Loading...
HomeMy WebLinkAboutUIG-Program-Grants 1996-to-1999Project Completion Report Alaska Energy Authority, Rural Energy Programs Chevak AVEC Diesel Engine Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: Budget Code 15629 Completion Date: 10/7/99 Agreement Number: 2175048 Election District: 38 Install electronic diesel generation set in Alaska Village Electric Cooperative (AVEC) power house in Chevak. A side benefit of electronically-controlled engines, in addition to decreased fuel requirements, is reduced emissions to the environment and the release of little or no exhaust smoke from start-up to full load. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's 25% share of total project cost. Page 134 Project Completion Report Alaska Energy Authority, Rural Energy Programs Ambler AVEC Diesel Engine Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: Budget Code 15627 Completion Date: 12/31/98 Agreement Number: 2175047 Election District: 37 This project installed a new diesel electric generating set with electronically-controlled, variable injection timing within the Alaska Village Electric Cooperative (AVEC) power house in Ambler to increase generating efficiency. In the course of installation, AVEC provided the Division with product information and engineering, a cost estimate breakdown and information on environmental impact. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's 25% share of total project cost. Page 138 Project Completion Report Alaska Energy Autholity, Rural Energy Programs Diomede New Generator Project Program: Rural Power System Upgrade Recipient: Diomede Joint Utilities Total Cost: $50,105.00 Funding Sources: Division: $37,579.00 Federal: Local: Other: $0.00 $12,526.00 $0.00 Project Description: \ Budget Code 15636 Completion Date: 10/28/98 Agreement Number: 2175057 Election District: 37 Purchase and install a new 180 kilowatt generator set to replace and upgrade one of Diomede Joint Utilities' existing generator sets. Supplemental Information: Project identified through the Utility Improvement Grant (UIG) Program process. Page 140 Project Completion Report Alaska Energy Authority, Rural Energy Programs Diomede New Power House Project Program: Rural Power System Upgrade Recipient: City of Diomede Total Cost $155,695.00 Funding Sources: Division: $116,771.00 Federal: Local: Other: $0.00 $38,924.00 $0.00 Project Description: Budget Code 15333 Completion Date: 7/24/98 Agreement Number: 2165059 Election District: 37 Design and construct one 20-foot by 34-foot panelized utility power house complete with foundation to replace existing Diomede facility. Purchase and install one 205 kW diesel generator set with related equipment: install two generator sets and related equipment from existing facility into new power house. Supplemental Information: The Division provided matching funds through the competitive Utility Improvement Grant (UIG) program. City of Diomede provided local funding •• 25% of total project cost. Page 141 Project Completion Report Alaska Energy Authority, Rural Energy Programs Galena Electric Distribution Upgrade Project Program: Rural Power System Upgrade Recipient City of Galena Tota! Cost: $111,000.00 Funding Sources: Division: $83,250.00 Federal: Local: Other: $0.00 $27,750.00 $0.00 Project Description: Budget Code 15189 Completion Date: 10/28/98 Agreement Number: 2155281 Election District: 36 A 1 :1 transformer was installed and a city feeder was removed to provide generator protection. Phase Ill of an electric distribution project was completed. The Division granted funds from the Utility Improvement Grant (UIG) program and administered the grant. Supplemental Information: Local funding was from the City of Galena which also provided all management, design, procurement and construction of the ·improvements. Page 143 Project Completion Report Alaska Energy Authority, Rural Energy Programs lliamna INNEC Metering, Heating Project Program: Rural Power System Upgrade Recipient: lliamna-Newhalen-Nondalton Electric Cooperative Total Cost: $152,000.00 Funding Sources: Division: $114,000.00 Federal: Local: Other: $0.00 $38,000.00 $0.00 Project Description: \ Budget Code 15624 Completion Date: 9/30/98 Agreement Number: 2175052 Election District: 40 This project had two components: 1. Agreement 2175052 -purchase and install new time-of- day metering equipment for lliamna-Newhalen-Nondalton Electric Cooperative (INNEC) which can distinguish at which time during the day power is being used. This will shift some demand to off-peak hours at lower rates and stimulate new electrical demand that was, for the most part, previously served by fuel oil and propane. The Tazimina Hydroelectric Project will supply the new power requirements. 2. Agreement 2175051 -install new electric boilers in the Newhalen and Nondalton schools in series with the existing oil-fired boilers. The project will use surplus power from the Tazimina Hydroelectric Project. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is from lliamna-Newhalen- Nondalton Electric Cooperative (INNEC) and represents required recipient contribution of 25% of total project cost. Page 144 Project Completion Report Alaska Energy Authortty, Rural Energy Programs Nikolai New Powerhouse Project Program: Rural Power System Upgrade Recipient: Nikolai Light and Power Utility Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: Budget Code 15625 Completion Date: 9/30/98 Agreement Number: 2175053 Election District: 36 Install a new powerhouse on a new gravel pad in Nikolai; relocate four diesel generator sets into the new building, re-pipe the day tank and relocate the waste heat system. Prepare as- built drawings of the completed project that are stamped and approved by an Alaska- registered engineer. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution from Nikolai Light and Power Utility which is owned by the City of Nikolai. It represents the required local grantee match of at least 25% of total project cost. Page 146 Project Completion Report Alaska Energy Authority, Rural Energy Programs Nikolski UIG Diesel Generator Unit Project Program: Rural Power System Upgrade Recipient: Umnak Power Company Total Cost $118,500.00 Funding Sources: Division: $83,000.00 Federal: Local: Other: $0.00 $35,500.00 $0.00 Project Description: Budget Code 15630 Completion Date: 9/30/98 Agreement Number: 2175054 Election District: 40 Purchase and install a new 60 kilowatt diesel generator unit with programmable switchgear to allow paralleling with existing 85 kW and 40 kW generator units. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is from Umnak Power Company. Page 147 Project Completion Report Alaska Energy Authority, Rural Energy Programs Noatak AVEC New Diesel Generator Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: Budget Code 15200 Completion Date: 3/23/98 Agreement Number: 2155283 Election District: 37 Install electronic diesel electric generator unit in the Alaska Village Electric Cooperative (AVEC) powerhouse in Noatak. A side benefit of electronically-controlled engines includes reduced emissions to the environment and minimized release of exhaust smoke from start-up to full load. Supplemental Information: Utility Improvement Grant Program project. Local contribution is from Alaska Village Electric Cooperative and is the required 25% of total project cost. Page 148 Project Completion Report Alaska Energy Authority, Rural Energy Programs Noorvik AVEC New Diesel Generator Unit Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: Budget Code 15329 Completion Date: 3/23/98 Agreement Number: 2165055 Election District: 37 Purchase and install electronically-controlled, variable injection timing diesel generator unit in Alaska Village Electric Cooperative (AVEC) powerhouse in Noorvik to increase generating efficiency. Supplemental Information: Utility Improvement Grant (UIG) Program project; local contribution was from Alaska Village Electric Cooperative and represented the required match of 25% of total project cost. Page 149 Project Completion Report Alaska Energy Authority, Rural Energy Programs Ouzinkie New Diesel Generator Project Program: Rural Power System Upgrade Recipient City of Ouzinkie Total Cost: $95,000.00 Funding Sources: Division: $71,250.00 Federal: Local: Other: $0.00 $23,750.00 $0.00 Project Description: I \ \ Budget Code 15623 Completion Date: 6/15/98 Agreement Number: 2175049 Election District: 6 Purchase and install a 245 kilowatt diesel generator set and related equipment to be installed in the new Ouzinkie utility powerhouse to meet peak load requirements. The generator unit will provide back-up power when the hydroelectric plant is not in operation (low water or for maintenance). Prepare as-built drawings of the completed project. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is from the City of Ouzinkie, owner of the electric utility, and represents the required 25% match of total project cost. Page 150 Project Completion Report Alaska Energy Authority, Rural Energy Programs Selawik AVEC Diesel Engine Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $133,333.00 Funding Sources: Division: $100,000.00 Federal: Local: Other: $0.00 $33,333.00 $0.00 Project Description: \ \ Budget Code 15330 Completion Date: 9/30/98 Agreement Number: 2165056 Election District: 37 Project installed a diesel electric generating set with electronically-controlled, variable injection timing within Alaska Village Electric Cooperative's Selawik power house to increase generating efficiency. AVEC provided design and engineering specifications for Division review. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's 25% share of total project cost. Page 151 Project Completion Report Alaska Energy Authority, Rural Energy Programs Shungnak AVEC Oil Blending System Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $22,840.00 Funding Sources: Division: $17,130.00 Federal: Local: Other: $0.00 $5,710.00 $0.00 Project Description: ' ~ • \ ·,, __ /'' Budget Code 15327 Completion Date: 12/31/98 Agreement Number: 2165057 Election District: 37 Install an oil blending system within the Alaska Village Electric Cooperative (AVEC) powerhouse in Shungnak to blend used lubricating oil into the diesel engine's fuel supply. This will increase generating efficiency and reduce environmental hazards associated with long- term storage of used lubricating oil. AVEC also provided information and specifications on the equipment, a cost estimate breakdown and information on environmental impact. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's 25% share of total project cost. Page 152 Project Completion Report Alaska Energy Authority, Rural Energy Programs Shungnak AVEC Diesel Engine Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0.00 $25,000.00 $0.00 Project Description: • Budget Code 15628 Completion Date: 12/31/98 Agreement Number: 2175046 Election District: 37 Project installed an electronic diesel electric gen set within the Alaska Village Electric Cooperative (AVEC) powerhouse in Shungnak to increase generating efficiency. A side benefit of electronically-controlled engines is reduced emissions to the environment and minimized release of exhaust smoke from start-up to full load. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's 25% share of total project cost. Page 153 Project Completion Report Alaska Energy AuthoMty, Rural Energy Programs Teller Powerhouse/Distribution Upgrade Project Program: Rural Power System Upgrade Recipient: Teller Power Company Total Cost: $294,900.00 Funding Sources: Division: $147,450.00 Federal: $0.00 Local: $147,450.00 Other: $0.00 Project Description: \ \ Budget Code 15186 Completion Date: 11/22/98 Agreement Number: 2155278 Election District: 37 Install new switchgear and replace existing panels in powerhouse; upgrade existing 120/208 volt and 480 volt primary distribution system with a new 2.4/4.16 kV three-phase system; replace existing 3-25kVa, 120/208c-2.4/4.16 kV with a new 3-100 kVa transformer bank and install heat exchanger for improved efficiency and reliability. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local funding is from Teller Power Co. UIG program requires a matching contribution from the grantee of at least 25% of total project cost. Page 154 Project Completion Report Alaska Energy Authority, Aural Energy Programs Ambler AVEC Oil Blending System Project Program: Rural Power System Upgrade Redpient: Alaska Village Electric Cooperative Total Cost: $22,840.00 Funding Sources: Division: $17,130.00 Federal: Local: Other: $0,00 $5,710.00 $0,00 Project Description: Budget Code 15326 Completion Date: 9/15/97 Agreement Number: 2165053 Election District: 37 Installation of oil blending system to increase overall generator efficiency and reduce environmental danger associated with long-term storage of used lubricating oil. The Division provided grant funds and reviewed design. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local funding --25% of total project cost -- was provided by Alaska Village Electric Cooperative Inc. (AVEC). Page 156 Project Completion Report Alaska Energy Authority, Rural Energy Programs Kwethluk Distribution Upgrade Project Program: Rural Power System Upgrade Recipient: Kwethluk Inc. Total Cost: $40,000.00 Funding Sources: Division: $30,000.00 Federal: Local: Other: $0.00 $10,000.00 $0.00 Project Description: Budget Code 15188 Completion Date: 3/20/97 Agreement Number: 2155280 Election District: 39 Repairs were made to the electric distribution system in Kwethluk to deal with safety hazards, to make the system compliant with the National Electrical Code and National Electrical Safety code and to reduce line loss. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local funding was from Kwethluk Inc., owner of the electric utility, and constituted the matching requirement of 25 percent of total project cost. Page 163 Project Completion Report Alaska Energy Authonty, Rural Energy Programs Noatak AVEC Oil Blending System Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $22,840.00 Funding Sources: Division: $17,130.00 Federal: Local: Other: $0.00 $5,170.00 $0.00 Project Description: Budget Code 15328 Completion Date: 3/3/97 Agreement Number: 2165054 Election District: 37 An oil blending system was installed in the Alaska Village Electric Cooperative (AVEC) power house to blend used lubricating oil into the engine's fuel supply. This will increase generating efficiency and reduce the environmental damage potential associated with the long-term storage of used lubricating oil. Supplemental Information: Utility Improvement Grant (UIG) Program project. The local contribution was from AVEC and represented the required 25% match of total project cost. Page 166 Project Completion Report Alaska Energy Authority, Rural Energy Programs Thorne Bay Power House Upgrade Project Program: Rural Power System Upgrade Rec!pient: City of Thorne Bay Total Cost: $112,500.00 Funding Sources: Division: $90,000.00 Federal: Local: Other: $0.00 $22,500.00 $0.00 Project Description: Budget Code 15187 Completion Date: 5/15/97 Agreement Number: 2155279 Election District: 5 A 500 amp circuit breaker, two 500 kVa pad-mounted transformers and diked fuel storage tanks were installed at the Thorne Bay powerplant. Included in the project was repair of the generator room and addition of a fire suppression system. The completed project meets National Electrical Code and National Electrical Safety Code regulations. The Division granted funds under the Utility Improvement (UIG) program and inspected the project upon completion. The City of Thorne Bay provided project design, management, procurement and construction. Supplemental Information: The local contribution was from the City of Thorne Bay. Page 171 Project Completion Report Alaska Energy Authority, Rural Energy Programs Kivalina AVEC Diesel Generator Unit Project Program: Rural Power System Upgrade Recipient: Alaska Village Electric Cooperative Total Cost: $100,000.00 Funding Sources: Division: $75,000.00 Federal: Local: Other: $0,00 $25,000.00 $0.00 Project Description: l \ Budget Code 15201 Completion Date: 6/30/96 Agreement Number: 2155284 Election District: 37 An electronically controlled diesel generator set was installed in the Kivalina powerhouse to increase generating efficiency, A side benefit of the new diesel engine is reduced emissions to the environment as well as a reduction in exhaust smoke from the time the engine is started until it reaches full load. Supplemental Information: Utility Improvement Grant (UIG) Program project. Local contribution is Alaska Village Electric Cooperative's required 25% share of total project cost. Page181 Project Completion Report Alaska Energy Authority, Rural Energy Programs Manley Electric Line Extension Project Program: Rural Power System Upgrade Recipient: Manley Utility Company Total Cost: $38,667.00 Funding Sources: Division: $29,000.00 Federal: Local: Other: $0.00 $9,667.00 $0.00 Project Description: Budget Code 15190 Completion Date: 3/31/96 Agreement Number: 2155282 Election District: 36 Three-tenths of a mile of single-phase powerline extension was constructed to supply power to three homes. An additional 500 feet of three-phase line extension was constructed to supply power to Manley Hot Springs Resort. Supplemental Information: Utility improvement Grant (UIG) Program project. The local contribution was from Manley Utility Company and represented the required 25% match of total project cost. Page 183