HomeMy WebLinkAboutE4FOR ENLARGED UVEC DISTRIBUTI PUMP ENCIOSUi SEE - 4 E EW I i Lc-) rn o � o � N co o 0 N 0 z CD 1" = 20'-0" >m GENERAL NOTES: O m A. INSTALL ALL CONDUCTORS IN GALVANIZED RIGID CONDUIT. FIELD ROUTE AND SIZE CONDUIT TO F ACCOMMODATE ALL CONDUCTORS PLUS 25% SPARE CAPACITY. 1/2" MINIMUM SIZE. B. SEE SHEEP E3 FOR HAZARDOUS AREA CLASSIFICATION_ INSTALL SEAL -OFFS AND EXPLOSIONPROOF Q EQUIPMENT WHERE REQUIRED BY CODE- C. UNLESS OTHERWISE i ROUTE ABOVE is GRADE y ON PIPING f RACKS y WHEREVER POSSIBLE. SHEET NOTES: � OC 1. PROPOSED LOCATION FOR METER BASE/DISCONNECT. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH W UTILITY PRIOR TO ROUGH -IN. SEE 1/E2 AND 2/E2_ 2. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-1. INSTALL PANEL TO MEET MINIMUM NEC-110.28 W CLEARANCE REQUIREMENTS. SEE 1/E2 AND SHEEP E8. SEE 5/E2 FOR MOUNTING DETAIL. 3. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-3. INSTALL PANEL TO MEET MINIMUM Q NEC-110.26 CLEARANCE REQUIREMENT. SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR MOUNTING DETAIL. " i 4. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-4. INSTALL PANEL TO MEET MINIMUM NEC-110.26 CLEARANCE REQUIREMENT. SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR MOUNTING DETAIL. I 5. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-5. INSTALL PANEL TO MEET MINIMUM J NEC-110.26 CLEARANCE REQUIREMENT. SEE 1/E2 AND SHEET E10. SEE 5/E2 FOR MOUNTING DETAIL Q 6. PROPOSED LOCATION FOR FUEL SYSTEM CONTROL PANEL CP-6. INSTALL PANEL TO MEET MINIMUM NEC-110.26 CLEARANCE REQUIREMENT. SEE 1/E2 AND SHEET El 1. SEE 6/E2 FOR MOUNTING DETAIL 7. MOUNT EM-STOP TO FENCING +48" ABOVE GRADE. INSTALL NAME PLATE ABOVE. SEE EQUIPMENT LIST, SHEET El- 8. SEE 3/E2 FOR TYPICAL LIGHT POLE DETAIL. M 9. SEE 1/E3, 3/E3 FOR CLASSIFIED AREAS AROUND GASOLINE AND AV. GAS STORAGE TANKS. ALL WORK J °° IN THE HAZARDOUS SHALL COMPLY WITH ARTICLES 500 AND 501 AREA OF THE NEC. PROVIDE SEAL -OFFS I N ON ALL CONDUIT PENETRATING CLASSIFIED LOCATIONS AS REQUIRED BY CODE- 10. INSTALL WP, GFCI RECEPTACLE BELOW "CP-6". SEE 6/E2. 11- MOUNT EM STOP +48" ABOVE GRADE ON LIGHTING POLE. INSTALL NAME PLATE ABOVE PER EQUIPMENT LIST, SHEET E1. SEE 3/E2 FOR MOUNTING DETAIL_ a 12_ INSTALL EM STOP MINIMUM 25"-0" FROM DISPENSING ENCLOSURE- 13. MOUNT MTU ANTENNA TO SECURITY LIGHT POLE. AIM TOWARD POWER PLANT. SEE 2/E13_ fi 14. MOUNT MTU TO UNISTRUT ABOVE DIKE WALL SIMILAR TO 5/E2.4a_ a w 15- SEE 4/E2 FOR TYPICAL LIGHT POLE DETAIL AT TANK FARM. INSTALL POLE NEAR CONTROL PANEL. w 16_ INSTALL WP, GFCI RECEPTACLE TO UNISTRUT SUPPORT ABOVE DIKE WALL ADJACENT TO CONTROL PANEL. mi EQUIPMENT SCHEDULE CIRCUIT TAG SOURCE DESTINATION HP AMPS VOLTS PHASE CONDUCTORS (CU, XHHW) SCHEDULE NOTES CP 1-03 CP-1 TANK MOUNTED POWER PLANT AREA LIGHTS 5 120 1 2# 10, 1 # 10 G 6,8 CP 1-04 CP-1 POWER PLANT SECURITY POLE LIGHT 1.6 120 1 2# 12, 1 # 12 G 7,8 CP 1-05 CP-1 MTU 4 120 1 8# 12, 1# 12 G 8 CP 1-06 CP-1 EM-3 N/A 120 1 2# 12, 1 # 12 G 8 CP 1-07 CP-1 GFCI RECEPTACLE 1.5 120 1 2# 12, 1 # 12 G 8 CP3-13 CP-3 TANK MOUNTED SCHOOL AREA LIGHTS 5 120 1 2# 10, 1 # 10 G 2,6 CP3-14 CP-3 SCHOOL SECURITY POLE LIGHT 1.6 120 1 2# 12, 1 # 12 G 2,7 CP4-13 CP-4 TANK MOUNTED AV. SERVICE AREA LIGHTS 5 120 1 2# 10, 1 # 10 G 1,2,6 CP4-14 CP-4 AV. SERVICE SECURITY POLE LIGHT 1.6 120 1 2# 12, 1 # 12 G 1,2,7 CP4-15 CP-4 HIGH LEVEL HORN /STROBE HS-1 0.1 120 1 2# 12, 1 12 G 1,2,10 CP4-16 CP-4 HIGH LEVEL FLOAT SWITCH TANK #11 N/A 120 1 2 12, 1#12 G 1,2,10 CP4-17 CP-4 HIGH LEVEL FLOAT SWITCH TANK # 12 N/A 120 1 2# 12, 1 # 12 G 1,2,10 CP4-18 CP-4 HIGH LEVEL FLOAT SWITCH TANK #13 N/A 120 1 2 12, 1 12 G 1,2,10 CP4-19 CP-4 HIGH LEVEL FLOAT SWITCH TANK #14 N/A 120 1 2# 12, 1 # 12 G 1,2,10 CP5-13 CP-5 TANK MOUNTED CORPORATION AREA LIGHTS 5 120 1 2#10, 1#10 G 1,2,6 CP5-14 CP-5 CORPORATION SECURITY POLE LIGHT 1.6 120 1 2# 12, 1 # 12 G 1,2,7 CP5-15 CP-5 HIGH LEVEL HORN /STROBE HS-2 0.1 120 1 2# 12, 1 # 12 G 1,2,9 CP5-16 CP-5 HIGH LEVEL FLOAT SWITCH TANK #24 N/A 120 1 2# 12, 1 # 12 G 1,2,9 CP5-17 CP-5 HIGH LEVEL FLOAT SWITCH TANK #25 N/A 120 1 2# 12, 1#12 G 1,2,9 CP5-18 CP-5 HIGH LEVEL FLOAT SWITCH TANK #26 N/A 120 1 2# 12, 1 # 12 G 1,2,9 C136-01 CP-6 AREA DRIVE THROUGH LIGHTS 7.5 208 1 2#8, 1#8 G 1,3,4 CP6-02 CP-6 SECURITY DRIVE THROUGH LIGHT 1.5 208 1 2#8, 1 #8 G 1,3,5 CP6-03 CP-6 EM-1 N/A 120 1 2# 12, 1 # 12 G 1,3 CP6-04 CP-6 EM-2 N/A 120 1 2#12, 1#12 G 1,3 CP6-05 CP-6 CP-3 (EM SHUTOFF LOCKOUT RELAY) N/A 120 1 2# 12, 1 # 12 G 1,3 CP6-06 CP-6 CP-4 EM SHUTOFF LOCKOUT RELAY N A 120 1 2 12, 1 12 G 1,3 CP6-07 CP-6 CP-5 (EM SHUTOFF LOCKOUT RELAY) VA 120 1 2# 12, 1 # 12 G 1,3 CP6-08 CP-6 GFCI RECEPTACLE 1.5 120 1 2# 12, 1 # 12 G 1,3 SCHEDULE NOTES: 1. PROVIDE SEAL —OFF AT CONNECTION AS REQUIRED PER CODE. 2. SEE 1/E10 FOR WIRING CONNECTIONS. 3. SEE 1/E11 FOR WIRING CONNECTIONS. 4. CONTROL WITH AREA DRIVE THROUGH SELECTOR SWITCH INSTALLED IN CONTROL PANEL. 5. CONTROL WITH SECURITY DRIVE THROUGH SELECTOR SWITCH INSTALLED IN CONTROL PANEL. 6- CONTROL WITH LOCAL AREA LIGHT SELECTOR SWITCH INSTALLED IN CONTROL PANEL. 7. CONTROL WITH LOCAL SECURITY LIGHT SELECTOR SWITCH INSTALLED IN CONTROL PANEL. 8_ SEE 2/E8 FOR WIRING CONNECTIONS. 9- SEE 2/E11 FOR WIRING CONNECTIONS. 10. SEE 4/E11 FOR WIRING CONNECTIONS_ VERIFY SCALES BAR IS ONE INCH ON ORIGINAL DRAWING 0 1" IF NOT ONE INCH ON THIS SHEET, ADJUST SCALES ACCORDINGLY. i N reo W C° C z_ 5` V' o ..20 � zN W z¢ �t1 0 0 W g <0 m0�Q Vo W W w Qci �1 Q J U 0° -v V/ U Q =a WN N ��- OFAW AW o� °4� '','°°°°°...°.°°°° nzit °° 010 °°°°°° °°� CHANNING LILLO o � oo EE-10285 w � � r AM l�l ��ssto�P�. �►�. DRAWN BY: CPL CHECKED BY: CPL DATE: 11 /18/05 JOB NUMBER: K4193 SCALE: AS SHOWN DRAWING TITLE: ELECTRICAL PLAN BULK TANK FARM SHEET: OF z"I