HomeMy WebLinkAboutAlaska_Energy_Statistics_Preliminary_Report_1960-2011_AEA_ISER_Nov_2012Alaska
Energy
Statistics
1960-2011
Preliminary Report
By
Ginny Fay, Alejandra Villalobos Melendez
and Corinna West
Institute of Social and Economic Research
University of Alaska Anchorage
in collaboration with
Alaska Energy Authority
November 2012
iD
40OU ENERGY AUTHORITY
Acknowledgments
We sincerely appreciate the time and effort of numerous electric utilities, AEA program managers and
staff, and many other colleagues who shared information, reviewed this report and provided valuable
feedback.
Suggested citation:
Fay, Ginny, Alejandra Villalobos Melendez, and Corinna West, 2012, Alaska Energy Statistics 1960-2011,
prepared for Alaska Energy Authority, November 2012, 32 pages.
TABLE OF CONTENTS
INTRODUCTION.............................................................................................................................. 4
SUMMARYAND HIGHLIGHTS......................................................................................................... 6
Table 1.a Utilities/Communities Participating in Power Cost Equalization Program, 2011..... 8
Table 1.b Average Consumption per Customer/Month in PCE communities, 2011................ 8
Figure 1. PCE Eligible Communities, 2011................................................................................ 9
Table 1.c Installed Capacity, 2010...........................................................................................
10
Table1.d Net Generation, 2011.............................................................................................
11
Table 1.e Net Generation by Fuel Type, 2011........................................................................
12
Figure 2. Alaska Utilities Net Generation by Fuel Type, 2011................................................
12
Table 1.f Fuel Use for Power Generation, 2011.....................................................................
13
Figure 3. Distribution of Fuel Used by Utilities for Power Generation in Alaska, 2011.........
14
Figure 4. Fuel Oil Used for Electricity Generation by Utilities by Energy Regions, 2011........
14
Table1.g Sales, 2011...............................................................................................................
15
Table1.h Revenue, 2011.........................................................................................................
16
Table 1.i Customers (Accounts), 2011....................................................................................
17
Figure 5. Distribution of Utility Sales, Revenue and Customers by Customer Type, 2011 ....
18
Utility Installed Capacity and Net Generation over time .....................................................
18
Figure 6. Installed Capacity by Prime Mover over Time, 1962-2010......................................
19
Figure 7. Net Generation by Fuel Type over Time, 1971-2011...............................................
19
Appendix A. Glossary of Terms .........................................
Appendix B. Maps of Energy Regions ...............................
Appendix C. Data Sources for Electric Energy Statistics ...
Appendix D. Reporting Requirements ..............................
3
................................................. 20
............................. 27
............................. 29
...................................................... 31
INTRODUCTION
Prior to 1985, the federal Alaska Power Administration published the Alaska Electric Power Statistics.
Then, the Alaska Energy Authority (formerly the Alaska Power Authority) began gathering statistical data
and publishing this annual report. In 1988, the Alaska Electric Power Statistics report became a
combined effort between the Alaska Systems Coordinating Council and the Alaska Energy Authority.
Beginning in 1993, the report became a joint effort between the Alaska Systems Coordinating Council
and the Alaska Department of Community and Regional Affairs, Division of Energy. After the 1995
report, no further reports were published until 2003 when a report was prepared by the Institute of
Social and Economic Research (ISER), University of Alaska Anchorage (UAA), with funding provided by
the Alaska Energy Authority (AEA), the Regulatory Commission of Alaska (RCA), and the Denali
Commission. Beginning in 2008, Alaska Electric Energy Statistics updates have been prepared by ISER in
partnership with AEA.
This report of the twenty-six edition of the Alaska Electric Energy Statistics was prepared by the Institute
of Social and Economic Research in collaboration with the Alaska Energy Authority. Data tables are
presented solely in digital form in a MS Excel workbook file. The workbook containing the data tables
are available on the ISER website at http:lliser.uaa.alaska.edu/PublicationS12012 11-
Alaska EnergyStatisticsCY2011Prelimina Tables.xlsx) and the AEA website
htt www.akener authority.org,l). The data tables are presented in a dataset format for convenient
use and manipulation. All data presented is identified by the geographic regions used historically in
previous Alaska Electric Energy Statistics' as well as AEA energy regions, Native corporation regions and
census areas. Due to delays in data availability, this preliminary report does not include installed
capacity data tables for 2011; however, we expect the final report to include updated installed capacity
information. The data tables available in this preliminary workbook are as follows:
Table
Description
Summary
Tables
By AEA Energy Regions
Table La
Utilities Participating in the Power Cost Equalization program
Table Lb
Installed Capacity (kW), 2010 — Final report will include 2011
Table 1.c
Net Generation (MWh)
Table 1.d
Net Generation by Fuel Type (MWh)
Table Le
Fuel Use for Power Generation (Physical Units, MMBtu)
Table 1.f
Sales (MWh)
Table 1.g
Revenue ($000)
Table 1.h
Customers (Accounts)
Detailed Tables
Installed Capacity
Table 2.1a Installed Capacity by Prime Mover by Plant (kW), 2010 — Final report will include
' The regions are: Arctic Northwest, South Central, South East, South West and Yukon.
2011
Table 2.1b
Installed Capacity by Prime Mover (Percent Distribution) —To be included in final
report
Net Generation and Disposition
Table 2.2a
Net Generation and Total Disposition (MWh)
Table 2.3a
Net Generation by Prime Mover (MWh)
Table 2.3b
Net Generation by Fuel Type and Fuel Use (MWh, Physical Units)
Table 2.3c
Net Generation, Fuel Use, and Fuel Cost by Plant (MWh, Physical Units, Dollars)
Table 2.4a
Utility CO2 Emissions (Metric Tons)
Revenue, Customers and Prices
Table 2.5a
Utility Sales, Revenue, and Customers (MWh, $000, Accounts)
Table 2.5b
Average Annual Energy Use and Rates (kWh/customer, $/customer, $/kWh)
Table 2.5c
Residential Rates and PCE payments ($/kWh)
Electric Utility Historical Tables
Table 3.1
Utility Installed Capacity by Prime Mover (kW) —To be included in final report
Table 3.2
Utility Installed Capacity by Region (kW) —To be included in final report
Table 3.3
Utility Net Generation by Fuel (GWh)
Table 3.4
Utility Net Generation by Region (MWh)
Table 3.5
Utility Sales, Revenue, and Customers (MWh, $000, Accounts)
Table 3.6
Average Annual Energy Use and Rates (kWh/customer, $/customer, cents/kWh)
This accompanying text is meant to provide a brief introduction, highlights and summary tables only.
The summary tables presented in this report use the AEA Energy regions. Maps illustrating these regions
are in Appendix B. We also include a glossary of terms.
Information on utility electricity capacity, generation, and other characteristics was gathered from
reports filed with the U.S. Department of Energy (DOE), Energy Information Administration (EIA).
Though data from these survey forms was not yet available on the EIA website when this preliminary
report was being prepared, the Alaska Energy Authority directly collected copies of the EIA survey forms
860, 861 and 923 from a select number of utilities. After EIA data files become available, a careful cross-
check between preliminary data gathered by AEA and these final published data files will be conducted
and a final report published. Additionally, we used data collected by the Alaska Energy Authority
through the Power Cost Equalization (PCE) program and a limited number of direct contacts with electric
power producers. This methodology allows us to produce this preliminary report with less of a lag time.
All producers of electricity with installed capacity greater than one megawatt are required by law to
report their operations to the federal government. A number of utilities in Alaska fall below that
installed capacity threshold. Information for these smaller utilities came primarily from the PCE
program.
In many parts of Alaska there is no utility -produced electricity available and any activity using electricity
requires self -generation. The number of such small installations (e.g. Point Baker, Port Protection,
Telida) is quite large and it would be a very expensive task to try to identify and contact each one
individually. As a result, this information is incomplete.
It is important to note, that this publication is meant to serve as general reference and broad overview
of electric power in Alaska. Because data comes from a variety of sources and imperfections in the
source data, the reader may find inconsistencies across different tables. For example, Table 2.5b shows
average rate per kilowatt-hour as calculated using the reported revenue, sales and customers; while
Table 2.5c shows average rate per kilowatt hour as reported by the utility to the PCE program; these two
rates are sometimes slightly different.2 Data in different tables may include different cases, or may be
guided by slightly different concept definitions depending on the data source. However, the authors of
this report believe that the data presented provide a reasonable and valuable overview of electric
power and energy across Alaska.
SUMMARY AND HIGHLIGHTS
The purpose of this report is to present electric power reference data for Alaska; it is not intended to
provide detailed analysis of energy production, consumption or uses. Nevertheless, this section
highlights information that may be of particular interest to the reader.
Scope of Report
The Alaska Energy Authority and the Institute of Social and Economic Research at the University of
Alaska Anchorage prepared this report, which primarily presents 2011 data on electricity produced by
utilities in Alaska, including summary and detailed tables showing:
• Installed capacity by (to be published • Net generation:
in final report):
➢
type of utility
➢ type of utility,
➢
prime mover
➢ prime mover
➢
fuel type
➢ plant
• Fuel
• Utility
➢ use
➢
sales
➢ cost
➢
revenue
➢ CO2emissions
➢
customers
average annual electricity use
average annual electricity price
Electricity Generation and Cost
• In 2010, Alaska had approximately 2,202 megawatts of utility installed capacity that generated
about 6.5 million megawatt -hours of electricity.
z Only for PCE communities. Communities for which the data source is EIA report the same calculated rate as in
Table 2.5b.
• In 2011, the statewide portion of electricity generated by natural gas increased from 57% to
58%; the portion of hydroelectric power decreased from 22% in 2010 to 20% in 2011;3
generation from oil products increased from 15%to 16%, while coal remained at 6%.
Generation from wind remained less than 1%, at about 0.3% statewide. The statewide picture
varies sharply by region.
• The Railbelt region is home to most of the state's population, which uses approximately 77% of
the electricity produced statewide. Natural gas is used to generate most of the electricity for the
Railbelt, but the region also has hydroelectric capacity.
• Many (but not all) communities in Southeast Alaska generate electricity with hydroelectric
capacity; some rely on diesel. Most use diesel for back-up generation.
• Rural communities in Western and Interior Alaska rely primarily on diesel to generate electricity,
but wind power is being added in a growing number of rural locations, financed largely by the
Denali Commission and the Alaska Renewable Energy Fund. Since 2008, the annual amount of
electricity generated by wind increased over nine fold to 20,348 MWh in 2010. In 2011, the
electricity generated by wind appears to have stabilized or decreased marginally to about
19,833 MWh.
• Wood was used to generate heat in community -level thermal facilities in about ten
communities, mostly in Southeast where wood resources are abundant.
• The average annual residential use per customer of electricity statewide in 2011 was about
7,770 kilowatt -hours —but that ranged from around 1,500 kilowatt-hours in places where
electricity is most expensive to more than 14,900 where it is cheapest. The national average
annual use per customer in 2010 was about 11,500 kilowatt-hours.4
Residents in communities in Southeast Alaska that rely primarily on hydroelectric power to generate
electricity had the lowest residential rates (as little as about 10 cents per kilowatt-hour in 2011).5
Residents of Anchorage and other places in Southcentral Alaska that rely mostly on natural gas for
generation paid around 13 cents per kilowatt-hour in 2011. Alaskans in small remote rural places that
rely on diesel had the most expensive electricity (from roughly 50 cents to more than $1.50 per kilowatt
hour in 2011). The state helps to lower the price of electricity of residential customers and community
buildings in most of those remote rural communities through the Power Cost Equalization program.
Nonetheless, rural customers continue to pay much higher rates than those in urban communities (see
Table Lb).
3 The amount of electricity produced from hydroelectric resources varies from year to year depending on water
levels. Over the last decade, hydro power does not show a significant positive or negative trend.
° Information regarding 2011 is not yet available; national average (2010) as published by E.I.A.
5 The construction of many of these facilities was paid for with public funds and financing which accounts in part for the lower
rates.
Electric Utilities Summary Tables
Table 1.a Utilities6/Communities Participating in Power Cost Equalization Program, 2011
by AEA Energy Regions
AEA Energy Region
Active
Inactive
Ineligible
Total
Percent Active
Aleutians
12
1
0
13
92%
Bering Straits
16
0
1
17
94%
Bristol Bay
25
1
0
26
96%
Copper River/Chugach
6
0
2
8
75%
Kodiak
4
1
1
6
67%
Lower Yukon-Kuskokwim
47
1
0
48
98%
North Slope
7
0
1
8
88%
Northwest Arctic
12
0
1
13
92%
Railbelt
Southeast
21
0
0
13
7
13
28
0%
75%
Yukon-Koyukuk/Upper Tanana 36 5 1 42 86%
State Total 186 9 27 222 84%
Table 1.b Average Consumption per Customer/Month in PCE communities, 2011
Summer 2011 (April - September)
Effective Rate Min Mean Max
$0.10 - $0.19
136
426
955
$0.20 - $0.29
131
368
886
$0.30 - $0.39
125
310
591
$0.40 - $0.49
101
360
535
$0.50 - $0.59
333
391
540
$0.60 - $0.69
More than $0.70 110 174
Winter 2011 (October - March)
234
Effective Rate
Min
Mean
Max
$0.10 - $0.19
114
506
1,080
$0.20 - $0.29
148
423
754
$0.30 - $0.39
76
377
618
$0.40 - $0.49
115
288
486
$0.50 - $0.59
242
338
420
$0.60 - $0.69
More than $0.70 180 209 258
6 Note: For utilities that serve many communities with no grid such as AVEC and AP&T, each community is counted
as a separate utility.
8
%••I
e•I
N
vi
v
c
E
E
0
U
W
W
U
a
VA
a�
3
iz
fA
C
E
K
O
L
3
0)
Of
m
o
•oU
V�
Y.
L
N
m
CLU
� a
o
•
C
in ®
>
-
-
W
o
p
m
o o
3
O"
A
6
m co
U
®
�
_
N
Q
Y
a
L
o
p
Y
.2
Y
r
c
,
t
a
o
Y
V
�
m
r-
of
e
O
a
W
V
a
c
0
ea
N
ev
3
�
O' a�
W
H E
O
0 o
L U
d �
3�
o
a LU
I
m
Table 1.c Installed Capacity, 20107
by AEA Energy Regions
AEA Energy Region
Total
(kW)
Percent of
Total
Aleutians
34,945
2%
Bering Straits
38,709
2%
Bristol Bay
27,561
1%
Copper River/Chugach
56,255
3%
Kodiak
63,056
3%
Lower Yukon-Kuskokwim
51,102
2%
North Slope
40,600
2%
Northwest Arctic
32,042
1%
Railbelt
1,418,213
64%
Southeast
410,733
19%
Yukon-Koyukuk/Upper Tanana
29,184
1%
State Total
2,202,400
100%
Installed capacity has remained stable without significant growth over the last few years. As of 2010,
there was about 2,200 MW of total installed capacity in the electric sector. The exception is wind
installed capacity which increased almost 50% from 7,884 kW in 2009 to 11,707 kW in 2010. Since 2008,
wind installed capacity increased more than fivefold. However, wind accounts for less than half of one
percent of the total installed capacity in Alaska.
• Railbelt hydroelectric installed capacity was 13% of the Railbelt total in 2010.
• Hydroelectric installed capacity was 20% of the statewide total in 2010.
• Railbelt total installed capacity was 64% of the statewide total in 2010.
Railbelt Hydroelectric: 190MW
Railbelt Total: 1,418 MW
Alaska Hydroelectric: 442 MW
Alaska Total: 2,202 MW
7The Alaska Energy Authority is leading an effort to collect installed capacity information, however, data are not yet
available. Installed capacity information will be updated spring 2013 when the final version of this report is
published.
10
Table 1.d Net Generation, 2011
by AEA Energy Regions
AEA Energy Region
Aleutians
Total
(MWh)
65,340
Percent of
Total
1%
Bering Straits
55,362
1%
Bristol Bay
55,145
1%
Copper River/Chugach
116,700
2%
Kodiak
150,503
2%
Lower Yukon-Kuskokwim
96,625
1%
North Slope
82,544
1%
Northwest Arctic
35,549
1%
Railbelt
5,075,507
77%
Southeast
785,190
12%
Yukon-Koyukuk/Upper Tanana
_
31,175
0%
State Total
6,549,640
100%
Compared to 2010, total net generation increased about 1% in 2011. Electricity generated by wind
remains at less than 1% of the statewide total (about 0.3%); but continues to increase, by about 5% from
20,348 MWh in 2010 to 21,382 MWh in 2011.
• Railbelt hydroelectric generation remained stable at about 8% of the Railbelt
total.
• Hydroelectric generation was 20% of the statewide total, decreasing from 22%
in 2010.
• Railbelt total generation was 77% of the statewide total, decreasing from 78% in
2010.
Railbelt Hydroelectric: 394,831 MWh
Railbelt Total: 5,075,507 MWh
Alaska Hydroelectric: 1,331,640 MWh
Alaska Total: 6,549,640 MWh
11
Table Le Net Generation by Fuel Type, 2011
by AEA Energy Regions
Oil Gas Coal Hydro Wind Total
AEA Energy Region (MWh)
Aleutians 62,960 0 0 2,379 1 65,340
Bering Straits 52,782 0 0 0 2,580 55,362
Bristol Bay 52,213 0 0 2,677 255 55,145
Copper River/Chugach
52,975
0
0
63,725
0
116,700
Kodiak
23,206
0
0
114,852
12,445
150,503
Lower Yukon-Kuskokwim
93,616
0
0
0
3,009
96,625
North Slope
27,313
55,231
0
0
0
82,544
Northwest Arctic
34,006
0
0
0
1,543
35,549
Railbelt
561,271
3,730,696
387,160
394,831
1,549
5,075,507
Southeast
32,014
0
0
753,176
0
785,190
Yukon -Koyukuk/
Upper Tanana
31,175
0
0
0
0
31,175
Total
1,023,531
3,785,927
387,160
1,331,640
21,382
6,549,640
16%
58%
6%
20%
0.3%
100%
Figure 2. Alaska Utilities Net Generation by Fuel Type, 2011
Wind
0.3%
12
Table 1.f Fuel Use for Power Generation, 2011
_ by AEA Energy Regions
Oils Gas Coal
AEA Energy Region (Short
(Barrels) (Mcf) Tons)
Aleutians 103,537 0 0
Bering Straits 85,152 0 0
Bristol Bay 87,430 0 0
Copper River/Chugach
110,405
0
0
Kodiak
42,078
0
0
Lower Yukon-Kuskokwim
171,227
0
0
North Slope
51,495
756,309
0
Northwest Arctic
57,633
_ 0
0
Railbelt
821,105
40,181,450
397,367
Southeast
64,203
0
0
Yukon-Koyukuk/Upper Tanana
55,823
0
0
Total (Physical Units)
1,650,088
40,937,759
397,367
Conversion Factor9(MMBtu)
5.825
1.025
19.536
Total MMBtu 9,611,760 41,961,203 7,762,962
The fossil fuel most used for electricity generation in Alaska is natural gas, though it is only available in
the Railbelt and some communities in the North Slope region. Natural gas accounts for 71% of fossil
fuels consumed by utilities for power generation, about a 1% point increase from 2010. The second
most used fossil fuel for power generation is diesel at about 16% of fuel used in 2011. The Railbelt
region consumes the most fuel oil for power generation in Alaska. With exception of the Golden Valley
Electric Association (GVEA), the utility that provides service in the Fairbanks area, the fuel oil is used for
stand-by generation. However, GVEA depends significantly in both fuel oil and coal for power
generation; about 99% of all the fuel oil used in the Railbelt is consumed by GVEA of which 71% is
naphtha, 24% HAGO and 5% distillate and residual fuel oil.
Compared to 2010, Railbelt consumption of diesel fuel decreased about 8%, but remained at about 53%
of the 2011 statewide fuel used by Alaska utilities. The Lower Yukon-Kuskokwim region remained at 11%
of diesel fuel used of the statewide total; but it decreased fuel used by 5%. Finally, coal makes up 13% of
the fossil fuels used and decreased by about 1% point compared to 2010. Coal is only used in the
Railbelt region, specifically in the Fairbanks area, which has a convenient local supply.
s Utilities in Alaska use a variety of fuel types which include: Distillate Fuel Oil, Jet Fuel, Residual Fuel Oil, Naphtha
and Heavy Atmospheric Gas Oil (HAGO). Each type of fuel has different characteristics and BTU content; all of
these fuels are included here under the label 'Oil'. For detail information, please refer to Table 2.3c Generation,
Fuel Use, Fuel Cost and Efficiency on the accompanying workbook to this publication.
9 Thermal conversion factors can be used to estimate the heat content in British thermal units (BTU) of a given
amount of energy measured in physical units. The conversion factors shown correspond the average amount of
BTUs found in barrels of oil, Mcf of natural gas, and short tons of coal, respectively, as published by the U.S. Energy
Information Administration.
13
In 2011, burning of fossil fuels to generate power produced about 3.5 million metric tons of carbon
dioxide.10 About 64% of utility COz emissions were produced from burning natural gas, 20% from diesel
and 16% from coal.
Figure 3. Distribution of Fuel Used by Utilities for Power Generation in Alaska, 2011
*Distribution based on MMBtu energy equivalent units.
Figure 4. Fuel Oil Used for Electricity Generation by Utilities by Energy Regions, 2011
Railbelt, 50%
Other, 2
� 11
Lower Yukon -
Aleutians, 6%
Kuskokwim, 10% Copper
River/Chugach, 7%
Yukon-
Koyukuk/Upper
Tanana, 3%
10 The amount carbon dioxide emissions associated with fuel consumption by stationary sources, such as a utility,
are lower when consuming natural gas (53.06 Kg CO2 /MMBtu, weighted national average) than when consuming
petroleum distillate fuels (73.15 Kg CO,jMMBtu). To find additional information please refer to the U.S. Energy
Information Administration website at _ ,gov/oiaf/1605/emission_factors.htn .
14
AEA Energy Region
Aleutians
Bering Straits
Bristol Bay
Copper River/Chugach
Kodiak
Lower Yukon-Kuskokwim
Northwest Arctic
Railbelt
Southeast
Yukon-Koyukuk/Upper
Table 1.g Sales, 2011
by AEA Energy Regions
Residential Commercial
8,751 41,762
17,345 22,262
14,975 25,092
24,123 78,817
35,079 22,249
Other ll
Total
Percent of Total
(MWh)
9,670
60,183
1%
13,322
52,929
1%
11,420
51,487
1%
5,213 108,153
86,916 144,244
31,523 36,043 22,423
17,066 58,361 1,492
89,989
76,919
12,657
13,412
8,209
34,278
640,126
2,125,764
1,050,834
4,817,024
328,067
326,603
161,277
815,947
Tanana 11,816 8,130 8,467 28,413 0%
Total 2,141,527 2,758,495 1,379,244 6,279,566
Percent of Total 34% 44% 22% 100%
Electricity sales show an increase of about 1% compared to 2010. Some regions appear to have
significant increases in reported sales. For example, the Aleutians region shows a 14% increase and
Bering Straits about 27%. However, the statewide generation levels remain stable increasing only about
1%.
As expected most of the electricity sales were in the Railbelt region. Nonetheless, the Southeast and
North Slope regions had the highest annual average use per residential customer of about 10,190 kWh
and 7,872 kWh, respectively; followed by the Railbelt region with an annual average use per residential
customer of 7,708 kWh. Unlike other interior regions, the North Slope region consumption is high
because some communities benefit from natural gas and the borough has a low flat rate structure per
kWh for all their communities. The Southeast region benefits from lower rates due to high hydropower
production financed in part with public funds that resulted in lower rates for consumers. The price of
heating oil has continued to increase over the last few years; relatively low electric rates in the
Southeast region have resulted in use of residential electric heating reflected as higher consumption per
11 Other includes sales to community and governmental facilities and industrial customers. Please note that in the
CY2009 publication, industrial customers were included in the commercial category; however starting in the CY
2010 publication industrial customers are included in the 'Other' category.
15
customer. The Yukon-Koyukuk/Upper Tanana and Bristol Bay regions had the lowest annual average
use per residential customer of about 3,922 kWh and 4,842 kWh, respectively.
Overall, slightly less than half, about 44%, of the electricity produced in Alaska was sold to commercial
customers. The North Slope and Railbelt regions had the highest annual average use per commercial
customer of about 71,085 kWh and 70,987 kWh, respectively. The Yukon-Koyukuk/Upper Tanana and
Kodiak regions have the lowest annual average use per commercial customer of about 13,285 kWh and
20,393 kWh, respectively.
Table 1.h Revenue, 2011
by AEA Energy Regions
Residential Commercial Other Total Percent of Total
AEA Energy Region
($000)
Aleutians
3,966
19,594
5,002
28,562 3%
Bering Straits
7,544
8,899
5,993
22,436 2%
Bristol Bay
7,376
12,197
6,106
25,680 3%
f
Copper River/Chugach
7,845
22,458
2,300
32,602 3%
Kodiak 6,949
Lower Yukon-Kuskokwim 17,238
North Slope 1,846
Northwest Arctic 6,444
95 26,547 3%
19,045 12,152 48,435 5%
6,622 218 8,686 1%
6,202 4,639 17,285 2%
Railbelt 271,217 261,745 165,168 698,129 68%
Southeast 41,764 39,753 18,036 99,543 10%
Yukon-Koyukuk/Upper Tanana
6,700
4,690
4,978
16,368 2%
Total
378,889
405,518
239,887
1,024,274
Percent of Total
37%
40%
23%
100%
Compared to 2010, 2011 revenue from electricity sales show an increase of about 11%. Distribution of
revenue across energy regions remained without significant change. The Northwest Arctic region had
the highest average revenue per residential customer per year of about $3,419; followed by the Lower
Yukon Kuskokwim region which averaged about $2,689. The North Slope region had the lowest average
revenue per residential customer per year of about $850; followed by the Railbelt and Southeast regions
which averaged about $1,275 and $1,297, respectively. Overall 40% of the revenue from electricity sales
came from the commercial sector because of their higher use (44% of sales, Table 1f).
16
AEA Energy Region
Aleutians
Bering Straits
Bristol Bay
Copper River/Chugach
Kodiak
Lower Yukon-Kuskokwim
North Slope
Northwest Arctic
Railbelt
Table 1.i Customers (Accounts), 2011
by AEA Energy Regions
Residential Commercial Other
1,560
Total Percent of Total
764 414 2,738 1%
3,372
526
407
4,305
1%
3,093
1,004
543
4,640
1%
4,059
1,495
148
5,702
2%
4,923
1,091
143 6,157 2%
6,410
1,632
879 8,921 3%
2,168
821
42 3,031 1%
1,885
220
246 2,351 1%
212,792 29,946 637 243,375 75%
Southeast
32,196
8,302
808
41,306 13%
Yukon-Koyukuk/Upper Tanana
3,013
612
498
4,123 1%
Total
275,471
46,413
4,765
326,649
Percent of Total
84%
14%
1%
100%
As expected, the regions with the most customer accounts are the Railbelt and Southeast. All other
regions, only account for 13% of total power customers. There were no significant changes in the
number of customer accounts or regional distribution between 2010 and 2011. Residential accounts
made up most of the power customers in Alaska, about 84%. Figure 5 shows in detail the distribution of
utility sales, revenue and customers by customer type.12
12 Industrial sales are included in the 'Other' category. 'Other' includes sales to community and governmental
facilities and others.
17
Figure 5. Distribution of Utility Sales, Revenue and Customers by Customer Type, 2011
100%
90%
80%
70
60% Other
50
■ Commercial
40% ■ Residential
30
20
10%
0%
Sales Revenue Customers
Utility Installed Capacity and Net Generation over time
Installed Capacity
In Alaska, utility installed capacity for power generation increased steadily from the 1970s to the late
1990s, peaking in 2001 at 2,259 MW. From 2002 to 2005 there was a steady decline to about 1,890 MW.
Since 2006, Alaska saw installed capacity growth, almost reaching 2001 levels in 2010 with 2,189 MW.
The prime mover type with the largest share of installed capacity is combustion gas turbines, which
comprised about 36%. Hydroelectric turbines, internal combustion generators and combined cycle gas
turbines had equal shares of 20% each. Finally, steam and wind turbines were the least common prime
movers in Alaska with shares of 3% and 0.5%, respectively.
Net Generation
Since records have been available, net generation in Alaska steadily increased at an average rate of 5%
per year, except in 1998 when there was a significant drop of about 10%. Natural gas is the most
prevalent fuel used for power generation comprising 58% in 2011. Generation from hydroelectric power
is the second most prevalent source of power and increased at about 5% per year. The shares of net
generation from petroleum products and coal remained stable over time, 16% and 6%, respectively, in
2011. Since 2008, wind generation has increased rapidly, though it does not currently represent a
significant share of statewide generation.
18
Figure 6. Installed Capacity by Prime Mover over Time, 1962-2010
2,500
2,000
Y 1,500
500
0 1
N LI'1 00 r1 '�r r\ O M CO M " In w r1 - n O
l0 �D w n rln w w w w m m M O O O -4
r-1 e-1 ri r-1 r-1 r-1 c-1 a-i r-1 e 4 r-1 �4 r-1 N N N N
7000
6000
5000
s
c 4000
0
4.1
3000
C7
a
z
2000
1000
■ Combined Cycle
■ Combustion Gas Turbine
Steam Turbine
Internal Combustion
�r Wind Turbine
Hydro
Figure 7. Net Generation by Fuel Type over Time,1971-2011
Gas
- Oil
Coal
■ Wind
0, Hydro
0 1 -T---r-
1-1 M Ln n M .-1 M In n M r1 M M n M r1 M In r\ M -4
� � � � � 00 00 00 00 0o rn rn rn rn rn o 0 0 0 o r1
rn M rn M rn rn rn rn rn rn M rn rn rn m o o O o O O
1-1 a-i r-1 r-1 -4 -1 r-1 -4 c-1 r-1 r-1 a--1 ci ei ri N N N N N N
19
Appendix A. Glossary of Terms13
Alaska Energy Authority (AEA): A public corporation of the state with a separate and independent legal
existence with the mission to construct, finance, and operate power projects and facilities that utilize
Alaska's natural resources to produce electricity and heat. http://www.akenergyauthority.org/
Auxiliary Generator: A generator at the electric plant site that provides power for the operation of the
electrical generating equipment itself, including related demands such as plant lighting, during periods
when the electric plant is not operating and power is unavailable from the grid. A black start generator
used to start main central station generators is considered to be an auxiliary generator.
Backup (Standby) Generator: A generator that is used only for test purposes, or in the event of an
emergency, such as a shortage of power needed to meet customer load requirements.
Barrel (bbl.): A unit of volume equal to 42 U.S. gallons.
Bituminous coal: A dense coal, usually black, sometimes dark brown, often with well-defined bands of
bright and dull material, used primarily as fuel in steam -electric power generation, with substantial
quantities also used for heat and power applications in manufacturing and to make coke. Bituminous
coal is the most abundant coal in active U.S. mining regions. Its moisture content usually is less than
20%. The heat content of bituminous coal ranges from 21 to 30 million BTU per ton on a moist, mineral -
matter -free basis. The heat content of bituminous coal consumed in the United States averages 24
million BTU per ton, on the as -received basis (i.e. containing both inherent moisture and mineral
matter).
British Thermal Unit: The British thermal unit (BTU or Btu) is a traditional unit of energy equal to about
1.06 kilojoules. It is approximately the amount of energy needed to heat 1 pound (0.454 kg) of waterl
°F (0.556 °C). It is used in the power, steam generation, heating and air conditioning industries. In
North America, the term "BTU" is used to describe the heat value (energy content) of fuels, and also to
describe the power of heating and cooling systems. When used as a unit of power, BTU per hour
(BTU/h) is the correct unit, though this is often abbreviated to just "BTU".
Capital Cost: The cost of field development, plant construction, and the equipment required for industry
operations.
Climate Change: A term used to refer to all forms of climatic inconsistency, but especially to significant
change from one prevailing climatic condition to another. In some cases, "climate change" has been
used synonymously with the term "global warming"; scientists, however, tend to use the term in a wider
sense inclusive of natural changes in climate, including climatic cooling.
Coal: A readily combustible black or brownish -black rock whose composition, including inherent
moisture, consists of more than 50% by weight and more than 70% by volume of carbonaceous material.
It is formed from plant remains that have been compacted, hardened, chemically altered, and
metamorphosed by heat and pressure over geologic time. It is estimated that Alaska holds about 15% of
13 U.S. Energy Information Administration glossary posted at www.eia.doe.gov.' plus multiple sources for additional
Alaska specific terms.
20
the world's coal resources, amounting to 170 billion identified short tons. Major coal provinces include
Northern Alaska, the Nenana area, Cook Inlet — Matanuska Valley, the Alaska Peninsula, and in the Gulf
of Alaska and the Bering River. Alaska coals exhibit low metallic trace elements, good ash -fusion
characteristics, and low nitrogen content making them favorable for meeting environmental constraints
on combustion in power plants.
Cogeneration system: A system using a common energy source to produce both electricity and thermal
energy for other uses, resulting in increased fuel efficiency.
Combined Cycle: An electric generating technology in which electricity is produced from a gas turbine in
combination with a steam turbine that uses otherwise lost heat exiting from the gas (combustion)
turbine. The exiting heat is routed to a conventional boiler or to a heat recovery steam generator for
utilization by a steam turbine in the production of electricity. This process increases the efficiency of the
electric generating unit.
Combustion: Chemical oxidation accompanied by the generation of light and heat.
Commercial Sector: An energy -consuming sector that consists of service -providing facilities and
equipment of businesses; Federal, State, and local governments; and other private and public
organizations, such as religious, social, or fraternal groups. The commercial sector includes institutional
living quarters. It also includes sewage treatment facilities. Common uses of energy associated with this
sector include space heating, water heating, air conditioning, lighting, refrigeration, cooking, and
running a wide variety of other equipment. Note: This sector includes generators that produce
electricity and/or useful thermal output primarily to support the activities of the above -mentioned
commercial establishments.
Consumer (energy): Any individually metered dwelling, building, establishment, or location.
Diesel #1: Also known as DF1 or Jet A. Diesel #1 is commonly used as a transportation and heating fuel
throughout most of northern rural AK. Diesel #1 has a lower gel temperature than Diesel #2 which is
sold as a transportation and heating fuel in warmer climates.
Diesel #2: Is commonly used throughout the US. In Alaska it is used for marine and highway diesel as
well as heating fuel in warmer regions. Diesel #2 is preferred over #1 where it is warm enough as it has
higher energy content and is typically cheaper.
Diesel Fuel: A fuel composed of distillates obtained in petroleum refining operation or blends of such
distillates with residual oil used in motor vehicles. The boiling point and specific gravity are higher for
diesel fuels than for gasoline.
Distillate Fuel Oil: A generic name for a refined petroleum product. It can refer to diesel, heating fuel or
jet fuel.
Electricity: A form of energy characterized by the presence and motion of elementary charged particles
generated by friction, induction, or chemical change.
Energy Balance: The difference between the total incoming and total outgoing energy. When the
energy budget is balanced, the system neither gains nor loses energy.
21
Energy Information Agency (EIA): An independent agency within the U.S. Department of Energy that
develops surveys, collects energy data, and analyzes and models energy issues.
http://www.eia.doe.gov/
Exports: Shipments of goods from within the 50 States and the District of Columbia to U.S. possessions
and territories or to foreign countries.
Fuel: Any material substance that can be consumed to supply heat, power, or mechanical energy.
Included are petroleum, coal, and natural gas (the fossil fuels), and other consumable materials, such as
uranium, biomass, and hydrogen.
Furnished without payment (power): The amount of electricity furnished by the electric utility without
charge, such as a municipality under a franchise agreement or for public street and highway lighting. It
does not include energy consumed by the utility.
Gallon: A volumetric measure equal to four quarts (231 cubic inches) used to measure fuel oil.
Gas: A non -solid, non -liquid combustible energy source that includes natural gas, coke -oven gas, blast -
furnace gas, and refinery gas.
Grid: The layout of an electrical distribution system.
Gross Domestic Disposition: The total amount of energy available for sale in the domestic region, i.e.
energy produced for sale in the domestic region in addition to energy imported for sale within the
domestic region.
Gross Extraction: The total amount of fuel obtained or produced by a power production plant.
Gross Generation: The total amount of electric energy produced by generating units and measured at
the generating terminal in kilowatt-hours (kWh) or megawatt hours (MWh).
Heating Degree Days (HDD): A measure of how cold a location is over a period of time relative to a base
temperature, most commonly specified as 65 degrees Fahrenheit. The measure is computed for each
day by subtracting the average of the day's high and low temperatures from the base temperature (65
degrees), with negative values set equal to zero. Each day's heating degree days are summed to create
a heating degree day measure fora specified reference period. Heating degree days are used in energy
analysis as an indicator of space heating energy requirements or use.
Hydroelectric Power: The use of flowing water to produce electrical energy. Storage hydro, run -of -river
hydro, wave, river in -stream, and tidal power are all forms of hydroelectric power.
Imports: Receipts of goods into the 50 States and the District of Columbia from U.S. possessions and
territories or from foreign countries.
Industrial Sector: An energy -consuming sector that consists of all facilities and equipment used for
producing, processing, or assembling goods. The industrial sector encompasses the following types of
activity: manufacturing, agriculture, timber harvest and wood processing, fishing and fish processing,
22
hunting, mining, oil and gas extraction, and construction. Overall energy use in this sector is largely for
process heat and cooling and powering machinery, with lesser amounts used for facility heating, air
conditioning, and lighting. Fossil fuels are also used as raw material inputs to manufactured products.
Note: This sector includes generators that produce electricity and/or useful thermal output primarily to
support the above -mentioned industrial activities.
Injections: Natural gas injected into storage reservoirs.
Installed Capacity: The maximum theoretical production output of a plant, based either on nameplate
capacity or actual (practically determined) capacity.
Internal Combustion: The process where fuel is burned, or combusted, inside a cylinder or turbine, such
as a diesel or jet engine, producing power directly as opposed to fuel burning externally, such as in a
steam engine. The term internal combustion engine usually refers to an engine in which combustion is
intermittent, such as the more familiar four-stroke and two-stroke piston engines. A second class of
internal combustion engines uses continuous combustion: gas turbines, jet engines and most rocket
engines.
Kilowatt-hour (kWh): A unit of energy equal to one kW applied for one hour; running a one kW hair
dryer for one hour would dissipate one kWh of electrical energy as heat. Also, one kWh is equivalent to
one thousand watt-hours.
Kilowatt (kW): One thousand watts of electricity (See Watt).
Load (Electric): Amount of electricity required to meet customer demand at any given time.
MCF: One thousand cubic feet.
Megawatt (MW): One million watts of electricity (See Watt).
Mining. An energy -consuming subsector of the industrial sector that consists of all facilities and
equipment used to extract energy and mineral resources.
Nameplate Capacity: The maximum rated output of an electric power production unit (i.e. generator,
prime mover) under specific conditions designated by the manufacturer. Capacity is usually indicated on
a nameplate physically attached to the generator.
Natural Gas: Gas in place at the time that a reservoir was converted to use as an underground storage
reservoir in contrast to injected gas volumes.
Net Capacity: The maximum load that an electrical apparatus (i.e. generating unit or station) can carry,
not including use by the electrical apparatus.
Net Domestic Disposition: The total amount of energy produced in the domestic region that is available
for sale within the domestic region, i.e. not including energy use by producers or energy exported for
sale outside of the domestic region.
23
Net Extraction: The total amount of fuel obtained or produced by a power production plant, not
including electric energy use by the plants.
Net Generation: The amount of gross generation not including the electrical energy consumed at the
generating station(s) for station service or auxiliaries. Note: Electricity required for pumping at pumped -
storage plants is regarded as electricity for station service and is deducted from gross generation.
Oil: A mixture of hydrocarbons usually existing in the liquid state in natural underground pools or
reservoirs. Gas is often found in association with oil (See Petroleum).
O&M: Operations and maintenance
Other: The "other" category is defined as representing electricity consumers not elsewhere classified.
This category includes public street and highway lighting service, public authority service to public
authorities, railroad and railway service, and interdepartmental services.
Peak: The amount of electricity required to meet customer demand at its highest. The summer peak
period begins June V and ends September 30th, and the winter peak period begins December 15t and
ends March 315t
Petroleum: A broadly defined class of liquid hydrocarbon mixtures. Included are crude oil, lease
condensate, unfinished oils, refined products obtained from the processing of crude oil, and natural gas
plant liquids. Note: Volumes of finished petroleum products include non -hydrocarbon compounds, such
as additives and detergents, after they have been blended into the products.
Petroleum Products: Petroleum products are obtained from the processing of crude oil (including lease
condensate), natural gas, and other hydrocarbon compounds. Petroleum products include unfinished
oils, liquefied petroleum gases, pentanes plus, aviation gasoline, motor gasoline, naphtha -type jet fuel,
kerosene -type jet fuel, kerosene, distillate fuel oil, residual fuel oil, petrochemical feedstocks, special
naphthas, lubricants, waxes, petroleum coke, asphalt, road oil, still gas, and miscellaneous products
Plant: A term commonly used either as a synonym for an industrial establishment or a generating facility
or to refer to a particular process within an establishment.
Power: The rate of producing, transferring, or using energy that is capable of doing work, most
commonly associated with electricity. Power is measured in watts and often expressed in kilowatts (kW)
or megawatts (MW).
Power Cost Equalization Program (PCE): Participating utilities receive state funding to reduce the charge
to consumers in rural areas where prices can be three to five times higher than prices in urban areas.
Prime Mover: The engine, turbine, water wheel, or similar machine that drives an electric generator; or,
for reporting purposes, a device that converts energy to electricity directly (e.g. photovoltaic solar and
fuel cells).
24
Prime Mover
Prime Mover Description I U.S. EIA]
Code
ST...........
Steam Turbine, including nuclear, geothermal and solar
steam (does not include combined cycle)
GT...........
Combustion (Gas) Turbine (includes jet engine design)
IC...........
Internal Combustion Engine (diesel, piston)
CA...........
Combined Cycle Steam Part
CT...........
Combined Cycle Combustion Turbine Part
CS...........
Combined Cycle Single Shaft (combustion turbine and
steam turbine share a single generator)
CC...........
Combined Cycle - Total Unit
HY...........
Hydraulic Turbine (includes turbines associated with
delivery of water by pipeline)
PS...........
Hydraulic Turbine — Reversible (pumped storage)
BT...........
Turbines used in a binary cycle such as geothermal
PV...........
Photovoltaic
WT...........
Wind Turbine
CE...........
Compressed Air Energy Storage
FC...........
Fuel Cell
OT...........
Other
NA...........
Unknown at this time (use only for plants/generators in
planning stage)
Pro Forma: A Latin term means "for the sake of form," it describes a method of calculating financial
results in order to emphasize either current or projected figures.
Purchased Capacity: The amount of energy and capacity available for purchase from outside the system.
Railbelt: The portion of Alaska that is near the Alaska Railroad, generally including Fairbanks, Anchorage,
the communities between these two cities, and the Kenai Peninsula.
Refinery: An installation that manufactures finished petroleum products from crude oil, unfinished oils,
natural gas liquids, other hydrocarbons, and oxygenates.
Re -injected: The forcing of gas under pressure into an oil reservoir in an attempt to increase recovery.
Renewable Energy Fund (REF): Established by the Alaska State Legislature and administered by the
Alaska Energy Authority to competitively award grants to qualified applicants for renewable energy
projects.
Renewable Energy Resources: Energy resources that are naturally replenishing but flow -limited. They
are virtually inexhaustible in duration but limited in the amount of energy that is available per unit of
time. Renewable energy resources include biomass, hydro, geothermal, solar, wind, ocean thermal,
wave action, and tidal action.
Residential Sector: An energy -consuming sector that consists of living quarters for private households.
Common uses of energy associated with this sector include space heating, water heating, air
25
conditioning, lighting, refrigeration, cooking, and running a variety of other appliances. The residential
sector excludes institutional living quarters.
Residual Fuel Oil: A general classification for the heavier oils that remain after the distillate fuel oils and
lighter hydrocarbons are distilled away in refinery operations. It is used in steam -powered vessels in
government service and inshore power plants, and can be issued for the production of electric power,
space heating, vessel bunkering, and various industrial purposes.
Revenue (Electricity): The total amount of money received by an entity from sales of its products and/or
services; gains from the sales or exchanges of assets, interest, and dividends earned on investments; and
other increases in the owner's equity, except those arising from capital adjustments.
Short Ton: A unit of weight equal to 2,000 pounds.
Space Heating: The use of energy to generate heat for warmth in housing units using space -heating
equipment. It does not include the use of energy to operate appliances (such as lights, televisions, and
refrigerators) that give off heat as a byproduct.
Steam: Water in vapor form; used as the working fluid in steam turbines and some heating systems.
Transmission System (Electric): An interconnected group of electric transmission lines and associated
equipment for moving or transferring electric energy in bulk between points of supply and points at
which it is transformed for delivery over the distribution system lines to consumers, or is delivered to
other electric systems.
Tonne (Ton): A unit of mass equal to 1,000 kilograms or 2,204.6 pounds, also known as a metric ton.
Total Disposition: The total amount of sold or transferred energy.
Turbine: A machine for generating rotary mechanical power from the energy of a moving force (such as
water, hot gas, wind, or steam). Turbines convert the kinetic energy to mechanical energy through the
principles of impulse and reaction, or a mixture of the two.
U.S. Department of Energy (DOE): Oversees programs, such as Wind Powering America, with the
mission to advance national, economic, and energy security; promote innovation; and ensure
environmental responsibility. http://www.energy.gov/
Watt (Electric): The electrical unit of power. The rate of energy transfer equivalent to one ampere of
electric current flowing under a pressure of one volt at unity power factor.
Watt (Thermal): A unit of power in the metric system, expressed in terms of energy per second, equal to
the work done at a rate of one joule per second.
Watt hour (Wh): The electrical energy unit of measure equal to one watt of power supplied to, or taken
from, an electric circuit steadily for one hour.
26
Appendix B. Maps of Energy Regions
Figurel. Alaska Energy Statistics 2003 Regions
Arctic & Northwest
5
Yukon 1
Southeast
Southwest
~ Soulhceniral
Figure 2. Native Corporation Regions
t
ARCTIC SLOPE -�
a• r
e
� CAL ISTA
SEALASKA
BRISTOL, _ ' a CH EACH
BAY I
4 KOHIAG
ALEM
Source: First Alaskans Institute
27
Figure 3. Alaska Census Area Map
Alaska Borough & Census Area Boundaries - 2010
w.asye
• �J
� ltrrs v.
aM
Fe:.e
0
� 6
Mw
C
3 I
FSGxrnS1�J4rrwmN
a :..ty Evnywe i,. F;
n MaN F.:IM
qew
.tber Aa ,
fd}IW4E
Source: 2010 Census, Alaska Department of Labor and Workforce Development
Figure 4. Alaska Energy Regions Map
Alaska Energy Regions
9k�
e
.1a K�
C, , R— ILhqh
0
P
f
9 G
Source: Alaska Energy Authority
28
Appendix C. Data Sources for Electric Energy Statistics
The primary data source for the electric power statistics are the U.S. Department of Energy
(DOE), Energy Information Administration (EIA) and the Alaska Energy Authority, Power Cost
Equalization program data. Every utility and industrial (including military) electrical generating
facility with a capacity greater than one megawatt is required to report their operating
characteristics to the EIA annually, and in some instances, monthly. This information is
compiled by the EIA and is available for every generating facility on their website:
( ;= ii. The forms of interest to compile this publication are the EIA 860,
861 and 923. These are reporting forms for capacity, generation, sales and revenues.
Following the methodology established in 2010, we continue to use the EIA database with some
modifications in order to publish this report more timely. Most utilities and industrial facilities
are required by law to report to the federal government each year on their activities using the
EIA forms; this information is then made available on the EIA website. This process causes a
delay; the lag time for the availability of the federal data is approximately two years. However,
it is redundant to collect the same information through a second questionnaire. Respondents
are required by law to report to the EIA and this should make the response rate high. In order
to expedite this process, the Alaska Energy Authority collected copies of the CY2011 EIA forms
from a selective group of utilities, and created a reduced data set.
Nonetheless, using EIA data poses some challenges because not all information reported in this
publication is collected via the EIA forms. First, the smallest utilities with installed capacity less
than one megawatt are not required to report to EIA and are not included in the EIA database.
Second, not all Alaska generating facilities report as required by law.
These forms collect data at different levels of aggregation; for example some at the utility level
only, while other data may be at the facility and/or generator level. This sometime causes
differences in the underlying definition of the data making reconciliation of the information in
the datasets within forms, and across the different forms sometimes difficult.
To supplement missing data we used the database for the annual Power Cost Equalization
Reports by the Alaska Energy Authority (AEA). Also, as needed, the Alaska Energy Authority and
ISER supplemented these data sources by contacting utilities directly.
These data sources allowed us to collect information for almost all the utilities in the state
without incurring the considerable cost of conducting a complete census of all producers. A
few of the smallest utilities that were not either in the EIA database or the Power Cost
Equalization database did not provide information for this report.
The 2011 Power Cost Equalization data provided data on the generation and sales (residential
and commercial) of all utilities participating in the Power Cost Equalization program, including a
breakdown by community for those utilities that operate in multiple communities, such as
Alaska Village Electric Cooperative (AVEC) and Alaska Power and Telephone (AP&T). The EIA
29
data for these utilities was in some cases reported only as a total across all communities, and
we used this as control totals.
The PCE database contains information collected through AEA's PCE Utility Monthly Report
which PCE participants must file. Utilities also report to the RCA annually for fuel cost
adjustments. Reporting to both entities should be consistent, however discrepancies are not
unusual. These discrepancies may be due to high turnover in small utilities, poor reporting and
limited staff to verify the utilities' self -reported data.
In addition, there are data (energy loss, use by facility and energy provided without charges)
that is not included in the PCE report. Because of this, the values found in table 2.2a may not
reflect a summation of all AP&T communities as reported in the PCE report. Rather they reflect
what was reported to the EIA directly as prepared by the utility itself. This same methodology
was implemented in the sales and revenues tables (2.4a) when deemed appropriate. The
intent is to create as comprehensive of a table as possible.
The summary information in the historical tables was calculated from the same sources
mentioned above. Data from these sources was calculated and re -formatted where appropriate
and consolidated into master data files from which all the tables in this report where built.
Inevitably the use of multiple data sources introduces some inconsistencies in reporting.
Notwithstanding, we believe that the Alaska Electric Power Statistics Preliminary 2011 update
report provides useful information on the state of electric power generation in Alaska.
30
Appendix D. Reporting Requirements
Energy Information Administration
Every utility facility with a capacity greater than one megawatt (MW) is required to report their
operating characteristics to the US Department of Energy (DOE), Energy Information
Administration (EIA) annually, and in some instances, monthly. This information is compiled by
the EIA and is available for every generating facility on their website (httR: www.eia.doe.gov
Specific reporting requirements are determined by the Department of Energy but collected,
assembled, and evaluated by the EIA according to the Federal Energy Administration Act of
1974. We obtained data for year 2011. Three EIA forms were used in this report:
EIA-860 Annual Electric Generator Report. This report contains information on capacity
and types of fuel used. It is completed by all existing plants and proposed (5-year plans)
plants that: 1) have a total generator nameplate capacity (sum for all generators at a
single site) of one MW or greater; and 2) where the plant is connected to the local or
regional electric power grid and has the ability to draw power from the grid or deliver
power to the grid.
EIA -860M Monthly Update to the Annual Electric Generator Report. This report
contains monthly updates to the EIA-860. It is completed by those who also completed
EIA-860 and additionally indicated a proposed change in generator production within
one month of the report period. The proposed change may be due to: 1) a new
generator scheduled to start commercial operation; 2) an existing generator scheduled
to retire from service; or 3) an existing generator with a proposed modification
scheduled.
EIA-861 Annual Electric Power Industry Report. This report contains information on
peak production, net generation, sales, and revenues. It is completed by electric
industry distributors including: electric utilities, wholesale power marketers (registered
with the Federal Energy Regulatory Commission), energy service providers (registered
with the Regulatory Commission of Alaska), and electric power producers.
EIA-923 Power Plant Operations Report. This report contains information on electric
power generation, fuel consumption, fossil fuel stocks, and fossil fuel cost and quality. It
is completed by all electric power plants that: 1) have a total generator nameplate
capacity (sum for generators at a single site) of one MW or greater; and 2) where the
plant is connected to the local or regional electric power grid and has the ability to draw
power from the grid or deliver power to the grid.
31
Power Cost Equalization Program and Regulatory Commission of Alaska
Participants of the Power Cost Equalization (PCE) program report to the Regulatory Commission
of Alaska (RCA) for fuel cost adjustments to their rates. The RCA has authority to maintain
accounts and records of public utilities that fall under its jurisdiction, under Alaska Statute
42.05.451. This responsibility allows the Regulatory Commission of Alaska to obtain
information from regulated utilities. Additionally, all utilities that serve ten or more customers
must obtain an operating certificate, which describes the authorized service area and scope of
operations of the utility. The RCA will issue a certificate when it finds the utility to be fit,
willing, and able to provide the service. The RCA maintains a list of both regulated and.
unregulated certified utilities. Utilities report annually to the RCA, but file a PCE Utility Monthly
Report with AEA.
32