HomeMy WebLinkAboutBethel_AVCP-RHA_2012
Pre-Feasibility Assessment for
Integration of Wood-Fired Heating Systems
Final Report
July 24, 2012
AVCP-RHA Housing Authority Complex
Bethel, Alaska
Presented by
CTA Architects Engineers
Jesse Vigil, Nick Salmon & Nathan Ratz
Lars Construction Management Services
Rex Goolsby
For
AVCP
In partnership with:
Fairbanks Economic Development Corporation
Alaska Wood Energy Development Task Group
Funded by
Alaska Energy Authority and U.S. Forest Service
306 W. Railroad, Suite 104
Missoula, MT 59802
406.728.9522
www.ctagroup.com
CTA Project: FEDC_BETHEL
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers i
July 24, 2012
TABLE OF CONTENTS
1.0 Executive Summary ................................................................................................... 1
2.0 Introduction ............................................................................................................... 3
3.0 Existing Building Systems.......................................................................................... 3
4.0 Energy Use ............................................................................................................... 5
5.0 Biomass Boiler Size ................................................................................................... 6
6.0 Wood Fuel Use .......................................................................................................... 7
7.0 Boiler Plant Location and Site Access ....................................................................... 8
8.0 Integration with Existing Heating Systems ................................................................. 8
9.0 Air Quality Permits ..................................................................................................... 9
10.0 Wood Heating Options .............................................................................................. 9
11.0 Estimated Costs ........................................................................................................ 9
12.0 Economic Analysis Assumptions ............................................................................... 9
13.0 Results of Evaluation ............................................................................................... 10
14.0 Project Funding ....................................................................................................... 10
15.0 Summary ................................................................................................................. 11
16.0 Recommended Action ............................................................................................. 11
Appendixes
Appendix A: Preliminary Estimates of Probable Cost ................................................ 1 pages
Appendix B: Cash Flow Analysis ............................................................................... 1 pages
Appendix C: Site Plan ................................................................................................. 2 page
Appendix D: Air Quality Report ................................................................................. 9 pages
Appendix E: Wood Fired Heating Technologies ........................................................ 3 pages
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 1 of 11
July 24, 2012
1.0 Executive Summary
The following assessment was commissioned to determine the preliminary technical and
economic feasibility of integrating a wood fired heating system at the AVCP-Housing
Authority Complex. The review was conducted on the assumption that the complex would
be served by a district heating loop.
The following tables summarize the current fuel use and the potential wood fuel use:
Table 1.1 - Fuel Use Summary
Fuel Avg. Use Average Average
Facility Name Type (Gallons) Annual Cost Cost/Gal.
Complex Fuel Oil 60,000 $377,400 $6.29
Estimate for
New
Regional
Headquarters
Office / New
Maintenance
Facility Fuel Oil 7,766 $48,848.14 $6.29
Total Fuel Oil 67,766 $426,248.14 $6.29
Table 1.2 - Annual Wood Fuel Use Summary
Chipped/
Fuel Cord Wood Ground
Oil Wood Pellets Wood
(Gallons) (Cords) (Tons) (Tons)
Current Campus 60,000 524.4 478.0 781.7
Expanded
Campus 7,766 67.9 61.9 101.2
Total 67,766 592.2 539.9 882.9
Note: Wood fuel use assumes offsetting 85% of the current energy use.
Based on the available wood fuel and the estimated biomass boiler size, only a pellet
option will be evaluated.
Pellet Wood Boiler Option
B.1: Central plant serving all buildings in the AVCP Complex.
The table on the following page summarizes the economic evaluation for this option:
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 2 of 11
July 24, 2012
Table 1.3 - Economic Evaluation Summary
Bethel AVCP RHA Biomass Heating System
Year 1 NPV NPV
20
Yr
30
Yr
Project Operating 30 yr 20 yr B/C B/C ACF ACF YR
Cost Savings at 3% at 3% Ratio Ratio YR 20 YR 30 ACF=PC
B.1 $3,400,000 $103,264 $6,570,870 $3,467,771 1.02 1.93 $5,016,876 $11,689,874 17
The AVCP-RHA campus appears to be a good candidate for the use of a district wood
biomass heating system. With the current economic assumptions and the current fuel use
the wood pellet boiler option has a B/C ratio of 1.02, which indicates an economically
favorable project.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 3 of 11
July 24, 2012
2.0 Introduction
The following assessment was commissioned to determine the preliminary technical and
economic feasibility of integrating a wood fired heating system at the AVCP-Housing
Authority Complex. The review was conducted on the assumption that the complex would
be served by a district heating loop.
3.0 Existing Building Systems
The AVCP RHA campus that is located on Ptarmigan Road has 8 housing buildings, 2
office buildings, and 3 warehouses / maintenance facilities. The current heating system
for the campus is a combination of heat loops and standalone systems. The table below
indicates the current heating systems outputs and condition.
Table 3.1 - Existing Heating System Summary
Heat BTU/hr Condition
Building System Output
Lulu Heron
Assisted
Living Facility
Boiler 1 764,000 Good
Boiler 2 764,000 Good
DHW 199,000 Good
Office /
Bunkhouse
(District
System)
Boiler 1 145,000 Good
Boiler 2 145,000 Good
Building A-E
(District
System)
Boiler 1 786,000 Fair
Boiler 2 786,000 Fair
12-Unit
Housing
Addition
Boiler 1 561,000 Good
Boiler 2 561,000 Good
DHW 1 315,000 Good
DHW 2 315,000 Good
DHW 3 315,000 Good
Warehouse 1 Unit Heater 185,000 Good
Warehouse 2 Unit Heater 185,000 Good
New
Regional
Headquarters
Office
Boiler 1 1,023,000
Excellent
(New)
Boiler 2 1,023,000
Excellent
(New)
Lulu Heron Assisted Living Facility
The Lulu Heron Assisted Living Facility is a wood framed building constructed in 1998.
The single story facility consists of approximately 15,480 square feet. The space consists
of 16-unit housing for elders and people with disabilities. In addition to the residential units
there are also support spaces including steam rooms, laundry facilities, and community
gathering rooms.
Domestic hot water is provided by one fuel oil water heater rated at 199,000 BTUH input
with 67 gallons of storage.
Office / Bunkhouse (District Heat Loop)
The Office and Bunkhouse facility consists of two separate wood framed buildings
constructed in 2004. The Office building is approximately 3,160 square feet and the
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 4 of 11
July 24, 2012
Bunkhouse building is approximately 1,680 square feet. The combined facility is heated
by two 145,000 Btu/hr output hot water boilers located in the Office building mechanical
room. The heating water is then piped via utilidor to the Bunkhouse building for
distribution. Domestic hot water is provided by an indirect-fired Amtrol Boilermate water
heater with a 41 gallon storage capacity.
Buildings A-E (District Heat Loop)
The Building A-E facility consists of 4 apartment buildings and one office building
constructed in 1987-1988. Building A and B are each approximately 5,220 square feet
and contain 4 apartment units each. Buildings C and D are approximately 6,700 square
feet and contain 6 apartment units each. Building E is approximately 9,760 square feet
and currently contains administrative offices. When the New Regional Headquarters
Office is completed the office will be renovated into a 30-bed dormitory for students
attending Yuut Yaqunviat Plot Training School and AVCP Regional Aircraft Maintenance
School.
The Building A-E facility is heated by two 786,000 Btu/hr output hot water boilers that are
located in the Building E mechanical room. Two existing utilidors extend from Building E,
one going to Building A and C, the other to Building B and D. Domestic hot water is
provided by an indirect fired water heater with a 140 gallon storage capacity.
12-Unit Housing Addition
The 12-Unit Housing Addition is a two story wood framed buildings constructed in 1998.
The facility is approximately 12,500 square feet and is heated by two 561,000 Btu/hr
output hot water boilers. Domestic hot water is provided by three fuel oil water heaters
rated at 315,000 input each. There currently is a laundry facility located at one end of the
building. The intent is that this will be moved to the New Regional Headquarters Office
when it is completed.
Warehouse 1
The warehouse is a metal building constructed in the mid-1990s. The facility is
approximately 4,500 square feet and is heated by a 185,000 Btu/hr output fuel oil unit
heater. There is no domestic hot water provided to the space.
Maintenance Facility
The warehouse is a metal building constructed in the mid-1990s. The facility is
approximately 4,500 square feet and is heated by a 185,000 Btu/hr output fuel oil unit
heater. Domestic hot water is provided by an electric water heaters rated at 4.5 KW input
with a 30 gallon storage capacity.
New Regional Headquarters Office / New Maintenance Facility
The facilities are still under construction; however it is assumed they will be complete by
the summer of 2012. The New Regional Headquarters Office is a two story, metal framed
building containing approximately 34,000 square feet and is heated by two 1,023,000
Btu/hr output hot water boilers on the district heating system.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 5 of 11
July 24, 2012
4.0 Energy Use
The AVCP-RHA purchases fuel oil in bulk and does not track individual building use. Also
there are 2 additional buildings that are still under construction that fuel data was not
available for. The following table summarizes the campus use and the estimated fuel use
for the new buildings:
Table 4.1 - Fuel Use Summary
Fuel Avg. Use Average Average
Facility Name Type (Gallons) Annual Cost Cost/Gal.
Complex Fuel Oil 60,000 $377,400 $6.29
Estimate for
New
Regional
Headquarters
Office / New
Maintenance
Facility Fuel Oil 7,766 $48,848.14 $6.29
Total Fuel Oil 67,766 $426,248.14 $6.29
Electrical energy consumption will increase with the installation of the wood fired boiler
system because of the power needed for the biomass boiler components such as draft
fans and the additional pumps needed to integrate into the existing heating systems. The
cash flow analysis accounts for the additional electrical energy consumption and reduces
the annual savings accordingly.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 6 of 11
July 24, 2012
5.0 Biomass Boiler Size
The following table summarized the connected load of the heating equipment:
Table 5.1 - Connected Boiler Load Summary
Likely
Peak System
Output Load Peak
MBH Factor MBH
Lulu Heron Assisted Living
Facility Boiler 1 Fuel Oil 764 0.66 504
Boiler 2 Fuel Oil 764 0.66 504
DHW Fuel Oil 199 0.66 131
Total 1140
Office / Bunkhouse Boiler 1 Fuel Oil 145 1.00 145
Boiler 2 Fuel Oil 145 0.66 96
Total 241
Bldg A-E Boiler 1 Fuel Oil 786 0.67 527
District System Boiler 2 Fuel Oil 786 0.67 527
Total 1053
12-Unit Housing Addition Boiler 1 Fuel Oil 561 1.00 561
Boiler 2 Fuel Oil 561 0.66 370
DWH Fuel Oil 315 1.00 315
DWH Fuel Oil 315 1.00 315
DWH Fuel Oil 315 1.00 315
Total 1246
Warehouse 1 Boiler Fuel Oil 185 1.00 185
Maintenance Facility Boiler
Fuel Oil 185 1.00 185
New Regional Headquarters Boiler Fuel Oil 1023 0.60 614
Boiler Fuel Oil 1023 0.60 614
Total 1228
Total Of All Buildings 8072 5182
Typically a wood heating system is sized to meet approximately 85% of the typical annual
heating energy use of the building. The existing heating systems would be used for the
other 15% of the time during peak heating conditions, during times when the biomass
heating system is down for servicing, and during swing months when only a few hours of
heating each day are required. Recent energy models have found that a boiler sized at
50% to 60% of the building peak load will typically accommodate 85% of the boiler run
hours.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 7 of 11
July 24, 2012
Table 5.2 - Proposed Biomass Boiler Size
Likely Biomass
System Biomass Boiler
Peak Boiler Size
MBH Factor MBH
Lulu Heron Assisted Living Facility 1140 0.6 684
Office / Bunkhouse 145 0.6 87
District Heat Loop 1053 0.6 632
12-Unit Housing Addition 1246 0.6 748
Warehouse 1 185 0.6 111
Maintenance Facility 185 0.6 111
New Regional Headquarters 1228 0.6 737
Campus District Heating System 5182 0.6 3109
6.0 Wood Fuel Use
The types of wood fuel available in the area include cord wood and wood pellets. The
estimated amount of wood fuel needed of each wood fuel type for each building was
calculated and is listed below:
Table 6.1 - Annual Wood Fuel Use Summary
Chipped/
Fuel Cord Wood Ground
Oil Wood Pellets Wood
(Gallons) (Cords) (Tons) (Tons)
Current Campus 60,000 524.4 478.0 781.7
Expanded
Campus 7,766 67.9 61.9 101.2
Total 67,766 592.2 539.9 882.9
Note: Wood fuel use assumes offsetting 85% of the current energy use.
The amount of wood fuel shown in the table is for offsetting 85% of the total fuel oil use.
The moisture content of the wood fuels and the overall wood burning system efficiencies
were accounted for in these calculations. The existing fuel oil boilers were assumed to be
80% efficient. Cord wood was assumed to be 20% moisture content (MC) with a system
efficiency of 65%. Wood pellets were assumed to be 7% MC with a system efficiency of
70%.
There is no wood harvesting or wood products industry in the area. Cord wood comes
from up river. Since there is a large enough potential demand of pellets, it is viable to
purchase pellets from plants in British Columbia, Washington, or Oregon and barge them
up to Bethel.
The unit fuel costs for fuel oil and the different fuel types were calculated and equalized to
dollars per million Btu ($/MMBtu) to allow for direct comparison. The Delivered $/MMBtu
is the cost of the fuel based on what is actually delivered to the heating system, which
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 8 of 11
July 24, 2012
includes all the inefficiencies of the different systems. The Gross $/MMBtu is the cost of
the fuel based on raw fuel, or the higher heating value and does not account for any
system inefficiencies. The following table summarizes the equalized fuel costs at different
fuel unit costs:
Table 6.2 - Unit Fuel Costs Equalized to $/MMBtu
Net
Gross System System
Delivered Gross
Fuel Type Units Btu/unit Efficiency Btu/unit $/unit $/MMBtu $/MMBtu
Fuel Oil gal 134500 0.8 107600 $5.50 $51.12 $40.89
$6.29 $58.46 $46.77
$7.00 $65.06 $52.04
Cord
Wood cords 16173800 0.65 10512970 $550.00 $52.32 $34.01
$600.00 $57.07 $37.10
$650.00 $61.83 $40.19
Pellets tons 16400000 0.7 11480000 $400.00 $34.84 $24.39
$460.00 $40.07 $28.05
$520.00 $45.30 $31.71
Chips tons 10800000 0.65 7020000 N/A N/A N/A
7.0 Boiler Plant Location and Site Access
None of the existing boiler rooms are large enough to fit a new biomass boiler so a new
stand alone boiler plant would be required. The best location for a plant would be an
addition to the new maintenance facility building. During the master planning of the
campus by Larsen Consulting Group the future addition location has been identified and
planned.
Any type of biomass boiler system will require access by delivery vehicles. For pellet and
chip boiler systems this would require an area for a trailer to turn around. The proposed
plant location would allow for good access.
8.0 Integration with Existing Heating Systems
Integration of a wood fired heating system varies from facility to facility. The 12 Unit
Apartment, Buildings A through E, New Office Building, Lulu Assisted Living Center,
Bunkhouse, and Office space would require the installation of new heating hot water
supply and return pipes to connect to the existing boiler supply and return pipes.
The Maintenance facility and Warehouse 2 would require the installation of new hot water
unit heaters.
The field visit confirmed the location of each boiler room and heating unit location in order
to identify an approximate point of connection from a district heating loop to each existing
building. Connections would typically be achieved with arctic pipe extended to the face of
each building, and extended up the exterior surface of the building in order to penetrate
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 9 of 11
July 24, 2012
exterior wall into the boiler room or building. Once the heating water supply and return
piping enters the existing boiler room it would be connected to existing supply and return
lines in appropriate locations in order to utilize existing pumping systems within each
building.
9.0 Air Quality Permits
Resource System Group (RSG) has completed and air quality feasibility study for three
new wood boilers in Bethel, Alaska. Bethel has favorable meteorology for dispersion of
emissions. Prevailing winds would likely blow emissions towards the southeast. In
addition, the proposed wood boilers will be small emission sources, whose sizes preclude
them from state permitting requirements. Therefore, we do not suggest advanced
emission control such as an ESP or baghouse. However, other design criteria have been
suggested to minimize emissions and maximize dispersion. These projects may be subject
to federal requirements.
10.0 Wood Heating Options
The technologies available to produce heating energy from wood based biomass are
varied in their approach, but largely can be separated into three types of heating plants:
cord wood, wood pellet and wood chip/ground wood fueled. See Appendix E for these
summaries.
Based on the available wood fuel and the estimated biomass boiler size, only a pellet
option will be evaluated.
Pellet Wood Boiler Option
B.1: Central plant serving all buildings in the AVCP Complex.
The wood pellet boiler option assumes a freestanding boiler building with adjacent free
standing pellet silo.
11.0 Estimated Costs
The total project costs are at a preliminary design level and are based on RS Means and
recent biomass project bid data. The estimates are shown in the appendix. These costs
are conservative and if a deeper level feasibility analysis is undertaken and/or further
design occurs, the costs may be able to be reduced.
12.0 Economic Analysis Assumptions
The cash flow analysis assumes fuel oil at $6.29/gal, electricity at $0.50/kwh, cord wood
delivered at $600/cord, and wood pellets delivered at $460/ton. The fuel oil, electricity,
and cord wood costs are based on the costs reported by the facility. Pellet costs were
obtained from an engineering study investigating using pellet boilers at the AVCP Housing
Authority Complex.
It is assumed that the wood boiler would supplant 85% of the estimated heating use, and
the existing heating systems would heat the remaining 15%. Each option assumes the
total project can be funded with grants and non obligated capital money. The following
inflation rates were used: O&M - 2%, Fossil Fuel – 5%, Wood Fuel – 3%, Discount Rate
for NPV calculation – 3%. The fossil fuel inflation rate is based on the DOE EIA website.
DOE is projecting a slight plateau with a long term inflation of approximately 5%. As a
point of comparison, oil prices have increased at an annual rate of over 8% since 2001.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 10 of 11
July 24, 2012
The analysis also accounts for additional electrical energy required for the wood fired
boiler system as well as the system pumps to distribute heating hot water to the buildings.
Wood fired boiler systems also will require more maintenance, and these additional
maintenance costs are also factored into the analysis.
13.0 Results of Evaluation
The following table summarizes the economic evaluation for each option:
Table 13.1 - Economic Evaluation Summary
Bethel AVCP RHA Biomass Heating System
Year 1 NPV NPV
20
Yr
30
Yr
Project Operating 30 yr 20 yr B/C B/C ACF ACF YR
Cost Savings at 3% at 3% Ratio Ratio YR 20 YR 30 ACF=PC
B.1 $3,400,000 $103,264 $6,570,870 $3,467,771 1.02 1.93 $5,016,876 $11,689,874 17
The benefit to cost ratio (B/C) takes the net present value (NPV) of the net energy savings
and divides it by the construction cost of the project. A B/C ratio greater than or equal to
1.0 indicates an economically advantageous project.
Accumulated cash flow (ACF) is another evaluation measure that is calculated in this
report and is similar to simple payback with the exception that accumulated cash flow
takes the cost of financing and fuel escalation into account. For many building owners,
having the accumulated cash flow equal the project cost within 15 years is considered
necessary for implementation. If the accumulated cash flow equals project cost in 20
years or more, that indicates a challenged project. Positive accumulated cash flow should
also be considered an avoided cost as opposed to a pure savings.
14.0 Project Funding
AVCP-RHA may pursue a biomass project grant from the Alaska Energy Authority.
AVCP-RHA could also enter into a performance contract for the project. Companies such
as Siemens, McKinstry, Johnson Controls and Chevron have expressed an interest in
participating in funding projects of all sizes throughout Alaska. This allows the facility
owner to pay for the project entirely from the guaranteed energy savings, and to minimize
the project funds required to initiate the project. The scope of the project may be
expanded to include additional energy conservation measures such as roof and wall
insulation and upgrading mechanical systems.
Pre-Feasibility Assessment for AVCP-RHA
Integration of Wood-Fired Heating Systems Bethel, Alaska
CTA Architects Engineers Page 11 of 11
July 24, 2012
15.0 Summary
The AVCP-RHA campus appears to be a good candidate for the use of a district wood
biomass heating system. With the current economic assumptions and the current fuel use
the wood pellet boiler option has a B/C ratio of 1.02, which indicates an economically
favorable project.
16.0 Recommended Actions
Most grant programs will likely require a full feasibility assessment. A full assessment
would provide more detail on the air quality issues, wood fuel resources, and a schematic
design of the boiler systems and system integration to obtain more accurate costs. It
would be also in the best interest of AVCP to evaluate if a wood biomass infrastructure
could be developed to help lower the overall cost of the wood fuel.
APPENDIX A
Preliminary Estimates of Probable Cost
Preliminary Estimates of Probable Cost
AVCP-RHA Biomass Heating Options
Bethel, AK
Option B.1 - AVCP Housing Campus
Biomass Boiler Building:$360,000
Wood Heating, Wood Handling System, & Pellet Silo: $470,000
Stack/Air Pollution Control Device:$100,000
Mechanical/Electrical within Boiler Building: $375,000
Underground Piping $275,000
12 Unit Apartment Integration $65,000
A to E Buildings Integration $72,000
New Office Building Integration $50,000
Bunkhouse Integration $37,000
Office Integration $37,000
Lulu Assisted Living Center Integation $42,250
Maintenance Facility Integration $47,000
Warehouse 2 Integration $47,000
Subtotal:$1,977,250
30% Remote Factor $593,175
Subtotal:$2,570,425
Design Fees, Building Permit, Miscellaneous Expenses 15%: $385,564
Subtotal:$2,955,989
15% Contingency:$443,398
Total Project Costs 3,399,387$
APPENDIX B
Cash Flow Analysis
AVCP: RHA Campus SystemOption B.1Bethel, AlaskaWood Pellet Boiler Date: July 24, 2012 Analyst: CTA Architects Engineers - Jesse Vigil & Nathan Ratz EXISTING CONDITIONSRHATotalExisting Fuel Type:Fuel Oil Fuel Oil Fuel Oil Fuel OilFuel Units:gal gal gal galCurrent Fuel Unit Cost:$6.29 $6.29 $6.29 $6.29 Estimated Average Annual Fuel Usage:67,76667,766Annual Heating Costs:$426,248 $0 $0 $0 $426,248ENERGY CONVERSION (to 1,000,000 Btu; or 1 dkt)Fuel Heating Value (Btu/unit of fuel):134500 134500 134500 134500Current Annual Fuel Volume (Btu):9,114,527,000 0 0 0Assumed efficiency of existing heating system (%):80% 80% 80% 80% Net Annual Energy Produced (Btu):7,291,621,600 0 0 0 7,291,621,600WOOD FUEL COSTWood Pellets$/ton: $460.00Assumed efficiency of wood heating system (%): 70% PROJECTED WOOD FUEL USAGEEstimated Btu content of wood fuel (Btu/lb) - Assumed 7% MC 8200 Tons of wood fuel to supplant net equivalent of 100% annual heating load.635Tons of wood fuel to supplant net equivalent of 85% annual heating load.54025 ton chip van loads to supplant net equivalent of 85% annual heating load.22 Project Capital Cost-$3,400,000 Project Financing InformationPercent Financed0.0%Est. Pwr Use 15000 kWh Type Hr/Wk Wk/Yr Total Hr Wage/Hr TotalAmount Financed$0 Elec Rate $0.500 /kWh Biomass System 2.0 40 80 $20.00 $1,600Amount of Grants$3,400,000 Other 0.0 40 0 $20.00 $01st 2 Year Learning 2.0 40 80 $20.00 $1,600Interest Rate5.00%Term10Annual Finance Cost (years)$0 32.9 years Net Benefit B/C Ratio$6,570,870 $3,170,870 1.93$3,467,771 $67,7711.02Year Accumulated Cash Flow > 0#N/AYear Accumulated Cash Flow > Project Capital Cost17Inflation FactorsO&M Inflation Rate2.0%Fossil Fuel Inflation Rate5.0%Wood Fuel Inflation Rate3.0%Electricity Inflation Rate5.0%Discount Rate for Net Present Value Calculation 3.0%Year Year Year Year Year Year Year Year Year Year Year Year Year Year Year Year Year YearCash flow Descriptions Unit Costs HeatingSource ProportionAnnual Heating Source VolumesHeating Units 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 20 25 30Existing Heating System Operating CostsDisplaced heating costs $6.29 67766 gal $426,248 $447,561 $469,939 $493,436 $518,107 $544,013 $571,213 $599,774 $629,763 $661,251 $694,313 $729,029 $765,480 $803,754 $843,942 $1,077,108 $1,374,693$1,754,495Displaced heating costs $6.290 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Displaced heating costs $6.290 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Displaced heating costs $6.290 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Biomass System Operating CostsWood Fuel ($/ton, delivered to boiler site)$460.00 85% 540 tons $248,347 $255,797 $263,471 $271,376 $279,517 $287,902 $296,539 $305,436 $314,599 $324,037 $333,758 $343,770 $354,083 $364,706 $375,647 $435,478 $504,838$585,246Small load existing fuel$6.29 15% 10165 gal $63,937 $67,134 $70,491 $74,015 $77,716$81,602 $85,682 $89,966 $94,464 $99,188 $104,147 $109,354$114,822 $120,563 $126,591 $161,566 $206,204 $263,174Small load existing fuel$6.29 15% 0 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Small load existing fuel$6.29 15% 0 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Small load existing fuel$6.29 15% 0 gal $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0 $0Additional Operation and Maintenance Costs$1,600 $1,632 $1,665 $1,698 $1,732 $1,767 $1,802 $1,838 $1,875 $1,912 $1,950 $1,989 $2,029 $2,070 $2,111 $2,331 $2,573$2,841Additional Operation and Maintenance Costs First 2 years$1,600 $1,632Additional Electrical Cost $0.500$7,500 $7,875 $8,269 $8,682 $9,116 $9,572 $10,051 $10,553 $11,081 $11,635 $12,217 $12,828 $13,469 $14,142 $14,849 $18,952 $24,188 $30,871Annual Operating Cost Savings$103,264$113,490$126,043$137,665$150,026$163,170$177,139$191,981$207,744$224,479$242,242$261,087$281,077$302,273$324,743$458,781$636,889$872,362Financed Project Costs - Principal and Interest0000000000 Displaced System Replacement Costs (year one only)0Net Annual Cash Flow103,264 113,490 126,043 137,665 150,026 163,170 177,139 191,981 207,744 224,479 242,242 261,087 281,077 302,273 324,743 458,781 636,889 872,362Accumulated Cash Flow103,264 216,754 342,797 480,461 630,488 793,657 970,797 1,162,778 1,370,522 1,595,002 1,837,243 2,098,330 2,379,407 2,681,680 3,006,423 5,016,876 7,825,065 11,689,874Additional Power UseAdditional MaintenanceSimple Payback: Total Project Cost/Year One Operating Cost Savings:Net Present Value (30 year analysis):Net Present Value (20 year analysis):
APPENDIX C
Site Plan
AVCP HOUSINGLOMACK BUILDINGTUGKAR BUILDING1600'800'400'0SCALE: 1:800MISSOULA, MT(406)728-9522Fax (406)728-8287Date®BIOMASS PRE-FEASIBILITY ASSESSMENTBETHEL, ALASKABETHEL OVERVIEWSSFNHR07/24/2012FEDCJ:BethelNORTHREF.SITE PLAN
OFFICE BUILDINGCURRENTLY UNDERCONSTRUCTIONAVCP HOUSING10'-0"180'-0"65'-0"175'-0"15'-0"PROPOSEDBOILER PLANT15'-0"92'-0"135'-0"130'-0"142'-0"25'-0"55'-0"150'-0"100'-0"200'100'50'0SCALE: 1:100MISSOULA, MT(406)728-9522Fax (406)728-8287Date®BIOMASS PRE-FEASIBILITY ASSESSMENTBETHEL, ALASKAAVCP HOUSINGSSFNHR07/24/2012FEDCJ:BethelSITE PLANNORTHREF.LEGENDPIPE ROUTINGBOILER ROOM
APPENDIX D
Air Quality Report
55 Railroad Row White River Junction, Vermont 05001
TEL 802.295.4999 FAX 802.295.1006 www.rsginc.com
INTRODUCTION
At your request, RSG has conducted an air quality feasibility study for three biomass energy
installations in Bethel. Bethel is located in southwest Alaska at the head of the Wood River and
has a population of 6,000 people. The following equipment is proposed:
A 250,000 Btu/hr (heat output) cord wood boiler at the Tukgar Building.
A 3,100,000 Btu/hr (heat output) pellet boiler at the AVCP Housing Complex.
A 250,000 Btu/hr (heat output) cord wood boiler at the Lomack Building.
STUDY AREA
A USGS map of the study area is provided in Figure 1 below. As shown, the area is flat with
much low‐lying areas along the Kuskokwin River. Relative to other sites in Alaska, the area is
densely populated. Our review of the area did not reveal any significant emission sources or
ambient air quality issues.
To: Nick Salmon
From: John Hinckley
Subject: Bethel Cluster Feasibility Study
Date: 24 July 2012
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 2
Figure 1: USGS Map Illustrating the Study Area
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 3
Figure 1 shows CTA Architects’ plan of the location of the proposed biomass facility at the
Tukgar Building and the surrounding buildings. As shown, two locations are being considered
for the proposed biomass equipment. The site is relatively flat and relatively densely populated
with one to two story tall buildings. The precise stack location and dimensions, and the biomass
equipment specifications have not been determined.
Figure 1: Overview of Tukgar Site
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 4
Figure 2 shows CTA Architects’ plan of the proposed biomass facility at the AVCP Building and
the surrounding buildings. Most of the buildings are approximately one to two stories tall. A
stand‐alone biomass facility is planned on the southeast corner of the site. The remote location
of the facility will provide a dispersion buffer between the stack and the office buildings.
Figure 2: Overview of AVCP Housing Site
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 5
Figure 3 shows CTA Architects’ plan of the proposed biomass facility at the Lomack Building
and the surrounding buildings. Most of the buildings are approximately one to two stories tall.
An addition is planned for the northern side of the building.
Figure 3: Overview of Lomack Building Building Site
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 6
METEOROLOGY
Meteorological data from Bethel, AK, was reviewed to develop an understanding of the weather
conditions. As shown, there is a relatively low percentage of “calms” or times when the wind is
not blowing.1 This data indicates only 1% of the year when calm winds occur, which suggests
there will be minimal time periods when thermal inversions and therefore poor emission
dispersion conditions can occur.
Figure 4: Wind Speed Data from Bethel, AK
1 See: http://climate.gi.alaska.edu/Climate/Wind/Direction/Bethel/BET.html
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 7
Figure 5 is a wind rose developed from wind speed and direction data collected in Bethel.1 This
shows prevailing winds are from the northeast (NNE and NE), meaning, they frequently blow
towards the southeast. Average wind speeds are up to 12 miles per hour in those directions.
This suggests emissions would typically be blown towards the southeast.
Figure 5: Wind Rose Showing Wind Speed and Direction
1 See: http://climate.gi.alaska.edu/Climate/Wind/Direction/Bethel/BET.html
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 8
DESIGN & OPERATION RECOMMENDATIONS
The following are suggested for designing this project:
Burn natural wood, whose characteristics (moisture content, bark content, species,
geometry) ‐ result in optimal combustion in the equipment selected for the project.
Do not install a rain cap above the stack. Rain caps obstruct vertical airflow and reduce
dispersion of emissions.
Construct the stack to at least 1.5 times the height of the tallest roofline of the adjacent
building. Hence, a 20 foot roofline would result in a minimum 30 foot stack.
Operate and maintain the boiler according to manufacturer’s recommendations.
Perform a tune‐up at least every other year as per manufacturer’s recommendations
and EPA guidance (see below for more discussion of EPA requirements)
Conduct regular observations of stack emissions. If emissions are not characteristic of
good boiler operation, make corrective actions.
These design and operation recommendations are based on the assumption that state‐of‐the‐
art combustion equipment is installed.
STATE AND FEDERAL PERMIT REQUIREMENTS
This project will not require an air pollution control permit from the Alaska Department of
Environmental Quality given the boilers’ relatively small size and corresponding quantity of
emissions. However, this project will be subject to new proposed requirements in the federal
“Area Source Rule” (40 CFR 63 JJJJJJ). A federal permit is not needed. However, there are various
record keeping, reporting and operation and maintenance requirements which must be
performed to demonstrate compliance with the requirements in the Area Source Rule. The
proposed changes have not been finalized. Until that time, the following requirements are
applicable:
Submit initial notification form to EPA within 120 days of startup.
Complete biennial tune ups per EPA method.
Submit tune‐up forms to EPA.
Please note the following:
Oil and coal fired boilers are also subject to this rule.
Gas fired boilers are not subject to this rule.
More requirements are applicable to boilers equal to or greater than 10 MMBtu/hr heat
input. These requirements typically warrant advanced emission controls, such as a
baghouse or an electrostatic precipitator (ESP).
The compliance guidance documents and compliance forms can be obtained on the following
EPA web page: http://www.epa.gov/boilercompliance/
Bethel Air Quality Feasibility Study Resource Systems Group, Inc.
24 July 2012 page 9
SUMMARY
RSG has completed an air quality feasibility study for three new wood boilers in Bethel, Alaska.
The boilers are not subject to state permitting requirements, but are subject to federal
requirements. Design criteria have been suggested to minimize emissions and maximize
dispersion. We do not suggest advanced emission controls (ESP, baghouse) for the following
reasons:
1. Bethel has favorable meteorology for dispersion of emissions.
2. The wood boilers will be relatively small emission sources.
3. There are no applicable federal or state emission limits.
4. The Bethel area is relatively rural with no significant emission sources.
Given the prevailing winds, we recommend wherever possible to construct boiler stacks on the
south to southwest sides of buildings.
While not mandatory, we recommend exploring the possibility of a cyclone or multi‐cyclone
technology for control of fly ash and larger particulate emissions. We also recommend
developing a compliance plan for the aforementioned federal requirements.
Please contact me if you have any comments or questions.
APPENDIX E
Wood Fired Heating Technologies
WOOD FIRED HEATING TECHNOLOGIES
CTA has developed wood-fired heating system projects using cord wood, wood pellet
and wood chips as the primary feedstock. A summary of each system type with the
benefits and disadvantages is noted below.
Cord Wood
Cord wood systems are hand-stoked wood boilers with a limited heat output of 150,000-
200,000 British Thermal Units per hour (Btu/hour). Cord wood systems are typically
linked to a thermal storage tank in order to optimize the efficiency of the system and
reduce the frequency of stoking. Cord wood boiler systems are also typically linked to
existing heat distribution systems via a heat exchanger. Product data from Garn, HS
Tarm and KOB identify outputs of 150,000-196,000 Btu/hr based upon burning eastern
hardwoods and stoking the boiler on an hourly basis. The cost and practicality of stoking
a wood boiler on an hourly basis has led most operators of cord wood systems to
integrate an adjacent thermal storage tank, acting similar to a battery, storing heat for
later use. The thermal storage tank allows the wood boiler to be stoked to a high fire
mode 3 times per day while storing heat for distribution between stoking. Cord wood
boilers require each piece of wood to be hand fed into the firebox, hand raking of the
grates and hand removal of ash. Ash is typically cooled in a barrel before being stock
piled and later broadcast as fertilizer.
Cordwood boilers are manufactured by a number of European manufacturers and an
American manufacturer with low emissions. These manufacturers currently do not
fabricate equipment with ASME (American Society of Mechanical Engineers)
certifications. When these non ASME boilers are installed in the United States,
atmospheric boilers rather than pressurized boilers are utilized. Atmospheric boilers
require more frequent maintenance of the boiler chemicals.
Emissions from cord wood systems are typically as follows:
PM2.5 >0.08 lb/MMbtu
NOx 0.23 lb/MMbtu
SO2 0.025 lb/MMbtu
CO2 195 lb/MMbtu
Benefits:
Small size
Lower cost
Local wood resource
Simple to operate
Disadvantages:
Hand fed - a large labor commitment
Typically atmospheric boilers (not ASME rated)
Thermal Storage is required
Page 1
Wood Pellet
Wood pellet systems can be hand fed from 40 pound bags, hand shoveled from 2,500
pound sacks of wood pellets, or automatically fed from an adjacent agricultural silo with
a capacity of 30-40 tons. Pellet boilers systems are typically linked to existing heat
distribution systems via a heat exchanger. Product data from KOB, Forest Energy and
Solagen identify outputs of 200,000-5,000,000 Btu/hr based upon burning pellets made
from waste products from the western timber industry. A number of pellet fuel
manufacturers produce all tree pellets utilizing bark and needles. All tree pellets have
significantly higher ash content, resulting in more frequent ash removal. Wood pellet
boilers typically require hand raking of the grates and hand removal of ash 2-3 times a
week. Automatic ash removal can be integrated into pellet boiler systems. Ash is
typically cooled in a barrel before being stock piled and later broadcast as fertilizer.
Pellet storage is very economical. Agricultural bin storage exterior to the building is
inexpensive and quick to install. Material conveyance is also borrowed from agricultural
technology. Flexible conveyors allow the storage to be located 20 feet or more from the
boiler with a single auger.
Emissions from wood pellet systems are typically as follows:
PM2.5 >0.09 lb/MMbtu
NOx 0.22 lb/MMbtu
SO2 0.025 lb/MMbtu
CO2 220 lb/MMbtu
Benefits:
Smaller size (relative to a chip system)
Consistent fuel and easy economical storage of fuel
Automated
Disadvantages:
Higher system cost
Higher cost wood fuel ($/MMBtu)
Page 2
Page 3
Wood Chip
Chip systems utilize wood fuel that is either chipped or ground into a consistent size of
2-4 inches long and 1-2 inches wide. Chipped and ground material includes fine
sawdust and other debris. The quality of the fuel varies based upon how the wood is
processed between the forest and the facility. Trees which are harvested in a manner
that minimizes contact with the ground and run through a chipper or grinder directly into
a clean chip van are less likely to be contaminated with rocks, dirt and other debris. The
quality of the wood fuel will also be impacted by the types of screens placed on the
chipper or grinder. Fuel can be screened to reduce the quantity of fines which typically
become airborne during combustion and represent lost heat and increased particulate
emissions.
Chipped fuel is fed from the chip van into a metering bin, or loaded into a bunker with a
capacity of 60 tons or more. Wood chip boilers systems are typically linked to existing
heat distribution systems via a heat exchanger. Product data from Hurst, Messersmith
and Biomass Combustion Systems identify outputs of 1,000,000 - 50,000,000 Btu/hr
based upon burning western wood fuels. Wood chip boilers typically require hand raking
of the grates and hand removal of ash daily. Automatic ash removal can be integrated
into wood chip boiler systems. Ash is typically cooled in a barrel before being stock piled
and later broadcast as fertilizer.
Emissions from wood chip systems are typically as follows:
PM2.5 0.21 lb/MMbtu
NOx 0.22 lb/MMbtu
SO2 0.025 lb/MMbtu
CO2 195 lb/MMbtu
Benefits:
Lowest fuel cost of three options ($/MMBtu)
Automated
Can use local wood resources
Disadvantages:
Highest initial cost of three types
Larger fuel storage required
Less consistent fuel can cause operational and performance issues