Loading...
HomeMy WebLinkAboutDCVR-LCMF-02.2DESIGN CLARIFICATION/VERIFICATION REQUEST CONTRACTOR: Hankal Construction, Inc. PROJECT: Unalakleet Bulk Fuel Upgrade SPEC. NO.: DC/VR NO.: LCMF-02.2 CONTRACT NO.: REG-06-088 DRAWING NO.: Tank Farm Control Panel DESCRIPTION OF REQUEST: Locate items: CP-1, MTU-1, CP-3, CP-4 and CP-5 per original design drawing E-4. See attached modified control panel mounting detail drawing. This request supersedes DCVR LCHF-02 on relocating above mentioned items. Please provide cost estimate with response to the modified control panel mounting changes. ATTACHMENT: YES® NO❑ WRITTEN B APPROVED Dip RFP REQUIRED: YES❑ NO❑ CHANGE ORDER: YES® NO❑ IF YES PROVIDE RFP: BY: DATE: Hankal Construction, Inc. DATE: 5-08-07 DATE: 5507 This is NOT an authorization for additional reimbursement or time extension. Authorization of such can be made only by the owner through a change order in accordance with the contract documents. DCVRFORM 3 0 E CRITICAL HIGH FUEL LEVEL ALARM HORN/STROBE. SEE PLANS FOR LOCATIONS, INSTALL WEATHERPROOF CAP ON TOP OF POST o ea b COORDINATE WITH FENCING CONTRACTOR TO PROVIDE MOUNT HORN/STROBE +24" MIN. 3"GRSC POSTS ON EITHER 1" GRSC, MIN. ABOVE TOP OF CONTROL PANEL. SIDE OFCONTROL PANEL CONDUIT SUPPORT, TYP. NT UNISTRUT WITH TO MOUNT U-BOLT. 3/4" PRESSURE TREATED MOUNT CONTROL PANEL MAX. 6'-6" MARINE GRADE PLYWOOD A.F.G. TO TOP OF PANEL. BACKER BOARD 3" HOT -DIPPED GALVANIZED PROVIDE STAINLESS STEEL BRACKET U-BOLTS WITH FLAT WASHERS AND ANCHOR TO ATTACH PANEL TO IN 4 LOCATIONS. BACKER BOARD IN 4 LOCATIONS. SEAL LIQUIDTIGHT WITH SILICON SEALANT. UNISTRUT CROSS BRACING, TYPICAL ALL FOUR SIDES. FUEL SYSTEM CONTROL PANEL PROVIDE UNISTRUT MOUNTING FRAME (SEE NOTES). ALL CONDUIT PENETRATIONS SHALL wViENTER/EXIT 40 PIPE THE BOTTOM OF THE b (TPICAL) CONTROL PANEL. in NEC CLEARSPACE PROVIDE CONDUIT SEAL WHERE REQUIRED BY CODE. SEE SHEET E3. SECURE CONDUIT PROVIDE SUITABLE PLATFORM CONSTRUCTED TO BACKER BOARD FROM 3" X 30" X 12 GAUGE HOT DIP GALVANIZED GRIP -STRUT AND PRESSURE TREATED TIMBERS OVER CONDUIT/PIPING. (IF ROUTED IN NEC 110.26 WORKING CLEARANCE) TO ALLOW USER TO STAND IN FRONT OF PANEL WITHOUT HAVING TO STAND ON CONDUIT OR PIPING. 36" MIN . I I X� DO' NOT ATTACH INSIDE OF DIKE WALL, DO NOT PENETRATE MEMBRANE LINER TANK FARM CONTROL PANEL MOUNTING DETAIL J % SCALE: 1" = 2' NOTES: SHALL BE 12 GA. STEEL HOT -DIPPED GALVANIZED UNISTRUT IN ACCORDANCE WITH SECTION 15190.2.05. UNAILAKLEET BULK FUEL FARM CONTROL PANEL MOUNTING DETAIL E3LCMFLLc UNALAKLEET, ALASKA 615 E. 82nd Ave. Suite 200 Anhcwap,AXN518 273-1&W DATE: 05/04/07 DRAWN BY: SHEET: DCVR: LCME 02.2 SCALE: AS SHOWN CHECKED BY: W.O. No: 05-756