HomeMy WebLinkAbout2017 Diesel Published ArticleAn Alaska case study: Diesel generator technologies
Nathan Green, Marc Mueller-Stoffels, and Erin Whitney
Citation: Journal of Renewable and Sustainable Energy 9, 061701 (2017);
View online: https://doi.org/10.1063/1.4986585
View Table of Contents: http://aip.scitation.org/toc/rse/9/6
Published by the American Institute of Physics
Articles you may be interested in
Preface: Technology and cost reviews for renewable energy in Alaska: Sharing our experience and know-how
Journal of Renewable and Sustainable Energy 9, 061501 (2017); 10.1063/1.5017516
An Alaska case study: Electrical transmission
Journal of Renewable and Sustainable Energy 9, 061702 (2017); 10.1063/1.4986582
Wind power project size and component costs: An Alaska case study
Journal of Renewable and Sustainable Energy 9, 061703 (2017); 10.1063/1.4986579
An Alaska case study: Solar photovoltaic technology in remote microgrids
Journal of Renewable and Sustainable Energy 9, 061704 (2017); 10.1063/1.4986577
An Alaska case study: Energy storage technologies
Journal of Renewable and Sustainable Energy 9, 061708 (2017); 10.1063/1.4986580
An Alaska case study: Cost estimates for integrating renewable technologies
Journal of Renewable and Sustainable Energy 9, 061709 (2017); 10.1063/1.4986581
An Alaska case study: Diesel generator technologies
Nathan Green,Marc Mueller-Stoffels,and Erin Whitney
Alaska Center for Energy and Power, University of Alaska Fairbanks, P.O. Box 755910,
Fairbanks, Alaska 99775-5910, USA
(Received 6 June 2017; accepted 26 September 2017; published online 8 December 2017)
Diesel generators are the main source of electrical generation in remote Alaska
communities; they also help to maintain grid frequency and voltage. In an analysis
of key performance metrics for diesel generators in Alaska, we found that the size
of the installed system directly affects capital costs, that is, larger systems are more
cost-effective per kilowatt. However, appropriately sizing a system for a commu-
nity is more cost-effective overall than significantly oversizing the system.
Capacity factors range from below 5% to over 25%. The low values are typically
for diesel-hydroelectric hybrid systems, for which this measure is not entirely accu-
rate. In addition, rural diesel plants may have low capacity factors since typically
there are three to four generators in-house. These generators are sized so that one to
two generators provide power at any given time; the remaining generators are
available as backup. Generators of this size can be expected to operate for approxi-
mately 60000–100000h, with larger engine blocks tending to have longer life-
spans. An appropriately maintained generator operating for 35% of the time will
last approximately 20 years, or 60,000 hours. The technology continues to see
advances in power output, efficiency, noise reduction, and emission control. The
shapes of combustion chambers in newer engines are designed to maximize the
combustion rate of fuel, thus increasing output power and fuel efficiency. The
common-rail fuel system can maintain high pressure from the fuel tank to injection,
which allows for finer vaporization of fuel and more complete combustion. Nitrous
oxide can be reduced through exhaust gas recirculation and selective catalytic
reduction. Control systems have also seen advancement. Mechanical control sys-
tems have been slowly phased out in favor of electronic control systems, which
allow for offsite monitoring of a system and reduction in the number of necessary
service calls. Diesel generators in rural Alaska communities remain difficult to
maintain to the degree necessary for smooth operation. Additionally, supervisory
control and data acquisition systems with remote control capabilities require con-
tinuous Internet connection, which is not always available in rural communities.
Published by AIP Publishing.https://doi.org/10.1063/1.4986585
INTRODUCTION
In much of rural Alaska, as with other remote locations where microgrids serve a commu-
nity, diesel generators are often used as the grid prime mover, meaning that they are responsi-
ble for maintaining grid frequency and voltage. Due to the cost of diesel fuel, significant energy
cost savings revolve around reducing fuel consumption. The nameplate outputs of individual
generators installed in rural Alaska vary from about 30kW to over 1MW. The best diesel gen-
erator systems convert roughly 40% of diesel fuel energy content into electricity. The remaining
fuel energy is converted into heat.
Even in non-remote settings, microgrids (and diesel generators) are receiving increasing
attention as insurance against power disruptions. According to the Electric Power Research
Institute, outages alone are estimated to cost anywhere from $104 billion to $164 billion. As
severe weather events are predicted to increase, the number of outages related to these events
1941-7012/2017/9(6)/061701/11/$30.00 Published by AIP Publishing.9, 061701-1
JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY 9, 061701 (2017)
and their economic costs are expected to rise. In such systems, diesel generators can provide a
backbone for general operation and other energy generation contributions.
This review of diesel generator technologies in Alaska is a result of Alaska Senate Bill
(SB) 138. In this bill, the Alaska State Legislature created an uncodified section of law entitled:
“Plan and Recommendations to the Legislature on Infrastructure Needed to Deliver Affordable
Energy of the State to Areas That Do Not Have Direct Access to a (proposed) North Slope
Natural Gas Pipeline.” To support the Alaska Energy Authority (AEA) in its development of an
Alaska Affordable Energy Strategy, the Alaska Center for Energy and Power (ACEP) con-
tracted with AEA to document technology development needs specific to Alaska with regard to
renewable and sustainable energy technologies. The intention was to determine what targeted,
energy technology development solutions could be implemented in Alaska to make energy
more affordable in the Alaska Affordable Energy Study area. While the focus was on technol-
ogy research solutions, other factors such as logistics, labor, and training were also addressed.
This review specifically explores the lifetime cost of diesel generation. The other reviews
resulting from SB 138 address additional technologies as well as the integration of those tech-
nologies with existing diesel systems to form cogenerating hybrid systems. Drafts of technology
reviews were vetted by expert roundtables in late February and early March 2016.
These reviews are not meant to be exhaustive discussions of energy technologies in Alaska
or proper designs for each technology, and they should not be used as guides for the choice
and installation of specific systems. As such, not all possible issues with power production and
each technology are addressed. Data for each technology were collected from surveys and pub-
lically available databases. Only completed projects, or projects with clearly reported data,
were included in each technology analysis. These distinctions and descriptions of data sources
are included in each technology review.
METHODS
Data were collected from public sources. Installation costs were gathered from project
Financial Close-Out Reports at the Denali Commission Project Database website (2016).
Operation and maintenance (O&M) cost data were collected from the Regulatory Commission
of Alaska (RCA). The numbers for kilowatt-hours (kWh) generated were collected from Power
Cost Equalization data at the Alaska Energy Data Gateway website (2016). When relevant,
costs were adjusted for inflation using Consumer Price Index data listed on the Alaska
Department of Labor and Workforce Development website (2016).
DISCUSSION
Capital costs
Each of the projects evaluated for this review received a Rural Power System Upgrade
(RPSU) grant to replace existing diesel generation that has reached the end of its operational
lifetime. Many, but not all, of the grants included a heat recovery system, an intermediate fuel
tank, and/or a distribution upgrade, but the RPSU reports do not provide a cost breakdown to
discern those costs. Some projects were built in parallel with others, thereby reducing costs
compared to scenarios that have separate project completions. The cost categories include
freight, labor, materials, planning and design, administration and overhead, and others. A list of
communities examined, along with installed capacities and comments about the scope of the
RPSU projects, is shown in Table I of the Appendix. The scale of the installed system directly
affects capital costs, as shown in Fig.1. Larger systems are more cost-effective per kilowatt
although more expensive overall. Appropriately sizing a system based and current and projected
growth or contraction of a community is necessary and more cost-effective overall than oversiz-
ing the system beyond the community’s needs.
061701-2 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
Operation and maintenance
Operation and maintenance (O&M) represent the cost to keep a generator operational
throughout its expected life. Such costs include labor and materials for inspections, repairs, and
other tasks but exclude the cost of fuel. A model was developed by the AEA and modified by
ACEP to approximate O&M costs for three generator classes: 4 cylinders, 6 cylinders, and
8–16 cylinders. These categories generally correspond to rated power outputs of 60–150kW,
151–600kW, and 601–1300kW, respectively, although there is overlap. The three cost models
are shown in Fig.2. The assumed maintenance intervals used in the model are shown in Table
II of the Appendix. The duration of each maintenance task is based on manufacturer specifica-
tions and shown in Table III of the Appendix. In-house labor, which was assumed at $60/h,
includes wages, benefits, and overhead. Contracted labor was assumed at $120/h plus travel and
per diem. Price escalation was not taken into account in these calculations. Daily inspections
and oil changes were the dominant cost factors of O&M because these tasks must be done fre-
quently. The total O&M costs for each size category were normalized by the assumed number
of operating hours over the life of the engine: 60000h for 4- and 6-cylinder engines and
100000h for 8- to 16-cylinder engines. It was assumed that the generators were operating with
a load factor that was 55% of nameplate capacity on average.
The cost per kilowatt-hour, shown in Fig.2, decreases as the size of installed capacity
increases because the load factor remains constant. However, for a given load, larger machines
are more costly to operate (overall and per kWh), which illustrates the importance of right-
sizing generators for the expected demand.
FIG. 1. Capital costs (2014 $) of RPSU diesel systems normalized by installed capacity. Larger systems are more cost-
effective per kW; however, appropriately sizing a system for a community is more cost-effective overall than significantly
oversizing the system.
FIG. 2. Operations and maintenance costs per kWh from calculated models and RCA data. According to the model, O&M
costs per kWh decrease as the generator size increases for a constant load factor (not a constant load). According to RCA
data, O&M costs per kWh are nearly flat for power plants ranging from 200 to 1500kW.
061701-3 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
The cost to operate a single generator does not necessarily scale with the cost to operate an
entire powerhouse. Operations and maintenance cost data were collected from the Regulatory
Commission of Alaska (RCA) for the communities seen in Table IV of the Appendix. The val-
ues include personnel costs, routine O&M, generator repairs, and other operating expenses;
they do not include office expenses, debt, insurance, depreciation, interest, and other administra-
tive costs. The values are plotted in Fig.2 along with the O&M cost model. The RCA data
indicate that O&M costs are relatively flat across different-sized plants as opposed to the O&M
model, which indicates an inverse relationship. There may be factors not fully understood from
the available dataset which contribute to power plant level O&M, causing the costs to differ
from generator level O&M.
Levelized cost of electricity (LCOE)
The levelized cost of electricity (LCOE) was determined by dividing the expected total
cost of a system over its lifetime by the expected total kilowatt-hours. To calculate lifetime
kilowatt-hours generated, we assumed that the generators in each community operated for
60000h with an average load factor of 55% of nameplate capacity. The costs for a diesel pow-
erhouse included fuel, O&M, and initial capital costs. Administrative costs were not included,
as they were not tracked at the level of detail necessary to separate general utility administra-
tion from specific diesel-related costs. Capital cost data were gathered from the Denali
Commission and the Alaska Energy Authority RPSU projects. Regulatory Commission of
Alaska data was used for O&M costs because the model discussed in the Operation and
Maintenance section broke down when scaled from an individual generator to an entire power-
house. The fuel costs were calculated by assuming an efficiency of 12kWh/gal of diesel and
lower and upper cost boundaries of $3/gal and $7/gal. These assumptions yielded fuel costs
ranging from 0.25 to 0.58 $/kWh.
In reality, fuel costs vary significantly by community and over time. A full economic anal-
ysis and projection of diesel fuel prices are beyond the scope of this report. The range of calcu-
lated LCOE values is shown in Fig.3. Fuel represents 30%–50% of total LCOE under the $3/
gallon assumption and 50%–80% of total LCOE under the $7/gal assumption. Fuel represents a
significant portion of LCOE, and its cost varies the most, which makes cost projections over
the lifetime of a project difficult without specifying a range of potential fuel prices.
Calculated LCOE values are similar to but not the same as residential rates (before power
cost equalization adjustment) in these communities because residential rates are calculated
based on administrative, O&M, and fuel costs. Generally, RPSU project capital expenses are
paid for by the Denali Commission and other grants, rather than by the community or local
FIG. 3. Levelized cost of electricity by installed capacity for two different fuel cost assumptions. Fuel represents a signifi-
cant portion of LCOE, and its cost is highly variable, making it difficult to accurately predict lifetime costs for generating
diesel electricity without accurate fuel cost models.
061701-4 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
utility. The levelized cost of electricity calculations represents the full cost of generation, not
the cost of delivery for the utility.
Conditions for greatest efficiency
The efficiency of diesel generators is often reported as the number of kilowatt-hours gener-
ated per gallon of fuel. Typical values for generators used in Alaska are 11–15kWh/gal.
Generators tend to have poor efficiency when lightly loaded, but efficiency plateaus at around
half the rated load and above. The steady-state efficiency of a diesel generator can be deduced
from fuel consumption (gal/h) curves. Oversizing generators leads to poor efficiencies and an
increase in total costs when compared to generators operating near rated output. Unfortunately,
not all generators in a powerhouse can maintain a fixed output due to varying loads. Control
schemes are often employed within power plants to provide the most cost-efficient combination
of generators for a given load.
Installation of auxiliary equipment can also affect efficiency. Heat is generated during the
non-ideal adiabatic compression of the cylinder air charge. After-coolers help to remove this
heat, which allows fuel to combust more completely. Also, poor fuel quality can lead to incom-
plete combustion and decreased efficiency. Filters and other emission-control devices reduce
the output of nitrogen oxide (NOx) and particulates but typically decrease overall efficiency.
Costs over time
In order to track the change in installation costs over time, the effect of the power plant
size must be taken into account. The installation cost ratio of each project was calculated rela-
tive to the cost curve. A value of 1 indicates that the project cost lies directly on the cost curve.
A value of 2 indicates that the project cost is double the curve. Installation cost ratios are plot-
ted over time in Fig.4. No trend is noticeable over the time for which installation cost data are
available. However, it is expected that costs increase over a longer period due to increased
emission standards and other regulatory drivers. Certain increased emission standards saw
national implementation beginning in 2007. Alaskan communities, however, received exemp-
tions and delayed implementation until 2014 which is outside the date range of the RPSU data-
set. The regulations are discussed further in the Technology and Regulatory Trends section
below.
Transportation
Project materials must be transported through Anchorage. Locations closer to Anchorage
and barge routes tend to have lower costs associated with transportation, but the distance to the
nearest hub is not the only factor. Even within established Alaskan regions, towns and villages
may not be comparably accessible. Communities that require equipment to be delivered via ice
FIG. 4. Installation cost ratio relative to the cost curve of Fig.1 by year. There is no significant trend over the time for
which installation cost data are available.
061701-5 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
road or air have much higher freight costs. Unfortunately, there is not a sufficient definition of
remoteness to perform a rigorous analysis of transportation costs. Additionally, any existing
trend will be less discernable from statistical noise after breaking up the dataset by regions.
Expected life
The nameplate outputs of individual generators installed in rural Alaska vary from about
30kW to over a megawatt. Generators of this size can expect to operate 60000–100000h, with
larger engine blocks tending to have longer lifespans. An appropriately maintained generator
operating for 60000h 35% of the time will last approximately 20years. However, the lifetime
of an individual generator does not necessarily match the lifetime of the powerhouse because
generators and other components can be replaced without rebuilding the powerhouse.
Capacity factor
The capacity factor of a diesel powerhouse is calculated by dividing the number of
kilowatt-hours generated by the number of kilowatt-hours the powerhouse would generate if
each of its generators were running at full capacity. The number of kilowatt-hours generated
was collected from Power Cost Equalization data on the Alaska Energy Data Gateway website.
The capacity factors for the RPSU projects are shown in Fig.5. Systems with a mixture of die-
sel and other sources are differentiated from systems that only use diesel generators.
Rural diesel plants typically have three to four generators in-house. The diesel plants are
sized so that one or two generators provide power at any given time; the remaining generators
are available as backup. The operating generators are not necessarily running at a full rated
load.
There are several examples in Fig.5 for hybrid systems before and after the addition of a
wind or hydroelectric resource. For diesel-hydroelectric hybrid systems, it appears that the
capacity factor of the diesel plants drops significantly after hydroelectric power is added. The
trend is less clear for the addition of wind power. This is likely due to the relative predictability
of hydroelectric power compared to wind. Since the changes in river flow occur more gradually
than wind flow, a larger portion of the grid can be reliably supported by the hydroelectric tur-
bines. Wind is intermittent by nature, and therefore, wind turbines should be sized more conser-
vatively in order to reduce extreme swings without storage to compensate. Furthermore, hydro-
electric turbine generators can operate synchronously, meaning that they can maintain a grid
with diesels turned off. Wind turbine generators cannot do so without energy storage and addi-
tional infrastructure.
FIG. 5. Capacity factor of diesel power plants by installed capacity. Rural power plants have low capacity factors because
at any given time, most generators are not running.
061701-6 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
Technology and regulatory trends
Diesel engines have been in use for over a hundred years, yet, the technology continues to
see advances in power output, efficiency, noise reduction, and emission control. The shapes of
combustion chambers in newer engines are designed to maximize the combustion rate of fuel,
thus increasing output power and fuel efficiency. Common-rail fuel systems can maintain high
pressure from the fuel tank to injection. High pressure consequently allows for finer vaporiza-
tion of the fuel and thus more complete combustion.
Nitrous oxide (NOx) is caused by high combustion temperatures in an oxygen-rich environ-
ment; NOx can be reduced through exhaust gas recirculation. This process lowers the adiabatic
flame temperature and increases the heat capacity of the air mixture in the combustion cham-
bers, allowing for combustion at a much lower temperature. Another method of NOx reduction,
selective catalytic reduction (SCR), passes the exhaust through a reducing catalyst such as
ammonia or urea to convert NOx into diatomic nitrogen and water.
Control systems have also seen advancement. Mechanical control systems have been slowly
phased out in favor of electronic control systems. Electronic control systems allow for offsite
monitoring of a system, reducing the number of necessary service calls.
From 2007 to 2014, the Environmental Protection Agency phased in mandates for non-road
diesel engines to use low-sulfur compared to ultra-low-sulfur diesel in most of the United
States. Additionally, new stationary diesel engines are required to meet certain emission stand-
ards. However, small facilities in rural Alaska have been given some exemptions due to the
high cost and the difficulty of operations in remote areas (ADEC, 2016). Pre-2014 model year
engines are exempt from diesel fuel sulfur requirements. Engines may be certified to marine
engine standards rather than land-based non-road engine standards. After-treatment devices for
NOx reduction, such as SCR, are not required. After-treatment devices for particulate matter are
not required for pre-2014 model year engines.
CONCLUSIONS
Diesel generators are the main source of electrical generation in remote Alaska communi-
ties; they also help to maintain grid frequency and voltage. In an analysis of key performance
metrics for diesel generators in Alaska, we found that the size of the installed system directly
affects capital costs, that is, larger systems are more cost-effective per kilowatt. However,
appropriately sizing a system for a community is more cost-effective overall than significantly
oversizing the system. Capacity factors range from below 5% to over 25%. The low values are
typically for diesel-hydroelectric hybrid systems, for which this measure is not entirely accu-
rate. In addition, rural diesel plants may have low capacity factors since typically there are
three to four generators in-house. These generators are sized so that one to two generators pro-
vide power at any given time; the remaining generators are available as backup. Generators of
this size can expect to operate approximately 60000–100000h, with larger engine blocks tend-
ing to have longer lifespans. An appropriately maintained generator operating for 35% of the
time will last approximately 20 years, or 60,000 hours.
The technology continues to see advances in power output, efficiency, noise reduction, and
emission control. The shapes of combustion chambers in newer engines are designed to maxi-
mize the combustion rate of fuel, thus increasing output power and fuel efficiency. The
common-rail fuel system can maintain high pressure from the fuel tank to injection, which
allows for finer vaporization of fuel and more complete combustion. Nitrous oxide can be
reduced through exhaust gas recirculation and selective catalytic reduction. Control systems
have also seen advancement. Mechanical control systems have been slowly phased out in favor
of electronic control systems, which allow for offsite monitoring of a system and reduction in
the number of necessary service calls.
Diesel generators in rural Alaska communities remain difficult to maintain the degree nec-
essary for smooth operation. Additionally, Supervisory Control and Data Acquisition systems
061701-7 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
with remote control capabilities require continuous Internet connection, which is not always
available in rural communities.
ACKNOWLEDGMENTS
The authors wish tothank the Alaska Energy Authority for its funding tosupport this project.
Many people have contributed information and insight to this report. For their review and
comments, we wish to thank John Cameron of Marsh Creek LLC; Steve Stassel; Ingemar
Mathiasson of the Northwest Arctic Borough; and Kris Noonan, Alan Fetters, and Neil McMahon
ofthe Alaska Energy Authority.
APPENDIX: ADDITIONAL DATA AND TABLES
TABLE I. List of communities examined in installation costs with some description of the RPSU grant.
Community
Installed
capacity (kW) Notes (all grants include the powerhouse, generators, and controls)
Akiachak 1500 Grant also includes a 15000 gal intermediate tank and a waste heat recovery loop
Angoon 1575 Grant also includes a waste heat recovery system
Arctic village 395 Grant also includes a distribution upgrade and a waste heat recovery system
Buckland 1125 Grant also includes a 12000 gal intermediate tank, a distribution upgrade, and a heat
exchanger for the existing waste heat recovery loop
Chefornak 1050 Grant also includes a 22000 gal intermediate tank and a heat exchanger for the existing
waste heat system
Chitina 302
Chuathbaluk 175 Grant shared with other middle Kuskokwim projects. Grant also includes tank farms for the
powerhouse, school, and village
Crooked Creek 220 Grant shared with other middle Kuskokwim projects. Grant also includes tank farms for the
powerhouse, school, and village
Deering 585 Grant also includes a 5000 gal intermediate tank and a heat exchanger for the existing waste
heat recovery system
Diomede 460 Grant also includes a distribution upgrade and a heat exchanger for the existing waste heat
loop
Elfin Cove 347 Built in parallel with a distribution upgrade project on a separate grant
Elim 1105
Golovin 580 Grant also includes a 12000 gal intermediate tank and a heat exchanger for the existing
waste heat system
Gustavus 840 Built in parallel with a Hydro system on a separate grant
Hughes 230 Grant also includes a 6000 gal intermediate tank
Karluk 108 Grant also includes a distribution upgrade
King Cove 2602 Hydro and diesel system
Kokhanok 490 Built in parallel with the bulk fuel project but on a separate grant
Kongiganak 755 Grant also includes a 12000 gal intermediate tank, a distribution upgrade, and a heat
exchanger for the existing waste heat loop
Kotlik 1390 Grant also includes a 12000 gal intermediate tank, a distribution upgrade, and a heat
exchanger for the existing waste heat loop
Koyukuk 202 Grant also includes a 12000 gal intermediate tank, a distribution upgrade, and a heat
exchanger for the existing waste heat loop
Kwigillingok 580 Grant also includes three 22000 gal bulk fuel tanks, a 12000 gal intermediate tank, a distri-
bution upgrade, and a heat exchanger for the existing waste heat loop
Manokotak 830 Grant also includes a 12000 gal intermediate tank and a heat exchanger for the existing
waste heat loop
Nikolski 200 Grant also includes re-plumbing for the existing intermediate tank
061701-8 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
TABLE I. (Continued.)
Community
Installed
capacity (kW) Notes (all grants include the powerhouse, generators, and controls)
Pedro Bay 260 Grant also includes a distribution upgrade and a waste heat recovery system
Pelican 920 Project was done in parallel with a bulk fuel storage project and preceded a hydro system
upgrade
Pilot point 318 Built in parallel with a bulk fuel project on a separate grant
Sleetmute 320 Grant shared with other middle Kuskokwim projects. Grant also includes tank farms
for powerhouse and school
Stevens village 290 Grant also includes a distribution upgrade
Stony River 130 Grant shared with other middle Kuskokwim projects. Grant also includes tank farms
for powerhouse, school, and village
Takotna 205 Grant shared with other middle Kuskokwim projects. Grant also includes tank farms
for powerhouse, school, and village
Tenakee Springs 240 Grant also includes a distribution upgrade, and some equipment for waste heat recovery
was installed, but no heat loop was close enough to utilize it
Tuluksak 490 Grant also includes a 12000 gal intermediate tank, a road upgrade, and a distribution upgrade
Tuntutuliak 610 Grant also includes a 4000 gal intermediate tank and a heat exchanger for future waste heat
recovery systems
TABLE II. Assumed Intervals of maintenance tasks. Note that each manufacturer specifies different maintenance intervals
for machines. The assumed intervals are simply approximations.
60–150 kW 151–600 kW 601–1300 kW
Maintenance category Interval (h) Interval (h) Interval (h)
Repeating maintenance
tasks: contracted
Replace the oil cooler and injectors 15000 10000 15000
Replace generator bearings 6000 6000 6000
Unscheduled maintenance/repair 15000 15000 15000
Repeating maintenance
tasks: in-house labor
Daily inspection 14 14 14
Check the battery electrolyte level,
adjust belts, and clean the radiator
250 250 250
Change oil and filter 250 250 500
Clean the crankcase breather 250 250 500
Check/lubricate fuel control linkage 1000 1000 1000
Drain fuel tank water and sediment 250 250 1000
Replace fuel filters and glycol filter 500 500 1000
Replace the air filter, hoses, and belts 2000 2000 2000
Adjust the valve lash 3000 3000 2000
Inspect turbocharger 2000 2000 2000
Inspect generator including bearings 2000 2000 2000
Replace coolant 6000 6000 6000
Inspect the engine speed sensor,
starting motor, and water pump
6000 6000 6000
One-time maintenance
tasks
Initial 250 service hours of inspection
and valve lash adjustment
250 250 250
First top end rebuild 15000 15000 15000
Second top end rebuild 30000 30000 30000
In-frame rebuild 45000 45000 45000
Third top end rebuild … 60000 60000
Fourth top end rebuild … 75000 75000
Fifth top end rebuild … … 90000
061701-9 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
TABLE III. Labor duration of maintenance tasks.
60–150 kW 151–600 kW 601–1300 kW
Maintenance category Labor (h) Labor (h) Labor (h)
Repeating maintenance
tasks: contracted
Replace the oil cooler and injectors 30.0 30.0 30.0
Replace generator bearings 30.0 30.0 30.0
Unscheduled maintenance/repair 30.0 40.0 40.0
Repeating maintenance
tasks: in-house labor
Daily inspection 1.0 1.0 2.0
Check the battery electrolyte level, adjust belts,
and clean the radiator
2.0 2.0 2.0
Change oil and filter 2.0 2.0 2.0
Clean the crankcase breather 1.0 1.0 1.0
Check/lubricate fuel control linkage 1.0 1.0 1.0
Drain fuel tank water and sediment 2.0 2.0 2.0
Replace fuel filters and glycol filter 2.0 2.0 2.0
Replace air filter, hoses, and belts 4.0 4.0 4.0
Adjust the valve lash 4.0 4.0 4.0
Inspect the turbocharger 1.0 1.0 1.0
Inspect the generator including bearings 1.0 1.0 1.0
Replace coolant 4.0 4.0 4.0
Inspect the engine speed sensor, starting motor,
and water pump
2.0 2.0 2.0
One-time maintenance
tasks
Initial 250 service hours of inspection and valve
lash adjustment
6.0 6.0 6.0
First top end rebuild 40.0 60.0 80.0
Second top end rebuild 40.0 60.0 80.0
In-frame rebuild 150.0 300.0 400.0
Third top end rebuild … 60.0 80.0
Fourth top end rebuild … 60.0 80.0
Fifth top end rebuild … … 80.0
TABLE IV. List of O&M costs reported for RCA and the installed capacity for the respective community.
Community Installed capacity (kW) O&M cost ($/kWh)
Akiachak 1500 0.14
Atka 200 0.13
Arctic village 395 0.38
Atmautluak 547 0.15
Buckland 1125 0.09
Chignik 577 0.18
Chitina 302 0.15
Deering 585 0.17
Diomede 460 0.26
Elfin Cove 347 0.18
Hughes 230 0.21
Kokhanok 490 0.18
Koyukuk 202 0.15
Manokotak 830 0.06
Nikolski 200 0.15
Ouzinkie 350 0.14
Pedro Bay 260 0.14
Pelican 920 0.17
061701-10 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)
ADEC (Alaska Department of Environmental Conservation),https://dec.alaska.gov/air/anpms/ulsd/ulsdnsps.htm for
Internal Combustion Engine Requirements, April 2016.
Alaska Department of Labor and Workforce Development,https://laborstats.alaska.gov/cpi/cpi for Consumer Price Index
data, January 2016.
Alaska Energy Data Gateway,https://akenergygateway.alaska.edu for Power Cost Equalization Data, January 2016.
Denali Commission Project Database,https://denali.gov for Rural Power System Upgrade (RPSU) projects, January 2016.
TABLE IV. (Continued.)
Community Installed capacity (kW) O&M cost ($/kWh)
Pilot Point 318 0.09
Takotna 205 0.24
Tenakee Springs 240 0.16
Tuluksak 490 0.15
Tuntutuliak 610 0.16
061701-11 Green, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061701 (2017)