HomeMy WebLinkAboutVillage of Minto - Minto Community Buildings Biomass Project Final Report - Nov 2015 - REF Grant 7071032
Minto Village Council
PO box 58026
Minto, AK 99758
Phone: (907) 798-7112
A project to Retrofit and Weatherize the Minto Lakeview Lodge
Project Location: Minto, AK 99758
Duration of Project: June 1st 2014 – Sept 30th 2015
Tribe submitting report: Minto Village Council
Award Number: DE-EE0006368
Tribal Point of Contact: Business Point of Contact:
Bessie Titus Melanie Titus
Tribal Administrator Tribal Bookkeeper
Minto Tribal Council Minto Tribal Council
P.O. Box 58026 P.O. Box 58026
Minto, AK 99758 Minto, AK 99758
Ph: 907-798-7112 Ph: 907-798-7112
Tribal P.O.C. E-mail: bessie.titus@tananachiefs.org Biz. P.O.C. E-mail: fullbloodedindian@hotmail.com
Main Tanana Chiefs Conference Technical Contact:
David Pelunis-Messier –TCC Rural Energy Coordinator
122 1st Ave Suite 600
Fairbanks, AK 99701
Ph: 907-452-8251 Ext 3479
E-mail: dave.pm@tananachiefs.org
08 Fall
Minto, Alaska Lakeview Lodge START Program
Weatherization and Rehab Project Final Report
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
2
Minto Village Council
START Final Report
Award:DE-EE0006368
Table of Contents
Executive Summary ......................................................................................................................... 3
Project Overview ............................................................................................................................. 4
Objectives........................................................................................................................................ 6
Description of Activities Performed (Including Photos and Graphs) .............................................. 9
Overview of Data .......................................................................................................................... 10
Conclusions and Recommendations ............................................................................................. 12
Conclusions .............................................................................................................................................................................. 12
Recommendations................................................................................................................................................................. 13
Lessons Learned ............................................................................................................................ 14
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
3
Minto Village Council
START Final Report
Award:DE-EE0006368
Executive Summary
Minto Village Council applied to the Alaska START (Strategic Technical Assistance
Response Team) Program in the spring of 2013 and was selected in the summer of 2013.
Minto Village Council acts as the governing body for the community of Minto and manages
most of the services in the community including transportation and the village
water/sewer system. The goal in becoming a START community was to help the tribe and
the community address the high cost of energy and to save the tribe money as it struggles
to provide vital services for all community members. The START program facilitated a
movement in the community to improve the village’s energy situation. It brought important
community stakeholders to the table to discuss possible energy solutions and provided
funding for the community to help weatherize the largest energy consumer, the Minto
Lakeview Lodge.
Figure 1. IRHA, Minto Village Council and DOE Tribally Energy Staff members standing in front of the
almost complete Minto Lakeview Lodge in fall 2014. From left to right Annie Silas (IRHA), Jesse Joseph
(IRHA Electrician), Kim Carlo (IRHA C.O.O.), Melanie Titus (Minto Village Council Book keeper) Laurie
Baker and grandson (Former Minto Village Council Member). Gareth Baker (Minto Village Council
Member), Pilar Thomas (Former DOE Tribal Energy Deputy Director), Bessie Titus (Minto Village Council
Tribal Administrator), Givey Kochanowski (DOE Tribal Energy Alaska Coordinator), Chunky Edwards
(Former IRHA Construction Foreman)
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
4
Minto Village Council
START Final Report
Award:DE-EE0006368
Project Overview
In the summer of 2013, Minto Village Council was accepted into the Dept. of Energy START
(Strategic Technical Assistance Response Team) Program to help the community reduce
their high costs of energy. Heating fuel in Minto at that time was ranging from $4.50/gal to
$6.50/gal and electric rates in the community were around $.60/kWh. The tribe had
recently signed a check made out to a local Fairbanks company, Chena Power for $35,000
for the purchase of a wood fired boiler to heat their 10,000 sq ft building, the Lakeview
Lodge. The Lakeview Lodge was and is very much the center of the community, but it had
not received any significant energy upgrades since it was constructed in the early 1980’s
with outdated building practices. The walls in the lodge were thin and the air leakage was
significant. Some of the offices literally could not be used because they were too cold during
the winter months.
During the early summer of 2013, energy specialists from the Alaska Energy Authority, the
Dept of Energy Tribal Energy Program, The Denali Commission, Alaska Energy Authority
(AEA), Alaska Housing Finance Corporation (AHFC), National Renewable Energy
Laboratory (NREL), Interior Regional Housing Authority (IRHA) and Tanana Chiefs
Conference (TCC) came to Minto and hosted a community meeting to identify and prioritize
the community’s energy needs.
Figure 1 Old View of the Minto Lakeview Lodge from the same aspect as Figure 1 before Renovation. Note the
stains on the building from 30+ years of frost buildup as the heat from inside the building met the extreme cold
temperatures on the outside
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
5
Minto Village Council
START Final Report
Award:DE-EE0006368
An array of options for the community were discussed including renewable energy, energy
efficiency, community infrastructure needs and the high cost of heating and electrifying the
Lakeview Lodge. After collecting information on all of the community’s options over the
next few months, the tribal council selected the 10,000 sq ft Lakeview Lodge as their main
focus for the project funds. The Lodge is home to the main tribal offices, elders nutrition
program, IGAP program, school lunch program, tribal operations, tribal transportation and
the Indian Child Welfare Act (ICWA) program. It was agreed IRHA would put together a
proposal for the project, the DOE would contribute $250k for weatherization and energy
efficiency and the tribe would match the DOE share with $113,158 from a state of Alaska
Capital Improvement Project (CIP) and donated in-kind staff time. The final product would
be a complete weatherization of the lodge and hopefully a 30-50% reduction in energy
costs.
Figure 2. This was one of the older doors on the lodge, insulated around the fr ame but still with numerous air
leaks around the entire frame and UV rays are reducing the effectiveness of the insulation
Work was planned during late 2013 and early 2014 and completed during the summer of
2014. During the winter of 2014/2015 the tribe was seeing reduced heating and electrical
bills. Very little information regarding the pre-renovation heating load of the building
exists, but according to the individuals responsible for delivering fuel to the Lakeview
Lodge, the heating load of the building was reduced dramatically. The tribe and community
are very happy with their updated, more affordable base of operations and would like to
thank the Department of Energy Tribal Energy Program and the State of Alaska for their
assistance with and funding for this important project. It should be noted that the DOE and
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
6
Minto Village Council
START Final Report
Award:DE-EE0006368
State of AK funding through the START grant has leveraged an additional $200k Village
Energy Efficiency Program (VEEP) grant and a $273k Renewable Energy Fund (REF)
biomass project grant that the community is now working to complete.
Figure 3. Mold and rot visible throughout the building's crawl space from various leaks and moisture issues. The
building’s knee walls were failing in some points when work was started but the knee walls would be shored up
and repaired over the course of the project
Objectives
The main objective listed in the approved Statement of Project Objectives (SOPO) is to
reduce energy costs on the building by between 30-50%. Although the electrical use in the
building has not declined dramatically we believe the fuel use has been reduced by
between 30-50%.
Other objectives of the project included spreading the message of energy efficiency
throughout the community. This objective has certainly been achieved. Since the
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
7
Minto Village Council
START Final Report
Award:DE-EE0006368
community wide energy meeting in 2013 there has been a lot of work moving the
community toward greater energy independence and sustainability. In the tribally run
transportation garage and fire hall, the tribal transportation director hired tribal members
and led the construction of a small rocket stove that is being fired 3-4 times per day and is
greatly reducing the fuel costs in that building.
As part of the START program, conversations and outreach were completed with village
residents and individuals were provided with energy efficiency education and LED lighting
for some homes. This has helped encourage the continuation of energy efficiency
conversation in the small, close-knit community.
Figure 4. Minto Village Council members in the newly renovated Minto Lakeview Lodge under LED lighting and
with new triple paned windows throughout the building
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
8
Minto Village Council
START Final Report
Award:DE-EE0006368
As a result of the START award, the community applied for and was granted funding from
the state of Alaska VEEP program to complete additional weatherization and upgrades to
the Minto fire hall. This work was completed during the summer of 2015 and at the time of
this report the fire hall is nearly complete and ready to begin housing the only fire truck in
the community.
An additional result of this project was that the tribe also applied for and was granted
funding to complete the construction of a small biomass boiler that is being designed to
heat the Lakeview Lodge and adjacent Minto Village Clinic. The grant funds came from the
state of Alaska Renewable Energy Fund in the amount of $273k and they are working with
the Alaska Native Tribal Health Consortium (ANTHC) to determine the best project
management approach to complete the construction of the biomass system that will service
both buildings.
Figure 5. Aerial view of the Minto Lakeview Lodge (Right) and Minto Clinic (Left) and the ap proximate location of
the biomass boiler slated for construction summer 2016 which will heat both buildings with locally sourced cord
wood
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
9
Minto Village Council
START Final Report
Award:DE-EE0006368
The fact that this project is moving forward underscores the significance of the START
award. When Minto was selected as a START community, they were prepared to install an
undersized biomass system that would have had the same problem as the fossil fuel
heating system, an inefficient building that was leaking air and heat into the outside world
and running inefficiently. The tribe is now following the mantra of “Efficiency First!”
weatherization of the Lakeview Lodge has been completed, the energy use was reduced
significantly and the tribe is now able to install a system that will supply heat to both
buildings affordable and efficiently.
Description of Activities Performed (Including Photos and Graphs)
The Lakeview Lodge was constructed in the early 1980s or late 1970s when oil was cheap
and building science was not focused on long-term energy use. Oil prices were less than
$1/gal in those days and the main focus was to construct a building, not to construct a
building that would operate efficiently over the next 30 years. Between the time the
Lakeview lodge was constructed and the time the building was weatherized, almost no
renovation to the exterior of the building or the building’s heating system occurred.
Before the weatherization and rehabilitation of the Minto Lakeview Lodge, the windows
were all original, the siding was original and many of the light fixtures we believe were
original. Leaks and improper drainage over the years also took their toll on the building
foundation and crawl space. The work that IRHA performed on the building is listed here:
1. Excavate foundation walls and replace rotting timbers with new foundation knee
walls, appropriately sealed with a water proofing membrane
2. Re-slope the drainage away from the building
3. Remove and rebuild the fire-escapes that are on either side of the building
4. Remove the t1-11 siding from the walls of the building and inspect insulation, fill in
gaps in the insulation and air seal around the existing, unsealed vapor barrier and
electrical connections with new fiberglass insulation
5. Re-install T1-11 siding and add 4 inches of rigid foam insulation to the exterior of
the building, fur out with furring strips and add new metal siding to the building.
This brought the R-value of the wall from an R-19 to what we estimate is at least an
R-41
6. Replace all single and double pane windows throughout the building with smaller
triple pane windows, repair drywall on the inside of the building and insulate the
exterior of these spaces
7. In the attic space, clear existing insulation, air-seal all electrical penetrations in the
ceiling drywall and re-insulate the ceiling bringing the total R-value in the attic from
an estimated R-21 to between an estimated R-70 - R-100
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
10
Minto Village Council
START Final Report
Award:DE-EE0006368
8. Install new exterior doors and arctic entryways on all of the exterior entrances to
the building
9. In the crawl space, all leaky plumbing connections were repaired and existing
circulating pumps, 32 total, were replaced with ECM circulating pumps. These
pumps use significantly less electricity and have an auto adapt function so they turn
off in the summer when they are not in use
10. Straighten the knee walls in the crawl space and shim them as needed, replace
rotten wood
11. Tune up and clean boiler and add a large Grundfos Magna circulating pump to
reduce energy use
12. Convert all lighting both interior and exterior throughout the building to LED
lighting using retrofit kits and new wall packs on the building’s exterior
13. Convert switches throughout the building to occupancy sensors so that lights will
turn off automatically when not in use
14. Install smoke detectors where needed and GFCI outlets in the kitchens and
bathrooms to bring electrical system up to current building code
Overview of Data
The data collected during the project is shown and discussed briefly in this section. It
should be noted that data collection was completed by a variety of people during the
START program and that previous administrations at the tribe were not as focused on
energy use or data collection, so minimal heating data was collected from actual records
before the retrofit work was done. The data was assembled based on conversations with
various tribal representatives, using estimates from reports that had been done on the
building and using conversations from the individuals who delivered fuel.
The data in the first graph below shows the electrical usage in kWh use and cost to the tribe
in dollars ($) for the years 2012-2014 during the months of January-September. These
months were selected because those are the months of 2015 that data is presently available
for at the time this report was drafted. The reduction in energy use for this period of time
was about 7% based on numbers before and after the retrofit work was done.
The NREL modeling shows a larger expected reduction in energy use of closer to 20%. We
believe the difference between estimated and predicted was caused by 3 main factors.
First - inaccurate data was used in the NREL modeling to predict yearly electrical
use of the Lakeview Lodge.
Second - the model did not predict that a number of circulating pumps that were not
previously working would begin working and thus consume energy.
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
11
Minto Village Council
START Final Report
Award:DE-EE0006368
Third – the model did not predict that increased comfort in the building would lead
to greater use of the space and thus greater energy consumption.
Figure 6. Electrical Use Graph Showing Cost ($) and kWh usage from Jan-Sept of 2012-2015, a slight reduction of
around 7% over previous years averages was observed.
The fuel data is graphed below and shows a number of scenarios. Dark Blue shows the
estimated fuel use before the retrofit of roughly 10,000 gallons and a presumed cost to the
tribe of $55,000. This information is based off conversations with tribal members and a
prefeasibility assessment that was done for wood heat in the Lakeview Lodge and clinic.
The NREL modeling used the square footage of the building, the boiler and hydronic system
and information on the local climate to predict that weatherization and upgrades to the
lodge would reduce fuel usage in the building from 10,000 gal of fuel per year to 7700 gal
of fuel per year, this is shown in Red. At a cost of $5.50/gal that would be a savings of
$12,650 per year. The tribe believes that a savings of close to 2300 gallons per year is
realistic and represents the actual savings.
Information collected from the tribe’s book keeper is shown in teal in the graph below and
only details total annual fuel consumption of 1,473 gal of fuel for the Lodge. The records also
show a cost of $4.80/gal for a total winter-time cost of $7,070. This would indicate a
reduction in fuel use of 86% which we believe is unrealistic based on the size of the
building and the improvements that were made. It is more likely that the record
keeping at the tribe was missing some of the fuel that has been delivered to the lodge.
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
2012 2013 2014 2015
Jan-Sept kWh usage
Cost to the Tribe ($)
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
12
Minto Village Council
START Final Report
Award:DE-EE0006368
It is believed that the Lodge has decreased its fuel consumption dramatically since the
weatherization upgrades because the individuals who deliver fuel have noticed a sharp
drop in fuel consumption at the lodge. TCC, Minto Village Council and IRHA plan to
continue to monitor the fuel usage at the lodge throughout the winter of 2015/2016 and
verify that the tribe is seeing significant sustained reductions in fuel consumption. These
entities would be happy to report results to the DOE as they become available.
Figure 7 This Graph shows the estimated fuel use pre project, the modelled fuel use post project and the
documented fuel use post-project. We believe the actual post project fuel use lies somewhere closer to the
modelled fuel use but still represents a reduction of 2300 gallons
Conclusions and Recommendations
Conclusions
The Minto Village Council and the community of Minto would like to express a sincere
thanks and appreciation to the Dept. of Energy Tribal Energy program for selecting Minto
as a START community. The community would also like to thank the contractor, Interior
Regional Housing Authority for their work on the building, the Minto Tribal Council’s past
and present members, and all of the community members who were hired to work on the
building. The focus on Minto’s energy situation that resulted after the START project was
started has had a very beneficial impact on our community.
Financially, being selected as a START community has brought in $723k worth of grant
funding to our small community ($250k START, $273k REF Biomass, $200k VEEP grant)
0 20000 40000 60000
Cost ($)
Gallons (#)
Observed Yearly Fuel Use
Post-Retrofit
Modelled Yearly Fuel Use
Post-Retrofit
Estimated Yearly Fuel Use
Before Retrofit
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
13
Minto Village Council
START Final Report
Award:DE-EE0006368
and has collectively saved the tribe thousands of dollars in energy costs. This funding has
put local residents to work, created numerous jobs and helped move the community
toward a more sustainable future.
In addition to the energy savings occupant comfort level in the building has increased
dramatically. This is believed to be the result of repairing zone valves, circulating pumps
and multiple thermostats and the improvements to the building shell. As a result of this
project, 4 offices that were previously unusable due to extreme cold during the winter
months are now usable and functional. This has allowed tribal operations staff and other
programs to expand their space and take advantage of the newly available offices. Although
the large reduction in electricity use that was anticipated has not been observed, it is
believed that this was a result of increased building use due to higher occupant comfort
level. It is also believed that replacing some of the non-working circulating pumps caused
the building to consume more electricity.
It is important to note that at the same time the building was weatherized, a commercial
grade range hood over the cook stoves was installed to bring the building up to current fire
code compliance. Although the above mentioned items have increased the electrical use in
the lodge, because of the energy efficiency upgrades, the tribe has seen a 7% reduction in
energy use from the average of 2012-2014 as compared to 2015.
Recommendations
Much of the recommendations are issues with the process rather than the outcome of the
START award.
Have the DOE offer an “owners rep” that knows the realities of working in rural
Alaska for the project to help the tribe determine which energy efficiency measures
make sense and which do not
Be aware of the tight construction schedule that exists in Alaska and help the tribe
meet important deadlines for reporting and shipping materials
Paperwork to begin the grant took a lot of time and energy and it is believed that
more assistance from the DOE would help us streamline the process
Mid-project meetings facilitated by the DOE would help the tribe stay organized and
help the project move forward in an efficient manner
For energy efficiency projects specifically helping the tribe install cost effective, easy
to use energy monitoring tools on the building would streamline future data
collection. It would also make sharing the data from energy savings with our
community, simple and easier
Ch’echalyu Bedzeyh Ti Xwt’ ana Tonidra Ghetslina Tsiyhyu
Native Village of Minto P.O. Box 26 Minto, Alaska 99758 ph (907)798-7112 fax (907) 798-7627
mintovillagecouncil@hotmail.com
14
Minto Village Council
START Final Report
Award:DE-EE0006368
Lessons Learned
The tribe learned many lessons on project management and energy efficiency from this
project, some lessons learned have been outlined below.
1. It is important to ensure all staff members are on board with responsibilities before
committing to a project of this scope and size.
2. For projects that occur during overlapping council election cycles, it is important to
educate new council members to keep them up to speed with projects that are
ongoing. This includes the purpose of the project, estimated outcomes, timelines and
responsibilities
3. Putting a plan in place early on in the project timeline to make sure that
responsibilities and meeting times are planned to review changes in the scope are
clearly identified. Keeping contractors in communication with the grant recipient in
respect to the scope of work is vital.
4. It is important to have an “owners rep” involved in the process, somebody who is on
the side of the tribe in this case, but is familiar with the work that will need to be
completed.
5. Energy bills in general are important to have to track the before and after use. The
electric bills were available but the heating bills before the project were unavailable
making before/after comparisons difficult. The tribe is now doing more work with
tracking heating and electric bills.