HomeMy WebLinkAboutTenakee Inlet Reconnaissance Study - Geothermal Resource - HDL Alasksa - 2012 - REF Grant 7040073GRC Transactions, Vol. 36, 2012
649
Keywords
Reconnaissance, shallow temperature survey, low tempera-
ture resource, Alaska, soil sampling, water chemistry, binary
power plant
ABSTRACT
A reconnaissance study of the Tenakee Inlet geothermal
resource was conducted in order to evaluate its nature and de-
termine if there is potential for power generation. The resource
is in a remote, rugged area of southeastern Alaska, accessible
via helicopter. A prior hot spring temperature measurement was
176 °F. Tenakee Creek is located to the immediate northeast of
the hot springs. The Queen Charlotte Fairweather fault system
lies to the west of the resource and is part of a transform plate
boundary with associated earthquakes and linements aligned
north to south. Fieldwork consisted of a shallow soil tempera-
ture survey and collection of soil, water, and rock samples. The
shallow soil temperature survey indicated a broader thermal area
than just around the hot springs and includes portions across
Tenakee Creek. Soil samples had chemical species that were
anomalous near the hot springs as well as across the creek in the
same areas as the higher temperature readings. Water samples
from the hot springs indicated fluids low in chlorine and bi-
carbonate but high in sulfate. The hot springs waters are most
likely associated with volcanic waters and perhaps heated by
steam from a deeper reservoir. Surface temperatures of the hot
springs ranged from 161 to 177°F over the course of the 15-day
long field effort. Based on the chalcedony geothermometry the
hot springs fluids may have been heated to 260°F. The surface
and subsurface temperatures are in the range appropriate for a
binary geothermal power plant.
Introduction
The purpose of the reconnaissance study was to evaluate
the nature of the resource and determine if there was potential
for power generation to serve the communities of Pelican and
Hoonah. The resource is located near the head of Tenakee Inlet
on northern Chichagof Island, in southeast Alaska. The Tenakee
Inlet Geothermal Resource is located approximately 19 air miles
southwest of Hoonah Alaska along an un-named river we have
called Tenakee Creek. Figure 1 presents a location map for the
hot springs. The area is characterized by rugged, steep terrain
covered with thick vegetation typical of the southeastern Alaska
rainforest. Topography limited the exploration area to the valley
floors and to the first bench above the river valley.
The resource is characterized at the surface by at least four
small hot springs that occur together on the southeast side of the
Tenakee Creek located at approximately 57° 59’ 24” N and 135°
56’ 20” W. An aerial photograph of the vicinity of the hot springs
is presented in Figure 2. The focus of the study was the immediate
hot springs area and approximately ¼ to ½ square mile surround-
ing the hot springs. There are two streams that bound the study
area on its southwestern and northeastern sides.
Reconnaissance of a Low-Temperature Geothermal Resource,
Tenakee Inlet, Alaska
Lorie M. Dilley, Trevor Crosby, and Ryan Norkoli
Hattenburg Dilley & Linnell, LLC
Anchorage, Alaska USA
ldilley@hdlalaska.com
Figure 1. Location map for Tenakee Inlet hot springs. Hot springs located
approximately 19 miles southwest of Hoonah Alaska in southeast Alaska.
There is a number of hot springs on Chichagof Island as shown by black
circles on the vicinity map.
650
Dilley, et al.
The hot springs shown in Figure 1 have been documented and
tested for minerals and temperature. The reported surface tempera-
ture of the Tenakee Inlet hot springs is 176°F with geochemistry
of the waters indicating a maximum subsurface temperature of
243°F (Motyka et al, 1983). The other hot springs in the region
have lower surface temperatures.
The Tenakee Inlet springs are comprised of four small springs
that flow from the base of a rock cliff approximately 40 to 50 feet
in height. The hot springs area is small about 50 feet long by 20
feet wide occurring on a gravel bar that is heavily vegetated with
alders, willows, and spruce trees. The gravel bar is approximately
800 feet long and 100 feet wide. The hot spring site and the location
of the four hot springs are shown in Figure 3. There is an outflow
creek from the spring site that leads to Tenakee Creek. A stream
named the Stairway to Heaven Creek cascades down the slope
and mixes with the outflow near the spring sites. Seeps occur
along the shore of the gravel bar and are periodically inundated
by Tenakee Creek.
Fieldwork consisted of collecting shallow soil temperature
data, as well as soil, water and rock samples from various loca-
tions surrounding the hot springs and the immediate vicinity. A
grid was established to systematically collect temperature data
and soil samples. Water and rock samples were more varied and
were dependent upon their location with respect to the hot spring.
Regional Characteristics
General Geology
The Tenakee Inlet area is composed of Devonian argillite,
graywackes and limestones that were subsequently intruded by
a wide variety of igneous rocks (Loney, et al 1975). These rocks
outcrop near the study area and north of it. The intrusives vary in
age, but are primarily Cretaceous in the study area and are mainly
diorite to granodiorite in nature. These rocks are widely distributed
on Chichagof Island. To the south of the study area there is a large
body of Tertiary intrusives consisting of hornblende leuoconorite
and troctolite. The Devonian sedimentary rocks have undergone
extensive regional and contact metamorphism. The
intrusives have metamorphosed them into hornfels,
and marbles. The rocks are intensely folded and
faulted. The fold axes trend northwest.
Structural Geology
The geologic structure of the area is dominated by
the Queen Charlotte-Fairweather (QCF) fault system
and the Chatham Strait Fault. The QCF fault system
lies to the immediate west of Chichagof Island and
the Chatham Strait Fault defines the Chatham strait
between Chichagof Island and Admiralty Island to
the east. The faults of the QCF system are active
right-lateral structures with large displacements.
The Chatham Strait Fault offsets rocks as young as
middle Tertiary and by as much as 90 miles. (Gehrels
and Berg 1994).
The QCF fault system defines the boundary
between the Pacific and North American plates. In
the middle Mesozoic prior and/or concurrent with
the intrusion of the igneous rocks in the study area,
southeast Alaska was involved in the subduction of
the Pacific Plate beneath the North American Plate,
which over time evolved into the dominant transform
plate boundary seen today. This tectonic activity
Figure 2. Aerial photograph of vicinity. Note location of the hot springs
on the southeast side of Tenakee Creek. Flow as indicated by blue arrow
is to the northeast and then near the top of the photograph, Tenakee Creek
turns to the southeast and flows into Tenakee Inlet. Boundary streams oc-
cur to the northeast and southwest of the hot springs.
Figure 3. Site map of hot springs area. Note the location of the four hot
springs, the seeps at the edge of Tenakee Creek and the outflow from the
hot springs. The first bench located above the hot springs is approximately
40 to 50 feet higher than the base of the slope. The sampling grid is par-
tially drawn for reference. The hot springs occur at grid point A4.
651
Dilley, et al.
has resulted in a complicated pattern of thrust, oblique slip, and
strike-slip faults on Chichagof Island. The rocks in the study
area are part of the Alexander Terrane, which is inferred to have
continental origins (Karl, 1999). The rocks are interpreted to
represent intermittent volcanic arc activity.
Modern earthquake activity occurs along the QCF fault sys-
tem. The most recent large magnitude earthquakes in the area of
the hot springs occurred in 1927 and 1939. The epicenter of the
1927 magnitude 7.1 event occurred at latitude 57.69 and longitude
-136.07. The 1939 magnitude 6 event occurred at latitude 58.00
and longitude -136.0. The hot springs are located at latitude 57.99
and longitude -135.939.
Climate
Climate in the region is maritime characterized by cool sum-
mers and mild winters. Foggy periods typically occur in the spring
and fall. Summer temperatures in Hoonah average from 52 to
63 °F, and winter temperatures from 26 to 39 °F. Precipitation in
Hoonah averages 100 inches annually, with 71 inches of snowfall.
During our fieldwork we established a small weather station
at the base camp near the hot springs. The temperatures in late
September – early October ranged from 36 to 48 °F. Precipitation
occurred on six of the 15 field days and ranged from 0.04 inches
to 1.02 inches.
Methodology
Fieldwork began on September 21, 2011 and was completed
on October 9, 2011. The Hattenburg Dilley & Linnell six-man
field team was based out of Hoonah and supported with full-time
helicopter transport provided by Coastal Helicopters. A grid was
developed based on 300 feet by 300 feet squares prior to the field-
work. This grid and the study area proposed were limited due to
topography, vegetation, and subsurface temperature information.
Three survey control points were established (two near the hot
springs and one on the east side hill) in order to maintain accurate
survey control for future fieldwork and development. A rectangular
grid was then established from the base line onto the surrounding
hot springs area. GPS coordinates were collected at grid points.
These points were used as the locations to collect the soil samples
and install shallow temperature probes. The field crew started
from the hot spring location and worked outward in a spiraling
pattern to gather the data, with tightly-defined 100 foot spacing
nearest the hot spring, then expanding to 300 ft spacing. At the
conclusion of the 15 day field work, the team had established over
120 grid points. Eighty-four temperature readings were obtained;
and 37 water, 63 soil and 7 rock samples were collected. Rock
outcrops were difficult to find, therefore only a few samples were
collected for petrographic analysis.
Field Work
Shallow Soil Temperature Survey
The shallow soil temperature survey used steel pipes as probes
inserted into the ground and a thermistor was installed. The equip-
ment included 5-1/2 foot long sections of 3/4” steel pipe for probes,
RTD (Resistance Temperature Detector) temperature measuring
devices, demolition hammers for driving probes up to 5 feet into
the ground, and data loggers/meters to record the temperature
measured by the RTD. The steel pipe was fabricated into a probe
by welding one end closed and hard facing it to allow it to penetrate
hard ground. Forty probes were fabricated and reused during the
study. The field work involved inserting the steel probes in the
ground, waiting for thermal equilibration, installing thermistors,
and measuring the temperature at the bottom of the probe, then
moving the probes to a new location and repeating the operation.
Readings that indicated higher temperatures were remeasured. It
took approximately 1 to 2 hours for the thermistors and ground
disturbance to equilibrate.
Selective Extraction Geochemical Analysis
We conducted a selective extraction geochemical study
consisting of obtaining samples from the B soil horizon and con-
ducting enzyme leach and terrasol selective digestion on the soil
sample. The method relies on the fact that geothermal systems,
like mineral deposits, have at the surface a number of chemical
elements that get distributed around their margins. Trace elements
can be trapped in amorphous oxide coatings on sand and silt grains
in soil near the surface. Enzyme leach and Terrasol digest these
coatings and releases the trapped trace elements. An analysis of
the sample is conducted for up to 68 trace and major elements by
ICP-Mass Spectrometry. The concentrations of these elements
are mapped and distinct patterns indicate areas of interest. Sam-
pling consisted of using a clean spoon to obtain soil from a hole
excavated below the organic layers. Care was taken to maintain
clean spoons and sampling equipment. An approximately 25 gram
sample collected using a stainless steel table spoon was placed
in a 50 ml plastic tube that was supplied by the laboratory. The
samples were typically fine-grained. Care was taken to avoid and/
or eliminate particles larger than about coarse sand.
Water Sampling
Water samples were collected for chemical analysis from the
hot springs, and Tenakee Creek. Additional samples were taken
upstream and downstream of the hot spring location and from
the two boundary streams. Temperature, pH, and conductivity
were collected on-site at each location. Sampling consisted of
collecting approximately 800 ml of water in several bottles sup-
plied by the laboratory. The bottles were washed using the fluid
to be collected. The water was filtered if it appeared to be cloudy.
The majority of the samples were not filtered due to the clear
nature of the water. In addition to the water samples collected
for chemical analysis, additional 25 ml samples were gathered at
select locations for isotope analysis.
Laboratory Analysis
Skyline/Actlabs of Tucson Arizona analyzed the soil samples.
The water samples were submitted to WetLab of Nevada for
cations/anions analyses, and geothermometer components, and
to Southern Methodist University in Texas for isotope analysis.
A selective extraction process (enhanced enzyme leach) was
used at Skyline Laboratories on the soil samples. The extraction
process leaches amorphous MnO2 and analyzes 68 trace and
major elements by ICP-Mass Spectrometry. The detection limits
are typically on ppb levels with a few elements at the ppm level.
652
Dilley, et al.
Water samples were analyzed for silica, metals, and various anions
and cations.
Data
Soil Temperature
The shallow soil temperature data obtained are presented in
Figure 4. The hottest temperatures occurred near the hot springs
and at the seeps found at the edge of Tenakee Creek. Tempera-
tures near the hot spring range from 81.2 to 108.9 °F. The hot
springs outflow had soil temperatures of between 58.3 and 86.1°F.
Seeps were observed when the water level in Tenakee Creek
was lowered during a few days of no rain. The one seep had a
nearby soil temperature of 130.5 °F. Temperatures on the hillside
above the spring ranged from 49.9 to 46.4 °F. A relatively cool
temperature of 44.3 °F was measured upstream of the hot springs
located near the edge of the gravel bar that hosts the hot springs.
The temperature readings in the 40’s were considered background
soil temperatures.
Additional temperatures
above background were en-
countered at several spots across
Tenakee Creek at the base of the
slope. The hottest shallow soil
temperatures across the creek
from the hot springs were 88.8 °F
and 59.5°F. There were several
points across the creek above 50
°F with one (56.5 °F) occurring
about 1,200 feet downstream
of the hot springs. These tem-
peratures do not appear to be
the result of outflow from the
hot springs. The temperature of
the water in Tenakee Creek was
approximately 40°F.
Water Data
The average chemical concentrations for the hot spring, seep,
and surface water samples were calculated. A location map of
these features is presented in Figure 3. The temperature of the hot
spring waters averaged 170°F with Hot Spring #1 having the hot-
test temperature of 177 °F on two sampling events and Hot Spring
#4 having the coldest at 161°F. The average water temperature for
hot springs #1 through #3 was 172°F. The average surface water
temperature was 40°F.
A spreadsheet developed by Powell and Cummings (2010) was
used to evaluate the chemistry of the water samples. Laboratory
data were entered into the spreadsheet and a series of standard
geothermal plots were developed. Geothermometers were calcu-
lated and ternary plots were produced. The CL-F-B plot shown in
Figure 4 indicates that the collected hot spring waters (HS) and the
surface water (SW) samples are from different populations. This
is important in that the two waters clearly represent separate types
of fluids. The often used Cl-SO4-HCO3 ternary plot illustrates the
amounts of major anions present in the geothermal
waters (Figure 5). This plot indicates that the hot
spring waters are low in chlorine (Cl) and bicar-
bonate (HCO3) and high in sulfate (SO4). It also
indicates that the hot spring waters are associated
with volcanic waters and perhaps heated by steam
from a deeper reservoir. A high sulfate spring is
typically associated with deeper boiling zones.
The isotope plot (Figure 6) indicates that both
the hot springs and surface waters are primarily
meteoric and have not mixed with other fluids.
The chalcedony geothermometer provides a
more accurate temperature for the hot spring
fluid at depth based on the concentrations of
silica and potassium/magnesium (Figure 6); it
shows that the hot spring fluids have been heated
to 260°F.
Soil Data
The soil chemistry was plotted for six ele-
ments; i.e., Arsenic (As); Cobalt (Co); Gold (Au); Figure 4. Shallow soil temperature survey results. Note the higher than background tempera-
tures on the north side of Tenakee Creek.
Figure 5. Plots of water chemistry data. The hot springs water (HS) is clearly different from the surface water (SW)
samples collected. The hot springs waters are high in SO4 and low in HCO3 and Cl indicating possibly waters as-
sociated with volcanic waters.
653
Dilley, et al.
Manganese (Mn); Titanium (Ti); and Vanadium (V). These chemi-
cal species had orders of magnitude changes in concentrations
across the sampling area. Data were contoured using roughly the
standard deviation in a particular elements concentration. Mercury
is usually used in geothermal exploration; however, the results did
not indicate a large variation in mercury concentration.
The species plotted indicated anomalous concentrations gen-
erally near the hot springs and along the outflow but also across
Tenakee Creek where the concentrations were higher in areas
of elevated soil temperatures. The highest concentration of gold
was near the confluence of the hot spring outflow and Tenakee
Creek. The highest concentration for arsenic was across the river
from the hot springs at the grid point that recorded the highest
temperature on that side of the river. In addition, vanadium had
higher concentrations along the ridge above the hot springs per-
haps indicating a fracture or fault.
Lineations
Lineations were determined
from stereographic aerial photo-
graphs and may represent faults
or joints. The lineations were not
observed on the ground due to the
dense vegetation, however during
the helicopter flights over the area,
many of the lineations could be
seen on a regional scale. Figure
7 presents the more notable linea-
tions and the course of Tenakee
Creek. The lineations are typically
aligned northwesterly with some
cross lineations. This alignment
is typical over the entire southeast
region and is due to the large QCF
fault system and regional tectonics. Particularly interesting is
the offset in Tenakee Creek near the hot springs. There is a set
of lineations that occur northwest and the creek is offset on east-
west lineations. The measurements obtained from geological
maps indicated steeply dipping lineations.
Preliminary Interpretations
In the Tenakee Inlet Area, based on shallow temperature probe
and soil analysis data there appears to be additional thermal areas
across Tenakee Creek from the known four hot springs. These
thermal areas would suggest that the geothermal source is larger
than just the known four hot springs. The occurrence of chemi-
cal anomalies in the soil in the hotter areas across Tenakee Creek
also suggests that the hot fluids are circulating near the surface
indicating permeability.
The lineations and general tectonics of the region suggest that
the hot springs were developed due to the wrenching of the cross
cutting lineations near the hot springs which led to the fractur-
ing of the rocks. Also given the high angle nature of many of the
lineations, it is reasonable to assume that high angle faults bring
the geothermal fluid to/near the surface. The earthquake data sug-
gest that the study area is tectonically active and that the igneous
intrusives are permeable.
Based on the water chemistry, the hot springs fluids are most
likely associated with volcanic waters and perhaps heated by
steam from a deeper reservoir. The chalcedony geothermometer
indicates that the hot spring fluids have encountered temperatures
on the order of 260°F. The average surface temperature of the hot
spring waters is 170°F. These surface and subsurface temperatures
are in the range that binary geothermal power plants operate.
Much like Chena the site benefits from having cool waters at ap-
proximately 40°F as a sink.
Additional Work
A conceptual model of the area still needs to be developed.
In addition, the hydrology of the study area should be evaluated.
Geophysical studies such as self potential (SP) would assist in
characterizing the area and provide additional subsurface informa-
tion. We will be conducting additional fieldwork in the summer
Figure 6. Isotope plot on the left indicates that the hot springs waters are primarily meteoric. The geothermetry was
based on the chalcedony geothermetry due to the concentrations of silica and potassium/magnesium as shown in
the plot on the right.
Figure 7. Major lineations in the study area. Note the offset of Tenakee
Creek near the hot springs possibly indicating a wrenching effect creating
permeability for the springs.
654
Dilley, et al.
of 2012. The following presents some of the fieldwork that still
needs to be done:
1. Fly overs with an infrared camera in the spring to evaluate
potential other “hot” areas. During the summer of 2012
we will collect surface water temperatures and estimate the
flow of Tenakee Creek (Does it freeze, does it still flow,
partially frozen during the early spring?).
2. Conduct a SP geophysical survey in order to evaluate the
hydrology of the area and provide additional subsurface
information.
3. Conduct additional studies of the area across Tenakee
Creek from the hot springs where we measured high tem-
peratures and obtained anomalous soil data.
4. Investigate further the seeps near the edge of Tenakee
Creek to determine if they are related to the known or other
hot springs. Excavate holes along the gravel bar to collect
groundwater samples and to evaluate possible flow from
the hot springs to the seeps.
5. Collect flow data from the hot springs, creek, and outflow
areas.
Acknowledgements
The project was funded through a renewable energy grant
administered by the Alaska Energy Authority (AEA). Hattenburg
Dilley & Linnell (HDL) was contracted by Inside Passage Electric
Cooperative (IPEC) to manage the project and conduct the field
studies and evaluation of the geothermal resource.
References
Gehrels G.E. and H.C. Berg (1994) Geology of Southeastern Alaska. The Geology of North America Vol. G-1. The Geological Society of America.
Karl, S.M. (1999). Preliminary Geologic Map of Northeast Chichagof Island, Alaska. US Geological Survey Open File Report 96-53.
Loney, R.A, D.A. Brew, L.J.P. Muffler and J.S. Pomeroy. (1975) Reconnais-sance Geology of Chichagof, Baranof, and Kruzof Islands, Southeastern
Alaska. US Geological Survey Professional Paper 792.
Motyka, R.J., M.A. Moorman, and S.A. Liss, (1983), Geothermal Resources
of Alaska: Alaska Department of Geology and Geophysical Survey, Miscellaneous Publication 8, 1 sheet scale 1:2,500,000.
Powell, T and W. Cummings, (2010). Spreadsheets for Geothermal Water and Gas Geochemistry. Proceedings Thirty-fifth Workshop on Geothermal Reservoir Engineering Stanford University. Stanford California.