HomeMy WebLinkAboutE4FOR ENLARGED
UVEC DISTRIBUTI
PUMP ENCIOSUi
SEE - 4
E
EW
I i
Lc-) rn
o �
o �
N
co o
0
N
0
z CD
1" = 20'-0"
>m
GENERAL NOTES: O
m
A. INSTALL ALL CONDUCTORS IN GALVANIZED RIGID CONDUIT. FIELD ROUTE AND SIZE CONDUIT TO F
ACCOMMODATE ALL CONDUCTORS PLUS 25% SPARE CAPACITY. 1/2" MINIMUM SIZE.
B. SEE SHEEP E3 FOR HAZARDOUS AREA CLASSIFICATION_ INSTALL SEAL -OFFS AND EXPLOSIONPROOF Q
EQUIPMENT WHERE REQUIRED BY CODE-
C. UNLESS
OTHERWISE
i ROUTE ABOVE
is GRADE
y ON
PIPING
f RACKS
y WHEREVER
POSSIBLE.
SHEET NOTES: �
OC
1. PROPOSED LOCATION FOR METER BASE/DISCONNECT. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH W
UTILITY PRIOR TO ROUGH -IN. SEE 1/E2 AND 2/E2_
2. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-1. INSTALL PANEL TO MEET MINIMUM NEC-110.28 W
CLEARANCE REQUIREMENTS. SEE 1/E2 AND SHEEP E8. SEE 5/E2 FOR MOUNTING DETAIL.
3. PROPOSED LOCATION FOR FUEL SYSTEM
CONTROL PANEL CP-3. INSTALL PANEL TO
MEET MINIMUM
Q
NEC-110.26 CLEARANCE REQUIREMENT.
SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR
MOUNTING DETAIL.
"
i
4. PROPOSED LOCATION FOR FUEL SYSTEM
CONTROL PANEL CP-4. INSTALL PANEL TO
MEET MINIMUM
NEC-110.26 CLEARANCE REQUIREMENT.
SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR
MOUNTING DETAIL.
I
5. PROPOSED LOCATION FOR FUEL SYSTEM
CONTROL PANEL CP-5. INSTALL PANEL TO
MEET MINIMUM
J
NEC-110.26 CLEARANCE REQUIREMENT.
SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR
MOUNTING DETAIL
Q
6. PROPOSED LOCATION FOR FUEL SYSTEM
CONTROL PANEL CP-6. INSTALL PANEL TO
MEET MINIMUM
NEC-110.26 CLEARANCE REQUIREMENT.
SEE 1/E2 AND SHEET El 1. SEE 6/E2 FOR
MOUNTING DETAIL
7. MOUNT EM-STOP TO FENCING +48" ABOVE GRADE. INSTALL NAME PLATE ABOVE. SEE EQUIPMENT LIST,
SHEET El-
8. SEE 3/E2 FOR TYPICAL LIGHT POLE DETAIL.
M
9. SEE 1/E3, 3/E3 FOR CLASSIFIED AREAS AROUND GASOLINE AND AV. GAS STORAGE TANKS. ALL WORK J °°
IN THE HAZARDOUS SHALL COMPLY WITH ARTICLES 500 AND 501 AREA OF THE NEC. PROVIDE SEAL -OFFS I N
ON ALL CONDUIT PENETRATING CLASSIFIED LOCATIONS AS REQUIRED BY CODE-
10. INSTALL WP, GFCI RECEPTACLE BELOW "CP-6". SEE 6/E2.
11- MOUNT EM STOP +48" ABOVE GRADE ON LIGHTING POLE. INSTALL NAME PLATE ABOVE PER EQUIPMENT
LIST, SHEET E1. SEE 3/E2 FOR MOUNTING DETAIL_
a
12_ INSTALL EM STOP MINIMUM 25"-0" FROM DISPENSING ENCLOSURE-
13. MOUNT MTU ANTENNA TO SECURITY LIGHT POLE. AIM TOWARD POWER PLANT. SEE 2/E13_ fi
14. MOUNT MTU TO UNISTRUT ABOVE DIKE WALL SIMILAR TO 5/E2.4a_
a
w
15- SEE 4/E2 FOR TYPICAL LIGHT POLE DETAIL AT TANK FARM. INSTALL POLE NEAR CONTROL PANEL.
w
16_ INSTALL WP, GFCI RECEPTACLE TO UNISTRUT SUPPORT ABOVE DIKE WALL ADJACENT TO CONTROL PANEL. mi
EQUIPMENT SCHEDULE
CIRCUIT TAG
SOURCE
DESTINATION
HP
AMPS
VOLTS
PHASE
CONDUCTORS (CU, XHHW)
SCHEDULE NOTES
CP 1-03
CP-1
TANK MOUNTED POWER PLANT AREA LIGHTS
5
120
1
2# 10, 1 # 10 G
6,8
CP 1-04
CP-1
POWER PLANT SECURITY POLE LIGHT
1.6
120
1
2# 12, 1 # 12 G
7,8
CP 1-05
CP-1
MTU
4
120
1
8# 12, 1# 12 G
8
CP 1-06
CP-1
EM-3
N/A
120
1
2# 12, 1 # 12 G
8
CP 1-07
CP-1
GFCI RECEPTACLE
1.5
120
1
2# 12, 1 # 12 G
8
CP3-13
CP-3
TANK MOUNTED SCHOOL AREA LIGHTS
5
120
1
2# 10, 1 # 10 G
2,6
CP3-14
CP-3
SCHOOL SECURITY POLE LIGHT
1.6
120
1
2# 12, 1 # 12 G
2,7
CP4-13
CP-4
TANK MOUNTED AV. SERVICE AREA LIGHTS
5
120
1
2# 10, 1 # 10 G
1,2,6
CP4-14
CP-4
AV. SERVICE SECURITY POLE LIGHT
1.6
120
1
2# 12, 1 # 12 G
1,2,7
CP4-15
CP-4
HIGH LEVEL HORN /STROBE HS-1
0.1
120
1
2# 12, 1 12 G
1,2,10
CP4-16
CP-4
HIGH LEVEL FLOAT SWITCH TANK #11
N/A
120
1
2 12, 1#12 G
1,2,10
CP4-17
CP-4
HIGH LEVEL FLOAT SWITCH TANK # 12
N/A
120
1
2# 12, 1 # 12 G
1,2,10
CP4-18
CP-4
HIGH LEVEL FLOAT SWITCH TANK #13
N/A
120
1
2 12, 1 12 G
1,2,10
CP4-19
CP-4
HIGH LEVEL FLOAT SWITCH TANK #14
N/A
120
1
2# 12, 1 # 12 G
1,2,10
CP5-13
CP-5
TANK MOUNTED CORPORATION AREA LIGHTS
5
120
1
2#10, 1#10 G
1,2,6
CP5-14
CP-5
CORPORATION SECURITY POLE LIGHT
1.6
120
1
2# 12, 1 # 12 G
1,2,7
CP5-15
CP-5
HIGH LEVEL HORN /STROBE HS-2
0.1
120
1
2# 12, 1 # 12 G
1,2,9
CP5-16
CP-5
HIGH LEVEL FLOAT SWITCH TANK #24
N/A
120
1
2# 12, 1 # 12 G
1,2,9
CP5-17
CP-5
HIGH LEVEL FLOAT SWITCH TANK #25
N/A
120
1
2# 12, 1#12 G
1,2,9
CP5-18
CP-5
HIGH LEVEL FLOAT SWITCH TANK #26
N/A
120
1
2# 12, 1 # 12 G
1,2,9
C136-01
CP-6
AREA DRIVE THROUGH LIGHTS
7.5
208
1
2#8, 1#8 G
1,3,4
CP6-02
CP-6
SECURITY DRIVE THROUGH LIGHT
1.5
208
1
2#8, 1 #8 G
1,3,5
CP6-03
CP-6
EM-1
N/A
120
1
2# 12, 1 # 12 G
1,3
CP6-04
CP-6
EM-2
N/A
120
1
2#12, 1#12 G
1,3
CP6-05
CP-6
CP-3 (EM SHUTOFF LOCKOUT RELAY)
N/A
120
1
2# 12, 1 # 12 G
1,3
CP6-06
CP-6
CP-4 EM SHUTOFF LOCKOUT RELAY
N A
120
1
2 12, 1 12 G
1,3
CP6-07
CP-6
CP-5 (EM SHUTOFF LOCKOUT RELAY)
VA
120
1
2# 12, 1 # 12 G
1,3
CP6-08
CP-6
GFCI RECEPTACLE
1.5
120
1
2# 12, 1 # 12 G
1,3
SCHEDULE NOTES:
1. PROVIDE SEAL —OFF AT CONNECTION AS REQUIRED PER CODE.
2. SEE 1/E10 FOR WIRING CONNECTIONS.
3. SEE 1/E11 FOR WIRING CONNECTIONS.
4. CONTROL WITH AREA DRIVE THROUGH SELECTOR SWITCH INSTALLED IN CONTROL PANEL.
5. CONTROL WITH SECURITY DRIVE THROUGH SELECTOR SWITCH INSTALLED IN CONTROL PANEL.
6- CONTROL WITH LOCAL AREA LIGHT SELECTOR SWITCH INSTALLED IN CONTROL PANEL.
7. CONTROL WITH LOCAL SECURITY LIGHT SELECTOR SWITCH INSTALLED IN CONTROL PANEL.
8_ SEE 2/E8 FOR WIRING CONNECTIONS.
9- SEE 2/E11 FOR WIRING CONNECTIONS.
10. SEE 4/E11 FOR WIRING CONNECTIONS_
VERIFY SCALES
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
IF NOT ONE INCH ON
THIS SHEET, ADJUST
SCALES ACCORDINGLY.
i N
reo
W C°
C
z_ 5`
V' o
..20
� zN
W z¢
�t1 0 0
W g
<0
m0�Q
Vo
W
W w
Qci
�1 Q J
U 0°
-v
V/ U Q
=a
WN
N
��- OFAW
AW
o�
°4�
'','°°°°°...°.°°°° nzit °° 010
°°°°°° °°�
CHANNING LILLO o � oo
EE-10285 w
� � r
AM
l�l ��ssto�P�. �►�.
DRAWN BY: CPL
CHECKED BY: CPL
DATE: 11 /18/05
JOB NUMBER: K4193
SCALE: AS SHOWN
DRAWING TITLE:
ELECTRICAL PLAN
BULK TANK FARM
SHEET: OF
z"I