = low LCOE
• The sCO2 cycle provides a 10 to 20% lower LCOE compared to traditional heat recovery
steam for baseload and cyclic operation
• Lower installed cost for the sCO2 system is due to its smaller system footprint and reduced
balance of plant requirements
• Lower O & M costs for sCO2 are possible because plant personnel are not needed for water
quality and treatment support functions typically found in steam-based plants
• The growing trend to operate CCGT plants on an as-needed basis favors single-phase sCO2
over steam due to no hardware damage and premature life due to thermal fatigue and flow-
assisted corrosion
Figure 11: Initial testing of the Echogen
250 kWe demonstration system was
completed during mid-2011 at the
American Electric Power (AEP) Dolan
Technology Center (Groveport, OH
U.S.A.).
13
CO2 running at ambient operating conditions which will vary with weather and seasonal
changes and with duty cycles similar to what future
commercial systems will experience in customer
installations. Testing will also provide long term
performance data on all system components.
As previously discussed in this paper, the EPS100
system completed detailed design in 2011 and is
currently in fabrication. Initial systems checkout testing
will be conducted at a New York based turbo-
machinery test facility provided by Echogen’s strategic
partner, Dresser-Rand Corporation, and will be installed
at a customer host facility for field testing in 2013.
OTHER sCO2 PROGRAMS
During late 2011, Echogen completed a 6-month, Phase
I SBIR project under contract to the U.S. Navy NAVSEA
Electric Ship Office. The project explored the feasibility
of using Echogen’s thermal engine technology to
improve efficiency and reduce fuel consumption for
marine power generation modules. Study results
indicate that an Echogen heat engine can potentially
reduce fuel consumption for propulsion and service
power turbines by over 20 percent within the
extremely tight packaging volume constraints found on
Naval surface ships. In a related project, Echogen
completed preliminary designs of systems for gas
turbine inlet chilling for power augmentation in which
exhaust heat-driven power generation can produce
significant additional power gains for both marine and
land-based applications. Detailed planning for a follow-
on Phase II prototype design and test program with the
U.S. Navy is currently underway.
In 2011, Echogen, as part of a team led by the Lawrence Berkeley National Laboratory (LBNL),
was notified that they received a USD $5 million, 3-year team award from the U.S. DOE
Geothermal Technology Office (19). Echogen’s USD $3.7 million sub-award will be used to
develop and demonstrate a thermal engine that produces electricity from circulating CO2 in
deep geothermal formations. A side benefit of the circulation of CO2 is that a fraction remains
sequestered within the geological formation. Phase 1 activities are well underway and include
developing the conceptual and preliminary design for the geothermal-driven heat engine.
Figure 12: Measured vs. predicted net
power output for the 250 kWe
demonstration heat engine at AEP.
Figure 13: The 250 kWe heat engine
will begin long term endurance testing
at the Akron Energy Systems district
heating facility (Akron, OH U.S.A)
during 2Q 2012.
14
Program Phases 2 and 3 will involve the detailed design, fabrication, installation and testing of
the heat engine at the SECARB Cranfield Geothermal Field located in Cranfield, MS U.S.A.
Echogen has conducted system design studies to define requirements for sCO2 heat engines
that can operate with full dry cooling for applications where cooling water is not available. The
sCO2 power cycle has the ability to operate totally water-free making it a very attractive
selection as the power block for emerging concentrating solar power (CSP) applications.
CONCLUSIONS
The systems trade study presented shows that sCO2 technology can displace steam for bottom
cycling on gas turbines by providing higher output power with lower installed cost and lower
O&M costs which can reduce LCOE by up to a 10 to 20 percent. Performance of the sCO2 heat
engine for converting heat to power from furnace and flue gas exhaust for large-scale industrial
applications will produce similar savings. In comparison to heat recovery steam generators, the
higher energy density of sCO2 reduces system component size and cost, and provides significant
advantages regarding system efficiency, footprint, and ease of installation. Echogen’s sCO2 heat
engine technology is transformational because it uses CO2 to:
• Generate electricity from useable (waste) heat without burning fuel or producing
resultant emissions
• Reduce reliance on grid delivered power for industrial applications and provide
insulation from fluctuating retail electricity costs
• Offset new energy production with recovered energy, reducing associated greenhouse
emissions by improving overall energy production efficiency
The sCO2 heat engine is a platform technology scalable from 250 kWe to greater than 50 MWe
to support the widest possible variety of industrial and utility scale applications. The Echogen
technology is thermal source agnostic, meaning that it is suitable with a wide range of heat
sources for energy recovery with efficiencies up to 30 percent.
REFERENCES
1) U.S. Energy Information Administration (EIA), International Energy Outlook 2011.
2) BCS, Inc. 2008, “Waste Heat Recovery – Technology and Opportunities in U.S. Industry,”
U.S. DOE Industrial Technologies Program.
3) Anon., “The Industrial Gas Turbine Global Maintenance Market,” Forecast International,
Dec. 2009.
15
4) Echogen Power Systems LLC 2012, Supercritical CO2 Heat Engines for Power Generation –
Combined Cycle Gas Turbine (CCGT) and Concentrating Solar Power (CSP) Useable (Waste) Heat
to Power: Echogen Power Systems LLC.
5) Persichilli, M., Held, T., Hostler, S., and Zdankiewicz, E., “Transforming Waste Heat to
Power through Development of a CO2-Based-Power Cycle,” presented at 16th
International Symposium for Compressor Users and Manufacturers, St. Petersburg, Russia;
08-10 June 2011.
6) Persichilli, M., Held, T., Hostler, S., Zdankiewicz, E., and Klapp, D., “Transforming Waste
Heat to Power through Development of a CO2-Based-Power Cycle,” presented at Electric
Power Expo 2011, Rosemount, IL U.S.A; 10-12 May, 2011.
7) Dostal V., Drsicoll. M., and Hejzlar, P., “A Supercritical Carbon Dioxide Cycle for Next
Generation Nuclear Reactors,” MIT-ANP-TR-100, The MIT Center for Advanced Nuclear
Energy Systems; 10 Mar 2004.
8) Wright, S., “Mighty Mite - A Turbine That Uses Supercritical Carbon Dioxide Can Deliver
Great Power from a Small Package,” Mechanical Engineering, Jan 2012; pp. 40-43.
9) Chen, Y. et.al, “Theoretical Research of Carbon Dioxide Power Cycle Application in
Automobile Industry to Reduce Vehicle’s Fuel Consumption,” Applied Thermal
Engineering, 25 (2005) 2041–2053.
10) Chen, Y., et.al, “Carbon Dioxide Cooling and Power Combined Cycle for Mobile
Applications,” Div. of Applied Thermodynamics and Refrigeration, Dept. of Energy
Technology, Royal Institute of Technology, Brinellvagaegen 60, Stockholm, Sweden.
11) Ganapathy, V., “Heat-Recovery Steam Generators: Understand the Basics,” Chemical
Engineering, Aug 1996, pp. 32-45.
12) GT-PRO/PEACE software; www.thermoflow.com; 2012.
13) Sampson, D., “Fleetwide Standardization of Steam Cycle Chemistry,” Power Magazine;
15 Mar 2006.
14) Cotton, I. and Kolarick, J., “HRSG Water-side Reliability – Design and Operating
Considerations,” PowerGen 94, Dec 1994.
15) Weed, R., “Changing Boiler Water Treatment Needs in High-Pressure Heat Recovery Steam
Generators,” presented at Annual International Water Conference 1999, Pittsburgh, PA;
18- 19 Oct 1999.
16) Starr, F., “Background to the Design of HRSG System and Implications for CCGT Plant
Cycling,” Power Plant Operation Maintenance and Materials Issues (OMMI),Vol. 2 (1).
16
17) Can Gulen, S., “A More Accurate Way to Calculate the Cost of Electricity,” Power
Magazine; 01 Jun 2011.
18) Anon., “NIST Updates Discount Rates for Federal Life-Cycle Cost Analyses,” U.S.
Department of Energy, Energy Efficiency and Renewable Energy (EERE),
http://www1.eere.energy.gov/femp/news; 15 Mar 2010.
19) Progress Release: “Department of Energy Awards More Than $11 Million to Advance
Innovative Geothermal Energy Technologies,” U.S. Department of Energy, Energy
Efficiency and Renewable Energy (EERE), http://apps1.eere.energy.gov/news/progress; 24
Jun 2011.