HomeMy WebLinkAboutE2CANT TOP OF POST
2" WEATHERHEAD MOUNTED TO
STEEL POLE, SEE STRUCTURAL.
PROVIDE 5' SLACK FOR
CONNECTION TO NEW
SERVICE DROP. COORDINATE
WITH LOCAL UTILITY FOR
EXACT LOCATION AND
CONNECTION_
2" GRSC, 4#3/0
CU, XHHW_
STAINLESS STEEL, 200A,208V,30,4W
COMBINATION METERPACK/
DISCONNECT WITH BREAKERS
SIZED AND LABELED AS
SHOWN.
SEE 2/E2 FOR MOUNTING
DETAIL
NTS
COMMON LOADS
em �
30/2
UNALAKLEET NATIVE
CORPORATION
0____�160/2
WEST COAST
AVIATION SERVICE
M �
60/2
BERING SEA SCHOOL
DISTRICT
n
0---i0/2
UNALAKLEET VALLEY
ELECTRICAL CORPORATI
om �
100/3
INSTALL PHOTOCELL P-1 ON NEMA 4
ENCLOSURE WHEN CALLED FOR ON
CONTROL PANEL ONE -LINE DIAGRAMS.
FIELD ADJUST TO TURN ALL EXTERIOR
FIXTURES CONTROLLED "ON" AT DUSK
AND "OFF" AT DAWN.
25' PRESSURE TREATED,
REA CLASS 5 WOOD POLE
PER WESTERN RED CEDAR
ASSOCIATION GUIDELINES
AND SPECIFICATIONS.
q
vulxsL-v I v, .,Tv, 11TI v
BURIED 1 "C, 3#6, 1 # 10
BURIED 1 -C, 3#6, 1 # 10
BURIED 1.5"C, 4# 1, 1 #6
9" ARM SECURELY MOUNTED
TO WOOD POLE
TYPE 'Al FIXTURE.
LIQUIDTIGHT FLEX.
NEMA 4X JUNCTION BOX
1 /2"C, 3# 12, TYP.
JEL SYSTEM CONTROL
-67, SEE SHEET El 1.
UNALAKLEET NATIVE CORPORATION
FUEL SYSTEM CONTROL
PANEL 'CP-5', SEE SHEET E10.
WEST COAST AVIATION SERVICE FUEL
SYSTEM CONTROL PANEL 'CP-4', SEE
SHEET E10.
BERING SEA SCHOOL DISTRICT FUEL
SYSTEM CONTROL PANEL 'CP-3', SEE
SHEET E10.
UNALAKLEET VALLEY ELECTRICAL
CORPORATION FUEL SYSTEM
CONTROL PANEL 'CP-1',
SEE SHEET E8.
DETAIL NOTES:
1- #2 B.C. TO TANK GROUNDING SYSTEM. SEE 2/E3.
2. #4 B.C_ TO JUMPER FOR CONNECTION TO NEUTRAL,
GROUND BUS & ENCLOSURE.
1 #4 B.C. TO GROUND RODS_ SEE 2/E2.
i
�- CONDUIT STRAP
TYPICAL
�, -- NEMA 4X JUNCTION BOX
MIN_ 24" SECTION OF LIQUIDTIGHT
FLEXIBLE CONDUIT WITH OFFSET
BEND TO ALLOW FOR GROUND
+20" MIN. A_F_G_ MOVEMENT, TYP.
PROVIDE CONDUIT SEAL WHERE
REQUIRED BY CODE.
GRADE-\
3# ! ! !
t
3
1 1 ! i 24" MIN.
o WRAP BELOW GRADE ' !
i PORTION OF POLE WITH I
;�. 2 WRAPS OF 6MIL BLACK ► _ _ _ _ _ _ _ _ _ _ TO CONTROL PANEL OR
POLYETHYLENE_ NEXT FIXTURE.
'iis F r TRANSITION TO GRSC FOR BELOW_ GRADE
g ° PORTION OF CONDUIT. SEE 1/E13 FOR
CONDUIT TRENCHING DETAIL.
TANK FARM POLE BASE DETAIL
CRITICAL HIGH FUEL LEVEL
ALARM HORN/STROBE_ SEE PLANS
FOR LOCATIONS-
1 - GRSC, MIN.
INSTALL WEATHERPROOF CAP ON
TOP OF POST
3/8"X5" HOT -DIPPED GALVANIZED
CARRIAGE BOLTS WITH FLAT
WASHERS
3/4" PRESSURE TREATED MARINE
GRADE PLYWOOD BACKING
COORDINATE WITH FENCING
CONTRACTOR TO PROVIDE
3"GRSC POSTS ON EITHER
SIDE OF CONTROL PANEL
TO MOUNT PLYWOOD AND
STRUT_
ROUTE CONDUIT WITH FUEL PIPING
WHERE POSSIBLE. SEE 4/E13
WHERE ADDITIONAL SUPPORTS
ARE REQUIRED.
•a
t'o
P :G •�. ..;y' rya�. o
f
almll Oki
COORDINATE WITH UVEC
FOR POWER SERVICE.
8"X8"X10'-0" PRESSURE
TREATED WOOD POST_
TYP. OF (2)
5-GANG METERPACK. SEE 1/E2.
METER SHALL BE NO HIGHER
THAN 5'-6" A_F_G.
SEE 1 /E2 FOR CONDUIT
SIZE/TYPE.
25' PRESSURE TREATED,
REA CLASS 5 WOOD POLE
PER WESTERN RED CEDAR
ASSOCIATION GUIDELINES
AND SPECIFICATIONS.
SUPPORT CONDUIT ON 5'-0" CENTERS MAX
SECURE METER CENTERS TO
PLYWOOD BACKING WITH
GALVANIZED UNISTRUT BRACKETS.
3/4" PRESSURE TREATED
MARINE GRADE PLYWOOD
BACKING SECURELY MOUNTED
TO POST WITH (4 EA.) 3/8"0,
3" LAG SCREWS AND FLAT
WASHERS.
#4 B.C. STAPLED SECURELY
6
PROVIDE UNISTRUT CONDUIT SUPPORT
TO POST
PROVIDE LIQUIDTIGHT FLEXIBLE
(2 EA_) 3/4"x 10'-0"
CONDUIT FOR ABOVE GRADE
CU CLAD GROUND RODS
PORTION OF CONDUIT WITH
SPACED MIN. 8'-0"
OFFSET BEND TO ALLOW FOR
APART_ BURY AFTER
GROUND MOVEMENT, TYP.
INSPECTION.
INSTALL CONDUIT SEALS WHERE REQUIRED.
GRADE -�
INSULATED, THREADED BUSHING, TYP.
TRANSITION TO GRSC FOR BELOW -GRADE
PORTION OF CONDUIT. SEE 1 /E 13 FOR
' • CONDUIT TRENCHING DETAIL.
4 —0
CONTROL PANELS.
�I
79_a•
WRAP BELOW GRADE
PORTION OF POLE WITH
2 WRAPS OF 6MIL BLACK
POLYETHYLENE.
V
METER BASE MOUNTING DETAIL
MOUNT HORN/STROBE +24" MIN.
ABOVE TOP OF CONTROL PANEL.
/ CONDUIT SUPPORT, TYP.
- MOUNT CONTROL PANEL MAX. 6'-6"
A.F.G. TO TOP OF PANEL.
STAINLESS STEEL UNISTRUT BRACKET
AND FITTINGS ANCHOR PANEL TO
UNISTRUT IN 4 LOCATIONS. SEAL
LIQUIDTIGHT WITH SILICON SEALANT.
ALL CONDUIT PENETRATIONS SHALL
ENTER/EXIT THE BOTTOM OF THE
CONTROL PANEL.
PROVIDE CONDUIT SEAL WHERE
REQUIRED BY CODE. SEE SHEET E3.
PROVIDE SUITABLE PLATFORM CONSTRUCTED
FROM 3" X 24" X 12 GAUGE HOT DIP
GALVANIZED GRIP -STRUT AND PRESSURE
TREATED TIMBERS OVER CONDUIT/PIPING_
(IF ROUTED IN NEC 110.26 WORKING
CLEARANCE) TO ALLOW USER TO STAND IN
FRONT OF PANEL WITHOUT HAVING TO STAND
ON CONDUIT OF PIPING_
CANT TOP OF POST
6"x6"x 10'-0" PRESSURE
TREATED WOOD POST_
TYP_ OF (2), SPACED
EQUALLY APART.
GRADE � 24" MIN
1
48"
30' PRESSURE TREATED,
REA CLASS 5 WOOD POLE
PER WESTERN RED CEDAR
ASSOCIATION GUIDELINES
AND SPECIFICATIONS_
EMERGENCY SIGNAGE_ SEE SHEET E1.
E
EMERGENCY STOP (WHERE APPLICABLE) L
SEE PLANS FOR LOCATIONS_Fo-]
GRADE-
WRAP BELOW GRADE
a PORTION OF POLE WITH f;
;.. 2 WRAPS OF 6MIL BLACK !
POLYETHYLENE.
NO SCALE
3/8"X3" HOT -DIPPED GALVANIZED
LAG BOLTS WITH FLAT WASHERS
FUEL SYSTEM CONTROL PANEL
ca STAINLESS STEEL UNISTRUT BRACKET
- AND FITTINGS ANCHOR PANEL TO
UNISTRUT IN 4 LOCATIONS_ SEAL
LIQUIDTIGHT WITH SILICON SEALANT.
3/4" PRESSURE TREATED MARINE GRADE
PLYWOOD BACKING
DUPLEX GFCI RECEPTACLE WITH LOCKABLE
"WHILE -IN -USE" COVER. (SEE PLANS
o FOR LOCATIONS.)
o PADLOCK
PROVIDE LIQUIDTIGHT FLEXIBLE CONDUIT
FOR ABOVE GRADE PORTION OF CONDUIT
WITH OFFSET BEND TO ALLOW FOR
GROUND MOVEMENT, TYP.
INSULATED, THREADED BUSHING, TYP_
I
i ! TRANSITION TO GRSC FOR BELOW -GRADE
30 PORTION OF CONDUIT. SEE 1 /E 13 FOR
! i CONDUIT TRENCHING DETAIL.
t
I, WRAP BELOW GRADE PORTION OF POST
Eit WITH 2 WRAPS OF 6MIL BLACK
POLYETHYLENE_
�- PHOTOCELL
1 /2"C, 3# 12, TYP. 23'-0"
CONDUIT STRAP
TYPICAL
� NEMA 4X JUNCTION BMX
MIN. 24' SECTION OF LIQUIDTIGHT
\ FLEXIBLE CONDUIT WITH OFFSET
� BEND TO ALLOW FOR GROUND
MOVEMENT, TYP.
y PROVIDE CONDUIT SEAL WHERE
REQUIRED BY CODE.
fill
t j 24" MIN.
a k
TO CONTROL PANEL OR
`'----------- NEXT FIXTURE.
I
r"1 1L
TRANSITION TO GRSC FOR BELOW -GRADE
ILL PORTION OF CONDUIT. SEE i /E13 FOR
CONDUIT TRENCHING DETAIL.
TENON MOUNT BRACKET. SEE 12/M-4
FOR CONNECTION DETAIL.
MOUNT FIXTURE WITHIN ARMS REACH OF
TANK FROM BEHIND HAND RAIL.
IN HAZARDOUS AREAS, KEEP FIXTURE
5'-0" FROM VENTS_ INSTALL CONDUIT
SEALS AS REQUIRED BY CODE. SEE SHEET
E3.
AIM FIXTURE TO EVENLY ILLUMINATED
PIPING AND VALVES BELOW.
• •' i' i
•� i i
•
i_
i
t_
•r
1
M
co N
A w4
cm W m
Z r.
v � Q
ch Z
s z1
w N�
Z L. D Y
W Z4
0 ui
r�z
¢_ ONU¢
JN
W w
m W
co
mi zz
T
Q
0m
U
V/ QUP
=Q
cW cq
In
G
0
In
co
s 0
im Z
s
)
s�
Q o
Fn
00 >
w
OF
°°°
AM
r•
AW
°49T"
00 000 0000 0000 o�o 00000 ****4
o CHANNING ULlO o //
,® EE-10285 f
= AM fFESSi�NP� �►''
I1�xxxx
DRAWN BY: CPL
CHECKED BY: CPL
DATE: 11 /18/05
JOB NUMBER. K4193
SCALE: AS SHOWN
DRAWING TITLE:
ONE -LINE DIAGRAMS
AND DETAILS
NO SCALE � NTS �uJ NO SCALE NTS SHEET: OF
v
E2