HomeMy WebLinkAbout05-756 C-17rn
r-
�2
O
2
0 10
20
SCALE IN FEET
SCALE: 1 " = 10'
I
PROPERTY CORNER
N 250694,31
E 352425.01
ABANDONED
GASOLINE
DISPENSER
WITH CANOPY
I
2„
UNALAKLEET TOWNSI TE
ADDITION NO. 1
PLAT 88-8
I
o\-
O�:10 S6
0
06
UNALAKLEET TOWNSI TE
PLAT 87-11
SHED
UNC YARD
TRANSITION
BOX, TYPICAL
(ABANDONED)
SHED
N 73°13'49" E
210.91'
STAND PIPE FOR
BULK LOADING
NOZZLE
1 NEW 5,000 GALLON
M-g PROTECTED GASOLINE
DISPENSING TANK
UNALAKLEET TOWNSI TE
ADDITION NO. 1
PLAT 88-8
FUEL OIL BULK HOSE
REEL WITH CANOPY,
ABANDON IN PLACE.
TO BE REMOVED BY
OTHERS
FUEL
TANK
NOTES
PROVIDE NEW FILL LIMITING VALVE, 7 GALLON SPILL CONTAINMENT MANHOLE,
2" MALE CAMLOCK AND FILL CAP. INSTALL IN EXISTING TANK.
2� PROVIDE ISOLATION BALL VALVE AND ANTI -SIPHON VALVE SPECIFICALLY
MANUFACTURED FOR ABOVE GROUND TANK SUCTION PUMP SYSTEMS WITH 5
TO 10 FEET OF HEAD PRESSURE.
:� PROVIDE FUSIBLE VALVE AND PRESSURE REGULATOR/SHEAR VALVE
SPECIFICALLY DESIGNED FOR USE WITH SUCTION PUMP DISPENSERS WHEN
CONNECTED TO ABOVE GROUND TANKS.
R:� EXISTING GASOLINE DISPENSING SYSTEM WILL BE RETAINED FOR BACK-UP.
5, OWNER FURNISHED TWO-HOSE/TWO-PRODUCT SUCTION PUMP DISPENSER
CURRENTLY DISPENSES A SINGLE PRODUCT FROM EXISTING 2000 GALLON
GASOLINE DISPENSING TANK, THIS PROJECT WILL CONVERT EXISTING
GASOLINE TANK TO FUEL OIL AND PROVIDE A NEW GASOLINE DISPENSING
TANK AND ASSOCIATED WORK TO DISPENSE A SECOND PRODUCT AT THE
OWNER FURNISHED DISPENSER. OWNER FURNISHED DISPENSER WILL BE
CONTROLLED THROUGH A REMOTE CONSOLE. THE FOLLOWING WORK IS
REQUIRED:
* PROVIDE NEW TANK WITH APPURTENANCES AND ASSOCIATED PIPING TO
EXISTING TWO -PRODUCT DISPENSER.
* PROVIDE NEW VALVES, PIPE SUPPORTS, AND ASSOCIATED ITEMS AS
INDICA TED.
EXISTING 5,000 GALLON
SINGLE WALL TANK
(NOT IN SERVICE)
PROPERTY LINE TO BE
VACATED BY UNC
EXISTING 2,000 GALLON SHED
PROTECTED FUEL OIL
DISPENSING TANK, CONVERT
TO FUEL OIL.
SHED
�5.0'�
F E
N n U L
I TANK
FILTER BOX 2» n�
(ABANDONED) I Y
-- o
REMOVE REMOVE EXISTING
2" 0 TANK FILL
PIPING, INSTALL
BLIND OR THREADED
CAP AT MAIN LINE
UNC GAS S TA TION
AND STORE
FINISHED FLOOR
ELEVATION = 13.5'
i
i
i
--------------
----
-
— N 7y=0„ E
107
POND ROAD
EXISTING 1-112"
ABOVE GROUND
GASOLINE PIPING,
CONVERT TO FUEL
OIL.
EXISTING DISPENSING •
ISLAND WITH TWO
HOSE/TWO PRODUCT
SUCTION PUMP
DISPENSER
EXISTING
BOLLARD
BOLLARD
(TYPICAL OF 4)
6
C-18
NEW 1-112"
SCHEDULE 80
ABOVE GROUND
GASOLINE PIPING
PROVIDE PIPE
SUPPORTS 8.0'
MAXIMUM ON
CEN TER 2
-14
2" FUEL OIL PIPING TO! BE UNALAKLEET TOWNSI TE
ABANDONED IN PLACE, ADDITION NO. 1
(REMOVED BY OTHERS) PLAT 88-8
F f 1
PIPING TO UNC BULK
TANK FARM,
2" GASOLINE PIPING TO BE DECOMMISSIONING OF
ABANDONED IN PLACE EXISTING TANKS IS
(REMOVED BY OTHERS) ADDITIVE ALTERNATE A
tESE
CORD DRAWING
DRAWINGS HAVE BEEN PREPARED
FROM MARKED -UP DRAWINGS SUPPLIED BY
THE CONTRACTOR. AN AS -BUILT SURVEY
HAS NOT BEEN CONDUCTED. FIELD VERIFY
ANY INFORMATION CONTAINED HEREON
BEFORE USING.
O
Z
Q
a
W
Z
W
Q
Q
J
Q
ui Q
pY
Q
�a
0 J
aQ
w
J ~
W W
D J
LL Y
Ya
J J
jQ
� Z
QCOO,
M
r^
N
0
o
a
0
U
a`
0
0
N
W
co
W
a
a
co
w
DRAWN BY: EE
CHECKED BY: GMO
DATE: 1 1 / 15/07
JOB NUMBER: 05-756
SCALE: AS SHOWN
DRAWING TITLE:
UNC GAS STATION
SITE PLAN
SHEET: OF
C-17