HomeMy WebLinkAboutACEP Hydrokinetic Energy Technologies - Status and Future Opportunities - Nov 2010 - REF Grant 2195437River, Tidal, and Ocean Current
Hydrokinetic Energy Technologies:
Status and Future Opportunities in
Alaska
Jerome B. Johnson and Dominique J. Pride
Prepared for the Alaska Energy Authority
By the Alaska Center for Energy and Power, November 1, 2010
o nrpcz ;5 - 'AC EP
Table of Contents
Listof Figures..................................................................................................................... .... ii
......................
List of Tables "'
........................
ExecutiveSummary...................................................................................................................................... 1
Introduction................................................................................................................................................... 3
Hydrokinetic Technology Status................................................................................................................... 8
Theregulatory environment..................................................................................................................... 8
Hydrokinetic river and tidal current technology types............................................................................. 9
Hydrokinetic Projects in Alaska................................................................................................................. 13
Rubyhydrokinetic project......................................................................................................................13
CookInlet project...................................................................................................................................14
Eagle hydrokinetic turbine project .................. -
Igiugigproject......................................................................................................................................... 15
Nenanaproject......................................................................................................................................1. 16
Notable Hydrokinetic Projects beyond Alaska........................................................................................... 16
Alaskan Hydrokinetic Power Resource Evaluation Projects...................................................................... 17
Challenges to Development of a Viable Alaskan Hydrokinetic Power Industry ........................................ 18
Conclusions and Approaches to Facilitating Hydrokinetic Power in Alaska.............................................23
Expected Five -Year Trajectory for Hydrokinetic Technology in Alaska...............................................24
References................................................................................................................................................... 26
1
List of Figures
Figure 1. Alaskan ocean currents
(http://www.ims.uaf.edu/NPRBdrifters/bering%20chukchi%20map.png).............................................
3
Figure 2. Southeast Alaska map of tidal energy resources (Alaska Energy Authority, 2009)......................
4
Figure 3. Map of Alaska rivers, identifying several sites studied for their river hydrokinetic
potential (Previsic and Bedard, 2008).....................................................................................................
4
Figure 4. Map of the Alaska outer continental shelf indicating regions of wave energy ..............................
5
Figure 5. Wind energy cost per kWh 1980-2010 (Poulson, 2003)...............................................................
5
Figure 6. New Energy EnCurrent Turbine (on left) and deployed in the Yukon River (pictures
courtesy of New Energy Corporation and Tom Ravens).........................................................................
6
Figure 7. Locations of active FERC permits in Alaska as of July 2010 (Miles, 2010)................................
8
Figure 9. Open -Centre Turbine fan blade (photo courtesy of OpenHydro)................................................
10
Figure 8. Horizontal axis cross -flow turbine (picture courtesy of ORPC)..................................................
10
Figure 10. Propeller blade horizontal axis turbine (photo courtesy of Verdent Power) .............................
10
Figure 11. The bioSTREAM oscillating hydrofoil (photo copyrighted by BioPower Systems Pty.
Ltd. (www.biopowersystems.com)........................................................................................................10
Figure 12. VIVACE vortex -induced vibration hydrokinetic turbine (picture courtesy of G. Simiao,
Vortex Hydro Energy, and M.M. Bernitsas, U. Michigan.....................................................................10
Figure 13. Underflow water wheel turbine (courtesy of Whitestone Power & Communications.
Design by Hasz Consulting Co.)............................................................................................................
11
Figure 14. Debris pile on a 5 kW turbine barge at Ruby, Alaska...............................................................14
Figure 15. Electric power versus tidal flow velocity for the ORPC TidGenTM turbine shown in
Figure8 (ORPC, 2010)..........................................................................................................................
14
Figure 16. New Energy 25 kW hydrokinetic electric turbine on the Yukon River at Eagle, Alaska
(August 2010).................................................................................................................. ..................
15
Figure 17. Log debris island impacting (upper left ) and carrying off (upper right and lower left) a
fish wheel on the Tanana River near Nanana, Alaska, on August 1, 2008, and depositing it
against a bridge pier (lower right) (courtesy of Stephen Lord).............................................................20
Figure 18. River ice freeze-up process........................................................................................................20
Figure 19. Calculated current velocity (a), specific power density (b), total specific discharge (c),
and maximum total specific discharge (d) for the Tanana River based on measurements made in
August2009...........................................................................................................................................
21
Figure 20. Tanana River daily discharge from 1962-2000 (Langley, 2006)..............................................21
Figure 21. Overnight accumulation of frazil ice on four different material types during Tanana
Riverfreeze-up......................................................................................................................................
22
m
List of Tables
Table 1. Estimated economics of hydrokinetic power generating devices in Alaska ................................... 7
Table 2. Permitting and leasing oversight agencies......................................................................................9
Table 3. Vertical axis turbine companies and turbine technology stage of development ........................... 1 I
Table 4. Horizontal axis turbine companies and turbine technology stage of development .......................12
Table 5. Other turbine type manufacturing companies and turbine technology stage of development ......12
Table S. Alaska hydrokinetic projects......................................................................................................... 13
iii
Executive Summary
This report outlines the status of hydrokinetic power generation technology, the expected trajectory of
improvement over the next five years, and recommended actions the state can take to accelerate this
technology field. The report is based on numerous sources as well as data collected by ACEP over the
past year at a hydrokinetic research site in Nenana, Alaska.
Turbines placed directly in river, ocean, or tidal current generate hydrokinetic power from the kinetic
energy of moving water (current). The available hydrokinetic power is a function of the density of the
water and the speed of the current cubed. The minimum current required to operate a hydrokinetic device
is typically 2-4 knots (1-2 m/s), but optimal currents are in the 5-7 knot (1.53.5 m/s) range.
The Alaska region contains about 40% of the total U.S. river energy resource, 90% of the total U.S. tidal
energy resource, and 40% of the U.S. continental shelf wave energy resource. Hydrokinetic turbines have
frequently been discussed as an option for generating power in communities located along Alaska's major
river systems, and for tidal energy applications in Cook Inlet and coastal Southeast Alaska.
Studies by the Electric Power Research Institute indicate that hydrokinetic turbines are a viable method of
generating power in Alaska. Electrical costs would range from $0.11/kWh for tidal energy in Knik Arm to
about $0.68/kWh for energy from rivers near remote communities. All costs are in 2010 dollars. Ongoing
studies to characterize the hydrokinetic potential of Alaskan river and tidal currents will provide improved
information needed for future hydrokinetic demonstration projects.
At present, two hydrokinetic turbines have been tested in Alaska (a 5 kW turbine at Ruby during 2008,
2009, and 2010, and a 25 kW turbine at Eagle in 2010). The Eagle deployment was grid -connected, and if
tests are successful, it will be converted to full commercial operation. Additional demonstration projects
are planned for Cook Inlet, the Tanana River, and the Kvichak River, with other interested communities
developing turbine deployment concepts.
Challenges to developing a commercial hydrokinetic industry in Alaska include determining the
technological, operational, and economic viability of hydrokinetic turbines, meeting permitting
requirements, and gaining stakeholder acceptance. Hydrokinetic technology can be affected by debris,
sediment, frazil, and surface ice; river dynamics (turbulence, current velocity, channel stability); and the
interaction of turbine operations with fish and marine mammals and their habitat. The question of turbine -
operation impacts on the aquatic environment is one of the major issues that will determine stakeholder
and permitting agency views toward this new technology. The 2010 hydrokinetic turbine demonstrations
conducted at Ruby and Eagle were significantly adversely affected by in -river debris floating on the
surface and neutrally buoyant debris. These experiences indicate that developing technology to mitigate
debris problems will need to be a high priority for practical hydrokinetic power production.
River and marine hydrokinetic technology (RMHT)--an emerging technology —is at a similar stage as
wind power generation technology was 15 to 20 years ago. For RMHT to move from the emerging stage
to the practical commercial stage requires support similar to that provided to wind technology
development during its nascent years. Financial support is needed for research to develop technology and
further an understanding of the river and marine environments that will host RMHT. Data and modeling
tools will be required to describe the interactions between RMHT and aquatic environments. Engagement
through dialogue with all relevant stakeholders is needed at the earliest stages of project development in
order to produce reasonable approaches to permitting and to develop Alaska -based expertise that is
integrated with the national scene.
Alaska is well positioned to facilitate RMHT as it transitions from emerging to developed technology
over the next five to ten years, by building on current and planned national and state structures. These
structures include the Bureau of Ocean Energy Management, Regulation and Enforcement (BOEMRE,
formerly the Minerals Management Service), the Department of Energy, and the Denali Commission, as
well as Alaska state funding support for renewable energy projects and development of emerging
technologies and research.
The one area where existing efforts and funding is lagging is the development of a science -based
understanding of how fish and marine mammals will interact with RMHT. Issues of fish and marine
mammals have a large stakeholder base related to ecological stewardship, economics, culture, and
lifestyle that significantly affect agency views about permit requirements. Agencies have indicated
repeatedly that they want to know how hydrokinetic technology will affect aquatic habitats and biology.
Five years ago, hydrokinetic technology consisted primarily of ideas in papers and studies. During the
interceding five years, these concepts have been developed into actual devices and demonstration
projects. Over the next five-year period, it is probable that permit requirements for demonstration projects
will be well defined, several demonstration projects will be underway or completed, and initial
commercial operations wilt have begun. Such progress assumes a continuation of the current state of high
interest and activity in the development of RMHT and a continuation of support for the technology from
agencies and stakeholders.
2
Introduction
Turbines placed directly in river, ocean, or tidal current generate hydrokinetic power from the kinetic
energy of moving water (current). The available hydrokinetic power depends on the speed of the river,
ocean, or tidal current and is a function of the density of the water and the speed of the current cubed. In
order to operate, hydrokinetic devices require a minimum current and water depth. The minimum current
required to operate a hydrokinetic device is typically 2-4 knots (1-2 m/s), but may be as low as 1 knot
(0.5 m/s), depending on the particular technology approach. Optimum currents are in the 5-7 knot (1.5
3.5 m/s) range. Water depth is an important factor in determining the total energy that can be extracted
from a site, since the cross -sectional area over which a turbine can extract energy is dependent on
adequate water level above the installed device. Hydrokinetic devices are ideally installed at locations that
have relatively steady flow throughout the year and are not prone to serious flood events, turbulence, or
extended periods of low water level.
In Alaska's riverine environments, water flow can fluctuate dramatically on a seasonal basis depending
primarily on the rate of seasonal snow and glacier ice melt. Tidal currents change direction and current
velocities vary depending on local geography and bathymetry and the gravitational influence of the moon
and sun. Ocean currents are a continuous directed flow of ocean water up to thousands of miles long.
Surface ocean currents are restricted to the upper 300 m (1000 ft) or so and are largely wind driven. Deep
ocean currents are driven by density and temperature gradients. Ocean passages in the Aleutian Islands
have been identified as areas with significant ocean current hydrokinetic energy potential (Figure 1).
70:
65:
60`
55`
160 175 W 170 L4 765' W 160'W 051W
m o sea" � kin
O �� aurmtvW-
Saxriaa Coesw Curren
e - 50 aorta Ca"N'Ak1 0 500
p c.® gdirq Shel Vbler
t 500 alerrGan Nash S". - Berag `+t4u -arvdN AM—
h .... Alabran Stream
SWp b" ice Edr V-- ad M.timun Frtersn
Madr ke Edge Mannwm aid Wm Ertaaa
7D' N
65' N
6C N
55N
Figure 1. Alaskan ocean currents(hnp://www,ims.uafedu/NPRBdrifters/tiering%20chukchi%20map.png)
The Alaska region hydrokinetic potential is significant, with about 40% of the total U.S. river energy
resource, 90% of the total U.S. tidal energy resource, and 40% of the U.S. continental shelf wave energy
resource (Miller et al., 1986; Previsic, 2007; Bedard et al., 2009). Hydrokinetic turbines have frequently
been discussed as an option for generating power in communities located along Alaska's major river
systems, and for tidal energy applications. Many inland communities in Alaska that are particularly
affected by high energy costs (paying more than three times the U.S. average) are situated along
navigable waterways that could host hydrokinetic installations. Several resource assessment studies have
been completed or are in the process of being completed, most in collaboration with or funded by the
Alaska Energy Authority (AEA) (Polagye and Bedard, 2006 Polagye and Previsic, 2006; Previsic, 2008;
Previsic and Bedard, 2008; Previsic and Bedard, 2009; Alaska Energy Authority, 2009) (Figures 2-4).
lal Electric Generation Potential
IW
1.3-25 ■ 75.100
25-50 ■ 100-220
50-75
iwe Power Potential
Wm
26 - 30 = 40. 50
30-40 =50-56
Figure 2. Southeast Alaska map of tidal energy resources (Alaska Energy Authority, 2009)
Tam= at Niaoley Not
Springs Y _ �s r ` LL
�r
_ 6 _
Yukon at Pilot Station
7anp at NV litescom
Yukon at Eagle
Taku at 1uncau
Figure 3. Map of Alaska rivers, identifying several sites studied for their river hydrokinetic potential
(Previsic and Bedard, 2008)
Figure 4. Map of the Alaska outer continental shelf indicating regions of wave energy
As of 2010, hydrokinetic devices are generally considered pre -commercial (Khan and Bhuyan, 2009). In
recent congressional testimony, Roger Bedard (Electric Power Research institute) commented, "The time
period for a MHK [marine hydrokinetic] technology to progress from a conceptual level to deployment of
a long-term full-scale prototype tested in the ocean is typically on the order of 5 to 10 years. The
technology is still in its emerging stage; like where wind technology was approximately 15 to 20 years
ago' (Marine Hydrokinetic Technologies, 2009). Since the late 1970s, when commercial wind projects in
the U.S. were first realized, the efficiency and reliability of wind turbines have increased while the capital
cost of wind turbines has decreased (EERE, 2008a). The cost of wind -generated electricity has dropped
by as much as 80% in the past thirty years (Figure 5), from as much as 30 cents per kilowatt hour in some
areas in 1980 to less than 5 cents per kilowatt hour in 2009 (AWEA, 2009).
Wind Energy Cost per KWh 1980-2010
Cost of wind -generated electricity"
Total wind 25.00
power cost
fcentsAWN # zo 00 Onshore .. Offshore
,--��
15.00
10.00
acw kef 5.00
pe For !
physical 0.00 5�i r r� rives—r—ram—r rgr r r a r r I r i r r i r r i r i r r r r
power
Shen windEnergy
* for a site with 8-9 nVs average annual wind speed
A S V 10
Figure 5. Wind energy cost per kWh 1980-2010 (Poulson, 2003)
5
As a technology becomes more mature, cost decreases may be achieved through learning -by -doing;
research, development, and demonstration innovations; improved communication between involved
parties; product standardization; and the redesign and scale alteration of a product (Junginger et al., 2005).
In economics, this concept is referred to as an experience curve, which "analyzes cost development of a
product or technology as a function of cumulative production" (Junginger et al., 2005, p. 133). Experience
curves have been applied to other energy technologies, including photovoltaic panels, combined -cycle gas
turbines, and carbon sequestration technologies (Junginger et al., 2005). It is reasonable to assume that
hydrokinetic turbines will follow a similar experience curve as that of wind technologies, with decreasing
costs as cumulative production increases.
The first hydrokinetic device deployed on a river system in the U.S. was deployed in Ruby, Alaska, in
2008 for one month (Figure 6), and briefly redeployed in 2009 and 2010 (a 5 kW New Energy EnCurrent
turbine). A 25 kW New Energy EnCurrent turbine was briefly installed in the Yukon River at Eagle
during the summer of 2010. Both turbine deployments experienced problems with in -river debris.
Figure 6. New Energy EnCurrent Turbine (on left) and deployed in the Yukon River
(pictures courtesy of New Energy Corporation and Tom Ravens)
The only grid -connected in -current river hydrokinetic project operating in the U.S. is a Hydro Green
Energy turbine installed behind an existing hydroelectric dam turbine near Hastings, Minnesota. This
turbine is installed in the engineered waterway of the dam and is used to capture the energy that remains
in the water current as it exits the dam (Neville, 2009). The dam filters out sediment and debris, making
the installation site relatively benign when compared with installations in uncontrolled river or tidal
currents where debris, sediment, and the river or marine environments impact turbine operations. All
other hydrokinetic projects (current and wave) are at various stages of technology development, prototype
testing, or demonstration. No full-scale commercial systems utilizing hydrokinetic turbines have yet been
deployed.
Hydrokinetic technologies are still in the developmental phase, making it difficult to conduct accurate
economic analysis for proposed installations. Once more devices are built and deployed, specific
estimates for costs can be made. Although preliminary, economic analyses for several proposed
hydrokinetic projects in Alaska have been conducted by the Electric Power Research Institute (see
Table 1).
0
Table 1. Estimated economics of hydrokinetic power generating devices in Alaska
Study Location
Power Production
(kW)
Capital Cost
(2010 $)
Cost per
kWh
2010 $
Annual O&M
Costs (2010 $)
Igiugig
40 kW
$315K
$0.68
$12.6K
Eagle
60 kW
$283K
$0.68
$6.8K
Whitestone
590 kW
$1.9M
$0.19
$135K
Knik Arm
17,000 kW
$123M
$0.11
$4.5M
Yakutat
5,200kW
$48M
$0.28
$JAM
The Electric Power Research Institute (EPRI) studied hypothetical in -river hydrokinetic installations at
Igiugig, Eagle, and Whitestone (Previsic, 2008). All costs in the studies have been updated to 2010
dollars. The Igiugig study proposed a 40 kW installation, which would produce 207 MWh per year of
electricity that would sell for $0.68/kWh. The capital cost for installation would be about $315,000, with
an annual operations and maintenance cost of roughly $12,600. This translates to about $7,900 per
installed M. The EPRI study of a 60 kW installation at Eagle on the Yukon River states a capital cost of
about $283,000 or about $6,000 per installed kW, with an annual operations and maintenance cost of
about $6,800. In total, the installation would generate 107 MWh per year of electricity that would sell for
$0.68/kWh. The EPRI conducted a study for a 590 kW hydrokinetic installation in Whitestone on the
Tanana River. The installation's capital cost is an estimated $1.9 million or about $3,300 per kW, with
annual operations and maintenance costs of roughly $135,000. The installation would produce 1,325
MWh of electricity per year that would sell for $0.19/kWh.
A study on in -stream tidal power was conducted by EPRI for Knik Arm in Cook Inlet (Polagye and
Previsic, 2006). All costs have been adjusted to 2010 dollars. The study concluded that a commercial
installation of an array of devices would extract an average of 17 MW of electricity from the tide. The
estimated capital cost of the array is $123 million, or about $2,500 per installed kW, with an annual
operations and maintenance cost of $4.5 million. The cost of electricity for utility generation would be
$0.11/kWh.
The EPRI conducted a wave -power feasibility study for Yakutat to assess the technical aspects, cost, and
economics of a potential wave -energy conversion project at the site (Previsic and Bedard, 2009). All costs
are in 2010 dollars. A 5.2 MW plant composed of an array of eight Oyster wave -energy conversion
devices has an estimated capital cost of about $48 million, or $8,900 per installed kW, and an annual
operation and maintenance cost of $1.4 million. The cost of electricity from the plant is an estimated
$0.281kWh.
Significant engineering and environmental issues must be resolved before commercial projects can be
realized in Alaska and elsewhere. In Alaska, evidence indicates that it may not be possible in many
locations to deploy hydrokinetic turbines year -around due to low wintertime current velocities and the
possible accumulation of frazil ice on turbine components. Frazil ice is ice that grows within the water
column during freeze-up of rivers and open ocean environments (see the section on challenges to
development). Staff at the Federal Regulatory Energy Commission (FERC) have identified a number of
concerns about hydrokinetic turbines related to water turbulence, corrosion, anchoring systems, fluid
leaks (e.g., hydraulic fluids), underwater transmission line effects, and installation and maintenance
problems (Wellinghoff et al., 2008). In addition to these more or less technical issues, there is also
concern from stakeholders and regulatory agencies over potential ecological effects related to marine
mammals and to marine and river fish (Bochlert et al., 2007; Polagye et al., 2010).
7
The remainder of this report outlines the status of hydrokinetic technology, challenges facing
development of commercial projects in Alaska, the expected trajectory of improvement over the next five
years, and recommended actions the state could take to accelerate this technology field. This report
focuses on river and tidal current hydrokinetic power technology, which is where most of the
development focus is presently directed in Alaska.
Hydrokinetic Technology Status
The regulatory environment
An important factor in determining the success or failure of realizing the potential of hydrokinetic energy
is the regulatory framework that governs hydrokinetic systems. Long time frames to achieve regulatory
approvals can result in a lack of investment in hydrokinetic systems with consequent retardation of
needed technology development. The FERC has a leading role in regulating hydrokinetic (and other)
energy through the Federal Power Act (FPA) authorization. Permits from the FERC give an individual
firm the exclusive right to study and eventually utilize the hydrokinetic potential of a reach of river or
marine region for which the permit applies. Figure 7 shows the locations of FERC permits for Alaskan
projects. The FERC permitting process is traditionally difficult for hydrokinetic projects because they are
currently lumped together with major hydroelectric dam projects, although FERC is streamlining the
process (Wellinghoffet al., 2008; Union of Concerned Scientists, 2009).
O a
O 0
O
0- s.
Figure 7. Locations of active FERC permits in Alaska as of July 2010 (Miles, 2010)
In addition to the FERC's regulatory role, other federal and state agencies provide input and their own
regulatory function, depending on a particular project's proposed location (see Table 2). For projects
located in ocean waters beyond the three-mile limit that defines state coastal waters, a project may require
approvals from several federal agencies to meet regulatory requirements. In addition to the FERC, the
Bureau of Ocean Energy Management, Regulation and Enforcement (BOEMRE) may regulate
hydrokinetic projects by issuing leases. The U.S. Fish and Wildlife Service (FWS), the National Marine
Fisheries Service (NMFS), and/or the U.S. Army Corps of Engineers (USACE) may also require
authorizations, depending on the nature of a particular project.
Within state waters, a project may need authorizations from both state and federal agencies to
accommodate federal laws related to the Clean Water Act, the Coastal Zone Management Act, and
relevant state regulations. Hydrokinetic projects on inland waterways require approvals from appropriate
state and federal agencies. In Alaska, the USACE, the Alaska Department of Fish and Game (ADF&G),
and the Alaska Department of Natural Resources (ADNR) have regulatory oversight. Input from other
stakeholders (e.g., FWS, NMFS, and local communities and groups) are taken into account during the
permitting process (Wellinghoff et al., 2008).
Table 2. Permitting and leasing oversight agencies
Agency
Regulatory Authority
Federal Energy Regulatory Commission (FERC)
In -water electric power generation (federal & state
waters
U.S. Anny Corps of Engineers (USACE)
Land use and navigable waterways (federal & state
waters)
Alaska Dept. of Fish and Game (ADF&G)
Fish and habitat (state waters
Alaska Dept. of Natural Resources ADNR
Land use state lands
NOAA National Marine Fisheries Service (NMFS)
Fish, marine mammal, and habitat conservation (federal
waters
U.S. Fish and Wildlife Service FWS
Fish federal waters
U.S. Dept. of the Interior Bureau of Ocean Energy
Management, Regulation and Enforcement BOEMRE
Regulation and leasing (federal waters)
The FERC has issued 143 hydrokinetic preliminary permits for potential hydrokinetic projects in the U.S.
Of the 143 permits issued by FERC, 28 are tidal projects, 13 are wave projects, and 102 are inland
projects. A majority of the inland permits are for projects on the lower Mississippi River, a largely
untapped source of hydrokinetic power (FERC, 2010). According to FERC, there are currently seven
issued hydrokinetic preliminary permits for Alaska, of which three are preliminary inland permits and
four are tidal preliminary permits.
Hydrokinetic river and tidal current technology types
River and tidal current hydrokinetic devices typically use vertical or horizontal axis turbines similar to
those developed for wind generation. Vertically oriented turbines are generally of the Darrius or Gorlov
type that "typically have two or more blades mounted along a vertical shaft to form a rotor; the kinetic
motion of the water current creates lift on the blades causing the rotor to turn driving a mechanical
generator" (EERE, 2008b) (Figure 8). The rotor turns in the same direction irrespective of the direction of
current flow, such that the turbine can operate in either river or tidal current environments. Horizontal
axis turbines are typically of three types: the Darrius/Gorlov type (Figure 8), a fan blade type (Figure 9),
or a propeller blade type (Figure 10).
A variety of hydrokinetic devices are under various stages of development and include utilizing a reverse
Archimedes screw mechanism, oscillating hydrofoil motions (Figure 11), vortex -induced vibrations
(Figure 12), traditional underflow water wheel technology (Figure 13), and other novel methods (EERE,
2008b; Bernitsas et al., 2008; Hasz Consulting, 2010). The underflow turbine was specifically designed to
address problems associated with operating turbines in debris- and sediment -filled rivers in Alaska. An
oscillating hydrofoil is "similar to an airplane wing, but in water; yaw control systems adjusts their angle
relative to the water stream, creating lift and drag forces that cause device oscillation; mechanical energy
from this oscillation feeds into a power conversion system" (SERE, 2008b).
0
d
i
Figure S. Horizontal axis cross -flow turbine
(picture courtesy of ORPC)
Figure 9. Open -Centre Turbine fan blade
(photo courtesy of OpenHydro)
Figure 10. Propeller blade horizontal axis turbine (photo courtesy of Verdent Power)
d' - W, !K 1`0_�W
.'`i
Figure 11. The bioSTREAM oscillating hydrofoil
{photo copyrighted by BioPower Systems Pty. Ltd.,
www.bioi2owersystems.com)
Figure 13. Underflow water wheel turbine
(courtesy of Whitestone Power & Communications. Design by
Hasz Consulting Co.)
Tables 3-5 list river and tidal current hydrokinetic turbine manufacturers and their stage of technology
development.
Table 3. Vertical axis turbine companies and turbine technology stage of development
Company
Location
Device
Stage of Technology
Capacity
Blue Energy
Canada
Blue Energy Ocean
Turbine
Scale model sea trials
250 kW
C-EnergyNetherlands
Wave Rotor
Scale model sea trials
30 kW
Lucid Energy Technologies
LLP
Goshen, IN
Gorlov Helical
Turbine
Scale model sea trials
20 kW
New Energy Corporation Inc.
Canada
EnCurrent Turbine
Full scale prototype
5-250 kW
Ponte di Archimede
International S.P.A.
Italy
Enermar
Scale model sea trials
25 kW
Sea Power International AB
Sweden
EXIM
Scale model sea trials
48-72 kW
11
Table 4. Horizontal axis turbine companies and turbine technology stage of development
Company
Location
Device
Stage of Technology
Capacity
Atlantis Resources
UK
Nereus
Scale model sea trials
150 kW
Corporation
Clean Current
Clean Current tidal
Power Systems
Canada
turbine generator
Full scale prototype
65 kW
Free Flow Power
Gloucester, MA
SmarTurbine Generator
Scale model tank testing
10 kW
Free Flow 69
UK
Osprey
Scale model sea trials
1 kW
Hammerfest
UK
Tidal Stream Turbine
Full scale prototype
300 kW
Strom UK
HydroCoil Power,
Wynnewood, PA
HydroCoil
Scale model sea trials
20- 40 kW
Inc.
Hydro Green
Huston, TX
Hydro+
Commercial
35 kW
Energy
Maine Current
300 kW-1.2
Turbines
UK
SeaGen
Full scale prototype
MW
Natural Currents
Highland, NY
RED HAWK Tidal
Scale model sea trials
125 kW
EnergyServices
Turbine
Ocean Flow
UK
Evopod
Scale model sea trials
1 kW
Energy
Ocean Renewable
Fall River, MA
ORPC Turbine
Scale model sea trials
32 kW
Power Company
Generating Unit
O enH dro
Ireland
O en -Centre Turbine
Full scale prototype
250 kW-1 MW
Robert Gordon
UK
Sea Snail
Full scale prototype
150 kW
University
SMD H drovision
UK
TidEl
Scale model tank testing
500 kW
Swanturbine Ltd.
UK
Swanturbine
Scale model sea trials
330 kW
Tidal Energy Pty.
Australia
Davidson -Hill Venturi
Scale model sea trials
Unavailable
Ltd.
Turbine
Tidal Generation
UK
DEEP -Gen
Full scale prototype
500 kW
Ltd.
Tidal Steam
UK
Triton
Scale model tank testing
10 MW
Tocardo Tidal
Netherlands
Tocardo Aqua 2800
Full scale prototype
32 kW
Energy Ltd.
University of
UK
Contra -Rotating Marine
Scale model sea trials
30 kW
Strathclyde
Turbine CoRMaT
Verdant Power
New York, NY
Free Flow System
Full scale proto e
35 kW-1 MW
Table 5. Other turbine type manufacturing companies and turbine technology stage of development
Company
Location
Device
Stage of Technology
Capacity
BioPower Systems Pty. Ltd.
Australia
bioStream
Detailed design
250 kW
Pulse Generation Ltd.
UK
Pulse Hydrofoil
Scale model tank
100 kW
testing
Scale model tow tank
Vortex induced
testing. Test
VIVACE
US
vibration
deployment in the St.
Unavailable
Claire river — 2010
Underflow
Underflow water wheel
US, Alaska
waterwheel
Conceptual
Unavailable
12
Hydrokinetic Projects in Alaska
Several funded projects in Alaska are underway to better define the hydrokinetic potential of Alaska's
inland rivers, to evaluate the performance of specific turbine technology in Alaska's river environments,
and to prepare for river and tidal demonstration projects. These projects, listed in Table 6, are described in
the following paragraphs.
Table 6. Alaska hydrokinetic projects
Location
Manufacturer
Device
Rub Yukon River
New Energy
5 kW EnCurrent Power Generation Systems
Cook Inlet
ORPC
(4) 250 kW TidGen TGU [2012]
(4) 500 kW OGen TGU [2013]
4 500 kW OGen TGU 2014
Eagle Yukon River
New Energy
25 kW EnCurrent Power Generation Systems
Igiugig (Kvichak River)
EPRI study/ AEA
renewable energy fund ant
Feasibility and Planning stage
Nenana Tanana River
ORPC
30 kW RiverGen TGU
Whitestone (Tanana River)
Whitestone Power &
Communications
Underflow waterwheel turbine (recently awarded a
DOD technology maturation ant
Ruby hydrokinetic project
In the summer of 2008, a 5 kW in -stream hydrokinetic generator developed by New Energy Corporation
was installed in the Yukon River at Ruby, Alaska, for a test period of one month. The project was
designed to harness electricity from the free -flowing Yukon River and test the viability of using a
hydrokinetic generator to offset the high -cast diesel fuel used to power the community's electrical grid.
The pontoon barge holding the turbine was anchored to cliffs approximately 200 m downstream of the
main Ruby slip. The project had a budget of $65,000, which covered the generator, the pontoon barge
onto which the generator was mounted, the transmission cable, the anchoring equipment, and a V-shaped
debris boom attached to the front of the boat to protect the generator from debris floating down the river
(Bryson, 2009). The turbine worked as anticipated, but slow current at the river's edge prevented much
electricity from being generated. The turbine was deployed again in the summer of 2009 and anchored to
concrete blocks 800 ft offshore in an area of swifter current. While the diversion system was effective, it
required regular cleaning, as entrapped floating and submerged debris adversely affected turbine
performance. Power transmission between the turbine and shore became a significant challenge, and the
power cable that was deployed only sent power to shore for four days before being worn through along
the riverbed. The turbine was left in the river through the rest of the summer with an Acoustic Doppler
Current Profiler taking measurements on river speed. In the summer of 2010, the anchor lines set during
the previous summer were retrieved and a power cable that was more protected and better anchored was
laid between the turbine and the shore. Using a 435 hp barge from a local barge line, the cable was
dragged from shore through the water to anchor buoys mid -channel. Unfortunately, the wide stretch of
river (900 m across) and the resources available prevented adjustment of the cable after the initial
placement. Further attempts to reposition the cable failed due to its extreme weight. In addition, a number
of high-water events throughout the summer brought unusual amounts of debris downriver, which
continued to prevent long-term deployment of the turbine barge, even though the debris boom was
redesigned twice to better enable it to shed debris (Figure 14). The turbine barge and power cable were
successfully pulled from the river in mid -September 2010, and the cable was re -spooled using heavy
equipment. The anchor lines were attached to three -eighths inch cable and laid on the river bottom; then
the cable was played out to shore and attached to a sturdy anchor ready for retrieval in the spring.
13
Figure 14. Debris pike on a 5 kW turbine barge at Ruby, Alaska
Cook Inlet project
A subsidiary of Ocean Renewable Power Company, ORPC, Alaska LLC (ORPC), has applied for a
FERC preliminary permit and filed a draft pilot project licensing application to install and test a series of
power systems in Cook Inlet near Fire Island. Cook Inlet has the second highest tidal range in North
America after the Bay of Fundy in Canada. The strong tidal resource makes Cook Inlet attractive for tidal
energy development (ORPC, 2010). In the summer of 2009, ORPC conducted in-depth marine
geophysical work at the site including bathymetry, side scan sonar, sub -bottom characterization, and
extensive current velocity surveys. Additionally, ORPC conducted a pre -deployment fish and marine
mammal study, and began a visual observation program to assess the frequency of occurrence and use of
the proposed deployment area by Cook Inlet beluga whales, which are on the Endangered Species list.
ORPC will continue this study through 2012, using state-of-the-art passive hydro -acoustic monitoring
technology to further characterize usage patterns of the area and assess any effects of the tidal energy
project on the distribution of these whales. Studies to determine the prevalence of debris, sediment, and
ice (during winter) will be conducted in the future. In August 2010, ORPC conducted performance testing
of their Beta TidGen"m Turbine Generator Unit at flow speeds of slightly more than 2.5 m/s (5 knots),
demonstrating that the turbine produced power within design performance tolerances (Figure 15).
i
Flow 5peee 0now
Figure 15. Electric power versus tidal flow velocity for the ORPC TidGenTIM turbine
shown in Figure 8 (ORPC, 2010).
14
Eagle hydrokinetic turbine project
The Alaska Power and Telephone Company (AP&T) received a grant from the Denali Commission in
2007 to install a hydrokinetic turbine in the upper Yukon River near Eagle, Alaska, as part of a pilot study
to determine the viability of the new technology. The pilot project includes fish studies to determine the
turbine's impact on local species and migrating salmon. If the five-year pilot project proves feasible and
economical, AP&T may install additional turbines to meet the utility's full load requirement. The
project's 25 kW New Energy Corp. EnCurrent turbine generator was installed in late spring 2010, and
operating systems were commissioned. The turbine was in service until early July, when it was damaged
during a period of very heavy debris drift on the river. The debris on the river surface piled up in front of
the turbine barge, and large submerged, neutrally buoyant debris damaged the barge's mooring
equipment. The turbine was removed from service, and the turbine barge was moved to shore for repair.
Heavy rains in the region damaged the Taylor Highway and delayed efforts to repair and redeploy the
turbine. After repairs in early August, the turbine barge was redeployed, and the turbine generator was
placed back into service supplying power to the grid at Eagle (Figure 16). The generating and power -
conversion equipment performed well. Turbine operation was halted again after another heavy drift event
in mid -August, which damaged the generator power cable. The turbine was removed from service, but the
barge was maintained on the mooring until late September, at which time all equipment was removed
from the river, winterized, and placed in storage at the community's diesel power plant. Plans are to
redeploy the turbine in spring 2011.
„ttih .
y 5Yi 'ii�
Figure 16. New Energy 25 kW hydrokinetic electric turbine on the Yukon River at
Eagle, Alaska (August 2010).
Igiugig project
Igiugig, a small community of less than 60 people in southwest Alaska, is located at the mouth of the
Kvichak River near Lake Iliamna. The village's position downriver from Lake Iliamna reduces
summer/winter variability in the flow of the river. A study conducted by EPRI (Previsic, 2008) indicated
that installation of a hydrokinetic turbine could help reduce the community's dependence on fossil fuels.
The river where the hydrokinetic device would be deployed remains ice -free throughout the winter.
Nonetheless, the device would need to be removed during spring breakup because of ice chunks that float
downriver from Lake Iliamna. The town currently operates three diesel generators with capacities of 60 to
100 M. Load patterns range from 40 to 95 kW, peaking during the cold winter months. Igiugig is in the
15
initial stages of implementing a plan to develop hydrokinetic turbine power -generation capability,
working with the AEA through an AIaska Renewable Energy Fund grant. A preliminary FERC permit has
been granted, and baseline studies are planned for 2011. The specific hydrokinetic technology has not yet
been determined, but plans are in place to install a turbine in 2012.
Nenana project
ORPC, Alaska LLC has a Denali Commission grant to demonstrate its hydrokinetic RivGenTM Turbine
Generator Unit (TGU) in the Tanana River at Nenana, Alaska. The full RivGenTM Power System will
include the TGU, bottom support frame, debris -diversion system, and power electronics to interconnect
the system into isolated micro -grids. Other participants in this project include the Alaska Hydrokinetic
Energy Test Center (AHERC) at the University of Alaska Fairbanks (UAF), the National Renewable
Energy Laboratory (NREL), the City of Nenana, and the Nenana Native Council. AHERC is
characterizing the environment of the Tanana River, helping with debris description and foundation
design in preparation for turbine installation, which is scheduled for 2012. AHERC will conduct studies
to determine the impact of the turbine once it is installed. Additionally, river debris, ice, and/or silt, which
could possibly damage a hydrokinetic device, are being studied.
Notable Hydrokinetic Projects beyond Alaska
Hydra Green Energy: Hastings, Minnesota, Project
Hydra Green Energy installed the first FERC-licensed commercial grid -connected hydrokinetic project in
the U.S. The project began operation in January 2009 with the installation of a 100 kW hydrokinetic
turbine in the Mississippi River near Hastings, Minnesota. The hydrokinetic turbine, which is installed
behind an existing hydroelectric turbine, generates electricity by capturing the energy that remains in the
water current upon exiting the dam. One benefit of installing the hydrokinetic turbine downriver from a
dam is the filtration of river debris by the existing dam, which otherwise could damage the hydrokinetic
turbine. There are plans to install a second 100 kW turbine at the site (Neville, 2009).
Clean Current: Race Rocks Tidal Energy Project
The Race Rocks Tidal Energy Project was undertaken as a means of offsetting diesel -generated electricity
at the Race Rocks Ecological Reserve on the Strait of Juan de Fuca in Canada. A 65 kW Clean Current
Tidal Turbine Generator (TTG) was installed from July to September 2006. Performance of the device
was tested over a two -month period, before it was connected to the battery -storage system at the reserve.
The device was in operation for five months and extracted power in water flows up to 6.6 knots.
However, the device was removed in May 2007 because of unacceptable performance of its water -
lubricated bearing system. In October 2008, the device was redeployed after the bearing system was
replaced (Clean Current Power Systems Incorporated, 2008).
Verdant Power: Roosevelt Island Tidal Energy Project
Verdant Power is operating the Roosevelt Island Tidal Energy (RITE) project in New York City's East
River. The project has been carried out in three phases. Prototype testing was conducted in phase one,
which ran from 2002 to 2006. During phase two —the demonstration phase that ran from 2006 to 2008—
Verdant operated an array of six full-scale 5 in diameter rotors. During phase two, the array produced 70
MWh over 9,000 turbine hours of operation. The project is currently in phase three, which began in 2009
and will continue until 2012. During this phase, Verdant plans to expand the scale of the project to l MW
by increasing the number of turbines in operation to 30, if the proper permit can be attained from FERC
(Verdant Power, 2009a).
16
Verdant Power: Cornwall Ontario River Energy Project
Verdant Power is operating the Cornwall Ontario River Energy Project (CORE) on the St. Lawrence
River near Cornwall, Ontario. The project utilizes three -blade, horizontal -axis turbines to extract energy
from the currents of the St. Lawrence River. The project is currently in the first of two phases. Phase one,
the demonstration pilot, began in 2007 and will continue until 2011. During this phase, resource analysis,
pilot permitting, and test deployments will be undertaken. During phase two, a commercial build -out will
take place from 2011 to 2013, which entails securing commercial permits, installing turbines with a
combined capacity of 5 MW (with future capacity additions up to 15 MW), and commercial sale of
electricity to the local grid (Verdant Power, 2009b)
The European Marine Energy Center Ltd (EMEC, 2010)
The European Marine Energy Center (EMEC) Ltd. is a multi -berth testing facility for wave and tidal
hydrokinetic devices. EMEC is located in Orkney, Scotland, because of the area's strong wave and tidal
resources and because Orkney is the most northerly town connected to the UK grid. The wave testing site
is located at Billia Croo, Mainland Orkney, and the tidal testing site is located at the Fall of Warness, off
the island of Eday. At the center, manufacturers of wave and tidal energy conversion devices are able to
test full-scale grid -connected prototypes. Services offered by EMEC include assessments of device
energy -conversion efficiency, structural integrity, and survivability in a marine environment.
Additionally, EMEC offers assistance with regulatory issues, grid connection, monitoring of weather and
marine conditions, harbor access, and engineering, office, and data support. Devices tested at EMEC's
wave site include Pelamis Wave Power's 750 and Aquamarine Power's Oyster. OpenHydro's Open
Centre Turbine was tested at the tidal testing site.
The Fundy Ocean Research Center for Energy (FORCE, 2010)
The Fundy Ocean Research Center for Energy (FORCE) is located at the Minas Passage of Bay of Fundy,
off the coast of Nova Scotia, Canada. The Bay of Fundy has the world's largest tidal range, which makes
it the ideal testing site for tidal energy devices. FORCE owns and operates a grid -connected testing and
demonstration facility with three births. The facility will be connected to a grid that serves both eastern
Canada and the United States. FORCE offers shared infrastructure, insurance, environmental monitoring,
and resource research. The companies that have or are currently testing their devices at the FORCE
facility include OpenHydro, Marine Current Turbines, and Clean Current Power (FORCE, 2010).
Alaskan Hydrokinetic Power Resource Evaluation Projects
The first step in developing hydrokinetic power resources requires knowledge of how much hydrokinetic
energy is potentially available, where it is located, and how local site conditions affect turbine
installations, operations, and maintenance. Two projects through the AEA are underway to characterize
potential hydrokinetic power for several rivers in Alaska, and a Department of Energy (DOE) study is
being conducted to characterize the hydrokinetic potential of rivers and constructed waterways throughout
the U.S. including Alaska. The AEA recently published results from an assessment of Alaska's coastal
tidal hydrokinetic potential (Alaska Energy Authority, 2009).
With funding from the AEA, the University of Alaska Anchorage (UAA) is conducting a two-year
hydrokinetic energy assessment of major rivers in Alaska. It is expected that the project will be extended
for a third year. In year one, UAA visited 17 sites on the Yukon and Kuskokwim Rivers including Bethel,
Lower Kalskag, Upper Kalskag, Aniak, Chuathbaluk, Napaimute, Galena, Koyukuk, Nulato, Kaltag,
Grayling, Anvik, Holy Cross, Marshall, Pilot Station, St. Mary's, and Mountain Village. In year two,
UAA visited 10 sites on the Kuskokwim, Susitna, and Copper Rivers including Whitestone, Tanacross,
Gakona, Copper Center, Chitina, Teller, Stony River, Sleetmute, Red Devil, and Crooked Creek. Based
on data collected and nearby USGS gage data, hydraulic and hydrologic models are being developed and
hydrokinetic energy potential is being assessed. Preliminary findings indicate that nearly all of the sites
17
have sufficient velocity to allow power generation. The sites farthest upstream have the highest velocities
and, therefore, the highest hydrokinetic power density. In Pilot Station (on the Yukon River), for example,
preliminary results indicate that the river could supply between 300 and 400 Watts per square meter of
river cross-section. During 2011, UAA plans to study five to ten additional sites including additional sites
on the upper Yukon. UAA is also doing modeling to estimate the impacts of hydrokinetic devices on river
velocity, water level, and sediment transport.
In the spring of 2010, UAA, UAF, and NREL began a collaborative project led by EPRI and funded by
DOE to conduct a nationwide hydrokinetic assessment. In April 2010, the AEA hosted a meeting of
national hydrology "experts," who provided guidance on what methodology to use in conducting the
assessment. In the first year of the study, the team made use of NHDPIus to obtain estimates of average
velocity and discharge at major river junctions of the U.S. ("NHDPIus" is an extension of the National
Hydrologic Database [NHDJ that includes DEM and river slope data.) The team determined that the top
ten river sections, in terms of gross power potential, are found on the Mississippi, Columbia, and Yukon
Rivers. Hydrologists are now working with the Corps of Engineers to gather additional river cross-section
data in order to provide higher resolution power -density estimates of these major sources of hydrokinetic
energy. In the second year, the practical limits of power availability will be assessed, accounting for
issues such as navigational uses of the rivers and impacts of hydrokinetic devices on river flow.
In December 2010, UAA and the Ocean Renewable Power Corporation (ORPC) will be receiving a DOE
grant to do abrasion testing of critical components (bearings and seals) of hydrokinetic devices. The
research team will construct a laboratory flume at UAA to test bearings and seals under sedimentary,
flow, and loading conditions that reflect the expected conditions at the ORPC field site in Cook Inlet. The
team is currently designing the flume apparatus and expects to begin testing in January 2011.
In partnership with ORPC, UAF has undertaken detailed characterization of a reach of the Tanana River
near Nenana, Alaska, in preparation for a second -stage planned deployment of ORPC's RivGenTm TGU
demonstration project in 2012. The river's characterization includes an examination of the site's available
year-round hydrokinetic energy potential as well as the river environment, since it may affect the turbine
installation. Aspects of the river environment of interest include river dynamics and channel stability,
sediment transport, debris flow, ice interactions, and fish. An analysis of modeling and of measurements
made in August 2009 indicates that in the main channel of the reach of river at the study site, the current
velocity maximum was about 6 knots (3 m/s) with an average velocity of about 4 knots (2 m/s). The
amount of available specific power per square meter ranged from 1900-6500 W/m' with most of the river
reach exceeding 2600 W/mZ. Analysis of turbulence data indicates that the river channel is stable in the
upper part of the reach and appears to be migrating from the left to the right shore at the downstream end
of the test site river reach. Recent findings indicate that the riverbed at Nenana has a large amount of bed -
load sediment transport ranging from sand size to cobble size, as a general function of current velocity.
Analysis of river morphology and hydrodynamics just below the railroad bridge indicates that the reach of
river just below the river may be most suitable for deployment of a TGU, and additional characterization
work is underway to confirm these findings.
Challenges to Development of a Viable Alaskan Hydrokinetic Power Industry
Developing a vibrant hydrokinetic commercial industry involves determining the technological,
operational, and economic viability of hydrokinetic turbines, meeting permitting requirements, and
gaining stakeholder acceptance.
Technological and economic viability is a function of a specific manufacturer's technology and power -
generation costs in target markets, and is not a topic of this report. Operational viability is affected by the
ability of a given hydrokinetic turbine technology and its support systems to operate in the river or tidal
18
environment of interest. For rivers in Alaska, this means operating in turbulent currents and specific
discharges that vary seasonally; it also means interaction with sediment, floating and submerged debris
(Figures 17), ice during freeze-up (Figure 18) and breakup, and local and migrating fish and marine
mammal populations. High -velocity currents, specific power density, and specific discharge are localized
in a river channel. Such channels have riverbeds and banks of sediment, gravel, and cobbles that may
migrate, causing the high -specific discharge flow to shift away from an installed turbine (Figure 19).
Debris exists at all depths in Alaskan rivers because of the presence of trees, branches, and twigs with
different degrees of absorbed water, and rocks and soil. At Ruby, efforts to protect the turbine from
floating driftwood using a simple A -frame prow were successful during earlier trials. However, debris
floating beneath the river surface snagged on the turbine's floating platform anchor chain, causing a
decrease in current velocity immediately in front of the turbine, with an associated reduction in electrical
output as the accumulated debris increased (Bryson, 2009). More severe debris problems plagued the
Ruby deployment (Figure 14) and the Eagle project turbine deployments during 2010. Alaskan rivers
carry debris throughout the open -water season, and more debris often enters rivers as stage increases;
however, the relationship between river stage and debris size, amount, and distribution throughout the
water column is not well understood or characterized. For large rivers, such as the Yukon, the relationship
between debris and river stage is even more complex, as tributaries with high local stage may dump large
amounts of debris into the main channel with little noticeable change in stage of the main river. Such
information is needed to determine how debris will interact with turbines and to develop debris -mitigation
methods.
The potential hydrokinetic energy of Alaskan rivers is highest during the period of open water and greatly
reduced during winter months when the rivers are covered by ice. For example, open -water season for the
Tanana River is nominally from sometime in May until sometime in October, with mean river discharge
ranging from about 708 to 1700 m3/s (25,000 to 60,000 ft3/s). During winter months, mean discharge
decreases to a low of about 200 m3/s (7000 ft3/s) (Langley, 2006) (Figure 20). These figures correspond to
main channel current velocities that can exceed 3 m/s during open water and drop to less than 0.8 m/s
during winter. This seasonal difference is significant to the operation of turbines, since most turbines
require current velocities of about 3 knots (1.5 m/s) to operate viably.
A first consideration for turbines installed below the water surface in winter is whether low currents are
sufficient to overcome turbine internal resistance to motion; another consideration is whether the turbine
is economically viable to operate, since low current velocities produce very small amounts of power. One
possible reason to operate a turbine throughout the winter is to capture energy at the transition between
ice -covered and open -water seasons during freeze-up in the fall and just after breakup in the spring.
Capturing energy at this transition might increase the period of high -current power conversion by as much
as 1 or 1 % months —energy that might otherwise be lost by the time taken to deploy and remove a turbine
each season (Figure 20). A challenge for turbines installed underwater is that of operating during the
initial freeze-up period, when the river is in a super -cooled state and frazil ice crystals form throughout
the water column, adhering to turbines or other objects in the water (Figures 18 and 21). A second
challenge is to ensure that the location of a submerged turbine is not prone to ice jams during spring
breakup. Susceptible locations can generally be determined by examining past ice jam occurrences, since
they tend to be caused by local constrictions in the river or by changes in flow direction.
19
Figure 17. Log debris island impacting (upper left ) and carrying off (upper right and lower left) a fish wheel on
the Tanana River near Nanana, Alaska, on August 1, 2008, and depositing it against a bridge pier (lower right)
(courtesy of Stephen Lord)
�,
T > Q>G \I� `>
i = O°C
(water tempera[urel
i
I frazil
Figure 18. River ice freeze-up process
NO]
Velocity Magnmide (Irds) Total Specific Discharge (W21s)
3-2 41f2Yncc6-3 32.4
2.9 292
2.6 6500 25.9
2.3 5850 227
2.0 5200 19.6
1.6 4550 162
13 3900 13.0
1.0 3250 97
07 1950 6.5
03 1300 3.3
0.0 0.0
1650
0
I
a b c d
Figure 19. Calculated current velocity (a), specific power density (b), total specific discharge (c), and maximum
total specific discharge (d) for the Tanana River based on measurements made in August 2009. The main channel
is stable from the upstream location (bottom of images), but becomes unstable at the downstream location (top of
images) as indicated by lower and less concentrated velocities, specific power density, and total specific
discharge. The migration of the main channel to the right bank is indicated by the shift of the line of maximum
total specific discharge from the left bank to the right bank at the downstream location (d) (Toniolo et al., 2010).
Max r
Near
s
I— lagan
W
CO
Z
i _
O
i
0
I I I
IM OCT NLV DFL IA,4 i'M VAI A79 IW _IME AH.Y AN SEAT
WMERYEAR M-MM
Figure 20. Tanana River daily discharge from
1962-2000 (Langley, 2006)
21
Figure 21. Overnight accumulation of frazil ice on four different material types during Tanana River freeze-up.
From right to left, the samples consist of an ABS sample mount for (1) teflon, (2) stainless steel, and (3) steel. Frazil
ice also adhered on the ABS (seen as the darker material in the lower half of each sample). The accumulation of
frazil ice on teflon was about the same as on the other samples (5-9 cm on the upstream side of the samples), but
slid off the teflon sample as it was removed from the water due to low adhesion,
The challenges described in this section are primarily related to river deployment of hydrokinetic
turbines, since bottom -founded turbines in many tidal locations will be well below the water surface, thus
avoiding surface debris and many problems related to ice in winter. However, concern about interaction
with fish and marine mammals and the influence of current flow dynamics including turbulence are
common concerns to both tidal and river deployments. In addition, in a location such as Cook Inlet,
sediment, turbulence -induced scour and shear, subsurface debris, and neutrally buoyant ice can influence
turbine operations. In addition, there is the ever-present need to address the concerns of permitting
agencies and other stakeholders over the relative benefits and impacts of hydrokinetic technology in both
river and marine environments.
Stakeholders with an interest in protecting aquatic environments will want to know the potential impacts
of hydrokinetic conversion technologies on fish and marine mammals and the aquatic habitat, and will
22
want to have input to the permitting process to protect stakeholder interests. Support or opposition from
stakeholders can affect the pace of acceptance for hydrokinetic energy in local communities (Hartzell,
2010). Conversely, many turbine developers and hydrokinetic power generation advocates express
frustration with the extent of study and the expense of meeting imposed permit requirements
(Greenemeier, 2010). The ability of turbine developers to raise investment capital is restricted when it
takes an excessively long time to obtain permits or when the permitting requirements are not well known,
a problem that permitting agencies recognize (WeIlinghoff et al., 2008).
Conclusions and Approaches to Facilitating Hydrokinetic Power in Alaska
Turbines placed directly in river, ocean, or tidal current generate hydrokinetic power from the kinetic
energy of moving water, typically require a minimum current of 2-4 knots (1--2 m/s), and provide optimal
performance at currents of between 5-7 knots (1.53.5 m/s). With over 90% of the total U.S. tidal
hydrokinetic resource and 40% of the U.S. river hydrokinetic resource, Alaska is well positioned to use
hydrokinetic turbines to help replace the use of fossil fuels. This is an especially attractive option for
reducing dependence on high -cost diesel in the many remote communities in Alaska that are situated
along navigable waterways.
Studies to characterize the hydrokinetic potential of Alaska river and tidal currents have concluded that
hydrokinetic turbines are a viable method of generating power in Alaska, with the cost of electricity
varying significantly depending on the location of the installation. In 2010 dollars, a 17 MW tidal power
generating facility at Knik Arm is estimated to cost around $2,500/kW, with electrical cost of about
$0.11/kWh. River hydrokinetic turbines located in remote locations range from $3,300—$8,000/kW, with
electrical costs of $0.19—$0.68/kWh (using 2010 dollars). Further studies are in progress not only to
characterize Alaskan river and tidal hydrokinetic power potential, but also to provide information needed
to plan future projects in Cook Inlet and the Tanana River and information of general interest for future
planning at a number of other Alaska rivers.
At present, only two hydrokinetic turbines have been tested in Alaska: a 5 kW turbine at Ruby for short
periods during 2008, 2009, and 2010, and a 25 kW turbine at Eagle during 2010. The deployment at
Eagle, which was grid -connected, can be readily converted to full commercial operation if tests are
successful. Additional demonstration projects are planned for Cook Inlet, the Tanana River, and the
Kvichak River, with other interested communities developing turbine deployment concepts. Additional
hydrokinetic projects outside of Alaska include Hydra Green Energy's 100 kW installation in Hastings,
Minnesota; Clean Current's 65 kW installation at Race Rocks Ecological Reserve in Canada; and Verdant
Power's tidal installations at Roosevelt Island in New York and a 5 MW installation on the St. Lawrence
River near Cornwall, Ontario.
Challenges to developing a commercial hydrokinetic industry in Alaska include determining the
technological, operational, and economic viability of hydrokinetic turbines, meeting permitting
requirements, and gaining stakeholder acceptance. Hydrokinetic technology can be affected by debris,
sediment, frazil and surface ice, river dynamics (turbulence, current velocity, channel stability), and the
effect of turbine operations on fish and marine mammals and their habitat. The question of turbine -
operation impacts on the aquatic environment is one of the major issues that will determine stakeholder
and permitting agency views toward this new technology.
River and marine hydrokinetic technology (RMHT) is still at the emerging stage of development and is
approximately at the same stage that wind power generation technology was 15 to 20 years ago (Marine
Hydrokinetic Technologies, 2009). Moving RMHT from the emerging stage into the practical commercial
stage will require support similar to that provided to wind technology development during its nascent
years. This support includes funding for research to develop emerging RMHT and developing an
23
understanding of the river and marine environments that will host RMHT. Funding support will also be
needed to develop data and modeling tools required to describe the interactions between RMHT and
aquatic environments. There is a need to engage all relevant stakeholders through dialogue at the earliest
stages of project development in order to develop reasonable approaches to permitting and to develop
Alaska -based expertise that is well integrated with the national scene.
In Alaska, the beginnings of many of the structures described in the previous paragraph are already in
place and can be used to help push RMHT toward commercial realization. The state legislature has
recently created an Emerging Technology Grant Fund to complement the existing Renewable Energy
Grant Fund, and the Denali Commission is actively supporting a hydrokinetic demonstration project at
Eagle. These are important steps, as they provide funds that directly develop in -state capabilities; they
demonstrate to federal agencies such as DOE and BOEMRE that the state has a serious interest in this
technology; and they provide a funding source that can be used to match federal grant funds at the
national level.
The beginnings of in -state capability and expertise for RMHT is also in place, with active efforts to
develop and deploy systems and conduct studies of river and marine environments, as described in earlier
sections. These projects and contacts involve partnerships in nationally funded and state -funded projects
(e.g., DOE, BOEMRE, AEA, and Denali Commission) and participation in workshops to examine the
ecological effects of tidal hydrokinetic technology. The AEA has created an Ocean/River and Geothermal
division that has established a RMHT interest group, is engaging manufacturers, users, and agencies in
dialogue, and is providing information through its online portal. The Alaska Hydrokinetic Energy
Research Center is working with industry, agency, and community stakeholders to provide applied
research, outreach, and training needed to facilitate development of an Alaska hydrokinetic industry.
Alaska is well positioned to facilitate the transition of RMHT from emerging technology through the next
five- to ten-year period that it is estimated to take before long-term prototype testing and
commercialization is realized (Marine Hydrokinetic Technologies, 2009). By building on existing
structures to ensure access to adequate development research funds (state and federal), developing in -state
expertise and capabilities, and engaging stakeholders, balanced and coordinated progress is possible.
The one area where existing efforts and funding is lagging is the development of a science -based
understanding of how fish and marine mammals will interact with RMHT. Issues of fish and marine
mammals have a large stakeholder base related to ecological stewardship, economics, culture, and
lifestyle that significantly affects agency views toward what requirements may be needed to permit
RMHT. Agencies have indicated repeatedly that what they wish to know is how hydrokinetic technology
will affect aquatic habitats and biology, to ensure that aquatic resources will be available to future
generations. The design and conduct of targeted studies, in cooperation with agencies, turbine
manufacturers, and communities, to assess the impacts of hydrokinetic turbine technology on the aquatic
environment would provide agencies with information needed to rationally define specific permit
requirements.
Expected Five -Year Trajectory for Hydrokinetic Technology in Alaska
Five years ago, hydrokinetic technology consisted primarily of ideas in papers and studies. During the
ensuing five years, these concepts have been developed into actual devices and demonstration projects. If
the current state of activity and high interest in developing RMHT continues, and with supportive
involvement of agencies and stakeholders, procedures for conducting demonstration projects should be
well defined in the near future. In addition, knowledge developed from the initial deployment of devices
will point to problems, solutions, and improved technology that aid second -generation efforts and longer -
term deployment systems. Over the next five years, it is likely that several long-term demonstration
projects will have been completed and that initial small-scale commercial systems will be installed and
24
operational. It is also likely that studies needed to better define the interaction between hydrokinetic
technology and the aquatic environment will be completed and that permit requirements for projects will
be well defined. A better understanding of the limits of application of RMHT during winter months
should also be known. The focus of development will be to optimize existing hydrokinetic technology,
improve technology based on identified operational problems, and develop better economic understanding
of how hydrokinetic power generation technology can be integrated into the family of other renewable
and fossil fuel energy sources and transmission systems.
25
References
Alaska Energy Authority. 2009. Renewable energy atlas of Alaska. Alaska Energy Authority
(htt://alaskarenewableencr .or alaskas-resources/alaskas-renewable-ener - otential , 28 pp.
AWEA. 2009. Wind web tutorial: Wind energy cost. Retrieved from http://www.awea.org/fag/
wwt costs.html
Bedard, R. J., Privisic,M., and Polagye, B. L. 2009. Marine energy: How much development potential is
there? RenewableEnergyWorld.com, Retrieved from
htt://www.renewablee.ner world.com/rea/news/ rint/article/2009/04/marine-ener -how-much-
development-potential-is-yhere
Bernitsas, M. M., et al. 2008. VIVACE (vortex induced vibration for aquatic clean energy): A new
concept in generation of clean and renewable energy from fluid flow, Journal of Offshore Mechanics
and Arctic Engineering, 130(4): 15.
Boehlert, G. W., McMurray, G. R., and Tortorici, C. E. (eds.). 2007. Ecological Effects of Wave Energy
Development in the Pacific Northwest: A scientific workshop, Oct. 11-12, 2007 (NOAA Technical
Memorandum NMFS-F/SPO-92, pp. 1.5-21.
Bryson, G. 2009 (February 4). In -river generator may give bush power alternative. Anchorage Daily
News, Retrieved from htt://www.adn.com/2009/02/04/679569/in-river- enerator-ma - ive-
bush.html.
Clean Current Power Systems Incorporated. 2008. The Race Rocks tidal energy project. Retrieved from
http://www.cleancurrent.com/technology/rrproject.htm
EERE. 2008a (July). 20% wind energy by 2030: Increasing wind energy's contribution to U.S. electricity
supply. Department of Energy. Retrieved from http://wwwl.eere.energy.gov/windandhydro/
pdfs/41869. pdf
EERE. 2008b. Marine and hydrokinetic technology glossary. Retrieved from
htt://wwwl.eere.ener ov/windandh dro/h drokinetic/techTutorial.as x
EMEC. 2010. Retrieved from http://www.cmec.org.uk/index.asp
FERC. 2010. Issued hydrokinetic preliminary permits. Retrieved from
http://www.fere,pov/industries/hydropower/indus-act/hydrokinetics/issued-hydrokinetic-permits-
map.pdf
FORCE. 2010. Retrieved from http_//force.imi3actworkshop.ca/about
Greenemeier, L. 2010. Going with the flow: Hydrokinetic power developers face technical and regulatory
hurdles in bid to tap tides. Scientific American. Retrieved from
htt://www.scientificamerican.com/article.cfm?idrtidal- ower-h dro
Hartzell, F. 2010 (February 25). GreenWave pusuring Mendocino wave energh project. Mendocino
Beacon (CA), Retrieved from http://www.mendocinobeacon.com, posted on
http://mendocoastcurrent.wordpress.com/2010/02/25 /y,reenwave-pursu ing-mendoc ino-wave-energy-
rp olectl .
041
Hasz Consulting. 2010. A conceptual design of a river in -stream energy conversion device for Alaskan
rivers. Unpublished consulting report to Whitestone Power and Communications, Hasz Consulting
Co., P.O. Box 1229, Delta Junction, AK 99737, 75 pp.
Junginger, M., Faaij, A., and Turkenberg, W. C. 2005. Global experience curves for wind farms. Energy
Policy, 33: 133-150.
Khan, J., and Bhuyan, G. S. 2009. Ocean energy: Global technology development status, PowerTech
Labs Inc. Prepared under ANNEX I — Review, exchange, and dissemination of information of ocean
energy systems, Final Technical Report IEA-OES Document No.: T0104, 83 pp.
Langley, D. 2006. Claculation of scour depth at the Parks highway bringe on the Tanana River at Nenana,
Alaska, using one- and two-dimensional hydraulic models. USGS Scientific Investigations Report
2006-5023.
Marine Hydrokinetic Technologies. 2009. Finding the Pathway to Commercialization: Hearing before the
Subcommittee on Energy and the Environment of the House Committee on Science and Technology,
111`' Congress (testimony of Roger Bedard).
Miles, A. 2010. FERC's hydrokinetic program: Marine energy regulatory framework — July 15, 2010.
http://www.cleanenergystates.org/JointProjects/METAP/METAP—Ann Miles-0715IO.pdf
Miller, G., Franceschi, J., Lese, W., and Rico, J. 1986. The allocation of kinetic hydro energy conversion
systems (KHECS) in USA drainage basins: Regional resource and potential power, NYUDAS 86-
151, Final Report, August, 54 pp.
Neville, A. 2009 (April 1). Hydrokinetic plant piggybacks on existing hydro plant. Retrieved from
http://www.powermag.com/issues/features/Hydrokinetic-Plant-Piggybacks-on-Existing-Hydro-
Plant—1794.htm]
ORPC. 2010. ORPC projects: Alaska. Retrieved from http://www.occanrenewablepower.com/
ocgenproj ect—aaska. htm
ORPC. 2010. Beta TidGenTM power system performance test report executive summary, Ocean
Renewable Power Company, August 16, 2010.
Polagye, B., and Bedard, R. 2006. Tidal in -stream energy resource assessment for Southeast Alaska,
EPRI North American tidal flow power feasibility project. Report to the Alaska Energy Authority,
EPRI-TP-003-AK (http://oceanenergy.epri.com/streamenergy.html), 64 pp.
Polagye, B., and Previsic, M. 2006. System level design, performance, cost, and economic assessment —
Knik Arm Alaska tidal in -stream power plant. EPRI-TP-006-AK
(http://occanenergL.epri.com/streamenergy.html), 128 pp.
Polagye, G., Copping, A., Kirkendall, K., Goehlert, G., Walker, S., Wainstein, M., and Van Cleve, B.
(Workshop Steering Committee). 2010. Environmental effects of tidal energy development: A
scientific workshop, Workshop briefing paper, University of Washington, Seattle, Washington,
March 22-24, 2010.
Poulson, S. 2003 (November). The spirit of the coming age: Shell's strategy for a renewable energy.
Presentation for Shell Wind Energy. Retrieved from http://www.wind-energie.de/
fileadmin/dokumente/Themen_A-Z/Ziele/Shell_Vortrag EE_Strategie 2003.pdf
27
Previsic, M. 2007. The technology: Wave energy development on the west coast. In: Ecological Effects of
Wave Energy Development in the Pacific Northwest: A scientific workshop, Oct. 11-12, 2007 (G.
W. Boehlert, G. R. McMurray, and C. E. Tortorici, eds.), NOAA Technical Memorandum NMFS-
F/SPO-92, pp. 15-21.
Previsic, M. 2008. System Level Design, Performance, Cost and Economic Assessment — Alaska River
In -Stream Power Plants. EPRI feasibility study, EPRI RP 006 Alaska, 99 pp.
Previsic, M., and Bedard, R. 2008. River In -stream Energy Conversion Characterization of Alaska Sites.
EPRI-RP-003_Alaska, February 29, 2009, 74 pp.
Previsic, M., and Bedard, R. 2009. Yakutat conceptual design, performance, cost and economic wave
power feasibility study, EPRI-WP-006-Alaska(hLtp://occanenergy.epri.com/waveenergy.htmi), 43
PP.
The Business Wire. 2007 (July 31). Denali Commission funds Alaska's first hydrokinetic river turbine
project at Eagle. Retrieved from http://www.thefreclibrary.com/Dcnali+
Commiss ion+Funds+Alaska%27s+First+Hydrokinetic+River+Turbi ne...-a0166996322
Toniolo, H., Duvoy, P., Vanlesberg, S., and J.B. Johnson. 2010. Modelling and field measurements in
support of the hydrokinetic resource assessment for the Tanana river at Nenana, Alaska. Proc, Inst.
Mech. Eng, J. Power and Energy, 224, Part A, DOI: 10.1243/09576509JPE 1017.
Verdant Power. 2009a. The RITE project. Retrieved from http://verdantpower.com/what-initiative/
Verdant Power. 2009b. The CORE project. Retrieved from hi!p://verdan-tpower.com/what-core/
Union of Concerned Scientist. 2009. How hydrokinetic energy works. Retrieved from
http://www.ucsusa.org/clean_energy/technology_and_impacts/energy_technologies/how-
hydrok inetic-energy-works. htm 1
Wellinghoff, J., Pederson, J., and Morenoff, D. L. 2008. Facilitating hydrokinetic energy developent
through regulaory innovation. Energy Law Journal, 29: 397-420,