08 Attachment I Conceptual Design Dwgs
COPPER RIVER SCHOOL DISTRICT KENNY LAKE SCHOOL 2010 WOOD PELLET BOILER PROJECT KENNY LAKE, ALASKA • 768 SF WOOD HEAT BUILDING WITH WOOD PELLET BOILER • 214 LF 2" PEX PRE -INSULATED BURIED HEAT PIPING • HEAT EXCHANGER CONNECTION TO SCHOOL BOILER ROOM PFtG�\G BARROW OCEAN OTZEBUE �J FAIRBANKS GAMBELL KENNY LAKE c ti ANCHORAGE BETHEL JUNEAU HOME EWARD b _ryN�KODIAK OGEP•N ���,�ll m 0 � 9e PROJECT LOCATION In Cooperation with: Copper River School District, Alaska Energy Authority ENGINEERS, INC.4111111110 PO BOX 232946 ANCHORAGE, AK 99523 PH: 907-349-1010 FAX: 907-349-1015 RECORD DRAWING CERTIFICATE THESE DRAWINGS REFLECT RECORDED INFORMATION OBTAINED DURING CONSTRUCTION. INFORMATION PROVIDED HEREIN IS ACCURATE TO THE BEST OF MY KNOWLEDGE. NAME DATE Construction Foreman FINAL DESIGN (Date) ADEC APPROVAL (Date) Construction Period (From) (To) As—Builts (Date) CONCEPTUAL DESIGN SHEET INDEX No. Title COVER SHEET AND SHEET INDEX 11.O...........GENERAL NOTES, LEGEND G1.1...........SITE SURVEY CIVIL DRAWINGS: C1.O...........SITE AND PIPING PLAN C2.0...........PIPING DETAILS ARCHITECTURAL: A1.O...........WOOD HEAT BLDG. - FLOOR PLAN A1.1...........WOOD HEAT BLDG. - ELEVATIONS A1.2........... WOOD HEAT BLDG. - FOUNDATION PLAN AND BUILDING SECTION MECHANICAL DRAWINGS: M1.0........... PROCESS SCHEMATIC Location Map Consultant SCOPE OF PROJECT THIS PROJECT WILL ADD A REMOTELY LOCATED WOOD PELLET FIRED HEATING PLANT TO SERVE THE EXISTING SCHOOL COMPLEX AT THE KENNY LAKE SCHOOL. THE HEATING SYSTEM WILL CONSIST OF A PELLET FIRED BOILER, APPROXIMATELY 1.5 MILLION BTU/HOUR. HEAT TO THE SCHOOL COMPLEX WILL BE DELIVERED WITH BURIED PREINSULATED 4" "PEX" PIPING GENERAL NOTES 1. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND SUBCONTRACTORS TO READ AND BE FAMILIAR WITH THE COMPLETE SET OF DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. VERIFY ALL NOTES, DIMENSIONS, SEQUENCE OF WORK, AND CONSTRAINTS IN PERFORMING THE WORK, NOTIFY ENGINEER OF ANY CONFLICT. ALL QUESTIONS OR CLARIFICATIONS SHALL BE SUBMITTED IN WRITING THROUGH THE GENERAL CONTRACTOR. 2. CONTRACTOR TO INSPECT THE EXISTING SITE AND BUILDING PRIOR TO BID. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL BUILDING PERMITS, LETTERS OF NON -OBJECTION, UTILITY SERVICES (ELECTRICAL AND TELEPHONE) AND APPLICATIONS AS REQUIRED. 3. ALL WORK INCLUDING PLUMBING, ELECTRICAL, AND STRUCTURAL, TO CONFORM TO APPROVED BUILDING CODES AS ADOPTED AND AMENDED BY THE STATE OF ALASKA, AND LOCAL ORDINANCES. 4. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REQUIRED SAFETY PRECAUTIONS, METHODS AND TECHNIQUES. 5. DIMENSIONS TO FACE OF STUD OR CONCRETE, UNLESS OTHERWISE NOTED. 6. ALL ELECTRICAL SYSTEMS, PANELS, WIRING, RECEPTACLES, LIGHTING, SWITCHES AND TRIM SHALL BE COMPLETE AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODES, STANDARDS AND PRACTICES. 7. DEMOLITION WORK MAY NOT BE SHOWN IN ITS ENTIRETY ON THE DRAWINGS, IT IS INTENDED THAT ALL DEMOLITION REQUIRED FOR A TURNKEY PROJECT, WHETHER SHOWN OR NOT, IS INCLUDED. 8. FOR CONSTRUCTION AND MATERIALS DETAILS, SEE SPECIFICATIONS. DESIGN CRITERIA BUILDING DESIGN ROOF SNOW LOAD (Pg) WIND SPEED SEISMIC DATA SOIL BEARING CAPACITY DESIGN TEMP INTERIOR LIVE LOAD 70 PSF 90 MPH (3 SEC GUST, EXPOSURE B, 1=1.25) SITE CLASS D - Sds = 0.83G, Sd1 = 0.43G 1=1.5 R=6.5 3000 PSF -50-F, 125 PSF CODE DATA 2006 IBC OCCUPANCY CLASSIFICATION: F-1 TYPE OF CONSTRUCTION: V-B NON RATED BUILDING AREA: BOILER BUILDING 768 SQ. FT< 8500SQ.FT. TABLE 503 HEAT INDEX: 13.807'F DAYS DISTANCE TO PROPERTY LINE X —> 10', OR OTHER BUILDINGS —>30' FIRE SPRINKLERS: NOT REQUIRED PER 20061BC SEC. 903.2.3 FOR V-B CONSTRUCTION FIRE RESISTANT EXTERIOR WALL NOT REQUIRED, FIRE EXTINGUISHERS: ONE 20A-2-BC @ 75' PER IFC SEC 906.1 PER TABLE 602. LEGEND EXISTING PROPOSED DESCRIPTION WOOD HEAT-SUPPLY/RETURN C-------___] CULVERT — — UGE — — UGE BURIED ELECTRICAL LINE OH OVERHEAD ELECTRIC -0 UTILITY POLE ROADS AND PAD —24 — _ _ —24 CONTOUR LINE pSTRUCTURE --'��---� DITCH LINE DIRECTION OF DRAINAGE --- — — PROPERTY LINE FOUND 2" DIA ALUMINUM CAP ON 5/8" DIA. REBAR. • FOUND 1" DIA. YELLOW PLASTIC CAP ON 5/8" DIA. REBAR SET "SURVEY MARK" NAIL + SET 8" SPIKE W 2 W ❑ LL w Q H ❑ U K OU C/ a W LL W Z Z m K U W O Q H z W z O w N F z O z D ❑ z 3 z0 4 u U K m w _ z0 w z F z U 2 Y Z U 0O o z�o u a �o IQ S 1 j wi '0 1 .,��. a CD z o J W a UJ y O Z LLI W Q Z 2 J LU w Y Q J 0 W z Z W Q z Lu 0 N Ef U LLJ w z cD W m F O m O w rn n a O a O z v � � 6 az o o ❑` a Sheet No. G1.0 S34 s35 74T��A \�� EGG�RSO� N\GHwPY s3 s2 9 m',Ar>a�PPPROXM APPROXIMATE R.O.W. SCHOOL PROPERTY BOUNDARY SCALE 1 "=40' O O 0 20 40 80 120 N GRAPHIC SCALE IN FEET n W w SURVEY CONTROL COORDINATES PT-# NORTHING EASTING ELEV. DESCRIPTOR 1 SOOO.OD 10D00.00 299.45 CP1 2 078.94 10077.99 302.92 CP2 _3 5230.12 1D107.86 298.47 FP3 4 490D52 10024.20 299.60 FP4 5 4628.10 9778.16 308.52 FP5 21 1 0 O O GO Z L Ld m MONUMENT LEGEND O CO FOUND 3 1/4" BLM MONUMENT \ !n DO 0 SET NAIL m ♦ SET 3" "SURVEY MARK" ( ) RECORD DIMENSION BLM LEGEND co METAL LIGHT POLEco Q SANITARY SEWER CLEAN ru w • POWER POLE Q SEPTIC RISER GUY WIRE Q PROPANE GAS BOTTLE 0 SPORTS POST -OHE- OVERHEAD ELECTRIC LIN ti TEST HOLE E❑ ELECTRIC TRANSFORMER ® WATER WELL cL TELEPHONE PEDESTAL O ABOVE GROUND FUEL TANK f YYITREE LINE OUNDER GROUND FUEL TANK EDGE OF GRAVEL ROAD, WP S3 52 T2S R2E 968 RM-05 S RM-02 SRM-03 302.3 WOODS 301.6 VOODS V A WOODS \ \ SHED CP3 F \ DBRARY 1 1 0 OUTHOUSE 299.7 WOODS 1�6/^111 1 '�1 296.4 WOOD BUILDING � OQy I (1 STORY) �O I II \ II UG OF WOODS ) / C, 32 33 34 35 36 - - 31 T. 1 S. MLLOV T. 2 S.At KENNY LAKE 5 4 3 2 1 6 THIS SURVEY o R/fP 8 9 11 12 7 TONSINA 16 15 14 13 18 ® OS U.S.G.S. QUAD VALDEZ (C-3), ALASKA, 1951, SCALE: 1" = 1 MILE MINOR REVISIONS - 1971 VICINITY MAP ' WOOD ATCO / BUILDING �- TRAILERS + 298.4 \ (1 STORY) WOODS \ �p1AE WOODS CpNp, PNO \ 1 (t STD \\ 300.1 PLAYGROUND h EQUIPMENT WOODEN NOTES BOARDWALK 1. PROJECT COORDINATES ARE BASED ON THE ASSUMED VALUES OF CP1. cFtper' PIS + 299.6 COVERED® \ \ / rD1 .q, \ \ 2. PRO ECT BEARINGS ARE BASED ON ELM TOWNSHIP PLAT FOR TOWNSHIP 2 WALKWAY /86B y \ \ SOUTH, RANGE 2 EAST, OF THE COPPER RIVER MERIDIAN. RM-08 \ •9? 9. '\OFF 1 9 \ �b' 3. PROJECT ELEVATIONS ARE BASED ON THE HIGH SCHOOL FINISH FLOOR - 300.5 ICE RINK ELEVATION AT THE NORTH ENTRANCE: 300.5 FEET. I BUILDING DIMENSIONS ARE TO OUTSIDE YS 3.0 OF METAL SIDING. CONCRETE F \ 4. THE CONTOUR INTERVAL IS ONE FOOT. FOUNDATION IS APROX. 0.32• INSIDE. RRMM107A0 bP4 I12 KENNY LAKE \ �j 5. THE INFORMATION SHOWN IS BASED ON A FIELD SURVEY PERFORMED BY R&M 1 HIGH SCHOOL \ \ CONSULTANTS, INC. DURING JANUARY, 1999. (1 STORY) \ 1 \ \ 6. THE SURFACE LOCATION OF THE ABOVE GROUND UTILITY STRUCTURES WERE 1 Ao 1 RM-04 \ \ DETERMINED BY FIELD SURVEY. THE LOCATION OF THE SUB -SURFACE UTILITIES WERE NOT DETERMINED. ADDITIONAL UTILITIES MAY EXIST \ 1 \ \ WTHIN THE MAPPING LIMITS FOR WHICH THERE ARE NO ABOVE GROUND \ 1 \ \ STRUCTURES, RECORD OR AS -BUILT DRAWINGS. T LEGAL DESCRIPTION 1 G \ A parcel of land located within the Chitina Recording District, more particularly described as follows: \ 0 'O 3,0 / S 1/2 of Lot 4, Section 2, Township 2 South, Range 2 East, Copper River \\ .p6 . Meridian, and the SW 1/4 NW 1/4, Section 2, Township 2, Range 2 East, Copper U g0 \ �' �- River Meridian. According to the official plat accepted by the United States Department of the Interior, Bureau of Land Management in Washington, D.C., on December 28, 1970. Subject to the ddescribed in �pNE1-FOAO' _ �OO F`A\N reservations and exceptions as Book 28, Pa 627, 628, 629, in the Chitina Recording District, -' `r¢,+ es and recorded Alaska. Containing 60.00 less. _ rri�P•.•' acres more or ♦ CP2 0111 G i 49 ............:*.1� ��••••••••I : Le L-1. C. Slory • '/ LS 7843 12 SITE SURVEY /\ CIO /\ SURVEYOR'S CERTIFICATE TOPOGRAPHIC AND ASBUILT SURVEY OF TRACK I hereby certify that I am properly Registered and Licensed KENNY LAKE SCHOOL to practice Land Surveying in the State of Alaska, and that LOCATED WITHIN this plan represents a survey made by me or under my direct supervision, and that the monuments shown hereon SEC. 2, T. 2 S., R. 2 E., COPPER RIVER MERIDIAN actually exist as described, and that all dimensions and other details are correct to the extent shown hereon. R&M CONSULTANTS, INC. 9101 Vanguard Drive, Anchorage, Alaska 99507 Lendle C. Story LS 7843 Date DRArm: RHB sI 1"=40' 1 PROJECT: 951023 -D: - CHECKED: LCS FIELD BK: 5-379 #1 1 DATE: 2/18/99 SHEET: 1 OF 1 W 2 W ❑ w 0 > of < Q H ❑ U of UU D D w ILL W z Z . K U W O Q H W w o z w z O W of Q LL r D o ❑ z O z z 4 u F U mDO uu = W O w z 2 F U 2 Y z U o z�o n acj- �o€ b i coi 41�`S # : •0. GAS CD z cn W Q m Q J Q LU w _ (n Q O J W z LZ >o > JU O O N Y Z o W UJ w m w Q m z O w IX rn n a U a 0 z v Ti o 7 G o.z m _ o o o ❑` a Sheet No. G1.1 S -- ------ - ------- 3. 0 �CP4 I Q 0 I I II 9.1 -86.6 FF a 3p�• 5 N KENNY LAKE HIGH SCHOOL 00 � I I � J BUILDING CONNECTION DETAIL SEE l\ G C2.0 / 70.1 \ �G 8.0 0 .� 3.0 O �< 29.0 - 9.0 20.6 C2.0 0 --- BUILDING CONNECTION DETAIL SEE C2.0 59, 7 I I I I I I I I I I I I I � /QC i I I I i I i I I I 1 214 LF BURIED 4" INSULATED HEAT PIPING 214 LF 1" SDR 11 HDPE INSULATED POTABLE WATER LINE 107 LF BURIED ELECTRICAL CONDUIT I� PROPOSED 24X32 WOOD HEAT BUILDING A1.0 PROPOSED 18' DIA WOOD PELLET SILO ---- W Y W ❑ LL W > o � 10 o a a w LL z � Z Z m U W Q W K Z W Z O W N F Z F n ❑ Z 0 z 0 0 W Q� U K W W 2 F z W VF,W 2 O O w Z 2 F U 2 Y 2 Uo �u q �o _moo ilk` z Z � Y 5 co z Q a w d LLJ 2 Y W Q °o z z w o o Y rl z o c/) W2 z w m W a ❑ m o W a � 3 o U O z � v v az o ❑ o a Sheet No. C1.0 6" MINUS, WELL GRADED, GRANULAR COMPACTABLE BACKFILL MATERIAL, WITH LESS NOTE: ALL TRENCHES AND OTHER EXCAVATIONS THAN 20 % PASSING THE #200 SIEVE -SELECTED SHALL BE SLOPED OR SHORED IN ACCORDANCE FROM TRENCH EXCAVATION OR IMPORTED. WITH OSHA STANDARDS. I COMPACT TO 90 % OF MAXIMUM DENSITY o— o— o— o o— 3" WIDE ALUMINUM BACKED DETECTABLE WARNING TAPE, "CAUTION BURIED PIPELINE BELOW", YELLOW WITH 24" MIN o 0 0 0 0 0 o C BLACK LETTERS, BURIED 12" TO 18" BELOW GRADE CENTERED ABOVE PIPE, 0 0 0 0 0 0 o SETON STYLE #85512 OR EQUAL 0 0 0 0 0 VARIES 1 o VARIES O O o -- PIPE BED MATERIAL- SAND 4 MIN. MIN. MIN. %TYPICAL PIPE TRENCH SECTION C2.0 NTS ALIGN ARCTIC BOX WITH WALL STUDS AND SCREW THRU ALUM FRAME TO FASTEN TO BUILDING 4" PEX PIPING INSTALLED THROUGH WALL PENETRATION BRASS 90* ELBOW (FIPT x FIPT) PEX X NPT FITTING - APPROVED BY PEX PIPE MFR. (DO NOT INTERCHANGE OTHER MFR. FITTINGS) COPPER TUBING SYSTEM INSIDE BUILDING FEMALE COPPER SWEAT ADAPTER (C x MIPT) Lill F\ BRASS 90° ELBOW (FIPT x FIPT) PEX X NPT FITTING - APPROVED BY PEX PIPE MFR. (DO NOT INTERCHANGE OTHER MFR. FITTINGS) AFTER CONNECTIONS ARE J COMPLETE FILL ARCTIC II BOX WITH FIBERGLASS BATT AND COVER WITH LID WOOD ARCTIC BOX NOTE: ARCTIC BOX FRAMING AND LID CUT AWAY FOR CLARITY HEAT PIPING CONNECTION WOOD HEAT BUILDING C2.0 SCALE: NTS TO BOILER ROOM NOTE: 1. DETERMINE CORRECT GHS & GHR PIPING. / MARK PIPES ACCORDINGLY. 2. INSULATED PIPES MAY NOT LINE UP EXACTLY AS SHOWN. CONNECT COPPER / TUBE SO GHS OR BOTH LINES MATCH UP. GYM SAME FOR GHR LINES / / / TURN 90" WITH MFR. APPROVED FITTING FOR PEX. INSULATE AND COVER OPEN CORNERS SHEET METAL SHROUD UNISTRUT PIPE CLAMPS 4" PEX TO HEAT BUILDING / 0 \ \ EXISTING EXTERIOR \ 0 C CyR WALL OF HIGH SCHOOL h'S FROM HEAT BUILDING HEAT PIPING CONNECTION THROUGH SCHOOL WALL SCALE:NTS W 2 W ❑ w w Q H ❑ U � oU C a W LL W z Z m K U W 0 Q 0 ww z w z 0 w N F z O z D ❑ z 3 z0 C3 4 u U W W m W m w0 O w z F U 2 Y Z U 0O CD z J Y s m _ cn Q Q Q W w 2 Lu 0 Y C7 o O 0- z O — z rn 0 0 N 0_ w52 da A U R Z o G� LLJ LLJ Z CD Mg Lu m w F Q m O w N a g a O z o _o az _ a o o ❑` a Sheet No. C2.0 SHEAR WALL SCHEDULE WALL DESIGNATION NAILING SPECIFIED OO O 1/2"CDX OR 5/8" T1-11 WITH 8d NAILS @ 6" O.C. © 112" CDX OR 5/8" T1-11 WITH 8d NAILS @ 3" O.C. SHEAR WALL NOTES: 1. NAILING SPECIFIED IS EDGE NAILING, FIELD TO BE NAILED 12" O.C. MIN, PER UBC. 2. NAIL / STAPLE FULL THICKNESS OF SHEATHING 3. WHERE SHEATHING IS APPLIED TO BOTH SIDES OF WALLS WHERE FASTENER SPACING IS LESS THAN 6" O.C., OFFSET PANEL JOINTS TO FALL ON DIFFERENT FRAMING MEMBERS. 4. 14 GA. STAPLES MAY BE SUBSTITUTED FOR 8d NAILS. 5. 7/16" OSB SHTG. and/or 5/8" T1-11 MAY BE SUBSTITUTED FOR 1/2" CD PLYWOOD. 6. BLOCK ALL SHEAR WALL PANEL EDGES. 7. OFFSET DOUBLE TOP PLATE LAP SPLICE FOR EXTERIOR WALLS A MINIMUM OF 48" WITH 8 - 16d NAILS AT CONNECTION. ROOF DIAPHRAGM NOTES: 1. USE 5/8" CDX PLYWOOD WITH 8d NAILS or 14 GA. STAPLES @ 6" O.C. AT BOUNDARIES and 6" O.C. AT OTHER PANEL EDGES. NAIL / STAPLE PANEL FIELDS @ 12" O.C. RIM, SILL, TOP & BOTTOM PLATE NAILING WALL DESIGNATION NAILING SPECIFIED O O O 10d @ 6" O.C. © 10d @ 3" O.C. O O AIR HOOD 24'-0" O O r PLAN FOR BUILDING AND SILO NORTH m O W > W ❑ 2 W > O a F ❑ of UU LL W Z Z m U W Q w 2 o Z w Z 0 W O Z n ❑ Z 3 0 ¢ ui U W W 1� z W m W 2 O O w Z 2 F U 2 Y z ed zi Uo �u m 90 Z. �Ci •'•T� � '•: �1 U Z o Z Y DO JZ -- Z = O W Y Q cf) O 00 > O ZZ z �Q z rn O Y o N LL U Z o C/i Lu LU Z_ CD Lu m 0 m 0 W of N Ua U aU O z � v v rn o az° a o 0 o a Sheet No. A1.0 SOUTH ELEVATION NORTH ELEVATION A2.0A2.0 va° = r-T ELECTRIC SEI ENTR USED ARCTIC ONNECTIONS 3 EAST ELEVATION A2.0 114 V-T a WEST ELEVATION A2.0 1 14„ = t,_o FYP.) W 2 W ❑ w w Q H ❑ U � OU C a w LL W Z Z m K U W O PO: H W K z w z O w N O z D ❑ Z 3 0 U W W Z W m 0 W m O 0 W Z < F U 2 Y Z zi po U ° �1�`S # : •0. GAS CD z Y m to W z Q O a Q W = Q Q Y > Q W 0 J z W z W m O O N Y da U Z L/3 uj uj Z_ CD Mg W m w F Q m o m n a U a o z z _o o.z o o ❑` a Sheet No. A1.1 2X10 VENT BLOCKING BETWEEN TRUSSES, TYP ---------------- R-38 BATT - INSULATION 3 5/8" #4 CONT. 20 GA. x 24" W TYPE 304 SS FLASHING, BENT AS SHOWN 12 14 2 BUILDING SECTION A 1.2 3/8" = r-0" — d a a 3" THICK EXTRUDED POLY. INSULATION, _ a DOW HIGHLOAD 40 OR EQUAL ° 2% S OPE 4'-0" V-4' SIMPSON HDU5-SDS2.5 HOLDOWN (3" MIN. CHORD) w/ SSTB16L ANCHOR BOLT HELD ON FORM w/ AM5/8 ANCHOR BOLT HOLDER AND ABS5/8 ANCHOR BOLT STABILIZER ON FORM, SEE PLAN FOR LOCATIONS 2X8PRESSURE TREATED SILL w/ SILL SEAL METAL ROOFING • ICE AND WATER SHIELD • 5/8" STRUCTURAL SHEATHING • PRE -MANUFACTURED TRUSSES 24" O.C. (9 1/2" HEEL HEIGHT) • METAL SIDING • BUILDING WRAP, TYVEK OR EQUAL • 1/2" CDX PLYWOOD • 2X8 STUDS - 24" O.C. • R-19 BATT INSULATION • 6 MIL VAPOR BARRIER • 1/2" CDX PLYWOOD • FRP (WHITE IN COLOR) FOUNDATION NOTES 1. CONCRETE 3000 PSI, 4" TO 5" SLUMP 2. OVERLAP SPLICES IN REINFORCING STEEL 25" MIN. 3. NATIVE SOIL MUST BE WELL DRAINED GRANULAR GRAVELLY OR SANDY SOIL. REMOVE ALL ORGANICS AND SILT/CLAY AND BACK FILL AS REQUIRED 4. STUD ON FOUNDATION SHOWN FOR CLARITY IN PLACING ANCHOR BOLTS 6" CONC. SLAB ON GRADE w/ #4's @ 15" O.C. EACH WAY ° a 6 MIL POLY FILM ` 1 UNDER SLAB (2) #5's CONT. r 4" GRANULAR BASE COURSE (D-1) UNDER INSULATION AND FOOTING COMPACT SUBGRADE 95% MAX DRY DENSITY, TYPICAL s FOUNDATION DETAIL BENT PL 3/8"x4"x12"x12' w/ WELDED REBAR FINISHED STUDS @ 24" O.C. TIED GRADE TO FND REBAR SLOPED 3" THICK EXTRUDED POLY. INSULATION, — DOW HIGHLOAD 40 OR EQUAL d a a _ — d a FOUNDATION SECTION AT O.H. DOOR A1.2 1" = v-o" 1'-1I" 3'-1" 5'-1 1/2" 12'-0" 1 3 1/2" 4 1/2" ♦ I I — I t — — — — H 1 3- x 72 DOOR r------ 12 _x 9- OVERHEAD DOOR 00 � I I � I ------ - ----1 ---I u-------------- I I 2 I I I I I I I I I I I I I I I I SLOPE _ o I I " 5L 23.5" x 23.5"' REMOVEABLE ---- u I--o- -- ------ PLATE STEEL WITH A 42" PROVIDE ADDITIONAL LONG x 29" WIDE x 28" HIGH #4 REBAR AROUND HOPE "HALF TOTE" SUMP PIT OPENING SUMP PIT, SEE DETAIL BELOW I I I o I I I I II I I I I I I I O I N � I I I I I I I I I I SIMP I I I I I I I I I ON #SSTB16L, 13 5/3' 12-5/8 EMBEDMENT, 1 5/8"0 0'C.P' NO SL NCHORBOLT, BSTITUTIONS I I I I I 00 I I I I I ifl 1 5/8"0 x 12" ZINC COATED STEEL ANCHOR BOLT, 48" O.C. TYP. MAX. (U.N.O.) w/ 5" EXPOSED THREAD, j SIMPSON #BP5/8-2 FLAT WASHER AND 5/8" HEX NUT, TYPICAL I I I I 00 ra --------- ----------------------- ---------------11 4-0— 5/83'-0 4'-04'-02'-04'-04'-0" 24'-0" FOUNDATION PLAN A1.2 318" =1'-o• 2-0., 1'-11 1/2" - • . • 1-1/4" THICK PLATE STEEL) • ° N (REMOVABLE) WITH (8 EA) 1" DRAINAGE HOLES AND A 1" x 3" CENTER SLOT 42" LONG x 29" WIDE x 28" HIGH HDPE "HALF TOTE" 5/8"x1" STEEL BAR WELDED SUMP PIT AROUND CHANNEL FRAME C6x10.5 CHANNEL FRAME w/ (8 EA) 3/4"0 x 6" LONG, ASTM-A449 or A325, BOLTS EQUALLY SPACED AND WELDED TO CHANNEL FRAME THEN WIRE TIED TO SLAB REBAR 5 SUMP PIT DETAIL A1.2 1-1/2" = T-a' d n -10 1/2" 3 1/2" 4 00 N) V -4" 11 5/8" PROVIDE ADDITIONAL #4 REBAR 6" O.C. _ AROUND SUMP PIT OPENING AND WIRE TIE TO GRATE FRAME 1- --- WELDED BOLTS _ud W 2 W ❑ LL W a w ❑ cai m � c� LL w LL W Z Z m m U W O Q H °w w o z w z O W of Q LL aRr o ❑ z O Z D 3 z0 4 u U W W Z W co Eu W 2 O z W z F U 2 Y Z zz m �o S€ ci �1�`S # : •0. GAS CD z Z Q Y Goa0 Z W Q Z�z Q w O W Y QU Q o 0 > O ZZ z �Q z Lu m O Y o 0 N Lt_ U Z o C/3 W LLJ CD Mg W m a ❑ m z o w rn n a U a o z I c az o o ❑` a Sheet No. A1.2 WOOD HEAT BLDG EXISTING SCHOOL I ' BOILER ROOM � � � OE%ISTING I O I EXISTING o L 5 I ' PYROT 400 2 CONTROLS O FREQUENCY DRIVES BURIED INSULATED O I AV_1 HEAT PIPING PUMP i i I HWS HE-1FXISIING GHS J— CP-1A I BUILDING � I I EXISTING HEAT LOADS PUMP I i HWR I GHR-------------f -- CP B � O I � I EXP. TANK PrROT 400 WOOD ---------------- PELLET-FlRED BOILER PROCESS DESCRIPTION II O1 HEAT SOURCE. II `------------------------ A WOOD PELLET BOILER OF ADVANCED DESIGN WILL PROVIDE BETWEEN 340,000 AND 1.33 MILLION BTU/HOUR OF HEAT TO A PRESSURIZED GLYCOL HYDRONIC LOOP. THE BOILER WILL BE AUTOMATICALLY STOKED FROM A 50-TON SILO LOCATED OUT THE WOOD HEAT BUILDING. THE BOILER HAS AN AUTOMATIC ASH COLLECTION THAT FEEDS INTO A BIN FOR EASY REMOVAL. AIR NOZZLES PERIODICALLY BLOW PARTICULATES OUT OF THE FIRE TUBES TO MINIMIZE MAINTENANCE. A MULTI -CYCLONE AND EXHAUST FAN REMOVE PARTICULATE MATTER OUT OF THE EXHAUST STREAM TO MINIMIZE POLLUTION OUTSIDE. O AIR SEPARATION. AN AIR SEPARATOR ELIMINATES AIR BUBBLES FROM THE HYDRONIC PIPING AND ACTS AS A STRAINER, CATCHING PARTICLES CIRCULATING IN THE HYDRONIC LOOP. O3 CIRCULATING PUMPS. A PRIMARY PUMP CIRCULATES UP TO 170 GPM THROUGH THE HYDRONIC LOOP TO THE HEAT EXCHANGER AT THE SCHOOL. A SECONDARY PUMP SERVES AS A BACKUP. THE PUMPS ARE CONTROLLED BY VARIABLE FREQUENCY DRIVES THAT VARY THE SPEED OF THE PUMPS, BASED UPON RETURN TEMPERATURE BACK TO THE BOILER. ® EXPANSION TANK. EXPANSION TANK ET-1 ACCOMMODATES THE EXPANSION OF THE GLYCOL HEAT TRANSFER FLUID, AS ITS TEMPERATURE RISES AND FALLS. O5 HEAT PIPING BETWEEN BUILDINGS. TWO BURIED AND INSULATED 4-IN PEX PIPES CONNECT THE WOOD PELLET BOILER GLYCOL LOOP TO THE SCHOOL HEAT SYSTEM. © HEAT EXCHANGER. A PLATE AND FRAME HEAT EXCHANGER SERVES TO SEPARATE THE TWO GLYCOL HEATING LOOPS (WOOD -PELLET BOILER GLYCOL LOOP AND SCHOOL HYDRONIC HEATING SYSTEM). THIS IS DONE TO PROTECT THE BUILDING FROM A FAILURE OF THE WOOD PELLET BOILER GLYCOL PIPING THAT COULD DRAIN OUT THE SCHOOL HYDRONIC HEATING PIPING. THE HEAT EXCHANGER TRANSFERS THE HEAT BUT KEEPS THE TWO FLUIDS SEPARATE. THE BUILDING SIDE OF THE HEAT EXCHANGER IS CONNECTED TO THE RETURN SIDE OF THE BUILDING HYDRONIC PIPING THAT FEEDS INTO THE BOILERS. IF THE HEAT TRANSFERRED TO THE BUILDING RETURN SIDE STAYS AT 180F, THEN THE BOILERS WILL NOT COME ON. IF THE TEMPERATURE GOES BELOW 170F, THEN THE BOILERS START UP AUTOMATICALLY. O BUILDING HEATING SYSTEM. THE EXISTING BUILDING HEATING SYSTEM CONSISTS OF THE TWO BUILDING BOILERS (2.1 MILLION BTU EACH), CIRCULATING PUMPS, PIPING, AND BUILDING HEAT LOADS. THIS SYSTEM OPERATES NORMALLY, WITH OR WITHOUT THE WOOD PELLET BOILER SYSTEM. W 2 W ❑ w w Q H ❑ U � OU C a w LL W Z Z m K U W O Q H W w z W z O w of z � O z D ❑ z 3 0 2 4 ui U K z W w z F U 2 Y Z �l i IIV�••. a : • � o Ij b'•.. i ,E• 1'Q�� CD z Y Go to U a Q W Q Q W w = Q Q J 0 O z z w rn 0 0 N Y U Z L/3 ui uj Z_ Lu m w 0 m o rn n a O a o z z v � � 6 az o o ❑` a Sheet No. M1.0