Loading...
HomeMy WebLinkAboutSystem Report - SNPWindNorthwindTurbines_hmrSystem Report - SNPWindNorthwindTurbines.hmr System Report - SNPWindNorthwindTurbines.hmr System architecture     Cat 3512 855kW: 855 kW     Cat 3512 655kW: 650 kW Cost summary Total net present cost: 23,077,230 $ Levelized cost of energy: 0.275 $/kWh Cost breakdown Component Initial Capital Annualized Capital Annualized Replacement Annual O&M Annual Fuel Total Annualized ($) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) Cat 3512 855kW 0 0 11,960 105,961 935,767 1,053,688 Cat 3512 655kW 0 0 9,395 96,178 495,995 601,568 Other 0 0 0 150,000 0 150,000 Totals 0 0 21,355 352,139 1,431,762 1,805,256 Annual electric energy production Component Production Fraction (kWh/yr) Cat 3512 855kW 4,435,520 68% Cat 3512 655kW 2,102,728 32% Total 6,538,247 100% System Report - SNPWindNorthwindTurbines_hmr_files/MonthlyAverageElectricProduction.png Annual electric energy consumption Load Consumption Fraction (kWh/yr) AC primary load 6,538,253 100% Total 6,538,253 100% Variable Value Units Renewable fraction: 0.000 Excess electricity: 0 kWh/yr Unmet load: 0 kWh/yr Capacity shortage: 1,026 kWh/yr Annual thermal energy production Component Production Fraction (kWh/yr) Cat 3512 855kW 1,148,159 64% Cat 3512 655kW 648,317 36% Boiler 0 0% Excess electricity 0 0% Total 1,796,476 100% Thermal load served: 86,870 kWh/yr Excess thermal energy: 1,709,606 kWh/yr System Report - SNPWindNorthwindTurbines_hmr_files/MonthlyAverageThermalProduction.png Cat 3512 855kW Variable Value Units Hours of operation: 6,233 hr/yr Number of starts: 515 starts/yr Operational life: 12.83 yr Average electrical output: 712 kW Minimum electrical output: 582 kW Maximum electrical output: 855 kW Average thermal output: 184.2 kW Minimum thermal output: 157.5 kW Maximum thermal output: 214 kW Annual fuel usage: 1,180,034 L/yr Specific fuel usage: 0.266 L/kWh Average electrical efficiency: 38.2 % Average total efficiency: 48.1 % System Report - SNPWindNorthwindTurbines_hmr_files/Generator1Output.png Cat 3512 655kW Variable Value Units Hours of operation: 6,126 hr/yr Number of starts: 971 starts/yr Operational life: 13.06 yr Average electrical output: 343 kW Minimum electrical output: 195.0 kW Maximum electrical output: 637 kW Average thermal output: 105.8 kW Minimum thermal output: 74.0 kW Maximum thermal output: 168.9 kW Annual fuel usage: 625,467 L/yr Specific fuel usage: 0.297 L/kWh Average electrical efficiency: 34.2 % Average total efficiency: 44.7 % System Report - SNPWindNorthwindTurbines_hmr_files/Generator2Output.png Emissions Pollutant Emissions (kg/yr) Carbon dioxide 4,754,478 Carbon monoxide 11,736 Unburned hydocarbons 1,300 Particulate matter 885 Sulfur dioxide 9,548 Nitrogen oxides 104,719