iUMPBACK CREEK HYDROEL ECTRIC PROJECT (FERC No. 8889)
INTAKE / DIVERSION FACILITIES REHABILITATION
0
" ! ,Fairbanks
Kodiak
PROJECT
G� LOCATION
Gulf Of
Alaska
REVIEWED
DISCIPDNE
icen
h
PROJECT SITE
(DWG C-01)
c
�jIF
CORDOVA
A '19 SEP 08I ISSUED FOR REVIEW
REV. (DATE I NATURE OF REVISION
BY I CHKD. I APPD.
HUMPBACK CREEK
HUMPBACK CREEK
WATERSHED
HUMPBACK CREEK PROJECT �REHABILITATIONI�
FERC-8889 CEC-OS-HBC-02
COVER SHEET AND
LOCATION MAPS
o � �� o HARH Aces
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507 The Energy Company
907 522 1707 voice • 907 522 3404 fax 9Y
DATE DWG NO,
ANCHORAGE, ALASKA 04/01/08
CEC DWG, N0. XXX-X-XX-xxxx-XXX
8889-XX
s
o_
0
0
0
o_
ti
0
a
�:, ,
DSGN.
CHKD.
CML
OWN.
'.. CHKD. IAECH.
I sueM. ��•
�.TlIXAi9al:rdda;i
REVIEWED
DWG N0.
c-o1
G-02
G-03
C—01
C-02
C-03
C-04
C—OS
C-06
C-07
C-08
S-01
S-02
S-03
S-04
S-05
S—O6
CEC N0.
xx
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
DRAWING TITLE
COVER SHEET AND LOCATION MAPS
DRAWING INDEX
GENERAL NOTES
SITE PLAN
PLAN AND PROFILE
LEFT ABUTMENT STABILIZATION, PLAN AND SECTIONS
INTAKE DIVERSION, EXCAVATION PLAN
PENSTOCK AND TUNNEL, PLAN (SHEET
1 OF 4)
PENSTOCK AND TUNNEL, PLAN (SHEET
2 OF 4)
PENSTOCK AND TUNNEL, PLAN (SHEET
3 OF 4)
PENSTOCK AND TUNNEL, PLAN (SHEET
4 OF 4)
INTAKE/DIVERSION CONCRETE OUTLINE,
PLANS
DIVERSION DAM, SECTIONS AND DETAILS
DIVERSION DAM, SECTIONS AND DETAILS
INTAKE/DIVERSION CONCRETE OUTLINE,
PLAN EL. 276
INTAKE CONCRETE OUTLINE, SECTION
INTAKE CONCRETE OUTLINE, SECTIONS
S-07*
XX
DIVERSION CONCRETE
REINFORCING, PLAN
AND
SECTIONS
5-08*
XX
DIVERSION
CONCRETE
REINFORCING, SECTION AND DETAILS
S-09*
XX
INTAKE
REINFORCING,
PLAN (SHEET 1 OF
2)
S-10*
XX
INTAKE
REINFORCING,
PLAN (SHEET 2 OF
2)
S-11*
XX
INTAKE
REINFORCING,
SECTIONS (SHEEP 1
OF
3)
S-12*
XX
INTAKE
REINFORCING,
SECTIONS (SHEEP 2
OF
3)
5-13*
XX
INTAKE
REINFORCING,
SECTIONS (SHEET 3
OF
3)
S-14*
XX
INTAKE
CONCRETE REINFORCING,
SECTIONS
AND DETAILS
S-15
XX
PENSTOCK,
ELEVATION (SHEET 1
OF 2)
S-16
XX
PENSTOCK,
ELEVATION (SHEET 2
OF 2)
*
NOT INCLUDED
FOR REVIEW
10 SEPT 08
JpN K YAaEE �
G �'. CE 10a4 .' •qi
'1'•e _ .... � yr
DISCIPLJNE
LEAD
DWG N0. CEC N0.
DRAWING TITLE
S-17*
XX
PENSTOCK, SECTION AND DETAILS
5-18*
XX
THRUST BLOCKS PLANS, SECTIONS, DETAILS
S-19*
XX
OUTLET PORTAL, PLAN AND SECTIONS
5-20*
XX
OUTLET PORTAL, SECTIONS AND DETAILS
5-21*
XX
INTAKE — MISC STEEL PLAN, SECTIONS, AND DETAILS
S-22*
XX
INTAKE — MISC STEEL PLAN, SECTIONS, AND DETAILS
5-23*
XX
INTAKE — MISC STEEL PLAN, SECTIONS, AND DETAILS
5-24*
XX
OUTLET PORTAL — MISC STEEL PLAN, SECTIONS, AND DETAILS
E-1*
XX
OVERALL PLAN, LEGEND
E-2*
XX
POWERHOUSE SITE PLAN
E-3*
XX
PENSTOCK PLAN
E-4*
XX
TUNNEL PLAN
E-5*
XX
INTAKE SITE PLAN
E-6*
XX
POWERHOUSE PLAN
E-7*
XX
INTAKE STRUCTURE PLAN
E-8*
XX
GATE PLAN
E-9*
XX
PENSTOCK, THRUST BLOCK DETAILS
E-10*
XX
POWER ONE LINE DIAGRAM
E-11*
XX
MONITOR/CONTROL POINTS LIST
M-1*
XX
EXTERIOR SLUICE GATE PLANS, SECTION AND DETAILS
M-2*
XX
INTERIOR SLUICE GATE PLANS, SECTION AND DETAILS
M-3*
XX
PENSTOCK INLET CLOSURE GATE PLAN, SECTION AND DETAILS
M-4*
XX
PENSTOCK EMERGENCY CLOSURE VALVE PLAN, SECTIONS AND DETAILS
M-5*
XX
OVERFLOW SPILLWAY GATE PLAN, SECTION AND DETAILS
M-6*
XX
OVERFLOW SPILLWAY GATE, SECTION AND DETAILS
M-7*
XX
JIB CRANE
M-8*
XX
INTAKE STRUCTURE HEATING /VENTILATION PLAN
M-9*
XX
TUNNEL VENTILATION PLAN
M-10*
XX
SCHEDULES, SECTIONS AND DETAILS
* NOT INCLUDED FOR REVIEW 10 SEPT 08
� i�L�CIILIi'
HUMPBACK CREEK PROJECT INTAKE/DIVERSION
FERC-8889 ^REHABILITATION ^
DRAWING INDEX
R&M CONSULTANTS, INC. I1fIIUII NUiILiI
9101 Vanguard Drive
Anchorage, Alaska 99507 The Ener COm 00
907 522 1707 voice • 907 522 3404 fax 9Y P %
DATE DWG ND.
ANCHORAGE, ALASKA 04/01/08 G — O Z
A 10 SEP OB ISSUED FOR REVIEW ,
REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX�X-XX-XXXX-XXX
GENERAL
• FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND SLOPE
• PROVIDE WEATHER PROTECTION DURING CONSTRUCTION TO PREVENT DAMAGE TO
STOCKPILED MATERIALS AND NEW CONSTRUCTION
• PROTECT EXISTING STRUCTURES AND ABURTANCES FROM DAMAGE DURING
CONSTRUCTION.
• REPORT TO THE OWNER UNSOUND STRUCTURAL OR GEOTECHNICAL CONDITIONS IF
THEY ARE OBSERVED OR CREATED DURING CONSTRUCTION.
• IMMEDIATELY REPORT TO OWNER'S REPRESENTATIVE CONDITIONS THAT VARY FROM
THOSE SHOWN ON THE DRAWINGS.
• COORDINATE WORK PLANS WITH OWNER'S REPRESENTATIVE.
• ASSUMED CONCRETE DENSITY: 150 POE
• ASSUMED STEEL DENSITY: 490 POE
• DESIGN LIVE LOAD ON INTAKE SLABS: 250 PST
• DESIGN POINT LOAD ON INTAKE SLABS: 6,500 LB
CONCRETE
Of. EXECUTE CONCRETE CONSTRUCTION AND CONCRETE TESTING IN FULL
ACCORDANCE WITH THE LATEST EDITIONS OF ACI AND ASTM SPECIFIED
REFERENCE STANDARDS
C2. DIVERSION DAM AND THRUST BLOCK CONCRETE: PROVIDE CONCRETE MIX MEETING THE FOLLOWING
REQUIREMENTS:
MIX A
• MIN PORTLAND CEMENT CONTENT (LB / CY OF CONC):
• MIN FLY ASH CONTENT (% CEMENTATION MATERIAL):
• MAX FLY ASH CONTENT (% CEMENTATION MATERIAL):
• TOTAL AIR CONTENT (%): _____
• WATER / CEMENT RATIO: _ __
• COARSE AGGREGATE ASTM C33 NO.
• MIN 56-DAY COMPRESSIVE STRENGTH (PSI): 3,000 PSI
GROUT
<<To be written based on specifications>>
REINFORCING STEEL FOR CONCRETE
R1.
R2.
R3.
R4.
R5.
R6.
MIX B
• MIN PORTLAND CEMENT CONTENT (LB / CY OF CONC): - - -
• MIN FLY ASH CONTENT (% CEMENTATION MATERIAL): __
• MAX FLY ASH CONTENT (% CEMENTATION MATERIAL): _ ---
• TOTAL AIR CONTENT (%): _____
• WATER / CEMENT RATIO: R7.
• COARSE AGGREGATE ASTM C33 NO.
• MIN 56-DAY COMPRESSIVE STRENGTH (PSI): 3,000 PSI
C3. INTAKE AND OUTLET STRUCTURE CONCRETE: PROVIDE CONCRETE MIX MEETING THE FOLLOWING
REQUIREMENTS:
• MIN PORTLAND CEMENT CONTENT (LB / CY OF CONC): - - -
• MIN FLY ASH CONTENT (% CEMENTATION MATERIAL): _ __
• MAX FLY ASH CONTENT (% CEMENTATION MATERIAL): -----
TOTAL AIR CONTENT (%): - -
• WATER / CEMENT RAT10: _ __
• COARSE AGGREGATE ASTM C33 NO.
• MIN 28-DAY COMPRESSIVE STRENGTH (PSI): 4,000 PSI
C4. MATERIALS FOR BEARING PAD CONCRETE
• CEMENT GROUT: MASTER FLOW 928 GROUT AS MANUFACTURED BY MASTER BUILDERS, INC.
• COURSE AGGREGATE: MAXIMUM AGGREGATE SIZE 3/8", WASHED CLEAN OF FINES, MEETING
• ASTM C 33' GRADING SIZE NO. 8.
• WATER: CLEAN, CLEAR, POTABLE AND NOT CONTAINING SUBSTANCES THAT CAUSE DISCOLORATION,
ODOR, AND UNUSUAL TASTE.
• MIX PROPORTIONS: ONE 55 LB BAG CEMENT GROUT MIXED WITH 25 LB. OF COURSE AGGREGATE
(DRY WEIGHT). WATER MIX QUANTITY ACCORDING TO MANUFACTURER'S RECOMMENDATIONS TO
ACHIEVE REQUIRED STRENGTH GAIN AND WORKABILITY.
• REQUIRED STRENGTH: COMPRESSIVE STRENGTH AT 3 DAYS: 3,000 PSI MINIMUM. COMPRESSIVE
• STRENGTH AT 28 DAYS: 6,000 PSI MINIMUM.
• AIR CONTENT: 5 TO 8%
C5. MIXING AND PLACEMENT OF BEARING PAD CONCRETE
• BEARING PAD CONCRETE SHALL BE MIXED TO A PLASTIC CONSISTENCY AND THE SLUMP SHALL NOT
EXCEED 6 INCH SLUMP MEASURED WITH A STANDARD SLUMP CONE. BEARING PAD CONCRETE WITH
EXCESS SLUMP MAY BE REJECTED BY THE ENGINEER. BEARING PAD CONCRETE REJECTED FOR
EXCESSIVE SLUMP SHALL BE IMMEDIATELY DISPOSED AT AN AREA INDICATED BY THE ENGINEER.
• BEARING PAD CONCRETE SHALL BE CONVEYED TO PLACE OF FINAL DEPOSIT BY METHODS THAT WILL
NOT CAUSE SEPARATION OR LOSS OF MATERIAL.
• BEARING PAD CONCRETE SHALL BE DEPOSITED IN OR CLOSE TO ITS FINAL POSITION; SEGREGATION
DUE TO RE -HANDLING OR FLOWING SHALL BE AVOIDED.
• BEARING PAD CONCRETE SHALL BE THOROUGHLY VIBRATED. VIBRATORS SHALL NOT BE HELD
AGAINST EMBEDDED MATERIAL. TOP SURFACES SHALL BE CHAMFERED DURING PLACEMENT.
• BEARING PAD CONCRETE SHALL NOT BE DROPPED AT A DISTANCE OF MORE THAN 3 FEET, AND
SHALL NOT BE DEPOSITED AS A LARGE QUANTITY AT ANY POINT. RUNNING OR WORKING THE
BEARING PAD CONCRETE SHALL NOT BE PERMITTED ALONG THE EDGE OF THE FORMS.
• BEARING PAD CONCRETE SHALL BE THOROUGHLY WORKED AROUND REINFORCEMENT AND EMBEDDED
ITEMS, AND INTO CORNERS OF FORMS BY EFFECTIVE VIBRATION. VIBRATORS SHALL PENETRATE EACH
LAYER AND INTO THE TOP OF THE UNDERLYING LAYER.
• SECURELY ANCHOR EMBEDDED ITEMS AND RESTRAIN THEM FROM FLOTATION OR MOVEMENT DURING
PLACEMENT OF BEARING PAD CONCRETE.
• INSTALL 3" PVC PIPES AROUND ANCHORS AND CAULK TO PREVENT CONCRETE FROM FLOWING INTO
PT ANCHOR HOLES.
• BEARING PAD CONCRETE SHALL NOT BE PLACED UNDERWATER NOR USED TO DISPLACE WATER
EXCEPT AS APPROVED BY THE ENGINEER.
DIVERSION AND CARE OF WATER
D.1 INTAKE CONSTRUCTION
<<To be written based on specifications>>
D.2 DIVERSION DAM CONSTRUCTION
<<To be written based on specifications>>
EXCAVATION AND SLOPE STABILIZATION
E1. LEFT ABUTMENT STABILIZATION
• ESTIMATED VOLUME OF MATERIAL TO REMOVE: CY
• FOLLOW REVIEWED EXCAVATION AND STABILIZATION PLAN
E2. INTAKE EXCAVATION AND STABILIZATION
• ESTIMATED VOLUME OF MATERIAL TO REMOVE: ___ CY
3 FOLLOW SUBMITTED AND OWNER REVIEWED EXCAVATION AND STABILIZATION
PROCEDURES
E3. DIVERSION DAM EXCAVATION
E ESTIMATED VOLUME OF MATERIAL TO REMOVE: __ CY
• FOLLOW SUBMITTED AND OWNER REVIEWED EXCAVATION AND STABIIZATION
a ROCEDURES
n
APPROVED: y\
0F 4(gS1'
b jDSGN. REVIEWED /...:.................i..DISCIPICML>':Lnw w M `j LEN MECH. 1� also ,po....• Eo ELECT•
o PROJECT MANAGER:
E
PROVIDE REINFORCING STEEL BARS FOR INTAKE/DIVERSION STRUCTURE.
INCLUDE 2 COMPONENT EPDXY ADHESIVE, WIRE TIES AND ACCESSORIES.
MATERIALS:
a. REINFORCING BARS: ASTM A615, GRADE 60, DEFORMED, NEW BILLET -STEEL.
b. CHAIRS, HANGERS, SPACERS AND OTHER SUPPORTS FOR REINFORCING BARS:
CONCRETE, METAL OR OTHER APPROVED MATERIAL.
FABRICATE IN ACCORDANCE WITH ACI 315.
PLACEMENT:
a. FURNISH AT FULL LENGTH TO THE EXTENT PRACTICAL.
b. SPLICE ONLY AT LOCATIONS SHOWN ON APPROVED SHOP DRAWINGS OR
AS OTHERWISE PERMITTED BY OWNER.
c. PLACE ACCORDING TO DIMENSIONS AT CENTERLINE, UNLESS OTHERWISE PRESCRIBED.
d. INSPECTION BY ENGINEER AS TO SIZE, SHAPE, LENGTH, SPLICING, POSITION AND
QUANTITY, SHALL BE CARRIED OUT PRIOR TO CONCRETE PLACEMENT.
e. ACCURATELY PLACE REINFORCING AND SECURE IN POSITION TO PREVENT
DISPLACEMENT
DURING PLACEMENT OF CONCRETE.
E DO NOT DISTURB IN PREVIOUSLY PLACED CONCRETE.
g. UNLESS OTHERWISE SHOWN OR DIRECTED, REINFORCING BARS SHALL BE PLACED
NO CLOSER THAN 1 INCH OF CLEAR SPACE FROM ANCHOR BOLTS, FORM TIES, OR
OTHE EMBEDDED METAL WORK.
h. CONCRETE SUPPORTS FOR REINFORCING BARS SHALL NOT BE USED WHERE SUCH
SUPPORTS
ARE EXPOSED AT SURFACES OF CONCRETE.
i. IMMEDIATELY BEFORE REINFORCEMENT IS EMBEDDED IN CONCRETE, CLEAN THE
SURFACES OF BAR AND BAR SUPPORTS OF HEAVY FLAKY RUST, LOOSE MILL SCALE,
DIRT, GREASE, OR OTHER FOREIGN SUBSTANCES. HEAVY FLAKY RUST THAT CAN BE
REMOVED BY FIRM RUBBING WITH BURLAP OR EQUIVALENT TREATMENT, SHALL BE
CONSIDERED OBJECTIONABLE.
TOLERANCE
1. REINFORCING BARS TO TOLERANCES SPECIFIED BELOW:
a. VARIATION OF PROTECTIVE COVERING:
WITH COVER OF 2-1/2 INCHES OR LESS 1/4-INCH
WITH COVER OF MORE THAN 2-1/2 INCHES 1/2-INCH
b. VARIATION FROM INDICATED SPACING: 1-INCH
ANCHOR BAR AND DOWELS INSTALLATION
a. REINFORCING STEEL FOR ANCHOR BARS OR DOWELS SHALL BE PROVIDED WITH
STANDARD HOOK
GEOMETRY PER ACI 318.
b. HOLES FOR ANCHOR BARS OR DOWEL INSTALLATION SHALL BE DRILLED AT A
DIAMETER 1/8-INC GREATER THAN THE ANCHOR DIAMETER. HOLES SHALL BE DRILLED
OR ROUGHENED WITH PERCUSSION DRILL.
a HOLES SHALL BE CLEANED WITH COMPRESSED AIR, BRUSHED WITH WIRE BRUSH, AND
CLEANED AGAI WITH COMPRESSED AIR. HOLES SHALL BE CLEANED AND SOUND AND
FREE OF STANDING WATER OR FROST HOLES MAY BE DAMP.
d. HOLES SHALL BE FILLED APPROXIMATELY HALF WAY WITH TWO -COMPONENT EPDXY
ADHESIVE. HOLES SHALL BE FILLED FROM THE REAR OF THE HOLE SLOWLY
WITHDRAWING THE STATIC MIXING NOZZLE TO AVOID CREATING AIR POCKETS.
e. ANCHOR BAR SHALL BE PUSHED INTO HOLE WHILE TURNING IT SLIGHTLY TO INSURE
POSITIVE DISTRIBUTION OF ADHESIVE. THE ANCHOR SHALL BE CONFIRMED TO BE FULLY
SEATED AT THE BOTTOM OF THE HOLE AND SOME ADHESIVE WILL FLOW FROM THE
TOP OF THE HOLE.
f. TWO -COMPONENT EPDXY ADHESIVE SHALL BE ALLOWED TO CURE FOR TIME SPECIFIED
BY THE ADHESIV MANUFACTURER PRIOR TO APPLYING ANY LOAD.
STRUCTURAL STEEL
S1. Materials shall meet the following grades/specifications:
• STRUCTURAL STEEL SHAPESGRADE 50, ASTM A572
• STRUCTURAL STEEL PLATESGRADE 50, ASTM A57
• STRUCTURAL STEEL PINS GRADE 50, ASTM A58
• STRUCTURAL TUBINGASTM A53
• BOLTS FOR STRUCTURAL STEEL CONNECTIONSHIGH STRENGTH GRADE, ASTM A325 GALVANIZED)
• NUTSASTM A563 (GALVANIZED
• WASHERSASTM F435, TYPE 1 (GALVANIZED
• WELDING ELECTRODESE70XX SERIES OF AWS SPECIFICATION A5.1 OR A5.5 UNLESS NOTED OTHERWISE
S2. PROVIDE HOT -DIP GALVANIZED STRUCTURAL STEEL AS NOTED
• CONTRACTOR -FURNISHED FERROUS METAL ITEMS SHALL BE GALVAIZED AS NOTED.
• PERFORM GALVANIZING IN ACCORDNACE WITH ASTM A385 AND ASTM A53 WITH MINIMUM OF 2 OUNCES
PER SQUARE FOOT OF SURFACE.
• MINIMIZE DISTORTION AND TWISTING OF MEMBERS DURING GALVANIZING IN ACCORDANCE WITH ASTM
A384.
S3. GALVANIZING REPAIR PAINT: HIGH ZINC DUST CONTENT PAINT FOR REGALVAIZING WELDS IN GALVANIZED
STEEL. PROVIDE PRODUCT MEETING MILITARY SPECIFICATIONS MIL-P-21035 (SHIPS).
S4. ERECTION OF STRUCTURAL STEEL.
• METAL FABRICATIONS SHALL BE PLACED ACCURATELY 0.
• CONNECTIONS SHALL FIT ACCURATELY TOGETHER 0
ANCHOR BOLTS
DRILLED IN
CONCRETE
EXPANSION ANCHORS (EXP ANC)
ANCHORSALL
MINIMUM EMBEDMENT ONO;
HAVIT
HILL FULLILIWINL, MINIMUM
DIAMETER
EMBEDMENT
ALLOWABLE TENSION
ALLOWABLE SHEAER
3 �'
1,290 LB
1,291 LB
4'
2,075 LB
2,169 LB
4
2,185 LB
3,524 LB
g
5 g
3,075 LB
6,040 LB
11
6.
3,455 LB
7,000 LB
VALUES SHOWN ARE FOR
INSTALLED WITH SPECIAL
INSTALLED WITH MINIMUM
OTHERWISE ON THE DRAWINGS
INSTALLATION WITH SPECIAL INSPECTION ALL EXP ANC SHALL BE
INSPECTION UNLESS NOTED OTHERWISE ANCHORS SHALL BE
SPACING FOR FULLY EFFECTIVE CAPACITY UNLESS NOTED
PROVIDE ALL S.S. ANCHORS UND.
ADHESIVE ANCHORS (ADH ANC)
ADHESIVE ANCHORS SHALL BE THREADED AISI 304 SS AND SHALL HAVE THE FOLLOWING
MINIMUM CAPACITIES AND MINIMUM EMBEDMENT UND;
DIAMETER
EMBEDMENT
ALLOWABLE TENSION
ALLOWABLE
SHEAER
°
3°
2,540 LB
1,875
LB
°
4
3,690 LB
3,335
LB
a°
5 a'
4,920 LB
4,685
LB
6
8,330LB
6,385
LB
7
10,250 LB
8,690
LB
1'
9'
10,910 LB
11,350
LB
INSTALLATION OF ADHESIVE ANCHORS REQUIRES SPECIAL INSPECTION CONSISTENT WITH ICBO
REPORT FOR SELECTED PRODUCT A➢HESIVE ANCHORS SHALL NET BE USED IN FIRE
RESISTIVE CONSTRUCTION. ANCHORS SHALL BE INSTALLED WITH MINIMUM SPACING FOR FULLY
EFFECTIVE CAPACITY UNLESS NOTED OTHERWISE ON THE DRAWINGS PROVIDE ALL SS.
ANCHORS UNIT,
SUBMITTALS
<<to be edited based on specifications.>>
SB I.
THE CONTRACTOR SHALL SUBMIT THE FOLLOWING FOR APPROVAL BY THE DESIGN ENGINEER:
a. CONCRETE MIX DESIGNS.
b.GROUT MIX DESIGNS (OR PROPRIETARY PRODUCTS PROPOSED).
SB 2. THE CONTRACTOR SHALL SUBMIT THE FOLLOWING FOR INFORMATION TO THE DESIGN ENGINEER:
d. NOTICE OF FORM PLACEMENT.
e. NOTICE OF REINFORCING STEEL PLACEMENT
f.. NOTICE OF CONCRETE PLACEMENT.
g. NOTICE OF GROUT PLACEMENT.
h. NOTICE OF MECHANICAL EQUIPMENT PLACEMENT.
i. NOTICE OF POST -TENSIONED ANCHOR TEST.
j. RESULTS OF CONCRETE AND GROUT TESTING.
SB 3. NO SHOP DRAWINGS FOR THE STEEL WORK ARE TO BE SUBMITTED.
OWNER SUPPLIED MATERIALS
ITEM
OTY
DESCRIPTION
EXTERIOR SLUICE GATE
1
8 FT HIGH BY 3 FT WIDE WITH FLUSH BOTTOM SEAL INCLUDING
CAST IRON THIMBLE FOR EMBE➢DING ❑N FACE ❑F ❑PENING.
INTERIOR SLUICE GATE
1
2 FT HIGH BY 2 FT WIDE WITH FLUSH BOTTOM SEAL INCLUDING
CAST IRON THIMBLE FOR EMBEDDING ❑N FACE OF ❑PENING.
PENSTOCK INLET CLOSURE GATE
1
5 FT HIGH BY 6 FT WIDE WITH FLUSH BOTTOM SEAL INCLUDING
CAST IRON THIMBLE FOR EMBEDDING ❑N FACE OF ❑PENING.
PENSTOCK EMERGENCY CLOSURE
1
52 INCH DIAMETER BUTTERFLY VALVE WITH LIMITIRQUE
VALVE
OPERATOR.
JIB CRANE
1
6,000 LB CAPACITY JIB CRANE WITH 20 FOOT AND SOCKET
MOUNTED BASE INCLUDES ALL EMBEDDED MATERIALS.
SDR32.5 HOPE PIPE. DIAMETERS ARE 54" ❑D, 50667" ID. EACH
54° HDPE PIPE WITH 20 FT LENGTH
12
SEGMENT HAS STUB END FLANGE FOR COMPRESSION FITTING TO
JOIN SEGMENTS.
54" HDPE PIPE WITH MANHOLE AND
1
SDR32.5 HDPE PIPE WITH 36` DIAMETER HDPE MANHOLE ACCESS.
15'-9 LENGTH
COMPRESSION COOPING
16
DUCTILE IRON BACKING RING COMPRESSION FITTING T❑ JOIN
HOPE PIPE WITH FLANGED ENDS.
CONTRACT 2 - INTAKE/DIVERSION REHABILITATION
SUGGESTED CONSTRUCTION SEQUENCE
1. MOBILIZATION
2.ESTABLISH CAMP AND LAY DOWN AREA ADJACENT THE CEC BUNK HOUSE AND AT SPUR ROADS.
3. STABILIZE LEFT ABUTMENT WITH SPOILS MOVED UPSTREAM AND OUT EYAK ROAD.
4. INSTALL UPSTREAM AND DOWNSTREAM COFFERDAMS, AND DIVERSION FLUME.
5. EXCAVATE AND STABILIZE SLOPES FOR INTAKE STRUCTURE.
6. BUILD INTAKE TO EL. 284, INSTALL SLUICE GATES AND PENSTOCK CLOSURE GATE.
T EXCAVATE ROCK FOR DIVERSION STRUCTURE.
9. BUILD DIVERSION DAM.
9. BUILD INTAKE TO FULL HEIGHT AND INSTALL TUNNEL ACCESS.
10. INSTALL SPILLWAY OVERFLOW GATE.
11. INSTALL PENSTOCK, PENSTOCK EMERGENCY CLOSURE VALVE, SADDLES, AND THRUST BLOCKS.
12. INSTALL WALKWAYS, STAIRS, AND LADDERS.
13. INSTALL DOWNSTREAM OUTLET PORTAL CLOSURE WALL, VENTILATION SYSTEM, AND TUNNEL ACCESS
DOOR,
14.INSTALL REMAINING MECHANICAL AND ELECTRICAL EQUIPMENT.
ABBREVIATIONS
AB
ANCHOR BLOCK
EW
EACH WAY
ADH
ADHESIVE
EXP ANC
EXPANSION ANCHOR
ALT
ALTERNATIVE
ANC
ANCHOR
FF
FAR FACE
BM
BEAM
GEO
GEOMETRY
BOT
BOTTOM
H
HIGH
CB
CATCH BASIN
HE
HIGH STRENGTH
CHK
CHECK
HSS
HOLLOW STRUCTURAL SECTION
CJ
CONSTRUCTION JOINT
CL
CENTERLINE
ID
INSIDE DIAMETER
COL
COLUMN
IN
INCHES
GONG
CONCRETE
INFO
INFORMATION
CONN
CONNECTION
INV
INVERT
CP
COMPLETE PENETRATION
CTP
CATALYST PAPER
LET
LEFT
LET
LIQUID PENETRANT WELD TEST
DEC
DEGREES
DEM
DEMOLITION
m
METER
DEL
DETAIL
MAX
MAXIMUM
DIA
DIAMETER
MIT
MANHOLE
DIM
DIMENSION
MIN
MINIMUM
DWG
DRAWING
mm
MILLIMETER
DWL
DOWEL
D/S
DOWNSTREAM
NF
NEAR FACE
NDT
NON DESTRUCTIVE TESTING
EA
EACH
NOM
NOMINAL
EF
EACH FACE
NTS
NOT TO SCALE
EJ
EXPANSION JOINT
E
ELEVATION
PL
PLATE
EMB
EMBEDMENT
PT ANC
POST TENSION ANCHOR
ES
EACH SIDE
PROJ
PROJECT
SECTION INDICATOR
DRAWING ON WHICH SECTION IS CUT
SECTION LETTER
A
0
DRAWING NUMBER ON
WHICH SECTION APPEARS
DRAWING ON WHICH SECTION APPEARS
SECTION A SECTION LETTER
1 O DRAWING NUMBER ON
WHICH SECTION IS CUT
LEGEND
NEW CONCRETE
®REINFORCED
CONCRETE
R RADIUS, RISER
REBAR REINFORCING STEEL
REINF REINFORCING, REINFORCED
REF REFERENCE
REQD REQUIRED
RT RIGHT
SCH
SCHEDULE
SHT
SHEET
SIM
SIMILAR
SST
STAINLESS STEEL
ST
SURGE TANK
STD
STANDARD
ST
STEEL
TEMP TEMPORARY
TYR TYPICAL
TIME TEMPERATURE
TOS TOP OF STEEL
GRAVEL BACKFILL
STRUCTURAL FILL
NEW CONCRETE W STEEL
SURFACE
SHOTCRETE UHMW-PE
GROUT
UHMW-PE ULTRA HIGH MOLECULAR WEIGHT POLYETHYLENE
GINO UNLESS NOTED OTHERWISE
U/S UPSTREAM
VERT VERTICAL
W WATT, WEST, WATER, WALL, WIDE
W/ WITH
W/0 WITHOUT
WCB WORKER'S COMPENSATION BOARD
WE WIDE FLANGE
WP WEATHERPROOF, WORKPOINT
8889-XX
_-----SHORELINE CAMP FACILITIES EXISTING POWERHOUSE
AND LAY DOWN AREA
PROJECT BOUNDARY FOR
TRANSMISSION LINE TO
SUBMARINE CABLE
EXISTING THRUST
BLOCKS (TYP.)
!�
CEC BUNKHOUSE
w
U
U
m
a
EXISTING
PENSTOCK BRIDGE
3
0
U
3
`o
m EXPANSION
� JOINT
EXISTING LOWER I �� 1) i� � ,
� � DOWNSTREAM
PENSTOCK ��- �I���i I�,��i��TUNNEL�PORTAL��� „
� t �� � l� )� /� "\
� ' . l— �
s NEW PENSTOCK ' � I1 � � ��(����`��� � �� T �NEL _.��
n / 1
> �-_ / �'
i �11 t It Ir �� i � a� �_ � A � �r I
i /
� �„ � (� l ��%�i � �- � �� —� � INTAKE DIVERSION
�,� I i r ��,� a �oii --� ��ti � �- --.—_ � i
v � I1 ,i �i �I,i � � � i
I ��` I A� � rJ` - Z_ � - �h -�
N
1��\V�d� � �. � ii 'r � i �r'�' � r
ILL t � �� L.6 �� r I i�r-,�� � � � � nrer/�M � E�.IvC f 1tiC
.� scALE; r' = 1oD' A`;A11v,-���"� � �� � _ _ C'UUI�R.ITI1��;.1�'�C.
�'I �'�'%""' —'� INTAKE/DIVERSION
o I'�I�✓=�"� �%--" — �;' HUMPBACK CREEK PROJECT
0 1Do zoo aoo aoo soo � �� /°'-� ` FERC-8889 REHABILITATION
—�--���'�`�� CEC-08—HBC-02
o _ ��
a SITE PLAN
"' APPROVED: v���
I � �� OF. q�gS�1
o DSGN. REVIEWED /�ySP'� �9,j � Q �� � HATCH RCNES
�*' 49 Q' � '•*� R&M CONSULTANTS, INC.
N CHKD. /..:...................:../ DISCIPLINE
% J 9101 Vanguard Drive
o CML !};,,,,,,,,,,,,,,,,,,,;,`� LEAD Anchorage, Aloska 99507
DWN. ! aae� w u� The Ener Com an
a MECH. /+b'•, � 19�4 ; �/� 907 522 1707 voice • 907 522 3404 faz 9y P i
� CHKD. 1��`°i;,, j1en'= r DATE DWG N0.
sueM. ��• ����";�— ANCHORAGE, ALASKA 04/01/os C-01
A f0 SFP gH ISSUED FOR REVIEW ,
a PROJECT MANAGER. REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX—X-XX—XXXX—XXX
8889-XX
PLAN
SCALE; 1" = 30'
0 30 60 90 120 150
WORKPOINT
COORDINATES
WP
NORTHING
FASTING
1
2,47 4,42fi.57
1,698,395.00
2
2,414,461.72
1,698,401.75
3
2,414,557.17
1,698,378.70
4
2,414,698.04
7,698,163.85
5
2,414,772,65
7,698,762.58
i 400
c�
3 '. ', '. '. '.
Y 380 ',
° � EXISTING GRCUND
3
v
360 � - � ,
s
v 340 �->_ owµ
U ' � o u / �lil�i� OUTLET PORTAL z CO a;
� w r w r 7�17i\ AND THRUST BLDCK n� N
a
$ 320 � \ o Ia- wl.
E a in _
= DNERSION INTAKE i '.
DAM � '. ``�
N 300
� � �
n � THRUST BLOCK EXISTING
I PENSTOCK
% 280
.� �111101111 or-t11111v 11i, I I II, t�tl �ll�llb tl �ilit�111�.11lllo,111i _
m
� -�
V 260 Ift�71Ir-111ii ,— _
I _ ._..... _..,li iiiia nr�niiii �o(Ilf�,lilfto�iill�tlli —�ffj� j�v Ir�oi11I— — _
('(3Rf=)t)�%A
erxr� � LLE('�1 RIC'
+� -_
220
L��iC�['L1tt1I�i�'L.I�tiC.
a —1+00 —0+50 0+00 o+so 1+0o i+5o 2+00 2+50 3+00 3+so 4+ao 4+so INTAKE/DIVERSION
o HUMPBACK CREEK PROJECT REHABILITATION
FERC-8889 CEC—OS—HBC-02
a PROFILE PLAN AND PROFILE
'!? SCALE: HORIZ t" = 30'
`* APPROVED: _ o F���� VERT 1 " = 30'
o DSGN. REVIEWED ��y�P'�� •� s�j o
o � � �' � HA1CH RCBES
N CHKD. %.'F:. 49 L�. �.. '.�J R&M CONSULTANTS, INC.
o CML � :::::: � DISCIPLINE 9101 Vanguard Drive
a DWN. MECH. Ib��': �Ktnyi�.�y'� �� 907 5221707 voice �e5907952273404 fax 9Y P Y
. �
N CHKO. 1�•.�•.,. .,.;��i he ner Com an
sueM. ��• ������";��=� ANCHORAGE, ALASKA DATE DWG N0.
04/01/OS C-02
A 10 SEP 08 ISSUED FOR REVIEW Y �(�( �(�(YV YYY
a PROJECT MANAGER: REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX-/\�/\/\�/�/�/�/��/\I\/\
��Z�I��•S�+ 1
i
355_�
THE ACCURACY OF THE INFORMATION
CONTAINED HEREIN, EffHER EXPRESSED
OR IMPLIED. i i
PPPROVED: _+� O F�q�\\
DSGN. REVIEWED /�y�P;••"... A�•Fr�1
.,•
CHKD. /••�•••••••••••••••••••�••�� DISCIPLINE
CML % ..:....................../
OWN. %a . • . / LEAD
CHKD. MECH. (+' •.; �K�g�4��'//
SUBM. ELECT. 1�\\\�"r����
PROJECT MANAGER:
�I �
� � � � I �I �� / ( � /
CP8 � ` i I !� ' � i � / r
i
� � / � � ^�
CP7 � � � �' � � �i � � � 2
--1 ,, � � / / ,' ��� / / � � �
/ - ----�' -- � ,�/ / / � � / j �
r / ----�--'�
% � � -���,- . / / I
l /l r E i / i I / � � I 1
�l i / � � � �� � I
�`� ' � % / �Ci / � I
��a2��� � � / � � �� � � I
/� � / � I
/ � / � /�,
��. � i / � � / � �� I
`•� / / }
1
1 ` �� � � i
,�o , / i
2 A � � � / I
�-�---�- I %�-
T i� J i
� � � / / i
l �� //� � / ( rt
N c'S � ' / i
S � j
/ � � / �
I �—� � �
/ � /
I � � ��
o
O� 2b
�, � / / /
\ / � ////, r� � ,
,gyp / / I ��/ /,—
/ 2 r� % ( �
� � � � � h� � / I � I r—
/ j /2A � � /, I I � i
i
f 2 I I � i
PLAN
SCALE; 1" = 5'
0 5 10 15 20 25
AS —BUILT
No.
Northin Eastin
WP1
2414356.4037,
1698363.4399
WP2
2414361.3168,
1698358.3231
WP3
2414364.0210,
1698377.1713
WP4
2414368.3812,
1698364.3522
WP5
2414376.9431,
1698385.2324
WP6
2414384.5275,
1698368.6175
WP7
2414390.4177,
1698361.3274
WPS
2414389.9298,
1698357.4639
NOTE:
1. APPROXIMATE ROCK CONTOURS BASED ON
SUBSURFACE INVESTIGATIONS COMPLETED IN MAY 2008.
REFERENCE GEOTECHNICAL BASELINE REPORT. CONTOURS
LOCATIONS SHOULD BE CONFIRMED
ISSUED FOR REVIEW- 8/10/08
������ LLEC`1'lt(C.`
HUMPBACK CREEK PROJECT
FERC-8889
LEFT ABUTMENT
PLAN AND
0R �� �I
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507
907 522 1707 vnlre • 907 522 3404 fnr
REHABILITATION
CEC-08-HBC-02
STABILIZATION
SECTION
The
ANCHORAGE, ALASKA V^04/o1/08 V v v C-O3
A ID SFP 08 ISSUED FOR REVIEW �( VY YYYY YY�(
REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX-/\—/\/\�/\/\/\/\�/\/\/\
� � � •
v
U
U
O
2
E
S
N
V)
r
N
M
U
E
� , f
2 0 / h � 3
l
/ ,�.` / I
r`,_ / /
,� ,� ,
/ _J
�`' 1 / 1 �' / � -- ���,, � ., �--� � � �
M � � �
__-..,.,J ,��, o ors Mo / 2 �h o � � /
i
,r'
2
r /%, �/
�, f,- '�' // /
f
- � � � � / �� / � � � / / I � � I
-- � � �� 2��� �� � / � � � �/ EL,\255,0
� I I ,/ � � l � ..zL//
�- - _ C1 —'_`--_---- � ' � — —�- — — I—
�_ {����---- ,� � � � � / / / � WP� —
r ��.._ ��_____ �%� rr�
o
�' �j fv \ � CL EX"
f'�� _rj I �'�� � � � SLUICE
/ i \ / /
� ' ( / EXC Vf
1 0
_%''' � 4'`O � �
_- - � �
r NOTE 1 � � / �
,,
��
V
`r
I
APPROVED:
o
DSGN.
0
`�
CHKD.
o
DWN.
CML
a
�
MECH.
CHKD.
SUBM.
a
��•
o
PROJECT MANAGER:
a
_
REVIEWED
f �
?' �2 2
s
/ / 2�
;�.•"`.. A<qs,� PLAN
•• 9 L>
' ��
49 �' � '*� DISCIPLINE SCALE; 1" = 5'
............. � I FM
�K92�'y� :y=/� D 5 1O 15 20 25
A I10 SEP 08I ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION
NOTES
1. APPROXIMATE ROCK CONTOURS BELOW STREAM BED MATERIAL
REFERENCE GEOLOGICAL BASELINE REPORT.
2. REFERENCE DRAWINGS S—01 & 5-04 FOR GRID LINE LOCATIONS
AND ORIENTATION OF SLUICE CHANNELS.
TUNNEL WORKPOINT
COORDINATES
WP
NORTHING
FASTING
1
x
x
2
x
x
� �'_' � Ei FC hI2lC
� INTAKE/DIVERSION
HUMPBACK CREEK PROJECT REHABILITATION
FERC-8889 CEC-08-HBC-02
INTAKE/ DIVERSION
EXCAVATION PLAN
����'� HA�CHRCR�S
R&M CONSULTANTS, INC.
9101 Vanguard Drlve
Anchorage, Alaska ssso7 The Energy Company
907 522 1707 voice • 907 522 3404 fax
DATE DWG N0. C-04
ANCHORAGE, ALASKA o4/o1/os �/�/�/�/ �/�/�/
BY CHKD. APPD. CEC DWG. NO. XXX-X-XX-XXXX-XXX
_/ /--- / /
U_�__�._-- ___
A I
I, ,
'1 i i � "
' I
N
m
� j
N i I I
M 1 I �
I I
/ ! � I
1
I i
U ' i
` i i
I �
I`
� �,
O i �
,i
i i 1
a � � `
1 �
o — �
;_
a
rn
� APPROVED:
I
a OSGN.
0
N CHKD.
CML
� DWN.
a MECH.
� CHKO,
-o SUBM. ��•
o PROJECT MANAGER:
a —
r'� V�••A`gs�v PLAN
REVIEWED ��y�P' -F91�
DISCIPLINE SCALE; 1" = 5'
*r. }9 m...........
/ ..:...................:., � LEAD
+L •'•: �KyZy� �• j� 0 5 10 15 20 25
•'• •'Oi
/� � � �
/� � � f
/�
i / / ''
t / / /
/ / /
o/ 2^� /2,�h 2�0
a ,/ � ��/
/ : --- 2
(J 1�
11 (�
�, � �
i
I
I
1 � '
II \ j
i
\\
II \
L 61 I
I
I
I
� \
� \
— * EXCAVATION ELEVATION
A I19 SEP 08I ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION
• APPROXIMATE ROCK CONTOURS
NOTES
1. CONTRACTOR DESIGNED FLOW DIVERSION THROUGH
COFFER DAMS. DESIGN FOR MIN DIVERSION FLOW
600 CFS. ESTIMATE FLOW FOR SELECTED RETURN
PERIODS PROVIDED IN SPECIFICATIONS,
2. INTAKE EXCAVATION PREVIOUSLY COMPLETED,
OC)PE12A�I�IV L. I V`C.
HUMPBACK CREEK PROJECT INTAKE/DIVERSION
FERC-8889 REHABILITATION
CEC-08—HBC-02
DIVERSION DAM
EXCAVATION PLAN
®� � �' � HA1CH RCCES
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska ssfio� The Ener Com an
907 522 1707 voice • 907 522 3404 fax 9Y P Y
DATE DWG N0. C
ANCHORAGE, ALASKA o4/01/08�/�/ �/�/�/C�/—O�./,!�/�/
BY CHKD. APPD. CEC DWG. N0. XXX—X-/�/�—XXXX-XXX
8889-XX
NOTES
1. REFERENCE DRAWING C-03 FOR WORKPOINT 3 COORDINATES.
2. REFERENCE DRAWINGS S-15 & 5-16 FOR ALL PENSTOCK STATIONING,
3. OWNER SUPPLIED 54" HOPE PIPE WITH STUB END AND DUCTILE IRON
COMPRESSION COUPLING.
E
a
m
�
I
APPROVED:
0
DSGN.
REVIEWED
0
w
CHKD.
o
CML
DWN.
MECH.
CHKD.
SUBM.
ELECT•
o
PROJECT MANAGER:
m
DISCIPLINE
LEAD
PLAN
o s 10 15 20 zs
A I10 SfP 09I ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION
YA� I I I c E 1z,
C;OOPEI2A I\i. 1tiC;
HUMPBACK CREEK PROJECT I INTAKE/DIVERSION
FERC-8889 REHABILITATION
CEC-08-HBC-02
PENSTOCK AND TUNNEL PLAN
(SHEET 2 OF 4)
0;&o
L
R&M CONSULTANTS, INC.
9101 Vanguard Drive
907 522 1707 oice • mu�nu
3404 fax The Energy C
vompany
DATE
ANCHORAGE, ALASKA 04/01/Os
BY CHKD. APPD, CEC DWG. NO. xxx-x-xx-xxxx�xxx
8889—XX
:::• 1
d
E
0
'n
I
APPROVED:
O
DSGN.
XX
0
CHKD.
XX
o
CIVIL
DWN,
XX
N
MECH.
CHKD.
XX
SUBM.
XX
v
CDT•
o
PROJECT
MANAGER:
a
REVIEWED
'' 49m � '*� DISCIPLINE
PLAN
A �10 SIF 08T� ISSUED FOR REVIEW
REV.I DATE 1 NATURE OF REVISION
-I
NOTES
1.
CONFIRM BLOCKOUT DIMENSIONS AND LOCATIONS WITH
OVERFLOW
SPILLGATE MANUFACTURER'S PLANS AND DIRECTIONS.
2.
INSTALL EMBEDDED ANCHORS AND ABUTMENT PLATES
FOLLOWING
OVERFLOW SPILLGATE MANUFACTURER'S PLANS AND DIRECTIONS.
3.
CONSTRUCT DIVERSION DAM TO CONTACT INTACT LEFT
ABUTMENT ROCK,
4.
ALTERNATE JIB CRANE INSTALLATION LOCATION, EMBED
SOCKET AND
REINF PER MANUFACTURER'S RECOMMENDATIONS.
5.
PLACE DENTAL CONCRETE TO PROVIDE CONTACT WITH
SOUND ROCK
ON D/S EDGE OF DIVERSION DAM,
6.
GATE STEM GUIDE IMBEDDED IN WORKING SLAB AT EL,
284
7.
GATE STEM AND HOIST EQUIPMENT TO BE SUPPORTED
ON STEEL FRAME.
COOPERr1'l] 1.I:v'C.
u
HUMPBACK CREEK PROJECT uvinr�c�vivcnoivil
FERC-8889 REHABILITATION
CEC-08—HBC—no)
INTAKE/DIVERSION CONCRETE OUTLINE
PLAN
R&M CONSULTANTS, INC.
9101 Vanguard Drive HA1CNACCfS
Anchorage, Alaska 99507 The Energy Company
907 522 1707 voice • 907 522 3404 fax 9Y P Y DATE DWG N0. S- O 1 1
ANCHORAGE, ALASKA 04/01/08
BY CHKD. APPD. CEC DWG, NO. XXX-X-XX�XXXX—XXX
8889-XX
v
U
U
a
E
N
n
M
i
x
U
m
'o
a`
a
.;
a
0
s
a
`r'
i
APPROVED:
Wo
OSGN.
0
r'
CHKD.
CML
d
DWN.
a
MECH.
CHKD.
�
SUBM.
a
��•
w
o
PR0.IECT MANAGER:
a
E D E
_10^
I I
-CREST , i
� PT (TYP) I
°� ° �. 270.93 I
d
� d
° �1 I
a
° d NOTE F
.. ° d e
1 I� t I l t ��; ` "y;[
d a
� d °
t; � d. I
° �
°
° -
ad ° °
d I
d Y
EL 253.0 ° � ° �� ° � �-
SECTION A
1/4 -1 _0" S-
lu/ E
1._9„ 2,_0. 4,_3,. 2._3.. I
EL. 276.0
UHMW ABUTMENT
I I I I PL (ES) (NOTE 4)
�I I I
I I
' I 1` I I I I
I
Ali; I I I\� I I I NOTE 5
1= I I I I� I
u I I I I I I� I I
EL 268.0 s I I I I I I �� (
EL. 267.5 I'ii1 I I I I I i I �.
II\
m m.
..
d' a
d
cd
° ,. °I d d ,
_ d °
d °
l�I�� �. .. � � d° . � � II .II Iliad
EL. 255.0 _. °. a � ° � ���
REVIEWED :��P' .�
DISCIPLINE
�•k •��•,. •,% LEAD
Q 7Y24 . s//
SECTION C
°Q ° Q . I
Y�
�1 ° I
a ..
�_
�� a.
�f _ ° ..° ° NOTE 3
r1-2i °'d a
EL 261.0 � � � d ° d °� ��
° � � � � °�
d ' d ,�`
d ° ���. � NOTE 6
��' °. ° �_
�_�
L d�° ° v � _ NOTE 2
�z11 t��. _ '` _
� a �c ,�
a °' �1�..-� ��rv..
° � � a' ��i„ ii�7il�
EL 252.0 � � ° .� � c �° � .°_ . d _
�� � LSOUND ROCK
PROFILE
DIVERSION DAM SLOPE
INTERSECTION PT
SECTION B
NOTES
1. CRESQT GEOMETRY:
I
� X
Y = 0.124x1.85
Y�,Y Y' _
2. PLACE DENTAL CONCRETE TO EL. 252.0 ABOVE DIVERSION DAM FACE
INTERSECTION WITH SOUND ROCK.
3. BED LEVEL WILL VARY WITH CREEK FLOW AND SEASONS.
4. ABUTMENT PLATE DIMS GIVEN ON 5-02, CONFIRM DIMS AND INSTALLATION
REQUIREMENTS WITH OVERFLOW SPILLWAY PLANS AND RECOMMENDATIONS.
5. PROVIDE REINFORCING REQUIRED AS PART OF MANUFACTURER DESIGNED
NOTE 6 STIFFENER AND EMBEDMENT SYSTEM.
EL 261.0 6. PLACE DENTAL CONCRETE TO PROVIDE CONTACT WITH SOUND ROCK
ON D/S EDGE OF DIVERSION OAM.
IIII 111� ii is
EL 258.0 � '� �+ C`Ut2DC) V��
HUMPBACK CREEK PROJECT INTAKE/DIVERSION
FERC-8889 REHABILITATION
CEC-08—HBC-02
DIVERSION DAM CONCRETE OUTLINE
SECTIONS AND DETAILS
o Q �`� � HA1CH ACN�S
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507 The Ener Com an
907 522 1707 voice • 907 522 3404 fax 9Y P Y
DATE DWG N0. S-0"
ANCHORAGE, ALASKA o4/01/08 L
A 10 SEP OB ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. N0. XXX—X�XX-XXXX'/�/�/�
����I��'D:�:1
EL. 284.0 EL. 284.0
PARAPET WALL
° I a d.
EL. 277.0
I d _
EL. 274.0 � EL. 276.0 — Q— � — — —
d
° � d n .a ad .. ° II I) ° d, �d°,.e
° ,. ° d°^ I .d.lJ CJ b°
ed n .° n
I I
° _d d d ' ° ° . ° .all KEY II. I � �
a ad
. � � ' l l EL. 268.0 I I
v ° a ° °
�� .'d d° � ° :I
`-! d I
s`,° ,d° °° e I d Od da is
d _ � � I. d
� d° a e n n I d°
ad
ad � 4.4 ° ° � aq < a ,'°i Q
EL. 258.0 �_____ ___. � d � --� -- —�_a
.\ . � ° ° . °
�III� lit�L', � III � � • �f � � �' �II(�11 ,ill °III-+—+�
-d
�'
EL. 252.0 ° � � � d
III � .� ° III -
M
0
0
3
v
n
U
V
a
a
E
NOTES
I 1. REFER TO NOTES 4 AND 5 ON DWG N0. 5-02.
2. DENTAL CONCRETE (TYP). SEE NOTE 7 ON DWG N0. 5-07.
.o
a
a
�3
O
E
s
'�
l
APPROVED:
Q
DSGN.
XX
REVIEWED
a
CHKD.
X%
CML
o
�-
OWN.
XX
MECH.
N
CHKD.
XX
SUBM.
XX
�o
ELE�•
o
PROJECT
MANAGER:
a
49tn Al
...............
JpN K YA9EE
� 19R4
DISCIPLINE
LFAD
SECTION D
'�4�-1'-°� S—
iv
SECTION A
1'-1 -0"
4
I
I�
�,
lt/ C1 C B A
IY D
I
I I
c
EL. 280.5
Ala
���
CFD
EL. 28
1 �-0"
(TYP)
EL. VARIES
.�
�\
�t``�
NOTE
EL. 25
QERSTOP SECTION E
-« � � C`OIfL�UVA
�__ � ELEC'1Ii1C'.
COC)1'� IL��� I I' L. I "�C:� ,
HUMPBACK CREEK PROJECT INTAKE/DIVERSION
FERC-8889 REHABILITATION
CEC-08-HBC-02
INTAKE/DIVERSION CONCRETE OUTLINE
SECTION
o � ��' � HA1CH ACN�S
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507 The Ener CORI OD
907 522 1707 voice • 907 522 3404 fax gY P y
DATE DWG N0.
ANCHORAGE, ALASKA 04/01/08 S- O 3
A 1gSEP98 ISSUED FOR REVIEW Y YY �(Y�(�( YY�(
REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX�/\�/\/�—/�/�/�/\—/\/�/�
a
2 3 4
10'-0" 10'—O"
E
S-3
I I I
0
U
u
n
s
N
N
M
S
U
c
a
0
E
a
\ I I I
G
S-6
EL. 263.0
\ \�
WP1
I
EL. 26�
.-6..
F
_
S-5
_
EL. 267
I I I
/ EL. 263.0
`? a
I / A ' % j' .
l° / Y.:
6
/ / - I I , ;�
/ � / ° � .I. .da ' H
�// � / � I a I° ; �
� � EL. 264.0
_ I (
E
S-3
`r'
I
APPROVED:
0
0
N
DscN.
xx
CHKD.
XX
o
CML
DWN.
XX
N
MECH.
CHKD.
XX
SUBM.
XX
-a
ELE�•
r
o
PROJECT MANAGER:
a
—
REVIEWED
49� 1�
...........
JOlN IL YAOFE
� 1924
4"
DISCIPLINE
LEAD
I
0
0
0
NI
4,_0„ 4,-0,.
`>f p `.1
� �� EL 275.Oa I � a�j/�"
I `r
P I I a /�
a 1._6„ I I
2'-8" I I
6 I I
SLOPE _
I I _ _� I
� I __-� I
EL 268.0 I � .. I—�—�—�----
/ I I I T
I � j I I I I
_ _ _ _ i I I _ I
' I I I I I
ec � I o I I I I I
i I I I I L
M _1_�—I-----
I � w I I
a
SLOPE 2% j I
�.a`iI? 5._6..1 I
d< /I 'I EL 275.0 G.9`�— I I
��, / �EL. 268.0 EL. 265.2 — I (
EL. 265.0 I
I I
_ -----�
,nll� iii�� FaR�lii�/I ;�i��l
0
.I
PLAN EL. 276
EXISTING
SHOTCRETE
1NNEL LINK•
(TYP)
M
a
PARTIAL PLAN EL. 284
NOTES
1. PROVIDE ROUGH OPENING BASED ON DOOR MANUFACTURER'S REQUIREMENTS. '.' ,' '� � ('(}[�..I)O'�'\
,rter� � �L�C I12E(_'
HUMPBACK CREEK PROJECT INTAKE/DIVERSION
FERC-8889 REHABILITATION
CEC-08—HBC-02
INTAKE/DIVERSION CONCRETE OUTLINE
PLAN EL. 276 AND EL. 284
o Q ��`' � HA1CH ACAS
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507 The Ener Com Ofl
907 522 1707 voice • 907 522 3404 fax 9Y P Y
ANCHORAGE, ALASKA DA04 01 08 DWG N0. �� 04
A 10 SFP W ISSUED FOR REVIEW V V V V V Y V YYY
REV. DATE NATURE OF REVISION BY CHKD. APPD. CEC DWG. NO. XXX®/��/�/��/�/�/�/��/�/�/�
� � � •
E-I:I:�'D:i:�
NOTES
1. PROVIDE ROUGH OPENING FOR DOUBLE 3'-0"x7'-6" DOORS.
2. PROVIDE ROUGH OPENING FOR SINGLE 3'-6"x7'-6" DOOR.
3. STEEL WORK PLATFORM A7 EL. 275.0.
E
a
0
`�
I
APPRDVED:
ro
DSGN.
XX
0
0
a
CHKD.
XX
CML
o
DWN.
XX
MECH.
N
CHKD.
XX
SUBM.
XX
ti
ELE�•
o
PRDJEGi
MANAGER:
a
REVIEWED
49m AI '•.
..................
..............
JO!!1 K YAdfE
CE 1924 . .
DISCIPLINE
LEAD
SECTION G
'i4"=''-0" S-1 S-4
A I10 SEP W I ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION
SECTION H
'i4"=''-0� S-1 S-4
BY I CHKD. I APPD.
__ �
c�ool�Lr�.�� 1���. t:�t;;.
HUMPBACK CREEK PROJECT INTAKE/DIVERSIO
FERC-8889 REHABILITATION
CEC-08—HBC—C
INTAKE CONCRETE OUTLINE
SECTION
o � � �' � HA1CN ACCES
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska ssso7 The Ener Com an
907 522 1707 voice • 907 522 3404 fax 9Y P Y
DATE DWG N0.
ANCHORAGE, ALASKA o4/o1/OS�/�/ �/�/�/S-O6
CEC DWG. N0. XXX—X-/�/��/�/�/�/�—/�/�/�
DRESSER COUPLING) --------- -"-- "--"----- rnu w rvo. �nr/
CI Cl/ATI(lAl
U
Z
LOCATION
STATION
PLAN LENGTH
TRUE LENGTH
MATERIAL
INSIDE DIAMETER
OUTSIDE DIAMETER
INVERT ELEVATION
INTAKE DOWNSTREAM CONC FACE
0.00
265.00
2.Z5
2.25
CONCRETE
START TRANSITION
2.25
264.97
6.75
6.75
STEEL
53.50
54.00
END TRANSITION
9.00
264.89
1.00
1.00
STEEL
53.50
54.00
END CONCRETE
10.00
264.87
15.31
15.31
STEEL
53.50
54.00
SADDLE N0.1
25.31
264.68
4.00
4.00
STEEL
53.50
54.00
EXPANSION JOINT �1 (DRESSER)
29.31
264.63
4.00
4.00
STEEL
53.50
54.OD
SADDLE N0.2
33.31
264.58
4.00
4.00
STEEL
53.50
54.00
VALVE FLANGE JOINT
37.31
264.52
0.62
0.63
STEEL
54.00
EMERGENCY PENSTOCK CLOSURE VALVE
37.93
264.52
0.62
0.63
STEEL
54.00
VALVE FLANGE JOINT
38.55
264.51
4.00
4.00
STEEL
53.50
54.00
SADDLE N0.3
42.55
264.46
20.00
20.00
STEEL
53.50
54.00
SADDLE N0.4
62.55
264.20
20.00
20.00
STEEL
53.50
54.00
SADDLE NO.S
82.55
263.95
9.01
9.01
STEEL
53.50
54.00
ANCHOR BLOCK N0.12
91.56
263.83
0.50
0.50
STEEL
53.50
54.00
CHANGE SHELL THICKNESS
92.06
263.83
0.50
0.50
STEEL
53.50
54.25
ANCHOR RING
92.56
263.82
0.50
0.50
STEEL
53.50
54.25
BEND START
93.06
263.81
5.27
5.27
STEEL
53.50
54.00
0
v'
I
APPROVED:
a
DSGN.
a
`�
CHKD.
o
DWN.
CML
a
N
MECH.
CHKD.
SUBM.
v
��•
o
PROJECT MANAGER:
a
-
REVIEWED
DISCIPLINE
LEAD
ELEVATION
SGLLE: t/4' = i'-0' 0 4 8 FEE7
SCALE:
4 _1,_O.
LOCATION
STATION
PLAN
LENGTH
TRUE
LENGTH
MATERIAL
INSIDE DIAMETER
OUTSIDE
DIAMETER
INVERT ELEVATION
ANCHOR BLOCK CENTER (BEND)
98.33
Z63.75
5.27
5.27
STEEL
53.50
54.00
BEND FINISH
103.60
263.68
0.50
0.50
STEEL
53.50
54.25
ANCHOR RING
104.70
263.67
0.50
0.50
STEEL
53.50
54.25
CHANGE SHELL THICKNESS
104.60
263.67
0.50
0.50
STEEL
53.50
54.00
ANCHOR BLOCK EXIT
105.10
263.66
ECCENTRIC REDUCER (NOTE 5)
6.47
6.47
STEEL
50.68
54.00
STEEL TO HDPE JOINT
117.57
263.58
2.00
2.00
HDPE
50.68
54.00
SADDLE N0.6
113.57
263.55
6.75
6.75
HDPE
50.68
54.00
MANHOLE
120.32
Z63.46
7.00
7.00
HDPE
50.fi8
54.00
HDPE JOINT 54/54
127.32
263.38
2.00
2.00
HDPE
50.68
54.00
SADDLE N0.7
129.32
263.35
18.00
18.00
HDPE
50.68
54.00
HDPE JOINT 54/54
147.31
263.12
2.00
2.00
HDPE
50.68
54.00
SADDLE N0.8
149.31
263.09
18.00
18.00
HDPE
50.68
54.00
HDPE JOINT 54/54
167.31
262.86
2.00
2.00
HDPE
50.68
54.00
SADDLE N0.9
169.31
262.84
18.OD
18.00
HDPE
50.68
54.00
HDPE JOINT 54/54
187.31
262.61
2.00
2.00
HDPE
50.68
54.00
SADDLE N0.10
189.31
262.58
18.00
18.00
HDPE
50.68
54.00
A I10 SEP OBI ISSUED FOR REVIEW
REV. DATE NATURE OF REVISION
BY I CHKD. I APPD.
■
w
Q
NOTES
1. ALL DIMENSIONS ON PENSTOCK ELEVATION ARE APPRO%IMATE. TABULATED STATIONING
AND DIMENSIONS GOVERN. PENSTOCK SLOPE IS NOT SHOWN ON THIS DRAWING.
2. 54"DIA BUTTERFLY VALVE (HENRY PRATi OR EQUAL) WITH AUMA ELECTRIC ACTUATOR
(OR EQUAL).
3. STEEL 54.25"OD, 53.5"ID WITH 4"HIGH x 5/8" THICK THRUST RING ATTACHED BY
1/4" FILLET WELDS EACH SIDE.
4. FLAT FACED STEEL FLANGE TO MATCH DIMENSIONS AND BOLTING PATTERN OF OWNER
SUPPLIED COMPRESSION COUPLING, WITH OWNER SUPPLIED HDPE PIPE SEE NOTE 6
BELOW.
5. STEEL ECCENTRIC REDUCER 54"OD 53.5"ID TO 51.18"OD 50.68"ID
6. SEE DWG G-03 AND TABLE OF OWNERS SUPPLIED MATERIAL. DETAILS FROM
MANUFACTURER GIVEN ON REF DWG. CONFlRM ALL DIMENSIONS.
� C`t?RI)t�Vi`�
Ll_�.(_ 1 KI('
HUMPBACK CREEK PROJECT �REHABILITATION��
FERC-8889 CEC-08-HBC-02
PENSTOCK ELEVATIONS
SHEET 1 OF 2
®� ��' o NR�CN ACAS
R&M CONSULTANTS, INC.
9101 Vanguard Drive
Anchorage, Alaska 99507 The Ener Com an
907 522 1707 voice • 907 522 3404 fax 9Y P Y
ANCHORAGE, ALASKA DATE DWG NO.
04/o�/os S- 1 5
CEC DWG. N0. XXX-X-XX-XXXX-XXX