Loading...
HomeMy WebLinkAboutE9L1 N REMOTE EMERGENCY SHUT-OFF ACTIVATED ALARM LIGHT (TANK FARM) RTU-1 CONTROL SCHEDULE INPUTS CONTROL FUNCTION DIi MTU (Kt) OPEN VALVE A=1 &START/STOP DISTRIBUTION PUMP DP-1 DI2 SPARE DI3 SPARE DI4 SPARE OUTPUTS K1 MTU (DI 1) BULK TANK FARM EM STOP ACTIVATED K2 MTU (DI2) DP-1 RUNNING LIGHT K3 SPARE K4 SPARE UVEC INTERMEDIATE TANK: USER TURNS ON THE SELECTOR SWITCH AT THE INTERMEDIATE TANK CONTROL PANEL `CP-2' LOCATED AT THE INTERMEDIATE TANK AND 'CP-1' LOCATED AT THE BULK TANK FARM TO TRANSFER FUEL. USER PRESSES THE PUMP START BUTTON AT CONTROL PANEL `CP-2'. A SIGNAL IS SENT TO OPEN ACTUATED BALL VALVE 'A-1' VIA RTU-1. AS SOON AS THE VALVE BEGINS TO OPEN, A "VALVE OPEN" LIGHT IS ILLUMINATED ON 'CP-11 . WHEN THE ACTUATED BALL. VALVE IS FULLY OPENED, A SIGNAL IS SENT TO TURN THE DISTRIBUTION PUMP `DP-1' ON, AND A "PUMP ON" LIGHT IS ILLUMINATED ON `CP-2' AND `CP-1' VIA `RTU-1'. THIS SHALL ALLOW FUEL TO FLOW FROM ONE OF THE MANUALLY SELECTED BULK TANKS TO THE INTERMEDIATE TANK_ TIMER `T-1' IS ENABLED TO ALLOW THE PUMP TO BE OPERATIONAL FOR AN ADJUSTABLE 0-16 HOURS, INITIALLY SET AT 7.5 HR_ USER PRESSES PUMP STOP BUTTON AT CONTROL PANEL `CP-2', CAUSING THE ACTUATED BALL VALVE AT THE BULK TANK FARM (A-1) TO CLOSE AND THE DISTRIBUTION PUMP TO STOP AT THE BULK TANK FARM VIA THE TELEMETRY PANEL `RTU-1'. A LIGHT SHALL BE ILLUMINATED AT CONTROL PANEL 'CP-1' WHEN THE ACTUATED BALL VALVE IS FULLY CLOSED. THE PUMP "ON" LIGHTS SHALL BE TURNED OFF AT BOTH CONTROL PANELS `CP-2' AND 'CP-1' VIA `RTU-1'. IN THE EVENT THAT THE INTERMEDIATE TANKS HIGH LEVEL SWITCH IS ACTIVATED, IT DOES THE SAME FUNCTION AS THE "STOP" BUTTON, PLUS A LIGHT SHALL BE ACTIVATED AT CONTROL PANEL `CP-2' INDICATING A HIGH FUEL LEVEL IN THE INTERMEDIATE TANK. ONCE THE HIGH FUEL LEVEL IS CLEARED, THE RESET BUTTON SHALL BE PRESSED TO CLEAR THE FAULT. IF THE CRITICAL HIGH SWITCH IS ACTIVATED, IT DOES THE SAME FUNCTION AS THE HIGH LEVEL SWITCH, PLUS IT ACTIVATES A CRITICAL LEVEL LIGHT AND A HORN STROBE LOCATED ABOVE 'CP-2' IF THE ALARM "SILENCE" BUTTON IS PRESSED, THE ALARM HORN IS DEACTIVATED (THE STROBE STAYS ENERGIZED)_ ONCE THE FAULT IS CLEARED AND THE RESET BUTTON IS PRESSED, THE HORN SIGNAL RETURNS TO ITS PREVIOUS STATE. a i" • a IF THE EMERGENCY PUSHBUTTON 'EM-3' IS ACTIVATED AT THE BULK TANK o r H-3 INTERMEDIATE TANK FARM, IT DOES THE SAME FUNCTION AS THE "STOP" BUTTON, PLUS ALL � N R1 HIGH LEVEL LOCKOUT RELAY CONTROL POWER IS SHUT DOWN AT THE CONTROL PANEL CP-1 WITH THE J � C.? W _ EXCEPTION OF THE HEATER, EM LOCKOUT RELAY, EXTERIOR LIGHT AND MTU_ IN THE EVENT THAT THE ACTUATED BALL VALVE IS OPEN WHEN THE Zst INTERMEDIATE TANK o FIELD + t i -- HIGH/CRITICAL HIGH 2_2 A z 2 FLOAT SWITCH, TYP. E-STOP IS PRESSED, A SIGNAL SHALL BE SENT FOR THE VALVE TO CLOSE. JUMPER, i + HIGH LEVEL LIGHT W i f C-3 ► ONCE THE VALVE IS FULLY CLOSED, ALL POWER SHALL BE DEACTIVATED AT 0 to TYPICAL. + 11 R2 INTERMEDIATE TANK THE ACTUATED BALL VALVE. A LIGHT IS ALSO ACTIVATED AT CONTROL PANEL w z N + CRITICAL LEVEL LOCKOUT RELAY `CP-1' AND CONTROL PANEL `CP-2' VIA THE TELEMETRY PANEL. rn R4-1 R1 _2 ` R' INTERMEDIATE TANK TO RESET THE SYSTEM, THE EM STOP MUSHROOM BUTTON 'EM-3' MUST BE (!} z Q If/CRITICAL LEVEL LIGHT REMOTE CIRCUIT BREAKER IN POWER PLANT PULLED BACK OUT WHICH WILL AUTOMATICALLY RESET THE SYSTEM BACK TO 0 w" SEE 1 /E6. NORMAL_ Q o MASTER POWER + + • � 0: Q 1 �� +T T+ EQUIPMENT GROUNDING CONDUCTOR 2 SS1wo SWITCH i � AND NEUTRAL. _ v• c J N START STOP _ i i LLI o �^ R1 1 R2-1 T1-1 J z� Qo --� R3 OPEN VALVE SIGNAL RELAY U m R3-1 FIELD ADJUST TO ALLOW NORMAL TANK FILL LABEL BREAKER AS: 40 T1 0-16 HR "ON" TIME DELAY RELAY "MAIN DISCONNECT. N Tm .. QU SET AT 7.5 HRS, TURN OFF BEFORE V1920 2 DISCONNECT 0 N - - - - - - � r - _ SERVICING PANEL".WN 4 4 / 1 32N ItYf u i it n.7 II9u�t�n{ cu, 1 1 F. DI o 0 OPEN VALVE `A-1' AND START/STOP _ _RTU _1_ _ DISTRIBUTION PUMP `DP-1' INPUT TO RTU NO SCALE DIESEL DISTRIBUTION PUMP 'DP-1' "ON" LIGHT FUEL SYSTEM "ON" LIGHT INTERMEDIATE TANK CRITICAL HIGH LEVEL HORN/STROBE FLOAT RESET RELAY HIGH LEVEL ALARM SILENCE RELAY SS-1 THRU SS-2 CONTACTS POSITION N OFF X - INDICATES CONTACT CLOSED NO SCALE I 20/1- SS2 1„ 11 -2 15/1 15/1 SPARE 15/1 r-----------------i THERMOSTATIC HEATER i SWITCH 10 1 + FAN N 15/1 1 1-�' CONTROL CIRCUIT SEE 1 /E9. CONTROL PANEL ENCLOSURE 0 a i 9 1 as '1 0 PHOTOCELL EXTERIOR LIGHT REMOTE TELEMETRY UNIT 'RTU-1' POWER PLAINTERMEDIATE CONTROL PANEL• PANELFUEL EM STOP SYSTEM SWITCH TANK O 1' DIESEL PIPELINE DISTRIBUTION DP STARTO- ON INTERMEDIATE iHIGH LEVEL - IT. LEVEL RESET SILENCE t��.► rim.►. v OF .. a ♦I ;�'q�_*4- 9T"00 oo°CHANNI L ®r EE-10285AM nr %FESSQfl 41p DRAWN BY: CPL CHECKED BY: CPL DATE: 11 / 18/05 JOB NUMBER: K4193 SCALE: AS SHOWN DRAWING TITLE: CONTROL PANEL 'CP-2$ SCHEMATIC DIAGRAMS AND DETAILS SHEET: OF