HomeMy WebLinkAbout05-756 M-1SCHEDULE AND LEGEND
VALVE & PUMP TAG SCHEDULE
VALVE & PUMP TAGS — 3"x5"x.08" ALUMINUM, 3/16" HOLES IN ALL FOUR CORNERS, BLACK
GERBER THERMAL TRANSFER FILM PRINTED LETTERS ON GERBER 220 HIGH PERFORMANCE VINYL
BACKGROUND, COLOR AS INDICATED, ONE SIDE ONLY. WARNING LIGHTS OR EQUAL.
INSTALLATION — SECURE EACH TAG TIGHT TO VALVE, PIPE, OR DEVICE WITH STAINLESS STEEL
CABLE TIES THROUGH ALL FOUR CORNERS.
TOMATO RED (UNC — UNLEADED GASOLINE)
11 "NORMALLY CLOSED, OPEN ONLY FOR BARGE DELIVERY"
12 "NORMALLY CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
13 "TP-6, CORPORATION, UNLEADED GASOLINE TRUCK LOADING"
14 „NORMALLY CLOSED, OPEN ONLY FOR PIPELINE PIGGING"
15 CLOSE FOR PIPELINE PIGGING"
16 "NORMALLY CLOSED, GASOLINE RECEIPT PIPELINE LOW POINT DRAIN"
17 "NORMALLY CLOSED, PRESSURE TEST CONNECTION"
1 g NORMALLY OPEN, CLOSE ONLY FOR MAINTENANCE"
APPLE GREEN (UNC — FUEL OIL)
21
"NORMALLY
CLOSED, OPEN ONLY FOR BARGE DELIVERY"
22
"NORMALLY
CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
23
"TP-5, CORPORATION,
FUEL OIL TRUCK LOADING"
24
"NORMALLY
CLOSED, OPEN ONLY FOR PIPELINE PIGGING"
25
"CLOSE FOR
PIPELINE PIGGING"
26
"NORMALLY
CLOSED, DIESEL RECEIPT PIPELINE LOW POINT DRAIN"
27
"NORMALLY
CLOSED, PRESSURE TEST CONNECTION"
BEIGE (BSSD — FUEL OIL)
31
"NORMALLY
CLOSED, OPEN ONLY FOR BARGE DELIVERY"
32
"NORMALLY
CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
33
"TP-2, SCHOOL,
FUEL OIL TRUCK LOADING"
34
"NORMALLY
OPEN, CLOSE DURING BARGE RECEIPT"
VIOLET (BSSD — JET "A")
41 "NORMALLY CLOSED, OPEN ONLY FOR BARGE DELIVERY"
42 "NORMALLY CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
43 "TP-1, SCHOOL, JET "A" TRUCK LOADING"
44 'NORMALLY OPEN, CLOSE ONLY FOR MAINTENANCE OR FOR FUTURE FILTER SEPARATOR"
LIGHT ORANGE (WCAS — AV GAS)
51 "NORMALLY CLOSED, OPEN ONLY FOR BARGE DELIVERY"
52 "NORMALLY CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
53 "TP-3, WEST COAST, AV GAS TRUCK LOADING"
54 "NORMALLY OPEN, CLOSE DURING BARGE RECEIPT"
55 "NORMALLY OPEN, CLOSE ONLY FOR MAINTENANCE OR FOR FUTURE FILTER SEPARATOR"
MEDIUM GRAY (WCAS — JET "A")
61 "NORMALLY CLOSED, OPEN ONLY FOR BARGE DELIVERY"
62 "NORMALLY CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
63 "TP-4, WEST COAST, JET "A" TRUCK LOADING"
64 "NORMALLY OPEN, CLOSE DURING BARGE RECEIPT"
65 "NORMALLY OPEN, CLOSE ONLY FOR MAINTENANCE OR FOR FUTURE FILTER SEPARATOR"
MAGENTA (UVEC — DIESEL #2)
WARNING SIGN & INFORMATIONAL PLACARD SCHEDULE:
WARNING SIGNS & INFORMATIONAL PLACARDS — PROVIDE ALL SIGNS INDICATED IN THE
SCHEDULE BELOW, QUANTITY & LOCATION AS INDICATED ON DRAWINGS. ALL SIGNS SHALL
BE 0.08" ALUMINUM PLATE,10"xl4" UNLESS INDICATED OTHERWISE OR REQUIRED TO BE
LARGER FOR SPECIFIED LETTER SIZE. PROVIDE 3/16" HOLES IN ALL FOUR CORNERS. WHITE
NON —REFLECTIVE VINYL BACKGROUND, 3M 3650-10, WITH 3M SERIES 225 HIGH
PERFORMANCE VINYL LETTERS, ONE SIDE ONLY. WARNING LIGHTS OR EQUAL.
WARNING SIGNS — RED LETTERING ON WHITE BACKGROUND.
OA "DANGER — FLAMMABLE, NO SMOKING" (3" HIGH 1/2" STROKE LETTERS-24"xl8")
OB "IN CASE OF SPILL CALL DEC 1-800-478-9300"
OC "DANGEROUS CARGO, NO VISITORS, NO SMOKING, NO OPEN LIGHTS" (3" HIGH 1/2"
STROKE LETTERS — 36"x24")
OD "DISPENSING INTO UNAPPROVED CONTAINERS PROHIBITED"
OE "STOP YOUR MOTOR"
OF "FUEL SYSTEM EMERGENCY SHUT OFF" (6"X12")
()"IN CASE OF FIRE OR SPILL TURN OFF MAIN BREAKER"
INFORMATIONAL PLACARDS — BLACK LETTERING ON WHITE BACKGROUND.
@I, CLOSE & LOCK BULK TANK MAIN VALVES AFTER EACH TRANSFER"
oll TURN OFF CONTROL PANEL POWER EACH NIGHT"
O"PRIOR TO FILLING BULK TANKS CEASE TRANSFER OPERATIONS"
O"CHOCK WHEELS, ATTACH STATIC WIRE, & VERIFY TANK CAPACITY PRIOR TO BULK
TRANSFER"
LO "DISPENSING NOT PERMITTED WHILE DISPENSING TANK BEING FILLED"
INSTALLATION — ATTACH TO FENCING WITH HOG RINGS OR STAINLESS STEEL CABLE
TIES. ATTACH TO STRUCTURES WITH STAINLESS STEEL LAGS OR BOLTS.
LEGEND
IIOII FLANGED BALL VALVE
L/1I FLANGED CHECK VALVE
ICI FLANGED FLEX FITTING
Iffil FLANGED EXPANSION
JOINT
VER TI CAL TRANSITION
(PIPE UP)
VER TI CAL TRANSITION
A (PIPE DOWN)
II II ACTUATED BALL VALVE
[�-- CAM LOCK COUPLING
0 METER
)\\\\( HOSE REEL
ICI FLANGED Y—STRAINER
(MESH SIZE)
FLANGED BASKET
STRAINER (MESH SIZE)
® FUSIBLE VAL VE
Q REDUCER
FIL TER
PRESSURE GAUGE OR
PRESSURE VACUUM GAUGE
® TRANSFER OR DISTRIBUTION PUMP
(p SUBMERSIBLE PUMP
G*-- ANTI —SIPHON VALVE OR
PLAN PRESSURE RELIEF VALVE,
SYMBOL INDICA TES
DIRECTION OF FLOW
ELEVA TION
PUMP
SCHEDULE
LABEL
FUNCTION
STYLE
MOTOR
DESIGN POINT
DP-1
DIESEL #2 DISTRIBUTION PUMP
POSITIVE DISPLACEMENT
15HP,
208V/PH
115
GPM
@
100 PSI
TP-1
JET "A" TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
TP-2
FUEL OIL TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
TP-3
AV GAS TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
TP-4
JET "A" TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
TP-5
FUEL OIL TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
TP-6
UNLEADED TRUCK LOADING PUMP
CENTRIFUGAL
2HP,
208VIlPH
80
GPM
@
70
FT
SP-1
Cl TY DIESEL DISPENSING
SUBMERSIBLE
3/4HP, 208VIlPH
10
GPM
@
80
FT
SP-2
CITY UNLEADED DISPENSING
SUBMERSIBLE
3/4HP, 208VIlPH
10
GPM
@
80
FT
W
Z
W
71 "NORMALLY CLOSED, OPEN ONLY FOR BARGE DELIVERY"
72 "NORMALL Y CLOSED, OPEN ONLY FOR TANK FILL AND ISSUE"
73 "NORMALLY OPEN, CLOSE DURING BARGE RECEIPT"
74 "NORMALLY CLOSED, OPEN FOR TRANSFERING TO POWER PLANT"
75 "NORMALLY OPEN, CLOSE ONLY FOR MAINTENANCE AND WHILE TRANSFERING TO POWER PLANT"
76 "NORMALL Y CLOSED OPEN FOR TRANSFERING TO TANK #3"
"NORMALLY CLOSED, PRESSURE TEST CONNECTION"
�$ NORMALLY CLOSED, POWER PLANT PIPELINE LOW POINT DRAIN"
0
79 NORMALLY OPEN, CLOSE TO ISOLATE BRIDGE LINES"
Z
gp "NORMALL Y CLOSED, OPEN TO RECEIVE FUEL FROM BULK TANK FARM"
81 "NORMALLY OPEN, POWER PLANT FUEL SUPPLY"
Q 3
N
044
0
WIZ
>
=oLLI
RECORD DRAWING
THESE DRAWINGS HAVE BEEN PREPARED
FROM MARKED -UP DRAWINGS SUPPLIED BY
THE CONTRACTOR. AN AS -BUILT SURVEY
HAS NOT BEEN CONDUCTED. FIELD VERIFY
ANY INFORMATION CONTAINED HEREON
BEFORE USING.
Q M
��GG CO
DRAWN BY: EE
CHECKED BY: GMO
DATE: 11 / 15/07
JOB NUMBER: 05-756
SCALE: AS SHOWN
DRAWING TITLE:
SCHEDULE AND LEGEND
SHEET: OF
M-1