HomeMy WebLinkAbout2017 Energy Storage Published ArticleAn Alaska case study: Energy storage technologies
Jeremy VanderMeer, Marc Mueller-Stoffels, and Erin Whitney
Citation: Journal of Renewable and Sustainable Energy 9, 061708 (2017);
View online: https://doi.org/10.1063/1.4986580
View Table of Contents: http://aip.scitation.org/toc/rse/9/6
Published by the American Institute of Physics
Articles you may be interested in
Preface: Technology and cost reviews for renewable energy in Alaska: Sharing our experience and know-how
Journal of Renewable and Sustainable Energy 9, 061501 (2017); 10.1063/1.5017516
An Alaska case study: Solar photovoltaic technology in remote microgrids
Journal of Renewable and Sustainable Energy 9, 061704 (2017); 10.1063/1.4986577
Wind power project size and component costs: An Alaska case study
Journal of Renewable and Sustainable Energy 9, 061703 (2017); 10.1063/1.4986579
An Alaska case study: Diesel generator technologies
Journal of Renewable and Sustainable Energy 9, 061701 (2017); 10.1063/1.4986585
An Alaska case study: Organic Rankine cycle technology
Journal of Renewable and Sustainable Energy 9, 061707 (2017); 10.1063/1.4986583
An Alaska case study: Biomass technology
Journal of Renewable and Sustainable Energy 9, 061705 (2017); 10.1063/1.4986578
An Alaska case study: Energy storage technologies
Jeremy VanderMeer,Marc Mueller-Stoffels,and Erin Whitney
Alaska Center for Energy and Power, University of Alaska Fairbanks, P.O. Box 755910,
Fairbanks, Alaska 99775-5910, USA
(Received 6 June 2017; accepted 14 September 2017; published online 21 December 2017)
In the analysis of energy storage systems (ESSs) in Alaska, the most significant
trend in the data considered is the increased variance in costs with time. Thus,
more options are now available for ESS with “low cost per kW/high cost per
kWh” and vice versa, indicating a greater variety of specialized ESS for targeted
applications. The data analyzed do not show any difference in the cost of energy
storage in Alaska compared to such costs in the rest of the nation or world. Alaska
has had relatively few energy storage technology failures, and most that occurred
were caused by improper operation. It is often difficult to justify energy storage
economically based on fuel savings alone. Significant work remains to quantify
other possible cost savings afforded by energy storage, such as reduced fuel
consumption and stress on a diesel generator by smoothing out the load. The lack
of standardization and quantification of costs and benefits is the main barrier to
determining the economic potential for implementation of energy storage in
Alaska. In addition, communities in Alaska often wish to avoid ESS that uses
hazardous materials since each community will eventually have to deal with
disposal issues.Published by AIP Publishing.https://doi.org/10.1063/1.4986580
INTRODUCTION
Since the discovery of electricity, humans have sought effective methods to store that energy
for use on demand. Energy storage systems (ESSs) provide a technological approach to managing
power supply to create a more resilient energy infrastructure. In this paper, ESS refers to systems
that store electrical energy (either chemical, mechanical, or electrical) and later return it to the grid.
There are 514 grid-connected ESS installations in the United States, totaling over 24GW of power
capacity. According to the U.S. Department of Energy (U.S. DOE, 2017), 159 new ESS projects
have been announced or contracted, which will increase grid-connected energy storage by 7.2GW.
Remote microgrids are not connected to a larger electrical grid. This means that they must
generate all electricity that is consumed within the grid. In Alaska, remote microgrids are small,
which means there are relatively few electrical loads in a system and thus a high level of stochas-
ticity in the total microgrid electrical load. Adding high penetrations of stochastic renewable
energy makes it increasingly difficult to match generation with demand. Energy storage systems
offer an attractive solution to this challenge. Alaska currently has eight grid-connected ESS instal-
lations totaling 61MW, with one project totaling 0.32MW currently contracted (U.S. DOE, 2017).
Energy storage systems can be divided into the energy storage unit and the power condition-
ing system, as shown in Fig.1. The energy storage unit determines the amount of energy that can
be stored, or the energy capacity, in kilowatt-hours. The power conditioning system is the inter-
face between the grid and the energy storage unit and controls charging and discharging. Thus,
the power conditioning system is largely responsible for the power in kilowatts of ESS.
This review of ESS in Alaska is a result of Alaska Senate Bill (SB) 138. In this bill, the
Alaska State Legislature created an uncodified section of law entitled “Plan and
Recommendations to the Legislature on Infrastructure Needed to Deliver Affordable Energy of
the State to Areas That Do Not Have Direct Access to a [proposed] North Slope Natural Gas
Pipeline.” To support the Alaska Energy Authority (AEA) in its development of an affordable
energy strategy for Alaska, the Alaska Center for Energy and Power (ACEP) contracted with
AEA to document technology development needs specific to the state with regard to renewable
1941-7012/2017/9(6)/061708/18/$30.00 Published by AIP Publishing.9, 061708-1
JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY 9, 061708 (2017)
and sustainable energy technologies. The intention was to determine what targeted, energy tech-
nology development solutions could be implemented in Alaska to make energy more affordable
in the Alaska Affordable Energy Study area. While the focus was on technology research solu-
tions, other factors such as logistics, labor, and training were also addressed. Drafts of technol-
ogy reviews were vetted by expert roundtables in late February and early March 2016.
These reviews are not meant to be exhaustive discussions of energy technologies in Alaska
or proper designs for each technology, and they should not be used as guides for the choice
and installation of specific systems. As such, not all possible issues with power production and
each technology are addressed. Data for each technology were collected from surveys and pub-
lically available databases. Only completed projects, or projects with clearly reported data,
were included in each technology analysis. These distinctions and descriptions of data sources
are included in each technology review.
METHODS
Deployment of ESS is still nascent in Alaska, with a few exceptions. Thus, the dataset
developed from AEA Renewable Energy Fund (REF) applications has been supplemented with
data from the U.S. DOE Global Energy Storage Database. The U.S. DOE database captures
installation data worldwide from Sandia National Laboratory’s energy storage reports (several
editions) and data collected by ACEP through personal communication with energy storage
developers and utilities. Data sources are detailed in Appendix A.
Lead-acid, advanced lead-acid (Xtreme Power), lithium-ion, flow (vanadium redox and
zinc-bromine), nickel-based (nickel cadmium) batteries, flywheels, compressed air, and closed-
loop pumped hydro and open-loop pumped hydro energy storage are the technologies repre-
sented by the available data. Demonstration projects were removed from this paper since many
of them had inexplicably high costs.
Note that none of the flow battery projects reported here are currently operational, includ-
ing the vanadium redox flow battery that Kotzebue had received a quote on from VRB before
the company went out of business, the zinc-bromine flow battery purchased by Kotzebue from
Premium Power, which was decommissioned and two other batteries that are contracted/under
construction. We are not certain, therefore, that the prices presented accurately reflect the cost
of functioning systems. All costs have been converted to 2015 dollars based on the Consumer
Price Index (CPI) (U.S. Bureau of Labor Statistics, 2016).
DISCUSSION
Capital costs by power and energy capacity
Energy storage systems generally consist of the actual storage device (e.g., a battery or fly-
wheel), which defines the energy capacity and theoretical maximum power available, and power
conversion systems, which determine the actual maximum power available for both charging
and discharging. As the two systems—storage device and power conversion system—are sepa-
rate units selected depending on a particular application, it makes sense to examine the capital
cost of systems in relation to both energy storage capacity and power capacity, referred to
herein as the Capacity and Power of an ESS. In the rest of this review, capital costs will be
FIG. 1. A basic energy storage system contains an energy storage unit and a power conditioning system; in this case, the energy
storage unit operates with a DC voltage and an inverter is used to convert the DC power into AC on the distribution or transmission
grid. The inverter will also need to be able to act as a rectifier and convert AC power into DC to charge the energy storage unit.
061708-2 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
referred to as CAPEX, which denotes the capital expenditures required to acquire the energy
storage system, as opposed to later operating expenses (OPEX).
Figures 2 and 3 show the cost per capacity ($/kWh) and rated power ($/kW) plotted against
capacity and rated power for global and Alaska projects. The variation in CAPEX/capacity and
CAPEX/power is wide, and no trends are obvious, both overall and within particular technologies.
The wide variation in CAPEX/capacity and CAPEX/power can be partly explained by differ-
ences in the infrastructure included in CAPEX. For example, one project simply involved replac-
ing the batteries in an existing installation, while other projects required various infrastructures
such as a building and interconnection. Cost breakdowns were not given for most of the data,
and it was not always clear what was included in CAPEX. All costs from REF applications for
projects in Alaska (labeled AK on the plots) include transport, hardware, and installation.
The variation can also be partly explained by the ratio of capacity to rated power (or the
duration in hours). CAPEX/power tends to be higher for ESS with a longer duration, while
CAPEX/capacity tends to be lower. The plots of CAPEX/capacity and CAPEX/power versus
duration can be seen in Figs.6 to 9 in Appendix A.
The costs presented in Figs.2 and 3 are best understood in the context of what each data
point represents. A short description of the different projects presented in these figures is given
in Appendix B and helps to explain the variation seen in costs. Note that the cost data on flow
batteries are for installations that are not currently operational.
FIG. 2. The plot of CAPEX/capacity versus capacity for non-hydro energy storage. The inset shows a scaled view of the y-axis
for easier viewing of lower CAPEX/capacity values. Data are shown for both global and Alaska installations. Flywheels tend to
be more expensive per capacity (kWh) than other forms of energy storage; they tend to be cheaper per rated power (see Fig.3).
FIG. 3. The plot of CAPEX/power versus power for non-hydro energy storage. Data are shown for both global and Alaska
installations.
061708-3 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
Table I shows mean values of CAPEX/power and CAPEX/capacity for global and Alaska
data. Similar to Figs.2 and 3, these values are best understood in the context of the projects
they represent. See Appendix B for an overview of the different projects.
Operation and maintenance ($/kW)
Data for global and Alaska operation and maintenance (O&M) costs were minimal. A
report by Sandia (Schoenung and Hassanzahl, 2003) gives the estimates shown in Table II. The
O&M values given for flow batteries are low, based on the experience and knowledge of the
authors.
Expected life and efficiency
The energy efficiency and expected number of cycles before replacement/overhaul, from a
2011 Sandia report (Schoenung, 2011), are shown in Table III. Electro-mechanical systems,
like pumped hydro and flywheels, typically can be overhauled at minimal cost, while electro-
chemical systems typically need to be replaced. The replacement period in years is used for
levelized cost of energy (LCOE) and levelized cost per cycle power (LCCP) calculations and
corresponds to the end of the cycle life. The performance metrics listed for flow batteries are
much higher than what the authors have experienced or are aware of in actual installations.
The expected efficiency of an ESS is highly technology and use dependent. Table III shows
average values for the round trip efficiency of different ESS technologies. For a given ESS, the
TABLE I. Mean CAPEX/power and CAPEX/capacity for global and Alaska data.
Global Alaska
Technology
Mean CAPEX/power
($/kW)
Mean CAPEX/capacity
($/kWh)
Mean CAPEX/power
($/kW)
Mean CAPEX/capacity
($/kWh)
Flow battery 8401 2444 3758 1089
Lead-acid battery 1785 1785 3472 2480
Lead-acid battery (advanced) 1408 5634 1328 5311
Lithium-ion battery 2292 2115 2172 7797
Nickel-based battery 1668 6674 979 2650
Closed-loop pumped hydro 1438 141
Open-loop pumped hydro 995 77
Compressed air energy storage 1120 80
Flywheel 3026 261978
TABLE II. O&M costs for different energy storage technologies, from Sandia’s 2003 report (Schoenung and Hassanzahl,
2003); O&M is reported in $/kWyr. Note: Costs have been increased by 30% to update them to 2015 dollars based on the
CPI. The costs for power generation are not as straightforward as the costs for energy storage, as O&M is influenced by
more variables.
Name O&M [$/(kWyr)]
Lead-acid battery (flooded cell)19.5
Lead-acid battery (advanced)6.5
Lithium-ion battery 32.5
Nickel cadmium battery 32.5
Zinc bromine flow battery 26
Vanadium redox flow battery 26
Flywheels (high speed)6.5
Compressed air energy storage (surface) 13
Pumped hydro 3.25
061708-4 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
round trip efficiency will vary depending on how it is operated. For example, a fly wheel’s effi-
ciency will vary depending on its rotational speed (amount of stored energy) and its power out-
put or input. The length of time between charge and discharge will also affect round trip effi-
ciency due to the rotational losses (friction) in the flywheel. Thus, the method of operation will
have a significant impact on the round trip efficiency of a flywheel. This is also true to varying
degrees for other ESS technologies. See the section on Conditions for the Greatest Efficiency
for a discussion of the different types of energy losses in an ESS.
Capacity factor
The capacity factor for energy storage technology is not applicable.
Diesel offset
General uses for ESS are peak shifting (charging during low load/high generation events
and discharging during high load/low generation events), power quality support (balancing high
ramp rates in the load or renewable generation), and supplying spinning reserve capacity (SRC:
the ability to meet suddenly rising demand or replace suddenly dropping generation; this allows
smaller generators or no diesel generators to run online). Peak shifting generally saves diesel
by increasing the utilization of renewable energy. Providing power quality support reduces
TABLE III. Performance characteristics of ESS technologies (Schoenung, 2011;Schoenung and Hassanzahl, 2003;Divya
and Ostergaard, 2009;Butler et al., 2000;Viswanathan et al., 2013).
Technology
Round trip efficiency
(%)
Depth of discharge
(%) Cycle life
Replacement period
(yr)
Lead-acid battery (flooded cell) 75 50 2000 6
Lead-acid battery (advanced) 80 50 2000 6
Lithium-ion battery 85 80 4000 10
Nickel cadmium battery 65 100 3000 10
Zinc bromine flow battery 70 100 3000 8
Vanadium redox flow battery 65 100 5000 10
Flywheels (high speed) 95 100 25000 20
Compressed air energy storage (surface) 70 100 25000 30
Pumped hydro 85 100 25000 30
FIG. 4. LCOE for energy storage applications. The inset shows a scaled view of the y-axis for easier viewing of lower
LCOE values. LCOE values for energy storage only show the energy throughput of the storage device and not the increase
in energy production from cheaper sources, such as renewable energy, that it enables. The LCOE and LCCP of energy stor-
age must be understood in terms of how they affect the cost of energy in the entire system.
061708-5 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
stress on diesel generators, which increases their lifespan and efficiency. Providing SRC saves
diesel by allowing a smaller or no diesel generator to run online, enabling a much higher use
of renewable energy.
Schaede et al.(2015)provided an example of possible diesel savings with energy storage.
They modelled Nome’s grid with 959kW/58kWh flywheel energy storage supplying SRC.
Nome’s grid has an average load of 4MW and an installed wind power capacity of 2.7MW.
The flywheels supplied SRC (as well as load leveling), which allowed smaller diesels to run
online and let wind power supply a higher fraction of the load when wind power was available,
reducing diesel consumption. The energy storage reduced diesel consumption by 850gal/week
during periods with high levels of wind power and by 450gal/week during periods with low
levels of wind power.
Cost per kWh
For energy storage, the levelized cost of energy (LCOE) is defined as the levelized cost of
storing energy ($/kWh stored). However, this metric does not give the whole picture since it
does not take into account the power at which energy storage is able to charge and discharge.
A second metric called levelized cost per cycle power (LCCP) is used for this. The LCCP,
which provides levelized cost per cycle per kW [$/(cyclekW)], does not take into account the
duration of the discharge (charge) and is more relevant for applications, such as power quality,
that need high power and not necessarily long duration.
The equations for LCOE and LCCP are given in Appendix C. Both LCOE and LCCP were
calculated assuming an inflation rate of 2%, an interest rate of 5%, and the typical depth of
FIG. 5. LCCP for energy storage applications.
TABLE IV. Mean LCOE and LCCP for global and Alaska data. Note that all data used in this paper for flow batteries are
from systems that are not currently operational.
Global Alaska
Technology
Mean LCOE
($/kWh)
Mean LCCP
[$/(cyclekW)]
Mean LCOE
($/kWh)
Mean LCCP
[$/(cyclekW)]
Flow battery 1.0 2.2 0.45 1.0
Lead-acid battery 2.8 1.1 3.8 2.1
Lead-acid battery (advanced) 8.5 0.85 8.0 0.80
Lithium-ion battery 1.1 0.81 4.0 0.77
Nickel-based battery 5.0 0.81 5.0 0.81
Closed-loop pumped hydro 0.013 0.12
Open-loop pumped hydro 0.0075 0.081
Compressed air energy storage 0.010 0.10
Flywheel 18 0.20
061708-6 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
discharge (DOD), cycle life, year life, and efficiency shown in Table III. These values can vary
widely depending on the system and how it is operated. Different energy storage technologies
have different replacement costs, which affect LCOE and LCCP, but are not considered here.
Figures 4 and 5 show a more detailed analysis on the cost of different ESS technologies and
show the LCOE and LCCP for global and Alaska energy storage system installations. The
mean values of LCOE and LCCP for global and Alaska data are shown in Table IV. Certain
technologies have a lower LCOE, while others have a lower LCCP, indicating their feasibility
for high energy or high power applications. Again, these values are best understood in the con-
text of the projects they represent, described in Appendix B. Note that the values for flow bat-
teries have been calculated using cost data from non-operational projects and performance data
from the literature that seem to be high based on the authors’ experience. Thus, these values
may offer overly optimistic figures.
Conditions for the greatest efficiency
The efficiencies of ESS are largely influenced by the technology type (see the section on
Expected Life and Efficiency) and usage. The three main forms of energy loss are charge/dis-
charge (losses in energy storage medium and power electronics), storage (self-discharge), and
parasitic due to balance of plant (e.g., cooling systems). An inefficiency is always associated
with converting electrical energy into chemical or mechanical energy. Between technologies,
levels of self-discharge vary, which results in losses during storage, with the more the losses,
the longer the storage. Other factors such as temperature can play a significant role as well.
Thus, the conditions for the greatest efficiency are technology and use dependent.
Cost curve over time
The U.S. DOE, together with industry, has developed the near-term (present–2018) goals
of under $250 per kWh of installed capacity for storage technologies and under $1750 per kW
of rated power for power conditioning technologies. The long-term (2018–2023) goals are under
$150/kWh for storage systems and under $1250/kW for power conditioning technologies (U.S.
DOE, 2013). These numbers need to be converted into CAPEX for the entire energy storage
TABLE V. Comparison of Sandia cost estimates with costs from global and Alaska data (2015 dollars) shows, on average,
significantly higher costs for Alaska.
Sandia Global and
Alaska
Calculated from Sandia Global Alaska
Tech1
Power
conditioning
cost ($/kW)
Energy
storage cost
($/kWh)
Mean
duration (h)
Mean
CAPEX/
power
($/kW)
Mean
CAPEX/
capacity
($/kWh)
CAPEX/
power
difference
($/kW)
CAPEX/
capacity
difference
($/kWh)
CAPEX/
power
difference
($/kW)
CAPEX/
capacity
difference
($/kWh)
Flow battery 420 525 4.2 2625 625 5776 1819 1133 464
Lead-acid battery 420 346.5 1 766.5 766.5 1018.5 1018.5 2705.5 1713.5
Lead-acid battery
(advanced)
420 346.5 0.25 506.625 2026.5 901.375 3607.5 821.375 3284.5
Lithium-ion battery 420 630 1.2 1176 980 1116 1135 996 6817
Nickel-based battery 292.5 780 0.31 534.3 1723.548 1133.7 4950.452 444.7 926.4516
Closed-loop pumped
hydro storage
1260 78.75 10 2047.5 204.75 609.5 63.75
Open-loop pumped
hydro storage
1260 78.75 13 2283.75 175.6731 1288.75 98.6731
Compressed
air storage
735 5.25 18 829.5 46.08333 290.5 33.91667
Flywheel 630 1680 0.033 685.44 20770.91 2340.56 241207.1
061708-7 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
system and divided by capacity and power for comparison with the costs of the ESS presented
in this paper. The total energy storage system costs (CAPEX) presented in this paper are an
average of $591/kW, $6.6/kWh higher than the short-term goal (2018) and an average of
$1213/kW and $860/kWh higher than the long-term goal (2023).
Installed costs by major components
Sandia’s reports include energy storage system costs by technology (Schoenung and
Hassanzahl, 2003;Schoenung, 2011). The authors split the costs between the power condition-
ing system, listed in $/kW, and the energy storage system, listed in $/kWh. The costs, updated
to 2015 dollars, are shown in Table V. Sandia’s cost estimates have been converted to total
CAPEX/capacity and CAPEX/power using the average duration of the different technologies.
These costs have then been compared with the global and Alaska data. The difference between
Sandia’s calculated costs and costs from the data is also shown in Table V. The data show, on
average, significantly higher costs except for pumped hydro storage, which is cheaper than
Sandia’s costs.
Transportation
Only one data entry had an estimate for transportation costs: Kotzebue budgeted $40000 for the
transport of a vanadium redox flow battery from VRB (the project did not go through).
Transportation costs are highly dependent on the weight, size, and shipping restrictions of the energy
storage unit as well as the distance and available means of transportation to the end destination.
Technology trends
Recent material advances, especially in nanotechnology, have been significant in the develop-
ment of ESS: low-cost, long-life electrodes and membranes for flow batteries, flywheel design,
increased surface area supercapacitors, and superconducting materials. New chemistries are the
focus of research: different redox equations and electrolyte solutions for lower cost, higher perfor-
mance, higher safety, and longer life of batteries and flow batteries. Inverters and converters have
been improving in performance and decreasing in price with advanced power electronics and new
topologies. System design is a major part of bringing a technology out of the lab and into a prod-
uct that is easy to use and maintain in the field. The electric vehicle (EV) market is a major
driver of ESS development, resulting in home and grid-connected batteries.
Tech-specific storage systems
Tech-specific storage systems (i.e., ultra-capacitors with wind) are not applicable to energy
storage technology.
Refurbishment/upgrade market
For electro-mechanical ESS such as pumped hydro and flywheels, refurbishment is often a
cost-effective way to extend the life of the system. An example of a growing refurbishment
market is old electric vehicle (EV) batteries. After the battery drops to 70%–80% of its initial
capacity, it becomes insufficient for automotive use. However, the battery is still useful for sta-
tionary energy storage. Nissan is the first EV manufacturer to launch a startup—Green Charge
Networks—which resells old Nissan Leaf batteries as part of stationary storage systems
(Neubauer and Pesaran, 2010;St. John, 2015).
Realized cost savings
Cost savings from integrating renewable power are difficult to gauge due to technical and
incentive impacts at the entire power system level. At the technical level, for example, effects
of diminished losses of secondary services such as recovered waste heat and reductions in fuel
efficiency are hard to gauge, as they depend not only on average reductions in load but also on
061708-8 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
specific operating schemes, such as minimum allowable loads on diesels and the spinning
reserve kept.
CONCLUSIONS
Deployment of ESS is nascent in Alaska, with a few exceptions. Thus, the dataset devel-
oped from AEA REF applications has been supplemented by data from the U.S. DOE Global
Energy Storage Database, which captures installation data worldwide from Sandia National
Laboratory’s energy storage reports (several editions) and data collected by ACEP through per-
sonal communication with energy storage developers and utilities.
Energy storage is hard to quantify in terms of performance, cost, and economic value.
Costs and performance in the overall energy storage market have been evolving sporadically,
and it is not easy to discern any clear trend. The most significant trend in the data considered
here is the increased variance in costs with time. Thus, more options for ESS with “low cost
per kW/high costs per kWh” and vice versa are now available, indicating a greater variety of
specialized ESS for targeted applications.
It is often difficult to justify energy storage economically based on fuel savings alone.
Significant work remains to quantify other possible cost savings afforded by energy storage,
such as reduced fuel consumption and stress on a diesel generator by smoothing out the load.
The data analyzed for this paper do not show any difference in the cost of energy storage
in Alaska compared to the rest of the nation or world. Alaska has had relatively few energy
storage technology failures, and most that occurred were caused by improper operation.
Recent material advances, especially in nanotechnology, have been significant in the devel-
opment of ESS: low-cost, long-life electrodes and membranes for flow batteries, flywheel
designs, and increased surface area supercapacitors and superconducting materials. New chem-
istries are a focus of research with regard to different oxidation-reduction reactions and electro-
lyte solutions for lower costs, higher performance, higher safety, and longer life of batteries
and flow batteries. Inverters and converters have been improving in performance and decreasing
in price, with advanced power electronics and new topologies. The electric vehicle market is a
major driver of energy storage system development, resulting in home and grid-connected bat-
tery development.
The lack of standardization and quantification of costs and benefits is the main barrier to
determining the economic potential for implementation of energy storage in Alaska. In addition,
communities in Alaska often wish to avoid ESS that uses hazardous materials since each com-
munity will eventually have to deal with disposal issues.
Energy efficiency grants could be leveraged for ESS. The development of standardized use
scenarios for the operation of such systems would maximize the economic benefits in Alaska.
These scenarios would ideally include quantification of economic savings, performance specifi-
cations for ESS manufacturers, and calculations of comparison metrics based on performance
specifications. Guidance documents for determining needs, required specifications, and selection
procedures for ESS would be extremely helpful. These documents should include information
on how to protect an investment from technical failures by agreeing on performance and life-
time guarantees as well as responsibility for failure.
ACKNOWLEDGMENTS
The authors wish tothank the Alaska Energy Authority for its funding tosupport this project.
Many people have contributed information and insight to this study. We wish to thank Abbas
Akhil and Ben Schenkman of Sandia National Laboratory, Tony Slatonbarker of Coffman
Engineers, and Josh Craft and Neil McMahon of the Alaska Energy Authority for their review and
comments.
APPENDIX A: ADDITIONAL ANALYSIS AND PLOTS
061708-9 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
FIG. 6. Plot of CAPEX/capacity versus duration. The high cost per capacity of flywheels and high duration of flow batteries
make this plot hard to read.
FIG. 7. Plot of CAPEX/capacity versus duration with flywheels and flow batteries removed.
FIG. 8. Plot of CAPEX/power versus duration. The high duration of flow batteries makes this plot hard to read.
FIG. 9. Plot of CAPEX/power versus duration with flow batteries removed.
061708-10 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE VI. Lithium-ion battery.Project name Source Date State CountryPower(kW)Capacity(kWh)CAPEX/power($/kW)CAPEX/capacity($/kWh) NotesNICE GRID project inCarros (SouthernFrance): PrimarySubstation Battery(PSB)DOE 7/31/2013 Provence-Alpes-C^ote dAzurFrance 1000 450 817.62 1816.93 There are 3 “NICE GRID”data points, consistent CAPEX/capacitywith varying CAPEX/Power.Jake Energy StorageCenter: RES AmericasDOE 2/25/2015 Illinois United States 19800 7920 1022.66 2556.66 Relatively lowCAPEX/power andhigh CAPEX/capacity.Elwood Energy StorageCenter: RES AmericasDOE 2/25/2015 Illinois United States 19800 7920 1022.66 2556.66 Relatively lowCAPEX/power andhigh CAPEX/capacity.KIUC Anahola SolarArray and BatteryDOE 12/29/2014 Hawaii United States 6000 4980 1175.69 1416.49Anchorage AreaBattery Energy StorageSystemDOE and ARTEC 1/1/2016 Alaska United States 25000 14250 1208.00 2119.30 Data are from ARCTEC“2013 Railbelt Energy Priorities.”Stafford Hill SolarFarm and Microgrid:Lithium IonDOE 12/18/2014 Vermont United States 2000 2000 1259.67 1259.6710 MW/10 MWh—Feldheim RegionalRegulating PowerStation (RRKW)DOE 2/14/2015 Brandenburg Germany 10000 10800 1447.78 1340.545kWh LiFePO4DIY ESSDOE 11/3/2012 Ile de France France 2 4 1802.30 901.15APPENDIX B: REFERENCED ENERGY STORAGE PROJECTS AND SOURCESTablesVI–Xlist the energy storage projects studied in this paper and where they are sourced.REFrefers to the Renewable Energy Fund,DOErefers tothe DOE global energy storage database,EETFrefers to the emerging energy technology fund,ACEPrefers to the Alaska Center for Energy and Power, andARTECrefers to Alaska Railbelt Cooperative Transmission & Electrical Company.
061708-11 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE VI. (Continued.)Project name Source Date State CountryPower(kW)Capacity(kWh)CAPEX/power($/kW)CAPEX/capacity($/kWh) Notes2 MW/4.4 MWh PugetSound Energy—Glacier WADOE 12/17/2014 Washing-ton United States 2000 4400 1914.69 870.31Oncor Battery Storage DOE 6/23/2014 Texas United States 250 750 2006.43 668.81JuiceBox Residentialsolar energy storageSES—AC-coupledpeak-shifting andbackupDOE 5/10/2015 California United States 5 5.85 2009.11 1717.19Landing Mall DR DOE 5/21/2011 Washing-ton United States 75 39.75 2117.78 3995.80 Remotely controlled byutility for demand response.Tuntutuliak REF 1/1/2011 Alaska United States 250 62.5 2654.00 10617 Tuntutuliak and Kwigillingok areidentical REF applications.Both were declinedfunding due to control andintegration issues.Kwigillingok installed Chevy-voltbatteries withan ABB PCS-100 inverter,the same specs and price.The very highCAPEX/capacity is likely partly dueto the very low duration.Kwigillingok REF 1/1/2011 Alaska United States 250 62.5 2654.00 1061790 kW/180 kWh SantaCruz County BuildingGCNDOE 9/28/2015 California United States 90 180 2784.15 1392.08ZECO Energy DOE #N/A Victoria Australia 33 41.25 3030.30 2424.24 This installation is off-grid,which is likely the cause for therelatively high cost.NICE GRID project inCarros (SouthernFrance): SecondaryDOE 8/24/2013 Provence-Alpes-C^ote dAzur France 250 480 3672.46 1912.74 There are 3 “NICE GRID”data points, consistentCAPEX/capacity with
061708-12 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE VI. (Continued.)Project name Source Date State CountryPower(kW)Capacity(kWh)CAPEX/power($/kW)CAPEX/capacity($/kWh) NotesSubstation Battery(SSB)varying CAPEX/Power.Fort Hunter LiggettBattery Storage ProjectDOE 10/1/2013 California United States 1000 1000 4074.23 4074.23 This installation is on a military base.Perhaps higher building standardsresult in high cost.NICE GRID project inCarros (SouthernFrance): Low VoltageGrid Batteries (LVGB)DOE 8/23/2013 Provence-Alpes-C^ote dAzur France 33 84.81 4636.94 1804.26 There are 3 “NICE GRID”data points, consistent CAPEX/capacity withvarying CAPEX/Power.UBC ElectrochemicalEnergy Storage ProjectDOE 11/6/2012 British Columbia Canada 1000 1000 5252.40 5252.40 This was installed on auniversity campus andintended for researchas well as grid support, whichpossibly led to high costs.
061708-13 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE VII. Lead-acid battery.Project name Source Date State Country Power (kW)Capacity(kWh)CAPEX/power($/kW)CAPEX/capacity($/kWh) NotesPREPA BESS 2 DOE 4/21/2002 Puerto Rico United States 20000 13400 763.6019 1139.704 This is the cost of replacing the existing installa-tion “PREPA BESS 1.” Having existing infra-structure results in the lowest CAPEX/Power.Stafford Hill Solar Farm andMicrogrid: Lead AcidDOE 12/18/2014 Vermont United States 2000 2400 1259.665 1049.721Kodiak-Pillar Mountain REF 1/1/2012 Alaska United States 3000 750 1327.818 5311.273 This is an “advanced” lead acid battery, whichresults in a higher CAPEX/capacity.KIUC Koloa—Xtreme Power DPR DOE 7/15/2011 Hawaii United States 1500 375 1408.405 5633.622 This is an “advanced” lead acid battery, whichresults in a higher CAPEX/capacity.PREPA BESS 1 DOE 2/10/1992 Puerto Rico United States 21000 14070 1660.707 2478.667 The higher cost is likely due to the early instal-lation date.Metlakatla BESS DOE 2/3/1997 Alaska United States 1000 1400 3459.063 2470.759 The higher cost is likely due to the early instal-lation date as well as being installed in a remotemicrogrid.061708-14 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE VIII. Flow battery.Project name Source Date State Country Power (kW)Capacity(kWh) CAPEX/($/kW)CAPEX/Capacity($/kWh) NotesKotzebue PremiumPowerREF 1/1/2010 Alaska Unite States of America 500 3700 1655.345 223.6953 The cost of purchasing, transporting, andinstalling a Zinc-Bromine Flow Batteryfrom Premium Power. It did not perform torequired specs, was decommissioned.RedFlow 300 kWAdelaideDOE 4/17/2015 South Australia Australia 300 660 3363.406 1528.821 The cost of purchasing and transporting aZinc-Bromine Flow Battery from RedFlow.Under construction.Kotzebue VRB REF 1/1/2008 Alaska Unite States of America 600 1800 5860.927 1953.642 The price quoted to Kotzebue for aVanadium Redox Flow Battery before VRBwent out of business.Minami HayakitaSubstation VanadiumRedox Flow BatteryDOE 4/17/2014 Hokkaido Japan 15000 60000 13438.93 3359.733 Project cost of installing Vanadium RedoxFlow Batteries. These costs are much higherpossibly due to higher infrastructure costs.Contracted/under construction.
061708-15 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
TABLE IX. Flywheel.Project name Source Date State Country Power (kW)Capacity(kWh)CAPEX/power($/kW)CAPEX/capacity($/kWh) NotesChugach FESS EETF 5/26/2015 Alaska United States of America 200 25 2210 17680 The installed cost of Flywheel energy storagefor Chugach’s announced project.Kwigillingok FESS REF 1/1/2010 Alaska United States of America 500 5 3100 310010 Kwigillingok, Tuntutuliak, and Kongiganaksubmitted identical REF applications which were not funded.Kipnuk also was not granted funding throughREF. Kwigillingok installed Lithium-ion Batteries instead.The high CAPEX/Capacity is due to the low Capacity.Tuntutuliak FESS REF 1/1/2010 Alaska United States of America 500 5 3100 310010Kongiganak FESS REF 1/1/2010 Alaska United States of America 500 5 3100 310010Kipnuk high penetration REF 1/1/2010 Alaska United States of America 500 5 3622 362183
061708-16 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
APPENDIX C: EQUATIONS FOR LCOE AND LCCP
Equations for LCOE:
LCOE ¼NPVc CRF
AnnualEnergyStored ;
NPVc ¼CAPEX þ
XN
j¼1
1 þ i
1 þ r
j
OM;
CRF ¼r
1 ð 1 þ rÞ N ;
AnnualEnergyStored ¼Cap DOD g Cycles
Years ;
where NPVc is the net present value of the annual cost of the system,CRF is the capitol recovery
factor (the ratio of a constant annual cost to the present value of that cost),CAPEX is the capital
TABLE X. Pumped storage and compressed air energy storage.
Project name Source Date State Country
Power
(MW)
Capacity
(MWh)
CAPEX/
power
($/kW)
CAPEX/
capacity
($/kWh) Notes
Yards Creek
Pumped Storage
DOE #N/A New Jersey United
States
400 2400 38 6 Open-loop
pumped hydro
Blenheim-Gilboa
Pumped Storage
Power Project
DOE 7/1/1973 New York United
States
1160 17400 659 44 Open-loop
pumped hydro
Northfield
Mountain Pumped
Storage
Hydroelectricity
Facility
DOE 12/31/1969 Massachusetts United
States
1119 8482 790 104 Open-loop
pumped hydro
Raccoon
Mountain Pumped
Storage Plant
DOE 1/1/1974 Tennessee United
States
1652 36344 934 42 Open-loop
pumped hydro
Silver Creek
Pumped Storage
Project
DOE 5/15/2012 Pennsylvania United
States
300 2400 1041 130 Closed-loop
pumped hydro
McIntosh
Compressed Air
Energy Storage
Plant
DOE 1/1/1991 Alabama United
States
110 2860 1048 40 Compressed air
energy storage
Pacific Gas and
Electric Company
Advanced
Underground
Compressed Air
Energy Storage
DOE 1/1/2015 California United
States
300 3000 1192 119 Compressed air
energy storage
Bath County
Pumped Storage
Station
DOE 1/12/1985 Virginia United
States
3003 30930.9 1200 117 Open-loop
pumped hydro
Lake Elsinore
Advanced
Pumped Storage
DOE 8/6/2007 California United
States
500 6000 1835 153 Closed-loop
pumped hydro
Ingula Pumped
Storage Scheme
DOE 11/1/2007 Kwa-Zulu Natal South
Africa
1332 21312 2350 147 Open-loop
pumped hydro
open-loop pumped
hydro
061708-17 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)
expenditure,i is the inflation rate,r is the interest rate,N is the system lifetime in years,Cap is
the capacity of the installation,DOD is the depth of discharge,g is the efficiency,Cycles is the
number of cycles the system is rated for, and Years is the number of years the system is rated for.
Equations for LCCP:
LCCP ¼NPVc CRF
Cycles Power=Years ;
where Power is the rated power of the energy storage system.
Butler, P., Grimes, P., Klassen, S., and Miles, R.http://www.sandia.gov/ess/publications/SAND2000-0893.pdf for “Zinc/
Bromine Batteries,” Sandia Report No. SAND2000-0893, 2000.
Divya, K. and Ostergaard, J., “Battery energy storage technology for power systems—An overview,”Electr. Power Syst.
Res.79(4), 511–520 (2009).
Neubauer, J. and Pesaran, A.,http://www.nrel.gov/transportation/energystorage/pdfs/48018.pdf for “PHEV/EV Li-Ion
Battery Second-Use Project,” NREL presentation, 2010.
Schaede, H., Schneider, M., VanderMeer, J., Mueller-Stoffels, M., and Rinderknecht, S., “Development of kinetic energy
storage systems for Island Grids,” in International Renewable Energy Symposium 2015, March (2015).
Schoenung, S., “Energy storage systems cost update,” Sandia Report No. SAND2011-2730 (2011).
Schoenung, S. and Hassanzahl W., “Long- vs. short-term energy storage technologies analysis,” Sandia Report No.
SAND2003-2783 (2003).
St. John, J.,http://www.greentechmedia.com/articles/read/nissan-green-charge-networks-turn-second-life-ev-batteries-into-
grid-storag for “Nissan, green charge networks turn ‘Second-Life’ EV batteries into grid storage business,” Greentech
Media article (2015).
U.S. Bureau of Labor Statistics,https://research.stlouisfed.org/fred2/data/CPIAUCSL.txt for “Consumer price index for all
urban consumers: All Items,” CPIAUCSL; accessed January 2016.
U.S. Department of Energy,http://energy.gov/sites/prod/files/2014/09/f18/Grid%20Energy%20Storage%20December%20
2013.pdf for “Grid Energy Storage,” U.S. Department of Energy Report, December 2013.
U.S. Department of Energy,www.energystorageexchange.org/projects for “Global Energy Storage Database” (retrieved in
2017).
Viswanathan, V., Kintner-Meyer, M., Balducci, P., and Jin, C.,http://energyenvironment.pnnl.gov/pdf/National_
Assessment_Storage_PHASE_II_vol_2_final.pdf for “National Assessment of Energy Storage for Grid Balancing and
Arbitrage Phase II Volume 2: Cost and Performance Characterization,” Pacific Northwest National Laboratory,
PNNL-21388, 2013.
061708-18 VanderMeer, Mueller-Stoffels, and Whitney J. Renewable Sustainable Energy 9, 061708 (2017)