r
1/2" = V-0"
AV. GAS JET 'A'
1/2" =1'-0"
FUEL OIL UNLEADED
1 /2" =1 `-0"
® !
�
C'
EQUIPMENT SCHEDULE
CIRCUIT TAG
SOURCE
DESTINATION
HP
AMPS
VOLTS
PHASE
CONDUCTORS (CU, XHHW)
SCHEDULE NOTES
CP 1-01
CP-1
DISTRIBUTION PUMP 'DP-1
15
208
3
3#6, 1 #8 G
6,7
CP 1-02
CP-1
ACTUATED BALL VALVE 'A-1'
5.0
120
1
6# 12, 1 # 12 G
6,7
CP 1-08
CP-1
DISPENSER ENCLOSURE LIGHT
2.5
120
1
2# 12, 1 # 12 G
4,7
CP3-01
CP-3
TRANSFER PUMP 'TP-1'
2
208
1
2# 12, 1 # 12 G
2,3
CP3-02
CP-3
ACTUATED BALL VALVE 'A-2'
1.6
120
1
6# 12, 1 # 12 G
2,3
CP3-03
CP-3
FLOW METER
0.2
2# 12, 1 # 12 G
2
CP3-04
CP-3
TRUCK FILL CABINET LIGHTING
2.5
120
1
2#12, 1#12 G
3,4
CP3-05
CP-3
ELECTRIC HOSE REEL 'EHR-1'
1 /2
120
1
2# 12, 1 # 12 G
3,5
CP3-06
CP-3
'TP-1' PUMP START/STOP SWITCH
N/A
2# 12, 1 # 12 G
2
CP3-07
CP-3
TRANSFER PUMP 'TP-2'
2
208
1
2# 12, 1 # 12 G
2,3
CP3-08
CP-3
ACTUATED BALL VALVE 'A-3'
1.6
120
1
6 12, 1 12 G
2,3
CP3-09
CP-3
FLOW METER
0.2
2# 12, 1 # 12 G
2
CP3-10
CP-3
TRUCK FILL CABINET LIGHTING
2.5
120
1
2# 12, 1 # 12 G
3,4
CP3-11
CP-3
ELECTRIC HOSE REEL 'EHR-2'
1 /2
120
1
2# 12, 1 # 12 G
3,4
CP3-12
CP-3
'TP-2' PUMP START/STOP SWITCH
N/A
2# 12, 1 # 12 G
2
CP4-01
CP-4
TRANSFER PUMP 'TP-3'
2
208
1
2# 12, 1 # 12 G
1,2,3
CP4-02
CP-4
ACTUATED BALL VALVE 'A-4'
1.6
120
1
6# 12, 1 # 12 G
1,2,3
CP4-03
CP-4
FLOW METER
0.2
2# 12, 1 # 12 G
1,2
CP4-04
CP-4
TRUCK FILL CABINET LIGHTING
2.5
120
1
2 12, 1 # 12 G
1,3,4
CP4-05
CP-4
ELECTRIC HOSE REEL 'EHR-3'
1 /2
120
1
2# 12, 1 # 12 G
1,3,5
CP4-06
CP-4
'TP-3' PUMP START STOP SWITCH
N/A
2 12, 1#12 G
1,2
CP4-07
CP-4
TRANSFER PUMP 'TP-4'
2
208
1
2# 12, 1 # 12 G
1,2,3
CP4-08
CP-4
ACTUATED BALL VALVE 'A-5'
1.6
120
1
6# 12, 1 # 12 G
1,2,3
CP4-09
CP-4
FLOW METER
0.2
2# 12, 1 # 12 G
1,2
CP4-10
CP-4
TRUCK FILL CABINET LIGHTING
2.5
120
1
2 12, 1 12 G
1,3,4
CP4-11
CP-4
ELECTRIC HOSE REEL 'EHR-4'
1 j2
120
1
2# 12, 1 12 G
1,3,5
CP4-12
CP-4
'TP-4' PUMP START/STOP SWITCH
N/A
2#12, 1#12 G
1,2
CP5-01
CP-5
TRANSFER PUMP 'TP-5'
2
208
1
2# 12, 1 # 12 G
1,2,3
CP5-02
CP-5
ACTUATED BALL VALVE 'A-6'
1.6
120
1
6# 12, 1 # 12 G
1,2,3
CP5-03
CP-5
FLOW METER
0.2
2# 12, 1 # 12 G
1,2
CP5-04
CP-5
TRUCK FILL CABINET LIGHTING
2.5
120
1
2#12, 1#12 G
1,3,4
CP5-05
CP-5
ELECTRIC HOSE REEL 'EHR-5'
1 /2
120
1
2# 12, 1 # 12 G
1,3,5
CP5-06
CP-5
'TP-5' PUMP START/STOP SWITCH
N/A
2# 12, 1 # 12 G
1,2
CP5-07
CP-5
TRANSFER PUMP 'TP-6'
2
208
1
2# 12, 1 # 12 G
1,2,3
CP5-08
CP-5
ACTUATED BALL VALVE 'A-7'
1.6
120
1
6# 12, 1 # 12 G
1,2,3
CP5-09
CP-5
FLOW METER
0.2
2# 12, 1 # 12 G
1,2
CP5-10
CP-5
TRUCK FILL CABINET LIGHTING
2.5
120
1
2#12, 1#12 G
1,3,4
CP5-11
CP-5
ELECTRIC HOSE REEL 'EHR-6'
1 /2
120
1
2# 12, 1 # 12 G
1,3,5
CP5-12
CP-5
'TP-6' PUMP START/STOP SWITCH
N/A
2#12, 1#12 G
1,2
SCHEDULE NOTES:
I. PROVIDE SEAL -OFF AT CONNECTION AS REQUIRED PER CODE.
2. SEE 1/E10 FOR WIRING CONNECTIONS_
3. SEE 2/E10 FOR WIRING CONNECTIONS.
4. CONTROL WITH LOCAL LIGHT SWITCH AS SHOWN ON PLAN_
5. CONTROL WITH LOCAL MOMENTARY CONTACT PUSHBUTTON.
6. SEE 1/E8 FOR WIRING CONNECTIONS.
7. SEE 2/E8 FOR WIRING CONNECTIONS.
GENERAL NOTES:
A. INSTALL ALL CONDUCTORS IN GALVANIZED RIGID CONDUIT. FIELD ROUTE AND SIZE CONDUIT TO
ACCOMODATE ALL CONDUCTORS PLUS 25% SPARE CAPACITY. 1/2" MINIMUM SIZE.
B. SEE SHEET E3 FOR HAZARDOUS AREA CLASSIFICATION. INSTALL SEAL -OFFS AND EXPLOSIONPROOF
EQUIPMENT WHERE REQUIRED BY CODE.
C. SEE 1/E4 FOR LOCATION OF CONTROL PANELS 'CP-3', CP-4', AND 'CP-5'.
SHEET NOTES:
1. PROVIDE CLASS 1, DIVISION 2 START/STOP CONTROL STATION. MOUNT TO UNISTRUT WELDED BRACKET_
COORDINATE EXACT LOCATION IN CABINET WITH OTHER EQUIPMENT PRIOR TO ROUGH -IN_
2. PROVIDE CLASS 1, DIVISION 2 MOMENTARY PUSHBUTTON TO CONTROL RE -WIND FEATURE OF ELECTRIC
HOSEREEL. MOUNT TO UNISTRUT WELDED BRACKET. COORDINATE EXACT LOCATION IN CABINET WITH
OTHER EQUIPMENT PRIOR TO ROUGH -IN_
3. PROVIDE CONNECTION TO ELECTRONIC FUEL METER. SEE 1 /Ei 0.
4. PROVIDE NEMA 4X START/STOP CONTROL STATION. MOUNT TO UNISTRUT WELDED BRACKET.
COORDINATE EXACT LOCATION IN CABINET WITH OTHER EQUIPMENT PRIOR TO ROUGH -IN_
5. PROVIDE NEMA 4X MOMENTARY PUSHBUTTON TO CONTROL RE —WIND FEATURE OF ELECTRIC
HOSEREEL. MOUNT TO UNISTRUT WELDED BRACKET. COORDINATE EXACT LOCATION IN CABINET WITH
OTHER EQUIPMENT PRIOR TO ROUGH —IN.
6. PROVIDE #2 B.C. FROM STATIC GROUNDING REEL TO SYSTEM GROUND. SEE 5/E3.
7_ PROVIDE NEMA 4X LIGHT SWITCH.
8_ PROVIDE CLASS 1, DIVISION 2 RATED LIGHT SWITCH.
1/2" =1'-0"
VERIFY SCALES
BAR IS ONE INCH ON
ORIGINAL DRAWING
0 1"
IF NOT ONE INCH ON
THIS SHEET, ADJUST
SCALES ACCORDINGLY.
9
■ N
uj 9
Zcm
~
��
F Z
0U)
Z N
M
� mY
ZQ
00
U0 c:
F-U
�a
c Uo
J N
WWw
05
Zw
Q
Um
U
V/
U04
Q
w 04
�04
.•• OF q ��
AMW
a00000a000000000 �� �,
,s o0 0
d.o* 4�0....000oao00 ooao o00 0000000 1 00
® o CHANNING LiLLO o00
® %EE-10285 AW
DRAWN BY: CPL
CHECKED BY: CPL
DATE: 11 / 18/05
JOB NUMBER: K4193
SCALE: AS SHOWN
DRAWING TITLE:
TRUCK FILL
ENLARGED ELECTRICAL
PLANS
SHEET: OF