HomeMy WebLinkAboutDCVR-HCI-30DESIGN CLARIFICATION/VERI,FICATION REQUEST CONTRACTOR: Hankal Construction, Inc. DC/VR NO.e HCI-30 PROJECT: Unalalkleet Bulk Fuel CONTRACT NO.: REG-0'6-08'8 Upgrade SPEC. NO.: DRAWING NO.: DESCRIPTION OF REQUEST: The motor of DP-1 is not capable of operating with the wye-delta soft start feature specified in SS 16900 2..03 1411. A wye-delta motor is required to achieve the performance desired. ATTACHMENT::. YESE NO[] CHANGE .ORDER: YES.Z :NOF] IF YES PROVIDE RFP: WRITTEN BY DAVE SHELL,ENBERGER DATE APPROVED BY �� _ DATE PAzg 40 RAVE Sft2LLETIBERGER t� eC Z0/07- RESPONSE: Provide motor capable of operating with specified Wye -Delta motor starter. This motor does not have to be explosion proof as specified, a non -explosion proof TEFC motor similar to attached motor in stock in Anchorage quoted by Hayden Electric Motors will be acceptable. Note this quote is for a US Motor 250T frame motor as a direct replacement for the 254T frame motor currently installed on the pump. It is the Contractors responsibility to coordinate new motor application with pump manufacturer. Submittal for DP-1 did not contain sufficient detail for determining if motor was suitable for application of the Wye -Delta motor starter. Submittal only indicted that a 208v/3ph 254T frame motor would be provided. Submittal approval stipulated it is the "Contractors responsibility for coordination with all other trades and the satisfactory performance of work". Spec Section 01300 ¶ 1.05 J. requires the Contractor to review and coordinate each submittal with other submittals, requirements of the work, and the Contract Documents. Spec Section 00700 ¶ 3.4.1, 6.12, 6.13.2 and 6.21.2 has similar wording for the Intent of the Contract Documents and Contractors Responsibilities. We are asking the Contractor to fully investigate the implementations of this recent discovery, in light of above information, and then the AUTHORITY can enter into negotiation with the Contractor for any allowable Change. R:FP REQUIRED;: YES 0 NQ yA-0 �A? C_ 7�- BY: DATE: This is NOT an authorization for additional reimbursement or time extension. Authorization of such can be made only by the owner through a -- -cha-nge--order--in-ac-corda-aoe with -the-contractdocuments. - -- -- DCVRFORM Aug 21 07 09:01a HAYDEN ELECTRIC MOTORS 907-646-9044 p.1 HAYq N ELECTRZG 4moTORS HAYDEN ELECTRIC MOTORS, INC. 4109 Old Seward Highway #300 Anchorage, Alaska 99503 (907) 561-1073 email: roger@hayden-ak.wm. Date and Time: Tuesday, August 21, 2007 9:01 AM To: GLEN From: Roger L. Saunders Company: LCMF ENGINEERING Fax No.: 907-646-9044 Fax No.: 273-1831 No. Of Pages: 3 GLEN: I have a US Electric Motor 15 Hp 12 lead motor on the shelf (model AE52) for $948.54. This motor in not explosion proof but it will operate at 208 VAC with a wye-delta starter. I was unable to locate a 12 lead explosion proof motor. Let me know if this will work for your application. Thank you, Roger L. Saunders Hug ci u/ uy:u la HAYULN tLtU I K1U MU I UKS UU1-646-9U44 p.2 I.:aof �roRL( US ELECTRICAL MOTORS 137033 Motor Wiring Diagram 12 Lead, Dual Voltage, Wte Start / Delta Run, Both Voltages LOW VOLTAGE HIGH VOLTAGE Y START L RUN Y START A RUN 6 7 8 9 1: 7 12 10 11 6 4 5 41 5� 6+ 4� 5i 6i 7 8 9 12 10 11 12 1� 12 10 11 1 2 3 1 2 3 1 t 2T 3� 1 2 3 ; ; L1 L2 L3 L7 L2 L3 L1 L2 L3 L1 L2 L3 FULL VOLTAGE ACROSS THE LINE START AND RUN ON A CONNECTIONS. ALSO SUITABLE FOR START ON Y, RUN ON A. Per NEMA MG1 1998-1.76, "A Wye Start, Delta Run motor is one arranged for starting by connecting to the supply with the primary winding initially connected in wye, then reconnected in delta for running condition." This is accomplished by a special Wye -Delta starter configuration using six leads from the motor and is intended to limit the inrush current required to start the motor. Motors designed by US Motors for Wye start, Delta Run may also be used for across the line starting using only the Delta connection. Damage will occur if the motor is operated with load for more than 30 seconds on the Wye without transition to Delta. To reverse direction of rotation, interchange leads L1 & L2. Each lead may have one or more cables comprising that lead. In such case, each cable will be marked with the appropriate lead number. Connecion Plaie. 137033 Revised: 12MM9 REP Connection Decal: 344138 Revised: 10/13/00 REP HUg L I U/ Ua:ULa MAYUtIV tLtzU I KICK IVIU I UKJ UU1-bob-UU44 p.3 I EFFECTIVE: HORIZONTAL MOTORS PRIW-- 193s 24JAN-05 SUPERSEDES: FRAME: 250T SHEET: 08-JUL-02 TYPE: CT,CTE,CTI,FCT 1 OF I P c F2F H-4 HOLES N BA IZE E G WIT 2E A ALL DIMENSIONS ARF IN INCHFS AND Mil I IMFTFRS 1 UNITS A E G J i K N O P 2 T 1N 12.13 5.00 .88 2.25 2.50 4.38 12.91 14.22 Z03 mm 308 127 22 57 ; 64 11i 328 361 52 UNITS W AA AB AG AF BA MIN MIN KE(Y IN 3.94 .38 1.60 10.97 1 a." 2.53 4.25 2.94 .375 MM 100 10 279 1 214 64 106 75 9.53 FRAMEM305 B e Bs ! D -.06 2E t.03 2F t.03 H +.05 U -.001 254T260 10.25 23.75 4.13 1 6.25 10.00 8.25 .53 1.625 603 105 1 159 254 210 13 4128 256T 12.00 25.50 5.00 1 6.25 10.00 10.00 .53 1.625 1 648 127 1 159 1 254 1 254 1 13 41 28 1: ALL ROUGH CASTING DIMENS4ONS MAY VARY BY 25' DUE TO CASTING AND/OR FABRICATION VARIATIONS. 2. LARGEST MOTOR WIDTH. 3: ALL TOLERANCE UNITS ARE IN INCHES. EMERSOM Motor%chnob9fes 4: CONDUIT BOX MAY BE LOCATED ON EITHER SIDE OF MOTOR. CONDUIT OPENINGS MAY BE LOCATED IN STEPS OF 90 DEGREES REGARDLESS OF LOCATION. STANDARD AS SHOWN WITH CONDUIT OPENING DOWN. 08/11/2007 16:10 907-344-1856 DYNAMIC SYSTEMS INC PAGE 01 DYNAMIC SYSTEMS INC. FAX COVER SHEET To: Dave Shellenber er Company: Ha! nkal Canst. lnc. From: Andy Subject: Clnalaklect Sulk Fuel Fax; 562-6496 Pages: Two I LUs 0r-4 E_ Date: Au ust 13 2007 Davc on Saturday Bryan called fxorn Unalakleet and advised tliat the fuel distribution. pump DP-1 only has nine leads. To properly connect the wye-delta starter to this motor we require twelve leads. We have to be able to break apart the center connection of 10 — 11 — 12. Page .l of 1 625-1 l20 1r. Huffman Rd, Anchorage, AK 99515 Phone:907.344.1846 Fax: 907.344.1856 E-mail. abuck(a)a%.net 09/11/2007 16:10 907-344-1855 kn 0 0 0 U c DYNAMIC SYSTEMS INC PAGE 02 Cl)(3005 r� V 2. Pressure 3. Product: PART 2 PRODUCTS 2.01 DISTRIBUTION PUMP 100 psi Unleaded Gasoline No. 2 Diesel Aviation Gasoline (100LL) Jet A-50 (Fuel Oil & Arctic Grade Diesel same) A. Positive displacement pump for petroleum service_ Base mounted with gear reducer, couplings, coupling guards, and motor factory mounted to base plate. Pump assembly shall be factory tested. B. 3-inch flanged inlet and 3-inch flanged outlet, ductile iron case, steel fitted, with cartridge type mechanical seal. Mechanical seal shall be of stainless steel construction, or of other corrosion resistant material, grafoil fitted, with silicon carbide 1 silicon carbide faces. Other seal designs will be considered provided they are suitable for operation down to -40 degrees F. C. Pump shall produce 115 gpm @ 420 rpm. Pump shall require no more than 5 feet of net positive suction head when operating at the specified design point. Set internal relief valve at 100 psi. Relief valve shall be factory set and tested. The working fluid for the Distribution Pump is #2 Diesel with a viscosity of 3.5 to 75 centistokes depending on fluid temperature. D. Pump casing shall be rated for 200 psi. E. Provide 1750 rpm 15 hp explosion proof 208v13phl60hz motor. Pump and motor shall have clockwise rotation, or the proper direction of rotation in the case of an alternate manufacturer that will result in the suction and discharge port configuration as shown on the Drawings. Viking Model LL4126A-R, or approved equal. 2.02 TRANSFER PUMPS A. Self -priming centrifugal pump for petroleum service. B. 2-inch NPT inlet and outlet, ductile iron case, bronze impeller, and self -lubricated Buna-N mechanical seal. C. Close coupled to 3,450 rpm., 2 hp explosion proof 208v11ph160hz motor. Pump shall produce 80 gpm @ 70' tdh. D. Gorman -Rupp 02K31-X2, no substitutes. Unalakleet Bulk Fuel Upgrade REG 06-088 / 02/2006 I5484-3 Fuel System Equipment