HomeMy WebLinkAboutDCVR-HCI-09DESIGN CLARIFICATION/VERIFICATION REQUEST
CONTRACTOR: Hankal Construction, Inc.,--
PROJECT: Unalakleet Bulk Fuel —
Upgrade
SPEC. NO.: 13200 2.05 A
DC/VR NO.: HCI-9
CONTRACT NO.: R.EG-06-088
Detail 1
DRAWING NO.: sheet M-4
DESCRIPTION OF REQUEST:
Detail indicates the High Level (95%) Alarms are to be installed on
the gasoline tanks only. We believe this is to include the AVGAS
tanks. It is unclear if the JET -A tanks are considered to be more
related to the gasoline product classification or to the diesel
product classification.
Please clarify if the JET -A tanks require the High Level Alarms
ATTACHMENT: YES NOE] CHANGE ORDER: YES NO[]
IF YES PROVIDE RFP;
WRITTEN BY: DAVE SHELLENBERGER DATE: August 9, 2006
APPROVED BY: i� _ DATE:
DAVE SHELLENBERGER / F _
RESPONSE:
rLeA off , J�� CLIc� I s CU7) UID4 Lctve
Sew 1 4 ,C1O f s J
� f
RFP REQUIRED; S O / P
BY: < /"
DATE: � 9
A/E
This is NOT an authorization for additional reimbursement or time
extension. Authorization of such can be made only by the owner through a
change order in accordance with the contract documents.