HomeMy WebLinkAboutWEATS Wind Turbine Foundation Design-Permafrost Toksook Bay 07-2007Foundation Design for Wind Turbines in Warming PermafrostBy Brent Petrie; Eric Marchegiani, P.E.; Chet Frost, P.E.; -AVECBenjamin Momblow, P.E.; – Coffman EngineersDavid Myers – S.T.G., Inc.Toksook Bay, AlaskaJuly 2007This project received financial support from the Alaska Village Electric Cooperative, Denali Commission, Coastal Villages Region Fund, U.S. Department of Energy, and the Alaska Energy Authority.
Background Information•27 of AVEC’s 52 villages are in wind regimes of class 4 or better.•Given the characteristics of an NW/100, this means that one machine should be able to produce about 250,000 kWh per year.•Given a diesel efficiency of 14 kWh/gallon generated by our new diesel sets, this means that one 100-kW wind turbine might displace about 17,800 gallons per year of diesel fuel use for power generation. A mini-wind farm of three units would displace about 53,400 gallons per year.
AVEC Systemwide Average Fuel Prices 1973 - 2006$0.354
$0.515
$0.578
$0.649
$0.718
$0.779
$0.968
$1.330
$1.601
$1.610
$1.565
$1.296
$1.203
$0.842
$0.980
$0.964
$1.033
$1.097
$1.190
$1.224
$1.259
$1.208
$1.215
$1.281$1.263$1.088$1.216$1.367$1.389$1.294$1.486$1.936$2.068$2.273
$-$0.250$0.500$0.750$1.000$1.250$1.500$1.750$2.000$2.250$2.500$2.7501973
1974
1975
1976
1977
1978
1979
1980
1981
1982
1983
1984
1985
1986
1987
1988
1989
1990
1991
1992
1993
1994
1995
19961997199819992000200120022003200420052006
YearCost
Many of AVEC’s villages are in Western Alaska have Class 4 or better wind regimes.
Consider that in 2006 AVEC:•Purchased 5.2 million gallons of diesel fuel•Actively used nearly 550 fuel tanks for storage•Took on fuel in 170 separate deliveries (including 44 by air)•Has only one village – Minto – that can be supplied by a fuel truck•Continued to experience electric load growth driven by new water and sewer systems, airports, schools and housing in the villagesThis load growth increases fuel use and fuel storage needs
Therefore, successful integration of wind generation could mean the following to AVEC:•A hedge against increasing fuel costs•A hedge against the increasing costs of marine deliveries•Extension of on-hand fuel supplies which may translate to favorable delivery scheduling by marine transporters•A reduction of the need to build expensive, additional storage on hard-to-acquire or difficult-to-construct sites.
To do such efforts cost effectively, we need to do good planning and coordinate efforts with other construction projects underway in the village.•The recent bulk fuel tank farm and power plant priorities of the Denali Commission provide some opportunity to coordinate logistics and use specialty equipment such as pile drivers or cranes that may be on-site.
Access for specialty equipment required to place foundations and erect turbines is a challenge.
Poor roads, water and sewer lines, boardwalks and existing overhead power and phone lines present obstacles and challenges.
Above ground water and sewer lines are often crossed with timber bridges that will only support an ATV or snowmachine.
Boardwalks can be easily damaged by heavy equipment or melting permafrost.
•They must not settle, tilt or be uplifted•Pile foundations (six to eight piles) may extend 1/3 to 2/3 the height of the tower into the groundFoundations in permafrost are a challenge
• Due to the significant capital expense of installing deep foundations in permafrost conditions, the turbine owner wants to make sure that the investment will consistently produce power over the – year life of the equipment.•Warming trends are affecting the expanse and depth of permafrost.•For example, the next slide shows that the mean annual temperature in Bethel has increased from less than 28° F to over 31° F in the 55 years from 1950 to 2005
University of Alaska Geophysical Institute Climate Trends
• Increasing mean temperatures may contribute to diminished snow cover, increased surface water, and other conditions that may lead to thawing in the underlying permafrost.•One manifestation of warming permafrost is the disappearance of lakes, which is thought to be caused when the permafrost under the lake thaws through its entire thickness and allows the lake to drain into the material below. (Science Magazine; June 03, 2005)The following slide illustrates the process.
Such processes can be noted today when one flies over the tundra and lake expanses of Western Alaska.Diminished lake sizes on Alaska's Yukon Flats are evident between 1954 (top: aerial photograph) and the 2000 (bottom: Landsat ETM+ image). Image credit: Institute of Arctic Biology, University of Alaska Fairbanks.
• In 2004, after two years of planning, AVEC and its construction manager, STG Inc., began mobilization of materials and equipment to the Toksook Bay wind project construction site.•The site was underlain by frozen soils extending 5 to 15 feet deep over a tilted bedrock base.•During the course of shipping the towers and piling, the turbine vendor alerted participants to a concern about the deep point of fixity and possible adverse harmonic conditions that might result.
Wind towers on land in most of the world are built with a ‘point of fixity’ at the base of the tower where it typically rests on a massive concrete foundation.Point of FixityReinforced Concrete Pad
100 ft30-60 ftIn order to be properly secured in permafrost, wind turbines may require pilings in the ground which are 1/3 to 2/3 of the height of the tower. The tower foundation is elevated to allow cold air to pass over the ground to keep it frozen and to avoid heaving of the tower base.
2 to 14 ftFrozen ground at surface in MarchFrost line in September/October after seasonal thawOne problem with Alaska permafrost conditions is that the point of fixity may be below the ground surface and may vary throughout the year as the frost line of the active layer migrates.
2 - 14 ftNo lateral support when thawed New ‘point of fixity’When the active layer is thawed, there is minimal to no lateral support to the piling near the base of the tower.Frozen/Solid Ground
In such conditions, the piles act as an extension of the tower.The rotating turbine, and strong wind forces can create destructive frequencies in the ‘extended’ tower.
This could be addressed by slowing down the turbine and losing valuable energy, especially in the late part of the year when the ground is thawed to its deepest, and when wind speeds are excellent for power production. This approach loses energy and requires complex monitoring of the system operation.
Alternative SolutionAn alternative solution is to stiffen the foundation and damper the structure by adding mass.In the case of two projects involving six towers in permafrost environments at Toksook Bay and Kasigluk, Alaska, pile foundations were modified by adding a 130,000 pound, concrete and steel mass between the tower base, and the piles.In Kasigluk, foundation piles were used with 24 inch helices to resist uplift and with thermal siphons to keep the ground frozen. The objective was to reduce the thickness of the active frost layer, and bring the point of fixity closer to the tower base. Temperature Acquisition Cables (TAC) have been installed at each tower in Kasigluk to monitor changes in ground temperature and to detect thawing below each tower.
Wind siteOverview – Toksook Bay5-15 feet of frozen silts lie over tilted bedrock at the site.
•Holes pre-drilled•Piles driven to refusal•Piles later cut
Rock bolts would be placed into the rock and tensioned to the pile cap.Additional Mass was added by placing a rebar cage and concrete in the pile.Drilling out center of piles to 20’ below end of pile
Six piles for a single tower foundation
Piles with Met tower
The steel foundation cap contains I-Beams to connect the piles and a ring to make the tower base.
Steel Foundation Star (Typical of 3)
Concrete and rebar was incorporated into the tower base and piles to add 130,000 pounds of dampening mass.
Rebar Cage to go into a pile.
•18’ driven pile•Drilled out 20’ below pile end•Installed rebar cage and poured concrete (3,000 PSI)•Design load 63 KIPS•Tested up to 2 times load 127 KIPS (0.019 in movement)•Tested up to 210 KIPS –less than ¼” movementVerification of pile testing
DrainConduitBolts
Rebar placement
Meter base and riser to connect to overhead distribution systemForms were placed underneath the foundation star to hold the concrete in place until it cured.
Foundation Design Criteria- Design Wind Speed = 130 mph (50 year)- Overturning moment = 1,830,000 ft lb- Total tower/turbine weight = 42,000 lbFrequency Analysis-Tower only natural frequency (supported on infinitely rigid base) = 1.15 Hz-Minimum natural frequency for tower and foundation = 1.07 HzBased upon 5% over maximum rotor frequency plus 5% factor of safety-Operating frequency of rotor – 0.97 Hz (58 rpm)
The Wind Turbine Controller is placed before the tower is set.
Danwin Tower Midway Platform
Danwin Tower Inside Flange/Bolt Holes
Tower/Turbine Specifications-108 feet from ground level to center of rotor- Rotor diameter (3 blades) = 61 feet
View from the top!
13,950 lb nacelle being prepared for its lift to the top of a 32 meter tower.
Cleaning the yaw gear teeth prior to setting it on top of the tower.
A Nacelle and tower are placed on a cured foundation.A foundation awaiting concrete is in the foreground.
Second tower section being put in place
Note wiring along ladder and mid point landing. A rope light is used to illuminate the inside of the white tower.
Met tower for power confirmation.Mast and meter base.
Meter BaseConcrete & Steel Mass
Three wind turbines completed at Toksook Bay.
Blade pitching post. Each tower has a blade pitching post to allow the rotor to be dismounted and the blade pitch adjusted.
Blade ExtendersBlade extenders add 1 meter of diameter (20 meters total) to the swept are to increase energy capture.
Tightening hub to turbine
Blades with blade extenders
At Akula Heights (also called Kasigluk) three NW 100 Turbines were installed east of the village on frozen sand and silt. No bedrock was encountered.• Mass was added by filling the steel foundation star with concrete, as in Toksook Bay.•Because there was no bedrock, piles with 24 inch helices were screwed into pilot holes predrilled into the ground.•Thermal siphons were added between, and outward of the piles to extract heat from the soil.
Special Equipment was required to twist the helical piles into the ground
Insulation was added below the tower base to resist thawing.
Installing thermopiles during the Spring at Kasigluk
Installed thermopiles at Kasigluk
Temperature sensor strings, similar to the following, have been installed at Kasigluk to monitor seasonal and long term changes in permafrost temperatures.TOP LEFT: Temperature Acquisition Cable (TAC) and ReaderBOTTOM LEFT: All TACs are permanently labeled with their serial number which ties in with owner information, last calibration date, number and spacing of sensors, & sensor identifications.RIGHT: An artists image of what an installed TAC looks like.TAC Images courtesy of Beaded Stream
Lessons Learned• Geotechnical information is criticalIn areas of complex geology or a highly varied active layer, it is useful to have information from the actual turbine site in order to recognize local variances.When acquiring geotechnical information, also acquire the permafrost temperature and, if possible, install a temperature acquisition cable to monitor temperatures up to the time of construction.Continue thermal monitoring of the turbine site after construction.
• MaterialsThe lack of appropriate local aggregate for concrete can increase costs. Appropriate aggregate may have to be imported in addition to importing cement and mixing equipment.Waiting for the concrete to cure and then testing it can consume valuable time and may require a demobilization and remobilization of the crew.An all steel foundation would require larger components to provide desired stiffness, but may reduce construction complexity by eliminating tasks involving concrete. Portions of such a foundation could be prefabricated and shipped to the site.
• Frequency Modeling should include the pile foundation.In a permafrost environment the point of fixity will rise and fall along the pile during the seasonal change.Under such conditions the piles may behave as an extension of the tower and the turbine, tower and foundation systems may interact to develop a frequency that could be damaging.
• MitigationAdverse harmonics could be mitigated through:•Adjusting turbine rpm, but slowing the turbine would reduce valuable energy output.•Addition of mass to dampen system response at known frequencies.•Stiffening the piles, pile caps, or tower.
2006. Institute of Arctic Biology, University of Alaska Fairbanks. National Aeronautics And Space Administration. NASA. 13 July 2007 <http://landsat.gsfc.nasa.gov/graphics/news/sci0007lg.jpg>. Fuller, Nicole R. Disappearing Lakes. Live Science. 13 July 2007 <http://www.livescience.com/environment/050603_lakes_gone.html>. "Mean Annual Temperatures: Bethel." Chart. 13 July 2007 <http://climate.gi.alaska.edu/ClimTrends/Change/betT.jpg>. Smith, L C., Y Sheng, G M. Macdonald, and L D. Hinzman. "Disappearing Arctic Lakes." ScienceJune 2005. 13 July 2007 <http://www.sciencemag.org>. "Temperature Change in Alaska 1971 - 2000." Map. 13 July 2007 <http://climate.gi.alaska.edu/ClimTrends/Change/TempChange.html>. "Alaska Mainland Regions; 50 Meter Wind Power." Chart. US Dept. of Energy, National Renewable Energy Laboratory. US Dept. of Energy, NREL, 2006. Works Cited