HomeMy WebLinkAboutVenetie Clinic Heat Recovery Project Agreement 2015 REF Grant 7071044Division of Enviromnental Health and Engineering Cooperative Project Agreement An Energy Efficiency Project Between: The Alaska. Native Tribal Health Consortium and The village of venetie, Alaska. Project No. AN 14-Z39 October 2014 COOPERATIVE PROJECT AGREEMENT ENERGY EFFICIENCY PROJECT VILLAGE OF VENETIE, ALASKA PROJECT NO. AN 14-Z39 To complete this project, ANTHC and the Village of Venetie mutually agree to the terms and conditions contained in this Agreement. For purposes of negotiating and finalizing this Agreement, if this document or any document executed in connection with it is transmitted by facsimile machine or electronic document, it shall be treated for all purposes as an original document. Additionally, the signature of any party on this document transmitted by way of a facsimile machine or electronic document shall be considered for all purposes as an original signature. Any such faxed or electronic document shall be considered to have the same binding legal effect as an original document. At the request of any party, any faxed document shall be re -executed by each signatory party in an original form. PREPARED BY: /a G / Date Craig Wod, P.E. Health Facilities Engineer DEHE, ANTHC RECOMMENDED BY: Date Daniel D. Reitz, P.'. Energy Efficiency Improvements Program Manager DEHE,ANTHC RECOMMENDED BY: a �T4vk Date David G. Beveridge, P. Director of Project MatiagAnent DEHE, ANTHC APPROVED BY: r Date Roald Helgrsen Chief Executive Officer ANTHC APPROVED BY VILLAGE OF VENETIE: Date First C Gf Native Village o.[' Venetie, Alaska COOPERATIVE PROJECT AGREEMENT ENERGY EFFICIENCY PROJECT VILLAGE OF VENETIE, ALASKA PROJECT NO. AN 14-Z39 TABLE OF CONTENTS A. —INTRODUCTION ^^^~^'-^'~~^--^'~^^^—'-^—^—^^-^^—^^^—~~^'~^^--^^~^~^^.—.l B. SCOPE OF PROJECT ........................ C. PROJECT C(}0T---.-----.---. Cl. Cost Estimate Table ----------------------------.—~.—..—..'--- C2. Project poud' .....~...~—..~~~. - - D. PROJECT -- ADMINISTRATION-----------~---^--'—~—^^--^^—^-^—.—..3 E. PROVISIONS FOR PROJECT � COMPLETION 3 - . ^~^^^"",AL HISTORIC PRESERVATION ACT REQUIREMENTS .......................... ...^.3 G. PARTICIPATION IN 7./��TI�/I�7�� _- —.5 H. OWNERSHIP OFPROJECT-INSTALLED EQUIPMENT ................................................... 5 COOPERATIVE PROJECT AGREEMENT ENERGY EFFICIENCY PROJECT VILLAGE OF VENETIE, ALASKA PROJECT NO. AN 14-Z39 A. INTRODUCTION DATE OF AGREEMENT: October 2014 Throughout this Cooperative Project Agreement (CPA) the following entities are referred to as follows: Native Village of Venetic Tribal Government = Tribe Village of Venetic = Alaska Native Tribal Health Consortium Village = Division of Environmental Health and Engineering ANTHC = Indian Health Service DEHE = Alaska Energy Authority IHS = Renewable Energy Fund AEA = REF The role of ANTHC, DEFIE is to create safe and healthy communities. Through Public Laws 86-121, 93-638, and 105-83, ANTIIC has assumed from the IHS the management of the sanitation facilities construction program, Under AEA REF Grant No. 7071044 for the construction of a jacket heat recovery system, the Village of Venetic has partnered with ANTHC to utilize recovered heat in a community facility. This CPA contains information about the project scope of work, funding, costs, and administration. B. SCOPE OF PROJECT This project will design and implement strategies identified in the 2013 Heat Recovery Feasibility Study in Venetic, Alaska to recover heat from the existing electrical power plant and utilize that heat to reduce the heat load in the newly constructed community health clinic. This project is expected to reduce the clinic's fuel oil usage by 2,300.gallons annually, VILLAGE OF VENETIE, COOPERATIVE PROJECT AGREEMENT PROJECT NO. AN 14-Z39 C. PROJECT COST Cl. Cost Estimate Table Job Type Scope of Work =-DS Design HR Heat recover Qty� j l Unit Cost I Extended Cost PAGE 2 OCTOBER 2014 AEA 970.00 $25,9q7--V25,970.00 530.00 $172,5$172,530,00 Tatai $198,5$198.500_on At the completion of the design phase, ANTHC Nvi11 reevaluate the project cost estimate to determine that there is adequate funding for implementation. If additional funding is needed, ANTHC will work with the community to develop alternative sources of funding. C 2. Project Funding Contributor Fiscal Year Description Amount SOA AEA 2014 State Grant No. 7071044 11N"1'HC 2014 $I98.S00 TOTAL PROJECT FUNDING Pt° �.c.t M mt Match In-Ki��d $ 5 �954 ANTHC will provide project expenditure documentation for the costs and expenses of this project directly to AEA as requests for reimbursement. Pursuant to the terms of the Grant, AEA's approval of reimbursement requests will be based on supporting documentation provided by ANTHC. The Village authorizes ANTHC to receive Grant reimbursements directly from AEA and to expend them according to this Agreement, the Grant Agreement and the General Provisions. The funding table shows the proposed distribution of funding for the scope of work to be performed under this CPA. Actual expenses may vary, and ANTHC may reallocate funding so long as the funds from each individual contributing agency are used only for components of the overall project that would be allowable if funded solely by that contributing agency, or as permitted under an otherwise applicable agreement. VILLAGE OF VENETIE, COOPERATIVE PROJECT AGREEMENT PROJECT NO. AN 14-Z39 PAGE 3 OCTOBER 2014 D. PROJECT ADMINISTRATION Project design will be completed by ANTHC. The project will be constructed by ANTHC management of local force account labor. Project design and implementation contracts will be awarded according to the following anticipated project schedule: Project Activity Date Verif Site Conditions October 2014 Develo Desi xn Sco e October 2014 Desi ri April 2015 Be in Installation June 2015 Commissionin August 2015 Evaluation October 2015 E. PROVISIONS FOR PROJECT COMPLETION The ANTHC DEHE General Provisions Manual defines the operating parameters for planning, design, and construction projects performed under this project. General Provisions dated March 2009 applicable to this Agreement are found in Attachment 1, which is hereby incorporated by reference. General Provisions apply only to ANTHC and the Village of Venetie. In lieu of the Acknowledgment of Project Completion referenced in the ANTHC DEHE General Provisions Manual, the AEA Notice of Project Closeout form will serve this purpose. The Village of Venetie is the Grantee under the award, and is responsible for compliance with the grant requirements as outlined in AEA Grant No. 7071044. However, ANTHC and the Village of Venetie will work collaboratively to ensure the grant requirements listed in FY 2011 Air Quality Agreement Appendix C: General Provisions, which is found in Attachment 2 and hereby incorporated by reference, are met. F. NATIONAL HISTORIC PRESERVATION ACT REQUIREMENTS The National Historic Preservation Act (NHPA) provides for the identification and protection of cultural resources including avoiding unnecessary disturbance of reported or known human burials and for providing mitigation when appropriate. The NHPA also requires Tribes to be consulting parties if archeological discoveries are made during construction. The Native American Graves Protection and Repatriation Act (NAGPRA) contains stipulations regarding the appropriate treatment and disposition of human burials, funerary, VILLAGE OF VENETIE, COOPERATIVE PROJECT AGREEMENT PAGE 4 PROJECT NO. AN 14-Z39 OCTOBER 2014 and associated items discovered on Federal lands or Indian Allotments. NAGPRA recognizes the inherent rights and claims of the Native people. Although NAGPRA often is inapplicable to ANTHC projects, ANTHC recognizes the inherent rights and claims of Tribes when human remains and associated items are uncovered through construction projects. Therefore, if construction for this project results in the discovery of ancient cultural items (i.e., Duman burials, associated items, and/or archaeological artifacts) ANTHC will notify the Native Villagc of Venetie Tribal Government and treat it as a consulting party. The Native Village of Venetie Tribal Government will help ensure compliance with the NHPA, NAGPRA, and ANTHC policy recognizing inherent rights and claims. The Tribal Council will: Identify and help locate any known or reported archaeological site, artifact, or ancient human remains prior to the beginning of construction to avoid unnecessary damage to sensitive resources. ANTHC will: • Delay construction in the vicinity of a discovery until procedures in conformance with 36 CFR Part 800, Subpart B are complete. • Identify and perform appropriate mitigation measures in conformance with Part 36 CFR 800, Subpart B. • Ensure an archaeologist has an opportunity to view and document any and all cultural items discovered during excavation if an adverse effect determination has been made. • Ensure that, if removal of ancient human remains is necessary, the archaeologist will remove the entire body and that there will be no further study, tests or photographs of the remains without the consent of the Village of Venetie (which will be provided in a separate agreement). + Contact the Village Public Safety Officer or State Troopers if a modern human burial is discovered and avoid any further disturbance of the scene until they have conducted any investigation that may be necessary. No police notification is needed for archaeological remains. • Ensure the inherent and legally protected rights of the Native Village of Venetie Tribal Government are respected, including their right to take possession of, control, and /or determine the appropriate disposition of any and all cultural items discovered during excavation on all but private lands. VILLAGE OF VENETIE, COOPERATIVE PROJECT AGREEMENT PAGE 5 PROJECT NO. AN 14-Z39 OCTOBER 2014 • Acknowledge that the inherent claims or rights of the Native Village of Venetie Tribal Government are not diminished by the fact that the land is under ownership by another party. • Ensure that, if a discovery is made on Federal lands, Indian Allotment lands, or lands not yet conveyed to the Village or Regional Corporation, employees, contractors and subcontractors involved in construction operations shall comply with the NAGPRA if appropriate. G. PARTICIPATION IN PROJECT ACTIVITIES The Village of Venetie will work collaboratively with ANTHC to meet grant requirements and complete the project scope of work as outlined in this CPA and AEA Grant No. 7071044, including the following: In order to meet requirements of the National Environmental Policy Act (NEPA), ANTHC uses the IHS Environmental Review (ER) process in accordance with the Department of Health and Human Services policies and procedures in General Administration Manual, Part 30, the Council on Environmental Quality regulations at 40 CFR 1500-1508 and with procedures published by IHS in the Federal Register, Vol.58, No.3, page 569. AVEC will be responsible for providing the ER documentation generated by ANTHC to the State and federal funding agencies to provide an Environmental Determination, as appropriate. H. OWNERSHIP OF PROJECT -INSTALLED EQUIPMENT The Village will assume ownership and responsibility for the operation and maintenance of all equipment installed within their buildings and property. APPENDIX Environmental Review Memorandum Attachment 1: General Provisions Attachment 2: AEA Renewable Energy Fund Grant Agreement No. 7071044 Appendix B Project Management and Reporting Requirements �A Nq 5 V G MEMORANDUM DATE: January 21, 2014 ALASKA NATIVE TRIBAL HEALTH CONSORTIUM Division of Environmental Health & Engineering 3900 Ambassador Street, Suite 301 Anchorage, Alaska 99508 � FROM: ANTHC Environmental Staff SUBJECT: Heat Recovery — Venetie, Alaska NEPA Environmental Review - CPA Project No. AN 14-Z39 TO: NEPA DETERMINATION Federal funding for this project requires an environmental review in accordance with the National Environmental Policy Act (NEPA), the National Historic Preservation Act (NHPA), the Endangered Species Act, the Clean Water Act, and other state and federal approvals. The Alaska Native Tribal Health Consortium (ANTHC) has considered all potential environmental concerns associated with the project, An Environmental Review has been conducted with respect to the proposed heat recovery system in Venetie, Alaska. FINDINGS The ANTHC uses the Indian Health Service (IHS) environmental review procedures for conducting environmental analyses of all health and sanitation facilities projects, as outlined in the Environmental Review Manual, issued in January 2007. Current IHS policy (Federal Register, Vol. 58, No. 3, January 6, 1993, pp. 569-572) allows for categorical exclusion of health and sanitation facility projects that do not have a significant impact on the environment, as determined by the attached "Environmental Review and Documentation." This environmental review finds that no additional environmental investigation is needed. Actions involving construction have been reviewed and no extraordinary or exceptional circumstances were found to exist. It is therefore recommended that the lead federal agency approve a detennination of eligibility for categorical exclusion from the requirement to conduct further envirorunental evaluation for this project. Venetie Heat Recovery System — Environmental Review Page 2 CPA Project No. AN 14-Z39 January 2014 BACKGROUND Venetic is located on the north side of the Chandalar River, 45 miles northwest of Fort Yukon. It lies at approximately 67.013890 North Latitude and-146.418610 West Longitude. (Sec. 10, T025N, R006E, Fairbanks Meridian.) Venetic is located in the Fairbanks Recording District. Known to early explorers as Old Robert's Village or Chandalar Village, Venetic was founded in 1895 by a man named Old Robert, who chose Venetic because of its plentiful fish and game. In 1899 the U.S. Geological Survey noted about 50 Natives living on the Chandalar; some were in small settlements of cabins about 7 miles above the mouth of the river, but most were in the mountainous part of the country beyond the Yukon Flats. They spent only the coldest winter months in cabins and the remainder of the year traveling for various food sources. In 1905 Venetic was a settlement of half a dozen cabins and 25 or 30 residents. The gold rush to the Chandalar region in 1906-07 brought a Iarge number of miners. A mining camp of nearly 40 cabins and attendant services was established at Caro, upriver from Venetic, and another store was located near the mouth of the East Fork. By 1910 the Chandalar was largely played out, and Caro almost completely abandoned. In 1943 the Venetic Indian Reservation was established, due to the combined efforts of the residents of Venetic, Arctic Village, Christian Village, and Robert's Fish Camp, who worked together to protect their land for subsistence use. At about this sank time, a school was established at Venetic, encouraging additional families to settle in the village. Eventually an airstrip, post office, and store were built. During the 1950s and 60s, the Ilse of seasonal camps declined, but the advent of the snowmachine enabled Venetic residents to renew use of areas which had traditionally been occupied seasonally. When the Alaska Native Claims Settlement Act (ANCSA) was passed in 1971, Venetic and Arctic Village opted for title to the 1.8 million acres of land in the former reservation, which they own as tenants in common through the Native Village of Venetic Tribal Government. SCOPE OF REVIEW This project will design and implement strategies identified in the 2013 Heat Recovery Feasibility Study in Venetic, Alaska to recover heat from the existing electrical power plant and utilize that heat to reduce the heat load in the newly constructed clinic. This project is expected to reduce the facility's fuel oil usage by 2,300 gallons annually CONDITIONAL APPROVAL/STIPULATIONS Given the environmental review performed by the ANTHC, the following conditional approvals are required for this project: Venetie Heat Recovery System — Environmental Review Page 3 CPA Project No. AN 14-Z39 January 2014 • Conduct a Section 106 Consultation and receive SHPO concurrence prior to construction activities. (# 17) • Re -vegetate disturbed soils. (#19) SUMMARY ANTHC has completed the environmental review for this project. ANTHC will revisit this environmental review to determine if potential environmental concerns have been addressed if the project scope changes. :. C) N c� cad ti O L M-4 a� %/ ai U U � > N as O a) CO Y co U s b on co >, c w a a 3 w c c°i �.oA� a o "a0 cr u co a r OU x U U cdd p cd oA n • In.co U cn z o �' U 0 b > Z 3cd y CO 4"' ram+ p bA cl o by w.fl U a " -e i 0 3 O ro 0. L � Q � N C) O cd cd �✓ C C w c o O, a� P� +r cd a o y td as Q s cd s e +;� c bi) c ��� 3aa E 3 �� o� Q�w 3 0 Q0 a > o o En a�i rs ^v a� . 2 c o NO � cn ❑ b a �, n a, v v, a � "a oA 0 a �, W lu v, x o 0 cci +� C z y b CO m co Cd o U .aQ CO aa^ a O aUi Q00 axi cd tw o 0 c 0 s0 v L � fn � Sr a a) y � O � � •U r" U � y� n ❑ N . .r O O w O7 C +"G•• �- '- 3 C 4 O ❑ Ll�. a to 4. O ° S L1 °o 3bj) s U o � c_ ° o C U U w° °' °' eii 0 oA 3 a°i a id w G V p U U v 0 aai U U ° ro 0 O u ao Ya }. D O o 0. 0 L co a) E U _Q y '+r G n{ A Gp ro a Ll ' F" Ems- U cd a z z Y Z � zapQQi a 0 z o w LV 0 3 ❑ ?� a w o L _ •� '� 3 o 0 U cd —O 0 cd 0 cdr••rn+ LS• a — N CZa n y cd cd Z co 3 v '" O C n .— a a ti v c > y 0 D O m cad a,roo cc Ua oo 00 v0 ba' o 'Uc[Uca 0 > cn O o 0. 0 0 y� 0� a ° y 0 O W N o cUd 0 0 o� .� aUJ n•.2 -0 °fl 0 C U o •b U CL A. a� G '^ C a, O U Cl+ ss o .a • bA Os .2 C7.0 c ^`' U o° a. 0 t� c� c. " µ H o. ° a) E cd a s a`ni > O O x ' a CO Y° 0 O O U a +n Q w rn �z° CO ° 3 w a �4 -- c�i �� v kr; t--� oc aU M O a� 'C O N bA '' w Cd a] cd O CD° 0 G° In 3 , a 0° i Ln o U D o a�'i w O co 3 ao U�� ° c a N c a o a rA Cd a, E c CO c awwi 3 0 cl o o•° vc ° v .0 cd 3 0 M b b ai o a�i a>i • 5 0 o 3 ^o w° G co 1•b U N p, - id •> a. Y N cd G 0 •� r. a••. Cd = My •D • G, . rl U U L Y — ' "i. � 0 (V > a�i y C .2 o o w y a L O — > Q."a o C 0 QrA Id U 3 = = = = a o a� 3 3 3 3� 3� '3 oA Q) ',= 0 �° o 0 0 0 0 3 '0 4 o, i O o o °�' o o' Cn b cd }, U a� Q. a a° a� o En Cd 0 Q. off 0. U N yLn 3 D ° o w a '> o Zo0 o c o o a ° U a o C o a o o5 cw c>'oao3��o w� N y U U U b U U U V O. U cyd ❑ y '[ cd mEl o N` 4C.4 F'• U F" f-� bTp E-' cU Fes-' U V C V ° a ° O O 'K O y O G O 0O ryn p C -O G7 .o0 to En w C� N fir, ° '- -- ` c bA CN w wo >Co n a$ ❑ o w U b 0 � a?.. c�V � y � 0 w a�i ca is cd ' ° >, � O a� y d = cd cd ❑ rn— CO > cd aU.+ U .U+ N Y O +U+ G .0 C L s.. � a� 3 „ . C o a� cc br co cd a �. o �. a� o a o cd ro a ❑ ;� ' d> w U N C cG N cad • r� U U o U U C ' O °° W '� .O cd o f bo 0 3 0 -� = x, C a> �.. C 7 C d ❑ c> cd re ca M ca cn c ,, " a U• 5 U. a� o bA > U w Cd bA N c3°3a' boUA C, c• O aCoUUNc UvU ;i. 00 0O 0 o o N 'on ocd a nc o o, '. i Q❑ .v o 0M 0`�d aoO C 'nN -0 cdy Q., Q, v9r7, W. cd O�. �'' o o Q. F" N 0— .0 cd : _.. .... 0. - o cocd NO O— = od Q❑ H 0 cd 9 FA H ucn o o `� Y 3 a 0?c co a3i cd .[ bn Cd C � N � It � INlz bn U O C •D o bA C a+ U O y y O 4, D O 0. c O a.+ _ cd p� 'N .D U "c] rZ O O ° 0 3❑ °L' c °�' o> 3 j : En � o � i i o� !1 cy,o � 3 0 o o '- a� a� a a� v b❑" o 0 En .0 v) Op bA cOCd-0 eU- U " O O cn o c Q. E x> j ca ❑ o Ob°.' E u u O a� 0U � E 0 D o al W -• .0r.. o CL tI'v77 u cd 0 o C r. r U C O ccb0 O Chy 0 , U3 N m O N V � � 77cu Ctl � �, E„_, � ,� Q • � � .0 O O 7 bl � C C•. ° V] Q. p Q) � ro .� ;' � ° ,� ❑ � � .� O.� w a3i a4,?d ='�'o =H cd s 0 cu a� � U N � .b w cn O Cd w s' i a7 C ❑ o m o ry v acn c cd -a_ L, aj ea o-0 ` Ivl c -4%1D 'CcdCn rn d.. O ❑ no 0 0 � �° �'� ro � � cad 8'00 -Clo N E U o� c u Efn. o o 04° o N > N O bn ti > co � N 3 y W [, a > N G cd b❑ r c 5 pA c � a :d 3 0 W o o= D.o coo � O b as p o ro ro N A 29 � b-0 9 A7 N s�0 U ry 11 a� bA > •C N 0 •0 3 0 m sn I c u 0 ate.. � 'x co 'O .O O N o CU 0 a vU, OL a� '• cd O b y G C cd Cd y rn F, u o E p O~ ^c Cd v > _ v U IQ ` b F" a>i 3 E= bA 00 z F- n u Z E- Z a Z Q z= c .5 Z Ei Q c� U °-' Z v b _ C-. 0 i v u �.2 . o ❑ go CC E N u L, �+ •Q p cn ..Q CL p ai C. Ei cd !1 stl U �, CO O. L Q O p L 0 0 U N •� C o�.0 O bAa] a�i vO a V) [C� pd C/3 s3 M CO Ul L. Cull CU A .V. a O 0r. 1~ ^' �" : j' n O y C O. O o4. c °'� °� Q b �3U-o v" > N ro {C� �O �ra� utd ° 0 a� .Ccc� `o o 0 cc_a -0 o❑ a0� 00 N a cnCoo 0 °noo. = Q. 'o bn oo ° 'n M .0 o0 XN c -p❑, c° o0 cy Cl) cn L. c-. � En S�-i C❑ iC cu C Ai^c �N•.I rn ° �30Ob `o 0 Ur 0 o M cl,puw b o00 _000'0 Noi�w�"oCdw�"on 5 E M. cd^" CV N N CV O N i4 O // a� v o 0 a L t1� O 0 U L' y .^ C + U Cd si U s w Q Q z z w"0L, o O � O 0.)o0 Ln o, U o n one o C. �oCJ � .��;.( a�i ❑ a� w C Q N 4E ° CO 0 N p, y o OA C+�, ¢ o C 0 -0 En U C •>, C) O O Cd rn O CC, 7 cd U N bA .�' cd +�•' N 3 s c p c +� w 4u) N O r: U y,,, O .n C,4 c� .D iot A O N N N one — "3 0 > cp `Jn w N 'In 7t — 0 Cn > X o > U CCf C O .7 • a3 O a COd N V cq N U O C •3 0 � � U oq x O c row Q U V w O vOi Xi x ¢ O e] N '0 .� y U co U O p O Cd GUi b � V N n 4J ❑ o'er.+ as U 3 as 0 U 4 o Cn bA T7 O 'C7 w c a, cz3 00,•a = a o a) .c a>�i C C .rA W at U Cd {a{:3.iy.� co En O co C p CL cd • w • Cn vl > ca w cd v > y o > CC U En C O N CS 'O E U N Q 3 U L: ° o co Cad a`ai 3 iv o -a 0 � 0 � Q -o° w 0 3 Q o 0 z 0 zw ���, o z � �.�Y ,0 o 0 ❑ o ° ai 0" ro o [= Q. U U� 0 0 -r 0 _ N U O '" s O a aO+ O O V) ^" O O nOi vi O > 3 n >3o E `'� a p a ,n a� O c� ay R U G u a� C ro w A, y� ro cz b a� U c� ;-o o cd > �' -0 c E! cu alcu G COv m � >. m m Q o N a O `. O A. w OR. w O O L aW N O a> `n 0 �O U.b .�L ar7 > N�"' • U i N G ��� 4' �`q M ro O L�"y Cad z o a�i C54 q .c E o N N 00 N z N U N G, co 0 o a o s Cf) c�i F ccd ai o N N '" n C cd � cry U z S n V] o c.., ^ coa 3 o o a ❑ Cd U O Ln co ,¢,.�� cd 3 o a) o. O rn o N p •9 N fV E : o 0 0 �; Ca U x U w cn o fl U r— 0 3 y w co y' cn ° U a o E cd �, x 0 E ya co � b ^' 3 E `° °c 000 cn 0 z w o L U p Ell ' N Ncqs c° -d 0. co .0 o cd E C° c •0 O _� d N V 7t _O co G cn o O c � n. 0 o N c U C s 4 H -o U +� = •• ❑'� 3 ° .x pa�i = Co c 9 U a°'A , d cc 2 dCd cn'� c °o c .5 a"i ao 3 U a'� d a c '' Ut: °� cn U odo (1) ° o z•�' o z o z o z o zU 'n m o Cd L. CIS Cd cd co �a�-0 10-v o cd� >,aA coo,. >, b 30 rn �+ cd "N� 0. •� Cl. 6.i vi '� Cd ,� ,� id vi sue, A. to U �' U U as • 0 U .� �d }' R. DA 0. � W +' U .b s.. Q• C p > E d bpD bA y y R. O p p p V pcd ° y u Cam. O°rn p +U+ cts 3 U CA O v Ca. N , p �] co 7 . � �{", '> 0.!". G o r a Ucc° cd0 [rid?' v cd .� TJ °n, cc '� E ° ' co � ❑ E ° ram, N s� p •U aA w O .� o° o o cn .� V y° �y o • 7 vpi 'tl G U p0... "a O m m v� R p p 0 a w 3 .m `° ;, '� $ a Q o �. L. N 7.. o> ayU.. N U N❑ �. O =. • N y •D N r. O b U� U' d` -' a' "" cts �.. d m ai ^d +� N N m O U N 3��8�.Sa�?dE���3°'���:° 3°3`�wacdU d _ � N f�l C1 M M ,Zr �10 w N O on Lol Li O CIS N z •L H U $. O 0 3' co E O 'D U Zcli ca U C N ±+ - G U C O a O O C O z cd L. co co o ° 03 Q o y co a LIU �l c D O N N N U >_ 0 ro C U p r, U 03 C � O � N 00 .� N m O , «f � O a`i c�i co O cz � N O ai 'b `� o 3 f Q ° m Ell � o p v o. Cd o .? �' cn a ° > — > 64 M ° ° >O a 0 obb > o a 2 ce c ` a>i N Y d co _ > o oCd o a�.15 c E N > ZQ Ems- z O N y> N C ,> O cd O % U i. -p w a�Nu L. oid y N L. y a p 3 p C N U a� a 3U����aw� �L U ++cl 00w ° cn U cn �, c. Q' 0E� = a a�i Q c= w 3 C7 own aUi � " > Q ° � 0 � � °En 3° rG L" ° N O L N O ° Cd Q❑ N a> o G o a ca C Q «f c v o co > i c Cd u w 3 U v 1..r3 J A i a-0- POWER PLANT F 0 } 1 WTP/WASHETERIA I a s o 00 1-1/2 ARCTIC o NEW CLINIC �� PIPE (BURIED) r1 0 <) O 0 L7 rl SITE PLAN 0 100' 200' ` Alaska Native VENETIE, AK Tribal Health Consortium Division of Environmental RECOVERED HEAT STUDY Health and Engineering SITE PLAN • w 7000 Akmh.eae rOrl,%lula. 701 • Menwey., Alwka.u.ae (WTI 7M3000 PRINTED DATE: 7/17/13 SHEET 2 OF 5