Presented at Electric Power Expo 2011, 10-12 May, 2011, Rosemount, IL U.S.A.
Transforming Waste Heat to Power
through Development of a CO2 - Based Power Cycle
Michael Persichilli (a), Timothy Held (a), Stephen Hostler (a), Edward Zdankiewicz (a), and David Klapp (b)
(a) Echogen Power Systems LLC
365 Water Street
Akron, OH 44308 U.S.A.
www.echogen.com
(b) American Electric Power (AEP) Co. Inc.
Dolan Technology Center
4001 Bixby Rd.
Groveport, OH 43125 U.S.A.
www.aep.com
Abstract
With global demand for energy expected to increase 60% by 2030, concerns about energy
affordability, security, and greenhouse gas emissions have heightened interest in energy
efficiency and grid demand reduction. In the U.S., legislators are striving to regulate GHG
emissions through market-based mechanisms, efficiency programs, demand reduction, and
economic incentives. Most of the world’s electrical power is generated by heat engines that
convert heat from fuel combustion into mechanical energy which is then converted into
electricity. The U.S. DOE estimates that 280,000 MW discharged annually in the U.S. as waste
heat could be recycled to provide 20% of U.S. electricity needs while slashing GHG by 20% and
saving USD $70-150B per year on energy costs. Various sources of independent data suggest
that this waste heat recovery opportunity is valued at over USD $600B (1). Similar, large
opportunities exist worldwide.
In response to this opportunity, Echogen Power Systems (Akron, OH U.S.A.) is developing power
generation technologies that transform heat from waste and renewable energy sources into
electricity and process heat. The thermal engine technology is based on a waste heat to power
cycle using a supercritical carbon dioxide working fluid in a closed loop. Supercritical carbon
dioxide is environmentally benign, non-toxic, with favorable heat and mass transport properties
that make it energy dense. Compared to organic and steam-based waste heat recovery
systems, supercritical CO2 can achieve high efficiencies over a wide temperature range of heat
sources with compact components resulting in a smaller system footprint.
This paper presents an overview on the Echogen system technology and associated leading
applications. Results are reported on field testing currently underway for an Echogen 250 kW
thermal engine at American Electric Power’s Dolan Research Laboratory.
2
Echogen Heat Engine Technology
Echogen is currently commercializing a waste heat to power system through development of a
proprietary thermal engine, which is entering the product introduction and customer
demonstration phase of development for industrial markets.
The breakthrough thermal engine technology is based on a waste heat to power cycle using
supercritical carbon dioxide (ScCO2) as the working fluid. ScCO2 is environmentally benign, non-
toxic, with favorable heat and mass transport properties. The higher energy density of ScCO2
reduces system component size and cost, and provides significant advantages regarding system
efficiency, footprint, and ease of installation. Our patent-pending thermal engines can
transform significant amounts of waste heat into electricity for applications ranging from
bottom cycling in gas turbines, stationary diesel engine gensets, industrial waste heat recovery,
solar thermal, geothermal, and hybrid alternatives to the internal combustion engine.
Figure 1 is a simplified process flow diagram for
the Echogen heat engine and consists of five
main components: waste heat and recuperator
heat exchangers, condenser, system pump, and
expander. Ancillary components (valves and
sensors) provide system monitoring and control.
Heat energy is introduced through a waste heat
exchanger installed into the exhaust stack for a
turbine, diesel, other reciprocating engine,
boiler, or other industrial heat source. The
heated ScCO2 passes through a turbine where
the waste heat is converted into mechanical
shaft work to produce electricity. A recuperator
recovers a portion of the residual heat while the
remainder is discharged from the system through
a water or air-cooled condenser. Operating
conditions maintain the CO2 in a supercritical condition during the heat recovery and power
generation portion of system cycle, and as a subcooled liquid at the pump inlet. The Echogen
technology can provide integrated power, heating and cooling through a flexible system
architecture which can be configured for power, co-generation or tri-generation.
Over a two-year time period, Echogen successfully advanced its technology from initial concept
to product prototypes. Prototype 1 (5 kW) (2008), based on NASA technology, was an
absorption heat pump using CO2 and carrier fluid, and reduced to practice our approach to
power generation. Prototype 2 (5 kW) (early 2009) utilized pure CO2, proved that a supercritical
cycle heat engine could be built for commercial application, and established a development
pathway for first product units. A 15 kW engineering unit was designed and built in 2009 to
Figure 1: Simplified process flow diagram for
the Echogen heat engine.
3
Figure 2: Carbon dioxide pressure versus
temperature (PT) phase diagram.
initially qualify the CO2 turbine design and scale-up for future commercial-scale systems. Having
achieved the milestone of delivering positive net power output during initial testing, the 15 kW
system currently provides a “wet rig” capability as an engineering lab-based system to enable
quick-turn evaluation of proposed configuration and/or controls changes for field systems
development and optimization.
The Advantages of Supercritical CO2
A key advantage of the Echogen technology is the use of supercritical CO2 as a working fluid for
heat recovery and power generation. A supercritical fluid is a substance at a temperature and
pressure above its critical temperature and pressure. The critical point represents the highest
temperature and pressure at which the substance can exist as a vapor and liquid in equilibrium.
As shown in Figure 2, above its critical point of 87.76°F at 1,070 psi (30.98°C at 73.78 bar),
carbon dioxide is a supercritical fluid and adopts properties midway between a gas and a liquid.
Carbon dioxide as a working fluid for power
generating cycles has many advantages. It is
inexpensive, non-flammable, and abundant in
nature. Due in part to its relative high working
pressure, a carbon dioxide system can be built
that is much more compact than systems using
other working fluids.
The high density and volumetric heat capacity of
CO2 with respect to other working fluids makes it
more energy dense meaning that the size of all
system components can be considerably reduced
without losing performance – including the
turbine, pump, and heat exchangers (2-4). Dostal
(5) compares CO2 turbines to steam-based
turbomachinery and indicates that CO2 turbines
are very compact and highly efficient with
simpler, single casing body designs while steam turbines usually require multiple turbine stages
(i.e., high, medium and low-pressure) and associated casings with a corresponding increase in
systems packaging complexity for additional inlet and outlet piping.
Carbon dioxide more effectively captures waste heat from sources that have an approximately
constant heat capacity, such as turbine exhaust or other gases. This is due to the character of
its heat capacity in the supercritical region which provides superior matching to the heat source
temperature profile compared to the boiling process utilized with other working fluids such as
steam or organic working fluids used in Organic Rankine Cycle (ORC) systems. The so-called
pinch point (see Figure 3) occurs during the constant-temperature phase change of subcritical
fluids, and limits the maximum fluid temperature, and thus cycle efficiency in other waste heat
recovery technologies. This phenomenon is not encountered in the heat exchange process with
4
CO2 due to its single-phase characteristics well above the critical point (6,7), thus permitting a
higher fluid temperature to be achieved for the same heat source.
Technology Comparison
A brief comparison of working fluids currently used commercially for power generation through
heat recovery is shown in Table 1. Unlike steam-based systems that require condensate control
and conditioned water for steam generation to prevent scaling, corrosion and fouling of system
piping and components, CO2 is a clean, non-scaling, non-fouling working fluid, and provided it is
maintained in a dry condition, it is non-corrosive as well. Also, due to the boiling heat exchange
process, a typical steam-based heat recovery system requires multiple stages (e.g. economizer,
boiler and superheater) and multiple pressures to efficiently extract heat from the source.
Effective management of stresses in the large steam drums often is a limiting factor in steam
system design, particularly for cyclic operation. The single-phase heat transfer process of CO2
permits simpler, more robust construction of the waste heat exchanger. Proper management of
the startup process also gives CO2 a much shorter potential heat-up and time to power than
typical steam-based systems.
Table 1: Comparison of Power Generating Cycles for Waste Heat Recovery
Parameter
ECHOGEN
ScCO2 Power Cycle
Organic
Rankine Cycle
Steam
Rankine Cycle
Source Temp Range (F)
400 to greater than 1,200
180 to 550
650+
Figure 3: Comparison of waste heat exchanger operation between a thermal source and different
working fluids shows the advantages of using supercritical CO2 as a working fluid for power
generation from waste heat. Source: derived from Refs. (6, 7).
HEAT SOURCE
WORKING FLUID:
FLUID WITH PHASE
CHANGE
PINCHING
RELATIVE HEAT
ENERGY
TOUT
TC
TIN
TH
HEAT SOURCE
WORKING FLUID:
CARBON DIOXIDE
NO PINCHING
RELATIVE HEAT
ENERGY
TOUT
TC
TIN
TH
Supercritical CO2 recovers waste
heat to a higher temperature
5
Working Fluid
Supercritical
carbon dioxide
HCFC, HFC or
volatile hydrocarbons
Treated water
Working Fluid Attributes
Non-corrosive, not-toxic,
non-flammable,
thermally stable
Limited temperature range,
flammable
Requires treatment to
reduce corrosion & mineral
deposition
ORC heat recovery systems use various hydro-chloro-fluoro-carbon (HCFC) refrigerants such as
R245fa (1,1,1,3,3-pentafluoropropane) and hydro-fluoro-carbons (HFCs), or light hydrocarbons
such as n-pentane and isobutene, or toluene. The HCFC and HFC fluids have limited
temperature capability due to their thermal decomposition to highly reactive hydrochlorides
and hydrofluorides. The high global warming potential of these fluids has led to regulatory
pressure to phase these fluids out of production and use. Hydrocarbon working fluids present
significant flammability hazards. For both classes of fluids, direct heat exchange from a high
temperature source is generally avoided by use of an intermediate heat transfer fluid loop,
which adds significant installation cost to ORC systems. The heat transfer fluids also have upper
temperature limits in the 572 to 662 F (300 to 350 C) range, which limits the maximum working
fluid temperature to lower operating temperatures. For higher temperature applications, the
temperature limit of the heat transfer fluid then requires use of a diverter and bypass stack to
accommodate continued operation of the main process when the heat recovery system is not
operating. Due to the superior thermal stability and non-flammability of CO2, direct heat
exchange from high temperature sources is possible, permitting higher working fluid
temperature (and thus higher cycle efficiency). With proper material selection and heat
exchanger design, the ScCO2 system is also capable of “dry-running,” where the main process
can operate uninterrupted when the heat recovery system is not operating, thus eliminating
the diverter and bypass stack.
Figure 4 compares the power output for a standalone LM2500 power generation turbine
compared to the power output of the LM2500 integrated with various heat recovery
technologies. The analysis was conducted using published performance data for the gas
turbine, the competing waste heat recovery technologies, and an Echogen utility-scale system
currently under development. Modeling results show that compared to steam-based and
Organic Rankine Cycle systems, the Echogen Cycle delivers higher performance, exceeding the
output of single-pressure Heat Recovery Steam Generators by a factor of 1.13 and comparable
ORC systems by a factor of 1.48. The Echogen heat engine technology is a smaller and lower
cost waste heat recovery solution compared to traditional power generation technologies such
as steam turbines, heat recovery steam generators and ORC systems. As a platform technology,
it is easily scalable from 250 kW to greater than 50 MW to support the widest possible variety
of industrial and utility applications. Echogen heat engines are thermal source agnostic,
meaning a wide range of heat sources are suitable for energy conversion to electricity. The
thermal engines work at operating temperatures from 400 F to greater than 1,200 F (204 C to
greater than 650 C) and conditions where other devices cannot operate, enabling a greater
amount of waste energy to be recovered and transformed to electricity or process heat.
6
Field Testing at American Electric Power
As shown in Figure 5, Echogen completed the design and fabrication of a 250 kW system in late
2009, and the system was installed during 2010 at the American Electric Power (AEP) Walnut
Test Facility located in Groveport, OH for beta testing.
The 250 kW system skid measures only 10 x 12 x 20 ft (width x height x length) and weighs less
than 49,000 lbs which allows for highway and truck transport without special Department of
Transportation (DOT) permits. Located within the skid are all of the components previously
described in Figure 1 including the main system pump, recuperator, condenser, system
controller, turbo-alternator and power electronics. For convenience of testing, the flue/exhaust
gas to CO2 waste heat exchanger was replaced by a heat transfer fluid to CO2 heat exchanger. A
slave natural gas-fired system is used to heat and circulate the heat transfer fluid. Water is
supplied to the condenser using a conventional cooling tower and circulation pump.
As part of the AEP Dolan Technology Center, the Walnut Test Facility provides unique research
and testing services for various distributed energy resources. Testing can be conducted on
generation, energy storage, and power quality devices in the 100kW to 1.5MW scale. Previous
testing by others at this AEP facility has included microturbines, fuel cells, advanced batteries,
renewable powered equipment, power electronics, and other related equipment, including
communications, protection and control equipment and components. Devices may be tested
singularly or in combination with other devices and may operate with or without connection to
the electric power grid. Interconnection to the AEP distribution system is through a 13.8 kV tap
Figure 4: System performance model for an Echogen utility scale heat engine integrated to a
LM2500 power generation turbine compared to competing waste heat recovery technologies.
7
point capable of handling devices up to 1.5MVA and is provided with separate bi-directional
metering to distinguish power used by the facility from power that could be exported. The test
site includes a low voltage switchgear, metering and protection, low and medium voltage
transformation, 250 psi nominal natural gas supply, and onsite water supply for cooling and
other needs. Standards based and custom testing are performed using best practices and
protocols developed over the 30-year history at AEP's Dolan Laboratory.
System testing has successfully progressed through several test phases including initial
checkout, shakedown and part load characterization of key system components. During testing,
the 250 kW thermal engine has achieved net power output with 80 days of operation and over
85 turbine starts. In future commercial installations, the actual net system power output from
the 250 kW thermal engine will range between 200 to 300 kW depending on the size and
temperature of the
heat source, and condenser water temperature. Specific tests were conducted to check out
Figure 5: Field testing of the Echogen 250 kW demonstration system ─ (1) the system skid completed factory
assembly and checkout with our systems integration partner, (2) was shipped by truck to the AEP Dolan
Technology Center test site (Groveport, OH), where (3) the system was installed, and (4) has achieved net power
output during field testing in 2010.
(1) (2)
(3) (4)
8
system controls for fully automated start/stop, alarm, shutdown, process adjustment, and
power grid synchronization. Performance data collected during characterization testing
included temperature, pressure and mass flowrate data to calculate heat transfer effectiveness
and pressure drop for all heat exchangers, system pump, turbine, and electrical generation
performance, and measurement of auxiliary loads. Net power has been successfully exported to
the AEP test grid. Test results have been compared to cycle model calculations to verify actual
versus predicted performance. In general, measured system and component performance has
been within expectations. The results of these comparisons have provided confidence in
prediction capabilities for system optimization, off design point operation, and system sizing
and component scale-up for planned multi-megawatt class thermal engines for utility scale
applications.
Testing for the remainder of 2011 will include further system optimization. After test
completion at AEP later this year, the thermal engine is scheduled to be redeployed to a
customer facility for long term durability and reliability tests. For this testing, a finned tube
waste heat exchanger, installed in the customer’s exhaust duct, will be used for heat input to
the cycle.
Conclusion
The Echogen ScCO2 cycle holds great promise in providing a flexible, efficient, low cost system
for waste heat recovery from a wide variety of applications. Initial testing of the 250kW scale
unit has demonstrated that the component and system performance is in line with
expectations. The results of this program have been used to guide the initial design of a multi-
megawatt scale system for use in large industrial and power generation applications.
Acknowledgements
The authors wish to thank Mark Terzola of Echogen for his support, review and constructive
inputs during the preparation of this technical paper.
About the Authors
Michael Persichilli is VP Business Development and Strategic Relationships for Echogen Power
Systems. Mr. Persichilli is a 30-year veteran in the power generation industry. He was formerly
with various operating units of Babcock & Wilcox and Babcock Power Inc. as a senior and
executive manager in a number of positions.
Timothy Held, Ph.D. is VP Engineering for Echogen Power Systems, where he is responsible for
all phases of technology and product development. Prior to joining Echogen in 2008, Dr. Held
was at GE Aviation for 13 years as a manager and technical leader for technology and product
development of gas turbine combustors for aeronautical and stationary power generation
applications.
Stephen Hostler, Ph.D. is a Lead Engineer for Echogen Power Systems. He has been involved
with all aspects in the development of the Echogen power generation technology since 2007.
Dr. Hostler is the Program Manager leading field testing of the 250 kW thermal engine at AEP.
9
Edward Zdankiewicz is a Lead Engineer for Echogen Power Systems. He has been involved with
all aspects in the development of the Echogen power generation technology since 2007. Mr.
Zdankiewicz has over 30 years experience in product and business development for process
systems equipment and controls for international markets involved in regenerative power
generation, water reclamation, environmental monitoring and control.
David Klapp is a Research Engineer at the American Electric Power’s Dolan Technology Center
since 2004. He is also Test Site Manager for the AEP Walnut Test Facility. Mr. Klapp’s research
work includes testing and failure analysis of utility system components and development of
power electronics systems for distributed grid applications. Prior to AEP, Mr. Klapp conducted
research on composite insulators and the detection of dielectric breakdown in power
electronics systems at the Clarkson High Voltage Lab, Clarkson University.
References
(1) Annual Energy Outlook 2010, U.S. Energy Information Administration Office of Integrated
Analysis and Forecasting, U.S. Department of Energy; April 2010.
(2) Petter Nekså et.al, SINTEF Energy Research Refrigeration and Air Conditioning,
Trondheim, Norway, “CO2 Refrigeration, Air Conditioning and Heat Pump Technology”.
(3) Yoshioka, A. et.al, “Development of Automobile Air Conditioning System Using CO2
Refrigerant,” Mitsubishi Heavy Industries Technical Review, v. 37, no. 3, pp. 78 – 82.
(4) Bullock, C. E., “Theoretical Performance of Carbon Dioxide in Subcritical and ASHRAE/NIST
Refrigerants,” Refrigerants for the 21st Century Conference, Gaithersburg, MD, pp. 20 –
26.
(5) Dostal, V., et. al., “A Supercritical Carbon Dioxide Cycle for Next Generation Nuclear
Reactors,” Report No. MIT-ANP-TR-100, MIT Center for Advanced Nuclear Energy
Systems; 10 Mar 2004; pp. 216-223.
(6) Chen, Y. et.al, “Theoretical Research of Carbon Dioxide Power Cycle Application in
Automobile Industry to Reduce Vehicle’s Fuel Consumption,” Applied Thermal
Engineering, 25 (2005) 2041–2053.
(7) Chen, Y., et.al, “Carbon Dioxide Cooling and Power Combined Cycle for Mobile
Applications,” Div. of Applied Thermodynamics and Refrigeration, Dept. of Energy
Technology, Royal Institute of Technology, Brinellvagaegen 60, Stockholm, Sweden.