HomeMy WebLinkAboutE10
NO SCALE
'r--- - -- - - - - - - - - -- -- - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - --- - - - - - - - - - - - - --- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -- - - - - - - - - -- ft `
1
UINALAKLEET VALLEY BERING STRAITS WEST COAST UNALAKLEET
IELECTRIC CORPORATION L DISTRICT AVIATION SERVICENATIVE CORPORATION
t
1
1
1
I
i
i
1
I
I
t
I
i
I
1
1
1
!
i
t
i
I
1
i
i
i
1
1
I
I
I
I
t
i
1
i
i
i
I
I
e
� 1
..�_
i Q Q 1 e Q
i t N `` (COMMON LOADS) !
1 1 JTP-2! i —— — — TP-1 1 i TP 3 DTP 4 � t IiTP 5�� DTP 6 � E!
Pr
1 JET "A �} Fu EL OIL j 1 I AV OAS � JE T ';A " I I� i ULL O!L UNLEADED
!--------------------� i----------------------�-------------------I 1
EM-1 EM-2
BULK TANK FARM
!
f----------- ----- ----- ----- ------------------------------------------------------------------------------ ----- ---------------------------- ---- II
.-------------------------------.,���
! 1
D-1
I 1
1 1
EM-5 I
I CD
�2 0 CP-7 I
SP-1 SP-2 ■ I
I EM-4 i
\,CITY DISPENSER �l
`-----------------------------�� r'
LEGEND
♦�
AREA LIGHT —SECURITY
o-E=
AREA LIGHT
Q�
FLOODLIGHT —OUTDOORS, WEATHERPROOF
Q
LIGHT FIXTURE —SURFACE MOUNTED ON CEILING
OA
FIXTURE TAG (LETTER INDICATES TYPE)
MOTOR (SIZED AS NOTED)
❑�
EMERGENCY SHUT—OFF BUTTON
M
METER PACK/DISCONNECT CABINET
cP—x
FUEL SYSTEM CONTROL PANEL (N0. INDICATES PANEL #)
GFCI RECEPTACLE
JQ
JUNCTION BOX
CONDUIT (3/4"G, 2#12, 1#12 GND UNLESS OTHERWISE NOTED, TYP.)
GROUNDING CONDUCTOR
--------
CONDUIT, BURIED
HOMERUN TO PANEL
L1
LOW LEVEL CUT—OFF SWITCH (N0. INDICATES SWITCH #)
H1
HIGH LEVEL CUT—OFF SWITCH (N0. INDICATES SWITCH #)
C1
CRITICAL HIGH LEVEL CUT—OFF SWITCH (N0. INDICATES SWITCH #)
Al
ACTUATED BALL VALVE (N0. INDICATES VALVE #)
OQ
ALARM HORN/STROBE
C
CONDUIT
CO
CONDUIT ONLY
GRSC
GALVANIZED RIGID STEEL CONDUIT
XP
EXPLOSION PROOF
WP
WEATHERPROOF
1
NOTE TAG (No. INDICATES NOTE)
LIGHT FIXTURE SCHEDULE
MANUFACTURER AND CATALOG
MOUNTING_
LAMPS
TYPE
LOCATION
NUMBER (OR APPROVED EQUAL)
DESCRIPTION
TYPE
HEIGHT
NO.
WATTS
TANK FARM
HUBBEL
MH ROADWAY FIXTURE WITH DIE CAST ALUMINUM
POLE ON
23'-0"
1
250
DRIVEWAY
#RMC-3-3—RMD-25H38-3
HOUSING, FLAT TEMPERED GLASS LENS, TYPE III
ARM
MH
WB04A
DISTRIBUTION, GRAY FINISH, MULTI —TAP, HPF BALLAST,
'
ARM—RBACWH4X2
PHOTOCELL AND 4'-0" ALUMINUM WOOD POLE ARM.
'
TANK FARM
LITHONIA
MH "SHOEBOX" FIXTURE WITH ALUMINUM HOUSING,
POLE
18'-0"
1
150
#KAD— 1 5OM—R4—TB—WWD09
TEMPERED GLASS LENS, TYPE IV DISTRIBUTION,
PSMH
Al
MULTI —TAP BALLAST AND 9" WOOD POLE ARM.
TRUCK FILL
GE
HAZARDOUS LOCATION INCANDESCENT FIXTURE WITH
SURFACE
CEILING
1
100
(HAZARDOUS)
#H8-120-10E-2C—KK
CLASS 1, DIV.2 RATING, INTEGRAL CONDUIT SEAL,INC
`
—CRA
GLOBE WITH GUARD, 30OW MAXIMUM MEDIUM BASE
i
TRUCK FILL
GE
ENCLOSED AND GASKETED INCANDESCENT FIXTURE
SURFACE
CEILING
i 1
100
(NON—HAZ)
#H7-120-10E-3C—DD
WITH CLEAR GLOBE AND GUARD, 150W MAXIMUM
INC
MEDIUM BASE INCANDESCENT BULB, AND
G
CEILING MOUNTING BASE.
POWER PLANT
LITHONIA
HPS WALL PACK
WALL
8'-0"
1
70
#TWAC-70S— 1 20—PE1
HPS
—CR
TANK FARM
DIESEL TANKS
LITHONIA
#TFR-250M—TA—TB—IS—
MH FLOODLIGHT WITH DIE—CAST ALUMINUM HOUSING,
CLEAR TEMPERED GLASS LENS, DARK BRONZE FINISH,
WALL
AS
SHOWN
1
250
PSMH
SCWA
2-3/8- TENON ADAPTOR, —40'F RATING, MULTI —TAP
PSMH BALLAST AND PSMH LAMP.
1
EM-1.2.3. EMERGENCY SHUTOFF_ PROVIDE AND INSTALL NEMA 4X ENCLOSURE WITH 2-1/4- DIAMETER
RED MUSHROOM HEAD MAINTAINED CONTACT PUSH BUTTON. 120V CONTACT BLOCK WITH 1 NORMALLY
CLOSED SET OF CONTACTS. PROVIDE NAME PLATE ABOVE SHUTOFF, ATTACHED WITH STAINLESS
STEEL SCREWS TO READ "FUEL SYSTEM EMERGENCY SHUTOFF"_ NAMEPLATE SHALL BE RED WITH
WHITE BACKGROUND. SIGN TO BE 6"x12".
EM-4 SAME AS EM-1 ONLY CLASS 1, DIVISION 2 ENCLOSURE.
L1—L2 LOW LEVEL FLOAT SWITCH_ 120V OPERATION WITH N/O & N/C CONTACTS ON EACH SWITCH. SEE MECH_
H —H8 HIGH LEVEL FLOAT SWITCH_ 120V OPERATION WITH N/O & N/C CONTACTS ON EACH SWITCH_ SEE MECH_
HI, Cl HIGH/CRITICAL HIGH LEVEL FLOAT SWITCH. 120V OPERATION WITH N/O & N/C CONTACTS ON
EACH SWITCH. SEE MECH.
A-1 THRU A-7 ACTUATED BALL VALVE. 120V OPERATION WITH (2 EA) FIELD CONVERTIBLE END SWITCHES. SEE MECH.
HS-1.2,3 NEMA 3R ALARM HORN/STROBE. 120V OPERATION. EDWARDS #95 R—N5 OR EQUAL.
MTU-1 MAIN TELEMETRY UNIT WITH MIN_ 2 INPUTS, 2 OUTPUTS, PLUS MIN. 2 SPARE INPUT/OUTPUT
CONNECTIONS FOR FUTURE_ PROVIDE WITH HEATER (COLD WEATHER PACKAGE) FOR OPERATION
AT —40'F.
RTU-1 REMOTE TELEMETRY UNIT WITH MIN. 4 INPUT, 4 OUTPUTS. PROVIDE WITH HEATER FOR
OPERATION AT —40`F
P-1 120V PHOTOCELL. (TYP. OF 6).
r
f r�
C
W�
--
z5X
ot-
o
zv
0U)
c z N
ch
j �
n♦ t� X
W ZQ
00
doU� U
Ua
C Lu
WWF
05
Qco
ci
Q J
Um
U
U/ QU
WIQ
LO
�N
OF
A I �
,415 �t
o
W /_1 o
� �I
°
.. cam, 04� °° y
ow
00°°°°°oo°oQo°° ° o° ......io
�o o... ............00000
o CHAN N LILLO /
® EE-10285 Q Aw
:
..
DRAWN BY: CPL, NVL
CHECKED BY: CPL
DATE: 11 /18/05
JOB NUMBER: K4193
SCALE: AS SHOWN
DRAWING TITLE:
ELECTRICAL LEGEND
FIXTURE SCHEDULE
FUEL SCHEMATIC DIAGRAM
AND EQUIPMENT LIST
SHEET: OF