3116" PLATE
0
2'-0" 3'-0"
INDUSTRIAL LA TCH,
HANDLE ACCESSIBLE
FROM INSIDE ONLY
1E 3116 " DOOR WITH
ANGLE STIFFENERS
(TYPICAL OF 3)
3 ENCLOSURE LOCK
—1
PLAN
PLATE 3'x3'x3/16 " BOLTED
ACCESS PANEL, LOCATE PER
BELOW PIPING PLANS, AND TO
ALLOW INSTALLATION OR
REMOVAL AND MAINTENANCE OF
INSTALLED EQUIPMENT
3'-0"
WELD —ON HINGE WITH
318" 0 PIN AND ZERK
FITTING (TYPICAL OF 2
ON EACH DOOR)
INDUSTRIAL LATCH
(TYPICAL OF 2)
NO TES:
1. ALL CONNECTIONS SHALL BE CONTINUOUSLY WELDED UNLESS OTHERWISE NOTED.
2. ENCLOSURE SHALL BE WELDED TO BASE LEGS (TYPICAL OF 6).
3. ENCLOSURE SHALL BE FROM A36 STEEL.
4. ENCLOSURE COATING: INTERIOR AND EXTERIOR OF ENCLOSURE, AND ENCLOSURE
BASE SHALL BE SAND BLASTED PER SSPC SP-10 (NEAR WHITE BLAST) AND
COATED WITH THE FOLLOWING COATING SYSTEMS:
PRIMED WITH DEVOE CA THA —COAT 302H (3-4 MILS DFT), INTERMEDIATE COATED
WITH DEVOE BAR RUST 233H (4-6 MILS DFT), AND TOP COATED WITH DEVOE
DEVTHANE 389 (2-3 MILS DFT).
5. CONTINUOUSLY WELD ALL SECTIONS OF PLATE AT CORNERS.
6. BOTTOM 4" OF ENCLOSURE FLOOR SHALL BE LIQUID TIGHT. PROVIDE TWO 1-114"0
THREADED DRAIN PLUGS IN THE BOTTOM OF ENCLOSURE.
7. MOUNT ALL EQUIPMENT AND PIPE SUPPORTS TO INVERTED CHANNELS WELDED TO
THE BOTTOM OF ENCLOSURE. PROVIDE 6" MINIMUM CLEARANCE BETWEEN BOTTOM
OF ENCLOSURE AND CHANNEL FOR ACCESS TO ALL MOUNTING BOLTS.
8. ENCLOSURE SHALL BE SHOP FABRICATED AND SHOP COATED. FABRICATOR SHALL
SUBMIT SHOP DRAWINGS PRIOR TO BEGINNING PROCUREMENT OR FABRICATION.
2 "0 SCH 80
PIPE --,
ENCLOSURE
PENE TRA TION
BOO T --�
2" ACTUATED
BALL VALVE —\
2"Ox12"
FLEX FITTING
(2" MP x 2'
FLOATING FLANGE)
PRESSURE GAUGE
(0 TO 300 PSI) —
2" FORGED
S TREE T
ELBOW —
2"Oxl2" FLEX
FITTING
(2"MPTX2'
FLOATING FLANGE)
PRESSURE/VACUUM GAUGE
(-30" Hg TO 100 PSI)
FIRE
EXTINGUISHER '
PUMP START/STOP STATION
AND HOSE REEL PUSH BUTTON
WITH UNI —STRUT SUPPORT
NO TE:
PROVIDE BLIND FLANGES AND BALL VALVE FOR FUTURE
FILTER SEPARATOR FOR WCAS JET "A" AND AVGAS, AND
BSSD JET "A" TRUCK FILL ENCLOSURES.
SCALE: 1" = 1'-0"
DRIP LEDGE
IA/I TLJ 9 /'i " I 10
P�
END
BULK
TRANSFER
NOZZLE
e�-
3"x3"x114"
TUBE STEEL
(TYPICAL)
pr �3p t
1 /4 - PLATE BOTTOM
1 " PRESSURE
RELIEF VALVE
SET A T 125 PSI
3 "X 1 " TEE
4 "X3" TEE
NO TE:
PROVIDE FOUR (8) 8 "X 12 "X 8 FEET LONG PRESSURE TREATED
TIMBERS EVENLY SPACED FOR UVEC PUMP ENCLOSURE
FOUNDATION, EMBED TWO THIRDS OF THE TIMBERS DEPTH
INTO THE MEMBRAINE LINER BALLAST.
SCALE: 1" = 1'-0"
3 "0 TO
TANK #3
3X 1 TEE -
I" PRESSURE
RELIEF VALVE
SET AT 125 PSI
FIRE EXTINGUISHER AND
PUMP START/STOP STATION
WITH UNI —STRUT SUPPORT-
—ju ny i u i uu
1-112"
nnnn i i
PLAN
cc-/-nA/g DOOR
ED ANGLE
6"x114"
-COND DOOR
? FIXED ANGLE
114" /� CONTINUOUSLY
WELDED TO TUBE STEEL
6 "x6 "x 1 /4 " TUBE STEEL
1-1 /4 "x3/8 " THICK
FLAT BAR DRILLED FOR
PADLOCK, PROVIDE
INDUSTRIAL GRADE
CORROSION RESISTANT
PADLOCK
=SIVE ANCHOR THESE DRAWINGS HAVE BEEN PREPARED
4" EMBED FROM MARKED -UP DRAWINGS SUPPLIED BN
THE CONTRACTOR. AN AS -BUILT SURVEY
HAS NOT BEEN CONDUCTED. FIELD VERIF'
LAGS FOR ANY INFORMATION CONTAINED HEREON
ENCLOSURE RFF(1RF IICIN(:
3"0 X 12" FLEX FITTING
(3" FIXED FLANGE X 3" FLOATING FLANGE)
cQo 0 MESHBASKET P KET 3 "0 TO Z
IAR IS ONE INCH ON
)RIGINAL DRAWING
0 1'
NOT ONE INCH ON
HIS SHEET, ADJUST
4"0 FROM
TAAIVC
PRESSURE/VACUUM
GAUGE (-13" Hg TO
100 PSI)
POSTION ACCESS PANEL TO ALLOW
INSTALLATION AND REMOVAL OF PUMP, BASE
PLATE AND MOTOR AS A UNIT.
O
Z
a
W
Z
W
a
U)
a
J
a
Q M
CO
Jm
04
a
di
Em
0
L
U
a
0
N
W
co
W
a
N
co
Lu
mi to
w
O�
C) a z
0
UJ
�0 W
DRAWN BY: EE
CHECKED BY: GMO
DATE: 11 /15/07
JOB NUMBER: 05— 756
SCALE: AS SHOWN
DRAWING TITLE:
PUMP
ENCLOSURE DETAILS
SHEET: OF
M-12