Energy Projects 1984 Appendix G-12 Tuluksak
Bethel Area Power Plan Feasibility Assessment APPENDIX G-12 TULUKSAK COMMUNITY REPORT DRAFT Prepared for the Alaska Power Authority by Harza Engineering Company and Darbyshire &Associates Draft April 1984 TABLE OF CONTENTS Introduction Background Population Housing Current Economic Activity Subsistence Cash Economy Future Economic Activity Current Energy Consumption Total Energy Electric Generation Future Energy Demand Formulation of the Supply Plans Economic Evaluation Base Case Supply Plan Optimized Base case Supply Plan Thermal Supply Plans Hydropower Supply Plans Fuel Cell Supply Plans Sensitivity Analysis Regional Summary Environmental Evaluation -i- Table No. XII-1 XII-2 XII-3 XII-4 XII-5 XII-6 XII-7 XII-8 XII-9 XII-10 LIST OF TABLES Title Tuluksak Household Size Tuluksak Employment and Income Tuluksak Projected Annual Earnings Tuluksak 1981 Fuel Prices and Consumption Existing Generating Facilities Tuluksak Energy Demand Forecast Most Likely Scenario,Present Worth and Benefit-Cost Ratio of the Supply Plans Most Likely Scenario,Sensitivity Analysis Using 0%Real Fuel Escalation Sensitivity Analysis,Present Worth of Supply Plans Ranking of Energy Supply Plans -ii- Page XII-3 XII-5 XII-7 XII-9 XII-10 XII-11 XII-14 XII-17 Xx11-18 XII-20 Exhibit No. 1 2 LIST OF EXHIBITS Community Location Map Tuluksak Population 1981 Economic and Energy Profile,Tuluksak Economic and Energy Projections,Tuluksak 1981 Primary Energy Consumption,Tuluksak 1981 Energy Balance,Tuluksak Electrical Distribution System -iii- TULUKSAK COMMUNITY REPORT Introduction The Bethel Area Power Plan Feasibility Assessment has been performed by Harza Engineeriny Company under contract to the Alaska Power Authority.The assessment was done to determine the best alternative(s)to meet the future electric generation and space heating needs of the Bethel region.The community of Tuluksak is within the study area,and is the subject of this Appendix.Detailed information on the overall regional assess- ment is contained in the Regional Report. The community report for Tuluksak is intended to be an informational and working document for the residents of the community.Much data has been collected on the community's background,population,housing,and its current economic and energy profiles.Existing electrical generation and transmis- sion facilities,as well as residential and commercial space heating needs,are documented in this report.Projections of future energy needs,based on future population,housing,and economic conditions,have been made.These projections have been used to develop alternative plans for meeting the electri- cal energy and space-heating needs of the region throuyh year 2002,and those of Tuluksak in particular.These alternative plans have been analyzed from both an economic and environmental standpoint. This community report for Tuluksak is submitted as a draft for review and comment by the residents.The Alaska Power Au- thority welcomes your comments and questions. Background Tuluksak is located in the Yukon-Kuskokwim Delta on the south bank of the Tuluksak River,36 miles northeast of Bethel (Exhibit 1).The village is located well within the lower end of the bottomland spruce-poplar forest belt that follows the course of the Kuskokwim River and its main tributaries.The remaining vegetation inland from the river bottom,containing the village site,is characterized as wet tundra.Standing water is present throughout the summer,which makes overland travel extremely difficult. Access to Tuluksak is principally by year-round charter air service and limited summer lighterage service from Bethel.There is no road system in the area,Overland movement is limited primarily to the winter season.The river is used as a roadway for taxis and truck freight during the winter season after the XII-1 ice has thickened.Fuel oil and other freight items are trucked Over this ice highway on an ""as-necessary"basis to meet late- winter shortages.Snow machines provide the most competent mode of travel in winter. "Tuluksak"is an Eskimo word which translates to "raven.” A village was reported to be at the present site in 1861 with the name of "Tul'yagmyut."The village is now incorporated. Beside the municipal government,Tuluksak's Native popula- tion is represented by an IRA Council which is recognized by the federal government as the offical tribal yoverning body of the village.The IRA Council form of yovernment was established under the Indian Reorganization Act of 1934.It is eligible to participate in some state and federal proyrams,and has received benefits under the Indian Self Determination Act,the State and Local Fiscal Assistance Act,the Housing and Community Develop- ment Act,the Comprehensive Employment Training Act (CETA),and the Indian Child Welfare Act. Another local organization,the village corporation,al- though not a government entity,exercises a variety of functions generally exercised by governments.The local village corpora- tion,Tulkisarmute,Inc.,was created under the Alaska Native Claims Settlement Act to receive and manage lands conveyed to it under the act,It is entitled to receive title to the surface estate of 92,160 acres of land.To date,no lands have been transferred to the corporation by the Bureau of Land Management. The village corporation also owns the local Native store and sells gasoline and diesel fuels to the community's residents. In conjunction with this study,a public meeting was held in Akiak in April 1982.Residents of Tuluksak were invited to attend. Population The population of Tuluksak increased from 150 in 1880 to 236 in 1980.As shown on Exhibit 2,between 1960 and 1980,the population population grew at an average annual rate of 2.8 percent.The racial composition has changed slightly from about 99 percent Alaskan Native in 1970 to about 98 percent by 1980. The age characteristics of the population have also changed.In 1970,the number of young people was high,and the average age was about 17.Since then,a significant number of young people apparently left the region in order to find jobs or to pursue their education.In 1980,the average age was about 20. Three scenarios of population projections are also present- ed on Exhibit 2.These projections were developed in conjunc- XII-2 tion with the three scenarios of economic projections which are presented in the following pages.The projected annual growth rates are a combined product of historical trends,actual rate of natural increase,potential economic yrowth,and immigration or emiyration,.The projections also reflect a general decline of state population growth rates predicted by the U.S.Depart- ment of Commerce,In year 2002,the Tuluksak population is expected to be between 281 and 316 persons. There were 42 housing units in the community in 1980.Of the housing units,36 were owner-occupied.The average number of persons per household was 5.6.Only 5 percent of the homes (2 houses)had complete plumbing facilities.HUD recently com- pleted construction of 27 additional homes in the community in 1981.Residents presently haul their water from a central watering point,A washeteria is in the process of being con- structed. The averaye floor space of the most recently built homes (HUD)is approximately 1200 square feet,while the older structures contain roughly half of this floor area.Whereas the Older homes are less well insulated,they are often better built and better sited away from wind exposure and snow drifting than the newer homes. The future housing stock will play an important role in determining future residential energy demands.The averaye number of persons per housing unit has not changed between 1970 and 1980.However,the improved household income and the supply of subsidized housing units are expected to decrease the average household size.As shown in Table XII-l,the average household size is expected to be between 4.0 and 5.0 by 2002. Table XII-1 TULUKSAK HOUSEHOLD SIZE Energy Demand Projections Year Low Most-Likely High 1980 (U.S.Census)N/A 5.6 N/A 1987 5.3 5.3 5.0 1992 5.2 5.2 4.8 2002 5.0 4.5 4.0 XII-3 Current Economic Activity This section describes the current villaye economy,in both its susbistence and cash forms.This assessment will serve as a basis for the economic projections. Subsistence Residents of Tuluksak depend on the environment in large part for subsistence,Subsistence can be defined as obtaining food,fiber,and shelter from the surrounding environment. Subsistence activities are pursued by a majority of the communi- ty's residents.A recent survey done in the Bethel region esti- Mates that approximately one-third of the residents surveyed obtained one-half or more of their foodstuffs by engaging in such subsistence activities as fishing,berrypicking,and col- lecting gamebirds along the sloughs and on the swampy tundra, It is also estimated that the remaining two-thirds of the resi- dents collect about one-fourth of their needs. Residents rely on subsistence activities tor a number of reasons:it is the traditional method of provision passed to the present generation by its forefathers;in time of high ship- ping and transportation costs,it offers savings over the pur- chase of costly foodstuffs;and it provides a fruitful form of recreation.Dog,king,and silver salmon,as well as ling cod, shellfish,whitefish,and blackfish,provide food for many residents of Tululsak.Residents also hunt moose,bear,beaver, mink,rabbit,ptarmigan,duck,and yeese. An estimate of the equivalent income obtained from subsist- ence activities can be regarded as that portion of the typical household budyet that is replaced by these subsistence items. Using the figures developed for the Bethel region and assuming a annual typical household budget of about $10,000,then the total cash value of these activities can be estimated at about $150,000 annually. Cash Economy Cash employment in Tuluksak exists in forms which are simi- lar to other outlying village economies in Alaska.Unemployment and underemployment are a problem in the community.A few paid positions exist with the city,school,health clinic,trading posts,and post office. Exhibit 3 shows the 1981 economic and eneryy protile for Tulusak.Exhibit 3 corresponds to the forecasting model output for Tuluksak as analyzed in this study.The forecastiny model is described in Appendix A.In Exhibit 3,total annual income XII-4 Or earnings,in 1981 dollars,are first presented for each economic activity,followed by the correspondiny number of average annual employment.The remaining columns present the end-use energy consumption for each activity.The column entitled "Electricity"corresponds to the total electricity demand,which is the sum of last column "Light and Electric Appliances"consumption and the electricity consumption used in "Cookiny,Space Heating,and Water Heating".For convenience, all consumption data are in Million Btu.The electric energy demand can be translated into kilowatt-hours by dividing the consumption in Btu by 3,413 (Btu per kilowatt-hour).The lower section of Exhibit 3 presents the residential sector with population,average househole size,and end-use demand.The last line summarizes the total demand from the commercial, government and residential sectors. Table xXII-2 below summarizes the 1981 averaye monthly employment and annual income by sector that are typically found in a village the size of Tuluksak.It should be noted that the numbers listed for each sector do not necessarily indicate full- time employment,More than one of these positions may be held by one person simultaneously or by the same person at different times of the year. Table XII-2 TULUKSAK EMPLOYMENT AND INCOME Average Monthly Annual _-Economic Activity _"Employment Earnings (1981 $) Renewable Resource Harvesting 4 $48,000 Mininy and Exploration 0 -0- Construction 22 259,000 Household Manufacturing 1 4,000 Transportation 1 9,000 Wholesale,Dist.0.5 4,000 Comm.and Utilities 2 29,000 Trade and Private Services 7 84,000 Finance and Real Estate 2 30,000 Non-Profit Organization 1 16,000 Local and Regional Government 31 512,000 State Agencies/Services 1 35,000 Federal Agencies/Services 3 35,000 Transfer Payments N/A 498,000 TOTAL $1,528,000 XII-5 As shown in Table XII-2,the primary sources of income to the village are local and reyional government,transfer pay- ments,construction,trade and private services,and renewable resource harvesting.These and other income sources are des- cribed below. Local and Regional Government.The villaye school system provides the largest number of cash-earning positions to Tuluk- sak residents.Two separate systems currently exist.The state-run Lower Kuskokwim School District provides a village high school,The elementary grades are provided by the Bureau of Indian Affairs School System.Positions associated with the systems are:principal teacher,certified teachers,substitute teachers,bilingual teachers,instructional aides,clerk/ typists,community educational coordinators,librarians,pre- school teachers,and athletic directors.Support positions that exist in the school are cooks,cook's helper,school maintenance and school custodian. Positions with the villaye yovernment take the following form:fee ayents,bookkeepers,city administrators,city clerks,city maintenance,city custodian,city recreation director,villaye public safety officer,village patrolman,IRA Council administrator, Transfer Payments.Non-employment forms of cash flow exist as transfer payments.Transfer payments are made directly to a household in two forms --cash and/or goods.Cash payments are made through social security,general welfare (SSI,Old Age, Blind,AFCD,VA,food stamps,etc.),home mortyaye subsidies, rental subsidies,and home energy and fuel purchase subsidies. A major subsidy is the state's Power Cost Assistance Program. Construction.Construction projects both in Tuluksak and throughout the reyion provide employment opportunities that typically represent the largest private cash-earning potential locally. Trade and Private Services.Retail trade activities pro- vide full-time manayerial,clerical,and stock room positions. A village corporation owned and operated store exists with other privately owned village stores.Private services are provided as well as small variety and novelty shops and small engine dealers and service. Renewable Resource Harvesting.Positions under this cate- gory include trapping,firewood gathering,fishing,and serving as guides in fishing,hunting,and excursion trips.The most cash-rewarding activity in this industry is commercial fishing. XII-6 Other Sources,The remaining income sources listed in Table XII-2 make up only a minor part of the total village in- come.State and federal agency services,finance and real estate,and communications and utilities,represent the largest income sources of this group. Future Economic Activity Future energy demand will depend upon the changes in the economy and the purchasing ability of the households.To reflect the potential changes over the next twenty years,three levels of expected change (most likely,low and high)were developed, The results of the economic projections for the years 1987, 1992,and 2002 are presented on Exhibit 4.Exhibit 4 is organized as described earlier for Exhibit 3.Table XII-3 sum- marizes the expected range of future economic activity.Total annual earnings,in constant 1981 dollars,are shown for the three scenarios.The difference between the low and high pro- jections represents the degree of confidence in projecting the future economic course of Tuluksak. Table XII-3 TULUKSAK PROJECTED ANNUAL EARNINGS (Constant 1981 Dollars) _Projections Year Low Most-Likely High 1981 (Surveyed)N/A $1,528,000 N/A 1987 $1,333,000 1,416,000 $1,727,000 1992 1,395,000 1,597,000 1,989,000 2002 1,509,000 1,897,000 2,256,000 By the year 1992,under the "Most-Likely"set of circum- stances,the total villaye cash economy is expected to have completed its recovery from the 1980's slump.The remainder of the forecast to the year 2002 is characterized by a period of slow and continual expansion at a rate of about 2 percent. The "High"forecast assumptions differ from the "Most- Likely"primarily in the severity of the anticipated slump dur- ing the early 1980's.The effect of these less severe reduc- tions is measured in the forecast as a slowly expanding economy of about 2 percent annual growth rate until 2002. XII-7 On the other side,the "Low"forecast assumptions represent a much more sudden and severe slump in the total income earnings potential of the village during the remainder of the 1980's. Recovery is expected from this "slump"period,caused by govern- mental cutbacks,due primarily to a shift in the regional econo- mic base toward decentralization.Still,this recovery is as- sumed to be slower and to begin at a much lower point than the most likely and high projections.By 1992,the total cash earn- ed in the economy is expected to be only 91 percent of the amount earned 10 years earlier.By the year 2002,the total cash earning potential of the village economy is expected to have recovered to the 1981 level. Current Energy Consumption An energy use inventory was conducted in order to gain an understanding of the total energy consumption,and the relative importance of electricity.Exhibit 5 presents a detailed list- ing of the energy consumption by end uses and by fuel type. Total Energy Space and water heating was the major energy end use with a total consumption of about 12,000 million Btu.A Btu (British Thermal Unit)is a measure of the amount of heat eneryy required to raise the temperature of a pound of water by one degree Fahrenheit.Fuel oil provided about 80 percent of the total heating needs,and the remaining was provided by wood.Residen- tial cooking consumed about 2,800 million Btu,from wood (75 percent),fuel oil (9 percent),propane/blazo (9 percent),and electricity (7 percent).Lights and electric appliances con- sumed an equivalent of about 6V0 million Btu.One kilowatt--hour is equal to 3,413 Btu. Table XII-4 summarizes the total consumption by fuel types. It also shows the average unit price of each fuel.The estimat- ed total cost to Tuluksak for their 1981 energy demand was about $230,000.Some 23 percent was spent on diesel fuel for generat- ing electricity. XII-8 Table XII-4 TULUKSAK 1981 FUEL PRICES AND CONSUMPTION Unit Annual Price Consumption Fuel oil $1.89/gal.75,000 gal. Diesel $1.89/gal.30,000 gal. Propane $120/100 lb bottle 10-100 lb bottles Blazo $3.50/gal.1,500 gal. Wood $150/cord 260 cords Because of the large quantities needed annually to meet year-round energy demands,the only economical supply method is by water barge.A regional lighteraye service is operated out of Bethel which uses the vast network of rivers and sloughs to deliver the fuels during the relatively short ice-free period of late summer and fall.Consequently,the vast majority of the annual fuel supply of the village must be delivered and stored on site during this portion of the year.Bulk fuel storage facilities are therefore a critical component of the present villaye energy system.Separate bulk fuel storage facilities are maintained in the villaye of Tuluksak for the LKSD high school,the BIA elementary school,and the village bulk fuel distributor,Tulkisarmute,Incorporated.All combined,the total storage capacity is approximately 89,000 gallons,which is not sufficiant to contain the total annual fuel needs. Exhibit 6 presents the village energy balance for 1981. Due to conversion factors and electric distribution losses,the "useful"energy was about 9,000 million Btu or 47 percent ot the total consumption, Electric Generation Present Demand.In 1981,the total electric demand of the village was about 230 megawatt hours (MWh).The 1981 peak de- mand was 65 kW. Existing Facilities.Three separate diesel electrical generating systems exist:one to provide power to the village, and two others for the two school systems.Table XII-5 below describes these systems.The distribution system (Exhibit 7)is two years old and in good condition.Under construction is a new generator building and system located at the far east end of XII-9 town.A new distribution system has also been constructed to serve the new housing installed this year. Table XII-5 EXISTING GENERATING FACILITIES Operating Owner/Operator Status Capacity (kW) Tulkisarmute Inc.Primary 55 Tulkisarmute Inc.Primary 100 LKSD Primary 75 LKSD Primary 75 LKSD Primary 25 BIA Primary 75 BIA Primary _50 Total Capacity 455 kW Future Energy Demand Three projections of future energy demand (low,most- likely,and high)were developed,based on current use,socio- economic projections,and assumptions regardiny future end use demand.The most likely scenario is based on the most likely projections of economic activities,population,and household Size described earlier.It also reflects a mid-range forecast of eneryy price trends.The low scenario reflects a more con- servative growth derived from the low projections of economic activities,population,and household size,as well as a real energy annual yrowth rate of 2.5 percent.The high scenario assumes a continuation of the subsidized present situation,both at the energy level and at the economic level. The forecasts are based on estimated growth in each econo- mic activity described earlier,and in the residential sector. Pages 1 throujyh 3 of Exhibit 4 present the end use projections for 1987,1992 and 2002 under the most likely scenario.Pages 4 through 6,and 7 through 9 present the projections for the low and high scenario,respectively.Table XII-6 summarizes the results.Space heating demand was increased by about 15 percent to reflect the average annual heating needs of the region,since 1981,the base year,was warmer than averaye.The total elec- tric energy demand is expected to vary between 325 and 490 MWh in year 2002,with a most likely energy demand of 405 MWh.The most likely 2002 peak demand is 115 kw. XII-10 Table XII-6 TULUKSAK ENERGY DEMAND FORECAST Most Low Likely High Total Energy Demand (Btu x 106) 1981 Demand N/A 16,747 N/A 1987 Demand 17,524 18,135 20,182 1992 Demand 19,407 21,655 24,611 2002 Demand 21,359 26,714 31,241 Electric Energy Demand (MWh) 1981 Demand 230 230 230 1987 Demand 260 265 295 1992 Demand 285 315 360 2002 Demand 325 405 490 Formulation of the Supply Plans To meet the projected energy demand,a base case and four alternative supply plans were formulated to examine the relative eneryy costs and environmental and socioeconomic impacts.With- in each alternative,subplans are also formulated to meet the combinations of electrical and total eneryy demand.The plans are representative of mixes of supply modes for meeting end-use demands. The four alternatives to the base case include coal direct combustion for meeting all the heating demand.A general de- scription of each supply plan is given in the followiny para- graphs. I.Base Case,The base case plan represents a continua- tion of the present practices of diesel generation for electricity.The base case plan also assumes the continued use of fuel oil for residential and non-residential heatiny needs.No new trasmission interties are included in the Base Case. II.Base Case Alternatives.The base case alternatives will utilize the diesel units as described in the base case,with inclusion of wind electric generation,waste heat recovery,and coal direct combustion for heating demand.A regional and sub-reyional transmission interties XII-1l were also evaluated.The optimization of the base case alternatives is given in the next section. For consistency between all alternative supply plans,it was assumed that the conversion to coal direct combusion would be in 1988,the same year as the coal fired plant would be in operation.All existing residential and non- residential systems would be converted to burn coal for heating. III.Thermal Alternatives.Five sub-plans were formulat- ed,including a 4-MW or a 10-MW coal-fired plant,located in Bethel.Transmission interties to the outlyiny villages were also considered for each of the five plans.The re- sults of the economic feasibility to intertie Tuluksak is presented in the following section. Supply Plan IIIA would consist of a 4-MW base load plant Supplemented by diesel generators to meet the peak demand. The heating demand in Bethel and the villages would be met by fuel oil until 1988 then coal direct combusion as de- scribed in the Base Case Alternatives. Supply Plan IIIB would consist of the same 4-MW base load plant with waste heat recovery that would supply about 25 percent of the heating demand in Bethel,The remaining heating demand would be met as in Plan IIIA. Supply Plan IIIC would consist of a 10-MW cycling plant that would generate the electric energy demand.The heat- ing demand would be met as in Plan IIIA. Supply Plan IIID would consist of the same 10-MW plant with waste heat recovery that would supply 62 percent of the heating demand in Bethel.The remaining heating demand would be met as in Plan IIIA. Supply Plan IIIE would also consist of a 10---MW plant with a supplemental boiler to supply about 80 percent of the total heatiny demand of Bethel.The remaining heating demand would be met as in Plan IIIA. IV.Hydroelectric Alternatives.Two sub-plans were formu- lated from the Chikuminuk Lake development,as described in Chapter IV.The 9.5-MW project (Plan IVA)was sized to meet the monthly electric energy requiremnets of the Bethel region through year 2002.The average annual energy pro- duction would be 60 GWh,or about 21 GWh more than the projected electric energy demand in 2002,under the most likely projections.That average surplus of energy would XII-12 meet about 7%of the total heating requirements of Bethel, in year 2002,The second plan (Plan IVB)consists of a development that approaches the topographic limits of the site.The 24-MW project would produce an average annual energy of 120 GWh.This development would meet the pro- jected electric energy demand and about 27%of the heating requirements of Bethel,in year 2002.In both plans,the remaining heating demand would be met by coal direct com- bustion,as in Plan ITIA. Both supply plans include a high voltage transmission line from Chikuminuk Lake to Bethel via Kwethluk and Akiachak. Additional transmission interties to the other village were also considered.The economic feasibility of interconnect- ed Tuluksak is presented in the following section. V.Fuel Cell Alternatives.Two fuel cell alternative plans were formulated.Both plans include a centralized 9-MW fuel cell electric generation plant,located in Bethel.The difference between the alternatives is that one plant (Plan VB)is designed for waste heat recovery, which could provide an estimated 12%of the heating demand in Bethel.The remaining heating demand would be met by coal direct combustion.As with the other plans,transmis- sion interties to Tuluksak were considered. The basic assumptions and cost estimates underlying each supply plan are given in the Regional Report. Economic Evaluation The economic parameters and assumptions used in the evalua- tion are based on the Power Authority guidelines (Economic Para- meters for the 1983 Fiscal Year).The economic analysis is done for the period starting in 1982 and ending in 2039,the last year of the 50-year economic life of the hydro project which would come on line in 1990.All costs are in terms of 1982 dollars.Petroleum fuels and coal are escalated at a real rate of 2.5 and 2.0 percent respectively,over the next twenty years. After year 2002,real escalation rates and load growths are assumed to be zero.A discount rate of 3.5 percent is used to calculate the present worth of costs occurring in different years on an equivalent basis. The present worth calculations were done according to the Power Authority evaluation procedure.The costs are busbar costs and do not include cost allowances for distribution,ad- ministration,taxes,etc.The present worth of consumer costs would be significantly higher than the present worth of busbar costs developed in this evaluation.However,since these addi- XII-13 tional costs are the same for all alternatives,the relative ranking of the alternatives would not be affected. Using the timing of capacity additions and costs presented in the Regional Report,the present worth of costs for each supply plan was computed.Table XII-7 summarizes the present worth of each supply plan for Tuluksak.The present worth com- putation was done separately for the heating demand and electric demand.Electric demand includes the costs associated with generation facilities and transmission interties. Table XII-7 MOST LIKELY SCENARIO PRESENT WORTH AND BENEFIT-COST RATIO OF THE SUPPLY PLANS Total Demand Benefit-Cost RatioPresentWorth(1982$x103)With With Heating Electric Total Base Optimized Supply Plan Demand Demand Demand Case Base Case Base Case Plan I 8,180 3,927 12,107 1.00 - Optimized Base Case Plan II 5,835 3,927 9,762 1,24 1,00 Thermal Plans Plan IIIA 5,835 3,927 9,762 1,24 1.00 Plan IIIB 5,835 3,927 9,762 1.24 1.00 Plan IIIC 5,835 3,927 9,762 1,24 1,00 Plan IIID 5,835 3,927 9,762 1.24 1.00 Plan IIIE 5,835 3,927 9,762 1.24 1,00 Hydroelectic Plans Plan IVA 5,835 3,927 9,762 1.24 1.00 Plan IVB 5,835 3,927 9,762 1,24 1.00 Fuel Cell Plans Plan VA 5,835 3,927 9,762 1.24 1,00 Plan VB 5,835 3,927 9,762 1.24 1.00 The following paragraphs describe the results for Tuluksak under each supply plan.A regional summary is presented at the end of this section, XII-14 Base Case Supply Plan The present worth of the Base Case using diesel plants for electric yeneration and fuel oil tor heating was first computed to serve as a reference,As shown on Table XII-7,the total present worth of the Base Case is $12,107,000,of which $3,927,000 is for electric energy demand, Optimized Base Case Supply Plan The Base Case Alternatives were optimized based on an eval- uation of coal direct combustion,wind generation,waste heat recovery,and transmission intertie.As described in the Regional Report,the analysis shows that conversion to coal direct combustion for heating would provide significant economic benefit.Under the Most Likely Scenario,assuming a complete conversion to coal direct combustion by 1988,the present worth of the heating costs would be reduced by atout $2,345,000 (in 1982 dollars)over the period 1988-2039.Wind generation was only found to be economically feasible in the villages of Eek and Tuntutuliak.Diesel waste heat recovery was not found to be economically attractive when it is compared to coal heating. Transmission intertie to Bethel or a sub-regional transmission intertie between Akiachak,Akiak,Kwethluk,and Tuluksak was not found to be economically feasible. As shown on Table XII-7,the total present worth of the Optimized Base Case is $9,762,000.The benefit-cost ratio is 1.24 when compared to the Base Case.The present worth of the electric energy demand is identical to the Base Case.The present worth of the heating demand was reduced from $8,180,000 to $5,835,000. Thermal Supply Plans As for the Optimized Base Case,an economic evaluation was performed to decide whether or not Tuluksak should be intertied to Bethel,site of the coal-fired plant.To reflect the share of construction cost for the central coal-fired plant in the present worth computation of each village,an incremental unit cost of $1,500 per kilowatt was used.This unit incremental cost was multiplied by the projected villaye peak demand in year 2002 to estimate the construction cost associated with that village. As shown in Exhibit 38 of the Regional Report,the present worth of the electric energy demand,with an intertie to Bethel, is much yreater than the present worth of the Base Case.As a result,it is not economically feasible to intertie Tuluksak, XII-15 The present worth is then equal to the present worth of the Optimized Base Case. Hydropower Supply Plans An economic evaluation of the intertie to Tuluksak was done,using an incremental hydroelectric construction cost of $3,000 per kilowatt.As shown on Exhibit 38 of the Regional Report,the present worth of the electric demand which includes the intertie is much greater than the present worth of the Base Case.As a result,it is not economically feasible to intertie Tuluksak. Fuel Cell Supply Plans An incremental construction cost of $1,000 per kilowatt was used for the economic evaluation of village interties.As shown on Exhibit 38 of the Regional Report,the present worth of the electric demand which includes the intertie is much greater than the present worth of the Base Case.As a result,it is not economically feasible to intertie Tuluksak,. Sensitivity Analysis The timing and rate of conversion from fuel oil to coal or electric heat to meet the heating demand would directly affect the value of ali supply plans,except the Base Case.For the purpose of the economic analysis,we assumed a 100 percent con- version in 1988 to coal direct combustion for space heating. But,actually,the conversion would be more proyressive.AS a result,the present worth of all alternative supply plans to the Base Case would increase,thereby reducing the difference with the Base Case. A sensitivity analysis was first performed to analyze the impacts of fuel escalation rates,The same supply plans were reevaluated using 0%real fuel escalation for fuel oil and coal. The results are summarized in Table XII-8. XII-16 Table XII-8 MOST LIKELY SCENARIO SENSITIVITY ANALYSIS USING 0%REAL FUEL ESCALATION Total Demand Benefit-Cost RatioPresentWorth(1982$x103)With With Heating Electric Total Base Optimized Supply Plan Demand Demand Demand Case Base Case Base Case Plan I 5,662 3,070 8,732 1.00 - Optimized Base Case Plan II 4,532 3,070 7,602 1.15 1,00 Thermal Plans Plan IIIA 4,532 3,070 7,602 1,15 1.00 Plan IIIB 4,532 3,070 7,602 1.15 1.00 Plan IIIc 4,532 3,970 7,602 1.15 1.00 Plan IIID 4,532 3,070 7,602 1.15 1.00 Plan IIIE 4,532 3,070 7,602 1.15 1.00 Hydroelectric Plans Plan IVA 4,532 3,070 7,602 1.15 1.00 Plan IVB 4,532 3,070 7,602 1.15 1.00 Fuel Cell Plans Plan VA 4,532 3,070 7,602 1.15 1.00 Plan VB 4,532 3,070 7,602 1.15 1.00 Table XII-8 shows that the benefit-cost ratio of the Opti- mized Base Case has decreased from 1.24 to 1.15,if there is no real escalation in fuel cost.The reduction in heating cost, assuming a complete conversion to coal direct combustion by 1988,has decreased from $2,345,000 to $1,130,000, Another sensitivity analysis was performed to analyze the impacts of the low and high projections of energy demand.Simi- lar supply plans using a 4-MW and 10-MW coal-fired plant,9-MW hydroelectric plant,and a 9-MW fuel cell plant were analyzed. The analysis was done using a 2.5%real escalation for fuel oil, and 2.0%for coal until year 2002.The results are presented in Table XII-9. XII-17 81T-IIxXTable XII-9 SENSITIVITY ANALYSIS PRESENT WORTH OF SUPPLY PLANS Low Scenario (1982 $x103) Most Likely Scenario High Scenario Heating Electric Total Heating Electric Total Heating Electric TotalSupplyPlanDemandDemandDemandDemandDemandDemandDemandDemandDemand Base Case Plan I 6,900 3,338 10,238 8,180 3,927 12,107 9,175 4,575 13,750 Optimized Base Case Plan II 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Thermal Plans Plan IIIA 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan IIIB 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan IIIC 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan IIID 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan IIIE 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Hydroelectric Plans Plan IVA 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan IVB 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Fuel Cell Plans Plan VA 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Plan VB 5,052 3,338 8,390 5,835 3,927 9,762 6,467 4,575 11,042 Under the Low Scenario,the conversion to coal-direct com- bustion for heating demand would still provide substantial sav- ings,assuming a 100%percent conversion in 1988.Under theHighScenario,it would still not be economically feasible to intertie Tuluksak to any regional supply plan. Regional Summary The regional analysis for Bethel and the twelve surrounding villages shows that conversion to coal direct combustion for heating would provide significant economic benefit.Under the Most Likely Scenario,assuming a complete conversion to coal direct combustion by 1988,the present worth of the heating costs would be reduced by about 30%or $169 million (in 1982 dollars)over the period 1988-2039,Wind generation was only found to be economically feasible in the villages of Eek and Tuntutuliak.Diesel waste heat recovery was not found to be economically attractive in the villages when it is compared to coal heating.Transmission interties to the outlying villages are only economically attractive under the Hydroelectric Supply Plans where the cost of electric generation (fuel and operation and maintenance costs)are negligible. Table XII-10 shows the ranking of the energy supply plans under the Low,Most Likely,and High Scenarios.The first part of the table shows the ranking under the total demand,including both the heating and electric demand.Under the Low Scenario, only the Fuel Cell Supply Plan with waste heat recovery (Plan VB)is more attractive than the Optimized Base Case.Under the Mostly Likely and High Scenarios,the Hydroelectric Supply Plans are the most attractive.Assuming no real fuel escalation over the period 1982-2039,the Optimized Base Case is the best plan, The second part of the table shows the ranking under the electric demand.Under the Most Likely Scenario,with real fuel escalation during the period 1982-2001,the Hydroelectric Supply Plans are the only plans which have a present worth lower than the Optimized Base Case.Under the Most Likely Scenario with no real fuel escalation,the Base Case Supply Plan has the lowest present worth. Environmental Evaluation A detailed description of the environmental impact,cost, or risk that may occur with each of the technologies associatedwiththeselectedenergysupplyplansisgivenintheRegional Report, XII-19 Oc-IIXTable XII-10 RANKING OF ENERGY SUPPLY PLANS Total Demand Electric Demand With Fuel Escalation*Without F.E.With Fuel Escalation*Without F.E. Low Most Likely High Most Likely Low Most Likely High Most Likely Supply Plans Scenario Scenario Scenario Scenario Scenario Scenario Scenario Scenario Base Case Plan I ll ll 11 10 1 3 4 1 Optimized Base Case Plan II 3 5 6 1 2 2 3 2 Thermal Plans Plan IIIA 7 7 7 6 5 5 5 4 Plan IIIB 5 4 4 4 5 5 5 4 Plan IIIC 9 9 9 9 6 6 6 6 Plan IIID 8 7 8 8 6 6 6 6 Plan IIIE 10 10 10 11 6 6 6 6 Hydroelectric Plans Plan IVA 2 2 2 3 4 1 1 5 Plan IVB 3 1 1 7 4 1 1 5 Fuel Cell Plans Plan VA 6 6 5 5 3 4 2 3 Plan VB 1 3 3 2 3 4 2 3 *Assumes 2.5%real escalation rate for fuel oil and 2.0%for coal during the period 1982-2001.No escalation rates are assumed after 2001. Environmentally,the Base Case is probably the most desir- able of all the selected supply plans.No transmission lines would be used.The small separate generating systems located throughout the region would not create any large impact.Envi- ronmental drawbacks to the Base Case are the potentials for spill and fire hazard involved in fuel handling and storage. Due to the use of coal for space heating,the supply plan alternatives would be less desireable than the Base Case.Run- off and dust from storage piles,combustion emissions,and ash disposal will all impact the environment to a certain degree, and the public acceptance to coal for space heating is yet to be determined. Other key environmental constraints involve impacts of the hydroelectric project operation on aquatic and terrestrial re- sources,and impacts of the transmission lines on birds and access to subsistence, XII-21 rE XHIBITetn MopSows°T ©a@Nunapitchuk3)>as sy oft S°q°\Atmautluak |4g ares ee22”0,8Napaskiak >Napakiak s.r &"SS 9 >by,'Et) ¢ ' war)rel ALASKA POWER AUTHORITY MILES BETHEL AREA POWER PLAN IBILITY MENi RBANK 04 Bn 16 20 FEASIBILITY ASSESSMENT - i a ee | BETHEL ANCHORAGE SCALE 1:1,000,000 COMMUNITY LOCATION MAP s See '3 JUNEAU K MAP HARZA ENGINEERING COMPANY Le EY MA* December 1982 Exhibit 2 TULUKSAK POPULATION HISTORICAL DATA,PROJECTIONS,ANNUAL GROWTH RATES Year 1950 1960 1970 1980 Year 1980 Annual Growth Rate: 1987 Annual Growth Rate: 1992 Annual Growth Rate: 2002 HISTORICAL DATA Annual Population Growth Rate (%) 116 1.7 137 3.6 195 1.9 236 PROJECTIONS Most Low Likely High 236 236 236 1.13%1.253%1.53% 255 257 262 1.0%1.253%1.53% 267 276 283 0.5%0.65%1.13% 281 295 316 BETHEL ARFA POWER STUDY FORECAST 1981 PROFILE,Tuluksak,Alaska Elect-Space Water Light &SECTOR Income Emplymt ricity Cooking Heating Heating Applianwoeeecoe----($000)---(No.)=--=<(Million Btu)a eateateees COMMERCIAL Renew.Res.Harvest 48 4 0 0 0 0 0 Mining &Exploration 0 0 0 0 0 0 0 Construction 259 22 0 0 0 0 0 Household Mfq.4 1 0 0 0 0 0 Transportation 9 1 0 0 40 0 0 Wholesale,Dist.4 0 1 0 25 0 1 Comm.and Utilities 29 2 0 0 0 0 0 Trade &Pvt.Service 84 7 20 0 437 0 20 Finance &Real Est.30 2 2 0 82 0 2 GOVERNMENT Non-Profit Org.16 1 11 0 109 97 11 Local &Reg.Govt.512 31 326 0 7208 1231 326 State Agencies/Svcs 9 1 3 0 63 0 3 Fed.Agencies/Svcs 35 3 1 0 79 0 1 ***Transfer Payments 489 TOTAL 1528 75 364 0 8043 1328 364 RESIDENTIAL Population (No.persons)236 Household Size 5.6 Total Households 42 Usage Rate (M.Btu/household)130 Total Res.Demand (M.Btu)421 2840 2294 109 218 TOTAL ENERGY (M.Btu)785 2840 10337 1437 582 €LIGIHX3 BETHEL AREA POWER STUDY FORECAST MOST-LIKELY Projection 10/15/82 SECTOR COMMERCIAL Renew.Res.Harvest Mining &Exploration Construction Household Mfg. Transportation Wholesale,Dist. Comm.and Utilities Trade &Pvt.Service Finance &Real Est. GOVERNMENT Non-Protit Org. Local &Reg.Govt. State Agencies/Svcs Fed.Agencies/Svcs ***Transfer Payments RESIDENTIAL 1987 FORECAST,Tuluksak,Alaska Population (No.persons) Household Size Total Households Usage Rate (M.Btu/household) Total Res.Demand (M.Btu) Elect=-Space Water Light &Income Emplymt ricity Cooking Heating Heating Applian($000)---(No.)--(Million Btu)-- 49 4 0 0 0 0 0 0 0 0 0 0 0 0 262 22 0 0 0 0 0 4 1 0 0 0 0 0 9 1 0 0 41 0 0 4 0 1 0 26 0 1 30 2 0 0 0 0 0 79 7 19 0 409 0 19 28 2 2 0 78 0 2 15 1 11 0 103 92 11 487 29 310 0 6849 1170 310 ll 1 4 0 70 0 4 22 2 1 0 48 0 1 416 1416 72 348 0 7624 1262 348 257 5.3 48 151 562 3795 3065 146 292 910 3795 10689 1408 640TOTALENERGY(M.Btu)6}0|abegbvLIGIHX3 BETHEL AREA POWER STUDY FORECAST MOST-LIKELY Projection 10/15/82 1992 FORECAST,Tuluksak,Alaska Elect- SECTOR Income Emplymt ricity Cookingacesheenheeteteaatetetens($000)---(No,)enwe nn nn =(Mill COMMERCIAL Renew.Res.Harvest 54 4 0 0 Mining &Exploration 0 0 0 0 Construction 291 24 0 0 Household Mfq.4 1 0 0 Transportation 10 1 0 0 Wholesale,Dist.4 0 2 0 Comm.and Utilities 33 2 0 0 Trade &Pvt.Service 88 8 21 0 Finance &Real Est.31 2 2 0 GOVERNMENT Non-Protit Org.16 1 11 0 Local &Reg.Govt.593 36 378 0 State Agencies/Svcs 11 1 4 0 Fed.Agencies/Svcs 22 2 1 0 *k*eTransfer Payments 440 TOTAL 1597 82 419 0 RESIDENTIAL Population (No.persons)276 Household Size 52 Total Households 53 Usage Rate (M.Btu/household)163 Total Res.Demand (M.Btu)662 4473 TOTAL ENERGY (M.Btu)1081 4473 Space Water Light & Heating Heating ApplianionBtu)ened 0 0 0 0 0 0 0 0 0 0 0 0 45 0 0 28 0 l 0 0 0 456 0 21 87 0 2 110 98 11 8342 1425 378 75 0 4 48 0 1 9191 1523 418 3613 172 344 12804 1695 762 6$0zebeygyLISIHX3. BETHEL AREA POWER STUDY FORECAST MOST-LIKELY Projection 10/15/82 2002 FORECAST,Tuluksak,Alaska Elect-Space Water Light & SECTOR Income Emplymt ricity Cooking Heating Heating Applianooo---($000)---(No.)=(Million Btu)--- COMMERCIAL Renew.Res.Harvest 60 5 0 0 0 0 0 Mining &Exploration 0 0 0 0 0 0 0 Construction 325 27 0 0 0 0 0 Household Mfq.5 1 0 0 0 0 0 Transportation 12 1 0 0 52 0 0 Wholesale,Dist.5 1 2 0 32 0 1 Comm.and Utilities 39 3 0 0 0 0 0 Trade &Pvt.Service 100 9 24 0 518 0 24 Finance &Real Est.37 3 3 0 104 0 3 GOVERNMENT Non-Profit Org.22 2 15 0 146 130 15 Local &Reg.Govt.671 41 428 0 9450 1614 428 State Agencies/Svcs 14 1 5 0 90 0 5 Fed.Agencies/Svcs 30 2 1 0 67 0 1 ***Transfer Payments 577 TOTAL 1897 96 478 0 10459 1744 477 RESIDENTIAL Population (No.persons)295 Household Size 4.5 Total Households 66 Usage Rate (M.Btu/household)179 Total Res.Demand (M.Btu)903 6097 4925 235 469 TOTAL ENERGY (M.Btu)1381 6097 15384 1979 946 6}0€ofegvLIGIHX3S BETHEL AREA POWER STUDY FORECAST LOW Projection 10/15/82 SECTOR COMMERCIAL Renew.Res.Harvest Mining &Exploration Construction Household Mfg. Transportation Wholesale,Dist. Comm.and Utilities Trade &Pvt.Service Finance &Real Est. GOVERNMENT Non-Profit Org. Local &Reg.Govt. State Agencies/Svcs Fed.Agencies/Svcs **keTransfer Payments RESIDENTIAL 1987 FORECAST,Tuluksak,Alaska Population (No.persons) Household Size Total Households Usage Rate (M.Btu/household) Total Res.Demand (M.Btu) Elect-Space Water Light & Income Emplymt ricity Cooking Heating Heating Applian($000)-- (No.)-aie (Million Btu)--- 47 4 0 0 0 0 0 0 0 °0 0 0 0 0 258 22 0 0 0 0 0 4 1 0 0 0 0 0 9 1 0 0 38 0 0 4 0 1 0 25 0 1 26 2 0 0 0 0 0 75 7 18 0 388 0 18 26 2 2 0 72 0 2 13 1 9 0 84 75 9 474 29 302 0 6671 1139 302 8 1 3 0 53 0 3 22 2 1 0 48 0 1 367 1333 72 336 0 7379 1214 336 255 53 48 147 542°3663 2958 141 282 878 3663 10337 1355 618TOTALENERGY(M.Btu)6JO+o6egvyLISIHX3 BETHEL AREA POWER STUDY FORECAST LOW Projection 10/15/82 1992 FORECAST,Tuluksak,Alaska Elect-Space Water Light &SECTOR Income Emplymt ricity Cooking Heating Heating Applianandesite($000)---(No.)mmm nnn nnn nn =(Million Btu)----<-------------- COMMERCIAL Renew.Res.Harvest 51 4 0 0 0 0 0 Mining &Exploration 0 0 0 0 0 0 0 Construction 265 22 0 0 0 0 0 Household Mfg.4 1 0 0 0 0 0 Transportation 9 1 0 0 40 0 0 Wholesale,Dist.4 0 1 0 27 0 1 Comm.and Utilities 31 2 0 0 0 0 0 Trade &Pvt.Service 81 7 19 0 419 0 19 Finance &Real Est.27 2 2 0 76 0 2 GOVERNMENT Non-Profit Org.14 1 10 0 93 82 10 Local &Reg.Govt.517 31 330 0 7282 1244 330 State Agencies/Svcs 9 1 3 0 59 0 3 Fed.Agencies/Svcs 16 1 0 0 36 0 0 **eTransfer Payments 367 TOTAL 1395 73 365 0 8032 1326 365 RESIDENTIAL Population (No.persons)267 Household Size 562 Total Households 51 Usage Rate (M.Btu/household)156 Total Res.Demand (M.Btu)614 4148 3350 160 319 TOTAL ENERGY (M.Btu)979 4148 11382 1486 684 630GabegvyLIGIHX3 BETHEL AREA POWER STUDY FORECAST LOW Projection 10/15/82 2002 FORECAST,Tuluksak,Alaska Elect Space Water Light & SECTOR Income Emplymt ricity Cooking Heating Heating Applianheaieshenienieteaieieaieeieteaietarieteniaiaes -=($000)---(No .)men ennnn--nH (Million Btu)e------------------COMMERCIAL Renew.Res.Harvest 58 5 0 0 0 0 0 Mining &Exploration 0 0 0 0 0 0 0 Construction 336 28 0 9 0 0 0 Household Mfg.4 1 0 0 0 0 0 Transportation 11 1 0 0 46 0 0 Wholesale,Dist.-5 0 2 0 31 0 1 Comm.and Utilities 34 2 0 0 0 0 0 Trade &Pvt.Service 87 8 21 0 451 0 21 Finance &Real Est.30 2 2 0 82 0 2 GOVERNMENT Non-Profit Org.15 1 1l 0 103 92 ll Local &Reg.Govt.537 32 342 0 7552 1290 342 State Agencies/Svcs 9 1 3 0 59 0 3 Fed.Agencies/Svcs 16 1 0 0 36 0 0 **kTransfer Payments 367 TOTAL 1509 82 381 0 8360 1382 380 RESIDENTIAL Population (No.persons)281 Household Size 5 Total Households 56 Usage Rate (M.Btu/household)168 Total Res.Demand (M.Btu)723 4883 3944 188 376 TOTAL ENERGY (M.Btu)1104 4883 12304 1570 756 '6409afegvyLISIHXS BETHEL AREA POWER STUDY FORECAST HIGH Projection 10/15/82 1987 FORECAST,Tuluksak,Alaska Elect -Space Water Light & SECTOR Income Emplymt ricity Cooking Heating Heating Applian ---- ---($000)---(No.)---(Million Btu)-- COMMERCIAL Renew.Res.Harvest 54 4 0 0 0 0 0 Mining &Exploration 0 0 0 0 0 0 0 Construction 313 26 0 0 0 0 0 Household Mfq.7 1 0 0 0 0 0 Transportation ll 1 0 0 46 0 0 Whoiesale,Dist.4 0 l 0 28 0 1 Comm.and Utilities 35 2 0 0 0 0 0 Trade &Pvt.Service 93 8 22 0 482 0 22 Finance &Real Est.34 3 2 0 94 0 2 GOVERNMENT Non-Protit Org.18 1 12 0 120 107 12 Local &Reg.Govt.543 33 346 0 7645 1306 346 State Agencies/Svcs 11 1 4 0 72 0 4 Fed.Agencies/Svcs 41 3 1 0 90 0 1 *k*eTransfer Payments 563 TOTAL 1727 83 388 0 8577 1413 388 RESIDENTIAL Population (No.persons)262 Household Size 5 Total Househoids 52 Usage Rate (M.Btu/household)153 Total Res.Demand (M.Btu)617 4167 3365 160 321 TOTAL ENERGY (M.Btu)1005 4167 11942 1573 709 640ZobegvyLISIHXS BETHEL AREA POWER STUDY FORECAST HIGH Projection 10/15/82 SECTOR COMMERCIAL Renew.Res.Harvest Mining &Exploration Canstruction Household Mfq. Transportation Wholesale,Dist. Comm.and Utilities Trade &Pvt.Service Finance &Real Est. GOVERNMENT Non-Profit Org. Local &Reg.Govt. State Agencies/Svcs Fed.Agencies/Svcs ***eTransfer Payments RESIDENTIAL 1992 FORECAST,Tuluksak,Alaska Population (No.persons) Household Size Total Households Usage Rate (M.Btu/household) Total Res.Demand (M.Btu) TOTAL ENERGY (M.Btu) Elect Space Water Light & Income Emplymt ricity Cooking Heating Heating Applian($000)--=(No.)eee renee nen (Million Btu)-- - 65 5 0 0 0 0 0 0 0 0 0 0 0 0 376 31 0 0 0 0 0 10 2 0 0 0 0 0 12 1 0 0 53 0 0 5 1 2 0 33 0 1 43 3 0 0 0 0 0 108 9 26 0 559 0 26 39 3 3 0 107 0 3 19 1 13 0 126 112 13 667 40 425 0 9389 1604 425 12 1 4 0 80 0 4 46 3 1 0 102 0 1 587 1989 100 474 0 10449 1716 473 283 4.8 59 166 754 5090 4111 196 392 1228 5090 14560 1912 865 630gebegyLISIHX3 BETHEL AREA POWER STUDY FORECAST HIGH Projection 10/15/82 SECTOR COMMERCIAL Renew.Res.Harvest Mining &Exploration Construction Household Mfg. Transportation Wholesale,Dist. Comm.and Utilities Trade &Pvt.Service Finance &Real Est. GOVERNMENT Non-Protit Org. Local &Reg.Govt. State Agencies/Svcs Fed.Agencies/Svcs ***Transfer Payments RESIDENTIAL 2002 FORECAST,Tuluksak,Alaska Population (No.persons) Household Size Total Households Usage Rate (M.Btu/household)Total Res.Demand (M.Btu) Elect- Income Emplymt ricity Cooking ($000)---(No.)-(Mill 76 6 0 0 0 0 0 0 486 41 0 0 11 2 0 0 14 1 0 0 6 1 2 0 50 3 0 0 121 10 29 0 44 3 3 0 20 2 14 0 701 42 447 0 13 1 4 0 53 4 2 0 661 2256 116 501 0 316 4 79 194 1176 7939 1677 7939TOTALENERGY(M.Btu) Space Water Light & Heating Heating Applian ion Btu)=-cone 0 0 0 0 0 0 0 0 0 0 0 0 62 0 0 39 0 1 0 0 0 624 0 29 121 0 3 132 117 14 9867 1685 447 88 0 4 118 0 2 11051 1802 500 6413 305 611 17464 2107 1111 630&ebegyLISIHX3 Exhibit 5 1981 PRIMARY ENERGY CONSUMPTION,TULUKSAK Residential Sector Million Btu Lights &Appliances Electricity 218 Space Heating Fuel Oil 942 Wood 1,352 Water Heating Fuel Oil 62 Wood 47 Cooking Electricity 203 Fuel Oil 247 Wood 2,158 Propane/Blazo 232 Total 5,461 Commercial Sector Lights &Appliances Electricity 23 Space &Water Heating Fuel Oil 584 Total 607 Government Sector Lights &Appliances Electricity 341 Space &Water Heating Fuel Oil 8,787 Total 9,128 Equivalent Btu :kilowatt- hour =3,413,Btu gallon of fuel oil =136,000 Btu gallon of blazo =136,000 Btu 100-1lb bottle of propane =2,500,000 Btu cord of wood =13,000,000 Btuen a a ae stor oes ==-a mn a 7 ee ay ae " _ EXHIBIT 6 o q © 8 ELECTRIC 2DIESELN 8 GENERATION LIGHTS Were REJECTED ENERGY PROPANE /BLAZO COOKING wooD ?,SPACE / VeoY AND DbFUELOIL5 WATER USEFUL ENERGY o =_HEATING S La)ALASKA POWER AUTHORITY BETHEL AREA POWER PLAN FEASIBILITY ASSESSMENT 1981 ENERGY BALANCE(UNITS:MILLION Btu) TULUKSAK HARZA ENGINEERING COMPANY December 1982 EXHIBIT 7 POWER HOUSE a t ' PROPOSED SWITCH __,TyGEAR/GROUND GRID™'\U/ LOCATION PROPOSED RIGHT-OF-WAY TO TULUKSAK JUNCTION ALASKA POWER AUTHORITY BETHEL AREA POWER PLAN FEASIBILITY ASSESSMENTTULUKSNGELECTRICALDisteiaTinee”PPP ROM SceLe I FET ELECTRICAL DISTRIBUTION SYSTEMP.E.COMPANY ELECTRICAL ENGINEERS HARZA ENGINEERING COMPANY *.0.Box 4-2543 Anchorage,AlaskaPhone(907)276-3442 4 Beso9 December 1982